CMC Operation Modes and EHTC
CMC Operation Modes and EHTC
Deepak Singh
FUNCTIONAL LOGIC DESCRIPTION OF CMC
CMC provides stable operation by operating the boiler and turbine in parallel correcting for any
load error by the only ultimate means possible. i.e. by adjusting the firing rate. The turbine
valves are used to balance the boiler and turbine by limiting the transient MW correction
through Throttle Pressure Deviations. Various advantages of CMC in Coordinated Mode can
be listed as below :
1. Enhancement of the unit response during change in unit load demand or change in throttle
pressure set point.
2. Enhancement of the unit performance, i.e., maintenance of critical unit / boiler
parameters within their safe limits.
3. Avoiding tripping of unit on tripping of any of the Unit Auxiliaries, such as ID Fan,
FD Fan, Coal Mill, PA Fan, BFP etc.
4. Increased availability and stability of unit, and thereby increasing the Plant Load Factor.
5. Increased efficiency of unit by maintaining proper combustion.
6. Reduced possibility of Grid failure on frequency change by providing frequency
correction on unit load set point in addition to free governing mode of operation.
7. Increased possibility of saving the unit under the effect of following operations :
a) on Islanding and House Load operation .
b) on tripping of the turbine.
c) on operation of load shedding relay etc.
For the purpose of clarity and lucidity, the control loop has been divided into eight sub-loops :
1. Mode of Operation Logic
2. Load Set Point Generation
3. Load Set Point Ramping
4. Calculation of Directional Releases & Run Up / Run Down Operation
5. Calorific Value Factor Calculation
6. Boiler Master Demand Calculation
7. Unit Capability and Run Back Calculation
8. Load Reference to Turbine Calculation
1. MANUAL MODE :
• both boiler and turbine are independently in operation
• boiler fuel & air feed controlled manually or automatically
• boiler master kept in manual
• turbine may be kept in Initial Pressure mode or in Limit Pressure mode
• No Run Back action in this mode
2. BOILER FOLLOW MODE :
Under the effect of the following binary signals, the system is transferred automatically to Boiler Follow
Mode –
• EHC Fault
• Turbine trip
• Load Shedding Relay operated
• Generator Circuit Breaker open
• Isolated Grid detected
In addition to the above , following features are also available in this mode :
a) RUN BACK ACTION
On tripping of any of the unit auxiliaries, the unit capability of generating full load is
reduced and unit stability is threatened. In order to enhance the stability of unit on
tripping of the auxiliaries, Turbine Run Back Action is initiated and Megawatt
output is reduced up to the capable limit at a predefined rate, so as to maintain
the critical parameters within safe limits, until the tripped equipment or it's standby
is brought back into operation . This is effected in Turbine Follow Mode.
Similarly, on tipping of Turbine / LSR operated / GCB open / Islanding operation,
Boiler Run Back Action is initiated, which in turn results into gradual reduction of
Boiler Load through Fuel & Air Feed until the HP Bypass & / Islanding capability.
This type of Run Back is effected in Boiler Follow Mode.
In this mode of operation, frequent Grid Frequency variations within 50.50 to 49.00
Hz are taken care of by the turbine within a dead band of +/- 0.03 Hz. The
Frequency Ramping rate from 0.02 to 1 .0 Hz. per minute in steps of 0.02 Hz and
MW drooping limit from 5% to 10% in steps of 1% are operator selectable. This
mode of operation well utilizes the boiler’s energy storing capability.
On change in frequency beyond the preset dead band of +0.5 to -1.0 Hz from the set
value of 50 Hz, a suitable correction on unit load set point within specified limits is
applied at the discretion of the operator.
• CMC table:
Throttle MW error
Pressure MW set
CMC Pressure & MW
error point
(Load controller
MW active)
Throttle- pressure
load set
TFM MW (Pressure MW error
point
Pressure error
controller active)
Produces
Throttle- pressure UNIT
RUN steam as BM
(Pressure Capability Pressure error
BACK per unit Bypassed
controller active) Signal
capability
2. LOAD SET POINT GENERATION
The load demand of the unit is decided either by load dispatch center or by manually generated
unit target load by the operator. This signal is limited by maximum and minimum load limits .
Over this limited signal , frequency correction is applied beyond the permitted dead band.
The frequency influence can be switched on / off by the operator in coordinated mode. The
frequency correction through boiler is limited up to a max. safe limit of frequency deviation ,
exceeding which, boiler may get disturbed or tripped . Beyond this limit , turbine frequency
influence is effected to safeguard the turbine from over speeding.
