MANY0706A.GB - Technical Manual Metacentre P4
MANY0706A.GB - Technical Manual Metacentre P4
MANY0706A.GB - Technical Manual Metacentre P4
bar
TM
P4
Metacentre P4
Index
4.0 Installation
4.1 Unit Location
4.2 Power Supply
4.3 Pressure Sensor Location
4.4 Compressor Interface PCB
4.5 Auxiliary Input
4.6 Auxiliary Output
4.7 RS485 Communications
5.0 Commissioning
5.1 Physical Checks
5.2 Pressure Display
5.3 Unit Configuration
5.4 Optional Features and Functions
7.0 Operation
7.1 User Interface
7.2 Sequence Rotation
7.3 Unit Status
7.4 Compressor Status
7.5 Unit Functions
7.6 Information Displays
7.7 Manual Sequence Rotation
7.8 Compressor Identification
7.9 Stop
7.10 Start
7.11 Power Failure Auto Restart
7.12 Failure Mode
7.13 Reset
7.14 Fault Codes
Page 1
Technical Manual
Lethal voltages are used within the product. Use 1.3 Service Maintenance and Repair
extreme caution when carrying out electrical
checks. Isolate the power supply before starting any Service, maintenance, repairs or modifications must
maintenance work. only be carried out by competent personnel under
qualified supervision.
It is not possible to anticipate every circumstance
that might represent a potential hazard. If the user If replacement parts are required use only genuine
employs an operating procedure, an item of parts from the original equipment manufacturer, or
equipment or a method of working which is not an alternative approved source.
specifically recommended the user must ensure the Carry out the following operations before opening or
product will not be damaged or made unsafe and removing any access panels or carrying out any
that there is no risk to persons or property. Failure work on the product :-
to observe safety precautions or implement safe
working practises may be considered dangerous • Isolate from the main electrical power supply.
practice or misuse of the product. Lock the isolator in the 'OFF' position and
remove the fuses.
1.2 Installation • Attach a label to the isolator switch and to the
product stating ‘WORK IN PROGRESS - DO
Installation work must only be carried out by a NOT APPLY VOLTAGE'. Do not switch on
competent person under qualified supervision. electrical power or attempt to start the unit if
A fused isolation switch must be fitted between the such a warning label is attached.
main power supply and the product. Ensure that all instructions concerning operation
The product should be mounted in such a location and maintenance are strictly followed and that the
as to allow operational and maintenance access complete product, with all accessories and safety
without obstruction or hazard and to allow clear devices, is kept in good working order.
visibility of indicators at all times. The accuracy of sensor devices must be checked
If raised platforms are required to provide access to on a regular basis. They must be renewed when
the product they must not interfere with normal acceptable tolerances are exceeded. Always ensure
operation or obstruct access. Platforms and stairs any pressure within a compressed air system is
should be of grid or plate construction with safety safely vented to atmosphere before attempting to
rails on all open sides. remove or install a sensor device.
The product must only be cleaned with a damp
1.3 Operation cloth, using mild detergents if necessary. Avoid the
The product must only be operated by competent use of any substances containing corrosive acids or
personnel under qualified supervision. alkalis.
Never remove or tamper with safety devices, guards Do not paint the control facial or obscure any
or insulation materials fitted to the unit. indications, controls, instructions or warnings.
Page 2
Metacentre P4
2. INTRODUCTION
The Metacentre P4 is a specialised 2.2 Pressure Detection and Control
supervisory and control product designed to
provide energy efficient optimised pressure The Metacentre P4 utilises the signal from an
and sequence management of up to 4 air electronic pressure sensor that can be
compressors operating on a common air mounted remotely from the Metacentre P4 in a
system. The Metacentre P4’s general suitable location in the compressed air
operating mode can be modified by a number system.
of adjustable parameters and priorities to
enable operation to be matched to site
requirements and characteristics.
