1.0 OVERVIEW
The purpose of this document is to explain and describe the implementation of Coordinated Master Control
and Boiler Master Control used in this project.
CJY00_2C21: RATIO Block used as ramp generator to limit the output rate of change
according to the TSE margin available. The Output High/Low limits are determined
according to Unit capability , TSE margin and the Maximum/minimum limit set by the
operator.
CJYOO_2P01: LEADLAG Block to provide a second order delay to Unit Load SP
generated.
CJY00_2N58: NUMERIC Block used to determine throttle pressure deviation. The
deviation of the Boiler master controller is selected and passed on according to the mode
(CMC/Boiler Follow) mode selected.
CJY00_2P02: GENLIN Block used to determine the influence of Throttle Pressure
deviation on generated Unit Load SP.
CJY00_2N51: NUMERIC Block used to pass the bias due to Throttle pressure deviation
when CMC mode is selected.
4CJY00_2C22: SUMMER Block for calculating the Load SP to EHTC after taking into
account the bias due to Throttle pressure deviation.
CJY00_02.CALCULATOR: CALC Block used to determine the Feed forward signal to
Boiler master after taking into account the frequency correction signal.
CJY00_2N52: NUMERIC Block to pass on Frequency correction signal when
Frequency influence is turned ON in EHTC.
CJY00_3P01, P02, P03, P04, P05, CJY00_4P01, P02: CALC Blocks used to determine
unit capability set point by selecting the minimum capability of the auxiliary devices as
the final setpoint.
CJY00_3N51 TO CJY00_3N73 & CJY00_4N51 TO CJY00_4N57: NUMERIC
Blocks used to determine individual equipment capability according to availability of the
equipment. If the equipment is ON then the capability of the equipment is passed on as
the value of the numeric by the corresponding logic otherwise zero is passed on.
CJY00_4N59 TO CJY00_4N68: NUMERIC Block for determining the individual
auxiliary equipment’s runback rate. The rate is kept as zero until the equipment’s
capability is more than the unit SP. Once the equipment’s capability comes below unit SP
a predetermined runback rate is passed on.
3CJY00_04.RUNBACK: HILOAVG Block used as high selector to select the highest of the
available run back rates.
CJY00_3C21: RATIO Block used as ramp generator for determining unit
capability. During runback the output is ramped according to the predetermined
rate of the equipment due to which the runback is initiated.
CJY00_4N69, CJY00_4N70: NUMERIC Blocks used by the operator to set
Maximum/ Minimum Load SP.
CJY00_4P05: CALC Block used to calculate the upper and lower limit of Unit SP ramp
generator.
Protection and Interlock:
The unit master is forced to Manual if any one of the following signals is present
ADS Fault
RUNBACK is in action
RUNUP is not permitted
RUNDOWN is not permitted.
Hand Operated A/M stations for Boiler Master: (Refer dwg. 3CJY00_06)
AutoManual stations located in UCP has the facility to take the controller individually to Manual
mode and manipulate the outputs. This is redundant to the facility available in OWS. This is
achieved using calculator and Logic blocks.
Functional Blocks used:
3CJY00_06.UCP: CALC Block – Increment and decrement command from UCP Auto
Manual stations are taken as inputs and the calculated value is written back to Unit
Master Auto Man Station.
Selection of Transmitters
Cas/Man Selection of controller.
UCP Mounted Operator Interfaces/Devices:
Hand Auto/Manual station for Boiler Master 3-CF-HK-8202.
Window Annunciators (based on customer inputs)
Main Steam Throttle Pressure at Turbine Inlet: (Refer dwg. 3CJY00_01)
Three independent measurements are available. The functional block MIDOF3 calculates the
middle value. The operator has the facility to select between these 4 values (3 transmitters and
Mid value) via GUI.
Functional Blocks used:
3CJY00_01. 3TX_1: HILOAVG block for operator selection.
Control Philosophy
The Set Point is either determined by the operator or depends on Boiler Load Index depending
upon the mode that is selected. If fixed SP mode is selected from MMI the SP is operator
determined. When the same is not selected the SP is determined based upon either Boiler Load
Index or Actual MW. Selection between the two is preset. The Boiler Master can be operated in
two different modes. When the Boiler Follow mode is selected the controller with a Feed Forward
signal based on either Boiler Load Index or EHTC Load Set Point is selected. The selection
between the two-feedforward signals is preset. When Coordinated Mode is selected the controller
with Unit Load SP generated by Coordinated Master as the Feed Forward Signal is selected for
control. When Manual mode is selected or when Run Back in Action the Boiler Master A/M
station trips to Manual mode. When ‘Run Back in Action’ signal is present Turbine Follow mode
Signal is automatically selected and the Unit capability comes down to match the available
capability. This signal is factored (MW to Fuel Ratio) and given as Boiler Master output to the
downstream controller viz., Fuel Master and Air Master signal respectively. This will result in
reduction of Steam Generation to match the available Unit Capacity. The turbine controller
switches to initial pressure mode and starts controlling the Throttle pressure simultaneously. In
order to provide for tracking during manual mode a switch is provided. This switches the Boiler
Master demand to actual Fuel Flow (in terms of Percentage) when Fuel Master controller is not in
Cas mode. With the tracking option ON, the Boiler Master Auto Manual Station Output is made to
track Actual fuel flow (Percentage value) when Fuel Master is in Manual mode. When Fuel Master
switches back to Cas mode a bump is avoided as Boiler Master A/M output was tracking actual
Fuel Flow. Operator can select the various modes of operation (Manual mode, Turbine Follow
mode, Boiler Follow mode and Coordinated Mode) provided the enabling conditions are present
and tripping conditions are not present.
The Auto Man Station is forced to CAS mode when Boiler Follow mode selection condition is
present.
The output of Auto/Man Station is forced to a value proportionate to Unit Capability when
Runback is in Action.
AI - Analog Input
AO - Analog Output
DI - Digital Input LB - Logic Block
DO - Digital Output NM - Numeric
NN - Node Number FL - Flag
MM - Module Number
SS - Slot Number
Abbreviation List:
MID OF 3 -Median value selection
HILOAVG -Selection of average or Operator select
PID -Proportional +Integral +Derivative control
RATIO -Ratio control
AUTOMAN -Auto/Manual station
SUMMER -Summing of inputs
GENLIN -Function Generator
SWITCH -Switching between inputs (S1,S2,S3,S4)
CALC -Calculator
OPLOLM -Output Low Limit
OPHILM -Output High Limit
ESWMAN -Switching externally (through logic block) to Manual mode
ESWCAS –Switching externally (through logic block) to Cascade mode
ESWAUTO -Switching externally (through logic block) to Auto mode
ESWENBST -Enabling Mode change
Tag. XXXX -Refers to the internal parameter of the tag
PVFL -Digital Status