Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Value Engineering

Download as pdf or txt
Download as pdf or txt
You are on page 1of 103

TUESDAY, OCTOBER 13, 2020

ABB Value Engineering Session


ABB/ECG UTW12
Dr. Wael El-Mamlouk, ECG Deputy Manager, Electrical Department
Eng. Ashraf AbouelHoda, Product Marketing Director-Smart Power
Eng. Amr Younis, ABB Technical and Design Promotion Manager

LV Switchboard
Short Circuit Calculations
MV & LV Transformer Substations
Theory & Short Circuit Calculations

IEC Standard for Short-circuit calculation : IEC 60909-0

– Short-circuit : “Accidental or intentional conductive path between two or more conductive parts forcing the electric potential
differences between these conductive parts to be equal or close to zero”

– Short-circuit current: “Overcurrent resulting from a short-circuit in an electric system”

October 15, 2020 Slide 3


MV & LV Transformer Substations
Network Elements affecting Short Circuit

Utility/Transformers Generators Motors Cables/Busway

October 15, 2020 Slide 4


MV & LV Transformer Substations
Theory & Short Circuit Calculations

Protection of 400V transformers at 750MVA (Example)

Sr (KVA) Uk (%) Rated Current Ir (A) S.C. Current (KA)


500 4 722 17.7
630 4 909 22.3
800 5 1155 22.6
1000 5 1443 28.1
1250 5 1804 34.9
1600 6.25 2309 35.7
2000 6.25 2887 44.3
2500 6.25 3608 54.8
3125 6.25 4510 67.7

October 15, 2020 Slide 7


MV & LV Transformer Substations
Theory & Short Circuit Calculations

Calculation of Short Circuit Currents


Asynchronous motors
• In case of short-circuit it functions as a generator with a
x”d from 20% to 25%
• a current equal to 4-6 times the In can be assumed as
contribution to the short-circuit
• the minimum criteria for taking into consideration the
phenomenon

(Ik short-circuit without motor contribution)

October 15, 2020 Slide 9


MV & LV Transformer Substations
Theory & Short Circuit Calculations

IEC 60909-1 : Motor Contribution values

October 15, 2020 Slide 10


MV & LV Transformer Substations
Theory & Short Circuit Calculations

IEC 60909-1 : Motor equivalent values

October 15, 2020 Slide 11



Low voltage selectivity
Selectivity definitions & standards
Low voltage selectivity
Selectivity definitions & standards

Definition of selectivity

IEC 60947-1 Standard: “Low voltage equipment IEC 60947-1


Part 1: General rules for low voltage equipment” def. 2.5.23

“Trip selectivity (for overcurrent) is a coordination between the operating characteristics of two or more
overcurrent protection devices, so that, when an overcurrent within established limits occurs, the device
destined to operate within those limits trips whereas the others do not trip”

October 15, 2020 Slide 13


Low voltage selectivity
Selectivity definitions & standards

Example
If selectivity is provided

• When a fault occurs ( Overload or Short-circuit)

• The protection device closes to the fault opens.

October 15, 2020 Slide 14


Low voltage selectivity
Selectivity definitions & standards

Example
If selectivity is NOT provided

• When a fault occurs ( Overload or Short-circuit)

• Both the upstream & downstream protection


devices could open.

The whole system will be out of service

October 15, 2020 Slide 15


Low voltage selectivity
Selectivity definitions & standards

Example
If selectivity is NOT provided

• When a fault occurs (Overload or Short-circuit)

• The upstream device could open first before any


other devices open.

