3SeriesCOMM A5

Download as pdf or txt
Download as pdf or txt
You are on page 1of 803

GE

Grid Solutions

3 Series
Protective Relay Platform
350 - 345 - 339

Communications Guide
3 Series revision: 2.6x
Manual P/N: 1601-0246-A5

E83849

LISTED
IND.CONT. EQ.
52TL

*1601-0246-A5*
Copyright © 2021 GE Multilin. All rights reserved.
GE Grid Solutions 3 Series Protective Relay Platform Communications Guide for revision
2.6x.
3 Series Protective Relay Platform, EnerVista, EnerVista Launchpad, and EnerVista 3 Series
Setup, are trademarks or registered trademarks of GE Multilin.
The contents of this manual are the property of GE Multilin. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin. The content of this manual is for informational use only and is subject to
change without notice.
Part number: 1601-0246-A5 (June 2021)

For further assistance


For product support, contact the information and call center as follows:
GE Grid Solutions
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Worldwide telephone: +1 905 927 7070
Europe/Middle East/Africa telephone: +34 94 485 88 54
North America toll-free: 1 800 547 8629
Fax: +1 905 927 5098
Worldwide e-mail: multilin.tech@ge.com
Europe e-mail: multilin.tech.euro@ge.com
Website: http://www.gegridsolutions.com/multilin

1-ii 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


Safety words and definitions
The following symbols used in this document indicate the following conditions:

Indicates a hazardous situation which, if not avoided, will result in death or serious
Note

injury.

Indicates a hazardous situation which, if not avoided, could result in death or serious
Note

injury.

Indicates a hazardous situation which, if not avoided, could result in minor or


Note

moderate injury.

Indicates practices not related to personal injury.


Note

Indicates general information and practices, including operational information and


practices, that are not related to personal injury.
NOTE

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 1-iii


1-iv 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
Table of Contents
1. INTRODUCTION Communications interfaces..........................................................................................1 - 2

2. RS485 INTERFACE Electrical Interface.............................................................................................................2 - 2


MODBUS Protocol ..............................................................................................................2 - 2
Data Frame Format and Data Rate.................................................................................2 - 2
Data Packet Format ................................................................................................................2 - 3
Error Checking ...........................................................................................................................2 - 3
CRC-16 Algorithm.....................................................................................................................2 - 4
Timing ............................................................................................................................................2 - 5
3 Series supported functions ..............................................................................................2 - 5
DNP protocol settings ......................................................................................................2 - 6
DNP communication...............................................................................................................2 - 6
DNP device profile....................................................................................................................2 - 7
DNP implementation ..............................................................................................................2 - 9
DNP serial EnerVista Setup ..................................................................................................2 - 13
DNP general................................................................................................................................2 - 15
IEC 60870-5-103 serial communication .................................................................2 - 17
Interoperability ..........................................................................................................................2 - 18
Physical layer............................................................................................................................2 - 18
Electrical interface........................................................................................................2 - 18
Optical interface............................................................................................................2 - 18
Transmission speed.....................................................................................................2 - 18
Link layer.....................................................................................................................................2 - 18
Application layer......................................................................................................................2 - 18
Transmission mode for application data ..........................................................2 - 18
Common address of ASDU.......................................................................................2 - 18
Selection of standard information numbers in monitor direction.........2 - 18
Selection of standard information numbers in control direction...........2 - 21
Basic application functions......................................................................................2 - 21
Miscellaneous.................................................................................................................2 - 22
Application level........................................................................................................................2 - 22
Application functions ............................................................................................................2 - 22
Type identification ..................................................................................................................2 - 22
Function type............................................................................................................................2 - 23
Information number ..............................................................................................................2 - 23
Data management ..................................................................................................................2 - 24
Digital states .............................................................................................................................2 - 24
Measurands...............................................................................................................................2 - 24
Commands ................................................................................................................................2 - 26
103 general settings ...............................................................................................................2 - 26

3. ETHERNET 350 Redundancy Options...............................................................................................3 - 2


INTERFACE 350 Parallel Redundancy Protocol (PRP)........................................................................3 - 4
350 High-availability Seamless Redundancy (HSR)..................................................3 - 5
350 Daisy Chain ........................................................................................................................3 - 5
350 LLA (Link Loss Alert) ........................................................................................................3 - 6
SNTP .........................................................................................................................................3 - 7
SNTP settings..............................................................................................................................3 - 7
SNTP modes................................................................................................................................3 - 7

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 2-v


MODBUS TCP/IP.................................................................................................................. 3 - 8
Data and control functions ................................................................................................. 3 - 8
Exception and error responses ......................................................................................... 3 - 9
Request response sequence .............................................................................................. 3 - 9
DNP Ethernet protocol settings................................................................................... 3 - 10
DNP communication .............................................................................................................. 3 - 10
DNP device profile ................................................................................................................... 3 - 11
DNP port allocation................................................................................................................. 3 - 13
DNP implementation .............................................................................................................. 3 - 14
DNP Ethernet EnerVista Setup ........................................................................................... 3 - 17
DNP general................................................................................................................................ 3 - 19
IEC60870-5-104 protocol............................................................................................... 3 - 22
IEC 60870-5-104 interoperability ..................................................................................... 3 - 22
IEC 60870-5-104 protocol settings.................................................................................. 3 - 30
IEC 60870-5-104 point lists ................................................................................................. 3 - 31
Summary of Ethernet client connections............................................................... 3 - 33

4. 3 SERIES IEC61850 GOOSE configuration via the 3 Series menus ......................................................4 - 2


GOOSE EnerVista 3 Series Setup software structure............................................................... 4 - 3
GOOSE transmission............................................................................................................... 4 - 5
GOOSE Rx..................................................................................................................................... 4 - 7
GOOSE Rx status ...................................................................................................................... 4 - 7
GOOSE Rx headers .................................................................................................................. 4 - 9
GOOSE receive dataset structure..................................................................................... 4 - 9
GOOSE remote inputs ............................................................................................................ 4 - 11
Using the Simplified GOOSE Configurator.............................................................. 4 - 13
Setting up the GOOSE Configurator ................................................................................ 4 - 14
Connection.................................................................................................................................. 4 - 16
Configuration ............................................................................................................................. 4 - 16
Using the IEC 61850 configurator.............................................................................. 4 - 27
Introduction to the 3 Series IEC61850 Device Configurator ............................... 4 - 27
3 Series GOOSE configuration - Lab................................................................................ 4 - 31
Configuration lab steps........................................................................................................4 - 33
IEC61850 Server ................................................................................................................. 4 - 46
Functionality............................................................................................................................... 4 - 48
IEC61850 Configurator.................................................................................................... 4 - 49
Online and offline setup........................................................................................................ 4 - 49
IEC 61850 Configurator Details ......................................................................................... 4 - 51
ICD/CID.........................................................................................................................................4 - 51
Settings........................................................................................................................................4 - 52
Reports.........................................................................................................................................4 - 55
GOOSE reception and GOOSE transmission...............................................................4 - 56

5. 350 OPC–UA Definitions and Acronyms ............................................................................................. 5 - 1


COMMUNICATION OPC–UA Architecture ....................................................................................................... 5 - 1
STANDARD OPC-UA Settings................................................................................................................. 5 - 2
OPC–UA Server Configuration Data.......................................................................... 5 - 2
OPC–UA Point Lists............................................................................................................ 5 - 3

6. USB INTERFACE MODBUS Protocol.............................................................................................................. 6 - 2


Data Frame Format and Data Rate ................................................................................ 6 - 2

2-vi 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


Data Packet Format ................................................................................................................6 - 2
Error Checking ...........................................................................................................................6 - 3
CRC-16 Algorithm.....................................................................................................................6 - 3
Timing ............................................................................................................................................6 - 4
3 Series supported functions ..............................................................................................6 - 4

7. 350 TIME 350 IEC 1588 Precision Time Protocol (PTP)...........................................................7 - 1


PROTOCOLS 350 Real Time Clock ................................................................................................................7 - 1

8. MODBUS Function Code 03H............................................................................................................8 - 1


FUNCTIONS Function Code 04H............................................................................................................8 - 3
Function Code 05H............................................................................................................8 - 4
Function Code 06H............................................................................................................8 - 9
Function Code 07H............................................................................................................8 - 10
Function Code 08H............................................................................................................8 - 11
Function Code 10H............................................................................................................8 - 11
Performing Commands Using Function Code 10H ..................................................8 - 13
Function Code 42H............................................................................................................8 - 14
Function Code 43H............................................................................................................8 - 15
Error Responses..................................................................................................................8 - 16

9. USING THE MODBUS User Map............................................................................................................9 - 2


MODBUS USER MAP

10. 339 MODBUS 339 MODBUS memory map..........................................................................................10 - 1


MEMORY MAP AND 339 Format Codes .............................................................................................................10 - 91
FORMAT CODES

11. 345 MODBUS 345 MODBUS memory map..........................................................................................11 - 1


MEMORY MAP AND 345 Format Codes .............................................................................................................11 - 78
FORMAT CODES

12. 350 MODBUS 350 MODBUS memory map..........................................................................................12 - 1


MEMORY MAP AND 350 Format Codes .............................................................................................................12 - 87
FORMAT CODES

A. IEC 61850 MICS..........................................................................................................................................A - 1


IMPLEMENTATION 1 INTRODUCTION......................................................................................................................A - 1
1.1 Logical Nodes List ...........................................................................................................A - 1
DETAILS
2 LOGICAL NODES ....................................................................................................................A - 4
2.1 System Logical Nodes. LN Group: L ........................................................................A - 4
2.2 Logical Nodes for protection functions. LN Group:P.......................................A - 5
2.3 Logical Nodes for protection related functions. LN Group: R .....................A - 19
2.4 Logical Nodes for generic references. LN Group: G........................................A - 24
2.5 Logical Nodes for metering and measurement. LN Group: M ...................A - 27

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 2-vii


2.6 Logical Nodes for switchgear. LN Group: X.........................................................A - 31
3 COMMON DATA CLASS....................................................................................................... A - 32
3.1 Common data class specifications for status information..........................A - 32
3.2 Common data class specifications for measurand information ..............A - 37
3.3 Common data class specifications for controllable status informationA - 45
3.4 Common data class specifications for description information...............A - 47
TICS........................................................................................................................................... A - 48
1 Introduction ............................................................................................................................A - 48
2 Implemented IntOp TISSUES........................................................................................... A - 48
Mandatory Edition 1 Tissues..............................................................................................A - 48
3 Other Implemented TISSUES........................................................................................... A - 50
PICS .......................................................................................................................................... A - 51
1 General...................................................................................................................................... A - 51
2 ASCI basic conformance statement............................................................................ A - 52
3 ACSI models conformance statement ....................................................................... A - 53
4 ACSI service conformance statement........................................................................ A - 55
PIXIT.......................................................................................................................................... A - 58
Introduction ................................................................................................................................ A - 58
PIXIT for Association model................................................................................................. A - 58
PIXIT for Server model............................................................................................................ A - 59
PIXIT for Data set model ....................................................................................................... A - 60
PIXIT for Substitution model................................................................................................A - 60
PIXIT for Setting group control model ............................................................................ A - 60
PIXIT for Reporting model .................................................................................................... A - 61
PIXIT for Logging model ........................................................................................................ A - 61
PIXIT for GOOSE publish model.......................................................................................... A - 62
PIXIT for GOOSE subscribe model .................................................................................... A - 63
PIXIT for GOOSE performance............................................................................................ A - 63
PIXIT for Control model.......................................................................................................... A - 64
PIXIT for Time synchronisation model............................................................................ A - 66
PIXIT for File transfer model................................................................................................A - 66
PIXIT for Service tracking model ......................................................................................A - 66

B. WARRANTY AND Warranty................................................................................................................................ B - 1


REVISION HISTORY Change notes ...................................................................................................................... B - 1
Manual Revision history........................................................................................................ B - 1
Major Updates........................................................................................................................... B - 2

2-viii 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


GE
Grid Solutions

3 Series Protective Relay Platform

Chapter 1: Introduction

Introduction

The Multilin 3 Series protective relay platform includes three different relays, the 350, 345,
and 339. Information in this manual applies to all 3 Series relays unless otherwise
indicated.
The 350 is a microprocessor-based relay for primary and backup overcurrent protection of
medium and low voltage distribution feeders. The relay is also suitable for providing
overcurrent and backup protection for small and medium size motors, transformers,
generators, and distribution bus-bars.
The 345 is a microprocessor-based relay for primary and backup protection of small to
medium size distribution transformers. The relay provides advanced algorithms for
automatic magnitude and phase compensation for more than twenty types of two-
winding transformers, good sensitivity for the detection of winding ground faults, and the
flexibility to set any of the phase, ground, neutral and negative sequence currents
overcurrent elements.
The 339 Motor Protection System is a microprocessor based relay providing suitable
protection of medium voltage motors. The basic protection functions of this relay include
motor thermal model, time-delayed and instantaneous overcurrent, ground overcurrent
and sensitive ground overcurrent protection. Additional control features such as logic
control are available for applications that require additional motor control functionality.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 1-1


COMMUNICATIONS INTERFACES CHAPTER 1: INTRODUCTION

Communications interfaces
Each 3 Series relay has three communications interfaces. These can be used
simultaneously:
• RS485
• USB
• Ethernet

1-2 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


GE
Grid Solutions

3 Series Protective Relay Platform

Chapter 2: RS485 interface

RS485 interface

The hardware or electrical interface in the 3 Series relay is two-wire RS485. In a two-wire
link, data is transmitted and received over the same two wires. Although RS485 two wire
communication is bi-directional, the data is never transmitted and received at the same
time. This means that the data flow is half duplex.
Polarity is important in RS485 communications. The '+' (positive) terminals of every device
NOTE:

must be connected together.


NOTE

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 2-1


ELECTRICAL INTERFACE CHAPTER 2: RS485 INTERFACE

Electrical Interface
RS485 lines should be connected in a daisy chain configuration with terminating networks
installed at each end of the link (i.e. at the master end and at the slave farthest from the
master). The terminating network should consist of a 120 W resistor in series with a 1 nF
ceramic capacitor when used with Belden 9841 RS485 wire. Shielded wire should always
be used to minimize noise. The shield should be connected to all of the 3 Series relay s as
well as the master, then grounded at one location only. This keeps the ground potential at
the same level for all of the devices on the serial link.

MODBUS Protocol
The 3 Series relay implements a subset of the Modicon Modbus RTU serial communication
standard. The Modbus protocol is hardware-independent. That is, the physical layer can be
any of a variety of standard hardware configurations. This includes USB, RS485, fibre
optics, etc. Modbus is a single master / multiple slave type of protocol suitable for a multi-
drop configuration.
The 3 Series relay is always a Modbus slave. It can not be programmed as a Modbus
master. Computers or PLCs are commonly programmed as masters.
Both monitoring and control are possible using read and write register commands. Other
commands are supported to provide additional functions.
The Modbus protocol has the following characteristics.
• Address: 1 to 254
• Supported Modbus function codes: 1H, 2H, 3H, 4H, 5H, 6H, 7H, 8H, 10H, 42H, 43H
For details see MODBUS Functions.

Data Frame Format and Data Rate


One data frame of an asynchronous transmission to or from a 3 Series relay typically
consists of 1 start bit, 8 data bits, and 1 stop bit. This produces a 10 bit data frame. This is
important for transmission through modems at high bit rates.
Modbus protocol can be implemented at any standard communication speed. The 3 Series
relay supports operation at 9600, 19200, 38400, 57600, and 115200 baud.
The USB interface will support only 115200 baud.
NOTE:

NOTE

2-2 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 2: RS485 INTERFACE MODBUS PROTOCOL

Data Packet Format


A complete request/response sequence consists of the following bytes (transmitted as
separate data frames):
Master Request Transmission:
SLAVE ADDRESS: 1 byte
FUNCTION CODE: 1 byte
DATA: variable number of bytes depending on FUNCTION CODE
CRC: 2 bytes
Slave Response Transmission:
SLAVE ADDRESS: 1 byte
FUNCTION CODE: 1 byte
DATA: variable number of bytes depending on FUNCTION CODE
CRC: 2 bytes
SLAVE ADDRESS: This is the first byte of every transmission. This byte represents the user-
assigned address of the slave device that is to receive the message sent by the master.
Each slave device must be assigned a unique address and only the addressed slave will
respond to a transmission that starts with its address. In a master request transmission the
SLAVE ADDRESS represents the address of the slave to which the request is being sent. In a
slave response transmission the SLAVE ADDRESS represents the address of the slave that is
sending the response.
FUNCTION CODE: This is the second byte of every transmission. Modbus defines function
codes of 1 to 127.
DATA: This will be a variable number of bytes depending on the FUNCTION CODE. This may
be Actual Values, Setpoints, or addresses sent by the master to the slave or by the slave to
the master.
CRC: This is a two byte error checking code.

Error Checking
The RTU version of Modbus includes a two byte CRC-16 (16 bit cyclic redundancy check)
with every transmission. The CRC-16 algorithm essentially treats the entire data stream
(data bits only; start, stop and parity ignored) as one continuous binary number. This
number is first shifted left 16 bits and then divided by a characteristic polynomial
(11000000000000101B). The 16 bit remainder of the division is appended to the end of the
transmission, MSByte first. The resulting message including CRC, when divided by the
same polynomial at the receiver will give a zero remainder if no transmission errors have
occurred.
If a 3 Series relay Modbus slave device receives a transmission in which an error is
indicated by the CRC-16 calculation, the slave device will not respond to the transmission.
A CRC-16 error indicates than one or more bytes of the transmission were received
incorrectly and thus the entire transmission should be ignored in order to avoid the 3 Series
relay performing any incorrect operation.
The CRC-16 calculation is an industry standard method used for error detection. An
algorithm is included here to assist programmers in situations where no standard CRC-16
calculation routines are available.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 2-3


MODBUS PROTOCOL CHAPTER 2: RS485 INTERFACE

CRC-16 Algorithm
Once the following algorithm is complete, the working register “A” will contain the CRC
value to be transmitted. Note that this algorithm requires the characteristic polynomial to
be reverse bit ordered. The MSBit of the characteristic polynomial is dropped since it does
not affect the value of the remainder. The following symbols are used in the algorithm:
—>: data transfer
A: 16 bit working register
AL: low order byte of A
AH: high order byte of A
CRC: 16 bit CRC-16 value
i, j: loop counters
(+): logical exclusive or operator
Di: i-th data byte (i = 0 to N-1)
G: 16 bit characteristic polynomial = 1010000000000001 with MSbit dropped and bit order
reversed
shr(x): shift right (the LSbit of the low order byte of x shifts into a carry flag, a '0' is shifted
into the MSbit of the high order byte of x, all other bits shift right one location
The algorithm is:

1. FFFF hex —> A

2. 0 —> i

3. 0 —> j

4. Di (+) AL —> AL

5. j+1 —> j

6. shr(A)

7. is there a carry? No: go to 8. Yes: G (+) A —> A

8. is j = 8? No: go to 5. Yes: go to 9.

9. i+1 —> i

10. is i = N? No: go to 3. Yes: go to 11.

11. A —> CRC

2-4 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 2: RS485 INTERFACE MODBUS PROTOCOL

Timing
Data packet synchronization is maintained by timing constraints. The receiving device
must measure the time between the reception of characters. If 3.5 character times elapse
without a new character or completion of the packet, then the communication link must
be reset (i.e. all slaves start listening for a new transmission from the master). Thus at
115200 baud a delay of greater than 3.5 x 1 / 115200 x 10 x = 0.3 ms will cause the
communication link to be reset.

3 Series supported functions


The following functions are supported by the 3 Series relay :
• FUNCTION CODE 03H - Read Setpoints
• FUNCTION CODE 04H - Read Actual Values
• FUNCTION CODE 05H - Execute Operation
• FUNCTION CODE 06H - Store Single Setpoint
• FUNCTION CODE 07H - Read Device Status
• FUNCTION CODE 08H - Loopback Test
• FUNCTION CODE 10H - Store Multiple Setpoints
Refer to section 6 of this guide for more details on MODBUS function codes.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 2-5


DNP PROTOCOL SETTINGS CHAPTER 2: RS485 INTERFACE

DNP protocol settings


DNP communication
The menu structure for the DNP protocol is shown below.

S1 DNP
DNP GENERAL S1 DNP GENERAL
DNP UNSOL RESPONSE* DNP ADDRESS
DEFAULT VARIATION • •
• • DNP TCP/UDP PORT
DNP CLIENT ADDRESS* CHANNEL 1 PORT
DNP POINTS LIST CHANNEL 2 PORT
TME SYNC IIN PER.
* Ethernet only
DNP MSG FRAG SIZE
DNP TCP CONN. T/O
FAULT REP MAPPING

DNP UNSOL RESPONSE*


FUNCTION POINT 0
• • • •
TIMEOUT POINT 1
MAX RETRIES POINT 2
DEST ADDRESS ...
POINT 63

DEFAULT VARIATION
DNP OBJECT 1 POINT 0 ON
• • • •
DNP OBJECT 2 POINT 0 OFF
DNP OBJECT 20 POINT 1 ON
DNP OBJECT 21 POINT 1 OFF
DNP OBJECT 22 ...
DNP OBJECT 23 POINT 15 ON
DNP OBJECT 30 POINT 15 OFF
DNP OBJECT 32
POINT 0 ENTRY
• •
DNP CLIENT ADDRESS*
POINT 1 ENTRY
CLIENT ADDRESS 1
POINT 2 ENTRY
• •
...
CLIENT ADDRESS 2
POINT 31 ENTRY
CLIENT ADDRESS 3
CLIENT ADDRESS 4
CLIENT ADDRESS 5

S1 DNP POINTS LIST


898769A2.cdr BINARY INPUTS
BINARY OUTPUTS
ANALOG INPUTS

Figure 2-1: DNP communication menu

2-6 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 2: RS485 INTERFACE DNP PROTOCOL SETTINGS

The following path is available using the keypad.


PATH: SETPOINTS > S1 RELAY SETUP > COMMUNICATIONS > DNP PROTOCOL > DNP GENERAL
To view the list of DNP Binary Inputs please refer to the Format Codes section - FC134B - of
this Guide.

DNP device profile

DNP 3.0 Device Profile

(Also see the IMPLEMENTATION TABLE in the following section)


Vendor Name: General Electric Multilin
Device Name: 3 Series relay
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Device Function:
□ Master
⊠ Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
Supported (the complete list is described in the attached table):

Binary Inputs (Object 1)


Binary Input Changes (Object 2)

Binary Outputs (Object 10)


Control Relay Output Block (Object 12)

Binary Counters (Object 20)


Frozen Counters (Object 21)
Counter Change Event (Object 22)
Frozen Counter Event (Object 23)

Analog Inputs (Object 30)


Analog Input Changes (Object 32)
Analog Deadbands (Object 34)

Time and Date (Object 50)

Internal Indications (Object 80)


Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):
Transmitted: 292 Transmitted: configurable up to 2048
Received: 292 Received: 2048
Maximum Data Link Re-tries: Maximum Application Layer Re-tries:
⊠None ⊠ None
□Fixed at 3 □ Configurable
□Configurable
Requires Data Link Layer Confirmation:
⊠ Never

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 2-7


DNP PROTOCOL SETTINGS CHAPTER 2: RS485 INTERFACE

DNP 3.0 Device Profile


□ Always
□ Sometimes
□ Configurable
Requires Application Layer Confirmation:
□ Never
□ Always
⊠ When reporting Event Data
⊠ When sending multi-fragment responses
□ Sometimes
□ Configurable
Timeouts while waiting for:
Data Link Confirm: ⊠ None □ Fixed □ Variable □ Configurable
Complete Appl. Fragment: ⊠ None □ Fixed □ Variable □ Configurable
Application Confirm: □ None ⊠ Fixed at 10 s □ Variable □ Configurable
Complete Appl. Response: ⊠ None □ Fixed at ___ □ Variable □ Configurable
Others:
Transmission Delay: No intentional delay
Need Time Interval: Configurable (default = 24 hrs.)
Select/Operate Arm Timeout: 10 s
Binary input change scanning period: 8 times per power system cycle
Analog input change scanning period: 500 ms
Counter change scanning period: 500 ms
Frozen counter event scanning period: 500 ms
Sends/Executes Control Operations:
WRITE Binary Outputs ⊠ Never □ Always □ Sometimes □Configurable
SELECT/OPERATE □ Never ⊠ Always □ Sometimes □ Configurable
DIRECT OPERATE □ Never ⊠Always □ Sometimes □ Configurable
DIRECT OPERATE – NO ACK □ Never ⊠ Always □ Sometimes □ Configurable
Count > 1 ⊠ Never □ Always □ Sometimes □ Configurable
Pulse On □ Never □ Always ⊠ Sometimes □ Configurable
Pulse Off □ Never □ Always ⊠ Sometimes □ Configurable
Latch On □ Never □ Always ⊠ Sometimes □ Configurable
Latch Off □ Never □ Always ⊠ Sometimes □ Configurable
Queue ⊠ Never □ Always □ Sometimes □ Configurable
Clear Queue ⊠ Never □ Always □ Sometimes □ Configurable
Explanation of ‘Sometimes’: Object 12 points are mapped to Virtual Inputs and Commands (Force
Coils). Both “Pulse On” and “Latch On” operations perform the same function in the 3 Series relay ;
that is, the appropriate Virtual Input or Coil is put into the “On” state. The On/Off times and Count
value are ignored. “Pulse Off” and “Latch Off” operations put the appropriate Virtual Input or Coil into
the “Off” state. “Trip” and “Close” operations both put the appropriate Virtual Input or coil into the
“On” state if a paired mapping is set, otherwise “Trip” will put into “Off” and “Close” will put into “On”.
Reports Binary Input Change Events when no Reports time-tagged Binary Input Change
specific variation requested: Events when no specific variation
requested:
□ Never □ Never
⊠ Only time-tagged ⊠ Binary Input Change With Time
□ Only non-time-tagged □ Binary Input Change With Relative Time
□ Configurable □ Configurable (attach explanation)
Sends Unsolicited Responses: Sends Static Data in Unsolicited Responses:

2-8 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 2: RS485 INTERFACE DNP PROTOCOL SETTINGS

DNP 3.0 Device Profile


□ Never ⊠ Never
□ Configurable □ When Device Restarts
□ Only certain objects □ When Status Flags Change
⊠ Sometimes No other options are permitted.
⊠ ENABLE/DISABLE unsolicited Function codes
supported
Explanation of ‘Sometimes’: It will be disabled for
RS-485 applications, since there is no collision
avoidance mechanism. For Ethernet communication
it will be available and it can be disabled or enabled
with the proper function code.
Default Counter Object/Variation: Counters Roll Over at:
□ No Counters Reported □ No Counters Reported
□ Configurable (attach explanation) □ Configurable (attach explanation)
⊠ Default Object: 20 ⊠ 16 Bits
Default Variation: 1
⊠ Point-by-point list attached □ Other Value: _____
⊠ Point-by-point list attached
Sends Multi-Fragment Responses:
⊠ Yes
□ No

DNP implementation

OBJECT REQUEST RESPONSE


OBJECT VARIATION DESCRIPTION FUNCTION QUALIFIER CODES FUNCTION QUALIFIER CODES
NO. NO. CODES (DEC) (HEX) CODES (DEC) (HEX)
1 0 Binary Input (Variation 0 is 1 (read) 22 00, 01 (start-stop) --- ---
used to request default (assign class) 06 (no range, or all)
variation) 07, 08 (limited
quantity) 17, 28
(index)
1 Binary Input 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
2 Binary Input with Status 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
2 0 Binary Input Change 1 (read) 06 (no range, or all) --- ---
(Variation 0 is used to 07, 08 (limited
request default variation) quantity)
1 Binary Input Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
without Time 07, 08 (limited 130 (unsol.
quantity) resp.)
2 Binary Input Change with 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Time 07, 08 (limited 130 (unsol.
quantity) resp.)
3 Binary Input Change with 1 (read) 06 (no range, or all) --- ---
Relative Time 07, 08 (limited
quantity)

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 2-9


DNP PROTOCOL SETTINGS CHAPTER 2: RS485 INTERFACE

OBJECT REQUEST RESPONSE


OBJECT VARIATION DESCRIPTION FUNCTION QUALIFIER CODES FUNCTION QUALIFIER CODES
NO. NO. CODES (DEC) (HEX) CODES (DEC) (HEX)
10 0 Binary Output Status 1 (read) 00, 01(start-stop) 06 --- ---
(Variation 0 is used to (no range, or all) 07,
request default variation) 08 (limited quantity)
17, 28 (index)
2 Binary Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
12 1 Control Relay Output Block 3 (select)4 00, 01 (start-stop) 129 (response) echo of request
(operate) 5 (direct 07, 08 (limited
op) 6 (dir. op, quantity) 17, 28
noack) (index)
20 0 Binary Counter (Variation 0 1 (read) 7 (freeze) 00, 01 (start-stop) --- ---
is used to request default 8 (freeze noack) 9 06 (no range, or all)
variation) (freeze clear) 10 07, 08 (limited
(frz. cl. noack) 22 quantity) 17, 28
(assign class) (index)
1 32-Bit Binary Counter 1 (read)7 (freeze) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
8 (freeze noack) 9 06 (no range, or all) 17, 28 (index) (see
(freeze clear) 10 07, 08 (limited Note 2)
(frz. cl. noack) 22 quantity) 17, 28
(assign class) (index)
2 16-Bit Binary Counter 1 (read) 7 (freeze) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
8 (freeze noack) 9 06 (no range, or all) 17, 28 (index) (see
(freeze clear) 10 07, 08 (limited Note 2)
(frz. cl. noack) 22 quantity) 17, 28
(assign class) (index)
5 32-Bit Binary Counter 1 (read) 7 (freeze) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
without Flag 8 (freeze noack) 9 06 (no range, or all) 17, 28 (index) (see
(freeze clear) 10 07, 08 (limited Note 2)
(frz. cl. noack) 22 quantity) 17, 28
(assign class) (index)
6 16-Bit Binary Counter 1 (read) 7 (freeze) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
without Flag 8 (freeze noack) 9 06 (no range, or all) 17, 28 (index) (see
(freeze clear) 10 07, 08 (limited Note 2)
(frz. cl. noack) 22 quantity) 17, 28
(assign class) (index)
21 0 Frozen Counter(Variation 0 1 (read) 22 00, 01 (start-stop) --- ---
is used to request (assign class) 06 (no range, or all)
defaultvariation) 07, 08 (limited
quantity) 17, 28
(index)
1 32-Bit Frozen Counter 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
2 16-Bit Frozen Counter 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
9 32-Bit Frozen Counter 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
without Flag (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
10 16-Bit Frozen Counter 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
without Flag (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)

2-10 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 2: RS485 INTERFACE DNP PROTOCOL SETTINGS

OBJECT REQUEST RESPONSE


OBJECT VARIATION DESCRIPTION FUNCTION QUALIFIER CODES FUNCTION QUALIFIER CODES
NO. NO. CODES (DEC) (HEX) CODES (DEC) (HEX)
22 0 Counter Change Event 1 (read) 06 (no range, or all) --- ---
(Variation 0 is used to 07, 08 (limited
request default variation) quantity)
1 32-Bit Counter Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event 07, 08 (limited 130 (unsol.
quantity) resp.)
2 16-Bit Counter Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event 07, 08 (limited 130 (unsol.
quantity) resp.)
5 32-Bit Counter Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event with Time 07, 08 (limited 130 (unsol.
quantity) resp.)
6 16-Bit Counter Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event with Time 07, 08 (limited 130 (unsol.
quantity) resp.)
23 0 Frozen Counter Event 1 (read) 06 (no range, or all) --- ---
(Variation 0 is used to 07, 08 (limited
request default variation) quantity)
1 32-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited 130 (unsol.
quantity) resp.)
2 16-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited 130 (unsol.
quantity) resp.)
5 32-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited 130 (unsol.
quantity) resp.)
6 16-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited 130 (unsol.
quantity) resp.)
30 0 Analog Input (Variation 0 is 1 (read) 22 00, 01 (start-stop) --- ---
used to request default (assign class) 06 (no range, or all)
variation) 07, 08 (limited
quantity) 17, 28
(index)
1 32-Bit Analog Input 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
2 16-Bit Analog Input 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
3 32-Bit Analog Input without 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Flag (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
4 16-Bit Analog Input without 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Flag (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
32 0 Analog Change Event 1 (read) 06 (no range, or all) --- ---
(Variation 0 is used to 07, 08 (limited
request default variation) quantity)
1 32-Bit Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
without Time 07, 08 (limited 130 (unsol.
quantity) resp.)

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 2-11


DNP PROTOCOL SETTINGS CHAPTER 2: RS485 INTERFACE

OBJECT REQUEST RESPONSE


OBJECT VARIATION DESCRIPTION FUNCTION QUALIFIER CODES FUNCTION QUALIFIER CODES
NO. NO. CODES (DEC) (HEX) CODES (DEC) (HEX)
2 16-Bit Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
without Time 07, 08 (limited 130 (unsol.
quantity) resp.)
3 32-Bit Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited 130 (unsol.
quantity) resp.)
4 16-Bit Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited 130 (unsol.
quantity) resp.)
34 0 Analog Input Reporting 1 (read) 00, 01 (start-stop) --- ---
Deadband (Variation 0 is 06 (no range, or all)
used to request 07, 08 (limited
defaultvariation) quantity) 17, 28
(index)
1 16-bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Reporting Deadband 06 (no range, or all) 17, 28 (index) (see
(default - see Note 1) 07, 08 (limited Note 2)
quantity) 17, 28
(index)
2 (write) 00, 01 (start-stop) --- ---
07, 08 (limited
quantity) 17, 28
(index)
2 32-bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Reporting Deadband 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
2 (write) 00, 01 (start-stop) --- ---
07, 08 (limited
quantity) 17, 28
(index)
50 1 Time and Date (default - 1 (read)2 (write) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
see Note 1) 06 (no range, or all) 17, 28 (index) (see
07 (limited qty=1) 08 Note 2)
(limited quantity) 17,
28 (index)
60 0 Class 0, 1, 2, and 3 Data 1 (read) 20 06 (no range, or all) --- ---
(enable unsol) 21
(disable unsol) 22
(assign class)
1 Class 0 Data 1 (read) 22 06 (no range, or all) --- ---
(assign class)
2 Class 1 Data 1 (read) 20 06 (no range, or all) --- ---
(enable unsol) 07, 08 (limited
quantity)
3 Class 2 Data 21 (disable unsol) --- ---
4 Class 3 Data 22 (assign class) --- ---
80 1 Internal Indications 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(index =7)
2 (write) (see 00 (start-stop) (index --- ---
Note 3) =7)
No Object (function code 13 (cold restart) --- --- ---
only) see Note 3
No Object (function code 14 (warm restart) --- --- ---
only)
No Object (function code 23 (delay meas.) --- --- ---
only)

2-12 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 2: RS485 INTERFACE DNP PROTOCOL SETTINGS

1. A default variation refers to the variation response when variation 0 is requested and/
NOTE:

or in class 0, 1, 2, or 3 scans. The default variations for object types 1, 2, 20, 21, 22, 23,
NOTE 30, and 32 are selected via relay settings. This optimizes the class 0 poll data size.
2. For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a
request is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests
sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for
change event objects, qualifiers 17 or 28 are always responded.)
Cold restarts are implemented the same as warm restarts – the 3 Series relay is not
restarted, but the DNP process is restarted.

DNP serial EnerVista Setup


The following tables show the settings needed to configure all the DNP 3.0 implementation
parameters.
Table 2-1: RS-485
SETTINGS PARAMETER RANGE FORMAT
RS485 Baud Rate 115200 9600, 19200, 38400, 57600, F101
115200
RS485 Comm Parity None None, Odd, Even F102
Rear 485 Protocol DNP 3.0 Modbus, IEC60870-5-103, DNP F97
3.0

In order to activate DNP 3.0 at the RS485 rear port, the setting "Rear 485 Protocol" must be
set to DNP 3.0. Once the setting has been changed, the relay must be switched off, then
switched on.
Table 2-2: DNP protocol
SETTINGS PARAMETER RANGE FORMAT
DNP Unsol Resp Function Disabled Disabled ; Enabled F126
DNP Unsol Resp Timeout 5s 0 to 60 s F1
DNP Unsol Resp Max Retries 10 1 to 255 F1
DNP Unsol Resp Dest Addr 1 0 to 65519 F1
DNP Time Sync IIN Period 1440 min 1 to 10080 min F1
DNP Message Fragment Size 240 30 to 2048 F1

DNP Object 1 Default Variation 2 1;2 F1


DNP Object 2 Default Variation 2 1;2 F1
DNP Object 20 Default Variation 1 1;2,5;6 F78
DNP Object 21 Default Variation 1 1 ; 2 ; 9 ; 10 F79
DNP Object 22 Default Variation 1 1;2,5;6 F80
DNP Object 23 Default Variation 1 1;2,5;6 F81
DNP Object 30 Default Variation 1 1 ; 2 ;3 ; 4 F82
DNP Object 32 Default Variation 1 1 ; 2 ;3 ; 4 F83
DNP TCP Connection Timeout 120 s 10 to 300 s F1
Fault Report Mapping in DNP/104 Disabled Disabled, Enabled F126

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 2-13


DNP PROTOCOL SETTINGS CHAPTER 2: RS485 INTERFACE

Table 2-3: DNP point list


SETTINGS PARAMETER RANGE FORMAT
Binary Input Point 0 Entry Select entry Operands F134B
from a list

Binary Input Point 63 Entry Select entry Operands F134B


from a list

Analog Input Point 0 Entry Select entry Analog parameters F88


from a list
Analog Input Point 0 Scale Factor 1 0.001 ; 0.01 ; 0.1 ; 1 ; 10 ; 100 ; F85
1000 ; 10000 ; 100000
Analog Input Point 0 Deadband 30000 0 to 100000000 F9

Analog Input Point 31 Entry Select entry Analog parameters F88


from a list
Analog Input Point 31 Scale Factor 1 0.001 ; 0.01 ; 0.1 ; 1 ; 10 ; 100 ; F85
1000 ; 10000 ; 100000
Analog Input Point 31 Deadband 30000 0 to 100000000 F9

Binary Output Point 0 ON Select entry Virtual Input 1 to 32 and Force F86
from a list Coils
Binary Output Point 0 OFF Select entry Virtual Input 1 to 32 and Force F86
from a list Coils

Binary Output Point 15 ON Select entry Virtual Input 1 to 32 and Force F86
from a list Coils
Binary Output Point 15 OFF Select entry Virtual Input 1 to 32 and Force F86
from a list Coils

• DNP UNSOL RESPONSE FUNCTION should be “Disabled” for RS485 applications, since
there is no collision avoidance mechanism.
• The DNP Time Sync IIN Period setting determines how often the Need Time Internal
Indication (IIN) bit is set by the 3 Series relay. Changing this time allows the 3 Series
relay to indicate that a time synchronization command is necessary more or less often
• Various settings have been included to configure Default Variation for the Binary
Inputs, Counters and Analog Inputs Objects. The default variation refers to the
variation response when variation 0 is requested, and/or in class 0, 1, 2, or 3 scans
• Up to 64 Binary Inputs and 32 Analog Input entries can be mapped to an item from a
list of 3 Series relay status events and metered values. Status events correspond to
format FC134B.
• Each Analog Input point Deadband and Scale Factor can be set individually instead of
setting a general deadband or scale for different metering groups. This will avoid scale
and deadband conflicts for different meterings of the same nature.
• Up to 16 Binary/Control Outputs can be configured by selecting a Virtual Input or
Command from a list of 32 Virtual Inputs and Commands (Force Coils). Some legacy
DNP implementations use a mapping of one DNP Binary Output to two physical or
virtual control points. In Order to configure Paired Control Points the source for states
ON and OFF should be set to different Virtual Inputs or Commands.
• The DNP Technical Committee recommends using contiguous point numbers, starting
at 0, for each data type, because some DNP3 Master implementations allocate
contiguous memory from point 0 to the last number for each data type.

2-14 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 2: RS485 INTERFACE DNP PROTOCOL SETTINGS

Binary Inputs are inputs to the Master. Binary Outputs are outputs from the Master.
NOTE:

NOTE

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 2-15


DNP PROTOCOL SETTINGS CHAPTER 2: RS485 INTERFACE

DNP general
Default variations for Object 1, 2 , 20 , 21 , 22 , 23 , 30 and Object 32 will be set by settings
and returned for the object in a response when no specific variation is specified in a Master
request.
Any change in the state of any binary point causes the generation of an event, and
consequently, if configured, an unsolicited response. Alternatively it is returned when the
Master asks for it. The same behavior will be seen when an analog value changes by more
than its configured deadband limit. There can be up to 3 masters in total, but only one
Serial Master.
The following Default Classes will be fixed for the different blocks of data:
Binary Input Points Default Class = 1
Analog Input Point Default Class = 2
Counters Default Class = 3
Each Data Point Class can be changed by protocol function code 22 in volatile mode. If a
restart is performed, the new values will be lost.
DNP Object 34 points can be used to change deadband values from the default for each
individual DNP Analog Input point. These new deadbands will be maintained such that in
the case of a relay restart, the values are not lost.
For the 350 and 339 relays, one Binary Counter has been hardcoded such that no option
can be modified by setting:
• Total_Number_of_Trips
Requests for Object 20 (Binary Counters), Object 21 (Frozen Counters), and Object 22
(Counter Change Events) must be accepted.
Function codes “Immediate Freeze”, “Freeze and Clear” etc. are accepted as well.
The FAULT REPORT MAPPING IN DNP/104 setpoint may be set to a value of "Disabled" or
"Enabled". When "Disabled", only the configurable Analog Input points are available
beginning at point index 0.When "Enabled", the Fault Report Values are assigned from
point 0 to 32 in the 339 and 350 relays, and from 0 to 38 in the 345 relay, with the
configurable Analog Inputs following the point numbers.
To support existing SCADA hardware not capable of 32-bit data reads, the upper and lower
16-bit portions of the fault report time and date values have been assigned to separate
points. To read a date or time, it is necessary to read both the upper and lower 16-bit
portions, concatenate these two values to form a 32-bit value and interpret the result in
the format associated with the point.

Fault Report Mapping 350 and 339 Fault Report Mapping 345
Disabled Enabled Disabled Enabled
- 0 Fault Report Date Upper 16 - 0 Fault Report Date Upper 16
- 1 Fault Report Date Lower 16 - 1 Fault Report Date Lower 16
- 2 Fault Report Time Upper 16 - 2 Fault Report Time Upper 16
- 3 Fault Report Time Lower 16 - 3 Fault Report Time Lower 16
- 4 Fault Report Fault Type - 4 Fault Report Fault Type
- 5 Fault Report Ia - 5 Fault Report Ia
- 6 Fault Report Ia Angle - 6 Fault Report Ia Angle
- 7 Fault Report Ib - 7 Fault Report Ib
- 8 Fault Report Ib Angle - 8 Fault Report Ib Angle
- 9 Fault Report Ic - 9 Fault Report Ic
- 10 Fault Report Ic Angle - 10 Fault Report Ic Angle
- 11 Fault Report Ig - 11 Fault Report Ig
- 12 Fault Report Ig Angle - 12 Fault Report Ig Angle

2-16 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 2: RS485 INTERFACE DNP PROTOCOL SETTINGS

Fault Report Mapping 350 and 339 Fault Report Mapping 345
Disabled Enabled Disabled Enabled
- 13 Fault Report In - 13 Fault Report In
- 14 Fault Report In Angle - 14 Fault Report In Angle
- 15 Fault Report Va - 15 Fault Report System Frequency
- 16 Fault Report Va Angle - 16 Fault Report Ia 2
- 17 Fault Report Vb - 17 Fault Report Ia 2 Angle
- 18 Fault Report Vb Angle - 18 Fault Report Ib 2
- 19 Fault Report Vc - 19 Fault Report Ib 2 Angle
- 20 Fault Report Vc Angle - 20 Fault Report Ic 2
- 21 Fault Report Vab - 21 Fault Report Ic 2 Angle
- 22 Fault Report Vab Angle - 22 Fault Report Ig 2
- 23 Fault Report Vbc - 23 Fault Report Ig 2 Angle
- 24 Fault Report Vbc Angle - 24 Fault Report In 2
- 25 Fault Report Vca - 25 Fault Report In 2 Angle
- 26 Fault Report Vca Angle - 26 Fault Report Idiff 1 PhA
- 27 Fault Report Vn - 27 Fault Report Idiff 1 PhA Angle
- 28 Fault Report Vn Angle - 28 Fault Report I Restraint PhA
- 29 Fault Report Vaux - 29 Fault Report I Restraint PhA Angle
- 30 Fault Report Vaux Angle - 30 Fault Report Idiff 1 PhB
- 31 Fault Report System Frequency - 31 Fault Report Idiff 1 PhB Angle
- 32 Fault Report Phases - 32 Fault Report I Restraint Ph B
0 33 Analog Input Point 0 Entry - 33 Fault Report I Restraint PhB Angle
1 34 Analog Input Point 1 Entry - 34 Fault Report Idiff 1 PhC
… … … - 35 Fault Report Idiff 1 PhC Angle
… … … - 36 Fault Report I Restraint PhC
31 64 Analog Input Point 31 Entry - 37 Fault Report I Restraint PhC Angle
- 38 Fault Report Phases
0 39 Analog Input Point 0 Entry
1 40 Analog Input Point 1 Entry
… … …
… … …
31 70 Analog Input Point 31 Entry

Some fault report data has been scaled to fit into a 16-bit value as follows:

Fault Report Data Scale


Fault Report Ia, Ib, Ic, Ia2, Ib2, Ic2 Format_F10 * 100 / CT Primary
Fault Report Ig, Ig2 Format_F10 * 100 / Gnd CT Primary
Fault Report In , In2 Format_F10 * 100 / CT Primary
Fault Report Va, Vb, Vc, Vab, Vbc, Vca, Vn Format_F9 * 10000 /( BusVTRatio * BusVTSecondary)
Fault Report Vaux Format_F9 * 10000 /( AuxVTRatio * AuxVTSecondary)
Fault Report System Frequency Format_F3
Fault Report Phases Format_F37

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 2-17


IEC 60870-5-103 SERIAL COMMUNICATION CHAPTER 2: RS485 INTERFACE

IEC 60870-5-103 serial communication

S1 60870-5-103
GENERAL S1 103 GENERAL
BINARY INPUTS SLAVE ADDRESS
MEASURANDS ▼
▼ SYNCH TIMEOUT
COMMANDS
S1 103 FIRST ASDU
S1 103 B INPUTS ID TYPE
POINT 0 ▼
▼ FUNCTION TYPE
POINT 0 FUNC TYPE INFORMATION NO
POINT 0 INFO NO SCAN TIMEOUT
... FIRST ANLG ENTRY
POINT 63 FIRST ANLG FACTOR
POINT 63FUNC TYPE FIRST ANLG OFFSET
POINT 63 INFO NO ...
NINTH ANLG ENTRY
NINTH ANLG FACTOR
S1 103 MEASURANDS NINTH ANLG OFFSET
FIRST ASDU .
SECOND ASDU .
THIRD ASDU .
.

FOURTH ASDU S1 103 FOURTH ASDU
ID TYPE

S1 103 B COMMANDS FUNCTION TYPE
CMD 0 FUNC TYPE INFORMATION NO
▼ SCAN TIMEOUT
CMD 0 INFO NO FIRST ANLG ENTRY
CMD 0 ON OPER FIRST ANLG FACTOR
CMD 0 OFF OPER FIRST ANLG OFFSET
... ...
CMD 15 FUNC TYPE NINTH ANLG ENTRY
CMD 15 INFO NO NINTH ANLG FACTOR
CMD 15 ON OPER NINTH ANLG OFFSET
898770A1.cdr CMD 15 OFF OPER

Figure 2-2: IEC 60870-5-103 serial communication menu

PATH: SETPOINTS > S1 RELAY SETUP > COMMUNICATIONS > IEC61870-5-103


To view the list of Binary Inputs please refer to the Format Codes section - FC134B - of this
Guide.

2-18 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 2: RS485 INTERFACE IEC 60870-5-103 SERIAL COMMUNICATION

Interoperability

Physical layer

Electrical interface

⊠ EIA RS-485
32 Number of loads for one protection equipment

Optical interface

□ Glass fibre
□ Plastic fibre
□ F-SMA type connector
□ BFOC/2,5 type connector

Transmission speed

⊠ 9600 bits/s
⊠ 19200 bits/s

Link layer There are no choices for the Link Layer.

Application layer

Transmission mode for application data


Mode 1 (least significant octet first), is used exclusively in this companion standard.

Common address of ASDU

⊠ One COMMON ADDRESS OF ASDU (identical with station address)


More than one COMMON ADDRESS OF ASDU

Selection of standard information numbers in monitor direction


Table 2-4: System functions in monitor direction
INF Semantics
⊠ <0> End of general interrogation
⊠ <0> Time synchronization
⊠ <2> Reset FCB
⊠ <3> Reset CU
⊠ <4> Start/restart
⊠ <5> Power on

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 2-19


IEC 60870-5-103 SERIAL COMMUNICATION CHAPTER 2: RS485 INTERFACE

Table 2-5: Status indications in monitor direction


INF Semantics 3 Series relay 3 Series relay
Identifier Data Text
□ <16> Auto-recloser active
□ <17> Teleprotection active
□ <18> Protection active
□ <19> LED reset
□ <20> Monitor direction blocked
□ <21> Test mode
□ <22> Local parameter setting
□ <23> Characteristic 1
□ <24> Characteristic 2
□ <25> Characteristic 3
□ <26> Characteristic 4
□ <27> Auxiliary input 1
□ <28> Auxiliary input 2
□ <29> Auxiliary input 3
□ <30> Auxiliary input 4

Table 2-6: Supervision indications in monitor direction


INF Semantics 3 Series relay 3 Series relay
Identifier Data Text
□ <32> Measurand supervision I
□ <33> Measurand supervision V
□ <35> Phase sequence supervision
□ <36> Trip circuit supervision
□ <37> I>> back-up operation
□ <38> VT fuse failure
□ <39> Teleprotection disturbed
□ <46> Group warning
□ <47> Group alarm

Table 2-7: Earth fault indications in monitor direction


INF Semantics 3 Series relay 3 Series relay
Identifier Data Text
□ INF Semantics 3 Series relay 3 Series relay
Identifier Data Text
□ <48> Earth fault L1
□ <49> Earth fault L2
□ <50> Earth fault L3
□ <51> Earth fault forward, i.e. line
□ <52> Earth fault reverse, i.e. busbar

Table 2-8: Fault indications in monitor direction


INF Semantics 3 Series relay 3 Series relay
Identifier Data Text
□ INF Semantics 3 Series relay 3 Series relay
Identifier Data Text
□ <64> Start / pick-up L1
□ <65> Start / pick-up L2
□ <66> Start / pick-up L3

2-20 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 2: RS485 INTERFACE IEC 60870-5-103 SERIAL COMMUNICATION

INF Semantics 3 Series relay 3 Series relay


Identifier Data Text
□ <67> Start / pick-up N
□ <68> General trip
□ <69> Trip L1
□ <70> Trip L2
□ <71> Trip L3
□ <72> Trip I>> (back-up operation)
□ <73> Fault location X in ohms
□ <74> Fault forward / line
□ <75> Fault reverse / busbar
□ <76> Teleprotection signal transmitted
□ <77> Teleprotection signal received
□ <78> Zone 1
□ <79> Zone 2
□ <80> Zone 3
□ <81> Zone 4
□ <82> Zone 5
□ <83> Zone 6
□ <84> General start / pick-up
□ <85> Breaker failure
□ <86> Trip measuring system L1
□ <87> Trip measuring system L2
□ <88> Trip measuring system L3
□ <89> Trip measuring system E
□ <90> Trip I>
□ <91> Trip I>>
□ <92> Trip IN>
□ <93> Trip IN>>

Table 2-9: Auto-reclosure indications in monitor direction


INF Semantics 3 Series relay 3 Series relay
Identifier Data Text
□ <128> CB ‘on’ by AR
□ <129> CB ‘on’ by long-time AR
□ <130> AR blocked

Table 2-10: Measurands in monitor direction


INF Semantics 3 Series relay 3 Series relay
Identifier Data Text
□ <144> Measurand I
□ <145> Measurands I, V
□ <146> Measurands I, V, P, Q
□ <147> Measurands In, Ven
□ <148> Measurands IL123, VL123, P, Q, f

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 2-21


IEC 60870-5-103 SERIAL COMMUNICATION CHAPTER 2: RS485 INTERFACE

Table 2-11: Generic functions in monitor direction


INF Semantics
□ <240> Read headings of all defined groups
□ <241> Read values or attributes of all entries of one group
□ <243> Read directory of a single entry
□ <244> Read value or attribute of a single entry
□ <245> End of general interrogation of generic data
□ <249> Write entry with confirmation
□ <250> Write entry with execution
□ <251> Write entry aborted

Selection of standard information numbers in control direction


Table 2-12: System functions in control direction
INF Semantics
⊠ <0> Initiation of general interrogation
⊠ <0> Time synchronization

Table 2-13: General commands in control direction


INF Semantics
□ <16> Auto-recloser on / off
□ <17> Teleprotection on / off
□ <18> Protection on / off
□ <19> LED reset
□ <23> Activate characteristic 1
□ <24> Activate characteristic 2
□ <25> Activate characteristic 3
□ <26> Activate characteristic 4

Table 2-14: General functions in control direction


INF Semantics
□ <240> Read headings of all defined groups
□ <241> Read values or attributes of all entries of one group
□ <243> Read directory of a single entry
□ <244> Read value or attribute of a single entry
□ <245> General interrogation of generic data
□ <248> Write entry
□ <249> Write entry with confirmation
□ <250> Write entry with execution
□ <251> Write entry abort

Basic application functions

□ Test mode
□ Blocking of monitor direction
□ Disturbance data
□ Generic services
□ Private data

2-22 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 2: RS485 INTERFACE IEC 60870-5-103 SERIAL COMMUNICATION

Miscellaneous

Measurand Max. MVAL = times rated value


1,2 or 2,4
Current L1 □ ⊠
Current L2 □ ⊠
Current L3 □ ⊠
Voltage L1-E □ ⊠
Voltage L2-E □ ⊠
Voltage L3-E □ ⊠
Active power P □ ⊠
Reactive power Q □ ⊠
Frequency f □ ⊠
Voltage L1-L2 □ ⊠

Application level

Application functions The unbalanced transmission mode of the protocol is used to avoid the possibility of more
than one protection device attempting to transmit on the channel at the same time, over
the RS485 port.
Data is transferred to the primary or control station (master) using the “data acquisition by
polling” principle. Cyclically, the master will request class 2 data to the secondary station
(slave).
When slave has class 1 data (high priority) pending, the ACD control bit will be set to 1
demanding the master to request for that data.
Periodically, the master may send a General Interrogation in order to update the complete
database.
The measurands will be sent to the primary station as a response to class 2 request. A
setting (0 to 60 min) is available to configure the desired interval, where 0 means
transmission as fast as possible.
The following functions are supported:
• Initialization
• General Interrogation
• Synchronization
• Commands transmission

Type identification The Type Identification implemented will be:


TYPE IDENTIFICATION UI8[1..8] <1..255>
<1..31>:= definitions of this companion standard(compatible range)
<32..255>:= for special use (private range)
Information in monitor direction:
<1>:= time-tagged message
<3>:= measurands I
<5>:= identification
<6>:= time synchronization
<8>:= general interrogation termination
<9>:= measurands II
Information in control direction:

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 2-23


IEC 60870-5-103 SERIAL COMMUNICATION CHAPTER 2: RS485 INTERFACE

<6>:= time synchronization


<7>:= general interrogation
<20>:= general command

Function type FUNCTION TYPE UI8 [1..8] <0..255>


<0..127>:= private range
<128..129>:= compatible range
<130..143>:= private range
<144..145>:= compatible range
<146..159>:= private range
<160..161>:= compatible range
<162..175>:= private range
<176..177>:= compatible range
<178..191>:= private range
<192..193>:= compatible range
<194..207>:= private range
<208..209>:= compatible range
<210..223>:= private range
<224..225>:= compatible range
<226..239>:= private range
<240..241>:= compatible range
<242..253>:= private range
<254..255>:= compatible range
The 3 Series relay is identified in this protocol as “overcurrent protection”, so it will use the
Function Type <160> for all the digital and analogues points proposed by the standard and
mapped in this profile. For the other data supported by the device, the customer will have
the capability to use them by setting a number from the private range.

Information number INFORMATION NUMBER := UI8 [1..8] <0..255>


Monitor direction := <0..255>

<0..15>:=system functions
<16..31>:= status
<32..47>:=supervision
<48..63>:=earth fault
<64..127>:=short circuit
<128..143>:=auto-reclosure
<144..159>:=measurands
<160..239>:=not used
<240..255>:=generic functions

Control direction:=<0..255>

<0..15>:=system functions
<16..31>:=general commands
<32..239>:=not used
<240..255>:=generic functions

2-24 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 2: RS485 INTERFACE IEC 60870-5-103 SERIAL COMMUNICATION

Data management
The 3 Series relay supports a fixed profile and data that is configurable using the EnerVista
3 Series Setup program.
The data that can be configured are:
• digital states
• measurands
• commands.

Digital states Digital states in the relay may be mapped using the EnerVista 3 Series Setup program. By
default, states are mapped to information numbers proposed by the standard, but the
user may delete these mappings if desired.
All the mapped information will be sent as a response to a general interrogation like ASDU
1.
For the other states, the customer can assign:
1. Information Number <1..255>
2. Function Type <0..255>.

Settings Digital Status Information Number Function Type


Point 1 Entry Select entry from list <0 – 255 > <0 – 255 >
….
.…
Point 64 Entry Select entry from list <0 – 255 > <0 – 255 >

This means that for each digital point 3 settings are required.
Example:

Modbus Address Description Value Format


43879 Point 1 Entry Digital Status 0x8242 (Undercurrent Trip) FC134
44223 Point 1 Entry Function Type 160 F1
44224 Point 1 Entry Information Number 144 F1

The “Point Entry Digital Status” reuses the DNP Binary Input 43029, 43030, …

Measurands Some analog points are supported by the 3 Series relay with compatible information
numbers that have been identified in the device profile.
For the other measurands, it is possible to use the EnerVista 3 Series Setup to select the
desired point and assign the Identification Type (3 or 9), Function Type <0..255>, and
Information Number <1..255>.
If the user selects Identification Type 3 (ASDU 3) only four measurands are available for
configuration, but if Identification Type 9 (ASDU 9) is selected, up to nine measurands can
be sent in the IEC103 slave answer. For each measurand, all metering values that the 3
Series relay supports, are available in order to be mapped. There are 3 possible
configurable ASDUS.
For example, eDataVab is the index in the Modbus Memory Map.

Modbus Address Description Value Format


44384 First ASDU Identification Type 3 or 9 F221
44385 First ASDU Function Type <0 - 255 > F1
44386 First ASDU Information Number < 0 - 255 > F1
44387 First ASDU Scan Timeout < 0 - 1000> secs F1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 2-25


IEC 60870-5-103 SERIAL COMMUNICATION CHAPTER 2: RS485 INTERFACE

Modbus Address Description Value Format


44388 First ASDU First Analogue Entry Disabled F88
44389 First ASDU First Analogue Factor 1 F3
44390 First ASDU First Analogue Offset 0 F1
44391 First ASDU Second Analogue Entry Disabled F88
44392 First ASDU Second Analogue Factor 1 F3
44393 First ASDU Second Analogue Offset 0 F1
………
44412 First ASDU Ninth Analogue Entry Disabled F88
44413 First ASDU Ninth Analogue Factor 1 F3
44414 First ASDU Ninth Analogue Offset 0 F1
44415 Second ASDU Identification Type 3 or 9 F221
44416 Second ASDU Function Type <0 - 255 > F1
44417 Second ASDU Information Number < 0 - 255 > F1
44418 Second ASDU Scan Timeout < 0 - 1000> secs F1
44419 Second ASDU First Analogue Entry Disabled
44420 Second ASDU First Analogue Factor 1 F3
44421 Second ASDU First Analogue Offset 0 F1
…..
44443 Second ASDU Ninth Analogue Entry Disabled
44444 Second ASDU Ninth Analogue Factor 1 F3
44445 Second ASDU Ninth Analogue Offset 0 F1
44446 Third ASDU Identification Type 3 or 9 F221
……
44476 Third ASDU Ninth Analogue Offset 0 F1
44477 Fourth ASDU Identification Type 3 or 9 F221
……
44507 Third ASDU Ninth Analogue Offset 0 F1

In the measurands configuration screen, with each selected measurement, a Factor and
an Offset must be configured.
• The Factor is a multiplier factor.
• The Offset is an offset factor to be applied to the relay measurement to make the final
measurement calculation to be sent to the master
The factor and offset parameters allow the user to perform different scaling in the relay
measurements. The final measurement sent to the IEC103 master will be: “a*x+b”, where
“x” is the relay measurement, “a” is the multiplier factor and “b” is the offset.
The measurands will be sent to the primary station as a response to a class 2 request.
There is a Timeout configurable with increments of 100 ms, between 0 and 60 min, in order
to configure the desired interval.

2-26 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 2: RS485 INTERFACE IEC 60870-5-103 SERIAL COMMUNICATION

Commands All the commands and virtual inputs are available to be mapped using the EnerVista Setup
program. It is possible to choose the desired command for the ON state and the same or
different command for the OFF state.
The user is able to select the Information Number <1..255> and the Function Type <0..255>
command mappings, but the Identification Type 20 (General Commands) is fixed.++ There
are 32 configurable commands.
In this case it will be necessary to define a new format.
For example, FC500:

Description Value
Virtual Input 1 1
Virtual Input 2 2
...
Virtual Input 32 32
Reset 33
Open 34
Close 35
Display Msg 36

Modbus Address Description Value Format


Command 1 Function Type <0 – 255 > F1
Command 1 Information Number < 0 – 255 > F1
Command 1 Operation ON 2 FC500
Command 1 Operation OFF 8 FC500
...
Command 16 Function Type <0 – 255 > F1
Command 16 Information Number < 0 – 255 > F1
Command 16 Operation ON 6 FC500
Command 16 Operation OFF 34 FC500

The “Command Operations ON and OFF” reuse the DNP Binary Outputs 43189, 43190,

103 general settings

Number Value Range


Comms Port COM1 Enum[None,Com1]
Slave Address 0 [0..254]
Synchronization Timeout 30 min [0..1440]min

If Comms Port is set to NONE, the IEC 870-5-103 communication protocol will not be
available.
If the user sets a value other than 0 in the Synchronization Timeout setting, when this time
expires without receiving a synchronization message, the Invalid bit will be set in the time
stamp of a time-tagged message.
It is necessary to configure other port settings: Baud Rate, etc.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 2-27


GE
Grid Solutions

3 Series Protective Relay Platform

Chapter 3: Ethernet interface

Ethernet interface

The Ethernet option for the 3 Series relay provides both a 1300 nm optical interface, and a
10/100 auto-negotiating copper interface. To select which interface is active, a MODBUS
setpoint (see below) must be modified:

MODBUS Hex Description Min Max Step Function Factory


Address Address Code Default
40191 BE EthernetConnectionType 0 1 1 FC230 0

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 3-1


350 REDUNDANCY OPTIONS CHAPTER 3: ETHERNET INTERFACE

350 Redundancy Options


Redundancy options are available for the 350 relay only.
NOTE:

NOTE Industrial real-time Ethernets typically demand much higher availability and uninterrupted
operation than office Ethernet solutions can provide. Even a short loss of connectivity can
result in loss of functionality, as for example in some automation, vehicular, power
generation, and power distribution systems.
To recover from a network failure, different standard redundancy schemes are applied
such as Parallel Redundancy Protocol (PRP), High-availability Seamless Redundancy (HSR)
and others.
The basic concept of both protocols, PRP and HSR, is to send practically identical frames
over different paths and discard one of the copies in reception, at best. If an error occurs or
one of the paths is down, the frame travelling through that path will not reach its
destination, but its copy will.
PRP operates on two independent networks. Each frame is replicated on the sending node
and transmitted over both networks. The receiving node processes the frame arriving first
and discards the subsequent copy. The PRP layer is responsible for this replicate/discard
function and hides the two networks from the upper layers. This scheme works without
explicit reconfiguration and switchover and therefore does not show a period of
unavailability.

Figure 3-1: Example of PRP with two LANs (LAN A and LAN B)

The two LANs, named LAN_A and LAN_B, are identical in protocol at the MAC level, but they
can differ in performance and topology. Transmission delays can also be different. The
LANs have no direct connection among them and they are assumed to be fail-
independent.
In some applications, only availability-critical nodes need a double attachment, while
others do not. In order to meet the specific requirements, PRP defines different kinds of
end nodes.
• The Dual Attached Node (DAN) is connected to both LANs.
• Uncritical nodes can be attached to only one LAN and are therefore called Single
Attached Nodes (SAN). SANs that need to communicate with each other are on the
same LAN.
• The Redundancy Box (RedBox) is used when a single interface node has to be
attached to both networks. Such a node can communicate with all other nodes. Since
a node behind a RedBox appears for other nodes like a DAN, it is called Virtual DANs
(VDAN). The RedBox itself is a DAN and acts as a proxy on behalf of its VDANs. The
RedBox has its own IP address for management purposes

3-2 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 3: ETHERNET INTERFACE 350 REDUNDANCY OPTIONS

Similarly to PRP, HSR is based in the duplication of every frame sent, but in a ring topology.
Each copy of the frame is injected in a different direction of the ring. If any of the links
between nodes is down, all nodes are still reachable. This topology forces every node in the
net to be HSR aware because they have to forward every message until it reaches its
destination. With that purpose, the redundancy information is located at the beginning of
the frame allowing a faster forwarding, see next figure.

Figure 3-2: Example of HSR with HSR Ring

Definitions
• PRP – Parallel Redundancy Protocol - redundancy protocol for high availability in
substation automation networks based on IEC 62439-3 Clause 4 and applicable to
networks based on Ethernet technology (ISO/IEC 8802-3).
• OSI - Open Systems Interconnection - model defined by the International Organization
for Standardization (ISO) for standardizing the functions of a communication system in
terms of abstraction layers. Similar communication functions are grouped into logical
layers. A layer serves the layer above it and is served by the layer below it. There are 7
layers: physical, data link, network, transport, session, presentation, application.
• DANP – Doubly Attached Node running PRP – a node that has two ports which operate
in parallel and are attached to the upper layers of the OSI communications stack
through a Link Redundancy Entity module.
• DANH – Doubly Attached Node with HSR protocol.
• LRE - Link Redundancy Entity – module operating at the link layer of the OSI stack and
responsible for handling duplicates and managing redundancy.
• SAN – Singly Attached Node – regular nodes with non-redundant network adapters
• RedBox – device attaching singly attached nodes (SANs) to a redundant network.
• RCT – Redundancy Check Trailer – PRP trailer added to frames and consisting of the
following fields:
– 16-bit sequence number (SeqNr);
– 4-bit LAN identifier (LanId);
– 12 bit frame size (LSDUsize);
– 16-bit suffix (PRPsuffix).

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 3-3


350 REDUNDANCY OPTIONS CHAPTER 3: ETHERNET INTERFACE

350 Parallel Redundancy Protocol (PRP)


PRP defines a redundancy protocol for high availability in substation automation networks.
It is applicable to networks based on Ethernet technology (ISO/IEC 8802-3).
PRP is designed to provide seamless recovery in case of a single failure in the network, by
using a combination of LAN duplication and frame duplication technique. Identical frames
are sent on two completely independent networks that connect source and destination,
see next figure.

Figure 3-3: Example of PRP Redundant Network

Under normal circumstances both frames will reach their destination and one of them will
be sent up the OSI stack to the destination application, while the second one will be
discarded. If an error occurs in one of the networks and traffic is prevented from flowing on
that path, connectivity will still be provided through the other network to ensure
continuous communication. However, care must be taken when designing the two LANs,
so that no single point of failure (such as a common power supply) is encountered, as such
scenarios can bring down both LANs simultaneously.
PRP uses specialized nodes called doubly attached nodes (DANPs) for handling the
duplicated frames. DANPs devices have an additional module at the link layer level, called
the Link Redundancy Entity (LRE). LRE is responsible for duplicating frames and adding the
specific PRP trailer when sending the frames out on the LAN, as well as making decisions
on received frames as to which one is sent up the OSI stack to the application layer and
which one is discarded. In essence LRE is responsible for making PRP transparent to the
higher layers of the stack. There is a second type of specialized device used in PRP
networks, called RedBox, with the role of connecting Single Attached Nodes (SANs) to a
redundant network.
350relays implement only the DANP functionality. The RedBox functionality is not
implemented.
The original standard IEC 62439-3 (2010) was amended to align PRP with the High-
availability Seamless Redundancy (HSR) protocol. To achieve this, the original PRP was
modified at the cost of losing compatibility with the PRP 2010 version. The revised
standard IEC 62439-3 (2012) is commonly referred to as PRP-1, while the original standard
is PRP-0. 350 relays support only PRP-1.
PRP can be enabled in configuration through a setting available on the network
configuration menu, REDUNDANCY, which already has the capability of enabling Failover
redundancy. When REDUNDANCY is set to PRP, the ports dedicated for PRP will operate in
redundant mode.
The rights associated with configuring PRP follow the security requirements for network
configuration.
PRP management through SNMP MIB is not supported, as the 350 relay doesn’t currently
support SNMP for configuration. Settings and actual values are only available through the
front panel and through EnerVista.

3-4 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 3: ETHERNET INTERFACE 350 REDUNDANCY OPTIONS

The PRP solution to implemented must ensure that performance requirements stated in
IEC 61850-5 Clause 13 are still met. It is specified under Clause 13 (Message performance
requirements) that messages of type 1A must meet the performance class P2/3, which is
3ms (See 3.7.1.1).
Each device in the daisy chain forwards the message until it reaches the destination.

350 High-availability Seamless Redundancy (HSR)


HSR defines a redundancy protocol for high availability in substation automation
networks, based on PRP principles, provides the property of zero recovery time, typically
used in ring topology but applicable to any topology.
In the 350 relay, HSR is implemented in devices with communication option number 5 and
it has two fiber optics. A frame is sent over both ports. A destination should receive, in the
fault-free state, two identical frames within a certain time skew, forward the first frame to
the application and discard the second frame when (and if) it comes. A sequence number
is used to recognize such duplicates.
In contrast to PRP (IEC 62439-3- Clause 4), with which it shares the operating principle, HSR
nodes are arranged into a ring, which allows the network to operate without dedicated
switches, since every node is able to forward frames from port to port. HSR originally
meant "High-availability Seamless Ring", but HSR is not limited to a simple ring topology.
Redundant connections to other HSR rings and to PRP networks are possible.

350 Daisy Chain


A daisy chain is an interconnection of devices where each device is connected in series to
the next.
When an Ethernet daisy-chain redundancy is selected, the 350 relay has two Ethernet
ports and it is working as an unmanaged Ethernet switch. The two Ethernet ports are used
for connecting each device to the ports of its two neighboring devices, see figure.

Figure 3-4: Ethernet daisy-chain redundancy

Each device in the daisy chain forwards the message until it reaches the destination.
Ports A and B use the same MAC (physical device) address and operate by chaining one
device with the next one.
It is important not to create a loop in this topology. Both ends of the chain can be
FASTPATH:

connected to different networks. The device operates only with one IP address through
these two ports.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 3-5


350 REDUNDANCY OPTIONS CHAPTER 3: ETHERNET INTERFACE

If a closed loop configuration is required, it is possible to use two RSTP switches as shown:

Figure 3-5: Ethernet daisy-chain loop with two RSTP switches

In case of a link loss, only port A generates an "Ethernet Link Failure" target message or
NOTE:

event message. Port B does not generate this message. In cases where a 350 device is
NOTE connected between 2 other devices and has a link failure on Port B, it will be necessary to
check the device connected to port B in order to identify the link failure.

350 LLA (Link Loss Alert)


Under Link Loss Alert (LLA) redundancy, port A has the priority. If the Port A LLA detects a
problem with the link, communications is switched to Port B. Port B is, in effect, acting as a
redundant or backup link to the network for Port A.
The operation of ports A and B are as follows:
Ports A and B both use the Port A MAC and IP address settings, while Port B is in standby
mode in that it does not actively communicate on the Ethernet network but does monitors
its Ethernet link.
If the setting LLA PRIORITY is enabled:
• The primary port is port A while secondary (redundant) port is port B.
• The primary port will always be used if available.
• If the link on primary port is lost switch over to secondary port occurs immediately.
• When the link on primary port is detected again, it is monitored for a period of time
(LLA TIMEOUT) to ensure the health of the network. After that period the
communication switch over to primary port automatically.
If the setting LLA PRIORITY is disabled:
• There is no priority, therefore there is no primary port. The communication switch over
from one Port to the other occurs when the link fails.
• In this case the LLA TIMEOUT setting does not act.

3-6 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 3: ETHERNET INTERFACE SNTP

SNTP

SNTP settings
With SNTP, the device can obtain the clock time over an Ethernet network, acting as an
SNTP client to receive time values from an SNTP server.
SNTP Port configures the ports that the device uses, so it’s necessary to configure it in all
cases.
The relay binds to the first unicast message (see below) received from any server, then
continues operating with the SNTP server in unicast mode. Any further responses from
other SNTP servers are ignored. In the unicast mode of operation the chosen time server
can go offline, in which case it takes about one minute for the device to signal an SNTP
FAIL state and switch again to anycast mode in order to try to find another time server.

SNTP modes
Three different modes of SNTP operation are supported. These modes are unicast,
broadcast and anycast.
To use SNTP in unicast mode, the SNTP IP Address must be set to the SNTP server IP
address. Once this address is set and the function setting is “UNICAST”, the device attempts
to obtain time values from the SNTP server. Since many time values are obtained and
averaged, it generally takes 10 seconds until the clock is synchronized with the SNTP
server.
It may take up to 30 seconds for the device to signal an SNTP FAIL state if the server is off-
line. In this case the main CPU generates an alarm similar to that of the IRIG-B case.
To use SNTP in broadcast mode, set the function setting to “BROADCAST”. The device
listens to SNTP messages sent to "all" the broadcast addresses for the subnet.
The device waits up to eighteen minutes (>1024 seconds) to receive an SNTP broadcast
message before signaling an SNTP FAIL state.
To use SNTP in anycast mode, set the function setting to “ANYCAST”. Anycast mode is
designed for use with a set of cooperating servers whose addresses are not known
beforehand by the client. The device sends a request to a multicast group address
assigned by IANA for SNTP protocol purposes. This address is 224.0.1.1 and a group of
SNTP servers listens to it. Upon receiving such a request, each server sends a unicast
response to the SNTP client.
The relay binds to the first unicast message received from any server, then it continues
operating with the SNTP server in unicast mode. Any further responses from other SNTP
servers are ignored. In the unicast mode of operation, the chosen time server can go
offline, in which case it takes about one minute for the device to signal an SNTP FAIL state
and to switch again to the anycast mode to try to find another time server.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 3-7


MODBUS TCP/IP CHAPTER 3: ETHERNET INTERFACE

MODBUS TCP/IP
This section describes the procedure to read and write data in a 3 Series relay using
MODBUS TCP protocol. The MODBUS communication allows the 3 Series relay to be
connected to a supervisor program or any other device with a master MODBUS
communication channel. The 3 Series will always be a slave station.
MODBUS TCP is a variant of the MODBUS protocol, intended for supervision and control of
automation equipment. It covers the use of MODBUS messaging in an 'Intranet' or
'Internet' environment using the TCP/IP protocols.
MODBUS TCP basically embeds a MODBUS frame into a TCP frame in a simple manner. This
is a connection-oriented transaction which means that every query expects a response.
When the relay communicates using MODBUS TCP, it does not require a checksum
calculation of the MODBUS frame as does the MODBUS RTU.
The 3 Series relays support only a subset of the MODBUS protocol functions.

Data and control functions


Supported Modbus function codes: 1H, 2H, 3H, 4H, 5H, 6H, 7H, 8H, 10H, 42H, 43H
For details see MODBUS Functions.
01H Read Coil Status
Just respond, no action required for now.
Outgoing message for this function is the same as input one.
02H Read Input Status
Just respond, no action required for now.
Outgoing message for this function is the same as input one.
03H Read Holding Registers
04H Read Input Registers
05H Force Single Coil
07H Read Exception Status
08H Diagnostics
16 (10 Hex) Preset Multiple Registers
42H Read Settings Group
43H Write Settings Group
Not a standard function
This function is used to write settings in a specific settings group.
Example: (In the example there is a write setting procedure in the Group 1 (00) , setting
address 0x09C1 and 2 bytes of data with value 0x0001.)

Field Name Hex


Slave Address FE
Function 43
Group Activation 00
Starting Address Hi 09
Starting Address Lo C1
No. of Registers Hi 00
No. of Registers Lo 01

3-8 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 3: ETHERNET INTERFACE MODBUS TCP/IP

Field Name Hex


Byte Count 04 02
Data Hi 00
Data Lo 01

Response:

Field Name Hex


Slave Address FE
Function 43
Starting Address Hi 09
Starting Address Lo C1
No. of Registers Hi 00
No. of Registers Lo 01

Exception and error responses


One data frame of an asynchronous transmission to or from a 3 Series relay typically
consists of 1 start bit, 8 data bits, and 1 stop bit. This produces a 10 bit data frame. This is
important for transmission through modems at high bit rates.

Request response sequence


A complete request/response sequence consists of the following bytes (transmitted as
separate data frames):
Master Request Transmission:
SLAVE ADDRESS: 1 byte
FUNCTION CODE: 1 byte
DATA: variable number of bytes depending on FUNCTION CODE
Slave Response Transmission:
SLAVE ADDRESS: 1 byte
FUNCTION CODE: 1 byte
DATA: variable number of bytes depending on FUNCTION CODE
SLAVE ADDRESS: This is the first byte of every transmission. This byte represents the user-
assigned address of the slave device that is to receive the message sent by the master.
Each slave device must be assigned a unique address and only the addressed slave will
respond to a transmission that starts with its address. In a master request transmission the
SLAVE ADDRESS represents the address of the slave to which the request is being sent. In a
slave response transmission the SLAVE ADDRESS represents the address of the slave that is
sending the response.
FUNCTION CODE: This is the second byte of every transmission. Modbus defines function
codes of 1 to 127.
DATA: This will be a variable number of bytes depending on the FUNCTION CODE. This may
be Actual Values, Setpoints, or addresses sent by the master to the slave or by the slave to
the master.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 3-9


DNP ETHERNET PROTOCOL SETTINGS CHAPTER 3: ETHERNET INTERFACE

DNP Ethernet protocol settings

DNP communication
The menu structure for the DNP protocol is shown below.

S1 DNP
DNP GENERAL S1 DNP GENERAL
DNP UNSOL RESPONSE* DNP ADDRESS
DEFAULT VARIATION • •
• • DNP TCP/UDP PORT
DNP CLIENT ADDRESS* CHANNEL 1 PORT
DNP POINTS LIST CHANNEL 2 PORT
TME SYNC IIN PER.
* Ethernet only
DNP MSG FRAG SIZE
DNP TCP CONN. T/O
FAULT REP MAPPING

DNP UNSOL RESPONSE*


FUNCTION POINT 0
• • • •
TIMEOUT POINT 1
MAX RETRIES POINT 2
DEST ADDRESS ...
POINT 63

DEFAULT VARIATION
DNP OBJECT 1 POINT 0 ON
• • • •
DNP OBJECT 2 POINT 0 OFF
DNP OBJECT 20 POINT 1 ON
DNP OBJECT 21 POINT 1 OFF
DNP OBJECT 22 ...
DNP OBJECT 23 POINT 15 ON
DNP OBJECT 30 POINT 15 OFF
DNP OBJECT 32
POINT 0 ENTRY
• •
DNP CLIENT ADDRESS*
POINT 1 ENTRY
CLIENT ADDRESS 1
POINT 2 ENTRY
• •
...
CLIENT ADDRESS 2
POINT 31 ENTRY
CLIENT ADDRESS 3
CLIENT ADDRESS 4
CLIENT ADDRESS 5

S1 DNP POINTS LIST


898769A2.cdr BINARY INPUTS
BINARY OUTPUTS
ANALOG INPUTS

Figure 3-6: DNP communication menu

3-10 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 3: ETHERNET INTERFACE DNP ETHERNET PROTOCOL SETTINGS

The following path is available using the keypad.


PATH: SETPOINTS > S1 RELAY SETUP > COMMUNICATIONS > DNP PROTOCOL > DNP GENERAL
To view the list of DNP Binary Inputs please refer to the Format Codes section - FC134B - of
this Guide.

DNP device profile

DNP 3.0 Device Profile

(Also see the IMPLEMENTATION TABLE in the following section)


Vendor Name: General Electric Multilin
Device Name: 3 Series relay
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Device Function:
□ Master
⊠ Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
Supported (the complete list is described in the attached table):

Binary Inputs (Object 1)


Binary Input Changes (Object 2)

Binary Outputs (Object 10)


Control Relay Output Block (Object 12)

Binary Counters (Object 20)


Frozen Counters (Object 21)
Counter Change Event (Object 22)
Frozen Counter Event (Object 23)

Analog Inputs (Object 30)


Analog Input Changes (Object 32)
Analog Deadbands (Object 34)

Time and Date (Object 50)

Internal Indications (Object 80)


Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):
Transmitted: 292 Transmitted: configurable up to 2048
Received: 292 Received: 2048
Maximum Data Link Re-tries: Maximum Application Layer Re-tries:
⊠None ⊠ None
□Fixed at 3 □ Configurable
□Configurable
Requires Data Link Layer Confirmation:
⊠ Never

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 3-11


DNP ETHERNET PROTOCOL SETTINGS CHAPTER 3: ETHERNET INTERFACE

DNP 3.0 Device Profile


□ Always
□ Sometimes
□ Configurable
Requires Application Layer Confirmation:
□ Never
□ Always
⊠ When reporting Event Data
⊠ When sending multi-fragment responses
□ Sometimes
□ Configurable
Timeouts while waiting for:
Data Link Confirm: ⊠ None □ Fixed □ Variable □ Configurable
Complete Appl. Fragment: ⊠ None □ Fixed □ Variable □ Configurable
Application Confirm: □ None ⊠ Fixed at 10 s □ Variable □ Configurable
Complete Appl. Response: ⊠ None □ Fixed at ___ □ Variable □ Configurable
Others:
Transmission Delay: No intentional delay
Need Time Interval: Configurable (default = 24 hrs.)
Select/Operate Arm Timeout: 10 s
Binary input change scanning period: 8 times per power system cycle
Analog input change scanning period: 500 ms
Counter change scanning period: 500 ms
Frozen counter event scanning period: 500 ms
Sends/Executes Control Operations:
WRITE Binary Outputs ⊠ Never □ Always □ Sometimes □Configurable
SELECT/OPERATE □ Never ⊠ Always □ Sometimes □ Configurable
DIRECT OPERATE □ Never ⊠Always □ Sometimes □ Configurable
DIRECT OPERATE – NO ACK □ Never ⊠ Always □ Sometimes □ Configurable
Count > 1 ⊠ Never □ Always □ Sometimes □ Configurable
Pulse On □ Never □ Always ⊠ Sometimes □ Configurable
Pulse Off □ Never □ Always ⊠ Sometimes □ Configurable
Latch On □ Never □ Always ⊠ Sometimes □ Configurable
Latch Off □ Never □ Always ⊠ Sometimes □ Configurable
Queue ⊠ Never □ Always □ Sometimes □ Configurable
Clear Queue ⊠ Never □ Always □ Sometimes □ Configurable
Explanation of ‘Sometimes’: Object 12 points are mapped to Virtual Inputs and Commands (Force
Coils). Both “Pulse On” and “Latch On” operations perform the same function in the 3 Series relay ;
that is, the appropriate Virtual Input or Coil is put into the “On” state. The On/Off times and Count
value are ignored. “Pulse Off” and “Latch Off” operations put the appropriate Virtual Input or Coil into
the “Off” state. “Trip” and “Close” operations both put the appropriate Virtual Input or coil into the
“On” state if a paired mapping is set, otherwise “Trip” will put into “Off” and “Close” will put into “On”.
Reports Binary Input Change Events when no Reports time-tagged Binary Input Change
specific variation requested: Events when no specific variation
requested:
□ Never □ Never
⊠ Only time-tagged ⊠ Binary Input Change With Time
□ Only non-time-tagged □ Binary Input Change With Relative Time
□ Configurable □ Configurable (attach explanation)
Sends Unsolicited Responses: Sends Static Data in Unsolicited Responses:

3-12 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 3: ETHERNET INTERFACE DNP ETHERNET PROTOCOL SETTINGS

DNP 3.0 Device Profile


□ Never ⊠ Never
□ Configurable □ When Device Restarts
□ Only certain objects □ When Status Flags Change
⊠ Sometimes No other options are permitted.
⊠ ENABLE/DISABLE unsolicited Function codes
supported
Explanation of ‘Sometimes’: It will be disabled for
RS-485 applications, since there is no collision
avoidance mechanism. For Ethernet communication
it will be available and it can be disabled or enabled
with the proper function code.
Default Counter Object/Variation: Counters Roll Over at:
□ No Counters Reported □ No Counters Reported
□ Configurable (attach explanation) □ Configurable (attach explanation)
⊠ Default Object: 20 ⊠ 16 Bits
Default Variation: 1
⊠ Point-by-point list attached □ Other Value: _____
⊠ Point-by-point list attached
Sends Multi-Fragment Responses:
⊠ Yes
□ No

DNP port allocation

Channel 1 Port Channel 2 Port DNP Availability


None None DNP not available over Ethernet port
None NETWORK-TCP One Master over TCP
None NETWORK-UDP "Various" Masters over UDP

NETWORK-TCP None One Master over TCP


NETWORK-TCP NETWORK-TCP Two Masters over TCP
NETWORK-TCP NETWORK-UDP One Master over TCP and "various" Masters over UDP

NETWORK-UDP None "Various" Masters over UDP


NETWORK-UDP NETWORK-TCP "Various" Masters over UDP and one Master over TCP
NETWORK-UDP NETWORK-UDP "Various" Masters over UDP

The DNP Eth Channel 1 Port and DNP Eth Channel 2 Port settings select the
communications port assigned to the DNP protocol for each Ethernet channel. When this
setting is set to "Network-TCP" the DNP protocol can be used over TCP/IP channels 1 or 2.
When this value is set to "Network-UDP" the DNP protocol can be used over UDP/IP on one
channel only.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 3-13


DNP ETHERNET PROTOCOL SETTINGS CHAPTER 3: ETHERNET INTERFACE

DNP implementation

OBJECT REQUEST RESPONSE


OBJECT VARIATION DESCRIPTION FUNCTION QUALIFIER CODES FUNCTION QUALIFIER CODES
NO. NO. CODES (DEC) (HEX) CODES (DEC) (HEX)
1 0 Binary Input (Variation 0 is 1 (read) 22 00, 01 (start-stop) --- ---
used to request default (assign class) 06 (no range, or all)
variation) 07, 08 (limited
quantity) 17, 28
(index)
1 Binary Input 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
2 Binary Input with Status 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
2 0 Binary Input Change 1 (read) 06 (no range, or all) --- ---
(Variation 0 is used to 07, 08 (limited
request default variation) quantity)
1 Binary Input Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
without Time 07, 08 (limited 130 (unsol.
quantity) resp.)
2 Binary Input Change with 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Time 07, 08 (limited 130 (unsol.
quantity) resp.)
3 Binary Input Change with 1 (read) 06 (no range, or all) --- ---
Relative Time 07, 08 (limited
quantity)
10 0 Binary Output Status 1 (read) 00, 01(start-stop) 06 --- ---
(Variation 0 is used to (no range, or all) 07,
request default variation) 08 (limited quantity)
17, 28 (index)
2 Binary Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
12 1 Control Relay Output Block 3 (select)4 00, 01 (start-stop) 129 (response) echo of request
(operate) 5 (direct 07, 08 (limited
op) 6 (dir. op, quantity) 17, 28
noack) (index)
20 0 Binary Counter (Variation 0 1 (read) 7 (freeze) 00, 01 (start-stop) --- ---
is used to request default 8 (freeze noack) 9 06 (no range, or all)
variation) (freeze clear) 10 07, 08 (limited
(frz. cl. noack) 22 quantity) 17, 28
(assign class) (index)
1 32-Bit Binary Counter 1 (read)7 (freeze) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
8 (freeze noack) 9 06 (no range, or all) 17, 28 (index) (see
(freeze clear) 10 07, 08 (limited Note 2)
(frz. cl. noack) 22 quantity) 17, 28
(assign class) (index)
2 16-Bit Binary Counter 1 (read) 7 (freeze) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
8 (freeze noack) 9 06 (no range, or all) 17, 28 (index) (see
(freeze clear) 10 07, 08 (limited Note 2)
(frz. cl. noack) 22 quantity) 17, 28
(assign class) (index)
5 32-Bit Binary Counter 1 (read) 7 (freeze) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
without Flag 8 (freeze noack) 9 06 (no range, or all) 17, 28 (index) (see
(freeze clear) 10 07, 08 (limited Note 2)
(frz. cl. noack) 22 quantity) 17, 28
(assign class) (index)

3-14 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 3: ETHERNET INTERFACE DNP ETHERNET PROTOCOL SETTINGS

OBJECT REQUEST RESPONSE


OBJECT VARIATION DESCRIPTION FUNCTION QUALIFIER CODES FUNCTION QUALIFIER CODES
NO. NO. CODES (DEC) (HEX) CODES (DEC) (HEX)
6 16-Bit Binary Counter 1 (read) 7 (freeze) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
without Flag 8 (freeze noack) 9 06 (no range, or all) 17, 28 (index) (see
(freeze clear) 10 07, 08 (limited Note 2)
(frz. cl. noack) 22 quantity) 17, 28
(assign class) (index)
21 0 Frozen Counter(Variation 0 1 (read) 22 00, 01 (start-stop) --- ---
is used to request (assign class) 06 (no range, or all)
defaultvariation) 07, 08 (limited
quantity) 17, 28
(index)
1 32-Bit Frozen Counter 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
2 16-Bit Frozen Counter 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
9 32-Bit Frozen Counter 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
without Flag (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
10 16-Bit Frozen Counter 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
without Flag (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
22 0 Counter Change Event 1 (read) 06 (no range, or all) --- ---
(Variation 0 is used to 07, 08 (limited
request default variation) quantity)
1 32-Bit Counter Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event 07, 08 (limited 130 (unsol.
quantity) resp.)
2 16-Bit Counter Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event 07, 08 (limited 130 (unsol.
quantity) resp.)
5 32-Bit Counter Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event with Time 07, 08 (limited 130 (unsol.
quantity) resp.)
6 16-Bit Counter Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event with Time 07, 08 (limited 130 (unsol.
quantity) resp.)
23 0 Frozen Counter Event 1 (read) 06 (no range, or all) --- ---
(Variation 0 is used to 07, 08 (limited
request default variation) quantity)
1 32-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited 130 (unsol.
quantity) resp.)
2 16-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited 130 (unsol.
quantity) resp.)
5 32-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited 130 (unsol.
quantity) resp.)
6 16-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited 130 (unsol.
quantity) resp.)

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 3-15


DNP ETHERNET PROTOCOL SETTINGS CHAPTER 3: ETHERNET INTERFACE

OBJECT REQUEST RESPONSE


OBJECT VARIATION DESCRIPTION FUNCTION QUALIFIER CODES FUNCTION QUALIFIER CODES
NO. NO. CODES (DEC) (HEX) CODES (DEC) (HEX)
30 0 Analog Input (Variation 0 is 1 (read) 22 00, 01 (start-stop) --- ---
used to request default (assign class) 06 (no range, or all)
variation) 07, 08 (limited
quantity) 17, 28
(index)
1 32-Bit Analog Input 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
2 16-Bit Analog Input 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
3 32-Bit Analog Input without 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Flag (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
4 16-Bit Analog Input without 1 (read) 22 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Flag (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
32 0 Analog Change Event 1 (read) 06 (no range, or all) --- ---
(Variation 0 is used to 07, 08 (limited
request default variation) quantity)
1 32-Bit Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
without Time 07, 08 (limited 130 (unsol.
quantity) resp.)
2 16-Bit Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
without Time 07, 08 (limited 130 (unsol.
quantity) resp.)
3 32-Bit Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited 130 (unsol.
quantity) resp.)
4 16-Bit Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited 130 (unsol.
quantity) resp.)
34 0 Analog Input Reporting 1 (read) 00, 01 (start-stop) --- ---
Deadband (Variation 0 is 06 (no range, or all)
used to request 07, 08 (limited
defaultvariation) quantity) 17, 28
(index)
1 16-bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Reporting Deadband 06 (no range, or all) 17, 28 (index) (see
(default - see Note 1) 07, 08 (limited Note 2)
quantity) 17, 28
(index)
2 (write) 00, 01 (start-stop) --- ---
07, 08 (limited
quantity) 17, 28
(index)
2 32-bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Reporting Deadband 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited Note 2)
quantity) 17, 28
(index)
2 (write) 00, 01 (start-stop) --- ---
07, 08 (limited
quantity) 17, 28
(index)

3-16 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 3: ETHERNET INTERFACE DNP ETHERNET PROTOCOL SETTINGS

OBJECT REQUEST RESPONSE


OBJECT VARIATION DESCRIPTION FUNCTION QUALIFIER CODES FUNCTION QUALIFIER CODES
NO. NO. CODES (DEC) (HEX) CODES (DEC) (HEX)
50 1 Time and Date (default - 1 (read)2 (write) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
see Note 1) 06 (no range, or all) 17, 28 (index) (see
07 (limited qty=1) 08 Note 2)
(limited quantity) 17,
28 (index)
60 0 Class 0, 1, 2, and 3 Data 1 (read) 20 06 (no range, or all) --- ---
(enable unsol) 21
(disable unsol) 22
(assign class)
1 Class 0 Data 1 (read) 22 06 (no range, or all) --- ---
(assign class)
2 Class 1 Data 1 (read) 20 06 (no range, or all) --- ---
(enable unsol) 07, 08 (limited
quantity)
3 Class 2 Data 21 (disable unsol) --- ---
4 Class 3 Data 22 (assign class) --- ---
80 1 Internal Indications 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(index =7)
2 (write) (see 00 (start-stop) (index --- ---
Note 3) =7)
No Object (function code 13 (cold restart) --- --- ---
only) see Note 3
No Object (function code 14 (warm restart) --- --- ---
only)
No Object (function code 23 (delay meas.) --- --- ---
only)

1. A default variation refers to the variation response when variation 0 is requested and/
NOTE:

or in class 0, 1, 2, or 3 scans. The default variations for object types 1, 2, 20, 21, 22, 23,
NOTE 30, and 32 are selected via relay settings. This optimizes the class 0 poll data size.
2. For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a
request is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests
sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for
change event objects, qualifiers 17 or 28 are always responded.)
Cold restarts are implemented the same as warm restarts – the 3 Series relay is not
restarted, but the DNP process is restarted.

DNP Ethernet EnerVista Setup


Table 3-1: DNP protocol
SETTINGS PARAMETER RANGE FORMAT
DNP Channel 1 Port NONE NONE ; NETWORK-TCP ; F87
NETWORK –UDP
DNP Channel 2 Port NONE NONE ; NETWORK-TCP ; F87
NETWORK –UDP
DNP Address 0 0 to 65519 F1
DNP Client Address 1 0. 0. 0. 0 F150
DNP Client Address 2 0. 0. 0. 0 F150
DNP Client Address 3 0. 0. 0. 0 F150
DNP Client Address 4 0. 0. 0. 0 F150
DNP Client Address 5 0. 0. 0. 0 F150

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 3-17


DNP ETHERNET PROTOCOL SETTINGS CHAPTER 3: ETHERNET INTERFACE

SETTINGS PARAMETER RANGE FORMAT


DNP TCP/UDP Port Number 20000 0 to 65535 F1
DNP Unsol Resp Function Disabled Disabled ; Enabled F126
DNP Unsol Resp Timeout 5s 0 to 60 s F1
DNP Unsol Resp Max Retries 10 1 to 255 F1
DNP Unsol Resp Dest Addr 1 0 to 65519 F1
DNP Time Sync IIN Period 1440 min 1 to 10080 min F1
DNP Message Fragment Size 240 30 to 2048 F1

DNP Object 1 Default Variation 2 1;2 F1


DNP Object 2 Default Variation 2 1;2 F1
DNP Object 20 Default Variation 1 1;2,5;6 F78
DNP Object 21 Default Variation 1 1 ; 2 ; 9 ; 10 F79
DNP Object 22 Default Variation 1 1;2,5;6 F80
DNP Object 23 Default Variation 1 1;2,5;6 F81
DNP Object 30 Default Variation 1 1 ; 2 ;3 ; 4 F82
DNP Object 32 Default Variation 1 1 ; 2 ;3 ; 4 F83
DNP TCP Connection Timeout 120 s 10 to 300 s F1
Fault Report Mapping in DNP/104 Disabled Disabled, Enabled F126

The setting DNP Unsolicited Response Timeout affects DNP TCP clients only; not serial
NOTE:

and UDP clients. Possible values that can be selected for this setting lie between 0 and 60
NOTE seconds.
In addition to this selected timeout, up to an additional 10 seconds is required to send
the response packet.

Table 3-2: DNP point list


SETTINGS PARAMETER RANGE FORMAT
Binary Input Point 0 Entry Select entry Operands FC134B
from a list

Binary Input Point 63 Entry Select entry Operands FC134B


from a list

Analog Input Point 0 Entry Select entry Analog parameters F88


from a list
Analog Input Point 0 Scale Factor 1 0.001 ; 0.01 ; 0.1 ; 1 ; 10 ; 100 ; F85
1000 ; 10000 ; 100000
Analog Input Point 0 Deadband 30000 0 to 100000000 F9

Analog Input Point 31 Entry Select entry Analog parameters F88


from a list
Analog Input Point 31 Scale Factor 1 0.001 ; 0.01 ; 0.1 ; 1 ; 10 ; 100 ; F85
1000 ; 10000 ; 100000
Analog Input Point 31 Deadband 30000 0 to 100000000 F9

Binary Output Point 0 ON Select entry Virtual Input 1 to 32 and Force F86
from a list Coils
Binary Output Point 0 OFF Select entry Virtual Input 1 to 32 and Force F86
from a list Coils

3-18 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 3: ETHERNET INTERFACE DNP ETHERNET PROTOCOL SETTINGS

SETTINGS PARAMETER RANGE FORMAT

Binary Output Point 15 ON Select entry Virtual Input 1 to 32 and Force F86
from a list Coils
Binary Output Point 15 OFF Select entry Virtual Input 1 to 32 and Force F86
from a list Coils

• The DNP Time Sync IIN Period setting determines how often the Need Time Internal
Indication (IIN) bit is set by the 3 Series relay. Changing this time allows the 3 Series
relay to indicate that a time synchroniztion command is necessary more or less often
• Various settings have been included to configure Default Variation for the Binary
Inputs, Counters and Analog Inputs Objects. The default variation refers to the
variation response when variation 0 is requested, and/or in class 0, 1, 2, or 3 scans
• Up to 64 Binary Inputs and 32 Analog Input entries can be mapped to an item from a
list of 3 Series relay status events and metered values. Status events correspond to
format FC134B.
• Each Analog Input point Deadband and Scale Factor can be set individually instead of
setting a general deadband or scale for different metering groups. This will avoid scale
and deadband conflicts for different meterings of the same nature.
• Up to 16 Binary/Control Outputs can be configured by selecting a Virtual Input or
Command from a list of 32 Virtual Inputs and Commands (Force Coils). Some legacy
DNP implementations use a mapping of one DNP Binary Output to two physical or
virtual control points. In Order to configure Paired Control Points the source for states
ON and OFF should be set to different Virtual Inputs or Commands.
• The DNP Technical Committee recommends using contiguous point numbers, starting
at 0, for each data type, because some DNP3 Master implementations allocate
contiguous memory from point 0 to the last number for each data type.
Binary Inputs are inputs to the Master. Binary Outputs are outputs from the Master.
NOTE:

NOTE

DNP general
Default variations for Object 1, 2 , 20 , 21 , 22 , 23 , 30 and Object 32 will be set by settings
and returned for the object in a response when no specific variation is specified in a Master
request.
Any change in the state of any binary point causes the generation of an event, and
consequently, if configured, an unsolicited response. Alternatively it is returned when the
Master asks for it. The same behavior will be seen when an analog value changes by more
than its configured deadband limit. There can be up to 3 masters in total, but only one
Serial Master.
The following Default Classes will be fixed for the different blocks of data:
Binary Input Points Default Class = 1
Analog Input Point Default Class = 2
Counters Default Class = 3
Each Data Point Class can be changed by protocol function code 22 in volatile mode. If a
restart is performed, the new values will be lost.
DNP Object 34 points can be used to change deadband values from the default for each
individual DNP Analog Input point. These new deadbands will be maintained such that in
the case of a relay restart, the values are not lost.
For the 350 and 339 relays, one Binary Counter has been hardcoded such that no option
can be modified by setting:
• Total_Number_of_Trips

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 3-19


DNP ETHERNET PROTOCOL SETTINGS CHAPTER 3: ETHERNET INTERFACE

Requests for Object 20 (Binary Counters), Object 21 (Frozen Counters), and Object 22
(Counter Change Events) must be accepted.
Function codes “Immediate Freeze”, “Freeze and Clear” etc. are accepted as well.
The FAULT REPORT MAPPING IN DNP/104 setpoint may be set to a value of "Disabled" or
"Enabled". When "Disabled", only the configurable Analog Input points are available
beginning at point index 0.When "Enabled", the Fault Report Values are assigned from
point 0 to 32 in the 339 and 350 relays, and from 0 to 38 in the 345 relay, with the
configurable Analog Inputs following the point numbers.
To support existing SCADA hardware not capable of 32-bit data reads, the upper and lower
16-bit portions of the fault report time and date values have been assigned to separate
points. To read a date or time, it is necessary to read both the upper and lower 16-bit
portions, concatenate these two values to form a 32-bit value and interpret the result in
the format associated with the point.

Fault Report Mapping 350 and 339 Fault Report Mapping 345
Disabled Enabled Disabled Enabled
- 0 Fault Report Date Upper 16 - 0 Fault Report Date Upper 16
- 1 Fault Report Date Lower 16 - 1 Fault Report Date Lower 16
- 2 Fault Report Time Upper 16 - 2 Fault Report Time Upper 16
- 3 Fault Report Time Lower 16 - 3 Fault Report Time Lower 16
- 4 Fault Report Fault Type - 4 Fault Report Fault Type
- 5 Fault Report Ia - 5 Fault Report Ia
- 6 Fault Report Ia Angle - 6 Fault Report Ia Angle
- 7 Fault Report Ib - 7 Fault Report Ib
- 8 Fault Report Ib Angle - 8 Fault Report Ib Angle
- 9 Fault Report Ic - 9 Fault Report Ic
- 10 Fault Report Ic Angle - 10 Fault Report Ic Angle
- 11 Fault Report Ig - 11 Fault Report Ig
- 12 Fault Report Ig Angle - 12 Fault Report Ig Angle
- 13 Fault Report In - 13 Fault Report In
- 14 Fault Report In Angle - 14 Fault Report In Angle
- 15 Fault Report Va - 15 Fault Report System Frequency
- 16 Fault Report Va Angle - 16 Fault Report Ia 2
- 17 Fault Report Vb - 17 Fault Report Ia 2 Angle
- 18 Fault Report Vb Angle - 18 Fault Report Ib 2
- 19 Fault Report Vc - 19 Fault Report Ib 2 Angle
- 20 Fault Report Vc Angle - 20 Fault Report Ic 2
- 21 Fault Report Vab - 21 Fault Report Ic 2 Angle
- 22 Fault Report Vab Angle - 22 Fault Report Ig 2
- 23 Fault Report Vbc - 23 Fault Report Ig 2 Angle
- 24 Fault Report Vbc Angle - 24 Fault Report In 2
- 25 Fault Report Vca - 25 Fault Report In 2 Angle
- 26 Fault Report Vca Angle - 26 Fault Report Idiff 1 PhA
- 27 Fault Report Vn - 27 Fault Report Idiff 1 PhA Angle
- 28 Fault Report Vn Angle - 28 Fault Report I Restraint PhA
- 29 Fault Report Vaux - 29 Fault Report I Restraint PhA Angle
- 30 Fault Report Vaux Angle - 30 Fault Report Idiff 1 PhB
- 31 Fault Report System Frequency - 31 Fault Report Idiff 1 PhB Angle
- 32 Fault Report Phases - 32 Fault Report I Restraint Ph B

3-20 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 3: ETHERNET INTERFACE DNP ETHERNET PROTOCOL SETTINGS

Fault Report Mapping 350 and 339 Fault Report Mapping 345
Disabled Enabled Disabled Enabled
0 33 Analog Input Point 0 Entry - 33 Fault Report I Restraint PhB Angle
1 34 Analog Input Point 1 Entry - 34 Fault Report Idiff 1 PhC
… … … - 35 Fault Report Idiff 1 PhC Angle
… … … - 36 Fault Report I Restraint PhC
31 64 Analog Input Point 31 Entry - 37 Fault Report I Restraint PhC Angle
- 38 Fault Report Phases
0 39 Analog Input Point 0 Entry
1 40 Analog Input Point 1 Entry
… … …
… … …
31 70 Analog Input Point 31 Entry

Some fault report data has been scaled to fit into a 16-bit value as follows:

Fault Report Data Scale


Fault Report Ia, Ib, Ic, Ia2, Ib2, Ic2 Format_F10 * 100 / CT Primary
Fault Report Ig, Ig2 Format_F10 * 100 / Gnd CT Primary
Fault Report In , In2 Format_F10 * 100 / CT Primary
Fault Report Va, Vb, Vc, Vab, Vbc, Vca, Vn Format_F9 * 10000 /( BusVTRatio * BusVTSecondary)
Fault Report Vaux Format_F9 * 10000 /( AuxVTRatio * AuxVTSecondary)
Fault Report System Frequency Format_F3
Fault Report Phases Format_F37

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 3-21


IEC60870-5-104 PROTOCOL CHAPTER 3: ETHERNET INTERFACE

IEC60870-5-104 protocol

S1 60870-5-104
GENERAL S1 104 GENERAL
CLIENT ADDRESS FUNCTION
POINT LIST • •
TCP PORT
SLAVE ADDRESS
CYCLIC DATA PERIOD
TCP CONN. TIMEOUT 104 BINARY INPUTS
OBJ INFO ADDR BIN POINT 0
OBJ INFO ADDR ALOG • •
OBJ INFO ADDR CNTR POINT 1
OBJ INFO ADDR CMD ...
FAULT REP MAPPING POINT 63

S1 104 CLIENT ADDRESS 104 ANALOG INPUTS


CLIENT ADDRESS 1 POINT 0 ENTRY
• • • •
CLIENT ADDRESS 2 POINT 0 SCALE FCTR
... POINT 0 DEADBAND
.
CLIENT ADDRESS 5 ... .
.
POINT 31 ENTRY
.
POINT 31 SCALE FCTR
S1 104 POINT LIST POINT 31 DEADBAND
BINARY INPUTS
ANALOG INPUTS
BINARY OUTPUTS 104 BINARY OUTPUTS
POINT 0 ON
• •
POINT 0 OFF
898794A2.cdr ... .
.
POINT 15 ON
.
POINT 15 OFF
.

Figure 3-7: IEC 60870-5-104 protocol menu

IEC 60870-5-104 interoperability


This document is adapted from the IEC 60870-5-104 standard. For this section the boxes
indicate the following: ⊠ – used in the standard direction; □– not used.
IEC 60870-5-104 Interoperability Document
1. System or device:
□ System definition.
□ Controlling station definition (master).
⊠ Controlled station definition (slave).
2. Application layer:
2.1. Transmission mode for application data:
Mode 1 (least significant octet first), as defined in Clause 4.10 of IEC 60870-5-4, is
used exclusively in this companion standard.
2.2. Common address of ADSU:

3-22 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 3: ETHERNET INTERFACE IEC60870-5-104 PROTOCOL

⊠ Two octets.
2.3. Information object address:
⊠ Three octets.
⊠ Structured
⊠ Unstructured
2.4. Cause of transmission:
⊠ Two octets (with originator address). Originator address is set to zero if not used.
2.5. Maximum length of APDU.
253 in both directions (the maximum length is a fixed system parameter).
2.6. Selection of standard ASDUs.
For the following lists, the boxes indicate the following: ⊠ – used in standard
direction; □ – not used.
Process information in monitor direction:
Table 3-3: Process information in monitor direction
Number / description Mnemonic
⊠ <1> := Single-point information M_SP_NA_1
□ <3> := Double-point information M_DP_NA_1
□ <5> := Step position information M_ST_NA_1
□ <7> := Bitstring of 32 bits M_BO_NA_1
□ <9> := Measured value, normalized value M_ME_NA_1
⊠ <11> := Measured value, scaled value M_ME_NB_1
□ <13> := Measured value, short floating point value M_ME_NC_1
⊠ <15> := Integrated totals M_IT_NA_1
□ <20> := Packed single-point information with status change detection M_SP_NA_1
□ <21> := Measured value, normalized value without quantity descriptor M_ME_ND_1
⊠ <30> := Single-point information with time tag CP56Time2a M_SP_TB_1
□ <31> := Double-point information with time tag CP56Time2a M_DP_TB_1
□ <32> := Step position information with time tag CP56Time2a M_ST_TB_1
□ <33> := Bitstring of 32 bits with time tag CP56Time2a M_BO_TB_1
□ <34> := Measured value, normalized value with time tag CP56Time2a M_ME_TD_1
⊠ <35> := Measured value, scaled value with time tag CP56Time2a M_ME_TE_1
□ <36> := Measured value, short floating point value with time tag CP56Time2a M_ME_TF_1
⊠ <37> := Integrated totals with time tag CP56Time2a M_IT_TB_1
□ <38> := Event of protection equipment with time tag CP56Time2a M_EP_TD_1
□ <39> := Packed start events of protection equipment with time tag M_EP_TE_1
CP56Time2a
□ <40> := Packed output circuit information of protection equipment with time M_EP_TF_1
tag CP56Time2a

Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>,
and <19> or of the set <30> to <40> are used.
Table 3-4: Process information in control direction
Number / description Mnemonic
⊠ <45> := Single command C_SC_NA_1
⊠ <46> := Double command C_DC_NA_1
□ <47> := Regulating step command C_RC_NA_1
□ <48> := Set point command, normalized value C_SE_NA_1
□ <49> := Set point command, scaled value C_SE_NB_1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 3-23


IEC60870-5-104 PROTOCOL CHAPTER 3: ETHERNET INTERFACE

Number / description Mnemonic


□ <50> := Set point command, short floating point value C_SE_NC_1
□ <51> := Bitstring of 32 bits C_BO_NA_1
⊠ <58> := Single command with time tag CP56Time2a C_SC_TA_1
⊠ <59> := Double command with time tag CP56Time2a C_DC_TA_1
□ <60> := Regulating step command with time tag CP56Time2a C_RC_TA_1
□ <61> := Set point command, normalized value with time tag CP56Time2a C_SE_TA_1
□ <62> := Set point command, scaled value with time tag CP56Time2a C_SE_TB_1
□ <63> := Set point command, short floating point value with time tag C_SE_TC_1
CP56Time2a
□ <64> := Bitstring of 32 bits with time tag CP56Time2a C_BO_TA_1

Either the ASDUs of the set <45> to <51> or of the set <58> to <64> are used.
Table 3-5: System information in monitor direction
Number / description Mnemonic
⊠ <70> := End of initialization M_EI_NA_1

Table 3-6: System information in control direction


Number / description Mnemonic
⊠ <100> := Interrogation command C_IC_NA_1
⊠ <101> := Counter interrogation command C_CI_NA_1
⊠ <102> := Read command C_RD_NA_1
⊠ <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1
⊠ <105> := Reset process command C_RP_NA_1
⊠ <107> := Test command with time tag CP56Time2a C_TS_TA_1

Table 3-7: Parameter in control direction


Number / description Mnemonic
□ <110> := Parameter of measured value, normalized value PE_ME_NA_1
⊠ <111> := Parameter of measured value, scaled value PE_ME_NB_1
□ <112> := Parameter of measured value, short floating point value PE_ME_NC_1
□ <113> := Parameter activation PE_AC_NA_1

Table 3-8: File transfer


Number / description Mnemonic
□ <120> := File ready F_FR_NA_1
□ <121> := Section ready F_SR_NA_1
□ <122> := Call directory, select file, call file, call section F_SC_NA_1
□ <123> := Last section, last segment F_LS_NA_1
□ <124> := Ack file, ack section F_AF_NA_1
□ <125> := Segment F_SG_NA_1
□ <126> := Directory (blank or X, available only in monitor [standard] direction) F_DR_TA_1
□ <127> := Query log - Request archive file F_SC_NB_1

Type identifier and cause of transmission assignments (station-specific parameters)


are shown in the following tables. In these tables, shaded boxes (░) are not
required, black boxes (█) are not permitted in the companion standard, empty cells
indicate the functions or ASDU are not used, and a cross (╳) indicates availability
only in the standard direction.

3-24 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 3: ETHERNET INTERFACE IEC60870-5-104 PROTOCOL

Table 3-9: Cause of transmission numbers


Number Cause of transmission
1 Periodic, cyclic
2 Background scan
3 Spontaneous
4 Initialized
5 Request or requested
6 Activation
7 Activation confirmation
8 Deactivation
9 Deactivation confirmation
10 Activation termination
11 Return information caused by local command
12 File transfer
13 Interrogated by group <number>
20 to 36 Requested by group <n> counter request
37 to 41 Unknown type identification
44 Unknown cause of transmission
45 Unknown command address of ADSU
46 Unknown information object address
47 Unknown information object address

Table 3-10: Cause of transmission assignments


Type identification Cause of transmission
No. Mnemonic 1 2 3 4 5 6 7 8 9 10 11 12 13 20 37 44 45 46 47
to to
36 41
<1> M_SP_NA_1 ░ ░ ╳ ░ ░ ░ ░ ░ ░ ╳ ░ ░ ░ ░ ░
<2> M_SP_TA_1 ░ ░ █ ░ █ ░ ░ ░ ░ ░ █ █ ░ ░ ░ ░ ░ ░ ░
<3> M_DP_NA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<4> M_DP_TA_1 ░ ░ █ ░ █ ░ ░ ░ ░ ░ █ █ ░ ░ ░ ░ ░ ░ ░
<5> M_ST_NA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<6> M_ST_TA_1 ░ ░ █ ░ █ ░ ░ ░ ░ ░ █ █ ░ ░ ░ ░ ░ ░ ░
<7> M_BO_NA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<8> M_BO_TA_1 ░ ░ █ ░ █ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<9> M_ME_NA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<10> M_ME_TA_1 ░ ░ █ ░ █ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<11> M_ME_NB_1 ╳ ░ ╳ ░ ░ ░ ░ ░ ░ ░ ░ ╳ ░ ░ ░ ░ ░
<12> M_ME_TB_1 ░ ░ █ ░ █ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<13> M_ME_NC_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<14> M_ME_TC_1 ░ ░ █ ░ █ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<15> M_IT_NA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ╳ ░ ░ ░ ░
<16> M_IT_TA_1 ░ ░ █ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ █ ░ ░ ░ ░
<17> M_EP_TA_1 ░ ░ █ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<18> M_EP_TB_1 ░ ░ █ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<19> M_EP_TC_1 ░ ░ █ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<20> M_PS_NA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<21> M_ME_ND_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<30> M_SP_TB_1 ░ ░ ╳ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 3-25


IEC60870-5-104 PROTOCOL CHAPTER 3: ETHERNET INTERFACE

Type identification Cause of transmission


No. Mnemonic 1 2 3 4 5 6 7 8 9 10 11 12 13 20 37 44 45 46 47
to to
36 41
<31> M_DP_TB_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<32> M_ST_TB_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<33> M_BO_TB_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<34> M_ME_TD_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<35> M_ME_TE_1 ░ ░ ? ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<36> M_ME_TF_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<37> M_IT_TB_1 ░ ░ ╳ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ╳ ░ ░ ░ ░
<38> M_EP_TD_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<39> M_EP_TE_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<40> M_EP_TF_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<45> C_SC_NA_1 ░ ░ ░ ░ ░ ╳ ╳ ╳ ╳ ╳ ░ ░ ░ ░ ░
<46> C_DC_NA_1 ░ ░ ░ ░ ░ ╳ ╳ ╳ ╳ ╳ ░ ░ ░ ░ ░
<47> C_RC_NA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<48> C_SE_NA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<49> C_SE_NB_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<50> C_SE_NC_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<51> C_BO_NA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<58> C_SC_TA_1 ░ ░ ░ ░ ░ ╳ ╳ ╳ ╳ ╳ ░ ░ ░ ░ ░
<59> C_DC_TA_1 ░ ░ ░ ░ ░ ╳ ╳ ╳ ╳ ╳ ░ ░ ░ ░ ░
<60> C_RC_TA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<61> C_SE_TA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<62> C_SE_TB_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<63> C_SE_TC_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<64> C_BO_TA_1 ░ ░ ░ ░ ░ █ █ ░ ░ ░ ░ ░
<70> M_EI_NA_1*) ░ ░ ░ ╳ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<100> C_IC_NA_1 ░ ░ ░ ░ ░ ╳ ╳ ╳ ╳ ╳ ░ ░ ░ ░ ░
<101> C_CI_NA_1 ░ ░ ░ ░ ░ ╳ ╳ ░ ░ ╳ ░ ░ ░ ░ ░
<102> C_RD_NA_1 ░ ░ ░ ░ ╳ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<103> C_CS_NA_1 ░ ░ ╳ ░ ░ ╳ ╳ ░ ░ ░ ░ ░ ░ ░ ░
<104> C_TS_NA_1 ░ ░ ░ ░ ░ █ █ ░ ░ ░ ░ ░ ░ ░ ░ █ █ █ █
<105> C_RP_NA_1 ░ ░ ░ ░ ░ ╳ ╳ ░ ░ ░ ░ ░ ░ ░ ░
<106> C_CD_NA_1 ░ ░ █ ░ ░ █ █ ░ ░ ░ ░ ░ ░ ░ ░ █ █ █ █
<107> C_TS_TA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<110> P_ME_NA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<111> P_ME_NB_1 ░ ░ ░ ░ ░ ╳ ╳ ░ ░ ░ ░ ░ ░ ╳ ░
<112> P_ME_NC_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<113> P_AC_NA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<120> F_FR_NA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<121> F_SR_NA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<122> F_SC_NA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<123> F_LS_NA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<124> F_AF_NA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░

3-26 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 3: ETHERNET INTERFACE IEC60870-5-104 PROTOCOL

Type identification Cause of transmission


No. Mnemonic 1 2 3 4 5 6 7 8 9 10 11 12 13 20 37 44 45 46 47
to to
36 41
<125> F_SG_NA_1 ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<126> F_DR_TA_1*) ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░
<127> F_SC_NB_1*) ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░ ░

3. Basic application functions:


3.1. Station initialization:
⊠ Remote initialization.
3.2. Cyclic data transmission:
⊠ Cyclic data transmission.
3.3. Read procedure:
⊠ Read procedure.
3.4. Spontaneous transmission:
⊠ Spontaneous transmission.
3.5. Double transmission of information objects with cause of transmission
spontaneous:
The following type identifications may be transmitted in succession caused by a
single status change of an information object. The particular information object
addresses for which double transmission is enabled are defined in a project-specific
list.
□ Single point information: M_SP_NA_1, M_SP_TA_1, M_SP_TB_1, and M_PS_NA_1.
□ Double point information: M_DP_NA_1, M_DP_TA_1, and M_DP_TB_1.
□ Step position information: M_ST_NA_1, M_ST_TA_1, and M_ST_TB_1.
□ Bitstring of 32 bits: M_BO_NA_1, M_BO_TA_1, and M_BO_TB_1 (if defined for a
specific project).
□ Measured value, normalized value: M_ME_NA_1, M_ME_TA_1, M_ME_ND_1, and
M_ME_TD_1.
□ Measured value, scaled value: M_ME_NB_1, M_ME_TB_1, and M_ME_TE_1.
□ Measured value, short floating point number: M_ME_NC_1, M_ME_TC_1, and
M_ME_TF_1.
3.6. Station interrogation:
⊠ Group 1.
⊠ Group 2.
⊠ Group 3.
⊠ Group 4.
⊠ Group 5.
⊠ Group 6.
⊠ Group 7.
⊠ Group 8.
⊠ Group 9.
⊠ Group 10.
⊠ Group 11.
⊠ Group 12.
⊠ Group 13.
⊠ Group 14.
⊠ Group 15.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 3-27


IEC60870-5-104 PROTOCOL CHAPTER 3: ETHERNET INTERFACE

⊠ Group 16.
⊠ Global.
3.7. Clock synchronization:
⊠ Clock synchronization (optional, see Clause 7.6).
□ Day of week used.
□ RESI, GEN (time tag substituted/not substituted)
□ SU-bit (summertime) used.
3.8. Command transmission:
⊠ Direct command transmission.
□ Direct setpoint command transmission.
⊠ Select and execute command.
□ Select and execute setpoint command.
⊠ C_SE ACTTERM used.
⊠ No additional definition.
⊠ Short pulse duration (duration determined by a system parameter in the
outstation).
⊠ Long pulse duration (duration determined by a system parameter in the
outstation).
⊠ Persistent output.
⊠ Supervision of maximum delay in command direction of commands and setpoint
commands.
Maximum allowable delay of commands and setpoint commands: 5 s.
3.9. Transmission of integrated totals:
⊠ Mode A: Local freeze with spontaneous transmission.
⊠ Mode B: Local freeze with counter interrogation.
⊠ Mode C: Freeze and transmit by counter-interrogation commands.
⊠ Mode D: Freeze by counter-interrogation command, frozen values reported
simultaneously.
⊠ Counter read.
⊠ Counter freeze without reset.
⊠ Counter freeze with reset.
⊠ Counter reset.
⊠ General request counter.
⊠ Request counter group 1.
⊠ Request counter group 2.
⊠ Request counter group 3.
⊠ Request counter group 4.
3.10. Parameter loading:
⊠ Threshold value.
□ Smoothing factor.
□ Low limit for transmission of measured values.
□ High limit for transmission of measured values.
3.11. Parameter activation:
□ Activation/deactivation of persistent cyclic or periodic transmission of the
addressed object.
3.12. Test procedure:
□ Test procedure.
3.13. File transfer in monitor direction:

3-28 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 3: ETHERNET INTERFACE IEC60870-5-104 PROTOCOL

□ Transparent file.
□ Transmission of disturbance data of protection equipment.
□ Transmission of sequences of events.
□ Transmission of sequences of recorded analog values.
3.14. File transfer in control direction:
□ Transparent file.
3.15. Background scan:
□ Background scan.
3.16. Definition of timeouts:

Parameter Default value Remarks Selected value


t0 30 s Timeout of connection establishment Configurable
t1 15 s Timeout of send or test APDUs 15 s
t2 10 s Timeout for acknowledgements in case of no 10 s
data messages t2 < t1
t3 20 s Timeout for sending test frames in case of a 20 s
long idle state

Maximum range of values for all time outs: 1 to 255 s, accuracy 1 s.


3.17. Maximum number of outstanding I-format APDUs (k) and latest acknowledge
APDUs (w):

Parameter Default value Remarks Selected value


k 12 APDUs Maximum difference receive sequence number 12 APDUs
to send state variable
w 8 APDUs Latest acknowledge after receiving w I-format 8 APDUs
APDUs

Maximum range of values k: 1 to 32767 (215 – 1) APDUs, accuracy 1 APDU.


Maximum range of values w: 1 to 32767 APDUs, accuracy 1 APDU.
Recommendation: w should not exceed two-thirds of k.
3.18. Port number:

Parameter Value Remarks


Port number 2404 In all cases

3.19. RFC 2200 suite:


RFC 2200 is an official Internet Standard which describes the state of
standardization of protocols used in the Internet as determined by the Internet
Architecture Board (IAB). It offers a broad spectrum of actual standards used in the
Internet. The suitable selection of documents from RFC 2200 defined in this
standard for given projects has to be chosen by the user of this standard.
⊠ Ethernet 802.3.
□ Serial X.21 interface.
□ Other selection(s) from RFC 2200 (list below if selected).

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 3-29


IEC60870-5-104 PROTOCOL CHAPTER 3: ETHERNET INTERFACE

IEC 60870-5-104 protocol settings


Select the Settings > Communications > IEC 60870-5-104 > Protocol menu item to open
the IEC 60870-5-104 protocol configuration window.

Settings Range Default


GENERAL
IEC 60870-5-104 Function Disabled, Enabled Disabled
IEC TCP Port 1 to 65535 2404
IEC Common Address of ASDU 0 to 65535 0
IEC Cyclic Data Period 0 to 65535 s 60 s
IEC TCP Connection Timeout 10 to 300 s 120 s
Fault Report Mapping in DNP/104 Disabled, Enabled Disabled
CLIENT ADDRESS
Client Address 1* 0.0.0.0
Client Address 2* 0.0.0.0
Client Address 3* 0.0.0.0
Client Address 4* 0.0.0.0
Client Address 5* 0.0.0.0

The Client Address setpoints marked "*" are shared with DNP, as only one protocol can be
NOTE:

active at a time.
NOTE
The 3 Series relay can be used as an IEC 60870-5-104 slave device connected to a
maximum of two masters (usually either an RTU or a SCADA master station). Since the 3
Series relay maintains two sets of IEC 60870-5-104 data change buffers, no more than two
masters should actively communicate with the 3 Series relay at one time. Five client
address settings are used to filter which master is suitable for communicating with 3
Series relay.
The IEC 60870-5-104 and DNP protocols cannot be used simultaneously. When the IEC
60870-5-104 FUNCTION setting is set to “Enabled”, the DNP protocol will not be
operational.
If IEC Cyclic Data Period is set to 0 there will be no cyclic data response.
Some other settings can be added to select the first address of the different Object
Information. These settings can be removed to be consistent with the UR but are very
useful for integrating the relay into a system.

Settings Range Default


Object Information Address Binary 1 to 16777215 1000
Object Information Address Analog 1 to 16777215 2000
Object Information Address Counters 1 to 16777215 3000
Object Information Address Command 1 to 16777215 4000

By default, the Object Information Address for the different data will be as follows:
M_SP (Single Points) = 1000
M_ME (Measured Value) = 2000
M_IT (Integrated Totals) = 3000
C_SC or C_DC (Single or Double Command) = 4000

3-30 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 3: ETHERNET INTERFACE IEC60870-5-104 PROTOCOL

IEC 60870-5-104 point lists


M_SP can be configured to a maximum of 64 points. The value for each point is user-
programmable and can be configured by assigning operands.
Up to 32 Measured values (M_ME) can be configured assigning metered values to each
data point.
The Commands points (C_SC or C_DC) can be configured to a maximum of 16 points
selecting data from a list of Virtual Inputs and Force Coil commands.
The following Integrated Total (M_IT) will be added to the set of data:
• Total Number of Trips
The table below shows all the Configurable Points settings:

Settings Range Default


Binary Input Point 0 Entry* Operands Off
Binary Input Point 63 Entry* Operands Off
Analog Input Point 0 Entry* Analog Parameters Disabled
Analog Input Point 0 Scale Factor* 0.001, 0.01, 0.1, 1, 10, 100, 1000, 10000, 1
100000
Analog Input Point 0 Deadband* 0 to 100000000 30000

Analog Input Point 31 Entry* Analog Parameters Disabled


Analog Input Point 31 Scale Factor* 0.001, 0.01, 0.1, 1, 10, 100, 1000, 10000, 1
100000
Analog Input Point 31 Deadband* 0 to 100000000 30000
Binary Output Point 0 ON* Virtual Input 1 to 32 and Force Coils Off
Binary Output Point 0 OFF* Virtual Input 1 to 32 and Force Coils Off

Binary Output Point 15 ON* Virtual Input 1 to 32 and Force Coils Off
Binary Output Point 15 OFF* Virtual Input 1 to 32 and Force Coils Off

The settings marked "*" are the same as those used by the DNP 3.0 protocol to configure
NOTE:

the point mapping from address 43878 to 44101.


NOTE
The IEC 60870-5-104 Deadbands settings are used to determine when to trigger
spontaneous responses containing M_ME_NB_1 analog data. Each setting represents the
threshold value for each M_ME_NB_1 analog point.
For example, to trigger spontaneous responses from the 3 Series relay when a current
value changes by 15 A, the "Analog Point xx Deadband" setting should be set to 15. Note
that these settings are the default values of the deadbands. P_ME_NB_1 (parameter of
measured value, scaled value) points can be used to change threshold values from the
default, for each individual M_ME_NB_1 analog point.
There are three ways to send the measurands to the Master station. As the measurands
will be part of the General Group and Group 2, when a general interrogation or group 2
interrogation takes place, all the measurands will be included in the response. There is also
a cyclic data period setting where the scan period is configured to send the measurands to
the Master. The final way is to send the measurands spontaneously when a deadband
overflow takes place.
Groups of Data
The data will be organized in groups in order to provide values when the controlling station
requests by general or group interrogation.
Group 1 will be set by the 64 Single Points (M_SP).
Group 2 will be set by the 32 Measured values (M_ME).

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 3-31


IEC60870-5-104 PROTOCOL CHAPTER 3: ETHERNET INTERFACE

These 64 Single Points and 32 Measured Values will also be sent as a response to a General
Interrogation.
Integrated Totals (M_IT) will have its own Counter Group 1 and these will be sent as a
response to a General Request Counter.
The FAULT REPORT MAPPING IN DNP/104 setpoint may be set to a value of "Disabled" or
"Enabled". When "Disabled", only the configurable Analog Input points are available
beginning with the configured information object address (IOA) for analog values.When
"Enabled", the Fault Report Values are assigned from IOA to IOA + 32 in the 339 and 350
relays, and from IOA to IOA + 38 in the 345 relay, with the configurable Analog Inputs
following that IOAs.To support existing SCADA hardware not capable of 32-bit data reads,
the upper and lower 16-bit portions of the fault report time and date values have been
assigned to separate points. To read a date or time, it is necessary to read both the upper
and lower 16-bit portions, concatenate these two values to form a 32-bit value, and
interpret the result in the format associated with the point.

Fault Report Mapping 350 and 339 Fault Report Mapping 345
Disabled Enabled Disabled Enabled
Disabled Enabled Disabled Enabled
- 0 Fault Report Date Upper 16 - 0 Fault Report Date Upper 16
- 1 Fault Report Date Lower 16 - 1 Fault Report Date Lower 16
- 2 Fault Report Time Upper 16 - 2 Fault Report Time Upper 16
- 3 Fault Report Time Lower 16 - 3 Fault Report Time Lower 16
- 4 Fault Report Fault Type - 4 Fault Report Fault Type
- 5 Fault Report Ia - 5 Fault Report Ia
- 6 Fault Report Ia Angle - 6 Fault Report Ia Angle
- 7 Fault Report Ib - 7 Fault Report Ib
- 8 Fault Report Ib Angle - 8 Fault Report Ib Angle
- 9 Fault Report Ic - 9 Fault Report Ic
- 10 Fault Report Ic Angle - 10 Fault Report Ic Angle
- 11 Fault Report Ig - 11 Fault Report Ig
- 12 Fault Report Ig Angle - 12 Fault Report Ig Angle
- 13 Fault Report In - 13 Fault Report In
- 14 Fault Report In Angle - 14 Fault Report In Angle
- 15 Fault Report Va - 15 Fault Report System Frequency
- 16 Fault Report Va Angle - 16 Fault Report Ia 2
- 17 Fault Report Vb - 17 Fault Report Ia 2 Angle
- 18 Fault Report Vb Angle - 18 Fault Report Ib 2
- 19 Fault Report Vc - 19 Fault Report Ib 2 Angle
- 20 Fault Report Vc Angle - 20 Fault Report Ic 2
- 21 Fault Report Vab - 21 Fault Report Ic 2 Angle
- 22 Fault Report Vab Angle - 22 Fault Report Ig 2
- 23 Fault Report Vbc - 23 Fault Report Ig 2 Angle
- 24 Fault Report Vbc Angle - 24 Fault Report In 2
- 25 Fault Report Vca - 25 Fault Report In 2 Angle
- 26 Fault Report Vca Angle - 26 Fault Report Idiff 1 PhA
- 27 Fault Report Vn - 27 Fault Report Idiff 1 PhA Angle
- 28 Fault Report Vn Angle - 28 Fault Report I Restraint PhA
- 29 Fault Report Vaux - 29 Fault Report I Restraint PhA Angle
- 30 Fault Report Vaux Angle - 30 Fault Report Idiff 1 PhB

3-32 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 3: ETHERNET INTERFACE SUMMARY OF ETHERNET CLIENT CONNECTIONS

Fault Report Mapping 350 and 339 Fault Report Mapping 345
Disabled Enabled Disabled Enabled
- 31 Fault Report System Frequency - 31 Fault Report Idiff 1 PhB Angle
- 32 Fault Report Phases - 32 Fault Report I Restraint Ph B
0 33 Analog Input Point 0 Entry - 33 Fault Report I Restraint PhB Angle
1 34 Analog Input Point 1 Entry - 34 Fault Report Idiff 1 PhC
… … … - 35 Fault Report Idiff 1 PhC Angle
… … … - 36 Fault Report I Restraint PhC
31 64 Analog Input Point 31 Entry - 37 Fault Report I Restraint PhC Angle
- 38 Fault Report Phases
0 39 Analog Input Point 0 Entry
1 40 Analog Input Point 1 Entry
… … …
… … …
31 70 Analog Input Point 31 Entry

Some fault report data has been scaled to fit into a 16-bit value as follows:

Fault Report Data Scale


Fault Report Ia, Ib, Ic, Ia2, Ib2, Ic2 Format_F10 * 100 / CT Primary
Fault Report Ig, Ig2 Format_F10 * 100 / Gnd CT Primary
Fault Report In , In2 Format_F10 * 100 / CT Primary
Fault Report Va, Vb, Vc, Vab, Vbc, Vca, Vn Format_F9 * 10000 /( BusVTRatio * BusVTSecondary)
Fault Report Vaux Format_F9 * 10000 /( AuxVTRatio * AuxVTSecondary)
Fault Report System Frequency Format_F3
Fault Report Phases Format_F37

Summary of Ethernet client connections


Table 3-11: Case A
Settings Ethernet
DNP CHANNEL 1 PORT NONE
DNP CHANNEL 2 PORT NONE
104 GENERAL FUNCTION DISABLE
Client 1 Client 2 Client 3
MODBUS NOTHING NOTHING
MODBUS MODBUS NOTHING
MODBUS MODBUS MODBUS

Table 3-12: Case B


Settings Ethernet
DNP CHANNEL 1 PORT TCP
DNP CHANNEL 2 PORT NONE
104 GENERAL FUNCTION DISABLE
Client 1 Client 2 Client 3

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 3-33


SUMMARY OF ETHERNET CLIENT CONNECTIONS CHAPTER 3: ETHERNET INTERFACE

Settings Ethernet
DNP NOTHING NOTHING
DNP MODBUS NOTHING
DNP MODBUS MODBUS

Table 3-13: Case C


Settings Ethernet
DNP CHANNEL 1 PORT UDP
DNP CHANNEL 2 PORT NONE
104 GENERAL FUNCTION DISABLE
Client 1 Client 2 Client 3 Client 4
DNP NOTHING NOTHING NOTHING
DNP MODBUS NOTHING NOTHING
DNP MODBUS MODBUS NOTHING
DNP MODBUS MODBUS MODBUS

Table 3-14: Case D


Settings Ethernet
DNP CHANNEL 1 PORT TCP
DNP CHANNEL 2 PORT TCP
104 GENERAL FUNCTION DISABLE
Client 1 Client 2 Client 3
DNP DNP NOTHING
DNP DNP MODBUS

Table 3-15: Case E


Settings Ethernet
DNP CHANNEL 1 PORT TCP
DNP CHANNEL 2 PORT UDP
104 GENERAL FUNCTION DISABLE
Client 1 Client 2 Client 3 Client 4
DNP-TCP DNP-UDP NOTHING NOTHING
DNP-TCP DNP-UDP MODBUS NOTHING
DNP-TCP DNP-UDP MODBUS MODBUS

Table 3-16: Case F


Settings Ethernet
DNP CHANNEL 1 PORT XX (any
value)
DNP CHANNEL 2 PORT XX (any
value)
104 GENERAL FUNCTION ENABLE
Client 1 Client 2 Client 3
IEC104 IEC104 NOTHING
IEC104 IEC104 MODBUS

3-34 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


GE
Grid Solutions

3 Series Protective Relay Platform

Chapter 4: 3 Series IEC61850 GOOSE

3 Series IEC61850 GOOSE

3 Series relays support the IEC61850 GOOSE messaging service. This service allows 3
Series relay units to exchange digital and analog information with other relays supporting
the same service. This information exchange is at speeds suitable for protection.
One example of how this communication service can be used within a protection scheme,
is to have it provide the communications link for a blocking scheme to protect a bus, as
shown in the above figure. In this example, if there is a fault on one of the feeders, say,
feeder A, both the instantaneous overcurrent element of the 350 feeder A and the
instantaneous overcurrent element of the 345 will pick up. The 345’s protection has been
coordinated with the downstream feeders such that if the 345 does not receive a GOOSE

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-1


GOOSE CONFIGURATION VIA THE 3 SERIES MENUS CHAPTER 4: 3 SERIES IEC61850 GOOSE

message from one of the feeders (in this case feeder A) within a specified period of time
after detection of the overcurrent fault, the 345 will trip its breaker, removing power to the
bus. If however, a GOOSE message is received from any one of the feeder relays, the 345
will delay the trip of its breaker long enough for the downstream feeder to remove the
fault.
Configuration of GOOSE messaging within the 3 Series family of relays can be
accomplished in one of three ways:
• Users familiar with both the 3 Series configuration menus and IEC61850
implementation within the 3 Series, may prefer to configure the relays directly through
the menus.
• For those not familiar with the 3 Series IEC61850 implementation and/or the 3 Series
menus, the 3 Series simplified GOOSE message tool may save time and effort.
• For those interested in a more IEC61850-centric approach, the IEC61850 configurator
tool may be used.

GOOSE configuration via the 3 Series menus


The 3 Series relay firmware supports IEC61850 GOOSE communications on the optional
communications daughter board.
Portions of the IEC61850 standard not pertaining to GOOSE, are not implemented in the 3
Series relay depending on order code and GOOSE type setting (found under S1 RELAY
SETUP > COMMUNICATIONS > GOOSE CONFIGURATION > GENERAL SETTINGS).

IEC61850 Feature Order Code includes Order Code includes Order Code includes
"IEC61850" & GOOSE Type "IEC61850" & GOOSE Type "IEC61850 GOOSE"
is "Simplified" is "Advanced" (and not "IEC61850")
Manufacturing Message Specification (MMS) Not Available Available Not Available
standard ISO/IEC 9506
GOOSE Transmission of analog values Not Available Available Not Available
GOOSE Reception of analog values Not Available Not Available Not Available
GOOSE Configuration storage MODBUS Set Points CID file and MODBUS Set MODBUS Set Points
Points
File system to maintain ICD/CID files Not Available Available Not Available

Configuration of transmission and reception settings for the GOOSE feature are performed
using EnerVista SR3 Setup Software.
The 3 Series relay firmware accepts GOOSE messages from 8 Series, UR, F650 and UR Plus.
The interoperability with other manufacturers will be guaranteed in almost all cases, by
implementing the reception side with nested structures (one level of nesting) and all the
standard data types.
GOOSE settings changes will take effect only after the 3 Series relay is re-booted. One
setting is available to Enable/Disable both Transmission and Reception. It is possible to
change these settings from the Front Panel of the relay.

4-2 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE GOOSE CONFIGURATION VIA THE 3 SERIES MENUS

Figure 4-1: EnerVista 3 Series Setup GOOSE General Settings

EnerVista 3 Series Setup software structure


The structure below provides a summary of how the EnerVista 3 Series Setup software
should be used to implement the sections detailed in this document, in order to enable
both transmission and reception of GOOSE messages.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-3


GOOSE CONFIGURATION VIA THE 3 SERIES MENUS CHAPTER 4: 3 SERIES IEC61850 GOOSE

4-4 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE GOOSE CONFIGURATION VIA THE 3 SERIES MENUS

GOOSE transmission
The 3 Series relay firmware supports one transmission dataset.
All elements in the transmit dataset must be Boolean values.
The user can define the number of items in the transmit data setup, to a maximum of 32.
The minimum number of items in a data set is 1.
The number of data items configured before the NULL (below), determines the dataset
length. It is also possible to map any Item to a fixed value (ON or OFF).
The IEDName is taken from setting S1 Relay Setup > Installation > Relay Name
Setting the IEDName to "Feeder_25Kv_Line1" (for example) would result in a DataSet
Reference:
Feeder_25Kv_Line1LDInts/LLN0$GOOSE1
Another, less common, possibility is to change the 123E setting ( using modbus ) for
example to "GOOSE_Points" resulting in a DataSet Reference:
Feeder_25Kv_Line1LDInts/LLN0$GOOSE_Points

Figure 4-2: EnerVista 3 Series Setup GOOSE Transmission page

• GOOSE ID: A string of up to 40 characters that represent the IEC 61850 GOOSE
application ID (GoID). This string identifies the GOOSE Tx message to the receiving
device.
• VLAN Identifier/Priority: a two-byte value whose 3 most significant bits define the
user priority and the twelve least significant bits are for the VLAN identifier.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-5


GOOSE CONFIGURATION VIA THE 3 SERIES MENUS CHAPTER 4: 3 SERIES IEC61850 GOOSE

VLAN PRIORITY
Range: 1 to 7
Default: 4
This setting selects the value of the priority field in the VLAN tag.
VLAN ID
Range: 0 to 4095
Default: 0
This setting selects the value of the ID field in the VLAN tag.
• ETYPE AppID: to select ISO/IEC 8802-3 frames containing GSE Management and
GOOSE messages and to distinguish the application association.
• Update Time: time to delay transmission of the next iteration of a particular GOOSE
message if no value within the message has changed. I.e. 60. Measured in ms.
• Conf Revision Number: This number updates automatically after Tx data set has been
modified and the relay power has been cycled.
• Destination MAC Address: This setting is required to ensure interoperability as some
vendors require valid range of destination MAC addresses in GOOSE messages.
• Quality Flags: In order to ensure interoperability with some vendors, there is a quality
flag associated with a data item. The quality flags item only can be set if its associated
data item is selected. The data type of the quality flags is Bitstring13 and the attribute
will always set to value “0” at the protocol level.
All the elements in a dataset can be mapped by the user to any available digital value
within the 3 Series relay, including:
• Alarm elements
• Protection elements (Pickup, Dropout and Operate of all available protection elements)
• Control element (all available control elements)
• Status of digital inputs
• Status of digital outputs
• Status of virtual inputs
• Status of virtual outputs.
The destination multicast address for GOOSE messages is composed of the MAC address
of the device, with the least significant bit in the most significant byte, set to 1.
The 3 Series relay relay does not generate ICD files that describe the format of transmitted
GOOSE items. EnerVista 3 Series Setup software is used to generate these files, and the
files must contain at least the following information:
• Mandatory Nodes: LLN0, LPHD, GGIO, etc.
• GOOSE Configuration: Control Block, Dataset, etc.
• Dataset configuration.
Once a GOOSE message is transmitted, it will be retransmitted at an increasing time
interval as follows: 4ms, 8ms, 16ms, and then 1 second.

4-6 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE GOOSE CONFIGURATION VIA THE 3 SERIES MENUS

GOOSE Rx
The 3 Series relay firmware allows the user to configure up to 8 separate GOOSE messages
for reception. One GOOSE message consists of 2 parts: Header and Dataset. The Header is
used for identification and the Dataset for data handling.
At this point , it is convenient to clarify the difference between Remote GOOSE and Remote
Device. One Remote Device can send more than one GOOSE, so from the reception point of
view, it is not very useful to handle Remote Devices. Instead, it is simpler to deal with
Remote GOOSE messages.
The 3 Series relay firmware is able to receive up to a total of 8 remote GOOSE messages
transmitted from up to a maximum of 8 remote devices.

GOOSE Rx status
In order to visualize the status of the incoming GOOSE messages, the following status
registers are available in the MODBUS memory map:

Data Item EnerVista 3 Series MMI Text Value Format Size in Modbus
Setup Text Code words Address
eDataRemoteGOOSEStatus Remote GOOSE Status REM GOOSE STAT 0xFFFF FFFF FC215 2 31515
eDataRemoteGOOSEHeaderStatus Remote GOOSE Header REM GOOSE HDR 0xFFFF FFFF FC215 2 31517
Status STAT

GOOSE 1 0x0000 0001


GOOSE 2 0x0000 0010
GOOSE 3 0x0000 0100
GOOSE 4 0x0000 1000

GOOSE 5 0x0001 0000


GOOSE 6 0x0010 0000
GOOSE 7 0x0100 0000
GOOSE 8 0x1000 0000

unsigned 32 bits GOOSE Receive Status Text String


Enum FC215 0x0001 eFMT_GOOSE1 GOOSE 1 RECEIVED
0x0002 eFMT_GOOSE2 GOOSE 2 RECEIVED
0x0004 eFMT_GOOSE3 GOOSE 3 RECEIVED
0x0008 eFMT_GOOSE4 GOOSE 4 RECEIVED
0x0010 eFMT_GOOSE5 GOOSE 5 RECEIVED
0x0020 eFMT_GOOSE6 GOOSE 6 RECEIVED
0x0040 eFMT_GOOSE7 GOOSE 7 RECEIVED
0x0080 eFMT_GOOSE8 GOOSE 8 RECEIVED

The GOOSE Header Status is set at 1 if all the header’s filters are passed. Otherwise, the
Header Status will be set at 0.
After a GOOSE header is accepted, the 3 Series relay firmware either accepts or rejects the
associated dataset. The firmware bases this decision on the RX dataset that has been
configured for the header. If both (Header and Dataset structure) are accepted, the Remote
GOOSE Status is set to 1, otherwise it is set to 0. If the header status is never set to 1, then
the associated GOOSE status always remains at 0.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-7


GOOSE CONFIGURATION VIA THE 3 SERIES MENUS CHAPTER 4: 3 SERIES IEC61850 GOOSE

The incoming GOOSE defines the timeout for the next message. GOOSE Header Status is
set to 0 if the next message is not received within the specified amount of time. GOOSE
Status is also set to 0 if the next message is not accepted within the specified amount of
time.
If a GOOSE message is received, and its header has not been configured for reception, the
firmware ignores the message.
It is possible to see this GOOSE status information from the 3 Series relay front panel.

Figure 4-3: EnerVista 3 Series Setup GOOSE Status page

4-8 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE GOOSE CONFIGURATION VIA THE 3 SERIES MENUS

GOOSE Rx headers
The 3 Series relay firmware supports GOOSE messages that contain up to one level of
nesting, and that are capable of mapping only digital values to the remote inputs.
The 3 Series relay firmware maintains the format of GOOSE messages that can be received
in MODBUS registers.
Configuration of GOOSE messages to be received by the device, is implemented using the
EnerVista 3 Series Setup software, as shown below, either by reading in and parsing the
ICD, or SCD file from a remote device, or by manually configuring the settings.

Figure 4-4: EnerVista 3 Series Setup GOOSE Rx Header

GOOSE receive dataset structure


The format of the GOOSE messages that can be accepted by the firmware is stored in
MODBUS registers. The maximum total storage size for the 8 Rx GOOSE structure is 250
registers. This means that the number of elements per Rx GOOSE is unlimited provided that
the total size of all Rx structures doesn’t exceed the defined limit of 250 registers.
The User can configure the Datasets of his choice, and if he exceeds the 250 registers limit
when he tries to SAVE, the following message appears, saying that the selection of the user
has exceeded the limit of 250 registers and that anything beyond will be lost.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-9


GOOSE CONFIGURATION VIA THE 3 SERIES MENUS CHAPTER 4: 3 SERIES IEC61850 GOOSE

Clicking on YES will save Dataset items selection up to 250 registers and the others will be
lost. The screen then refreshes, reflecting the saved data. Clicking on NO will do nothing
and the user can make changes on the screen (shown below).
The RX GOOSE message data types that are handled by the software, are:
Bool, Byte, Ubyte, Short, Ushort, Long, Ulong, Int64, Uint64, Float, Double, Btime4, Btime6,
Utctime, Bcd, Vstring, Ostring, OVstring, Bstring, Bvstring

Figure 4-5: EnerVista 3 Series Setup GOOSE Dataset

4-10 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE GOOSE CONFIGURATION VIA THE 3 SERIES MENUS

GOOSE remote inputs


The firmware allows the user to map each of the digital data points received in a data set,
configured for reception, to one of 32 GOOSE remote inputs.
More than 1 GOOSE remote input can be mapped to the same data element, in a data set
belonging to a received GOOSE message.
GOOSE remote inputs can only be mapped to digital data elements.
The firmware considers a GOOSE remote input to be in the “on/off” state when the digital
data element to which it is mapped, is in the “on/off” state.
The firmware allows the user to assign a string name to each of the 32 remote inputs, and
allows the string name assigned to each remote input to be up to 14 characters.

Figure 4-6: EnerVista 3 Series Setup GOOSE Remote Inputs - 1 of 2

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-11


GOOSE CONFIGURATION VIA THE 3 SERIES MENUS CHAPTER 4: 3 SERIES IEC61850 GOOSE

Figure 4-7: EnerVista 3 Series Setup GOOSE Remote Inputs - 2 of 2

The following format indicates the source of the GOOSE message:


The string name of each remote input is maintained in a set of MODBUS registers, where
each string name consumes up to 7 MODBUS registers.
Each GOOSE remote input can be mapped to one of the following functions:
• protection element block (all protection elements that have a single or multiple block
setting)
• user assignable LED
• digital output
• group setting change (350 and 345 only)
The 3 Series relay records changes in GOOSE remote inputs in the Event Log.
The time recorded in a GOOSE remote input’s event log entry, is the time at which the
change in the input’s state is detected.
The 3 Series relay invokes a logic (block / control) function when its corresponding GOOSE
remote input is asserted.
In the 3 Series relay there are many different settings where it is possible to select between
a Contact Input (1 to 10 ), a Virtual Input (1 to 32 ) or a Logic Element (1 to 16). In all of these
settings it is also possible to select Remote Input (1-32 ) if the GOOSE feature is enabled on
the relay.

4-12 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE USING THE SIMPLIFIED GOOSE CONFIGURATOR

Using the Simplified GOOSE Configurator

The simplified GOOSE configuration tool has no way of sensing manual changes to the
NOTE:

GOOSE configuration menus and so when used, the SGC tool overwrites the entire
NOTE IEC61850 settings of all settings files within the offline site. For this reason it is not
advisable to mix the two techniques.

3 Series GOOSE Implementation


Before we proceed with the configuration tool we will review the 3 Series IEC61850
implementation. The 3 Series family of relays can receive and transmit both digital and
analog information. However, currently only digital status information received via GOOSE
can be used in the 3 Series relays.
Transmission Data Block
Each 3 Series relay has one GOOSE transmission data block consisting of up to 64 data
items. Once configured, this block is transmitted at power-up, on a pre-configured time
basis (ranging from 1 to 60 seconds) and within a window of 4 to 10 ms after a digital point
within the data block has changed state.
Receive Data Block
Each 3 Series relay has eight GOOSE receive data blocks. Each receive data block consists
of up to 64 data items and is configured to receive the transmission from a specific device
on the network. Received digital status information from any of the eight receive data
blocks is mapped into the local relay’s 32 remote inputs such that the status can be made
available to the relay.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-13


USING THE SIMPLIFIED GOOSE CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

The total number of items that can be received is affected by the number of GOOSE
NOTE:

receives that have been configured, the type of data item, and by whether or not the
NOTE quality is to be received with the item.

Setting up the GOOSE Configurator

This section will explain how to setup GOOSE messaging between two relays using the
Simplified GOOSE Configurator (SGC). As stated earlier, the purpose of the SGC is to allow
the user to configure the 3 Series relays to share digital data points via GOOSE without
requiring a detailed understanding of the IEC61850 model or of how to configure GOOSE
within the relay. As SGC may not allow advanced users the flexibility for a complex
application, manual configuration could be required and used.
SGC is only intended to modify offline settings files. There is no support for online devices
and only settings files of firmware version 1.4x and higher, with the 2E/3E option, will be
included in the simplified GOOSE configuration screen for any given site.
Setting up the Simplified GOOSE Configurator is a three-step process:
1. Create a GOOSE Site (in the offline window) that will contain all the related relay
settings files, then add the associated 3 Series IED settings files to this site.
2. Launch the Simplified GOOSE Configurator, configure the GOOSE transmissions for
each relay, then save and exit the tool.
3. Download the settings files to the associated relays.
Each of these steps will be explained in detail in the following section. IEC61850 GOOSE
messaging uses Ethernet, so the 3 Series relay must be equipped with an Ethernet port
and support the IEC61850 GOOSE messaging option. Each relay can be connected to the
Ethernet LAN through either the fiber optic (preferred) or twisted pair Ethernet port but not
BOTH at the same time.

4-14 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE USING THE SIMPLIFIED GOOSE CONFIGURATOR

Once an IP address and subnet mask have been configured within each relay, and the
power cycled, the relays can be connected though a switch to the computer running the
EnerVista 3 Series Setup configuration software. Please note that an IP address and subnet
mask are not required for GOOSE but are required to configure the relays for operation via
Ethernet. For simplicity, the objective of this exercise is to configure the relay labeled 228
to send a GOOSE message containing the status of Virtual Input 1 to the relay labeled 230.
Upon reception of the message, relay 230 will use this Virtual Input status to control output
relay number 3.
The 3 Series relay can save RX dataset information to a maximum of 250 items. If GOOSE
NOTE:

configured through SGC requires a single device to receive GOOSE messages from multiple
NOTE senders, such that the total items may be more that 250, then additional items beyond 250
may not get saved in the settings file. In such a case, it is recommended to manually verify
the saved configuration in the receiver device once (under Setpoints > S1 Relay Setup >
Communication > GOOSE Configuration > Reception > RX dataset) to avoid
communication problems.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-15


USING THE SIMPLIFIED GOOSE CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

Connection

Once an IP address and subnet mask have been configured within each relay, and the
power cycled, the relays can be connected though a switch to the computer running the
EnerVista 3 Series Setup software.

Configuration
Launch the EnerVista 3 Series Setup software, and using the help menu, ensure that the
EnerVista 3 Series Setup software is version 1.41 or higher. If it is not, go to the GE Multilin
website and download the latest copy of the EnerVista 3 Series Setup software before
proceeding. .

4-16 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE USING THE SIMPLIFIED GOOSE CONFIGURATOR

1. CONFIGURE THE RELAYS USING THE DEVICE SETUP MENU, ensuring the relay
firmware is version 1.40 or higher and that the relay includes either the 2E or 3E
option in its order code.

2. CREATE AN OFFLINE SITE AND ADD THE DEVICE SETTINGS FILES:


Note that an additional tree labeled IEC61850 Devices is also created. This is a place
holder for non-3-Series CID files so that all project-related files can be located within
one site.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-17


USING THE SIMPLIFIED GOOSE CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

2.1. Right-click the offline File tree and select Add New Site (see figure below). This
selection will launch another window requesting the name of the new site. In
our example, GOOSE was entered for the site name. Once the site name has
been entered, selecting OK will create a new site in the offline window with a
name corresponding to that which was entered.

Note that an additional tree labeled IEC61850 Devices is also created. This is a place
holder for non-3-Series CID files such that all project-related files can be located
within one site.

2.2. Right-click the offline site named GOOSE (see above figure). You will see
several selections:
– Add New Site: This selection will add a new site to the root of the offline tree.
– Remove Site: This selection removes the site and settings files branches from the
offline settings file list.
– Rename Site: This selection renames the site name:
– Move Settings File: This selection allows the user to move a settings file from one
site to another.
– Simplified GOOSE Configurator: This selection launches the Simplified GOOSE
Configurator for the given site branch. The feature will be grayed out if the
highlighted item is not a site name or settings file within a site branch. Therefore

4-18 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE USING THE SIMPLIFIED GOOSE CONFIGURATOR

any settings file off the root of the offline tree will not be considered for this
feature.

2.3. Select New Settings File and enter the order code of the first relay.

Note that the setting file name 228_GOOSE7 now appears under the site GOOSE.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-19


USING THE SIMPLIFIED GOOSE CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

2.4. Using the browser select the name (in this case 228_GOOSE7) and location of
the offline settings file. Once entered select Save, then OK.

2.5. Repeat this process to enter the second setting file (using the name
230_GOOSE7), then again select Save and OK.

Both settings files should now appear under the offline site GOOSE.
3. LAUNCH THE SGC TOOL AND CONFIGURE THE TRANSMISSIONS:

4-20 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE USING THE SIMPLIFIED GOOSE CONFIGURATOR

Now that we’ve created the offline settings files for our relays it is time to launch the
Simplified GOOSE Configurator (SGC) tool.
3.1. Right-click the site GOOSE, then select Simplified GOOSE Configurator to
launch the SGC tool.
When the SGC tool is launched, a screen will appear that displays a grid. The first
column of this grid contains the transmission device list and the first row contains the
reception device list.
For the reception row, the second column and those to the right will correspond to one
of the devices in the site list. Each of these columns has 32 cells which represent the
digital information that each device will be receiving, and the associated remote
input. The last column will always be used as a placeholder for a non-3-Series device
(Generic IED). This will allow the user to select data items that do not map to any 3
Series device but will be used by other devices. Any data items found in this column
will not be saved to a device; it is used only to build the transmission data set in the
transmitting 3 Series relay. To make the configuration easy, we allow the user to drag
and drop items from the transmission tree to the corresponding column of the device
that will receive the information.
When we expand each device within the transmission column, we will see a tree
similar to what we have in the offline tree.

Again each reception device column has 32 entries corresponding to the 32 remote
inputs of this device into which the associated status information is mapped.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-21


USING THE SIMPLIFIED GOOSE CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

At the bottom of the screen there is a selection to determine if quality bits are to be
included with the value. Users have an option to Enable/Disable Quality here. In our
example application we are going to send just the status of Virtual Input 1 from the
relay labeled 228 to the relay labeled 230, so the Value Only selection will be made by
clicking on that portion of the screen.
Also located at the bottom of the screen are the icons the restore Restore and Default:
– Restore if selected will restore the screen to the last save position
– Default if selected will set all the screen information to default values.
To configure Relay228_GOOSE7 to transmit Virtual Input 1 proceed as follows:

4-22 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE USING THE SIMPLIFIED GOOSE CONFIGURATOR

The simplified GOOSE Configuration Tool required all settings files to be present before
NOTE:

launching the tool. If at a later date settings files need to be added or removed, the
NOTE above process must be repeated from the beginning.

3.2. In the Transmission Device column expand the tree of 228_GOOSE7 such that
Virtual input 1 is displayed. Left-click Virtual Input 1 in the Transmission Device
column and drag this point into the relay(s) that are to receive the status of this
point.
In our example we would left-click Virtual Input 1 and drag it into the Reception
column corresponding to the relay labeled 230_GOOSE7. In this case we dragged
Virtual Input 1 from the relay labeled 228_GOOSE7 into the first row of relay
230_GOOSE7. This position corresponds to Remote Input 1. This is the process that is
used to configured both the transmission and reception. Once the configuration is
complete, select Save. The SGC program then takes the information within the screen
and determines how to set up the transmission and reception list for each device.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-23


USING THE SIMPLIFIED GOOSE CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

3.3. Before the final step of downloading the settings to each relay, we need to
enable the Virtual Input within 228_GOOSE7 such that we can change its
status.

3.4. Since Remote Input 1 of 230_GOOSE7 will receive the status of the Virtual Input
of 228_GOOSE7, we must configure a logic element within 230_GOOSE7 to use
the status of Remote Input 1 to drive the status of Relay 3 as shown. Once these
settings have been saved we can proceed to the next step: downloading the
offline Settings files to the relays.

4-24 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE USING THE SIMPLIFIED GOOSE CONFIGURATOR

4. DOWNLOAD THE SETTINGS FILES TO THE ASSOCIATED RELAYS

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-25


USING THE SIMPLIFIED GOOSE CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

4.1. Right-click the settings file labeled 228_GOOSE7 and select Write Setting File
to Device. This action launches a second window showing all devices
configured for the online window. To start the download process to Relay 228,
click Relay 228 such that it is highlighted, then select Send.

4.2. Once the download is complete, repeat the process for the setting file labeled
230_GOOSE7 and relay 230. At this point the GOOSE messaging configuration
is complete.
4.3. To test the GOOSE messaging first, open the Virtual Input Commands window
of Relay 228, then under 230’s Actual Values branch, open the Output Relays
window.

Force Virtual Input number 1 of 228 on or off and monitor the status of Relay 3 in
Relay 230. Note that the status of Relay 3 follows the status of Virtual Input 1 of Relay
228.
This completes the exercise.

4-26 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE USING THE IEC 61850 CONFIGURATOR

Using the IEC 61850 configurator

Introduction to the 3 Series IEC61850 Device Configurator


The 3 Series family of relays supports the IEC61850 GOOSE messaging service.

This service offers 3 Series relays the ability to exchange digital and analog information
with other relays supporting the same service, at speeds suitable for protection. The
configuration of GOOSE messaging within the 3 Series family of relays can be
accomplished in one of three ways:
1. For those users familiar with both the 3 Series configuration menus and IEC61850
implementation within the 3 Series, they may prefer to configure the relays directly
through the 3 Series menus if the GOOSE messaging is restricted to the exchange of
digital point status.
2. For those not familiar with 3 Series IEC61850 implementation and/or the 3 Series
menus, the above 3 Series Simplified GOOSE Message tool may save time and effort,
and is again restricted to the exchange of digital status information.
3. The 3 Series IEC61850 Device Configurator may be used with 3 Series relays
supporting the “3E” option and itself supports the configuration of both digital and
analog items for transmission.
This section of the Communications Guide deals with configuration of GOOSE messages
via the 3 Series IEC61850 Device Configurator.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-27


USING THE IEC 61850 CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

An Ethernet connection is required for programming relays using the IEC61850 Device
NOTE:

Configurator; connecting to the relay via USB is not recommended.


NOTE
For details on establishing an Ethernet Connection please refer to "SR3 GOOSE
configuration - Lab".

3 Series GOOSE implementation


Before we proceed we will review the 3 Series IEC61850 implementation. The 3 Series
family of relays can receive and transmit both digital and analog information. However,
currently only digital status information received via GOOSE can be used within the
3 Series relays.
Transmission data block
Each 3 Series relay has one GOOSE transmission data block consisting of up to 64 data
items. Once configured, this block is transmitted at power-up, on a pre-configured time
basis (ranging from 1 to 60 seconds) and within a window of 4 to 10 ms after a digital point
within the data block has changed state.
Reception data blocks
Each 3 Series relay has eight GOOSE receive data blocks. Each receive data block consists
of up to 64 data items and is configured to receive the transmission from a specific device
on the network. Received digital status information from any of the eight receive data
blocks is mapped into the local relay’s 32 remote digital input locations such that this
status can be used by the local relay.
The total number of items that can be received is affected by the number of GOOSE
NOTE:

receives that have been configured, the type of data item, and by whether or not the
NOTE quality is to be received with the item.

4-28 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE USING THE IEC 61850 CONFIGURATOR

The 3 Series IEC61850 Device Configurator allows the user to build the GOOSE
transmission by dragging and dropping digital and analog values from the 3 Series logical
nodes directly into the GOOSE transmission message. The 3 Series IEC61850 logical nodes
include five General Generic Input/Output logical nodes referred to as GGIO X where "X"
represents an index (from 1 to 7 in the case of the 3 Series) used to differentiate between
different GGIO logical nodes.

The 3 Series Contact I/O, and Virtual Inputs, and the status of Logic Elements are not data
types defined within IEC61850. The GGIO logical nodes are used to map none IEC61850
data into IEC61850 as “general generic” data which is defined within the IEC61850
standard. The 3 Series Contact I/O, Virtual Inputs and the status of Logic Elements are
mapped into GGIO2, 3 and 4 respectively.
Also available are GGIO7 (Analog Operands) and rtdGGIO6 (RTDs). See Appendix A for the
NOTE:

complete IEC 61850 implementation.


NOTE
Let’s take a moment to examine GGIO logical nodes further before moving on. We will take
Virtual Inputs as our example:

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-29


USING THE IEC 61850 CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

Within 3 Series relays there are 32 Virtual Inputs. The status of each of these 32 Virtual
Inputs is automatically mapped into GGIO3 indication 1 through 32 within the stVal bit. In
other words, each stVal bit within each indication, reflects the status of the corresponding
Virtual Input. In addition to the individual digital status, each indication area contains a
time stamp for the last change and an indication of the quality of the data. Within the
EnerVista 3 Series Setup software, the user can drag and drop the stVal bit or other digital
or analog values, from resident logical nodes into the GOOSE message in order to build the
GOOSE message that this relay will eventually transmit.

4-30 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE USING THE IEC 61850 CONFIGURATOR

GGIO5 contains the status of the remote inputs received by this relay while GGIO1 contains
the status of the remote outputs configured under Setpoints > S1 Relay Setup >
Communication > Transmission.

3 Series GOOSE configuration - Lab


This section explains how to setup GOOSE messaging between two relays using the 3
Series IEC61850 Device Configurator. Please note that only relay settings files with
firmware version 1.41 or higher, with the 3E option, support this feature.

For simplicity, the objective of this exercise will be to demonstrate how to configure the
3 Series relay labeled 228 (using the 3 Series IEC61850 Device Configurator portion of the
EnerVista 3 Series Setup software) to send a GOOSE message containing the status of
Virtual Input 1 to the 3 Series relay labeled 254.
Once the IP address and subnet mask have been configured within each relay using the
procedures outlined earlier in this guide, and the power to the relays cycled, the relays are
ready to be connect though a switch to the computer running the EnerVista 3 Series
Setup software. Please note that an IP address and subnet mask are not required for
GOOSE messaging but are required to allow configuration of the relays via Ethernet.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-31


USING THE IEC 61850 CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

Launch the EnerVista 3 Series Setup software and using the Help menu, ensure that the
EnerVista 3 Series Setup software is version 1.41 or higher. If it is not, go to the GE Multilin
website and download the latest copy of the EnerVista 3 Series Setup software before
proceeding.

1. Configure both relays in the EnerVista 3 Series Setup software and set the GOOSE
transmission of both relays to Advanced.
2. Configure relay 228’s GOOSE transmission.
3. Configure relay 254’s GOOSE reception.
4. Testing

4-32 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE USING THE IEC 61850 CONFIGURATOR

Configuration lab
steps

1. Configure both relays in the EnerVista 3 Series Setup software and set the GOOSE
transmission of both relays to Advanced.
Configure both 3 Series relays into the EnerVista 3 Series Setup application using the
following procedure
1.1. Launch the EnerVista 3 Series Setup software and select Device Setup.
1.2. Select Add Site.
1.3. Enter an optional site name.
1.4. Select Add Device.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-33


USING THE IEC 61850 CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

1.5. Enter an optional device name.


1.6. Set the interface to Ethernet and enter the first relays IP address, and Slave
address.
1.7. To verify communications and ensure the correct order code is entered, select
Read Order Code.
1.8. After a brief period of time the software program should read the relay’s order
code and fill it in within the work area. If the software fails to connect to the
relay and read the order code, an error message will appear indicating that
either the relay was not connected to the network correctly, or the IP address,
subnet mask and/or the ModBus Slave address entered in the software does
not match the relay. Troubleshoot accordingly.

4-34 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE USING THE IEC 61850 CONFIGURATOR

1.9. Repeat for the second 3 Series relay.


1.10. Select OK to save the settings and return to the Main Menu.
- Before we can configure the relay using the IEC61850 Device Configuration tool we
must set the GOOSE message transmission of both relays to Advanced as follows:

1.11. For relay 228, open Setpoints > Communications > GOOSE Configuration >
General Settings.
For EnerVista 3 Series Setup software version 2.2x and earlier, this menu option is under
NOTE:

Transmission instead of General Settings.


NOTE
1.12. Set the GOOSE Type to Advanced.
1.13. Select Save.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-35


USING THE IEC 61850 CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

1.14. Repeat for Relay 254.

2. Configure relay 228’s GOOSE transmission


The following steps are used to configure relay 228’s transmission:

2.1. Right-click relay 228, then select IEC61850 Device Configurator to launch the
software

4-36 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE USING THE IEC 61850 CONFIGURATOR

2.2. Select the Settings tab, then enter a unique IED name for this relay. For this lab
exercise select “one” by a left double-click on the cell to the left of the cell
labeled "IEC Name", and enter “one”.
2.3. Select the GOOSE transmission tab to configure the actual GOOSE
transmission name and data within the transmission that will be sent.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-37


USING THE IEC 61850 CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

2.4. Within the GOOSE transmission control block work area you will see the SR3xx
IED icon with IED name “one”. Click the icon and open the directory tree until the
GOOSE ID is displayed.
2.5. Click the GOOSE ID to allow the GOOSE transmission properties work area to
become visible for editing.
2.6. Enter a unique name for the GOOSE transmission. In our example we will use
the name TX1. Once entered, and the configuration complete, the name TX1
will be assigned to the GOOSE message transmitted from this relay. Optionally,
you can also enter a unique name for the GOOSE control block.
2.7. The directory tree within the data set source work area can be expanded such
that digital and analog data values of different logical nodes can be accessed.
Sixty four of these data values can be dragged into the data settlements work
area to form the GOOSE message that will be transmitted.

4-38 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE USING THE IEC 61850 CONFIGURATOR

To build the content of the GOOSE transmission proceed as follows:

2.8. Within the dataset sources work area, open the directory tree of the IED labeled
“one” to expose the logical nodes.
2.9. To transmit the status of Virtual Input 1 which is contained within logical node
GGIO3, open the directory of logical node GGIO3 to view indication one.
2.10. Within indication one status bit sval will contain the status of Virtual Input 1.
Once visible, left-click and drag the status value (sVal) of indication one into the
data sets elements list.
2.11. Select Save and once saved, you will see a confirmation message appear on
the computer screen.
3. Configure relay 254’s GOOSE reception.
The next step is to export relay 228’s modified CID file to the computer such that the
structure of GOOSE message TX1 can be used to configure the structure of the
reception within relay 254. Within the 3 Series relays, the CID file settings are resident
in both the on-line and off-line memory area of the relay. The EnerVista 3 Series
Setup software modifies the CID file settings located in the off-line area while loading,
running the CID settings that were present at power-up. Only at power-up are the off-
line CID file settings loaded into the on-line memory area in order for them to take
effect. Given that the EnerVista 3 Series Setup software exports only the on-line CID
file, the power to relay 228 must first be cycled before the file can be exported.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-39


USING THE IEC 61850 CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

To export 228’s CID file to the computer perform the following steps after cycling
relay 228’s power:

3.1. From the Main Menu right-click relay 228 and select Export CID file.

3.2. Enter a name for the CID file that will be exported (in our example lab, we will
use the name 228_Lab_1), then select Save. Once saved, a confirmation
message appears on the computer screen.

4-40 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE USING THE IEC 61850 CONFIGURATOR

Relay 228’s GOOSE message TX1’s structure must be known by all relays receiving
this message. The structure of GOOSE TX1 is contained within relay 228’s CID file.
To load this structure into relay 254 proceed as follows:

3.3. From the main 3 Series menu, right-click relay 254 and select IEC61850 Device
Configurator, then select GOOSE Reception.
3.4. To load the structure of TX1 into relay 254, select ADD IED, then select the
name of the file containing relay 228’s CID file which, in our example, is
228_Lab_1.CID, then select Open.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-41


USING THE IEC 61850 CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

3.5. Relay 228’s GOOSE message appears as an icon. This process can be repeated
to load the structures of up to seven additional GOOSE messages into relay
254.

4-42 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE USING THE IEC 61850 CONFIGURATOR

3.6. Open the directory of relay 228’s GOOSE transmission until the status bit of
Virtual Input 1 (sVal) is displayed.
3.7. Click and drag the bit labeled status value (sVal) into the first data item location
of the reception as shown. This action maps the status of Ind 1 (sVal) which is
Virtual input 1 into the first remote input of relay 254.
3.8. If available, additional items from relay 228’s TX1 transmission, or other GOOSE
messages loaded into Relay 254, could be mapped into the remaining 31
locations within relay 254’s receive area. Select Save.

Once the CID file is modified, relay 254’s power must be cycled to load the new CID file
NOTE:

settings for the GOOSE message into the on-line area to take effect.
NOTE
4. Testing.
To test the operation, proceed as follows:

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-43


USING THE IEC 61850 CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

4.1. Open Virtual input commands on relay 228.

4.2. Open the Remote Input Status under Actual Values on Relay 254, and note
that when Virtual Input 1 of relay 228 is forced to a logic 1 or a logic 0, the
status of Remote Input 1 of relay 254 changes to the same state, proving that
the GOOSE transmission and reception were configured correctly.

4-44 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE USING THE IEC 61850 CONFIGURATOR

This completes the exercise.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-45


IEC61850 SERVER CHAPTER 4: 3 SERIES IEC61850 GOOSE

IEC61850 Server
The IEC 61850 Server reports data including the logical device, data sets, data control
block, logical nodes and their data attributes to the IEC 61850 Client, such as the Local
HMI, RTU or Gateway.
The following is a list of logical nodes and number of instances that are supported by 3
Series relays. For a complete description of logical nodes, see Appendix A: IEC 61850
Implementation Details.

L: System Logical Nodes Description ANSI 350 339 345


LPHD 1 Physical device information - Yes Yes Yes
LLN0 Logical node zero - Yes Yes Yes

P: Logical Nodes for protection Description ANSI 350 339 345


functions
phsPIOC Instantaneous Overcurrent 50P Yes(2) - Yes(2)
ndPIOC Instantaneous Neutral Overcurrent 50N Yes(2) Yes(1) Yes(2)
gndPIOC Instantaneous Ground Overcurrent 50G Yes(2) - Yes(2)
gndPIOC Ground Fault 50G - Yes(1) -
hsePIOC Instantaneous Sensitive Ground 50SG Yes(2) - Yes(2)
Overcurrent
ngseqPIOC Instantaneous Negative Sequence 50_2(46) Yes(1) - Yes(2)
Overcurrent
scPIOC Short Circuit 50P - Yes(1) -
phsPTOC Time Phase Overcurrent 51P Yes(1) Yes(1) Yes(2)
ndPTOC Time Neutral Overcurrent 51N Yes(1) Yes(1) Yes(2)
gndPTOC Time Ground Overcurrent 51G Yes(1) - Yes(2)
hsePTOC Time Sensitive Ground Overcurrent 51SG Yes(1) - Yes(2)
ngseqPTOC Time Negative Sequence Overcurrent 51_2(46) Yes(1) - Yes(2)
jamPTOC Mechanical Jam 51R - Yes(1) -
unbalPTOC Current Unbalance 46 - Yes(1) -
accelPTOC Acceleration 48 - Yes(1) -
ldincPTOC Load Increase - - Yes(1) -
PTUC Phase undecurrent 37 - Yes(1) -
PTOF Overfrequency 81O Yes(4) Yes(2) -
phsPTOV Phase Overvoltage 59P Yes(4) Yes(2) -
auxPTOV Auxiliary Overvoltage 59X Yes(1) - -
ndPTOV Neutral Overvoltage 59N Yes(4) - -
ngseqPTOV Negative Sequence Overvoltage 59_2 Yes(2) Yes(1) -
phsrevPTOV Phase Reversal Overvoltage 47 - Yes(1) -
phsPTUV Phase Undervoltage 27P Yes(4) Yes(2) -
auxPTUV Auxiliary Undervoltage 27X Yes(1) -
psseqPTUV Positive Sequence Undervoltage 27P_1 Yes(1) Yes(2) -
PTUF Underfrequency 81U Yes(4) Yes(2) -
PTTR Thermal O/L 49 Yes(1) Yes(1) Yes(1)
PDOP Directional Power 32 Yes(2) Yes(2) -
ndPDOP Wattmetric Ground Fault 32N Yes(2) - -
PMRI Restart Inhibit 66 - Yes(1) -

4-46 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE IEC61850 SERVER

P: Logical Nodes for protection Description ANSI 350 339 345


functions
PDUP UnderPower 37P - Yes(1) -
pcntPDIF Percent Differential 87T - - Yes(1)
instPDIF Instantaneous Differential 87T-50 - - Yes(1)
rgfPDIF Restricted Ground Fault RGF - - Yes(2)

R: Logical Nodes for protection Description ANSI 350 339 345


functions
ndRDIR Neutral Directional Overcurrent 67N Yes(1) Yes(1) -
gndRDIR Ground Directional Overcurrent 67G Yes(1) - -
hseRDIR Sensitive Ground Directional 67SG Yes(1) - -
Overcurrent
phsRDIR Phase Directional Overcurrent 67P Yes(1) - -
RREC Autorecloser 79 Yes(1) - -
rptRFLO Fault Report - Yes(1) Yes(1) Yes(1)
RBRF Breaker Failure 50BF Yes(1) Yes(1) Yes(2)
RSYN Synchrocheck 25 Yes(1) - -

G: Logical Nodes for generic Description ANSI 350 339 345


functions
GGIO1 Remote Outputs - Yes Yes Yes
GGIO2 Contact Inputs/Outputs - Yes Yes Yes
GGIO3 Virtual Inputs - Yes Yes Yes
GGIO4 Logic Elements - Yes Yes Yes
GGIO5 Remote Inputs - Yes Yes Yes
rtdGGIO6 RTD's - - Yes -
GGIO7 Analog Operands - Yes Yes Yes

M: Logical Nodes for metering Description ANSI 350 339 345


and measurement
MMXU1 Measurement - Yes Yes Yes
MMXU2 Measurement - - - Yes
MMXU3 Differential Current - - - Yes
MMXU4 Differential 2 Harmonic - - - Yes
MMXU5 Differential 5 Harmonic - - - Yes
MMXU6 Restraint Current - - - Yes
MSQI1 Sequence and Imbalance - Yes Yes Yes
MSQI2 Sequence and Imbalance - - - Yes
MMTR1 Metering (Energy) - Yes Yes -

X: Logical Nodes for switchgear Description ANSI 350 339 SR345


XCBR Circuit Breaker - Yes Yes Yes(2)

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-47


IEC61850 SERVER CHAPTER 4: 3 SERIES IEC61850 GOOSE

Functionality
CLIENT CONNECTIONS
The 3 Series relay supports up to three IEC61850 concurrent client connections.
LOGICAL DEVICES AND REPORTS
Supported buffered and un-buffered report, and the report triggers are shown in the
Supported Triggers list.
Supported Triggers
• Data-change
• Integrity
• General-interrogation
Supported buffered and un-buffered report option fields are shown in the Field list.
Field
• Sequence number
• Report time stamp
• Reason for inclusion
• Data set name
• Data-ref
• Buffer-overflow (Buffered reports only)
• Entry id (Buffered reports only)
• Conf- revision
Report control block configuration settings are modified from the IEC61850 advanced
configurator writing directly to a CID file.
The datasets for reports are fully configurable with CDCs from any Logical Node.

4-48 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE IEC61850 CONFIGURATOR

IEC61850 Configurator
The 3 Series relay supports the IEC 61850 protocol which is identified by order code
Communications option "3E".
The IEC 61850 Configurator is found in both the online and offline section of the EnerVista
3 Series Setup software for configuring both the online and offline 3 Series relay settings
files.

Online and offline setup


ONLINE SETTINGS FILE
Two options are available to configure the relay’s online settings file.
1. Configuration
– Configure the 3 Series relay (having order code option: IEC 61850) through the
Device Setup or Quick Connect screen.
– The IEC 61850 Configurator “tree” item is displayed after Maintenance.

– Launch the online IEC 61850 configurator screen, by double-clicking IEC61850


Configurator.
– Select the required settings from the different tabs in the configurator screen to
complete the IEC 61850 configuration.
2. Online right-click option
– Select any online relay and right-click the selected “tree” item. More options
become available for selection, as shown in the next examples.
Example of Additional Options
Export ICD file: The menu option generates a default ICD file with the respective order
code option and saves the file to the path the user has selected previously.

Read Device Settings: This menu option reads all settings from the relay by modbus
and TFTP, and creates a 3 Series relay file with extension *.sr3. The new *.sr3 file
consists of two sections: one containing all modbus settings, and another in which
IEC61850-related configuration is implemented.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-49


IEC61850 CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

Export CID file: This menu option gets the CID file from the relay by TFTP and creates a
3 Series relay file with extension *.CID.
When creating a CID file using a 3rd party ICT/SCL tool, ensure the following guidlines are
FASTPATH:

followed:

– The order code in the CID file must match the device order code if writing the CID
file directly into the relay (without using the Enervista software).
– The maximum allowed services must be equal or below the specified limits as in
ICD/CID.
– Configure Datasets only in "LLN0" logical node.
– Creating new LD, LN, and communication-AP settings is not recommended.

OFFLINE SETTINGS FILE


The Export ICD file menu option generates a default ICD file with the respective order code
option and saves the file to the path the user has selected previously.
The Export CID File menu option generates the CID file, extracting all 61850 configuration
from the *.sr3 file.

4-50 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE IEC61850 CONFIGURATOR

IEC 61850 Configurator Details


The IEC 61850 Configurator allows the user to edit all sections of the IEC61850 CID and ICD
file. Close the IEC 61850 session to perform other operations in the EnerVista 3 Series
Setup software.
The IEC 61850 configurator consists of five sections:
• ICD/CID
• Settings
• Reports
• GOOSE Reception
• GOOSE Transmission

ICD/CID The ICD/CID tab consists of the ICD Explorer window on the left. The ICD Explorer window
allows the user to navigate through the data model of the relay and change desired IEC
61850 parameters such as the Logical Device Name, MMS port, etc. which are displayed
on the right.

To Modify the Parameters


1. Select a parameter in the ICD Explorer window to open the Attributes window in the
right part of the screen.
2. In the Attributes window, double-click in the Value column of the table and enter the
new value for that parameter.
For example, from the Attributes window set the IED name, description, and
configuration version for the Logical Device, as shown in the preceding figure.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-51


IEC61850 CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

Settings The Settings tab consists of General Settings and DAI Settings.
1. General Settings
IED NameRange:
Up to 64 alphanumeric characters
The IED Name represents the MMS domain name (IEC 61850 logical device) where all
IEC/MMS logical nodes are located. Valid characters for these values are upper and
lowercase letters, numbers, and the underscore (_) character, and the first character
in the string must be a letter. This conforms to the IEC 61850 standard.
LDevice inst
Range: Up to 64 alphanumeric characters
The setting represents the MMS domain name (IEC 61850 logical device) where all IEC/
MMS logical nodes are located. Valid characters for these values are upper and
lowercase letters, numbers, and the underscore (_) character. The first character in the
string must be a letter. This conforms to the IEC 61850 standard.
2. DAI Settings
DAI settings contains these features for configuration: MMXU & MSQI logical nodes,
GGIO3 logical node, XCBR logical node.
MMXU & MSQI Logical nodes
Range: 1 to 100.000 %
The MMXU & MSQI deadband settings represent the deadband values used to
determine when to update the MMXU “mag” and “cVal” values from the associated
“instmag” and “instcVal” values. The “mag” and “cVal” values are used for the IEC
61850 buffered and unbuffered reports. The settings correspond to the associated
“db” data items in the CF functional constraint of the MMXU logical node, as per the
IEC 61850 standard. According to IEC 61850-7-3, the db value “shall represent the
percentage of difference between the maximum and minimum in units of 0.001%”.
Thus, it is important to know the maximum value for each MMXU measured quantity,
since this represents the 100.00% value for the deadband.
MIN/MAX VALUES FOR MMXU NODES
The equations to calculate minimum (min) and maximum (max) values in the MMXU
nodes are as follows:
Table 4-1: Calculate Min/Max MMXU Node Values
MMXU Node To Calculate
TotW Max (350)= (Phase CT Primary * 115 A ) * (Phase VT Ratio * BusVTRatio * 240 V)
TotVar *(scale W/kW/MW)
TotVA Max(339) = (Phase CT Primary * 115 A ) * (Phase VT Ratio * BusVTRatio * 240 V)
*(scale W/kW/MW)
Max(339 two speed) = (SpeedTwoPhase CT Primary * 115 A ) * (Phase VT Ratio
* BusVTRatio * 240 V) *scaleW/kW/MW

min = -max
TotPF max = 1
min = -1
Hz max = 80
min = 30
Hte max = 15
min = -15
PPV max = BusVTRatio * 240 V
min = 0
PhV max = BusVTRatio * 240 V
min = 0
A$phsA Max(350,345) = (Phase CT Primary * 115A)
A$phsB Max(339) = (Phase CT Primary * 115A)
A$phsC Max(339 two speed) = (SpeedTwoPhase CT Primary * 115 A)

min = 0

4-52 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE IEC61850 CONFIGURATOR

MMXU Node To Calculate


A$neut Max(350) = (Ground CT Primary * 115A)
Max(350 SG) = (SensitiveGround CT Primary * 115A)
Max(339) = (Ground CT Primary * 115A)
Max(339 SG) = (SensitiveGround CT Primary * 115A)
Max(339CBCT) = 15

min = 0
A$net Max(350,345) = (Phase CT Primary * 115A)
Max(339) = (Phase CT Primary * 115A)
Max(339 two speed) = (SpeedTwoPhase CT Primary * 115 A)

min = 0
A$res Max = (Ground CT Primary * 115A)
Max(SG) = (SensitiveGround CT Primary * 115A)
min = 0
AuxV max = AuxVTRatio * 240V
min = 0
SeqA$c1, c2 ,c3 Max(350,345) = (Phase CT Primary * 115A)
Max(339) = (Phase CT Primary * 115A)
Max(339 two speed) = (SpeedTwoPhase CT Primary * 115 A)

min = 0
SeqV$c1,c2,c3 max = (BusVTRatio * 240)
min = 0
dbAng angle dB = (DB percentage* 360)

GGIO3 Logical Node


Range: Enum
These are the control models supported: (0) status only, (1) direct-with-normal-
security.
XCBR Logical Node
Range: Enum for ctlModel and 500:60000ms for sboTimeout
The IEC61850 "operate" command must be executed after "select" command within
the XCBR1 pos sboTimeout setting value to be successful.
XCBR1 pos cltModel can be configured as (0)status only, (1) direct-with-nomal-
security, (2)sbo-with-normal-security, (3)direct-with-enhanced-security,(4)sbo-with-
enhanced-security
MMXU TotW, TotVar, TotVA
Range: none, k, M
The multiplier of the TotW, TotVar,TotVA can be modified to select the scale of the
values to be sent between none, kilo or Mega. (W,Var,VA).

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-53


IEC61850 CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

4-54 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 4: 3 SERIES IEC61850 GOOSE IEC61850 CONFIGURATOR

Reports The Reports tab in the IEC 61580 Configurator permits configuration of data sets and
report control blocks for buffered and unbuffered reports.

The screen helps the user to create, modify and delete Report Control Blocks (RCBs) and
Datasets. Each Report Control Block must have a maximum of 4 different clients up to a
maximum of 8 Report Control Blocks linked to their Datasets. Each dataset must have a
maximum of 64 elements in total.
There are two screens available in the Report tab window:
• Report control block: used to add the required report control block.
– RCB Name: The first character in the value of this attribute must be a letter (upper
or lower case). The rest of the characters must be a number, a letter (upper or
lower case) or a “_”. The maximum number of characters allowed in IEC61850
Configurator is 30 and IEC61850 MMS Library adds 2 more characters indicating
the number of the instance of the RCB depending on the number of IEC61850
clients configured.
– Description: The maximum number of characters allowed is 32.
• Dataset sources: Each report control block can be appended with dataset items in the
screen using a drag and drop operation.
The following buttons are available in the Reports window.
• “Add Report” button and “Remove Report” button: Both buttons are in the lower side of
the screen.
• Note that a Report control block can also be added by right clicking the LD entry under
the IED name in the "tree".
The “Remove Report” button deletes an existing Report control block.
Note that the Report can also be deleted by right clicking the configured existing
report.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 4-55


IEC61850 CONFIGURATOR CHAPTER 4: 3 SERIES IEC61850 GOOSE

Add/Remove Report Control Block


1. Click the “Add Report” button.
The button is available in the lower side of the screen and is used to add a report
control block. (a Report can also be added by right clicking the LD entry under the IED
name in the "tree" )
The “New Report Control Block” window appears.
2. In the “New Report Control Block” window under “Select Report Type”, select the radio
button for a buffered or unbuffered report.
3. In the “IEC61850 Clients N#” dropdown list, select 1 or any other available number.
4. Click the “Next” button to proceed with further configuration (else click “Cancel” to
discard the new configuration).
5. In the “Select DataSet” window, select the radio button for “New DataSet” or “Existing
DataSet”.
Report Properties
The report properties section can be viewed when any configured report is selected.
All the available parameters of the Report control block are displayed when clicking
“Report Advanced Configuration”. Respective OptFields, TrgOps can be configured by
either selecting “True” or “False”. Buffer time is given in milliseconds.
Configure Dataset Items
1. Select the required logical node under IED name> LD name relay “tree”.
2. Go to the required dataset item.
3. Drag and drop the item to the “DataSet Elements” section.
Maximum Report Control Blocks
The 3 Series relay supports a maximum of 8 report control blocks. Buffered and unbuffered
reports are both included in the maximum. The user can configure reports based on the
Report Configurations Supported table as follows.
Table 4-2: Report Configurations Supported
Buffered Report Unbuffered Report Total Reports
8 0 8
7 1 8
6 2 8
5 3 8
4 4 8
3 5 8
2 6 8
1 7 8

GOOSE reception and The GOOSE tabs in IEC61850 Configurator permits configuration of data set and GOOSE
GOOSE transmission control block for transmission and the subscription for the reception of gooses.
The use of this two tabs is described in the section Using the IEC 61850 configurator on
page 4-27.

4-56 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


GE
Grid Solutions

3 Series Protective Relay Platform

Chapter 5: 350 OPC–UA


Communication Standard

350 OPC–UA Communication Standard

This chapter describes the implementation process for the OPC-UA (OLE for Process
Control – Unified Architecture) in the 350 relay.
OPC-UA communication is available for the 350 relay only.
NOTE:

NOTE

Definitions and Acronyms


• OPC-UA – OLE for Process Control - Unified Architecture
• OLE – Object Linking and Embedding
• SOA – Service Oriented Architecture
• DA – Data Access
• AE – Alarms and Events
• SDK – Software Development Kit
• CTT – Compliance Test Tool

OPC–UA Architecture
The OPC communication is done through Client-Server architecture. In the case of the 350
relay, the relay is implemented as the Server.
The parts that are being supported are:
• OPC-UA DA
– Read and write actions of the data service. The data service deals with real-time
data, not historical data.
• OPC-UA AE
– Lecture events service.
• OPC-UA Methods
– Service commonly used for commands

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 5-1


OPC-UA SETTINGS CHAPTER 5: 350 OPC–UA COMMUNICATION STANDARD

OPC-UA Settings
OPCUA Enable
Range: Disabled, Enabled
Default: Disabled
The OPCUA Enable setting is only for a 350 relay with a communications Order Code 4.
In this case only, the OPC-UA and the IEC61850 protocol do not run simultaneously. If
IEC61850 is running by default but it is desired to use OPC-UA instead, the user must put
the OPCUA Enable setting to Enabled. Then, the relay must be rebooted. This will run the
OPC-UA instead of the IEC61850.
In the 350 relay with communications Order Code 5, this setting is not visible and both
protocols run simultaneously.

OPC–UA Server Configuration Data


The servers internal configuration data are the following:
• OPC-UA connection port is 4842
• Maximum number of sessions per server is 2
• The server has the following data types:
– Double - used for Analog Values
– Boolean - used for Digital, Logic, Input and Output data
• The server guarantees the reading of 60 nodes. If the number of nodes is bigger than
this value, the response time increases proportionally to the number of nodes.

5-2 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 5: 350 OPC–UA COMMUNICATION STANDARD OPC–UA POINT LISTS

OPC–UA Point Lists


• Modeling for the following:
Events
All digital signals available are defined as an event source. So, the Server connection is
declared as a unique event notifier.
Alarms
The alarms are not supported.
Commands
The Open&Close breaker and Reset commands have been implemented as Method
services.
• The OPC-UA server has implemented the following Analog, Digital, Input, Logic and
Command points, as shown in the tables.
Table 5-1: Analog points
Data Description
W Real Power
VAr Reactive Power
VA Apparent Power
PF Power Factor
Freq Frequency
Vab PhA to PhB Voltage
Vab_ang Va angle
Vbc PhB to Ph CVoltage
Vbc_ang Vb angle
Vca PhCtoPhAVoltage
Vca_ang Vc angle
Va_mag Va magnitude
Va_ang Va angle
Vb_mag Vb magnitude
Vb_ang Vb angle
Vc_mag Vc magnitude
Vc_ang V cangle
Vn_mag Vn magnitude
Vn_ang Vn angle
Ia_mag Ia magnitude
Ia_ang Ia angle
Ib_mag Ib magnitude
Ib_ang Ib angle
Ic_mag Ic magnitude
Ic_ang Ic angle
Ig_mag Ground magnitude
Ig_ang Ground angle
In_mag Neutral magnitude
In_ang Neutral angle
Is_mag Sensitive Ground magnitude
Is_ang Sensitive Ground angle
Vaux_mag Auxiliary Voltage magnitude

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 5-3


OPC–UA POINT LISTS CHAPTER 5: 350 OPC–UA COMMUNICATION STANDARD

Data Description
Vaux_ang Auxiliary Voltage angle
IseqPos_mag Positive Sequence Current magnitude
IseqPos_ang Positive Sequence Current angle
IseqNeg_mag Negative Sequence Current magnitude
IseqNeg_ang Negative Sequence Current angle
IseqZero_mag Zero Sequence Current magnitude
IseqZero_ang Zero Sequence Current angle
VseqPos_mag Positive Sequence Voltage magnitude
VseqPos_ang Positive Sequence Voltage angle
VseqNeg_mag Negative Sequence Voltage magnitude
VseqNeg_ang Negative Sequence Voltage angle
VseqZero_mag Zero Sequence Voltage magnitude
VseqZero_ang Zero Sequence Voltage angle
Power1_WGF 32N Wattmetric Power1
Power2_WGF 32N Wattmetric Power2
Power1_32DP Directional Power1
Power2_32DP Directional Power2
Ia_2ndHarmc 2nd Harmonic Ia
Ib_2ndHarmc 2nd Harmonic Ib
Ic_2ndHarmc 2nd Harmonic Ic
Therm_Cap_PhA Thermal Capacity PhA
Therm_Cap_PhB Thermal Capacity PhB
Therm_Cap_PhC Thermal Capacity PhC
Enrgy_Mvarh_Neg Mvarh Generation
Enrgy_MWh_Neg MWh Generation
Enrgy_Mvarh_Pos Mvarh Consumption
Enrgy_MWh_Pos MWh Consumption

Table 5-2: Digital points


Data Description
Data
PIOC_1_PKP Phase IOC1 PKP
PIOC_1_phA_PKP Phase A IOC1 PKP
PIOC_1_phB_PKP Phase B IOC1 PKP
PIOC_1_phC_PKP Phase C IOC1 PKP
PIOC_1_OP Phase IOC1 OP
PIOC_1_phA_OP Phase A IOC1 OP
PIOC_1_phB_OP Phase B IOC1 OP
PIOC_1_phC_OP Phase C IOC1 OP
PIOC_1_BLK Phase IOC1 BLK
PIOC_2_PKP Phase IOC2 PKP
PIOC_2_phA_PKP Phase A IOC2 PKP
PIOC_2_phB_PKP Phase B IOC2 PKP
PIOC_2_phC_PKP Phase C IOC2 PKP
PIOC_2_OP Phase IOC2 OP
PIOC_2_phA_OP Phase A IOC2 OP
PIOC_2_phB_OP Phase B IOC2 OP

5-4 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 5: 350 OPC–UA COMMUNICATION STANDARD OPC–UA POINT LISTS

Data Description
PIOC_2_phC_OP Phase C IOC2 OP
PIOC_2_BLK Phase IOC2 BLK
NIOC_1_PKP Neutral IOC1 PKP
NIOC_1_OP Neutral IOC1 OP
NIOC_1_BLK Neutral IOC1 BLK
NIOC_2_PKP Neutral IOC2 PKP
NIOC_2_OP Neutral IOC2 OP
NIOC_2_BLK Neutral IOC2 BLK
GIOC_1_PKP Ground IOC1 PKP
GIOC_1_OP Ground IOC1 OP
GIOC_1_BLK Ground IOC1 BLK
GIOC_2_PKP Ground IOC2 PKP
GIOC_2_OP Ground IOC2 OP
GIOC_2_BLK Ground IOC2 BLK
SGIOC_1_PKP Sensitive Ground IOC1 PKP
SGIOC_1_OP Sensitive Ground IOC1 OP
SGIOC_1_BLK Sensitive Ground IOC1 BLK
SGIOC_2_PKP Sensitive Ground IOC2 PKP
SGIOC_2_OP Sensitive Ground IOC2 OP
SGIOC_2_BLK Sensitive Ground IOC2 BLK
NegSeq_IOC_PKP Negative Sequence IOC PKP
NegSeq_IOC_OP Negative Sequence IOC OP
NegSeq_IOC_BLK Negative Sequence IOC BLK
PTOC_1_PKP Phase TOC1 PKP
PTOC_1_phA_PKP Phase A TOC1 PKP
PTOC_1_phB_PKP Phase B TOC1 PKP
PTOC_1_phC_PKP Phase C TOC1 PKP
PTOC_1_OP Phase TOC1 OP
PTOC_1_phA_OP Phase A TOC1 OP
PTOC_1_phB_OP Phase B TOC1 OP
PTOC_1_phC_OP Phase C TOC1 OP
PTOC_1_BLK Phase TOC1 BLK
NTOC_1_PKP Neutral TOC1 PKP
NTOC_1_OP Neutral TOC1 OP
NTOC_1_BLK Neutral TOC1 BLK
GTOC_1_PKP Ground TOC1 PKP
GTOC_1_OP Ground TOC1 OP
GTOC_1_BLK Ground TOC1 BLK
SGTOC_1_PKP Sensitive Ground TOC1 PKP
SGTOC_1_OP Sensitive Ground TOC1 OP
SGTOC_1_BLK Sensitive Ground TOC1 BLK
OF_1_PKP OverFrequency1 PKP
OF_1_OP OverFrequency1 OP
OF_1_BLK OverFrequency1 BLK
OF_2_PKP OverFrequency2 PKP
OF_2_OP OverFrequency2 OP
OF_2_BLK OverFrequency2 BLK

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 5-5


OPC–UA POINT LISTS CHAPTER 5: 350 OPC–UA COMMUNICATION STANDARD

Data Description
POV_PKP Phase OV PKP
POV_phA_PKP Phase A OV PKP
POV_phB_PKP Phase B OV PKP
POV_phC_PKP Phase C OV PKP
POV_OP Phase OV OP
POV_phA_OP Phase A OV OP
POV_phB_OP Phase B OV OP
POV_phC_OP Phase C OV OP
POV_BLK Phase OV BLK
AuxOV_PKP Auxiliary OV PKP
AuxOV_OP Auxiliary OV OP
AuxOV_BLK Auxiliary OV BLK
NOV_PKP Neutral OV PKP
NOV_OP Neutral OV OP
NOV_BLK Neutral OV BLK
NegSeqOV_PKP Negative Sequence OV PKP
NegSeqOV_OP Negative Sequence OV OP
NegSeqOV_BLK Negative Sequence OV BLK
PUV_PKP Phase UV PKP
PUV_phA_PKP Phase A UV PKP
PUV_phB_PKP Phase B UV PKP
PUV_phC_PKP Phase C UV PKP
PUV_OP Phase UV OP
PUV_phA_OP Phase A UV OP
PUV_phB_OP Phase B UV OP
PUV_phC_OP Phase C UV OP
PUV_BLK Phase UV BLK
AuxUV_PKP Auxiliary UV PKP
AuxUV_OP Auxiliary UV OP
AuxUV_BLK Auxiliary UV BLK
UF_1_PKP UnderFrequency1 PKP
UF_1_OP UnderFrequency1 OP
UF_1_BLK UnderFrequency1 BLK
UF_2_PKP UnderFrequency2 PKP
UF_2_OP UnderFrequency2 OP
UF_2_BLK UnderFrequency2 BLK
Therm_OP Thermal Model OP
Therm_BLK Therma lModel BLK
NDirOC_OP Ntrl Dir OC OP
NDirOC_BLK Ntrl Dir OC BLK
GDirOC_OP Ground Dir OC OP
GDirOC_BLK Ground Dir OC BLK
PDirOC_OP Phase Dir OC OP
PhADirOC_OP Phase A Dir OC OP
PhBDirOC_OP Phase B Dir OC OP
PhCDirOC_OP Phase C Dir OC OP
PDirOC_BLK Phase Dir OC BLK

5-6 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 5: 350 OPC–UA COMMUNICATION STANDARD OPC–UA POINT LISTS

Data Description
AR_Close_OP AR Close
AR_Disabled_OP AR Disabled
AR_ExtInit_OP AR Ext Init
AR_InProgress_OP AR In Progress
AR_Ready_OP AR Ready
WGF_1_PKP Wattmetric1 PKP
WGF_1_OP Wattmetric1 OP
WGF_1_BLK Wattmetric1 BLK
WGF_2_PKP Wattmetric2 PKP
WGF_2_OP Wattmetric2 OP
WGF_2_BLK Wattmetric2 BLK
DirPower32DP_1_PKP DirectionalPower1 PKP
DirPower32DP_1_OP DirectionalPower1 OP
DirPower32DP_1_BLK DirectionalPower1 BLK
DirPower32DP_2_PKP DirectionalPower2 PKP
DirPower32DP_2_OP DirectionalPower2 OP
DirPower32DP_2_BLK DirectionalPower2 BLK
HRMC_2nd_PKP Harmonic 2nd PKP
HRMC_2nd_OP Harmonic 2nd OP
BrokenCond46BC_PKP BrokenConductor 46BC PKP
BrokenCond46BC_OP BrokenConductor 46BC OP
BrokenCond46BC_BLK BrokenConducto r46BC BLK
CTFail_1_PKP CT Fail 2 BLK
CTFail_1_OP CT Fail 1 PKP
CTFail_1_BLK CT Fail 1 OP
PUV_2_PKP Phase A UV 2 PKP
PUV_2_phA_PKP Phase A UV 2 PKP
PUV_2_phB_PKP Phase B UV 2 PKP
PUV_2_phC_PKP Phase C UV 2 PKP
PUV_2_OP Phase A UV 2 OP
PUV_2_phA_OP Phase A UV 2 OP
PUV_2_phB_OP Phase B UV 2 OP
PUV_2_phC_OP Phase C UV 2 OP
PUV_2_BLK Phase UV 2 BLK
PUV_3_PKP Phase UV 3 PKP
PUV_3_phA_PKP Phase A UV 3 PKP
PUV_3_phB_PKP Phase B UV 3 PKP
PUV_3_phC_PKP Phase C UV 3 PKP
PUV_3_OP Phase UV 3 OP
PUV_3_phA_OP Phase A UV 3 OP
PUV_3_phB_OP Phase B UV 3 OP
PUV_3_phC_OP Phase C UV 3 OP
PUV_3_BLK Phase UV 3 BLK
PUV_4_PKP Phase UV 4 PKP
PUV_4_phA_PKP Phase A UV 4 PKP
PUV_4_phB_PKP Phase B UV 4 PKP
PUV_4_phC_PKP Phase C UV 4

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 5-7


OPC–UA POINT LISTS CHAPTER 5: 350 OPC–UA COMMUNICATION STANDARD

Data Description
PUV_4_OP Phase UV 4 OP
PUV_4_phA_OP Phase A UV 4 OP
PUV_4_phB_OP Phase B UV 4 OP
PUV_4_phC_OP Phase C UV 4 OP
PUV_4_BLK Phase UV 4 BLK
POV_2_PKP Phase OV 2 PKP
POV_2_phA_PKP Phase A OV 2 PKP
POV_2_phB_PKP Phase B OV 2 PKP
POV_2_phC_PKP Phase C OV 2 PKP
POV_2_OP Phase OV 2 OP
POV_2_phA_OP Phase A OV 2 OP
POV_2_phB_OP Phase B OV 2 OP
POV_2_phC_OP Phase C OV 2 OP
POV_2_BLK Phase OV 2 BLK
POV_3_PKP Phase OV 3 PKP
POV_3_phA_PKP Phase A OV 3 PKP
POV_3_phB_PKP Phase B OV 3 PKP
POV_3_phC_PKP Phase C OV 3 PKP
POV_3_OP Phase OV 3 OP
POV_3_phA_OP Phase A OV 3 OP
POV_3_phB_OP Phase B OV 3 OP
POV_3_phC_OP Phase C OV 3 OP
POV_3_BLK Phase OV 3 BLK
POV_4_PKP Phase OV 4 PKP
POV_4_phA_PKP Phase A OV 4 PKP
POV_4_phB_PKP Phase B OV 4 PKP
POV_4_phC_PKP Phase C OV 4 PKP
POV_4_OP Phase OV 4 OP
POV_4_phA_OP Phase A OV 4 OP
POV_4_phB_OP Phase B OV 4 OP
POV_4_phC_OP Phase C OV 4 OP
POV_4_BLK Phase OV 4 BLK
NOV_2_PKP Neutral OV 2 PKP
NOV_2_OP Neutral OV 2 OP
NOV_2_BLK Neutral OV 2 BLK
NOV_3_PKP Neutral OV 3 PKP
NOV_3_OP Neutral OV 3 OP
NOV_3_BLK Neutral OV 3 BLK
NOV_4_PKP Neutral OV 4 PKP
NOV_4_OP Neutral OV 4 OP
NOV_4_BLK Neutral OV 4 BLK
NegSeqOV_2_PKP Neg Seq OV 2 PKP
NegSeqOV_2_OP Neg Seq OV 2 OP
NegSeqOV_2_BLK Neg Seq OV 2 BLK
OF_3_PKP Over Frequency 3 PKP
OF_3_OP Over Frequency 3 OP
OF_3_BLK Over Frequency 3 BLK

5-8 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 5: 350 OPC–UA COMMUNICATION STANDARD OPC–UA POINT LISTS

Data Description
OF_4_PKP Over Frequency 4 PKP
OF_4_OP Over Frequency 4 OP
OF_4_BLK Over Frequency 4 BLK
UF_3_PKP Under Frequency 3 PKP
UF_3_OP Under Frequency 3 OP
UF_3_BLK Under Frequency 3 BLK
UF_4_PKP Under Frequency 4 PKP
UF_4_OP Under Frequency 4 OP
UF_4_BLK Under Frequency 4 BLK
FuseFail_PKP Fuse Fail PKP
FuseFail_OP Fuse Fail OP
PosSeq_UV_PKP Positive Sequence UV PKP
PosSeq_UV_OP Positive Sequence UV OP
PosSeq_UV_BLK Positive Sequence UV BLK
Synchk_OP Syncrocheck OP
Synchk_Close_OP Syncrocheck Close OP
Synchk_Cond_OP Syncrocheck Condition OP
CLP_PKP Cold Load Pickup PKP
CLP_OP Cold Load Pickup OP
VoltHertz_PKP Volt Hertz PKP
VoltHertz_OP Volt Hertz OP
VoltHertz_BLK Volt Hertz BLK

Table 5-3: Input points


Data Description
CI_1 Contact Input 1
CI_2 Contact Input 2
CI_3 Contact Input 3
CI_4 Contact Input 4
CI_5 Contact Input 5
CI_6 Contact Input 6
CI_7 Contact Input 7
CI_8 Contact Input 8
CI_9 Contact Input 9
CI_10 Contact Input 10
VI_1 Virtual Input 1
VI_2 Virtual Input 2
VI_3 Virtual Input 3
VI_4 Virtual Input 4
VI_5 Virtual Input 5
VI_6 Virtual Input 6
VI_7 Virtual Input 7
VI_8 Virtual Input 8
VI_9 Virtual Input 9
VI_10 Virtual Input 10
VI_11 Virtual Input 11
VI_12 Virtual Input 12

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 5-9


OPC–UA POINT LISTS CHAPTER 5: 350 OPC–UA COMMUNICATION STANDARD

Data Description
VI_13 Virtual Input 13
VI_14 Virtual Input 14
VI_15 Virtual Input 15
VI_16 Virtual Input 16
VI_17 Virtual Input 17
VI_18 Virtual Input 18
VI_19 Virtual Input 19
VI_20 Virtual Input 20
VI_21 Virtual Input 21
VI_22 Virtual Input 22
VI_23 Virtual Input 23
VI_24 Virtual Input 24
VI_25 Virtual Input 25
VI_26 Virtual Input 26
VI_27 Virtual Input 27
VI_28 Virtual Input 28
VI_29 Virtual Input 29
VI_30 Virtual Input 30
VI_31 Virtual Input 31
VI_32 Virtual Input 32
RI_1 Remote Input 1
RI_2 Remote Input 2
RI_3 Remote Input 3
RI_4 Remote Input 4
RI_5 Remote Input 5
RI_6 Remote Input 6
RI_7 Remote Input 7
RI_8 Remote Input 8
RI_9 Remote Input 9
RI_10 Remote Input 10
RI_11 Remote Input 11
RI_12 Remote Input 12
RI_13 Remote Input 13
RI_14 Remote Input 14
RI_15 Remote Input 15
RI_16 Remote Input 16
RI_17 Remote Input 17
RI_18 Remote Input 18
RI_19 Remote Input 19
RI_20 Remote Input 20
RI_21 Remote Input 21
RI_22 Remote Input 22
RI_23 Remote Input 23
RI_24 Remote Input 24
RI_25 Remote Input 25
RI_26 Remote Input 26
RI_27 Remote Input 27

5-10 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 5: 350 OPC–UA COMMUNICATION STANDARD OPC–UA POINT LISTS

Data Description
RI_28 Remote Input 28
RI_29 Remote Input 29
RI_30 Remote Input 30
RI_31 Remote Input 31
RI_32 Remote Input 32

Table 5-4: Output points


Data Description
RO_1 Remote Output 1
RO_2 Remote Output 2
RO_3 Remote Output 3
RO_4 Remote Output 4
RO_5 Remote Output 5
RO_6 Remote Output 6
RO_7 Remote Output 7
RO_8 Remote Output 8
RO_9 Remote Output 9
RO_10 Remote Output 10
RO_11 Remote Output 11
RO_12 Remote Output 12
RO_13 Remote Output 13
RO_14 Remote Output 14
RO_15 Remote Output 15
RO_16 Remote Output 16
RO_17 Remote Output 17
RO_18 Remote Output 18
RO_19 Remote Output 19
RO_20 Remote Output 20
RO_21 Remote Output 21
RO_22 Remote Output 22
RO_23 Remote Output 23
RO_24 Remote Output 24
RO_25 Remote Output 25
RO_26 Remote Output 26
RO_27 Remote Output 27
RO_28 Remote Output 28
RO_29 Remote Output 29
RO_30 Remote Output 30
RO_31 Remote Output 31
RO_32 Remote Output 32
CO_1 Contact Output 1
CO_2 Contact Output 2
CO_3 Contact Output 3
CO_4 Contact Output 4
CO_5 Contact Output 5
CO_6 Contact Output 6
CO_7 Contact Output 7

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 5-11


OPC–UA POINT LISTS CHAPTER 5: 350 OPC–UA COMMUNICATION STANDARD

Table 5-5: Logic points


Data Description
Logic_1 Logic Element 1
Logic_2 Logic Element 2
Logic_3 Logic Element 3
Logic_4 Logic Element 4
Logic_5 Logic Element 5
Logic_6 Logic Element 6
Logic_7 Logic Element 7
Logic_8 Logic Element 8
Logic_9 Logic Element 9
Logic_10 Logic Element 10
Logic_11 Logic Element 11
Logic_12 Logic Element 12
Logic_13 Logic Element 13
Logic_14 Logic Element 14
Logic_15 Logic Element 15
Logic_16 Logic Element 16

Table 5-6: Commands


Data Description
Reset Reset
Open Open
Close Close

5-12 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


GE
Grid Solutions

3 Series Protective Relay Platform

Chapter 6: USB interface

USB interface

The USB inferface supports only the Modbus protocol.


