FD 70 Caq410594
FD 70 Caq410594
FD 70 Caq410594
FD 70
CAQ410594
Instruction book
Atlas Copco
FD 70
CAQ410594
Instruction book
Original instructions
Copyright notice
Any unauthorized use or copying of the contents or any part thereof is prohibited.
This applies in particular to trademarks, model denominations, part numbers and
drawings.
This instruction book is valid for CE as well as non-CE labelled machines. It meets the
requirements for instructions specified by the applicable European directives as
identified in the Declaration of Conformity.
2016 - 03
www.atlascopco.com
Instruction book
Table of contents
1 Safety precautions..........................................................................................................4
2 General description........................................................................................................ 9
2.1 INTRODUCTION...................................................................................................................................9
3 Elektronikon® α regulator............................................................................................17
2 CAQ410594
Instruction book
4 Installation.....................................................................................................................25
4.4 PICTOGRAPHS................................................................................................................................. 31
5 Operating instructions................................................................................................. 32
5.1 WARNINGS......................................................................................................................................32
5.2 STARTING....................................................................................................................................... 32
5.4 STOPPING.......................................................................................................................................33
6 Maintenance instructions............................................................................................ 35
7 Device settings............................................................................................................. 36
8 Problem solving............................................................................................................37
9 Technical data...............................................................................................................39
11 Declaration of conformity............................................................................................ 42
CAQ410594 3
Instruction book
1 Safety precautions
Explanation
Danger to life
Warning
Important note
General precautions
All responsibility for any damage or injury resulting from neglecting these precautions, or
non-observance of the normal caution and care required for installation, operation,
maintenance and repair, even if not expressly stated, will be disclaimed by the
manufacturer.
4 CAQ410594
Instruction book
CAQ410594 5
Instruction book
Also consult following safety precautions: Safety precautions during operation and Safety
precautions during maintenance or repair.
These precautions apply to machinery processing or consuming air or inert gas. Processing
of any other gas requires additional safety precautions typical to the application which are
not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.
6 CAQ410594
Instruction book
Also consult following safety precautions: Safety precautions during installation and Safety
precautions during maintenance or repair.
These precautions apply to machinery processing or consuming air or inert gas. Processing
of any other gas requires additional safety precautions typical to the application which are
not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.
CAQ410594 7
Instruction book
flush abundantly with fresh water over the clothing until all refrigerant is flushed away; then
seek medical first aid.
21. The following safety precautions are stressed when handling desiccant:
• Take precautions not to inhale desiccant dust.
• Check that the working area is adequately ventilated; if required, use breathing protection.
• Do not overfill the dryer when replacing desiccant.
Also consult following safety precautions: Safety precautions during installation and Safety
precautions during operation.
These precautions apply to machinery processing or consuming air or inert gas. Processing
of any other gas requires additional safety precautions typical to the application which are
not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.
8 CAQ410594
Instruction book
2 General description
2.1 Introduction
Introduction
FD air dryers remove moisture from compressed air by cooling the air to near freezing point. This causes
water to condense. The condensate is automatically drained. The dried air is warmed up before leaving the
dryer.
The dryers can be provided with the options as described in section Available options.
General view
AI Air inlet
AO Air outlet
E Elektronikon® α controller
1 Supply cable entrance
2 Condensate drain
3 Manual drain valve
CAQ410594 9
Instruction book
Detail views
FD 60 up to FD 95
Reference Name
1 Insulating block with heat exchangers
2 Electronic condensate drain
3 Pressure switch, fan control
4 Condenser
5 Condenser cooling fan
6 Refrigerant compressor
7 Hot gas bypass valve
8 Refrigerant filter / dryer
9 Capillary
10 Manual condensate drain outlet
11 Automatic drain outlet
10 CAQ410594
Instruction book
Flow diagram - FD 60 up to FD 95
1 Heat exchanger
2 Evaporator
3 Water separator
4 Refrigerant compressor
5 Hot gas bypass valve
6 Condenser
7 Refrigerant dryer/filter
8 Capillary
9 Electronic condensate drain
10 Liquid separator
11 Cooling fan
Dm Manual drain valve
Description
Compressed air enters heat exchanger (1) and is cooled by the outgoing, cold, dried air. Water in the
incoming air starts to condense. The air then flows through heat exchanger/evaporator (2) where the
refrigerant evaporates, causing the air to be cooled further to close to the evaporating temperature of the
refrigerant. More water in the air condenses. The cold air then flows through the water separator (3) where
all the condensate is separated from the air.