1 2 3 4
Page 3
Technical Manual
a
PH
PT a
PL PH
b PT
PL
b
c
PH
PT
PL
Page 4
Metacentre P4
Tolerance is a pressure band above and In situations where the loading of an additional
below the set pressure control levels that compressor, at the PL pressure set point, is
accommodates for an exceptional instance of inadequate to match a significant and/or
abrupt and/or significant increase, or abrupt increase in air demand the additional
decrease, in demand without compromise to reaction of the P4, while pressure deviates into
optimal energy efficient control. the ‘tolerance’ limit, is dynamically calculated.
The time before an additional compressor is
loaded, to increase generation capacity
PH + TO
further, will vary in accordance with the
TO
urgency of the situation.
PH
PT
The P4’s dynamic reaction algorithm is pre-set
PL
by default to accommodate for the majority of
TO
installation characteristics.
PL - TO
Page 5
Technical Manual
Page 6
Metacentre P4
Each compressor in a system is initially The new sequence order arrangement after a
assigned to the P4 with a fixed and rotation event would be:
unchanging number reference, 1 to 4.
Compressor 1 = D
The ‘duty’ that a compressor is assigned in Compressor 2 = B
any set ‘Rotation’ sequence arrangement is Compressor 3 = A
defined by a letter, A to D. Compressor 4 = C
A = the ‘Duty’ compressor, the first to be Compressor 3, that has the least recorded
utilised. running hours, will now be utilised to a greater
B = The ‘Standby’ compressor, the second to extent in the new sequence arrangement;
be utilised. potentially increasing the running hours at a
C = The ‘Second Standby’ compressor, the faster rate.
third to be utilised.
D = The ‘Third Standby’ compressor, the forth The P4 continuously monitors the running
to be utilised. status of each compressor and maintains a
record of the accumulated running hours.
Compressor ‘duty’ assignments are reviewed, These are available, and adjustable, in the
and re-arranged as appropriate in accordance P4’s compressor running hour’s menu. The P4
with the selected rotation strategy, at each uses these values in EHR mode. The P4’s
rotation event. running hours record should be routinely
checked, and adjusted if necessary, to ensure
a close match with the actual run hours
Equal Hours Run Mode displayed on each compressor.
Page 7
Technical Manual
Page 8
Metacentre P4
As demand reduces (D) is the first compressor This feature is intended to allow the system to
to be unloaded, followed by (C) and then (B) if react to changes in pressure target levels in a
demand continues to reduce. smooth and energy efficient manner without
abrupt overreaction.
The last compressor to be unloaded, if
demand reduces significantly, is (A). The
compressor assigned as (A) in the sequence 1 2
is the first to be loaded and the last to be
unloaded.
Tables:
When pressure set points change, a change Select the ‘day’ or day function as
from one ‘Table’ to another, the P4 will required:
increase, or decrease, the pressure target
levels towards the new table settings in a #1 = Monday to #7 = Sunday
gradual transition over a period of time. #8 = each working day of the week, excluding
Saturday and Sunday
#9 = each working day of the weeky.
#- (dash) = deactivate
Page 9
Technical Manual
#2 A C D B
To define an interval time (more than
one rotation event a day) select ‘#t’ for the day #3 A D B C
function and press Enter:
#4 A B C D
S01 04.02 RP
Example 2:
For a four-compressor system, that includes a
#t 12:00 compressor (for example compressor 4) that is
2 less efficient, or otherwise less desirable to
operate for other reasons, it may be
convenient to ensure the compressor is only
utilised as an emergency backup. To achieve
this assign compressor number 4 with a lower
An ‘intervals per day’ value will appear and
priority.
flash. Select the required number of rotation
events per day (1 to 96). The hour and
Compressors 1 to 3 = priority 1
minutes display will now show the interval time
Compressor 4 = priority 2
between each rotation event; 1 = every 24hrs
to 96 = every 15 minutes (example: 2 = every
12hrs). 1 2 3 4
#2 B C A D
#4 A B C D
Priority settings can be used to modify the
‘Rotation’ sequence assignment. Compressors Example 3:
can be assigned a ‘priority’ of 1 to 4; where 1 For a four-compressor system that includes a
is the highest priority. Any compressor can be variable speed compressor (compressor
assigned any priority and any number of number 1) and a fixed speed compressor that
compressors can have the same priority. is only required as an emergency backup
(compressor number 4) it may be desirable to
Example 1: ensure the variable speed compressor is
For a four-compressor system, that includes a always utilised first, and the backup
single variable speed compressor assigned as compressor utilised last, in any sequence
compressor number ‘1’, it may be desirable to arrangement.
