Pel004 1071 004
Pel004 1071 004
Pel004 1071 004
Gemstart 4
Volume 3 - Specification Reference
Technical Handbook 15G0012(E)
Gemstart 4
Volume 3 - Specification Reference
Foreword
This Technical Handbook provides the User with the information necessary to Install,
Commission, Operate, Maintain and Test the equipment (as applicable). It is essential
that any Operator(s) reads and understands the content of this Technical
Handbook and follows the instructions contained within.
Every care has been taken to ensure the accuracy of the contents at the date of publication.
If the use of this equipment introduces new technology to your Operators, product training is
available from ALSTOM T&D Ltd to assist you in complying with relevant Health and Safety
Regulations.
Should you require further guidance or information regarding this equipment, or information
on our After Sales Services available, please contact our Customer Services Department at the
address below who will be pleased to assist:
Our policy is one of continuous product development. We reserve the right to supply
equipment that may vary from that described.
The information contained within this Technical Handbook may not be reproduced or passed
on to third parties, either wholly or in part, without the express prior written consent of
ALSTOM T&D Ltd.
15G0012(E)
Page 3
Gemstart 4
Volume 3 - Specification Reference
All relevant Warnings and Cautions shall be noted and their content strictly adhered to during
the Installation, Commissioning, Operation, Maintenance and Testing (where applicable) of
this equipment.
This equipment uses, or controls, fatal voltages. It is recommended therefore that Operators
working with, or near to, the equipment should be trained in resuscitation techniques.
The User has a duty of care to ensure that the equipment and/or its individual components
are disposed of in accordance with local and national Environmental Legislation and
Regulations. Some components may present a particular hazard to the environment if not
disposed of correctly.
The equipment must not be modified without prior consultation with ALSTOM T&D Ltd.
Modification without ALSTOM’s consent may invalidate the warranty and any product liability.
Should the Operator/User require any guidance or advice regarding the equipment, this can
be obtained by contacting ALSTOM at the address below:
15G0012(E)
Page 4
Gemstart 4
Volume 3 - Specification Reference
Customer Services
ALSTOM’s Customer Services Department can provide continuous Customer support
throughout the lifetime of your equipment. A comprehensive range of services is available,
including:
ALSTOM’s specialised Customer Service Engineers are available to provide the services listed
above, either in our Salford workshop, or alternatively, at your site.
To assist us in providing an efficient and timely service, before contacting ALSTOM to discuss
existing equipment, please help us by having the following information available:
The original ALSTOM works order number or
The unit serial number and the unit type and voltage
When you have the information listed above, please contact us at the address below:
15G0012(E)
Page 5
Gemstart 4
Volume 3 - Specification Reference
Table of Revisions
Edition Description
A Original issue
B Completely revised
15G0012(E)
Page 6
Gemstart 4
Volume 3 - Specification Reference
ADVICE: information
CAUTION: precautions to
intended to assist in
be taken to avoid
performing specified
damaging the equipment
tasks
YOUR ATTENTION IS DANGER, ELECTRICITY:
DRAWN: specific precautions to be taken
points that should be to avoid injury to
noted. personnel.
MECHANICAL
DANGER: precautions
to be taken to avoid
injury to personnel.
15G0012(E)
Page 7
Gemstart 4
Volume 3 - Specification Reference
Contents
15G0012(E)
Page 8
Gemstart 4
Volume 3 - Specification Reference
List of Figures
Figure 1 Gemstart 3 curves ............................................................................................ 81
Figure 2 - Gemstart 4 curves ............................................................................................ 82
List of Tables
15G0012(E)
Page 9
Gemstart 4
Volume 3 - Specification Reference
Readership
The publication is a reference for engineers who are responsible for setting up and
configuring Gemstart 4.
Related publications
n Volume 1: Gemstart 4 User Guide
Volume 1 is for the general engineer and user who will install, commission,
use and maintain Gemstart 4
n Volume 2: Gemstart 4 Design guide
Volume 2 is for the expert engineer who needs to exploit the advanced
facilities provided by Gemstart 4
15G0012(E)
Page 10
Gemstart 4
Volume 3 - Specification Reference
2 Introduction
2.1 Definitions
This reference manual specifies the detail of the functions of Gemstart 4
q Contactor types
q Input functions
q Protection functions
Each of the items is defined individually. The information for each set of items
follows the same layout which is briefly described in the following sections.
15G0012(E)
Page 11
Gemstart 4
Volume 3 - Specification Reference
n Fault codes:
GEMSTART 4 LINK: The fault code sent on the GS4 link when the input is
activated
GEMSTART 3 LINK:
Trip: Fault code sent on GS3 compatible link if Tripped
Alarm: Fault code sent on GS3 compatible link if in Alarm
Warn: Fault code sent on GS3 compatible link if in Warn
n Description:
A description of the input function and the expected device which activates
it
n Application notes:
Any comments which may help in applying the input function. This could
include methods of applying the function and any special circumstances
The table shows the function type, the options available for polarity and the
type of fault that can be initiated when the input event occurs.
Abbreviation Meaning
N/A Not Applicable
N/O Normally Open. The input closes when active
N/C Normally Closed. The input opens when active
LT Latched trip. The trip flag must be cleared by a reset trips
command
SCT Self Clearing Trip. If the trip input signal clears the trip flag is
cleared automatically
LA Latched Alarm. The alarm flag must be cleared by a reset trips
or reset alarms command
SCW Self Clearing Warn. If the warn input signal clears the warn flag
is cleared automatically
None No faults are flagged when an input is defined as this
15G0012(E)
Page 12
Gemstart 4
Volume 3 - Specification Reference
15G0012(E)
Page 13
Gemstart 4
Volume 3 - Specification Reference
15G0012(E)
Page 14
Gemstart 4
Volume 3 - Specification Reference
3 Functional specifications
3.1 Contactor type
To define the type of control required from a Gemstart 4 unit the contact type
must be configured. Various styles of automation are provided each of which is
described in the following datasheets:
15G0012(E)
Page 15
Gemstart 4
Volume 3 - Specification Reference
Description
This two speed starter allows a motor with two sets of windings to be
controlled. The two windings have two different sets of protection settings. The
only link between the two protection sets is the thermal content mimic of the
motor. The Dahlander motor uses tapped windings to provide the two winding
connection methods.
A close A command closes the Low Speed contactor and close B closes the
High speed contactor. In Manual and Local modes this contactor must go
through stop to change speed. A change of speed from the Host is taken
through stop automatically.
The Line contactor for the High speed connection may be omitted. The Low
speed contactor and High speed star contactor must be wired in to prevent
these contactors being closed at the same time and creating a short across the
3 phases.
Connections
The software contactor control block is defined as:
Inputs Outputs
Low Speed Aux A A Low Speed contactor
High Speed Line Aux (Opt) B B High Speed Line cont.
High speed star Aux C C High speed Star cont.
D D No Trips
Dahlander
(Low or High
Start)
15G0012(E)
Page 16
Gemstart 4
Volume 3 - Specification Reference
Configuration
Special Settings
This contactor type can be used as a follower contactor if the A and B Aux are
wired in. The contactor will followed Low Speed Start if the A Aux is closed with
B and C Open. A High speed start is followed if the B Aux is closed with the A
Aux open.
Application notes
The configuration item ‘slow down delay’ provides a minimum time the motor
must remain in the stopped condition when moving from high speed to low
speed. There is no delay when moving from low to high speed.
Example. A Two Speed motor is running in high speed with a 30s Slow
Down Time.
Case 1: The stop button is pressed and the motor stops. The Low Start
button is pressed 10s later. Gemstart displays “Slow Down Delay.” for 20s then
the low speed contactor is closed.
Case 2: The Low Start button is pressed while in High Speed. Gemstart
displays “Slow Down Delay.” for 30s then the low speed contactor is closed.
The slow down delay will not be maintained though a power down. Therefore
a long delay can be reset by power cycling Gemstart.
15G0012(E)
Page 17
Gemstart 4
Volume 3 - Specification Reference
Description
A two speed starter allows a motor with two sets of windings to be controlled.
The two windings have two different sets of protection settings. The only link
between the two protection sets is the thermal content mimic of the motor. This
version of Two Speed will allow the motor to be started in High or Low .
A close A command closes the Low Speed contactor and close B closes the
High speed contactor. A change of speed is allowed in all control modes.
Options
There are no options to wiring these contactors as Gemstart must know the
state of contactors. By knowing both contactor positions Gemstart can ensure
that a 3 phase short is not generated by having both contactors closed at the
same time.
Connections
Inputs Outputs
Low Speed Aux (Optional) A A Low Speed
High Speed Aux (Optional) B B High Speed
C C Trip active
D D No Trips
Two Speed
(Low or High Start)
15G0012(E)
Page 18
Gemstart 4
Volume 3 - Specification Reference
Configuration
Special Settings
This contactor type can be used as a follower contactor if the A and B Aux are
wired in.
Application notes
The configuration item ‘slow down delay’ provides a minimum time the motor
must remain in the stopped condition when moving from high speed to low
speed. There is no delay when moving from low to high speed.
Example. A Two Speed motor is running in high speed with a 30s Slow
Down Time.
Case 1: The stop button is pressed and the motor stops. The Low Start
button is pressed 10s later. Gemstart displays “Slow Down Delay.” for 20s then
the low speed contactor is closed.
Case 2: The Low Start button is pressed while in High Speed. Gemstart
displays “Slow Down Delay.” for 30s then the low speed contactor is closed.
The slow down delay will not be maintained though a power down. Therefore
a long delay can be reset by power cycling Gemstart.