The condensate is automatically drained by electronic condensate drain (9).
The cold, dried air flows through heat exchanger (1) where it is warmed up by the incoming air to
approximately 10 ˚C (18 ˚F) below the incoming air temperature.
Condensation in the air net cannot occur unless the air is cooled to below the pressure dew point, indicated
on the screen of the Elektronikon ® α regulator.
CAQ410594 11
Instruction book
Flow diagram - FD 60 up to FD 95
1 Heat exchanger
2 Evaporator
3 Water separator
4 Refrigerant compressor
5 Hot gas bypass valve
6 Condenser
7 Refrigerant dryer/filter
8 Capillary
9 Electronic condensate drain
10 Liquid separator
11 Cooling fan
Dm Manual drain valve
Description
Compressor (4) delivers hot, high-pressure refrigerant gas which flows through condenser (6) where most
of the refrigerant condenses.
The liquid refrigerant flows via the dryer/filter (7) to the capillary tube (8) and leaves the capillary tube at
evaporating pressure.
The refrigerant enters evaporator (2) where it withdraws heat from the compressed air by further
evaporation at constant pressure. The heated refrigerant leaves the evaporator and is sucked in by the
compressor. Before the compressor there is a liquid separator (10) which protects the compressor against
liquid knock.
12 CAQ410594
Instruction book
Flow diagram - FD 60 up to FD 95
1 Heat exchanger
2 Evaporator
3 Water separator
4 Refrigerant compressor
5 Hot gas bypass valve
6 Condenser
7 Refrigerant dryer/filter
8 Capillary
9 Electronic condensate drain
10 Liquid separator
11 Cooling fan
Dm Manual drain valve
Description
The condenser (6) pressure must be kept as constant as possible to obtain stable operation. Fan control
switch (P) therefore stops and starts the condenser cooling fan (11).
If, under partial or no load, the evaporator pressure drops to 2.25 bar(e) (32.63 psig), the hot gas bypass
valve opens and hot, high-pressure gas is fed to the evaporator circuit to prevent the evaporator pressure
from dropping any further.
CAQ410594 13
Instruction book
1 Drain outlet
2 Test button
3 Manual drain valve
The dryers are equipped with an electronic condensate drain. The condensate from the condensate trap
accumulates in a collector. When the condensate reaches a predefined level, it is discharged through the
drain outlet (1).
The condensate can also be drained by pressing the test button (2).
The drain filter can be cleaned by opening the manual drain valve, see section Maintenance instructions.
Filter option
On FD 60 up to FD 95, this option comprises a DD filter, mounted at the dryer inlet and a PD filter,
mounted at the dryer outlet. Both filters are integrated in the dryer volume. Both filters are equipped with a
14 CAQ410594
Instruction book
pressure drop indicator, which is visible through the top panel grating. Dryer inlet and outlet connections
are on top of the unit allowing easy installation against the wall.
Reference Description
1 DD filter at dryer inlet
2 PD filter at dryer outlet
3 Pressure drop indicator
CAQ410594 15
Instruction book
and to collect the oil in a collector. The condensate drained through OSD meets the requirements of the
environmental codes (oil content <10 mg/l).
Description
FD dryers are single phase devices. See Electrical diagrams.
Fan control switch (P) starts fan motor (M2) as soon as the condenser pressure reaches the upper set point
of the switch and will stop the fan motor when the condenser pressure decreases to its lower set point.
The refrigerant compressor motor has a built-in protection. If the compressor motor stops without apparent
reason, it will probably be the thermal protection which has tripped. In such a case, the compressor will
restart when the motor windings have cooled down, which may take up to 2 hours.
16 CAQ410594
Instruction book
3 Elektronikon® α regulator
Control panel
Control panel
General description
The Elektronikon® α regulator automatically controls the dryer, i.e.:
• It switches the dryer on and off in order to save energy (Energy Efficient Mode).
• It monitors the dew point temperature to ensure safe operation.
• It switches the dryer off in case of risk for freezing.
• It controls an alarm to notify a high relative humidity.
