RXYMQ-AVMK Service Manual
RXYMQ-AVMK Service Manual
RXYMQ-AVMK Service Manual
Service
Manual
RXYMQ-A Series
Heat Pump 50/60 Hz
SiME332106E
Introduction .................................................................................... 1
1. Safety Cautions.......................................................................................2
1.1 Warnings and Cautions Regarding Safety of Workers.............................2
1.2 Warnings and Cautions Regarding Safety of Users.................................4
2. Icons Used ..............................................................................................6
3. Revision History ......................................................................................7
i Table of Contents
SiME332106E
Table of Contents ii
SiME332106E
6. Check ..................................................................................................271
6.1 High Pressure Check ...........................................................................271
6.2 Low Pressure Check ............................................................................272
6.3 Superheat Operation Check.................................................................273
6.4 Power Transistor Check .......................................................................275
6.5 Refrigerant Overcharge Check.............................................................278
6.6 Refrigerant Shortage Check.................................................................279
6.7 Vacuuming and Dehydration Procedure ..............................................280
6.8 Thermistor Check .................................................................................281
6.9 Pressure Sensor Check .......................................................................284
6.10 Broken Wire Check of the Relay Wires ................................................285
6.11 Fan Motor Connector Check (Power Supply Cable) ............................285
6.12 Fan Motor Connector Check (Signal Cable) ........................................287
6.13 Electronic Expansion Valve Coil Check ...............................................288
v Table of Contents
SiME332106E
Introduction
1. Safety Cautions.......................................................................................2
1.1 Warnings and Cautions Regarding Safety of Workers.............................2
1.2 Warnings and Cautions Regarding Safety of Users.................................4
2. Icons Used ..............................................................................................6
3. Revision History ......................................................................................7
Introduction 1
Safety Cautions SiME332106E
1. Safety Cautions
Be sure to read the following safety cautions before conducting repair work.
After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the
customer.
This manual is for the
person in charge of
maintenance and
inspection.
Caution Items The caution items are classified into Warning and Caution. The Warning items are
especially important since death or serious injury can result if they are not followed closely. The
Caution items can also lead to serious accidents under some conditions if they are not
followed. Therefore, be sure to observe all the safety caution items described below.
Pictograms This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown in the illustration or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown in the illustration or near the symbol.
2 Introduction
SiME332106E Safety Cautions
Warning
Do not turn the air conditioner on or off by plugging in or
unplugging the power cable.
Plugging in or unplugging the power cable to operate the equipment may
cause an electrical shock or fire.
Do not mix air or gas other than the specified refrigerant (R-32 /
R-410A / R-22) in the refrigerant system.
If air enters the refrigerant system, an excessively high pressure results,
causing equipment damage and injury.
Caution
Do not repair electrical components with wet hands.
Working on the equipment with wet hands may cause an electrical shock.
Be sure to turn off the power switch and unplug the power cable
when cleaning the equipment.
The internal fan rotates at a high speed, and may cause injury.
Introduction 3
Safety Cautions SiME332106E
Be sure to use parts listed in the service parts list of the applicable
model and appropriate tools to conduct repair work. Never attempt
to modify the equipment.
The use of inappropriate parts or tools may cause an electrical shock,
excessive heat generation or fire.
If the power cable and lead wires are scratched or have deteriorated,
be sure to replace them.
Damaged cable and wires may cause an electrical shock, excessive heat
generation or fire.
When wiring between the indoor and outdoor units, make sure that
the terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section may
cause an electrical shock, excessive heat generation or fire.
Do not mix air or gas other than the specified refrigerant (R-32 /
R-410A / R-22) in the refrigerant system.
If air enters the refrigerant system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leaking point and
repair it before charging the refrigerant. After charging the
refrigerant, make sure that there is no leak.
If the leaking point cannot be located and the repair work must be
stopped, be sure to pump-down, and close the service valve, to prevent
refrigerant gas from leaking into the room. Refrigerant gas itself is
harmless, but it may generate toxic gases when it contacts flames, such
as those from fan type and other heaters, stoves and ranges.
When relocating the equipment, make sure that the new installation
site has sufficient strength to withstand the weight of the
equipment.
If the installation site does not have sufficient strength or the installation
work is not conducted securely, the equipment may fall and cause injury.
4 Introduction
SiME332106E Safety Cautions
Warning
Check to make sure that the power cable plug is not dirty or loose,
then insert the plug into a power outlet securely.
If the plug is dusty or has a loose connection, it may cause an electrical
shock or fire.
Caution
Installation of a leakage breaker is necessary in some cases
depending on the conditions of the installation site, to prevent
electrical shocks.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage may cause water to enter the room and wet the furniture
and floor.
Introduction 5
Icons Used SiME332106E
2. Icons Used
The following icons are used to attract the attention of the reader to specific information.
Icon Type of Description
Information
Warning Warning is used when there is danger of personal injury.
Warning
Caution Caution is used when there is danger that the reader,
Caution through incorrect manipulation, may damage equipment,
lose data, get an unexpected result or have to restart (part
of) a procedure.
Note Note provides information that is not indispensable, but
Note may nevertheless be valuable to the reader, such as tips
and tricks.
Reference Reference guides the reader to other places in this binder
Reference or in this manual, where he/she will find additional
information on a specific topic.
6 Introduction
SiME332106E Revision History
3. Revision History
Month / Year Version Revised contents
09 / 2021 SiME332106E First edition
Introduction 7
SiME332106E
Part 1
General Information
1. Model Names
1.1 Outdoor Unit
Capacity range HP 4 5 6
Power
kW 11.3 14.1 16.0 supply,
Standard
Capacity index 100 125 150
Heat Pump 4A — — VMK
RXYMQ
4A 5A 6A YFK
2. External Appearance
2.1 Outdoor Unit
4, 5, 6 HP
RXYMQ4AVMK
RXYMQ4AYFK RXYMQ5AYFK RXYMQ6AYFK
Wall mounted
Wall mounted
FXAQ-AR
3. Capacity Range
3.1 Connection Ratio
Total capacity index of the indoor units
Connection ratio =
Capacity index of the outdoor units
4. Specifications
Model name RXYMQ4AVMK RXYMQ4AYFK
Power supply 1 phase, 220-240 V, 50/60 Hz 3 phase, 380-415/400 V, 50/60 Hz
(1)
Cooling capacity at T1 1 Capacity kW 11.3 11.3
Capacity Btu/h 38,500 38,500
EER kW/kW 4.10 4.07
EER Btu/W·h 14.00 13.90
PI kW 2.75 2.77
(2)
Cooling capacity at T1 1 Capacity kW 11.3 11.3
Capacity Btu/h 38,500 38,500
EER kW/kW 4.13 4.09
EER Btu/W·h 14.10 13.95
PI kW 2.73 2.76
Cooling capacity at T3 1 Capacity kW 10.4 10.6
Capacity Btu/h 35,400 36,200
EER kW/kW 3.14 3.14
EER Btu/W·h 10.70 10.70
PI kW 3.31 3.38
CSPF 3 W/W 5.80 5.70
Power factor 0.9 0.9
Cooling capacity at T4 1 Capacity kW 10.1 10.1
Capacity Btu/h 34,400 34,400
EER kW/kW 2.96 2.97
EER Btu/W·h 10.10 10.15
PI kW 3.41 3.39
Heating capacity at H1 1 Capacity kW 12.6 12.6
Capacity Btu/h 43,000 43,000
COP kW/kW 4.70 4.50
COP Btu/W·h 16.04 15.37
PI kW 2.68 2.80
Allowed indoor capacity Nom. 100 100
index connection Min. 50 50
Max. 130 130
Dimensions Unit mm 870×1,100×460 870×1,100×460
(H×W×D) Packed unit mm 1,010×1,190×560 1,010×1,190×560
Mass Unit kg 100 120
Packed unit kg 114 134
Heat Type
Cross fin coil Cross fin coil
exchanger
Fan Type Propeller Propeller
Discharge direction Side Side
Motor Quantity 1 1
Model Brushless DC Brushless DC
Output/pcs W 234 600
Airflow Cooling m³/min 87 123
rate Heating m³/min 94 145
Compressor Quantity 1 1
Motor Quantity 1 1
Model Inverter Inverter
Type Hermetically sealed swing type Hermetically sealed swing type
Refrigerant Refrigerant name R-410A R-410A
Charge kg 4.2 4.95
Piping Liquid Type Flare connection Flare connection
connections Diameter (OD) mm 9.5 9.5
Gas Type Flare connection Brazing connection
Diameter (OD) mm 15.9 15.9
Safety devices High pressure switch, Fan driver overload protector,
High pressure switch, Fan driver overload protector, Inverter overload protector, Fuse,
Inverter overload protector, Fuse,
Bimetal thermostat (external overload relay),
Bimetal thermostat (external overload relay) Over/under voltage protection PCB
Standard accessories Installation manuals, Operation manual, Installation manuals, Operation manual,
Ferrite core, etc. Auxiliary pipe, etc.
Drawing No. C: 2D135391B C: 2D135391B
Notes:
1. The above data are based on the following conditions.
Condition Indoor DB (°C) Indoor WB (°C) Outdoor DB (°C) Outdoor WB (°C) Reference standard
(1)
T1 27.0 19.0 35.0 — ISO 15042:2011
(2)
T1 26.6 19.4 35.0 — AHRI-1230
T3 29.0 19.0 46.0 — ISO 15042:2011
T4 26.6 19.4 48.0 — AHRI-1230
H1 20.0 — 7.0 6.0 ISO 15042:2011
Notes:
1. The above data are based on the following conditions.
Condition Indoor DB (°C) Indoor WB (°C) Outdoor DB (°C) Outdoor WB (°C) Reference standard
(1)
T1 27.0 19.0 35.0 — ISO 15042:2011
(2)
T1 26.6 19.4 35.0 — AHRI-1230
T3 29.0 19.0 46.0 — ISO 15042:2011
T4 26.6 19.4 48.0 — AHRI-1230
H1 20.0 — 7.0 6.0 ISO 15042:2011
Part 2
Refrigerant Circuit
(15) R3T Thermistor Used to detect suction pipe temperature, and for other purposes.
(Suction pipe: Ts)
Thermistor This detects temperature of liquid pipe between the air heat exchanger and main
(16) R4T (Heat exchanger liquid electronic expansion valve. Used to make judgments on the recover or discharge
pipe: Tf) refrigerants to the refrigerant regulator.
Thermistor This detects temperature of liquid pipe after subcooling heat exchanger.
(Subcooling heat
(17) R5T
exchanger liquid pipe:
Tsc)
Thermistor This detects temperature of gas pipe on the evaporation side of subcooling heat
(18) R6T (Subcooling heat exchanger. Used to exercise the constant control of superheating degree at the
exchanger gas pipe: Tsh) outlet of subcooling heat exchanger.
Thermistor Used to detect liquid pipe temperature of air heat exchanger.
(19) R7T (Heat exchanger deicer:
Tb)
RXYMQ4AVMK
C: 3D132648A
(13)
(2)
(10)
(14)
(8)
(19)
(16)
(7)
(1)
(5)
(3)
(11)
(4)
(18)
(12)
(9)
(6)
(15)
(17)
RXYMQ4/5/6AYFK
C: 3D132707A
(13)
(2)
(10)
(14)
(8)
(19)
(16)
(7)
(1)
(5)
(3)
(11)
(4)
(15)
(18)
(12)
(9)
(6)
(17)
Electronic expansion valve All indoor units Used for gas superheating degree
(1) Y1E control while in cooling or subcooling
degree control while in heating.
(2) Suction air thermistor R1T All indoor units Used for thermostat control.
Indoor liquid pipe thermistor All indoor units Used for gas superheating degree
(3) R2T control while in cooling or subcooling
degree control while in heating.
(4) Indoor gas pipe thermistor R3T All indoor units Used for gas superheating degree
control while in cooling.
(4)
(3)
(2)
(1)
(3)
(1)
(2)
(4)
C: 4D121746
C: 4D115598B
FXMQ-PB FXMQ-AR
(4) (4)
(3) (3)
(2) (2)
(1) (1)
C: 4D110285 C: 4D097585B
FXAQ20/25/32/40/50AR FXAQ63AR
(2) (2)
(4) (4)
C: 4D121516A C: 4D122027A
Thermistor (Subcooling
heat exchanger gas pipe)
(R6T)
Side View
Electronic expansion
valve (Inverter cooling)
(Y3E)
Electronic expansion
Compressor
valve (Injection)
(M1C)
(Y2E)
Thermistor (Subcooling
heat exchanger liquid pipe)
(R5T)
C: 1P627964E
Back view
Thermistor
(Heat exchanger deicer)
(R7T)
Thermistor
(Heat exchanger liquid pipe)
(R4T)
C: 1P627964E
2.2 RXYMQ4/5/6AYFK
Top View
Side View
Thermistor (Subcooling
heat exchanger gas pipe)
(R6T)
Compressor
(M1C)
C: 1P642649E
Back view
Thermistor
(Heat exchanger deicer)
Thermistor (R7T)
(Heat exchanger liquid pipe)
(R4T)
C: 1P642649E
Part 3
Remote Controller
1. Applicable Models
Wired remote controller Wireless remote controller
Series
Navigation Madoka Remote controller Receiver
FXFSQ-AR
BRC7M632F-6
(1)
FXDQ-PD
FXDQ-ND BRC1H81W7
BRC1E63 BRC4M150W16
BRC1H81S7 BRC4M61-6
FXMQ-PB
FXMQ-AR
FXAQ-AR BRC7N618-6
Note(s) 1. Some functions are not available depending on the remote controller type. Refer to page 26
for details.
Function list
FXFSQ-AR
Category Function
BRC1E63 BRC4M150
ON/OFF operation ● ●
Operation mode switching ● ●
Setting temperature ● ●
Swing pattern selection ● ●
Switchable fan speed (Ventilation amount) ● ●
Display switching function ● —
Basic performance
Backlight function ● ●
Display automatic OFF ● —
Multilingual correspond ● ●
Timer function (Time schedule display) ● —
Key lock function ● —
Contrast adjustment ● —
Automatic Eco airflow rate ● ●
Eco infrared floor temperature sensor ● —
Sensing sensor stop mode ● —
Sensing sensor low mode ● —
Setpoint range set ● —
Setback ● —
Energy saving function
OFF timer (programmed) ● —
Weekly schedule timer ● —
ON/OFF timer — ●
Setting temperature automatic recovery ● —
VRTsmart control ● —
VRT control ● —
Active circulation airflow ● —
Forced cooling ON operation ● —
Automatic cooling/heating changeover ● —
Independent up-and-down airflow ● —
Automatic direct air (when human sensing) ● —
Hot start function ● ●
Draft prevention ● —
Comfortable function
Two selectable temperature sensors ● —
Application for high ceiling ● —
Service contact display ● —
Model name display (indoor/outdoor) ● —
Filter sign/reset ● ●
Operation time accumulation time display ● —
Operation data display ● —
●: Available
—: Not available
Basic Screen
• Operation mode changeover
The items on each menu vary
• Temperature setting
depending on the connected
• Airflow rate
models.
• Airflow direction
• Menu display
• Confirmation of each setting
• On
• Off
• Cancel Basic screen
• Operation lamp
Press Cancel button Press Cancel
for 4 seconds or more. button once.
Press Cancel
button once.
Press Cancel button
for 4 seconds or more.
- +
(5)
(1) ON/OFF
When OFF, press to turn ON the system. As a result, the status indicator (5) will turn ON too.
When ON, press to turn OFF the system. As a result, the status indicator (5) will turn OFF
too.
(2) ENTER/ACTIVATE/SET
From the home screen, enter the main menu.
From the main menu, enter one of the submenus.
From their respective submenu, activate an operation/ventilation mode.
In one of the submenus, confirm a setting.
(3) CYCLE/ADJUST
Cycle left.
Adjust a setting (default: decrease).
(4) CYCLE/ADJUST
Cycle right.
Adjust a setting (default: increase).
Note(s) For a full description of the behavior of the status indicator, see the installer and user reference
guide.
Home screens Depending on installer configuration, the controller either has a standard or a detailed home
screen. In most cases, the standard home screen gives you only the active operation mode,
messages (if any), and the setpoint temperature (in case of Cooling, Heating, or
Auto operation mode). The detailed home screen gives you all kinds of information through
status icons.
Standard Detailed
(1) (1) 19
(2) (2)
(3) (3)
(1) Messages
(2) Active operation mode
(3) Setpoint temperature
Note(s) The controller is equipped with a power saving function that causes the screen to go blank after
a period of inactivity. To make the screen light up again, press one of the buttons.
Status icons
Icon Description Icon Description
System operation. Indicates that the system is Periodic inspection. Indicates that the indoor or
operating. outdoor unit is being inspected.
Bluetooth. Indicates that the controller is Backup. Indicates that in the system an indoor unit is
communicating with a mobile device, for use with the set as backup indoor unit.
Daikin Control Assistant app.
Individual airflow direction. Indicates that the
Centralized control. Indicates that the system is
individual airflow direction setting is enabled.
controlled by central control equipment (optional
accessory) and that control of the system by the Information. Indicates that the system has a
controller is limited. message to convey. To see the message, go to the
Changeover under centralized control. Indicates information screen.
that the cooling/heating changeover is under Warning. Indicates that an error occurred, or that an
centralized control by another indoor unit, or by an indoor unit component needs to be maintained.
optional cool/ heat selector that is connected to the
outdoor unit. Demand control. Indicates that the system's energy
Defrost/Hot start. Indicates that the defrost/hot start consumption is being limited, and that it is running
mode is active. with restricted capacity.
End of demand control. Indicates that the system's
Timer. Indicates that the schedule timer or OFF timer energy consumption is no longer being limited, and
is enabled. that it is no longer running with restricted capacity.
Clock not set. Indicates that controller's clock is not Rotation. Indicates that Rotation mode is active.
set.
Self-cleaning filter operation. Indicates that self- Setback. Indicates that the indoor unit is operating
cleaning filter operation is active. under setback conditions.
Inspection. Indicates that the indoor or outdoor unit is Ventilation. Indicates that a heat reclaim ventilation
being inspected. unit is connected.
The Bluetooth® word mark and logos are registered trademarks owned by the Bluetooth SIG,
Inc. and use of such marks by Daikin Europe N.V. is under license. Other trademarks and trade
names are those of their respective owners.
13
2
1
6
3
7 4
8
5
9
10
11
12
18
17
15
14
16 19
20
FXFSQ-AR (BRC7M632F-6)
26 25
21
22
23 24
21
23 25
24 22
26
FXAQ-AR (BRC7N618-6)
23
22
24
25
21
26
3. Main/Sub Setting
Main/Sub setting is necessary when 1 indoor unit is controlled by 2 remote controllers. The
remote controllers are set at factory to Main, so you have to change one remote controller from
Main to Sub. To change a remote controller from Main to Sub, proceed as follows:
Note(s) 1. It is not possible to change the Main/Sub setting from Main to Sub when only one remote
controller is connected.
2. When 2 remote controllers are being used, it is not possible to change the setting from Main
to Sub if one of the remote controllers is already set as Main.
a c
a Outdoor unit
b Indoor unit
c Master remote controller
a c d
a Outdoor unit
b Indoor unit
c Master remote controller
d Slave remote controller
Note(s) The following functions are not available for slave controllers:
Auto operation mode
Individual airflow direction
Filter auto clean
Setback temperature setpoints
Draft prevention
Duty rotation
Main/Sub switch S S
(SS1) M M
Transmitter assembly
S
M
2 3
1
SS1
SS2
3
Wireless address 3
3
switch (SS2)
2
2
2
1
1
1
The side painted black indicates
the switch knob position.
Transmitter assembly
S
M
2 3
1
SS1
SS2
1. Hold down the FILTER SIGN RESET button and the INSPECTION button for at least 4
seconds to get the Field Setting mode.
(Indicated in the display area in the figure.)
2. Press the SELECT button and select a multiple setting (A/b). Each time the button is
pressed the display switches between A and b.
3. Press the TEMP buttons to set the address.
Address can be set from 1 to 6, but set it to 1-3 and to same address as the receiver. (The
receiver does not work with address 4-6.)
4. When the RESERVE button is pressed, the setting is confirmed and the usual display
returns.
Address
Multiple setting
2
4
Item 2 is
displayed.
Select the desired
Group No. using Press the Menu/Enter
the / (Up/Down) button.
buttons, and then
press the
Menu/Enter
button.
Item 2 is
displayed.
Item 2 is
displayed.
Select the desired
Group No. using Press the Menu/Enter
the / (Up/Down) button.
buttons, and then
press the
Menu/Enter
button.
Item 2 is
displayed.
First level
Group (Group): A group is a group of indoor units.
Second level
Define an address for the indoor unit.
Apply settings.
Indoor/Outdoor
F1 F2
F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2
RC
Group Control by Remote Controller
1-00 Main RC RC Sub RC
(automatic unit address)
1-01 1-02
F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2
No Remote Controller
RC
1-03
1-04
Caution When turning the power supply on, the unit may often not accept any operation after all
indications were displayed once for about 1 minute on the liquid crystal display. This is not an
operative fault.