ensure the variable speed compressor is
continuously utilised in any sequence Compressor 1 (variable speed) = priority 1
arrangement as the ‘duty’ or ‘top-up’ unit. To Compressors 2 and 3 = priority 2
achieve this assign compressor number 1 with Compressor 4 (back-up) = priority 3
a higher priority than the remaining three fixed
speed compressors.
Page 10
Metacentre P4
3.7 Prefill:
1 2 3 4
Example 4:
Compressors can be separated in to rotation
groups. In this example compressors 1 and 2,
of a four-compressor system, have been set
as a high priority group and compressors 3
and 4 as a lower priority group. Compressors
1 and 2 will always be utilised first in any
sequence arrangement and will be rotated at At system start (manual start or automated
each ‘Rotation’ event. Compressors 3 and 4 start from standby) the P4 will only load
will always be utilised as lower priority in any compressors that have been pre-set for prefill
sequence arrangement and will be rotated at operation, for a pre-set period of time. The
each ‘Rotation’ event. prefill time (PT) can be adjusted to suit system
characteristics. The aim is to increase
1 2 3 4 pressure to normal operational levels, using
only the pre-determined compressors, prior to
1 1 2 2 the prefill time expiring.
Page 11
Technical Manual
P01 01.0# 01
# - --:--
---
0# = 01 02 04 03
Page 12
Metacentre P4
VOLTAGE SELECT
Regular routine monitoring of pressure
115Vac differential across air treatment equipment is
recommended.
Check the input voltage select link wires on
4.4 Pressure Sensor Connection
the P4’s power supply PCB, adjust if
necessary.
The pressure sensor must be connected to
terminal X05 of the P4 using an earth
4.3 Pressure Sensor Location screened, two-core (0.5mm2 CSA minimum),
cable no greater than 100m (330ft) in length.
The system pressure sensor (P) must be
located in a position that will continuously
X05
experience pressure that is common to all
-
compressors. 26
25
+ +
Generation Side Pressure Control: 4-20mA
P
1
Page 13
Technical Manual
4.5 Compressor Interface PCB The ‘i-PCB’ uses a 12V to 250V input voltage
detection system and universal relay contact
The ‘i-PCB’ is designed to interface a control outputs (250V ‘CE’ / 115V ‘UL’ @ 5A
compressor with the P4 using a 6-core, earth maximum). Integrated directly into the circuits
shielded, cable no greater than 100m (330ft) of an air compressor, the ‘i-PCB’ avoids the
in length. need for additional relays or remote inputs.
The ‘i-PCB’ also acts as an electrical barrier
Each compressor in the system must be between the compressor and the P4 providing
assigned a unique identification number from protection and voltage isolation.
1 up to the number of compressors in the
system. The identification number should be 3.5.1 Input Functions
clearly indicated on each compressor for
operational reference. The ‘i-PCB’ is fitted with a six-pin terminal C04
for compressor monitoring. The ‘i-PCB’ uses
For each compressor connected to the P4 two inputs (Ready and Run) to determine
utilising an ‘i-PCB,’ the signal wires must be compressor status. An Alarm input can be
connected to the P4 terminals dedicated for used if compressor alarm indication is
the assigned compressor reference number. available and required. The Alarm input is
optional and is not necessary for system
operation.
Ready Input:
C01 C02 C04
The ‘Ready’ connection is intended to indicate
that the compressor is in a ‘started’ state, has
i-PCB #1 no operational inhibiting fault condition and is
C03 ready to respond to P4 regulation without
1 2 3 4 5 6 C05 manual intervention.
