Calculation of Wind Loads On Duopitch Canopies - Eurocode 3
Calculation of Wind Loads On Duopitch Canopies - Eurocode 3
Calculation of Wind Loads On Duopitch Canopies - Eurocode 3
Eurocode Project:
Applied.com
Subject:
Free online calculation tools for structural
design according to Eurocodes Designer:
Date:
Eurocode 1
Wind load on duopitch canopies (net pressure
coefficients and overall force coefficient)
Description:
Calculation of wind load action effects on duopitch canopies (i.e. roofs of structures not enclosed with
permanent side walls). The net effect of the wind pressure on the upper and lower surface for zones A,
B, C, D on the roof surface are calculated from the corresponding net pressure coefficients. The overall
effect of the wind action on the structure is also calculated from the corresponding force coefficient.
According to:
EN 1991-1-4:2005+A1:2010 Section 7.3
Applicable for:
Roofs of structures not enclosed with permanent side walls such as petrol stations, dutch barns etc.
Duopitch slope between -20° and +30°
Supported
National
Annexes:
A) Calculation of pressure coefficients: Only countries that adopt CEN recommended values for section
7.3 of EN1991-1-4 are supported. B) Peak velocity pressure: The value of the peak velocity pressure can
be specified manually. Otherwise automatic calculation of peak velocity pressure is supported, in
addition to countries that adopt the CEN recommended values for NDPs, also for the following
National Annexes: Finland, Portugal. The National Annexes of Germany, Norway, Spain, Sweden,
Switzerland are NOT supported (enter peak velocity pressure manually).
Input
Terrain category = I
https://eurocodeapplied.com/design/en1991/wind-pressure-duopitch-canopy 1/8
2/16/24, 2:23 PM Calculation of wind loads on duopitch canopies - Eurocode 1
Definiton of blockage factor for canopy roofs (see also EN1991-1-4 Figure 7.15)
Structural factor c sc d = 1
Results
Net wind pressure on zone A wnet,A = (-0.290 or +0.290)
kN/m2
Net wind pressure on zone B wnet,B = (-0.665 or +0.843)
kN/m2
Net wind pressure on zone C wnet,C = (-0.656 or +0.618)
kN/m2
Net wind pressure on zone D wnet,D = (-0.543 or +0.187)
kN/m2
https://eurocodeapplied.com/design/en1991/wind-pressure-duopitch-canopy 2/8
2/16/24, 2:23 PM Calculation of wind loads on duopitch canopies - Eurocode 1
Pressure zones for duopitch canopy roofs, reproduced from EN1991-1-4 Table 7.7 and Figure 7.17
Notes
1. The overall force coefficient corresponds to the resulting wind force and it can be used for the
design of the overall load bearing structure. The net pressure coefficients represent the
maximum local pressure for all wind directions and they should be used in the design of
roofing elements and fixings.
2. The calculated net wind pressure corresponds to the overall wind effect including the wind
pressure on both the top surface and the bottom surface for all wind directions.
3. The sign convention for the net pressure and the overall force is the same as its external
pressure part. Negative pressure values correspond to suction directed away from the surface
i.e. inducing uplift on the canopy roof.
4. Both positive and negative wind pressure should be examined, i.e. directed both upwards
(negative value) and downwards (positive value).
5. The location of the center of pressure for the overall wind force is located in the middle of each
of the two sloped faces of the canopy. Six cases should be examined with upwards force,
downwards force, or no force on each of the two faces according to EN1991-1-4 §7.3(6) (see
figure above)
6. Downwind of the position of maximum blockage the value of the blockage factor φ = 0 should
be used, according to EN1991-1-4 §7.3(4).
7. A structural factor cscd different than 1.0 may be applicable in accordance with EN1991-1-4
Section 6. A value of cscd = 1.0 is generally conservative for small structures not-susceptible to
wind turbulence effects such as buildings with height less than 15 m.
8. The calculated wind action effects are characteristic values (unfactored). Appropriate load
factors should be applied for the relevant design situation. For ULS verifications the partial load
factor γQ = 1.50 is applicable for variable actions.
9. Horizontal wind friction forces should be considered in accordance with EN1991-1-4 §7.5.
https://eurocodeapplied.com/design/en1991/wind-pressure-duopitch-canopy 3/8
2/16/24, 2:23 PM Calculation of wind loads on duopitch canopies - Eurocode 1
Details
Input Data
Terrain category: = I
Basic wind velocity: vb = 16 m/s
Horizontal dimension of rectangular plan parallel to the wind direction: d = 91.2 m
Horizontal dimension of rectangular plan perpendicular to the wind direction (crosswind
dimension): b = 220 m
Height of canopy from ground up to the maximum roof level: h = 13 m
Roof pitch angle: α = 6 °
Degree of blockage under the canopy roof: φ = 0
Orography factor at reference height ze: c0(ze) = 1
Structural factor: cscd = 1
Nationally Defined Parameters
Air density: ρ = 1.25 kg/m3
Additional rules defined in the National Annex for the calculation of peak velocity pressure
qp(ze): = None
Note that the reference area calculated above corresponds to each sloped face of the duopitch roof
(i.e. half of the total roof area).
