V-Series DSR III
V-Series DSR III
V-Series DSR III
75”
Flip 180°
3rd cut - 12.25”
2nd cut - 14”
1st cut - 15”
1” Binder
Diagnostic Manual
DSR III
DSR
Diagnostics Manual
DSRIIIIIIDiagnostics
TK
TK 61096-EN-18-OD
61096-EN-18-OD (Rev.
(Rev. 0,
0, 04-14)
DiagnosticsManual
04-14)
Manual
TK 61096-EN-18-OD
TK 61096-EN-18-OD
(Rev. 0, 04/14)
(Rev. 0, 04/14)
Direct Smart Reefer III
Microprocessor
Control System
Revision 380 XX, 544 XX
Software
TK 61096-EN-18-OD (Rev. 0, 04-14)
Diagnostic Manual
This manual is published for informational purposes only and the information so provided should not be considered as all-inclusive
or covering all contingencies. If further information is required Thermo King Corporation should be consulted.
Sale of product shown in this manual is subject to Thermo King's terms and conditions including, but not limited to, the THERMO
KING WARRANTY. Such terms and conditions are available upon request.
Thermo King's warranty will not apply to any equipment which has been "so repaired or altered outside the manufacturers plants as,
in the manufacturers judgment, to effect it's stability".
No warranties, express or implied, including warranties of fitness for a particular purpose or merchantability, or warranties arising
from course of dealing or usage of trade, are made regarding the information, recommendations and descriptions contained herein.
Manufacturer is not responsible and will not be held liable in contract or in tort (including negligence) for any special, indirect or
consequential damages, including injury or damage caused to vehicles, contents or persons, by reason of the installation of any
Thermo King product or its mechanical failure.
ABOUT THIS MANUAL
Because not everyone is familiar with microprocessor-based control systems, please take a few minutes
to read this page. It explains the content and structure of this manual. This will make it easier for you to
find the information you need.
Section 4 - Operation
This section shows you how to operate the Direct Smart Reefer Microprocessor Controller.
Section 5 - Diagnostics
This section shows you how to diagnosis problems. It includes both alarm code diagnostics and other
symptom diagnostics.
i
THIS PAGE INTENTIONALLY LEFT BLANK
ii
Table of Contents
About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .i
System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .i
Software Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .i
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .i
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .i
Service Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .i
DSR P Controller Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .i
Schematics and Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .i
List of Figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
General Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Refrigerant Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Microprocessor Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Welding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Electrical Hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
High Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Low Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Typical Safety Decals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Direct Smart Reefer Microprocessor Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
In-cab Control Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Electronic Control Module (ECM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Electronic Control System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Microprocessors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Logic Board and Power Board. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Printed Circuit Board I/O Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
System Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
System Relays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
System Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
System Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Unit Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
External Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Switches and Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Motors and Motor Protectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Clutches. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Power Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Systems and Equipment Covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Service Procedures
Microprocessor Procedures
A02A Recording Existing Microprocessor Settings
A04A Microprocessor Setup
A12A ESD (Electrostatic Discharge) Procedures
A26A Welding on Units Equipped with Microprocessors
A28A Setting Unit Running Time Hourmeters
A46A Updating the DSR microprocessor
Printed Circuit Board Procedures
B02A Printed Circuit Board Removal and Replacement
Miscellaneous Procedures
D01A Return Air Temperature Sensor Test
F06A 3 Wire Magnetic Door Switch
H02A Deutsch Connector Repair using Pigtail
H04A Checking Harness Continuity
DSR µP Controller Information
DSR µP Controller Software Features
and Interchange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Schematics and Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
2E22072, Rev. B, V-100, V-200, V-300 MAX 10/30 DSR III P Controller Schematic Diagram
Table of Contents
2E21994, Rev. B, V-100, V-200, V-300 MAX 10/30 DSR III P Controller Wiring Diagram
2E37652, Rev. A, V-100 20/50 DSR III P Controller Schematic Diagram
2E37653, Rev. A, V-100 20/50 DSR III P Controller Wiring Diagram
2E16632, Rev. B, V-200, V-300 MAX 20/50 DSR III P Controller Schematic Diagram
2E16631, Rev. B, V-200, V-300 MAX 20/50 DSR III P Controller Wiring Diagram
2E16811, Rev. A, V-200, V-300 MAX Spectrum DSR III P Controller Schematic Diagram
2E16812, Rev. A, V-200, V-300 MAX Spectrum DSR III P Controller Wiring Diagram
2E28293, Rev. C, V-500, V-600 MAX 10/20/30/50, 1 Temp & Spectrum DSR III P Controller Schematic Diagram
2E28292, Rev. C, V-500, V-600 MAX 10/20/30/50, 1 Temp & Spectrum DSR III P Controller Wiring Diagram
Table of Contents
List of Figures
Figure 2-1: DSR III Microprocessor Block Diagram: for Logic Board 1 and Power Board 1 Units. . . . . . . . . . . 2-1
Figure 2-2: DSR III Microprocessor Block Diagram: for Logic Board 2 and Power Board 1/2 Units . . . . . . . . . 2-2
Figure 2-3: In-cab Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Figure 2-4: A Platform 2 ECM configuration, with LB2, PB1 and PB2 mounted . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Figure 2-5: Internal Layout of a Platform 2Electronic Control Module, showing PB1 and PB2 . . . . . . . . . . . . . 2-5
Figure 3-1: Start Routine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Figure 3-2: Mono-temp unit in cool mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Figure 3-3: Multi-temp unit in cool mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Figure 3-4: Unit in null mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Figure 3-5: Unit in Alarm mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Figure 3-6: Mono-temp unit in heat mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Figure 3-7: Table of temperatures and operating modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Figure 3-8: Multi-temp unit in heat mode in both compartments or one in heat mode and the other in null . . . 3-5
Figure 3-9: Multi-temp unit in heat mode in one compartment and cooling mode in the other . . . . . . . . . . . . . 3-5
Figure 3-10: Mono-temp unit in defrost mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Figure 3-11: Multi-temp unit in defrost mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Figure 3-12: Mono-temp unit with reverse cycle in condenser defrost mode. . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Figure 3-13: Unit in evacuation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Figure 3-14: Direct Smart Reefer III Microprocessor Controller Menus and Screens . . . . . . . . . . . . . . . . . . . . 3-9
Figure 3-15: DSR III Main Menu Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Figure 3-16: DSR III Hourmeters Menu Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
Figure 3-17: DSR III Information Menu Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Figure 3-18: DSR III Installation (Guarded Access) Menu Screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
Figure 3-19: DSR III Evacuation Menu Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Figure 4-1: In-cab Control Box, with all icons illuminated in the Standard Display . . . . . . . . . . . . . . . . . . . . . . 4-1
Figure 4-2: The Standard Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Figure 4-3: Typical Standard Display reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Figure 4-4: The Standard Display, with a load compartment temperature of 3°C . . . . . . . . . . . . . . . . . . . . . . . 4-4
Figure 4-5: The Standard Display, with an alarm icon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Figure 4-6: The Standard Display, with a setpoint of 10.8 and a declining compartment temperature . . . . . . . 4-5
Figure 4-7: The Standard Display, with a Return Air Alarm and alarm icon . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Figure 4-8: The Standard Display, with main and remote compartment temperature readings . . . . . . . . . . . . . 4-6
Figure 4-9: The Standard Display, with a setpoint of -18°C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Figure 4-10: The Standard Display, with a setpoint of 5ºC for the remote compartment . . . . . . . . . . . . . . . . . . 4-8
Figure 4-11: The Standard Display, with standard multi-temperature compartment selection . . . . . . . . . . . . . . 4-9
Figure 4-12: The Standard Display, showing the temperature in both compartments . . . . . . . . . . . . . . . . . . . . 4-9
Figure 4-13: The Standard Display, with standard C1 compartment selection. . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Figure 4-14: The Standard Display, showing the temperature only in compartment 1 . . . . . . . . . . . . . . . . . . 4-10
Figure 4-15: The Standard Display, with standard C2 compartment selection . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Figure 4-16: The Standard Display, showing the temperature only in compartment 2 . . . . . . . . . . . . . . . . . . 4-11
Figure 4-17: The Standard Display, with standard 1 - 1 compartment selection . . . . . . . . . . . . . . . . . . . . . . . 4-12
Figure 4-18: The Standard Display, showing the temperature as a single temperature unit . . . . . . . . . . . . . . 4-12
Figure 4-19: The Standard Display, showing defrost off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Figure 4-20: The Standard Display, showing defrost on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Figure 4-21: The Standard Display, showing the defrost symbol and the defrost icon . . . . . . . . . . . . . . . . . . 4-14
Figure 4-22: The Standard Display, showing defrost off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Figure 4-23: The Standard Display, showing defrost activated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
Figure 4-24: The Standard Display, showing the dFC letters and the defrost icon . . . . . . . . . . . . . . . . . . . . . 4-15
Figure 4-25: The Standard Display, showing the software revision at the Information Menu . . . . . . . . . . . . . 4-16
Figure 4-26: The Standard Display, showing the bAt (Low Battery Voltage) alarm . . . . . . . . . . . . . . . . . . . . . 4-17
Figure 4-27: The Standard Display, showing the Evacuation Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19
1
List of Figures
2
Section 1
Section 1
Safety Precautions
General Practices ................................. 1 - 1
Refrigerant ............................................ 1 - 1
First Aid 1-1
Electrical ............................................... 1 - 2
Microprocessor Service 1-2
Welding 1-2
Batteries 1-2
1. Always wear goggles or safety glasses. At Thermo King we recognize the need to
Refrigerant and battery acid can permanently preserve the environment and limit the
damage the eyes. potential harm to the ozone layer that can
result from allowing refrigerant to escape
2. Keep hands, clothing and tools clear of fans into the atmosphere.
and belts when the unit is running.
We strictly adhere to a policy that promotes
3. Be sure gauge manifold hoses are in good the recovery and limits the loss of refrigerant
condition. Never let them come in contact into the atmosphere.
with belts, fans, pulleys or hot surfaces.
When working on transport refrigeration
4. Never apply heat to a sealed refrigeration systems a recovery process that prevents or
system or container. minimizes refrigerant loss to the atmosphere
is required by law. In addition, service
5. Refrigerants in the presence of an open personnel must be aware of European Union,
flame produce toxic gases. These gases are national, and local regulations governing the
severe respiratory irritants capable of use of refrigerants and certification of
causing death. technicians.
6. Be sure all mounting bolts are the correct When refrigerants are exposed to the
length for the application and are securely atmosphere in liquid form, they evaporate
tightened. rapidly, freezing anything they contact. If they
contact the skin severe frostbite can result. In
7. Use extreme caution when drilling holes in the event of frostbite, the objectives of first aid
the unit. Holes may weaken structural are to protect the frozen area from additional
components. Holes drilled in wiring can injury and to warm it rapidly.
cause fire or explosion. Holes drilled into the
refrigeration system will release refrigerant.
First Aid
8. Use caution when working around exposed 1. Warm the frozen area by immersing it in
coil fins. The fins can cause painful luke-warm (not hot) water or by covering the
lacerations. area with warm blankets.
9. Use caution when working with refrigerant 2. Obtain medical assistance as soon as
in a closed or confined area with a limited possible.
air supply such as a trailer, container or hold
of a ship. Refrigerant tends to displace air 3. If refrigerant contacts the eyes, flush them
and can cause oxygen depletion which may with water immediately and obtain medical
result in unconsciousness or death due to assistance as soon as possible.
suffocation.
(07/12) 1-1
Section 1 - Safety Precautions
Refrigeration Oil Batteries
When removing a battery from the unit,
Avoid contact with the eyes. Avoid prolonged ALWAYS disconnect the negative battery
contact with the skin or clothing. Wash hands terminal (-) first. Then remove the positive
thoroughly after handling refrigeration oil to terminal (+). DO NOT LET A
prevent skin irritation. DISCONNECTED TERMINAL WITHOUT
ISOLATION. WHEN RECONNECTING THE
BATTERY TERMINALS, CONNECT THE
First Aid POSITIVE TERMINAL (+) FIRST, AND
In case of eye contact, flush immediately with CONNECT THE NEGATIVE (-) TERMINAL
water for at least 15 minutes. Obtain medical LAST.
assistance as soon as possible.
Electrical Hazards
Electrical
High Voltage
Microprocessor Service Units with optional Electric Standby utilize 115
Precautions must be taken to prevent or 230 volt, single-phase power or 230 to 400
electrostatic discharge when servicing the volt three-phase AC power any time the unit is
microprocessor and related components. A operating in Electric mode. This voltage
potential difference less than that required to potential is also present any time the unit is
produce a small spark between a finger and a connected to standby power. Extreme care must
doorknob can cause severe damage to solid be used when working on the unit, as these
state components. Refer to Service Procedure voltages are capable of causing serious injury or
A12A, ESD (Electrostatic Discharge) death.
Procedure in this manual and the Electrostatic
Discharge Training Guide (TK 40282-1) for 1. When working on the high voltage circuits, do
additional information. not make any rapid movements. Unplanned
movements can cause contact with high voltage.
(07/12) 1-2
Section 1 - Safety Precautions
First Aid
Immediate action must be taken after a person
has received an electrical shock. Medical
attention should be summoned as soon as
possible.
Low Voltage
Control circuits can be 12 volt DC or 24 volt
DC. This voltage potential is not considered
dangerous, but the large amount of current
available can cause severe burns if shorted to
ground.
(07/12) 1-3
Section 1 - Safety Precautions
Typical Safety Decals
(07/12) 1-4
Section 1 - Safety Precautions
Direct Smart Reefer
Microprocessor Notes
(07/12) 1-5
Section 1 - Safety Precautions
(07/12) 1-6
Section 2
Section 2
System Description
Block Diagrams .................................... 2 - 1
Unit Power........................................... 2 - 10
External Devices................................. 2 - 10
Sensors 2 - 11
Switches and Transducers 2 - 11
Valves 2 - 11
Relays 2 - 12
Motors and Motor Protectors 2 - 13
Clutches 2 - 13
Contactors 2 - 13
Power Sources 2 - 13
Heaters 2 - 13
Figure 2-1 DSR III Microprocessor Controller Block Diagram: for Logic Board 1 and Power Board 1 Units
(04/14) 2-1
Section 2 - System Description
Direct Smart Reefer Microprocessor Controller Block Diagram:
for DSR III P Controllers with Logic Board 2 and Power Board 1/2
Standby Power
-optional- In-Cab Control Box
(secondary power source) Vehicle Battery Contains:
12V or 24V AC/DC Controlling (master) microprocessor
(primary power source) LCD Display, with operator and maintainer backlit screens
Function backlit keys
12V or 24V DC Alarm buzzer
Figure 2-2 DSR III Microprocessor Controller Block Diagram: for Logic Board 2
and Power Board 1/2 Units
(04/14) 2-2
Section 2 - System Description
General Description
Thermo King units that use the Direct Smart In-Cab Control Box
Reefer Microprocessor Control System
The In-cab Control Box contains the Electronic
(referred to, throughout the remainder of this
Control System’s controlling (master)
manual, as a DSR P Controller) are
microprocessor, microprocessor software, LCD
temperature-control units mounted on small-
display screen, touch-sensitive function keys,
and medium-sized trucks. Units provide
and discrete electronic components. It is usually
cooling and defrosting by means of the vehicle
mounted on or above the truck instrument
motor or DC motor (in models operating
panel. The In-cab Control Box is connected to
electrically, the second compressor is driven by
the ECM by a cable that contains
an Electric Standby Motor).
communications, voltage, and chassis/ground
Defrost is accomplished by hot gas. Heat is
wires.
provided by the hot gas system and by the
forced-convection air-flow created by the fans.
(04/14) 2-3
Section 2 - System Description
The unit can be operated by the ECM without an The ECM microprocessor(s) also receives input
In-cab Control Box. However, operating conditions signals from load compartment sensors and
for the unit must be selected with the In-cab Control switches, the vehicle battery, engine,
Box before it is disconnected from the ECM. compressor clutches, an optional Electrical
Standby, and solenoid valves. These inputs are
sent to the In-cab Control Box microprocessor,
Electronic Control Module (ECM)
where it determines if faulty or out-of-range
The ECM, located inside the unit’s condenser, conditions exist.
contains the system’s secondary
microprocessor(s), I/O connectors, output The ECM can be configured with Logic Board
relays, fuses, LEDs, cooling fan, and discrete 1 (LB1) and Power Board 1 (PB1) that are
electronic components mounted on one or two attached to the ECM enclosure. This
printed circuit boards (platforms). The configuration is referred to as Platform 1.
microprocessor(s) receives output signals from
the load compartment return air sensor and The ECM can also be configured with Logic
electronic thermostat. These signals are sent to Board 2 (LB2) and Power Boards 1 and 2 (PB1
the microprocessor in the In-cab Control Box. & PB2) that are attached to the ECM enclosure.
Based on setpoint temperature and other This configuration is referred to as Platform 1
parameters, the In-cab Control Box and 2.
microprocessor determines when to adjust the
temperature-control state in the main and/or See Figure 2-4 for a Platform 2 configuration,
remote load compartment to Cool, Heat, or Null with LB2, PB1 and PB2. See Figure 2-5 for
mode, or to initiate a Defrost cycle. internal layout of ECM (PB1 and PB2 are
identical).
Figure 2-4 ECM configuration, with LB2, PB1 and PB2 mounted
Callout Description
1 Power Board 1 (PB1)
2 Power Board 2 (PB2)
3 Plastic Support
4 Logic Board 2 (LB2)
(04/14) 2-4
Section 2 - System Description
Figure 2-5 Internal Layout of Electronic Control Module, showing PB1 and PB2
Callout Description
1 Connector C-1, LB1
2 Connector C-2, PB1
3 Connector C-3, PB2
4 Connector PSC1, PB1
5 Connector PSC2, PB2
(04/14) 2-5
Section 2 - System Description
• The microprocessor in the In-cab Control C-1 Input and Output Connector for
Box receives information signals from the Direct-Drive Truck Units (LB1 or LB2)
ECM microprocessors regarding unit Pin Wire # Description
operations and power. The In-cab
A2 LPCO Low Pressure Cutout Switch Input
microprocessor send signals to the ECM
microprocessors regarding setpoint and A3 DSW1 Door Switch 1
parameter settings, manual defrost, and the A4 CH5 (PNK, B, CHT) Signal Ground
functioning of the evaporator, condenser, (Temp sensors 1&2, Pressure
Sensor)
and other system components
A5 CF-02 Output, Condenser Fan Speed
• Changes made at the In-cab Control Box are Control
processed by the In-cab microprocessor. A6 EX2 Input, Low Pressure adjustable
Signals are routed to the microprocessor in pressure switch
LB1 or LB2, which analyses and processes A7 BAT Battery Voltage Sensing
the commands. Signals are sent to the A8 03 DC Battery Power Source
applicable relays on PB1 / PB2, which B1 DSW2 Door Switch 2
energise solenoid valves or activate system B2 OL Input, Overload relay
electrical devices, such as fan motors, B3 EX1 Input
clutches, heaters, etc.
