HSC941

GENSET CONTROLLER

USER MANUAL
CONTENTS

1 OVERVIEW .............................................................................................................................................. 6
2 CHARACTERISTICS ................................................................................................................................ 6
3 SPECIFICATION ...................................................................................................................................... 8
4 OPERATION .......................................................................................................................................... 10
4.1 KEYS FUNCTIONS ......................................................................................................................... 10
4.2 CONTROLLER PANEL.................................................................................................................... 11
4.3 AUTO START/STOP OPERATION ................................................................................................. 12
4.3.1 ILLUSTRATION ....................................................................................................................... 12
4.3.2 AUTO START SEQUENCE ....................................................................................................... 12
4.3.3 AUTOMATIC STOP SEQUENCE ............................................................................................. 12
4.4 MANUAL START/STOP OPERATION ........................................................................................... 13
5 GENSET SWITCH CONTROL PROCEDURES ....................................................................................... 14
5.1 HSC941 SWITCH CONTROL PROCEDURE................................................................................... 14
5.1.1 MANUAL CLOSE/OPEN PROCEDURE ................................................................................... 14
5.1.2 AUTO CLOSE/OPEN PROCEDURE ......................................................................................... 14
6 PROTECTIONS ...................................................................................................................................... 15
6.1 WARNINGS .................................................................................................................................... 15
6.2 SHUTDOWN ALARMS ................................................................................................................... 17
7 WIRING CONNECTION ......................................................................................................................... 19
8 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS .................................................. 21
8.1 CONTENTS AND SCOPES OF PARAMETERS SETTING .............................................................. 21
8.2 DEFINABLE CONTENTS OF PROMMABLE OUTPUT PORT ........................................................ 28
8.3 DEFINABLE CONTENTS OF DIGITAL INPUT PORT ..................................................................... 29
8.4 SENSOR SELECTION ..................................................................................................................... 30
8.5 CONDITIONS OF CRANK DISCONNECT SELECTION .................................................................. 31
9 PARAMETER SETTING ......................................................................................................................... 32
9.1 MENU ............................................................................................................................................. 32
9.2 PARAMETER SETTING .................................................................................................................. 32
9.3 CONTROLLER INFORMATION ...................................................................................................... 33
9.4 LANGUAGE SELECTION ................................................................................................................ 33
9.5 DATE/TIME SETTING .................................................................................................................... 33
10 SENSOR SETTING .............................................................................................................................. 34
11 COMMISSIONING ............................................................................................................................... 35
12 TYPICAL APPLICATION ..................................................................................................................... 36
13 CONNECTION OF CONTROLLER AND ENGINE ................................................................................ 37
14 INSTALLATION ................................................................................................................................... 38

HSC941Genset Controller User Manual Page 2 of 40


14.1 FIXING CLIPS ............................................................................................................................... 38
14.2 OVERALL DIMENSIONS AND PANEL CUTOUT ......................................................................... 38
15 TROUNBLESHOOTING ....................................................................................................................... 40

HSC941Genset Controller User Manual Page 3 of 40


Registered trademark
No. 28 Xuemei Street, Zhengzhou, Henan, China
Tel: +86-371-67988888/67981888/67992951
+86-371-67981000(overseas)
Fax: +86-371-67992952
Web: www.smartgen.com.cn/
www.smartgen.cn/
Email: sales@smartgen.cn

All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written permission of
the copyright holder.
SmartGen reserves the right to change the contents of this document without prior notice.

Table 1 Software Version

Date Version Note


2023-10-12 1.0 Original release.
Modify several parameter ranges; modify several Chinese
2023-11-20 1.1
descriptions; add parameter configuration items.

HSC941Genset Controller User Manual Page 4 of 40


Table 2 Notation Clarification

Sign Instruction

Highlights an essential element of a procedure to ensure correctness.


NOTE
Indicates a procedure or practice, which, if not strictly observed, could result in
CAUTION! damage or destruction of equipment.

Indicates a procedure or practice, which could result in injury to personnel or


WARNING! loss of life if not followed correctly.

HSC941Genset Controller User Manual Page 5 of 40


1 OVERVIEW

HSC941 Genset Controller integrates the digital, intelligent and network technology for automation
and monitoring system of single unit, realizes the engine speed adjustment, the genset automatic
start/stop, data measurement, alarm protection and “three remotes” functions. It applies LCD display,
optional interface operation with Chinese and English. It is simple to operate and reliable to run.
HSC941 Genset Controller adopts microprocessor technique to achieve precision measurement of
various parameters, value adjustment, timing and threshold setting, etc. All the parameters can be
configured from front panel, or adjusted and monitored via PC by USB interface or RS485 interface.
Because of the characteristics of compact structure, simple wiring and high reliability, it can be widely
used in all types of genset automatic systems.

2 CHARACTERISTICS

HSC941: used for automation of sigle unit by driving the stepping motor to adjust the throttle
opening and then adjust the speed, to control genset automatic start/stop by remote signal;
Its main characteristics are as follows:
——LCD display with backlight, 132x64 size, simple Chinese and English display, push-button
operation;
——Hard acrylic screen material with great wear-resisting and scratch-resisting performance,
which are used to protect the screen;
——Silicone panel and push buttons, which can better adapt to extreme temperature environment;
——RS485 communication interface, which enables “three remotes” (remote control, remote
measuring, remote communication) functions by MODBUS protocol;
——Suitable for 3P4W, 1P2W, 3P3W, 2P3W power supply 50Hz/60Hz systems;
——Collect and display generation 3-phase voltage, 3-phase current, frequency and power
parameters;
Generator
Line Voltage Uab, Ubc, Uca
Phase Voltage Ua, Ub, Uc
Frequency Hz
Load
Current Ia, Ib, Ic Unit: A
Each phase and total active power P Unit: kW
Reactive Power Q Unit: kvar
Apparent Power S Unit: kVA
Power Factor PF
Accumulated Total Generator Power W Unit: kWh
Output Percentage with Loading %
——With Gen over/under voltage, over/under frequency, over current functions;
——Speed adjustment function (by driving a stepping motor);
——Precise measurement of various parameters of engine:
Speed Unit: r/min
Temp. Unit: °C/°F
Oil Pressure Unit: kPa/psi/bar
Fuel Level Unit: %

HSC941Genset Controller User Manual Page 6 of 40


Battery Voltage Unit: V
Charger D+ Voltage Unit: V
Total Running Time Up to 99999999 hours
Total Start Times Up to 999999 times
——Control Protection: automatic start/stop of genset, open/close and perfect fault display and
protection functions;
——With ETS, idle speed control, preheating control, speed drop/raise control, all of them are relay
outputs;
——Parameter setting: allow users to modify and set parameters, meanwhile they shall be stored
in the internal FLASH and will not be lost even in case of power outage; all of them can be
adjusted from the front panel of the controller and also can be modified on PC via USB or
RS485 interface;
——Two fixed analog sensors (temperature, oil pressure);
——A flexible analog sensor can be set as temperature, pressure or level sensor, or set as Aux.
input 6 and used in different occasions;
——A variety of temperature, pressure, fuel level sensor curves can be used directly, and can be
defined by users;
——Multiple conditions of crank disconnect (gen frequency, speed, oil pressure) are optional;
——Wide power supply range: DC (8~35)V, adapting to different starting battery volts;
——Scheduled start/stop functions (once for monthly/weekly/daily and can be set with or without
load);
——All parameters apply digital adjustment, getting rid of conventional analog modulation of
normal potentiometer, improving the reliability and stability of the whole device;
——Rubber seal designed between the shell and the screen with protection level IP65;
——Metal fixing clips are used to fix the controller;
——Modular structure design, anti-flaming ABS enclosure, pluggable connection terminals, built-in
mounting with compact structure and easy installation.