15G0012(E)
Page 19
Gemstart 4
Volume 3 - Specification Reference
Description
A two speed starter allows a motor with two sets of windings to be controlled.
The two windings have two different sets of protection settings. The only link
between the two protection sets is the thermal content mimic of the motor. This
version of Two Speed will not allow the motor to be started in High Speed.
High Speed can only be started if Low Speed has completed the Startup phase.
A high speed start from the stop condition will automatically cycle through a
low speed start first before moving to high speed.
A close A command closes the Low Speed contactor and close B closes the
High speed contactor. A change of speed is allowed in all control modes.
Options
There are no options to wiring these contactors as Gemstart must know the
state of contactors. By knowing both contactor positions Gemstart can ensure
that a 3 phase short is not generated by having both contactors closed at the
same time.
Connections
Inputs Outputs
Low Speed Aux (Optional) A A Low Speed
High Speed Aux (Optional) B B High Speed
C C Trip active
D D No Trips
Two Speed (Low Start)
All inputs are Normally Closed.
15G0012(E)
Page 20
Gemstart 4
Volume 3 - Specification Reference
Configuration:
Special Settings:
This contactor type can be used as a follower contactor if the A and B Aux are
wired in.
Application notes:
The configuration item ‘slow down delay’ provides a minimum time the motor
must remain in the stopped condition when moving from high speed to low
speed. There is no delay when moving from low to high speed.
Example. A Two Speed motor is running in high speed with a 30s Slow
Down Time.
Case 1: The stop button is pressed and the motor stops. The Low Start
button is pressed 10s later. Gemstart displays “Slow Down Delay.” for 20s then
the low speed contactor is closed.
Case 2: The Low Start button is pressed while in High Speed. Gemstart
displays “Slow Down Delay.” for 30s then the low speed contactor is closed.
The slow down delay will not be maintained though a power down. Therefore
a long delay can be reset by power cycling Gemstart.
15G0012(E)
Page 21
Gemstart 4
Volume 3 - Specification Reference
3.1.4 DOL-E
Description:
The Direct On Line Electrically Held (DOL-E) contactor is the simplest and most
common contactor type. The contactor is held closed while the Output to the
contactor is on.
Options:
The auxiliary connection from the contactor can be fed back to Gemstart to
allow the status of the contactor to be reported to the user. If the auxiliary is not
connected and the Contactor Input is configured to Closed then the position of
the contactor is assumed from the intended contactor status.
Connections:
Inputs Outputs
Contactor Aux (Optional) A A Contactor
B B Off
C C Trip active
D D No Trips
DOL-E
15G0012(E)
Page 22
Gemstart 4
Volume 3 - Specification Reference
Configuration:
Special Settings:
This contactor type can be used as a follower contactor if the A Aux is wired in.
15G0012(E)
Page 23
Gemstart 4
Volume 3 - Specification Reference
Description:
The latching contactor is a mechanically latched contactor which uses two coils
to latch the contactor closed or delatch the contactor. Output A is used to latch
(close) the contactor. Output B is used to delatch (open) the contactor.
Options:
None
Connections:
Inputs Outputs
Line Aux A A Latch
B B Delatch
C C Trip active
D D No Trips
DOL-L
15G0012(E)
Page 24
Gemstart 4
Volume 3 - Specification Reference
Configuration:
Special Settings:
This contactor type can be used as a follower contactor if the A Aux is wired in.
15G0012(E)
Page 25
Gemstart 4
Volume 3 - Specification Reference
3.1.6 Forward/Reverse
(Gemstart 4.3 only)
Description:
Options:
There are no options to wiring these contactors as Gemstart must know the
state of contactors. By knowing both contactor positions Gemstart can ensure
that a 3 phase short is not generated by having both contactors closed at the
same time.
Connections:
Inputs Outputs
Forward Contactor Aux A A Forward Contactor
Reverse Contactor Aux B B Reverse Contactor
C C Trip active
D D No Trips
Forward/Reverse
15G0012(E)
Page 26
Gemstart 4
Volume 3 - Specification Reference
Configuration:
Special settings:
15G0012(E)
Page 27
Gemstart 4
Volume 3 - Specification Reference
Description:
This allows Gemstart to be used for simple I/O. Minimal error checking is
performed on the outputs. The only change to outputs is that Outputs A and B
are turned Off if the Link has failed and Gemstart is configured to Link Fail
Trip.
The 4 bit Host Command is used as the source for the 4 off GP outputs. These
4 bits can be modified by the HHP if the HHP is in control. On returning the
HHP to Monitor the GP Outputs are updated with the Host command again
and could therefore resume their original state.
Options:
No options.
Connections:
The software contactor control block is defined as:
Inputs Outputs
A A Command bit 0
B B Command bit 1
C C Command bit 2
D D Command bit 3
GP I/O
15G0012(E)
Page 28
Gemstart 4
Volume 3 - Specification Reference
Configuration:
Special Settings:
No special settings.
15G0012(E)
Page 29
Gemstart 4
Volume 3 - Specification Reference
Description:
This contactor type allows easy control of a latching device which is normally
manually controlled rather than via Gemstart.
Opening this contactor type will activate the Trip Output for a fixed duration.
Closing will activate the Close Output for a fixed duration. The Running Aux is
fed to Input A as the Open Aux may not report Open when the drive is tripped.
Manual control
Once the contactor driver has come out of the latching or tripping state it will
follow any changes on the auxiliary input.
Options:
The Closing coil does not have to be used on this contactor type. This allows
units with only one output to be used to monitor and trip an MCCB.
Connections:
Inputs Outputs
Running Aux A A Trip coil
B B Closing Coil (Optional)
C C Trip active
D D No Trips
MCCB
15G0012(E)
Page 30
Gemstart 4
Volume 3 - Specification Reference
Configuration:
Special Settings:
This contactor type defaults to a follower contactor. The A Aux must be wired
in.
15G0012(E)
Page 31
Gemstart 4
Volume 3 - Specification Reference
Description:
Motor operated valves use a motor to open or close a valve. Limit switches at
either end of the valve travel indicate when the motor has reached the fully
closed or fully open position.
A close A command Opens the valve for maximum flow. A close B command
Closes the valve for no flow. When the relevant limit switch is activated the
contactor is opened. In Manual and Local modes this contactor must go
through stop to change direction. A change of direction from the Host is taken
through stop automatically.
Valve fully Open = “Open Limit Switch” Open Circuit = Input 7 Open
Options:
There are no options to wiring these contactors as Gemstart must know the
state of contactors. By knowing both contactor positions Gemstart can ensure
that a 3 phase short is not generated by having both contactors closed at the
same time.
Connections:
Inputs Outputs
Opening Contactor Aux A A Open Valve Contactor
Closing Contactor Aux B B Close Valve Contactor
Fully Open Limit Switch C C Trip active
Fully Closed Limit Switch D D No Trips
Forward/Reverse
15G0012(E)
Page 32
Gemstart 4
Volume 3 - Specification Reference
Configuration:
Special Settings:
Application Notes:
The limit travel switches must be placed in line with the forward and reverse
contactors. To implement this slave open and close relays are required see
example circuits in Volume 1.
To provide remote positional indication status bit 11 and status bit 13 must be
configured to inputs 7 and 8.
15G0012(E)
Page 33
Gemstart 4
Volume 3 - Specification Reference
Description:
For units with a single output for the line contactor. Used to drive a Star Delta
changeover relay. After the minimum start time has expired Gemstart will wait
for the Star contactor to open and then the current to drop below 100% FLC
before ending startup.
Options:
The Delta Auxiliary does not have to be connected.
Connections:
Inputs Outputs
Line Aux A A Line Cont. (and timer relay)
Delta Aux (Optional) B B Off
Star Aux C C Trip active
D D No Trips
Star/Delta (1)
All inputs are Normally Closed.
15G0012(E)
Page 34
Gemstart 4
Volume 3 - Specification Reference
Configuration:
Special Settings:
This contactor type can be used as a follower contactor if the A Aux is wired in.
The minimum start time can be set to a fixed time roughly equal to the time to
delta of the star/delta relay.
15G0012(E)
Page 35
Gemstart 4
Volume 3 - Specification Reference
Description:
This is the same two output method of Gemstart 3. Output A drives the star
contactor and Output B drives the Delta contactor. Both outputs are slaved
from the interlock circuit.
The Line contactor is slaved from the auxiliaries of the Star or Delta contactors.
The statistics for Contactor C are maintained for the Line Contactor.
When a start command is actioned, the Star contactor (and therefore the line
contactor) is pulled in. The starter will remain in this state until the line current
decays to FLC. The star contact will then open and the Gemstart will wait until
the line current decays to zero. The Delta contactor will then be closed. The
Start period will then finish when the line current again falls below FLC.
Options:
There are no options to wiring these contactors as Gemstart must know the
state of contactors. By knowing both contactor positions Gemstart can ensure
that a 3 phase short is not generated by having both contactors closed at the
same time.
Connections:
Inputs Outputs
Star Aux A A Star Contactor
Delta Aux B B Delta Contactor
C C Trip active
D D No Trips
Star/Delta (2)
15G0012(E)
Page 36
Gemstart 4
Volume 3 - Specification Reference
Configuration:
Special Settings:
This contactor type can be used as a follower contactor if the A Aux is wired in.
Closing the Star contactor will put Gemstart in to the Star startup condition.
15G0012(E)
Page 37
Gemstart 4
Volume 3 - Specification Reference
Description:
Three outputs are provided to drive each contactor individually. This improves
the control of the line contactor and improves fault reporting of contactor
faults.