B4 BLK Input, Thermostat Sensor 1
B5 EF-02 Output, Evaporator Fan Speed
Logic Board and Power Board Control
Logic Board (LB1 or LB2) and Power Board (s) B6 RXD RX Comms Signal to the In-cab
Control Box (RS-485)
PB1/PB2 are located in the ECM. Each printed
circuit board is populated with a B7 TXD TX Comms Signal to the In-cab
Control Box (RS-485)
microprocessor and discrete electronic
components, and connected by wires to B8 X1 Standby DC Power Source
analogue and digital I/O devices. A PCB, in C1 12 DK1 Input, Defrost Temperature
addition to physically connecting these Switch
components, is an interface between the C2 12B DK3 Input, DC thermal Motor
microprocessor and the unit valves, evaporator Protection
and condenser fan motor contactors, heaters, C3 G Input, Thermostat Sensor 2
and the In-cab Control Box. C4 HP Input, High Pressure to THPCO
C5 5V DC Power input to pressure
Printed Circuit Board I/O Connectors Sensor THPCO
C6 12A DK2 Input, Defrost temp switch
The pins for connectors C-1 on LB1 or LB2, C-2
on PB1, C-3 on PB2 are different for each C7 9V 9-volts Output Voltage to the
In-cab Control Box
direct-drive truck unit. These differences are noted
in the schematic diagrams for each unit. C8 12C DK4 Input, Power supply thermal
protection
C-1 Input and Output Connector for C-2 Input and Output Connector for
Direct-Drive Truck Units (LB1 or LB2) Direct-Drive Truck Units (PB1)
Pin Wire # Description Pin Wire # Description
A1 CH7 (CHH, CHJ, GND) Ground, 1 EF1-01 Relay RY7 Input
Chassis 2 EF1 Relay RY7 Output
(04/14) 2-6
Section 2 - System Description
C-2 Input and Output Connector for C-3 Input and Output Connector for
Direct-Drive Truck Units (PB1) Direct-Drive Truck Units (PB2)
Pin Wire # Description Pin Wire # Description
3 CF1-02 Relay RY6 Input 11 27-02 Relay RY19 Output
3 CF1-01 Relay RY6 Input 12 EXR2-01 Relay RY19 Input
4 CF1 Relay RY6 Output
PSC2 Input Connector for Direct-Drive Truck
4 CHG Relay RY6 Output
Units (PB2)
5 26A Relay RY5 Output
6 EF2 Relay RY8 Output Pin Wire # Description
3 CF2-01 Relay RY10 Input F8 (PB2) Protects the load connected to relays
RY11, RY12, RY13, RY15 and RY16
4 CF2-02 Relay RY10 Output
F9 (PB2) Protects the load connected to relay
4 CF2 Relay RY10 Output RY17
5 33 Relay RY11 Input F10 (PB2) Protects the load connected to relay
6 EF4 Relay RY18 Output RY18
7 B3 Relay RY12 Output F11 (PB 2) Protects the load connected to relay
8 Relay RY15 Output RY19
(04/14) 2-7
Section 2 - System Description
Check the value of each fuse on the electrical Relay
diagrams for each unit. No. Unit Type Description
RY4 1, 3, 4, 5, 6, Host Defrost Hot Gas Solenoid
Description of Fuses Located in the Vehicle
7, 11 Valve (PS1)
Fuse # Description RY5 1, 3, 4, 5, 6, Heat Pilot Solenoid (PS5)
F20 (except Located on the Electric Box. 7, 11
V-100) Protects the transformer from RY6 1, 3, 4, 5, 6, Condenser Fan Motor 1
possible overloads 7, 11 (CFM1)
F21 Located in the engine compartment. RY7 1, 3, 4, 5, 6, Evaporator Fan Motor 1
Protects the vehicle battery from 7, 11 (EFM1)
possible overloads RY8 1, 3, 4, 5, 6, Evaporator Fan Motor 2
F22 (except Located on the Electric Box. 7 (EFM2)
V-100) Protects the transformer from RY9 1, 5, 11 Heater 1, Heater 2
possible overloads
RY9 3, 4, 6, 7 Serial/Parallel CFM1, CFM2
F14 Located in the engine compartment. RY10 3, 4, 6, 7 Condenser Fan Motor 2
Protects wires 014 and BAT from (CFM2)
possible overloads
RY11 2, 6, 7 Remote Liquid Solenoid Valve
F15 Located on the electric box. Protects (PS2)
the Electronic Control Module (ECM)
RY12 2, 6, 7 Host Liquid Solenoid Valve
from potential overloads
(PS3)
F16 Located on the electric box. Protects
RY13 2, 6, 7 Remote Defrost Hot Gas
the Electronic Control Module (ECM)
Solenoid Valve (PS4)
from potential overloads
RY17 2, 3, 4, 6, 7 Remote Evaporator Fan 3
F17 Located on the electric box. Protects (EF3)
the tracking power line from potential
overloads RY18 6, 7 Remote Evaporator Fan 4
(EF4)
F18 (only Located on the electric box. Protects
RY19 3, 4, 7 Heater 1, Heater 2
V-100/ the ventilator power circuit of the
MAX 20/50) condenser at low speed RY19 6 Heater 3, Heater 4
F30 Located in the electric harness. BATR 1, 5, 6, 7, Battery Relay
Protects the condenser fan 1 11
F31 Located in the electric harness. STDR 5, 7, 11 Stand-By Relay
Protects the condenser fan 2 OLR 4, 5, 7, 11 Overload Relay
C1R 5, 7, 11 Switching Relay
Check the value of each fuse on the electrical SR 11 Starter Relay
diagrams for each unit
Unit Type:
(04/14) 2-8
Section 2 - System Description
RY1 to RY9 = located on PCB 1 System Inputs
RY10 to RY19 = located on PCB 2
BATR = located in unit control box Input Description Notes
STDR = located in unit control box Sensor 1 Return Air Sensor Platform 1,
OLR = located in unit control box (analog) (main evaporator) wires PNK,
C1R = located in unit control box BLK
ER1 = located in unit control box
Sensor 2 Return Air Sensor Platform 1,
RM = located in condenser unit
(analog) (remote evaporator) wires G, B
SR = located in unit control box
ACC On-the-road Power to Platform 1,
(digital) Unit Controls wire 03
BAT Battery Voltage Level Platform 1,
(analog) wire BAT
STD BY Optional Electric Platform 1,
(digital) Standby wire X1
DK1 Defrost Termination Platform 1,
(digital) (main evaporator) wire 12
DK2 Defrost Termination Platform 2,
(digital) (remote evaporator) wire 12A
LPCO Low Pressure Cutout Platform 1,
(digital) Switch wire LPCO
HP High Pressure Platform 1,
Transducer wires HP, 5V,
CHT (analog)
OL Electric Motor Protector Platform 1,
(digital) Overload (Electric wire OL
Standby)
DSW1 Door Switch 1 Platform 1,
(digital) wire DSW1
DSW2 Door Switch 2 Platform 2,
(digital) wire DSW2
EX1 Multifunction Input Platform 1
(digital)
EX2 Multifunction Input Platform 2
(digital)
DK3 Motor Thermal Platform 1,
Protection wire 12B
DK4 Power Supply Thermal Platform 2,
Protection wire 12C
(04/14) 2-9
Section 2 - System Description
System Outputs NOTE: Outputs are applicable for vehicles
with a single temperature/main load
Output Description Notes
compartment, or with bi-temperature/main
CLU1 Vehicle Compressor Platform 1,
and remote load compartments.
Clutch wire CLU1-01
CLU2 Electric Standby Clutch Platform 1,
wire CLU1-02
CMC Compressor Motor Platform 1, Unit Power
Contactor wire CMC
PS1 Host Evaporator Hot Gas Platform 1,
Unit power is supplied from the vehicle battery.
Solenoid (defrost) wire 26
Device power is supplied through the fuse F21
PS2 Liquid Line Solenoid (on Platform 2,
located near the vehicle battery. Power to the
remote evaporator) wire 33
In-cab Control Box is supplied from the ECM.
PS3 Liquid Line Solenoid (on Platform 2,
main evaporator) wire B3 An Electric Standby option supplies rectified DC
PS4 Hot Gas Solenoid (defrost, Platform 2, power from the standby power pack, whenever a
remote evaporator) wire 28 source of standby power is connected to the unit.
PS5 Condenser Solenoid Platform 1, Device power is supplied through the electric
(heat) wire 26A relay in the power pack. Power supply protection
PS6 Liquid Line Solenoid Valve Platform 2 is achieved by means of a fuse located in the
(AC System) primary transformer (except V-100 20/50). For
PS7 Bypass Between the High Platform 1, more information see the electrical diagrams for
and Low Pressure Lines wire 29 each unit.
PS11 Pressure Regulation Line Platform 2,
Bypass wire 34
(in remote evaporator
suction line, Spectrum External Devices
units)
CF1 Condenser Fan 1 Platform 1,
wire CF1 External devices (such as the evaporator return
(V-100/200/3 air temperature sensors, coil temperature
00), CF1-02 sensor, HP and LPCO switches) provide
(V-500/600) temperature-control data to the ECM
CF2 Condenser Fan 2 Platform 1, microprocessor.
wire CF2;
V-500/600 The microprocessor, in turn, energises outputs
wire CF2-02 to maintain the desired compartment
EF1, Evaporator Fans 1 and 2 Platform 1, temperature; displays information on the In-cab
EF2 (main compartment) wires EF1, Control Box display; and protects the unit from
EF2 excessive pressures and temperatures.
EF3, Evaporator Fans 3 and 4 Platform 2,
EF4 (remote compartment) wires EF3, The operating characteristics of many of these
EF4 devices is dependent on the type of refrigerant
DH1 Main Evaporator Drain Platform 1, used* and other unit specific requirements. For
Heaters wire 27-01 the exact operating temperatures and pressures
DH2 Remote Evaporator or Platform 2, of these devices, consult the Maintenance
Condenser Drain Heaters wire 27-03 Manual for the specific unit.
(V-500),
27-03 (V-600)
(04/14) 2 - 10
Section 2 - System Description
* Single temperature 10 and 20 model units use R-134a Defrost Termination Switch (DK 1, DK2) -
refrigerant; MAX, and MAX SPECTRUM 10, 20, 30, normally closed, DK1 or DK2 opens to stop the
and 50 model units use R-404A refrigerant.
defrost operation in the load compartment
(DK1 for the main load compartment, DK2 for
Sensors a remote load compartment, also used for
condenser defrost in reverse cycle units).
Return Air Temperature Sensor - senses the
temperature of the air returning to the Door Switches (DSW1, DSW2) - used to stop
evaporator coil. For bi-temperature units, the unit operation except in defrost mode, when the
temperature for both compartments is displayed load compartment doors are opened.
on the In-cab Control Box.
Overload Switch (OL) - used to protect the
motor from an electrical overload. When this
Switches and Transducers normally open switch closes, the unit shuts down.
Low Pressure Cut-out (LPCO) Switch -
Thermal protection switch (HTT1, HTT2) -
opens when the refrigerant suction line pressure
opens when engine temperature exceeds a
falls below a determined pressure and stops unit
determined value. This information is used by
operation.
the microprocessor to energise the tEP alarm.
Low pressure adjustable pressure switch
Power supply thermal protection switch
LPS (some SPECTRUM units) - opens when
(THMR1/2) - Alarm tP4 appears when the
the pressure in the refrigerant suction tube falls
power supply temperature exceeds the preset
below a specific pressure and activates the
value.
solenoid valve which controls the frigorific
capacity of the compressor.
Valves
High Pressure Transducer - used to control
the high-pressure circuit of the unit. Hot Gas Solenoid Valve - during heat and
defrost cycles, this valve energises to route hot
Liquid Injection Switch LIS (MAX units) - gas to the evaporator coil.
closes when the temperature of the refrigerant
gas leaving the compressor exceeds a Liquid Injection Valve LIV (MAX units) -
determined temperature and activates the liquid energises to inject liquid refrigerant into the
injection valve (LIV) if the road clutch (CLU1) suction line near the compressor, in order to
is also activated. The LIV allows liquid cool it down and then discharge gas leaving the
refrigerant to flow from the liquid line to the compressor.
metering orifice that is attached to the suction
Liquid Solenoid Valve (Bi-temperature
line fitting on the compressor. As the refrigerant
units) - during a cool cycle, this valve energises
passes through the metering orifice, it expands
to inject liquid refrigerant into the evaporator
and evaporates, and cools the suction gas
entering the compressor. This cooling effect is coil.
transferred to the discharge gas leaving the Heating Pilot Solenoid Valve (30/50 units
compressor. When the discharge gas is cooled without reverse cycle) - during the heating
to a determined value, the LIS opens and cycle, it prevents hot gas from flowing to the
refrigerant no longer flows through the liquid condenser coil.
injection system.
(04/14) 2 - 11
Section 2 - System Description
Expansion Valve - restricts (controls) the flow Relays
of high-pressure liquid coolant into the
Control relays are energised by the
evaporator and thereby lowers coolant pressure.
microprocessor(s), depending on I/O
This also lowers coolant temperature and
requirements. In turn, the relay energises its
boiling point allowing for efficient cooling of
corresponding specified device, such as a
the load compartment.
motor, clutch, pilot solenoid, valve, fan, or
KVL suction pressure regulator valve heater. Each relay is fuse-protected.
- protects compressor operation and start-up by
Battery Relay BATR - when this relay is
impeding suction pressure from rising too high.
energised, the unit is powered from the vehicle
The KVL is mounted in the suction line
battery.
immediately upstream of the compressor. The
KVL closes when suction pressure increases. Standby Relay STDR - when this relay is
Normal pressure setting for this valve is 29 psi energised, the unit is powered from the electric
(200 kPa). power supply.
KVP Evaporation Pressure Regulation Valve CR1 switching relay - when this relay is
- installed in the suction line behind the energised, power is disconnected from the
evaporator, it regulates evaporation pressure in battery relay. This prevents the two power
installations with one or more evaporators and sources for the unit (battery and electric power
one compressor. In the TC units running with supply) from being connected at the same time.
different evaporation pressures, the KVP is
installed behind the evaporator with highest Overload Relay OLR - protects the electric
pressure. motor that drives the Electric Standby
compressor. The overload relay opens the circuit
Check valve - guarantees proper air circulation to the microprocessor (which de-energises the
in one direction only. Prevents migration and motor contactor and the electric motor) if the
condensation from hot evaporator to cold motor overloads for any reason (e.g., low line
evaporator in TC units. voltage or an improper power supply) during
Electric Standby operation.
Check valve (V-200/V300 20/50 units) -
Isolates the compressor driven by the truck SR start relay (single-phase units only) -
motor from the Electric Standby compressor when this relay is energised, the starter
and prevents compressor oil and refrigerant capacitor turns on the AC motor.
from flowing between the two compressors.
Reverse Cycle Valve (4 way) - Reverses the Motors and Motor Protectors
refrigeration cycle.
Evaporator Fan Motor (EFM1, EFM2,
Compressor cooling capacity control EFM3, EFM4) - draws air across the
solenoid valve (reverse cycle and some evaporator coil during cool or heat operation.
SPECTRUM units) - Allows refrigerant gas to The evaporator fan motor is turned off during
flow from the discharge line to the suction line defrost cycles.
in certain conditions to control the cooling
Condenser Fan Motor (CFM1, CFM2) -
capacity of the compressor.
turns on, as determined by the condenser fan
pressure switch, to flow air across the
condenser coil during cool and heat operation.
(04/14) 2 - 12
Section 2 - System Description
Clutches Systems and Equipment
Vehicle Compressor Clutch (CCL1) - Covered
energises to activate the engine driven
compressor when cooling, heating, or defrost The information contained in this manual
operation is required. applies to, but is not limited to, the following
Direct-Drive Truck systems and their associated
Standby Compressor Clutch (CCL2) - evaporators and condensers.
energises to activate the motor-driven
compressor when cooling, heating, or defrost Evaporator/
operation is required and the optional Electric System Description Condenser
Standby is active. 900874 V-100 20 1PH 701519 / 701521
12VDC
Contactors 900875 V-100 20 1PH 701520 / 701522
24VDC
Compressor Motor Contactor (CMC) - for 900876 V-100 MAX 20 1PH 701529 / 701531
units with an Electric Standby option, closes to 12VDC
provide electrical power to the Vac motor. 900877 V-100 MAX 20 1PH 701530 / 701532
24VDC
Power Sources 900878 V-100 MAX 50 1PH 701543 / 701545
12VDC
Electric Standby - substitutes the vehicle’s 900879 V-100 MAX 50 1PH 701544 / 701546
engine-driven compressor with a second, 24VDC
electrically powered compressor and an 901865 V-500 MAX 10 702669 / 702681
external power source. This ensures operational 12VDC
continuity when the vehicle is parked and the 901865 V-500 MAX 10 702670 / 702682
unit is on. 24VDC
901866 V-500 MAX 20 702671 / 702681
Battery – provides 12 Vdc or 24 Vdc power to
12VDC
the unit and the ECM. LB1 or LB2 in the ECM
901866 V-500 MAX 20 702672 / 702682
provides between 7.5 and 9 Vdc power to the
24VDC
In-cab Control Box.
901867 V-500 MAX 30 702673 / 702681
12VDC
Heaters 901867 V-500 MAX 30 702674 / 702682
24VDC
Drain Heater - Consists of two resistors in
901868 V-500 MAX 50 702675 / 702681
parallel that are used to prevent ice build-up in
12VDC
the evaporator or condenser drain pipe. They
901868 V-500 MAX 50 702676 / 702682
are activated when the corresponding klixon
24VDC
(DK1 or DK2) is closed.
901869 V-500 10 12VDC 702677 / 702683
901869 V-500 10 24VDC 702678 / 702684
901870 V-500 20 12VDC 702679 / 702683
901870 V-500 20 24VDC 702680 / 702684
902022 V-500 MAX 10 702836 / 702847
Spectrum 12VDC
(2xES300)
(04/14) 2 - 13
Section 2 - System Description
Evaporator/ Evaporator/
System Description Condenser System Description Condenser
902022 V-500 MAX 10 702837 / 702848 902234 V-200 MAX 30 703199 / 703201
Spectrum 24VDC 12VDC Spectrum
(2xES300) (2xES100)
902022 V-500 MAX 10 702836 / 702849 902234 V-200 MAX 30 703200 / 703202
Spectrum 12VDC 24VDC Spectrum
(ES300+2xES150) (2xES100)
902022 V-500 MAX 10 702837 / 702850 902236 V-200 MAX 50 703209 / 703211
Spectrum 24VDC 12VDC Spectrum
(ES300+2xES150) (2xES100)
902023 V-500 MAX 20 702838 / 702847 902236 V-200 MAX 50 703210 / 703212
Spectrum 12VDC 24VDC Spectrum
(2xES300) (2xES100)
902023 V-500 MAX 20 702839 / 702848 902362 V-300 MAX 30 700338 / 703342
Spectrum 24VDC Spectrum 12VDC
(2xES300) (2xES150)
902023 V-500 MAX 20 702838 / 702849 902362 V-300 MAX 30 700339 / 703343
Spectrum 12VDC Spectrum 24VDC
(ES300+2xES150) (2xES150)
902023 V-500 MAX 20 702839 / 702850 902362 V-300 MAX 30 700338 / 703350
Spectrum 24VDC Spectrum 12VDC
(ES300+2xES150) (ES150+ES100)
902024 V-500 MAX 30 702840 / 702847 902362 V-300 MAX 30 700339 / 703351
Spectrum 12VDC Spectrum 24VDC
(2xES300) (ES150+ES100)
902024 V-500 MAX 30 702841 / 702848 902362 V-300 MAX 30 700338 / 703353
Spectrum 24VDC Spectrum 12VDC
(2xES300) (ES200+ES100)
902024 V-500 MAX 30 702840 / 702849 902362 V-300 MAX 30 700339 / 703354
Spectrum 12VDC Spectrum 24VDC
(ES300+2xES150) (ES150+ES100)
902024 V-500 MAX 30 702841 / 702850 902363 V-300 MAX 50 700361 / 703372
Spectrum 24VDC Spectrum 12VDC
(ES300+2xES150) (2xES150)
902025 V-500 MAX 50 702842 / 702847 902363 V-300 MAX 50 700362 / 703373
Spectrum 12VDC Spectrum 24VDC
(2xES300) (2xES150)
902025 V-500 MAX 50 702843 / 702848 902363 V-300 MAX 50 700361 / 703375
Spectrum 24VDC Spectrum 12VDC
(2xES300) (ES150+ES100)
902025 V-500 MAX 50 702842 / 702849 902363 V-300 MAX 50 700362 / 703376
Spectrum 12VDC Spectrum 24VDC
(ES300+2xES150) (ES150+ES100)
902025 V-500 MAX 50 702843 / 702850 902363 V-300 MAX 50 700361 / 703378
Spectrum 24VDC Spectrum 12VDC
(ES300+2xES150) (ES200+ES100)
(04/14) 2 - 14
Section 2 - System Description
Evaporator/
System Description Condenser
902363 V-300 MAX 50 700362 / 703379
Spectrum 24VDC
(ES150+ES100)
902533 V-600 MAX 10 703677 / 703679
12VDC
902533 V-600 MAX 10 703678 / 703680
24VDC
902534 V-600 MAX 20 703684 / 703679
12VDC
902534 V-600 MAX 20 703685 / 703680
24VDC
902535 V-600 MAX 30 703686 / 703679
12VDC
902535 V-600 MAX 30 703687 / 703680
24VDC
902536 V-600 MAX 50 703688 / 703679
12VDC
902536 V-600 MAX 50 703689 / 703680
24VDC
920238 V-200 20 720617 / 720629
920239 V-200 MAX 20 720618 / 720630
920240 V-300 20 720619 / 720631
920241 V-300 MAX 20 720620 / 720632
920242 V-200 10 720625 / 720629
920243 V-200 MAX 10 720626 / 720630
920244 V-300 10 720627 / 720631
920245 V-300 MAX 10 720628 / 720632
920248 V-100 10 720637 / 720639
920249 V-100 MAX 10 720621 / 720638
(04/14) 2 - 15
Section 2 - System Description
(04/14) 2 - 16
Section 3
Section 3
Software Description
Software Operation .............................. 3 - 1
Software Revisions and Changes 3-1
Unit Operation 3-1
(04/14) 3-1
Section 3 - Software Description
In the case of starting up the electric Cool mode operation: Mono-temp units
compressors (unit electric operating mode), in
order to prevent excessive on/off cycling, which
could result in winders overheating, the
controller has two parameters that limit the
maximum on/off frequency that electric motors
can work under.
