Pinal-Chapter 5 - Heater
Pinal-Chapter 5 - Heater
Pinal-Chapter 5 - Heater
HEATER DESIGN
The energy used to heat the feedwater is usually derived from steam
extracted between the stages of the steam turbine. Therefore, the steam
that would be used to perform expansion work in the turbine (and therefore
generate power) is not utilized for that purpose. The percentage of the total cycle
steam mass flow used for the feedwater heater is termed the extraction
fraction and must be carefully optimized for maximum power plant thermal
efficiency since increasing this fraction causes a decrease in turbine power
output.
HEATER NO. 1
Inlet Feed Water Temperature: t 18=38.64 ℃
Outlet Feed Water Temperature:t 19=58.71℃
Temperature of steam entering:t 2=68.71 ℃
Temperature of condensate leaving:t 3=68.71 ℃
Mass of steam entering: m2=3.3485 kg /s
Mass of condensate leaving:m3=3.3485 kg /s
Energy Balance:
m2 ℎ 2+ m21 ℎ21=m3 ℎ 3+ m22 ℎ22
Where,
ℎ2=2425.0584 kJ /kg
ℎ3 =287.578 kJ /kg
Q R1=7,157.3531 kW
A. Length of tube
Q R= AUθ
Where:
t max −t min
θ=
t max
ln ln
t min
t max=68.71− 58.71=10 ℃
10 −30.07
θ= ℃
10
ln
30.07
Heaters | 194
θ=18.223℃
From Power Plant Theory and Design by Potter (Figure 8-23) Page 373 with the
velocity of 2.25 m/s(7.38ft/s); with an average film temperature = t 2 – 0.8 LMTD.
Heaters | 195
100 650
125 700
1 29.44408 U
2
708.88816 BTU 1.055 kJ (3.28 ft) ℎr kW 1000W 1.8 ℉ ℃
U= × × × × × × ×
2
ℎr − ft − ℉ BTU m
2
3600 s kJ /s kW ℃ K
W
U =4 ,02 2.98 2
−K
m
From page 9-74, Fig. 9.4.24 (b), Mark’s Standard handbook for Mechanical
Engineers, 11th Edition with an average water temperature twa= tave film - LMTD.
t wa=5 4.1356 −18.223 ℃=3 5.9126℃=96.6427 ℉
0 0.96
96.6427 Correction Factor
200 1.02
W 1 kW
U =4 ,02 2.98 − K ( 0.9 89 ) ×
m
2
1000 W
kW
U =3. 979 2
−K
m
Heaters | 196
(
7,157.3531 kW =A 3. 979
kW
m
2 )
− K ( 18.223 ℃ )
2
A=98.7094 m
Where:
π 2
A s= D
4 s
OD = 2.22 cm
ID = 1.97 cm
π 2 π 2
A NT = d n= ( 0.0222 m ) ( 787 tubes )=0.3046
4 4
Then,
Heaters | 197
0.225 ( π4 D )=0.3046 m
s
2 2
Ds =1.3129 m=131.29 cm
Where:
3
m
Q=ms v f 3 =3.3485 ( 1.022 ×10 )=0.00 3422
−3
s
2
π Ds
A=
4
Thus,
2
3 π ( 0.0197 m ) V
0.00 3422 m /s=
4
m
V =11.2268
s
HEATER NO. 2
Inlet Feed Water Temperature: t 19=58.71℃
Outlet Feed Water Temperature:t 20=78.78 ℃
Temperature of condensate entering:t 4=68.84 ℃
Temperature of steam entering:t 5=88.78 ℃
Temperature of condensate leaving:t 6=88.78 ℃
Mass of condensate entering:m4 =3.3485 kg /s
Mass of steam entering: m5=2. 221 kg /s
Mass of condensate leaving:m6=5.5695 kg /s
Energy Balance:
m4 ℎ 4+ m5 ℎ5 + m19 ℎ19=m6 ℎ6 +m20 ℎ20
Q R=m4 ℎ 4 +m5 ℎ 5 − m6 ℎ6
Where,
ℎ 4=288.2087 kJ /kg
Heaters | 198
ℎ5 =2658.148 kJ /kg
ℎ6 =371.7407 kJ /kg
Q R2=4,798.4037 kW
A. Length of tube
Q R= AUθ
Where:
θ max −θmin
θ=
θ
ln max
θ min
By temp balance:
m4 t 4 +m5 t 5=m6 t wo
3.3485 ( 68.84 )+ 2.221 ( 88.78 ) =5.5695t wo
t wo =76.7917 ℃
θmax =88.78 −76.7917=11.9883℃
11.9883− 3 0.07
θ= ℃
11.9883
ln
3 0.07
θ=19.6626 ℃
From Power Plant Theory and Design by Potter (Figure 8-23) Page 373 with the
velocity of 2.25 m/s(7.38ft/s); with an average film temperature = t 5 – 0.8 LMTD.
