STD720 Spec

Download as pdf or txt
Download as pdf or txt
You are on page 1of 17

SmartLine

Technical Information

STD700 SmartLine Differential Pressure


Specification 34-ST-03-101, July 2020

Introduction

Part of the SmartLine® family of products, the STD700 is


suitable for monitoring, control and data acquisition featuring
piezoresistive sensor technology. By combining pressure
sensing with on chip temperature compensation capabilities
STD700 offers high accuracy, stability and performance over a
wide range of application pressures and temperatures. The
SmartLine family is also fully tested and compliant with
Experion® PKS providing the highest level of compatibility
assurance and integration capabilities. SmartLine easily meets
the most demanding application needs for pressure
measurement applications.
Best in Class Features:

o Accuracies up to 0.05% of span standard & 0.04% of span


optional
o Stability up to 0.02% of URL per year for 10 years
o Automatic static pressure & temperature compensation
o Rangeability up to 100:1
o Response times as fast as 100ms
o Alphanumeric display capabilities
o External zero, span, & configuration capability
o Polarity insensitive electrical connections
Figure 1 – STD700 Differential Pressure
o Comprehensive on-board diagnostic capabilities Transmitters feature field-proven piezoresistive
o Integral Dual Seal design for highest safety based on sensor technology
ANSI/NFPA 70-202 and ANSI/ISA 12.27.0
o World class overpressure protection
o Full compliance to SIL 2/3 requirements. Communications/Output Options:
o Modular design characteristics
o Honeywell Digitally Enhanced (DE)
o Available with additional 4-year warranty
o HART ® (version 7.0)
Span & Range Limits: o FOUNDATION™ Fieldbus
Model URL LRL Min Span
All transmitters are available with the above listed
“inH2O (mbar) “inH2O (mbar) “inH2O (mbar)
communications protocols.
STD720 400 (1000) -400 (1000) 4 (10)
Model psi (bar) psi (bar) psi (bar)
STD730 100 (7.0) -100 (-7.0) 1 (0.07)
STD770 3000 (210) -100 (-7.0) 30 (2.1)
2 STD700 Smart Pressure Transmitter

Description Configuration Tools


The SmartLine family pressure transmitters are designed External Three Button Configuration Option
around a high performance piezo-resistive sensor. This one Suitable for all electrical and environmental requirements,
sensor actually integrates multiple sensors linking process SmartLine offers the ability to configure the transmitter and
pressure measurement with on-board static pressure (DP display via three externally accessible buttons when a
Models) and temperature compensation measurements. display option is selected. Zero/span capabilities are also
This level of performance allows the ST 700 to replace most optionally available via these buttons with or without
competitive transmitters available today. selection of the display option.

Internal Two Button Configuration Option


Indication/Display Option
The Simple display has two buttons that can be used for
The ST 700 modular design accommodates a basic Basic configuration such as re ranging, PV Engineering unit
alphanumeric LCD display. setting, Zero/Span settings and Loop testing and calibration
functions.
Basic Alphanumeric LCD Display Features
o Modular (may be added or removed in the field) Hand Held Configuration
o 0, 90,180, & 270 degree position adjustments SmartLine transmitters feature two-way communication and
o Configurable (HART only) and standard (Pa, KPa, configuration capability between the operator and the
MPa, KGcm2, Torr, ATM, inH2O, mH2O, bar, mbar, transmitter. All Honeywell transmitters are designed and
inH2O, inHG, FTH2O, mmH2O, mm HG, & psi) tested for compliance with the offered communication
measurement units protocols and are designed to operate with any Standards
o Supports Flow engineering units compliant handheld configuration device.

o 2 Lines 16 Characters (4.13H x 1.83W mm)


o Square root output indication (√) Personal Computer Configuration
Honeywell’s SCT 3000 Configuration Toolkit provides an easy
Simple LCD Display Features way to configure Digitally Enhanced (DE) instruments using a
o Modular (may be added or removed in the field) personal computer as the configuration interface. Field Device
o Supports HART protocol variant Manager (FDM) Software and FDM Express are also
o 0, 90,180, & 270 degree position adjustments available for managing HART & Fieldbus device
configurations.
o Configurable (HART only) and standard (Pa, KPa,
MPa, KGcm2, Torr, ATM, inH2O, mH2O, bar, mbar, Modular Design
inH2O, inHG, FTH2O, mmH2O, mm HG, & psi) To help contain maintenance & inventory costs, all ST 700
measurement units. transmitters are modular in design supporting the user’s
o Supports Flow engineering units ability to replace meter bodies, add indicators or change
o 2 Lines 6 digits PV (9.95H x 4.20W mm) 8 Characters electronic modules without affecting overall performance or
o Square root output indication (√) and Write protect approval body certifications. Each meter body is uniquely
Indication characterized to provide in-tolerance performance over a wide
o Built in Basic Device Configuration through Internal range of application variations in temperature and pressure
Buttons – Range/Engineering Unit/Loop Test /Loop and due to the Honeywell advanced interface, electronic
Calibration/Zero /Span Setting modules may be swapped with any electronics module
without losing in-tolerance performance characteristics.
Diagnostics
SmartLine transmitters all offer digitally accessible Modular Features
diagnostics which aid in providing advanced warning of o Meter body replacement
possible failure events minimizing unplanned shutdowns, o Exchange/replace electronics/comms modules*
providing lower overall operational costs o Add or remove integral indicator*
o Add or remove lightning protection (terminal connection)*
System Integration
* Field replaceable in all electrical environments (including IS)
o SmartLine communications protocols all meet the most
except flameproof without violating agency approvals.
current published standards for HART/DE/Fieldbus.
o Integration with Honeywell’s Experion PKS offers the With no performance effects, Honeywell’s unique modularity
following unique advantages. results in lower inventory needs and lower overall
operating costs.
o Tamper reporting
o FDM Plant Area Views with Health summaries
o All ST 700 units are Experion tested to provide the
highest level of compatibility assurance
STD700 Smart Pressure Transmitter 3

Performance Specifications
Reference Accuracy (conformance to +/-3 Sigma)
Table 1