Basic
screen is
displayed.
Press and
hold the Press the Cancel
Cancel button button once.
for 4 seconds Select an item from Service Select the desired item from
or more. settings menu and press the Item 2 sub menu, and
Menu/Enter button. press Menu/Enter button.
Service
Press the Item 2 is Item 3 is
settings menu
Cancel displayed. displayed.
is displayed. Press Cancel button. Press Cancel button.
button.
Press and
hold the
Cancel button
for 4 seconds
or more. Select the desired item from the
Maintenance menu, and then Select the desired Unit No.
Maintenance press the Menu/Enter button. using the / (Up/Down)
Item 2 is
menu is buttons. The corresponding
displayed. data will be displayed.
displayed. Press the Cancel button.
Maintenance
Item 2 Remarks
Menu
Addressed Unit No.: 0 - 15 Select the unit number you want to check.
Sensor
Value Code
00: Remote controller thermistor (°C)
01: Suction air thermistor (°C) 5
02: Heat exchanger liquid pipe thermistor (°C)
03: Heat exchanger gas pipe thermistor (°C)
04: Indoor unit address No.
05: Outdoor unit address No.
06: BS unit address No.
07: Zone control address No.
08: Cooling/Heating batch address No.
09: Demand/low-noise address No.
22: Displays human presence detection rate (%) (see 7) in
Area 1 (see 6). Display value × 10%. Displays 15 for
units with no sensing type mounted.
23: Displays human presence detection rate (%) (see 7) in
Area 2 (see 6). Display value × 10%. Displays 15 for
units with no sensing type mounted.
24: Displays human presence detection rate (%) (see 7) in
Area 3 (see 6). Display value × 10%. Displays 15 for
units with no sensing type mounted.
25: Displays human presence detection rate (%) (see 7) in
Area 4 (see 6). Display value × 10%. Displays 15 for
units with no sensing type mounted.
26: Infrared sensor (°C) (See 8). Displays – for units with
no sensing type mounted.
Data The corresponding data will be displayed, based on the
Unit No. and Code selected.
1: Displays suction air temperature after correction for all models.
2: Displays temperature only for applicable models.
3: Displays floor temperature used for control (including correction) when the sensor kit is
connected.
4: Displays control temperature (temperature near the person when the sensor kit is
connected).
5: Displays suction air temperature after correction when the sensor kit is connected.
6: Areas mean four areas shown on the below.
7: For human presence detection rate (%), human motion is recognized by digital output
ranging from 0 to 5 V. (5 V is output when no human presence is detected, and 0 V is output
when human presence is detected.)
4
1 3
2
Detection areas of presence sensor
(Corresponding to the punched mark
80 cm above the floor on the inner frame of the panel:
~)
Reference
(1) 0% detection rate: Human presence is not detected at all.
(2) 25% detection rate: Human presence is detected, but the sensor does not recognize human
presence.
(3) 50% detection rate: The sensor recognizes human presence (small human motion).
(4) 75% detection rate: The sensor recognized human presence (large human motion).
(5) 100% detection rate: The sensor constantly outputs 0 V. Continuing this condition will
display an error.
8: Directly displays a measured value sent from the adaptor PCB.
Contrast Extremal
input
interlock
Remote Information
controller
field settings
Part 4
Functions and Control
1. Operation Flowchart..............................................................................50
2. Stop Control ..........................................................................................51
2.1 Abnormal Shutdown ...............................................................................51
2.2 When System is in Stop Control.............................................................51
3. Standby Control ....................................................................................52
3.1 Restart Standby......................................................................................52
3.2 Crankcase Heater Control......................................................................52
4. Startup Control ......................................................................................53
4.1 Cooling Startup Control ..........................................................................53
4.2 Heating Startup Control..........................................................................53
5. Normal Control ......................................................................................54
5.1 List of Functions in Normal Control ........................................................54
5.2 Compressor Control ...............................................................................55
5.3 Compressor Capacity Control ................................................................56
5.4 Compressor Step Control.......................................................................57
5.5 Electronic Expansion Valve Control .......................................................58
5.6 Step Control of Outdoor Fans ................................................................58
6. Protection Control .................................................................................59
6.1 High Pressure Protection Control...........................................................59
6.2 Low Pressure Protection Control............................................................60
6.3 Discharge Pipe Protection Control .........................................................60
6.4 Inverter Protection Control .....................................................................61
6.5 Heating Operation Prohibition ................................................................64
6.6 Overload Protection Control ...................................................................64
7. Special Control......................................................................................65
7.1 Pump Down Residual Control ................................................................65
7.2 Oil Return Control...................................................................................65
7.3 Defrost Control .......................................................................................67
8. Outline of Control (Indoor Unit) .............................................................68
8.1 Set Temperature and Control Target Temperature................................68
8.2 Thermostat Control.................................................................................69
8.3 Automatic Airflow Rate Control ..............................................................72
8.4 Airflow Direction Control.........................................................................73
8.5 Auto Draft Reducing Control (FXFSQ-AR only) .....................................74
8.6 Eco Full Automatic Control (FXFSQ-AR only)........................................74
8.7 Drain Pump Control................................................................................75
8.8 Freeze-Up Prevention Control................................................................77
8.9 Dew Condensation Prevention Control ..................................................78
8.10 Electronic Expansion Valve Control .......................................................79
8.11 Circulation Airflow (FXFSQ-AR only) .....................................................80
8.12 Hot Start Control (In Heating Operation Only)........................................81
8.13 Heater Control (Optional PCB KRP1B series is required.).....................82
1. Operation Flowchart
For detailed description of each function in the flow below, refer to the details on related function
on the following pages.
Stop control
(1) Abnormal shutdown
(2) When system is in stop control
Special control
Standby control
(1) Restart standby
(2) Crankcase heater control
(1) Pump down residual control
(note 2)
Thermostat ON
Startup control
(include pressure equalization before startup)
(1) Cooling startup control
(2) Heating startup control
Thermostat OFF
Abnormality
End of
startup
control
Normal control
(1) List of functions in normal control
(2) Compressor control
(3) Compressor capacity control
(4) Compressor step control
(5) Electronic expansion valve control Conditions met for oil return
(6) Step control of outdoor unit fans (2) Oil return control (note 1)
Protection control
(1) High pressure protection control
(2) Low pressure protection control Conditions met for defrosting
(3) Defrost control (note 1)
(3) Discharge pipe protection control
(4) Inverter protection control
(5) Heating operation prohibition
(6) Overload protection control
Note(s) 1. If the indoor unit stops or the thermostat turns OFF while in oil return control or defrost
control, pump down residual operation is performed on completion of the oil return operation
or defrost control.
2. Not performed during cooling mode.
2. Stop Control
2.1 Abnormal Shutdown
In order to protect compressors, if any of the abnormal state occurs, the system will make "stop
with thermostat OFF" and the error will be determined according to the number of retry times.
(Refer to Error Codes and Descriptions on page 153 for the items to determine the error.)
3. Standby Control
3.1 Restart Standby
Used to forcedly stop the compressor for a period of 5 minutes, in order to prevent the frequent
ON/OFF of the compressor and equalize the pressure within the refrigerant system.
In addition, the outdoor fan carry out the residual operation for a while to accelerate pressure
equalizing and to suppress melting of the refrigerant to the evaporator.
4. Startup Control
This control is used to equalize the pressure in the front and back of the compressor prior to the
startup of the compressor, thus reducing startup loads. Furthermore, the inverter is turned ON
to charge the capacitor.
To avoid stresses to the compressor due to oil return or else after the startup, the following
control is made and the position of the four way valve is also determined.
Pc : High pressure sensor detection value
Pe : Low pressure sensor detection value
Ta : Outdoor air temperature
Te : Low pressure equivalent saturation temperature
Td : Discharge temperature
0 Hz
Compressor (M1C)
480 pulse (fully open)
Electronic expansion 0 pulse
valve (Main)
(Y1E) 480 pulse (fully open)
Electronic expansion 0 pulse
valve (Refrigerant jacket)
(Y3E)
Min.
step
0 Hz 15 sec.
Compressor (M1C)
T (Ta – Te) control
Step 4
Fan motor (M1F)
5. Normal Control
5.1 List of Functions in Normal Control
Pc : High pressure sensor detection value
Pe : Low pressure sensor detection value
Tc : High pressure equivalent saturation temperature
Te : Low pressure equivalent saturation temperature
Cooling
Electric
Part Name RXYMQ-A Function
Symbol
Compressor motor M1C PI control by Te target.
Fan motor M1F Fan speed 9 steps to keep minimum Tc target 41°C.
Electronic expansion valve 0 pulse: closed (thermostat OFF)
(Main) Y1E 0-480 pulses: open (thermostat ON)
Electronic expansion valve 0-480 pulse at compressor ON
(Injection) Y2E
: equipped
—: not equipped
Heating
: equipped
—: not equipped
In case of target evaporation (or condensation) temperature adjustment, first the capacity is
adjusted by changing the indoor unit airflow to L tap. If the capacity is still too much, the target
evaporation (or condensation) temperature is elevated further to adjust.
2. VRT Control
When one or more of the connected indoor units are not VRTsmart control applicable
models
If the required capacity becomes low (or high) in all indoor units (Room temperature Th1 - set
temperature), the target evaporation (or condensation) temperature is elevated further to adjust.
In the outdoor unit, the difference of temperature (∆T) in all indoor units is checked and the set
temperature is changed. Unlike VRTsmart control, there is no airflow control of the indoor units.
6 7 8 9 10 11
Te: Low pressure equivalent saturation temperature (°C)
TeS: Te target value (varies according to Te setting, compressor operation frequency, etc.)
Compressor
0 Hz
Main 480
Y1E pulses
0
Compressor
0 Hz
Main 480
Y1E pulses
0
* When the system detects that outdoor air temperature (Ta) reaches 41°C or more, the control
of fan revolutions will be changed to 1,060 rpm automatically.
Note(s) Table shown above is for external static pressure level 0. In case of high external static
pressure, the unit will re-adjust fan revolutions automatically and values may differ.
When capacity priority mode is set, values may differ.
6. Protection Control
6.1 High Pressure Protection Control
This high pressure protection control is used to prevent the activation of protection devices due
to abnormal increase of high pressure and to protect compressors against the transient
increase of high pressure.
Cooling
The following control is performed in the entire system.
Normal control
Pc: High pressure sensor detection
Pc > 3.55 MPa Pc < 3.04 MPa value for each outdoor unit.
Heating
The following control is performed in the entire system.
Normal operation
Cooling
Because of common low pressure, the following control is performed in the system.
Normal control
Pe < 0.35 MPa Pe > 0.40 MPa Pe: Low pressure sensor detection
value for master unit.
Heating
The following control is performed in the system.
Normal operation
Normal control
Normal control
A B
Cooling
Heating
Graph A
26
24
22
20
18
CTi1 (A)
16
14
12
10
8
43 44 45 46 47 48 49 50 51 52 53
Ta (°C)
Graph B
24
22
20
18
16
CTi1 (A)
14
12
10
6
43 44 45 46 47 48 49 50 51 52 53
Ta (°C)
Normal control
Cooling
Heating
Normal control
A B
Cooling
Heating
Normal control
Overload standby
(Error code F3 is output)
7. Special Control
7.1 Pump Down Residual Control
Pc : High pressure sensor detection value
Pe : Low pressure sensor detection value
To avoid refrigerant emigration when outdoor unit stops operation (thermostat or safety), all
electronic expansion valves are closed.
Starting conditions
Oil return control is not conducted before 2 hours have elapsed from the activation of power
supply.
After 2 hours have elapsed, oil return control starts when the following item meets the
reference value.
• Total amount of oil discharged from the compressor
(The total amount of oil discharged from the compressor is computed from Tc, Te, and
compressor loads.)
Oil return control starts every 8 hours of cumulative operation of the compressor, even if the
reference value is not met.
Temperature 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35°C
Temperature 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35°C
Examples are given to illustrate a control target temperature that satisfies the remote controller
set temperature.
Temperature 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 ˚C
Temperature 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 ˚C
Examples are given to illustrate a control target temperature that satisfies the remote controller
set temperature.
Normal operation
Cooling operation
ΔT ≤ –1.0°C
Normal operation
Thermostat OFF
(Thermostat ON)
ΔT ≥ +1.0°C
Heating operation
T 1.0°C
Normal operation
Thermostat OFF
(Thermostat ON)
T –1.0°C
Dry operation
When Tro 24.5°C
Tr < Tro – 1.0°C
Dry operation Thermostat OFF
Tr > Tro + 1.0°C
: Description of symbols
ΔT = Detected room temperature – Remote controller set temperature
Tro: Detected room temperature at the start of dry operation
Tr: Determined by the room temperature detected by the thermistor
Note(s) 1: The thermistor used to detect room temperature is according to the field setting 10(20)-2.
Normal operation
Cooling operation
ΔT ≤ –1.0°C
Normal operation
Thermostat OFF
(Thermostat ON)
ΔT ≥ +1.0°C
Heating operation
T 1.0°C
Normal operation
Thermostat OFF
(Thermostat ON)
T –1.0°C
Dry operation
When Tro ≤ 24.5°C
Tr < Tro – 1.0°C
Dry operation Thermostat OFF
Tr > Tro + 1.0°C
: Description of symbols
ΔT = Detected room temperature – Remote controller set temperature
Tro: Detected room temperature at the start of dry operation
Tr: Determined by the room temperature detected by the thermistor
Cooling thermostat ON
Cooling thermostat OFF
Display change
Cooling → Heating
Display change
Heating → Cooling
3°C
(D
2 + 2)°C
Indoor unit
P0
P1
P2
P4 P3
Thermostat ON
(running)
OFF
ON
Error display
OFF
ON
Drain pump
OFF
5 min.
Thermostat ON
(running)
OFF
A3
ON
Error display
OFF
ON
Drain pump
OFF
When the float switch turns OFF, the thermostat turns OFF simultaneously.
After the thermostat turns OFF, the drain pump continues to operate for another 5 minutes.
1: If the float switch turns ON again during the residual operation of the drain pump, cooling
operation also turns on again (thermostat ON).
2: If the float switch remains OFF even after the residual operation of the drain pump has
ended, the error code A3 is displayed on the remote controller.
The drain pump turns OFF once residual operation has ended, then turns ON again after 5
seconds.
3: After A3 is displayed and the unit comes to an abnormal stop, the thermostat will remain
OFF even if the float switch turns ON again.
8.7.3 If the Float Switch is OFF with the Thermostat OFF in Cooling
Operation
OFF
Float switch
ON
Thermostat ON
(running)
OFF
A3
ON
Error display
OFF
ON
Drain pump
OFF
5 min. 5 sec.
When the float switch turns OFF, the drain pump turns ON simultaneously.
If the float switch remains OFF even after residual operation of the drain pump has ended,
the error code A3 is displayed on the remote controller.
The drain pump turns OFF once residual operation has ended, then turns ON again after 5
seconds.
8.7.4 If the Float Switch Turns OFF and ON Continuously, or the Float
Switch Turns OFF While AF Displayed
∗1 ∗2 ∗3
} }
OFF
Float switch
ON
1st 2nd 3rd 4th 5th
Thermostat ON
(running)
OFF
AF A3
ON
Error display
OFF
ON
Drain pump
OFF
When the float switch turns OFF, the drain pump turns ON simultaneously.
1: If the float switch continues to turn OFF and ON 5 times consecutively, it is judged as a drain
system error and the error code AF is displayed on the remote controller.
2: The drain pump continues to turn ON/OFF in accordance with the float switch ON/OFF even
after AF is displayed on the remote controller.
3: While the error code AF is displayed, if the float switch remains OFF even after the residual
operation of the drain pump has ended, the error code A3 will be displayed on the remote
controller.
When freeze-up prevention is activated, the airflow rate is fixed to L tap. When the following
conditions for cancelling are satisfied, it will reset.
+7ºC
0ºC
–5ºC
Freeze-up prevention control
Forced OFF by thermostat Normal operation
10 min.
Start Cancel
Note(s) When the indoor unit is a round flow or multi flow type, if the air outlet is set as dual-directional
or tri-directional, the starting conditions will be changed as follows.
Liquid pipe temperature 1°C (for total of 15 minutes)
or
Liquid pipe temperature 0°C (for 1 minute continuously)
During freeze-up prevention control, the airflow rate is fixed to LL.
(The cancelling conditions are same as the standard.)
Refer to the table below for flap action under this control.
Indoor unit
P0
P1
P2
P4 P3
Flap position AIR
(Observed horizontally)
Starting condition
Indoor unit
P0
P1
P2
P4 P3
Flap position AIR
(Observed horizontally)
FXAQ-AR
Position A P4
B (minutes) 20
Position C P3
Note(s) When there is any change to fan operation, airflow direction and operation ON/OFF state during
dew condensation prevention control, this control is canceled.
This function is used to adjust the opening of the electronic expansion valve so that
superheating degree (SH), which is calculated from the detection temperature (Tg) of the gas
pipe thermistor (R3T) and the detection temperature (Tl) of the liquid temperature thermistor
(R2T) of the indoor unit, will come close to a target superheating degree (SHS).
At that time, correction to the superheating degree is made according to the differences (T)
between set temperature and suction air temperature.
SH = Tg – Tl
Where,
This function is used to adjust the opening of the electronic expansion valve so that the high
pressure equivalent saturated temperature (Tc), which is converted from the detected pressure
of the high pressure sensor in the outdoor unit, and the subcooling degree (SC), which is
calculated from the detected temperature (Tl) of the liquid temperature thermistor (R2T) in the
indoor unit, will come close to the target subcooling degree (SCS).
At that time, corrections to the subcooling degree are made according to differences (T)
between set temperature and suction air temperatures.
SC = Tc – Tl
Where,
Set temp.
Target temp. Δt
Time
Indicates the horizontal flap is in the position of reducing airflow volume (the flap is inverted).
Indicates the horizontal flap is in the position of reducing airflow volume (the flap is inverted).
Indicates the horizontal flap is in the position of reducing airflow volume (the flap is inverted).
Indicates the horizontal flap is in the position of reducing airflow volume (the flap is inverted).
LL
The fan is not OFF before initiating the hot start: LL
The fan is OFF before initiating the hot start: OFF
OFF
Remote controller Normal control
Louver
setting
P0 (Horizontal)
Normal control
While in heating operation, the heater control (ON/OFF) is conducted as shown below.
ON Set temperature
OFF
2ºC 2ºC
Overload control
When the system is overloaded in heating operation, the heater will be turned OFF in the
following two manners.
1. The heater control (ON/OFF) is conducted through the liquid pipe temperature (R2T) of the
indoor unit.
ON 43ºC 50ºC Liquid pipe temperature
OFF
2. The heater control (ON/OFF) is conducted by converting the heater temperature into the
condensing pressure equivalent saturated temperature (Tc) according to the temperature
detection through the high pressure sensor (S1NPH) of the outdoor unit.
ON 50ºC 60ºC Condensing pressure
equivalent saturated
temperature
OFF
Residual operation time = 100 seconds on ceiling suspended type or 60 seconds on other types
Part 5
Field Settings and
Test Operation
1. Field Settings for Indoor Unit.................................................................84
1.1 Field Settings with Remote Controller ....................................................84
1.2 List of Field Settings for Indoor Unit .......................................................90
1.3 Applicable Field Settings ........................................................................92
1.4 Details of Field Settings for Indoor Unit..................................................93
1.5 Operation Control Mode .......................................................................106
2. Field Settings for Outdoor Unit............................................................108
2.1 Function Setting ...................................................................................108
2.2 Settings by DIP Switches .....................................................................109
2.3 Settings by BS Buttons.........................................................................112
2.4 Normal Mode........................................................................................114
2.5 Monitor Mode (Mode 1) ........................................................................115
2.6 Setting Mode (Mode 2).........................................................................118
2.7 Eco Mode Setting .................................................................................130
2.8 Night-Time Low Noise Operation and Demand Operation...................131
3. Test Operation ....................................................................................135
3.1 Checks before Test Operation .............................................................135
3.2 Checkpoints..........................................................................................135
3.3 Test Operation Procedure ....................................................................136
3.4 Turn Power ON ....................................................................................138
1.1.1 BRC1E63
Basic screen
CAUTION
When an optional accessory is installed on the indoor unit, settings of the indoor
unit may be changed. See the manual of the optional accessory.
For field setting details of the outdoor unit, see installation manual attached to the
outdoor unit.
1. Modes (Mode),
2. Units (Unit),
3. Settings (SW),
Making Field
Settings
7. Select desired “Second Code No.. Multiple identical mode number settings are available.
In the case of group total setting, all of Second Code No. which may be set are displayed as
"*".
"*" is changed to Second Code No. to be set. And, Second Code No. "-" means no function.
Applying Field
Settings
Mode No.
4
3
5
1,6
Setting
To set the field settings, you have to change:
Mode No.
First code No.
Second code No.