• OnC: The minimum amount of time that an
electric compressor should remain
connected Figure 3-2 Mono-temp unit in cool mode
• OfC: The minimum amount of time that an While operating in cool mode, the outlets that
electric compressor should remain cool the compressor (either road or electric) are
disconnected, before restarting. activated in order to move the cooling fluid
around the circuit. Apart from the compressor,
Options the evaporator fans work at maximum speed
and the condensor fans are
• The Heat option provides heating by hot gas
activated/deactivated at high or low speed,
or reverse cycle.
depending on the discharge line pressure
• The Electric Standby option provides a indicated by the transducer. As a result, when
second compressor driven by an electric the pressure reading exceeds the value
motor. determined by the CFP parameter, the high
speed condensor fans are activated if the unit
• The SPECTRUM options provide does not have a condensor fan speed control
temperature control for two-compartment system, or low speed fans when the fans in the
systems. unit have a speed control system. When the
pressure reading drops below CFP - CFd, the
Operation condensor fans switch off. In the case of units
The vehicle engine must be running and the unit equipped with condensor fan speed control,
must be turned on. On units with Electric when the pressure reading exceeds the level
Standby, connect the external power cord and determined by parameter FS1, the fans move to
the unit switches to Electric mode operation. high speed mode. However, when the pressure
Unit operation can be tailored, as required, reading drops below the level determined by the
using programmable settings that are shown parameters FS1 - FS2, the condensor fans
later is this section. return to low speed mode.
(04/14) 3-2
Section 3 - Software Description
Cool mode operation: Multi-temp units Null mode operation: All units
Figure 3-3 Multi-temp unit in cool mode Figure 3-4 Unit in null mode
When in cooling mode in both compartments The unit operates in Null mode when the
(or one in cooling mode and the other in setpoint temperature is reached and cooling (or
null), this unit works similarly to the heating) is not required. All outputs are
mono-temp version, only the liquid solenoid de-energised except for UNIT ON signal. If the
valves in the compartments that operate in cool temperature rises a pre-determined number of
mode (PS2 and PS3) and the evaporator fans in degrees, the unit restarts in Cool mode. If the
those compartments, switch on. If a temperature falls a pre-determined number of
compartment reaches the setpoint, both the degrees, and a heat option is present, the unit
evaporator fans and the compartment solenoid restarts in Heat mode.
valves will switch off (if the EFC parameter is
on, the evaporator fans of the compartment in In addition, the evaporator fans (parameter
null mode will remain on). EFc) operate during Null mode.
Firmware version 544.xx. Compartment Depending on the unit operating mode before
Selection: going into null mode, the RV (reverse cycle
valve) and PS5 valves can remain in the same
• C1: Just read the Return Air Temperature mode as prior to starting.
Sensor Compartment 1 and inputs DK1 and
DSW1. Return Air Temperature Sensor Alarm mode
Compartment 2, and DK2 and DSW2 inputs
are ignored.
(04/14) 3-3
Section 3 - Software Description
Heat mode operation Mono-temp units When the unit is operating in heat mode, the
outlets that affect the compressor (road or
electric) switch on to move the cooling fluid
If the Heat mode option is present, the unit around the circuit. Apart from the compressor,
enters Heat mode when the temperature falls a the PS1 defrost valve switches on and the
pre-determined number of degrees below the evaporator fans operate at maximum speed in
setpoint temperature. the case of units equipped with the hot gas
heating system. In the case of units with the
cycle inversion heating system, the reverse
cycle valve switches on and the speed of the
evaporator fan depends on the pressure reading
of the discharge line. When the pressure
exceeds the level determined by the EFP
parameter, the evaporator fans switch on at low
speed. If the pressure continues to rise and
Figure 3-6 Mono-temp unit in heat mode exceeds the level determined by parameter FS3,
the evaporator fans switch to high speed.
The unit works in heat mode until the setpoint
temperature is reached. Then, it goes into null As regards the condensor fans, in the case of
mode. units equipped with the hot gas heating system,
• If the temperature drops a preestablished operations are related to the pressure reading at
number of degrees, the unit restarts in heat the discharge line. When the pressure reading is
mode. below the level determined by the CSP
• If the temperature reaches a preestablished parameter, the PS5 valve is activated and blocks
level, the unit restarts in cool mode. the way of the hot gases to the condensor. If the
pressure reading exceeds the level determined
by CSP, the condensor fans switch on at
maximum speed and the PS5 valve is
deactivated to reduce the pressure in the system
to CSP - CSd. At this time, the PS5 valve
switches on again and the condensor fans
switch off. In units equipped with a reverse
cycle heating system, the condensor fans
operate constantly at low speed.
(04/14) 3-4
Section 3 - Software Description
Heat mode operation Multi-Temp Units
When the unit operates in heat mode in both
compartments (or one in heat mode and the
other in null), this works similarly to the
mono-temp version, except that the solenoid
defrost valves in the compartments that work in
heat mode (PS1 and PS4) and the compartment
evaporator fans, switch on. If a compartment
Figure 3-9 Multi-temp unit in heat mode in one
reaches the setpoint, both the evaporator fans
compartment and cooling mode in the other
and the solenoid valves in that compartment
will switch off. Firmware version 544.xx. Compartment
Selection:
(04/14) 3-5
Section 3 - Software Description
When defrost is required, the microprocessor Evaporator Defrost Mode Operation:
output energises the hot gas solenoid to supply Multi-Temp units
hot refrigerant to the evaporator coil, except In multi-temp units, defrost starts only if a
reverse cycle units where the cooling cycle is compartment is in COOL mode, or NULL if
reversed to generate heat in the evaporator. The one has previously been in COOL (besides
Defrost Initiation Timer (DIT) has counted-down having a corresponding input DKi closed).
its required time-setting, and the Defrost
Termination Switch (DK1 or DK2) is closed. When the unit operates in evaporator defrost
mode, machine operation is similar to the
The unit remains in Defrost mode until the mono-temp version, but with the following
Defrost Termination Switch setpoint is reached differences:
(that is, when the evaporator coil temperature
rises to 14°C (58°F), or until the Defrost • The solenoid defrost valves of the
Termination Timer (DTT) count is completed). evaporators (PS1 or PS4) that have been
If the evaporator coil temperature does not rise running below 0ºC (defrost switch off) will
above 14°C (58°F) within the defrost duration switch on.
time limit, the microprocessor terminates the
defrost operation. • If a compartment has not operated below
0ºC (defrost switch on), it will switch to null
During the defrost cycle, condensor fan mode (no solenoid valve will be activated).
operation resembles that of the heating unit
described previously. • The evaporator fans of both compartments
will remain off.
The startup of the evaporator fans is delayed for
several seconds after Defrost mode ends, to • Defrosting will conclude when the defrost
prevent water from the melting ice from being switches in the compartments that have
sprayed on the load. participated in the cycle open.
For details of programmable defrost features,
see the Programmable Features in this section.
(04/14) 3-6
Section 3 - Software Description
Firmware version 544.xx. Compartment Evacuation Mode (MSK544.xx only)
Selection: Possibility for the CONTROLS to
activate/deactivate this mode in which:
• 1-2: Only enter into defrost mode
compartments having their Defrost • Fairly all solenoid valves are activated: PS1,
Termination Switch (DKi) closed. When PS2, PS3, PS4, PS7, PS8 and PS9.
DKi opens the compartment switch to
NULL. Defrost will terminate when all • The remaining relevant loads are NOT
compartments DKi who entered defrost activated: PS5 (open refrigerant flux), CFi,
cycle is open. EFi, RV, CMC, CLUi, EXR.
• C1: Only enter defrost mode Compartment 1 • DK1, DK2, DSW1 and DSW2 inputs shall
if DK1 input is closed, and it will work like a not be considered (e.g. drain heaters shall
single-temp unit. The state of DK2 input is not be activated, nor any alarm, associated to
ignored. doors opening, generated or buzzer
activated).
• C2: Only enter defrost mode Compartment 2
if DK2 input is closed, and it will work like a
single-temp unit. The state of DK1 input is
ignored.
(04/14) 3-7
Section 3 - Software Description
Menu Screens
• Main Menu
• Hourmeters Menu
• Information Menu
(04/14) 3-8
Section 3 - Software Description
Direct Smart Reefer Microprocessor Controller
Menus and Screens
(viewed at the In-cab Control Box)
Standard
Display
Main Menu
To access: press the Select key. Press the Select key to access each menu screen.
dFC
Alarms dEF Condenser manual
SP SP2 CSE (544.xx only)
(see alarm Manual Setpoint 1 Setpoint 2 Compartment
defrost (reverse
codes below) Defrost selection
cycle units)
--- C ---
Comms
Failure
HC tH CC EC
Hour Vehicle Electric
Total Hours
Counter for Compressor Compressor
Maintenance Hours Hours
Information Menu
To access: press and hold the Up Arrow + Enter keys for 3 seconds.
Firmware versions 121 15 and 273 02/03: The information menu scrolls automatically.
Firmware versions 380 xx: Use the SELECT key to view:
121/273/
(all icons) 380/544 XX 134, 404 bAt xC / tyy
Display
380 XX HP
Refrigerant Battery Compartments/
Test Software High Pressure
Type Voltage Unit Type
Version
Evacuation Menu
To access press and hold Up and Down Arrow keys for 7 seconds
EUA StA
(544.xx only)
Evacuation Mode
Figure 3-14 Direct Smart Reefer Microprocessor Controller Menus and Screens
(04/14) 3-9
Section 3 - Software Description
Menu Flowcharts From the
Standard Display,
Menu Type do the following:
The following pages include flowcharts of the Press and hold
four DSR P Controller menus, as viewed at Hourmeters Menu the Select key
the In-cab Control Box. Examine the flowcharts for 3 seconds,
Screens include:
and become familiar with the sequence of the HC (Hour Counter for
then use the
screens, before reading detailed descriptions of Select key to
Maintenance)
access a screen
the screens in the Programmable Features tH (Total Hours)
section. CC (Vehicle Compressor
Hours)
The table below describes the four menus; the EC (Electric Compressor
screens contained within each menu; and the Hours)
keys that you must press to access each menu.
DSR P Controller Menu Screens
From the Information Menu Press and hold
Standard Display, the Enter and Up
Menu Type do the following: Screens include: arrow keys for
(all icons) (Display Test) 3 seconds to
380 XX, 544 XX (Software enter the
Main Menu Press the
Version) Information Menu,
Select key
134, 404 (Refrigerant Type) press the Select
Screens include:
bAt (Battery Voltage) key.
Alarm screens: HP (High Pressure)
P1E (Temp Probe 1 alarm) xC / tyy (Number of
P2E (Temp Probe 2 alarm) compartments / Unit type)
OL (Overload alarm)
bAt (Low Battery Voltage
alarm)
HP (HPCO alarm)
LP (LPCO alarm)
PSE (HPCO Pressure Sensor
alarm)
tEP (Electric Standby Motor
Thermal protection alarm)
tP4 (Power Supply Thermal
Protection Alarm)
dr1 (Door Switch 1 alarm)
dr2 (Door Switch 2 alarm)
tCO (ECM Temperature
Control alarm)
SOF (Software Failure alarm)
- C - (Communications Failure
alarm)
dEF (Evaporator Manual
Defrost)
dFC (Condenser Manual
Defrost, Reverse Cycle Units)
SP (Setpoint 1)
SP 2 (Setpoint 2)
CSE (Compartment Selection)
(544.xx only)
(04/14) 3 - 10
Section 3 - Software Description
From the From the
Standard Display, Standard Display,
Menu Type do the following: Menu Type do the following:
Press and hold Press and hold
Installation (Guarded the Enter and Evacuation Menu the Up and Down
Access) Menu Down Arrow keys (MSK544.xx only) Arrow keys for 7
for 3 seconds. seconds.
Screens include: To scroll through Screens include:
SPL (Setpoint Temperature the menu press EUA StA (Evacuation State
Minimum Value) the UP or mode))
SPH (Setpoint Temperature DOWN keys.
Maximum Value)
SL2 (Zone 2 Setpoint
Temperature Minimum Value)
(544.xx only)
SH2 (Zone 2 Setpoint
Temperature Maximum Value)
(544.xx only)
diF (Setpoints Differential)
SSC (Soft Start Cycles)
dit (Evaporator Defrost
Initiation Timer)
dtt (Evaporator Defrost
Termination Timer)
di2 (Condenser Defrost
Initiation Timer)
dt2 (Condenser Defrost
Termination Timer)
EFc (Evaporator Fan
Constant Blow)
dAL (Out-of-Range Alarms)
HC (Hour Counter Initial
Value)
dSP (Door Switches
Present/Polarity)
bE (Buzzer Enable)
tu (Thermostat Units)
Pu (Pressure Units)
trE (Temperature display
resolution)
(04/14) 3 - 11
Section 3 - Software Description
Standard
Display SP2
Setpoint 2
SELECT
Key SELECT
Key
Alarm Codes
(if present) CSE
Can include: (MSK544.XX only)
P1E (Temperature Probe 1)
P2E (Temperature Probe 2)
Compartment Selection
OL (Electric Motor Protection Switch
Overload)
bAt (Low Battery Voltage)
HP (HPCO Switch fault) SELECT
LP (LPCO Switch fault) Key
PSE (HPCO pressure sensor fault)
tEP (B-100 only) (Thermal
protection alarm)
tP4 (Thermal Protection Alarm)
dr1 (Door Switch 1 fault)
dr2 (Door Switch 2 fault)
Standard Display
tCO (Temperature Control Alarm)
SOF (Software failure)
SELECT
Key
dEF
Evaporator Manual Defrost
SELECT
Key
dFC
Condenser Manual Defrost
SP
SELECT Setpoint 1
Key
(04/14) 3 - 12
Section 3 - Software Description
SELECT
Key
Standard
Display
SELECT
Key
HC
Hours remaining until next
maintenance operation
SELECT
Key
tH
Unit Total Hours
SELECT
Key
CC
Vehicle or DC motor (B-100)
compressor hours
SELECT
Key
EC
Electric Compressor/
Motor Hours
(04/14) 3 - 13
Section 3 - Software Description
In fo rm atio n M en u
S creen s
S tandard
D isplay
380XX,
121 X 544
X , 273 X XX X X
X , 380
S oftw are V ersion
134, 404
R efrigerant T ype
bAt
B attery V oltage
HP
H igh P ressure
xC / tyy
C om partm ents / U nit T ype
S tandard
D isplay
(04/14) 3 - 14
Section 3 - Software Description
Down Arrow
Key Down Arrow
Down Arrow
Key
Key
SPH
(Zone 1 Setpoint Temperature
Maximum Value)
EFc
Evaporator Fan tu
SL2 (544.xx only) Constant Blow Thermostat Units
Zone 2 Setpoint
Temperature Minimum
Value
Down Arrow Down Arrow
Key Key
Down Arrow
Key
Down Arrow
Key
Down Arrow Down Arrow
Key and Key
diF
Setpoints Differential
Down Arrow
Key CSE (544.xx only) trE
Compartment Selection Temperature visualisation
SSC resolution
Soft Start Cycles
dit
Evaporator Defrost
HC
Initiation Timer
Hour Counter Initial Value
Standard
Down Arrow Display
Key
Down Arrow
dtt Key NOTE: The Up Arrow key can be used
Evaporator Defrost to scroll back through the screens.
Termination Timer
Down Arrow
Key
dSP
Door Switches
di2 Present/Polarity
(Condenser Defrost
Initiation Timer)
(04/14) 3 - 15
Section 3 - Software Description
Standard Display
EUA StA
(Evacuation Mode State)
Standard Display
(04/14) 3 - 16
Section 3 - Software Description
Programming Aids Alarm Codes Displayed in the Main Menu
Alarm Alarm
When programming many features at the same Code Description
time, such as during the initial setup of the DSR
P1E Return Air Temperature Sensor in the
P Controller, it is wise to obtain and complete main load compartment is faulty.
a copy of the Setup Sheet shown in Service The temperature reading on the In-cab
Procedure A02A. Be certain that all customer Control Box displays [----] when the
specified settings are included when completing Return Air Temperature sensor reading is
this setup sheet. The sheet is used to confirm out of the readable range. This might be
each entry, to be certain that the correct settings caused by a short circuit or an open circuit
at the Return Air Temperature sensor.
are programmed.
P2E For vehicles with a remote load
compartment, this alarm indicates that the
Return Air Temperature Sensor in the
remote compartment is faulty.
Main Menu and Its Screens For details, see the description for alarm
code P1E.
Entering Main Menu OL For units with an Electric Standby option,
1. Press the In-cab Control Box On/Off switch on. this alarm indicates that there is an
overload in the electric motor protector
The unit undergoes a 20-second system check. switch. The unit shuts down until the
During this time, the Standard Display shows alarm condition is corrected. (The unit is
the word CHECK. shut down whether the unit is in Cool,
Heat, or Defrost mode).
2. After the system check, the return air bAt Low battery voltage. Battery voltage is
temperature setting is displayed at the below 10.5 Vdc on 12 V systems, or
Standard Display. For bi-temperature units, below 21 Vdc on 24 volt systems. The unit
the return air temperature for both load shuts down. The battery is possibly
damaged, or a short circuits exists in
compartments is displayed.
battery wires 2 or BAT, or fuse 21.
3. Press and release the Select key. If an alarm HP High Pressure Cut-Out Switch fault. The
unit shuts down when there is excessively
exists, its code appears in the display. See high pressure in the refrigerant circuit.
the following table for the alarm codes that The unit shuts down, but [HP] and the
can appear. alarm icon are displayed on the In-cab
Control Box. When the alarm condition is
4. If there is more than one alarm, other alarm corrected, the unit returns to a Null state.
screens can be viewed, in sequence, by LP Low Pressure Cut-Out Switch fault. The
pressing the Select key and toggling through unit shuts down when there is excessively
the alarms. low pressure in the refrigerant circuit. The
unit shuts down, but [LP] and the alarm
icon are displayed on the In-cab Control
The following table, Alarm Codes Displayed in Box. When the alarm condition is
the Main Menu, describes the alarms that can corrected, the unit returns to a Null state.
exist with the DSR P Controller. See Section 5
- Diagnostics, for a detailed explanation of an
alarm, its possible causes, and the actions to
take to diagnose the source(s) of the alarm.
(04/14) 3 - 17
Section 3 - Software Description
Alarm Alarm Alarm Alarm
Code Description Code Description
PSE HPCO pressure sensor is faulty or SOF Software failure. The software in the
disconnected. This indicates that the microprocessor is corrupted. The unit
reading from the HP sensor is out of the shuts down. The microprocessor must be
readable range (<0.5 V or >4.5V). reprogrammed. See Service Procedure
The unit remains in its existing mode A04A in Section 6.
(Cool, Heat, Null, Defrost) for a time -C- Total communications failure between the
determined by the factory-set Pressure microprocessor in the In-cab Control Box
Sensor Error Time Delay Time [PSt] and the microprocessor(s) in the ECM.
parameter. Unit is not able to turn on and operate.
If the alarm continues longer than the
[PSt] time, the unit shuts down. The [- C -] alarm code is not part of the
Main Menu alarms. When a Main Menu
tEP Indicates that the thermal protection
alarm occurs, the In-cab Control Box can
circuit has opened in one of the two
communicate with the ECM, and I/O and
electric standby motors (D.C. or A.C.) due
parameter statuses can be checked.
to engine overheating or circuit failure.
When the [- C -] alarm code occurs, there
tp4 Indicates the power supply thermal are no communications between the
protection circuit has opened due to In-cab Control Box and the ECM, and I/O
overheating of the power supply or circuit and parameter statuses cannot be
failure. checked at the In-cab Control Box.
dr1 Door 1 in Zone 1 is open or door switch
DSW1 is faulty. The audible alarm buzzer Accessing Additional Main Menu Screens
is activated.
If the unit is in Cool or Heat modes when
1. After all (if any) alarms are viewed, press the
the alarm occurs, the unit shuts down. Select key, until a flashing [dEF] is viewed.
When the door is closed, the unit starts in This indicates the Evaporator Manual Defrost
Null mode. function. To change the [dEF] setting, press the
If the unit is in Defrost mode when the Enter key, then use the Up Arrow or Down
alarm occurs, it remains in Defrost mode. Arrow keys to change the defrost setting to ON
dr2 Door 2 in Zone 2 is open or door switch or OFF.
DSW2 is faulty. The audible alarm buzzer
is activated.
2. Press the Select key. In reverse cycle units
If the unit is in Cool or Heat modes when
the alarm occurs, the unit shuts down. the screen shows [dFC], which indicates that
When the door is closed, the unit starts in the condenser manual defrost function is
Null mode. activated. To change the [dFC] setting, press
If the unit is in Defrost mode when the the Enter key, then use the Up Arrow or
alarm occurs, it remains in Defrost mode. Down Arrow keys to change the defrost
tCO The Temperature Cut-Out value for the setting to ON or OFF.