READY LAMP 0V
LED 1 LED 2
+V
X01
1 2 3 4 5 6
Page 14
Metacentre P4
0Vac
+V
0V
+V
0V
READY AUXILIARY SWITCH
Page 15
Technical Manual
requirement. Seq
IN
Alarm Lamp OUT NO
0V C
+V
IN
3
C
OUT
2 IN
NC
NC
C03
Page 16
Metacentre P4
+V
Note: Compressors that use electronic
pressure detection but are not equipped with a
LOAD remote pressure control enable feature will not
SOLENOID
automatically revert to local control if the P4 is
stopped or experiences a fault or loss of
power.
COMPRESSOR CONTROLLER
INPUTS
C
NC
NO
C
NC
NO
OUT IN
C02
Remote Load Local/Remote
or
Remote Load Enable
Inputs Common
Three Wire Pressure Switch Connections:
LOAD
SOLENOID
0V
+V
C01
RUN-ON
TIMER
SEQ
LOAD
C
NC
C
NC
NO
OUT IN
C02 stopped or experiences a fault or loss of
power.
Page 17
Technical Manual
Page 18
Metacentre P4
The P4 is equipped with an auxiliary input; The P4 is equipped with an RS485 network
terminals 31 and 32 (X07). communications capability using the Multi485
protocol. This facility can be used for remote
The function of the input is menu selectable connectivity to optional networked units and
and can be adapted for differing application modules with Multi485 communications
requirements. capabilities.
X06
Menu Items – S02:AI
L1 30 L1
L2 29 L2
X07 28 RS485
32 27
31
The function of the output is menu selectable a) Never route an RS485 data
and can be adapted for differing application communications or low voltage signal cable
requirements. alongside a high voltage or 3-phase power
supply cable. If it is necessary to cross the
path of a power supply cable(s), always cross
Menu Items – S02:AO at a right angle.
Page 19
Technical Manual
Before applying power to the P4 ensure that S01 - Ct Real Time Clock Set
the power supply connections are correct and S01 - AR Auto Restart Enable
secure and that the operating voltage selector S01 - RP Rotation Interval
is set correctly for the power supply voltage in
use; 115Vac or 230Vac (+-10%), 50/60Hz. C02 – 01/04 Compressor #1-4
Configuration
Open the front panel of the P4 and check the
location of the link wire(s) connected to the C01 - 01/04 Compressor #1-4
‘Voltage Selection’ terminals of the power Running Hours
supply PCB. If necessary, change the link wire
locations to those illustrated for the voltage in T01 - PH High Pressure Set Point
use. T01 - PL Low Pressure Set Point
T01 - Pm Minimum Pressure Alarm
T01 - SQ Sequence Algorithm
Installation T01 – 01/04 Compressor #1-4 Priority
Switch on the power supply to the P4. 5.4 Optional Features and Functions
The control program identification will be Installation requirements may involve the
displayed for a short period followed by the implementation of additional or optional
normal operational User display. functions and features; implement as required.
Menu Navigation
Page 20
Metacentre P4
Page 21
Technical Manual
Page 0 Page 1
Page 2
Item 1 Value
Item 2 Value Page 3 Item 1 Value
Item 3 Value Item 2 Value
Page 4
Item 4 Value Item 3 Value
Item 5 Value Page 5 Item 4 Value
Item 6 Value Item 5 Value
Page 0 Page 1
Page 2
Item 1 Value
Item 2 Value Page 3
Item 1 Value
Item 3 Value Item 2 Value
Page 4
Item 4 Value Item 3 Value
Item 5 Value Page 5 Item 4 Value
Item 6 Value Item 5 Value
Page 22
Metacentre P4
6.1 Menus:
Fault Log
E01
Page 23
Technical Manual
Configuration Diagnostics
S02 D01
Sensor Calibration
S04
1O Pressure Offset
1R Pressure Range
Compressor Configuration
C02
01 Compressor #1 Configuration
to
04 Compressor #4 Configuration
Page 24
Metacentre P4
Tables P01 – 01 to 28
The ‘Pressure Schedule’ items 01 to 28
T0# – PH High Pressure Set Point
The ‘upper’ or ‘unload’ pressure set point that
will be used when the ‘Table’ is active.