In order to control the dryer and to read and modify programmable parameters, the regulator has a control
panel provided with:
• 4 pictographs to indicate what is shown on the display
• 2 alarm pictographs that become alight when critical values are reached
• 2 keys to go through the menu of the regulator
• A key to enter a menu or to validate values
• A button to manually start and stop the dryer
CAQ410594 17
Instruction book
Control panel
Procedure
When the voltage is switched on, the text “www.atlascopco.com” is rolling on the display (2).
When pushing the ON/OFF button (1), the dryer starts and the display of the Elektronikon® α regulator
becomes active, see next section.
When an external power failure occurs, the dryer will automatically return to its original
working condition, i.e. the condition from before the power failure.
18 CAQ410594
Instruction book
Main screen
The display shows the dew point temperature and the dryer status.
The dryer status is indicated by means of pictographs underneath the display.
Typical screen example:
3 °C
Explanation:
• The dew point is 3 °C (37.4 °F).
• The Energy Efficient Mode is active. See section Modifying dryer regulation mode to change.
The display can also show all measured and programmed parameters, see section Scrolling through all
screens.
CAQ410594 19
Instruction book
Reference Designation
1 Pictograph for dew point temperature
2 Pictograph for ambient temperature
3 Pictograph for relative humidity
4 Pictograph for indication of regular operation mode or energy efficient mode
When selecting one of the first three items, the corresponding actual value is shown on the display.
When selecting the fourth item, the regulation mode of the regulator is shown on the display. ON means
that the dryer is working in an Energy Efficient Mode, OFF means that Energy Efficient Mode is not
selected and dryer is working in Regular Mode. See section Modifying the dryer regulation mode to
change.
Examples of typical conditions:
1. The third pictograph is selected. The relative humidity is shown on the display (26%). The Energy
Efficient Mode is not activated.
26 %
2. The fourth pictograph is selected. The word “ON“ in the display means that the dryer is working in
Energy Efficient Mode.
ON
-1 °C
Result:
• The dew point temperature value will flash on the display.
• The freezing alarm indicator pictograph will light up.
• The dryer will switch off.
• The voltage free contact will switch (can be used as an external alarm).
The dryer will restart automatically as soon as the dew point (LAT) is again above 0.3 °C (32.54 °F).
2. High relative humidity alarm indicator
When a relative humidity value of more than 50 % (for a dew point temperature above 10 °C (50 °F))
is measured during more than one minute, typically following information will appear:
20 CAQ410594
Instruction book
56 %
Result:
• The relative humidity value will flash on the display.
• The high relative humidity alarm indicator pictograph will light up.
• The voltage free contact will switch (can be used for an external alarm).
Alarm reset:
Control panel
After an alarm situation, the regulator can be reset by pushing the left (9) and right scroll key (11)
simultaneously.
Description
The standard relative humidity calculation is based on the measured dew point (LAT) and the ambient
temperature. The air temperature at the outlet of the dryer can however exceed the ambient temperature
with a number of degrees. This has a positive impact on the real relative humidity of the air. To take this
into account, a positive offset can be added to the ambient temperature.
Tdryer outlet = Tambient + Toffset
CAQ410594 21
Instruction book
Remark: The calculation used for the high relative humidity alarm indicator (see section Scrolling through
all screens) is independent of this offset value and is always based on ambient temperature, which is the
most severe condition.
The standard offset value is 0 °C (0 °F).
Description
The dryer has two regulation modes:
• Regular Mode:
The dryer regulates to a fixed dew point
• Energy Efficient Mode:
The dryer regulates the dew point between the best achievable dew point and a safe dew point.
Control panel
22 CAQ410594
Instruction book
When selecting the Regular/Energy Efficient Mode item (see section Scrolling through all screens), the
dryer regulation mode can be changed as follows:
• Press the Enter key (10) once.
• Press the left scroll key (9) or the right scroll key (11) to choose between ‘ON’ and ‘OFF’.
• Press the Enter key (10) again to confirm the selection.
Activation and deactivation of the remote start/stop function is done by pressing the right scroll key (11)
and the Enter key (10) simultaneously.
Activation: press keys 10 and 11 simultaneously. The text REMOTE is displayed during a short time.
Deactivation: press keys 10 and 11 simultaneously. The text LOCAL is displayed during a short time.
CAQ410594 23
Instruction book
Factory setting is local start/stop. If the remote start/stop function is activated and a voltage failure occurs,
the setting will remain REMOTE when the voltage returns if the ARAVF function (see previous chapter) is
active. The dryer will start automatically when the voltage is on again.