For information on using the USB port on the 3 Series relay, please refer to section 3 of the
appropriate 3 Series relay Instruction Manual.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 6-1


MODBUS PROTOCOL CHAPTER 6: USB INTERFACE

MODBUS Protocol
The 3 Series relay implements a subset of the Modicon Modbus RTU serial communication
standard. The Modbus protocol is hardware-independent. That is, the physical layer can be
any of a variety of standard hardware configurations. This includes USB, RS485, fibre
optics, etc. Modbus is a single master / multiple slave type of protocol suitable for a multi-
drop configuration.
The 3 Series relay is always a Modbus slave. It can not be programmed as a Modbus
master. Computers or PLCs are commonly programmed as masters.
Both monitoring and control are possible using read and write register commands. Other
commands are supported to provide additional functions.
The Modbus protocol has the following characteristics.
• Address: 1 to 254
• Supported Modbus function codes: 1H, 2H, 3H, 4H, 5H, 6H, 7H, 8H, 10H, 42H, 43H
For details see MODBUS Functions.

Data Frame Format and Data Rate


One data frame of an asynchronous transmission to or from a 3 Series relay typically
consists of 1 start bit, 8 data bits, and 1 stop bit. This produces a 10 bit data frame. This is
important for transmission through modems at high bit rates.
Modbus protocol can be implemented at any standard communication speed. The 3 Series
relay supports operation at 9600, 19200, 38400, 57600, and 115200 baud.
The USB interface will support only 115200 baud.
NOTE:

NOTE

Data Packet Format


A complete request/response sequence consists of the following bytes (transmitted as
separate data frames):
Master Request Transmission:
SLAVE ADDRESS: 1 byte
FUNCTION CODE: 1 byte
DATA: variable number of bytes depending on FUNCTION CODE
CRC: 2 bytes
Slave Response Transmission:
SLAVE ADDRESS: 1 byte
FUNCTION CODE: 1 byte
DATA: variable number of bytes depending on FUNCTION CODE
CRC: 2 bytes
SLAVE ADDRESS: This is the first byte of every transmission. This byte represents the user-
assigned address of the slave device that is to receive the message sent by the master.
Each slave device must be assigned a unique address and only the addressed slave will
respond to a transmission that starts with its address. In a master request transmission the
SLAVE ADDRESS represents the address of the slave to which the request is being sent. In a
slave response transmission the SLAVE ADDRESS represents the address of the slave that is
sending the response.
FUNCTION CODE: This is the second byte of every transmission. Modbus defines function
codes of 1 to 127.

6-2 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 6: USB INTERFACE MODBUS PROTOCOL

DATA: This will be a variable number of bytes depending on the FUNCTION CODE. This may
be Actual Values, Setpoints, or addresses sent by the master to the slave or by the slave to
the master.
CRC: This is a two byte error checking code.

Error Checking
The RTU version of Modbus includes a two byte CRC-16 (16 bit cyclic redundancy check)
with every transmission. The CRC-16 algorithm essentially treats the entire data stream
(data bits only; start, stop and parity ignored) as one continuous binary number. This
number is first shifted left 16 bits and then divided by a characteristic polynomial
(11000000000000101B). The 16 bit remainder of the division is appended to the end of the
transmission, MSByte first. The resulting message including CRC, when divided by the
same polynomial at the receiver will give a zero remainder if no transmission errors have
occurred.
If a 3 Series relay Modbus slave device receives a transmission in which an error is
indicated by the CRC-16 calculation, the slave device will not respond to the transmission.
A CRC-16 error indicates than one or more bytes of the transmission were received
incorrectly and thus the entire transmission should be ignored in order to avoid the 3 Series
relay performing any incorrect operation.
The CRC-16 calculation is an industry standard method used for error detection. An
algorithm is included here to assist programmers in situations where no standard CRC-16
calculation routines are available.

CRC-16 Algorithm
Once the following algorithm is complete, the working register “A” will contain the CRC
value to be transmitted. Note that this algorithm requires the characteristic polynomial to
be reverse bit ordered. The MSBit of the characteristic polynomial is dropped since it does
not affect the value of the remainder. The following symbols are used in the algorithm:
—>: data transfer
A: 16 bit working register
AL: low order byte of A
AH: high order byte of A
CRC: 16 bit CRC-16 value
i, j: loop counters
(+): logical exclusive or operator
Di: i-th data byte (i = 0 to N-1)
G: 16 bit characteristic polynomial = 1010000000000001 with MSbit dropped and bit order
reversed
shr(x): shift right (the LSbit of the low order byte of x shifts into a carry flag, a '0' is shifted
into the MSbit of the high order byte of x, all other bits shift right one location
The algorithm is:

1. FFFF hex —> A

2. 0 —> i

3. 0 —> j

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 6-3


MODBUS PROTOCOL CHAPTER 6: USB INTERFACE

4. Di (+) AL —> AL

5. j+1 —> j

6. shr(A)

7. is there a carry? No: go to 8. Yes: G (+) A —> A

8. is j = 8? No: go to 5. Yes: go to 9.

9. i+1 —> i

10. is i = N? No: go to 3. Yes: go to 11.

11. A —> CRC

Timing
Data packet synchronization is maintained by timing constraints. The receiving device
must measure the time between the reception of characters. If 3.5 character times elapse
without a new character or completion of the packet, then the communication link must
be reset (i.e. all slaves start listening for a new transmission from the master). Thus at
115200 baud a delay of greater than 3.5 x 1 / 115200 x 10 x = 0.3 ms will cause the
communication link to be reset.

3 Series supported functions


The following functions are supported by the 3 Series relay :
• FUNCTION CODE 03H - Read Setpoints
• FUNCTION CODE 04H - Read Actual Values
• FUNCTION CODE 05H - Execute Operation
• FUNCTION CODE 06H - Store Single Setpoint
• FUNCTION CODE 07H - Read Device Status
• FUNCTION CODE 08H - Loopback Test
• FUNCTION CODE 10H - Store Multiple Setpoints
Refer to section 6 of this guide for more details on MODBUS function codes.

6-4 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


GE
Grid Solutions

3 Series Protective Relay Platform

Chapter 7: 350 Time Protocols

350 Time Protocols

Time protocols are available for the 350 relay only.


NOTE:

NOTE

350 IEC 1588 Precision Time Protocol (PTP)


The 350 relay supports PTP V2 protocol. The present values of the PTP protocol are
displayed here.
PATH: Actual Values > A1 Status
The RTC Sync Source actual value is the time synchronizing source the relay is using at
present. Possible sources are: PTP Clock, IRIG-B, SNTP and Internal.

PATH: Actual Values > A1 Status > PTP


Grandmaster ID: GRAND MAS HI + GRAND MAS LO is the grandmaster Identity code
being received from the present PTP grandmaster, if any. When the relay is not using any
PTP grandmaster, this actual value is zero. The grandmaster Identity code is specified by
PTP to be globally unique, so one can always know which clock is grandmaster in system
with multiple grandmaster-capable clocks.

350 Real Time Clock


PATH: SETPOINTS > S1 RELAY SETUP > CLOCK
PTP FUNCTION
Range: Enabled, Disabled
Default: Disabled
When “Disabled” is selected for this setting, PTP is disabled on the port. The relay does
not generate, or listen to, PTP messages on the port.
PTP STRICT POWER PROFILE
Range: Enabled, Disabled
Default: Disabled
Power profile (IEEE Std C37.238™ 2011) requires that the relay selects as a grandmaster:

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 7-1


350 IEC 1588 PRECISION TIME PROTOCOL (PTP) CHAPTER 7: 350 TIME PROTOCOLS

• only power profile compliant clocks


• that the delivered time has a worst-case error of ±1 μs
• and, that the peer delay mechanism be implemented.
With the Strict Power Profile setting set to “Enabled”, the relay selects as the master only
clocks displaying the IEEE_C37_238 identification codes. It uses a port only when the
peer delay mechanism is operational. With the Strict Power Profile setting set to
“Disabled”, the relay uses clocks without the power profile identification when no power
profile clocks are present, and uses ports even if the peer delay mechanism is non-
operational. This setting applies to all of the relay’s PTP-capable ports.
PTP DOMAIN NUMBER
Range: 0 to 255
Default: 0
The setting is set to the domain number of the grandmaster-capable clock(s) to which
they can be synchronized. A network can support multiple time distribution domains,
each distinguished with a unique domain number. More commonly, there is a single
domain using the default domain number zero. The setting applies to all of the relay’s
PTP-capable ports.
PTP VLAN PRIORITY
Range: 0 to 7
Default: 4
The setting selects the value of the priority field in the 802.1Q VLAN tag in request
messages issued by the relay’s peer delay mechanism. In compliance with PP (Power
Profile) the default VLAN priority is 4, but it is recommended that in accordance with PTP
it be set to 7.
Depending on the characteristics of the device to which the relay is directly linked, VLAN
Priority may have no effect.
The setting applies to all of the relay’s PTP-capable ports.
PTP VLAN ID
Range: 0 to 4095
Default: 0
The setting selects the value of the ID field in the 802.1Q VLAN tag in request messages
issued by the relay’s peer delay mechanism. It is provided in compliance with PP (Power
Profile).
As these messages have a destination address that indicates they are not to be bridged,
their VLAN ID serves no function, and so may be left at its default value. Depending on
the characteristics of the device to which the relay is directly linked, VLAN ID may have
no effect.
The setting applies to all of the relay’s PTP-capable ports
PTP EPOCH
Range: UTC since 1995, UTC since 1900, UTC since 1970, TAI since 1970
Default: UTC since 1995
The setting selects the origin of the time scale.

7-2 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


GE
Grid Solutions

3 Series Protective Relay Platform

Chapter 8: MODBUS Functions

MODBUS Functions

Function Code 03H


Modbus implementation: Read Holding Registers
3 Series relay implementation: Read Setpoints
For the 3 Series relay implementation of Modbus, this function code can be used to read
any setpoints (“holding registers”). Holding registers are 16 bit (two byte) values
transmitted high order byte first. Thus all 3 Series relay Setpoints are sent as two bytes.
The maximum number of registers that can be read in one transmission is 125.
The slave response to this function code is the slave address, function code, a count of the
number of data bytes to follow, the data itself and the CRC. Each data item is sent as a two
byte number with the high order byte sent first.
For example, consider a request for slave 17 to respond with 3 registers starting at address
006B. For this example the register data in these addresses is as follows:

Address Data
006B 022B
006C 0000
006D 0064

The master/slave packets have the following format:


Table 8-1: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 03H
MASTER TRANSMISSION BYTES EXAMPLE DESCRIPTION
SLAVE ADDRESS 1 11 message for slave 17
FUNCTION CODE 1 03 read registers
DATA STARTING ADDRESS 2 00 6B data starting at 006B
NUMBER OF SETPOINTS 2 00 03 3 registers = 6 bytes
total
CRC 2 76 87 CRC error code

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 8-1


FUNCTION CODE 03H CHAPTER 8: MODBUS FUNCTIONS

SLAVE RESPONSE BYTES EXAMPLE DESCRIPTION


SLAVE ADDRESS 1 11 message from slave
17
FUNCTION CODE 1 03 read registers
BYTE COUNT 1 06 3 registers = 6 bytes
DATA 1 (see definition above) 2 02 2B value in address
006B
DATA 2 (see definition above) 2 00 00 value in address
006C
DATA 3 (see definition above) 2 00 64 value in address
006D
CRC 2 54 83 CRC error code

Query:
The query message specifies the starting register and quantity of registers to be read.
Registers are addressed starting at zero: registers 1 to 16 are addressed as 0 to 15.
Here is an example of a request to read registers 40172 to 40175 from slave device 254:

Field Name Hex


Slave Address FE
Function 03
Starting Address Hi 00
Starting Address Lo AB
No. of Points Hi 00
No. of Points Lo 04

Response:
The register data in the response message are packed as two bytes per register, with the
binary contents right justified within each byte. For each register, the first byte contains the
high order bits and the second contains the low order bits.
The response is returned when the data is completely assembled.

Field Name Hex


Slave Address FE
Function 03
Byte Count 08
Data Hi (Register 40172) 00
Data Lo (Register 40172) FE
Data Hi (Register 40173) 00
Data Lo (Register 40173) 04
Data Hi (Register 40174) 00
Data Lo (Register 40174) 00
Data Hi (Register 40175) 00
Data Lo (Register 40175) 00

The contents of register 40172 are shown as the two byte values of 00 FE hex, or254
decimal. The contents of registers 40173 to 40175 are 00 04, 00 00 and 00 00 hex, or 4, 0
and 0 decimal.

8-2 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 8: MODBUS FUNCTIONS FUNCTION CODE 04H

Function Code 04H


Modbus Implementation: Read Input Registers
3 Series relay implementation: Read Actual Values
For the 3 Series relay implementation of Modbus, this function code can be used to read
any actual values (“input registers”). Input registers are 16 bit (two byte) values transmitted
high order byte first. Thus all 3 Series relay Actual Values are sent as two bytes. The
maximum number of registers that can be read in one transmission is 125.
The slave response to this function code is the slave address, function code, a count of the
data bytes to follow, the data itself and the CRC. Each data item is sent as a two byte
number with the high order byte sent first.
For example, request slave 17 to respond with 1 register starting at address 0008. For this
example the value in this register (0008) is 0000.
Table 8-2: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 04H
MASTER TRANSMISSION BYTES EXAMPLE DESCRIPTION
SLAVE ADDRESS 1 11 message for slave 17
FUNCTION CODE 1 04 read registers
DATA STARTING ADDRESS 2 00 08 data starting at 0008
NUMBER OF ACTUAL VALUES 2 00 01 1 register = 2 bytes
CRC 2 B2 98 CRC error code

SLAVE RESPONSE BYTES EXAMPLE DESCRIPTION


SLAVE ADDRESS 1 11 message from slave
17
FUNCTION CODE 1 04 read registers
BYTE COUNT 1 02 1 register = 2 bytes
DATA (see definition above) 2 00 00 value in address
0008
CRC 2 78 F3 CRC error code

Query:
The query message specifies the starting register and quantity of registers to be read.
Registers are addressed starting at zero: registers 1 to 16 are addressed as 0 to 15.
Here is an example of a request to read register 30305 from slave device 254:

Field Name Hex


Slave Address FE
Function 04
Starting Address Hi 01
Starting Address Lo 30
No. of Points Hi 00
No. of Points Lo 01

Response:
The register data in the response message are packed as two bytes per register, with the
binary contents right justified within each byte. For each register, the first byte contains the
high order bits and the second contains the low order bits.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 8-3


FUNCTION CODE 05H CHAPTER 8: MODBUS FUNCTIONS

Field Name Hex


Slave Address FE
Function 04
Byte Count 02
Data Hi (Register 30305) 80
Data Lo (Register 30305) 80

Function Code 05H


Modbus Implementation: Force Single Coil
3 Series relay Implementation: Execute Operation
This function code allows the master to request a 3 Series relay to perform specific
command operations.
For example, to request slave 17 to execute operation code 1 (reset), we have the following
master/slave packet format:
Table 8-3: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 05H
MASTER TRANSMISSION BYTES EXAMPLE DESCRIPTION
SLAVE ADDRESS 1 11 message for slave 17
FUNCTION CODE 1 05 execute operation
OPERATION CODE 2 00 01 operation code 1
CODE VALUE 2 FF 00 perform function
CRC 2 DF 6A CRC error code

SLAVE RESPONSE BYTES EXAMPLE DESCRIPTION


SLAVE ADDRESS 1 11 message from slave
17
FUNCTION CODE 1 05 execute operation
OPERATION CODE 2 00 01 operation code 1
CODE VALUE 2 FF 00 perform function
CRC 2 DF 6A CRC error code

Forces a single coil (0X reference) to either ON or OFF.


The query message specifies the coil reference to be forced. Coils are addressed starting at
zero: coil 1 is addressed as 0.
The requested ON/OFF state is specified by a constant in the query data field.
A value of FF 00 hex requests the coil to be ON. A value of 00 00 requests it to be OFF. All
other values are illegal and will not affect the coil.
Force Virtual Inputs:

Description Coil Address (HEX) Description Coil Address (HEX)

Virtual Input 1 0x1000 Virtual Input 17 0x1010


Virtual Input 2 0x1001 Virtual Input 18 0x1011
Virtual Input 3 0x1002 Virtual Input 19 0x1012
Virtual Input 4 0x1003 Virtual Input 20 0x1013
Virtual Input 5 0x1004 Virtual Input 21 0x1014

8-4 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 8: MODBUS FUNCTIONS FUNCTION CODE 05H

Description Coil Address (HEX) Description Coil Address (HEX)


Virtual Input 6 0x1005 Virtual Input 22 0x1015
Virtual Input 7 0x1006 Virtual Input 23 0x1016
Virtual Input 8 0x1007 Virtual Input 24 0x1017
Virtual Input 9 0x1008 Virtual Input 25 0x1018
Virtual Input 10 0x1009 Virtual Input 26 0x1019
Virtual Input 11 0x100A Virtual Input 27 0x101A
Virtual Input 12 0x100B Virtual Input 28 0x101B
Virtual Input 13 0x100C Virtual Input 29 0x101C
Virtual Input 14 0x100D Virtual Input 30 0x101D
Virtual Input 15 0x100E Virtual Input 31 0x101E
Virtual Input 16 0x100F Virtual Input 32 0x101F

Commands are different for each 3 Series relay:


339 Commands:

Description Coil Address (DEC)


Reset 1
Lockout Reset 2
Open 4
Close 5
Validate RMIO 12
Emergency Restart 13
Clear Last Trip Data Prompt 96
Reset MWh and Mvarh Meters 97
Clear Trip Counters 99
Clear Event Records 100
Clear Waveform Data 101
Clear Data Logger 103
Clear Learned Data 106
Trigger Waveform Capture 120
Start Data Log 121
Stop Data Log 122
Clear Security Log 126
Simulate Key Press - Nav Up Key 142
Simulate Key Press - Nav Left Key 143
Simulate Key Press - Nav Down Key 144
Simulate Key Press - Nav Right Key 145
Simulate Key Press - Up Key 146
Simulate Key Press - Down Key 147
Simulate Key Press - Enter Key 148
Simulate Key Press - Menu Key 149
Simulate Key Press - Escape Key 150
Simulate Key Press - Reset Key 151
Reload Factory Setpoints 2 161
Reload Factory Setpoints 1 162
Motor Data Logger Clear 182

345 Commands:

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 8-5


FUNCTION CODE 05H CHAPTER 8: MODBUS FUNCTIONS

Description Coil Address (DEC)


Reset 1
Activate Group 1 7
Activate Group 2 8
Active Group 11
Clear Event Records 100
Clear Waveform Data 101
Clear Maintenance Timer 102
Clear Thermal Image 105
Trigger Waveform Capture 120
Force Virtual Input 1 State 4096
Force Virtual Input 2 State 4097
Force Virtual Input 3 State 4098
Force Virtual Input 4 State 4099
Force Virtual Input 5 State 4100
Force Virtual Input 6 State 4101
Force Virtual Input 7 State 4102
Force Virtual Input 8 State 4103
Force Virtual Input 9 State 4104
Force Virtual Input 10 State 4105
Force Virtual Input 11 State 4106
Force Virtual Input 12 State 4107
Force Virtual Input 13 State 4108
Force Virtual Input 14 State 4109
Force Virtual Input 15 State 4110
Force Virtual Input 16 State 4111
Force Virtual Input 17 State 4112
Force Virtual Input 18 State 4113
Force Virtual Input 19 State 4114
Force Virtual Input 20 State 4115
Force Virtual Input 21 State 4116
Force Virtual Input 22 State 4117
Force Virtual Input 23 State 4118
Force Virtual Input 24 State 4119
Force Virtual Input 25 State 4120
Force Virtual Input 26 State 4121
Force Virtual Input 27 State 4122
Force Virtual Input 28 State 4123
Force Virtual Input 29 State 4124
Force Virtual Input 30 State 4125
Force Virtual Input 31 State 4126
Force Virtual Input 32 State 4127

350 Commands:

8-6 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 8: MODBUS FUNCTIONS FUNCTION CODE 05H

Description Coil Address (DEC)


Reset 1
Open 4
Close 5
Activate Group 1 7
Activate Group 2 8
Active Group 11
Reset MWh and Mvarh Meters 97
Clear Trip Counters 99
Clear Event Records 100
Clear Waveform Data 101
Clear Maintenance Timer 102
Clear Thermal Image 105
Trigger Waveform Capture 120
Force Virtual Input 1 State 4096
Force Virtual Input 2 State 4097
Force Virtual Input 3 State 4098
Force Virtual Input 4 State 4099
Force Virtual Input 5 State 4100
Force Virtual Input 6 State 4101
Force Virtual Input 7 State 4102
Force Virtual Input 8 State 4103
Force Virtual Input 9 State 4104
Force Virtual Input 10 State 4105
Force Virtual Input 11 State 4106
Force Virtual Input 12 State 4107
Force Virtual Input 13 State 4108
Force Virtual Input 14 State 4109
Force Virtual Input 15 State 4110
Force Virtual Input 16 State 4111
Force Virtual Input 17 State 4112
Force Virtual Input 18 State 4113
Force Virtual Input 19 State 4114
Force Virtual Input 20 State 4115
Force Virtual Input 21 State 4116
Force Virtual Input 22 State 4117
Force Virtual Input 23 State 4118
Force Virtual Input 24 State 4119
Force Virtual Input 25 State 4120
Force Virtual Input 26 State 4121
Force Virtual Input 27 State 4122
Force Virtual Input 28 State 4123
Force Virtual Input 29 State 4124
Force Virtual Input 30 State 4125
Force Virtual Input 31 State 4126
Force Virtual Input 32 State 4127

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 8-7


FUNCTION CODE 05H CHAPTER 8: MODBUS FUNCTIONS

Query:
Here is an example of a request to force Virtual Input1 to ON in slave device 254:

Field Name Hex


Slave Address FE
Function 05
Coil Address Hi 10
Coil Address Lo 00
Force Data Hi FF
Force Data Lo 00

Response:
The normal response is an echo of the query, returned after the coil state has been forced.

Field Name Hex


Slave Address FE
Function 05
Coil Address Hi 10
Coil Address Lo 00
Force Data Hi FF
Force Data Lo 00

8-8 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 8: MODBUS FUNCTIONS FUNCTION CODE 06H

Function Code 06H


Modbus Implementation: Preset Single Register
3 Series relay Implementation: Store Single Setpoint
This command allows the master to store a single setpoint into the memory of a 3 Series
relay. The slave response to this function code is to echo the entire master transmission.
For example, request slave 17 to store the value 2 in setpoint address 04 5C. After the
transmission in this example is complete, setpoints address 04 5C will contain the value
0002. The master/slave packet format is shown below:
Table 8-4: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 06H
MASTER TRANSMISSION BYTES EXAMPLE DESCRIPTION
SLAVE ADDRESS 1 11 message for slave 17
FUNCTION CODE 1 06 store single setpoint
DATA STARTING ADDRESS 2 04 5C setpoint address 04
5C
DATA 2 00 02 data for setpoint
address 04 5C
CRC 2 CB B9 CRC error code

SLAVE RESPONSE BYTES EXAMPLE DESCRIPTION


SLAVE ADDRESS 1 11 message from slave
17
FUNCTION CODE 1 06 store single setpoint
DATA STARTING ADDRESS 2 04 5C setpoint address 04
5C
DATA 2 00 02 data stored in
setpoint address 04
5C
CRC 2 CB B9 CRC error code

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 8-9


FUNCTION CODE 07H CHAPTER 8: MODBUS FUNCTIONS

Function Code 07H


Modbus Implementation: Read Exception Status
3 Series relay Implementation: Read Device Status
This is a function used to quickly read the status of a selected device. A short message
length allows for rapid reading of status. The status byte returned will have individual bits
set to 1 or 0 depending on the status of the slave device. For this example, consider the
following 3 Series relay general status byte:
The master/slave packets have the following format:
Table 8-5: Function code 7 bitmask
Bit Function
0 Alarm
1 Trip
2 Self Test
3 Breaker Connected
4 52a Contact
5 52b Contact
6 Maintenance
7 Relay in Service

Table 8-6: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 07H


MASTER TRANSMISSION BYTES EXAMPLE DESCRIPTION
SLAVE ADDRESS 1 11 message for slave 17
FUNCTION CODE 1 07 read device status
CRC 2 4C 22 CRC error code

SLAVE RESPONSE BYTES EXAMPLE DESCRIPTION


SLAVE ADDRESS 1 11 message from slave
17
FUNCTION CODE 1 07 read device status
DEVICE STATUS (see definition 1 2C status = 00101100 (in
above) binary)
CRC 2 22 28 CRC error code

Query:

Field Name Hex


Slave Address FE
Function 07

Response:

Field Name Hex


Slave Address FE
Function 07
Device Status (see definition above) 2C

8-10 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 8: MODBUS FUNCTIONS FUNCTION CODE 08H

Function Code 08H


Modbus Implementation: Loopback
Test 3 Series relay Implementation: Loopback Test
This function is used to test the integrity of the communication link. The 3 Series relay will
echo the request.
For example, consider a loopback test from slave 17:
Table 8-7: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 08H
MASTER TRANSMISSION BYTES EXAMPLE DESCRIPTION
SLAVE ADDRESS 1 11 message for slave 17
FUNCTION CODE 1 08 loopback test
DIAG CODE 2 00 00 must be 00 00
DATA 2 00 00 must be 00 00
CRC 2 E0 0B CRC error code

SLAVE RESPONSE BYTES EXAMPLE DESCRIPTION


SLAVE ADDRESS 1 11 message from slave
17
FUNCTION CODE 1 08 loopback test
DIAG CODE 2 00 00 must be 00 00
DATA 2 00 00 must be 00 00
CRC 2 E0 0B CRC error code

Function Code 10H


Modbus Implementation: Preset Multiple Registers
3 Series relay Implementation: Store Multiple Setpoints
This function code allows multiple Setpoints to be stored into the 3 Series relay memory.
Modbus “registers” are 16-bit (two byte) values transmitted high order byte first. Thus all 3
Series relay setpoints are sent as two bytes. The maximum number of Setpoints that can
be stored in one transmission is dependent on the slave device. Modbus allows up to a
maximum of 60 holding registers to be stored. The 3 Series relay response to this function
code is to echo the slave address, function code, starting address, the number of Setpoints
stored, and the CRC.
For example, consider a request for slave 17 to store the value 00 02 to setpoint address 04
5C and the value 01 F4 to setpoint address 04 5D. After the transmission in this example is
complete, 3 Series relay slave 17 will have the following setpoints information stored:

Address Data
04 5C 00 02
04 5D 01 F4

The master/slave packets have the following format:

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 8-11


FUNCTION CODE 10H CHAPTER 8: MODBUS FUNCTIONS

Table 8-8: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 10H


MASTER TRANSMISSION BYTES EXAMPLE DESCRIPTION
SLAVE ADDRESS 1 11 message for slave 17
FUNCTION CODE 1 10 store setpoints
DATA STARTING ADDRESS 2 04 5C setpoint address 04
5C
NUMBER OF SETPOINTS 2 00 02 2 setpoints = 4 bytes
total
BYTE COUNT 1 04 4 bytes of data
DATA 1 2 00 02 data for setpoint
address 04 5C
DATA 2 2 01 F4 data for setpoint
address 04 5D
CRC 2 31 11 CRC error code

SLAVE RESPONSE BYTES EXAMPLE DESCRIPTION


SLAVE ADDRESS 1 11 message from slave
17
FUNCTION CODE 1 10 store setpoints
DATA STARTING ADDRESS 2 04 5C setpoint address 04
5C
NUMBER OF SETPOINTS 2 00 02 2 setpoints
CRC 2 82 7A CRC error code

Query:
The query message specifies the register references to be preset. Registers are addressed
starting at zero: register 1 is addressed as 0.
The requested preset values are specified in the query data field. Data is packed as two
bytes per register.
Here is an example of a request to preset two registers starting at 43851 to 00 01 and 00
00 hex, in slave device 254:

Field Name Hex


Slave Address FE
Function 10
Starting Address Hi 0F
Starting Address Lo 0A
No. of Registers Hi 00
No. of Registers Lo 02
Byte Count 04 04
Data Hi 00
Data Lo 01
Data Hi 00
Data Lo 00

Response:
The normal response returns the slave address, function code, starting address, and
quantity of registers preset.

8-12 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 8: MODBUS FUNCTIONS FUNCTION CODE 10H

Field Name Hex


Slave Address FE
Function 10
Starting Address Hi 0F
Starting Address Lo 0A
No. of Registers Hi 00
No. of Registers Lo 02

Performing Commands Using Function Code 10H


Commands can be performed using function code 16 (10H) as well as function code 5.
When using FUNCTION CODE 16, the Command Function register must be written with a
value of 5. The Command Operation register must be written with a valid command
operation number. The Command Data registers must be written with valid data; this is
dependent upon the command operation.
For example, consider a request for slave 17 to perform command operation 1 (RESET): The
master/slave packets have the following format:
Table 8-9: MASTER/SLAVE PACKET FORMAT FOR PERFORMING COMMANDS
MASTER TRANSMISSION BYTES EXAMPLE DESCRIPTION
SLAVE ADDRESS 1 11 message for slave 17
FUNCTION CODE 1 10 store multiple
setpoints
DATA STARTING ADDRESS 2 00 80 setpoint address 00
80
NUMBER OF SETPOINTS 2 00 02 2 setpoints = 4 bytes
total
BYTE COUNT 1 04 4 bytes of data
DATA 1 2 00 05 data for address 00
80
DATA 2 2 00 01 data for address 00
81
CRC 2 7E CE CRC error code

SLAVE RESPONSE BYTES EXAMPLE DESCRIPTION


SLAVE ADDRESS 1 11 message from slave
17
FUNCTION CODE 1 10 store multiple
setpoints
DATA STARTING ADDRESS 2 00 80 setpoint address 00
80
NUMBER OF SETPOINTS 2 00 02 2 setpoints
CRC 2 42 B0 CRC error code

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 8-13


FUNCTION CODE 42H CHAPTER 8: MODBUS FUNCTIONS

Function Code 42H


Modbus Implementation: (not a standard function)
3 Series relay Implementation: Read Settings Group
All protection functions for the 345 and 350 relays have two sets of settings - Group 1 and
Group 2. This function number is used to read the settings for each group. (This function
does not apply to the 339 relay.)
Example:

Field Name Hex


Slave Address FE
Function 42
Group Activation 00
Starting Address Hi 0A
Starting Address Lo B3
No. of Registers Hi 00
No. of Registers Lo 01

Response:

Field Name Hex

Slave Address FE
Function 42
Byte Count 02
Data Hi 00
Data Lo 00

8-14 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 8: MODBUS FUNCTIONS FUNCTION CODE 43H

Function Code 43H


Modbus Implementation: (not a standard function)
3 Series relay Implementation: Write Settings Group
All protection functions for the 345 and 350 relays have two sets of settings - Group 1 and
Group 2. This function is used to write settings in a specific settings group. (This function
does not apply to the 339 relay.)
Example: (In the example there is a write setting procedure in the Group 1 (00), setting
address 0x09C1 and 2 bytes of data with value 0x0001.)

Field Name Hex


Slave Address FE
Function 43
Group Activation 00
Starting Address Hi 09
Starting Address Lo C1
No. of Registers Hi 00
No. of Registers Lo 01
Byte Count 04 02
Data Hi 00
Data Lo 01

Response:

Field Name Hex


Slave Address FE
Function 43
Starting Address Hi 09
Starting Address Lo C1
No. of Registers Hi 00
No. of Registers Lo 01

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 8-15


ERROR RESPONSES CHAPTER 8: MODBUS FUNCTIONS

Error Responses
When a 3 Series relay detects an error other than a CRC error, a response will be sent to the
master. The MSBit of the FUNCTION CODE byte will be set to 1 (i.e. the function code sent
from the slave will be equal to the function code sent from the master plus 128). The
following byte will be an exception code indicating the type of error that occurred.
Transmissions received from the master with CRC errors will be ignored by the 3 Series
relay.
The slave response to an error (other than CRC error) will be:
SLAVE ADDRESS: 1 byte
FUNCTION CODE: 1 byte (with MSbit set to 1)
EXCEPTION CODE: 1 byte
CRC: 2 bytes
The 3 Series relay implements the following exception response codes:
01 - ILLEGAL FUNCTION
The function code transmitted is not one of the functions supported by the 3 Series
relay.
02 - ILLEGAL DATA ADDRESS
The address referenced in the data field transmitted by the master is not an allowable
address for the 3 Series relay.
03 - ILLEGAL DATA VALUE
The value referenced in the data field transmitted by the master is not within range for
the selected data address.

8-16 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


GE
Grid Solutions

3 Series Protective Relay Platform

Chapter 9: Using the MODBUS User


Map

Using the MODBUS User Map

3 Series relay units incorporate a powerful feature called Modbus User Map, that allows
the user to read 125 non-consecutive data records.
A master computer will often have to interrogate continuously several connected slave
relays. If the values being read are "randomly" positioned along the memory map, reading
them may require several transmissions, and this may cause a communications overload.
Data records that are positioned in this manner in the memory map, can be remapped to
the address of an adjacent record in the User Map area, so that they can be accessible to
the master computer with only a single read operation.
To program the map this way, addresses for the required records must be written in the
index area, which is located at the addresses from 40524 (0x020B) to 40648 (0x287).
Only single data from the Actual Values subset can be set in the map. The ranges of
addresses that can be configured in that index area are:
Range1 : 30001 to 30523 (Product Device Code to Internal Fault Cause)
[The address 30302 (Current Security Access Level) cannot be configured.]
Range2 : 30946 to 32036 (Alarm Status 4 to Last Actual Values Register)
The values that correspond to the points provisioned in the User Map index (40524
(0x020B) to 40648 (0x287)) may be read from the Actual Values map area located at the
addresses from 30524 (0x020B) to 30648 (0x0287).

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 9-1


MODBUS USER MAP CHAPTER 9: USING THE MODBUS USER MAP

MODBUS User Map


Table 9-1: User Map Settings
MODBUS Hex Description Min Max Step Format 339 Factory 345 Factory 350 Factory
Address Addr. Code Default Default Default
40524 20B User Map Address 1 30001 43763 1 F1 30305 Device 30305 Device 30305 Device
Status Status Status
40525 20C User Map Address 2 30001 43763 1 F1 30505 LED Status 30505 LED Status 30505 LED Status
40526 20D User Map Address 3 30001 43763 1 F1 30506 LED Status 30506 LED Status 30506 LED Status
40527 20E User Map Address 4 30001 43763 1 F1 30960 Trip Status 1 30960 Trip Status 1 30960 Trip Status 1
40528 20F User Map Address 5 30001 43763 1 F1 30961 Trip Status 1 30961 Trip Status 1 30961 Trip Status 1
40529 210 User Map Address 6 30001 43763 1 F1 30958 Trip Status 2 30958 Trip Status 2 30958 Trip Status 2
40530 211 User Map Address 7 30001 43763 1 F1 30959 Trip Status 2 30959 Trip Status 2 30959 Trip Status 2
40531 212 User Map Address 8 30001 43763 1 F1 30956 Trip Status 3 30956 Trip Status 3 30956 Trip Status 3
40532 213 User Map Address 9 30001 43763 1 F1 30957 Trip Status 3 30957 Trip Status 3 30957 Trip Status 3
40533 214 User Map Address 10 30001 43763 1 F1 30954 Trip Status 4 30954 Trip Status 4 30954 Trip Status 4
40534 215 User Map Address 11 30001 43763 1 F1 30955 Trip Status 4 30955 Trip Status 4 30955 Trip Status 4
40535 216 User Map Address 12 30001 43763 1 F1 30952 Alarm 30952 Alarm 30952 Alarm
Status 1 Status 1 Status 1
40536 217 User Map Address 13 30001 43763 1 F1 30953 Alarm 30953 Alarm 30953 Alarm
Status 1 Status 1 Status 1
40537 218 User Map Address 14 30001 43763 1 F1 30950 Alarm 30950 Alarm 30950 Alarm
Status 2 Status 2 Status 2
40538 219 User Map Address 15 30001 43763 1 F1 30951 Alarm 30951 Alarm 30951 Alarm
Status 2 Status 2 Status 2
40539 21A User Map Address 16 30001 43763 1 F1 30948 Alarm 30948 Alarm 30948 Alarm
Status 3 Status 3 Status 3
40540 21B User Map Address 17 30001 43763 1 F1 30949 Alarm 30949 Alarm 30949 Alarm
Status 3 Status 3 Status 3
40541 21C User Map Address 18 30001 43763 1 F1 30946 Alarm 30946 Alarm 30946 Alarm
Status 4 Status 4 Status 4
40542 21D User Map Address 19 30001 43763 1 F1 30947 Alarm 30947 Alarm 30947 Alarm
Status 4 Status 4 Status 4
40543 21E User Map Address 20 30001 43763 1 F1 30976 Cntrl 30976 Cntrl 30976 Cntrl
Element Status 1 Element Status 1 Element Status 1
40544 21F User Map Address 21 30001 43763 1 F1 30977 Cntrl 30977 Cntrl 30977 Cntrl
Element Status 1 Element Status 1 Element Status 1
40545 220 User Map Address 22 30001 43763 1 F1 30974 Cntrl 30974 Cntrl 30974 Cntrl
Element Status 2 Element Status 2 Element Status 2
40546 221 User Map Address 23 30001 43763 1 F1 30975 Cntrl 30975 Cntrl 30975 Cntrl
Element Status 2 Element Status 2 Element Status 2
40547 222 User Map Address 24 30001 43763 1 F1 30972 Cntrl 30972 Cntrl 30972 Cntrl
Element Status 3 Element Status 3 Element Status 3
40548 223 User Map Address 25 30001 43763 1 F1 30973 Cntrl 30973 Cntrl 30973 Cntrl
Element Status 3 Element Status 3 Element Status 3
40549 224 User Map Address 26 30001 43763 1 F1 30970 Cntrl 30970 Cntrl 30970 Cntrl
Element Status 4 Element Status 4 Element Status 4
40550 225 User Map Address 27 30001 43763 1 F1 30971 Cntrl 30971 Cntrl 30971 Cntrl
Element Status 4 Element Status 4 Element Status 4
40551 226 User Map Address 28 30001 43763 1 F1 30984 Block Status 30984 Block Status 30984 Block Status
1 1 1
40552 227 User Map Address 29 30001 43763 1 F1 30985 Block Status 30985 Block Status 30985 Block Status
1 1 1

9-2 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 9: USING THE MODBUS USER MAP MODBUS USER MAP

MODBUS Hex Description Min Max Step Format 339 Factory 345 Factory 350 Factory
Address Addr. Code Default Default Default
40553 228 User Map Address 30 30001 43763 1 F1 30982 Block Status 30982 Block Status 30982 Block Status
2 2 2
40554 229 User Map Address 31 30001 43763 1 F1 30983 Block Status 30983 Block Status 30983 Block Status
2 2 2
40555 22A User Map Address 32 30001 43763 1 F1 30980 Block Status 30980 Block Status 30980 Block Status
3 3 3
40556 22B User Map Address 33 30001 43763 1 F1 30981 Block Status 30981 Block Status 30981 Block Status
3 3 3
40557 22C User Map Address 34 30001 43763 1 F1 30978 Block Status 30978 Block Status 30978 Block Status
4 4 4
40558 22D User Map Address 35 30001 43763 1 F1 30979 Block Status 30979 Block Status 30979 Block Status
4 4 4
40559 22E User Map Address 36 30001 43763 1 F1 30186 Cause of 30186 Cause of 30186 Cause of
Last Trip Last Trip Last Trip
40560 22F User Map Address 37 30001 43763 1 F1 30308 Time to Trip 30285 Contact 30285 Contact
Input 1-32 Input 1-32
40561 230 User Map Address 38 30001 43763 1 F1 30309 Time to Trip 30286 Contact 30286 Contact
Input 1-32 Input 1-32
40562 231 User Map Address 39 30001 43763 1 F1 30313 Time to 30298 Contact 30298 Contact
Reset Output 1-32 Output 1-32
40563 232 User Map Address 40 30001 43763 1 F1 30307 Thermal 30299 Contact 30299 Contact
Capacity Used Output 1-32 Output 1-32
40564 233 User Map Address 41 30001 43763 1 F1 30336 Motor Load 30288 Virtual Input 30288 Virtual Input
1-32 1-32
40565 234 User Map Address 42 30001 43763 1 F1 30285 Contact 30289 Virtual Input 30289 Virtual Input
Input 1-32 1-32 1-32
40566 235 User Map Address 43 30001 43763 1 F1 30286 Contact 30317 Active 30317 Active
Input 1-32 Setpoint Group Setpoint Group
40567 236 User Map Address 44 30001 43763 1 F1 30298 Contact 30291 Logic 30291 Logic
Output 1-32 Element 1-16 Element 1-16
40568 237 User Map Address 45 30001 43763 1 F1 30299 Contact 30296 Remote 30296 Remote
Output 1-32 Input 1-32 Input 1-32
40569 238 User Map Address 46 30001 43763 1 F1 30288 Virtual Input 30297 Remote 30297 Remote
1-32 Input 1-32 Input 1-32
40570 239 User Map Address 47 30001 43763 1 F1 30289 Virtual Input 30300 Remote 30300 Remote
1-32 Output 1-32 Output 1-32
40571 23A User Map Address 48 30001 43763 1 F1 30290 Virtual 30301 Remote 30301 Remote
Output 1-32 Output 1-32 Output 1-32
40572 23B User Map Address 49 30001 43763 1 F1 30291 Virtual 30328 W1a 30328 Ia
Output 1-32
40573 23C User Map Address 50 30001 43763 1 F1 30296 Remote 30329 W1a 30329 Ia
Input 1-32
40574 23D User Map Address 51 30001 43763 1 F1 30297 Remote 30330 W1b 30330 Ib
Input 1-32
40575 23E User Map Address 52 30001 43763 1 F1 30300 Remote 30331 W1b 30331 Ib
Output 1-32
40576 23F User Map Address 53 30001 43763 1 F1 30301 Remote 30332 W1c 30332 Ic
Output 1-32
40577 240 User Map Address 54 30001 43763 1 F1 30192 Pre-Trip Ia 30333 W1c 30333 Ic
40578 241 User Map Address 55 30001 43763 1 F1 30193 Pre-Trip Ia 30326 W1n 30326 In
40579 242 User Map Address 56 30001 43763 1 F1 30194 Pre-Trip Ib 30327 W1n 30327 In
40580 243 User Map Address 57 30001 43763 1 F1 30195 Pre-Trip Ib 30338 W1g 30334 Iavg
40581 244 User Map Address 58 30001 43763 1 F1 30196 Pre-Trip Ic 30339 W1g 30335 Iavg
40582 245 User Map Address 59 30001 43763 1 F1 30197 Pre-Trip Ic 30324 W1sg 30338 Ig
40583 246 User Map Address 60 30001 43763 1 F1 30328 Ia 30325 W1sg 30339 Ig

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 9-3


MODBUS USER MAP CHAPTER 9: USING THE MODBUS USER MAP

MODBUS Hex Description Min Max Step Format 339 Factory 345 Factory 350 Factory
Address Addr. Code Default Default Default
40584 247 User Map Address 61 30001 43763 1 F1 30329 Ia 30319 Relay 1 Coil 30324 Sense Ig
Status
40585 248 User Map Address 62 30001 43763 1 F1 30330 Ib 30320 Relay 2 Coil 30325 Sense Ig
Staus
40586 249 User Map Address 63 30001 43763 1 F1 30331 Ib 31665 W2a 30319 Trip Coil
Status
40587 24A User Map Address 64 30001 43763 1 F1 30332 Ic 31666 W2a 30320 Close Coil
Staus
40588 24B User Map Address 65 30001 43763 1 F1 30333 Ic 31667 W2b 30001
40589 24C User Map Address 66 30001 43763 1 F1 30326 In 31668 W2b 30001
40590 24D User Map Address 67 30001 43763 1 F1 30327 In 31669 W2c 30001
40591 24E User Map Address 68 30001 43763 1 F1 30334 Iavg 31670 W2c 30001
40592 24F User Map Address 69 30001 43763 1 F1 30335 Iavg 31671 W2n 30001
40593 250 User Map Address 70 30001 43763 1 F1 30338 Ig 31672 W2n 30001
40594 251 User Map Address 71 30001 43763 1 F1 30339 Ig 31673 W2g 30001
40595 252 User Map Address 72 30001 43763 1 F1 30324 Sense Ig 31674 W2g 30001
40596 253 User Map Address 73 30001 43763 1 F1 30325 Sense Ig 31675 W2sg 30001
40597 254 User Map Address 74 30001 43763 1 F1 30319 Relay 1 Coil 31675 W2sg 30001
Status
40598 255 User Map Address 75 30001 43763 1 F1 30320 Relay 2 Coil 31677 Diff Phase A 30001
Status
40599 256 User Map Address 76 30001 43763 1 F1 30429 RTD 1 31678 Diff Phase A 30001
40600 257 User Map Address 77 30001 43763 1 F1 30430 RTD 2 31679 Diff Phase B 30001
40601 258 User Map Address 78 30001 43763 1 F1 30431 RTD 3 31680 Diff Phase B 30001
40602 259 User Map Address 79 30001 43763 1 F1 30432 RTD 4 31681 Diff Phase C 30001
40603 25A User Map Address 80 30001 43763 1 F1 30433 RTD 5 31682 Diff Phase C 30001
40604 25B User Map Address 81 30001 43763 1 F1 30434 RTD 6 31683 2nd 30001
Harmonic Phase A
40605 25C User Map Address 82 30001 43763 1 F1 30420 RTD 7 31684 2nd 30001
Harmonic Phase B
40606 25D User Map Address 83 30001 43763 1 F1 30421 RTD 8 31685 2nd 30001
Harmonic Phase C
40607 25E User Map Address 84 30001 43763 1 F1 30422 RTD 9 31686 5th 30001
Harmonic Phase A
40608 25F User Map Address 85 30001 43763 1 F1 30423 RTD 10 31687 5th 30001
Harmonic Phase B
40609 260 User Map Address 86 30001 43763 1 F1 30424 RTD 11 31688 5th 30001
Harmonic Phase C
40610 261 User Map Address 87 30001 43763 1 F1 30425 RTD 12 31695 I Restraint 30001
Ph A
40611 262 User Map Address 88 30001 43763 1 F1 30358 Vab 31696 I Restraint 30001
Ph A
40612 263 User Map Address 89 30001 43763 1 F1 30359 Vbc 31697 I Restraint 30001
Ph B
40613 264 User Map Address 90 30001 43763 1 F1 30360 Vca 31698 I Restraint 30001
Ph B
40614 265 User Map Address 91 30001 43763 1 F1 30361 Average 31699 I Restraint 30001
Line Voltage Ph C
40615 266 User Map Address 92 30001 43763 1 F1 30366 Frequency 31700 I Restraint 30001
Ph C
40616 267 User Map Address 93 30001 43763 1 F1 30384 Power 30001 30001
Factor
40617 268 User Map Address 94 30001 43763 1 F1 30385 Real Power 30001 30001

9-4 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 9: USING THE MODBUS USER MAP MODBUS USER MAP

MODBUS Hex Description Min Max Step Format 339 Factory 345 Factory 350 Factory
Address Addr. Code Default Default Default
40618 269 User Map Address 95 30001 43763 1 F1 30386 Real Power 30001 30001
40619 26A User Map Address 96 30001 43763 1 F1 30389 Reative 30001 30001
Power
40620 26B User Map Address 97 30001 43763 1 F1 30390 Reative 30001 30001
Power
40621 26C User Map Address 98 30001 43763 1 F1 30391 Apparent 30001 30001
Power
40622 26D User Map Address 99 30001 43763 1 F1 30392 Apparent 30001 30001
Power
40623 26E User Map Address 100 30001 43763 1 F1 30001 30001 30001
40624 26F User Map Address 101 30001 43763 1 F1 30001 30001 30001
40625 270 User Map Address 102 30001 43763 1 F1 30001 30001 30001
40626 271 User Map Address 103 30001 43763 1 F1 30001 30001 30001
40627 272 User Map Address 104 30001 43763 1 F1 30001 30001 30001
40628 273 User Map Address 105 30001 43763 1 F1 30001 30001 30001
40629 274 User Map Address 106 30001 43763 1 F1 30001 30001 30001
40630 275 User Map Address 107 30001 43763 1 F1 30001 30001 30001
40631 276 User Map Address 108 30001 43763 1 F1 30001 30001 30001
40632 277 User Map Address 109 30001 43763 1 F1 30001 30001 30001
40633 278 User Map Address 110 30001 43763 1 F1 30001 30001 30001
40634 279 User Map Address 111 30001 43763 1 F1 30001 30001 30001
40635 27A User Map Address 112 30001 43763 1 F1 30001 30001 30001
40636 27B User Map Address 113 30001 43763 1 F1 30001 30001 30001
40637 27C User Map Address 114 30001 43763 1 F1 30001 30001 30001
40638 27D User Map Address 115 30001 43763 1 F1 30001 30001 30001
40639 27E User Map Address 116 30001 43763 1 F1 30001 30001 30001
40640 27F User Map Address 117 30001 43763 1 F1 30001 30001 30001
40641 280 User Map Address 118 30001 43763 1 F1 30001 30001 30001
40642 281 User Map Address 119 30001 43763 1 F1 30001 30001 30001
40643 282 User Map Address 120 30001 43763 1 F1 30001 30001 30001
40644 283 User Map Address 121 30001 43763 1 F1 30001 30001 30001
40645 284 User Map Address 122 30001 43763 1 F1 30001 30001 30001
40646 285 User Map Address 123 30001 43763 1 F1 30001 30001 30001
40647 286 User Map Address 124 30001 43763 1 F1 30001 30001 30001
40648 287 User Map Address 125 30001 43763 1 F1 30001 30001 30001

Table 9-2: User Map Actual Values


MODBUS Hex Description Min Max Step Format Factory
Address Address Code Default
30524 20B User Map Value 1 0 0xFFFF 1 F1 0
30525 20C User Map Value 2 0 0xFFFF 1 F1 0
30526 20D User Map Value 3 0 0xFFFF 1 F1 0
30527 20E User Map Value 4 0 0xFFFF 1 F1 0
30528 20F User Map Value 5 0 0xFFFF 1 F1 0
30529 210 User Map Value 6 0 0xFFFF 1 F1 0
30530 211 User Map Value 7 0 0xFFFF 1 F1 0
30531 212 User Map Value 8 0 0xFFFF 1 F1 0
30532 213 User Map Value 9 0 0xFFFF 1 F1 0

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 9-5


MODBUS USER MAP CHAPTER 9: USING THE MODBUS USER MAP

MODBUS Hex Description Min Max Step Format Factory


Address Address Code Default
30533 214 User Map Value 10 0 0xFFFF 1 F1 0
30534 215 User Map Value 11 0 0xFFFF 1 F1 0
30535 216 User Map Value 12 0 0xFFFF 1 F1 0
30536 217 User Map Value 13 0 0xFFFF 1 F1 0
30537 218 User Map Value 14 0 0xFFFF 1 F1 0
30538 219 User Map Value 15 0 0xFFFF 1 F1 0
30539 21A User Map Value 16 0 0xFFFF 1 F1 0
30540 21B User Map Value 17 0 0xFFFF 1 F1 0
30541 21C User Map Value 18 0 0xFFFF 1 F1 0
30542 21D User Map Value 19 0 0xFFFF 1 F1 0
30543 21E User Map Value 20 0 0xFFFF 1 F1 0
30544 21F User Map Value 21 0 0xFFFF 1 F1 0
30545 220 User Map Value 22 0 0xFFFF 1 F1 0
30546 221 User Map Value 23 0 0xFFFF 1 F1 0
30547 222 User Map Value 24 0 0xFFFF 1 F1 0
30548 223 User Map Value 25 0 0xFFFF 1 F1 0
30549 224 User Map Value 26 0 0xFFFF 1 F1 0
30550 225 User Map Value 27 0 0xFFFF 1 F1 0
30551 226 User Map Value 28 0 0xFFFF 1 F1 0
30552 227 User Map Value 29 0 0xFFFF 1 F1 0
30553 228 User Map Value 30 0 0xFFFF 1 F1 0
30554 229 User Map Value 31 0 0xFFFF 1 F1 0
30555 22A User Map Value 32 0 0xFFFF 1 F1 0
30556 22B User Map Value 33 0 0xFFFF 1 F1 0
30557 22C User Map Value 34 0 0xFFFF 1 F1 0
30558 22D User Map Value 35 0 0xFFFF 1 F1 0
30559 22E User Map Value 36 0 0xFFFF 1 F1 0
30560 22F User Map Value 37 0 0xFFFF 1 F1 0
30561 230 User Map Value 38 0 0xFFFF 1 F1 0
30562 231 User Map Value 39 0 0xFFFF 1 F1 0
30563 232 User Map Value 40 0 0xFFFF 1 F1 0
30564 233 User Map Value 41 0 0xFFFF 1 F1 0
30565 234 User Map Value 42 0 0xFFFF 1 F1 0
30566 235 User Map Value 43 0 0xFFFF 1 F1 0
30567 236 User Map Value 44 0 0xFFFF 1 F1 0
30568 237 User Map Value 45 0 0xFFFF 1 F1 0
30569 238 User Map Value 46 0 0xFFFF 1 F1 0
30570 239 User Map Value 47 0 0xFFFF 1 F1 0
30571 23A User Map Value 48 0 0xFFFF 1 F1 0
30572 23B User Map Value 49 0 0xFFFF 1 F1 0
30573 23C User Map Value 50 0 0xFFFF 1 F1 0
30574 23D User Map Value 51 0 0xFFFF 1 F1 0
30575 23E User Map Value 52 0 0xFFFF 1 F1 0
30576 23F User Map Value 53 0 0xFFFF 1 F1 0
30577 240 User Map Value 54 0 0xFFFF 1 F1 0
30578 241 User Map Value 55 0 0xFFFF 1 F1 0

9-6 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 9: USING THE MODBUS USER MAP MODBUS USER MAP

MODBUS Hex Description Min Max Step Format Factory


Address Address Code Default
30579 242 User Map Value 56 0 0xFFFF 1 F1 0
30580 243 User Map Value 57 0 0xFFFF 1 F1 0
30581 244 User Map Value 58 0 0xFFFF 1 F1 0
30582 245 User Map Value 59 0 0xFFFF 1 F1 0
30583 246 User Map Value 60 0 0xFFFF 1 F1 0
30584 247 User Map Value 61 0 0xFFFF 1 F1 0
30585 248 User Map Value 62 0 0xFFFF 1 F1 0
30586 249 User Map Value 63 0 0xFFFF 1 F1 0
30587 24A User Map Value 64 0 0xFFFF 1 F1 0
30588 24B User Map Value 65 0 0xFFFF 1 F1 0
30589 24C User Map Value 66 0 0xFFFF 1 F1 0
30590 24D User Map Value 67 0 0xFFFF 1 F1 0
30591 24E User Map Value 68 0 0xFFFF 1 F1 0
30592 24F User Map Value 69 0 0xFFFF 1 F1 0
30593 250 User Map Value 70 0 0xFFFF 1 F1 0
30594 251 User Map Value 71 0 0xFFFF 1 F1 0
30595 252 User Map Value 72 0 0xFFFF 1 F1 0
30596 253 User Map Value 73 0 0xFFFF 1 F1 0
30597 254 User Map Value 74 0 0xFFFF 1 F1 0
30598 255 User Map Value 75 0 0xFFFF 1 F1 0
30599 256 User Map Value 76 0 0xFFFF 1 F1 0
30600 257 User Map Value 77 0 0xFFFF 1 F1 0
30601 258 User Map Value 78 0 0xFFFF 1 F1 0
30602 259 User Map Value 79 0 0xFFFF 1 F1 0
30603 25A User Map Value 80 0 0xFFFF 1 F1 0
30604 25B User Map Value 81 0 0xFFFF 1 F1 0
30605 25C User Map Value 82 0 0xFFFF 1 F1 0
30606 25D User Map Value 83 0 0xFFFF 1 F1 0
30607 25E User Map Value 84 0 0xFFFF 1 F1 0
30608 25F User Map Value 85 0 0xFFFF 1 F1 0
30609 260 User Map Value 86 0 0xFFFF 1 F1 0
30610 261 User Map Value 87 0 0xFFFF 1 F1 0
30611 262 User Map Value 88 0 0xFFFF 1 F1 0
30612 263 User Map Value 89 0 0xFFFF 1 F1 0
30613 264 User Map Value 90 0 0xFFFF 1 F1 0
30614 265 User Map Value 91 0 0xFFFF 1 F1 0
30615 266 User Map Value 92 0 0xFFFF 1 F1 0
30616 267 User Map Value 93 0 0xFFFF 1 F1 0
30617 268 User Map Value 94 0 0xFFFF 1 F1 0
30618 269 User Map Value 95 0 0xFFFF 1 F1 0
30619 26A User Map Value 96 0 0xFFFF 1 F1 0
30620 26B User Map Value 97 0 0xFFFF 1 F1 0
30621 26C User Map Value 98 0 0xFFFF 1 F1 0
30622 26D User Map Value 99 0 0xFFFF 1 F1 0
30623 26E User Map Value 100 0 0xFFFF 1 F1 0
30624 26F User Map Value 101 0 0xFFFF 1 F1 0

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 9-7


MODBUS USER MAP CHAPTER 9: USING THE MODBUS USER MAP

MODBUS Hex Description Min Max Step Format Factory


Address Address Code Default
30625 270 User Map Value 102 0 0xFFFF 1 F1 0
30626 271 User Map Value 103 0 0xFFFF 1 F1 0
30627 272 User Map Value 104 0 0xFFFF 1 F1 0
30628 273 User Map Value 105 0 0xFFFF 1 F1 0
30629 274 User Map Value 106 0 0xFFFF 1 F1 0
30630 275 User Map Value 107 0 0xFFFF 1 F1 0
30631 276 User Map Value 108 0 0xFFFF 1 F1 0
30632 277 User Map Value 109 0 0xFFFF 1 F1 0
30633 278 User Map Value 110 0 0xFFFF 1 F1 0
30634 279 User Map Value 111 0 0xFFFF 1 F1 0
30635 27A User Map Value 112 0 0xFFFF 1 F1 0
30636 27B User Map Value 113 0 0xFFFF 1 F1 0
30637 27C User Map Value 114 0 0xFFFF 1 F1 0
30638 27D User Map Value 115 0 0xFFFF 1 F1 0
30639 27E User Map Value 116 0 0xFFFF 1 F1 0
30640 27F User Map Value 117 0 0xFFFF 1 F1 0
30641 280 User Map Value 118 0 0xFFFF 1 F1 0
30642 281 User Map Value 119 0 0xFFFF 1 F1 0
30643 282 User Map Value 120 0 0xFFFF 1 F1 0
30644 283 User Map Value 121 0 0xFFFF 1 F1 0
30645 284 User Map Value 122 0 0xFFFF 1 F1 0
30646 285 User Map Value 123 0 0xFFFF 1 F1 0
30647 286 User Map Value 124 0 0xFFFF 1 F1 0
30648 287 User Map Value 125 0 0xFFFF 1 F1 0

9-8 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


GE
Grid Solutions

3 Series Protective Relay Platform

Chapter 10: 339 MODBUS memory


map and Format Codes

339 MODBUS memory map and Format Codes

The 339, 345, and 350 relays have different MODBUS maps and Format Codes. Make sure
NOTE:

you are looking at the chapter corresponding to your relay model.


NOTE

The Cause of Last trip register (MODBUS Address 30186) returns a combined value of
NOTE:

Pickup And Operate.


NOTE
For example, for a Phase TOC 1 Trip:
0x90C1 Ph TOC1 Trip PKP
0x90C2 Ph TOC1 Trip OP
Upon Phase TOC 1 Trip, the value read from 30186 Cause of Last Trip register is: 0x90C3

339 MODBUS memory map

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
PRODUCT INFORMATION
30001 0x0 Product Device Code 0 1 1 --- F22 L2 1
30002 0x1 Hardware Revision 0 26 1 --- F15 1 1
30003 0x2 Firmware Version 0 0xFFFF 1 --- F3 231 1
30006 0x5 Boot Version 0 0xFFFF 1 --- F3 100 1
30008 0x7 Serial Number 0 6 1 --- F22 L2MA09000 6
001
30014 0xD Order Code 0 16 1 --- F22 339- 16
CP5G5HISS
XXS
30030 0x1D MAC Address 0 0xFFFF 1 --- FC214 0 3
30035 0x22 Comms HW Version 0 26 1 --- F15 0 1
30037 0x24 Build Date 0 6 1 --- F22 Unknown 6
30043 0x2A Build Time 0 4 1 --- F22 Unknown 4
30051 0x32 Comm Build Date 0 6 1 --- F22 Unknown 6

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-1


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30057 0x38 Comm Build Time 0 4 1 --- F22 Unknown 4
30061 0x3C Comm Revision 0 0xFFFF 1 --- F3 231 1
30063 0x3E Comm Boot Code Revision 0 0xFFFF 1 --- F3 200 1
30064 0x3F RMIO Value 0 4 1 --- F22 4
30068 0x43 FPGA Revision 0 0xFFFF 1 --- F3 0 1
30135 0x86 Main Boot Code Date 0 6 1 --- F22 Unknown 6
30141 0x8C Main Boot Code Time 0 4 1 --- F22 Unknown 4
30145 0x90 Comms Boot Code Date 0 6 1 --- F22 Unknown 6
30151 0x96 Comms Boot Code Time 0 4 1 --- F22 Unknown 4
LAST TRIP DATA
30186 0xB9 Cause of Last Trip 0 0xFFFF 1 --- FC134 0 1
REAL-TIME CLOCK
30223 0xDE Weekday 0 7 1 --- None 0 1
30224 0xDF Current Date 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
9
30226 0xE1 Current Time 0 0X173BEA5F 0 --- F19 0 2
30228 0xE3 Daylight Savings Active 0 1 1 --- FC126 0 1
TRIP COUNTERS
30230 0xE5 Total Number of Trips 0 10000 1 --- F1 0 1
COUNTERS
30246 0xF5 Number of Emergency 0 65535 1 --- F1 0 1
Restarts
30257 0x100 Number of Motor Starts 0 65535 1 --- F1 0 1
30259 0x102 Motor Running Hours 0 65535 1 hrs F1 0 1
TIMERS
30262 0x105 Start Timer 1 0 3600 1 s F1 0 1
30263 0x106 Start Timer 2 0 3600 1 s F1 0 1
30264 0x107 Start Timer 3 0 3600 1 s F1 0 1
30265 0x108 Start Timer 4 0 3600 1 s F1 0 1
30266 0x109 Start Timer 5 0 3600 1 s F1 0 1
30270 0x10D Overload Lockout 0 65535 1 s F1 0 1
30271 0x10E Starts/Hour Block 0 3600 1 s F1 0 1
30272 0x10F Time Between Starts 0 3601 1 s F1B 0 1
Lockout Time
30273 0x110 Restart Block 0 50000 1 s F1 0 1
30278 0x115 Therman Inhibit Timer 0 65535 1 s F1 0 1
30279 0x116 Motor Lockout Time 0 65535 1 s F1 0 1
INPUTS / OUTPUTS
30285 0x11C Contact Input 32-1 (Bit Field) 0 0xFFFFFFFF 1 --- FC167 0 2
30288 0x11F Virtual Input 32-1 (Bit Field) 0 0xFFFFFFFF 1 --- FC167 0 2
30290 0x121 Virtual Output 32-1 (Bit Field) 0 0xFFFFFFFF 1 --- FC167 0 2
30296 0x127 Remote Input 32-1 (Bit Field) 0 0xFFFFFFFF 1 --- FC167 0 2
30298 0x129 Contact Output 32-1 (Bit 0 0xFFFFFFFF 1 --- FC167 0 2
Field)
30300 0x12B Remote Output 32-1 (Bit 0 0xFFFFFFFF 1 --- FC167 0 2
Field)
CURRENT METERING
30323 0x142 CBCT Ground Current 0 65535 1 A F3 0 1

10-2 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30326 0x145 Neutral Current 0 100000 1 A F10 0 2
30328 0x147 Phase A Current 0 1200000 1 A F10 0 2
30330 0x149 Phase B Current 0 1200000 1 A F10 0 2
30332 0x14B Phase C Current 0 1200000 1 A F10 0 2
30334 0x14D Average Phase Current 0 1200000 1 A F10 0 2
30336 0x14F Motor Load 0 30000 1 x FLA F3 0 1
30337 0x150 Current Unbalance 0 10000 1 % F3 0 1
30338 0x151 Ground Current 0 1200000 1 A F10 0 2
PHASE ANGLES
30343 0x156 Ia Angle 0 359 1 ° F1 0 1
30344 0x157 Ib Angle 0 359 1 ° F1 0 1
30345 0x158 Ic Angle 0 359 1 ° F1 0 1
30346 0x159 Van Angle 0 359 1 ° F1 0 1
30347 0x15A Vbn Angle 0 359 1 ° F1 0 1
30348 0x15B Vcn Angle 0 359 1 ° F1 0 1
30349 0x15C Ground Current Angle 0 359 1 ° F1 0 1
30350 0x15D Neutral Current Angle 0 359 1 ° F1 0 1
30353 0x160 Vab Angle 0 359 1 ° F1 0 1
30354 0x161 Vbc Angle 0 359 1 ° F1 0 1
30355 0x162 Vca Angle 0 359 1 ° F1 0 1
BIASED MOTOR LOAD METERING
30356 0x163 Biased Motor Load 0 30000 1 x FLA F3 0 1
POWER & ENERGY METERING
30384 0x17F Power Factor -99 100 1 --- F21 0 1
30385 0x180 Real Power -1000000000 1000000000 1 kW F13 0 2
30389 0x184 Reactive Power -1000000000 1000000000 1 kvar F13 0 2
30392 0x187 MWh Consumption 0 999999999 1 MWh F17 0 2
30394 0x189 Mvarh Consumption 0 999999999 1 Mvarh F17 0 2
30396 0x18B Mvarh Generation 0 999999999 1 Mvarh F17 0 2
30398 0x18D Apparent Power 0 1000000000 1 kVA F10 0 2
30400 0x18F MWh Generation 0 999999999 1 MWh F17 0 2
30402 0x191 Real Power MW -1000000000 1000000000 1 MW F13 0 2
30404 0x193 Reactive Power MW -1000000000 1000000000 1 Mvar F13 0 2
RTD METERING
30420 0x1A3 RTD 7 Temp -50 251 1 °C F4 0 1
30421 0x1A4 RTD 8 Temp -50 251 1 °C F4 0 1
30422 0x1A5 RTD 9 Temp -50 251 1 °C F4 0 1
30423 0x1A6 RTD 10 Temp -50 251 1 °C F4 0 1
30424 0x1A7 RTD 11 Temp -50 251 1 °C F4 0 1
30425 0x1A8 RTD 12 Temp -50 251 1 °C F4 0 1
30427 0x1AA Hottest Stator RTD 0 12 1 --- F1 0 1
30428 0x1AB Hottest Stator RTD -50 251 1 °C F4 0 1
30429 0x1AC RTD 1 Temperature -50 251 1 °C F4 0 1
30430 0x1AD RTD 2 Temperature -50 251 1 °C F4 0 1
30431 0x1AE RTD 3 Temperature -50 251 1 °C F4 0 1
30432 0x1AF RTD 4 Temperature -50 251 1 °C F4 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-3


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30433 0x1B0 RTD 5 Temperature -50 251 1 °C F4 0 1
30434 0x1B1 RTD 6 Temperature -50 251 1 °C F4 0 1
TEMPERATURE
30435 0x1B2 Ambient Temperature -50 250 1 ° F4 25 1
NEGATIVE SEQUENCE VOLTAGE ANGLE
30463 0x1CE Negative Sequence Voltage 0 359 1 °Lag F1 0 1
Angle
LEARNED DATA
30467 0x1D2 Learned Acceleration Time 0 65535 1 s F2 0 1
30468 0x1D3 Learned Starting Current 0 1200000 1 A F10 0 2
30470 0x1D5 Learned Starting Capacity 0 100 1 % F1 0 1
30471 0x1D6 Last Acceleration Time 0 65535 1 s F2 0 1
30472 0x1D7 Last Starting Current 0 1200000 1 A F10 0 2
30474 0x1D9 Last Start TCU 0 100 1 % F1 0 1
30475 0x1DA Learned Average Load 0 30000 1 x FLA F3 0 1
30476 0x1DB Learned Run Time After 0 65535 1 --- F1 0 1
Start (days)
30477 0x1DC Learned Run Time After 0 1339 1 --- F1 0 1
Start (minutes)
NEGATIVE SEQUENCE VOLTAGE METERING
30479 0x1DE Negative Sequence Voltage 0 65535 1 V F1 0 1
RTD MAXIMUMS
30485 0x1E4 RTD 1 Maximum -50 250 1 °C F4 0 1
Temperature
30486 0x1E5 RTD 2 Maximum -50 250 1 °C F4 0 1
Temperature
30487 0x1E6 RTD 3 Maximum -50 250 1 °C F4 0 1
Temperature
30488 0x1E7 RTD 4 Maximum -50 250 1 °C F4 0 1
Temperature
30489 0x1E8 RTD 5 Maximum -50 250 1 °C F4 0 1
Temperature
30490 0x1E9 RTD 6 Maximum -50 250 1 °C F4 0 1
Temperature
30491 0x1EA RTD 7 MAX Temp -50 250 1 °C F4 0 1
30492 0x1EB RTD 8 MAX Temp -50 250 1 °C F4 0 1
30493 0x1EC RTD 9 MAX Temp -50 250 1 °C F4 0 1
30494 0x1ED RTD 10 MAX Temp -50 250 1 °C F4 0 1
30495 0x1EE RTD 11 MAX Temp -50 250 1 °C F4 0 1
30496 0x1EF RTD 12 MAX Temp -50 250 1 °C F4 0 1
LED STATUS
30505 0x1F8 LED Status 0 0xFFFFFFFF 1 --- FC144A 0 2
USER MAP ACTUAL VALUES
30524 0x20B User Map Value 1 0 0xFFFF 1 --- F1 0 1
30525 0x20C User Map Value 2 0 0xFFFF 1 --- F1 0 1
30526 0x20D User Map Value 3 0 0xFFFF 1 --- F1 0 1
30527 0x20E User Map Value 4 0 0xFFFF 1 --- F1 0 1
30528 0x20F User Map Value 5 0 0xFFFF 1 --- F1 0 1
30529 0x210 User Map Value 6 0 0xFFFF 1 --- F1 0 1

10-4 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30530 0x211 User Map Value 7 0 0xFFFF 1 --- F1 0 1
30531 0x212 User Map Value 8 0 0xFFFF 1 --- F1 0 1
30532 0x213 User Map Value 9 0 0xFFFF 1 --- F1 0 1
30533 0x214 User Map Value 10 0 0xFFFF 1 --- F1 0 1
30534 0x215 User Map Value 11 0 0xFFFF 1 --- F1 0 1
30535 0x216 User Map Value 12 0 0xFFFF 1 --- F1 0 1
30536 0x217 User Map Value 13 0 0xFFFF 1 --- F1 0 1
30537 0x218 User Map Value 14 0 0xFFFF 1 --- F1 0 1
30538 0x219 User Map Value 15 0 0xFFFF 1 --- F1 0 1
30539 0x21A User Map Value 16 0 0xFFFF 1 --- F1 0 1
30540 0x21B User Map Value 17 0 0xFFFF 1 --- F1 0 1
30541 0x21C User Map Value 18 0 0xFFFF 1 --- F1 0 1
30542 0x21D User Map Value 19 0 0xFFFF 1 --- F1 0 1
30543 0x21E User Map Value 20 0 0xFFFF 1 --- F1 0 1
30544 0x21F User Map Value 21 0 0xFFFF 1 --- F1 0 1
30545 0x220 User Map Value 22 0 0xFFFF 1 --- F1 0 1
30546 0x221 User Map Value 23 0 0xFFFF 1 --- F1 0 1
30547 0x222 User Map Value 24 0 0xFFFF 1 --- F1 0 1
30548 0x223 User Map Value 25 0 0xFFFF 1 --- F1 0 1
30549 0x224 User Map Value 26 0 0xFFFF 1 --- F1 0 1
30550 0x225 User Map Value 27 0 0xFFFF 1 --- F1 0 1
30551 0x226 User Map Value 28 0 0xFFFF 1 --- F1 0 1
30552 0x227 User Map Value 29 0 0xFFFF 1 --- F1 0 1
30553 0x228 User Map Value 30 0 0xFFFF 1 --- F1 0 1
30554 0x229 User Map Value 31 0 0xFFFF 1 --- F1 0 1
30555 0x22A User Map Value 32 0 0xFFFF 1 --- F1 0 1
30556 0x22B User Map Value 33 0 0xFFFF 1 --- F1 0 1
30557 0x22C User Map Value 34 0 0xFFFF 1 --- F1 0 1
30558 0x22D User Map Value 35 0 0xFFFF 1 --- F1 0 1
30559 0x22E User Map Value 36 0 0xFFFF 1 --- F1 0 1
30560 0x22F User Map Value 37 0 0xFFFF 1 --- F1 0 1
30561 0x230 User Map Value 38 0 0xFFFF 1 --- F1 0 1
30562 0x231 User Map Value 39 0 0xFFFF 1 --- F1 0 1
30563 0x232 User Map Value 40 0 0xFFFF 1 --- F1 0 1
30564 0x233 User Map Value 41 0 0xFFFF 1 --- F1 0 1
30565 0x234 User Map Value 42 0 0xFFFF 1 --- F1 0 1
30566 0x235 User Map Value 43 0 0xFFFF 1 --- F1 0 1
30567 0x236 User Map Value 44 0 0xFFFF 1 --- F1 0 1
30568 0x237 User Map Value 45 0 0xFFFF 1 --- F1 0 1
30569 0x238 User Map Value 46 0 0xFFFF 1 --- F1 0 1
30570 0x239 User Map Value 47 0 0xFFFF 1 --- F1 0 1
30571 0x23A User Map Value 48 0 0xFFFF 1 --- F1 0 1
30572 0x23B User Map Value 49 0 0xFFFF 1 --- F1 0 1
30573 0x23C User Map Value 50 0 0xFFFF 1 --- F1 0 1
30574 0x23D User Map Value 51 0 0xFFFF 1 --- F1 0 1
30575 0x23E User Map Value 52 0 0xFFFF 1 --- F1 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-5


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30576 0x23F User Map Value 53 0 0xFFFF 1 --- F1 0 1
30577 0x240 User Map Value 54 0 0xFFFF 1 --- F1 0 1
30578 0x241 User Map Value 55 0 0xFFFF 1 --- F1 0 1
30579 0x242 User Map Value 56 0 0xFFFF 1 --- F1 0 1
30580 0x243 User Map Value 57 0 0xFFFF 1 --- F1 0 1
30581 0x244 User Map Value 58 0 0xFFFF 1 --- F1 0 1
30582 0x245 User Map Value 59 0 0xFFFF 1 --- F1 0 1
30583 0x246 User Map Value 60 0 0xFFFF 1 --- F1 0 1
30584 0x247 User Map Value 61 0 0xFFFF 1 --- F1 0 1
30585 0x248 User Map Value 62 0 0xFFFF 1 --- F1 0 1
30586 0x249 User Map Value 63 0 0xFFFF 1 --- F1 0 1
30587 0x24A User Map Value 64 0 0xFFFF 1 --- F1 0 1
30588 0x24B User Map Value 65 0 0xFFFF 1 --- F1 0 1
30589 0x24C User Map Value 66 0 0xFFFF 1 --- F1 0 1
30590 0x24D User Map Value 67 0 0xFFFF 1 --- F1 0 1
30591 0x24E User Map Value 68 0 0xFFFF 1 --- F1 0 1
30592 0x24F User Map Value 69 0 0xFFFF 1 --- F1 0 1
30593 0x250 User Map Value 70 0 0xFFFF 1 --- F1 0 1
30594 0x251 User Map Value 71 0 0xFFFF 1 --- F1 0 1
30595 0x252 User Map Value 72 0 0xFFFF 1 --- F1 0 1
30596 0x253 User Map Value 73 0 0xFFFF 1 --- F1 0 1
30597 0x254 User Map Value 74 0 0xFFFF 1 --- F1 0 1
30598 0x255 User Map Value 75 0 0xFFFF 1 --- F1 0 1
30599 0x256 User Map Value 76 0 0xFFFF 1 --- F1 0 1
30600 0x257 User Map Value 77 0 0xFFFF 1 --- F1 0 1
30601 0x258 User Map Value 78 0 0xFFFF 1 --- F1 0 1
30602 0x259 User Map Value 79 0 0xFFFF 1 --- F1 0 1
30603 0x25A User Map Value 80 0 0xFFFF 1 --- F1 0 1
30604 0x25B User Map Value 81 0 0xFFFF 1 --- F1 0 1
30605 0x25C User Map Value 82 0 0xFFFF 1 --- F1 0 1
30606 0x25D User Map Value 83 0 0xFFFF 1 --- F1 0 1
30607 0x25E User Map Value 84 0 0xFFFF 1 --- F1 0 1
30608 0x25F User Map Value 85 0 0xFFFF 1 --- F1 0 1
30609 0x260 User Map Value 86 0 0xFFFF 1 --- F1 0 1
30610 0x261 User Map Value 87 0 0xFFFF 1 --- F1 0 1
30611 0x262 User Map Value 88 0 0xFFFF 1 --- F1 0 1
30612 0x263 User Map Value 89 0 0xFFFF 1 --- F1 0 1
30613 0x264 User Map Value 90 0 0xFFFF 1 --- F1 0 1
30614 0x265 User Map Value 91 0 0xFFFF 1 --- F1 0 1
30615 0x266 User Map Value 92 0 0xFFFF 1 --- F1 0 1
30616 0x267 User Map Value 93 0 0xFFFF 1 --- F1 0 1
30617 0x268 User Map Value 94 0 0xFFFF 1 --- F1 0 1
30618 0x269 User Map Value 95 0 0xFFFF 1 --- F1 0 1
30619 0x26A User Map Value 96 0 0xFFFF 1 --- F1 0 1
30620 0x26B User Map Value 97 0 0xFFFF 1 --- F1 0 1
30621 0x26C User Map Value 98 0 0xFFFF 1 --- F1 0 1

10-6 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30622 0x26D User Map Value 99 0 0xFFFF 1 --- F1 0 1
30623 0x26E User Map Value 100 0 0xFFFF 1 --- F1 0 1
30624 0x26F User Map Value 101 0 0xFFFF 1 --- F1 0 1
30625 0x270 User Map Value 102 0 0xFFFF 1 --- F1 0 1
30626 0x271 User Map Value 103 0 0xFFFF 1 --- F1 0 1
30627 0x272 User Map Value 104 0 0xFFFF 1 --- F1 0 1
30628 0x273 User Map Value 105 0 0xFFFF 1 --- F1 0 1
30629 0x274 User Map Value 106 0 0xFFFF 1 --- F1 0 1
30630 0x275 User Map Value 107 0 0xFFFF 1 --- F1 0 1
30631 0x276 User Map Value 108 0 0xFFFF 1 --- F1 0 1
30632 0x277 User Map Value 109 0 0xFFFF 1 --- F1 0 1
30633 0x278 User Map Value 110 0 0xFFFF 1 --- F1 0 1
30634 0x279 User Map Value 111 0 0xFFFF 1 --- F1 0 1
30635 0x27A User Map Value 112 0 0xFFFF 1 --- F1 0 1
30636 0x27B User Map Value 113 0 0xFFFF 1 --- F1 0 1
30637 0x27C User Map Value 114 0 0xFFFF 1 --- F1 0 1
30638 0x27D User Map Value 115 0 0xFFFF 1 --- F1 0 1
30639 0x27E User Map Value 116 0 0xFFFF 1 --- F1 0 1
30640 0x27F User Map Value 117 0 0xFFFF 1 --- F1 0 1
30641 0x280 User Map Value 118 0 0xFFFF 1 --- F1 0 1
30642 0x281 User Map Value 119 0 0xFFFF 1 --- F1 0 1
30643 0x282 User Map Value 120 0 0xFFFF 1 --- F1 0 1
30644 0x283 User Map Value 121 0 0xFFFF 1 --- F1 0 1
30645 0x284 User Map Value 122 0 0xFFFF 1 --- F1 0 1
30646 0x285 User Map Value 123 0 0xFFFF 1 --- F1 0 1
30647 0x286 User Map Value 124 0 0xFFFF 1 --- F1 0 1
30648 0x287 User Map Value 125 0 0xFFFF 1 --- F1 0 1
EVENT RECORDER DETAILS
30652 0x28B Bus VT Secondary 50 240 1 V F1 120 1
30654 0x28D CT Primary 10 5000 1 A F1 100 1
30655 0x28E Ground CT Primary 10 1500 1 A F1 100 1
30656 0x28F VT Ratio 10 3000 1 1 F2 10 1
30658 0x291 Power Unit 0 1 1 --- FC430 0 1
30659 0x292 Event Recorder Last Reset 2 0x010107D8 0X0C1F082E 0 --- F18 0x010107D 2
words 8
30661 0x294 Total Number of Events 0 65535 1 --- F1 0 1
Since Last Clear
30662 0x295 Event Cause 0 0xFFFF 1 --- FC134 0 1
30663 0x296 Event Time 0 0X173BEA5F 0 --- F19 0 2
30665 0x298 Event Date 0x010107D8 0X0C1F082E 0 --- F18 0x010107D 2
8
30667 0x29A Event Ia 0 65535 1 x CT F17A 0 1
30668 0x29B Event Ib 0 65535 1 x CT F17A 0 1
30669 0x29C Event Ic 0 65535 1 x CT F17A 0 1
30670 0x29D Event Ig 0 65535 1 x CT F17A 0 1
30671 0x29E Event In 0 65535 1 x CT F17A 0 1
30672 0x29F Event Isgrd 0 6000 1 x CT F3 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-7


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30673 0x2A0 Event Ia Angle 0 359 1 ° F1 0 1
30674 0x2A1 Event Ib Angle 0 359 1 ° F1 0 1
30675 0x2A2 Event Ic Angle 0 359 1 ° F1 0 1
30676 0x2A3 Event Igrd Angle 0 359 1 ° F1 0 1
30677 0x2A4 Event In Angle 0 359 1 ° F1 0 1
30678 0x2A5 Event Vab 0 65535 1 x VT F17A 0 1
30679 0x2A6 Event Vbc 0 65535 1 x VT F17A 0 1
30680 0x2A7 Event Vca 0 65535 1 x VT F17A 0 1
30681 0x2A8 Event Van 0 65535 1 x VT F17A 0 1
30682 0x2A9 Event Vbn 0 65535 1 x VT F17A 0 1
30683 0x2AA Event Vcn 0 65535 1 x VT F17A 0 1
30684 0x2AB Event Va Angle 0 359 1 ° F1 0 1
30685 0x2AC Event Vb Angle 0 359 1 ° F1 0 1
30686 0x2AD Event Vc Angle 0 359 1 ° F1 0 1
30687 0x2AE Event Vc Angle 0 359 1 ° F1 0 1
30688 0x2AF Frequency 0 12000 1 Hz F3 0 1
30689 0x2B0 Event Power Factor -99 100 1 --- F21 0 1
30690 0x2B1 Event Real Power -65535 65535 1 x F7 0 1
CTxVT
30691 0x2B2 Event Reactive Power -65535 65535 1 x F7 0 1
CTxVT
30692 0x2B3 Event Apparent Power 0 65535 1 x F17A 0 1
CTxVT
30693 0x2B4 Event Thermal Capacity 0 100 1 % F1 0 1
30694 0x2B5 Event Motor Load 0 30000 1 x FLA F3 0 1
30695 0x2B6 Event Unbalance 0 10000 1 % F3 0 1
30696 0x2B7 Event CBCT Current 0 65535 1 A F3 0 1
30697 0x2B8 Event Self-Test Event 0 0xFFFFFFFF 2 --- FC188 0 2
TRANSIENT RECORDER SAMPLES
30720 0x2CF Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 1
30721 0x2D0 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 2
30722 0x2D1 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 3
30723 0x2D2 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 4
30724 0x2D3 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 5
30725 0x2D4 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 6
30726 0x2D5 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 7
30727 0x2D6 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 8
30728 0x2D7 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 9
30729 0x2D8 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 10
30730 0x2D9 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 11

10-8 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30731 0x2DA Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 12
30732 0x2DB Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 13
30733 0x2DC Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 14
30734 0x2DD Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 15
30735 0x2DE Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 16
30736 0x2DF Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 17
30737 0x2E0 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 18
30738 0x2E1 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 19
30739 0x2E2 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 20
30740 0x2E3 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 21
30741 0x2E4 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 22
30742 0x2E5 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 23
30743 0x2E6 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 24
30744 0x2E7 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 25
30745 0x2E8 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 26
30746 0x2E9 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 27
30747 0x2EA Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 28
30748 0x2EB Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 29
30749 0x2EC Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 30
30750 0x2ED Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 31
30751 0x2EE Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 32
30752 0x2EF Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 33
30753 0x2F0 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 34
30754 0x2F1 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 35
30755 0x2F2 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 36
30756 0x2F3 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 37
30757 0x2F4 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 38
30758 0x2F5 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 39

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-9


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30759 0x2F6 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 40
30760 0x2F7 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 41
30761 0x2F8 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 42
30762 0x2F9 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 43
30763 0x2FA Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 44
30764 0x2FB Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 45
30765 0x2FC Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 46
30766 0x2FD Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 47
30767 0x2FE Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 48
30768 0x2FF Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 49
30769 0x300 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 50
30770 0x301 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 51
30771 0x302 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 52
30772 0x303 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 53
30773 0x304 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 54
30774 0x305 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 55
30775 0x306 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 56
30776 0x307 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 57
30777 0x308 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 58
30778 0x309 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 59
30779 0x30A Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 60
30780 0x30B Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 61
30781 0x30C Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 62
30782 0x30D Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 63
30783 0x30E Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 64
30784 0x30F Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 65
30785 0x310 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 66
30786 0x311 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 67

10-10 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30787 0x312 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 68
30788 0x313 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 69
30789 0x314 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 70
30790 0x315 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 71
30791 0x316 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 72
30792 0x317 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 73
30793 0x318 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 74
30794 0x319 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 75
30795 0x31A Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 76
30796 0x31B Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 77
30797 0x31C Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 78
30798 0x31D Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 79
30799 0x31E Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 80
30800 0x31F Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 81
30801 0x320 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 82
30802 0x321 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 83
30803 0x322 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 84
30804 0x323 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 85
30805 0x324 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 86
30806 0x325 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 87
30807 0x326 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 88
30808 0x327 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 89
30809 0x328 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 90
30810 0x329 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 91
30811 0x32A Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 92
30812 0x32B Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 93
30813 0x32C Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 94
30814 0x32D Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 95

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-11


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30815 0x32E Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 96
30816 0x32F Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 97
30817 0x330 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 98
30818 0x331 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 99
30819 0x332 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 100
30820 0x333 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 101
30821 0x334 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 102
30822 0x335 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 103
30823 0x336 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 104
30824 0x337 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 105
30825 0x338 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 106
30826 0x339 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 107
30827 0x33A Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 108
30828 0x33B Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 109
30829 0x33C Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 110
30830 0x33D Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 111
30831 0x33E Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 112
30832 0x33F Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 113
30833 0x340 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 114
30834 0x341 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 115
30835 0x342 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 116
30836 0x343 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 117
30837 0x344 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 118
30838 0x345 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 119
30839 0x346 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 120
30840 0x347 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 121
30841 0x348 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 122
30842 0x349 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 123

10-12 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30843 0x34A Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 124
30844 0x34B Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 125
30845 0x34C Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 126
30846 0x34D Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 127
30847 0x34E Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 128
DATA LOGGER
30860 0x35B Number of Triggers Since 0 32767 1 --- F4 0 1
Clear
30861 0x35C No. of Data Log Samples 0 256 1 --- F4 0 1
Stored
30862 0x35D Data Log Start Index 0 256 1 --- F4 0 1
30863 0x35E Data LogTrigger Cause 0 256 1 --- F4 0 1
30864 0x35F Data Log Trigger Cause 0 0xFFFF 1 --- FC133A 0 1
30865 0x360 Data Log Trigger Date 0x010107D8 0X0C1F082E 1 --- F18 2
0x010107D
8
30867 0x362 Data Log Trigger Time 0 0X173BEA5F 1 --- F19 0 2
30869 0x364 Data Log Status 0 4 1 --- F75 0 1
30881 0x370 Data Log Sample DLSS + 0 -32767 32767 0 --- F4 0 1
30882 0x371 Data Log Sample DLSS + 1 -32767 32767 0 --- F4 0 1
30883 0x372 Data Log Sample DLSS + 2 -32767 32767 0 --- F4 0 1
30884 0x373 Data Log Sample DLSS + 3 -32767 32767 0 --- F4 0 1
30885 0x374 Data Log Sample DLSS + 4 -32767 32767 0 --- F4 0 1
30886 0x375 Data Log Sample DLSS + 5 -32767 32767 0 --- F4 0 1
30887 0x376 Data Log Sample DLSS + 6 -32767 32767 0 --- F4 0 1
30888 0x377 Data Log Sample DLSS + 7 -32767 32767 0 --- F4 0 1
30889 0x378 Data Log Sample DLSS + 8 -32767 32767 0 --- F4 0 1
30890 0x379 Data Log Sample DLSS + 9 -32767 32767 0 --- F4 0 1
30891 0x37A Data Log Sample DLSS + 10 -32767 32767 0 --- F4 0 1
30892 0x37B Data Log Sample DLSS + 11 -32767 32767 0 --- F4 0 1
30893 0x37C Data Log Sample DLSS + 12 -32767 32767 0 --- F4 0 1
30894 0x37D Data Log Sample DLSS + 13 -32767 32767 0 --- F4 0 1
30895 0x37E Data Log Sample DLSS + 14 -32767 32767 0 --- F4 0 1
30896 0x37F Data Log Sample DLSS + 15 -32767 32767 0 --- F4 0 1
30897 0x380 Data Log Sample DLSS + 16 -32767 32767 0 --- F4 0 1
30898 0x381 Data Log Sample DLSS + 17 -32767 32767 0 --- F4 0 1
30899 0x382 Data Log Sample DLSS + 18 -32767 32767 0 --- F4 0 1
30900 0x383 Data Log Sample DLSS + 19 -32767 32767 0 --- F4 0 1
30901 0x384 Data Log Sample DLSS + 20 -32767 32767 0 --- F4 0 1
30902 0x385 Data Log Sample DLSS + 21 -32767 32767 0 --- F4 0 1
30903 0x386 Data Log Sample DLSS + 22 -32767 32767 0 --- F4 0 1
30904 0x387 Data Log Sample DLSS + 23 -32767 32767 0 --- F4 0 1
30905 0x388 Data Log Sample DLSS + 24 -32767 32767 0 --- F4 0 1
30906 0x389 Data Log Sample DLSS + 25 -32767 32767 0 --- F4 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-13


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30907 0x38A Data Log Sample DLSS + 26 -32767 32767 0 --- F4 0 1
30908 0x38B Data Log Sample DLSS + 27 -32767 32767 0 --- F4 0 1
30909 0x38C Data Log Sample DLSS + 28 -32767 32767 0 --- F4 0 1
30910 0x38D Data Log Sample DLSS + 29 -32767 32767 0 --- F4 0 1
30911 0x38E Data Log Sample DLSS + 30 -32767 32767 0 --- F4 0 1
30912 0x38F Data Log Sample DLSS + 31 -32767 32767 0 --- F4 0 1
30913 0x390 Data Log Sample DLSS + 32 -32767 32767 0 --- F4 0 1
30914 0x391 Data Log Sample DLSS + 33 -32767 32767 0 --- F4 0 1
30915 0x392 Data Log Sample DLSS + 34 -32767 32767 0 --- F4 0 1
30916 0x393 Data Log Sample DLSS + 35 -32767 32767 0 --- F4 0 1
30917 0x394 Data Log Sample DLSS + 36 -32767 32767 0 --- F4 0 1
30918 0x395 Data Log Sample DLSS + 37 -32767 32767 0 --- F4 0 1
30919 0x396 Data Log Sample DLSS + 38 -32767 32767 0 --- F4 0 1
30920 0x397 Data Log Sample DLSS + 39 -32767 32767 0 --- F4 0 1
30921 0x398 Data Log Sample DLSS + 40 -32767 32767 0 --- F4 0 1
30922 0x399 Data Log Sample DLSS + 41 -32767 32767 0 --- F4 0 1
30923 0x39A Data Log Sample DLSS + 42 -32767 32767 0 --- F4 0 1
30924 0x39B Data Log Sample DLSS + 43 -32767 32767 0 --- F4 0 1
30925 0x39C Data Log Sample DLSS + 44 -32767 32767 0 --- F4 0 1
30926 0x39D Data Log Sample DLSS + 45 -32767 32767 0 --- F4 0 1
30927 0x39E Data Log Sample DLSS + 46 -32767 32767 0 --- F4 0 1
30928 0x39F Data Log Sample DLSS + 47 -32767 32767 0 --- F4 0 1
30929 0x3A0 Data Log Sample DLSS + 48 -32767 32767 0 --- F4 0 1
30930 0x3A1 Data Log Sample DLSS + 49 -32767 32767 0 --- F4 0 1
30931 0x3A2 Data Log Sample DLSS + 50 -32767 32767 0 --- F4 0 1
30932 0x3A3 Data Log Sample DLSS + 51 -32767 32767 0 --- F4 0 1
30933 0x3A4 Data Log Sample DLSS + 52 -32767 32767 0 --- F4 0 1
30934 0x3A5 Data Log Sample DLSS + 53 -32767 32767 0 --- F4 0 1
30935 0x3A6 Data Log Sample DLSS + 54 -32767 32767 0 --- F4 0 1
30936 0x3A7 Data Log Sample DLSS + 55 -32767 32767 0 --- F4 0 1
30937 0x3A8 Data Log Sample DLSS + 56 -32767 32767 0 --- F4 0 1
30938 0x3A9 Data Log Sample DLSS + 57 -32767 32767 0 --- F4 0 1
30939 0x3AA Data Log Sample DLSS + 58 -32767 32767 0 --- F4 0 1
30940 0x3AB Data Log Sample DLSS + 59 -32767 32767 0 --- F4 0 1
30941 0x3AC Data Log Sample DLSS + 60 -32767 32767 0 --- F4 0 1
30942 0x3AD Data Log Sample DLSS + 61 -32767 32767 0 --- F4 0 1
30943 0x3AE Data Log Sample DLSS + 62 -32767 32767 0 --- F4 0 1
30944 0x3AF Data Log Sample DLSS + 63 -32767 32767 0 --- F4 0 1
STATUS BUFFER
30946 0x3B1 Alarm Status 4 0 0xFFFFFFFF 1 --- FC182 0 2
30948 0x3B3 Alarm Status 3 0 0xFFFFFFFF 1 --- FC181 0 2
30950 0x3B5 Alarm Status 2 0 0xFFFFFFFF 1 --- FC180 0 2
30952 0x3B7 Alarm Status 1 0 0xFFFFFFFF 1 --- FC179 0 2
30954 0x3B9 Trip Status 4 0 0xFFFFFFFF 1 --- FC186 0 2
30956 0x3BB Trip Status 3 0 0xFFFFFFFF 1 --- FC185 0 2
30958 0x3BD Trip Status 2 0 0xFFFFFFFF 1 --- FC184 0 2

10-14 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30960 0x3BF Trip Status 1 0 0xFFFFFFFF 1 --- FC183 0 2
30966 0x3C5 Message Status 2 0 0xFFFFFFFF 1 --- FC188 0 2
30968 0x3C7 Message Status 1 0 0xFFFFFFFF 1 --- FC187 0 2
30970 0x3C9 Control Element Status 4 0 0xFFFFFFFF 1 --- FC194 0 2
30974 0x3CD Control Element Status 2 0 0xFFFFFFFF 1 --- FC192 0 2
30976 0x3CF Control Element Status 1 0 0xFFFFFFFF 1 --- FC191 0 2
30978 0x3D1 Block Status 4 0 0xFFFFFFFF 1 --- FC203 0 2
30980 0x3D3 Block Status 3 0 0xFFFFFFFF 1 --- FC202 0 2
30982 0x3D5 Block Status 2 0 0xFFFFFFFF 1 --- FC201 0 2
30984 0x3D7 Block Status 1 0 0xFFFFFFFF 1 --- FC200 0 2
61850 STATUS
31510 0x5E5 61850 Status 0 2 1 --- FC108 0 1
31511 0x5E6 61850 N.V. Status 0 4 1 --- FC434 0 1
IEC61850 GOOSE STATUS
31515 0x5EA Remote GOOSE Status 0 0xFFFFFFFF 1 --- FC215 0 2
31517 0x5EC Remote GOOSE Header 0 0xFFFFFFFF 1 --- FC215 0 2
Status
PHASE OV TRIP STATUS
31533 0x5FC Trip Phase A Status 5 0 65535 1 --- FC134 0 1
31534 0x5FD Trip Phase B Status 5 0 65535 1 --- FC134 0 1
31535 0x5FE Trip Phase C Status 5 0 65535 1 --- FC134 0 1
PHASE UV TRIP STATUS
31536 0x5FF Trip Phase A Status 6 0 65535 1 --- FC134 0 1
31537 0x600 Trip Phase B Status 6 0 65535 1 --- FC134 0 1
31538 0x601 Trip Phase C Status 6 0 65535 1 --- FC134 0 1
PHASE OV2 TRIP STATUS
31545 0x608 0 65535 1 --- FC134 0 1
PhaseOV2Trip_PhaseAStatus
31546 0x609 0 65535 1 --- FC134 0 1
PhaseOV2Trip_PhaseBStatus
31547 0x60A 0 65535 1 --- FC134 0 1
PhaseOV2Trip_PhaseCStatus
PHASE UV2 TRIP STATUS
31548 0x60B 0 65535 1 --- FC134 0 1
PhaseUV2Trip_PhaseAStatus
31549 0x60C 0 65535 1 --- FC134 0 1
PhaseUV2Trip_PhaseBStatus
31550 0x60D 0 65535 1 --- FC134 0 1
PhaseUV2Trip_PhaseCStatus
PHASE OV3 TRIP STATUS
31551 0x60E 0 65535 1 --- FC134 0 1
PhaseOV3Trip_PhaseAStatus
31552 0x60F 0 65535 1 --- FC134 0 1
PhaseOV3Trip_PhaseBStatus
31553 0x610 0 65535 1 --- FC134 0 1
PhaseOV3Trip_PhaseCStatus
PHASE UV3 TRIP STATUS
31554 0x611 0 65535 1 --- FC134 0 1
PhaseUV3Trip_PhaseAStatus

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-15


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
31555 0x612 0 65535 1 --- FC134 0 1
PhaseUV3Trip_PhaseBStatus
31556 0x613 0 65535 1 --- FC134 0 1
PhaseUV3Trip_PhaseCStatus
PHASE OV4 TRIP STATUS
31557 0x614 0 65535 1 --- FC134 0 1
PhaseOV4Trip_PhaseAStatus
31558 0x615 0 65535 1 --- FC134 0 1
PhaseOV4Trip_PhaseBStatus
31559 0x616 0 65535 1 --- FC134 0 1
PhaseOV4Trip_PhaseCStatus
PHASE UV4 TRIP STATUS
31560 0x617 0 65535 1 --- FC134 0 1
PhaseUV4Trip_PhaseAStatus
31561 0x618 0 65535 1 --- FC134 0 1
PhaseUV4Trip_PhaseBStatus
31562 0x619 0 65535 1 --- FC134 0 1
PhaseUV4Trip_PhaseCStatus
PHASE OV ALARM STATUS
31581 0x62C Alarm Phase A Status 5 0 65535 1 --- FC134 0 1
31582 0x62D Alarm Phase B Status 5 0 65535 1 --- FC134 0 1
31583 0x62E Alarm Phase C Status 5 0 65535 1 --- FC134 0 1
PHASE UV ALARM STATUS
31584 0x62F Alarm Phase A Status 6 0 65535 1 --- FC134 0 1
31585 0x630 Alarm Phase B Status 6 0 65535 1 --- FC134 0 1
31586 0x631 Alarm Phase C Status 6 0 65535 1 --- FC134 0 1
PHASE TOC2 ALARM STATUS
31590 0x635 0 65535 1 --- FC134 0 1
Phase51PTOC_2Alarm_Phas
eAStatus
31591 0x636 0 65535 1 --- FC134 0 1
Phase51PTOC_2Alarm_Phas
eBStatus
31592 0x637 0 65535 1 --- FC134 0 1
Phase51PTOC_2Alarm_Phas
eCStatus
PHASE OV 2 ALARM STATUS
31593 0x638 0 65535 1 --- FC134 0 1
PhaseOV2Alarm_PhaseAStat
us
31594 0x639 0 65535 1 --- FC134 0 1
PhaseOV2Alarm_PhaseBStat
us
31595 0x63A 0 65535 1 --- FC134 0 1
PhaseOV2Alarm_PhaseCStat
us
PHASE UV 2 ALARM STATUS
31596 0x63B 0 65535 1 --- FC134 0 1
PhaseUV2Alarm_PhaseAStat
us
31597 0x63C 0 65535 1 --- FC134 0 1
PhaseUV2Alarm_PhaseBStat
us
31598 0x63D 0 65535 1 --- FC134 0 1
PhaseUV2Alarm_PhaseCStat
us

10-16 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
VOLTAGE METERING
30358 0x165 Vab Voltage 0 65535 1 V F1 0 1
30359 0x166 Vbc Voltage 0 65535 1 V F1 0 1
30360 0x167 Vca Voltage 0 65535 1 V F1 0 1
30361 0x168 Average Line Voltage 0 65535 1 V F1 0 1
30362 0x169 Van Voltage 0 65535 1 V F1 0 1
30363 0x16A Vbn Voltage 0 65535 1 V F1 0 1
30364 0x16B Vcn Voltage 0 65535 1 V F1 0 1
30365 0x16C Average Phase Voltage 0 65535 1 V F1 0 1
30366 0x16D Frequency 0 12000 1 Hz F3 0 1
31746 0x6D1 Vab Voltage (32 bits) 0 0xFFFF 1 V F9 0 2
31748 0x6D3 Vbc Voltage (32 bits) 0 0xFFFF 1 V F9 0 2
31750 0x6D5 Vca Voltage (32 bits) 0 0xFFFF 1 V F9 0 2
31752 0x6D7 Van Voltage (32 bits) 0 0xFFFF 1 V F9 0 2
31754 0x6D9 Vbn Voltage (32 bits) 0 0xFFFF 1 V F9 0 2
31756 0x6DB Vcn Voltage (32 bits) 0 0xFFFF 1 V F9 0 2
31758 0x6DD Vn Voltage (32 bits) 0 0xFFFF 1 V F9 0 2
31760 0x6DF VAux Voltage (32 bits) 0 0xFFFF 1 V F9 0 2
31762 0x6E1 Positive Sequence Voltage 0 0xFFFF 1 V F9 0 2
(32 bits)
31764 0x6E3 Negative Sequence Voltage 0 0xFFFF 1 V F9 0 2
(32 bits)
31766 0x6E5 Zero Sequence Voltage (32 0 0xFFFF 1 V F9 0 2
bits)
31768 0x6E7 0 65535 1 V F9 0 2
31770 0x6E9 0 65535 1 V F9 0 2
TRANSIENT RECORDER
30707 0x2C2 Transient Recorder Last 0x010107D8 0X0C1F082E 0 --- F18 2
Cleared 0x010107D
8
30709 0x2C4 Transient Recorder Available 0 6 1 --- F1 0 1
Records
30710 0x2C5 Trace Memory Trigger Date 0x010107D8 0X0C1F082E 0 --- F18 2
0x010107D
8
30712 0x2C7 Trace Memory Trigger Time 0 0X173BEA5F 0 --- F19 0 2
30714 0x2C9 Trace Memory Trigger 0 0xD002 0 --- FC133 0 1
Cause
30715 0x2CA Trace Memory Trigger 0 12000 1 Hz F3 60 1
Frequency
30716 0x2CB Total Triggers 0 0xFFFF 1 --- F1 0 1
30718 0x2CD Trigger Position (Actual 0 6143 1 --- F1 25 1
Value)
30719 0x2CE Trace Memory Start Index 0 6143 1 --- F1 0 1
31773 0x6EC Transient Sampling Rate 0 3 1 --- FC429 0 1
Status
FAULT REPORT
31775 0x6EE Fault Report Date 0x010107D9 0x0C1F0833 0 --- F18 2
0x010107D
9
31777 0x6F0 Fault Report Time 0 0X173BEA5F 0 --- F19 0 2

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-17


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
31779 0x6F2 Fault Report Fault Type 0 2 1 --- FC134C 0 1
31780 0x6F3 Fault Report Ia 0 1200000 1 A F10 0 2
31782 0x6F5 Fault Report Ia Angle 0 359 1 ° F1 0 1
31783 0x6F6 Fault Report Ib 0 1200000 1 A F10 0 2
31785 0x6F8 Fault Report Ib Angle 0 359 1 ° F1 0 1
31786 0x6F9 Fault Report Ic 0 1200000 1 A F10 0 2
31788 0x6FB Fault Report Ic Angle 0 359 1 ° F1 0 1
31789 0x6FC Fault Report Ig 0 1200000 1 A F10 0 2
31791 0x6FE Fault Report Ig Angle 0 359 1 ° F1 0 1
31792 0x6FF Fault Report In 0 100000 1 A F10 0 2
31794 0x701 Fault Report In Angle 0 359 1 ° F1 0 1
31795 0x702 Fault Report Va 0 65535 1 V F9 0 2
31797 0x704 Fault Report Va Angle 0 359 1 ° F1 0 1
31798 0x705 Fault Report Vb 0 65535 1 V F9 0 2
31800 0x707 Fault Report Vb Angle 0 359 1 ° F1 0 1
31801 0x708 Fault Report Vc 0 65535 1 V F9 0 2
31803 0x70A Fault Report Vc Angle 0 359 1 ° F1 0 1
31804 0x70B Fault Report Vab 0 0xFFFF 1 V F9 0 2
31806 0x70D Fault Report Vab Angle 0 359 1 ° F1 0 1
31807 0x70E Fault Report Vbc 0 0xFFFF 1 V F9 0 2
31809 0x710 Fault Report Vbc Angle 0 359 1 ° F1 0 1
31810 0x711 Fault Report Vca 0 0xFFFF 1 V F9 0 2
31812 0x713 Fault Report Vca Angle 0 359 1 ° F1 0 1
31813 0x714 Fault Report Vn 0 65535 1 V F9 0 2
31815 0x716 Fault Report Vn Angle 0 359 1 ° F1 0 1
31816 0x717 Fault Report Vaux 0 65535 1 V F9 0 2
31818 0x719 Fault Report Vaux Angle 0 359 1 ° F1 0 1
31853 0x73C Fault Report Phases 1 7 1 --- F37 1 1
31854 0x73D Fault Report Firmware 0 0xFFFF 1 --- F3 220 1
Version
31855 0x73E Fault Report Order Code 0 16 1 --- F22 339- 12
CP5G5HISS
XXS
31867 0x74A Fault Report Feeder Name 0 10 1 --- F22 Motor 10
Name
DIRECTIONAL POWER
31739 0x6CA Directional Power 1 -1000000 1000000 1 kW F13 0 2
31741 0x6CC Directional Power 2 -1000000 1000000 1 kW F13 0 2
31880 0x757 Directional Power 1 -1000 1000 1 MW F13 0 2
31882 0x759 Directional Power 2 -1000 1000 1 MW F13 0 2
DEVICE STATUS
30302 0x12D Current Security Access 0 3 1 --- F1 0 1
Level
30305 0x130 Device Status 0 0xFFFF 1 --- FC129 0 1
30306 0x131 Extended Status 0 0xFFFF 1 --- FC178 0 1
30307 0x132 Thermal Capacity Used 0 100 1 % F1 0 1
30308 0x133 Time to Overload Trip -1 99999 1 s F20 -1 2
30319 0x13E Relay1 Coil Status 0 1 1 --- FC125 0 1

10-18 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30320 0x13F Relay2 Coil Status 0 1 1 --- FC125 0 1
31887 0x75E Breaker Health 0 100000 1 --- F9 0 2
31889 0x760 Breaker Last Trip Time 0 10000 1 ms F1 0 1
31890 0x761 Breaker Avg Trip Time 0 10000 1 ms F1 0 1
31891 0x762 Breaker Last Close Time 0 10000 1 ms F1 0 1
31892 0x763 Breaker Avg Close Time 0 10000 1 ms F1 0 1
31893 0x764 Breaker Last Charge Time 0 60000 1 ms F1 0 1
31894 0x765 Breaker Avg Charge Time 0 60000 1 ms F1 0 1
ENHANCED LEARNED DATA
32010 0x7D9 Number of Records 0 65535 1 --- F1 0 1
32011 0x7DA Date of Record 0x010107D8 0x0C1F082E 1 --- F18 2
0x010107D
8
32013 0x7DC Learned Acceleration Time 0 65535 1 s F2 0 1
32014 0x7DD Learned Starting Current 0 1200000 1 A F10 0 2
32016 0x7DF Learned Starting Capacity 0 100 1 % F1 0 1
32017 0x7E0 Last Starting Current 0 1200000 1 A F10 0 2
32019 0x7E2 Last Starting Capacity 0 100 1 % F1 0 1
32020 0x7E3 Last Acceleration Time 0 65535 1 s F2 0 1
32021 0x7E4 Learned Motor Load 0 30000 1 x FLA F3 0 1
32022 0x7E5 Learned Run Time After 0 65535 1 days F1 0 1
Start (days)
32023 0x7E6 Learned Run Time After 0 1339 1 min F1 0 1
Start (minutes)
MOTOR START DATA LOGGER
32040 0x7F7 Motor Data Log Number Of 0 0xFFFF 1 --- F1 0 1
Triggers
32041 0x7F8 Motor Data Log Number Of 0 0xFFFF 1 --- F1 0 1
Samples Stored
32042 0x7F9 Motor Data Log Start Index 0 0xFFFF 1 --- F1 0 1
32043 0x7FA Motor Data Log Trigger -32767 32767 1 --- F4 0 1
Index
32044 0x7FB Motor Data Log Trigger 0 0xFFFF 1 --- F1 0 1
Cause
32045 0x7FC Motor Data Log Trigger Date 0x010107D8 0X0C1F082E 1 --- F18 2
0x010107D
8
32047 0x7FE Motor Data Log Trigger 0 0X173BEA5F 1 --- F19 0 2
Time
32049 0x800 Motor Data Log Status 0 4 1 --- F75 0 1
32050 0x801 Motor Data Log Num Buffers 0 6 1 --- F1 0 1
Available
32060 0x80B Motor Data Log Sample 0 -32767 32767 0 --- F4 1 1
32061 0x80C Motor Data Log Sample 1 -32767 32767 0 --- F4 1 1
32062 0x80D Motor Data Log Sample 2 -32767 32767 0 --- F4 1 1
32063 0x80E Motor Data Log Sample 3 -32767 32767 0 --- F4 1 1
32064 0x80F Motor Data Log Sample 4 -32767 32767 0 --- F4 1 1
32065 0x810 Motor Data Log Sample 5 -32767 32767 0 --- F4 1 1
32066 0x811 Motor Data Log Sample 6 -32767 32767 0 --- F4 1 1
32067 0x812 Motor Data Log Sample 7 -32767 32767 0 --- F4 1 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-19


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
32068 0x813 Motor Data Log Sample 8 -32767 32767 0 --- F4 1 1
32069 0x814 Motor Data Log Sample 9 -32767 32767 0 --- F4 1 1
32070 0x815 Motor Data Log Sample 10 -32767 32767 0 --- F4 1 1
32071 0x816 Motor Data Log Sample 11 -32767 32767 0 --- F4 1 1
32072 0x817 Motor Data Log Sample 12 -32767 32767 0 --- F4 1 1
32073 0x818 Motor Data Log Sample 13 -32767 32767 0 --- F4 1 1
32074 0x819 Motor Data Log Sample 14 -32767 32767 0 --- F4 1 1
32075 0x81A Motor Data Log Sample 15 -32767 32767 0 --- F4 1 1
32076 0x81B Motor Data Log Sample 16 -32767 32767 0 --- F4 1 1
32077 0x81C Motor Data Log Sample 17 -32767 32767 0 --- F4 1 1
32078 0x81D Motor Data Log Sample 18 -32767 32767 0 --- F4 1 1
32079 0x81E Motor Data Log Sample 19 -32767 32767 0 --- F4 1 1
32080 0x81F Motor Data Log Sample 20 -32767 32767 0 --- F4 1 1
32081 0x820 Motor Data Log Sample 21 -32767 32767 0 --- F4 1 1
32082 0x821 Motor Data Log Sample 22 -32767 32767 0 --- F4 1 1
32083 0x822 Motor Data Log Sample 23 -32767 32767 0 --- F4 1 1
32084 0x823 Motor Data Log Sample 24 -32767 32767 0 --- F4 1 1
32085 0x824 Motor Data Log Sample 25 -32767 32767 0 --- F4 1 1
32086 0x825 Motor Data Log Sample 26 -32767 32767 0 --- F4 1 1
32087 0x826 Motor Data Log Sample 27 -32767 32767 0 --- F4 1 1
32088 0x827 Motor Data Log Sample 28 -32767 32767 0 --- F4 1 1
32089 0x828 Motor Data Log Sample 29 -32767 32767 0 --- F4 1 1
32090 0x829 Motor Data Log Sample 30 -32767 32767 0 --- F4 1 1
32091 0x82A Motor Data Log Sample 31 -32767 32767 0 --- F4 1 1
32092 0x82B Motor Data Log Sample 32 -32767 32767 0 --- F4 1 1
32093 0x82C Motor Data Log Sample 33 -32767 32767 0 --- F4 1 1
32094 0x82D Motor Data Log Sample 34 -32767 32767 0 --- F4 1 1
32095 0x82E Motor Data Log Sample 35 -32767 32767 0 --- F4 1 1
32096 0x82F Motor Data Log Sample 36 -32767 32767 0 --- F4 1 1
32097 0x830 Motor Data Log Sample 37 -32767 32767 0 --- F4 1 1
32098 0x831 Motor Data Log Sample 38 -32767 32767 0 --- F4 1 1
32099 0x832 Motor Data Log Sample 39 -32767 32767 0 --- F4 1 1
32100 0x833 Motor Data Log Sample 40 -32767 32767 0 --- F4 1 1
32101 0x834 Motor Data Log Sample 41 -32767 32767 0 --- F4 1 1
32102 0x835 Motor Data Log Sample 42 -32767 32767 0 --- F4 1 1
32103 0x836 Motor Data Log Sample 43 -32767 32767 0 --- F4 1 1
32104 0x837 Motor Data Log Sample 44 -32767 32767 0 --- F4 1 1
32105 0x838 Motor Data Log Sample 45 -32767 32767 0 --- F4 1 1
32106 0x839 Motor Data Log Sample 46 -32767 32767 0 --- F4 1 1
32107 0x83A Motor Data Log Sample 47 -32767 32767 0 --- F4 1 1
32108 0x83B Motor Data Log Sample 48 -32767 32767 0 --- F4 1 1
32109 0x83C Motor Data Log Sample 49 -32767 32767 0 --- F4 1 1
32110 0x83D Motor Data Log Sample 50 -32767 32767 0 --- F4 1 1
32111 0x83E Motor Data Log Sample 51 -32767 32767 0 --- F4 1 1
32112 0x83F Motor Data Log Sample 52 -32767 32767 0 --- F4 1 1
32113 0x840 Motor Data Log Sample 53 -32767 32767 0 --- F4 1 1

10-20 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
32114 0x841 Motor Data Log Sample 54 -32767 32767 0 --- F4 1 1
32115 0x842 Motor Data Log Sample 55 -32767 32767 0 --- F4 1 1
32116 0x843 Motor Data Log Sample 56 -32767 32767 0 --- F4 1 1
32117 0x844 Motor Data Log Sample 57 -32767 32767 0 --- F4 1 1
32118 0x845 Motor Data Log Sample 58 -32767 32767 0 --- F4 1 1
32119 0x846 Motor Data Log Sample 59 -32767 32767 0 --- F4 1 1
32120 0x847 Motor Data Log Sample 60 -32767 32767 0 --- F4 1 1
32121 0x848 Motor Data Log Sample 61 -32767 32767 0 --- F4 1 1
32122 0x849 Motor Data Log Sample 62 -32767 32767 0 --- F4 1 1
32123 0x84A Motor Data Log Sample 63 -32767 32767 0 --- F4 1 1
DEMAND
32170 0x879 Current Demand 1 Last Rst 0x010107D9 0x0C1F0833 0 --- F18 2
Date 0x010107D
9
32172 0x87B Current Demand 1 Last Rst 0 0X173BEA5F 0 --- F19 0 2
Time
32174 0x87D Current Demand 1 PhA 0 300000 1 A F10 0 2
32176 0x87F Current Demand 1 PhB 0 300000 1 A F10 0 2
32178 0x881 Current Demand 1 PhC 0 300000 1 A F10 0 2
32180 0x883 Max Current Demand 1 PhA 0 300000 1 A F10 0 2
32182 0x885 Max Current Demand 1 PhB 0 300000 1 A F10 0 2
32184 0x887 Max Current Demand 1 PhC 0 300000 1 A F10 0 2
32186 0x889 Current Demand 1 PhA Date 0x010107D9 0x0C1F0833 0 --- F18 2
0x010107D
9
32188 0x88B Current Demand 1 PhB Date 0x010107D9 0x0C1F0833 0 --- F18 2
0x010107D
9
32190 0x88D Current Demand 1 PhC Date 0x010107D9 0x0C1F0833 0 --- F18 2
0x010107D
9
32192 0x88F Current Demand 1 PhA Time 0 0X173BEA5F 0 --- F19 0 2
32194 0x891 Current Demand 1 PhB Time 0 0X173BEA5F 0 --- F19 0 2
32196 0x893 Current Demand 1 PhC Time 0 0X173BEA5F 0 --- F19 0 2
32226 0x8B1 Power Demand Last Rst 0x010107D9 0x0C1F0833 0 --- F18 2
Date 0x010107D
9
32228 0x8B3 Power Demand Last Rst 0 0X173BEA5F 0 --- F19 0 2
Time
32230 0x8B5 Real Power Demand 0 1000000 1 kW F10 0 2
32232 0x8B7 Reactive Power Demand 0 1000000 1 kvar F10 0 2
32234 0x8B9 Apparent Power Demand 0 1000000 1 kVA F10 0 2
32236 0x8BB Max Real Power Demand 0 1000000 1 kW F10 0 2
32238 0x8BD Max Reactive Power 0 1000000 1 kvar F10 0 2
Demand
32240 0x8BF Max Apparent Power 0 1000000 1 kVA F10 0 2
Demand
32242 0x8C1 Real Power Demand Date 0x010107D9 0x0C1F0833 0 --- F18 2
0x010107D
9
32244 0x8C3 Reactive Power Demand 0x010107D9 0x0C1F0833 0 --- F18 2
Date 0x010107D
9

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-21


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
32246 0x8C5 Apparent Power Demand 0x010107D9 0x0C1F0833 0 --- F18 2
Date 0x010107D
9
32248 0x8C7 Real Power Demand Time 0 0X173BEA5F 0 --- F19 0 2
32250 0x8C9 Reactive Power Demand 0 0X173BEA5F 0 --- F19 0 2
Time
32252 0x8CB Apparent Power Demand 0 0X173BEA5F 0 --- F19 0 2
Time
SETPOINTS
MESSAGE TIMES
40120 0x77 Flash Message Time 1 65535 1 s F1 5 1
40121 0x78 Message Timeout 1 65535 1 s F1 30 1
COMMANDS
40129 0x80 Command address 0 0xFFFF 0 --- F1 0 1
40130 0x81 Command Function 0 0xFFFF 0 --- F1 0 1
40131 0x82 Command Data 1 0 0xFFFF 0 --- F1 0 1
40132 0x83 Command Data 2 0 0xFFFF 0 --- F1 0 1
40133 0x84 Command Data 3 0 0xFFFF 0 --- F1 0 1
40134 0x85 Command Data 4 0 0xFFFF 0 --- F1 0 1
40135 0x86 Command Data 5 0 0xFFFF 0 --- F1 0 1
40136 0x87 Command Data 6 0 0xFFFF 0 --- F1 0 1
40137 0x88 Command Data 7 0 0xFFFF 0 --- F1 0 1
40138 0x89 Command Data 8 0 0xFFFF 0 --- F1 0 1
40139 0x8A Command Data 9 0 0xFFFF 0 --- F1 0 1
40140 0x8B Command Data 10 0 0xFFFF 0 --- F1 0 1
RS485 COMMUNICATIONS
40172 0xAB Slave Address 1 254 1 --- F1 254 1
40173 0xAC RS485 Baud Rate 0 4 1 --- FC101 4 1
40174 0xAD RS485 Parity 0 2 1 --- FC102 0 1
40175 0xAE Rear 485 Port Protocol 0 2 1 --- F97 0 1
ETHERNET COMMUNICATIONS
40180 0xB3 SNTP Mode 0 3 1 --- FC100 0 1
40181 0xB4 SNTP IP Address 0 0xFFFFFFFF 1 --- FC150 0 2
40183 0xB6 Ethernet IP address 0 0xFFFFFFFF 1 --- FC150 0 2
40185 0xB8 Ethernet subnet mask 0 0xFFFFFFFF 1 --- FC150 2
0xFFFFFC00
40187 0xBA Ethernet gateway address 0 0xFFFFFFFF 1 --- FC150 0 2
40189 0xBC SNTP Port 0 65535 1 --- F1 0 1
40191 0xBE Ethernet ConnectionType 0 1 1 --- FC230 0 1
40194 0xC1 High Eth Message Enable 0 1 1 --- FC126 1 1
REAL-TIME CLOCK
40228 0xE3 Set Date 0x010107D9 0x0C1F0833 0 --- F18 2
0x010107D
9
40230 0xE5 Set Time 0 0X173BEA5F 0 --- F19 0 2
40232 0xE7 Time Offset From UTC -2400 2400 25 hrs F6 0 1
40233 0xE8 IRIG-B 0 1 1 --- FC126 0 1
40234 0xE9 Daylight Savings 0 1 1 --- FC126 0 1

10-22 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
40235 0xEA DST Start Month 0 12 1 --- FC169 0 1
40236 0xEB DST Start Week 0 5 1 --- FC170 0 1
40237 0xEC DST Start Weekday 0 7 1 --- FC171 0 1
40238 0xED DST End Month 0 12 1 --- FC169 0 1
40239 0xEE DST End Week 0 5 1 --- FC170 0 1
40240 0xEF DST End Weekday 0 7 1 --- FC171 0 1
REMOTE INPUTS
40260 0x103 Remote Inputs 0 0xFFFFFFFF 1 --- FC167 0 2
CURRENT SENSING
40267 0x10A CT Primary 10 5000 1 A F1 100 1
40268 0x10B Ground CT Secondary 0 2 1 --- FC104 2 1
40269 0x10C High Speed CT Primary 10 5000 1 A F1 100 1
40271 0x10E Ground CT Primary 10 5000 1 A F1 100 1
40273 0x110 Phase CT Secondary 0 1 1 --- FC415 1 1
VOLTAGE SENSING
40276 0x113 3 Phase Voltage Connection 0 1 1 --- FC106 0 1
40281 0x118 Bus VT Secondary 50 240 1 V F1 120 1
40282 0x119 Bus VT Ratio 10 3000 1 1 F2 10 1
POWER SYSTEM
40284 0x11B Supply Frequency 0 1 1 Hz FC107 0 1
40285 0x11C Relay Name 0 9 1 --- F22 Motor 9
Name
40295 0x126 Power Unit 0 1 1 --- FC430 0 1
40296 0x127 Phase Sequence 0 1 1 --- FC124A 0 1
40298 0x129 Motor FLA 50 50000 1 A F2 1000 1
40299 0x12A High Speed FLA 50 50000 1 A F2 1000 1
40300 0x12B Bus Voltage 100 20000 1 V F1 3000 1
MOTOR
40308 0x133 Feeder Rating 100 10000 1 kW F1 3000 1
40309 0x134 High Speed Motor Rating 100 10000 1 kW F1 3000 1
SWITCHING DEVICE
40310 0x135 Switching Device 0 1 1 --- FC235 0 1
ENABLE TWO-SPEED MOTOR
40311 0x136 Enable Two Speed 0 1 1 --- FC126 0 1
VFD
40314 0x139 VFD Function 0 1 1 --- FC126 0 1
40315 0x13A VFD Bypass Switch 0 0xEF02 1 --- F89 0 1
PRESET STATISTICS
40330 0x149 Set Number of Motor Starts 0 50000 1 --- F1 0 1
40331 0x14A Set Number of Emergency 0 50000 1 --- F1 0 1
Restarts
40332 0x14B Preset Motor Running Hours 0 65535 1 --- F1 0 1
USER MAP ADDRESSES
40524 0x20B User Map Address 1 30001 39999 1 --- F1 30305 1
40525 0x20C User Map Address 2 30001 39999 1 --- F1 30505 1
40526 0x20D User Map Address 3 30001 39999 1 --- F1 30506 1
40527 0x20E User Map Address 4 30001 39999 1 --- F1 30960 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-23


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
40528 0x20F User Map Address 5 30001 39999 1 --- F1 30961 1
40529 0x210 User Map Address 6 30001 39999 1 --- F1 30958 1
40530 0x211 User Map Address 7 30001 39999 1 --- F1 30959 1
40531 0x212 User Map Address 8 30001 39999 1 --- F1 30956 1
40532 0x213 User Map Address 9 30001 39999 1 --- F1 30957 1
40533 0x214 User Map Address 10 30001 39999 1 --- F1 30954 1
40534 0x215 User Map Address 11 30001 39999 1 --- F1 30955 1
40535 0x216 User Map Address 12 30001 39999 1 --- F1 30952 1
40536 0x217 User Map Address 13 30001 39999 1 --- F1 30953 1
40537 0x218 User Map Address 14 30001 39999 1 --- F1 30950 1
40538 0x219 User Map Address 15 30001 39999 1 --- F1 30951 1
40539 0x21A User Map Address 16 30001 39999 1 --- F1 30948 1
40540 0x21B User Map Address 17 30001 39999 1 --- F1 30949 1
40541 0x21C User Map Address 18 30001 39999 1 --- F1 30946 1
40542 0x21D User Map Address 19 30001 39999 1 --- F1 30947 1
40543 0x21E User Map Address 20 30001 39999 1 --- F1 30976 1
40544 0x21F User Map Address 21 30001 39999 1 --- F1 30977 1
40545 0x220 User Map Address 22 30001 39999 1 --- F1 30974 1
40546 0x221 User Map Address 23 30001 39999 1 --- F1 30975 1
40547 0x222 User Map Address 24 30001 39999 1 --- F1 30972 1
40548 0x223 User Map Address 25 30001 39999 1 --- F1 30973 1
40549 0x224 User Map Address 26 30001 39999 1 --- F1 30970 1
40550 0x225 User Map Address 27 30001 39999 1 --- F1 30971 1
40551 0x226 User Map Address 28 30001 39999 1 --- F1 30984 1
40552 0x227 User Map Address 29 30001 39999 1 --- F1 30985 1
40553 0x228 User Map Address 30 30001 39999 1 --- F1 30982 1
40554 0x229 User Map Address 31 30001 39999 1 --- F1 30983 1
40555 0x22A User Map Address 32 30001 39999 1 --- F1 30980 1
40556 0x22B User Map Address 33 30001 39999 1 --- F1 30981 1
40557 0x22C User Map Address 34 30001 39999 1 --- F1 30978 1
40558 0x22D User Map Address 35 30001 39999 1 --- F1 30979 1
40559 0x22E User Map Address 36 30001 39999 1 --- F1 30186 1
40560 0x22F User Map Address 37 30001 39999 1 --- F1 30308 1
40561 0x230 User Map Address 38 30001 39999 1 --- F1 30309 1
40562 0x231 User Map Address 39 30001 39999 1 --- F1 30313 1
40563 0x232 User Map Address 40 30001 39999 1 --- F1 30307 1
40564 0x233 User Map Address 41 30001 39999 1 --- F1 30336 1
40565 0x234 User Map Address 42 30001 39999 1 --- F1 30285 1
40566 0x235 User Map Address 43 30001 39999 1 --- F1 30286 1
40567 0x236 User Map Address 44 30001 39999 1 --- F1 30298 1
40568 0x237 User Map Address 45 30001 39999 1 --- F1 30299 1
40569 0x238 User Map Address 46 30001 39999 1 --- F1 30288 1
40570 0x239 User Map Address 47 30001 39999 1 --- F1 30289 1
40571 0x23A User Map Address 48 30001 39999 1 --- F1 30257 1
40572 0x23B User Map Address 49 30001 39999 1 --- F1 30291 1
40573 0x23C User Map Address 50 30001 39999 1 --- F1 30296 1

10-24 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
40574 0x23D User Map Address 51 30001 39999 1 --- F1 30297 1
40575 0x23E User Map Address 52 30001 39999 1 --- F1 30300 1
40576 0x23F User Map Address 53 30001 39999 1 --- F1 30301 1
40577 0x240 User Map Address 54 30001 39999 1 --- F1 30192 1
40578 0x241 User Map Address 55 30001 39999 1 --- F1 30193 1
40579 0x242 User Map Address 56 30001 39999 1 --- F1 30194 1
40580 0x243 User Map Address 57 30001 39999 1 --- F1 30195 1
40581 0x244 User Map Address 58 30001 39999 1 --- F1 30196 1
40582 0x245 User Map Address 59 30001 39999 1 --- F1 30197 1
40583 0x246 User Map Address 60 30001 39999 1 --- F1 30328 1
40584 0x247 User Map Address 61 30001 39999 1 --- F1 30329 1
40585 0x248 User Map Address 62 30001 39999 1 --- F1 30330 1
40586 0x249 User Map Address 63 30001 39999 1 --- F1 30331 1
40587 0x24A User Map Address 64 30001 39999 1 --- F1 30332 1
40588 0x24B User Map Address 65 30001 39999 1 --- F1 30333 1
40589 0x24C User Map Address 66 30001 39999 1 --- F1 30326 1
40590 0x24D User Map Address 67 30001 39999 1 --- F1 30327 1
40591 0x24E User Map Address 68 30001 39999 1 --- F1 30334 1
40592 0x24F User Map Address 69 30001 39999 1 --- F1 30335 1
40593 0x250 User Map Address 70 30001 39999 1 --- F1 30338 1
40594 0x251 User Map Address 71 30001 39999 1 --- F1 30339 1
40595 0x252 User Map Address 72 30001 39999 1 --- F1 30324 1
40596 0x253 User Map Address 73 30001 39999 1 --- F1 30325 1
40597 0x254 User Map Address 74 30001 39999 1 --- F1 30319 1
40598 0x255 User Map Address 75 30001 39999 1 --- F1 30320 1
40599 0x256 User Map Address 76 30001 39999 1 --- F1 30429 1
40600 0x257 User Map Address 77 30001 39999 1 --- F1 30430 1
40601 0x258 User Map Address 78 30001 39999 1 --- F1 30431 1
40602 0x259 User Map Address 79 30001 39999 1 --- F1 30432 1
40603 0x25A User Map Address 80 30001 39999 1 --- F1 30433 1
40604 0x25B User Map Address 81 30001 39999 1 --- F1 30434 1
40605 0x25C User Map Address 82 30001 39999 1 --- F1 30420 1
40606 0x25D User Map Address 83 30001 39999 1 --- F1 30421 1
40607 0x25E User Map Address 84 30001 39999 1 --- F1 30422 1
40608 0x25F User Map Address 85 30001 39999 1 --- F1 30423 1
40609 0x260 User Map Address 86 30001 39999 1 --- F1 30424 1
40610 0x261 User Map Address 87 30001 39999 1 --- F1 30425 1
40611 0x262 User Map Address 88 30001 39999 1 --- F1 31746 1
40612 0x263 User Map Address 89 30001 39999 1 --- F1 31748 1
40613 0x264 User Map Address 90 30001 39999 1 --- F1 31750 1
40614 0x265 User Map Address 91 30001 39999 1 --- F1 31768 1
40615 0x266 User Map Address 92 30001 39999 1 --- F1 30366 1
40616 0x267 User Map Address 93 30001 39999 1 --- F1 30384 1
40617 0x268 User Map Address 94 30001 39999 1 --- F1 30385 1
40618 0x269 User Map Address 95 30001 39999 1 --- F1 30386 1
40619 0x26A User Map Address 96 30001 39999 1 --- F1 30389 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-25


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
40620 0x26B User Map Address 97 30001 39999 1 --- F1 30390 1
40621 0x26C User Map Address 98 30001 39999 1 --- F1 30406 1
40622 0x26D User Map Address 99 30001 39999 1 --- F1 30407 1
40623 0x26E User Map Address 100 30001 39999 1 --- F1 30001 1
40624 0x26F User Map Address 101 30001 39999 1 --- F1 30001 1
40625 0x270 User Map Address 102 30001 39999 1 --- F1 30001 1
40626 0x271 User Map Address 103 30001 39999 1 --- F1 30001 1
40627 0x272 User Map Address 104 30001 39999 1 --- F1 30001 1
40628 0x273 User Map Address 105 30001 39999 1 --- F1 30001 1
40629 0x274 User Map Address 106 30001 39999 1 --- F1 30001 1
40630 0x275 User Map Address 107 30001 39999 1 --- F1 30001 1
40631 0x276 User Map Address 108 30001 39999 1 --- F1 30001 1
40632 0x277 User Map Address 109 30001 39999 1 --- F1 30001 1
40633 0x278 User Map Address 110 30001 39999 1 --- F1 30001 1
40634 0x279 User Map Address 111 30001 39999 1 --- F1 30001 1
40635 0x27A User Map Address 112 30001 39999 1 --- F1 30001 1
40636 0x27B User Map Address 113 30001 39999 1 --- F1 30001 1
40637 0x27C User Map Address 114 30001 39999 1 --- F1 30001 1
40638 0x27D User Map Address 115 30001 39999 1 --- F1 30001 1
40639 0x27E User Map Address 116 30001 39999 1 --- F1 30001 1
40640 0x27F User Map Address 117 30001 39999 1 --- F1 30001 1
40641 0x280 User Map Address 118 30001 39999 1 --- F1 30001 1
40642 0x281 User Map Address 119 30001 39999 1 --- F1 30001 1
40643 0x282 User Map Address 120 30001 39999 1 --- F1 30001 1
40644 0x283 User Map Address 121 30001 39999 1 --- F1 30001 1
40645 0x284 User Map Address 122 30001 39999 1 --- F1 30001 1
40646 0x285 User Map Address 123 30001 39999 1 --- F1 30001 1
40647 0x286 User Map Address 124 30001 39999 1 --- F1 30001 1
40648 0x287 User Map Address 125 30001 39999 1 --- F1 30001 1
TRANSIENT RECORDER TRIGGERS
40650 0x289 Trigger On Input 1 0 0xEF02 1 --- F89A 0 1
40651 0x28A Trigger On Input 2 0 0xEF02 1 --- F89A 0 1
40652 0x28B Trigger On Input 3 0 0xEF02 1 --- F89A 0 1
EVENT RECORDER
40649 0x288 Recording of Block Events 0 1 1 --- FC126 1 1
40654 0x28D Recording of Pickup Events 0 1 1 --- FC126 0 1
40655 0x28E Recording of Contact Input 0 1 1 --- FC126 1 1
Events
40656 0x28F Recording of Virtual Input 0 1 1 --- FC126 1 1
Events
40657 0x290 Recording of Remote Inputs 0 1 1 --- FC126 1 1
40658 0x291 Recording of Logic Element 0 1 1 --- FC126 1 1
Events
40660 0x293 Recording of Trip Events 0 1 1 --- FC126 1 1
40661 0x294 Recording of Alarm Events 0 1 1 --- FC126 1 1
40662 0x295 Recording of Control Events 0 1 1 --- FC126 1 1
40665 0x298 Recording of Dropout Events 0 1 1 --- FC126 0 1

10-26 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
40666 0x299 Recording of Set Time/Date 0 1 1 --- FC126 0 1
Events
40667 0x29A Event Record Selector 1 65535 1 --- F1 1 1
DATA LOGGER
40680 0x2A7 Data Log Channel Selector -32767 32767 1 --- F4 0 1
40681 0x2A8 Data Log Sample Selector -32767 32767 1 --- F4 0 1
(DLSS)
40682 0x2A9 Sample Rate 0 3 1 --- F74 1 1
40683 0x2AA Continuous Mode 0 1 1 --- FC126 0 1
40685 0x2AC Data LoggerTrigger Position 0 100 1 % F1 25 1
40686 0x2AD Data Log Trigger Source 0 0xC942 1 --- FC133A 0 1
40687 0x2AE Channel 1 Source 0 35 1 --- F77 1 1
40688 0x2AF Channel 2 Source 0 35 1 --- F77 2 1
40689 0x2B0 Channel 3 Source 0 35 1 --- F77 3 1
40690 0x2B1 Channel 4 Source 0 35 1 --- F77 0 1
40691 0x2B2 Channel 5 Source 0 35 1 --- F77 0 1
40692 0x2B3 Channel 6 Source 0 35 1 --- F77 0 1
40693 0x2B4 Channel 7 Source 0 35 1 --- F77 0 1
40694 0x2B5 Channel 8 Source 0 35 1 --- F77 0 1
40695 0x2B6 Channel 9 Source 0 35 1 --- F77 0 1
40696 0x2B7 Channel 10 Source 0 35 1 --- F77 0 1
THERMAL PROTECTION
40698 0x2B9 Enable Thermal Model 0 1 1 --- FC126 0 1
40699 0x2BA Thermal O/L Curve 0 1 1 --- FC236 0 1
40700 0x2BB Start Thermal Protection 0 0x1DF 1 --- F89B 0 1
40701 0x2BC Thermal Alarm Enable 0 1 1 --- FC126 0 1
40702 0x2BD Overload Pickup Level 101 125 1 x FLA F3 101 1
40703 0x2BE Unbalance K Factor 0 19 1 --- F1 0 1
40704 0x2BF Cool Time Constant Running 1 1000 1 min F1 15 1
40705 0x2C0 Cool Time Constant Stopped 1 1000 1 min F1 30 1
40706 0x2C1 Hot/Cold Safe Stall Ratio 1 100 1 --- F3 85 1
40707 0x2C2 Thermal Capacity Alarm 10 100 1 % F1 75 1
Level
40708 0x2C3 Standard Overload Curve 1 15 1 --- F1 4 1
40710 0x2C5 RTD Bias - Minimum 0 130 1 °C F1 40 1
Temperature
40711 0x2C6 RTD Bias - Center 40 155 1 °C F1 110 1
Temperature
40712 0x2C7 RTD Bias - Maximum 130 250 1 °C F1 130 1
Temperature
40714 0x2C9 Overload Reset Mode 0 1 1 --- FC160 1 1
40715 0x2CA Locked Rotor Current 20 110 1 x FLA F2 60 1
40716 0x2CB Safe Stall Time Cold 10 6000 1 s F2 100 1
MECHANICAL JAM
40718 0x2CD Enable Mechanical Jam 0 1 1 --- FC126 0 1
40719 0x2CE Mechanical Jam Level 101 450 1 x FLA F3 450 1
40720 0x2CF Mechanical Jam Delay 10 3000 1 s F3 10 1
TEMPERATURE

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-27


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
40820 0x333 Enable Ambient Temp 0 2 1 --- FC206 0 1
40821 0x334 HI Alarm Level 20 80 1 °C F1 60 1
40822 0x335 Low Alarm Level -40 20 1 °C F4 10 1
40823 0x336 Hysteresis Level 2 10 1 °C F1 2 1
40824 0x337 Time Delay 1 60 1 min F1 1 1
40825 0x338 Output Relays 0 0x7F 1 --- FC198 0 1
UNDERCURRENT
40831 0x33E Enable Undercurrent Alarm 0 1 1 --- FC126 0 1
40832 0x33F Enable Undercurrent Trip 0 1 1 --- FC126 0 1
40833 0x340 BLK Undercurrent On Start 0 600 1 s F1 0 1
40834 0x341 Undercurrent Alarm Level 10 95 1 x FLA F3 70 1
40835 0x342 Undercurrent Alarm Delay 100 6000 1 s F3 100 1
40836 0x343 Undercurrent Trip Level 10 95 1 x FLA F3 60 1
40837 0x344 Undercurrent Trip Delay 100 6000 1 s F3 100 1
UNDERPOWER
40840 0x347 Enable Underpower Trip 0 1 1 --- FC126 0 1
40841 0x348 Enable Underpower Alarm 0 1 1 --- FC126 0 1
40842 0x349 Underpower Alarm Level 1 100 1 %MNR F1 70 1
40843 0x34A Underpower Alarm Delay 10 600 1 s F2 10 1
40844 0x34B Underpower Trip Level 1 100 1 %MNR F1 60 1
40845 0x34C Underpower Trip Delay 10 600 1 s F2 10 1
40846 0x34D Block Underpower on Start 0 600 1 s F1 0 1
ACCELERATION
40850 0x351 Accel Time Func 0 1 1 --- FC126 0 1
40852 0x353 Acceleration Trip Timer 10 2500 1 s F2 100 1
GROUND FAULT
40863 0x35E Enable Ground Fault Alarm 0 1 1 --- FC126 0 1
40864 0x35F Enable Ground Fault Trip 0 1 1 --- FC126 0 1
40865 0x360 Ground Alarm Level 3 100 1 x CT F3 10 1
40866 0x361 CBCT Ground Alarm Level 50 1500 1 A F3 1000 1
40867 0x362 Ground Alarm Delay On 0 6000 1 s F3 0 1
Start
40868 0x363 Ground Trip Level 3 100 1 x CT F3 10 1
40869 0x364 CBCT Ground Trip Level 50 1500 1 A F3 1000 1
40870 0x365 Ground Trip Delay On Start 0 1000 1 s F3 0 1
40871 0x366 Ground Alarm Delay On Run 0 6000 1 s F3 0 1
40872 0x367 Ground Trip Delay On Run 0 500 1 s F3 0 1
40874 0x369 Enable Load Increase Alarm 0 1 1 --- FC126 0 1
LOAD INCREASE
40875 0x36A Load Increase Alarm Level 50 150 1 %FLA F1 150 1
40876 0x36B Load Increase Alarm Delay 100 6000 1 s F3 150 1
CURRENT UNBALANCE
40855 0x356 Enable Current Unbalance 0 1 1 --- FC126 0 1
Alarm
40856 0x357 Enable Current Unbalance 0 1 1 --- FC126 0 1
Trip

10-28 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
40857 0x358 Current Unbalance Alarm 400 4000 1 % F3 1500 1
Level
40858 0x359 Current Unbalance Alarm 100 10000 1 s F3 100 1
Delay
40859 0x35A Current Unbalance Trip 400 4000 1 % F3 3000 1
Level
40860 0x35B Current Unbalance Trip 0 10000 1 s F3 1000 1
Delay
40880 0x36F Current Unbalance Trip 0 1 1 --- F93 0 1
Curve
40881 0x370 Current Unbalance Trip Max 0 100000 1 --- F11 100 2
Time
40883 0x372 Current Unbalance Trip Min 0 100000 1 --- F11 25 2
Time
40885 0x374 Current Unbalance Trip 0 100000 1 --- F11 100 2
Reset Time
TRANSIENT RECORDER
40668 0x29B Trigger on Pickup 0 1 1 --- FC103 0 1
40669 0x29C Trigger on Dropout 0 1 1 --- FC103 0 1
40670 0x29D Trigger on Alarm 0 1 1 --- FC103 0 1
40671 0x29E Trigger on Dropout 0 1 1 --- FC103 0 1
40672 0x29F Trace Memory Channel 0 16 1 --- F26A 0 1
Selector
40673 0x2A0 Trace Memory Buffer 0 10 1 --- F1 0 1
Selector
40674 0x2A1 Trace Memory Sample Index 0 6144 1 --- F1 0 1
40676 0x2A3 Trace Memory Trigger 0 100 1 % F1 20 1
Position
40677 0x2A4 Trigger Mode 0 1 1 --- FC148 0 1
40678 0x2A5 Number of Records 0 2 1 --- F95 0 1
40887 0x376 Transient Sampling Rate 0 3 1 --- FC429 0 1
PHASE REVERSAL
40903 0x386 Voltage Phase Reversal 0 2 1 --- FC140 0 1
VT FUSE FAIL
40908 0x38B VT Fuse Fail 0 2 1 --- FC140 0 1
MOTOR RUNNING HOURS
40910 0x38D Motor Running Hours Alarm 0 1 1 --- FC126 0 1
40911 0x38E Motor Running Hours Limit 0 65535 1 hrs F1 0 1
START INHIBITS
40917 0x394 Start Inhibit Margin 0 26 1 % F1B 10 1
40919 0x396 Starts/Hour Limit 1 6 1 --- F1B 6 1
40920 0x397 Time Between Starts 1 3601 1 s F1B 3601 1
40921 0x398 Start Inhibit Relays 0 0x7F 1 --- FC198 4 1
40926 0x39D Restart Block Time 1 50001 1 s F1B 50001 1
RELAY STATUS
40927 0x39E Relay Status 0 1 1 --- F99 0 1
SHORT CIRCUIT
40948 0x3B3 Short Circuit Function 0 3 1 --- FC197 0 1
40949 0x3B4 Short Circuit Pickup 100 2000 1 x CT F3 600 1
40950 0x3B5 Short Circuit Delay 0 6000 1 s F3 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-29


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
CONTACT INPUT NAMES (1 TO 8)
40961 0x3C0 Input Name 1 0 7 1 --- F22 52a 7
Contact
40970 0x3C9 Input Name 2 0 7 1 --- F22 52b 7
Contact
40979 0x3D2 Input Name 3 0 7 1 --- F22 Input 3 7
40988 0x3DB Input Name 4 0 7 1 --- F22 Input 4 7
40997 0x3E4 Input Name 5 0 7 1 --- F22 Input 5 7
41006 0x3ED Input Name 6 0 7 1 --- F22 Input 6 7
41015 0x3F6 Input Name 7 0 7 1 --- F22 Input 7 7
41024 0x3FF Input Name 8 0 7 1 --- F22 Input 8 7
LOGIC ELEMENTS
41118 0x45D Timer 1 Pickup Delay 0 60000 1 ms F1 0 1
41119 0x45E Timer 1 Dropout Delay 0 60000 1 ms F1 0 1
41120 0x45F Logic Element 1 Function 0 4 1 --- FC205 0 1
41121 0x460 Logic Element 1 Asserted 0 1 1 --- FC103 0 1
41122 0x461 Logic Element 1 Relay 0 0x7F 1 --- FC198 0 1
41126 0x465 Timer 2 Pickup Delay 0 60000 1 ms F1 0 1
41127 0x466 Timer 2 Dropout Delay 0 60000 1 ms F1 0 1
41128 0x467 Logic Element 2 Function 0 4 1 --- FC205 0 1
41129 0x468 Logic Element 2 Asserted 0 1 1 --- FC103 0 1
41130 0x469 Logic Element 2 Relay 0 0x7F 1 --- FC198 0 1
41134 0x46D Timer 3 Pickup Delay 0 60000 1 ms F1 0 1
41135 0x46E Timer 3 Dropout Delay 0 60000 1 ms F1 0 1
41136 0x46F Logic Element 3 Function 0 4 1 --- FC205 0 1
41137 0x470 Logic Element 3 Asserted 0 1 1 --- FC103 0 1
41138 0x471 Logic Element 3 Relay 0 0x7F 1 --- FC198 0 1
41142 0x475 Timer 4 Pickup Delay 0 60000 1 ms F1 0 1
41143 0x476 Timer 4 Dropout Delay 0 60000 1 ms F1 0 1
41144 0x477 Logic Element 4 Function 0 4 1 --- FC205 0 1
41145 0x478 Logic Element 4 Asserted 0 1 1 --- FC103 0 1
41146 0x479 Logic Element 4 Relay 0 0x7F 1 --- FC198 0 1
41150 0x47D Timer 5 Pickup Delay 0 60000 1 ms F1 0 1
41151 0x47E Timer 5 Dropout Delay 0 60000 1 ms F1 0 1
41152 0x47F Logic Element 5 Function 0 4 1 --- FC205 0 1
41153 0x480 Logic Element 5 Asserted 0 1 1 --- FC103 0 1
41154 0x481 Logic Element 5 Relay 0 0x7F 1 --- FC198 0 1
41158 0x485 Timer 6 Pickup Delay 0 60000 1 ms F1 0 1
41159 0x486 Timer 6 Dropout Delay 0 60000 1 ms F1 0 1
41160 0x487 Logic Element 6 Function 0 4 1 --- FC205 0 1
41161 0x488 Logic Element 6 Asserted 0 1 1 --- FC103 0 1
41162 0x489 Logic Element 6 Relay 0 0x7F 1 --- FC198 0 1
41166 0x48D Timer 7 Pickup Delay 0 60000 1 ms F1 0 1
41167 0x48E Timer 7 Dropout Delay 0 60000 1 ms F1 0 1
41168 0x48F Logic Element 7 Function 0 4 1 --- FC205 0 1
41169 0x490 Logic Element 7 Asserted 0 1 1 --- FC103 0 1
41170 0x491 Logic Element 7 Relay 0 0x7F 1 --- FC198 0 1

10-30 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
41174 0x495 Timer 8 Pickup Delay 0 60000 1 ms F1 0 1
41175 0x496 Timer 8 Dropout Delay 0 60000 1 ms F1 0 1
41176 0x497 Logic Element 8 Function 0 4 1 --- FC205 0 1
41177 0x498 Logic Element 8 Asserted 0 1 1 --- FC103 0 1
41178 0x499 Logic Element 8 Relay 0 0x7F 1 --- FC198 0 1
41182 0x49D Timer 9 Pickup Delay 0 60000 1 ms F1 0 1
41183 0x49E Timer 9 Dropout Delay 0 60000 1 ms F1 0 1
41184 0x49F Logic Element 9 Function 0 4 1 --- FC205 0 1
41185 0x4A0 Logic Element 9 Asserted 0 1 1 --- FC103 0 1
41186 0x4A1 Logic Element 9 Relay 0 0x7F 1 --- FC198 0 1
41190 0x4A5 Timer 10 Pickup Delay 0 60000 1 ms F1 0 1
41191 0x4A6 Timer 10 Dropout Delay 0 60000 1 ms F1 0 1
41192 0x4A7 Logic Element 10 Function 0 4 1 --- FC205 0 1
41193 0x4A8 Logic Element 10 Asserted 0 1 1 --- FC103 0 1
41194 0x4A9 Logic Element 10 Relay 0 0x7F 1 --- FC198 0 1
41198 0x4AD Timer 11 Pickup Delay 0 60000 1 ms F1 0 1
41199 0x4AE Timer 11 Dropout Delay 0 60000 1 ms F1 0 1
41200 0x4AF Logic Element 11 Function 0 4 1 --- FC205 0 1
41201 0x4B0 Logic Element 11 Asserted 0 1 1 --- FC103 0 1
41202 0x4B1 Logic Element 11 Relay 0 0x7F 1 --- FC198 0 1
41206 0x4B5 Timer 12 Pickup Delay 0 60000 1 ms F1 0 1
41207 0x4B6 Timer 12 Dropout Delay 0 60000 1 ms F1 0 1
41208 0x4B7 Logic Element 12 Function 0 4 1 --- FC205 0 1
41209 0x4B8 Logic Element 12 Asserted 0 1 1 --- FC103 0 1
41210 0x4B9 Logic Element 12 Relay 0 0x7F 1 --- FC198 0 1
41214 0x4BD Timer 13 Pickup Delay 0 60000 1 ms F1 0 1
41215 0x4BE Timer 13 Dropout Delay 0 60000 1 ms F1 0 1
41216 0x4BF Logic Element 13 Function 0 4 1 --- FC205 0 1
41217 0x4C0 Logic Element 13 Asserted 0 1 1 --- FC103 0 1
41218 0x4C1 Logic Element 13 Relay 0 0x7F 1 --- FC198 0 1
41222 0x4C5 Timer 14 Pickup Delay 0 60000 1 ms F1 0 1
41223 0x4C6 Timer 14 Dropout Delay 0 60000 1 ms F1 0 1
41224 0x4C7 Logic Element 14 Function 0 4 1 --- FC205 0 1
41225 0x4C8 Logic Element 14 Asserted 0 1 1 --- FC103 0 1
41226 0x4C9 Logic Element 14 Relay 0 0x7F 1 --- FC198 0 1
41230 0x4CD Timer 15 Pickup Delay 0 60000 1 ms F1 0 1
41231 0x4CE Timer 15 Dropout Delay 0 60000 1 ms F1 0 1
41232 0x4CF Logic Element 15 Function 0 4 1 --- FC205 0 1
41233 0x4D0 Logic Element 15 Asserted 0 1 1 --- FC103 0 1
41234 0x4D1 Logic Element 15 Relay 0 0x7F 1 --- FC198 0 1
41238 0x4D5 Timer 16 Pickup Delay 0 60000 1 ms F1 0 1
41239 0x4D6 Timer 16 Dropout Delay 0 60000 1 ms F1 0 1
41240 0x4D7 Logic Element 16 Function 0 4 1 --- FC205 0 1
41241 0x4D8 Logic Element 16 Asserted 0 1 1 --- FC103 0 1
41242 0x4D9 Logic Element 16 Relay 0 0x7F 1 --- FC198 0 1
CONTACT INPUT ASSIGNMENT

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-31


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
41374 0x55D Lockout Reset 0 0xEF02 1 --- F89A 0 1
41380 0x563 Remote Reset 0 0xEF02 1 --- F89A 0 1
41386 0x569 Remote Open 0 0xEF02 0 --- F89A 0 1
41387 0x56A Remote Close 0 0xEF02 0 --- F89A 0 1
41389 0x56C Breaker 52a Contact 0 0x40 0 --- FC204A 0 1
41390 0x56D Breaker 52b Contact 0 0x41 0 --- FC204C 0 1
41391 0x56E Local Mode 0 0xEF02 0 --- F89 0 1
41406 0x57D High Speed Switch 0 0xEF02 1 --- F89 0 1
41407 0x57E Low Speed Switch 0 0xEF02 1 --- F89 0 1
41408 0x57F Emergency Restart 0 0xEF02 1 --- F89A 0 1
CONTACT INPUT NAMES (9 TO 10)
41435 0x59A Input Name 9 0 7 1 --- F22 Input 9 7
41444 0x5A3 Input Name 10 0 7 1 --- F22 Input 10 7
CONTACT INPUTS
41454 0x5AD Input 9 Debounce Interval 1 64 1 ms F1 2 1
41455 0x5AE Input 10 Debounce Interval 1 64 1 ms F1 2 1
41456 0x5AF Input 1 Debounce Interval 1 64 1 ms F1 2 1
41457 0x5B0 Input 2 Debounce Interval 1 64 1 ms F1 2 1
41458 0x5B1 Input 3 Debounce Interval 1 64 1 ms F1 2 1
41459 0x5B2 Input 4 Debounce Interval 1 64 1 ms F1 2 1
41460 0x5B3 Input 5 Debounce Interval 1 64 1 ms F1 2 1
41461 0x5B4 Input 6 Debounce Interval 1 64 1 ms F1 2 1
41462 0x5B5 Input 7 Debounce Interval 1 64 1 ms F1 2 1
41463 0x5B6 Input 8 Debounce Interval 1 64 1 ms F1 2 1
41465 0x5B8 Select DC Voltage 0 3 1 --- FC123 2 1
FRONT PANEL SETUP
41475 0x5C2 Screen Saver 0 10000 1 min F1C 0 1
41498 0x5D9 Stopped LED Colour 0 3 1 --- FC157 1 1
41500 0x5DB Starting LED Colour 0 3 1 --- FC157 3 1
41502 0x5DD Running LED Colour 0 3 1 --- FC157 2 1
OUTPUT RELAYS
41509 0x5E4 Close Relay Type 0 1 1 --- FC199 0 1
41510 0x5E5 Relay 3 Type 0 1 1 --- FC199 0 1
41511 0x5E6 Relay 4 Type 0 1 1 --- FC199 0 1
41512 0x5E7 Relay 5 Type 0 1 1 --- FC199 0 1
41513 0x5E8 Relay 6 Type 0 1 1 --- FC199 0 1
OUTPUT RELAY BLOCKING
41547 0x60A Block Relay 1 Trip 0 0xEF02 1 --- F89 0 1
41548 0x60B Block Relay 2 Close 0 0xEF02 1 --- F89 0 1
OUTPUT RELAY OPERATION
41552 0x60F Relay 1 Operation 0 1 1 --- FC208 1 1
41553 0x610 Relay 2 Operation 0 1 1 --- FC208 1 1
41554 0x611 Relay 3 Operation 0 1 1 --- FC208 1 1
41555 0x612 Relay 4 Operation 0 1 1 --- FC208 1 1
41556 0x613 Relay 5 Operation 0 1 1 --- FC208 1 1
41557 0x614 Relay 6 Operation 0 1 1 --- FC208 1 1

10-32 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
PROGRAMMABLE LEDs
41522 0x5F1 LED 1 Type 0 1 1 --- FC199 0 1
41523 0x5F2 LED 2 Type 0 1 1 --- FC199 0 1
41524 0x5F3 LED 3 Type 0 1 1 --- FC199 0 1
41525 0x5F4 LED 4 Type 0 1 1 --- FC199 0 1
41526 0x5F5 LED 5 Type 0 1 1 --- FC199 0 1
41527 0x5F6 LED 6 Type 0 1 1 --- FC199 0 1
41528 0x5F7 LED 7 Type 0 1 1 --- FC199 0 1
41529 0x5F8 LED 8 Type 0 1 1 --- FC199 0 1
41570 0x621 LED 1 Source 0 0xFFFF 1 --- FC134B 0 1
41572 0x623 LED 2 Source 0 0xFFFF 1 --- FC134B 0 1
41574 0x625 LED 3 Source 0 0xFFFF 1 --- FC134B 0 1
41576 0x627 LED 4 Source 0 0xFFFF 1 --- FC134B 0 1
41578 0x629 LED 5 Source 0 0xFFFF 1 --- FC134B 0 1
41579 0x62A LED 5 Color 0 3 1 --- FC157 3 1
41580 0x62B LED 6 Source 0 0xFFFF 1 --- FC134B 0 1
41581 0x62C LED 6 Color 0 3 1 --- FC157 3 1
41582 0x62D LED 7 Source 0 0xFFFF 1 --- FC134B 0 1
41583 0x62E LED 7 Color 0 3 1 --- FC157 3 1
41584 0x62F LED 8 Source 0 0xFFFF 1 --- FC134B 0 1
41585 0x630 LED 8 Color 0 3 1 --- FC157 3 1
BREAKER TRIP COUNTER
42210 0x8A1 Breaker Trip Counter Initial 0 10000 1 --- F1 0 1
Trips
42211 0x8A2 Breaker Trip Counter 0 2 1 --- FC206 0 1
Function
42212 0x8A3 Breaker Trip Counter Limit 1 10000 1 trips F1 1 1
42213 0x8A4 Breaker Trip Counter Relay 0 0x7F 1 --- FC198 0 1
COIL MONITORS
42214 0x8A5 Bypass Breaker Status 0 1 1 --- FC126 0 1
42215 0x8A6 Relay1 Coil Monitor Function 0 2 1 --- FC206 0 1
42216 0x8A7 Relay1 Coil Monitor Pickup 1 10 1 s F1 5 1
42217 0x8A8 Relay1 Coil Monitor Relay 0 0x7F 1 --- FC198 0 1
42218 0x8A9 Bypass Breaker Status 0 1 1 --- FC126 0 1
42219 0x8AA Relay2 Coil Monitor Function 0 2 1 --- FC206 0 1
42220 0x8AB Relay2 Coil Monitor Pickup 1 10 1 s F1 5 1
42221 0x8AC Relay2 Coil Monitor Relay 0 0x7F 1 --- FC198 0 1
OUTPUT RELAY SEAL-IN
42222 0x8AD Relay 1 Seal-In 0 999 1 s F3 4 1
42223 0x8AE Relay 2 Seal-In 0 999 1 s F3 4 1
COLD LOAD PICKUP
42251 0x8CA Block Sensitive Ground IOC1 0 1 1 --- FC103A 0 1
42252 0x8CB Block Sensitive Ground IOC2 0 1 1 --- FC103A 0 1
42253 0x8CC Raise Sensitive Ground TOC 0 100 1 % F1 0 1
Pickup
42254 0x8CD Block Negative Sequence 0 1 1 --- FC103A 0 1
IOC

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-33


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42255 0x8CE Raise Negative Sequence 0 100 1 % F1 0 1
TOC
BREAKER FAIL
42262 0x8D5 Breaker Failure Function 0 2 1 --- FC206 0 1
42263 0x8D6 Breaker Failure Delay 1 3 100 1 s F3 10 1
42264 0x8D7 Breaker Failure Current 5 2000 1 x CT F3 100 1
42265 0x8D8 Breaker Failure Delay 2 0 100 1 s F3 0 1
42266 0x8D9 Breaker Failure Relays 0 0x7F 1 --- FC198 0 1
42267 0x8DA Breaker Failure Ext Initiate 0 0xEF02 1 --- F89 0 1
FLEXCURVE A
42278 0x8E5 Flex Curve A 1.03 X PU 0 65535 1 100 ms F1 0 1
42279 0x8E6 Flex Curve A 1.05 X PU 0 65535 1 100 ms F1 0 1
42280 0x8E7 Flex Curve A 1.10 X PU 0 65535 1 100 ms F1 0 1
42281 0x8E8 Flex Curve A 1.20 X PU 0 65535 1 100 ms F1 0 1
42282 0x8E9 Flex Curve A 1.30 X PU 0 65535 1 100 ms F1 0 1
42283 0x8EA Flex Curve A 1.40 X PU 0 65535 1 100 ms F1 0 1
42284 0x8EB Flex Curve A 1.50 X PU 0 65535 1 100 ms F1 0 1
42285 0x8EC Flex Curve A 1.60 X PU 0 65535 1 100 ms F1 0 1
42286 0x8ED Flex Curve A 1.70 X PU 0 65535 1 100 ms F1 0 1
42287 0x8EE Flex Curve A 1.80 X PU 0 65535 1 100 ms F1 0 1
42288 0x8EF Flex Curve A 1.90 X PU 0 65535 1 100 ms F1 0 1
42289 0x8F0 Flex Curve A 2.00 X PU 0 65535 1 100 ms F1 0 1
42290 0x8F1 Flex Curve A 2.10 X PU 0 65535 1 100 ms F1 0 1
42291 0x8F2 Flex Curve A 2.20 X PU 0 65535 1 100 ms F1 0 1
42292 0x8F3 Flex Curve A 2.30 X PU 0 65535 1 100 ms F1 0 1
42293 0x8F4 Flex Curve A 2.40 X PU 0 65535 1 100 ms F1 0 1
42294 0x8F5 Flex Curve A 2.50 X PU 0 65535 1 100 ms F1 0 1
42295 0x8F6 Flex Curve A 2.60 X PU 0 65535 1 100 ms F1 0 1
42296 0x8F7 Flex Curve A 2.70 X PU 0 65535 1 100 ms F1 0 1
42297 0x8F8 Flex Curve A 2.80 X PU 0 65535 1 100 ms F1 0 1
42298 0x8F9 Flex Curve A 2.90 X PU 0 65535 1 100 ms F1 0 1
42299 0x8FA Flex Curve A 3.00 X PU 0 65535 1 100 ms F1 0 1
42300 0x8FB Flex Curve A 3.10 X PU 0 65535 1 100 ms F1 0 1
42301 0x8FC Flex Curve A 3.20 X PU 0 65535 1 100 ms F1 0 1
42302 0x8FD Flex Curve A 3.30 X PU 0 65535 1 100 ms F1 0 1
42303 0x8FE Flex Curve A 3.40 X PU 0 65535 1 100 ms F1 0 1
42304 0x8FF Flex Curve A 3.50 X PU 0 65535 1 100 ms F1 0 1
42305 0x900 Flex Curve A 3.60 X PU 0 65535 1 100 ms F1 0 1
42306 0x901 Flex Curve A 3.70 X PU 0 65535 1 100 ms F1 0 1
42307 0x902 Flex Curve A 3.80 X PU 0 65535 1 100 ms F1 0 1
42308 0x903 Flex Curve A 3.90 X PU 0 65535 1 100 ms F1 0 1
42309 0x904 Flex Curve A 4.00 X PU 0 65535 1 100 ms F1 0 1
42310 0x905 Flex Curve A 4.10 X PU 0 65535 1 100 ms F1 0 1
42311 0x906 Flex Curve A 4.20 X PU 0 65535 1 100 ms F1 0 1
42312 0x907 Flex Curve A 4.30 X PU 0 65535 1 100 ms F1 0 1
42313 0x908 Flex Curve A 4.40 X PU 0 65535 1 100 ms F1 0 1

10-34 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42314 0x909 Flex Curve A 4.50 X PU 0 65535 1 100 ms F1 0 1
42315 0x90A Flex Curve A 4.60 X PU 0 65535 1 100 ms F1 0 1
42316 0x90B Flex Curve A 4.70 X PU 0 65535 1 100 ms F1 0 1
42317 0x90C Flex Curve A 4.80 X PU 0 65535 1 100 ms F1 0 1
42318 0x90D Flex Curve A 4.90 X PU 0 65535 1 100 ms F1 0 1
42319 0x90E Flex Curve A 5.00 X PU 0 65535 1 100 ms F1 0 1
42320 0x90F Flex Curve A 5.10 X PU 0 65535 1 100 ms F1 0 1
42321 0x910 Flex Curve A 5.20 X PU 0 65535 1 100 ms F1 0 1
42322 0x911 Flex Curve A 5.30 X PU 0 65535 1 100 ms F1 0 1
42323 0x912 Flex Curve A 5.40 X PU 0 65535 1 100 ms F1 0 1
42324 0x913 Flex Curve A 5.50 X PU 0 65535 1 100 ms F1 0 1
42325 0x914 Flex Curve A 5.60 X PU 0 65535 1 100 ms F1 0 1
42326 0x915 Flex Curve A 5.70 X PU 0 65535 1 100 ms F1 0 1
42327 0x916 Flex Curve A 5.80 X PU 0 65535 1 100 ms F1 0 1
42328 0x917 Flex Curve A 5.90 X PU 0 65535 1 100 ms F1 0 1
42329 0x918 Flex Curve A 6.00 X PU 0 65535 1 100 ms F1 0 1
42330 0x919 Flex Curve A 6.50 X PU 0 65535 1 100 ms F1 0 1
42331 0x91A Flex Curve A 7.00 X PU 0 65535 1 100 ms F1 0 1
42332 0x91B Flex Curve A 7.50 X PU 0 65535 1 100 ms F1 0 1
42333 0x91C Flex Curve A 8.00 X PU 0 65535 1 100 ms F1 0 1
42334 0x91D Flex Curve A 8.50 X PU 0 65535 1 100 ms F1 0 1
42335 0x91E Flex Curve A 9.00 X PU 0 65535 1 100 ms F1 0 1
42336 0x91F Flex Curve A 9.50 X PU 0 65535 1 100 ms F1 0 1
42337 0x920 Flex Curve A 10.00 X PU 0 65535 1 100 ms F1 0 1
42338 0x921 Flex Curve A 10.50 X PU 0 65535 1 100 ms F1 0 1
42339 0x922 Flex Curve A 11.00 X PU 0 65535 1 100 ms F1 0 1
42340 0x923 Flex Curve A 11.50 X PU 0 65535 1 100 ms F1 0 1
42341 0x924 Flex Curve A 12.00 X PU 0 65535 1 100 ms F1 0 1
42342 0x925 Flex Curve A 12.50 X PU 0 65535 1 100 ms F1 0 1
42343 0x926 Flex Curve A 13.00 X PU 0 65535 1 100 ms F1 0 1
42344 0x927 Flex Curve A 13.50 X PU 0 65535 1 100 ms F1 0 1
42345 0x928 Flex Curve A 14.00 X PU 0 65535 1 100 ms F1 0 1
42346 0x929 Flex Curve A 14.50 X PU 0 65535 1 100 ms F1 0 1
42347 0x92A Flex Curve A 15.00 X PU 0 65535 1 100 ms F1 0 1
42348 0x92B Flex Curve A 15.50 X PU 0 65535 1 100 ms F1 0 1
42349 0x92C Flex Curve A 16.00 X PU 0 65535 1 100 ms F1 0 1
42350 0x92D Flex Curve A 16.50 X PU 0 65535 1 100 ms F1 0 1
42351 0x92E Flex Curve A 17.00 X PU 0 65535 1 100 ms F1 0 1
42352 0x92F Flex Curve A 17.50 X PU 0 65535 1 100 ms F1 0 1
42353 0x930 Flex Curve A 18.00 X PU 0 65535 1 100 ms F1 0 1
42354 0x931 Flex Curve A 18.50 X PU 0 65535 1 100 ms F1 0 1
42355 0x932 Flex Curve A 19.00 X PU 0 65535 1 100 ms F1 0 1
42356 0x933 Flex Curve A 19.50 X PU 0 65535 1 100 ms F1 0 1
42357 0x934 Flex Curve A 20.00 X PU 0 65535 1 100 ms F1 0 1
FLEXCURVE B
42380 0x94B Flex Curve B 1.03 X PU 0 65535 1 100 ms F1 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-35


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42381 0x94C Flex Curve B 1.05 X PU 0 65535 1 100 ms F1 0 1
42382 0x94D Flex Curve B 1.10 X PU 0 65535 1 100 ms F1 0 1
42383 0x94E Flex Curve B 1.20 X PU 0 65535 1 100 ms F1 0 1
42384 0x94F Flex Curve B 1.30 X PU 0 65535 1 100 ms F1 0 1
42385 0x950 Flex Curve B 1.40 X PU 0 65535 1 100 ms F1 0 1
42386 0x951 Flex Curve B 1.50 X PU 0 65535 1 100 ms F1 0 1
42387 0x952 Flex Curve B 1.60 X PU 0 65535 1 100 ms F1 0 1
42388 0x953 Flex Curve B 1.70 X PU 0 65535 1 100 ms F1 0 1
42389 0x954 Flex Curve B 1.80 X PU 0 65535 1 100 ms F1 0 1
42390 0x955 Flex Curve B 1.90 X PU 0 65535 1 100 ms F1 0 1
42391 0x956 Flex Curve B 2.00 X PU 0 65535 1 100 ms F1 0 1
42392 0x957 Flex Curve B 2.10 X PU 0 65535 1 100 ms F1 0 1
42393 0x958 Flex Curve B 2.20 X PU 0 65535 1 100 ms F1 0 1
42394 0x959 Flex Curve B 2.30 X PU 0 65535 1 100 ms F1 0 1
42395 0x95A Flex Curve B 2.40 X PU 0 65535 1 100 ms F1 0 1
42396 0x95B Flex Curve B 2.50 X PU 0 65535 1 100 ms F1 0 1
42397 0x95C Flex Curve B 2.60 X PU 0 65535 1 100 ms F1 0 1
42398 0x95D Flex Curve B 2.70 X PU 0 65535 1 100 ms F1 0 1
42399 0x95E Flex Curve B 2.80 X PU 0 65535 1 100 ms F1 0 1
42400 0x95F Flex Curve B 2.90 X PU 0 65535 1 100 ms F1 0 1
42401 0x960 Flex Curve B 3.00 X PU 0 65535 1 100 ms F1 0 1
42402 0x961 Flex Curve B 3.10 X PU 0 65535 1 100 ms F1 0 1
42403 0x962 Flex Curve B 3.20 X PU 0 65535 1 100 ms F1 0 1
42404 0x963 Flex Curve B 3.30 X PU 0 65535 1 100 ms F1 0 1
42405 0x964 Flex Curve B 3.40 X PU 0 65535 1 100 ms F1 0 1
42406 0x965 Flex Curve B 3.50 X PU 0 65535 1 100 ms F1 0 1
42407 0x966 Flex Curve B 3.60 X PU 0 65535 1 100 ms F1 0 1
42408 0x967 Flex Curve B 3.70 X PU 0 65535 1 100 ms F1 0 1
42409 0x968 Flex Curve B 3.80 X PU 0 65535 1 100 ms F1 0 1
42410 0x969 Flex Curve B 3.90 X PU 0 65535 1 100 ms F1 0 1
42411 0x96A Flex Curve B 4.00 X PU 0 65535 1 100 ms F1 0 1
42412 0x96B Flex Curve B 4.10 X PU 0 65535 1 100 ms F1 0 1
42413 0x96C Flex Curve B 4.20 X PU 0 65535 1 100 ms F1 0 1
42414 0x96D Flex Curve B 4.30 X PU 0 65535 1 100 ms F1 0 1
42415 0x96E Flex Curve B 4.40 X PU 0 65535 1 100 ms F1 0 1
42416 0x96F Flex Curve B 4.50 X PU 0 65535 1 100 ms F1 0 1
42417 0x970 Flex Curve B 4.60 X PU 0 65535 1 100 ms F1 0 1
42418 0x971 Flex Curve B 4.70 X PU 0 65535 1 100 ms F1 0 1
42419 0x972 Flex Curve B 4.80 X PU 0 65535 1 100 ms F1 0 1
42420 0x973 Flex Curve B 4.90 X PU 0 65535 1 100 ms F1 0 1
42421 0x974 Flex Curve B 5.00 X PU 0 65535 1 100 ms F1 0 1
42422 0x975 Flex Curve B 5.10 X PU 0 65535 1 100 ms F1 0 1
42423 0x976 Flex Curve B 5.20 X PU 0 65535 1 100 ms F1 0 1
42424 0x977 Flex Curve B 5.30 X PU 0 65535 1 100 ms F1 0 1
42425 0x978 Flex Curve B 5.40 X PU 0 65535 1 100 ms F1 0 1
42426 0x979 Flex Curve B 5.50 X PU 0 65535 1 100 ms F1 0 1

10-36 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42427 0x97A Flex Curve B 5.60 X PU 0 65535 1 100 ms F1 0 1
42428 0x97B Flex Curve B 5.70 X PU 0 65535 1 100 ms F1 0 1
42429 0x97C Flex Curve B 5.80 X PU 0 65535 1 100 ms F1 0 1
42430 0x97D Flex Curve B 5.90 X PU 0 65535 1 100 ms F1 0 1
42431 0x97E Flex Curve B 6.00 X PU 0 65535 1 100 ms F1 0 1
42432 0x97F Flex Curve B 6.50 X PU 0 65535 1 100 ms F1 0 1
42433 0x980 Flex Curve B 7.00 X PU 0 65535 1 100 ms F1 0 1
42434 0x981 Flex Curve B 7.50 X PU 0 65535 1 100 ms F1 0 1
42435 0x982 Flex Curve B 8.00 X PU 0 65535 1 100 ms F1 0 1
42436 0x983 Flex Curve B 8.50 X PU 0 65535 1 100 ms F1 0 1
42437 0x984 Flex Curve B 9.00 X PU 0 65535 1 100 ms F1 0 1
42438 0x985 Flex Curve B 9.50 X PU 0 65535 1 100 ms F1 0 1
42439 0x986 Flex Curve B 10.00 X PU 0 65535 1 100 ms F1 0 1
42440 0x987 Flex Curve B 10.50 X PU 0 65535 1 100 ms F1 0 1
42441 0x988 Flex Curve B 11.00 X PU 0 65535 1 100 ms F1 0 1
42442 0x989 Flex Curve B 11.50 X PU 0 65535 1 100 ms F1 0 1
42443 0x98A Flex Curve B 12.00 X PU 0 65535 1 100 ms F1 0 1
42444 0x98B Flex Curve B 12.50 X PU 0 65535 1 100 ms F1 0 1
42445 0x98C Flex Curve B 13.00 X PU 0 65535 1 100 ms F1 0 1
42446 0x98D Flex Curve B 13.50 X PU 0 65535 1 100 ms F1 0 1
42447 0x98E Flex Curve B 14.00 X PU 0 65535 1 100 ms F1 0 1
42448 0x98F Flex Curve B 14.50 X PU 0 65535 1 100 ms F1 0 1
42449 0x990 Flex Curve B 15.00 X PU 0 65535 1 100 ms F1 0 1
42450 0x991 Flex Curve B 15.50 X PU 0 65535 1 100 ms F1 0 1
42451 0x992 Flex Curve B 16.00 X PU 0 65535 1 100 ms F1 0 1
42452 0x993 Flex Curve B 16.50 X PU 0 65535 1 100 ms F1 0 1
42453 0x994 Flex Curve B 17.00 X PU 0 65535 1 100 ms F1 0 1
42454 0x995 Flex Curve B 17.50 X PU 0 65535 1 100 ms F1 0 1
42455 0x996 Flex Curve B 18.00 X PU 0 65535 1 100 ms F1 0 1
42456 0x997 Flex Curve B 18.50 X PU 0 65535 1 100 ms F1 0 1
42457 0x998 Flex Curve B 19.00 X PU 0 65535 1 100 ms F1 0 1
42458 0x999 Flex Curve B 19.50 X PU 0 65535 1 100 ms F1 0 1
42459 0x99A Flex Curve B 20.00 X PU 0 65535 1 100 ms F1 0 1
NEUTRAL IOC
42490 0x9B9 Neutral IOC Function 0 3 1 --- FC197 0 1
42491 0x9BA Neutral IOC Pickup 5 2000 1 x CT F3 100 1
42492 0x9BB Neutral IOC Delay 0 30000 1 s F3 0 1
GROUND DIRECTIONAL
42556 0x9FB Ground Directional Function 0 3 1 --- FC207 0 1
NEGATIVE SEQUENCE OVERVOLTAGE
42560 0x9FF Negative Sequence OV 0 3 1 --- FC197 0 1
Function
42561 0xA00 Negative Sequence OV 0 125 1 x VT F3 30 1
Pickup
42562 0xA01 Negative Sequence OV 0 60000 1 s F3 200 1
Delay
PHASE OVERVOLTAGE1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-37


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42566 0xA05 Phase OV Function 0 3 1 --- FC197 0 1
42567 0xA06 Phase OV Pickup 0 125 1 x VT F3 125 1
42568 0xA07 Phase OV Delay 0 60000 1 s F3 200 1
42569 0xA08 Phase OV Phases 1 3 1 --- F92 1 1
PHASE UNDERVOLTAGE1
42570 0xA09 Phase UV Function 0 3 1 --- FC197 0 1
42571 0xA0A Phase UV Pickup 0 125 1 x VT F3 75 1
42572 0xA0B Phase UV Curve 0 1 1 --- F93 1 1
42573 0xA0C Phase UV Delay 0 60000 1 s F3 200 1
42574 0xA0D Phase UV Phases 1 3 1 --- F92 1 1
42575 0xA0E Phase UV Minimum Voltage 0 125 1 x VT F3 30 1
UNDERFREQUENCY
42584 0xA17 Underfrequency 1 Function 0 3 1 --- FC197 0 1
42585 0xA18 Underfrequency 1 Pickup 4000 7000 1 Hz F3 5900 1
42586 0xA19 Underfrequency 1 Delay 10 60000 1 s F3 200 1
42587 0xA1A Minimum UF Voltage 1 0 125 1 x VT F3 70 1
42588 0xA1B Underfrequency 2 Function 0 3 1 --- FC197 0 1
42589 0xA1C Underfrequency 2 Pickup 4000 7000 1 Hz F3 5900 1
42590 0xA1D Underfrequency 2 Delay 10 60000 1 s F3 200 1
42591 0xA1E Minimum UF Voltage 2 0 125 1 x VT F3 70 1
OVERFREQUENCY
42592 0xA1F Overfrequency 1 Function 0 3 1 --- FC197 0 1
42593 0xA20 Overfrequency 1 Pickup 4000 7000 1 Hz F3 6050 1
42594 0xA21 Overfrequency 1 Delay 10 60000 1 s F3 200 1
42595 0xA22 Overfrequency 2 Function 0 3 1 --- FC197 0 1
42596 0xA23 Overfrequency 2 Pickup 4000 7000 1 Hz F3 6050 1
42597 0xA24 Overfrequency 2 Delay 10 60000 1 s F3 200 1
PROTECTION ELEMENT RELAY CONFIGURATION
42738 0xAB1 Neutral IOC 1 Relay 0 0x7F 1 --- FC198 0 1
42752 0xABF Negative Sequence 0 0x7F 1 --- FC198 0 1
Overvoltage Relay
42754 0xAC1 Phase Overvoltage Relay 0 0x7F 1 --- FC198 0 1
42755 0xAC2 Phase Undervoltage Relay 0 0x7F 1 --- FC198 0 1
42758 0xAC5 Underfrequency 1 Relay 0 0x7F 1 --- FC198 0 1
42759 0xAC6 Underfrequency 2 Relay 0 0x7F 1 --- FC198 0 1
42760 0xAC7 Overfrequency 1 Relay 0 0x7F 1 --- FC198 0 1
42761 0xAC8 Overfrequency 2 Relay 0 0x7F 1 --- FC198 0 1
42764 0xACB Negative Sequence IOC 0 0x7F 1 --- FC198 0 1
Relays
42765 0xACC Short Circuit Relays 0 0x7F 1 --- FC198 0 1
42766 0xACD Mechanical Jam Relays 0 0x7F 1 --- FC198 0 1
42767 0xACE Underpower Relays 0 0x7F 1 --- FC198 0 1
42768 0xACF Acceleration Relays 0 0x7F 1 --- FC198 0 1
42769 0xAD0 Undercurrent Relays 0 0x7F 1 --- FC198 0 1
42770 0xAD1 Current Unbalance Relays 0 0x7F 1 --- FC198 0 1
42771 0xAD2 Load Increase Alarm Relays 0 0x7F 1 --- FC198 0 1
42772 0xAD3 Ground Trip Relays 0 0x7F 1 --- FC198 0 1

10-38 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42773 0xAD4 Welded Contactor Relays 0 0x7F 1 --- FC198 0 1
42774 0xAD5 RTD Trouble Relays 0 0x7F 1 --- FC198 0 1
42775 0xAD6 High Speed Undercurrent 0 0x7F 1 --- FC198 0 1
Relays
42781 0xADC Motor Running Hours Alarm 0 0x7F 1 --- FC198 0 1
Relays
WELDED CONTACTOR
42783 0xADE Enable Welded Contactor 0 2 1 --- FC206 0 1
42784 0xADF Welded Contactor Current 5 2000 1 x CT F3 100 1
42785 0xAE0 Welded Contactor Time 3 100 1 s F3 10 1
Delay 1
42786 0xAE1 Welded Contactor Time 0 100 1 s F3 0 1
Delay 2
42787 0xAE2 Welded Contactor Ext 0 0xEF02 1 --- F89 0 1
Initiate
TWO-SPEED MOTOR PROTECTION
42789 0xAE4 High Speed Thermal OL 0 1 1 --- FC236 0 1
Curve
42790 0xAE5 High Speed O/L No. 1 15 1 --- F1 4 1
42791 0xAE6 High Speed S/C Func 0 3 1 --- FC197 0 1
42797 0xAEC High Speed S/C Pickup 100 2000 1 x CT F3 600 1
42798 0xAED High Speed S/C Delay 0 6000 1 s F3 0 1
42799 0xAEE High Speed SC Relays 0 0x7F 1 --- FC198 0 1
42802 0xAF1 Acceleration Time On 10 2500 1 s F2 100 1
Stopped
42803 0xAF2 Acceleration Time On Low 10 2500 1 s F2 100 1
Speed
42807 0xAF6 High Speed Undercurrent 0 600 1 s F1 0 1
Block On Start
42808 0xAF7 High Speed U/C Alarm 0 1 1 --- FC126 0 1
Enable
42809 0xAF8 High Speed U/C Alarm 10 95 1 x FLA F3 70 1
Pickup
42810 0xAF9 High Speed U/C Alarm Delay 100 6000 1 s F3 100 1
42811 0xAFA High Speed U/C Trip Enable 0 1 1 --- FC126 0 1
42812 0xAFB High Speed U/C Trip Pickup 10 95 1 x FLA F3 60 1
42813 0xAFC High Speed U/C Trip Delay 100 6000 1 s F3 100 1
VIRTUAL INPUT NAMES
42884 0xB43 Virtual Input Name 1 0 9 1 --- F22 Virtual IN 1 9
42893 0xB4C Virtual Input Name 2 0 9 1 --- F22 Virtual IN 2 9
42902 0xB55 Virtual Input Name 3 0 9 1 --- F22 Virtual IN 3 9
42911 0xB5E Virtual Input Name 4 0 9 1 --- F22 Virtual IN 4 9
42920 0xB67 Virtual Input Name 5 0 9 1 --- F22 Virtual IN 5 9
42929 0xB70 Virtual Input Name 6 0 9 1 --- F22 Virtual IN 6 9
42938 0xB79 Virtual Input Name 7 0 9 1 --- F22 Virtual IN 7 9
42947 0xB82 Virtual Input Name 8 0 9 1 --- F22 Virtual IN 8 9
42956 0xB8B Virtual Input Name 9 0 9 1 --- F22 Virtual IN 9 9
42965 0xB94 Virtual Input Name 10 0 9 1 --- F22 Virtual IN 9
10
42974 0xB9D Virtual Input Name 11 0 9 1 --- F22 Virtual IN 9
11

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-39


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42983 0xBA6 Virtual Input Name 12 0 9 1 --- F22 Virtual IN 9
12
42992 0xBAF Virtual Input Name 13 0 9 1 --- F22 Virtual IN 9
13
43001 0xBB8 Virtual Input Name 14 0 9 1 --- F22 Virtual IN 9
14
43010 0xBC1 Virtual Input Name 15 0 9 1 --- F22 Virtual IN 9
15
43019 0xBCA Virtual Input Name 16 0 9 1 --- F22 Virtual IN 9
16
43028 0xBD3 Virtual Input Name 17 0 9 1 --- F22 Virtual IN 9
17
43037 0xBDC Virtual Input Name 18 0 9 1 --- F22 Virtual IN 9
18
43046 0xBE5 Virtual Input Name 19 0 9 1 --- F22 Virtual IN 9
19
43055 0xBEE Virtual Input Name 20 0 9 1 --- F22 Virtual IN 9
20
43064 0xBF7 Virtual Input Name 21 0 9 1 --- F22 Virtual IN 9
21
43073 0xC00 Virtual Input Name 22 0 9 1 --- F22 Virtual IN 9
22
43082 0xC09 Virtual Input Name 23 0 9 1 --- F22 Virtual IN 9
23
43091 0xC12 Virtual Input Name 24 0 9 1 --- F22 Virtual IN 9
24
43100 0xC1B Virtual Input Name 25 0 9 1 --- F22 Virtual IN 9
25
43109 0xC24 Virtual Input Name 26 0 9 1 --- F22 Virtual IN 9
26
43118 0xC2D Virtual Input Name 27 0 9 1 --- F22 Virtual IN 9
27
43127 0xC36 Virtual Input Name 28 0 9 1 --- F22 Virtual IN 9
28
43136 0xC3F Virtual Input Name 29 0 9 1 --- F22 Virtual IN 9
29
43145 0xC48 Virtual Input Name 30 0 9 1 --- F22 Virtual IN 9
30
43154 0xC51 Virtual Input Name 31 0 9 1 --- F22 Virtual IN 9
31
43163 0xC5A Virtual Input Name 32 0 9 1 --- F22 Virtual IN 9
32
SIMULATION
RTD PROTECTION
40335 0x14E RTD 1 Alarm PKP Delay 0 60000 1 s F3 200 1
40336 0x14F RTD 2 Alarm PKP Delay 0 60000 1 s F3 200 1
40337 0x150 RTD 3 Alarm PKP Delay 0 60000 1 s F3 200 1
40338 0x151 RTD 4 Alarm PKP Delay 0 60000 1 s F3 200 1
40339 0x152 RTD 5 Alarm PKP Delay 0 60000 1 s F3 200 1
40340 0x153 RTD 6 Alarm PKP Delay 0 60000 1 s F3 200 1
40341 0x154 RTD 7 Alarm PKP Delay 0 60000 1 s F3 200 1
40342 0x155 RTD 8 Alarm PKP Delay 0 60000 1 s F3 200 1
40343 0x156 RTD 9 Alarm PKP Delay 0 60000 1 s F3 200 1
40344 0x157 RTD 10 Alarm PKP Delay 0 60000 1 s F3 200 1

10-40 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
40345 0x158 RTD 11 Alarm PKP Delay 0 60000 1 s F3 200 1
40346 0x159 RTD 12 Alarm PKP Delay 0 60000 1 s F3 200 1
40347 0x15A RTD 1 Alarm DPO Delay 0 60000 1 s F3 200 1
40348 0x15B RTD 2 Alarm DPO Delay 0 60000 1 s F3 200 1
40349 0x15C RTD 3 Alarm DPO Delay 0 60000 1 s F3 200 1
40350 0x15D RTD 4 Alarm DPO Delay 0 60000 1 s F3 200 1
40351 0x15E RTD 5 Alarm DPO Delay 0 60000 1 s F3 200 1
40352 0x15F RTD 6 Alarm DPO Delay 0 60000 1 s F3 200 1
40353 0x160 RTD 7 Alarm DPO Delay 0 60000 1 s F3 200 1
40354 0x161 RTD 8 Alarm DPO Delay 0 60000 1 s F3 200 1
40355 0x162 RTD 9 Alarm DPO Delay 0 60000 1 s F3 200 1
40356 0x163 RTD 10 Alarm DPO Delay 0 60000 1 s F3 200 1
40357 0x164 RTD 11 Alarm DPO Delay 0 60000 1 s F3 200 1
40358 0x165 RTD 12 Alarm DPO Delay 0 60000 1 s F3 200 1
40359 0x166 RTD 1 Trip PKP Delay 0 60000 1 s F3 200 1
40360 0x167 RTD 2 Trip PKP Delay 0 60000 1 s F3 200 1
40361 0x168 RTD 3 Trip PKP Delay 0 60000 1 s F3 200 1
40362 0x169 RTD 4 Trip PKP Delay 0 60000 1 s F3 200 1
40363 0x16A RTD 5 Trip PKP Delay 0 60000 1 s F3 200 1
40364 0x16B RTD 6 Trip PKP Delay 0 60000 1 s F3 200 1
40365 0x16C RTD 7 Trip PKP Delay 0 60000 1 s F3 200 1
40366 0x16D RTD 8 Trip PKP Delay 0 60000 1 s F3 200 1
40367 0x16E RTD 9 Trip PKP Delay 0 60000 1 s F3 200 1
40368 0x16F RTD 10 Trip PKP Delay 0 60000 1 s F3 200 1
40369 0x170 RTD 11 Trip PKP Delay 0 60000 1 s F3 200 1
40370 0x171 RTD 12 Trip PKP Delay 0 60000 1 s F3 200 1
40371 0x172 RTD 1 Trip DPO Delay 0 60000 1 s F3 200 1
40372 0x173 RTD 2 Trip DPO Delay 0 60000 1 s F3 200 1
40373 0x174 RTD 3 Trip DPO Delay 0 60000 1 s F3 200 1
40374 0x175 RTD 4 Trip DPO Delay 0 60000 1 s F3 200 1
40375 0x176 RTD 5 Trip DPO Delay 0 60000 1 s F3 200 1
40376 0x177 RTD 6 Trip DPO Delay 0 60000 1 s F3 200 1
40377 0x178 RTD 7 Trip DPO Delay 0 60000 1 s F3 200 1
40378 0x179 RTD 8 Trip DPO Delay 0 60000 1 s F3 200 1
40379 0x17A RTD 9 Trip DPO Delay 0 60000 1 s F3 200 1
40380 0x17B RTD 10 Trip DPO Delay 0 60000 1 s F3 200 1
40381 0x17C RTD 11 Trip DPO Delay 0 60000 1 s F3 200 1
40382 0x17D RTD 12 Trip DPO Delay 0 60000 1 s F3 200 1
40390 0x185 RTD 7 Application 0 7 1 --- FC121 0 1
40391 0x186 RTD 7 Name 0 9 1 --- F22 RTD 7 9
40401 0x190 RTD 7 Alarm Temp 1 250 1 °C F4 130 1
40402 0x191 RTD 7 Trip Voting 0 12 1 --- FC122 0 1
40403 0x192 RTD 7 Trip Temp 1 250 1 °C F4 155 1
40404 0x193 RTD 8 Application 0 7 1 --- FC121 0 1
40405 0x194 RTD 8 Name 0 9 1 --- F22 RTD 8 9
40415 0x19E RTD 8 Alarm Temp 1 250 1 °C F4 130 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-41