Reference
Maximum Stability Accuracy1,2
Model URL LRL Min Span Turndown (% URL/Year (% Span)
Ratio for 10 years) Standard/
optional
STD720 400 in H2O (1000 mbar) -400 in H2O (-1000 mbar) 4 in H2O (10 mbar) 100:1 0.020
STD730 100 psi (7.0 bar) -100 psi (-7.0 bar) 1 psi (0.07 bar) 100:1 0.020 0.05 / 0.04
STD770 3000 psi (210 bar) -100 psi (-7.0 bar) 30 psi (2.1bar) 100:1 0.020
Zero and span may be set anywhere within the listed (URL/LRL) range limits

Accuracy, Temperature and Static Pressure Effects: (Conformance to +/-3)


Table 2
Combined Zero &
Combined Zero & Span
Accuracy1,2 Span Static Line
temperature Effect
(% of Span) Pressure Effect
(% Span / 28oC (50oF))
(% Span/1000psi)
Reference C
Model URL A B D E F G
Turndown (see URL units)
400 in H2O
STD720 16:1 25 (62.5) 0.050 0.020
(1000 mbar)
Accuracy
Standard

100 psi
STD730 4:1 0.005 0.045 25 (1.75) 0.100 0.010
(7.0 bar)
0.065 0.010
3000 psi
STD740 10:1 300 (21)
(210 bar)
400 in H2O
STD720 16:1 25 (62.5) 0.050 0.020
(1000 mbar)
Accuracy
option
High

100 psi
STD730 4:1 0.005 0.035 25 (1.75) 0.100 0.010
(7.0 bar)
0.065 0.010
3000 psi
STD740 10:1 300 (21)
(210 bar)
Turn Down Effect Temp Effect Static Effect

Total Performance (% of Span):

Total Performance = +/- √(Accuracy)2 + (Temp Effect)2+ (Static Line Pressure Effect)2

Total Performance Examples (for comparison): standard accuracy, 5:1 Turndown, up to 50 oF shift & up to 1000 psi
Static Pressure
STD720 @ 80” H2O: 0.218% of span
STD730 @ 20 psi: 0.199 % of span
STD770 @ 600 psi: 0.196 % of span
Typical Calibration Frequency:
Calibration verification is recommended every two (2) years

Notes:
1. Terminal Based Accuracy – Includes combined effects of linearity, hysteresis and repeatability. Analog output adds 0.005% of span
2. For zero based spans and reference conditions of: 25oC (77oF), 0 psig static pressure, 10 to 55% RH and 316SS barrier diaphragm.
4 STD700 Smart Pressure Transmitter

Operating Conditions – All Models


Reference Rated Condition Operative Limits Transportation and
Parameter
Condition Storage
°C °F °C °F °C °F °C °F
Ambient Temperature1 25±1 77±2 -40 to 85 -40 to 185 -40 to 85 -40 to 185 -55 to 120 -67 to 248
Meter Body Temperature2 25±1 77±2 -40 to 110 -40 to 230 -40 to 125 -40 to 257 -55 to 120 -67 to 248
Humidity %RH 10 to 55 0 to 100 0 to 100 0 to 100
Vac. Region – Min. Pressure

mmHg absolute Atmospheric 25 2 (short term ) 3


inH2O absolute Atmospheric 13 1 (short term ) 3

Supply Voltage 10.8 to 42.4 Vdc at terminals (IS versions limited to 30 Vdc)
Load Resistance 0 to 1,440 ohms (as shown in Figure 2)
Maximum Allowable
Working Pressure (MAWP)4,5
(ST 700 products are rated to
Maximum Allowable Working 4,500 psi (310 bar)
Pressure. MAWP depends on
Approval Agency and transmitter
materials of construction.)
1
LCD Display operating temperature -20°C to +70°C Storage temperature -30°C to 80°C.
2
Silicone 704 minimum temperature rating is 0oC (32oF). NEOBEE® M-20 minimum temperature rating is -15oC (5oF)”.
For STD720 at temperatures below -15oC URL is reduced to 100” H2O. NEOBEE is a registered trademark of Stepan Company
3
Short term equals 2 hours at 70°C (158°F)
4
MAWP applies for temperatures -40 to 125°C. Static Pressure Limit is de-rated to 3,000 psi for -26°C to -40°C. for all models. Use of
graphite o-rings de-rates transmitter to 3,625 psi. Use of 1/2:” process adaptors with graphite o-rings de-rates transmitter to 3,000 psi.
5
Consult factory for MAWP of ST 700 transmitters with CRN approval.

Figure 2 - Supply voltage and loop resistance chart & calculations


STD700 Smart Pressure Transmitter 5

Performance Under Rated Conditions – All Models


Parameter Description
Analog Output Two-wire, 4 to 20 mA (HART & DE Transmitters only)
Digital Communications: Honeywell DE, HART 7 protocol or FOUNDATION Fieldbus ITK 6.0.1 compliant
All transmitters, irrespective of protocol have polarity insensitive connections.
HART & DE Output Failure Honeywell Standard: NAMUR NE 43
Modes Compliance:
(NAMUR for DE Units requires Normal Limits: 3.8 – 20.8 mA 3.8 – 20.5
selecting display and mA
configuration buttons or factory Failure Mode: ≤ 3.6 mA and ≥ 21.0 mA ≤ 3.6 mA and ≥
configuration) 21.0 mA
Supply Voltage Effect 0.005% span per volt.
Transmitter Turn on Time
(includes power up & test HART or DE: 2.5 sec. Foundation Fieldbus: Host dependant
algorithms)
Response Time DE/HART Analog Output FOUNDATION Fieldbus
(delay + time constant)
100mS 150mS (Host Dependant)
Damping Time Constant HART: Adjustable from 0 to 32 seconds in 0.1 increments. Default: 0.50 seconds
DE: Discrete values 0, .16, .32, .48, 1, 2, 4, 8, 16, 32 seconds. Default: 0.48 seconds
Vibration Effect Less than +/- 0.1% of URL w/o damping
Per IEC60770-1 field or pipeline, high vibration level (10-2000Hz: 0.21
displacement/3g max acceleration)
Electromagnetic Compatibility IEC 61326-3-1
Lightning Protection Option Leakage Current: 10uA max @ 42.4VDC 93C
Impulse rating: 8/20uS 5000A (>10 strikes) 10000A (1 strike min.)
10/1000uS 200A (> 300 strikes)