Table 3 Data Collection

Type Name Symbol Unit


Line Voltage Uab,Ubc,Uca V
Phase Voltage Ua、Ub、Uc V
Generator
Frequency ƒ Hz
Phase Sequence / °
Current Ia、Ib、Ic A
Each Phase and
P kW
Total Active Power
Load Reactive Power Q kvar
Apparent Power S kVA
Power Factor λ(PF) /
Gen Total Power W kWh
Load Output Percentage= (Active Power/Rated Power) ×100%

HSC941Genset Controller User Manual Page 7 of 40


3 SPECIFICATION

Table 4 Performance Parameter

Item Content
Working Voltage DC8V ~ DC35V, continuous power supply
Overall Consumption Standby≤2W, running<8W (stepping motor adjustment)
Phase Voltage
Range: AC15V ~ AC360V (ph-N)
Resolution: 1V
Accuracy: 1%
AC Voltage
Line Voltage
Range: AC30V ~ AC720V (ph- ph)
Resolution: 1V
Accuracy: 1%
Range: 50Hz/60Hz
AC Frequency Resolution: 0.1Hz
Accuracy: 0.1Hz
Rated: 20mA
Range: 0mA ~ 40mA
AC Current
Resolution: 0.1A (One Side Current)
Accuracy: 1%
Voltage Range: 1.0V ~ 24V(RMS)
Speed Sensor
Frequency Range: 100Hz ~ 10000Hz
Range: DC0V ~ DC60V
Charger (D+) Voltage Resolution: 0.1V
Accuracy: 1%
Resistor Input
Range: 0Ω ~ 6000Ω
Analog Sensor
Resolution: 0.1Ω
Accuracy: 1Ω (below 300Ω)
Fuel Relay Output 5A DC28V DC power supply output
Crank Relay Output 5A DC28V DC power supply output
Digital Output 1~4 5A DC28V DC power supply output
Digital Input 1~5 Low threshold voltage 1.2V, max. input voltage 60V
Steady Speed Change Rate <1.5%
Steady Speed Fluctuation Rate <0.5%
Instantaneous Speed Change Sudden decreased load <+10%
Rate Sudden increased load >-15%
Recovery Time <5s
Stepping Motor Specification 2-phase hybrid type, driving current ≤1A
Isolation, max. communication distance is 1000m,
RS485 Interface impedance-120Ω shielding wire is recommended, its single-end
connect with ground.
Vibration 5Hz~8Hz: ±7.5mm

HSC941Genset Controller User Manual Page 8 of 40


Item Content
8Hz~500Hz: a ±2g
IEC 60068-2-6
50g, 11ms, half-sine, three consecutive shocks are applied in each
of the three mutually perpendicular directions, i.e. a total of 18
Shock
times.
IEC 60068-2-27
25g,16ms, half-sine
Bump
IEC 60255-21-2
According to EN 61010-1 installation category (over voltage
Production Compliance
category) III, 300V, pollution class 2, altitude 3000m
Case Dimensions 135 mm x 110 mm x 46mm
Panel Cutout 116.5mm x 91.5mm
Working Temperature (-25~+70)˚C;
Working Humidity (20~95)%RH
Storage Temperature (-25~+70)˚C;
Protection Level IP65
Apply AC2.2kV voltage between high voltage terminal and low
Insulation voltage terminal. The leakage current is not more than 3mA within
1min.
Weight 0.36kg

HSC941Genset Controller User Manual Page 9 of 40


4 OPERATION

4.1 KEYS FUNCTIONS

Table 5 Keys Descriptions

Icon Key Description


Can stop the running genset in Manual/Auto mode;
Can reset the shutdown alarm in genset alarm state;
Stop/Reset Press this key for more than 3s to test panel display and indicators are
normal or not (lamp test) in stop mode;
During stop process, press this key again to stop genset immediately.

Start Press this key to start the genset in Manual or Manual Test mode.

Press this key and the controller goes in Manual mode. Press this key
Manual
and up key (or down key) can adjust the LCD contrast.

Auto Press this key and controller goes in Auto mode.

Close/Open Press this key can control the switch close/open in manual mode.

Press this key to enter the menu setting and can move the cursor and
Set/Confirm
confirm the setttings in parameter setting.
Screen scroll, move up the cursor or increase value in parameter
Up/Increase
setting.
Screen scroll, move down the cursor and decrease value in parameter
Down/Decrease
setting.

HSC941Genset Controller User Manual Page 10 of 40


4.2 CONTROLLER PANEL

Fig.1 HSC941 Front Panel Indication


NOTE: Description for parts of indicators.

Table 6 Alarm Indicator Description

Alarm Type Alarm Indicator


Warning Slow flashing (once per second)
Shutdown Fast flashing (5 times per second)
NOTE 1: Status Indicator: it will not be illuminated in standby state, flashes once for 1s during start or stop
process, always be illuminated in normal running;
NOTE2: Gen normal indication: displays ● when power generation is normal, displays ○ when there is no power
generation.

HSC941Genset Controller User Manual Page 11 of 40


4.3 AUTO START/STOP OPERATION

4.3.1 ILLUSTRATION

Press the key and the indicator beside is illuminated, which means the genset is in Auto Start
Mode.

4.3.2 AUTO START SEQUENCE

a) When remote start input is active, it enters “Start Delay”;


b) LCD displays “Start Delay” countdown;
c) When start delay is over, preheating relay is energized (if configured), “Preheat delay XXs”
information will be displayed on LCD;
d) When preheating delay is over, the fuel relay outputs for 1s, the stepping motor drives the
throttle to rotate the setting starting angle, and then the start relay outputs; if the genset
doesn’t start successfully during the “Start Time”, the fuel relay and start relay will stop
outputting and enters the “Crank Rest Time” to wait for next crank;
e) If the genset does not start successfully in setting attemps, the fifth line of LCD is black and
displays “Start Failure” alarm;
f) If it starts during the attemps, it enters “Safety on time”, the stepping motor drives throttle to
adjust the speed, and during this period, Low Oil Pressure, High Water Temperature, Under
Speed, Charing Failure and Auxiliary Input (configured) alarms are all inactive; after “Safety on
time”, it enters “Start Idle Delay” (if configured);
g) During “Start idle delay”, under speed, under frequency, under voltage alarms are inactive.
When this delay is over, “Warming up delay” is initiated (if configured);
h) When “Warming up delay” is over, if generator status is normal, its indicator will be illuminated.
If generator voltage and frequency have reached on-load requirements, then generator close
relay will be energized, the genset will take load and generator power indicator will be
illuminated, it will enter normal running status; If voltage or frequency is abnormal, the
controller will initiate alarm and shut down (alarm information will be displayed on LCD).
NOTE: When remote start (off load) is applied to start, the procedure is the same as the above, only in h), the
generator close relay is deactivated, and moreover, genset is off load.