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
40416 0x19F RTD 8 Trip Voting 0 12 1 --- FC122 0 1
40417 0x1A0 RTD 8 Trip Temp 1 250 1 °C F4 155 1
40418 0x1A1 RTD 9 Application 0 7 1 --- FC121 0 1
40419 0x1A2 RTD 9 Name 0 9 1 --- F22 RTD 9 9
40429 0x1AC RTD 9 Alarm Temp 1 250 1 °C F4 130 1
40430 0x1AD RTD 9 Trip Voting 0 12 1 --- FC122 0 1
40431 0x1AE RTD 9 Trip Temp 1 250 1 °C F4 155 1
40432 0x1AF RTD 10 Application 0 7 1 --- FC121 0 1
40433 0x1B0 RTD 10 Name 0 9 1 --- F22 RTD 10 9
40443 0x1BA RTD 10 Alarm Temp 1 250 1 °C F4 130 1
40444 0x1BB RTD 10 Trip Voting 0 12 1 --- FC122 0 1
40445 0x1BC RTD 10 Trip Temp 1 250 1 °C F4 155 1
40446 0x1BD RTD 11 Application 0 7 1 --- FC121 0 1
40447 0x1BE RTD 11 Name 0 9 1 --- F22 RTD 11 9
40457 0x1C8 RTD 11 Alarm Temp 1 250 1 °C F4 130 1
40458 0x1C9 RTD 11 Trip Voting 0 12 1 --- FC122 0 1
40459 0x1CA RTD 11 Trip Temp 1 250 1 °C F4 155 1
40460 0x1CB RTD 12 Application 0 7 1 --- FC121 0 1
40461 0x1CC RTD 12 Name 0 9 1 --- F22 RTD 12 9
40471 0x1D6 RTD 12 Alarm Temp 1 250 1 °C F4 130 1
40472 0x1D7 RTD 12 Trip Voting 0 12 1 --- FC122 0 1
40473 0x1D8 RTD 12 Trip Temp 1 250 1 °C F4 155 1
40731 0x2DA RTD Trouble Alarm 0 1 1 --- FC126 0 1
40732 0x2DB Enable RTD Bias 0 1 1 --- FC126 0 1
40735 0x2DE RTD 1 Application 0 7 1 --- FC121 0 1
40736 0x2DF RTD 1 Name 0 9 1 --- F22 RTD 1 9
40746 0x2E9 RTD 1 Alarm Temperature 1 250 1 °C F4 130 1
40747 0x2EA RTD 1 Trip Voting 0 12 1 --- FC122 0 1
40748 0x2EB RTD 1 Trip Temperature 1 250 1 °C F4 155 1
40749 0x2EC RTD 2 Application 0 7 1 --- FC121 0 1
40750 0x2ED RTD 2 Name 0 9 1 --- F22 RTD 2 9
40760 0x2F7 RTD 2 Alarm Temperature 1 250 1 °C F4 130 1
40761 0x2F8 RTD 2 Trip Voting 0 12 1 --- FC122 0 1
40762 0x2F9 RTD 2 Trip Temperature 1 250 1 °C F4 155 1
40763 0x2FA RTD 3 Application 0 7 1 --- FC121 0 1
40764 0x2FB RTD 3 Name 0 9 1 --- F22 RTD 3 9
40774 0x305 RTD 3 Alarm Temperature 1 250 1 °C F4 130 1
40775 0x306 RTD 3 Trip Voting 0 12 1 --- FC122 0 1
40776 0x307 RTD 3 Trip Temperature 1 250 1 °C F4 155 1
40777 0x308 RTD 4 Application 0 7 1 --- FC121 0 1
40778 0x309 RTD 4 Name 0 9 1 --- F22 RTD 4 9
40788 0x313 RTD 4 Alarm Temperature 1 250 1 °C F4 130 1
40789 0x314 RTD 4 Trip Voting 0 12 1 --- FC122 0 1
40790 0x315 RTD 4 Trip Temperature 1 250 1 °C F4 155 1
40791 0x316 RTD 5 Application 0 7 1 --- FC121 0 1
40792 0x317 RTD 5 Name 0 9 1 --- F22 RTD 5 9

10-42 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
40802 0x321 RTD 5 Alarm Temperature 1 250 1 °C F4 130 1
40803 0x322 RTD 5 Trip Voting 0 12 1 --- FC122 0 1
40804 0x323 RTD 5 Trip Temperature 1 250 1 °C F4 155 1
40805 0x324 RTD 6 Application 0 7 1 --- FC121 0 1
40806 0x325 RTD 6 Name 0 9 1 --- F22 RTD 6 9
40816 0x32F RTD 6 Alarm Temperature 1 250 1 °C F4 130 1
40817 0x330 RTD 6 Trip Voting 0 12 1 --- FC122 0 1
40818 0x331 RTD 6 Trip Temperature 1 250 1 °C F4 155 1
43560 0xDE7 RTD 1 Alarm 0 1 1 --- FC126 0 1
43561 0xDE8 RTD 1 Trip 0 1 1 --- FC126 0 1
43562 0xDE9 RTD 2 Alarm 0 1 1 --- FC126 0 1
43563 0xDEA RTD 2 Trip 0 1 1 --- FC126 0 1
43564 0xDEB RTD 3 Alarm 0 1 1 --- FC126 0 1
43565 0xDEC RTD 3 Trip 0 1 1 --- FC126 0 1
43566 0xDED RTD 4 Alarm 0 1 1 --- FC126 0 1
43567 0xDEE RTD 4 Trip 0 1 1 --- FC126 0 1
43568 0xDEF RTD 5 Alarm 0 1 1 --- FC126 0 1
43569 0xDF0 RTD 5 Trip 0 1 1 --- FC126 0 1
43570 0xDF1 RTD 6 Alarm 0 1 1 --- FC126 0 1
43571 0xDF2 RTD 6 Trip 0 1 1 --- FC126 0 1
43572 0xDF3 RTD 7 Alarm 0 1 1 --- FC126 0 1
43573 0xDF4 RTD 7 Trip 0 1 1 --- FC126 0 1
43574 0xDF5 RTD 8 Alarm 0 1 1 --- FC126 0 1
43575 0xDF6 RTD 8 Trip 0 1 1 --- FC126 0 1
43576 0xDF7 RTD 9 Alarm 0 1 1 --- FC126 0 1
43577 0xDF8 RTD 9 Trip 0 1 1 --- FC126 0 1
43578 0xDF9 RTD 10 Alarm 0 1 1 --- FC126 0 1
43579 0xDFA RTD 10 Trip 0 1 1 --- FC126 0 1
43580 0xDFB RTD 11 Alarm 0 1 1 --- FC126 0 1
43581 0xDFC RTD 11 Trip 0 1 1 --- FC126 0 1
43582 0xDFD RTD 12 Alarm 0 1 1 --- FC126 0 1
43583 0xDFE RTD 12 Trip 0 1 1 --- FC126 0 1
43586 0xE01 RTD 1 Relays 0 0x7F 1 --- FC198 0 1
43587 0xE02 RTD 2 Relays 0 0x7F 1 --- FC198 0 1
43588 0xE03 RTD 3 Relays 0 0x7F 1 --- FC198 0 1
43589 0xE04 RTD 4 Relays 0 0x7F 1 --- FC198 0 1
43590 0xE05 RTD 5 Relays 0 0x7F 1 --- FC198 0 1
43591 0xE06 RTD 6 Relays 0 0x7F 1 --- FC198 0 1
43592 0xE07 RTD 7 Relays 0 0x7F 1 --- FC198 0 1
43593 0xE08 RTD 8 Relays 0 0x7F 1 --- FC198 0 1
43594 0xE09 RTD 9 Relays 0 0x7F 1 --- FC198 0 1
43595 0xE0A RTD 10 Relays 0 0x7F 1 --- FC198 0 1
43596 0xE0B RTD 11 Relays 0 0x7F 1 --- FC198 0 1
43597 0xE0C RTD 12 Relays 0 0x7F 1 --- FC198 0 1
43599 0xE0E RTD 1 Block1 0 0xEF02 1 --- F89 0 1
43600 0xE0F RTD 1 Block2 0 0xEF02 1 --- F89 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-43


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
43601 0xE10 RTD 1 Block3 0 0xEF02 1 --- F89 0 1
43602 0xE11 RTD 2 Block1 0 0xEF02 1 --- F89 0 1
43603 0xE12 RTD 2 Block2 0 0xEF02 1 --- F89 0 1
43604 0xE13 RTD 2 Block3 0 0xEF02 1 --- F89 0 1
43605 0xE14 RTD 3 Block1 0 0xEF02 1 --- F89 0 1
43606 0xE15 RTD 3 Block2 0 0xEF02 1 --- F89 0 1
43607 0xE16 RTD 3 Block3 0 0xEF02 1 --- F89 0 1
43608 0xE17 RTD 4 Block1 0 0xEF02 1 --- F89 0 1
43609 0xE18 RTD 4 Block2 0 0xEF02 1 --- F89 0 1
43610 0xE19 RTD 4 Block3 0 0xEF02 1 --- F89 0 1
43611 0xE1A RTD 5 Block1 0 0xEF02 1 --- F89 0 1
43612 0xE1B RTD 5 Block2 0 0xEF02 1 --- F89 0 1
43613 0xE1C RTD 5 Block3 0 0xEF02 1 --- F89 0 1
43614 0xE1D RTD 6 Block1 0 0xEF02 1 --- F89 0 1
43615 0xE1E RTD 6 Block2 0 0xEF02 1 --- F89 0 1
43616 0xE1F RTD 6 Block3 0 0xEF02 1 --- F89 0 1
43617 0xE20 RTD 7 Block1 0 0xEF02 1 --- F89 0 1
43618 0xE21 RTD 7 Block2 0 0xEF02 1 --- F89 0 1
43619 0xE22 RTD 7 Block3 0 0xEF02 1 --- F89 0 1
43620 0xE23 RTD 8 Block1 0 0xEF02 1 --- F89 0 1
43621 0xE24 RTD 8 Block2 0 0xEF02 1 --- F89 0 1
43622 0xE25 RTD 8 Block3 0 0xEF02 1 --- F89 0 1
43623 0xE26 RTD 9 Block1 0 0xEF02 1 --- F89 0 1
43624 0xE27 RTD 9 Block2 0 0xEF02 1 --- F89 0 1
43625 0xE28 RTD 9 Block3 0 0xEF02 1 --- F89 0 1
43626 0xE29 RTD 10 Block1 0 0xEF02 1 --- F89 0 1
43627 0xE2A RTD 10 Block2 0 0xEF02 1 --- F89 0 1
43628 0xE2B RTD 10 Block3 0 0xEF02 1 --- F89 0 1
43629 0xE2C RTD 11 Block1 0 0xEF02 1 --- F89 0 1
43630 0xE2D RTD 11 Block2 0 0xEF02 1 --- F89 0 1
43631 0xE2E RTD 11 Block3 0 0xEF02 1 --- F89 0 1
43632 0xE2F RTD 12 Block1 0 0xEF02 1 --- F89 0 1
43633 0xE30 RTD 12 Block2 0 0xEF02 1 --- F89 0 1
43634 0xE31 RTD 12 Block3 0 0xEF02 1 --- F89 0 1
PHASE OVERVOLTAGE2
43733 0xE94 Phase OV 2 Function 0 3 1 --- FC197 0 1
43734 0xE95 Phase OV 2 Pickup 0 125 1 x VT F3 125 1
43735 0xE96 Phase OV 2 Delay 0 60000 1 s F3 200 1
43736 0xE97 Phase OV 2 Phases 1 3 1 --- F92 1 1
PHASE UNDERVOLTAGE2
43737 0xE98 Phase UV 2 Function 0 3 1 --- FC197 0 1
43738 0xE99 Phase UV 2 Pickup 0 125 1 x VT F3 75 1
43739 0xE9A Phase UV 2 Curve 0 1 1 --- F93 1 1
43740 0xE9B Phase UV 2 Delay 0 60000 1 s F3 200 1
43741 0xE9C Phase UV 2 Phases 1 3 1 --- F92 1 1
43742 0xE9D Phase UV 2 Min Voltage 0 125 1 x VT F3 30 1

10-44 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
PHASE OVERVOLTAGE2 (RELAYS & BLOCKS)
43743 0xE9E Phase OV 2 Relays 0 0x7F 1 --- FC198 0 1
43744 0xE9F Phase OV 2 Block 1 0 0xEF02 1 --- F89 0 1
43745 0xEA0 Phase OV 2 Block 1 0 0xEF02 1 --- F89 0 1
43746 0xEA1 Phase OV 2 Block 1 0 0xEF02 1 --- F89 0 1
PHASE UNDERVOLTAGE2 (RELAYS & BLOCKS)
43747 0xEA2 Phase UV 2 Relays 0 0x7F 1 --- FC198 0 1
43748 0xEA3 Phase UV 2 Block 1 0 0xEF02 1 --- F89 0 1
43749 0xEA4 Phase UV 2 Block 1 0 0xEF02 1 --- F89 0 1
43750 0xEA5 Phase UV 2 Block 1 0 0xEF02 1 --- F89 0 1
FORCE VIRTUAL INPUTS
43764 0xEB3 Force Virtual Input 1 0 1 1 --- FC103 0 1
43765 0xEB4 Force Virtual Input 2 0 1 1 --- FC103 0 1
43766 0xEB5 Force Virtual Input 3 0 1 1 --- FC103 0 1
43767 0xEB6 Force Virtual Input 4 0 1 1 --- FC103 0 1
43768 0xEB7 Force Virtual Input 5 0 1 1 --- FC103 0 1
43769 0xEB8 Force Virtual Input 6 0 1 1 --- FC103 0 1
43770 0xEB9 Force Virtual Input 7 0 1 1 --- FC103 0 1
43771 0xEBA Force Virtual Input 8 0 1 1 --- FC103 0 1
43772 0xEBB Force Virtual Input 9 0 1 1 --- FC103 0 1
43773 0xEBC Force Virtual Input 10 0 1 1 --- FC103 0 1
43774 0xEBD Force Virtual Input 11 0 1 1 --- FC103 0 1
43775 0xEBE Force Virtual Input 12 0 1 1 --- FC103 0 1
43776 0xEBF Force Virtual Input 13 0 1 1 --- FC103 0 1
43777 0xEC0 Force Virtual Input 14 0 1 1 --- FC103 0 1
43778 0xEC1 Force Virtual Input 15 0 1 1 --- FC103 0 1
43779 0xEC2 Force Virtual Input 16 0 1 1 --- FC103 0 1
43780 0xEC3 Force Virtual Input 17 0 1 1 --- FC103 0 1
43781 0xEC4 Force Virtual Input 18 0 1 1 --- FC103 0 1
43782 0xEC5 Force Virtual Input 19 0 1 1 --- FC103 0 1
43783 0xEC6 Force Virtual Input 20 0 1 1 --- FC103 0 1
43784 0xEC7 Force Virtual Input 21 0 1 1 --- FC103 0 1
43785 0xEC8 Force Virtual Input 22 0 1 1 --- FC103 0 1
43786 0xEC9 Force Virtual Input 23 0 1 1 --- FC103 0 1
43787 0xECA Force Virtual Input 24 0 1 1 --- FC103 0 1
43788 0xECB Force Virtual Input 25 0 1 1 --- FC103 0 1
43789 0xECC Force Virtual Input 26 0 1 1 --- FC103 0 1
43790 0xECD Force Virtual Input 27 0 1 1 --- FC103 0 1
43791 0xECE Force Virtual Input 28 0 1 1 --- FC103 0 1
43792 0xECF Force Virtual Input 29 0 1 1 --- FC103 0 1
43793 0xED0 Force Virtual Input 30 0 1 1 --- FC103 0 1
43794 0xED1 Force Virtual Input 31 0 1 1 --- FC103 0 1
43795 0xED2 Force Virtual Input 32 0 1 1 --- FC103 0 1
DNP OVER ETHERNET PORT
43836 0xEFB DNP/Ethernet Channel 1 0 2 1 --- F87 0 1
Port

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-45


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
43837 0xEFC DNP/Ethernet Channel 2 0 2 1 --- F87 0 1
Port
IEC60870-5-104 PROTOCOL
43838 0xEFD IEC 60870-5-104 Function 0 1 1 --- FC126 0 1
43839 0xEFE IEC TCP Port 1 65535 1 --- F1 2404 1
43840 0xEFF IEC Common Address of 0 65535 1 --- F1 0 1
ASDU
43841 0xF00 IEC Cyclic Data Period 0 65535 1 s F1 60 1
43842 0xF01 IEC TCP Connection Timeout 10 300 1 s F1 120 1
43843 0xF02 Object Information Address 1 16777215 1 --- F9 1000 2
Binary
43845 0xF04 Object Information Address 1 16777215 1 --- F9 2000 2
Analog
43847 0xF06 Object Information Address 1 16777215 1 --- F9 3000 2
Counters
43849 0xF08 Object Information Address 1 16777215 1 --- F9 4000 2
Command
DNP / IEC60870-5-104 SHARED SETTINGS
43851 0xF0A DNP Address 0 65519 1 --- F1 0 1
43852 0xF0B DNP Client Address 1 0 0xFFFFFFFF 1 --- FC150 0 2
43854 0xF0D DNP Client Address 2 0 0xFFFFFFFF 1 --- FC150 0 2
43856 0xF0F DNP Client Address 3 0 0xFFFFFFFF 1 --- FC150 0 2
43858 0xF11 DNP Client Address 4 0 0xFFFFFFFF 1 --- FC150 0 2
43860 0xF13 DNP Client Address 5 0 0xFFFFFFFF 1 --- FC150 0 2
43862 0xF15 DNP TCP/UDP Port Number 0 65535 1 --- F1 20000 1
43863 0xF16 DNP Unsolicited Response 0 1 1 --- FC126 0 1
Function
43864 0xF17 DNP Unsolicited Response 0 60 1 s F1 5 1
Timeout
43865 0xF18 DNP Unsolicited Response 1 255 1 --- F1 10 1
Maximum Retries
43866 0xF19 DNP Unsolicited Response 0 65519 1 --- F1 1 1
Destination Address
43867 0xF1A DNP Time Sync IIN Period 1 10080 1 min F1 1440 1
43868 0xF1B DNP Message Fragment Size 30 2048 1 --- F1 240 1
43869 0xF1C DNP Object 1 Default 1 2 1 --- F1 2 1
Variation
43870 0xF1D DNP Object 2 Default 1 2 1 --- F1 2 1
Variation
43871 0xF1E DNP Object 20 Default 1 6 1 --- F78 1 1
Variation
43872 0xF1F DNP Object 21 Default 1 10 1 --- F79 1 1
Variation
43873 0xF20 DNP Object 22 Default 1 6 1 --- F80 1 1
Variation
43874 0xF21 DNP Object 23 Default 1 6 1 --- F81 1 1
Variation
43875 0xF22 DNP Object 30 Default 1 4 1 --- F82 1 1
Variation
43876 0xF23 DNP Object 32 Default 1 4 1 --- F83 1 1
Variation
43877 0xF24 DNP TCP Connection 10 300 1 s F1 120 1
Timeout

10-46 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
DNP / IEC60870-5-103 / IEC60870-5-104 BINARY INPUTS
43878 0xF25 Binary Input Point 0 Entry 0 0xFFFF 1 --- FC134B 0 1
43879 0xF26 Binary Input Point 1 Entry 0 0xFFFF 1 --- FC134B 0 1
43880 0xF27 Binary Input Point 2 Entry 0 0xFFFF 1 --- FC134B 0 1
43881 0xF28 Binary Input Point 3 Entry 0 0xFFFF 1 --- FC134B 0 1
43882 0xF29 Binary Input Point 4 Entry 0 0xFFFF 1 --- FC134B 0 1
43883 0xF2A Binary Input Point 5 Entry 0 0xFFFF 1 --- FC134B 0 1
43884 0xF2B Binary Input Point 6 Entry 0 0xFFFF 1 --- FC134B 0 1
43885 0xF2C Binary Input Point 7 Entry 0 0xFFFF 1 --- FC134B 0 1
43886 0xF2D Binary Input Point 8 Entry 0 0xFFFF 1 --- FC134B 0 1
43887 0xF2E Binary Input Point 9 Entry 0 0xFFFF 1 --- FC134B 0 1
43888 0xF2F Binary Input Point 10 Entry 0 0xFFFF 1 --- FC134B 0 1
43889 0xF30 Binary Input Point 11 Entry 0 0xFFFF 1 --- FC134B 0 1
43890 0xF31 Binary Input Point 12 Entry 0 0xFFFF 1 --- FC134B 0 1
43891 0xF32 Binary Input Point 13 Entry 0 0xFFFF 1 --- FC134B 0 1
43892 0xF33 Binary Input Point 14 Entry 0 0xFFFF 1 --- FC134B 0 1
43893 0xF34 Binary Input Point 15 Entry 0 0xFFFF 1 --- FC134B 0 1
43894 0xF35 Binary Input Point 16 Entry 0 0xFFFF 1 --- FC134B 0 1
43895 0xF36 Binary Input Point 17 Entry 0 0xFFFF 1 --- FC134B 0 1
43896 0xF37 Binary Input Point 18 Entry 0 0xFFFF 1 --- FC134B 0 1
43897 0xF38 Binary Input Point 19 Entry 0 0xFFFF 1 --- FC134B 0 1
43898 0xF39 Binary Input Point 20 Entry 0 0xFFFF 1 --- FC134B 0 1
43899 0xF3A Binary Input Point 21 Entry 0 0xFFFF 1 --- FC134B 0 1
43900 0xF3B Binary Input Point 22 Entry 0 0xFFFF 1 --- FC134B 0 1
43901 0xF3C Binary Input Point 23 Entry 0 0xFFFF 1 --- FC134B 0 1
43902 0xF3D Binary Input Point 24 Entry 0 0xFFFF 1 --- FC134B 0 1
43903 0xF3E Binary Input Point 25 Entry 0 0xFFFF 1 --- FC134B 0 1
43904 0xF3F Binary Input Point 26 Entry 0 0xFFFF 1 --- FC134B 0 1
43905 0xF40 Binary Input Point 27 Entry 0 0xFFFF 1 --- FC134B 0 1
43906 0xF41 Binary Input Point 28 Entry 0 0xFFFF 1 --- FC134B 0 1
43907 0xF42 Binary Input Point 29 Entry 0 0xFFFF 1 --- FC134B 0 1
43908 0xF43 Binary Input Point 30 Entry 0 0xFFFF 1 --- FC134B 0 1
43909 0xF44 Binary Input Point 31 Entry 0 0xFFFF 1 --- FC134B 0 1
43910 0xF45 Binary Input Point 32 Entry 0 0xFFFF 1 --- FC134B 0 1
43911 0xF46 Binary Input Point 33 Entry 0 0xFFFF 1 --- FC134B 0 1
43912 0xF47 Binary Input Point 34 Entry 0 0xFFFF 1 --- FC134B 0 1
43913 0xF48 Binary Input Point 35 Entry 0 0xFFFF 1 --- FC134B 0 1
43914 0xF49 Binary Input Point 36 Entry 0 0xFFFF 1 --- FC134B 0 1
43915 0xF4A Binary Input Point 37 Entry 0 0xFFFF 1 --- FC134B 0 1
43916 0xF4B Binary Input Point 38 Entry 0 0xFFFF 1 --- FC134B 0 1
43917 0xF4C Binary Input Point 39 Entry 0 0xFFFF 1 --- FC134B 0 1
43918 0xF4D Binary Input Point 40 Entry 0 0xFFFF 1 --- FC134B 0 1
43919 0xF4E Binary Input Point 41 Entry 0 0xFFFF 1 --- FC134B 0 1
43920 0xF4F Binary Input Point 42 Entry 0 0xFFFF 1 --- FC134B 0 1
43921 0xF50 Binary Input Point 43 Entry 0 0xFFFF 1 --- FC134B 0 1
43922 0xF51 Binary Input Point 44 Entry 0 0xFFFF 1 --- FC134B 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-47


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
43923 0xF52 Binary Input Point 45 Entry 0 0xFFFF 1 --- FC134B 0 1
43924 0xF53 Binary Input Point 46 Entry 0 0xFFFF 1 --- FC134B 0 1
43925 0xF54 Binary Input Point 47 Entry 0 0xFFFF 1 --- FC134B 0 1
43926 0xF55 Binary Input Point 48 Entry 0 0xFFFF 1 --- FC134B 0 1
43927 0xF56 Binary Input Point 49 Entry 0 0xFFFF 1 --- FC134B 0 1
43928 0xF57 Binary Input Point 50 Entry 0 0xFFFF 1 --- FC134B 0 1
43929 0xF58 Binary Input Point 51 Entry 0 0xFFFF 1 --- FC134B 0 1
43930 0xF59 Binary Input Point 52 Entry 0 0xFFFF 1 --- FC134B 0 1
43931 0xF5A Binary Input Point 53 Entry 0 0xFFFF 1 --- FC134B 0 1
43932 0xF5B Binary Input Point 54 Entry 0 0xFFFF 1 --- FC134B 0 1
43933 0xF5C Binary Input Point 55 Entry 0 0xFFFF 1 --- FC134B 0 1
43934 0xF5D Binary Input Point 56 Entry 0 0xFFFF 1 --- FC134B 0 1
43935 0xF5E Binary Input Point 57 Entry 0 0xFFFF 1 --- FC134B 0 1
43936 0xF5F Binary Input Point 58 Entry 0 0xFFFF 1 --- FC134B 0 1
43937 0xF60 Binary Input Point 59 Entry 0 0xFFFF 1 --- FC134B 0 1
43938 0xF61 Binary Input Point 60 Entry 0 0xFFFF 1 --- FC134B 0 1
43939 0xF62 Binary Input Point 61 Entry 0 0xFFFF 1 --- FC134B 0 1
43940 0xF63 Binary Input Point 62 Entry 0 0xFFFF 1 --- FC134B 0 1
43941 0xF64 Binary Input Point 63 Entry 0 0xFFFF 1 --- FC134B 0 1
DNP / IEC60870-5-104 BINARY OUTPUTS
44070 0xFE5 Binary Output Point 0 ON 0 40 1 --- F86 0 1
44071 0xFE6 Binary Output Point 0 OFF 0 40 1 --- F86 0 1
44072 0xFE7 Binary Output Point 1 ON 0 40 1 --- F86 0 1
44073 0xFE8 Binary Output Point 1 OFF 0 40 1 --- F86 0 1
44074 0xFE9 Binary Output Point 2 ON 0 40 1 --- F86 0 1
44075 0xFEA Binary Output Point 2 OFF 0 40 1 --- F86 0 1
44076 0xFEB Binary Output Point 3 ON 0 40 1 --- F86 0 1
44077 0xFEC Binary Output Point 3 OFF 0 40 1 --- F86 0 1
44078 0xFED Binary Output Point 4 ON 0 40 1 --- F86 0 1
44079 0xFEE Binary Output Point 4 OFF 0 40 1 --- F86 0 1
44080 0xFEF Binary Output Point 5 ON 0 40 1 --- F86 0 1
44081 0xFF0 Binary Output Point 5 OFF 0 40 1 --- F86 0 1
44082 0xFF1 Binary Output Point 6 ON 0 40 1 --- F86 0 1
44083 0xFF2 Binary Output Point 6 OFF 0 40 1 --- F86 0 1
44084 0xFF3 Binary Output Point 7 ON 0 40 1 --- F86 0 1
44085 0xFF4 Binary Output Point 7 OFF 0 40 1 --- F86 0 1
44086 0xFF5 Binary Output Point 8 ON 0 40 1 --- F86 0 1
44087 0xFF6 Binary Output Point 8 OFF 0 40 1 --- F86 0 1
44088 0xFF7 Binary Output Point 9 ON 0 40 1 --- F86 0 1
44089 0xFF8 Binary Output Point 9 OFF 0 40 1 --- F86 0 1
44090 0xFF9 Binary Output Point 10 ON 0 40 1 --- F86 0 1
44091 0xFFA Binary Output Point 10 OFF 0 40 1 --- F86 0 1
44092 0xFFB Binary Output Point 11 ON 0 40 1 --- F86 0 1
44093 0xFFC Binary Output Point 11 OFF 0 40 1 --- F86 0 1
44094 0xFFD Binary Output Point 12 ON 0 40 1 --- F86 0 1
44095 0xFFE Binary Output Point 12 OFF 0 40 1 --- F86 0 1

10-48 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44096 0xFFF Binary Output Point 13 ON 0 40 1 --- F86 0 1
44097 0x1000 Binary Output Point 13 OFF 0 40 1 --- F86 0 1
44098 0x1001 Binary Output Point 14 ON 0 40 1 --- F86 0 1
44099 0x1002 Binary Output Point 14 OFF 0 40 1 --- F86 0 1
44100 0x1003 Binary Output Point 15 ON 0 40 1 --- F86 0 1
44101 0x1004 Binary Output Point 15 OFF 0 40 1 --- F86 0 1
DNP / IEC60870-5-104 ANALOG INPUTS
43942 0xF65 Analog Input Point 0 Entry 0 251 1 --- F88 0 1
43943 0xF66 Analog Input Point 0 Scale 1 9 1 --- F85 4 1
Factor
43944 0xF67 Analog Input Point 0 0 100000000 1 --- F9 30000 2
Deadband
43946 0xF69 Analog Input Point 1 Entry 0 251 1 --- F88 0 1
43947 0xF6A Analog Input Point 1 Scale 1 9 1 --- F85 4 1
Factor
43948 0xF6B Analog Input Point 1 0 100000000 1 --- F9 30000 2
Deadband
43950 0xF6D Analog Input Point 2 Entry 0 251 1 --- F88 0 1
43951 0xF6E Analog Input Point 2 Scale 1 9 1 --- F85 4 1
Factor
43952 0xF6F Analog Input Point 2 0 100000000 1 --- F9 30000 2
Deadband
43954 0xF71 Analog Input Point 3 Entry 0 251 1 --- F88 0 1
43955 0xF72 Analog Input Point 3 Scale 1 9 1 --- F85 4 1
Factor
43956 0xF73 Analog Input Point 3 0 100000000 1 --- F9 30000 2
Deadband
43958 0xF75 Analog Input Point 4 Entry 0 251 1 --- F88 0 1
43959 0xF76 Analog Input Point 4 Scale 1 9 1 --- F85 4 1
Factor
43960 0xF77 Analog Input Point 4 0 100000000 1 --- F9 30000 2
Deadband
43962 0xF79 Analog Input Point 5 Entry 0 251 1 --- F88 0 1
43963 0xF7A Analog Input Point 5 Scale 1 9 1 --- F85 4 1
Factor
43964 0xF7B Analog Input Point 5 0 100000000 1 --- F9 30000 2
Deadband
43966 0xF7D Analog Input Point 6 Entry 0 251 1 --- F88 0 1
43967 0xF7E Analog Input Point 6 Scale 1 9 1 --- F85 4 1
Factor
43968 0xF7F Analog Input Point 6 0 100000000 1 --- F9 30000 2
Deadband
43970 0xF81 Analog Input Point 7 Entry 0 251 1 --- F88 0 1
43971 0xF82 Analog Input Point 7 Scale 1 9 1 --- F85 4 1
Factor
43972 0xF83 Analog Input Point 7 0 100000000 1 --- F9 30000 2
Deadband
43974 0xF85 Analog Input Point 8 Entry 0 251 1 --- F88 0 1
43975 0xF86 Analog Input Point 8 Scale 1 9 1 --- F85 4 1
Factor
43976 0xF87 Analog Input Point 8 0 100000000 1 --- F9 30000 2
Deadband
43978 0xF89 Analog Input Point 9 Entry 0 251 1 --- F88 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-49


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
43979 0xF8A Analog Input Point 9 Scale 1 9 1 --- F85 4 1
Factor
43980 0xF8B Analog Input Point 9 0 100000000 1 --- F9 30000 2
Deadband
43982 0xF8D Analog Input Point 10 Entry 0 251 1 --- F88 0 1
43983 0xF8E Analog Input Point 10 Scale 1 9 1 --- F85 4 1
Factor
43984 0xF8F Analog Input Point 10 0 100000000 1 --- F9 30000 2
Deadband
43986 0xF91 Analog Input Point 11 Entry 0 251 1 --- F88 0 1
43987 0xF92 Analog Input Point 11 Scale 1 9 1 --- F85 4 1
Factor
43988 0xF93 Analog Input Point 11 0 100000000 1 --- F9 30000 2
Deadband
43990 0xF95 Analog Input Point 12 Entry 0 251 1 --- F88 0 1
43991 0xF96 Analog Input Point 12 Scale 1 9 1 --- F85 4 1
Factor
43992 0xF97 Analog Input Point 12 0 100000000 1 --- F9 30000 2
Deadband
43994 0xF99 Analog Input Point 13 Entry 0 251 1 --- F88 0 1
43995 0xF9A Analog Input Point 13 Scale 1 9 1 --- F85 4 1
Factor
43996 0xF9B Analog Input Point 13 0 100000000 1 --- F9 30000 2
Deadband
43998 0xF9D Analog Input Point 14 Entry 0 251 1 --- F88 0 1
43999 0xF9E Analog Input Point 14 Scale 1 9 1 --- F85 4 1
Factor
44000 0xF9F Analog Input Point 14 0 100000000 1 --- F9 30000 2
Deadband
44002 0xFA1 Analog Input Point 15 Entry 0 251 1 --- F88 0 1
44003 0xFA2 Analog Input Point 15 Scale 1 9 1 --- F85 4 1
Factor
44004 0xFA3 Analog Input Point 15 0 100000000 1 --- F9 30000 2
Deadband
44006 0xFA5 Analog Input Point 16 Entry 0 251 1 --- F88 0 1
44007 0xFA6 Analog Input Point 16 Scale 1 9 1 --- F85 4 1
Factor
44008 0xFA7 Analog Input Point 16 0 100000000 1 --- F9 30000 2
Deadband
44010 0xFA9 Analog Input Point 17 Entry 0 251 1 --- F88 0 1
44011 0xFAA Analog Input Point 17 Scale 1 9 1 --- F85 4 1
Factor
44012 0xFAB Analog Input Point 17 0 100000000 1 --- F9 30000 2
Deadband
44014 0xFAD Analog Input Point 18 Entry 0 251 1 --- F88 0 1
44015 0xFAE Analog Input Point 18 Scale 1 9 1 --- F85 4 1
Factor
44016 0xFAF Analog Input Point 18 0 100000000 1 --- F9 30000 2
Deadband
44018 0xFB1 Analog Input Point 19 Entry 0 251 1 --- F88 0 1
44019 0xFB2 Analog Input Point 19 Scale 1 9 1 --- F85 4 1
Factor
44020 0xFB3 Analog Input Point 19 0 100000000 1 --- F9 30000 2
Deadband

10-50 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44022 0xFB5 Analog Input Point 20 Entry 0 251 1 --- F88 0 1
44023 0xFB6 Analog Input Point 20 Scale 1 9 1 --- F85 4 1
Factor
44024 0xFB7 Analog Input Point 20 0 100000000 1 --- F9 30000 2
Deadband
44026 0xFB9 Analog Input Point 21 Entry 0 251 1 --- F88 0 1
44027 0xFBA Analog Input Point 21 Scale 1 9 1 --- F85 4 1
Factor
44028 0xFBB Analog Input Point 21 0 100000000 1 --- F9 30000 2
Deadband
44030 0xFBD Analog Input Point 22 Entry 0 251 1 --- F88 0 1
44031 0xFBE Analog Input Point 22 Scale 1 9 1 --- F85 4 1
Factor
44032 0xFBF Analog Input Point 22 0 100000000 1 --- F9 30000 2
Deadband
44034 0xFC1 Analog Input Point 23 Entry 0 251 1 --- F88 0 1
44035 0xFC2 Analog Input Point 23 Scale 1 9 1 --- F85 4 1
Factor
44036 0xFC3 Analog Input Point 23 0 100000000 1 --- F9 30000 2
Deadband
44038 0xFC5 Analog Input Point 24 Entry 0 251 1 --- F88 0 1
44039 0xFC6 Analog Input Point 24 Scale 1 9 1 --- F85 4 1
Factor
44040 0xFC7 Analog Input Point 24 0 100000000 1 --- F9 30000 2
Deadband
44042 0xFC9 Analog Input Point 25 Entry 0 251 1 --- F88 0 1
44043 0xFCA Analog Input Point 25 Scale 1 9 1 --- F85 4 1
Factor
44044 0xFCB Analog Input Point 25 0 100000000 1 --- F9 30000 2
Deadband
44046 0xFCD Analog Input Point 26 Entry 0 251 1 --- F88 0 1
44047 0xFCE Analog Input Point 26 Scale 1 9 1 --- F85 4 1
Factor
44048 0xFCF Analog Input Point 26 0 100000000 1 --- F9 30000 2
Deadband
44050 0xFD1 Analog Input Point 27 Entry 0 251 1 --- F88 0 1
44051 0xFD2 Analog Input Point 27 Scale 1 9 1 --- F85 4 1
Factor
44052 0xFD3 Analog Input Point 27 0 100000000 1 --- F9 30000 2
Deadband
44054 0xFD5 Analog Input Point 28 Entry 0 251 1 --- F88 0 1
44055 0xFD6 Analog Input Point 28 Scale 1 9 1 --- F85 4 1
Factor
44056 0xFD7 Analog Input Point 28 0 100000000 1 --- F9 30000 2
Deadband
44058 0xFD9 Analog Input Point 29 Entry 0 251 1 --- F88 0 1
44059 0xFDA Analog Input Point 29 Scale 1 9 1 --- F85 4 1
Factor
44060 0xFDB Analog Input Point 29 0 100000000 1 --- F9 30000 2
Deadband
44062 0xFDD Analog Input Point 30 Entry 0 251 1 --- F88 0 1
44063 0xFDE Analog Input Point 30 Scale 1 9 1 --- F85 4 1
Factor

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-51


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44064 0xFDF Analog Input Point 30 0 100000000 1 --- F9 30000 2
Deadband
44066 0xFE1 Analog Input Point 31 Entry 0 251 1 --- F88 0 1
44067 0xFE2 Analog Input Point 31 Scale 1 9 1 --- F85 4 1
Factor
44068 0xFE3 Analog Input Point 31 0 100000000 1 --- F9 30000 2
Deadband
44102 0x1005 Fault Report Mapping 0 1 1 --- FC126 0 1
Enable
AUTORECLOSE
44152 0x1037 Negative Sequence TOC 0 1 1 --- FC103 0 1
Shot 1
44172 0x104B Negative Sequence TOC 0 1 1 --- FC103 0 1
Shot 2
44192 0x105F Negative Sequence TOC 0 1 1 --- FC103 0 1
Shot 3
44197 0x1064 Negative Sequence TOC 0 1 1 --- FC103 0 1
Shot 4
IEC60870-5-103 BINARY INPUT POINTS
44221 0x107C Binary In Point 0 Entry 0 255 1 --- F1 0 1
Function Type
44222 0x107D Binary In Point 0 Entry 0 255 1 --- F1 0 1
Information Number
44223 0x107E Binary In Point 1 Entry 0 255 1 --- F1 0 1
Function Type
44224 0x107F Binary In Point 1 Entry 0 255 1 --- F1 0 1
Information Number
44225 0x1080 Binary In Point 2 Entry 0 255 1 --- F1 0 1
Function Type
44226 0x1081 Binary In Point 2 Entry 0 255 1 --- F1 0 1
Information Number
44227 0x1082 Binary In Point 3 Entry 0 255 1 --- F1 0 1
Function Type
44228 0x1083 Binary In Point 3 Entry 0 255 1 --- F1 0 1
Information Number
44229 0x1084 Binary In Point 4 Entry 0 255 1 --- F1 0 1
Function Type
44230 0x1085 Binary In Point 4 Entry 0 255 1 --- F1 0 1
Information Number
44231 0x1086 Binary In Point 5 Entry 0 255 1 --- F1 0 1
Function Type
44232 0x1087 Binary In Point 5 Entry 0 255 1 --- F1 0 1
Information Number
44233 0x1088 Binary In Point 6 Entry 0 255 1 --- F1 0 1
Function Type
44234 0x1089 Binary In Point 6 Entry 0 255 1 --- F1 0 1
Information Number
44235 0x108A Binary In Point 7 Entry 0 255 1 --- F1 0 1
Function Type
44236 0x108B Binary In Point 7 Entry 0 255 1 --- F1 0 1
Information Number
44237 0x108C Binary In Point 8 Entry 0 255 1 --- F1 0 1
Function Type
44238 0x108D Binary In Point 8 Entry 0 255 1 --- F1 0 1
Information Number

10-52 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44239 0x108E Binary In Point 9 Entry 0 255 1 --- F1 0 1
Function Type
44240 0x108F Binary In Point 9 Entry 0 255 1 --- F1 0 1
Information Number
44241 0x1090 Binary In Point 10 Entry 0 255 1 --- F1 0 1
Function Type
44242 0x1091 Binary In Point 10 Entry 0 255 1 --- F1 0 1
Information Number
44243 0x1092 Binary In Point 11 Entry 0 255 1 --- F1 0 1
Function Type
44244 0x1093 Binary In Point 11 Entry 0 255 1 --- F1 0 1
Information Number
44245 0x1094 Binary In Point 12 Entry 0 255 1 --- F1 0 1
Function Type
44246 0x1095 Binary In Point 12 Entry 0 255 1 --- F1 0 1
Information Number
44247 0x1096 Binary In Point 13 Entry 0 255 1 --- F1 0 1
Function Type
44248 0x1097 Binary In Point 13 Entry 0 255 1 --- F1 0 1
Information Number
44249 0x1098 Binary In Point 14 Entry 0 255 1 --- F1 0 1
Function Type
44250 0x1099 Binary In Point 14 Entry 0 255 1 --- F1 0 1
Information Number
44251 0x109A Binary In Point 15 Entry 0 255 1 --- F1 0 1
Function Type
44252 0x109B Binary In Point 15 Entry 0 255 1 --- F1 0 1
Information Number
44253 0x109C Binary In Point 16 Entry 0 255 1 --- F1 0 1
Function Type
44254 0x109D Binary In Point 16 Entry 0 255 1 --- F1 0 1
Information Number
44255 0x109E Binary In Point 17 Entry 0 255 1 --- F1 0 1
Function Type
44256 0x109F Binary In Point 17 Entry 0 255 1 --- F1 0 1
Information Number
44257 0x10A0 Binary In Point 18 Entry 0 255 1 --- F1 0 1
Function Type
44258 0x10A1 Binary In Point 18 Entry 0 255 1 --- F1 0 1
Information Number
44259 0x10A2 Binary In Point 19 Entry 0 255 1 --- F1 0 1
Function Type
44260 0x10A3 Binary In Point 19 Entry 0 255 1 --- F1 0 1
Information Number
44261 0x10A4 Binary In Point 20 Entry 0 255 1 --- F1 0 1
Function Type
44262 0x10A5 Binary In Point 20 Entry 0 255 1 --- F1 0 1
Information Number
44263 0x10A6 Binary In Point 21 Entry 0 255 1 --- F1 0 1
Function Type
44264 0x10A7 Binary In Point 21 Entry 0 255 1 --- F1 0 1
Information Number
44265 0x10A8 Binary In Point 22 Entry 0 255 1 --- F1 0 1
Function Type
44266 0x10A9 Binary In Point 22 Entry 0 255 1 --- F1 0 1
Information Number

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-53


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44267 0x10AA Binary In Point 23 Entry 0 255 1 --- F1 0 1
Function Type
44268 0x10AB Binary In Point 23 Entry 0 255 1 --- F1 0 1
Information Number
44269 0x10AC Binary In Point 24 Entry 0 255 1 --- F1 0 1
Function Type
44270 0x10AD Binary In Point 24 Entry 0 255 1 --- F1 0 1
Information Number
44271 0x10AE Binary In Point 25 Entry 0 255 1 --- F1 0 1
Function Type
44272 0x10AF Binary In Point 25 Entry 0 255 1 --- F1 0 1
Information Number
44273 0x10B0 Binary In Point 26 Entry 0 255 1 --- F1 0 1
Function Type
44274 0x10B1 Binary In Point 26 Entry 0 255 1 --- F1 0 1
Information Number
44275 0x10B2 Binary In Point 27 Entry 0 255 1 --- F1 0 1
Function Type
44276 0x10B3 Binary In Point 27 Entry 0 255 1 --- F1 0 1
Information Number
44277 0x10B4 Binary In Point 28 Entry 0 255 1 --- F1 0 1
Function Type
44278 0x10B5 Binary In Point 28 Entry 0 255 1 --- F1 0 1
Information Number
44279 0x10B6 Binary In Point 29 Entry 0 255 1 --- F1 0 1
Function Type
44280 0x10B7 Binary In Point 29 Entry 0 255 1 --- F1 0 1
Information Number
44281 0x10B8 Binary In Point 30 Entry 0 255 1 --- F1 0 1
Function Type
44282 0x10B9 Binary In Point 30 Entry 0 255 1 --- F1 0 1
Information Number
44283 0x10BA Binary In Point 31 Entry 0 255 1 --- F1 0 1
Function Type
44284 0x10BB Binary In Point 31 Entry 0 255 1 --- F1 0 1
Information Number
44285 0x10BC Binary In Point 32 Entry 0 255 1 --- F1 0 1
Function Type
44286 0x10BD Binary In Point 32 Entry 0 255 1 --- F1 0 1
Information Number
44287 0x10BE Binary In Point 33 Entry 0 255 1 --- F1 0 1
Function Type
44288 0x10BF Binary In Point 33 Entry 0 255 1 --- F1 0 1
Information Number
44289 0x10C0 Binary In Point 34 Entry 0 255 1 --- F1 0 1
Function Type
44290 0x10C1 Binary In Point 34 Entry 0 255 1 --- F1 0 1
Information Number
44291 0x10C2 Binary In Point 35 Entry 0 255 1 --- F1 0 1
Function Type
44292 0x10C3 Binary In Point 35 Entry 0 255 1 --- F1 0 1
Information Number
44293 0x10C4 Binary In Point 36 Entry 0 255 1 --- F1 0 1
Function Type
44294 0x10C5 Binary In Point 36 Entry 0 255 1 --- F1 0 1
Information Number

10-54 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44295 0x10C6 Binary In Point 37 Entry 0 255 1 --- F1 0 1
Function Type
44296 0x10C7 Binary In Point 37 Entry 0 255 1 --- F1 0 1
Information Number
44297 0x10C8 Binary In Point 38 Entry 0 255 1 --- F1 0 1
Function Type
44298 0x10C9 Binary In Point 38 Entry 0 255 1 --- F1 0 1
Information Number
44299 0x10CA Binary In Point 39 Entry 0 255 1 --- F1 0 1
Function Type
44300 0x10CB Binary In Point 39 Entry 0 255 1 --- F1 0 1
Information Number
44301 0x10CC Binary In Point 40 Entry 0 255 1 --- F1 0 1
Function Type
44302 0x10CD Binary In Point 40 Entry 0 255 1 --- F1 0 1
Information Number
44303 0x10CE Binary In Point 41 Entry 0 255 1 --- F1 0 1
Function Type
44304 0x10CF Binary In Point 41 Entry 0 255 1 --- F1 0 1
Information Number
44305 0x10D0 Binary In Point 42 Entry 0 255 1 --- F1 0 1
Function Type
44306 0x10D1 Binary In Point 42 Entry 0 255 1 --- F1 0 1
Information Number
44307 0x10D2 Binary In Point 43 Entry 0 255 1 --- F1 0 1
Function Type
44308 0x10D3 Binary In Point 43 Entry 0 255 1 --- F1 0 1
Information Number
44309 0x10D4 Binary In Point 44 Entry 0 255 1 --- F1 0 1
Function Type
44310 0x10D5 Binary In Point 44 Entry 0 255 1 --- F1 0 1
Information Number
44311 0x10D6 Binary In Point 45 Entry 0 255 1 --- F1 0 1
Function Type
44312 0x10D7 Binary In Point 45 Entry 0 255 1 --- F1 0 1
Information Number
44313 0x10D8 Binary In Point 46 Entry 0 255 1 --- F1 0 1
Function Type
44314 0x10D9 Binary In Point 46 Entry 0 255 1 --- F1 0 1
Information Number
44315 0x10DA Binary In Point 47 Entry 0 255 1 --- F1 0 1
Function Type
44316 0x10DB Binary In Point 47 Entry 0 255 1 --- F1 0 1
Information Number
44317 0x10DC Binary In Point 48 Entry 0 255 1 --- F1 0 1
Function Type
44318 0x10DD Binary In Point 48 Entry 0 255 1 --- F1 0 1
Information Number
44319 0x10DE Binary In Point 49 Entry 0 255 1 --- F1 0 1
Function Type
44320 0x10DF Binary In Point 49 Entry 0 255 1 --- F1 0 1
Information Number
44321 0x10E0 Binary In Point 50 Entry 0 255 1 --- F1 0 1
Function Type
44322 0x10E1 Binary In Point 50 Entry 0 255 1 --- F1 0 1
Information Number

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-55


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44323 0x10E2 Binary In Point 51 Entry 0 255 1 --- F1 0 1
Function Type
44324 0x10E3 Binary In Point 51 Entry 0 255 1 --- F1 0 1
Information Number
44325 0x10E4 Binary In Point 52 Entry 0 255 1 --- F1 0 1
Function Type
44326 0x10E5 Binary In Point 52 Entry 0 255 1 --- F1 0 1
Information Number
44327 0x10E6 Binary In Point 53 Entry 0 255 1 --- F1 0 1
Function Type
44328 0x10E7 Binary In Point 53 Entry 0 255 1 --- F1 0 1
Information Number
44329 0x10E8 Binary In Point 54 Entry 0 255 1 --- F1 0 1
Function Type
44330 0x10E9 Binary In Point 54 Entry 0 255 1 --- F1 0 1
Information Number
44331 0x10EA Binary In Point 55 Entry 0 255 1 --- F1 0 1
Function Type
44332 0x10EB Binary In Point 55 Entry 0 255 1 --- F1 0 1
Information Number
44333 0x10EC Binary In Point 56 Entry 0 255 1 --- F1 0 1
Function Type
44334 0x10ED Binary In Point 56 Entry 0 255 1 --- F1 0 1
Information Number
44335 0x10EE Binary In Point 57 Entry 0 255 1 --- F1 0 1
Function Type
44336 0x10EF Binary In Point 57 Entry 0 255 1 --- F1 0 1
Information Number
44337 0x10F0 Binary In Point 58 Entry 0 255 1 --- F1 0 1
Function Type
44338 0x10F1 Binary In Point 58 Entry 0 255 1 --- F1 0 1
Information Number
44339 0x10F2 Binary In Point 59 Entry 0 255 1 --- F1 0 1
Function Type
44340 0x10F3 Binary In Point 59 Entry 0 255 1 --- F1 0 1
Information Number
44341 0x10F4 Binary In Point 60 Entry 0 255 1 --- F1 0 1
Function Type
44342 0x10F5 Binary In Point 60 Entry 0 255 1 --- F1 0 1
Information Number
44343 0x10F6 Binary In Point 61 Entry 0 255 1 --- F1 0 1
Function Type
44344 0x10F7 Binary In Point 61 Entry 0 255 1 --- F1 0 1
Information Number
44345 0x10F8 Binary In Point 62 Entry 0 255 1 --- F1 0 1
Function Type
44346 0x10F9 Binary In Point 62 Entry 0 255 1 --- F1 0 1
Information Number
44347 0x10FA Binary In Point 63 Entry 0 255 1 --- F1 0 1
Function Type
44348 0x10FB Binary In Point 63 Entry 0 255 1 --- F1 0 1
Information Number
DNP / IEC60870-5-103 BINARY OUTPUT POINTS
44349 0x10FC Binary Out Point 0 Entry 0 255 1 --- F1 0 1
Function Type

10-56 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44350 0x10FD Binary Out Point 0 Entry 0 255 1 --- F1 0 1
Information Number
44351 0x10FE Binary Out Point 1 Entry 0 255 1 --- F1 0 1
Function Type
44352 0x10FF Binary Out Point 1 Entry 0 255 1 --- F1 0 1
Information Number
44353 0x1100 Binary Out Point 2 Entry 0 255 1 --- F1 0 1
Function Type
44354 0x1101 Binary Out Point 2 Entry 0 255 1 --- F1 0 1
Information Number
44355 0x1102 Binary Out Point 3 Entry 0 255 1 --- F1 0 1
Function Type
44356 0x1103 Binary Out Point 3 Entry 0 255 1 --- F1 0 1
Information Number
44357 0x1104 Binary Out Point 4 Entry 0 255 1 --- F1 0 1
Function Type
44358 0x1105 Binary Out Point 4 Entry 0 255 1 --- F1 0 1
Information Number
44359 0x1106 Binary Out Point 5 Entry 0 255 1 --- F1 0 1
Function Type
44360 0x1107 Binary Out Point 5 Entry 0 255 1 --- F1 0 1
Information Number
44361 0x1108 Binary Out Point 6 Entry 0 255 1 --- F1 0 1
Function Type
44362 0x1109 Binary Out Point 6 Entry 0 255 1 --- F1 0 1
Information Number
44363 0x110A Binary Out Point 7 Entry 0 255 1 --- F1 0 1
Function Type
44364 0x110B Binary Out Point 7 Entry 0 255 1 --- F1 0 1
Information Number
44365 0x110C Binary Out Point 8 Entry 0 255 1 --- F1 0 1
Function Type
44366 0x110D Binary Out Point 8 Entry 0 255 1 --- F1 0 1
Information Number
44367 0x110E Binary Out Point 9 Entry 0 255 1 --- F1 0 1
Function Type
44368 0x110F Binary Out Point 9 Entry 0 255 1 --- F1 0 1
Information Number
44369 0x1110 Binary Out Point 10 Entry 0 255 1 --- F1 0 1
Function Type
44370 0x1111 Binary Out Point 10 Entry 0 255 1 --- F1 0 1
Information Number
44371 0x1112 Binary Out Point 11 Entry 0 255 1 --- F1 0 1
Function Type
44372 0x1113 Binary Out Point 11 Entry 0 255 1 --- F1 0 1
Information Number
44373 0x1114 Binary Out Point 12 Entry 0 255 1 --- F1 0 1
Function Type
44374 0x1115 Binary Out Point 12 Entry 0 255 1 --- F1 0 1
Information Number
44375 0x1116 Binary Out Point 13 Entry 0 255 1 --- F1 0 1
Function Type
44376 0x1117 Binary Out Point 13 Entry 0 255 1 --- F1 0 1
Information Number
44377 0x1118 Binary Out Point 14 Entry 0 255 1 --- F1 0 1
Function Type

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-57


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44378 0x1119 Binary Out Point 14 Entry 0 255 1 --- F1 0 1
Information Number
44379 0x111A Binary Out Point 15 Entry 0 255 1 --- F1 0 1
Function Type
44380 0x111B Binary Out Point 15 Entry 0 255 1 --- F1 0 1
Information Number
DNP / IEC60870-5-103 ADDRESSING
44382 0x111D IEC60870-5-103 Slave 0 254 1 --- F1 0 1
Address
44383 0x111E Synchronization Timeout 0 1440 1 min F1 0 1
IEC60870-5-103 MEASURANDS
44384 0x111F 103 First ASDU Identification 3 9 1 --- FC221 3 1
Type
44385 0x1120 103 First ASDU Function 0 255 1 --- F1 0 1
Type
44386 0x1121 103 First ASDU Information 0 255 1 --- F1 0 1
Number
44387 0x1122 103 First ASDU Scan 0 1000 1 s F1 0 1
Timeout
44388 0x1123 103 First ASDU First 0 251 1 --- F88 0 1
Analogue Entry
44389 0x1124 103 First ASDU First 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44390 0x1125 103 First ASDU First 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44391 0x1126 103 First ASDU Second 0 251 1 --- F88 0 1
Analogue Entry
44392 0x1127 103 First ASDU Second 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44393 0x1128 103 First ASDU Second 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44394 0x1129 103 First ASDU Third 0 251 1 --- F88 0 1
Analogue Entry
44395 0x112A 103 First ASDU Third 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44396 0x112B 103 First ASDU Third 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44397 0x112C 103 First ASDU Fourth 0 251 1 --- F88 0 1
Analogue Entry
44398 0x112D 103 First ASDU Fourth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44399 0x112E 103 First ASDU Fourth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44400 0x112F 103 First ASDU Fifth 0 251 1 --- F88 0 1
Analogue Entry
44401 0x1130 103 First ASDU Fifth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44402 0x1131 103 First ASDU Fifth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44403 0x1132 103 First ASDU Sixth 0 251 1 --- F88 0 1
Analogue Entry
44404 0x1133 103 First ASDU Sixth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44405 0x1134 103 First ASDU Sixth 0 0xFFFF 1 --- F1 0 1
Analogue Offset

10-58 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44406 0x1135 103 First ASDU Seventh 0 251 1 --- F88 0 1
Analogue Entry
44407 0x1136 103 First ASDU Seventh 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44408 0x1137 103 First ASDU Seventh 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44409 0x1138 103 First ASDU Eigth 0 251 1 --- F88 0 1
Analogue Entry
44410 0x1139 103 First ASDU Eigth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44411 0x113A 103 First ASDU Eigth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44412 0x113B 103 First ASDU Ninth 0 251 1 --- F88 0 1
Analogue Entry
44413 0x113C 103 First ASDU Ninth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44414 0x113D 103 First ASDU Ninth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44415 0x113E 103 Second ASDU 3 9 1 --- FC221 3 1
Identification Type
44416 0x113F 103 Second ASDU Function 0 255 1 --- F1 0 1
Type
44417 0x1140 103 Second ASDU 0 255 1 --- F1 0 1
Information Number
44418 0x1141 103 Second ASDU Scan 0 1000 1 s F1 0 1
Timeout
44419 0x1142 103 Second ASDU First 0 251 1 --- F88 0 1
Analogue Entry
44420 0x1143 103 Second ASDU First 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44421 0x1144 103 Second ASDU First 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44422 0x1145 103 Second ASDU Second 0 251 1 --- F88 0 1
Analogue Entry
44423 0x1146 103 Second ASDU Second 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44424 0x1147 103 Second ASDU Second 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44425 0x1148 103 Second ASDU Third 0 251 1 --- F88 0 1
Analogue Entry
44426 0x1149 103 Second ASDU Third 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44427 0x114A 103 Second ASDU Third 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44428 0x114B 103 Second ASDU Fourth 0 251 1 --- F88 0 1
Analogue Entry
44429 0x114C 103 Second ASDU Fourth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44430 0x114D 103 Second ASDU Fourth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44431 0x114E 103 Second ASDU Fifth 0 251 1 --- F88 0 1
Analogue Entry
44432 0x114F 103 Second ASDU Fifth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44433 0x1150 103 Second ASDU Fifth 0 0xFFFF 1 --- F1 0 1
Analogue Offset

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-59


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44434 0x1151 103 Second ASDU Sixth 0 251 1 --- F88 0 1
Analogue Entry
44435 0x1152 103 Second ASDU Sixth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44436 0x1153 103 Second ASDU Sixth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44437 0x1154 103 Second ASDU Seventh 0 251 1 --- F88 0 1
Analogue Entry
44438 0x1155 103 Second ASDU Seventh 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44439 0x1156 103 Second ASDU Seventh 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44440 0x1157 103 Second ASDU Eigth 0 251 1 --- F88 0 1
Analogue Entry
44441 0x1158 103 Second ASDU Eigth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44442 0x1159 103 Second ASDU Eigth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44443 0x115A 103 Second ASDU Ninth 0 251 1 --- F88 0 1
Analogue Entry
44444 0x115B 103 Second ASDU Ninth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44445 0x115C 103 Second ASDU Ninth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44446 0x115D 103 Third ASDU 3 9 1 --- FC221 3 1
Identification Type
44447 0x115E 103 Third ASDU Function 0 255 1 --- F1 0 1
Type
44448 0x115F 103 Third ASDU Information 0 255 1 --- F1 0 1
Number
44449 0x1160 103 Third ASDU Scan 0 1000 1 s F1 0 1
Timeout
44450 0x1161 103 Third ASDU First 0 251 1 --- F88 0 1
Analogue Entry
44451 0x1162 103 Third ASDU First 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44452 0x1163 103 Third ASDU First 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44453 0x1164 103 Third ASDU Second 0 251 1 --- F88 0 1
Analogue Entry
44454 0x1165 103 Third ASDU Second 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44455 0x1166 103 Third ASDU Second 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44456 0x1167 103 Third ASDU Third 0 251 1 --- F88 0 1
Analogue Entry
44457 0x1168 103 Third ASDU Third 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44458 0x1169 103 Third ASDU Third 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44459 0x116A 103 Third ASDU Fourth 0 251 1 --- F88 0 1
Analogue Entry
44460 0x116B 103 Third ASDU Fourth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44461 0x116C 103 Third ASDU Fourth 0 0xFFFF 1 --- F1 0 1
Analogue Offset

10-60 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44462 0x116D 103 Third ASDU Fifth 0 251 1 --- F88 0 1
Analogue Entry
44463 0x116E 103 Third ASDU Fifth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44464 0x116F 103 Third ASDU Fifth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44465 0x1170 103 Third ASDU Sixth 0 251 1 --- F88 0 1
Analogue Entry
44466 0x1171 103 Third ASDU Sixth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44467 0x1172 103 Third ASDU Sixth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44468 0x1173 103 Third ASDU Seventh 0 251 1 --- F88 0 1
Analogue Entry
44469 0x1174 103 Third ASDU Seventh 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44470 0x1175 103 Third ASDU Seventh 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44471 0x1176 103 Third ASDU Eigth 0 251 1 --- F88 0 1
Analogue Entry
44472 0x1177 103 Third ASDU Eigth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44473 0x1178 103 Third ASDU Eigth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44474 0x1179 103 Third ASDU Ninth 0 251 1 --- F88 0 1
Analogue Entry
44475 0x117A 103 Third ASDU Ninth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44476 0x117B 103 Third ASDU Ninth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44477 0x117C 103 Fourth ASDU 3 9 1 --- FC221 3 1
Identification Type
44478 0x117D 103 Fourth ASDU Function 0 255 1 --- F1 0 1
Type
44479 0x117E 103 Fourth ASDU 0 255 1 --- F1 0 1
Information Number
44480 0x117F 103 Fourth ASDU Scan 0 1000 1 s F1 0 1
Timeout
44481 0x1180 103 Fourth ASDU First 0 251 1 --- F88 0 1
Analogue Entry
44482 0x1181 103 Fourth ASDU First 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44483 0x1182 103 Fourth ASDU First 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44484 0x1183 103 Fourth ASDU Second 0 251 1 --- F88 0 1
Analogue Entry
44485 0x1184 103 Fourth ASDU Second 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44486 0x1185 103 Fourth ASDU Second 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44487 0x1186 103 Fourth ASDU Third 0 251 1 --- F88 0 1
Analogue Entry
44488 0x1187 103 Fourth ASDU Third 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44489 0x1188 103 Fourth ASDU Third 0 0xFFFF 1 --- F1 0 1
Analogue Offset

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-61


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44490 0x1189 103 Fourth ASDU Fourth 0 251 1 --- F88 0 1
Analogue Entry
44491 0x118A 103 Fourth ASDU Fourth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44492 0x118B 103 Fourth ASDU Fourth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44493 0x118C 103 Fourth ASDU Fifth 0 251 1 --- F88 0 1
Analogue Entry
44494 0x118D 103 Fourth ASDU Fifth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44495 0x118E 103 Fourth ASDU Fifth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44496 0x118F 103 Fourth ASDU Sixth 0 251 1 --- F88 0 1
Analogue Entry
44497 0x1190 103 Fourth ASDU Sixth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44498 0x1191 103 Fourth ASDU Sixth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44499 0x1192 103 Fourth ASDU Seventh 0 251 1 --- F88 0 1
Analogue Entry
44500 0x1193 103 Fourth ASDU Seventh 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44501 0x1194 103 Fourth ASDU Seventh 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44502 0x1195 103 Fourth ASDU Eigth 0 251 1 --- F88 0 1
Analogue Entry
44503 0x1196 103 Fourth ASDU Eigth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44504 0x1197 103 Fourth ASDU Eigth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44505 0x1198 103 Fourth ASDU Ninth 0 251 1 --- F88 0 1
Analogue Entry
44506 0x1199 103 Fourth ASDU Ninth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44507 0x119A 103 Fourth ASDU Ninth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
PASSWORD SECURITY
44536 0x11B7 Security Passcode Master 1 0 1 1 --- F22 0 1
44537 0x11B8 Security Passcode Master 2 0 1 1 --- F22 0 1
44538 0x11B9 Security Passcode Master 3 0 1 1 --- F22 0 1
44539 0x11BA Security Passcode Master 4 0 1 1 --- F22 0 1
44540 0x11BB Security Passcode Master 5 0 1 1 --- F22 0 1
44541 0x11BC Security Passcode Local 0 1 1 --- F22 0 1
Setpoint 1
44542 0x11BD Security Passcode Local 0 1 1 --- F22 0 1
Setpoint 2
44543 0x11BE Security Passcode Local 0 1 1 --- F22 0 1
Setpoint 3
44544 0x11BF Security Passcode Local 0 1 1 --- F22 0 1
Setpoint 4
44545 0x11C0 Security Passcode Local 0 1 1 --- F22 0 1
Setpoint 5
44546 0x11C1 Security Passcode Local 0 1 1 --- F22 0 1
Control 1

10-62 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44547 0x11C2 Security Passcode Local 0 1 1 --- F22 0 1
Control 2
44548 0x11C3 Security Passcode Local 0 1 1 --- F22 0 1
Control 3
44549 0x11C4 Security Passcode Local 0 1 1 --- F22 0 1
Control 4
44550 0x11C5 Security Passcode Local 0 1 1 --- F22 0 1
Control 5
44551 0x11C6 Security Passcode Remote 0 1 1 --- F22 0 1
Setpoint 1
44552 0x11C7 Security Passcode Remote 0 1 1 --- F22 0 1
Setpoint 2
44553 0x11C8 Security Passcode Remote 0 1 1 --- F22 0 1
Setpoint 3
44554 0x11C9 Security Passcode Remote 0 1 1 --- F22 0 1
Setpoint 4
44555 0x11CA Security Passcode Remote 0 1 1 --- F22 0 1
Setpoint 5
44556 0x11CB Security Passcode Remote 0 1 1 --- F22 0 1
Control 1
44557 0x11CC Security Passcode Remote 0 1 1 --- F22 0 1
Control 2
44558 0x11CD Security Passcode Remote 0 1 1 --- F22 0 1
Control 3
44559 0x11CE Security Passcode Remote 0 1 1 --- F22 0 1
Control 4
44560 0x11CF Security Passcode Remote 0 1 1 --- F22 0 1
Control 5
44561 0x11D0 Security Passcode Entry 0 1 1 --- F22 0 1
Master 1
44562 0x11D1 Security Passcode Entry 0 1 1 --- F22 0 1
Master 2
44563 0x11D2 Security Passcode Entry 0 1 1 --- F22 0 1
Master 3
44564 0x11D3 Security Passcode Entry 0 1 1 --- F22 0 1
Master 4
44565 0x11D4 Security Passcode Entry 0 1 1 --- F22 0 1
Master 5
44566 0x11D5 Security Passcode Entry 0 1 1 --- F22 0 1
Setpoints 1
44567 0x11D6 Security Passcode Entry 0 1 1 --- F22 0 1
Setpoints 2
44568 0x11D7 Security Passcode Entry 0 1 1 --- F22 0 1
Setpoints 3
44569 0x11D8 Security Passcode Entry 0 1 1 --- F22 0 1
Setpoints 4
44570 0x11D9 Security Passcode Entry 0 1 1 --- F22 0 1
Setpoints 5
44571 0x11DA Security Passcode Entry 0 1 1 --- F22 0 1
Control 1
44572 0x11DB Security Passcode Entry 0 1 1 --- F22 0 1
Control 2
44573 0x11DC Security Passcode Entry 0 1 1 --- F22 0 1
Control 3
44574 0x11DD Security Passcode Entry 0 1 1 --- F22 0 1
Control 4

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-63


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44575 0x11DE Security Passcode Entry 0 1 1 --- F22 0 1
Control 5
44576 0x11DF Overwrite Local Setpoint 0 1 1 --- FC103A 0 1
Password
VIRTUAL INPUT FUNCTION
44580 0x11E3 Virtual Input 1 Function 0 1 1 --- FC126 0 1
44581 0x11E4 Virtual Input 2 Function 0 1 1 --- FC126 0 1
44582 0x11E5 Virtual Input 3 Function 0 1 1 --- FC126 0 1
44583 0x11E6 Virtual Input 4 Function 0 1 1 --- FC126 0 1
44584 0x11E7 Virtual Input 5 Function 0 1 1 --- FC126 0 1
44585 0x11E8 Virtual Input 6 Function 0 1 1 --- FC126 0 1
44586 0x11E9 Virtual Input 7 Function 0 1 1 --- FC126 0 1
44587 0x11EA Virtual Input 8 Function 0 1 1 --- FC126 0 1
44588 0x11EB Virtual Input 9 Function 0 1 1 --- FC126 0 1
44589 0x11EC Virtual Input 10 Function 0 1 1 --- FC126 0 1
44590 0x11ED Virtual Input 11 Function 0 1 1 --- FC126 0 1
44591 0x11EE Virtual Input 12 Function 0 1 1 --- FC126 0 1
44592 0x11EF Virtual Input 13 Function 0 1 1 --- FC126 0 1
44593 0x11F0 Virtual Input 14 Function 0 1 1 --- FC126 0 1
44594 0x11F1 Virtual Input 15 Function 0 1 1 --- FC126 0 1
44595 0x11F2 Virtual Input 16 Function 0 1 1 --- FC126 0 1
44596 0x11F3 Virtual Input 17 Function 0 1 1 --- FC126 0 1
44597 0x11F4 Virtual Input 18 Function 0 1 1 --- FC126 0 1
44598 0x11F5 Virtual Input 19 Function 0 1 1 --- FC126 0 1
44599 0x11F6 Virtual Input 20 Function 0 1 1 --- FC126 0 1
44600 0x11F7 Virtual Input 21 Function 0 1 1 --- FC126 0 1
44601 0x11F8 Virtual Input 22 Function 0 1 1 --- FC126 0 1
44602 0x11F9 Virtual Input 23 Function 0 1 1 --- FC126 0 1
44603 0x11FA Virtual Input 24 Function 0 1 1 --- FC126 0 1
44604 0x11FB Virtual Input 25 Function 0 1 1 --- FC126 0 1
44605 0x11FC Virtual Input 26 Function 0 1 1 --- FC126 0 1
44606 0x11FD Virtual Input 27 Function 0 1 1 --- FC126 0 1
44607 0x11FE Virtual Input 28 Function 0 1 1 --- FC126 0 1
44608 0x11FF Virtual Input 29 Function 0 1 1 --- FC126 0 1
44609 0x1200 Virtual Input 30 Function 0 1 1 --- FC126 0 1
44610 0x1201 Virtual Input 31 Function 0 1 1 --- FC126 0 1
44611 0x1202 Virtual Input 32 Function 0 1 1 --- FC126 0 1
VIRTUAL INPUT TYPE
44612 0x1203 Virtual Input 1 Type 0 1 1 --- FC199 0 1
44613 0x1204 Virtual Input 2 Type 0 1 1 --- FC199 0 1
44614 0x1205 Virtual Input 3 Type 0 1 1 --- FC199 0 1
44615 0x1206 Virtual Input 4 Type 0 1 1 --- FC199 0 1
44616 0x1207 Virtual Input 5 Type 0 1 1 --- FC199 0 1
44617 0x1208 Virtual Input 6 Type 0 1 1 --- FC199 0 1
44618 0x1209 Virtual Input 7 Type 0 1 1 --- FC199 0 1
44619 0x120A Virtual Input 8 Type 0 1 1 --- FC199 0 1
44620 0x120B Virtual Input 9 Type 0 1 1 --- FC199 0 1

10-64 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44621 0x120C Virtual Input 10 Type 0 1 1 --- FC199 0 1
44622 0x120D Virtual Input 11 Type 0 1 1 --- FC199 0 1
44623 0x120E Virtual Input 12 Type 0 1 1 --- FC199 0 1
44624 0x120F Virtual Input 13 Type 0 1 1 --- FC199 0 1
44625 0x1210 Virtual Input 14 Type 0 1 1 --- FC199 0 1
44626 0x1211 Virtual Input 15 Type 0 1 1 --- FC199 0 1
44627 0x1212 Virtual Input 16 Type 0 1 1 --- FC199 0 1
44628 0x1213 Virtual Input 17 Type 0 1 1 --- FC199 0 1
44629 0x1214 Virtual Input 18 Type 0 1 1 --- FC199 0 1
44630 0x1215 Virtual Input 19 Type 0 1 1 --- FC199 0 1
44631 0x1216 Virtual Input 20 Type 0 1 1 --- FC199 0 1
44632 0x1217 Virtual Input 21 Type 0 1 1 --- FC199 0 1
44633 0x1218 Virtual Input 22 Type 0 1 1 --- FC199 0 1
44634 0x1219 Virtual Input 23 Type 0 1 1 --- FC199 0 1
44635 0x121A Virtual Input 24 Type 0 1 1 --- FC199 0 1
44636 0x121B Virtual Input 25 Type 0 1 1 --- FC199 0 1
44637 0x121C Virtual Input 26 Type 0 1 1 --- FC199 0 1
44638 0x121D Virtual Input 27 Type 0 1 1 --- FC199 0 1
44639 0x121E Virtual Input 28 Type 0 1 1 --- FC199 0 1
44640 0x121F Virtual Input 29 Type 0 1 1 --- FC199 0 1
44641 0x1220 Virtual Input 30 Type 0 1 1 --- FC199 0 1
44642 0x1221 Virtual Input 31 Type 0 1 1 --- FC199 0 1
44643 0x1222 Virtual Input 32 Type 0 1 1 --- FC199 0 1
IEC61850 GOOSE
44645 0x1224 Enable GOOSE Transmission 0 1 1 --- FC126 0 1
44646 0x1225 Enable GOOSE 0 1 1 --- FC126 0 1
44647 0x1226 GOOSE Name 0 20 1 --- F22 20
SR3_GOOSE
1
44667 0x123A VLAN Identifier 0 4095 1 --- F1 0 1
44668 0x123B VLAN Priority 1 7 1 --- F1 4 1
44669 0x123C Application Identifier 0 0x3FFF 1 --- F1 0 1
44670 0x123D Update Time 1000 60000 1 ms F1 10000 1
44671 0x123E DataSet Name 0 20 1 --- F22 GOOSE1 20
44691 0x1252 Control Block Name 0 20 1 --- F22 gcb01 20
44711 0x1266 Conf Revision Number 1 0xFFFF 1 --- F1 1 1
44712 0x1267 Destination MAC Address 0 0xFFFF 1 --- FC214 0 3
44715 0x126A MMS TCP Port Number 1 65535 1 --- F1 102 1
44716 0x126B TCP Connection Timeout 10 1800 1 s F1 120 1
IEC61850 GOOSE TRANSMISSION DATASET ITEMS
44718 0x126D DataSet Item 1 0 0xFFFF 1 --- FC134B 0 1
44719 0x126E Item 1 Quality 0 1 1 --- FC126 0 1
44720 0x126F DataSet Item 2 0 0xFFFF 1 --- FC134B 0 1
44721 0x1270 Item 2 Quality 0 1 1 --- FC126 0 1
44722 0x1271 DataSet Item 3 0 0xFFFF 1 --- FC134B 0 1
44723 0x1272 Item 3 Quality 0 1 1 --- FC126 0 1
44724 0x1273 DataSet Item 4 0 0xFFFF 1 --- FC134B 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-65


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44725 0x1274 Item 4 Quality 0 1 1 --- FC126 0 1
44726 0x1275 DataSet Item 5 0 0xFFFF 1 --- FC134B 0 1
44727 0x1276 Item 5 Quality 0 1 1 --- FC126 0 1
44728 0x1277 DataSet Item 6 0 0xFFFF 1 --- FC134B 0 1
44729 0x1278 Item 6 Quality 0 1 1 --- FC126 0 1
44730 0x1279 DataSet Item 7 0 0xFFFF 1 --- FC134B 0 1
44731 0x127A Item 7 Quality 0 1 1 --- FC126 0 1
44732 0x127B DataSet Item 8 0 0xFFFF 1 --- FC134B 0 1
44733 0x127C Item 8 Quality 0 1 1 --- FC126 0 1
44734 0x127D DataSet Item 9 0 0xFFFF 1 --- FC134B 0 1
44735 0x127E Item 9 Quality 0 1 1 --- FC126 0 1
44736 0x127F DataSet Item 10 0 0xFFFF 1 --- FC134B 0 1
44737 0x1280 Item 10 Quality 0 1 1 --- FC126 0 1
44738 0x1281 DataSet Item 11 0 0xFFFF 1 --- FC134B 0 1
44739 0x1282 Item 11 Quality 0 1 1 --- FC126 0 1
44740 0x1283 DataSet Item 12 0 0xFFFF 1 --- FC134B 0 1
44741 0x1284 Item 12 Quality 0 1 1 --- FC126 0 1
44742 0x1285 DataSet Item 13 0 0xFFFF 1 --- FC134B 0 1
44743 0x1286 Item 13 Quality 0 1 1 --- FC126 0 1
44744 0x1287 DataSet Item 14 0 0xFFFF 1 --- FC134B 0 1
44745 0x1288 Item 14 Quality 0 1 1 --- FC126 0 1
44746 0x1289 DataSet Item 15 0 0xFFFF 1 --- FC134B 0 1
44747 0x128A Item 15 Quality 0 1 1 --- FC126 0 1
44748 0x128B DataSet Item 16 0 0xFFFF 1 --- FC134B 0 1
44749 0x128C Item 16 Quality 0 1 1 --- FC126 0 1
44750 0x128D DataSet Item 17 0 0xFFFF 1 --- FC134B 0 1
44751 0x128E Item 17 Quality 0 1 1 --- FC126 0 1
44752 0x128F DataSet Item 18 0 0xFFFF 1 --- FC134B 0 1
44753 0x1290 Item 18 Quality 0 1 1 --- FC126 0 1
44754 0x1291 DataSet Item 19 0 0xFFFF 1 --- FC134B 0 1
44755 0x1292 Item 19 Quality 0 1 1 --- FC126 0 1
44756 0x1293 DataSet Item 20 0 0xFFFF 1 --- FC134B 0 1
44757 0x1294 Item 20 Quality 0 1 1 --- FC126 0 1
44758 0x1295 DataSet Item 21 0 0xFFFF 1 --- FC134B 0 1
44759 0x1296 Item 21 Quality 0 1 1 --- FC126 0 1
44760 0x1297 DataSet Item 22 0 0xFFFF 1 --- FC134B 0 1
44761 0x1298 Item 22 Quality 0 1 1 --- FC126 0 1
44762 0x1299 DataSet Item 23 0 0xFFFF 1 --- FC134B 0 1
44763 0x129A Item 23 Quality 0 1 1 --- FC126 0 1
44764 0x129B DataSet Item 24 0 0xFFFF 1 --- FC134B 0 1
44765 0x129C Item 24 Quality 0 1 1 --- FC126 0 1
44766 0x129D DataSet Item 25 0 0xFFFF 1 --- FC134B 0 1
44767 0x129E Item 25 Quality 0 1 1 --- FC126 0 1
44768 0x129F DataSet Item 26 0 0xFFFF 1 --- FC134B 0 1
44769 0x12A0 Item 26 Quality 0 1 1 --- FC126 0 1
44770 0x12A1 DataSet Item 27 0 0xFFFF 1 --- FC134B 0 1

10-66 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44771 0x12A2 Item 27 Quality 0 1 1 --- FC126 0 1
44772 0x12A3 DataSet Item 28 0 0xFFFF 1 --- FC134B 0 1
44773 0x12A4 Item 28 Quality 0 1 1 --- FC126 0 1
44774 0x12A5 DataSet Item 29 0 0xFFFF 1 --- FC134B 0 1
44775 0x12A6 Item 29 Quality 0 1 1 --- FC126 0 1
44776 0x12A7 DataSet Item 30 0 0xFFFF 1 --- FC134B 0 1
44777 0x12A8 Item 30 Quality 0 1 1 --- FC126 0 1
44778 0x12A9 DataSet Item 31 0 0xFFFF 1 --- FC134B 0 1
44779 0x12AA Item 31 Quality 0 1 1 --- FC126 0 1
44780 0x12AB DataSet Item 32 0 0xFFFF 1 --- FC134B 0 1
44781 0x12AC Item 32 Quality 0 1 1 --- FC126 0 1
IEC61850 GOOSE RX1 CONFIGURATION
44786 0x12B1 Rx GOOSE1 Function 0 1 1 --- FC126 0 1
44787 0x12B2 Rx GOOSE1 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE1
44807 0x12C6 Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
44827 0x12DA RX1 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb01
44847 0x12EE RX1 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
44848 0x12EF EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX2 CONFIGURATION
44852 0x12F3 Rx GOOSE2 Function 0 1 1 --- FC126 0 1
44853 0x12F4 Rx GOOSE2 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE2
44873 0x1308 Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
44893 0x131C RX2 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb02
44913 0x1330 RX2 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
44914 0x1331 EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX3 CONFIGURATION
44918 0x1335 Rx GOOSE3 Function 0 1 1 --- FC126 0 1
44919 0x1336 Rx GOOSE3 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE3
44939 0x134A Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
44959 0x135E RX3 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb03
44979 0x1372 RX3 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
44980 0x1373 EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX4 CONFIGURATION

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-67


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44984 0x1377 Rx GOOSE4 Function 0 1 1 --- FC126 0 1
44985 0x1378 Rx GOOSE4 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE4
45005 0x138C Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
45025 0x13A0 RX4 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb04
45045 0x13B4 RX4 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
45046 0x13B5 EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX5 CONFIGURATION
45050 0x13B9 Rx GOOSE5 Function 0 1 1 --- FC126 0 1
45051 0x13BA Rx GOOSE5 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE5
45071 0x13CE Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
45091 0x13E2 RX5 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb05
45111 0x13F6 RX5 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
45112 0x13F7 EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX6 CONFIGURATION
45116 0x13FB Rx GOOSE6 Function 0 1 1 --- FC126 0 1
45117 0x13FC Rx GOOSE6 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE6
45137 0x1410 Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
45157 0x1424 RX6 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb06
45177 0x1438 RX6 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
45178 0x1439 EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX7 CONFIGURATION
45182 0x143D Rx GOOSE7 Function 0 1 1 --- FC126 0 1
45183 0x143E Rx GOOSE7 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE7
45203 0x1452 Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
45223 0x1466 RX7 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb07
45243 0x147A RX7 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
45244 0x147B EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX8 CONFIGURATION

10-68 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
45248 0x147F Rx GOOSE8 Function 0 1 1 --- FC126 0 1
45249 0x1480 Rx GOOSE8 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE8
45269 0x1494 Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
45289 0x14A8 RX8 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb08
45309 0x14BC RX8 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
45310 0x14BD EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE DATASET STRUCTURE BUFFER
45314 0x14C1 DataSet Struct Buffer 0 0xFFFF 1 --- FC216 0 250
IEC61850 GOOSE REMOTE INPUTS
45567 0x15BE Remote Input 1 Name 0 7 1 --- F22 RI 1 7
45583 0x15CE Remote Input 1 GOOSE 0 0x80 1 --- FC219 0 1
Source
45584 0x15CF Remote Input 1 Item Source 0 0xFFFF 1 --- FC217 0 1
45585 0x15D0 Remote Input 1 Item Mask 0 0xFFFF 1 --- FC218 0 1
45586 0x15D1 Remote Input 1 Default 0 3 1 --- FC220 1 1
State
45588 0x15D3 Remote Input 2 Name 0 7 1 --- F22 RI 2 7
45604 0x15E3 Remote Input 2 GOOSE 0 0x80 1 --- FC219 0 1
Source
45605 0x15E4 Remote Input 2 Item Source 0 0xFFFF 1 --- FC217 0 1
45606 0x15E5 Remote Input 2 Item Mask 0 0xFFFF 1 --- FC218 0 1
45607 0x15E6 Remote Input 2 Default 0 3 1 --- FC220 1 1
State
45609 0x15E8 Remote Input 3 Name 0 7 1 --- F22 RI 3 7
45625 0x15F8 Remote Input 3 GOOSE 0 0x80 1 --- FC219 0 1
Source
45626 0x15F9 Remote Input 3 Item Source 0 0xFFFF 1 --- FC217 0 1
45627 0x15FA Remote Input 3 Item Mask 0 0xFFFF 1 --- FC218 0 1
45628 0x15FB Remote Input 3 Default 0 3 1 --- FC220 1 1
State
45630 0x15FD Remote Input 4 Name 0 7 1 --- F22 RI 4 7
45646 0x160D Remote Input 4 GOOSE 0 0x80 1 --- FC219 0 1
Source
45647 0x160E Remote Input 4 Item Source 0 0xFFFF 1 --- FC217 0 1
45648 0x160F Remote Input 4 Item Mask 0 0xFFFF 1 --- FC218 0 1
45649 0x1610 Remote Input 4 Default 0 3 1 --- FC220 1 1
State
45651 0x1612 Remote Input 5 Name 0 7 1 --- F22 RI 5 7
45667 0x1622 Remote Input 5 GOOSE 0 0x80 1 --- FC219 0 1
Source
45668 0x1623 Remote Input 5 Item Source 0 0xFFFF 1 --- FC217 0 1
45669 0x1624 Remote Input 5 Item Mask 0 0xFFFF 1 --- FC218 0 1
45670 0x1625 Remote Input 5 Default 0 3 1 --- FC220 1 1
State
45672 0x1627 Remote Input 6 Name 0 7 1 --- F22 RI 6 7

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-69


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
45688 0x1637 Remote Input 6 GOOSE 0 0x80 1 --- FC219 0 1
Source
45689 0x1638 Remote Input 6 Item Source 0 0xFFFF 1 --- FC217 0 1
45690 0x1639 Remote Input 6 Item Mask 0 0xFFFF 1 --- FC218 0 1
45691 0x163A Remote Input 6 Default 0 3 1 --- FC220 1 1
State
45693 0x163C Remote Input 7 Name 0 7 1 --- F22 RI 7 7
45709 0x164C Remote Input 7 GOOSE 0 0x80 1 --- FC219 0 1
Source
45710 0x164D Remote Input 7 Item Source 0 0xFFFF 1 --- FC217 0 1
45711 0x164E Remote Input 7 Item Mask 0 0xFFFF 1 --- FC218 0 1
45712 0x164F Remote Input 7 Default 0 3 1 --- FC220 1 1
State
45714 0x1651 Remote Input 8 Name 0 7 1 --- F22 RI 8 7
45730 0x1661 Remote Input 8 GOOSE 0 0x80 1 --- FC219 0 1
Source
45731 0x1662 Remote Input 8 Item Source 0 0xFFFF 1 --- FC217 0 1
45732 0x1663 Remote Input 8 Item Mask 0 0xFFFF 1 --- FC218 0 1
45733 0x1664 Remote Input 8 Default 0 3 1 --- FC220 1 1
State
45735 0x1666 Remote Input 9 Name 0 7 1 --- F22 RI 9 7
45751 0x1676 Remote Input 9 GOOSE 0 0x80 1 --- F1 0 1
Source
45752 0x1677 Remote Input 9 Item Source 0 0xFFFF 1 --- FC217 0 1
45753 0x1678 Remote Input 9 Item Mask 0 0xFFFF 1 --- FC218 0 1
45754 0x1679 Remote Input 9 Default 0 3 1 --- FC220 1 1
State
45756 0x167B Remote Input 10 Name 0 7 1 --- F22 RI 10 7
45772 0x168B Remote Input 10 GOOSE 0 0x80 1 --- F1 0 1
Source
45773 0x168C Remote Input 10 Item 0 0xFFFF 1 --- FC217 0 1
Source
45774 0x168D Remote Input 10 Item Mask 0 0xFFFF 1 --- FC218 0 1
45775 0x168E Remote Input 10 Default 0 3 1 --- FC220 1 1
State
45777 0x1690 Remote Input 11 Name 0 7 1 --- F22 RI 11 7
45793 0x16A0 Remote Input 11 GOOSE 0 0x80 1 --- F1 0 1
Source
45794 0x16A1 Remote Input 11 Item 0 0xFFFF 1 --- FC217 0 1
Source
45795 0x16A2 Remote Input 11 Item Mask 0 0xFFFF 1 --- FC218 0 1
45796 0x16A3 Remote Input 11 Default 0 3 1 --- FC220 1 1
State
45798 0x16A5 Remote Input 12 Name 0 7 1 --- F22 RI 12 7
45814 0x16B5 Remote Input 12 GOOSE 0 0x80 1 --- F1 0 1
Source
45815 0x16B6 Remote Input 12 Item 0 0xFFFF 1 --- FC217 0 1
Source
45816 0x16B7 Remote Input 12 Item Mask 0 0xFFFF 1 --- FC218 0 1
45817 0x16B8 Remote Input 12 Default 0 3 1 --- FC220 1 1
State
45819 0x16BA Remote Input 13 Name 0 7 1 --- F22 RI 13 7

10-70 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
45835 0x16CA Remote Input 13 GOOSE 0 0x80 1 --- F1 0 1
Source
45836 0x16CB Remote Input 13 Item 0 0xFFFF 1 --- FC217 0 1
Source
45837 0x16CC Remote Input 13 Item Mask 0 0xFFFF 1 --- FC218 0 1
45838 0x16CD Remote Input 13 Default 0 3 1 --- FC220 1 1
State
45840 0x16CF Remote Input 14 Name 0 7 1 --- F22 RI 14 7
45856 0x16DF Remote Input 14 GOOSE 0 0x80 1 --- F1 0 1
Source
45857 0x16E0 Remote Input 14 Item 0 0xFFFF 1 --- FC217 0 1
Source
45858 0x16E1 Remote Input 14 Item Mask 0 0xFFFF 1 --- FC218 0 1
45859 0x16E2 Remote Input 14 Default 0 3 1 --- FC220 1 1
State
45861 0x16E4 Remote Input 15 Name 0 7 1 --- F22 RI 15 7
45877 0x16F4 Remote Input 15 GOOSE 0 0x80 1 --- F1 0 1
Source
45878 0x16F5 Remote Input 15 Item 0 0xFFFF 1 --- FC217 0 1
Source
45879 0x16F6 Remote Input 15 Item Mask 0 0xFFFF 1 --- FC218 0 1
45880 0x16F7 Remote Input 15 Default 0 3 1 --- FC220 1 1
State
45882 0x16F9 Remote Input 16 Name 0 7 1 --- F22 RI 16 7
45898 0x1709 Remote Input 16 GOOSE 0 0x80 1 --- F1 0 1
Source
45899 0x170A Remote Input 16 Item 0 0xFFFF 1 --- FC217 0 1
Source
45900 0x170B Remote Input 16 Item Mask 0 0xFFFF 1 --- FC218 0 1
45901 0x170C Remote Input 16 Default 0 3 1 --- FC220 1 1
State
45903 0x170E Remote Input 17 Name 0 7 1 --- F22 RI 17 7
45919 0x171E Remote Input 17 GOOSE 0 0x80 1 --- F1 0 1
Source
45920 0x171F Remote Input 17 Item 0 0xFFFF 1 --- FC217 0 1
Source
45921 0x1720 Remote Input 17 Item Mask 0 0xFFFF 1 --- FC218 0 1
45922 0x1721 Remote Input 17 Default 0 3 1 --- FC220 1 1
State
45924 0x1723 Remote Input 18 Name 0 7 1 --- F22 RI 18 7
45940 0x1733 Remote Input 18 GOOSE 0 0x80 1 --- F1 0 1
Source
45941 0x1734 Remote Input 18 Item 0 0xFFFF 1 --- FC217 0 1
Source
45942 0x1735 Remote Input 18 Item Mask 0 0xFFFF 1 --- FC218 0 1
45943 0x1736 Remote Input 18 Default 0 3 1 --- FC220 1 1
State
45945 0x1738 Remote Input 19 Name 0 7 1 --- F22 RI 19 7
45961 0x1748 Remote Input 19 GOOSE 0 0x80 1 --- F1 0 1
Source
45962 0x1749 Remote Input 19 Item 0 0xFFFF 1 --- FC217 0 1
Source
45963 0x174A Remote Input 19 Item Mask 0 0xFFFF 1 --- FC218 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-71


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
45964 0x174B Remote Input 19 Default 0 3 1 --- FC220 1 1
State
45966 0x174D Remote Input 20 Name 0 7 1 --- F22 RI 20 7
45982 0x175D Remote Input 20 GOOSE 0 0x80 1 --- F1 0 1
Source
45983 0x175E Remote Input 20 Item 0 0xFFFF 1 --- FC217 0 1
Source
45984 0x175F Remote Input 20 Item Mask 0 0xFFFF 1 --- FC218 0 1
45985 0x1760 Remote Input 20 Default 0 3 1 --- FC220 1 1
State
45987 0x1762 Remote Input 21 Name 0 7 1 --- F22 RI 21 7
46003 0x1772 Remote Input 21 GOOSE 0 0x80 1 --- F1 0 1
Source
46004 0x1773 Remote Input 21 Item 0 0xFFFF 1 --- FC217 0 1
Source
46005 0x1774 Remote Input 21 Item Mask 0 0xFFFF 1 --- FC218 0 1
46006 0x1775 Remote Input 21 Default 0 3 1 --- FC220 1 1
State
46008 0x1777 Remote Input 22 Name 0 7 1 --- F22 RI 22 7
46024 0x1787 Remote Input 22 GOOSE 0 0x80 1 --- F1 0 1
Source
46025 0x1788 Remote Input 22 Item 0 0xFFFF 1 --- FC217 0 1
Source
46026 0x1789 Remote Input 22 Item Mask 0 0xFFFF 1 --- FC218 0 1
46027 0x178A Remote Input 22 Default 0 3 1 --- FC220 1 1
State
46029 0x178C Remote Input 23 Name 0 7 1 --- F22 RI 23 7
46045 0x179C Remote Input 23 GOOSE 0 0x80 1 --- F1 0 1
Source
46046 0x179D Remote Input 23 Item 0 0xFFFF 1 --- FC217 0 1
Source
46047 0x179E Remote Input 23 Item Mask 0 0xFFFF 1 --- FC218 0 1
46048 0x179F Remote Input 23 Default 0 3 1 --- FC220 1 1
State
46050 0x17A1 Remote Input 24 Name 0 7 1 --- F22 RI 24 7
46066 0x17B1 Remote Input 24 GOOSE 0 0x80 1 --- F1 0 1
Source
46067 0x17B2 Remote Input 24 Item 0 0xFFFF 1 --- FC217 0 1
Source
46068 0x17B3 Remote Input 24 Item Mask 0 0xFFFF 1 --- FC218 0 1
46069 0x17B4 Remote Input 24 Default 0 3 1 --- FC220 1 1
State
46071 0x17B6 Remote Input 25 Name 0 7 1 --- F22 RI 25 7
46087 0x17C6 Remote Input 25 GOOSE 0 0x80 1 --- F1 0 1
Source
46088 0x17C7 Remote Input 25 Item 0 0xFFFF 1 --- FC217 0 1
Source
46089 0x17C8 Remote Input 25 Item Mask 0 0xFFFF 1 --- FC218 0 1
46090 0x17C9 Remote Input 25 Default 0 3 1 --- FC220 1 1
State
46092 0x17CB Remote Input 26 Name 0 7 1 --- F22 RI 26 7
46108 0x17DB Remote Input 26 GOOSE 0 0x80 1 --- F1 0 1
Source

10-72 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
46109 0x17DC Remote Input 26 Item 0 0xFFFF 1 --- FC217 0 1
Source
46110 0x17DD Remote Input 26 Item Mask 0 0xFFFF 1 --- FC218 0 1
46111 0x17DE Remote Input 26 Default 0 3 1 --- FC220 1 1
State
46113 0x17E0 Remote Input 27 Name 0 7 1 --- F22 RI 27 7
46129 0x17F0 Remote Input 27 GOOSE 0 0x80 1 --- F1 0 1
Source
46130 0x17F1 Remote Input 27 Item 0 0xFFFF 1 --- FC217 0 1
Source
46131 0x17F2 Remote Input 27 Item Mask 0 0xFFFF 1 --- FC218 0 1
46132 0x17F3 Remote Input 27 Default 0 3 1 --- FC220 1 1
State
46134 0x17F5 Remote Input 28 Name 0 7 1 --- F22 RI 28 7
46150 0x1805 Remote Input 28 GOOSE 0 0x80 1 --- F1 0 1
Source
46151 0x1806 Remote Input 28 Item 0 0xFFFF 1 --- FC217 0 1
Source
46152 0x1807 Remote Input 28 Item Mask 0 0xFFFF 1 --- FC218 0 1
46153 0x1808 Remote Input 28 Default 0 3 1 --- FC220 1 1
State
46155 0x180A Remote Input 29 Name 0 7 1 --- F22 RI 29 7
46171 0x181A Remote Input 29 GOOSE 0 0x80 1 --- F1 0 1
Source
46172 0x181B Remote Input 29 Item 0 0xFFFF 1 --- FC217 0 1
Source
46173 0x181C Remote Input 29 Item Mask 0 0xFFFF 1 --- FC218 0 1
46174 0x181D Remote Input 29 Default 0 3 1 --- FC220 1 1
State
46176 0x181F Remote Input 30 Name 0 7 1 --- F22 RI 30 7
46192 0x182F Remote Input 30 GOOSE 0 0x80 1 --- F1 0 1
Source
46193 0x1830 Remote Input 30 Item 0 0xFFFF 1 --- FC217 0 1
Source
46194 0x1831 Remote Input 30 Item Mask 0 0xFFFF 1 --- FC218 0 1
46195 0x1832 Remote Input 30 Default 0 3 1 --- FC220 1 1
State
46197 0x1834 Remote Input 31 Name 0 7 1 --- F22 RI 31 7
46213 0x1844 Remote Input 31 GOOSE 0 0x80 1 --- F1 0 1
Source
46214 0x1845 Remote Input 31 Item 0 0xFFFF 1 --- FC217 0 1
Source
46215 0x1846 Remote Input 31 Item Mask 0 0xFFFF 1 --- FC218 0 1
46216 0x1847 Remote Input 31 Default 0 3 1 --- FC220 1 1
State
46218 0x1849 Remote Input 32 Name 0 7 1 --- F22 RI 32 7
46234 0x1859 Remote Input 32 GOOSE 0 0x80 1 --- F1 0 1
Source
46235 0x185A Remote Input 32 Item 0 0xFFFF 1 --- FC217 0 1
Source
46236 0x185B Remote Input 32 Item Mask 0 0xFFFF 1 --- FC218 0 1
46237 0x185C Remote Input 32 Default 0 3 1 --- FC220 1 1
State

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-73


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
BKR HEALTH
46428 0x191B Breaker Health Function 0 2 1 --- FC206 0 1
46429 0x191C Breaker Health Mode 0 1 1 --- FC433 0 1
46430 0x191D Breaker Health Limit 0 100000 1 --- F9 0 2
46432 0x191F Breaker Health Trip Time 0 1000 1 s F3 5 1
Pickup
46433 0x1920 Breaker Health Close Time 0 1000 1 s F3 5 1
Pickup
46434 0x1921 Breaker Health Charge Time 0 6000 1 s F3 1500 1
Pickup
46435 0x1922 Breaker Health Spring 0 0xEF02 1 --- F89A 0 1
Charge Input
46436 0x1923 Breaker Health Block1 0 0xEF02 1 --- F89 0 1
46437 0x1924 Breaker Health Block2 0 0xEF02 1 --- F89 0 1
46438 0x1925 Breaker Health Block3 0 0xEF02 1 --- F89 0 1
46439 0x1926 Breaker Health Output 0 0x7F 1 --- FC198 0 1
Relays
46452 0x1933 Breaker Health Incomp Trp/ 0 60000 1 s F3 10 1
Cls Time
46453 0x1934 Breaker Health Incomp 0 60000 1 s F3 4500 1
Charge Time
LOGIC ELEMENT NAMES
46240 0x185F Logic Element 1 Name 0 9 1 --- F22 Logic El #1 9
46249 0x1868 Logic Element 2 Name 0 9 1 --- F22 Logic El #2 9
46258 0x1871 Logic Element 3 Name 0 9 1 --- F22 Logic El #3 9
46267 0x187A Logic Element 4 Name 0 9 1 --- F22 Logic El #4 9
46276 0x1883 Logic Element 5 Name 0 9 1 --- F22 Logic El #5 9
46285 0x188C Logic Element 6 Name 0 9 1 --- F22 Logic El #6 9
46294 0x1895 Logic Element 7 Name 0 9 1 --- F22 Logic El #7 9
46303 0x189E Logic Element 8 Name 0 9 1 --- F22 Logic El #8 9
46314 0x18A9 High Speed Undercurrent 0 0xEF02 1 --- F89 0 1
Block 1
46315 0x18AA High Speed Undercurrent 0 0xEF02 1 --- F89 0 1
Block 2
46316 0x18AB High Speed Undercurrent 0 0xEF02 1 --- F89 0 1
Block 3
46492 0x195B Logic Element 9 Name 0 9 1 --- F22 Logic El #9 9
46501 0x1964 Logic Element 10 Name 0 9 1 --- F22 Logic El 9
#10
46510 0x196D Logic Element 11 Name 0 9 1 --- F22 Logic El 9
#11
46519 0x1976 Logic Element 12 Name 0 9 1 --- F22 Logic El 9
#12
46528 0x197F Logic Element 13 Name 0 9 1 --- F22 Logic El 9
#13
46537 0x1988 Logic Element 14 Name 0 9 1 --- F22 Logic El 9
#14
46546 0x1991 Logic Element 15 Name 0 9 1 --- F22 Logic El 9
#15
46555 0x199A Logic Element 16 Name 0 9 1 --- F22 Logic El 9
#16
SETPOINT GROUP SETTINGS

10-74 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42604 0xA2B Negative Sequence IOC 0 3 1 --- FC197 0 1
Function
42605 0xA2C Negative Sequence IOC 5 2000 1 x CT F3 100 1
Pickup
42606 0xA2D Negative Sequence IOC 0 30000 1 s F3 0 1
Delay
46833 0x1AB0 Directional Power 1 Function 0 4 1 --- FC205 0 1
46834 0x1AB1 Directional Power 1 RCA 0 359 1 ° F1 0 1
46835 0x1AB2 Directional Power 1 SMIN -1200 1200 1 x F7 100 1
Rated
Power
46836 0x1AB3 Directional Power 1 Pickup 0 6000 1 s F2 5 1
Delay
46837 0x1AB4 Directional Power 1 Output 0 0x3F 1 --- FC198 0 1
Relays 3-6
46841 0x1AB8 Directional Power 2 Function 0 4 1 --- FC205 0 1
46842 0x1AB9 Directional Power 2 RCA 0 359 1 ° F1 0 1
46843 0x1ABA Directional Power 2 SMIN -1200 1200 1 x F7 100 1
Rated
Power
46844 0x1ABB Directional Power 2 Pickup 0 6000 1 s F2 5 1
Delay
46845 0x1ABC Directional Power 2 Output 0 0x3F 1 --- FC198 0 1
Relays 3-6
PROTECTION FUNCTION BLOCKING
42644 0xA53 Neutral IOC 1 Block 1 0 0xEF02 1 --- F89 0 1
42645 0xA54 Neutral IOC 1 Block 2 0 0xEF02 1 --- F89 0 1
42646 0xA55 Neutral IOC 1 Block 3 0 0xEF02 1 --- F89 0 1
42686 0xA7D Negative Sequence OV 0 0xEF02 1 --- F89 0 1
Block 1
42687 0xA7E Negative Sequence OV 0 0xEF02 1 --- F89 0 1
Block 2
42688 0xA7F Negative Sequence OV 0 0xEF02 1 --- F89 0 1
Block 3
42692 0xA83 Phase OV Block 1 0 0xEF02 1 --- F89 0 1
42693 0xA84 Phase OV Block 2 0 0xEF02 1 --- F89 0 1
42694 0xA85 Phase OV Block 3 0 0xEF02 1 --- F89 0 1
42695 0xA86 Phase UV Block 1 0 0xEF02 1 --- F89 0 1
42696 0xA87 Phase UV Block 2 0 0xEF02 1 --- F89 0 1
42697 0xA88 Phase UV Block 3 0 0xEF02 1 --- F89 0 1
42704 0xA8F Underfrequency 1 Block 1 0 0xEF02 1 --- F89 0 1
42705 0xA90 Underfrequency 1 Block 2 0 0xEF02 1 --- F89 0 1
42706 0xA91 Underfrequency 1 Block 3 0 0xEF02 1 --- F89 0 1
42707 0xA92 Underfrequency 2 Block 1 0 0xEF02 1 --- F89 0 1
42708 0xA93 Underfrequency 2 Block 2 0 0xEF02 1 --- F89 0 1
42709 0xA94 Underfrequency 2 Block 3 0 0xEF02 1 --- F89 0 1
42710 0xA95 Overfrequency 1 Block 1 0 0xEF02 1 --- F89 0 1
42711 0xA96 Overfrequency 1 Block 2 0 0xEF02 1 --- F89 0 1
42712 0xA97 Overfrequency 1 Block 3 0 0xEF02 1 --- F89 0 1
42713 0xA98 Overfrequency 2 Block 1 0 0xEF02 1 --- F89 0 1
42714 0xA99 Overfrequency 2 Block 2 0 0xEF02 1 --- F89 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-75


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42715 0xA9A Overfrequency 2 Block 3 0 0xEF02 1 --- F89 0 1
42716 0xA9B Short Circuit Block 1 0 0xEF02 1 --- F89 0 1
42717 0xA9C Short Circuit Block 2 0 0xEF02 1 --- F89 0 1
42718 0xA9D Short Circuit Block 3 0 0xEF02 1 --- F89 0 1
42728 0xAA7 Negative Sequence IOC 0 0xEF02 1 --- F89 0 1
Block 1
42729 0xAA8 Negative Sequence IOC 0 0xEF02 1 --- F89 0 1
Block 2
42730 0xAA9 Negative Sequence IOC 0 0xEF02 1 --- F89 0 1
Block 3
46323 0x18B2 Ground Trip Block 1 0 0xEF02 1 --- F89 0 1
46324 0x18B3 Ground Trip Block 2 0 0xEF02 1 --- F89 0 1
46325 0x18B4 Ground Trip Block 3 0 0xEF02 1 --- F89 0 1
46326 0x18B5 Load Increase Alarm Block 1 0 0xEF02 1 --- F89 0 1
46327 0x18B6 Load Increase Alarm Block 2 0 0xEF02 1 --- F89 0 1
46328 0x18B7 Load Increase Alarm Block 3 0 0xEF02 1 --- F89 0 1
46329 0x18B8 Current Unbalance Block 1 0 0xEF02 1 --- F89 0 1
46330 0x18B9 Current Unbalance Block 2 0 0xEF02 1 --- F89 0 1
46331 0x18BA Current Unbalance Block 3 0 0xEF02 1 --- F89 0 1
46332 0x18BB Undercurrent Block 1 0 0xEF02 1 --- F89 0 1
46333 0x18BC Undercurrent Block 2 0 0xEF02 1 --- F89 0 1
46334 0x18BD Undercurrent Block 3 0 0xEF02 1 --- F89 0 1
46335 0x18BE Acceleration Block 1 0 0xEF02 1 --- F89 0 1
46336 0x18BF Acceleration Block 2 0 0xEF02 1 --- F89 0 1
46337 0x18C0 Acceleration Block 3 0 0xEF02 1 --- F89 0 1
46338 0x18C1 Underpower Block 1 0 0xEF02 1 --- F89 0 1
46339 0x18C2 Underpower Block 2 0 0xEF02 1 --- F89 0 1
46340 0x18C3 Underpower Block 3 0 0xEF02 1 --- F89 0 1
46341 0x18C4 Mechanical Jam Block 1 0 0xEF02 1 --- F89 0 1
46342 0x18C5 Mechanical Jam Block 2 0 0xEF02 1 --- F89 0 1
46343 0x18C6 Mechanical Jam Block 3 0 0xEF02 1 --- F89 0 1
46356 0x18D3 RTD Trouble Block 1 0 0xEF02 1 --- F89 0 1
46357 0x18D4 RTD Trouble Block 2 0 0xEF02 1 --- F89 0 1
46358 0x18D5 RTD Trouble Block 3 0 0xEF02 1 --- F89 0 1
46359 0x18D6 High Speed SC Block 1 0 0xEF02 1 --- F89 0 1
46360 0x18D7 High Speed SC Block 2 0 0xEF02 1 --- F89 0 1
46361 0x18D8 High Speed SC Block 3 0 0xEF02 1 --- F89 0 1
46838 0x1AB5 Directional Power 1 Block 1 0 0xEF02 1 --- F89 0 1
46839 0x1AB6 Directional Power 1 Block 2 0 0xEF02 1 --- F89 0 1
46840 0x1AB7 Directional Power 1 Block 3 0 0xEF02 1 --- F89 0 1
46846 0x1ABD Directional Power 2 Block 1 0 0xEF02 1 --- F89 0 1
46847 0x1ABE Directional Power 2 Block 2 0 0xEF02 1 --- F89 0 1
46848 0x1ABF Directional Power 2 Block 3 0 0xEF02 1 --- F89 0 1
FAULT REPORT
46985 0x1B48 Fault Report Delay 0 60000 1 s F3 10 1
46986 0x1B49 Fault Report Trigger 0 0xFFFF 1 --- FC134E 0x8002 1
ENHANCED LEARNED DATA

10-76 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
46991 0x1B4E Learned Data Record 1 65535 1 --- F1 1 1
Selector
MOTOR START DATA LOGGER
47001 0x1B58 Motor Data Log Number 0 6 1 --- F1 1 1
Selector
47002 0x1B59 Motor Data Log Channel -32767 32767 1 --- F4 1 1
Selector
47003 0x1B5A Motor Data Log Sample -32767 32767 1 --- F4 1 1
Selector
LOGIC ELEMENTS (TRIGGERS & BLOCKS)
41123 0x462 Logic Element 1 Trigger 0 5 1 --- FC149 0 1
Logic
41124 0x463 Logic Element 1 Block Logic 0 5 1 --- FC149 0 1
41131 0x46A Logic Element 2 Trigger 0 5 1 --- FC149 0 1
Logic
41132 0x46B Logic Element 2 Block Logic 0 5 1 --- FC149 0 1
41139 0x472 Logic Element 3 Trigger 0 5 1 --- FC149 0 1
Logic
41140 0x473 Logic Element 3 Block Logic 0 5 1 --- FC149 0 1
41147 0x47A Logic Element 4 Trigger 0 5 1 --- FC149 0 1
Logic
41148 0x47B Logic Element 4 Block Logic 0 5 1 --- FC149 0 1
41155 0x482 Logic Element 5 Trigger 0 5 1 --- FC149 0 1
Logic
41156 0x483 Logic Element 5 Block Logic 0 5 1 --- FC149 0 1
41163 0x48A Logic Element 6 Trigger 0 5 1 --- FC149 0 1
Logic
41164 0x48B Logic Element 6 Block Logic 0 5 1 --- FC149 0 1
41171 0x492 Logic Element 7 Trigger 0 5 1 --- FC149 0 1
Logic
41172 0x493 Logic Element 7 Block Logic 0 5 1 --- FC149 0 1
41179 0x49A Logic Element 8 Trigger 0 5 1 --- FC149 0 1
Logic
41180 0x49B Logic Element 8 Block Logic 0 5 1 --- FC149 0 1
41187 0x4A2 Logic Element 9 Trigger 0 5 1 --- FC149 0 1
Logic
41188 0x4A3 Logic Element 9 Block Logic 0 5 1 --- FC149 0 1
41195 0x4AA Logic Element 10 Trigger 0 5 1 --- FC149 0 1
Logic
41196 0x4AB Logic Element 10 Block 0 5 1 --- FC149 0 1
Logic
41203 0x4B2 Logic Element 11 Trigger 0 5 1 --- FC149 0 1
Logic
41204 0x4B3 Logic Element 11 Block 0 5 1 --- FC149 0 1
Logic
41211 0x4BA Logic Element 12 Trigger 0 5 1 --- FC149 0 1
Logic
41212 0x4BB Logic Element 12 Block 0 5 1 --- FC149 0 1
Logic
41219 0x4C2 Logic Element 13 Trigger 0 5 1 --- FC149 0 1
Logic
41220 0x4C3 Logic Element 13 Block 0 5 1 --- FC149 0 1
Logic

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-77


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
41227 0x4CA Logic Element 14 Trigger 0 5 1 --- FC149 0 1
Logic
41228 0x4CB Logic Element 14 Block 0 5 1 --- FC149 0 1
Logic
41235 0x4D2 Logic Element 15 Trigger 0 5 1 --- FC149 0 1
Logic
41236 0x4D3 Logic Element 15 Block 0 5 1 --- FC149 0 1
Logic
41243 0x4DA Logic Element 16 Trigger 0 5 1 --- FC149 0 1
Logic
41244 0x4DB Logic Element 16 Block 0 5 1 --- FC149 0 1
Logic
43470 0xD8D Logic Element 1 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43471 0xD8E Logic Element 1 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43472 0xD8F Logic Element 1 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43473 0xD90 Logic Element 1 Block 1 0 0xFFFF 1 --- FC134B 0 1
43474 0xD91 Logic Element 1 Block 2 0 0xFFFF 1 --- FC134B 0 1
43475 0xD92 Logic Element 1 Block 3 0 0xFFFF 1 --- FC134B 0 1
43476 0xD93 Logic Element 2 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43477 0xD94 Logic Element 2 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43478 0xD95 Logic Element 2 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43479 0xD96 Logic Element 2 Block 1 0 0xFFFF 1 --- FC134B 0 1
43480 0xD97 Logic Element 2 Block 2 0 0xFFFF 1 --- FC134B 0 1
43481 0xD98 Logic Element 2 Block 3 0 0xFFFF 1 --- FC134B 0 1
43482 0xD99 Logic Element 3 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43483 0xD9A Logic Element 3 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43484 0xD9B Logic Element 3 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43485 0xD9C Logic Element 3 Block 1 0 0xFFFF 1 --- FC134B 0 1
43486 0xD9D Logic Element 3 Block 2 0 0xFFFF 1 --- FC134B 0 1
43487 0xD9E Logic Element 3 Block 3 0 0xFFFF 1 --- FC134B 0 1
43488 0xD9F Logic Element 4 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43489 0xDA0 Logic Element 4 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43490 0xDA1 Logic Element 4 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43491 0xDA2 Logic Element 4 Block 1 0 0xFFFF 1 --- FC134B 0 1
43492 0xDA3 Logic Element 4 Block 2 0 0xFFFF 1 --- FC134B 0 1
43493 0xDA4 Logic Element 4 Block 3 0 0xFFFF 1 --- FC134B 0 1
43494 0xDA5 Logic Element 5 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43495 0xDA6 Logic Element 5 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43496 0xDA7 Logic Element 5 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43497 0xDA8 Logic Element 5 Block 1 0 0xFFFF 1 --- FC134B 0 1
43498 0xDA9 Logic Element 5 Block 2 0 0xFFFF 1 --- FC134B 0 1
43499 0xDAA Logic Element 5 Block 3 0 0xFFFF 1 --- FC134B 0 1
43500 0xDAB Logic Element 6 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43501 0xDAC Logic Element 6 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43502 0xDAD Logic Element 6 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43503 0xDAE Logic Element 6 Block 1 0 0xFFFF 1 --- FC134B 0 1
43504 0xDAF Logic Element 6 Block 2 0 0xFFFF 1 --- FC134B 0 1
43505 0xDB0 Logic Element 6 Block 3 0 0xFFFF 1 --- FC134B 0 1

10-78 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
43506 0xDB1 Logic Element 7 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43507 0xDB2 Logic Element 7 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43508 0xDB3 Logic Element 7 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43509 0xDB4 Logic Element 7 Block 1 0 0xFFFF 1 --- FC134B 0 1
43510 0xDB5 Logic Element 7 Block 2 0 0xFFFF 1 --- FC134B 0 1
43511 0xDB6 Logic Element 7 Block 3 0 0xFFFF 1 --- FC134B 0 1
43512 0xDB7 Logic Element 8 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43513 0xDB8 Logic Element 8 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43514 0xDB9 Logic Element 8 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43515 0xDBA Logic Element 8 Block 1 0 0xFFFF 1 --- FC134B 0 1
43516 0xDBB Logic Element 8 Block 2 0 0xFFFF 1 --- FC134B 0 1
43517 0xDBC Logic Element 8 Block 3 0 0xFFFF 1 --- FC134B 0 1
46365 0x18DC Logic Element 9 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46366 0x18DD Logic Element 9 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46367 0x18DE Logic Element 9 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46368 0x18DF Logic Element 9 Block 1 0 0xFFFF 1 --- FC134B 0 1
46369 0x18E0 Logic Element 9 Block 2 0 0xFFFF 1 --- FC134B 0 1
46370 0x18E1 Logic Element 9 Block 3 0 0xFFFF 1 --- FC134B 0 1
46371 0x18E2 Logic Element 10 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46372 0x18E3 Logic Element 10 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46373 0x18E4 Logic Element 10 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46374 0x18E5 Logic Element 10 Block 1 0 0xFFFF 1 --- FC134B 0 1
46375 0x18E6 Logic Element 10 Block 2 0 0xFFFF 1 --- FC134B 0 1
46376 0x18E7 Logic Element 10 Block 3 0 0xFFFF 1 --- FC134B 0 1
46377 0x18E8 Logic Element 11 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46378 0x18E9 Logic Element 11 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46379 0x18EA Logic Element 11 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46380 0x18EB Logic Element 11 Block 1 0 0xFFFF 1 --- FC134B 0 1
46381 0x18EC Logic Element 11 Block 2 0 0xFFFF 1 --- FC134B 0 1
46382 0x18ED Logic Element 11 Block 3 0 0xFFFF 1 --- FC134B 0 1
46383 0x18EE Logic Element 12 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46384 0x18EF Logic Element 12 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46385 0x18F0 Logic Element 12 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46386 0x18F1 Logic Element 12 Block 1 0 0xFFFF 1 --- FC134B 0 1
46387 0x18F2 Logic Element 12 Block 2 0 0xFFFF 1 --- FC134B 0 1
46388 0x18F3 Logic Element 12 Block 3 0 0xFFFF 1 --- FC134B 0 1
46389 0x18F4 Logic Element 13 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46390 0x18F5 Logic Element 13 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46391 0x18F6 Logic Element 13 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46392 0x18F7 Logic Element 13 Block 1 0 0xFFFF 1 --- FC134B 0 1
46393 0x18F8 Logic Element 13 Block 2 0 0xFFFF 1 --- FC134B 0 1
46394 0x18F9 Logic Element 13 Block 3 0 0xFFFF 1 --- FC134B 0 1
46395 0x18FA Logic Element 14 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46396 0x18FB Logic Element 14 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46397 0x18FC Logic Element 14 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46398 0x18FD Logic Element 14 Block 1 0 0xFFFF 1 --- FC134B 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-79


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
46399 0x18FE Logic Element 14 Block 2 0 0xFFFF 1 --- FC134B 0 1
46400 0x18FF Logic Element 14 Block 3 0 0xFFFF 1 --- FC134B 0 1
46401 0x1900 Logic Element 15 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46402 0x1901 Logic Element 15 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46403 0x1902 Logic Element 15 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46404 0x1903 Logic Element 15 Block 1 0 0xFFFF 1 --- FC134B 0 1
46405 0x1904 Logic Element 15 Block 2 0 0xFFFF 1 --- FC134B 0 1
46406 0x1905 Logic Element 15 Block 3 0 0xFFFF 1 --- FC134B 0 1
46407 0x1906 Logic Element 16 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46408 0x1907 Logic Element 16 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46409 0x1908 Logic Element 16 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46410 0x1909 Logic Element 16 Block 1 0 0xFFFF 1 --- FC134B 0 1
46411 0x190A Logic Element 16 Block 2 0 0xFFFF 1 --- FC134B 0 1
46412 0x190B Logic Element 16 Block 3 0 0xFFFF 1 --- FC134B 0 1
47012 0x1B63 Logic Element 1 Number of 2 8 1 --- F1 3 1
Triggers
47013 0x1B64 Logic Element 1 Number of 2 4 1 --- F1 3 1
Blocks
47014 0x1B65 Logic Element 1 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47015 0x1B66 Logic Element 1 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47016 0x1B67 Logic Element 1 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47017 0x1B68 Logic Element 1 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47018 0x1B69 Logic Element 1 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47019 0x1B6A Logic Element 1 Block 4 0 0xFFFF 1 --- FC134B 0 1
47020 0x1B6B Logic Element 2 Number of 2 8 1 --- F1 3 1
Triggers
47021 0x1B6C Logic Element 2 Number of 2 4 1 --- F1 3 1
Blocks
47022 0x1B6D Logic Element 2 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47023 0x1B6E Logic Element 2 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47024 0x1B6F Logic Element 2 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47025 0x1B70 Logic Element 2 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47026 0x1B71 Logic Element 2 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47027 0x1B72 Logic Element 2 Block 4 0 0xFFFF 1 --- FC134B 0 1
47028 0x1B73 Logic Element 3 Number of 2 8 1 --- F1 3 1
Triggers
47029 0x1B74 Logic Element 3 Number of 2 4 1 --- F1 3 1
Blocks
47030 0x1B75 Logic Element 3 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47031 0x1B76 Logic Element 3 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47032 0x1B77 Logic Element 3 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47033 0x1B78 Logic Element 3 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47034 0x1B79 Logic Element 3 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47035 0x1B7A Logic Element 3 Block 4 0 0xFFFF 1 --- FC134B 0 1
47036 0x1B7B Logic Element 4 Number of 2 8 1 --- F1 3 1
Triggers
47037 0x1B7C Logic Element 4 Number of 2 4 1 --- F1 3 1
Blocks
47038 0x1B7D Logic Element 4 Trigger 4 0 0xFFFF 1 --- FC134B 0 1

10-80 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
47039 0x1B7E Logic Element 4 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47040 0x1B7F Logic Element 4 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47041 0x1B80 Logic Element 4 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47042 0x1B81 Logic Element 4 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47043 0x1B82 Logic Element 4 Block 4 0 0xFFFF 1 --- FC134B 0 1
47044 0x1B83 Logic Element 5 Number of 2 8 1 --- F1 3 1
Triggers
47045 0x1B84 Logic Element 5 Number of 2 4 1 --- F1 3 1
Blocks
47046 0x1B85 Logic Element 5 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47047 0x1B86 Logic Element 5 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47048 0x1B87 Logic Element 5 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47049 0x1B88 Logic Element 5 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47050 0x1B89 Logic Element 5 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47051 0x1B8A Logic Element 5 Block 4 0 0xFFFF 1 --- FC134B 0 1
47052 0x1B8B Logic Element 6 Number of 2 8 1 --- F1 3 1
Triggers
47053 0x1B8C Logic Element 6 Number of 2 4 1 --- F1 3 1
Blocks
47054 0x1B8D Logic Element 6 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47055 0x1B8E Logic Element 6 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47056 0x1B8F Logic Element 6 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47057 0x1B90 Logic Element 6 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47058 0x1B91 Logic Element 6 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47059 0x1B92 Logic Element 6 Block 4 0 0xFFFF 1 --- FC134B 0 1
47060 0x1B93 Logic Element 7 Number of 2 8 1 --- F1 3 1
Triggers
47061 0x1B94 Logic Element 7 Number of 2 4 1 --- F1 3 1
Blocks
47062 0x1B95 Logic Element 7 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47063 0x1B96 Logic Element 7 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47064 0x1B97 Logic Element 7 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47065 0x1B98 Logic Element 7 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47066 0x1B99 Logic Element 7 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47067 0x1B9A Logic Element 7 Block 4 0 0xFFFF 1 --- FC134B 0 1
47068 0x1B9B Logic Element 8 Number of 2 8 1 --- F1 3 1
Triggers
47069 0x1B9C Logic Element 8 Number of 2 4 1 --- F1 3 1
Blocks
47070 0x1B9D Logic Element 8 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47071 0x1B9E Logic Element 8 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47072 0x1B9F Logic Element 8 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47073 0x1BA0 Logic Element 8 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47074 0x1BA1 Logic Element 8 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47075 0x1BA2 Logic Element 8 Block 4 0 0xFFFF 1 --- FC134B 0 1
47076 0x1BA3 Logic Element 9 Number of 2 8 1 --- F1 3 1
Triggers
47077 0x1BA4 Logic Element 9 Number of 2 4 1 --- F1 3 1
Blocks
47078 0x1BA5 Logic Element 9 Trigger 4 0 0xFFFF 1 --- FC134B 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-81


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
47079 0x1BA6 Logic Element 9 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47080 0x1BA7 Logic Element 9 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47081 0x1BA8 Logic Element 9 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47082 0x1BA9 Logic Element 9 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47083 0x1BAA Logic Element 9 Block 4 0 0xFFFF 1 --- FC134B 0 1
47084 0x1BAB Logic Element 10 Number of 2 8 1 --- F1 3 1
Triggers
47085 0x1BAC Logic Element 10 Number of 2 4 1 --- F1 3 1
Blocks
47086 0x1BAD Logic Element 10 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47087 0x1BAE Logic Element 10 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47088 0x1BAF Logic Element 10 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47089 0x1BB0 Logic Element 10 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47090 0x1BB1 Logic Element 10 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47091 0x1BB2 Logic Element 10 Block 4 0 0xFFFF 1 --- FC134B 0 1
47092 0x1BB3 Logic Element 11 Number of 2 8 1 --- F1 3 1
Triggers
47093 0x1BB4 Logic Element 11 Number of 2 4 1 --- F1 3 1
Blocks
47094 0x1BB5 Logic Element 11 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47095 0x1BB6 Logic Element 11 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47096 0x1BB7 Logic Element 11 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47097 0x1BB8 Logic Element 11 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47098 0x1BB9 Logic Element 11 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47099 0x1BBA Logic Element 11 Block 4 0 0xFFFF 1 --- FC134B 0 1
47100 0x1BBB Logic Element 12 Number of 2 8 1 --- F1 3 1
Triggers
47101 0x1BBC Logic Element 12 Number of 2 4 1 --- F1 3 1
Blocks
47102 0x1BBD Logic Element 12 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47103 0x1BBE Logic Element 12 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47104 0x1BBF Logic Element 12 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47105 0x1BC0 Logic Element 12 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47106 0x1BC1 Logic Element 12 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47107 0x1BC2 Logic Element 12 Block 4 0 0xFFFF 1 --- FC134B 0 1
47108 0x1BC3 Logic Element 13 Number of 2 8 1 --- F1 3 1
Triggers
47109 0x1BC4 Logic Element 13 Number of 2 4 1 --- F1 3 1
Blocks
47110 0x1BC5 Logic Element 13 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47111 0x1BC6 Logic Element 13 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47112 0x1BC7 Logic Element 13 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47113 0x1BC8 Logic Element 13 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47114 0x1BC9 Logic Element 13 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47115 0x1BCA Logic Element 13 Block 4 0 0xFFFF 1 --- FC134B 0 1
47116 0x1BCB Logic Element 14 Number of 2 8 1 --- F1 3 1
Triggers
47117 0x1BCC Logic Element 14 Number of 2 4 1 --- F1 3 1
Blocks
47118 0x1BCD Logic Element 14 Trigger 4 0 0xFFFF 1 --- FC134B 0 1

10-82 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
47119 0x1BCE Logic Element 14 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47120 0x1BCF Logic Element 14 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47121 0x1BD0 Logic Element 14 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47122 0x1BD1 Logic Element 14 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47123 0x1BD2 Logic Element 14 Block 4 0 0xFFFF 1 --- FC134B 0 1
47124 0x1BD3 Logic Element 15 Number of 2 8 1 --- F1 3 1
Triggers
47125 0x1BD4 Logic Element 15 Number of 2 4 1 --- F1 3 1
Blocks
47126 0x1BD5 Logic Element 15 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47127 0x1BD6 Logic Element 15 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47128 0x1BD7 Logic Element 15 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47129 0x1BD8 Logic Element 15 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47130 0x1BD9 Logic Element 15 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47131 0x1BDA Logic Element 15 Block 4 0 0xFFFF 1 --- FC134B 0 1
47132 0x1BDB Logic Element 16 Number of 2 8 1 --- F1 3 1
Triggers
47133 0x1BDC Logic Element 16 Number of 2 4 1 --- F1 3 1
Blocks
47134 0x1BDD Logic Element 16 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47135 0x1BDE Logic Element 16 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47136 0x1BDF Logic Element 16 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47137 0x1BE0 Logic Element 16 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47138 0x1BE1 Logic Element 16 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47139 0x1BE2 Logic Element 16 Block 4 0 0xFFFF 1 --- FC134B 0 1
DEMAND
47189 0x1C14 Current Demand 1 Function 0 2 1 --- FC206 0 1
47191 0x1C16 Current Demand 1 0 2 1 --- FC431 0 1
Measurement Type
47192 0x1C17 Current Demand 1 90% 0 4 1 --- FC432 2 1
Response Time
47193 0x1C18 Current Demand 1 Time 0 4 1 --- FC432 3 1
Interval
47194 0x1C19 Current Demand 1 Pkp 10 10000 1 A F1 1000 1
47195 0x1C1A Current Demand 1 Relays 0 0x7F 1 --- FC198 0 1
47196 0x1C1B Current Demand 1 Block 1 0 0xEF02 1 --- F89 0 1
47197 0x1C1C Current Demand 1 Block 2 0 0xEF02 1 --- F89 0 1
47198 0x1C1D Current Demand 1 Block 3 0 0xEF02 1 --- F89 0 1
47209 0x1C28 Real Power Demand 0 2 1 --- FC206 0 1
Function
47210 0x1C29 Real Power Demand 0 2 1 --- FC431 0 1
Measurement Type
47211 0x1C2A Real Power Demand 90% 0 4 1 --- FC432 2 1
Response Time
47212 0x1C2B Real Power Demand Time 0 4 1 --- FC432 3 1
Interval
47213 0x1C2C Real Power Demand Pkp 1 3000000 1 kW F10 10000 2
47215 0x1C2E Real Power Demand Relays 0 0x7F 1 --- FC198 0 1
47216 0x1C2F Real Power Demand Block 1 0 0xEF02 1 --- F89 0 1
47217 0x1C30 Real Power Demand Block 2 0 0xEF02 1 --- F89 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-83


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
47218 0x1C31 Real Power Demand Block 3 0 0xEF02 1 --- F89 0 1
47219 0x1C32 Reactive Power Demand 0 2 1 --- FC206 0 1
Function
47220 0x1C33 Reactive Power Demand 0 2 1 --- FC431 0 1
Measurement Type
47221 0x1C34 Reactive Power Demand 0 4 1 --- FC432 2 1
90% Response Time
47222 0x1C35 Reactive Power Demand 0 4 1 --- FC432 3 1
Time Interval
47223 0x1C36 Reactive Power Demand 1 3000000 1 kvar F10 10000 2
Pkp
47225 0x1C38 Reactive Power Demand 0 0x7F 1 --- FC198 0 1
Relays
47226 0x1C39 Reactive Power Demand 0 0xEF02 1 --- F89 0 1
Block 1
47227 0x1C3A Reactive Power Demand 0 0xEF02 1 --- F89 0 1
Block 2
47228 0x1C3B Reactive Power Demand 0 0xEF02 1 --- F89 0 1
Block 3
47229 0x1C3C Apparent Power Demand 0 2 1 --- FC206 0 1
Function
47230 0x1C3D Apparent Power Demand 0 2 1 --- FC431 0 1
Measurement Type
47231 0x1C3E Apparent Power Demand 0 4 1 --- FC432 2 1
90% Response Time
47232 0x1C3F Apparent Power Demand 0 4 1 --- FC432 3 1
Time Interval
47233 0x1C40 Apparent Power Demand 1 3000000 1 kVA F10 10000 2
Pkp
47235 0x1C42 Apparent Power Demand 0 0x7F 1 --- FC198 0 1
Relays
47236 0x1C43 Apparent Power Demand 0 0xEF02 1 --- F89 0 1
Block 1
47237 0x1C44 Apparent Power Demand 0 0xEF02 1 --- F89 0 1
Block 2
47238 0x1C45 Apparent Power Demand 0 0xEF02 1 --- F89 0 1
Block 3
LOCKOUT
47242 0x1C49 Lockout Function 0 1 1 --- FC126 0 1
47243 0x1C4A Lockout Input 1 0 0xFFFF 1 --- FC134D 0 1
47244 0x1C4B Lockout Input 2 0 0xFFFF 1 --- FC134D 0 1
47245 0x1C4C Lockout Input 3 0 0xFFFF 1 --- FC134D 0 1
47246 0x1C4D Lockout Input 4 0 0xFFFF 1 --- FC134D 0 1
47247 0x1C4E Lockout Input 5 0 0xFFFF 1 --- FC134D 0 1
47248 0x1C4F Lockout Input 6 0 0xFFFF 1 --- FC134D 0 1
47249 0x1C50 Lockout Input 7 0 0xFFFF 1 --- FC134D 0 1
47250 0x1C51 Lockout Input 8 0 0xFFFF 1 --- FC134D 0 1
47251 0x1C52 Lockout Input 9 0 0xFFFF 1 --- FC134D 0 1
47252 0x1C53 Lockout Input 10 0 0xFFFF 1 --- FC134D 0 1
47253 0x1C54 Lockout Supervision 0 0xFFFF 1 --- FC134C 1 1
47254 0x1C55 Lockout Reset 0 0xFFFF 1 --- FC134F 0 1
47255 0x1C56 Lockout Reset From PB 0 1 1 --- FC126 0 1
Reset

10-84 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
47256 0x1C57 Lockout Block Reset Lockout 0 0xFFFF 1 --- FC134D 0x8002 1
47257 0x1C58 Lockout Block 1 0 0xEF02 1 --- F89 0 1
47258 0x1C59 Lockout Block 2 0 0xEF02 1 --- F89 0 1
47259 0x1C5A Lockout Block 3 0 0xEF02 1 --- F89 0 1
POSITIVE SEQ UV
47263 0x1C5E Positive Seq UV 1 Function 0 3 1 --- FC197 0 1
47264 0x1C5F Positive Seq UV 1 Pkp 0 125 1 x VT F3 75 1
47265 0x1C60 Positive Seq UV 1 Curve 0 1 1 --- F93 1 1
47266 0x1C61 Positive Seq UV 1 Delay 0 60000 1 s F3 200 1
47267 0x1C62 Positive Seq UV 1 Min V 0 125 1 x VT F3 10 1
47268 0x1C63 Positive Seq UV 1 Relays 0 0x7F 1 --- FC198 0 1
47269 0x1C64 Positive Seq UV 1 Block 1 0 0xEF02 1 --- F89 0 1
47270 0x1C65 Positive Seq UV 1 Block 2 0 0xEF02 1 --- F89 0 1
47271 0x1C66 Positive Seq UV 1 Block 3 0 0xEF02 1 --- F89 0 1
47272 0x1C67 Positive Seq UV 2 Function 0 3 1 --- FC197 0 1
47273 0x1C68 Positive Seq UV 2 Pkp 0 125 1 x VT F3 75 1
47274 0x1C69 Positive Seq UV 2 Curve 0 1 1 --- F93 1 1
47275 0x1C6A Positive Seq UV 2 Delay 0 60000 1 s F3 200 1
47276 0x1C6B Positive Seq UV 2 Min V 0 125 1 x VT F3 10 1
47277 0x1C6C Positive Seq UV 2 Relays 0 0x7F 1 --- FC198 0 1
47278 0x1C6D Positive Seq UV 2 Block 1 0 0xEF02 1 --- F89 0 1
47279 0x1C6E Positive Seq UV 2 Block 2 0 0xEF02 1 --- F89 0 1
47280 0x1C6F Positive Seq UV 2 Block 3 0 0xEF02 1 --- F89 0 1
CT FAILURE
47282 0x1C71 CT Failure Function 0 2 1 --- FC206 0 1
47285 0x1C74 CT Failure Output Relays 3-6 0 0x3F 1 --- FC198 0 1
47286 0x1C75 CT Failure Block 1 0 0xEF02 1 --- F89 0 1
47287 0x1C76 CT Failure Block 2 0 0xEF02 1 --- F89 0 1
47288 0x1C77 CT Failure Block 3 0 0xEF02 1 --- F89 0 1
47296 0x1C7F W1 CT Fail 3I0 Current PKP 3 200 1 x CT F3 10 1
47297 0x1C80 W1 CT Fail 3V0 Voltage 5 200 1 x VT F3 20 1
Inhibit
47298 0x1C81 W1 CT Fail GND Current 2 200 1 x CT F3 20 1
Inhibit
47300 0x1C83 W1 CT Fail Time Delay 0 6000 1 s F3 0 1
TESTING
47303 0x1C86 Force leds 0 1 --- FC126 0 1
47304 0x1C87 Led 1 0 1 --- FC103 0 1
47305 0x1C88 Led 2 0 1 --- FC103 0 1
47306 0x1C89 Led 3 0 1 --- FC103 0 1
47307 0x1C8A Led 4 0 1 --- FC103 0 1
47308 0x1C8B Led 5 0 1 --- FC103 0 1
47309 0x1C8C Led 6 0 1 --- FC103 0 1
47310 0x1C8D Led 7 0 1 --- FC103 0 1
47311 0x1C8E Led 8 0 1 --- FC103 0 1
47312 0x1C8F Led 9 0 1 --- FC103 0 1
47313 0x1C90 Led 10 0 1 --- FC103 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-85


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
47314 0x1C91 Led 11 0 1 --- FC103 0 1
47315 0x1C92 Led 12 0 1 --- FC103 0 1
47318 0x1C95 Force Output Relays 0 1 --- FC126 0 1
47319 0x1C96 Relay 1 Trip 0 1 --- FC103 0 1
47320 0x1C97 Relay 2 Close 0 1 --- FC103 0 1
47321 0x1C98 Relay 3 Auxiliary 0 1 --- FC103 0 1
47322 0x1C99 Relay 4 Auxiliary 0 1 --- FC103 0 1
47323 0x1C9A Relay 5 Auxiliary 0 1 --- FC103 0 1
47324 0x1C9B Relay 6 Auxiliary 0 1 --- FC103 0 1
61850 MAPPING
47327 0x1C9E Analog input 1 Value 0 251 1 --- F88 0 1
47328 0x1C9F Analog input 1 db 0 100000 1 % F17 0 2
47330 0x1CA1 Analog input 1 Min -2147483648 2147483647 1 --- F13 0 2
47332 0x1CA3 Analog input 1 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47334 0x1CA5 Analog input 2 Value 0 251 1 --- F88 0 1
47335 0x1CA6 Analog input 2 db 0 100000 1 % F17 0 2
47337 0x1CA8 Analog input 2 Min -2147483648 2147483647 1 --- F13 0 2
47339 0x1CAA Analog input 2 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47341 0x1CAC Analog input 3 Value 0 251 1 --- F88 0 1
47342 0x1CAD Analog input 3 db 0 100000 1 % F17 0 2
47344 0x1CAF Analog input 3 Min -2147483648 2147483647 1 --- F13 0 2
47346 0x1CB1 Analog input 3 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47348 0x1CB3 Analog input 4 Value 0 251 1 --- F88 0 1
47349 0x1CB4 Analog input 4 db 0 100000 1 % F17 0 2
47351 0x1CB6 Analog input 4 Min -2147483648 2147483647 1 --- F13 0 2
47353 0x1CB8 Analog input 4 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47355 0x1CBA Analog input 5 Value 0 251 1 --- F88 0 1
47356 0x1CBB Analog input 5 db 0 100000 1 % F17 0 2
47358 0x1CBD Analog input 5 Min -2147483648 2147483647 1 --- F13 0 2
47360 0x1CBF Analog input 5 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47362 0x1CC1 Analog input 6 Value 0 251 1 --- F88 0 1
47363 0x1CC2 Analog input 6 db 0 100000 1 % F17 0 2
47365 0x1CC4 Analog input 6 Min -2147483648 2147483647 1 --- F13 0 2
47367 0x1CC6 Analog input 6 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47369 0x1CC8 Analog input 7 Value 0 251 1 --- F88 0 1
47370 0x1CC9 Analog input 7 db 0 100000 1 % F17 0 2
47372 0x1CCB Analog input 7 Min -2147483648 2147483647 1 --- F13 0 2
47374 0x1CCD Analog input 7 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47376 0x1CCF Analog input 8 Value 0 251 1 --- F88 0 1
47377 0x1CD0 Analog input 8 db 0 100000 1 % F17 0 2
47379 0x1CD2 Analog input 8 Min -2147483648 2147483647 1 --- F13 0 2

10-86 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
47381 0x1CD4 Analog input 8 Max -2147483648 2147483647 1 --- F13 214748364 2
7
FLEXCURVE C
47387 0x1CDA Flex Curve C 1.03 X PU 0 65535 1 ms F1 0 1
47388 0x1CDB Flex Curve C 1.05 X PU 0 65535 1 ms F1 0 1
47389 0x1CDC Flex Curve C 1.10 X PU 0 65535 1 ms F1 0 1
47390 0x1CDD Flex Curve C 1.20 X PU 0 65535 1 ms F1 0 1
47391 0x1CDE Flex Curve C 1.30 X PU 0 65535 1 ms F1 0 1
47392 0x1CDF Flex Curve C 1.40 X PU 0 65535 1 ms F1 0 1
47393 0x1CE0 Flex Curve C 1.50 X PU 0 65535 1 ms F1 0 1
47394 0x1CE1 Flex Curve C 1.60 X PU 0 65535 1 ms F1 0 1
47395 0x1CE2 Flex Curve C 1.70 X PU 0 65535 1 ms F1 0 1
47396 0x1CE3 Flex Curve C 1.80 X PU 0 65535 1 ms F1 0 1
47397 0x1CE4 Flex Curve C 1.90 X PU 0 65535 1 ms F1 0 1
47398 0x1CE5 Flex Curve C 2.00 X PU 0 65535 1 ms F1 0 1
47399 0x1CE6 Flex Curve C 2.10 X PU 0 65535 1 ms F1 0 1
47400 0x1CE7 Flex Curve C 2.20 X PU 0 65535 1 ms F1 0 1
47401 0x1CE8 Flex Curve C 2.30 X PU 0 65535 1 ms F1 0 1
47402 0x1CE9 Flex Curve C 2.40 X PU 0 65535 1 ms F1 0 1
47403 0x1CEA Flex Curve C 2.50 X PU 0 65535 1 ms F1 0 1
47404 0x1CEB Flex Curve C 2.60 X PU 0 65535 1 ms F1 0 1
47405 0x1CEC Flex Curve C 2.70 X PU 0 65535 1 ms F1 0 1
47406 0x1CED Flex Curve C 2.80 X PU 0 65535 1 ms F1 0 1
47407 0x1CEE Flex Curve C 2.90 X PU 0 65535 1 ms F1 0 1
47408 0x1CEF Flex Curve C 3.00 X PU 0 65535 1 ms F1 0 1
47409 0x1CF0 Flex Curve C 3.10 X PU 0 65535 1 ms F1 0 1
47410 0x1CF1 Flex Curve C 3.20 X PU 0 65535 1 ms F1 0 1
47411 0x1CF2 Flex Curve C 3.30 X PU 0 65535 1 ms F1 0 1
47412 0x1CF3 Flex Curve C 3.40 X PU 0 65535 1 ms F1 0 1
47413 0x1CF4 Flex Curve C 3.50 X PU 0 65535 1 ms F1 0 1
47414 0x1CF5 Flex Curve C 3.60 X PU 0 65535 1 ms F1 0 1
47415 0x1CF6 Flex Curve C 3.70 X PU 0 65535 1 ms F1 0 1
47416 0x1CF7 Flex Curve C 3.80 X PU 0 65535 1 ms F1 0 1
47417 0x1CF8 Flex Curve C 3.90 X PU 0 65535 1 ms F1 0 1
47418 0x1CF9 Flex Curve C 4.00 X PU 0 65535 1 ms F1 0 1
47419 0x1CFA Flex Curve C 4.10 X PU 0 65535 1 ms F1 0 1
47420 0x1CFB Flex Curve C 4.20 X PU 0 65535 1 ms F1 0 1
47421 0x1CFC Flex Curve C 4.30 X PU 0 65535 1 ms F1 0 1
47422 0x1CFD Flex Curve C 4.40 X PU 0 65535 1 ms F1 0 1
47423 0x1CFE Flex Curve C 4.50 X PU 0 65535 1 ms F1 0 1
47424 0x1CFF Flex Curve C 4.60 X PU 0 65535 1 ms F1 0 1
47425 0x1D00 Flex Curve C 4.70 X PU 0 65535 1 ms F1 0 1
47426 0x1D01 Flex Curve C 4.80 X PU 0 65535 1 ms F1 0 1
47427 0x1D02 Flex Curve C 4.90 X PU 0 65535 1 ms F1 0 1
47428 0x1D03 Flex Curve C 5.00 X PU 0 65535 1 ms F1 0 1
47429 0x1D04 Flex Curve C 5.10 X PU 0 65535 1 ms F1 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-87


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
47430 0x1D05 Flex Curve C 5.20 X PU 0 65535 1 ms F1 0 1
47431 0x1D06 Flex Curve C 5.30 X PU 0 65535 1 ms F1 0 1
47432 0x1D07 Flex Curve C 5.40 X PU 0 65535 1 ms F1 0 1
47433 0x1D08 Flex Curve C 5.50 X PU 0 65535 1 ms F1 0 1
47434 0x1D09 Flex Curve C 5.60 X PU 0 65535 1 ms F1 0 1
47435 0x1D0A Flex Curve C 5.70 X PU 0 65535 1 ms F1 0 1
47436 0x1D0B Flex Curve C 5.80 X PU 0 65535 1 ms F1 0 1
47437 0x1D0C Flex Curve C 5.90 X PU 0 65535 1 ms F1 0 1
47438 0x1D0D Flex Curve C 6.00 X PU 0 65535 1 ms F1 0 1
47439 0x1D0E Flex Curve C 6.50 X PU 0 65535 1 ms F1 0 1
47440 0x1D0F Flex Curve C 7.00 X PU 0 65535 1 ms F1 0 1
47441 0x1D10 Flex Curve C 7.50 X PU 0 65535 1 ms F1 0 1
47442 0x1D11 Flex Curve C 8.00 X PU 0 65535 1 ms F1 0 1
47443 0x1D12 Flex Curve C 8.50 X PU 0 65535 1 ms F1 0 1
47444 0x1D13 Flex Curve C 9.00 X PU 0 65535 1 ms F1 0 1
47445 0x1D14 Flex Curve C 9.50 X PU 0 65535 1 ms F1 0 1
47446 0x1D15 Flex Curve C 10.00 X PU 0 65535 1 ms F1 0 1
47447 0x1D16 Flex Curve C 10.50 X PU 0 65535 1 ms F1 0 1
47448 0x1D17 Flex Curve C 11.00 X PU 0 65535 1 ms F1 0 1
47449 0x1D18 Flex Curve C 11.50 X PU 0 65535 1 ms F1 0 1
47450 0x1D19 Flex Curve C 12.00 X PU 0 65535 1 ms F1 0 1
47451 0x1D1A Flex Curve C 12.50 X PU 0 65535 1 ms F1 0 1
47452 0x1D1B Flex Curve C 13.00 X PU 0 65535 1 ms F1 0 1
47453 0x1D1C Flex Curve C 13.50 X PU 0 65535 1 ms F1 0 1
47454 0x1D1D Flex Curve C 14.00 X PU 0 65535 1 ms F1 0 1
47455 0x1D1E Flex Curve C 14.50 X PU 0 65535 1 ms F1 0 1
47456 0x1D1F Flex Curve C 15.00 X PU 0 65535 1 ms F1 0 1
47457 0x1D20 Flex Curve C 15.50 X PU 0 65535 1 ms F1 0 1
47458 0x1D21 Flex Curve C 16.00 X PU 0 65535 1 ms F1 0 1
47459 0x1D22 Flex Curve C 16.50 X PU 0 65535 1 ms F1 0 1
47460 0x1D23 Flex Curve C 17.00 X PU 0 65535 1 ms F1 0 1
47461 0x1D24 Flex Curve C 17.50 X PU 0 65535 1 ms F1 0 1
47462 0x1D25 Flex Curve C 18.00 X PU 0 65535 1 ms F1 0 1
47463 0x1D26 Flex Curve C 18.50 X PU 0 65535 1 ms F1 0 1
47464 0x1D27 Flex Curve C 19.00 X PU 0 65535 1 ms F1 0 1
47465 0x1D28 Flex Curve C 19.50 X PU 0 65535 1 ms F1 0 1
47466 0x1D29 Flex Curve C 20.00 X PU 0 65535 1 ms F1 0 1
FLEXCURVE D
47468 0x1D2B Flex Curve D 1.03 X PU 0 65535 1 ms F1 0 1
47469 0x1D2C Flex Curve D 1.05 X PU 0 65535 1 ms F1 0 1
47470 0x1D2D Flex Curve D 1.10 X PU 0 65535 1 ms F1 0 1
47471 0x1D2E Flex Curve D 1.20 X PU 0 65535 1 ms F1 0 1
47472 0x1D2F Flex Curve D 1.30 X PU 0 65535 1 ms F1 0 1
47473 0x1D30 Flex Curve D 1.40 X PU 0 65535 1 ms F1 0 1
47474 0x1D31 Flex Curve D 1.50 X PU 0 65535 1 ms F1 0 1
47475 0x1D32 Flex Curve D 1.60 X PU 0 65535 1 ms F1 0 1

10-88 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
47476 0x1D33 Flex Curve D 1.70 X PU 0 65535 1 ms F1 0 1
47477 0x1D34 Flex Curve D 1.80 X PU 0 65535 1 ms F1 0 1
47478 0x1D35 Flex Curve D 1.90 X PU 0 65535 1 ms F1 0 1
47479 0x1D36 Flex Curve D 2.00 X PU 0 65535 1 ms F1 0 1
47480 0x1D37 Flex Curve D 2.10 X PU 0 65535 1 ms F1 0 1
47481 0x1D38 Flex Curve D 2.20 X PU 0 65535 1 ms F1 0 1
47482 0x1D39 Flex Curve D 2.30 X PU 0 65535 1 ms F1 0 1
47483 0x1D3A Flex Curve D 2.40 X PU 0 65535 1 ms F1 0 1
47484 0x1D3B Flex Curve D 2.50 X PU 0 65535 1 ms F1 0 1
47485 0x1D3C Flex Curve D 2.60 X PU 0 65535 1 ms F1 0 1
47486 0x1D3D Flex Curve D 2.70 X PU 0 65535 1 ms F1 0 1
47487 0x1D3E Flex Curve D 2.80 X PU 0 65535 1 ms F1 0 1
47488 0x1D3F Flex Curve D 2.90 X PU 0 65535 1 ms F1 0 1
47489 0x1D40 Flex Curve D 3.00 X PU 0 65535 1 ms F1 0 1
47490 0x1D41 Flex Curve D 3.10 X PU 0 65535 1 ms F1 0 1
47491 0x1D42 Flex Curve D 3.20 X PU 0 65535 1 ms F1 0 1
47492 0x1D43 Flex Curve D 3.30 X PU 0 65535 1 ms F1 0 1
47493 0x1D44 Flex Curve D 3.40 X PU 0 65535 1 ms F1 0 1
47494 0x1D45 Flex Curve D 3.50 X PU 0 65535 1 ms F1 0 1
47495 0x1D46 Flex Curve D 3.60 X PU 0 65535 1 ms F1 0 1
47496 0x1D47 Flex Curve D 3.70 X PU 0 65535 1 ms F1 0 1
47497 0x1D48 Flex Curve D 3.80 X PU 0 65535 1 ms F1 0 1
47498 0x1D49 Flex Curve D 3.90 X PU 0 65535 1 ms F1 0 1
47499 0x1D4A Flex Curve D 4.00 X PU 0 65535 1 ms F1 0 1
47500 0x1D4B Flex Curve D 4.10 X PU 0 65535 1 ms F1 0 1
47501 0x1D4C Flex Curve D 4.20 X PU 0 65535 1 ms F1 0 1
47502 0x1D4D Flex Curve D 4.30 X PU 0 65535 1 ms F1 0 1
47503 0x1D4E Flex Curve D 4.40 X PU 0 65535 1 ms F1 0 1
47504 0x1D4F Flex Curve D 4.50 X PU 0 65535 1 ms F1 0 1
47505 0x1D50 Flex Curve D 4.60 X PU 0 65535 1 ms F1 0 1
47506 0x1D51 Flex Curve D 4.70 X PU 0 65535 1 ms F1 0 1
47507 0x1D52 Flex Curve D 4.80 X PU 0 65535 1 ms F1 0 1
47508 0x1D53 Flex Curve D 4.90 X PU 0 65535 1 ms F1 0 1
47509 0x1D54 Flex Curve D 5.00 X PU 0 65535 1 ms F1 0 1
47510 0x1D55 Flex Curve D 5.10 X PU 0 65535 1 ms F1 0 1
47511 0x1D56 Flex Curve D 5.20 X PU 0 65535 1 ms F1 0 1
47512 0x1D57 Flex Curve D 5.30 X PU 0 65535 1 ms F1 0 1
47513 0x1D58 Flex Curve D 5.40 X PU 0 65535 1 ms F1 0 1
47514 0x1D59 Flex Curve D 5.50 X PU 0 65535 1 ms F1 0 1
47515 0x1D5A Flex Curve D 5.60 X PU 0 65535 1 ms F1 0 1
47516 0x1D5B Flex Curve D 5.70 X PU 0 65535 1 ms F1 0 1
47517 0x1D5C Flex Curve D 5.80 X PU 0 65535 1 ms F1 0 1
47518 0x1D5D Flex Curve D 5.90 X PU 0 65535 1 ms F1 0 1
47519 0x1D5E Flex Curve D 6.00 X PU 0 65535 1 ms F1 0 1
47520 0x1D5F Flex Curve D 6.50 X PU 0 65535 1 ms F1 0 1
47521 0x1D60 Flex Curve D 7.00 X PU 0 65535 1 ms F1 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-89


339 MODBUS MEMORY MAP CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
47522 0x1D61 Flex Curve D 7.50 X PU 0 65535 1 ms F1 0 1
47523 0x1D62 Flex Curve D 8.00 X PU 0 65535 1 ms F1 0 1
47524 0x1D63 Flex Curve D 8.50 X PU 0 65535 1 ms F1 0 1
47525 0x1D64 Flex Curve D 9.00 X PU 0 65535 1 ms F1 0 1
47526 0x1D65 Flex Curve D 9.50 X PU 0 65535 1 ms F1 0 1
47527 0x1D66 Flex Curve D 10.00 X PU 0 65535 1 ms F1 0 1
47528 0x1D67 Flex Curve D 10.50 X PU 0 65535 1 ms F1 0 1
47529 0x1D68 Flex Curve D 11.00 X PU 0 65535 1 ms F1 0 1
47530 0x1D69 Flex Curve D 11.50 X PU 0 65535 1 ms F1 0 1
47531 0x1D6A Flex Curve D 12.00 X PU 0 65535 1 ms F1 0 1
47532 0x1D6B Flex Curve D 12.50 X PU 0 65535 1 ms F1 0 1
47533 0x1D6C Flex Curve D 13.00 X PU 0 65535 1 ms F1 0 1
47534 0x1D6D Flex Curve D 13.50 X PU 0 65535 1 ms F1 0 1
47535 0x1D6E Flex Curve D 14.00 X PU 0 65535 1 ms F1 0 1
47536 0x1D6F Flex Curve D 14.50 X PU 0 65535 1 ms F1 0 1
47537 0x1D70 Flex Curve D 15.00 X PU 0 65535 1 ms F1 0 1
47538 0x1D71 Flex Curve D 15.50 X PU 0 65535 1 ms F1 0 1
47539 0x1D72 Flex Curve D 16.00 X PU 0 65535 1 ms F1 0 1
47540 0x1D73 Flex Curve D 16.50 X PU 0 65535 1 ms F1 0 1
47541 0x1D74 Flex Curve D 17.00 X PU 0 65535 1 ms F1 0 1
47542 0x1D75 Flex Curve D 17.50 X PU 0 65535 1 ms F1 0 1
47543 0x1D76 Flex Curve D 18.00 X PU 0 65535 1 ms F1 0 1
47544 0x1D77 Flex Curve D 18.50 X PU 0 65535 1 ms F1 0 1
47545 0x1D78 Flex Curve D 19.00 X PU 0 65535 1 ms F1 0 1
47546 0x1D79 Flex Curve D 19.50 X PU 0 65535 1 ms F1 0 1
47547 0x1D7A Flex Curve D 20.00 X PU 0 65535 1 ms F1 0 1

10-90 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

339 Format Codes


In some cases names of settings displayed in the HMI have been shortened. The Long
Definition column below contains the full name used in the Enervista Setup software, when
applicable. In many cases the long description is the same as the description.

Code Type Definition Long Definition


F1 unsigned 16 bits Unsigned Value
Example: 1234 stored as 1234
F1B unsigned 16 bits Unsigned Value Max Value = OFF
Example: 1234 stored as 1234
F1C unsigned 16 bits Unsigned Value Min Value = OFF
Example: 1234 stored as 1234
F2 unsigned 16 bits Unsigned Value 1 Decimal Place
Example: 123.4 stored as 1234
F2B unsigned 16 bits Unsigned Value 1 Decimal Place
Example: 123.4 stored as 1234
F3 unsigned 16 bits Unsigned Value 2 Decimal Places
Example: 12.34 stored as 1234
F3B unsigned 16 bits Unsigned Value 2 Decimal Places
Example: 12.34 stored as 1234
F4 signed 16 bits 2's Complement Signed Value
Example: -1234 stored as -1234 i.e. 64302
F4B signed 16 bits 2's Complement Signed Value Max Value
= OFF
Example: -1234 stored as -1234 i.e. 64302
F5 signed 16 bits 2's Complement Signed Value 1 Decimal
Place
Example: -123.4 stored as -1234 i.e. 64302
F6 signed 16 bits 2's Complement Signed Value 2 Decimal
Places
Example: -12.34 stored as -1234 i.e. 64302
F7 signed 16 bits 2's Complement Signed Value 3 Decimal
Places
Example: -1.234 stored as -1234 i.e. 64302
F8 signed 16 bits 2's Complement Signed Value 4 Decimal
Places
Example: -0.1234 stored as -1234 i.e. 64302
F9 unsigned 32 bits Unsigned Long Value
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: 123456 stored as 123456
i.e. 1st word: 0001 hex 2nd word: E240 hex
F10 unsigned 32 bits Unsigned Long Value 1 Decimal Place
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: 12345.6 stored as 123456
i.e. 1st word: 0001 hex 2nd word: E240 hex

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-91


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


F11 unsigned 32 bits Unsigned Long Value 1 Decimal Place
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: 1234.56 stored as 123456
i.e. 1st word: 0001 hex 2nd word: E240 hex
F12 signed 32 bits 2's Complement Signed Long Value
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: -123456 stored as -123456
i.e. 1st word: FFFE hex 2nd word: 1DC0 hex
F13 signed 32 bits 2's Complement Signed Long Value 1
Decimal Place
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: -12345.6 stored as -123456
i.e. 1st word: FFFE hex 2nd word: 1DC0 hex
F14 signed 32 bits 2's Complement Signed Long Value 2
Decimal Places
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: -1234.56 stored as -123456
i.e. 1st word: FFFE hex 2nd word: 1DC0 hex
F14A signed 32 bits 2's Complement Signed Long Value 3
Decimal Places
F15 unsigned 16 bits Hardware Revision
0 Prototype Prototype
1 A A
2 B B
3 C C
4 D D
5 E E
6 F F
7 G G
8 H H
9 I I
10 J J
11 K K
12 L L
13 M M
14 N N
15 O O
16 P P
17 Q Q
18 R R
19 S S
20 T T
21 U U
22 V V

10-92 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


23 W W
24 X X
25 Y Y
26 Z Z
F16 signed 16 bits 2's Complement Signed Value 1 Decimal
Place
F17 unsigned 32 bits Unsigned Long Value 3 Decimal Places
F17A unsigned 16 bits Unsigned Value 3 Decimal Places
F18 unsigned 32 bits Date MM/DD/YYYY
1st byte Month 1 to 12
2nd byte Day 1 to 31
3rd and 4th byte Year 2000 to 2099 2000 stored as 34867152 (i.e. 1st word: 0214 2nd word 07D0)
Example: Feb 20
F19 unsigned 32 bits Time HH:MM:SS.sss
1st byte Hours 0 to 23
2nd byte Minutes 0 to 59
3rd and 4th byte miliSeconds 0 to 59999
Example: 2:05pm stored as 235208704 (i.e. 1st word: 0E05 2nd word 0000)
F20 signed 32 bits 2's Complement Signed Long Value
F21 signed 16 bits 2's Complement Signed Value 2 Decimal
Places (Power Factor)
F22 unsigned 16 bits Two 8-BIT Characters Packed Into 16-BIT
Unsigned
F23 unsigned 16 bits Unsigned Value 3 Decimal Places
F24 unsigned 16 bits Unsigned Value AS Seconds SHOW AS
Duration Max Value = OFF
F24B unsigned 16 bits Unsigned Value AS Seconds SHOW AS
Duration
F25 unsigned 16 bits Trace Memory Channel Data
0 Leading Leading
1 Lagging Lagging
F26 unsigned 16 bits 350 Trace Memory Channel Data
F26A unsigned 16 bits 339 Trace Memory Channel Data
0 Va Va
1 Vb Vb
2 Vc Vc
3 ICBCT ICBCT
4 Not Used Not Used
5 Not Used Not Used
6 Ia Ia
7 Ib Ib
8 Ic Ic
9 Ig Ig
10 Inputs 1-16 Inputs 1-16
11 Outputs 1-16 Outputs 1-16
12 Virtual Inputs1-16 Virtual Inputs 1-16
13 Virtual Inputs7-32 Virtual Inputs 17-32
14 Remote INs 1-16 Remote Inputs 1-16

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-93


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


15 Remote INs 17-32 Remote Inputs 17-32
16 Logic Elements Logic Elements
F26B unsigned 16 bits 345 Trace Memory Channel Data
F27 unsigned 32 bits Unsigned Long Value 4 Decimal Places
F36 unsigned 16 bits OC Curve Selection
0 Extremely Inverse Extremely Inverse
1 Very Inverse Very Inverse
2 Normally Inverse Normally Inverse
3 Moderately Inverse Moderately Inverse
4 Definite Time Definite Time
5 IEC Curve A IEC Curve A
6 IEC Curve B IEC Curve B
7 IEC Curve C IEC Curve C
10 IAC Extr. Inverse IAC Extremely Inverse
11 IAC Very Inverse IAC Very Inverse
12 IAC Inverse IAC Inverse
13 IAC Short Inverse IAC Short Inverse
14 IEC Short Inverse IEC Short Inverse
F37 unsigned 16 bits OC Pickup flags
1 Phase A Phase A
2 Phase B Phase B
4 Phase C Phase C
7 All Phases All Phases
F38 unsigned 16 bits OC Direction pickup flags
0x10 Direction PKP Ph A Direction PKP Phase A
0x20 Direction PKP Ph B Direction PKP Phase B
0x40 Direction PKP Ph C Direction PKP Phase C
0x80 Direction Pickup Direction Pickup
0xF0 Direction Direction
F48 unsigned 16 bits Simulation Status
0 Disabled Disabled
1 Prefault State Prefault State
2 Fault State Fault State
3 Postfault State Postfault State
F68 unsigned 16 bits Reset Time Model
0 Instantaneous Instantaneous
1 Linear Linear
F74 unsigned 16 bits Data Logger Sample Rate
0 1 Cycle 1 Cycle
1 1 Second 1 Second
2 1 Minute 1 Minute
3 1 Hour 1 Hour
F75 unsigned 16 bits Data Logger Status
0 Stopped Stopped
1 Started Started
2 Triggered Triggered
3 Pretrigger Pretrigger

10-94 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


4 PostTrigger PostTrigger
F76 unsigned 16 bits Overcurrent Direction
0 Disabled Disabled
1 Forward Forward
2 Reverse Reverse
F77 unsigned 16 bits Data Logger Channel Data
0 Disabled Disabled
1 Phase A Current Phase A Current
2 Phase B Current Phase B Current
3 Phase C Current Phase C Current
4 Avg Phase Current Average Phase Current
5 Motor Load Motor Load
6 Current Unbalance Current Unbalance
7 Gnd Current Gnd Current
8 System Frequency System Frequency
9 Vab Vab
10 Vbc Vbc
11 Vca Vca
12 Van Van
13 Vbn Vbn
14 Vcn Vcn
15 Power Factor Power Factor
16 Real Power Real Power
17 Reactive Pwr Reactive Power
18 Apparent Pwr Apparent Power
19 Positive Watthours Positive Watthours
20 Positive Varhours Positive Varhours
21 Hottest Stator RTD Hottest Stator RTD
22 Therm Cap. Used Thermal Capacity Used
23 RTD #1 RTD #1
24 RTD #2 RTD #2
25 RTD #3 RTD #3
26 RTD #4 RTD #4
27 RTD #5 RTD #5
28 RTD #6 RTD #6
29 Breaker Status Breaker Status
30 RTD #7 RTD #7
31 RTD #8 RTD #8
32 RTD #9 RTD #9
33 RTD #10 RTD #10
34 RTD #11 RTD #11
35 RTD #12 RTD #12
F77B unsigned 16 bits 345 Data Logger Channel Data
F78 unsigned 16 bits DNP Object 20 Default Variation
1 1 (1) 32-Bit Binary Counter
2 2 (2) 16-Bit Binary Counter
5 5 (5) 32-Bit Binary Counter w/o Flag

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-95


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


6 6 (6) 16-Bit Binary Counter w/o Flag
F79 unsigned 16 bits DNP Object 21 Default Variation
1 1 (1) 32-Bit Frozen Counter
2 2 (2) 16-Bit Frozen Counter
9 9 (9) 32-Bit Frozen Counter w/o Flag
10 10 (10) 16-Bit Frozen Counter w/o Flag
F80 unsigned 16 bits DNP Object 22 Default Variation
1 1 (1) 32-Bit Counter Change Event
2 2 (2) 16-Bit Counter Change Event
5 5 (5) 32-Bit Counter Change Event w Time
6 6 (6) 16-Bit Counter Change Event w Time
F81 unsigned 16 bits DNP Object 23 Default Variation
1 1 (1) 32-Bit Frozen Counter Event
2 2 (2) 16-Bit Frozen Counter Event
5 5 (5) 32-Bit Frozen Counter Event w Time
6 6 (6) 16-Bit Frozen Counter Event w Time
F82 unsigned 16 bits DNP Object 30 Default Variation
1 1 (1) 32-Bit Analog Input
2 2 (2) 16-Bit Analog Input
3 3 (3) 32-Bit Analog Input w/o Flag
4 4 (4) 16-Bit Analog Input w/o Flag
F83 unsigned 16 bits DNP Object 32 Default Variation
1 1 (1) 32-Bit Analog Change Event w/o Time
2 2 (2) 16-Bit Analog Change Event w/o Time
3 3 (3) 32-Bit Analog Change Event w Time
4 4 (4) 16-Bit Analog Change Event w Time
F85 unsigned 16 bits DNP Analog Input Point Scale Factor
1 / 0.001 / 0.001
2 / 0.01 / 0.01
3 / 0.1 / 0.1
4 /1 /1
5 / 10 / 10
6 / 100 / 100
7 / 1000 / 1000
8 / 10000 / 10000
9 / 100000 / 100000
F86 unsigned 16 bits DNP and 103 Binary Output Points
0 Off Off
1 Virtual Input 1 Virtual Input 1
2 Virtual Input 2 Virtual Input 2
3 Virtual Input 3 Virtual Input 3
4 Virtual Input 4 Virtual Input 4
5 Virtual Input 5 Virtual Input 5
6 Virtual Input 6 Virtual Input 6
7 Virtual Input 7 Virtual Input 7
8 Virtual Input 8 Virtual Input 8
9 Virtual Input 9 Virtual Input 9

10-96 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


10 Virtual Input 10 Virtual Input 10
11 Virtual Input 11 Virtual Input 11
12 Virtual Input 12 Virtual Input 12
13 Virtual Input 13 Virtual Input 13
14 Virtual Input 14 Virtual Input 14
15 Virtual Input 15 Virtual Input 15
16 Virtual Input 16 Virtual Input 16
17 Virtual Input 17 Virtual Input 17
18 Virtual Input 18 Virtual Input 18
19 Virtual Input 19 Virtual Input 19
20 Virtual Input 20 Virtual Input 20
21 Virtual Input 21 Virtual Input 21
22 Virtual Input 22 Virtual Input 22
23 Virtual Input 23 Virtual Input 23
24 Virtual Input 24 Virtual Input 24
25 Virtual Input 25 Virtual Input 25
26 Virtual Input 26 Virtual Input 26
27 Virtual Input 27 Virtual Input 27
28 Virtual Input 28 Virtual Input 28
29 Virtual Input 29 Virtual Input 29
30 Virtual Input 30 Virtual Input 30
31 Virtual Input 31 Virtual Input 31
32 Virtual Input 32 Virtual Input 32
33 FC: Reset Force Coil: Reset
34 FC: Open Breaker Force Coil: Open Breaker
35 FC: Close Breaker Force Coil: Close Breaker
36 FC: Display Msg Force Coil: Display Message
37 FC: Clear Curr Dmd1 Force Coil: Clear Current Dmd1
39 FC: Clear Pwr Dmd Force Coil: Clear Power Dmd
40 FC:Clear Fault Rep FC:Clear Fault Rep
F87 unsigned 16 bits DNP/Ethernet Channel Port
0 None None
1 TCP TCP
2 UDP UDP
F88 unsigned 16 bits Analog Values
0 Disabled Disabled
1 Phase A Current Phase A Current
2 Phase B Current Phase B Current
3 Phase C Current Phase C Current
4 Avg Phase Current Average Phase Current
7 Gnd Current Gnd Current
8 System Frequency System Frequency
9 Vab Vab
10 Vbc Vbc
11 Vca Vca
12 Van Van
13 Vbn Vbn

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-97


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


14 Vcn Vcn
15 Power Factor Power Factor
16 Real Power Real Power
17 Reactive Pwr Reactive Power
18 Apparent Pwr Apparent Power
19 Positive Watthours Positive Watthours
20 Positive Varhours Positive Varhours
21 Negative Watthours Negative Watthours
22 Negative Varhours Negative Varhours
26 Ntrl Current Ntrl Current
27 Ntrl Voltage Ntrl Voltage
46 NSeq Voltage Negative Sequence Voltage
47 Avg Phase Voltage Avg Phase Voltage
48 Avg Line Voltage Avg Line Voltage
55 Dir Power 1 Directional Power 1
56 Dir Power 2 Directional Power 2
60 FR Date (Upper 16) Fault Report Date (Upper 16)
61 FR Date (Lower 16) Fault Report Date (Lower 16)
62 FR Time (Upper 16) Fault Report Time (Upper 16)
63 FR Time (Lower 16) Fault Report Time (Lower 16)
64 FR Fault Type Fault Report Fault Type
65 FR Ia Fault Report Ia
66 FR Ia Angle Fault Report Ia Angle
67 FR Ib Fault Report Ib
68 FR Ib Angle Fault Report Ib Angle
69 FR Ic Fault Report Ic
70 FR Ic Angle Fault Report Ic Angle
71 FR Ig Fault Report Ig
72 FR Ig Angle Fault Report Ig Angle
73 FR In Fault Report In
74 FR In Angle Fault Report In Angle
75 FR Va Fault Report Va
76 FR Va Angle Fault Report Va Angle
77 FR Vb Fault Report Vb
78 FR Vb Angle Fault Report Vb Angle
79 FR Vc Fault Report Vc
80 FR Vc Angle Fault Report Vc Angle
81 FR Vab Fault Report Vab
82 FR Vab Angle Fault Report Vab Angle
83 FR Vbc Fault Report Vbc
84 FR Vbc Angle Fault Report Vbc Angle
85 FR Vca Fault Report Vca
86 FR Vca Angle Fault Report Vca Angle
87 FR Vn Fault Report Vn
88 FR Vn Angle Fault Report Vn Angle
89 FR Vaux Fault Report Vaux
90 FR Vaux Angle Fault Report Vaux Angle

10-98 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


91 FR System Freq Fault Report System Frequency
114 FR Phases Fault Report Phases
115 Current Dmd 1 PhA Current Demand 1 PhA
116 Current Dmd 1 PhB Current Demand 1 PhB
117 Current Dmd 1 PhC Current Demand 1 PhC
118 Max Curr Dmd1 PhA Max Current Demand 1 PhA
119 Max Curr Dmd1 PhB Max Current Demand 1 PhB
120 Max Curr Dmd1 PhC Max Current Demand 1 PhC
127 Real Pwr Dmd Real Power Demand
128 React Pwr Dmd Reactive Power Demand
129 App Pwr Dmd Apparent Power Demand
130 Max Real Pwr Dmd Max Real Power Demand
131 Max React Pwr Dmd Max Reactive Power Demand
132 Max App Pwr Dmd Max Apparent Power Demand
133 Total Num of Trips Total Num of Trips
134 Num Emerg Restarts Number Of Emergency Restarts
135 Num Motor Starts Number of Motor Starts
136 Motor Run Hours Motor Running Hours
137 Start Timer 1 Start Timer 1
138 Start Timer 2 Start Timer 2
139 Start Timer 3 Start Timer 3
140 Start Timer 4 Start Timer 4
141 Start Timer 5 Start Timer 5
142 Motor Stop Hours Motor Stopped Hours
143 Overload Lockout Overload Lockout
144 Starts/Hr Lockout Starts/Hour Lockout
145 Time Betw Starts Time Between Starts
146 Restart Inhibit Restart Inhibit
147 Thrm Inhib Timer Thermal Start Inhibit Timer
148 Motor Lockout Time Motor Lockout Time
149 Thermal Cap Used Thermal Cap Used
150 Time to Trip Time to Overload Trip
151 Time To Reset Time To Reset
152 CBCT CBCT
153 Motor Load Motor Load
154 Curr Unbalance Current Unbalance
155 PhA Curr Angle PhA Current Angle
156 PhB Curr Angle PhB Current Angle
157 PhC Curr Angle PhC Current Angle
158 Van Angle Van Angle
159 Vbn Angle Vbn Angle
160 Vcn Angle Vcn Angle
161 Ig Angle Ig Angle
162 In Angle In Angle
163 Ntrl Voltage Angle Neutral Voltage Angle
165 Vab Angle Vab Angle
166 Vbc Angle Vbc Angle

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-99


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


167 Vca Angle Vca Angle
168 Biased Motor Load Biased Motor Load
171 Voltage Unbalance Voltage Unbalance
172 RTD 7 Temp RTD 7 Temp
173 RTD 8 Temp RTD 8 Temp
174 RTD 9 Temp RTD 9 Temp
175 RTD 10 Temp RTD 10 Temp
176 RTD 11 Temp RTD 11 Temp
177 RTD 12 Temp RTD 12 Temp
178 Internal Temp Internal Temp
179 Hottest Stator RTD Hottest Stator RTD
180 Hottst St RTD Temp Hottest Stator RTD Temperature
181 RTD 1 Temp RTD 1 Temp
182 RTD 2 Temp RTD 2 Temp
183 RTD 3 Temp RTD 3 Temp
184 RTD 4 Temp RTD 4 Temp
185 RTD 5 Temp RTD 5 Temp
186 RTD 6 Temp RTD 6 Temp
187 Ambient Temp Ambient Temperature
188 Internal Temp Max Internal Temperature Max
193 Neg Seq V Angle Negative Sequence V Angle
195 Learned Acc Time Learned Acceleration Time
196 Learned Start Curr Learned Starting Current
197 Learned Start Cap Learned Starting Capacity
198 Last Acc Time Last Acceleration Time
199 Last Start Curr Last Starting Current
200 Last Start TCU Last Start TCU
201 Learned Avg Load Learned Average Load
202 RunTime in Days Learned Run Time After Start (days)
203 RunTime in Mins Learned Run Time After Start (minutes)
204 I^2 Counter I^2 Counter
205 Avg Motor Load Average Motor Load Learned
237 BKR Health Breaker Health
238 BKR Last Trip Time Breaker Last Trip Time
239 BKR Avg Trip Time Breaker Average Trip Time
240 BKR Last Close Time Breaker Last Close Time
241 BKR Avg Close Time Breaker Average Close Time
242 BKR Last Charge Time Breaker Last Charge Time
243 BKR Avg Charge Time Breaker Average Charge Time
F89 unsigned 16 bits Autoreclose Block
0 Off Off
1 On On
0x40 Contact Input 1 Contact Input 1
0x41 Contact Input 2 Contact Input 2
0x42 Contact Input 3 Contact Input 3
0x43 Contact Input 4 Contact Input 4
0x44 Contact Input 5 Contact Input 5

10-100 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x45 Contact Input 6 Contact Input 6
0x46 Contact Input 7 Contact Input 7
0x47 Contact Input 8 Contact Input 8
0x48 Contact Input 9 Contact Input 9
0x49 Contact Input 10 Contact Input 10
0x80 Virtual Input 1 Virtual Input 1
0x81 Virtual Input 2 Virtual Input 2
0x82 Virtual Input 3 Virtual Input 3
0x83 Virtual Input 4 Virtual Input 4
0x84 Virtual Input 5 Virtual Input 5
0x85 Virtual Input 6 Virtual Input 6
0x86 Virtual Input 7 Virtual Input 7
0x87 Virtual Input 8 Virtual Input 8
0x88 Virtual Input 9 Virtual Input 9
0x89 Virtual Input 10 Virtual Input 10
0x8A Virtual Input 11 Virtual Input 11
0x8B Virtual Input 12 Virtual Input 12
0x8C Virtual Input 13 Virtual Input 13
0x8D Virtual Input 14 Virtual Input 14
0x8E Virtual Input 15 Virtual Input 15
0x8F Virtual Input 16 Virtual Input 16
0x90 Virtual Input 17 Virtual Input 17
0x91 Virtual Input 18 Virtual Input 18
0x92 Virtual Input 19 Virtual Input 19
0x93 Virtual Input 20 Virtual Input 20
0x94 Virtual Input 21 Virtual Input 21
0x95 Virtual Input 22 Virtual Input 22
0x96 Virtual Input 23 Virtual Input 23
0x97 Virtual Input 24 Virtual Input 24
0x98 Virtual Input 25 Virtual Input 25
0x99 Virtual Input 26 Virtual Input 26
0x9A Virtual Input 27 Virtual Input 27
0x9B Virtual Input 28 Virtual Input 28
0x9C Virtual Input 29 Virtual Input 29
0x9D Virtual Input 30 Virtual Input 30
0x9E Virtual Input 31 Virtual Input 31
0x9F Virtual Input 32 Virtual Input 32
0xC0 Logic Element 1 Logic Element 1
0xC1 Logic Element 2 Logic Element 2
0xC2 Logic Element 3 Logic Element 3
0xC3 Logic Element 4 Logic Element 4
0xC4 Logic Element 5 Logic Element 5
0xC5 Logic Element 6 Logic Element 6
0xC6 Logic Element 7 Logic Element 7
0xC7 Logic Element 8 Logic Element 8
0xC8 Logic Element 9 Logic Element 9
0xC9 Logic Element 10 Logic Element 10

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-101


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xCA Logic Element 11 Logic Element 11
0xCB Logic Element 12 Logic Element 12
0xCC Logic Element 13 Logic Element 13
0xCD Logic Element 14 Logic Element 14
0xCE Logic Element 15 Logic Element 15
0xCF Logic Element 16 Logic Element 16
0x1C0 Remote Input 1 Remote Input 1
0x1C1 Remote Input 2 Remote Input 2
0x1C2 Remote Input 3 Remote Input 3
0x1C3 Remote Input 4 Remote Input 4
0x1C4 Remote Input 5 Remote Input 5
0x1C5 Remote Input 6 Remote Input 6
0x1C6 Remote Input 7 Remote Input 7
0x1C7 Remote Input 8 Remote Input 8
0x1C8 Remote Input 9 Remote Input 9
0x1C9 Remote Input 10 Remote Input 10
0x1CA Remote Input 11 Remote Input 11
0x1CB Remote Input 12 Remote Input 12
0x1CC Remote Input 13 Remote Input 13
0x1CD Remote Input 14 Remote Input 14
0x1CE Remote Input 15 Remote Input 15
0x1CF Remote Input 16 Remote Input 16
0x1D0 Remote Input 17 Remote Input 17
0x1D1 Remote Input 18 Remote Input 18
0x1D2 Remote Input 19 Remote Input 19
0x1D3 Remote Input 20 Remote Input 20
0x1D4 Remote Input 21 Remote Input 21
0x1D5 Remote Input 22 Remote Input 22
0x1D6 Remote Input 23 Remote Input 23
0x1D7 Remote Input 24 Remote Input 24
0x1D8 Remote Input 25 Remote Input 25
0x1D9 Remote Input 26 Remote Input 26
0x1DA Remote Input 27 Remote Input 27
0x1DB Remote Input 28 Remote Input 28
0x1DC Remote Input 29 Remote Input 29
0x1DD Remote Input 30 Remote Input 30
0x1DE Remote Input 31 Remote Input 31
0x1DF Remote Input 32 Remote Input 32
0xA9C1 CT Fail Alarm PKP CT Fail Alarm PKP
0xA9C2 CT Fail Alarm OP CT Fail Alarm OP
F89A unsigned 16 bits BKR Health Charge Input
0 Off Off
0x40 Contact Input 1 Contact Input 1
0x41 Contact Input 2 Contact Input 2
0x42 Contact Input 3 Contact Input 3
0x43 Contact Input 4 Contact Input 4
0x44 Contact Input 5 Contact Input 5

10-102 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x45 Contact Input 6 Contact Input 6
0x46 Contact Input 7 Contact Input 7
0x47 Contact Input 8 Contact Input 8
0x48 Contact Input 9 Contact Input 9
0x49 Contact Input 10 Contact Input 10
0x80 Virtual Input 1 Virtual Input 1
0x81 Virtual Input 2 Virtual Input 2
0x82 Virtual Input 3 Virtual Input 3
0x83 Virtual Input 4 Virtual Input 4
0x84 Virtual Input 5 Virtual Input 5
0x85 Virtual Input 6 Virtual Input 6
0x86 Virtual Input 7 Virtual Input 7
0x87 Virtual Input 8 Virtual Input 8
0x88 Virtual Input 9 Virtual Input 9
0x89 Virtual Input 10 Virtual Input 10
0x8A Virtual Input 11 Virtual Input 11
0x8B Virtual Input 12 Virtual Input 12
0x8C Virtual Input 13 Virtual Input 13
0x8D Virtual Input 14 Virtual Input 14
0x8E Virtual Input 15 Virtual Input 15
0x8F Virtual Input 16 Virtual Input 16
0x90 Virtual Input 17 Virtual Input 17
0x91 Virtual Input 18 Virtual Input 18
0x92 Virtual Input 19 Virtual Input 19
0x93 Virtual Input 20 Virtual Input 20
0x94 Virtual Input 21 Virtual Input 21
0x95 Virtual Input 22 Virtual Input 22
0x96 Virtual Input 23 Virtual Input 23
0x97 Virtual Input 24 Virtual Input 24
0x98 Virtual Input 25 Virtual Input 25
0x99 Virtual Input 26 Virtual Input 26
0x9A Virtual Input 27 Virtual Input 27
0x9B Virtual Input 28 Virtual Input 28
0x9C Virtual Input 29 Virtual Input 29
0x9D Virtual Input 30 Virtual Input 30
0x9E Virtual Input 31 Virtual Input 31
0x9F Virtual Input 32 Virtual Input 32
0xC0 Logic Element 1 Logic Element 1
0xC1 Logic Element 2 Logic Element 2
0xC2 Logic Element 3 Logic Element 3
0xC3 Logic Element 4 Logic Element 4
0xC4 Logic Element 5 Logic Element 5
0xC5 Logic Element 6 Logic Element 6
0xC6 Logic Element 7 Logic Element 7
0xC7 Logic Element 8 Logic Element 8
0xC8 Logic Element 9 Logic Element 9
0xC9 Logic Element 10 Logic Element 10

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-103


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xCA Logic Element 11 Logic Element 11
0xCB Logic Element 12 Logic Element 12
0xCC Logic Element 13 Logic Element 13
0xCD Logic Element 14 Logic Element 14
0xCE Logic Element 15 Logic Element 15
0xCF Logic Element 16 Logic Element 16
0x1C0 Remote Input 1 Remote Input 1
0x1C1 Remote Input 2 Remote Input 2
0x1C2 Remote Input 3 Remote Input 3
0x1C3 Remote Input 4 Remote Input 4
0x1C4 Remote Input 5 Remote Input 5
0x1C5 Remote Input 6 Remote Input 6
0x1C6 Remote Input 7 Remote Input 7
0x1C7 Remote Input 8 Remote Input 8
0x1C8 Remote Input 9 Remote Input 9
0x1C9 Remote Input 10 Remote Input 10
0x1CA Remote Input 11 Remote Input 11
0x1CB Remote Input 12 Remote Input 12
0x1CC Remote Input 13 Remote Input 13
0x1CD Remote Input 14 Remote Input 14
0x1CE Remote Input 15 Remote Input 15
0x1CF Remote Input 16 Remote Input 16
0x1D0 Remote Input 17 Remote Input 17
0x1D1 Remote Input 18 Remote Input 18
0x1D2 Remote Input 19 Remote Input 19
0x1D3 Remote Input 20 Remote Input 20
0x1D4 Remote Input 21 Remote Input 21
0x1D5 Remote Input 22 Remote Input 22
0x1D6 Remote Input 23 Remote Input 23
0x1D7 Remote Input 24 Remote Input 24
0x1D8 Remote Input 25 Remote Input 25
0x1D9 Remote Input 26 Remote Input 26
0x1DA Remote Input 27 Remote Input 27
0x1DB Remote Input 28 Remote Input 28
0x1DC Remote Input 29 Remote Input 29
0x1DD Remote Input 30 Remote Input 30
0x1DE Remote Input 31 Remote Input 31
0x1DF Remote Input 32 Remote Input 32
0xA9C1 CT Fail Alarm PKP CT Fail Alarm PKP
0xA9C2 CT Fail Alarm OP CT Fail Alarm OP
F89B unsigned 16 bits Start Thermal Protection
0 Off Off
1 On On
0x40 Contact Input 1 Contact Input 1
0x41 Contact Input 2 Contact Input 2
0x42 Contact Input 3 Contact Input 3
0x43 Contact Input 4 Contact Input 4

10-104 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x44 Contact Input 5 Contact Input 5
0x45 Contact Input 6 Contact Input 6
0x46 Contact Input 7 Contact Input 7
0x47 Contact Input 8 Contact Input 8
0x48 Contact Input 9 Contact Input 9
0x49 Contact Input 10 Contact Input 10
0x80 Virtual Input 1 Virtual Input 1
0x81 Virtual Input 2 Virtual Input 2
0x82 Virtual Input 3 Virtual Input 3
0x83 Virtual Input 4 Virtual Input 4
0x84 Virtual Input 5 Virtual Input 5
0x85 Virtual Input 6 Virtual Input 6
0x86 Virtual Input 7 Virtual Input 7
0x87 Virtual Input 8 Virtual Input 8
0x88 Virtual Input 9 Virtual Input 9
0x89 Virtual Input 10 Virtual Input 10
0x8A Virtual Input 11 Virtual Input 11
0x8B Virtual Input 12 Virtual Input 12
0x8C Virtual Input 13 Virtual Input 13
0x8D Virtual Input 14 Virtual Input 14
0x8E Virtual Input 15 Virtual Input 15
0x8F Virtual Input 16 Virtual Input 16
0x90 Virtual Input 17 Virtual Input 17
0x91 Virtual Input 18 Virtual Input 18
0x92 Virtual Input 19 Virtual Input 19
0x93 Virtual Input 20 Virtual Input 20
0x94 Virtual Input 21 Virtual Input 21
0x95 Virtual Input 22 Virtual Input 22
0x96 Virtual Input 23 Virtual Input 23
0x97 Virtual Input 24 Virtual Input 24
0x98 Virtual Input 25 Virtual Input 25
0x99 Virtual Input 26 Virtual Input 26
0x9A Virtual Input 27 Virtual Input 27
0x9B Virtual Input 28 Virtual Input 28
0x9C Virtual Input 29 Virtual Input 29
0x9D Virtual Input 30 Virtual Input 30
0x9E Virtual Input 31 Virtual Input 31
0x9F Virtual Input 32 Virtual Input 32
0xC0 Logic Element 1 Logic Element 1
0xC1 Logic Element 2 Logic Element 2
0xC2 Logic Element 3 Logic Element 3
0xC3 Logic Element 4 Logic Element 4
0xC4 Logic Element 5 Logic Element 5
0xC5 Logic Element 6 Logic Element 6
0xC6 Logic Element 7 Logic Element 7
0xC7 Logic Element 8 Logic Element 8
0xC8 Logic Element 9 Logic Element 9

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-105


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xC9 Logic Element 10 Logic Element 10
0xCA Logic Element 11 Logic Element 11
0xCB Logic Element 12 Logic Element 12
0xCC Logic Element 13 Logic Element 13
0xCD Logic Element 14 Logic Element 14
0xCE Logic Element 15 Logic Element 15
0xCF Logic Element 16 Logic Element 16
0x1C0 Remote Input 1 Remote Input 1
0x1C1 Remote Input 2 Remote Input 2
0x1C2 Remote Input 3 Remote Input 3
0x1C3 Remote Input 4 Remote Input 4
0x1C4 Remote Input 5 Remote Input 5
0x1C5 Remote Input 6 Remote Input 6
0x1C6 Remote Input 7 Remote Input 7
0x1C7 Remote Input 8 Remote Input 8
0x1C8 Remote Input 9 Remote Input 9
0x1C9 Remote Input 10 Remote Input 10
0x1CA Remote Input 11 Remote Input 11
0x1CB Remote Input 12 Remote Input 12
0x1CC Remote Input 13 Remote Input 13
0x1CD Remote Input 14 Remote Input 14
0x1CE Remote Input 15 Remote Input 15
0x1CF Remote Input 16 Remote Input 16
0x1D0 Remote Input 17 Remote Input 17
0x1D1 Remote Input 18 Remote Input 18
0x1D2 Remote Input 19 Remote Input 19
0x1D3 Remote Input 20 Remote Input 20
0x1D4 Remote Input 21 Remote Input 21
0x1D5 Remote Input 22 Remote Input 22
0x1D6 Remote Input 23 Remote Input 23
0x1D7 Remote Input 24 Remote Input 24
0x1D8 Remote Input 25 Remote Input 25
0x1D9 Remote Input 26 Remote Input 26
0x1DA Remote Input 27 Remote Input 27
0x1DB Remote Input 28 Remote Input 28
0x1DC Remote Input 29 Remote Input 29
0x1DD Remote Input 30 Remote Input 30
0x1DE Remote Input 31 Remote Input 31
0x1DF Remote Input 32 Remote Input 32
F90 unsigned 16 bits Operate / Do Not Operate
0 Do Not Operate Do Not Operate
1 Operate Operate
F91 signed 16 bits Edit Group
F92 unsigned 16 bits Phases
1 Any One Any One
2 Any Two Any Two
3 All Three All Three

10-106 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


F92A unsigned 16 bits Phases + Average
F93 unsigned 16 bits Phase UV Curve
0 Definite Time Definite Time
1 Inverse Time Inverse Time
F94 unsigned 16 bits Breaker Control
0 Disabled Disabled
1 Contact Input 1 Contact Input 1
2 Contact Input 2 Contact Input 2
3 Contact Input 3 Contact Input 3
4 Contact Input 4 Contact Input 4
5 Contact Input 5 Contact Input 5
6 Contact Input 6 Contact Input 6
7 Contact Input 7 Contact Input 7
8 Contact Input 8 Contact Input 8
9 Contact Input 9 Contact Input 9
10 Contact Input 10 Contact Input 10
F95 unsigned 16 bits Transient Recorder Buffer
0 1 1
1 3 3
2 6 6
F96 unsigned 16 bits Directional Polarizing
1 Voltage Voltage
2 Current Current
3 Dual Dual
F97 unsigned 16 bits Rear 485 Port Protocol
0 Modbus Modbus
1 IEC60870-5-103 IEC60870-5-103
2 DNP 3.0 DNP 3.0
F98 unsigned 16 bits Simulated Key Press
0 No Key Press No Key Press
1 Nav Up Key Nav Up Key
2 Nav Left Key Nav Left Key
3 Nav Down Key Navigation Down Key
4 Nav Right Key Navigation Right Key
5 Up Key Up Key
6 Down Key Down Key
7 Enter Key Enter Key
8 Menu Key Menu Key
9 Escape Key Escape Key
10 Reset Key Reset Key
F99 unsigned 16 bits SR 3 Relay Status
0 Not Ready Not Ready
1 Ready Ready
FC100 unsigned 16 bits SNTP Mode
0 Disabled Disabled
1 Unicast Unicast
2 Anycast Anycast

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-107


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


3 Broadcast Broadcast
FC101 unsigned 16 bits RS 485 Baud Rate
0 9600 baud 9600 baud
1 19200 baud 19200 baud
2 38400 baud 38400 baud
3 57600 baud 57600 baud
4 115200 baud 115200 baud
FC102 unsigned 16 bits RS 485 Parity
0 None None
1 Odd Odd
2 Even Even
FC103 unsigned 16 bits Off / On Selection
0 Off Off
1 On On
FC103A unsigned 16 bits No / Yes Selection
0 NO NO
1 YES YES
FC104 unsigned 16 bits Ground CT Type
0 1 A Secondary 1 A Secondary
1 5 A Secondary 5 A Secondary
2 50:00.0 50:00.0
FC105 unsigned 16 bits Differential CT Type
0 None None
1 1 A Secondary 1 A Secondary
2 5 A Secondary 5 A Secondary
3 Direct Connect Direct Connect
FC106 unsigned 16 bits Voltage Transformer Connection Type
0 Wye Wye
1 Delta Delta
FC107 unsigned 16 bits Supply Frequency
0 60 Hz 60 Hz
1 50 Hz 50 Hz
FC108 unsigned 16 bits 61850 Status
0 Not Ready Not Ready
1 Ready Ready
2 Default CID Default CID
FC109 unsigned 16 bits Flex Logic Status
0 OK OK
1 Unknown Token Unknown Token
2 TooMany Latches Too Many Latches
3 TooMany Timers Too Many Timers
4 TooMany + OneShots Too Many + One Shots
5 TooMany - OneShots Too Many - One Shots
6 TooMany Duel1Shots Too Many Duel One Shots
7 Stack Overflow Stack Overflow
8 Stack Underflow Stack Underflow
9 Program Too Long Program Too Long

10-108 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


FC111 unsigned 16 bits Trip Relays
0 Trip Trip
1 Alarm Alarm
FC112 unsigned 16 bits Communication Status
0 Error Error
1 OK OK
FC115 unsigned 16 bits Alarm Type Selection
0 Off Off
1 Trip Trip
2 Alarm Alarm
FC116 unsigned 16 bits Switch Type
0 Open Open
1 Closed Closed
FC117 unsigned 16 bits Directional Voltage
0 Measured (Vx) Measured (Vx)
1 Calculated (VTs) Calculated (VTs)
FC118 unsigned 16 bits WGF Voltage
0 Calculated (Vn) Calculated (Vn)
1 Measured (Vx) Measured (Vx)
FC119 unsigned 16 bits WGF Current
0 Calculated (In) Calculated (In)
1 Measured (Ig) Measured (Ig)
FC120 unsigned 16 bits RTD Type
0 100 Ohm Pt 100 Ohm Platinum
FC121 unsigned 16 bits RTD Application
0 None None
1 Stator Stator
2 Bearing Bearing
3 Ambient Ambient
6 Other Other
FC122 unsigned 16 bits RTD Voting Selection
0 Off Off
1 RTD #1 RTD #1
2 RTD #2 RTD #2
3 RTD #3 RTD #3
4 RTD #4 RTD #4
5 RTD #5 RTD #5
6 RTD #6 RTD #6
7 RTD #7 RTD #7
8 RTD #8 RTD #8
9 RTD #9 RTD #9
10 RTD #10 RTD #10
11 RTD #11 RTD #11
12 RTD #12 RTD #12
FC123 unsigned 16 bits Select DV Voltage
0 17V Threshold 17V Threshold
1 33V Threshold 33V Threshold

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-109


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


2 84V Threshold 84V Threshold
3 166V Threshold 166V Threshold
FC124 unsigned 16 bits Phase Rotation
0 ABC ABC
1 CBA CBA
FC124A unsigned 16 bits Phase Rotation
0 ABC ABC
1 ACB ACB
FC125 unsigned 16 bits Coil Monitor
0 Healthy Healthy
1 Unhealthy Unhealthy
FC126 unsigned 16 bits Disabled / Enabled Selection
0 Disabled Disabled
1 Enabled Enabled
FC127 unsigned 16 bits System Language
0 English English
1 Chinese Chinese
FC128 unsigned 16 bits Command Status
5 None None
FC129 unsigned 16 bits Relay Status
FC130 unsigned 16 bits LED Flash
FC131 unsigned 16 bits Comm Fail Mode
1 Serial Serial
2 Serial & Ethernet Serial & Ethernet
4 Serial & FieldBus Serial & FieldBus
8 Ethernet Ethernet
16 FieldBus FieldBus
32 Ethernet&Fieldbus Ethernet & Fieldbus
64 All All
FC133 unsigned 16 bits Cause of Waveform Trigger
0 None None
1 Command Command
0x00C0 Logic Element 1 Logic Element 1
0x00C1 Logic Element 2 Logic Element 2
0x00C2 Logic Element 3 Logic Element 3
0x00C3 Logic Element 4 Logic Element 4
0x00C4 Logic Element 5 Logic Element 5
0x00C5 Logic Element 6 Logic Element 6
0x00C6 Logic Element 7 Logic Element 7
0x00C7 Logic Element 8 Logic Element 8
0x00C8 Logic Element 9 Logic Element 9
0x00C9 Logic Element 10 Logic Element 10
0x00CA Logic Element 11 Logic Element 11
0x00CB Logic Element 12 Logic Element 12
0x00CC Logic Element 13 Logic Element 13
0x00CD Logic Element 14 Logic Element 14
0x00CE Logic Element 15 Logic Element 15

10-110 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x00CF Logic Element 16 Logic Element 16
0x00D0 VO 17 Virtual Output 17
0x00D1 VO 18 Virtual Output 18
0x00D2 VO 19 Virtual Output 19
0x00D3 VO 20 Virtual Output 20
0x00D4 VO 21 Virtual Output 21
0x00D5 VO 22 Virtual Output 22
0x00D6 VO 23 Virtual Output 23
0x00D7 VO 24 Virtual Output 24
0x00D8 VO 25 Virtual Output 25
0x00D9 VO 26 Virtual Output 26
0x00DA VO 27 Virtual Output 27
0x00DB VO 28 Virtual Output 28
0x00DC VO 29 Virtual Output 29
0x00DD VO 30 Virtual Output 30
0x00DE VO 31 Virtual Output 31
0x00DF VO 32 Virtual Output 32
0x8001 Any Trip PickUp Any Trip PickUp
0x8002 Any Trip Any Trip
0x8004 Any Trip DropOut Any Trip DropOut
0xA001 Any Alarm PickUp Any Alarm PickUp
0xA002 Any Alarm Any Alarm
0xA004 Any Alarm DropOut Any Alarm DropOut
0xC002 Any Inhibit Any Inhibit
0xD000 Input 1 Input 1
0xD001 Input 2 Input 2
0xD002 Input 3 Input 3
FC133A unsigned 16 bits Data Log Trigger
0 None None
1 Command Command
0x00C0 Logic Element 1 Logic Element 1
0x00C1 Logic Element 2 Logic Element 2
0x00C2 Logic Element 3 Logic Element 3
0x00C3 Logic Element 4 Logic Element 4
0x00C4 Logic Element 5 Logic Element 5
0x00C5 Logic Element 6 Logic Element 6
0x00C6 Logic Element 7 Logic Element 7
0x00C7 Logic Element 8 Logic Element 8
0x00C8 Logic Element 9 Logic Element 9
0x00C9 Logic Element 10 Logic Element 10
0x00CA Logic Element 11 Logic Element 11
0x00CB Logic Element 12 Logic Element 12
0x00CC Logic Element 13 Logic Element 13
0x00CD Logic Element 14 Logic Element 14
0x00CE Logic Element 15 Logic Element 15
0x00CF Logic Element 16 Logic Element 16
0x8001 Any Trip PickUp Any Trip PickUp

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-111


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x8002 Any Trip Any Trip
0x8004 Any Trip DropOut Any Trip DropOut
0xA001 Any Alarm PickUp Any Alarm PickUp
0xA002 Any Alarm Any Alarm
0xA004 Any Alarm DropOut Any Alarm DropOut
0xC002 Any Inhibit Any Inhibit
FC134 unsigned 16 bits Cause of Event
0 No Evnt/Trp ToDate No Event/Trip To Date
1 Ctrl. Pwr Lost Control Power Lost
2 Ctrl. Pwr Applied Control Power Applied
3 Date or Time Set Date or Time Set
4 Reset Reset
5 Lockout Rst Closed Lockout Reset Closed
6 Factory Reload Factory Reload
7 Clock Not Set Clock Not Set
8 IRIG-B Failure IRIG-B Failure
9 Reset Trip Counter Reset Trip Counter
10 BKR Status Unknown Breaker Status Unknown
11 Clear Event Rec Clear Event Records
12 Clear Transt Rec Clear Transient Records
13 Clear Therm Cap Clear Thermal Capacity
14 Comm. Alert 1 Comm. Alert 1
15 Comm. Alert 2 Comm. Alert 2
16 Comm. Alert 3 Comm. Alert 3
17 Ethernet Link Fail Ethernet Link Failure
18 High ENET Traffic High Ethernet Traffic
19 Intern Temp. >80C Internal Temperature High
20 RMIO Mismatch RMIO Mismatch
22 Emergency Restart Emergency Restart
23 Trace Mem. Trigger Trace Mem. Trigger
24 Rx Goose 1 ON Rx Goose 1 ON
25 Rx Goose 1 OFF Rx Goose 1 OFF
26 Rx Goose 2 ON Rx Goose 2 ON
27 Rx Goose 2 OFF Rx Goose 2 OFF
28 Rx Goose 3 ON Rx Goose 3 ON
29 Rx Goose 3 OFF Rx Goose 3 OFF
30 Rx Goose 4 ON Rx Goose 4 ON
31 Rx Goose 4 OFF Rx Goose 4 OFF
32 Rx Goose 5 ON Rx Goose 5 ON
33 Rx Goose 5 OFF Rx Goose 5 OFF
34 Rx Goose 6 ON Rx Goose 6 ON
35 Rx Goose 6 OFF Rx Goose 6 OFF
36 Rx Goose 7 ON Rx Goose 7 ON
37 Rx Goose 7 OFF Rx Goose 7 OFF
38 Rx Goose 8 ON Rx Goose 8 ON
39 Rx Goose 8 OFF Rx Goose 8 OFF
40 Eth Link A Fail Ethernet Link A Fail