P02
07 04 X
T0# - PL Low Pressure Set Point
The ‘lower’ or ‘load’ pressure set point that will 01 PF X
be used when the ‘Table’ is active. 02 PT - MIN
T0# - Pm Minimum Pressure Alarm
03 PP 0 BAR
The miniumum pressure ‘Warning’ or ‘Alarm’ 04 01 X
level that will be used when the ‘Table’ is
active.
Prefill
T0# - SQ Sequence Strategy
The sequence control strategy mode that will P02 - PF Prefill Function
be used when the table is active. Determines the ‘Prefill’ strategy or function that
will be used at system startup.
T0# - 01 Compressor #1 Priority
The ‘priority’ setting for compressor number #1
that will be used when the table is active. = Prefill function OFF
= Prefill, Back-up Mode
T0# - 02 Compressor #2 Priority ! X
The ‘priority’ setting for compressor number #2 = Prefill, Standard Mode
that will be used when the table is active.
P02 - PT Prefill Time
T0# - 03 Compressor #3 Priority Sets the maximum time allowed for a system
The ‘priority’ setting for compressor number #3 ‘Prefill’ at startup.
that will be used when the table is active.
P02 - PP Prefill Pressure
T0# - 04 Compressor #4 Priority If pressure is at, or above, this setting at
The ‘priority’ setting for compressor number #4 system startup the prefill function will be
that will be used when the table is active. abandoned immediately and normal pressure
control and sequence strategy will be
# = Table 01, 02 or 03 implemented. This setting is intended to inhibit
‘Prefill’ operation if pressure is already at an
acceptible level at system startup.
Priority Settings:
: compressor(s) can be inhibited from use P02 – 01 to 04 Compressor #1 to #4
while a table is active by selecting “X” priority. The function of compressor #1 to #4 during
The compressor will be held offload and will the ‘Prefill’ period.
not be utilised under any circumstances.
= do not use
= use for primary prefill
! = use for emergency backup
Page 25
Technical Manual
C01 1
Compressor Connectivity:
+V=!
Page 26
Metacentre P4
E01 S01
15 -: --- . -- 06 BL 5
01 E : ERR . 01 08 Ct 1 . 18:00
02 -:--- . -- 08 PS X
03 -:--- . -- 08 AR
04 -:--- . -- 08 RP 9 . 00:00
E01 – 01 to 15
Features and Functions
Error Log; presented in chronological order;
entry 01 = most recent. S01 - Ct Real Time Clock Set
Adjustment for the internal real time clock.
Each error log item will show the error code. (Hours, Minutes, Date, Month, Year)
To view details for the selected error log item The ‘Day of the Week’ (1= Monday to
press ENTER. 7=Sunday) is automatically calculated and set
in accordance with the Day, Month and Year.
E01 01.01 S01 - PS Pressure Schedule Enable
The first information display shows the: = enable Power Failure Auto Restart
a) The Error Code
b) Error Code symbols (if applicable) The P4 will only automatically restart when
c) The date the error occurred power is restored if the P4 was in an
d) The time the error occurred operational ‘Started’ state when the power
e) The active operational functions of the loss or disruption occurred.
P4 at the time the error occurred;
(see: P4 Status Display) S01 - RP Rotation Interval
Sets the sequence ‘Rotation’ interval or time.
To return to the main error log menu screen
press ESCAPE. S01 - TS Default Table Select
Determines the ‘Table’ that will be used by
To view the second information screen press default when ‘Pressure Schedule’ is not active
ENTER. and no table is selected remotely on a digital
input.
Page 27
Technical Manual
Typically the display will remain usable for a S02 - AI Auxiliary Input Function
much longer period for time. Adjusting the
backlight to high levels will reduce service life.
