Value Engineering
Value Engineering
Value Engineering
– Short-circuit : “Accidental or intentional conductive path between two or more conductive parts forcing the electric potential
differences between these conductive parts to be equal or close to zero”
Definition of selectivity
“Trip selectivity (for overcurrent) is a coordination between the operating characteristics of two or more
overcurrent protection devices, so that, when an overcurrent within established limits occurs, the device
destined to operate within those limits trips whereas the others do not trip”
Example
If selectivity is provided
Example
If selectivity is NOT provided
Example
If selectivity is NOT provided
Time-Current Curves
Short-Circuit Zone
• Magnetic protection
• S, D, I & EF Protection
Standards definition
The definition of back-up is given by
“Back-up is a coordination of two overcurrent protective devices in series, where the protective device on
the supply side, with or without the assistance of the other protective device, trips first in order to
prevents any excessive stress on downstream devices”.
Back-Up protection
Basic concept
Back-up is used by those who need to contain the
plant costs
Back-Up protection
Example
Ik = 100 kA Ik = 100 kA
XT2L 160 XT2L 160 XT2L 160 Icu = 120kA XT2N 160 XT2N 160 XT2N 160 Icu = 36kA
No limits
Rated Current In = 125 A
(Iu < 6300 A)
The ambient air temperature does not exceed +40 °C and its average over a period of 24 h
does not exceed +35 °C.
The lower limit of the ambient air temperature is –5 °C.
• Fixed (Standard)
• Plug-in
• Withdrawable
Transient overvoltage SPDs (Type 2 and 3) needed to complete a coordinated SPD set for equipment
protection
Surge risk
With LPS
or aerial network
Type 1 Type 2 Type 2 / Type 3
Type 1+2 40kA 20kA / 10kA
25kA / 15kA
Without LPS
or aerial network
Type 2 70kA
MDB
SDB
Close to equipment
Cloud access
points
Field devices
Signaling modules
– The CMS-700:
• branch monitoring
• connected to the Ekip UP via Modbus
TCP/IP.
Signalling 4% 7%
Current Measuring 6% 9%
- Disconnector
Isolation - Switch disconnector
- Switch Fuse
Short Circuit Protection - Circuit Breaker (Magnetic)
- Manual Motor Starter
Control - Contactor
- Thermal / Electronic
Overload Protection
Overload Relay
M
3~
T
T T
rpm
rpm rpm
I I I
General Characteristics
- Low starting current (only at successful start)
- Transmission peaks at loaded start
- Low starting torque (often too low)
- Long starting time Delta Contactor
Line Contactor
T T T
I I I
General Characteristics
Line
- Adjustable starting current Contactor
- Correct starting torque matching the need
- Possibility to soft stop
- Medium long starting time
Softstarter
- Minimum mechanical wear.
Built in
Electronic
overload
Built in
By-pass
M
Theory of Operation
U
100%
Theory of operation
U I T
100%
U = 50% I = 50%
T = 25%
t rpm rpm
T
T T
rpm
rpm rpm
I
I I
rpm
rpm rpm
General Characteristics
- Full control of speed, current and torque
- Energy saving from reducing speed
- Mostly used for process control
- No Value for full speed applications AC
- Creates Harmonics DC
speed
DC
AC
time M
Overlap
October 15, 2020 Slide 64 This picture doesn’t represent any actual size of market, it just a visualization to explain the market split
—
Motor Starting
Manual Motor Starters
Motors Starting
Manual Motor Starters
Control
Control Overload
protection
Miniature Circuit Breakers Residual Current Devices Surge Protective Devices Arc Fault Detection
(MCBs) (RCDs) (SPDs) Devices (AFDDs)
− Protection against − Protection against earth − Protection against surges − Protection against arc
overloads and short circuits fault currents and the impact of direct faults (parallel, series and
• MCBs • Residual Current Circuit and indirect lightning earth arc faults)
• High Performance Circuit Breakers (RCCBs) • SPD Class I, II & III (Type 1, • S-ARC1: AFDD with
Breakers (HPCBs) • RCBOs: RCCBs with Type 2, Type 1+2, …) integrated MCB
• Selective Main Circuit integrated MCB • Data line protection • DS-ARC1: AFDD with
Breakers (SMCBs) integrated RCBO
RCDs can be classified by their suitability for detecting different forms of residual current
– Type AC, sensitive to alternating current only
• Suitable for all systems where users have sinusoidal earth current.