10-112 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


41 Eth Link B Fail Ethernet Link B Fail
0x0040 Contact IN 1 On Contact Input 1 On
0x0041 Contact IN 2 On Contact Input 2 On
0x0042 Contact IN 3 On Contact Input 3 On
0x0043 Contact IN 4 On Contact Input 4 On
0x0044 Contact IN 5 On Contact Input 5 On
0x0045 Contact IN 6 On Contact Input 6 On
0x0046 Contact IN 7 On Contact Input 7 On
0x0047 Contact IN 8 On Contact Input 8 On
0x0048 Contact IN 9 On Contact Input 9 On
0x0049 Contact IN 10 On Contact Input 10 On
0x0060 Contact IN 1 Off Contact Input 1 Off
0x0061 Contact IN 2 Off Contact Input 2 Off
0x0062 Contact IN 3 Off Contact Input 3 Off
0x0063 Contact IN 4 Off Contact Input 4 Off
0x0064 Contact IN 5 Off Contact Input 5 Off
0x0065 Contact IN 6 Off Contact Input 6 Off
0x0066 Contact IN 7 Off Contact Input 7 Off
0x0067 Contact IN 8 Off Contact Input 8 Off
0x0068 Contact IN 9 Off Contact Input 9 Off
0x0069 Contact IN 10 Off Contact Input 10 Off
0x0080 Virtual IN 1 On Virtual Input 1 On
0x0081 Virtual IN 2 On Virtual Input 2 On
0x0082 Virtual IN 3 On Virtual Input 3 On
0x0083 Virtual IN 4 On Virtual Input 4 On
0x0084 Virtual IN 5 On Virtual Input 5 On
0x0085 Virtual IN 6 On Virtual Input 6 On
0x0086 Virtual IN 7 On Virtual Input 7 On
0x0087 Virtual IN 8 On Virtual Input 8 On
0x0088 Virtual IN 9 On Virtual Input 9 On
0x0089 Virtual IN 10 On Virtual Input 10 On
0x008A Virtual IN 11 On Virtual Input 11 On
0x008B Virtual IN 12 On Virtual Input 12 On
0x008C Virtual IN 13 On Virtual Input 13 On
0x008D Virtual IN 14 On Virtual Input 14 On
0x008E Virtual IN 15 On Virtual Input 15 On
0x008F Virtual IN 16 On Virtual Input 16 On
0x0090 Virtual IN 17 On Virtual Input 17 On
0x0091 Virtual IN 18 On Virtual Input 18 On
0x0092 Virtual IN 19 On Virtual Input 19 On
0x0093 Virtual IN 20 On Virtual Input 20 On
0x0094 Virtual IN 21 On Virtual Input 21 On
0x0095 Virtual IN 22 On Virtual Input 22 On
0x0096 Virtual IN 23 On Virtual Input 23 On
0x0097 Virtual IN 24 On Virtual Input 24 On
0x0098 Virtual IN 25 On Virtual Input 25 On
0x0099 Virtual IN 26 On Virtual Input 26 On

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-113


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x009A Virtual IN 27 On Virtual Input 27 On
0x009B Virtual IN 28 On Virtual Input 28 On
0x009C Virtual IN 29 On Virtual Input 29 On
0x009D Virtual IN 30 On Virtual Input 30 On
0x009E Virtual IN 31 On Virtual Input 31 On
0x009F Virtual IN 32 On Virtual Input 32 On
0x00A0 Virtual IN 1 Off Virtual Input 1 Off
0x00A1 Virtual IN 2 Off Virtual Input 2 Off
0x00A2 Virtual IN 3 Off Virtual Input 3 Off
0x00A3 Virtual IN 4 Off Virtual Input 4 Off
0x00A4 Virtual IN 5 Off Virtual Input 5 Off
0x00A5 Virtual IN 6 Off Virtual Input 6 Off
0x00A6 Virtual IN 7 Off Virtual Input 7 Off
0x00A7 Virtual IN 8 Off Virtual Input 8 Off
0x00A8 Virtual IN 9 Off Virtual Input 9 Off
0x00A9 Virtual IN 10 Off Virtual Input 10 Off
0x00AA Virtual IN 11 Off Virtual Input 11 Off
0x00AB Virtual IN 12 Off Virtual Input 12 Off
0x00AC Virtual IN 13 Off Virtual Input 13 Off
0x00AD Virtual IN 14 Off Virtual Input 14 Off
0x00AE Virtual IN 15 Off Virtual Input 15 Off
0x00AF Virtual IN 16 Off Virtual Input 16 Off
0x00B0 Virtual IN 17 Off Virtual Input 17 Off
0x00B1 Virtual IN 18 Off Virtual Input 18 Off
0x00B2 Virtual IN 19 Off Virtual Input 19 Off
0x00B3 Virtual IN 20 Off Virtual Input 20 Off
0x00B4 Virtual IN 21 Off Virtual Input 21 Off
0x00B5 Virtual IN 22 Off Virtual Input 22 Off
0x00B6 Virtual IN 23 Off Virtual Input 23 Off
0x00B7 Virtual IN 24 Off Virtual Input 24 Off
0x00B8 Virtual IN 25 Off Virtual Input 25 Off
0x00B9 Virtual IN 26 Off Virtual Input 26 Off
0x00BA Virtual IN 27 Off Virtual Input 27 Off
0x00BB Virtual IN 28 Off Virtual Input 28 Off
0x00BC Virtual IN 29 Off Virtual Input 29 Off
0x00BD Virtual IN 30 Off Virtual Input 30 Off
0x00BE Virtual IN 31 Off Virtual Input 31 Off
0x00BF Virtual IN 32 Off Virtual Input 32 Off
0x01C0 Remote IN 1 On Remote Input 1 On
0x01C1 Remote IN 2 On Remote Input 2 On
0x01C2 Remote IN 3 On Remote Input 3 On
0x01C3 Remote IN 4 On Remote Input 4 On
0x01C4 Remote IN 5 On Remote Input 5 On
0x01C5 Remote IN 6 On Remote Input 6 On
0x01C6 Remote IN 7 On Remote Input 7 On
0x01C7 Remote IN 8 On Remote Input 8 On
0x01C8 Remote IN 9 On Remote Input 9 On

10-114 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x01C9 Remote IN 10 On Remote Input 10 On
0x01CA Remote IN 11 On Remote Input 11 On
0x01CB Remote IN 12 On Remote Input 12 On
0x01CC Remote IN 13 On Remote Input 13 On
0x01CD Remote IN 14 On Remote Input 14 On
0x01CE Remote IN 15 On Remote Input 15 On
0x01CF Remote IN 16 On Remote Input 16 On
0x01D0 Remote IN 17 On Remote Input 17 On
0x01D1 Remote IN 18 On Remote Input 18 On
0x01D2 Remote IN 19 On Remote Input 19 On
0x01D3 Remote IN 20 On Remote Input 20 On
0x01D4 Remote IN 21 On Remote Input 21 On
0x01D5 Remote IN 22 On Remote Input 22 On
0x01D6 Remote IN 23 On Remote Input 23 On
0x01D7 Remote IN 24 On Remote Input 24 On
0x01D8 Remote IN 25 On Remote Input 25 On
0x01D9 Remote IN 26 On Remote Input 26 On
0x01DA Remote IN 27 On Remote Input 27 On
0x01DB Remote IN 28 On Remote Input 28 On
0x01DC Remote IN 29 On Remote Input 29 On
0x01DD Remote IN 30 On Remote Input 30 On
0x01DE Remote IN 31 On Remote Input 31 On
0x01DF Remote IN 32 On Remote Input 32 On
0x01E0 Remote IN 1 Off Remote Input 1 Off
0x01E1 Remote IN 2 Off Remote Input 2 Off
0x01E2 Remote IN 3 Off Remote Input 3 Off
0x01E3 Remote IN 4 Off Remote Input 4 Off
0x01E4 Remote IN 5 Off Remote Input 5 Off
0x01E5 Remote IN 6 Off Remote Input 6 Off
0x01E6 Remote IN 7 Off Remote Input 7 Off
0x01E7 Remote IN 8 Off Remote Input 8 Off
0x01E8 Remote IN 9 Off Remote Input 9 Off
0x01E9 Remote IN 10 Off Remote Input 10 Off
0x01EA Remote IN 11 Off Remote Input 11 Off
0x01EB Remote IN 12 Off Remote Input 12 Off
0x01EC Remote IN 13 Off Remote Input 13 Off
0x01ED Remote IN 14 Off Remote Input 14 Off
0x01EE Remote IN 15 Off Remote Input 15 Off
0x01EF Remote IN 16 Off Remote Input 16 Off
0x01F0 Remote IN 17 Off Remote Input 17 Off
0x01F1 Remote IN 18 Off Remote Input 18 Off
0x01F2 Remote IN 19 Off Remote Input 19 Off
0x01F3 Remote IN 20 Off Remote Input 20 Off
0x01F4 Remote IN 21 Off Remote Input 21 Off
0x01F5 Remote IN 22 Off Remote Input 22 Off
0x01F6 Remote IN 23 Off Remote Input 23 Off
0x01F7 Remote IN 24 Off Remote Input 24 Off

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-115


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x01F8 Remote IN 25 Off Remote Input 25 Off
0x01F9 Remote IN 26 Off Remote Input 26 Off
0x01FA Remote IN 27 Off Remote Input 27 Off
0x01FB Remote IN 28 Off Remote Input 28 Off
0x01FC Remote IN 29 Off Remote Input 29 Off
0x01FD Remote IN 30 Off Remote Input 30 Off
0x01FE Remote IN 31 Off Remote Input 31 Off
0x01FF Remote IN 32 Off Remote Input 32 Off
0x8002 Any Trip Any Trip
0x8041 Therm O/L Trip PKP Thermal Overload Trip PKP
0x8042 Therm O/L Trip OP Thermal Overload Trip OP
0x8044 Therm O/L Trip DPO Thermal Overload Trip DPO
0x8081 GF Trip PKP GF Trip PKP
0x8082 GF Trip OP GF Trip OP
0x8084 GF Trip DPO GF Trip DPO
0x80C2 Accel Trip OP Acceleration Trip OP
0x8141 Under Pwr Trip PKP Under Power Trip PKP
0x8142 Under Pwr Trip OP Under Power Trip OP
0x8144 Under Pwr Trip DPO Under Power Trip DPO
0x8181 Single PH Trip PKP Single PH Trip PKP
0x8182 Single PH Trip OP Single PH Trip OP
0x8184 Single PH Trip DPO Single PH Trip DPO
0x8201 Mech Jam Trip PKP Mech Jam Trip PKP
0x8202 Mech Jam Trip OP Mech Jam Trip OP
0x8204 Mech Jam Trip DPO Mech Jam Trip DPO
0x8241 U/CURR Trip PKP U/CURR Trip PKP
0x8242 U/CURR Trip OP U/CURR Trip OP
0x8244 U/CURR Trip DPO U/CURR Trip DPO
0x8281 UNBAL Trip PKP Unbalance Trip PKP
0x8282 UNBAL Trip OP Unbalance Trip OP
0x8284 UNBAL Trip DPO Unbalance Trip DPO
0x82C1 RTD 1 Trip PKP RTD 1 Trip PKP
0x82C2 RTD 1 Trip OP RTD 1 Trip OP
0x8301 RTD 2 Trip PKP RTD 2 Trip PKP
0x8302 RTD 2 Trip OP RTD 2 Trip OP
0x8341 RTD 3 Trip PKP RTD 3 Trip PKP
0x8342 RTD 3 Trip OP RTD 3 Trip OP
0x8381 RTD 4 Trip PKP RTD 4 Trip PKP
0x8382 RTD 4 Trip OP RTD 4 Trip OP
0x83C1 RTD 5 Trip PKP RTD 5 Trip PKP
0x83C2 RTD 5 Trip OP RTD 5 Trip OP
0x8401 RTD 6 Trip PKP RTD 6 Trip PKP
0x8402 RTD 6 Trip OP RTD 6 Trip OP
0x84C1 LE 1 Trip PKP Logic Element 1 Trip PKP
0x84C2 LE 1 Trip OP Logic Element 1 Trip OP
0x84C4 LE 1 Trip DPO Logic Element 1 Trip DPO
0x8501 LE 2 Trip PKP Logic Element 2 Trip PKP

10-116 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x8502 LE 2 Trip OP Logic Element 2 Trip OP
0x8504 LE 2 Trip DPO Logic Element 2 Trip DPO
0x8541 LE 3 Trip PKP Logic Element 3 Trip PKP
0x8542 LE 3 Trip OP Logic Element 3 Trip OP
0x8544 LE 3 Trip DPO Logic Element 3 Trip DPO
0x8581 LE 4 Trip PKP Logic Element 4 Trip PKP
0x8582 LE 4 Trip OP Logic Element 4 Trip OP
0x8584 LE 4 Trip DPO Logic Element 4 Trip DPO
0x85C1 LE 5 Trip PKP Logic Element 5 Trip PKP
0x85C2 LE 5 Trip OP Logic Element 5 Trip OP
0x85C4 LE 5 Trip DPO Logic Element 5 Trip DPO
0x8601 LE 6 Trip PKP Logic Element 6 Trip PKP
0x8602 LE 6 Trip OP Logic Element 6 Trip OP
0x8604 LE 6 Trip DPO Logic Element 6 Trip DPO
0x8641 LE 7 Trip PKP Logic Element 7 Trip PKP
0x8642 LE 7 Trip OP Logic Element 7 Trip OP
0x8644 LE 7 Trip DPO Logic Element 7 Trip DPO
0x8681 LE 8 Trip PKP Logic Element 8 Trip PKP
0x8682 LE 8 Trip OP Logic Element 8 Trip OP
0x8684 LE 8 Trip DPO Logic Element 8 Trip DPO
0x86C1 RTD 7 Trip PKP RTD 7 Trip PKP
0x86C2 RTD 7 Trip OP RTD 7 Trip OP
0x8701 RTD 8 Trip PKP RTD 8 Trip PKP
0x8702 RTD 8 Trip OP RTD 8 Trip OP
0x8741 RTD 9 Trip PKP RTD 9 Trip PKP
0x8742 RTD 9 Trip OP RTD 9 Trip OP
0x8781 RTD 10 Trip PKP RTD 10 Trip PKP
0x8782 RTD 10 Trip OP RTD 10 Trip OP
0x87C1 RTD 11 Trip PKP RTD 11 Trip PKP
0x87C2 RTD 11 Trip OP RTD 11 Trip OP
0x8801 RTD 12 Trip PKP RTD 12 Trip PKP
0x8802 RTD 12 Trip OP RTD 12 Trip OP
0x8841 PosSeq UV1 Trp PKP Positive Sequence UV 1 Trp PKP
0x8842 PosSeq UV1 Trip OP Positive Sequence UV 1 Trip OP
0x8844 PosSeq UV1 Trp DPO Positive Sequence UV 1 Trp DPO
0x8901 PosSeq UV2 Trp PKP Positive Sequence UV 2 Trp PKP
0x8902 PosSeq UV2 Trip OP Positive Sequence UV 2 Trip OP
0x8904 PosSeq UV2 Trp DPO Positive Sequence UV 2 Trp DPO
0x89C2 Self Test OP Self Test OP
0x89C4 Self Test DPO Self Test Trip DPO
0x8F81 Fuse Fail Trip PKP Fuse Fail Trip PKP
0x8F82 Fuse Fail Trip OP Fuse Fail Trip OP
0x8F84 Fuse Fail Trip DPO Fuse Fail Trip DPO
0x8FC1 Ph Revrsl Trip PKP Ph Revrsl Trip PKP
0x8FC2 Ph Revrsl Trip OP Ph Revrsl Trip OP
0x8FC4 Ph Revrsl Trip DPO Ph Revrsl Trip DPO
0x9041 Ntrl IOC1 Trip PKP Neutral IOC 1 Trip PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-117


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x9042 Ntrl IOC1 Trip OP Neutral IOC 1 Trip OP
0x9044 Ntrl IOC1 Trip DPO Neutral IOC 1 Trip DPO
0x90C1 Ph TOC1 Trip PKP Phase TOC 1 Trip PKP
0x90C2 Ph TOC1 Trip OP Phase TOC 1 Trip OP
0x90C4 Ph TOC1 Trip DPO Phase TOC 1 Trip DPO
0x90C9 Ph A TOC1 Trip PKP Phase A TOC 1 Trip PKP
0x90CA Ph A TOC1 Trip OP Phase A TOC 1 Trip OP
0x90CC Ph A TOC1 Trip DPO Phase A TOC 1 Trip DPO
0x90D1 Ph B TOC1 Trip PKP Phase B TOC 1 Trip PKP
0x90D2 Ph B TOC1 Trip OP Phase B TOC 1 Trip OP
0x90D4 Ph B TOC1 Trip DPO Phase B TOC 1 Trip DPO
0x90E1 Ph C TOC1 Trip PKP Phase C TOC 1 Trip PKP
0x90E2 Ph C TOC1 Trip OP Phase C TOC 1 Trip OP
0x90E4 Ph C TOC1 Trip DPO Phase C TOC 1 Trip DPO
0x9101 Ntrl TOC1 Trip PKP Neutral TOC 1 Trip PKP
0x9102 Ntrl TOC1 Trip OP Neutral TOC 1 Trip OP
0x9104 Ntrl TOC1 Trip DPO Neutral TOC 1 Trip DPO
0x9241 Dir Pwr 1 Trip PKP Directional Pwr 1 Trip PKP
0x9242 Dir Pwr 1 Trip OP Directional Pwr 1 Trip OP
0x9281 Dir Pwr 2 Trip PKP Directional Pwr 2 Trip PKP
0x9282 Dir Pwr 2 Trip OP Directional Pwr 2 Trip OP
0x93C1 NSeq OV Trp PKP Negative Sequence OV Trip PKP
0x93C2 NSeq OV Trp OP Negative Sequence OV Trip OP
0x93C4 NSeq OV Trp DPO Negative Sequence OV Trip DPO
0x9441 Ph OV1 Trip PKP Phase OV1 Trip PKP
0x9442 Ph OV1 Trip OP Phase OV 1 Trip OP
0x9444 Ph OV1 Trip DPO Phase OV1 Trip DPO
0x9449 Ph A OV1 Trip PKP Phase A OV1 Trip PKP
0x944A Ph A OV1 Trip OP Phase A OV1 Trip OP
0x944C Ph A OV1 Trip DPO Phase A OV1 Trip DPO
0x9451 Ph B OV1 Trip PKP Phase B OV1 Trip PKP
0x9452 Ph B OV1 Trip OP Phase B OV1 Trip OP
0x9454 Ph B OV1 Trip DPO Phase B OV1 Trip DPO
0x9461 Ph C OV1 Trip PKP Phase C OV1 Trip PKP
0x9462 Ph C OV1 Trip OP Phase C OV1 Trip OP
0x9464 Ph C OV1 Trip DPO Phase C OV1 Trip DPO
0x9481 Ph UV1 Trip PKP Phase UV1 Trip PKP
0x9482 Ph UV1 Trip OP Phase UV 1 Trip OP
0x9484 Ph UV1 Trip DPO Phase UV1 Trip DPO
0x9489 Ph A UV1 Trip PKP Phase A UV1 Trip PKP
0x948A Ph A UV1 Trip OP Phase A UV1 Trip OP
0x948C Ph A UV1 Trip DPO Phase A UV1 Trip DPO
0x9491 Ph B UV1 Trip PKP Phase B UV1 Trip PKP
0x9492 Ph B UV1 Trip OP Phase B UV1 Trip OP
0x9494 Ph B UV1 Trip DPO Phase B UV1 Trip DPO
0x94A1 Ph C UV1 Trip PKP Phase C UV1 Trip PKP
0x94A2 Ph C UV1 Trip OP Phase C UV1 Trip OP

10-118 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x94A4 Ph C UV1 Trip DPO Phase C UV1 Trip DPO
0x9541 UndrFreq1 Trip PKP Underfrequency 1 Trip PKP
0x9542 UndrFreq1 Trip OP Underfrequency 1 Trip OP
0x9544 UndrFreq1 Trip DPO Underfrequency 1 Trip DPO
0x9581 UndrFreq2 Trip PKP Underfrequency 2 Trip PKP
0x9582 UndrFreq2 Trip OP Underfrequency 2 Trip OP
0x9584 UndrFreq2 Trip DPO Underfrequency 2 Trip DPO
0x95C1 OverFreq1 Trip PKP Overfrequency 1 Trip PKP
0x95C2 OverFreq1 Trip OP Overfrequency 1 Trip OP
0x95C4 OverFreq1 Trip DPO Overfrequency 1 Trip DPO
0x9601 OverFreq2 Trip PKP Overfrequency 2 Trip PKP
0x9602 OverFreq2 Trip OP Overfrequency 2 Trip OP
0x9604 OverFreq2 Trip DPO Overfrequency 2 Trip DPO
0x9881 Ph OV2 Trip PKP Phase OV 2 Trip PKP
0x9882 Ph OV2 Trip OP Phase OV 2 Trip OP
0x9884 Ph OV2 Trip DPO Phase OV 2 Trip DPO
0x9889 Ph A OV2 Trip PKP Phase A OV2 Trip PKP
0x988A Ph A OV2 Trip OP Phase A OV2 Trip OP
0x988C Ph A OV2 Trip DPO Phase A OV2 Trip DPO
0x9891 Ph B OV2 Trip PKP Phase B OV2 Trip PKP
0x9892 Ph B OV2 Trip OP Phase B OV2 Trip OP
0x9894 Ph B OV2 Trip DPO Phase B OV2 Trip DPO
0x98A1 Ph C OV2 Trip PKP Phase C OV2 Trip PKP
0x98A2 Ph C OV2 Trip OP Phase C OV2 Trip OP
0x98A4 Ph C OV2 Trip DPO Phase C OV2 Trip DPO
0x98C1 Ph UV2 Trip PKP Phase UV 2 Trip PKP
0x98C2 Ph UV2 Trip OP Phase UV 2 Trip OP
0x98C4 Ph UV2 Trip DPO Phase UV 2 Trip DPO
0x98C9 Ph A UV2 Trip PKP Phase A UV2 Trip PKP
0x98CA Ph A UV2 Trip OP Phase A UV2 Trip OP
0x98CC Ph A UV2 Trip DPO Phase A UV2 Trip DPO
0x98D1 Ph B UV2 Trip PKP Phase B UV2 Trip PKP
0x98D2 Ph B UV2 Trip OP Phase B UV2 Trip OP
0x98D4 Ph B UV2 Trip DPO Phase B UV2 Trip DPO
0x98E1 Ph C UV2 Trip PKP Phase C UV2 Trip PKP
0x98E2 Ph C UV2 Trip OP Phase C UV2 Trip OP
0x98E4 Ph C UV2 Trip DPO Phase C UV2 Trip DPO
0x9901 S/C Trip PKP S/C Trip PKP
0x9902 S/C Trip OP S/C Trip OP
0x9904 S/C Trip DPO S/C Trip DPO
0x9941 SPD2 S/C Trip PKP SPD2 S/C Trip PKP
0x9942 SPD2 S/C Trip OP SPD2 S/C Trip OP
0x9944 SPD2 S/C Trip DPO SPD2 S/C Trip DPO
0x9981 SPD2 U/C Trip PKP SPD2 U/C Trip PKP
0x9982 SPD2 U/C Trip OP SPD2 U/C Trip OP
0x9984 SPD2 U/C Trip DPO SPD2 U/C Trip DPO
0x9C01 LE 9 Trip PKP Logic Element 9 Trip PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-119


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x9C02 LE 9 Trip OP Logic Element 9 Trip OP
0x9C04 LE 9 Trip DPO Logic Element 9 Trip DPO
0x9C41 LE 10 Trip PKP Logic Element 10 Trip PKP
0x9C42 LE 10 Trip OP Logic Element 10 Trip OP
0x9C44 LE 10 Trip DPO Logic Element 10 Trip DPO
0x9C81 LE 11 Trip PKP Logic Element 11 Trip PKP
0x9C82 LE 11 Trip OP Logic Element 11 Trip OP
0x9C84 LE 11 Trip DPO Logic Element 11 Trip DPO
0x9CC1 LE 12 Trip PKP Logic Element 12 Trip PKP
0x9CC2 LE 12 Trip OP Logic Element 12 Trip OP
0x9CC4 LE 12 Trip DPO Logic Element 12 Trip DPO
0x9D01 LE 13 Trip PKP Logic Element 13 Trip PKP
0x9D02 LE 13 Trip OP Logic Element 13 Trip OP
0x9D04 LE 13 Trip DPO Logic Element 13 Trip DPO
0x9D41 LE 14 Trip PKP Logic Element 14 Trip PKP
0x9D42 LE 14 Trip OP Logic Element 14 Trip OP
0x9D44 LE 14 Trip DPO Logic Element 14 Trip DPO
0x9D81 LE 15 Trip PKP Logic Element 15 Trip PKP
0x9D82 LE 15 Trip OP Logic Element 15 Trip OP
0x9D84 LE 15 Trip DPO Logic Element 15 Trip DPO
0x9DC1 LE 16 Trip PKP Logic Element 16 Trip PKP
0x9DC2 LE 16 Trip OP Logic Element 16 Trip OP
0x9DC4 LE 16 Trip DPO Logic Element 16 Trip DPO
0xA002 Any Alarm Any Alarm
0xA042 Therm Lvl Alrm OP Thermal Level Alarm OP
0xA044 Therm Lvl Alrm DPO Thermal Level Alarm DPO
0xA081 Gnd Fault Alrm PKP Ground Fault Alarm PKP
0xA082 Gnd Fault Alrm OP Ground Fault Alarm OP
0xA084 Gnd Fault Alrm DPO Ground Fault Alarm DPO
0xA0C2 Accel Alarm OP Accel Alarm OP
0xA141 Under Pwr Alrm PKP Under Power Alarm PKP
0xA142 Under Pwr Alrm OP Under Power Alarm OP
0xA144 Under Pwr Alrm DPO Under Power Alarm DPO
0xA201 Mech Jam Alarm PKP Mech Jam Alarm PKP
0xA202 Mech Jam Alarm OP Mech Jam Alarm OP
0xA204 Mech Jam Alarm DPO Mech Jam Alarm DPO
0xA241 U/CURR Alarm PKP U/CURR Alarm PKP
0xA242 U/CURR Alarm OP U/CURR Alarm OP
0xA244 U/CURR Alarm DPO U/CURR Alarm DPO
0xA281 UNBAL Alarm PKP Unbalance Alarm PKP
0xA282 UNBAL Alarm OP Unbalance Alarm OP
0xA284 UNBAL Alarm DPO Unbalance Alarm DPO
0xA2C1 RTD 1 Alarm PKP RTD 1 Alarm PKP
0xA2C2 RTD 1 Alarm OP RTD 1 Alarm OP
0xA301 RTD 2 Alarm PKP RTD 2 Alarm PKP
0xA302 RTD 2 Alarm OP RTD 2 Alarm OP
0xA341 RTD 3 Alarm PKP RTD 3 Alarm PKP

10-120 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0xA342 RTD 3 Alarm OP RTD 3 Alarm OP
0xA381 RTD 4 Alarm PKP RTD 4 Alarm PKP
0xA382 RTD 4 Alarm OP RTD 4 Alarm OP
0xA3C1 RTD 5 Alarm PKP RTD 5 Alarm PKP
0xA3C2 RTD 5 Alarm OP RTD 5 Alarm OP
0xA401 RTD 6 Alarm PKP RTD 6 Alarm PKP
0xA402 RTD 6 Alarm OP RTD 6 Alarm OP
0xA442 RTD Trouble Alr OP RTD Trouble Alarm
0xA482 Relay Not Ready Relay Not Ready
0xA4C1 LE 1 Alarm PKP Logic Element 1 Alarm PKP
0xA4C2 LE 1 Alarm OP Logic Element 1 Alarm OP
0xA4C4 LE 1 Alarm DPO Logic Element 1 Alarm DPO
0xA501 LE 2 Alarm PKP Logic Element 2 Alarm PKP
0xA502 LE 2 Alarm OP Logic Element 2 Alarm OP
0xA504 LE 2 Alarm DPO Logic Element 2 Alarm DPO
0xA541 LE 3 Alarm PKP Logic Element 3 Alarm PKP
0xA542 LE 3 Alarm OP Logic Element 3 Alarm OP
0xA544 LE 3 Alarm DPO Logic Element 3 Alarm DPO
0xA581 LE 4 Alarm PKP Logic Element 4 Alarm PKP
0xA582 LE 4 Alarm OP Logic Element 4 Alarm OP
0xA584 LE 4 Alarm DPO Logic Element 4 Alarm DPO
0xA5C1 LE 5 Alarm PKP Logic Element 5 Alarm PKP
0xA5C2 LE 5 Alarm OP Logic Element 5 Alarm OP
0xA5C4 LE 5 Alarm DPO Logic Element 5 Alarm DPO
0xA601 LE 6 Alarm PKP Logic Element 6 Alarm PKP
0xA602 LE 6 Alarm OP Logic Element 6 Alarm OP
0xA604 LE 6 Alarm DPO Logic Element 6 Alarm DPO
0xA641 LE 7 Alarm PKP Logic Element 7 Alarm PKP
0xA642 LE 7 Alarm OP Logic Element 7 Alarm OP
0xA644 LE 7 Alarm DPO Logic Element 7 Alarm DPO
0xA681 LE 8 Alarm PKP Logic Element 8 Alarm PKP
0xA682 LE 8 Alarm OP Logic Element 8 Alarm OP
0xA684 LE 8 Alarm DPO Logic Element 8 Alarm DPO
0xA6C1 RTD 7 Alarm PKP RTD 7 Alarm PKP
0xA6C2 RTD 7 Alarm OP RTD 7 Alarm OP
0xA701 RTD 8 Alarm PKP RTD 8 Alarm PKP
0xA702 RTD 8 Alarm OP RTD 8 Alarm OP
0xA741 RTD 9 Alarm PKP RTD 9 Alarm PKP
0xA742 RTD 9 Alarm OP RTD 9 Alarm OP
0xA781 RTD 10 Alarm PKP RTD 10 Alarm PKP
0xA782 RTD 10 Alarm OP RTD 10 Alarm OP
0xA7C1 RTD 11 Alarm PKP RTD 11 Alarm PKP
0xA7C2 RTD 11 Alarm OP RTD 11 Alarm OP
0xA801 RTD 12 Alarm PKP RTD 12 Alarm PKP
0xA802 RTD 12 Alarm OP RTD 12 Alarm OP
0xA841 PosSeq UV1 AlrmPKP Positive Sequence UV 1 Alarm PKP
0xA842 PosSeq UV1 Alrm OP Positive Sequence UV 1 Alarm OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-121


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xA844 PosSeq UV1 AlrmDPO Positive Sequence UV 1 Alarm DPO
0xA882 BKR Alarm Breaker Alarm
0xA901 PosSeq UV2 AlrmPKP Positive Sequence UV 2 Alarm PKP
0xA902 PosSeq UV2 Alrm OP Positive Sequence UV 2 Alarm OP
0xA904 PosSeq UV2 AlrmDPO Positive Sequence UV 2 Alarm DPO
0xA982 Motor Run Hrs OP Motor Running Hours OP
0xA9C1 CTFail Alrm PKP CT Fail Alarm PKP
0xA9C2 CTFail Alrm OP CT Fail Alarm OP
0xA9C4 CTFail Alrm DPO CT Fail Alarm DPO
0xAA01 Welded ContactrPKP Welded ContactrPKP
0xAA02 Welded Contactr OP Welded Contactr OP
0xAA04 Welded ContactrDPO Welded ContactrDPO
0xAA42 SPD SW Not Cnfg OP SPD SW Not Cnfg OP
0xAA82 SPD SW Fail OP SPD SW Fail OP
0xAAC1 Load Incr Alrm PKP Load Incr Alrm PKP
0xAAC2 Load Incr Alrm OP Load Incr Alrm OP
0xAAC4 Load Incr Alrm DPO Load Incr Alrm DPO
0xAB02 BKR Trip Time Breaker Trip Time
0xAB42 BKR Close Time Breaker Close Time
0xAB82 BKR Charge Time Breaker Charge Time
0xABC1 HI Amb Temp PKP High Ambient Temperature Alarm PKP
0xABC2 HI Amb Temp OP High Ambient Temperature Alarm
0xABC4 HI Amb Temp DPO High Ambient Temperature Alarm DPO
0xAC01 LO Amb Temp PKP Low Ambient Temperature Alarm PKP
0xAC02 LO Amb Temp OP Low Ambient Temperature Alarm
0xAC04 LO Amb Temp DPO Low Ambient Temperature Alarm DPO
0xAC42 Self Test Alarm OP Self Test Alarm OP
0xAC44 Self Test Alrm DPO Self Test Alarm DPO
0xACC2 BKRTrpCntrAlrm OP Breaker Trip Control Alarm OP
0xACC4 BKRTrpCntrAlrm DPO Breaker Trip Control Alarm DPO
0xAD01 R1 CoilMonAlrm PKP Trip Coil Monitor Alarm PKP
0xAD02 R1 CoilMonAlrm OP Trip Coil Monitor Alarm OP
0xAD04 R1 CoilMonAlrm DPO Trip Coil Monitor Alarm DPO
0xAD41 R2 CoilMonAlrm PKP Close Coil Monitor Alarm PKP
0xAD42 R2 CoilMonAlrm OP Close Coil Monitor Alarm OP
0xAD44 R2 CoilMonAlrm DPO Close Coil Monitor Alarm DPO
0xAD81 BKR Fail Alrm PKP Breaker Fail Alarm PKP
0xAD82 BKR Fail Alrm OP Breaker Fail Alarm OP
0xAD84 BKR Fail Alrm DPO Breaker Fail Alarm DPO
0xADC2 BKR Stat Fail OP Breaker Status Fail OP
0xADC4 BKR Stat Fail DPO Breaker Status Fail DPO
0xAE82 BKR Trp/Cls Fail Breaker Trip/Close Fail
0xAEC2 BKR Charge Fail Breaker Charge Fail
0xAF81 Fuse Fail Alrm PKP Fuse Fail Alarm PKP
0xAF82 Fuse Fail Alrm OP Fuse Fail Alarm OP
0xAF84 Fuse Fail Alrm DPO Fuse Fail Alarm DPO
0xAFC1 Ph Revrsl Alrm PKP Ph Reversal Alarm PKP

10-122 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0xAFC2 Ph Revrsl Alarm OP Ph Reversal Alarm OP
0xAFC4 Ph Revrsl Alrm DPO Ph Reversal Alarm DPO
0xB041 Ntrl IOC1 Alrm PKP Neutral IOC 1 Alarm PKP
0xB042 Ntrl IOC1 Alrm OP Neutral IOC 1 Alarm OP
0xB044 Ntrl IOC1 Alrm DPO Neutral IOC 1 Alarm DPO
0xB0C1 Ph TOC1 Alarm PKP Phase TOC 1 Alarm PKP
0xB0C2 Ph TOC1 Alarm OP Phase TOC 1 Alarm OP
0xB0C4 Ph TOC1 Alarm DPO Phase TOC 1 Alarm DPO
0xB0C9 Ph A TOC1 Alrm PKP Phase A TOC 1 Alarm PKP
0xB0CA Ph A TOC1 Alrm OP Phase A TOC 1 Alarm OP
0xB0CC Ph A TOC1 Alrm DPO Phase A TOC 1 Alarm DPO
0xB0D1 Ph B TOC1 Alrm PKP Phase B TOC 1 Alarm PKP
0xB0D2 Ph B TOC1 Alrm OP Phase B TOC 1 Alarm OP
0xB0D4 Ph B TOC1 Alrm DPO Phase B TOC 1 Alarm DPO
0xB0E1 Ph C TOC1 Alrm PKP Phase C TOC 1 Alarm PKP
0xB0E2 Ph C TOC1 Alrm OP Phase C TOC 1 Alarm OP
0xB0E4 Ph C TOC1 Alrm DPO Phase C TOC 1 Alarm DPO
0xB101 Ntrl TOC1 Alrm PKP Neutral TOC 1 Alarm PKP
0xB102 Ntrl TOC1 Alrm OP Neutral TOC 1 Alarm OP
0xB104 Ntrl TOC1 Alrm DPO Neutral TOC 1 Alarm DPO
0xB241 Dir Pwr 1 Alrm PKP Directional Pwr 1 Alarm PKP
0xB242 Dir Pwr 1 Alarm OP Directional Pwr 1 Alarm OP
0xB281 Dir Pwr 2 Alrm PKP Directional Pwr 2 Alarm PKP
0xB282 Dir Pwr 2 Alarm OP Directional Pwr 2 Alarm OP
0xB341 NtrlDir RevAlmPKP Neutral Directional Reverse Alarm PKP
0xB342 NtrlDir RevAlm OP Neutral Directional Alarm OP
0xB344 NtrlDir RevAlmDPO Neutral Directional Reverse Alarm DPO
0xB3C1 NSeq OV Alrm PKP Negative Sequence OV Alarm PKP
0xB3C2 NSeq OV Alrm OP Negative Sequence OV Alarm OP
0xB3C4 NSeq OV Alrm DPO Negative Sequence OV Alarm DPO
0xB441 Ph OV1 Alarm PKP Phase OV1 Alarm PKP
0xB442 Ph OV1 Alarm OP Phase OV 1 Alarm OP
0xB444 Ph OV1 Alarm DPO Phase OV1 Alarm DPO
0xB449 Ph A OV1 Alarm PKP Phase A OV1 Alarm PKP
0xB44A Ph A OV1 Alarm OP Phase A OV1 Alarm OP
0xB44C Ph A OV1 Alarm DPO Phase A OV1 Alarm DPO
0xB451 Ph B OV1 Alarm PKP Phase B OV1 Alarm PKP
0xB452 Ph B OV1 Alarm OP Phase B OV1 Alarm OP
0xB454 Ph B OV1 Alarm DPO Phase B OV1 Alarm DPO
0xB461 Ph C OV1 Alarm PKP Phase C OV1 Alarm PKP
0xB462 Ph C OV1 Alarm OP Phase C OV1 Alarm OP
0xB464 Ph C OV1 Alarm DPO Phase C OV1 Alarm DPO
0xB481 Ph UV1 Alarm PKP Phase UV1 Alarm PKP
0xB482 Ph UV1 Alarm OP Phase UV 1 Alarm OP
0xB484 Ph UV1 Alarm DPO Phase UV1 Alarm DPO
0xB489 Ph A UV1 Alarm PKP Phase A UV1 Alarm PKP
0xB48A Ph A UV1 Alarm OP Phase A UV1 Alarm OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-123


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xB48C Ph A UV1 Alarm DPO Phase A UV1 Alarm DPO
0xB491 Ph B UV1 Alarm PKP Phase B UV1 Alarm PKP
0xB492 Ph B UV1 Alarm OP Phase B UV1 Alarm OP
0xB494 Ph B UV1 Alarm DPO Phase B UV1 Alarm DPO
0xB4A1 Ph C UV1 Alarm PKP Phase C UV1 Alarm PKP
0xB4A2 Ph C UV1 Alarm OP Phase C UV1 Alarm OP
0xB4A4 Ph C UV1 Alarm DPO Phase C UV1 Alarm DPO
0xB541 UndrFreq1 Alrm PKP Underfrequency 1 Alarm PKP
0xB542 UndrFreq1 Alrm OP Underfrequency 1 Alarm OP
0xB544 UndrFreq1 Alrm DPO Underfrequency 1 Alarm DPO
0xB581 UndrFreq2 Alrm PKP Underfrequency 2 Alarm PKP
0xB582 UndrFreq2 Alrm OP Underfrequency 2 Alarm OP
0xB584 UndrFreq2 Alrm DPO Underfrequency 2 Alarm DPO
0xB5C1 OverFreq1 Alrm PKP Overfrequency 1 Alarm PKP
0xB5C2 OverFreq1 Alrm OP Overfrequency 1 Alarm OP
0xB5C4 OverFreq1 Alrm DPO Overfrequency 1 Alarm DPO
0xB601 OverFreq2 Alrm PKP Overfrequency 2 Alarm PKP
0xB602 OverFreq2 Alrm OP Overfrequency 2 Alarm OP
0xB604 OverFreq2 Alrm DPO Overfrequency 2 Alarm DPO
0xB702 Curr Dmd1 Alrm OP Current Demand 1 Alarm OP
0xB70A C Dmd1 PhA Alrm OP Current Demand 1 PhA Alarm OP
0xB712 C Dmd1 PhB Alrm OP Current Demand 1 PhB Alarm OP
0xB722 C Dmd1 PhC Alrm OP Current Demand 1 PhC Alarm OP
0xB742 RealP Dmd Alrm OP Real Power Demand Alarm OP
0xB782 ReacP Dmd Alrm OP Reactive Power Demand Alarm OP
0xB7C2 AppP Dmd Alrm OP Apparent Power Demand Alarm OP
0xB881 Ph OV2 Alarm PKP Phase OV 2 Alarm PKP
0xB882 Ph OV2 Alarm OP Phase OV 2 Alarm OP
0xB884 Ph OV2 Alarm DPO Phase OV 2 Alarm DPO
0xB889 Ph A OV2 Alarm PKP Ph A OV2 Alarm PKP
0xB88A Ph A OV2 Alarm OP Ph A OV2 Alarm OP
0xB88C Ph A OV2 Alarm DPO Ph A OV2 Alarm DPO
0xB891 Ph B OV2 Alarm PKP Ph B OV2 Alarm PKP
0xB892 Ph B OV2 Alarm OP Ph B OV2 Alarm OP
0xB894 Ph B OV2 Alarm DPO Ph B OV2 Alarm DPO
0xB8A1 Ph C OV2 Alarm PKP Ph C OV2 Alarm PKP
0xB8A2 Ph C OV2 Alarm OP Ph C OV2 Alarm OP
0xB8A4 Ph C OV2 Alarm DPO Ph C OV2 Alarm DPO
0xB8C1 Ph UV2 Alarm PKP Phase UV 2 Alarm PKP
0xB8C2 Ph UV2 Alarm OP Phase UV 2 Alarm OP
0xB8C4 Ph UV2 Alarm DPO Phase UV 2 Alarm DPO
0xB8C9 Ph A UV2 Alarm PKP Ph A UV2 Alarm PKP
0xB8CA Ph A UV2 Alarm OP Ph A UV2 Alarm OP
0xB8CC Ph A UV2 Alarm DPO Ph A UV2 Alarm DPO
0xB8D1 Ph B UV2 Alarm PKP Ph B UV2 Alarm PKP
0xB8D2 Ph B UV2 Alarm OP Ph B UV2 Alarm OP
0xB8D4 Ph B UV2 Alarm DPO Ph B UV2 Alarm DPO

10-124 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0xB8E1 Ph C UV2 Alarm PKP Ph C UV2 Alarm PKP
0xB8E2 Ph C UV2 Alarm OP Ph C UV2 Alarm OP
0xB8E4 Ph C UV2 Alarm DPO Ph C UV2 Alarm DPO
0xB901 S/C Alarm PKP S/C Alarm PKP
0xB902 S/C Alarm OP S/C Alarm OP
0xB904 S/C Alarm DPO S/C Alarm DPO
0xB941 SPD2 S/C Alarm PKP SPD2 S/C Alarm PKP
0xB942 SPD2 S/C Alarm OP SPD2 S/C Alarm OP
0xB944 SPD2 S/C Alarm DPO SPD2 S/C Alarm DPO
0xB981 SPD2 U/C Alarm PKP SPD2 U/C Alarm PKP
0xB982 SPD2 U/C Alarm OP SPD2 U/C Alarm OP
0xB984 SPD2 U/C Alarm DPO SPD2 U/C Alarm DPO
0xBC01 LE 9 Alarm PKP Logic Element 9 Alarm PKP
0xBC02 LE 9 Alarm OP Logic Element 9 Alarm OP
0xBC04 LE 9 Alarm DPO Logic Element 9 Alarm DPO
0xBC41 LE 10 Alarm PKP Logic Element 10 Alarm PKP
0xBC42 LE 10 Alarm OP Logic Element 10 Alarm OP
0xBC44 LE 10 Alarm DPO Logic Element 10 Alarm DPO
0xBC81 LE 11 Alarm PKP Logic Element 11 Alarm PKP
0xBC82 LE 11 Alarm OP Logic Element 11 Alarm OP
0xBC84 LE 11 Alarm DPO Logic Element 11 Alarm DPO
0xBCC1 LE 12 Alarm PKP Logic Element 12 Alarm PKP
0xBCC2 LE 12 Alarm OP Logic Element 12 Alarm OP
0xBCC4 LE 12 Alarm DPO Logic Element 12 Alarm DPO
0xBD01 LE 13 Alarm PKP Logic Element 13 Alarm PKP
0xBD02 LE 13 Alarm OP Logic Element 13 Alarm OP
0xBD04 LE 13 Alarm DPO Logic Element 13 Alarm DPO
0xBD41 LE 14 Alarm PKP Logic Element 14 Alarm PKP
0xBD42 LE 14 Alarm OP Logic Element 14 Alarm OP
0xBD44 LE 14 Alarm DPO Logic Element 14 Alarm DPO
0xBD81 LE 15 Alarm PKP Logic Element 15 Alarm PKP
0xBD82 LE 15 Alarm OP Logic Element 15 Alarm OP
0xBD84 LE 15 Alarm DPO Logic Element 15 Alarm DPO
0xBDC1 LE 16 Alarm PKP Logic Element 16 Alarm PKP
0xBDC2 LE 16 Alarm OP Logic Element 16 Alarm OP
0xBDC4 LE 16 Alarm DPO Logic Element 16 Alarm DPO
0xC002 Any Inhibit Any Inhibit
0xC042 Output Relay 3 On Output Relay 3 On
0xC044 Output Relay 3 Off Output Relay 3 Off
0xC082 Output Relay 4 On Output Relay 4 On
0xC084 Output Relay 4 Off Output Relay 4 Off
0xC0C2 Output Relay 5 On Output Relay 5 On
0xC0C4 Output Relay 5 Off Output Relay 5 Off
0xC102 Output Relay 6 On Output Relay 6 On
0xC104 Output Relay 6 Off Output Relay 6 Off
0xC142 Self-Test Rly 7 OP Self-Test Rly 7 OP
0xC144 Self-Tst Rly 7 DPO Self-Tst Rly 7 DPO

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-125


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xC202 BKR Connected Breaker Connected OP
0xC242 High Speed OP High Speed OP
0xC282 Low Speed OP Low Speed OP
0xC2C2 Any Pkp OP Any Pkp OP
0xC302 Stopped Stopped
0xC342 Starting Starting
0xC382 Running Running
0xC3C2 Motor Online OP Motor Online OP
0xC402 Emergency Restart Emergency Restart
0xC441 Hot RTD PKP Hot RTD PKP
0xC442 Hot RTD OP Hot RTD OP
0xC481 Lockout PKP Lockout PKP
0xC482 Lockout OP Lockout OP
0xC484 Lockout DPO Lockout DPO
0xC4C1 LE 1 PKP Logic Element 1 PKP
0xC4C2 LE 1 OP Logic Element 1 OP
0xC4C4 LE 1 DPO Logic Element 1 DPO
0xC501 LE 2 PKP Logic Element 2 PKP
0xC502 LE 2 OP Logic Element 2 OP
0xC504 LE 2 DPO Logic Element 2 DPO
0xC541 LE 3 PKP Logic Element 3 PKP
0xC542 LE 3 OP Logic Element 3 OP
0xC544 LE 3 DPO Logic Element 3 DPO
0xC581 LE 4 PKP Logic Element 4 PKP
0xC582 LE 4 OP Logic Element 4 OP
0xC584 LE 4 DPO Logic Element 4 DPO
0xC5C1 LE 5 PKP Logic Element 5 PKP
0xC5C2 LE 5 OP Logic Element 5 OP
0xC5C4 LE 5 DPO Logic Element 5 DPO
0xC601 LE 6 PKP Logic Element 6 PKP
0xC602 LE 6 OP Logic Element 6 OP
0xC604 LE 6 DPO Logic Element 6 DPO
0xC641 LE 7 PKP Logic Element 7 PKP
0xC642 LE 7 OP Logic Element 7 OP
0xC644 LE 7 DPO Logic Element 7 DPO
0xC681 LE 8 PKP Logic Element 8 PKP
0xC682 LE 8 OP Logic Element 8 OP
0xC684 LE 8 DPO Logic Element 8 DPO
0xC742 VFD Bypassed VFD Bypassed
0xC744 VFD Not Bypassed VFD Not Bypassed
0xC902 BKR Open Breaker Open
0xC942 BKR Close Breaker Close
0xC982 Maint. Req. OP Maintenance Required OP
0xCA02 52a Contact OP 52a Contact OP
0xCA42 52b Contact OP 52b Contact OP
0xCA82 Reset OK Reset OK
0xCAC2 L/O Rst Closed OP Lockout Reset Closed OP

10-126 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0xCAC4 L/O Rst Closed DPO Lockout Reset Closed DPO
0xCCC2 BKR Stat Open Breaker Status Open OP
0xCD02 BKR Stat Clsd Breaker Status Closed OP
0xCD82 Testing ON Testing ON
0xCD84 Testing OFF Testing OFF
0xCE82 Therm Inhibit OP Therm Inhibit OP
0xCE84 Therm Inhibit DPO Thermal Inhibit DPO
0xCEC2 Restart Inhibit OP Restart Inhibit OP
0xCEC4 Restart Inhib Off Restart Inhib Off
0xCF02 Starts/Hr Inhib OP Starts/Hr Inhibit OP
0xCF04 Start/Hr Inhib Off Start/Hr Inhib Off
0xCF42 T-BT-Strt Inhib OP T-BT-Strt Inhibit OP
0xCF44 T-BT-Strt InhibOff T-BT-Strt InhibOff
0xCF81 Fuse Fail InhibPKP Fuse Fail InhibPKP
0xCF82 Fuse Fail Inhib OP Fuse Fail Inhibit OP
0xCF84 Fuse Fail InhibDPO Fuse Fail Inhibit DPO
0xCFC2 Ph Rev Inhibit OP Ph Reversal Inhibit OP
0xCFC4 Ph Rev Inhibit DPO Ph Rev Inhibit DPO
0xD241 Dir Pwr 1 PKP Directional Pwr 1 PKP
0xD242 Dir Pwr 1 OP Directional Pwr 1 OP
0xD281 Dir Pwr 2 PKP Directional Pwr 2 PKP
0xD282 Dir Pwr 2 OP Directional Pwr 2 OP
0xD341 Ntrl Dir Rev PKP Neutral Directional Reverse PKP
0xD342 Ntrl Dir Rev OP Neutral Directional Rev OP
0xD344 Ntrl Dir Rev DPO Neutral Directional Reverse DPO
0xDC01 LE 9 PKP Logic Element 9 PKP
0xDC02 LE 9 OP Logic Element 9 OP
0xDC04 LE 9 DPO Logic Element 9 DPO
0xDC41 LE 10 PKP Logic Element 10 PKP
0xDC42 LE 10 OP Logic Element 10 OP
0xDC44 LE 10 DPO Logic Element 10 DPO
0xDC81 LE 11 PKP Logic Element 11 PKP
0xDC82 LE 11 OP Logic Element 11 OP
0xDC84 LE 11 DPO Logic Element 11 DPO
0xDCC1 LE 12 PKP Logic Element 12 PKP
0xDCC2 LE 12 OP Logic Element 12 OP
0xDCC4 LE 12 DPO Logic Element 12 DPO
0xDD01 LE 13 PKP Logic Element 13 PKP
0xDD02 LE 13 OP Logic Element 13 OP
0xDD04 LE 13 DPO Logic Element 13 DPO
0xDD41 LE 14 PKP Logic Element 14 PKP
0xDD42 LE 14 OP Logic Element 14 OP
0xDD44 LE 14 DPO Logic Element 14 DPO
0xDD81 LE 15 PKP Logic Element 15 PKP
0xDD82 LE 15 OP Logic Element 15 OP
0xDD84 LE 15 DPO Logic Element 15 DPO
0xDDC1 LE 16 PKP Logic Element 16 PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-127


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xDDC2 LE 16 OP Logic Element 16 OP
0xDDC4 LE 16 DPO Logic Element 16 DPO
0xE002 Any Block Any Block
0xE004 Any Block DPO Any Block DPO
0xE042 Therm O/L Block Thermal Level Block
0xE044 Therm O/L Blk DPO Thermal Level Block DPO
0xE082 Gnd Fault Blk Gnd Fault Blk
0xE084 Gnd Fault Blk DPO Gnd Fault Blk DPO
0xE0C2 Accel Blk Accel Blk
0xE0C4 Accel Block DPO Accel Block DPO
0xE182 Output Relay 1 Blk Output Relay 1 Block
0xE184 Relay 1 Blk DPO Relay 1 Block DPO
0xE1C2 Output Relay 2 Blk Output Relay 2 Block
0xE1C4 Relay 2 Blk DPO Relay 2 Block DPO
0xE202 Mech Jam Blk Mech Jam Blk
0xE204 Mech Jam Blk DPO Mech Jam Blk DPO
0xE242 U/CURR Blk U/CURR Blk
0xE244 U/CURR Blk DPO U/CURR Blk DPO
0xE282 UNBAL Blk UNBAL Blk
0xE284 UNBAL Blk DPO Unbalance Block DPO
0xE2C2 RTD1 Block RTD1 Block
0xE2C4 RTD1 Blk DPO RTD1 Blk DPO
0xE302 RTD2 Block RTD2 Block
0xE304 RTD2 Blk DPO RTD2 Blk DPO
0xE342 RTD3 Block RTD3 Block
0xE344 RTD3 Blk DPO RTD3 Blk DPO
0xE382 RTD4 Block RTD4 Block
0xE384 RTD4 Blk DPO RTD4 Blk DPO
0xE3C2 RTD5 Block RTD5 Block
0xE3C4 RTD5 Blk DPO RTD5 Blk DPO
0xE402 RTD6 Block RTD6 Block
0xE404 RTD6 Blk DPO RTD6 Blk DPO
0xE442 RTDTrouble Block RTDTrouble Block
0xE444 RTDTrouble Blk DPO RTDTrouble Blk DPO
0xE6C2 RTD7 Block RTD7 Block
0xE6C4 RTD7 Blk DPO RTD7 Blk DPO
0xE702 RTD8 Block RTD8 Block
0xE704 RTD8 Blk DPO RTD8 Blk DPO
0xE742 RTD9 Block RTD9 Block
0xE744 RTD9 Blk DPO RTD9 Blk DPO
0xE782 RTD10 Block RTD10 Block
0xE784 RTD10 Blk DPO RTD10 Blk DPO
0xE7C2 RTD11 Block RTD11 Block
0xE7C4 RTD11 Blk DPO RTD11 Blk DPO
0xE802 RTD12 Block RTD12 Block
0xE804 RTD12 Blk DPO RTD12 Blk DPO
0xE842 PosSeq UV1 Block Positive Sequence UV 1 Block

10-128 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0xE844 PosSeq UV1 BlckDPO Positive Sequence UV 1 Block DPO
0xE902 PosSeq UV2 Block Positive Sequence UV 2 Block
0xE904 PosSeq UV2 BlckDPO Positive Sequence UV 2 Block DPO
0xE9C2 CTFail Block CT Fail Block
0xE9C4 CTFail Block DPO CT Fail Block DPO
0xEAC2 Load Incr Block Load Increase Block
0xEAC4 Load Incr Blk DPO Load Increase Block DPO
0xF042 Ntrl IOC1 Block Neutral IOC 1 Block
0xF044 Ntrl IOC1 Blk DPO Neutral IOC 1 Block DPO
0xF0C2 Ph TOC1 Block Phase TOC 1 Block
0xF0C4 Ph TOC1 Block DPO Phase TOC 1 Block DPO
0xF102 Ntrl TOC1 Block Neutral TOC 1 Block
0xF104 Ntrl TOC1 BlockDPO Neutral TOC 1 Block DPO
0xF242 Dir Pwr 1 Block Directional Pwr 1 Block
0xF244 Dir Pwr 1 Blk DPO Directional Pwr 1 Block DPO
0xF282 Dir Pwr 2 Block Directional Pwr 2 Block
0xF284 Dir Pwr 2 Blk DPO Directional Pwr 2 Block DPO
0xF342 Ntrl Dir Rev Block Neutral Directional Rev Block
0xF344 Ntrl Dir Block DPO Neutral Directional Block DPO
0xF3C2 NSeq OV Block Negative Sequence OV OP
0xF3C4 NSeq OV Blk DPO Negative Sequence OV Block DPO
0xF442 Ph OV1 Block Ph OV 1 Block
0xF444 Ph OV1 Block DPO Ph OV 1 Block DPO
0xF482 Ph UV1 Block Ph UV 1 Block
0xF484 Ph UV1 Block DPO Ph UV 1 Block DPO
0xF542 UndrFreq1 Block Underfrequency 1 Block
0xF544 UndrFreq1 BlockDPO Underfrequency 1 Block DPO
0xF582 UndrFreq2 Block Underfrequency 2 Block
0xF584 UndrFreq2 BlockDPO Underfrequency 2 Block DPO
0xF5C2 OverFreq1 Block Overfrequency 1 Block
0xF5C4 OverFreq1 Blk DPO Overfrequency 1 Block DPO
0xF602 OverFreq2 Block Overfrequency 2 Block
0xF604 OverFreq2 BlockDPO Overfrequency 2 Block DPO
0xF702 Curr Dmd1 Block Current Demand 1 Block OP
0xF704 Curr Dmd1 Blk DPO Current Demand 1 Block DPO
0xF742 RealP Dmd Block Real Power Demand Block OP
0xF744 RealP Dmd Blk DPO Real Power Demand Block DPO
0xF782 ReacP Dmd Block Reactive Power Demand Block OP
0xF784 ReacP Dmd Blk DPO Reactive Power Demand Block DPO
0xF7C2 AppP Dmd Block Apparent Power Demand Block OP
0xF7C4 AppP Dmd Block DPO Apparent Power Demand Block DPO
0xF882 Ph OV2 Block Ph OV2 Block
0xF884 Ph OV2 Block DPO Ph OV2 Block DPO
0xF8C2 Ph UV2 Block Ph UV2 Block
0xF8C4 Ph UV2 Block DPO Ph UV2 Block DPO
0xF902 S/C Blk S/C Blk
0xF904 S/C Blk DPO S/C Blk DPO

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-129


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xF942 SPD2 S/C Blk SPD2 S/C Blk
0xF944 SPD2 S/C Blk DPO SPD2 S/C Blk DPO
0xF982 SPD2 U/C Block SPD2 U/C Block
0xF984 SPD2 U/C Blk DPO SPD2 U/C Blk DPO
FC134A unsigned 16 bits Active Targets
0 No Active Targets No Active Targets
7 Clock Not Set Clock Not Set
8 IRIG-B Failure IRIG-B Failure
14 Comm. Alert 1 Comm. Alert 1
15 Comm. Alert 2 Comm. Alert 2
16 Comm. Alert 3 Comm. Alert 3
17 Ethernet Link Fail Ethernet Link Failure
18 High ENET Traffic High Ethernet Traffic
19 Intern Temp. >80C Internal Temperature High
20 RMIO Mismatch RMIO Mismatch
40 Eth Link A Fail Ethernet Link A Fail
41 Eth Link B Fail Ethernet Link B Fail
0x8040 Therm O/L Trip Therm O/L Trip
0x8080 Gnd Fault Trip Gnd Fault Trip
0x80C0 Accel Trip Accel Trip
0x8140 UndrPower Trip Under Power Trip
0x8180 Single Ph Trip Single Ph Trip
0x8200 Mech Jam Trip Mech Jam Trip
0x8240 U/Curr Trip U/Curr Trip
0x8280 UNBAL Trip UNBAL Trip
0x82C0 RTD 1 Trip RTD 1 Trip
0x8300 RTD 2 Trip RTD 2 Trip
0x8340 RTD 3 Trip RTD 3 Trip
0x8380 RTD 4 Trip RTD 4 Trip
0x83C0 RTD 5 Trip RTD 5 Trip
0x8400 RTD 6 Trip RTD 6 Trip
0x8480 Relay Not Config Relay Not Config
0x84C0 LE 1 Trip Logic Element 1 Trip
0x8500 LE 2 Trip Logic Element 2 Trip
0x8540 LE 3 Trip Logic Element 3 Trip
0x8580 LE 4 Trip Logic Element 4 Trip
0x85C0 LE 5 Trip Logic Element 5 Trip
0x8600 LE 6 Trip Logic Element 6 Trip
0x8640 LE 7 Trip Logic Element 7 Trip
0x8680 LE 8 Trip Logic Element 8 Trip
0x86C0 RTD 7 Trip RTD 7 Trip
0x8700 RTD 8 Trip RTD 8 Trip
0x8740 RTD 9 Trip RTD 9 Trip
0x8780 RTD 10 Trip RTD 10 Trip
0x87C0 RTD 11 Trip RTD 11 Trip
0x8800 RTD 12 Trip RTD 12 Trip
0x8840 PosSeq UV1 Trip Positive Sequence UV 1 Trip

10-130 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x8900 PosSeq UV2 Trip Positive Sequence UV 2 Trip
0x89C0 Self Test Trip Self Test Trip
0x8D00 Rly #1 Trip OP Rly #1 Trip OP
0x8D40 Rly #2 Trip OP Rly #2 Trip OP
0x8D80 BKR Failure BKR Failure
0x8F80 Fuse Fail Trip Fuse Fail Trip
0x8FC0 Ph Revrsl Trip Phase Reversal Trip
0x9040 Ntrl IOC1 Trip Neutral IOC 1 Trip
0x90C0 Ph TOC1 Trip Phase TOC 1 Trip
0x9100 Ntrl TOC1 Trip Neutral TOC 1 Trip
0x9240 Dir Pwr 1 Trip Directional Pwr 1 Trip
0x9280 Dir Pwr 2 Trip Directional Pwr 2 Trip
0x93C0 NSeq OV Trip Negative Sequence OV Trip
0x9440 Ph OV1 Trip Phase OV 1 Trip
0x9480 Ph UV1 Trip Phase UV 1 Trip
0x9540 UndrFreq1 Trip Underfrequency 1 Trip
0x9580 UndrFreq2 Trip Underfrequency 2 Trip
0x95C0 OverFreq1 Trip Overfrequency 1 Trip
0x9600 OverFreq2 Trip Overfrequency 2 Trip
0x9880 Ph OV2 Trip Ph OV2 Trip
0x98C0 Ph UV2 Trip Ph UV2 Trip
0x9900 S/C Trip S/C Trip
0x9940 SPD2 S/C Trip SPD2 S/C Trip
0x9980 SPD2 U/C Trip SPD2 U/C Trip
0x9C00 LE 9 Trip Logic Element 9 Trip
0x9C40 LE 10 Trip Logic Element 10 Trip
0x9C80 LE 11 Trip Logic Element 11 Trip
0x9CC0 LE 12 Trip Logic Element 12 Trip
0x9D00 LE 13 Trip Logic Element 13 Trip
0x9D40 LE 14 Trip Logic Element 14 Trip
0x9D80 LE 15 Trip Logic Element 15 Trip
0x9DC0 LE 16 Trip Logic Element 16 Trip
0xA040 Therm Lvl Alrm Thermal Level Alarm
0xA080 Gnd Fault Alarm Gnd Fault Alarm
0xA0C0 Accel Alarm Accel Alarm
0xA140 Under Pwr Alarm Under Power Alarm
0xA200 Mech Jam Alarm Mech Jam Alarm
0xA240 U/Curr Alarm Under Current Alarm
0xA280 UNBAL Alarm Unbalance Alarm
0xA2C0 RTD 1 Alarm RTD 1 Alarm
0xA300 RTD 2 Alarm RTD 2 Alarm
0xA340 RTD 3 Alarm RTD 3 Alarm
0xA380 RTD 4 Alarm RTD 4 Alarm
0xA3C0 RTD 5 Alarm RTD 5 Alarm
0xA400 RTD 6 Alarm RTD 6 Alarm
0xA440 RTD Trouble Alrm RTD Trouble Alarm
0xA480 Not Configured Not Configured

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-131


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xA4C0 LE 1 Alarm Logic Element 1 Alarm
0xA500 LE 2 Alarm Logic Element 2 Alarm
0xA540 LE 3 Alarm Logic Element 3 Alarm
0xA580 LE 4 Alarm Logic Element 4 Alarm
0xA5C0 LE 5 Alarm Logic Element 5 Alarm
0xA600 LE 6 Alarm Logic Element 6 Alarm
0xA640 LE 7 Alarm Logic Element 7 Alarm
0xA680 LE 8 Alarm Logic Element 8 Alarm
0xA6C0 RTD 7 Alarm RTD 7 Alarm
0xA700 RTD 8 Alarm RTD 8 Alarm
0xA740 RTD 9 Alarm RTD 9 Alarm
0xA780 RTD 10 Alarm RTD 10 Alarm
0xA7C0 RTD 11 Alarm RTD 11 Alarm
0xA800 RTD 12 Alarm RTD 12 Alarm
0xA840 PosSeq UV1 Alrm Positive Sequence UV 1 Alarm
0xA880 BKR Alarm Breaker Alarm
0xA900 PosSeq UV2 Alrm Positive Sequence UV 2 Alarm
0xA980 Motor Running Hrs Motor Running Hrs
0xA9C0 CTFail Alrm CT Fail Alarm
0xAA00 Welded Contactr Welded Contactr
0xAA40 SPD SW Not Config SPD SW Not Config
0xAA80 SPD SW Fail SPD SW Fail
0xAAC0 Load Incr Alarm Load Incr Alarm
0xAB00 BKR Trip Time Breaker Trip Time
0xAB40 BKR Close Time Breaker Close Time
0xAB80 BKR Charge Time Breaker Charge Time
0xABC0 HI Ambient Temp High Ambient Temperature Alarm
0xAC00 LO Ambient Temp Low Ambient Temperature Alarm
0xAC40 Self Test Alarm Self Test Alarm
0xACC0 BKRTrpCntrAlrm Breaker Trip Control Alarm
0xAD00 Rly1 Coil Mn Alrm Relay # 1 Coil Monitor Alarm
0xAD40 Rly2 Coil Mn Alrm Relay # 2 Coil Monitor Alarm
0xAD80 BKR Fail Alrm BKR Fail Alrm
0xADC0 BKRStatus Fail Breaker Status Fail
0xAE80 BKR Trp/Cls Fail Breaker Trip/Close Fail
0xAEC0 BKR Charge Fail Breaker Charge Fail
0xAF80 Fuse Fail Alrm Fuse Fail Alrm
0xAFC0 Ph Revrsl Alrm Phase Reversal Alarm
0xB040 Ntrl IOC1 Alarm Neutral IOC 1 Alarm
0xB0C0 Ph TOC1 Alarm Phase TOC 1 Alarm
0xB100 Ntrl TOC1 Alrm Neutral TOC 1 Alarm
0xB240 Dir Pwr 1 Alarm Directional Pwr 1 Alarm
0xB280 Dir Pwr 2 Alarm Directional Pwr 2 Alarm
0xB3C0 NSeq OV Alarm Negative Sequence OV Alarm
0xB440 Ph OV1 Alarm Phase OV 1 Alarm
0xB480 Ph UV1 Alarm Phase UV 1 Alarm
0xB540 UndrFreq1 Alarm Underfrequency 1 Alarm

10-132 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0xB580 UndrFreq2 Alarm Underfrequency 2 Alarm
0xB5C0 OverFreq1 Alrm Overfrequency 1 Alarm
0xB600 OverFreq2 Alrm Overfrequency 2 Alarm
0xB700 Curr Dmd1 Alrm Current Demand 1 Alarm
0xB740 RealP Dmd Alrm Real Power Demand Alarm
0xB780 ReacP Dmd Alrm Reactive Power Demand Alarm
0xB7C0 AppP Dmd Alrm Apparent Power Demand Alarm
0xB880 Ph OV2 Alarm Ph OV2 Alarm
0xB8C0 Ph UV2 Alarm Ph UV2 Alarm
0xB900 S/C Alarm S/C Alarm
0xB940 SPD2 S/C Alarm SPD2 S/C Alarm
0xB980 SPD2 U/C Alarm SPD2 U/C Alarm
0xBC00 LE 9 Alarm Logic Element 9 Alarm
0xBC40 LE 10 Alarm Logic Element 10 Alarm
0xBC80 LE 11 Alarm Logic Element 11 Alarm
0xBCC0 LE 12 Alarm Logic Element 12 Alarm
0xBD00 LE 13 Alarm Logic Element 13 Alarm
0xBD40 LE 14 Alarm Logic Element 14 Alarm
0xBD80 LE 15 Alarm Logic Element 15 Alarm
0xBDC0 LE 16 Alarm Logic Element 16 Alarm
0xC040 Output Relay 3 Output Relay 3
0xC080 Output Relay 4 Output Relay 4
0xC0C0 Output Relay 5 Output Relay 5
0xC100 Output Relay 6 Output Relay 6
0xC140 Output Relay 7 Output Relay 7
0xC180 Relay1 Coil Relay # 1 Coil
0xC1C0 Relay2 Coil Relay # 2 Coil
0xC200 BKR Connected Breaker Connected
0xC240 High Speed High Speed
0xC280 Low Speed Low Speed
0xC300 Stopped Stopped
0xC340 Starting Starting
0xC380 Running Running
0xC3C0 Motor Online Motor Online
0xC400 Emergency Restart Emergency Restart
0xC440 Hot RTD Hot RTD
0xC480 Lockout Lockout
0xC4C0 LE 1 LE 1
0xC500 LE 2 LE 2
0xC540 LE 3 LE 3
0xC580 LE 4 LE 4
0xC5C0 LE 5 LE 5
0xC600 LE 6 LE 6
0xC640 LE 7 LE 7
0xC680 LE 8 LE 8
0xC900 Open BKR Open Breaker
0xC940 Close BKR Close Breaker

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-133


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xC980 Maint Required Maint Required
0xCA00 52a Contact 52a Contact
0xCA40 52b Contact 52b Contact
0xCAC0 L/O Rst Closed Lockout Reset Closed
0xCCC0 BKR Stat Open Breaker Status Open
0xCD00 BKR Stat Clsd Breaker Status Closed
0xCD80 Testing Testing
0xCE80 Therm Inhibit Therm Inhibit
0xCEC0 Restart Inhibit Restart Inhibit
0xCF00 Starts/Hr Inhib Starts/Hr Inhibit
0xCF40 T-BT-Strt Inhib T-BT-Strt Inhibit
0xCF80 Fuse Fail Inhib Fuse Fail Inhibit
0xCFC0 Ph Revrsl Inhib Phase Reversal Inhibit
0xD240 Dir Pwr 1 Directional Pwr 1
0xD280 Dir Pwr 2 Directional Pwr 2
0xD340 Ntrl Dir Rev Neutral Directional Rev
0xDC00 LE 9 LE 9
0xDC40 LE 10 LE 10
0xDC80 LE 11 LE 11
0xDCC0 LE 12 LE 12
0xDD00 LE 13 LE 13
0xDD40 LE 14 LE 14
0xDD80 LE 15 LE 15
0xDDC0 LE 16 LE 16
0xE040 Therm O/L Block Thermal Level Block
0xE080 Gnd Fault Blk Gnd Fault Blk
0xE0C0 Accel Block Accel Block
0xE180 Output Relay 1 BLK Output Relay 1 BLK
0xE1C0 Output Relay 2 BLK Output Relay 2 BLK
0xE200 Mech Jam Block Mech Jam Block
0xE240 U/Curr Block U/Curr Block
0xE280 UNBAL Block UNBAL Block
0xE2C0 RTD1 Block RTD1 Block
0xE300 RTD2 Block RTD2 Block
0xE340 RTD3 Block RTD3 Block
0xE380 RTD4 Block RTD4 Block
0xE3C0 RTD5 Block RTD5 Block
0xE400 RTD6 Block RTD6 Block
0xE440 RTD Trouble Blk RTD Trouble Blk
0xE6C0 RTD7 Block RTD7 Block
0xE700 RTD8 Block RTD8 Block
0xE740 RTD9 Block RTD9 Block
0xE780 RTD10 Block RTD10 Block
0xE7C0 RTD11 Block RTD11 Block
0xE800 RTD12 Block RTD12 Block
0xE840 PosSeq UV1 Block Positive Sequence UV 1 Block
0xE900 PosSeq UV2 Block Positive Sequence UV 2 Block

10-134 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0xE9C0 CTFail Block CT Fail Block
0xEAC0 Load Incr Block Load Increase Block
0xF040 Ntrl IOC1 Block Neutral IOC 1 Block
0xF0C0 Ph TOC1 Block Phase TOC 1 Block
0xF100 Ntrl TOC1 Block Neutral TOC 1 Block
0xF240 Dir Pwr 1 Block Directional Pwr 1 Block
0xF280 Dir Pwr 2 Block Directional Pwr 2 Block
0xF340 Ntrl Dir Rev Block Neutral Directional Block
0xF3C0 NSeq OV Block Negative Sequence OV Block
0xF440 Ph OV1 Block Phase OV 1 Block
0xF480 Ph UV1 Block Phase UV 1 Block
0xF540 UndrFreq1 Block Underfrequency 1 Block
0xF580 UndrFreq2 Block Underfrequency 2 Block
0xF5C0 OverFreq1 Block Overfrequency 1 Block
0xF600 OverFreq2 Block Overfrequency 2 Block
0xF700 Curr Dmd1 Block Current Demand 1 Block
0xF740 RealPwr Dmd Block Real Power Demand Block
0xF780 ReacPwr Dmd Block Reactive Power Demand Block
0xF7C0 AppPwr Dmd Block Apparent Power Demand Block
0xF880 Ph OV2 Block Ph OV2 Block
0xF8C0 Ph UV2 Block Ph UV2 Block
0xF900 S/C Blk S/C Blk
0xF940 SPD2 S/C Blk SPD2 S/C Blk
0xF980 SPD2 U/C Block SPD2 U/C Block
FC134B unsigned 16 bits DNP Binary Inputs
0 Off Off
0x0001 On On
0x0040 Contact IN 1 On Contact Input 1 On
0x0041 Contact IN 2 On Contact Input 2 On
0x0042 Contact IN 3 On Contact Input 3 On
0x0043 Contact IN 4 On Contact Input 4 On
0x0044 Contact IN 5 On Contact Input 5 On
0x0045 Contact IN 6 On Contact Input 6 On
0x0046 Contact IN 7 On Contact Input 7 On
0x0047 Contact IN 8 On Contact Input 8 On
0x0048 Contact IN 9 On Contact Input 9 On
0x0049 Contact IN 10 On Contact Input 10 On
0x0060 Contact IN 1 Off Contact Input 1 Off
0x0061 Contact IN 2 Off Contact Input 2 Off
0x0062 Contact IN 3 Off Contact Input 3 Off
0x0063 Contact IN 4 Off Contact Input 4 Off
0x0064 Contact IN 5 Off Contact Input 5 Off
0x0065 Contact IN 6 Off Contact Input 6 Off
0x0066 Contact IN 7 Off Contact Input 7 Off
0x0067 Contact IN 8 Off Contact Input 8 Off
0x0068 Contact IN 9 Off Contact Input 9 Off
0x0069 Contact IN 10 Off Contact Input 10 Off

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-135


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x0080 Virtual IN 1 On Virtual Input 1 On
0x0081 Virtual IN 2 On Virtual Input 2 On
0x0082 Virtual IN 3 On Virtual Input 3 On
0x0083 Virtual IN 4 On Virtual Input 4 On
0x0084 Virtual IN 5 On Virtual Input 5 On
0x0085 Virtual IN 6 On Virtual Input 6 On
0x0086 Virtual IN 7 On Virtual Input 7 On
0x0087 Virtual IN 8 On Virtual Input 8 On
0x0088 Virtual IN 9 On Virtual Input 9 On
0x0089 Virtual IN 10 On Virtual Input 10 On
0x008A Virtual IN 11 On Virtual Input 11 On
0x008B Virtual IN 12 On Virtual Input 12 On
0x008C Virtual IN 13 On Virtual Input 13 On
0x008D Virtual IN 14 On Virtual Input 14 On
0x008E Virtual IN 15 On Virtual Input 15 On
0x008F Virtual IN 16 On Virtual Input 16 On
0x0090 Virtual IN 17 On Virtual Input 17 On
0x0091 Virtual IN 18 On Virtual Input 18 On
0x0092 Virtual IN 19 On Virtual Input 19 On
0x0093 Virtual IN 20 On Virtual Input 20 On
0x0094 Virtual IN 21 On Virtual Input 21 On
0x0095 Virtual IN 22 On Virtual Input 22 On
0x0096 Virtual IN 23 On Virtual Input 23 On
0x0097 Virtual IN 24 On Virtual Input 24 On
0x0098 Virtual IN 25 On Virtual Input 25 On
0x0099 Virtual IN 26 On Virtual Input 26 On
0x009A Virtual IN 27 On Virtual Input 27 On
0x009B Virtual IN 28 On Virtual Input 28 On
0x009C Virtual IN 29 On Virtual Input 29 On
0x009D Virtual IN 30 On Virtual Input 30 On
0x009E Virtual IN 31 On Virtual Input 31 On
0x009F Virtual IN 32 On Virtual Input 32 On
0x01C0 Remote IN 1 On Remote Input 1 On
0x01C1 Remote IN 2 On Remote Input 2 On
0x01C2 Remote IN 3 On Remote Input 3 On
0x01C3 Remote IN 4 On Remote Input 4 On
0x01C4 Remote IN 5 On Remote Input 5 On
0x01C5 Remote IN 6 On Remote Input 6 On
0x01C6 Remote IN 7 On Remote Input 7 On
0x01C7 Remote IN 8 On Remote Input 8 On
0x01C8 Remote IN 9 On Remote Input 9 On
0x01C9 Remote IN 10 On Remote Input 10 On
0x01CA Remote IN 11 On Remote Input 11 On
0x01CB Remote IN 12 On Remote Input 12 On
0x01CC Remote IN 13 On Remote Input 13 On
0x01CD Remote IN 14 On Remote Input 14 On
0x01CE Remote IN 15 On Remote Input 15 On

10-136 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x01CF Remote IN 16 On Remote Input 16 On
0x01D0 Remote IN 17 On Remote Input 17 On
0x01D1 Remote IN 18 On Remote Input 18 On
0x01D2 Remote IN 19 On Remote Input 19 On
0x01D3 Remote IN 20 On Remote Input 20 On
0x01D4 Remote IN 21 On Remote Input 21 On
0x01D5 Remote IN 22 On Remote Input 22 On
0x01D6 Remote IN 23 On Remote Input 23 On
0x01D7 Remote IN 24 On Remote Input 24 On
0x01D8 Remote IN 25 On Remote Input 25 On
0x01D9 Remote IN 26 On Remote Input 26 On
0x01DA Remote IN 27 On Remote Input 27 On
0x01DB Remote IN 28 On Remote Input 28 On
0x01DC Remote IN 29 On Remote Input 29 On
0x01DD Remote IN 30 On Remote Input 30 On
0x01DE Remote IN 31 On Remote Input 31 On
0x01DF Remote IN 32 On Remote Input 32 On
0x01E0 Remote IN 1 Off Remote Input 1 Off
0x01E1 Remote IN 2 Off Remote Input 2 Off
0x01E2 Remote IN 3 Off Remote Input 3 Off
0x01E3 Remote IN 4 Off Remote Input 4 Off
0x01E4 Remote IN 5 Off Remote Input 5 Off
0x01E5 Remote IN 6 Off Remote Input 6 Off
0x01E6 Remote IN 7 Off Remote Input 7 Off
0x01E7 Remote IN 8 Off Remote Input 8 Off
0x01E8 Remote IN 9 Off Remote Input 9 Off
0x01E9 Remote IN 10 Off Remote Input 10 Off
0x01EA Remote IN 11 Off Remote Input 11 Off
0x01EB Remote IN 12 Off Remote Input 12 Off
0x01EC Remote IN 13 Off Remote Input 13 Off
0x01ED Remote IN 14 Off Remote Input 14 Off
0x01EE Remote IN 15 Off Remote Input 15 Off
0x01EF Remote IN 16 Off Remote Input 16 Off
0x01F0 Remote IN 17 Off Remote Input 17 Off
0x01F1 Remote IN 18 Off Remote Input 18 Off
0x01F2 Remote IN 19 Off Remote Input 19 Off
0x01F3 Remote IN 20 Off Remote Input 20 Off
0x01F4 Remote IN 21 Off Remote Input 21 Off
0x01F5 Remote IN 22 Off Remote Input 22 Off
0x01F6 Remote IN 23 Off Remote Input 23 Off
0x01F7 Remote IN 24 Off Remote Input 24 Off
0x01F8 Remote IN 25 Off Remote Input 25 Off
0x01F9 Remote IN 26 Off Remote Input 26 Off
0x01FA Remote IN 27 Off Remote Input 27 Off
0x01FB Remote IN 28 Off Remote Input 28 Off
0x01FC Remote IN 29 Off Remote Input 29 Off
0x01FD Remote IN 30 Off Remote Input 30 Off

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-137


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x01FE Remote IN 31 Off Remote Input 31 Off
0x01FF Remote IN 32 Off Remote Input 32 Off
0x8002 Any Trip Any Trip
0x8041 Therm O/L Trip PKP Thermal Overload Trip PKP
0x8042 Therm O/L Trip OP Thermal Overload Trip OP
0x8044 Therm O/L Trip DPO Thermal Overload Trip DPO
0x8081 GF Trip PKP GF Trip PKP
0x8082 GF Trip OP GF Trip OP
0x8084 GF Trip DPO GF Trip DPO
0x80C2 Accel Trip OP Acceleration Trip OP
0x8141 Under Pwr Trip PKP Under Power Trip PKP
0x8142 Under Pwr Trip OP Under Power Trip OP
0x8144 Under Pwr Trip DPO Under Power Trip DPO
0x8181 Single PH Trip PKP Single PH Trip PKP
0x8182 Single PH Trip OP Single PH Trip OP
0x8184 Single PH Trip DPO Single PH Trip DPO
0x8201 Mech Jam Trip PKP Mech Jam Trip PKP
0x8202 Mech Jam Trip OP Mech Jam Trip OP
0x8204 Mech Jam Trip DPO Mech Jam Trip DPO
0x8241 U/CURR Trip PKP U/CURR Trip PKP
0x8242 U/CURR Trip OP U/CURR Trip OP
0x8244 U/CURR Trip DPO U/CURR Trip DPO
0x8281 UNBAL Trip PKP Unbalance Trip PKP
0x8282 UNBAL Trip OP Unbalance Trip OP
0x8284 UNBAL Trip DPO Unbalance Trip DPO
0x82C1 RTD 1 Trip PKP RTD 1 Trip PKP
0x82C2 RTD 1 Trip OP RTD 1 Trip OP
0x8301 RTD 2 Trip PKP RTD 2 Trip PKP
0x8302 RTD 2 Trip OP RTD 2 Trip OP
0x8341 RTD 3 Trip PKP RTD 3 Trip PKP
0x8342 RTD 3 Trip OP RTD 3 Trip OP
0x8381 RTD 4 Trip PKP RTD 4 Trip PKP
0x8382 RTD 4 Trip OP RTD 4 Trip OP
0x83C1 RTD 5 Trip PKP RTD 5 Trip PKP
0x83C2 RTD 5 Trip OP RTD 5 Trip OP
0x8401 RTD 6 Trip PKP RTD 6 Trip PKP
0x8402 RTD 6 Trip OP RTD 6 Trip OP
0x84C1 LE 1 Trip PKP Logic Element 1 Trip PKP
0x84C2 LE 1 Trip OP Logic Element 1 Trip OP
0x84C4 LE 1 Trip DPO Logic Element 1 Trip DPO
0x8501 LE 2 Trip PKP Logic Element 2 Trip PKP
0x8502 LE 2 Trip OP Logic Element 2 Trip OP
0x8504 LE 2 Trip DPO Logic Element 2 Trip DPO
0x8541 LE 3 Trip PKP Logic Element 3 Trip PKP
0x8542 LE 3 Trip OP Logic Element 3 Trip OP
0x8544 LE 3 Trip DPO Logic Element 3 Trip DPO
0x8581 LE 4 Trip PKP Logic Element 4 Trip PKP

10-138 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x8582 LE 4 Trip OP Logic Element 4 Trip OP
0x8584 LE 4 Trip DPO Logic Element 4 Trip DPO
0x85C1 LE 5 Trip PKP Logic Element 5 Trip PKP
0x85C2 LE 5 Trip OP Logic Element 5 Trip OP
0x85C4 LE 5 Trip DPO Logic Element 5 Trip DPO
0x8601 LE 6 Trip PKP Logic Element 6 Trip PKP
0x8602 LE 6 Trip OP Logic Element 6 Trip OP
0x8604 LE 6 Trip DPO Logic Element 6 Trip DPO
0x8641 LE 7 Trip PKP Logic Element 7 Trip PKP
0x8642 LE 7 Trip OP Logic Element 7 Trip OP
0x8644 LE 7 Trip DPO Logic Element 7 Trip DPO
0x8681 LE 8 Trip PKP Logic Element 8 Trip PKP
0x8682 LE 8 Trip OP Logic Element 8 Trip OP
0x8684 LE 8 Trip DPO Logic Element 8 Trip DPO
0x86C1 RTD 7 Trip PKP RTD 7 Trip PKP
0x86C2 RTD 7 Trip OP RTD 7 Trip OP
0x8701 RTD 8 Trip PKP RTD 8 Trip PKP
0x8702 RTD 8 Trip OP RTD 8 Trip OP
0x8741 RTD 9 Trip PKP RTD 9 Trip PKP
0x8742 RTD 9 Trip OP RTD 9 Trip OP
0x8781 RTD 10 Trip PKP RTD 10 Trip PKP
0x8782 RTD 10 Trip OP RTD 10 Trip OP
0x87C1 RTD 11 Trip PKP RTD 11 Trip PKP
0x87C2 RTD 11 Trip OP RTD 11 Trip OP
0x8801 RTD 12 Trip PKP RTD 12 Trip PKP
0x8802 RTD 12 Trip OP RTD 12 Trip OP
0x8841 PosSeq UV1 Trp PKP Positive Sequence UV 1 Trp PKP
0x8842 PosSeq UV1 Trip OP Positive Sequence UV 1 Trip OP
0x8844 PosSeq UV1 Trp DPO Positive Sequence UV 1 Trp DPO
0x8901 PosSeq UV2 Trp PKP Positive Sequence UV 2 Trp PKP
0x8902 PosSeq UV2 Trip OP Positive Sequence UV 2 Trip OP
0x8904 PosSeq UV2 Trp DPO Positive Sequence UV 2 Trp DPO
0x89C2 Self Test OP Self Test OP
0x8F81 Fuse Fail Trip PKP Fuse Fail Trip PKP
0x8F82 Fuse Fail Trip OP Fuse Fail Trip OP
0x8F84 Fuse Fail Trip DPO Fuse Fail Trip DPO
0x8FC1 Ph Revrsl Trip PKP Ph Revrsl Trip PKP
0x8FC2 Ph Revrsl Trip OP Ph Revrsl Trip OP
0x8FC4 Ph Revrsl Trip DPO Ph Revrsl Trip DPO
0x9041 Ntrl IOC1 Trip PKP Neutral IOC 1 Trip PKP
0x9042 Ntrl IOC1 Trip OP Neutral IOC 1 Trip OP
0x9044 Ntrl IOC1 Trip DPO Neutral IOC 1 Trip DPO
0x90C1 Ph TOC1 Trip PKP Phase TOC 1 Trip PKP
0x90C2 Ph TOC1 Trip OP Phase TOC 1 Trip OP
0x90C4 Ph TOC1 Trip DPO Phase TOC 1 Trip DPO
0x90C9 Ph A TOC1 Trip PKP Phase A TOC 1 Trip PKP
0x90CA Ph A TOC1 Trip OP Phase A TOC 1 Trip OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-139


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x90CC Ph A TOC1 Trip DPO Phase A TOC 1 Trip DPO
0x90D1 Ph B TOC1 Trip PKP Phase B TOC 1 Trip PKP
0x90D2 Ph B TOC1 Trip OP Phase B TOC 1 Trip OP
0x90D4 Ph B TOC1 Trip DPO Phase B TOC 1 Trip DPO
0x90E1 Ph C TOC1 Trip PKP Phase C TOC 1 Trip PKP
0x90E2 Ph C TOC1 Trip OP Phase C TOC 1 Trip OP
0x90E4 Ph C TOC1 Trip DPO Phase C TOC 1 Trip DPO
0x9101 Ntrl TOC1 Trip PKP Neutral TOC 1 Trip PKP
0x9102 Ntrl TOC1 Trip OP Neutral TOC 1 Trip OP
0x9104 Ntrl TOC1 Trip DPO Neutral TOC 1 Trip DPO
0x9241 Dir Pwr 1 Trip PKP Directional Pwr 1 Trip PKP
0x9242 Dir Pwr 1 Trip OP Directional Pwr 1 Trip OP
0x9281 Dir Pwr 2 Trip PKP Directional Pwr 2 Trip PKP
0x9282 Dir Pwr 2 Trip OP Directional Pwr 2 Trip OP
0x93C1 NSeq OV Trp PKP Negative Sequence OV Trip PKP
0x93C2 NSeq OV Trp OP Negative Sequence OV Trip OP
0x93C4 NSeq OV Trp DPO Negative Sequence OV Trip DPO
0x9441 Ph OV1 Trip PKP Phase OV1 Trip PKP
0x9442 Ph OV1 Trip OP Phase OV 1 Trip OP
0x9444 Ph OV1 Trip DPO Phase OV1 Trip DPO
0x9449 Ph A OV1 Trip PKP Phase A OV1 Trip PKP
0x944A Ph A OV1 Trip OP Phase A OV1 Trip OP
0x944C Ph A OV1 Trip DPO Phase A OV1 Trip DPO
0x9451 Ph B OV1 Trip PKP Phase B OV1 Trip PKP
0x9452 Ph B OV1 Trip OP Phase B OV1 Trip OP
0x9454 Ph B OV1 Trip DPO Phase B OV1 Trip DPO
0x9461 Ph C OV1 Trip PKP Phase C OV1 Trip PKP
0x9462 Ph C OV1 Trip OP Phase C OV1 Trip OP
0x9464 Ph C OV1 Trip DPO Phase C OV1 Trip DPO
0x9481 Ph UV1 Trip PKP Phase UV1 Trip PKP
0x9482 Ph UV1 Trip OP Phase UV 1 Trip OP
0x9484 Ph UV1 Trip DPO Phase UV1 Trip DPO
0x9489 Ph A UV1 Trip PKP Phase A UV1 Trip PKP
0x948A Ph A UV1 Trip OP Phase A UV1 Trip OP
0x948C Ph A UV1 Trip DPO Phase A UV1 Trip DPO
0x9491 Ph B UV1 Trip PKP Phase B UV1 Trip PKP
0x9492 Ph B UV1 Trip OP Phase B UV1 Trip OP
0x9494 Ph B UV1 Trip DPO Phase B UV1 Trip DPO
0x94A1 Ph C UV1 Trip PKP Phase C UV1 Trip PKP
0x94A2 Ph C UV1 Trip OP Phase C UV1 Trip OP
0x94A4 Ph C UV1 Trip DPO Phase C UV1 Trip DPO
0x9541 UndrFreq1 Trip PKP Underfrequency 1 Trip PKP
0x9542 UndrFreq1 Trip OP Underfrequency 1 Trip OP
0x9544 UndrFreq1 Trip DPO Underfrequency 1 Trip DPO
0x9581 UndrFreq2 Trip PKP Underfrequency 2 Trip PKP
0x9582 UndrFreq2 Trip OP Underfrequency 2 Trip OP
0x9584 UndrFreq2 Trip DPO Underfrequency 2 Trip DPO

10-140 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x95C1 OverFreq1 Trip PKP Overfrequency 1 Trip PKP
0x95C2 OverFreq1 Trip OP Overfrequency 1 Trip OP
0x95C4 OverFreq1 Trip DPO Overfrequency 1 Trip DPO
0x9601 OverFreq2 Trip PKP Overfrequency 2 Trip PKP
0x9602 OverFreq2 Trip OP Overfrequency 2 Trip OP
0x9604 OverFreq2 Trip DPO Overfrequency 2 Trip DPO
0x9881 Ph OV2 Trip PKP Phase OV 2 Trip PKP
0x9882 Ph OV2 Trip OP Phase OV 2 Trip OP
0x9884 Ph OV2 Trip DPO Phase OV 2 Trip DPO
0x9889 Ph A OV2 Trip PKP Phase A OV2 Trip PKP
0x988A Ph A OV2 Trip OP Phase A OV2 Trip OP
0x988C Ph A OV2 Trip DPO Phase A OV2 Trip DPO
0x9891 Ph B OV2 Trip PKP Phase B OV2 Trip PKP
0x9892 Ph B OV2 Trip OP Phase B OV2 Trip OP
0x9894 Ph B OV2 Trip DPO Phase B OV2 Trip DPO
0x98A1 Ph C OV2 Trip PKP Phase C OV2 Trip PKP
0x98A2 Ph C OV2 Trip OP Phase C OV2 Trip OP
0x98A4 Ph C OV2 Trip DPO Phase C OV2 Trip DPO
0x98C1 Ph UV2 Trip PKP Phase UV 2 Trip PKP
0x98C2 Ph UV2 Trip OP Phase UV 2 Trip OP
0x98C4 Ph UV2 Trip DPO Phase UV 2 Trip DPO
0x98C9 Ph A UV2 Trip PKP Phase A UV2 Trip PKP
0x98CA Ph A UV2 Trip OP Phase A UV2 Trip OP
0x98CC Ph A UV2 Trip DPO Phase A UV2 Trip DPO
0x98D1 Ph B UV2 Trip PKP Phase B UV2 Trip PKP
0x98D2 Ph B UV2 Trip OP Phase B UV2 Trip OP
0x98D4 Ph B UV2 Trip DPO Phase B UV2 Trip DPO
0x98E1 Ph C UV2 Trip PKP Phase C UV2 Trip PKP
0x98E2 Ph C UV2 Trip OP Phase C UV2 Trip OP
0x98E4 Ph C UV2 Trip DPO Phase C UV2 Trip DPO
0x9901 S/C Trip PKP S/C Trip PKP
0x9902 S/C Trip OP S/C Trip OP
0x9904 S/C Trip DPO S/C Trip DPO
0x9941 SPD2 S/C Trip PKP SPD2 S/C Trip PKP
0x9942 SPD2 S/C Trip OP SPD2 S/C Trip OP
0x9944 SPD2 S/C Trip DPO SPD2 S/C Trip DPO
0x9981 SPD2 U/C Trip PKP SPD2 U/C Trip PKP
0x9982 SPD2 U/C Trip OP SPD2 U/C Trip OP
0x9984 SPD2 U/C Trip DPO SPD2 U/C Trip DPO
0x9C01 LE 9 Trip PKP Logic Element 9 Trip PKP
0x9C02 LE 9 Trip OP Logic Element 9 Trip OP
0x9C04 LE 9 Trip DPO Logic Element 9 Trip DPO
0x9C41 LE 10 Trip PKP Logic Element 10 Trip PKP
0x9C42 LE 10 Trip OP Logic Element 10 Trip OP
0x9C44 LE 10 Trip DPO Logic Element 10 Trip DPO
0x9C81 LE 11 Trip PKP Logic Element 11 Trip PKP
0x9C82 LE 11 Trip OP Logic Element 11 Trip OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-141


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x9C84 LE 11 Trip DPO Logic Element 11 Trip DPO
0x9CC1 LE 12 Trip PKP Logic Element 12 Trip PKP
0x9CC2 LE 12 Trip OP Logic Element 12 Trip OP
0x9CC4 LE 12 Trip DPO Logic Element 12 Trip DPO
0x9D01 LE 13 Trip PKP Logic Element 13 Trip PKP
0x9D02 LE 13 Trip OP Logic Element 13 Trip OP
0x9D04 LE 13 Trip DPO Logic Element 13 Trip DPO
0x9D41 LE 14 Trip PKP Logic Element 14 Trip PKP
0x9D42 LE 14 Trip OP Logic Element 14 Trip OP
0x9D44 LE 14 Trip DPO Logic Element 14 Trip DPO
0x9D81 LE 15 Trip PKP Logic Element 15 Trip PKP
0x9D82 LE 15 Trip OP Logic Element 15 Trip OP
0x9D84 LE 15 Trip DPO Logic Element 15 Trip DPO
0x9DC1 LE 16 Trip PKP Logic Element 16 Trip PKP
0x9DC2 LE 16 Trip OP Logic Element 16 Trip OP
0x9DC4 LE 16 Trip DPO Logic Element 16 Trip DPO
0xA002 Any Alarm Any Alarm
0xA042 Therm Lvl Alrm OP Thermal Level Alarm OP
0xA044 Therm Lvl Alrm DPO Thermal Level Alarm DPO
0xA081 Gnd Fault Alrm PKP Ground Fault Alarm PKP
0xA082 Gnd Fault Alrm OP Ground Fault Alarm OP
0xA084 Gnd Fault Alrm DPO Ground Fault Alarm DPO
0xA0C2 Accel Alarm OP Accel Alarm OP
0xA141 Under Pwr Alrm PKP Under Power Alarm PKP
0xA142 Under Pwr Alrm OP Under Power Alarm OP
0xA144 Under Pwr Alrm DPO Under Power Alarm DPO
0xA201 Mech Jam Alarm PKP Mech Jam Alarm PKP
0xA202 Mech Jam Alarm OP Mech Jam Alarm OP
0xA204 Mech Jam Alarm DPO Mech Jam Alarm DPO
0xA241 U/CURR Alarm PKP U/CURR Alarm PKP
0xA242 U/CURR Alarm OP U/CURR Alarm OP
0xA244 U/CURR Alarm DPO U/CURR Alarm DPO
0xA281 UNBAL Alarm PKP Unbalance Alarm PKP
0xA282 UNBAL Alarm OP Unbalance Alarm OP
0xA284 UNBAL Alarm DPO Unbalance Alarm DPO
0xA2C1 RTD 1 Alarm PKP RTD 1 Alarm PKP
0xA2C2 RTD 1 Alarm OP RTD 1 Alarm OP
0xA301 RTD 2 Alarm PKP RTD 2 Alarm PKP
0xA302 RTD 2 Alarm OP RTD 2 Alarm OP
0xA341 RTD 3 Alarm PKP RTD 3 Alarm PKP
0xA342 RTD 3 Alarm OP RTD 3 Alarm OP
0xA381 RTD 4 Alarm PKP RTD 4 Alarm PKP
0xA382 RTD 4 Alarm OP RTD 4 Alarm OP
0xA3C1 RTD 5 Alarm PKP RTD 5 Alarm PKP
0xA3C2 RTD 5 Alarm OP RTD 5 Alarm OP
0xA401 RTD 6 Alarm PKP RTD 6 Alarm PKP
0xA402 RTD 6 Alarm OP RTD 6 Alarm OP

10-142 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0xA442 RTD Trouble Alr OP RTD Trouble Alarm
0xA4C1 LE 1 Alarm PKP Logic Element 1 Alarm PKP
0xA4C2 LE 1 Alarm OP Logic Element 1 Alarm OP
0xA4C4 LE 1 Alarm DPO Logic Element 1 Alarm DPO
0xA501 LE 2 Alarm PKP Logic Element 2 Alarm PKP
0xA502 LE 2 Alarm OP Logic Element 2 Alarm OP
0xA504 LE 2 Alarm DPO Logic Element 2 Alarm DPO
0xA541 LE 3 Alarm PKP Logic Element 3 Alarm PKP
0xA542 LE 3 Alarm OP Logic Element 3 Alarm OP
0xA544 LE 3 Alarm DPO Logic Element 3 Alarm DPO
0xA581 LE 4 Alarm PKP Logic Element 4 Alarm PKP
0xA582 LE 4 Alarm OP Logic Element 4 Alarm OP
0xA584 LE 4 Alarm DPO Logic Element 4 Alarm DPO
0xA5C1 LE 5 Alarm PKP Logic Element 5 Alarm PKP
0xA5C2 LE 5 Alarm OP Logic Element 5 Alarm OP
0xA5C4 LE 5 Alarm DPO Logic Element 5 Alarm DPO
0xA601 LE 6 Alarm PKP Logic Element 6 Alarm PKP
0xA602 LE 6 Alarm OP Logic Element 6 Alarm OP
0xA604 LE 6 Alarm DPO Logic Element 6 Alarm DPO
0xA641 LE 7 Alarm PKP Logic Element 7 Alarm PKP
0xA642 LE 7 Alarm OP Logic Element 7 Alarm OP
0xA644 LE 7 Alarm DPO Logic Element 7 Alarm DPO
0xA681 LE 8 Alarm PKP Logic Element 8 Alarm PKP
0xA682 LE 8 Alarm OP Logic Element 8 Alarm OP
0xA684 LE 8 Alarm DPO Logic Element 8 Alarm DPO
0xA6C1 RTD 7 Alarm PKP RTD 7 Alarm PKP
0xA6C2 RTD 7 Alarm OP RTD 7 Alarm OP
0xA701 RTD 8 Alarm PKP RTD 8 Alarm PKP
0xA702 RTD 8 Alarm OP RTD 8 Alarm OP
0xA741 RTD 9 Alarm PKP RTD 9 Alarm PKP
0xA742 RTD 9 Alarm OP RTD 9 Alarm OP
0xA781 RTD 10 Alarm PKP RTD 10 Alarm PKP
0xA782 RTD 10 Alarm OP RTD 10 Alarm OP
0xA7C1 RTD 11 Alarm PKP RTD 11 Alarm PKP
0xA7C2 RTD 11 Alarm OP RTD 11 Alarm OP
0xA801 RTD 12 Alarm PKP RTD 12 Alarm PKP
0xA802 RTD 12 Alarm OP RTD 12 Alarm OP
0xA841 PosSeq UV1 AlrmPKP Positive Sequence UV 1 Alarm PKP
0xA842 PosSeq UV1 Alrm OP Positive Sequence UV 1 Alarm OP
0xA844 PosSeq UV1 AlrmDPO Positive Sequence UV 1 Alarm DPO
0xA882 BKR Alarm Breaker Alarm
0xA901 PosSeq UV2 AlrmPKP Positive Sequence UV 2 Alarm PKP
0xA902 PosSeq UV2 Alrm OP Positive Sequence UV 2 Alarm OP
0xA904 PosSeq UV2 AlrmDPO Positive Sequence UV 2 Alarm DPO
0xA982 Motor Run Hrs OP Motor Running Hours OP
0xA9C1 CTFail Alrm PKP CT Fail Alarm PKP
0xA9C2 CTFail Alrm OP CT Fail Alarm OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-143


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xA9C4 CTFail Alrm DPO CT Fail Alarm DPO
0xAA01 Welded ContactrPKP Welded ContactrPKP
0xAA02 Welded Contactr OP Welded Contactr OP
0xAA04 Welded ContactrDPO Welded ContactrDPO
0xAA42 SPD SW Not Cnfg OP SPD SW Not Cnfg OP
0xAA82 SPD SW Fail OP SPD SW Fail OP
0xAAC1 Load Incr Alrm PKP Load Incr Alrm PKP
0xAAC2 Load Incr Alrm OP Load Incr Alrm OP
0xAAC4 Load Incr Alrm DPO Load Incr Alrm DPO
0xAB02 BKR Trip Time Breaker Trip Time
0xAB42 BKR Close Time Breaker Close Time
0xAB82 BKR Charge Time Breaker Charge Time
0xABC1 HI Amb Temp PKP High Ambient Temperature Alarm PKP
0xABC2 HI Amb Temp OP High Ambient Temperature Alarm
0xABC4 HI Amb Temp DPO High Ambient Temperature Alarm DPO
0xAC01 LO Amb Temp PKP Low Ambient Temperature Alarm PKP
0xAC02 LO Amb Temp OP Low Ambient Temperature Alarm
0xAC04 LO Amb Temp DPO Low Ambient Temperature Alarm DPO
0xAC42 Self Test Alarm OP Self Test Alarm OP
0xACC2 BKRTrpCntrAlrm OP Breaker Trip Control Alarm OP
0xAD02 R1 CoilMonAlrm OP Trip Coil Monitor Alarm OP
0xAD42 R2 CoilMonAlrm OP Close Coil Monitor Alarm OP
0xAD81 BKR Fail Alrm PKP Breaker Fail Alarm PKP
0xAD82 BKR Fail Alrm OP Breaker Fail Alarm OP
0xADC2 BKR Stat Fail OP Breaker Status Fail OP
0xAE82 BKR Trp/Cls Fail Breaker Trip/Close Fail
0xAEC2 BKR Charge Fail Breaker Charge Fail
0xAF81 Fuse Fail Alrm PKP Fuse Fail Alarm PKP
0xAF82 Fuse Fail Alrm OP Fuse Fail Alarm OP
0xAF84 Fuse Fail Alrm DPO Fuse Fail Alarm DPO
0xAFC1 Ph Revrsl Alrm PKP Ph Reversal Alarm PKP
0xAFC2 Ph Revrsl Alarm OP Ph Reversal Alarm OP
0xAFC4 Ph Revrsl Alrm DPO Ph Reversal Alarm DPO
0xB041 Ntrl IOC1 Alrm PKP Neutral IOC 1 Alarm PKP
0xB042 Ntrl IOC1 Alrm OP Neutral IOC 1 Alarm OP
0xB044 Ntrl IOC1 Alrm DPO Neutral IOC 1 Alarm DPO
0xB0C1 Ph TOC1 Alarm PKP Phase TOC 1 Alarm PKP
0xB0C2 Ph TOC1 Alarm OP Phase TOC 1 Alarm OP
0xB0C4 Ph TOC1 Alarm DPO Phase TOC 1 Alarm DPO
0xB0C9 Ph A TOC1 Alrm PKP Phase A TOC 1 Alarm PKP
0xB0CA Ph A TOC1 Alrm OP Phase A TOC 1 Alarm OP
0xB0CC Ph A TOC1 Alrm DPO Phase A TOC 1 Alarm DPO
0xB0D1 Ph B TOC1 Alrm PKP Phase B TOC 1 Alarm PKP
0xB0D2 Ph B TOC1 Alrm OP Phase B TOC 1 Alarm OP
0xB0D4 Ph B TOC1 Alrm DPO Phase B TOC 1 Alarm DPO
0xB0E1 Ph C TOC1 Alrm PKP Phase C TOC 1 Alarm PKP
0xB0E2 Ph C TOC1 Alrm OP Phase C TOC 1 Alarm OP

10-144 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0xB0E4 Ph C TOC1 Alrm DPO Phase C TOC 1 Alarm DPO
0xB101 Ntrl TOC1 Alrm PKP Neutral TOC 1 Alarm PKP
0xB102 Ntrl TOC1 Alrm OP Neutral TOC 1 Alarm OP
0xB104 Ntrl TOC1 Alrm DPO Neutral TOC 1 Alarm DPO
0xB241 Dir Pwr 1 Alrm PKP Directional Pwr 1 Alarm PKP
0xB242 Dir Pwr 1 Alarm OP Directional Pwr 1 Alarm OP
0xB281 Dir Pwr 2 Alrm PKP Directional Pwr 2 Alarm PKP
0xB282 Dir Pwr 2 Alarm OP Directional Pwr 2 Alarm OP
0xB342 NtrlDir RevAlm OP Neutral Directional Alarm OP
0xB344 NtrlDir RevAlmDPO Neutral Directional Reverse Alarm DPO
0xB3C1 NSeq OV Alrm PKP Negative Sequence OV Alarm PKP
0xB3C2 NSeq OV Alrm OP Negative Sequence OV Alarm OP
0xB3C4 NSeq OV Alrm DPO Negative Sequence OV Alarm DPO
0xB441 Ph OV1 Alarm PKP Phase OV1 Alarm PKP
0xB442 Ph OV1 Alarm OP Phase OV 1 Alarm OP
0xB444 Ph OV1 Alarm DPO Phase OV1 Alarm DPO
0xB449 Ph A OV1 Alarm PKP Phase A OV1 Alarm PKP
0xB44A Ph A OV1 Alarm OP Phase A OV1 Alarm OP
0xB44C Ph A OV1 Alarm DPO Phase A OV1 Alarm DPO
0xB451 Ph B OV1 Alarm PKP Phase B OV1 Alarm PKP
0xB452 Ph B OV1 Alarm OP Phase B OV1 Alarm OP
0xB454 Ph B OV1 Alarm DPO Phase B OV1 Alarm DPO
0xB461 Ph C OV1 Alarm PKP Phase C OV1 Alarm PKP
0xB462 Ph C OV1 Alarm OP Phase C OV1 Alarm OP
0xB464 Ph C OV1 Alarm DPO Phase C OV1 Alarm DPO
0xB481 Ph UV1 Alarm PKP Phase UV1 Alarm PKP
0xB482 Ph UV1 Alarm OP Phase UV 1 Alarm OP
0xB484 Ph UV1 Alarm DPO Phase UV1 Alarm DPO
0xB489 Ph A UV1 Alarm PKP Phase A UV1 Alarm PKP
0xB48A Ph A UV1 Alarm OP Phase A UV1 Alarm OP
0xB48C Ph A UV1 Alarm DPO Phase A UV1 Alarm DPO
0xB491 Ph B UV1 Alarm PKP Phase B UV1 Alarm PKP
0xB492 Ph B UV1 Alarm OP Phase B UV1 Alarm OP
0xB494 Ph B UV1 Alarm DPO Phase B UV1 Alarm DPO
0xB4A1 Ph C UV1 Alarm PKP Phase C UV1 Alarm PKP
0xB4A2 Ph C UV1 Alarm OP Phase C UV1 Alarm OP
0xB4A4 Ph C UV1 Alarm DPO Phase C UV1 Alarm DPO
0xB541 UndrFreq1 Alrm PKP Underfrequency 1 Alarm PKP
0xB542 UndrFreq1 Alrm OP Underfrequency 1 Alarm OP
0xB544 UndrFreq1 Alrm DPO Underfrequency 1 Alarm DPO
0xB581 UndrFreq2 Alrm PKP Underfrequency 2 Alarm PKP
0xB582 UndrFreq2 Alrm OP Underfrequency 2 Alarm OP
0xB584 UndrFreq2 Alrm DPO Underfrequency 2 Alarm DPO
0xB5C1 OverFreq1 Alrm PKP Overfrequency 1 Alarm PKP
0xB5C2 OverFreq1 Alrm OP Overfrequency 1 Alarm OP
0xB5C4 OverFreq1 Alrm DPO Overfrequency 1 Alarm DPO
0xB601 OverFreq2 Alrm PKP Overfrequency 2 Alarm PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-145


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xB602 OverFreq2 Alrm OP Overfrequency 2 Alarm OP
0xB604 OverFreq2 Alrm DPO Overfrequency 2 Alarm DPO
0xB702 Curr Dmd1 Alrm OP Current Demand 1 Alarm OP
0xB70A C Dmd1 PhA Alrm OP Current Demand 1 PhA Alarm OP
0xB712 C Dmd1 PhB Alrm OP Current Demand 1 PhB Alarm OP
0xB722 C Dmd1 PhC Alrm OP Current Demand 1 PhC Alarm OP
0xB742 RealP Dmd Alrm OP Real Power Demand Alarm OP
0xB782 ReacP Dmd Alrm OP Reactive Power Demand Alarm OP
0xB7C2 AppP Dmd Alrm OP Apparent Power Demand Alarm OP
0xB881 Ph OV2 Alarm PKP Phase OV 2 Alarm PKP
0xB882 Ph OV2 Alarm OP Phase OV 2 Alarm OP
0xB884 Ph OV2 Alarm DPO Phase OV 2 Alarm DPO
0xB889 Ph A OV2 Alarm PKP Ph A OV2 Alarm PKP
0xB88A Ph A OV2 Alarm OP Ph A OV2 Alarm OP
0xB88C Ph A OV2 Alarm DPO Ph A OV2 Alarm DPO
0xB891 Ph B OV2 Alarm PKP Ph B OV2 Alarm PKP
0xB892 Ph B OV2 Alarm OP Ph B OV2 Alarm OP
0xB894 Ph B OV2 Alarm DPO Ph B OV2 Alarm DPO
0xB8A1 Ph C OV2 Alarm PKP Ph C OV2 Alarm PKP
0xB8A2 Ph C OV2 Alarm OP Ph C OV2 Alarm OP
0xB8A4 Ph C OV2 Alarm DPO Ph C OV2 Alarm DPO
0xB8C1 Ph UV2 Alarm PKP Phase UV 2 Alarm PKP
0xB8C2 Ph UV2 Alarm OP Phase UV 2 Alarm OP
0xB8C4 Ph UV2 Alarm DPO Phase UV 2 Alarm DPO
0xB8C9 Ph A UV2 Alarm PKP Ph A UV2 Alarm PKP
0xB8CA Ph A UV2 Alarm OP Ph A UV2 Alarm OP
0xB8CC Ph A UV2 Alarm DPO Ph A UV2 Alarm DPO
0xB8D1 Ph B UV2 Alarm PKP Ph B UV2 Alarm PKP
0xB8D2 Ph B UV2 Alarm OP Ph B UV2 Alarm OP
0xB8D4 Ph B UV2 Alarm DPO Ph B UV2 Alarm DPO
0xB8E1 Ph C UV2 Alarm PKP Ph C UV2 Alarm PKP
0xB8E2 Ph C UV2 Alarm OP Ph C UV2 Alarm OP
0xB8E4 Ph C UV2 Alarm DPO Ph C UV2 Alarm DPO
0xB901 S/C Alarm PKP S/C Alarm PKP
0xB902 S/C Alarm OP S/C Alarm OP
0xB904 S/C Alarm DPO S/C Alarm DPO
0xB941 SPD2 S/C Alarm PKP SPD2 S/C Alarm PKP
0xB942 SPD2 S/C Alarm OP SPD2 S/C Alarm OP
0xB944 SPD2 S/C Alarm DPO SPD2 S/C Alarm DPO
0xB981 SPD2 U/C Alarm PKP SPD2 U/C Alarm PKP
0xB982 SPD2 U/C Alarm OP SPD2 U/C Alarm OP
0xB984 SPD2 U/C Alarm DPO SPD2 U/C Alarm DPO
0xBC01 LE 9 Alarm PKP Logic Element 9 Alarm PKP
0xBC02 LE 9 Alarm OP Logic Element 9 Alarm OP
0xBC04 LE 9 Alarm DPO Logic Element 9 Alarm DPO
0xBC41 LE 10 Alarm PKP Logic Element 10 Alarm PKP
0xBC42 LE 10 Alarm OP Logic Element 10 Alarm OP

10-146 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0xBC44 LE 10 Alarm DPO Logic Element 10 Alarm DPO
0xBC81 LE 11 Alarm PKP Logic Element 11 Alarm PKP
0xBC82 LE 11 Alarm OP Logic Element 11 Alarm OP
0xBC84 LE 11 Alarm DPO Logic Element 11 Alarm DPO
0xBCC1 LE 12 Alarm PKP Logic Element 12 Alarm PKP
0xBCC2 LE 12 Alarm OP Logic Element 12 Alarm OP
0xBCC4 LE 12 Alarm DPO Logic Element 12 Alarm DPO
0xBD01 LE 13 Alarm PKP Logic Element 13 Alarm PKP
0xBD02 LE 13 Alarm OP Logic Element 13 Alarm OP
0xBD04 LE 13 Alarm DPO Logic Element 13 Alarm DPO
0xBD41 LE 14 Alarm PKP Logic Element 14 Alarm PKP
0xBD42 LE 14 Alarm OP Logic Element 14 Alarm OP
0xBD44 LE 14 Alarm DPO Logic Element 14 Alarm DPO
0xBD81 LE 15 Alarm PKP Logic Element 15 Alarm PKP
0xBD82 LE 15 Alarm OP Logic Element 15 Alarm OP
0xBD84 LE 15 Alarm DPO Logic Element 15 Alarm DPO
0xBDC1 LE 16 Alarm PKP Logic Element 16 Alarm PKP
0xBDC2 LE 16 Alarm OP Logic Element 16 Alarm OP
0xBDC4 LE 16 Alarm DPO Logic Element 16 Alarm DPO
0xC002 Any Inhibit Any Inhibit
0xC042 Output Relay 3 On Output Relay 3 On
0xC082 Output Relay 4 On Output Relay 4 On
0xC0C2 Output Relay 5 On Output Relay 5 On
0xC102 Output Relay 6 On Output Relay 6 On
0xC142 Self-Test Rly 7 OP Self-Test Rly 7 OP
0xC202 BKR Connected Breaker Connected OP
0xC242 High Speed OP High Speed OP
0xC282 Low Speed OP Low Speed OP
0xC2C2 Any Pkp OP Any Pkp OP
0xC302 Stopped Stopped
0xC342 Starting Starting
0xC382 Running Running
0xC3C2 Motor Online OP Motor Online OP
0xC402 Emergency Restart Emergency Restart
0xC441 Hot RTD PKP Hot RTD PKP
0xC442 Hot RTD OP Hot RTD OP
0xC482 Lockout OP Lockout OP
0xC484 Lockout DPO Lockout DPO
0xC4C1 LE 1 PKP Logic Element 1 PKP
0xC4C2 LE 1 OP Logic Element 1 OP
0xC4C4 LE 1 DPO Logic Element 1 DPO
0xC501 LE 2 PKP Logic Element 2 PKP
0xC502 LE 2 OP Logic Element 2 OP
0xC504 LE 2 DPO Logic Element 2 DPO
0xC541 LE 3 PKP Logic Element 3 PKP
0xC542 LE 3 OP Logic Element 3 OP
0xC544 LE 3 DPO Logic Element 3 DPO

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-147


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xC581 LE 4 PKP Logic Element 4 PKP
0xC582 LE 4 OP Logic Element 4 OP
0xC584 LE 4 DPO Logic Element 4 DPO
0xC5C1 LE 5 PKP Logic Element 5 PKP
0xC5C2 LE 5 OP Logic Element 5 OP
0xC5C4 LE 5 DPO Logic Element 5 DPO
0xC601 LE 6 PKP Logic Element 6 PKP
0xC602 LE 6 OP Logic Element 6 OP
0xC604 LE 6 DPO Logic Element 6 DPO
0xC641 LE 7 PKP Logic Element 7 PKP
0xC642 LE 7 OP Logic Element 7 OP
0xC644 LE 7 DPO Logic Element 7 DPO
0xC681 LE 8 PKP Logic Element 8 PKP
0xC682 LE 8 OP Logic Element 8 OP
0xC684 LE 8 DPO Logic Element 8 DPO
0xC742 VFD Bypassed VFD Bypassed
0xC744 VFD Not Bypassed VFD Not Bypassed
0xC902 BKR Open Breaker Open
0xC942 BKR Close Breaker Close
0xC982 Maint. Req. OP Maintenance Required OP
0xCA02 52a Contact OP 52a Contact OP
0xCA42 52b Contact OP 52b Contact OP
0xCA82 Reset OK Reset OK
0xCAC2 L/O Rst Closed OP Lockout Reset Closed OP
0xCCC2 BKR Stat Open Breaker Status Open OP
0xCD02 BKR Stat Clsd Breaker Status Closed OP
0xCD82 Testing ON Testing ON
0xCD84 Testing OFF Testing OFF
0xCE82 Therm Inhibit OP Therm Inhibit OP
0xCEC2 Restart Inhibit OP Restart Inhibit OP
0xCF02 Starts/Hr Inhib OP Starts/Hr Inhibit OP
0xCF42 T-BT-Strt Inhib OP T-BT-Strt Inhibit OP
0xCF81 Fuse Fail InhibPKP Fuse Fail InhibPKP
0xCF82 Fuse Fail Inhib OP Fuse Fail Inhibit OP
0xCFC2 Ph Rev Inhibit OP Ph Reversal Inhibit OP
0xCFC4 Ph Rev Inhibit DPO Ph Rev Inhibit DPO
0xD241 Dir Pwr 1 PKP Directional Pwr 1 PKP
0xD242 Dir Pwr 1 OP Directional Pwr 1 OP
0xD281 Dir Pwr 2 PKP Directional Pwr 2 PKP
0xD282 Dir Pwr 2 OP Directional Pwr 2 OP
0xD342 Ntrl Dir Rev OP Neutral Directional Rev OP
0xD344 Ntrl Dir Rev DPO Neutral Directional Reverse DPO
0xDC01 LE 9 PKP Logic Element 9 PKP
0xDC02 LE 9 OP Logic Element 9 OP
0xDC04 LE 9 DPO Logic Element 9 DPO
0xDC41 LE 10 PKP Logic Element 10 PKP
0xDC42 LE 10 OP Logic Element 10 OP

10-148 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0xDC44 LE 10 DPO Logic Element 10 DPO
0xDC81 LE 11 PKP Logic Element 11 PKP
0xDC82 LE 11 OP Logic Element 11 OP
0xDC84 LE 11 DPO Logic Element 11 DPO
0xDCC1 LE 12 PKP Logic Element 12 PKP
0xDCC2 LE 12 OP Logic Element 12 OP
0xDCC4 LE 12 DPO Logic Element 12 DPO
0xDD01 LE 13 PKP Logic Element 13 PKP
0xDD02 LE 13 OP Logic Element 13 OP
0xDD04 LE 13 DPO Logic Element 13 DPO
0xDD41 LE 14 PKP Logic Element 14 PKP
0xDD42 LE 14 OP Logic Element 14 OP
0xDD44 LE 14 DPO Logic Element 14 DPO
0xDD81 LE 15 PKP Logic Element 15 PKP
0xDD82 LE 15 OP Logic Element 15 OP
0xDD84 LE 15 DPO Logic Element 15 DPO
0xDDC1 LE 16 PKP Logic Element 16 PKP
0xDDC2 LE 16 OP Logic Element 16 OP
0xDDC4 LE 16 DPO Logic Element 16 DPO
0xE002 Any Block Any Block
0xE042 Therm O/L Block Thermal Level Block
0xE082 Gnd Fault Blk Gnd Fault Blk
0xE0C2 Accel Blk Accel Blk
0xE182 Output Relay 1 Blk Output Relay 1 Block
0xE1C2 Output Relay 2 Blk Output Relay 2 Block
0xE202 Mech Jam Blk Mech Jam Blk
0xE242 U/CURR Blk U/CURR Blk
0xE282 UNBAL Blk UNBAL Blk
0xE2C2 RTD1 Block RTD1 Block
0xE302 RTD2 Block RTD2 Block
0xE342 RTD3 Block RTD3 Block
0xE382 RTD4 Block RTD4 Block
0xE3C2 RTD5 Block RTD5 Block
0xE402 RTD6 Block RTD6 Block
0xE442 RTDTrouble Block RTDTrouble Block
0xE6C2 RTD7 Block RTD7 Block
0xE702 RTD8 Block RTD8 Block
0xE742 RTD9 Block RTD9 Block
0xE782 RTD10 Block RTD10 Block
0xE7C2 RTD11 Block RTD11 Block
0xE802 RTD12 Block RTD12 Block
0xE842 PosSeq UV1 Block Positive Sequence UV 1 Block
0xE902 PosSeq UV2 Block Positive Sequence UV 2 Block
0xE9C2 CTFail Block CT Fail Block
0xEAC2 Load Incr Block Load Increase Block
0xF042 Ntrl IOC1 Block Neutral IOC 1 Block
0xF0C2 Ph TOC1 Block Phase TOC 1 Block

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-149


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xF102 Ntrl TOC1 Block Neutral TOC 1 Block
0xF242 Dir Pwr 1 Block Directional Pwr 1 Block
0xF282 Dir Pwr 2 Block Directional Pwr 2 Block
0xF342 Ntrl Dir Rev Block Neutral Directional Rev Block
0xF3C2 NSeq OV Block Negative Sequence OV OP
0xF442 Ph OV1 Block Ph OV 1 Block
0xF482 Ph UV1 Block Ph UV 1 Block
0xF542 UndrFreq1 Block Underfrequency 1 Block
0xF582 UndrFreq2 Block Underfrequency 2 Block
0xF5C2 OverFreq1 Block Overfrequency 1 Block
0xF602 OverFreq2 Block Overfrequency 2 Block
0xF702 Curr Dmd1 Block Current Demand 1 Block OP
0xF742 RealP Dmd Block Real Power Demand Block OP
0xF782 ReacP Dmd Block Reactive Power Demand Block OP
0xF7C2 AppP Dmd Block Apparent Power Demand Block OP
0xF882 Ph OV2 Block Ph OV2 Block
0xF8C2 Ph UV2 Block Ph UV2 Block
0xF902 S/C Blk S/C Blk
0xF942 SPD2 S/C Blk SPD2 S/C Blk
0xF982 SPD2 U/C Block SPD2 U/C Block
FC134C unsigned 16 bits Logic Element Trigger
0x0000 Off Off
0x0001 On On
0x0040 Contact IN 1 On Contact Input 1 On
0x0041 Contact IN 2 On Contact Input 2 On
0x0042 Contact IN 3 On Contact Input 3 On
0x0043 Contact IN 4 On Contact Input 4 On
0x0044 Contact IN 5 On Contact Input 5 On
0x0045 Contact IN 6 On Contact Input 6 On
0x0046 Contact IN 7 On Contact Input 7 On
0x0047 Contact IN 8 On Contact Input 8 On
0x0048 Contact IN 9 On Contact Input 9 On
0x0049 Contact IN 10 On Contact Input 10 On
0x0060 Contact IN 1 Off Contact Input 1 Off
0x0061 Contact IN 2 Off Contact Input 2 Off
0x0062 Contact IN 3 Off Contact Input 3 Off
0x0063 Contact IN 4 Off Contact Input 4 Off
0x0064 Contact IN 5 Off Contact Input 5 Off
0x0065 Contact IN 6 Off Contact Input 6 Off
0x0066 Contact IN 7 Off Contact Input 7 Off
0x0067 Contact IN 8 Off Contact Input 8 Off
0x0068 Contact IN 9 Off Contact Input 9 Off
0x0069 Contact IN 10 Off Contact Input 10 Off
0x0080 Virtual IN 1 On Virtual Input 1 On
0x0081 Virtual IN 2 On Virtual Input 2 On
0x0082 Virtual IN 3 On Virtual Input 3 On
0x0083 Virtual IN 4 On Virtual Input 4 On

10-150 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x0084 Virtual IN 5 On Virtual Input 5 On
0x0085 Virtual IN 6 On Virtual Input 6 On
0x0086 Virtual IN 7 On Virtual Input 7 On
0x0087 Virtual IN 8 On Virtual Input 8 On
0x0088 Virtual IN 9 On Virtual Input 9 On
0x0089 Virtual IN 10 On Virtual Input 10 On
0x008A Virtual IN 11 On Virtual Input 11 On
0x008B Virtual IN 12 On Virtual Input 12 On
0x008C Virtual IN 13 On Virtual Input 13 On
0x008D Virtual IN 14 On Virtual Input 14 On
0x008E Virtual IN 15 On Virtual Input 15 On
0x008F Virtual IN 16 On Virtual Input 16 On
0x0090 Virtual IN 17 On Virtual Input 17 On
0x0091 Virtual IN 18 On Virtual Input 18 On
0x0092 Virtual IN 19 On Virtual Input 19 On
0x0093 Virtual IN 20 On Virtual Input 20 On
0x0094 Virtual IN 21 On Virtual Input 21 On
0x0095 Virtual IN 22 On Virtual Input 22 On
0x0096 Virtual IN 23 On Virtual Input 23 On
0x0097 Virtual IN 24 On Virtual Input 24 On
0x0098 Virtual IN 25 On Virtual Input 25 On
0x0099 Virtual IN 26 On Virtual Input 26 On
0x009A Virtual IN 27 On Virtual Input 27 On
0x009B Virtual IN 28 On Virtual Input 28 On
0x009C Virtual IN 29 On Virtual Input 29 On
0x009D Virtual IN 30 On Virtual Input 30 On
0x009E Virtual IN 31 On Virtual Input 31 On
0x009F Virtual IN 32 On Virtual Input 32 On
0x00A0 Virtual IN 1 Off Virtual Input 1 Off
0x00A1 Virtual IN 2 Off Virtual Input 2 Off
0x00A2 Virtual IN 3 Off Virtual Input 3 Off
0x00A3 Virtual IN 4 Off Virtual Input 4 Off
0x00A4 Virtual IN 5 Off Virtual Input 5 Off
0x00A5 Virtual IN 6 Off Virtual Input 6 Off
0x00A6 Virtual IN 7 Off Virtual Input 7 Off
0x00A7 Virtual IN 8 Off Virtual Input 8 Off
0x00A8 Virtual IN 9 Off Virtual Input 9 Off
0x00A9 Virtual IN 10 Off Virtual Input 10 Off
0x00AA Virtual IN 11 Off Virtual Input 11 Off
0x00AB Virtual IN 12 Off Virtual Input 12 Off
0x00AC Virtual IN 13 Off Virtual Input 13 Off
0x00AD Virtual IN 14 Off Virtual Input 14 Off
0x00AE Virtual IN 15 Off Virtual Input 15 Off
0x00AF Virtual IN 16 Off Virtual Input 16 Off
0x00B0 Virtual IN 17 Off Virtual Input 17 Off
0x00B1 Virtual IN 18 Off Virtual Input 18 Off
0x00B2 Virtual IN 19 Off Virtual Input 19 Off

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-151


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x00B3 Virtual IN 20 Off Virtual Input 20 Off
0x00B4 Virtual IN 21 Off Virtual Input 21 Off
0x00B5 Virtual IN 22 Off Virtual Input 22 Off
0x00B6 Virtual IN 23 Off Virtual Input 23 Off
0x00B7 Virtual IN 24 Off Virtual Input 24 Off
0x00B8 Virtual IN 25 Off Virtual Input 25 Off
0x00B9 Virtual IN 26 Off Virtual Input 26 Off
0x00BA Virtual IN 27 Off Virtual Input 27 Off
0x00BB Virtual IN 28 Off Virtual Input 28 Off
0x00BC Virtual IN 29 Off Virtual Input 29 Off
0x00BD Virtual IN 30 Off Virtual Input 30 Off
0x00BE Virtual IN 31 Off Virtual Input 31 Off
0x00BF Virtual IN 32 Off Virtual Input 32 Off
0x01C0 Remote IN 1 On Remote Input 1 On
0x01C1 Remote IN 2 On Remote Input 2 On
0x01C2 Remote IN 3 On Remote Input 3 On
0x01C3 Remote IN 4 On Remote Input 4 On
0x01C4 Remote IN 5 On Remote Input 5 On
0x01C5 Remote IN 6 On Remote Input 6 On
0x01C6 Remote IN 7 On Remote Input 7 On
0x01C7 Remote IN 8 On Remote Input 8 On
0x01C8 Remote IN 9 On Remote Input 9 On
0x01C9 Remote IN 10 On Remote Input 10 On
0x01CA Remote IN 11 On Remote Input 11 On
0x01CB Remote IN 12 On Remote Input 12 On
0x01CC Remote IN 13 On Remote Input 13 On
0x01CD Remote IN 14 On Remote Input 14 On
0x01CE Remote IN 15 On Remote Input 15 On
0x01CF Remote IN 16 On Remote Input 16 On
0x01D0 Remote IN 17 On Remote Input 17 On
0x01D1 Remote IN 18 On Remote Input 18 On
0x01D2 Remote IN 19 On Remote Input 19 On
0x01D3 Remote IN 20 On Remote Input 20 On
0x01D4 Remote IN 21 On Remote Input 21 On
0x01D5 Remote IN 22 On Remote Input 22 On
0x01D6 Remote IN 23 On Remote Input 23 On
0x01D7 Remote IN 24 On Remote Input 24 On
0x01D8 Remote IN 25 On Remote Input 25 On
0x01D9 Remote IN 26 On Remote Input 26 On
0x01DA Remote IN 27 On Remote Input 27 On
0x01DB Remote IN 28 On Remote Input 28 On
0x01DC Remote IN 29 On Remote Input 29 On
0x01DD Remote IN 30 On Remote Input 30 On
0x01DE Remote IN 31 On Remote Input 31 On
0x01DF Remote IN 32 On Remote Input 32 On
0x01E0 Remote IN 1 Off Remote Input 1 Off
0x01E1 Remote IN 2 Off Remote Input 2 Off

10-152 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x01E2 Remote IN 3 Off Remote Input 3 Off
0x01E3 Remote IN 4 Off Remote Input 4 Off
0x01E4 Remote IN 5 Off Remote Input 5 Off
0x01E5 Remote IN 6 Off Remote Input 6 Off
0x01E6 Remote IN 7 Off Remote Input 7 Off
0x01E7 Remote IN 8 Off Remote Input 8 Off
0x01E8 Remote IN 9 Off Remote Input 9 Off
0x01E9 Remote IN 10 Off Remote Input 10 Off
0x01EA Remote IN 11 Off Remote Input 11 Off
0x01EB Remote IN 12 Off Remote Input 12 Off
0x01EC Remote IN 13 Off Remote Input 13 Off
0x01ED Remote IN 14 Off Remote Input 14 Off
0x01EE Remote IN 15 Off Remote Input 15 Off
0x01EF Remote IN 16 Off Remote Input 16 Off
0x01F0 Remote IN 17 Off Remote Input 17 Off
0x01F1 Remote IN 18 Off Remote Input 18 Off
0x01F2 Remote IN 19 Off Remote Input 19 Off
0x01F3 Remote IN 20 Off Remote Input 20 Off
0x01F4 Remote IN 21 Off Remote Input 21 Off
0x01F5 Remote IN 22 Off Remote Input 22 Off
0x01F6 Remote IN 23 Off Remote Input 23 Off
0x01F7 Remote IN 24 Off Remote Input 24 Off
0x01F8 Remote IN 25 Off Remote Input 25 Off
0x01F9 Remote IN 26 Off Remote Input 26 Off
0x01FA Remote IN 27 Off Remote Input 27 Off
0x01FB Remote IN 28 Off Remote Input 28 Off
0x01FC Remote IN 29 Off Remote Input 29 Off
0x01FD Remote IN 30 Off Remote Input 30 Off
0x01FE Remote IN 31 Off Remote Input 31 Off
0x01FF Remote IN 32 Off Remote Input 32 Off
0x8002 Any Trip Any Trip
0x8041 Therm O/L Trip PKP Thermal Overload Trip PKP
0x8042 Therm O/L Trip OP Thermal Overload Trip OP
0x8044 Therm O/L Trip DPO Thermal Overload Trip DPO
0x8081 GF Trip PKP GF Trip PKP
0x8082 GF Trip OP GF Trip OP
0x8084 GF Trip DPO GF Trip DPO
0x80C2 Accel Trip OP Acceleration Trip OP
0x8141 Under Pwr Trip PKP Under Power Trip PKP
0x8142 Under Pwr Trip OP Under Power Trip OP
0x8144 Under Pwr Trip DPO Under Power Trip DPO
0x8181 Single PH Trip PKP Single PH Trip PKP
0x8182 Single PH Trip OP Single PH Trip OP
0x8184 Single PH Trip DPO Single PH Trip DPO
0x8201 Mech Jam Trip PKP Mech Jam Trip PKP
0x8202 Mech Jam Trip OP Mech Jam Trip OP
0x8204 Mech Jam Trip DPO Mech Jam Trip DPO

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-153


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x8241 U/CURR Trip PKP U/CURR Trip PKP
0x8242 U/CURR Trip OP U/CURR Trip OP
0x8244 U/CURR Trip DPO U/CURR Trip DPO
0x8281 UNBAL Trip PKP Unbalance Trip PKP
0x8282 UNBAL Trip OP Unbalance Trip OP
0x8284 UNBAL Trip DPO Unbalance Trip DPO
0x82C1 RTD 1 Trip PKP RTD 1 Trip PKP
0x82C2 RTD 1 Trip OP RTD 1 Trip OP
0x8301 RTD 2 Trip PKP RTD 2 Trip PKP
0x8302 RTD 2 Trip OP RTD 2 Trip OP
0x8341 RTD 3 Trip PKP RTD 3 Trip PKP
0x8342 RTD 3 Trip OP RTD 3 Trip OP
0x8381 RTD 4 Trip PKP RTD 4 Trip PKP
0x8382 RTD 4 Trip OP RTD 4 Trip OP
0x83C1 RTD 5 Trip PKP RTD 5 Trip PKP
0x83C2 RTD 5 Trip OP RTD 5 Trip OP
0x8401 RTD 6 Trip PKP RTD 6 Trip PKP
0x8402 RTD 6 Trip OP RTD 6 Trip OP
0x84C1 LE 1 Trip PKP Logic Element 1 Trip PKP
0x84C2 LE 1 Trip OP Logic Element 1 Trip OP
0x84C4 LE 1 Trip DPO Logic Element 1 Trip DPO
0x8501 LE 2 Trip PKP Logic Element 2 Trip PKP
0x8502 LE 2 Trip OP Logic Element 2 Trip OP
0x8504 LE 2 Trip DPO Logic Element 2 Trip DPO
0x8541 LE 3 Trip PKP Logic Element 3 Trip PKP
0x8542 LE 3 Trip OP Logic Element 3 Trip OP
0x8544 LE 3 Trip DPO Logic Element 3 Trip DPO
0x8581 LE 4 Trip PKP Logic Element 4 Trip PKP
0x8582 LE 4 Trip OP Logic Element 4 Trip OP
0x8584 LE 4 Trip DPO Logic Element 4 Trip DPO
0x85C1 LE 5 Trip PKP Logic Element 5 Trip PKP
0x85C2 LE 5 Trip OP Logic Element 5 Trip OP
0x85C4 LE 5 Trip DPO Logic Element 5 Trip DPO
0x8601 LE 6 Trip PKP Logic Element 6 Trip PKP
0x8602 LE 6 Trip OP Logic Element 6 Trip OP
0x8604 LE 6 Trip DPO Logic Element 6 Trip DPO
0x8641 LE 7 Trip PKP Logic Element 7 Trip PKP
0x8642 LE 7 Trip OP Logic Element 7 Trip OP
0x8644 LE 7 Trip DPO Logic Element 7 Trip DPO
0x8681 LE 8 Trip PKP Logic Element 8 Trip PKP
0x8682 LE 8 Trip OP Logic Element 8 Trip OP
0x8684 LE 8 Trip DPO Logic Element 8 Trip DPO
0x86C1 RTD 7 Trip PKP RTD 7 Trip PKP
0x86C2 RTD 7 Trip OP RTD 7 Trip OP
0x8701 RTD 8 Trip PKP RTD 8 Trip PKP
0x8702 RTD 8 Trip OP RTD 8 Trip OP
0x8741 RTD 9 Trip PKP RTD 9 Trip PKP

10-154 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x8742 RTD 9 Trip OP RTD 9 Trip OP
0x8781 RTD 10 Trip PKP RTD 10 Trip PKP
0x8782 RTD 10 Trip OP RTD 10 Trip OP
0x87C1 RTD 11 Trip PKP RTD 11 Trip PKP
0x87C2 RTD 11 Trip OP RTD 11 Trip OP
0x8801 RTD 12 Trip PKP RTD 12 Trip PKP
0x8802 RTD 12 Trip OP RTD 12 Trip OP
0x8841 PosSeq UV1 Trp PKP Positive Sequence UV 1 Trp PKP
0x8842 PosSeq UV1 Trip OP Positive Sequence UV 1 Trip OP
0x8844 PosSeq UV1 Trp DPO Positive Sequence UV 1 Trp DPO
0x8901 PosSeq UV2 Trp PKP Positive Sequence UV 2 Trp PKP
0x8902 PosSeq UV2 Trip OP Positive Sequence UV 2 Trip OP
0x8904 PosSeq UV2 Trp DPO Positive Sequence UV 2 Trp DPO
0x8F81 Fuse Fail Trip PKP Fuse Fail Trip PKP
0x8F82 Fuse Fail Trip OP Fuse Fail Trip OP
0x8F84 Fuse Fail Trip DPO Fuse Fail Trip DPO
0x8FC1 Ph Revrsl Trip PKP Ph Revrsl Trip PKP
0x8FC2 Ph Revrsl Trip OP Ph Revrsl Trip OP
0x8FC4 Ph Revrsl Trip DPO Ph Revrsl Trip DPO
0x9041 Ntrl IOC1 Trip PKP Neutral IOC 1 Trip PKP
0x9042 Ntrl IOC1 Trip OP Neutral IOC 1 Trip OP
0x9044 Ntrl IOC1 Trip DPO Neutral IOC 1 Trip DPO
0x90C1 Ph TOC1 Trip PKP Phase TOC 1 Trip PKP
0x90C2 Ph TOC1 Trip OP Phase TOC 1 Trip OP
0x90C4 Ph TOC1 Trip DPO Phase TOC 1 Trip DPO
0x9101 Ntrl TOC1 Trip PKP Neutral TOC 1 Trip PKP
0x9102 Ntrl TOC1 Trip OP Neutral TOC 1 Trip OP
0x9104 Ntrl TOC1 Trip DPO Neutral TOC 1 Trip DPO
0x9241 Dir Pwr 1 Trip PKP Directional Pwr 1 Trip PKP
0x9242 Dir Pwr 1 Trip OP Directional Pwr 1 Trip OP
0x9281 Dir Pwr 2 Trip PKP Directional Pwr 2 Trip PKP
0x9282 Dir Pwr 2 Trip OP Directional Pwr 2 Trip OP
0x93C1 NSeq OV Trp PKP Negative Sequence OV Trip PKP
0x93C2 NSeq OV Trp OP Negative Sequence OV Trip OP
0x93C4 NSeq OV Trp DPO Negative Sequence OV Trip DPO
0x9441 Ph OV1 Trip PKP Phase OV1 Trip PKP
0x9442 Ph OV1 Trip OP Phase OV 1 Trip OP
0x9444 Ph OV1 Trip DPO Phase OV1 Trip DPO
0x9481 Ph UV1 Trip PKP Phase UV1 Trip PKP
0x9482 Ph UV1 Trip OP Phase UV 1 Trip OP
0x9484 Ph UV1 Trip DPO Phase UV1 Trip DPO
0x9541 UndrFreq1 Trip PKP Underfrequency 1 Trip PKP
0x9542 UndrFreq1 Trip OP Underfrequency 1 Trip OP
0x9544 UndrFreq1 Trip DPO Underfrequency 1 Trip DPO
0x9581 UndrFreq2 Trip PKP Underfrequency 2 Trip PKP
0x9582 UndrFreq2 Trip OP Underfrequency 2 Trip OP
0x9584 UndrFreq2 Trip DPO Underfrequency 2 Trip DPO

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-155


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x95C1 OverFreq1 Trip PKP Overfrequency 1 Trip PKP
0x95C2 OverFreq1 Trip OP Overfrequency 1 Trip OP
0x95C4 OverFreq1 Trip DPO Overfrequency 1 Trip DPO
0x9601 OverFreq2 Trip PKP Overfrequency 2 Trip PKP
0x9602 OverFreq2 Trip OP Overfrequency 2 Trip OP
0x9604 OverFreq2 Trip DPO Overfrequency 2 Trip DPO
0x9881 Ph OV2 Trip PKP Phase OV 2 Trip PKP
0x9882 Ph OV2 Trip OP Phase OV 2 Trip OP
0x9884 Ph OV2 Trip DPO Phase OV 2 Trip DPO
0x98C1 Ph UV2 Trip PKP Phase UV 2 Trip PKP
0x98C2 Ph UV2 Trip OP Phase UV 2 Trip OP
0x98C4 Ph UV2 Trip DPO Phase UV 2 Trip DPO
0x9901 S/C Trip PKP S/C Trip PKP
0x9902 S/C Trip OP S/C Trip OP
0x9904 S/C Trip DPO S/C Trip DPO
0x9941 SPD2 S/C Trip PKP SPD2 S/C Trip PKP
0x9942 SPD2 S/C Trip OP SPD2 S/C Trip OP
0x9944 SPD2 S/C Trip DPO SPD2 S/C Trip DPO
0x9981 SPD2 U/C Trip PKP SPD2 U/C Trip PKP
0x9982 SPD2 U/C Trip OP SPD2 U/C Trip OP
0x9984 SPD2 U/C Trip DPO SPD2 U/C Trip DPO
0x9C01 LE 9 Trip PKP Logic Element 9 Trip PKP
0x9C02 LE 9 Trip OP Logic Element 9 Trip OP
0x9C04 LE 9 Trip DPO Logic Element 9 Trip DPO
0x9C41 LE 10 Trip PKP Logic Element 10 Trip PKP
0x9C42 LE 10 Trip OP Logic Element 10 Trip OP
0x9C44 LE 10 Trip DPO Logic Element 10 Trip DPO
0x9C81 LE 11 Trip PKP Logic Element 11 Trip PKP
0x9C82 LE 11 Trip OP Logic Element 11 Trip OP
0x9C84 LE 11 Trip DPO Logic Element 11 Trip DPO
0x9CC1 LE 12 Trip PKP Logic Element 12 Trip PKP
0x9CC2 LE 12 Trip OP Logic Element 12 Trip OP
0x9CC4 LE 12 Trip DPO Logic Element 12 Trip DPO
0x9D01 LE 13 Trip PKP Logic Element 13 Trip PKP
0x9D02 LE 13 Trip OP Logic Element 13 Trip OP
0x9D04 LE 13 Trip DPO Logic Element 13 Trip DPO
0x9D41 LE 14 Trip PKP Logic Element 14 Trip PKP
0x9D42 LE 14 Trip OP Logic Element 14 Trip OP
0x9D44 LE 14 Trip DPO Logic Element 14 Trip DPO
0x9D81 LE 15 Trip PKP Logic Element 15 Trip PKP
0x9D82 LE 15 Trip OP Logic Element 15 Trip OP
0x9D84 LE 15 Trip DPO Logic Element 15 Trip DPO
0x9DC1 LE 16 Trip PKP Logic Element 16 Trip PKP
0x9DC2 LE 16 Trip OP Logic Element 16 Trip OP
0x9DC4 LE 16 Trip DPO Logic Element 16 Trip DPO
0xA002 Any Alarm Any Alarm
0xA042 Therm Lvl Alrm OP Thermal Level Alarm OP

10-156 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0xA044 Therm Lvl Alrm DPO Thermal Level Alarm DPO
0xA081 Gnd Fault Alrm PKP Ground Fault Alarm PKP
0xA082 Gnd Fault Alrm OP Ground Fault Alarm OP
0xA084 Gnd Fault Alrm DPO Ground Fault Alarm DPO
0xA0C2 Accel Alarm OP Accel Alarm OP
0xA141 Under Pwr Alrm PKP Under Power Alarm PKP
0xA142 Under Pwr Alrm OP Under Power Alarm OP
0xA144 Under Pwr Alrm DPO Under Power Alarm DPO
0xA201 Mech Jam Alarm PKP Mech Jam Alarm PKP
0xA202 Mech Jam Alarm OP Mech Jam Alarm OP
0xA204 Mech Jam Alarm DPO Mech Jam Alarm DPO
0xA241 U/CURR Alarm PKP U/CURR Alarm PKP
0xA242 U/CURR Alarm OP U/CURR Alarm OP
0xA244 U/CURR Alarm DPO U/CURR Alarm DPO
0xA281 UNBAL Alarm PKP Unbalance Alarm PKP
0xA282 UNBAL Alarm OP Unbalance Alarm OP
0xA284 UNBAL Alarm DPO Unbalance Alarm DPO
0xA2C1 RTD 1 Alarm PKP RTD 1 Alarm PKP
0xA2C2 RTD 1 Alarm OP RTD 1 Alarm OP
0xA301 RTD 2 Alarm PKP RTD 2 Alarm PKP
0xA302 RTD 2 Alarm OP RTD 2 Alarm OP
0xA341 RTD 3 Alarm PKP RTD 3 Alarm PKP
0xA342 RTD 3 Alarm OP RTD 3 Alarm OP
0xA381 RTD 4 Alarm PKP RTD 4 Alarm PKP
0xA382 RTD 4 Alarm OP RTD 4 Alarm OP
0xA3C1 RTD 5 Alarm PKP RTD 5 Alarm PKP
0xA3C2 RTD 5 Alarm OP RTD 5 Alarm OP
0xA401 RTD 6 Alarm PKP RTD 6 Alarm PKP
0xA402 RTD 6 Alarm OP RTD 6 Alarm OP
0xA442 RTD Trouble Alr OP RTD Trouble Alarm
0xA4C1 LE 1 Alarm PKP Logic Element 1 Alarm PKP
0xA4C2 LE 1 Alarm OP Logic Element 1 Alarm OP
0xA4C4 LE 1 Alarm DPO Logic Element 1 Alarm DPO
0xA501 LE 2 Alarm PKP Logic Element 2 Alarm PKP
0xA502 LE 2 Alarm OP Logic Element 2 Alarm OP
0xA504 LE 2 Alarm DPO Logic Element 2 Alarm DPO
0xA541 LE 3 Alarm PKP Logic Element 3 Alarm PKP
0xA542 LE 3 Alarm OP Logic Element 3 Alarm OP
0xA544 LE 3 Alarm DPO Logic Element 3 Alarm DPO
0xA581 LE 4 Alarm PKP Logic Element 4 Alarm PKP
0xA582 LE 4 Alarm OP Logic Element 4 Alarm OP
0xA584 LE 4 Alarm DPO Logic Element 4 Alarm DPO
0xA5C1 LE 5 Alarm PKP Logic Element 5 Alarm PKP
0xA5C2 LE 5 Alarm OP Logic Element 5 Alarm OP
0xA5C4 LE 5 Alarm DPO Logic Element 5 Alarm DPO
0xA601 LE 6 Alarm PKP Logic Element 6 Alarm PKP
0xA602 LE 6 Alarm OP Logic Element 6 Alarm OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-157


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xA604 LE 6 Alarm DPO Logic Element 6 Alarm DPO
0xA641 LE 7 Alarm PKP Logic Element 7 Alarm PKP
0xA642 LE 7 Alarm OP Logic Element 7 Alarm OP
0xA644 LE 7 Alarm DPO Logic Element 7 Alarm DPO
0xA681 LE 8 Alarm PKP Logic Element 8 Alarm PKP
0xA682 LE 8 Alarm OP Logic Element 8 Alarm OP
0xA684 LE 8 Alarm DPO Logic Element 8 Alarm DPO
0xA6C1 RTD 7 Alarm PKP RTD 7 Alarm PKP
0xA6C2 RTD 7 Alarm OP RTD 7 Alarm OP
0xA701 RTD 8 Alarm PKP RTD 8 Alarm PKP
0xA702 RTD 8 Alarm OP RTD 8 Alarm OP
0xA741 RTD 9 Alarm PKP RTD 9 Alarm PKP
0xA742 RTD 9 Alarm OP RTD 9 Alarm OP
0xA781 RTD 10 Alarm PKP RTD 10 Alarm PKP
0xA782 RTD 10 Alarm OP RTD 10 Alarm OP
0xA7C1 RTD 11 Alarm PKP RTD 11 Alarm PKP
0xA7C2 RTD 11 Alarm OP RTD 11 Alarm OP
0xA801 RTD 12 Alarm PKP RTD 12 Alarm PKP
0xA802 RTD 12 Alarm OP RTD 12 Alarm OP
0xA841 PosSeq UV1 AlrmPKP Positive Sequence UV 1 Alarm PKP
0xA842 PosSeq UV1 Alrm OP Positive Sequence UV 1 Alarm OP
0xA844 PosSeq UV1 AlrmDPO Positive Sequence UV 1 Alarm DPO
0xA882 BKR Alarm Breaker Alarm
0xA901 PosSeq UV2 AlrmPKP Positive Sequence UV 2 Alarm PKP
0xA902 PosSeq UV2 Alrm OP Positive Sequence UV 2 Alarm OP
0xA904 PosSeq UV2 AlrmDPO Positive Sequence UV 2 Alarm DPO
0xA982 Motor Run Hrs OP Motor Running Hours OP
0xA9C1 CTFail Alrm PKP CT Fail Alarm PKP
0xA9C2 CTFail Alrm OP CT Fail Alarm OP
0xA9C4 CTFail Alrm DPO CT Fail Alarm DPO
0xAA01 Welded ContactrPKP Welded ContactrPKP
0xAA02 Welded Contactr OP Welded Contactr OP
0xAA04 Welded ContactrDPO Welded ContactrDPO
0xAA42 SPD SW Not Cnfg OP SPD SW Not Cnfg OP
0xAA82 SPD SW Fail OP SPD SW Fail OP
0xAAC1 Load Incr Alrm PKP Load Incr Alrm PKP
0xAAC2 Load Incr Alrm OP Load Incr Alrm OP
0xAAC4 Load Incr Alrm DPO Load Incr Alrm DPO
0xAB02 BKR Trip Time Breaker Trip Time
0xAB42 BKR Close Time Breaker Close Time
0xAB82 BKR Charge Time Breaker Charge Time
0xABC1 HI Amb Temp PKP High Ambient Temperature Alarm PKP
0xABC2 HI Amb Temp OP High Ambient Temperature Alarm
0xABC4 HI Amb Temp DPO High Ambient Temperature Alarm DPO
0xAC01 LO Amb Temp PKP Low Ambient Temperature Alarm PKP
0xAC02 LO Amb Temp OP Low Ambient Temperature Alarm
0xAC04 LO Amb Temp DPO Low Ambient Temperature Alarm DPO

10-158 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0xAC42 Self Test Alarm OP Self Test Alarm OP
0xACC2 BKRTrpCntrAlrm OP Breaker Trip Control Alarm OP
0xAD02 R1 CoilMonAlrm OP Trip Coil Monitor Alarm OP
0xAD42 R2 CoilMonAlrm OP Close Coil Monitor Alarm OP
0xAD81 BKR Fail Alrm PKP Breaker Fail Alarm PKP
0xAD82 BKR Fail Alrm OP Breaker Fail Alarm OP
0xADC2 BKR Stat Fail OP Breaker Status Fail OP
0xAE82 BKR Trp/Cls Fail Breaker Trip/Close Fail
0xAEC2 BKR Charge Fail Breaker Charge Fail
0xAF81 Fuse Fail Alrm PKP Fuse Fail Alarm PKP
0xAF82 Fuse Fail Alrm OP Fuse Fail Alarm OP
0xAF84 Fuse Fail Alrm DPO Fuse Fail Alarm DPO
0xAFC1 Ph Revrsl Alrm PKP Ph Reversal Alarm PKP
0xAFC2 Ph Revrsl Alarm OP Ph Reversal Alarm OP
0xAFC4 Ph Revrsl Alrm DPO Ph Reversal Alarm DPO
0xB041 Ntrl IOC1 Alrm PKP Neutral IOC 1 Alarm PKP
0xB042 Ntrl IOC1 Alrm OP Neutral IOC 1 Alarm OP
0xB044 Ntrl IOC1 Alrm DPO Neutral IOC 1 Alarm DPO
0xB0C1 Ph TOC1 Alarm PKP Phase TOC 1 Alarm PKP
0xB0C2 Ph TOC1 Alarm OP Phase TOC 1 Alarm OP
0xB0C4 Ph TOC1 Alarm DPO Phase TOC 1 Alarm DPO
0xB101 Ntrl TOC1 Alrm PKP Neutral TOC 1 Alarm PKP
0xB102 Ntrl TOC1 Alrm OP Neutral TOC 1 Alarm OP
0xB104 Ntrl TOC1 Alrm DPO Neutral TOC 1 Alarm DPO
0xB241 Dir Pwr 1 Alrm PKP Directional Pwr 1 Alarm PKP
0xB242 Dir Pwr 1 Alarm OP Directional Pwr 1 Alarm OP
0xB281 Dir Pwr 2 Alrm PKP Directional Pwr 2 Alarm PKP
0xB282 Dir Pwr 2 Alarm OP Directional Pwr 2 Alarm OP
0xB342 NtrlDir RevAlm OP Neutral Directional Alarm OP
0xB344 NtrlDir RevAlmDPO Neutral Directional Reverse Alarm DPO
0xB3C1 NSeq OV Alrm PKP Negative Sequence OV Alarm PKP
0xB3C2 NSeq OV Alrm OP Negative Sequence OV Alarm OP
0xB3C4 NSeq OV Alrm DPO Negative Sequence OV Alarm DPO
0xB441 Ph OV1 Alarm PKP Phase OV1 Alarm PKP
0xB442 Ph OV1 Alarm OP Phase OV 1 Alarm OP
0xB444 Ph OV1 Alarm DPO Phase OV1 Alarm DPO
0xB481 Ph UV1 Alarm PKP Phase UV1 Alarm PKP
0xB482 Ph UV1 Alarm OP Phase UV 1 Alarm OP
0xB484 Ph UV1 Alarm DPO Phase UV1 Alarm DPO
0xB541 UndrFreq1 Alrm PKP Underfrequency 1 Alarm PKP
0xB542 UndrFreq1 Alrm OP Underfrequency 1 Alarm OP
0xB544 UndrFreq1 Alrm DPO Underfrequency 1 Alarm DPO
0xB581 UndrFreq2 Alrm PKP Underfrequency 2 Alarm PKP
0xB582 UndrFreq2 Alrm OP Underfrequency 2 Alarm OP
0xB584 UndrFreq2 Alrm DPO Underfrequency 2 Alarm DPO
0xB5C1 OverFreq1 Alrm PKP Overfrequency 1 Alarm PKP
0xB5C2 OverFreq1 Alrm OP Overfrequency 1 Alarm OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-159


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xB5C4 OverFreq1 Alrm DPO Overfrequency 1 Alarm DPO
0xB601 OverFreq2 Alrm PKP Overfrequency 2 Alarm PKP
0xB602 OverFreq2 Alrm OP Overfrequency 2 Alarm OP
0xB604 OverFreq2 Alrm DPO Overfrequency 2 Alarm DPO
0xB702 Curr Dmd1 Alrm OP Current Demand 1 Alarm OP
0xB742 RealP Dmd Alrm OP Real Power Demand Alarm OP
0xB782 ReacP Dmd Alrm OP Reactive Power Demand Alarm OP
0xB7C2 AppP Dmd Alrm OP Apparent Power Demand Alarm OP
0xB881 Ph OV2 Alarm PKP Phase OV 2 Alarm PKP
0xB882 Ph OV2 Alarm OP Phase OV 2 Alarm OP
0xB884 Ph OV2 Alarm DPO Phase OV 2 Alarm DPO
0xB8C1 Ph UV2 Alarm PKP Phase UV 2 Alarm PKP
0xB8C2 Ph UV2 Alarm OP Phase UV 2 Alarm OP
0xB8C4 Ph UV2 Alarm DPO Phase UV 2 Alarm DPO
0xB901 S/C Alarm PKP S/C Alarm PKP
0xB902 S/C Alarm OP S/C Alarm OP
0xB904 S/C Alarm DPO S/C Alarm DPO
0xB941 SPD2 S/C Alarm PKP SPD2 S/C Alarm PKP
0xB942 SPD2 S/C Alarm OP SPD2 S/C Alarm OP
0xB944 SPD2 S/C Alarm DPO SPD2 S/C Alarm DPO
0xB981 SPD2 U/C Alarm PKP SPD2 U/C Alarm PKP
0xB982 SPD2 U/C Alarm OP SPD2 U/C Alarm OP
0xB984 SPD2 U/C Alarm DPO SPD2 U/C Alarm DPO
0xBC01 LE 9 Alarm PKP Logic Element 9 Alarm PKP
0xBC02 LE 9 Alarm OP Logic Element 9 Alarm OP
0xBC04 LE 9 Alarm DPO Logic Element 9 Alarm DPO
0xBC41 LE 10 Alarm PKP Logic Element 10 Alarm PKP
0xBC42 LE 10 Alarm OP Logic Element 10 Alarm OP
0xBC44 LE 10 Alarm DPO Logic Element 10 Alarm DPO
0xBC81 LE 11 Alarm PKP Logic Element 11 Alarm PKP
0xBC82 LE 11 Alarm OP Logic Element 11 Alarm OP
0xBC84 LE 11 Alarm DPO Logic Element 11 Alarm DPO
0xBCC1 LE 12 Alarm PKP Logic Element 12 Alarm PKP
0xBCC2 LE 12 Alarm OP Logic Element 12 Alarm OP
0xBCC4 LE 12 Alarm DPO Logic Element 12 Alarm DPO
0xBD01 LE 13 Alarm PKP Logic Element 13 Alarm PKP
0xBD02 LE 13 Alarm OP Logic Element 13 Alarm OP
0xBD04 LE 13 Alarm DPO Logic Element 13 Alarm DPO
0xBD41 LE 14 Alarm PKP Logic Element 14 Alarm PKP
0xBD42 LE 14 Alarm OP Logic Element 14 Alarm OP
0xBD44 LE 14 Alarm DPO Logic Element 14 Alarm DPO
0xBD81 LE 15 Alarm PKP Logic Element 15 Alarm PKP
0xBD82 LE 15 Alarm OP Logic Element 15 Alarm OP
0xBD84 LE 15 Alarm DPO Logic Element 15 Alarm DPO
0xBDC1 LE 16 Alarm PKP Logic Element 16 Alarm PKP
0xBDC2 LE 16 Alarm OP Logic Element 16 Alarm OP
0xBDC4 LE 16 Alarm DPO Logic Element 16 Alarm DPO

10-160 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0xC002 Any Inhibit Any Inhibit
0xC042 Output Relay 3 On Output Relay 3 On
0xC082 Output Relay 4 On Output Relay 4 On
0xC0C2 Output Relay 5 On Output Relay 5 On
0xC102 Output Relay 6 On Output Relay 6 On
0xC142 Self-Test Rly 7 OP Self-Test Rly 7 OP
0xC182 Rly1 Coil OP Relay # 1 Coil OP
0xC1C2 Rly2 Coil OP Relay # 2 Coil OP
0xC202 BKR Connected Breaker Connected OP
0xC242 High Speed OP High Speed OP
0xC282 Low Speed OP Low Speed OP
0xC2C2 Any Pkp OP Any Pkp OP
0xC302 Stopped Stopped
0xC342 Starting Starting
0xC382 Running Running
0xC3C2 Motor Online OP Motor Online OP
0xC402 Emergency Restart Emergency Restart
0xC441 Hot RTD PKP Hot RTD PKP
0xC442 Hot RTD OP Hot RTD OP
0xC482 Lockout OP Lockout OP
0xC484 Lockout DPO Lockout DPO
0xC4C1 LE 1 PKP Logic Element 1 PKP
0xC4C2 LE 1 OP Logic Element 1 OP
0xC4C4 LE 1 DPO Logic Element 1 DPO
0xC501 LE 2 PKP Logic Element 2 PKP
0xC502 LE 2 OP Logic Element 2 OP
0xC504 LE 2 DPO Logic Element 2 DPO
0xC541 LE 3 PKP Logic Element 3 PKP
0xC542 LE 3 OP Logic Element 3 OP
0xC544 LE 3 DPO Logic Element 3 DPO
0xC581 LE 4 PKP Logic Element 4 PKP
0xC582 LE 4 OP Logic Element 4 OP
0xC584 LE 4 DPO Logic Element 4 DPO
0xC5C1 LE 5 PKP Logic Element 5 PKP
0xC5C2 LE 5 OP Logic Element 5 OP
0xC5C4 LE 5 DPO Logic Element 5 DPO
0xC601 LE 6 PKP Logic Element 6 PKP
0xC602 LE 6 OP Logic Element 6 OP
0xC604 LE 6 DPO Logic Element 6 DPO
0xC641 LE 7 PKP Logic Element 7 PKP
0xC642 LE 7 OP Logic Element 7 OP
0xC644 LE 7 DPO Logic Element 7 DPO
0xC681 LE 8 PKP Logic Element 8 PKP
0xC682 LE 8 OP Logic Element 8 OP
0xC684 LE 8 DPO Logic Element 8 DPO
0xC742 VFD Bypassed VFD Bypassed
0xC744 VFD Not Bypassed VFD Not Bypassed

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-161


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xC902 BKR Open Breaker Open
0xC942 BKR Close Breaker Close
0xC982 Maint. Req. OP Maintenance Required OP
0xCA02 52a Contact OP 52a Contact OP
0xCA42 52b Contact OP 52b Contact OP
0xCA82 Reset OK Reset OK
0xCAC2 L/O Rst Closed OP Lockout Reset Closed OP
0xCCC2 BKR Stat Open Breaker Status Open OP
0xCD02 BKR Stat Clsd Breaker Status Closed OP
0xCD82 Testing ON Testing ON
0xCD84 Testing OFF Testing OFF
0xCE82 Therm Inhibit OP Therm Inhibit OP
0xCEC2 Restart Inhibit OP Restart Inhibit OP
0xCF02 Starts/Hr Inhib OP Starts/Hr Inhibit OP
0xCF42 T-BT-Strt Inhib OP T-BT-Strt Inhibit OP
0xCF81 Fuse Fail InhibPKP Fuse Fail InhibPKP
0xCF82 Fuse Fail Inhib OP Fuse Fail Inhibit OP
0xCFC2 Ph Rev Inhibit OP Ph Reversal Inhibit OP
0xCFC4 Ph Rev Inhibit DPO Ph Rev Inhibit DPO
0xD241 Dir Pwr 1 PKP Directional Pwr 1 PKP
0xD242 Dir Pwr 1 OP Directional Pwr 1 OP
0xD281 Dir Pwr 2 PKP Directional Pwr 2 PKP
0xD282 Dir Pwr 2 OP Directional Pwr 2 OP
0xD342 Ntrl Dir Rev OP Neutral Directional Rev OP
0xD344 Ntrl Dir Rev DPO Neutral Directional Reverse DPO
0xDC01 LE 9 PKP Logic Element 9 PKP
0xDC02 LE 9 OP Logic Element 9 OP
0xDC04 LE 9 DPO Logic Element 9 DPO
0xDC41 LE 10 PKP Logic Element 10 PKP
0xDC42 LE 10 OP Logic Element 10 OP
0xDC44 LE 10 DPO Logic Element 10 DPO
0xDC81 LE 11 PKP Logic Element 11 PKP
0xDC82 LE 11 OP Logic Element 11 OP
0xDC84 LE 11 DPO Logic Element 11 DPO
0xDCC1 LE 12 PKP Logic Element 12 PKP
0xDCC2 LE 12 OP Logic Element 12 OP
0xDCC4 LE 12 DPO Logic Element 12 DPO
0xDD01 LE 13 PKP Logic Element 13 PKP
0xDD02 LE 13 OP Logic Element 13 OP
0xDD04 LE 13 DPO Logic Element 13 DPO
0xDD41 LE 14 PKP Logic Element 14 PKP
0xDD42 LE 14 OP Logic Element 14 OP
0xDD44 LE 14 DPO Logic Element 14 DPO
0xDD81 LE 15 PKP Logic Element 15 PKP
0xDD82 LE 15 OP Logic Element 15 OP
0xDD84 LE 15 DPO Logic Element 15 DPO
0xDDC1 LE 16 PKP Logic Element 16 PKP

10-162 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0xDDC2 LE 16 OP Logic Element 16 OP
0xDDC4 LE 16 DPO Logic Element 16 DPO
0xE002 Any Block Any Block
0xE042 Therm O/L Block Thermal Level Block
0xE082 Gnd Fault Blk Gnd Fault Blk
0xE0C2 Accel Blk Accel Blk
0xE182 Output Relay 1 Blk Output Relay 1 Block
0xE1C2 Output Relay 2 Blk Output Relay 2 Block
0xE202 Mech Jam Blk Mech Jam Blk
0xE242 U/CURR Blk U/CURR Blk
0xE282 UNBAL Blk UNBAL Blk
0xE2C2 RTD1 Block RTD1 Block
0xE302 RTD2 Block RTD2 Block
0xE342 RTD3 Block RTD3 Block
0xE382 RTD4 Block RTD4 Block
0xE3C2 RTD5 Block RTD5 Block
0xE402 RTD6 Block RTD6 Block
0xE442 RTDTrouble Block RTDTrouble Block
0xE6C2 RTD7 Block RTD7 Block
0xE702 RTD8 Block RTD8 Block
0xE742 RTD9 Block RTD9 Block
0xE782 RTD10 Block RTD10 Block
0xE7C2 RTD11 Block RTD11 Block
0xE802 RTD12 Block RTD12 Block
0xE842 PosSeq UV1 Block Positive Sequence UV 1 Block
0xE902 PosSeq UV2 Block Positive Sequence UV 2 Block
0xE9C2 CTFail Block CT Fail Block
0xEAC2 Load Incr Block Load Increase Block
0xF042 Ntrl IOC1 Block Neutral IOC 1 Block
0xF0C2 Ph TOC1 Block Phase TOC 1 Block
0xF102 Ntrl TOC1 Block Neutral TOC 1 Block
0xF242 Dir Pwr 1 Block Directional Pwr 1 Block
0xF282 Dir Pwr 2 Block Directional Pwr 2 Block
0xF342 Ntrl Dir Rev Block Neutral Directional Rev Block
0xF3C2 NSeq OV Block Negative Sequence OV OP
0xF442 Ph OV1 Block Ph OV 1 Block
0xF482 Ph UV1 Block Ph UV 1 Block
0xF542 UndrFreq1 Block Underfrequency 1 Block
0xF582 UndrFreq2 Block Underfrequency 2 Block
0xF5C2 OverFreq1 Block Overfrequency 1 Block
0xF602 OverFreq2 Block Overfrequency 2 Block
0xF702 Curr Dmd1 Block Current Demand 1 Block OP
0xF742 RealP Dmd Block Real Power Demand Block OP
0xF782 ReacP Dmd Block Reactive Power Demand Block OP
0xF7C2 AppP Dmd Block Apparent Power Demand Block OP
0xF882 Ph OV2 Block Ph OV2 Block
0xF8C2 Ph UV2 Block Ph UV2 Block

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-163


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xF902 S/C Blk S/C Blk
0xF942 SPD2 S/C Blk SPD2 S/C Blk
0xF982 SPD2 U/C Block SPD2 U/C Block
FC134D unsigned 16 bits Lockout Trigger
0 Off Off
0x0001 On On
0x0040 Contact IN 1 On Contact Input 1 On
0x0041 Contact IN 2 On Contact Input 2 On
0x0042 Contact IN 3 On Contact Input 3 On
0x0043 Contact IN 4 On Contact Input 4 On
0x0044 Contact IN 5 On Contact Input 5 On
0x0045 Contact IN 6 On Contact Input 6 On
0x0046 Contact IN 7 On Contact Input 7 On
0x0047 Contact IN 8 On Contact Input 8 On
0x0048 Contact IN 9 On Contact Input 9 On
0x0049 Contact IN 10 On Contact Input 10 On
0x0060 Contact IN 1 Off Contact Input 1 Off
0x0061 Contact IN 2 Off Contact Input 2 Off
0x0062 Contact IN 3 Off Contact Input 3 Off
0x0063 Contact IN 4 Off Contact Input 4 Off
0x0064 Contact IN 5 Off Contact Input 5 Off
0x0065 Contact IN 6 Off Contact Input 6 Off
0x0066 Contact IN 7 Off Contact Input 7 Off
0x0067 Contact IN 8 Off Contact Input 8 Off
0x0068 Contact IN 9 Off Contact Input 9 Off
0x0069 Contact IN 10 Off Contact Input 10 Off
0x0080 Virtual IN 1 On Virtual Input 1 On
0x0081 Virtual IN 2 On Virtual Input 2 On
0x0082 Virtual IN 3 On Virtual Input 3 On
0x0083 Virtual IN 4 On Virtual Input 4 On
0x0084 Virtual IN 5 On Virtual Input 5 On
0x0085 Virtual IN 6 On Virtual Input 6 On
0x0086 Virtual IN 7 On Virtual Input 7 On
0x0087 Virtual IN 8 On Virtual Input 8 On
0x0088 Virtual IN 9 On Virtual Input 9 On
0x0089 Virtual IN 10 On Virtual Input 10 On
0x008A Virtual IN 11 On Virtual Input 11 On
0x008B Virtual IN 12 On Virtual Input 12 On
0x008C Virtual IN 13 On Virtual Input 13 On
0x008D Virtual IN 14 On Virtual Input 14 On
0x008E Virtual IN 15 On Virtual Input 15 On
0x008F Virtual IN 16 On Virtual Input 16 On
0x0090 Virtual IN 17 On Virtual Input 17 On
0x0091 Virtual IN 18 On Virtual Input 18 On
0x0092 Virtual IN 19 On Virtual Input 19 On
0x0093 Virtual IN 20 On Virtual Input 20 On
0x0094 Virtual IN 21 On Virtual Input 21 On

10-164 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x0095 Virtual IN 22 On Virtual Input 22 On
0x0096 Virtual IN 23 On Virtual Input 23 On
0x0097 Virtual IN 24 On Virtual Input 24 On
0x0098 Virtual IN 25 On Virtual Input 25 On
0x0099 Virtual IN 26 On Virtual Input 26 On
0x009A Virtual IN 27 On Virtual Input 27 On
0x009B Virtual IN 28 On Virtual Input 28 On
0x009C Virtual IN 29 On Virtual Input 29 On
0x009D Virtual IN 30 On Virtual Input 30 On
0x009E Virtual IN 31 On Virtual Input 31 On
0x009F Virtual IN 32 On Virtual Input 32 On
0x8002 Any Trip Any Trip
0x8042 Therm O/L Trip OP Thermal Overload Trip OP
0x8082 GF Trip OP GF Trip OP
0x80C2 Accel Trip OP Acceleration Trip OP
0x8142 Under Pwr Trip OP Under Power Trip OP
0x8182 Single PH Trip OP Single PH Trip OP
0x8202 Mech Jam Trip OP Mech Jam Trip OP
0x8242 U/CURR Trip OP U/CURR Trip OP
0x8282 UNBAL Trip OP Unbalance Trip OP
0x82C2 RTD 1 Trip OP RTD 1 Trip OP
0x8302 RTD 2 Trip OP RTD 2 Trip OP
0x8342 RTD 3 Trip OP RTD 3 Trip OP
0x8382 RTD 4 Trip OP RTD 4 Trip OP
0x83C2 RTD 5 Trip OP RTD 5 Trip OP
0x8402 RTD 6 Trip OP RTD 6 Trip OP
0x84C2 LE 1 Trip OP Logic Element 1 Trip OP
0x8502 LE 2 Trip OP Logic Element 2 Trip OP
0x8542 LE 3 Trip OP Logic Element 3 Trip OP
0x8582 LE 4 Trip OP Logic Element 4 Trip OP
0x85C2 LE 5 Trip OP Logic Element 5 Trip OP
0x8602 LE 6 Trip OP Logic Element 6 Trip OP
0x8642 LE 7 Trip OP Logic Element 7 Trip OP
0x8682 LE 8 Trip OP Logic Element 8 Trip OP
0x86C2 RTD 7 Trip OP RTD 7 Trip OP
0x8702 RTD 8 Trip OP RTD 8 Trip OP
0x8742 RTD 9 Trip OP RTD 9 Trip OP
0x8782 RTD 10 Trip OP RTD 10 Trip OP
0x87C2 RTD 11 Trip OP RTD 11 Trip OP
0x8802 RTD 12 Trip OP RTD 12 Trip OP
0x8842 PosSeq UV1 Trip OP Positive Sequence UV 1 Trip OP
0x8902 PosSeq UV2 Trip OP Positive Sequence UV 2 Trip OP
0x89C2 Self Test OP Self Test OP
0x8F82 Fuse Fail Trip OP Fuse Fail Trip OP
0x8FC2 Ph Revrsl Trip OP Ph Revrsl Trip OP
0x9042 Ntrl IOC1 Trip OP Neutral IOC 1 Trip OP
0x90C2 Ph TOC1 Trip OP Phase TOC 1 Trip OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-165


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x90CA Ph A TOC1 Trip OP Phase A TOC 1 Trip OP
0x90D2 Ph B TOC1 Trip OP Phase B TOC 1 Trip OP
0x90E2 Ph C TOC1 Trip OP Phase C TOC 1 Trip OP
0x9102 Ntrl TOC1 Trip OP Neutral TOC 1 Trip OP
0x9242 Dir Pwr 1 Trip OP Directional Pwr 1 Trip OP
0x9282 Dir Pwr 2 Trip OP Directional Pwr 2 Trip OP
0x93C2 NSeq OV Trp OP Negative Sequence OV Trip OP
0x9442 Ph OV1 Trip OP Phase OV 1 Trip OP
0x944A Ph A OV1 Trip OP Phase A OV1 Trip OP
0x9452 Ph B OV1 Trip OP Phase B OV1 Trip OP
0x9462 Ph C OV1 Trip OP Phase C OV1 Trip OP
0x9482 Ph UV1 Trip OP Phase UV 1 Trip OP
0x948A Ph A UV1 Trip OP Phase A UV1 Trip OP
0x9492 Ph B UV1 Trip OP Phase B UV1 Trip OP
0x94A2 Ph C UV1 Trip OP Phase C UV1 Trip OP
0x9542 UndrFreq1 Trip OP Underfrequency 1 Trip OP
0x9582 UndrFreq2 Trip OP Underfrequency 2 Trip OP
0x95C2 OverFreq1 Trip OP Overfrequency 1 Trip OP
0x9602 OverFreq2 Trip OP Overfrequency 2 Trip OP
0x9882 Ph OV2 Trip OP Phase OV 2 Trip OP
0x988A Ph A OV2 Trip OP Phase A OV2 Trip OP
0x9892 Ph B OV2 Trip OP Phase B OV2 Trip OP
0x98A2 Ph C OV2 Trip OP Phase C OV2 Trip OP
0x98C2 Ph UV2 Trip OP Phase UV 2 Trip OP
0x98CA Ph A UV2 Trip OP Phase A UV2 Trip OP
0x98D2 Ph B UV2 Trip OP Phase B UV2 Trip OP
0x98E2 Ph C UV2 Trip OP Phase C UV2 Trip OP
0x9902 S/C Trip OP S/C Trip OP
0x9942 SPD2 S/C Trip OP SPD2 S/C Trip OP
0x9982 SPD2 U/C Trip OP SPD2 U/C Trip OP
0x9C02 LE 9 Trip OP Logic Element 9 Trip OP
0x9C42 LE 10 Trip OP Logic Element 10 Trip OP
0x9C82 LE 11 Trip OP Logic Element 11 Trip OP
0x9CC2 LE 12 Trip OP Logic Element 12 Trip OP
0x9D02 LE 13 Trip OP Logic Element 13 Trip OP
0x9D42 LE 14 Trip OP Logic Element 14 Trip OP
0x9D82 LE 15 Trip OP Logic Element 15 Trip OP
0x9DC2 LE 16 Trip OP Logic Element 16 Trip OP
FC134E unsigned 16 bits Fault Report Trigger
0 Off Off
0x8002 Any Trip Any Trip
0x8042 Therm O/L Trip OP Thermal Overload Trip OP
0x8082 GF Trip OP GF Trip OP
0x80C2 Accel Trip OP Acceleration Trip OP
0x8142 Under Pwr Trip OP Under Power Trip OP
0x8182 Single PH Trip OP Single PH Trip OP
0x8202 Mech Jam Trip OP Mech Jam Trip OP

10-166 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x8242 U/CURR Trip OP U/CURR Trip OP
0x8282 UNBAL Trip OP Unbalance Trip OP
0x82C2 RTD 1 Trip OP RTD 1 Trip OP
0x8302 RTD 2 Trip OP RTD 2 Trip OP
0x8342 RTD 3 Trip OP RTD 3 Trip OP
0x8382 RTD 4 Trip OP RTD 4 Trip OP
0x83C2 RTD 5 Trip OP RTD 5 Trip OP
0x8402 RTD 6 Trip OP RTD 6 Trip OP
0x84C2 LE 1 Trip OP Logic Element 1 Trip OP
0x8502 LE 2 Trip OP Logic Element 2 Trip OP
0x8542 LE 3 Trip OP Logic Element 3 Trip OP
0x8582 LE 4 Trip OP Logic Element 4 Trip OP
0x85C2 LE 5 Trip OP Logic Element 5 Trip OP
0x8602 LE 6 Trip OP Logic Element 6 Trip OP
0x8642 LE 7 Trip OP Logic Element 7 Trip OP
0x8682 LE 8 Trip OP Logic Element 8 Trip OP
0x86C2 RTD 7 Trip OP RTD 7 Trip OP
0x8702 RTD 8 Trip OP RTD 8 Trip OP
0x8742 RTD 9 Trip OP RTD 9 Trip OP
0x8782 RTD 10 Trip OP RTD 10 Trip OP
0x87C2 RTD 11 Trip OP RTD 11 Trip OP
0x8802 RTD 12 Trip OP RTD 12 Trip OP
0x8842 PosSeq UV1 Trip OP Positive Sequence UV 1 Trip OP
0x8902 PosSeq UV2 Trip OP Positive Sequence UV 2 Trip OP
0x89C2 Self Test OP Self Test OP
0x8F82 Fuse Fail Trip OP Fuse Fail Trip OP
0x8FC2 Ph Revrsl Trip OP Ph Revrsl Trip OP
0x9042 Ntrl IOC1 Trip OP Neutral IOC 1 Trip OP
0x90C2 Ph TOC1 Trip OP Phase TOC 1 Trip OP
0x90CA Ph A TOC1 Trip OP Phase A TOC 1 Trip OP
0x90D2 Ph B TOC1 Trip OP Phase B TOC 1 Trip OP
0x90E2 Ph C TOC1 Trip OP Phase C TOC 1 Trip OP
0x9102 Ntrl TOC1 Trip OP Neutral TOC 1 Trip OP
0x9242 Dir Pwr 1 Trip OP Directional Pwr 1 Trip OP
0x9282 Dir Pwr 2 Trip OP Directional Pwr 2 Trip OP
0x93C2 NSeq OV Trp OP Negative Sequence OV Trip OP
0x9442 Ph OV1 Trip OP Phase OV 1 Trip OP
0x944A Ph A OV1 Trip OP Phase A OV1 Trip OP
0x9452 Ph B OV1 Trip OP Phase B OV1 Trip OP
0x9462 Ph C OV1 Trip OP Phase C OV1 Trip OP
0x9482 Ph UV1 Trip OP Phase UV 1 Trip OP
0x948A Ph A UV1 Trip OP Phase A UV1 Trip OP
0x9492 Ph B UV1 Trip OP Phase B UV1 Trip OP
0x94A2 Ph C UV1 Trip OP Phase C UV1 Trip OP
0x9542 UndrFreq1 Trip OP Underfrequency 1 Trip OP
0x9582 UndrFreq2 Trip OP Underfrequency 2 Trip OP
0x95C2 OverFreq1 Trip OP Overfrequency 1 Trip OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-167


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x9602 OverFreq2 Trip OP Overfrequency 2 Trip OP
0x9882 Ph OV2 Trip OP Phase OV 2 Trip OP
0x988A Ph A OV2 Trip OP Phase A OV2 Trip OP
0x9892 Ph B OV2 Trip OP Phase B OV2 Trip OP
0x98A2 Ph C OV2 Trip OP Phase C OV2 Trip OP
0x98C2 Ph UV2 Trip OP Phase UV 2 Trip OP
0x98CA Ph A UV2 Trip OP Phase A UV2 Trip OP
0x98D2 Ph B UV2 Trip OP Phase B UV2 Trip OP
0x98E2 Ph C UV2 Trip OP Phase C UV2 Trip OP
0x9902 S/C Trip OP S/C Trip OP
0x9942 SPD2 S/C Trip OP SPD2 S/C Trip OP
0x9982 SPD2 U/C Trip OP SPD2 U/C Trip OP
0x9C02 LE 9 Trip OP Logic Element 9 Trip OP
0x9C42 LE 10 Trip OP Logic Element 10 Trip OP
0x9C82 LE 11 Trip OP Logic Element 11 Trip OP
0x9CC2 LE 12 Trip OP Logic Element 12 Trip OP
0x9D02 LE 13 Trip OP Logic Element 13 Trip OP
0x9D42 LE 14 Trip OP Logic Element 14 Trip OP
0x9D82 LE 15 Trip OP Logic Element 15 Trip OP
0x9DC2 LE 16 Trip OP Logic Element 16 Trip OP
FC134F unsigned 16 bits Lockout Reset
0 Off Off
0x0001 On On
0x0040 Contact IN 1 On Contact Input 1 On
0x0041 Contact IN 2 On Contact Input 2 On
0x0042 Contact IN 3 On Contact Input 3 On
0x0043 Contact IN 4 On Contact Input 4 On
0x0044 Contact IN 5 On Contact Input 5 On
0x0045 Contact IN 6 On Contact Input 6 On
0x0046 Contact IN 7 On Contact Input 7 On
0x0047 Contact IN 8 On Contact Input 8 On
0x0048 Contact IN 9 On Contact Input 9 On
0x0049 Contact IN 10 On Contact Input 10 On
0x0060 Contact IN 1 Off Contact Input 1 Off
0x0061 Contact IN 2 Off Contact Input 2 Off
0x0062 Contact IN 3 Off Contact Input 3 Off
0x0063 Contact IN 4 Off Contact Input 4 Off
0x0064 Contact IN 5 Off Contact Input 5 Off
0x0065 Contact IN 6 Off Contact Input 6 Off
0x0066 Contact IN 7 Off Contact Input 7 Off
0x0067 Contact IN 8 Off Contact Input 8 Off
0x0068 Contact IN 9 Off Contact Input 9 Off
0x0069 Contact IN 10 Off Contact Input 10 Off
0x0080 Virtual IN 1 On Virtual Input 1 On
0x0081 Virtual IN 2 On Virtual Input 2 On
0x0082 Virtual IN 3 On Virtual Input 3 On
0x0083 Virtual IN 4 On Virtual Input 4 On

10-168 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x0084 Virtual IN 5 On Virtual Input 5 On
0x0085 Virtual IN 6 On Virtual Input 6 On
0x0086 Virtual IN 7 On Virtual Input 7 On
0x0087 Virtual IN 8 On Virtual Input 8 On
0x0088 Virtual IN 9 On Virtual Input 9 On
0x0089 Virtual IN 10 On Virtual Input 10 On
0x008A Virtual IN 11 On Virtual Input 11 On
0x008B Virtual IN 12 On Virtual Input 12 On
0x008C Virtual IN 13 On Virtual Input 13 On
0x008D Virtual IN 14 On Virtual Input 14 On
0x008E Virtual IN 15 On Virtual Input 15 On
0x008F Virtual IN 16 On Virtual Input 16 On
0x0090 Virtual IN 17 On Virtual Input 17 On
0x0091 Virtual IN 18 On Virtual Input 18 On
0x0092 Virtual IN 19 On Virtual Input 19 On
0x0093 Virtual IN 20 On Virtual Input 20 On
0x0094 Virtual IN 21 On Virtual Input 21 On
0x0095 Virtual IN 22 On Virtual Input 22 On
0x0096 Virtual IN 23 On Virtual Input 23 On
0x0097 Virtual IN 24 On Virtual Input 24 On
0x0098 Virtual IN 25 On Virtual Input 25 On
0x0099 Virtual IN 26 On Virtual Input 26 On
0x009A Virtual IN 27 On Virtual Input 27 On
0x009B Virtual IN 28 On Virtual Input 28 On
0x009C Virtual IN 29 On Virtual Input 29 On
0x009D Virtual IN 30 On Virtual Input 30 On
0x009E Virtual IN 31 On Virtual Input 31 On
0x009F Virtual IN 32 On Virtual Input 32 On
0xA4C2 LE 1 Alarm OP Logic Element 1 Alarm OP
0xA502 LE 2 Alarm OP Logic Element 2 Alarm OP
0xA542 LE 3 Alarm OP Logic Element 3 Alarm OP
0xA582 LE 4 Alarm OP Logic Element 4 Alarm OP
0xA5C2 LE 5 Alarm OP Logic Element 5 Alarm OP
0xA602 LE 6 Alarm OP Logic Element 6 Alarm OP
0xA642 LE 7 Alarm OP Logic Element 7 Alarm OP
0xA682 LE 8 Alarm OP Logic Element 8 Alarm OP
0xBC02 LE 9 Alarm OP Logic Element 9 Alarm OP
0xBC42 LE 10 Alarm OP Logic Element 10 Alarm OP
0xBC82 LE 11 Alarm OP Logic Element 11 Alarm OP
0xBCC2 LE 12 Alarm OP Logic Element 12 Alarm OP
0xBD02 LE 13 Alarm OP Logic Element 13 Alarm OP
0xBD42 LE 14 Alarm OP Logic Element 14 Alarm OP
0xBD82 LE 15 Alarm OP Logic Element 15 Alarm OP
0xBDC2 LE 16 Alarm OP Logic Element 16 Alarm OP
0xC4C2 LE 1 OP Logic Element 1 OP
0xC502 LE 2 OP Logic Element 2 OP
0xC542 LE 3 OP Logic Element 3 OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-169


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xC582 LE 4 OP Logic Element 4 OP
0xC5C2 LE 5 OP Logic Element 5 OP
0xC602 LE 6 OP Logic Element 6 OP
0xC642 LE 7 OP Logic Element 7 OP
0xC682 LE 8 OP Logic Element 8 OP
0xDC02 LE 9 OP Logic Element 9 OP
0xDC42 LE 10 OP Logic Element 10 OP
0xDC82 LE 11 OP Logic Element 11 OP
0xDCC2 LE 12 OP Logic Element 12 OP
0xDD02 LE 13 OP Logic Element 13 OP
0xDD42 LE 14 OP Logic Element 14 OP
0xDD82 LE 15 OP Logic Element 15 OP
0xDDC2 LE 16 OP Logic Element 16 OP
FC135 unsigned 16 bits Motor Speed During Trip / Motor Speed
During Event
0 Low Speed Low Speed
1 High Speed High Speed
FC136 unsigned 16 bits Motor Speed During Trip / Motor Speed
During Event
0 None None
1 A A
2 B B
FC139 unsigned 16 bits Starter Type
0 None None
1 FV Nonreversing Full Voltage Nonreversing
2 FV Reversing Full Voltage Reversing
3 Two Speed Two Speed
4 Wye-Delta Wye-Delta
5 Inverter Inverter
6 Soft Starter Soft Starter
7 Custom Starter Custom Starter
FC140 unsigned 16 bits Interlock Function
0 Disabled Disabled
1 Trip Trip
2 Alarm Alarm
FC141 unsigned 16 bits Timer Type
0 Millisecond Millisecond
1 Second Second
2 Minute Minute
FC142 unsigned 16 bits FlexLogic Bit Field EEETTTTTTTSSSSSS
0x0000 Off Off
0x0001 On On
0x0040 Contact Inputs Contact Inputs
0x0080 Virtual Inputs Virtual Inputs
0x00C0 Virtual Outputs Virtual Outputs
0x01C0 Remote Inputs Remote Inputs
0x0380 Insert Insert

10-170 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x0400 End End
0x0440 NOT NOT
0x0480 XOR XOR
0x04C0 LATCH LATCH
0x0500 OR OR
0x0540 AND AND
0x0580 NOR NOR
0x05C0 NAND NAND
0x0600 TIMER TIMER
0x0640 ASSIGN ASSIGN
0x8000 Trip Trip
0x9241 Dir Pwr 1 Trip PKP Directional Pwr 1 Trip PKP
0x9242 Dir Pwr 1 Trip OP Directional Pwr 1 Trip OP
0x9281 Dir Pwr 2 Trip PKP Directional Pwr 2 Trip PKP
0x9282 Dir Pwr 2 Trip OP Directional Pwr 2 Trip OP
0xA000 Alarm Alarm
0xA9C1 CTFail Alrm PKP CT Fail Alarm PKP
0xA9C2 CTFail Alrm OP CT Fail Alarm OP
0xA9C4 CTFail Alrm DPO CT Fail Alarm DPO
0xB241 Dir Pwr 1 Alrm PKP Directional Pwr 1 Alarm PKP
0xB242 Dir Pwr 1 Alarm OP Directional Pwr 1 Alarm OP
0xB281 Dir Pwr 2 Alrm PKP Directional Pwr 2 Alarm PKP
0xB282 Dir Pwr 2 Alarm OP Directional Pwr 2 Alarm OP
0xC000 Control Control
0xC742 VFD Bypassed VFD Bypassed
0xC744 VFD Not Bypassed VFD Not Bypassed
0xC9C1 CTFail PKP CT Fail PKP
0xC9C2 CTFail OP CT Fail OP
0xC9C4 CTFail DPO CT Fail DPO
0xD241 Dir Pwr 1 PKP Directional Pwr 1 PKP
0xD242 Dir Pwr 1 OP Directional Pwr 1 OP
0xD281 Dir Pwr 2 PKP Directional Pwr 2 PKP
0xD282 Dir Pwr 2 OP Directional Pwr 2 OP
0xE9C2 CTFail Block CT Fail Block
0xF242 Dir Pwr 1 Block Directional Pwr 1 Block
0xF282 Dir Pwr 2 Block Directional Pwr 2 Block
FC143 unsigned 16 bits Drive Status
0 Drive Unavailable Drive Unavailable
1 Available Auto Available Auto
2 Available Manual Available Manual
3 Available Available
4 Running Running
5 ESD Trip / Stop ESD Trip / Stop
FC144 unsigned 32 bits LED Status - 350
FC144A unsigned 32 bits LED Status - 339
0x00000300 Hot RTD Amber Hot RTD Amber
0x00000400 Running Red Running Red

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-171


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x00000800 Running Green Running Green
0x00000C00 Running Amber Running Amber
0x00001000 Starting Red Starting Red
0x00002000 Starting Green Starting Green
0x00003000 Starting Amber Starting Amber
0x00004000 Stopped Red Stopped Red
0x00008000 Stopped Green Stopped Green
0x0000C000 Stopped Amber Stopped Amber
0x00030000 Maintenance Amber Maintenance Amber
0x000C0000 Pickup Amber Pickup Amber
0x00300000 Alarm Amber Alarm Amber
0x00400000 Trip Red Trip Red
0x01000000 Start Inhibit Red Start Inhibit Red
0x04000000 Lockout Red Lockout Red
0x30000000 Trouble Amber Trouble Amber
0x80000000 In Service Green In Service Green
FC144B unsigned 32 bits LED Status - 345
FC145 unsigned 16 bits Element Status 1
FC146 unsigned 16 bits Element Status 2
FC147 unsigned 16 bits LED Intensity
0 Level 1 Level 1
12 Level 5 Level 5
15 Level 6 Level 6
3 Level 2 Level 2
6 Level 3 Level 3
9 Level 4 Level 4
FC148 unsigned 16 bits Trigger Mode
0 Overwrite Overwrite
1 Protected Protected
FC149 unsigned 16 bits OR / AND Selection
0 OR OR
1 AND AND
2 NOR NOR
3 NAND NAND
4 XOR XOR
5 XNOR XNOR
FC149A unsigned 16 bits AND / LATCH Selection
0 AND AND
1 LATCH LATCH
FC150 unsigned 32 bits IP Address
FC155 unsigned 16 bits Profibus Baud Rate
0x0001 9600 9600
0x0002 19200 19200
0x0004 31250 31250
0x0008 45450 45450
0x0010 93750 93750
0x0020 187500 187500

10-172 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x0040 500000 500000
0x0080 1500000 1500000
0x07E2 Auto Detect Auto Detect
FC156 unsigned 16 bits DeviceNet Baud Rate
0 125 kbps 125 kbps
1 250 kbps 250 kbps
2 500 kbps 500 kbps
FC157 unsigned 16 bits LED Colour
0 Off Off
1 Red Red
2 Green Green
3 Orange Orange
FC157A unsigned 16 bits LED Colour (Subset A)
0 None None
1 Red Red
2 Green Green
FC160 unsigned 16 bits Auto/Manual Mode
0 Auto Auto
1 Manual Manual
FC167 unsigned 32 bits Contact/Virtual Input/Output Status
FC168 unsigned 32 bits Contact/Virtual Input/Output Status
FC169 unsigned 16 bits Month
0 Not Set Not Set
1 January January
2 February February
3 March March
4 April April
5 May May
6 June June
7 July July
8 August August
9 September September
10 October October
11 November November
12 December December
FC170 unsigned 16 bits Count of Week
0 Not Set Not Set
1 1st 1st
2 2nd 2nd
3 3rd 3rd
4 4th 4th
5 Last Last
FC171 unsigned 16 bits Weekdays
0 Not Set Not Set
1 SUN SUN
2 MON MON
3 TUE TUE

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-173


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


4 WED WED
5 THU THU
6 FRI FRI
7 SAT SAT
FC172 unsigned 16 bits Auto/Manual Control Stop Mode
0 Always Enabled Always Enabled
1 Follow Ctrl Mode Follow Control Mode
FC173 unsigned 16 bits Wire Selection
0 2W 2W
1 3W 3W
FC174 unsigned 16 bits Source Stop Action
0 Stop Stop
1 Trip Trip
FC175 unsigned 16 bits Test Auto/Manual Mode
0 On On
1 Off Off
2 Unaffected Unaffected
FC176 unsigned 16 bits Auxiliary VT Connection
0 Vab VT Vab VT
1 Vbc VT Vbc VT
2 Vca VT Vca VT
3 Van VT Van VT
4 Vbn VT Vbn VT
5 Vcn VT Vcn VT
FC177 unsigned 16 bits LED Color Invert
0 Green/Red Green/Red
1 Red/Green Red/Green
FC178 unsigned 16 bits Motor Status
0x0000 Lockout Lockout
0x0001 Non-Lockout Trip Non-Lockout Trip
0x0040 Tripped Tripped
0x0080 Overload Overload
0x00C0 Running Running
0x01C0 Overload Lockout Overload Lockout
0x0380 Starting Starting
0x0400 Stopping Stopping
0x0440 Inhibit Inhibit
0x0480 Stopped Stopped
0x04C0 Self Test Fault Self Test Fault
0x0500 Alarm Alarm
0x0540 Forward Forward
0x0580 Reverse Reverse
0x05C0 Low Speed Low Speed
0x0600 High Speed High Speed
FC179 unsigned 32 bits Alarm Status 1
0x00000001 Any Alarm Any Alarm
0x00000002 Therm Level Alarm Thermal Level Alarm

10-174 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x00000004 Gnd Fault Alarm Gnd Fault Alarm
0x00000008 Acceleration Alarm Acceleration Alarm
0x00000020 Under Pwr Alarm Under Power Alarm
0x00000040 Reserved Reserved
0x00000080 Reserved Reserved
0x00000100 Mech Jam Alarm Mechanical Jam Alarm
0x00000200 Under Curr Alarm Undercurrent Alarm
0x00000400 Unbalance Alarm Unbalance Alarm
0x00000800 RTD 1 Alarm RTD 1 Alarm
0x00001000 RTD 2 Alarm RTD 2 Alarm
0x00002000 RTD 3 Alarm RTD 3 Alarm
0x00004000 RTD 4 Alarm RTD 4 Alarm
0x00008000 RTD 5 Alarm RTD 5 Alarm
0x00010000 RTD 6 Alarm RTD 6 Alarm
0x00020000 RTD Trouble Alarm RTD Trouble Alarm
0x00040000 Not Configured Not Configured
0x00080000 LE 1 Alarm Logic Element 1 Alarm
0x00100000 LE 2 Alarm Logic Element 2 Alarm
0x00200000 LE 3 Alarm Logic Element 3 Alarm
0x00400000 LE 4 Alarm Logic Element 4 Alarm
0x00800000 LE 5 Alarm Logic Element 5 Alarm
0x01000000 LE 6 Alarm Logic Element 6 Alarm
0x02000000 LE 7 Alarm Logic Element 7 Alarm
0x04000000 LE 8 Alarm Logic Element 8 Alarm
0x08000000 RTD 7 Alarm RTD 7 Alarm
0x10000000 RTD 8 Alarm RTD 8 Alarm
0x20000000 RTD 9 Alarm RTD 9 Alarm
0x40000000 RTD 10 Alarm RTD 10 Alarm
0x80000000 RTD 11 Alarm RTD 11 Alarm
FC180 unsigned 32 bits Alarm Status 2
0x00000001 RTD 12 Alarm RTD 12 Alarm
0x00000002 Reserved Reserved
0x00000004 Reserved Reserved
0x00000008 Reserved Reserved
0x00000010 Reserved Reserved
0x00000020 Reserved Reserved
0x00000040 Motor Run Hrs Motor Running Hours
0x00000080 I^2 Counter Alarm I^2 Counter Alarm
0x00000100 Welded Contactor Welded Contactor
0x00000200 SPD SW Not Config SPD SW Not Config
0x00000400 SPD SW Fail SPD SW Fail
0x00000800 Reserved Reserved
0x00001000 Load Increase Alrm Load Increase Alarm
0x00002000 Reserved Reserved
0x00004000 Reserved Reserved
0x00008000 High Ambient Temp High Ambient Temperature Alarm
0x00010000 Low Ambient Temp Low Ambient Temperature Alarm

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-175


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x00020000 Self Test Alarm Self Test Alarm
0x00040000 Comm Fail Alarm Comm Fail Alarm
0x00080000 BKRTrip Cntr Alarm Breaker Trip Counter Alarm
0x00100000 Rly1 74 Alarm Relay 1 74 Alarm
0x00200000 Rly2 74 Alarm Relay 2 74 Alarm
0x00400000 BKR Fail Alarm Breaker Fail Alarm
0x00800000 BKR Status Failure Breaker Status Failure
0x01000000 Reserved Reserved
0x02000000 CLP Alarm Cold Load PKP Alarm
0x04000000 Reserved Reserved
0x08000000 BKR2 Status Fail Breaker 2 Status Failure
0x10000000 Reserved Reserved
0x20000000 BKR2 Fail Alrm Breaker 2 Failure Alarm
0x40000000 FuseFail Alarm Fuse Fail Alarm
0x80000000 Ph Revrsl Alarm Phase Reversal Alarm
FC181 unsigned 32 bits Alarm Status 3
0x00000001 Ph IOC1 Alarm Phase IOC 1 Alarm
0x00000002 Ntrl IOC1 Alarm Neutral IOC 1 Alarm
0x00000004 Gnd IOC1 Alarm Ground IOC 1 Alarm
0x00000008 Ph TOC1 Alarm Phase TOC 1 Alarm
0x00000020 Gnd TOC1 Alarm Sensitive Ground TOC 1 Alarm
0x00000040 Ph IOC2 Alarm Phase IOC 2 Alarm
0x00000080 Ntrl IOC2 Alarm Neutral IOC 2 Alarm
0x00000100 Gnd IOC2 Alarm Ground IOC 2 Alarm
0x00000200 Ph TOC2 Alrm Phase TOC 2 Alarm
0x00000800 Gnd TOC2 Alrm Sensitive Ground TOC 2 Alarm
0x00001000 SGnd TOC1 Alarm Sensitive Ground TOC 1 Alarm
0x00002000 Ntrl Dir Rev Alm Neutral Directional Alarm
0x00008000 NSeq OV Alarm Negative Sequence OV Alarm
0x00010000 Ntrl OV Alarm Ntrl OV Alarm
0x00020000 Phase OV Alarm Phase OV Alarm
0x00040000 Phase UV Alarm Phase UV Alarm
0x00080000 Aux OV Alarm Auxiliary OV Alarm
0x00100000 Aux UV Alarm Auxiliary UV Alarm
0x00200000 UnderFreq1 Alarm Underfrequency 1 Alarm
0x00400000 UnderFreq2 Alarm Underfrequency 2 Alarm
0x00800000 OverFreq1 Alrm Overfrequency 1 Alarm
0x01000000 OverFreq2 Alrm Overfrequency 2 Alarm
0x02000000 SGnd IOC1 Alarm Sensitive Ground IOC 1 Alarm
0x04000000 SGnd IOC2 Alarm Sensitive Ground IOC 2 Alarm
0x10000000 Diff 87P Alarm Diff 87P Alarm
0x20000000 Diff 87REF 1 Alarm Diff 87REF 1 Alarm
0x40000000 Diff 87REF 2 Alarm Diff 87REF 2 Alarm
0x80000000 Inst 50/87P Alarm Inst 50/87P Alarm
FC182 unsigned 32 bits Alarm Status 4
0x00000004 Ph OV2 Alarm Phase OV 2 Alarm
0x00000008 Ph UV2 Alarm Phase UV 2 Alarm

10-176 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x00000010 Short Circuit Alrm Short Circuit Alarm
0x00000020 SPD2 S/C Alarm SPD2 S/C Alarm
0x00000040 SPD2 U/C Alarm SPD2 U/C Alarm
0x00000080 SGnd TOC2 Alarm Sensitive Ground TOC 2 Alarm
0x00000100 Reserved Reserved
0x00000200 Reserved Reserved
0x00000400 Reserved Reserved
0x00000800 Reserved Reserved
0x00001000 Reserved Reserved
0x00002000 Reserved Reserved
0x00004000 Reserved Reserved
0x00008000 Reserved Reserved
0x00010000 LE 9 Alarm Logic Element 9 Alarm
0x00020000 LE 10 Alarm Logic Element 10 Alarm
0x00040000 LE 11 Alarm Logic Element 11 Alarm
0x00080000 LE 12 Alarm Logic Element 12 Alarm
0x00100000 LE 13 Alarm Logic Element 13 Alarm
0x00200000 LE 14 Alarm Logic Element 14 Alarm
0x00400000 LE 15 Alarm Logic Element 15 Alarm
0x00800000 LE 16 Alarm Logic Element 16 Alarm
0x01000000 Reserved Reserved
0x02000000 Reserved Reserved
0x04000000 Reserved Reserved
0x08000000 Reserved Reserved
0x10000000 Reserved Reserved
0x20000000 Reserved Reserved
0x40000000 Reserved Reserved
0x80000000 Reserved Reserved
FC183 unsigned 32 bits Trip Status 1
0x00000001 Any Trip Any Trip
0x00000002 Therm O/L Trip Thermal O/L Trip
0x00000004 Gnd Fault Trip Gnd Fault Trip
0x00000008 Acceleration Trip Acceleration Trip
0x00000020 Under Pwr Trip Under Power Trip
0x00000040 Single Phase Trip Single Phase Trip
0x00000080 Reserved Reserved
0x00000100 Mech Jam Trip Mechanical Jam Trip
0x00000200 Under Curr Trip Undercurrent Trip
0x00000400 Unbalance Trip Unbalance Trip
0x00000800 RTD 1 Trip RTD 1 Trip
0x00001000 RTD 2 Trip RTD 2 Trip
0x00002000 RTD 3 Trip RTD 3 Trip
0x00004000 RTD 4 Trip RTD 4 Trip
0x00008000 RTD 5 Trip RTD 5 Trip
0x00010000 RTD 6 Trip RTD 6 Trip
0x00020000 Comm Fail Trip Comm Fail Trip
0x00040000 Relay Not Config. Relay Not Configured

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-177


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x00080000 LE 1 Trip Logic Element 1 Trip
0x00100000 LE 2 Trip Logic Element 2 Trip
0x00200000 LE 3 Trip Logic Element 3 Trip
0x00400000 LE 4 Trip Logic Element 4 Trip
0x00800000 LE 5 Trip Logic Element 5 Trip
0x01000000 LE 6 Trip Logic Element 6 Trip
0x02000000 LE 7 Trip Logic Element 7 Trip
0x04000000 LE 8 Trip Logic Element 8 Trip
0x08000000 RTD 7 Trip RTD 7 Trip
0x10000000 RTD 8 Trip RTD 8 Trip
0x20000000 RTD 9 Trip RTD 9 Trip
0x40000000 RTD 10 Trip RTD 10 Trip
0x80000000 RTD 11 Trip RTD 11 Trip
FC184 unsigned 32 bits Trip Status 2
0x00000001 RTD 12 Trip RTD 12 Trip
0x00000002 Reserved Reserved
0x00000004 Reserved Reserved
0x00000008 Reserved Reserved
0x00000010 Reserved Reserved
0x00000020 Reserved Reserved
0x00000040 Reserved Reserved
0x00000080 Self Test Trip Self Test Trip
0x00000100 Reserved Reserved
0x00000200 Reserved Reserved
0x00000400 Reserved Reserved
0x00000800 Reserved Reserved
0x00001000 Reserved Reserved
0x00002000 Reserved Reserved
0x00004000 Reserved Reserved
0x00008000 Reserved Reserved
0x00010000 Reserved Reserved
0x00020000 Reserved Reserved
0x00040000 Reserved Reserved
0x00080000 BKRTrip Cntr Trip Breaker Trip Counter Trip
0x00100000 Rly1 74 Trip Relay 1 74 Trip
0x00200000 Rly2 74 Trip Relay 2 74 Trip
0x00400000 BKR Failure Breaker Failure
0x00800000 Reserved Reserved
0x01000000 Reserved Reserved
0x02000000 Reserved Reserved
0x04000000 Reserved Reserved
0x08000000 Reserved Reserved
0x10000000 Reserved Reserved
0x20000000 BKR 2 Failure Breaker 2 Failure
0x40000000 FuseFail Trip FuseFail Trip
0x80000000 Ph Revrsl Trip Phase Reversal Trip
FC185 unsigned 32 bits Trip Status 3

10-178 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x00000001 Ph IOC1 Trip Phase IOC 1 Trip
0x00000002 Ntrl IOC1 Trip Neutral IOC 1 Trip
0x00000004 Gnd IOC1 Trip Ground IOC 1 Trip
0x00000008 Ph TOC1 Trip Phase TOC 1 Trip
0x00000020 Gnd TOC1 Trip Sensitive Ground TOC 1 Trip
0x00000040 Ph IOC2 Trip Phase IOC 2 Trip
0x00000080 Ntrl IOC2 Trip Neutral IOC 2 Trip
0x00000100 Gnd IOC2 Trip Ground IOC 2 Trip
0x00000200 Ph TOC2 Trip Phase TOC 2 Trip
0x00000800 Gnd TOC2 Trip Sensitive Ground TOC 2 Trip
0x00001000 SGnd TOC1 Trip Sensitive Ground TOC 1 Trip
0x00002000 Reserved Reserved
0x00004000 Reserved Reserved
0x00008000 NSeq OV Trip Negative Sequence OV Trip
0x00010000 Ntrl OV Trip Ntrl OV Trip
0x00020000 Phase OV Trip Phase OV Trip
0x00040000 Phase UV Trip Phase UV Trip
0x00080000 Aux OV Trip Auxiliary OV Trip
0x00100000 Aux UV Trip Auxiliary UV Trip
0x00200000 UnderFreq1 Trip Underfrequency 1 Trip
0x00400000 UnderFreq2 Trip Underfrequency 2 Trip
0x00800000 OVERFREQ1 TRIP Overfrequency 1 Trip
0x01000000 OVERFREQ2 TRIP Overfrequency 2 Trip
0x02000000 SGnd IOC1 Trip Sensitive Ground IOC 1 Trip
0x04000000 SGnd IOC2 Trip Sensitive Ground IOC 2 Trip
0x10000000 Diff 87P Trip Diff 87P Trip
0x20000000 Diff 87REF 1 Trip Diff 87REF 1 Trip
0x40000000 Diff 87REF 2 Trip Diff 87REF 2 Trip
0x80000000 Inst 50/87P Trip Inst 50/87P Trip
FC186 unsigned 32 bits Trip Status 4
0x00000004 Phase OV 2 Trip Phase OV 2 Trip
0x00000008 Phase UV 2 Trip Phase UV 2 Trip
0x00000010 Short Circuit Trip Short Circuit Trip
0x00000020 SPD2 S/C Trip SPD2 S/C Trip
0x00000040 SPD2 U/C Trip SPD2 U/C Trip
0x00000080 SGnd TOC2 Trip Sensitive Ground TOC 2 Trip
0x00000100 Reserved Reserved
0x00000200 Reserved Reserved
0x00000400 Reserved Reserved
0x00000800 Reserved Reserved
0x00001000 Reserved Reserved
0x00002000 Reserved Reserved
0x00004000 Reserved Reserved
0x00008000 Reserved Reserved
0x00010000 LE 9 Trip Logic Element 9 Trip
0x00020000 LE 10 Trip Logic Element 10 Trip
0x00040000 LE 11 Trip Logic Element 11 Trip

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-179


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x00080000 LE 12 Trip Logic Element 12 Trip
0x00100000 LE 13 Trip Logic Element 13 Trip
0x00200000 LE 14 Trip Logic Element 14 Trip
0x00400000 LE 15 Trip Logic Element 15 Trip
0x00800000 LE 16 Trip Logic Element 16 Trip
0x01000000 Reserved Reserved
0x02000000 Reserved Reserved
0x04000000 Reserved Reserved
0x08000000 Reserved Reserved
0x10000000 Reserved Reserved
0x20000000 Reserved Reserved
0x40000000 Reserved Reserved
0x80000000 Reserved Reserved
FC187 unsigned 32 bits Message Status 1
FC188 unsigned 32 bits Message Status 2
FC189 unsigned 32 bits Message Status 3
FC190 unsigned 32 bits Message Status 4
FC191 unsigned 32 bits Ctrl Element Status 1
FC192 unsigned 32 bits Ctrl Element Status 2
FC193 unsigned 32 bits Ctrl Status 3
FC194 unsigned 32 bits Ctrl Status 4
FC195 unsigned 16 bits Command Status
0 Normal Normal
1 Gain Forced to X1 Gain Forced to X1
FC196 unsigned 16 bits Digital Alarm
0 Active Low Active Low
1 Active High Active High
FC197 unsigned 16 bits Breaker Counter Alarm
0 Disabled Disabled
1 Alarm Alarm
2 Latched Alarm Latched Alarm
3 Trip Trip
FC198 unsigned 16 bits Output Relay Operation
FC199 unsigned 16 bits Output Relay Type
0 Self-Reset Self-Reset
1 Latched Latched
FC200 unsigned 32 bits Block Status 1
FC201 unsigned 32 bits Block Status 2
FC202 unsigned 32 bits Block Status 3
FC203 unsigned 32 bits Block Status 4
FC204 unsigned 16 bits Contact Input FlexLogic Bit Field Values
0x0000 Disabled Disabled
0x0040 Contact Input 1 Contact Input 1
0x0041 Contact Input 2 Contact Input 2
0x0042 Contact Input 3 Contact Input 3
0x0043 Contact Input 4 Contact Input 4
0x0044 Contact Input 5 Contact Input 5

10-180 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x0045 Contact Input 6 Contact Input 6
0x0046 Contact Input 7 Contact Input 7
0x0047 Contact Input 8 Contact Input 8
0x0048 Contact Input 9 Contact Input 9
0x0049 Contact Input 10 Contact Input 10
FC204A unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset A)
0x0000 Disabled Disabled
0x0040 Contact Input 1 Contact Input 1
FC204B unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset B)
0x0000 Disabled Disabled
0x0042 Contact Input 3 Contact Input 3
0x0043 Contact Input 4 Contact Input 4
0x0044 Contact Input 5 Contact Input 5
0x0045 Contact Input 6 Contact Input 6
0x0046 Contact Input 7 Contact Input 7
0x0047 Contact Input 8 Contact Input 8
0x0048 Contact Input 9 Contact Input 9
0x0049 Contact Input 10 Contact Input 10
FC204C unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset C)
0x0000 Disabled Disabled
0x0041 Contact Input 2 Contact Input 2
FC204D unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset D)
0x0000 Disabled Disabled
0x0042 Contact Input 3 W2 Breaker 52a (CI#3)
FC204E unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset E)
0x0000 Disabled Disabled
0x0044 Contact Input 5 Contact Input 5
0x0045 Contact Input 6 Contact Input 6
0x0046 Contact Input 7 Contact Input 7
0x0047 Contact Input 8 Contact Input 8
0x0048 Contact Input 9 Contact Input 9
0x0049 Contact Input 10 Contact Input 10
FC204F unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset F)
0x0000 Disabled Disabled
0x0043 Contact Input 4 W2 Breaker 52b (CI#4)
FC205 unsigned 16 bits Element Type 1
0 Disabled Disabled
1 Alarm Alarm
2 Latched Alarm Latched Alarm
3 Trip Trip
4 Control Control
FC206 unsigned 16 bits Element Type 2
0 Disabled Disabled

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-181


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


1 Alarm Alarm
2 Latched Alarm Latched Alarm
FC207 unsigned 16 bits Element Type 3
0 Disabled Disabled
1 Alarm Alarm
2 Latched Alarm Latched Alarm
3 Control Control
FC208 unsigned 16 bits Relay Operation (Failsafe
0 Failsafe Failsafe
1 Non-Failsafe Non-Failsafe
FC212 unsigned 16 bits LCD Test Paint Color
0 None None
1 Red Red
2 Green Green
3 Blue Blue
FC214 unsigned 16 bits MAC Address
FC215 unsigned 32 bits GOOSE Receive Status
FC216 unsigned 16 bits Received GOOSE Message Formatting
0x0000 { {
0x0001 } }
0x0002 Bool Bool
0x0003 Byte Byte
0x0004 Ubyte Ubyte
0x0005 Short Short
0x0006 Ushort Ushort
0x0007 Long Long
0x0008 Ulong Ulong
0x0009 Int64 Int64
0x000A Uint64 Uint64
0x000B Float Float
0x000C Double Double
0x000D Btime4 Btime4
0x000E Btime6 Btime6
0x000F Utctime Utctime
0x0010 Bcd Bcd
0x0011 Vstring Vstring
0x0012 Ostring Ostring
0x0013 Ovstring Ovstring
0x0014 Bstring Bstring
0x0015 Bvstring Bvstring
0x00FF Row Row
FC217 unsigned 16 bits Remote Input Item Source
FC218 unsigned 16 bits Remote Input Item Mask
FC219 unsigned 32 bits GOOSE Source
0x0000 Disabled Disabled
0x0001 1 1
0x0002 2 2

10-182 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


0x0004 3 3
0x0008 4 4
0x0010 5 5
0x0020 6 6
0x0040 7 7
0x0080 8 8
FC220 unsigned 16 bits Remote Input Default State
0 On On
1 Off Off
2 Latest/On Latest/On
3 Latest/Off Latest/Off
FC221 unsigned 16 bits IEC103 ASDU Identification Type
3 3 3
9 9 9
FC222 unsigned 16 bits GOOSE Type
0 Simplified Simplified
1 Advanced Advanced
FC225 unsigned 16 bits Security Audit Trail Change Method
0 Unknown Unknown
1 USB USB
2 COM1 COM1
3 Ethernet Ethernet
4 KeyPad KeyPad
FC226 unsigned 16 bits Security Audit Trail Event Type
0 Unknown Unknown
1 Setpoint Change Setpoint Change
2 Firmware File Firmware File
3 Factory Reload Factory Reload
4 Setpoint File Setpoint File
FC230 unsigned 16 bits Ethernet Connection Type
0 Copper Copper
1 Fiber Fiber
FC235 unsigned 16 bits Switching Device
0 BKR Breaker
1 Contactor Contactor
FC236 unsigned 16 bits Thermal O/L Curve
0 Standard Standard
1 Flex Curve Flex Curve
FC240 unsigned 16 bits Self Test Error
0 None None
1 Order Code Error Order Code Error
2 RTC Error RTC Error
4 Cal Error Cal Error
8 EEPROM Error EEPROM Error
16 System Health System Health
17 PSU Serial# Blank PSU Serial# Blank
18 INP Serial# Blank INP Serial# Blank

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-183


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


19 ANLG Serial# Blank ANLG Serial# Blank
20 MAG Serial# Blank MAG Serial# Blank
21 COMM Serial# Blank COMM Serial# Blank
22 CCP Serial# Blank CCP Serial# Blank
23 CPU Serial# Blank CPU Serial# Blank
24 PSU Serial# Inval PSU Serial# Invalid
25 INP Serial# Inval INP Serial# Invalid
26 ANLG Serial# Inval ANLG Serial# Invalid
27 MAG Serial# Inval MAG Serial# Invalid
28 COMM Serial# Inval COMM Serial# Invalid
29 CCP Serial# Inval CCP Serial# Invalid
30 CPU Serial# Inval CPU Serial# Invalid
32 3.3V Error 3.3V Error
64 Analog V Error Analog V Error
128 DPRAM Checksum DPRAM Checksum
256 DPRAM Heart Beat DPRAM Heart Beat
512 COMM Error COMM Error
513 DAUGHTER Error DAUGHTER Error
514 COMM HW Rev Error COMM HW Revision Error
1024 Link Error Link Error
2048 Traffic Error Traffic Error
4096 Internal Temp Internal Temp
FC401 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 None None
FC402 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 None None
FC403 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 None None
FC404 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 Off Off
1 On On
FC405 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 100 Ohm Pt 100 Ohm Platinum
1 120 Ohm Ni 120 Ohm Nickel
2 100 Ohm Ni 100 Ohm Nickel
FC406 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 Off Off
1 On On
FC407 unsigned 16 bits PC Program Reserved for Output Relay
Bits (Do Not Use)
0 Disabled Disabled
3 3 3
4 4 4

10-184 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES 339 FORMAT CODES

Code Type Definition Long Definition


5 5 5
6 6 6
7 7 7
FC408 unsigned 16 bits Inrush Function
FC409 unsigned 16 bits Inhibit Mode
0 Per Phase Per Phase
1 2-out-of-3 2-out-of-3
2 Average Average
FC410 unsigned 16 bits Overexcitation Function
FC411 unsigned 16 bits Internal Compensation
0 Internal(software) Internal(software)
1 External(with CTs) External(with CTs)
FC412 unsigned 16 bits Winding Connection
0 Wye Wye
1 Delta Delta
2 Zig-Zag Zig-Zag
FC413 unsigned 16 bits Grounding Connection
0 Not Within zone Not Within zone
1 Within zone Within zone
FC415 unsigned 16 bits SR345 CT Type
0 1 A Secondary 1 A Secondary
1 5 A Secondary 5 A Secondary
FC418 unsigned 16 bits CT Inputs
FC419 unsigned 16 bits XFMR Type
FC420 unsigned 16 bits Modbus File Transfer State
0 Idle Idle
1 Write Write
2 Read Read
3 File Error File Error
4 File OK File OK
5 Start Start
6 Ready Ready
7 File Over File Over
FC421 unsigned 16 bits Redundancy type
FC422 unsigned 16 bits Redundancy Port
FC423 unsigned 16 bits Redundancy State
FC424 unsigned 16 bits Dead Condition
FC425 unsigned 16 bits Epoch type
FC426 unsigned 16 bits RSTP State
FC427 unsigned 16 bits WGF Curve Selection
0 Inverse Inverse
4 Definite Time Definite Time
8 Flex Curve A Flex Curve A
9 Flex Curve B Flex Curve B
FC428 unsigned 16 bits Fault Recorder Type
0 TOC A TOC A
1 TOC B TOC B

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 10-185


339 FORMAT CODES CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


2 TOC C TOC C
FC429 unsigned 16 bits Transient Sampling Rate
0 4 4
1 8 8
2 16 16
3 32 32
FC430 unsigned 16 bits Power Unit
0 Kw Kw
1 Mw Mw
FC431 unsigned 16 bits Demand Measurement Type
0 Blk Interval Blk Interval
1 Exponential Exponential
2 Rolling Dmd Rolling Dmd
FC432 unsigned 16 bits Demand Time
0 5 min 5 min
1 10 min 10 min
2 15 min 15 min
3 20 min 20 min
4 30 min 30 min
FC433 unsigned 16 bits BKR Alarm Counter
0 Detection Detection
1 Monitoring Monitoring
FC434 unsigned 16 bits 61850 NV Status
0 Unknown Unknown
1 Header Error Header Error
2 Parse Error Parse Error
3 Passed to Validated Passed to Validated
4 Empty Empty
FC435 unsigned 16 bits Volts Per Herz Voltage Mode
FC436 unsigned 16 bits Volts Per Herz Curves
None

10-186 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


GE
Grid Solutions

3 Series Protective Relay Platform

Chapter 11: 345 MODBUS memory


map and Format Codes

345 MODBUS memory map and Format Codes

The 339, 345, and 350 relays have different MODBUS maps and Format Codes. Make sure
NOTE:

you are looking at the chapter corresponding to your relay model.


