HSC941 en
HSC941 en
HSC941 en
GENSET CONTROLLER
USER MANUAL
CONTENTS
1 OVERVIEW .............................................................................................................................................. 6
2 CHARACTERISTICS ................................................................................................................................ 6
3 SPECIFICATION ...................................................................................................................................... 8
4 OPERATION .......................................................................................................................................... 10
4.1 KEYS FUNCTIONS ......................................................................................................................... 10
4.2 CONTROLLER PANEL.................................................................................................................... 11
4.3 AUTO START/STOP OPERATION ................................................................................................. 12
4.3.1 ILLUSTRATION ....................................................................................................................... 12
4.3.2 AUTO START SEQUENCE ....................................................................................................... 12
4.3.3 AUTOMATIC STOP SEQUENCE ............................................................................................. 12
4.4 MANUAL START/STOP OPERATION ........................................................................................... 13
5 GENSET SWITCH CONTROL PROCEDURES ....................................................................................... 14
5.1 HSC941 SWITCH CONTROL PROCEDURE................................................................................... 14
5.1.1 MANUAL CLOSE/OPEN PROCEDURE ................................................................................... 14
5.1.2 AUTO CLOSE/OPEN PROCEDURE ......................................................................................... 14
6 PROTECTIONS ...................................................................................................................................... 15
6.1 WARNINGS .................................................................................................................................... 15
6.2 SHUTDOWN ALARMS ................................................................................................................... 17
7 WIRING CONNECTION ......................................................................................................................... 19
8 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS .................................................. 21
8.1 CONTENTS AND SCOPES OF PARAMETERS SETTING .............................................................. 21
8.2 DEFINABLE CONTENTS OF PROMMABLE OUTPUT PORT ........................................................ 28
8.3 DEFINABLE CONTENTS OF DIGITAL INPUT PORT ..................................................................... 29
8.4 SENSOR SELECTION ..................................................................................................................... 30
8.5 CONDITIONS OF CRANK DISCONNECT SELECTION .................................................................. 31
9 PARAMETER SETTING ......................................................................................................................... 32
9.1 MENU ............................................................................................................................................. 32
9.2 PARAMETER SETTING .................................................................................................................. 32
9.3 CONTROLLER INFORMATION ...................................................................................................... 33
9.4 LANGUAGE SELECTION ................................................................................................................ 33
9.5 DATE/TIME SETTING .................................................................................................................... 33
10 SENSOR SETTING .............................................................................................................................. 34
11 COMMISSIONING ............................................................................................................................... 35
12 TYPICAL APPLICATION ..................................................................................................................... 36
13 CONNECTION OF CONTROLLER AND ENGINE ................................................................................ 37
14 INSTALLATION ................................................................................................................................... 38
All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written permission of
the copyright holder.
SmartGen reserves the right to change the contents of this document without prior notice.
Sign Instruction
HSC941 Genset Controller integrates the digital, intelligent and network technology for automation
and monitoring system of single unit, realizes the engine speed adjustment, the genset automatic
start/stop, data measurement, alarm protection and “three remotes” functions. It applies LCD display,
optional interface operation with Chinese and English. It is simple to operate and reliable to run.
HSC941 Genset Controller adopts microprocessor technique to achieve precision measurement of
various parameters, value adjustment, timing and threshold setting, etc. All the parameters can be
configured from front panel, or adjusted and monitored via PC by USB interface or RS485 interface.
Because of the characteristics of compact structure, simple wiring and high reliability, it can be widely
used in all types of genset automatic systems.