Electrical Control Module has been
exceeded 3. Press the Select key. An [SP] appears, to
(>85°C [> 185°F]).
The internal temperature of the ECM
indicate the setpoint temperature for the
might exceed the temperature value return air temperature in the single or
because the internal ECM fan has failed, primary load compartment of the vehicle.
or the NTC sensor used to measure the To change the [SP] setting, do the following:
module temperature is faulty.
If the temperature is exceeded for more • Press the Up Arrow key to increase the
than 30 seconds, the unit shuts down.
return air temperature by 1-degree
increments.
(04/14) 3 - 18
Section 3 - Software Description
• Press the Down Arrow key to decrease the Press the key UP or DOWN to change
return air temperature by 1-degree increments. option between the four different options
available:
• Press and release the ENTER key to enter
the setpoint, or press and release the • 1-2 This is the standard multi-temperature
SELECT key to enter the setpoint and return setting where both compartments (zones) are
to the Standard Display. active.
NOTE: If the Select or Enter key is not • C1: Compartment 1 is active while
pressed within 20 seconds to select a new Compartment 2 is disabled.
setpoint temperature, the unit continues to
operate at the original setpoint temperature. • C2: Compartment 2 is active while
Compartment 1 is disabled.
4. For vehicles with two compartments and
bi-temperature functions, the screen displays • 1-1: Compartments 1 and 2 are combined to
[SP2]. This indicates the setpoint for the operate as a single temperature unit; only the
return air temperature in the second (remote) temperature for Compartment 1 is displayed.
compartment.
To change the [SP2] setting, do the 6. Press and release the ENTER key to select
following: an option or press and release the SELECT
key to select an option and return to the
• Press the Up Arrow key to increase the standard screen.
return air temperature by 1-degree
increments. Leaving the Main Menu
Leaving the Main Menu can be accomplished in
• Press the Down Arrow key to decrease the several ways.
return air temperature by 1-degree
increments. • Press the Select key until you have toggled
through all of the Main Menu screens.
NOTE: If the Select or Enter key is not
pressed within 20 seconds to select a new • Turn the unit off and back on. The In-cab
setpoint temperature, the unit continues to Control Box exits the Main Menu, at any
operate at the original setpoint temperature. point in the scrolling sequence, and returns
to the Standard Display.
5. Press and release the ENTER key to set the
setpoint value or press and release the • Allow the display to time out. The In-cab
SELECT key to set the setpoint and return to Control Box automatically exits the Main
Standard Display (380.xx) or move to the Menu and return to the Standard Display, if
CSE (Compartment Selection) screen no key is pressed for 20 seconds.
(544.xx).
(04/14) 3 - 19
Section 3 - Software Description
Hourmeters Menu and Its Screens [tH] (Total Hours)
• From the Standard Display, press and hold Factory setting - n/a
the Select key for 3 seconds, then release it. This hourmeter indicates the total number of
The first Hourmeters Menu screen, [HC], hours that the unit has been in operation.
appears.
[CC] (Vehicle compressor hours)
• Press the Select key to access other
Hourmeters Menu screens. Programming Choices - n/a
[HC] (Hours Counter for Maintenance) Unit of Measurement: Firmware 380.03 and
previous versions: Tens of hours (e.g.150
Programming Choices - 1000 through 5000 = 1500 hours)
Unit of Measurement: Firmware 380.03 and Firmware 380.06 and later versions: Hours
previous versions: Tens of hours (e.g.150
= 1500 hours) Parameter Set By - n/a
(04/14) 3 - 20
Section 3 - Software Description
[EC] (Electric Standby compressor hours Information Menu and Its Screens
Programming Choices - n/a The following paragraphs describe the
Information Menu screens that can we viewed.
Unit of Measurement: Firmware 380.03 and See the Direct Smart Reefer Microprocessor
previous versions: Tens of hours (e.g.150
Controller Menus and Screens flowchart for
= 1500 hours)
reference.
Firmware 380.06 and later versions: Hours
To access the Information Menu, do the
Parameter Set By - n/a following:
Factory setting - n/a • From the Standard Display, press and hold
the Up Arrow key and Enter key for three
This hourmeter indicates the total number of seconds, then release them. The first
hours that the Electric Standby compressor Information Menu screen, [all icons],
has been operating, if the unit is equipped appears.
with an Electric Standby option. This
parameter also indicates the total hours that [all icons] Display Test
clutch CLU2 has been engaged while the
electric motor is running. Programming Choices - none
• Press the Select key until you have toggled Factory setting - n/a
through all of the Hourmeters screens. This screen displays all of the In-cab Control
Box icons, to indicate that they are functioning
• Turn the unit off and back on. The In-cab and visible.
Control Box exits the Hourmeters Menu, at
any point in the scrolling sequence, and Software Version
returns to the Standard Display.
Programming Choices - current or future
• Allow the display to time out. The In-cab revisions
Control Box automatically exits the Unit of Measurement - alphanumeric
Hourmeters Menu and return to the Standard number
Display, if no key is pressed for 20 seconds.
Parameter Set By - n/a
(04/14) 3 - 21
Section 3 - Software Description
[134, 404] Refrigerant Type [xC / tyy] Number of Compartments / Unit
Type
Programming Choices - 134 or 404
Programming Choices - n/a
Unit of Measurement - n/a
Unit of Measurement - numerals
Parameter Set By - n/a
Parameter Set By - n/a
Factory setting - 134 or 404
Factory setting - depends on the unit
V-100, V-200, V-300, and V-500 units are Displays the number of load compartments for
charged with R-134a refrigerant. R-404A the vehicle (xC, where x = 1 or 2
refrigerant is available for use on MAX, and compartments), and the unit type (type = 10, 20,
MAX SPECTRUM. 30, or 50).
[bAt] Battery Voltage
Leaving the Information Menu
Programming Choices - n/a
Scroll through the screens using the Select key.
Unit of Measurement - volts DC After the last information screen is shown, the
Control Box returns to the Standard Display.
Parameter Set By - n/a
• For vehicles with 24 Vdc batteries, if the The Installation (Guarded Access) Menu
voltage drops below 21 Vdc, the unit shuts contains screens that are changed by trained and
down. A 24 Vdc unit functions with a authorised DSR P Controller maintenance
voltage range over 21 Vdc. personnel. The parameters shown on these
screens impact many of the primary operating
[HP] High Pressure settings for the unit. Only personnel who are
familiar with the unit and DSR P Controller
Programming Choices - n/a
functions are allowed to change the Installation
Unit of Measurement - PSIG or BAR, in (Guarded Access) Menu parameters.
decimals
To change or update the parameter settings in
Parameter Set By - n/a the Installation (Guarded Access) Menu, see
Service Procedure A04A.
Factory setting - P
(04/14) 3 - 22
Section 3 - Software Description
To access the Installation (Guarded Access) NOTE: If SPL and SPH are set to the same
Menu, do the following: value in a unit, the unit will operate at the set
temperature and will not deviate.
• From the Standard Display, press and hold
the Down Arrow and Enter key for three [SL2] Zone 2 Setpoint Temperature
seconds, then release it. The first Installation Minimum Value (544.xx only)
(Guarded Access) Menu screen, [diF],
Programming Choices: -40ºC to SPH in
appears in versions prior to 380 XX and
1-degree increments
[SPL] in versions 380 XX and later.
Unit of Measurement: ºC or ºF
• Use the Up Arrow or Down Arrow key to
toggle through the other Installation Parameter set by: Maintenance personnel
(Guarded Access) Menu screens.
Factory Setting: -32ºC (R-404A) or -20ºC
NOTE: Some versions of the Direct Smart (R-134a)
Reefer display the Setpoint Temperature (SP)
as the first Installation (Guarded Access) This parameter allows maintenance personnel
Menu screen. to set the minimum value of the setpoint 2.
Factory Setting: -32ºC (R-404A) or -20ºC This parameter allows maintenance personnel
to set the maximum value of the setpoint 2.
(R-134a)
NOTE: If SL2 and SH2 are set to the same
This parameter allows maintenance personnel
value in a unit, the unit will operate at the set
to set the minimum value of the setpoint 1.
temperature in compartment 2 and will not
[SPH] Setpoint Temperature Maximum Value deviate.
Unit of Measurement: ºC or ºF
(04/14) 3 - 23
Section 3 - Software Description
[diF] Setpoint Temperature Differentials [dit] Evaporator Defrost Initiation Timer
(04/14) 3 - 24
Section 3 - Software Description
[di2] Condenser Defrost Initiation Timer [EFc] Evaporator Fans Constant Blow
This parameter allows maintenance personnel [CSE] Compartment Selection (544.xx only)
to set the Defrost Termination Timer on the Programming Choices: 1-2, C1, C2, 1-1
condenser, which begins counting from the
initiation of a Defrost mode. When the timer Unit of Measurement: n/a
times-out, the unit switches from Defrost mode
Parameter Set By - Maintenance Personnel
to Null mode. The timer resets at the end of a
Defrost mode, or after the Defrost Termination Factory setting: 1-2
Timer has timed-out.
This parameter allows maintenance personnel to
If the timer is set at 0 (zero), this is a test set the compartment configuration in Spectrum
position. Defrost mode stops in 15 seconds. units.
(04/14) 3 - 25
Section 3 - Software Description
[HC] Hourmeter Initial Value [dSP] Door Switches Present/Polarity
(04/14) 3 - 26
Section 3 - Software Description
This parameter allows maintenance personnel [trE] Temperature visualisation resolution
to set the following conditions:
Programming choices: 0 (whole),
• 0 = disable the buzzer so that there is no 1 (0.5 resolution), 2 (0.1 resolution)
audible sound when certain alarm conditions Measurement unit: N/a
exist
Parameter set by: Maintenance staff
• 1 = enable the buzzer for normal functioning
Manufacturing adjustment: 0
• 2 = enable the buzzer to perform normal This parameter allows maintenance staff to
functioning, plus to be activated whenever make adjustments if the temperature on the
an In-cab Control Box key is pressed in-cab control box is displayed in whole
numbers or with decimals with a resolution of
• 3 = enable the buzzer to become activated
0.1 or 0.5.
only when an In-cab Control Box key is
pressed.
Programming Choices - 0C or 0F
(04/14) 3 - 27
Section 3 - Software Description
Evacuation Menu and Its Screens While in EVACUATION mode the IN CAB
(544.xx only) display shows alternatively the message “EUA
StA”, which stands for “EUAcuation
The following paragraphs describe the StAte/mode”, and the standard main
Evacuation Menu screens that can be viewed. visualisation (compartment temperatures).
See the Direct Smart Reefer Microprocessor
Controller Menus and Screens flowchart for
reference.
(04/14) 3 - 28
Section 4
Section 4
Operation
In-cab Control Box Features ............... 4 - 1
Keypad 4-1
Display 4-1
Keypad Keys and Buzzer 4-2
Buzzers.................................................. 4 - 6
Figure 4-1 In-cab Control Box, with all icons illuminated in the Standard Display
Keypad Display
The five touch-sensitive keys are used to turn The display normally shows the Standard
the unit “on” and “off,” change the setpoint Display of return air temperature. The display
temperature, observe unit operating conditions shown here has all possible segments and icons
and alarm codes, and control or change the lighted.
unit’s operating parameters.
(04/14) 4-1
Section 4 - Operation
Keypad Keys and Buzzer
The keys are illuminated any time the unit is turned on. This makes nighttime operation much easier.
On/Off Key Turns the unit on and off. Always lit (except when the unit is disconnected). Provides a
visual indication that the unit is powered-up.
Select Key Scrolls through the menu screens.
Up Arrow Chooses menu screen actions or increases the setpoint temperature or other settings.
Key
Down Arrow Chooses menu screen actions or decreases the setpoint temperature or other settings.
Key
Enter Key Executes menu screen actions or loads the setpoint temperature or other new settings.
The In-cab Control Box, at unit startup and In addition, the icons located at the sides and
during normal operation, shows the Standard bottom of the display indicate the operating
Display and the return air temperature(s), as mode of the unit, and indicate if any alarm
determined by the Return Air Temperature codes are present. The display shown here has
sensor(s) in the load compartment(s). all possible display icons turned “on”.
(04/14) 4-2
Section 4 - Operation
Display Icons
0 Degrees Icon Indicates whether the on-screen temperature reading is in degrees Celsius (0C) or
C
0
F degrees Fahrenheit (0F).
Maintenance Appears when a user-defined maintenance event should occur.
Icon
Defrost Icon Appears when the evaporator coil is defrosting (the unit is in Evaporator Defrost mode)
Condernser Appears when the condenser coil is defrosting and at the same time as the defrost
Defrost Icon icon (the unit is in Condenser Defrost mode)
Alarm Icon Appears when an alarm condition has been detected by the microprocessor.
Setpoint Icon Appears when the setpoint temperature is being shown in the display.
SP
Combined Indicates that the bi-temperature unit is working as a single temperature unit.
SP compartment
Icon
(04/14) 4-3
Section 4 - Operation
The Standard Display
The Standard Display appears when the unit is turned on and no other functions have been selected. The
return air temperature appears in the display. In Figure 4-4, the display shows a load compartment
temperature of 3 degrees C, and that the unit is cooling the load compartment.
Figure 4-4 The Standard Display, with a load compartment temperature of 3°C
NOTE: The unit undergoes a 20-second system check when the On/Off switch is turned On. During this
time, the Standard Display shows the word CHEck.
NOTE: This information applies only to the OL (Electric Standby overload) alarm and bAt (low
battery voltage) alarm.
(04/14) 4-4
Section 4 - Operation
Auto Start After an Alarm
When an alarm stops unit operation, the Alarm icon appears on the Standard Display. After the
condition that caused the alarm is corrected, the unit starts automatically.
Figure 4-6 The Standard Display, with a setpoint of 10.8 and a declining compartment temperature
For single temperature units, when a Return Air Sensor alarm [P1E] occurs in the load compartment,
the return air temperature reading on the Standard Display is replaced by the - - - icon. The Alarm icon
also appears. See Figure 4-7.
Figure 4-7 The Standard Display, with a Return Air Alarm and alarm icon
For bi-temperature units, when a Return Air Sensor alarm [P2E] occurs in the remote compartment, the
return air temperature reading for the remote compartment is replaced by the - - - icon. The temperature
reading for the main compartment continues to be displayed. The Alarm icon also appears.
In Figure 4-8, the temperature reading for the main compartment is -10°C. The temperature reading for
the remote compartment has been replaced by - - -. The Alarm icon appears.
(04/14) 4-5
Section 4 - Operation
Figure 4-8 The Standard Display, with main and remote compartment temperature readings
Buzzers
The buzzers are energised when the vehicle battery and the electrical supply are connected
simultaneously (the unit continues running in Standby mode). The buzzers are also energised when the
doors are opened, if this option has been selected.
(04/14) 4-6
Section 4 - Operation
Changing the Setpoint
2. Press the Select key twice (three times for reverse cycle units) to choose the setpoint display. The
Setpoint icon SP and the current setpoint temperature appear. See Figure 4-9.
3. Press the Up Arrow key or Down Arrow key to select a higher or lower setpoint. Each time an arrow
key is pressed, the temperature changes by 1 degree.
NOTE: If the Select or Enter key is not pressed within 20 seconds to select a new setpoint
temperature, the unit continues to operate at the original Setpoint temperature.
4. Press and release the ENTER key to enter the setpoint, or press and release the SELECT key to enter
the setpoint and return to the Standard Display.
(04/14) 4-7
Section 4 - Operation
For Bi-Temperature Units (with Main and Remote Compartments)
Figure 4-10 The Standard Display, with a setpoint of 5ºC for the remote compartment
2. Press the Select key twice to choose the setpoint display. The setpoint icon SP and the current
setpoint temperature appear. See Figure 4-9.
3. Press the Up Arrow key or Down Arrow key to select a higher or lower setpoint. Each time an arrow
key is pressed, the temperature changes by 1 degree.
NOTE: If the Select or Enter key is not pressed within 20 seconds to select a new setpoint
temperature, the unit continues to operate at the original Setpoint temperature.
4. Press and release the ENTER key to enter the setpoint, or press and release the SELECT key to enter
the setpoint and go to the remote compartment temperature setting screen.
1. The current setpoint temperature for the remote compartment and the letters SP2 appear on the display. See
Figure 4-10.
2. Press the Up Arrow key or Down Arrow key to select a higher or lower setpoint. Each time an arrow
key is pressed, the temperature changes by 1 degree.
NOTE: If the Select or Enter key is not pressed within 20 seconds to select a new setpoint
temperature, the unit continues to operate at the original Setpoint temperature.
3. Press and release the ENTER key to enter the setpoint, or press and release the SELECT key to enter
the setpoint and return to Standard Display (380.xx) or move to the CSE (Compartment Selection)
screen (544.xx).
(04/14) 4-8
Section 4 - Operation
For the Compartment Selection (544.xx only)
1. Press the key UP or DOWN to change options between the four different options available:
• 1-2: This is the standard multi-temperature setting where both compartments (zones) are active.
Figure 4-11 The Standard Display, with standard multi-temperature compartment selection
Figure 4-12 The Standard Display, showing the temperature in both compartments
(04/14) 4-9
Section 4 - Operation
• C1: Compartment 1 is active while Compartment 2 is disabled.
– Only the temperature for compartment 1 appears on the screen, while no reading is shown for
compartment 2.
Figure 4-14 The Standard Display, showing the temperature only in compartment 1
(04/14) 4 - 10
Section 4 - Operation
• C2: Compartment 2 is active while Compartment 1 is disabled.
– Only the temperature for compartment 2 appears on the screen, while no reading is shown for
compartment 1.
Figure 4-16 The Standard Display, showing the temperature only in compartment 2
(04/14) 4 - 11
Section 4 - Operation
• 1-1: Compartments 1 and 2 are combined to operate as a single temperature unit; only the
temperature for Compartment 1 is displayed.
– The screen is shown as that of a single temperature unit but with the triangle symbol activated to
indicate that it is actually a bi-temperature unit operating as a single temperature unit.
Figure 4-18 The Standard Display, showing the temperature as a single temperature unit
• Press and release the ENTER key to select an option or press and release the SELECT key to select
an option and return to the standard screen.
(04/14) 4 - 12
Section 4 - Operation
Initiating a Manual Defrost Cycle in the Evaporator
CAUTION: Before initiating a manual defrost, make sure that the unit is not already in manual
defrost. Check to see if the defrost icon appears on the Standard Display.
NOTE: If the unit is not running, or if the coil temperature is not below 2°C, the request for
a manual defrost is ignored.
1. The unit must be running and the evaporator coil temperature must be below 2°C. Press and release the
Select key once. [dEF] appears (flashing) on the screen, with the letters OFF. See Figure 4-19.
2. Press the Enter key and either the Up Arrow or Down Arrow key. The letters On appears on the
screen. This means that the manual defrost is activated. See Figure 4-20.
(04/14) 4 - 13
Section 4 - Operation
3. Press the Select key two times, to return to the Standard Display. (Press the Select key three times for
bi-temperature or reverse cycle units), where the compartment temperature (380.xx) or the letters
dEF (544.xx) and the DEFROST icon will appear when the defrost cycle starts. See Figure 4-21.
Figure 4-21 The Standard Display, showing the dEF letters (544.xx only) and the defrost icon
4. A defrost cycle terminates automatically, in accordance with the [dtt] time set at the Parameters
screen. See Section 3 for a description of the [dtt] parameter.
NOTE: The letters dEF will remain on screen for a while after returning to cool mode.
CAUTION: Before initiating a manual defrost, make sure that the unit is not already in manual
defrost. Check to see if the defrost icon appears on the Standard Display.
(04/14) 4 - 14
Section 4 - Operation
NOTE: If the unit is not running, or if the coil temperature is not below 2°C, the request for a
manual defrost is ignored.
1. The unit must be running and the condenser coil temperature must be kept below 2ºC. Press and release the
Select key twice. [dFC] appears (flashing) on the screen, with the letters OFF. Refer to Figure 4-22.
2. Press the Enter key and either the Up Arrow or Down Arrow key. The letters On appear on the
screen, which means that manual defrost is activated. Refer to Figure 4-23.
3. Press the Select key two times, to return to the Standard Display, where the compartment
temperature (380.xx) or the letters dFC (544.xx) and the DEFROST icons will appear when the
defrost cycle starts. Refer to Figure 4-24.
Figure 4-24 The Standard Display, showing the dFC letters and the defrost icons.
4. A defrost cycle terminates automatically, in accordance with the [dt2] time set at the Parameters
screen. See Section 3 for a description of the [dt2] parameter.