NOTE

The Cause of Last trip register (MODBUS Address 30186) returns a combined value of
NOTE:

Pickup And Operate.


NOTE
For example, for a Phase TOC 1 Trip:
0x90C1 Ph TOC1 Trip PKP
0x90C2 Ph TOC1 Trip OP
Upon Phase TOC 1 Trip, the value read from 30186 Cause of Last Trip register is: 0x90C3

345 MODBUS memory map

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
PRODUCT INFORMATION
30001 0x0 Product Device Code 0 1 1 --- F22 L3 1
30002 0x1 Hardware Revision 0 26 1 --- F15 1 1
30003 0x2 Firmware Version 0 0xFFFF 1 --- F3 231 1
30006 0x5 Boot Version 0 0xFFFF 1 --- F3 100 1
30008 0x7 Serial Number 0 6 1 --- F22 L3MA09000 6
001
30014 0xD Order Code 0 16 1 --- F22 345- 16
EP5G5HEM
NNSNNN
30030 0x1D MAC Address 0 0xFFFF 1 --- FC214 0 3
30035 0x22 Comms HW Version 0 26 1 --- F15 0 1
30037 0x24 Build Date 0 6 1 --- F22 Unknown 6
30043 0x2A Build Time 0 4 1 --- F22 Unknown 4
30051 0x32 Comm Build Date 0 6 1 --- F22 Unknown 6

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-1


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
30057 0x38 Comm Build Time 0 4 1 --- F22 Unknown 4
30061 0x3C Comm Revision 0 0xFFFF 1 --- F3 231 1
30063 0x3E Comm Boot Code Revision 0 0xFFFF 1 --- F3 200 1
30068 0x43 FPGA Revision 0 0xFFFF 1 --- F3 0 1
30135 0x86 Main Boot Code Date 0 6 1 --- F22 Unknown 6
30141 0x8C Main Boot Code Time 0 4 1 --- F22 Unknown 4
30145 0x90 Comms Boot Code Date 0 6 1 --- F22 Unknown 6
30151 0x96 Comms Boot Code Time 0 4 1 --- F22 Unknown 4
LAST TRIP DATA
30186 0xB9 Cause of Last Trip 0 0xFFFF 1 --- FC134 0 1
REAL-TIME CLOCK
30223 0xDE Weekday 0 7 1 --- None 0 1
30224 0xDF Current Date 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
9
30226 0xE1 Current Time 0 0X173BEA5F 0 --- F19 0 2
30228 0xE3 Daylight Savings Active 0 1 1 --- FC126 0 1
INPUTS / OUTPUTS
30285 0x11C Contact Input 32-1 (Bit Field) 0 0xFFFFFFFF 1 --- FC167 0 2
30288 0x11F Virtual Input 32-1 (Bit Field) 0 0xFFFFFFFF 1 --- FC167 0 2
30290 0x121 Virtual Output 32-1 (Bit Field) 0 0xFFFFFFFF 1 --- FC167 0 2
30296 0x127 Remote Input 32-1 (Bit Field) 0 0xFFFFFFFF 1 --- FC167 0 2
30298 0x129 Contact Output 32-1 (Bit 0 0xFFFFFFFF 1 --- FC167 0 2
Field)
30300 0x12B Remote Output 32-1 (Bit 0 0xFFFFFFFF 1 --- FC167 0 2
Field)
DEVICE STATUS
30302 0x12D Current Security Access 0 3 1 --- F1 0 1
Level
30305 0x130 Device Status 0 0xFFFF 1 --- FC129 0 1
30317 0x13C Active Setpoint Group 0 1 1 --- F1 0 1
30319 0x13E Relay1 Coil Status 0 1 1 --- FC125 0 1
30320 0x13F Relay2 Coil Status 0 1 1 --- FC125 0 1
30321 0x140 TRIP COIL BKR2 STATUS 0 1 1 --- FC125 0 1
WINDING 1 CURRENT METERING
30324 0x143 Sensitive Ground Current 0 0xFFFFFFFF 1 A F11 0 2
30326 0x145 Neutral Current 0 100000 1 A F10 0 2
30328 0x147 Phase A Current 0 1200000 1 A F10 0 2
30330 0x149 Phase B Current 0 1200000 1 A F10 0 2
30332 0x14B Phase C Current 0 1200000 1 A F10 0 2
30338 0x151 Ground Current 0 1200000 1 A F10 0 2
30343 0x156 Ia Angle 0 359 1 ° F1 0 1
30344 0x157 Ib Angle 0 359 1 ° F1 0 1
30345 0x158 Ic Angle 0 359 1 ° F1 0 1
30349 0x15C Ground Current Angle 0 359 1 ° F1 0 1
30350 0x15D Neutral Current Angle 0 359 1 ° F1 0 1
30437 0x1B4 Event Phase A Thermal 0 1500 1 % F2 0 1
Capacity

11-2 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
30438 0x1B5 Event Phase B Thermal 0 1500 1 % F2 0 1
Capacity
30439 0x1B6 Event Phase C Thermal 0 1500 1 % F2 0 1
Capacity
30456 0x1C7 Negative Sequence Current 0 65535 1 A F1 0 1
Magnitude
30457 0x1C8 Negative Sequence Current 0 359 1 °Lag F1 0 1
Angle
30478 0x1DD Negative Sequence Current 0 65535 1 A F2 0 1
Magnitude
RTD METERING
30420 0x1A3 RTD 7 Temp -50 251 1 °C F4 0 1
30421 0x1A4 RTD 8 Temp -50 251 1 °C F4 0 1
30422 0x1A5 RTD 9 Temp -50 251 1 °C F4 0 1
30423 0x1A6 RTD 10 Temp -50 251 1 °C F4 0 1
30424 0x1A7 RTD 11 Temp -50 251 1 °C F4 0 1
30425 0x1A8 RTD 12 Temp -50 251 1 °C F4 0 1
30427 0x1AA Hottest Stator RTD 0 12 1 --- F1 0 1
30428 0x1AB Hottest Stator RTD -50 251 1 °C F4 0 1
30429 0x1AC RTD 1 Temperature -50 251 1 °C F4 0 1
30430 0x1AD RTD 2 Temperature -50 251 1 °C F4 0 1
30431 0x1AE RTD 3 Temperature -50 251 1 °C F4 0 1
30432 0x1AF RTD 4 Temperature -50 251 1 °C F4 0 1
30433 0x1B0 RTD 5 Temperature -50 251 1 °C F4 0 1
30434 0x1B1 RTD 6 Temperature -50 251 1 °C F4 0 1
TEMPERATURE
30435 0x1B2 Ambient Temperature -50 250 1 ° F4 25 1
RTD MAXIMUMS
30485 0x1E4 RTD 1 Maximum -50 250 1 °C F4 0 1
Temperature
30486 0x1E5 RTD 2 Maximum -50 250 1 °C F4 0 1
Temperature
30487 0x1E6 RTD 3 Maximum -50 250 1 °C F4 0 1
Temperature
30488 0x1E7 RTD 4 Maximum -50 250 1 °C F4 0 1
Temperature
30489 0x1E8 RTD 5 Maximum -50 250 1 °C F4 0 1
Temperature
30490 0x1E9 RTD 6 Maximum -50 250 1 °C F4 0 1
Temperature
30491 0x1EA RTD 7 MAX Temp -50 250 1 °C F4 0 1
30492 0x1EB RTD 8 MAX Temp -50 250 1 °C F4 0 1
30493 0x1EC RTD 9 MAX Temp -50 250 1 °C F4 0 1
30494 0x1ED RTD 10 MAX Temp -50 250 1 °C F4 0 1
30495 0x1EE RTD 11 MAX Temp -50 250 1 °C F4 0 1
30496 0x1EF RTD 12 MAX Temp -50 250 1 °C F4 0 1
LED STATUS
30505 0x1F8 LED Status 0 0xFFFFFFFF 1 --- FC144B 0 2
USER MAP ACTUAL VALUES

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-3


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
30524 0x20B User Map Value 1 0 0xFFFF 1 --- F1 0 1
30525 0x20C User Map Value 2 0 0xFFFF 1 --- F1 0 1
30526 0x20D User Map Value 3 0 0xFFFF 1 --- F1 0 1
30527 0x20E User Map Value 4 0 0xFFFF 1 --- F1 0 1
30528 0x20F User Map Value 5 0 0xFFFF 1 --- F1 0 1
30529 0x210 User Map Value 6 0 0xFFFF 1 --- F1 0 1
30530 0x211 User Map Value 7 0 0xFFFF 1 --- F1 0 1
30531 0x212 User Map Value 8 0 0xFFFF 1 --- F1 0 1
30532 0x213 User Map Value 9 0 0xFFFF 1 --- F1 0 1
30533 0x214 User Map Value 10 0 0xFFFF 1 --- F1 0 1
30534 0x215 User Map Value 11 0 0xFFFF 1 --- F1 0 1
30535 0x216 User Map Value 12 0 0xFFFF 1 --- F1 0 1
30536 0x217 User Map Value 13 0 0xFFFF 1 --- F1 0 1
30537 0x218 User Map Value 14 0 0xFFFF 1 --- F1 0 1
30538 0x219 User Map Value 15 0 0xFFFF 1 --- F1 0 1
30539 0x21A User Map Value 16 0 0xFFFF 1 --- F1 0 1
30540 0x21B User Map Value 17 0 0xFFFF 1 --- F1 0 1
30541 0x21C User Map Value 18 0 0xFFFF 1 --- F1 0 1
30542 0x21D User Map Value 19 0 0xFFFF 1 --- F1 0 1
30543 0x21E User Map Value 20 0 0xFFFF 1 --- F1 0 1
30544 0x21F User Map Value 21 0 0xFFFF 1 --- F1 0 1
30545 0x220 User Map Value 22 0 0xFFFF 1 --- F1 0 1
30546 0x221 User Map Value 23 0 0xFFFF 1 --- F1 0 1
30547 0x222 User Map Value 24 0 0xFFFF 1 --- F1 0 1
30548 0x223 User Map Value 25 0 0xFFFF 1 --- F1 0 1
30549 0x224 User Map Value 26 0 0xFFFF 1 --- F1 0 1
30550 0x225 User Map Value 27 0 0xFFFF 1 --- F1 0 1
30551 0x226 User Map Value 28 0 0xFFFF 1 --- F1 0 1
30552 0x227 User Map Value 29 0 0xFFFF 1 --- F1 0 1
30553 0x228 User Map Value 30 0 0xFFFF 1 --- F1 0 1
30554 0x229 User Map Value 31 0 0xFFFF 1 --- F1 0 1
30555 0x22A User Map Value 32 0 0xFFFF 1 --- F1 0 1
30556 0x22B User Map Value 33 0 0xFFFF 1 --- F1 0 1
30557 0x22C User Map Value 34 0 0xFFFF 1 --- F1 0 1
30558 0x22D User Map Value 35 0 0xFFFF 1 --- F1 0 1
30559 0x22E User Map Value 36 0 0xFFFF 1 --- F1 0 1
30560 0x22F User Map Value 37 0 0xFFFF 1 --- F1 0 1
30561 0x230 User Map Value 38 0 0xFFFF 1 --- F1 0 1
30562 0x231 User Map Value 39 0 0xFFFF 1 --- F1 0 1
30563 0x232 User Map Value 40 0 0xFFFF 1 --- F1 0 1
30564 0x233 User Map Value 41 0 0xFFFF 1 --- F1 0 1
30565 0x234 User Map Value 42 0 0xFFFF 1 --- F1 0 1
30566 0x235 User Map Value 43 0 0xFFFF 1 --- F1 0 1
30567 0x236 User Map Value 44 0 0xFFFF 1 --- F1 0 1
30568 0x237 User Map Value 45 0 0xFFFF 1 --- F1 0 1

11-4 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
30569 0x238 User Map Value 46 0 0xFFFF 1 --- F1 0 1
30570 0x239 User Map Value 47 0 0xFFFF 1 --- F1 0 1
30571 0x23A User Map Value 48 0 0xFFFF 1 --- F1 0 1
30572 0x23B User Map Value 49 0 0xFFFF 1 --- F1 0 1
30573 0x23C User Map Value 50 0 0xFFFF 1 --- F1 0 1
30574 0x23D User Map Value 51 0 0xFFFF 1 --- F1 0 1
30575 0x23E User Map Value 52 0 0xFFFF 1 --- F1 0 1
30576 0x23F User Map Value 53 0 0xFFFF 1 --- F1 0 1
30577 0x240 User Map Value 54 0 0xFFFF 1 --- F1 0 1
30578 0x241 User Map Value 55 0 0xFFFF 1 --- F1 0 1
30579 0x242 User Map Value 56 0 0xFFFF 1 --- F1 0 1
30580 0x243 User Map Value 57 0 0xFFFF 1 --- F1 0 1
30581 0x244 User Map Value 58 0 0xFFFF 1 --- F1 0 1
30582 0x245 User Map Value 59 0 0xFFFF 1 --- F1 0 1
30583 0x246 User Map Value 60 0 0xFFFF 1 --- F1 0 1
30584 0x247 User Map Value 61 0 0xFFFF 1 --- F1 0 1
30585 0x248 User Map Value 62 0 0xFFFF 1 --- F1 0 1
30586 0x249 User Map Value 63 0 0xFFFF 1 --- F1 0 1
30587 0x24A User Map Value 64 0 0xFFFF 1 --- F1 0 1
30588 0x24B User Map Value 65 0 0xFFFF 1 --- F1 0 1
30589 0x24C User Map Value 66 0 0xFFFF 1 --- F1 0 1
30590 0x24D User Map Value 67 0 0xFFFF 1 --- F1 0 1
30591 0x24E User Map Value 68 0 0xFFFF 1 --- F1 0 1
30592 0x24F User Map Value 69 0 0xFFFF 1 --- F1 0 1
30593 0x250 User Map Value 70 0 0xFFFF 1 --- F1 0 1
30594 0x251 User Map Value 71 0 0xFFFF 1 --- F1 0 1
30595 0x252 User Map Value 72 0 0xFFFF 1 --- F1 0 1
30596 0x253 User Map Value 73 0 0xFFFF 1 --- F1 0 1
30597 0x254 User Map Value 74 0 0xFFFF 1 --- F1 0 1
30598 0x255 User Map Value 75 0 0xFFFF 1 --- F1 0 1
30599 0x256 User Map Value 76 0 0xFFFF 1 --- F1 0 1
30600 0x257 User Map Value 77 0 0xFFFF 1 --- F1 0 1
30601 0x258 User Map Value 78 0 0xFFFF 1 --- F1 0 1
30602 0x259 User Map Value 79 0 0xFFFF 1 --- F1 0 1
30603 0x25A User Map Value 80 0 0xFFFF 1 --- F1 0 1
30604 0x25B User Map Value 81 0 0xFFFF 1 --- F1 0 1
30605 0x25C User Map Value 82 0 0xFFFF 1 --- F1 0 1
30606 0x25D User Map Value 83 0 0xFFFF 1 --- F1 0 1
30607 0x25E User Map Value 84 0 0xFFFF 1 --- F1 0 1
30608 0x25F User Map Value 85 0 0xFFFF 1 --- F1 0 1
30609 0x260 User Map Value 86 0 0xFFFF 1 --- F1 0 1
30610 0x261 User Map Value 87 0 0xFFFF 1 --- F1 0 1
30611 0x262 User Map Value 88 0 0xFFFF 1 --- F1 0 1
30612 0x263 User Map Value 89 0 0xFFFF 1 --- F1 0 1
30613 0x264 User Map Value 90 0 0xFFFF 1 --- F1 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-5


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
30614 0x265 User Map Value 91 0 0xFFFF 1 --- F1 0 1
30615 0x266 User Map Value 92 0 0xFFFF 1 --- F1 0 1
30616 0x267 User Map Value 93 0 0xFFFF 1 --- F1 0 1
30617 0x268 User Map Value 94 0 0xFFFF 1 --- F1 0 1
30618 0x269 User Map Value 95 0 0xFFFF 1 --- F1 0 1
30619 0x26A User Map Value 96 0 0xFFFF 1 --- F1 0 1
30620 0x26B User Map Value 97 0 0xFFFF 1 --- F1 0 1
30621 0x26C User Map Value 98 0 0xFFFF 1 --- F1 0 1
30622 0x26D User Map Value 99 0 0xFFFF 1 --- F1 0 1
30623 0x26E User Map Value 100 0 0xFFFF 1 --- F1 0 1
30624 0x26F User Map Value 101 0 0xFFFF 1 --- F1 0 1
30625 0x270 User Map Value 102 0 0xFFFF 1 --- F1 0 1
30626 0x271 User Map Value 103 0 0xFFFF 1 --- F1 0 1
30627 0x272 User Map Value 104 0 0xFFFF 1 --- F1 0 1
30628 0x273 User Map Value 105 0 0xFFFF 1 --- F1 0 1
30629 0x274 User Map Value 106 0 0xFFFF 1 --- F1 0 1
30630 0x275 User Map Value 107 0 0xFFFF 1 --- F1 0 1
30631 0x276 User Map Value 108 0 0xFFFF 1 --- F1 0 1
30632 0x277 User Map Value 109 0 0xFFFF 1 --- F1 0 1
30633 0x278 User Map Value 110 0 0xFFFF 1 --- F1 0 1
30634 0x279 User Map Value 111 0 0xFFFF 1 --- F1 0 1
30635 0x27A User Map Value 112 0 0xFFFF 1 --- F1 0 1
30636 0x27B User Map Value 113 0 0xFFFF 1 --- F1 0 1
30637 0x27C User Map Value 114 0 0xFFFF 1 --- F1 0 1
30638 0x27D User Map Value 115 0 0xFFFF 1 --- F1 0 1
30639 0x27E User Map Value 116 0 0xFFFF 1 --- F1 0 1
30640 0x27F User Map Value 117 0 0xFFFF 1 --- F1 0 1
30641 0x280 User Map Value 118 0 0xFFFF 1 --- F1 0 1
30642 0x281 User Map Value 119 0 0xFFFF 1 --- F1 0 1
30643 0x282 User Map Value 120 0 0xFFFF 1 --- F1 0 1
30644 0x283 User Map Value 121 0 0xFFFF 1 --- F1 0 1
30645 0x284 User Map Value 122 0 0xFFFF 1 --- F1 0 1
30646 0x285 User Map Value 123 0 0xFFFF 1 --- F1 0 1
30647 0x286 User Map Value 124 0 0xFFFF 1 --- F1 0 1
30648 0x287 User Map Value 125 0 0xFFFF 1 --- F1 0 1
EVENT RECORDER DETAILS
30654 0x28D W1 CT Primary 1 6000 1 A F1 500 1
30655 0x28E W1 Ground CT Primary 1 6000 1 A F1 50 1
30656 0x28F W2 CT Primary 1 6000 1 A F1 5 1
30657 0x290 W2 Ground CT Primary 1 6000 1 A F1 5 1
30659 0x292 Event Recorder Last Reset 2 0x010107D8 0X0C1F082E 0 --- F18 0x010107D 2
words 8
30661 0x294 Total Number of Events 0 65535 1 --- F1 0 1
Since Last Clear
30662 0x295 Event Cause 0 0xFFFF 1 --- FC134 0 1
30663 0x296 Event Time 0 0X173BEA5F 0 --- F19 0 2

11-6 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
30665 0x298 Event Date 0x010107D8 0X0C1F082E 0 --- F18 0x010107D 2
8
30667 0x29A W1 Ia 0 65535 1 x CT F3 0 1
30668 0x29B W1 Ib 0 65535 1 x CT F3 0 1
30669 0x29C W1 Ic 0 65535 1 x CT F3 0 1
30670 0x29D W1 Ig 0 65535 1 x CTg F3 0 1
30671 0x29E W1 Igd 0 65535 1 x CT F3 0 1
30672 0x29F W1 Igr 0 65535 1 x CT F3 0 1
30673 0x2A0 W1 I_2 0 65535 1 x CT F3 0 1
30674 0x2A1 W1 Ia Angle 0 359 1 ° F1 0 1
30675 0x2A2 W1 Ib Angle 0 359 1 ° F1 0 1
30676 0x2A3 W1 Ic Angle 0 359 1 ° F1 0 1
30677 0x2A4 W1 Ig Angle 0 359 1 ° F1 0 1
30678 0x2A5 W1 In 0 65535 1 x CT F3 0 1
30679 0x2A6 W1 In Angle 0 359 1 ° F1 0 1
30680 0x2A7 W2 Ia 0 65535 1 x CT F3 0 1
30681 0x2A8 W2 Ib 0 65535 1 x CT F3 0 1
30682 0x2A9 W2 Ic 0 65535 1 x CT F3 0 1
30683 0x2AA W2 Ig 0 65535 1 x CTg F3 0 1
30684 0x2AB W2 Igd 0 65535 1 x CT F3 0 1
30685 0x2AC W2 Igr 0 65535 1 x CT F3 0 1
30686 0x2AD W2 I_2 0 65535 1 x CT F3 0 1
30687 0x2AE W2 Ia Angle 0 359 1 ° F1 0 1
30688 0x2AF W2 Ib Angle 0 359 1 ° F1 0 1
30689 0x2B0 W2 Ic Angle 0 359 1 ° F1 0 1
30690 0x2B1 W2 Ig Angle 0 359 1 ° F1 0 1
30691 0x2B2 W2 In 0 65535 1 x CT F3 0 1
30692 0x2B3 W2 In Angle 0 359 1 ° F1 0 1
30693 0x2B4 Ph A Diff. 0 65535 1 x CT F3 0 1
(W1)
30694 0x2B5 Ph B Diff. 0 65535 1 x CT F3 0 1
(W1)
30695 0x2B6 Ph C Diff. 0 65535 1 x CT F3 0 1
(W1)
30696 0x2B7 Ph A Restr. 0 65535 1 x CT F3 0 1
(W1)
30697 0x2B8 Ph B Restr. 0 65535 1 x CT F3 0 1
(W1)
30698 0x2B9 Ph C Restr. 0 65535 1 x CT F3 0 1
(W1)
30699 0x2BA 2nd Harm Ph A diff 0 65535 1 % fo F2 0 1
30700 0x2BB 2nd Harm Ph B diff 0 65535 1 % fo F2 0 1
30701 0x2BC 2nd Harm Ph C diff 0 65535 1 % fo F2 0 1
30702 0x2BD Phase A Thermal Capacity 0 1500 1 % F2 0 1
30703 0x2BE Phase B Thermal Capacity 0 1500 1 % F2 0 1
30704 0x2BF Phase C Thermal Capacity 0 1500 1 % F2 0 1
30705 0x2C0 Event Self-Test Event 0 0xFFFFFFFF 2 --- FC188 0 2

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-7


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
TRANSIENT RECORDER SAMPLES
30720 0x2CF Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 1
30721 0x2D0 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 2
30722 0x2D1 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 3
30723 0x2D2 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 4
30724 0x2D3 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 5
30725 0x2D4 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 6
30726 0x2D5 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 7
30727 0x2D6 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 8
30728 0x2D7 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 9
30729 0x2D8 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 10
30730 0x2D9 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 11
30731 0x2DA Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 12
30732 0x2DB Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 13
30733 0x2DC Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 14
30734 0x2DD Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 15
30735 0x2DE Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 16
30736 0x2DF Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 17
30737 0x2E0 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 18
30738 0x2E1 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 19
30739 0x2E2 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 20
30740 0x2E3 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 21
30741 0x2E4 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 22
30742 0x2E5 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 23
30743 0x2E6 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 24
30744 0x2E7 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 25
30745 0x2E8 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 26
30746 0x2E9 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 27

11-8 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
30747 0x2EA Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 28
30748 0x2EB Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 29
30749 0x2EC Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 30
30750 0x2ED Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 31
30751 0x2EE Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 32
30752 0x2EF Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 33
30753 0x2F0 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 34
30754 0x2F1 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 35
30755 0x2F2 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 36
30756 0x2F3 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 37
30757 0x2F4 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 38
30758 0x2F5 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 39
30759 0x2F6 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 40
30760 0x2F7 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 41
30761 0x2F8 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 42
30762 0x2F9 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 43
30763 0x2FA Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 44
30764 0x2FB Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 45
30765 0x2FC Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 46
30766 0x2FD Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 47
30767 0x2FE Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 48
30768 0x2FF Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 49
30769 0x300 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 50
30770 0x301 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 51
30771 0x302 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 52
30772 0x303 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 53
30773 0x304 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 54

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-9


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
30774 0x305 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 55
30775 0x306 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 56
30776 0x307 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 57
30777 0x308 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 58
30778 0x309 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 59
30779 0x30A Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 60
30780 0x30B Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 61
30781 0x30C Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 62
30782 0x30D Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 63
30783 0x30E Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 64
30784 0x30F Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 65
30785 0x310 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 66
30786 0x311 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 67
30787 0x312 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 68
30788 0x313 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 69
30789 0x314 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 70
30790 0x315 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 71
30791 0x316 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 72
30792 0x317 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 73
30793 0x318 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 74
30794 0x319 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 75
30795 0x31A Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 76
30796 0x31B Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 77
30797 0x31C Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 78
30798 0x31D Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 79
30799 0x31E Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 80
30800 0x31F Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 81

11-10 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
30801 0x320 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 82
30802 0x321 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 83
30803 0x322 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 84
30804 0x323 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 85
30805 0x324 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 86
30806 0x325 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 87
30807 0x326 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 88
30808 0x327 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 89
30809 0x328 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 90
30810 0x329 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 91
30811 0x32A Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 92
30812 0x32B Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 93
30813 0x32C Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 94
30814 0x32D Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 95
30815 0x32E Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 96
30816 0x32F Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 97
30817 0x330 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 98
30818 0x331 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 99
30819 0x332 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 100
30820 0x333 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 101
30821 0x334 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 102
30822 0x335 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 103
30823 0x336 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 104
30824 0x337 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 105
30825 0x338 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 106
30826 0x339 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 107
30827 0x33A Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 108

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-11


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
30828 0x33B Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 109
30829 0x33C Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 110
30830 0x33D Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 111
30831 0x33E Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 112
30832 0x33F Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 113
30833 0x340 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 114
30834 0x341 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 115
30835 0x342 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 116
30836 0x343 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 117
30837 0x344 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 118
30838 0x345 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 119
30839 0x346 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 120
30840 0x347 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 121
30841 0x348 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 122
30842 0x349 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 123
30843 0x34A Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 124
30844 0x34B Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 125
30845 0x34C Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 126
30846 0x34D Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 127
30847 0x34E Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 128
STATUS BUFFER
30946 0x3B1 Alarm Status 4 0 0xFFFFFFFF 1 --- FC182 0 2
30948 0x3B3 Alarm Status 3 0 0xFFFFFFFF 1 --- FC181 0 2
30950 0x3B5 Alarm Status 2 0 0xFFFFFFFF 1 --- FC180 0 2
30952 0x3B7 Alarm Status 1 0 0xFFFFFFFF 1 --- FC179 0 2
30954 0x3B9 Trip Status 4 0 0xFFFFFFFF 1 --- FC186 0 2
30956 0x3BB Trip Status 3 0 0xFFFFFFFF 1 --- FC185 0 2
30960 0x3BF Trip Status 1 0 0xFFFFFFFF 1 --- FC183 0 2
30966 0x3C5 Message Status 2 0 0xFFFFFFFF 1 --- FC188 0 2
30968 0x3C7 Message Status 1 0 0xFFFFFFFF 1 --- FC187 0 2
30970 0x3C9 Control Element Status 4 0 0xFFFFFFFF 1 --- FC194 0 2
30974 0x3CD Control Element Status 2 0 0xFFFFFFFF 1 --- FC192 0 2

11-12 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
30976 0x3CF Control Element Status 1 0 0xFFFFFFFF 1 --- FC191 0 2
30978 0x3D1 Block Status 4 0 0xFFFFFFFF 1 --- FC203 0 2
30980 0x3D3 Block Status 3 0 0xFFFFFFFF 1 --- FC202 0 2
30982 0x3D5 Block Status 2 0 0xFFFFFFFF 1 --- FC201 0 2
30984 0x3D7 Block Status 1 0 0xFFFFFFFF 1 --- FC200 0 2
61850 STATUS
31510 0x5E5 61850 Status 0 2 1 --- FC108 0 1
31511 0x5E6 61850 N.V. Status 0 4 1 --- FC434 0 1
IEC61850 GOOSE STATUS
31515 0x5EA Remote GOOSE Status 0 0xFFFFFFFF 1 --- FC215 0 2
31517 0x5EC Remote GOOSE Header 0 0xFFFFFFFF 1 --- FC215 0 2
Status
THERMAL MODEL TRIP STATUS
31521 0x5F0 Trip Phase A Status 1 0 65535 1 --- FC134 0 1
31522 0x5F1 Trip Phase B Status 1 0 65535 1 --- FC134 0 1
31523 0x5F2 Trip Phase C Status 1 0 65535 1 --- FC134 0 1
PHASE IOC1 TRIP STATUS
31524 0x5F3 Trip Phase A Status 2 0 65535 1 --- FC134 0 1
31525 0x5F4 Trip Phase B Status 2 0 65535 1 --- FC134 0 1
31526 0x5F5 Trip Phase C Status 2 0 65535 1 --- FC134 0 1
PHASE TOC1 TRIP STATUS
31527 0x5F6 Trip Phase A Status 3 0 65535 1 --- FC134 0 1
31528 0x5F7 Trip Phase B Status 3 0 65535 1 --- FC134 0 1
31529 0x5F8 Trip Phase C Status 3 0 65535 1 --- FC134 0 1
PHASE IOC2 TRIP STATUS
31530 0x5F9 Trip Phase A Status 4 0 65535 1 --- FC134 0 1
31531 0x5FA Trip Phase B Status 4 0 65535 1 --- FC134 0 1
31532 0x5FB Trip Phase C Status 4 0 65535 1 --- FC134 0 1
DIFFERENTIAL TRIP STATUS
31539 0x602 Diff Trip PhA Status 0 65535 1 --- FC134 0 1
31540 0x603 Diff Trip PhB Status 0 65535 1 --- FC134 0 1
31541 0x604 Diff Trip PhC Status 0 65535 1 --- FC134 0 1
PHASE TOC2 TRIP STATUS
31542 0x605 0 65535 1 --- FC134 0 1
Phase51PTOC_2Trip_PhaseA
Status
31543 0x606 0 65535 1 --- FC134 0 1
Phase51PTOC_2Trip_PhaseB
Status
31544 0x607 0 65535 1 --- FC134 0 1
Phase51PTOC_2Trip_PhaseC
Status
THERMAL MODEL ALARM STATUS
31569 0x620 Alarm Phase A Status 1 0 65535 1 --- FC134 0 1
31570 0x621 Alarm Phase B Status 1 0 65535 1 --- FC134 0 1
31571 0x622 Alarm Phase C Status 1 0 65535 1 --- FC134 0 1
PHASE IOC1 ALARM STATUS

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-13


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
31572 0x623 Alarm Phase A Status 2 0 65535 1 --- FC134 0 1
31573 0x624 Alarm Phase B Status 2 0 65535 1 --- FC134 0 1
31574 0x625 Alarm Phase C Status 2 0 65535 1 --- FC134 0 1
PHASE TOC1 ALARM STATUS
31575 0x626 Alarm Phase A Status 3 0 65535 1 --- FC134 0 1
31576 0x627 Alarm Phase B Status 3 0 65535 1 --- FC134 0 1
31577 0x628 Alarm Phase C Status 3 0 65535 1 --- FC134 0 1
PHASE IOC2 ALARM STATUS
31578 0x629 Alarm Phase A Status 4 0 65535 1 --- FC134 0 1
31579 0x62A Alarm Phase B Status 4 0 65535 1 --- FC134 0 1
31580 0x62B Alarm Phase C Status 4 0 65535 1 --- FC134 0 1
DIFFERENTIAL ALARM STATUS
31587 0x632 Diff Alarm PhA Status 0 65535 1 --- FC134 0 1
31588 0x633 Diff Alarm PhB Status 0 65535 1 --- FC134 0 1
31589 0x634 Diff Alarm PhC Status 0 65535 1 --- FC134 0 1
PHASE TOC2 ALARM STATUS
31590 0x635 0 65535 1 --- FC134 0 1
Phase51PTOC_2Alarm_Phas
eAStatus
31591 0x636 0 65535 1 --- FC134 0 1
Phase51PTOC_2Alarm_Phas
eBStatus
31592 0x637 0 65535 1 --- FC134 0 1
Phase51PTOC_2Alarm_Phas
eCStatus
WINDING 2 CURRENT METERING
31665 0x680 Ia2 0 100000 1 A F10 0 2
31667 0x682 Ib2 0 100000 1 A F10 0 2
31669 0x684 Ic2 0 100000 1 A F10 0 2
31671 0x686 In2 0 100000 1 A F10 0 2
31673 0x688 Ig2 0 100000 1 A F10 0 2
31675 0x68A Isg2 0 100000 1 A F11 0 2
PHASE DIFFERENTIAL CURRENT METERING
31677 0x68C Idiff 1 Ph A 0 100000 1 x CT F11 0 2
31679 0x68E Idiff 1 Ph B 0 100000 1 x CT F11 0 2
31681 0x690 Idiff 1 Ph C 0 100000 1 x CT F11 0 2
31683 0x692 Idiff 2 Ph A 0 1000 1 % fo F2 0 1
31684 0x693 Idiff 2 Ph B 0 1000 1 % fo F2 0 1
31685 0x694 Idiff 2 Ph C 0 1000 1 % fo F2 0 1
31686 0x695 Idiff 5 Ph A 0 1000 1 % fo F2 0 1
31687 0x696 Idiff 5 Ph B 0 1000 1 % fo F2 0 1
31688 0x697 Idiff 5 Ph C 0 1000 1 % fo F2 0 1
RESTRAINT CURRENT METERING
31695 0x69E I Restraint Ph A 0 100000 1 x CT F11 0 2
31697 0x6A0 I Restraint Ph B 0 100000 1 x CT F11 0 2
31699 0x6A2 I Restraint Ph C 0 100000 1 x CT F11 0 2
PHASE ANGLES

11-14 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
31701 0x6A4 Ia2 Angle 0 359 1 --- F1 0 1
31702 0x6A5 Ib2 Angle 0 359 1 --- F1 0 1
31703 0x6A6 Ic2 Angle 0 359 1 --- F1 0 1
31704 0x6A7 Ig2 Angle 0 359 1 --- F1 0 1
31705 0x6A8 In2 Angle 0 359 1 --- F1 0 1
31706 0x6A9 Idiff 1 PhA Angle 0 359 1 --- F1 0 1
31707 0x6AA Idiff 1 PhB Angle 0 359 1 --- F1 0 1
31708 0x6AB Idiff 1 PhC Angle 0 359 1 --- F1 0 1
31709 0x6AC Idiff 2 PhA Angle 0 359 1 --- F1 0 1
31710 0x6AD Idiff 2 PhB Angle 0 359 1 --- F1 0 1
31711 0x6AE Idiff 2 PhC Angle 0 359 1 --- F1 0 1
31712 0x6AF Idiff 5 PhA Angle 0 359 1 --- F1 0 1
31713 0x6B0 Idiff 5 PhB Angle 0 359 1 --- F1 0 1
31714 0x6B1 Idiff 5 PhC Angle 0 359 1 --- F1 0 1
31715 0x6B2 Irestraint A Angle 0 359 1 --- F1 0 1
31716 0x6B3 Irestraint B Angle 0 359 1 --- F1 0 1
31717 0x6B4 Irestraint C Angle 0 359 1 --- F1 0 1
31721 0x6B8 W2 Neg Seq Angle 0 359 1 ° F1 0 1
GROUND DIFFERENTIAL CURRENT METERING
31724 0x6BB W1 Ground Differential 0 1000000 1 x CT F11 0 2
Current
31726 0x6BD W1 Ground Differential 0 359 1 ° F1 0 1
Angle
31727 0x6BE W2 Ground Differential 0 1000000 1 x CT F11 0 2
Current
31729 0x6C0 W2 Ground Differential 0 359 1 ° F1 0 1
Angle
WINDING 2 NEGATIVE SEQUENCE CURRENT METERING
31720 0x6B7 W2 Neg Sequence 0 0xFFFF 1 A F1 0 1
31730 0x6C1 W2 Neg Sequence 0 0xFFFF 1 A F2 0 1
TRANSIENT RECORDER
30707 0x2C2 Transient Recorder Last 0x010107D8 0X0C1F082E 0 --- F18 0x010107D 2
Cleared 8
30709 0x2C4 Transient Recorder Available 0 6 1 --- F1 0 1
Records
30710 0x2C5 Trace Memory Trigger Date 0x010107D8 0X0C1F082E 0 --- F18 0x010107D 2
8
30712 0x2C7 Trace Memory Trigger Time 0 0X173BEA5F 0 --- F19 0 2
30714 0x2C9 Trace Memory Trigger 0 0xD002 0 --- FC133 0 1
Cause
30715 0x2CA Trace Memory Trigger 0 12000 1 Hz F3 60 1
Frequency
30716 0x2CB Total Triggers 0 0xFFFF 1 --- F1 0 1
30718 0x2CD Trigger Position (Actual 0 6143 1 --- F1 25 1
Value)
30719 0x2CE Trace Memory Start Index 0 6143 1 --- F1 0 1
31773 0x6EC Transient Sampling Rate 0 3 1 --- FC429 0 1
Status
FAULT REPORT

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-15


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
31775 0x6EE Fault Report Date 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
9
31777 0x6F0 Fault Report Time 0 0X173BEA5F 0 --- F19 0 2
31779 0x6F2 Fault Report Fault Type 0 2 1 --- FC134C 0 1
31780 0x6F3 Fault Report Ia 0 1200000 1 A F10 0 2
31782 0x6F5 Fault Report Ia Angle 0 359 1 ° F1 0 1
31783 0x6F6 Fault Report Ib 0 1200000 1 A F10 0 2
31785 0x6F8 Fault Report Ib Angle 0 359 1 ° F1 0 1
31786 0x6F9 Fault Report Ic 0 1200000 1 A F10 0 2
31788 0x6FB Fault Report Ic Angle 0 359 1 ° F1 0 1
31789 0x6FC Fault Report Ig 0 1200000 1 A F10 0 2
31791 0x6FE Fault Report Ig Angle 0 359 1 ° F1 0 1
31792 0x6FF Fault Report In 0 100000 1 A F10 0 2
31794 0x701 Fault Report In Angle 0 359 1 ° F1 0 1
31819 0x71A Fault Report System 0 12000 1 Hz F3 0 1
Frequency
31820 0x71B Fault Report Ia 2 0 1200000 1 A F10 0 2
31822 0x71D Fault Report Ia 2 Angle 0 359 1 ° F1 0 1
31823 0x71E Fault Report Ib 2 0 1200000 1 A F10 0 2
31825 0x720 Fault Report Ib 2 Angle 0 359 1 ° F1 0 1
31826 0x721 Fault Report Ic 2 0 1200000 1 A F10 0 2
31828 0x723 Fault Report Ic 2 Angle 0 359 1 ° F1 0 1
31829 0x724 Fault Report Ig 2 0 1200000 1 A F10 0 2
31831 0x726 Fault Report Ig 2 Angle 0 359 1 ° F1 0 1
31832 0x727 Fault Report In 2 0 100000 1 A F10 0 2
31834 0x729 Fault Report In 2 Angle 0 359 1 ° F1 0 1
31835 0x72A Fault Report Idiff 1 PhA 0 100000 1 x CT F11 0 2
31837 0x72C Fault Report Idiff 1 PhA 0 359 1 --- F1 0 1
Angle
31838 0x72D Fault Report I Restraint PhA 0 100000 1 x CT F11 0 2
31840 0x72F Fault Report I Restraint PhA 0 359 1 --- F1 0 1
Angle
31841 0x730 Fault Report Idiff 1 PhB 0 100000 1 x CT F11 0 2
31843 0x732 Fault Report Idiff 1 PhB 0 359 1 --- F1 0 1
Angle
31844 0x733 Fault Report I Restraint PhB 0 100000 1 x CT F11 0 2
31846 0x735 Fault Report I Restraint PhB 0 359 1 --- F1 0 1
Angle
31847 0x736 Fault Report Idiff 1 PhC 0 100000 1 x CT F11 0 2
31849 0x738 Fault Report Idiff 1 PhC 0 359 1 --- F1 0 1
Angle
31850 0x739 Fault Report I Restraint PhC 0 100000 1 x CT F11 0 2
31852 0x73B Fault Report I Restraint PhC 0 359 1 --- F1 0 1
Angle
31853 0x73C Fault Report Phases 1 7 1 --- F37 1 1
31854 0x73D Fault Report Firmware 0 0xFFFF 1 --- F3 220 1
Version

11-16 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
31855 0x73E Fault Report Order Code 0 16 1 --- F22 345- 12
EP5G5HEM
NNSNNN
31867 0x74A Fault Report Feeder Name 0 10 1 --- F22 Transformer 10
Name
TRIP COUNTERS
31904 0x76F 0 10000 1 --- F1 0 1
DEMAND
32170 0x879 Current Demand 1 Last Rst 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
Date 9
32172 0x87B Current Demand 1 Last Rst 0 0X173BEA5F 0 --- F19 0 2
Time
32174 0x87D Current Demand 1 PhA 0 300000 1 A F10 0 2
32176 0x87F Current Demand 1 PhB 0 300000 1 A F10 0 2
32178 0x881 Current Demand 1 PhC 0 300000 1 A F10 0 2
32180 0x883 Max Current Demand 1 PhA 0 300000 1 A F10 0 2
32182 0x885 Max Current Demand 1 PhB 0 300000 1 A F10 0 2
32184 0x887 Max Current Demand 1 PhC 0 300000 1 A F10 0 2
32186 0x889 Current Demand 1 PhA Date 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
9
32188 0x88B Current Demand 1 PhB Date 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
9
32190 0x88D Current Demand 1 PhC Date 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
9
32192 0x88F Current Demand 1 PhA Time 0 0X173BEA5F 0 --- F19 0 2
32194 0x891 Current Demand 1 PhB Time 0 0X173BEA5F 0 --- F19 0 2
32196 0x893 Current Demand 1 PhC Time 0 0X173BEA5F 0 --- F19 0 2
32198 0x895 Current Demand 2 Last Rst 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
Date 9
32200 0x897 Current Demand 2 Last Rst 0 0X173BEA5F 0 --- F19 0 2
Time
32202 0x899 Current Demand 2 PhA 0 300000 1 A F10 0 2
32204 0x89B Current Demand 2 PhB 0 300000 1 A F10 0 2
32206 0x89D Current Demand 2 PhC 0 300000 1 A F10 0 2
32208 0x89F Max Current Demand 2 PhA 0 300000 1 A F10 0 2
32210 0x8A1 Max Current Demand 2 PhB 0 300000 1 A F10 0 2
32212 0x8A3 Max Current Demand 2 PhC 0 300000 1 A F10 0 2
32214 0x8A5 Current Demand 2 PhA Date 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
9
32216 0x8A7 Current Demand 2 PhB Date 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
9
32218 0x8A9 Current Demand 2 PhC Date 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
9
32220 0x8AB Current Demand 2 PhA Time 0 0X173BEA5F 0 --- F19 0 2
32222 0x8AD Current Demand 2 PhB Time 0 0X173BEA5F 0 --- F19 0 2
32224 0x8AF Current Demand 2 PhC Time 0 0X173BEA5F 0 --- F19 0 2
SETPOINTS
MESSAGE TIMES
40120 0x77 Flash Message Time 1 65535 1 s F1 5 1
40121 0x78 Message Timeout 1 65535 1 s F1 30 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-17


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
COMMANDS
40129 0x80 Command address 0 0xFFFF 0 --- F1 0 1
40130 0x81 Command Function 0 0xFFFF 0 --- F1 0 1
40131 0x82 Command Data 1 0 0xFFFF 0 --- F1 0 1
40132 0x83 Command Data 2 0 0xFFFF 0 --- F1 0 1
40133 0x84 Command Data 3 0 0xFFFF 0 --- F1 0 1
40134 0x85 Command Data 4 0 0xFFFF 0 --- F1 0 1
40135 0x86 Command Data 5 0 0xFFFF 0 --- F1 0 1
40136 0x87 Command Data 6 0 0xFFFF 0 --- F1 0 1
40137 0x88 Command Data 7 0 0xFFFF 0 --- F1 0 1
40138 0x89 Command Data 8 0 0xFFFF 0 --- F1 0 1
40139 0x8A Command Data 9 0 0xFFFF 0 --- F1 0 1
40140 0x8B Command Data 10 0 0xFFFF 0 --- F1 0 1
RS485 COMMUNICATIONS
40172 0xAB Slave Address 1 254 1 --- F1 254 1
40173 0xAC RS485 Baud Rate 0 4 1 --- FC101 4 1
40174 0xAD RS485 Parity 0 2 1 --- FC102 0 1
40175 0xAE Rear 485 Port Protocol 0 2 1 --- F97 0 1
ETHERNET COMMUNICATIONS
40180 0xB3 SNTP Mode 0 3 1 --- FC100 0 1
40181 0xB4 SNTP IP Address 0 0xFFFFFFFF 1 --- FC150 0 2
40183 0xB6 Ethernet IP address 0 0xFFFFFFFF 1 --- FC150 0 2
40185 0xB8 Ethernet subnet mask 0 0xFFFFFFFF 1 --- FC150 0xFFFFFC00 2
40187 0xBA Ethernet gateway address 0 0xFFFFFFFF 1 --- FC150 0 2
40189 0xBC SNTP Port 0 65535 1 --- F1 0 1
40191 0xBE EthernetConnectionType 0 1 1 --- FC230 0 1
(Copper or Fiber)
40194 0xC1 High Eth Message Enable 0 1 1 --- FC126 1 1
REAL-TIME CLOCK
40228 0xE3 Set Date 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
9
40230 0xE5 Set Time 0 0X173BEA5F 0 --- F19 0 2
40232 0xE7 Time Offset From UTC -2400 2400 25 hrs F6 0 1
40233 0xE8 IRIG-B 0 1 1 --- FC126 0 1
40234 0xE9 Daylight Savings 0 1 1 --- FC126 0 1
40235 0xEA DST Start Month 0 12 1 --- FC169 0 1
40236 0xEB DST Start Week 0 5 1 --- FC170 0 1
40237 0xEC DST Start Weekday 0 7 1 --- FC171 0 1
40238 0xED DST End Month 0 12 1 --- FC169 0 1
40239 0xEE DST End Week 0 5 1 --- FC170 0 1
40240 0xEF DST End Weekday 0 7 1 --- FC171 0 1
REMOTE INPUTS
40260 0x103 Remote Inputs 0 0xFFFFFFFF 1 --- FC167 0 2
POWER SYSTEM
40284 0x11B Supply Frequency 0 1 1 Hz FC107 0 1

11-18 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
40285 0x11C Relay Name 0 9 1 --- F22 Transformer 9
Name
40295 0x126 Power Unit 0 1 1 --- FC430 0 1
40296 0x127 Phase Sequence 0 1 1 --- FC124A 0 1
USER MAP ADDRESSES
40524 0x20B User Map Address 1 30001 39999 1 --- F1 30305 1
40525 0x20C User Map Address 2 30001 39999 1 --- F1 30505 1
40526 0x20D User Map Address 3 30001 39999 1 --- F1 30506 1
40527 0x20E User Map Address 4 30001 39999 1 --- F1 30960 1
40528 0x20F User Map Address 5 30001 39999 1 --- F1 30961 1
40529 0x210 User Map Address 6 30001 39999 1 --- F1 30958 1
40530 0x211 User Map Address 7 30001 39999 1 --- F1 30959 1
40531 0x212 User Map Address 8 30001 39999 1 --- F1 30956 1
40532 0x213 User Map Address 9 30001 39999 1 --- F1 30957 1
40533 0x214 User Map Address 10 30001 39999 1 --- F1 30954 1
40534 0x215 User Map Address 11 30001 39999 1 --- F1 30955 1
40535 0x216 User Map Address 12 30001 39999 1 --- F1 30952 1
40536 0x217 User Map Address 13 30001 39999 1 --- F1 30953 1
40537 0x218 User Map Address 14 30001 39999 1 --- F1 30950 1
40538 0x219 User Map Address 15 30001 39999 1 --- F1 30951 1
40539 0x21A User Map Address 16 30001 39999 1 --- F1 30948 1
40540 0x21B User Map Address 17 30001 39999 1 --- F1 30949 1
40541 0x21C User Map Address 18 30001 39999 1 --- F1 30946 1
40542 0x21D User Map Address 19 30001 39999 1 --- F1 30947 1
40543 0x21E User Map Address 20 30001 39999 1 --- F1 30976 1
40544 0x21F User Map Address 21 30001 39999 1 --- F1 30977 1
40545 0x220 User Map Address 22 30001 39999 1 --- F1 30974 1
40546 0x221 User Map Address 23 30001 39999 1 --- F1 30975 1
40547 0x222 User Map Address 24 30001 39999 1 --- F1 30972 1
40548 0x223 User Map Address 25 30001 39999 1 --- F1 30973 1
40549 0x224 User Map Address 26 30001 39999 1 --- F1 30970 1
40550 0x225 User Map Address 27 30001 39999 1 --- F1 30971 1
40551 0x226 User Map Address 28 30001 39999 1 --- F1 30984 1
40552 0x227 User Map Address 29 30001 39999 1 --- F1 30985 1
40553 0x228 User Map Address 30 30001 39999 1 --- F1 30982 1
40554 0x229 User Map Address 31 30001 39999 1 --- F1 30983 1
40555 0x22A User Map Address 32 30001 39999 1 --- F1 30980 1
40556 0x22B User Map Address 33 30001 39999 1 --- F1 30981 1
40557 0x22C User Map Address 34 30001 39999 1 --- F1 30978 1
40558 0x22D User Map Address 35 30001 39999 1 --- F1 30979 1
40559 0x22E User Map Address 36 30001 39999 1 --- F1 30186 1
40560 0x22F User Map Address 37 30001 39999 1 --- F1 30285 1
40561 0x230 User Map Address 38 30001 39999 1 --- F1 30286 1
40562 0x231 User Map Address 39 30001 39999 1 --- F1 30298 1
40563 0x232 User Map Address 40 30001 39999 1 --- F1 30299 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-19


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
40564 0x233 User Map Address 41 30001 39999 1 --- F1 30288 1
40565 0x234 User Map Address 42 30001 39999 1 --- F1 30289 1
40566 0x235 User Map Address 43 30001 39999 1 --- F1 30317 1
40567 0x236 User Map Address 44 30001 39999 1 --- F1 30291 1
40568 0x237 User Map Address 45 30001 39999 1 --- F1 30296 1
40569 0x238 User Map Address 46 30001 39999 1 --- F1 30297 1
40570 0x239 User Map Address 47 30001 39999 1 --- F1 30300 1
40571 0x23A User Map Address 48 30001 39999 1 --- F1 30301 1
40572 0x23B User Map Address 49 30001 39999 1 --- F1 30328 1
40573 0x23C User Map Address 50 30001 39999 1 --- F1 30329 1
40574 0x23D User Map Address 51 30001 39999 1 --- F1 30330 1
40575 0x23E User Map Address 52 30001 39999 1 --- F1 30331 1
40576 0x23F User Map Address 53 30001 39999 1 --- F1 30332 1
40577 0x240 User Map Address 54 30001 39999 1 --- F1 30333 1
40578 0x241 User Map Address 55 30001 39999 1 --- F1 30326 1
40579 0x242 User Map Address 56 30001 39999 1 --- F1 30327 1
40580 0x243 User Map Address 57 30001 39999 1 --- F1 30338 1
40581 0x244 User Map Address 58 30001 39999 1 --- F1 30339 1
40582 0x245 User Map Address 59 30001 39999 1 --- F1 30324 1
40583 0x246 User Map Address 60 30001 39999 1 --- F1 30325 1
40584 0x247 User Map Address 61 30001 39999 1 --- F1 30319 1
40585 0x248 User Map Address 62 30001 39999 1 --- F1 30320 1
40586 0x249 User Map Address 63 30001 39999 1 --- F1 31665 1
40587 0x24A User Map Address 64 30001 39999 1 --- F1 31666 1
40588 0x24B User Map Address 65 30001 39999 1 --- F1 31667 1
40589 0x24C User Map Address 66 30001 39999 1 --- F1 31668 1
40590 0x24D User Map Address 67 30001 39999 1 --- F1 31669 1
40591 0x24E User Map Address 68 30001 39999 1 --- F1 31670 1
40592 0x24F User Map Address 69 30001 39999 1 --- F1 31671 1
40593 0x250 User Map Address 70 30001 39999 1 --- F1 31672 1
40594 0x251 User Map Address 71 30001 39999 1 --- F1 31673 1
40595 0x252 User Map Address 72 30001 39999 1 --- F1 31674 1
40596 0x253 User Map Address 73 30001 39999 1 --- F1 31675 1
40597 0x254 User Map Address 74 30001 39999 1 --- F1 31676 1
40598 0x255 User Map Address 75 30001 39999 1 --- F1 31677 1
40599 0x256 User Map Address 76 30001 39999 1 --- F1 31678 1
40600 0x257 User Map Address 77 30001 39999 1 --- F1 31679 1
40601 0x258 User Map Address 78 30001 39999 1 --- F1 31680 1
40602 0x259 User Map Address 79 30001 39999 1 --- F1 31681 1
40603 0x25A User Map Address 80 30001 39999 1 --- F1 31682 1
40604 0x25B User Map Address 81 30001 39999 1 --- F1 31683 1
40605 0x25C User Map Address 82 30001 39999 1 --- F1 31684 1
40606 0x25D User Map Address 83 30001 39999 1 --- F1 31685 1
40607 0x25E User Map Address 84 30001 39999 1 --- F1 31686 1
40608 0x25F User Map Address 85 30001 39999 1 --- F1 31687 1

11-20 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
40609 0x260 User Map Address 86 30001 39999 1 --- F1 31688 1
40610 0x261 User Map Address 87 30001 39999 1 --- F1 31695 1
40611 0x262 User Map Address 88 30001 39999 1 --- F1 31696 1
40612 0x263 User Map Address 89 30001 39999 1 --- F1 31697 1
40613 0x264 User Map Address 90 30001 39999 1 --- F1 31698 1
40614 0x265 User Map Address 91 30001 39999 1 --- F1 31699 1
40615 0x266 User Map Address 92 30001 39999 1 --- F1 31700 1
40616 0x267 User Map Address 93 30001 39999 1 --- F1 30001 1
40617 0x268 User Map Address 94 30001 39999 1 --- F1 30001 1
40618 0x269 User Map Address 95 30001 39999 1 --- F1 30001 1
40619 0x26A User Map Address 96 30001 39999 1 --- F1 30001 1
40620 0x26B User Map Address 97 30001 39999 1 --- F1 30001 1
40621 0x26C User Map Address 98 30001 39999 1 --- F1 30001 1
40622 0x26D User Map Address 99 30001 39999 1 --- F1 30001 1
40623 0x26E User Map Address 100 30001 39999 1 --- F1 30001 1
40624 0x26F User Map Address 101 30001 39999 1 --- F1 30001 1
40625 0x270 User Map Address 102 30001 39999 1 --- F1 30001 1
40626 0x271 User Map Address 103 30001 39999 1 --- F1 30001 1
40627 0x272 User Map Address 104 30001 39999 1 --- F1 30001 1
40628 0x273 User Map Address 105 30001 39999 1 --- F1 30001 1
40629 0x274 User Map Address 106 30001 39999 1 --- F1 30001 1
40630 0x275 User Map Address 107 30001 39999 1 --- F1 30001 1
40631 0x276 User Map Address 108 30001 39999 1 --- F1 30001 1
40632 0x277 User Map Address 109 30001 39999 1 --- F1 30001 1
40633 0x278 User Map Address 110 30001 39999 1 --- F1 30001 1
40634 0x279 User Map Address 111 30001 39999 1 --- F1 30001 1
40635 0x27A User Map Address 112 30001 39999 1 --- F1 30001 1
40636 0x27B User Map Address 113 30001 39999 1 --- F1 30001 1
40637 0x27C User Map Address 114 30001 39999 1 --- F1 30001 1
40638 0x27D User Map Address 115 30001 39999 1 --- F1 30001 1
40639 0x27E User Map Address 116 30001 39999 1 --- F1 30001 1
40640 0x27F User Map Address 117 30001 39999 1 --- F1 30001 1
40641 0x280 User Map Address 118 30001 39999 1 --- F1 30001 1
40642 0x281 User Map Address 119 30001 39999 1 --- F1 30001 1
40643 0x282 User Map Address 120 30001 39999 1 --- F1 30001 1
40644 0x283 User Map Address 121 30001 39999 1 --- F1 30001 1
40645 0x284 User Map Address 122 30001 39999 1 --- F1 30001 1
40646 0x285 User Map Address 123 30001 39999 1 --- F1 30001 1
40647 0x286 User Map Address 124 30001 39999 1 --- F1 30001 1
40648 0x287 User Map Address 125 30001 39999 1 --- F1 30001 1
TRANSIENT RECORDER TRIGGERS
40650 0x289 Trigger On Input 1 0 0xEF02 1 --- F89A 0 1
40651 0x28A Trigger On Input 2 0 0xEF02 1 --- F89A 0 1
40652 0x28B Trigger On Input 3 0 0xEF02 1 --- F89A 0 1
EVENT RECORDER

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-21


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
40649 0x288 Recording of Block Events 0 1 1 --- FC126 1 1
40654 0x28D Recording of Pickup Events 0 1 1 --- FC126 0 1
40655 0x28E Recording of Contact Input 0 1 1 --- FC126 1 1
Events
40656 0x28F Recording of Virtual Input 0 1 1 --- FC126 1 1
Events
40657 0x290 Recording of Remote Inputs 0 1 1 --- FC126 1 1
40658 0x291 Recording of Logic Element 0 1 1 --- FC126 1 1
Events
40660 0x293 Recording of Trip Events 0 1 1 --- FC126 1 1
40661 0x294 Recording of Alarm Events 0 1 1 --- FC126 1 1
40662 0x295 Recording of Control Events 0 1 1 --- FC126 1 1
40665 0x298 Recording of Dropout Events 0 1 1 --- FC126 0 1
40666 0x299 Recording of Set Time/Date 0 1 1 --- FC126 0 1
Events
40667 0x29A Event Record Selector 1 65535 1 --- F1 1 1
TEMPERATURE
40820 0x333 Enable Ambient Temp 0 2 1 --- FC206 0 1
40821 0x334 HI Alarm Level 20 80 1 °C F1 60 1
40822 0x335 Low Alarm Level -40 20 1 °C F4 10 1
40823 0x336 Hysteresis Level 2 10 1 °C F1 2 1
40824 0x337 Time Delay 1 60 1 min F1 1 1
40825 0x338 Output Relays 0 0x7F 1 --- FC198 0 1
TRANSIENT RECORDER
40668 0x29B Trigger on Pickup 0 1 1 --- FC103 0 1
40669 0x29C Trigger on Dropout 0 1 1 --- FC103 0 1
40670 0x29D Trigger on Alarm 0 1 1 --- FC103 0 1
40671 0x29E Trigger on Dropout 0 1 1 --- FC103 0 1
40672 0x29F Trace Memory Channel 0 16 1 --- F26B 0 1
Selector
40673 0x2A0 Trace Memory Buffer 0 10 1 --- F1 0 1
Selector
40674 0x2A1 Trace Memory Sample Index 0 6144 1 --- F1 0 1
40676 0x2A3 Trace Memory Trigger 0 100 1 % F1 20 1
Position
40677 0x2A4 Trigger Mode 0 1 1 --- FC148 0 1
40678 0x2A5 Number of Records 0 2 1 --- F95 0 1
40887 0x376 Transient Sampling Rate 0 3 1 --- FC429 0 1
RELAY STATUS
40927 0x39E Relay Status 0 1 1 --- F99 0 1
CONTACT INPUT NAMES (1 TO 8)
40961 0x3C0 Input Name 1 0 7 1 --- F22 BKR1 52a 7
(CI#1)
40970 0x3C9 Input Name 2 0 7 1 --- F22 BKR1 52b 7
(CI#2)
40979 0x3D2 Input Name 3 0 7 1 --- F22 BKR2 52a 7
(CI#3)
40988 0x3DB Input Name 4 0 7 1 --- F22 BKR2 52b 7
(CI#4)

11-22 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
40997 0x3E4 Input Name 5 0 7 1 --- F22 Input 5 7
41006 0x3ED Input Name 6 0 7 1 --- F22 Input 6 7
41015 0x3F6 Input Name 7 0 7 1 --- F22 Input 7 7
41024 0x3FF Input Name 8 0 7 1 --- F22 Input 8 7
EDIT SETPOINT GROUP
41113 0x458 Edit Setpoint Group -1 1 1 --- F91 0 1
LOGIC ELEMENTS
41118 0x45D Timer 1 Pickup Delay 0 60000 1 ms F1 0 1
41119 0x45E Timer 1 Dropout Delay 0 60000 1 ms F1 0 1
41120 0x45F Logic Element 1 Function 0 4 1 --- FC205 0 1
41121 0x460 Logic Element 1 Asserted 0 1 1 --- FC103 0 1
41122 0x461 Logic Element 1 Relay 0 0x7F 1 --- FC198 0 1
41126 0x465 Timer 2 Pickup Delay 0 60000 1 ms F1 0 1
41127 0x466 Timer 2 Dropout Delay 0 60000 1 ms F1 0 1
41128 0x467 Logic Element 2 Function 0 4 1 --- FC205 0 1
41129 0x468 Logic Element 2 Asserted 0 1 1 --- FC103 0 1
41130 0x469 Logic Element 2 Relay 0 0x7F 1 --- FC198 0 1
41134 0x46D Timer 3 Pickup Delay 0 60000 1 ms F1 0 1
41135 0x46E Timer 3 Dropout Delay 0 60000 1 ms F1 0 1
41136 0x46F Logic Element 3 Function 0 4 1 --- FC205 0 1
41137 0x470 Logic Element 3 Asserted 0 1 1 --- FC103 0 1
41138 0x471 Logic Element 3 Relay 0 0x7F 1 --- FC198 0 1
41142 0x475 Timer 4 Pickup Delay 0 60000 1 ms F1 0 1
41143 0x476 Timer 4 Dropout Delay 0 60000 1 ms F1 0 1
41144 0x477 Logic Element 4 Function 0 4 1 --- FC205 0 1
41145 0x478 Logic Element 4 Asserted 0 1 1 --- FC103 0 1
41146 0x479 Logic Element 4 Relay 0 0x7F 1 --- FC198 0 1
41150 0x47D Timer 5 Pickup Delay 0 60000 1 ms F1 0 1
41151 0x47E Timer 5 Dropout Delay 0 60000 1 ms F1 0 1
41152 0x47F Logic Element 5 Function 0 4 1 --- FC205 0 1
41153 0x480 Logic Element 5 Asserted 0 1 1 --- FC103 0 1
41154 0x481 Logic Element 5 Relay 0 0x7F 1 --- FC198 0 1
41158 0x485 Timer 6 Pickup Delay 0 60000 1 ms F1 0 1
41159 0x486 Timer 6 Dropout Delay 0 60000 1 ms F1 0 1
41160 0x487 Logic Element 6 Function 0 4 1 --- FC205 0 1
41161 0x488 Logic Element 6 Asserted 0 1 1 --- FC103 0 1
41162 0x489 Logic Element 6 Relay 0 0x7F 1 --- FC198 0 1
41166 0x48D Timer 7 Pickup Delay 0 60000 1 ms F1 0 1
41167 0x48E Timer 7 Dropout Delay 0 60000 1 ms F1 0 1
41168 0x48F Logic Element 7 Function 0 4 1 --- FC205 0 1
41169 0x490 Logic Element 7 Asserted 0 1 1 --- FC103 0 1
41170 0x491 Logic Element 7 Relay 0 0x7F 1 --- FC198 0 1
41174 0x495 Timer 8 Pickup Delay 0 60000 1 ms F1 0 1
41175 0x496 Timer 8 Dropout Delay 0 60000 1 ms F1 0 1
41176 0x497 Logic Element 8 Function 0 4 1 --- FC205 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-23


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
41177 0x498 Logic Element 8 Asserted 0 1 1 --- FC103 0 1
41178 0x499 Logic Element 8 Relay 0 0x7F 1 --- FC198 0 1
41182 0x49D Timer 9 Pickup Delay 0 60000 1 ms F1 0 1
41183 0x49E Timer 9 Dropout Delay 0 60000 1 ms F1 0 1
41184 0x49F Logic Element 9 Function 0 4 1 --- FC205 0 1
41185 0x4A0 Logic Element 9 Asserted 0 1 1 --- FC103 0 1
41186 0x4A1 Logic Element 9 Relay 0 0x7F 1 --- FC198 0 1
41190 0x4A5 Timer 10 Pickup Delay 0 60000 1 ms F1 0 1
41191 0x4A6 Timer 10 Dropout Delay 0 60000 1 ms F1 0 1
41192 0x4A7 Logic Element 10 Function 0 4 1 --- FC205 0 1
41193 0x4A8 Logic Element 10 Asserted 0 1 1 --- FC103 0 1
41194 0x4A9 Logic Element 10 Relay 0 0x7F 1 --- FC198 0 1
41198 0x4AD Timer 11 Pickup Delay 0 60000 1 ms F1 0 1
41199 0x4AE Timer 11 Dropout Delay 0 60000 1 ms F1 0 1
41200 0x4AF Logic Element 11 Function 0 4 1 --- FC205 0 1
41201 0x4B0 Logic Element 11 Asserted 0 1 1 --- FC103 0 1
41202 0x4B1 Logic Element 11 Relay 0 0x7F 1 --- FC198 0 1
41206 0x4B5 Timer 12 Pickup Delay 0 60000 1 ms F1 0 1
41207 0x4B6 Timer 12 Dropout Delay 0 60000 1 ms F1 0 1
41208 0x4B7 Logic Element 12 Function 0 4 1 --- FC205 0 1
41209 0x4B8 Logic Element 12 Asserted 0 1 1 --- FC103 0 1
41210 0x4B9 Logic Element 12 Relay 0 0x7F 1 --- FC198 0 1
41214 0x4BD Timer 13 Pickup Delay 0 60000 1 ms F1 0 1
41215 0x4BE Timer 13 Dropout Delay 0 60000 1 ms F1 0 1
41216 0x4BF Logic Element 13 Function 0 4 1 --- FC205 0 1
41217 0x4C0 Logic Element 13 Asserted 0 1 1 --- FC103 0 1
41218 0x4C1 Logic Element 13 Relay 0 0x7F 1 --- FC198 0 1
41222 0x4C5 Timer 14 Pickup Delay 0 60000 1 ms F1 0 1
41223 0x4C6 Timer 14 Dropout Delay 0 60000 1 ms F1 0 1
41224 0x4C7 Logic Element 14 Function 0 4 1 --- FC205 0 1
41225 0x4C8 Logic Element 14 Asserted 0 1 1 --- FC103 0 1
41226 0x4C9 Logic Element 14 Relay 0 0x7F 1 --- FC198 0 1
41230 0x4CD Timer 15 Pickup Delay 0 60000 1 ms F1 0 1
41231 0x4CE Timer 15 Dropout Delay 0 60000 1 ms F1 0 1
41232 0x4CF Logic Element 15 Function 0 4 1 --- FC205 0 1
41233 0x4D0 Logic Element 15 Asserted 0 1 1 --- FC103 0 1
41234 0x4D1 Logic Element 15 Relay 0 0x7F 1 --- FC198 0 1
41238 0x4D5 Timer 16 Pickup Delay 0 60000 1 ms F1 0 1
41239 0x4D6 Timer 16 Dropout Delay 0 60000 1 ms F1 0 1
41240 0x4D7 Logic Element 16 Function 0 4 1 --- FC205 0 1
41241 0x4D8 Logic Element 16 Asserted 0 1 1 --- FC103 0 1
41242 0x4D9 Logic Element 16 Relay 0 0x7F 1 --- FC198 0 1
REMOTE RESET
41380 0x563 Remote Reset 0 0xEF02 1 --- F89A 0 1
WINDING 1 BREAKER

11-24 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
41388 0x56B Breaker Connected 0 0x49 0 --- FC204B 0 1
41389 0x56C Breaker 52a Contact 0 0x40 0 --- FC204A 0 1
41390 0x56D Breaker 52b Contact 0 0x41 0 --- FC204C 0 1
SETPOINT GROUP CHANGE
41404 0x57B Set Group 2 Active 0 0xEF02 1 --- F89 0 1
41405 0x57C Block Group Change 0 0xEF02 1 --- F89 0 1
WINDING 2 BREAKER
41414 0x585 Breaker 2 Connected 0 0x49 0 --- FC204B 0 1
41415 0x586 Breaker 2 52a Contact 0 0x42 0 --- FC204D 0 1
41416 0x587 Breaker 2 52b Contact 0 0x43 0 --- FC204F 0 1
TRANSFORMER SETUP
41420 0x58B XFMR Rated MVA 0 20000 1 MVA F11 500 2
41422 0x58D XFRM Type 0 25 1 --- FC419 0 1
41423 0x58E Phase Compensation 0 1 1 --- FC411 0 1
41424 0x58F Winding 1 Ph-Ph Voltage 1 25000 1 kV F11 1380 2
41426 0x591 Winding 1 Grounding 0 1 0 --- FC413 0 1
41427 0x592 Winding 2 Ph-Ph Voltage 1 25000 1 kV F11 416 2
41429 0x594 Winding 2 Grounding 0 1 0 --- FC413 0 1
CONTACT INPUT NAMES (9 TO 10)
41435 0x59A Input Name 9 0 7 1 --- F22 Input 9 7
41444 0x5A3 Input Name 10 0 7 1 --- F22 Input 10 7
CONTACT INPUTS
41454 0x5AD Input 9 Debounce Interval 1 64 1 ms F1 2 1
41455 0x5AE Input 10 Debounce Interval 1 64 1 ms F1 2 1
41456 0x5AF Input 1 Debounce Interval 1 64 1 ms F1 2 1
41457 0x5B0 Input 2 Debounce Interval 1 64 1 ms F1 2 1
41458 0x5B1 Input 3 Debounce Interval 1 64 1 ms F1 2 1
41459 0x5B2 Input 4 Debounce Interval 1 64 1 ms F1 2 1
41460 0x5B3 Input 5 Debounce Interval 1 64 1 ms F1 2 1
41461 0x5B4 Input 6 Debounce Interval 1 64 1 ms F1 2 1
41462 0x5B5 Input 7 Debounce Interval 1 64 1 ms F1 2 1
41463 0x5B6 Input 8 Debounce Interval 1 64 1 ms F1 2 1
41465 0x5B8 Select DC Voltage 0 3 1 --- FC123 2 1
FRONT PANEL SETUP
41475 0x5C2 Screen Saver 0 10000 1 min F1C 0 1
41498 0x5D9 Breaker Open Color 0 3 1 --- FC157 2 1
41500 0x5DB Breaker Close Color 0 3 1 --- FC157 2 1
41502 0x5DD W2 Breaker Open Colour 0 3 1 --- FC157 2 1
41504 0x5DF W2 Breaker Closed Colour 0 3 1 --- FC157 2 1
OUTPUT RELAYS
41510 0x5E5 Relay 3 Type 0 1 1 --- FC199 0 1
41511 0x5E6 Relay 4 Type 0 1 1 --- FC199 0 1
41512 0x5E7 Relay 5 Type 0 1 1 --- FC199 0 1
41513 0x5E8 Relay 6 Type 0 1 1 --- FC199 0 1
41547 0x60A Block Relay 1 Trip 0 0xEF02 1 --- F89 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-25


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
41549 0x60C Block Relay 2 Trip 0 0xEF02 1 --- F89 0 1
PROGRAMMABLE LEDs
41522 0x5F1 LED 1 Type 0 1 1 --- FC199 0 1
41523 0x5F2 LED 2 Type 0 1 1 --- FC199 0 1
41524 0x5F3 LED 3 Type 0 1 1 --- FC199 0 1
41525 0x5F4 LED 4 Type 0 1 1 --- FC199 0 1
41526 0x5F5 LED 5 Type 0 1 1 --- FC199 0 1
41527 0x5F6 LED 6 Type 0 1 1 --- FC199 0 1
41528 0x5F7 LED 7 Type 0 1 1 --- FC199 0 1
41529 0x5F8 LED 8 Type 0 1 1 --- FC199 0 1
41570 0x621 LED 1 Source 0 0xFFFF 1 --- FC134B 0 1
41572 0x623 LED 2 Source 0 0xFFFF 1 --- FC134B 0 1
41574 0x625 LED 3 Source 0 0xFFFF 1 --- FC134B 0 1
41576 0x627 LED 4 Source 0 0xFFFF 1 --- FC134B 0 1
41578 0x629 LED 5 Source 0 0xFFFF 1 --- FC134B 0 1
41579 0x62A LED 5 Color 0 3 1 --- FC157 3 1
41580 0x62B LED 6 Source 0 0xFFFF 1 --- FC134B 0 1
41581 0x62C LED 6 Color 0 3 1 --- FC157 3 1
41582 0x62D LED 7 Source 0 0xFFFF 1 --- FC134B 0 1
41583 0x62E LED 7 Color 0 3 1 --- FC157 3 1
41584 0x62F LED 8 Source 0 0xFFFF 1 --- FC134B 0 1
41585 0x630 LED 8 Color 0 3 1 --- FC157 3 1
BREAKER TRIP COUNTER
41563 0x61A W2 Breaker Trip Counter 0 10000 1 --- F1 0 1
Initial Trips
41564 0x61B W2 Breaker Trip Counter 0 2 1 --- FC206 0 1
Function
41565 0x61C W2 Breaker Trip Counter 1 10000 1 trips F1 1 1
Limit
41566 0x61D W2 Breaker Trip Counter 0 0x7F 1 --- FC198 0 1
Relay
42210 0x8A1 W1 Breaker Trip Counter 0 10000 1 --- F1 0 1
Initial Trips
42211 0x8A2 W1 Breaker Trip Counter 0 2 1 --- FC206 0 1
Function
42212 0x8A3 W1 Breaker Trip Counter 1 10000 1 trips F1 1 1
Pickup
42213 0x8A4 W1 Breaker Trip Counter 0 0x7F 1 --- FC198 0 1
Relay
COIL MONITORS
42214 0x8A5 Bypass Breaker Status 0 1 1 --- FC126 0 1
42215 0x8A6 Relay1 Coil Monitor Function 0 2 1 --- FC206 0 1
42216 0x8A7 Relay1 Coil Monitor Pickup 1 10 1 s F1 5 1
42217 0x8A8 Relay1 Coil Monitor Relay 0 0x7F 1 --- FC198 0 1
42218 0x8A9 Bypass Breaker Status 0 1 1 --- FC126 0 1
42219 0x8AA Relay2 Coil Monitor Function 0 2 1 --- FC206 0 1
42220 0x8AB Relay2 Coil Monitor Pickup 1 10 1 s F1 5 1
42221 0x8AC Relay2 Coil Monitor Relay 0 0x7F 1 --- FC198 0 1

11-26 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
TRIP RELAY SEAL-IN
42222 0x8AD Relay 1 Seal-In 0 999 1 s F3 4 1
42224 0x8AF Relay 2 Trip Seal-In 0 999 1 s F3 4 1
W1 BREAKER FAIL
42262 0x8D5 Breaker Failure Function 0 2 1 --- FC206 0 1
42263 0x8D6 Breaker Failure Delay 1 3 100 1 s F3 10 1
42264 0x8D7 Breaker Failure Current 5 2000 1 x CT F3 100 1
42265 0x8D8 Breaker Failure Delay 2 0 100 1 s F3 0 1
42266 0x8D9 Breaker Failure Relays 0 0x7F 1 --- FC198 0 1
42267 0x8DA Breaker Failure Ext Initiate 0 0xEF02 1 --- F89 0 1
PHASE IOC1
42485 0x9B4 Phase IOC Function 0 3 1 --- FC197 0 1
42486 0x9B5 Phase IOC Pickup 5 2000 1 x CT F3 100 1
42487 0x9B6 Phase IOC Delay 0 30000 1 s F3 0 1
NEUTRAL IOC1
42490 0x9B9 Neutral IOC Function 0 3 1 --- FC197 0 1
42491 0x9BA Neutral IOC Pickup 5 2000 1 x CT F3 100 1
42492 0x9BB Neutral IOC Delay 0 30000 1 s F3 0 1
GROUND IOC1
42494 0x9BD Ground IOC Function 0 3 1 --- FC197 0 1
42495 0x9BE Ground IOC Pickup 5 2000 1 x CT F3 100 1
42496 0x9BF Ground IOC Delay 0 30000 1 s F3 0 1
PHASE TOC1
42498 0x9C1 Phase Time OC Function 0 3 1 --- FC197 0 1
42499 0x9C2 Phase Time OC Pickup 5 2000 1 x CT F3 100 1
42500 0x9C3 Phase Time OC Curve 0 14 1 --- F36 0 1
42501 0x9C4 Phase Time OC Multiplier 5 5000 1 --- F3 100 1
42502 0x9C5 Phase Time OC Reset 0 1 1 --- F68 0 1
NEUTRAL TOC1
42504 0x9C7 Neutral Time OC Function 0 3 1 --- FC197 0 1
42505 0x9C8 Neutral Time OC Pickup 5 2000 1 x CT F3 100 1
42506 0x9C9 Neutral Time OC Curve 0 14 1 --- F36 0 1
42507 0x9CA Neutral Time OC Multiplier 5 5000 1 --- F3 100 1
42508 0x9CB Neutral Time OC Reset 0 1 1 --- F68 0 1
GROUND TOC1
42510 0x9CD Ground Time OC Function 0 3 1 --- FC197 0 1
42511 0x9CE Ground Time OC Pickup 5 2000 1 x CT F3 100 1
42512 0x9CF Ground Time OC Curve 0 14 1 --- F36 0 1
42513 0x9D0 Ground Time OC Multiplier 5 5000 1 --- F3 100 1
42514 0x9D1 Ground Time OC Reset 0 1 1 --- F68 0 1
PHASE IOC2
42516 0x9D3 Phase IOC 2 Function 0 3 1 --- FC197 0 1
42517 0x9D4 Phase IOC 2 Pickup 5 2000 1 x CT F3 100 1
42518 0x9D5 Phase IOC 2 Delay 0 30000 1 s F3 0 1
NEUTRAL IOC2

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-27


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
42521 0x9D8 Neutral IOC 2 Function 0 3 1 --- FC197 0 1
42522 0x9D9 Neutral IOC 2 Pickup 5 2000 1 x CT F3 100 1
42523 0x9DA Neutral IOC 2 Delay 0 30000 1 s F3 0 1
GROUND IOC2
42525 0x9DC Ground IOC 2 Function 0 3 1 --- FC197 0 1
42526 0x9DD Ground IOC 2 Pickup 5 2000 1 x CT F3 100 1
42527 0x9DE Ground IOC 2 Delay 0 30000 1 s F3 0 1
PHASE TOC2
42529 0x9E0 Phase Time OC 2 Function 0 3 1 --- FC197 0 1
42530 0x9E1 Phase Time OC 2 Pickup 5 2000 1 x CT F3 100 1
42531 0x9E2 Phase Time OC 2 Curve 0 14 1 --- F36 0 1
42532 0x9E3 Phase Time OC 2 Multiplier 5 5000 1 --- F3 100 1
42533 0x9E4 Phase Time OC 2 Reset 0 1 1 --- F68 0 1
NEUTRAL TOC2
42535 0x9E6 Neutral Time OC 2 Function 0 3 1 --- FC197 0 1
42536 0x9E7 Neutral Time OC 2 Pickup 5 2000 1 x CT F3 100 1
42537 0x9E8 Neutral Time OC 2 Curve 0 14 1 --- F36 0 1
42538 0x9E9 Neutral Time OC 2 Multiplier 5 5000 1 --- F3 100 1
42539 0x9EA Neutral Time OC 2 Reset 0 1 1 --- F68 0 1
GROUND TOC2
42541 0x9EC Ground Time OC 2 Function 0 3 1 --- FC197 0 1
42542 0x9ED Ground Time OC 2 Pickup 5 2000 1 x CT F3 100 1
42543 0x9EE Ground Time OC 2 Curve 0 14 1 --- F36 0 1
42544 0x9EF Ground Time OC 2 Multiplier 5 5000 1 --- F3 100 1
42545 0x9F0 Ground Time OC 2 Reset 0 1 1 --- F68 0 1
SENSITIVE GROUND TOC1
42547 0x9F2 Sensitive Ground Time OC 0 3 1 --- FC197 0 1
Function
42548 0x9F3 Sensitive Ground Time OC 5 3000 1 x CT F17A 1000 1
Pickup
42549 0x9F4 Sensitive Ground Time OC 0 14 1 --- F36 0 1
Curve
42550 0x9F5 Sensitive Ground Time OC 5 5000 1 --- F3 100 1
Multiplier
42551 0x9F6 Sensitive Ground Time OC 0 1 1 --- F68 0 1
Reset
SENSITIVE GROUND IOC1
42598 0xA25 Sensitive Ground IOC 0 3 1 --- FC197 0 1
Function
42599 0xA26 Sensitive Ground IOC Pickup 5 3000 1 x CT F17A 1000 1
42600 0xA27 Sensitive Ground IOC Delay 0 30000 1 s F3 0 1
SENSITIVE GROUND IOC2
42601 0xA28 Sensitive Ground 2 IOC 0 3 1 --- FC197 0 1
Function
42602 0xA29 Sensitive Ground 2 IOC 5 3000 1 x CT F17A 1000 1
Pickup
42603 0xA2A Sensitive Ground 2 IOC 0 30000 1 s F3 0 1
Delay

11-28 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
TRANSFORMER PERCENT DIFFERENTIAL
42608 0xA2F XFMR Pcnt Func 0 3 1 --- FC197 0 1
42609 0xA30 Minimum Diff Pkp 5 100 1 x CT F3 10 1
42610 0xA31 Slope1 15 100 1 % F1 30 1
42611 0xA32 Break 1 50 400 1 x CT F3 150 1
42612 0xA33 Break 2 100 1000 1 x CT F3 150 1
42613 0xA34 Slope 2 50 100 1 % F1 95 1
42614 0xA35 Inrush Inhbit Func 0 1 1 --- FC408 1 1
42615 0xA36 Inrush Level 1 400 1 % fo F2 200 1
42616 0xA37 Inrush Inhibit Mode 0 3 1 --- FC409 0 1
42617 0xA38 Overexcitation Func 0 1 1 --- FC410 0 1
42618 0xA39 Overexcitation Level 10 400 1 % fo F2 100 1
42619 0xA3A Output Relays 0 0x7F 1 --- FC198 0 1
RESTRICTED GROUND FAULT1
42620 0xA3B RGF 1 Pickup 2 2000 1 x CT F17A 5 1
42621 0xA3C GND Current SPVSN Level 2 1000 1 x CTg F17A 10 1
42624 0xA3F Restd Gnd Fault 1 Func 0 3 1 --- FC197 0 1
42625 0xA40 REF CT Input 1 0 1 1 --- FC418 0 1
42626 0xA41 RGF 1 Pickup 2 2000 1 x CT F3 5 1
42627 0xA42 RGF 1 Slope 0 100 1 % F1 20 1
42628 0xA43 RGF 1 Delay 0 60000 1 s F3 50 1
42629 0xA44 GND Current SPVSN 0 1 1 --- FC126 0 1
42630 0xA45 GND Current SPVSN Level 2 1000 1 x CTg F3 10 1
RESTRICTED GROUND FAULT2
42622 0xA3D RGF 2 Pickup 2 2000 1 x CT F17A 5 1
42623 0xA3E GND Current SPVSN Level 2 2000 1 x CTg F17A 10 1
42631 0xA46 Restd Gnd Fault 2 Func 0 3 1 --- FC197 0 1
42632 0xA47 REF CT Input 2 0 1 1 --- FC418 0 1
42633 0xA48 RGF 2 Pickup 2 2000 1 x CT F3 5 1
42634 0xA49 RGF 2 Slope 0 100 1 % F1 20 1
42635 0xA4A RGF 2 Delay 0 60000 1 s F3 50 1
42636 0xA4B GND Current SPVSN 0 1 1 --- FC126 0 1
42637 0xA4C GND Current SPVSN Level 2 2000 1 x CTg F3 10 1
TRANSFORMER INSTANTANEOUS DIFFERENTIAL
42638 0xA4D Inst Diff Function 0 3 1 --- FC197 0 1
42639 0xA4E Inst Diff Pickup 300 2000 1 x CT F3 800 1
W2 BYPASS BREAKER STATUS
42816 0xAFF Bypass Breaker 2 Status 0 1 1 --- FC126 0 1
VIRTUAL INPUT NAMES
42884 0xB43 Virtual Input Name 1 0 9 1 --- F22 Virtual IN 1 9
42893 0xB4C Virtual Input Name 2 0 9 1 --- F22 Virtual IN 2 9
42902 0xB55 Virtual Input Name 3 0 9 1 --- F22 Virtual IN 3 9
42911 0xB5E Virtual Input Name 4 0 9 1 --- F22 Virtual IN 4 9
42920 0xB67 Virtual Input Name 5 0 9 1 --- F22 Virtual IN 5 9
42929 0xB70 Virtual Input Name 6 0 9 1 --- F22 Virtual IN 6 9

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-29


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
42938 0xB79 Virtual Input Name 7 0 9 1 --- F22 Virtual IN 7 9
42947 0xB82 Virtual Input Name 8 0 9 1 --- F22 Virtual IN 8 9
42956 0xB8B Virtual Input Name 9 0 9 1 --- F22 Virtual IN 9 9
42965 0xB94 Virtual Input Name 10 0 9 1 --- F22 Virtual IN 9
10
42974 0xB9D Virtual Input Name 11 0 9 1 --- F22 Virtual IN 9
11
42983 0xBA6 Virtual Input Name 12 0 9 1 --- F22 Virtual IN 9
12
42992 0xBAF Virtual Input Name 13 0 9 1 --- F22 Virtual IN 9
13
43001 0xBB8 Virtual Input Name 14 0 9 1 --- F22 Virtual IN 9
14
43010 0xBC1 Virtual Input Name 15 0 9 1 --- F22 Virtual IN 9
15
43019 0xBCA Virtual Input Name 16 0 9 1 --- F22 Virtual IN 9
16
43028 0xBD3 Virtual Input Name 17 0 9 1 --- F22 Virtual IN 9
17
43037 0xBDC Virtual Input Name 18 0 9 1 --- F22 Virtual IN 9
18
43046 0xBE5 Virtual Input Name 19 0 9 1 --- F22 Virtual IN 9
19
43055 0xBEE Virtual Input Name 20 0 9 1 --- F22 Virtual IN 9
20
43064 0xBF7 Virtual Input Name 21 0 9 1 --- F22 Virtual IN 9
21
43073 0xC00 Virtual Input Name 22 0 9 1 --- F22 Virtual IN 9
22
43082 0xC09 Virtual Input Name 23 0 9 1 --- F22 Virtual IN 9
23
43091 0xC12 Virtual Input Name 24 0 9 1 --- F22 Virtual IN 9
24
43100 0xC1B Virtual Input Name 25 0 9 1 --- F22 Virtual IN 9
25
43109 0xC24 Virtual Input Name 26 0 9 1 --- F22 Virtual IN 9
26
43118 0xC2D Virtual Input Name 27 0 9 1 --- F22 Virtual IN 9
27
43127 0xC36 Virtual Input Name 28 0 9 1 --- F22 Virtual IN 9
28
43136 0xC3F Virtual Input Name 29 0 9 1 --- F22 Virtual IN 9
29
43145 0xC48 Virtual Input Name 30 0 9 1 --- F22 Virtual IN 9
30
43154 0xC51 Virtual Input Name 31 0 9 1 --- F22 Virtual IN 9
31
43163 0xC5A Virtual Input Name 32 0 9 1 --- F22 Virtual IN 9
32
SIMULATION
RTD PROTECTION
40335 0x14E RTD 1 Alarm PKP Delay 0 60000 1 s F3 200 1
40336 0x14F RTD 2 Alarm PKP Delay 0 60000 1 s F3 200 1

11-30 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
40337 0x150 RTD 3 Alarm PKP Delay 0 60000 1 s F3 200 1
40338 0x151 RTD 4 Alarm PKP Delay 0 60000 1 s F3 200 1
40339 0x152 RTD 5 Alarm PKP Delay 0 60000 1 s F3 200 1
40340 0x153 RTD 6 Alarm PKP Delay 0 60000 1 s F3 200 1
40341 0x154 RTD 7 Alarm PKP Delay 0 60000 1 s F3 200 1
40342 0x155 RTD 8 Alarm PKP Delay 0 60000 1 s F3 200 1
40343 0x156 RTD 9 Alarm PKP Delay 0 60000 1 s F3 200 1
40344 0x157 RTD 10 Alarm PKP Delay 0 60000 1 s F3 200 1
40345 0x158 RTD 11 Alarm PKP Delay 0 60000 1 s F3 200 1
40346 0x159 RTD 12 Alarm PKP Delay 0 60000 1 s F3 200 1
40347 0x15A RTD 1 Alarm DPO Delay 0 60000 1 s F3 200 1
40348 0x15B RTD 2 Alarm DPO Delay 0 60000 1 s F3 200 1
40349 0x15C RTD 3 Alarm DPO Delay 0 60000 1 s F3 200 1
40350 0x15D RTD 4 Alarm DPO Delay 0 60000 1 s F3 200 1
40351 0x15E RTD 5 Alarm DPO Delay 0 60000 1 s F3 200 1
40352 0x15F RTD 6 Alarm DPO Delay 0 60000 1 s F3 200 1
40353 0x160 RTD 7 Alarm DPO Delay 0 60000 1 s F3 200 1
40354 0x161 RTD 8 Alarm DPO Delay 0 60000 1 s F3 200 1
40355 0x162 RTD 9 Alarm DPO Delay 0 60000 1 s F3 200 1
40356 0x163 RTD 10 Alarm DPO Delay 0 60000 1 s F3 200 1
40357 0x164 RTD 11 Alarm DPO Delay 0 60000 1 s F3 200 1
40358 0x165 RTD 12 Alarm DPO Delay 0 60000 1 s F3 200 1
40359 0x166 RTD 1 Trip PKP Delay 0 60000 1 s F3 200 1
40360 0x167 RTD 2 Trip PKP Delay 0 60000 1 s F3 200 1
40361 0x168 RTD 3 Trip PKP Delay 0 60000 1 s F3 200 1
40362 0x169 RTD 4 Trip PKP Delay 0 60000 1 s F3 200 1
40363 0x16A RTD 5 Trip PKP Delay 0 60000 1 s F3 200 1
40364 0x16B RTD 6 Trip PKP Delay 0 60000 1 s F3 200 1
40365 0x16C RTD 7 Trip PKP Delay 0 60000 1 s F3 200 1
40366 0x16D RTD 8 Trip PKP Delay 0 60000 1 s F3 200 1
40367 0x16E RTD 9 Trip PKP Delay 0 60000 1 s F3 200 1
40368 0x16F RTD 10 Trip PKP Delay 0 60000 1 s F3 200 1
40369 0x170 RTD 11 Trip PKP Delay 0 60000 1 s F3 200 1
40370 0x171 RTD 12 Trip PKP Delay 0 60000 1 s F3 200 1
40371 0x172 RTD 1 Trip DPO Delay 0 60000 1 s F3 200 1
40372 0x173 RTD 2 Trip DPO Delay 0 60000 1 s F3 200 1
40373 0x174 RTD 3 Trip DPO Delay 0 60000 1 s F3 200 1
40374 0x175 RTD 4 Trip DPO Delay 0 60000 1 s F3 200 1
40375 0x176 RTD 5 Trip DPO Delay 0 60000 1 s F3 200 1
40376 0x177 RTD 6 Trip DPO Delay 0 60000 1 s F3 200 1
40377 0x178 RTD 7 Trip DPO Delay 0 60000 1 s F3 200 1
40378 0x179 RTD 8 Trip DPO Delay 0 60000 1 s F3 200 1
40379 0x17A RTD 9 Trip DPO Delay 0 60000 1 s F3 200 1
40380 0x17B RTD 10 Trip DPO Delay 0 60000 1 s F3 200 1
40381 0x17C RTD 11 Trip DPO Delay 0 60000 1 s F3 200 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-31


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
40382 0x17D RTD 12 Trip DPO Delay 0 60000 1 s F3 200 1
40390 0x185 RTD 7 Application 0 7 1 --- FC121 0 1
40391 0x186 RTD 7 Name 0 9 1 --- F22 RTD 7 9
40401 0x190 RTD 7 Alarm Temp 1 250 1 °C F4 130 1
40402 0x191 RTD 7 Trip Voting 0 12 1 --- FC122 0 1
40403 0x192 RTD 7 Trip Temp 1 250 1 °C F4 155 1
40404 0x193 RTD 8 Application 0 7 1 --- FC121 0 1
40405 0x194 RTD 8 Name 0 9 1 --- F22 RTD 8 9
40415 0x19E RTD 8 Alarm Temp 1 250 1 °C F4 130 1
40416 0x19F RTD 8 Trip Voting 0 12 1 --- FC122 0 1
40417 0x1A0 RTD 8 Trip Temp 1 250 1 °C F4 155 1
40418 0x1A1 RTD 9 Application 0 7 1 --- FC121 0 1
40419 0x1A2 RTD 9 Name 0 9 1 --- F22 RTD 9 9
40429 0x1AC RTD 9 Alarm Temp 1 250 1 °C F4 130 1
40430 0x1AD RTD 9 Trip Voting 0 12 1 --- FC122 0 1
40431 0x1AE RTD 9 Trip Temp 1 250 1 °C F4 155 1
40432 0x1AF RTD 10 Application 0 7 1 --- FC121 0 1
40433 0x1B0 RTD 10 Name 0 9 1 --- F22 RTD 10 9
40443 0x1BA RTD 10 Alarm Temp 1 250 1 °C F4 130 1
40444 0x1BB RTD 10 Trip Voting 0 12 1 --- FC122 0 1
40445 0x1BC RTD 10 Trip Temp 1 250 1 °C F4 155 1
40446 0x1BD RTD 11 Application 0 7 1 --- FC121 0 1
40447 0x1BE RTD 11 Name 0 9 1 --- F22 RTD 11 9
40457 0x1C8 RTD 11 Alarm Temp 1 250 1 °C F4 130 1
40458 0x1C9 RTD 11 Trip Voting 0 12 1 --- FC122 0 1
40459 0x1CA RTD 11 Trip Temp 1 250 1 °C F4 155 1
40460 0x1CB RTD 12 Application 0 7 1 --- FC121 0 1
40461 0x1CC RTD 12 Name 0 9 1 --- F22 RTD 12 9
40471 0x1D6 RTD 12 Alarm Temp 1 250 1 °C F4 130 1
40472 0x1D7 RTD 12 Trip Voting 0 12 1 --- FC122 0 1
40473 0x1D8 RTD 12 Trip Temp 1 250 1 °C F4 155 1
40731 0x2DA RTD Trouble Alarm 0 1 1 --- FC126 0 1
40735 0x2DE RTD 1 Application 0 7 1 --- FC121 0 1
40736 0x2DF RTD 1 Name 0 9 1 --- F22 RTD 1 9
40746 0x2E9 RTD 1 Alarm Temperature 1 250 1 °C F4 130 1
40747 0x2EA RTD 1 Trip Voting 0 12 1 --- FC122 0 1
40748 0x2EB RTD 1 Trip Temperature 1 250 1 °C F4 155 1
40749 0x2EC RTD 2 Application 0 7 1 --- FC121 0 1
40750 0x2ED RTD 2 Name 0 9 1 --- F22 RTD 2 9
40760 0x2F7 RTD 2 Alarm Temperature 1 250 1 °C F4 130 1
40761 0x2F8 RTD 2 Trip Voting 0 12 1 --- FC122 0 1
40762 0x2F9 RTD 2 Trip Temperature 1 250 1 °C F4 155 1
40763 0x2FA RTD 3 Application 0 7 1 --- FC121 0 1
40764 0x2FB RTD 3 Name 0 9 1 --- F22 RTD 3 9
40774 0x305 RTD 3 Alarm Temperature 1 250 1 °C F4 130 1

11-32 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
40775 0x306 RTD 3 Trip Voting 0 12 1 --- FC122 0 1
40776 0x307 RTD 3 Trip Temperature 1 250 1 °C F4 155 1
40777 0x308 RTD 4 Application 0 7 1 --- FC121 0 1
40778 0x309 RTD 4 Name 0 9 1 --- F22 RTD 4 9
40788 0x313 RTD 4 Alarm Temperature 1 250 1 °C F4 130 1
40789 0x314 RTD 4 Trip Voting 0 12 1 --- FC122 0 1
40790 0x315 RTD 4 Trip Temperature 1 250 1 °C F4 155 1
40791 0x316 RTD 5 Application 0 7 1 --- FC121 0 1
40792 0x317 RTD 5 Name 0 9 1 --- F22 RTD 5 9
40802 0x321 RTD 5 Alarm Temperature 1 250 1 °C F4 130 1
40803 0x322 RTD 5 Trip Voting 0 12 1 --- FC122 0 1
40804 0x323 RTD 5 Trip Temperature 1 250 1 °C F4 155 1
40805 0x324 RTD 6 Application 0 7 1 --- FC121 0 1
40806 0x325 RTD 6 Name 0 9 1 --- F22 RTD 6 9
40816 0x32F RTD 6 Alarm Temperature 1 250 1 °C F4 130 1
40817 0x330 RTD 6 Trip Voting 0 12 1 --- FC122 0 1
40818 0x331 RTD 6 Trip Temperature 1 250 1 °C F4 155 1
43560 0xDE7 RTD 1 Alarm 0 1 1 --- FC126 0 1
43561 0xDE8 RTD 1 Trip 0 1 1 --- FC126 0 1
43562 0xDE9 RTD 2 Alarm 0 1 1 --- FC126 0 1
43563 0xDEA RTD 2 Trip 0 1 1 --- FC126 0 1
43564 0xDEB RTD 3 Alarm 0 1 1 --- FC126 0 1
43565 0xDEC RTD 3 Trip 0 1 1 --- FC126 0 1
43566 0xDED RTD 4 Alarm 0 1 1 --- FC126 0 1
43567 0xDEE RTD 4 Trip 0 1 1 --- FC126 0 1
43568 0xDEF RTD 5 Alarm 0 1 1 --- FC126 0 1
43569 0xDF0 RTD 5 Trip 0 1 1 --- FC126 0 1
43570 0xDF1 RTD 6 Alarm 0 1 1 --- FC126 0 1
43571 0xDF2 RTD 6 Trip 0 1 1 --- FC126 0 1
43572 0xDF3 RTD 7 Alarm 0 1 1 --- FC126 0 1
43573 0xDF4 RTD 7 Trip 0 1 1 --- FC126 0 1
43574 0xDF5 RTD 8 Alarm 0 1 1 --- FC126 0 1
43575 0xDF6 RTD 8 Trip 0 1 1 --- FC126 0 1
43576 0xDF7 RTD 9 Alarm 0 1 1 --- FC126 0 1
43577 0xDF8 RTD 9 Trip 0 1 1 --- FC126 0 1
43578 0xDF9 RTD 10 Alarm 0 1 1 --- FC126 0 1
43579 0xDFA RTD 10 Trip 0 1 1 --- FC126 0 1
43580 0xDFB RTD 11 Alarm 0 1 1 --- FC126 0 1
43581 0xDFC RTD 11 Trip 0 1 1 --- FC126 0 1
43582 0xDFD RTD 12 Alarm 0 1 1 --- FC126 0 1
43583 0xDFE RTD 12 Trip 0 1 1 --- FC126 0 1
43586 0xE01 RTD 1 Relays 0 0x7F 1 --- FC198 0 1
43587 0xE02 RTD 2 Relays 0 0x7F 1 --- FC198 0 1
43588 0xE03 RTD 3 Relays 0 0x7F 1 --- FC198 0 1
43589 0xE04 RTD 4 Relays 0 0x7F 1 --- FC198 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-33


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
43590 0xE05 RTD 5 Relays 0 0x7F 1 --- FC198 0 1
43591 0xE06 RTD 6 Relays 0 0x7F 1 --- FC198 0 1
43592 0xE07 RTD 7 Relays 0 0x7F 1 --- FC198 0 1
43593 0xE08 RTD 8 Relays 0 0x7F 1 --- FC198 0 1
43594 0xE09 RTD 9 Relays 0 0x7F 1 --- FC198 0 1
43595 0xE0A RTD 10 Relays 0 0x7F 1 --- FC198 0 1
43596 0xE0B RTD 11 Relays 0 0x7F 1 --- FC198 0 1
43597 0xE0C RTD 12 Relays 0 0x7F 1 --- FC198 0 1
43599 0xE0E RTD 1 Block1 0 0xEF02 1 --- F89 0 1
43600 0xE0F RTD 1 Block2 0 0xEF02 1 --- F89 0 1
43601 0xE10 RTD 1 Block3 0 0xEF02 1 --- F89 0 1
43602 0xE11 RTD 2 Block1 0 0xEF02 1 --- F89 0 1
43603 0xE12 RTD 2 Block2 0 0xEF02 1 --- F89 0 1
43604 0xE13 RTD 2 Block3 0 0xEF02 1 --- F89 0 1
43605 0xE14 RTD 3 Block1 0 0xEF02 1 --- F89 0 1
43606 0xE15 RTD 3 Block2 0 0xEF02 1 --- F89 0 1
43607 0xE16 RTD 3 Block3 0 0xEF02 1 --- F89 0 1
43608 0xE17 RTD 4 Block1 0 0xEF02 1 --- F89 0 1
43609 0xE18 RTD 4 Block2 0 0xEF02 1 --- F89 0 1
43610 0xE19 RTD 4 Block3 0 0xEF02 1 --- F89 0 1
43611 0xE1A RTD 5 Block1 0 0xEF02 1 --- F89 0 1
43612 0xE1B RTD 5 Block2 0 0xEF02 1 --- F89 0 1
43613 0xE1C RTD 5 Block3 0 0xEF02 1 --- F89 0 1
43614 0xE1D RTD 6 Block1 0 0xEF02 1 --- F89 0 1
43615 0xE1E RTD 6 Block2 0 0xEF02 1 --- F89 0 1
43616 0xE1F RTD 6 Block3 0 0xEF02 1 --- F89 0 1
43617 0xE20 RTD 7 Block1 0 0xEF02 1 --- F89 0 1
43618 0xE21 RTD 7 Block2 0 0xEF02 1 --- F89 0 1
43619 0xE22 RTD 7 Block3 0 0xEF02 1 --- F89 0 1
43620 0xE23 RTD 8 Block1 0 0xEF02 1 --- F89 0 1
43621 0xE24 RTD 8 Block2 0 0xEF02 1 --- F89 0 1
43622 0xE25 RTD 8 Block3 0 0xEF02 1 --- F89 0 1
43623 0xE26 RTD 9 Block1 0 0xEF02 1 --- F89 0 1
43624 0xE27 RTD 9 Block2 0 0xEF02 1 --- F89 0 1
43625 0xE28 RTD 9 Block3 0 0xEF02 1 --- F89 0 1
43626 0xE29 RTD 10 Block1 0 0xEF02 1 --- F89 0 1
43627 0xE2A RTD 10 Block2 0 0xEF02 1 --- F89 0 1
43628 0xE2B RTD 10 Block3 0 0xEF02 1 --- F89 0 1
43629 0xE2C RTD 11 Block1 0 0xEF02 1 --- F89 0 1
43630 0xE2D RTD 11 Block2 0 0xEF02 1 --- F89 0 1
43631 0xE2E RTD 11 Block3 0 0xEF02 1 --- F89 0 1
43632 0xE2F RTD 12 Block1 0 0xEF02 1 --- F89 0 1
43633 0xE30 RTD 12 Block2 0 0xEF02 1 --- F89 0 1
43634 0xE31 RTD 12 Block3 0 0xEF02 1 --- F89 0 1
CURRENT SENSING

11-34 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
43658 0xE49 W1 SGnd CT Primary 1 600 1 A F1 50 1
43659 0xE4A W2 SGnd CT Primary 1 600 1 A F1 50 1
43660 0xE4B W1 Phase CT Primary 1 6000 1 A F1 5 1
43661 0xE4C W1 Phase CT Secondary 0 1 1 --- FC415 0 1
43662 0xE4D W2 Phase CT Primary 1 6000 1 A F1 5 1
43663 0xE4E W2 Phase CT Secondary 0 1 1 --- FC415 0 1
43664 0xE4F W1 Gnd CT Primary 1 6000 1 A F1 5 1
43665 0xE50 W1 Gnd CT Secondary 0 1 1 --- FC415 0 1
43666 0xE51 W2 Gnd CT Primary 1 6000 1 A F1 5 1
43667 0xE52 W2 Gnd CT Secondary 0 1 1 --- FC415 0 1
PROTECTION ELEMENT CT INPUTS
43670 0xE55 Phase TOC 1 CT Input 0 1 1 --- FC418 0 1
43671 0xE56 Phase TOC 2 CT Input 0 1 1 --- FC418 0 1
43672 0xE57 Phase IOC 1 CT Input 0 1 1 --- FC418 0 1
43673 0xE58 Phase IOC 2 CT Input 0 1 1 --- FC418 0 1
43674 0xE59 Ground TOC 1 CT Input 0 1 1 --- FC418 0 1
43675 0xE5A Ground TOC 2 CT Input 0 1 1 --- FC418 0 1
43676 0xE5B Ground IOC 1 CT Input 0 1 1 --- FC418 0 1
43677 0xE5C Ground IOC 2 CT Input 0 1 1 --- FC418 0 1
43678 0xE5D Neutral TOC 1 CT Input 0 1 1 --- FC418 0 1
43679 0xE5E Neutral TOC 2 CT Input 0 1 1 --- FC418 0 1
43680 0xE5F Neutral IOC 1 CT Input 0 1 1 --- FC418 0 1
43681 0xE60 Neutral IOC 2 CT Input 0 1 1 --- FC418 0 1
43682 0xE61 Negative Sequence TOC 1 0 1 1 --- FC418 0 1
CT Input
43683 0xE62 Negative Sequence TOC 2 0 1 1 --- FC418 0 1
CT Input
43685 0xE64 Sensitive Ground TOC 1 CT 0 1 1 --- FC418 0 1
Input
43686 0xE65 Sensitive Ground TOC 2 CT 0 1 1 --- FC418 0 1
Input
43687 0xE66 Sensitive Ground IOC 1 CT 0 1 1 --- FC418 0 1
Input
43688 0xE67 Sensitive Ground IOC 2 CT 0 1 1 --- FC418 0 1
Input
43689 0xE68 Negative Sequence IOC 1 CT 0 1 1 --- FC418 0 1
Input
43690 0xE69 Negative Sequence IOC 2 CT 0 1 1 --- FC418 0 1
Input
NEGATIVE SEQUENCE TOC1
43691 0xE6A Neg Seq TOC1 Func 0 3 1 --- FC197 0 1
43692 0xE6B Neg Seq TOC1 PkP 5 2000 1 x CT F3 100 1
43693 0xE6C Neg Seq TOC1 Curve 0 14 1 --- F36 0 1
43694 0xE6D Neg Seq TOC1 TDM 5 5000 1 --- F3 100 1
43695 0xE6E Neg Seg TOC1 Reset 0 1 1 --- F68 0 1
43696 0xE6F Neg Seq TOC1 Relays 0 0x7F 1 --- FC198 0 1
NEGATIVE SEQUENCE TOC2
43697 0xE70 Neg Seq TOC2 Func 0 3 1 --- FC197 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-35


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
43698 0xE71 Neg Seq TOC2 PkP 5 2000 1 x CT F3 100 1
43699 0xE72 Neg Seq TOC2 Curve 0 14 1 --- F36 0 1
43700 0xE73 Neg Seq TOC2 TDM 5 5000 1 --- F3 100 1
43701 0xE74 Neg Seg TOC2 Reset 0 1 1 --- F68 0 1
43702 0xE75 Neg Seq TOC2 Relays 0 0x7F 1 --- FC198 0 1
W2 BREAKER FAIL
43712 0xE7F Breaker Failure 2 Function 0 2 1 --- FC206 0 1
43713 0xE80 Breaker Failure 2 Delay 1 3 100 1 s F3 10 1
43714 0xE81 Breaker Failure 2 Current 5 2000 1 x CT F3 100 1
(W2)
43715 0xE82 Breaker Failure 2 Delay 2 0 100 1 s F3 0 1
43716 0xE83 Breaker Failure 2 Relays 0 0x7F 1 --- FC198 0 1
43717 0xE84 BF 2 EXT INITIATE 0 0xEF02 1 --- F89 0 1
SENSITIVE GROUND TOC2
43727 0xE8E Sensitive Ground Time OC 2 0 3 1 --- FC197 0 1
Function
43728 0xE8F Sensitive Ground Time OC 2 5 3000 1 x CT F17A 1000 1
Pickup
43729 0xE90 Sensitive Ground Time OC 2 0 14 1 --- F36 0 1
Reset
43730 0xE91 Sensitive Ground Time OC 2 5 5000 1 --- F3 100 1
Multiplier
43731 0xE92 Sensitive Ground Time OC 2 0 1 1 --- F68 0 1
Reset
FORCE VIRTUAL INPUTS
43764 0xEB3 Force Virtual Input 1 0 1 1 --- FC103 0 1
43765 0xEB4 Force Virtual Input 2 0 1 1 --- FC103 0 1
43766 0xEB5 Force Virtual Input 3 0 1 1 --- FC103 0 1
43767 0xEB6 Force Virtual Input 4 0 1 1 --- FC103 0 1
43768 0xEB7 Force Virtual Input 5 0 1 1 --- FC103 0 1
43769 0xEB8 Force Virtual Input 6 0 1 1 --- FC103 0 1
43770 0xEB9 Force Virtual Input 7 0 1 1 --- FC103 0 1
43771 0xEBA Force Virtual Input 8 0 1 1 --- FC103 0 1
43772 0xEBB Force Virtual Input 9 0 1 1 --- FC103 0 1
43773 0xEBC Force Virtual Input 10 0 1 1 --- FC103 0 1
43774 0xEBD Force Virtual Input 11 0 1 1 --- FC103 0 1
43775 0xEBE Force Virtual Input 12 0 1 1 --- FC103 0 1
43776 0xEBF Force Virtual Input 13 0 1 1 --- FC103 0 1
43777 0xEC0 Force Virtual Input 14 0 1 1 --- FC103 0 1
43778 0xEC1 Force Virtual Input 15 0 1 1 --- FC103 0 1
43779 0xEC2 Force Virtual Input 16 0 1 1 --- FC103 0 1
43780 0xEC3 Force Virtual Input 17 0 1 1 --- FC103 0 1
43781 0xEC4 Force Virtual Input 18 0 1 1 --- FC103 0 1
43782 0xEC5 Force Virtual Input 19 0 1 1 --- FC103 0 1
43783 0xEC6 Force Virtual Input 20 0 1 1 --- FC103 0 1
43784 0xEC7 Force Virtual Input 21 0 1 1 --- FC103 0 1
43785 0xEC8 Force Virtual Input 22 0 1 1 --- FC103 0 1

11-36 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
43786 0xEC9 Force Virtual Input 23 0 1 1 --- FC103 0 1
43787 0xECA Force Virtual Input 24 0 1 1 --- FC103 0 1
43788 0xECB Force Virtual Input 25 0 1 1 --- FC103 0 1
43789 0xECC Force Virtual Input 26 0 1 1 --- FC103 0 1
43790 0xECD Force Virtual Input 27 0 1 1 --- FC103 0 1
43791 0xECE Force Virtual Input 28 0 1 1 --- FC103 0 1
43792 0xECF Force Virtual Input 29 0 1 1 --- FC103 0 1
43793 0xED0 Force Virtual Input 30 0 1 1 --- FC103 0 1
43794 0xED1 Force Virtual Input 31 0 1 1 --- FC103 0 1
43795 0xED2 Force Virtual Input 32 0 1 1 --- FC103 0 1
DNP OVER ETHERNET PORT
43836 0xEFB DNP/Ethernet Channel 1 0 2 1 --- F87 0 1
Port
43837 0xEFC DNP/Ethernet Channel 2 0 2 1 --- F87 0 1
Port
IEC60870-5-104 PROTOCOL
43838 0xEFD IEC 60870-5-104 Function 0 1 1 --- FC126 0 1
43839 0xEFE IEC TCP Port 1 65535 1 --- F1 2404 1
43840 0xEFF IEC Common Address of 0 65535 1 --- F1 0 1
ASDU
43841 0xF00 IEC Cyclic Data Period 0 65535 1 s F1 60 1
43842 0xF01 IEC TCP Connection Timeout 10 300 1 s F1 120 1
43843 0xF02 Object Information Address 1 16777215 1 --- F9 1000 2
Binary
43845 0xF04 Object Information Address 1 16777215 1 --- F9 2000 2
Analog
43847 0xF06 Object Information Address 1 16777215 1 --- F9 3000 2
Counters
43849 0xF08 Object Information Address 1 16777215 1 --- F9 4000 2
Command
DNP / IEC60870-5-104 SHARED SETTINGS
43851 0xF0A DNP Address 0 65519 1 --- F1 0 1
43852 0xF0B DNP Client Address 1 0 0xFFFFFFFF 1 --- FC150 0 2
43854 0xF0D DNP Client Address 2 0 0xFFFFFFFF 1 --- FC150 0 2
43856 0xF0F DNP Client Address 3 0 0xFFFFFFFF 1 --- FC150 0 2
43858 0xF11 DNP Client Address 4 0 0xFFFFFFFF 1 --- FC150 0 2
43860 0xF13 DNP Client Address 5 0 0xFFFFFFFF 1 --- FC150 0 2
43862 0xF15 DNP TCP/UDP Port Number 0 65535 1 --- F1 20000 1
43863 0xF16 DNP Unsolicited Response 0 1 1 --- FC126 0 1
Function
43864 0xF17 DNP Unsolicited Response 0 60 1 s F1 5 1
Timeout
43865 0xF18 DNP Unsolicited Response 1 255 1 --- F1 10 1
Maximum Retries
43866 0xF19 DNP Unsolicited Response 0 65519 1 --- F1 1 1
Destination Address
43867 0xF1A DNP Time Sync IIN Period 1 10080 1 min F1 1440 1
43868 0xF1B DNP Message Fragment Size 30 2048 1 --- F1 240 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-37


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
43869 0xF1C DNP Object 1 Default 1 2 1 --- F1 2 1
Variation
43870 0xF1D DNP Object 2 Default 1 2 1 --- F1 2 1
Variation
43871 0xF1E DNP Object 20 Default 1 6 1 --- F78 1 1
Variation
43872 0xF1F DNP Object 21 Default 1 10 1 --- F79 1 1
Variation
43873 0xF20 DNP Object 22 Default 1 6 1 --- F80 1 1
Variation
43874 0xF21 DNP Object 23 Default 1 6 1 --- F81 1 1
Variation
43875 0xF22 DNP Object 30 Default 1 4 1 --- F82 1 1
Variation
43876 0xF23 DNP Object 32 Default 1 4 1 --- F83 1 1
Variation
43877 0xF24 DNP TCP Connection 10 300 1 s F1 120 1
Timeout
DNP / IEC60870-5-103 / IEC60870-5-104 BINARY INPUTS
43878 0xF25 Binary Input Point 0 Entry 0 0xFFFF 1 --- FC134B 0 1
43879 0xF26 Binary Input Point 1 Entry 0 0xFFFF 1 --- FC134B 0 1
43880 0xF27 Binary Input Point 2 Entry 0 0xFFFF 1 --- FC134B 0 1
43881 0xF28 Binary Input Point 3 Entry 0 0xFFFF 1 --- FC134B 0 1
43882 0xF29 Binary Input Point 4 Entry 0 0xFFFF 1 --- FC134B 0 1
43883 0xF2A Binary Input Point 5 Entry 0 0xFFFF 1 --- FC134B 0 1
43884 0xF2B Binary Input Point 6 Entry 0 0xFFFF 1 --- FC134B 0 1
43885 0xF2C Binary Input Point 7 Entry 0 0xFFFF 1 --- FC134B 0 1
43886 0xF2D Binary Input Point 8 Entry 0 0xFFFF 1 --- FC134B 0 1
43887 0xF2E Binary Input Point 9 Entry 0 0xFFFF 1 --- FC134B 0 1
43888 0xF2F Binary Input Point 10 Entry 0 0xFFFF 1 --- FC134B 0 1
43889 0xF30 Binary Input Point 11 Entry 0 0xFFFF 1 --- FC134B 0 1
43890 0xF31 Binary Input Point 12 Entry 0 0xFFFF 1 --- FC134B 0 1
43891 0xF32 Binary Input Point 13 Entry 0 0xFFFF 1 --- FC134B 0 1
43892 0xF33 Binary Input Point 14 Entry 0 0xFFFF 1 --- FC134B 0 1
43893 0xF34 Binary Input Point 15 Entry 0 0xFFFF 1 --- FC134B 0 1
43894 0xF35 Binary Input Point 16 Entry 0 0xFFFF 1 --- FC134B 0 1
43895 0xF36 Binary Input Point 17 Entry 0 0xFFFF 1 --- FC134B 0 1
43896 0xF37 Binary Input Point 18 Entry 0 0xFFFF 1 --- FC134B 0 1
43897 0xF38 Binary Input Point 19 Entry 0 0xFFFF 1 --- FC134B 0 1
43898 0xF39 Binary Input Point 20 Entry 0 0xFFFF 1 --- FC134B 0 1
43899 0xF3A Binary Input Point 21 Entry 0 0xFFFF 1 --- FC134B 0 1
43900 0xF3B Binary Input Point 22 Entry 0 0xFFFF 1 --- FC134B 0 1
43901 0xF3C Binary Input Point 23 Entry 0 0xFFFF 1 --- FC134B 0 1
43902 0xF3D Binary Input Point 24 Entry 0 0xFFFF 1 --- FC134B 0 1
43903 0xF3E Binary Input Point 25 Entry 0 0xFFFF 1 --- FC134B 0 1
43904 0xF3F Binary Input Point 26 Entry 0 0xFFFF 1 --- FC134B 0 1
43905 0xF40 Binary Input Point 27 Entry 0 0xFFFF 1 --- FC134B 0 1
43906 0xF41 Binary Input Point 28 Entry 0 0xFFFF 1 --- FC134B 0 1

11-38 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
43907 0xF42 Binary Input Point 29 Entry 0 0xFFFF 1 --- FC134B 0 1
43908 0xF43 Binary Input Point 30 Entry 0 0xFFFF 1 --- FC134B 0 1
43909 0xF44 Binary Input Point 31 Entry 0 0xFFFF 1 --- FC134B 0 1
43910 0xF45 Binary Input Point 32 Entry 0 0xFFFF 1 --- FC134B 0 1
43911 0xF46 Binary Input Point 33 Entry 0 0xFFFF 1 --- FC134B 0 1
43912 0xF47 Binary Input Point 34 Entry 0 0xFFFF 1 --- FC134B 0 1
43913 0xF48 Binary Input Point 35 Entry 0 0xFFFF 1 --- FC134B 0 1
43914 0xF49 Binary Input Point 36 Entry 0 0xFFFF 1 --- FC134B 0 1
43915 0xF4A Binary Input Point 37 Entry 0 0xFFFF 1 --- FC134B 0 1
43916 0xF4B Binary Input Point 38 Entry 0 0xFFFF 1 --- FC134B 0 1
43917 0xF4C Binary Input Point 39 Entry 0 0xFFFF 1 --- FC134B 0 1
43918 0xF4D Binary Input Point 40 Entry 0 0xFFFF 1 --- FC134B 0 1
43919 0xF4E Binary Input Point 41 Entry 0 0xFFFF 1 --- FC134B 0 1
43920 0xF4F Binary Input Point 42 Entry 0 0xFFFF 1 --- FC134B 0 1
43921 0xF50 Binary Input Point 43 Entry 0 0xFFFF 1 --- FC134B 0 1
43922 0xF51 Binary Input Point 44 Entry 0 0xFFFF 1 --- FC134B 0 1
43923 0xF52 Binary Input Point 45 Entry 0 0xFFFF 1 --- FC134B 0 1
43924 0xF53 Binary Input Point 46 Entry 0 0xFFFF 1 --- FC134B 0 1
43925 0xF54 Binary Input Point 47 Entry 0 0xFFFF 1 --- FC134B 0 1
43926 0xF55 Binary Input Point 48 Entry 0 0xFFFF 1 --- FC134B 0 1
43927 0xF56 Binary Input Point 49 Entry 0 0xFFFF 1 --- FC134B 0 1
43928 0xF57 Binary Input Point 50 Entry 0 0xFFFF 1 --- FC134B 0 1
43929 0xF58 Binary Input Point 51 Entry 0 0xFFFF 1 --- FC134B 0 1
43930 0xF59 Binary Input Point 52 Entry 0 0xFFFF 1 --- FC134B 0 1
43931 0xF5A Binary Input Point 53 Entry 0 0xFFFF 1 --- FC134B 0 1
43932 0xF5B Binary Input Point 54 Entry 0 0xFFFF 1 --- FC134B 0 1
43933 0xF5C Binary Input Point 55 Entry 0 0xFFFF 1 --- FC134B 0 1
43934 0xF5D Binary Input Point 56 Entry 0 0xFFFF 1 --- FC134B 0 1
43935 0xF5E Binary Input Point 57 Entry 0 0xFFFF 1 --- FC134B 0 1
43936 0xF5F Binary Input Point 58 Entry 0 0xFFFF 1 --- FC134B 0 1
43937 0xF60 Binary Input Point 59 Entry 0 0xFFFF 1 --- FC134B 0 1
43938 0xF61 Binary Input Point 60 Entry 0 0xFFFF 1 --- FC134B 0 1
43939 0xF62 Binary Input Point 61 Entry 0 0xFFFF 1 --- FC134B 0 1
43940 0xF63 Binary Input Point 62 Entry 0 0xFFFF 1 --- FC134B 0 1
43941 0xF64 Binary Input Point 63 Entry 0 0xFFFF 1 --- FC134B 0 1
DNP / IEC60870-5-104 BINARY OUTPUTS
44070 0xFE5 Binary Output Point 0 ON 0 40 1 --- F86 0 1
44071 0xFE6 Binary Output Point 0 OFF 0 40 1 --- F86 0 1
44072 0xFE7 Binary Output Point 1 ON 0 40 1 --- F86 0 1
44073 0xFE8 Binary Output Point 1 OFF 0 40 1 --- F86 0 1
44074 0xFE9 Binary Output Point 2 ON 0 40 1 --- F86 0 1
44075 0xFEA Binary Output Point 2 OFF 0 40 1 --- F86 0 1
44076 0xFEB Binary Output Point 3 ON 0 40 1 --- F86 0 1
44077 0xFEC Binary Output Point 3 OFF 0 40 1 --- F86 0 1
44078 0xFED Binary Output Point 4 ON 0 40 1 --- F86 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-39


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44079 0xFEE Binary Output Point 4 OFF 0 40 1 --- F86 0 1
44080 0xFEF Binary Output Point 5 ON 0 40 1 --- F86 0 1
44081 0xFF0 Binary Output Point 5 OFF 0 40 1 --- F86 0 1
44082 0xFF1 Binary Output Point 6 ON 0 40 1 --- F86 0 1
44083 0xFF2 Binary Output Point 6 OFF 0 40 1 --- F86 0 1
44084 0xFF3 Binary Output Point 7 ON 0 40 1 --- F86 0 1
44085 0xFF4 Binary Output Point 7 OFF 0 40 1 --- F86 0 1
44086 0xFF5 Binary Output Point 8 ON 0 40 1 --- F86 0 1
44087 0xFF6 Binary Output Point 8 OFF 0 40 1 --- F86 0 1
44088 0xFF7 Binary Output Point 9 ON 0 40 1 --- F86 0 1
44089 0xFF8 Binary Output Point 9 OFF 0 40 1 --- F86 0 1
44090 0xFF9 Binary Output Point 10 ON 0 40 1 --- F86 0 1
44091 0xFFA Binary Output Point 10 OFF 0 40 1 --- F86 0 1
44092 0xFFB Binary Output Point 11 ON 0 40 1 --- F86 0 1
44093 0xFFC Binary Output Point 11 OFF 0 40 1 --- F86 0 1
44094 0xFFD Binary Output Point 12 ON 0 40 1 --- F86 0 1
44095 0xFFE Binary Output Point 12 OFF 0 40 1 --- F86 0 1
44096 0xFFF Binary Output Point 13 ON 0 40 1 --- F86 0 1
44097 0x1000 Binary Output Point 13 OFF 0 40 1 --- F86 0 1
44098 0x1001 Binary Output Point 14 ON 0 40 1 --- F86 0 1
44099 0x1002 Binary Output Point 14 OFF 0 40 1 --- F86 0 1
44100 0x1003 Binary Output Point 15 ON 0 40 1 --- F86 0 1
44101 0x1004 Binary Output Point 15 OFF 0 40 1 --- F86 0 1
DNP / IEC60870-5-104 ANALOG INPUTS
43942 0xF65 Analog Input Point 0 Entry 0 251 1 --- F88 0 1
43943 0xF66 Analog Input Point 0 Scale 1 9 1 --- F85 4 1
Factor
43944 0xF67 Analog Input Point 0 0 100000000 1 --- F9 30000 2
Deadband
43946 0xF69 Analog Input Point 1 Entry 0 251 1 --- F88 0 1
43947 0xF6A Analog Input Point 1 Scale 1 9 1 --- F85 4 1
Factor
43948 0xF6B Analog Input Point 1 0 100000000 1 --- F9 30000 2
Deadband
43950 0xF6D Analog Input Point 2 Entry 0 251 1 --- F88 0 1
43951 0xF6E Analog Input Point 2 Scale 1 9 1 --- F85 4 1
Factor
43952 0xF6F Analog Input Point 2 0 100000000 1 --- F9 30000 2
Deadband
43954 0xF71 Analog Input Point 3 Entry 0 251 1 --- F88 0 1
43955 0xF72 Analog Input Point 3 Scale 1 9 1 --- F85 4 1
Factor
43956 0xF73 Analog Input Point 3 0 100000000 1 --- F9 30000 2
Deadband
43958 0xF75 Analog Input Point 4 Entry 0 251 1 --- F88 0 1
43959 0xF76 Analog Input Point 4 Scale 1 9 1 --- F85 4 1
Factor
43960 0xF77 Analog Input Point 4 0 100000000 1 --- F9 30000 2
Deadband

11-40 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
43962 0xF79 Analog Input Point 5 Entry 0 251 1 --- F88 0 1
43963 0xF7A Analog Input Point 5 Scale 1 9 1 --- F85 4 1
Factor
43964 0xF7B Analog Input Point 5 0 100000000 1 --- F9 30000 2
Deadband
43966 0xF7D Analog Input Point 6 Entry 0 251 1 --- F88 0 1
43967 0xF7E Analog Input Point 6 Scale 1 9 1 --- F85 4 1
Factor
43968 0xF7F Analog Input Point 6 0 100000000 1 --- F9 30000 2
Deadband
43970 0xF81 Analog Input Point 7 Entry 0 251 1 --- F88 0 1
43971 0xF82 Analog Input Point 7 Scale 1 9 1 --- F85 4 1
Factor
43972 0xF83 Analog Input Point 7 0 100000000 1 --- F9 30000 2
Deadband
43974 0xF85 Analog Input Point 8 Entry 0 251 1 --- F88 0 1
43975 0xF86 Analog Input Point 8 Scale 1 9 1 --- F85 4 1
Factor
43976 0xF87 Analog Input Point 8 0 100000000 1 --- F9 30000 2
Deadband
43978 0xF89 Analog Input Point 9 Entry 0 251 1 --- F88 0 1
43979 0xF8A Analog Input Point 9 Scale 1 9 1 --- F85 4 1
Factor
43980 0xF8B Analog Input Point 9 0 100000000 1 --- F9 30000 2
Deadband
43982 0xF8D Analog Input Point 10 Entry 0 251 1 --- F88 0 1
43983 0xF8E Analog Input Point 10 Scale 1 9 1 --- F85 4 1
Factor
43984 0xF8F Analog Input Point 10 0 100000000 1 --- F9 30000 2
Deadband
43986 0xF91 Analog Input Point 11 Entry 0 251 1 --- F88 0 1
43987 0xF92 Analog Input Point 11 Scale 1 9 1 --- F85 4 1
Factor
43988 0xF93 Analog Input Point 11 0 100000000 1 --- F9 30000 2
Deadband
43990 0xF95 Analog Input Point 12 Entry 0 251 1 --- F88 0 1
43991 0xF96 Analog Input Point 12 Scale 1 9 1 --- F85 4 1
Factor
43992 0xF97 Analog Input Point 12 0 100000000 1 --- F9 30000 2
Deadband
43994 0xF99 Analog Input Point 13 Entry 0 251 1 --- F88 0 1
43995 0xF9A Analog Input Point 13 Scale 1 9 1 --- F85 4 1
Factor
43996 0xF9B Analog Input Point 13 0 100000000 1 --- F9 30000 2
Deadband
43998 0xF9D Analog Input Point 14 Entry 0 251 1 --- F88 0 1
43999 0xF9E Analog Input Point 14 Scale 1 9 1 --- F85 4 1
Factor
44000 0xF9F Analog Input Point 14 0 100000000 1 --- F9 30000 2
Deadband
44002 0xFA1 Analog Input Point 15 Entry 0 251 1 --- F88 0 1
44003 0xFA2 Analog Input Point 15 Scale 1 9 1 --- F85 4 1
Factor

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-41


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44004 0xFA3 Analog Input Point 15 0 100000000 1 --- F9 30000 2
Deadband
44006 0xFA5 Analog Input Point 16 Entry 0 251 1 --- F88 0 1
44007 0xFA6 Analog Input Point 16 Scale 1 9 1 --- F85 4 1
Factor
44008 0xFA7 Analog Input Point 16 0 100000000 1 --- F9 30000 2
Deadband
44010 0xFA9 Analog Input Point 17 Entry 0 251 1 --- F88 0 1
44011 0xFAA Analog Input Point 17 Scale 1 9 1 --- F85 4 1
Factor
44012 0xFAB Analog Input Point 17 0 100000000 1 --- F9 30000 2
Deadband
44014 0xFAD Analog Input Point 18 Entry 0 251 1 --- F88 0 1
44015 0xFAE Analog Input Point 18 Scale 1 9 1 --- F85 4 1
Factor
44016 0xFAF Analog Input Point 18 0 100000000 1 --- F9 30000 2
Deadband
44018 0xFB1 Analog Input Point 19 Entry 0 251 1 --- F88 0 1
44019 0xFB2 Analog Input Point 19 Scale 1 9 1 --- F85 4 1
Factor
44020 0xFB3 Analog Input Point 19 0 100000000 1 --- F9 30000 2
Deadband
44022 0xFB5 Analog Input Point 20 Entry 0 251 1 --- F88 0 1
44023 0xFB6 Analog Input Point 20 Scale 1 9 1 --- F85 4 1
Factor
44024 0xFB7 Analog Input Point 20 0 100000000 1 --- F9 30000 2
Deadband
44026 0xFB9 Analog Input Point 21 Entry 0 251 1 --- F88 0 1
44027 0xFBA Analog Input Point 21 Scale 1 9 1 --- F85 4 1
Factor
44028 0xFBB Analog Input Point 21 0 100000000 1 --- F9 30000 2
Deadband
44030 0xFBD Analog Input Point 22 Entry 0 251 1 --- F88 0 1
44031 0xFBE Analog Input Point 22 Scale 1 9 1 --- F85 4 1
Factor
44032 0xFBF Analog Input Point 22 0 100000000 1 --- F9 30000 2
Deadband
44034 0xFC1 Analog Input Point 23 Entry 0 251 1 --- F88 0 1
44035 0xFC2 Analog Input Point 23 Scale 1 9 1 --- F85 4 1
Factor
44036 0xFC3 Analog Input Point 23 0 100000000 1 --- F9 30000 2
Deadband
44038 0xFC5 Analog Input Point 24 Entry 0 251 1 --- F88 0 1
44039 0xFC6 Analog Input Point 24 Scale 1 9 1 --- F85 4 1
Factor
44040 0xFC7 Analog Input Point 24 0 100000000 1 --- F9 30000 2
Deadband
44042 0xFC9 Analog Input Point 25 Entry 0 251 1 --- F88 0 1
44043 0xFCA Analog Input Point 25 Scale 1 9 1 --- F85 4 1
Factor
44044 0xFCB Analog Input Point 25 0 100000000 1 --- F9 30000 2
Deadband
44046 0xFCD Analog Input Point 26 Entry 0 251 1 --- F88 0 1

11-42 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44047 0xFCE Analog Input Point 26 Scale 1 9 1 --- F85 4 1
Factor
44048 0xFCF Analog Input Point 26 0 100000000 1 --- F9 30000 2
Deadband
44050 0xFD1 Analog Input Point 27 Entry 0 251 1 --- F88 0 1
44051 0xFD2 Analog Input Point 27 Scale 1 9 1 --- F85 4 1
Factor
44052 0xFD3 Analog Input Point 27 0 100000000 1 --- F9 30000 2
Deadband
44054 0xFD5 Analog Input Point 28 Entry 0 251 1 --- F88 0 1
44055 0xFD6 Analog Input Point 28 Scale 1 9 1 --- F85 4 1
Factor
44056 0xFD7 Analog Input Point 28 0 100000000 1 --- F9 30000 2
Deadband
44058 0xFD9 Analog Input Point 29 Entry 0 251 1 --- F88 0 1
44059 0xFDA Analog Input Point 29 Scale 1 9 1 --- F85 4 1
Factor
44060 0xFDB Analog Input Point 29 0 100000000 1 --- F9 30000 2
Deadband
44062 0xFDD Analog Input Point 30 Entry 0 251 1 --- F88 0 1
44063 0xFDE Analog Input Point 30 Scale 1 9 1 --- F85 4 1
Factor
44064 0xFDF Analog Input Point 30 0 100000000 1 --- F9 30000 2
Deadband
44066 0xFE1 Analog Input Point 31 Entry 0 251 1 --- F88 0 1
44067 0xFE2 Analog Input Point 31 Scale 1 9 1 --- F85 4 1
Factor
44068 0xFE3 Analog Input Point 31 0 100000000 1 --- F9 30000 2
Deadband
44102 0x1005 Fault Report Mapping 0 1 1 --- FC126 0 1
Enable
AUTORECLOSE
44137 0x1028 Negative Sequence TOC 0 1 1 --- FC103 0 1
Initiate
THERMAL MODEL
44211 0x1072 Thermal Overload Function 0 3 1 --- FC197 0 1
44212 0x1073 Heat Time Constant 30 6000 1 min F2 60 1
44213 0x1074 Cool Time Constant 100 600 1 --- F3 200 1
44214 0x1075 Pickup Level 5 2000 1 x CT F3 100 1
44215 0x1076 Alarm Level 700 1100 1 % F2 800 1
44216 0x1077 Output Relays 3-7 0 0x7F 1 --- FC198 0 1
IEC60870-5-103 BINARY INPUT POINTS
44221 0x107C Binary In Point 0 Entry 0 255 1 --- F1 0 1
Function Type
44222 0x107D Binary In Point 0 Entry 0 255 1 --- F1 0 1
Information Number
44223 0x107E Binary In Point 1 Entry 0 255 1 --- F1 0 1
Function Type
44224 0x107F Binary In Point 1 Entry 0 255 1 --- F1 0 1
Information Number
44225 0x1080 Binary In Point 2 Entry 0 255 1 --- F1 0 1
Function Type

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-43


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44226 0x1081 Binary In Point 2 Entry 0 255 1 --- F1 0 1
Information Number
44227 0x1082 Binary In Point 3 Entry 0 255 1 --- F1 0 1
Function Type
44228 0x1083 Binary In Point 3 Entry 0 255 1 --- F1 0 1
Information Number
44229 0x1084 Binary In Point 4 Entry 0 255 1 --- F1 0 1
Function Type
44230 0x1085 Binary In Point 4 Entry 0 255 1 --- F1 0 1
Information Number
44231 0x1086 Binary In Point 5 Entry 0 255 1 --- F1 0 1
Function Type
44232 0x1087 Binary In Point 5 Entry 0 255 1 --- F1 0 1
Information Number
44233 0x1088 Binary In Point 6 Entry 0 255 1 --- F1 0 1
Function Type
44234 0x1089 Binary In Point 6 Entry 0 255 1 --- F1 0 1
Information Number
44235 0x108A Binary In Point 7 Entry 0 255 1 --- F1 0 1
Function Type
44236 0x108B Binary In Point 7 Entry 0 255 1 --- F1 0 1
Information Number
44237 0x108C Binary In Point 8 Entry 0 255 1 --- F1 0 1
Function Type
44238 0x108D Binary In Point 8 Entry 0 255 1 --- F1 0 1
Information Number
44239 0x108E Binary In Point 9 Entry 0 255 1 --- F1 0 1
Function Type
44240 0x108F Binary In Point 9 Entry 0 255 1 --- F1 0 1
Information Number
44241 0x1090 Binary In Point 10 Entry 0 255 1 --- F1 0 1
Function Type
44242 0x1091 Binary In Point 10 Entry 0 255 1 --- F1 0 1
Information Number
44243 0x1092 Binary In Point 11 Entry 0 255 1 --- F1 0 1
Function Type
44244 0x1093 Binary In Point 11 Entry 0 255 1 --- F1 0 1
Information Number
44245 0x1094 Binary In Point 12 Entry 0 255 1 --- F1 0 1
Function Type
44246 0x1095 Binary In Point 12 Entry 0 255 1 --- F1 0 1
Information Number
44247 0x1096 Binary In Point 13 Entry 0 255 1 --- F1 0 1
Function Type
44248 0x1097 Binary In Point 13 Entry 0 255 1 --- F1 0 1
Information Number
44249 0x1098 Binary In Point 14 Entry 0 255 1 --- F1 0 1
Function Type
44250 0x1099 Binary In Point 14 Entry 0 255 1 --- F1 0 1
Information Number
44251 0x109A Binary In Point 15 Entry 0 255 1 --- F1 0 1
Function Type
44252 0x109B Binary In Point 15 Entry 0 255 1 --- F1 0 1
Information Number

11-44 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44253 0x109C Binary In Point 16 Entry 0 255 1 --- F1 0 1
Function Type
44254 0x109D Binary In Point 16 Entry 0 255 1 --- F1 0 1
Information Number
44255 0x109E Binary In Point 17 Entry 0 255 1 --- F1 0 1
Function Type
44256 0x109F Binary In Point 17 Entry 0 255 1 --- F1 0 1
Information Number
44257 0x10A0 Binary In Point 18 Entry 0 255 1 --- F1 0 1
Function Type
44258 0x10A1 Binary In Point 18 Entry 0 255 1 --- F1 0 1
Information Number
44259 0x10A2 Binary In Point 19 Entry 0 255 1 --- F1 0 1
Function Type
44260 0x10A3 Binary In Point 19 Entry 0 255 1 --- F1 0 1
Information Number
44261 0x10A4 Binary In Point 20 Entry 0 255 1 --- F1 0 1
Function Type
44262 0x10A5 Binary In Point 20 Entry 0 255 1 --- F1 0 1
Information Number
44263 0x10A6 Binary In Point 21 Entry 0 255 1 --- F1 0 1
Function Type
44264 0x10A7 Binary In Point 21 Entry 0 255 1 --- F1 0 1
Information Number
44265 0x10A8 Binary In Point 22 Entry 0 255 1 --- F1 0 1
Function Type
44266 0x10A9 Binary In Point 22 Entry 0 255 1 --- F1 0 1
Information Number
44267 0x10AA Binary In Point 23 Entry 0 255 1 --- F1 0 1
Function Type
44268 0x10AB Binary In Point 23 Entry 0 255 1 --- F1 0 1
Information Number
44269 0x10AC Binary In Point 24 Entry 0 255 1 --- F1 0 1
Function Type
44270 0x10AD Binary In Point 24 Entry 0 255 1 --- F1 0 1
Information Number
44271 0x10AE Binary In Point 25 Entry 0 255 1 --- F1 0 1
Function Type
44272 0x10AF Binary In Point 25 Entry 0 255 1 --- F1 0 1
Information Number
44273 0x10B0 Binary In Point 26 Entry 0 255 1 --- F1 0 1
Function Type
44274 0x10B1 Binary In Point 26 Entry 0 255 1 --- F1 0 1
Information Number
44275 0x10B2 Binary In Point 27 Entry 0 255 1 --- F1 0 1
Function Type
44276 0x10B3 Binary In Point 27 Entry 0 255 1 --- F1 0 1
Information Number
44277 0x10B4 Binary In Point 28 Entry 0 255 1 --- F1 0 1
Function Type
44278 0x10B5 Binary In Point 28 Entry 0 255 1 --- F1 0 1
Information Number
44279 0x10B6 Binary In Point 29 Entry 0 255 1 --- F1 0 1
Function Type

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-45


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44280 0x10B7 Binary In Point 29 Entry 0 255 1 --- F1 0 1
Information Number
44281 0x10B8 Binary In Point 30 Entry 0 255 1 --- F1 0 1
Function Type
44282 0x10B9 Binary In Point 30 Entry 0 255 1 --- F1 0 1
Information Number
44283 0x10BA Binary In Point 31 Entry 0 255 1 --- F1 0 1
Function Type
44284 0x10BB Binary In Point 31 Entry 0 255 1 --- F1 0 1
Information Number
44285 0x10BC Binary In Point 32 Entry 0 255 1 --- F1 0 1
Function Type
44286 0x10BD Binary In Point 32 Entry 0 255 1 --- F1 0 1
Information Number
44287 0x10BE Binary In Point 33 Entry 0 255 1 --- F1 0 1
Function Type
44288 0x10BF Binary In Point 33 Entry 0 255 1 --- F1 0 1
Information Number
44289 0x10C0 Binary In Point 34 Entry 0 255 1 --- F1 0 1
Function Type
44290 0x10C1 Binary In Point 34 Entry 0 255 1 --- F1 0 1
Information Number
44291 0x10C2 Binary In Point 35 Entry 0 255 1 --- F1 0 1
Function Type
44292 0x10C3 Binary In Point 35 Entry 0 255 1 --- F1 0 1
Information Number
44293 0x10C4 Binary In Point 36 Entry 0 255 1 --- F1 0 1
Function Type
44294 0x10C5 Binary In Point 36 Entry 0 255 1 --- F1 0 1
Information Number
44295 0x10C6 Binary In Point 37 Entry 0 255 1 --- F1 0 1
Function Type
44296 0x10C7 Binary In Point 37 Entry 0 255 1 --- F1 0 1
Information Number
44297 0x10C8 Binary In Point 38 Entry 0 255 1 --- F1 0 1
Function Type
44298 0x10C9 Binary In Point 38 Entry 0 255 1 --- F1 0 1
Information Number
44299 0x10CA Binary In Point 39 Entry 0 255 1 --- F1 0 1
Function Type
44300 0x10CB Binary In Point 39 Entry 0 255 1 --- F1 0 1
Information Number
44301 0x10CC Binary In Point 40 Entry 0 255 1 --- F1 0 1
Function Type
44302 0x10CD Binary In Point 40 Entry 0 255 1 --- F1 0 1
Information Number
44303 0x10CE Binary In Point 41 Entry 0 255 1 --- F1 0 1
Function Type
44304 0x10CF Binary In Point 41 Entry 0 255 1 --- F1 0 1
Information Number
44305 0x10D0 Binary In Point 42 Entry 0 255 1 --- F1 0 1
Function Type
44306 0x10D1 Binary In Point 42 Entry 0 255 1 --- F1 0 1
Information Number

11-46 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44307 0x10D2 Binary In Point 43 Entry 0 255 1 --- F1 0 1
Function Type
44308 0x10D3 Binary In Point 43 Entry 0 255 1 --- F1 0 1
Information Number
44309 0x10D4 Binary In Point 44 Entry 0 255 1 --- F1 0 1
Function Type
44310 0x10D5 Binary In Point 44 Entry 0 255 1 --- F1 0 1
Information Number
44311 0x10D6 Binary In Point 45 Entry 0 255 1 --- F1 0 1
Function Type
44312 0x10D7 Binary In Point 45 Entry 0 255 1 --- F1 0 1
Information Number
44313 0x10D8 Binary In Point 46 Entry 0 255 1 --- F1 0 1
Function Type
44314 0x10D9 Binary In Point 46 Entry 0 255 1 --- F1 0 1
Information Number
44315 0x10DA Binary In Point 47 Entry 0 255 1 --- F1 0 1
Function Type
44316 0x10DB Binary In Point 47 Entry 0 255 1 --- F1 0 1
Information Number
44317 0x10DC Binary In Point 48 Entry 0 255 1 --- F1 0 1
Function Type
44318 0x10DD Binary In Point 48 Entry 0 255 1 --- F1 0 1
Information Number
44319 0x10DE Binary In Point 49 Entry 0 255 1 --- F1 0 1
Function Type
44320 0x10DF Binary In Point 49 Entry 0 255 1 --- F1 0 1
Information Number
44321 0x10E0 Binary In Point 50 Entry 0 255 1 --- F1 0 1
Function Type
44322 0x10E1 Binary In Point 50 Entry 0 255 1 --- F1 0 1
Information Number
44323 0x10E2 Binary In Point 51 Entry 0 255 1 --- F1 0 1
Function Type
44324 0x10E3 Binary In Point 51 Entry 0 255 1 --- F1 0 1
Information Number
44325 0x10E4 Binary In Point 52 Entry 0 255 1 --- F1 0 1
Function Type
44326 0x10E5 Binary In Point 52 Entry 0 255 1 --- F1 0 1
Information Number
44327 0x10E6 Binary In Point 53 Entry 0 255 1 --- F1 0 1
Function Type
44328 0x10E7 Binary In Point 53 Entry 0 255 1 --- F1 0 1
Information Number
44329 0x10E8 Binary In Point 54 Entry 0 255 1 --- F1 0 1
Function Type
44330 0x10E9 Binary In Point 54 Entry 0 255 1 --- F1 0 1
Information Number
44331 0x10EA Binary In Point 55 Entry 0 255 1 --- F1 0 1
Function Type
44332 0x10EB Binary In Point 55 Entry 0 255 1 --- F1 0 1
Information Number
44333 0x10EC Binary In Point 56 Entry 0 255 1 --- F1 0 1
Function Type

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-47


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44334 0x10ED Binary In Point 56 Entry 0 255 1 --- F1 0 1
Information Number
44335 0x10EE Binary In Point 57 Entry 0 255 1 --- F1 0 1
Function Type
44336 0x10EF Binary In Point 57 Entry 0 255 1 --- F1 0 1
Information Number
44337 0x10F0 Binary In Point 58 Entry 0 255 1 --- F1 0 1
Function Type
44338 0x10F1 Binary In Point 58 Entry 0 255 1 --- F1 0 1
Information Number
44339 0x10F2 Binary In Point 59 Entry 0 255 1 --- F1 0 1
Function Type
44340 0x10F3 Binary In Point 59 Entry 0 255 1 --- F1 0 1
Information Number
44341 0x10F4 Binary In Point 60 Entry 0 255 1 --- F1 0 1
Function Type
44342 0x10F5 Binary In Point 60 Entry 0 255 1 --- F1 0 1
Information Number
44343 0x10F6 Binary In Point 61 Entry 0 255 1 --- F1 0 1
Function Type
44344 0x10F7 Binary In Point 61 Entry 0 255 1 --- F1 0 1
Information Number
44345 0x10F8 Binary In Point 62 Entry 0 255 1 --- F1 0 1
Function Type
44346 0x10F9 Binary In Point 62 Entry 0 255 1 --- F1 0 1
Information Number
44347 0x10FA Binary In Point 63 Entry 0 255 1 --- F1 0 1
Function Type
44348 0x10FB Binary In Point 63 Entry 0 255 1 --- F1 0 1
Information Number
DNP / IEC60870-5-103 BINARY OUTPUT POINTS
44349 0x10FC Binary Out Point 0 Entry 0 255 1 --- F1 0 1
Function Type
44350 0x10FD Binary Out Point 0 Entry 0 255 1 --- F1 0 1
Information Number
44351 0x10FE Binary Out Point 1 Entry 0 255 1 --- F1 0 1
Function Type
44352 0x10FF Binary Out Point 1 Entry 0 255 1 --- F1 0 1
Information Number
44353 0x1100 Binary Out Point 2 Entry 0 255 1 --- F1 0 1
Function Type
44354 0x1101 Binary Out Point 2 Entry 0 255 1 --- F1 0 1
Information Number
44355 0x1102 Binary Out Point 3 Entry 0 255 1 --- F1 0 1
Function Type
44356 0x1103 Binary Out Point 3 Entry 0 255 1 --- F1 0 1
Information Number
44357 0x1104 Binary Out Point 4 Entry 0 255 1 --- F1 0 1
Function Type
44358 0x1105 Binary Out Point 4 Entry 0 255 1 --- F1 0 1
Information Number
44359 0x1106 Binary Out Point 5 Entry 0 255 1 --- F1 0 1
Function Type
44360 0x1107 Binary Out Point 5 Entry 0 255 1 --- F1 0 1
Information Number

11-48 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44361 0x1108 Binary Out Point 6 Entry 0 255 1 --- F1 0 1
Function Type
44362 0x1109 Binary Out Point 6 Entry 0 255 1 --- F1 0 1
Information Number
44363 0x110A Binary Out Point 7 Entry 0 255 1 --- F1 0 1
Function Type
44364 0x110B Binary Out Point 7 Entry 0 255 1 --- F1 0 1
Information Number
44365 0x110C Binary Out Point 8 Entry 0 255 1 --- F1 0 1
Function Type
44366 0x110D Binary Out Point 8 Entry 0 255 1 --- F1 0 1
Information Number
44367 0x110E Binary Out Point 9 Entry 0 255 1 --- F1 0 1
Function Type
44368 0x110F Binary Out Point 9 Entry 0 255 1 --- F1 0 1
Information Number
44369 0x1110 Binary Out Point 10 Entry 0 255 1 --- F1 0 1
Function Type
44370 0x1111 Binary Out Point 10 Entry 0 255 1 --- F1 0 1
Information Number
44371 0x1112 Binary Out Point 11 Entry 0 255 1 --- F1 0 1
Function Type
44372 0x1113 Binary Out Point 11 Entry 0 255 1 --- F1 0 1
Information Number
44373 0x1114 Binary Out Point 12 Entry 0 255 1 --- F1 0 1
Function Type
44374 0x1115 Binary Out Point 12 Entry 0 255 1 --- F1 0 1
Information Number
44375 0x1116 Binary Out Point 13 Entry 0 255 1 --- F1 0 1
Function Type
44376 0x1117 Binary Out Point 13 Entry 0 255 1 --- F1 0 1
Information Number
44377 0x1118 Binary Out Point 14 Entry 0 255 1 --- F1 0 1
Function Type
44378 0x1119 Binary Out Point 14 Entry 0 255 1 --- F1 0 1
Information Number
44379 0x111A Binary Out Point 15 Entry 0 255 1 --- F1 0 1
Function Type
44380 0x111B Binary Out Point 15 Entry 0 255 1 --- F1 0 1
Information Number
DNP / IEC60870-5-103 ADDRESSING
44382 0x111D IEC60870-5-103 Slave 0 254 1 --- F1 0 1
Address
44383 0x111E Synchronization Timeout 0 1440 1 min F1 0 1
IEC60870-5-103 MEASURANDS
44384 0x111F 103 First ASDU Identification 3 9 1 --- FC221 3 1
Type
44385 0x1120 103 First ASDU Function 0 255 1 --- F1 0 1
Type
44386 0x1121 103 First ASDU Information 0 255 1 --- F1 0 1
Number
44387 0x1122 103 First ASDU Scan 0 1000 1 s F1 0 1
Timeout
44388 0x1123 103 First ASDU First 0 251 1 --- F88 0 1
Analogue Entry

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-49


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44389 0x1124 103 First ASDU First 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44390 0x1125 103 First ASDU First 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44391 0x1126 103 First ASDU Second 0 251 1 --- F88 0 1
Analogue Entry
44392 0x1127 103 First ASDU Second 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44393 0x1128 103 First ASDU Second 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44394 0x1129 103 First ASDU Third 0 251 1 --- F88 0 1
Analogue Entry
44395 0x112A 103 First ASDU Third 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44396 0x112B 103 First ASDU Third 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44397 0x112C 103 First ASDU Fourth 0 251 1 --- F88 0 1
Analogue Entry
44398 0x112D 103 First ASDU Fourth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44399 0x112E 103 First ASDU Fourth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44400 0x112F 103 First ASDU Fifth 0 251 1 --- F88 0 1
Analogue Entry
44401 0x1130 103 First ASDU Fifth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44402 0x1131 103 First ASDU Fifth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44403 0x1132 103 First ASDU Sixth 0 251 1 --- F88 0 1
Analogue Entry
44404 0x1133 103 First ASDU Sixth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44405 0x1134 103 First ASDU Sixth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44406 0x1135 103 First ASDU Seventh 0 251 1 --- F88 0 1
Analogue Entry
44407 0x1136 103 First ASDU Seventh 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44408 0x1137 103 First ASDU Seventh 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44409 0x1138 103 First ASDU Eigth 0 251 1 --- F88 0 1
Analogue Entry
44410 0x1139 103 First ASDU Eigth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44411 0x113A 103 First ASDU Eigth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44412 0x113B 103 First ASDU Ninth 0 251 1 --- F88 0 1
Analogue Entry
44413 0x113C 103 First ASDU Ninth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44414 0x113D 103 First ASDU Ninth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44415 0x113E 103 Second ASDU 3 9 1 --- FC221 3 1
Identification Type

11-50 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44416 0x113F 103 Second ASDU Function 0 255 1 --- F1 0 1
Type
44417 0x1140 103 Second ASDU 0 255 1 --- F1 0 1
Information Number
44418 0x1141 103 Second ASDU Scan 0 1000 1 s F1 0 1
Timeout
44419 0x1142 103 Second ASDU First 0 251 1 --- F88 0 1
Analogue Entry
44420 0x1143 103 Second ASDU First 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44421 0x1144 103 Second ASDU First 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44422 0x1145 103 Second ASDU Second 0 251 1 --- F88 0 1
Analogue Entry
44423 0x1146 103 Second ASDU Second 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44424 0x1147 103 Second ASDU Second 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44425 0x1148 103 Second ASDU Third 0 251 1 --- F88 0 1
Analogue Entry
44426 0x1149 103 Second ASDU Third 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44427 0x114A 103 Second ASDU Third 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44428 0x114B 103 Second ASDU Fourth 0 251 1 --- F88 0 1
Analogue Entry
44429 0x114C 103 Second ASDU Fourth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44430 0x114D 103 Second ASDU Fourth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44431 0x114E 103 Second ASDU Fifth 0 251 1 --- F88 0 1
Analogue Entry
44432 0x114F 103 Second ASDU Fifth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44433 0x1150 103 Second ASDU Fifth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44434 0x1151 103 Second ASDU Sixth 0 251 1 --- F88 0 1
Analogue Entry
44435 0x1152 103 Second ASDU Sixth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44436 0x1153 103 Second ASDU Sixth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44437 0x1154 103 Second ASDU Seventh 0 251 1 --- F88 0 1
Analogue Entry
44438 0x1155 103 Second ASDU Seventh 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44439 0x1156 103 Second ASDU Seventh 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44440 0x1157 103 Second ASDU Eigth 0 251 1 --- F88 0 1
Analogue Entry
44441 0x1158 103 Second ASDU Eigth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44442 0x1159 103 Second ASDU Eigth 0 0xFFFF 1 --- F1 0 1
Analogue Offset

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-51


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44443 0x115A 103 Second ASDU Ninth 0 251 1 --- F88 0 1
Analogue Entry
44444 0x115B 103 Second ASDU Ninth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44445 0x115C 103 Second ASDU Ninth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44446 0x115D 103 Third ASDU 3 9 1 --- FC221 3 1
Identification Type
44447 0x115E 103 Third ASDU Function 0 255 1 --- F1 0 1
Type
44448 0x115F 103 Third ASDU Information 0 255 1 --- F1 0 1
Number
44449 0x1160 103 Third ASDU Scan 0 1000 1 s F1 0 1
Timeout
44450 0x1161 103 Third ASDU First 0 251 1 --- F88 0 1
Analogue Entry
44451 0x1162 103 Third ASDU First 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44452 0x1163 103 Third ASDU First 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44453 0x1164 103 Third ASDU Second 0 251 1 --- F88 0 1
Analogue Entry
44454 0x1165 103 Third ASDU Second 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44455 0x1166 103 Third ASDU Second 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44456 0x1167 103 Third ASDU Third 0 251 1 --- F88 0 1
Analogue Entry
44457 0x1168 103 Third ASDU Third 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44458 0x1169 103 Third ASDU Third 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44459 0x116A 103 Third ASDU Fourth 0 251 1 --- F88 0 1
Analogue Entry
44460 0x116B 103 Third ASDU Fourth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44461 0x116C 103 Third ASDU Fourth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44462 0x116D 103 Third ASDU Fifth 0 251 1 --- F88 0 1
Analogue Entry
44463 0x116E 103 Third ASDU Fifth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44464 0x116F 103 Third ASDU Fifth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44465 0x1170 103 Third ASDU Sixth 0 251 1 --- F88 0 1
Analogue Entry
44466 0x1171 103 Third ASDU Sixth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44467 0x1172 103 Third ASDU Sixth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44468 0x1173 103 Third ASDU Seventh 0 251 1 --- F88 0 1
Analogue Entry
44469 0x1174 103 Third ASDU Seventh 0 0xFFFF 1 --- F3 0 1
Analogue Factor

11-52 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44470 0x1175 103 Third ASDU Seventh 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44471 0x1176 103 Third ASDU Eigth 0 251 1 --- F88 0 1
Analogue Entry
44472 0x1177 103 Third ASDU Eigth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44473 0x1178 103 Third ASDU Eigth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44474 0x1179 103 Third ASDU Ninth 0 251 1 --- F88 0 1
Analogue Entry
44475 0x117A 103 Third ASDU Ninth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44476 0x117B 103 Third ASDU Ninth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44477 0x117C 103 Fourth ASDU 3 9 1 --- FC221 3 1
Identification Type
44478 0x117D 103 Fourth ASDU Function 0 255 1 --- F1 0 1
Type
44479 0x117E 103 Fourth ASDU 0 255 1 --- F1 0 1
Information Number
44480 0x117F 103 Fourth ASDU Scan 0 1000 1 s F1 0 1
Timeout
44481 0x1180 103 Fourth ASDU First 0 251 1 --- F88 0 1
Analogue Entry
44482 0x1181 103 Fourth ASDU First 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44483 0x1182 103 Fourth ASDU First 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44484 0x1183 103 Fourth ASDU Second 0 251 1 --- F88 0 1
Analogue Entry
44485 0x1184 103 Fourth ASDU Second 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44486 0x1185 103 Fourth ASDU Second 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44487 0x1186 103 Fourth ASDU Third 0 251 1 --- F88 0 1
Analogue Entry
44488 0x1187 103 Fourth ASDU Third 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44489 0x1188 103 Fourth ASDU Third 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44490 0x1189 103 Fourth ASDU Fourth 0 251 1 --- F88 0 1
Analogue Entry
44491 0x118A 103 Fourth ASDU Fourth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44492 0x118B 103 Fourth ASDU Fourth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44493 0x118C 103 Fourth ASDU Fifth 0 251 1 --- F88 0 1
Analogue Entry
44494 0x118D 103 Fourth ASDU Fifth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44495 0x118E 103 Fourth ASDU Fifth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44496 0x118F 103 Fourth ASDU Sixth 0 251 1 --- F88 0 1
Analogue Entry

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-53


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44497 0x1190 103 Fourth ASDU Sixth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44498 0x1191 103 Fourth ASDU Sixth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44499 0x1192 103 Fourth ASDU Seventh 0 251 1 --- F88 0 1
Analogue Entry
44500 0x1193 103 Fourth ASDU Seventh 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44501 0x1194 103 Fourth ASDU Seventh 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44502 0x1195 103 Fourth ASDU Eigth 0 251 1 --- F88 0 1
Analogue Entry
44503 0x1196 103 Fourth ASDU Eigth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44504 0x1197 103 Fourth ASDU Eigth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44505 0x1198 103 Fourth ASDU Ninth 0 251 1 --- F88 0 1
Analogue Entry
44506 0x1199 103 Fourth ASDU Ninth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44507 0x119A 103 Fourth ASDU Ninth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
PASSWORD SECURITY
44536 0x11B7 Security Passcode Master 1 0 1 1 --- F22 0 1
44537 0x11B8 Security Passcode Master 2 0 1 1 --- F22 0 1
44538 0x11B9 Security Passcode Master 3 0 1 1 --- F22 0 1
44539 0x11BA Security Passcode Master 4 0 1 1 --- F22 0 1
44540 0x11BB Security Passcode Master 5 0 1 1 --- F22 0 1
44541 0x11BC Security Passcode Local 0 1 1 --- F22 0 1
Setpoint 1
44542 0x11BD Security Passcode Local 0 1 1 --- F22 0 1
Setpoint 2
44543 0x11BE Security Passcode Local 0 1 1 --- F22 0 1
Setpoint 3
44544 0x11BF Security Passcode Local 0 1 1 --- F22 0 1
Setpoint 4
44545 0x11C0 Security Passcode Local 0 1 1 --- F22 0 1
Setpoint 5
44546 0x11C1 Security Passcode Local 0 1 1 --- F22 0 1
Control 1
44547 0x11C2 Security Passcode Local 0 1 1 --- F22 0 1
Control 2
44548 0x11C3 Security Passcode Local 0 1 1 --- F22 0 1
Control 3
44549 0x11C4 Security Passcode Local 0 1 1 --- F22 0 1
Control 4
44550 0x11C5 Security Passcode Local 0 1 1 --- F22 0 1
Control 5
44551 0x11C6 Security Passcode Remote 0 1 1 --- F22 0 1
Setpoint 1
44552 0x11C7 Security Passcode Remote 0 1 1 --- F22 0 1
Setpoint 2
44553 0x11C8 Security Passcode Remote 0 1 1 --- F22 0 1
Setpoint 3

11-54 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44554 0x11C9 Security Passcode Remote 0 1 1 --- F22 0 1
Setpoint 4
44555 0x11CA Security Passcode Remote 0 1 1 --- F22 0 1
Setpoint 5
44556 0x11CB Security Passcode Remote 0 1 1 --- F22 0 1
Control 1
44557 0x11CC Security Passcode Remote 0 1 1 --- F22 0 1
Control 2
44558 0x11CD Security Passcode Remote 0 1 1 --- F22 0 1
Control 3
44559 0x11CE Security Passcode Remote 0 1 1 --- F22 0 1
Control 4
44560 0x11CF Security Passcode Remote 0 1 1 --- F22 0 1
Control 5
44561 0x11D0 Security Passcode Entry 0 1 1 --- F22 0 1
Master 1
44562 0x11D1 Security Passcode Entry 0 1 1 --- F22 0 1
Master 2
44563 0x11D2 Security Passcode Entry 0 1 1 --- F22 0 1
Master 3
44564 0x11D3 Security Passcode Entry 0 1 1 --- F22 0 1
Master 4
44565 0x11D4 Security Passcode Entry 0 1 1 --- F22 0 1
Master 5
44566 0x11D5 Security Passcode Entry 0 1 1 --- F22 0 1
Setpoints 1
44567 0x11D6 Security Passcode Entry 0 1 1 --- F22 0 1
Setpoints 2
44568 0x11D7 Security Passcode Entry 0 1 1 --- F22 0 1
Setpoints 3
44569 0x11D8 Security Passcode Entry 0 1 1 --- F22 0 1
Setpoints 4
44570 0x11D9 Security Passcode Entry 0 1 1 --- F22 0 1
Setpoints 5
44571 0x11DA Security Passcode Entry 0 1 1 --- F22 0 1
Control 1
44572 0x11DB Security Passcode Entry 0 1 1 --- F22 0 1
Control 2
44573 0x11DC Security Passcode Entry 0 1 1 --- F22 0 1
Control 3
44574 0x11DD Security Passcode Entry 0 1 1 --- F22 0 1
Control 4
44575 0x11DE Security Passcode Entry 0 1 1 --- F22 0 1
Control 5
44576 0x11DF Overwrite Local Setpoint 0 1 1 --- FC103A 0 1
Password
VIRTUAL INPUT FUNCTION
44580 0x11E3 Virtual Input 1 Function 0 1 1 --- FC126 0 1
44581 0x11E4 Virtual Input 2 Function 0 1 1 --- FC126 0 1
44582 0x11E5 Virtual Input 3 Function 0 1 1 --- FC126 0 1
44583 0x11E6 Virtual Input 4 Function 0 1 1 --- FC126 0 1
44584 0x11E7 Virtual Input 5 Function 0 1 1 --- FC126 0 1
44585 0x11E8 Virtual Input 6 Function 0 1 1 --- FC126 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-55


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44586 0x11E9 Virtual Input 7 Function 0 1 1 --- FC126 0 1
44587 0x11EA Virtual Input 8 Function 0 1 1 --- FC126 0 1
44588 0x11EB Virtual Input 9 Function 0 1 1 --- FC126 0 1
44589 0x11EC Virtual Input 10 Function 0 1 1 --- FC126 0 1
44590 0x11ED Virtual Input 11 Function 0 1 1 --- FC126 0 1
44591 0x11EE Virtual Input 12 Function 0 1 1 --- FC126 0 1
44592 0x11EF Virtual Input 13 Function 0 1 1 --- FC126 0 1
44593 0x11F0 Virtual Input 14 Function 0 1 1 --- FC126 0 1
44594 0x11F1 Virtual Input 15 Function 0 1 1 --- FC126 0 1
44595 0x11F2 Virtual Input 16 Function 0 1 1 --- FC126 0 1
44596 0x11F3 Virtual Input 17 Function 0 1 1 --- FC126 0 1
44597 0x11F4 Virtual Input 18 Function 0 1 1 --- FC126 0 1
44598 0x11F5 Virtual Input 19 Function 0 1 1 --- FC126 0 1
44599 0x11F6 Virtual Input 20 Function 0 1 1 --- FC126 0 1
44600 0x11F7 Virtual Input 21 Function 0 1 1 --- FC126 0 1
44601 0x11F8 Virtual Input 22 Function 0 1 1 --- FC126 0 1
44602 0x11F9 Virtual Input 23 Function 0 1 1 --- FC126 0 1
44603 0x11FA Virtual Input 24 Function 0 1 1 --- FC126 0 1
44604 0x11FB Virtual Input 25 Function 0 1 1 --- FC126 0 1
44605 0x11FC Virtual Input 26 Function 0 1 1 --- FC126 0 1
44606 0x11FD Virtual Input 27 Function 0 1 1 --- FC126 0 1
44607 0x11FE Virtual Input 28 Function 0 1 1 --- FC126 0 1
44608 0x11FF Virtual Input 29 Function 0 1 1 --- FC126 0 1
44609 0x1200 Virtual Input 30 Function 0 1 1 --- FC126 0 1
44610 0x1201 Virtual Input 31 Function 0 1 1 --- FC126 0 1
44611 0x1202 Virtual Input 32 Function 0 1 1 --- FC126 0 1
VIRTUAL INPUT TYPE
44612 0x1203 Virtual Input 1 Type 0 1 1 --- FC199 0 1
44613 0x1204 Virtual Input 2 Type 0 1 1 --- FC199 0 1
44614 0x1205 Virtual Input 3 Type 0 1 1 --- FC199 0 1
44615 0x1206 Virtual Input 4 Type 0 1 1 --- FC199 0 1
44616 0x1207 Virtual Input 5 Type 0 1 1 --- FC199 0 1
44617 0x1208 Virtual Input 6 Type 0 1 1 --- FC199 0 1
44618 0x1209 Virtual Input 7 Type 0 1 1 --- FC199 0 1
44619 0x120A Virtual Input 8 Type 0 1 1 --- FC199 0 1
44620 0x120B Virtual Input 9 Type 0 1 1 --- FC199 0 1
44621 0x120C Virtual Input 10 Type 0 1 1 --- FC199 0 1
44622 0x120D Virtual Input 11 Type 0 1 1 --- FC199 0 1
44623 0x120E Virtual Input 12 Type 0 1 1 --- FC199 0 1
44624 0x120F Virtual Input 13 Type 0 1 1 --- FC199 0 1
44625 0x1210 Virtual Input 14 Type 0 1 1 --- FC199 0 1
44626 0x1211 Virtual Input 15 Type 0 1 1 --- FC199 0 1
44627 0x1212 Virtual Input 16 Type 0 1 1 --- FC199 0 1
44628 0x1213 Virtual Input 17 Type 0 1 1 --- FC199 0 1
44629 0x1214 Virtual Input 18 Type 0 1 1 --- FC199 0 1

11-56 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44630 0x1215 Virtual Input 19 Type 0 1 1 --- FC199 0 1
44631 0x1216 Virtual Input 20 Type 0 1 1 --- FC199 0 1
44632 0x1217 Virtual Input 21 Type 0 1 1 --- FC199 0 1
44633 0x1218 Virtual Input 22 Type 0 1 1 --- FC199 0 1
44634 0x1219 Virtual Input 23 Type 0 1 1 --- FC199 0 1
44635 0x121A Virtual Input 24 Type 0 1 1 --- FC199 0 1
44636 0x121B Virtual Input 25 Type 0 1 1 --- FC199 0 1
44637 0x121C Virtual Input 26 Type 0 1 1 --- FC199 0 1
44638 0x121D Virtual Input 27 Type 0 1 1 --- FC199 0 1
44639 0x121E Virtual Input 28 Type 0 1 1 --- FC199 0 1
44640 0x121F Virtual Input 29 Type 0 1 1 --- FC199 0 1
44641 0x1220 Virtual Input 30 Type 0 1 1 --- FC199 0 1
44642 0x1221 Virtual Input 31 Type 0 1 1 --- FC199 0 1
44643 0x1222 Virtual Input 32 Type 0 1 1 --- FC199 0 1
IEC61850 GOOSE
44645 0x1224 Enable GOOSE Transmission 0 1 1 --- FC126 0 1
44646 0x1225 Enable GOOSE 0 1 1 --- FC126 0 1
44647 0x1226 GOOSE Name 0 20 1 --- F22 20
SR3_GOOSE
1
44667 0x123A VLAN Identifier 0 4095 1 --- F1 0 1
44668 0x123B VLAN Priority 1 7 1 --- F1 4 1
44669 0x123C Application Identifier 0 0x3FFF 1 --- F1 0 1
44670 0x123D Update Time 1000 60000 1 ms F1 10000 1
44671 0x123E DataSet Name 0 20 1 --- F22 GOOSE1 20
44691 0x1252 Control Block Name 0 20 1 --- F22 gcb01 20
44711 0x1266 Conf Revision Number 1 0xFFFF 1 --- F1 1 1
44712 0x1267 Destination MAC Address 0 0xFFFF 1 --- FC214 0 3
44715 0x126A MMS TCP Port Number 1 65535 1 --- F1 102 1
44716 0x126B TCP Connection Timeout 10 1800 1 s F1 120 1
IEC61850 GOOSE TRANSMISSION DATASET ITEMS
44718 0x126D DataSet Item 1 0 0xFFFF 1 --- FC134B 0 1
44719 0x126E Item 1 Quality 0 1 1 --- FC126 0 1
44720 0x126F DataSet Item 2 0 0xFFFF 1 --- FC134B 0 1
44721 0x1270 Item 2 Quality 0 1 1 --- FC126 0 1
44722 0x1271 DataSet Item 3 0 0xFFFF 1 --- FC134B 0 1
44723 0x1272 Item 3 Quality 0 1 1 --- FC126 0 1
44724 0x1273 DataSet Item 4 0 0xFFFF 1 --- FC134B 0 1
44725 0x1274 Item 4 Quality 0 1 1 --- FC126 0 1
44726 0x1275 DataSet Item 5 0 0xFFFF 1 --- FC134B 0 1
44727 0x1276 Item 5 Quality 0 1 1 --- FC126 0 1
44728 0x1277 DataSet Item 6 0 0xFFFF 1 --- FC134B 0 1
44729 0x1278 Item 6 Quality 0 1 1 --- FC126 0 1
44730 0x1279 DataSet Item 7 0 0xFFFF 1 --- FC134B 0 1
44731 0x127A Item 7 Quality 0 1 1 --- FC126 0 1
44732 0x127B DataSet Item 8 0 0xFFFF 1 --- FC134B 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-57


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44733 0x127C Item 8 Quality 0 1 1 --- FC126 0 1
44734 0x127D DataSet Item 9 0 0xFFFF 1 --- FC134B 0 1
44735 0x127E Item 9 Quality 0 1 1 --- FC126 0 1
44736 0x127F DataSet Item 10 0 0xFFFF 1 --- FC134B 0 1
44737 0x1280 Item 10 Quality 0 1 1 --- FC126 0 1
44738 0x1281 DataSet Item 11 0 0xFFFF 1 --- FC134B 0 1
44739 0x1282 Item 11 Quality 0 1 1 --- FC126 0 1
44740 0x1283 DataSet Item 12 0 0xFFFF 1 --- FC134B 0 1
44741 0x1284 Item 12 Quality 0 1 1 --- FC126 0 1
44742 0x1285 DataSet Item 13 0 0xFFFF 1 --- FC134B 0 1
44743 0x1286 Item 13 Quality 0 1 1 --- FC126 0 1
44744 0x1287 DataSet Item 14 0 0xFFFF 1 --- FC134B 0 1
44745 0x1288 Item 14 Quality 0 1 1 --- FC126 0 1
44746 0x1289 DataSet Item 15 0 0xFFFF 1 --- FC134B 0 1
44747 0x128A Item 15 Quality 0 1 1 --- FC126 0 1
44748 0x128B DataSet Item 16 0 0xFFFF 1 --- FC134B 0 1
44749 0x128C Item 16 Quality 0 1 1 --- FC126 0 1
44750 0x128D DataSet Item 17 0 0xFFFF 1 --- FC134B 0 1
44751 0x128E Item 17 Quality 0 1 1 --- FC126 0 1
44752 0x128F DataSet Item 18 0 0xFFFF 1 --- FC134B 0 1
44753 0x1290 Item 18 Quality 0 1 1 --- FC126 0 1
44754 0x1291 DataSet Item 19 0 0xFFFF 1 --- FC134B 0 1
44755 0x1292 Item 19 Quality 0 1 1 --- FC126 0 1
44756 0x1293 DataSet Item 20 0 0xFFFF 1 --- FC134B 0 1
44757 0x1294 Item 20 Quality 0 1 1 --- FC126 0 1
44758 0x1295 DataSet Item 21 0 0xFFFF 1 --- FC134B 0 1
44759 0x1296 Item 21 Quality 0 1 1 --- FC126 0 1
44760 0x1297 DataSet Item 22 0 0xFFFF 1 --- FC134B 0 1
44761 0x1298 Item 22 Quality 0 1 1 --- FC126 0 1
44762 0x1299 DataSet Item 23 0 0xFFFF 1 --- FC134B 0 1
44763 0x129A Item 23 Quality 0 1 1 --- FC126 0 1
44764 0x129B DataSet Item 24 0 0xFFFF 1 --- FC134B 0 1
44765 0x129C Item 24 Quality 0 1 1 --- FC126 0 1
44766 0x129D DataSet Item 25 0 0xFFFF 1 --- FC134B 0 1
44767 0x129E Item 25 Quality 0 1 1 --- FC126 0 1
44768 0x129F DataSet Item 26 0 0xFFFF 1 --- FC134B 0 1
44769 0x12A0 Item 26 Quality 0 1 1 --- FC126 0 1
44770 0x12A1 DataSet Item 27 0 0xFFFF 1 --- FC134B 0 1
44771 0x12A2 Item 27 Quality 0 1 1 --- FC126 0 1
44772 0x12A3 DataSet Item 28 0 0xFFFF 1 --- FC134B 0 1
44773 0x12A4 Item 28 Quality 0 1 1 --- FC126 0 1
44774 0x12A5 DataSet Item 29 0 0xFFFF 1 --- FC134B 0 1
44775 0x12A6 Item 29 Quality 0 1 1 --- FC126 0 1
44776 0x12A7 DataSet Item 30 0 0xFFFF 1 --- FC134B 0 1
44777 0x12A8 Item 30 Quality 0 1 1 --- FC126 0 1

11-58 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
44778 0x12A9 DataSet Item 31 0 0xFFFF 1 --- FC134B 0 1
44779 0x12AA Item 31 Quality 0 1 1 --- FC126 0 1
44780 0x12AB DataSet Item 32 0 0xFFFF 1 --- FC134B 0 1
44781 0x12AC Item 32 Quality 0 1 1 --- FC126 0 1
IEC61850 GOOSE RX1 CONFIGURATION
44786 0x12B1 Rx GOOSE1 Function 0 1 1 --- FC126 0 1
44787 0x12B2 Rx GOOSE1 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE1
44807 0x12C6 Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
44827 0x12DA RX1 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb01
44847 0x12EE RX1 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
44848 0x12EF EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX2 CONFIGURATION
44852 0x12F3 Rx GOOSE2 Function 0 1 1 --- FC126 0 1
44853 0x12F4 Rx GOOSE2 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE2
44873 0x1308 Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
44893 0x131C RX2 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb02
44913 0x1330 RX2 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
44914 0x1331 EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX3 CONFIGURATION
44918 0x1335 Rx GOOSE3 Function 0 1 1 --- FC126 0 1
44919 0x1336 Rx GOOSE3 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE3
44939 0x134A Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
44959 0x135E RX3 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb03
44979 0x1372 RX3 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
44980 0x1373 EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX4 CONFIGURATION
44984 0x1377 Rx GOOSE4 Function 0 1 1 --- FC126 0 1
44985 0x1378 Rx GOOSE4 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE4
45005 0x138C Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-59


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
45025 0x13A0 RX4 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb04
45045 0x13B4 RX4 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
45046 0x13B5 EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX5 CONFIGURATION
45050 0x13B9 Rx GOOSE5 Function 0 1 1 --- FC126 0 1
45051 0x13BA Rx GOOSE5 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE5
45071 0x13CE Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
45091 0x13E2 RX5 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb05
45111 0x13F6 RX5 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
45112 0x13F7 EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX6 CONFIGURATION
45116 0x13FB Rx GOOSE6 Function 0 1 1 --- FC126 0 1
45117 0x13FC Rx GOOSE6 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE6
45137 0x1410 Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
45157 0x1424 RX6 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb06
45177 0x1438 RX6 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
45178 0x1439 EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX7 CONFIGURATION
45182 0x143D Rx GOOSE7 Function 0 1 1 --- FC126 0 1
45183 0x143E Rx GOOSE7 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE7
45203 0x1452 Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
45223 0x1466 RX7 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb07
45243 0x147A RX7 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
45244 0x147B EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX8 CONFIGURATION
45248 0x147F Rx GOOSE8 Function 0 1 1 --- FC126 0 1
45249 0x1480 Rx GOOSE8 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE8

