Intentional Islanding Operations of Distributed Generation Systems With A Load Shedding Algorithm
Intentional Islanding Operations of Distributed Generation Systems With A Load Shedding Algorithm
Intentional Islanding Operations of Distributed Generation Systems With A Load Shedding Algorithm
Abstract—Intentional islanding is a condition in which a To implement a successful intentional island, the system
distributed generation source continues to supply power to the local should detect the islanding event, as soon as the grid gets
loads during a catastrophic utility failure. With a properly co- disconnected. An efficient islanding detection algorithm is
ordinated and sophisticated control scheme, islanding can be a needed for this task. Several islanding detection methods are
possible solution, to ensure reliable power to the critical loads. This
proposed in the literature. These can be broadly classified as
paper analyzes a control scheme for intentional islanding operation
of an inverter based DG system. In grid connected mode, the local methods and remote methods. Remote methods are based
interface control is designed to provide constant active and reactive on the communication between local DG and the utility grid
power to the load. When grid is disconnected, an islanding whereas local methods rely on monitoring parameters like
detection algorithm will transfer the inverter into voltage control voltage and frequency at the DG site [5]-[6].
mode. The mismatch between load and generation is removed by Many works have been reported in the literature regarding
implementing a load shedding algorithm. This paper also the interface and control of the DG systems in grid connected
investigates the performance and the Non Detection Zones of the and islanding modes. In [7], two control algorithms are
islanding detection scheme with different interface controllers. proposed for grid connected and islanded operation, with an
Key words—Distributed generation (DG), Grid connected intelligent load shedding algorithm and an algorithm for
mode, Islanded mode, Anti islanding methods, Non Detection Zone synchronization. In [8], the effect of different interface control
(NDZ), Point of Common Coupling (PCC) on islanding detection is analyzed. Reference [9] proposes a
control strategy based on voltage controlled voltage source
I. INTRODUCTION converter which inherently provide an islanding detection
The gap between the generation and demand of the power method with negligible NDZ.
provided by conventional sources of power is fast increasing. This paper presents a control strategy for grid connected as
This is due to inadequate transmission capacity and the non well as islanding modes of operation. Initially the DG system
uniform allocation of load and generating centers. The need of operates in a current controlled mode to provide the required
the hour is to tap the potential of distributed generation to power to the load. When the grid gets disconnected, a simple
meet the increasing power demand. However, many problems passive detection algorithm transfers the system to voltage
arise due to the change in power grid paradigm from the control mode. A priority based load shedding scheme, based
conventional centralized power stations to the deregulated on the measurement of the voltage at PCC, is used to
structure [1]. One of the major concerns in this regard is neutralize the load generation mismatch.
islanding. Islanding is a condition in which a part of The paper is organized as follows. Section II introduces a
study system and systematically explains the modeling of the
distribution network is supplied by a DG, even when the main
control scheme for grid connected and islanding modes.
grid is disconnected from the system [2]. The island will
Section III explains the islanding detection algorithm and the
remain operational for a long time, if the DG alone can meet analytical explanation for the NDZ. Section IV presents the
the local load demand. This may interfere with the recloser load shedding algorithm. Section V analyzes the performance
system, protection co-ordination and can even lead to hazards. of the system by conducting time domain simulations in
In spite of the fact that the likelihood of the islanding is very MATLAB/SIMULINK. Section VI concludes the paper.
less, because of the above mentioned problems, current
standards require disconnection of the DG system from the
grid when islanding is detected [3]. Also controlled islanding II. STUDY SYSTEM
can improve the reliability of the power system considerably. Fig.1 shows the single line diagram of the system under
Moreover in a system with high DG penetration, the study. The system consists of a DG represented by a dc source
disconnection can create several power quality problems. interfaced to the grid through a voltage source inverter, LC
Hence in order to maximize the benefits from DG, it is filter and a breaker. L and C represent the inductance and
advisable to go for intentional islanding. IEEE 1547 states that capacitance values of the filter and R represents the combined
one of its tasks for future consideration is the implementation ohmic losses in the filter inductor and on state resistance of the
of intentional islanding [4].
+
Ic abc Iq PI
+
-
Pref
A phase locked loop (PLL) is used to determine the frequency cos(wt),sin(wt)
Vgd
Divide
and angular reference at the Point of Common Coupling Va Vgd Idref
abc
(PCC). Vb dq
dq
PCC Vc abc Vd Vgq
i
Vgq Reference
CB Iqref
cos(wt),sin(wt) Divide ω*Li for PWM
R L C generation
GRID
PLL Qref
++
-
PI
+
+
LC FILER
+-
DG VSI Id
RLC 1 RLC 2
Iq
Va Vb Vc
PI +
current in the dq axis. According to (4) and (5), active and Ic abc Iq Vgdref
Vgd
+
PI
cos(wt),sin(wt) Idref
Va Vgd abc
Vb dq dq
abc
Vc Id Reference
Vgq Iqref
cos(wt),sin(wt) ωLi for PWM
+-
PI generation
PLL +
+-
Vgqref PI +
+
Iq
Vgq
Va Vb Vc
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY SURATHKAL. Downloaded on April 20,2021 at 11:02:04 UTC from IEEE Xplore. Restrictions apply.