(04/14) 4 - 15
Section 4 - Operation
Checking the Software Revision
Figure 4-25 The Standard Display, showing the software revision at the Information Menu
1. Make sure that the unit is on and the Standard Display is showing.
2. Press and hold both the Up Arrow and Enter keys for three seconds. The first Information Menu
screen, [all icons], appears.
3. Press the Select key. The second screen to appear indicates the software version. The numbers 380
XX or 544 XX are shown, where “XX” indicates software version for the DSR III P Controller
microprocessor. See Figure 4-25.
(04/14) 4 - 16
Section 4 - Operation
Viewing and Clearing Alarm Codes
Figure 4-26 The Standard Display, showing the bAt (Low Battery Voltage) alarm
If the Alarm icon is present, one or more alarms have been detected.
To View Alarm Codes The alarm code shown in Figure 4-26 is for
alarm code bAt (Low Battery Voltage).
NOTE: See the table on the following page for
a list of DSR P Controller alarm codes. In
Section 3, see the table named Alarm Codes To Clear Alarm Codes
Displayed in the Main Menu for detailed • Correct the cause of the alarm code.
descriptions of DSR P Controller alarm
codes. • Press the Select key to remove the alarm
code.
If the Alarm icon is present, press the Select
key once to show the Alarm screen. The most
If more than one alarm code is present, press
recent alarm code is shown on the display. the Select key to clear each alarm code
• If no alarm conditions have occurred, the individually.
Alarm icon does not appear. (If the Select
key is pressed, the Alarm screen does not
appear).
(04/14) 4 - 17
Section 4 - Operation
DSR P Controller Alarm Codes
The following table indicates the alarm codes that the DSR P Controller can experience. All of the
alarm codes can appear on the display of the In-cab Control Box. In Section 3, see the table entitled
Alarm Codes Displayed in the Main Menu for a description of each alarm code.
Auto or
Manual
Restart
Alarm After Alarm
Code is Cleared Description
P1E Auto When [----] appears: indicates that the return air temperature in the main load
compartment is outside of the readable range.
P2E Auto When [----] appears: indicates that the return air temperature in the remote load
compartment is outside of the readable range.
OL Manual Electric Standby electric motor protector overload.
bAt Manual Low battery voltage.
HP Auto High Pressure in refrigeration system failure (HPCO fault).
LP Auto Low Pressure in refrigeration system failure (LPCO fault).
PSE Auto High Pressure sensor fault.
tEP Auto Electric standby motor thermal protection alarm
tP4 Auto Power supply thermal protection automatic alarm
dr1 Auto Door open or Door Switch 1 faulty.
dr2 Auto Door open or Door Switch 2 faulty.
tCO Auto Electronic Control Module internal temperature exceeds specified limit.
SOF Auto Microprocessor software failure.
-C- ------- Communications failure between the In-Cab Control Box and the ECM.
(04/14) 4 - 18
Section 4 - Operation
Initiating the Evacuation Mode
1. From the Standard Display, press and hold the Up Arrow key and Down Arrow key for seven seconds, then
release them. The Evacuation Menu screen appears.
2. To return to the Standard Display, Press and hold the Up Arrow key and Down Arrow key for seven
seconds, then release them, or switch off the In-cab Control Box.
NOTE: If this operation is done using the vehicle's battery for a very long time, you should connect it
to a charger to avoid discharging it.
(04/14) 4 - 19
Section 4 - Operation
(04/14) 4 - 20
Section 5
Section 5
Diagnostics
DSRP Controller Notes ..................... 5 - 1
The following procedures might not readily The DSR P Controller printed circuit board(s)
apparent, but must be followed when working and In-cab Control Box can be damaged by
on units equipped with DSR P Controller electrostatic discharge. Any time that work is
microprocessors. performed directly on the printed circuit boards,
do the following:
• Turn off the unit before connecting or
disconnecting the vehicle battery • Use an ESD wrist strap, as shown in Service
Procedure A12A, ESD (Electrostatic
• Never use testers, consisting of a battery and Discharge) Procedure.
a light bulb, to test circuits on any
microprocessor-based equipment • Keep all printed circuit boards in anti-static
bags at all times.
• Any time the microprocessor is replaced, use
these Service Procedures: • Protect all defective printed circuit boards
and In-cab Control Boxes from physical
– A02A - Recording Existing damage by placing them in the shipping
Microprocessor Settings carton supplied with the replacement. They
will be returned for failure analysis and
– A04A - Microprocessor Setup possible re-manufacture.
(Programming the DSR Microprocessor)
(04/14) 5-1
Section 5 - Diagnostics
DSR P Controller Diagnostic Part 1 - Corrective Actions as
Hints a Result of Alarm Codes
Section 5 is devoted to diagnostic routines In Section 3, see the table entitled Alarm Codes
designed to help the technician quickly identify Displayed in the Main Menu for a description of
the cause of a problem and repair it, using the the DSR P Controller alarm codes. In Section
correct tools, information, and procedures. It is 4, see the sub-section entitled DSR P
important that the required procedures be Controller Alarm Codes for a description of the
followed exactly. Failure to do so might result types of alarm codes that the DSR P
in an incomplete repair. Controller can experience.
(04/14) 5-2
Section 5 - Diagnostics
ALARM CODES, THEIR CAUSES AND CORRECTIVE ACTIONS
Code Cause or Explanation Corrective Action (check in order shown)
P1E, P2E Return Air Temperature Sensor 1. Check the Return Air Temperature sensor by checking
Fault the Standard Display.
(P1E = Main Load Compartment) - If the Standard Display shows [----], the return air
(P2E = Remote Load temperature is outside of the readable range. The
Compartment, if applicable) Return Air Temperature sensor might be defective, or
the circuit is open or has shorted.
A problem exists with the Return Air
Temperature sensor (temperature 2. Check the sensor connector at the sensor for damage
probe) or its wiring. The sensor is a or a broken wire.
thermistor-type sensor and can be 3. With the Return Air Temperature sensor disconnected,
checked with an ohmmeter. The check the sensor with an ohmmeter. Sensor resistance
sensor is located in the return air should should be close to shown below for each
stream before the evaporator coil. temperature:
The wiring is part of the sensor
harness. Temp Resistance Temp Resistance
(deg. C) (kOhms) (deg. C) (kOhms)
-25 86.43 45 4.911
-20 67.77 50 4.160
-15 53.41 55 3.536
-10 42.47 60 3.020
-5 33.90 65 2.588
0 27.28 70 2.228
5 22.05 75 1.924
10 17.96 80 1.668
15 14.69 85 1.451
20 12.09 90 1.266
25 10.00 95 1.108
30 8.313 100 0.9731
35 6.940 105 0.8572
40 5.827 110 0.7576
(04/14) 5-3
Section 5 - Diagnostics
ALARM CODES, THEIR CAUSES AND CORRECTIVE ACTIONS (continued)
Code Cause or Explanation Corrective Action (check in order shown)
P1E, P2E 7. Disconnect the sensor and temporarily connect a new
(continued) sensor. Run the unit in Cool and Heat modes. If the
new sensor displays correctly on the In-cab Control
Box, the removed sensor is malfunctioning.
8. If the resistance of the sensor and harness is correct,
replace the microprocessor. If the problem persists,
replace LB1 or LB2 and re-install the original
microprocessor.
9. Check the sensor, using Service Procedure D01A.
OL Electric Standby Overload 1. Allow the motor protector or overload relay several
minutes to cool. Turn the unit off and back on to clear
DANGER: High voltage is present
the alarm.
any time the unit is connected to
Electric Standby power. Death or 2. Check the voltage on all phases of the motor, to be
serious injury could result from sure it is within specification.
unsafe or improper handling of 3. Check for excessive drive motor current. Check the
the Electric Standby equipment. nameplate on the motor for the full-load amperage
rating. Correct any condition contributing to excessive
The optional Electric Standby motor load.
electric motor protector has tripped
4. Check the refrigeration system for any problems that
on single-phase units, or the
might cause an overload condition.
overload relay has tripped on
three-phase units. This alarm is 5. Check the adjustment of the OLR thermal relay, which
cleared automatically whenever the should be adjusted to the maximum amperage of the
unit is turned off and back on, using electric motor (based on the star configuration,
the In-cab Control Box On/Off key or in 3-phase units).
when the Electric Standby power 6. Check the continuity of the wire between overload
source is turned off and on. relay OL and pin B2, connector C-1 on LB1 or LB2.
See Service Procedure H04A.
7. Check for continuity between overload relay terminals
97 and 98. The contacts should be Normally Closed.
See Service Procedure H04A.
8. Check the CHX circuit for continuity to chassis ground.
bAt Low Battery Voltage 1. Check that the cables to the battery (BAT and CHA)
(alarm does not occur if the unit are tightly attached to the battery terminals.
is in Electric Standby mode) 2. Check the battery terminals for corrosion. The vehicle
NOTE: This alarm code can occur battery might be discharged or its electrolytic cells
if the unit is rapidly switched on might be damaged or leaking.
and off. Wait 5-10 seconds after 3. Check the operation of the truck alternator. Make sure
switching the unit off before that the belt is properly adjusted.
turning it back on. 4. At the battery, use a voltmeter or multi-meter to check
the voltage.
- For 12V units, the voltage must be between 10.5 Vdc
and 15.0 Vdc.
- For 24V units, the voltage must be between 21 Vdc
and 30 Vdc.
5. At connector C-1 on LB1 or LB2, check pins A1
(CH7-CHH) and A7 (BAT) for a pushed pin.
6. If the problem persists, replace LB1 or LB2.
(04/14) 5-4
Section 5 - Diagnostics
ALARM CODES, THEIR CAUSES AND CORRECTIVE ACTIONS (continued)
Code Cause or Explanation Corrective Action (check in order shown)
HP High Discharge Pressure 1. This alarm indicates that the refrigerant discharge
pressure, as sensed by the transducer, is excessively
high.
When the discharge pressure rises above the specified
value, the transducer opens the circuit to the
compressor clutch and stops compressor (and unit)
operations.
The transducer is connected to LB1 or LB2 at
connector C-1, pin C4 (high pressure), and C-1, pin C5
(5V power). Check for a pushed pin, loose pin crimp,
or broken wire.
2. Check for obstructions, debris, or dirt on the condenser
coil and condenser fans. (Obstructions can increase
the discharge pressure).
3. Check the connector on the transducer for a pushed
pin or missing pin wedge, loose pin crimp, or broken
wire. See Service Procedure H02A.
4. Check if the pressure transducer is faulty.
5. Check the refrigeration system for high discharge
pressure and correct the condition, as required.
6. Connect a pressure gauge to the high-pressure side of
the unit, with the unit operating. Check the high
pressure reading at the gauge. At the Information Menu
screen of the In-cab Control Box, check the
high-pressure reading. Verify that the high-pressure
reading at the Information Menu screen is the same as
the high-pressure reading at the pressure gauge. If not:
• Determine if the voltage between 5V-CHT is
approximately 5V. If the voltage is higher, check point 4.
(04/14) 5-5
Section 5 - Diagnostics
ALARM CODES, THEIR CAUSES AND CORRECTIVE ACTIONS (continued)
Code Cause or Explanation Corrective Action (check in order shown)
LP Low Suction Pressure 1. This alarm indicates that the suction pressure, as
sensed by the Low Pressure Cut-Out (LPCO) switch,
is excessively low. When the suction pressure falls
below the specified value, the LPCO opens the circuit
to the compressor clutch and stops compressor (and
unit) operations.
The LPCO is connected to LB1 or LB2 at connector
C-1, pin A2. Check for a pushed pin, loose pin crimp,
or broken wire.
2. Check compressor and unit operation for cause of the
low suction pressure. Check for possible obstruction in
the suction line or a lack of heat exchange in the
evaporator.
3. Inspect for blocked or dirty evaporator coil (causing
reduced volume of refrigerant reaching the evaporator
and contributing to reduced suction).
4. Determine if there is increased amperage draw at the
LPCO, for indication of a defective LPCO switch.
5. Check ground bolts and continuity between the
grounds and CHH (pin A1, connect C-1)
PSE High Pressure Sensor Fault 1. This alarm code indicates that the signal from the HP
sensor is outside of the readable range (<0.5 Vdc [at 0
psi] or >4.5 Vdc [at 500 psi]), and that a fault exists
with the high discharge pressure sensor.
2. Inspect for a blocked or dirty condenser coil.
3. Inspect for a faulty High Pressure transducer.
4. Check that pin C4 at connector C-1 on LB1 or LB2 is
connected (check for a pushed pin or loose pin crimp),
not corroded, and is not obstructed by dirt.
5. Observe the continuity between CHT (pin A4,
connector C-1) and the ground bolts.
6. Make sure that the voltage between pins A4 and C4 on
connector C-1 corresponds to the table below.
(04/14) 5-6
Section 5 - Diagnostics
ALARM CODES, THEIR CAUSES AND CORRECTIVE ACTIONS (continued)
Code Cause or Explanation Corrective Action (check in order shown)
tEP Electric standby motor thermal 1. This alarm code indicates that the thermal protection
protection alarm circuit has opened in one of the two Electric Standby
motors (D.C. or A.C.) due to engine overheating or
circuit failure.
2. If alarm persists, use a multimeter to check voltage
between the R1K resistance posts (located in aerial
connector next to the ECM).
• If 12 or 24 VDC, check the voltage at LB1 or LB2
between connector C-1, pin C2 (DK3), and connector
C-1, pin A1 (CH). If 0 VDC, test for continuity between
R1K resistance and pin C2. If 12 or 24 VDC, replace
LB1 or LB2, using Service Procedure B02A. Perform
complete microprocessor setup using Service
Procedure A04A.
• If 0 VDC, go to Item 3.
3. Determine which motor matches the open thermal
protection circuit. In B-100 10 units this will be possible
only in the D.C. motor.
4. If circuit is open, disconnect C-40 connector in DC
motor and measure thermal switch continuity:
• Test brushes, pulley and correct belt alignment.
• Check refrigeration system for any problems that might
cause DC motor overheating.
• If problem persists, replace DC motor using procedure
shown in Direct Drive Units (DSR) Service Manual TK
52979-18-BD. Chapter B-100 10/20.
5. Disconnect C-2 connector in AC motor and measure
thermal switch continuity, if circuit is open.
• Test pulley and correct belt alignment.
• Check refrigeration system for any problems that might
cause AC motor overheating.
• If problem persists, replace AC motor using procedure
shown in Direct Drive Units (DSR) Maintenance
Manual TK 52979-18-BD. Chapter B-100 10/20.
tP4 Power supply thermal protection 1. This alarm code indicates that the power supply
alarm thermal protection circuit has opened due to
overheating of the rectifier bridges or circuit failure.
2. If the alarm continues, use a multimeter to test the
current through each rectifier bridge (2R wires). Verify
that the current through each rectifier bridge does not
exceed 15 A.
3. Check that the rectifier bridge heat sink is clean and
that the rectifier bridges are properly installed.
(04/14) 5-7
Section 5 - Diagnostics
ALARM CODES, THEIR CAUSES AND CORRECTIVE ACTIONS (continued)
Code Cause or Explanation Corrective Action (check in order shown)
dr1, dr2 Door Open/Door Switch Failure 1. This alarm indicates one or more of the following:
- A door is open. Check if the door is open and close it.
- Wire DSW1 between door switch 1 and LB1 or LB2,
or wire DSW2 between door switch 2 and LB2, is
defective. Remove the applicable door switch and
check the wire to the switch for voltage of +5 Vdc.
- Voltage at A3 of connector C-1 or pin B1 of connector
C-1 on LB1 or LB2, is faulty.
2. Confirm that the load compartment doors are closed.
Check the In-cab Control Box screen. If the [dr1] or
[dr2] alarm codes still appear, check the DSW1 and
DSW2 door switches for damage, cut or broken wires,
corrosion, or misalignment.
3. Check the polarity setting at the Installation (Guarded
Access) Menu. Make sure that the polarity for a
Normally Closed door switch is 0, and that the polarity
for a Normally Open door switch is 1.
tCO Electronic Control Module 1. This alarm indicates that the microprocessor has detected
Internal Temperature Exceeds an excessively high (>90°C) temperature inside the ECM
Limit enclosure. The board has exceeded the max operating
temperature either due to high ambient or internal heat
rise. Contact Service if the alarm code repeats.
SOF Microprocessor Software Failure 1. This alarm code indicates the In-cab Control Box
microprocessor has become defective, or that the
software has become corrupted.
2. If the software is corrupt, the microprocessor must be
reprogrammed. Complete the microprocessor setup
using Service Procedure A04A.
3. If the ECM microprocessor is corrupted or damaged,
replace the microprocessor by replacing LB1 or LB2,
using Service Procedure B02A. Complete the
microprocessor setup, using Service Procedure H04A.
4. If the firmware has been updated from MSK380.xx to
MSK544.xx, this alarm is to notify that the parameters
have been reset. To fix it, the appropriate parameters
for the unit must be charged using Service Procedure
A04A.
(04/14) 5-8
Section 5 - Diagnostics
ALARM CODES, THEIR CAUSES AND CORRECTIVE ACTIONS (continued)
Code Cause or Explanation Corrective Action (check in order shown)
-C- Communications Failure, 1. Check the cable between LB1 or LB2 and the In-cab
Microprocessor to In-cab Control Control Box. Look for a loose connector or damage to
Box. the cable. Look for disconnected wires or damaged
pins on the cable, at connector C-1 on LB1 or LB2, or
at the connector on the In-cab Control Box. Look for
dirt or debris at all connectors.
2. Using a multimeter, check the voltage at LB1 or LB2
between connector C-1, pin C7 (9V), and connector
C-1, pin A1 (CH). Minimum voltage = 7.5 Vdc.
Maximum voltage = 9 Vdc.
3. Check the continuity of all wires from LB1 or LB2 to the
In-cab Control Box: black wire at connector C-1, pin B6
(RDX, comms); blue wire at connector C-1, pin B7
(TXD, comms); yellow/green wire at connector C-1, pin
A1 (in splice) (CH, ground); red wire at connector C-1,
pin C7 (9V, In-cab power supply); and shield wire at
connector C-1, pin A1 (in splice) (GND, shield). See
Service Procedure H04A.
4. In microprocessors with firmware versions 380.xx and
more recent, test to reinstall the firmware again. See
Service Procedure A46A.
5. If the problem persists, reload the configuration
parameters of the unit. See Service Procedure A04A.
6. Remove and replace the In-cab Control Box. If the
replacement does not function, replace LB1 or LB2.
(04/14) 5-9
Section 5 - Diagnostics
Part 2 - Corrective Actions as Important Diagnostic Considerations
a Result of Other Symptoms • In some cases, replacement of LB1 or LB2,
and/or PB1/PB2 is suggested. If replacing
the printed circuit board corrects the
A problem with the unit might exist without
problem, recheck the new printed circuit
generating an alarm code. The following pages
board and the original printed circuit board,
are suggested corrective actions to be taken
as the original printed circuit board might
when dealing with these symptoms. They have
not have been defective.
been broken into sections for ease in locating
specific symptoms. • When performing diagnostics, consider if
the problem is caused by the refrigeration
system rather than the controls.
(04/14) 5 - 10
Section 5 - Diagnostics
No voltage in 01 and/or 03 (pin Check the continuity between the ECM side and the
A8, connector C-1) in the ECM, battery side. If no continuity, repair the wiring.
even with the ignition on.
Loose or disconnected printed Check LB1 or LB2 connector C1, to be sure they
circuit board connector. are attached securely.
Unit will not operate on Blown unit power fuse F21 Check unit power fuse F21, located near the
vehicle power, but the vehicle battery.
In-Cab Control Box
display turns on.
Loose or disconnected printed Check LB1 or LB2 connector C1, PB1 connector
circuit board connector. C2 and PB2 connector C3 to be sure they are
attached securely.
No voltage in wires 2 and/or 2A Check unit power fuse F21 and BATR relay.
Replace, if necessary.
Defective microprocessor or Replace In-cab Control Box or
printed circuit board. LB1 or LB2, and/or PB1/PB2. Setup the
replacement printed circuit board in accordance
with Service Procedure A04A.
(04/14) 5 - 11
Section 5 - Diagnostics
An alarm is activated in the Correct the condition that caused the alarm.
In-cab Control Box.
Defective wiring harness or Check wiring and connections for CLU1-01 circuit.
loose connector for CLU1-01 Using the schematic diagram, check splice 2.
circuit.
Vehicle compressor Refrigerant system problem. Check refrigerant system. Check for level
clutch is engaged, but refrigerant level
unit is not cooling.
Defective compressor Determine if the compressor is defective. Replace
it, if necessary.
(04/14) 5 - 12
Section 5 - Diagnostics
Blown unit power fuse F21. Check unit power fuse F21 located near the vehicle
battery.