4 Airflow direction adjustment Refer to the page on the right for details. 102
range
13 (23) Setting of static pressure High static
5 Standard — — 102
selection pressure
External static pressure
6 Refer to the page on the right for details. 103
settings
Setting of swing patterns when
7 Refer to the page on the right for details. 103
cooling thermostat is OFF
13 Setting of circulation airflow Disabled Enabled — — 103
14 Circulation airflow patterns Pattern 1 Pattern 2 Pattern 3 Pattern 4 104
Switching panel type Standard
15 Designer panel — — 104
panel
Humidification when heating
1 thermostat is OFF Not equipped Equipped — — 104
Note(s) 1. Settings are made simultaneously for the entire group, however, if you select the mode No. inside
parentheses, you can also set by each individual unit. Setting changes however cannot be checked except
in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so they cannot
be set individually. Setting changes also cannot be checked.
3. Do not make settings other than those described above. Nothing is displayed for functions the indoor unit
is not equipped with.
4. 88 or Checking the connection. Please stand by. may be displayed to indicate the remote controller is
resetting when returning to normal mode.
5. BRC1H81 series only
36
34 In cooling
32
24
22
20
17 19 21 23 25 27 29 31 33 35 37
Suction air temperature (°C)
32
30
28
Set temperature (°C)
26 In heating
Suction air Remote controller Suction air
thermistor thermistor thermistor
24
Suction air Remote controller Suction air
22 thermistor thermistor thermistor
20
18
16
14
14 16 18 20 22 24 26 28 30 32 34
Suction air temperature (°C)
10 (20) 2 01 02 02 02# 02 03
11 (21) 8 01 01 02 03# 04 01
The thermistor to be used
Remote controller thermistor — — — —
Suction air thermistor —
Infrared floor sensor — — —
01 30 minutes
10 (20) 7
02 60 minutes
Human detection
State of absence
31
30
29
Set temperature (°C)
28
27 Cooling (at 28°C)
26
21
Heating (at 20°C)
20
19
18
17
30 (60)∗ 60 (120)∗
Elapsed time of absence (min.)
∗ The values in parentheses represent the time
when Second code No. is 02.
The set temperature displayed on the remote controller remains the same even if the target
temperature is shifted.
As soon as people are detected while the temperature is shifted, this control will be
cancelled (reset).
1.4.7 Low Airflow Setting when Thermostat OFF during VRTsmart Control
This setting changes the airflow volume to LL in coordination with the VRTsmart control when
cooling thermostat OFF is set. Also, the airflow direction is changed to horizontal.
When disabled:
12 (22)-6 (the airflow volume setting when cooling thermostat OFF is enabled)
13 (23)-7 (the swing setting when cooling thermostat OFF is enabled) is as set
When enabled: LL when Te ≥ 7°C
: Factory setting
Mode First Code Second Contents
No. No. Code No.
01 Disabled
10 (20) 11
02 Enabled
01 Normal
11 (21) 2
02 Fan OFF
01 Standard
11 (21) 3 02 Slightly increased
03 Increased
Note that this setting is effective only during the heating operation.
01 High sensitivity
02 Low sensitivity
11 (21) 6
03 Standard sensitivity
04 Infrared presence/floor sensor disabled
: Factory setting
Mode First Second Contents
No. Code No. Code No.
01 OFF
11 (21) 7 02 Completion of airflow adjustment
03 Start of airflow adjustment
Note(s) 1. Make sure that the external static pressure is within the range of specifications before making
settings. If it is outside the range, automatic adjustment fails, which may cause an insufficient
airflow volume or leakage of water.
2. If the air passageway including duct or blow-off ports is changed after automatic adjustment,
make sure to perform automatic airflow adjustment again.
: Factory setting
Mode First Code Second
Contents
No. No. Code No.
01 Suction air temperature only
02 Priority given on the suction air temperature
11 (21) 8
03 Standard
04 Priority given on the floor temperature
: Factory setting
Mode First Second
Contents
No. Code No. Code No.
ON: Forced OFF (prohibition of using the remote controller)
01
OFF: Permission of using the remote controller
OFF ON: Operation
02
12 (22) 1 ON OFF: Stop
ON: Operation
03 OFF: The system stops, then the applicable unit indicates A0. The
other indoor units indicate U9.
1. The air conditioner will start operation suddenly after power failure,
Caution or when the main power supply is restored. The user might be surprised
and wonder why the air conditioner turned ON suddenly.
2. During maintenance, if the main power supply is turned OFF while the
units are in operation, the units will automatically start operation
(the fan will rotate) after the power supply is restored due to completion
of the maintenance work.
01 4°C
02 2°C
12 (22) 11
03 0°C
04 –2°C
FXFSQ25-80AR
: Factory setting
FXFSQ100-140AR
: Factory setting
Note(s) 1. The Second Code No. is factory set to Standard/All-direction airflow. For High ceiling (1) or
(2), initial setting by remote controller is required.
2. A closing member kit (optional) is required for 4-, 3-, or 2-direction airflow.
FXAQ-AR
: Factory setting
First
Mode Second
Code Contents
No. Code No.
No.
01 Standard
13
(23) 0 02 Slightly higher
03 High
Note(s) 1. Some indoor unit models are not equipped with draft prevention (upward) function.
2. When the model FXFSQ-AR is attached with a closing member kit, set the Second Code No.
to 02 or 03.
01 Disabled
13 (23) 13
02 Enabled
Indicates the horizontal flap is in the position of reducing airflow volume (where the flap is
reversed).
Indicates the horizontal flap is in the position of reducing airflow volume (where the flap is
reversed).
01 Normal
15 (25) 5
02 Individual
: Factory setting
Control by remote controller
Operation
RXYMQ4AVMK
ON
OFF
1 2 3 4 1 2 3 4
DS2 DS1
RXYMQ4-6AYFK
ON
OFF
1 2 3 4 1 2 3 4
DS1 DS2
(1)
Microcomputer
normal monitor
(HAP)
Connection terminal
for transmission use
The figure below shows the required position of the DIP switches on spare PCB. Change DIP
switches at time of power disconnected.
Application model The setting method (represents the position of switches)
RXYMQ4AVMK Set DS1-2, DS1-4, DS2-1, and DS2-3 to ON.
ON
OFF
1 2 3 4 1 2 3 4
DS2 DS1
ڦ5(029,1*0$,13&%
ە5(029(7+(&29(56&5(:6%()25(5(029,1*7+((/(&75,&$/&20321(17
127'2,1*620$<'$0$*(7+(5()5,*(5$173,3(
ە5(3/$&(7+(*5($6(217+(+($76,1.:,7+1(:*5($6(
127'2,1*620$<&$86(7+(3&%72)$,/'8(72,168)),&,(17&22/,1*
㻱㻸㻱㻯㻚㻌㻯㻻㻹㻼㻻㻺㻱㻺㼀㻿
㻾㻱㻹㻻㼂㻭㻸 㻹㻻㼁㻺㼀㻵㻺㻳㻌㻼㻸㻭㼀㻱
㻲㻵㼄㻭㼀㻵㻻㻺
㻾㻱㻲㻾㻵㻳㻱㻾㻚㻌㻼㻵㻼㻱 㻿㻯㻾㻱㼃㻌㻮
㻲㻵㼄㻭㼀㻵㻻㻺 㻯㻻㼂㻱㻾
㻿㻯㻾㻱㼃㻌㻭
㻰㻵㻿㼀㻾㻵㻮㼁㼀㻱㻌
㼀㻴㻱㻌㻳㻾㻱㻭㻿㻱
㻡
㻭㻿㻌㻱㼂㻱㻺㻸㼅㻌
㻭㻿㻌㻼㻻㻿㻵㻮㻸㻱
㼀㻵㻳㻴㼀㻱㻺㻵㻺㻳㻌㼀㻻㻾㻽㼁㻱㻌㻝㻚㻡㻥s㻜㻚㻞㻺㼙
C: 3P473957
Monitor mode
Normal mode:
Blank: If no abnormality is detected and initialization of communication was completed.
Flashing combination of letter and number (4 digits): Error code detected by outdoor
control or trouble by communication.
Setting mode: Used to make changes to operating status, performance settings or address
setting.
Monitor mode: Used to verify contents of settings, quantity of units, current value of some
parameters during operation of outdoor unit.
Mode changing procedure can be selected using the MODE (BS1) button as shown
below:
Press and hold the
MODE (BS1) button Press the MODE
for 5 seconds or more (BS1) button once
Setting mode Normal mode Monitor mode
Press the MODE
SEG1 SEG2 SEG3 (BS1) button once SEG1 SEG2 SEG3 SEG1 SEG2 SEG3
Selection between normal mode, monitor mode (Mode 1) and setting mode (Mode 2).
SEG1 SEG2 SEG3
Press MODE (BS1) button for more than 5 sec. Normal mode Press MODE (BS1) button once.
(Initial condition)
Blinking
Initializing
ON
OFF
Initializing completed
Normal
Example: E7-01
Normal
To enter monitor mode, press the
MODE (BS1) button while in BS1
normal mode.
MODE
BS3
Checking for description of data
Press the RETURN (BS3) button to RETURN
confirm.
The current state of monitoring item will
appear on the 7 segment display.
BS3
RETURN
Press the RETURN (BS3) button to
return to the initial state of monitor mode.
BS1
MODE
Press the MODE (BS1) button to return Normal
to normal mode.
19 Description of error 1. 1 9
(2 cycles before)
1: Numbers in the "No." column represent the number of times to press the BS button.
2: Number of indoor units connected: represents the number of indoor units connected to a
single outdoor system.
3: Number of outdoor units: represents the number of outdoor units connected to a single
DIII-NET that is a communication line.
4: Number of terminal units: represents the number of indoor units connected to a single
DIII-NET that is a communication line.
Item Contents
No. Display Display
1 Description Description
SEG SEG SEG SEG SEG SEG
1 2 3 1 2 3
Description of retry Refer to information in Error Code via
23 1. 2 3
(latest) Outdoor Unit PCB on page 152.
Description of retry
24 1. 2 4
(1 cycle before)
25 Description of retry 1. 2 5
(2 cycles before)
Number of outdoor units Possible 0-63
0
28 connected in a multi 1. 2 8 6 3
system
Outdoor unit PCB status 0: judgment in
0
judgment process
32 1. 3 2 1
1: normal 2
2: abnormal
Number of abnormal Possible 0-15 0
33 status judgment outdoor 1. 3 3 1 5
unit PCB
Number of connected RA Possible 0-63 0
38 indoor (through BP unit) 1 3 8 6 3
Cooling comfort setting Possible 0-3 0
40 1. 4 0 3
Heating comfort setting Possible 0-6 0
41 (see mode 2 No. 9) 1 4 1 6
High pressure (MPa) Possible 0.1-9.99 0. 1 0
42 1. 4 2 9. 9 9
BS1
SET
BS3
RETURN
Selection of setting conditions
Default
Press the SET (BS2) button to select
the setting condition you want.
SET
BS3
RETURN
Press the RETURN (BS3) button to
return to the initial state of setting
mode.
BS3
RETURN
BS1
Item Contents
Display Display
No.
Description SEG SEG SEG Description SEG SEG SEG
1 2 3 1 2 3
Low noise/ Used to make address setting for low Address:
2 demand address noise/demand address. 2. 0 2 0~ 0
31 3 1
Indoor fan Used to force the fan of indoor unit to H Normal operation 0
5 2. 0 5
forced H tap. Indoor fan H 1
Forced Used to force all indoor units to operate Normal operation 0
6 2. 0 6
thermostat ON forced thermostat ON. Forced thermostat ON 1
Te setting Used to make setting of targeted Standard: 6°C 2
evaporating temperature for cooling High sensible: 7°C 3
operation. High sensible: 8°C 4
8 2. 0 8
High sensible: 9°C 5
High sensible: 10°C 6
High sensible: 11°C 7
Tc setting Used to make setting of targeted Low sensible: 41°C 1
9 condensing temperature for heating 2. 0 9 Standard: 43°C 3
operation. High sensible: 46°C 6
Defrost selection Used to adjust the defrost start Defrost IN –2° 0
10 setting temperature of outdoor coil, to initiate 2. 1 0 Normal 1
defrosting earlier/later. Defrost IN +2° 2
Eco setting is available from an external input. Unavailable 0
When this configuration is set, it is not possible to turn the Low noise level input 1
Eco refrigerant control ON/OFF using the remote Demand input 2
11 2. 1 1
controller. Also, depending on the settings, low noise
operation or demand operation may not be performed
using the external control adaptor.
External low Used to receive external low noise or Input LNO/DE
12 noise/demand demand signal. 2. 1 2 OFF 0
setting ON 1
AIRNET Used to set address of AIRNET Address:
13 address 2. 1 3 0~ 0
63 6 3
High EST mode High external static pressure mode ON (Auto adjust and 0
for outdoor fan setting re-judge)
OFF (Auto adjust without 1
18 2. 1 8 re-judge)
Forced level 0 2
Forced level 1 3
Forced level 2 4
Refrigerant Used to set the system to refrigerant Refrigerant recovery
21 recovery/ recovery mode (without compressor 2. 2 1 OFF 0
vacuuming run). ON 1
Automatic Automatic night-time low noise OFF 0
night-time low operation. Time for the operation is Level 1 1
22 noise operation subject to the start and end time 2. 2 2 Level 2 2
settings. Level 3 3
Used to set Eco mode invalid. Valid 0
When this configuration is set, it is not possible to turn the Invalid for cooling 1
23 Eco mode ON/OFF using the external control adaptor. 2. 2 3 Invalid for heating 2
Invalid 3
Item Contents
Display Display
No.
Description SEG SEG SEG Description SEG SEG SEG
1 2 3 1 2 3
External Low noise level when the external low Level 1 1
25 night-time low noise signal is input at option
2. 2 5
Level 2 2
noise operation DTA104A61. Level 3 3
level
Automatic Time to start automatic “night-time low About 8:00 PM 1
night-time low noise” operation. (“Night-time low noise” About 10:00 PM 2
26 2. 2 6
noise operation level setting should also be made.) About 12:00 AM 3
start
Automatic Time to stop automatic “night-time low About 6:00 AM 1
night-time low noise” operation. (“Night-time low noise” About 7:00 AM 2
27 2. 2 7 About 8:00 AM 3
noise operation level setting should also be made.)
stop
Power transistor Used to troubleshoot DC compressor.
check Inverter waveforms are output without
wire connections to the compressor. It is 2. 2 8
OFF 0
28
useful to determine whether the relevant ON (10 Hz) 1
trouble has resulted from the
compressor or inverter PCB.
Capacity priority Cancel the low noise level control if
29 capacity is required while low noise 2. 2 9 OFF 0
operation or night-time low noise ON 1
operation is in progress.
Demand 1 Used to make a change to the targeted Level 1 (60%) 1
setting power consumption level when the Level 2 (65%) 2
demand 1 control signal is inputted. Level 3 (70%) 3
Level 4 (75%) 4
30 2. 3 0 Level 5 (80%) 5
Level 6 (85%) 6
Level 7 (90%) 7
Level 8 (95%) 8
Demand 2 Used to use a targeted power current Level 1 (40%) 1
31 setting level when the demand 2 control signal 2. 3 1 Level 2 (50%) 2
is inputted. Level 3 (55%) 3
Constant Used to set constant demand 1 or 2 OFF 0
32 demand setting control without inputting any external 2. 3 2 Demand 1 (Mode 2-30) 1
signal. Demand 2 (Mode 2-31) 2
Indoor fan upper Forced fan speed to low indoor units Cooling and heating 0
34 limit thermostat ON if total indoor 2. 3 4 Heating only 1
thermostat-ON > index 130. Never 2
Tc target setting To change Tc target cooling. Higher 0
35 2. 3 5 Lower 1
Do not use ~7
Outdoor fan Outdoor fan noise countermeasure (limit Standard 0
42 fan speed). 2. 4 2 Mode A 1
Mode B 2
Defrost four way At time defrost starts/end. Capacity priority 0
43 2. 4 3
valve Compressor OFF 1
Defrost Priority during defrost. Indoor priority 0
50 2. 5 0
Defrost priority 1
Item Contents
Display Display
No.
Description SEG SEG SEG Description SEG SEG SEG
1 2 3 1 2 3
VRTsmart Used to change upper limit of target Low 1 0
control evaporation temperature in VRTsmart Low 2 1
Te upper limit control. Low 3 2
Low 4 3
76 2. 7 6 Low 5 4
Low 6 5
Standard 6
High 7
VRTsmart Used to change lower limit of target Low 0
control condensation temperature in VRTsmart Standard 1
Tc lower limit control. High 1 2
High 2 3
77 2. 7 7 High 3 4
High 4 5
High 5 6
High 6 7
VRT control Used to change upper limit of target Standard 4
78 Te upper limit evaporation temperature in VRT 2. 7 8 High 6
control.
VRT control Used to change lower limit of target Standard 2
79 Tc lower limit condensation temperature in VRT 2. 7 9 Low 3
control.
Cooling comfort setting ECO 0
Mild 1
81 2. 8 1
Quick 2
Powerful 3
Heating comfort setting ECO 0
82 2. 8 2 Mild 1
Quick 2
Powerful 3
Mode 2-8: Te target temperature for cooling operation. Change the setting in function of
required operation method during cooling. (Mode 2-23 should be 1 or 3)
Default value: 2 (Te target: 6°C). The refrigerant temperature is fixed to average indoor
evaporating temperature of 6°C, independent from the situation. It corresponds to the
standard operation which is known and can be expected from/under previous VRV
systems.
Set 3-7: High Sensible. The refrigerant temperature is set higher/lower in cooling
compared to basic operation. The focus under high sensible mode is comfort feeling for
the customer. The selection method of indoor units is important and has to be considered
as the available capacity is not the same as under basic operation. Activate this setting
under cooling operation.
Mode 2-8 Te target
2 6°C (default)
3 7°C
4 8°C
5 9°C
6 10°C
7 11°C
Mode 2-11: Eco level setting for Eco mode via External control adaptor (Optional).
Mode 2-11 Meaning Level
0 Inactive (default) —
Eco mode active by low noise
1 Standard
terminal short-circuit
Eco mode can be activated by short circuit the terminal on External control adaptor
(Optional) according to 2-11 setting. (2-23 should be “0”)
This unit can operate with “Te fix control” and “Eco mode”.
Eco mode means “VRT” & “VRTsmart” control
If the terminal on external control adaptor is not connected by short circuit and 2-11 is not
0, the system operates according to 2-8 setting.
Mode 2-12: Enable input “DTA104A61/62”: enable the low noise function and/or power
consumption limitation. If the system needs to be running under low noise operation or under
power consumption limitation conditions when an external signal is sent to the unit, this
setting should be changed. This setting will only be effective when the optional external
control adaptor for outdoor unit (DTA104A61/62) is installed and the address set by DIP
switches on DTA104A61/62 corresponds to the address set on the outdoor unit(s) – set 2-.
Default value: 0.
To enable input from DTA104A61/62, change the item 2-12 to 1.
Mode 2-22: Selection automatic night-time low noise operation level. The outdoor can
switch automatically to a pre-set night-time low noise operation level during night-time
judgment.
Default value: 0. Auto night-time low noise operation not active.
Set 1: use level 1.
Set 2: use level 2.
Set 3: use level 3.
Set period: refer to set the item 2-26 for start time and the item 2-27 for end time.
Mode 2-25: Night-time low noise operation level when using external input to optional board
DTA104A61/62.
If the system needs to be running under low noise operation conditions when an external
signal is sent to the unit, this setting defines the level of low noise that will be applied.
This setting will only be effective when the optional external control adaptor for outdoor
unit DTA104A61/62 is installed and the setting is enabled (mode 2-12-1).
When night-time low noise operation is actually performed, conditions can be checked
via mode 1-1.
The night-time low noise operation will not be performed in one of following conditions:
Startup of system, or
During oil return, or
30 minutes after external input opened, or
Capacity priority setting is active (refer to mode 2-29-1) and limit condition is met.
Default value: 2 (level 2)
Night-time low noise operation level can be selected to 1, 2, or 3 (field setting 2-25-1, 2,
3).
Mode 2-26: Start time automatic night-time low noise operation. When the auto
night-time low noise operation is active (refer to field setting 2-22) outdoor will start when
start time is reached. The time judgment is taken from outdoor air tendency.
52 dB(A)
Night
quiet mode
Mode 2-27: Stop time automatic night-time low noise operation. When the auto
night-time low noise operation is active (refer to field setting 2-22), outdoor unit will stop the
night-time low noise operation level automatically when stop time is reached.
Default value: 3 (8:00 AM)
Field setting 1: 6:00 AM, 2: 7:00 AM
Mode 2-28: Power transistor check mode. To evaluate the output of the power transistors.
Use this function in case error code is displayed related to defective inverter PCB or
compressor is locked.
Default value: 0. Power transistor check mode is not active.
Field setting 1: Power transistor check mode is active.