Materials Specifications (see model selection guide for availability/restrictions with various models)
Parameter Description
Barrier Diaphragms Material 316L SS, Hastelloy® C-2762, Monel® 400 3, Tantalum
Process Head Material 316 SS4, Carbon Steel (Zinc-plated) 5, Hastelloy C-2766
Vent/Drain Valves & Plugs 1 316 SS4, Hastelloy C-2762
Head Gaskets Glass-filled PTFE standard. Viton® and graphite are optional.
Carbon Steel (Zinc plated) standard. Options include 316 SS, NACE A286 SS bolts,
Meter Body Bolting
Monel K500, Super Duplex and B7M.
Adapter Flange materials include 316 SS, Hastelloy C-276 and Monel 400. Bolt
Optional Adapter Flange and
material for flanges is dependent on process head bolts material chosen. Standard
Bolts
adaptor seal material is glass-filled PTFE. Viton and graphite are optional.
Mounting Bracket 2” Pipe, Carbon Steel (Zinc-plated) or 304 Stainless Steel or 316 Stainless Steel
Fill Fluid Silicone 200 , CTFE, NEOBEE M-20 or Silicone 704
Pure Polyester Powder Coated Low Copper (<0.4%)-Aluminum. Meets NEMA 4X,
Electronic Housing
IP66, & IP67. All stainless steel housing is optional.
Can be mounted in virtually any position using the standard mounting bracket. Bracket
Mounting
is designed to mount on 2-inch (50 mm) vertical or horizontal pipe. See Figure 3.
Process Connections 1/4- NPT or 1/2- NPT with adapter (meets DIN requirements)
Wiring Accepts up to 16 AWG (1.5 mm diameter).
Dimensions See Figure 4.
Net Weight 8.3 pounds (3.8 Kg) with Aluminum Housing.
1 2
Vent/Drains are sealed with Teflon® Hastelloy C-276 or UNS N10276
3 4
Monel 400 or UNS N04400 Supplied as 316 SS or as Grade CF8M, the casting equivalent of 316 SS.
5
Carbon Steel heads are zinc-plated and not recommended for water service due to hydrogen migration. For that service, use 316 stainless steel wetted
Process Heads.
6
Hastelloy C-276 or UNS N10276. Supplied as indicated or as Grade CW12MW, the casting equivalent of Hastelloy C-276
6 STD700 Smart Pressure Transmitter

Communications Protocols & Diagnostics

HART Protocol
Software Download
Version: Utilizes Class-3 of the Common Software Download
HART 7 procedure as per FF-883 which allows the field devices of any
Power Supply manufacturer to receive software upgrades from any host.
Voltage: 10.8 to 42.4Vdc at terminals Honeywell Digitally Enhanced (DE)
Load: Maximum 1440 ohms See Figure 2 DE is a Honeywell proprietary protocol which provides digital
Minimum Load: 0 ohms. (For handheld communications a communications between Honeywell DE enabled field
minimum load of 250 ohms is required) devices and Hosts.
Foundation Fieldbus (FF) Power Supply
Power Supply Requirements Voltage: 10.8 to 42.4Vdc at terminals
Voltage: 9.0 to 32.0Vdc at terminals Load: Maximum 1440 ohms See figure 2
Steady State Current: 17.6mAdc Standard Diagnostics
Software Download Current: 27.4mAdc ST 700 top level diagnostics are reported as either critical
Available Function Blocks or non-critical and readable via the DD/DTM tools or
Block Type Qty Execution Time integral display as shown below.
Critical Diagnostics
Resource 1 n/a HART DD/DTM Tools Basic Display Simple Display
Transducer 1 n/a Electronic Module Electronics module fault Fault Comm El
DAC Failure
Diagnostic 1 n/a
Meter Body NVM Meter Body fault Fault Mtrbody
Analog Input 1* 30 ms Corrupt
Config. Data Corrupt Electronics module fault Fault Comm El
PID w/Autotune 1 45 ms
Electronic Module Electronics module fault Fault Comm El
Integrator 1 30 ms Diag Failure
Meter Body Critical Meter Body fault Fault Mtrbody
Signal Char (SC) 1 30 ms Failure
LCD Display 1 n/a Sensor Comms Meter Body Comm fault Fault Mbd Com
Timeout
Flow Block 1 30 ms
Non-Critical Diagnostics
Input Selector 1 30 ms
HART DD/DTM Tools
Arithmetic 1 30 ms Display Failure
* AI block may have two (2) additional instantiations. Electronic Module Comm Failure
All available function blocks adhere to FOUNDATION Meter Body Excess Correct
Fieldbus standards. PID blocks support ideal & robust PID Sensor Over Temperature
algorithms with full implementation of Auto-tuning. Fixed Current Mode

Link Active Scheduler PV Out of Range

Transmitters can perform as a backup Link Active No Factory Calibration

Scheduler and take over when the host is disconnected. No DAC Compensation
LRV Set Error – Zero Config. Button
Acting as a LAS, the device ensures scheduled data
URV Set Error – Zero Config. Button
transfers typically used for the regular, cyclic transfer of
AO Out of Range
control loop data between devices on the Fieldbus.
Loop Current Noise
Number of Devices/Segment
Meter Body Unreliable Comm
Entity IS model: 6 devices/segment
Tamper Alarm,
Schedule Entries No DAC Calibration
18 maximum schedule entries Sensor Supply Voltage Low

Number of VCR’s: 24 max Refer to ST 700 manuals for additional level diagnostic
Compliance Testing: Tested according to ITK 6.0.1 information
STD700 Smart Pressure Transmitter 7

Hazardous Areal Certifications:

MSG COMM. ELECTRICAL AMBIENT TEMP


AGENCY TYPE OF PROTECTION
CODE OPTION PARAMETERS (Ta)
Explosionproof:
Class I, Division 1, Groups A, B, C, D;
Dust Ignition Proof:
T5: -50 ºC to 85ºC
Class II, III, Division 1, Groups E, F, G; All Note 1
T6: -50 ºC to 65ºC
T6..T5
Class l, Zone 0/1, AEx db IIC T6..T5 Ga/Gb
Class ll, Zone 21, AEx tb IIIC T95o Db
Intrinsically Safe: 4-20 mA /
Class I, II, III, Division 1, Groups A, B, C, D, Note 2a -50 ºC to 70ºC
DE/ HART
E, F, G: T4
FM Class l, Zone 0, AEx ia IIC T4 Ga Foundation -50 ºC to 70ºC
A ApprovalsTM FISCO Field Device (Only for FF Option) Note 2b
Fieldbus
USA Ex ia IIC T4 Ga; Ex ic IIC T4 Gc
Nonincendive: 4-20 mA /
Class I, Division 2, Groups A, B, C, D DE/ HART/
Note 1 -50 ºC to 85ºC
locations, T4 Foundation
Class l, Zone 2, AEx nA IIC T4 Gc Fieldbus
Enclosure: Type 4X/ IP66/ IP67 All All -
STANDARDS: FM Class 3600:2011; FM Class 3610: 2010; FM Class 3611: 2004; FM Class
3615: 2006; FM Class 3616: 2011; FM Class 3810: 2005; ANSI/ISA 60079-0: 2013; ANSI/UL
60079-1: 2015; ANSI/UL 60079-11: 2014; ANSI/ISA 60079-15: 2012; ANSI/UL 60079-26: 2017;
ANSI/UL 60079-31: 2015; ANSI/NEMA 250: 2003; ANSI/ IEC 60529: 2004
Explosion Proof:
Class I, Division 1, Groups A, B, C, D;
Class II, Division 1, Groups E, F, G;
Class III, Division 1, T6..T5 T5: -50oC TO 85oC
All Note 1
Class I Zone 1 AEx db IIC T6..T5 Ga/Gb T6: -50oC TO 65oC
Ex db IIC T6..T5 Ga/Gb
Zone 22 AEx tb IIIC T95o Db
Ex tb IIIC T95o Db
Intrinsically Safe:
Class I, II, III, Division 1, Groups A, B, C, D; 4-20 mA /
Note 2 -50oC TO 70oC
Canadian Class II, Division 1, Groups E, F, G; DE/ HART
Standards Class III, Division 1, T4
Association Class I Zone 0, AEx ia IIC T4 Ga
B Class I Zone 2, AEx ic IIC T4 Gc
(CSA)
USA and Ex ia IIC T4 Ga
Foundation -50oC TO 70oC
Canada Ex ic IIC T4 Gc Note 2
Fieldbus
FISCO Field Device (Only for FF Option)
Ex ia IIC T4 Ga;
Ex ic IIC T4 Gc
Nonincendive:
Class I, Division 2, Groups A, B, C, D; 4-20 mA /
Class II, Division 2, Groups F, G; DE/ HART/
Note 1 -50oC to 85oC
Class III, Division 2, T4 Foundation
Class I Zone 2 AEx nA IIC T4 Gc Fieldbus
Ex nA IIC T4 Gc
Enclosure: Type 4X/ IP66/ IP67 All All -
MSG COMM. ELECTRICAL AMBIENT TEMP
AGENCY TYPE OF PROTECTION
CODE OPTION PARAMETERS (Ta)
STANDARDS: CSA C22.2 No. 0-10; CSA C22.2 No. 94-M91; CSA C22.2 No. 25-1966; CSA C22.2
No. 30-M1986; CSA C22.2 No. 142-M1987; CSA C22.2 No. 157-92; CSA C22.2 No. 213-M1987;
CSA-C22.2 No. 60529:05; CSA-C22.2 No. 60079-0:11; CSA-C22.2 No. 60079-1:11; CSA-C22.2
No. 60079-11:11; CSA-C22.2 No. 60079-15:12; CSA-C22.2 No. 60079-31:12; ISA 12.12.01-
2010; ISA 60079-0: 2009; ISA 60079-11: 2011; ISA 60079-15: 2009; ISA 60079-26: 2008; ISA-
60079-27:2007 (12.02.04)-2006 (R2011); UL 913 Ed. 6; UL 916:1998; ANSI/ISA-12.27.01-2011
Flameproof: SIRA 12ATEX2233X
T5: -50oC TO 85oC
II 1/2 G Ex db IIC T6..T5 Ga/Gb All Note 1
T6: -50oC TO 65oC
II 2 D Ex tb IIIC T95oC…T120oC Db
Intrinsically Safe: SIRA 12ATEX2233X 4-20 mA / DE/
Note 2 -50oC TO 70oC
II 1 G Ex ia IIC T4 Ga HART
FISCO Field Device (Only for FF Option) Foundation
II 1 G Ex ia IIC T4 Ga Note 2 -50oC TO 70oC
Fieldbus
Zone 2, Increase Safety: SIRA
4-20 mA / DE/
12ATEX4234X Note 1 -50oC TO 85oC
C ATEX HART/
II 3 G Ex ec IIC T4 Gc
Zone 2, Intrinsically Safe: SIRA
4-20 mA / DE/
12ATEX4234X
HART/
II 3 G Ex ic IIC T4 Gc Note 2 -50oC TO 85oC
Foundation
FISCO Field Device (Only for FF Option)
Fieldbus
II 3 G Ex ic IIC T4 Gc
Enclosure: IP66/ IP67 All All -
STANDARDS: EN 60079-0: 2012/A11: 2013; EN 60079-1: 2014; EN 60079-7: 2015; EN 60079-
11: 2012; EN 60079-26: 2015; EN 60079-31: 2009
Flameproof: IECEx SIR 12.0100X
T5: -50oC TO 85oC
Ex db IIC T6..T5 Ga/Gb All Note 1
T6: -50oC TO 65oC
Ex tb IIIC T95oC…T120oC Db
Intrinsically Safe: IECEx SIR 12.0100X 4-20 mA / DE/
Note 2 -50oC TO 70oC
Ex ia IIC T4 Ga HART
FISCO Field Device (Only for FF Option) Foundation
Ex ia IIC T4 Ga; Ex ic IIC T4 Gc Note 2 -50oC TO 70oC
Fieldbus
Zone 2, Increase Safety: IECEx SIR 4-20 mA / DE/
12.0100X HART/
IECEx Note 1 -50oC TO 85oC
D Ex ec IIC T4 Gc Foundation
World
Fieldbus
Zone 2, Intrinsically Safe: IECEx SIR
4-20 mA / DE/
12.0100X
HART/
Ex ic IIC T4 Gc Note 2 -50oC TO 85oC
Foundation
FISCO Field Device (Only for FF Option)
Fieldbus
Ex ic IIC T4 Gc
Enclosure: IP66/ IP67 All All -
STANDARDS: IEC 60079-0: 2011; IEC 60079-1: 2014; IEC 60079-7: 2017; IEC 60079-11: 2011;
IEC 60079-26: 2014; IEC 60079-31: 2013
Flameproof :
T5: -50oC TO 85oC
Ex d IIC T6…T5 Ga/Gb All Note 1
T6: -50oC TO 65oC
Ex tb IIIC T95oC…T120oC Db
Intrinsically Safe: 4-20 mA / DE/
Note 2 -50oC TO 70oC
Ex ia IIC Ga T4 HART
FISCO Field Device (Only for FF Option) Foundation
Ex ia IIC T4 Ga; Ex ic IIC T4 Gc Note 2 -50oC TO 70oC
Fieldbus
SAEx Zone 2, Increase Safety: 4-20 mA / DE/
E
South Africa II 3 G Ex ec IIC T4 Gc HART/
Note 1 -50oC TO 85oC
Foundation
Fieldbus
Zone 2, Intrinsically Safe: 4-20 mA / DE/
Ex ic IIC T4 Gc HART/
Note 2 -50oC TO 85oC
FISCO Field Device (Only for FF Option) Foundation
Ex ic IIC T4 Gc Fieldbus
Enclosure: IP66/ IP67 All All -
Flameproof:
T5: -50oC TO 85oC
Ex db IIC T6..T5 Ga/Gb All Note 1
T6: -50oC TO 65oC
Ex tb IIIC T95oC…T120oC Db
Intrinsically Safe: 4-20 mA / DE/
Note 2a -50oC TO 70oC
Ex ia IIC T4 Ga HART