The whole system will be out of service

October 15, 2020 Slide 16


Low voltage selectivity
Selectivity definitions & standards

Time-Current Curves
Short-Circuit Zone

• Magnetic protection
• S, D, I & EF Protection

Current, Time, Energy, Zone, Directional & Zone


Directional Selectivity

October 15, 2020 Slide 17


Low voltage selectivity
Selectivity definitions & standards

Partial & Total selectivity


Example

Upstream circuit breaker A :


T4N 250 PR221DS In = 250 (Icu = 36kA)

Downstream circuit breaker B


S 294 C100 (Icu = 15kA)

October 15, 2020 Slide 18


Low voltage selectivity
Selectivity definitions & standards

Partial & Total selectivity


Example

Upstream circuit breaker A :


T4N 250 PR221DS In = 160 (Icu = 36kA)

Downstream circuit breaker B


S 294 C100 (Icu = 15kA)

October 15, 2020 Slide 19



Low voltage Back-up
Back-up definitions & standards
Low voltage selectivity
Back-Up protection

Standards definition
The definition of back-up is given by

IEC 60947-1 Standard: “Low voltage equipment IEC 60947-1


Part 1: General rules for low voltage equipment” def. 2.5.24

“Back-up is a coordination of two overcurrent protective devices in series, where the protective device on
the supply side, with or without the assistance of the other protective device, trips first in order to
prevents any excessive stress on downstream devices”.

October 15, 2020 Slide 21


Low voltage selectivity
Back-Up protection

Back-Up protection
Basic concept
Back-up is used by those who need to contain the
plant costs

The use of a current-limiting circuit breaker on the


supply side permits the installation of lower
performance circuit breakers on the load side

Both the continuity of service and the selectivity


are sacrificed

October 15, 2020 Slide 22


Low voltage selectivity
Back-Up protection

Back-Up protection
Example

T5L 250 T5L 250

Ik = 100 kA Ik = 100 kA

XT2L 160 XT2L 160 XT2L 160 Icu = 120kA XT2N 160 XT2N 160 XT2N 160 Icu = 36kA

October 15, 2020 Slide 23


Low voltage selectivity
Back-Up protection

Back-Up protection table

October 15, 2020 Slide 24



Low voltage Miniature CBs
IEC 60947-2 vs IEC 60898-1
IEC 60947-2 vs IEC 60898-1
Miniature Circuit Breakers

IEC 60947-2 IEC 60898-1

People Instructed Uninstructed


Maintenance Possible Not possible
< 1000 Vac < 440 Vac
Rated Voltage (Ue)
< 1500 Vdc < 220 Vdc

Ambient Temperature 40° C 30° C

No limits
Rated Current In = 125 A
(Iu < 6300 A)

Short circuit breaking Icn = 25 kA (ac)


current
No limits for Icu
Icn = 10 kA (dc)

October 15, 2020 Slide 26



IP code
IEC 60529
IP code
IEC 60529

October 15, 2020 Slide 28


IP code
Example

October 15, 2020 Slide 29



Ambient Temperature
IEC 61439-1
Ambient Temperature
IEC 61439-1

7.1.1 Ambient air temperature

7.1.1.1 Ambient air temperature for indoor installations

The ambient air temperature does not exceed +40 °C and its average over a period of 24 h
does not exceed +35 °C.
The lower limit of the ambient air temperature is –5 °C.

October 15, 2020 Slide 31



Form of separation
IEC 61439-1
Form of separation
IEC 61439-1

October 15, 2020 Slide 33



Circuit breakers version
Fixed, Plug-in and Withdrawable
Basics of standards
Circuit breakers version

• Fixed (Standard)
• Plug-in

• Withdrawable

October 15, 2020 Slide 35



LV Switchboard Busbar
Coating materials
LV Switchboard Busbar
Coating materials

Busbar coating material:

• Bare copper busbar.


• Tin plated copper busbar.
• Silver Plated copper busbar. Bare copper busbar Tin plated copper busbar
• Copper busbar with silver plating
at joints.

Silver Plated copper busbar Copper busbar with silver


plating at joints.

October 15, 2020 Slide 37



Surge Protection Device (SPD)
SPD coordination
Common cause of lightning transient

Indirect strike as far as 1km away cause


transient/surge problems irrespective of whether
structural LPS fitted or not.