4.3.3 AUTOMATIC STOP SEQUENCE

a) When remote start input is inactive, it enters “Stop Delay”;


b) When stop delay is over, “Stop Cooling Delay” is energized and gen close relay is deactivated,
the gen supply indicator is exstinguished;
c) When it enters “Stop Idle Delay” (if configured), the idling speed relay is energized;
d) When it enters “ETS Solenoid Hold” (if configured), ETS relay is energized while fuel relay is
de-energized;
e) When it enters “Wait for Gen-set Stop”, and complete stop is detected automatically;
f) When the generator stops completely, it enters gen standby status; and the controller alarms if
genset cannot stop (the stop failure warning is displayed on LCD).

HSC941Genset Controller User Manual Page 12 of 40


4.4 MANUAL START/STOP OPERATION

a) Press key and controller enters “Manual Mode”, the indicator of manual mode is

illuminated. Then press key to start the genset, it can detect crank disconnect condition
and generator accelerates to high-speed running automatically. If high water temperature, low
oil pressure, abnormal voltage occurs during running, it can protect genset to stop quickly (See
4.3.2 of Auto start Sequence c~h). After the normal running with high-speed, controller will
initiate a gen close signal.

b) Manual Stop: press key to stop the running genset. (See 4.3.3 Auto Stop Sequence b~f).

HSC941Genset Controller User Manual Page 13 of 40


5 GENSET SWITCH CONTROL PROCEDURES

5.1 HSC941 SWITCH CONTROL PROCEDURE

5.1.1 MANUAL CLOSE/OPEN PROCEDURE

When controller in Manual Mode, the switch control procedures will start through manual control
procedure.

If manual close enables, press key, if gen is off load, the gen close will output and when

close delay is over, the indicator of close/open is illuminated; press key, if gen is on-load, the gen
open will output and when open delay is over, the indicator of close/open is exstinguished.
If manual close is disabled, the key of close/open is deactivated.

5.1.2 AUTO CLOSE/OPEN PROCEDURE

When controller is in Auto or Stop Mode, the switch control procedure will perform the automatic
close/open procedure.
When genset is in normal running, gen and frequency reach the on-load conditions, the controller
will excute close/open automatically; the gen off load changes to gen on-load, the gen close will output.
When close delay is over, the indicator of close/open is illuminated; the gen on-load changes to gen off
load, the gen open will output. When open delay is over, the indicator of close/open is extinguished.
NOTE 1: When input port is configured “Gen close status input”, the close/open indicator is consistent only with
the input status of input port. When input port is active, the close/open indicator is illuminated, which means that
the current status is on-load; when input port is inactive, the close/open indicator is extinguished, which means
that the current status is off load.

HSC941Genset Controller User Manual Page 14 of 40


6 PROTECTIONS

6.1 WARNINGS

When controller detects the warning signal, it only issues warning but not shut down.

Table 7 Warning Alarms

No. Type Description


When it dectects that the temperature of input port is high and
1 High Temp. (IN) shutdown is not allowed, the controller will send a warning signal and
displays it on LCD.
When it dectects that the oil pressure of input port is low and
Low Oil Pressure
2 shutdown is not allowed, the controller will send a warning signal and
(IN)
displays it on LCD.
When “ETS Solenoid Hold”/”Wait for Genset Stop Delay” is over, if the
3 Fail to Stop genset does not stop completely, the controller will send a warning
signal and displays it on LCD.
When it detects that the charger voltage of genset is less than the set
4 Charging Failure threshold, the controller will send a warning signal and displays it on
LCD.
When it detects that the battery voltage is less than the set threshold,
5 Battery Under Volt.
the controller will send a warning signal and displays it on LCD.
When it detects that the battery voltage is great than the set threshold,
6 Battery Over Volt.
the controller will send a warning signal and displays it on LCD.
When it detects that the external warning input is active, the controller
7 External Warn Input
will send a warning signal and displays it on LCD.
When it detects that the genset speed is 0 and the loss of speed delay
Loss of Speed
8 is set to 0, the controller will send a warning signal and displays it on
Signal
LCD.
Low Coolant Level When it detects that the low coolant level of input is active, the
9
(IN) controller will send a warning signal and displays it on LCD.
When it detects that the low fuel level of input is active, the controller
10 Low Fuel Level (IN)
will send a warning signal and displays it on LCD.
When it detects that the gen current is greater than the set threshold
11 Gen Over Current and the delay is not 0, the controller will send a warning signal and
displays it on LCD.
When the temperature sensor is open and the act is set as warning,
12 Temp. Sensor Open
the controller will send a warning signal and displays it on LCD.
When the oil pressure sensor is open and the act is set as warning, the
13 OP Sensor Open
controller will send a warning signal and displays it on LCD.
When the flexible sensor is set as temperature, oil presssrue or level
14 Flex. Sensor Open sensor, the sensor is open and the act is set as warning, the controller
will send a warning signal and displays it on LCD.

HSC941Genset Controller User Manual Page 15 of 40


No. Type Description
When the sampling temperature is over than the set high warning
threshold, or greater than the high shutdown threshold and shutdown
15 High Temp.
is not allowed, the controller will send a warning signal and displays it
on LCD.
When the sampling presssure of oil pressure sensor is greater than the
low warning threshold, or sampling pressure is greater than the set low
16 Low Oil Pressure
shutdown threshold and shutdown is not allowed, the controller will
send a warning signal and displays it on LCD.
When the flexible sensor is set as temperature, oil pressure or level
sensor, the sampling value is greater or lower than the warning
17 Flex. Sensor
threshold, the controller will send a warning signal and displays it on
LCD.

HSC941Genset Controller User Manual Page 16 of 40


6.2 SHUTDOWN ALARMS

When controller detects the shutdown alarm, it will open and stop immediately and display the
alarm type.

Table 8 Shutdown Alarms

No. Type Description


Emergency Shutdown When it detects that the input of emergency alarm, the controller
1
Alarm will send an alarm signal and displays it on LCD.
When it detects that the input of high temperature alarm and
High Temp. Shutdown
2 shutdown is allowed, the controller will send an alarm signal and
Alarm (IN)
displays it on LCD.
When it detects that the input of low oil pressure alarm and
Low Oil Pressure
3 shutdown is allowed, the controller will send an alarm signal and
Shutdown Alarm (IN)
displays it on LCD.
Over Speed Shutdown When it detects that the genset speed is over the set threshold, the
4
Alarm controller will send an alarm signal and displays it on LCD.
Under Speed Shutdown When it detects that the genset speed is under the set threshold,
5
Alarm the controller will send an alarm signal and displays it on LCD.
When it detects that the genset speed is 0 and the delay is not 0,
6 Loss of Speed Signal
the controller will send an alarm signal and displays it on LCD.
When it detects that the genset voltage is greater than the set
7 Gen Over Voltage threshold, the controller will send an alarm signal and displays it on
LCD.
When it detects that the genset voltage is less than the set
8 Gen Under Voltage threshold, the controller will send an alarm signal and displays it on
LCD.
Crank Disconnect Within the set start attemps, if the genset crank disconnect fails,
9
Failure the controller will send an alarm and displays it on LCD.
When it detects that the genset frequency is greater than the set
10 Gen Over Frequency threshold, the controller will send an alarm signal and displays it on
LCD.
When it detects that the genset frequency is less than the set
11 Gen Under Frequency threshold, the controller will send an alarm signal and displays it on
LCD.
No Generation When it detects that the genset frequency is 0, the controller will
12
Shutdown Alarm send an alarm signal and displays it on LCD.
When it detects that the input of low fuel level shutdown is active,
13 Low Fuel Level
the controller will send an alarm signal and displays it on LCD.
When it detects that the input of low coolant level is active, the
14 Low Coolant Level (IN)
controller will send an alarm signal and displays it on LCD.
When it detcts that the input of low oil level is active, the controller
15 Low Oil Level (IN)
will send an alarm signal and displays it on LCD.
When the temperature sensor is open and the act of parameter
16 Temp. Sensor Open configuration is set as shutdown, the controller will send an alarm
signal and displays it on LCD.