S02 08.01 AI
S02
NO
10
01
ER
P> BAR
X 01:T1
02 NC 4
03 PM 10.0 BAR The function of the Auxiliary input.
Page 28
Metacentre P4
S02 - AO Auxiliary Output Function The contacts of the Auxiliary output relay
are rated for 115V (UL), 240V (CE), at 5 Amps
S02 09.01 AO maximum.
NO (Normally Open)
The auxiliary output relay contacts are
normally open and will close circuit when the
set function is active or true.
NC (Normally Closed)
The auxiliary output relay contacts are
normally closed and will open circuit when the
set function is active or true; or in the event of
a P4 shutdown or power supply disruption.
Page 29
Technical Manual
2) Calibration Procedure
S04
a) Offset: Expose the sensor to atmosphere
and adjust the ‘offset’ setting (if necessary)
01 1O 0 BAR until the detected pressure display shows
02 1R 16.0 BAR 0.0bar (0psi).
If the sensor is a –1.0(minus one bar.g) to Correct pressure sensor set-up and
15.0bar type, set the ‘offset’ to –1.0bar (minus calibration is critical for successful system
one bar) and the range to 15.0bar. operation. It is recommended that pressure
Note: The ‘range’ value equates to the sensor calibration is examined, and adjusted if
maximum value not the scope of the sensor. necessary, annually or a pre-determined
routine periodic basis.
Execute the calibration procedure.
Page 30
Metacentre P4
Digital Inputs:
ON (closed circuit)
Pulsing
Page 31
Technical Manual
7. OPERATION
7.1 User Interface
12:00 #1
a b
Display:
a) Time of day (24hrs)
a b b) Day of the week
#1 = Monday to #7 = Sunday
7.0
BAR
c
Press Up or Down to return to the
d 1 e Sequence/Status display.
10:35
f 1 2 3 4 7.3 Unit Status:
g A B C D
System Pressure:
h Increasing to normal operational levels
(Prefill, target pressure change or at
a) System Pressure Value system start)
b) System pressure Units Below the active lower, or load, pressure
c) Unit Status set point
d) Unit Active Functions Between the lower, or load, and upper, or
e) Time unload, active pressure set points
f) Compressor Number
g) Compressor Sequence Assignment Above the upper, or unload, active
h) Compressor Status pressure set point
Page 32
Metacentre P4
Sequence Rotation:
Equal Hours Run
P00
First In First Out
#4 18:00
Timer Rotation
18 / 05 / 2006
Active Functions:
ABCD
Power Failure Auto-Restart
Standby
1 Day of the week (#4: Thursday), the
Table #1 time of day (18:00) and the date (18/05/2006)
2 of the next automated sequence rotation
Table #2
event.
3
Table #3
Remote Manual Override The active ‘mode’ of operation
Prefill Function
“ABCD” The current active rotation sequence
Pressure Schedule assignment.
1
The current active ‘Table’ (T01)
Upper, or unload, pressure set point
Lower, or load, pressure set point
Minimum pressure Alarm (Warning)
Page 33
Technical Manual
Tables
Page 34
Metacentre P4
Each fault type has a unique numeric code. To Display the Software Version:
ERR.01 Pressure Sensor Press and hold Reset then press Escape.
The clock time display will change to show the
software version ID (example: “E01”).