FISCO Field Device (Only for FF Option) Foundation


Note 2b -50oC TO 70oC
Ex ia IIC T4 Ga; Ex ic IIC T4 Gc Fieldbus
INMETRO
F Brazil Zone 2, Increase Safety: 4-20 mA / DE/
II 3 G Ex ec IIC T4 Gc HART/
Note 1 -50oC TO 85oC
Foundation
Fieldbus
Zone 2, Intrinsically Safe: 4-20 mA / DE/
Ex ic IIC T4 Gc HART/
Note 2 -50oC TO 85oC
FISCO Field Device (Only for FF Option) Foundation
Ex ic IIC T4 Gc Fieldbus
Enclosure : IP 66/67 All All -
Flameproof:
T5: -50oC TO 85oC
Ex db IIC T6..T5 Ga/Gb All Note 1
T6: -50oC TO 65oC
Ex tb IIIC T 95oC Db
Intrinsically Safe: 4-20 mA / DE/
Note 2 -50oC TO 70oC
Ex ia IIC T4 Ga HART
FISCO Field Device (Only for FF Option) Foundation
Ex ia IIC T4 Ga; Ex ic IIC T4 Gc Note 2 -50oC TO 70oC
Fieldbus
NEPSI Zone 2, Increase Safety: 4-20 mA / DE/
G
CHINA II 3 G Ex ec IIC T4 Gc HART/
Note 1 -50oC TO 85oC
Foundation
Fieldbus
Zone 2, Intrinsically Safe: 4-20 mA / DE/
Ex ic IIC T4 Gc HART/
Note 2 -50oC TO 85oC
FISCO Field Device (Only for FF Option) Foundation
Ex ic IIC T4 Gc Fieldbus
Enclosure : IP 66/67 All All -
Flameproof : T4: -50oC TO 85oC
Ex d IIC T4, T5, T6 All Note 1 T5: -50oC TO 85oC
Ex tD A21 IP66/IP67 T95oC…T120 oC T6: -50oC TO 65oC
KOSHA 4-20 mA /
H Note 2 Ta= -50 ºC to 70ºC
Korea Intrinsically Safe: DE/ HART
Ex ia IIC T4 Foundation Ta= -50 ºC to 70ºC
Note 2
Fieldbus
Enclosure: IP66/ IP67 All All -
Flameproof:
T5: -50oC TO 85oC
Ga/Gb Ex d IIC T6..T5 All Note 1
T6: -50oC TO 65oC
Ex tb IIIC Db T 85oC
Intrinsically Safe: 4-20 mA /
Note 2 -50oC TO 70oC
Ga Ex ia IIC T4 X DE/ HART
FISCO Field Device
(Only for FF Option) Foundation
Note 2 -50oC TO 70oC
EAC Ga Ex ia IIC T4 X Fieldbus
Russia, Belarus
Zone 2, Non Sparking: 4-20 mA /
I and
2 Ex nA IIC T4 Gc X DE/ HART/
Kazakhstan Note 1 -50oC TO 85oC
Foundation
Fieldbus
Zone 2, Intrinsically Safe:
4-20 mA /
Ga Ex ic IIC T4 X
DE/ HART/
FISCO Field Device Note 2 -50oC TO 85oC
Foundation
(Only for FF Option)
Fieldbus
2 Ex ic IIC T4 Gc X
Enclosure : IP 66/67 All All
Flameproof: T5: -50oC TO 85oC
All Note 1
Ex d IIC T6..T5 Ga/Gb T6: -50oC TO 65oC
Intrinsically Safe: 4-20 mA / DE/
Note 2 -50oC TO 70oC
Ex ia IIC T4 Ga HART
FISCO Field Device (Only for FF Option) Foundation
CCoE Ex ia IIC T4 Ga; Ex ic IIC T4 Gc Note 2 -50oC TO 70oC
J Fieldbus
INDIA
Non Sparking 4-20 mA / DE/
Ex nA IIC T4 Gc HART/
Note 1 -50oC TO 85oC
Foundation
Fieldbus
Enclosure: IP66/ IP67 All All -
Flameproof:
T5: -50oC TO 85oC
II 1/2 G Ex db IIC T6..T5 Ga/Gb All Note 1
T6: -50oC TO 65oC
II 2 D Ex tb IIIC T95oC…T120oC Db
UATR Intrinsically Safe: 4-20 mA / DE/
K Note 2 -50oC TO 70oC
UKRAINE II 1 G Ex ia IIC T4 Ga HART
FISCO Field Device (Only for FF Option) Foundation
II 1 G Ex ia IIC T4 Ga Note 2 -50oC TO 70oC
Fieldbus
Enclosure: IP66/ IP67 All All -
Notes:
1. Operating Parameters:
Voltage= 11 to 42 V DC Current= 4-20 mA Normal
= 10 to 30 V (FF) = 30 mA (FF)
2. Intrinsically Safe Entity Parameters
a. Analog/ DE/ HART Entity Values:
Vmax= Ui = 30V Imax= Ii= 105mA Ci = 4.2nF Li =984 uH Pi =0.9W
Transmitter with Terminal Block Revision E or Later
Vmax= Ui = 30V Imax= Ii= 225mA Ci = 4.2nF Li = 0 Pi =0.9W
Note : Transmitter with Terminal Block Revision E or later
The revision is on the label that is on the module. There will be two lines of text on the label:
• First is the Module Part #: 50049839-001 or 50049839-002
• Second line has the supplier information, along with the REVISION:
XXXXXXX-EXXXX, THE “X” is production related, THE POSITION of the “E” IS THE REVISION.
b. Foundation Fieldbus- Entity Values
Vmax= Ui = 30V Imax= Ii= 180mA Ci = 0nF Li = 984 uH Pi =1W