October 15, 2020 Slide 39


Co-ordination of SPD types

Fire and electric shock hazards from flashover

Service entrance SPDs prevent flashover to preserve life

Used alone, Type 1 SPDs do not protect electronics:


An LPS “that employs only equipotential SPDs provides no effective protection against failure of sensitive
electrical or electronic systems” BS EN 62305-4 Page 16

Transient overvoltage SPDs (Type 2 and 3) needed to complete a coordinated SPD set for equipment
protection

October 15, 2020 Slide 40


Co-ordination of SPD types

SPDs on same installation need to operate together effectively

• Ensure Type 1 handles high energy surges and


• Type 2 & 3 SPDs limit overvoltages respectively
• Poor co-ordination could result in damage to SPDs and equipment

October 15, 2020 Slide 41


Coordinated SPD (Overvoltage and transient current SPDs)

October 15, 2020 Slide 42


Coordinated SPD (Overvoltage and transient current SPDs)

Surge risk

With LPS
or aerial network
Type 1 Type 2 Type 2 / Type 3
Type 1+2 40kA 20kA / 10kA
25kA / 15kA
Without LPS
or aerial network
Type 2 70kA

MDB
SDB
Close to equipment

October 15, 2020 Slide 43



Smart LV switchboard
Solution architecture
Different Communication Systems
Low voltage switchboard integration in Centralized Management Systems

Controlling Circuit Breakers: -


– Trip commands: circuit breakers must be provided with shunt opening release accessory.
– Operation Control: circuit breakers must be provided with Electrical Motors accessories.

October 15, 2020 Slide 45


Smart LV switchboard
Solution architecture

ABB Ability EDCS

Cloud access
points

Field devices

October 15, 2020 Slide 46


Applications
Retrofitting and upgrading public buildings

Solution with Ekip Up and CMS-700


– The Ekip UP:
• collects information (status, alarms and Sub Distribution
the number of operations) via Ekip Board

Signaling modules

– The CMS-700:
• branch monitoring
• connected to the Ekip UP via Modbus
TCP/IP.

– ABB Ability EDCS


• data analysis
• visualization

October 15, 2020 Slide 47


Smart LV switchboard
Budgetary commercial comparison with basic switchboard

Main Switchboard (Basic Price = 1,570,000 LE)


Solution TCP Comm. EDCS

Signalling 4% 7%

Current Measuring 6% 9%

Energy Measuring 11% 15%

MDB incoming = 3200A


Outgoings = 2500A, 1000A (ACBs)
1000A, 200A, 160A (MCCBs)
Capacitor bank = 350KVAR

October 15, 2020 Slide 48



Motor Starting
Basic Motor Circuit Components
Motors Starting
Motor Protection & Control

- Disconnector
Isolation - Switch disconnector

- Switch Fuse
Short Circuit Protection - Circuit Breaker (Magnetic)
- Manual Motor Starter
Control - Contactor

- Thermal / Electronic
Overload Protection
Overload Relay

M
3~

October 15, 2020 Slide 50



Motor Starting
Starting methods
Motors Starting
Motor Protection and Control

Direct Online Starters


- Traditional starting method
- Full voltage with no control of the start
- Combinations for motor protection
- Compact and cost-efficient solution
- Mostly used for small motors, usually <15 kW

Potential electrical problems


- Warm cables
- Tripping breakers

Potential mechanical problems


- Slipping belts
- Heavy wear and tear
- Damaged products

October 15, 2020 Slide 52


Motors Starting Methods
Direct Online Starters

Light Load Medium Load Heavy Load

T
T T

rpm
rpm rpm
I I I

rpm rpm rpm

October 15, 2020 Slide 53


Motors Starting Methods
Star-Delta Starter

General Characteristics
- Low starting current (only at successful start)
- Transmission peaks at loaded start
- Low starting torque (often too low)
- Long starting time Delta Contactor

- Always direct stop


- Many devices – complex wiring Star Contactor

- Double motor cables

Line Contactor

October 15, 2020 Slide 54


Motors Starting Methods
Star-Delta Starter

Light Load Medium Load Heavy Load

T T T

rpm rpm rpm

I I I

rpm rpm rpm

October 15, 2020 Slide 55


Motors Starting Methods
Soft Starters

General Characteristics
Line
- Adjustable starting current Contactor
- Correct starting torque matching the need
- Possibility to soft stop
- Medium long starting time
Softstarter
- Minimum mechanical wear.