Terrain roughness
The roughness length z0 and the minimum height zmin are specified in EN1991-1-4 Table 4.1 as a
function of the terrain category. For terrain category I the corresponding values are z0 = 0.010 m and
zmin = 1.0 m.
The terrain factor kr depending on the roughness length z0 = 0.010 m is calculated in accordance with
EN1991-1-4 equation (4.5):
The roughness factor cr(ze) at the reference height ze accounts for the variability of the mean wind
velocity at the site. It is calculated in accordance with EN1991-1-4 equation 4.4. For the examined case
ze ≥ zmin:
https://eurocodeapplied.com/design/en1991/wind-pressure-duopitch-canopy 4/8
2/16/24, 2:23 PM Calculation of wind loads on duopitch canopies - Eurocode 1
cr(ze) = kr ⋅ ln(max{ze, zmin} / z0) = 0.1698 ⋅ ln(max{13.000 m, 1.0 m} / 0.010 m) = 1.2172
Orography factor
Where orography (e.g. hills, cliffs etc.) is significant its effect in the wind velocities should be taken
into account using an orography factor c0(ze) different than 1.0, as specified in EN1994-1-1 §4.3.3. The
recommended procedure in EN1994-1-1 §4.3.3 for calculation of the orography factor c0(ze) is
described in EN1994-1-1 §A.3.
In the following calculations the orography factor is considered as c0(ze) = 1.000.
Wind turbulence
The turbulence intensity Iv(ze) at reference height ze is defined as the standard deviation of the
turbulence divided by the mean wind velocity. It is calculated in accordance with EN1991-1-4 equation
4.7. For the examined case ze ≥ zmin.
Iv(ze) = kI / [ c0(ze) ⋅ ln(max{ze, zmin} / z0) ] = 1.000 / [ 1.000 ⋅ ln(max{13.000 m, 1.0 m} / 0.010 m) ] =
0.1395
where ρ is the density of the air in accordance with EN1991-1-4 §4.5(1). In this calculation the
following value is considered: ρ = 1.25 kg/m3. Note that by definition 1 N = 1 kg⋅m/s2.
For structural surfaces consisting of more than one skin EN1991-1-4 §7.2.10 is applicable.
For the different pressure zones on the canopy roof the following net pressures are obtained:
- For zone A: wnet,A = -0.290 kN/m2 or +0.290 kN/m2
(zones A is the remaining central region of the two sloped faces located more than d'/10 = 9.170 m or
b/10 = 22.000 m from the edges and the central ridge)
https://eurocodeapplied.com/design/en1991/wind-pressure-duopitch-canopy 6/8
2/16/24, 2:23 PM Calculation of wind loads on duopitch canopies - Eurocode 1
Negative values for the overall pressure coefficient correspond to suction directed away from the
upper surface inducing uplift forces on the roof. Both positive and negative values should be
considered, as explained below.
Structural factor
The structural factor cscd takes into account the structure size effects from the non-simultaneous
occurrence of peak wind pressures on the surface and the dynamic effects of structural vibrations
due to turbulence. The structural factor cscd is determined in accordance with EN1991-1-4 Section 6. A
value of cscd = 1.0 is generally conservative for small structures not-susceptible to wind turbulence
effects such as buildings with height less than 15 m.
In the following calculations the structural factor is considered as cscd = 1.000.
The wind force Fw corresponding to the overall wind effect on each sloped face of the canopy roof is
calculated in accordance with EN1991-1-4 equation 5.3:
Fw = cscd ⋅ cf ⋅ Aref ⋅ qp(ze)
where Aref = 10087.259 m2 is the reference wind area for each sloped face of the canopy roof as
calculated above.
For the examined case:
- Maximum overall wind force (acting downwards):
Fw = 1.000 ⋅ (+0.320) ⋅ 10087.259 m2 ⋅ 0.468 kN/m2 = +1512.15 kN
Negative values correspond to suction directed away from the external surface inducing uplift forces
on the canopy roof. Both positive and negative values should be considered.
Additional notes
Horizontal wind friction forces should be considered in accordance with EN1991-1-4 §7.5.
For roofs with permanent walls see EN1991-1-4 §7.2 and the relevant calculation Wind load on
duopitch roofs.
The calculated wind action effects are characteristic values (unfactored). Appropriate load
factors should be applied for the relevant design situation. For ULS verifications the partial load
factor γQ = 1.50 is applicable for variable actions according to EN1990.
https://eurocodeapplied.com/design/en1991/wind-pressure-duopitch-canopy 7/8
2/16/24, 2:23 PM Calculation of wind loads on duopitch canopies - Eurocode 1
Eurocode EurocodeApplied.com
Applied.com Copyright © 2017-2024. All rights reserved.
https://eurocodeapplied.com/design/en1991/wind-pressure-duopitch-canopy 8/8