The star contactor is on Output C and not Output A to ensure that an interlock
will remove all volts from the motor. i.e. Opening the Line and Delta
contactors removes volts from the star so the need for an interlock to the star
contactor is reduced.
With the above connections the star and line contactors are closed together,
and then the line contactor is held through the changeover and opens at the
same time as the delta contactor.
When a start command is actioned, the Star contactor and the line contactor
are pulled in. The starter will remain in this state until the line current decays to
FLC. The star contact will then open and the Gemstart will wait until the line
current decays to zero. The Delta contactor will then be closed. The Start
period will then finish when the line current again falls below FLC.
Options:
The auxiliary connection from the contactor can be fed back to Gemstart to
allow the status of the contactor to be reported to the user. If the auxiliary is not
connected and the Contactor Input is configured to Closed then the position of
the contactor is assumed from the intended contactor status.
There are no options to wiring these contactors as Gemstart must know the
state of contactors. By knowing both contactor positions Gemstart can ensure
that a 3 phase short is not generated by having both contactors closed at the
same time.
15G0012(E)
Page 38
Gemstart 4
Volume 3 - Specification Reference
Connections:
Inputs Outputs
Line Aux (Optional) A A Line Contactor
Delta Aux B B Delta Contactor
Star Aux C C Star Contactor
D D No Trips
Star/Delta (3)
Configuration:
Special Settings:
This contactor type can be used as a follower contactor if the A Aux is wired in
15G0012(E)
Page 39
Gemstart 4
Volume 3 - Specification Reference
Description:
A Variable Speed Drive (VSD) can be controlled from Gemstart for simple
control tasks. This driver operates with in built delays to wait for the VSD to
power on after a start command.
Options:
Connections:
Inputs Outputs
Running A A Line Contactor
Reversing (Optional) B B Off
C C Reverse (Optional)
D D No Trips
VSD (Logic)
15G0012(E)
Page 40
Gemstart 4
Volume 3 - Specification Reference
Configuration:
Special Settings:
15G0012(E)
Page 41
Gemstart 4
Volume 3 - Specification Reference
Description:
A Variable Speed Drive can be controlled from Gemstart for simple control
tasks.
Options:
RUN/stop is provided as a Mains and a Volt Free output. The Mains output will
require an interposing relay. The volt free output can be used to feed the VSD
directly.
Connections:
Inputs Outputs
Running A A RUN/stop
Reversing (Optional) B B Off
C C Reverse (Optional)
D D RUN/stop (Optional)
VSD (Logic)
15G0012(E)
Page 42
Gemstart 4
Volume 3 - Specification Reference
Configuration:
Special Settings:
This contactor can be defined as a follower. If the Running input goes active a
Start A is generated. If the Reversing input and Running input become active a
Start B is generated.
Output 2 can be used to control a line contactor which is placed before the
VSD. This ensures that an Interlock fault will isolate the VSD and the motor. To
operate with a line contactor output 2 should be configured to be ON.
15G0012(E)
Page 43
Gemstart 4
Volume 3 - Specification Reference
This item is configured in percent FLC with a limit of 1000% of the CT rating.
The actual function of this input is contactor type dependent – consult relevant
contactor type data sheet for further information.
15G0012(E)
Page 44
Gemstart 4
Volume 3 - Specification Reference
The actual function of this input is contactor type dependent – consult relevant
contactor type data sheet for further information.
The actual function of this input is contactor type dependent – consult relevant
contactor type data sheet for further information.
15G0012(E)
Page 45
Gemstart 4
Volume 3 - Specification Reference
The status options available to the hardware outputs are defined below:
Option Description
Off The output is Off all the time.
On The output source is on all the time.
Contactor Output A This output is generally used to control contactor A.
Contactor Output B This output is generally used to control contactor B.
If contactor B does not exist this output is Off all the
time.
Contactor Output C This output is generally used to control contactor C.
If contactor C does not exist then this output
defaults to the “Trip Present” status bit.
Contactor Output D This output is generally used to control contactor D.
If contactor D does not exist then this output
defaults to the “No Trips Present” status bit.
GP Output A A GP Output bit supplied by the Host via the serial
link.
GP Output B A GP Output bit supplied by the Host via the serial
link.
GP Output C A GP Output bit supplied by the Host via the serial
link.
GP Output D A GP Output bit supplied by the Host via the serial
link.
Motor Stopped The contactors are open and there is no current
flowing.
Running One of the contactors is closed.
Running A Contactor A is, or should be, closed.
Running B Contactor B is, or should be, closed. (4.3 only)
In Startup Gemstart is in the startup phase.
Motor Available to Host The motor is available for serial link commands.
I.e. Gemstart is in Auto or Priority Mode, there are
no trips present, and the contactor is not in the test
position.
Any Fault Present A Warn, Alarm, Trip or LTrip (Latched trip) is
present. I.e. there is a non zero fault code.
No Trips Present There are no Trips or LTrips present.
Warn Present There is a Warning present.
Alarm Present There is an Alarm present.
Self Clearing Trip There is a (self clearing) Trip present.
Present
Latched Trip present There is a (latching) LTrip present.
Available to Priority A priority command can start the motor. I.e. there
are no trips present, the contactor is not in the test
position and the Hard Stop input is not active.
Available to Manual A priority command can start the motor. I.e.
Gemstart is in Manual Mode, there are no trips
present, the contactor is not in the test position and
the Hard Stop and Process Stop inputs are not
active.
15G0012(E)
Page 46
Gemstart 4
Volume 3 - Specification Reference
If the auxiliary status does not match the intended contactor status a number of
faults can be reported. If the contactor has just changed state a “Failed to
Open” or ”Failed to Close” fault is reported. If the contactor has been in the
correct state then an “Unexpected Close” or Unexpected Open” fault is
reported.
Selecting No with force the user to issue a Manual Mode Stop or HHP stop
before sending the opposite direction command.
15G0012(E)
Page 47
Gemstart 4
Volume 3 - Specification Reference
Similar functionality is provided for all 3 Star/Delta contactor types. I.e. the Star
contactor will not be closed within a configured time of the Delta contactor
being closed.
Forward/Reverse and MOV contactors implement the Slow Down Time delay
when changing direction.
15G0012(E)
Page 48
Gemstart 4
Volume 3 - Specification Reference
15G0012(E)
Page 49
Gemstart 4
Volume 3 - Specification Reference
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed (negative edge), Normally Open (positive
edge)
REPORTING OPTIONS: None
Fault codes:
GEMSTART 4 LINK: N/A
GEMSTART 3 LINK:
TRIP: N/A
Alarm: N/A
Warn: N/A
Description:
Application notes:
Used for counting Kilowatt hour pulses, rotary transducer pulses etc. The
maximum counting frequency is 15 Hz.
15G0012(E)
Page 50
Gemstart 4
Volume 3 - Specification Reference
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed, Normally Open
REPORTING OPTIONS: Off, Warn, Alarm, Trip, LTrip
Fault codes:
GEMSTART 4 LINK: 36
GEMSTART 3 LINK:
TRIP: 61
Alarm: 62
Warn: 63
Description:
Any auxiliary volt free contact indicating an error condition from third party
equipment.
An active signal applied to this input will cause a device fault. The Gemstart
action will depend on the configured reporting option and a fault code will be
sent on the serial link.
Application notes:
Defaults to a normally Closed, Self clearing Warn. Typical devices which could
use this function are:
q Miniature Circuit Breakers
q Moulded Case Circuit Breakers
q Air Circuit Breakers
q Variable Speed Drive
15G0012(E)
Page 51
Gemstart 4
Volume 3 - Specification Reference
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed, Normally Open
REPORTING OPTIONS: Off, Warn, Alarm, Trip, LTrip
Fault codes:
GEMSTART 4 LINK: 29
GEMSTART 3 LINK:
TRIP: 29
Alarm: 29
Warn: 29
Description:
An active signal applied to this input will cause an ELCB Fault. The Gemstart
action will depend on the configured reporting option and a fault code will be
sent on the serial link.
Application notes:
Defaults to a Normally closed, Latching trip. This function may complement the
Earth fault protection available by the unit by providing personnel protection
levels. If this is required then, to ensure health and safety compliance, the
interlock input must be used.
15G0012(E)
Page 52
Gemstart 4
Volume 3 - Specification Reference
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed, Normally Open
Fault codes:
GEMSTART 4 LINK: N/A
GEMSTART 3 LINK:
TRIP: N/A
Alarm: N/A
Warn: N/A
Description:
The Emergency Start functions ignore all trip conditions and close the
contactor.
The Emergency Start functions are level triggered functions that force
Emergency Manual Mode while they are active. Emergency Manual Mode
M
(LCD displays E ) is the highest priority mode. I.e. it will override HHP and
Priority modes.
While in Emergency Manual Mode all LTrips and Trips are reported on the link
as Alarms and Warns respectively. As soon as the Emergency Start is removed
any LTrips that have occurred or Trips that are still active are automatically
actioned. While Emergency Start is active Gemstart will display a status
message “Emergency Start”.
Application notes:
These functions are for a very specific function and should not be used for
normal operation. They should only be used to start the motor in circumstances
where it is better for the motor to be damaged rather than tripped. E.g. for a
fire pump or gas extractor.
The only way to stop or prevent a start command being actioned is to open the
Interlock input. Restoring volts to the interlock input with the Emergency Start
still active will re-close the contactor.
Due to the urgent need for action in an emergency state, if Emergency Start A
and Emergency Start B, are both active then the A input will be actioned and
the B input ignored.