Built in
Electronic
overload

Built in
By-pass
M

October 15, 2020 Slide 56


Soft starters
Principal Function

Theory of Operation

Anti-parallel connected thyristors Voltage reduction during starting

U
100%

October 15, 2020 Slide 57


Soft Starters
Principal Function

Theory of operation

U I T
100%

U = 50% I = 50%
T = 25%

t rpm rpm

October 15, 2020 Slide 58


Soft Starters
Load Types

Light Load Medium Load Heavy Load

T
T T

rpm
rpm rpm
I
I I

rpm
rpm rpm

October 15, 2020 Slide 59


Soft Starters
Sometimes the benefits are really obvious

Conveyor Belts Water Hammering

October 15, 2020 Slide 60


Soft Starters
Coordination of Protection

Coordination Type 2 for Soft starters

Semi-conductor fuses (High speed fuses) are the only type of


fuses that are fast enough to achieve a fully type 2 coordination
when using a soft starter. A separate overload relay for the
motor protection is always required in combination with this
type of fuse. If replacing the semi-conductor fuses with an MCCB,
MMS or similar, type 1 coordination will be achieved instead.

October 15, 2020 Slide 62


Motors Starting Methods
Variable Speed Drives

General Characteristics
- Full control of speed, current and torque
- Energy saving from reducing speed
- Mostly used for process control
- No Value for full speed applications AC
- Creates Harmonics DC

speed
DC
AC

time M

October 15, 2020 Slide 63


The motor starting market
Which starter shall be select

Full speed Constant speed Variable speed

Un-controlled start “Semi-controlled “start Controlled start

Medium voltage/High power etc.


Single phase motors,
small motors, etc.

DOL Y/D Softstarter Drive

Small motor ratings Higher ratings All ratings

Overlap

October 15, 2020 Slide 64 This picture doesn’t represent any actual size of market, it just a visualization to explain the market split

Motor Starting
Manual Motor Starters
Motors Starting
Manual Motor Starters

 Disconnect  Disconnect  Disconnect


 Short-circuit  Short-circuit  Short circuit
protection protection protection
 Overload  Overload  Manual control
protection protection
 Phase-failure  Phase-failure
 Manual control  Manual control

 Control

 Control  Overload
protection

October 15, 2020 Slide 66



DIN-Rail Range overview
Protection of people and assets
DIN-Rail Range overview
Protection of people and assets – 4 classes of protection

Miniature Circuit Breakers Residual Current Devices Surge Protective Devices Arc Fault Detection
(MCBs) (RCDs) (SPDs) Devices (AFDDs)
− Protection against − Protection against earth − Protection against surges − Protection against arc
overloads and short circuits fault currents and the impact of direct faults (parallel, series and
• MCBs • Residual Current Circuit and indirect lightning earth arc faults)

• High Performance Circuit Breakers (RCCBs) • SPD Class I, II & III (Type 1, • S-ARC1: AFDD with
Breakers (HPCBs) • RCBOs: RCCBs with Type 2, Type 1+2, …) integrated MCB

• Selective Main Circuit integrated MCB • Data line protection • DS-ARC1: AFDD with
Breakers (SMCBs) integrated RCBO

October 15, 2020 Slide 68



DIN-Rail Products
Residual Current Devices (RCDs)
Residual Current Devices (RCDs)
Classification of RCDs

RCDs can be classified by their suitability for detecting different forms of residual current
– Type AC, sensitive to alternating current only
• Suitable for all systems where users have sinusoidal earth current.
– Type A, sensitive to alternating and/or pulsating current with DC components
• Suitable for protecting systems in which the user equipment has electronic devices for rectifying the current
– Type B to provide protection in case of alternating residual sinusoidal currents up to 1.000 Hz, pulsating direct residual currents and
smooth direct residual currents
• Recommended for use with drives and inverters for supplying motors for pumps

October 15, 2020 Slide 70



Busway
IEC 61439-1 2011, IEC 61439-6 2012
Copper Conductors Busway Specifications
50DegC
Tested