III. ISLANDING DETECTION ALGORITHM IV. LOAD SHEDDING ALGORITHM
In our system we consider a simple hybrid passive islanding With the suggested islanding detection algorithm, some
detection method based on frequency (OFP/UFP) and voltage load generation mismatch is needed, for transferring the
(OVP/UVP) measurement, for implementing the intentional control from grid connected to islanded mode. But such a
islanding operations. The frequency and voltage variations are system cannot sustain an island due to the excessive variation
dependent on the load generation mismatch. If these of frequency and voltage. Hence, when the required demand is
parameters exceed the threshold specified by the algorithm, more, some load should be cut off using an efficient load
islanding will be detected. shedding scheme, to prevent the voltage and frequency
An islanding detection algorithm should be collapse. Here a priority based load shedding is implemented.
dependable, secure and fast. It should discriminate between The magnitude of the voltage at the PCC, obtained from the
islanding and other events and should detect all possible
DQ PLL, is continuously measured. When it crosses the
formation of islands. The threshold value is decided based on
specified voltage level, specified in the algorithm shown in
the above requirements. Moreover, with this algorithm,
Fig.5, signal is given to the circuit breaker to remove the load.
islanding is detected only if the parameter excursions remain
for a sufficient time delay. This will help to prevent the Load 2 is made to have more priority than load 1, and will not
misinterpretation of other grid dynamics for islanding. shut down until large voltage variation persists. [11]
Islanding detection algorithm is shown in Fig.4. The first voltage levels 0.15pu and 0.3pu corresponds to
But if the generation-load mismatch is negligible, this immediate trip of load 1 and load 2. The second voltage level
algorithm cannot detect islanding within the required time 0.1pu triggers a load shedding command only when the
frame and will produce Non Detection Zones. NDZ is defined voltage remains there for the specified time delay. T1 and T2
as the range of loads for which islanding is not detected. For a are the delay time for load 1 and load 2 respectively, where
constant power controlled interface operating in unity power T2>T1
factor mode, the NDZ for OVP/UVP and OFP/UFP can be
derived as (11) and (12) V. SIMULATION RESULTS AND DISCUSSION
[V V
max
]2 − 1 ≤
ΔP
P
[
≤ V V
min
]2 − 1 ( 11 )
The performance of the system in grid connected and
islanding mode of operation is analyzed using the simulated
Qf . (
1 − ⎡⎢ f f
⎣ max ⎥⎦ P
)
⎤ 2 ≤ ΔQ ≤ Qf . (
1 − ⎡⎢ f f
⎣
⎤2
min ⎥⎦
) (12 )
system in MATLAB/SIMULINK. The simulated system is
shown in Fig.6. The inverter is operating with unity power
Qf is the quality factor of the local load circuit and Vmax, Vmin, factor, delivering 10kW power to the load. The system
fmax and fmin represents the maximum and minimum frequency parameters are given in table 1.
and voltage limits. For a current controlled interface the NDZ
for the OFP/UFP remains the same as above but that of
Start
OVP/UVP protection turns out to be different as shown in (13)
[V V
max
] 1 ≤ ΔPP ≤ [V
− V
min
]− 1 (13 )
Vd=Vref-u1
START
S2 S1
2 2
Measure voltage 1
and frequenc y 1
0.1 0.3
Vd 0.1 0.15 Vd
Is NO YES
1.1pu<vd<0. YES
88pu Is S2==2 Is S 1==2
YES NO NO
NO
NO NO
Is 60.5Hz < Is S2==1 RETURN Is S1==1
f < 59.3Hz
YES YES
YES Increase t
Lasted for
NO
Lasted for
T2 period
NO T1 period
Is t > delay NO
YES
TRIP LOAD 2
Islanding is detec ted TRIP LOAD 1
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY SURATHKAL. Downloaded on April 20,2021 at 11:02:04 UTC from IEEE Xplore. Restrictions apply.