Transmitter with Terminal Block Revision F or Later


Vmax= Ui = 30V Imax= Ii= 225mA Ci =0nF Li = 0 Pi =1 W
FISCO Field Device
Vmax= Ui = 17.5V Imax= Ii= 380 mA Ci = 0nF Li = 0 Pi =5.32 W
Note : Transmitter with Terminal Block Revision F or later
The revision is on the label that is on the module. There will be two lines of text on the label:
• First is the Module Part #: 50049839-003 or 50049839-004
• Second line has the supplier information, along with the REVISION:
XXXXXXX-EXXXX, THE “X” is production related, THE POSITION of the “E” IS THE REVISION.

Approval Certifications:
This certificate defines the certifications covered for the ST 800 Pressure Transmitter family of
products, including the SMV 800 Smart Multivariable Transmitter. It represents the compilation of
the five certificates Honeywell currently has covering the certification of these products into marine
applications.

For SmartLine Pressure Transmitter and SMV800 Smart Multivarible Transmitter

Marine Certificates American Bureau of Shipping (ABS) - 2009 Steel Vessel Rules 1-1-4/3.7, 4-6-2/5.15, 4-8-3/13 &
13.5, 4-8-4/27.5.1, 4-9-7/13. Certificate number: 04-HS417416-PDA

Bureau Veritas (BV) - Product Code: 389:1H. Certificate number: 12660/B0 BV


Det Norske Veritas (DNV) - Location Classes: Temperature D, Humidity B, Vibration A, EMC B,
Enclosure C. For salt spray exposure; enclosure of 316 SST or 2-part epoxy protection with 316
SST bolts to be applied. Certificate number: A-11476
Korean Register of Shipping (KR) - Certificate number: LOX17743-AE001
Lloyd's Register (LR) - Certificate number: 02/60001(E1) & (E2)
SIL 2/3 Certification IEC 61508 SIL 2 for non-redundant use and SIL 3 for redundant use according to EXIDA and TÜV
Nord Sys Tec GmbH & Co. KG under the following standards: IEC61508-1: 2010; IEC 61508-2:
2010; IEC61508-3: 2010.

Other Certification Options


Materials
o NACE MRO175, MRO103, ISO15156
Mounting & Dimensional Drawings
millimeters
Reference Dimensions: inches

Mounting Configurations

Figure 3 – Typical mounting configurations of STD720, STD730 & STD770 for reference only

Dimensions

Figure 4 – Typical mounting dimensions of STD720, STD730 & STD770 for reference only
Model Selection Guide
Model Selection Guides are subject to change and are inserted into the specifications as guidance only.

Model STD700
Differential Pressure Transmitter
Model Selection Guide:
34-ST-16-101 Issue 26

Instructions: Make selections from all Tables: Key through XIII using column below the proper arrow. Asterisk indicates
availability. Letter (a) refer to restrictions highlighted in the restrictions table. Tables delimited w ith dashes.

KEY NUMBER URL LRL Max Span Min Span Units Selection Availability
400/(1000) -400/(-1000) 400/(1000) 4.0 (10) " H2O (mbar) STD720
a. Measurement
100 (7.0) -100 (-7.0) 100 (7.0) 1 (0.07) psi (bar) STD730
Range
3000 (210) -100 (-7.0) 3000 (210) 30 (2.1) psi (bar) STD770

TABLE I METER BODY SELECTIONS


Process Head Material Diaphragm Material
316L Stainless Steel A_ _ _ _ _ _ * * *
Hastelloy® C-276 B______ * * *
Plated Carbon Steel
Monel® 400 C______ * * *
a. Process Tantalum D______ a a a
Wetted Heads & 316L Stainless Steel E______ * * *
Diaphragm Hastelloy C-276 F______ * * *
316 Stainless Steel
Materials Monel 400 G______ * * *
Tantalum H______ a a a
Hastelloy C-276 J______ * * *
Hastelloy C-276
Tantalum K______ a a a
Monel 400 Monel® 400 L______ a a a
Silicone Oil 200 _1_____ * * *
Fluorinated Oil CTFE _2_____ * * *
b. Fill Fluid
Silicone Oil 704 _3_____ * * *
NEOBEE® M-20 _4_____ * * *
c. Process None None (1/4" NPTF female thread Std) _ _ A_ _ _ _ ** *
Connection 1/2" NPT female Materials to Match Head & Head Bolt Materials Selections 1 __H____ ** *
Carbon Steel ___C___ * * *
316 SS ___S___ * * *
Grade 660 (NACE A286) with NACE 304 SS Nuts ___N___ * * *
d. Bolt/Nut
Grade 660 (NACE A286) Bolts & Nuts ___K___ p p p
Materials
Monel K500 _ _ _ M_ _ _ p p p
Super Duplex ___D___ p p p
B7M ___B___ * * *
Head Type Vent Type Location Vent Material
Single Ended None None None ____1__ * * *
Single Ended Standard Vent Side Matches Head Material 1 ____2__ * * *
e. Vent/Drain
Single Ended Center Vent Side Stainless Steel Only ____3__ t t t
Type/Location 1
Dual Ended Standard Vent End Matches Head Material ____4__ * * *
Dual Ended Center Vent End Stainless Steel Only ____5__ t t t
1
Dual Ended Std Vent/Plug Side/End Matches Head Material ____6__ * * *
Teflon® or PTFE (Glass Filled) _ _ _ _ _ A_ * * *
f. Gasket ®
Viton or Fluorocarbon Elastomer _____B_ * * *
Material
Graphite _____C_ * * *
g. Static
Standard Static Pressure - 4500 psig (315 bar) _ _ _ _ _ _S * * *
Pressure