11-60 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
45269 0x1494 Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
45289 0x14A8 RX8 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb08
45309 0x14BC RX8 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
45310 0x14BD EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE DATASET STRUCTURE BUFFER
45314 0x14C1 DataSet Struct Buffer 0 0xFFFF 1 --- FC216 0 250
IEC61850 GOOSE REMOTE INPUTS
45567 0x15BE Remote Input 1 Name 0 7 1 --- F22 RI 1 7
45583 0x15CE Remote Input 1 GOOSE 0 0x80 1 --- FC219 0 1
Source
45584 0x15CF Remote Input 1 Item Source 0 0xFFFF 1 --- FC217 0 1
45585 0x15D0 Remote Input 1 Item Mask 0 0xFFFF 1 --- FC218 0 1
45586 0x15D1 Remote Input 1 Default 0 3 1 --- FC220 1 1
State
45588 0x15D3 Remote Input 2 Name 0 7 1 --- F22 RI 2 7
45604 0x15E3 Remote Input 2 GOOSE 0 0x80 1 --- FC219 0 1
Source
45605 0x15E4 Remote Input 2 Item Source 0 0xFFFF 1 --- FC217 0 1
45606 0x15E5 Remote Input 2 Item Mask 0 0xFFFF 1 --- FC218 0 1
45607 0x15E6 Remote Input 2 Default 0 3 1 --- FC220 1 1
State
45609 0x15E8 Remote Input 3 Name 0 7 1 --- F22 RI 3 7
45625 0x15F8 Remote Input 3 GOOSE 0 0x80 1 --- FC219 0 1
Source
45626 0x15F9 Remote Input 3 Item Source 0 0xFFFF 1 --- FC217 0 1
45627 0x15FA Remote Input 3 Item Mask 0 0xFFFF 1 --- FC218 0 1
45628 0x15FB Remote Input 3 Default 0 3 1 --- FC220 1 1
State
45630 0x15FD Remote Input 4 Name 0 7 1 --- F22 RI 4 7
45646 0x160D Remote Input 4 GOOSE 0 0x80 1 --- FC219 0 1
Source
45647 0x160E Remote Input 4 Item Source 0 0xFFFF 1 --- FC217 0 1
45648 0x160F Remote Input 4 Item Mask 0 0xFFFF 1 --- FC218 0 1
45649 0x1610 Remote Input 4 Default 0 3 1 --- FC220 1 1
State
45651 0x1612 Remote Input 5 Name 0 7 1 --- F22 RI 5 7
45667 0x1622 Remote Input 5 GOOSE 0 0x80 1 --- FC219 0 1
Source
45668 0x1623 Remote Input 5 Item Source 0 0xFFFF 1 --- FC217 0 1
45669 0x1624 Remote Input 5 Item Mask 0 0xFFFF 1 --- FC218 0 1
45670 0x1625 Remote Input 5 Default 0 3 1 --- FC220 1 1
State
45672 0x1627 Remote Input 6 Name 0 7 1 --- F22 RI 6 7
45688 0x1637 Remote Input 6 GOOSE 0 0x80 1 --- FC219 0 1
Source
45689 0x1638 Remote Input 6 Item Source 0 0xFFFF 1 --- FC217 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-61


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
45690 0x1639 Remote Input 6 Item Mask 0 0xFFFF 1 --- FC218 0 1
45691 0x163A Remote Input 6 Default 0 3 1 --- FC220 1 1
State
45693 0x163C Remote Input 7 Name 0 7 1 --- F22 RI 7 7
45709 0x164C Remote Input 7 GOOSE 0 0x80 1 --- FC219 0 1
Source
45710 0x164D Remote Input 7 Item Source 0 0xFFFF 1 --- FC217 0 1
45711 0x164E Remote Input 7 Item Mask 0 0xFFFF 1 --- FC218 0 1
45712 0x164F Remote Input 7 Default 0 3 1 --- FC220 1 1
State
45714 0x1651 Remote Input 8 Name 0 7 1 --- F22 RI 8 7
45730 0x1661 Remote Input 8 GOOSE 0 0x80 1 --- FC219 0 1
Source
45731 0x1662 Remote Input 8 Item Source 0 0xFFFF 1 --- FC217 0 1
45732 0x1663 Remote Input 8 Item Mask 0 0xFFFF 1 --- FC218 0 1
45733 0x1664 Remote Input 8 Default 0 3 1 --- FC220 1 1
State
45735 0x1666 Remote Input 9 Name 0 7 1 --- F22 RI 9 7
45751 0x1676 Remote Input 9 GOOSE 0 0x80 1 --- F1 0 1
Source
45752 0x1677 Remote Input 9 Item Source 0 0xFFFF 1 --- FC217 0 1
45753 0x1678 Remote Input 9 Item Mask 0 0xFFFF 1 --- FC218 0 1
45754 0x1679 Remote Input 9 Default 0 3 1 --- FC220 1 1
State
45756 0x167B Remote Input 10 Name 0 7 1 --- F22 RI 10 7
45772 0x168B Remote Input 10 GOOSE 0 0x80 1 --- F1 0 1
Source
45773 0x168C Remote Input 10 Item 0 0xFFFF 1 --- FC217 0 1
Source
45774 0x168D Remote Input 10 Item Mask 0 0xFFFF 1 --- FC218 0 1
45775 0x168E Remote Input 10 Default 0 3 1 --- FC220 1 1
State
45777 0x1690 Remote Input 11 Name 0 7 1 --- F22 RI 11 7
45793 0x16A0 Remote Input 11 GOOSE 0 0x80 1 --- F1 0 1
Source
45794 0x16A1 Remote Input 11 Item 0 0xFFFF 1 --- FC217 0 1
Source
45795 0x16A2 Remote Input 11 Item Mask 0 0xFFFF 1 --- FC218 0 1
45796 0x16A3 Remote Input 11 Default 0 3 1 --- FC220 1 1
State
45798 0x16A5 Remote Input 12 Name 0 7 1 --- F22 RI 12 7
45814 0x16B5 Remote Input 12 GOOSE 0 0x80 1 --- F1 0 1
Source
45815 0x16B6 Remote Input 12 Item 0 0xFFFF 1 --- FC217 0 1
Source
45816 0x16B7 Remote Input 12 Item Mask 0 0xFFFF 1 --- FC218 0 1
45817 0x16B8 Remote Input 12 Default 0 3 1 --- FC220 1 1
State
45819 0x16BA Remote Input 13 Name 0 7 1 --- F22 RI 13 7
45835 0x16CA Remote Input 13 GOOSE 0 0x80 1 --- F1 0 1
Source

11-62 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
45836 0x16CB Remote Input 13 Item 0 0xFFFF 1 --- FC217 0 1
Source
45837 0x16CC Remote Input 13 Item Mask 0 0xFFFF 1 --- FC218 0 1
45838 0x16CD Remote Input 13 Default 0 3 1 --- FC220 1 1
State
45840 0x16CF Remote Input 14 Name 0 7 1 --- F22 RI 14 7
45856 0x16DF Remote Input 14 GOOSE 0 0x80 1 --- F1 0 1
Source
45857 0x16E0 Remote Input 14 Item 0 0xFFFF 1 --- FC217 0 1
Source
45858 0x16E1 Remote Input 14 Item Mask 0 0xFFFF 1 --- FC218 0 1
45859 0x16E2 Remote Input 14 Default 0 3 1 --- FC220 1 1
State
45861 0x16E4 Remote Input 15 Name 0 7 1 --- F22 RI 15 7
45877 0x16F4 Remote Input 15 GOOSE 0 0x80 1 --- F1 0 1
Source
45878 0x16F5 Remote Input 15 Item 0 0xFFFF 1 --- FC217 0 1
Source
45879 0x16F6 Remote Input 15 Item Mask 0 0xFFFF 1 --- FC218 0 1
45880 0x16F7 Remote Input 15 Default 0 3 1 --- FC220 1 1
State
45882 0x16F9 Remote Input 16 Name 0 7 1 --- F22 RI 16 7
45898 0x1709 Remote Input 16 GOOSE 0 0x80 1 --- F1 0 1
Source
45899 0x170A Remote Input 16 Item 0 0xFFFF 1 --- FC217 0 1
Source
45900 0x170B Remote Input 16 Item Mask 0 0xFFFF 1 --- FC218 0 1
45901 0x170C Remote Input 16 Default 0 3 1 --- FC220 1 1
State
45903 0x170E Remote Input 17 Name 0 7 1 --- F22 RI 17 7
45919 0x171E Remote Input 17 GOOSE 0 0x80 1 --- F1 0 1
Source
45920 0x171F Remote Input 17 Item 0 0xFFFF 1 --- FC217 0 1
Source
45921 0x1720 Remote Input 17 Item Mask 0 0xFFFF 1 --- FC218 0 1
45922 0x1721 Remote Input 17 Default 0 3 1 --- FC220 1 1
State
45924 0x1723 Remote Input 18 Name 0 7 1 --- F22 RI 18 7
45940 0x1733 Remote Input 18 GOOSE 0 0x80 1 --- F1 0 1
Source
45941 0x1734 Remote Input 18 Item 0 0xFFFF 1 --- FC217 0 1
Source
45942 0x1735 Remote Input 18 Item Mask 0 0xFFFF 1 --- FC218 0 1
45943 0x1736 Remote Input 18 Default 0 3 1 --- FC220 1 1
State
45945 0x1738 Remote Input 19 Name 0 7 1 --- F22 RI 19 7
45961 0x1748 Remote Input 19 GOOSE 0 0x80 1 --- F1 0 1
Source
45962 0x1749 Remote Input 19 Item 0 0xFFFF 1 --- FC217 0 1
Source
45963 0x174A Remote Input 19 Item Mask 0 0xFFFF 1 --- FC218 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-63


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
45964 0x174B Remote Input 19 Default 0 3 1 --- FC220 1 1
State
45966 0x174D Remote Input 20 Name 0 7 1 --- F22 RI 20 7
45982 0x175D Remote Input 20 GOOSE 0 0x80 1 --- F1 0 1
Source
45983 0x175E Remote Input 20 Item 0 0xFFFF 1 --- FC217 0 1
Source
45984 0x175F Remote Input 20 Item Mask 0 0xFFFF 1 --- FC218 0 1
45985 0x1760 Remote Input 20 Default 0 3 1 --- FC220 1 1
State
45987 0x1762 Remote Input 21 Name 0 7 1 --- F22 RI 21 7
46003 0x1772 Remote Input 21 GOOSE 0 0x80 1 --- F1 0 1
Source
46004 0x1773 Remote Input 21 Item 0 0xFFFF 1 --- FC217 0 1
Source
46005 0x1774 Remote Input 21 Item Mask 0 0xFFFF 1 --- FC218 0 1
46006 0x1775 Remote Input 21 Default 0 3 1 --- FC220 1 1
State
46008 0x1777 Remote Input 22 Name 0 7 1 --- F22 RI 22 7
46024 0x1787 Remote Input 22 GOOSE 0 0x80 1 --- F1 0 1
Source
46025 0x1788 Remote Input 22 Item 0 0xFFFF 1 --- FC217 0 1
Source
46026 0x1789 Remote Input 22 Item Mask 0 0xFFFF 1 --- FC218 0 1
46027 0x178A Remote Input 22 Default 0 3 1 --- FC220 1 1
State
46029 0x178C Remote Input 23 Name 0 7 1 --- F22 RI 23 7
46045 0x179C Remote Input 23 GOOSE 0 0x80 1 --- F1 0 1
Source
46046 0x179D Remote Input 23 Item 0 0xFFFF 1 --- FC217 0 1
Source
46047 0x179E Remote Input 23 Item Mask 0 0xFFFF 1 --- FC218 0 1
46048 0x179F Remote Input 23 Default 0 3 1 --- FC220 1 1
State
46050 0x17A1 Remote Input 24 Name 0 7 1 --- F22 RI 24 7
46066 0x17B1 Remote Input 24 GOOSE 0 0x80 1 --- F1 0 1
Source
46067 0x17B2 Remote Input 24 Item 0 0xFFFF 1 --- FC217 0 1
Source
46068 0x17B3 Remote Input 24 Item Mask 0 0xFFFF 1 --- FC218 0 1
46069 0x17B4 Remote Input 24 Default 0 3 1 --- FC220 1 1
State
46071 0x17B6 Remote Input 25 Name 0 7 1 --- F22 RI 25 7
46087 0x17C6 Remote Input 25 GOOSE 0 0x80 1 --- F1 0 1
Source
46088 0x17C7 Remote Input 25 Item 0 0xFFFF 1 --- FC217 0 1
Source
46089 0x17C8 Remote Input 25 Item Mask 0 0xFFFF 1 --- FC218 0 1
46090 0x17C9 Remote Input 25 Default 0 3 1 --- FC220 1 1
State
46092 0x17CB Remote Input 26 Name 0 7 1 --- F22 RI 26 7

11-64 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
46108 0x17DB Remote Input 26 GOOSE 0 0x80 1 --- F1 0 1
Source
46109 0x17DC Remote Input 26 Item 0 0xFFFF 1 --- FC217 0 1
Source
46110 0x17DD Remote Input 26 Item Mask 0 0xFFFF 1 --- FC218 0 1
46111 0x17DE Remote Input 26 Default 0 3 1 --- FC220 1 1
State
46113 0x17E0 Remote Input 27 Name 0 7 1 --- F22 RI 27 7
46129 0x17F0 Remote Input 27 GOOSE 0 0x80 1 --- F1 0 1
Source
46130 0x17F1 Remote Input 27 Item 0 0xFFFF 1 --- FC217 0 1
Source
46131 0x17F2 Remote Input 27 Item Mask 0 0xFFFF 1 --- FC218 0 1
46132 0x17F3 Remote Input 27 Default 0 3 1 --- FC220 1 1
State
46134 0x17F5 Remote Input 28 Name 0 7 1 --- F22 RI 28 7
46150 0x1805 Remote Input 28 GOOSE 0 0x80 1 --- F1 0 1
Source
46151 0x1806 Remote Input 28 Item 0 0xFFFF 1 --- FC217 0 1
Source
46152 0x1807 Remote Input 28 Item Mask 0 0xFFFF 1 --- FC218 0 1
46153 0x1808 Remote Input 28 Default 0 3 1 --- FC220 1 1
State
46155 0x180A Remote Input 29 Name 0 7 1 --- F22 RI 29 7
46171 0x181A Remote Input 29 GOOSE 0 0x80 1 --- F1 0 1
Source
46172 0x181B Remote Input 29 Item 0 0xFFFF 1 --- FC217 0 1
Source
46173 0x181C Remote Input 29 Item Mask 0 0xFFFF 1 --- FC218 0 1
46174 0x181D Remote Input 29 Default 0 3 1 --- FC220 1 1
State
46176 0x181F Remote Input 30 Name 0 7 1 --- F22 RI 30 7
46192 0x182F Remote Input 30 GOOSE 0 0x80 1 --- F1 0 1
Source
46193 0x1830 Remote Input 30 Item 0 0xFFFF 1 --- FC217 0 1
Source
46194 0x1831 Remote Input 30 Item Mask 0 0xFFFF 1 --- FC218 0 1
46195 0x1832 Remote Input 30 Default 0 3 1 --- FC220 1 1
State
46197 0x1834 Remote Input 31 Name 0 7 1 --- F22 RI 31 7
46213 0x1844 Remote Input 31 GOOSE 0 0x80 1 --- F1 0 1
Source
46214 0x1845 Remote Input 31 Item 0 0xFFFF 1 --- FC217 0 1
Source
46215 0x1846 Remote Input 31 Item Mask 0 0xFFFF 1 --- FC218 0 1
46216 0x1847 Remote Input 31 Default 0 3 1 --- FC220 1 1
State
46218 0x1849 Remote Input 32 Name 0 7 1 --- F22 RI 32 7
46234 0x1859 Remote Input 32 GOOSE 0 0x80 1 --- F1 0 1
Source
46235 0x185A Remote Input 32 Item 0 0xFFFF 1 --- FC217 0 1
Source

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-65


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
46236 0x185B Remote Input 32 Item Mask 0 0xFFFF 1 --- FC218 0 1
46237 0x185C Remote Input 32 Default 0 3 1 --- FC220 1 1
State
LOGIC ELEMENT NAMES
46240 0x185F Logic Element 1 Name 0 9 1 --- F22 Logic El #1 9
46249 0x1868 Logic Element 2 Name 0 9 1 --- F22 Logic El #2 9
46258 0x1871 Logic Element 3 Name 0 9 1 --- F22 Logic El #3 9
46267 0x187A Logic Element 4 Name 0 9 1 --- F22 Logic El #4 9
46276 0x1883 Logic Element 5 Name 0 9 1 --- F22 Logic El #5 9
46285 0x188C Logic Element 6 Name 0 9 1 --- F22 Logic El #6 9
46294 0x1895 Logic Element 7 Name 0 9 1 --- F22 Logic El #7 9
46303 0x189E Logic Element 8 Name 0 9 1 --- F22 Logic El #8 9
46492 0x195B Logic Element 9 Name 0 9 1 --- F22 Logic El #9 9
46501 0x1964 Logic Element 10 Name 0 9 1 --- F22 Logic El 9
#10
46510 0x196D Logic Element 11 Name 0 9 1 --- F22 Logic El 9
#11
46519 0x1976 Logic Element 12 Name 0 9 1 --- F22 Logic El 9
#12
46528 0x197F Logic Element 13 Name 0 9 1 --- F22 Logic El 9
#13
46537 0x1988 Logic Element 14 Name 0 9 1 --- F22 Logic El 9
#14
46546 0x1991 Logic Element 15 Name 0 9 1 --- F22 Logic El 9
#15
46555 0x199A Logic Element 16 Name 0 9 1 --- F22 Logic El 9
#16
SETPOINT GROUP SETTINGS
42604 0xA2B Negative Sequence IOC 0 3 1 --- FC197 0 1
Function
42605 0xA2C Negative Sequence IOC 5 2000 1 x CT F3 100 1
Pickup
42606 0xA2D Negative Sequence IOC 0 30000 1 s F3 0 1
Delay
46886 0x1AE5 Negative Sequence IOC 2 0 3 1 --- FC197 0 1
Function
46887 0x1AE6 Negative Sequence IOC 2 5 2000 1 x CT F3 100 1
Pickup
46888 0x1AE7 Negative Sequence IOC 2 0 30000 1 s F3 0 1
Delay
PROTECTION FUNCTION BLOCKING
42641 0xA50 Phase IOC 1 Block 1 0 0xEF02 1 --- F89 0 1
42642 0xA51 Phase IOC 1 Block 2 0 0xEF02 1 --- F89 0 1
42643 0xA52 Phase IOC 1 Block 3 0 0xEF02 1 --- F89 0 1
42644 0xA53 Neutral IOC 1 Block 1 0 0xEF02 1 --- F89 0 1
42645 0xA54 Neutral IOC 1 Block 2 0 0xEF02 1 --- F89 0 1
42646 0xA55 Neutral IOC 1 Block 3 0 0xEF02 1 --- F89 0 1
42647 0xA56 Ground IOC 1 Block 1 0 0xEF02 1 --- F89 0 1
42648 0xA57 Ground IOC 1 Block 2 0 0xEF02 1 --- F89 0 1
42649 0xA58 Ground IOC 1 Block 3 0 0xEF02 1 --- F89 0 1

11-66 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
42650 0xA59 Phase TOC Block 1 0 0xEF02 1 --- F89 0 1
42651 0xA5A Phase TOC Block 2 0 0xEF02 1 --- F89 0 1
42652 0xA5B Phase TOC Block 3 0 0xEF02 1 --- F89 0 1
42653 0xA5C Neutral TOC Block 1 0 0xEF02 1 --- F89 0 1
42654 0xA5D Neutral TOC Block 2 0 0xEF02 1 --- F89 0 1
42655 0xA5E Neutral TOC Block 3 0 0xEF02 1 --- F89 0 1
42656 0xA5F Ground TOC Block 1 0 0xEF02 1 --- F89 0 1
42657 0xA60 Ground TOC Block 2 0 0xEF02 1 --- F89 0 1
42658 0xA61 Ground TOC Block 3 0 0xEF02 1 --- F89 0 1
42659 0xA62 Phase IOC 2 Block 1 0 0xEF02 1 --- F89 0 1
42660 0xA63 Phase IOC 2 Block 2 0 0xEF02 1 --- F89 0 1
42661 0xA64 Phase IOC 2 Block 3 0 0xEF02 1 --- F89 0 1
42662 0xA65 Neutral IOC 2 Block 1 0 0xEF02 1 --- F89 0 1
42663 0xA66 Neutral IOC 2 Block 2 0 0xEF02 1 --- F89 0 1
42664 0xA67 Neutral IOC 2 Block 3 0 0xEF02 1 --- F89 0 1
42665 0xA68 Ground IOC 2 Block 1 0 0xEF02 1 --- F89 0 1
42666 0xA69 Ground IOC 2 Block 2 0 0xEF02 1 --- F89 0 1
42667 0xA6A Ground IOC 2 Block 3 0 0xEF02 1 --- F89 0 1
42668 0xA6B Phase TOC 2 Block 1 0 0xEF02 1 --- F89 0 1
42669 0xA6C Phase TOC 2 Block 2 0 0xEF02 1 --- F89 0 1
42670 0xA6D Phase TOC 2 Block 3 0 0xEF02 1 --- F89 0 1
42671 0xA6E Neutral TOC 2 Block 1 0 0xEF02 1 --- F89 0 1
42672 0xA6F Neutral TOC 2 Block 2 0 0xEF02 1 --- F89 0 1
42673 0xA70 Neutral TOC 2 Block 3 0 0xEF02 1 --- F89 0 1
42674 0xA71 Ground TOC 2 Block 1 0 0xEF02 1 --- F89 0 1
42675 0xA72 Ground TOC 2 Block 2 0 0xEF02 1 --- F89 0 1
42676 0xA73 Ground TOC 2 Block 3 0 0xEF02 1 --- F89 0 1
42677 0xA74 Sensitive Ground TOC Block 0 0xEF02 1 --- F89 0 1
1
42678 0xA75 Sensitive Ground TOC Block 0 0xEF02 1 --- F89 0 1
2
42679 0xA76 Sensitive Ground TOC Block 0 0xEF02 1 --- F89 0 1
3
42719 0xA9E Thermal Model Block 1 0 0xEF02 1 --- F89 0 1
42720 0xA9F Thermal Model Block 2 0 0xEF02 1 --- F89 0 1
42721 0xAA0 Thermal Model Block 3 0 0xEF02 1 --- F89 0 1
42722 0xAA1 50SG IOC 1 Block 1 0 0xEF02 1 --- F89 0 1
42723 0xAA2 50SG IOC 1 Block 2 0 0xEF02 1 --- F89 0 1
42724 0xAA3 50SG IOC 1 Block 3 0 0xEF02 1 --- F89 0 1
42725 0xAA4 50SG IOC 2 Block 1 0 0xEF02 1 --- F89 0 1
42726 0xAA5 50SG IOC 2 Block 2 0 0xEF02 1 --- F89 0 1
42727 0xAA6 50SG IOC 2 Block 3 0 0xEF02 1 --- F89 0 1
42728 0xAA7 Negative Sequence IOC 0 0xEF02 1 --- F89 0 1
Block 1
42729 0xAA8 Negative Sequence IOC 0 0xEF02 1 --- F89 0 1
Block 2

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-67


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
42730 0xAA9 Negative Sequence IOC 0 0xEF02 1 --- F89 0 1
Block 3
42731 0xAAA Neg Seq TOC1 Block 1 0 0xEF02 1 --- F89 0 1
42732 0xAAB Neg Seq TOC1 Block 2 0 0xEF02 1 --- F89 0 1
42733 0xAAC Neg Seq TOC1 Block 3 0 0xEF02 1 --- F89 0 1
42734 0xAAD Neg Seq TOC2 Block 1 0 0xEF02 1 --- F89 0 1
42735 0xAAE Neg Seq TOC2 Block 2 0 0xEF02 1 --- F89 0 1
42736 0xAAF Neg Seq TOC2 Block 3 0 0xEF02 1 --- F89 0 1
46320 0x18AF Breaker Failure Block 1 0 0xEF02 1 --- F89 0 1
46321 0x18B0 Breaker Failure Block 2 0 0xEF02 1 --- F89 0 1
46322 0x18B1 Breaker Failure Block 3 0 0xEF02 1 --- F89 0 1
46344 0x18C7 XFMR Block 1 0 0xEF02 1 --- F89 0 1
46345 0x18C8 XFMR Block 2 0 0xEF02 1 --- F89 0 1
46346 0x18C9 XFMR Block 3 0 0xEF02 1 --- F89 0 1
46347 0x18CA RGF 1 Block1 0 0xEF02 1 --- F89 0 1
46348 0x18CB REF 1 Block2 0 0xEF02 1 --- F89 0 1
46349 0x18CC RGF 1 Block3 0 0xEF02 1 --- F89 0 1
46350 0x18CD RGF 2 Block1 0 0xEF02 1 --- F89 0 1
46351 0x18CE RGF 2 Block2 0 0xEF02 1 --- F89 0 1
46352 0x18CF RGF 2 Block3 0 0xEF02 1 --- F89 0 1
46353 0x18D0 Inst Diff Block1 0 0xEF02 1 --- F89 0 1
46354 0x18D1 Inst Diff Block2 0 0xEF02 1 --- F89 0 1
46355 0x18D2 Inst Diff Block3 0 0xEF02 1 --- F89 0 1
46362 0x18D9 Sensitive Ground TOC2 Block 0 0xEF02 1 --- F89 0 1
1
46363 0x18DA Sensitive Ground TOC2 Block 0 0xEF02 1 --- F89 0 1
2
46364 0x18DB Sensitive Ground TOC2 Block 0 0xEF02 1 --- F89 0 1
3
46889 0x1AE8 Negative Sequence IOC 2 0 0xEF02 1 --- F89 0 1
Block 1
46890 0x1AE9 Negative Sequence IOC 2 0 0xEF02 1 --- F89 0 1
Block 2
46891 0x1AEA Negative Sequence IOC 2 0 0xEF02 1 --- F89 0 1
Block 3
PROTECTION ELEMENT RELAY CONFIGURATION
42737 0xAB0 Phase IOC 1 Relay 0 0x7F 1 --- FC198 0 1
42738 0xAB1 Neutral IOC 1 Relay 0 0x7F 1 --- FC198 0 1
42739 0xAB2 Ground IOC 1 Relay 0 0x7F 1 --- FC198 0 1
42740 0xAB3 Phase TOC1 Relay 0 0x7F 1 --- FC198 0 1
42741 0xAB4 Neutral TOC Relay 0 0x7F 1 --- FC198 0 1
42742 0xAB5 Ground TOC1 Relay 0 0x7F 1 --- FC198 0 1
42743 0xAB6 Phase IOC 2 Relay 0 0x7F 1 --- FC198 0 1
42744 0xAB7 Neutral IOC 2 Relay 0 0x7F 1 --- FC198 0 1
42745 0xAB8 Ground IOC 2 Relay 0 0x7F 1 --- FC198 0 1
42746 0xAB9 Phase TOC 2 Relay 0 0x7F 1 --- FC198 0 1
42747 0xABA Neutral TOC 2 Relay 0 0x7F 1 --- FC198 0 1

11-68 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
42748 0xABB Ground TOC 2 Relay 0 0x7F 1 --- FC198 0 1
42749 0xABC Sensitive Ground TOC1 0 0x7F 1 --- FC198 0 1
Relay
42762 0xAC9 Sensitive Ground IOC 1 Relay 0 0x7F 1 --- FC198 0 1
42763 0xACA Sensitive Ground IOC2 Relay 0 0x7F 1 --- FC198 0 1
42764 0xACB Negative Sequence IOC 0 0x7F 1 --- FC198 0 1
Relays
42774 0xAD5 RTD Trouble Relays 0 0x7F 1 --- FC198 0 1
42776 0xAD7 REF 1 Relays 0 0x7F 1 --- FC198 0 1
42777 0xAD8 REF 2 Relays 0 0x7F 1 --- FC198 0 1
42778 0xAD9 Inst Diff Relays 0 0x7F 1 --- FC198 0 1
42782 0xADD Sensitive Ground TOC2 0 0x7F 1 --- FC198 0 1
Relay
46892 0x1AEB Negative Sequence IOC 2 0 0x7F 1 --- FC198 0 1
Relays
FAULT REPORT
46985 0x1B48 Fault Report Delay 0 60000 1 s F3 10 1
46986 0x1B49 Fault Report Trigger 0 0xFFFF 1 --- FC134E 0x8002 1
LOGIC ELEMENTS (TRIGGERS & BLOCKS)
41123 0x462 Logic Element 1 Trigger 0 5 1 --- FC149 0 1
Logic
41124 0x463 Logic Element 1 Block Logic 0 5 1 --- FC149 0 1
41131 0x46A Logic Element 2 Trigger 0 5 1 --- FC149 0 1
Logic
41132 0x46B Logic Element 2 Block Logic 0 5 1 --- FC149 0 1
41139 0x472 Logic Element 3 Trigger 0 5 1 --- FC149 0 1
Logic
41140 0x473 Logic Element 3 Block Logic 0 5 1 --- FC149 0 1
41147 0x47A Logic Element 4 Trigger 0 5 1 --- FC149 0 1
Logic
41148 0x47B Logic Element 4 Block Logic 0 5 1 --- FC149 0 1
41155 0x482 Logic Element 5 Trigger 0 5 1 --- FC149 0 1
Logic
41156 0x483 Logic Element 5 Block Logic 0 5 1 --- FC149 0 1
41163 0x48A Logic Element 6 Trigger 0 5 1 --- FC149 0 1
Logic
41164 0x48B Logic Element 6 Block Logic 0 5 1 --- FC149 0 1
41171 0x492 Logic Element 7 Trigger 0 5 1 --- FC149 0 1
Logic
41172 0x493 Logic Element 7 Block Logic 0 5 1 --- FC149 0 1
41179 0x49A Logic Element 8 Trigger 0 5 1 --- FC149 0 1
Logic
41180 0x49B Logic Element 8 Block Logic 0 5 1 --- FC149 0 1
41187 0x4A2 Logic Element 9 Trigger 0 5 1 --- FC149 0 1
Logic
41188 0x4A3 Logic Element 9 Block Logic 0 5 1 --- FC149 0 1
41195 0x4AA Logic Element 10 Trigger 0 5 1 --- FC149 0 1
Logic
41196 0x4AB Logic Element 10 Block 0 5 1 --- FC149 0 1
Logic

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-69


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
41203 0x4B2 Logic Element 11 Trigger 0 5 1 --- FC149 0 1
Logic
41204 0x4B3 Logic Element 11 Block 0 5 1 --- FC149 0 1
Logic
41211 0x4BA Logic Element 12 Trigger 0 5 1 --- FC149 0 1
Logic
41212 0x4BB Logic Element 12 Block 0 5 1 --- FC149 0 1
Logic
41219 0x4C2 Logic Element 13 Trigger 0 5 1 --- FC149 0 1
Logic
41220 0x4C3 Logic Element 13 Block 0 5 1 --- FC149 0 1
Logic
41227 0x4CA Logic Element 14 Trigger 0 5 1 --- FC149 0 1
Logic
41228 0x4CB Logic Element 14 Block 0 5 1 --- FC149 0 1
Logic
41235 0x4D2 Logic Element 15 Trigger 0 5 1 --- FC149 0 1
Logic
41236 0x4D3 Logic Element 15 Block 0 5 1 --- FC149 0 1
Logic
41243 0x4DA Logic Element 16 Trigger 0 5 1 --- FC149 0 1
Logic
41244 0x4DB Logic Element 16 Block 0 5 1 --- FC149 0 1
Logic
43470 0xD8D Logic Element 1 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43471 0xD8E Logic Element 1 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43472 0xD8F Logic Element 1 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43473 0xD90 Logic Element 1 Block 1 0 0xFFFF 1 --- FC134B 0 1
43474 0xD91 Logic Element 1 Block 2 0 0xFFFF 1 --- FC134B 0 1
43475 0xD92 Logic Element 1 Block 3 0 0xFFFF 1 --- FC134B 0 1
43476 0xD93 Logic Element 2 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43477 0xD94 Logic Element 2 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43478 0xD95 Logic Element 2 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43479 0xD96 Logic Element 2 Block 1 0 0xFFFF 1 --- FC134B 0 1
43480 0xD97 Logic Element 2 Block 2 0 0xFFFF 1 --- FC134B 0 1
43481 0xD98 Logic Element 2 Block 3 0 0xFFFF 1 --- FC134B 0 1
43482 0xD99 Logic Element 3 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43483 0xD9A Logic Element 3 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43484 0xD9B Logic Element 3 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43485 0xD9C Logic Element 3 Block 1 0 0xFFFF 1 --- FC134B 0 1
43486 0xD9D Logic Element 3 Block 2 0 0xFFFF 1 --- FC134B 0 1
43487 0xD9E Logic Element 3 Block 3 0 0xFFFF 1 --- FC134B 0 1
43488 0xD9F Logic Element 4 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43489 0xDA0 Logic Element 4 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43490 0xDA1 Logic Element 4 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43491 0xDA2 Logic Element 4 Block 1 0 0xFFFF 1 --- FC134B 0 1
43492 0xDA3 Logic Element 4 Block 2 0 0xFFFF 1 --- FC134B 0 1
43493 0xDA4 Logic Element 4 Block 3 0 0xFFFF 1 --- FC134B 0 1
43494 0xDA5 Logic Element 5 Trigger 1 0 0xFFFF 1 --- FC134B 0 1

11-70 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
43495 0xDA6 Logic Element 5 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43496 0xDA7 Logic Element 5 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43497 0xDA8 Logic Element 5 Block 1 0 0xFFFF 1 --- FC134B 0 1
43498 0xDA9 Logic Element 5 Block 2 0 0xFFFF 1 --- FC134B 0 1
43499 0xDAA Logic Element 5 Block 3 0 0xFFFF 1 --- FC134B 0 1
43500 0xDAB Logic Element 6 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43501 0xDAC Logic Element 6 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43502 0xDAD Logic Element 6 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43503 0xDAE Logic Element 6 Block 1 0 0xFFFF 1 --- FC134B 0 1
43504 0xDAF Logic Element 6 Block 2 0 0xFFFF 1 --- FC134B 0 1
43505 0xDB0 Logic Element 6 Block 3 0 0xFFFF 1 --- FC134B 0 1
43506 0xDB1 Logic Element 7 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43507 0xDB2 Logic Element 7 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43508 0xDB3 Logic Element 7 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43509 0xDB4 Logic Element 7 Block 1 0 0xFFFF 1 --- FC134B 0 1
43510 0xDB5 Logic Element 7 Block 2 0 0xFFFF 1 --- FC134B 0 1
43511 0xDB6 Logic Element 7 Block 3 0 0xFFFF 1 --- FC134B 0 1
43512 0xDB7 Logic Element 8 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43513 0xDB8 Logic Element 8 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43514 0xDB9 Logic Element 8 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43515 0xDBA Logic Element 8 Block 1 0 0xFFFF 1 --- FC134B 0 1
43516 0xDBB Logic Element 8 Block 2 0 0xFFFF 1 --- FC134B 0 1
43517 0xDBC Logic Element 8 Block 3 0 0xFFFF 1 --- FC134B 0 1
46365 0x18DC Logic Element 9 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46366 0x18DD Logic Element 9 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46367 0x18DE Logic Element 9 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46368 0x18DF Logic Element 9 Block 1 0 0xFFFF 1 --- FC134B 0 1
46369 0x18E0 Logic Element 9 Block 2 0 0xFFFF 1 --- FC134B 0 1
46370 0x18E1 Logic Element 9 Block 3 0 0xFFFF 1 --- FC134B 0 1
46371 0x18E2 Logic Element 10 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46372 0x18E3 Logic Element 10 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46373 0x18E4 Logic Element 10 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46374 0x18E5 Logic Element 10 Block 1 0 0xFFFF 1 --- FC134B 0 1
46375 0x18E6 Logic Element 10 Block 2 0 0xFFFF 1 --- FC134B 0 1
46376 0x18E7 Logic Element 10 Block 3 0 0xFFFF 1 --- FC134B 0 1
46377 0x18E8 Logic Element 11 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46378 0x18E9 Logic Element 11 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46379 0x18EA Logic Element 11 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46380 0x18EB Logic Element 11 Block 1 0 0xFFFF 1 --- FC134B 0 1
46381 0x18EC Logic Element 11 Block 2 0 0xFFFF 1 --- FC134B 0 1
46382 0x18ED Logic Element 11 Block 3 0 0xFFFF 1 --- FC134B 0 1
46383 0x18EE Logic Element 12 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46384 0x18EF Logic Element 12 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46385 0x18F0 Logic Element 12 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46386 0x18F1 Logic Element 12 Block 1 0 0xFFFF 1 --- FC134B 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-71


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
46387 0x18F2 Logic Element 12 Block 2 0 0xFFFF 1 --- FC134B 0 1
46388 0x18F3 Logic Element 12 Block 3 0 0xFFFF 1 --- FC134B 0 1
46389 0x18F4 Logic Element 13 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46390 0x18F5 Logic Element 13 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46391 0x18F6 Logic Element 13 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46392 0x18F7 Logic Element 13 Block 1 0 0xFFFF 1 --- FC134B 0 1
46393 0x18F8 Logic Element 13 Block 2 0 0xFFFF 1 --- FC134B 0 1
46394 0x18F9 Logic Element 13 Block 3 0 0xFFFF 1 --- FC134B 0 1
46395 0x18FA Logic Element 14 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46396 0x18FB Logic Element 14 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46397 0x18FC Logic Element 14 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46398 0x18FD Logic Element 14 Block 1 0 0xFFFF 1 --- FC134B 0 1
46399 0x18FE Logic Element 14 Block 2 0 0xFFFF 1 --- FC134B 0 1
46400 0x18FF Logic Element 14 Block 3 0 0xFFFF 1 --- FC134B 0 1
46401 0x1900 Logic Element 15 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46402 0x1901 Logic Element 15 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46403 0x1902 Logic Element 15 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46404 0x1903 Logic Element 15 Block 1 0 0xFFFF 1 --- FC134B 0 1
46405 0x1904 Logic Element 15 Block 2 0 0xFFFF 1 --- FC134B 0 1
46406 0x1905 Logic Element 15 Block 3 0 0xFFFF 1 --- FC134B 0 1
46407 0x1906 Logic Element 16 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46408 0x1907 Logic Element 16 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46409 0x1908 Logic Element 16 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46410 0x1909 Logic Element 16 Block 1 0 0xFFFF 1 --- FC134B 0 1
46411 0x190A Logic Element 16 Block 2 0 0xFFFF 1 --- FC134B 0 1
46412 0x190B Logic Element 16 Block 3 0 0xFFFF 1 --- FC134B 0 1
47012 0x1B63 Logic Element 1 Number of 2 8 1 --- F1 3 1
Triggers
47013 0x1B64 Logic Element 1 Number of 2 4 1 --- F1 3 1
Blocks
47014 0x1B65 Logic Element 1 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47015 0x1B66 Logic Element 1 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47016 0x1B67 Logic Element 1 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47017 0x1B68 Logic Element 1 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47018 0x1B69 Logic Element 1 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47019 0x1B6A Logic Element 1 Block 4 0 0xFFFF 1 --- FC134B 0 1
47020 0x1B6B Logic Element 2 Number of 2 8 1 --- F1 3 1
Triggers
47021 0x1B6C Logic Element 2 Number of 2 4 1 --- F1 3 1
Blocks
47022 0x1B6D Logic Element 2 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47023 0x1B6E Logic Element 2 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47024 0x1B6F Logic Element 2 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47025 0x1B70 Logic Element 2 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47026 0x1B71 Logic Element 2 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47027 0x1B72 Logic Element 2 Block 4 0 0xFFFF 1 --- FC134B 0 1

11-72 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
47028 0x1B73 Logic Element 3 Number of 2 8 1 --- F1 3 1
Triggers
47029 0x1B74 Logic Element 3 Number of 2 4 1 --- F1 3 1
Blocks
47030 0x1B75 Logic Element 3 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47031 0x1B76 Logic Element 3 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47032 0x1B77 Logic Element 3 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47033 0x1B78 Logic Element 3 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47034 0x1B79 Logic Element 3 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47035 0x1B7A Logic Element 3 Block 4 0 0xFFFF 1 --- FC134B 0 1
47036 0x1B7B Logic Element 4 Number of 2 8 1 --- F1 3 1
Triggers
47037 0x1B7C Logic Element 4 Number of 2 4 1 --- F1 3 1
Blocks
47038 0x1B7D Logic Element 4 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47039 0x1B7E Logic Element 4 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47040 0x1B7F Logic Element 4 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47041 0x1B80 Logic Element 4 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47042 0x1B81 Logic Element 4 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47043 0x1B82 Logic Element 4 Block 4 0 0xFFFF 1 --- FC134B 0 1
47044 0x1B83 Logic Element 5 Number of 2 8 1 --- F1 3 1
Triggers
47045 0x1B84 Logic Element 5 Number of 2 4 1 --- F1 3 1
Blocks
47046 0x1B85 Logic Element 5 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47047 0x1B86 Logic Element 5 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47048 0x1B87 Logic Element 5 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47049 0x1B88 Logic Element 5 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47050 0x1B89 Logic Element 5 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47051 0x1B8A Logic Element 5 Block 4 0 0xFFFF 1 --- FC134B 0 1
47052 0x1B8B Logic Element 6 Number of 2 8 1 --- F1 3 1
Triggers
47053 0x1B8C Logic Element 6 Number of 2 4 1 --- F1 3 1
Blocks
47054 0x1B8D Logic Element 6 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47055 0x1B8E Logic Element 6 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47056 0x1B8F Logic Element 6 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47057 0x1B90 Logic Element 6 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47058 0x1B91 Logic Element 6 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47059 0x1B92 Logic Element 6 Block 4 0 0xFFFF 1 --- FC134B 0 1
47060 0x1B93 Logic Element 7 Number of 2 8 1 --- F1 3 1
Triggers
47061 0x1B94 Logic Element 7 Number of 2 4 1 --- F1 3 1
Blocks
47062 0x1B95 Logic Element 7 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47063 0x1B96 Logic Element 7 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47064 0x1B97 Logic Element 7 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47065 0x1B98 Logic Element 7 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47066 0x1B99 Logic Element 7 Trigger 8 0 0xFFFF 1 --- FC134B 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-73


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
47067 0x1B9A Logic Element 7 Block 4 0 0xFFFF 1 --- FC134B 0 1
47068 0x1B9B Logic Element 8 Number of 2 8 1 --- F1 3 1
Triggers
47069 0x1B9C Logic Element 8 Number of 2 4 1 --- F1 3 1
Blocks
47070 0x1B9D Logic Element 8 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47071 0x1B9E Logic Element 8 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47072 0x1B9F Logic Element 8 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47073 0x1BA0 Logic Element 8 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47074 0x1BA1 Logic Element 8 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47075 0x1BA2 Logic Element 8 Block 4 0 0xFFFF 1 --- FC134B 0 1
47076 0x1BA3 Logic Element 9 Number of 2 8 1 --- F1 3 1
Triggers
47077 0x1BA4 Logic Element 9 Number of 2 4 1 --- F1 3 1
Blocks
47078 0x1BA5 Logic Element 9 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47079 0x1BA6 Logic Element 9 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47080 0x1BA7 Logic Element 9 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47081 0x1BA8 Logic Element 9 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47082 0x1BA9 Logic Element 9 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47083 0x1BAA Logic Element 9 Block 4 0 0xFFFF 1 --- FC134B 0 1
47084 0x1BAB Logic Element 10 Number of 2 8 1 --- F1 3 1
Triggers
47085 0x1BAC Logic Element 10 Number of 2 4 1 --- F1 3 1
Blocks
47086 0x1BAD Logic Element 10 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47087 0x1BAE Logic Element 10 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47088 0x1BAF Logic Element 10 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47089 0x1BB0 Logic Element 10 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47090 0x1BB1 Logic Element 10 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47091 0x1BB2 Logic Element 10 Block 4 0 0xFFFF 1 --- FC134B 0 1
47092 0x1BB3 Logic Element 11 Number of 2 8 1 --- F1 3 1
Triggers
47093 0x1BB4 Logic Element 11 Number of 2 4 1 --- F1 3 1
Blocks
47094 0x1BB5 Logic Element 11 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47095 0x1BB6 Logic Element 11 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47096 0x1BB7 Logic Element 11 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47097 0x1BB8 Logic Element 11 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47098 0x1BB9 Logic Element 11 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47099 0x1BBA Logic Element 11 Block 4 0 0xFFFF 1 --- FC134B 0 1
47100 0x1BBB Logic Element 12 Number of 2 8 1 --- F1 3 1
Triggers
47101 0x1BBC Logic Element 12 Number of 2 4 1 --- F1 3 1
Blocks
47102 0x1BBD Logic Element 12 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47103 0x1BBE Logic Element 12 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47104 0x1BBF Logic Element 12 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47105 0x1BC0 Logic Element 12 Trigger 7 0 0xFFFF 1 --- FC134B 0 1

11-74 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
47106 0x1BC1 Logic Element 12 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47107 0x1BC2 Logic Element 12 Block 4 0 0xFFFF 1 --- FC134B 0 1
47108 0x1BC3 Logic Element 13 Number of 2 8 1 --- F1 3 1
Triggers
47109 0x1BC4 Logic Element 13 Number of 2 4 1 --- F1 3 1
Blocks
47110 0x1BC5 Logic Element 13 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47111 0x1BC6 Logic Element 13 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47112 0x1BC7 Logic Element 13 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47113 0x1BC8 Logic Element 13 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47114 0x1BC9 Logic Element 13 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47115 0x1BCA Logic Element 13 Block 4 0 0xFFFF 1 --- FC134B 0 1
47116 0x1BCB Logic Element 14 Number of 2 8 1 --- F1 3 1
Triggers
47117 0x1BCC Logic Element 14 Number of 2 4 1 --- F1 3 1
Blocks
47118 0x1BCD Logic Element 14 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47119 0x1BCE Logic Element 14 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47120 0x1BCF Logic Element 14 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47121 0x1BD0 Logic Element 14 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47122 0x1BD1 Logic Element 14 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47123 0x1BD2 Logic Element 14 Block 4 0 0xFFFF 1 --- FC134B 0 1
47124 0x1BD3 Logic Element 15 Number of 2 8 1 --- F1 3 1
Triggers
47125 0x1BD4 Logic Element 15 Number of 2 4 1 --- F1 3 1
Blocks
47126 0x1BD5 Logic Element 15 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47127 0x1BD6 Logic Element 15 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47128 0x1BD7 Logic Element 15 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47129 0x1BD8 Logic Element 15 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47130 0x1BD9 Logic Element 15 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47131 0x1BDA Logic Element 15 Block 4 0 0xFFFF 1 --- FC134B 0 1
47132 0x1BDB Logic Element 16 Number of 2 8 1 --- F1 3 1
Triggers
47133 0x1BDC Logic Element 16 Number of 2 4 1 --- F1 3 1
Blocks
47134 0x1BDD Logic Element 16 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47135 0x1BDE Logic Element 16 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47136 0x1BDF Logic Element 16 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47137 0x1BE0 Logic Element 16 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47138 0x1BE1 Logic Element 16 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47139 0x1BE2 Logic Element 16 Block 4 0 0xFFFF 1 --- FC134B 0 1
DEMAND
47189 0x1C14 Current Demand 1 Function 0 2 1 --- FC206 0 1
47191 0x1C16 Current Demand 1 0 2 1 --- FC431 0 1
Measurement Type
47192 0x1C17 Current Demand 1 90% 0 4 1 --- FC432 2 1
Response Time

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-75


345 MODBUS MEMORY MAP CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
47193 0x1C18 Current Demand 1 Time 0 4 1 --- FC432 3 1
Interval
47194 0x1C19 Current Demand 1 Pkp 10 10000 1 A F1 1000 1
47195 0x1C1A Current Demand 1 Relays 0 0x7F 1 --- FC198 0 1
47196 0x1C1B Current Demand 1 Block 1 0 0xEF02 1 --- F89 0 1
47197 0x1C1C Current Demand 1 Block 2 0 0xEF02 1 --- F89 0 1
47198 0x1C1D Current Demand 1 Block 3 0 0xEF02 1 --- F89 0 1
47199 0x1C1E Current Demand 2 Function 0 2 1 --- FC206 0 1
47201 0x1C20 Current Demand 2 0 2 1 --- FC431 0 1
Measurement Type
47202 0x1C21 Current Demand 2 90% 0 4 1 --- FC432 2 1
Response Time
47203 0x1C22 Current Demand 2 Time 0 4 1 --- FC432 3 1
Interval
47204 0x1C23 Current Demand 2 Pkp 10 10000 1 A F1 1000 1
47205 0x1C24 Current Demand 2 Relays 0 0x7F 1 --- FC198 0 1
47206 0x1C25 Current Demand 2 Block 1 0 0xEF02 1 --- F89 0 1
47207 0x1C26 Current Demand 2 Block 2 0 0xEF02 1 --- F89 0 1
47208 0x1C27 Current Demand 2 Block 3 0 0xEF02 1 --- F89 0 1
LOCKOUT
47242 0x1C49 Lockout Function 0 1 1 --- FC126 0 1
47243 0x1C4A Lockout Input 1 0 0xFFFF 1 --- FC134D 0 1
47244 0x1C4B Lockout Input 2 0 0xFFFF 1 --- FC134D 0 1
47245 0x1C4C Lockout Input 3 0 0xFFFF 1 --- FC134D 0 1
47246 0x1C4D Lockout Input 4 0 0xFFFF 1 --- FC134D 0 1
47247 0x1C4E Lockout Input 5 0 0xFFFF 1 --- FC134D 0 1
47248 0x1C4F Lockout Input 6 0 0xFFFF 1 --- FC134D 0 1
47249 0x1C50 Lockout Input 7 0 0xFFFF 1 --- FC134D 0 1
47250 0x1C51 Lockout Input 8 0 0xFFFF 1 --- FC134D 0 1
47251 0x1C52 Lockout Input 9 0 0xFFFF 1 --- FC134D 0 1
47252 0x1C53 Lockout Input 10 0 0xFFFF 1 --- FC134D 0 1
47253 0x1C54 Lockout Supervision 0 0xFFFF 1 --- FC134C 1 1
47254 0x1C55 Lockout Reset 0 0xFFFF 1 --- FC134F 0 1
47255 0x1C56 Lockout Reset From PB 0 1 1 --- FC126 0 1
Reset
47256 0x1C57 Lockout Block Reset Lockout 0 0xFFFF 1 --- FC134D 0x8002 1
47257 0x1C58 Lockout Block 1 0 0xEF02 1 --- F89 0 1
47258 0x1C59 Lockout Block 2 0 0xEF02 1 --- F89 0 1
47259 0x1C5A Lockout Block 3 0 0xEF02 1 --- F89 0 1
TESTING
47303 0x1C86 Force leds 0 1 --- FC126 0 1
47304 0x1C87 Led 1 0 1 --- FC103 0 1
47305 0x1C88 Led 2 0 1 --- FC103 0 1
47306 0x1C89 Led 3 0 1 --- FC103 0 1
47307 0x1C8A Led 4 0 1 --- FC103 0 1
47308 0x1C8B Led 5 0 1 --- FC103 0 1
47309 0x1C8C Led 6 0 1 --- FC103 0 1

11-76 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
47310 0x1C8D Led 7 0 1 --- FC103 0 1
47311 0x1C8E Led 8 0 1 --- FC103 0 1
47312 0x1C8F Led 9 0 1 --- FC103 0 1
47313 0x1C90 Led 10 0 1 --- FC103 0 1
47314 0x1C91 Led 11 0 1 --- FC103 0 1
47315 0x1C92 Led 12 0 1 --- FC103 0 1
47318 0x1C95 Force Output Relays 0 1 --- FC126 0 1
47319 0x1C96 Relay 1 Trip 0 1 --- FC103 0 1
47320 0x1C97 Relay 2 Close 0 1 --- FC103 0 1
47321 0x1C98 Relay 3 Auxiliary 0 1 --- FC103 0 1
47322 0x1C99 Relay 4 Auxiliary 0 1 --- FC103 0 1
47323 0x1C9A Relay 5 Auxiliary 0 1 --- FC103 0 1
47324 0x1C9B Relay 6 Auxiliary 0 1 --- FC103 0 1
61850 MAPPING
47327 0x1C9E Analog input 1 Value 0 251 1 --- F88 0 1
47328 0x1C9F Analog input 1 db 0 100000 1 % F17 0 2
47330 0x1CA1 Analog input 1 Min -2147483648 2147483647 1 --- F13 0 2
47332 0x1CA3 Analog input 1 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47334 0x1CA5 Analog input 2 Value 0 251 1 --- F88 0 1
47335 0x1CA6 Analog input 2 db 0 100000 1 % F17 0 2
47337 0x1CA8 Analog input 2 Min -2147483648 2147483647 1 --- F13 0 2
47339 0x1CAA Analog input 2 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47341 0x1CAC Analog input 3 Value 0 251 1 --- F88 0 1
47342 0x1CAD Analog input 3 db 0 100000 1 % F17 0 2
47344 0x1CAF Analog input 3 Min -2147483648 2147483647 1 --- F13 0 2
47346 0x1CB1 Analog input 3 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47348 0x1CB3 Analog input 4 Value 0 251 1 --- F88 0 1
47349 0x1CB4 Analog input 4 db 0 100000 1 % F17 0 2
47351 0x1CB6 Analog input 4 Min -2147483648 2147483647 1 --- F13 0 2
47353 0x1CB8 Analog input 4 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47355 0x1CBA Analog input 5 Value 0 251 1 --- F88 0 1
47356 0x1CBB Analog input 5 db 0 100000 1 % F17 0 2
47358 0x1CBD Analog input 5 Min -2147483648 2147483647 1 --- F13 0 2
47360 0x1CBF Analog input 5 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47362 0x1CC1 Analog input 6 Value 0 251 1 --- F88 0 1
47363 0x1CC2 Analog input 6 db 0 100000 1 % F17 0 2
47365 0x1CC4 Analog input 6 Min -2147483648 2147483647 1 --- F13 0 2
47367 0x1CC6 Analog input 6 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47369 0x1CC8 Analog input 7 Value 0 251 1 --- F88 0 1
47370 0x1CC9 Analog input 7 db 0 100000 1 % F17 0 2
47372 0x1CCB Analog input 7 Min -2147483648 2147483647 1 --- F13 0 2

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-77


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
47374 0x1CCD Analog input 7 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47376 0x1CCF Analog input 8 Value 0 251 1 --- F88 0 1
47377 0x1CD0 Analog input 8 db 0 100000 1 % F17 0 2
47379 0x1CD2 Analog input 8 Min -2147483648 2147483647 1 --- F13 0 2
47381 0x1CD4 Analog input 8 Max -2147483648 2147483647 1 --- F13 214748364 2
7

345 Format Codes


In some cases names of settings displayed in the HMI have been shortened. The Long
Definition column below contains the full name used in the Enervista Setup software, when
applicable. In many cases the long description is the same as the description.

Code Type Definition Long Definition


F1 unsigned 16 bits Unsigned Value
Example: 1234 stored as 1234
F1B unsigned 16 bits Unsigned Value Max Value = OFF
Example: 1234 stored as 1234
F1C unsigned 16 bits Unsigned Value Min Value = OFF
Example: 1234 stored as 1234
F2 unsigned 16 bits Unsigned Value 1 Decimal Place
Example: 123.4 stored as 1234
F2B unsigned 16 bits Unsigned Value 1 Decimal Place
Example: 123.4 stored as 1234
F3 unsigned 16 bits Unsigned Value 2 Decimal Places
Example: 12.34 stored as 1234
F3B unsigned 16 bits Unsigned Value 2 Decimal Places
Example: 12.34 stored as 1234
F4 signed 16 bits 2's Complement Signed Value
Example: -1234 stored as -1234 i.e. 64302
F4B signed 16 bits 2's Complement Signed Value Max Value
= OFF
Example: -1234 stored as -1234 i.e. 64302
F5 signed 16 bits 2's Complement Signed Value 1 Decimal
Place
Example: -123.4 stored as -1234 i.e. 64302
F6 signed 16 bits 2's Complement Signed Value 2 Decimal
Places
Example: -12.34 stored as -1234 i.e. 64302
F7 signed 16 bits 2's Complement Signed Value 3 Decimal
Places
Example: -1.234 stored as -1234 i.e. 64302
F8 signed 16 bits 2's Complement Signed Value 4 Decimal
Places
Example: -0.1234 stored as -1234 i.e. 64302

11-78 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


F9 unsigned 32 bits Unsigned Long Value
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: 123456 stored as 123456
i.e. 1st word: 0001 hex 2nd word: E240 hex
F10 unsigned 32 bits Unsigned Long Value 1 Decimal Place
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: 12345.6 stored as 123456
i.e. 1st word: 0001 hex 2nd word: E240 hex
F11 unsigned 32 bits Unsigned Long Value 1 Decimal Place
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: 1234.56 stored as 123456
i.e. 1st word: 0001 hex 2nd word: E240 hex
F12 signed 32 bits 2's Complement Signed Long Value
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: -123456 stored as -123456
i.e. 1st word: FFFE hex 2nd word: 1DC0 hex
F13 signed 32 bits 2's Complement Signed Long Value 1
Decimal Place
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: -12345.6 stored as -123456
i.e. 1st word: FFFE hex 2nd word: 1DC0 hex
F14 signed 32 bits 2's Complement Signed Long Value 2
Decimal Places
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: -1234.56 stored as -123456
i.e. 1st word: FFFE hex 2nd word: 1DC0 hex
F14A signed 32 bits 2's Complement Signed Long Value 3
Decimal Places
F15 unsigned 16 bits Hardware Revision
0 Prototype Prototype
1 A A
2 B B
3 C C
4 D D
5 E E
6 F F
7 G G
8 H H
9 I I
10 J J
11 K K
12 L L

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-79


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


13 M M
14 N N
15 O O
16 P P
17 Q Q
18 R R
19 S S
20 T T
21 U U
22 V V
23 W W
24 X X
25 Y Y
26 Z Z
F16 signed 16 bits 2's Complement Signed Value 1 Decimal
Place
F17 unsigned 32 bits Unsigned Long Value 3 Decimal Places
F17A unsigned 16 bits Unsigned Value 3 Decimal Places
F18 unsigned 32 bits Date MM/DD/YYYY
1st byte Month 1 to 12
2nd byte Day 1 to 31
3rd and 4th byte Year 2000 to 2099 2000 stored as 34867152 (i.e. 1st word: 0214 2nd word 07D0)
Example: Feb 20
F19 unsigned 32 bits Time HH:MM:SS.sss
1st byte Hours 0 to 23
2nd byte Minutes 0 to 59
3rd and 4th byte miliSeconds 0 to 59999
Example: 2:05pm stored as 235208704 (i.e. 1st word: 0E05 2nd word 0000)
F20 signed 32 bits 2's Complement Signed Long Value
F21 signed 16 bits 2's Complement Signed Value
F22 unsigned 16 bits Two 8-BIT Characters Packed Into 16-BIT
Unsigned
F23 unsigned 16 bits Unsigned Value
F24 unsigned 16 bits Unsigned Value AS Seconds SHOW AS
Duration
F24B unsigned 16 bits Unsigned Value AS Seconds SHOW AS
Duration
F25 unsigned 16 bits Trace Memory Channel Data
0 Leading Leading
1 Lagging Lagging
F26 unsigned 16 bits 350 Trace Memory Channel Data
F26A unsigned 16 bits 339 Trace Memory Channel Data
4 Not Used Not Used
5 Not Used Not Used
6 Ia Ia
7 Ib Ib
8 Ic Ic
9 Ig Ig

11-80 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


10 Inputs 1-16 Inputs 1-16
11 Outputs 1-16 Outputs 1-16
12 Virtual Inputs1-16 Virtual Inputs 1-16
13 Virtual Inputs7-32 Virtual Inputs 17-32
14 Remote INs 1-16 Remote Inputs 1-16
15 Remote INs 17-32 Remote Inputs 17-32
16 Logic Elements Logic Elements
F26B unsigned 16 bits 345 Trace Memory Channel Data
0 W2 Ia W2 Ia
1 W2 Ib W2 Ib
2 W2 Ic W2 Ic
3 W2 Ig W2 Ig
4 Not Used Not Used
5 Not Used Not Used
6 W1 Ia W1 Ia
7 W1 Ib W1 Ib
8 W1 Ic W1 Ic
9 W1 Ig W1 Ig
10 Inputs 1-16 Inputs 1-16
11 Outputs 1-16 Outputs 1-16
12 Virtual Inputs1-16 Virtual Inputs 1-16
13 Virtual Inputs7-32 Virtual Inputs 17-32
14 Remote INs 1-16 Remote Inputs 1-16
15 Remote INs 17-32 Remote Inputs 17-32
16 Logic Elements Logic Elements
F27 unsigned 32 bits Unsigned Long Value
F36 unsigned 16 bits OC Curve Selection
0 Extremely Inverse Extremely Inverse
1 Very Inverse Very Inverse
2 Normally Inverse Normally Inverse
3 Moderately Inverse Moderately Inverse
4 Definite Time Definite Time
5 IEC Curve A IEC Curve A
6 IEC Curve B IEC Curve B
7 IEC Curve C IEC Curve C
10 IAC Extr. Inverse IAC Extremely Inverse
11 IAC Very Inverse IAC Very Inverse
12 IAC Inverse IAC Inverse
13 IAC Short Inverse IAC Short Inverse
14 IEC Short Inverse IEC Short Inverse
F37 unsigned 16 bits OC Pickup flags
1 Phase A Phase A
2 Phase B Phase B
4 Phase C Phase C
7 All Phases All Phases
F38 unsigned 16 bits OC Direction pickup flags
0x10 Direction PKP Ph A Direction PKP Phase A

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-81


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x20 Direction PKP Ph B Direction PKP Phase B
0x40 Direction PKP Ph C Direction PKP Phase C
0x80 Direction Pickup Direction Pickup
0xF0 Direction Direction
F48 unsigned 16 bits Simulation Status
0 Disabled Disabled
1 Prefault State Prefault State
2 Fault State Fault State
3 Postfault State Postfault State
F68 unsigned 16 bits Reset Time Model
0 Instantaneous Instantaneous
1 Linear Linear
F74 unsigned 16 bits Data Logger Sample Rate
0 1 Cycle 1 Cycle
1 1 Second 1 Second
2 1 Minute 1 Minute
3 1 Hour 1 Hour
F75 unsigned 16 bits Data Logger Status
0 Stopped Stopped
1 Started Started
2 Triggered Triggered
3 Pretrigger Pretrigger
4 PostTrigger PostTrigger
F76 unsigned 16 bits Overcurrent Direction
0 Disabled Disabled
1 Forward Forward
2 Reverse Reverse
F77 unsigned 16 bits Data Logger Channel Data
0 Disabled Disabled
1 Phase A Current Phase A Current
2 Phase B Current Phase B Current
3 Phase C Current Phase C Current
4 Avg Phase Current Average Phase Current
6 Current Unbalance Current Unbalance
7 Gnd Current Gnd Current
8 System Frequency System Frequency
22 Vbc S2 Vbc S2
F77B unsigned 16 bits 345 Data Logger Channel Data
0 Disabled Disabled
1 W1 Phase A Current W1 Phase A Current
2 W1 Phase B Current W1 Phase B Current
3 W1 Phase C Current W1 Phase C Current
4 W1 Curr Unbalance W1 Current Unbalance
5 W1 Gnd Current W1 Ground Current
6 W1 Therm Cap. Used W1 Thermal Capacity Used
7 W2 Phase A Current W2 Phase A Current
8 W2 Phase B Current W2 Phase B Current

11-82 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


9 W2 Phase C Current W2 Phase C Current
10 W2 Curr Unbalance W2 Current Unbalance
11 W2 Gnd Current W2 Ground Current
12 W2 Therm Cap. Used W2 Therm Capacity Used
F78 unsigned 16 bits DNP Object 20 Default Variation
1 1 (1) 32-Bit Binary Counter
2 2 (2) 16-Bit Binary Counter
5 5 (5) 32-Bit Binary Counter w/o Flag
6 6 (6) 16-Bit Binary Counter w/o Flag
F79 unsigned 16 bits DNP Object 21 Default Variation
1 1 (1) 32-Bit Frozen Counter
2 2 (2) 16-Bit Frozen Counter
9 9 (9) 32-Bit Frozen Counter w/o Flag
10 10 (10) 16-Bit Frozen Counter w/o Flag
F80 unsigned 16 bits DNP Object 22 Default Variation
1 1 (1) 32-Bit Counter Change Event
2 2 (2) 16-Bit Counter Change Event
5 5 (5) 32-Bit Counter Change Event w Time
6 6 (6) 16-Bit Counter Change Event w Time
F81 unsigned 16 bits DNP Object 23 Default Variation
1 1 (1) 32-Bit Frozen Counter Event
2 2 (2) 16-Bit Frozen Counter Event
5 5 (5) 32-Bit Frozen Counter Event w Time
6 6 (6) 16-Bit Frozen Counter Event w Time
F82 unsigned 16 bits DNP Object 30 Default Variation
1 1 (1) 32-Bit Analog Input
2 2 (2) 16-Bit Analog Input
3 3 (3) 32-Bit Analog Input w/o Flag
4 4 (4) 16-Bit Analog Input w/o Flag
F83 unsigned 16 bits DNP Object 32 Default Variation
1 1 (1) 32-Bit Analog Change Event w/o Time
2 2 (2) 16-Bit Analog Change Event w/o Time
3 3 (3) 32-Bit Analog Change Event w Time
4 4 (4) 16-Bit Analog Change Event w Time
F85 unsigned 16 bits DNP Analog Input Point Scale Factor
1 / 0.001 / 0.001
2 / 0.01 / 0.01
3 / 0.1 / 0.1
4 /1 /1
5 / 10 / 10
6 / 100 / 100
7 / 1000 / 1000
8 / 10000 / 10000
9 / 100000 / 100000
F86 unsigned 16 bits DNP and 103 Binary Output Points
0 Off Off
1 Virtual Input 1 Virtual Input 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-83


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


2 Virtual Input 2 Virtual Input 2
3 Virtual Input 3 Virtual Input 3
4 Virtual Input 4 Virtual Input 4
5 Virtual Input 5 Virtual Input 5
6 Virtual Input 6 Virtual Input 6
7 Virtual Input 7 Virtual Input 7
8 Virtual Input 8 Virtual Input 8
9 Virtual Input 9 Virtual Input 9
10 Virtual Input 10 Virtual Input 10
11 Virtual Input 11 Virtual Input 11
12 Virtual Input 12 Virtual Input 12
13 Virtual Input 13 Virtual Input 13
14 Virtual Input 14 Virtual Input 14
15 Virtual Input 15 Virtual Input 15
16 Virtual Input 16 Virtual Input 16
17 Virtual Input 17 Virtual Input 17
18 Virtual Input 18 Virtual Input 18
19 Virtual Input 19 Virtual Input 19
20 Virtual Input 20 Virtual Input 20
21 Virtual Input 21 Virtual Input 21
22 Virtual Input 22 Virtual Input 22
23 Virtual Input 23 Virtual Input 23
24 Virtual Input 24 Virtual Input 24
25 Virtual Input 25 Virtual Input 25
26 Virtual Input 26 Virtual Input 26
27 Virtual Input 27 Virtual Input 27
28 Virtual Input 28 Virtual Input 28
29 Virtual Input 29 Virtual Input 29
30 Virtual Input 30 Virtual Input 30
31 Virtual Input 31 Virtual Input 31
32 Virtual Input 32 Virtual Input 32
33 FC: Reset Force Coil: Reset
36 FC: Display Msg Force Coil: Display Message
37 FC: Clear Curr Dmd1 Force Coil: Clear Current Dmd1
38 FC: Clear Curr Dmd2 Force Coil: Clear Current Dmd2
40 FC:Clear Fault Rep FC:Clear Fault Rep
F87 unsigned 16 bits DNP/Ethernet Channel Port
0 None None
1 TCP TCP
2 UDP UDP
F88 unsigned 16 bits Analog Values
0 Disabled Disabled
1 Phase A Current Phase A Current
2 Phase B Current Phase B Current
3 Phase C Current Phase C Current
7 Gnd Current Gnd Current
23 Therm Cap. Phase A Thermal Capacity Phase A

11-84 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


24 Therm Cap. Phase B Thermal Capacity Phase B
25 Therm Cap. Phase C Thermal Capacity Phase C
26 Ntrl Current Ntrl Current
29 NSeq Current Negative Sequence Current
30 W2 Phase A Current W2 Phase A Current
31 W2 Phase B Current W2 Phase B Current
32 W2 Phase C Current W2 Phase C Current
33 W2 Gnd Current W2 Ground Current
34 W2 SGnd Current W2 Sensitive Ground Current
35 Ph A Diff Current Phase A Differential Current
36 Ph B Diff Current Phase B Differential Current
37 Ph C Diff Current Phase C Differential Current
38 Ph A RESTR Current Phase A Restraint Current
39 Ph B RESTR Current Phase B Restraint Current
40 Ph C RESTR Current Phase C Restraint Current
41 W1 Gnd Dif Current W1 Ground Differential Current
42 W2 Gnd Dif Current W2 Ground Differential Current
43 SGnd Current Sensitive Ground Current
44 NSeq Current W2 Negative Sequence Current
45 Ntrl Current W2 Ntrl Current W2
60 FR Date (Upper 16) Fault Report Date (Upper 16)
61 FR Date (Lower 16) Fault Report Date (Lower 16)
62 FR Time (Upper 16) Fault Report Time (Upper 16)
63 FR Time (Lower 16) Fault Report Time (Lower 16)
64 FR Fault Type Fault Report Fault Type
65 FR Ia Fault Report Ia
66 FR Ia Angle Fault Report Ia Angle
67 FR Ib Fault Report Ib
68 FR Ib Angle Fault Report Ib Angle
69 FR Ic Fault Report Ic
70 FR Ic Angle Fault Report Ic Angle
71 FR Ig Fault Report Ig
72 FR Ig Angle Fault Report Ig Angle
73 FR In Fault Report In
74 FR In Angle Fault Report In Angle
91 FR System Freq Fault Report System Frequency
92 FR Ia 2 Fault Report Ia 2
93 FR Ia 2 Angle Fault Report Ia 2 Angle
94 FR Ib 2 Fault Report Ib 2
95 FR Ib 2 Angle Fault Report Ib 2 Angle
96 FR Ic 2 Fault Report Ic 2
97 FR Ic 2 Angle Fault Report Ic 2 Angle
98 FR Ig 2 Fault Report Ig 2
99 FR Ig 2 Angle Fault Report Ig 2 Angle
100 FR In 2 Fault Report In 2
101 FR In 2 Angle Fault Report In 2 Angle
102 FR Idiff 1 PhA Fault Report Idiff 1 PhA

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-85


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


103 FR Idiff 1 PhA Ang Fault Report Idiff 1 PhA Angle
104 FR I Restr PhA Fault Report I Restraint PhA
105 FR I Restr PhA Ang Fault Report I Restraint PhA Angle
106 FR Idiff 1 PhB Fault Report Idiff 1 PhB
107 FR Idiff 1 PhB Ang Fault Report Idiff 1 PhB Angle
108 FR I Restr Ph B Fault Report I Restraint Ph B
109 FR I Restr PhB Ang Fault Report I Restraint PhB Angle
110 FR Idiff 1 PhC Fault Report Idiff 1 PhC
111 FR Idiff 1 PhC Ang Fault Report Idiff 1 PhC Angle
112 FR I Restr PhC Fault Report I Restraint PhC
113 FR I Restr PhC Ang Fault Report I Restraint PhC Angle
114 FR Phases Fault Report Phases
115 Current Dmd 1 PhA Current Demand 1 PhA
116 Current Dmd 1 PhB Current Demand 1 PhB
117 Current Dmd 1 PhC Current Demand 1 PhC
118 Max Curr Dmd1 PhA Max Current Demand 1 PhA
119 Max Curr Dmd1 PhB Max Current Demand 1 PhB
120 Max Curr Dmd1 PhC Max Current Demand 1 PhC
121 Current Dmd 2 PhA Current Demand 2 PhA
122 Current Dmd 2 PhB Current Demand 2 PhB
123 Current Dmd 2 PhC Current Demand 2 PhC
124 Max Curr Dmd2 PhA Max Current Demand 2 PhA
125 Max Curr Dmd2 PhB Max Current Demand 2 PhB
126 Max Curr Dmd2 PhC Max Current Demand 2 PhC
133 Total Num of Trips Total Num of Trips
154 Curr Unbalance Current Unbalance
155 PhA Curr Angle PhA Current Angle
156 PhB Curr Angle PhB Current Angle
157 PhC Curr Angle PhC Current Angle
161 Ig Angle Ig Angle
162 In Angle In Angle
172 RTD 7 Temp RTD 7 Temp
173 RTD 8 Temp RTD 8 Temp
174 RTD 9 Temp RTD 9 Temp
175 RTD 10 Temp RTD 10 Temp
176 RTD 11 Temp RTD 11 Temp
177 RTD 12 Temp RTD 12 Temp
178 Internal Temp Internal Temp
181 RTD 1 Temp RTD 1 Temp
182 RTD 2 Temp RTD 2 Temp
183 RTD 3 Temp RTD 3 Temp
184 RTD 4 Temp RTD 4 Temp
185 RTD 5 Temp RTD 5 Temp
186 RTD 6 Temp RTD 6 Temp
187 Ambient Temp Ambient Temperature
188 Internal Temp Max Internal Temperature Max
190 Neg Seq I Angle Negative Sequence I Angle

11-86 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


207 Idiff 2 Ph A Idiff 2 Ph A
208 Idiff 2 Ph B Idiff 2 Ph B
209 Idiff 2 Ph C Idiff 2 Ph C
210 Idiff 5 Ph A Idiff 5 Ph A
211 Idiff 5 Ph B Idiff 5 Ph B
212 Idiff 5 Ph C Idiff 5 Ph C
213 Ia2 Angle Ia2 Angle
214 Ib2 Angle Ib2 Angle
215 Ic2 Angle Ic2 Angle
216 Ig2 Angle Ig2 Angle
217 In2 Angle In2 Angle
218 Idiff 1 PhA Angle Idiff 1 PhA Angle
219 Idiff 1 PhB Angle Idiff 1 PhB Angle
220 Idiff 1 PhC Angle Idiff 1 PhC Angle
221 Idiff 2 PhA Angle Idiff 2 PhA Angle
222 Idiff 2 PhB Angle Idiff 2 PhB Angle
223 Idiff 2 PhC Angle Idiff 2 PhC Angle
224 Idiff 5 PhA Angle Idiff 5 PhA Angle
225 Idiff 5 PhB Angle Idiff 5 PhB Angle
226 Idiff 5 PhC Angle Idiff 5 PhC Angle
227 Irestraint A Angle Irestraint A Angle
228 Irestraint B Angle Irestraint B Angle
229 Irestraint C Angle Irestraint C Angle
232 W2 Neg Seq Angle W2 Negative Sequence Angle
235 W1 Gnd Dif Angle W1 Ground Dif Angle
236 W2 Gnd Dif Angle W2 Ground Dif Angle
237 BKR Health Breaker Health
238 BKR Last Trip Time Breaker Last Trip Time
239 BKR Avg Trip Time Breaker Average Trip Time
240 BKR Last Close Time Breaker Last Close Time
241 BKR Avg Close Time Breaker Average Close Time
242 BKR Last Charge Time Breaker Last Charge Time
243 BKR Avg Charge Time Breaker Average Charge Time
244 W2BKR Health W2 Breaker Health
245 W2BKR Last Trip Time W2 Breaker Last Trip Time
246 W2BKR Avg Trip Time W2 Breaker Average Trip Time
247 W2BKR Last Clse Time W2 Breaker Last Close Time
248 W2BKR Avg Clse Time W2 Breaker Average Close Time
249 W2BKR Last Chrg Time W2 Breaker Last Charge Time
250 W2BKR Avg Chrg Time W2 Breaker Average Charge Time
251 W2BKR Tot Num Trips W2 Breaker Total Number of Trips
F89 unsigned 16 bits Autoreclose Block
0 Off Off
1 On On
0x40 Contact Input 1 Contact Input 1
0x41 Contact Input 2 Contact Input 2
0x42 Contact Input 3 Contact Input 3

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-87


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x43 Contact Input 4 Contact Input 4
0x44 Contact Input 5 Contact Input 5
0x45 Contact Input 6 Contact Input 6
0x46 Contact Input 7 Contact Input 7
0x47 Contact Input 8 Contact Input 8
0x48 Contact Input 9 Contact Input 9
0x49 Contact Input 10 Contact Input 10
0x80 Virtual Input 1 Virtual Input 1
0x81 Virtual Input 2 Virtual Input 2
0x82 Virtual Input 3 Virtual Input 3
0x83 Virtual Input 4 Virtual Input 4
0x84 Virtual Input 5 Virtual Input 5
0x85 Virtual Input 6 Virtual Input 6
0x86 Virtual Input 7 Virtual Input 7
0x87 Virtual Input 8 Virtual Input 8
0x88 Virtual Input 9 Virtual Input 9
0x89 Virtual Input 10 Virtual Input 10
0x8A Virtual Input 11 Virtual Input 11
0x8B Virtual Input 12 Virtual Input 12
0x8C Virtual Input 13 Virtual Input 13
0x8D Virtual Input 14 Virtual Input 14
0x8E Virtual Input 15 Virtual Input 15
0x8F Virtual Input 16 Virtual Input 16
0x90 Virtual Input 17 Virtual Input 17
0x91 Virtual Input 18 Virtual Input 18
0x92 Virtual Input 19 Virtual Input 19
0x93 Virtual Input 20 Virtual Input 20
0x94 Virtual Input 21 Virtual Input 21
0x95 Virtual Input 22 Virtual Input 22
0x96 Virtual Input 23 Virtual Input 23
0x97 Virtual Input 24 Virtual Input 24
0x98 Virtual Input 25 Virtual Input 25
0x99 Virtual Input 26 Virtual Input 26
0x9A Virtual Input 27 Virtual Input 27
0x9B Virtual Input 28 Virtual Input 28
0x9C Virtual Input 29 Virtual Input 29
0x9D Virtual Input 30 Virtual Input 30
0x9E Virtual Input 31 Virtual Input 31
0x9F Virtual Input 32 Virtual Input 32
0xC0 Logic Element 1 Logic Element 1
0xC1 Logic Element 2 Logic Element 2
0xC2 Logic Element 3 Logic Element 3
0xC3 Logic Element 4 Logic Element 4
0xC4 Logic Element 5 Logic Element 5
0xC5 Logic Element 6 Logic Element 6
0xC6 Logic Element 7 Logic Element 7
0xC7 Logic Element 8 Logic Element 8

11-88 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0xC8 Logic Element 9 Logic Element 9
0xC9 Logic Element 10 Logic Element 10
0xCA Logic Element 11 Logic Element 11
0xCB Logic Element 12 Logic Element 12
0xCC Logic Element 13 Logic Element 13
0xCD Logic Element 14 Logic Element 14
0xCE Logic Element 15 Logic Element 15
0xCF Logic Element 16 Logic Element 16
0x1C0 Remote Input 1 Remote Input 1
0x1C1 Remote Input 2 Remote Input 2
0x1C2 Remote Input 3 Remote Input 3
0x1C3 Remote Input 4 Remote Input 4
0x1C4 Remote Input 5 Remote Input 5
0x1C5 Remote Input 6 Remote Input 6
0x1C6 Remote Input 7 Remote Input 7
0x1C7 Remote Input 8 Remote Input 8
0x1C8 Remote Input 9 Remote Input 9
0x1C9 Remote Input 10 Remote Input 10
0x1CA Remote Input 11 Remote Input 11
0x1CB Remote Input 12 Remote Input 12
0x1CC Remote Input 13 Remote Input 13
0x1CD Remote Input 14 Remote Input 14
0x1CE Remote Input 15 Remote Input 15
0x1CF Remote Input 16 Remote Input 16
0x1D0 Remote Input 17 Remote Input 17
0x1D1 Remote Input 18 Remote Input 18
0x1D2 Remote Input 19 Remote Input 19
0x1D3 Remote Input 20 Remote Input 20
0x1D4 Remote Input 21 Remote Input 21
0x1D5 Remote Input 22 Remote Input 22
0x1D6 Remote Input 23 Remote Input 23
0x1D7 Remote Input 24 Remote Input 24
0x1D8 Remote Input 25 Remote Input 25
0x1D9 Remote Input 26 Remote Input 26
0x1DA Remote Input 27 Remote Input 27
0x1DB Remote Input 28 Remote Input 28
0x1DC Remote Input 29 Remote Input 29
0x1DD Remote Input 30 Remote Input 30
0x1DE Remote Input 31 Remote Input 31
0x1DF Remote Input 32 Remote Input 32
F89A unsigned 16 bits BKR Health Charge Input
0 Off Off
0x40 Contact Input 1 Contact Input 1
0x41 Contact Input 2 Contact Input 2
0x42 Contact Input 3 Contact Input 3
0x43 Contact Input 4 Contact Input 4
0x44 Contact Input 5 Contact Input 5

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-89


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x45 Contact Input 6 Contact Input 6
0x46 Contact Input 7 Contact Input 7
0x47 Contact Input 8 Contact Input 8
0x48 Contact Input 9 Contact Input 9
0x49 Contact Input 10 Contact Input 10
0x80 Virtual Input 1 Virtual Input 1
0x81 Virtual Input 2 Virtual Input 2
0x82 Virtual Input 3 Virtual Input 3
0x83 Virtual Input 4 Virtual Input 4
0x84 Virtual Input 5 Virtual Input 5
0x85 Virtual Input 6 Virtual Input 6
0x86 Virtual Input 7 Virtual Input 7
0x87 Virtual Input 8 Virtual Input 8
0x88 Virtual Input 9 Virtual Input 9
0x89 Virtual Input 10 Virtual Input 10
0x8A Virtual Input 11 Virtual Input 11
0x8B Virtual Input 12 Virtual Input 12
0x8C Virtual Input 13 Virtual Input 13
0x8D Virtual Input 14 Virtual Input 14
0x8E Virtual Input 15 Virtual Input 15
0x8F Virtual Input 16 Virtual Input 16
0x90 Virtual Input 17 Virtual Input 17
0x91 Virtual Input 18 Virtual Input 18
0x92 Virtual Input 19 Virtual Input 19
0x93 Virtual Input 20 Virtual Input 20
0x94 Virtual Input 21 Virtual Input 21
0x95 Virtual Input 22 Virtual Input 22
0x96 Virtual Input 23 Virtual Input 23
0x97 Virtual Input 24 Virtual Input 24
0x98 Virtual Input 25 Virtual Input 25
0x99 Virtual Input 26 Virtual Input 26
0x9A Virtual Input 27 Virtual Input 27
0x9B Virtual Input 28 Virtual Input 28
0x9C Virtual Input 29 Virtual Input 29
0x9D Virtual Input 30 Virtual Input 30
0x9E Virtual Input 31 Virtual Input 31
0x9F Virtual Input 32 Virtual Input 32
0xC0 Logic Element 1 Logic Element 1
0xC1 Logic Element 2 Logic Element 2
0xC2 Logic Element 3 Logic Element 3
0xC3 Logic Element 4 Logic Element 4
0xC4 Logic Element 5 Logic Element 5
0xC5 Logic Element 6 Logic Element 6
0xC6 Logic Element 7 Logic Element 7
0xC7 Logic Element 8 Logic Element 8
0xC8 Logic Element 9 Logic Element 9
0xC9 Logic Element 10 Logic Element 10

11-90 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0xCA Logic Element 11 Logic Element 11
0xCB Logic Element 12 Logic Element 12
0xCC Logic Element 13 Logic Element 13
0xCD Logic Element 14 Logic Element 14
0xCE Logic Element 15 Logic Element 15
0xCF Logic Element 16 Logic Element 16
0x1C0 Remote Input 1 Remote Input 1
0x1C1 Remote Input 2 Remote Input 2
0x1C2 Remote Input 3 Remote Input 3
0x1C3 Remote Input 4 Remote Input 4
0x1C4 Remote Input 5 Remote Input 5
0x1C5 Remote Input 6 Remote Input 6
0x1C6 Remote Input 7 Remote Input 7
0x1C7 Remote Input 8 Remote Input 8
0x1C8 Remote Input 9 Remote Input 9
0x1C9 Remote Input 10 Remote Input 10
0x1CA Remote Input 11 Remote Input 11
0x1CB Remote Input 12 Remote Input 12
0x1CC Remote Input 13 Remote Input 13
0x1CD Remote Input 14 Remote Input 14
0x1CE Remote Input 15 Remote Input 15
0x1CF Remote Input 16 Remote Input 16
0x1D0 Remote Input 17 Remote Input 17
0x1D1 Remote Input 18 Remote Input 18
0x1D2 Remote Input 19 Remote Input 19
0x1D3 Remote Input 20 Remote Input 20
0x1D4 Remote Input 21 Remote Input 21
0x1D5 Remote Input 22 Remote Input 22
0x1D6 Remote Input 23 Remote Input 23
0x1D7 Remote Input 24 Remote Input 24
0x1D8 Remote Input 25 Remote Input 25
0x1D9 Remote Input 26 Remote Input 26
0x1DA Remote Input 27 Remote Input 27
0x1DB Remote Input 28 Remote Input 28
0x1DC Remote Input 29 Remote Input 29
0x1DD Remote Input 30 Remote Input 30
0x1DE Remote Input 31 Remote Input 31
0x1DF Remote Input 32 Remote Input 32
F89B unsigned 16 bits Start Thermal Protection
0 Off Off
1 On On
0x40 Contact Input 1 Contact Input 1
0x41 Contact Input 2 Contact Input 2
0x42 Contact Input 3 Contact Input 3
0x43 Contact Input 4 Contact Input 4
0x44 Contact Input 5 Contact Input 5
0x45 Contact Input 6 Contact Input 6

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-91


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x46 Contact Input 7 Contact Input 7
0x47 Contact Input 8 Contact Input 8
0x48 Contact Input 9 Contact Input 9
0x49 Contact Input 10 Contact Input 10
0x80 Virtual Input 1 Virtual Input 1
0x81 Virtual Input 2 Virtual Input 2
0x82 Virtual Input 3 Virtual Input 3
0x83 Virtual Input 4 Virtual Input 4
0x84 Virtual Input 5 Virtual Input 5
0x85 Virtual Input 6 Virtual Input 6
0x86 Virtual Input 7 Virtual Input 7
0x87 Virtual Input 8 Virtual Input 8
0x88 Virtual Input 9 Virtual Input 9
0x89 Virtual Input 10 Virtual Input 10
0x8A Virtual Input 11 Virtual Input 11
0x8B Virtual Input 12 Virtual Input 12
0x8C Virtual Input 13 Virtual Input 13
0x8D Virtual Input 14 Virtual Input 14
0x8E Virtual Input 15 Virtual Input 15
0x8F Virtual Input 16 Virtual Input 16
0x90 Virtual Input 17 Virtual Input 17
0x91 Virtual Input 18 Virtual Input 18
0x92 Virtual Input 19 Virtual Input 19
0x93 Virtual Input 20 Virtual Input 20
0x94 Virtual Input 21 Virtual Input 21
0x95 Virtual Input 22 Virtual Input 22
0x96 Virtual Input 23 Virtual Input 23
0x97 Virtual Input 24 Virtual Input 24
0x98 Virtual Input 25 Virtual Input 25
0x99 Virtual Input 26 Virtual Input 26
0x9A Virtual Input 27 Virtual Input 27
0x9B Virtual Input 28 Virtual Input 28
0x9C Virtual Input 29 Virtual Input 29
0x9D Virtual Input 30 Virtual Input 30
0x9E Virtual Input 31 Virtual Input 31
0x9F Virtual Input 32 Virtual Input 32
0xC0 Logic Element 1 Logic Element 1
0xC1 Logic Element 2 Logic Element 2
0xC2 Logic Element 3 Logic Element 3
0xC3 Logic Element 4 Logic Element 4
0xC4 Logic Element 5 Logic Element 5
0xC5 Logic Element 6 Logic Element 6
0xC6 Logic Element 7 Logic Element 7
0xC7 Logic Element 8 Logic Element 8
0xC8 Logic Element 9 Logic Element 9
0xC9 Logic Element 10 Logic Element 10
0xCA Logic Element 11 Logic Element 11

11-92 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0xCB Logic Element 12 Logic Element 12
0xCC Logic Element 13 Logic Element 13
0xCD Logic Element 14 Logic Element 14
0xCE Logic Element 15 Logic Element 15
0xCF Logic Element 16 Logic Element 16
0x1C0 Remote Input 1 Remote Input 1
0x1C1 Remote Input 2 Remote Input 2
0x1C2 Remote Input 3 Remote Input 3
0x1C3 Remote Input 4 Remote Input 4
0x1C4 Remote Input 5 Remote Input 5
0x1C5 Remote Input 6 Remote Input 6
0x1C6 Remote Input 7 Remote Input 7
0x1C7 Remote Input 8 Remote Input 8
0x1C8 Remote Input 9 Remote Input 9
0x1C9 Remote Input 10 Remote Input 10
0x1CA Remote Input 11 Remote Input 11
0x1CB Remote Input 12 Remote Input 12
0x1CC Remote Input 13 Remote Input 13
0x1CD Remote Input 14 Remote Input 14
0x1CE Remote Input 15 Remote Input 15
0x1CF Remote Input 16 Remote Input 16
0x1D0 Remote Input 17 Remote Input 17
0x1D1 Remote Input 18 Remote Input 18
0x1D2 Remote Input 19 Remote Input 19
0x1D3 Remote Input 20 Remote Input 20
0x1D4 Remote Input 21 Remote Input 21
0x1D5 Remote Input 22 Remote Input 22
0x1D6 Remote Input 23 Remote Input 23
0x1D7 Remote Input 24 Remote Input 24
0x1D8 Remote Input 25 Remote Input 25
0x1D9 Remote Input 26 Remote Input 26
0x1DA Remote Input 27 Remote Input 27
0x1DB Remote Input 28 Remote Input 28
0x1DC Remote Input 29 Remote Input 29
0x1DD Remote Input 30 Remote Input 30
0x1DE Remote Input 31 Remote Input 31
0x1DF Remote Input 32 Remote Input 32
F90 unsigned 16 bits Operate / Do Not Operate
0 Do Not Operate Do Not Operate
1 Operate Operate
F91 signed 16 bits Edit Group
-1 Active Group Active Group
0 SP Group 1 Active Setpoint Group 1 Active
1 SP Group 2 Active Setpoint Group 2 Active
F92 unsigned 16 bits Phases
1 Any One Any One
2 Any Two Any Two

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-93


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


3 All Three All Three
F92A unsigned 16 bits Phases + Average
F93 unsigned 16 bits Phase UV Curve
0 Definite Time Definite Time
1 Inverse Time Inverse Time
F94 unsigned 16 bits Breaker Control
0 Disabled Disabled
1 Contact Input 1 Contact Input 1
2 Contact Input 2 Contact Input 2
3 Contact Input 3 Contact Input 3
4 Contact Input 4 Contact Input 4
5 Contact Input 5 Contact Input 5
6 Contact Input 6 Contact Input 6
7 Contact Input 7 Contact Input 7
8 Contact Input 8 Contact Input 8
9 Contact Input 9 Contact Input 9
10 Contact Input 10 Contact Input 10
F95 unsigned 16 bits Transient Recorder Buffer
0 1 1
1 3 3
2 6 6
F96 unsigned 16 bits Directional Polarizing
1 Voltage Voltage
2 Current Current
3 Dual Dual
F97 unsigned 16 bits Rear 485 Port Protocol
0 Modbus Modbus
1 IEC60870-5-103 IEC60870-5-103
2 DNP 3.0 DNP 3.0
F98 unsigned 16 bits Simulated Key Press
0 No Key Press No Key Press
1 Nav Up Key Nav Up Key
2 Nav Left Key Nav Left Key
3 Nav Down Key Navigation Down Key
4 Nav Right Key Navigation Right Key
5 Up Key Up Key
6 Down Key Down Key
7 Enter Key Enter Key
8 Menu Key Menu Key
9 Escape Key Escape Key
10 Reset Key Reset Key
F99 unsigned 16 bits SR 3 Relay Status
0 Not Ready Not Ready
1 Ready Ready
FC100 unsigned 16 bits SNTP Mode
0 Disabled Disabled
1 Unicast Unicast

11-94 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


2 Anycast Anycast
3 Broadcast Broadcast
FC101 unsigned 16 bits RS 485 Baud Rate
0 9600 baud 9600 baud
1 19200 baud 19200 baud
2 38400 baud 38400 baud
3 57600 baud 57600 baud
4 115200 baud 115200 baud
FC102 unsigned 16 bits RS 485 Parity
0 None None
1 Odd Odd
2 Even Even
FC103 unsigned 16 bits Off / On Selection
0 Off Off
1 On On
FC103A unsigned 16 bits No / Yes Selection
0 NO NO
1 YES YES
FC104 unsigned 16 bits Ground CT Type
0 1 A Secondary 1 A Secondary
1 5 A Secondary 5 A Secondary
2 50:00.0 50:00.0
FC105 unsigned 16 bits Differential CT Type
0 None None
1 1 A Secondary 1 A Secondary
2 5 A Secondary 5 A Secondary
3 Direct Connect Direct Connect
FC106 unsigned 16 bits Voltage Transformer Connection Type
FC107 unsigned 16 bits Supply Frequency
0 60 Hz 60 Hz
1 50 Hz 50 Hz
FC108 unsigned 16 bits 61850 Status
0 Not Ready Not Ready
1 Ready Ready
2 Default CID Default CID
FC109 unsigned 16 bits Flex Logic Status
0 OK OK
1 Unknown Token Unknown Token
2 TooMany Latches Too Many Latches
3 TooMany Timers Too Many Timers
4 TooMany + OneShots Too Many + One Shots
5 TooMany - OneShots Too Many - One Shots
6 TooMany Duel1Shots Too Many Duel One Shots
7 Stack Overflow Stack Overflow
8 Stack Underflow Stack Underflow
9 Program Too Long Program Too Long
FC111 unsigned 16 bits Trip Relays

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-95


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0 Trip Trip
1 Alarm Alarm
FC112 unsigned 16 bits Communication Status
0 Error Error
1 OK OK
FC115 unsigned 16 bits Alarm Type Selection
0 Off Off
1 Trip Trip
2 Alarm Alarm
FC116 unsigned 16 bits Switch Type
0 Open Open
1 Closed Closed
FC117 unsigned 16 bits Directional Voltage
0 Measured (Vx) Measured (Vx)
1 Calculated (VTs) Calculated (VTs)
FC118 unsigned 16 bits WGF Voltage
0 Calculated (Vn) Calculated (Vn)
1 Measured (Vx) Measured (Vx)
FC119 unsigned 16 bits WGF Current
0 Calculated (In) Calculated (In)
1 Measured (Ig) Measured (Ig)
FC120 unsigned 16 bits RTD Type
FC121 unsigned 16 bits RTD Application
0 None None
3 Ambient Ambient
4 Top Oil Top Oil
5 Bottom Oil Bottom Oil
6 Other Other
FC122 unsigned 16 bits RTD Voting Selection
0 Off Off
1 RTD #1 RTD #1
2 RTD #2 RTD #2
3 RTD #3 RTD #3
4 RTD #4 RTD #4
5 RTD #5 RTD #5
6 RTD #6 RTD #6
7 RTD #7 RTD #7
8 RTD #8 RTD #8
9 RTD #9 RTD #9
10 RTD #10 RTD #10
11 RTD #11 RTD #11
12 RTD #12 RTD #12
FC123 unsigned 16 bits Select DV Voltage
0 17V Threshold 17V Threshold
1 33V Threshold 33V Threshold
2 84V Threshold 84V Threshold
3 166V Threshold 166V Threshold

11-96 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


FC124 unsigned 16 bits Phase Rotation
0 ABC ABC
1 CBA CBA
FC124A unsigned 16 bits Phase Rotation
0 ABC ABC
1 ACB ACB
FC125 unsigned 16 bits Coil Monitor
0 Healthy Healthy
1 Unhealthy Unhealthy
FC126 unsigned 16 bits Disabled / Enabled Selection
0 Disabled Disabled
1 Enabled Enabled
FC127 unsigned 16 bits System Language
0 English English
1 Chinese Chinese
FC128 unsigned 16 bits Command Status
5 None None
FC129 unsigned 16 bits Relay Status
FC130 unsigned 16 bits LED Flash
FC131 unsigned 16 bits Comm Fail Mode
1 Serial Serial
2 Serial & Ethernet Serial & Ethernet
4 Serial & FieldBus Serial & FieldBus
8 Ethernet Ethernet
16 FieldBus FieldBus
32 Ethernet&Fieldbus Ethernet & Fieldbus
64 All All
FC133 unsigned 16 bits Cause of Waveform Trigger
0 None None
1 Command Command
0x00C0 VO 1 Virtual Output 1
0x00C1 VO 2 Virtual Output 2
0x00C2 VO 3 Virtual Output 3
0x00C3 VO 4 Virtual Output 4
0x00C4 VO 5 Virtual Output 5
0x00C5 VO 6 Virtual Output 6
0x00C6 VO 7 Virtual Output 7
0x00C7 VO 8 Virtual Output 8
0x00C8 VO 9 Virtual Output 9
0x00C9 VO 10 Virtual Output 10
0x00CA VO 11 Virtual Output 11
0x00CB VO 12 Virtual Output 12
0x00CC VO 13 Virtual Output 13
0x00CD VO 14 Virtual Output 14
0x00CE VO 15 Virtual Output 15
0x00CF VO 16 Virtual Output 16
0x00D0 VO 17 Virtual Output 17

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-97


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x00D1 VO 18 Virtual Output 18
0x00D2 VO 19 Virtual Output 19
0x00D3 VO 20 Virtual Output 20
0x00D4 VO 21 Virtual Output 21
0x00D5 VO 22 Virtual Output 22
0x00D6 VO 23 Virtual Output 23
0x00D7 VO 24 Virtual Output 24
0x00D8 VO 25 Virtual Output 25
0x00D9 VO 26 Virtual Output 26
0x00DA VO 27 Virtual Output 27
0x00DB VO 28 Virtual Output 28
0x00DC VO 29 Virtual Output 29
0x00DD VO 30 Virtual Output 30
0x00DE VO 31 Virtual Output 31
0x00DF VO 32 Virtual Output 32
0x8001 Any Trip PickUp Any Trip PickUp
0x8002 Any Fault Any Fault
0x8004 Any Trip DropOut Any Trip DropOut
0xA001 Any Alarm PickUp Any Alarm PickUp
0xA002 Any Alarm Any Alarm
0xA004 Any Alarm DropOut Any Alarm DropOut
0xC002 Any Ctrl Any Ctrl
0xD000 Input 1 Input 1
0xD001 Input 2 Input 2
0xD002 Input 3 Input 3
FC133A unsigned 16 bits Data Log Trigger
0 None None
1 Command Command
0x00C0 VO 1 Virtual Output 1
0x00C1 VO 2 Virtual Output 2
0x00C2 VO 3 Virtual Output 3
0x00C3 VO 4 Virtual Output 4
0x00C4 VO 5 Virtual Output 5
0x00C5 VO 6 Virtual Output 6
0x00C6 VO 7 Virtual Output 7
0x00C7 VO 8 Virtual Output 8
0x00C8 VO 9 Virtual Output 9
0x00C9 VO 10 Virtual Output 10
0x00CA VO 11 Virtual Output 11
0x00CB VO 12 Virtual Output 12
0x00CC VO 13 Virtual Output 13
0x00CD VO 14 Virtual Output 14
0x00CE VO 15 Virtual Output 15
0x00CF VO 16 Virtual Output 16
0x00D0 VO 17 Virtual Output 17
0x00D1 VO 18 Virtual Output 18
0x00D2 VO 19 Virtual Output 19

11-98 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x00D3 VO 20 Virtual Output 20
0x00D4 VO 21 Virtual Output 21
0x00D5 VO 22 Virtual Output 22
0x00D6 VO 23 Virtual Output 23
0x00D7 VO 24 Virtual Output 24
0x00D8 VO 25 Virtual Output 25
0x00D9 VO 26 Virtual Output 26
0x00DA VO 27 Virtual Output 27
0x00DB VO 28 Virtual Output 28
0x00DC VO 29 Virtual Output 29
0x00DD VO 30 Virtual Output 30
0x00DE VO 31 Virtual Output 31
0x00DF VO 32 Virtual Output 32
0x8001 Any Trip PickUp Any Trip PickUp
0x8002 Any Fault Any Fault
0x8004 Any Trip DropOut Any Trip DropOut
0xA001 Any Alarm PickUp Any Alarm PickUp
0xA002 Any Alarm Any Alarm
0xA004 Any Alarm DropOut Any Alarm DropOut
0xC002 Any Ctrl Any Ctrl
FC134 unsigned 16 bits Cause of Event
0 No Evnt/Trp ToDate No Event/Trip To Date
1 Ctrl. Pwr Lost Control Power Lost
2 Ctrl. Pwr Applied Control Power Applied
3 Date or Time Set Date or Time Set
4 Reset Reset
5 Lockout Rst Closed Lockout Reset Closed
6 Factory Reload Factory Reload
7 Clock Not Set Clock Not Set
8 IRIG-B Failure IRIG-B Failure
9 Reset Trip Counter Reset Trip Counter
10 BKR Status Unknown Breaker Status Unknown
11 Clear Event Rec Clear Event Records
12 Clear Transt Rec Clear Transient Records
13 Clear Therm Cap Clear Thermal Capacity
14 Comm. Alert 1 Comm. Alert 1
15 Comm. Alert 2 Comm. Alert 2
16 Comm. Alert 3 Comm. Alert 3
17 Ethernet Link Fail Ethernet Link Failure
18 High ENET Traffic High Ethernet Traffic
19 Intern Temp. >80C Internal Temperature High
20 RMIO Mismatch RMIO Mismatch
21 BKR2 Status Unkwn Breaker 2 Status Unknown
22 Emergency Restart Emergency Restart
23 Trace Mem. Trigger Trace Mem. Trigger
24 Rx Goose 1 ON Rx Goose 1 ON
25 Rx Goose 1 OFF Rx Goose 1 OFF

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-99


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


26 Rx Goose 2 ON Rx Goose 2 ON
27 Rx Goose 2 OFF Rx Goose 2 OFF
28 Rx Goose 3 ON Rx Goose 3 ON
29 Rx Goose 3 OFF Rx Goose 3 OFF
30 Rx Goose 4 ON Rx Goose 4 ON
31 Rx Goose 4 OFF Rx Goose 4 OFF
32 Rx Goose 5 ON Rx Goose 5 ON
33 Rx Goose 5 OFF Rx Goose 5 OFF
34 Rx Goose 6 ON Rx Goose 6 ON
35 Rx Goose 6 OFF Rx Goose 6 OFF
36 Rx Goose 7 ON Rx Goose 7 ON
37 Rx Goose 7 OFF Rx Goose 7 OFF
38 Rx Goose 8 ON Rx Goose 8 ON
39 Rx Goose 8 OFF Rx Goose 8 OFF
40 Eth Link A Fail Ethernet Link A Fail
41 Eth Link B Fail Ethernet Link B Fail
0x0040 Contact IN 1 On Contact Input 1 On
0x0041 Contact IN 2 On Contact Input 2 On
0x0042 Contact IN 3 On Contact Input 3 On
0x0043 Contact IN 4 On Contact Input 4 On
0x0044 Contact IN 5 On Contact Input 5 On
0x0045 Contact IN 6 On Contact Input 6 On
0x0046 Contact IN 7 On Contact Input 7 On
0x0047 Contact IN 8 On Contact Input 8 On
0x0048 Contact IN 9 On Contact Input 9 On
0x0049 Contact IN 10 On Contact Input 10 On
0x0060 Contact IN 1 Off Contact Input 1 Off
0x0061 Contact IN 2 Off Contact Input 2 Off
0x0062 Contact IN 3 Off Contact Input 3 Off
0x0063 Contact IN 4 Off Contact Input 4 Off
0x0064 Contact IN 5 Off Contact Input 5 Off
0x0065 Contact IN 6 Off Contact Input 6 Off
0x0066 Contact IN 7 Off Contact Input 7 Off
0x0067 Contact IN 8 Off Contact Input 8 Off
0x0068 Contact IN 9 Off Contact Input 9 Off
0x0069 Contact IN 10 Off Contact Input 10 Off
0x0080 Virtual IN 1 On Virtual Input 1 On
0x0081 Virtual IN 2 On Virtual Input 2 On
0x0082 Virtual IN 3 On Virtual Input 3 On
0x0083 Virtual IN 4 On Virtual Input 4 On
0x0084 Virtual IN 5 On Virtual Input 5 On
0x0085 Virtual IN 6 On Virtual Input 6 On
0x0086 Virtual IN 7 On Virtual Input 7 On
0x0087 Virtual IN 8 On Virtual Input 8 On
0x0088 Virtual IN 9 On Virtual Input 9 On
0x0089 Virtual IN 10 On Virtual Input 10 On
0x008A Virtual IN 11 On Virtual Input 11 On

11-100 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x008B Virtual IN 12 On Virtual Input 12 On
0x008C Virtual IN 13 On Virtual Input 13 On
0x008D Virtual IN 14 On Virtual Input 14 On
0x008E Virtual IN 15 On Virtual Input 15 On
0x008F Virtual IN 16 On Virtual Input 16 On
0x0090 Virtual IN 17 On Virtual Input 17 On
0x0091 Virtual IN 18 On Virtual Input 18 On
0x0092 Virtual IN 19 On Virtual Input 19 On
0x0093 Virtual IN 20 On Virtual Input 20 On
0x0094 Virtual IN 21 On Virtual Input 21 On
0x0095 Virtual IN 22 On Virtual Input 22 On
0x0096 Virtual IN 23 On Virtual Input 23 On
0x0097 Virtual IN 24 On Virtual Input 24 On
0x0098 Virtual IN 25 On Virtual Input 25 On
0x0099 Virtual IN 26 On Virtual Input 26 On
0x009A Virtual IN 27 On Virtual Input 27 On
0x009B Virtual IN 28 On Virtual Input 28 On
0x009C Virtual IN 29 On Virtual Input 29 On
0x009D Virtual IN 30 On Virtual Input 30 On
0x009E Virtual IN 31 On Virtual Input 31 On
0x009F Virtual IN 32 On Virtual Input 32 On
0x00A0 Virtual IN 1 Off Virtual Input 1 Off
0x00A1 Virtual IN 2 Off Virtual Input 2 Off
0x00A2 Virtual IN 3 Off Virtual Input 3 Off
0x00A3 Virtual IN 4 Off Virtual Input 4 Off
0x00A4 Virtual IN 5 Off Virtual Input 5 Off
0x00A5 Virtual IN 6 Off Virtual Input 6 Off
0x00A6 Virtual IN 7 Off Virtual Input 7 Off
0x00A7 Virtual IN 8 Off Virtual Input 8 Off
0x00A8 Virtual IN 9 Off Virtual Input 9 Off
0x00A9 Virtual IN 10 Off Virtual Input 10 Off
0x00AA Virtual IN 11 Off Virtual Input 11 Off
0x00AB Virtual IN 12 Off Virtual Input 12 Off
0x00AC Virtual IN 13 Off Virtual Input 13 Off
0x00AD Virtual IN 14 Off Virtual Input 14 Off
0x00AE Virtual IN 15 Off Virtual Input 15 Off
0x00AF Virtual IN 16 Off Virtual Input 16 Off
0x00B0 Virtual IN 17 Off Virtual Input 17 Off
0x00B1 Virtual IN 18 Off Virtual Input 18 Off
0x00B2 Virtual IN 19 Off Virtual Input 19 Off
0x00B3 Virtual IN 20 Off Virtual Input 20 Off
0x00B4 Virtual IN 21 Off Virtual Input 21 Off
0x00B5 Virtual IN 22 Off Virtual Input 22 Off
0x00B6 Virtual IN 23 Off Virtual Input 23 Off
0x00B7 Virtual IN 24 Off Virtual Input 24 Off
0x00B8 Virtual IN 25 Off Virtual Input 25 Off
0x00B9 Virtual IN 26 Off Virtual Input 26 Off

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-101


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x00BA Virtual IN 27 Off Virtual Input 27 Off
0x00BB Virtual IN 28 Off Virtual Input 28 Off
0x00BC Virtual IN 29 Off Virtual Input 29 Off
0x00BD Virtual IN 30 Off Virtual Input 30 Off
0x00BE Virtual IN 31 Off Virtual Input 31 Off
0x00BF Virtual IN 32 Off Virtual Input 32 Off
0x01C0 Remote IN 1 On Remote Input 1 On
0x01C1 Remote IN 2 On Remote Input 2 On
0x01C2 Remote IN 3 On Remote Input 3 On
0x01C3 Remote IN 4 On Remote Input 4 On
0x01C4 Remote IN 5 On Remote Input 5 On
0x01C5 Remote IN 6 On Remote Input 6 On
0x01C6 Remote IN 7 On Remote Input 7 On
0x01C7 Remote IN 8 On Remote Input 8 On
0x01C8 Remote IN 9 On Remote Input 9 On
0x01C9 Remote IN 10 On Remote Input 10 On
0x01CA Remote IN 11 On Remote Input 11 On
0x01CB Remote IN 12 On Remote Input 12 On
0x01CC Remote IN 13 On Remote Input 13 On
0x01CD Remote IN 14 On Remote Input 14 On
0x01CE Remote IN 15 On Remote Input 15 On
0x01CF Remote IN 16 On Remote Input 16 On
0x01D0 Remote IN 17 On Remote Input 17 On
0x01D1 Remote IN 18 On Remote Input 18 On
0x01D2 Remote IN 19 On Remote Input 19 On
0x01D3 Remote IN 20 On Remote Input 20 On
0x01D4 Remote IN 21 On Remote Input 21 On
0x01D5 Remote IN 22 On Remote Input 22 On
0x01D6 Remote IN 23 On Remote Input 23 On
0x01D7 Remote IN 24 On Remote Input 24 On
0x01D8 Remote IN 25 On Remote Input 25 On
0x01D9 Remote IN 26 On Remote Input 26 On
0x01DA Remote IN 27 On Remote Input 27 On
0x01DB Remote IN 28 On Remote Input 28 On
0x01DC Remote IN 29 On Remote Input 29 On
0x01DD Remote IN 30 On Remote Input 30 On
0x01DE Remote IN 31 On Remote Input 31 On
0x01DF Remote IN 32 On Remote Input 32 On
0x01E0 Remote IN 1 Off Remote Input 1 Off
0x01E1 Remote IN 2 Off Remote Input 2 Off
0x01E2 Remote IN 3 Off Remote Input 3 Off
0x01E3 Remote IN 4 Off Remote Input 4 Off
0x01E4 Remote IN 5 Off Remote Input 5 Off
0x01E5 Remote IN 6 Off Remote Input 6 Off
0x01E6 Remote IN 7 Off Remote Input 7 Off
0x01E7 Remote IN 8 Off Remote Input 8 Off
0x01E8 Remote IN 9 Off Remote Input 9 Off

11-102 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x01E9 Remote IN 10 Off Remote Input 10 Off
0x01EA Remote IN 11 Off Remote Input 11 Off
0x01EB Remote IN 12 Off Remote Input 12 Off
0x01EC Remote IN 13 Off Remote Input 13 Off
0x01ED Remote IN 14 Off Remote Input 14 Off
0x01EE Remote IN 15 Off Remote Input 15 Off
0x01EF Remote IN 16 Off Remote Input 16 Off
0x01F0 Remote IN 17 Off Remote Input 17 Off
0x01F1 Remote IN 18 Off Remote Input 18 Off
0x01F2 Remote IN 19 Off Remote Input 19 Off
0x01F3 Remote IN 20 Off Remote Input 20 Off
0x01F4 Remote IN 21 Off Remote Input 21 Off
0x01F5 Remote IN 22 Off Remote Input 22 Off
0x01F6 Remote IN 23 Off Remote Input 23 Off
0x01F7 Remote IN 24 Off Remote Input 24 Off
0x01F8 Remote IN 25 Off Remote Input 25 Off
0x01F9 Remote IN 26 Off Remote Input 26 Off
0x01FA Remote IN 27 Off Remote Input 27 Off
0x01FB Remote IN 28 Off Remote Input 28 Off
0x01FC Remote IN 29 Off Remote Input 29 Off
0x01FD Remote IN 30 Off Remote Input 30 Off
0x01FE Remote IN 31 Off Remote Input 31 Off
0x01FF Remote IN 32 Off Remote Input 32 Off
0x8002 Any Trip Any Trip
0x8042 Therm O/L Trip OP Thermal Overload Trip OP
0x8044 Therm O/L Trip DPO Thermal Overload Trip DPO
0x804A Therm PhA Trip OP Thermal Phase A Trip OP
0x804C Therm PhA Trip DPO Thermal Phase A Trip DPO
0x8052 Therm PhB Trip OP Thermal Phase B Trip OP
0x8054 Therm PhB Trip DPO Thermal Phase B Trip DPO
0x8062 Therm PhC Trip OP Thermal Phase C Trip OP
0x8064 Therm PhC Trip DPO Thermal Phase C Trip DPO
0x8081 RTD 1 Trip PKP RTD 1 Trip PKP
0x8082 RTD 1 Trip OP RTD 1 Trip OP
0x80C1 RTD 2 Trip PKP RTD 2 Trip PKP
0x80C2 RTD 2 Trip OP RTD 2 Trip OP
0x8101 RTD 3 Trip PKP RTD 3 Trip PKP
0x8102 RTD 3 Trip OP RTD 3 Trip OP
0x8141 RTD 4 Trip PKP RTD 4 Trip PKP
0x8142 RTD 4 Trip OP RTD 4 Trip OP
0x8201 RTD 5 Trip PKP RTD 5 Trip PKP
0x8202 RTD 5 Trip OP RTD 5 Trip OP
0x8241 RTD 6 Trip PKP RTD 6 Trip PKP
0x8242 RTD 6 Trip OP RTD 6 Trip OP
0x8281 RTD 7 Trip PKP RTD 7 Trip PKP
0x8282 RTD 7 Trip OP RTD 7 Trip OP
0x82C1 RTD 8 Trip PKP RTD 8 Trip PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-103


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x82C2 RTD 8 Trip OP RTD 8 Trip OP
0x8301 RTD 9 Trip PKP RTD 9 Trip PKP
0x8302 RTD 9 Trip OP RTD 9 Trip OP
0x8341 RTD 10 Trip PKP RTD 10 Trip PKP
0x8342 RTD 10 Trip OP RTD 10 Trip OP
0x8381 RTD 11 Trip PKP RTD 11 Trip PKP
0x8382 RTD 11 Trip OP RTD 11 Trip OP
0x83C1 RTD 12 Trip PKP RTD 12 Trip PKP
0x83C2 RTD 12 Trip OP RTD 12 Trip OP
0x84C1 LE 1 Trip PKP Logic Element 1 Trip PKP
0x84C2 LE 1 Trip OP Logic Element 1 Trip OP
0x84C4 LE 1 Trip DPO Logic Element 1 Trip DPO
0x8501 LE 2 Trip PKP Logic Element 2 Trip PKP
0x8502 LE 2 Trip OP Logic Element 2 Trip OP
0x8504 LE 2 Trip DPO Logic Element 2 Trip DPO
0x8541 LE 3 Trip PKP Logic Element 3 Trip PKP
0x8542 LE 3 Trip OP Logic Element 3 Trip OP
0x8544 LE 3 Trip DPO Logic Element 3 Trip DPO
0x8581 LE 4 Trip PKP Logic Element 4 Trip PKP
0x8582 LE 4 Trip OP Logic Element 4 Trip OP
0x8584 LE 4 Trip DPO Logic Element 4 Trip DPO
0x85C1 LE 5 Trip PKP Logic Element 5 Trip PKP
0x85C2 LE 5 Trip OP Logic Element 5 Trip OP
0x85C4 LE 5 Trip DPO Logic Element 5 Trip DPO
0x8601 LE 6 Trip PKP Logic Element 6 Trip PKP
0x8602 LE 6 Trip OP Logic Element 6 Trip OP
0x8604 LE 6 Trip DPO Logic Element 6 Trip DPO
0x8641 LE 7 Trip PKP Logic Element 7 Trip PKP
0x8642 LE 7 Trip OP Logic Element 7 Trip OP
0x8644 LE 7 Trip DPO Logic Element 7 Trip DPO
0x8681 LE 8 Trip PKP Logic Element 8 Trip PKP
0x8682 LE 8 Trip OP Logic Element 8 Trip OP
0x8684 LE 8 Trip DPO Logic Element 8 Trip DPO
0x89C2 Self Test OP Self Test OP
0x89C4 Self Test DPO Self Test Trip DPO
0x9001 Ph IOC1 Trip PKP Phase IOC 1 Trip PKP
0x9002 Ph IOC1 Trip OP Phase IOC 1 Trip OP
0x9004 Ph IOC1 Trip DPO Phase IOC 1 Trip DPO
0x9009 Ph A IOC1 Trip PKP Phase A IOC 1 Trip PKP
0x900A Ph A IOC1 Trip OP Phase A IOC 1 Trip OP
0x900C Ph A IOC1 Trip DPO Phase A IOC 1 Trip DPO
0x9011 Ph B IOC1 Trip PKP Phase B IOC 1 Trip PKP
0x9012 Ph B IOC1 Trip OP Phase B IOC 1 Trip OP
0x9014 Ph B IOC1 Trip DPO Phase B IOC 1 Trip DPO
0x9021 Ph C IOC1 Trip PKP Phase C IOC 1 Trip PKP
0x9022 Ph C IOC1 Trip OP Phase C IOC 1 Trip OP
0x9024 Ph C IOC1 Trip DPO Phase C IOC 1 Trip DPO

11-104 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x9041 Ntrl IOC1 Trip PKP Neutral IOC 1 Trip PKP
0x9042 Ntrl IOC1 Trip OP Neutral IOC 1 Trip OP
0x9044 Ntrl IOC1 Trip DPO Neutral IOC 1 Trip DPO
0x9081 Gnd IOC1 Trip PKP Ground IOC 1 Trip PKP
0x9082 Gnd IOC1 Trip OP Ground IOC 1 Trip OP
0x9084 Gnd IOC1 Trip DPO Ground IOC 1 Trip DPO
0x90C1 Ph TOC1 Trip PKP Phase TOC 1 Trip PKP
0x90C2 Ph TOC1 Trip OP Phase TOC 1 Trip OP
0x90C4 Ph TOC1 Trip DPO Phase TOC 1 Trip DPO
0x90C9 Ph A TOC1 Trip PKP Phase A TOC 1 Trip PKP
0x90CA Ph A TOC1 Trip OP Phase A TOC 1 Trip OP
0x90CC Ph A TOC1 Trip DPO Phase A TOC 1 Trip DPO
0x90D1 Ph B TOC1 Trip PKP Phase B TOC 1 Trip PKP
0x90D2 Ph B TOC1 Trip OP Phase B TOC 1 Trip OP
0x90D4 Ph B TOC1 Trip DPO Phase B TOC 1 Trip DPO
0x90E1 Ph C TOC1 Trip PKP Phase C TOC 1 Trip PKP
0x90E2 Ph C TOC1 Trip OP Phase C TOC 1 Trip OP
0x90E4 Ph C TOC1 Trip DPO Phase C TOC 1 Trip DPO
0x9101 Ntrl TOC1 Trip PKP Neutral TOC 1 Trip PKP
0x9102 Ntrl TOC1 Trip OP Neutral TOC 1 Trip OP
0x9104 Ntrl TOC1 Trip DPO Neutral TOC 1 Trip DPO
0x9141 Gnd TOC1 Trip PKP Ground TOC Trip PKP
0x9142 Gnd TOC1 Trip OP Ground TOC 1 Trip OP
0x9144 Gnd TOC1 Trip DPO Ground TOC Trip DPO
0x9181 Ph IOC2 Trip PKP Phase IOC 2 Trip PKP
0x9182 Ph IOC2 Trip OP Phase IOC 2 Trip OP
0x9184 Ph IOC2 Trip DPO Phase IOC 2 Trip DPO
0x9189 Ph A IOC2 Trip PKP Phase A IOC 2 Trip PKP
0x918A Ph A IOC2 Trip OP Phase A IOC 2 Trip OP
0x918C Ph A IOC2 Trip DPO Phase A IOC 2 Trip DPO
0x9191 Ph B IOC2 Trip PKP Phase B IOC 2 Trip PKP
0x9192 Ph B IOC2 Trip OP Phase B IOC 2 Trip OP
0x9194 Ph B IOC2 Trip DPO Phase B IOC 2 Trip DPO
0x91A1 Ph C IOC2 Trip PKP Phase C IOC 2 Trip PKP
0x91A2 Ph C IOC2 Trip OP Phase C IOC 2 Trip OP
0x91A4 Ph C IOC2 Trip DPO Phase C IOC 2 Trip DPO
0x91C1 Ntrl IOC2 Trip PKP Neutral IOC 2 Trip PKP
0x91C2 Ntrl IOC2 Trip OP Neutral IOC 2 Trip OP
0x91C4 Ntrl IOC2 Trip DPO Neutral IOC 2 Trip DPO
0x9201 Gnd IOC2 Trip PKP Ground IOC 2 Trip PKP
0x9202 Gnd IOC2 Trip OP Ground IOC 2 Trip OP
0x9204 Gnd IOC2 Trip DPO Ground IOC 2 Trip DPO
0x9241 Ph TOC2 Trip PKP Phase TOC 2 Trip PKP
0x9242 Ph TOC2 Trip OP Phase TOC 2 Trip OP
0x9244 Ph TOC2 Trip DPO Phase TOC 2 Trip DPO
0x9249 Ph A TOC2 Trip PKP Phase A TOC 2 Trip PKP
0x924A Ph A TOC2 Trip OP Phase A TOC 2 Trip OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-105


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x924C Ph A TOC2 Trip DPO Phase A TOC 2 Trip DPO
0x9251 Ph B TOC2 Trip PKP Phase B TOC 2 Trip PKP
0x9252 Ph B TOC2 Trip OP Phase B TOC 2 Trip OP
0x9254 Ph B TOC2 Trip DPO Phase B TOC 2 Trip DPO
0x9261 Ph C TOC2 Trip PKP Phase C TOC 2 Trip PKP
0x9262 Ph C TOC2 Trip OP Phase C TOC 2 Trip OP
0x9264 Ph C TOC2 Trip DPO Phase C TOC 2 Trip DPO
0x9281 Ntrl TOC2 Trip PKP Neutral TOC 2 Trip PKP
0x9282 Ntrl TOC2 Trip OP Neutral TOC 2 Trip OP
0x9284 Ntrl TOC2 Trip DPO Neutral TOC 2 Trip DPO
0x92C1 Gnd TOC2 Trip PKP Ground TOC 2 Trip PKP
0x92C2 Gnd TOC2 Trip OP Ground TOC 2 Trip OP
0x92C4 Gnd TOC2 Trip DPO Ground TOC 2 Trip DPO
0x9301 SGnd TOC1 Trip PKP Sensitive Ground TOC 1 Trip PKP
0x9302 SGnd TOC1 Trip OP Sensitive Ground TOC 1 Trip OP
0x9304 SGnd TOC1 Trip DPO Sensitive Ground TOC 1 Trip DPO
0x9641 SGnd IOC1 Trip PKP Sensitive Ground IOC 1 Trip PKP
0x9642 SGnd IOC1 Trip OP Sensitive Ground IOC 1 Trip OP
0x9644 SGnd IOC1 Trip DPO Sensitive Ground IOC 1 Trip DPO
0x9681 SGnd IOC2 Trip PKP Sensitive Ground IOC 2 Trip PKP
0x9682 SGnd IOC2 Trip OP Sensitive Ground IOC 2 Trip OP
0x9684 SGnd IOC2 Trip DPO Sensitive Ground IOC 2 Trip DPO
0x96C1 NSeq IOC Trp PKP Negative Sequence IOC Trip PKP
0x96C2 NSeq IOC Trp OP Negative Sequence IOC Trip OP
0x96C4 NSeq IOC Trp DPO Negative Sequence IOC Trip DPO
0x9701 Pcnt Diff Trip PKP Pcnt Diff Trip PKP
0x9702 Pcnt Diff Trip OP Pcnt Diff Trip OP
0x9704 Pcnt Diff Trip DPO Pcnt Diff Trip DPO
0x9709 Ph Diff A Trip PKP Ph Diff A Trip PKP
0x970A Ph Diff A Trip OP Ph Diff A Trip OP
0x970C Ph Diff A Trip DPO Ph Diff A Trip DPO
0x9711 Ph Diff B Trip PKP Ph Diff B Trip PKP
0x9712 Ph Diff B Trip OP Ph Diff B Trip OP
0x9714 Ph Diff B Trip DPO Ph Diff B Trip DPO
0x9721 Ph Diff C Trip PKP Ph Diff C Trip PKP
0x9722 Ph Diff C Trip OP Ph Diff C Trip OP
0x9724 Ph Diff C Trip DPO Ph Diff C Trip DPO
0x9741 RGF1 Trip PKP RGF1 Trip PKP
0x9742 RGF1 Trip OP RGF1 Trip OP
0x9744 RGF1 Trip DPO RGF1 Trip DPO
0x9781 RGF2 Trip PKP RGF2 Trip PKP
0x9782 RGF2 Trip OP RGF2 Trip OP
0x9784 RGF2 Trip DPO RGF2 Trip DPO
0x97C1 Inst Diff Trip PKP Inst Diff Trip PKP
0x97C2 Inst Diff Trip OP Inst Diff Trip OP
0x97C4 Inst Diff Trip DPO Inst Diff Trip DPO
0x9801 NSeq TOC1 Trip PKP Negative Sequence TOC 1 Trip PKP

11-106 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x9802 NSeq TOC1 Trip OP Negative Sequence TOC 1 Trip OP
0x9804 NSeq TOC1 Trip DPO Negative Sequence TOC 1 Trip DPO
0x9841 NSeq TOC2 Trip PKP Negative Sequence TOC 2 Trip PKP
0x9842 NSeq TOC2 Trip OP Negative Sequence TOC 2 Trip OP
0x9844 NSeq TOC2 Trip DPO Negative Sequence TOC 2 Trip DPO
0x9901 NSeq IOC 2 Trp PKP Negative Sequence IOC 2 Trip PKP
0x9902 NSeq IOC 2 Trp OP Negative Sequence IOC 2 Trip OP
0x9904 NSeq IOC 2 Trp DPO Negative Sequence IOC 2 Trip DPO
0x99C1 SGnd TOC2 Trip PKP Sensitive Ground TOC 2 Trip PKP
0x99C2 SGnd TOC2 Trip OP Sensitive Ground TOC 2 Trip OP
0x99C4 SGnd TOC2 Trip DPO Sensitive Ground TOC 2 Trip DPO
0x9C01 LE 9 Trip PKP Logic Element 9 Trip PKP
0x9C02 LE 9 Trip OP Logic Element 9 Trip OP
0x9C04 LE 9 Trip DPO Logic Element 9 Trip DPO
0x9C41 LE 10 Trip PKP Logic Element 10 Trip PKP
0x9C42 LE 10 Trip OP Logic Element 10 Trip OP
0x9C44 LE 10 Trip DPO Logic Element 10 Trip DPO
0x9C81 LE 11 Trip PKP Logic Element 11 Trip PKP
0x9C82 LE 11 Trip OP Logic Element 11 Trip OP
0x9C84 LE 11 Trip DPO Logic Element 11 Trip DPO
0x9CC1 LE 12 Trip PKP Logic Element 12 Trip PKP
0x9CC2 LE 12 Trip OP Logic Element 12 Trip OP
0x9CC4 LE 12 Trip DPO Logic Element 12 Trip DPO
0x9D01 LE 13 Trip PKP Logic Element 13 Trip PKP
0x9D02 LE 13 Trip OP Logic Element 13 Trip OP
0x9D04 LE 13 Trip DPO Logic Element 13 Trip DPO
0x9D41 LE 14 Trip PKP Logic Element 14 Trip PKP
0x9D42 LE 14 Trip OP Logic Element 14 Trip OP
0x9D44 LE 14 Trip DPO Logic Element 14 Trip DPO
0x9D81 LE 15 Trip PKP Logic Element 15 Trip PKP
0x9D82 LE 15 Trip OP Logic Element 15 Trip OP
0x9D84 LE 15 Trip DPO Logic Element 15 Trip DPO
0x9DC1 LE 16 Trip PKP Logic Element 16 Trip PKP
0x9DC2 LE 16 Trip OP Logic Element 16 Trip OP
0x9DC4 LE 16 Trip DPO Logic Element 16 Trip DPO
0xA002 Any Alarm Any Alarm
0xA042 Therm Lvl Alrm OP Thermal Level Alarm OP
0xA044 Therm Lvl Alrm DPO Thermal Level Alarm DPO
0xA04A Therm PhA Alrm OP Thermal Phase A Alarm OP
0xA04C Therm PhA Alrm DPO Thermal Phase A Alarm DPO
0xA052 Therm PhB Alrm OP Thermal Phase B Alarm OP
0xA054 Therm PhB Alrm DPO Thermal Phase B Alarm DPO
0xA062 Therm PhC Alrm OP Thermal Phase C Alarm OP
0xA064 Therm PhC Alrm DPO Thermal Phase C Alarm DPO
0xA081 RTD 1 Alarm PKP RTD 1 Alarm PKP
0xA082 RTD 1 Alarm OP RTD 1 Alarm OP
0xA0C1 RTD 2 Alarm PKP RTD 2 Alarm PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-107


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xA0C2 RTD 2 Alarm OP RTD 2 Alarm OP
0xA101 RTD 3 Alarm PKP RTD 3 Alarm PKP
0xA102 RTD 3 Alarm OP RTD 3 Alarm OP
0xA141 RTD 4 Alarm PKP RTD 4 Alarm PKP
0xA142 RTD 4 Alarm OP RTD 4 Alarm OP
0xA201 RTD 5 Alarm PKP RTD 5 Alarm PKP
0xA202 RTD 5 Alarm OP RTD 5 Alarm OP
0xA241 RTD 6 Alarm PKP RTD 6 Alarm PKP
0xA242 RTD 6 Alarm OP RTD 6 Alarm OP
0xA281 RTD 7 Alarm PKP RTD 7 Alarm PKP
0xA282 RTD 7 Alarm OP RTD 7 Alarm OP
0xA2C1 RTD 8 Alarm PKP RTD 8 Alarm PKP
0xA2C2 RTD 8 Alarm OP RTD 8 Alarm OP
0xA301 RTD 9 Alarm PKP RTD 9 Alarm PKP
0xA302 RTD 9 Alarm OP RTD 9 Alarm OP
0xA341 RTD 10 Alarm PKP RTD 10 Alarm PKP
0xA342 RTD 10 Alarm OP RTD 10 Alarm OP
0xA381 RTD 11 Alarm PKP RTD 11 Alarm PKP
0xA382 RTD 11 Alarm OP RTD 11 Alarm OP
0xA3C1 RTD 12 Alarm PKP RTD 12 Alarm PKP
0xA3C2 RTD 12 Alarm OP RTD 12 Alarm OP
0xA402 RTD Trouble Alr OP RTD Trouble Alarm
0xA482 Relay Not Ready Relay Not Ready
0xA4C1 LE 1 Alarm PKP Logic Element 1 Alarm PKP
0xA4C2 LE 1 Alarm OP Logic Element 1 Alarm OP
0xA4C4 LE 1 Alarm DPO Logic Element 1 Alarm DPO
0xA501 LE 2 Alarm PKP Logic Element 2 Alarm PKP
0xA502 LE 2 Alarm OP Logic Element 2 Alarm OP
0xA504 LE 2 Alarm DPO Logic Element 2 Alarm DPO
0xA541 LE 3 Alarm PKP Logic Element 3 Alarm PKP
0xA542 LE 3 Alarm OP Logic Element 3 Alarm OP
0xA544 LE 3 Alarm DPO Logic Element 3 Alarm DPO
0xA581 LE 4 Alarm PKP Logic Element 4 Alarm PKP
0xA582 LE 4 Alarm OP Logic Element 4 Alarm OP
0xA584 LE 4 Alarm DPO Logic Element 4 Alarm DPO
0xA5C1 LE 5 Alarm PKP Logic Element 5 Alarm PKP
0xA5C2 LE 5 Alarm OP Logic Element 5 Alarm OP
0xA5C4 LE 5 Alarm DPO Logic Element 5 Alarm DPO
0xA601 LE 6 Alarm PKP Logic Element 6 Alarm PKP
0xA602 LE 6 Alarm OP Logic Element 6 Alarm OP
0xA604 LE 6 Alarm DPO Logic Element 6 Alarm DPO
0xA641 LE 7 Alarm PKP Logic Element 7 Alarm PKP
0xA642 LE 7 Alarm OP Logic Element 7 Alarm OP
0xA644 LE 7 Alarm DPO Logic Element 7 Alarm DPO
0xA681 LE 8 Alarm PKP Logic Element 8 Alarm PKP
0xA682 LE 8 Alarm OP Logic Element 8 Alarm OP
0xA684 LE 8 Alarm DPO Logic Element 8 Alarm DPO

11-108 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0xA6C2 Curr Dmd1 Alrm OP Current Demand 1 Alarm OP
0xA6CA C Dmd1 PhA Alrm OP Current Demand 1 PhA Alarm OP
0xA6D2 C Dmd1 PhB Alrm OP Current Demand 1 PhB Alarm OP
0xA6E2 C Dmd1 PhC Alrm OP Current Demand 1 PhC Alarm OP
0xA702 Curr Dmd2 Alrm OP Current Demand 2 Alarm OP
0xA70A C Dmd2 PhA Alrm OP Current Demand 2 PhA Alarm OP
0xA712 C Dmd2 PhB Alrm OP Current Demand 2 PhB Alarm OP
0xA722 C Dmd2 PhC Alrm OP Current Demand 2 PhC Alarm OP
0xA842 W1BKR Alarm W1 Breaker Alarm
0xA882 W1BKR Trip Time W1 Breaker Trip Time
0xA8C2 W1BKR Close Time W1 Breaker Close Time
0xA902 W1BKR Charge Time W1 Breaker Charge Time
0xA942 W2BKR Alarm W2 Breaker Alarm
0xA982 W2BKR Trip Time W2 Breaker Trip Time
0xA9C2 W2BKR Close Time W2 Breaker Close Time
0xAA02 W2BKR Charge Time W2 Breaker Charge Time
0xABC1 HI Amb Temp PKP High Ambient Temperature Alarm PKP
0xABC2 HI Amb Temp OP High Ambient Temperature Alarm
0xABC4 HI Amb Temp DPO High Ambient Temperature Alarm DPO
0xAC01 LO Amb Temp PKP Low Ambient Temperature Alarm PKP
0xAC02 LO Amb Temp OP Low Ambient Temperature Alarm
0xAC04 LO Amb Temp DPO Low Ambient Temperature Alarm DPO
0xAC42 Self Test Alarm OP Self Test Alarm OP
0xAC44 Self Test Alrm DPO Self Test Alarm DPO
0xACC2 BKRTrpCntrAlrm OP Breaker Trip Control Alarm OP
0xAD01 R1 CoilMonAlrm PKP Trip Coil Monitor Alarm PKP
0xAD02 R1 CoilMonAlrm OP Trip Coil Monitor Alarm OP
0xAD04 R1 CoilMonAlrm DPO Trip Coil Monitor Alarm DPO
0xAD41 R2 CoilMonAlrm PKP Close Coil Monitor Alarm PKP
0xAD42 R2 CoilMonAlrm OP Close Coil Monitor Alarm OP
0xAD44 R2 CoilMonAlrm DPO Close Coil Monitor Alarm DPO
0xAD81 BKR1 Fail Alrm PKP Breaker 1 Fail Alarm PKP
0xAD82 BKR1 Fail Alrm OP Breaker 1 Fail Alarm OP
0xAD84 BKR1 Fail Alrm DPO Breaker 1 Fail Alarm DPO
0xADC1 BKR Stat Fail PKP Breaker Status Fail PKP
0xADC2 BKR Stat Fail OP Breaker Status Fail OP
0xADC4 BKR Stat Fail DPO Breaker Status Fail DPO
0xAEC1 BKR2 Stat Fail PKP Breaker 2 Status Fail PKP
0xAEC2 BKR2 Stat Fail OP Breaker 2 Status Fail OP
0xAEC4 BKR2 Stat Fail DPO Breaker 2 Status Fail DPO
0xAF41 BKR2 Fail Alrm PKP Breaker 2 Fail Alarm PKP
0xAF42 BKR2 Fail Alrm OP Breaker 2 Fail Alarm OP
0xAF44 BKR2 Fail Alrm DPO Breaker 2 Fail Alarm DPO
0xB001 Ph IOC1 Alarm PKP Phase IOC 1 Alarm PKP
0xB002 Ph IOC1 Alarm OP Phase IOC 1 Alarm OP
0xB004 Ph IOC1 Alarm DPO Phase IOC 1 Alarm DPO
0xB009 Ph A IOC1 Alrm PKP Phase A IOC 1 Alarm PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-109


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xB00A Ph A IOC1 Alrm OP Phase A IOC 1 Alarm OP
0xB00C Ph A IOC1 Alrm DPO Phase A IOC 1 Alarm DPO
0xB011 Ph B IOC1 Alrm PKP Phase B IOC 1 Alarm PKP
0xB012 Ph B IOC1 Alrm OP Phase B IOC 1 Alarm OP
0xB014 Ph B IOC1 Alrm DPO Phase B IOC 1 Alarm DPO
0xB021 Ph C IOC1 Alrm PKP Phase C IOC 1 Alarm PKP
0xB022 Ph C IOC1 Alrm OP Phase C IOC 1 Alarm OP
0xB024 Ph C IOC1 Alrm DPO Phase C IOC 1 Alarm DPO
0xB041 Ntrl IOC1 Alrm PKP Neutral IOC 1 Alarm PKP
0xB042 Ntrl IOC1 Alrm OP Neutral IOC 1 Alarm OP
0xB044 Ntrl IOC1 Alrm DPO Neutral IOC 1 Alarm DPO
0xB081 Gnd IOC1 Alarm PKP Ground IOC 1 Alarm PKP
0xB082 Gnd IOC1 Alarm OP Ground IOC 1 Alarm OP
0xB084 Gnd IOC1 Alarm DPO Ground IOC 1 Alarm DPO
0xB0C1 Ph TOC1 Alarm PKP Phase TOC 1 Alarm PKP
0xB0C2 Ph TOC1 Alarm OP Phase TOC 1 Alarm OP
0xB0C4 Ph TOC1 Alarm DPO Phase TOC 1 Alarm DPO
0xB0C9 Ph A TOC1 Alrm PKP Phase A TOC 1 Alarm PKP
0xB0CA Ph A TOC1 Alrm OP Phase A TOC 1 Alarm OP
0xB0CC Ph A TOC1 Alrm DPO Phase A TOC 1 Alarm DPO
0xB0D1 Ph B TOC1 Alrm PKP Phase B TOC 1 Alarm PKP
0xB0D2 Ph B TOC1 Alrm OP Phase B TOC 1 Alarm OP
0xB0D4 Ph B TOC1 Alrm DPO Phase B TOC 1 Alarm DPO
0xB0E1 Ph C TOC1 Alrm PKP Phase C TOC 1 Alarm PKP
0xB0E2 Ph C TOC1 Alrm OP Phase C TOC 1 Alarm OP
0xB0E4 Ph C TOC1 Alrm DPO Phase C TOC 1 Alarm DPO
0xB101 Ntrl TOC1 Alrm PKP Neutral TOC 1 Alarm PKP
0xB102 Ntrl TOC1 Alrm OP Neutral TOC 1 Alarm OP
0xB104 Ntrl TOC1 Alrm DPO Neutral TOC 1 Alarm DPO
0xB141 Gnd TOC1 Alarm PKP Ground TOC Alarm PKP
0xB142 Gnd TOC1 Alarm OP Ground TOC 1 Alarm OP
0xB144 Gnd TOC1 Alarm DPO Ground TOC Alarm DPO
0xB181 Ph IOC2 Alarm PKP Phase IOC 2 Alarm PKP
0xB182 Ph IOC2 Alarm OP Phase IOC 2 Alarm OP
0xB184 Ph IOC2 Alarm DPO Phase IOC 2 Alarm DPO
0xB189 Ph A IOC2 Alrm PKP Phase A IOC 2 Alarm PKP
0xB18A Ph A IOC2 Alrm OP Phase A IOC 2 Alarm OP
0xB18C Ph A IOC2 Alrm DPO Phase A IOC 2 Alarm DPO
0xB191 Ph B IOC2 Alrm PKP Phase B IOC 2 Alarm PKP
0xB192 Ph B IOC2 Alrm OP Phase B IOC 2 Alarm OP
0xB194 Ph B IOC2 Alrm DPO Phase B IOC 2 Alarm DPO
0xB1A1 Ph C IOC2 Alrm PKP Phase C IOC 2 Alarm PKP
0xB1A2 Ph C IOC2 Alrm OP Phase C IOC 2 Alarm OP
0xB1A4 Ph C IOC2 Alrm DPO Phase C IOC 2 Alarm DPO
0xB1C1 Ntrl IOC2 Alrm PKP Neutral IOC 2 Alarm PKP
0xB1C2 Ntrl IOC2 Alrm OP Neutral IOC 2 Alarm OP
0xB1C4 Ntrl IOC2 Alrm DPO Neutral IOC 2 Alarm DPO

11-110 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0xB201 Gnd IOC2 Alarm PKP Ground IOC 2 Alarm PKP
0xB202 Gnd IOC2 Alarm OP Ground IOC 2 Alarm OP
0xB204 Gnd IOC2 Alarm DPO Ground IOC 2 Alarm DPO
0xB241 Ph TOC2 Alrm PKP Phase TOC 2 Alarm PKP
0xB242 Ph TOC2 Alrm OP Phase TOC 2 Alarm OP
0xB244 Ph TOC2 Alrm DPO Phase TOC 2 Alarm DPO
0xB249 Ph A TOC2 Alrm PKP Phase A TOC 2 Alarm PKP
0xB24A Ph A TOC2 Alrm OP Phase A TOC 2 Alarm OP
0xB24C Ph A TOC2 Alrm DPO Phase A TOC 2 Alarm DPO
0xB251 Ph B TOC2 Alrm PKP Phase B TOC 2 Alarm PKP
0xB252 Ph B TOC2 Alrm OP Phase B TOC 2 Alarm OP
0xB254 Ph B TOC2 Alrm DPO Phase B TOC 2 Alarm DPO
0xB261 Ph C TOC2 Alrm PKP Phase C TOC 2 Alarm PKP
0xB262 Ph C TOC2 Alrm OP Phase C TOC 2 Alarm OP
0xB264 Ph C TOC2 Alrm DPO Phase C TOC 2 Alarm DPO
0xB281 Ntrl TOC2 Alrm PKP Neutral TOC 2 Alarm PKP
0xB282 Ntrl TOC2 Alrm OP Neutral TOC 2 Alarm OP
0xB284 Ntrl TOC2 Alrm DPO Neutral TOC 2 Alarm DPO
0xB2C1 Gnd TOC2 Alarm PKP Ground TOC 2 Alarm PKP
0xB2C2 Gnd TOC2 Alarm OP Ground TOC 2 Alarm OP
0xB2C4 Gnd TOC2 Alarm DPO Ground TOC 2 Alarm DPO
0xB301 SGnd TOC1 Alrm PKP Sensitive Ground TOC 1 Alarm PKP
0xB302 SGnd TOC1 Alrm OP Sensitive Ground TOC 1 Alarm OP
0xB304 SGnd TOC1 Alrm DPO Sensitive Ground TOC 1 Alarm DPO
0xB641 SGnd IOC1 Alrm PKP Sensitive Ground IOC 1 Alarm PKP
0xB642 SGnd IOC1 Alrm OP Sensitive Ground IOC 1 Alarm OP
0xB644 SGnd IOC1 Alrm DPO Sensitive Ground IOC 1 Alarm DPO
0xB681 SGnd IOC2 Alrm PKP Sensitive Ground IOC 2 Alarm PKP
0xB682 SGnd IOC2 Alrm OP Sensitive Ground IOC 2 Alarm OP
0xB684 SGnd IOC2 Alrm DPO Sensitive Ground IOC 2 Alarm DPO
0xB6C1 NSeq IOC Alrm PKP Negative Sequence IOC Alarm PKP
0xB6C2 NSeq IOC Alrm OP NSeq IOC Alrm OP
0xB6C4 NSeq IOC Alrm DPO Negative Sequence IOC Alarm DPO
0xB701 Pcnt Diff Alrm PKP Pcnt Diff Alrm PKP
0xB702 Pcnt Diff Alrm OP Pcnt Diff Alrm OP
0xB704 Pcnt Diff Alrm DPO Pcnt Diff Alrm DPO
0xB709 Ph Dif A Alarm PKP Ph Dif A Alarm PKP
0xB70A Ph Dif A Alarm OP Ph Dif A Alarm OP
0xB70C Ph Dif A Alarm DPO Ph Dif A Alarm DPO
0xB711 Ph Dif B Alarm PKP Ph Dif B Alarm PKP
0xB712 Ph Dif B Alarm OP Ph Dif B Alarm OP
0xB714 Ph Dif B Alarm DPO Ph Dif B Alarm DPO
0xB721 Ph Dif C Alarm PKP Ph Dif C Alarm PKP
0xB722 Ph Dif C Alarm OP Ph Dif C Alarm OP
0xB724 Ph Dif C Alarm DPO Ph Dif C Alarm DPO
0xB741 RGF1 Alarm PKP RGF1 Alarm PKP
0xB742 RGF1 Alarm OP RGF1 Alarm OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-111


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xB744 RGF1 Alarm DPO RGF1 Alarm DPO
0xB781 RGF2 Alarm PKP RGF2 Alarm PKP
0xB782 RGF2 Alarm OP RGF2 Alarm OP
0xB784 RGF2 Alarm DPO RGF2 Alarm DPO
0xB7C1 Inst Diff Alrm PKP Inst Diff Alrm PKP
0xB7C2 Inst Diff Alrm OP Inst Diff Alrm OP
0xB7C4 Inst Diff Alrm DPO Inst Diff Alrm DPO
0xB801 NSeq TOC1 Alrm PKP Negative Sequence TOC 1 Alarm PKP
0xB802 NSeq TOC1 Alrm OP Negative Sequence TOC 1 Alarm OP
0xB804 NSeq TOC1 Alrm DPO Negative Sequence TOC 1 Alarm DPO
0xB841 NSeq TOC2 Alrm PKP Negative Sequence TOC 2 Alarm PKP
0xB842 NSeq TOC2 Alrm OP Negative Sequence TOC 2 Alarm OP
0xB844 NSeq TOC2 Alrm DPO Negative Sequence TOC 2 Alarm DPO
0xB901 NSeq IOC 2 AlrmPKP Negative Sequence IOC 2 Alarm PKP
0xB902 NSeq IOC 2 Alrm OP Negative Sequence IOC 2 Alarm OP
0xB904 NSeq IOC 2 AlrmDPO Negative Sequence IOC 2 Alarm DPO
0xB9C1 SGnd TOC2 Alrm PKP Sensitive Ground TOC 2 Alarm PKP
0xB9C2 SGnd TOC2 Alrm OP Sensitive Ground TOC 2 Alarm OP
0xB9C4 SGnd TOC2 Alrm DPO Sensitive Ground TOC 2 Alarm DPO
0xBA02 W1BKR Trp/Cls Fail W1 Breaker Trip/Close Fail
0xBA42 W1BKR Charge Fail W1 Breaker Charge Fail
0xBA82 W2BKR Trp/Cls Fail W2 Breaker Trip/Close Fail
0xBAC2 W2BKR Charge Fail W2 Breaker Charge Fail
0xBB02 W2BKRTrpCntrAlrm OP W2BKRTrpCntrAlrm OP
0xBC01 LE 9 Alarm PKP Logic Element 9 Alarm PKP
0xBC02 LE 9 Alarm OP Logic Element 9 Alarm OP
0xBC04 LE 9 Alarm DPO Logic Element 9 Alarm DPO
0xBC41 LE 10 Alarm PKP Logic Element 10 Alarm PKP
0xBC42 LE 10 Alarm OP Logic Element 10 Alarm OP
0xBC44 LE 10 Alarm DPO Logic Element 10 Alarm DPO
0xBC81 LE 11 Alarm PKP Logic Element 11 Alarm PKP
0xBC82 LE 11 Alarm OP Logic Element 11 Alarm OP
0xBC84 LE 11 Alarm DPO Logic Element 11 Alarm DPO
0xBCC1 LE 12 Alarm PKP Logic Element 12 Alarm PKP
0xBCC2 LE 12 Alarm OP Logic Element 12 Alarm OP
0xBCC4 LE 12 Alarm DPO Logic Element 12 Alarm DPO
0xBD01 LE 13 Alarm PKP Logic Element 13 Alarm PKP
0xBD02 LE 13 Alarm OP Logic Element 13 Alarm OP
0xBD04 LE 13 Alarm DPO Logic Element 13 Alarm DPO
0xBD41 LE 14 Alarm PKP Logic Element 14 Alarm PKP
0xBD42 LE 14 Alarm OP Logic Element 14 Alarm OP
0xBD44 LE 14 Alarm DPO Logic Element 14 Alarm DPO
0xBD81 LE 15 Alarm PKP Logic Element 15 Alarm PKP
0xBD82 LE 15 Alarm OP Logic Element 15 Alarm OP
0xBD84 LE 15 Alarm DPO Logic Element 15 Alarm DPO
0xBDC1 LE 16 Alarm PKP Logic Element 16 Alarm PKP
0xBDC2 LE 16 Alarm OP Logic Element 16 Alarm OP

11-112 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0xBDC4 LE 16 Alarm DPO Logic Element 16 Alarm DPO
0xC042 Output Relay 3 On Output Relay 3 On
0xC044 Output Relay 3 Off Output Relay 3 Off
0xC082 Output Relay 4 On Output Relay 4 On
0xC084 Output Relay 4 Off Output Relay 4 Off
0xC0C2 Output Relay 5 On Output Relay 5 On
0xC0C4 Output Relay 5 Off Output Relay 5 Off
0xC102 Output Relay 6 On Output Relay 6 On
0xC104 Output Relay 6 Off Output Relay 6 Off
0xC142 Self-Test Rly 7 OP Self-Test Rly 7 OP
0xC144 Self-Tst Rly 7 DPO Self-Tst Rly 7 DPO
0xC202 BKR Connected Breaker Connected OP
0xC2C2 BKR2 Connected Breaker 2 Connected OP
0xC401 Hot RTD PKP Hot RTD PKP
0xC402 Hot RTD OP Hot RTD OP
0xC482 Any Pkp OP Any Pkp OP
0xC4C1 LE 1 PKP Logic Element 1 PKP
0xC4C2 LE 1 OP Logic Element 1 OP
0xC4C4 LE 1 DPO Logic Element 1 DPO
0xC501 LE 2 PKP Logic Element 2 PKP
0xC502 LE 2 OP Logic Element 2 OP
0xC504 LE 2 DPO Logic Element 2 DPO
0xC541 LE 3 PKP Logic Element 3 PKP
0xC542 LE 3 OP Logic Element 3 OP
0xC544 LE 3 DPO Logic Element 3 DPO
0xC581 LE 4 PKP Logic Element 4 PKP
0xC582 LE 4 OP Logic Element 4 OP
0xC584 LE 4 DPO Logic Element 4 DPO
0xC5C1 LE 5 PKP Logic Element 5 PKP
0xC5C2 LE 5 OP Logic Element 5 OP
0xC5C4 LE 5 DPO Logic Element 5 DPO
0xC601 LE 6 PKP Logic Element 6 PKP
0xC602 LE 6 OP Logic Element 6 OP
0xC604 LE 6 DPO Logic Element 6 DPO
0xC641 LE 7 PKP Logic Element 7 PKP
0xC642 LE 7 OP Logic Element 7 OP
0xC644 LE 7 DPO Logic Element 7 DPO
0xC681 LE 8 PKP Logic Element 8 PKP
0xC682 LE 8 OP Logic Element 8 OP
0xC684 LE 8 DPO Logic Element 8 DPO
0xC882 Setpoint Group2 On Setpoint Group2 On
0xC982 Maint. Req. OP Maintenance Required OP
0xCA02 52a Contact OP 52a Contact OP
0xCA04 52a Contact DPO 52a Contact DPO
0xCA42 52b Contact OP 52b Contact OP
0xCA44 52b Contact DPO 52b Contact DPO
0xCA82 Reset OK Reset OK

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-113


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xCAC2 L/O Rst Closed OP Lockout Reset Closed OP
0xCAC4 L/O Rst Closed DPO Lockout Reset Closed DPO
0xCC01 Lockout PKP Lockout PKP
0xCC02 Lockout OP Lockout OP
0xCC04 Lockout DPO Lockout DPO
0xCC42 Testing ON Testing ON
0xCC44 Testing OFF Testing OFF
0xCCC2 BKR Stat Open Breaker Status Open OP
0xCD02 BKR Stat Clsd Breaker Status Closed OP
0xCD42 Setpoint Group1 On Setpoint Group1 On
0xDA02 BKR2 52a Cont OP BKR2 52a Cont OP
0xDA04 BKR2 52a Cont DPO BKR2 52a Cont DPO
0xDA42 BKR2 52b Cont OP BKR2 52b Cont OP
0xDA44 BKR2 52b Cont DPO BKR2 52b Cont DPO
0xDA81 BKR2 Stat Open PKP BKR2 Stat Open PKP
0xDA82 BKR2 Stat Open BKR2 Stat Open
0xDA84 BKR2 Stat Open DPO BKR2 Stat Open DPO
0xDAC1 BKR2 Stat Clsd PKP BKR2 Stat Clsd PKP
0xDAC2 BKR2 Stat Clsd BKR2 Stat Clsd
0xDAC4 BKR2 Stat Clsd DPO BKR2 Stat Clsd DPO
0xDB01 Trip BKR 1 PKP Trip BKR 1 PKP
0xDB02 Trip BKR 1 OP Trip BKR 1 OP
0xDB04 Trip BKR 1 DPO Trip BKR 1 DPO
0xDB41 Trip BKR 2 PKP Trip BKR 2 PKP
0xDB42 Trip BKR 2 OP Trip BKR 2 OP
0xDB44 Trip BKR 2 DPO Trip BKR 2 DPO
0xDB82 2nd Hmnc Diff OP 2nd Hmnc Diff OP
0xDB8A 2nd Hmnc Diff Ph A 2nd Harmonic Diff Ph A
0xDB92 2nd Hmnc Diff Ph B 2nd Harmonic Diff Ph B
0xDBA2 2nd Hmnc Diff Ph C 2nd Harmonic Diff Ph C
0xDBC2 5th Hmnc Diff OP 5th Hmnc Diff OP
0xDBCA 5th Hmnc Diff Ph A 5th Harmonic Diff Ph A
0xDBD2 5th Hmnc Diff Ph B 5th Harmonic Diff Ph B
0xDBE2 5th Hmnc Diff Ph C 5th Harmonic Diff Ph C
0xDC01 LE 9 PKP Logic Element 9 PKP
0xDC02 LE 9 OP Logic Element 9 OP
0xDC04 LE 9 DPO Logic Element 9 DPO
0xDC41 LE 10 PKP Logic Element 10 PKP
0xDC42 LE 10 OP Logic Element 10 OP
0xDC44 LE 10 DPO Logic Element 10 DPO
0xDC81 LE 11 PKP Logic Element 11 PKP
0xDC82 LE 11 OP Logic Element 11 OP
0xDC84 LE 11 DPO Logic Element 11 DPO
0xDCC1 LE 12 PKP Logic Element 12 PKP
0xDCC2 LE 12 OP Logic Element 12 OP
0xDCC4 LE 12 DPO Logic Element 12 DPO
0xDD01 LE 13 PKP Logic Element 13 PKP

11-114 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0xDD02 LE 13 OP Logic Element 13 OP
0xDD04 LE 13 DPO Logic Element 13 DPO
0xDD41 LE 14 PKP Logic Element 14 PKP
0xDD42 LE 14 OP Logic Element 14 OP
0xDD44 LE 14 DPO Logic Element 14 DPO
0xDD81 LE 15 PKP Logic Element 15 PKP
0xDD82 LE 15 OP Logic Element 15 OP
0xDD84 LE 15 DPO Logic Element 15 DPO
0xDDC1 LE 16 PKP Logic Element 16 PKP
0xDDC2 LE 16 OP Logic Element 16 OP
0xDDC4 LE 16 DPO Logic Element 16 DPO
0xE002 Any Block Any Block
0xE004 Any Block DPO Any Block DPO
0xE042 Therm O/L Block Thermal Level Block
0xE044 Therm O/L Blk DPO Thermal Level Block DPO
0xE082 RTD1 Block RTD1 Block
0xE084 RTD1 Blk DPO RTD1 Blk DPO
0xE0C2 RTD2 Block RTD2 Block
0xE0C4 RTD2 Blk DPO RTD2 Blk DPO
0xE102 RTD3 Block RTD3 Block
0xE104 RTD3 Blk DPO RTD3 Blk DPO
0xE142 RTD4 Block RTD4 Block
0xE144 RTD4 Blk DPO RTD4 Blk DPO
0xE182 Output Relay 1 Blk Output Relay 1 Block
0xE184 Relay 1 Blk DPO Relay 1 Block DPO
0xE1C2 Output Relay 2 Blk Output Relay 2 Block
0xE1C4 Relay 2 Blk DPO Relay 2 Block DPO
0xE202 RTD5 Block RTD5 Block
0xE204 RTD5 Blk DPO RTD5 Blk DPO
0xE242 RTD6 Block RTD6 Block
0xE244 RTD6 Blk DPO RTD6 Blk DPO
0xE282 RTD7 Block RTD7 Block
0xE284 RTD7 Blk DPO RTD7 Blk DPO
0xE2C2 RTD8 Block RTD8 Block
0xE2C4 RTD8 Blk DPO RTD8 Blk DPO
0xE302 RTD9 Block RTD9 Block
0xE304 RTD9 Blk DPO RTD9 Blk DPO
0xE342 RTD10 Block RTD10 Block
0xE344 RTD10 Blk DPO RTD10 Blk DPO
0xE382 RTD11 Block RTD11 Block
0xE384 RTD11 Blk DPO RTD11 Blk DPO
0xE3C2 RTD12 Block RTD12 Block
0xE3C4 RTD12 Blk DPO RTD12 Blk DPO
0xE402 RTDTrouble Block RTDTrouble Block
0xE404 RTDTrouble Blk DPO RTDTrouble Blk DPO
0xE6C2 Curr Dmd1 Block Current Demand 1 Block OP
0xE6C4 Curr Dmd1 Blk DPO Current Demand 1 Block DPO

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-115


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xE702 Curr Dmd2 Block Current Demand 2 Block OP
0xE704 Curr Dmd2 Blk DPO Current Demand 2 Block DPO
0xE882 Group Change Blk Group Change Blk
0xE884 Grp Change Blk DPO Group Change Block DPO
0xEC02 Lockout Block Lockout Block
0xEC04 Lockout Block DPO Lockout Block DPO
0xF002 Ph IOC1 Block Phase IOC 1 Block
0xF004 Ph IOC1 Block DPO Phase IOC 1 Block DPO
0xF042 Ntrl IOC1 Block Neutral IOC 1 Block
0xF044 Ntrl IOC1 Blk DPO Neutral IOC 1 Block DPO
0xF082 Gnd IOC1 Block Ground IOC 1 Block
0xF084 Gnd IOC1 Block DPO Ground IOC 1 Block DPO
0xF0C2 Ph TOC1 Block Phase TOC 1 Block
0xF0C4 Ph TOC1 Block DPO Phase TOC 1 Block DPO
0xF102 Ntrl TOC1 Block Neutral TOC 1 Block
0xF104 Ntrl TOC1 BlockDPO Neutral TOC 1 Block DPO
0xF142 Gnd TOC1 Block Ground TOC 1 Block
0xF144 Gnd TOC1 Block DPO Ground TOC 1 Block DPO
0xF182 Ph IOC2 Block Phase IOC 2 Block
0xF184 Ph IOC2 Block DPO Phase IOC 2 Block DPO
0xF1C2 Ntrl IOC2 Block Neutral IOC 2 Block
0xF1C4 Ntrl IOC2 Blk DPO Neutral IOC 2 Block DPO
0xF202 Gnd IOC2 Block Ground IOC 2 Block
0xF204 Gnd IOC2 Block DPO Ground IOC 2 Block DPO
0xF242 Ph TOC2 Block Phase TOC 2 Block
0xF244 Ph TOC2 Block DPO Phase TOC 2 Block DPO
0xF282 Ntrl TOC2 Block Neutral TOC 2 Block
0xF284 Ntrl TOC2 Blk DPO Neutral TOC 2 Block DPO
0xF2C2 Gnd TOC2 Block Ground TOC 2 Block
0xF2C4 Gnd TOC2 Blk DPO Ground TOC 2 Block DPO
0xF302 SGnd TOC1 Block Sensitive Ground TOC 1 Block
0xF304 SGnd TOC1 BlockDPO Sensitive Ground TOC 1 Block DPO
0xF642 SGnd IOC1 Block Sensitive Ground IOC 1 Block
0xF644 SGnd IOC1 Blk DPO Sensitive Ground IOC 1 Block DPO
0xF682 SGnd IOC2 Block Sensitive Ground IOC 2 Block
0xF684 SGnd IOC2 Blk DPO Sensitive Ground IOC 2 Block DPO
0xF6C2 NSeq IOC Block Negative Sequence IOC Block
0xF6C4 NSeq IOC Block DPO Negative Sequence IOC Block DPO
0xF702 Pcnt Diff Block Pcnt Diff Block
0xF704 Ph Diff Block DPO Ph Diff Block DPO
0xF742 RGF1 Block RGF1 Block
0xF744 RGF1 Block DPO RGF1 Block DPO
0xF782 RGF2 Block RGF2 Block
0xF784 RGF2 Block DPO RGF2 Block DPO
0xF7C2 Inst Diff Block Inst Diff Block
0xF7C4 Inst Diff BlockDPO Inst Diff BlockDPO
0xF802 NSeq TOC1 Blk Negative Sequence TOC 1 Block

11-116 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0xF804 NSeq TOC1 Blk DPO Negative Sequence TOC 1 Block DPO
0xF842 NSeq TOC2 Blk Negative Sequence TOC 2 Block
0xF844 NSeq TOC2 Blk DPO Negative Sequence TOC 2 Block DPO
0xF902 NSeq IOC 2 Block Negative Sequence IOC 2 Block
0xF904 NSeq IOC 2 Blk DPO Negative Sequence IOC 2 Block DPO
0xF9C2 SGnd TOC2 Block Sensitive Ground TOC 2 Block
0xF9C4 SGnd TOC2 Blk DPO Sensitive Ground TOC 2 Block DPO
0xFB02 Trip BKR1 Blk Trip BKR1 Blk
0xFB04 Trip BKR1 Blk DPO Trip Breaker 1 Block DPO
0xFB42 Trip BKR2 Blk Trip BKR2 Blk
0xFB44 Trip BKR2 Blk DPO Trip Breaker 2 Block DPO
FC134A unsigned 16 bits Active Targets
0 No Active Targets No Active Targets
7 Clock Not Set Clock Not Set
8 IRIG-B Failure IRIG-B Failure
14 Comm. Alert 1 Comm. Alert 1
15 Comm. Alert 2 Comm. Alert 2
16 Comm. Alert 3 Comm. Alert 3
17 Ethernet Link Fail Ethernet Link Failure
18 High ENET Traffic High Ethernet Traffic
19 Intern Temp. >80C Internal Temperature High
20 RMIO Mismatch RMIO Mismatch
21 BKR2 Status Unkwn BKR2 Status Unkwn
40 Eth Link A Fail Ethernet Link A Fail
41 Eth Link B Fail Ethernet Link B Fail
0x8040 Therm O/L Trip Therm O/L Trip
0x8080 RTD 1 Trip RTD 1 Trip
0x80C0 RTD 2 Trip RTD 2 Trip
0x8100 RTD 3 Trip RTD 3 Trip
0x8140 RTD 4 Trip RTD 4 Trip
0x8200 RTD 5 Trip RTD 5 Trip
0x8240 RTD 6 Trip RTD 6 Trip
0x8280 RTD 7 Trip RTD 7 Trip
0x82C0 RTD 8 Trip RTD 8 Trip
0x8300 RTD 9 Trip RTD 9 Trip
0x8340 RTD 10 Trip RTD 10 Trip
0x8380 RTD 11 Trip RTD 11 Trip
0x83C0 RTD 12 Trip RTD 12 Trip
0x8480 Relay Not Config Relay Not Config
0x84C0 LE 1 Trip Logic Element 1 Trip
0x8500 LE 2 Trip Logic Element 2 Trip
0x8540 LE 3 Trip Logic Element 3 Trip
0x8580 LE 4 Trip Logic Element 4 Trip
0x85C0 LE 5 Trip Logic Element 5 Trip
0x8600 LE 6 Trip Logic Element 6 Trip
0x8640 LE 7 Trip Logic Element 7 Trip
0x8680 LE 8 Trip Logic Element 8 Trip

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-117


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x89C0 Self Test Trip Self Test Trip
0x8D00 Rly #1 Trip OP Rly #1 Trip OP
0x8D40 Rly #2 Trip OP Rly #2 Trip OP
0x8D80 BKR Failure BKR Failure
0x8F40 Breaker 2 Failure Breaker 2 Failure
0x9000 Ph IOC1 Trip Phase IOC 1 Trip
0x9040 Ntrl IOC1 Trip Neutral IOC 1 Trip
0x9080 Gnd IOC1 Trip Ground IOC 1 Trip
0x90C0 Ph TOC1 Trip Phase TOC 1 Trip
0x9100 Ntrl TOC1 Trip Neutral TOC 1 Trip
0x9140 Gnd TOC1 Trip Ground TOC 1 Trip
0x9180 Ph IOC2 Trip Phase IOC 2 Trip
0x91C0 Ntrl IOC2 Trip Neutral IOC 2 Trip
0x9200 Gnd IOC2 Trip Ground IOC 2 Trip
0x9240 Ph TOC2 Trip Phase TOC 2 Trip
0x9280 Ntrl TOC2 Trip Neutral TOC 2 Trip
0x92C0 Gnd TOC2 Trip Ground TOC 2 Trip
0x9300 SGnd TOC1 Trip Sensitive Ground TOC 1 Trip
0x9640 SGnd IOC1 Trip Sensitive Ground IOC 1 Trip
0x9680 SGnd IOC2 Trip Sensitive Ground IOC 2 Trip
0x96C0 NSeq IOC Trip Negative Sequence IOC Trip
0x9700 Pcnt DIFF Trip Pcnt DIFF Trip
0x9740 RGF1 Trip RGF1 Trip
0x9780 RGF2 Trip RGF2 Trip
0x97C0 Inst DIFF Trip Inst DIFF Trip
0x9800 NSeq TOC1 Trip Negative Sequence TOC 1 Trip
0x9840 NSeq TOC2 Trip Negative Sequence TOC 2 Trip
0x9900 NSeq IOC 2 Trip Negative Sequence IOC 2 Trip
0x99C0 SGnd TOC2 Trip Sensitive Ground TOC 2 Trip
0x9C00 LE 9 Trip Logic Element 9 Trip
0x9C40 LE 10 Trip Logic Element 10 Trip
0x9C80 LE 11 Trip Logic Element 11 Trip
0x9CC0 LE 12 Trip Logic Element 12 Trip
0x9D00 LE 13 Trip Logic Element 13 Trip
0x9D40 LE 14 Trip Logic Element 14 Trip
0x9D80 LE 15 Trip Logic Element 15 Trip
0x9DC0 LE 16 Trip Logic Element 16 Trip
0xA040 Therm Lvl Alrm Thermal Level Alarm
0xA080 RTD 1 Alarm RTD 1 Alarm
0xA0C0 RTD 2 Alarm RTD 2 Alarm
0xA100 RTD 3 Alarm RTD 3 Alarm
0xA140 RTD 4 Alarm RTD 4 Alarm
0xA200 RTD 5 Alarm RTD 5 Alarm
0xA240 RTD 6 Alarm RTD 6 Alarm
0xA280 RTD 7 Alarm RTD 7 Alarm
0xA2C0 RTD 8 Alarm RTD 8 Alarm
0xA300 RTD 9 Alarm RTD 9 Alarm

11-118 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0xA340 RTD 10 Alarm RTD 10 Alarm
0xA380 RTD 11 Alarm RTD 11 Alarm
0xA3C0 RTD 12 Alarm RTD 12 Alarm
0xA400 RTD Trouble Alrm RTD Trouble Alarm
0xA480 Not Configured Not Configured
0xA4C0 LE 1 Alarm Logic Element 1 Alarm
0xA500 LE 2 Alarm Logic Element 2 Alarm
0xA540 LE 3 Alarm Logic Element 3 Alarm
0xA580 LE 4 Alarm Logic Element 4 Alarm
0xA5C0 LE 5 Alarm Logic Element 5 Alarm
0xA600 LE 6 Alarm Logic Element 6 Alarm
0xA640 LE 7 Alarm Logic Element 7 Alarm
0xA680 LE 8 Alarm Logic Element 8 Alarm
0xA6C0 Curr Dmd1 Alrm Current Demand 1 Alarm
0xA700 Curr Dmd2 Alrm Current Demand 2 Alarm
0xA840 W1BKR Alarm W1 Breaker Alarm
0xA880 W1BKR Trip Time W1 Breaker Trip Time
0xA8C0 W1BKR Close Time W1 Breaker Close Time
0xA900 W1BKR Charge Time W1 Breaker Charge Time
0xA940 W2BKR Alarm W2 Breaker Alarm
0xA980 W2BKR Trip Time W2 Breaker Trip Time
0xA9C0 W2BKR Close Time W2 Breaker Close Time
0xAA00 W2BKR Charge Time W2 Breaker Charge Time
0xABC0 HI Ambient Temp High Ambient Temperature Alarm
0xAC00 LO Ambient Temp Low Ambient Temperature Alarm
0xAC40 Self Test Alarm Self Test Alarm
0xACC0 BKRTrpCntrAlrm Breaker Trip Control Alarm
0xAD00 Rly1 Coil Mn Alrm Relay # 1 Coil Monitor Alarm
0xAD40 Rly2 Coil Mn Alrm Relay # 2 Coil Monitor Alarm
0xAD80 BKR Fail Alrm BKR Fail Alrm
0xADC0 BKRStatus Fail Breaker Status Fail
0xAEC0 BKR2 Status Fail BKR2 Status Fail
0xAF40 BKR2 Fail Alrm BKR2 Fail Alrm
0xB000 Ph IOC1 Alarm Phase IOC 1 Alarm
0xB040 Ntrl IOC1 Alarm Neutral IOC 1 Alarm
0xB080 Gnd IOC1 Alarm Ground IOC 1 Alarm
0xB0C0 Ph TOC1 Alarm Phase TOC 1 Alarm
0xB100 Ntrl TOC1 Alrm Neutral TOC 1 Alarm
0xB140 Gnd TOC1 Alarm Ground TOC 1 Alarm
0xB180 Ph IOC2 Alarm Phase IOC 2 Alarm
0xB1C0 Ntrl IOC2 Alarm Neutral IOC 2 Alarm
0xB200 Gnd IOC2 Alarm Ground IOC 2 Alarm
0xB240 Ph TOC2 Alarm Phase TOC 2 Alarm
0xB280 Ntrl TOC2 Alrm Neutral TOC 2 Alarm
0xB2C0 Gnd TOC2 Alarm Ground TOC 2 Alarm
0xB300 SGnd TOC1 Alarm Sensitive Ground TOC 1 Alarm
0xB640 SGnd IOC1 Alarm Sensitive Ground IOC 1 Alarm

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-119


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xB680 SGnd IOC2 Alarm Sensitive Ground IOC 2 Alarm
0xB6C0 NSeq IOC Alrm Negative Sequence IOC Alarm
0xB700 Pcnt DIFF Alarm Pcnt DIFF Alarm
0xB740 RGF1 Alarm RGF1 Alarm
0xB780 RGF2 Alarm RGF2 Alarm
0xB7C0 Inst DIFF Alarm Inst DIFF Alarm
0xB800 NSeq TOC1 Alarm Negative Sequence TOC 1 Alarm
0xB840 NSeq TOC2 Alarm Negative Sequence TOC 2 Alarm
0xB900 NSeq IOC 2 Alarm Negative Sequence IOC 2 Alarm
0xB9C0 SGnd TOC2 Alarm Sensitive Ground TOC 2 Alarm
0xBA00 W1BKR Trp/Cls Fail W1 Breaker Trip/Close Fail
0xBA40 W1BKR Charge Fail W1 Breaker Charge Fail
0xBA80 W2BKR Trp/Cls Fail W2 Breaker Trip/Close Fail
0xBAC0 W2BKR Charge Fail W2 Breaker Charge Fail
0xBB00 W2BKRTrpCntAlrm W2BKRTrpCntAlrm
0xBC00 LE 9 Alarm Logic Element 9 Alarm
0xBC40 LE 10 Alarm Logic Element 10 Alarm
0xBC80 LE 11 Alarm Logic Element 11 Alarm
0xBCC0 LE 12 Alarm Logic Element 12 Alarm
0xBD00 LE 13 Alarm Logic Element 13 Alarm
0xBD40 LE 14 Alarm Logic Element 14 Alarm
0xBD80 LE 15 Alarm Logic Element 15 Alarm
0xBDC0 LE 16 Alarm Logic Element 16 Alarm
0xC040 Output Relay 3 Output Relay 3
0xC080 Output Relay 4 Output Relay 4
0xC0C0 Output Relay 5 Output Relay 5
0xC100 Output Relay 6 Output Relay 6
0xC140 Output Relay 7 Output Relay 7
0xC180 Relay1 Coil Relay # 1 Coil
0xC1C0 Relay2 Coil Relay # 2 Coil
0xC200 BKR Connected Breaker Connected
0xC2C0 BKR2 Connected Breaker 2 Connected
0xC400 Hot RTD Hot RTD
0xC4C0 LE 1 LE 1
0xC500 LE 2 LE 2
0xC540 LE 3 LE 3
0xC580 LE 4 LE 4
0xC5C0 LE 5 LE 5
0xC600 LE 6 LE 6
0xC640 LE 7 LE 7
0xC680 LE 8 LE 8
0xC880 Setpoint Group2 Setpoint Group2
0xC980 Maint Required Maint Required
0xCA00 52a Contact 52a Contact
0xCA40 52b Contact 52b Contact
0xCA80 Reset OK Reset OK
0xCAC0 L/O Rst Closed Lockout Reset Closed

11-120 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0xCC00 Lockout Lockout
0xCC40 Testing Testing
0xCD00 BKR Stat Clsd Breaker Status Closed
0xCD40 Setpoint Group1 Setpoint Group1
0xDA00 BKR 2 52a Contact BKR 2 52a Contact
0xDA40 BKR 2 52b Contact BKR 2 52b Contact
0xDA80 BKR 2 Status Open BKR 2 Status Open
0xDAC0 BKR2 Status Closed BKR2 Status Closed
0xDB00 Trip BKR 1 Trip Breaker 1
0xDB40 Trip BKR 2 Trip Breaker 2
0xDB80 2nd Hmnc Diff 2nd Harmonic Diff
0xDBC0 5th Hmnc Diff 5th Harmonic Diff
0xDC00 LE 9 LE 9
0xDC40 LE 10 LE 10
0xDC80 LE 11 LE 11
0xDCC0 LE 12 LE 12
0xDD00 LE 13 LE 13
0xDD40 LE 14 LE 14
0xDD80 LE 15 LE 15
0xDDC0 LE 16 LE 16
0xE040 Therm O/L Block Thermal Level Block
0xE080 RTD1 Block RTD1 Block
0xE0C0 RTD2 Block RTD2 Block
0xE100 RTD3 Block RTD3 Block
0xE140 RTD4 Block RTD4 Block
0xE180 Output Relay 1 BLK Output Relay 1 BLK
0xE1C0 Output Relay 2 BLK Output Relay 2 BLK
0xE200 RTD5 Block RTD5 Block
0xE240 RTD6 Block RTD6 Block
0xE280 RTD7 Block RTD7 Block
0xE2C0 RTD8 Block RTD8 Block
0xE300 RTD9 Block RTD9 Block
0xE340 RTD10 Block RTD10 Block
0xE380 RTD11 Block RTD11 Block
0xE3C0 RTD12 Block RTD12 Block
0xE400 RTD Trouble Blk RTD Trouble Blk
0xE6C0 Curr Dmd1 Block Current Demand 1 Block
0xE700 Curr Dmd2 Block Current Demand 2 Block
0xE880 Group Change Blk Group Change Blk
0xEC00 Lockout Block Lockout Block
0xF000 Ph IOC1 Block Phase IOC 1 Block
0xF040 Ntrl IOC1 Block Neutral IOC 1 Block
0xF080 Gnd IOC1 Block Ground IOC 1 Block
0xF0C0 Ph TOC1 Block Phase TOC 1 Block
0xF100 Ntrl TOC1 Block Neutral TOC 1 Block
0xF140 Gnd TOC1 Block Ground TOC 1 Block
0xF180 Ph IOC2 Block Phase IOC 2 Block

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-121


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xF1C0 Ntrl IOC2 Block Neutral IOC 2 Block
0xF200 Gnd IOC2 Block Ground IOC 2 Block
0xF240 Ph TOC2 Block Phase TOC 2 Block
0xF280 Ntrl TOC2 Block Neutral TOC 2 Block
0xF2C0 Gnd TOC2 Block Ground TOC 2 Block
0xF300 SGnd TOC1 Block Sensitive Ground TOC 1 Block
0xF640 SGnd IOC1 Block Sensitive Ground IOC 1 Block
0xF680 SGnd IOC2 Block Sensitive Ground IOC 2 Block
0xF6C0 NSeq IOC Block Negative Sequence IOC Block
0xF700 Pcnt DIFF Block Pcnt DIFF Block
0xF740 RGF1 Block RGF1 Block
0xF780 RGF2 Block RGF2 Block
0xF7C0 Inst DIFF Block Inst DIFF Block
0xF800 NSeq TOC1 Block Negative Sequence TOC 1 Block
0xF840 NSeq TOC2 Block Negative Sequence TOC 2 Block
0xF900 NSeq IOC 2 Block Negative Sequence IOC 2 Block
0xF9C0 SGnd TOC2 Block Sensitive Ground TOC 2 Block
0xFB00 Trip BKR1 Block Trip BKR1 Block
0xFB40 Trip BKR2 Block Trip BKR2 Block
FC134B unsigned 16 bits DNP Binary Inputs
0 Off Off
0x0001 On On
0x0040 Contact IN 1 On Contact Input 1 On
0x0041 Contact IN 2 On Contact Input 2 On
0x0042 Contact IN 3 On Contact Input 3 On
0x0043 Contact IN 4 On Contact Input 4 On
0x0044 Contact IN 5 On Contact Input 5 On
0x0045 Contact IN 6 On Contact Input 6 On
0x0046 Contact IN 7 On Contact Input 7 On
0x0047 Contact IN 8 On Contact Input 8 On
0x0048 Contact IN 9 On Contact Input 9 On
0x0049 Contact IN 10 On Contact Input 10 On
0x0060 Contact IN 1 Off Contact Input 1 Off
0x0061 Contact IN 2 Off Contact Input 2 Off
0x0062 Contact IN 3 Off Contact Input 3 Off
0x0063 Contact IN 4 Off Contact Input 4 Off
0x0064 Contact IN 5 Off Contact Input 5 Off
0x0065 Contact IN 6 Off Contact Input 6 Off
0x0066 Contact IN 7 Off Contact Input 7 Off
0x0067 Contact IN 8 Off Contact Input 8 Off
0x0068 Contact IN 9 Off Contact Input 9 Off
0x0069 Contact IN 10 Off Contact Input 10 Off
0x0080 Virtual IN 1 On Virtual Input 1 On
0x0081 Virtual IN 2 On Virtual Input 2 On
0x0082 Virtual IN 3 On Virtual Input 3 On
0x0083 Virtual IN 4 On Virtual Input 4 On
0x0084 Virtual IN 5 On Virtual Input 5 On

11-122 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x0085 Virtual IN 6 On Virtual Input 6 On
0x0086 Virtual IN 7 On Virtual Input 7 On
0x0087 Virtual IN 8 On Virtual Input 8 On
0x0088 Virtual IN 9 On Virtual Input 9 On
0x0089 Virtual IN 10 On Virtual Input 10 On
0x008A Virtual IN 11 On Virtual Input 11 On
0x008B Virtual IN 12 On Virtual Input 12 On
0x008C Virtual IN 13 On Virtual Input 13 On
0x008D Virtual IN 14 On Virtual Input 14 On
0x008E Virtual IN 15 On Virtual Input 15 On
0x008F Virtual IN 16 On Virtual Input 16 On
0x0090 Virtual IN 17 On Virtual Input 17 On
0x0091 Virtual IN 18 On Virtual Input 18 On
0x0092 Virtual IN 19 On Virtual Input 19 On
0x0093 Virtual IN 20 On Virtual Input 20 On
0x0094 Virtual IN 21 On Virtual Input 21 On
0x0095 Virtual IN 22 On Virtual Input 22 On
0x0096 Virtual IN 23 On Virtual Input 23 On
0x0097 Virtual IN 24 On Virtual Input 24 On
0x0098 Virtual IN 25 On Virtual Input 25 On
0x0099 Virtual IN 26 On Virtual Input 26 On
0x009A Virtual IN 27 On Virtual Input 27 On
0x009B Virtual IN 28 On Virtual Input 28 On
0x009C Virtual IN 29 On Virtual Input 29 On
0x009D Virtual IN 30 On Virtual Input 30 On
0x009E Virtual IN 31 On Virtual Input 31 On
0x009F Virtual IN 32 On Virtual Input 32 On
0x00A0 Virtual IN 1 Off Virtual Input 1 Off
0x00A1 Virtual IN 2 Off Virtual Input 2 Off
0x00A2 Virtual IN 3 Off Virtual Input 3 Off
0x00A3 Virtual IN 4 Off Virtual Input 4 Off
0x00A4 Virtual IN 5 Off Virtual Input 5 Off
0x00A5 Virtual IN 6 Off Virtual Input 6 Off
0x00A6 Virtual IN 7 Off Virtual Input 7 Off
0x00A7 Virtual IN 8 Off Virtual Input 8 Off
0x00A8 Virtual IN 9 Off Virtual Input 9 Off
0x00A9 Virtual IN 10 Off Virtual Input 10 Off
0x00AA Virtual IN 11 Off Virtual Input 11 Off
0x00AB Virtual IN 12 Off Virtual Input 12 Off
0x00AC Virtual IN 13 Off Virtual Input 13 Off
0x00AD Virtual IN 14 Off Virtual Input 14 Off
0x00AE Virtual IN 15 Off Virtual Input 15 Off
0x00AF Virtual IN 16 Off Virtual Input 16 Off
0x00B0 Virtual IN 17 Off Virtual Input 17 Off
0x00B1 Virtual IN 18 Off Virtual Input 18 Off
0x00B2 Virtual IN 19 Off Virtual Input 19 Off
0x00B3 Virtual IN 20 Off Virtual Input 20 Off

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-123


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x00B4 Virtual IN 21 Off Virtual Input 21 Off
0x00B5 Virtual IN 22 Off Virtual Input 22 Off
0x00B6 Virtual IN 23 Off Virtual Input 23 Off
0x00B7 Virtual IN 24 Off Virtual Input 24 Off
0x00B8 Virtual IN 25 Off Virtual Input 25 Off
0x00B9 Virtual IN 26 Off Virtual Input 26 Off
0x00BA Virtual IN 27 Off Virtual Input 27 Off
0x00BB Virtual IN 28 Off Virtual Input 28 Off
0x00BC Virtual IN 29 Off Virtual Input 29 Off
0x00BD Virtual IN 30 Off Virtual Input 30 Off
0x00BE Virtual IN 31 Off Virtual Input 31 Off
0x00BF Virtual IN 32 Off Virtual Input 32 Off
0x01C0 Remote IN 1 On Remote Input 1 On
0x01C1 Remote IN 2 On Remote Input 2 On
0x01C2 Remote IN 3 On Remote Input 3 On
0x01C3 Remote IN 4 On Remote Input 4 On
0x01C4 Remote IN 5 On Remote Input 5 On
0x01C5 Remote IN 6 On Remote Input 6 On
0x01C6 Remote IN 7 On Remote Input 7 On
0x01C7 Remote IN 8 On Remote Input 8 On
0x01C8 Remote IN 9 On Remote Input 9 On
0x01C9 Remote IN 10 On Remote Input 10 On
0x01CA Remote IN 11 On Remote Input 11 On
0x01CB Remote IN 12 On Remote Input 12 On
0x01CC Remote IN 13 On Remote Input 13 On
0x01CD Remote IN 14 On Remote Input 14 On
0x01CE Remote IN 15 On Remote Input 15 On
0x01CF Remote IN 16 On Remote Input 16 On
0x01D0 Remote IN 17 On Remote Input 17 On
0x01D1 Remote IN 18 On Remote Input 18 On
0x01D2 Remote IN 19 On Remote Input 19 On
0x01D3 Remote IN 20 On Remote Input 20 On
0x01D4 Remote IN 21 On Remote Input 21 On
0x01D5 Remote IN 22 On Remote Input 22 On
0x01D6 Remote IN 23 On Remote Input 23 On
0x01D7 Remote IN 24 On Remote Input 24 On
0x01D8 Remote IN 25 On Remote Input 25 On
0x01D9 Remote IN 26 On Remote Input 26 On
0x01DA Remote IN 27 On Remote Input 27 On
0x01DB Remote IN 28 On Remote Input 28 On
0x01DC Remote IN 29 On Remote Input 29 On
0x01DD Remote IN 30 On Remote Input 30 On
0x01DE Remote IN 31 On Remote Input 31 On
0x01DF Remote IN 32 On Remote Input 32 On
0x01E0 Remote IN 1 Off Remote Input 1 Off
0x01E1 Remote IN 2 Off Remote Input 2 Off
0x01E2 Remote IN 3 Off Remote Input 3 Off

11-124 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x01E3 Remote IN 4 Off Remote Input 4 Off
0x01E4 Remote IN 5 Off Remote Input 5 Off
0x01E5 Remote IN 6 Off Remote Input 6 Off
0x01E6 Remote IN 7 Off Remote Input 7 Off
0x01E7 Remote IN 8 Off Remote Input 8 Off
0x01E8 Remote IN 9 Off Remote Input 9 Off
0x01E9 Remote IN 10 Off Remote Input 10 Off
0x01EA Remote IN 11 Off Remote Input 11 Off
0x01EB Remote IN 12 Off Remote Input 12 Off
0x01EC Remote IN 13 Off Remote Input 13 Off
0x01ED Remote IN 14 Off Remote Input 14 Off
0x01EE Remote IN 15 Off Remote Input 15 Off
0x01EF Remote IN 16 Off Remote Input 16 Off
0x01F0 Remote IN 17 Off Remote Input 17 Off
0x01F1 Remote IN 18 Off Remote Input 18 Off
0x01F2 Remote IN 19 Off Remote Input 19 Off
0x01F3 Remote IN 20 Off Remote Input 20 Off
0x01F4 Remote IN 21 Off Remote Input 21 Off
0x01F5 Remote IN 22 Off Remote Input 22 Off
0x01F6 Remote IN 23 Off Remote Input 23 Off
0x01F7 Remote IN 24 Off Remote Input 24 Off
0x01F8 Remote IN 25 Off Remote Input 25 Off
0x01F9 Remote IN 26 Off Remote Input 26 Off
0x01FA Remote IN 27 Off Remote Input 27 Off
0x01FB Remote IN 28 Off Remote Input 28 Off
0x01FC Remote IN 29 Off Remote Input 29 Off
0x01FD Remote IN 30 Off Remote Input 30 Off
0x01FE Remote IN 31 Off Remote Input 31 Off
0x01FF Remote IN 32 Off Remote Input 32 Off
0x8002 Any Trip Any Trip
0x8042 Therm O/L Trip OP Thermal Overload Trip OP
0x8044 Therm O/L Trip DPO Thermal Overload Trip DPO
0x804A Therm PhA Trip OP Thermal Phase A Trip OP
0x804C Therm PhA Trip DPO Thermal Phase A Trip DPO
0x8052 Therm PhB Trip OP Thermal Phase B Trip OP
0x8054 Therm PhB Trip DPO Thermal Phase B Trip DPO
0x8062 Therm PhC Trip OP Thermal Phase C Trip OP
0x8064 Therm PhC Trip DPO Thermal Phase C Trip DPO
0x8081 RTD 1 Trip PKP RTD 1 Trip PKP
0x8082 RTD 1 Trip OP RTD 1 Trip OP
0x80C1 RTD 2 Trip PKP RTD 2 Trip PKP
0x80C2 RTD 2 Trip OP RTD 2 Trip OP
0x8101 RTD 3 Trip PKP RTD 3 Trip PKP
0x8102 RTD 3 Trip OP RTD 3 Trip OP
0x8141 RTD 4 Trip PKP RTD 4 Trip PKP
0x8142 RTD 4 Trip OP RTD 4 Trip OP
0x8201 RTD 5 Trip PKP RTD 5 Trip PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-125


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x8202 RTD 5 Trip OP RTD 5 Trip OP
0x8241 RTD 6 Trip PKP RTD 6 Trip PKP
0x8242 RTD 6 Trip OP RTD 6 Trip OP
0x8281 RTD 7 Trip PKP RTD 7 Trip PKP
0x8282 RTD 7 Trip OP RTD 7 Trip OP
0x82C1 RTD 8 Trip PKP RTD 8 Trip PKP
0x82C2 RTD 8 Trip OP RTD 8 Trip OP
0x8301 RTD 9 Trip PKP RTD 9 Trip PKP
0x8302 RTD 9 Trip OP RTD 9 Trip OP
0x8341 RTD 10 Trip PKP RTD 10 Trip PKP
0x8342 RTD 10 Trip OP RTD 10 Trip OP
0x8381 RTD 11 Trip PKP RTD 11 Trip PKP
0x8382 RTD 11 Trip OP RTD 11 Trip OP
0x83C1 RTD 12 Trip PKP RTD 12 Trip PKP
0x83C2 RTD 12 Trip OP RTD 12 Trip OP
0x84C1 LE 1 Trip PKP Logic Element 1 Trip PKP
0x84C2 LE 1 Trip OP Logic Element 1 Trip OP
0x84C4 LE 1 Trip DPO Logic Element 1 Trip DPO
0x8501 LE 2 Trip PKP Logic Element 2 Trip PKP
0x8502 LE 2 Trip OP Logic Element 2 Trip OP
0x8504 LE 2 Trip DPO Logic Element 2 Trip DPO
0x8541 LE 3 Trip PKP Logic Element 3 Trip PKP
0x8542 LE 3 Trip OP Logic Element 3 Trip OP
0x8544 LE 3 Trip DPO Logic Element 3 Trip DPO
0x8581 LE 4 Trip PKP Logic Element 4 Trip PKP
0x8582 LE 4 Trip OP Logic Element 4 Trip OP
0x8584 LE 4 Trip DPO Logic Element 4 Trip DPO
0x85C1 LE 5 Trip PKP Logic Element 5 Trip PKP
0x85C2 LE 5 Trip OP Logic Element 5 Trip OP
0x85C4 LE 5 Trip DPO Logic Element 5 Trip DPO
0x8601 LE 6 Trip PKP Logic Element 6 Trip PKP
0x8602 LE 6 Trip OP Logic Element 6 Trip OP
0x8604 LE 6 Trip DPO Logic Element 6 Trip DPO
0x8641 LE 7 Trip PKP Logic Element 7 Trip PKP
0x8642 LE 7 Trip OP Logic Element 7 Trip OP
0x8644 LE 7 Trip DPO Logic Element 7 Trip DPO
0x8681 LE 8 Trip PKP Logic Element 8 Trip PKP
0x8682 LE 8 Trip OP Logic Element 8 Trip OP
0x8684 LE 8 Trip DPO Logic Element 8 Trip DPO
0x9001 Ph IOC1 Trip PKP Phase IOC 1 Trip PKP
0x9002 Ph IOC1 Trip OP Phase IOC 1 Trip OP
0x9004 Ph IOC1 Trip DPO Phase IOC 1 Trip DPO
0x9009 Ph A IOC1 Trip PKP Phase A IOC 1 Trip PKP
0x900A Ph A IOC1 Trip OP Phase A IOC 1 Trip OP
0x900C Ph A IOC1 Trip DPO Phase A IOC 1 Trip DPO
0x9011 Ph B IOC1 Trip PKP Phase B IOC 1 Trip PKP
0x9012 Ph B IOC1 Trip OP Phase B IOC 1 Trip OP

11-126 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x9014 Ph B IOC1 Trip DPO Phase B IOC 1 Trip DPO
0x9021 Ph C IOC1 Trip PKP Phase C IOC 1 Trip PKP
0x9022 Ph C IOC1 Trip OP Phase C IOC 1 Trip OP
0x9024 Ph C IOC1 Trip DPO Phase C IOC 1 Trip DPO
0x9041 Ntrl IOC1 Trip PKP Neutral IOC 1 Trip PKP
0x9042 Ntrl IOC1 Trip OP Neutral IOC 1 Trip OP
0x9044 Ntrl IOC1 Trip DPO Neutral IOC 1 Trip DPO
0x9081 Gnd IOC1 Trip PKP Ground IOC 1 Trip PKP
0x9082 Gnd IOC1 Trip OP Ground IOC 1 Trip OP
0x9084 Gnd IOC1 Trip DPO Ground IOC 1 Trip DPO
0x90C1 Ph TOC1 Trip PKP Phase TOC 1 Trip PKP
0x90C2 Ph TOC1 Trip OP Phase TOC 1 Trip OP
0x90C4 Ph TOC1 Trip DPO Phase TOC 1 Trip DPO
0x90C9 Ph A TOC1 Trip PKP Phase A TOC 1 Trip PKP
0x90CA Ph A TOC1 Trip OP Phase A TOC 1 Trip OP
0x90CC Ph A TOC1 Trip DPO Phase A TOC 1 Trip DPO
0x90D1 Ph B TOC1 Trip PKP Phase B TOC 1 Trip PKP
0x90D2 Ph B TOC1 Trip OP Phase B TOC 1 Trip OP
0x90D4 Ph B TOC1 Trip DPO Phase B TOC 1 Trip DPO
0x90E1 Ph C TOC1 Trip PKP Phase C TOC 1 Trip PKP
0x90E2 Ph C TOC1 Trip OP Phase C TOC 1 Trip OP
0x90E4 Ph C TOC1 Trip DPO Phase C TOC 1 Trip DPO
0x9101 Ntrl TOC1 Trip PKP Neutral TOC 1 Trip PKP
0x9102 Ntrl TOC1 Trip OP Neutral TOC 1 Trip OP
0x9104 Ntrl TOC1 Trip DPO Neutral TOC 1 Trip DPO
0x9141 Gnd TOC1 Trip PKP Ground TOC Trip PKP
0x9142 Gnd TOC1 Trip OP Ground TOC 1 Trip OP
0x9144 Gnd TOC1 Trip DPO Ground TOC Trip DPO
0x9181 Ph IOC2 Trip PKP Phase IOC 2 Trip PKP
0x9182 Ph IOC2 Trip OP Phase IOC 2 Trip OP
0x9184 Ph IOC2 Trip DPO Phase IOC 2 Trip DPO
0x9189 Ph A IOC2 Trip PKP Phase A IOC 2 Trip PKP
0x918A Ph A IOC2 Trip OP Phase A IOC 2 Trip OP
0x918C Ph A IOC2 Trip DPO Phase A IOC 2 Trip DPO
0x9191 Ph B IOC2 Trip PKP Phase B IOC 2 Trip PKP
0x9192 Ph B IOC2 Trip OP Phase B IOC 2 Trip OP
0x9194 Ph B IOC2 Trip DPO Phase B IOC 2 Trip DPO
0x91A1 Ph C IOC2 Trip PKP Phase C IOC 2 Trip PKP
0x91A2 Ph C IOC2 Trip OP Phase C IOC 2 Trip OP
0x91A4 Ph C IOC2 Trip DPO Phase C IOC 2 Trip DPO
0x91C1 Ntrl IOC2 Trip PKP Neutral IOC 2 Trip PKP
0x91C2 Ntrl IOC2 Trip OP Neutral IOC 2 Trip OP
0x91C4 Ntrl IOC2 Trip DPO Neutral IOC 2 Trip DPO
0x9201 Gnd IOC2 Trip PKP Ground IOC 2 Trip PKP
0x9202 Gnd IOC2 Trip OP Ground IOC 2 Trip OP
0x9204 Gnd IOC2 Trip DPO Ground IOC 2 Trip DPO
0x9241 Ph TOC2 Trip PKP Phase TOC 2 Trip PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-127


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x9242 Ph TOC2 Trip OP Phase TOC 2 Trip OP
0x9244 Ph TOC2 Trip DPO Phase TOC 2 Trip DPO
0x9249 Ph A TOC2 Trip PKP Phase A TOC 2 Trip PKP
0x924A Ph A TOC2 Trip OP Phase A TOC 2 Trip OP
0x924C Ph A TOC2 Trip DPO Phase A TOC 2 Trip DPO
0x9251 Ph B TOC2 Trip PKP Phase B TOC 2 Trip PKP
0x9252 Ph B TOC2 Trip OP Phase B TOC 2 Trip OP
0x9254 Ph B TOC2 Trip DPO Phase B TOC 2 Trip DPO
0x9261 Ph C TOC2 Trip PKP Phase C TOC 2 Trip PKP
0x9262 Ph C TOC2 Trip OP Phase C TOC 2 Trip OP
0x9264 Ph C TOC2 Trip DPO Phase C TOC 2 Trip DPO
0x9281 Ntrl TOC2 Trip PKP Neutral TOC 2 Trip PKP
0x9282 Ntrl TOC2 Trip OP Neutral TOC 2 Trip OP
0x9284 Ntrl TOC2 Trip DPO Neutral TOC 2 Trip DPO
0x92C1 Gnd TOC2 Trip PKP Ground TOC 2 Trip PKP
0x92C2 Gnd TOC2 Trip OP Ground TOC 2 Trip OP
0x92C4 Gnd TOC2 Trip DPO Ground TOC 2 Trip DPO
0x9301 SGnd TOC1 Trip PKP Sensitive Ground TOC 1 Trip PKP
0x9302 SGnd TOC1 Trip OP Sensitive Ground TOC 1 Trip OP
0x9304 SGnd TOC1 Trip DPO Sensitive Ground TOC 1 Trip DPO
0x9641 SGnd IOC1 Trip PKP Sensitive Ground IOC 1 Trip PKP
0x9642 SGnd IOC1 Trip OP Sensitive Ground IOC 1 Trip OP
0x9644 SGnd IOC1 Trip DPO Sensitive Ground IOC 1 Trip DPO
0x9681 SGnd IOC2 Trip PKP Sensitive Ground IOC 2 Trip PKP
0x9682 SGnd IOC2 Trip OP Sensitive Ground IOC 2 Trip OP
0x9684 SGnd IOC2 Trip DPO Sensitive Ground IOC 2 Trip DPO
0x96C1 NSeq IOC Trp PKP Negative Sequence IOC Trip PKP
0x96C2 NSeq IOC Trp OP Negative Sequence IOC Trip OP
0x96C4 NSeq IOC Trp DPO Negative Sequence IOC Trip DPO
0x9701 Pcnt Diff Trip PKP Pcnt Diff Trip PKP
0x9702 Pcnt Diff Trip OP Pcnt Diff Trip OP
0x9704 Pcnt Diff Trip DPO Pcnt Diff Trip DPO
0x9709 Ph Diff A Trip PKP Ph Diff A Trip PKP
0x970A Ph Diff A Trip OP Ph Diff A Trip OP
0x970C Ph Diff A Trip DPO Ph Diff A Trip DPO
0x9711 Ph Diff B Trip PKP Ph Diff B Trip PKP
0x9712 Ph Diff B Trip OP Ph Diff B Trip OP
0x9714 Ph Diff B Trip DPO Ph Diff B Trip DPO
0x9721 Ph Diff C Trip PKP Ph Diff C Trip PKP
0x9722 Ph Diff C Trip OP Ph Diff C Trip OP
0x9724 Ph Diff C Trip DPO Ph Diff C Trip DPO
0x9741 RGF1 Trip PKP RGF1 Trip PKP
0x9742 RGF1 Trip OP RGF1 Trip OP
0x9744 RGF1 Trip DPO RGF1 Trip DPO
0x9781 RGF2 Trip PKP RGF2 Trip PKP
0x9782 RGF2 Trip OP RGF2 Trip OP
0x9784 RGF2 Trip DPO RGF2 Trip DPO

11-128 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x97C1 Inst Diff Trip PKP Inst Diff Trip PKP
0x97C2 Inst Diff Trip OP Inst Diff Trip OP
0x97C4 Inst Diff Trip DPO Inst Diff Trip DPO
0x9801 NSeq TOC1 Trip PKP Negative Sequence TOC 1 Trip PKP
0x9802 NSeq TOC1 Trip OP Negative Sequence TOC 1 Trip OP
0x9804 NSeq TOC1 Trip DPO Negative Sequence TOC 1 Trip DPO
0x9841 NSeq TOC2 Trip PKP Negative Sequence TOC 2 Trip PKP
0x9842 NSeq TOC2 Trip OP Negative Sequence TOC 2 Trip OP
0x9844 NSeq TOC2 Trip DPO Negative Sequence TOC 2 Trip DPO
0x9901 NSeq IOC 2 Trp PKP Negative Sequence IOC 2 Trip PKP
0x9902 NSeq IOC 2 Trp OP Negative Sequence IOC 2 Trip OP
0x9904 NSeq IOC 2 Trp DPO Negative Sequence IOC 2 Trip DPO
0x99C1 SGnd TOC2 Trip PKP Sensitive Ground TOC 2 Trip PKP
0x99C2 SGnd TOC2 Trip OP Sensitive Ground TOC 2 Trip OP
0x99C4 SGnd TOC2 Trip DPO Sensitive Ground TOC 2 Trip DPO
0x9C01 LE 9 Trip PKP Logic Element 9 Trip PKP
0x9C02 LE 9 Trip OP Logic Element 9 Trip OP
0x9C04 LE 9 Trip DPO Logic Element 9 Trip DPO
0x9C41 LE 10 Trip PKP Logic Element 10 Trip PKP
0x9C42 LE 10 Trip OP Logic Element 10 Trip OP
0x9C44 LE 10 Trip DPO Logic Element 10 Trip DPO
0x9C81 LE 11 Trip PKP Logic Element 11 Trip PKP
0x9C82 LE 11 Trip OP Logic Element 11 Trip OP
0x9C84 LE 11 Trip DPO Logic Element 11 Trip DPO
0x9CC1 LE 12 Trip PKP Logic Element 12 Trip PKP
0x9CC2 LE 12 Trip OP Logic Element 12 Trip OP
0x9CC4 LE 12 Trip DPO Logic Element 12 Trip DPO
0x9D01 LE 13 Trip PKP Logic Element 13 Trip PKP
0x9D02 LE 13 Trip OP Logic Element 13 Trip OP
0x9D04 LE 13 Trip DPO Logic Element 13 Trip DPO
0x9D41 LE 14 Trip PKP Logic Element 14 Trip PKP
0x9D42 LE 14 Trip OP Logic Element 14 Trip OP
0x9D44 LE 14 Trip DPO Logic Element 14 Trip DPO
0x9D81 LE 15 Trip PKP Logic Element 15 Trip PKP
0x9D82 LE 15 Trip OP Logic Element 15 Trip OP
0x9D84 LE 15 Trip DPO Logic Element 15 Trip DPO
0x9DC1 LE 16 Trip PKP Logic Element 16 Trip PKP
0x9DC2 LE 16 Trip OP Logic Element 16 Trip OP
0x9DC4 LE 16 Trip DPO Logic Element 16 Trip DPO
0xA002 Any Alarm Any Alarm
0xA042 Therm Lvl Alrm OP Thermal Level Alarm OP
0xA044 Therm Lvl Alrm DPO Thermal Level Alarm DPO
0xA04A Therm PhA Alrm OP Thermal Phase A Alarm OP
0xA04C Therm PhA Alrm DPO Thermal Phase A Alarm DPO
0xA052 Therm PhB Alrm OP Thermal Phase B Alarm OP
0xA054 Therm PhB Alrm DPO Thermal Phase B Alarm DPO
0xA062 Therm PhC Alrm OP Thermal Phase C Alarm OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-129