The operation of load set point guidance is dependent upon the availability of directional releases , which are
generated as logic combination of the operating limitations of the following controls in auto-1.
1. Boiler Master Control
2. Fuel Master Control
3. PA Header Pr Control
4. Air Master Control
5. ID Master Control
6. FW Master Control
Operating limitations are provided by the above controls in auto on control deviation or controller output going
beyond pre selected safe operating limits . Under these conditions, the operation of load set point ramping
is blocked in the direction resulting into unsafe operation of the unit or any of the auxiliaries and Run up /
Run down action on load set point is initiated until the unit is brought back into safe operating zone.
Further during run back operation negative directional release is directly made available , enabling the load set
point guidance to unload its output up to Run Back limit.
5. CALORIFIC VALUE FACTOR CALCULATION
In order to take care the effect of changes in calorific value of coal, indirect
calculation of calorific value factor is made from the resultant changes in
Megawatt generation separately. MW generated out off any Furnace Oil flow is
subtracted from the total MW generated in order to find out the MW generated out
off coal only . The ratio of total coal flow and the MW generated out of coal is used
to calculate the calorific value factor with 2nd order delay in order to take care of
the process delay in change of coal quality. The calorific value correction is
applied on the measured total coal flow & thus it is effective in all the modes of
CMC except in Manual Mode , in which case Fuel & Air are controlled manually .
Based on the running status of the following plant auxiliaries, unit capability is calculated :
i) ID FAN
ii) FD FAN
iii) AIR PRE HEATER
iv) BFP
v) CWP
vi) CEP
vii) COAL MILL / COAL FEEDER
viii) PA FAN
On tripping of any of the above auxiliary equipments, the capability of the unit to generate full
load (MW Output) is reduced by an amount equal to the capability of the tripped equipment .
Under such conditions , load must be reduced up to the capable limit of the unit at such a
rate that critical parameters of the boiler remain within safe limit, and stability of the unit is
not disturbed . This action of load reduction on tripping of any of the auxiliary equipments is
called RUN BACK ACTION & is effected in Turbine Follow Mode. Under Manual mode of
operation , no run back action has been envisaged .
Under the effect of Run Back Action, Boiler Follow / Coordinated Mode is automatically
transferred to Turbine Follow Mode , and load is reduced by boiler by reducing firing rate
demand up to the preset capable limit , i.e., Run Back Limit, at a specified gradient, i.e., Run
Back Rate. It may be noted here that for each set of drive there is a particular gradient, by
which the running auxiliaries and unit will be unloaded . How ever for selecting run back
gradient a maximum selection has been deployed so that unit / boiler can be unloaded at a
faster rate determined by the tripped equipment. Minimum output of the individual
capabilities of all the plant auxiliaries forms Unit Running Capability .
8. LOAD REFERENCE TO TURBINE CALCULATION
The unit load set point is delayed suitably matching with the delay caused by Coal
Feeders, Pulverizers and boiler inertia. Turbine load set point thus created is
summed up with pressure correction signal in order to limit the pressure variation
beyond a preset dead band. The purpose of pressure correction on turbine load
set point is to have a check back, how boiler is coping up with the turbine
demand, and to influence later to avoid unnecessary gap. Over this signal, load
deviation signal resulting from Free Governing Operation on Grid Frequency
Change, is added. Before the resultant signal is sent to turbine, it is limited by
max. / min. limits, which are also influenced by TSE Margins. This signal is used
by turbine in Coordinated Mode only for MW generation .
EHC OPERATION :
Control of Steam Input to Turbine through Main Steam Stop & Control Valves
having Hydraulic actuators through –
- Electro Hydraulic Controller providing prime control
- Mechanical Hydraulic Controller serving as back up to EHC by tracking a
signal 5–10% above the EHC output
The EHC consists of the following controllers :
1. Admission Controller (Position Controller),
2. Speed Controller,
3. Load Controller and
4. Pressure Controller.
ADMISSION CONTROLLER :
M M
A I
Load cont. O/P X N M
hr
I
Position
reference
Press Cont. O/P N
SPEED CONTROLLER :
- PD+P control structure
- time dependent speed reference signal,
- gradient is influenced by TSE margins,
- controlling the speed of turbine during :
1. start up and shut down of the turbine ,
2. synchronization of the generator with power grid ,
3. load control after synchronization in lower load range ,
4. load shedding to provide station / house load ,
5. rapid and large frequency fluctuations .
Track
Turbine Nact-120
trip
dN/dT monitoring:
• During rolling of the turbine, if between the speed of 700-2850 rpm dN/dT < 108 rpm/min, then
dN/dT is less than monitoring signal appears to alarm the operator.