If the remote start/stop function is activated but the ARAVF function is not active, the setting will change
into LOCAL when the voltage returns. The dryer will not start automatically when the voltage is on again.
Error messages
In case of an error of the temperature sensors, one or two pictographs may start flickering:
1. If the dew point temperature pictograph is blinking, the dew point temperature sensor is missing or
not well connected (loose contact):
2. If the ambient temperature pictograph is blinking, the ambient temperature sensor is missing or not
well connected (loose contact):
24 CAQ410594
Instruction book
4 Installation
FD 60 up to FD 95
CAQ410594 25
Instruction book
26 CAQ410594
Instruction book
FD 60 up to FD 95
CAQ410594 27
Instruction book
Instructions Description
1 It is recommended to install bypass pipes over the dryer with ball valves to isolate
the dryer during service operations without disturbing the compressed air delivery.
2 Ventilation:
The inlet grid(s) and ventilation fan should be installed in such way that any
recirculation of the cooling air to the inlet gratings of the dryer is avoided.
The air velocity to the grid(s) must to be limited to 5 m/s.
Maximum allowable pressure drop over the cooling air ducts is 30 Pa (0.12 in WC).
If 30 Pa is exceeded, a ventilation fan is required at the outlet of the cooling air
ducts.
3 Install the dryer on a level floor, suitable for taking the weight of the dryer.
4 Filter type DD for general purpose filtration at the inlet of the dryer (particle removal
down to 1 micron with a maximum of oil carry-over of 0.5 ppm) and high efficiency
PD filter at the dryer outlet (particle removal down to 0.01 micron, maximum of oil
carry-over 0.01 ppm).
If applicable, a QD active carbon filter can be installed downstream of the PD filter
to remove undesired oil vapours and odours.
The standard dryers FD 40 up to FD 95 are supplied without filters.
5 Power supply cable to be sized and installed by a qualified electrician. Fuses: see
section Fuse values.
6 The condensate drain pipes from the dryer to the collection point must not become
submerged in the collected condensate.
If the condensate contains oil, do not allow untreated condensate to enter the
sewer.
7 As an option an integrated OSD can be added to separate the oil from the water
that is coming from the drain of the dryer.
The standard dryers FD 60 up to FD 95 are delivered without OSD.
• All pipes to be installed stressless to the dryer. Do not use the dryer as
support for external pipes.
• Avoid installation of the dryer in corrosive atmosphere.
• The dryer is not designed for outdoor use.
Service diagrams
Reference Description
MTR1 Compressor motor
F1 Compressor overload
F2 Fan overload
28 CAQ410594
Instruction book
Reference Description
C1 Compressor run capacitor
C2 Compressor start capacitor
C3 Fan run capacitor
KM1 Relay
MTR2 Fan motor (condenser)
PS1 Pressure switch condenser fan
CT Compressor terminal
RT Relay terminal KM1
B1 Electronic water drain
CAQ410594 29
Instruction book
Text Description
(1) Customer's installation
(2) Installation client
(3) Compressor connection
(4) Compressor
(5) Fan switch
(6) Fan
(7) Fan connection
(8) Drain
(9) Supply + drain connection
(10) Supply
Name Reference
KM1 Current relay
MTR2 Fan motor (condenser)
PS1 Pressure switch condenser fan
CT Compressor terminal
RT Relay terminal KM1
B1 Electronic water drain
TT90 Temperature sensor 'dew point'
TT01 Temperature sensor 'ambient'
MTR1 Compressor motor
F1 Compressor overload
F2 Fan overload
C2 Compressor start capacitor
C3 Fan run capacitor
30 CAQ410594
Instruction book
4.4 Pictographs
Pictographs
Reference Description
1 Dryer outlet
2 Dryer inlet
3 Automatic condensate drain
4 Warning, voltage
5 Warning: switch off the voltage, depressurise the compressor and read the
instruction book before carrying out maintenance work
Reference Name
20 Status indication of dust/oil filters
CAQ410594 31
Instruction book
5 Operating instructions
5.1 Warnings
Safety precautions
The operator must apply all relevant safety precautions, including those mentioned in this manual.
Altitude operation
Consult your supplier if operating above 3000 m (9843 ft).