15G0012(E)
Page 53
Gemstart 4
Volume 3 - Specification Reference
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed, Normally Open
REPORTING OPTIONS: Self clearing Trip (except in manual mode where no fault is
flagged)
Fault codes:
GEMSTART 4 LINK: 10
GEMSTART 3 LINK:
TRIP: 11
Alarm: 11
Warn: 11
Description:
Application notes:
Defaults to a Normally Closed, Latched trip (see above for trip reporting).
The Hard Stop will attempt to put the unit in manual mode. This will be
successful if no higher priority modes are active (i.e. Priority or HHP modes).
Useful where a Stop in any mode is required from a remote push button.
15G0012(E)
Page 54
Gemstart 4
Volume 3 - Specification Reference
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed, Normally Open
REPORTING OPTIONS: N/A
Fault codes:
GEMSTART 4 LINK: N/A
GEMSTART 3 LINK:
TRIP: N/A
Alarm: N/A
Warn: N/A
Description:
A start signal is latched by the unit. Release of Start signal will not open the
contactor. A separate signal is needed.
A start signal is not latched. Release of the start signal will open the contactor.
Application notes:
Manual Inch is for two wire control using a single push-button for jogging or
inching the motor.
If Start B and INCH select are configured to the same input then Start B will act
as an INCH input. Start A will operate as a Run input.
15G0012(E)
Page 55
Gemstart 4
Volume 3 - Specification Reference
3.3.7 Interlock
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed
REPORTING OPTIONS: Off, Warn, Alarm, Trip, LTrip
Fault codes:
GEMSTART 4 LINK: 12
GEMSTART 3 LINK:
TRIP: 12
Alarm: 12
Warn: 12
Description:
Application notes:
Usually a normally closed self clearing trip. Used to indicate that an unsafe
condition has occurred and the contactor requires opening.
Usually applied to the Interlock input where it directly removes the feed to the
contactor.
15G0012(E)
Page 56
Gemstart 4
Volume 3 - Specification Reference
3.3.8 Isolator
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed, Normally Open
REPORTING OPTIONS: Off, Warn, Alarm, Trip, LTrip
Fault codes:
GEMSTART 4 LINK: 03
GEMSTART 3 LINK:
TRIP: 03
Alarm: 03
Warn: 03
Description:
Application notes:
15G0012(E)
Page 57
Gemstart 4
Volume 3 - Specification Reference
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed, Normally Open
REPORTING OPTIONS: N/A
Fault codes:
GEMSTART 4 LINK: N/A
GEMSTART 3 LINK:
TRIP: N/A
Alarm: N/A
Warn: N/A
Description:
Application notes:
Defaults to a Normally Closed input. Opening the signal will select manual
mode. Ideal for Manual / Auto selection.
15G0012(E)
Page 58
Gemstart 4
Volume 3 - Specification Reference
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed, Normally Open
REPORTING OPTIONS: N/A
Fault codes:
GEMSTART 4 LINK: 18 Release manual start Warn
80 Manual start and stop active warn
20 Fwd/Rev Warn
GEMSTART 3 LINK:
TRIP: N/A
Alarm: N/A
Warn: 57 Release manual start Warn
63 Gemstart 4 Warn
20 Fwd/Rev Warn
Description:
An active signal will cause a start request for contactor A (or B). If the unit is in
manual mode and available then the unit will close the relevant contactor.
If a single contactor type (such as DOLE) is selected then Manual Input B acts
as a second source of start for that contactor
15G0012(E)
Page 59
Gemstart 4
Volume 3 - Specification Reference
Application notes:
When used with Remote Select, Start A and Start B can be used as start signals
from different sources. Start A is the Local Start and Start B is the Remote Start.
15G0012(E)
Page 60
Gemstart 4
Volume 3 - Specification Reference
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed, Normally Open
REPORTING OPTIONS: Off, Warn, Alarm, Trip, LTrip
Fault codes:
GEMSTART 4 LINK: 07
GEMSTART 3 LINK:
TRIP: 30
Alarm: 30
Warn: 30
Description:
An active signal applied to this input will cause an Overload Relay Fault.
This will cause a fault code on the Serial Link. A fault on the Hand Held
Programmer and a condition as defined when configured.
Application notes:
Can be fed into Interlock input for direct action upon contactor.
15G0012(E)
Page 61
Gemstart 4
Volume 3 - Specification Reference
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed, Normally Open
REPORTING OPTIONS: None
Fault codes:
GEMSTART 4 LINK: 80 Manual start and stop active warn
GEMSTART 3 LINK:
TRIP: N/A
Alarm: N/A
Warn: 63 Gemstart 4 Warn
Description:
Application notes:
When used with Remote Select, Stop A and Stop B can be used as stop signals
from different sources. Stop A is the Local Stop and Stop B is the Remote Stop.
15G0012(E)
Page 62
Gemstart 4
Volume 3 - Specification Reference
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed, Normally Open
REPORTING OPTIONS: N/A
Fault codes:
GEMSTART 4 LINK: N/A
GEMSTART 3 LINK:
TRIP: N/A
Alarm: N/A
Warn: N/A
Description:
When Manual Mode is enabled, Remote Select allows the source of Manual
Commands to be switched between a local start and stop (Manual Start A and
Process Stop A) and a remote start and stop (Manual Start B and Process Stop
B).
When Remote Select is enabled it will enable the Remote inputs and disable
the Local inputs. When Remote Select is disabled the Local Inputs are enabled
and Remote inputs disabled.
If the source of Remote Select is Open or Closed then all 4 Process Start A/B
and Process Stop A/B inputs are all enabled in Manual mode.
The following table summarises the influence of Remote Select:
Manual Remote Select Local Remote LCD
Mode Mode
Manual Start A Manual Start B
Process Stop A Process Stop B
Disabled Ignored Ignored Ignored A,P or H
Enabled Source = Open or Closed Active Active M
Enabled Input is Inactive “Local” Active Ignored M
L
15G0012(E)
Page 63
Gemstart 4
Volume 3 - Specification Reference
Application notes:
This function can be used to monitor a Local / Remote selector switch. In this
context Local and Remote are both sources of Manual Control. This function
cannot be used with two direction contactors. It can only be used with DOL-E,
Star/Delta, MCCB, VSD or DOL-L.
NB The INCH function is not affected by Remote Select and is therefore always
active. This means the INCH function cannot be used for one start source but
not the other. However if Inch mode is needed in one mode but not the other,
then use Manual Start x and Process Stop x to look at the same input.
A change in the Remote Select input will generate an edge on the start input if
the start input is configured to “Mode Change”.
E a r th F a u lt CT3 C T2 C T1
N e u tr a l
L iv e
L iv e
O /P 1
N e u tr a l
D e la tc h
E a r th
N e u tr a l
In te r lo c k
O /P 2
I/ P 1
C o n t. F ie ld S T O P
S ta tu s
I/ P 2
S ta r t A F ie ld S T A R T
I/ P 3
S to p A R L
I/ P 4
R e m o te
I/ P 5
PA M M
I/ P 6
S ta r t B &
S to p B P L C -1
I/ P 7
I/ P 8
S e r ia l
L in k
I/ P 9 PLC
To PLC
O /P 3
When the switch is changed to ‘L’ (Local) position the Start A and Stop A inputs
control Gemstart. In this case the PLC input is ignored.
15G0012(E)
Page 64
Gemstart 4
Volume 3 - Specification Reference
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed, Normally Open
REPORTING OPTIONS: None
Fault codes:
GEMSTART 4 LINK: N/A
GEMSTART 3 LINK:
TRIP: N/A
Alarm: N/A
Warn: N/A
Description:
An active edge will allow the pre-defined set of trips and counters to be reset
from the field device.
Application notes:
This function would typically be used to reset overload trips although a wide
range of reset options are available. Note that other reset options are
available (HHP, serial link and Front panel stop switch).
The reset options are defined in CFG/User IF/Reset Input. The reset input
standard settings will reset:
q Alarms
q Overloads
q Motor protection
q Application protection
q Interlocks
15G0012(E)
Page 65
Gemstart 4
Volume 3 - Specification Reference
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed, Normally Open
REPORTING OPTIONS: N/A
Fault codes:
GEMSTART 4 LINK: N/A
GEMSTART 3 LINK:
TRIP: N/A
Alarm: N/A
Warn: N/A
Description:
On “two contactor” types, pressing Test Mode Start again will operate the B
contactor. Subsequent operations will toggle between A and B. The first
operation in Test mode will always be to Contactor A.
The config item “Test Mode Start”, “Source (N/O) = Open” will be added to
the Manual Controls menu. Advanced setting for this function will also be
added. The standard options are Open and Normally Open.
This feature has not been added to the old (single output) GS4.2.
Application notes:
Use a push button on the chassis casing to test that the contactors can be
operated. The function only operates when the chassis is in test position and no
trips are present.
15G0012(E)
Page 66
Gemstart 4
Volume 3 - Specification Reference
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed, Normally Open
REPORTING OPTIONS: Off, Warn, Alarm, Trip, LTrip
Fault codes:
GEMSTART 4 LINK: 54
GEMSTART 3 LINK:
TRIP: 61 & Status word bit 7
Alarm: 62 & Status word bit 7
Warn: 63 & Status word bit 7
Description:
This signal indicates that the motor starter has been withdrawn to the Test
Position. Whilst In this mode the following items of protection are disabled:
q Undercurrent
q Number of operations (of the contactor)
q Hours Run
q Trip counters
Application notes:
This function allows for the chassis to be tested off load without affecting the
chassis wear statistics.