An alarm is activated in the Correct the condition that caused the alarm.
In-cab Control Box.
Defective wiring harness or Check wiring and connections for CLU1-01 circuit.
loose connector for CLU1-01 Using the schematic diagram, check harness
circuit. splice.
Vehicle compressor Refrigerant system problem. Check refrigerant system. Check for level
clutch is engaged but refrigerant level
vehicle is not heating.
Defective compressor Determine if the compressor is defective. Replace
it, if necessary.
(04/14) 5 - 13
Section 5 - Diagnostics
Defrost Initiation Time [dit] is In the Installation (Guarded Access) Menu, scroll to
not set or set to an incorrect the [dit] parameter screen. Check if the time (factory
time. default = 240 minutes) is too short or too long
between defrost initiation cycles. Change the time
setting, as required.
Defrost klixon (DK1/DK2) wire Inspect the wiring and connector and make sure
12/12A not connected in the that DK1/DK2 wire 12/12A is securely connected.
ECM (at pins C1 or C6 of
connector C1).
Defrost klixon (DK) is defective Inspect the klixon for defects. Replace the klixon,
as required.
The condenser will not Vehicle not running or unit not Start vehicle and turn unit on.
defrost (reverse cycle turned on.
units only).
Initiate a manual defrost cycle Press the Select key until the display briefly shows
using the Main Menu. [dFC]. The defrost icon should appear. Accordingly,
press the Enter key, then the Up or Down arrow
key, to change settings. This will change the defrost
setting in 1-degree Celsius increments.
Defrost Initiation Time [di2] is In the Installation (Guarded Access) Menu, scroll to
not set or set to an incorrect the [di2] parameter screen. Check if the time
time. (factory default = 240 minutes) is too short or too
long between defrost initiation cycles. Change the
time setting, as required.
(04/14) 5 - 14
Section 5 - Diagnostics
UNIT WILL NOT DEFROST - VEHICLE POWER (continued)
Symptom Cause Corrective Action
The condenser will not Vehicle compressor clutch must If the compressor clutch does not energise,
defrost (reverse cycle be energised and compressor determine the cause of the problem by following the
units only) (continued). must be operating. instructions in the UNIT NOT COOLING –
VEHICLE POWER section.
Defrost klixon (DK2) wire 12A Inspect the wiring and connector and make sure
not connected in the ECM that DK2 wire 12A is securely connected.
(at pin C6 of connector C1
on LB1 / LB2).
Defrost klixon (DK2) is Inspect the klixon for defects. Replace the klixon,
defective. as required.
Compressor is Blown hot gas solenoid fuse F5. Check the hot gas solenoid fuse F5. Check all loads
running, hot gas connected to the relays protected by F5 (see
solenoid is not section 2 of this manual) to ensure there are no
energised. short circuits or defects that have caused the fuse
to blow.
Loose or defective wire 26 to Check wire 26 to the hot gas solenoid, PS1. Check
hot gas solenoid. the pin connections at PB1 connector C-2, pin 8 for
crimps or loose connections.
Defective hot gas solenoid, Check hot gas solenoid PS1 for proper operation.
PS1.
Open hot gas solenoid Check the continuity of the hot gas solenoid coil.
See Service Procedure H04A.
Not output voltage to the hot For defective relay on PB1, replace PB1. If the
gas solenoid (wire 26) solenoid is not energised after replacement of PB1,
Replace LB1 or LB2.
(04/14) 5 - 15
Section 5 - Diagnostics
UNIT WILL NOT DEFROST - VEHICLE POWER (continued)
Symptom Cause Corrective Action
Compressor is Refrigerant system problem. Check refrigerant system.
running, hot gas valve
is energised, but unit
is not defrosting.
Evaporator fan(s) stuck on. Check operation of evaporator fans.
(04/14) 5 - 16
Section 5 - Diagnostics
Blown unit power fuse F21. Check unit power fuse F21 located near the vehicle
battery.
Blown evaporator fan fuses on Check evaporator fan fuses F3 and F4 for units with
PB1 / PB2. one or two fans on PB1, and fuses F9 and F10 for
units with three or four fans on PB2. Check
evaporator fan motors for short to ground.
Open evaporator fan motors. Check the continuity of the evaporator fan motors.
See Service Procedure H04A.
Loose or defective EF1, EF2, Check the EF1, EF2, EF3 or EF4 circuit to the
EF3 or EF4 circuit to the evaporator fan motors.
evaporator fan motors.
Evaporator fans The fan speed control signal is Check that the fan speed control signal is not too
should be running but too low. low (close to 1 V), pin B5 of connector C-1 on LB1
are not (units with fan or LB2. Check the DSR microprocessor
speed control only). parameters. Replace LB1 or LB2, as needed.
Defective LB1 or LB2: Replace LB1 or LB2.
Defective relay on PB1/PB2: Replace PB1/PB2.
Not all evaporator fans The microprocessor has been Check the DSR microprocessor parameters.
are running. programmed for the wrong
unit.
(04/14) 5 - 17
Section 5 - Diagnostics
CONDENSER FANS DO NOT OPERATE - VEHICLE POWER
The unit is equipped with 1 or 2 condenser fans. These fans operate in Cool mode when the condenser fan
pressure switch is closed.
Symptom Cause Corrective Action
Condenser fans Vehicle not running or unit not Start vehicle and turn unit on. Be sure conditions
should be running but turned on. require condenser fans to be operating.
are not.
Blown unit power fuse F21. Check unit power fuse F21 located near the vehicle
battery.
Defective wiring harness or Check wiring and connections for the CF1-01 or
loose connector for CF1-01 CF1-02 circuits.
circuit (for units with CFM1) or
CF1-02 (for units with CFM2)
circuits.
Discharge pressure is greater Enter cab control information Menu and display HP
than CFP but fan is not value; test that pressure reading is correct, using
energised. gauge. Check refrigeration system and replace high
pressure transducer, if applicable.
The fan speed control signal is Check that the fan speed control signal is not too
too low (units with fan speed low (close to 1 V), pin A5 of connector C-1 on LB1
control only). or LB2. Check the DSR microprocessor
parameters. Replace LB1 or LB2, as needed.
(04/14) 5 - 18
Section 5 - Diagnostics
CONDENSER FANS DO NOT OPERATE - VEHICLE POWER (continued)
The unit is equipped with 1 or 2 condenser fans. These fans operate in Cool mode when the condenser fan
pressure switch is closed.
Symptom Cause Corrective Action
Condenser fans Blown condenser fan fuses. Check in-line fuses F30 (CF1), F31 (CF2) in the
should be running but See the applicable electric harness in control box - condenser section. Check
are not (continued). schematic for the unit. the condenser fan motors for short to ground.
Open condenser fan motor Check continuity of condenser fan motors CFM1
circuits. and CFM2. See Service Procedure H04A.
(04/14) 5 - 19
Section 5 - Diagnostics
UNIT WILL NOT OPERATE - BATTERY DRIVEN (B-100)
Symptom Cause Corrective Action
Unit does not operate Vehicle ignition switch is not on Turn vehicle ignition switch on.
and the In-cab Control
Box screen remains
blank. Power ignition fuse F14 blown. Check power ignition fuse F14 located near vehicle
battery. Replace, if necessary.
Fuse F1 in Logic board LB1 Check fuse F1 (5A) in LB1. Replace, if necessary.
blown
Service vehicle battery.
Dead or disconnected vehicle
battery.
Verify that cable is connected between LB1 in the
Defective or disconnected ECM and the In-cab Control Box.
In-cab Control Box
Check continuity between ECM side and battery
No voltage in BAT (pin A7, side. If no continuity, repair wiring.
connector C-1) and/or 03
(pinA8, connector C-1) in the
ECM, even with the ignition on.
Check connectors C1 on LB1 to ensure they are
Loose or disconnected printed securely attached
circuit board connector.
Replace In-cab Control Box. Setup replacement
Defective microprocessor or In-cab Control Box in accordance with Service
printed circuit board. Procedure A04A.
Unit does not operate Blown FP power ignition fuse. Check FP power ignition fuse (100A in 12V units;
but In-cab Control Box 60A in 24V units), located near vehicle battery.
screen remains lit. Replace, if necessary.
Loose or disconnected printed Check connectors C1 on LB1 to ensure they are
circuit board connector. securely attached.
No voltage in RM relay Check FP power ignition fuse (100A in 12V units;
connector 30. 60A in 24V units) and RM relay. Replace, if
necessary.
Defective microprocessor on Replace in-Cab Control Box or LB1.
Logic board LB1. Defective microprocessor in logic board: Replace
LB1.
Setup replacement printed circuit board in
accordance with Service Procedure A04A.
(04/14) 5 - 20
Section 5 - Diagnostics
(04/14) 5 - 21
Section 5 - Diagnostics
(04/14) 5 - 22
Section 5 - Diagnostics
EVAPORATOR FAN WILL NOT OPERATE - BATTERY DRIVEN (B-100)
The unit is equipped with 1 evaporator fan.
Symptom Cause Corrective Action
Evaporator fan should Vehicle not running or unit not Start vehicle and turn unit on. Make sure conditions
be running but is not. turned on. require evaporator fans to be operating.
Blown FP power ignition fuse. Check FP power ignition fuse located near vehicle
battery. Replace, if necessary.
Evaporator fan F3 fuse blown Check evaporator fan F3 fuse, located on the
on PB1. printed circuit board. Check EFM evaporator fan
Electric Standby motor for short circuit to ground.
Loose or defective EFM circuit Check Electric Standby evaporator fan motor EFM
to Electric Standby evaporator circuit.
fan motor.
CONDENSER FAN WILL NOT OPERATE - BATTERY DRIVEN (B-100)
The unit is equipped with 1 condenser fan. This fan operates in Cool mode when the condenser fan pressure
switch is closed.
Symptom Cause Corrective Action
Condenser fan should Vehicle not running or unit not Start vehicle and turn unit on. Make sure conditions
be running but is not. turned on. require condenser fans to be operating.
Blown FP power ignition fuse. Check FP power ignition fuse located near vehicle
battery. Replace, if necessary.
(04/14) 5 - 23
Section 5 - Diagnostics
CONDENSER FAN WILL NOT OPERATE - BATTERY DRIVEN (B-100) (continued)
Symptom Cause Corrective Action
Condenser fan should Discharge pressure is greater Enter cab control information Menu and display HP
be running but is not than CFP but fan is not value; test that pressure reading is correct, using
(continued). energised. gauge. Check refrigeration system and replace high
pressure transducer, if applicable.
Condenser fan F30 fuse in the Check F30 in-line fuse in condenser harness. Test
harness. See electric Electric Standby condenser fan motor for short
schematic for the unit or sizes circuit to ground.
and description table in
Section 2.
Condenser fan motor capacitor Check Electric Standby CFM condenser fan motor
circuit open. continuity. See Service Procedure H04A.
UNIT WILL NOT OPERATE - ELECTRIC STANDBY POWER (except B-100 20 and V-100 20/50)
Symptom Cause Corrective Action
Unit will not operate on Unit not connected to Standby Connect power cord. Verify that the Electric
Electric Standby power power or Standby power is Standby power is turned on and is the correct
and the In-cab Control turned off. voltage.
Box display remains
blank.
Blown transformer primary Check transformer primary fuse F20.
fuse F20.
(04/14) 5 - 24
Section 5 - Diagnostics
UNIT WILL NOT OPERATE - ELECTRIC STANDBY POWER (except B-100 20 and V-100 20/50) (continued)
Symptom Cause Corrective Action
Unit will not operate on Defective bridge rectifier. Check the bridge rectifier, using a digital multimeter.
Electric Standby power See the schematic diagram for the voltage
and the In-cab Control requirements at the 12V or 24V bridge connections.
Box display remains
blank. (continued).
Defective step-down Check transformer continuity. See Service
transformer. Procedure H04A.
Pin X1 is misaligned or fit Examine the terminals. Bend the pins into
incorrectly on connector C-1 alignment or replace the connector, as necessary.
Defective or disconnected Verify cable is connected at the ECM and the In-cab
In-cab Control Box Control Box.
Loose or disconnected LB1 Check connectors C-1 on PB1 and/or C-2 on PB2
and/or PB2 connector. to be sure they are attached securely.
Unit will not operate on Defective Electric Standby Check Electric Standby relay STDR for functioning.
Electric Standby power power pack or circuitry Check the connection of wire 2RA between STDR
but In-cab Control Box and battery terminal board TB.
turns on.
Defective logic board LB1/LB2 Defective relay on power board PB1/PB2: Replace
or power board PB1/PB2. PB1/PB2.
Defective microprocessor in logic board: Replace
LB1/LB2.
UNIT NOT COOLING - ELECTRIC STANDBY POWER (except B-100 20 and V-100 20/50)
Symptom Cause Corrective Action
Electric Standby motor Power cord not plugged in or Connect the power cord and turn the unit on. Make
is not running, unit not turned on. sure that the setpoint and load compartment
compressor clutch temperature requires Cool mode.
does not engage.
Defective bridge rectifier. Check the bridge rectifier, using a digital multimeter.
(04/14) 5 - 25
Section 5 - Diagnostics
UNIT NOT COOLING - ELECTRIC STANDBY POWER (except B-100 20 and V-100 20/50) (continued)
Symptom Cause Corrective Action
Electric Standby motor Defective step-down Check the continuity of the transformer. See
is not running, transformer Service Procedure H04A, Checking Harness
compressor clutch Continuity.
does not engage
(continued).
Blown transformer fuse Check transformer fuse F20.
Blown hot gas solenoid fuse F5. Check power fuse F5 on PB1 and check all loads
connected to the relays protected by fuse F5.
Defective electric relay STDR Check electric relay STDR, located in the Electric
Standby power pack.
Discharge pressure above the Verify that the discharge pressure is below the
HPCO value, or Low Pressure HPCO value and that the LPCO is closed.
Cut-Out switch is open
Defective wiring harness or Check wiring and connections for the CLU2 circuit.
loose connector for the CLU2
circuit.
Defective wiring harness or a Inspect the wiring and connections for the CMC
loose connector for the CMC circuit.
circuit
Electric Standby motor Open Electric Standby Check the continuity of the Electric Standby
is running, compressor clutch coil or compressor clutch coil. See Service Procedure
compressor clutch defective clutch. H04A.
does not engage.
Defective wiring harness or Inspect the wiring and connector for the CLU2 circuit.
loose connector for CLU2 circuit
(04/14) 5 - 26
Section 5 - Diagnostics
UNIT NOT COOLING - ELECTRIC STANDBY POWER (except B-100 20 and V-100 20/50) (continued)
Symptom Cause Corrective Action
Electric Standby motor Loose or defective 2RA circuit Check the 2RA circuit to the Electric Standby motor
is running, to the Electric Standby motor contactor.
compressor clutch contactor.
does not engage
(continued).
Electric Standby motor Open Compressor Motor Check continuity on the CMC at wires L1/T1A and
is not running, and the Contactor (CMC). L2/T2A for single-phase units, and at wires L1/T1B,
compressor clutch L2/T2B, and L3/T3B for 3-phase units. See Service
does engage. Procedure H04A.
Open or defective L1, L2, Check that wiring is connected. Check wires L1, L2,
and/or L3 wire to the CMC. and/or L3 for shorts, abrasions, or damage.
Defective CMC wire connection Inspect pin 10 at connector C-2 on PB1 on the
from the ECM (pin 10, ECM. Check for bent or missing pin. Replace PB1,
connector C-2 on PB1) as necessary.
Electric Standby motor overload Turn unit off, allow overload relay to cool and turn
relay OLR has tripped. the unit back on to reset the overload relay. Check
motor operation to determine cause for overload
relay tripping.
Electric Standby There is a problem with the Check the Return Air Temperature sensors and
compressor clutch is refrigeration system. setpoint, check the refrigerant level, check the
engaged, but the unit evaporator and condenser for obstructions or
is not cooling. not-functioning valves.
(04/14) 5 - 27
Section 5 - Diagnostics
UNIT NOT HEATING - ELECTRIC STANDBY POWER (continued)
Symptom Cause Corrective Action
Electric Standby motor Defective bridge rectifier. Check the bridge rectifier, using a digital multimeter.
is not running,
compressor clutch
does not engage
(continued).
Defective step-down Check the continuity of the transformer. See
transformer Service Procedure H04A.
Defective electric relay STDR Check electric relay STDR, located in the Electric
Standby power pack.
Fuses F1 is blown. Check fuse F1 in ECM logic board.
Discharge pressure above the Verify that the discharge pressure is below the
HPCO value, or Low Pressure HPCO value and that the LPCO is closed.
Cut-Out switch is open
Defective wiring harness or Check wiring and connections for the CLU2 circuit.
loose connector for the CLU2
circuit.
Defective wiring harness or a Inspect the wiring and connections for the CMC
loose connector for the CMC circuit.
circuit
Electric Standby motor Open Electric Standby Check the continuity of the Electric Standby
is running, compressor clutch coil or compressor clutch coil. See Service Procedure
compressor clutch defective clutch. H04A.
does not engage.
(04/14) 5 - 28
Section 5 - Diagnostics
UNIT NOT HEATING - ELECTRIC STANDBY POWER (continued)
Symptom Cause Corrective Action
Electric Standby motor Defective wiring harness or Inspect the wiring and connector for the CLU2
is running, loose connector for CLU2 circuit.
compressor clutch circuit
does not engage
(continued).
Loose or defective 2RA circuit Check the 2RA circuit to the Electric Standby motor
to the Electric Standby motor contactor.
contactor.
Electric Standby motor Open Compressor Motor Check continuity on the CMC at wires L1/T1A and
is not running, and the Contactor (CMC). L2/T2A for single-phase units, and at wires L1/T1B,
compressor clutch L2/T2B, and L3/T3B for 3-phase units. See Service
does engage. Procedure H04A.
Open or defective L1, L2, Check that wiring is connected. Check wires L1, L2,
and/or L3 wire to the CMC. and/or L3 for shorts, abrasions, or damage.
Defective CMC wire Inspect pin 10, connector C-2 on PB1 on the ECM.
connection from the ECM (pin Check for bent or missing pin. Repair wire CMC
10, connector C-2 on PB1) connection or replace PB1, as necessary.
Electric Standby motor Turn unit off, allow overload relay to cool and turn
overload relay OLR has the unit back on to reset the overload relay. Check
tripped. motor operation to determine cause for overload
relay tripping.
Electric Standby There is a problem with the Check the Return Air Temperature sensors and
compressor clutch is refrigeration system. setpoint, check the refrigerant level, check the
engaged, but the unit evaporator and condenser for obstructions or
is not heating. not-functioning valves.
(04/14) 5 - 29
Section 5 - Diagnostics
UNIT WILL NOT DEFROST - ELECTRIC STANDBY POWER (except B-100 20)
Symptom Cause Corrective Action
Unit does not defrost. Power cord not plugged in or Connect power cord and turn unit on.
unit not turned on.
Initiate a manual defrost cycle Press the Select key until the display briefly shows
using the Select and Enter [dEF]. The defrost icon should appear. As desired,
Keys. press the Enter key, then the Up or Down arrow
key, to change the defrost setting in 1-degree
Celsius increments.
Defrost Initiation Time [dit] is not In the Installation (Guarded Access) Menu, scroll to
set or set to an incorrect time. the [dit] parameter screen. Check if the time (factory
default = 240 minutes) is too short or too long
between defrost initiation cycles. Change the time
setting, as required.
For units with older versions of Switch off the unit with the Direct Smart Reefer,
software revision 121 21: The before switching off the vehicle.
unit has been switched off using
the vehicle key.
Defrost klixon (DK1/DK2) wire Inspect the wiring and connector and make sure
12/12A not connected in the that DK1/DK2 wire 12/12A is securely connected.
ECM (at pin C1/C6 of connector
C-1 on LB1 or LB2).
The condenser will not Power cord not plugged in or Connect the power cord and turn the unit on.
defrost reverse cycle unit not turned on.
units only).
Initiate a manual defrost cycle Press the Select key until the display briefly shows
using the Select and Enter [dEF]. The defrost icon should appear. Accordingly,
Keys. press the Enter key, then the Up or Down arrow
key, to change settings. This will change the defrost
setting in 1-degree Celsius increments.
(04/14) 5 - 30
Section 5 - Diagnostics
UNIT WILL NOT DEFROST - ELECTRIC STANDBY POWER (except B-100 20) (continued)
Symptom Cause Corrective Action
The condenser will not Defrost Initiation Time [di2] is In the Installation (Guarded Access) Menu, scroll to
defrost reverse cycle not set or set to an incorrect the [di2] parameter screen. Check if the time
units only) (continued). time. (factory default = 240 minutes) is too short or too
long between defrost initiation cycles. Change the
time setting, as required.