ERR.04 Internal 24V Fault
Page 35
Technical Manual
20mm
IEC 5mm 5 i-PCB 6
Power 50VA
Temperature 0°C to 46°C (32°F to 115°F)
Humidity 95% RH non-condensing
8mm Ø
286mm
Page 36
Metacentre P4
33 34 35 36
C01
X08
X06 C03
C04
4
+VDC C03
3
X05
31 32
+VDC C05 C06
X07
A-GND SEQ C08
2
Ai2 C06 C07
GND C07
Ao +VDC C07
1
C08
Ai3 C08
27 28 29 30
C010
C09
X06
C09
X09
C010
C+ C019
1 C020
SEQ
C011
X08
2 C021
25 26
C012 C04
X05
3 C022
C013
X04
C03
4
L2 L1
C023
C014 C019
5 C024
+
-
19 20 21 22 23 24
C015 R-SEQ 10k
6 C025
C016 C024
24Vac
XPM485
RS485#2
GND
C026 C034 150k
C017 C06
X04
8 C027
C018 150k
C019 C012
24Vac
C020
C011
SEQ
R5 C021
X02
C012 C022
C023
C01/3
L2 L1 RS485#1
R6 C024
13 14 15 16 17 18
10k
Multi485
C01/4 C025
X07
C023
GND
C026 C027
X03
C013 C027
C09 R1
C014 C028 C018
C010
R2 C029
C015
X03
C030
R3
C016 C033
8 9 10 11 12
10k
C017 C034
24Vac
C022
R4
X01
C026
X02
C018
2
1
C031
C016
0VDC
C032
7
C029
C028
10k
6
24Vac
0Vac
C021
2 3 4 5
C025
X01
X02
XPM-TAC24
X03
C015
2
1
1
2
24Vac
1
N
E
E
L
0Vac - earthed
X01
L N E
230Vac 10%
115Vac 10%
Page 37
Technical Manual
Connection Diagram:
Terminal PCB
33 34 35 36
240V 'CE' / 115V 'UL' @ 5A maximum.
X08
Auxiliary Output #1
31 32
X07
Auxiliary Input #1
330ft (100m) max
L1
27 28 29 30
L1
X06 L2 L2
Multi485
L1
L2
100m (330ft) max
-
25 26
- Ai1 System
X05
Pressure
+ +
4-20mA
19 20 21 22 23 24
+20VDC 6
i-PCB 4
Di5 Ready/Run 5
Ai2 Alarm/Serv. 4
X04
- GND 3
100m (330ft) max
R5 LOAD 2
R1 SEQ 1
4
I-PCB 6-core
13 14 15 16 17 18
+20VDC 6
i-PCB 3
Di4 Ready/Run 5
Di8 Alarm/Serv. 4
X03
- GND 3
100m (330ft) max
R4 LOAD 2
R1 SEQ 1
3
I-PCB 6-core
+20VDC
8 9 10 11 12
6
i-PCB 2
Di3 Ready/Run 5
Di7 Alarm/Serv. 4
X02
- GND 3
100m (330ft) max
R3 LOAD 2
R1 SEQ 1
2
7
I-PCB 6-core
+20VDC
6
6
i-PCB 1
Di2 Ready/Run 5
2 3 4 5
Di6 Alarm/Serv.
X01
4
- GND 3
100m (330ft) max
R2 LOAD 2
1
R1 SEQ
1
1
I-PCB 6-core
Page 38
Metacentre P4
XPM-TAC24
Power Supply Module
BLUE BLACK
BROWN ORANGE
RED WHITE
GREEN VIOLET
1 2 3 4 X04
T3.15A T1.6A T1.6A T1.0A 1 2 3 4
115V
115V +-10%
IEC T1.0A FH1
5x20mm
1 2 3 4
X03 X02
2 1 2 X01
N L E E
24Vac/2 24Vac/1
earthed isolated NL E
Page 39
Technical Manual
P4 Commissioning Form
Customer Contact Customer Ref:
Comp #1 Manufacturer
3
Comp #1 Model/Type
bar m /min Comp #1 Working Pressure bar/psi
#1 kW VA Hz
Comp #1 Full Load Capacity m3/min
Comp #2 Manufacturer
bar m3/min Comp #2 Model/Type
#2 kW VA Hz Comp #2 Working Pressure bar/psi
Comp #2 Full Load Capacity m3/min
Comp #3 Manufacturer
bar m3/min Comp #3 Model/Type
#3 kW VA Hz Comp #3 Working Pressure bar/psi
Comp #3 Full Load Capacity m3/min
Comp #4 Manufacturer
bar m3/min Comp #4 Model/Type
#4 kW VA Hz Comp #4 Working Pressure bar/psi
Comp #4 Full Load Capacity m3/min
Page 40
Metacentre P4
Page 41