15G0012(E)
Page 67
Gemstart 4
Volume 3 - Specification Reference
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed, Normally Open
REPORTING OPTIONS: Off, Warn, Alarm, Trip, LTrip
Fault codes:
GEMSTART 4 LINK: 06
GEMSTART 3 LINK:
TRIP: 06
Alarm: 06
Warn: 06
Description:
An active signal applied to this input will cause a Thermistor relay fault
300ms later. The time delay allows time for the relay to pick up after power
cycling.
Application notes:
A Normally closed, Latched trip. This function is used for measuring motor
winding temperatures on motors equipped with PTC probes enabling the
motor to be tripped at a threshold temperature.
15G0012(E)
Page 68
Gemstart 4
Volume 3 - Specification Reference
Menu location:
Source:
Advanced settings:
SENSE OPTIONS: Normally Closed, Normally Open
REPORTING OPTIONS: Off, Warn, Alarm, Trip, LTrip
Fault codes:
GEMSTART 4 LINK: 37 (38 for user text 2)
GEMSTART 3 LINK:
TRIP: 09 (10 for user text 2)
Alarm: 09 (10 for user text 2)
Warn: 36 (37 for user text 2)
Description:
Application notes:
Defaults to a Normally Closed, Latched trip reporting User text 1 (or User Text
2)
With the reporting options set to OFF, the User Text message is still displayed
on the LCD while the source input is active. This allows an active “Stop” input
to be reported locally, without generating a fault report on the serial link.
15G0012(E)
Page 69
Gemstart 4
Volume 3 - Specification Reference
CFG/Contactor/Fail/Recover Voltages p 71
CFG/Motor Protection/FLC Setting p 72
CFG/Motor Protection/Startup Current p 73
CFG/Motor Protection/Startup Time p 75
CFG/Motor Protection/Thermal Overload p 77
CFG/Motor Protection/Thermal Reset Delay p 83
CFG/Motor Protection/Restart Inhibit p 84
CFG/Motor Protection/Single Phasing p 85
CFG/Motor Protection/Imbalance p 86
CFG/Motor Protection/Starts in Hour p 87
CFG/Motor Protection/Speed sense p 88
CFG/Motor Protection/Voltage protection p 89
CFG/Motor Protection/Earth Fault Protection p 91
CFG/Contactor/Advanced settings/Contactor protection p 94
CFG/Measurements/Power rating p 95
CFG/Application Protection/Set ALC p 96
CFG/Application Protection/Phase Reversal p 97
CFG/Application Protection/Under Current p 98
CFG/Application Protection/Instant ALC p 99
CFG/Application Protection/Constant ALC p 100
CFG/Application Protection/Under Power p 101
CFG/Application Protection/Over Power p 103
CFG/Application Protection/Power Factor High p 105
CFG/Application Protection/Power Factor Low p 106
CFG/Application Protection/AutoRestart p 107
15G0012(E)
Page 70
Gemstart 4
Volume 3 - Specification Reference
At the Low Threshold the Auto restart function will initiate and the Gemstart will
enter and display ‘Low motor Volts’.
At the High threshold the Gemstart will recover from the ‘Low motor Volts’
condition.
15G0012(E)
Page 71
Gemstart 4
Volume 3 - Specification Reference
Pre-requisites
Before the HHP can display FLC as percentage and Amps, the CT Rating and
CT Turns must be configured.
Configuration items
FLC Setting
Select the option that is the first below the FLC value named on the Motor
Rating Plate. Remember that the HHP will display the equivalent Amps reading
if possible.
Protection wizard
The FLC setting is changed by the Motor Setup Wizard. The suggested
option is the first option below the Motor FLC rating.
Additional information
None.
15G0012(E)
Page 72
Gemstart 4
Volume 3 - Specification Reference
This protection feature trips Gemstart if the highest phase current rises above
the trip limit.
This item is configured in terms of FLC. The equivalent Amps value is also
displayed.
Prerequisites
To correctly configure this item in Amps the CT Rating, CT Turns and FLC
Setting must be configured.
Configuration items
Start Current Limit
Off, 100% to 2000%FLC in 10% steps. Standard 800% (Maximum
is 1000% Nominal CT)
Advanced Settings
Protection Active No, Yes
Severity Warn, Alarm, Trip, Trip & Alarm, LTrip
Pre Warn Level Off, 70, 80, 90, 100%
Disabled in Startup No, Yes
Select a Start Current Limit which is greater than the Inrush current of the
motor. Allow a margin of about 15% to avoid false trips.
The Start Current Limit cannot exceed 10 times the Nominal CT value due to
limits on the output from a CT. If the limit is configured to be too high,
Gemstart will repair the limit to the maximum value.
Protection wizard
The Motor Setup Wizard will offer a configuration of this item which is the
highest of the following options:
q The next value greater than the start inrush current
q The next value greater than the average of the start inrush current and stall
current
For example: if Inrush Current is 550% and the stall current is 600%, the
Motor Setup Wizard will suggest the first option above 600 i.e. 610%
For example: if Startup Peak Current was 630% and the Wizard Margin is
15%, the option offer is the first option above 1.15*630%=724% i.e. the
option 730% is offered.
15G0012(E)
Page 73
Gemstart 4
Volume 3 - Specification Reference
If the Wizard Setting is accepted the Advanced Settings / Protection Active Item
is forced to Yes.
Additional information
For very high instantaneous currents the Contactor Protection feature may hold
the contactor closed for a short time until the fuse blows. During such a delay
Gemstart will display “Stop Delayed.”
Information about the peak current is available from two statistics available on
the HHP.
n Currents / Peak Current
This displays the peak of the highest phase since the last startup. This
variable is continuously updated and is not limited to the startup phase
n Start / Startup Peak
This displays the peak of the highest phase current which was reached
during the last successful start. Note that this value is only updated when
the startup becomes successful, i.e. when the current drops to 100%FLC. If
the motor is stopped or trips during startup then the start was not successful
and this statistic is not updated
15G0012(E)
Page 74
Gemstart 4
Volume 3 - Specification Reference
Once a motor reaches its running speed the current drops to the application
running current. If, at the end of the Startup Time, the motor current is greater
than 125% FLC then a fault will be generated.
The Startup Time Protection Feature stops once the current drops below 100%
FLC or the Startup time has elapsed.
Pre-requisites
The FLC figure must be configured before this feature will work. The FLC value
is required to allow the end of the startup phase to be detected.
Configuration items
Start Time Limit
Off, 00m01s to 99m59s, Standard 60s
Advanced Settings
Protection Active No, Yes
Severity Warn, Alarm, Trip, Trip & Alarm, LTrip
Pre Warn Level Off, 70, 80, 90, 100%
Disabled in Startup No, Yes
Select a Start Time Limit which is greater than the motor acceleration time and
less than the stall withstand time.
Protection wizard
The Motor Setup Wizard will offer a configuration of this item which is the
highest of the following options:
q The next value greater than the acceleration time
q The next value greater than the average of the acceleration time and stall
withstand time from hot
For example: if Acceleration time is 6s and the stall withstand time from hot
is 9s, the Motor Setup Wizard will suggest the first option above (6+9)/2=7.5s
i.e. 8s
For example: if Startup Time was 7s and the Wizard Margin is 15%, the
option offered is the first option above 1.15*7=8.05s i.e. the option 9s is
offered.
If the Wizard Setting is accepted the Advanced Settings / Protection Active Item
is forced to Yes.
15G0012(E)
Page 75
Gemstart 4
Volume 3 - Specification Reference
Additional information
Information about the startup time is available from the statistics available on
the HHP.
n Start / Startup Time
This displays the time taken for the current to drop to 100%FLC. Note that
this value is only updated when the startup becomes successful, i.e. when
the current drops to 100%FLC. If the motor is stopped or trips during
startup then the start was not successful and this statistic is not updated
n When setting the Startup time remember to take into account the
Minimum Start Time. Minimum Start time is defined in the contactor
advanced settings and defaults to 10s for the star delta contactors and 1 s
for all other contactor types. The Start Time limit must be greater than the
Minimum Startup time.
15G0012(E)
Page 76
Gemstart 4
Volume 3 - Specification Reference
Two sets of curves are available, Gemstart 3 and Gemstart 4. The Gemstart 3
curves are provided to allow you to provide exactly the same protection and
thermal information as you could with Gemstart 3. The Gemstart 4 curves offer
a larger range of curves and provide the thermal information in a slightly
easier way.
An Auto option is also available which will select a GS4 curve based on the
configured Start Time Limit and Start Current Limit. The resultant “curve” will
lie somewhere between curve 1 and curve 31 although not exactly on a
numbered curve. The Auto Curve will trip after running for the Start Time Limit
at the Start Current Limit.
Gemstart 3 Curve
This curve is the same as the Gemstart 3 curve. Gemstart trips when the
thermal content reaches 110%. The 100% level is the Hot condition, i.e. after
extended running at 100%FLC.
Gemstart 4 Curve
There are 31 new curves for Gemstart 4. The thermal content is reported as a
percentage of the trip level.
Gemstart 4 curves can be configured with the ratio of the “hot stall withstand
time” to the “cold stall withstand time”. This allows a better model of the
thermal content to be maintained during normal (<= FLC) running.
Pre-requisites
For this protection feature to operate correctly the FLC Setting must be correctly
configured.
15G0012(E)
Page 77
Gemstart 4
Volume 3 - Specification Reference
Configuration items
Overload Curve Type
Off, Gemstart 3, Gemstart 4, Auto (GS4)
Gemstart 3 Curve (Only Displayed if Gemstart 3 Curve Type)
Off, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14
Gemstart 4 Curve (Only Displayed if Gemstart 4 Curve Type)
Off, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19,
20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31
Hot/Cold Ratio (Only Displayed if Gemstart 4 Curve Type)
Unknown, 1 to 100% in 1% steps
Advanced Settings
Protection Active No, Yes
Severity Warn, Alarm, Trip, Trip & Alarm, LTrip
Pre Warn Level Off, 70, 80, 90, 100%
Disabled in Startup No, Yes
The process of selecting the best overload curve for Gemstart 4 is described in
Chapter 2 Volume 1 - User Guide.