5.2 Starting
Control panel
Control panel
Procedure
Step Action
1 If installed, close the dryer bypass valve.
2 Press the ON/OFF button (1) on the control panel.
3 Open the dryer air inlet valve (customer's installation).
4 Approx. 5 minutes later, open the dryer air outlet valve (customer's installation).
5 Approx. 10 minutes later, the nominal dew point will be reached.
Attention
Avoid using the ON/OFF button repeatedly within a short time period, as this could
cause the thermal protection of the compressor motor to trip.
32 CAQ410594
Instruction book
Procedure
Regularly check:
• The pressure dew point on the control panel of the Elektronikon® α regulator. The pressure dew point
will deviate from nominal if the air inlet conditions or volume flow differ from nominal.
• That condensate is discharged via condensate outlet (2). The amount of discharged condensate
depends on the operating conditions.
5.4 Stopping
Control panel
Control panel
CAQ410594 33
Instruction book
Procedure
Step Action
1 Close the dryer inlet and outlet valves (customer's installation).
2 Press the ON/OFF button (1) on the control panel.
Attention
Avoid using the ON/OFF button repeatedly within a short time period, as this could
cause the thermal overload protection of the compressor motor to trip.
34 CAQ410594
Instruction book
6 Maintenance instructions
Attention
The dryers described in this manual contain HFC based refrigerant.
Safety precautions
When handling refrigerant, all applicable safety precautions must be observed. Please be aware of
the following points:
• Contact of refrigerant with the skin will cause freezing. Special gloves must be worn. If contacted
with the skin, the skin should be rinsed with water. On no account may clothing be removed.
• Fluid refrigerant will also cause freezing of the eyes; safety glasses must hence be worn.
• Refrigerant is harmful. Do not inhale refrigerant vapors. Check that the working area is adequately
ventilated.
When removing bodywork panels, be aware that internal elements such as the pipes can become hot.
Therefore, wait until the dryer has cooled down before removing the panels.
Before starting any maintenance or repair work, switch off the voltage and close the air inlet and outlet
valves.
Local legislation
Local legislation may stipulate that:
• Work on the refrigerant circuit of the cooling dryer or on any equipment which influences its function
must be undertaken by an authorized control body.
• The installation should be checked once a year by an authorized control body.
General
For references see Introduction .
The following remarks should be kept in mind:
• Keep the dryer clean.
• Brush or blow off the finned surface of condenser regularly.
• Inspect and clean the electronic condensate drain weekly.
• Functioning of the drain can be checked by pushing the TEST button of the drain, consult
section Condensate drain system.
• Cleaning of the drain filter can be done by opening the manual drain valve during a few
seconds. Hold a towel against the drain outlet when opening.
• Apply the drain wear kit once per year (see Spare Parts list for part number).
Note: these maintenance intervals are intended for well ventilated, not dusty and not high humidity
environments. For particularly high humidity ambient conditions, the intervals should be halved.
CAQ410594 35
Instruction book
7 Device settings
36 CAQ410594
Instruction book
8 Problem solving
Precautions
Apply all relevant safety precautions. See section Safety precautions. Consult also section
Maintenance instructions.
Use only genuine parts. Any damage or malfunction caused by the use of unauthorized
parts is not covered by Warranty or Product Liability.
CAQ410594 37
Instruction book
38 CAQ410594
Instruction book
9 Technical data
Frequency Voltage FD 70
IEC
50 Hz 230 V 20 A
Reference conditions
50 Hz
Compressed air inlet pressure (13 bar versions) bar(e) 7
Compressed air inlet temperature ˚C 35
Ambient temperature ˚C 25
Dew point ˚C 3
Cooling air inlet temperature ˚C 25
Limitations
Standard version
All data are stated under nominal conditions, see section Reference conditions and limitations .
CAQ410594 39
Instruction book
40 CAQ410594
Instruction book
CAQ410594 41
Instruction book
11 Declaration of conformity
42 CAQ410594
Instruction book
On the Declaration of Conformity / Declaration by the Manufacturer, the harmonized and/or other
standards that have been used for the design are shown and/or referred to.
The Declaration of Conformity / Declaration by the Manufacturer is part of the documentation that is
supplied with this device.
CAQ410594 43
In order to be First in Mind—First in Choice® for all your quality
compressed air needs, Atlas Copco delivers the products and
services that help to increase your business’ efficiency and
profitability.
Atlas Copco's pursuit of innovation never ceases, driven by our
need for reliability and efficiency. Always working with you, we
are committed to providing you the customized quality air
solution that is the driving force behind your business.
www.atlascopco.com