2 CHARACTERISTICS
HSC941: used for automation of sigle unit by driving the stepping motor to adjust the throttle
opening and then adjust the speed, to control genset automatic start/stop by remote signal;
Its main characteristics are as follows:
——LCD display with backlight, 132x64 size, simple Chinese and English display, push-button
operation;
——Hard acrylic screen material with great wear-resisting and scratch-resisting performance,
which are used to protect the screen;
——Silicone panel and push buttons, which can better adapt to extreme temperature environment;
——RS485 communication interface, which enables “three remotes” (remote control, remote
measuring, remote communication) functions by MODBUS protocol;
——Suitable for 3P4W, 1P2W, 3P3W, 2P3W power supply 50Hz/60Hz systems;
——Collect and display generation 3-phase voltage, 3-phase current, frequency and power
parameters;
Generator
Line Voltage Uab, Ubc, Uca
Phase Voltage Ua, Ub, Uc
Frequency Hz
Load
Current Ia, Ib, Ic Unit: A
Each phase and total active power P Unit: kW
Reactive Power Q Unit: kvar
Apparent Power S Unit: kVA
Power Factor PF
Accumulated Total Generator Power W Unit: kWh
Output Percentage with Loading %
——With Gen over/under voltage, over/under frequency, over current functions;
——Speed adjustment function (by driving a stepping motor);
——Precise measurement of various parameters of engine:
Speed Unit: r/min
Temp. Unit: °C/°F
Oil Pressure Unit: kPa/psi/bar
Fuel Level Unit: %
Item Content
Working Voltage DC8V ~ DC35V, continuous power supply
Overall Consumption Standby≤2W, running<8W (stepping motor adjustment)
Phase Voltage
Range: AC15V ~ AC360V (ph-N)
Resolution: 1V
Accuracy: 1%
AC Voltage
Line Voltage
Range: AC30V ~ AC720V (ph- ph)
Resolution: 1V
Accuracy: 1%
Range: 50Hz/60Hz
AC Frequency Resolution: 0.1Hz
Accuracy: 0.1Hz
Rated: 20mA
Range: 0mA ~ 40mA
AC Current
Resolution: 0.1A (One Side Current)
Accuracy: 1%
Voltage Range: 1.0V ~ 24V(RMS)
Speed Sensor
Frequency Range: 100Hz ~ 10000Hz
Range: DC0V ~ DC60V
Charger (D+) Voltage Resolution: 0.1V
Accuracy: 1%
Resistor Input
Range: 0Ω ~ 6000Ω
Analog Sensor
Resolution: 0.1Ω
Accuracy: 1Ω (below 300Ω)
Fuel Relay Output 5A DC28V DC power supply output
Crank Relay Output 5A DC28V DC power supply output
Digital Output 1~4 5A DC28V DC power supply output
Digital Input 1~5 Low threshold voltage 1.2V, max. input voltage 60V
Steady Speed Change Rate <1.5%
Steady Speed Fluctuation Rate <0.5%
Instantaneous Speed Change Sudden decreased load <+10%
Rate Sudden increased load >-15%
Recovery Time <5s
Stepping Motor Specification 2-phase hybrid type, driving current ≤1A
Isolation, max. communication distance is 1000m,
RS485 Interface impedance-120Ω shielding wire is recommended, its single-end
connect with ground.
Vibration 5Hz~8Hz: ±7.5mm
Start Press this key to start the genset in Manual or Manual Test mode.
Press this key and the controller goes in Manual mode. Press this key
Manual
and up key (or down key) can adjust the LCD contrast.
Close/Open Press this key can control the switch close/open in manual mode.
Press this key to enter the menu setting and can move the cursor and
Set/Confirm
confirm the setttings in parameter setting.
Screen scroll, move up the cursor or increase value in parameter
Up/Increase
setting.
Screen scroll, move down the cursor and decrease value in parameter
Down/Decrease
setting.
4.3.1 ILLUSTRATION
Press the key and the indicator beside is illuminated, which means the genset is in Auto Start
Mode.
a) Press key and controller enters “Manual Mode”, the indicator of manual mode is
illuminated. Then press key to start the genset, it can detect crank disconnect condition
and generator accelerates to high-speed running automatically. If high water temperature, low
oil pressure, abnormal voltage occurs during running, it can protect genset to stop quickly (See
4.3.2 of Auto start Sequence c~h). After the normal running with high-speed, controller will
initiate a gen close signal.
b) Manual Stop: press key to stop the running genset. (See 4.3.3 Auto Stop Sequence b~f).