Function:
Inverter circuit gives output of 10 rps in sequence by all 6 transistors. Remove the
U/V/W terminals of the compressor, and connect to the inverter checker module. If all
6 LEDs blink, the transistors switch correctly.
When the power transistor check mode is set back to 0 (default), after turning off the
power supply, 2 LEDs will light up to indicate discharge of the DC voltage.
Wait until the LEDs are OFF before returning fasten terminals back to the compressor
terminals.
Minimum requirements to refer to the result on the inverter checker module:
Line (for RXYMQ4AVMK) or all 3 phases (for RXYMQ4-6AYFK) and neutral are
available, and
Inverter circuit is active. Check if the green LED “HBP” on the main PCB (for
RXYMQ4AVMK) or "HAP" on the inverter PCB (for RXYMQ4-6AYFK) is blinking
normally (approximately 1/second). If LED is OFF, need to exit the “standby mode” of
the inverter:
Disconnect and reconnect power supply control PCB, or
Forced thermostat ON condition, or
Make shortly set 2-6-1 (forced thermostat ON indoor), or
2-20-1 (manual refrigerant charge).
Once the LED is blinking on the PCB, change related setting immediately back to set
0 to deactivate related function.
Diode module generates the required 300 VDC (for RXYMQ4AVMK) or 500 VDC (for
RXYMQ4-6AYFK).
Cautions:
To stop the power transistor check mode, change setting to default 2-28-0.
Output to U/V/W will also stop when outdoor unit main PCB decides standby mode of
inverter circuit.
Below time graphs show the different steps during the power transistor check mode.
Switching sequence during power transistor check mode:
RXYMQ4AVMK
Check 1: AC power input (L, N on X1M: power supply terminal block) around 220 V
Check 2: DC voltage on inverter circuit capacitor (C+,C–) increases to around 310 V.
Check 3: VDC = 1.42 × VAC power supply (calculation from Check 1 and Check 2)
Check 4: AC U/V/W 10 rps intermediate (at fasten U/V/W) around 10 V
Check 5: DC voltage drop (discharge inverter circuit capacitor DC) check difference between “C+, C–” within 2
LED (V phase) brightness reduce till off.
RXYMQ4-6AYFK
∗Night-time
Level 1
Mode 2-30: Power consumption limitation level 1. If the system needs to be running
under power consumption limitation conditions via the external control adaptor for outdoor
unit DTA104A61/62. This setting defines the level power consumption limitation that will be
applied for level 1. The level is according the table.
Default: 3 (70%)
Field setting:
Mode 2-30 current limit set (%)
1 60
2 65
3 70 (default)
4 75
5 80
6 85
7 90
8 95
Mode 2-31: Power consumption limitation level 2. If the system needs to be running
under power consumption limitation conditions via the external control adaptor for outdoor
unit DTA104A61/62. This setting defines the level power consumption limitation that will be
applied for level 2. The level is according the table.
Default: 1 (40%)
Field setting:
Mode 2-31 current limit set (%)
1 40 (default)
2 50
3 55
Mode 2-32: Forced, all time, power consumption limitation operation (no external control
adaptor is required to perform power consumption limitation).
If the system always needs to be running under power consumption limitation conditions,
this setting activates and defines the level power consumption limitation that will be
applied continuously. The level is according to the table.
Default value:0 (OFF).
Mode 2-81: Cooling comfort setting. The comfort level is related to the timing and the
effort (power consumption) which is put in achieving a certain room temperature by changing
temporally the refrigerant temperature to different values in order to achieve requested
conditions more quickly.
Default value: 1 (Mild). Undershoot during cooling operation is allowed compared to the
requested refrigerant temperature, in order to achieve the required room temperature
very fast. The undershoot is not allowed from the startup moment. The startup occurs
under the condition which is defined by the operation mode. In case of cooling operation
the evaporating temperature is allowed to go down to 6°C on temporary base depending
on the situation. When the request from the indoor units becomes more moderate, the
system will eventually go to the steady state condition which is defined by the operation
method above. The startup condition is different from the powerful and quick comfort
setting.
Field setting:
0: Eco. The original refrigerant temperature target, which is defined by the Te setting
(field setting 2-8) in cooling mode, is kept without any correction, unless for protection
control.
Te 3°C
time
Mode 2-82: Heating comfort setting. The comfort level is related to the timing and the effort
(power consumption) which is put in achieving a certain room temperature by changing
temporally the refrigerant temperature to different values in order to achieve requested
conditions more quickly.
Default value: 1 (Mild). Overshooting during heating operation is allowed compared to
the requested refrigerant temperature, in order to achieve the required room temperature
very fast. The overshoot is not allowed from the startup moment. The startup occurs
under the condition which is defined by the operation mode. In case of heating operation
the condense temperature is allowed to go up to 46°C on temporary base depending on
the situation. When the request from the indoor units becomes more moderate, the
system will eventually go to the steady state condition which is defined by the operation
method above. The startup condition is different from the powerful and quick comfort
setting.
Field setting:
0: “Eco”. The original refrigerant temperature target, which is defined by the Tc setting
(field setting 2-9) in heating mode, is kept without any correction, unless for protection
control.
2: “Quick”. Overshoot during heating operation is allowed compared to the requested
refrigerant temperature, in order to achieve the required room temperature very fast.
The overshoot is allowed from the start up moment. In case of heating operation the
condense temperature is allowed to go up to 46°C on temporary base depending on
the situation. When the request from the indoor units becomes more moderate, the
system will eventually go to the steady state condition which is defined by the
operation method above.
3: “Powerful”. The overshoot is allowed from the start up moment. In case of heating
operation the condense temperature is allowed to go up to 49°C on temporary base
depending on the situation. This setting is used in conjunction with setting 2-9.
Mode 2-83: Allocation of cool/heat master logic. When system contains VRV DX indoor
and RA indoor (through BP units), it is required to assign the cool/heat change over logic to
follow.
Default value: 1. RA cool/heat master logic. Any RA indoor unit that is switched first, is
assigned as cool/heat master as long this unit is in operation (regardless thermostat
status). Only when this indoor unit is switched OFF operation (by remote controller),
other indoor unit can become cool/heat master:
Priority is given to indoor unit operating in the same mode as the previous cool/heat
master switched OFF operation.
Only no more indoor unit operate in the same mode as the previous cool/heat master,
other RA indoor unit can become cool/heat master to switch to the other operation
mode.
RA indoor unit that is operating, but demanding the other operation mode set by the
cool/heat master, enters the “stand-by mode”: operation LED blinks.
VRV indoor unit change the operation mode immediately when outdoor unit receives
change of operation mode from the current cool/heat master RA indoor unit.
Field Setting 0: VRV cool/heat master logic.
At time of first startup, or when cool/heat master was released, one of connected VRV
DX indoor unit can be assigned cool/heat master. The symbol “locked cool/heat
selector” blinks. In case of wireless controller kit is used, the green clock LED
blinks on the receiver.
Confirm cool/heat master to a VRV DX indoor unit: press once the cool/heat selector
button
Mode 2-84: Initial opening electronic expansion valve BP unit heating thermostat-ON:
Default value: 1 (500 pulse)
Field setting 0: 400 pulse, 2: 600 pulse, 3: 300 pulse.
Mode 2-90: Indoor unit without power U4 error generation. In case an indoor unit needs
maintenance or repair on the electric side, it is possible to keep the rest of the VRV DX
indoor units operating without power supply to some indoor unit(s).
Default value: 0. Not active.
Field setting 1: Possible to operate system when some indoor units are temporary
without power supply. The following conditions must be fulfilled:
Maximum equivalent piping length of the farthest indoor less than 120 m.
Index indoor units power simultaneously less than 30% of the nominal outdoor.
Total capacity is less than 30% of the nominal one of the outdoor unit.
Operation time is limited to 24 hours period.
It is recommended to shut down connected indoor units at the same floor.
Not possible to use service mode operation (e.g. recovery mode).
Backup operation has priority over this special feature.
Not possible to use when the indoor unit electronic expansion valve is defective.
Not possible to use with systems that include BP units.
It is necessary to wait for 10 min. before shutting down the connected indoor units
after indoor units operation is stopped.
Mode 2-96: Eco level setting for Eco mode by main PCB
Default value: 0
Mode 2-96 Eco level setting
0 OFF (default)
1 Low
2 Standard
When Eco mode is set as unavailable (Outdoor unit external control adaptor is
unnecessary)
Eco mode control is unavailable during cooling operation.
When the Eco level of Eco mode control is set as Standard/Low or Eco mode control is
set as unavailable by external control adaptor
Setting description Setting mode
Item Condition Description External control adaptor Outdoor unit PCB
Eco level Standard Eco level set as Short-circuit the low Set mode 2-11 to
Standard by low noise noise level terminal in Eco setting by low noise
level the terminal TeS1 level input
Eco level set as Short-circuit the demand Set mode 2-11 to
Standard by demand input terminal 3 – C in Eco setting by demand
control the terminal TeS1 input
Low Eco level set as Low Short-circuit the demand
by demand control input terminal 2 – C in
the terminal TeS1
Eco control unavailable Eco control set as Open the low noise Set mode 2-11 to
unavailable by low level terminal in the Eco setting by low noise
noise level terminal TeS1 level input
Eco control set as Open the demand Set mode 2-11 to
unavailable by input terminal in the Eco setting by demand
demand control terminal TeS1 input
1. Connect the external control adaptor and short-circuit the input terminal TeS1 if necessary.
2. Set mode 2-11 (External Eco Setting) to Eco setting by low noise level input or Eco
setting by demand input according to the short-circuited terminal.
1 The lowest temperature between the above and mode 2-76 VRTsmart control Te upper limit
is set.
2 The highest temperature between the above and mode 2-77 VRTsmart control Tc lower limit
is set.
A. When night-time low noise operation is carried out by external contact (with the use of
the external control adaptor for outdoor unit)
1. Connect external control adaptor for outdoor unit and short circuit terminal of night-time low
noise operation (Refer below figure). If carrying out demand or low noise input, connect the
adaptor’s terminals as shown below. External control adaptor for outdoor unit Host computer
Outside wiring indicated monitor panel by dotted line or demand controller
F1 X
F2 X
P3 X
P4 X
2. While in setting mode 2, set the item 2-12 (External low noise or demand setting) to ON.
3. If necessary, while in setting mode 2, select an external low noise level for the item 2-25.
4. If necessary, while in setting mode 2, set the item 2-29 (Capacity priority setting) to ON. (If
the condition is set to ON, when the air conditioning load reaches a high level, the low noise
operation command will be ignored to put the system into normal operation mode.)
B. When night-time low noise operation is carried out automatically (External control
adaptor for outdoor unit is not required)
1. While in setting mode 2, select a night-time low noise operation level for the item 2-22.
2. If necessary, while in setting mode 2, select a starting time of night-time low noise operation
(i.e., 8:00 PM, 10:00 PM, or 12:00 AM) for the item 2-26. (Use the starting time as a guide since
it is estimated according to outdoor temperatures.)
3. If necessary, while in setting mode 2, select an ending time of night-time low noise operation
(i.e., 06:00 AM, 07:00 AM, or 08:00 AM) for the item 2-27. (Use the ending time as a guide since
it is estimated according to outdoor air temperatures.)
4. If necessary, while in setting mode 2, set the item 2-29 (Capacity priority setting) to ON. (If the
condition is set to ON, when the air conditioning load reaches a high level, the system will be put
into normal operation mode even during night-time.)
Level 3
Operation sound level set with
night-time low noise operation
setting
Level 3 The compressor operates at Set the item 2-32 to Demand 2, and the item
55% or less of rating. 2-31 to Level 3.
Demand 3 — Forced thermostat OFF Short circuit "3" and "C". —
: However the demand operation does not occur in the following operation modes.
(1) Startup control
(2) Oil return control
(3) Defrost control
(4) Pump down residual control
If carrying out demand or low noise input, connect the adaptor’s terminals as shown below.
F1 X
F2 X
P3 X
P4 X
A. When the demand operation is carried out by external contact (with the use of the
external control adaptor for outdoor unit).
1. Connect external control adaptor for outdoor unit and short circuit terminals as required
(Refer to the figure above).
2. While in setting mode 2, set the item 2-12 (External low noise or demand setting) to ON.
3. If necessary, while in setting mode 2, select a demand 1 level for the item 2-30.
B. When the constant demand operation is carried out. (Use of the external control
adaptor for outdoor unit is not required.)
1. While in setting mode 2, set the item 2-32 (Constant demand setting) to Level 1.
While in setting mode 2, select a demand 1 level for the item 2-30.
Power consumption
Rated
Demand level 1 Demand level 2 Demand level 3 The power
instructing instructing instructing consumption
80% during the
demand level 1
70% instructing can be
60% set with the
Power consumption set by "Demand 1 level
"Demand 1 level setting". setting".
40% ("70% of rated
power
consumption" has
been set at
Forced thermostat OFF factory.)
(Fan operation)
70%
60% The power consumption set with
#Demand level #Demand level
"Demand 1 level setting". 2 instructing 3 instructing
40%
#During constant demand
operation, when the
Forced thermostat OFF external demand
(Fan operation) instruction is received, the
instruction with higher
demand level has the
precedence.
3. Test Operation
3.1 Checks before Test Operation
Before carrying out a test operation, proceed as follows:
Step Action
Make sure the voltage at the primary side of the safety breaker is:
1 220-240 V ± 10% for 1-phase units;
380-415 V ± 10% for 3-phase units.
2 Fully open the liquid and the gas stop valve.
3.2 Checkpoints
To carry out a test operation, check the following:
Check that the temperature setting of the remote controller is at the lowest level in cooling
mode or use test mode.
Go through the following checklist:
Checkpoints Cautions or warnings
Are all units securely installed? Dangerous for turning over during storm
Possible damage to pipe connections
Is the earth wire installed according to the applicable Dangerous if electric leakage occurs
local standard?
Are all air inlets and outlets of the indoor and outdoor Poor cooling
units unobstructed? Poor heating
Does the drain flow out smoothly? Water leakage
Is piping adequately heat-insulated? Water leakage
Have the connections been checked for gas Poor cooling
leakage? Poor heating
Stop
Is the supply voltage conform to the specifications on Incorrect operation
the name plate?
Are the cable sizes as specified and according to Damage of cables
local regulations?
Are the remote controller signals received by the No operation
unit?
Warning Be sure to inform other installers or attach the front panel well before leaving with the power
supply turned on for the outdoor unit.
Before powering ON
Protect the electronic components with insulating tape in accordance with the Service
Precautions label attached to the front panel.
All indoor units connected with the outdoor unit will operate automatically after powering on.
To ensure safety, check the indoor unit installation has been completed.
The test operation is automatically carried out, the outdoor unit display will indicate t01 and
the indication "Test operation" and "Under centralized control" will display on the user
interface of indoor units.
Steps during the automatic system test run procedure:
t01: control before start up (pressure equalization)
t02: cooling start up control
t03: cooling stable condition
t04: communication check
t05: stop valve check
t06: pipe length check
t07: refrigerant amount check
t08: in case [2-88]=0, detailed refrigerant situation check (RXYMQ4AVMK only)
t09: pump down operation
t10: unit stop
If the automatic refrigerant charge function has been used, t07 and t08 will not be displayed
during the test operation, as they have already been checked during automatic refrigerant
charge operation.
During the test operation, it is not possible to stop the unit operation from a user interface. To
abort the operation, press BS3. The unit will stop after ±30 seconds.
5. Check the test operation results on the outdoor unit segment display.
Normal completion: no indication on the segment display (idle)
Abnormal completion: indication of error code on the segment display
Take actions for correcting the abnormality. When the test operation is fully completed, normal
operation will be possible after 5 minutes.
6. Be sure to attach the front panel of the outdoor unit after test operation is completed.
OFF
Light up
Normal Abnormal
Initialization in
progress
(∗) The master unit is the outdoor unit to which the transmission wiring for
the indoor units is connected.
The other outdoor units are slave units.
Part 6
Service Diagnosis
minute before entering service mode again. In case of continuous execution, the outdoor unit
PCB may sometimes display an error code. If any error codes are displayed, press the
RETURN (BS3) button. If performing the above operation still does not eliminate the error,
reconnect the unit to the power supply.
3.80 3.70
3.60 3.50
3.40 3.30
3.20 3.10
3.00 2.90
2.80 2.70
2.60 2.50
2.40 2.30
2.20 2.10
2.00 1.90
1.80 1.70
1.60 1.50
1.40 1.30
1.20 1.10
1.00 0.90
0.80 0.70
0.60 0.50
0.40 0.30
0.20 0.10
0.00 –0.10
–50 –40 –30 –20 –10 0 10 20 30 40 50 60
Temperature ˚C
2. Symptom-based Troubleshooting
Symptom Supposed Cause Countermeasure
1 The system does not start operation at all. Blowout of fuse(s) Turn Off the power supply and then
replace the fuse(s).
Cutout of breaker(s) • If the knob of any breaker is in its
OFF position, turn ON the power
supply.
• If the knob of any circuit breaker is
in its tripped position, do not turn
ON the power supply.
ON
Knob
Tripped
OFF
Circuit breaker
2 Individual airflow direction setting different from the actual Check the "Louver operation different from setting" error
airflow direction diagnosis.
3 While not operating, the louver does not close completely. Turn off the circuit breaker and then turn it on again.
The remote controller menu does not display energy saving
operating mode for when people are not present.
Refer to "Infrared presence/floor sensor error (CE)" in
The remote controller menu does not display the stop function troubleshooting.
4
for when people are not present.
The remote controller menu does not display the automatic
draft prevention function.
The menu does not display the eco-friendly display function. No defect.
5
Set the clock.
During cooling and dry operation, the louver automatically No defect.
6 switches from horizontal (P0) to one-level downward (P1). When relative ambient humidity is higher, automatic louver
control will be activated.
During heating operation, the use of an airflow block will not No defect.
7 cause other louvers to turn downward (P4). In heating operation, if an airflow block is set, then the air outlet
control outside the airflow block will be within the range P0-P3.
When using airflow block, the airflow block will be routinely No defect.
8
lifted (become horizontal) during heating operation. Set louver to horizontal (P0) during thermostat OFF.
Although people are not present, the infrared presence sensor Check if there are any objects that generate temperature
detects human presence. change when moving.
For example:
· An electric heater with swing function
9
· Doors, curtains, blind switches
· Output of paper from a fax machine or a printer
· Turning on/off of incandescent lights
· Moving objects
Although people are present, the infrared presence sensor fails Check for the following conditions.
to determine their presence. · Lack of movement
10 · Facing away from the sensor
· Little skin exposed
· Slight movement in a place far from the sensor
Large difference between floor temperature and actual Check for the following conditions.
temperature · Sensor detection zone affected by solar radiation
· High or low temperature objects in the sensor detection zone
11 · Large difference between floor temperature and temperature
of the living space
· Sensors installed near walls may be affected by wall
temperature.
Error diagnosis of "Louver operation different from setting"
Connect to the
connector
correctly before
action verification.
NO
1 MΩ or more? Defective local power supply
NO
1 MΩ or more? Compressor abnormality
Screen
Operation lamp
Menu/Enter button
FXFSQ25ARV1
Take the corrective action specific to the RXYMQ4AVMK Applicable
model names
model.
35
7
24
6
1
1. Press the INSPECTION button to select the inspection mode “ ”.
0 appears on display and blinks.
“UNIT No.” appears.
2. Press PROGRAMMING TIMER button and change the unit number.
Press to change the unit number until the indoor unit beeps and perform the following
operation according to the number of beeps.
Number of beeps
3 short beeps.............Perform all steps from 3 to 6.
1 short beep .............Perform 3 and 6 steps.
1 long beep .............Normal state
3. Press OPERATION MODE SELECTOR button.
0 on the left-hand of the error code blinks.
4. Press PROGRAMMING TIMER button and change the error code.
Press until the indoor unit beeps twice.
5. Press OPERATION MODE SELECTOR button.
0 on the right-hand of the error code blinks.
6. Press PROGRAMMING TIMER button and change the error code.
Press until the indoor unit makes a long beep.
The error code is fixed when the indoor unit makes a long beep.
7. Reset of the display
Press the OPERATION MODE SELECTOR button to get the display back to the normal
state.
The error codes for forced stop outdoor or retry are item:
17, 18, 19: description of error (outdoor system stopped operation).
23, 24, 25: description of retry.
SEG1 SEG2 SEG3
Normal
MODE
Displaying check 1
BS3
BS1
The tables on the following pages show a full list of possible error codes displayed on the 3
digit 7 segment display of the outdoor unit. The error code contains an upper and lower digit.
To scroll between upper and lower error digit, use the SET (BS2) button.
The errors cover problems detected in the outdoor unit or the communication.
Errors detected on the indoor unit are not shown on the outdoor display. For inspecting error
code on indoor unit, please consult:
Display of the remote controller connected to the indoor units.
If there are no remote controllers, there should be a central control device set up. Prior to
start up, make the necessary group number settings on each indoor unit.