1
Except Carbon Steel Heads shall use 316SS Vent/Drain, Plugs & Adapters w hen required
1 2 3

STD770
STD730
H L L H H 90o L STD720

TABLE II Meter Body & Connection Orientation


Standard High Side Left, Low Side Right2 / Std Head Orientation 1 * * *
Head/Connect 2
Reversed Low Side Left, High Side Right / Std Head Orientation 2 * * *
Orientation
90/Standard High Side Left, Low Side Right2 / 900 Head Rotation 3 h h h

TABLE III Agency Approvals (see data sheet for Approval Code Details)
No Approvals Required 0 * * *
FM Explosion proof, Intrinsically Safe, Non-incendive, & Dustproof A * * *
CSA Explosion proof, Intrinsically Safe, Non-incendive, & Dustproof B * * *
ATEX Explosion proof, Intrinsically Safe & Non-incendive C * * *
IECEx Explosion proof, Intrinsically Safe & Non-incendive D * * *
SAEx Explosion proof, Intrinsically Safe & Non-incendive E * * *
Approvals INMETRO Explosion proof, Intrinsically Safe & Non-incendive F * * *
NEPSI Explosion proof, Intrinsically Safe & Non-incendive G * * *
KOSHA Explosion proof, Intrinsically Safe & Non-incendive H * * *
EAC Customs Union (Russia,Belarus,Kazakhstan) Ex Approval Flame proof, Intrinsically Safe I * * *
ATEX/IECEx Explosion proof, Intrinsically Safe & Non-incendive 1 * * *
CCoE Explosion proof, Intrinsically Safe & Non-incendive J * * *
UATR Flameproof, Intrinsically Safe & Dustproof K * * *

TABLE IV TRANSMITTER ELECTRONICS SELECTIONS


Material Connection Lightning Protection
Polyester Powder Coated Aluminum 1/2 NPT None A_ _ * * *
Polyester Powder Coated Aluminum M20 None B__ * * *
a. Electronic
Polyester Powder Coated Aluminum 1/2 NPT Yes C__ * * *
Housing Material
Polyester Powder Coated Aluminum M20 Yes D__ * * *
& Connection
316 Stainless Steel (Grade CF8M) 1/2 NPT None E__ * * *
Type
316 Stainless Steel (Grade CF8M) M20 None F__ * * *
316 Stainless Steel (Grade CF8M) 1/2 NPT Yes G__ * * *
316 Stainless Steel (Grade CF8M) M20 Yes H__ * * *
Analog Output Digital Protocol
b. Output/ 4-20mA dc HART Protocol _H_ * * *
Protocol 4-20mA dc DE Protocol _D_ * * *
n/a Foundation Fieldbus _F_ * * *
Indicator Ext Zero, Span & Config Buttons Languages
None None None __0 * * *
None Yes (Zero/Span Only) None __A f f f
c. Customer
Basic None English __B * * *
Interface
Basic Yes English __C * * *
Selections
Standard (w/internal
Zero, Span & Conf None English __D u u u
Buttons)

TABLE V CONFIGURATION SELECTIONS


a. Application Diagnostics
Software Standard Diagnostics 1__ * * *
Write Protect Fail Mode High & Low Output Lim its 3
b. Output Limit, Disabled High> 21.0mAdc Honeywell Std (3.8 - 20.8 mAdc) _1_ f f f
Failsafe & Write Disabled Low< 3.6mAdc Honeywell Std (3.8 - 20.8 mAdc) _2_ f f f
Protect Settings Enabled High> 21.0mAdc Honeywell Std (3.8 - 20.8 mAdc) _3_ f f f
Enabled Low< 3.6mAdc Honeywell Std (3.8 - 20.8 mAdc) _4_ f f f
Enabled N/A N/A Fieldbus _5_ g g g
Disabled N/A N/A Fieldbus _6_ g g g
c. General Factory Standard __S * * *
Configuration Custom Configuration (Unit Data Required from customer) __C * * *
2
Left side/Right side as view ed from the customer connection perspective
3
NAMUR Output Limits 3.8 - 20.5mAdc can be configured by the customer or select custom configuration Table Vc
STD770
STD730
STD720
TABLE VI CALIBRATION & ACCURACY SELECTIONS
Accuracy Calibrated Range Calibration Qty
Standard Factory Std Single Calibration A * * *
a. Accuracy and
Standard Custom (Unit Data Required) Single Calibration B * * *
Calibration
High Accuracy Factory Std Single Calibration E s s s
High Accuracy Custom (Unit Data Required) Single Calibration F s s s

TABLE VII ACCESSORY SELECTIONS


Bracket Type Material
None None 0___ * * *
Angle Bracket Carbon Steel 1___ * * *
Angle Bracket 304 SS 2___ * * *
a. Mounting Angle Bracket 316 SS 3___ * * *
Bracket Marine Approved Bracket Carbon Steel 8___ * * *
Marine Approved Bracket 304 SS 4___ * * *
Flat Bracket Carbon Steel 5___ * * *
Flat Bracket 304 SS 6___ * * *
Flat Bracket 316 SS 7___ * * *
Custom er Tag Type
b. Customer No customer tag _0__ * * *
Tag One Wired Stainless Steel Tag (Up to 4 lines 26 char/line) _1__ * * *
Two Wired Stainless Steel Tag (Up to 4 lines 26 char/line) _2__ * * *
Unassem bled Conduit Plugs & Adapters
No Conduit Plugs or Adapters Required _ _ A0 * * *
c. Unassembled
1/2 NPT Male to 3/4 NPT Female 316 SS Certified Conduit Adapter _ _ A2 n n n
Conduit
1/2 NPT 316 SS Certified Conduit Plug _ _ A6 n n n
Plugs &
M20 316 SS Certified Conduit Plug _ _ A7 m m m
Adapters ®
Minifast 4 pin (1/2 NPT) (not suitable for X-Proof applications) _ _ A8 n n n
Minifast® 4 pin (M20) (not suitable for X-Proof applications) _ _ A9 m m m

