Remote Terminal Units - Data sheet

Analog input 560AIR01


RTU560 product line

Analog input, 8 channels


• AD converter resolution: 16 bit
• Measuring ranges: +/-2 mA; +/-5 mA; +/-10
mA; +/-20 mA; +/-40 mA; +/-2 V DC; +/-20 V
DC

Application communication unit. The module transmits relevant


The 560AIR01 is a module of the RTU560 product line changes as event via the RTU I/O bus.
and records up to 8 analog measured values.
The 8 differential inputs are galvanically connected to the
The module 560AIR01 is able to process the following power supply.
types of signals:
• Analog measured values (AMI) Single-ended or differential input values are resolved by
• Measured floating point information (MFI) up to 4096 steps (12 bit plus sign) for 100 % measurement
amplitude.
Following measurement ranges can be configured:
• ± 2 mA
The differential inputs are protected against static and
• ± 5 mA dynamic over-voltages by a protection circuit. A low-pass
• ± 10 mA filter suppresses unwanted frequency components.
• ± 20 mA
• ± 40 mA The internal high resolution of the AD converter allows to
• ± 2 V DC scan all measuring ranges with the same resolution. An
• ± 20 V DC additional measurement channel is used for automatic
Other input ranges and live zero values are generated zero calibration. This compensates the longterm drift of
from these values by conversion on the communication the components.
unit (CMU).
For elimination of tolerances a calibration is done during
production.
Characteristics
Measuring range and line frequency are easily to
configure by the RTUtil500 configuration tool. The
Analog inputs synchronization of the scan cycle with the line frequency
is used to increase the line frequency interference
Basic signal checks and cyclic processing functions
suppression of the DC input signal.
are already be done locally in order to unburden the
Frequency Conversion time Scan cycle time
per channel (same for all
channels)
60 Hz 54 ms 486 ms
50 Hz 54 ms 486 ms
16.7 Hz 155 ms 1395 ms

Power supply input


The required power for the module is supplied via the
RTU560 backplane.

I/O controller (IOC)


The micro-controller (MPU) on the module processes all
time critical I/O tasks of the parameterized processing
functions. Moreover it carries out the interactive
communication with theI/O bus. All configuration data and
processing parameters are loaded by the communication
unit via the RTU560 I/O bus.

The module is equipped with a serial interface to the


RTU560 I/O bus on the backplane.

The analog input unit can execute the following processing


functions on the measured values:
• Scan cycle and line frequency interference
suppression
• Zero value supervision and switching detection
• Smoothing
• Threshold value monitoring on absolute value or with
accumulation
• Periodic transmission and background cycles
The module provides a data buffer for temporally storing
of up to 50 event messages including time stamps. The
events are stored in chronological order designated for
transmission to the communication unit (CMU).

During initialization and operation the module carries


out a number of tests. If a fault occurs it is reported to
the communication unit. All fault conditions impairing the
function of the module are displayed as common fault
signal by a red LED. A failure of the connected module(s)
is detected and signalized by the communication unit.
Technical data Mechanical layout
In addition to the RTU500 series general technical data,
Dimensions 160 mm x 100 mm, 3HE
the following applies: euro card format
4R (20 mm) front panel
Housing type Printed circuit board
Analog input channels 560AIR01
Mounting for mounting in RTU560
Inputs 8 differential inputs
racks
Configurable measuring • ± 2 mA
Weight 0.3 kg
range • ± 5 mA
• ± 10 mA
• ± 20 mA Connection type
• ± 40 mA
RTU560 backplane 48 pole type F DIN 41612
• ± 2 V DC
connector
• ± 20 V DC
Input impedance 150 Ω @ ±2 mA and 5 mA
Immunity test
50 Ω @ ±10 to ±40 mA
Electrostatic discharge 8 kV air / 6 kV contact (level
110 kΩ @ ±2 and ±20 V DC IEC 61000-4-2 3)
Max. load 80 mA continuous @ ±10 to Performance criteria A
±40 mA
Electrical fast transient / 2 kV (level 3)
40 mA continuous @ ±2 and Burst
±5 mA IEC 61000-4-4 Performance criteria A
Surge 2 kV (level 3)
38 V/ 0.5 mA @ ±2 and ±20 IEC 61000-4-5
V DC Performance criteria A
Resolution 12 bit + sign

11 bit + sign @ ±2 V DC Environmental conditions - climatic


AD converter resolution 16 bit Operating temperature -25 °C ... 70 °C
Accuracy at 25 °C ≤ 0.1 % EN 60068-2-14
Start up -40 °C
≤ 0.2 % @ ±2 V DC EN 60068-2-1
Linearity error at 25 °C ≤ 0.1 % Max. operating temperature, +85 °C
Temperature drift ≤ 100 ppm/K (0... 70 °C) max. 96h
Max. common mode input ±150 V DC (electrical limit) EN 60068-2-2
voltage Relative humidity 5 ... 95 %
±8 V DC (functional limit) EN 60068-2-30 (non condensing)
Max. differential input ± 4 V DC (current input)
voltage
± 38 V DC (voltage input) Ordering information
Common mode rejection > 70 dB @ 25 °C 560AIR01 R0001 1KGT036500R0001

> 60 dB @ 0… 25 °C
Configurable line frequency • 16.7 Hz
fN • 50 Hz
• 60 Hz
Line frequency interference > 100 dB @ fN ±2 %
suppression
> 45 dB @ fN ±10 %

Current consumption for power supplied via RTU560


backplane
5 V DC 75 mA
24 V DC --

Signaling by LEDs
ERR (red) Common fault information
for the module
Hitachi Power Grids Germany AG We reserve the right to make technical We reserve all rights in this document and in the ABB is a registered trademark of ABB
changes or modify the contents of this subject matter and illustrations contained therein. Asea Brown Boveri Ltd. Manufactured by/
1KGT 150 929 V007 1

P.O. Box 42 01 30 document without prior notice. With regard Any reproduction, disclosure to third parties or for a Hitachi Power Grids company.
68280 Mannheim, Germany to purchase orders, the agreed particulars utilization of its contents – in whole or in parts – is
shall prevail. Hitachi ABB Power Grids does forbidden without prior written consent of Hitachi
not accept any responsibility whatsoever ABB Power Grids.
for potential errors or possible lack of © 2024 Hitachi Power Grids
hitachienergy.com/rtu information in this document. All rights reserved

You might also like