Operation Reference
Error code Description
lamp page
Outdoor Unit E1 l Outdoor unit main PCB abnormality 194
Current leakage detection 195
E2 l
Missing of leakage detection core 196
E3 l Activation of high pressure switch 197
E4 l Activation of low pressure sensor 199
E5 l Compressor motor lock 200
E7 l Outdoor fan motor abnormality 202
E9 l Electronic expansion valve coil abnormality 205
F3 l Discharge pipe temperature abnormality 206
F4 l Wet alarm 208
F6 l Refrigerant overcharged 210
H3 l Harness abnormality (between outdoor unit main PCB and inverter PCB) 211
H5 l OL activation (compressor overload) 212
H7 l Outdoor fan PCB abnormality 214
H9 l Outdoor air thermistor (R1T) abnormality 215
J3 l Discharge pipe thermistor (R21T) abnormality 215
J5 l Suction pipe thermistor (R3T) abnormality 215
J6 l Heat exchanger deicer thermistor (R7T) abnormality 215
J7 l Subcooling heat exchanger liquid pipe thermistor (R5T) abnormality 215
J8 l Heat exchanger liquid pipe thermistor (R4T) abnormality 215
J9 l Subcooling heat exchanger gas pipe thermistor (R6T) abnormality 215
JA l High pressure sensor abnormality 217
JC l Low pressure sensor abnormality 218
L1 l Inverter circuit abnormality 219
L2 l Momentary power failure during test operation 221
L4 l Inverter radiation fin temperature rise abnormality 222
L5 l Compressor instantaneous overcurrent 224
L8 l Compressor overcurrent 226
L9 l Compressor startup abnormality 228
Troubleshooting
Error code
Description of error Diagnosis
Infrared floor sensor error An abnormality other than the ones mentioned above has been
detected.
CE - 04
Check if the temperature nearby the sensor is too high, and if there is
any foreign matter that may cause noise.
U4 - 01 Indoor-Outdoor transmission error Refer to the U4 flowchart.
UA - 13 Refrigerant type error The type of refrigerant used for the indoor unit is different from that
used for the outdoor unit.
Not applicable for self-cleaning decoration An outdoor unit is not applicable for the self-cleaning decoration panel
UA - 15 panel (when the self-cleaning decoration is connected.
panel is mounted)
As there are various combinations of indoor and outdoor units, the sub codes of A0 - A3 are not
shown in this table.
H3 - 02 Connection error between main PCB and inverter PCB Refer to the H3 flowchart and make a diagnosis based
on the Error code shown to the left.
Defective overload protector for M1C (Q1M) Refer to the H5 flowchart and make a diagnosis based
H5 - 01
on the Error code shown to the left.
Defective fan PCB for M1F Refer to the H7 flowchart and make a diagnosis based
H7 - 21
on the Error code shown to the left.
H9 - 01 Defective outdoor air thermistor (R1T) Refer to the H9 flowchart and make a diagnosis based
on the Error code shown to the left.
J3 - 16 Defective discharge pipe thermistor (R21T): Open
Refer to the J3 flowchart and make a diagnosis
J3 - 17 Defective discharge pipe thermistor (R21T): Short
based on the Error code shown to the left.
J3 - 56 Discharge pipe warning
Defective suction pipe thermistor (R3T) Refer to the J5 flowchart and make a diagnosis
J5 - 01 of the thermistor based
on the Error code shown to the left.
Defective heat exchanger deicer thermistor (R7T) Refer to the J6 flowchart and make a diagnosis
J6 - 01 of the thermistor based
on the Error code shown to the left.
Defective subcooling heat exchanger liquid pipe Refer to the J7 flowchart and make a diagnosis
J7 - 06 thermistor (R5T) of the thermistor based
on the Error code shown to the left.
Defective heat exchanger liquid pipe thermistor (R4T) Refer to the J8 flowchart and make a diagnosis
J8 - 01 of the thermistor based
on the Error code shown to the left.
Defective subcooling heat exchanger gas pipe
J9 - 01 Refer to the J9 flowchart and make a diagnosis
thermistor (R6T)
of the thermistor based
Error detection of subcooling heat exchanger gas pipe on the Error code shown to the left.
J9 - 08 thermistor (R6T)
Troubleshooting
Error code
Description of error Diagnosis
JA - 06 Defective high pressure sensor: Open Refer to the JA flowchart and make a diagnosis
of the sensor based
JA - 07 Defective high pressure sensor: Short on the Error code shown to the left.
JC - 06 Defective low pressure sensor: Open Refer to the JC flowchart and make a diagnosis
of the sensor based
JC - 07 Defective low pressure sensor: Short on the Error code shown to the left.
L1 - 01 IPM error: Compressor M1C
L1 - 02 Defective current sensor: Compressor M1C
L1 - 03 Current offset: Compressor M1C The inverter PCB may be defective or a PCB other than
the specified is mounted.
L1 - 04 IGBT error: Compressor M1C
Refer to the L1 flowchart and make a diagnosis based
L1 - 05 Jumper settings error: Compressor M1C on the Error code shown to the left.
L1 - 36 EEPROM abnormality: Compressor M1C
L1 - 47 Power supply voltage abnormality: Compressor M1C
L2 - 01 Momentary power failure Refer to the L2 flowchart and make a diagnosis based on
L2 - 04 Power ON the Error code shown to the left.
L4 - 01 Radiation fin temperature rise: Inverter for M1C Refer to the L4 flowchart and make a diagnosis based
L4 - 06 Radiation fin temperature rise: Inverter fan M1F on the Error code shown to the left.
Current offset error Refer to the L5 flowchart and make a diagnosis based
L5 - 03
on the Error code shown to the left.
Compressor M1C overcurrent error Refer to the L8 flowchart and make a diagnosis
L8 - 03 of the compressor based
on the Error code shown to the left.
L9 - 01 Compressor M1C startup error Refer to the L9 flowchart and make a diagnosis
of the compressor based
L9 - 13 Compressor M1C output open phase on the Error code shown to the left.
LC - 14 PCB inverter error (Compressor M1C) Refer to the LC flowchart and make a diagnosis based
LC - 19 PCB inverter error (Fan M1F) on the Error code shown to the left.
Inverter circuit capacitor high voltage Refer to the P1 flowchart and make a diagnosis based
P1 - 01
Unbalanced power supply voltage on the Error code shown to the left.
P3 - 01 Defective reactor thermistor 1 Refer to the P3 flowchart and make a diagnosis based on
P3 - 04 Defective reactor thermistor 2 the Error code shown to the left.
P4 - 01 Defective radiation fin thermistor Refer to the P4 flowchart and make a diagnosis based
P4 - 02 Defective fan M1F fin sensor on the Error code shown to the left.
PJ - 04 Incorrect type of compressor Refer to the PJ flowchart and make a diagnosis based
PJ - 09 Incorrect type of fan on the Error code shown to the left.
U0 - 05 Refrigerant shortage warning (cooling)
Refer to the U0 flowchart and make a diagnosis based
U0 - 06 Refrigerant shortage warning (heating)
on the Error code shown to the left.
U0 - 08 Refrigerant shortage
U1 - 16 Open phase for power supply Refer to the U1 flowchart and make a diagnosis based on
U1 - 19 Hz error for power supply the Error code shown to the left.
U2 - 01 Shortage of inverter power supply voltage Refer to the U2 flowchart and make a diagnosis based
U2 - 02 Power phase loss on the Error code shown to the left.
Initial installation alarm / Test operation failed due to
U3 - 02
indoor unit error
U3 - 03 Test operation not conducted
U3 - 04 Abnormal end of test operation
Premature end of test operation during initial
U3 - 05
transmission error – check indoor unit error U4 / U9
Premature end of test operation during normal Refer to the U3 flowchart and make a diagnosis based
U3 - 06 transmission error on the Error code shown to the left.
Premature end of test operation due to transmission
U3 - 07 error
Premature end of test operation due to transmission
U3 - 08
error of all units
Troubleshooting
Error code
Description of error Diagnosis
Error when external control adaptor for outdoor unit is
U7 - 01
installed
U7 - 02 Alarm when external control adaptor for outdoor unit is Refer to the U7 flowchart and make a diagnosis based
installed on the Error code shown to the left.
Error Code A0
Method of Error Detects open or short circuit between external input terminals in indoor unit.
Detection
Error Decision An open circuit occurs between external input terminals with the remote controller set for
Conditions external ON/OFF input.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
External
protection device is
connected to terminals T1 and YES Activation of external
T2 of the indoor unit protection device.
terminal block.
NO
External
ON/OFF input (mode
No. 12, first code No. 1) has
YES Change the second code
been set to external protection
device input (second code No. to 01 or 02.
No. 03) by remote
controller.
NO
Error Code A1
Method of Error Data from EEPROM is checked.
Detection
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Error Code A3
Method of Error By float switch OFF detection
Detection
Error Decision Float switch goes OFF when the conditions for water level rise are not met
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is power supply NO
220-240 V provided? Provide 220-240 V power
supply.
YES
The float
switch is NO A short circuit NO
connected to the indoor connector is Connect either a short circuit
unit PCB. (∗1) connected. (∗1) connector or float switch and
turn ON again.
YES YES
The
float switch Becomes
contact is forming a YES normal when the NO
short circuit (continuity check connector (∗1) of the indoor Replace the indoor unit
with the connector (∗1) unit PCB is short control PCB (A1P).
disconnected) circuited.
NO YES
Defective connection of
connector.
NO The float switch NO
Water builds up
in the drain pan. functions normally. Replace the float switch (S1L).
YES YES
Modify the float switch's
connection and turn ON again.
The
drain pump is NO
connected to the Connect the drain pump and
indoor unit PCB. turn ON again.
(∗2)
YES
The drain
pump works when the YES
power supply is reset for the Check the drain piping for
indoor unit. clogging or upward slope, etc.
NO
The
voltage of
drain pump
terminals (∗2) is in NO
accordance to the criteria Replace the indoor unit control
(∗3) (within 5 minutes of PCB (A1P).
resetting the power
supply).
YES
Replace the drain pump or
check for dirt, etc.
Note(s)
1: Float switch (S1L) / 2: Drain pump (M1P) 3: Drain pump (M1P)
Model Note
short circuit connector connector voltage
FXFSQ-AR X15A X25A 13 VDC –
FXDQ-PD X8A X25A 220-240 VAC –
FXDQ-ND X8A X25A 220-240 VAC –
FXMQ-PB X15A X25A 13 VDC –
FXMQ-AR X8A Y1, Y2 220-240 VAC –
Error Code A6
Method of Error Abnormal fan revolutions are detected by a signal output from the fan motor.
Detection
Supposed Broken wires in, short circuit of, or disconnection of connectors from the fan motor harness
Causes Defective fan motor
(Broken wires or defective insulation)
Abnormal signal output from the fan motor (defective circuit)
Defective indoor unit control PCB
Instantaneous disturbance in the power supply voltage
Fan motor lock
(Due to motor or external causes)
The fan does not rotate due to foreign matter blocking the fan.
Disconnection of the connector between the high-power PCB and the low-power PCB
Troubleshooting
Are there
any foreign matter YES
Remove the foreign matter.
around the fan?
NO
Is the
connector properly NO
connected to the indoor Properly connect the connector.
unit control PCB?
(∗1)
YES
By
disconnecting the
connector, the fan can be NO Replace the fan motor (M1F).
lightly rotated by
hand.
YES
CHECK 17
Disconnect the connector
from the fan motor, and then
make measurement of
resistance between pins.
Is the
resistance NO
between the pins less than Replace the indoor unit control
the judgment PCB (A1P).
criteria?
YES
Replace the fan motor and the
indoor unit control PCB (A1P).
Error Code A6
Method of Error This error is detected if there is no revolution detection signal output from the fan motor.
Detection
Error Decision When no revolutions can be detected even at the maximum output voltage to the fan
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Are the
X4A and X27A NO
connectors securely Properly connect the connectors.
connected? (At this time, check for any
defective connector contact or
YES broken wires.)
Is
the
power of 12
VDC supplied
between the Pins 1
and 3 when the X27A is YES CHECK 16
disconnected and the Check the indoor fan motor and
power supply turns
the wiring circuits of the fan
ON?
motor.
NO
Error Code A6
Method of Error Error from the current flow on the fan PCB
Detection Error from the rotation speed of the fan motor in operation
Error from the position signal of the fan motor
Error from the current flow on the fan PCB when the fan motor starting operation
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
There is a YES
foreign matter around the Remove the foreign matter.
fan.
NO
The fan
motor connectors
(X1A and X2A) of the fan PCB YES
(A2P) are disconnected.
Connect the connector
properly.
NO
The connectors
between the indoor unit YES
PCB (A1P) and the fan Connect the connector
PCB (A2P) are properly.
disconnected.
NO
YES
The fan
can be moved lightly
by hand after the fan motor NO
connector of the fan PCB Replace the indoor fan
(A2P) is removed. motor (M1F).
YES
The
resistance between
the power wire terminals of YES
the fan motor and motor frame Replace the indoor fan
(metal part) is 1 M or motor (M1F).
below.
NO
CHECK 16
Remove the power wire
connector from the fan motor
and measure the resistance
between U and V, V and W, and
W and U phases.
NO
CHECK 17
Remove the signal connector
from the fan motor and check
the resistance.
Between
VCC and GND
terminals, and between GND YES
and HW, HV, or HU terminals Replace the indoor fan
are below 1 Ω. motor (M1F).
NO
The HAP
lamp of the indoor
unit PCB (A1P) blinks and the YES
Replace the fan PCB (A2P).
HAP lamp of the fan PCB
(A2P) is off.
NO
Replace the indoor fan
motor (M1F).
Troubleshooting
Caution Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Turn OFF the power supply and
wait for 10 minutes.
NO
The fan
motor connector (∗1) is NO
connected to the indoor unit Connect the connector correctly.
control PCB
(A1P).
YES
It is
possible to rotate
the fan manually when the
fan motor connector is NO Replace the fan motor (M1F).
disconnected from the indoor
unit control PCB
(A1P).
YES
Resistance
between UVW of fan YES
motor is unbalanced, or Replace the fan motor (M1F).
short-circuited.
NO
Turn ON the power supply and
check the HAP lamp on the indoor
unit control PCB (A1P).
The HAP
lamp on the indoor unit NO Replace the indoor unit control
control PCB is
blinking. PCB (A1P).
YES
1 Check also if the relay connector between the indoor unit control PCB and the fan motor are
correctly connected.
Error Code A8
Method of Error Error is detected by checking the input voltage of the fan motor.
Detection
Error Decision When the input voltage of fan motor is 150 V or less, or 386 V or more.
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
There are
problems on the YES
condition of power supply Correct any fault.
described above.
NO
A8 YES
Reoccurrence of Check and correct each wiring.
error.
NO
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
There are
problems YES
on the condition of power Correct any fault.
supply described
above.
NO
Is the X27A
connector on the main NO
Properly connect the connector.
PCB properly connected?
YES
Is the
harness connecting YES
the X27A and the terminal block Replace the harness.
(X2M) disconnected?
NO
NO
Turn OFF the power once and turn
ON again. Then, start operation
with remote controller.
YES
Replace the indoor unit PCB
(A1P).
Error Decision Pin input for electronic expansion valve coil is abnormal when initializing microcomputer.
Conditions Either of the following conditions is seen/caused/occurs while the unit stops operation.
Temperature of suction air (R1T) – temperature of liquid pipe (R2T) > 8°C.
Temperature of liquid pipe of heat exchanger (R2T) shows fixed degrees or below.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
NO
Power is supplied. Replace the electronic expansion
valve main body.
YES
Electronic expansion
NO
valve is connected to Shut the power supply OFF after
X5A/X7A of indoor connection and then restart.
unit PCB.
YES
CHECK 18
Check of electronic NO
expansion valve coil Replace the electronic expansion
indicates normal. valve coil.
YES
NO
Error Code AF
Method of Error Water leakage from the humidifier system is detected based on float switch ON/OFF operation
Detection while the compressor is not in operation.
Error Decision The float switch changes from ON to OFF while the compressor is not in operation.
Conditions Error code is displayed but the system operates continuously.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Field drain
piping has a defect such as YES
Modify the drain piping.
upward sloping.
NO
A humidifier
unit (optional accessory) is YES
installed on the Check if the humidifier unit is
indoor unit. leaking.
NO
Defective indoor unit
control PCB (A1P).
Error Decision Any of the following conditions is established while the grille is elevating.
Conditions The storage detection limit switch does not detect anything for a prescribed time while the
grille is moving upward.
The position detection limit switch does not detect anything for a prescribed time while the
grille is moving upward.
The position detection limit switch detects a position for less than one second while the grille
is moving downward.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
YES
A wire is tangled. Correct the winding of wire.
NO
YES
Is the drive unit normal? Normal.
NO
Check the limit switch, gear,
motor of the drive unit.
Error Code AJ
Method of Error Capacity is determined according to resistance of the capacity setting adaptor and the memory
Detection inside the IC memory on the indoor unit PCB, and whether the value is normal or abnormal is
determined.
Error Decision The capacity code is not saved to the PCB, and the capacity setting adaptor is not connected.
Conditions A capacity that does not exist for that unit is set.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
The NO
indoor unit PCB was replaced Replace the indoor unit control
with a spare PCB. PCB (A1P).
YES
The
capacity setting NO
adaptor was installed when Install a capacity setting
replacing the PCB. adaptor.
Error Code C1
Method of Error Transmission conditions between the indoor unit control PCB (A1P) and fan PCB (A2P) are
Detection checked via microcomputer.
Error Decision When normal transmission is not carried out for a certain duration.
Conditions
Supposed Defective connection of the connector between indoor unit control PCB (A1P) and fan PCB
Causes (A2P)
Defective indoor unit control PCB (A1P)
Defective fan PCB (A2P)
External factor, such as instantaneous power failure
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is the
connector between
indoor unit PCB (A1P) and fan NO Connect the connector accurately.
PCB (A2P) accurately
connected? (∗1)
YES
Confirm the condition of
transmission on indoor unit
PCB using field setting mode.
(∗2)
Under above
field setting mode, NO Replace the indoor unit control
second code No. is 01. PCB (A1P).
YES
Connect the connector X70A
and turn ON the power again.
C1
YES Replace the fan PCB (A2P).
Reoccurrence
of error.
NO
Note(s) 1. Pull out and insert the connector once and check if it is absolutely connected.
2. Method to check transmission part of indoor unit control PCB.
(1) Turn OFF the power and remove the connector X70A of indoor unit control PCB (A1P).
(2) Short circuit X70A.
(3) After turning ON the power, check below numbers under field setting from remote controller.
(Confirmation: Second code No. at the condition of first code No. 21 on mode No. 41)
Determination 01: Normal
Other than 01: Transmission error on indoor unit control PCB
After confirmation, turn OFF the power, take off the short circuit and connect X70A back to
original condition.
Error Decision Error is decided when transmission has been lost for 15 seconds and the error code is
Conditions displayed on the remote controller 60 seconds later.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is the
connector X70A on the NO
indoor unit control PCB Connect the connector correctly.
connected correctly?
YES
NO
Turn OFF the power supply and
then turn it ON again. Then, start
operation with remote controller.
Error is displayed NO
again. Normal.
YES
Check the indoor unit control
PCB (A1P).
Error Decision When transmission communication between the indoor unit PCB and the auto grille control PCB
Conditions is not normally performed for a certain period of time or more.
Supposed Defective connection of the transmission communication connector between the indoor unit
Causes PCB and the auto grille control PCB
Defective indoor unit PCB
Defective auto grille control PCB
External factors (e.g. noise)
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is the X70A
connector on the indoor NO
Properly connect the connector.
unit PCB properly
connected?
YES
Is the X12A NO
connector on the auto grille Properly connect the connector.
control PCB properly
connected?
YES
NO
NO
Turn OFF the power once and turn
ON again. Then, start grille
operation with remote controller.
Is
"Auto grille
elevation operation" NO
displayed in the remote Check the indoor unit PCB and
controller menu? the auto grille control PCB.
YES
Can NO
the target unit be Check the indoor unit PCB and
selected? the auto grille control PCB.
YES
Normal.
Error Decision The thermistor becomes disconnected or shorted while the unit is running.
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
CHECK 11 NO
Normal? Replace the thermistor.
YES
Replace the indoor unit
control PCB (A1P).
Error Code C6
Method of Error Transmission conditions with the fan PCB (A2P) are checked using the indoor unit PCB (A1P).
Detection
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Does the
fan PCB part No. NO
match that of the spare Replace it with the correct
parts list? fan PCB (A2P).
YES
Has the
indoor unit control PCB NO After establishing
(A1P) been replaced with a
spare PCB? transmission for indoor and
outdoor, diagnose the
operation again.
YES
Was
the correct
capacity setting
adaptor installed when NO
Install the correct capacity
replacing it with a spare setting adaptor.
PCB?
YES
After establishing
transmission for indoor and
outdoor, diagnose the
operation again.
Error Decision Based on the communication data, decide whether the combination of capacity setting and the
Conditions type of fan driver is correct.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is the indoor
NO
unit PCB (A1P) replaced by After transmission between
the spare PCB? the indoor and the outdoor
PCBs is established, perform
operation again and then
YES
perform diagnosis again.