⚫ Standard: IEC 61439-1 2011, IEC 61439-6 2012


⚫ Certificates: KEMA KEUR certification
⚫ Icw: 30kA~100kA
⚫ Ui/Ue: 1000V / 1000V
⚫ IP Rating: IP41, IP54, IP65 (Feeder); IP41, IP54 (Plug-in)
⚫ Frequency: 50Hz / 60Hz
⚫ Busway service:
✓ L1+L2+L3+50% Housing ground
✓ L1+L2+L3+100%N+50% Housing ground
✓ L1+L2+L3+100%N+50% Internal ground
✓ L1+L2+L3+200%N+50% Housing ground
⚫ Rated Current:
✓ 400A, 630A, 800A, 1000A, 1250A, 1600A, 2000A, 2500A, 3200A, 4000A, 5000A
⚫ Tap off unit:
✓ Rating: 16A~160A, 200A~250A, 400A~500A, 630A, 800A~1000A
✓ MCCB: GE Record C, Record Plus, NS

October 15, 2020 73


Aluminum Conductors Busway Specifications

⚫ Standard: IEC 61439-1 2011, IEC 61439-6 2012


⚫ Certificates: KEMA KEUR certification
⚫ Icw: 10kA ~ 80kA
⚫ Ui/Ue: 1000V / 690V
⚫ IP Rating: IP40, IP54, IP65 (Feeder); IP40, IP54 (Plug-in)
⚫ Frequency: 50Hz / 60Hz
⚫ Busway service:
✓ L1+L2+L3+50% Housing ground
✓ L1+L2+L3+100%N+50% Housing ground
✓ L1+L2+L3+100%N+50% Internal ground
✓ L1+L2+L3+200%N+50% Housing ground
⚫ Rated Current:
✓ 250A, 400A, 500A, 630A, 800A, 1000A, 1250A, 1350A, 1600A, 2000A, 2500A, 3200A, 4000A

⚫ Aluminum conductor: Copper plating first, then tin plating


⚫ Busway temperature rise is lower than 70K

October 15, 2020 74


Phase tabs at busway outlet

Insulating layers of cables (core insulation and


outer insulation) are insulating electrically as •
well as thermally, while busway use sandwich
construction in whole length with totally
enclosed housing. Heat disperses through
conduction mode. Busway has superior heat
dissipation performance compared to cable.

October 15, 2020 75


Busway Vs Cables
Case Study
4000A, 3P4W

Busway Vs Cables

As per Egyptian code:


The combined cross-sectional area of all cables installed in the
tray shall not exceed 50% of the interior cross-sectional area of
the cable tray.

For 4000A load we will select 9 Aluminum cables with cross 591mm
section area 300mm2, 9 AL Cables (3x300+150+150E)
-The total width of the cables installed on cable tray = 1446mm
-The total width of the busway = 591mm

1446mm

9 AL Cables (3x300+150+150E)

October 15, 2020 Slide 76



Medium Voltage Switchgear
IEC 62271-200
Medium Voltage Primary Switchgear
Circuit Breaker Execution Types

ROF Type CB’s Cassette Type CB’s

October 15, 2020 Slide 78


Medium Voltage Secondary Switchgear (RMU)
Comparison

ABB UniSec - AIS ABB SafeRing/SafePlus - GIS

October 15, 2020 Slide 79


Medium Voltage Secondary Switchgear (RMU)
Comparison

Feeder with fused switch-disconnector Feeder with circuit-breaker and switch-disconnector

SFC F SBC V

October 15, 2020 Slide 80


Medium Voltage Secondary Switchgear (RMU)
LBS + Fuse

Fuse Rating According to EDC Specifications:

Fuse Ratings:
Rated voltage: 24KV
Rated Frequency: 50HZ
Rated Breaking Capacity: 40KA

The Transformer Rating (KVA) 100 200 300 500 800 1000 1500
Nominal current for (H.R.C) 10 16 25 40 40 63 80
fuse at 40 deg. C

October 15, 2020 Slide 81



Capacitor Bank
Detuned Reactor Selection
Power Quality – Harmonic basics
Conclusion

Conclusion of Harmonics
— Harmonics are not good for the electrical devices & network
— If not controlled, they can lead to sever problem (technical as well as financial loss)

— Capacitor banks are more susceptible to harmonics and must be protected by a suitable reactor
— Detuning reactor must be selected carefully