Protection wizard
The Motor Setup Wizard will force the Curve Type to Gemstart 4 and setup
the curve number and Hot Cold Ratio based on the Stall Withstand Times. The
offered curve will trip the motor after running at the Stall current for the Stall
Withstand time from cold. The Hot Cold Ratio is set to the Hot over Cold Stall
Withstand Times.
The Motor Protection Wizard forces Thermal Overload into the Auto
setting. This will trip the motor after the motor has been running for the Start
Time Limit at the Start Current Limit. The Hot/Cold Ratio is forced to Unknown.
Additional information
Hot/Cold Ratio
The Hot/Cold Ratio setting modifies the thermal model to allow a Hot Start to
use the full Stall Withstand Time From Hot as well as limiting cold starts to the
Stall Withstand Time From Cold.
The Hot/Cold Ratio modification works by derating the heating effect during
normal running. Normal running is when the current is below the pickup level
(107%). This means that even after extended running at 100%FLC there is still
enough thermal content left to allow a start duration equal to the Hot
Withstand Time.
When Hot/Cold Ratio is not used (Gemstart 3 Curves) or is set to Unknown the
normal heating effect is not derated. (This is equivalent to a Hot/Cold Ratio of
about 13%.)
15G0012(E)
Page 78
Gemstart 4
Volume 3 - Specification Reference
Related statistics
Information about the thermal content is available from the statistics available
on the HHP.
n Start / Therm Used by Start
This displays the thermal content used by the last successful start. Note that
this value is only updated when the startup becomes successful, i.e. when
the current drops to 100%FLC. If the motor is stopped or trips during
startup then the start was not successful and this statistic is not updated
n Therm / Thermal Content
This is the estimated thermal content of the motor. For Gemstart 4 Curves
the percentage is a percentage of the Trip Level
n Therm / Time to Trip/Avail
If the motor is running this is the estimated time to reach the Trip Level. If
the motor is stopped this is the estimated time for the motor to become
available
Gemstart 3 Gemstart 4
Trip Level 110% 100%
Overload Pickup Level 105% 107%
15G0012(E)
Page 79
Gemstart 4
Volume 3 - Specification Reference
The following equations allow the effect of fault currents to be predicted. The
time to trip and time to available times can be calculated or read from the
charts shown in Figures 1 and 2.
Gemstart 3 Gemstart 4
Time to Trip æ 1.1 - TS ö æ 1 - TS ö
= - k * lnçç1 - 2 ÷ = -k * lnçç1 - ÷
è I - TS ÷ø è [ I 1 . 07 ]2
- T ÷
S ø
Time to available æ TS - TA ö æ T - TA ö
= - k * lnçç1 - ÷ = -k * lnçç1 - S ÷
è TS ÷ø è TS ÷ø
Normal running =I 2
= I 2 * (1 - Hot _ Cold _ Ratio)
15G0012(E)
Page 80
Gemstart 4
Volume 3 - Specification Reference
Gemstart 3 Curves
10000
1000
Curve 14
Curve 13
Curve 12
Curve 11
100 Curve 10
Time to Trip (s)
Curve 9
Curve 8
Curve 7
10 Curve 6
Curve 5
Curve 4
Curve 3
Curve 2
1
Curve 1
0.1
0 1 2 3 4 5 6 7 8 9 10 11
Fault Level (xFLC)
15G0012(E)
Page 81
Gemstart 4
Volume 3 - Specification Reference
Gemstart 4 Curves
Curve 31
100000 Curve 30
Curve 29
Curve 28
Curve 27
Curve 26
10000
Curve 25
Curve 24
Curve 23
Curve 22
1000 Curve 21
Curve 20
Curve 19
Time to Trip (s)
Curve 18
100 Curve 17
Curve 16
Curve 15
Curve 14
Curve 13
10 Curve 12
Curve 11
Curve 10
Curve 9
1 Curve 8
Curve 7
Curve 6
Curve 5
Curve 4
0.1
Curve 3
0 1 2 3 4 5 6 7 8 9 10 11 Curve 2
Fault Level (xFLC) Curve 1
15G0012(E)
Page 82
Gemstart 4
Volume 3 - Specification Reference
Thermal Reset Delay gives a fixed delay after, and only after, a Thermal
Overload fault occurs. Restart Inhibit will always prevent a start if there is not
enough thermal headroom to start the motor.
Pre-requisites
None.
Configuration items
Thermal Reset Delay Time
Off,1, 2, 5, 10, 15, 20, 30 minutes
Advanced Settings
Protection Active No, Yes
Severity Warn, Alarm, Trip, Trip & Alarm, LTrip
Pre Warn Level Off, 70, 80, 90, 100%
Disabled in Startup No, Yes
Set to OFF unless you wish to have a fixed delay after every Thermal Overload
Trip.
Protection wizard
Additional information
Information about the Thermal Reset Delay is available from the statistics
available on the HHP.
15G0012(E)
Page 83
Gemstart 4
Volume 3 - Specification Reference
Restart Inhibit works by adding the thermal content used by the last successful
start to the present thermal content. Once the total is less than 100% the
Restart Inhibit fault is removed.
Pre-requisites
None.
Configuration items
Restart Inhibit Enable
Off, On
Advanced Settings
Protection Active No, Yes
Severity Warn, Alarm, Trip, Trip & Alarm, LTrip
Pre Warn Level Off, 70, 80, 90, 100%
Disabled in Startup No, Yes
Protection wizard
Additional information
Information about Reset Inhibit is available from the statistics available on the
HHP.
n Therm / Therm to Trip/Avail
If the motor is stopped this is the estimated time for the motor to become
available
See Thermal Overload for the Time to Available Equation and Chart.
15G0012(E)
Page 84
Gemstart 4
Volume 3 - Specification Reference
A single phasing fault is the same as an Imbalance fault of 80% present for a
user configured time. Note that this means that a single phasing fault cannot
occur unless the highest phase is at least 80%FLC.
Pre-requisites
None.
Configuration items
Single Phasing Time
Off, 0.1s to 25.5s in 0.1s steps
Advanced Settings
Protection Active No, Yes
Severity Warn, Alarm, Trip, Trip & Alarm, LTrip
Pre Warn Level Off, 70, 80, 90, 100%
Disabled in Startup No, Yes
Select the shortest time unless you are experiencing nuisance trips.
Protection wizard
Additional information
See Imbalance.
15G0012(E)
Page 85
Gemstart 4
Volume 3 - Specification Reference
Imbalance monitors the highest and lowest average phase currents. The
Imbalance current is calculated by subtracting the lowest from the highest
phase. The fault level is calculated as a ratio of the Imbalance Current to the
Highest Phase or 100%FLC current, whichever is highest.
Highest _ Phase - LowestPhase
Imbalance =
Highest _ of ( Highest _ Phase,100% FLC )
Pre-requisites
None.
Configuration items
Imbalance Limit
Off, 5% to 100% of highest current in 5% steps
Imbalance Time
0, 0.1 to 25.5s in 0.1s steps, Standard 0.5s
Advanced Settings
Protection Active No, Yes
Severity Warn, Alarm, Trip, Trip & Alarm, LTrip
Pre Warn Level Off, 70, 80, 90, 100%
Disabled in Startup No, Yes
Protection wizard
For example: the highest imbalance since the last start is 10%. The Tolerance
level is set to 15%. The Wizard will offer a new configuration above
10%*1.15=11.5% i.e. 15%.
Additional information
15G0012(E)
Page 86
Gemstart 4
Volume 3 - Specification Reference
A rolling total of the number of starts in the last hour is maintained. As the
oldest starts drop out of the count the Starts in Hour Trip is removed to allow
further starts to be actioned.
Pre-requisites
None.
Configuration items
Start in Hour Limit
Off, 1, 2, 3, 5, 8, 12, 30
Advanced Settings
Protection Active No, Yes
Severity Warn, Alarm, Trip, Trip & Alarm, LTrip
Pre Warn Level Off, 70, 80, 90, 100%
Disabled in Startup No, Yes
If the motor has a maximum starts in an Hour then set the Limit to match.
Otherwise set the Limit to Off.
Protection wizard
The Motor Setup Wizards selects the value equal to or below the actual Motor
Limit.
Additional information
Information about the number of Starts in the Last Hour is available from the
statistics available on the HHP.
n Counters / Starts in Hour
The total number of starts in the last hour
The history of when starts occurred is held in 4 counters. Therefore each start
operation is held in one of the counters for between 45 and 60 minutes.
15G0012(E)
Page 87
Gemstart 4
Volume 3 - Specification Reference
The Speed Sense timer is started when the contactor is closed. Once the timer
elapses and while the motor is running, Speed Sense will trip the motor if the
Speed Sense input is, or becomes, inactive.
Pre-requisites
None.
Configuration items
Speed Sense Limit
Off, 1 to 255s in 1s steps
Speed Sense Source
Off, On, Interlock, Input 1, ..., Input 4
Speed Sense I/P Sense
N/O, N/C
Advanced Settings
Protection Active No, Yes
Severity Warn, Alarm, Trip, Trip & Alarm, LTrip
Pre Warn Level Off, 70, 80, 90, 100%
Disabled in Startup No, Yes
Leave the Speed Sense Limit Off if the motor does not have a Centrifugal
Switch.