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xA064 Therm PhC Alrm DPO Thermal Phase C Alarm DPO
0xA081 RTD 1 Alarm PKP RTD 1 Alarm PKP
0xA082 RTD 1 Alarm OP RTD 1 Alarm OP
0xA0C1 RTD 2 Alarm PKP RTD 2 Alarm PKP
0xA0C2 RTD 2 Alarm OP RTD 2 Alarm OP
0xA101 RTD 3 Alarm PKP RTD 3 Alarm PKP
0xA102 RTD 3 Alarm OP RTD 3 Alarm OP
0xA141 RTD 4 Alarm PKP RTD 4 Alarm PKP
0xA142 RTD 4 Alarm OP RTD 4 Alarm OP
0xA201 RTD 5 Alarm PKP RTD 5 Alarm PKP
0xA202 RTD 5 Alarm OP RTD 5 Alarm OP
0xA241 RTD 6 Alarm PKP RTD 6 Alarm PKP
0xA242 RTD 6 Alarm OP RTD 6 Alarm OP
0xA281 RTD 7 Alarm PKP RTD 7 Alarm PKP
0xA282 RTD 7 Alarm OP RTD 7 Alarm OP
0xA2C1 RTD 8 Alarm PKP RTD 8 Alarm PKP
0xA2C2 RTD 8 Alarm OP RTD 8 Alarm OP
0xA301 RTD 9 Alarm PKP RTD 9 Alarm PKP
0xA302 RTD 9 Alarm OP RTD 9 Alarm OP
0xA341 RTD 10 Alarm PKP RTD 10 Alarm PKP
0xA342 RTD 10 Alarm OP RTD 10 Alarm OP
0xA381 RTD 11 Alarm PKP RTD 11 Alarm PKP
0xA382 RTD 11 Alarm OP RTD 11 Alarm OP
0xA3C1 RTD 12 Alarm PKP RTD 12 Alarm PKP
0xA3C2 RTD 12 Alarm OP RTD 12 Alarm OP
0xA402 RTD Trouble Alr OP RTD Trouble Alarm
0xA4C1 LE 1 Alarm PKP Logic Element 1 Alarm PKP
0xA4C2 LE 1 Alarm OP Logic Element 1 Alarm OP
0xA4C4 LE 1 Alarm DPO Logic Element 1 Alarm DPO
0xA501 LE 2 Alarm PKP Logic Element 2 Alarm PKP
0xA502 LE 2 Alarm OP Logic Element 2 Alarm OP
0xA504 LE 2 Alarm DPO Logic Element 2 Alarm DPO
0xA541 LE 3 Alarm PKP Logic Element 3 Alarm PKP
0xA542 LE 3 Alarm OP Logic Element 3 Alarm OP
0xA544 LE 3 Alarm DPO Logic Element 3 Alarm DPO
0xA581 LE 4 Alarm PKP Logic Element 4 Alarm PKP
0xA582 LE 4 Alarm OP Logic Element 4 Alarm OP
0xA584 LE 4 Alarm DPO Logic Element 4 Alarm DPO
0xA5C1 LE 5 Alarm PKP Logic Element 5 Alarm PKP
0xA5C2 LE 5 Alarm OP Logic Element 5 Alarm OP
0xA5C4 LE 5 Alarm DPO Logic Element 5 Alarm DPO
0xA601 LE 6 Alarm PKP Logic Element 6 Alarm PKP
0xA602 LE 6 Alarm OP Logic Element 6 Alarm OP
0xA604 LE 6 Alarm DPO Logic Element 6 Alarm DPO
0xA641 LE 7 Alarm PKP Logic Element 7 Alarm PKP
0xA642 LE 7 Alarm OP Logic Element 7 Alarm OP
0xA644 LE 7 Alarm DPO Logic Element 7 Alarm DPO

11-130 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0xA681 LE 8 Alarm PKP Logic Element 8 Alarm PKP
0xA682 LE 8 Alarm OP Logic Element 8 Alarm OP
0xA684 LE 8 Alarm DPO Logic Element 8 Alarm DPO
0xA6C2 Curr Dmd1 Alrm OP Current Demand 1 Alarm OP
0xA6CA C Dmd1 PhA Alrm OP Current Demand 1 PhA Alarm OP
0xA6D2 C Dmd1 PhB Alrm OP Current Demand 1 PhB Alarm OP
0xA6E2 C Dmd1 PhC Alrm OP Current Demand 1 PhC Alarm OP
0xA702 Curr Dmd2 Alrm OP Current Demand 2 Alarm OP
0xA70A C Dmd2 PhA Alrm OP Current Demand 2 PhA Alarm OP
0xA712 C Dmd2 PhB Alrm OP Current Demand 2 PhB Alarm OP
0xA722 C Dmd2 PhC Alrm OP Current Demand 2 PhC Alarm OP
0xA842 W1BKR Alarm W1 Breaker Alarm
0xA882 W1BKR Trip Time W1 Breaker Trip Time
0xA8C2 W1BKR Close Time W1 Breaker Close Time
0xA902 W1BKR Charge Time W1 Breaker Charge Time
0xA942 W2BKR Alarm W2 Breaker Alarm
0xA982 W2BKR Trip Time W2 Breaker Trip Time
0xA9C2 W2BKR Close Time W2 Breaker Close Time
0xAA02 W2BKR Charge Time W2 Breaker Charge Time
0xABC1 HI Amb Temp PKP High Ambient Temperature Alarm PKP
0xABC2 HI Amb Temp OP High Ambient Temperature Alarm
0xABC4 HI Amb Temp DPO High Ambient Temperature Alarm DPO
0xAC01 LO Amb Temp PKP Low Ambient Temperature Alarm PKP
0xAC02 LO Amb Temp OP Low Ambient Temperature Alarm
0xAC04 LO Amb Temp DPO Low Ambient Temperature Alarm DPO
0xAC42 Self Test Alarm OP Self Test Alarm OP
0xACC2 BKRTrpCntrAlrm OP Breaker Trip Control Alarm OP
0xAD01 R1 CoilMonAlrm PKP Trip Coil Monitor Alarm PKP
0xAD02 R1 CoilMonAlrm OP Trip Coil Monitor Alarm OP
0xAD04 R1 CoilMonAlrm DPO Trip Coil Monitor Alarm DPO
0xAD41 R2 CoilMonAlrm PKP Close Coil Monitor Alarm PKP
0xAD42 R2 CoilMonAlrm OP Close Coil Monitor Alarm OP
0xAD44 R2 CoilMonAlrm DPO Close Coil Monitor Alarm DPO
0xAD81 BKR1 Fail Alrm PKP Breaker 1 Fail Alarm PKP
0xAD82 BKR1 Fail Alrm OP Breaker 1 Fail Alarm OP
0xAD84 BKR1 Fail Alrm DPO Breaker 1 Fail Alarm DPO
0xADC2 BKR Stat Fail OP Breaker Status Fail OP
0xAEC2 BKR2 Stat Fail OP Breaker 2 Status Fail OP
0xAF41 BKR2 Fail Alrm PKP Breaker 2 Fail Alarm PKP
0xAF42 BKR2 Fail Alrm OP Breaker 2 Fail Alarm OP
0xAF44 BKR2 Fail Alrm DPO Breaker 2 Fail Alarm DPO
0xB001 Ph IOC1 Alarm PKP Phase IOC 1 Alarm PKP
0xB002 Ph IOC1 Alarm OP Phase IOC 1 Alarm OP
0xB004 Ph IOC1 Alarm DPO Phase IOC 1 Alarm DPO
0xB009 Ph A IOC1 Alrm PKP Phase A IOC 1 Alarm PKP
0xB00A Ph A IOC1 Alrm OP Phase A IOC 1 Alarm OP
0xB00C Ph A IOC1 Alrm DPO Phase A IOC 1 Alarm DPO

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-131


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xB011 Ph B IOC1 Alrm PKP Phase B IOC 1 Alarm PKP
0xB012 Ph B IOC1 Alrm OP Phase B IOC 1 Alarm OP
0xB014 Ph B IOC1 Alrm DPO Phase B IOC 1 Alarm DPO
0xB021 Ph C IOC1 Alrm PKP Phase C IOC 1 Alarm PKP
0xB022 Ph C IOC1 Alrm OP Phase C IOC 1 Alarm OP
0xB024 Ph C IOC1 Alrm DPO Phase C IOC 1 Alarm DPO
0xB041 Ntrl IOC1 Alrm PKP Neutral IOC 1 Alarm PKP
0xB042 Ntrl IOC1 Alrm OP Neutral IOC 1 Alarm OP
0xB044 Ntrl IOC1 Alrm DPO Neutral IOC 1 Alarm DPO
0xB081 Gnd IOC1 Alarm PKP Ground IOC 1 Alarm PKP
0xB082 Gnd IOC1 Alarm OP Ground IOC 1 Alarm OP
0xB084 Gnd IOC1 Alarm DPO Ground IOC 1 Alarm DPO
0xB0C1 Ph TOC1 Alarm PKP Phase TOC 1 Alarm PKP
0xB0C2 Ph TOC1 Alarm OP Phase TOC 1 Alarm OP
0xB0C4 Ph TOC1 Alarm DPO Phase TOC 1 Alarm DPO
0xB0C9 Ph A TOC1 Alrm PKP Phase A TOC 1 Alarm PKP
0xB0CA Ph A TOC1 Alrm OP Phase A TOC 1 Alarm OP
0xB0CC Ph A TOC1 Alrm DPO Phase A TOC 1 Alarm DPO
0xB0D1 Ph B TOC1 Alrm PKP Phase B TOC 1 Alarm PKP
0xB0D2 Ph B TOC1 Alrm OP Phase B TOC 1 Alarm OP
0xB0D4 Ph B TOC1 Alrm DPO Phase B TOC 1 Alarm DPO
0xB0E1 Ph C TOC1 Alrm PKP Phase C TOC 1 Alarm PKP
0xB0E2 Ph C TOC1 Alrm OP Phase C TOC 1 Alarm OP
0xB0E4 Ph C TOC1 Alrm DPO Phase C TOC 1 Alarm DPO
0xB101 Ntrl TOC1 Alrm PKP Neutral TOC 1 Alarm PKP
0xB102 Ntrl TOC1 Alrm OP Neutral TOC 1 Alarm OP
0xB104 Ntrl TOC1 Alrm DPO Neutral TOC 1 Alarm DPO
0xB141 Gnd TOC1 Alarm PKP Ground TOC Alarm PKP
0xB142 Gnd TOC1 Alarm OP Ground TOC 1 Alarm OP
0xB144 Gnd TOC1 Alarm DPO Ground TOC Alarm DPO
0xB181 Ph IOC2 Alarm PKP Phase IOC 2 Alarm PKP
0xB182 Ph IOC2 Alarm OP Phase IOC 2 Alarm OP
0xB184 Ph IOC2 Alarm DPO Phase IOC 2 Alarm DPO
0xB189 Ph A IOC2 Alrm PKP Phase A IOC 2 Alarm PKP
0xB18A Ph A IOC2 Alrm OP Phase A IOC 2 Alarm OP
0xB18C Ph A IOC2 Alrm DPO Phase A IOC 2 Alarm DPO
0xB191 Ph B IOC2 Alrm PKP Phase B IOC 2 Alarm PKP
0xB192 Ph B IOC2 Alrm OP Phase B IOC 2 Alarm OP
0xB194 Ph B IOC2 Alrm DPO Phase B IOC 2 Alarm DPO
0xB1A1 Ph C IOC2 Alrm PKP Phase C IOC 2 Alarm PKP
0xB1A2 Ph C IOC2 Alrm OP Phase C IOC 2 Alarm OP
0xB1A4 Ph C IOC2 Alrm DPO Phase C IOC 2 Alarm DPO
0xB1C1 Ntrl IOC2 Alrm PKP Neutral IOC 2 Alarm PKP
0xB1C2 Ntrl IOC2 Alrm OP Neutral IOC 2 Alarm OP
0xB1C4 Ntrl IOC2 Alrm DPO Neutral IOC 2 Alarm DPO
0xB201 Gnd IOC2 Alarm PKP Ground IOC 2 Alarm PKP
0xB202 Gnd IOC2 Alarm OP Ground IOC 2 Alarm OP

11-132 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0xB204 Gnd IOC2 Alarm DPO Ground IOC 2 Alarm DPO
0xB241 Ph TOC2 Alrm PKP Phase TOC 2 Alarm PKP
0xB242 Ph TOC2 Alrm OP Phase TOC 2 Alarm OP
0xB244 Ph TOC2 Alrm DPO Phase TOC 2 Alarm DPO
0xB249 Ph A TOC2 Alrm PKP Phase A TOC 2 Alarm PKP
0xB24A Ph A TOC2 Alrm OP Phase A TOC 2 Alarm OP
0xB24C Ph A TOC2 Alrm DPO Phase A TOC 2 Alarm DPO
0xB251 Ph B TOC2 Alrm PKP Phase B TOC 2 Alarm PKP
0xB252 Ph B TOC2 Alrm OP Phase B TOC 2 Alarm OP
0xB254 Ph B TOC2 Alrm DPO Phase B TOC 2 Alarm DPO
0xB261 Ph C TOC2 Alrm PKP Phase C TOC 2 Alarm PKP
0xB262 Ph C TOC2 Alrm OP Phase C TOC 2 Alarm OP
0xB264 Ph C TOC2 Alrm DPO Phase C TOC 2 Alarm DPO
0xB281 Ntrl TOC2 Alrm PKP Neutral TOC 2 Alarm PKP
0xB282 Ntrl TOC2 Alrm OP Neutral TOC 2 Alarm OP
0xB284 Ntrl TOC2 Alrm DPO Neutral TOC 2 Alarm DPO
0xB2C1 Gnd TOC2 Alarm PKP Ground TOC 2 Alarm PKP
0xB2C2 Gnd TOC2 Alarm OP Ground TOC 2 Alarm OP
0xB2C4 Gnd TOC2 Alarm DPO Ground TOC 2 Alarm DPO
0xB301 SGnd TOC1 Alrm PKP Sensitive Ground TOC 1 Alarm PKP
0xB302 SGnd TOC1 Alrm OP Sensitive Ground TOC 1 Alarm OP
0xB304 SGnd TOC1 Alrm DPO Sensitive Ground TOC 1 Alarm DPO
0xB641 SGnd IOC1 Alrm PKP Sensitive Ground IOC 1 Alarm PKP
0xB642 SGnd IOC1 Alrm OP Sensitive Ground IOC 1 Alarm OP
0xB644 SGnd IOC1 Alrm DPO Sensitive Ground IOC 1 Alarm DPO
0xB681 SGnd IOC2 Alrm PKP Sensitive Ground IOC 2 Alarm PKP
0xB682 SGnd IOC2 Alrm OP Sensitive Ground IOC 2 Alarm OP
0xB684 SGnd IOC2 Alrm DPO Sensitive Ground IOC 2 Alarm DPO
0xB6C1 NSeq IOC Alrm PKP Negative Sequence IOC Alarm PKP
0xB6C2 NSeq IOC Alrm OP NSeq IOC Alrm OP
0xB6C4 NSeq IOC Alrm DPO Negative Sequence IOC Alarm DPO
0xB701 Pcnt Diff Alrm PKP Pcnt Diff Alrm PKP
0xB702 Pcnt Diff Alrm OP Pcnt Diff Alrm OP
0xB704 Pcnt Diff Alrm DPO Pcnt Diff Alrm DPO
0xB709 Ph Dif A Alarm PKP Ph Dif A Alarm PKP
0xB70A Ph Dif A Alarm OP Ph Dif A Alarm OP
0xB70C Ph Dif A Alarm DPO Ph Dif A Alarm DPO
0xB711 Ph Dif B Alarm PKP Ph Dif B Alarm PKP
0xB712 Ph Dif B Alarm OP Ph Dif B Alarm OP
0xB714 Ph Dif B Alarm DPO Ph Dif B Alarm DPO
0xB721 Ph Dif C Alarm PKP Ph Dif C Alarm PKP
0xB722 Ph Dif C Alarm OP Ph Dif C Alarm OP
0xB724 Ph Dif C Alarm DPO Ph Dif C Alarm DPO
0xB741 RGF1 Alarm PKP RGF1 Alarm PKP
0xB742 RGF1 Alarm OP RGF1 Alarm OP
0xB744 RGF1 Alarm DPO RGF1 Alarm DPO
0xB781 RGF2 Alarm PKP RGF2 Alarm PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-133


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xB782 RGF2 Alarm OP RGF2 Alarm OP
0xB784 RGF2 Alarm DPO RGF2 Alarm DPO
0xB7C1 Inst Diff Alrm PKP Inst Diff Alrm PKP
0xB7C2 Inst Diff Alrm OP Inst Diff Alrm OP
0xB7C4 Inst Diff Alrm DPO Inst Diff Alrm DPO
0xB801 NSeq TOC1 Alrm PKP Negative Sequence TOC 1 Alarm PKP
0xB802 NSeq TOC1 Alrm OP Negative Sequence TOC 1 Alarm OP
0xB804 NSeq TOC1 Alrm DPO Negative Sequence TOC 1 Alarm DPO
0xB841 NSeq TOC2 Alrm PKP Negative Sequence TOC 2 Alarm PKP
0xB842 NSeq TOC2 Alrm OP Negative Sequence TOC 2 Alarm OP
0xB844 NSeq TOC2 Alrm DPO Negative Sequence TOC 2 Alarm DPO
0xB901 NSeq IOC 2 AlrmPKP Negative Sequence IOC 2 Alarm PKP
0xB902 NSeq IOC 2 Alrm OP Negative Sequence IOC 2 Alarm OP
0xB904 NSeq IOC 2 AlrmDPO Negative Sequence IOC 2 Alarm DPO
0xB9C1 SGnd TOC2 Alrm PKP Sensitive Ground TOC 2 Alarm PKP
0xB9C2 SGnd TOC2 Alrm OP Sensitive Ground TOC 2 Alarm OP
0xB9C4 SGnd TOC2 Alrm DPO Sensitive Ground TOC 2 Alarm DPO
0xBA02 W1BKR Trp/Cls Fail W1 Breaker Trip/Close Fail
0xBA42 W1BKR Charge Fail W1 Breaker Charge Fail
0xBA82 W2BKR Trp/Cls Fail W2 Breaker Trip/Close Fail
0xBAC2 W2BKR Charge Fail W2 Breaker Charge Fail
0xBB02 W2BKRTrpCntrAlrm OP W2BKRTrpCntrAlrm OP
0xBC01 LE 9 Alarm PKP Logic Element 9 Alarm PKP
0xBC02 LE 9 Alarm OP Logic Element 9 Alarm OP
0xBC04 LE 9 Alarm DPO Logic Element 9 Alarm DPO
0xBC41 LE 10 Alarm PKP Logic Element 10 Alarm PKP
0xBC42 LE 10 Alarm OP Logic Element 10 Alarm OP
0xBC44 LE 10 Alarm DPO Logic Element 10 Alarm DPO
0xBC81 LE 11 Alarm PKP Logic Element 11 Alarm PKP
0xBC82 LE 11 Alarm OP Logic Element 11 Alarm OP
0xBC84 LE 11 Alarm DPO Logic Element 11 Alarm DPO
0xBCC1 LE 12 Alarm PKP Logic Element 12 Alarm PKP
0xBCC2 LE 12 Alarm OP Logic Element 12 Alarm OP
0xBCC4 LE 12 Alarm DPO Logic Element 12 Alarm DPO
0xBD01 LE 13 Alarm PKP Logic Element 13 Alarm PKP
0xBD02 LE 13 Alarm OP Logic Element 13 Alarm OP
0xBD04 LE 13 Alarm DPO Logic Element 13 Alarm DPO
0xBD41 LE 14 Alarm PKP Logic Element 14 Alarm PKP
0xBD42 LE 14 Alarm OP Logic Element 14 Alarm OP
0xBD44 LE 14 Alarm DPO Logic Element 14 Alarm DPO
0xBD81 LE 15 Alarm PKP Logic Element 15 Alarm PKP
0xBD82 LE 15 Alarm OP Logic Element 15 Alarm OP
0xBD84 LE 15 Alarm DPO Logic Element 15 Alarm DPO
0xBDC1 LE 16 Alarm PKP Logic Element 16 Alarm PKP
0xBDC2 LE 16 Alarm OP Logic Element 16 Alarm OP
0xBDC4 LE 16 Alarm DPO Logic Element 16 Alarm DPO
0xC042 Output Relay 3 On Output Relay 3 On

11-134 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0xC082 Output Relay 4 On Output Relay 4 On
0xC0C2 Output Relay 5 On Output Relay 5 On
0xC102 Output Relay 6 On Output Relay 6 On
0xC142 Self-Test Rly 7 OP Self-Test Rly 7 OP
0xC202 BKR Connected Breaker Connected OP
0xC2C2 BKR2 Connected Breaker 2 Connected OP
0xC401 Hot RTD PKP Hot RTD PKP
0xC402 Hot RTD OP Hot RTD OP
0xC482 Any Pkp OP Any Pkp OP
0xC4C1 LE 1 PKP Logic Element 1 PKP
0xC4C2 LE 1 OP Logic Element 1 OP
0xC4C4 LE 1 DPO Logic Element 1 DPO
0xC501 LE 2 PKP Logic Element 2 PKP
0xC502 LE 2 OP Logic Element 2 OP
0xC504 LE 2 DPO Logic Element 2 DPO
0xC541 LE 3 PKP Logic Element 3 PKP
0xC542 LE 3 OP Logic Element 3 OP
0xC544 LE 3 DPO Logic Element 3 DPO
0xC581 LE 4 PKP Logic Element 4 PKP
0xC582 LE 4 OP Logic Element 4 OP
0xC584 LE 4 DPO Logic Element 4 DPO
0xC5C1 LE 5 PKP Logic Element 5 PKP
0xC5C2 LE 5 OP Logic Element 5 OP
0xC5C4 LE 5 DPO Logic Element 5 DPO
0xC601 LE 6 PKP Logic Element 6 PKP
0xC602 LE 6 OP Logic Element 6 OP
0xC604 LE 6 DPO Logic Element 6 DPO
0xC641 LE 7 PKP Logic Element 7 PKP
0xC642 LE 7 OP Logic Element 7 OP
0xC644 LE 7 DPO Logic Element 7 DPO
0xC681 LE 8 PKP Logic Element 8 PKP
0xC682 LE 8 OP Logic Element 8 OP
0xC684 LE 8 DPO Logic Element 8 DPO
0xC882 Setpoint Group2 On Setpoint Group2 On
0xC982 Maint. Req. OP Maintenance Required OP
0xCA02 52a Contact OP 52a Contact OP
0xCA42 52b Contact OP 52b Contact OP
0xCAC2 L/O Rst Closed OP Lockout Reset Closed OP
0xCC02 Lockout OP Lockout OP
0xCC04 Lockout DPO Lockout DPO
0xCC42 Testing ON Testing ON
0xCC44 Testing OFF Testing OFF
0xCCC2 BKR Stat Open Breaker Status Open OP
0xCD02 BKR Stat Clsd Breaker Status Closed OP
0xCD42 Setpoint Group1 On Setpoint Group1 On
0xDA02 BKR2 52a Cont OP BKR2 52a Cont OP
0xDA42 BKR2 52b Cont OP BKR2 52b Cont OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-135


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xDA82 BKR2 Stat Open BKR2 Stat Open
0xDAC2 BKR2 Stat Clsd BKR2 Stat Clsd
0xDB02 Trip BKR 1 OP Trip BKR 1 OP
0xDB42 Trip BKR 2 OP Trip BKR 2 OP
0xDB82 2nd Hmnc Diff OP 2nd Hmnc Diff OP
0xDB8A 2nd Hmnc Diff Ph A 2nd Harmonic Diff Ph A
0xDB92 2nd Hmnc Diff Ph B 2nd Harmonic Diff Ph B
0xDBA2 2nd Hmnc Diff Ph C 2nd Harmonic Diff Ph C
0xDBC2 5th Hmnc Diff OP 5th Hmnc Diff OP
0xDBCA 5th Hmnc Diff Ph A 5th Harmonic Diff Ph A
0xDBD2 5th Hmnc Diff Ph B 5th Harmonic Diff Ph B
0xDBE2 5th Hmnc Diff Ph C 5th Harmonic Diff Ph C
0xDC01 LE 9 PKP Logic Element 9 PKP
0xDC02 LE 9 OP Logic Element 9 OP
0xDC04 LE 9 DPO Logic Element 9 DPO
0xDC41 LE 10 PKP Logic Element 10 PKP
0xDC42 LE 10 OP Logic Element 10 OP
0xDC44 LE 10 DPO Logic Element 10 DPO
0xDC81 LE 11 PKP Logic Element 11 PKP
0xDC82 LE 11 OP Logic Element 11 OP
0xDC84 LE 11 DPO Logic Element 11 DPO
0xDCC1 LE 12 PKP Logic Element 12 PKP
0xDCC2 LE 12 OP Logic Element 12 OP
0xDCC4 LE 12 DPO Logic Element 12 DPO
0xDD01 LE 13 PKP Logic Element 13 PKP
0xDD02 LE 13 OP Logic Element 13 OP
0xDD04 LE 13 DPO Logic Element 13 DPO
0xDD41 LE 14 PKP Logic Element 14 PKP
0xDD42 LE 14 OP Logic Element 14 OP
0xDD44 LE 14 DPO Logic Element 14 DPO
0xDD81 LE 15 PKP Logic Element 15 PKP
0xDD82 LE 15 OP Logic Element 15 OP
0xDD84 LE 15 DPO Logic Element 15 DPO
0xDDC1 LE 16 PKP Logic Element 16 PKP
0xDDC2 LE 16 OP Logic Element 16 OP
0xDDC4 LE 16 DPO Logic Element 16 DPO
0xE002 Any Block Any Block
0xE042 Therm O/L Block Thermal Level Block
0xE082 RTD1 Block RTD1 Block
0xE0C2 RTD2 Block RTD2 Block
0xE102 RTD3 Block RTD3 Block
0xE142 RTD4 Block RTD4 Block
0xE182 Output Relay 1 Blk Output Relay 1 Block
0xE1C2 Output Relay 2 Blk Output Relay 2 Block
0xE202 RTD5 Block RTD5 Block
0xE242 RTD6 Block RTD6 Block
0xE282 RTD7 Block RTD7 Block

11-136 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0xE2C2 RTD8 Block RTD8 Block
0xE302 RTD9 Block RTD9 Block
0xE342 RTD10 Block RTD10 Block
0xE382 RTD11 Block RTD11 Block
0xE3C2 RTD12 Block RTD12 Block
0xE402 RTDTrouble Block RTDTrouble Block
0xE6C2 Curr Dmd1 Block Current Demand 1 Block OP
0xE702 Curr Dmd2 Block Current Demand 2 Block OP
0xE882 Group Change Blk Group Change Blk
0xEC02 Lockout Block Lockout Block
0xF002 Ph IOC1 Block Phase IOC 1 Block
0xF042 Ntrl IOC1 Block Neutral IOC 1 Block
0xF082 Gnd IOC1 Block Ground IOC 1 Block
0xF0C2 Ph TOC1 Block Phase TOC 1 Block
0xF102 Ntrl TOC1 Block Neutral TOC 1 Block
0xF142 Gnd TOC1 Block Ground TOC 1 Block
0xF182 Ph IOC2 Block Phase IOC 2 Block
0xF1C2 Ntrl IOC2 Block Neutral IOC 2 Block
0xF202 Gnd IOC2 Block Ground IOC 2 Block
0xF242 Ph TOC2 Block Phase TOC 2 Block
0xF282 Ntrl TOC2 Block Neutral TOC 2 Block
0xF2C2 Gnd TOC2 Block Ground TOC 2 Block
0xF302 SGnd TOC1 Block Sensitive Ground TOC 1 Block
0xF642 SGnd IOC1 Block Sensitive Ground IOC 1 Block
0xF682 SGnd IOC2 Block Sensitive Ground IOC 2 Block
0xF6C2 NSeq IOC Block Negative Sequence IOC Block
0xF702 Pcnt Diff Block Pcnt Diff Block
0xF742 RGF1 Block RGF1 Block
0xF782 RGF2 Block RGF2 Block
0xF7C2 Inst Diff Block Inst Diff Block
0xF802 NSeq TOC1 Blk Negative Sequence TOC 1 Block
0xF842 NSeq TOC2 Blk Negative Sequence TOC 2 Block
0xF902 NSeq IOC 2 Block Negative Sequence IOC 2 Block
0xF9C2 SGnd TOC2 Block Sensitive Ground TOC 2 Block
0xFB02 Trip BKR1 Blk Trip BKR1 Blk
0xFB42 Trip BKR2 Blk Trip BKR2 Blk
FC134C unsigned 16 bits Logic Element Trigger
0x0000 Off Off
0x0001 On On
0x0040 Contact IN 1 On Contact Input 1 On
0x0041 Contact IN 2 On Contact Input 2 On
0x0042 Contact IN 3 On Contact Input 3 On
0x0043 Contact IN 4 On Contact Input 4 On
0x0044 Contact IN 5 On Contact Input 5 On
0x0045 Contact IN 6 On Contact Input 6 On
0x0046 Contact IN 7 On Contact Input 7 On
0x0047 Contact IN 8 On Contact Input 8 On

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-137


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x0048 Contact IN 9 On Contact Input 9 On
0x0049 Contact IN 10 On Contact Input 10 On
0x0060 Contact IN 1 Off Contact Input 1 Off
0x0061 Contact IN 2 Off Contact Input 2 Off
0x0062 Contact IN 3 Off Contact Input 3 Off
0x0063 Contact IN 4 Off Contact Input 4 Off
0x0064 Contact IN 5 Off Contact Input 5 Off
0x0065 Contact IN 6 Off Contact Input 6 Off
0x0066 Contact IN 7 Off Contact Input 7 Off
0x0067 Contact IN 8 Off Contact Input 8 Off
0x0068 Contact IN 9 Off Contact Input 9 Off
0x0069 Contact IN 10 Off Contact Input 10 Off
0x0080 Virtual IN 1 On Virtual Input 1 On
0x0081 Virtual IN 2 On Virtual Input 2 On
0x0082 Virtual IN 3 On Virtual Input 3 On
0x0083 Virtual IN 4 On Virtual Input 4 On
0x0084 Virtual IN 5 On Virtual Input 5 On
0x0085 Virtual IN 6 On Virtual Input 6 On
0x0086 Virtual IN 7 On Virtual Input 7 On
0x0087 Virtual IN 8 On Virtual Input 8 On
0x0088 Virtual IN 9 On Virtual Input 9 On
0x0089 Virtual IN 10 On Virtual Input 10 On
0x008A Virtual IN 11 On Virtual Input 11 On
0x008B Virtual IN 12 On Virtual Input 12 On
0x008C Virtual IN 13 On Virtual Input 13 On
0x008D Virtual IN 14 On Virtual Input 14 On
0x008E Virtual IN 15 On Virtual Input 15 On
0x008F Virtual IN 16 On Virtual Input 16 On
0x0090 Virtual IN 17 On Virtual Input 17 On
0x0091 Virtual IN 18 On Virtual Input 18 On
0x0092 Virtual IN 19 On Virtual Input 19 On
0x0093 Virtual IN 20 On Virtual Input 20 On
0x0094 Virtual IN 21 On Virtual Input 21 On
0x0095 Virtual IN 22 On Virtual Input 22 On
0x0096 Virtual IN 23 On Virtual Input 23 On
0x0097 Virtual IN 24 On Virtual Input 24 On
0x0098 Virtual IN 25 On Virtual Input 25 On
0x0099 Virtual IN 26 On Virtual Input 26 On
0x009A Virtual IN 27 On Virtual Input 27 On
0x009B Virtual IN 28 On Virtual Input 28 On
0x009C Virtual IN 29 On Virtual Input 29 On
0x009D Virtual IN 30 On Virtual Input 30 On
0x009E Virtual IN 31 On Virtual Input 31 On
0x009F Virtual IN 32 On Virtual Input 32 On
0x00A0 Virtual IN 1 Off Virtual Input 1 Off
0x00A1 Virtual IN 2 Off Virtual Input 2 Off
0x00A2 Virtual IN 3 Off Virtual Input 3 Off

11-138 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x00A3 Virtual IN 4 Off Virtual Input 4 Off
0x00A4 Virtual IN 5 Off Virtual Input 5 Off
0x00A5 Virtual IN 6 Off Virtual Input 6 Off
0x00A6 Virtual IN 7 Off Virtual Input 7 Off
0x00A7 Virtual IN 8 Off Virtual Input 8 Off
0x00A8 Virtual IN 9 Off Virtual Input 9 Off
0x00A9 Virtual IN 10 Off Virtual Input 10 Off
0x00AA Virtual IN 11 Off Virtual Input 11 Off
0x00AB Virtual IN 12 Off Virtual Input 12 Off
0x00AC Virtual IN 13 Off Virtual Input 13 Off
0x00AD Virtual IN 14 Off Virtual Input 14 Off
0x00AE Virtual IN 15 Off Virtual Input 15 Off
0x00AF Virtual IN 16 Off Virtual Input 16 Off
0x00B0 Virtual IN 17 Off Virtual Input 17 Off
0x00B1 Virtual IN 18 Off Virtual Input 18 Off
0x00B2 Virtual IN 19 Off Virtual Input 19 Off
0x00B3 Virtual IN 20 Off Virtual Input 20 Off
0x00B4 Virtual IN 21 Off Virtual Input 21 Off
0x00B5 Virtual IN 22 Off Virtual Input 22 Off
0x00B6 Virtual IN 23 Off Virtual Input 23 Off
0x00B7 Virtual IN 24 Off Virtual Input 24 Off
0x00B8 Virtual IN 25 Off Virtual Input 25 Off
0x00B9 Virtual IN 26 Off Virtual Input 26 Off
0x00BA Virtual IN 27 Off Virtual Input 27 Off
0x00BB Virtual IN 28 Off Virtual Input 28 Off
0x00BC Virtual IN 29 Off Virtual Input 29 Off
0x00BD Virtual IN 30 Off Virtual Input 30 Off
0x00BE Virtual IN 31 Off Virtual Input 31 Off
0x00BF Virtual IN 32 Off Virtual Input 32 Off
0x01C0 Remote IN 1 On Remote Input 1 On
0x01C1 Remote IN 2 On Remote Input 2 On
0x01C2 Remote IN 3 On Remote Input 3 On
0x01C3 Remote IN 4 On Remote Input 4 On
0x01C4 Remote IN 5 On Remote Input 5 On
0x01C5 Remote IN 6 On Remote Input 6 On
0x01C6 Remote IN 7 On Remote Input 7 On
0x01C7 Remote IN 8 On Remote Input 8 On
0x01C8 Remote IN 9 On Remote Input 9 On
0x01C9 Remote IN 10 On Remote Input 10 On
0x01CA Remote IN 11 On Remote Input 11 On
0x01CB Remote IN 12 On Remote Input 12 On
0x01CC Remote IN 13 On Remote Input 13 On
0x01CD Remote IN 14 On Remote Input 14 On
0x01CE Remote IN 15 On Remote Input 15 On
0x01CF Remote IN 16 On Remote Input 16 On
0x01D0 Remote IN 17 On Remote Input 17 On
0x01D1 Remote IN 18 On Remote Input 18 On

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-139


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x01D2 Remote IN 19 On Remote Input 19 On
0x01D3 Remote IN 20 On Remote Input 20 On
0x01D4 Remote IN 21 On Remote Input 21 On
0x01D5 Remote IN 22 On Remote Input 22 On
0x01D6 Remote IN 23 On Remote Input 23 On
0x01D7 Remote IN 24 On Remote Input 24 On
0x01D8 Remote IN 25 On Remote Input 25 On
0x01D9 Remote IN 26 On Remote Input 26 On
0x01DA Remote IN 27 On Remote Input 27 On
0x01DB Remote IN 28 On Remote Input 28 On
0x01DC Remote IN 29 On Remote Input 29 On
0x01DD Remote IN 30 On Remote Input 30 On
0x01DE Remote IN 31 On Remote Input 31 On
0x01DF Remote IN 32 On Remote Input 32 On
0x01E0 Remote IN 1 Off Remote Input 1 Off
0x01E1 Remote IN 2 Off Remote Input 2 Off
0x01E2 Remote IN 3 Off Remote Input 3 Off
0x01E3 Remote IN 4 Off Remote Input 4 Off
0x01E4 Remote IN 5 Off Remote Input 5 Off
0x01E5 Remote IN 6 Off Remote Input 6 Off
0x01E6 Remote IN 7 Off Remote Input 7 Off
0x01E7 Remote IN 8 Off Remote Input 8 Off
0x01E8 Remote IN 9 Off Remote Input 9 Off
0x01E9 Remote IN 10 Off Remote Input 10 Off
0x01EA Remote IN 11 Off Remote Input 11 Off
0x01EB Remote IN 12 Off Remote Input 12 Off
0x01EC Remote IN 13 Off Remote Input 13 Off
0x01ED Remote IN 14 Off Remote Input 14 Off
0x01EE Remote IN 15 Off Remote Input 15 Off
0x01EF Remote IN 16 Off Remote Input 16 Off
0x01F0 Remote IN 17 Off Remote Input 17 Off
0x01F1 Remote IN 18 Off Remote Input 18 Off
0x01F2 Remote IN 19 Off Remote Input 19 Off
0x01F3 Remote IN 20 Off Remote Input 20 Off
0x01F4 Remote IN 21 Off Remote Input 21 Off
0x01F5 Remote IN 22 Off Remote Input 22 Off
0x01F6 Remote IN 23 Off Remote Input 23 Off
0x01F7 Remote IN 24 Off Remote Input 24 Off
0x01F8 Remote IN 25 Off Remote Input 25 Off
0x01F9 Remote IN 26 Off Remote Input 26 Off
0x01FA Remote IN 27 Off Remote Input 27 Off
0x01FB Remote IN 28 Off Remote Input 28 Off
0x01FC Remote IN 29 Off Remote Input 29 Off
0x01FD Remote IN 30 Off Remote Input 30 Off
0x01FE Remote IN 31 Off Remote Input 31 Off
0x01FF Remote IN 32 Off Remote Input 32 Off
0x8002 Any Trip Any Trip

11-140 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x8042 Therm O/L Trip OP Thermal Overload Trip OP
0x8044 Therm O/L Trip DPO Thermal Overload Trip DPO
0x8081 RTD 1 Trip PKP RTD 1 Trip PKP
0x8082 RTD 1 Trip OP RTD 1 Trip OP
0x80C1 RTD 2 Trip PKP RTD 2 Trip PKP
0x80C2 RTD 2 Trip OP RTD 2 Trip OP
0x8101 RTD 3 Trip PKP RTD 3 Trip PKP
0x8102 RTD 3 Trip OP RTD 3 Trip OP
0x8141 RTD 4 Trip PKP RTD 4 Trip PKP
0x8142 RTD 4 Trip OP RTD 4 Trip OP
0x8201 RTD 5 Trip PKP RTD 5 Trip PKP
0x8202 RTD 5 Trip OP RTD 5 Trip OP
0x8241 RTD 6 Trip PKP RTD 6 Trip PKP
0x8242 RTD 6 Trip OP RTD 6 Trip OP
0x8281 RTD 7 Trip PKP RTD 7 Trip PKP
0x8282 RTD 7 Trip OP RTD 7 Trip OP
0x82C1 RTD 8 Trip PKP RTD 8 Trip PKP
0x82C2 RTD 8 Trip OP RTD 8 Trip OP
0x8301 RTD 9 Trip PKP RTD 9 Trip PKP
0x8302 RTD 9 Trip OP RTD 9 Trip OP
0x8341 RTD 10 Trip PKP RTD 10 Trip PKP
0x8342 RTD 10 Trip OP RTD 10 Trip OP
0x8381 RTD 11 Trip PKP RTD 11 Trip PKP
0x8382 RTD 11 Trip OP RTD 11 Trip OP
0x83C1 RTD 12 Trip PKP RTD 12 Trip PKP
0x83C2 RTD 12 Trip OP RTD 12 Trip OP
0x84C1 LE 1 Trip PKP Logic Element 1 Trip PKP
0x84C2 LE 1 Trip OP Logic Element 1 Trip OP
0x84C4 LE 1 Trip DPO Logic Element 1 Trip DPO
0x8501 LE 2 Trip PKP Logic Element 2 Trip PKP
0x8502 LE 2 Trip OP Logic Element 2 Trip OP
0x8504 LE 2 Trip DPO Logic Element 2 Trip DPO
0x8541 LE 3 Trip PKP Logic Element 3 Trip PKP
0x8542 LE 3 Trip OP Logic Element 3 Trip OP
0x8544 LE 3 Trip DPO Logic Element 3 Trip DPO
0x8581 LE 4 Trip PKP Logic Element 4 Trip PKP
0x8582 LE 4 Trip OP Logic Element 4 Trip OP
0x8584 LE 4 Trip DPO Logic Element 4 Trip DPO
0x85C1 LE 5 Trip PKP Logic Element 5 Trip PKP
0x85C2 LE 5 Trip OP Logic Element 5 Trip OP
0x85C4 LE 5 Trip DPO Logic Element 5 Trip DPO
0x8601 LE 6 Trip PKP Logic Element 6 Trip PKP
0x8602 LE 6 Trip OP Logic Element 6 Trip OP
0x8604 LE 6 Trip DPO Logic Element 6 Trip DPO
0x8641 LE 7 Trip PKP Logic Element 7 Trip PKP
0x8642 LE 7 Trip OP Logic Element 7 Trip OP
0x8644 LE 7 Trip DPO Logic Element 7 Trip DPO

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-141


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x8681 LE 8 Trip PKP Logic Element 8 Trip PKP
0x8682 LE 8 Trip OP Logic Element 8 Trip OP
0x8684 LE 8 Trip DPO Logic Element 8 Trip DPO
0x9001 Ph IOC1 Trip PKP Phase IOC 1 Trip PKP
0x9002 Ph IOC1 Trip OP Phase IOC 1 Trip OP
0x9004 Ph IOC1 Trip DPO Phase IOC 1 Trip DPO
0x9041 Ntrl IOC1 Trip PKP Neutral IOC 1 Trip PKP
0x9042 Ntrl IOC1 Trip OP Neutral IOC 1 Trip OP
0x9044 Ntrl IOC1 Trip DPO Neutral IOC 1 Trip DPO
0x9081 Gnd IOC1 Trip PKP Ground IOC 1 Trip PKP
0x9082 Gnd IOC1 Trip OP Ground IOC 1 Trip OP
0x9084 Gnd IOC1 Trip DPO Ground IOC 1 Trip DPO
0x90C1 Ph TOC1 Trip PKP Phase TOC 1 Trip PKP
0x90C2 Ph TOC1 Trip OP Phase TOC 1 Trip OP
0x90C4 Ph TOC1 Trip DPO Phase TOC 1 Trip DPO
0x9101 Ntrl TOC1 Trip PKP Neutral TOC 1 Trip PKP
0x9102 Ntrl TOC1 Trip OP Neutral TOC 1 Trip OP
0x9104 Ntrl TOC1 Trip DPO Neutral TOC 1 Trip DPO
0x9141 Gnd TOC1 Trip PKP Ground TOC Trip PKP
0x9142 Gnd TOC1 Trip OP Ground TOC 1 Trip OP
0x9144 Gnd TOC1 Trip DPO Ground TOC Trip DPO
0x9181 Ph IOC2 Trip PKP Phase IOC 2 Trip PKP
0x9182 Ph IOC2 Trip OP Phase IOC 2 Trip OP
0x9184 Ph IOC2 Trip DPO Phase IOC 2 Trip DPO
0x91C1 Ntrl IOC2 Trip PKP Neutral IOC 2 Trip PKP
0x91C2 Ntrl IOC2 Trip OP Neutral IOC 2 Trip OP
0x91C4 Ntrl IOC2 Trip DPO Neutral IOC 2 Trip DPO
0x9201 Gnd IOC2 Trip PKP Ground IOC 2 Trip PKP
0x9202 Gnd IOC2 Trip OP Ground IOC 2 Trip OP
0x9204 Gnd IOC2 Trip DPO Ground IOC 2 Trip DPO
0x9241 Ph TOC2 Trip PKP Phase TOC 2 Trip PKP
0x9242 Ph TOC2 Trip OP Phase TOC 2 Trip OP
0x9244 Ph TOC2 Trip DPO Phase TOC 2 Trip DPO
0x9281 Ntrl TOC2 Trip PKP Neutral TOC 2 Trip PKP
0x9282 Ntrl TOC2 Trip OP Neutral TOC 2 Trip OP
0x9284 Ntrl TOC2 Trip DPO Neutral TOC 2 Trip DPO
0x92C1 Gnd TOC2 Trip PKP Ground TOC 2 Trip PKP
0x92C2 Gnd TOC2 Trip OP Ground TOC 2 Trip OP
0x92C4 Gnd TOC2 Trip DPO Ground TOC 2 Trip DPO
0x9301 SGnd TOC1 Trip PKP Sensitive Ground TOC 1 Trip PKP
0x9302 SGnd TOC1 Trip OP Sensitive Ground TOC 1 Trip OP
0x9304 SGnd TOC1 Trip DPO Sensitive Ground TOC 1 Trip DPO
0x9641 SGnd IOC1 Trip PKP Sensitive Ground IOC 1 Trip PKP
0x9642 SGnd IOC1 Trip OP Sensitive Ground IOC 1 Trip OP
0x9644 SGnd IOC1 Trip DPO Sensitive Ground IOC 1 Trip DPO
0x9681 SGnd IOC2 Trip PKP Sensitive Ground IOC 2 Trip PKP
0x9682 SGnd IOC2 Trip OP Sensitive Ground IOC 2 Trip OP

11-142 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x9684 SGnd IOC2 Trip DPO Sensitive Ground IOC 2 Trip DPO
0x96C1 NSeq IOC Trp PKP Negative Sequence IOC Trip PKP
0x96C2 NSeq IOC Trp OP Negative Sequence IOC Trip OP
0x96C4 NSeq IOC Trp DPO Negative Sequence IOC Trip DPO
0x9701 Pcnt Diff Trip PKP Pcnt Diff Trip PKP
0x9702 Pcnt Diff Trip OP Pcnt Diff Trip OP
0x9704 Pcnt Diff Trip DPO Pcnt Diff Trip DPO
0x9741 RGF1 Trip PKP RGF1 Trip PKP
0x9742 RGF1 Trip OP RGF1 Trip OP
0x9744 RGF1 Trip DPO RGF1 Trip DPO
0x9781 RGF2 Trip PKP RGF2 Trip PKP
0x9782 RGF2 Trip OP RGF2 Trip OP
0x9784 RGF2 Trip DPO RGF2 Trip DPO
0x97C1 Inst Diff Trip PKP Inst Diff Trip PKP
0x97C2 Inst Diff Trip OP Inst Diff Trip OP
0x97C4 Inst Diff Trip DPO Inst Diff Trip DPO
0x9801 NSeq TOC1 Trip PKP Negative Sequence TOC 1 Trip PKP
0x9802 NSeq TOC1 Trip OP Negative Sequence TOC 1 Trip OP
0x9804 NSeq TOC1 Trip DPO Negative Sequence TOC 1 Trip DPO
0x9841 NSeq TOC2 Trip PKP Negative Sequence TOC 2 Trip PKP
0x9842 NSeq TOC2 Trip OP Negative Sequence TOC 2 Trip OP
0x9844 NSeq TOC2 Trip DPO Negative Sequence TOC 2 Trip DPO
0x9901 NSeq IOC 2 Trp PKP Negative Sequence IOC 2 Trip PKP
0x9902 NSeq IOC 2 Trp OP Negative Sequence IOC 2 Trip OP
0x9904 NSeq IOC 2 Trp DPO Negative Sequence IOC 2 Trip DPO
0x99C1 SGnd TOC2 Trip PKP Sensitive Ground TOC 2 Trip PKP
0x99C2 SGnd TOC2 Trip OP Sensitive Ground TOC 2 Trip OP
0x99C4 SGnd TOC2 Trip DPO Sensitive Ground TOC 2 Trip DPO
0x9C01 LE 9 Trip PKP Logic Element 9 Trip PKP
0x9C02 LE 9 Trip OP Logic Element 9 Trip OP
0x9C04 LE 9 Trip DPO Logic Element 9 Trip DPO
0x9C41 LE 10 Trip PKP Logic Element 10 Trip PKP
0x9C42 LE 10 Trip OP Logic Element 10 Trip OP
0x9C44 LE 10 Trip DPO Logic Element 10 Trip DPO
0x9C81 LE 11 Trip PKP Logic Element 11 Trip PKP
0x9C82 LE 11 Trip OP Logic Element 11 Trip OP
0x9C84 LE 11 Trip DPO Logic Element 11 Trip DPO
0x9CC1 LE 12 Trip PKP Logic Element 12 Trip PKP
0x9CC2 LE 12 Trip OP Logic Element 12 Trip OP
0x9CC4 LE 12 Trip DPO Logic Element 12 Trip DPO
0x9D01 LE 13 Trip PKP Logic Element 13 Trip PKP
0x9D02 LE 13 Trip OP Logic Element 13 Trip OP
0x9D04 LE 13 Trip DPO Logic Element 13 Trip DPO
0x9D41 LE 14 Trip PKP Logic Element 14 Trip PKP
0x9D42 LE 14 Trip OP Logic Element 14 Trip OP
0x9D44 LE 14 Trip DPO Logic Element 14 Trip DPO
0x9D81 LE 15 Trip PKP Logic Element 15 Trip PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-143


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x9D82 LE 15 Trip OP Logic Element 15 Trip OP
0x9D84 LE 15 Trip DPO Logic Element 15 Trip DPO
0x9DC1 LE 16 Trip PKP Logic Element 16 Trip PKP
0x9DC2 LE 16 Trip OP Logic Element 16 Trip OP
0x9DC4 LE 16 Trip DPO Logic Element 16 Trip DPO
0xA002 Any Alarm Any Alarm
0xA042 Therm Lvl Alrm OP Thermal Level Alarm OP
0xA044 Therm Lvl Alrm DPO Thermal Level Alarm DPO
0xA081 RTD 1 Alarm PKP RTD 1 Alarm PKP
0xA082 RTD 1 Alarm OP RTD 1 Alarm OP
0xA0C1 RTD 2 Alarm PKP RTD 2 Alarm PKP
0xA0C2 RTD 2 Alarm OP RTD 2 Alarm OP
0xA101 RTD 3 Alarm PKP RTD 3 Alarm PKP
0xA102 RTD 3 Alarm OP RTD 3 Alarm OP
0xA141 RTD 4 Alarm PKP RTD 4 Alarm PKP
0xA142 RTD 4 Alarm OP RTD 4 Alarm OP
0xA201 RTD 5 Alarm PKP RTD 5 Alarm PKP
0xA202 RTD 5 Alarm OP RTD 5 Alarm OP
0xA241 RTD 6 Alarm PKP RTD 6 Alarm PKP
0xA242 RTD 6 Alarm OP RTD 6 Alarm OP
0xA281 RTD 7 Alarm PKP RTD 7 Alarm PKP
0xA282 RTD 7 Alarm OP RTD 7 Alarm OP
0xA2C1 RTD 8 Alarm PKP RTD 8 Alarm PKP
0xA2C2 RTD 8 Alarm OP RTD 8 Alarm OP
0xA301 RTD 9 Alarm PKP RTD 9 Alarm PKP
0xA302 RTD 9 Alarm OP RTD 9 Alarm OP
0xA341 RTD 10 Alarm PKP RTD 10 Alarm PKP
0xA342 RTD 10 Alarm OP RTD 10 Alarm OP
0xA381 RTD 11 Alarm PKP RTD 11 Alarm PKP
0xA382 RTD 11 Alarm OP RTD 11 Alarm OP
0xA3C1 RTD 12 Alarm PKP RTD 12 Alarm PKP
0xA3C2 RTD 12 Alarm OP RTD 12 Alarm OP
0xA402 RTD Trouble Alr OP RTD Trouble Alarm
0xA4C1 LE 1 Alarm PKP Logic Element 1 Alarm PKP
0xA4C2 LE 1 Alarm OP Logic Element 1 Alarm OP
0xA4C4 LE 1 Alarm DPO Logic Element 1 Alarm DPO
0xA501 LE 2 Alarm PKP Logic Element 2 Alarm PKP
0xA502 LE 2 Alarm OP Logic Element 2 Alarm OP
0xA504 LE 2 Alarm DPO Logic Element 2 Alarm DPO
0xA541 LE 3 Alarm PKP Logic Element 3 Alarm PKP
0xA542 LE 3 Alarm OP Logic Element 3 Alarm OP
0xA544 LE 3 Alarm DPO Logic Element 3 Alarm DPO
0xA581 LE 4 Alarm PKP Logic Element 4 Alarm PKP
0xA582 LE 4 Alarm OP Logic Element 4 Alarm OP
0xA584 LE 4 Alarm DPO Logic Element 4 Alarm DPO
0xA5C1 LE 5 Alarm PKP Logic Element 5 Alarm PKP
0xA5C2 LE 5 Alarm OP Logic Element 5 Alarm OP

11-144 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0xA5C4 LE 5 Alarm DPO Logic Element 5 Alarm DPO
0xA601 LE 6 Alarm PKP Logic Element 6 Alarm PKP
0xA602 LE 6 Alarm OP Logic Element 6 Alarm OP
0xA604 LE 6 Alarm DPO Logic Element 6 Alarm DPO
0xA641 LE 7 Alarm PKP Logic Element 7 Alarm PKP
0xA642 LE 7 Alarm OP Logic Element 7 Alarm OP
0xA644 LE 7 Alarm DPO Logic Element 7 Alarm DPO
0xA681 LE 8 Alarm PKP Logic Element 8 Alarm PKP
0xA682 LE 8 Alarm OP Logic Element 8 Alarm OP
0xA684 LE 8 Alarm DPO Logic Element 8 Alarm DPO
0xA6C2 Curr Dmd1 Alrm OP Current Demand 1 Alarm OP
0xA702 Curr Dmd2 Alrm OP Current Demand 2 Alarm OP
0xA842 W1BKR Alarm W1 Breaker Alarm
0xA882 W1BKR Trip Time W1 Breaker Trip Time
0xA8C2 W1BKR Close Time W1 Breaker Close Time
0xA902 W1BKR Charge Time W1 Breaker Charge Time
0xA942 W2BKR Alarm W2 Breaker Alarm
0xA982 W2BKR Trip Time W2 Breaker Trip Time
0xA9C2 W2BKR Close Time W2 Breaker Close Time
0xAA02 W2BKR Charge Time W2 Breaker Charge Time
0xABC1 HI Amb Temp PKP High Ambient Temperature Alarm PKP
0xABC2 HI Amb Temp OP High Ambient Temperature Alarm
0xABC4 HI Amb Temp DPO High Ambient Temperature Alarm DPO
0xAC01 LO Amb Temp PKP Low Ambient Temperature Alarm PKP
0xAC02 LO Amb Temp OP Low Ambient Temperature Alarm
0xAC04 LO Amb Temp DPO Low Ambient Temperature Alarm DPO
0xAC42 Self Test Alarm OP Self Test Alarm OP
0xACC2 BKRTrpCntrAlrm OP Breaker Trip Control Alarm OP
0xAD01 R1 CoilMonAlrm PKP Trip Coil Monitor Alarm PKP
0xAD02 R1 CoilMonAlrm OP Trip Coil Monitor Alarm OP
0xAD04 R1 CoilMonAlrm DPO Trip Coil Monitor Alarm DPO
0xAD41 R2 CoilMonAlrm PKP Close Coil Monitor Alarm PKP
0xAD42 R2 CoilMonAlrm OP Close Coil Monitor Alarm OP
0xAD44 R2 CoilMonAlrm DPO Close Coil Monitor Alarm DPO
0xAD81 BKR1 Fail Alrm PKP Breaker 1 Fail Alarm PKP
0xAD82 BKR1 Fail Alrm OP Breaker 1 Fail Alarm OP
0xAD84 BKR1 Fail Alrm DPO Breaker 1 Fail Alarm DPO
0xADC2 BKR Stat Fail OP Breaker Status Fail OP
0xAEC2 BKR2 Stat Fail OP Breaker 2 Status Fail OP
0xAF41 BKR2 Fail Alrm PKP Breaker 2 Fail Alarm PKP
0xAF42 BKR2 Fail Alrm OP Breaker 2 Fail Alarm OP
0xAF44 BKR2 Fail Alrm DPO Breaker 2 Fail Alarm DPO
0xB001 Ph IOC1 Alarm PKP Phase IOC 1 Alarm PKP
0xB002 Ph IOC1 Alarm OP Phase IOC 1 Alarm OP
0xB004 Ph IOC1 Alarm DPO Phase IOC 1 Alarm DPO
0xB041 Ntrl IOC1 Alrm PKP Neutral IOC 1 Alarm PKP
0xB042 Ntrl IOC1 Alrm OP Neutral IOC 1 Alarm OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-145


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xB044 Ntrl IOC1 Alrm DPO Neutral IOC 1 Alarm DPO
0xB081 Gnd IOC1 Alarm PKP Ground IOC 1 Alarm PKP
0xB082 Gnd IOC1 Alarm OP Ground IOC 1 Alarm OP
0xB084 Gnd IOC1 Alarm DPO Ground IOC 1 Alarm DPO
0xB0C1 Ph TOC1 Alarm PKP Phase TOC 1 Alarm PKP
0xB0C2 Ph TOC1 Alarm OP Phase TOC 1 Alarm OP
0xB0C4 Ph TOC1 Alarm DPO Phase TOC 1 Alarm DPO
0xB101 Ntrl TOC1 Alrm PKP Neutral TOC 1 Alarm PKP
0xB102 Ntrl TOC1 Alrm OP Neutral TOC 1 Alarm OP
0xB104 Ntrl TOC1 Alrm DPO Neutral TOC 1 Alarm DPO
0xB141 Gnd TOC1 Alarm PKP Ground TOC Alarm PKP
0xB142 Gnd TOC1 Alarm OP Ground TOC 1 Alarm OP
0xB144 Gnd TOC1 Alarm DPO Ground TOC Alarm DPO
0xB181 Ph IOC2 Alarm PKP Phase IOC 2 Alarm PKP
0xB182 Ph IOC2 Alarm OP Phase IOC 2 Alarm OP
0xB184 Ph IOC2 Alarm DPO Phase IOC 2 Alarm DPO
0xB1C1 Ntrl IOC2 Alrm PKP Neutral IOC 2 Alarm PKP
0xB1C2 Ntrl IOC2 Alrm OP Neutral IOC 2 Alarm OP
0xB1C4 Ntrl IOC2 Alrm DPO Neutral IOC 2 Alarm DPO
0xB201 Gnd IOC2 Alarm PKP Ground IOC 2 Alarm PKP
0xB202 Gnd IOC2 Alarm OP Ground IOC 2 Alarm OP
0xB204 Gnd IOC2 Alarm DPO Ground IOC 2 Alarm DPO
0xB241 Ph TOC2 Alrm PKP Phase TOC 2 Alarm PKP
0xB242 Ph TOC2 Alrm OP Phase TOC 2 Alarm OP
0xB244 Ph TOC2 Alrm DPO Phase TOC 2 Alarm DPO
0xB281 Ntrl TOC2 Alrm PKP Neutral TOC 2 Alarm PKP
0xB282 Ntrl TOC2 Alrm OP Neutral TOC 2 Alarm OP
0xB284 Ntrl TOC2 Alrm DPO Neutral TOC 2 Alarm DPO
0xB2C1 Gnd TOC2 Alarm PKP Ground TOC 2 Alarm PKP
0xB2C2 Gnd TOC2 Alarm OP Ground TOC 2 Alarm OP
0xB2C4 Gnd TOC2 Alarm DPO Ground TOC 2 Alarm DPO
0xB301 SGnd TOC1 Alrm PKP Sensitive Ground TOC 1 Alarm PKP
0xB302 SGnd TOC1 Alrm OP Sensitive Ground TOC 1 Alarm OP
0xB304 SGnd TOC1 Alrm DPO Sensitive Ground TOC 1 Alarm DPO
0xB641 SGnd IOC1 Alrm PKP Sensitive Ground IOC 1 Alarm PKP
0xB642 SGnd IOC1 Alrm OP Sensitive Ground IOC 1 Alarm OP
0xB644 SGnd IOC1 Alrm DPO Sensitive Ground IOC 1 Alarm DPO
0xB681 SGnd IOC2 Alrm PKP Sensitive Ground IOC 2 Alarm PKP
0xB682 SGnd IOC2 Alrm OP Sensitive Ground IOC 2 Alarm OP
0xB684 SGnd IOC2 Alrm DPO Sensitive Ground IOC 2 Alarm DPO
0xB6C1 NSeq IOC Alrm PKP Negative Sequence IOC Alarm PKP
0xB6C2 NSeq IOC Alrm OP NSeq IOC Alrm OP
0xB6C4 NSeq IOC Alrm DPO Negative Sequence IOC Alarm DPO
0xB701 Pcnt Diff Alrm PKP Pcnt Diff Alrm PKP
0xB702 Pcnt Diff Alrm OP Pcnt Diff Alrm OP
0xB704 Pcnt Diff Alrm DPO Pcnt Diff Alrm DPO
0xB741 RGF1 Alarm PKP RGF1 Alarm PKP

11-146 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0xB742 RGF1 Alarm OP RGF1 Alarm OP
0xB744 RGF1 Alarm DPO RGF1 Alarm DPO
0xB781 RGF2 Alarm PKP RGF2 Alarm PKP
0xB782 RGF2 Alarm OP RGF2 Alarm OP
0xB784 RGF2 Alarm DPO RGF2 Alarm DPO
0xB7C1 Inst Diff Alrm PKP Inst Diff Alrm PKP
0xB7C2 Inst Diff Alrm OP Inst Diff Alrm OP
0xB7C4 Inst Diff Alrm DPO Inst Diff Alrm DPO
0xB801 NSeq TOC1 Alrm PKP Negative Sequence TOC 1 Alarm PKP
0xB802 NSeq TOC1 Alrm OP Negative Sequence TOC 1 Alarm OP
0xB804 NSeq TOC1 Alrm DPO Negative Sequence TOC 1 Alarm DPO
0xB841 NSeq TOC2 Alrm PKP Negative Sequence TOC 2 Alarm PKP
0xB842 NSeq TOC2 Alrm OP Negative Sequence TOC 2 Alarm OP
0xB844 NSeq TOC2 Alrm DPO Negative Sequence TOC 2 Alarm DPO
0xB901 NSeq IOC 2 AlrmPKP Negative Sequence IOC 2 Alarm PKP
0xB902 NSeq IOC 2 Alrm OP Negative Sequence IOC 2 Alarm OP
0xB904 NSeq IOC 2 AlrmDPO Negative Sequence IOC 2 Alarm DPO
0xB9C1 SGnd TOC2 Alrm PKP Sensitive Ground TOC 2 Alarm PKP
0xB9C2 SGnd TOC2 Alrm OP Sensitive Ground TOC 2 Alarm OP
0xB9C4 SGnd TOC2 Alrm DPO Sensitive Ground TOC 2 Alarm DPO
0xBA02 W1BKR Trp/Cls Fail W1 Breaker Trip/Close Fail
0xBA42 W1BKR Charge Fail W1 Breaker Charge Fail
0xBA82 W2BKR Trp/Cls Fail W2 Breaker Trip/Close Fail
0xBAC2 W2BKR Charge Fail W2 Breaker Charge Fail
0xBB02 W2BKRTrpCntrAlrm OP W2BKRTrpCntrAlrm OP
0xBC01 LE 9 Alarm PKP Logic Element 9 Alarm PKP
0xBC02 LE 9 Alarm OP Logic Element 9 Alarm OP
0xBC04 LE 9 Alarm DPO Logic Element 9 Alarm DPO
0xBC41 LE 10 Alarm PKP Logic Element 10 Alarm PKP
0xBC42 LE 10 Alarm OP Logic Element 10 Alarm OP
0xBC44 LE 10 Alarm DPO Logic Element 10 Alarm DPO
0xBC81 LE 11 Alarm PKP Logic Element 11 Alarm PKP
0xBC82 LE 11 Alarm OP Logic Element 11 Alarm OP
0xBC84 LE 11 Alarm DPO Logic Element 11 Alarm DPO
0xBCC1 LE 12 Alarm PKP Logic Element 12 Alarm PKP
0xBCC2 LE 12 Alarm OP Logic Element 12 Alarm OP
0xBCC4 LE 12 Alarm DPO Logic Element 12 Alarm DPO
0xBD01 LE 13 Alarm PKP Logic Element 13 Alarm PKP
0xBD02 LE 13 Alarm OP Logic Element 13 Alarm OP
0xBD04 LE 13 Alarm DPO Logic Element 13 Alarm DPO
0xBD41 LE 14 Alarm PKP Logic Element 14 Alarm PKP
0xBD42 LE 14 Alarm OP Logic Element 14 Alarm OP
0xBD44 LE 14 Alarm DPO Logic Element 14 Alarm DPO
0xBD81 LE 15 Alarm PKP Logic Element 15 Alarm PKP
0xBD82 LE 15 Alarm OP Logic Element 15 Alarm OP
0xBD84 LE 15 Alarm DPO Logic Element 15 Alarm DPO
0xBDC1 LE 16 Alarm PKP Logic Element 16 Alarm PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-147


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xBDC2 LE 16 Alarm OP Logic Element 16 Alarm OP
0xBDC4 LE 16 Alarm DPO Logic Element 16 Alarm DPO
0xC042 Output Relay 3 On Output Relay 3 On
0xC082 Output Relay 4 On Output Relay 4 On
0xC0C2 Output Relay 5 On Output Relay 5 On
0xC102 Output Relay 6 On Output Relay 6 On
0xC142 Self-Test Rly 7 OP Self-Test Rly 7 OP
0xC182 Rly1 Coil OP Relay # 1 Coil OP
0xC1C2 Rly2 Coil OP Relay # 2 Coil OP
0xC202 BKR Connected Breaker Connected OP
0xC2C2 BKR2 Connected Breaker 2 Connected OP
0xC401 Hot RTD PKP Hot RTD PKP
0xC402 Hot RTD OP Hot RTD OP
0xC482 Any Pkp OP Any Pkp OP
0xC4C1 LE 1 PKP Logic Element 1 PKP
0xC4C2 LE 1 OP Logic Element 1 OP
0xC4C4 LE 1 DPO Logic Element 1 DPO
0xC501 LE 2 PKP Logic Element 2 PKP
0xC502 LE 2 OP Logic Element 2 OP
0xC504 LE 2 DPO Logic Element 2 DPO
0xC541 LE 3 PKP Logic Element 3 PKP
0xC542 LE 3 OP Logic Element 3 OP
0xC544 LE 3 DPO Logic Element 3 DPO
0xC581 LE 4 PKP Logic Element 4 PKP
0xC582 LE 4 OP Logic Element 4 OP
0xC584 LE 4 DPO Logic Element 4 DPO
0xC5C1 LE 5 PKP Logic Element 5 PKP
0xC5C2 LE 5 OP Logic Element 5 OP
0xC5C4 LE 5 DPO Logic Element 5 DPO
0xC601 LE 6 PKP Logic Element 6 PKP
0xC602 LE 6 OP Logic Element 6 OP
0xC604 LE 6 DPO Logic Element 6 DPO
0xC641 LE 7 PKP Logic Element 7 PKP
0xC642 LE 7 OP Logic Element 7 OP
0xC644 LE 7 DPO Logic Element 7 DPO
0xC681 LE 8 PKP Logic Element 8 PKP
0xC682 LE 8 OP Logic Element 8 OP
0xC684 LE 8 DPO Logic Element 8 DPO
0xC882 Setpoint Group2 On Setpoint Group2 On
0xC982 Maint. Req. OP Maintenance Required OP
0xCA02 52a Contact OP 52a Contact OP
0xCA42 52b Contact OP 52b Contact OP
0xCA82 Reset OK Reset OK
0xCAC2 L/O Rst Closed OP Lockout Reset Closed OP
0xCC02 Lockout OP Lockout OP
0xCC04 Lockout DPO Lockout DPO
0xCC42 Testing ON Testing ON

11-148 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0xCC44 Testing OFF Testing OFF
0xCCC2 BKR Stat Open Breaker Status Open OP
0xCD02 BKR Stat Clsd Breaker Status Closed OP
0xCD42 Setpoint Group1 On Setpoint Group1 On
0xDA02 BKR2 52a Cont OP BKR2 52a Cont OP
0xDA42 BKR2 52b Cont OP BKR2 52b Cont OP
0xDA82 BKR2 Stat Open BKR2 Stat Open
0xDAC2 BKR2 Stat Clsd BKR2 Stat Clsd
0xDB02 Trip BKR 1 OP Trip BKR 1 OP
0xDB04 Trip BKR 1 DPO Trip BKR 1 DPO
0xDB42 Trip BKR 2 OP Trip BKR 2 OP
0xDB44 Trip BKR 2 DPO Trip BKR 2 DPO
0xDB82 2nd Hmnc Diff OP 2nd Hmnc Diff OP
0xDB8A 2nd Hmnc Diff Ph A 2nd Harmonic Diff Ph A
0xDB92 2nd Hmnc Diff Ph B 2nd Harmonic Diff Ph B
0xDBA2 2nd Hmnc Diff Ph C 2nd Harmonic Diff Ph C
0xDBC2 5th Hmnc Diff OP 5th Hmnc Diff OP
0xDBCA 5th Hmnc Diff Ph A 5th Harmonic Diff Ph A
0xDBD2 5th Hmnc Diff Ph B 5th Harmonic Diff Ph B
0xDBE2 5th Hmnc Diff Ph C 5th Harmonic Diff Ph C
0xDC01 LE 9 PKP Logic Element 9 PKP
0xDC02 LE 9 OP Logic Element 9 OP
0xDC04 LE 9 DPO Logic Element 9 DPO
0xDC41 LE 10 PKP Logic Element 10 PKP
0xDC42 LE 10 OP Logic Element 10 OP
0xDC44 LE 10 DPO Logic Element 10 DPO
0xDC81 LE 11 PKP Logic Element 11 PKP
0xDC82 LE 11 OP Logic Element 11 OP
0xDC84 LE 11 DPO Logic Element 11 DPO
0xDCC1 LE 12 PKP Logic Element 12 PKP
0xDCC2 LE 12 OP Logic Element 12 OP
0xDCC4 LE 12 DPO Logic Element 12 DPO
0xDD01 LE 13 PKP Logic Element 13 PKP
0xDD02 LE 13 OP Logic Element 13 OP
0xDD04 LE 13 DPO Logic Element 13 DPO
0xDD41 LE 14 PKP Logic Element 14 PKP
0xDD42 LE 14 OP Logic Element 14 OP
0xDD44 LE 14 DPO Logic Element 14 DPO
0xDD81 LE 15 PKP Logic Element 15 PKP
0xDD82 LE 15 OP Logic Element 15 OP
0xDD84 LE 15 DPO Logic Element 15 DPO
0xDDC1 LE 16 PKP Logic Element 16 PKP
0xDDC2 LE 16 OP Logic Element 16 OP
0xDDC4 LE 16 DPO Logic Element 16 DPO
0xE002 Any Block Any Block
0xE042 Therm O/L Block Thermal Level Block
0xE082 RTD1 Block RTD1 Block

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-149


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xE0C2 RTD2 Block RTD2 Block
0xE102 RTD3 Block RTD3 Block
0xE142 RTD4 Block RTD4 Block
0xE182 Output Relay 1 Blk Output Relay 1 Block
0xE1C2 Output Relay 2 Blk Output Relay 2 Block
0xE202 RTD5 Block RTD5 Block
0xE242 RTD6 Block RTD6 Block
0xE282 RTD7 Block RTD7 Block
0xE2C2 RTD8 Block RTD8 Block
0xE302 RTD9 Block RTD9 Block
0xE342 RTD10 Block RTD10 Block
0xE382 RTD11 Block RTD11 Block
0xE3C2 RTD12 Block RTD12 Block
0xE402 RTDTrouble Block RTDTrouble Block
0xE6C2 Curr Dmd1 Block Current Demand 1 Block OP
0xE702 Curr Dmd2 Block Current Demand 2 Block OP
0xE882 Group Change Blk Group Change Blk
0xEC02 Lockout Block Lockout Block
0xF002 Ph IOC1 Block Phase IOC 1 Block
0xF042 Ntrl IOC1 Block Neutral IOC 1 Block
0xF082 Gnd IOC1 Block Ground IOC 1 Block
0xF0C2 Ph TOC1 Block Phase TOC 1 Block
0xF102 Ntrl TOC1 Block Neutral TOC 1 Block
0xF142 Gnd TOC1 Block Ground TOC 1 Block
0xF182 Ph IOC2 Block Phase IOC 2 Block
0xF1C2 Ntrl IOC2 Block Neutral IOC 2 Block
0xF202 Gnd IOC2 Block Ground IOC 2 Block
0xF242 Ph TOC2 Block Phase TOC 2 Block
0xF282 Ntrl TOC2 Block Neutral TOC 2 Block
0xF2C2 Gnd TOC2 Block Ground TOC 2 Block
0xF302 SGnd TOC1 Block Sensitive Ground TOC 1 Block
0xF642 SGnd IOC1 Block Sensitive Ground IOC 1 Block
0xF682 SGnd IOC2 Block Sensitive Ground IOC 2 Block
0xF6C2 NSeq IOC Block Negative Sequence IOC Block
0xF702 Pcnt Diff Block Pcnt Diff Block
0xF742 RGF1 Block RGF1 Block
0xF782 RGF2 Block RGF2 Block
0xF7C2 Inst Diff Block Inst Diff Block
0xF802 NSeq TOC1 Blk Negative Sequence TOC 1 Block
0xF842 NSeq TOC2 Blk Negative Sequence TOC 2 Block
0xF902 NSeq IOC 2 Block Negative Sequence IOC 2 Block
0xF9C2 SGnd TOC2 Block Sensitive Ground TOC 2 Block
0xFB02 Trip BKR1 Blk Trip BKR1 Blk
0xFB42 Trip BKR2 Blk Trip BKR2 Blk
FC134D unsigned 16 bits Lockout Trigger
0 Off Off
0x0001 On On

11-150 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x0040 Contact IN 1 On Contact Input 1 On
0x0041 Contact IN 2 On Contact Input 2 On
0x0042 Contact IN 3 On Contact Input 3 On
0x0043 Contact IN 4 On Contact Input 4 On
0x0044 Contact IN 5 On Contact Input 5 On
0x0045 Contact IN 6 On Contact Input 6 On
0x0046 Contact IN 7 On Contact Input 7 On
0x0047 Contact IN 8 On Contact Input 8 On
0x0048 Contact IN 9 On Contact Input 9 On
0x0049 Contact IN 10 On Contact Input 10 On
0x0060 Contact IN 1 Off Contact Input 1 Off
0x0061 Contact IN 2 Off Contact Input 2 Off
0x0062 Contact IN 3 Off Contact Input 3 Off
0x0063 Contact IN 4 Off Contact Input 4 Off
0x0064 Contact IN 5 Off Contact Input 5 Off
0x0065 Contact IN 6 Off Contact Input 6 Off
0x0066 Contact IN 7 Off Contact Input 7 Off
0x0067 Contact IN 8 Off Contact Input 8 Off
0x0068 Contact IN 9 Off Contact Input 9 Off
0x0069 Contact IN 10 Off Contact Input 10 Off
0x0080 Virtual IN 1 On Virtual Input 1 On
0x0081 Virtual IN 2 On Virtual Input 2 On
0x0082 Virtual IN 3 On Virtual Input 3 On
0x0083 Virtual IN 4 On Virtual Input 4 On
0x0084 Virtual IN 5 On Virtual Input 5 On
0x0085 Virtual IN 6 On Virtual Input 6 On
0x0086 Virtual IN 7 On Virtual Input 7 On
0x0087 Virtual IN 8 On Virtual Input 8 On
0x0088 Virtual IN 9 On Virtual Input 9 On
0x0089 Virtual IN 10 On Virtual Input 10 On
0x008A Virtual IN 11 On Virtual Input 11 On
0x008B Virtual IN 12 On Virtual Input 12 On
0x008C Virtual IN 13 On Virtual Input 13 On
0x008D Virtual IN 14 On Virtual Input 14 On
0x008E Virtual IN 15 On Virtual Input 15 On
0x008F Virtual IN 16 On Virtual Input 16 On
0x0090 Virtual IN 17 On Virtual Input 17 On
0x0091 Virtual IN 18 On Virtual Input 18 On
0x0092 Virtual IN 19 On Virtual Input 19 On
0x0093 Virtual IN 20 On Virtual Input 20 On
0x0094 Virtual IN 21 On Virtual Input 21 On
0x0095 Virtual IN 22 On Virtual Input 22 On
0x0096 Virtual IN 23 On Virtual Input 23 On
0x0097 Virtual IN 24 On Virtual Input 24 On
0x0098 Virtual IN 25 On Virtual Input 25 On
0x0099 Virtual IN 26 On Virtual Input 26 On
0x009A Virtual IN 27 On Virtual Input 27 On

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-151


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x009B Virtual IN 28 On Virtual Input 28 On
0x009C Virtual IN 29 On Virtual Input 29 On
0x009D Virtual IN 30 On Virtual Input 30 On
0x009E Virtual IN 31 On Virtual Input 31 On
0x009F Virtual IN 32 On Virtual Input 32 On
0x00A0 Virtual IN 1 Off Virtual Input 1 Off
0x00A1 Virtual IN 2 Off Virtual Input 2 Off
0x00A2 Virtual IN 3 Off Virtual Input 3 Off
0x00A3 Virtual IN 4 Off Virtual Input 4 Off
0x00A4 Virtual IN 5 Off Virtual Input 5 Off
0x00A5 Virtual IN 6 Off Virtual Input 6 Off
0x00A6 Virtual IN 7 Off Virtual Input 7 Off
0x00A7 Virtual IN 8 Off Virtual Input 8 Off
0x00A8 Virtual IN 9 Off Virtual Input 9 Off
0x00A9 Virtual IN 10 Off Virtual Input 10 Off
0x00AA Virtual IN 11 Off Virtual Input 11 Off
0x00AB Virtual IN 12 Off Virtual Input 12 Off
0x00AC Virtual IN 13 Off Virtual Input 13 Off
0x00AD Virtual IN 14 Off Virtual Input 14 Off
0x00AE Virtual IN 15 Off Virtual Input 15 Off
0x00AF Virtual IN 16 Off Virtual Input 16 Off
0x00B0 Virtual IN 17 Off Virtual Input 17 Off
0x00B1 Virtual IN 18 Off Virtual Input 18 Off
0x00B2 Virtual IN 19 Off Virtual Input 19 Off
0x00B3 Virtual IN 20 Off Virtual Input 20 Off
0x00B4 Virtual IN 21 Off Virtual Input 21 Off
0x00B5 Virtual IN 22 Off Virtual Input 22 Off
0x00B6 Virtual IN 23 Off Virtual Input 23 Off
0x00B7 Virtual IN 24 Off Virtual Input 24 Off
0x00B8 Virtual IN 25 Off Virtual Input 25 Off
0x00B9 Virtual IN 26 Off Virtual Input 26 Off
0x00BA Virtual IN 27 Off Virtual Input 27 Off
0x00BB Virtual IN 28 Off Virtual Input 28 Off
0x00BC Virtual IN 29 Off Virtual Input 29 Off
0x00BD Virtual IN 30 Off Virtual Input 30 Off
0x00BE Virtual IN 31 Off Virtual Input 31 Off
0x00BF Virtual IN 32 Off Virtual Input 32 Off
0x8002 Any Trip Any Trip
0x8042 Therm O/L Trip OP Thermal Overload Trip OP
0x804A Therm PhA Trip OP Thermal Phase A Trip OP
0x8052 Therm PhB Trip OP Thermal Phase B Trip OP
0x8062 Therm PhC Trip OP Thermal Phase C Trip OP
0x8082 RTD 1 Trip OP RTD 1 Trip OP
0x80C2 RTD 2 Trip OP RTD 2 Trip OP
0x8102 RTD 3 Trip OP RTD 3 Trip OP
0x8142 RTD 4 Trip OP RTD 4 Trip OP
0x8202 RTD 5 Trip OP RTD 5 Trip OP

11-152 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x8242 RTD 6 Trip OP RTD 6 Trip OP
0x8282 RTD 7 Trip OP RTD 7 Trip OP
0x82C2 RTD 8 Trip OP RTD 8 Trip OP
0x8302 RTD 9 Trip OP RTD 9 Trip OP
0x8342 RTD 10 Trip OP RTD 10 Trip OP
0x8382 RTD 11 Trip OP RTD 11 Trip OP
0x83C2 RTD 12 Trip OP RTD 12 Trip OP
0x84C2 LE 1 Trip OP Logic Element 1 Trip OP
0x8502 LE 2 Trip OP Logic Element 2 Trip OP
0x8542 LE 3 Trip OP Logic Element 3 Trip OP
0x8582 LE 4 Trip OP Logic Element 4 Trip OP
0x85C2 LE 5 Trip OP Logic Element 5 Trip OP
0x8602 LE 6 Trip OP Logic Element 6 Trip OP
0x8642 LE 7 Trip OP Logic Element 7 Trip OP
0x8682 LE 8 Trip OP Logic Element 8 Trip OP
0x9002 Ph IOC1 Trip OP Phase IOC 1 Trip OP
0x900A Ph A IOC1 Trip OP Phase A IOC 1 Trip OP
0x9012 Ph B IOC1 Trip OP Phase B IOC 1 Trip OP
0x9022 Ph C IOC1 Trip OP Phase C IOC 1 Trip OP
0x9042 Ntrl IOC1 Trip OP Neutral IOC 1 Trip OP
0x9082 Gnd IOC1 Trip OP Ground IOC 1 Trip OP
0x90C2 Ph TOC1 Trip OP Phase TOC 1 Trip OP
0x90CA Ph A TOC1 Trip OP Phase A TOC 1 Trip OP
0x90D2 Ph B TOC1 Trip OP Phase B TOC 1 Trip OP
0x90E2 Ph C TOC1 Trip OP Phase C TOC 1 Trip OP
0x9102 Ntrl TOC1 Trip OP Neutral TOC 1 Trip OP
0x9142 Gnd TOC1 Trip OP Ground TOC 1 Trip OP
0x9182 Ph IOC2 Trip OP Phase IOC 2 Trip OP
0x918A Ph A IOC2 Trip OP Phase A IOC 2 Trip OP
0x9192 Ph B IOC2 Trip OP Phase B IOC 2 Trip OP
0x91A2 Ph C IOC2 Trip OP Phase C IOC 2 Trip OP
0x91C2 Ntrl IOC2 Trip OP Neutral IOC 2 Trip OP
0x9202 Gnd IOC2 Trip OP Ground IOC 2 Trip OP
0x9242 Ph TOC2 Trip OP Phase TOC 2 Trip OP
0x924A Ph A TOC2 Trip OP Phase A TOC 2 Trip OP
0x9252 Ph B TOC2 Trip OP Phase B TOC 2 Trip OP
0x9262 Ph C TOC2 Trip OP Phase C TOC 2 Trip OP
0x9282 Ntrl TOC2 Trip OP Neutral TOC 2 Trip OP
0x92C2 Gnd TOC2 Trip OP Ground TOC 2 Trip OP
0x9302 SGnd TOC1 Trip OP Sensitive Ground TOC 1 Trip OP
0x9642 SGnd IOC1 Trip OP Sensitive Ground IOC 1 Trip OP
0x9682 SGnd IOC2 Trip OP Sensitive Ground IOC 2 Trip OP
0x96C2 NSeq IOC Trp OP Negative Sequence IOC Trip OP
0x9702 Pcnt Diff Trip OP Pcnt Diff Trip OP
0x970A Ph Diff A Trip OP Ph Diff A Trip OP
0x9712 Ph Diff B Trip OP Ph Diff B Trip OP
0x9722 Ph Diff C Trip OP Ph Diff C Trip OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-153


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x9742 RGF1 Trip OP RGF1 Trip OP
0x9782 RGF2 Trip OP RGF2 Trip OP
0x97C2 Inst Diff Trip OP Inst Diff Trip OP
0x9802 NSeq TOC1 Trip OP Negative Sequence TOC 1 Trip OP
0x9842 NSeq TOC2 Trip OP Negative Sequence TOC 2 Trip OP
0x9902 NSeq IOC 2 Trp OP Negative Sequence IOC 2 Trip OP
0x99C2 SGnd TOC2 Trip OP Sensitive Ground TOC 2 Trip OP
0x9C02 LE 9 Trip OP Logic Element 9 Trip OP
0x9C42 LE 10 Trip OP Logic Element 10 Trip OP
0x9C82 LE 11 Trip OP Logic Element 11 Trip OP
0x9CC2 LE 12 Trip OP Logic Element 12 Trip OP
0x9D02 LE 13 Trip OP Logic Element 13 Trip OP
0x9D42 LE 14 Trip OP Logic Element 14 Trip OP
0x9D82 LE 15 Trip OP Logic Element 15 Trip OP
0x9DC2 LE 16 Trip OP Logic Element 16 Trip OP
FC134E unsigned 16 bits Fault Report Trigger
0 Off Off
0x8002 Any Trip Any Trip
0x8042 Therm O/L Trip OP Thermal Overload Trip OP
0x804A Therm PhA Trip OP Thermal Phase A Trip OP
0x8052 Therm PhB Trip OP Thermal Phase B Trip OP
0x8062 Therm PhC Trip OP Thermal Phase C Trip OP
0x8082 RTD 1 Trip OP RTD 1 Trip OP
0x80C2 RTD 2 Trip OP RTD 2 Trip OP
0x8102 RTD 3 Trip OP RTD 3 Trip OP
0x8142 RTD 4 Trip OP RTD 4 Trip OP
0x8202 RTD 5 Trip OP RTD 5 Trip OP
0x8242 RTD 6 Trip OP RTD 6 Trip OP
0x8282 RTD 7 Trip OP RTD 7 Trip OP
0x82C2 RTD 8 Trip OP RTD 8 Trip OP
0x8302 RTD 9 Trip OP RTD 9 Trip OP
0x8342 RTD 10 Trip OP RTD 10 Trip OP
0x8382 RTD 11 Trip OP RTD 11 Trip OP
0x83C2 RTD 12 Trip OP RTD 12 Trip OP
0x84C2 LE 1 Trip OP Logic Element 1 Trip OP
0x8502 LE 2 Trip OP Logic Element 2 Trip OP
0x8542 LE 3 Trip OP Logic Element 3 Trip OP
0x8582 LE 4 Trip OP Logic Element 4 Trip OP
0x85C2 LE 5 Trip OP Logic Element 5 Trip OP
0x8602 LE 6 Trip OP Logic Element 6 Trip OP
0x8642 LE 7 Trip OP Logic Element 7 Trip OP
0x8682 LE 8 Trip OP Logic Element 8 Trip OP
0x9002 Ph IOC1 Trip OP Phase IOC 1 Trip OP
0x900A Ph A IOC1 Trip OP Phase A IOC 1 Trip OP
0x9012 Ph B IOC1 Trip OP Phase B IOC 1 Trip OP
0x9022 Ph C IOC1 Trip OP Phase C IOC 1 Trip OP
0x9042 Ntrl IOC1 Trip OP Neutral IOC 1 Trip OP

11-154 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x9082 Gnd IOC1 Trip OP Ground IOC 1 Trip OP
0x90C2 Ph TOC1 Trip OP Phase TOC 1 Trip OP
0x90CA Ph A TOC1 Trip OP Phase A TOC 1 Trip OP
0x90D2 Ph B TOC1 Trip OP Phase B TOC 1 Trip OP
0x90E2 Ph C TOC1 Trip OP Phase C TOC 1 Trip OP
0x9102 Ntrl TOC1 Trip OP Neutral TOC 1 Trip OP
0x9142 Gnd TOC1 Trip OP Ground TOC 1 Trip OP
0x9182 Ph IOC2 Trip OP Phase IOC 2 Trip OP
0x918A Ph A IOC2 Trip OP Phase A IOC 2 Trip OP
0x9192 Ph B IOC2 Trip OP Phase B IOC 2 Trip OP
0x91A2 Ph C IOC2 Trip OP Phase C IOC 2 Trip OP
0x91C2 Ntrl IOC2 Trip OP Neutral IOC 2 Trip OP
0x9202 Gnd IOC2 Trip OP Ground IOC 2 Trip OP
0x9242 Ph TOC2 Trip OP Phase TOC 2 Trip OP
0x924A Ph A TOC2 Trip OP Phase A TOC 2 Trip OP
0x9252 Ph B TOC2 Trip OP Phase B TOC 2 Trip OP
0x9262 Ph C TOC2 Trip OP Phase C TOC 2 Trip OP
0x9282 Ntrl TOC2 Trip OP Neutral TOC 2 Trip OP
0x92C2 Gnd TOC2 Trip OP Ground TOC 2 Trip OP
0x9302 SGnd TOC1 Trip OP Sensitive Ground TOC 1 Trip OP
0x9642 SGnd IOC1 Trip OP Sensitive Ground IOC 1 Trip OP
0x9682 SGnd IOC2 Trip OP Sensitive Ground IOC 2 Trip OP
0x96C2 NSeq IOC Trp OP Negative Sequence IOC Trip OP
0x9702 Pcnt Diff Trip OP Pcnt Diff Trip OP
0x970A Ph Diff A Trip OP Ph Diff A Trip OP
0x9712 Ph Diff B Trip OP Ph Diff B Trip OP
0x9722 Ph Diff C Trip OP Ph Diff C Trip OP
0x9742 RGF1 Trip OP RGF1 Trip OP
0x9782 RGF2 Trip OP RGF2 Trip OP
0x97C2 Inst Diff Trip OP Inst Diff Trip OP
0x9802 NSeq TOC1 Trip OP Negative Sequence TOC 1 Trip OP
0x9842 NSeq TOC2 Trip OP Negative Sequence TOC 2 Trip OP
0x9902 NSeq IOC 2 Trp OP Negative Sequence IOC 2 Trip OP
0x99C2 SGnd TOC2 Trip OP Sensitive Ground TOC 2 Trip OP
0x9C02 LE 9 Trip OP Logic Element 9 Trip OP
0x9C42 LE 10 Trip OP Logic Element 10 Trip OP
0x9C82 LE 11 Trip OP Logic Element 11 Trip OP
0x9CC2 LE 12 Trip OP Logic Element 12 Trip OP
0x9D02 LE 13 Trip OP Logic Element 13 Trip OP
0x9D42 LE 14 Trip OP Logic Element 14 Trip OP
0x9D82 LE 15 Trip OP Logic Element 15 Trip OP
0x9DC2 LE 16 Trip OP Logic Element 16 Trip OP
FC134F unsigned 16 bits Lockout Reset
0 Off Off
0x0001 On On
0x0040 Contact IN 1 On Contact Input 1 On
0x0041 Contact IN 2 On Contact Input 2 On

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-155


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x0042 Contact IN 3 On Contact Input 3 On
0x0043 Contact IN 4 On Contact Input 4 On
0x0044 Contact IN 5 On Contact Input 5 On
0x0045 Contact IN 6 On Contact Input 6 On
0x0046 Contact IN 7 On Contact Input 7 On
0x0047 Contact IN 8 On Contact Input 8 On
0x0048 Contact IN 9 On Contact Input 9 On
0x0049 Contact IN 10 On Contact Input 10 On
0x0060 Contact IN 1 Off Contact Input 1 Off
0x0061 Contact IN 2 Off Contact Input 2 Off
0x0062 Contact IN 3 Off Contact Input 3 Off
0x0063 Contact IN 4 Off Contact Input 4 Off
0x0064 Contact IN 5 Off Contact Input 5 Off
0x0065 Contact IN 6 Off Contact Input 6 Off
0x0066 Contact IN 7 Off Contact Input 7 Off
0x0067 Contact IN 8 Off Contact Input 8 Off
0x0068 Contact IN 9 Off Contact Input 9 Off
0x0069 Contact IN 10 Off Contact Input 10 Off
0x0080 Virtual IN 1 On Virtual Input 1 On
0x0081 Virtual IN 2 On Virtual Input 2 On
0x0082 Virtual IN 3 On Virtual Input 3 On
0x0083 Virtual IN 4 On Virtual Input 4 On
0x0084 Virtual IN 5 On Virtual Input 5 On
0x0085 Virtual IN 6 On Virtual Input 6 On
0x0086 Virtual IN 7 On Virtual Input 7 On
0x0087 Virtual IN 8 On Virtual Input 8 On
0x0088 Virtual IN 9 On Virtual Input 9 On
0x0089 Virtual IN 10 On Virtual Input 10 On
0x008A Virtual IN 11 On Virtual Input 11 On
0x008B Virtual IN 12 On Virtual Input 12 On
0x008C Virtual IN 13 On Virtual Input 13 On
0x008D Virtual IN 14 On Virtual Input 14 On
0x008E Virtual IN 15 On Virtual Input 15 On
0x008F Virtual IN 16 On Virtual Input 16 On
0x0090 Virtual IN 17 On Virtual Input 17 On
0x0091 Virtual IN 18 On Virtual Input 18 On
0x0092 Virtual IN 19 On Virtual Input 19 On
0x0093 Virtual IN 20 On Virtual Input 20 On
0x0094 Virtual IN 21 On Virtual Input 21 On
0x0095 Virtual IN 22 On Virtual Input 22 On
0x0096 Virtual IN 23 On Virtual Input 23 On
0x0097 Virtual IN 24 On Virtual Input 24 On
0x0098 Virtual IN 25 On Virtual Input 25 On
0x0099 Virtual IN 26 On Virtual Input 26 On
0x009A Virtual IN 27 On Virtual Input 27 On
0x009B Virtual IN 28 On Virtual Input 28 On
0x009C Virtual IN 29 On Virtual Input 29 On

11-156 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x009D Virtual IN 30 On Virtual Input 30 On
0x009E Virtual IN 31 On Virtual Input 31 On
0x009F Virtual IN 32 On Virtual Input 32 On
0x00A0 Virtual IN 1 Off Virtual Input 1 Off
0x00A1 Virtual IN 2 Off Virtual Input 2 Off
0x00A2 Virtual IN 3 Off Virtual Input 3 Off
0x00A3 Virtual IN 4 Off Virtual Input 4 Off
0x00A4 Virtual IN 5 Off Virtual Input 5 Off
0x00A5 Virtual IN 6 Off Virtual Input 6 Off
0x00A6 Virtual IN 7 Off Virtual Input 7 Off
0x00A7 Virtual IN 8 Off Virtual Input 8 Off
0x00A8 Virtual IN 9 Off Virtual Input 9 Off
0x00A9 Virtual IN 10 Off Virtual Input 10 Off
0x00AA Virtual IN 11 Off Virtual Input 11 Off
0x00AB Virtual IN 12 Off Virtual Input 12 Off
0x00AC Virtual IN 13 Off Virtual Input 13 Off
0x00AD Virtual IN 14 Off Virtual Input 14 Off
0x00AE Virtual IN 15 Off Virtual Input 15 Off
0x00AF Virtual IN 16 Off Virtual Input 16 Off
0x00B0 Virtual IN 17 Off Virtual Input 17 Off
0x00B1 Virtual IN 18 Off Virtual Input 18 Off
0x00B2 Virtual IN 19 Off Virtual Input 19 Off
0x00B3 Virtual IN 20 Off Virtual Input 20 Off
0x00B4 Virtual IN 21 Off Virtual Input 21 Off
0x00B5 Virtual IN 22 Off Virtual Input 22 Off
0x00B6 Virtual IN 23 Off Virtual Input 23 Off
0x00B7 Virtual IN 24 Off Virtual Input 24 Off
0x00B8 Virtual IN 25 Off Virtual Input 25 Off
0x00B9 Virtual IN 26 Off Virtual Input 26 Off
0x00BA Virtual IN 27 Off Virtual Input 27 Off
0x00BB Virtual IN 28 Off Virtual Input 28 Off
0x00BC Virtual IN 29 Off Virtual Input 29 Off
0x00BD Virtual IN 30 Off Virtual Input 30 Off
0x00BE Virtual IN 31 Off Virtual Input 31 Off
0x00BF Virtual IN 32 Off Virtual Input 32 Off
0xA4C2 LE 1 Alarm OP Logic Element 1 Alarm OP
0xA502 LE 2 Alarm OP Logic Element 2 Alarm OP
0xA542 LE 3 Alarm OP Logic Element 3 Alarm OP
0xA582 LE 4 Alarm OP Logic Element 4 Alarm OP
0xA5C2 LE 5 Alarm OP Logic Element 5 Alarm OP
0xA602 LE 6 Alarm OP Logic Element 6 Alarm OP
0xA642 LE 7 Alarm OP Logic Element 7 Alarm OP
0xA682 LE 8 Alarm OP Logic Element 8 Alarm OP
0xBC02 LE 9 Alarm OP Logic Element 9 Alarm OP
0xBC42 LE 10 Alarm OP Logic Element 10 Alarm OP
0xBC82 LE 11 Alarm OP Logic Element 11 Alarm OP
0xBCC2 LE 12 Alarm OP Logic Element 12 Alarm OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-157


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xBD02 LE 13 Alarm OP Logic Element 13 Alarm OP
0xBD42 LE 14 Alarm OP Logic Element 14 Alarm OP
0xBD82 LE 15 Alarm OP Logic Element 15 Alarm OP
0xBDC2 LE 16 Alarm OP Logic Element 16 Alarm OP
0xC4C2 LE 1 OP Logic Element 1 OP
0xC502 LE 2 OP Logic Element 2 OP
0xC542 LE 3 OP Logic Element 3 OP
0xC582 LE 4 OP Logic Element 4 OP
0xC5C2 LE 5 OP Logic Element 5 OP
0xC602 LE 6 OP Logic Element 6 OP
0xC642 LE 7 OP Logic Element 7 OP
0xC682 LE 8 OP Logic Element 8 OP
0xDC02 LE 9 OP Logic Element 9 OP
0xDC42 LE 10 OP Logic Element 10 OP
0xDC82 LE 11 OP Logic Element 11 OP
0xDCC2 LE 12 OP Logic Element 12 OP
0xDD02 LE 13 OP Logic Element 13 OP
0xDD42 LE 14 OP Logic Element 14 OP
0xDD82 LE 15 OP Logic Element 15 OP
0xDDC2 LE 16 OP Logic Element 16 OP
FC135 unsigned 16 bits Motor Speed During Trip / Motor Speed
During Event
FC136 unsigned 16 bits Motor Speed During Trip / Motor Speed
During Event
0 None None
1 A A
2 B B
FC139 unsigned 16 bits Starter Type
0 None None
4 Wye-Delta Wye-Delta
5 Inverter Inverter
6 Soft Starter Soft Starter
7 Custom Starter Custom Starter
FC140 unsigned 16 bits Interlock Function
0 Disabled Disabled
1 Trip Trip
2 Alarm Alarm
FC141 unsigned 16 bits Timer Type
0 Millisecond Millisecond
1 Second Second
2 Minute Minute
FC142 unsigned 16 bits FlexLogic Bit Field EEETTTTTTTSSSSSS
0x0000 Off Off
0x0001 On On
0x0040 Contact Inputs Contact Inputs
0x0080 Virtual Inputs Virtual Inputs
0x00C0 Virtual Outputs Virtual Outputs

11-158 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x01C0 Remote Inputs Remote Inputs
0x0380 Insert Insert
0x0400 End End
0x0440 NOT NOT
0x0480 XOR XOR
0x04C0 LATCH LATCH
0x0500 OR OR
0x0540 AND AND
0x0580 NOR NOR
0x05C0 NAND NAND
0x0600 TIMER TIMER
0x0640 ASSIGN ASSIGN
0x8000 Trip Trip
0x9901 NSeq IOC 2 Trp PKP Negative Sequence IOC 2 Trip PKP
0x9902 NSeq IOC 2 Trp OP Negative Sequence IOC 2 Trip OP
0x9904 NSeq IOC 2 Trp DPO Negative Sequence IOC 2 Trip DPO
0xA000 Alarm Alarm
0xB881 CTFail 1 Alrm PKP W1 CT Fail Alarm PKP
0xB882 CTFail 1 Alrm OP W1 CT Fail Alarm OP
0xB884 CTFail 1 Alrm DPO W1 CT Fail Alarm DPO
0xB8C1 CTFail 2 Alrm PKP W2 CT Fail Alarm PKP
0xB8C2 CTFail 2 Alrm OP W2 CT Fail Alarm OP
0xB8C4 CTFail 2 Alrm DPO W2 CT Fail Alarm DPO
0xB901 NSeq IOC 2 AlrmPKP Negative Sequence IOC 2 Alarm PKP
0xB902 NSeq IOC 2 Alrm OP Negative Sequence IOC 2 Alarm OP
0xB904 NSeq IOC 2 AlrmDPO Negative Sequence IOC 2 Alarm DPO
0xC000 Control Control
0xD881 CTFail 1 PKP W1 CT Fail PKP
0xD882 CTFail 1 OP W1 CT Fail OP
0xD884 CTFail 1 DPO W1 CT Fail DPO
0xD901 NSeq IOC 2 PKP Negative Sequence IOC 2 PKP
0xD902 NSeq IOC 2 OP Negative Sequence IOC 2 OP
0xD904 NSeq IOC 2 DPO Negative Sequence IOC 2 DPO
0xD8C1 CTFail 2 PKP W2 CT Fail PKP
0xD8C2 CTFail 2 OP W2 CT Fail OP
0xD8C4 CTFail 2 DPO W2 CT Fail DPO
0xF882 CTFail 1 Block W1 CT Fail Block
0xF8C2 CTFail 2 Block W2 CT Fail Block
0xF902 NSeq IOC 2 Block Negative Sequence IOC 2 Block
FC143 unsigned 16 bits Drive Status
0 Drive Unavailable Drive Unavailable
1 Available Auto Available Auto
2 Available Manual Available Manual
3 Available Available
4 Running Running
5 ESD Trip / Stop ESD Trip / Stop
FC144 unsigned 32 bits LED Status - 350

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-159


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


FC144A unsigned 32 bits LED Status - 339
FC144B unsigned 32 bits LED Status - 345
0x00000100 W2 Closed Red W2 Closed Red
0x00000200 W2 Closed Green W2 Closed Green
0x00000300 W2 Closed Amber W2 Closed Amber
0x00000400 W2 Open Red W2 Open Red
0x00000800 W2 Open Green W2 Open Green
0x00000C00 W2 Open Amber W2 Open Amber
0x00001000 W1 Closed Red W1 Closed Red
0x00002000 W1 Closed Green W1 Closed Green
0x00003000 W1 Closed Amber W1 Closed Amber
0x00004000 W1 Open Red W1 Open Red
0x00008000 W1 Open Green W1 Open Green
0x0000C000 W1 Open Amber W1 Open Amber
0x00030000 Maintenance Amber Maintenance Amber
0x000C0000 Pickup Amber Pickup Amber
0x00300000 Alarm Amber Alarm Amber
0x00400000 Trip Red Trip Red
0x01000000 SP Group 2 Red SP Group 2 Red
0x02000000 SP Group 2 Green SP Group 2 Green
0x03000000 SP Group 2 Amber SP Group 2 Amber
0x04000000 SP Group 1 Red SP Group 1 Red
0x08000000 SP Group 1 Green SP Group 1 Green
0x0C000000 SP Group 1 Amber SP Group 1 Amber
0x30000000 Trouble Amber Trouble Amber
0x80000000 In Service Green In Service Green
FC145 unsigned 16 bits Element Status 1
FC146 unsigned 16 bits Element Status 2
FC147 unsigned 16 bits LED Intensity
0 Level 1 Level 1
12 Level 5 Level 5
15 Level 6 Level 6
3 Level 2 Level 2
6 Level 3 Level 3
9 Level 4 Level 4
FC148 unsigned 16 bits Trigger Mode
0 Overwrite Overwrite
1 Protected Protected
FC149 unsigned 16 bits OR / AND Selection
0 OR OR
1 AND AND
2 NOR NOR
3 NAND NAND
4 XOR XOR
5 XNOR XNOR
FC149A unsigned 16 bits AND / LATCH Selection
0 AND AND

11-160 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


1 LATCH LATCH
FC150 unsigned 32 bits IP Address
FC155 unsigned 16 bits Profibus Baud Rate
0x0001 9600 9600
0x0002 19200 19200
0x0004 31250 31250
0x0008 45450 45450
0x0010 93750 93750
0x0020 187500 187500
0x0040 500000 500000
0x0080 1500000 1500000
0x07E2 Auto Detect Auto Detect
FC156 unsigned 16 bits DeviceNet Baud Rate
0 125 kbps 125 kbps
1 250 kbps 250 kbps
2 500 kbps 500 kbps
FC157 unsigned 16 bits LED Colour
0 Off Off
1 Red Red
2 Green Green
3 Orange Orange
FC157A unsigned 16 bits LED Colour (Subset A)
0 None None
1 Red Red
2 Green Green
FC160 unsigned 16 bits Auto/Manual Mode
0 Auto Auto
1 Manual Manual
FC167 unsigned 32 bits Contact/Virtual Input/Output Status
FC168 unsigned 32 bits Contact/Virtual Input/Output Status
FC169 unsigned 16 bits Month
0 Not Set Not Set
1 January January
2 February February
3 March March
4 April April
5 May May
6 June June
7 July July
8 August August
9 September September
10 October October
11 November November
12 December December
FC170 unsigned 16 bits Count of Week
0 Not Set Not Set
1 1st 1st

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-161


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


2 2nd 2nd
3 3rd 3rd
4 4th 4th
5 Last Last
FC171 unsigned 16 bits Weekdays
0 Not Set Not Set
1 SUN SUN
2 MON MON
3 TUE TUE
4 WED WED
5 THU THU
6 FRI FRI
7 SAT SAT
FC172 unsigned 16 bits Auto/Manual Control Stop Mode
0 Always Enabled Always Enabled
1 Follow Ctrl Mode Follow Control Mode
FC173 unsigned 16 bits Wire Selection
0 2W 2W
1 3W 3W
FC174 unsigned 16 bits Source Stop Action
0 Stop Stop
1 Trip Trip
FC175 unsigned 16 bits Test Auto/Manual Mode
0 On On
1 Off Off
2 Unaffected Unaffected
FC176 unsigned 16 bits Auxiliary VT Connection
0 Vab VT Vab VT
1 Vbc VT Vbc VT
2 Vca VT Vca VT
3 Van VT Van VT
4 Vbn VT Vbn VT
5 Vcn VT Vcn VT
FC177 unsigned 16 bits LED Color Invert
0 Green/Red Green/Red
1 Red/Green Red/Green
FC178 unsigned 16 bits Motor Status
FC179 unsigned 32 bits Alarm Status 1
0x00000001 Any Alarm Any Alarm
0x00000002 Therm Level Alarm Thermal Level Alarm
0x00000004 Gnd Fault Alarm Gnd Fault Alarm
0x00000008 Acceleration Alarm Acceleration Alarm
0x00000020 Under Pwr Alarm Under Power Alarm
0x00000040 Reserved Reserved
0x00000080 Reserved Reserved
0x00000100 Mech Jam Alarm Mechanical Jam Alarm
0x00000200 Under Curr Alarm Undercurrent Alarm

11-162 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x00000400 Unbalance Alarm Unbalance Alarm
0x00000800 RTD 1 Alarm RTD 1 Alarm
0x00001000 RTD 2 Alarm RTD 2 Alarm
0x00002000 RTD 3 Alarm RTD 3 Alarm
0x00004000 RTD 4 Alarm RTD 4 Alarm
0x00008000 RTD 5 Alarm RTD 5 Alarm
0x00010000 RTD 6 Alarm RTD 6 Alarm
0x00020000 RTD Trouble Alarm RTD Trouble Alarm
0x00040000 Not Configured Not Configured
0x00080000 LE 1 Alarm Logic Element 1 Alarm
0x00100000 LE 2 Alarm Logic Element 2 Alarm
0x00200000 LE 3 Alarm Logic Element 3 Alarm
0x00400000 LE 4 Alarm Logic Element 4 Alarm
0x00800000 LE 5 Alarm Logic Element 5 Alarm
0x01000000 LE 6 Alarm Logic Element 6 Alarm
0x02000000 LE 7 Alarm Logic Element 7 Alarm
0x04000000 LE 8 Alarm Logic Element 8 Alarm
0x08000000 RTD 7 Alarm RTD 7 Alarm
0x10000000 RTD 8 Alarm RTD 8 Alarm
0x20000000 RTD 9 Alarm RTD 9 Alarm
0x40000000 RTD 10 Alarm RTD 10 Alarm
0x80000000 RTD 11 Alarm RTD 11 Alarm
FC180 unsigned 32 bits Alarm Status 2
0x00000001 RTD 12 Alarm RTD 12 Alarm
0x00000002 Reserved Reserved
0x00000004 Reserved Reserved
0x00000008 Reserved Reserved
0x00000010 Reserved Reserved
0x00000020 Reserved Reserved
0x00000040 Motor Run Hrs Motor Running Hours
0x00000080 I^2 Counter Alarm I^2 Counter Alarm
0x00000100 Welded Contactor Welded Contactor
0x00000800 Reserved Reserved
0x00001000 Load Increase Alrm Load Increase Alarm
0x00002000 Reserved Reserved
0x00004000 Reserved Reserved
0x00008000 High Ambient Temp High Ambient Temperature Alarm
0x00010000 Low Ambient Temp Low Ambient Temperature Alarm
0x00020000 Self Test Alarm Self Test Alarm
0x00040000 Comm Fail Alarm Comm Fail Alarm
0x00080000 BKRTrip Cntr Alarm Breaker Trip Counter Alarm
0x00100000 Rly1 74 Alarm Relay 1 74 Alarm
0x00200000 Rly2 74 Alarm Relay 2 74 Alarm
0x00400000 BKR Fail Alarm Breaker Fail Alarm
0x00800000 BKR Status Failure Breaker Status Failure
0x01000000 Reserved Reserved
0x02000000 CLP Alarm Cold Load PKP Alarm

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-163


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x04000000 Reserved Reserved
0x08000000 BKR2 Status Fail Breaker 2 Status Failure
0x10000000 Reserved Reserved
0x20000000 BKR2 Fail Alrm Breaker 2 Failure Alarm
0x80000000 Ph Revrsl Alarm Phase Reversal Alarm
FC181 unsigned 32 bits Alarm Status 3
0x00000001 Ph IOC1 Alarm Phase IOC 1 Alarm
0x00000002 Ntrl IOC1 Alarm Neutral IOC 1 Alarm
0x00000004 Gnd IOC1 Alarm Ground IOC 1 Alarm
0x00000008 Ph TOC1 Alarm Phase TOC 1 Alarm
0x00000010 Ntrl TOC1 Alarm Neutral TOC1 Alarm
0x00000020 Gnd TOC1 Alarm Sensitive Ground TOC 1 Alarm
0x00000040 Ph IOC2 Alarm Phase IOC 2 Alarm
0x00000080 Ntrl IOC2 Alarm Neutral IOC 2 Alarm
0x00000100 Gnd IOC2 Alarm Ground IOC 2 Alarm
0x00000200 Ph TOC2 Alrm Phase TOC 2 Alarm
0x00000400 Ntrl TOC2 Alarm Neutral TOC 2 Alarm
0x00000800 Gnd TOC2 Alrm Sensitive Ground TOC 2 Alarm
0x00001000 SGnd TOC1 Alarm Sensitive Ground TOC 1 Alarm
0x00002000 Ntrl Dir Rev Alm Neutral Directional Alarm
0x00008000 NSeq OV Alarm Negative Sequence OV Alarm
0x00010000 Ntrl OV Alarm Ntrl OV Alarm
0x00020000 Phase OV Alarm Phase OV Alarm
0x00040000 Phase UV Alarm Phase UV Alarm
0x00080000 Aux OV Alarm Auxiliary OV Alarm
0x00100000 Aux UV Alarm Auxiliary UV Alarm
0x00200000 UnderFreq1 Alarm Underfrequency 1 Alarm
0x00400000 UnderFreq2 Alarm Underfrequency 2 Alarm
0x00800000 OverFreq1 Alrm Overfrequency 1 Alarm
0x01000000 OverFreq2 Alrm Overfrequency 2 Alarm
0x02000000 SGnd IOC1 Alarm Sensitive Ground IOC 1 Alarm
0x04000000 SGnd IOC2 Alarm Sensitive Ground IOC 2 Alarm
0x08000000 Nseq IOC Alarm Negative Sequence IOC Alarm
0x10000000 Diff 87P Alarm Diff 87P Alarm
0x20000000 Diff 87REF 1 Alarm Diff 87REF 1 Alarm
0x40000000 Diff 87REF 2 Alarm Diff 87REF 2 Alarm
0x80000000 Inst 50/87P Alarm Inst 50/87P Alarm
FC182 unsigned 32 bits Alarm Status 4
0x00000001 NSeq TOC1 Alarm Negative Sequence TOC 1 Alarm
0x00000002 NSeq TOC2 Alarm Negative Sequence TOC 2 Alarm
0x00000004 Ph OV2 Alarm Phase OV 2 Alarm
0x00000008 Ph UV2 Alarm Phase UV 2 Alarm
0x00000010 Short Circuit Alrm Short Circuit Alarm
0x00000020 SPD2 S/C Alarm SPD2 S/C Alarm
0x00000040 SPD2 U/C Alarm SPD2 U/C Alarm
0x00000080 SGnd TOC2 Alarm Sensitive Ground TOC 2 Alarm
0x00000100 Reserved Reserved

11-164 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x00000200 Reserved Reserved
0x00000400 Reserved Reserved
0x00000800 Reserved Reserved
0x00001000 Reserved Reserved
0x00002000 Reserved Reserved
0x00004000 Reserved Reserved
0x00008000 Reserved Reserved
0x00010000 LE 9 Alarm Logic Element 9 Alarm
0x00020000 LE 10 Alarm Logic Element 10 Alarm
0x00040000 LE 11 Alarm Logic Element 11 Alarm
0x00080000 LE 12 Alarm Logic Element 12 Alarm
0x00100000 LE 13 Alarm Logic Element 13 Alarm
0x00200000 LE 14 Alarm Logic Element 14 Alarm
0x00400000 LE 15 Alarm Logic Element 15 Alarm
0x00800000 LE 16 Alarm Logic Element 16 Alarm
0x01000000 Reserved Reserved
0x02000000 Reserved Reserved
0x04000000 Reserved Reserved
0x08000000 Reserved Reserved
0x10000000 Reserved Reserved
0x20000000 Reserved Reserved
0x40000000 Reserved Reserved
0x80000000 Reserved Reserved
FC183 unsigned 32 bits Trip Status 1
0x00000001 Any Trip Any Trip
0x00000002 Therm O/L Trip Thermal O/L Trip
0x00000004 Gnd Fault Trip Gnd Fault Trip
0x00000008 Acceleration Trip Acceleration Trip
0x00000020 Under Pwr Trip Under Power Trip
0x00000040 Single Phase Trip Single Phase Trip
0x00000080 Reserved Reserved
0x00000100 Mech Jam Trip Mechanical Jam Trip
0x00000200 Under Curr Trip Undercurrent Trip
0x00000400 Unbalance Trip Unbalance Trip
0x00000800 RTD 1 Trip RTD 1 Trip
0x00001000 RTD 2 Trip RTD 2 Trip
0x00002000 RTD 3 Trip RTD 3 Trip
0x00004000 RTD 4 Trip RTD 4 Trip
0x00008000 RTD 5 Trip RTD 5 Trip
0x00010000 RTD 6 Trip RTD 6 Trip
0x00020000 Comm Fail Trip Comm Fail Trip
0x00040000 Relay Not Config. Relay Not Configured
0x00080000 LE 1 Trip Logic Element 1 Trip
0x00100000 LE 2 Trip Logic Element 2 Trip
0x00200000 LE 3 Trip Logic Element 3 Trip
0x00400000 LE 4 Trip Logic Element 4 Trip
0x00800000 LE 5 Trip Logic Element 5 Trip

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-165


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x01000000 LE 6 Trip Logic Element 6 Trip
0x02000000 LE 7 Trip Logic Element 7 Trip
0x04000000 LE 8 Trip Logic Element 8 Trip
0x08000000 RTD 7 Trip RTD 7 Trip
0x10000000 RTD 8 Trip RTD 8 Trip
0x20000000 RTD 9 Trip RTD 9 Trip
0x40000000 RTD 10 Trip RTD 10 Trip
0x80000000 RTD 11 Trip RTD 11 Trip
FC184 unsigned 32 bits Trip Status 2
0x00000001 RTD 12 Trip RTD 12 Trip
0x00000002 Reserved Reserved
0x00000004 Reserved Reserved
0x00000008 Reserved Reserved
0x00000010 Reserved Reserved
0x00000020 Reserved Reserved
0x00000040 Reserved Internal Temperature Trip
0x00000080 Self Test Trip Self Test Trip
0x00000100 Reserved Reserved
0x00000200 Reserved Reserved
0x00000400 Reserved Reserved
0x00000800 Reserved Reserved
0x00001000 Reserved Reserved
0x00002000 Reserved Reserved
0x00004000 Reserved Reserved
0x00008000 Reserved Reserved
0x00010000 Reserved Reserved
0x00020000 Reserved Reserved
0x00040000 Reserved Reserved
0x00080000 BKRTrip Cntr Trip Breaker Trip Counter Trip
0x00100000 Rly1 74 Trip Relay 1 74 Trip
0x00200000 Rly2 74 Trip Relay 2 74 Trip
0x00400000 BKR Failure Breaker Failure
0x00800000 Reserved Reserved
0x01000000 Reserved Reserved
0x02000000 Reserved Reserved
0x04000000 Reserved Reserved
0x08000000 Reserved Reserved
0x10000000 Reserved Reserved
0x20000000 BKR 2 Failure Breaker 2 Failure
0x80000000 Ph Revrsl Trip Phase Reversal Trip
FC185 unsigned 32 bits Trip Status 3
0x00000001 Ph IOC1 Trip Phase IOC 1 Trip
0x00000002 Ntrl IOC1 Trip Neutral IOC 1 Trip
0x00000004 Gnd IOC1 Trip Ground IOC 1 Trip
0x00000008 Ph TOC1 Trip Phase TOC 1 Trip
0x00000010 Ntrl TOC1 Trip Neutral TOC1 Trip
0x00000020 Gnd TOC1 Trip Sensitive Ground TOC 1 Trip

11-166 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x00000040 Ph IOC2 Trip Phase IOC 2 Trip
0x00000080 Ntrl IOC2 Trip Neutral IOC 2 Trip
0x00000100 Gnd IOC2 Trip Ground IOC 2 Trip
0x00000200 Ph TOC2 Trip Phase TOC 2 Trip
0x00000400 Ntrl TOC2 Trip Neutral TOC 2 Trip
0x00000800 Gnd TOC2 Trip Sensitive Ground TOC 2 Trip
0x00001000 SGnd TOC1 Trip Sensitive Ground TOC 1 Trip
0x00002000 Reserved Reserved
0x00004000 Reserved Reserved
0x00008000 NSeq OV Trip Negative Sequence OV Trip
0x00010000 Ntrl OV Trip Ntrl OV Trip
0x00020000 Phase OV Trip Phase OV Trip
0x00040000 Phase UV Trip Phase UV Trip
0x00080000 Aux OV Trip Auxiliary OV Trip
0x00100000 Aux UV Trip Auxiliary UV Trip
0x00200000 UnderFreq1 Trip Underfrequency 1 Trip
0x00400000 UnderFreq2 Trip Underfrequency 2 Trip
0x00800000 OVERFREQ1 TRIP Overfrequency 1 Trip
0x01000000 OVERFREQ2 TRIP Overfrequency 2 Trip
0x02000000 SGnd IOC1 Trip Sensitive Ground IOC 1 Trip
0x04000000 SGnd IOC2 Trip Sensitive Ground IOC 2 Trip
0x08000000 Nseq IOC Trip Negative Sequence IOC Trip
0x10000000 Diff 87P Trip Diff 87P Trip
0x20000000 Diff 87REF 1 Trip Diff 87REF 1 Trip
0x40000000 Diff 87REF 2 Trip Diff 87REF 2 Trip
0x80000000 Inst 50/87P Trip Inst 50/87P Trip
FC186 unsigned 32 bits Trip Status 4
0x00000001 NSeq TOC1 Trip Negative Sequence TOC 1 Trip
0x00000002 NSeq TOC2 Trip Negative Sequence TOC 2 Trip
0x00000004 Phase OV 2 Trip Phase OV 2 Trip
0x00000008 Phase UV 2 Trip Phase UV 2 Trip
0x00000010 Short Circuit Trip Short Circuit Trip
0x00000020 SPD2 S/C Trip SPD2 S/C Trip
0x00000040 SPD2 U/C Trip SPD2 U/C Trip
0x00000080 SGnd TOC2 Trip Sensitive Ground TOC 2 Trip
0x00000100 Reserved Reserved
0x00000200 Reserved Reserved
0x00000400 Reserved Reserved
0x00000800 Reserved Reserved
0x00001000 Reserved Reserved
0x00002000 Reserved Reserved
0x00004000 Reserved Reserved
0x00008000 Reserved Reserved
0x00010000 LE 9 Trip Logic Element 9 Trip
0x00020000 LE 10 Trip Logic Element 10 Trip
0x00040000 LE 11 Trip Logic Element 11 Trip
0x00080000 LE 12 Trip Logic Element 12 Trip

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-167


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x00100000 LE 13 Trip Logic Element 13 Trip
0x00200000 LE 14 Trip Logic Element 14 Trip
0x00400000 LE 15 Trip Logic Element 15 Trip
0x00800000 LE 16 Trip Logic Element 16 Trip
0x01000000 Reserved Reserved
0x02000000 Reserved Reserved
0x04000000 Reserved Reserved
0x08000000 Reserved Reserved
0x10000000 Reserved Reserved
0x20000000 Reserved Reserved
0x40000000 Reserved Reserved
0x80000000 Reserved Reserved
FC187 unsigned 32 bits Message Status 1
FC188 unsigned 32 bits Message Status 2
FC189 unsigned 32 bits Message Status 3
FC190 unsigned 32 bits Message Status 4
FC191 unsigned 32 bits Ctrl Element Status 1
FC192 unsigned 32 bits Ctrl Element Status 2
FC193 unsigned 32 bits Ctrl Status 3
FC194 unsigned 32 bits Ctrl Status 4
FC195 unsigned 16 bits Command Status
0 Normal Normal
1 Gain Forced to X1 Gain Forced to X1
FC196 unsigned 16 bits Digital Alarm
0 Active Low Active Low
1 Active High Active High
FC197 unsigned 16 bits Breaker Counter Alarm
0 Disabled Disabled
1 Alarm Alarm
2 Latched Alarm Latched Alarm
3 Trip Trip
FC198 unsigned 16 bits Output Relay Operation
FC199 unsigned 16 bits Output Relay Type
0 Self-Reset Self-Reset
1 Latched Latched
FC200 unsigned 32 bits Block Status 1
FC201 unsigned 32 bits Block Status 2
FC202 unsigned 32 bits Block Status 3
FC203 unsigned 32 bits Block Status 4
FC204 unsigned 16 bits Contact Input FlexLogic Bit Field Values
0x0000 Disabled Disabled
0x0040 Contact Input 1 Contact Input 1
0x0041 Contact Input 2 Contact Input 2
0x0042 Contact Input 3 Contact Input 3
0x0043 Contact Input 4 Contact Input 4
0x0044 Contact Input 5 Contact Input 5
0x0045 Contact Input 6 Contact Input 6

11-168 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x0046 Contact Input 7 Contact Input 7
0x0047 Contact Input 8 Contact Input 8
0x0048 Contact Input 9 Contact Input 9
0x0049 Contact Input 10 Contact Input 10
FC204A unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset A)
0x0000 Disabled Disabled
0x0040 Contact Input 1 Contact Input 1
FC204B unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset B)
0x0000 Disabled Disabled
0x0044 Contact Input 5 Contact Input 5
0x0045 Contact Input 6 Contact Input 6
0x0046 Contact Input 7 Contact Input 7
0x0047 Contact Input 8 Contact Input 8
0x0048 Contact Input 9 Contact Input 9
0x0049 Contact Input 10 Contact Input 10
FC204C unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset C)
0x0000 Disabled Disabled
0x0041 Contact Input 2 Contact Input 2
FC204D unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset D)
0x0000 Disabled Disabled
0x0042 Contact Input 3 W2 Breaker 52a (CI#3)
FC204E unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset E)
0x0000 Disabled Disabled
0x0044 Contact Input 5 Contact Input 5
0x0045 Contact Input 6 Contact Input 6
0x0046 Contact Input 7 Contact Input 7
0x0047 Contact Input 8 Contact Input 8
0x0048 Contact Input 9 Contact Input 9
0x0049 Contact Input 10 Contact Input 10
FC204F unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset F)
0x0000 Disabled Disabled
0x0043 Contact Input 4 W2 Breaker 52b (CI#4)
FC205 unsigned 16 bits Element Type 1
0 Disabled Disabled
1 Alarm Alarm
2 Latched Alarm Latched Alarm
3 Trip Trip
4 Control Control
FC206 unsigned 16 bits Element Type 2
0 Disabled Disabled
1 Alarm Alarm
2 Latched Alarm Latched Alarm
FC207 unsigned 16 bits Element Type 3

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-169


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0 Disabled Disabled
1 Alarm Alarm
2 Latched Alarm Latched Alarm
3 Control Control
FC208 unsigned 16 bits Relay Operation (Failsafe
0 Failsafe Failsafe
1 Non-Failsafe Non-Failsafe
FC212 unsigned 16 bits LCD Test Paint Color
0 None None
1 Red Red
2 Green Green
3 Blue Blue
FC214 unsigned 16 bits MAC Address
FC215 unsigned 32 bits GOOSE Receive Status
FC216 unsigned 16 bits Received GOOSE Message Formatting
0x0000 { {
0x0001 } }
0x0002 Bool Bool
0x0003 Byte Byte
0x0004 Ubyte Ubyte
0x0005 Short Short
0x0006 Ushort Ushort
0x0007 Long Long
0x0008 Ulong Ulong
0x0009 Int64 Int64
0x000A Uint64 Uint64
0x000B Float Float
0x000C Double Double
0x000D Btime4 Btime4
0x000E Btime6 Btime6
0x000F Utctime Utctime
0x0010 Bcd Bcd
0x0011 Vstring Vstring
0x0012 Ostring Ostring
0x0013 Ovstring Ovstring
0x0014 Bstring Bstring
0x0015 Bvstring Bvstring
0x00FF Row Row
FC217 unsigned 16 bits Remote Input Item Source
FC218 unsigned 16 bits Remote Input Item Mask
FC219 unsigned 32 bits GOOSE Source
0x0000 Disabled Disabled
0x0001 1 1
0x0002 2 2
0x0004 3 3
0x0008 4 4
0x0010 5 5

11-170 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


0x0020 6 6
0x0040 7 7
0x0080 8 8
FC220 unsigned 16 bits Remote Input Default State
0 On On
1 Off Off
2 Latest/On Latest/On
3 Latest/Off Latest/Off
FC221 unsigned 16 bits IEC103 ASDU Identification Type
3 3 3
9 9 9
FC222 unsigned 16 bits GOOSE Type
0 Simplified Simplified
1 Advanced Advanced
FC225 unsigned 16 bits Security Audit Trail Change Method
0 Unknown Unknown
1 USB USB
2 COM1 COM1
3 Ethernet Ethernet
4 KeyPad KeyPad
FC226 unsigned 16 bits Security Audit Trail Event Type
0 Unknown Unknown
1 Setpoint Change Setpoint Change
2 Firmware File Firmware File
3 Factory Reload Factory Reload
4 Setpoint File Setpoint File
FC230 unsigned 16 bits Ethernet Connection Type
0 Copper Copper
1 Fiber Fiber
FC235 unsigned 16 bits Switching Device
0 BKR Breaker
1 Contactor Contactor
FC236 unsigned 16 bits Thermal O/L Curve
FC240 unsigned 16 bits Self Test Error
0 None None
1 Order Code Error Order Code Error
2 RTC Error RTC Error
4 Cal Error Cal Error
8 EEPROM Error EEPROM Error
16 System Health System Health
17 PSU Serial# Blank PSU Serial# Blank
18 INP Serial# Blank INP Serial# Blank
19 ANLG Serial# Blank ANLG Serial# Blank
20 MAG Serial# Blank MAG Serial# Blank
21 COMM Serial# Blank COMM Serial# Blank
22 CCP Serial# Blank CCP Serial# Blank
23 CPU Serial# Blank CPU Serial# Blank

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-171


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


24 PSU Serial# Inval PSU Serial# Invalid
25 INP Serial# Inval INP Serial# Invalid
26 ANLG Serial# Inval ANLG Serial# Invalid
27 MAG Serial# Inval MAG Serial# Invalid
28 COMM Serial# Inval COMM Serial# Invalid
29 CCP Serial# Inval CCP Serial# Invalid
30 CPU Serial# Inval CPU Serial# Invalid
32 3.3V Error 3.3V Error
64 Analog V Error Analog V Error
128 DPRAM Checksum DPRAM Checksum
256 DPRAM Heart Beat DPRAM Heart Beat
512 COMM Error COMM Error
513 DAUGHTER Error DAUGHTER Error
514 COMM HW Rev Error COMM HW Revision Error
1024 Link Error Link Error
2048 Traffic Error Traffic Error
4096 Internal Temp Internal Temp
FC401 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 None None
FC402 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 None None
FC403 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 None None
FC404 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 Off Off
1 On On
FC405 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 100 Ohm Pt 100 Ohm Platinum
1 120 Ohm Ni 120 Ohm Nickel
2 100 Ohm Ni 100 Ohm Nickel
FC406 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 Off Off
1 On On
FC407 unsigned 16 bits PC Program Reserved for Output Relay
Bits (Do Not Use)
0 Disabled Disabled
3 3 3
4 4 4
5 5 5
6 6 6
7 7 7
FC408 unsigned 16 bits Inrush Function
0 Disabled Disabled

11-172 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


1 2nd harm Block 2nd harmonic Block
FC409 unsigned 16 bits Inhibit Mode
0 Per Phase Per Phase
1 2-out-of-3 2-out-of-3
2 Average Average
3 1-out-of-3 1-out-of-3
FC410 unsigned 16 bits Overexcitation Function
0 Disabled Disabled
1 5th harm 5th harmonic
FC411 unsigned 16 bits Internal Compensation
0 Internal(software) Internal(software)
1 External(with CTs) External(with CTs)
FC412 unsigned 16 bits Winding Connection
0 Wye Wye
1 Delta Delta
2 Zig-Zag Zig-Zag
FC413 unsigned 16 bits Grounding Connection
0 Not Within zone Not Within zone
1 Within zone Within zone
FC415 unsigned 16 bits SR345 CT Type
0 1 A Secondary 1 A Secondary
1 5 A Secondary 5 A Secondary
FC418 unsigned 16 bits CT Inputs
0 CT (W1) CT (W1)
1 CT (W2) CT (W2)
FC419 unsigned 16 bits XFMR Type
0 Y/y0\2 Y/y0º
1 Y/y180\2 Y/y180º
2 Y/d30\2 Y/d30º
3 Y/d150\2 Y/d150º
4 Y/d210\2 Y/d210º
5 Y/d330\2 Y/d330º
6 Y/z30\2 Y/z30º
7 Y/z150\2 Y/z150º
8 Y/z210\2 Y/z210º
9 Y/z330\2 Y/z330º
10 D/d0\2 D/d0º
11 D/d60\2 D/d60º
12 D/d120\2 D/d120º
13 D/d180\2 D/d180º
14 D/d240\2 D/d240º
15 D/d300\2 D/d300º
16 D/y30\2 D/y30º
17 D/y150\2 D/y150º
18 D/y210\2 D/y210º
19 D/y330\2 D/y330º
20 D/z0\2 D/z0º

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-173


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


21 D/z60\2 D/z60º
22 D/z120\2 D/z120º
23 D/z180\2 D/z180º
24 D/z240\2 D/z240º
25 D/z300\2 D/z300º
FC420 unsigned 16 bits Modbus File Transfer State
0 Idle Idle
1 Write Write
2 Read Read
3 File Error File Error
4 File OK File OK
5 Start Start
6 Ready Ready
7 File Over File Over
FC421 unsigned 16 bits Redundancy type
FC422 unsigned 16 bits Redundancy Port
FC423 unsigned 16 bits Redundancy State
FC424 unsigned 16 bits Dead Condition
FC425 unsigned 16 bits Epoch type
FC426 unsigned 16 bits RSTP State
FC427 unsigned 16 bits WGF Curve Selection
0 Inverse Inverse
4 Definite Time Definite Time
8 Flex Curve A Flex Curve A
9 Flex Curve B Flex Curve B
FC428 unsigned 16 bits Fault Recorder Type
0 TOC A TOC A
1 TOC B TOC B
2 TOC C TOC C
FC429 unsigned 16 bits Transient Sampling Rate
0 4 4
1 8 8
2 16 16
3 32 32
FC430 unsigned 16 bits Power Unit
0 Kw Kw
1 Mw Mw
FC431 unsigned 16 bits Demand Measurement Type
0 Blk Interval Blk Interval
1 Exponential Exponential
2 Rolling Dmd Rolling Dmd
FC432 unsigned 16 bits Demand Time
0 5 min 5 min
1 10 min 10 min
2 15 min 15 min
3 20 min 20 min
4 30 min 30 min

11-174 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES

Code Type Definition Long Definition


FC433 unsigned 16 bits BKR Alarm Counter
0 Detection Detection
1 Monitoring Monitoring
FC434 unsigned 16 bits 61850 NV Status
0 Unknown Unknown
1 Header Error Header Error
2 Parse Error Parse Error
3 Passed to Validated Passed to Validated
4 Empty Empty
FC435 unsigned 16 bits Volts Per Herz Voltage Mode
FC436 unsigned 16 bits Volts Per Herz Curves
None

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-175


345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES

11-176 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


GE
Grid Solutions

3 Series Protective Relay Platform

Chapter 12: 350 MODBUS memory


map and Format Codes

350 MODBUS memory map and Format Codes

The 339, 345, and 350 relays have different MODBUS maps and Format Codes. Make sure
NOTE:

you are looking at the chapter corresponding to your relay model.


NOTE

The Cause of Last trip register (MODBUS Address 30186) returns a combined value of
NOTE:

Pickup And Operate.


NOTE
For example, for a Phase TOC 1 Trip:
0x90C1 Ph TOC1 Trip PKP
0x90C2 Ph TOC1 Trip OP
Upon Phase TOC 1 Trip, the value read from 30186 Cause of Last Trip register is: 0x90C3

350 MODBUS memory map

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
ACTUAL VALUES
PRODUCT INFORMATION
30001 0x0 Product Device Code 0 1 1 --- F22 L0 1
30002 0x1 Hardware Revision 0 26 1 --- F15 1 1
30003 0x2 Firmware Version 0 0xFFFF 1 --- F3 231 1
30006 0x5 Boot Version 0 0xFFFF 1 --- F3 100 1
30008 0x7 Serial Number 0 6 1 --- F22 L0MA08000 6
001
30014 0xD Order Code 0 16 1 --- F22 350- 16
EP5G5HSSN
NSNDN
30030 0x1D MAC Address 0 0xFFFF 1 --- FC214 0 3
30035 0x22 Comms HW Version 0 26 1 --- F15 0 1
30037 0x24 Build Date 0 6 1 --- F22 Unknown 6
30043 0x2A Build Time 0 4 1 --- F22 Unknown 4
30051 0x32 Comm Build Date 0 6 1 --- F22 Unknown 6

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-1


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30057 0x38 Comm Build Time 0 4 1 --- F22 Unknown 4
30061 0x3C Comm Revision 0 0xFFFF 1 --- F3 231 1
30063 0x3E Comm Boot Code Revision 0 0xFFFF 1 --- F3 200 1
30068 0x43 FPGA Revision 0 0xFFFF 1 --- F3 0 1
30135 0x86 Main Boot Code Date 0 6 1 --- F22 Unknown 6
30141 0x8C Main Boot Code Time 0 4 1 --- F22 Unknown 4
30145 0x90 Comms Boot Code Date 0 6 1 --- F22 Unknown 6
30151 0x96 Comms Boot Code Time 0 4 1 --- F22 Unknown 4
LAST TRIP DATA
30186 0xB9 Cause of Last Trip 0 0xFFFF 1 --- FC134 0 1
REAL-TIME CLOCK
30223 0xDE Weekday 0 7 1 --- None 0 1
30224 0xDF Current Date 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
9
30226 0xE1 Current Time 0 0x173BEA5F 0 --- F19 0 2
30228 0xE3 Daylight Savings Active 0 1 1 --- FC126 0 1
TRIP COUNTERS
30230 0xE5 Total Number of Trips 0 10000 1 --- F1 0 1
INPUTS / OUTPUTS
30285 0x11C Contact Input 32-1 (Bit Field) 0 0xFFFFFFFF 1 --- FC167 0 2
30288 0x11F Virtual Input 32-1 (Bit Field) 0 0xFFFFFFFF 1 --- FC167 0 2
30290 0x121 Virtual Output 32-1 (Bit Field) 0 0xFFFFFFFF 1 --- FC167 0 2
30296 0x127 Remote Input 32-1 (Bit Field) 0 0xFFFFFFFF 1 --- FC167 0 2
30298 0x129 Contact Output 32-1 (Bit 0 0xFFFFFFFF 1 --- FC167 0 2
Field)
30300 0x12B Remote Output 32-1 (Bit 0 0xFFFFFFFF 1 --- FC167 0 2
Field)
CURRENT METERING
30324 0x143 Sensitive Ground Current 0 0xFFFFFFFF 1 A F11 0 2
30326 0x145 Neutral Current 0 100000 1 A F10 0 2
30328 0x147 Phase A Current 0 1200000 1 A F10 0 2
30330 0x149 Phase B Current 0 1200000 1 A F10 0 2
30332 0x14B Phase C Current 0 1200000 1 A F10 0 2
30334 0x14D Average Phase Current 0 1200000 1 A F10 0 2
30338 0x151 Ground Current 0 1200000 1 A F10 0 2
SECOND HARMONIC
31743 0x6CE Ph A Current 2nd Hrmc 0 1000 1 % F2 0 1
31744 0x6CF Ph B Current 2nd Hrmc 0 1000 1 % F2 0 1
31745 0x6D0 Ph C Current 2nd Hrmc 0 1000 1 % F2 0 1
PHASE ANGLES
30343 0x156 Ia Angle 0 359 1 ° F1 0 1
30344 0x157 Ib Angle 0 359 1 ° F1 0 1
30345 0x158 Ic Angle 0 359 1 ° F1 0 1
30346 0x159 Van Angle 0 359 1 ° F1 0 1
30347 0x15A Vbn Angle 0 359 1 ° F1 0 1
30348 0x15B Vcn Angle 0 359 1 ° F1 0 1
30349 0x15C Ground Current Angle 0 359 1 ° F1 0 1

12-2 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30350 0x15D Neutral Current Angle 0 359 1 ° F1 0 1
30351 0x15E Neutral Voltage Angle 0 359 1 °Lag F1 0 1
30352 0x15F Vaux Angle 0 359 1 ° F1 0 1
30353 0x160 Vab Angle 0 359 1 ° F1 0 1
30354 0x161 Vbc Angle 0 359 1 ° F1 0 1
30355 0x162 Vca Angle 0 359 1 ° F1 0 1
SYNCROCHECK
30368 0x16F Frequency 2000 8000 1 Hz F3 2000 1
30369 0x170 Frequency 2000 8000 1 Hz F3 2000 1
POWER & ENERGY METERING
30384 0x17F Power Factor -99 100 1 --- F21 0 1
30385 0x180 Real Power -1000000000 1000000000 1 kW F13 0 2
30389 0x184 Reactive Power -1000000000 1000000000 1 kvar F13 0 2
30392 0x187 MWh Consumption 0 999999999 1 MWh F17 0 2
30394 0x189 Mvarh Consumption 0 999999999 1 Mvarh F17 0 2
30396 0x18B Mvarh Generation 0 999999999 1 Mvarh F17 0 2
30398 0x18D Apparent Power 0 1000000000 1 kVA F10 0 2
30400 0x18F MWh Generation 0 999999999 1 MWh F17 0 2
30402 0x191 Real Power MW -1000000000 1000000000 1 MW F13 0 2
30404 0x193 Reactive Power MW -1000000000 1000000000 1 Mvar F13 0 2
TEMPERATURE
30435 0x1B2 Ambient Temperature -50 250 1 ° F4 25 1
30437 0x1B4 Event Phase A Thermal 0 1500 1 % F2 0 1
Capacity
30438 0x1B5 Event Phase B Thermal 0 1500 1 % F2 0 1
Capacity
30439 0x1B6 Event Phase C Thermal 0 1500 1 % F2 0 1
Capacity
LED STATUS
30505 0x1F8 LED Status 0 0xFFFFFFFF 1 --- FC144 0 2
USER MAP ACTUAL VALUES
30524 0x20B User Map Value 1 0 0xFFFF 1 --- F1 0 1
30525 0x20C User Map Value 2 0 0xFFFF 1 --- F1 0 1
30526 0x20D User Map Value 3 0 0xFFFF 1 --- F1 0 1
30527 0x20E User Map Value 4 0 0xFFFF 1 --- F1 0 1
30528 0x20F User Map Value 5 0 0xFFFF 1 --- F1 0 1
30529 0x210 User Map Value 6 0 0xFFFF 1 --- F1 0 1
30530 0x211 User Map Value 7 0 0xFFFF 1 --- F1 0 1
30531 0x212 User Map Value 8 0 0xFFFF 1 --- F1 0 1
30532 0x213 User Map Value 9 0 0xFFFF 1 --- F1 0 1
30533 0x214 User Map Value 10 0 0xFFFF 1 --- F1 0 1
30534 0x215 User Map Value 11 0 0xFFFF 1 --- F1 0 1
30535 0x216 User Map Value 12 0 0xFFFF 1 --- F1 0 1
30536 0x217 User Map Value 13 0 0xFFFF 1 --- F1 0 1
30537 0x218 User Map Value 14 0 0xFFFF 1 --- F1 0 1
30538 0x219 User Map Value 15 0 0xFFFF 1 --- F1 0 1
30539 0x21A User Map Value 16 0 0xFFFF 1 --- F1 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-3


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30540 0x21B User Map Value 17 0 0xFFFF 1 --- F1 0 1
30541 0x21C User Map Value 18 0 0xFFFF 1 --- F1 0 1
30542 0x21D User Map Value 19 0 0xFFFF 1 --- F1 0 1
30543 0x21E User Map Value 20 0 0xFFFF 1 --- F1 0 1
30544 0x21F User Map Value 21 0 0xFFFF 1 --- F1 0 1
30545 0x220 User Map Value 22 0 0xFFFF 1 --- F1 0 1
30546 0x221 User Map Value 23 0 0xFFFF 1 --- F1 0 1
30547 0x222 User Map Value 24 0 0xFFFF 1 --- F1 0 1
30548 0x223 User Map Value 25 0 0xFFFF 1 --- F1 0 1
30549 0x224 User Map Value 26 0 0xFFFF 1 --- F1 0 1
30550 0x225 User Map Value 27 0 0xFFFF 1 --- F1 0 1
30551 0x226 User Map Value 28 0 0xFFFF 1 --- F1 0 1
30552 0x227 User Map Value 29 0 0xFFFF 1 --- F1 0 1
30553 0x228 User Map Value 30 0 0xFFFF 1 --- F1 0 1
30554 0x229 User Map Value 31 0 0xFFFF 1 --- F1 0 1
30555 0x22A User Map Value 32 0 0xFFFF 1 --- F1 0 1
30556 0x22B User Map Value 33 0 0xFFFF 1 --- F1 0 1
30557 0x22C User Map Value 34 0 0xFFFF 1 --- F1 0 1
30558 0x22D User Map Value 35 0 0xFFFF 1 --- F1 0 1
30559 0x22E User Map Value 36 0 0xFFFF 1 --- F1 0 1
30560 0x22F User Map Value 37 0 0xFFFF 1 --- F1 0 1
30561 0x230 User Map Value 38 0 0xFFFF 1 --- F1 0 1
30562 0x231 User Map Value 39 0 0xFFFF 1 --- F1 0 1
30563 0x232 User Map Value 40 0 0xFFFF 1 --- F1 0 1
30564 0x233 User Map Value 41 0 0xFFFF 1 --- F1 0 1
30565 0x234 User Map Value 42 0 0xFFFF 1 --- F1 0 1
30566 0x235 User Map Value 43 0 0xFFFF 1 --- F1 0 1
30567 0x236 User Map Value 44 0 0xFFFF 1 --- F1 0 1
30568 0x237 User Map Value 45 0 0xFFFF 1 --- F1 0 1
30569 0x238 User Map Value 46 0 0xFFFF 1 --- F1 0 1
30570 0x239 User Map Value 47 0 0xFFFF 1 --- F1 0 1
30571 0x23A User Map Value 48 0 0xFFFF 1 --- F1 0 1
30572 0x23B User Map Value 49 0 0xFFFF 1 --- F1 0 1
30573 0x23C User Map Value 50 0 0xFFFF 1 --- F1 0 1
30574 0x23D User Map Value 51 0 0xFFFF 1 --- F1 0 1
30575 0x23E User Map Value 52 0 0xFFFF 1 --- F1 0 1
30576 0x23F User Map Value 53 0 0xFFFF 1 --- F1 0 1
30577 0x240 User Map Value 54 0 0xFFFF 1 --- F1 0 1
30578 0x241 User Map Value 55 0 0xFFFF 1 --- F1 0 1
30579 0x242 User Map Value 56 0 0xFFFF 1 --- F1 0 1
30580 0x243 User Map Value 57 0 0xFFFF 1 --- F1 0 1
30581 0x244 User Map Value 58 0 0xFFFF 1 --- F1 0 1
30582 0x245 User Map Value 59 0 0xFFFF 1 --- F1 0 1
30583 0x246 User Map Value 60 0 0xFFFF 1 --- F1 0 1
30584 0x247 User Map Value 61 0 0xFFFF 1 --- F1 0 1
30585 0x248 User Map Value 62 0 0xFFFF 1 --- F1 0 1

12-4 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30586 0x249 User Map Value 63 0 0xFFFF 1 --- F1 0 1
30587 0x24A User Map Value 64 0 0xFFFF 1 --- F1 0 1
30588 0x24B User Map Value 65 0 0xFFFF 1 --- F1 0 1
30589 0x24C User Map Value 66 0 0xFFFF 1 --- F1 0 1
30590 0x24D User Map Value 67 0 0xFFFF 1 --- F1 0 1
30591 0x24E User Map Value 68 0 0xFFFF 1 --- F1 0 1
30592 0x24F User Map Value 69 0 0xFFFF 1 --- F1 0 1
30593 0x250 User Map Value 70 0 0xFFFF 1 --- F1 0 1
30594 0x251 User Map Value 71 0 0xFFFF 1 --- F1 0 1
30595 0x252 User Map Value 72 0 0xFFFF 1 --- F1 0 1
30596 0x253 User Map Value 73 0 0xFFFF 1 --- F1 0 1
30597 0x254 User Map Value 74 0 0xFFFF 1 --- F1 0 1
30598 0x255 User Map Value 75 0 0xFFFF 1 --- F1 0 1
30599 0x256 User Map Value 76 0 0xFFFF 1 --- F1 0 1
30600 0x257 User Map Value 77 0 0xFFFF 1 --- F1 0 1
30601 0x258 User Map Value 78 0 0xFFFF 1 --- F1 0 1
30602 0x259 User Map Value 79 0 0xFFFF 1 --- F1 0 1
30603 0x25A User Map Value 80 0 0xFFFF 1 --- F1 0 1
30604 0x25B User Map Value 81 0 0xFFFF 1 --- F1 0 1
30605 0x25C User Map Value 82 0 0xFFFF 1 --- F1 0 1
30606 0x25D User Map Value 83 0 0xFFFF 1 --- F1 0 1
30607 0x25E User Map Value 84 0 0xFFFF 1 --- F1 0 1
30608 0x25F User Map Value 85 0 0xFFFF 1 --- F1 0 1
30609 0x260 User Map Value 86 0 0xFFFF 1 --- F1 0 1
30610 0x261 User Map Value 87 0 0xFFFF 1 --- F1 0 1
30611 0x262 User Map Value 88 0 0xFFFF 1 --- F1 0 1
30612 0x263 User Map Value 89 0 0xFFFF 1 --- F1 0 1
30613 0x264 User Map Value 90 0 0xFFFF 1 --- F1 0 1
30614 0x265 User Map Value 91 0 0xFFFF 1 --- F1 0 1
30615 0x266 User Map Value 92 0 0xFFFF 1 --- F1 0 1
30616 0x267 User Map Value 93 0 0xFFFF 1 --- F1 0 1
30617 0x268 User Map Value 94 0 0xFFFF 1 --- F1 0 1
30618 0x269 User Map Value 95 0 0xFFFF 1 --- F1 0 1
30619 0x26A User Map Value 96 0 0xFFFF 1 --- F1 0 1
30620 0x26B User Map Value 97 0 0xFFFF 1 --- F1 0 1
30621 0x26C User Map Value 98 0 0xFFFF 1 --- F1 0 1
30622 0x26D User Map Value 99 0 0xFFFF 1 --- F1 0 1
30623 0x26E User Map Value 100 0 0xFFFF 1 --- F1 0 1
30624 0x26F User Map Value 101 0 0xFFFF 1 --- F1 0 1
30625 0x270 User Map Value 102 0 0xFFFF 1 --- F1 0 1
30626 0x271 User Map Value 103 0 0xFFFF 1 --- F1 0 1
30627 0x272 User Map Value 104 0 0xFFFF 1 --- F1 0 1
30628 0x273 User Map Value 105 0 0xFFFF 1 --- F1 0 1
30629 0x274 User Map Value 106 0 0xFFFF 1 --- F1 0 1
30630 0x275 User Map Value 107 0 0xFFFF 1 --- F1 0 1
30631 0x276 User Map Value 108 0 0xFFFF 1 --- F1 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-5


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30632 0x277 User Map Value 109 0 0xFFFF 1 --- F1 0 1
30633 0x278 User Map Value 110 0 0xFFFF 1 --- F1 0 1
30634 0x279 User Map Value 111 0 0xFFFF 1 --- F1 0 1
30635 0x27A User Map Value 112 0 0xFFFF 1 --- F1 0 1
30636 0x27B User Map Value 113 0 0xFFFF 1 --- F1 0 1
30637 0x27C User Map Value 114 0 0xFFFF 1 --- F1 0 1
30638 0x27D User Map Value 115 0 0xFFFF 1 --- F1 0 1
30639 0x27E User Map Value 116 0 0xFFFF 1 --- F1 0 1
30640 0x27F User Map Value 117 0 0xFFFF 1 --- F1 0 1
30641 0x280 User Map Value 118 0 0xFFFF 1 --- F1 0 1
30642 0x281 User Map Value 119 0 0xFFFF 1 --- F1 0 1
30643 0x282 User Map Value 120 0 0xFFFF 1 --- F1 0 1
30644 0x283 User Map Value 121 0 0xFFFF 1 --- F1 0 1
30645 0x284 User Map Value 122 0 0xFFFF 1 --- F1 0 1
30646 0x285 User Map Value 123 0 0xFFFF 1 --- F1 0 1
30647 0x286 User Map Value 124 0 0xFFFF 1 --- F1 0 1
30648 0x287 User Map Value 125 0 0xFFFF 1 --- F1 0 1
EVENT RECORDER DETAILS
30652 0x28B Bus VT Secondary 50 240 1 V F1 120 1
30653 0x28C Aux VT Secondary 50 240 1 V F1 110 1
30654 0x28D CT Primary 1 6000 1 A F1 500 1
30655 0x28E Ground CT Primary 1 6000 1 A F1 50 1
30656 0x28F VT Ratio 10 50000 1 F2 10 1
30657 0x290 Aux VT Ratio 10 50000 1 F2 10 1
30658 0x291 Power Unit 0 1 1 --- FC430 0 1
30659 0x292 Event Recorder Last Reset 2 0x010107D8 0x0C1F082E 0 --- F18 0x010107D 2
words 8
30661 0x294 Total Number of Events 0 65535 1 --- F1 0 1
Since Last Clear
30662 0x295 Event Cause 0 0xFFFF 1 --- FC134 0 1
30663 0x296 Event Time 0 0x173BEA5F 0 --- F19 0 2
30665 0x298 Event Date 0x010107D8 0x0C1F082E 0 --- F18 0x010107D 2
8
30667 0x29A Event Ia 0 0xFFFF 1 x CT F17A 0 1
30668 0x29B Event Ib 0 0xFFFF 1 x CT F17A 0 1
30669 0x29C Event Ic 0 0xFFFF 1 x CT F17A 0 1
30670 0x29D Event Ig 0 0xFFFF 1 x CT F17A 0 1
30671 0x29E Event In 0 0xFFFF 1 x CT F17A 0 1
30672 0x29F Event Isgrd 0 0xFFFF 1 x CT F17A 0 1
30673 0x2A0 Event Ia Angle 0 359 1 ° F1 0 1
30674 0x2A1 Event Ib Angle 0 359 1 ° F1 0 1
30675 0x2A2 Event Ic Angle 0 359 1 ° F1 0 1
30676 0x2A3 Event Igrd Angle 0 359 1 ° F1 0 1
30677 0x2A4 Event In Angle 0 359 1 ° F1 0 1
30678 0x2A5 Event Vab 0 65535 1 x VT F17A 0 1
30679 0x2A6 Event Vbc 0 65535 1 x VT F17A 0 1
30680 0x2A7 Event Vca 0 65535 1 x VT F17A 0 1

12-6 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30681 0x2A8 Event Van 0 65535 1 x VT F17A 0 1
30682 0x2A9 Event Vbn 0 65535 1 x VT F17A 0 1
30683 0x2AA Event Vcn 0 65535 1 x VT F17A 0 1
30684 0x2AB Event Vaux 0 65535 1 x VT F17A 0 1
30685 0x2AC Event Va Angle 0 359 1 ° F1 0 1
30686 0x2AD Event Vb Angle 0 359 1 ° F1 0 1
30687 0x2AE Event Vc Angle 0 359 1 ° F1 0 1
30688 0x2AF Event Vc Angle 0 359 1 ° F1 0 1
30689 0x2B0 Frequency 0 12000 1 Hz F3 0 1
30690 0x2B1 Event Power Factor -99 100 1 --- F21 0 1
30691 0x2B2 Event Real Power -65535 65535 1 x F7 0 1
CTxVT
30692 0x2B3 Event Reactive Power -65535 65535 1 x F7 0 1
CTxVT
30693 0x2B4 Event Apparent Power 0 65535 1 x F17A 0 1
CTxVT
30694 0x2B5 Phase A Thermal Capacity 0 1500 1 % F2 0 1
30695 0x2B6 Phase B Thermal Capacity 0 1500 1 % F2 0 1
30696 0x2B7 Phase C Thermal Capacity 0 1500 1 % F2 0 1
30697 0x2B8 Event Self-Test Event 0 0xFFFFFFFF 2 --- FC188 0 2
TRANSIENT RECORDER SAMPLES
30720 0x2CF Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 1
30721 0x2D0 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 2
30722 0x2D1 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 3
30723 0x2D2 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 4
30724 0x2D3 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 5
30725 0x2D4 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 6
30726 0x2D5 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 7
30727 0x2D6 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 8
30728 0x2D7 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 9
30729 0x2D8 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 10
30730 0x2D9 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 11
30731 0x2DA Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 12
30732 0x2DB Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 13
30733 0x2DC Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 14
30734 0x2DD Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 15
30735 0x2DE Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 16

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-7


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30736 0x2DF Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 17
30737 0x2E0 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 18
30738 0x2E1 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 19
30739 0x2E2 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 20
30740 0x2E3 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 21
30741 0x2E4 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 22
30742 0x2E5 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 23
30743 0x2E6 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 24
30744 0x2E7 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 25
30745 0x2E8 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 26
30746 0x2E9 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 27
30747 0x2EA Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 28
30748 0x2EB Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 29
30749 0x2EC Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 30
30750 0x2ED Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 31
30751 0x2EE Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 32
30752 0x2EF Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 33
30753 0x2F0 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 34
30754 0x2F1 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 35
30755 0x2F2 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 36
30756 0x2F3 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 37
30757 0x2F4 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 38
30758 0x2F5 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 39
30759 0x2F6 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 40
30760 0x2F7 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 41
30761 0x2F8 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 42
30762 0x2F9 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 43
30763 0x2FA Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 44

12-8 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30764 0x2FB Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 45
30765 0x2FC Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 46
30766 0x2FD Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 47
30767 0x2FE Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 48
30768 0x2FF Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 49
30769 0x300 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 50
30770 0x301 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 51
30771 0x302 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 52
30772 0x303 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 53
30773 0x304 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 54
30774 0x305 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 55
30775 0x306 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 56
30776 0x307 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 57
30777 0x308 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 58
30778 0x309 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 59
30779 0x30A Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 60
30780 0x30B Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 61
30781 0x30C Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 62
30782 0x30D Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 63
30783 0x30E Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 64
30784 0x30F Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 65
30785 0x310 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 66
30786 0x311 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 67
30787 0x312 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 68
30788 0x313 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 69
30789 0x314 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 70
30790 0x315 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 71
30791 0x316 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 72

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-9


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30792 0x317 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 73
30793 0x318 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 74
30794 0x319 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 75
30795 0x31A Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 76
30796 0x31B Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 77
30797 0x31C Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 78
30798 0x31D Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 79
30799 0x31E Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 80
30800 0x31F Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 81
30801 0x320 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 82
30802 0x321 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 83
30803 0x322 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 84
30804 0x323 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 85
30805 0x324 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 86
30806 0x325 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 87
30807 0x326 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 88
30808 0x327 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 89
30809 0x328 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 90
30810 0x329 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 91
30811 0x32A Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 92
30812 0x32B Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 93
30813 0x32C Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 94
30814 0x32D Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 95
30815 0x32E Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 96
30816 0x32F Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 97
30817 0x330 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 98
30818 0x331 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 99
30819 0x332 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 100

12-10 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30820 0x333 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 101
30821 0x334 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 102
30822 0x335 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 103
30823 0x336 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 104
30824 0x337 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 105
30825 0x338 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 106
30826 0x339 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 107
30827 0x33A Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 108
30828 0x33B Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 109
30829 0x33C Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 110
30830 0x33D Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 111
30831 0x33E Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 112
30832 0x33F Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 113
30833 0x340 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 114
30834 0x341 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 115
30835 0x342 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 116
30836 0x343 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 117
30837 0x344 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 118
30838 0x345 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 119
30839 0x346 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 120
30840 0x347 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 121
30841 0x348 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 122
30842 0x349 Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 123
30843 0x34A Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 124
30844 0x34B Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 125
30845 0x34C Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 126
30846 0x34D Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 127
30847 0x34E Sample Index + Trace -32767 32767 1 --- F4 0 1
Memory Sample 128

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-11


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
STATUS BUFFER
30948 0x3B3 Alarm Status 3 0 0xFFFFFFFF 1 --- FC181 0 2
30950 0x3B5 Alarm Status 2 0 0xFFFFFFFF 1 --- FC180 0 2
30952 0x3B7 Alarm Status 1 0 0xFFFFFFFF 1 --- FC179 0 2
30956 0x3BB Trip Status 3 0 0xFFFFFFFF 1 --- FC185 0 2
30958 0x3BD Trip Status 2 0 0xFFFFFFFF 1 --- FC184 0 2
30960 0x3BF Trip Status 1 0 0xFFFFFFFF 1 --- FC183 0 2
30966 0x3C5 Message Status 2 0 0xFFFFFFFF 1 --- FC188 0 2
30968 0x3C7 Message Status 1 0 0xFFFFFFFF 1 --- FC187 0 2
30970 0x3C9 Control Element Status 4 0 0xFFFFFFFF 1 --- FC194 0 2
30972 0x3CB Control Element Status 3 0 0xFFFFFFFF 1 --- FC193 0 2
30974 0x3CD Control Element Status 2 0 0xFFFFFFFF 1 --- FC192 0 2
30976 0x3CF Control Element Status 1 0 0xFFFFFFFF 1 --- FC191 0 2
30980 0x3D3 Block Status 3 0 0xFFFFFFFF 1 --- FC202 0 2
30982 0x3D5 Block Status 2 0 0xFFFFFFFF 1 --- FC201 0 2
30984 0x3D7 Block Status 1 0 0xFFFFFFFF 1 --- FC200 0 2
61850 STATUS
31510 0x5E5 61850 Status 0 2 1 --- FC108 0 1
31511 0x5E6 61850 N.V. Status 0 4 1 --- FC434 0 1
IEC61850 GOOSE STATUS
31515 0x5EA Remote GOOSE Status 0 0xFFFFFFFF 1 --- FC215 0 2
31517 0x5EC Remote GOOSE Header 0 0xFFFFFFFF 1 --- FC215 0 2
Status
THERMAL MODEL TRIP STATUS
31521 0x5F0 Trip Phase A Status 1 0 65535 1 --- FC134 0 1
31522 0x5F1 Trip Phase B Status 1 0 65535 1 --- FC134 0 1
31523 0x5F2 Trip Phase C Status 1 0 65535 1 --- FC134 0 1
PHASE IOC1 TRIP STATUS
31524 0x5F3 Trip Phase A Status 2 0 65535 1 --- FC134 0 1
31525 0x5F4 Trip Phase B Status 2 0 65535 1 --- FC134 0 1
31526 0x5F5 Trip Phase C Status 2 0 65535 1 --- FC134 0 1
PHASE TOC1 TRIP STATUS
31527 0x5F6 Trip Phase A Status 3 0 65535 1 --- FC134 0 1
31528 0x5F7 Trip Phase B Status 3 0 65535 1 --- FC134 0 1
31529 0x5F8 Trip Phase C Status 3 0 65535 1 --- FC134 0 1
PHASE IOC2 TRIP STATUS
31530 0x5F9 Trip Phase A Status 4 0 65535 1 --- FC134 0 1
31531 0x5FA Trip Phase B Status 4 0 65535 1 --- FC134 0 1
31532 0x5FB Trip Phase C Status 4 0 65535 1 --- FC134 0 1
PHASE OV TRIP STATUS
31533 0x5FC Trip Phase A Status 5 0 65535 1 --- FC134 0 1
31534 0x5FD Trip Phase B Status 5 0 65535 1 --- FC134 0 1
31535 0x5FE Trip Phase C Status 5 0 65535 1 --- FC134 0 1
PHASE UV TRIP STATUS
31536 0x5FF Trip Phase A Status 6 0 65535 1 --- FC134 0 1
31537 0x600 Trip Phase B Status 6 0 65535 1 --- FC134 0 1

12-12 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
31538 0x601 Trip Phase C Status 6 0 65535 1 --- FC134 0 1
PHASE OV2 TRIP STATUS
31545 0x608 0 65535 1 --- FC134 0 1
PhaseOV2Trip_PhaseAStatus
31546 0x609 0 65535 1 --- FC134 0 1
PhaseOV2Trip_PhaseBStatus
31547 0x60A 0 65535 1 --- FC134 0 1
PhaseOV2Trip_PhaseCStatus
PHASE UV2 TRIP STATUS
31548 0x60B 0 65535 1 --- FC134 0 1
PhaseUV2Trip_PhaseAStatus
31549 0x60C 0 65535 1 --- FC134 0 1
PhaseUV2Trip_PhaseBStatus
31550 0x60D 0 65535 1 --- FC134 0 1
PhaseUV2Trip_PhaseCStatus
PHASE OV3 TRIP STATUS
31551 0x60E 0 65535 1 --- FC134 0 1
PhaseOV3Trip_PhaseAStatus
31552 0x60F 0 65535 1 --- FC134 0 1
PhaseOV3Trip_PhaseBStatus
31553 0x610 0 65535 1 --- FC134 0 1
PhaseOV3Trip_PhaseCStatus
PHASE UV3 TRIP STATUS
31554 0x611 0 65535 1 --- FC134 0 1
PhaseUV3Trip_PhaseAStatus
31555 0x612 0 65535 1 --- FC134 0 1
PhaseUV3Trip_PhaseBStatus
31556 0x613 0 65535 1 --- FC134 0 1
PhaseUV3Trip_PhaseCStatus
PHASE OV4 TRIP STATUS
31557 0x614 0 65535 1 --- FC134 0 1
PhaseOV4Trip_PhaseAStatus
31558 0x615 0 65535 1 --- FC134 0 1
PhaseOV4Trip_PhaseBStatus
31559 0x616 0 65535 1 --- FC134 0 1
PhaseOV4Trip_PhaseCStatus
PHASE UV4 TRIP STATUS
31560 0x617 0 65535 1 --- FC134 0 1
PhaseUV4Trip_PhaseAStatus
31561 0x618 0 65535 1 --- FC134 0 1
PhaseUV4Trip_PhaseBStatus
31562 0x619 0 65535 1 --- FC134 0 1
PhaseUV4Trip_PhaseCStatus
THERMAL MODEL ALARM STATUS
31569 0x620 Alarm Phase A Status 1 0 65535 1 --- FC134 0 1
31570 0x621 Alarm Phase B Status 1 0 65535 1 --- FC134 0 1
31571 0x622 Alarm Phase C Status 1 0 65535 1 --- FC134 0 1
PHASE IOC1 ALARM STATUS
31572 0x623 Alarm Phase A Status 2 0 65535 1 --- FC134 0 1
31573 0x624 Alarm Phase B Status 2 0 65535 1 --- FC134 0 1
31574 0x625 Alarm Phase C Status 2 0 65535 1 --- FC134 0 1
PHASE TOC1 ALARM STATUS
31575 0x626 Alarm Phase A Status 3 0 65535 1 --- FC134 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-13


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
31576 0x627 Alarm Phase B Status 3 0 65535 1 --- FC134 0 1
31577 0x628 Alarm Phase C Status 3 0 65535 1 --- FC134 0 1
PHASE IOC2 ALARM STATUS
31578 0x629 Alarm Phase A Status 4 0 65535 1 --- FC134 0 1
31579 0x62A Alarm Phase B Status 4 0 65535 1 --- FC134 0 1
31580 0x62B Alarm Phase C Status 4 0 65535 1 --- FC134 0 1
PHASE OV ALARM STATUS
31581 0x62C Alarm Phase A Status 5 0 65535 1 --- FC134 0 1
31582 0x62D Alarm Phase B Status 5 0 65535 1 --- FC134 0 1
31583 0x62E Alarm Phase C Status 5 0 65535 1 --- FC134 0 1
PHASE UV ALARM STATUS
31584 0x62F Alarm Phase A Status 6 0 65535 1 --- FC134 0 1
31585 0x630 Alarm Phase B Status 6 0 65535 1 --- FC134 0 1
31586 0x631 Alarm Phase C Status 6 0 65535 1 --- FC134 0 1
PHASE TOC2 ALARM STATUS
31590 0x635 0 65535 1 --- FC134 0 1
Phase51PTOC_2Alarm_Phas
eAStatus
31591 0x636 0 65535 1 --- FC134 0 1
Phase51PTOC_2Alarm_Phas
eBStatus
31592 0x637 0 65535 1 --- FC134 0 1
Phase51PTOC_2Alarm_Phas
eCStatus
PHASE OV 2 ALARM STATUS
31593 0x638 0 65535 1 --- FC134 0 1
PhaseOV2Alarm_PhaseAStat
us
31594 0x639 0 65535 1 --- FC134 0 1
PhaseOV2Alarm_PhaseBStat
us
31595 0x63A 0 65535 1 --- FC134 0 1
PhaseOV2Alarm_PhaseCStat
us
PHASE UV 2 ALARM STATUS
31596 0x63B 0 65535 1 --- FC134 0 1
PhaseUV2Alarm_PhaseAStat
us
31597 0x63C 0 65535 1 --- FC134 0 1
PhaseUV2Alarm_PhaseBStat
us
31598 0x63D 0 65535 1 --- FC134 0 1
PhaseUV2Alarm_PhaseCStat
us
PHASE OV 3 ALARM STATUS
31599 0x63E 0 65535 1 --- FC134 0 1
PhaseOV3Alarm_PhaseAStat
us
31600 0x63F 0 65535 1 --- FC134 0 1
PhaseOV3Alarm_PhaseBStat
us
31601 0x640 0 65535 1 --- FC134 0 1
PhaseOV3Alarm_PhaseCStat
us
PHASE UV 3 ALARM STATUS

12-14 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
31602 0x641 0 65535 1 --- FC134 0 1
PhaseUV3Alarm_PhaseAStat
us
31603 0x642 0 65535 1 --- FC134 0 1
PhaseUV3Alarm_PhaseBStat
us
31604 0x643 0 65535 1 --- FC134 0 1
PhaseUV3Alarm_PhaseCStat
us
PHASE OV 4 ALARM STATUS
31605 0x644 0 65535 1 --- FC134 0 1
PhaseOV4Alarm_PhaseAStat
us
31606 0x645 0 65535 1 --- FC134 0 1
PhaseOV4Alarm_PhaseBStat
us
31607 0x646 0 65535 1 --- FC134 0 1
PhaseOV4Alarm_PhaseCStat
us
PHASE UV 4 ALARM STATUS
31608 0x647 0 65535 1 --- FC134 0 1
PhaseUV4Alarm_PhaseAStat
us
31609 0x648 0 65535 1 --- FC134 0 1
PhaseUV4Alarm_PhaseBStat
us
31610 0x649 0 65535 1 --- FC134 0 1
PhaseUV4Alarm_PhaseCStat
us
VOLTS PER HERTZ
31613 0x64C Volts per Hertz 0 400 1 V/Hz F3 0 1
32N WATTMETRIC
31734 0x6C5 Wattmetric Power 1 -999999999 999999999 1 W F13 0 2
31736 0x6C7 Wattmetric Power 2 -999999999 999999999 1 W F13 0 2
SYMMETRICAL COMPONENTS
30454 0x1C5 Positive Sequence Current 0 65535 1 A F1 0 1
Magnitude
30455 0x1C6 Positive Sequence Current 0 359 1 °Lag F1 0 1
Angle
30456 0x1C7 Negative Sequence Current 0 65535 1 A F1 0 1
Magnitude
30457 0x1C8 Negative Sequence Current 0 359 1 °Lag F1 0 1
Angle
30458 0x1C9 Zero Sequence Current 0 65535 1 A F1 0 1
Magnitude
30459 0x1CA Zero Sequence Current 0 359 1 °Lag F1 0 1
Angle
30460 0x1CB Positive Sequence Voltage 0 65535 1 V F1 0 1
Magnitude
30461 0x1CC Positive Sequence Voltage 0 359 1 °Lag F1 0 1
Angle
30462 0x1CD Negative Sequence Voltage 0 6000 1 kV F2 0 1
Magnitude
30463 0x1CE Negative Sequence Voltage 0 359 1 °Lag F1 0 1
Angle
30464 0x1CF Zero Sequence Voltage 0 60000 1 kV F3 0 1
Magnitude

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-15


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30465 0x1D0 Zero Sequence Voltage 0 359 1 °Lag F1 0 1
Angle
30466 0x1D1 Zero Seq V Mag 0 65535 1 kV F1 0 1
30478 0x1DD Negative Sequence Current 0 65535 1 A F2 0 1
Magnitude
30479 0x1DE Negative Sequence Voltage 0 65535 1 V F1 0 1
31762 0x6E1 Positive Sequence Voltage 0 0xFFFF 1 V F9 0 2
(32 bits)
31764 0x6E3 Negative Sequence Voltage 0 0xFFFF 1 V F9 0 2
(32 bits)
31766 0x6E5 Zero Sequence Voltage (32 0 0xFFFF 1 V F9 0 2
bits)
VOLTAGE METERING
30358 0x165 Vab Voltage 0 65535 1 V F1 0 1
30359 0x166 Vbc Voltage 0 65535 1 V F1 0 1
30360 0x167 Vca Voltage 0 65535 1 V F1 0 1
30361 0x168 Average Line Voltage 0 65535 1 V F1 0 1
30362 0x169 Van Voltage 0 65535 1 V F1 0 1
30363 0x16A Vbn Voltage 0 65535 1 V F1 0 1
30364 0x16B Vcn Voltage 0 65535 1 V F1 0 1
30365 0x16C Average Phase Voltage 0 65535 1 V F1 0 1
30366 0x16D Frequency 0 12000 1 Hz F3 0 1
30367 0x16E Neutral Voltage 0 65535 1 V F1 0 1
30376 0x177 Auxiliary Voltage 0 65535 1 Vaux F1 0 1
31746 0x6D1 Vab Voltage (32 bits) 0 0xFFFF 1 V F9 0 2
31748 0x6D3 Vbc Voltage (32 bits) 0 0xFFFF 1 V F9 0 2
31750 0x6D5 Vca Voltage (32 bits) 0 0xFFFF 1 V F9 0 2
31752 0x6D7 Van Voltage (32 bits) 0 0xFFFF 1 V F9 0 2
31754 0x6D9 Vbn Voltage (32 bits) 0 0xFFFF 1 V F9 0 2
31756 0x6DB Vcn Voltage (32 bits) 0 0xFFFF 1 V F9 0 2
31758 0x6DD Vn Voltage (32 bits) 0 0xFFFF 1 V F9 0 2
31760 0x6DF VAux Voltage (32 bits) 0 0xFFFF 1 V F9 0 2
31768 0x6E7 0 65535 1 V F9 0 2
31770 0x6E9 0 65535 1 V F9 0 2
TRANSIENT RECORDER
30707 0x2C2 Transient Recorder Last 0x010107D8 0x0C1F082E 0 --- F18 0x010107D 2
Cleared 8
30709 0x2C4 Transient Recorder Available 0 6 1 --- F1 0 1
Records
30710 0x2C5 Trace Memory Trigger Date 0x010107D8 0x0C1F082E 0 --- F18 0x010107D 2
8
30712 0x2C7 Trace Memory Trigger Time 0 0x173BEA5F 0 --- F19 0 2
30714 0x2C9 Trace Memory Trigger 0 0xD002 0 --- FC133 0 1
Cause
30715 0x2CA Trace Memory Trigger 0 12000 1 Hz F3 60 1
Frequency
30716 0x2CB Total Triggers 0 0xFFFF 1 --- F1 0 1
30718 0x2CD Trigger Position (Actual 0 6143 1 --- F1 25 1
Value)
30719 0x2CE Trace Memory Start Index 0 6143 1 --- F1 0 1

12-16 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
31773 0x6EC Transient Sampling Rate 0 3 1 --- FC429 0 1
Status
FAULT REPORT
31775 0x6EE Fault Report Date 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
9
31777 0x6F0 Fault Report Time 0 0x173BEA5F 0 --- F19 0 2
31779 0x6F2 Fault Report Fault Type 0 2 1 --- FC134C 0 1
31780 0x6F3 Fault Report Ia 0 1200000 1 A F10 0 2
31782 0x6F5 Fault Report Ia Angle 0 359 1 ° F1 0 1
31783 0x6F6 Fault Report Ib 0 1200000 1 A F10 0 2
31785 0x6F8 Fault Report Ib Angle 0 359 1 ° F1 0 1
31786 0x6F9 Fault Report Ic 0 1200000 1 A F10 0 2
31788 0x6FB Fault Report Ic Angle 0 359 1 ° F1 0 1
31789 0x6FC Fault Report Ig 0 1200000 1 A F10 0 2
31791 0x6FE Fault Report Ig Angle 0 359 1 ° F1 0 1
31792 0x6FF Fault Report In 0 100000 1 A F10 0 2
31794 0x701 Fault Report In Angle 0 359 1 ° F1 0 1
31795 0x702 Fault Report Va 0 65535 1 V F9 0 2
31797 0x704 Fault Report Va Angle 0 359 1 ° F1 0 1
31798 0x705 Fault Report Vb 0 65535 1 V F9 0 2
31800 0x707 Fault Report Vb Angle 0 359 1 ° F1 0 1
31801 0x708 Fault Report Vc 0 65535 1 V F9 0 2
31803 0x70A Fault Report Vc Angle 0 359 1 ° F1 0 1
31804 0x70B Fault Report Vab 0 0xFFFF 1 V F9 0 2
31806 0x70D Fault Report Vab Angle 0 359 1 ° F1 0 1
31807 0x70E Fault Report Vbc 0 0xFFFF 1 V F9 0 2
31809 0x710 Fault Report Vbc Angle 0 359 1 ° F1 0 1
31810 0x711 Fault Report Vca 0 0xFFFF 1 V F9 0 2
31812 0x713 Fault Report Vca Angle 0 359 1 ° F1 0 1
31813 0x714 Fault Report Vn 0 65535 1 V F9 0 2
31815 0x716 Fault Report Vn Angle 0 359 1 ° F1 0 1
31816 0x717 Fault Report Vaux 0 65535 1 V F9 0 2
31818 0x719 Fault Report Vaux Angle 0 359 1 ° F1 0 1
31853 0x73C Fault Report Phases 1 7 1 --- F37 1 1
31854 0x73D Fault Report Firmware 0 0xFFFF 1 --- F3 220 1
Version
31855 0x73E Fault Report Order Code 0 16 1 --- F22 350- 12
EP5G5HSSN
NSNDN
31867 0x74A Fault Report Feeder Name 0 10 1 --- F22 Feeder 10
Name
DIRECTIONAL POWER
31739 0x6CA Directional Power 1 -1000000 1000000 1 kW F13 0 2
31741 0x6CC Directional Power 2 -1000000 1000000 1 kW F13 0 2
31880 0x757 Directional Power 1 -1000 1000 1 MW F13 0 2
31882 0x759 Directional Power 2 -1000 1000 1 MW F13 0 2
DEVICE STATUS

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-17


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
30302 0x12D Current Security Access 0 3 1 --- F1 0 1
Level
30305 0x130 Device Status 0 0xFFFF 1 --- FC129 0 1
30317 0x13C Active Setpoint Group 0 1 1 --- F1 0 1
30319 0x13E Relay1 Coil Status 0 1 1 --- FC125 0 1
30320 0x13F Relay2 Coil Status 0 1 1 --- FC125 0 1
31887 0x75E Breaker Health 0 100000 1 --- F9 0 2
31889 0x760 Breaker Last Trip Time 0 10000 1 ms F1 0 1
31890 0x761 Breaker Avg Trip Time 0 10000 1 ms F1 0 1
31891 0x762 Breaker Last Close Time 0 10000 1 ms F1 0 1
31892 0x763 Breaker Avg Close Time 0 10000 1 ms F1 0 1
31893 0x764 Breaker Last Charge Time 0 60000 1 ms F1 0 1
31894 0x765 Breaker Avg Charge Time 0 60000 1 ms F1 0 1
HSR PRP SETTINGS
32128 0x84F RTC Sync Source 0 5 1 --- FC422 0 1
32129 0x850 Grand Master ID Low 0 4 1 --- F22 L0 4
32133 0x854 Grand Master ID High 0 4 1 --- F22 L0 4
32137 0x858 PTP Accuracy -2147483648 2147483647 1 --- F12 0 2
32139 0x85A PTP State 0 3 1 --- FC423 0 1
32140 0x85B PTP Port B State 0 3 1 --- FC423 0 1
32141 0x85C PRP HSR Version 0 4 1 --- F22 L0 4
32145 0x860 DAISY_CHAIN Version 0 4 1 --- F22 L0 4
32149 0x864 Bypass Version 0 4 1 --- F22 L0 4
32153 0x868 LLA Version 0 4 1 --- F22 L0 4
32157 0x86C PRP total sent Port A 0 0xFFFFFFFF 1 --- F9 0 2
32159 0x86E PRP total sent Port B 0 0xFFFFFFFF 1 --- F9 0 2
32161 0x870 PRP total errors Port A 0 0xFFFFFFFF 1 --- F9 0 2
32163 0x872 PRP total errors Port B 0 0xFFFFFFFF 1 --- F9 0 2
32165 0x874 RSTP Port A State 0 2 1 --- FC426 0 1
32166 0x875 RSTP Port B State 0 2 1 --- FC426 0 1
DEMAND
32170 0x879 Current Demand 1 Last Rst 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
Date 9
32172 0x87B Current Demand 1 Last Rst 0 0x173BEA5F 0 --- F19 0 2
Time
32174 0x87D Current Demand 1 PhA 0 300000 1 A F10 0 2
32176 0x87F Current Demand 1 PhB 0 300000 1 A F10 0 2
32178 0x881 Current Demand 1 PhC 0 300000 1 A F10 0 2
32180 0x883 Max Current Demand 1 PhA 0 300000 1 A F10 0 2
32182 0x885 Max Current Demand 1 PhB 0 300000 1 A F10 0 2
32184 0x887 Max Current Demand 1 PhC 0 300000 1 A F10 0 2
32186 0x889 Current Demand 1 PhA Date 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
9
32188 0x88B Current Demand 1 PhB Date 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
9
32190 0x88D Current Demand 1 PhC Date 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
9
32192 0x88F Current Demand 1 PhA Time 0 0x173BEA5F 0 --- F19 0 2

12-18 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
32194 0x891 Current Demand 1 PhB Time 0 0x173BEA5F 0 --- F19 0 2
32196 0x893 Current Demand 1 PhC Time 0 0x173BEA5F 0 --- F19 0 2
32226 0x8B1 Power Demand Last Rst 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
Date 9
32228 0x8B3 Power Demand Last Rst 0 0x173BEA5F 0 --- F19 0 2
Time
32230 0x8B5 Real Power Demand 0 1000000 1 kW F10 0 2
32232 0x8B7 Reactive Power Demand 0 1000000 1 kvar F10 0 2
32234 0x8B9 Apparent Power Demand 0 1000000 1 kVA F10 0 2
32236 0x8BB Max Real Power Demand 0 1000000 1 kW F10 0 2
32238 0x8BD Max Reactive Power 0 1000000 1 kvar F10 0 2
Demand
32240 0x8BF Max Apparent Power 0 1000000 1 kVA F10 0 2
Demand
32242 0x8C1 Real Power Demand Date 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
9
32244 0x8C3 Reactive Power Demand 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
Date 9
32246 0x8C5 Apparent Power Demand 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
Date 9
32248 0x8C7 Real Power Demand Time 0 0x173BEA5F 0 --- F19 0 2
32250 0x8C9 Reactive Power Demand 0 0x173BEA5F 0 --- F19 0 2
Time
32252 0x8CB Apparent Power Demand 0 0x173BEA5F 0 --- F19 0 2
Time
SETPOINTS
MESSAGE TIMES
40120 0x77 Flash Message Time 1 65535 1 s F1 5 1
40121 0x78 Message Timeout 1 65535 1 s F1 30 1
COMMANDS
40129 0x80 Command address 0 0xFFFF 0 --- F1 0 1
40130 0x81 Command Function 0 0xFFFF 0 --- F1 0 1
40131 0x82 Command Data 1 0 0xFFFF 0 --- F1 0 1
40132 0x83 Command Data 2 0 0xFFFF 0 --- F1 0 1
40133 0x84 Command Data 3 0 0xFFFF 0 --- F1 0 1
40134 0x85 Command Data 4 0 0xFFFF 0 --- F1 0 1
40135 0x86 Command Data 5 0 0xFFFF 0 --- F1 0 1
40136 0x87 Command Data 6 0 0xFFFF 0 --- F1 0 1
40137 0x88 Command Data 7 0 0xFFFF 0 --- F1 0 1
40138 0x89 Command Data 8 0 0xFFFF 0 --- F1 0 1
40139 0x8A Command Data 9 0 0xFFFF 0 --- F1 0 1
40140 0x8B Command Data 10 0 0xFFFF 0 --- F1 0 1
RS485 COMMUNICATIONS
40172 0xAB Slave Address 1 254 1 --- F1 254 1
40173 0xAC RS485 Baud Rate 0 4 1 --- FC101 4 1
40174 0xAD RS485 Parity 0 2 1 --- FC102 0 1
40175 0xAE Rear 485 Port Protocol 0 2 1 --- F97 0 1
ETHERNET COMMUNICATIONS
40180 0xB3 SNTP Mode 0 3 1 --- FC100 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-19


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
40181 0xB4 SNTP IP Address 0 0xFFFFFFFF 1 --- FC150 0 2
40183 0xB6 Ethernet IP address 0 0xFFFFFFFF 1 --- FC150 0 2
40185 0xB8 Ethernet subnet mask 0 0xFFFFFFFF 1 --- FC150 0xFFFFFC00 2
40187 0xBA Ethernet gateway address 0 0xFFFFFFFF 1 --- FC150 0 2
40189 0xBC SNTP Port 0 65535 1 --- F1 0 1
40191 0xBE EthernetConnectionType 0 1 1 --- FC230 0 1
(Copper or Fiber)
40194 0xC1 High Eth Message Enable 0 1 1 --- FC126 1 1
REAL-TIME CLOCK
40228 0xE3 Set Date 0x010107D9 0x0C1F0833 0 --- F18 0x010107D 2
9
40230 0xE5 Set Time 0 0x173BEA5F 0 --- F19 0 2
40232 0xE7 Time Offset From UTC -2400 2400 25 hrs F6 0 1
40233 0xE8 IRIG-B 0 1 1 --- FC126 0 1
40234 0xE9 Daylight Savings 0 1 1 --- FC126 0 1
40235 0xEA DST Start Month 0 12 1 --- FC169 0 1
40236 0xEB DST Start Week 0 5 1 --- FC170 0 1
40237 0xEC DST Start Weekday 0 7 1 --- FC171 0 1
40238 0xED DST End Month 0 12 1 --- FC169 0 1
40239 0xEE DST End Week 0 5 1 --- FC170 0 1
40240 0xEF DST End Weekday 0 7 1 --- FC171 0 1
REMOTE INPUTS
40260 0x103 Remote Inputs 0 0xFFFFFFFF 1 --- FC167 0 2
CURRENT SENSING
40267 0x10A CT Primary 1 6000 1 A F1 500 1
40268 0x10B Ground CT Secondary 0 1 1 --- FC104 1 1
40271 0x10E Ground CT Primary 1 6000 1 A F1 50 1
40272 0x10F Sensitive Ground CT Primary 1 600 1 A F1 50 1
40273 0x110 Phase CT Secondary 0 1 1 --- FC415 1 1
VOLTAGE
40276 0x113 3 Phase Voltage Connection 0 1 1 --- FC106 0 1
40277 0x114 Auxiliary VT Connection 0 6 1 --- FC176 0 1
40278 0x115 Auxiliary VT Primary 110 690 1 V F1 415 1
40279 0x116 Auxiliary VT Secondary 50 240 1 V F1 110 1
40280 0x117 Aux VT Ratio 10 50000 1 F2 10 1
40281 0x118 Bus VT Secondary 50 240 1 V F1 120 1
40282 0x119 Bus VT Ratio 10 50000 1 F2 10 1
POWER SYSTEM
40284 0x11B Supply Frequency 0 1 1 Hz FC107 0 1
40285 0x11C Feeder Name 0 9 1 --- F22 Feeder 9
Name
40295 0x126 Power Unit 0 1 1 --- FC430 0 1
40296 0x127 Phase Sequence 0 1 1 --- FC124A 0 1
USER MAP ADDRESSES
40524 0x20B User Map Address 1 30001 39999 1 --- F1 30305 1
40525 0x20C User Map Address 2 30001 39999 1 --- F1 30505 1
40526 0x20D User Map Address 3 30001 39999 1 --- F1 30506 1

12-20 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
40527 0x20E User Map Address 4 30001 39999 1 --- F1 30960 1
40528 0x20F User Map Address 5 30001 39999 1 --- F1 30961 1
40529 0x210 User Map Address 6 30001 39999 1 --- F1 30958 1
40530 0x211 User Map Address 7 30001 39999 1 --- F1 30959 1
40531 0x212 User Map Address 8 30001 39999 1 --- F1 30956 1
40532 0x213 User Map Address 9 30001 39999 1 --- F1 30957 1
40533 0x214 User Map Address 10 30001 39999 1 --- F1 30954 1
40534 0x215 User Map Address 11 30001 39999 1 --- F1 30955 1
40535 0x216 User Map Address 12 30001 39999 1 --- F1 30952 1
40536 0x217 User Map Address 13 30001 39999 1 --- F1 30953 1
40537 0x218 User Map Address 14 30001 39999 1 --- F1 30950 1
40538 0x219 User Map Address 15 30001 39999 1 --- F1 30951 1
40539 0x21A User Map Address 16 30001 39999 1 --- F1 30948 1
40540 0x21B User Map Address 17 30001 39999 1 --- F1 30949 1
40541 0x21C User Map Address 18 30001 39999 1 --- F1 30946 1
40542 0x21D User Map Address 19 30001 39999 1 --- F1 30947 1
40543 0x21E User Map Address 20 30001 39999 1 --- F1 30976 1
40544 0x21F User Map Address 21 30001 39999 1 --- F1 30977 1
40545 0x220 User Map Address 22 30001 39999 1 --- F1 30974 1
40546 0x221 User Map Address 23 30001 39999 1 --- F1 30975 1
40547 0x222 User Map Address 24 30001 39999 1 --- F1 30972 1
40548 0x223 User Map Address 25 30001 39999 1 --- F1 30973 1
40549 0x224 User Map Address 26 30001 39999 1 --- F1 30970 1
40550 0x225 User Map Address 27 30001 39999 1 --- F1 30971 1
40551 0x226 User Map Address 28 30001 39999 1 --- F1 30984 1
40552 0x227 User Map Address 29 30001 39999 1 --- F1 30985 1
40553 0x228 User Map Address 30 30001 39999 1 --- F1 30982 1
40554 0x229 User Map Address 31 30001 39999 1 --- F1 30983 1
40555 0x22A User Map Address 32 30001 39999 1 --- F1 30980 1
40556 0x22B User Map Address 33 30001 39999 1 --- F1 30981 1
40557 0x22C User Map Address 34 30001 39999 1 --- F1 30978 1
40558 0x22D User Map Address 35 30001 39999 1 --- F1 30979 1
40559 0x22E User Map Address 36 30001 39999 1 --- F1 30186 1
40560 0x22F User Map Address 37 30001 39999 1 --- F1 30285 1
40561 0x230 User Map Address 38 30001 39999 1 --- F1 30286 1
40562 0x231 User Map Address 39 30001 39999 1 --- F1 30298 1
40563 0x232 User Map Address 40 30001 39999 1 --- F1 30299 1
40564 0x233 User Map Address 41 30001 39999 1 --- F1 30288 1
40565 0x234 User Map Address 42 30001 39999 1 --- F1 30289 1
40566 0x235 User Map Address 43 30001 39999 1 --- F1 30317 1
40567 0x236 User Map Address 44 30001 39999 1 --- F1 30291 1
40568 0x237 User Map Address 45 30001 39999 1 --- F1 30296 1
40569 0x238 User Map Address 46 30001 39999 1 --- F1 30297 1
40570 0x239 User Map Address 47 30001 39999 1 --- F1 30300 1
40571 0x23A User Map Address 48 30001 39999 1 --- F1 30301 1
40572 0x23B User Map Address 49 30001 39999 1 --- F1 30328 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-21


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
40573 0x23C User Map Address 50 30001 39999 1 --- F1 30329 1
40574 0x23D User Map Address 51 30001 39999 1 --- F1 30330 1
40575 0x23E User Map Address 52 30001 39999 1 --- F1 30331 1
40576 0x23F User Map Address 53 30001 39999 1 --- F1 30332 1
40577 0x240 User Map Address 54 30001 39999 1 --- F1 30333 1
40578 0x241 User Map Address 55 30001 39999 1 --- F1 30326 1
40579 0x242 User Map Address 56 30001 39999 1 --- F1 30327 1
40580 0x243 User Map Address 57 30001 39999 1 --- F1 30334 1
40581 0x244 User Map Address 58 30001 39999 1 --- F1 30335 1
40582 0x245 User Map Address 59 30001 39999 1 --- F1 30338 1
40583 0x246 User Map Address 60 30001 39999 1 --- F1 30339 1
40584 0x247 User Map Address 61 30001 39999 1 --- F1 30324 1
40585 0x248 User Map Address 62 30001 39999 1 --- F1 30325 1
40586 0x249 User Map Address 63 30001 39999 1 --- F1 30319 1
40587 0x24A User Map Address 64 30001 39999 1 --- F1 30320 1
40588 0x24B User Map Address 65 30001 39999 1 --- F1 30001 1
40589 0x24C User Map Address 66 30001 39999 1 --- F1 30001 1
40590 0x24D User Map Address 67 30001 39999 1 --- F1 30001 1
40591 0x24E User Map Address 68 30001 39999 1 --- F1 30001 1
40592 0x24F User Map Address 69 30001 39999 1 --- F1 30001 1
40593 0x250 User Map Address 70 30001 39999 1 --- F1 30001 1
40594 0x251 User Map Address 71 30001 39999 1 --- F1 30001 1
40595 0x252 User Map Address 72 30001 39999 1 --- F1 30001 1
40596 0x253 User Map Address 73 30001 39999 1 --- F1 30001 1
40597 0x254 User Map Address 74 30001 39999 1 --- F1 30001 1
40598 0x255 User Map Address 75 30001 39999 1 --- F1 30001 1
40599 0x256 User Map Address 76 30001 39999 1 --- F1 30001 1
40600 0x257 User Map Address 77 30001 39999 1 --- F1 30001 1
40601 0x258 User Map Address 78 30001 39999 1 --- F1 30001 1
40602 0x259 User Map Address 79 30001 39999 1 --- F1 30001 1
40603 0x25A User Map Address 80 30001 39999 1 --- F1 30001 1
40604 0x25B User Map Address 81 30001 39999 1 --- F1 30001 1
40605 0x25C User Map Address 82 30001 39999 1 --- F1 30001 1
40606 0x25D User Map Address 83 30001 39999 1 --- F1 30001 1
40607 0x25E User Map Address 84 30001 39999 1 --- F1 30001 1
40608 0x25F User Map Address 85 30001 39999 1 --- F1 30001 1
40609 0x260 User Map Address 86 30001 39999 1 --- F1 30001 1
40610 0x261 User Map Address 87 30001 39999 1 --- F1 30001 1
40611 0x262 User Map Address 88 30001 39999 1 --- F1 30001 1
40612 0x263 User Map Address 89 30001 39999 1 --- F1 30001 1
40613 0x264 User Map Address 90 30001 39999 1 --- F1 30001 1
40614 0x265 User Map Address 91 30001 39999 1 --- F1 30001 1
40615 0x266 User Map Address 92 30001 39999 1 --- F1 30001 1
40616 0x267 User Map Address 93 30001 39999 1 --- F1 30001 1
40617 0x268 User Map Address 94 30001 39999 1 --- F1 30001 1
40618 0x269 User Map Address 95 30001 39999 1 --- F1 30001 1

12-22 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
40619 0x26A User Map Address 96 30001 39999 1 --- F1 30001 1
40620 0x26B User Map Address 97 30001 39999 1 --- F1 30001 1
40621 0x26C User Map Address 98 30001 39999 1 --- F1 30001 1
40622 0x26D User Map Address 99 30001 39999 1 --- F1 30001 1
40623 0x26E User Map Address 100 30001 39999 1 --- F1 30001 1
40624 0x26F User Map Address 101 30001 39999 1 --- F1 30001 1
40625 0x270 User Map Address 102 30001 39999 1 --- F1 30001 1
40626 0x271 User Map Address 103 30001 39999 1 --- F1 30001 1
40627 0x272 User Map Address 104 30001 39999 1 --- F1 30001 1
40628 0x273 User Map Address 105 30001 39999 1 --- F1 30001 1
40629 0x274 User Map Address 106 30001 39999 1 --- F1 30001 1
40630 0x275 User Map Address 107 30001 39999 1 --- F1 30001 1
40631 0x276 User Map Address 108 30001 39999 1 --- F1 30001 1
40632 0x277 User Map Address 109 30001 39999 1 --- F1 30001 1
40633 0x278 User Map Address 110 30001 39999 1 --- F1 30001 1
40634 0x279 User Map Address 111 30001 39999 1 --- F1 30001 1
40635 0x27A User Map Address 112 30001 39999 1 --- F1 30001 1
40636 0x27B User Map Address 113 30001 39999 1 --- F1 30001 1
40637 0x27C User Map Address 114 30001 39999 1 --- F1 30001 1
40638 0x27D User Map Address 115 30001 39999 1 --- F1 30001 1
40639 0x27E User Map Address 116 30001 39999 1 --- F1 30001 1
40640 0x27F User Map Address 117 30001 39999 1 --- F1 30001 1
40641 0x280 User Map Address 118 30001 39999 1 --- F1 30001 1
40642 0x281 User Map Address 119 30001 39999 1 --- F1 30001 1
40643 0x282 User Map Address 120 30001 39999 1 --- F1 30001 1
40644 0x283 User Map Address 121 30001 39999 1 --- F1 30001 1
40645 0x284 User Map Address 122 30001 39999 1 --- F1 30001 1
40646 0x285 User Map Address 123 30001 39999 1 --- F1 30001 1
40647 0x286 User Map Address 124 30001 39999 1 --- F1 30001 1
40648 0x287 User Map Address 125 30001 39999 1 --- F1 30001 1
TRANSIENT RECORDER TRIGGERS
40650 0x289 Trigger On Input 1 0 0xEF02 1 --- F89A 0 1
40651 0x28A Trigger On Input 2 0 0xEF02 1 --- F89A 0 1
40652 0x28B Trigger On Input 3 0 0xEF02 1 --- F89A 0 1
EVENT RECORDER
40649 0x288 Recording of Block Events 0 1 1 --- FC126 1 1
40654 0x28D Recording of Pickup Events 0 1 1 --- FC126 0 1
40655 0x28E Recording of Contact Input 0 1 1 --- FC126 1 1
Events
40656 0x28F Recording of Virtual Input 0 1 1 --- FC126 1 1
Events
40657 0x290 Recording of Remote Inputs 0 1 1 --- FC126 1 1
40658 0x291 Recording of Logic Element 0 1 1 --- FC126 1 1
Events
40660 0x293 Recording of Trip Events 0 1 1 --- FC126 1 1
40661 0x294 Recording of Alarm Events 0 1 1 --- FC126 1 1
40662 0x295 Recording of Control Events 0 1 1 --- FC126 1 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-23


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
40665 0x298 Recording of Dropout Events 0 1 1 --- FC126 0 1
40666 0x299 Recording of Set Time/Date 0 1 1 --- FC126 0 1
Events
40667 0x29A Event Record Selector 1 65535 1 --- F1 1 1
THERMAL PROTECTION
40699 0x2BA Thermal O/L Curve 0 2 1 --- FC236 0 1
TEMPERATURE
40820 0x333 Enable Ambient Temp 0 2 1 --- FC206 0 1
40821 0x334 HI Alarm Level 20 80 1 °C F1 60 1
40822 0x335 Low Alarm Level -40 20 1 °C F4 10 1
40823 0x336 Hysteresis Level 2 10 1 °C F1 2 1
40824 0x337 Time Delay 1 60 1 min F1 1 1
40825 0x338 Output Relays 0 0x7F 1 --- FC198 0 1
TRANSIENT RECORDER
40668 0x29B Trigger on Pickup 0 1 1 --- FC103 0 1
40669 0x29C Trigger on Dropout 0 1 1 --- FC103 0 1
40670 0x29D Trigger on Alarm 0 1 1 --- FC103 0 1
40671 0x29E Trigger on Dropout 0 1 1 --- FC103 0 1
40672 0x29F Trace Memory Channel 0 16 1 --- F26 0 1
Selector
40673 0x2A0 Trace Memory Buffer 0 10 1 --- F1 0 1
Selector
40674 0x2A1 Trace Memory Sample Index 0 6144 1 --- F1 0 1
40676 0x2A3 Trace Memory Trigger 0 100 1 % F1 20 1
Position
40677 0x2A4 Trigger Mode 0 1 1 --- FC148 0 1
40678 0x2A5 Number of Records 0 2 1 --- F95 0 1
40887 0x376 Transient Sampling Rate 0 3 1 --- FC429 0 1
VT FUSE FAIL
40908 0x38B VT Fuse Fail 0 2 1 --- FC140 0 1
RELAY STATUS
40927 0x39E Relay Status 0 1 1 --- F99 0 1
CONTACT INPUT NAMES (1 TO 8)
40961 0x3C0 Input Name 1 0 7 1 --- F22 52a 7
Contact
40970 0x3C9 Input Name 2 0 7 1 --- F22 52b 7
Contact
40979 0x3D2 Input Name 3 0 7 1 --- F22 Input 3 7
40988 0x3DB Input Name 4 0 7 1 --- F22 Input 4 7
40997 0x3E4 Input Name 5 0 7 1 --- F22 Input 5 7
41006 0x3ED Input Name 6 0 7 1 --- F22 Input 6 7
41015 0x3F6 Input Name 7 0 7 1 --- F22 Input 7 7
41024 0x3FF Input Name 8 0 7 1 --- F22 Input 8 7
EDIT SETPOINT GROUP
41113 0x458 Edit Setpoint Group -1 1 1 --- F91 0 1
LOGIC ELEMENTS
41118 0x45D Timer 1 Pickup Delay 0 60000 1 ms F1 0 1
41119 0x45E Timer 1 Dropout Delay 0 60000 1 ms F1 0 1