Tℎerefore ,t ave film=88.78 − 0.8 (19.6626 ℃ )=73.0499 ℃=163.4898 ℉
175 850
1 63.4898 U
2
803.9592 BTU 1.055 kJ (3.28 ft) ℎr kW 1000 W 1.8 ℉ ℃
U= × × × × × × ×
2
ℎr − ft − ℉ BTU m 2
3600 s kJ / s kW ℃ K
W
U =4,562.5135 2
−K
m
Heaters | 199
From page 9-74, Fig. 9.4.24 (b), Mark’s Standard handbook for Mechanical
Engineers, 11th Edition with an average water temperature twa= tave film - LMTD.
t wa=73.0499− 19.6626 ℃=5 3.3873 ℃=128.0971 ℉
100 1
1 28.0971 Correction Factor
200 1.02
Correction factor=1.00 56
W 1 kW
U =4,562.5135 − K ( 1.0056 ) ×
m
2
1000 W
kW
U =4.5881 2
−K
m
(
4,562.5135 kW = A 4.5881
kW
m
2 )
− K ( 19.6626 ℃ )
2
A=50.5744 m
Heaters | 200
Where:
π 2
A s= D
4 s
OD = 2.22 cm
ID = 1.97 cm
π 2 π 2 2
A NT = d n= ( 0.0222 m ) ( 40 3 tubes ) =0.15599 m
4 4
Then,
0.225 ( π4 D )=0.15599 m
s
2 2
Where:
3
m
Q=ms v f 6 =2.221 ( 1.0 351 ×10 )=0.0023
−3
s
2
π Ds
A=
4
Thus,
2
3 π ( 0.0197 m ) V
0.0023 m /s=
4
m
V =7. 5458
s
DEAERATOR
Boiler Operating Pressure, P8 = 97.2924 kPa
Mass of condensate entering:m7=5.5695 kg /s
Mass of steam entering: m8=1.1674 kg /s
Mass of feedwater entering:m20=56.9478 kg /s
Heaters | 201
Deaerator Operating Pressure, PC = 0.972924 g
Where:
m8 = Steam mass flowrate (kg/hr)
Kv = Valve coefficient required
P8 = Pressure upstream of the control valve (bar a)
PC = Pressure downstream of the control valve (bar a)
So,
kg 3600 s kg
m8=1.1674 × =4,202.64
s 1 ℎr ℎr
¯¿
P8= ( 97.2924 kPa+101.325 kPa ) ×1 =1.9862 ā ¿
100 kPa
Thus,
kg
4,202.64 =12 K v (1.9862 ā)
ℎr
K v =170.3267
Equipment Required
● A DN80 two port valve with standard equal percentage trim (Kvs = 100)
Heaters | 202
● A pneumatic actuator able to close a DN80 valve against a pressure of
1.28719 bar.
The pump discharge pressure onto the control valve is 2 bar g. From
steam tables, the specific volume of water at 2 bar g and 87.5 ℃ is 1.0344 x 10-3
m3/kg.
It is important to determine the pressure required behind the water
distribution nozzle to give proper distribution; the control valve selection must
take this into consideration. It is assumed that a pressure of 1.8 bar is required at
the inlet to the distributor nozzle.
The sizing parameters for the water control valve are:
3
kg 3600 s −3 m
V =62.5173 × ×1.0344 ×10
s 1 ℎr kg
3
m
V =232.8044
ℎr
P = 2 bar g
Po = 1.8 bar g
Calculating Kv to determine the size of the control valve for liquid service:
V =K v
√ ∆P
G
Heaters | 203
Kv = Valve coefficient required
∆ P = Pressure drop across the valve (bar)
G = Relative density of fluid (water = 1)
So,
m3
232.8044 =K v
ℎr 1 √
2 −1.8
K v =520.5665
● Two DN150 two port valve with standard trim (Kvs = 320)
● An electric actuator that will close a DN150 valve against the maximum
● A level controller to accept the signal from the capacitance probe, and
HEATER NO. 3
Inlet Feed Water Temperature: t 22=98.94 ℃
Heaters | 204
Outlet Feed Water Temperature:t 23=127.96 ℃
Temperature of condensate entering:t 10=98.87 ℃
Temperature of steam entering:t 11=132.96 ℃
Temperature of condensate leaving:t 12=128.68℃
Mass of condensate entering:m10=6. 7369 kg/ s
Mass of steam entering: m11=3.6504 kg /s
Mass of condensate leaving:m12=10.3873 kg /s
Energy Balance:
m10 ℎ 10+ m11 ℎ11 + m22 ℎ22=m12 ℎ12 +m23 ℎ 23
Where,
ℎ10=414.3989 kJ /kg
ℎ12=540.6827 kJ /kg
Q R4=7,133.3523 kW
A. Length of tube
Q R= AUθ
Where:
θ max −θmin
θ=
θ max
ln
θ min
By temp balance:
m10 t 10+ m11 t 11 =m12 t wo
t wo =110.8502 ℃
Heaters | 205
22.1098 − 34.09
θ= ℃
22.1098
ln
34.09
θ=27.669 ℃
From Power Plant Theory and Design by Potter (Figure 8-23) Page 373 with the
velocity of 2.25 m/s(7.38ft/s); with an average film temperature = t 11 – 0.8 LMTD.