— Active filters with suitable values are used to mitigate the harmonics

October 15, 2020 Slide 83


Power Quality – Capacitor bank
Capacitors Rating at different voltages

Capacitors Rating

October 15, 2020 Slide 84


Causes of Harmonics
Consequences

Power Factor & Resonance


• Resonance can cause amplification of harmonics in an electrical
network leading to equipment failure.
• Resonance is impossible to avoid
• Capacitors & reactors will always create resonance for some
frequency(ies)
M
• Solution: 2
 1 
o Add a reactor in series with each capacitor and this detuning
Z( ) = R +  L −
2

reactor must be selected carefully  C
• Note:
o Detuned reactors protects the power factor its self ONLY and
doesn’t eliminate or mitigate the harmonics on the network
U
RESONANCE

October 15, 2020 Slide 85


Power Quality – Harmonic basics
Resonance

Series and Parallel Resonance


1
Impedance: 𝑍  = 𝐿 −
⍵𝐶 L C

Resonance at frequency 0 for which 0L = 1/0C


Z(0) → 0

Harmonic current present at 0 will be dramatically amplified !!

⍵𝐿 L
Impedance: 𝑍  =
1 − ⍵2L 𝐶

Resonance at frequency 0 for which 02 LC = 1


Z(0) → infinite

Harmonic voltage present at 0 will be dramatically amplified !!


C

October 15, 2020 Slide 86


Power Quality – Harmonic basics
Resonance

How to customize the resonance?


— By creating resonances where we know there is no harmonic solicitation
— Transformer: imposed
— Capacitor: imposed (& changing)

— Add a reactor in series with each capacitor

October 15, 2020 Slide 88


Power Quality – Harmonic basics
Suitable Reactor Factor

Typical reactor values Reactor percentage :


— Choose the tuning order (resonance
frequency) BELOW the first significant p (%) = ( fn / fo)2 *100
harmonic order
— Check also not to disturb the remote 1
control frequency. n0 = = (f0/fn)
P
— ABB mainly uses detuned reactors of:

— 7% reactor : n0 = 3.78
Resonance frequency
tuning on 3.78*50Hz = 189 Hz
for systems with 5th harmonic
fN
— 14% reactor : n0 = 2.67
f0 =
p
tuning on 2.67*50Hz = 134 Hz
for systems with 3rd harmonic

October 15, 2020 Slide 89


Power Quality – Harmonic basics
Suitable Reactor Factor

The bigger the reactor


The bigger the voltage rise on capacitor The bigger the size The higher the losses (for same current)

The bigger the reactor, HIGHER the cost

October 15, 2020 Slide 90


Power Quality – Harmonic basics
Reactor protected capacitor

Example of voltage increase on the capacitor:


— U = 400 V
— Capacitor in serie with 7% reactor, p=0.07

UL = p/(1-p).U
U

UC = U/(1-p)

— UC = 400/(1-0.07)= 430 V, choose capacitor having min.430V nom. Voltage


— UL = 0.07/(1-0.07)*400= 30 V

October 15, 2020 Slide 91


Power Quality – Harmonic basics
Reactor protected capacitor

Example of 50 KVAR capacitor step module with reactor

Reactor Capacitors

Mounting plate

Contactor
— Compatible with ARTUK and MNS 3.0 Fuses holder

October 15, 2020 Slide 92


Power Quality – Harmonic basics
Reactor protected capacitor

Example of 100 KVAR capacitor shelf

Capacitors

Mounting plate
Fuses holder Contactors
— Compatible with System Pro-E

October 15, 2020 Slide 93


Capacitor Bank
System pro E power series

Capacitor bank of 1200KVAR


Example 1200kvar:
– Incoming breaker E2.2 2500A
– Rear busbar system 2x80x10 in each phase
– 12 capacitor units of 100kvar
– Each column has capacity of 400kvar
– Depth 700mm
– Combined with TBBS Emax column and RBBS
rear busbars

October 15, 2020 Slide 94


Capacitor Bank
Precise control and monitoring of system power quality

Mode of switching
The modes of switching for all the
programmable
switching sequences are normal or integral,
progressive or direct, linear or circular