If the motor has a centrifugal switch set the Speed Sense Limit to the first setting
below the lowest of the following:
n Stall withstand time from hot
n Acceleration time
Protection Wizard
The Chassis Setup Wizard will define the Speed Sense Source.
If the speed sense source is not set to Off or On the Motor Setup Wizard will
offer a Speed Sense Limit which is the first value below the lowest of the
following:
n Stall withstand time from hot
n Acceleration time
Additional Information
None.
15G0012(E)
Page 88
Gemstart 4
Volume 3 - Specification Reference
The fault levels for Voltage Protection are variable and defined as:
As Gemstart does not transmit to the Host while in a Supply Fail condition
(<65%) an “Under Voltage Warn” condition will not been seen by the Host.
However there are two configurations of Voltage Protection which may be
useful:
If you wish to latch a supply dip condition set the severity to Alarm.
If you wish to receive a warning when the supply voltage drops below 70, 80,
90 or 100% of the control supply voltage then set the PreWarn level to the
appropriate level.
Pre Requisites
For the PreWarn level to work correctly the Control Voltage must be correctly
configured.
Configuration Items
Voltage Protection Enabled
No, Yes
Advanced Protection Settings
Protection Active No, Yes
Severity Warn, Alarm, Trip, Trip & Alarm, LTrip
Pre Warn Level Off, 70, 80, 90, 100%
Disabled in Startup No, Yes
For one Gemstart on each MCC (or Control Supply circuit if different) enable
the protection and set the PreWarn level to 90%.
15G0012(E)
Page 89
Gemstart 4
Volume 3 - Specification Reference
Protection Wizard
Additional Information
A Gemstart with Voltage Protection disabled will report “Supply Fail Warn” on
the LCD if a supply dip of longer than 12ms occurs or the average voltage
drops below 65% of 110V/220V. The fault is not reported to the Host.
A Supply Fail condition is defined as starting when the average voltage drops
below 65% of 110/220V or if the instantaneous voltage has not been above
92/184V (the peak of 65Vrms) for 12ms. A Supply Fail ends when the average
climbs above 90% of 110/220V
15G0012(E)
Page 90
Gemstart 4
Volume 3 - Specification Reference
Two fault levels are provided. A Start EFC active during the startup phase
(Until the highest phase falls below 100% FLC) and a standard EFC active
during normal running. The Start EFC allows for an increase in the protection
and Warn levels during start up to avoid nuisance tripping due to CT
mismatches which are accentuated during the high current start phase. In
addition if nuisance tripping continues to be a problem then EF Ignore at Start
can be used
In addition to the two fault levels two timers are used to provide comprehensive
control in event of an earth fault.
The first Earth Fault Timer, Delay to Detect, is used to prevent nuisance trips or
in the case of layered protection to allow protection devices lower in the chain
to trip first. If an earth fault is present for the duration of this timer’s setting
then Gemstart will trip - but not immediately. This is where the second timer,
Delay to Trip, comes in.
The second timer, Delay to Trip, holds the contactor closed to allow the fuses
to break the Earth Fault. The contactor is then opened and although the fault
has cleared, Gemstart will still flag an Earth Fault LTrip. The Delay to Trip timer
is required in 3 phase systems with 2 CT's and a CBCT. In 3 CT systems
Contactor Protection will ensure that the contactor is held closed while the fault
current is above the contactor break rating.
The advantage of having two delays is that an earth fault condition will still be
detected and flagged even if the fault is removed by a fuse blowing.
NOTE: The additional Delay to Trip is only required when all 3
phases are not being measured, or contactor protection is not
configured.
Explanation: The additional earth fault delay is implemented to allow the
fuse to blow before opening the contactor when very high fault currents are
flowing to earth. This is the aim of type 2 co-ordination.
All contactors are only rated to break currents up to a limit. Therefore if
Gemstart can guarantee not to open the contactor while the instantaneous
current is above that limit, no delay needs to be calculated or configured.
However for this to work correctly, Gemstart must be reading from 3 CT's.
As Earth Faults have serious safety implications this fault can only be cleared
with a HHP in Control (i.e. with the Key in the active position).
Pre-requisites
There are 2 hardware methods of Earth Fault Detection. The first method, by
CBCT, uses a CBCT with a load resistor to generate enough voltage at the
Earth Fault input to trip Gemstart.
15G0012(E)
Page 91
Gemstart 4
Volume 3 - Specification Reference
The second method, by CT, sums the 3 phase CT’s externally and passes the
residual current through a resistor across the Earth Fault input.
Configuration items
Earth Fault Current (EFC)
25% to 150% of EF Rating in 1% steps, Standard 100%
Start EFC
EFC + 0% to 100% in 1% steps
EF Ignore at Start
0.0, 0.4, 0.7, 1.0s
EF Delay to Detect
Off, 0, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 1.0, 1.2, 1.5, 1.8, 2.2,
2.7, 3.3, 3.9, 4.7, 5.6, 6.8, 8.2, 10s
Should only be used if residually connected CT’s are measuring the earth fault
Start with 0.1s. This time can be increase to improve rejection of nuisance trips.
If downstream protection is present this time should be set to be longer than
the downstream protections trip time.
The next table summaries how to set up the Earth Fault Timers.
15G0012(E)
Page 92
Gemstart 4
Volume 3 - Specification Reference
Protection wizard
For example: if the Earth Fault Current has reached 35% of the Nominal
Earth Fault Current since the last startup and the Wizard Tolerance level is set
to 15%, the new option offered is 35%*1.15=40.25, i.e. 41% will be offered
as the new configuration.
The Delay to Detect and Delay to Trip times are not affected.
Additional information
Information about the number of Starts in the Last Hour is available from the
statistics available on the HHP.
n Currents. / Earth Crnt(%Fault)
This item displays the Earth Fault Current as a percentage of the Fault Level
and in Amps
15G0012(E)
Page 93
Gemstart 4
Volume 3 - Specification Reference
To allow this to be fully implemented the following details about the contactor
and fuse must be configured.
q The maximum breaking current of the contactor
q The time for the fuse to blow at the above current
Fuse Time
The Fuse Time is the maximum time that Gemstart will wait for the fuse to blow
while the current is above the Maximum Contactor Rating. If the contactor has
not opened by the end of the Fuse Time Gemstart will open the contactor even
if the currents are still high.
Pre-requisites
To see the Contactor Rating in Amps as well as percent the CT Rating and
number of turns must first be defined.
Configuration items
Contactor Rating Break Current
100% to 2000% in 10% steps. Standard 1000%
Fuse Time
0, 0.1, 0.15, 0.22, 0.33, 0.47, 0.68, 1, 1.5, 2.2, 3.3, 4.7, 6.8, 10,
15, 22s
Select the first Contactor Rating below the contactor Maximum (RMS) Break
Current.
1. From the Time to Blow chart for the in line fuses, read off the time to
blow at the Contactor Rating Current
2. Use the next highest value for the Time to Blow configuration
Protection wizard
15G0012(E)
Page 94
Gemstart 4
Volume 3 - Specification Reference
Additional information
q While Contactor Protection is active and preventing a trip, Gemstart
displays “Stop Delayed.”
the calculation of power as a percentage for display and the serial link.
Pre Requisites
None.
Configuration Items
Power Rating
Unknown
0.10 to 0.99 in 0.01 steps,
1.0 to 9.9 in 0.1 steps,
10 to 99 in 1 steps,
100 to 990 in 10 steps (kW)
Protection Wizard
Power Factor is calculated by dividing the Real Power by the Apparent Power.
15G0012(E)
Page 95
Gemstart 4
Volume 3 - Specification Reference
Pre-requisites
This item is configured as a percentage of the CT rating. If you wish to see the
Amps rating as you are configuring this item then you must configure the CT
rating and CT turns first.
Configuration items
ALC Setting
25% to 150% of CT Rating in 1% steps
Protection wizard
Additional information
The percentage values displayed on Gemstart and the HHP are displayed as a
percentage of the FLC Setting during the startup phase. At all other times
currents are displayed as a percentage of the ALC Setting.
15G0012(E)
Page 96
Gemstart 4
Volume 3 - Specification Reference
Pre-requisites
Configuration items
Phase Reversal Enable
Off, On
Advanced Settings
Protection Active No, Yes
Severity Warn, Alarm, Trip, Trip & Alarm, LTrip
Pre Warn Level Off, 70, 80, 90, 100%
Disabled in Startup No, Yes
Protection wizard
Additional information
None.
15G0012(E)
Page 97
Gemstart 4
Volume 3 - Specification Reference
Under Current protection can be used to detect loss of load or changes in the
load characteristics.
Pre-requisites
Configuration items
Under Current Limit
Off, 5% to 100%ALC in 5% steps
Under Current Time
0 to 6000s in 1s steps (only expect 9m99s to be configurable),
Standard 10s
Advanced Settings
Protection Active No, Yes
Severity Warn, Alarm, Trip, Trip & Alarm, LTrip
Pre Warn Level Off, 70, 80, 90, 100%
Disabled in Startup No, Yes
If Under Current Protection is required set the Under Current Limit to a value
above the no load current.
The Under Current Time should be set to ensure that gaps in the load are
ignored. At the same time the time should be short enough to prevent damage
from continuous dry running.
Protection wizard
For example: if the lowest current was 50% and the Wizard Margin is set to
15% then the new option offered is the first option below 50*(100-
15)%=42.5% i.e. 40% option is offered.
The configuration wizard does not modify the Under Current Time.