– Type A, sensitive to alternating and/or pulsating current with DC components
• Suitable for protecting systems in which the user equipment has electronic devices for rectifying the current
– Type B to provide protection in case of alternating residual sinusoidal currents up to 1.000 Hz, pulsating direct residual currents and
smooth direct residual currents
• Recommended for use with drives and inverters for supplying motors for pumps
Busway Vs Cables
For 4000A load we will select 9 Aluminum cables with cross 591mm
section area 300mm2, 9 AL Cables (3x300+150+150E)
-The total width of the cables installed on cable tray = 1446mm
-The total width of the busway = 591mm
1446mm
9 AL Cables (3x300+150+150E)
SFC F SBC V
Fuse Ratings:
Rated voltage: 24KV
Rated Frequency: 50HZ
Rated Breaking Capacity: 40KA
The Transformer Rating (KVA) 100 200 300 500 800 1000 1500
Nominal current for (H.R.C) 10 16 25 40 40 63 80
fuse at 40 deg. C
Conclusion of Harmonics
— Harmonics are not good for the electrical devices & network
— If not controlled, they can lead to sever problem (technical as well as financial loss)
— Capacitor banks are more susceptible to harmonics and must be protected by a suitable reactor
— Detuning reactor must be selected carefully
— Active filters with suitable values are used to mitigate the harmonics
Capacitors Rating
⍵𝐿 L
Impedance: 𝑍 =
1 − ⍵2L 𝐶
— 7% reactor : n0 = 3.78
Resonance frequency
tuning on 3.78*50Hz = 189 Hz
for systems with 5th harmonic
fN
— 14% reactor : n0 = 2.67
f0 =
p
tuning on 2.67*50Hz = 134 Hz
for systems with 3rd harmonic
UL = p/(1-p).U
U
UC = U/(1-p)
Reactor Capacitors
Mounting plate
Contactor
— Compatible with ARTUK and MNS 3.0 Fuses holder
Capacitors
Mounting plate
Fuses holder Contactors
— Compatible with System Pro-E
Mode of switching
The modes of switching for all the
programmable
switching sequences are normal or integral,
progressive or direct, linear or circular
Network Elements
– One 22KV MVSG (6-Cells)
– Two 22/0.4KV Oil Distribution Transformer – ONAN
– One 400v Generator.
– Copper BW from each ODT and GEN to MDB incomings.
– 400v MDB consisting of:
• Two incomings from each ODT.
• One incoming from generator.
• Bus coupler.
• Five Outgoing feeders to VSDs
• Other inductive load with total power of 300KW.
• PFC, one on each section.
– Five 400KW VSD – 400V. (3 on section 1 & 2 on section 2)
– Five Motors fed from the VSDs. (3Duty + 2 Standby)
Assumptions
Scenarios
– Design Number 1:
• Considering the VSD type is standard harmonic type.
– Design Number 2:
• Considering the VSD type is standard harmonic type
with passive filter to achieve 10% TDDi.
– Design Number 3:
• Considering VSD type is standard harmonic type with
AHF to achieve 10% TDDi.
– Design Number 4:
• Considering the VSD type is low harmonic type.