• It also blocks any further rise in speed & brings back the speed reference to 600 rpm. It is
introduced to take care of low acceleration rate of turbine at the critical speeds between 700-
2850 rpm.
LOAD CONTROL LOOP
The Load controller is used fro controlling the turbine output during load operation. For
selecting the load controller a push button module ‘Load controller ON/OFF’ is provided. An
indication ‘Load controller in action’ is provided on the turbine control panel.
Function
The Load controller is used to maintain the load set by the operator or AUTOMATIC load
dispatch center. The Load controller comes into action only after synchronization and the
block load is achieved. Before that it remains in follow mode for taking over the control from
Speed controller in a smooth manner.
Max & min. limited cumulative load reference consisting of the following :
• Load gradient of 0-25 MW/min (adjustable from desk)
• time dependent load reference value limited by load gradient and TSE Upper & Lower
Margins (While for TSE margin 0-30oK corresponds to 0-25 MW/min)
• frequency dependent load reference value, which can be switched on / off from
the control desk.
• throttle steam pressure dependent load reference correction value
• Load shedding
• 5 % drooping characteristics, under the effect of high frequency or when the power
plant together with a section of the power grid becomes isolated ( i.e., ISLANDING
operation ) during load control
Load Set Point/ Load reference (Pr)
Generated manually from turbine desk or from CMC
• The follow mode & fast calibration (FM) signal are used for different purposes as
explained below;
(This follow mode is must so that the Prlim is brought back to zero after breaker opens.)
• After synchronization, Prlim tracks the actual load so that more time is not wasted in
bringing the Prlim from zero to working value.
•During this follow mode fast calibration signal is given so that Prlim follows Pact without
any delay.
A pressure influence signal during operation of turbine in ‘LP mode’ is added in Prlim
value whenever there is a press deviation. The correction of 12 MW for the change
of 4 Ksc (linear relation) is implemented in order to prevent drop or rise of MS
pressure.
This correction allows the load controller to manage small pressure changes &
prevents the Pressure Controller coming in to service in LP mode.
Frequency Influence
S
S U
U COM SU
M
M MIN PARA MM
M
M TOR ER
+ E
E R
LOAD PRTD R
DEMAND SUM PR
FROM PR
BOILER
S
P U
LOAD GRADIENT
SETTER M
M
UP E
M
LO I R
N I
M
I
& LOAD CONTROLLER
N
TSE UPPER TSE LOWER OUTPUT
TSE INFLUENCE
ON/OFF
LOAD GRD.
ON/OFF
TSE MARGIN
Load Limiter
Prlim, after frequency correction, is fed to a MIN selector with the Load Limiter.
In Emergency situation Load limiter can be used for fast load reduction. While doing so Pr
should also be reduced, so that during loading load increases as per Prlim & not as per
Load limiter.
Isolated Grid Logics
Isolated Grid is detected provided following conditions are met :-
i) Speed nact.>3036 rpm.
AND ii) Error to load controller > 8.4% for 6 sec.
AND iii) Load controller is ‘ON’
AND iv) Speed controller is not in action.
AND v) Pressure controller is not in action.
It is reset either by GCB ‘OFF’
OR
Error to load controller is less that 8.4% and isolated grid reset command is
issued by the operator.
• During isolated grid condition, the Load Controller is made sluggish by reducing the
input gain from 0.51 to 0.047 and the integral action time is increased by 10 times.
LOAD SHEDDING
In case of sudden loss of export load, the output of the load controller is
immediately reduced below the output of the speed controller which is set at
station load. Due to maximum selection speed controller assumes control
and returns the turbine back to almost the rated speed.
This provision improves the dynamic response of the closing of the steam
control valves and keeps the turbine speed from rising along the droop
characteristics.
Follow Mode of Load Controller:
1. Follow Above:
This mode is in operation during following conditions.
•Generator breaker is OPEN , OR
•Load controller is OFF , OR
•Actual load < block load (21 MW) and LC error >5%
During this follow mode, the load controller output remains below speed controller
output all the time by 150mV. This ensures that as long as above conditions exist, Load
controller does not come into action.
2. Follow Low:
This follow mode appears once the GCB is closed and Speed controller is still in action.
During this mode also the Load controller output tracks the Speed controller output with
error of 150 mV. The only difference in this mode is that the Load controller output can go
more that Speed controller output but it cannot go 150mV below the Speed controller
output. The advantage is that, load controller can be taken in service in any time without
any delay.