Is a proper
capacity setting adaptor NO
installed when replaced by the Install a proper capacity
space PCB? setting adaptor.
YES
Error Decision When an abnormal signal is detected at the start of operation of the fan motor.
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is the fan
motor connector (X901A) NO
Properly connect the connector.
connected properly?
YES
Resistances
between UVW phases of
YES
the fan motor are imbalanced, or Replace the fan motor.
there is a short circuit
between UVW.
NO
Error Code CE
Method of Error The contents of a failure vary with the detailed error code. Check the code and proceed with the
Detection flowchart.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Error code
See diagnosis procedure 1.
CE-01
Error code
See diagnosis procedure 2.
CE-02
Error code
See diagnosis procedure 3.
CE-03
Error code
See diagnosis procedure 4.
CE-04
Troubleshooting
Diagnosis procedure 1
Infrared presence sensor
error (Error code CE-01)
Is the
connection
of the connector
on infrared presence NO
sensor PCB (A3P) and Connect the connector correctly.
the connector
X81A on A1P
normal?
YES
Is the
connection of the NO
Connect the connector correctly.
sensor connector
normal?
YES
Displays
15 by the above NO
Normal.
verification method.
YES
Displays CE-01
again or 15 for NO
Normal.
sensor and
address data.
YES
Replace the sensor.
Troubleshooting
Diagnosis procedure 2
Infrared floor sensor error
(Error code CE-02)
Is the
connection
of the connector
on infrared floor NO
sensor PCB (A2P) and Connect the connector correctly.
the connector
X81A on A1P
normal?
YES
Is the
connection of the NO
Connect the connector correctly.
sensor connector
normal?
YES
Displays
"--" by the above NO
Normal.
verification method.
YES
Displays CE-02
again or "--" for NO
Normal.
sensor and
address data.
YES
Replace the sensor.
Troubleshooting
Diagnosis procedure 3
Infrared floor sensor error
(Error code CE-03)
Is the
connection
of the connector
on infrared floor NO
sensor PCB (A2P) and Connect the connector correctly.
the connector
X81A on A1P
normal?
YES
Is the
connection of the NO
Connect the connector correctly.
sensor connector
normal?
YES
Displays
"--" by the above NO
Normal.
verification method.
YES
Displays
CE-03 again or "--" NO
for sensor and address Normal.
data.
YES
Replace the sensor.
Troubleshooting
Diagnosis procedure 4
Infrared floor sensor error
(Error code CE-04)
Is the
connection
of the connector
on infrared floor NO
sensor PCB (A2P) and Connect the connector correctly.
the connector
X81A on A1P
normal?
YES
Is the
connection of the NO
Connect the connector correctly.
sensor connector
normal?
YES
Displays
"--" by the above NO
Normal.
verification
method.
YES
Displays
CE-04 again or "--" NO
for sensor and address Normal.
data.
YES
Replace the sensor.
Error Code CJ
Method of Error Error detection is carried out by the temperature detected by the remote controller thermistor.
Detection
Error Decision When the remote controller thermistor becomes disconnected or shorted while the unit is
Conditions running.
Error code is displayed but the system operates continuously.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is CJ YES
displayed on the remote Replace the remote
controller? controller.
NO
External factor other than
equipment error.
(for example, noise etc.)
Error Code E1
Method of Error Abnormality is detected under the communication conditions in the hardware section between
Detection the indoor unit and outdoor unit.
Error Decision When the communication conditions in the hardware section between the indoor unit and the
Conditions outdoor unit are not normal.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
YES
Return to normal? External factor other than
error (for example, noise
etc.).
NO
Check if
inside / outside
YES
relay wires of outdoor Connect the inside/outside
unit main PCB is relay wires correctly.
disconnected.
NO
Error Code E2
Sub code: 01
Method of Error Current leakage is detected in the earth leakage detection circuit. Error is detected on the
Detection outdoor unit main PCB.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Check
if the
connection to the NO
current sensor (T1A) is Correct the wiring.
correctly wired.
YES
NO
Defective
insulation of parts YES
other than the Replace the corresponding
parts.
compressor
NO
Reconnect the wires, and
then reconnect the unit to the Normal
power supply. (Keep operating)
It is possibly caused by
temporary oil return or
refrigerant stagnation.
(Perform maintenance
during long-term
shutdown such as a
power outage.)
Error Code E2
Sub code: 06
Method of Error Detect error according to whether or not there is continuity across the connector (X101A).
Detection
Error Decision When no current flows at the time of turning ON the power supply.
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
YES
Error Code E3
Method of Error Detect continuity across the high pressure switch in the protection device circuit.
Detection
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Are the NO
above 3 points Remedy defective points.
OK?
YES
(1) Mount a pressure gauge on the high pressure
service port.
(2) Reset the operation using the remote controller,
and then restart the operation.
Is the
operating
Does the error E3 YES pressure of the NO
high pressure switch Replace the high pressure
recur?
normal switch. (S1PH)
(4.0 MPa)?
NO YES
CHECK 12
Compare the voltage
measurement of the connector
of the pressure sensor (1) with the NO Replace the high pressure sensor
measurement of the pressure gauge.
Are the characteristics (S1NPH).
of the high pressure
sensor normal? (1) Use the table on CHECK 12
to convert the voltage measurement
into pressure measurement.
YES
A Go to the next page
CHECK 12
Service Checker
Connect the service checker, and then compare the high pressure value
measured by the service checker with the voltage measurement of the
connector of the pressure sensor (1)
Are both
NO
pressure values the Replace the outdoor unit
same? main PCB (A1P).
YES
-The high pressure sensor is normal, and outdoor unit main PCB is also
normal.
-The high pressure has really become high.
CHECK 1 Eliminate factors that cause the high pressure to rise.
Error Code E4
Method of Error Make judgment of pressure detected by the low pressure sensor with the outdoor unit main
Detection PCB.
Error Decision When low pressure caused a drop while the compressor is in operation:
Conditions Operating pressure: 0.07 MPa
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is the stop NO
Open the stop valve.
valve open?
YES
(1) Mount a pressure gauge on the low pressure
service port.
(2) Reset the operation using the remote
controller, and then restart the operation.
CHECK 12
Compare the
voltage measurement of
the connector of the pressure NO
sensor (1) with the measurement Replace the low pressure sensor.
of the pressure gauge. (S1NPL)
Are the characteristics of the
low pressure sensor (1) Use the table on CHECK 12 to
normal?
convert the voltage measurement into
pressure measurement.
YES
CHECK 12
Service Checker
Connect the service checker, and then compare the low pressure value
measured by the service checker with the voltage measurement of the
connector of the pressure sensor (1)
Are both
NO
pressure values the Replace the outdoor unit main
same? PCB (A1P).
YES
- The low pressure sensor is normal, and outdoor unit main PCB is
also normal.
- The low pressure has really become low.
CHECK 2 Eliminate factors that cause the low pressure to decrease.
Error Code E5
Method of Error Outdoor unit main PCB takes the position signal from UVW line connected between the inverter
Detection and compressor, and the error is detected when any abnormality is observed in the
phase-current waveform.
Error Decision When the compressor motor does not operate even by starting it in forced startup mode.
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is the stop NO
valve open? Field factor
Open the stop valve.
YES
Check the connection wiring for
compressor M1C.
Is the
connection line NO
of the compressor Replace the connection line,
normal? and then securely connect the
connector.
YES
Power OFF
Are wire
connections
made to phases U, V NO Make proper wire connections.
and W in the proper
order and W
manner?
U
YES
V
Are wire
connections NO
made according Make proper wire connections.
to the wiring
diagram?
YES
A
The insulation
resistance of the YES
Replace the compressor (M1C).
compressor is low
(< 100 k )
Power OFF NO
The
internal wiring of YES
the compressor coil is
defective.
NO
Restart the
compressor, and then NO
check for the operation. Quit work.
Does the error Pressure equalization failure
recur? may have occurred. Check for
the refrigerant system.
Power ON YES
Has the
compressor
started up at high YES
differential pressure Pressure equalization failure.
(0.5 MPa or Check for the refrigerant
more)? system.
NO
CHECK 4
NO
Power OFF Is the power Replace the relevant PCB (1).
transistor
normal?
YES
RXYMQ4-6AYFK only
Error Code E7
Method of Error Detect according to the value of current flowing through the PCB.
Detection Detect error of the fan motor system according to the fan revolutions detected by the Hall IC
during the fan motor runs.
Error Decision When overcurrent is detected (Detecting overcurrent 4 times will shut down the system).
Conditions When the fan revolutions fall below a given level for a period of 6 seconds while in fan motor
rotation mode (Detecting shortage of revolutions will shut down the system).
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Turn OFF the power supply, and then wait for a period of 10 minutes.
There is
foreign matter around the YES
Remove the foreign matter.
applicable fan.
NO
Connector is YES
Insert the connector.
disconnected.
NO
The fan
can be rotated
by hand when NO
disconnecting the Replace the fan motor (M1F).
connector from the
fan motor.
YES
Resistance
between the fan
motor power supply cable YES
terminal and the motor frame Replace the fan motor (M1F).
(metallic part) is less
than 1 M .
NO
A
RXYMQ4AVMK
CHECK 16
Check for the connector
(power supply cable) of the
fan motor.
Resistance
between U, V, W
phases of the fan motor
power supply cable has lost YES
Replace the fan motor (M1F).
balance or short circuit is
caused between U, V,
W phases.
NO
Turn ON the power supply to
check for the HAP lamp on
the outdoor main PCB (A1P)
The HAP NO
lamp on A1P blinks. Replace the outdoor main PCB
(A1P).
YES
Replace the fan motor (M1F).
RXYMQ4-6AYFK
A
CHECK 16
Check for the connector
(power supply cable) of the
fan motor.
Resistance
between U, V, W
phases of the fan motor
power supply cable has lost balance YES Replace the fan motor (M1F).
or short circuit is caused
between U, V, W
phases.
NO
Turn ON the power supply to check for the following LED lamps.
(1) LED lamp on the inverter PCB (A3P)
(2) LED lamp on the fan PCB (A4P)
NO
Replace the fan motor (M1F).
Error Code E9
Method of Error Detect according to whether or not there is continuity across the electronic expansion valve
Detection coils (Y1E, Y2E, Y3E, Y4E).
Error Decision When no current flows through common (COM+) at the time of turning ON the power supply.
Conditions
Supposed Disconnection of connectors from electronic expansion valves (Y1E, Y2E, Y3E, Y4E)
Causes Defective electronic expansion valve coil
Defective outdoor unit main PCB
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
CHECK 18
Is sub code one of YES The resistance of NO
the following? the electronic expansion Replace the defective electronic
E9-48, 54 valve coil is expansion valve coil.
normal.
NO YES
Replace the outdoor unit main PCB
(A1P).
Check for electronic
expansion valves applicable
to the error code E9 while in
monitor mode.
• Sub code
Y1E: E9-01
Y2E: E9-03
Y3E: E9-04
Y4E: E9-26
Connector for
the electronic expansion NO
valve of the outdoor unit main Properly and securely connect the
PCB (A1P) is connector.
connected.
YES
CHECK 18
The resistance of the NO
electronic expansion Replace the electronic expansion
valve coil is valve coil.
normal.
YES
Replace the outdoor unit main PCB
(A1P).
Error Code F3
Method of Error Detect according to temperature detected with the discharge pipe or compressor body
Detection thermistor.
Error Decision When discharge pipe temperature becomes abnormally high (i.e., 135°C or more)
Conditions When discharge pipe temperature sharply rises (remains at 120°C or more for a period of
consecutive 10 minutes)
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
NO
Is the stop valve open? Open the stop valve.
YES
CHECK 11
Are
the characteristics NO
Replace the discharge pipe
of the discharge pipe
thermistor normal? thermistor (R21T).
YES
Service Checker
Connect the Service Checker, and then compare the
discharge pipe temperature measured by the Service
Checker and the measurement of discharge pipe
surface temperature.
Is the
temperature
checked by the NO
Service Checker same as Replace the outdoor unit main
the measurement of the PCB (A1P).
temperature?
YES
• Thermistor is normal, and temperature detection with
the outdoor unit main PCB is also normal.
• The discharge pipe temperature has really become
high.
CHECK 3 Eliminate the causes of superheat operation.
Error Code F4
Method of Error In cooling operation, detect the condition under which liquid refrigerant returns to the
Detection compressor, according to the temperature and pressure of each part.
Error Decision When the following wet state continues for a period of 180 minutes, an alert is issued.
Conditions An error is defined for 240 minutes.
Wet state in outdoor units
When the following wet state continues for a period of 180 minutes, an alert is issued.
Wet state in some of indoor units
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Are the
characteristics of the NO
Replace the suction pipe
suction pipe thermistor thermistor.
normal?
YES
Are the
discharge pipe NO
thermistor characteristics Replace the discharge
normal? pipe thermistor.
YES
Are the high
pressure sensor NO
Replace the high
characteristics pressure sensor
normal?
(S1NPH).
YES
Service Checker
Use the Service Checker to find indoor units
operating under the following conditions:
& • Gas pipe temperature (R3T) - Liquid pipe temperature (R2T) < 2.5°C
• Electronic expansion valve opening < 300 pulse
Error Code F6
Method of Error Detect overcharged refrigerant according to outdoor air temperature, heat exchanger liquid pipe
Detection temperature, and subcooling liquid pipe temperature during test operation.
Error Decision When the amount of refrigerant, which is calculated using outdoor air temperature, heat
Conditions exchanger liquid pipe temperature, and subcooling liquid pipe temperature during test
operation, exceeds the regular charge amount by 30% or more
(If refrigerant is charged slightly over the regular charge amount, F6 may be displayed on the
remote controller.)
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
YES
Disconnect the outdoor air
thermistor, the heat exchanger
liquid pipe thermistor, and
subcooling liquid pipe
thermistor from the outdoor
unit main PCB, and then make
measurement of resistance
using a multimeter.
CHECK 11 NO
Replace abnormal thermistors,
Normal? and then operate the system.
YES
Remedy refrigerant overcharging.
Error Code H3
Method of Error Check for the transmission conditions of the harnesses between the PCBs (X28A (A1P) and
Detection X6A (A3P)), and relay connector, if any, using microcomputer.
Error Decision When normal transmission between PCBs is disabled during the compressor stops running.
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
YES
Harness error Return the relevant harness to
normal.
NO
NO
H3 error recurs. Complete countermeasures.
YES
Replace the inverter PCB. (1)
Error Code H5
Method of Error A compressor overload is detected through compressor OL.
Detection
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
NO
CHECK 11 NG
Check the discharge pipe Replace the discharge pipe
thermistor. thermistor.
OK
Is the OL connector NO
(1) properly connected? Connect the connector (1)
properly.
YES
Disconnect the connector (1)
from the PCB.
Check the
resistance between Nearly 0
the 2 terminals on the Replace the outdoor unit
connector (1). main PCB (A1P).
Resistance
Disconnect the 2 terminals of
the OL (Q1M).
Resistance
Replace the OL (Q1M).
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is
resistance
between Vcc-UVW
and between GND-UVW NO Replace the fan motor (M1F).
of the fan motor lead in
balance?
YES
Replace the fan PCB (A4P).
Error Decision When the system is in operation and the thermistor causes wiring disconnection or short circuit
Conditions in it.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Thermistor is NO
connected to the Connect the connector and turn
connector. ON again.
YES
CHECK 11
Resistance is
normal when
measured after NO
disconnecting the Replace the thermistor (1).
thermistor from the
outdoor unit
main PCB.
YES
Replace the outdoor unit main
PCB (A1P).
Error RXYMQ-A
Code Applicable Thermistor
Electric symbol Connector
H9 Outdoor air thermistor R1T X18A
J3 Discharge pipe thermistor R21T X19A
J5 Suction pipe thermistor R3T
J6 Heat exchanger deicer thermistor R7T
J7 Subcooling heat exchanger liquid pipe thermistor R5T X30A (Group
connector)
J8 Heat exchanger liquid pipe thermistor R4T
J9 Subcooling heat exchanger gas pipe thermistor R6T
Error Code JA
Method of Error Detect according to temperature detected with the high pressure sensor.
Detection
Error Decision The high pressure sensor is short circuit or open circuit.
Conditions (Pressure range: 0-4.3 MPa)
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Are the
characteristics of the
high pressure sensor
normal? (Make a comparison NO
between voltage characteristics Replace the high pressure sensor
and gauge pressure.) (S1NPH).
CHECK 12
YES
Is the outdoor
unit main PCB
detection pressure normal?
Make a comparison between data NO
on pressure checked by the Service Replace the outdoor unit main
Checker and the voltage PCB (A1P).
characteristics.
CHECK 12
YES
Reset the operation, and then
restart it.
Are the
characteristics of the high NO
pressure sensor normal? Replace the high pressure sensor
(S1NPH).
YES
Replace the outdoor unit main
PCB (A1P).
Error Code JC
Method of Error Detect according to temperature detected with the low pressure sensor.
Detection
Error Decision The low pressure sensor is short circuit or open circuit.
Conditions (Pressure range: 0-1.7 MPa)
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Are the
characteristics of
the low pressure
sensor normal? (Make a NO
comparison between voltage Replace the low pressure sensor
characteristics and gauge (S1NPL).
pressure.)
CHECK 12
YES
Is the
outdoor unit main
PCB detection pressure
normal? Make a comparison NO
between data on pressure checked by Replace the outdoor unit main
the Service Checker and the PCB (A1P).
voltage characteristics.
CHECK 12
YES
Reset the operation, and then
restart it.
Are the
characteristics of the low NO
pressure sensor Replace the low pressure sensor
normal? (S1NPL).
YES
Replace the outdoor unit main
PCB (A1P).
Error Code L1
Method of Error Error is detected based on the current value during waveform output before starting
Detection compressor.
Error is detected based on the value from current sensor during synchronous operation when
starting the unit.
Troubleshooting RXYMQ4AVMK
RXYMQ4-6AYFK
YES
Return to normal? The error could have resulted from
external factors other than failures
(e.g. external noise or thunder).
NO
CHECK 4
Is the power NO
transistor normal?
Is the
YES insulation to
ground resistance of the NO
Replace both the compressor (M1C)
compressor 100 k or
more? and the inverter PCB (A3P).
YES
Replace the inverter PCB (A3P).
CHECK 4
Is the power NO
transistor of the fan Replace both the inverter PCB (A3P)
driver normal? and the fan PCB (A4P).
YES
Replace the inverter PCB (A3P).
Error Code L2
Method of Error Momentary power failure is detected by the PCB.
Detection
Error Decision Judgment is made by AC power frequency detection circuit on the outdoor unit main PCB
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Error
recurs after NO
turning OFF the power Temporary problem
and ON again.
YES
Any
disconnection
of connectors, loose
contact or wiring disconnection YES
Correct any fault.
in the transmission wirings to
the outdoor unit main
PCB?
NO
Replace the outdoor unit
main PCB (A1P).
Error Code L4
Method of Error Detect temperature of power module of the inverter circuit.
Detection
Error Decision Thermistor located inside the power module of the inverter circuit for compressor and fan motor.
Conditions Cooling tube plate poor heat-exchange.
NO
Is the stop valve open? Open the stop valve.
YES
Does the
connector X111A of fin
thermistor connect to the NO
Connect the connector correctly.
outdoor unit main PCB
correctly?
YES
NO
NO
Keep operating.
Subcode L4-06
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Normal? NO
Rectify troubles.
YES
Turn
ON the power
supply. Does the error YES
Replace the relevant PCB (2).
recur when operation
starts?
NO
Continue operation.
Field factor. Heat sink radiation fin
temperature may have risen due to
high outdoor air temperature.
Error Code L5
Method of Error Detect current flowing through the power transistor.
Detection
Error Decision The current instantaneously exceeds A (A) in the power transistor.
Conditions Trigger point
Compressor model A (A)
2Y350APAX2N 48.1
2Y420AVAY1N 48.55
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
NO
Is the stop valve open? Open the stop valve.
YES
Check for the leads of the
compressor.
• For compressor M1C
Are the
Power OFF leads of the NO
compressor normal? Replace the leads of the
compressor.
YES
Are
wiring and wire NO
connections to the Rectify the wiring and
compressor wire connections.
normal?
YES
NO
The internal
wiring of the YES
compressor coil is Replace the compressor
defective. (M1C).
NO
CHECK 4
Is the power NO
Replace the relevant
transistor normal? PCB (1).
YES
Restarting the NO
system results in the Continue operation.
recurrence of the
( )
The error could have
error. resulted from causes
YES such as instantaneous
power failure.
RXYMQ4-6AYFK Only
Power OFF Replace the inverter PCB (A3P).
Restarting the NO
system results in the Continue operation.
recurrence of the
error.
YES
Replace the
compressor (M1C).
Error Code L8
Method of Error Detect current flowing through the power transistor.
Detection
Error Decision (1) The secondary-side inverter current exceeds A (A) for a period of 5 consecutive seconds.
Conditions (2) The secondary-side inverter current exceeds B (A) for a period of 260 consecutive seconds.