HSC941Genset Controller User Manual Page 17 of 40


No. Type Description
When the oil pressusure sensor is open and the act of parameter
Oil Pressure Sensor
17 configuration is set as shutdown, the controller will send an alarm
Open
signal and displays it on LCD.
When the Aux. sensor is configured as temperature, oil pressure or
level sensor and opens, the act of parameter configureation is set
18 Aux. Sensor Open
as shutdown, the controller will send an alarm signal and displays it
on LCD.
When sampling temperature is over than the set threshold and
High Temp. Shutdown
19 allowed to shut down, the controller will send an alarm signal and
Alarm
displays it on LCD.
When the sampling oil pressure is less than the set threshold and
Low Oil Pressure
20 allowed to shut down, the controller will send an alarm signal and
Shutdown Alarm
displays it on LCD.
When the Aux. sensor is configured as temperature, oil pressure or
Aux. Sensor Shutdown level sensor, the sampling value is over or less than the shutdown
21
Alarm threshold of Aux. sensor, and allow then Aux. sensor to shut down,
the controller will send an alarm signal and displays it on LCD.

HSC941Genset Controller User Manual Page 18 of 40


7 WIRING CONNECTION

The back panel of HSC941 controller is as follows;

Fig.2- HSC941Controller Back Panel

Table 9 Terminal Connection Description

No. Function Cable Size Remark


1 B- 2.5mm2 Connect with starter battery negative.
Connect with starter battery positive. If wire length
2 B+ 2.5mm2 is over 30m, it’s better to double wires in parallel.
Max. 20A fuse is recommended.
3 Emergency Stop 1.5mm2 Connect with B+ via emergency stop button.
4 Fuel Relay Output 1.0mm2 B+ is supplied by 3 points, rated 5A.
B+ is supplied by 3 points, rated 5A.
5 Crank Relay Output 1.0mm2
Connect to starter coil.
Connect with Charger D+ (WL) terminal. If this
6 Charger (D+) Input 1.0mm2
terminal doesn’t exist, hang it in the air.
7 Flex. Relay Output 1 1.0mm2 B+ is supplied by 2 points, rated 5A.
8 Flex. Relay Output 2 1.0mm2 B+ is supplied by 2 points, rated 5A.
9 Flex. Relay Output 3 1.0mm2 B+ is supplied by 2 points, rated 5A.
10 Flex. Relay Output 4 1.0mm2 B+ is supplied by 2 points, rated 5A.
Used as Aux. sensor (temperature, pressure or level
11 Aux. Sensor Input 1.0mm2
sensors are optional) or digital input port 6.
Used to connect the water/cylinder temperature
12 Temp. Sensor Input 1.0mm2
resistance sensor.

HSC941Genset Controller User Manual Page 19 of 40


No. Function Cable Size Remark
Oil Pressure Sensor
13 1.0mm2 Used to connect oil pressure resistance sensor.
Input
14 COM GND 1.5mm2 Connect with B- internally.
Connect with speed sensor, and shielding line is
15 Speed Sensor Input 1.0mm2
recommended.
Controller inside has been connected to battery
16 Speed Sensor Input 1.0mm2 negative. Connect with speed sensor, and shielding
line is recommended.
17 S11 1.0mm2
Externally connected with stepping motor, S11 and
18 S12 1.0mm2
S12 are one phase, S21 and S22 are the other
19 S21 1.0mm2
phase.
20 S22 1.0mm2
21 Aux. Digi. Input 1 1.0mm2 Ground connected is active (B-).
22 Aux. Digi. Input 2 1.0mm2 Ground connected is active (B-).
23 Aux. Digi. Input 3 1.0mm2 Ground connected is active (B-).
24 Aux. Digi. Input 4 1.0mm2 Ground connected is active (B-).
25 Aux. Digi. Input 5 1.0mm2 Ground connected is active (B-).
26 Input Port COM 1.0mm2 Connect with B- externally.
27 RS485- 0.5mm2
Impedance-120Ω shielding wire is recommended,
28 RS485+ 0.5mm2
and the single-end shall be earth connected.
29 RS485 COM GND /
Generator U-phase Connect to U-phase of generator (2A fuse is
30 1.0mm2
Voltage Input recommended).
Generator V-phase Connect to V-phase of generator (2A fuse is
31 1.0mm2
Voltage Input recommended).
Generator W-phase Connect to W-phase of generator (2A fuse is
32 1.0mm2
Voltage Input recommended).
Connect to N-Wire of generator (2A fuse is
33 Generator N-Wire Input 1.0mm2
recommended).
1.0mm2 Externally connect to secondary coil of current
34 CT A-phase Input
transformer (rated 20mA).
1.0mm2 Externally connect to secondary coil of current
35 CT B-phase Input
transformer (rated 20mA).
1.0mm2 Externally connect to secondary coil of current
36 CT C-phase Input
transformer (rated 20mA).
1.0mm2 Common grounded, connect to starter battery
37 CT COM
negative.
NOTE 1: USB ports on the back panel are configurable parameter ports, and users can directly program the
controller on PC.
Cable requirements: Power supply B+, B-, emergency input, 2.5mm2;
AC current input, 1.0mm2;
Digital input, analog input, D+, AC voltage sampling input, 1.0mm2;
Output ports are based on the current of relay output, 10-16A(2.5mm2, 5-10A(1.5mm2),
below 5A(1.0mm2), RS485 using 0.5mm2.

HSC941Genset Controller User Manual Page 20 of 40


8 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS

8.1 CONTENTS AND SCOPES OF PARAMETERS SETTING

Table 10 Contents and Scopes of Parameters Setting

No. Items Parameters Defaults Description


Time from active remote start signal
1 Start Delay (0-3600)s 1
to unit start.
Time from inactive start signal to unit
2 Stop Delay (0-3600)s 1
stop.
When engine start fails, the max. start
attemps. When reaches to the set
3 Start Attemps (1-10)times 3
start attemps, the controller will send
a start failure signal.
Time for pre-powering the heat plug
4 Pre-heating Time (0-300)s 0
before starter is powered up.
5 Chock On Time (0-300)s 0 Time for chock is powered on.
Time for starter is powered on each
6 Cranking Time (3-60)s 8
time.
The waiting time before the second
7 Crank Rest Time (3-60)s 10
power up when engine start fails.
Alarms for low oil pressure, high water
temperature, under speed, under
8 Safety On (1-60)s 10
frequency, under voltage, charing
failure are inactive.
Running time for genset idling speed
9 Start Idle Time (0-3600)s 0
when the genset is starting.
Warming up time between generator
10 Warming Up Time (0-3600)s 10
switch on and high speed running.
Cooling time before genset stops,
11 Cooling Time (3-3600)s 10
after it unloads.
Running time for genset idling speed
12 Stop Idle Time (0-3600)s 0
when the genset stops.
Time for the stop electromagnet
13 ETS Solenoid Hold (0-120)s 20
energization as the genset is stopping.
Time after “idle delay” is over before
the complete stop when “ETS Solenoid
Hold” is set “0”; time after “ETS
14 After Stop Time (0-120)s 0
Solenoid Hold” delay is over before the
complete stop when it is set other
than “0”.
The width of gen close pulse, which
15 Switch On Dealy (0-10)s 5.0
means continuous output when it is 0.

