1100 K VAStandby
1100 K VAStandby
1100 K VAStandby
STANDBY
880 ekW 1100 kVA
50 Hz 1500 rpm 400 Volts
Caterpillar is leading the power generation
marketplace with Power Solutions engineered
to deliver unmatched flexibility, expandability,
reliability, and cost-effectiveness.
Image shown may not
reflect actual package.
FEATURES
FUEL/EMISSIONS STRATEGY CAT® C32 ATAAC DIESEL ENGINE
• Low Emissions • Utilizes ACERT™ Technology
• Reliable, rugged, durable design
DESIGN CRITERIA • Four-cycle diesel engine combines consistent
• The generator set accepts 100% rated load in one performance and excellent fuel economy with
step per NFPA 110 and meets ISO 8528-5 transient minimum weight
response. • Electronic engine control
FULL RANGE OF ATTACHMENTS CAT GENERATOR
• Wide range of bolt-on system expansion • Designed to match the performance and output
attachments, factory designed and tested characteristics of Cat diesel engines
• Flexible packaging options for easy and cost • Single point access to accessory connections
effective installation • UL 1446 recognized Class H insulation
SINGLE-SOURCE SUPPLIER CAT EMCP 4 CONTROL PANELS
• Fully prototype tested with certified torsional • Simple user friendly interface and navigation
vibration analysis available • Scalable system to meet a wide range of
customer needs
WORLDWIDE PRODUCT SUPPORT
• Integrated Control System and Communications
• Cat dealers provide extensive post sale support
Gateway
including maintenance and repair agreements
• Cat dealers have over 1,800 dealer branch stores
operating in 200 countries
• The Cat® S•O•SSM program cost effectively detects
internal engine component condition, even the
presence of unwanted fluids and combustion
by-products
STANDBY 880 ekW 1100 kVA
50 Hz 1500 rpm 400 Volts
Power Termination • Bus bar (NEMA or IEC mechanical lug holes) [ ] Circuit breakers, UL listed, 3 pole with shunt trip,
• Top cable entry 100% rated, manual or electrically operated
[ ] Circuit breakers, IEC compliant, 3 or 4 pole with
shunt trip, manual or electrically operated
[ ] Bottom cable entry
[ ] Power terminations can be located on the right, left
and/or rear as an option. Multiple circuit breaker
options
SPECIFICATIONS
TECHNICAL DATA
Meets or Exceeds International Specifications: AS1359, Ratings are based on SAE J1349 standard conditions.
CSA, IEC60034-1, ISO3046, ISO8528, NEMA MG 1-22, These ratings also apply at ISO3046 standard conditions.
NEMA MG 1-33, UL508A, 72/23/EEC, 98/37/EC, Fuel rates are based on fuel oil of 35º API [16º C (60º F)]
2004/108/EC gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb)
Standby - Output available with varying load for the when used at 29º C (85º F) and weighing 838.9 g/liter
duration of the interruption of the normal source power. (7.001 lbs/U.S. gal.). Additional ratings may be available
Average power output is 70% of the standby power for specific customer requirements, contact your Cat
rating. Typical operation is 200 hours per year, with representative for details. For information regarding Low
maximum expected usage of 500 hours per year. Sulfur fuel and Biodiesel capability, please consult your
Standby power in accordance with ISO8528. Fuel stop Cat dealer.
power in accordance with ISO3046. Standby ambients
shown indicate ambient temperature at 100% load which
results in a coolant top tank temperature just below the
shutdown temperature.
DIMENSIONS
Package Dimensions
Length Information not
Width available at this time.
Height