Additional information
Information about the minimum phase current is available from the statistics
available on the HHP.
n Currents / Min&MaxALC
This item displays the minimum (and maximum) value for the highest
phase current since the end of the last startup phase. The current is
displayed as a percentage of the ALC Setting
15G0012(E)
Page 98
Gemstart 4
Volume 3 - Specification Reference
Pre-requisites
Configuration items
Instant ALC Limit
Off, 100% to 1000%ALC in 10% steps
Advanced Settings
Protection Active No, Yes
Severity Warn, Alarm, Trip, Trip & Alarm, LTrip
Pre Warn Level Off, 70, 80, 90, 100%
Disabled in Startup No, Yes
Set the Instant ALC Limit to a value above the peak running current of the
motor but below the Locked Rotor Current.
Protection wizard
The Application Protection Wizard monitors the highest current since the
end of the last startup. The new option offered is the first option above the
highest current plus the Wizard Margin.
For example: if the highest current since the end of startup is 132%ALC and
the Wizard Margin is set to 15%. The new option offered is 132*1.15=152. So
option 160% is offered.
Additional information
Information about the peak ALC current is available from the statistics
available on the HHP.
n Currents / Min&MaxALC
This item displays the maximum (and minimum) phase current since the
end of the last startup phase. The current is displayed as a percentage of
the ALC Setting
15G0012(E)
Page 99
Gemstart 4
Volume 3 - Specification Reference
This protection is useful for detecting partial blockages or other events which
cause a higher than normal load to be present for an extended time.
Pre-requisites
Configuration items
Continuous ALC Limit
Off, 100% to 2000%ALC in 10% steps. Standard 800% (Maximum
is 1000% Nominal CT)
Continuous ALC time
00m00s to 99m59s in 1s steps. Standard 00m10s
Advanced Settings
Protection Active No, Yes
Severity Warn, Alarm, Trip, Trip & Alarm, LTrip
Pre Warn Level Off, 70, 80, 90, 100%
Disabled in Startup No, Yes
Set the Continuous ALC Limit to a value less than the Instant ALC limit.
Select a time which will not cause nuisance trips under normal operational
conditions.
Protection wizard
The Application Protection Wizard offers a new value which is half way
between the ALC and the Instantaneous ALC fault limit.
Additional information
None.
15G0012(E)
Page 100
Gemstart 4
Volume 3 - Specification Reference
Under Power has a delay to trip time to allow short drops in power to be
ignored.
Pre Requisites
Motor Power Rating, Motor Voltage, CT Rating, and Control Supply Phase have
been configured;
Gemstart is NOT in Test Position.
Power can be calculated as long as the CT rating, motor voltage and control
supply phase have been defined. However as Under Power is configured as a
percentage of the Power Rating then that also must be configured to allow
Under Power Protection to operate.
Configuration Items
If a pre warn level of 70, 80 or 90% is selected, the warn level is calculated as
a percentage of the difference from 100% to the fault level.
For example if the fault level is 60% and the pre warn is set to 90% then the
pre warn level is 90% of the way from 100% to 60% i.e. 64%.
15G0012(E)
Page 101
Gemstart 4
Volume 3 - Specification Reference
Protection Wizard
If the Wizard settings for Under Power Limit are accepted, the Advanced
Setting/Protection Active item is forced to Yes.
Additional Information
None.
15G0012(E)
Page 102
Gemstart 4
Volume 3 - Specification Reference
Over Power has a delay to trip time to allow short increases in power to be
ignored.
See also Under Power, Power Factor High, and Power Factor Low.
Pre Requisites
Motor Power Rating, Motor Voltage, CT Rating, and Control Supply Phase have
been configured;
Power can be calculated as long as the CT rating, motor voltage and control
supply phase have been defined. However as Over Power is configured as a
percentage of the Power Rating then that also must be configured to allow
Over Power Protection to operate.
Configuration Items
If a pre warn level of 70, 80 or 90% is selected, the warn level is calculated as
a percentage of the difference from 100% to the fault level.
For example if the fault level is 60% and the pre warn is set to 90% then the
pre warn level is 90% of the way from 100% to 60% i.e. 64%.
15G0012(E)
Page 103
Gemstart 4
Volume 3 - Specification Reference
Protection Wizard
If the Wizard settings for Over Power Limit are accepted, the Advanced
Setting/Protection Active item is forced to Yes.
Additional Information
None.
15G0012(E)
Page 104
Gemstart 4
Volume 3 - Specification Reference
Pre Requisites
Configuration Items
For Power Factor High the pre warn levels 70, 80, and 90% correspond to 0.3,
0.2 and 0.1 below the configured fault limit.
Protection Wizard
For example if the maximum power factor since the end of the last startup is
0.72 and the Protection Wizard is setup with a 15% tolerance then the new
option offered for Power Factor High will be the first option above
0.72+0.15=-0.87 i.e. 0.90
If the Wizard settings for Power Factor High Limit are accepted, the Advanced
Setting/Protection Active item is forced to Yes.
Additional Information
None.
15G0012(E)
Page 105
Gemstart 4
Volume 3 - Specification Reference
Pre Requisites
Configuration Items
For Power Factor Low the pre warn levels 70, 80, and 90% correspond to 0.3,
0.2 and 0.1 above the configured fault limit.
Protection Wizard
For example if the minimum power factor since the end of the last startup is
0.35 and the Protection Wizard is setup with a 25% tolerance then the new
option offered for Power Factor Low will be the first option below 0.35-0.25=-
0.10 i.e. 0.10
If the Wizard settings for Power Factor Low Limit are accepted, the Advanced
Setting/Protection Active item is forced to Yes.
Additional Information
None.
15G0012(E)
Page 106
Gemstart 4
Volume 3 - Specification Reference
Control Supply
Present
Lost
Contactor Status
Closed
Open
<-- Ride Through --> <-- Hold Off --> <---- Delay to Restart ---->
<-- Up to 200ms --> <---- (Up to 99m59s) ---->
<---- Up to 30s (Max Dip Time) ---->
The first phase of AutoRestart is the Ride Through Phase. Ride Through
starts when the control supply is lost. During this phase the close command to
the contactor is maintained. The status of the contactor is unknown while there
are no volts present. If the supply is restored within the “Ride Through” period
Gemstart will automatically and immediately re-close the contactor. This will
allow your plant to continue running for short breaks of the control supply.
15G0012(E)
Page 107
Gemstart 4
Volume 3 - Specification Reference
NOTE: Any close which occurs during the Ride through period will not
be recorded in any statistics nor will it update the Starts/hour
counter.
If the supply is not restored within the Ride Through time, or a
second dip occurs within 1 second of the first dip, the contactor is
opened and AutoRestart moves into the Hold Off phase.
If the Ride Through time is set to Off the contactor will be opened when a
Supply Fail condition is detected. (A supply fail is when there are no volts for
10ms or the average drops to the Voltage Fail Level). A Max option is also
offered which will try to hold the contactor closed for as long as Gemstart has
enough power to run.
Turning Ride Through OFF puts Gemstart straight into the hold off phase.
Setting Ride Through = OFF does not disable auto restart.
The second phase of AutoRestart is the Hold Off Phase. During this time
Gemstart is waiting for the control supply to be restored. Gemstart may power
down during this phase. The end of Hold Off is when the average voltage rises
above the Voltage Recovery level. The configuration options for the recovery
levels vary dependant on the type of Gemstart as shown below.
If the supply is restored within the Dip Time then AutoRestart moves into the
Delay to Start phase.
If the Dip Time is exceeded without the supply being restored then AutoRestart
is aborted.
During the third phase, the Delay to Start Phase, Gemstart will wait for the
configured time before re-closing the contactor. After the Delay to Start time
has elapsed the contactor is then re-closed.
Turning Max Dip Time to OFF will disable Auto Restart. Setting Max Dip Time
to OFF does not disable the Ride through facility
15G0012(E)
Page 108
Gemstart 4
Volume 3 - Specification Reference
Pre Requisites
Configuration Items
Ride Through
Off, 40, 80, 120, 160, 200ms, Max
Max Dip Time
Off, 0.5 to 10s in 0.5s steps, 11, 12, 13, 14, 15, 17, 20, 25, 30s
Delay to Restart
00m00s to 99m59s
Select a ride through time which is longer than the hold in time for the
contactor. If your application can be restarted after stopping for 200ms then
pick the 200ms option. Selecting Max will attempt to hold the contactor closed
for as long as Gemstart keeps running. This can be up to 1s (or longer for
brown outs) depending on the voltage before the supply failed.
Select a Dip Time that matches the time your application or process can stand
without requiring a controlled startup.
The control supply to several Gemstart is likely to return at the same time.
Delay to Restart allows you to configure the order in which your process
restarts.
Protection Wizard
Additional Information
If a second supply fail condition occurs after some motors have restarted but
others are waiting for the Delay to Restart, it is very likely that only the motors
which have already started will go through another AutoRestart. This is
because the later motors are still measuring the dip time from the original loss
of supply. In this situation the control system will need to perform a controlled
restart.
The Gemstart 4.2 measures voltage to +/- 10% and hence the voltage
thresholds for triggering auto restart are limited. There is also more
possibilities for thresholds to vary between Gemstart units. In the case where
volts dip to 70% before restoring it is likely that some units will enter auto
restart whilst others will not. Loss of supply to 60% or less will guarantee all
units enter the restart condition. Similarly restoration of power can occur at a
spread of voltages
15G0012(E)
Page 109
TRANSMISSION & DISTRIBUTION – Distribution Switchgear
PO Box 28, Lichfield Road, Stafford, ST17 4LN, England Tel.: +44 (0)1785 254391 Fax: +44 (0)1785 274400
Internet: www.alstom.com