HSC941Genset Controller User Manual Page 21 of 40


No. Items Parameters Defaults Description
Teeth number of the engine, for
judging of starter separation
16 Engine Flywheel Teeth (1-300) 118 conditions and inspecting of engine
speed. See the installation
instructions.
17 Generator Poles (2-32) 4
The alarm delay for high/low Gen
18 Gen Abnormal Delay (0-20.0)s 10.0
voltage.
When the Gen voltage is higher than
this value and the set “Gen Abnormal
Delay” continues, it is considered as
Gen Over Volt.
19 (30-620)V 264 high Gen voltage and sends a Gen
Threshold (Shutdown)
abnormal shutdown alarm. When set
to 620V, the high voltage signal is not
detected.
When the sampling voltage is lower
than this value and the set “Gen
Gen Under Volt. Abnormal Delay” continues, it is
20 Threshold (30-620)V 88 considered as low Gen voltage and
(Shutdown) sends a sginal of Gen abnormal
shutdown alarm. When set to 30V, the
low voltage signal is not detected.
When engine speed is lower than this
value and lasts for 10s, it is
Under Speed Threshold
21 (0-6000)r/min 1000 considered as under speed and send a
(Shutdown)
signal of under speed shutdown
alarm.
When engine speed is over than this
Over Speed Threshold value and lasts for 2s, it is considered
22 (0-6000)r/min 4200
(Shudown) as over speed and send a signal of
over speed shutdown alarm.
When generator frequency is less than
this value (not 0) and lasts for 10s, it is
Gen Under Frequency
23 (0-75.0)Hz 45.0 considered as under frequency and
Threshold (Shutdown)
send a signal of under frequency
shutdown alarm.
When generator frequency is over than
this value and lasts for 2s, it is
Gen Over Frequency
24 (0-75.0)Hz 68.0 considered as over frequency and
Threshold (Shutdown)
send a signal of over frequency
shutdown alarm.
When set the loss of speed signal
Loss of Speed Signal
25 (0-20.0)s 5.0 shutdown delay as 0, it will only warn
Delay
not stop.

HSC941Genset Controller User Manual Page 22 of 40


No. Items Parameters Defaults Description
During the normal running of genset,
Charging Failure when D+(WL) voltage is less than this
26 (0-30)V 6.0
Threshold (Warn) value and lasts for 5s, it will send a
shutdown alarm.
When battery voltage is higher than
Battery Over Volt. this value and lasts for 20s, it will send
27 (12-40)V 33.0
Threshold (Warn) an abnormal signal of battery voltage,
it will only warn not stop.
When battery voltage is less than this
Battery Under Volt. value and lasts for 20s, it will send an
28 (4-30)V 8.0
Threshold (Warn) abnormal signal of battery voltage, it
will only warn not stop.
29 Aux. Output 1 (0-17) 15 Default: Chock on control.
30 Aux. Output 2 (0-17) 2 Default: ETS hold control.
31 Aux. Output 3 (0-17) 3 Default: Idle speed control.
32 Aux. Output 4 (0-17) 5 Default: Gen close.
33 Aux. Input 1 Set (0-16) 1 Default: High temperature alarm input.
34 Aux. Input 1 Active (0-1) 0 Default: Close.
Time from detecting active input to
35 Aux. Input 1 Delay (0-20.0)s 2.0
confirmation.
36 Aux. Input 2 Set (0-16) 2 Default: Low oil pressusre alarm input.
37 Aux. Input 2 Active (0-1) 0 Default: Close.
Time from detecting active input to
38 Aux. Input 2 Delay (0-20.0)s 2.0
confirm.
39 Aux. Input 3 Set (0-16) 10 Default: Remote start input.
40 Aux. Input 3 Active (0-1) 0 Default: Close.
从检测输入口有效到确认的时间。
41 Aux. Input 3 Delay (0-20.0)s 2.0 Time from detecting active input to
confirm.
42 Aux. Input 4 Set (0-16) 11 Default: Low fuel level warning input.
43 Aux. Input 4 Active (0-1) 0 Default: Close.
Time from detecting active input to
44 Aux. Input 4 Delay (0-20.0)s 2.0
confirm.
45 Aux. Input 5 Set (0-15) 3 Default: External warning input.
46 Aux. Input 5 Active (0-1) 0 Default: Close.
Time from detecting active input to
47 Aux. Input 5 Delay (0-20.0)s 2.0
confirm.
0: Stop mode
48 Start Status Select (0-2) 0 1: Manual mode
2: Auto mode.
The communication address of
49 Controller Add. (1-254) 1
controller.
50 Password Set (0-9999) 1234 See Note 6.

HSC941Genset Controller User Manual Page 23 of 40


No. Items Parameters Defaults Description
The conditions for starter separation,
such as speed, Gen frequency and oil
Crank Disconnect
51 (0-3) 1 pressure. The purpose is to separate
Condition Select
the starter motor and the engine as
soon as possible. See Table 14.
When engine speed is over than this
Engine Speed for Crank
52 (0-3000)r/min 360 value, it is considered as crank
Disconnect
disconnect, the starter will separate.
When generator frequency is over than
Generator Frequecny this value during starting process, it is
53 (0.0-30.0)Hz 14.0
for Crank Disconnect considered as crank disconnect and
the starter will separate.
When the engine oil pressure is over
Oil Pressure for Crank than this value during starting process,
54 (0-400)Kpa 200
Disconnect it is considered as crank disconnect
and the starter will separate.
High Temp. Inhibit Default: high temperature shutdown
55 (0-1) 0
Shutdown and see Note 1 for functions.
Low Oil Preesure Default: low oil pressure shutdown
56 (0-1) 0
Shutdown and see Note 2 for functions.
0: 3P4W; 1: 2P3W;
57 Volt. Input (0-3) 0 3: 1P2W; 3: 3P3W.
See Note 3 for functions.
(0-6000) Provide standard for rated speed
58 Rated Speed 1500
r/min adjustment.
(0-6000) Provide standard for idling speed
59 Idling Speed 900
r/min adjustment.
The speed raising rate when idling
60 Idle Slope (0-6000) 10
speed changes to rated speed.
The speed adjusts the gain duiring
61 Idle Gain (1-1000) 150
engine idling running.
The throttle opening before engine
62 Starting Angle (0-90)° 45
starting.
Crank Disconnect The start opening of throttle after
63 (0-90)° 35
Angle crank disconnect.
64 Proportional Gain (1-3000) 1100
65 Integral Gain (1-3000) 20
66 Differential Gain (1-3000) 1
67 Overall Gain (1-1000) 100 The speed adjusted gain during rated
68 Gain Window (1-1000) 1 speed running.
69 Window Gain (1000-3000) 1950
70 Position Gain (0-1000) 0
71 Compensation Gain (0-100) 0
72 Scheduled Start Enable (0-1) 0 Default: Disable.