October 15, 2020 Slide 95



Harmonics Case Study
Technical & Commercial
Case Study
Case Study

Network Elements
– One 22KV MVSG (6-Cells)
– Two 22/0.4KV Oil Distribution Transformer – ONAN
– One 400v Generator.
– Copper BW from each ODT and GEN to MDB incomings.
– 400v MDB consisting of:
• Two incomings from each ODT.
• One incoming from generator.
• Bus coupler.
• Five Outgoing feeders to VSDs
• Other inductive load with total power of 300KW.
• PFC, one on each section.
– Five 400KW VSD – 400V. (3 on section 1 & 2 on section 2)
– Five Motors fed from the VSDs. (3Duty + 2 Standby)

October 15, 2020 Slide 97


Case Study
Case Study

Assumptions

• Design ambient temperature of 45⁰C


• IP54 for all panels.
• Form 2b for MDB.
• Distance:
o 100m between transformers & MDB.
o 100m between generator and MDB.
o 30m between VSDs and motors.

October 15, 2020 Slide 98


Case Study
Case Study

Scenarios

– Design Number 1:
• Considering the VSD type is standard harmonic type.
– Design Number 2:
• Considering the VSD type is standard harmonic type
with passive filter to achieve 10% TDDi.
– Design Number 3:
• Considering VSD type is standard harmonic type with
AHF to achieve 10% TDDi.
– Design Number 4:
• Considering the VSD type is low harmonic type.

October 15, 2020 Slide 99


Case Study
Case Study

Output

– Transformer sizing with maximum loading of 80%


– Generator sizing as a backup generator to supply the full
load.
– Cable sizing.
– Busway sizing.
– CBs sizing.
– PFC sizing and whether it shall be detuned or not.
– Type of each element in the network.
– Harmonic analysis study containing all the design
elements.
– SLD of each design.

October 15, 2020 Slide 100


Case Study
Case Study

Aim of Study

– Showing the harmonic effect on each element in the


network and its drawbacks in a numeric way
• Technically & • Commercially

October 15, 2020 Slide 101


Case Study
Harmonic Analysis Study

Technical Output

LV Side
Transformer Cables Between
Permissible Selected Cables Between
Design Scenario Drive Solution Rated Power PFC (KVAR) MDB & Other
Load (VA) BW (A) Current Voltage MDB & Drive
(VA) Loads
Distortion Distortion
TDDi% THDv%

SH ACS880-07-0820A-3 - 3,150,000 2,533,400 5,000 31.8% 10.7% Detuned 550 3x 5G240/120 5G300/150

SH+PF ACS880-07-0820A-3 FN 341x-310-99 2,500,000 2,492,900 4,000 3.1% 1.5% Detuned 550 3x 5G240/120 5G300/150

SH+AHF 10% ACS880-07-0820A-3 PQFI-M30 S30 2,500,000 2,430,100 4,000 9.9% 3.4% 550 2x 5G300/150 5G150/95

SH+AHF 5% ACS880-07-0820A-3 PQFI-V1-M45 S30 2,500,000 2,482,300 4,000 4.9% 1.7% 550 2x 5G300/150 5G150/95

LH ACS880-37-0870A-3 - 2,500,000 2,496,700 4,000 2.1% 1.7% 550 2x 5G300/150 5G150/95

October 15, 2020 Slide 102


Case Study
Harmonic Analysis Study

Commercial Output

SH SH+PF SH+AHF LH
# Item Quantity Quantity Quantity Quantity
Unit Price Total Price Unit Price Total Price Unit Price Total Price Unit Price Total Price
1 22KV MVSG (6-Cells) 1 EGP 1,925,000 EGP 1,925,000 1 EGP 1,925,000 EGP 1,925,000 1 EGP 1,925,000 EGP 1,925,000 1 EGP 1,925,000 EGP 1,925,000

2 110V DC System (Battery & Battery Charger According To EDC) 1 EGP 300,000 EGP 300,000 1 EGP 300,000 EGP 300,000 1 EGP 300,000 EGP 300,000 1 EGP 300,000 EGP 300,000

