Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

A60Q

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

AMP-TRAP®–Form 101

A60Q SEMICONDUCTOR PROTECTION FUSES


A60Q Amp-trap Form 101 Semiconductor
®

Protection fuses feature the only 600 volt AC/DC


rating in the industry of similar size (1-1/2” x
13/32”) fuses protecting semiconductors. A60Q
also has the lowest l2t of all similar fuses and
excellent cycling ability. Applications include
inverters and small equipment requiring extremely
fast response to faults, without the need to carry
sustained heavy overloads.

Features/Benefits
➤ Lowest l t of any fuse this size for greater protection
2

➤ Excellent cycling ability gives advantage in equip-


ment design
➤ 600V AC/DC rated

Ratings Approvals
➤ AC: 5-40A ➤ UL Recognized
600VAC, 200kA I.R. Component
➤ DC: 5-40A ➤ AC: UL Guide JFHR2
600VDC, 100kA I.R.
L/R = 10ms File E60314
➤ DC: UL File E60314

HIGHLIGHTS: APPLICATIONS:
Catalog Numbering System A 60 Q 30 - 2
➤ 600VAC/DC Rated ➤ Protection of small
Amp-trap Fuse A
➤ Extremely Fast Acting inverters and drives,
®

➤ Current Limiting and equipment requir-


ing the highest Rated Volts - 600 60
➤ Lowest l t 2

degree of protection Q
➤ Excellent Cycling Style
Ability
Amperes 30

Mounting Type
Ferrule, midget dims. 2
(1-1/2” x 13/32”)

Standard Fuse Ampere Ratings, Catalog Numbers
AMPERE CATALOG AMPERE CATALOG
RATING NUMBER RATING NUMBER fuse holders for a60Q fuses
5 A60Q5-2 20 A60Q20-2 USM Series . . . . UltrasafeTM Fuse Holders
6 A60Q6-2 25 A60Q25-2 303 Series . . . . . Midget Fuse Blocks
8 A60Q8-2 30 A60Q30-2
10 A60Q10-2 35 A60Q35-2
12 A60Q12-2 40 A60Q40-2 1-1/2”
15 A60Q15-2 (38.1 mm) 13/32”
(10.3 mm)
For ampere ratings and styles not listed, call Technical Services.

D 18
AMP-TRAP®–Form 101

A60Q SEMICONDUCTOR PROTECTION FUSES


I t at 600VAC, 100kA
2
Watts Loss Data
AMPERE WATTS LOSS @ WATTS LOSS @
2
AMPERE MELTING I t CLEARING I2t RATING 80% RATING (W) 100%RATING (W)
RATING (A2s) (A2s)
5 0.5 0.7
5 5 60 8 0.7 1.1
8 6.5 70 10 0.9 1.5
10 10 110 12 1.3 2.0
12 17 150 15 1.9 3.0
15 26 180 20 2.6 4.4
20 41 330 25 2.9 5.3
25 69 440 30 3.0 5.8
30 132 860 35 3.3 6.4
35 197 1300 40 3.6 7.0
40 276 1800

A60Q5 to 40
D
Melting Time – Current Data, 600V Fuses

Peak Let-Thru Current Data ­– A60Q5 to 40, 600 Volts AC


Max. Instantaneous Peak Let-Thru Amperes
Time in Seconds

Available Current in RMS Symmetrical Amperes

I t at 600VDC,100kA, L/R = 10 ms
2

AMPERE CLEARING I2t


RATING (A2s)

5 40
8 42
10 70
12 90
15 110
20 200
25 260
30 520
35 780
40 1100

Current in Amperes

D 19