Output
Aim of Study
Technical Output
LV Side
Transformer Cables Between
Permissible Selected Cables Between
Design Scenario Drive Solution Rated Power PFC (KVAR) MDB & Other
Load (VA) BW (A) Current Voltage MDB & Drive
(VA) Loads
Distortion Distortion
TDDi% THDv%
SH ACS880-07-0820A-3 - 3,150,000 2,533,400 5,000 31.8% 10.7% Detuned 550 3x 5G240/120 5G300/150
SH+PF ACS880-07-0820A-3 FN 341x-310-99 2,500,000 2,492,900 4,000 3.1% 1.5% Detuned 550 3x 5G240/120 5G300/150
SH+AHF 10% ACS880-07-0820A-3 PQFI-M30 S30 2,500,000 2,430,100 4,000 9.9% 3.4% 550 2x 5G300/150 5G150/95
SH+AHF 5% ACS880-07-0820A-3 PQFI-V1-M45 S30 2,500,000 2,482,300 4,000 4.9% 1.7% 550 2x 5G300/150 5G150/95
Commercial Output
SH SH+PF SH+AHF LH
# Item Quantity Quantity Quantity Quantity
Unit Price Total Price Unit Price Total Price Unit Price Total Price Unit Price Total Price
1 22KV MVSG (6-Cells) 1 EGP 1,925,000 EGP 1,925,000 1 EGP 1,925,000 EGP 1,925,000 1 EGP 1,925,000 EGP 1,925,000 1 EGP 1,925,000 EGP 1,925,000
2 110V DC System (Battery & Battery Charger According To EDC) 1 EGP 300,000 EGP 300,000 1 EGP 300,000 EGP 300,000 1 EGP 300,000 EGP 300,000 1 EGP 300,000 EGP 300,000
3 22/0.4KV Dry Type Transformer - ANAF 2 EGP 1,372,500 EGP 2,745,000 2 EGP 1,035,000 EGP 2,070,000 2 EGP 1,035,000 EGP 2,070,000 2 EGP 1,035,000 EGP 2,070,000
4 Busway Between Transformer & MDB 200 EGP 50,000 EGP 10,000,000 200 EGP 30,000 EGP 6,000,000 200 EGP 30,000 EGP 6,000,000 200 EGP 30,000 EGP 6,000,000
5 400v MDB 1 EGP 4,595,635 EGP 4,595,635 1 EGP 4,595,635 EGP 4,595,635 1 EGP 4,653,600 EGP 4,653,600 1 EGP 4,595,635 EGP 4,595,635
6 PFC 2 EGP 579,144 EGP 1,158,288 2 EGP 579,144 EGP 1,158,288 2 EGP 361,965 EGP 723,930 2 EGP 361,965 EGP 723,930
7 Solution 0 EGP - EGP - 5 EGP 219,978 EGP 1,099,890 1 EGP 3,025,039 EGP 3,025,039 0 EGP - EGP -
8 Cables From MDB To Motor & Drive 150 EGP 7,776 EGP 1,166,400 150 EGP 7,776 EGP 1,166,400 150 EGP 6,442 EGP 966,300 150 EGP 6,442 EGP 966,300
9 Cables From MDB To Other Loads 40 EGP 3,619 EGP 144,760 40 EGP 3,619 EGP 144,760 40 EGP 1,769 EGP 70,760 40 EGP 1,769 EGP 70,760
10 400V LV Drive 5 EGP - 5 EGP 550,000 EGP 2,750,000 5 EGP 550,000 EGP 2,750,000 5 EGP 880,000 EGP 4,400,000
11 400V LV Motor 5 EGP 720,000 EGP 3,600,000 5 EGP 720,000 EGP 3,600,000 5 EGP 720,000 EGP 3,600,000 5 EGP 720,000 EGP 3,600,000
SH SH+PF SH+AHF LH
Standard Harmonic
Drive & Motor MV
14% 9%
Transformers
Cables 11%
5%
LV
22%
Busway
39%
Busway
24%
Cables
5%
LV
23%
Cables LV
4% 21%
MV Transformers Busway LV Cables Drive & Motor Solution
Low Harmonic
MV
9%
Transformers
Drive & Motor 8%
33%
Busway
24%
Cables
4%
LV
22%
MV Transformers Busway LV Cables Drive & Motor
De-tuned range
+ Harmonic
Standard range 1 Reinforced range 1 De-tuned range 2
filtering
solution 3