3 22/0.4KV Dry Type Transformer - ANAF 2 EGP 1,372,500 EGP 2,745,000 2 EGP 1,035,000 EGP 2,070,000 2 EGP 1,035,000 EGP 2,070,000 2 EGP 1,035,000 EGP 2,070,000

4 Busway Between Transformer & MDB 200 EGP 50,000 EGP 10,000,000 200 EGP 30,000 EGP 6,000,000 200 EGP 30,000 EGP 6,000,000 200 EGP 30,000 EGP 6,000,000

5 400v MDB 1 EGP 4,595,635 EGP 4,595,635 1 EGP 4,595,635 EGP 4,595,635 1 EGP 4,653,600 EGP 4,653,600 1 EGP 4,595,635 EGP 4,595,635

6 PFC 2 EGP 579,144 EGP 1,158,288 2 EGP 579,144 EGP 1,158,288 2 EGP 361,965 EGP 723,930 2 EGP 361,965 EGP 723,930

7 Solution 0 EGP - EGP - 5 EGP 219,978 EGP 1,099,890 1 EGP 3,025,039 EGP 3,025,039 0 EGP - EGP -

8 Cables From MDB To Motor & Drive 150 EGP 7,776 EGP 1,166,400 150 EGP 7,776 EGP 1,166,400 150 EGP 6,442 EGP 966,300 150 EGP 6,442 EGP 966,300

9 Cables From MDB To Other Loads 40 EGP 3,619 EGP 144,760 40 EGP 3,619 EGP 144,760 40 EGP 1,769 EGP 70,760 40 EGP 1,769 EGP 70,760

10 400V LV Drive 5 EGP - 5 EGP 550,000 EGP 2,750,000 5 EGP 550,000 EGP 2,750,000 5 EGP 880,000 EGP 4,400,000

11 400V LV Motor 5 EGP 720,000 EGP 3,600,000 5 EGP 720,000 EGP 3,600,000 5 EGP 720,000 EGP 3,600,000 5 EGP 720,000 EGP 3,600,000

EGP 25,635,083 EGP 24,809,973 EGP 26,084,629 EGP 24,651,625

SH SH+PF SH+AHF LH

October 15, 2020 Slide 103


Case Study
Design Number 1: Considering the VSD type is standard harmonic type

Standard Harmonic
Drive & Motor MV
14% 9%
Transformers
Cables 11%
5%

LV
22%

Busway
39%

MV Transformers Busway LV Cables Drive & Motor

October 15, 2020 Slide 104


Case Study
Design Number 2: Considering the VSD type is standard harmonic type with passive filter to
achieve 10% TDDi
Standard Harmonic With Passive Filter
Solution MV
5% 9%
Transformers
8%
Drive & Motor
26%

Busway
24%

Cables
5%

LV
23%

MV Transformers Busway LV Cables Drive & Motor Solution

October 15, 2020 Slide 105


Case Study
Design Number 3: Considering VSD type is standard harmonic type with AHF to achieve 10%
TDDi
Standard Harmonic With Passive Filter
Solution MV
12% 8% Transformers
8%

Drive & Motor


24%
Busway
23%

Cables LV
4% 21%
MV Transformers Busway LV Cables Drive & Motor Solution

October 15, 2020 Slide 106


Case Study
Design Number 4: Considering the VSD type is low harmonic type

Low Harmonic

MV
9%
Transformers
Drive & Motor 8%
33%

Busway
24%

Cables
4%

LV
22%
MV Transformers Busway LV Cables Drive & Motor

October 15, 2020 Slide 107


Quick selection guide
APCQ series

“Quick” selection guide

Qcomp = P  (tg1 − tg2 )


Non linear loads total power (kVA)
Transformer rated power (kVA)

< 15% 15 to 25% > 25% > 60%

De-tuned range
+ Harmonic
Standard range 1 Reinforced range 1 De-tuned range 2
filtering
solution 3

1Providing there is no resonance


2 Reactorvalue must not interfere with existing telecommunication frequency.
October 15, 2020 Slide 108 3
Requires harmonic analysis. Please contact ABB’s specialist.

You might also like