When controller in Manual Mode, the switch control procedures will start through manual control
procedure.
If manual close enables, press key, if gen is off load, the gen close will output and when
close delay is over, the indicator of close/open is illuminated; press key, if gen is on-load, the gen
open will output and when open delay is over, the indicator of close/open is exstinguished.
If manual close is disabled, the key of close/open is deactivated.
When controller is in Auto or Stop Mode, the switch control procedure will perform the automatic
close/open procedure.
When genset is in normal running, gen and frequency reach the on-load conditions, the controller
will excute close/open automatically; the gen off load changes to gen on-load, the gen close will output.
When close delay is over, the indicator of close/open is illuminated; the gen on-load changes to gen off
load, the gen open will output. When open delay is over, the indicator of close/open is extinguished.
NOTE 1: When input port is configured “Gen close status input”, the close/open indicator is consistent only with
the input status of input port. When input port is active, the close/open indicator is illuminated, which means that
the current status is on-load; when input port is inactive, the close/open indicator is extinguished, which means
that the current status is off load.
6.1 WARNINGS
When controller detects the warning signal, it only issues warning but not shut down.
When controller detects the shutdown alarm, it will open and stop immediately and display the
alarm type.
9.1 MENU
Press key to enter parameter setting menu after controller starting, the menu items are as
follows:
Input the correct password (factory default:1234) to set all the items of Table 10. When more items
are needed, such as voltage calibration, please contact with manufacturer.
Notes:
a) Please modify the controller parameters (crank disconnect conditions selection, programmable
input, output port configuration, various delays) in standby mode, otherwise alarm shutdown or
other abnormal conditions may occur.
b) The over voltage threshold value must be greater than the under voltage threshold, otherwise
there will be both over voltage and under voltage.
c) The over speed threshold value must be greater than the under speed threshold, otherwise,
there will be both over speed and under speed.
d) The generator frequency should be set as lower value as possible when crank disconnect, so
that the starter motor can separate as soon as possible.
e) The Aux. input port 1~6 cannot be set as the same item, otherwise, the incorrect function may
occur. While the Aux. output port 1~4 can be set as the same.
f) If the shutdown after the high temperature cooling, please set a selection of “High Temperature
Cooling Shutdown” in any Aux. input port, and it should be grounded.
a) The interface can display the development information of controller, such as software version,
hardware version, release date;
b) Press key to display the status of digital input port and output port;
When sensors are reselected, the sensor curves will be transferred into the standard value. For
example, if temperature sensor is SGH (120°C resistor type), its sensor curve is SGH (120°C resistor
type); if select the SGD (120°C resistor type), the temperature sensor curve is SGD curve.
When there is difference between standard sensor curves and used sensor curves, users can
select “custom sensor “and input the custom sensor curve;
When the sensor curve is inputted, x value (resistor) must be inputted from small to large,
otherwise, mistake occurs;
If sensor type is selected as “none”, sensor curve is not working;
If the corresponding sensor has alarm switch only, users must set this sensor as “none”, otherwise,
shutdown or warning may occur;
The headmost or backmost values in the vertical coordinates can be set as the same as below.
N/m2
Item kgf/cm2 bar psi
Pa
1Pa 1 1.02x10-5 1x10-5 1.45x10-4
1kgf/cm2 9.8x104 1 0.98 14.2
1bar 1x105 1.02 1 14.5
1psi 6.89x103 7.03x10-2 6.89x10-2 1
CAUTION: The starting and fuel output ports should be extended with large capacity relays;
CAUTION: The Gen closing output port must be extended with relay externally while using.
Unit:mm
Table 16 Troubleshooting
_________________________________