Trigger point
Compressor model A (A) B (A)
2Y350APAX2N 22.1 22.1
2Y420AVAY1N 22.5 18.6
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
NO
Is the stop valve open? Open the stop valve.
YES
Check for the leads of the
compressor.
• For compressor M1C
Are the
Power OFF leads of the NO
compressor normal? Replace the leads of the
compressor.
YES
Are
wiring and wire NO
connections to the Rectify the wiring and
compressor wire connections.
normal?
YES
NO
The internal
wiring of the YES
compressor coil is Replace the compressor
defective. (M1C).
NO
CHECK 4
NO
Is the power Replace the relevant
transistor normal? PCB (1).
YES
Connect the compressor lead
wires and restart.
NO
L8 recurs. Continue operation.
YES
The difference
between high and low pressure NO
Defective equalization of
before restarting is less than the refrigerant line.
0.2 MPa.
YES
RXYMQ4-6AYFK Only
Power OFF Replace the inverter PCB (A3P).
Restarting the NO
system results in the Continue operation.
recurrence of the
error.
YES
Diagnose the
compressor (M1C).
Error Code L9
Method of Error Detect error according to the signal waveform of compressor.
Detection
Error Decision When compressor startup operation has not been completed.
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Startup for NO
the first time after Go to the next page.
installation? (Startup failure in aging operation)
YES
Is a proper NO
amount of refrigerant Charge a proper amount of
charged? refrigerant.
YES
Refrigerant
is stagnated. YES
(The unit is out of power Solve the refrigerant stagnation.
supply for more than 6 (Power should be supplied for more
hours.) than 6 hours.)
NO
Is the
insulation NO
resistance of the Replace the compressor (M1C).
compressor 100 k
or more?
YES
Are the
leads of the YES
compressor Connect the leads of the compressor.
disconnected?
NO
Apply power, and then restart
operation.
Refrigerant
is stagnated.
(The unit is out of power YES
Solve the refrigerant stagnation.
supply for more than (Power should be supplied for more
6 hours.) than 6 hours.)
NO
Is the
insulation
resistance of the NO
compressor 100 k Replace the compressor (M1C).
or more?
YES
NO
CHECK 4
Is the power NO
Replace the relevant PCB (1).
transistor normal?
YES
Recheck for the compressor and the
refrigerant system.
Error Code LC
Method of Error Check for the transmission conditions between microcomputers on the outdoor unit main PCB
Detection using a microcomputer.
Error Decision Normal transmission is disabled for a given period of time or more.
Conditions
Supposed Connection error between microcomputers on the outdoor unit main PCB
Causes Defective outdoor unit main PCB (transmission block)
Defective noise filter
External factors (e.g. noise)
Defective compressor
Defective fan motor
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is the harness
between terminal block NO
and outdoor unit main PCB Properly connect the harness.
securely connected?
(1)
YES
The insulation
resistance of the YES Replace the compressor.
compressor is less than
100 k .
NO
The insulation
resistance of the fan motor YES Replace the fan motor.
is less than
1M
NO
The
microcomputer normal
monitor (green) on the outdoor NO
Replace the outdoor unit main PCB
unit main PCB (A1P) is (A1P).
blinking.
YES
YES Replace the outdoor unit main PCB
The LC error recurs.
(A1P).
NO
Continue operation.
The error could have resulted from
causes such as instantaneous
power failure.
Note(s)
1. Connect and disconnect the connector once to ensure that it is securely connected.
Error Code LC
Method of Error Check for the transmission conditions between the inverter PCB and the outdoor unit main PCB
Detection using a microcomputer.
Error Decision Normal transmission is disabled for a given period of time or more.
Conditions
Supposed Defective connection between the inverter PCB and the outdoor unit main PCB
Causes Defective outdoor unit main PCB (transmission block)
Defective noise filter
External factors (e.g. noise)
Defective compressor
Defective fan motor
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is the
connector
between outdoor unit NO
main PCB and inverter PCB Properly connect the connector.
securely connected?
(1)
YES
Does the
inverter PCB part No. NO
match that of the spare Replace with a proper PCB.
parts list?
YES
The insulation
resistance of the YES
compressor is less Replace the compressor (M1C).
than 100 k .
NO
The insulation
resistance of the fan motor YES
Replace the fan motor (M1F).
is less than
1M
NO
The service
monitor (green) on the NO
outdoor unit main This is not the LC error.
PCB (A1P) is Recheck the error code.
blinking.
YES
The service
monitor (green) on the NO The fuse of the NO
inverter PCB (A3P) is noise filter PCB has blown Replace the inverter PCB (A3P).
blinking. out.
YES
YES Replace all of the inverter PCB (A3P),
the fan PCB (A4P) and the noise filter
Is the PCB (A2P).
connector between
the inverter PCB and the fan NO
Properly connect the connector.
PCB securely connected?
YES
The service
monitor (green) on the fan NO
Replace the fan PCB (A4P).
PCB (A4P) is blinking.
YES
YES
The LC error recurs. Replace the outdoor unit main PCB
(A1P).
NO
Continue operation.
The error could have resulted from
causes such as instantaneous
power failure.
Note(s)
1. Connect and disconnect the connector once to ensure that it is securely connected.
Error Code P1
Method of Error The voltage waveform of the main circuit capacitor of the inverter is used to check for errors.
Detection
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is power supply
voltage within NO
Correct the power supply
rated voltage ±10%? voltage.
YES
Error Code P1
Method of Error Detect voltage imbalance through inverter PCB.
Detection
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is supply
voltage imbalance over YES YES
Open phase? Correct the open phase of
approximately 12 V?
(1) power supply.
NO NO
Rectify the power supply
voltage imbalance.
Take countermeasures (listed
below).
Is the imbalance of
YES
voltage applied to the inverter Defective noise filter, inverter
over approximately PCB or wiring
12 V? (2)
Turn OFF the power supply,
and then check and repair
NO
wirings in the main circuit and
<If voltage can be monitored> defective components.
(1) Loose contact and wiring
Use equipment capable of constantly disconnection between the
recording power supply voltages (e.g. power supply and the
Memory Hi-Corder) to record power inverter
supply voltages between phases (2) Wiring disconnection in or
(R-S, S-T, and R-T) for a period of loose contact of noise filter
consecutive 1 week.
Take countermeasures.
Replace the inverter PCB
(A3P).
Explanation to users Use the document “Notice of Inspection Results” attached to spare part.
Hand the “Notice of Inspection Results” to user to ask Be sure to explain user that “power supply
him/her to rectify the imbalance. voltage imbalance” will occur and Daikin
accepts no responsibility for the imbalance.
Note(s)
1. Make measurement of voltage at the power supply terminal block (X1M).
2. Make measurement of voltage at the L1, L2 and L3 terminals of diode module located on
the inverter PCB during the compressor is in operation.
Error Code P3
Method of Error Detect according to the value detected with the reactor surface thermistor.
Detection
Error Decision When the system is in operation and the thermistor causes wiring disconnection or short circuit
Conditions in it.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Make measurement of
resistance of the radiation
fin thermistor.
Is the
resistance of the NO
thermistor normal? Replace the inverter PCB (A3P).
YES
Turn ON the
power supply. YES
Replace the inverter PCB (A3P).
Does the error
recur?
NO
Continue operation.
Error Code P4
Method of Error Detect the resistance of the following thermistors during the compressor stops running:
Detection (1) Radiation fin thermistor
(2) Thermistor located in PCB circuit
Error Decision When the resistance of the thermistor comes to a value equivalent to open or short circuit.
Conditions
Error is not decided while the unit operation is continued.
P4 will be displayed by pressing the inspection button.
Make measurement of
resistance of the radiation
fin thermistor.
CHECK 11
Is the resistance of the NO
radiation fin thermistor Replace the relevant PCB (1).
normal?
YES
The
insulation resistance YES
of the compressor is Replace the compressor
less than 100 k . (M1C).
NO
The insulation
resistance of the fan motor YES
Replace the fan motor.
is less than 1 M .
NO
Turn ON the
power supply. YES
Replace the relevant PCB (1).
Does the error
recur?
NO
Continue operation.
Subcode P4-02
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
The insulation
resistance of the fan YES
Replace the fan motor.
motor is
less than 1 M .
NO
Turn ON
the power supply. YES
Replace the relevant PCB
Does the error recur?
(2).
NO
Continue operation.
Error Code PJ
Method of Error This error is detected according to communications with the outdoor unit main PCB
Detection (RXYMQ4AVMK) or inverter PCB (RXYMQ4-6AYFK).
Error Decision Make judgment according to communication data on whether or not the type of the outdoor unit
Conditions main PCB (RXYMQ4AVMK) or inverter PCB (RXYMQ4-6AYFK) is correct.
Troubleshooting RXYMQ4AVMK
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Does the
outdoor unit main PCB NO
part No. match that of the Replace with a correct
spare parts list? outdoor unit main PCB
(A1P).
YES
Has the
DIP switch setting
been made properly to NO
Properly make DIP switch
replace the outdoor unit setting.
main PCB? (After completion of setting,
reset the power supply.)
YES
Replace the outdoor unit
main PCB (A1P).
RXYMQ4-6AYFK
Does the
inverter PCB part NO
No. match that of the Replace with a correct
spare parts list? inverter PCB (A3P).
YES
Error Code U0
Sub code: 05
Method of Error Detects refrigerant shortage according to the ending conditions of cooling oil return control.
Detection
Error Decision Cooling oil return control does not finish according to the ending conditions, and the time is
Conditions up for 3 consecutive times.
No abnormality is determined, and the operation continues.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Are the
characteristics of the NO
suction pipe thermistor Replace the thermistor
normal? (R3T).
YES
Are the
characteristics of the NO
low pressure sensor Replace the low pressure
normal? sensor (S1NPL).
YES
CHECK 2 CHECK 2
NO YES
Is refrigerant shortage detected Is another cause detected as a Correct the abnormally low
as a cause of abnormally cause of abnormally low pressure.
low pressure? pressure?
YES NO
CHECK 3 CHECK 3
NO YES
Is refrigerant shortage detected Is another cause detected Correct the superheat
as a cause of superheat as a cause of superheat operation.
operation? operation?
YES NO
CHECK 7 YES
Is refrigerant Correct the insufficient low
insufficient? refrigerant condition.
NO
Replace the outdoor unit
main PCB (A1P).
Error Code U0
Sub code: 06
Method of Error Detects refrigerant shortage according to the difference between low pressure equivalent
Detection saturation temperature and suction pipe temperature, opening degree of main electronic
expansion valve, or superheating operation.
Error Decision The following conditions are satisfied for 20 minutes or more.
Conditions Suction pipe temperature – Low pressure equivalent saturation temperature > 30°C
Opening degree of main electronic expansion valve (Y1E) > 480 pulses
Discharge pipe temperature > 125°C, or low pressure < 0.15 MPa and high pressure < 2.1
MPa simultaneously.
No abnormality is determined, and the operation continues.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Are the
characteristics of the NO
suction pipe thermistor Replace the thermistor
normal? (R3T).
YES
Are the
characteristics of the NO
low pressure sensor Replace the low pressure
normal? sensor (S1NPL).
YES
CHECK 2 CHECK 2
NO YES
Is refrigerant shortage detected Is another cause detected as a Correct the abnormally low
as a cause of abnormally cause of abnormally low pressure.
low pressure? pressure?
YES NO
CHECK 3 CHECK 3
NO YES
Is refrigerant shortage detected Is another cause detected Correct the superheat
as a cause of superheat as a cause of superheat operation.
operation? operation?
YES NO
CHECK 7 YES
Is refrigerant Correct the insufficient low
insufficient? refrigerant condition.
NO
Replace the outdoor unit
main PCB (A1P).
Error Code U0
Sub code: -08
Method of Error Detects refrigerant shortage according to the difference between low pressure equivalent
Detection saturation temperature and suction pipe temperature, opening degree of main electronic
expansion valve or indoor unit electronic expansion valve, inverter fin temperature, or outdoor
air temperature, etc.
Error Decision All of the following conditions are satisfied for 5 minutes or more, 4 times within 240 minutes.
Conditions Suction pipe temperature – Low pressure equivalent saturation temperature > 15°C
Opening degree of main electronic expansion valve (Y1E) > 480 pulses
Inverter fin temperature < Outdoor air temperature
Outdoor air temperature – Low pressure equivalent saturation temperature > 15°C
Opening degree of the electronic expansion valve of all the indoor units that have thermostat
ON is 400 pulses or more
High pressure equivalent saturation temperature – Thermostat ON indoor unit liquid pipe
temperature < 5°C
Compressor operates in minimum step
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
CHECK 11
Are the NO
characteristics of the Replace the outdoor air
outdoor air thermistor thermistor (R1T).
(R1T) normal?
YES
CHECK 11
Are the NO
characteristics of the Replace the suction pipe
suction pipe thermistor (R3T).
thermistor (R3T)
normal?
YES
Are the
characteristics of
the inverter fin temperature NO
thermistor normal? Replace the relevant PCB
(Refer to L4 (1).
troubleshooting.)
YES
CHECK 12
NO
Are the characteristics Replace the low pressure
of the low pressure sensor (S1NPL).
sensor normal?
YES
CHECK 12
Are the characteristics NO
Replace the high pressure
of the high pressure sensor (S1NPH).
sensor normal?
YES
CHECK 18
Are the characteristics and NO
insulation of the electronic expansion Replace the electronic
valve (refrigerant jacket) expansion valve coil (Y3E).
(Y3E) normal?
YES
CHECK 2 CHECK 2
NO YES
Is refrigerant shortage detected Is another cause detected as a Correct the abnormally low
as a cause of abnormally cause of abnormally low pressure.
low pressure? pressure?
YES NO
CHECK 3 CHECK 3
Is refrigerant shortage detected NO Is another cause detected YES
as a cause of superheating Correct the superheating
as a cause of superheating operation.
operation? operation?
YES NO
CHECK 7 YES
Is refrigerant Correct the insufficient low
insufficient? refrigerant condition.
NO
Replace the relevant
PCB(s) (2).
If the error recurs, replace
the electronic expansion
valve (refrigerant jacket)
(Y3E).
Error Code U1
Method of Error The phase of each phase is detected by phase detection circuit and open phase is judged.
Detection
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Power supply
harness
(3-phase, 4 wires) is NO
Connect the harness properly.
properly connected to
the terminal
block.
YES
Power supply
voltage falls within NO
380 V to 415 V between Check the power supply for
L1-L2, L2-L3 and abnormalities.
L3-L1.
YES
The connectors
between the terminal
block, noise filter PCB and NO
inverter PCB are properly Connect the connectors properly.
connected.
YES
YES
Replace the noise filter PCB (A2P) and
the inverter PCB (A3P).
Error Code U2
Method of Error Detect the voltage of capacitor of the main circuit in the outdoor unit main PCB.
Detection
Error Decision When the voltage in the DC circuit (between diode module and power module) falls below
Conditions 220-240 VDC (RXYMQ4AVMK) or 380 VDC (RXYMQ4-6AYFK).
Troubleshooting RXYMQ4AVMK
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
NO
The insulation
resistance of the YES
compressor is less than Replace the compressor
100 k . (M1C).
NO
The insulation
resistance of the fan YES
Replace the fan motor.
motor is less
than 1 M . If the motor gets severely
damaged, the outdoor
unit main PCB (A1P)
NO should also be replaced.
CHECK 4
NO
Is the power Replace the outdoor unit
transistor normal? main PCB (A1P).
The
outdoor unit main YES
Replace the outdoor unit
PCB has damage.
main PCB (A1P).
If the outdoor unit main
NO PCB gets severely
damaged, the
compressor and the fan
Turn ON the power supply, motor may have been
and then press the ON button. damaged.
The
system enters
standby mode before the YES
Replace the outdoor unit
outdoor fan starts main PCB (A1P).
rotating.
NO
The
system enters
standby mode before YES
completing the startup Replace the outdoor unit
operation of the main PCB (A1P).
compressor. If the outdoor unit main
PCB gets severely
NO damaged, check for the
compressor.
YES
The error U2 recurs. Check for wirings.
NO
Continue operation.
The error could have
resulted from causes such
as instantaneous power
failure.
RXYMQ4-6AYFK
NO
The
insulation resistance YES
of the compressor is less Replace the compressor
than 100 k . (M1C).
NO
The insulation
resistance of the fan motor YES Replace the fan motor
is less than (M1F).
1M . If the motor gets severely
damaged, the inverter
PCB (A3P) should also
NO be replaced.
CHECK 4
Is the power NO Replace the inverter PCB
transistor normal? (A3P).
YES
The
system enters
standby mode before the YES
Replace the inverter PCB
outdoor unit fan starts (A3P).
rotating.
NO
The system
enters standby
mode before completing YES Replace the inverter PCB
the startup operation of the (A3P).
compressor.
If the inverter PCB gets
severely damaged, check
NO for the compressor.
NO
Continue operation.
The error could have
resulted from causes such
as instantaneous power
failure.
Error Code U3
Method of Error The check operation has not been executed.
Detection
Error Decision Error is decided when the unit starts operation without check operation.
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Error Code U4
Method of Error Microcomputer checks if transmission between indoor and outdoor units is normal.
Detection
Error Decision Transmission is not carried out normally for a certain amount of time.
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
NO
U4-01 Go to the next page.
U4-03
YES (Indoor unit system
transmission error)
Has the
indoor or
outdoor unit PCB
been replaced, or has YES
the indoor-outdoor Press and hold RETURN
transmission (BS3) on the master outdoor
wiring been unit main PCB (A1P) for a
modified? period of 5 seconds or more.
(The system will not operate
for a period of 12 minutes at
maximum.)
NO
Do all
indoor unit Are the
remote controllers in NO indoor-outdoor YES
the same refrigerant transmission wirings Replace the indoor unit PCB.
system display normal?
U4?
YES NO
Modify the transmission
wirings.
Reset the power supply once.
Correct the voltage.
(2)
YES YES
Are the
indoor-outdoor NO
transmission wirings Modify the transmission
normal? wirings.
YES
Replace the outdoor unit main
PCB (A1P).
U4-03
Indication YES
after launch test Check controller indoor units:
operation? (1) Some error about
thermistor, or fan motor,
electronic expansion
NO valve, or defective PCB.
(2) Test operation was
Operate all indoor units. interrupted by the MODE
(BS1) button.
NO
Do all units display U9? Check all indoor error
indication.
YES
Error code U5
Method of Error Microcomputer checks if transmission between indoor unit and remote controller is normal.
Detection
Error Decision When transmission is not carried out normally for a certain amount of time.
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Main/Sub
Control by 2 YES setting of both YES
remote controllers remote controllers is Set one of the remote
set to Main. controllers to Sub, turn OFF
the power supply temporarily,
NO then restart operation.
NO
Resets
All indoor unit NO normally when NO
PCB microcomputer power supply is turned Replace the indoor unit
normal monitors OFF temporarily. PCB.
blinking
YES YES
The error could be produced by
Replace the remote controller noise. Check the surrounding
and restart operation. area and restart operation. (Ex.:
Heavy-duty wireless equipment,
etc.)
YES
Is operation normal? Normal.
NO
YES
Is operation normal? Normal.
NO
The error could be produced by
noise. Check the surrounding
area and restart operation.
Error Code U7
Method of Error Microcomputer checks if transmission between outdoor units is normal.
Detection
Error Decision Transmission is not carried out normally for a certain amount of time
Conditions
Supposed Connection error of transmission wirings between outdoor unit and external control adaptor
Causes for outdoor unit
Cool/Heat selection setting error
Cool/Heat unified address setting error (functional unit, external control adaptor for outdoor
unit)
Defective outdoor unit main PCB
Defective external control adaptor for outdoor unit
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
U7-01
Error code Sub code
Go to Diagnosis Flowchart-1.
(Transmission error when the
external control adaptor is
mounted)
U7-02
Error code Sub code
Go to Diagnosis Flowchart-2.
(Transmission error when the
external control adaptor is
mounted)
U7-11
Error code Sub code
Go to Diagnosis Flowchart-11.
(Connection of excess indoor
units for test operation)
Diagnosis Flowchart-1
U7-01
Error code Sub code
Is
there any
wiring
disconnection or wiring NO
error in the transmission Modify the transmission wirings
wirings to the external to the external control adaptor for
control adaptor for outdoor unit.
outdoor unit?
YES
Is the
microcomputer
normal monitor on the NO Is power supplied to NO
outdoor unit main PCB Supply power to the outdoor
the outdoor unit? unit.
blinking?
YES YES
Replace the outdoor unit main
PCB (A1P).
Is the
Is the power supply
microcomputer cable of the external
normal monitor on the NO NO
control adaptor for outdoor Connect the power supply cable
external control adaptor unit connected to the
for outdoor unit of the external control adaptor
16 VDC power for outdoor unit to the 16 VDC
blinking? supply line? power supply line.
YES YES
Replace the external control
adaptor PCB.
Replace the outdoor unit
main PCB (A1P).