HSC941Genset Controller User Manual Page 24 of 40


No. Items Parameters Defaults Description
Scheduled Start
73 (0-1) 0 Default: Off load.
On-load
Scheduled Start Cycle
74 (0-2) 0 Default: 0 Monthly.
Set
Scheduled Start Date
75 (1-31) 1 The scheduled start date.
Set
Scheduled Start Weekly
76 (0-6) 0 Default: 0 Sunday
Set
Scheduled Start Hour
77 (0-23) 0 The scheduled start hour.
Set
Scheduled Start Minute
78 (0-59) 0 The scheduled start minute.
Set
Scheduled Start The continuous running time after
79 (0-9999)min 0
Running Time automatic started.
Temperature Sensor
80 (0-12) 8 SGX See Table 13.
Select
81 Pressure Sensor Select (0-12) 8 SGX See Table 13.
0: Aux. input 6 Set
1: Temp. Sensor
Reuse Aux. Sensor
82 (0-3) 0 2: Pressure Sensor
Select
3: Level Sensor
Details see Note 4.
(0-12) 8 Corresponding to the temperature,
83 Aux. Sensor Curve (0-12) 8 pressure, level sensor curve function
(0-7) 3 settings.
Default: when Aux. sensor is higher or
Aux. Sensor Inhibit lower than the setting threshold
84 (0-1) 0
Shutdown (high/low is up to sensor type), it will
stop and alarm.
85 Temp. Sensor Open (0-2) 1 0: Indication;
Oil Pressure Sensor 1: Warn;
86 (0-2) 1
Open 2: Shutdown Alarm
Indication means display “+++” on LCD
87 Aux. Sensor Open (0-2) 1
of corresponding sensor.
When the temperature of external
connected temperature sensor is over
than this value, it will send a high
temperature signal. This value only be
judged when safety delay is over and
High Water Temp.
88 (0-300)℃ 98 only for the external temperature
Shutdown Threshold
sensor of input port. When the setting
value is 300, it will not send a high
temperature signal (only for
temperature sensor, not include the
digital input port.)

HSC941Genset Controller User Manual Page 25 of 40


No. Items Parameters Defaults Description
When the pressure of external
connected pressure sensor is less
than this value, it will start the delay of
low oil pressure. This value only be
Low Oil Pressure
89 (0-1000)kPa 103 judged when safety delay is over.
Shutdown Threshold
When the setting value is 0, it will not
send a signal of low oil pressure (only
for pressure sensor, not include the
digital input port).
(0-300)ºC Corresponding to the shutdown
Aux. Sensor Shutdown
90 (0-1000)kPa 98 threshold setting of temperauture,
Threshold
(0-100)% pressure, level sensor.
When the temperature of external
connected temperature sensor is over
than this value, it will send a high
High Water Temp.
91 (0-300)℃ 95 temperature signal. This value only be
Warn Threshold
judged when safety delay is over, only
for external connected temperature
sensor of input port.
When the pressure of external
connected pressure sensor is less
than this value, it will start the low oil
pressure delay. This value only be
Low Oil Pressure Warn
92 (0-1000)kPa 124 judged when safety delay is over.
Threshold
When the setting value is 0, it will not
send a signal of low oil pressure (only
for pressure sensor, not include the
digial input port).
(0-300)ºC Corresponding to the warning
Aux. Sensor Warn
93 (0-1000)kPa 95 threshold setting of temperature,
Threshold
(0-100)% pressure and level sensor.
94 Aux. Input 6 Set (0-16) 0 Default: Not used.
95 Aux. Input 6 Active (0-1) 0 Default: Closed.
Time from detecting active input port
96 Aux. Input 6 Delay (0-20.0)s 2.0
to confirmation.
(5-6000A)/20 The change for external connected
97 CT Change 50
mA current transformer.
The rated current of generator, used
98 Full-load Current (5-6000) A 100
for calculation of load overcurrent.
When load current is over than the
Over Current setting value, it is considered as over
99 (50-130)% 120
Percentage current. It will not send a warning
alarm if the value is 0.

HSC941Genset Controller User Manual Page 26 of 40


No. Items Parameters Defaults Description
When the generator current is higher
than the shutdown threshold and lasts
100 Over Current Delay (0-3000)s 30
for the delay time, it is considered as
high generator current shutdown.
101 Rated Power (0-6000kW 66 The rated power of unit.
0: Disable 1: Enable;
When it enables, close/open by
102 Manual Close Enable (0-1) 1
manually press the key; while disables,
it will close/open automatically.
Cooling Fan Open
103 (0-255)℃ 60 When an output port is configured as
Temp.
cooling fan output, it will control the
Cooling Fan Close
104 (0-255)℃ 40 open/close of cooling fan.
Temp.
0: Custom temperature sensor;
1: Custom pressure sensor;
2: Custom Aux. sensor;
105 Custom Sensor Curve (0-2) 0 Select the sensor to be set, and then
enter the resistance value of each
point on the curve and corresponding
value. 8 points need to be entered.
NOTE 1: If set the parameter as “High Temp. Inhibit Shutdown”, or set the prommable input port as “High Temp.
Inhibit Input” and it is active, when the temperature is over than the setting value of ““High Temp. Inhibit Shutdown” or
the signal of “High Temp. Alarm Input” is active, the controller will only send a warning signal but not stop the unit.
NOTE 2: If set the parameter as “Low Oil Pressure Inhibit Shutdown”, or set the prommable input port as “Low Oil
Pressure Inhibit Input” and it is active, when the oil pressure is less than the setting value of “Low Oil Pressure Inhibit
Shutdown” or the signal of “Low Oil Pressure Alarm Input” is active, the controller will only send a warning signal but
not stop the unit.
NOTE 3: If set the parameter as 3P3W, the max. threshold value of Gen over voltage shutdown maybe 620V; when
set as others, the max. value only be 360V.
NOTE 4: Reuse input port to select digital input or sensor, and confure it to be one of them and active. For instance,
reuse the input port 6 and configure it as digital input port, the related configurations are active; if configure it as Aux.
sensor, the related options of temperature, pressusre or level sensor are active.
NOTE 5:When setting parameter via PC, the default password (1234) will not be entered without change. If the
password is changed or be firstly written into configuration via PC, the password should be entered into the module.
NOTE 6: After entering into the correct password and before the LCD backlight dimmed, entering into the password
window again, the parameter setting interface may be entered directly by inputting the serial number.

