11.

50

ACCU ACCU ACCU 4MM THK. STEEL PLATE


01 02 03 ANCHOR WELDED TO SLEEVE

ROLLED B.I. PIPE GA 16


EXPANSION BOLT WELDED JOINT PIPE SLEEVE
TO VERIFY ACCU PLATFORM ANCHORED TO SLAB
LOCATION AT SITE 4"Ø X 8" LONG PVC SLEEVE
BOTTOM OF SLAB 3/8" Ø ROUND BAR HANGER
TYP. DETAIL FOR INSULATED PIPES
EXCEPT WITHOUT CLAD (SLOPING)
FIN. CEILING LINE
IF APPLICABLE RUBBER VIBRATION
ISOLATOR
INSIDE OUTSIDE
1" Ø PVC FCU DRAIN PIPE;

3TR ACU
TAP TO EXISTING
FCU WASTE PIPE DRAIN 1" THK. ANULAR RUBBER SEAL
03 3/4"Ø PVC DRAIN PIPE;
(ALL ENDS OF SLEEVE)
FCU TAP TO THE NEAREST WALL
DRAIN PIPE
CAULK OR NON SHRINK GROUT
FLR. LINE
GENERAL NOTES :
1. CONTRACTOR IS ADVISED TO VISIT AND SURVEY THE PLACE OF INSTALLATION.
2. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE
PIPE SLEEVE THRU CLOSELY HIS WORKS WITH THE OTHER TRADES CONCERNED.
CEILING SUSPENDED 3. BORING OF HOLES THRU FLOORS, SLABS, WALLS, ETC. SHALL BE DONE
FCU MOUNTING DETAILS WALL DETAILS BY THIS MECHANICAL CONTRACTOR INCLUDING RETOUCHING OF THE SAME.
NTS
4. ALL INSTALLATION WORKS SHALL BE DONE IN A NEAT AND A WORK-MANLIKE
NTS MANNER.
5. AS-BUILT PLANS SHALL BE PROVIDED BY THIS CONTRACTOR AFTER
COMPLETION OF WORKS.
1" Ø PVC FCU DRAIN PIPE;
3TR ACU

TAP TO EXISTING
WASTE PIPE DRAIN FCU
01 VERIFY TO ACU SPECIFICATIONS :
MANUFACTURER 1. COPPER PIPES
A. HARD DRAWN TYPE
B. INSULATION: 1/2" THK RUBBER INSULATION WITH VAPOR BARRIER
2. DRAIN PIPES:
A. MATERIAL: 3/4" Ø UPVC PIPES "ATLANTA", "NELTEX", OR
APPROVED EQUAL TO BE TAPPED TO THE NEAREST FLOOR DRAIN.
SERVICE PANEL B. ALL DRAIN PIPES SHALL BE PROPERLY INSULATED WITH 1/2" THICK
NOTE: USE G.E. BRAND OR
APPROVED EQUAL BOLT-ON
RUBBER INSULATION.
3. ELECTRICAL:

14.82
TYPE CB W/ NEMA3 ENCLOSURE
FCU UNIT 1/2"Ø ESLON BLUE PIPE A. CONDUIT: EMT PIPE
ACCU BASE B. WIRE: THHN WIRE "PHELPS DODGE" OR APPROVED EQUAL
C. CONDUIT AND WIRE SIZE AS PER MANUFACTURERS RECOMENDATION.
REFRIGERANT
COPPER PIPES
P-TRAP
ANGULAR
PLATFORN

PROVIDE NEOPRENE REFRIGERANT


VIBRATION ISOLATOR COPPER PIPES COVER

FCU DRAIN CONNECTION DETAIL LEGEND


50 X 50 X 6mm THK. ANGULAR NTS

1" Ø PVC FCU DRAIN PIPE;


PLATFORM W/ 3 COATS PRIMER
GRAY FIN.
FCU FAN COIL UNIT
3TR ACU

FCU
TAP TO EXISTING
WASTE PIPE DRAIN
#
02
ACCU AIR COOLED
CONDENSING UNIT
# (OUTDOOR)
ACCU MOUNTING DETAILS
NTS TF TRANSFER FAN
#
CIRCUIT BREAKER
(BY ELECTRICAL CONTRACTOR)
T THERMOSTAT

1Sl EXHAUST FAN SWITCH

STEEL TRUSS FLOOR SLAB


REFRIGERANT PIPING
CIRCUIT BREAKER;
ANCHOR BOLT BY MECHANICAL
CONTRACTOR
3/8"Ø THREADED ROUND BAR FCU DRAIN
BOLT REFER TO MECH'L
U-BOLT
AIRCONDITIONING SYSTEM LAYOUT POLYETHYLENE TAPE
SCHEDULE OF EQUIPMENT
FOR KW RATING FCU
SCALE 1:50 M ACCU
CONTROL WIRING CONDUITS
CONTROL WIRING
POWER WIRING CONDUITS
ELASTOMETRIC RUBBER CONTROL DESCRIPTIONS
INSULATION "AEROFLEX"
AIRCONDITIONING EQUIPMENTS SCHEDULE : OR APPROVED EQUAL
1. THERMOSTAT T SHALL HAVE OFF FAN COOL CONTROL
2. SWICTH TO FAN SHALL START FCU FAN.
COOLING POWER ANGLE BAR APPLY 3. SWICTH TO COOL (FAN) SHALL START THE ACCU
UNIT TR AIR FLOW REFRIGERANT PIPES DOUBLE COAT WITH FAN ON
CAPACITY SOURCE MODEL TYPE REMARKS
DESIGNATION CAPACITY (CFM) PROTECTIVE PAINT FINAL
(BTU/HR) (Ø/V/HZ) 4. THERMOSTAT SHALL CYCLE THE ACCU TO MAINTAIN
ROOM TEMPERATURE AT 24°C
SPLIT TYPE / FREE BLOW /
FCU/ACCU-1 3.00 TR 36000 1200 1/230V/60 UNITS SHALL BE " CARRIER" OR "KOPPEL"
CEILING CASSETTE
REFRIGERANT PIPE HANGER /
FCU/ACCU-2 3.00 TR 36000 1200 1/230V/60
SPLIT TYPE / FREE BLOW /
CEILING CASSETTE
UNITS SHALL BE " CARRIER" OR "KOPPEL" INSULATION DETAILS ELECTRICAL SCHEMATIC DIAGRAM
NTS NTS
SPLIT TYPE / FREE BLOW /
FCU/ACCU-3 3.00 TR 36000 1200 1/230V/60 CEILING CASSETTE
UNITS SHALL BE " CARRIER" OR "KOPPEL"

PROFESSIONAL MECHANICAL ENGINEER: PRC NO.: PROJECT TITLE: OWNER SHEET CONTENTS DRAWN BY SHEET NO.

PTR NO.: REVISED BY


RRJ / PETROL BOUTIQUE 1/1
DATE ISSUED: CHECK BY
M
PLACE ISSUED: LOCATION : GF, ST-03, WE-HOME TOWN CENTER, SINILOAN, LAGUNA FASHION TREND APPAREL CORP. DATE
ADDRESS: # 48 Felix Avenue Brgy. San Isidro Cainta Rizal 1900