Defrost klixon (DK2) wire 12A Inspect the wiring and the terminals. Make sure that
not connected in the ECM (at pin DK2 wire 12A is securely connected.
C6 of connector C-1 on LB1 or
LB2).
Blown host hot gas solenoid Check host hot gas solenoid fuse F5 at pin 8 of PB1
fuse F5 or remote hot gas connector C-2, and/or remote hot gas solenoid fuse
solenoid fuse F8. F8 at pin 10 of PB2 connector C-3. Check hot gas
solenoid coil for short to ground. If present, check
defrost drain heaters for short to ground.
Open hot gas solenoid coil. Check continuity of hot gas solenoid coil. See
Service Procedure H04A.
Defective hot gas solenoid. Check hot gas solenoid PS1 (host) or PS4 (remote)
for proper operation.
(04/14) 5 - 31
Section 5 - Diagnostics
UNIT WILL NOT DEFROST - ELECTRIC STANDBY POWER (except B-100 20) (continued)
Symptom Cause Corrective Action
Compressor is Loose or defective 26 circuit to Check the 26 circuit to hot gas solenoid PS1 (at pin
running, hot gas hot gas solenoid. 8 of PB1 connector C-2), or the 28 circuit to hot gas
solenoid is not solenoid PS4 (at pin 10 of PB2 connector C-3).
energised (continued).
(04/14) 5 - 32
Section 5 - Diagnostics
CONDENSER FANS DO NOT OPERATE - ELECTRIC STANDBY POWER (except B-100 20 and V-100 20/50)
The unit is equipped with 1 or 2 condenser fans. These fans operate in cool mode when the condenser fan
pressure switch is closed
Symptom Cause Corrective Action
Condenser fans Power cord not plugged in or Connect power cord and turn unit on. Be sure
should be running but unit not turned on. conditions require condenser fans to be operating.
are not.
Discharge pressure is greater Enter cab control information Menu and display HP
than CFP but fan is not value; test that pressure reading is correct, using
energised. gauge. Check refrigeration system and replace high
pressure transducer, if applicable.
Blown condenser fan fuses F30 Check the condenser fan fuses F30 and/or F31 in
and F31 in condenser section harnesses. Check the condenser fan motors for
harness. (See the applicable short to ground.
electric schematic for the unit,
or the table in Section 2.
(04/14) 5 - 33
Section 5 - Diagnostics
CONDENSER FANS DO NOT OPERATE - ELECTRIC STANDBY POWER (except B-100 20 and V-100 20/50) (continued)
The unit is equipped with 1 or 2 condenser fans. These fans operate in cool mode when the condenser fan
pressure switch is closed
Symptom Cause Corrective Action
Condenser fans Open condenser fan motors. Check continuity of condenser fan motors. See
should be running but Service Procedure H04A.
are not (continued).
The fan speed control signal is The fan speed control signal is too low.
too low.
Check that the fan speed control signal is not too
low (close to 1 V), pin A5 of connector C-1 on logic
board. Check the DSR microprocessor parameters.
Replace logic board LB1/LB2, as needed.
Loose or defective CF1-02 and Check the CF1-02 circuit (for units with a single
CF2-02 circuits to condenser condenser fan) and the CF2-02 circuit (for units with
fan motors. two condense fans) to condenser fan motors CFM1
and/or CFM2.
Not all condenser fans The microprocessor has been Check the DSR microprocessor parameters. As
are running. programmed for the wrong unit. necessary, reprogram the microprocessor, using
Service Procedure H04A.
EVAPORATOR FANS DO NOT OPERATE - ELECTRIC STANDBY POWER (except B-100 20 and V-100 20/50)
Symptom Cause Corrective Action
Evaporator fans Power cord not plugged in or Connect power cord and turn unit on. Be sure
should be running but unit not turned on. conditions require condenser fans to be operating.
are not.
Defective wiring harness or Check wiring and connections for EF1 and EF2
loose connector for EF1 or circuits.
EF 2 circuits
(04/14) 5 - 34
Section 5 - Diagnostics
EVAPORATOR FANS DO NOT OPERATE - ELECTRIC STANDBY POWER (except B-100 20 and V-100 20/50) (continued)
Symptom Cause Corrective Action
Evaporator fans Blown evaporator fan fuses on Check evaporator fan fuses F3 and F4 for units with
should be running but PB1/PB2. one or two fans on the power board PB1 and F9
are not (continued). and F10 for units with three or four fans on the
power board PB2. Check evaporator fan motors for
short to ground.
Blown evaporator fan fuse F3 Check 15A/12V or 10A/24V evaporator fan fuses
and F4 on PB1 (fuse F9 on F3 and F4 (and F9), located on PB1/PB2. Check
PB2 is for units with evaporator evaporator fan motors EFM1 and EFM2 for short to
fan EF3) ground. For units with EF3, check evaporator fan
motor EFM3 for short to ground.
Open evaporator fan motors Check the continuity of the evaporator fan motors.
Service Procedure H04A.
Loose or defective EF1, EF2, Check the EF1, EF2, or EF3, or EF4 circuit to the
or EF3, or EF4 circuit to the evaporator fan motors.
evaporator fan motors
Evaporator fans The fan speed control signal is Check that the fan speed control signal is not too
should be running but too low. low (close to 1 V), pin B5 of connector C-1 on
are not (units with fan LB1/LB2. Check the DSR microprocessor
speed control only). parameters. Replace LB1/LB2, as needed.
Not all condenser fans The microprocessor has been Check the DSR microprocessor parameters.
are running. programmed for the wrong unit.
(04/14) 5 - 35
Section 5 - Diagnostics
UNIT WILL NOT OPERATE - ELECTRIC STANDBY POWER (B-100 20 only)
Symptom Cause Corrective Action
Unit will not operate on Unit not connected to Standby Connect power cord. Verify that the Electric Standby
Electric Standby power power or Standby power is power is turned on and is at correct voltage.
and In-cab Control Box turned off.
display remains blank.
AC/DC SMPS power supply Check voltage between AC/DC SMPS power
does not operate. supply V+ and V- posts (12 VDC for 12V units, 24
VDC for 24V units). Replace power supply, if
necessary. Check for short circuit between X1, 2RB
wires and chassis. AC/DC SMPS power supply has
an auto-protection mechanism that turns off supply
in case of short circuit or overload.
Defective or disconnected Verify cable is connected at the ECM and the In-cab
In-cab Control Box Control Box.
Loose or disconnected LB1 Check connectors C-1 on LB1 to ensure they are
connector securely attached
Unit will not operate on Defective Electric Standby Check Electric ER1 Standby relay is operating.
Electric Standby power power pack or circuitry Check 2RB wire connection between ER1 and
but In-cab Control Box SMPS AC/DC power supply.
turns on.
Defective In-cab Control Box Check PC connection between ER1 and PB1.
microprocessor or LB1 or PB1. Replace In-cab Control Box or LB1 or PB1.
(04/14) 5 - 36
Section 5 - Diagnostics
UNIT NOT COOLING - ELECTRIC STANDBY POWER (B-100 20 only) (continued)
Symptom Cause Corrective Action
AC motor fails to run. AC/DC SMPS power supply Check voltage between AC/DC SMPS power
(continued). does not operate. supply V+ and V- posts (12 VDC for 12V units, 24
VDC for 24V units). Replace power supply, if
necessary.
Check for short circuit between X1, 2RB wires and
chassis. AC/DC SMPS power supply has an
auto-protection mechanism that turns off supply in
case of short circuit or overload.
Defective electric ER1 relay. Check electric ER1 relay, located in the Electric
Standby power pack.
Discharge pressure is above Verify that the discharge pressure is below the
HPCO value or the Low Pressure HPCO value and that the LPCO is closed.
Cut-Out switch is open.
Defective CMC Compressor Check CMC circuit wiring and connections, replace
Motor Contactor. contactor, if necessary.
AC motor runs, but Refrigeration system problem. Check return air temperature sensors and setpoint,
unit fails to refrigerate. refrigerant level, evaporator and condenser for
obstructions or non-operating valves.
(04/14) 5 - 37
Section 5 - Diagnostics
UNIT NOT COOLING - ELECTRIC STANDBY POWER (B-100 20 only) (continued)
Symptom Cause Corrective Action
AC motor runs, but Defective DC motor. Check brushes and replace, if applicable.
unit fails to refrigerate Determine if DC power supply is defective and
(continued). replace, if necessary. Use procedure shown in
Direct Drive Units (DSR) Maintenance Manual TK
52979-18-BD. Chapter B-100 10/20
DC motor belt incorrectly Test DC motor belt and replace, if necessary. Use
mounted or defective. procedure shown in Direct Drive Units (DSR)
Maintenance Manual TK 52979-18-BD. Chapter
B-100 10/20
Initiate a manual defrost cycle Press the Select key until [dEF] is briefly displayed
using the Select and Enter on screen. The defrost icon should appear.
Keys. Accordingly, press the Enter key, then the Up or
Down arrow key, to change settings. This will
change the defrost setting in 1-degree Celsius
increments.
Defrost Initiation Time [dit] is In the Installation (Guarded Access) Menu, scroll to
not set or set incorrectly. the [dit] parameter screen. Check if setting (factory
default = 240 minutes) is too short or too long
between defrost initiation cycles. Change the time
setting, as required.
Defrost klixon (DK) wire 12 is Check wiring and terminals. Make sure the DK
not connected to ECM (pin C1, cable 12 is securely connected.
connector C-1)
(04/14) 5 - 38
Section 5 - Diagnostics
UNIT WILL NOT DEFROST - ELECTRIC STANDBY POWER (B-100 20 only) (continued)
Symptom Cause Corrective Action
Compressor is AC/DC SMPS power supply Check voltage between AC/DC SMPS power
running; hot gas does not operate. supply V+ and V- posts (12 VDC for 12V units, 24
solenoid is not VDC for 24V units). Replace power supply, if
energised. necessary. Check for short circuit between X1, 2RB
wires and chassis. AC/DC SMPS power supply has
an auto-protection mechanism that turns off supply
in case of short circuit or overload.
Hot gas solenoid F5 fuse Check host hot gas solenoid F5 fuse on PB1.
blown. Check all loads connected to relays protected by
fuse F5.
Open hot gas solenoid coil. Check gas solenoid coil continuity. See Service
Procedure H04A.
Defective hot gas solenoid. Check hot gas solenoid PS1 (host) for proper
operation.
Loose or defective 26 circuit to Check circuit 26 to the hot gas solenoid, PS1 (pin 8,
hot gas solenoid. PB1 connector C-2).
(04/14) 5 - 39
Section 5 - Diagnostics
CONDENSER FAN WILL NOT OPERATE - ELECTRIC STANDBY POWER (B-100 20 only)
The unit is equipped with 1 condenser fan. The fan runs in cooling mode when the condenser fan pressure
switch is closed.
Symptom Cause Corrective Action
Condenser fan should Power cord not plugged in or Connect the power cord and turn the unit on. Make
be running but is not. unit not turned on. sure conditions require condenser fans to be
operating.
Discharge pressure is greater Enter cab control information Menu and display HP
than CFP but fan is not value; test that pressure reading is correct, using
energised. gauge. Check refrigeration system and replace high
pressure transducer, if applicable.
AC/DC SMPS power supply Check voltage between AC/DC SMPS power
does not operate. supply V+ and V- posts (12 VDC for 12V units, 24
VDC for 24V units). Replace power supply, if
necessary. Check for short circuit between X1, 2RB
wires and chassis. AC/DC SMPS power supply has
an auto-protection mechanism that turns off supply
in case of short circuit or overload.
Condenser inline fuse F30 in Check in line fuse F30 in the condenser harness
the condenser harness section section. Test Electric Standby condenser fan motor
blown. See electric schematic for short circuit to ground.
for the unit or Sizes and
description of fuses table in
Section 2.
Condenser fan motor capacitor Check continuity of condenser fan Electric Standby
circuit open. motors. See Service Procedure H04A.
(04/14) 5 - 40
Section 5 - Diagnostics
CONDENSER FAN WILL NOT OPERATE - ELECTRIC STANDBY POWER (B-100 20 only) (continued)
The unit is equipped with 1 condenser fan. The fan runs in cooling mode when the condenser fan pressure
switch is closed.
Symptom Cause Corrective Action
Condenser fan should Defective wiring harness or Check CF1 circuit wiring and connections.
be running but is not loose CF1 circuit connectors.
(continued).
EVAPORATOR FAN WILL NOT OPERATE - ELECTRIC STANDBY POWER (B-100 20 only)
Symptom Cause Corrective Action
Evaporator fan should Power cord not plugged in or Connect the power cord and turn the unit on.
be running but is not. unit not turned on. Make sure conditions require condenser fans to be
operating.
AC/DC SMPS power supply Check voltage between AC/DC SMPS power
does not operate. supply V+ and V- posts (12 VDC for 12V units, 24
VDC for 24V units). Replace power supply, if
necessary. Check for short circuit between X1, 2RB
wires and chassis. AC/DC SMPS power supply has
an auto-protection mechanism that turns off supply
in case of short circuit or overload.
Evaporator fan F3 fuse blown Check evaporator fan F3 fuse, located on the
on PB1. power board PB1. Check EFM evaporator fan
Electric Standby motor for short circuit to ground.
(04/14) 5 - 41
Section 5 - Diagnostics
EVAPORATOR FAN WILL NOT OPERATE - ELECTRIC STANDBY POWER (B-100 20 only) (continued)
Symptom Cause Corrective Action
Evaporator fan should Electric Standby evaporator Check Electric Standby evaporator fan motor
be running but is not fan motor open. continuity. See Service Procedure H04A.
(continued).
Loose or defective EFM circuit Check evaporator fan Electric Standby EFM circuit.
to Electric Standby evaporator
fan motor.
Open evaporator fan motors. Check the continuity of the evaporator fan motors.
See Service Procedure H04A.
ERRATIC OPERATION
Symptom Cause Corrective Action
Intermittent or erratic Loose logic circuit board Check the C-1 connector on logic board LB1 or LB2
operation of the connector C-1. to be sure that they are attached securely.
microprocessor. Check the interface pins connectivity between the
logic board and power board.
Defective wiring harness. Check wiring harness for damage. Verify all
connections are secure.
Loose or broken ground wires Check all ground wires and connections. A
or connections. common ground point is located next to the ECM.
(04/14) 5 - 42
Section 6
Section 6
Service Procedures
MICROPROCESSOR PROCEDURES
MISCELLANEOUS PROCEDURES
Where Used
All units equipped with DSR P Controller microprocessors and Revision 380 XX or 544 XX software.
Purpose
This procedure should be used to retrieve and record the current settings of a microprocessor. These
settings will then be duplicated in the replacement microprocessor. This must be done prior to
replacement of a microprocessor.
1 P41PA02A - 04/14
Service Procedure A02A
STEP ACTION RESULTS COMMENTS
16 Press the Select key. The Refrigerant Type [134] or Record the [134] or [404]
[404] screen appears. setting on the Setup Sheet.
17 Press the Select key. The Battery Voltage [bAt] screen Record the [bAt] setting on the
appears. Setup Sheet.
18 Press the Select key. The High Pressure [HP] screen Record the [HP] setting on the
appears. Setup Sheet.
19 Press the Select key. The Compartments / Unit Type Record the [xC / tyy] setting
[xC/ tyy] screen appears. on the Setup Sheet.
20 Press the Select key. The display returns to the
Standard Display.
21 Press and hold the Down The setpoint temperature Record the [SPL] setting on
Arrow and Enter keys for minimum value parameter [SPL] the Setup Sheet.
3 seconds. screen appears on the
installation menu (guarded
NOTE: In some software
access).
versions, the setpoint
temperature [SP] appears
first.
22 Press the Down key The setpoint temperature Record the [SPH] setting on
maximum value parameter [SPH] the Setup Sheet.
screen appears (MSK544.xx
only).
23 Press the Down key The Zone 2 setpoint temperature Record the [SL2] setting on
minimum value parameter [SL2] the Setup Sheet.
screen appears (MSK544.xx
only).
24 Press the Down key The Zone 2 setpoint temperature Record the [SH2] setting on
maximum value parameter [SH2] the Setup Sheet.
screen appears (MSK544.xx
only).
25 Press the Down key The Setpoints Differential [diF] Record the [diF] setting on the
parameter screen appears. Setup Sheet.
26 Press the Down key. The Soft Start Cycles [SSC] Record the [SSC] setting on
parameter screen appears. the Setup Sheet.
27 Press the Down key. The Evaporator Defrost Initiation Record the [dit] setting on the
Timer [dit] parameter screen Setup Sheet.
appears.
28 Press the Down key. The Evaporator Defrost Record the [dtt] setting on the
Termination Timer [dtt] parameter Setup Sheet.
screen appears.
29 Press the Down Key The condenser Defrost Initiation Record the [di2] setting on the
Timer [di2] parameter screen Setup Sheet.
appears.
30 Press the Down key. The condenser Defrost Record the [dt2] setting on
Termination Timer [dt2] the Setup Sheet.
parameter screen appears.
31 Press the Down key. The Evaporator Fans Constant Record the [EFc] setting on
Blow [EFc] parameter screen the Setup Sheet.
appears.
32 Press the Down key. The Out-of-Range Alarm [dAL] Record the [dAL] setting on
parameter screen appears. the Setup Sheet.
33 Press the Down key. The Compartment Selection Record the [CSE] setting on
[CSE] parameter screen appears the Setup Sheet.
(MSK544.xx only).
34 Press the Down key. The Hour Counter Initial Value Record the [HC] setting on the
[HC] parameter screen appears. Setup Sheet.
P41PA02A - 04/14 2
Service Procedure A02A
STEP ACTION RESULTS COMMENTS
35 Press the Down key. The Door Switches Record the [dSP] setting on
Present/Polarity [dSP] parameter the Setup Sheet.
screen appears.
36 Press the Down key. The Buzzer Enable [bE] Record the [bE] setting on the
parameter screen appears. Setup Sheet.
37 Press the Down key. The Thermostat Units [bu] Record the [bu] setting on the
parameter screen appears. Setup Sheet.
38 Press the Down key. The Pressure Units [Pu] Record the [Pu] setting on the
parameter screen appears. Setup Sheet.
39 Press the Down key. The display returns to the All current microprocessor
Standard Display. settings have been retrieved
and recorded.
3 P41PA02A - 04/14
Service Procedure A02A
SETUP SHEET
SOFTWARE REVISION
ACCESS KEY FUNCTION STANDARD SETTING RECORDED SETTING
Press “Up Arrow” + Display Check --- ---
“Enter” and hold for
3 seconds.
Software Revision [380 xx, 544 xx] Software Revision
appears automatically
when Display Check is
finished
HOURMETERS ACCESS
ACCESS KEY FUNCTION STANDARD SETTING RECORDED SETTING
Press and hold “Select” key Hourmeters Menu
for 3 seconds
“Select” [HC] accumulated hours
“Select” [tH] accumulated hours
“Select” [CC] accumulated hours
“Select” [EC] accumulated hours
INFORMATION MENU
ACCESS KEY FUNCTION STANDARD SETTING RECORDED SETTING
Press “Up Arrow + “Enter” Information Menu
and hold for 3 seconds
Press the “Select” key. [all icons] ---
Press the “Select” key. [380 xx, 544 xx] ---
Press the “Select” key. [134] or [404] 134 (for R-134a) or
404 (for R-404A)
Press the “Select” key. [bAt] Measured voltage (0-30V)
Press the “Select” key. [HP] Measured pressure
(0 to 500 PSIG)
Press the “Select” key. [xC / tyy] x for the number of
compartments;
yy for unit type
P41PA02A - 04/14 4
Service Procedure A02A
INSTALLATION (GUARDED ACCESS) MENU
ACCESS KEY FUNCTION STANDARD SETTING RECORDED SETTING
“Down” [dt2] 45 (for MSK 380.xx)
30 (for MSK 544.xx)
“Down” [EFc] Off
“Down” [dAL] 0
“Down” [CSE] (MSK544.XX only) 1-2
“Down” [dSP] 1 (normally open)
“Down” [HC] 150 [= 1500 hours]
“Down” [bE] 2 (enabled and when
pressed)
“Down” [tu] C (Celsius)
“Down” [Pu] P (PSI)
5 P41PA02A - 04/14
Service Procedure A02A
P41PA02A - 04/14 6
Service Procedure A04A
Microprocessor Setup (Programming the DSR Microprocessor)
Where
All units equipped with a DSR P Controller microprocessor and Revision 380 XX or 544 XX
software.
Purpose
This procedure is used to program a DSR microprocessor.
Required Tools
• A PC loaded with Wintrac software (for 380 XX software versions, the minimum Wintrac version is
4.8 and for 544 XX software versions, the minimum Wintrac version is 5.6.1) and serial port RS-232
• Configuration files (downloaded from the Thermo King Information Central Intranet site)
1 P41PA04A - 04/14
Service Procedure A04A
STEP ACTION RESULTS COMMENTS
7 Power-up the truck ignition key or
connect the DSR unit to a standby
power source. (The DSR controller
must have a source of electrical
power, in order to be programmed).
