Specification 300
Specification 300
Specification 300
Alert
Pipe Length (Branched) 130 m (427 ft) 560 m (1,837 ft)
Disabled
Pipe Lengths 1 Pipe 1 Pipe 2 Pipe 3 Pipe 4 Pipe
Depending On 100 m 110 m 100 m 80 m 70 m Fault
Number Of Pipes In Use (328 ft) (361 ft) (328 ft) (262 ft) (230 ft)
Power
StaX PSU PSU, Auto Pipe Clean
Smoke and Alarm
No. Of Holes (A/B/C) 30/40/45 40/80/100 Threshold Levels
Computer Design Tool ASPIRE Detector OK
Pipe Inlet: External diameter 25 mm or 1.05 in (3/4 in IPS) Detector Fault
Exhaust: External diameter 25 mm or 1.05 in (3/4 in IPS) via adaptor
Relays 7 programmable relays (latching or non-latching states) Aspirator Fault
Contacts rated 2 A @ 30 VDC (Resistive)
Airflow Fault
IP Rating IP40
Power Fault
Cable Access 4 x 26 mm (1.02 in) cable entries
Cable Termination 4 x 26 mm (1.02 in) cable entries Filter Fault
Dynamic Range 0.001% to 32% obs/m (0.0003% to 10% obs/ft) Smoke Chamber Fault
Sensitivity Range 0.005 to 20% obs/m (0.0016% to 6.25% obs/ft)
VESDAnet Fault
Threshold Setting Range Alert: 0.005% to 2.0% obs/m (0.0016% to 0.625% obs/ft)
Action: 0.005% to 2.0% obs/m (0.0016% to 0.625% obs/ft)
StaX Module Fault
Fire1: 0.010% to 2.0% obs/m (0.0031% to 0.625% obs/ft)
Fire2: 0.020% to 20.0% obs/m (0.0063% to 6.25% obs/ft)
Software Features Event log: Up to 20,000 events
Smoke level, user actions, alarms and faults with time and date stamp
AutoLearn: Detector learns Alarm Thresholds and Flow Fault thresholds by
monitoring the environment.