HSC941Genset Controller User Manual Page 27 of 40


8.2 DEFINABLE CONTENTS OF PROMMABLE OUTPUT PORT

Table 11 Definable Contents of Programmable Output Port 1~4

No. Item Description


0 Not Used It will not output when select this item.
It includes all the shutdown alarms and warnings, when there
is only warning alarm input, this alarm will not latch; while
1 Common Alarm
shutdown alarm occurs, this alarm will latch until the alarm
reset.
It is used for the genset with ETS solenoid. Pull-in acts when
2 ETS Solenoid Control stop idle is over, opening acts when the setting “ETS
Solenoid Hold” is over.
It is used for unit with idling speed. Pull-in acts during
starting, opening acts when entering into high-speed
3 Idle Control
warming up. Pull-in acts in stop idle and opening acts in unit
stop.
Closing acts before starting, while opening acts before
4 Preheat Control
starter is powered on.
5 Gen Close When closing time is set to 0, it is continuous closing.
Output when starts, and output for 2s when there is no
6 Excitation Output
generation frequency in high-speed warming up.
7 Gen Open It is without this function when close time is set as 0.
Pull-in acts when entering the high-speed warming up and
8 Speed Up Control the pull-in time is the delay time for high-speed warming up.
It opens when speed up auxiliary input is active.
Pull-in acts when entering stop idle process or ETS solenoid
9 Speed Down Control hold and the pull-in time is the delay time for stop idle. It
opens when speed down auxiliary input is active.
Output when genset is normal running, it opens when speed
10 Genset Running Output
is less than the speed of crank disconnect.
Pull-in acts when fuel level is lower than the set fuel pump
open threshold or low fuel level warning input is active; it
11 Fuel Pump Control
opens when fuel level is higher than the set fuel pump close
threshold and low fuel level warning input is inactive.
Output when entering the high-speed warming up, it opens
12 High-speed Control
after high-speed cooling.
13 System in Auto Mode The controller is operating in automatic mode.
14 Fuel Relay Output It controls fuel relay output.
Output when starts, and output the setting time during safety
15 Choke On Control
running.
Output when water temperature is higher than the cooling fan
open threshold during genset normal running, while it opens
16 Cooling Fan Output
when the water temperature is lower than the cooling fan
close threshold.
17 Reserved

HSC941Genset Controller User Manual Page 28 of 40


8.3 DEFINABLE CONTENTS OF DIGITAL INPUT PORT

Table 12 Definable Contents of Digital Input Port 1~6 (GND (B-)

No. Item Description


0 Not Used

1 When safety running delay is over, if this signal is active, genset


High Temp. Alarm
will alarm and stop immediately.
2 Low Oil Pressure Alarm
3 External Warning If this signal is active, it only warn but not stop.
External Shutdown
4 If this signal is active, the genset will alarm and stop immediately.
Alarm
When this signal is active and genset is in normal running, if high
temperature occurs, the controller will stop after high-speed
5 Cooling Shutdown
cooling; when this signal is inactive, if high temperature occurs,
the controller will stop in high-speed directly.
6 Gen Close Status Connect with auxiliary point on power generation on-load switch.
If this signal is active, the controller uses a speed control
7 60Hz Active
parameter of 60Hz.
High Temp. Shutdown If this signal is active, high temperature shutdown will be inhibited.
8
Inhibit See parameter configuration Table 10 Note 1.
Low Oil Pressure If this signal is active, low oil pressure shutdown will be inhibited.
9
Shutdown Inhibit See parameter configuration Table 10 Note 2.
In auto mode, when input is active, can start genset automatically
10 Remote Start Input and the genset will take load after normal running. When input is
inactive, can stop the genset automatically.
11 Low Fuel Level Warning
Connect with digital input of sensor, the controller will send a
Low Coolant Level
12 warning alarm when input is active.
Warning
Low Fuel Level
13
Shutdown Connect with digital input of sensor, the controller will send a
Low Coolant Level shutdown alarm when input is active.
14
Shutdown
In auto mode, if this signal is active, no matter if there is a remote
start input signal or not, genset will not start; if genset has been
15 Auto Start Inhibit already in normal running, the genst will not execute stop
operation. When this signal is inactive, genset will execute start or
stop operation automatically.
Connect with digital input, the controller will send a shutdown
16 Low Oil Level Alarm
alarm when input is active.

HSC941Genset Controller User Manual Page 29 of 40


8.4 SENSOR SELECTION

Table 13 Sensor Selection

No. Sensor Curve Type Remark


00 None
01 Custom Res Curve
02 VDO
03 SGH
04 SGD
05 CURTIS
Temperature Defined resistance’s range is (0~1)kΩ.
1 06 DATCON
Sensor Factory default is SGX sensor.
07 VOLVO-EC
08 SGX
09 Custom (4-20)mA curve
10 Custom (0-5)V curve
11 Reserved
12 Reserved
00 None
01 Custom Res Curve
02 VDO
03 SGH
04 SGD
05 CURTIS Default as resistance, defined
Oil Pressure
2 06 DATCON resistance’s range is (0~1)kΩ. Factory
Sensor
07 VOLVO-EC default is SGX sensor.
08 SGX
09 Custom (4-20)mA curve
10 Custom (0-5)V curve
11 Reserved
12 Reserved
00 None
01 Custom Res Curve
02 SGH
03 SGD
3 Level Sensor Defined resistance’s range is (0~1)kΩ.
04 Custom (4-20)mA curve
05 Custom (0-5)V curve
06 Reserved
07 Reserved

HSC941Genset Controller User Manual Page 30 of 40


8.5 CONDITIONS OF CRANK DISCONNECT SELECTION

Table 14 Crank Disconnect Conditions

No. Setting Description


0 Speed
1 Speed + Gen Frequency
2 Speed + Oil Pressure
3 Speed + Gen + Oil Pressure
NOTE 1: There are 3 conditions to make starter disconnected with engine, that is, speed, generator frequency and
engine oil pressure, among which the speed is required;
NOTE 2: Speed sensor is the magnetic equipment installed in starter for detecting flywheel teeth;
NOTE 3: When speed is selected, users must ensure that the number of flywheel teeth is the same with setting,
otherwise, “over speed stop” or “under speed stop” may be caused;
NOTE 4: If gen frequency is not selected in crank disconnected setting, the related power will not be collected and
displayed by controller (can be applied to pump units)

HSC941Genset Controller User Manual Page 31 of 40


9 PARAMETER SETTING

9.1 MENU

Press key to enter parameter setting menu after controller starting, the menu items are as
follows:

1 Controller Parameter Setting


2 Controller Information
3 Language
4 Date/Time Setting

9.2 PARAMETER SETTING

Input the correct password (factory default:1234) to set all the items of Table 10. When more items
are needed, such as voltage calibration, please contact with manufacturer.
Notes:
a) Please modify the controller parameters (crank disconnect conditions selection, programmable
input, output port configuration, various delays) in standby mode, otherwise alarm shutdown or
other abnormal conditions may occur.
b) The over voltage threshold value must be greater than the under voltage threshold, otherwise
there will be both over voltage and under voltage.
c) The over speed threshold value must be greater than the under speed threshold, otherwise,
there will be both over speed and under speed.
d) The generator frequency should be set as lower value as possible when crank disconnect, so
that the starter motor can separate as soon as possible.
e) The Aux. input port 1~6 cannot be set as the same item, otherwise, the incorrect function may
occur. While the Aux. output port 1~4 can be set as the same.
f) If the shutdown after the high temperature cooling, please set a selection of “High Temperature
Cooling Shutdown” in any Aux. input port, and it should be grounded.