Diagnosis Flowchart-2
U7-02
Error code Sub code
Cool/Heat
selection for the
external control adaptor YES
Unified Cool/Heat
for outdoor unit is set to addresses for outdoor
“Unified Master”. units in the
outdoor-outdoor
transmission are
NO duplicated. Make
address setting again.
Cool/Heat
selection for the
external control adaptor for NO
Replace the outdoor unit
outdoor unit is set to main PCB (A1P).
“Unified Slave”.
YES
Is the
microcomputer
normal monitor on the NO Is power supplied NO
to the outdoor unit? Supply power to the
outdoor unit control outdoor unit.
PCB blinking?
YES
YES Replace the outdoor unit
main PCB (A1P).
Is the Is the power
microcomputer supply cable of the
normal monitor on the NO external control adaptor for NO
external control adaptor for Connect the power
outdoor unit connected to
outdoor unit supply cable of the
the 16 VDC power
blinking? external control adaptor
supply line?
for outdoor unit to the
16 VDC power supply
YES line.
YES
Does
the error
recur when setting
Cool/Heat selection for NO
the external control Replace the external control
adaptor for outdoor adaptor for outdoor unit main
unit to “IND”? PCB (A1P).
YES
Replace the outdoor unit
main PCB (A1P).
Diagnosis Flowchart-11
U7-11
Error code Sub code
There
is an error in
the connection of YES
indoor-outdoor, indoor-indoor, Rectify the error in the connection
and outdoor multi of transmission wirings, and then
transmission reset the power supply.
wirings.
NO
The
capacity to
connect indoor units NO
Check the capacity to connect
falls within the specified
range. indoor units.
YES
Replace the outdoor unit main
PCB (A1P).
Error code U8
Method of Error In case of controlling with 2 remote controllers, check the system using microcomputer if signal
Detection transmission between indoor unit and remote controller (main and sub remote controller) is
normal.
Error Decision Transmission is not carried out normally for a certain amount of time.
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Main/Sub
Using 2 remote NO setting of the remote NO
controllers control. Set Main/Sub setting of the
controller is set to remote controller to Main.
Main. Turn OFF the power supply,
YES YES and restart operation.
Main/Sub
setting of both remote NO
controllers are set to Turn the power OFF and
Sub. then restart. If an error
occurs, replace the remote
YES controller PCB.
Set Main/Sub setting of one
remote controller to Main.
Turn OFF the power supply,
and restart operation.
Error Code U9
Method of Error Detect the error signal for the other indoor unit within the circuit by outdoor unit main PCB.
Detection
Error Decision The error decision is made on any other indoor units within the system concerned.
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
YES
U9 has
been displayed for 2 NO
Re-diagnose by display after
minutes or more. passage of 2 minutes or more.
YES
The outdoor unit main PCB
indicated by the error code U9 is
normal.
Check for the indoor unit of other
system, and then conduct
troubleshooting by diagnosis
according to the Error Code
Flowchart.
Error Code UA
Method of Error A difference occurs in data by the type of refrigerant between indoor and outdoor units.
Detection The number of indoor units connected is out of the allowable range.
Error Decision The error decision is made as soon as either of the abnormalities aforementioned is detected.
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
UA-17
Error code Sub code
Go to Diagnosis Flowchart-1.
(Connection of excess indoor
units)
UA-18
Error code Sub code
Go to Diagnosis Flowchart-2.
(Connection of incorrect models
of indoor units)
UA-20
Error code Sub code
Go to Diagnosis Flowchart-3.
(Improper combination of outdoor
units)
UA-21
Error code Sub code
Go to Diagnosis Flowchart-4.
(Wrong connection)
Diagnosis Flowchart-1
UA-17
Error code Sub code
The number
of indoor units
connected to the same YES
Replace the outdoor unit main
system is less than 64. PCB (A1P).
NO
Excess indoor units are
connected.
Diagnosis Flowchart-2 Check for the connection to
connect the proper number of
UA-18 indoor units.
Error code Sub code
Check if
the refrigerant
type of the outdoor YES
unit corresponds to that Replace the outdoor unit main
of the indoor unit. PCB (A1P).
NO
Match the refrigerant types of the
outdoor unit and the indoor unit.
Diagnosis Flowchart-3
UA-20
Error code Sub code
NO
Multi connection? Replace the outdoor unit main
PCB (A1P).
YES
Was the A
outdoor unit NO different model NO
main PCB replaced with a of outdoor unit is Replace the outdoor unit main
spare PCB? connected. PCB (A1P).
YES YES
Check for the model of outdoor
unit.
NO
Was proper setting of Make setting again, and then
spare PCB made? reset the power supply.
YES
Diagnosis Flowchart-4
UA-21
Error code Sub code
Replace the outdoor unit main
PCB (A1P).
Error Code UC
Method of Error The principal indoor unit detects the same address as that of its own on any other indoor unit.
Detection
Error Decision The error decision is made as soon as the abnormality aforementioned is detected.
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Error Code UE
Method of Error Microcomputer checks if transmission between indoor unit and centralized controller is normal.
Detection
Error Decision Transmission is not carried out normally for a certain amount of time
Conditions
Supposed Transmission error between optional controllers for centralized controller and indoor unit
Causes Connector for setting main controller is disconnected.
(or disconnection of connector for independent / combined use changeover switch.)
Defective PCB for central remote controller
Defective indoor unit PCB
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Check
the indoor
unit for which
UE is displayed. Is YES
A
the transmission error
UE caused on
all indoor
units?
NO
Is the
power supply of NO
the indoor unit, on which Make sure there are no
the UE occurred, hazardous situations, and
turned ON? then turn ON the power
supply.
YES
Has
the setting of
central control Can the
NO setting of central YES
group No. been made with Make correct setting of the
the indoor unit on control group No be
made? central control group No.
which the UE
occurred?
NO
YES For
VRV systems,
can the setting of NO
central control group No. be Check outdoor units to which
made in one and the the refrigerant system is
same refrigerant connected.
system?
YES
Was the Check whether or not there
central control NO are no problems with the
group No. for indoor transmission wiring length,
unit changed? types of cables and wires,
number of units connected,
YES and others. If no problems,
replace the indoor unit PCB.
Reset the power supplies of
every centralized controller.
For the intelligent Touch
controller, register the air
conditioner again while in
DIII-NET test run menu.
Check
the transmission
wiring between NG
centralized controller for Correct the wiring.
any broken wire.
CHECK 15
OK
Check the
transmission
wiring between main NG
centralized controller for Correct the wiring.
any broken wire.
CHECK 15
OK
YES
Disconnect the transmission
wiring of the main centralized
controller, and then check the
voltage between the
transmission terminals (F1 and
F2) of the master unit
transmission equipment using
a multimeter.
Is the
voltage
between the NO
terminals F1 (+) and F2 (-) Replace the centralized
in the range of 15.2 controller.
to 17.6 VDC?
YES
Centralized controller:
Normal
It is supposed that the error
results from external factors
(e.g. noises) from other
equipment.
Error Code UF
Method of Error On check operation, the number of indoor units in terms of transmission is not corresponding to
Detection that of indoor units that have made changes in temperature.
Error Decision The error is determined as soon as the abnormality aforementioned is detected through
Conditions checking the system for any erroneous connection of units on the check operation.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
YES
Is
Is the check NO indoor-outdoor YES
operation unit transmission wiring Replace the indoor unit PCB.
carried out? normal?
YES
NO
Is
indoor-outdoor NO
unit transmission wiring After fixing incorrect wiring,
normal? press and hold the RETURN
(BS3) button on the outdoor
unit main PCB for 5 seconds.
YES The unit will not run for up to
12 minutes.
Error Code UH
Method of Error Detect an indoor unit with no auto address setting.
Detection
Error Decision The error decision is made as soon as the abnormality aforementioned is detected.
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is Does
electricity an error
being introduced occur even after
for the first time after YES 12 minutes elapses NO
installation or after an indoor from the time when electricity Normal
or outdoor unit main is introduced to indoor
PCB has been and outdoor units?
replaced?
NO YES
Is
indoor-outdoor unit NO
transmission After fixing incorrect wiring,
wiring normal? press and hold the RETURN
(BS3) button on the outdoor
YES unit main PCB for 5 seconds.
The unit will not run for up to
Press and hold the RETURN 12 minutes.
(BS3) button on the outdoor
unit main PCB for 5 seconds
NO
Does an error occur? Normal
YES
Does a UH
error occur for all NO
Replace the indoor unit PCB.
indoor units in the
system?
YES
Replace the outdoor unit main
PCB (A1P).
6. Check
6.1 High Pressure Check
CHECK 1 Referring to the Fault Tree Analysis (FTA) shown below, probe the defective points.
Defective high pressure sensor Is the pressure value checked with the Service
Checker corresponding to the measurement value of
[In heating] the pressure sensor?
If the indoor unit electronic Defective Defective indoor unit
control liquid pipe thermistor Is the connector properly connected?
expansion valve excessively Are the thermistor resistance characteristics normal?
throttled: Defective main
(2) PCB Are the voltage characteristics normal?
[In cooling] Short circuit Is the suction air temperature more than 43C?
High suction air
temperature of
High suction outdoor unit High outdoor air Is the outdoor air temperature more than 43C?
air temperature
temperature
of the High suction Short circuit Is the suction air temperature more than 27C?
condenser air temperature
High room
of indoor unit
temperature Is the room temperature more than 27C?
Defective suction air thermistor of indoor unit Is the connector properly connected?
Are the thermistor resistance characteristics normal?
[In heating]
High suction air temperature of outdoor unit Is the outdoor air temperature more than 16CWB?
Defective outdoor air temperature thermistor of outdoor unit Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Degradation Dirty condenser Is the heat exchanger clogged? (In cooling)
in condensing
capacity
Mixing of non-condensable gas Is air or else mixed in the refrigerant system?
Improper model selection [In heating] Is the indoor unit too small compared to
the large-sized outdoor unit?
Note(s)
1. In cooling, it is normal if the outdoor unit electronic expansion valve (main) is fully
open.
2. In heating, the indoor unit electronic expansion valve is used for subcooling
degree control.
Defective outdoor Defective valve coil Are the coil resistance and insulation normal?
[In heating] unit electronic
If the outdoor unit expansion valve Defective valve body
electronic
expansion valve Defective low pressure Is the pressure value checked with the Service Checker corresponding
excessively sensor to the measurement value of the pressure sensor?
throttled: Defective Defective suction pipe
thermistor Check for the thermistor resistance and connection.
(4) control
Defective main PCB
[In cooling] Low suction air Short circuit Is the suction air temperature less than 14°C?
temperature of
indoor unit Low room temperature Is the room temperature less than 14°C?
Low suction air
temperature of Defective suction air thermistor of indoor unit Is the connector properly connected?
Are the thermistor resistance characteristics normal?
the evaporator
Low suction air temperature of outdoor unit Is the outdoor air temperature less than –20°C?
Defective outdoor air temperature thermistor of outdoor unit Is the connector properly connected?
[In heating]
Are the thermistor resistance characteristics normal?
Abnormal piping length Does the piping length fall in the permissible range?
High pipe
Bent or crashed pipe Conduct visual checks for pipe conditions.
resistance
Clogging of foreign materials Is there any temperature difference caused before and after the filter or
branch pipe?
Stop valve closed Check to be sure the stop valve is open.
Less
circulation
quantity of Refrigerant shortage Refer to CHECK 7.
refrigerant Moisture choke Eliminate moisture by vacuum operation. (Refer to CHECK 8.)
Note(s)
1. For details of compressor capacity control while in cooling refer to Compressor
Capacity Control on page 56.
2. The “low pressure protection control” includes low pressure protection control and
hot gas bypass control.
3. In cooling, the indoor unit electronic expansion valve is used for “superheating
degree control”.
4. In heating, the outdoor unit electronic expansion valve is used for “superheating
degree control of outdoor heat exchanger”.
Superheat due to
shaft damage
Compressor
overheat Superheat due to
defective compressor
Defective indoor Defective valve coil Are the coil resistance and insulation normal?
unit electronic
[In cooling] expansion valve Defective valve body
If the indoor unit
electronic Defective gas pipe Is the connector properly connected?
expansion valve is thermistor of indoor unit Are the thermistor resistance characteristics normal?
throttled too much: Defective
(2) control Defective thermistor for
indoor unit liquid pipe Is the connector properly connected?
Defective Are the thermistor resistance characteristics normal?
superheating
degree Defective main
control. PCB
Defective Defective valve coil Are the coil resistance and insulation normal?
outdoor unit
electronic
expansion valve Defective valve body
[In heating]
Defective low pressure Is the pressure value checked with the Service
If the outdoor unit Checker corresponding to the measurement
electronic sensor
value of the pressure sensor?
expansion valve Defective Defective suction pipe
control thermistor Is the connector properly connected?
excessively Are the thermistor resistance characteristics normal?
throttled: (3) Defective main Are the voltage characteristics normal?
PCB
Refrigerant
shortage Refer to CHECK 7 .
Abnormal piping length Does the piping length fall in the permissible range?
High pipe
resistance (Including moisture choke) Eliminate moisture by vacuum operation. (Refer to CHECK 8 .)
Note(s)
1. Refer to “Low pressure protection control” for hot gas bypass control.
2. “Superheating temperature control” in cooling is conducted by indoor unit electronic
expansion valve.
3. Superheating temperature control in heating is conducted by outdoor unit electronic
expansion valve (main).
4. After verifying the residual voltage, pull out the outdoor fan motor connector.
If a strong wind causes the outdoor fan to rotate, the capacitor may store electricity.
Therefore, make sure that the fan is still and then pull out the outdoor fan motor connector.
5. Disconnect the connection wire between the power transistor and the compressor.
Remove the connection wire from the compressor.
At this point, make sure that there is no deformation of the Faston terminal at the front end of
the connection wire.
6. Use a multimeter to measure the resistance listed in the table.
Among the three phases listed in the table, if there is one phase with unbalanced resistance
(with a value five times higher than the other values), then the power transistor is defective.
When normal, all phases have the same resistance value.
Multimeter Resistance Multimeter Resistance
Red (+) Black (–) Red (+) Black (–)
C+ U C– U
C+ V C– V
C+ W C– W
U C+ U C–
V C+ V C–
W C+ W C–
Compressor
RXYMQ4-6AYFK
Perform the following procedures prior to check.
(1) Power OFF.
(2) Remove all the wiring connected to the PCB where power transistors are mounted on.
When using the digital type of multimeter, make measurement in diode check mode.
Measuring point Judgment
No. Remarks
+ – Criteria
1 P2 U Due to
condenser
2 P2 V charge and so
1.2 V and more on, resistance
measurement
3 P2 W may require
some time.
4 U P2
5 V P2
6 W P2
0.3 ~ 0.7 V ―
7 N32 U
8 N32 V
9 N32 W
10 U N32 Due to
condenser
11 V N32 charge and so
on, resistance
1.2 V and more measurement
12 W N32 may require
some time.
N32
P2
Cooling
High pressure
dropping control
High pressure Frequency comes to
gradually rises with the minimum level.
increase in
frequency. Subcooling degree
becomes higher.
(Liquid connection
High pressure pipe temperature
lowers.)
(Low pressure is
maintained at a
constant level.)
Low pressure
Low pressure rises due
to decreased
compressor output.
Frequency
(Degree of overcharge)
Proper amount Higher degree of overcharge
(Degree of overcharge)
Proper amount Higher degree of overcharge
Cooling
The opening degree of the indoor unit Fan control is activated for high
electronic expansion valve becomes pressure protection under
larger. cooling control at low outdoor
Either of the electronic expansion air temperature, i.e., the fan is
valves becomes fully open. hunting at high pressure.
Frequency comes to the minimum level.
High pressure
(Low pressure
is maintained at High pressure drops
a constant with decrease in
level.) compressor capacity.
Low pressure
Low pressure rises as the
opening degree of the indoor
unit electronic expansion
valve becomes larger.
Frequency slightly increases If frequency comes to the
under the capacity control. minimum level, low
Frequency pressure cannot be
maintained.
To maintain low
pressure,
frequency drops
due to the
capacity control.
Heating
The opening degree of the outdoor unit electronic expansion valve becomes larger.
The outdoor unit electronic expansion valve fully opens and frequency increases.
Discharge pipe or low pressure dropping control
Frequency comes to
High pressure the minimum level.
(High pressure
is maintained at
a constant
level.)
Low pressure
Frequency
Detected Pressure
4.15 4.15
PH (MPa) = × VH – × 0.5
PH, PL 3.0 3.0
(kg/cm2)(MPa) 1.7 1.7
PL (MPa) = × VL – × 0.5
51.0 5.0 3.0 3.0
35.7 3.5
30.6 3.0
25.5 2.5
20.4 2.0
Low Pressure (PL)
15.3 1.5
10.2 1.0
5.1 0.5
0 0
–5.1 –0.5
–0.5 0 0.5 1 1.5 2 2.5 3 3.5 4
Output Voltage VH, VL (VDC)
(4) Red
Black High
(3)
pressure
sensor
(2)
Microcomputer
A/D input (1) White
Make measurement of DC
voltage between these wires.
X31A (Blue)
(4) Red
a b c d Outdoor
unit
Red U
White V
Black W
Red
White
Black
Judgment
Model
Black-Red Black-White
FXDQ20-32PD 81.0 ± 10% 102.0 ± 10%
FXDQ40ND 81.0 ± 10% 102.0 ± 10%
FXDQ50/63ND 44.0 ± 10% 44.0 ± 10%
FXMQ50-140PB
Measurement of power wire connector.
Remove the X1A connector from the fan PCB (A2P) and measure the resistance between the
U and V, V and W, and W and U phases of the motor connector (with five conductors) and
check that each phase are balanced (within a permissible dispersion range of ±20%)
Connector power wire use (X1A)
Red (5) U
— (4)
White (3) V
— (2)
Black (1) W
White (1) FG
— (5) —
— (6) —
FXMQ50-140PB
Measurement of signal wire connector.
Remove the X2A connector and measure the resistance between GND and Vcc, Hw, Hv, or Hu
terminals of the motor connector (with five conductors).
Connector signal wire use (X2A)
Orange (3) Hw
Blue (2) HV
Yellow (1) HU
Outdoor unit
X21A (Y1E)
X22A (Y2E) *2
X23A (Y3E)
X22A (Y2E) *1 X25A (Y4E)
(White) 1 (Orange) 1
(Yellow) 2 (Red) 2
Measuring points Judgment criteria
(Orange) 3 (Yellow) 3
1-6
(Blue) 4 (Black) 4 2-6
35-55
3-6
— 5 — 5 4-6
(1) Orange
(2) Red
(3) Yellow
(4) Black
(5) —
(6) Gray
FXDQ-PD, FXDQ-ND
White (1)
φ1 Measuring points Judgment criteria
Red (6) M 1-2 No continuity
φ3
Orange (3) 1-3 92 Ω
1-6 46 Ω
φ2 φ4 2-4 92 Ω
2-6 46 Ω
Yellow Blue
(2) (4)
(1) White
(2) Yellow
(3) Orange
(4) Blue
(5) —
(6) Red
FXMQ-AR
White (1) Measuring points Judgment criteria
1
Red (6) M 1-2 No continuity
3 1-3 300
Orange (3)
1-6 150
2 4
2-4 300
2-6 150
Yellow Blue
(2) (4)
Blue — Orange
(4) (5) (3)
FXAQ-AR
White (1) Measuring points Judgment criteria
1
1-2 No continuity
Red (5) M
3 1-3 300
Orange (3) 1-5 150
2-4 300
2 4
2-6 150
Yellow Brown Blue
(2) (6) (4)
(1) White
(2) Yellow
(3) Orange
(4) Blue
(5) Red
(6) Brown
Part 7
Appendix
1. Wiring Diagrams..................................................................................291
1.1 Outdoor Unit .........................................................................................291
1.2 VRV Indoor Unit ...................................................................................293
1. Wiring Diagrams
1.1 Outdoor Unit
RXYMQ4AVMK
C: 3D133942
RXYMQ4/5/6AYFK
C: 3D133944A
3D121473A
3D130909
3D124914B
3D110450B
FXMQ40/50/63/80/100ARV1
3D127112
);04$59
'
;$
1.2.5 Wall Mounted
FXAQ20/25/32/40/50/63ARVM
;$
32:(56833/< 02'(/1$0(
~ 9+] );$ 5 4$59(
~ 9+] );$4$59(*
~9 );$4$590
+]
')
3D118250G
SiME332106E
Part 7 Appendix
Warning z Daikin products are manufactured for export to numerous countries throughout the world. Prior to
purchase, please confirm with your local authorized importer, distributor and/or retailer whether this
product conforms to the applicable standards, and is suitable for use, in the region where the product
will be used. This statement does not purport to exclude, restrict or modify the application of any local
legislation.
z Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
z Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorized parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
z Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any inquiries, please contact your local importer, distributor and/or retailer.
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
https://www.daikin.com/products/ac/
© All rights reserved
Specifications, designs and other content appearing in this brochure are current as of September 2021 but subject to change without notice.
SiME332106E
09/2021 AK.K