VSI From
g [Pulse] LC FILTER GRID
+
A A A aA A a aA A
DG B B B bB B b bB
B
-
C C C cC C c cC
C
PCC LS CB
1
A
B
C
com
A
B
C
CB1
C
A
B
VABC Signal(s) Pulses [Pulse]
b
a
c
PWM GENERATOR
B
A
C
B
A
C
Vabc In1 RLC LOAD 1 RLC LOAD 2
Out1 [VABC]
C
B
A
C
B
A
Iabc In2
CONTROLLER
Figure.6.Simulated System
Grid gets disconnected at t=2sec.Designing the interface
control as constant current controlled, four cases as analyzed.
Active Power(watts)
4
x 10
Case1: Load is adjusted to operate the inverter at 100% 2
active power (P) balance and 100% reactive power
balance (Q) 0
Case2: Load is adjusted at 50% rated P and 100% Q balance
Case1 Case2 Case3 Case4
Case 4: Load at 100% rated P and 96.6% Q balance -2
0 0.5 1 1.5 2 2.5 3 3.5 4
Case 5: Load at 125% rated P and 103.4% Q balance. Time(s)
The simulated results are shown in Fig.7.With the above (a)
5000
Reactive Power(Var)
TABLE 1 1
Vd(pu)
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY SURATHKAL. Downloaded on April 20,2021 at 11:02:04 UTC from IEEE Xplore. Restrictions apply.
10 300
Reactive Power m ism atch (% )
Id and Idref
CONSTANT POWER CONTROLLED
200
CONSTANT CURRENT CONTROLLED
5 100
5.5% OF
-14% -8.17% 0% 12.8% 29%
0
0
OV UV -100
0 0.5 1 1.5 2 2.5 3 3.5 4
-5 -7.15% Time(s)
50
UF
Iq and Iqref
-10
-15 -10 -5 0 5 10 15 20 25 30
Active Power Mismatch(%)
0
Figure.8. Simulated NDZ for constant current controlled interface
and constant power controlled interface for OVP/UVP and -50
OVF/UVF protection 0 0.5 1 1.5 2 2.5 3 3.5 4
Time(s)
Figure 11: Id and Iq tracking Idref and Iqref
Certain points which are noted from the results:
1) The NDZ for the constant power controlled 1
Vabc(pu)
interface is larger comparing with the current
0
controlled interface.
2) NDZ for reactive power mismatch is less -1
comparing with the active power mismatch. Reactive 1.9 2 2.1 2.2 2.3
Time(s)
power variations are more sensitive and produce 200
notable deviations in frequency to trigger islanding
detection. When grid is not providing the desired Iabc(A)
0
reactive power, frequency varies, to reach the
resonant frequency of the load.
-200
3) With the specified islanding detection algorithm, 1.9 2 2.1 2.2 2.3
Time(s)
both active and reactive power variations are needed 1
for reliable detection. Large active power mismatch
LS
0.5
can produce frequency deviation in addition to Load sheddding command
to circuit breaker
0.5
PCC. After the grid gets disconnected at t=2sec, the Figure. 12. (a)Three phase voltage at the PCC (b) Three phase current from
algorithm waits for the specified time delay and will the inverter (c) Command from the load shedding algorithm to shut down the
give a switching command at 2.05sec. Load shedding load (d) Islanding detection algorithm output
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY SURATHKAL. Downloaded on April 20,2021 at 11:02:04 UTC from IEEE Xplore. Restrictions apply.
Centre-Varennes, Natural Resour. Canada, Varennes, QC, Canada, [9] F. Gao and M. R. Iravani, "A control strategy for a distributed
Tech. Rep. CETC-Varennes 2004-074, 2004. generation unit in grid-connected and autonomous modes of operation,"
[7] I.J. Balaguer, Q.Lei, S.Yang, U.Supatti and F. Z. Peng, “Control for IEEE Transactions on Power Delivery, vol. 23, pp. 850- 859, Apr 2008.
grid-connected and intentional islanding operations of distributed power [10] Z. Ye, A. Kolwalkar, Y. Zhang, P. Du, and R. Walling, “Evaluation of
generation”, IEEE Trans. Ind. Electron., vol. 58, pp. 147-157,Jan.2011. anti-islanding schemes based on non detection zone concept, ”IEEE
[8] H. H. Zeineldin, E. F. El-Saadany, and M. M. A. Salama, “Impact of DG Trans. Power Electron., vol. 19, no. 5, pp. 1171–1176, Sep.2004.
Interface Control on Islanding detection and non-detection zones”, [11] L. Xu and D. Chen, “Control and operation of a DC Microgrid with
IEEE Trans. Power Del., vol. 21, pp. 1515-1523, Jul. 2006. variable generation and energy storage”, IEEE Trans. Power Del,
Vol.26,Oct.2011
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY SURATHKAL. Downloaded on April 20,2021 at 11:02:04 UTC from IEEE Xplore. Restrictions apply.