HSC941Genset Controller User Manual Page 32 of 40


9.3 CONTROLLER INFORMATION

a) The interface can display the development information of controller, such as software version,
hardware version, release date;

b) Press key to display the status of digital input port and output port;

9.4 LANGUAGE SELECTION

Simplified Chinese and English are displayed on this interface.

9.5 DATE/TIME SETTING

Calibrate the date and time of controller by the setting item.


NOTE: Press key at any time can immediately stop the current parameter setting, and return to previous
setting menu.

HSC941Genset Controller User Manual Page 33 of 40


10 SENSOR SETTING

When sensors are reselected, the sensor curves will be transferred into the standard value. For
example, if temperature sensor is SGH (120°C resistor type), its sensor curve is SGH (120°C resistor
type); if select the SGD (120°C resistor type), the temperature sensor curve is SGD curve.
When there is difference between standard sensor curves and used sensor curves, users can
select “custom sensor “and input the custom sensor curve;
When the sensor curve is inputted, x value (resistor) must be inputted from small to large,
otherwise, mistake occurs;
If sensor type is selected as “none”, sensor curve is not working;
If the corresponding sensor has alarm switch only, users must set this sensor as “none”, otherwise,
shutdown or warning may occur;
The headmost or backmost values in the vertical coordinates can be set as the same as below.

Fig. 3 Sensor Curve Diagram

Table 15 Normal Pressure Unit Conversion Form

N/m2
Item kgf/cm2 bar psi
Pa
1Pa 1 1.02x10-5 1x10-5 1.45x10-4
1kgf/cm2 9.8x104 1 0.98 14.2
1bar 1x105 1.02 1 14.5
1psi 6.89x103 7.03x10-2 6.89x10-2 1

HSC941Genset Controller User Manual Page 34 of 40


11 COMMISSIONING

It is recommended to perform the following checks before running the system:


——Ensure that all the wiring connections are correct and the cable diameter is suitable;
——Ensure that the controller DC power has fuse, controller’s positive and negative connected to
starter battery;
——Take proper action to prevent engine to crank disconnect (e.g. remove the connection wire of
fuel valve.) If checking is OK, connect the starter battery and select manual mode, controller
will execute the routine;
——Set controller under manual mode, press “Start” key, genset will start. If start fails after pre-set
start attempts, controller will send signal of start failure, then press “Stop” to reset controller;
——Recover the action of stopping enging start (e.g. connection wire of fuel valve), press start key
again, genset will start. If everything goes well, genset will go to normal running after idle
running (if idle running is set). During this time, please observe engine’s running situations, AC
generator’s voltage and frequency and DC generator voltage. If something abnormal occurs,
stop genset running and check all wires connection according to this manual;
——Select the auto status from front panel, and then connect to remote start signal. The genset
will automatically enter to normal running status and send a Gen close command;
——Disconnect the remote start signal, the genset will enter the stop status automatically, and
send a Gen open command. If not like this, please refer to the manual to check the switch
control wirings;
——If there is any other question, please contact SmartGen’s service.

HSC941Genset Controller User Manual Page 35 of 40


12 TYPICAL APPLICATION

Fig. 4 HSC941Typical Application Diagram

CAUTION: The starting and fuel output ports should be extended with large capacity relays;

CAUTION: The Gen closing output port must be extended with relay externally while using.

HSC941Genset Controller User Manual Page 36 of 40


13 CONNECTION OF CONTROLLER AND ENGINE

Fig. 5 Controller and Engine Connection Diagram

HSC941Genset Controller User Manual Page 37 of 40


14 INSTALLATION

14.1 FIXING CLIPS

——Controller is panel built-in design; it is fixed by clips when installed;


——Withdraw the fixing clip screw (turn anticlockwise) until it reaches proper position;
——Pull the fixing clip backwards (towards the back of the controller) and ensure that the four
clips are inside their allotted slots;
——Turn the fixing clips screws clockwise until they are fixed on the panel;
——Care shoud be taken not to over tighten the screws of fixing clips.

14.2 OVERALL DIMENSIONS AND PANEL CUTOUT

Unit:mm

Fig. 6 Overall and Panel Cutout Dimensions


——Battery Voltage Input:
HSC941 controller can suit for wide range of battery voltage DC(8~35)V. Negative of battery must
be connected with the engine shell. Diameter of wire that connects from power supply B+ and B- to
battery positive and negative must be over 2.5mm2. If floating charger is configured, please firstly
connect output wires of charger to battery’s positive and negative directly, then, connect wires
from battery’s positive and negative to controller’s positive and negative input terminals in order to
prevent charger disturbing the controller’s normal working.
——Speed Sensor Input:
Speed sensor is the magnetic equipment installed in engine body to detect flywheel teeth. Its
connection wires to controller should apply 2-core shielding line. The shielding layer should
connect to No. 14 terminal in controller while another side is hanging in air. The other two signal
wires are connected to No.15 and No.16 terminals of controller. The output voltage of speed
sensor should be within AC(1~24)V (RMS) at full speed. AC12V is recommended (at rated speed).
When installs the speed sensor, let the sensor spun to contacting flywheel first, then, port out 1/3
lap, and lock the nuts of sensor at last.
——Output and Expand Relays:
All outputs of controller are relay contact output type. If it needs to expand the relays, please add
freewheel diode to both ends of expand relay’s coils (when coils of relay have DC current) or,
increase resistance-capacitance return circuit (when coils of relay have AC current), in order to
prevent disturbance to controller or other equipment.

HSC941Genset Controller User Manual Page 38 of 40


——AC Input:
Current input of HSC941 controller must be connected to outside current transformer. And the
current transformer’s secondary side current must be 20mA. At the same time, the phases of
current transformer and input voltage must be correct. Otherwise, the collected current and active
power may not be correct
——Withstand Voltage Test:
When controller has been installed in control panel, if it needs voltage withstand test, please
disconnect controller’s all terminal connections, in order to prevent high voltage entering controller
and damaging it.
NOTE 1: ICOM terminal must be connected to battery negative;
NOTE 2: When there is load current, transformer’ secondary side is prohibited to open circuit.

HSC941Genset Controller User Manual Page 39 of 40


15 TROUNBLESHOOTING

Table 16 Troubleshooting

Symptoms Possible Solutions


Check starting batteries;
Controller no response with
Check controller connection wirings;
power
Check DC fuse.
Check the water/cylinder temperature is too high or not;
Genset shutdown Check the genset AC voltage;
Check DC fuse.
Low oil pressure alarm after
Check the oil pressure sensor and its connections.
crank disconnect
High water temp. alarm after
Check the temperature sensor and its connections.
crank disconnect
Check related switch and its connections according to the
Shutdown alarm in running information on LCD;
Check programmable inputs.
Check fuel circuit and its connections;
Check starting batteries;
Crank not disconnect
Check speed sensor and its connections;
Refer to engine manual.
Check starter connections;
Starter no response
Check starting batteries.
Cross the stepping motor S11 and S12;
Stepping motor reverses Or cross the stepping motor S21 and S22;
Or change the configuration by PC (motor reduction direction)
Check the voltage of magnetic sensor cannot be lower than 2V when
starting;
Loss of speed control
Check whether S11, S12, S21 and S22 of stepping motor are in good
contact.

_________________________________

HSC941Genset Controller User Manual Page 40 of 40