Tℎerefore ,t ave film=132.96 − 0.8 ( 27.669℃ )=1 10.8248℃=2 31.4846 ℉
250 1000
2 31.4846 U
2
925.9384 BTU 1.055 kJ (3.28 ft ) ℎr kW 1000 W 1.8 ℉ ℃
U= × × × × × × ×
2
ℎr − ft −℉ BTU m 2
3600 s kJ /s kW ℃ K
W
U =5,254.7523 2
−K
m
From page 9-74, Fig. 9.4.24 (b), Mark’s Standard handbook for Mechanical
Engineers, 11th Edition with an average water temperature twa= tave film - LMTD.
t wa=110.8248 −27.669 ℃=83.1558 ℃=181.6804 ℉
100 1
181.6804 Correction Factor
200 1.02
Correction factor=1.01 63
W 1 kW
U =5,254.7523 − K ( 1.01 63 ) ×
m
2
1000W
kW
U =5.3404 2
−K
m
(
7,133.3523 kW = A 5.3404
kW
m
2 )
− K ( 27.669 ℃ )
Heaters | 206
2
A=48.2755 m
Where:
π 2
A s= D
4 s
OD = 2.22 cm
π 2 π 2 2
A NT = d n= ( 0.0222 m ) ( 385 tubes )=0. 149 m
4 4
Then,
0.225 ( π4 D )=0.149 m
s
2 2
Ds =0.9182 m=91.82 cm
Where:
3
m
Q=ms v f 12=3.6504 ( 1.0684 ×10 )=0.00 39
−3
s
Heaters | 207
2
π Ds
A=
4
Thus,
2
3 (V ) π ( 0.0197 m )
0.00 39 m /s=
4
m
V =12.795
s
HEATER NO. 4
Inlet Feed Water Temperature: t 23=127.96 ℃
Outlet Feed Water Temperature:t 24=156.97 ℃
Temperature of condensate entering:t 13=128.79℃
Temperature of steam entering:t 14=161.98 ℃
Temperature of condensate leaving:t 15=140.51℃
Mass of condensate entering:m13=10.3873 kg /s
Mass of steam entering: m14=3.4169 kg /s
Mass of condensate leaving:m15=1 3.8041 kg/s
Energy Balance:
m13 ℎ 13+m14 ℎ14 +m23 ℎ 23=m15 ℎ15 +m24 ℎ 24
Where,
ℎ13=541.3236 kJ /kg
ℎ15=591.3188 kJ /kg
Q R5=6,964.9642 kW
A. Length of tube
Q R= AUθ
Heaters | 208
Where:
θ max −θmin
θ=
θ max
ln
θ min
By temp balance:
m13 t 13+ m14 t 14=m15 t wo
10.3873 ( 128.79 ) +3.4169 ( 161.98 )=1 3.8041 t wo
t wo =137.0064 ℃
θmax =161.98 −1 37.0064=24.9736 ℃
24.9736 − 34.02
θ= ℃
24.9736
ln
34.02
θ=29.2641℃
From Power Plant Theory and Design by Potter (Figure 8-23) Page 373 with the
velocity of 2.25 m/s(7.38ft/s); with an average film temperature = t 14 – 0.8 LMTD.
∴ t ave film =161.98− 0.8 ( 29.2641℃ )=1 38.5687 ℃=281.4237 ℉
281.4237 U
2
928.9932 BTU 1.055 kJ (3.28 ft) ℎr kW 1000W 1.8 ℉ ℃
U= × × × × × × ×
2
ℎr − ft − ℉ BTU m 2
3600 s kJ /s kW ℃ K
W
U =5 ,272.0884 2
−K
m
From page 9-74, Fig. 9.4.24 (b), Mark’s Standard handbook for Mechanical
Engineers, 11th Edition with an average water temperature twa= tave film - LMTD.
t wa=138.5687 − 29.2641℃=109.3046 ℃=228.7482℉
100 1
200 1.02
Heaters | 209
228.7482 Correction Factor
Correction factor=1.0 257
W 1 kW
U =5 ,272.0884 − K ( 1.0 257 ) ×
m
2
1000 W
kW
U =5.4076 2
−K
m
(
6,964.9642 kW =A 5 .4076
kW
m
2 )
− K (29.2641 ℃ )
2
A=44.0128 m
Where:
π 2
A s= D
4 s
OD = 2.22 cm
π 2 π 2 2
A NT = d n= ( 0.0222 m ) ( 351 tubes )=0. 1357 m
4 4
Then,
Heaters | 210
0.225 ( π4 D )=0.1357 m
s
2 2
Ds =0 .8763 m=87.63 cm
Where:
3
m
Q=ms v f 15=3.4169 ( 1.0 803 ×10 )=0.00 369
−3
s
2
π Ds
A=
4
Thus,
(V )π ( 0.0197 m )2
0.00 369 m3 /s=
4
m
V =1 2.1061
s
Heaters | 211