TABLE VIII OTHER Certifications & Options: (String in sequence com m a delim ited (XX, XX, XX,….)
None - No additional options 00 * * *
NACE MR0175; MR0103; ISO15156 (FC33338) Process wetted parts only FG * * *
b
NACE MR0175; MR0103; ISO15156 (FC33339) Process wetted and non-wetted parts F7 c c c
Marine (DNV, ABS, BV, KR, LR) MT d d d
EN10204 Type 3.1 Material Traceability (FC33341) FX * * *
Certificate of Conformance (F3391) F3 * * *
b
Calibration Test Report & Certificate of Conformance (F3399) F1 * * *
Certifications & Certificate of Origin (F0195) F5 * * *
Warranty FMEDA (SIL 2/3) Certification (FC33337) FE j j j
Over-Pressure Leak Test Certificate (1.5X MAWP) (F3392) TP * * *
Cert Clean for O2 or CL2 service per ASTM G93 OX e e e
PMI Certification1 PM * * *
Extended Warranty Additional 1 year 01 * * *
Extended Warranty Additional 2 years 02 * * *
b
Extended Warranty Additional 3 years 03 * * *
Extended Warranty Additional 4 years 04 * * *

TABLE IX Manufacturing Specials


Factory Factory Identification 0000 * * *
MODEL RESTRICTIONS
Available Only with Not Available with
Restriction Letter
Table Selection(s) Table Selection(s)
a VIII F7, FG
c 1d _ _ _ N,K,D,B _ _ _ Ia D,H,K,L _ _ _ _ _ _
d IV a C, D,G,H _ _ VIIa 1,2,3,5,6,7 _ _ _
e Ib _2_____
f IVb _F_
g IVb _ H, D _
Ie _ _ _ _ 4, 5, 6_ _
h
VIIa 1,2,3,4,5,6,7,8 _ _ _
j IVb _H_ Vb _ 1,2,6 _
m IV a B, D, F, H _ _
n IV a A, C, E, G _ _
p III B- No CRN number available
s Ia A, E _ _ _ _ _ _
t Ia J, K, L _ _ _ _ _ _
u IVb _H_
b Select only one option from this group
1
The PM option is available on all Smartline Pressure Transmitter process wetted parts such as process heads, flanges, bushings and vent
plugs except plated carbon steel process heads and flanges. PM option information is also available on diaphragms except STG and STA in-
line construction pressure transmitters.

FIELD INSTALLABLE REPLACEMENT PARTS


Description Kit Number
Integrally Mounted Basic Indicator Kit (Compatible with all Electronic Modules) 50049911-501
Terminal Strip w/Lightning Protection Kit for HART or DE Modules 50075472-532
Terminal Strip w/Lightning Protection Kit for FFB Module 50075472-534
Terminal Strip w/o Lightening Protection for HART or DE Modules 50075472-533
Terminal Strip w/o Lightening Protection FFB Module 50075472-531
HART Electronics Module 50049849-501
HART Electronics Module w/connection for external configuration buttons 50049849-502
DE Electronics Module 50049849-503
DE Electronics Module w/connection for external configuration buttons 50049849-504
FFB Electronics Module Kit 50049849-509
FFB Electronics Module w/connection for external configuration buttons 50049849-510
Standard Display Module 50126003-501

PRODUCT MANUALS
Description Part Number
Product Manual ST 700 Smart Transmitter User Manual - English 34-ST-25-44
Product Manual ST 700 Smart Transmitter HART/DE Communications Manual - English 34-ST-25-47
Product Manual ST 700 Smart Transmitter Safety Manual - English 34-ST-25-37
Product Manual ST 700 Smart Transmitter Foundation Fieldbus Manual - English 34-ST-25-48
Product Manual ST 700 Smart Transmitter Function Block Manual - English 34-ST-25-49
All product documentation is available at www.honeywellprocess.com.
Sales and Service
For application assistance, current specifications, ordering, pricing, and name of the nearest Authorized Distributor,
contact one of the offices below.

ASIA PACIFIC EMEA AMERICAS


Honeywell Process Solutions, Honeywell Process Solutions, Honeywell Process Solutions,
Phone: + 800 12026455 or Phone: + 800 12026455 or Phone: (TAC) (800) 423-9883
+44 (0) 1202645583 +44 (0) 1202645583 or (215) 641-3610
(TAC) hfs-tac- (Sales) 1-800-343-0228
support@honeywell.com
Email: (Sales) Email: (Sales)
Australia
FP-Sales-Apps@Honeywell.com FP-Sales-Apps@Honeywell.com
Honeywell Limited
Phone: +(61) 7-3846 1255 or or
FAX: +(61) 7-3840 6481 (TAC) (TAC)
Toll Free 1300-36-39-36 hfs-tac-support@honeywell.com hfs-tac-support@honeywell.com
Toll Free Fax:
1300-36-04-70

China – PRC - Shanghai Web Web


Honeywell China Inc. Knowledge Base search Knowledge Base search
Phone: (86-21) 5257-4568 engine http://bit.ly/2N5Vldi engine http://bit.ly/2N5Vldi
Fax: (86-21) 6237-2826

Singapore
Honeywell Pte Ltd.
Phone: +(65) 6580 3278
Fax: +(65) 6445-3033

South Korea
Honeywell Korea Co Ltd
Phone: +(822) 799 6114
Fax: +(822) 792 9015

Specifications are subject to change without notice.

For more information


To learn more about SmartLine Pressure
Transmitters visit www.honeywellprocess.com
Or contact your Honeywell Account Manager

Process Solutions
Honeywell
1250 W Sam Houston Pkwy S
Houston, TX 77042

Honeywell Control Systems Ltd


Honeywell House, Skimped Hill Lane
Bracknell, England, RG12 1EB

Shanghai City Centre, 100 Jungi Road


Shanghai, China 20061
34-ST-03-101
July 2020
www.honeywellprocess.com 2020 Honeywell International Inc.

You might also like