8 Run the Wintrac software program
9 At the Wintrac screen, click on the
Seek Device icon (the truck graphic)
P41PA04A - 04/14 2
Service Procedure A04A
STEP ACTION RESULTS COMMENTS
12 Click the restore button at the A Windows browser appears to
bottom of the screen. choose the unit file.
15 Close Wintrac.
16 Switch the truck ignition key to Off or
turn off power to the standby electric
power source.
3 P41PA04A - 04/14
Service Procedure A04A
STEP ACTION RESULTS COMMENTS
Saving Parameter Files
To save a file and its parameter settings, in order to upload it to other units with the identical
configuration, perform the following:
1 Set the parameter as required. See
the adjacent illustration.
P41PA04A - 04/14 4
Service Procedure A12A
ESD (Electrostatic Discharge) Procedure
Where Used:
All solid state applications.
Purpose:
To prevent ESD (electrostatic discharge) damage while working on a microprocessor. ESD (electro-
static discharge) is an invisible enemy which can only be counteracted by using good procedures.
Failure to follow stated procedures may result in electronic component failure. Additional information
may be found in the ELECTRO STATIC DISCHARGE (ESD) TRAINING GUIDE TK40282.
1 P41PA12A - 04/05
Service Procedure A12A
P41PA12A - 04/05 2
Service Procedure A26A
Welding on Units Equipped with Microprocessors
Where Used
All units equipped with DSR P Controller microprocessors.
Purpose
To prevent damage to the microprocessor during welding operations. Electric welding generates
extremely high amperage currents which can damage electrical and electronic components. In order to
minimize the possibility of damage the following procedures must be followed.
1 P41PA26A - 04/05
Service Procedure A26A
P41PA26A - 04/05 2
Service Procedure A28A
Setting Unit Running Time Hourmeters
Where used
All new replacement DSR P Controller microprocessors only.
Purpose
This procedure should be followed to set the unit running time hourmeters for [HC] (Remaining Hours
Counter).
Setting Hourmeters
NOTE: If the controller is replaced with a new one and the previous value is unknown, estimate the
number of hours the unit had been running since the last check and subtract the normal
maintenance period indicated for this type of unit (normally 1500 h). This will determine the value to
be entered as the HC parameter. This value must be changed again when entering the normal
maintenance period (normally 1500 h) at the next service check.
1 P41PA28A - 10/09
Service Procedure A28A
P41PA28A - 10/09 2
Service Procedure A46A
Updating the DSR microprocessor
Where used
All units equipped with a DSR µP Controller microprocessor and revision 380 XX or 544.xx software.
Purpose
This procedure is used to update a DSR microprocessor.
Required tools
• Configuration files (downloaded from the Thermo King Information Central ESA Intranet site)
1 P41PA46A - 04/14
Service Procedure A46A
STEP ACTION RESULT REMARKS
7 Power-up the truck ignition key or
connect the DSR unit to a standby
power source. (The DSR controller
must have a source of electrical
power, in order to be programmed).
8 Run EXE file "MSKXXX.xx" from the
computer. Click on the option to
Verify Upload.
P41PA46A - 04/14 2
Service Procedure B02A
Printed Circuit Board Removal and Replacement
Where Used
All units equipped with DSR P Controller microprocessors.
Purpose
This procedure should be followed when replacing Logic board LB1 or LB2, and power boards PB1
and/or PB2.
1 P41PB02A - 04/14
Service Procedure B02A
STEP ACTION RESULTS COMMENTS
6 For V-200 and V-300 20/50 units:
Open the ECM cover.
Remove the nut (1) that secure
the Electric Box enclosure.
P41PB02A - 04/14 2
Service Procedure B02A
STEP ACTION RESULTS COMMENTS
8 Only for V-500 and V-600 1 PH
units: Remove the two nuts (1)
that secure the condenser
enclosure to the unit. Separate
the enclosure from the unit.
3 P41PB02A - 04/14
Service Procedure B02A
STEP ACTION RESULTS COMMENTS
11 For an LB1 or LB2, remove the
plastic clip (2) and the four
screws (1) that secure PCB o the
ECM enclosure.
P41PB02A - 04/14 4
Service Procedure D01A
Return Air Temperature Sensor Test
Where Used
All DSR P Controller microprocessors and other solid state controller applications.
Purpose
This procedure is used to confirm the proper operation of Return Air Temperature sensor 1 (Sensor 1),
located in the single or main load compartment, and Return Air Temperature sensor 2 (Sensor 2),
located in the remote load compartment of multi-temp vehicles.
1 P41PD01A - 04/14
Service Procedure D01A
STEP ACTION RESULTS COMMENTS
4 Check the Standard Display for The display should show [----],
the temperature in the main or meaning that the applicable
remote load compartment. Return Air Temperature sensor
(Sensor 1 in the main load
compartment, or Sensor 2 in the
remote load compartment) is
disconnected.
5 Using a high quality digital The voltage must be between If the voltage is correct, replace
multimeter, check the voltage at 4.90 Vdc and 5.10 Vdc. the sensor.
the sensor plug, on the sensor
half of the wire that is still
connected to the printed circuit
board.
6 If the voltage measured in Step 5 The voltage must be between If the voltage is correct at Step 6,
is incorrect, check the voltage at 4.90 Vdc and 5.10 Vdc. but incorrect at Step 5, the
the sensor connector at the problem is in the wiring.
ECM, at the following connector
locations: If the voltage is incorrect at
Step 5 and Step 6, the problem
Sensor 1 = Logic board LB1/LB2
is in the microprocessor.
at connector C-1, pin A4 and pin
B4.
Sensor 2 = Logic board LB1/LB2
at connector C-1, pin A4 and pin
C3.
7 Completely disconnect the Depending on the ambient • If the resistance is OK, and
return air temperature sensor temperature, the resistance step 6 is OK, the problem is in
from the ECM. Check the should be what is indicated in the wiring.
resistance between wires PNK the Table of temperatures • If the wiring is OK, replace the
and BLK. and operating modes in Section return air temperature sensor.
3, Software Description.
P41PD01A - 04/14 2
Service Procedure F06A
3 Wire Magnetic Door Switch
Where Used
All 3-wire magnetic door switch applications
Purpose
This information is used to install and wire the 3-wire magnetic door switch.
Door Switch
Magnet
This distance to be
no more than 19 mm
IMPORTANT INFORMATION: +12 volts is connected to the red wire, and chassis ground is connected
to the black wire, to energise the door switch. When the door is closed no voltage is present on the white
DS wire to the microprocessor. When the door is open +12 volts is present on the white DS wire to
inform the microprocessor that the door is open. The magnet should be no more than 19 mm from the
door switch when the door switch is closed.
1 P41PF06A - 04/05
Service Procedure F06A
Document Control
REVISIONS
Any changes must be verified with all WHERE USED documents to insure correctness.
Date By Changes
12/12/96 CA Original
17/04/05 PAF English measurements deleted; metric only used for DSR P Controller microprocessor
application
I41PF06A - 04/05 2
Service Procedure H02A
Deutsch Connector Repair Using Pigtail
Where Used
All units equipped with DSR P Controller microprocessors.
Purpose
This procedure should be used to repair a broken pin in any of the Deutsch connectors used on the unit.
The service part numbers are shown below.
Deutsch Connectors
Male DEUTSCH pin with pigtail 44-9701
1 P41PH02A - 04/05
Service Procedure H02A
STEP ACTION RESULTS COMMENTS
6 Insert the replacement pin with
short lead into the connector
from the back of the shell.
7 Check to be sure the pin is fully
seated and locked in the shell.
8 Re-install the orange locking
wedge from the front side of the
connector shell.
9 Insert the shrink tubing over the See Figure 1.
harness wire and position it far
enough away from the joint that
it does not shrink prematurely
when soldering.
10 Carefully strip 13 mm of Trim wire lengths, as required, to
insulation from the end of the pin properly fit harness.
wire and the matching harness
See Figure 2.
wire.
11 Twist the ends of the wire See Figure 3.
together to create a compact,
mechanically strong connection.
12 Using a small soldering iron, See Figure 4.
solder the connection using rosin
core solder.
13 Position the shrink tubing over See Figure 5.
the connection.
14 Shrink the tubing in place using The connection may be
the small soldering iron. additionally insulated with
electrical tape, if necessary.
15 Reinstall the connector on the
mating connector.
16 Carefully position the harness
and replace any cable ties
removed or missing.
P41PH02A - 04/05 2
Service Procedure H02A
3 P41PH02A - 04/05
Service Procedure H02A
P41PH02A - 04/05 4
Service Procedure H04A
Checking Harness Continuity
Where Used
All DSR P Controller microprocessors and other solid state controller applications.
Purpose
To illustrate the correct procedures for checking harness continuity on equipment utilizing solid state
devices.
1 P41PH04A - 04/05
Service Procedure H04A
STEP ACTION RESULTS COMMENTS
4 Always wear a grounded wrist Failure to use a grounded wrist
strap when working on exposed strap and/or failure to observe
solid state circuits (such as other ESD (Electrostatic
changing a software IC). Discharge) procedures can
result in damage to solid state
components. This damage might
not be immediately noticeable.
See Service Procedure A12A
ESD (Electrostatic Discharge)
Procedure for additional
information on ESD procedures.
GENERAL PROCEDURES
1 Locate the suspect circuit on the
appropriate wiring diagram.
2 Isolate both ends of the circuit Harness connections might be
using the following methods, as determined by consulting the
required. wiring diagrams.
• Disconnect the appropriate CAUTION: Failure to isolate
connector at the interface
both ends might cause
module.
misleading results.
• Disconnect the device
connector at the device.
• Remove the wire from the
device terminal.
3 Using jumpers as required, The meter must show a very low Be certain the ohmmeter battery
connect each end of the circuit to resistance (less than 1.0 ohm), is good and the meter zeros with
a high quality multimeter. indicating circuit continuity. If not, the leads held together.
the circuit is open or has
excessive resistance.
Troubleshoot the circuit to
determine the cause using the
wiring diagrams.
4 After determining that the circuit The meter should indicate an
passes a continuity test, remove open circuit. If continuity is
one lead and connect it to indicated, the circuit is shorted to
chassis ground to check for a ground. Troubleshoot the circuit
short to ground. to determine the cause of the
short using the wiring diagrams.
P41PH04A - 04/05 2
Section 7
DSR III P Controller Information
DSRP Controller Software Features
and Interchange.................................... 7 - 1
THIS PAGE IS INTENTIONALLY BLANK
Section 7
7Section 7 - DSR III P Controller Information
DSR III P Controller Software Features and Interchange
To identify the software version used with your DSR III P Controller, see Checking the Software
Revision, in Section 4, Operation.
CAUTION: The software of a replacement microprocessor should always be checked, to be certain
that it is the current software revision level.
(04/14) 7-1
Section 7 - DSR III P Controller Information
(04/14) 7-2
Section 8
Schematics and Wiring Diagrams
Number Description
2E22072, Rev. B V-100, V-200, V-300 MAX 10/30 DSR III P Controller Schematic Diagram
2E21994, Rev. B V-100, V-200, V-300 MAX 10/30 DSR III P Controller Wiring Diagram
2E37652, Rev. A V-100 MAX 20/50 DSR III P Controller Schematic Diagram
2E37653, Rev. A V-100 MAX 20/50 DSR III P Controller Wiring Diagram
2E16632, Rev. B V-200, V-300 MAX 20/50 DSR III P Controller Schematic Diagram
2E16631, Rev. B V-200, V-300 MAX 20/50 DSR III P Controller Wiring Diagram
2E16811, Rev. A V-200, V-300 MAX Spectrum DSR P III Controller Schematic Diagram
2E16812, Rev. A V-200, V-300 MAX Spectrum DSR P III Controller Wiring Diagram
2E28293, Rev. C V-500, V-600 MAX 10/20/30/50, 1 Temp & Spectrum DSR III P
Controller Schematic Diagram
2E28292, Rev. C V-500, V-600 MAX 10/20/30/50, 1 Temp & Spectrum DSR III P
Controller Wiring Diagram
THIS PAGE IS INTENTIONALLY BLANK
Section 8
8Section 8 - Schematics and Wiring Diagrams
The following schematic diagrams and wiring diagrams are for V-100, V-200, V-300, V-500, and V-600
units that use the DSR III P Controller.
Diagram, Schematic
TK Part Number Description
2E22072, Rev. B V-100/V-200/V-300 MAX, 10/30, Single Temp, 12V/24V
2E37652, Rev. A V-100 MAX, 20/50, Single Temp, 1PH, 50Hz, 12V/24V
2E16632, Rev. B V-200/V-300 MAX, 20/50, Single Temp, 12V/24V
2E16811, Rev. A V-200/V-300 MAX, Spectrum, 12V/24V
2E28293, Rev. C V-500/V-600 MAX, 10/20/30/50, Single Temp and Spectrum, 1PH/3PH, 50/60Hz,
12V/24V
Diagram, Wiring
TK Part Number Description
2E21994, Rev. B V-100/V-200/V-300 MAX, 10/30, Single Temp, 12V/24V
2E27653, Rev. A V-100 MAX, 20/50, Single Temp, 1PH, 50Hz, 12V/24V
2E16631, Rev. B V-200/V-300 MAX, 20/50, Single Temp, 12V/24V
2E16812, Rev. A V-200/V-300 MAX, Spectrum, 12V/24V
2E28292, Rev. C V-500/V-600 MAX, 10/20/30/50, Single Temp and Spectrum, 1PH/3PH, 50/60Hz,
12V/24V
(04/14) 8-1
Section 8 - Schematics and Wiring Diagrams
(04/14) 8-2
2E22072 DSR III MICROPROCESSOR CONTROLLER SCHEMATIC DIAGRAM, V-100, V-200, V-300 MAX, 10/30 - Page 1 of 1
RELEASED
A 14/Feb/2013
/ / 1
8-3
2E21994 DSR III MICROPROCESSOR CONTROLLER WIRING DIAGRAM, V-100, V-200, V-300 MAX, 10/30 - Page 1 of 1
RELEASED
A 14/Feb/2013
/ / 1
8-4
2E37652 DSR III MICROPROCESSOR CONTROLLER SCHEMATIC DIAGRAM, V-100 MAX, 20/50 - PAGE 1 OF 2
8-5
2E37652 DSR III MICROPROCESSOR CONTROLLER SCHEMATIC DIAGRAM, V-100 MAX, 20/50 - PAGE 2 OF 2
8-6
2E37653 DSR III MICROPROCESSOR CONTROLLER WIRING DIAGRAM, V-100 MAX, 20/50 - PAGE 1 OF 3
8-7
2E37653 DSR III MICROPROCESSOR CONTROLLER WIRING DIAGRAM, V-100 MAX, 20/50 - PAGE 2 OF 3
8-8
2E37653 DSR III MICROPROCESSOR CONTROLLER WIRING DIAGRAM, V-100 MAX, 20/50 - PAGE 3 OF 3
8-9
2E16632 DSR III MICROPROCESSOR CONTROLLER SCHEMATIC DIAGRAM, V-200, V-300 MAX, 20/50 - PAGE 1 OF 3
RELEASED 19/Feb/2014
/ /
8-10
2E16632 DSR III MICROPROCESSOR CONTROLLER SCHEMATIC DIAGRAM, V-200, V-300 MAX, 20/50 - PAGE 2 OF 3
RELEASED
R E 19/Feb/2014
e
8-11
2E16632 DSR III MICROPROCESSOR CONTROLLER SCHEMATIC DIAGRAM, V-200, V-300 MAX, 20/50 - PAGE 3 OF 3
RELEASED
R D 19/Feb/2014
b
8-12
2E16631 DSR III MICROPROCESSOR CONTROLLER WIRING DIAGRAM, V-200, V-300 MAX, 20/50 - PAGE 1 OF 4
8-13
2E16631 DSR III MICROPROCESSOR CONTROLLER WIRING DIAGRAM, V-200, V-300 MAX, 20/50 - PAGE 2 OF 4
12V
24V
8-14
2E16631DSR III MICROPROCESSOR CONTROLLER WIRING DIAGRAM, V-200, V-300 MAX, 20/50 - PAGE 3 OF 4
1PH
50Hz & 60Hz
12V
24V
8-15
2E16631DSR III MICROPROCESSOR CONTROLLER WIRING DIAGRAM, V-200, V-300 MAX, 20/50 - PAGE 4 OF 4
12V
24V
8-16
2E16811 DSR III MICROPROCESSOR CONTROLLER SCHEMATIC DIAGRAM, V-200, V-300 MAX, MULTI-TEMP - PAGE 1 OF 1
RELEASED 14/Feb/2013
8-17
2E16812 DSR III MICROPROCESSOR CONTROLLER WIRING DIAGRAM, V-200, V-300 MAX, MULTI-TEMP - PAGE 1 OF 1
RELEASED 14/Feb/2013
8-18
2E28293 DSR III MICROPROCESSOR CONTROLLER SCHEMATIC DIAGRAM, V-500, V-600 MAX, 10/20/30/50, 1 TEMP & SPECTRUM - PAGE 1 OF 5
RELEASED
A 10/Dec/2013
/ 1
8-19
2E28293 DSR III MICROPROCESSOR CONTROLLER SCHEMATIC DIAGRAM, V-500, V-600 MAX, 10/20/30/50, 1 TEMP & SPECTRUM - PAGE 2 OF 5
RELEASED
A 10/Dec/2013
/ 1
8-20
2E28293 DSR III MICROPROCESSOR CONTROLLER SCHEMATIC DIAGRAM, V-500, V-600 MAX, 10/20/30/50, 1 TEMP & SPECTRUM - PAGE 3 OF 5
1 PH
3 PH 5 0 H Z /6 0 H Z
RELEASED 10/Dec/2013
12V
24V
8-21
2E28293 DSR III MICROPROCESSOR CONTROLLER SCHEMATIC DIAGRAM, V-500, V-600 MAX, 10/20/30/50, 1 TEMP & SPECTRUM - PAGE 4 OF 5
RELEASED 10/Dec/2013
230 / 3 / 60
8-22
2E28293 DSR III MICROPROCESSOR CONTROLLER SCHEMATIC DIAGRAM, V-500, V-600 MAX, 10/20/30/50, 1 TEMP & SPECTRUM - PAGE 5 OF 5
RELEASED
A 10/Dec/2013
/ 1
8-23
12E28292 DSR III MICROPROCESSOR CONTROLLER WIRING DIAGRAM, V-500, V-600 MAX, 10/20/30/50, 1 TEMP & SPECTRUM - PAGE 1 OF 6
RELEASED
REL A D 10/Dec/2013
/ c/ 1
8-24
12E28292 DSR III MICROPROCESSOR CONTROLLER WIRING DIAGRAM, V-500, V-600 MAX, 10/20/30/50, 1 TEMP & SPECTRUM - PAGE 2 OF 6
RELEASED
REL A D 10/Dec/2013
/ c/ 1
8-25
12E28292 DSR III MICROPROCESSOR CONTROLLER WIRING DIAGRAM, V-500, V-600 MAX, 10/20/30/50, 1 TEMP & SPECTRUM - PAGE 3 OF 6
RELEASED
REL A D 10/Dec/2013
/ c/ 1
3 PH
12V
24V
8-26
12E28292 DSR III MICROPROCESSOR CONTROLLER WIRING DIAGRAM, V-500, V-600 MAX, 10/20/30/50, 1 TEMP & SPECTRUM - PAGE 4 OF 6
RELEASED
REL A D 10/Dec/2013
/ c/ 1
1 PH
12V
24V
8-27
12E28292 DSR III MICROPROCESSOR CONTROLLER WIRING DIAGRAM, V-500, V-600 MAX, 10/20/30/50, 1 TEMP & SPECTRUM - PAGE 5 OF 6
RELEASED
REL A D 10/Dec/2013
/ c/ 1
2 3 0 V / 3 PH / 6 0 H z
12V
24V
8-28
12E28292 DSR III MICROPROCESSOR CONTROLLER WIRING DIAGRAM, V-500, V-600 MAX, 10/20/30/50, 1 TEMP & SPECTRUM - PAGE 6 OF 6
RELEASED
REL A D 10/Dec/2013
/ c/ 1
8-29
8-30
Changes and Comments
You are invited to comment on this manual so it can be updated and improved to better meet your
needs. Any corrections or comments are welcome. Please complete the following information:
Name: _______________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
Thermo King,
Attention of Technical Service
For European Area, Department,
Return This Form To: Monivea Road,
Galway, Ireland
Fax: +353 91 703380
THIS PAGE INTENTIONALLY LEFT BLANK