12-24 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
41120 0x45F Logic Element 1 Function 0 4 1 --- FC205 0 1
41121 0x460 Logic Element 1 Asserted 0 1 1 --- FC103 0 1
41122 0x461 Logic Element 1 Relay 0 0x7F 1 --- FC198 0 1
41126 0x465 Timer 2 Pickup Delay 0 60000 1 ms F1 0 1
41127 0x466 Timer 2 Dropout Delay 0 60000 1 ms F1 0 1
41128 0x467 Logic Element 2 Function 0 4 1 --- FC205 0 1
41129 0x468 Logic Element 2 Asserted 0 1 1 --- FC103 0 1
41130 0x469 Logic Element 2 Relay 0 0x7F 1 --- FC198 0 1
41134 0x46D Timer 3 Pickup Delay 0 60000 1 ms F1 0 1
41135 0x46E Timer 3 Dropout Delay 0 60000 1 ms F1 0 1
41136 0x46F Logic Element 3 Function 0 4 1 --- FC205 0 1
41137 0x470 Logic Element 3 Asserted 0 1 1 --- FC103 0 1
41138 0x471 Logic Element 3 Relay 0 0x7F 1 --- FC198 0 1
41142 0x475 Timer 4 Pickup Delay 0 60000 1 ms F1 0 1
41143 0x476 Timer 4 Dropout Delay 0 60000 1 ms F1 0 1
41144 0x477 Logic Element 4 Function 0 4 1 --- FC205 0 1
41145 0x478 Logic Element 4 Asserted 0 1 1 --- FC103 0 1
41146 0x479 Logic Element 4 Relay 0 0x7F 1 --- FC198 0 1
41150 0x47D Timer 5 Pickup Delay 0 60000 1 ms F1 0 1
41151 0x47E Timer 5 Dropout Delay 0 60000 1 ms F1 0 1
41152 0x47F Logic Element 5 Function 0 4 1 --- FC205 0 1
41153 0x480 Logic Element 5 Asserted 0 1 1 --- FC103 0 1
41154 0x481 Logic Element 5 Relay 0 0x7F 1 --- FC198 0 1
41158 0x485 Timer 6 Pickup Delay 0 60000 1 ms F1 0 1
41159 0x486 Timer 6 Dropout Delay 0 60000 1 ms F1 0 1
41160 0x487 Logic Element 6 Function 0 4 1 --- FC205 0 1
41161 0x488 Logic Element 6 Asserted 0 1 1 --- FC103 0 1
41162 0x489 Logic Element 6 Relay 0 0x7F 1 --- FC198 0 1
41166 0x48D Timer 7 Pickup Delay 0 60000 1 ms F1 0 1
41167 0x48E Timer 7 Dropout Delay 0 60000 1 ms F1 0 1
41168 0x48F Logic Element 7 Function 0 4 1 --- FC205 0 1
41169 0x490 Logic Element 7 Asserted 0 1 1 --- FC103 0 1
41170 0x491 Logic Element 7 Relay 0 0x7F 1 --- FC198 0 1
41174 0x495 Timer 8 Pickup Delay 0 60000 1 ms F1 0 1
41175 0x496 Timer 8 Dropout Delay 0 60000 1 ms F1 0 1
41176 0x497 Logic Element 8 Function 0 4 1 --- FC205 0 1
41177 0x498 Logic Element 8 Asserted 0 1 1 --- FC103 0 1
41178 0x499 Logic Element 8 Relay 0 0x7F 1 --- FC198 0 1
41182 0x49D Timer 9 Pickup Delay 0 60000 1 ms F1 0 1
41183 0x49E Timer 9 Dropout Delay 0 60000 1 ms F1 0 1
41184 0x49F Logic Element 9 Function 0 4 1 --- FC205 0 1
41185 0x4A0 Logic Element 9 Asserted 0 1 1 --- FC103 0 1
41186 0x4A1 Logic Element 9 Relay 0 0x7F 1 --- FC198 0 1
41190 0x4A5 Timer 10 Pickup Delay 0 60000 1 ms F1 0 1
41191 0x4A6 Timer 10 Dropout Delay 0 60000 1 ms F1 0 1
41192 0x4A7 Logic Element 10 Function 0 4 1 --- FC205 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-25


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
41193 0x4A8 Logic Element 10 Asserted 0 1 1 --- FC103 0 1
41194 0x4A9 Logic Element 10 Relay 0 0x7F 1 --- FC198 0 1
41198 0x4AD Timer 11 Pickup Delay 0 60000 1 ms F1 0 1
41199 0x4AE Timer 11 Dropout Delay 0 60000 1 ms F1 0 1
41200 0x4AF Logic Element 11 Function 0 4 1 --- FC205 0 1
41201 0x4B0 Logic Element 11 Asserted 0 1 1 --- FC103 0 1
41202 0x4B1 Logic Element 11 Relay 0 0x7F 1 --- FC198 0 1
41206 0x4B5 Timer 12 Pickup Delay 0 60000 1 ms F1 0 1
41207 0x4B6 Timer 12 Dropout Delay 0 60000 1 ms F1 0 1
41208 0x4B7 Logic Element 12 Function 0 4 1 --- FC205 0 1
41209 0x4B8 Logic Element 12 Asserted 0 1 1 --- FC103 0 1
41210 0x4B9 Logic Element 12 Relay 0 0x7F 1 --- FC198 0 1
41214 0x4BD Timer 13 Pickup Delay 0 60000 1 ms F1 0 1
41215 0x4BE Timer 13 Dropout Delay 0 60000 1 ms F1 0 1
41216 0x4BF Logic Element 13 Function 0 4 1 --- FC205 0 1
41217 0x4C0 Logic Element 13 Asserted 0 1 1 --- FC103 0 1
41218 0x4C1 Logic Element 13 Relay 0 0x7F 1 --- FC198 0 1
41222 0x4C5 Timer 14 Pickup Delay 0 60000 1 ms F1 0 1
41223 0x4C6 Timer 14 Dropout Delay 0 60000 1 ms F1 0 1
41224 0x4C7 Logic Element 14 Function 0 4 1 --- FC205 0 1
41225 0x4C8 Logic Element 14 Asserted 0 1 1 --- FC103 0 1
41226 0x4C9 Logic Element 14 Relay 0 0x7F 1 --- FC198 0 1
41230 0x4CD Timer 15 Pickup Delay 0 60000 1 ms F1 0 1
41231 0x4CE Timer 15 Dropout Delay 0 60000 1 ms F1 0 1
41232 0x4CF Logic Element 15 Function 0 4 1 --- FC205 0 1
41233 0x4D0 Logic Element 15 Asserted 0 1 1 --- FC103 0 1
41234 0x4D1 Logic Element 15 Relay 0 0x7F 1 --- FC198 0 1
41238 0x4D5 Timer 16 Pickup Delay 0 60000 1 ms F1 0 1
41239 0x4D6 Timer 16 Dropout Delay 0 60000 1 ms F1 0 1
41240 0x4D7 Logic Element 16 Function 0 4 1 --- FC205 0 1
41241 0x4D8 Logic Element 16 Asserted 0 1 1 --- FC103 0 1
41242 0x4D9 Logic Element 16 Relay 0 0x7F 1 --- FC198 0 1
CONTACT INPUT ASSIGNMENT
41380 0x563 Remote Reset 0 0xEF02 1 --- F89A 0 1
41386 0x569 Remote Open 0 0xEF02 0 --- F89A 0 1
41387 0x56A Remote Close 0 0xEF02 0 --- F89A 0 1
41388 0x56B Breaker Connected 0 0x49 0 --- FC204B 0 1
41389 0x56C Breaker 52a Contact 0 0x40 0 --- FC204A 0 1
41390 0x56D Breaker 52b Contact 0 0x41 0 --- FC204C 0 1
41391 0x56E Local Mode 0 0xEF02 0 --- F89 0 1
41404 0x57B Set Group 2 Active 0 0xEF02 1 --- F89 0 1
41405 0x57C Block Group Change 0 0xEF02 1 --- F89 0 1
CONTACT INPUT NAMES (9 TO 10)
41435 0x59A Input Name 9 0 7 1 --- F22 Input 9 7
41444 0x5A3 Input Name 10 0 7 1 --- F22 Input 10 7
CONTACT INPUTS

12-26 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
41454 0x5AD Input 9 Debounce Interval 1 64 1 ms F1 2 1
41455 0x5AE Input 10 Debounce Interval 1 64 1 ms F1 2 1
41456 0x5AF Input 1 Debounce Interval 1 64 1 ms F1 2 1
41457 0x5B0 Input 2 Debounce Interval 1 64 1 ms F1 2 1
41458 0x5B1 Input 3 Debounce Interval 1 64 1 ms F1 2 1
41459 0x5B2 Input 4 Debounce Interval 1 64 1 ms F1 2 1
41460 0x5B3 Input 5 Debounce Interval 1 64 1 ms F1 2 1
41461 0x5B4 Input 6 Debounce Interval 1 64 1 ms F1 2 1
41462 0x5B5 Input 7 Debounce Interval 1 64 1 ms F1 2 1
41463 0x5B6 Input 8 Debounce Interval 1 64 1 ms F1 2 1
41465 0x5B8 Select DC Voltage 0 3 1 --- FC123 2 1
FRONT PANEL SETUP
41475 0x5C2 Screen Saver 0 10000 1 min F1C 0 1
LEDs
41498 0x5D9 Breaker Open LED Colour 0 3 1 --- FC157 2 1
41500 0x5DB Breaker Closed LED Colour 0 3 1 --- FC157 2 1
OUTPUT RELAYS
41510 0x5E5 Relay 3 Type 0 1 1 --- FC199 0 1
41511 0x5E6 Relay 4 Type 0 1 1 --- FC199 0 1
41512 0x5E7 Relay 5 Type 0 1 1 --- FC199 0 1
41513 0x5E8 Relay 6 Type 0 1 1 --- FC199 0 1
OUTPUT RELAY BLOCKING
41547 0x60A Block Relay 1 Trip 0 0xEF02 1 --- F89 0 1
41548 0x60B Block Relay 2 Close 0 0xEF02 1 --- F89 0 1
PROGRAMMABLE LEDs
41522 0x5F1 LED 1 Type 0 1 1 --- FC199 0 1
41523 0x5F2 LED 2 Type 0 1 1 --- FC199 0 1
41524 0x5F3 LED 3 Type 0 1 1 --- FC199 0 1
41525 0x5F4 LED 4 Type 0 1 1 --- FC199 0 1
41526 0x5F5 LED 5 Type 0 1 1 --- FC199 0 1
41527 0x5F6 LED 6 Type 0 1 1 --- FC199 0 1
41528 0x5F7 LED 7 Type 0 1 1 --- FC199 0 1
41529 0x5F8 LED 8 Type 0 1 1 --- FC199 0 1
41570 0x621 LED 1 Source 0 0xFFFF 1 --- FC134B 0 1
41572 0x623 LED 2 Source 0 0xFFFF 1 --- FC134B 0 1
41574 0x625 LED 3 Source 0 0xFFFF 1 --- FC134B 0 1
41576 0x627 LED 4 Source 0 0xFFFF 1 --- FC134B 0 1
41578 0x629 LED 5 Source 0 0xFFFF 1 --- FC134B 0 1
41579 0x62A LED 5 Color 0 3 1 --- FC157 3 1
41580 0x62B LED 6 Source 0 0xFFFF 1 --- FC134B 0 1
41581 0x62C LED 6 Color 0 3 1 --- FC157 3 1
41582 0x62D LED 7 Source 0 0xFFFF 1 --- FC134B 0 1
41583 0x62E LED 7 Color 0 3 1 --- FC157 3 1
41584 0x62F LED 8 Source 0 0xFFFF 1 --- FC134B 0 1
41585 0x630 LED 8 Color 0 3 1 --- FC157 3 1
BREAKER TRIP COUNTER

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-27


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42210 0x8A1 Breaker Trip Counter Initial 0 10000 1 --- F1 0 1
Trips
42211 0x8A2 Breaker Trip Counter 0 2 1 --- FC206 0 1
Function
42212 0x8A3 Breaker Trip Counter Limit 1 10000 1 trips F1 1 1
42213 0x8A4 Breaker Trip Counter Relay 0 0x7F 1 --- FC198 0 1
COIL MONITORS
42214 0x8A5 Bypass Breaker Status 0 1 1 --- FC126 0 1
TRIP COIL
42215 0x8A6 Relay1 Coil Monitor Function 0 2 1 --- FC206 0 1
42216 0x8A7 Relay1 Coil Monitor Pickup 1 10 1 s F1 5 1
42217 0x8A8 Relay1 Coil Monitor Relay 0 0x7F 1 --- FC198 0 1
42218 0x8A9 Bypass Breaker Status 0 1 1 --- FC126 0 1
CLOSE COIL
42219 0x8AA Relay2 Coil Monitor Function 0 2 1 --- FC206 0 1
42220 0x8AB Relay2 Coil Monitor Pickup 1 10 1 s F1 5 1
42221 0x8AC Relay2 Coil Monitor Relay 0 0x7F 1 --- FC198 0 1
RELAY 1 TRIP
42222 0x8AD Relay 1 Seal-In 0 999 1 s F3 4 1
RELAY 2 CLOSE
42223 0x8AE Relay 2 Seal-In 0 999 1 s F3 4 1
USER CURVE
42241 0x8C0 User Curve A Parameter 0 1250000 1 s F27 500 2
42243 0x8C2 User Curve B Parameter 0 30000 1 s F27 0 2
42245 0x8C4 User Curve P Parameter 0 30000 1 --- F27 400 2
42247 0x8C6 User Curve Q Parameter 0 20000 1 --- F27 10000 2
42249 0x8C8 User Curve K Parameter 0 1999 1 s F23 0 1
COLD LOAD PICKUP
42225 0x8B0 Cold Load Pickup Function 0 2 1 --- FC206 0 1
42226 0x8B1 Cold Load Pickup Block Time 1 1000 1 s F1 5 1
42227 0x8B2 Outage Time before Cold 1 1000 1 min F1 20 1
Load Pickup
42228 0x8B3 External Cold Load Pickup 0 0xEF02 1 --- F89 0 1
Initiate
42229 0x8B4 Block Phase IOC 1 0 1 1 --- FC103A 0 1
42230 0x8B5 Block Phase IOC 2 0 1 1 --- FC103A 0 1
42231 0x8B6 Block Ground IOC 1 0 1 1 --- FC103A 0 1
42232 0x8B7 Block Ground IOC 2 0 1 1 --- FC103A 0 1
42233 0x8B8 Block Neutral IOC 1 0 1 1 --- FC103A 0 1
42234 0x8B9 Block Neutral IOC 2 0 1 1 --- FC103A 0 1
42235 0x8BA Raise Phase TOC Pickup 0 100 1 % F1 0 1
42236 0x8BB Raise Ground TOC Pickup 0 100 1 % F1 0 1
42237 0x8BC Raise Neutral TOC Pickup 0 100 1 % F1 0 1
42238 0x8BD Output Relays 0 0x7C 1 --- F1 0 1
42239 0x8BE Select Setting Group -1 1 1 --- F91 -1 1
42251 0x8CA Block Sensitive Ground IOC1 0 1 1 --- FC103A 0 1
42252 0x8CB Block Sensitive Ground IOC2 0 1 1 --- FC103A 0 1

12-28 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42253 0x8CC Raise Sensitive Ground TOC 0 100 1 % F1 0 1
Pickup
42254 0x8CD Block Negative Sequence 0 1 1 --- FC103A 0 1
IOC
42255 0x8CE Raise Negative Sequence 0 100 1 % F1 0 1
TOC
BREAKER FAILURE
42262 0x8D5 Breaker Failure Function 0 2 1 --- FC206 0 1
42263 0x8D6 Breaker Failure Delay 1 3 100 1 s F3 10 1
42264 0x8D7 Breaker Failure Current 5 2000 1 x CT F3 100 1
42265 0x8D8 Breaker Failure Delay 2 0 100 1 s F3 0 1
42266 0x8D9 Breaker Failure Relays 0 0x7F 1 --- FC198 0 1
42267 0x8DA Breaker Failure Ext Initiate 0 0xEF02 1 --- F89 0 1
FLEXCURVE A
42278 0x8E5 Flex Curve A 1.03 X PU 0 65535 1 ms F1 0 1
42279 0x8E6 Flex Curve A 1.05 X PU 0 65535 1 ms F1 0 1
42280 0x8E7 Flex Curve A 1.10 X PU 0 65535 1 ms F1 0 1
42281 0x8E8 Flex Curve A 1.20 X PU 0 65535 1 ms F1 0 1
42282 0x8E9 Flex Curve A 1.30 X PU 0 65535 1 ms F1 0 1
42283 0x8EA Flex Curve A 1.40 X PU 0 65535 1 ms F1 0 1
42284 0x8EB Flex Curve A 1.50 X PU 0 65535 1 ms F1 0 1
42285 0x8EC Flex Curve A 1.60 X PU 0 65535 1 ms F1 0 1
42286 0x8ED Flex Curve A 1.70 X PU 0 65535 1 ms F1 0 1
42287 0x8EE Flex Curve A 1.80 X PU 0 65535 1 ms F1 0 1
42288 0x8EF Flex Curve A 1.90 X PU 0 65535 1 ms F1 0 1
42289 0x8F0 Flex Curve A 2.00 X PU 0 65535 1 ms F1 0 1
42290 0x8F1 Flex Curve A 2.10 X PU 0 65535 1 ms F1 0 1
42291 0x8F2 Flex Curve A 2.20 X PU 0 65535 1 ms F1 0 1
42292 0x8F3 Flex Curve A 2.30 X PU 0 65535 1 ms F1 0 1
42293 0x8F4 Flex Curve A 2.40 X PU 0 65535 1 ms F1 0 1
42294 0x8F5 Flex Curve A 2.50 X PU 0 65535 1 ms F1 0 1
42295 0x8F6 Flex Curve A 2.60 X PU 0 65535 1 ms F1 0 1
42296 0x8F7 Flex Curve A 2.70 X PU 0 65535 1 ms F1 0 1
42297 0x8F8 Flex Curve A 2.80 X PU 0 65535 1 ms F1 0 1
42298 0x8F9 Flex Curve A 2.90 X PU 0 65535 1 ms F1 0 1
42299 0x8FA Flex Curve A 3.00 X PU 0 65535 1 ms F1 0 1
42300 0x8FB Flex Curve A 3.10 X PU 0 65535 1 ms F1 0 1
42301 0x8FC Flex Curve A 3.20 X PU 0 65535 1 ms F1 0 1
42302 0x8FD Flex Curve A 3.30 X PU 0 65535 1 ms F1 0 1
42303 0x8FE Flex Curve A 3.40 X PU 0 65535 1 ms F1 0 1
42304 0x8FF Flex Curve A 3.50 X PU 0 65535 1 ms F1 0 1
42305 0x900 Flex Curve A 3.60 X PU 0 65535 1 ms F1 0 1
42306 0x901 Flex Curve A 3.70 X PU 0 65535 1 ms F1 0 1
42307 0x902 Flex Curve A 3.80 X PU 0 65535 1 ms F1 0 1
42308 0x903 Flex Curve A 3.90 X PU 0 65535 1 ms F1 0 1
42309 0x904 Flex Curve A 4.00 X PU 0 65535 1 ms F1 0 1
42310 0x905 Flex Curve A 4.10 X PU 0 65535 1 ms F1 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-29


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42311 0x906 Flex Curve A 4.20 X PU 0 65535 1 ms F1 0 1
42312 0x907 Flex Curve A 4.30 X PU 0 65535 1 ms F1 0 1
42313 0x908 Flex Curve A 4.40 X PU 0 65535 1 ms F1 0 1
42314 0x909 Flex Curve A 4.50 X PU 0 65535 1 ms F1 0 1
42315 0x90A Flex Curve A 4.60 X PU 0 65535 1 ms F1 0 1
42316 0x90B Flex Curve A 4.70 X PU 0 65535 1 ms F1 0 1
42317 0x90C Flex Curve A 4.80 X PU 0 65535 1 ms F1 0 1
42318 0x90D Flex Curve A 4.90 X PU 0 65535 1 ms F1 0 1
42319 0x90E Flex Curve A 5.00 X PU 0 65535 1 ms F1 0 1
42320 0x90F Flex Curve A 5.10 X PU 0 65535 1 ms F1 0 1
42321 0x910 Flex Curve A 5.20 X PU 0 65535 1 ms F1 0 1
42322 0x911 Flex Curve A 5.30 X PU 0 65535 1 ms F1 0 1
42323 0x912 Flex Curve A 5.40 X PU 0 65535 1 ms F1 0 1
42324 0x913 Flex Curve A 5.50 X PU 0 65535 1 ms F1 0 1
42325 0x914 Flex Curve A 5.60 X PU 0 65535 1 ms F1 0 1
42326 0x915 Flex Curve A 5.70 X PU 0 65535 1 ms F1 0 1
42327 0x916 Flex Curve A 5.80 X PU 0 65535 1 ms F1 0 1
42328 0x917 Flex Curve A 5.90 X PU 0 65535 1 ms F1 0 1
42329 0x918 Flex Curve A 6.00 X PU 0 65535 1 ms F1 0 1
42330 0x919 Flex Curve A 6.50 X PU 0 65535 1 ms F1 0 1
42331 0x91A Flex Curve A 7.00 X PU 0 65535 1 ms F1 0 1
42332 0x91B Flex Curve A 7.50 X PU 0 65535 1 ms F1 0 1
42333 0x91C Flex Curve A 8.00 X PU 0 65535 1 ms F1 0 1
42334 0x91D Flex Curve A 8.50 X PU 0 65535 1 ms F1 0 1
42335 0x91E Flex Curve A 9.00 X PU 0 65535 1 ms F1 0 1
42336 0x91F Flex Curve A 9.50 X PU 0 65535 1 ms F1 0 1
42337 0x920 Flex Curve A 10.00 X PU 0 65535 1 ms F1 0 1
42338 0x921 Flex Curve A 10.50 X PU 0 65535 1 ms F1 0 1
42339 0x922 Flex Curve A 11.00 X PU 0 65535 1 ms F1 0 1
42340 0x923 Flex Curve A 11.50 X PU 0 65535 1 ms F1 0 1
42341 0x924 Flex Curve A 12.00 X PU 0 65535 1 ms F1 0 1
42342 0x925 Flex Curve A 12.50 X PU 0 65535 1 ms F1 0 1
42343 0x926 Flex Curve A 13.00 X PU 0 65535 1 ms F1 0 1
42344 0x927 Flex Curve A 13.50 X PU 0 65535 1 ms F1 0 1
42345 0x928 Flex Curve A 14.00 X PU 0 65535 1 ms F1 0 1
42346 0x929 Flex Curve A 14.50 X PU 0 65535 1 ms F1 0 1
42347 0x92A Flex Curve A 15.00 X PU 0 65535 1 ms F1 0 1
42348 0x92B Flex Curve A 15.50 X PU 0 65535 1 ms F1 0 1
42349 0x92C Flex Curve A 16.00 X PU 0 65535 1 ms F1 0 1
42350 0x92D Flex Curve A 16.50 X PU 0 65535 1 ms F1 0 1
42351 0x92E Flex Curve A 17.00 X PU 0 65535 1 ms F1 0 1
42352 0x92F Flex Curve A 17.50 X PU 0 65535 1 ms F1 0 1
42353 0x930 Flex Curve A 18.00 X PU 0 65535 1 ms F1 0 1
42354 0x931 Flex Curve A 18.50 X PU 0 65535 1 ms F1 0 1
42355 0x932 Flex Curve A 19.00 X PU 0 65535 1 ms F1 0 1
42356 0x933 Flex Curve A 19.50 X PU 0 65535 1 ms F1 0 1

12-30 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42357 0x934 Flex Curve A 20.00 X PU 0 65535 1 ms F1 0 1
FLEXCURVE B
42380 0x94B Flex Curve B 1.03 X PU 0 65535 1 ms F1 0 1
42381 0x94C Flex Curve B 1.05 X PU 0 65535 1 ms F1 0 1
42382 0x94D Flex Curve B 1.10 X PU 0 65535 1 ms F1 0 1
42383 0x94E Flex Curve B 1.20 X PU 0 65535 1 ms F1 0 1
42384 0x94F Flex Curve B 1.30 X PU 0 65535 1 ms F1 0 1
42385 0x950 Flex Curve B 1.40 X PU 0 65535 1 ms F1 0 1
42386 0x951 Flex Curve B 1.50 X PU 0 65535 1 ms F1 0 1
42387 0x952 Flex Curve B 1.60 X PU 0 65535 1 ms F1 0 1
42388 0x953 Flex Curve B 1.70 X PU 0 65535 1 ms F1 0 1
42389 0x954 Flex Curve B 1.80 X PU 0 65535 1 ms F1 0 1
42390 0x955 Flex Curve B 1.90 X PU 0 65535 1 ms F1 0 1
42391 0x956 Flex Curve B 2.00 X PU 0 65535 1 ms F1 0 1
42392 0x957 Flex Curve B 2.10 X PU 0 65535 1 ms F1 0 1
42393 0x958 Flex Curve B 2.20 X PU 0 65535 1 ms F1 0 1
42394 0x959 Flex Curve B 2.30 X PU 0 65535 1 ms F1 0 1
42395 0x95A Flex Curve B 2.40 X PU 0 65535 1 ms F1 0 1
42396 0x95B Flex Curve B 2.50 X PU 0 65535 1 ms F1 0 1
42397 0x95C Flex Curve B 2.60 X PU 0 65535 1 ms F1 0 1
42398 0x95D Flex Curve B 2.70 X PU 0 65535 1 ms F1 0 1
42399 0x95E Flex Curve B 2.80 X PU 0 65535 1 ms F1 0 1
42400 0x95F Flex Curve B 2.90 X PU 0 65535 1 ms F1 0 1
42401 0x960 Flex Curve B 3.00 X PU 0 65535 1 ms F1 0 1
42402 0x961 Flex Curve B 3.10 X PU 0 65535 1 ms F1 0 1
42403 0x962 Flex Curve B 3.20 X PU 0 65535 1 ms F1 0 1
42404 0x963 Flex Curve B 3.30 X PU 0 65535 1 ms F1 0 1
42405 0x964 Flex Curve B 3.40 X PU 0 65535 1 ms F1 0 1
42406 0x965 Flex Curve B 3.50 X PU 0 65535 1 ms F1 0 1
42407 0x966 Flex Curve B 3.60 X PU 0 65535 1 ms F1 0 1
42408 0x967 Flex Curve B 3.70 X PU 0 65535 1 ms F1 0 1
42409 0x968 Flex Curve B 3.80 X PU 0 65535 1 ms F1 0 1
42410 0x969 Flex Curve B 3.90 X PU 0 65535 1 ms F1 0 1
42411 0x96A Flex Curve B 4.00 X PU 0 65535 1 ms F1 0 1
42412 0x96B Flex Curve B 4.10 X PU 0 65535 1 ms F1 0 1
42413 0x96C Flex Curve B 4.20 X PU 0 65535 1 ms F1 0 1
42414 0x96D Flex Curve B 4.30 X PU 0 65535 1 ms F1 0 1
42415 0x96E Flex Curve B 4.40 X PU 0 65535 1 ms F1 0 1
42416 0x96F Flex Curve B 4.50 X PU 0 65535 1 ms F1 0 1
42417 0x970 Flex Curve B 4.60 X PU 0 65535 1 ms F1 0 1
42418 0x971 Flex Curve B 4.70 X PU 0 65535 1 ms F1 0 1
42419 0x972 Flex Curve B 4.80 X PU 0 65535 1 ms F1 0 1
42420 0x973 Flex Curve B 4.90 X PU 0 65535 1 ms F1 0 1
42421 0x974 Flex Curve B 5.00 X PU 0 65535 1 ms F1 0 1
42422 0x975 Flex Curve B 5.10 X PU 0 65535 1 ms F1 0 1
42423 0x976 Flex Curve B 5.20 X PU 0 65535 1 ms F1 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-31


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42424 0x977 Flex Curve B 5.30 X PU 0 65535 1 ms F1 0 1
42425 0x978 Flex Curve B 5.40 X PU 0 65535 1 ms F1 0 1
42426 0x979 Flex Curve B 5.50 X PU 0 65535 1 ms F1 0 1
42427 0x97A Flex Curve B 5.60 X PU 0 65535 1 ms F1 0 1
42428 0x97B Flex Curve B 5.70 X PU 0 65535 1 ms F1 0 1
42429 0x97C Flex Curve B 5.80 X PU 0 65535 1 ms F1 0 1
42430 0x97D Flex Curve B 5.90 X PU 0 65535 1 ms F1 0 1
42431 0x97E Flex Curve B 6.00 X PU 0 65535 1 ms F1 0 1
42432 0x97F Flex Curve B 6.50 X PU 0 65535 1 ms F1 0 1
42433 0x980 Flex Curve B 7.00 X PU 0 65535 1 ms F1 0 1
42434 0x981 Flex Curve B 7.50 X PU 0 65535 1 ms F1 0 1
42435 0x982 Flex Curve B 8.00 X PU 0 65535 1 ms F1 0 1
42436 0x983 Flex Curve B 8.50 X PU 0 65535 1 ms F1 0 1
42437 0x984 Flex Curve B 9.00 X PU 0 65535 1 ms F1 0 1
42438 0x985 Flex Curve B 9.50 X PU 0 65535 1 ms F1 0 1
42439 0x986 Flex Curve B 10.00 X PU 0 65535 1 ms F1 0 1
42440 0x987 Flex Curve B 10.50 X PU 0 65535 1 ms F1 0 1
42441 0x988 Flex Curve B 11.00 X PU 0 65535 1 ms F1 0 1
42442 0x989 Flex Curve B 11.50 X PU 0 65535 1 ms F1 0 1
42443 0x98A Flex Curve B 12.00 X PU 0 65535 1 ms F1 0 1
42444 0x98B Flex Curve B 12.50 X PU 0 65535 1 ms F1 0 1
42445 0x98C Flex Curve B 13.00 X PU 0 65535 1 ms F1 0 1
42446 0x98D Flex Curve B 13.50 X PU 0 65535 1 ms F1 0 1
42447 0x98E Flex Curve B 14.00 X PU 0 65535 1 ms F1 0 1
42448 0x98F Flex Curve B 14.50 X PU 0 65535 1 ms F1 0 1
42449 0x990 Flex Curve B 15.00 X PU 0 65535 1 ms F1 0 1
42450 0x991 Flex Curve B 15.50 X PU 0 65535 1 ms F1 0 1
42451 0x992 Flex Curve B 16.00 X PU 0 65535 1 ms F1 0 1
42452 0x993 Flex Curve B 16.50 X PU 0 65535 1 ms F1 0 1
42453 0x994 Flex Curve B 17.00 X PU 0 65535 1 ms F1 0 1
42454 0x995 Flex Curve B 17.50 X PU 0 65535 1 ms F1 0 1
42455 0x996 Flex Curve B 18.00 X PU 0 65535 1 ms F1 0 1
42456 0x997 Flex Curve B 18.50 X PU 0 65535 1 ms F1 0 1
42457 0x998 Flex Curve B 19.00 X PU 0 65535 1 ms F1 0 1
42458 0x999 Flex Curve B 19.50 X PU 0 65535 1 ms F1 0 1
42459 0x99A Flex Curve B 20.00 X PU 0 65535 1 ms F1 0 1
VIRTUAL INPUT NAMES
42884 0xB43 Virtual Input Name 1 0 9 1 --- F22 Virtual IN 1 9
42893 0xB4C Virtual Input Name 2 0 9 1 --- F22 Virtual IN 2 9
42902 0xB55 Virtual Input Name 3 0 9 1 --- F22 Virtual IN 3 9
42911 0xB5E Virtual Input Name 4 0 9 1 --- F22 Virtual IN 4 9
42920 0xB67 Virtual Input Name 5 0 9 1 --- F22 Virtual IN 5 9
42929 0xB70 Virtual Input Name 6 0 9 1 --- F22 Virtual IN 6 9
42938 0xB79 Virtual Input Name 7 0 9 1 --- F22 Virtual IN 7 9
42947 0xB82 Virtual Input Name 8 0 9 1 --- F22 Virtual IN 8 9
42956 0xB8B Virtual Input Name 9 0 9 1 --- F22 Virtual IN 9 9

12-32 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42965 0xB94 Virtual Input Name 10 0 9 1 --- F22 Virtual IN 9
10
42974 0xB9D Virtual Input Name 11 0 9 1 --- F22 Virtual IN 9
11
42983 0xBA6 Virtual Input Name 12 0 9 1 --- F22 Virtual IN 9
12
42992 0xBAF Virtual Input Name 13 0 9 1 --- F22 Virtual IN 9
13
43001 0xBB8 Virtual Input Name 14 0 9 1 --- F22 Virtual IN 9
14
43010 0xBC1 Virtual Input Name 15 0 9 1 --- F22 Virtual IN 9
15
43019 0xBCA Virtual Input Name 16 0 9 1 --- F22 Virtual IN 9
16
43028 0xBD3 Virtual Input Name 17 0 9 1 --- F22 Virtual IN 9
17
43037 0xBDC Virtual Input Name 18 0 9 1 --- F22 Virtual IN 9
18
43046 0xBE5 Virtual Input Name 19 0 9 1 --- F22 Virtual IN 9
19
43055 0xBEE Virtual Input Name 20 0 9 1 --- F22 Virtual IN 9
20
43064 0xBF7 Virtual Input Name 21 0 9 1 --- F22 Virtual IN 9
21
43073 0xC00 Virtual Input Name 22 0 9 1 --- F22 Virtual IN 9
22
43082 0xC09 Virtual Input Name 23 0 9 1 --- F22 Virtual IN 9
23
43091 0xC12 Virtual Input Name 24 0 9 1 --- F22 Virtual IN 9
24
43100 0xC1B Virtual Input Name 25 0 9 1 --- F22 Virtual IN 9
25
43109 0xC24 Virtual Input Name 26 0 9 1 --- F22 Virtual IN 9
26
43118 0xC2D Virtual Input Name 27 0 9 1 --- F22 Virtual IN 9
27
43127 0xC36 Virtual Input Name 28 0 9 1 --- F22 Virtual IN 9
28
43136 0xC3F Virtual Input Name 29 0 9 1 --- F22 Virtual IN 9
29
43145 0xC48 Virtual Input Name 30 0 9 1 --- F22 Virtual IN 9
30
43154 0xC51 Virtual Input Name 31 0 9 1 --- F22 Virtual IN 9
31
43163 0xC5A Virtual Input Name 32 0 9 1 --- F22 Virtual IN 9
32
SIMULATION
NEGATIVE SEQUENCE TOC1
43691 0xE6A Neg Seq TOC1 Func 0 3 1 --- FC197 0 1
43692 0xE6B Neg Seq TOC1 PkP 5 2000 1 x CT F3 100 1
43693 0xE6C Neg Seq TOC1 Curve 0 15 1 --- F36 0 1
43694 0xE6D Neg Seq TOC1 TDM 5 5000 1 --- F3 100 1
43695 0xE6E Neg Seg TOC1 Reset 0 1 1 --- F68 0 1
43696 0xE6F Neg Seq TOC1 Relays 0 0x7F 1 --- FC198 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-33


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
PHASE OVERVOLTAGE2
43733 0xE94 Phase OV 2 Function 0 3 1 --- FC197 0 1
43734 0xE95 Phase OV 2 Pickup 0 125 1 x VT F3 125 1
43735 0xE96 Phase OV 2 Delay 0 60000 1 s F3 200 1
43736 0xE97 Phase OV 2 Phases 1 3 1 --- F92 1 1
PHASE UNDERVOLTAGE2
43737 0xE98 Phase UV 2 Function 0 3 1 --- FC197 0 1
43738 0xE99 Phase UV 2 Pickup 0 125 1 x VT F3 75 1
43739 0xE9A Phase UV 2 Curve 0 1 1 --- F93 1 1
43740 0xE9B Phase UV 2 Delay 0 60000 1 s F3 200 1
43741 0xE9C Phase UV 2 Phases 1 3 1 --- F92 1 1
43742 0xE9D Phase UV 2 Min Voltage 0 125 1 x VT F3 30 1
PHASE OVERVOLTAGE2 (RELAYS & BLOCKS)
43743 0xE9E Phase OV 2 Relays 0 0x7F 1 --- FC198 0 1
43744 0xE9F Phase OV 2 Block 1 0 0xEF02 1 --- F89 0 1
43745 0xEA0 Phase OV 2 Block 1 0 0xEF02 1 --- F89 0 1
43746 0xEA1 Phase OV 2 Block 1 0 0xEF02 1 --- F89 0 1
PHASE UNDERVOLTAGE2 (RELAYS & BLOCKS)
43747 0xEA2 Phase UV 2 Relays 0 0x7F 1 --- FC198 0 1
43748 0xEA3 Phase UV 2 Block 1 0 0xEF02 1 --- F89 0 1
43749 0xEA4 Phase UV 2 Block 1 0 0xEF02 1 --- F89 0 1
43750 0xEA5 Phase UV 2 Block 1 0 0xEF02 1 --- F89 0 1
NEUTRAL DIRECTIONAL
43751 0xEA6 NDir Block OC Dir UN 0 1 1 --- FC126 0 1
GROUND DIRECTIONAL
42556 0x9FB Ground Directional Function 0 3 1 --- FC207 0 1
43752 0xEA7 GDir Block OC Dir UN 0 1 1 --- FC126 0 1
PHASE DIRECTIONAL
43753 0xEA8 Pha Dir Function 0 3 1 --- FC207 0 1
43754 0xEA9 Pha Dir Polarizing 1 3 1 --- F96 1 1
43755 0xEAA Pha Dir MTA 0 359 1 ° F1 30 1
43756 0xEAB Min POL Voltage 5 125 1 x VT F3 5 1
43757 0xEAC Blk OC Undthrld 0 1 1 --- FC126 1 1
43758 0xEAD Pha Dir Relays 0 0x7F 1 --- FC198 0 1
43759 0xEAE Ph Dir Block 1 0 0xEF02 1 --- F89 0 1
43760 0xEAF Ph Dir Block 2 0 0xEF02 1 --- F89 0 1
43761 0xEB0 Ph Dir Block 3 0 0xEF02 1 --- F89 0 1
FORCE VIRTUAL INPUTS
43764 0xEB3 Force Virtual Input 1 0 1 1 --- FC103 0 1
43765 0xEB4 Force Virtual Input 2 0 1 1 --- FC103 0 1
43766 0xEB5 Force Virtual Input 3 0 1 1 --- FC103 0 1
43767 0xEB6 Force Virtual Input 4 0 1 1 --- FC103 0 1
43768 0xEB7 Force Virtual Input 5 0 1 1 --- FC103 0 1
43769 0xEB8 Force Virtual Input 6 0 1 1 --- FC103 0 1
43770 0xEB9 Force Virtual Input 7 0 1 1 --- FC103 0 1
43771 0xEBA Force Virtual Input 8 0 1 1 --- FC103 0 1

12-34 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
43772 0xEBB Force Virtual Input 9 0 1 1 --- FC103 0 1
43773 0xEBC Force Virtual Input 10 0 1 1 --- FC103 0 1
43774 0xEBD Force Virtual Input 11 0 1 1 --- FC103 0 1
43775 0xEBE Force Virtual Input 12 0 1 1 --- FC103 0 1
43776 0xEBF Force Virtual Input 13 0 1 1 --- FC103 0 1
43777 0xEC0 Force Virtual Input 14 0 1 1 --- FC103 0 1
43778 0xEC1 Force Virtual Input 15 0 1 1 --- FC103 0 1
43779 0xEC2 Force Virtual Input 16 0 1 1 --- FC103 0 1
43780 0xEC3 Force Virtual Input 17 0 1 1 --- FC103 0 1
43781 0xEC4 Force Virtual Input 18 0 1 1 --- FC103 0 1
43782 0xEC5 Force Virtual Input 19 0 1 1 --- FC103 0 1
43783 0xEC6 Force Virtual Input 20 0 1 1 --- FC103 0 1
43784 0xEC7 Force Virtual Input 21 0 1 1 --- FC103 0 1
43785 0xEC8 Force Virtual Input 22 0 1 1 --- FC103 0 1
43786 0xEC9 Force Virtual Input 23 0 1 1 --- FC103 0 1
43787 0xECA Force Virtual Input 24 0 1 1 --- FC103 0 1
43788 0xECB Force Virtual Input 25 0 1 1 --- FC103 0 1
43789 0xECC Force Virtual Input 26 0 1 1 --- FC103 0 1
43790 0xECD Force Virtual Input 27 0 1 1 --- FC103 0 1
43791 0xECE Force Virtual Input 28 0 1 1 --- FC103 0 1
43792 0xECF Force Virtual Input 29 0 1 1 --- FC103 0 1
43793 0xED0 Force Virtual Input 30 0 1 1 --- FC103 0 1
43794 0xED1 Force Virtual Input 31 0 1 1 --- FC103 0 1
43795 0xED2 Force Virtual Input 32 0 1 1 --- FC103 0 1
DNP OVER ETHERNET PORT
43836 0xEFB DNP/Ethernet Channel 1 0 2 1 --- F87 0 1
Port
43837 0xEFC DNP/Ethernet Channel 2 0 2 1 --- F87 0 1
Port
IEC60870-5-104 PROTOCOL
43838 0xEFD IEC 60870-5-104 Function 0 1 1 --- FC126 0 1
43839 0xEFE IEC TCP Port 1 65535 1 --- F1 2404 1
43840 0xEFF IEC Common Address of 0 65535 1 --- F1 0 1
ASDU
43841 0xF00 IEC Cyclic Data Period 0 65535 1 s F1 60 1
43842 0xF01 IEC TCP Connection Timeout 10 300 1 s F1 120 1
43843 0xF02 Object Information Address 1 16777215 1 --- F9 1000 2
Binary
43845 0xF04 Object Information Address 1 16777215 1 --- F9 2000 2
Analog
43847 0xF06 Object Information Address 1 16777215 1 --- F9 3000 2
Counters
43849 0xF08 Object Information Address 1 16777215 1 --- F9 4000 2
Command
DNP / IEC60870-5-104 SHARED SETTINGS
43851 0xF0A DNP Address 0 65519 1 --- F1 0 1
43852 0xF0B DNP Client Address 1 0 0xFFFFFFFF 1 --- FC150 0 2
43854 0xF0D DNP Client Address 2 0 0xFFFFFFFF 1 --- FC150 0 2

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-35


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
43856 0xF0F DNP Client Address 3 0 0xFFFFFFFF 1 --- FC150 0 2
43858 0xF11 DNP Client Address 4 0 0xFFFFFFFF 1 --- FC150 0 2
43860 0xF13 DNP Client Address 5 0 0xFFFFFFFF 1 --- FC150 0 2
43862 0xF15 DNP TCP/UDP Port Number 0 65535 1 --- F1 20000 1
43863 0xF16 DNP Unsolicited Response 0 1 1 --- FC126 0 1
Function
43864 0xF17 DNP Unsolicited Response 0 60 1 s F1 5 1
Timeout
43865 0xF18 DNP Unsolicited Response 1 255 1 --- F1 10 1
Maximum Retries
43866 0xF19 DNP Unsolicited Response 0 65519 1 --- F1 1 1
Destination Address
43867 0xF1A DNP Time Sync IIN Period 1 10080 1 min F1 1440 1
43868 0xF1B DNP Message Fragment Size 30 2048 1 --- F1 240 1
43869 0xF1C DNP Object 1 Default 1 2 1 --- F1 2 1
Variation
43870 0xF1D DNP Object 2 Default 1 2 1 --- F1 2 1
Variation
43871 0xF1E DNP Object 20 Default 1 6 1 --- F78 1 1
Variation
43872 0xF1F DNP Object 21 Default 1 10 1 --- F79 1 1
Variation
43873 0xF20 DNP Object 22 Default 1 6 1 --- F80 1 1
Variation
43874 0xF21 DNP Object 23 Default 1 6 1 --- F81 1 1
Variation
43875 0xF22 DNP Object 30 Default 1 4 1 --- F82 1 1
Variation
43876 0xF23 DNP Object 32 Default 1 4 1 --- F83 1 1
Variation
43877 0xF24 DNP TCP Connection 10 300 1 s F1 120 1
Timeout
DNP / IEC60870-5-103 / IEC60870-5-104 BINARY INPUTS
43878 0xF25 Binary Input Point 0 Entry 0 0xFFFF 1 --- FC134B 0 1
43879 0xF26 Binary Input Point 1 Entry 0 0xFFFF 1 --- FC134B 0 1
43880 0xF27 Binary Input Point 2 Entry 0 0xFFFF 1 --- FC134B 0 1
43881 0xF28 Binary Input Point 3 Entry 0 0xFFFF 1 --- FC134B 0 1
43882 0xF29 Binary Input Point 4 Entry 0 0xFFFF 1 --- FC134B 0 1
43883 0xF2A Binary Input Point 5 Entry 0 0xFFFF 1 --- FC134B 0 1
43884 0xF2B Binary Input Point 6 Entry 0 0xFFFF 1 --- FC134B 0 1
43885 0xF2C Binary Input Point 7 Entry 0 0xFFFF 1 --- FC134B 0 1
43886 0xF2D Binary Input Point 8 Entry 0 0xFFFF 1 --- FC134B 0 1
43887 0xF2E Binary Input Point 9 Entry 0 0xFFFF 1 --- FC134B 0 1
43888 0xF2F Binary Input Point 10 Entry 0 0xFFFF 1 --- FC134B 0 1
43889 0xF30 Binary Input Point 11 Entry 0 0xFFFF 1 --- FC134B 0 1
43890 0xF31 Binary Input Point 12 Entry 0 0xFFFF 1 --- FC134B 0 1
43891 0xF32 Binary Input Point 13 Entry 0 0xFFFF 1 --- FC134B 0 1
43892 0xF33 Binary Input Point 14 Entry 0 0xFFFF 1 --- FC134B 0 1
43893 0xF34 Binary Input Point 15 Entry 0 0xFFFF 1 --- FC134B 0 1
43894 0xF35 Binary Input Point 16 Entry 0 0xFFFF 1 --- FC134B 0 1
43895 0xF36 Binary Input Point 17 Entry 0 0xFFFF 1 --- FC134B 0 1

12-36 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
43896 0xF37 Binary Input Point 18 Entry 0 0xFFFF 1 --- FC134B 0 1
43897 0xF38 Binary Input Point 19 Entry 0 0xFFFF 1 --- FC134B 0 1
43898 0xF39 Binary Input Point 20 Entry 0 0xFFFF 1 --- FC134B 0 1
43899 0xF3A Binary Input Point 21 Entry 0 0xFFFF 1 --- FC134B 0 1
43900 0xF3B Binary Input Point 22 Entry 0 0xFFFF 1 --- FC134B 0 1
43901 0xF3C Binary Input Point 23 Entry 0 0xFFFF 1 --- FC134B 0 1
43902 0xF3D Binary Input Point 24 Entry 0 0xFFFF 1 --- FC134B 0 1
43903 0xF3E Binary Input Point 25 Entry 0 0xFFFF 1 --- FC134B 0 1
43904 0xF3F Binary Input Point 26 Entry 0 0xFFFF 1 --- FC134B 0 1
43905 0xF40 Binary Input Point 27 Entry 0 0xFFFF 1 --- FC134B 0 1
43906 0xF41 Binary Input Point 28 Entry 0 0xFFFF 1 --- FC134B 0 1
43907 0xF42 Binary Input Point 29 Entry 0 0xFFFF 1 --- FC134B 0 1
43908 0xF43 Binary Input Point 30 Entry 0 0xFFFF 1 --- FC134B 0 1
43909 0xF44 Binary Input Point 31 Entry 0 0xFFFF 1 --- FC134B 0 1
43910 0xF45 Binary Input Point 32 Entry 0 0xFFFF 1 --- FC134B 0 1
43911 0xF46 Binary Input Point 33 Entry 0 0xFFFF 1 --- FC134B 0 1
43912 0xF47 Binary Input Point 34 Entry 0 0xFFFF 1 --- FC134B 0 1
43913 0xF48 Binary Input Point 35 Entry 0 0xFFFF 1 --- FC134B 0 1
43914 0xF49 Binary Input Point 36 Entry 0 0xFFFF 1 --- FC134B 0 1
43915 0xF4A Binary Input Point 37 Entry 0 0xFFFF 1 --- FC134B 0 1
43916 0xF4B Binary Input Point 38 Entry 0 0xFFFF 1 --- FC134B 0 1
43917 0xF4C Binary Input Point 39 Entry 0 0xFFFF 1 --- FC134B 0 1
43918 0xF4D Binary Input Point 40 Entry 0 0xFFFF 1 --- FC134B 0 1
43919 0xF4E Binary Input Point 41 Entry 0 0xFFFF 1 --- FC134B 0 1
43920 0xF4F Binary Input Point 42 Entry 0 0xFFFF 1 --- FC134B 0 1
43921 0xF50 Binary Input Point 43 Entry 0 0xFFFF 1 --- FC134B 0 1
43922 0xF51 Binary Input Point 44 Entry 0 0xFFFF 1 --- FC134B 0 1
43923 0xF52 Binary Input Point 45 Entry 0 0xFFFF 1 --- FC134B 0 1
43924 0xF53 Binary Input Point 46 Entry 0 0xFFFF 1 --- FC134B 0 1
43925 0xF54 Binary Input Point 47 Entry 0 0xFFFF 1 --- FC134B 0 1
43926 0xF55 Binary Input Point 48 Entry 0 0xFFFF 1 --- FC134B 0 1
43927 0xF56 Binary Input Point 49 Entry 0 0xFFFF 1 --- FC134B 0 1
43928 0xF57 Binary Input Point 50 Entry 0 0xFFFF 1 --- FC134B 0 1
43929 0xF58 Binary Input Point 51 Entry 0 0xFFFF 1 --- FC134B 0 1
43930 0xF59 Binary Input Point 52 Entry 0 0xFFFF 1 --- FC134B 0 1
43931 0xF5A Binary Input Point 53 Entry 0 0xFFFF 1 --- FC134B 0 1
43932 0xF5B Binary Input Point 54 Entry 0 0xFFFF 1 --- FC134B 0 1
43933 0xF5C Binary Input Point 55 Entry 0 0xFFFF 1 --- FC134B 0 1
43934 0xF5D Binary Input Point 56 Entry 0 0xFFFF 1 --- FC134B 0 1
43935 0xF5E Binary Input Point 57 Entry 0 0xFFFF 1 --- FC134B 0 1
43936 0xF5F Binary Input Point 58 Entry 0 0xFFFF 1 --- FC134B 0 1
43937 0xF60 Binary Input Point 59 Entry 0 0xFFFF 1 --- FC134B 0 1
43938 0xF61 Binary Input Point 60 Entry 0 0xFFFF 1 --- FC134B 0 1
43939 0xF62 Binary Input Point 61 Entry 0 0xFFFF 1 --- FC134B 0 1
43940 0xF63 Binary Input Point 62 Entry 0 0xFFFF 1 --- FC134B 0 1
43941 0xF64 Binary Input Point 63 Entry 0 0xFFFF 1 --- FC134B 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-37


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
DNP / IEC60870-5-104 BINARY OUTPUTS
44070 0xFE5 Binary Output Point 0 ON 0 40 1 --- F86 0 1
44071 0xFE6 Binary Output Point 0 OFF 0 40 1 --- F86 0 1
44072 0xFE7 Binary Output Point 1 ON 0 40 1 --- F86 0 1
44073 0xFE8 Binary Output Point 1 OFF 0 40 1 --- F86 0 1
44074 0xFE9 Binary Output Point 2 ON 0 40 1 --- F86 0 1
44075 0xFEA Binary Output Point 2 OFF 0 40 1 --- F86 0 1
44076 0xFEB Binary Output Point 3 ON 0 40 1 --- F86 0 1
44077 0xFEC Binary Output Point 3 OFF 0 40 1 --- F86 0 1
44078 0xFED Binary Output Point 4 ON 0 40 1 --- F86 0 1
44079 0xFEE Binary Output Point 4 OFF 0 40 1 --- F86 0 1
44080 0xFEF Binary Output Point 5 ON 0 40 1 --- F86 0 1
44081 0xFF0 Binary Output Point 5 OFF 0 40 1 --- F86 0 1
44082 0xFF1 Binary Output Point 6 ON 0 40 1 --- F86 0 1
44083 0xFF2 Binary Output Point 6 OFF 0 40 1 --- F86 0 1
44084 0xFF3 Binary Output Point 7 ON 0 40 1 --- F86 0 1
44085 0xFF4 Binary Output Point 7 OFF 0 40 1 --- F86 0 1
44086 0xFF5 Binary Output Point 8 ON 0 40 1 --- F86 0 1
44087 0xFF6 Binary Output Point 8 OFF 0 40 1 --- F86 0 1
44088 0xFF7 Binary Output Point 9 ON 0 40 1 --- F86 0 1
44089 0xFF8 Binary Output Point 9 OFF 0 40 1 --- F86 0 1
44090 0xFF9 Binary Output Point 10 ON 0 40 1 --- F86 0 1
44091 0xFFA Binary Output Point 10 OFF 0 40 1 --- F86 0 1
44092 0xFFB Binary Output Point 11 ON 0 40 1 --- F86 0 1
44093 0xFFC Binary Output Point 11 OFF 0 40 1 --- F86 0 1
44094 0xFFD Binary Output Point 12 ON 0 40 1 --- F86 0 1
44095 0xFFE Binary Output Point 12 OFF 0 40 1 --- F86 0 1
44096 0xFFF Binary Output Point 13 ON 0 40 1 --- F86 0 1
44097 0x1000 Binary Output Point 13 OFF 0 40 1 --- F86 0 1
44098 0x1001 Binary Output Point 14 ON 0 40 1 --- F86 0 1
44099 0x1002 Binary Output Point 14 OFF 0 40 1 --- F86 0 1
44100 0x1003 Binary Output Point 15 ON 0 40 1 --- F86 0 1
44101 0x1004 Binary Output Point 15 OFF 0 40 1 --- F86 0 1
DNP / IEC60870-5-104 ANALOG INPUTS
43942 0xF65 Analog Input Point 0 Entry 0 251 1 --- F88 0 1
43943 0xF66 Analog Input Point 0 Scale 1 9 1 --- F85 4 1
Factor
43944 0xF67 Analog Input Point 0 0 100000000 1 --- F9 30000 2
Deadband
43946 0xF69 Analog Input Point 1 Entry 0 251 1 --- F88 0 1
43947 0xF6A Analog Input Point 1 Scale 1 9 1 --- F85 4 1
Factor
43948 0xF6B Analog Input Point 1 0 100000000 1 --- F9 30000 2
Deadband
43950 0xF6D Analog Input Point 2 Entry 0 251 1 --- F88 0 1
43951 0xF6E Analog Input Point 2 Scale 1 9 1 --- F85 4 1
Factor

12-38 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
43952 0xF6F Analog Input Point 2 0 100000000 1 --- F9 30000 2
Deadband
43954 0xF71 Analog Input Point 3 Entry 0 251 1 --- F88 0 1
43955 0xF72 Analog Input Point 3 Scale 1 9 1 --- F85 4 1
Factor
43956 0xF73 Analog Input Point 3 0 100000000 1 --- F9 30000 2
Deadband
43958 0xF75 Analog Input Point 4 Entry 0 251 1 --- F88 0 1
43959 0xF76 Analog Input Point 4 Scale 1 9 1 --- F85 4 1
Factor
43960 0xF77 Analog Input Point 4 0 100000000 1 --- F9 30000 2
Deadband
43962 0xF79 Analog Input Point 5 Entry 0 251 1 --- F88 0 1
43963 0xF7A Analog Input Point 5 Scale 1 9 1 --- F85 4 1
Factor
43964 0xF7B Analog Input Point 5 0 100000000 1 --- F9 30000 2
Deadband
43966 0xF7D Analog Input Point 6 Entry 0 251 1 --- F88 0 1
43967 0xF7E Analog Input Point 6 Scale 1 9 1 --- F85 4 1
Factor
43968 0xF7F Analog Input Point 6 0 100000000 1 --- F9 30000 2
Deadband
43970 0xF81 Analog Input Point 7 Entry 0 251 1 --- F88 0 1
43971 0xF82 Analog Input Point 7 Scale 1 9 1 --- F85 4 1
Factor
43972 0xF83 Analog Input Point 7 0 100000000 1 --- F9 30000 2
Deadband
43974 0xF85 Analog Input Point 8 Entry 0 251 1 --- F88 0 1
43975 0xF86 Analog Input Point 8 Scale 1 9 1 --- F85 4 1
Factor
43976 0xF87 Analog Input Point 8 0 100000000 1 --- F9 30000 2
Deadband
43978 0xF89 Analog Input Point 9 Entry 0 251 1 --- F88 0 1
43979 0xF8A Analog Input Point 9 Scale 1 9 1 --- F85 4 1
Factor
43980 0xF8B Analog Input Point 9 0 100000000 1 --- F9 30000 2
Deadband
43982 0xF8D Analog Input Point 10 Entry 0 251 1 --- F88 0 1
43983 0xF8E Analog Input Point 10 Scale 1 9 1 --- F85 4 1
Factor
43984 0xF8F Analog Input Point 10 0 100000000 1 --- F9 30000 2
Deadband
43986 0xF91 Analog Input Point 11 Entry 0 251 1 --- F88 0 1
43987 0xF92 Analog Input Point 11 Scale 1 9 1 --- F85 4 1
Factor
43988 0xF93 Analog Input Point 11 0 100000000 1 --- F9 30000 2
Deadband
43990 0xF95 Analog Input Point 12 Entry 0 251 1 --- F88 0 1
43991 0xF96 Analog Input Point 12 Scale 1 9 1 --- F85 4 1
Factor
43992 0xF97 Analog Input Point 12 0 100000000 1 --- F9 30000 2
Deadband
43994 0xF99 Analog Input Point 13 Entry 0 251 1 --- F88 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-39


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
43995 0xF9A Analog Input Point 13 Scale 1 9 1 --- F85 4 1
Factor
43996 0xF9B Analog Input Point 13 0 100000000 1 --- F9 30000 2
Deadband
43998 0xF9D Analog Input Point 14 Entry 0 251 1 --- F88 0 1
43999 0xF9E Analog Input Point 14 Scale 1 9 1 --- F85 4 1
Factor
44000 0xF9F Analog Input Point 14 0 100000000 1 --- F9 30000 2
Deadband
44002 0xFA1 Analog Input Point 15 Entry 0 251 1 --- F88 0 1
44003 0xFA2 Analog Input Point 15 Scale 1 9 1 --- F85 4 1
Factor
44004 0xFA3 Analog Input Point 15 0 100000000 1 --- F9 30000 2
Deadband
44006 0xFA5 Analog Input Point 16 Entry 0 251 1 --- F88 0 1
44007 0xFA6 Analog Input Point 16 Scale 1 9 1 --- F85 4 1
Factor
44008 0xFA7 Analog Input Point 16 0 100000000 1 --- F9 30000 2
Deadband
44010 0xFA9 Analog Input Point 17 Entry 0 251 1 --- F88 0 1
44011 0xFAA Analog Input Point 17 Scale 1 9 1 --- F85 4 1
Factor
44012 0xFAB Analog Input Point 17 0 100000000 1 --- F9 30000 2
Deadband
44014 0xFAD Analog Input Point 18 Entry 0 251 1 --- F88 0 1
44015 0xFAE Analog Input Point 18 Scale 1 9 1 --- F85 4 1
Factor
44016 0xFAF Analog Input Point 18 0 100000000 1 --- F9 30000 2
Deadband
44018 0xFB1 Analog Input Point 19 Entry 0 251 1 --- F88 0 1
44019 0xFB2 Analog Input Point 19 Scale 1 9 1 --- F85 4 1
Factor
44020 0xFB3 Analog Input Point 19 0 100000000 1 --- F9 30000 2
Deadband
44022 0xFB5 Analog Input Point 20 Entry 0 251 1 --- F88 0 1
44023 0xFB6 Analog Input Point 20 Scale 1 9 1 --- F85 4 1
Factor
44024 0xFB7 Analog Input Point 20 0 100000000 1 --- F9 30000 2
Deadband
44026 0xFB9 Analog Input Point 21 Entry 0 251 1 --- F88 0 1
44027 0xFBA Analog Input Point 21 Scale 1 9 1 --- F85 4 1
Factor
44028 0xFBB Analog Input Point 21 0 100000000 1 --- F9 30000 2
Deadband
44030 0xFBD Analog Input Point 22 Entry 0 251 1 --- F88 0 1
44031 0xFBE Analog Input Point 22 Scale 1 9 1 --- F85 4 1
Factor
44032 0xFBF Analog Input Point 22 0 100000000 1 --- F9 30000 2
Deadband
44034 0xFC1 Analog Input Point 23 Entry 0 251 1 --- F88 0 1
44035 0xFC2 Analog Input Point 23 Scale 1 9 1 --- F85 4 1
Factor
44036 0xFC3 Analog Input Point 23 0 100000000 1 --- F9 30000 2
Deadband

12-40 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44038 0xFC5 Analog Input Point 24 Entry 0 251 1 --- F88 0 1
44039 0xFC6 Analog Input Point 24 Scale 1 9 1 --- F85 4 1
Factor
44040 0xFC7 Analog Input Point 24 0 100000000 1 --- F9 30000 2
Deadband
44042 0xFC9 Analog Input Point 25 Entry 0 251 1 --- F88 0 1
44043 0xFCA Analog Input Point 25 Scale 1 9 1 --- F85 4 1
Factor
44044 0xFCB Analog Input Point 25 0 100000000 1 --- F9 30000 2
Deadband
44046 0xFCD Analog Input Point 26 Entry 0 251 1 --- F88 0 1
44047 0xFCE Analog Input Point 26 Scale 1 9 1 --- F85 4 1
Factor
44048 0xFCF Analog Input Point 26 0 100000000 1 --- F9 30000 2
Deadband
44050 0xFD1 Analog Input Point 27 Entry 0 251 1 --- F88 0 1
44051 0xFD2 Analog Input Point 27 Scale 1 9 1 --- F85 4 1
Factor
44052 0xFD3 Analog Input Point 27 0 100000000 1 --- F9 30000 2
Deadband
44054 0xFD5 Analog Input Point 28 Entry 0 251 1 --- F88 0 1
44055 0xFD6 Analog Input Point 28 Scale 1 9 1 --- F85 4 1
Factor
44056 0xFD7 Analog Input Point 28 0 100000000 1 --- F9 30000 2
Deadband
44058 0xFD9 Analog Input Point 29 Entry 0 251 1 --- F88 0 1
44059 0xFDA Analog Input Point 29 Scale 1 9 1 --- F85 4 1
Factor
44060 0xFDB Analog Input Point 29 0 100000000 1 --- F9 30000 2
Deadband
44062 0xFDD Analog Input Point 30 Entry 0 251 1 --- F88 0 1
44063 0xFDE Analog Input Point 30 Scale 1 9 1 --- F85 4 1
Factor
44064 0xFDF Analog Input Point 30 0 100000000 1 --- F9 30000 2
Deadband
44066 0xFE1 Analog Input Point 31 Entry 0 251 1 --- F88 0 1
44067 0xFE2 Analog Input Point 31 Scale 1 9 1 --- F85 4 1
Factor
44068 0xFE3 Analog Input Point 31 0 100000000 1 --- F9 30000 2
Deadband
44102 0x1005 Fault Report Mapping 0 1 1 --- FC126 0 1
Enable
AUTORECLOSE SHOT 1
44139 0x102A Phase IOC 1 Shot 1 Initiate 0 1 1 --- FC103 0 1
44140 0x102B Phase IOC 2 Shot 1 Initiate 0 1 1 --- FC103 0 1
44141 0x102C Neutral IOC 1 Shot 1 Initiate 0 1 1 --- FC103 0 1
44142 0x102D Neutral IOC 2 Shot 1 Initiate 0 1 1 --- FC103 0 1
44143 0x102E Ground IOC 1 Shot 1 Initiate 0 1 1 --- FC103 0 1
44144 0x102F Ground IOC 2 Shot 1 Initiate 0 1 1 --- FC103 0 1
44145 0x1030 Phase TOC Shot 1 0 1 1 --- FC103 0 1
44146 0x1031 Neutral TOC Shot 1 0 1 1 --- FC103 0 1
44147 0x1032 Ground TOC Shot 1 0 1 1 --- FC103 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-41


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44148 0x1033 Sensitive Ground IOC 1 Shot 0 1 1 --- FC103 0 1
1 Initiate
44149 0x1034 Sensitive Ground IOC 2 Shot 0 1 1 --- FC103 0 1
1 Initiate
44150 0x1035 Sensitive Ground TOC Shot 1 0 1 1 --- FC103 0 1
44151 0x1036 Block Negative Sequence 0 1 1 --- FC103 0 1
IOC Shot 1
AUTORECLOSE SHOT 2
44159 0x103E Phase IOC 1 Shot 2 Initiate 0 1 1 --- FC103 0 1
44160 0x103F Phase IOC 2 Shot 2 Initiate 0 1 1 --- FC103 0 1
44161 0x1040 Neutral IOC 1 Shot 2 Initiate 0 1 1 --- FC103 0 1
44162 0x1041 Neutral IOC 2 Shot 2 Initiate 0 1 1 --- FC103 0 1
44163 0x1042 Ground IOC 1 Shot 2 Initiate 0 1 1 --- FC103 0 1
44164 0x1043 Ground IOC 2 Shot 2 Initiate 0 1 1 --- FC103 0 1
44165 0x1044 Phase TOC Shot 2 0 1 1 --- FC103 0 1
44166 0x1045 Neutral TOC Shot 2 0 1 1 --- FC103 0 1
44167 0x1046 Ground TOC Shot 2 0 1 1 --- FC103 0 1
44168 0x1047 Sensitive Ground IOC 1 Shot 0 1 1 --- FC103 0 1
2 Initiate
44169 0x1048 Sensitive Ground IOC 2 Shot 0 1 1 --- FC103 0 1
2 Initiate
44170 0x1049 Sensitive Ground TOC Shot 2 0 1 1 --- FC103 0 1
44171 0x104A Block Negative Sequence 0 1 1 --- FC103 0 1
IOC Shot 2
AUTORECLOSE SHOT 3
44179 0x1052 Phase IOC 1 Shot 3 Initiate 0 1 1 --- FC103 0 1
44180 0x1053 Phase IOC 2 Shot 3 Initiate 0 1 1 --- FC103 0 1
44181 0x1054 Neutral IOC 1 Shot 3 Initiate 0 1 1 --- FC103 0 1
44182 0x1055 Neutral IOC 2 Shot 3 Initiate 0 1 1 --- FC103 0 1
44183 0x1056 Ground IOC 1 Shot 3 Initiate 0 1 1 --- FC103 0 1
44184 0x1057 Ground IOC 2 Shot 3 Initiate 0 1 1 --- FC103 0 1
44185 0x1058 Phase TOC Shot 3 0 1 1 --- FC103 0 1
44186 0x1059 Neutral TOC Shot 3 0 1 1 --- FC103 0 1
44187 0x105A Ground TOC Shot 3 0 1 1 --- FC103 0 1
44188 0x105B Sensitive Ground IOC 1 Shot 0 1 1 --- FC103 0 1
3 Initiate
44189 0x105C Sensitive Ground IOC 2 Shot 0 1 1 --- FC103 0 1
3 Initiate
44190 0x105D Sensitive Ground TOC Shot 3 0 1 1 --- FC103 0 1
44191 0x105E Block Negative Sequence 0 1 1 --- FC103 0 1
IOC Shot 3
AUTORECLOSE
42257 0x8D0 Initiate Reclosure 0 0xFFFF 1 --- F1 0 1
42259 0x8D2 Block Reclosure 0 0xFFFF 1 --- F1 0 1
44109 0x100C AR Function 0 1 1 --- FC126 0 1
44110 0x100D Number of Shots 1 4 1 --- F1 1 1
44111 0x100E Dead Time Shot 1 1 6000 1 s F2 10 1
44112 0x100F Dead Time Shot 2 1 6000 1 s F2 20 1
44113 0x1010 Dead Time Shot 3 1 6000 1 s F2 30 1

12-42 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44114 0x1011 Dead Time Shot 4 1 6000 1 s F2 40 1
44115 0x1012 Reset Lockout Time 1 6000 1 s F2 100 1
44116 0x1013 Incomplete Sequence Time 1 6000 1 s F2 50 1
44117 0x1014 Reset Time 1 6000 1 s F2 50 1
44118 0x1015 Block AR 0 0xEF02 1 --- F89 0 1
44119 0x1016 External Initiate 0 0xEF02 1 --- F89 0 1
44120 0x1017 Phase IOC 1 Initiate 0 1 1 --- FC103 0 1
44121 0x1018 Phase IOC 2 Initiate 0 1 1 --- FC103 0 1
44122 0x1019 Neutral IOC 1 Initiate 0 1 1 --- FC103 0 1
44123 0x101A Neutral IOC 2 Initiate 0 1 1 --- FC103 0 1
44124 0x101B Ground IOC 1 Initiate 0 1 1 --- FC103 0 1
44125 0x101C Ground IOC 2 Initiate 0 1 1 --- FC103 0 1
44126 0x101D Phase TOC Initiate 0 1 1 --- FC103 0 1
44127 0x101E Neutral TOC Initiate 0 1 1 --- FC103 0 1
44128 0x101F Ground TOC Initiate 0 1 1 --- FC103 0 1
44129 0x1020 AR Ready Relays 0 0x7F 1 --- FC198 0 1
44130 0x1021 AR In-Progress Relays 0 0x7F 1 --- FC198 0 1
44131 0x1022 AR N/Ready Relays 0 0x7F 1 --- FC198 0 1
44132 0x1023 Select Setting Group -1 1 1 --- F91 0 1
44133 0x1024 Sensitive Ground IOC 1 0 1 1 --- FC103 0 1
Initiate
44134 0x1025 Sensitive Ground IOC 2 0 1 1 --- FC103 0 1
Initiate
44135 0x1026 Sensitive Ground TOC 0 1 1 --- FC103 0 1
Initiate
44136 0x1027 Negative Sequence IOC 0 1 1 --- FC103 0 1
Initiate
44137 0x1028 Negative Sequence TOC 0 1 1 --- FC103 0 1
Initiate
44152 0x1037 Negative Sequence TOC 0 1 1 --- FC103 0 1
Shot 1
44172 0x104B Negative Sequence TOC 0 1 1 --- FC103 0 1
Shot 2
44192 0x105F Negative Sequence TOC 0 1 1 --- FC103 0 1
Shot 3
44197 0x1064 Negative Sequence TOC 0 1 1 --- FC103 0 1
Shot 4
AUTORECLOSE SHOT 4
44198 0x1065 Block Negative Sequence 0 1 1 --- FC103 0 1
IOC Shot 4
44199 0x1066 Phase IOC 1 Shot 4 Initiate 0 1 1 --- FC103 0 1
44200 0x1067 Phase IOC 2 Shot 4 Initiate 0 1 1 --- FC103 0 1
44201 0x1068 Neutral IOC 1 Shot 4 Initiate 0 1 1 --- FC103 0 1
44202 0x1069 Neutral IOC 2 Shot 4 Initiate 0 1 1 --- FC103 0 1
44203 0x106A Ground IOC 1 Shot 4 Initiate 0 1 1 --- FC103 0 1
44204 0x106B Ground IOC 2 Shot 4 Initiate 0 1 1 --- FC103 0 1
44205 0x106C Phase TOC Shot 4 0 1 1 --- FC103 0 1
44206 0x106D Neutral TOC Shot 4 0 1 1 --- FC103 0 1
44207 0x106E Ground TOC Shot 4 0 1 1 --- FC103 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-43


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44208 0x106F Sensitive Ground IOC 1 Shot 0 1 1 --- FC103 0 1
4 Initiate
44209 0x1070 Sensitive Ground IOC 2 Shot 0 1 1 --- FC103 0 1
4 Initiate
44210 0x1071 Sensitive Ground TOC Shot 4 0 1 1 --- FC103 0 1
THERMAL OVERLOAD
44211 0x1072 Thermal Overload Function 0 3 1 --- FC197 0 1
44212 0x1073 Heat Time Constant 30 6000 1 min F2 60 1
44213 0x1074 Cool Time Constant 100 600 1 --- F3 200 1
44214 0x1075 Pickup Level 5 2000 1 x CT F3 100 1
44215 0x1076 Alarm Level 700 1100 1 % F2 800 1
44216 0x1077 Output Relays 3-7 0 0x7F 1 --- FC198 0 1
IEC60870-5-103 BINARY INPUT POINTS
44221 0x107C Binary In Point 0 Entry 0 255 1 --- F1 0 1
Function Type
44222 0x107D Binary In Point 0 Entry 0 255 1 --- F1 0 1
Information Number
44223 0x107E Binary In Point 1 Entry 0 255 1 --- F1 0 1
Function Type
44224 0x107F Binary In Point 1 Entry 0 255 1 --- F1 0 1
Information Number
44225 0x1080 Binary In Point 2 Entry 0 255 1 --- F1 0 1
Function Type
44226 0x1081 Binary In Point 2 Entry 0 255 1 --- F1 0 1
Information Number
44227 0x1082 Binary In Point 3 Entry 0 255 1 --- F1 0 1
Function Type
44228 0x1083 Binary In Point 3 Entry 0 255 1 --- F1 0 1
Information Number
44229 0x1084 Binary In Point 4 Entry 0 255 1 --- F1 0 1
Function Type
44230 0x1085 Binary In Point 4 Entry 0 255 1 --- F1 0 1
Information Number
44231 0x1086 Binary In Point 5 Entry 0 255 1 --- F1 0 1
Function Type
44232 0x1087 Binary In Point 5 Entry 0 255 1 --- F1 0 1
Information Number
44233 0x1088 Binary In Point 6 Entry 0 255 1 --- F1 0 1
Function Type
44234 0x1089 Binary In Point 6 Entry 0 255 1 --- F1 0 1
Information Number
44235 0x108A Binary In Point 7 Entry 0 255 1 --- F1 0 1
Function Type
44236 0x108B Binary In Point 7 Entry 0 255 1 --- F1 0 1
Information Number
44237 0x108C Binary In Point 8 Entry 0 255 1 --- F1 0 1
Function Type
44238 0x108D Binary In Point 8 Entry 0 255 1 --- F1 0 1
Information Number
44239 0x108E Binary In Point 9 Entry 0 255 1 --- F1 0 1
Function Type
44240 0x108F Binary In Point 9 Entry 0 255 1 --- F1 0 1
Information Number

12-44 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44241 0x1090 Binary In Point 10 Entry 0 255 1 --- F1 0 1
Function Type
44242 0x1091 Binary In Point 10 Entry 0 255 1 --- F1 0 1
Information Number
44243 0x1092 Binary In Point 11 Entry 0 255 1 --- F1 0 1
Function Type
44244 0x1093 Binary In Point 11 Entry 0 255 1 --- F1 0 1
Information Number
44245 0x1094 Binary In Point 12 Entry 0 255 1 --- F1 0 1
Function Type
44246 0x1095 Binary In Point 12 Entry 0 255 1 --- F1 0 1
Information Number
44247 0x1096 Binary In Point 13 Entry 0 255 1 --- F1 0 1
Function Type
44248 0x1097 Binary In Point 13 Entry 0 255 1 --- F1 0 1
Information Number
44249 0x1098 Binary In Point 14 Entry 0 255 1 --- F1 0 1
Function Type
44250 0x1099 Binary In Point 14 Entry 0 255 1 --- F1 0 1
Information Number
44251 0x109A Binary In Point 15 Entry 0 255 1 --- F1 0 1
Function Type
44252 0x109B Binary In Point 15 Entry 0 255 1 --- F1 0 1
Information Number
44253 0x109C Binary In Point 16 Entry 0 255 1 --- F1 0 1
Function Type
44254 0x109D Binary In Point 16 Entry 0 255 1 --- F1 0 1
Information Number
44255 0x109E Binary In Point 17 Entry 0 255 1 --- F1 0 1
Function Type
44256 0x109F Binary In Point 17 Entry 0 255 1 --- F1 0 1
Information Number
44257 0x10A0 Binary In Point 18 Entry 0 255 1 --- F1 0 1
Function Type
44258 0x10A1 Binary In Point 18 Entry 0 255 1 --- F1 0 1
Information Number
44259 0x10A2 Binary In Point 19 Entry 0 255 1 --- F1 0 1
Function Type
44260 0x10A3 Binary In Point 19 Entry 0 255 1 --- F1 0 1
Information Number
44261 0x10A4 Binary In Point 20 Entry 0 255 1 --- F1 0 1
Function Type
44262 0x10A5 Binary In Point 20 Entry 0 255 1 --- F1 0 1
Information Number
44263 0x10A6 Binary In Point 21 Entry 0 255 1 --- F1 0 1
Function Type
44264 0x10A7 Binary In Point 21 Entry 0 255 1 --- F1 0 1
Information Number
44265 0x10A8 Binary In Point 22 Entry 0 255 1 --- F1 0 1
Function Type
44266 0x10A9 Binary In Point 22 Entry 0 255 1 --- F1 0 1
Information Number
44267 0x10AA Binary In Point 23 Entry 0 255 1 --- F1 0 1
Function Type
44268 0x10AB Binary In Point 23 Entry 0 255 1 --- F1 0 1
Information Number

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-45


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44269 0x10AC Binary In Point 24 Entry 0 255 1 --- F1 0 1
Function Type
44270 0x10AD Binary In Point 24 Entry 0 255 1 --- F1 0 1
Information Number
44271 0x10AE Binary In Point 25 Entry 0 255 1 --- F1 0 1
Function Type
44272 0x10AF Binary In Point 25 Entry 0 255 1 --- F1 0 1
Information Number
44273 0x10B0 Binary In Point 26 Entry 0 255 1 --- F1 0 1
Function Type
44274 0x10B1 Binary In Point 26 Entry 0 255 1 --- F1 0 1
Information Number
44275 0x10B2 Binary In Point 27 Entry 0 255 1 --- F1 0 1
Function Type
44276 0x10B3 Binary In Point 27 Entry 0 255 1 --- F1 0 1
Information Number
44277 0x10B4 Binary In Point 28 Entry 0 255 1 --- F1 0 1
Function Type
44278 0x10B5 Binary In Point 28 Entry 0 255 1 --- F1 0 1
Information Number
44279 0x10B6 Binary In Point 29 Entry 0 255 1 --- F1 0 1
Function Type
44280 0x10B7 Binary In Point 29 Entry 0 255 1 --- F1 0 1
Information Number
44281 0x10B8 Binary In Point 30 Entry 0 255 1 --- F1 0 1
Function Type
44282 0x10B9 Binary In Point 30 Entry 0 255 1 --- F1 0 1
Information Number
44283 0x10BA Binary In Point 31 Entry 0 255 1 --- F1 0 1
Function Type
44284 0x10BB Binary In Point 31 Entry 0 255 1 --- F1 0 1
Information Number
44285 0x10BC Binary In Point 32 Entry 0 255 1 --- F1 0 1
Function Type
44286 0x10BD Binary In Point 32 Entry 0 255 1 --- F1 0 1
Information Number
44287 0x10BE Binary In Point 33 Entry 0 255 1 --- F1 0 1
Function Type
44288 0x10BF Binary In Point 33 Entry 0 255 1 --- F1 0 1
Information Number
44289 0x10C0 Binary In Point 34 Entry 0 255 1 --- F1 0 1
Function Type
44290 0x10C1 Binary In Point 34 Entry 0 255 1 --- F1 0 1
Information Number
44291 0x10C2 Binary In Point 35 Entry 0 255 1 --- F1 0 1
Function Type
44292 0x10C3 Binary In Point 35 Entry 0 255 1 --- F1 0 1
Information Number
44293 0x10C4 Binary In Point 36 Entry 0 255 1 --- F1 0 1
Function Type
44294 0x10C5 Binary In Point 36 Entry 0 255 1 --- F1 0 1
Information Number
44295 0x10C6 Binary In Point 37 Entry 0 255 1 --- F1 0 1
Function Type
44296 0x10C7 Binary In Point 37 Entry 0 255 1 --- F1 0 1
Information Number

12-46 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44297 0x10C8 Binary In Point 38 Entry 0 255 1 --- F1 0 1
Function Type
44298 0x10C9 Binary In Point 38 Entry 0 255 1 --- F1 0 1
Information Number
44299 0x10CA Binary In Point 39 Entry 0 255 1 --- F1 0 1
Function Type
44300 0x10CB Binary In Point 39 Entry 0 255 1 --- F1 0 1
Information Number
44301 0x10CC Binary In Point 40 Entry 0 255 1 --- F1 0 1
Function Type
44302 0x10CD Binary In Point 40 Entry 0 255 1 --- F1 0 1
Information Number
44303 0x10CE Binary In Point 41 Entry 0 255 1 --- F1 0 1
Function Type
44304 0x10CF Binary In Point 41 Entry 0 255 1 --- F1 0 1
Information Number
44305 0x10D0 Binary In Point 42 Entry 0 255 1 --- F1 0 1
Function Type
44306 0x10D1 Binary In Point 42 Entry 0 255 1 --- F1 0 1
Information Number
44307 0x10D2 Binary In Point 43 Entry 0 255 1 --- F1 0 1
Function Type
44308 0x10D3 Binary In Point 43 Entry 0 255 1 --- F1 0 1
Information Number
44309 0x10D4 Binary In Point 44 Entry 0 255 1 --- F1 0 1
Function Type
44310 0x10D5 Binary In Point 44 Entry 0 255 1 --- F1 0 1
Information Number
44311 0x10D6 Binary In Point 45 Entry 0 255 1 --- F1 0 1
Function Type
44312 0x10D7 Binary In Point 45 Entry 0 255 1 --- F1 0 1
Information Number
44313 0x10D8 Binary In Point 46 Entry 0 255 1 --- F1 0 1
Function Type
44314 0x10D9 Binary In Point 46 Entry 0 255 1 --- F1 0 1
Information Number
44315 0x10DA Binary In Point 47 Entry 0 255 1 --- F1 0 1
Function Type
44316 0x10DB Binary In Point 47 Entry 0 255 1 --- F1 0 1
Information Number
44317 0x10DC Binary In Point 48 Entry 0 255 1 --- F1 0 1
Function Type
44318 0x10DD Binary In Point 48 Entry 0 255 1 --- F1 0 1
Information Number
44319 0x10DE Binary In Point 49 Entry 0 255 1 --- F1 0 1
Function Type
44320 0x10DF Binary In Point 49 Entry 0 255 1 --- F1 0 1
Information Number
44321 0x10E0 Binary In Point 50 Entry 0 255 1 --- F1 0 1
Function Type
44322 0x10E1 Binary In Point 50 Entry 0 255 1 --- F1 0 1
Information Number
44323 0x10E2 Binary In Point 51 Entry 0 255 1 --- F1 0 1
Function Type
44324 0x10E3 Binary In Point 51 Entry 0 255 1 --- F1 0 1
Information Number

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-47


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44325 0x10E4 Binary In Point 52 Entry 0 255 1 --- F1 0 1
Function Type
44326 0x10E5 Binary In Point 52 Entry 0 255 1 --- F1 0 1
Information Number
44327 0x10E6 Binary In Point 53 Entry 0 255 1 --- F1 0 1
Function Type
44328 0x10E7 Binary In Point 53 Entry 0 255 1 --- F1 0 1
Information Number
44329 0x10E8 Binary In Point 54 Entry 0 255 1 --- F1 0 1
Function Type
44330 0x10E9 Binary In Point 54 Entry 0 255 1 --- F1 0 1
Information Number
44331 0x10EA Binary In Point 55 Entry 0 255 1 --- F1 0 1
Function Type
44332 0x10EB Binary In Point 55 Entry 0 255 1 --- F1 0 1
Information Number
44333 0x10EC Binary In Point 56 Entry 0 255 1 --- F1 0 1
Function Type
44334 0x10ED Binary In Point 56 Entry 0 255 1 --- F1 0 1
Information Number
44335 0x10EE Binary In Point 57 Entry 0 255 1 --- F1 0 1
Function Type
44336 0x10EF Binary In Point 57 Entry 0 255 1 --- F1 0 1
Information Number
44337 0x10F0 Binary In Point 58 Entry 0 255 1 --- F1 0 1
Function Type
44338 0x10F1 Binary In Point 58 Entry 0 255 1 --- F1 0 1
Information Number
44339 0x10F2 Binary In Point 59 Entry 0 255 1 --- F1 0 1
Function Type
44340 0x10F3 Binary In Point 59 Entry 0 255 1 --- F1 0 1
Information Number
44341 0x10F4 Binary In Point 60 Entry 0 255 1 --- F1 0 1
Function Type
44342 0x10F5 Binary In Point 60 Entry 0 255 1 --- F1 0 1
Information Number
44343 0x10F6 Binary In Point 61 Entry 0 255 1 --- F1 0 1
Function Type
44344 0x10F7 Binary In Point 61 Entry 0 255 1 --- F1 0 1
Information Number
44345 0x10F8 Binary In Point 62 Entry 0 255 1 --- F1 0 1
Function Type
44346 0x10F9 Binary In Point 62 Entry 0 255 1 --- F1 0 1
Information Number
44347 0x10FA Binary In Point 63 Entry 0 255 1 --- F1 0 1
Function Type
44348 0x10FB Binary In Point 63 Entry 0 255 1 --- F1 0 1
Information Number
DNP / IEC60870-5-103 BINARY OUTPUT POINTS
44349 0x10FC Binary Out Point 0 Entry 0 255 1 --- F1 0 1
Function Type
44350 0x10FD Binary Out Point 0 Entry 0 255 1 --- F1 0 1
Information Number
44351 0x10FE Binary Out Point 1 Entry 0 255 1 --- F1 0 1
Function Type

12-48 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44352 0x10FF Binary Out Point 1 Entry 0 255 1 --- F1 0 1
Information Number
44353 0x1100 Binary Out Point 2 Entry 0 255 1 --- F1 0 1
Function Type
44354 0x1101 Binary Out Point 2 Entry 0 255 1 --- F1 0 1
Information Number
44355 0x1102 Binary Out Point 3 Entry 0 255 1 --- F1 0 1
Function Type
44356 0x1103 Binary Out Point 3 Entry 0 255 1 --- F1 0 1
Information Number
44357 0x1104 Binary Out Point 4 Entry 0 255 1 --- F1 0 1
Function Type
44358 0x1105 Binary Out Point 4 Entry 0 255 1 --- F1 0 1
Information Number
44359 0x1106 Binary Out Point 5 Entry 0 255 1 --- F1 0 1
Function Type
44360 0x1107 Binary Out Point 5 Entry 0 255 1 --- F1 0 1
Information Number
44361 0x1108 Binary Out Point 6 Entry 0 255 1 --- F1 0 1
Function Type
44362 0x1109 Binary Out Point 6 Entry 0 255 1 --- F1 0 1
Information Number
44363 0x110A Binary Out Point 7 Entry 0 255 1 --- F1 0 1
Function Type
44364 0x110B Binary Out Point 7 Entry 0 255 1 --- F1 0 1
Information Number
44365 0x110C Binary Out Point 8 Entry 0 255 1 --- F1 0 1
Function Type
44366 0x110D Binary Out Point 8 Entry 0 255 1 --- F1 0 1
Information Number
44367 0x110E Binary Out Point 9 Entry 0 255 1 --- F1 0 1
Function Type
44368 0x110F Binary Out Point 9 Entry 0 255 1 --- F1 0 1
Information Number
44369 0x1110 Binary Out Point 10 Entry 0 255 1 --- F1 0 1
Function Type
44370 0x1111 Binary Out Point 10 Entry 0 255 1 --- F1 0 1
Information Number
44371 0x1112 Binary Out Point 11 Entry 0 255 1 --- F1 0 1
Function Type
44372 0x1113 Binary Out Point 11 Entry 0 255 1 --- F1 0 1
Information Number
44373 0x1114 Binary Out Point 12 Entry 0 255 1 --- F1 0 1
Function Type
44374 0x1115 Binary Out Point 12 Entry 0 255 1 --- F1 0 1
Information Number
44375 0x1116 Binary Out Point 13 Entry 0 255 1 --- F1 0 1
Function Type
44376 0x1117 Binary Out Point 13 Entry 0 255 1 --- F1 0 1
Information Number
44377 0x1118 Binary Out Point 14 Entry 0 255 1 --- F1 0 1
Function Type
44378 0x1119 Binary Out Point 14 Entry 0 255 1 --- F1 0 1
Information Number
44379 0x111A Binary Out Point 15 Entry 0 255 1 --- F1 0 1
Function Type

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-49


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44380 0x111B Binary Out Point 15 Entry 0 255 1 --- F1 0 1
Information Number
DNP / IEC60870-5-103 ADDRESSING
44382 0x111D IEC60870-5-103 Slave 0 254 1 --- F1 0 1
Address
44383 0x111E Synchronization Timeout 0 1440 1 min F1 0 1
IEC60870-5-103 MEASURANDS
44384 0x111F 103 First ASDU Identification 3 9 1 --- FC221 3 1
Type
44385 0x1120 103 First ASDU Function 0 255 1 --- F1 0 1
Type
44386 0x1121 103 First ASDU Information 0 255 1 --- F1 0 1
Number
44387 0x1122 103 First ASDU Scan 0 1000 1 s F1 0 1
Timeout
44388 0x1123 103 First ASDU First 0 251 1 --- F88 0 1
Analogue Entry
44389 0x1124 103 First ASDU First 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44390 0x1125 103 First ASDU First 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44391 0x1126 103 First ASDU Second 0 251 1 --- F88 0 1
Analogue Entry
44392 0x1127 103 First ASDU Second 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44393 0x1128 103 First ASDU Second 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44394 0x1129 103 First ASDU Third 0 251 1 --- F88 0 1
Analogue Entry
44395 0x112A 103 First ASDU Third 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44396 0x112B 103 First ASDU Third 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44397 0x112C 103 First ASDU Fourth 0 251 1 --- F88 0 1
Analogue Entry
44398 0x112D 103 First ASDU Fourth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44399 0x112E 103 First ASDU Fourth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44400 0x112F 103 First ASDU Fifth 0 251 1 --- F88 0 1
Analogue Entry
44401 0x1130 103 First ASDU Fifth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44402 0x1131 103 First ASDU Fifth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44403 0x1132 103 First ASDU Sixth 0 251 1 --- F88 0 1
Analogue Entry
44404 0x1133 103 First ASDU Sixth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44405 0x1134 103 First ASDU Sixth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44406 0x1135 103 First ASDU Seventh 0 251 1 --- F88 0 1
Analogue Entry
44407 0x1136 103 First ASDU Seventh 0 0xFFFF 1 --- F3 0 1
Analogue Factor

12-50 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44408 0x1137 103 First ASDU Seventh 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44409 0x1138 103 First ASDU Eigth 0 251 1 --- F88 0 1
Analogue Entry
44410 0x1139 103 First ASDU Eigth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44411 0x113A 103 First ASDU Eigth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44412 0x113B 103 First ASDU Ninth 0 251 1 --- F88 0 1
Analogue Entry
44413 0x113C 103 First ASDU Ninth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44414 0x113D 103 First ASDU Ninth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44415 0x113E 103 Second ASDU 3 9 1 --- FC221 3 1
Identification Type
44416 0x113F 103 Second ASDU Function 0 255 1 --- F1 0 1
Type
44417 0x1140 103 Second ASDU 0 255 1 --- F1 0 1
Information Number
44418 0x1141 103 Second ASDU Scan 0 1000 1 s F1 0 1
Timeout
44419 0x1142 103 Second ASDU First 0 251 1 --- F88 0 1
Analogue Entry
44420 0x1143 103 Second ASDU First 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44421 0x1144 103 Second ASDU First 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44422 0x1145 103 Second ASDU Second 0 251 1 --- F88 0 1
Analogue Entry
44423 0x1146 103 Second ASDU Second 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44424 0x1147 103 Second ASDU Second 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44425 0x1148 103 Second ASDU Third 0 251 1 --- F88 0 1
Analogue Entry
44426 0x1149 103 Second ASDU Third 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44427 0x114A 103 Second ASDU Third 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44428 0x114B 103 Second ASDU Fourth 0 251 1 --- F88 0 1
Analogue Entry
44429 0x114C 103 Second ASDU Fourth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44430 0x114D 103 Second ASDU Fourth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44431 0x114E 103 Second ASDU Fifth 0 251 1 --- F88 0 1
Analogue Entry
44432 0x114F 103 Second ASDU Fifth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44433 0x1150 103 Second ASDU Fifth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44434 0x1151 103 Second ASDU Sixth 0 251 1 --- F88 0 1
Analogue Entry
44435 0x1152 103 Second ASDU Sixth 0 0xFFFF 1 --- F3 0 1
Analogue Factor

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-51


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44436 0x1153 103 Second ASDU Sixth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44437 0x1154 103 Second ASDU Seventh 0 251 1 --- F88 0 1
Analogue Entry
44438 0x1155 103 Second ASDU Seventh 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44439 0x1156 103 Second ASDU Seventh 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44440 0x1157 103 Second ASDU Eigth 0 251 1 --- F88 0 1
Analogue Entry
44441 0x1158 103 Second ASDU Eigth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44442 0x1159 103 Second ASDU Eigth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44443 0x115A 103 Second ASDU Ninth 0 251 1 --- F88 0 1
Analogue Entry
44444 0x115B 103 Second ASDU Ninth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44445 0x115C 103 Second ASDU Ninth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44446 0x115D 103 Third ASDU 3 9 1 --- FC221 3 1
Identification Type
44447 0x115E 103 Third ASDU Function 0 255 1 --- F1 0 1
Type
44448 0x115F 103 Third ASDU Information 0 255 1 --- F1 0 1
Number
44449 0x1160 103 Third ASDU Scan 0 1000 1 s F1 0 1
Timeout
44450 0x1161 103 Third ASDU First 0 251 1 --- F88 0 1
Analogue Entry
44451 0x1162 103 Third ASDU First 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44452 0x1163 103 Third ASDU First 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44453 0x1164 103 Third ASDU Second 0 251 1 --- F88 0 1
Analogue Entry
44454 0x1165 103 Third ASDU Second 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44455 0x1166 103 Third ASDU Second 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44456 0x1167 103 Third ASDU Third 0 251 1 --- F88 0 1
Analogue Entry
44457 0x1168 103 Third ASDU Third 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44458 0x1169 103 Third ASDU Third 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44459 0x116A 103 Third ASDU Fourth 0 251 1 --- F88 0 1
Analogue Entry
44460 0x116B 103 Third ASDU Fourth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44461 0x116C 103 Third ASDU Fourth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44462 0x116D 103 Third ASDU Fifth 0 251 1 --- F88 0 1
Analogue Entry
44463 0x116E 103 Third ASDU Fifth 0 0xFFFF 1 --- F3 0 1
Analogue Factor

12-52 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44464 0x116F 103 Third ASDU Fifth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44465 0x1170 103 Third ASDU Sixth 0 251 1 --- F88 0 1
Analogue Entry
44466 0x1171 103 Third ASDU Sixth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44467 0x1172 103 Third ASDU Sixth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44468 0x1173 103 Third ASDU Seventh 0 251 1 --- F88 0 1
Analogue Entry
44469 0x1174 103 Third ASDU Seventh 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44470 0x1175 103 Third ASDU Seventh 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44471 0x1176 103 Third ASDU Eigth 0 251 1 --- F88 0 1
Analogue Entry
44472 0x1177 103 Third ASDU Eigth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44473 0x1178 103 Third ASDU Eigth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44474 0x1179 103 Third ASDU Ninth 0 251 1 --- F88 0 1
Analogue Entry
44475 0x117A 103 Third ASDU Ninth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44476 0x117B 103 Third ASDU Ninth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44477 0x117C 103 Fourth ASDU 3 9 1 --- FC221 3 1
Identification Type
44478 0x117D 103 Fourth ASDU Function 0 255 1 --- F1 0 1
Type
44479 0x117E 103 Fourth ASDU 0 255 1 --- F1 0 1
Information Number
44480 0x117F 103 Fourth ASDU Scan 0 1000 1 s F1 0 1
Timeout
44481 0x1180 103 Fourth ASDU First 0 251 1 --- F88 0 1
Analogue Entry
44482 0x1181 103 Fourth ASDU First 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44483 0x1182 103 Fourth ASDU First 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44484 0x1183 103 Fourth ASDU Second 0 251 1 --- F88 0 1
Analogue Entry
44485 0x1184 103 Fourth ASDU Second 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44486 0x1185 103 Fourth ASDU Second 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44487 0x1186 103 Fourth ASDU Third 0 251 1 --- F88 0 1
Analogue Entry
44488 0x1187 103 Fourth ASDU Third 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44489 0x1188 103 Fourth ASDU Third 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44490 0x1189 103 Fourth ASDU Fourth 0 251 1 --- F88 0 1
Analogue Entry
44491 0x118A 103 Fourth ASDU Fourth 0 0xFFFF 1 --- F3 0 1
Analogue Factor

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-53


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44492 0x118B 103 Fourth ASDU Fourth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44493 0x118C 103 Fourth ASDU Fifth 0 251 1 --- F88 0 1
Analogue Entry
44494 0x118D 103 Fourth ASDU Fifth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44495 0x118E 103 Fourth ASDU Fifth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44496 0x118F 103 Fourth ASDU Sixth 0 251 1 --- F88 0 1
Analogue Entry
44497 0x1190 103 Fourth ASDU Sixth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44498 0x1191 103 Fourth ASDU Sixth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44499 0x1192 103 Fourth ASDU Seventh 0 251 1 --- F88 0 1
Analogue Entry
44500 0x1193 103 Fourth ASDU Seventh 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44501 0x1194 103 Fourth ASDU Seventh 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44502 0x1195 103 Fourth ASDU Eigth 0 251 1 --- F88 0 1
Analogue Entry
44503 0x1196 103 Fourth ASDU Eigth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44504 0x1197 103 Fourth ASDU Eigth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
44505 0x1198 103 Fourth ASDU Ninth 0 251 1 --- F88 0 1
Analogue Entry
44506 0x1199 103 Fourth ASDU Ninth 0 0xFFFF 1 --- F3 0 1
Analogue Factor
44507 0x119A 103 Fourth ASDU Ninth 0 0xFFFF 1 --- F1 0 1
Analogue Offset
PASSWORD SECURITY
44536 0x11B7 Security Passcode Master 1 0 1 1 --- F22 0 1
44537 0x11B8 Security Passcode Master 2 0 1 1 --- F22 0 1
44538 0x11B9 Security Passcode Master 3 0 1 1 --- F22 0 1
44539 0x11BA Security Passcode Master 4 0 1 1 --- F22 0 1
44540 0x11BB Security Passcode Master 5 0 1 1 --- F22 0 1
44541 0x11BC Security Passcode Local 0 1 1 --- F22 0 1
Setpoint 1
44542 0x11BD Security Passcode Local 0 1 1 --- F22 0 1
Setpoint 2
44543 0x11BE Security Passcode Local 0 1 1 --- F22 0 1
Setpoint 3
44544 0x11BF Security Passcode Local 0 1 1 --- F22 0 1
Setpoint 4
44545 0x11C0 Security Passcode Local 0 1 1 --- F22 0 1
Setpoint 5
44546 0x11C1 Security Passcode Local 0 1 1 --- F22 0 1
Control 1
44547 0x11C2 Security Passcode Local 0 1 1 --- F22 0 1
Control 2
44548 0x11C3 Security Passcode Local 0 1 1 --- F22 0 1
Control 3

12-54 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44549 0x11C4 Security Passcode Local 0 1 1 --- F22 0 1
Control 4
44550 0x11C5 Security Passcode Local 0 1 1 --- F22 0 1
Control 5
44551 0x11C6 Security Passcode Remote 0 1 1 --- F22 0 1
Setpoint 1
44552 0x11C7 Security Passcode Remote 0 1 1 --- F22 0 1
Setpoint 2
44553 0x11C8 Security Passcode Remote 0 1 1 --- F22 0 1
Setpoint 3
44554 0x11C9 Security Passcode Remote 0 1 1 --- F22 0 1
Setpoint 4
44555 0x11CA Security Passcode Remote 0 1 1 --- F22 0 1
Setpoint 5
44556 0x11CB Security Passcode Remote 0 1 1 --- F22 0 1
Control 1
44557 0x11CC Security Passcode Remote 0 1 1 --- F22 0 1
Control 2
44558 0x11CD Security Passcode Remote 0 1 1 --- F22 0 1
Control 3
44559 0x11CE Security Passcode Remote 0 1 1 --- F22 0 1
Control 4
44560 0x11CF Security Passcode Remote 0 1 1 --- F22 0 1
Control 5
44561 0x11D0 Security Passcode Entry 0 1 1 --- F22 0 1
Master 1
44562 0x11D1 Security Passcode Entry 0 1 1 --- F22 0 1
Master 2
44563 0x11D2 Security Passcode Entry 0 1 1 --- F22 0 1
Master 3
44564 0x11D3 Security Passcode Entry 0 1 1 --- F22 0 1
Master 4
44565 0x11D4 Security Passcode Entry 0 1 1 --- F22 0 1
Master 5
44566 0x11D5 Security Passcode Entry 0 1 1 --- F22 0 1
Setpoints 1
44567 0x11D6 Security Passcode Entry 0 1 1 --- F22 0 1
Setpoints 2
44568 0x11D7 Security Passcode Entry 0 1 1 --- F22 0 1
Setpoints 3
44569 0x11D8 Security Passcode Entry 0 1 1 --- F22 0 1
Setpoints 4
44570 0x11D9 Security Passcode Entry 0 1 1 --- F22 0 1
Setpoints 5
44571 0x11DA Security Passcode Entry 0 1 1 --- F22 0 1
Control 1
44572 0x11DB Security Passcode Entry 0 1 1 --- F22 0 1
Control 2
44573 0x11DC Security Passcode Entry 0 1 1 --- F22 0 1
Control 3
44574 0x11DD Security Passcode Entry 0 1 1 --- F22 0 1
Control 4
44575 0x11DE Security Passcode Entry 0 1 1 --- F22 0 1
Control 5
44576 0x11DF Overwrite Local Setpoint 0 1 1 --- FC103A 0 1
Password

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-55


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
VIRTUAL INPUT FUNCTION
44580 0x11E3 Virtual Input 1 Function 0 1 1 --- FC126 0 1
44581 0x11E4 Virtual Input 2 Function 0 1 1 --- FC126 0 1
44582 0x11E5 Virtual Input 3 Function 0 1 1 --- FC126 0 1
44583 0x11E6 Virtual Input 4 Function 0 1 1 --- FC126 0 1
44584 0x11E7 Virtual Input 5 Function 0 1 1 --- FC126 0 1
44585 0x11E8 Virtual Input 6 Function 0 1 1 --- FC126 0 1
44586 0x11E9 Virtual Input 7 Function 0 1 1 --- FC126 0 1
44587 0x11EA Virtual Input 8 Function 0 1 1 --- FC126 0 1
44588 0x11EB Virtual Input 9 Function 0 1 1 --- FC126 0 1
44589 0x11EC Virtual Input 10 Function 0 1 1 --- FC126 0 1
44590 0x11ED Virtual Input 11 Function 0 1 1 --- FC126 0 1
44591 0x11EE Virtual Input 12 Function 0 1 1 --- FC126 0 1
44592 0x11EF Virtual Input 13 Function 0 1 1 --- FC126 0 1
44593 0x11F0 Virtual Input 14 Function 0 1 1 --- FC126 0 1
44594 0x11F1 Virtual Input 15 Function 0 1 1 --- FC126 0 1
44595 0x11F2 Virtual Input 16 Function 0 1 1 --- FC126 0 1
44596 0x11F3 Virtual Input 17 Function 0 1 1 --- FC126 0 1
44597 0x11F4 Virtual Input 18 Function 0 1 1 --- FC126 0 1
44598 0x11F5 Virtual Input 19 Function 0 1 1 --- FC126 0 1
44599 0x11F6 Virtual Input 20 Function 0 1 1 --- FC126 0 1
44600 0x11F7 Virtual Input 21 Function 0 1 1 --- FC126 0 1
44601 0x11F8 Virtual Input 22 Function 0 1 1 --- FC126 0 1
44602 0x11F9 Virtual Input 23 Function 0 1 1 --- FC126 0 1
44603 0x11FA Virtual Input 24 Function 0 1 1 --- FC126 0 1
44604 0x11FB Virtual Input 25 Function 0 1 1 --- FC126 0 1
44605 0x11FC Virtual Input 26 Function 0 1 1 --- FC126 0 1
44606 0x11FD Virtual Input 27 Function 0 1 1 --- FC126 0 1
44607 0x11FE Virtual Input 28 Function 0 1 1 --- FC126 0 1
44608 0x11FF Virtual Input 29 Function 0 1 1 --- FC126 0 1
44609 0x1200 Virtual Input 30 Function 0 1 1 --- FC126 0 1
44610 0x1201 Virtual Input 31 Function 0 1 1 --- FC126 0 1
44611 0x1202 Virtual Input 32 Function 0 1 1 --- FC126 0 1
VIRTUAL INPUT TYPE
44612 0x1203 Virtual Input 1 Type 0 1 1 --- FC199 0 1
44613 0x1204 Virtual Input 2 Type 0 1 1 --- FC199 0 1
44614 0x1205 Virtual Input 3 Type 0 1 1 --- FC199 0 1
44615 0x1206 Virtual Input 4 Type 0 1 1 --- FC199 0 1
44616 0x1207 Virtual Input 5 Type 0 1 1 --- FC199 0 1
44617 0x1208 Virtual Input 6 Type 0 1 1 --- FC199 0 1
44618 0x1209 Virtual Input 7 Type 0 1 1 --- FC199 0 1
44619 0x120A Virtual Input 8 Type 0 1 1 --- FC199 0 1
44620 0x120B Virtual Input 9 Type 0 1 1 --- FC199 0 1
44621 0x120C Virtual Input 10 Type 0 1 1 --- FC199 0 1
44622 0x120D Virtual Input 11 Type 0 1 1 --- FC199 0 1
44623 0x120E Virtual Input 12 Type 0 1 1 --- FC199 0 1

12-56 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44624 0x120F Virtual Input 13 Type 0 1 1 --- FC199 0 1
44625 0x1210 Virtual Input 14 Type 0 1 1 --- FC199 0 1
44626 0x1211 Virtual Input 15 Type 0 1 1 --- FC199 0 1
44627 0x1212 Virtual Input 16 Type 0 1 1 --- FC199 0 1
44628 0x1213 Virtual Input 17 Type 0 1 1 --- FC199 0 1
44629 0x1214 Virtual Input 18 Type 0 1 1 --- FC199 0 1
44630 0x1215 Virtual Input 19 Type 0 1 1 --- FC199 0 1
44631 0x1216 Virtual Input 20 Type 0 1 1 --- FC199 0 1
44632 0x1217 Virtual Input 21 Type 0 1 1 --- FC199 0 1
44633 0x1218 Virtual Input 22 Type 0 1 1 --- FC199 0 1
44634 0x1219 Virtual Input 23 Type 0 1 1 --- FC199 0 1
44635 0x121A Virtual Input 24 Type 0 1 1 --- FC199 0 1
44636 0x121B Virtual Input 25 Type 0 1 1 --- FC199 0 1
44637 0x121C Virtual Input 26 Type 0 1 1 --- FC199 0 1
44638 0x121D Virtual Input 27 Type 0 1 1 --- FC199 0 1
44639 0x121E Virtual Input 28 Type 0 1 1 --- FC199 0 1
44640 0x121F Virtual Input 29 Type 0 1 1 --- FC199 0 1
44641 0x1220 Virtual Input 30 Type 0 1 1 --- FC199 0 1
44642 0x1221 Virtual Input 31 Type 0 1 1 --- FC199 0 1
44643 0x1222 Virtual Input 32 Type 0 1 1 --- FC199 0 1
IEC61850 GOOSE
44645 0x1224 Enable GOOSE Transmission 0 1 1 --- FC126 0 1
44646 0x1225 Enable GOOSE 0 1 1 --- FC126 0 1
44647 0x1226 GOOSE Name 0 20 1 --- F22 20
SR3_GOOSE
1
44667 0x123A VLAN Identifier 0 4095 1 --- F1 0 1
44668 0x123B VLAN Priority 1 7 1 --- F1 4 1
44669 0x123C Application Identifier 0 0x3FFF 1 --- F1 0 1
44670 0x123D Update Time 1000 60000 1 ms F1 10000 1
44671 0x123E DataSet Name 0 20 1 --- F22 GOOSE1 20
44691 0x1252 Control Block Name 0 20 1 --- F22 gcb01 20
44711 0x1266 Conf Revision Number 1 0xFFFF 1 --- F1 1 1
44712 0x1267 Destination MAC Address 0 0xFFFF 1 --- FC214 0 3
44715 0x126A MMS TCP Port Number 1 65535 1 --- F1 102 1
44716 0x126B TCP Connection Timeout 10 1800 1 s F1 120 1
IEC61850 GOOSE TRANSMISSION DATASET ITEMS
44718 0x126D DataSet Item 1 0 0xFFFF 1 --- FC134B 0 1
44719 0x126E Item 1 Quality 0 1 1 --- FC126 0 1
44720 0x126F DataSet Item 2 0 0xFFFF 1 --- FC134B 0 1
44721 0x1270 Item 2 Quality 0 1 1 --- FC126 0 1
44722 0x1271 DataSet Item 3 0 0xFFFF 1 --- FC134B 0 1
44723 0x1272 Item 3 Quality 0 1 1 --- FC126 0 1
44724 0x1273 DataSet Item 4 0 0xFFFF 1 --- FC134B 0 1
44725 0x1274 Item 4 Quality 0 1 1 --- FC126 0 1
44726 0x1275 DataSet Item 5 0 0xFFFF 1 --- FC134B 0 1
44727 0x1276 Item 5 Quality 0 1 1 --- FC126 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-57


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44728 0x1277 DataSet Item 6 0 0xFFFF 1 --- FC134B 0 1
44729 0x1278 Item 6 Quality 0 1 1 --- FC126 0 1
44730 0x1279 DataSet Item 7 0 0xFFFF 1 --- FC134B 0 1
44731 0x127A Item 7 Quality 0 1 1 --- FC126 0 1
44732 0x127B DataSet Item 8 0 0xFFFF 1 --- FC134B 0 1
44733 0x127C Item 8 Quality 0 1 1 --- FC126 0 1
44734 0x127D DataSet Item 9 0 0xFFFF 1 --- FC134B 0 1
44735 0x127E Item 9 Quality 0 1 1 --- FC126 0 1
44736 0x127F DataSet Item 10 0 0xFFFF 1 --- FC134B 0 1
44737 0x1280 Item 10 Quality 0 1 1 --- FC126 0 1
44738 0x1281 DataSet Item 11 0 0xFFFF 1 --- FC134B 0 1
44739 0x1282 Item 11 Quality 0 1 1 --- FC126 0 1
44740 0x1283 DataSet Item 12 0 0xFFFF 1 --- FC134B 0 1
44741 0x1284 Item 12 Quality 0 1 1 --- FC126 0 1
44742 0x1285 DataSet Item 13 0 0xFFFF 1 --- FC134B 0 1
44743 0x1286 Item 13 Quality 0 1 1 --- FC126 0 1
44744 0x1287 DataSet Item 14 0 0xFFFF 1 --- FC134B 0 1
44745 0x1288 Item 14 Quality 0 1 1 --- FC126 0 1
44746 0x1289 DataSet Item 15 0 0xFFFF 1 --- FC134B 0 1
44747 0x128A Item 15 Quality 0 1 1 --- FC126 0 1
44748 0x128B DataSet Item 16 0 0xFFFF 1 --- FC134B 0 1
44749 0x128C Item 16 Quality 0 1 1 --- FC126 0 1
44750 0x128D DataSet Item 17 0 0xFFFF 1 --- FC134B 0 1
44751 0x128E Item 17 Quality 0 1 1 --- FC126 0 1
44752 0x128F DataSet Item 18 0 0xFFFF 1 --- FC134B 0 1
44753 0x1290 Item 18 Quality 0 1 1 --- FC126 0 1
44754 0x1291 DataSet Item 19 0 0xFFFF 1 --- FC134B 0 1
44755 0x1292 Item 19 Quality 0 1 1 --- FC126 0 1
44756 0x1293 DataSet Item 20 0 0xFFFF 1 --- FC134B 0 1
44757 0x1294 Item 20 Quality 0 1 1 --- FC126 0 1
44758 0x1295 DataSet Item 21 0 0xFFFF 1 --- FC134B 0 1
44759 0x1296 Item 21 Quality 0 1 1 --- FC126 0 1
44760 0x1297 DataSet Item 22 0 0xFFFF 1 --- FC134B 0 1
44761 0x1298 Item 22 Quality 0 1 1 --- FC126 0 1
44762 0x1299 DataSet Item 23 0 0xFFFF 1 --- FC134B 0 1
44763 0x129A Item 23 Quality 0 1 1 --- FC126 0 1
44764 0x129B DataSet Item 24 0 0xFFFF 1 --- FC134B 0 1
44765 0x129C Item 24 Quality 0 1 1 --- FC126 0 1
44766 0x129D DataSet Item 25 0 0xFFFF 1 --- FC134B 0 1
44767 0x129E Item 25 Quality 0 1 1 --- FC126 0 1
44768 0x129F DataSet Item 26 0 0xFFFF 1 --- FC134B 0 1
44769 0x12A0 Item 26 Quality 0 1 1 --- FC126 0 1
44770 0x12A1 DataSet Item 27 0 0xFFFF 1 --- FC134B 0 1
44771 0x12A2 Item 27 Quality 0 1 1 --- FC126 0 1
44772 0x12A3 DataSet Item 28 0 0xFFFF 1 --- FC134B 0 1
44773 0x12A4 Item 28 Quality 0 1 1 --- FC126 0 1

12-58 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44774 0x12A5 DataSet Item 29 0 0xFFFF 1 --- FC134B 0 1
44775 0x12A6 Item 29 Quality 0 1 1 --- FC126 0 1
44776 0x12A7 DataSet Item 30 0 0xFFFF 1 --- FC134B 0 1
44777 0x12A8 Item 30 Quality 0 1 1 --- FC126 0 1
44778 0x12A9 DataSet Item 31 0 0xFFFF 1 --- FC134B 0 1
44779 0x12AA Item 31 Quality 0 1 1 --- FC126 0 1
44780 0x12AB DataSet Item 32 0 0xFFFF 1 --- FC134B 0 1
44781 0x12AC Item 32 Quality 0 1 1 --- FC126 0 1
IEC61850 GOOSE RX1 CONFIGURATION
44786 0x12B1 Rx GOOSE1 Function 0 1 1 --- FC126 0 1
44787 0x12B2 Rx GOOSE1 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE1
44807 0x12C6 Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
44827 0x12DA RX1 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb01
44847 0x12EE RX1 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
44848 0x12EF EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX2 CONFIGURATION
44852 0x12F3 Rx GOOSE2 Function 0 1 1 --- FC126 0 1
44853 0x12F4 Rx GOOSE2 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE2
44873 0x1308 Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
44893 0x131C RX2 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb02
44913 0x1330 RX2 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
44914 0x1331 EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX3 CONFIGURATION
44918 0x1335 Rx GOOSE3 Function 0 1 1 --- FC126 0 1
44919 0x1336 Rx GOOSE3 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE3
44939 0x134A Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
44959 0x135E RX3 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb03
44979 0x1372 RX3 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
44980 0x1373 EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX4 CONFIGURATION
44984 0x1377 Rx GOOSE4 Function 0 1 1 --- FC126 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-59


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
44985 0x1378 Rx GOOSE4 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE4
45005 0x138C Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
45025 0x13A0 RX4 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb04
45045 0x13B4 RX4 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
45046 0x13B5 EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX5 CONFIGURATION
45050 0x13B9 Rx GOOSE5 Function 0 1 1 --- FC126 0 1
45051 0x13BA Rx GOOSE5 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE5
45071 0x13CE Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
45091 0x13E2 RX5 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb05
45111 0x13F6 RX5 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
45112 0x13F7 EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX6 CONFIGURATION
45116 0x13FB Rx GOOSE6 Function 0 1 1 --- FC126 0 1
45117 0x13FC Rx GOOSE6 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE6
45137 0x1410 Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
45157 0x1424 RX6 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb06
45177 0x1438 RX6 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
45178 0x1439 EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX7 CONFIGURATION
45182 0x143D Rx GOOSE7 Function 0 1 1 --- FC126 0 1
45183 0x143E Rx GOOSE7 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE7
45203 0x1452 Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
45223 0x1466 RX7 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb07
45243 0x147A RX7 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
45244 0x147B EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE RX8 CONFIGURATION
45248 0x147F Rx GOOSE8 Function 0 1 1 --- FC126 0 1

12-60 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
45249 0x1480 Rx GOOSE8 ID 0 20 1 --- F22 20
DEVICE_IED
2_GOOSE8
45269 0x1494 Incoming GOOSE DataSet 0 20 1 --- F22 DEVICE/ 20
Name LLN0$GOOS
ESR3
45289 0x14A8 RX8 Control Block Name 0 20 1 --- F22 DEVICE/ 20
LLN0$GO$g
cb08
45309 0x14BC RX8 DataSet Configuration 1 0xFFFF 1 --- F1 1 1
Revision
45310 0x14BD EType AppID 0 0x3FFF 1 --- F1 0 1
IEC61850 GOOSE DATASET STRUCTURE BUFFER
45314 0x14C1 DataSet Struct Buffer 0 0xFFFF 1 --- FC216 0 250
IEC61850 GOOSE REMOTE INPUTS
45567 0x15BE Remote Input 1 Name 0 7 1 --- F22 RI 1 7
45583 0x15CE Remote Input 1 GOOSE 0 0x80 1 --- FC219 0 1
Source
45584 0x15CF Remote Input 1 Item Source 0 0xFFFF 1 --- FC217 0 1
45585 0x15D0 Remote Input 1 Item Mask 0 0xFFFF 1 --- FC218 0 1
45586 0x15D1 Remote Input 1 Default 0 3 1 --- FC220 1 1
State
45588 0x15D3 Remote Input 2 Name 0 7 1 --- F22 RI 2 7
45604 0x15E3 Remote Input 2 GOOSE 0 0x80 1 --- FC219 0 1
Source
45605 0x15E4 Remote Input 2 Item Source 0 0xFFFF 1 --- FC217 0 1
45606 0x15E5 Remote Input 2 Item Mask 0 0xFFFF 1 --- FC218 0 1
45607 0x15E6 Remote Input 2 Default 0 3 1 --- FC220 1 1
State
45609 0x15E8 Remote Input 3 Name 0 7 1 --- F22 RI 3 7
45625 0x15F8 Remote Input 3 GOOSE 0 0x80 1 --- FC219 0 1
Source
45626 0x15F9 Remote Input 3 Item Source 0 0xFFFF 1 --- FC217 0 1
45627 0x15FA Remote Input 3 Item Mask 0 0xFFFF 1 --- FC218 0 1
45628 0x15FB Remote Input 3 Default 0 3 1 --- FC220 1 1
State
45630 0x15FD Remote Input 4 Name 0 7 1 --- F22 RI 4 7
45646 0x160D Remote Input 4 GOOSE 0 0x80 1 --- FC219 0 1
Source
45647 0x160E Remote Input 4 Item Source 0 0xFFFF 1 --- FC217 0 1
45648 0x160F Remote Input 4 Item Mask 0 0xFFFF 1 --- FC218 0 1
45649 0x1610 Remote Input 4 Default 0 3 1 --- FC220 1 1
State
45651 0x1612 Remote Input 5 Name 0 7 1 --- F22 RI 5 7
45667 0x1622 Remote Input 5 GOOSE 0 0x80 1 --- FC219 0 1
Source
45668 0x1623 Remote Input 5 Item Source 0 0xFFFF 1 --- FC217 0 1
45669 0x1624 Remote Input 5 Item Mask 0 0xFFFF 1 --- FC218 0 1
45670 0x1625 Remote Input 5 Default 0 3 1 --- FC220 1 1
State
45672 0x1627 Remote Input 6 Name 0 7 1 --- F22 RI 6 7
45688 0x1637 Remote Input 6 GOOSE 0 0x80 1 --- FC219 0 1
Source

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-61


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
45689 0x1638 Remote Input 6 Item Source 0 0xFFFF 1 --- FC217 0 1
45690 0x1639 Remote Input 6 Item Mask 0 0xFFFF 1 --- FC218 0 1
45691 0x163A Remote Input 6 Default 0 3 1 --- FC220 1 1
State
45693 0x163C Remote Input 7 Name 0 7 1 --- F22 RI 7 7
45709 0x164C Remote Input 7 GOOSE 0 0x80 1 --- FC219 0 1
Source
45710 0x164D Remote Input 7 Item Source 0 0xFFFF 1 --- FC217 0 1
45711 0x164E Remote Input 7 Item Mask 0 0xFFFF 1 --- FC218 0 1
45712 0x164F Remote Input 7 Default 0 3 1 --- FC220 1 1
State
45714 0x1651 Remote Input 8 Name 0 7 1 --- F22 RI 8 7
45730 0x1661 Remote Input 8 GOOSE 0 0x80 1 --- FC219 0 1
Source
45731 0x1662 Remote Input 8 Item Source 0 0xFFFF 1 --- FC217 0 1
45732 0x1663 Remote Input 8 Item Mask 0 0xFFFF 1 --- FC218 0 1
45733 0x1664 Remote Input 8 Default 0 3 1 --- FC220 1 1
State
45735 0x1666 Remote Input 9 Name 0 7 1 --- F22 RI 9 7
45751 0x1676 Remote Input 9 GOOSE 0 0x80 1 --- F1 0 1
Source
45752 0x1677 Remote Input 9 Item Source 0 0xFFFF 1 --- FC217 0 1
45753 0x1678 Remote Input 9 Item Mask 0 0xFFFF 1 --- FC218 0 1
45754 0x1679 Remote Input 9 Default 0 3 1 --- FC220 1 1
State
45756 0x167B Remote Input 10 Name 0 7 1 --- F22 RI 10 7
45772 0x168B Remote Input 10 GOOSE 0 0x80 1 --- F1 0 1
Source
45773 0x168C Remote Input 10 Item 0 0xFFFF 1 --- FC217 0 1
Source
45774 0x168D Remote Input 10 Item Mask 0 0xFFFF 1 --- FC218 0 1
45775 0x168E Remote Input 10 Default 0 3 1 --- FC220 1 1
State
45777 0x1690 Remote Input 11 Name 0 7 1 --- F22 RI 11 7
45793 0x16A0 Remote Input 11 GOOSE 0 0x80 1 --- F1 0 1
Source
45794 0x16A1 Remote Input 11 Item 0 0xFFFF 1 --- FC217 0 1
Source
45795 0x16A2 Remote Input 11 Item Mask 0 0xFFFF 1 --- FC218 0 1
45796 0x16A3 Remote Input 11 Default 0 3 1 --- FC220 1 1
State
45798 0x16A5 Remote Input 12 Name 0 7 1 --- F22 RI 12 7
45814 0x16B5 Remote Input 12 GOOSE 0 0x80 1 --- F1 0 1
Source
45815 0x16B6 Remote Input 12 Item 0 0xFFFF 1 --- FC217 0 1
Source
45816 0x16B7 Remote Input 12 Item Mask 0 0xFFFF 1 --- FC218 0 1
45817 0x16B8 Remote Input 12 Default 0 3 1 --- FC220 1 1
State
45819 0x16BA Remote Input 13 Name 0 7 1 --- F22 RI 13 7
45835 0x16CA Remote Input 13 GOOSE 0 0x80 1 --- F1 0 1
Source

12-62 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
45836 0x16CB Remote Input 13 Item 0 0xFFFF 1 --- FC217 0 1
Source
45837 0x16CC Remote Input 13 Item Mask 0 0xFFFF 1 --- FC218 0 1
45838 0x16CD Remote Input 13 Default 0 3 1 --- FC220 1 1
State
45840 0x16CF Remote Input 14 Name 0 7 1 --- F22 RI 14 7
45856 0x16DF Remote Input 14 GOOSE 0 0x80 1 --- F1 0 1
Source
45857 0x16E0 Remote Input 14 Item 0 0xFFFF 1 --- FC217 0 1
Source
45858 0x16E1 Remote Input 14 Item Mask 0 0xFFFF 1 --- FC218 0 1
45859 0x16E2 Remote Input 14 Default 0 3 1 --- FC220 1 1
State
45861 0x16E4 Remote Input 15 Name 0 7 1 --- F22 RI 15 7
45877 0x16F4 Remote Input 15 GOOSE 0 0x80 1 --- F1 0 1
Source
45878 0x16F5 Remote Input 15 Item 0 0xFFFF 1 --- FC217 0 1
Source
45879 0x16F6 Remote Input 15 Item Mask 0 0xFFFF 1 --- FC218 0 1
45880 0x16F7 Remote Input 15 Default 0 3 1 --- FC220 1 1
State
45882 0x16F9 Remote Input 16 Name 0 7 1 --- F22 RI 16 7
45898 0x1709 Remote Input 16 GOOSE 0 0x80 1 --- F1 0 1
Source
45899 0x170A Remote Input 16 Item 0 0xFFFF 1 --- FC217 0 1
Source
45900 0x170B Remote Input 16 Item Mask 0 0xFFFF 1 --- FC218 0 1
45901 0x170C Remote Input 16 Default 0 3 1 --- FC220 1 1
State
45903 0x170E Remote Input 17 Name 0 7 1 --- F22 RI 17 7
45919 0x171E Remote Input 17 GOOSE 0 0x80 1 --- F1 0 1
Source
45920 0x171F Remote Input 17 Item 0 0xFFFF 1 --- FC217 0 1
Source
45921 0x1720 Remote Input 17 Item Mask 0 0xFFFF 1 --- FC218 0 1
45922 0x1721 Remote Input 17 Default 0 3 1 --- FC220 1 1
State
45924 0x1723 Remote Input 18 Name 0 7 1 --- F22 RI 18 7
45940 0x1733 Remote Input 18 GOOSE 0 0x80 1 --- F1 0 1
Source
45941 0x1734 Remote Input 18 Item 0 0xFFFF 1 --- FC217 0 1
Source
45942 0x1735 Remote Input 18 Item Mask 0 0xFFFF 1 --- FC218 0 1
45943 0x1736 Remote Input 18 Default 0 3 1 --- FC220 1 1
State
45945 0x1738 Remote Input 19 Name 0 7 1 --- F22 RI 19 7
45961 0x1748 Remote Input 19 GOOSE 0 0x80 1 --- F1 0 1
Source
45962 0x1749 Remote Input 19 Item 0 0xFFFF 1 --- FC217 0 1
Source
45963 0x174A Remote Input 19 Item Mask 0 0xFFFF 1 --- FC218 0 1
45964 0x174B Remote Input 19 Default 0 3 1 --- FC220 1 1
State

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-63


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
45966 0x174D Remote Input 20 Name 0 7 1 --- F22 RI 20 7
45982 0x175D Remote Input 20 GOOSE 0 0x80 1 --- F1 0 1
Source
45983 0x175E Remote Input 20 Item 0 0xFFFF 1 --- FC217 0 1
Source
45984 0x175F Remote Input 20 Item Mask 0 0xFFFF 1 --- FC218 0 1
45985 0x1760 Remote Input 20 Default 0 3 1 --- FC220 1 1
State
45987 0x1762 Remote Input 21 Name 0 7 1 --- F22 RI 21 7
46003 0x1772 Remote Input 21 GOOSE 0 0x80 1 --- F1 0 1
Source
46004 0x1773 Remote Input 21 Item 0 0xFFFF 1 --- FC217 0 1
Source
46005 0x1774 Remote Input 21 Item Mask 0 0xFFFF 1 --- FC218 0 1
46006 0x1775 Remote Input 21 Default 0 3 1 --- FC220 1 1
State
46008 0x1777 Remote Input 22 Name 0 7 1 --- F22 RI 22 7
46024 0x1787 Remote Input 22 GOOSE 0 0x80 1 --- F1 0 1
Source
46025 0x1788 Remote Input 22 Item 0 0xFFFF 1 --- FC217 0 1
Source
46026 0x1789 Remote Input 22 Item Mask 0 0xFFFF 1 --- FC218 0 1
46027 0x178A Remote Input 22 Default 0 3 1 --- FC220 1 1
State
46029 0x178C Remote Input 23 Name 0 7 1 --- F22 RI 23 7
46045 0x179C Remote Input 23 GOOSE 0 0x80 1 --- F1 0 1
Source
46046 0x179D Remote Input 23 Item 0 0xFFFF 1 --- FC217 0 1
Source
46047 0x179E Remote Input 23 Item Mask 0 0xFFFF 1 --- FC218 0 1
46048 0x179F Remote Input 23 Default 0 3 1 --- FC220 1 1
State
46050 0x17A1 Remote Input 24 Name 0 7 1 --- F22 RI 24 7
46066 0x17B1 Remote Input 24 GOOSE 0 0x80 1 --- F1 0 1
Source
46067 0x17B2 Remote Input 24 Item 0 0xFFFF 1 --- FC217 0 1
Source
46068 0x17B3 Remote Input 24 Item Mask 0 0xFFFF 1 --- FC218 0 1
46069 0x17B4 Remote Input 24 Default 0 3 1 --- FC220 1 1
State
46071 0x17B6 Remote Input 25 Name 0 7 1 --- F22 RI 25 7
46087 0x17C6 Remote Input 25 GOOSE 0 0x80 1 --- F1 0 1
Source
46088 0x17C7 Remote Input 25 Item 0 0xFFFF 1 --- FC217 0 1
Source
46089 0x17C8 Remote Input 25 Item Mask 0 0xFFFF 1 --- FC218 0 1
46090 0x17C9 Remote Input 25 Default 0 3 1 --- FC220 1 1
State
46092 0x17CB Remote Input 26 Name 0 7 1 --- F22 RI 26 7
46108 0x17DB Remote Input 26 GOOSE 0 0x80 1 --- F1 0 1
Source
46109 0x17DC Remote Input 26 Item 0 0xFFFF 1 --- FC217 0 1
Source

12-64 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
46110 0x17DD Remote Input 26 Item Mask 0 0xFFFF 1 --- FC218 0 1
46111 0x17DE Remote Input 26 Default 0 3 1 --- FC220 1 1
State
46113 0x17E0 Remote Input 27 Name 0 7 1 --- F22 RI 27 7
46129 0x17F0 Remote Input 27 GOOSE 0 0x80 1 --- F1 0 1
Source
46130 0x17F1 Remote Input 27 Item 0 0xFFFF 1 --- FC217 0 1
Source
46131 0x17F2 Remote Input 27 Item Mask 0 0xFFFF 1 --- FC218 0 1
46132 0x17F3 Remote Input 27 Default 0 3 1 --- FC220 1 1
State
46134 0x17F5 Remote Input 28 Name 0 7 1 --- F22 RI 28 7
46150 0x1805 Remote Input 28 GOOSE 0 0x80 1 --- F1 0 1
Source
46151 0x1806 Remote Input 28 Item 0 0xFFFF 1 --- FC217 0 1
Source
46152 0x1807 Remote Input 28 Item Mask 0 0xFFFF 1 --- FC218 0 1
46153 0x1808 Remote Input 28 Default 0 3 1 --- FC220 1 1
State
46155 0x180A Remote Input 29 Name 0 7 1 --- F22 RI 29 7
46171 0x181A Remote Input 29 GOOSE 0 0x80 1 --- F1 0 1
Source
46172 0x181B Remote Input 29 Item 0 0xFFFF 1 --- FC217 0 1
Source
46173 0x181C Remote Input 29 Item Mask 0 0xFFFF 1 --- FC218 0 1
46174 0x181D Remote Input 29 Default 0 3 1 --- FC220 1 1
State
46176 0x181F Remote Input 30 Name 0 7 1 --- F22 RI 30 7
46192 0x182F Remote Input 30 GOOSE 0 0x80 1 --- F1 0 1
Source
46193 0x1830 Remote Input 30 Item 0 0xFFFF 1 --- FC217 0 1
Source
46194 0x1831 Remote Input 30 Item Mask 0 0xFFFF 1 --- FC218 0 1
46195 0x1832 Remote Input 30 Default 0 3 1 --- FC220 1 1
State
46197 0x1834 Remote Input 31 Name 0 7 1 --- F22 RI 31 7
46213 0x1844 Remote Input 31 GOOSE 0 0x80 1 --- F1 0 1
Source
46214 0x1845 Remote Input 31 Item 0 0xFFFF 1 --- FC217 0 1
Source
46215 0x1846 Remote Input 31 Item Mask 0 0xFFFF 1 --- FC218 0 1
46216 0x1847 Remote Input 31 Default 0 3 1 --- FC220 1 1
State
46218 0x1849 Remote Input 32 Name 0 7 1 --- F22 RI 32 7
46234 0x1859 Remote Input 32 GOOSE 0 0x80 1 --- F1 0 1
Source
46235 0x185A Remote Input 32 Item 0 0xFFFF 1 --- FC217 0 1
Source
46236 0x185B Remote Input 32 Item Mask 0 0xFFFF 1 --- FC218 0 1
46237 0x185C Remote Input 32 Default 0 3 1 --- FC220 1 1
State
ARC FLASH
46415 0x190E Arc Flash Function 0 4 1 --- FC205 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-65


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
46416 0x190F Arc Flash HS Phase Pickup 5 3000 1 x CT F3 200 1
46417 0x1910 Arc Flash HS Ground Pickup 5 3000 1 x CT F3 100 1
46418 0x1911 Arc Flash Light Sensor 1 0 1 1 --- FC126 0 1
46419 0x1912 Arc Flash Light Sensor 2 0 1 1 --- FC126 0 1
46420 0x1913 Arc Flash Light Sensor 3 0 1 1 --- FC126 0 1
46421 0x1914 Arc Flash Light Sensor 4 0 1 1 --- FC126 0 1
46422 0x1915 Arc Flash Block 0 0xEF02 1 --- F89 0 1
46423 0x1916 Arc Flash Output Relays 5-6 0 0x7F 1 --- FC198 0 1
46424 0x1917 Arc Flash HS Sens Ground 5 3000 1 x CT F17A 100 1
Pickup
46425 0x1918 Arc Flash Heartbeat Delay 0 1440 1 min F1C 10 1
46426 0x1919 Arc Flash Seal-in Timer 0 999 1 s F3 100 1
BKR HEALTH
46428 0x191B Breaker Health Function 0 2 1 --- FC206 0 1
46429 0x191C Breaker Health Mode 0 1 1 --- FC433 0 1
46430 0x191D Breaker Health Limit 0 100000 1 --- F9 0 2
46432 0x191F Breaker Health Trip Time 0 1000 1 s F3 5 1
Pickup
46433 0x1920 Breaker Health Close Time 0 1000 1 s F3 5 1
Pickup
46434 0x1921 Breaker Health Charge Time 0 6000 1 s F3 1500 1
Pickup
46435 0x1922 Breaker Health Spring 0 0xEF02 1 --- F89A 0 1
Charge Input
46436 0x1923 Breaker Health Block1 0 0xEF02 1 --- F89 0 1
46437 0x1924 Breaker Health Block2 0 0xEF02 1 --- F89 0 1
46438 0x1925 Breaker Health Block3 0 0xEF02 1 --- F89 0 1
46439 0x1926 Breaker Health Output 0 0x7F 1 --- FC198 0 1
Relays
46452 0x1933 Breaker Health Incomp Trp/ 0 60000 1 s F3 10 1
Cls Time
46453 0x1934 Breaker Health Incomp 0 60000 1 s F3 4500 1
Charge Time
LOGIC ELEMENT NAMES
46240 0x185F Logic Element 1 Name 0 9 1 --- F22 Logic El #1 9
46249 0x1868 Logic Element 2 Name 0 9 1 --- F22 Logic El #2 9
46258 0x1871 Logic Element 3 Name 0 9 1 --- F22 Logic El #3 9
46267 0x187A Logic Element 4 Name 0 9 1 --- F22 Logic El #4 9
46276 0x1883 Logic Element 5 Name 0 9 1 --- F22 Logic El #5 9
46285 0x188C Logic Element 6 Name 0 9 1 --- F22 Logic El #6 9
46294 0x1895 Logic Element 7 Name 0 9 1 --- F22 Logic El #7 9
46303 0x189E Logic Element 8 Name 0 9 1 --- F22 Logic El #8 9
46492 0x195B Logic Element 9 Name 0 9 1 --- F22 Logic El #9 9
46501 0x1964 Logic Element 10 Name 0 9 1 --- F22 Logic El 9
#10
46510 0x196D Logic Element 11 Name 0 9 1 --- F22 Logic El 9
#11
46519 0x1976 Logic Element 12 Name 0 9 1 --- F22 Logic El 9
#12

12-66 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
46528 0x197F Logic Element 13 Name 0 9 1 --- F22 Logic El 9
#13
46537 0x1988 Logic Element 14 Name 0 9 1 --- F22 Logic El 9
#14
46546 0x1991 Logic Element 15 Name 0 9 1 --- F22 Logic El 9
#15
46555 0x199A Logic Element 16 Name 0 9 1 --- F22 Logic El 9
#16
SYNCROCHECK
46737 0x1A50 Synchrocheck function 0 0xFFFFFFFF 1 --- FC126 0 1
enable
46738 0x1A51 Dead bus voltage level 0 125 1 x VT F3 10 1
46739 0x1A52 Live bus voltage level 3 125 1 x VT F3 50 1
46740 0x1A53 Dead line voltage level 0 125 1 x VT F3 10 1
46741 0x1A54 Live line voltage level 3 125 1 x VT F3 50 1
46742 0x1A55 Voltage Difference 10 10000 1 V F1 1000 1
46743 0x1A56 Angle Difference 2 80 1 ° F1 10 1
46744 0x1A57 Frequency Slip 5 500 1 Hz F3 5 1
46745 0x1A58 Breaker Closing Time 0 100 1 s F3 10 1
46746 0x1A59 Dead Condition 0 7 1 --- FC424 0 1
46747 0x1A5A Snapshots Events 0 0xEF02 1 --- F89 0 1
46748 0x1A5B Output Relays 3-7 0 0x7F 1 --- FC198 0 1
46749 0x1A5C Angle Offset 0 359 1 ° F1 0 1
46750 0x1A5D Synchro Bypass 0 0x1DF 1 --- F89B 0 1
OPCUA
46773 0x1A74 OPCUA Enable 0 1 1 --- FC126 0 1
HSR PRP SETTINGS
46771 0x1A72 LLA Priority 0 1 1 --- FC126 1 1
46772 0x1A73 LLA Timeout 0 65535 1 s F1 300 1
46774 0x1A75 Redundancy mode 0 5 1 --- FC421 0 1
46775 0x1A76 PTP Function 0 1 1 --- FC126 0 1
46776 0x1A77 PTP Port A Path Delay Adder 0 0xFFFFFFFF 1 --- F9 0 2
46778 0x1A79 PTP Port A Path Delay -32767 32767 1 --- F4 0 1
Assymetry
46779 0x1A7A PTP Port B Path Delay Adder 0 0xFFFFFFFF 1 --- F9 0 2
46781 0x1A7C PTP Port B Path Delay -32767 32767 1 --- F4 0 1
Assymetry
46782 0x1A7D PTP Strict Power Profile 0 1 1 --- FC126 0 1
46783 0x1A7E PTP Domain Number 0 255 1 --- F1 0 1
46784 0x1A7F PTP VLAN Priority 0 7 1 --- F1 4 1
46785 0x1A80 PTP VLAN ID 0 4095 1 --- F1 0 1
46786 0x1A81 PTP EPOCH 0 3 1 --- FC425 0 1
46787 0x1A82 RSTP Bridge Priority 0 61440 4096 --- F9 32768 2
46789 0x1A84 Port A Priority 0 240 16 --- F9 128 2
46791 0x1A86 Port A Path Cost 0 2000000 1 --- F9 200000 2
46793 0x1A88 Port B Priority 0 240 16 --- F9 128 2
46795 0x1A8A Port B Path Cost 0 2000000 1 --- F9 200000 2
SECOND HARMONIC INHIBIT

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-67


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
46851 0x1AC2 Hrmc 2nd Function 0 3 1 --- FC207 0 1
46852 0x1AC3 Hrmc 2nd Pickup 1 400 1 % F2 200 1
46853 0x1AC4 Hrmc 2nd Delay 0 60000 1 s F3 0 1
46854 0x1AC5 Hrmc 2nd Phases for OP 0 3 1 --- F92A 0 1
46855 0x1AC6 Hrmc 2nd Min OP Current 3 300 1 x CT F3 100 1
46856 0x1AC7 Hrmc 2nd Output Relays 3-6 0 0x3F 1 --- FC198 0 1
PHASE UNDERVOLTAGE3
46897 0x1AF0 Phase UV 3 Function 0 3 1 --- FC197 0 1
46898 0x1AF1 Phase UV 3 Pickup 0 125 1 x VT F3 75 1
46899 0x1AF2 Phase UV 3 Curve 0 1 1 --- F93 1 1
46900 0x1AF3 Phase UV 3 Delay 0 60000 1 s F3 200 1
46901 0x1AF4 Phase UV 3 Phases 1 3 1 --- F92 1 1
46902 0x1AF5 Phase UV 3 Min Voltage 0 125 1 x VT F3 30 1
PHASE UNDERVOLTAGE3 (RELAYS & BLOCKS)
46903 0x1AF6 Phase UV3 Relays 0 0x7F 1 --- FC198 0 1
46904 0x1AF7 Phase UV 3 Block 1 0 0xEF02 1 --- F89 0 1
46905 0x1AF8 Phase UV 3 Block 2 0 0xEF02 1 --- F89 0 1
46906 0x1AF9 Phase UV 3 Block 3 0 0xEF02 1 --- F89 0 1
PHASE UNDERVOLTAGE4
46907 0x1AFA Phase UV 4 Function 0 3 1 --- FC197 0 1
46908 0x1AFB Phase UV 4 Pickup 0 125 1 x VT F3 75 1
46909 0x1AFC Phase UV 4 Curve 0 1 1 --- F93 1 1
46910 0x1AFD Phase UV 4 Delay 0 60000 1 s F3 200 1
46911 0x1AFE Phase UV 4 Phases 1 3 1 --- F92 1 1
46912 0x1AFF Phase UV 4 Min Voltage 0 125 1 x VT F3 30 1
PHASE UNDERVOLTAGE4 (RELAYS & BLOCKS)
46913 0x1B00 Phase UV4 Relays 0 0x7F 1 --- FC198 0 1
46914 0x1B01 Phase UV 4 Block 1 0 0xEF02 1 --- F89 0 1
46915 0x1B02 Phase UV 4 Block 2 0 0xEF02 1 --- F89 0 1
46916 0x1B03 Phase UV 4 Block 3 0 0xEF02 1 --- F89 0 1
PHASE OVERVOLTAGE3
46917 0x1B04 Phase OV 3 Function 0 3 1 --- FC197 0 1
46918 0x1B05 Phase OV 3 Pkp 0 125 1 x VT F3 125 1
46919 0x1B06 Phase OV 3 Delay 0 60000 1 s F3 200 1
46920 0x1B07 PH OV 3 Phases 1 3 1 --- F92 1 1
PHASE OVERVOLTAGE3 (RELAYS & BLOCKS)
46922 0x1B09 Phase OV 3 Block 1 0 0xEF02 1 --- F89 0 1
46923 0x1B0A Phase OV 3 Block 2 0 0xEF02 1 --- F89 0 1
46924 0x1B0B Phase OV 3 Block 3 0 0xEF02 1 --- F89 0 1
PHASE OVERVOLTAGE4
46925 0x1B0C Phase OV 4 Function 0 3 1 --- FC197 0 1
46926 0x1B0D Phase OV 4 Pkp 0 125 1 x VT F3 125 1
46927 0x1B0E Phase OV 4 Delay 0 60000 1 s F3 200 1
46928 0x1B0F PH OV 4 Phases 1 3 1 --- F92 1 1
PHASE OVERVOLTAGE4 (RELAYS & BLOCKS)
46921 0x1B08 Phase OV3 Relays 0 0x7F 1 --- FC198 0 1

12-68 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
46929 0x1B10 Phase OV 4 Block 1 0 0xEF02 1 --- F89 0 1
46930 0x1B11 Phase OV 4 Block 2 0 0xEF02 1 --- F89 0 1
46931 0x1B12 Phase OV 4 Block 3 0 0xEF02 1 --- F89 0 1
46932 0x1B13 Phase OV 4 Relays 0 0x7F 1 --- FC198 0 1
FAULT REPORT
46985 0x1B48 Fault Report Delay 0 60000 1 s F3 10 1
46986 0x1B49 Fault Report Trigger 0 0xFFFF 1 --- FC134E 0x8002 1
LOGIC ELEMENTS (TRIGGERS & BLOCKS)
41123 0x462 Logic Element 1 Trigger 0 5 1 --- FC149 0 1
Logic
41124 0x463 Logic Element 1 Block Logic 0 5 1 --- FC149 0 1
41131 0x46A Logic Element 2 Trigger 0 5 1 --- FC149 0 1
Logic
41132 0x46B Logic Element 2 Block Logic 0 5 1 --- FC149 0 1
41139 0x472 Logic Element 3 Trigger 0 5 1 --- FC149 0 1
Logic
41140 0x473 Logic Element 3 Block Logic 0 5 1 --- FC149 0 1
41147 0x47A Logic Element 4 Trigger 0 5 1 --- FC149 0 1
Logic
41148 0x47B Logic Element 4 Block Logic 0 5 1 --- FC149 0 1
41155 0x482 Logic Element 5 Trigger 0 5 1 --- FC149 0 1
Logic
41156 0x483 Logic Element 5 Block Logic 0 5 1 --- FC149 0 1
41163 0x48A Logic Element 6 Trigger 0 5 1 --- FC149 0 1
Logic
41164 0x48B Logic Element 6 Block Logic 0 5 1 --- FC149 0 1
41171 0x492 Logic Element 7 Trigger 0 5 1 --- FC149 0 1
Logic
41172 0x493 Logic Element 7 Block Logic 0 5 1 --- FC149 0 1
41179 0x49A Logic Element 8 Trigger 0 5 1 --- FC149 0 1
Logic
41180 0x49B Logic Element 8 Block Logic 0 5 1 --- FC149 0 1
41187 0x4A2 Logic Element 9 Trigger 0 5 1 --- FC149 0 1
Logic
41188 0x4A3 Logic Element 9 Block Logic 0 5 1 --- FC149 0 1
41195 0x4AA Logic Element 10 Trigger 0 5 1 --- FC149 0 1
Logic
41196 0x4AB Logic Element 10 Block 0 5 1 --- FC149 0 1
Logic
41203 0x4B2 Logic Element 11 Trigger 0 5 1 --- FC149 0 1
Logic
41204 0x4B3 Logic Element 11 Block 0 5 1 --- FC149 0 1
Logic
41211 0x4BA Logic Element 12 Trigger 0 5 1 --- FC149 0 1
Logic
41212 0x4BB Logic Element 12 Block 0 5 1 --- FC149 0 1
Logic
41219 0x4C2 Logic Element 13 Trigger 0 5 1 --- FC149 0 1
Logic
41220 0x4C3 Logic Element 13 Block 0 5 1 --- FC149 0 1
Logic
41227 0x4CA Logic Element 14 Trigger 0 5 1 --- FC149 0 1
Logic

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-69


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
41228 0x4CB Logic Element 14 Block 0 5 1 --- FC149 0 1
Logic
41235 0x4D2 Logic Element 15 Trigger 0 5 1 --- FC149 0 1
Logic
41236 0x4D3 Logic Element 15 Block 0 5 1 --- FC149 0 1
Logic
41243 0x4DA Logic Element 16 Trigger 0 5 1 --- FC149 0 1
Logic
41244 0x4DB Logic Element 16 Block 0 5 1 --- FC149 0 1
Logic
43470 0xD8D Logic Element 1 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43471 0xD8E Logic Element 1 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43472 0xD8F Logic Element 1 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43473 0xD90 Logic Element 1 Block 1 0 0xFFFF 1 --- FC134B 0 1
43474 0xD91 Logic Element 1 Block 2 0 0xFFFF 1 --- FC134B 0 1
43475 0xD92 Logic Element 1 Block 3 0 0xFFFF 1 --- FC134B 0 1
43476 0xD93 Logic Element 2 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43477 0xD94 Logic Element 2 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43478 0xD95 Logic Element 2 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43479 0xD96 Logic Element 2 Block 1 0 0xFFFF 1 --- FC134B 0 1
43480 0xD97 Logic Element 2 Block 2 0 0xFFFF 1 --- FC134B 0 1
43481 0xD98 Logic Element 2 Block 3 0 0xFFFF 1 --- FC134B 0 1
43482 0xD99 Logic Element 3 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43483 0xD9A Logic Element 3 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43484 0xD9B Logic Element 3 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43485 0xD9C Logic Element 3 Block 1 0 0xFFFF 1 --- FC134B 0 1
43486 0xD9D Logic Element 3 Block 2 0 0xFFFF 1 --- FC134B 0 1
43487 0xD9E Logic Element 3 Block 3 0 0xFFFF 1 --- FC134B 0 1
43488 0xD9F Logic Element 4 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43489 0xDA0 Logic Element 4 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43490 0xDA1 Logic Element 4 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43491 0xDA2 Logic Element 4 Block 1 0 0xFFFF 1 --- FC134B 0 1
43492 0xDA3 Logic Element 4 Block 2 0 0xFFFF 1 --- FC134B 0 1
43493 0xDA4 Logic Element 4 Block 3 0 0xFFFF 1 --- FC134B 0 1
43494 0xDA5 Logic Element 5 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43495 0xDA6 Logic Element 5 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43496 0xDA7 Logic Element 5 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43497 0xDA8 Logic Element 5 Block 1 0 0xFFFF 1 --- FC134B 0 1
43498 0xDA9 Logic Element 5 Block 2 0 0xFFFF 1 --- FC134B 0 1
43499 0xDAA Logic Element 5 Block 3 0 0xFFFF 1 --- FC134B 0 1
43500 0xDAB Logic Element 6 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43501 0xDAC Logic Element 6 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43502 0xDAD Logic Element 6 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43503 0xDAE Logic Element 6 Block 1 0 0xFFFF 1 --- FC134B 0 1
43504 0xDAF Logic Element 6 Block 2 0 0xFFFF 1 --- FC134B 0 1
43505 0xDB0 Logic Element 6 Block 3 0 0xFFFF 1 --- FC134B 0 1
43506 0xDB1 Logic Element 7 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43507 0xDB2 Logic Element 7 Trigger 2 0 0xFFFF 1 --- FC134B 0 1

12-70 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
43508 0xDB3 Logic Element 7 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43509 0xDB4 Logic Element 7 Block 1 0 0xFFFF 1 --- FC134B 0 1
43510 0xDB5 Logic Element 7 Block 2 0 0xFFFF 1 --- FC134B 0 1
43511 0xDB6 Logic Element 7 Block 3 0 0xFFFF 1 --- FC134B 0 1
43512 0xDB7 Logic Element 8 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
43513 0xDB8 Logic Element 8 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
43514 0xDB9 Logic Element 8 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
43515 0xDBA Logic Element 8 Block 1 0 0xFFFF 1 --- FC134B 0 1
43516 0xDBB Logic Element 8 Block 2 0 0xFFFF 1 --- FC134B 0 1
43517 0xDBC Logic Element 8 Block 3 0 0xFFFF 1 --- FC134B 0 1
46365 0x18DC Logic Element 9 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46366 0x18DD Logic Element 9 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46367 0x18DE Logic Element 9 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46368 0x18DF Logic Element 9 Block 1 0 0xFFFF 1 --- FC134B 0 1
46369 0x18E0 Logic Element 9 Block 2 0 0xFFFF 1 --- FC134B 0 1
46370 0x18E1 Logic Element 9 Block 3 0 0xFFFF 1 --- FC134B 0 1
46371 0x18E2 Logic Element 10 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46372 0x18E3 Logic Element 10 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46373 0x18E4 Logic Element 10 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46374 0x18E5 Logic Element 10 Block 1 0 0xFFFF 1 --- FC134B 0 1
46375 0x18E6 Logic Element 10 Block 2 0 0xFFFF 1 --- FC134B 0 1
46376 0x18E7 Logic Element 10 Block 3 0 0xFFFF 1 --- FC134B 0 1
46377 0x18E8 Logic Element 11 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46378 0x18E9 Logic Element 11 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46379 0x18EA Logic Element 11 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46380 0x18EB Logic Element 11 Block 1 0 0xFFFF 1 --- FC134B 0 1
46381 0x18EC Logic Element 11 Block 2 0 0xFFFF 1 --- FC134B 0 1
46382 0x18ED Logic Element 11 Block 3 0 0xFFFF 1 --- FC134B 0 1
46383 0x18EE Logic Element 12 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46384 0x18EF Logic Element 12 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46385 0x18F0 Logic Element 12 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46386 0x18F1 Logic Element 12 Block 1 0 0xFFFF 1 --- FC134B 0 1
46387 0x18F2 Logic Element 12 Block 2 0 0xFFFF 1 --- FC134B 0 1
46388 0x18F3 Logic Element 12 Block 3 0 0xFFFF 1 --- FC134B 0 1
46389 0x18F4 Logic Element 13 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46390 0x18F5 Logic Element 13 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46391 0x18F6 Logic Element 13 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46392 0x18F7 Logic Element 13 Block 1 0 0xFFFF 1 --- FC134B 0 1
46393 0x18F8 Logic Element 13 Block 2 0 0xFFFF 1 --- FC134B 0 1
46394 0x18F9 Logic Element 13 Block 3 0 0xFFFF 1 --- FC134B 0 1
46395 0x18FA Logic Element 14 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46396 0x18FB Logic Element 14 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46397 0x18FC Logic Element 14 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46398 0x18FD Logic Element 14 Block 1 0 0xFFFF 1 --- FC134B 0 1
46399 0x18FE Logic Element 14 Block 2 0 0xFFFF 1 --- FC134B 0 1
46400 0x18FF Logic Element 14 Block 3 0 0xFFFF 1 --- FC134B 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-71


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
46401 0x1900 Logic Element 15 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46402 0x1901 Logic Element 15 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46403 0x1902 Logic Element 15 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46404 0x1903 Logic Element 15 Block 1 0 0xFFFF 1 --- FC134B 0 1
46405 0x1904 Logic Element 15 Block 2 0 0xFFFF 1 --- FC134B 0 1
46406 0x1905 Logic Element 15 Block 3 0 0xFFFF 1 --- FC134B 0 1
46407 0x1906 Logic Element 16 Trigger 1 0 0xFFFF 1 --- FC134B 0 1
46408 0x1907 Logic Element 16 Trigger 2 0 0xFFFF 1 --- FC134B 0 1
46409 0x1908 Logic Element 16 Trigger 3 0 0xFFFF 1 --- FC134B 0 1
46410 0x1909 Logic Element 16 Block 1 0 0xFFFF 1 --- FC134B 0 1
46411 0x190A Logic Element 16 Block 2 0 0xFFFF 1 --- FC134B 0 1
46412 0x190B Logic Element 16 Block 3 0 0xFFFF 1 --- FC134B 0 1
47012 0x1B63 Logic Element 1 Number of 2 8 1 --- F1 3 1
Triggers
47013 0x1B64 Logic Element 1 Number of 2 4 1 --- F1 3 1
Blocks
47014 0x1B65 Logic Element 1 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47015 0x1B66 Logic Element 1 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47016 0x1B67 Logic Element 1 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47017 0x1B68 Logic Element 1 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47018 0x1B69 Logic Element 1 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47019 0x1B6A Logic Element 1 Block 4 0 0xFFFF 1 --- FC134B 0 1
47020 0x1B6B Logic Element 2 Number of 2 8 1 --- F1 3 1
Triggers
47021 0x1B6C Logic Element 2 Number of 2 4 1 --- F1 3 1
Blocks
47022 0x1B6D Logic Element 2 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47023 0x1B6E Logic Element 2 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47024 0x1B6F Logic Element 2 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47025 0x1B70 Logic Element 2 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47026 0x1B71 Logic Element 2 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47027 0x1B72 Logic Element 2 Block 4 0 0xFFFF 1 --- FC134B 0 1
47028 0x1B73 Logic Element 3 Number of 2 8 1 --- F1 3 1
Triggers
47029 0x1B74 Logic Element 3 Number of 2 4 1 --- F1 3 1
Blocks
47030 0x1B75 Logic Element 3 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47031 0x1B76 Logic Element 3 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47032 0x1B77 Logic Element 3 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47033 0x1B78 Logic Element 3 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47034 0x1B79 Logic Element 3 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47035 0x1B7A Logic Element 3 Block 4 0 0xFFFF 1 --- FC134B 0 1
47036 0x1B7B Logic Element 4 Number of 2 8 1 --- F1 3 1
Triggers
47037 0x1B7C Logic Element 4 Number of 2 4 1 --- F1 3 1
Blocks
47038 0x1B7D Logic Element 4 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47039 0x1B7E Logic Element 4 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47040 0x1B7F Logic Element 4 Trigger 6 0 0xFFFF 1 --- FC134B 0 1

12-72 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
47041 0x1B80 Logic Element 4 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47042 0x1B81 Logic Element 4 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47043 0x1B82 Logic Element 4 Block 4 0 0xFFFF 1 --- FC134B 0 1
47044 0x1B83 Logic Element 5 Number of 2 8 1 --- F1 3 1
Triggers
47045 0x1B84 Logic Element 5 Number of 2 4 1 --- F1 3 1
Blocks
47046 0x1B85 Logic Element 5 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47047 0x1B86 Logic Element 5 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47048 0x1B87 Logic Element 5 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47049 0x1B88 Logic Element 5 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47050 0x1B89 Logic Element 5 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47051 0x1B8A Logic Element 5 Block 4 0 0xFFFF 1 --- FC134B 0 1
47052 0x1B8B Logic Element 6 Number of 2 8 1 --- F1 3 1
Triggers
47053 0x1B8C Logic Element 6 Number of 2 4 1 --- F1 3 1
Blocks
47054 0x1B8D Logic Element 6 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47055 0x1B8E Logic Element 6 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47056 0x1B8F Logic Element 6 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47057 0x1B90 Logic Element 6 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47058 0x1B91 Logic Element 6 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47059 0x1B92 Logic Element 6 Block 4 0 0xFFFF 1 --- FC134B 0 1
47060 0x1B93 Logic Element 7 Number of 2 8 1 --- F1 3 1
Triggers
47061 0x1B94 Logic Element 7 Number of 2 4 1 --- F1 3 1
Blocks
47062 0x1B95 Logic Element 7 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47063 0x1B96 Logic Element 7 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47064 0x1B97 Logic Element 7 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47065 0x1B98 Logic Element 7 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47066 0x1B99 Logic Element 7 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47067 0x1B9A Logic Element 7 Block 4 0 0xFFFF 1 --- FC134B 0 1
47068 0x1B9B Logic Element 8 Number of 2 8 1 --- F1 3 1
Triggers
47069 0x1B9C Logic Element 8 Number of 2 4 1 --- F1 3 1
Blocks
47070 0x1B9D Logic Element 8 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47071 0x1B9E Logic Element 8 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47072 0x1B9F Logic Element 8 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47073 0x1BA0 Logic Element 8 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47074 0x1BA1 Logic Element 8 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47075 0x1BA2 Logic Element 8 Block 4 0 0xFFFF 1 --- FC134B 0 1
47076 0x1BA3 Logic Element 9 Number of 2 8 1 --- F1 3 1
Triggers
47077 0x1BA4 Logic Element 9 Number of 2 4 1 --- F1 3 1
Blocks
47078 0x1BA5 Logic Element 9 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47079 0x1BA6 Logic Element 9 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47080 0x1BA7 Logic Element 9 Trigger 6 0 0xFFFF 1 --- FC134B 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-73


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
47081 0x1BA8 Logic Element 9 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47082 0x1BA9 Logic Element 9 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47083 0x1BAA Logic Element 9 Block 4 0 0xFFFF 1 --- FC134B 0 1
47084 0x1BAB Logic Element 10 Number of 2 8 1 --- F1 3 1
Triggers
47085 0x1BAC Logic Element 10 Number of 2 4 1 --- F1 3 1
Blocks
47086 0x1BAD Logic Element 10 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47087 0x1BAE Logic Element 10 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47088 0x1BAF Logic Element 10 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47089 0x1BB0 Logic Element 10 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47090 0x1BB1 Logic Element 10 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47091 0x1BB2 Logic Element 10 Block 4 0 0xFFFF 1 --- FC134B 0 1
47092 0x1BB3 Logic Element 11 Number of 2 8 1 --- F1 3 1
Triggers
47093 0x1BB4 Logic Element 11 Number of 2 4 1 --- F1 3 1
Blocks
47094 0x1BB5 Logic Element 11 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47095 0x1BB6 Logic Element 11 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47096 0x1BB7 Logic Element 11 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47097 0x1BB8 Logic Element 11 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47098 0x1BB9 Logic Element 11 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47099 0x1BBA Logic Element 11 Block 4 0 0xFFFF 1 --- FC134B 0 1
47100 0x1BBB Logic Element 12 Number of 2 8 1 --- F1 3 1
Triggers
47101 0x1BBC Logic Element 12 Number of 2 4 1 --- F1 3 1
Blocks
47102 0x1BBD Logic Element 12 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47103 0x1BBE Logic Element 12 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47104 0x1BBF Logic Element 12 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47105 0x1BC0 Logic Element 12 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47106 0x1BC1 Logic Element 12 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47107 0x1BC2 Logic Element 12 Block 4 0 0xFFFF 1 --- FC134B 0 1
47108 0x1BC3 Logic Element 13 Number of 2 8 1 --- F1 3 1
Triggers
47109 0x1BC4 Logic Element 13 Number of 2 4 1 --- F1 3 1
Blocks
47110 0x1BC5 Logic Element 13 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47111 0x1BC6 Logic Element 13 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47112 0x1BC7 Logic Element 13 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47113 0x1BC8 Logic Element 13 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47114 0x1BC9 Logic Element 13 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47115 0x1BCA Logic Element 13 Block 4 0 0xFFFF 1 --- FC134B 0 1
47116 0x1BCB Logic Element 14 Number of 2 8 1 --- F1 3 1
Triggers
47117 0x1BCC Logic Element 14 Number of 2 4 1 --- F1 3 1
Blocks
47118 0x1BCD Logic Element 14 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47119 0x1BCE Logic Element 14 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47120 0x1BCF Logic Element 14 Trigger 6 0 0xFFFF 1 --- FC134B 0 1

12-74 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
47121 0x1BD0 Logic Element 14 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47122 0x1BD1 Logic Element 14 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47123 0x1BD2 Logic Element 14 Block 4 0 0xFFFF 1 --- FC134B 0 1
47124 0x1BD3 Logic Element 15 Number of 2 8 1 --- F1 3 1
Triggers
47125 0x1BD4 Logic Element 15 Number of 2 4 1 --- F1 3 1
Blocks
47126 0x1BD5 Logic Element 15 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47127 0x1BD6 Logic Element 15 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47128 0x1BD7 Logic Element 15 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47129 0x1BD8 Logic Element 15 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47130 0x1BD9 Logic Element 15 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47131 0x1BDA Logic Element 15 Block 4 0 0xFFFF 1 --- FC134B 0 1
47132 0x1BDB Logic Element 16 Number of 2 8 1 --- F1 3 1
Triggers
47133 0x1BDC Logic Element 16 Number of 2 4 1 --- F1 3 1
Blocks
47134 0x1BDD Logic Element 16 Trigger 4 0 0xFFFF 1 --- FC134B 0 1
47135 0x1BDE Logic Element 16 Trigger 5 0 0xFFFF 1 --- FC134B 0 1
47136 0x1BDF Logic Element 16 Trigger 6 0 0xFFFF 1 --- FC134B 0 1
47137 0x1BE0 Logic Element 16 Trigger 7 0 0xFFFF 1 --- FC134B 0 1
47138 0x1BE1 Logic Element 16 Trigger 8 0 0xFFFF 1 --- FC134B 0 1
47139 0x1BE2 Logic Element 16 Block 4 0 0xFFFF 1 --- FC134B 0 1
SETPOINT GROUP SETTINGS
40197 0xC4 Volts Per Hertz Function 0 3 1 --- FC197 0 1
40198 0xC5 Volts Per Hertz Voltage 0 1 1 --- FC435 0 1
Mode
40199 0xC6 Volts Per Hertz Pickup 80 400 1 V/Hz F3 105 1
40200 0xC7 Volts Per Hertz Curve 4 18 1 --- FC436 4 1
40201 0xC8 Volts per Hertz TD Multiplier 5 60000 1 --- F3 100 1
40202 0xC9 Volts per Hertz Reset Time 0 600000 1 --- F11 100 2
42485 0x9B4 Phase IOC Function 0 3 1 --- FC197 0 1
42486 0x9B5 Phase IOC Pickup 5 2000 1 x CT F3 100 1
42487 0x9B6 Phase IOC Delay 0 30000 1 s F3 0 1
42490 0x9B9 Neutral IOC Function 0 3 1 --- FC197 0 1
42491 0x9BA Neutral IOC Pickup 5 2000 1 x CT F3 100 1
42492 0x9BB Neutral IOC Delay 0 30000 1 s F3 0 1
42494 0x9BD Ground IOC Function 0 3 1 --- FC197 0 1
42495 0x9BE Ground IOC Pickup 5 2000 1 x CT F3 100 1
42496 0x9BF Ground IOC Delay 0 30000 1 s F3 0 1
42498 0x9C1 Phase Time OC Function 0 3 1 --- FC197 0 1
42499 0x9C2 Phase Time OC Pickup 5 2000 1 x CT F3 100 1
42500 0x9C3 Phase Time OC Curve 0 15 1 --- F36 0 1
42501 0x9C4 Phase Time OC Multiplier 5 5000 1 --- F3 100 1
42502 0x9C5 Phase Time OC Reset 0 1 1 --- F68 0 1
42504 0x9C7 Neutral Time OC Function 0 3 1 --- FC197 0 1
42505 0x9C8 Neutral Time OC Pickup 5 2000 1 x CT F3 100 1
42506 0x9C9 Neutral Time OC Curve 0 15 1 --- F36 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-75


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42507 0x9CA Neutral Time OC Multiplier 5 5000 1 --- F3 100 1
42508 0x9CB Neutral Time OC Reset 0 1 1 --- F68 0 1
42510 0x9CD Ground Time OC Function 0 3 1 --- FC197 0 1
42511 0x9CE Ground Time OC Pickup 5 2000 1 x CT F3 100 1
42512 0x9CF Ground Time OC Curve 0 15 1 --- F36 0 1
42513 0x9D0 Ground Time OC Multiplier 5 5000 1 --- F3 100 1
42514 0x9D1 Ground Time OC Reset 0 1 1 --- F68 0 1
42516 0x9D3 Phase IOC 2 Function 0 3 1 --- FC197 0 1
42517 0x9D4 Phase IOC 2 Pickup 5 2000 1 x CT F3 100 1
42518 0x9D5 Phase IOC 2 Delay 0 30000 1 s F3 0 1
42521 0x9D8 Neutral IOC 2 Function 0 3 1 --- FC197 0 1
42522 0x9D9 Neutral IOC 2 Pickup 5 2000 1 x CT F3 100 1
42523 0x9DA Neutral IOC 2 Delay 0 30000 1 s F3 0 1
42525 0x9DC Ground IOC 2 Function 0 3 1 --- FC197 0 1
42526 0x9DD Ground IOC 2 Pickup 5 2000 1 x CT F3 100 1
42527 0x9DE Ground IOC 2 Delay 0 30000 1 s F3 0 1
42547 0x9F2 Sensitive Ground Time OC 0 3 1 --- FC197 0 1
Function
42548 0x9F3 Sensitive Ground Time OC 5 3000 1 x CT F17A 1000 1
Pickup
42549 0x9F4 Sensitive Ground Time OC 0 15 1 --- F36 0 1
Curve
42550 0x9F5 Sensitive Ground Time OC 5 5000 1 --- F3 100 1
Multiplier
42551 0x9F6 Sensitive Ground Time OC 0 1 1 --- F68 0 1
Reset
42552 0x9F7 Neutral Directional Function 0 3 1 --- FC207 0 1
42553 0x9F8 Neutral Directional 1 3 1 --- F96 1 1
Polarizing
42554 0x9F9 Neutral Directional MTA 0 359 1 °Lead F1 315 1
42555 0x9FA Neutral Directional 5 125 1 x VT F3 5 1
Minimum Voltage
42560 0x9FF Negative Sequence OV 0 3 1 --- FC197 0 1
Function
42561 0xA00 Negative Sequence OV 0 125 1 x VT F3 30 1
Pickup
42562 0xA01 Negative Sequence OV 0 60000 1 s F3 200 1
Delay
42563 0xA02 Neutral OV Function 0 3 1 --- FC197 0 1
42564 0xA03 Neutral OV Pickup 0 125 1 x VT F3 30 1
42565 0xA04 Neutral OV Delay 0 60000 1 s F3 200 1
42566 0xA05 Phase OV Function 0 3 1 --- FC197 0 1
42567 0xA06 Phase OV Pickup 0 125 1 x VT F3 125 1
42568 0xA07 Phase OV Delay 0 60000 1 s F3 200 1
42569 0xA08 Phase OV Phases 1 3 1 --- F92 1 1
42570 0xA09 Phase UV Function 0 3 1 --- FC197 0 1
42571 0xA0A Phase UV Pickup 0 125 1 x VT F3 75 1
42572 0xA0B Phase UV Curve 0 1 1 --- F93 1 1
42573 0xA0C Phase UV Delay 0 60000 1 s F3 200 1
42574 0xA0D Phase UV Phases 1 3 1 --- F92 1 1

12-76 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42575 0xA0E Phase UV Minimum Voltage 0 125 1 x VT F3 30 1
42576 0xA0F Auxiliary OV Function 0 3 1 --- FC197 0 1
42577 0xA10 Auxiliary OV Pickup 0 125 1 x VT F3 30 1
42578 0xA11 Auxiliary OV Delay 0 60000 1 s F3 200 1
42579 0xA12 Auxiliary UV Function 0 3 1 --- FC197 0 1
42580 0xA13 Auxiliary UV Pickup 0 125 1 x VT F3 75 1
42581 0xA14 Auxiliary UV Curve 0 1 1 --- F93 1 1
42582 0xA15 Auxiliary UV Delay 0 60000 1 s F3 200 1
42583 0xA16 Auxiliary Minimum Voltage 0 125 1 x VT F3 30 1
42584 0xA17 Underfrequency 1 Function 0 3 1 --- FC197 0 1
42585 0xA18 Underfrequency 1 Pickup 4000 7000 1 Hz F3 5900 1
42586 0xA19 Underfrequency 1 Delay 10 60000 1 s F3 200 1
42587 0xA1A Minimum UF Voltage 1 0 125 1 x VT F3 70 1
42588 0xA1B Underfrequency 2 Function 0 3 1 --- FC197 0 1
42589 0xA1C Underfrequency 2 Pickup 4000 7000 1 Hz F3 5900 1
42590 0xA1D Underfrequency 2 Delay 10 60000 1 s F3 200 1
42591 0xA1E Minimum UF Voltage 2 0 125 1 x VT F3 70 1
42592 0xA1F Overfrequency 1 Function 0 3 1 --- FC197 0 1
42593 0xA20 Overfrequency 1 Pickup 4000 7000 1 Hz F3 6050 1
42594 0xA21 Overfrequency 1 Delay 10 60000 1 s F3 200 1
42595 0xA22 Overfrequency 2 Function 0 3 1 --- FC197 0 1
42596 0xA23 Overfrequency 2 Pickup 4000 7000 1 Hz F3 6050 1
42597 0xA24 Overfrequency 2 Delay 10 60000 1 s F3 200 1
42598 0xA25 Sensitive Ground IOC 0 3 1 --- FC197 0 1
Function
42599 0xA26 Sensitive Ground IOC Pickup 5 3000 1 x CT F17A 1000 1
42600 0xA27 Sensitive Ground IOC Delay 0 30000 1 s F3 0 1
42601 0xA28 Sensitive Ground 2 IOC 0 3 1 --- FC197 0 1
Function
42602 0xA29 Sensitive Ground 2 IOC 5 3000 1 x CT F17A 1000 1
Pickup
42603 0xA2A Sensitive Ground 2 IOC 0 30000 1 s F3 0 1
Delay
42604 0xA2B Negative Sequence IOC 0 3 1 --- FC197 0 1
Function
42605 0xA2C Negative Sequence IOC 5 2000 1 x CT F3 100 1
Pickup
42606 0xA2D Negative Sequence IOC 0 30000 1 s F3 0 1
Delay
46799 0x1A8E Wattmetric 1 Function 0 4 1 --- FC205 0 1
46800 0x1A8F Wattmetric 1 Voltage 0 1 1 --- FC118 0 1
46801 0x1A90 Wattmetric 1 Voltage Pickup 2 300 1 x VT F3 20 1
46802 0x1A91 Wattmetric 1 Current 0 1 1 --- FC119 0 1
46803 0x1A92 Wattmetric 1 Current Pickup 2 20000 1 x CT F17A 60 1
46804 0x1A93 Wattmetric 1 Power Pickup 1 1200 1 x F17A 100 1
CTxVT
46805 0x1A94 Wattmetric 1 Ref Power 1 1200 1 x F17A 500 1
Pickup CTxVT
46806 0x1A95 Wattmetric 1 ECA 0 359 1 ° F1 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-77


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
46807 0x1A96 Wattmetric 1 Power Pickup 0 30000 1 s F3 20 1
Delay
46808 0x1A97 Wattmetric 1 Curve 0 9 1 --- FC427 4 1
46809 0x1A98 Wattmetric 1 Multiplier 1 200 1 s F3 100 1
46810 0x1A99 Wattmetric 1 Output Relays 0 0x3F 1 --- FC198 0 1
3-6
46814 0x1A9D Wattmetric 2 Function 0 4 1 --- FC205 0 1
46815 0x1A9E Wattmetric 2 Voltage 0 1 1 --- FC118 0 1
46816 0x1A9F Wattmetric 2 Voltage Pickup 2 300 1 x VT F3 20 1
46817 0x1AA0 Wattmetric 2 Current 0 1 1 --- FC119 0 1
46818 0x1AA1 Wattmetric 2 Current Pickup 2 20000 1 x CT F17A 60 1
46819 0x1AA2 Wattmetric 2 Power Pickup 1 1200 1 x F17A 100 1
CTxVT
46820 0x1AA3 Wattmetric 2 Ref Power 1 1200 1 x F17A 500 1
Pickup CTxVT
46821 0x1AA4 Wattmetric 2 ECA 0 359 1 ° F1 0 1
46822 0x1AA5 Wattmetric 2 Power Pickup 0 30000 1 s F3 20 1
Delay
46823 0x1AA6 Wattmetric 2 Curve 0 9 1 --- FC427 4 1
46824 0x1AA7 Wattmetric 2 Multiplier 1 200 1 s F3 100 1
46825 0x1AA8 Wattmetric 2 Output Relays 0 0x3F 1 --- FC198 0 1
3-6
46833 0x1AB0 Directional Power 1 Function 0 4 1 --- FC205 0 1
46834 0x1AB1 Directional Power 1 RCA 0 359 1 ° F1 0 1
46835 0x1AB2 Directional Power 1 SMIN -1200 1200 1 x F7 100 1
Rated
Power
46836 0x1AB3 Directional Power 1 Pickup 0 6000 1 s F2 5 1
Delay
46837 0x1AB4 Directional Power 1 Output 0 0x3F 1 --- FC198 0 1
Relays 3-6
46841 0x1AB8 Directional Power 2 Function 0 4 1 --- FC205 0 1
46842 0x1AB9 Directional Power 2 RCA 0 359 1 ° F1 0 1
46843 0x1ABA Directional Power 2 SMIN -1200 1200 1 x F7 100 1
Rated
Power
46844 0x1ABB Directional Power 2 Pickup 0 6000 1 s F2 5 1
Delay
46845 0x1ABC Directional Power 2 Output 0 0x3F 1 --- FC198 0 1
Relays 3-6
46859 0x1ACA Broken Conductor Function 0 4 1 --- FC205 0 1
46860 0x1ACB Broken Conductor I_2/I_1 200 1000 1 % F2 200 1
Ratio
46861 0x1ACC Broken Conductor I_1 Min 5 100 1 x CT F3 10 1
46862 0x1ACD Broken Conductor I_1 Max 5 500 1 x CT F3 150 1
46863 0x1ACE Broken Conductor Pickup 0 60000 1 s F17A 20000 1
Delay
46864 0x1ACF Broken Conductor Output 0 0x3F 1 --- FC198 0 1
Relays 3-6
46933 0x1B14 Negative Seq OV 2 Function 0 3 1 --- FC197 0 1
46934 0x1B15 Negative Seq OV 2 Pkp 0 125 1 x VT F3 30 1
46935 0x1B16 Negative Seq OV 2 Delay 0 60000 1 s F3 200 1

12-78 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
46940 0x1B1B Auxiliary UV 2 Function 0 3 1 --- FC197 0 1
46941 0x1B1C Auxiliary UV 2 Pickup 0 125 1 x VT F3 75 1
46942 0x1B1D Auxiliary UV 2 Curve 0 1 1 --- F93 1 1
46943 0x1B1E Auxiliary UV 2 Delay 0 60000 1 s F3 200 1
46948 0x1B23 Aux UV2 Min Voltage 0 125 1 x VT F3 30 1
46949 0x1B24 Neutral OV 2 Function 0 3 1 --- FC197 0 1
46950 0x1B25 Neutral OV 2 Pickup 0 125 1 x VT F3 30 1
46951 0x1B26 Neutral OV 2 Delay 0 60000 1 s F3 200 1
46956 0x1B2B Neutral OV 3 Function 0 3 1 --- FC197 0 1
46957 0x1B2C Neutral OV 3 Pickup 0 125 1 x VT F3 30 1
46958 0x1B2D Neutral OV 3 Delay 0 60000 1 s F3 200 1
46963 0x1B32 Neutral OV 4 Function 0 3 1 --- FC197 0 1
46964 0x1B33 Neutral OV 4 Pickup 0 125 1 x VT F3 30 1
46965 0x1B34 Neutral OV 4 Delay 0 60000 1 s F3 200 1
46970 0x1B39 Overfrequency 3 Function 0 3 1 --- FC197 0 1
46971 0x1B3A Overfrequency 3 Pickup 4000 7000 1 Hz F3 6050 1
46972 0x1B3B Overfrequency 3 Delay 10 60000 1 s F3 200 1
46977 0x1B40 Overfrequency 4 Function 0 3 1 --- FC197 0 1
46978 0x1B41 Overfrequency 4 Pickup 4000 7000 1 Hz F3 6050 1
46979 0x1B42 Overfrequency 4 Delay 10 60000 1 s F3 200 1
47143 0x1BE6 Underfrequency 3 Function 0 3 1 --- FC197 0 1
47144 0x1BE7 Underfrequency 3 Pkp 4000 7000 1 Hz F3 5900 1
47145 0x1BE8 Underfrequency 3 Delay 10 60000 1 s F3 200 1
47146 0x1BE9 Minimum UF Voltage 3 0 125 1 x VT F3 70 1
47151 0x1BEE Underfrequency 4 Function 0 3 1 --- FC197 0 1
47152 0x1BEF Underfrequency 4 Pkp 4000 7000 1 Hz F3 5900 1
47153 0x1BF0 Underfrequency 4 Delay 10 60000 1 s F3 200 1
47154 0x1BF1 Minimum UF Voltage 4 0 125 1 x VT F3 70 1
PROTECTION FUNCTION BLOCKING
40205 0xCC Volts Per Hertz Block 1 0 0xEF02 1 --- F89 0 1
40206 0xCD Volts Per Hertz Block 2 0 0xEF02 1 --- F89 0 1
40207 0xCE Volts Per Hertz Block 3 0 0xEF02 1 --- F89 0 1
42641 0xA50 Phase IOC 1 Block 1 0 0xEF02 1 --- F89 0 1
42642 0xA51 Phase IOC 1 Block 2 0 0xEF02 1 --- F89 0 1
42643 0xA52 Phase IOC 1 Block 3 0 0xEF02 1 --- F89 0 1
42644 0xA53 Neutral IOC 1 Block 1 0 0xEF02 1 --- F89 0 1
42645 0xA54 Neutral IOC 1 Block 2 0 0xEF02 1 --- F89 0 1
42646 0xA55 Neutral IOC 1 Block 3 0 0xEF02 1 --- F89 0 1
42647 0xA56 Ground IOC 1 Block 1 0 0xEF02 1 --- F89 0 1
42648 0xA57 Ground IOC 1 Block 2 0 0xEF02 1 --- F89 0 1
42649 0xA58 Ground IOC 1 Block 3 0 0xEF02 1 --- F89 0 1
42650 0xA59 Phase TOC Block 1 0 0xEF02 1 --- F89 0 1
42651 0xA5A Phase TOC Block 2 0 0xEF02 1 --- F89 0 1
42652 0xA5B Phase TOC Block 3 0 0xEF02 1 --- F89 0 1
42653 0xA5C Neutral TOC Block 1 0 0xEF02 1 --- F89 0 1
42654 0xA5D Neutral TOC Block 2 0 0xEF02 1 --- F89 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-79


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42655 0xA5E Neutral TOC Block 3 0 0xEF02 1 --- F89 0 1
42656 0xA5F Ground TOC Block 1 0 0xEF02 1 --- F89 0 1
42657 0xA60 Ground TOC Block 2 0 0xEF02 1 --- F89 0 1
42658 0xA61 Ground TOC Block 3 0 0xEF02 1 --- F89 0 1
42659 0xA62 Phase IOC 2 Block 1 0 0xEF02 1 --- F89 0 1
42660 0xA63 Phase IOC 2 Block 2 0 0xEF02 1 --- F89 0 1
42661 0xA64 Phase IOC 2 Block 3 0 0xEF02 1 --- F89 0 1
42662 0xA65 Neutral IOC 2 Block 1 0 0xEF02 1 --- F89 0 1
42663 0xA66 Neutral IOC 2 Block 2 0 0xEF02 1 --- F89 0 1
42664 0xA67 Neutral IOC 2 Block 3 0 0xEF02 1 --- F89 0 1
42665 0xA68 Ground IOC 2 Block 1 0 0xEF02 1 --- F89 0 1
42666 0xA69 Ground IOC 2 Block 2 0 0xEF02 1 --- F89 0 1
42667 0xA6A Ground IOC 2 Block 3 0 0xEF02 1 --- F89 0 1
42677 0xA74 Sensitive Ground TOC Block 0 0xEF02 1 --- F89 0 1
1
42678 0xA75 Sensitive Ground TOC Block 0 0xEF02 1 --- F89 0 1
2
42679 0xA76 Sensitive Ground TOC Block 0 0xEF02 1 --- F89 0 1
3
42680 0xA77 67N Block 1 0 0xEF02 1 --- F89 0 1
42681 0xA78 67N Block 2 0 0xEF02 1 --- F89 0 1
42682 0xA79 67N Block 3 0 0xEF02 1 --- F89 0 1
42686 0xA7D Negative Sequence OV 0 0xEF02 1 --- F89 0 1
Block 1
42687 0xA7E Negative Sequence OV 0 0xEF02 1 --- F89 0 1
Block 2
42688 0xA7F Negative Sequence OV 0 0xEF02 1 --- F89 0 1
Block 3
42689 0xA80 Neutral OV Block 1 0 0xEF02 1 --- F89 0 1
42690 0xA81 Neutral OV Block 2 0 0xEF02 1 --- F89 0 1
42691 0xA82 Neutral OV Block 3 0 0xEF02 1 --- F89 0 1
42692 0xA83 Phase OV Block 1 0 0xEF02 1 --- F89 0 1
42693 0xA84 Phase OV Block 2 0 0xEF02 1 --- F89 0 1
42694 0xA85 Phase OV Block 3 0 0xEF02 1 --- F89 0 1
42695 0xA86 Phase UV Block 1 0 0xEF02 1 --- F89 0 1
42696 0xA87 Phase UV Block 2 0 0xEF02 1 --- F89 0 1
42697 0xA88 Phase UV Block 3 0 0xEF02 1 --- F89 0 1
42698 0xA89 Auxiliary OV Block 1 0 0xEF02 1 --- F89 0 1
42699 0xA8A Auxiliary OV Block 2 0 0xEF02 1 --- F89 0 1
42700 0xA8B Auxiliary OV Block 3 0 0xEF02 1 --- F89 0 1
42701 0xA8C Auxiliary UV Block 1 0 0xEF02 1 --- F89 0 1
42702 0xA8D Auxiliary UV Block 2 0 0xEF02 1 --- F89 0 1
42703 0xA8E Auxiliary UV Block 3 0 0xEF02 1 --- F89 0 1
42704 0xA8F Underfrequency 1 Block 1 0 0xEF02 1 --- F89 0 1
42705 0xA90 Underfrequency 1 Block 2 0 0xEF02 1 --- F89 0 1
42706 0xA91 Underfrequency 1 Block 3 0 0xEF02 1 --- F89 0 1
42707 0xA92 Underfrequency 2 Block 1 0 0xEF02 1 --- F89 0 1
42708 0xA93 Underfrequency 2 Block 2 0 0xEF02 1 --- F89 0 1

12-80 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42709 0xA94 Underfrequency 2 Block 3 0 0xEF02 1 --- F89 0 1
42710 0xA95 Overfrequency 1 Block 1 0 0xEF02 1 --- F89 0 1
42711 0xA96 Overfrequency 1 Block 2 0 0xEF02 1 --- F89 0 1
42712 0xA97 Overfrequency 1 Block 3 0 0xEF02 1 --- F89 0 1
42713 0xA98 Overfrequency 2 Block 1 0 0xEF02 1 --- F89 0 1
42714 0xA99 Overfrequency 2 Block 2 0 0xEF02 1 --- F89 0 1
42715 0xA9A Overfrequency 2 Block 3 0 0xEF02 1 --- F89 0 1
42719 0xA9E Thermal Model Block 1 0 0xEF02 1 --- F89 0 1
42720 0xA9F Thermal Model Block 2 0 0xEF02 1 --- F89 0 1
42721 0xAA0 Thermal Model Block 3 0 0xEF02 1 --- F89 0 1
42722 0xAA1 50SG IOC 1 Block 1 0 0xEF02 1 --- F89 0 1
42723 0xAA2 50SG IOC 1 Block 2 0 0xEF02 1 --- F89 0 1
42724 0xAA3 50SG IOC 1 Block 3 0 0xEF02 1 --- F89 0 1
42725 0xAA4 50SG IOC 2 Block 1 0 0xEF02 1 --- F89 0 1
42726 0xAA5 50SG IOC 2 Block 2 0 0xEF02 1 --- F89 0 1
42727 0xAA6 50SG IOC 2 Block 3 0 0xEF02 1 --- F89 0 1
42728 0xAA7 Negative Sequence IOC 0 0xEF02 1 --- F89 0 1
Block 1
42729 0xAA8 Negative Sequence IOC 0 0xEF02 1 --- F89 0 1
Block 2
42730 0xAA9 Negative Sequence IOC 0 0xEF02 1 --- F89 0 1
Block 3
42731 0xAAA Neg Seq TOC1 Block 1 0 0xEF02 1 --- F89 0 1
42732 0xAAB Neg Seq TOC1 Block 2 0 0xEF02 1 --- F89 0 1
42733 0xAAC Neg Seq TOC1 Block 3 0 0xEF02 1 --- F89 0 1
46811 0x1A9A Wattmetric 1 Block 1 0 0xEF02 1 --- F89 0 1
46812 0x1A9B Wattmetric 1 Block 2 0 0xEF02 1 --- F89 0 1
46813 0x1A9C Wattmetric 1 Block 3 0 0xEF02 1 --- F89 0 1
46826 0x1AA9 Wattmetric 2 Block 1 0 0xEF02 1 --- F89 0 1
46827 0x1AAA Wattmetric 2 Block 2 0 0xEF02 1 --- F89 0 1
46828 0x1AAB Wattmetric 2 Block 3 0 0xEF02 1 --- F89 0 1
46838 0x1AB5 Directional Power 1 Block 1 0 0xEF02 1 --- F89 0 1
46839 0x1AB6 Directional Power 1 Block 2 0 0xEF02 1 --- F89 0 1
46840 0x1AB7 Directional Power 1 Block 3 0 0xEF02 1 --- F89 0 1
46846 0x1ABD Directional Power 2 Block 1 0 0xEF02 1 --- F89 0 1
46847 0x1ABE Directional Power 2 Block 2 0 0xEF02 1 --- F89 0 1
46848 0x1ABF Directional Power 2 Block 3 0 0xEF02 1 --- F89 0 1
46865 0x1AD0 Broken Conductor Block 1 0 0xEF02 1 --- F89 0 1
46866 0x1AD1 Broken Conductor Block 2 0 0xEF02 1 --- F89 0 1
46867 0x1AD2 Broken Conductor Block 3 0 0xEF02 1 --- F89 0 1
46936 0x1B17 Negative Seq OV 2 Block 1 0 0xEF02 1 --- F89 0 1
46937 0x1B18 Negative Seq OV 2 Block 2 0 0xEF02 1 --- F89 0 1
46938 0x1B19 Negative Seq OV 2 Block 3 0 0xEF02 1 --- F89 0 1
46944 0x1B1F Auxiliary UV 2 Block 1 0 0xEF02 1 --- F89 0 1
46945 0x1B20 Auxiliary UV 2 Block 2 0 0xEF02 1 --- F89 0 1
46946 0x1B21 Auxiliary UV 2 Block 3 0 0xEF02 1 --- F89 0 1
46952 0x1B27 Neutral OV 2 Block 1 0 0xEF02 1 --- F89 0 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-81


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
46953 0x1B28 Neutral OV 2 Block 2 0 0xEF02 1 --- F89 0 1
46954 0x1B29 Neutral OV 2 Block 3 0 0xEF02 1 --- F89 0 1
46959 0x1B2E Neutral OV 3 Block 1 0 0xEF02 1 --- F89 0 1
46960 0x1B2F Neutral OV 3 Block 2 0 0xEF02 1 --- F89 0 1
46961 0x1B30 Neutral OV 3 Block 3 0 0xEF02 1 --- F89 0 1
46966 0x1B35 Neutral OV 4 Block 1 0 0xEF02 1 --- F89 0 1
46967 0x1B36 Neutral OV 4 Block 2 0 0xEF02 1 --- F89 0 1
46968 0x1B37 Neutral OV 4 Block 3 0 0xEF02 1 --- F89 0 1
46973 0x1B3C Overfrequency 3 Block 1 0 0xEF02 1 --- F89 0 1
46974 0x1B3D Overfrequency 3 Block 2 0 0xEF02 1 --- F89 0 1
46975 0x1B3E Overfrequency 3 Block 3 0 0xEF02 1 --- F89 0 1
46980 0x1B43 Overfrequency 4 Block 1 0 0xEF02 1 --- F89 0 1
46981 0x1B44 Overfrequency 4 Block 2 0 0xEF02 1 --- F89 0 1
47147 0x1BEA Underfrequency 3 Block 1 0 0xEF02 1 --- F89 0 1
47148 0x1BEB Underfrequency 3 Block 2 0 0xEF02 1 --- F89 0 1
47149 0x1BEC Underfrequency 3 Block 3 0 0xEF02 1 --- F89 0 1
47155 0x1BF2 Underfrequency 4 Block 1 0 0xEF02 1 --- F89 0 1
47156 0x1BF3 Underfrequency 4 Block 2 0 0xEF02 1 --- F89 0 1
47157 0x1BF4 Underfrequency 4 Block 3 0 0xEF02 1 --- F89 0 1
PROTECTION ELEMENT RELAY CONFIGURATION
40204 0xCB Volts Per Hertz Relays 0 0x7F 1 --- FC198 0 1
42737 0xAB0 Phase IOC 1 Relay 0 0x7F 1 --- FC198 0 1
42738 0xAB1 Neutral IOC 1 Relay 0 0x7F 1 --- FC198 0 1
42739 0xAB2 Ground IOC 1 Relay 0 0x7F 1 --- FC198 0 1
42740 0xAB3 Phase TOC1 Relay 0 0x7F 1 --- FC198 0 1
42741 0xAB4 Neutral TOC Relay 0 0x7F 1 --- FC198 0 1
42742 0xAB5 Ground TOC1 Relay 0 0x7F 1 --- FC198 0 1
42743 0xAB6 Phase IOC 2 Relay 0 0x7F 1 --- FC198 0 1
42744 0xAB7 Neutral IOC 2 Relay 0 0x7F 1 --- FC198 0 1
42745 0xAB8 Ground IOC 2 Relay 0 0x7F 1 --- FC198 0 1
42749 0xABC Sensitive Ground TOC1 0 0x7F 1 --- FC198 0 1
Relay
42750 0xABD Neutral Directional (67N) 0 0x7F 1 --- FC198 0 1
Relay
42752 0xABF Negative Sequence 0 0x7F 1 --- FC198 0 1
Overvoltage Relay
42753 0xAC0 Neutral Overvoltage Relay 0 0x7F 1 --- FC198 0 1
42754 0xAC1 Phase Overvoltage Relay 0 0x7F 1 --- FC198 0 1
42755 0xAC2 Phase Undervoltage Relay 0 0x7F 1 --- FC198 0 1
42756 0xAC3 Auxiliary OVervoltage Relay 0 0x7F 1 --- FC198 0 1
42757 0xAC4 AuxiliaryUndervoltage Relay 0 0x7F 1 --- FC198 0 1
42758 0xAC5 Underfrequency 1 Relay 0 0x7F 1 --- FC198 0 1
42759 0xAC6 Underfrequency 2 Relay 0 0x7F 1 --- FC198 0 1
42760 0xAC7 Overfrequency 1 Relay 0 0x7F 1 --- FC198 0 1
42761 0xAC8 Overfrequency 2 Relay 0 0x7F 1 --- FC198 0 1
42762 0xAC9 Sensitive Ground IOC 1 Relay 0 0x7F 1 --- FC198 0 1
42763 0xACA Sensitive Ground IOC2 Relay 0 0x7F 1 --- FC198 0 1

12-82 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
42764 0xACB Negative Sequence IOC 0 0x7F 1 --- FC198 0 1
Relays
46939 0x1B1A Negative Seq OV 2 Relays 0 0x7F 1 --- FC198 0 1
46947 0x1B22 Auxiliary UV 2 Relay 0 0x7F 1 --- FC198 0 1
46955 0x1B2A Neutral OV 2 Relay 0 0x7F 1 --- FC198 0 1
46962 0x1B31 Neutral OV 3 Relay 0 0x7F 1 --- FC198 0 1
46969 0x1B38 Neutral OV 4 Relay 0 0x7F 1 --- FC198 0 1
46976 0x1B3F Overfrequency 3 Relay 0 0x7F 1 --- FC198 0 1
46983 0x1B46 Overfrequency 4 Relay 0 0x7F 1 --- FC198 0 1
47150 0x1BED Underfrequency 3 Relays 0 0x7F 1 --- FC198 0 1
47158 0x1BF5 Underfrequency 4 Relays 0 0x7F 1 --- FC198 0 1
DEMAND
47189 0x1C14 Current Demand 1 Function 0 2 1 --- FC206 0 1
47191 0x1C16 Current Demand 1 0 2 1 --- FC431 0 1
Measurement Type
47192 0x1C17 Current Demand 1 90% 0 4 1 --- FC432 2 1
Response Time
47193 0x1C18 Current Demand 1 Time 0 4 1 --- FC432 3 1
Interval
47194 0x1C19 Current Demand 1 Pkp 10 10000 1 A F1 1000 1
47195 0x1C1A Current Demand 1 Relays 0 0x7F 1 --- FC198 0 1
47196 0x1C1B Current Demand 1 Block 1 0 0xEF02 1 --- F89 0 1
47197 0x1C1C Current Demand 1 Block 2 0 0xEF02 1 --- F89 0 1
47198 0x1C1D Current Demand 1 Block 3 0 0xEF02 1 --- F89 0 1
47209 0x1C28 Real Power Demand 0 2 1 --- FC206 0 1
Function
47210 0x1C29 Real Power Demand 0 2 1 --- FC431 0 1
Measurement Type
47211 0x1C2A Real Power Demand 90% 0 4 1 --- FC432 2 1
Response Time
47212 0x1C2B Real Power Demand Time 0 4 1 --- FC432 3 1
Interval
47213 0x1C2C Real Power Demand Pkp 1 3000000 1 kW F10 10000 2
47215 0x1C2E Real Power Demand Relays 0 0x7F 1 --- FC198 0 1
47216 0x1C2F Real Power Demand Block 1 0 0xEF02 1 --- F89 0 1
47217 0x1C30 Real Power Demand Block 2 0 0xEF02 1 --- F89 0 1
47218 0x1C31 Real Power Demand Block 3 0 0xEF02 1 --- F89 0 1
47219 0x1C32 Reactive Power Demand 0 2 1 --- FC206 0 1
Function
47220 0x1C33 Reactive Power Demand 0 2 1 --- FC431 0 1
Measurement Type
47221 0x1C34 Reactive Power Demand 0 4 1 --- FC432 2 1
90% Response Time
47222 0x1C35 Reactive Power Demand 0 4 1 --- FC432 3 1
Time Interval
47223 0x1C36 Reactive Power Demand 1 3000000 1 kvar F10 10000 2
Pkp
47225 0x1C38 Reactive Power Demand 0 0x7F 1 --- FC198 0 1
Relays
47226 0x1C39 Reactive Power Demand 0 0xEF02 1 --- F89 0 1
Block 1

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-83


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
47227 0x1C3A Reactive Power Demand 0 0xEF02 1 --- F89 0 1
Block 2
47228 0x1C3B Reactive Power Demand 0 0xEF02 1 --- F89 0 1
Block 3
47229 0x1C3C Apparent Power Demand 0 2 1 --- FC206 0 1
Function
47230 0x1C3D Apparent Power Demand 0 2 1 --- FC431 0 1
Measurement Type
47231 0x1C3E Apparent Power Demand 0 4 1 --- FC432 2 1
90% Response Time
47232 0x1C3F Apparent Power Demand 0 4 1 --- FC432 3 1
Time Interval
47233 0x1C40 Apparent Power Demand 1 3000000 1 kVA F10 10000 2
Pkp
47235 0x1C42 Apparent Power Demand 0 0x7F 1 --- FC198 0 1
Relays
47236 0x1C43 Apparent Power Demand 0 0xEF02 1 --- F89 0 1
Block 1
47237 0x1C44 Apparent Power Demand 0 0xEF02 1 --- F89 0 1
Block 2
47238 0x1C45 Apparent Power Demand 0 0xEF02 1 --- F89 0 1
Block 3
LOCKOUT
47242 0x1C49 Lockout Function 0 1 1 --- FC126 0 1
47243 0x1C4A Lockout Input 1 0 0xFFFF 1 --- FC134D 0 1
47244 0x1C4B Lockout Input 2 0 0xFFFF 1 --- FC134D 0 1
47245 0x1C4C Lockout Input 3 0 0xFFFF 1 --- FC134D 0 1
47246 0x1C4D Lockout Input 4 0 0xFFFF 1 --- FC134D 0 1
47247 0x1C4E Lockout Input 5 0 0xFFFF 1 --- FC134D 0 1
47248 0x1C4F Lockout Input 6 0 0xFFFF 1 --- FC134D 0 1
47249 0x1C50 Lockout Input 7 0 0xFFFF 1 --- FC134D 0 1
47250 0x1C51 Lockout Input 8 0 0xFFFF 1 --- FC134D 0 1
47251 0x1C52 Lockout Input 9 0 0xFFFF 1 --- FC134D 0 1
47252 0x1C53 Lockout Input 10 0 0xFFFF 1 --- FC134D 0 1
47253 0x1C54 Lockout Supervision 0 0xFFFF 1 --- FC134C 1 1
47254 0x1C55 Lockout Reset 0 0xFFFF 1 --- FC134F 0 1
47255 0x1C56 Lockout Reset From PB 0 1 1 --- FC126 0 1
Reset
47256 0x1C57 Lockout Block Reset Lockout 0 0xFFFF 1 --- FC134D 0x8002 1
47257 0x1C58 Lockout Block 1 0 0xEF02 1 --- F89 0 1
47258 0x1C59 Lockout Block 2 0 0xEF02 1 --- F89 0 1
47259 0x1C5A Lockout Block 3 0 0xEF02 1 --- F89 0 1
POSITIVE SEQ UV
47263 0x1C5E Positive Seq UV 1 Function 0 3 1 --- FC197 0 1
47264 0x1C5F Positive Seq UV 1 Pkp 0 125 1 x VT F3 75 1
47265 0x1C60 Positive Seq UV 1 Curve 0 1 1 --- F93 1 1
47266 0x1C61 Positive Seq UV 1 Delay 0 60000 1 s F3 200 1
47267 0x1C62 Positive Seq UV 1 Min V 0 125 1 x VT F3 10 1
47268 0x1C63 Positive Seq UV 1 Relays 0 0x7F 1 --- FC198 0 1
47269 0x1C64 Positive Seq UV 1 Block 1 0 0xEF02 1 --- F89 0 1

12-84 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
47270 0x1C65 Positive Seq UV 1 Block 2 0 0xEF02 1 --- F89 0 1
47271 0x1C66 Positive Seq UV 1 Block 3 0 0xEF02 1 --- F89 0 1
CT FAILURE
47282 0x1C71 CT Failure Function 0 2 1 --- FC206 0 1
47285 0x1C74 CT Failure Output Relays 3-6 0 0x3F 1 --- FC198 0 1
47286 0x1C75 CT Failure Block 1 0 0xEF02 1 --- F89 0 1
47287 0x1C76 CT Failure Block 2 0 0xEF02 1 --- F89 0 1
47288 0x1C77 CT Failure Block 3 0 0xEF02 1 --- F89 0 1
47296 0x1C7F W1 CT Fail 3I0 Current PKP 3 200 1 x CT F3 10 1
47297 0x1C80 W1 CT Fail 3V0 Voltage 5 200 1 x VT F3 20 1
Inhibit
47298 0x1C81 W1 CT Fail GND Current 2 200 1 x CT F3 20 1
Inhibit
47299 0x1C82 W1 CT Fail Sens GND 5 2000 1 x CT F17A 200 1
Current Inhibit
47300 0x1C83 W1 CT Fail Time Delay 0 6000 1 s F3 0 1
TESTING
47303 0x1C86 Force leds 0 1 --- FC126 0 1
47304 0x1C87 Led 1 0 1 --- FC103 0 1
47305 0x1C88 Led 2 0 1 --- FC103 0 1
47306 0x1C89 Led 3 0 1 --- FC103 0 1
47307 0x1C8A Led 4 0 1 --- FC103 0 1
47308 0x1C8B Led 5 0 1 --- FC103 0 1
47309 0x1C8C Led 6 0 1 --- FC103 0 1
47310 0x1C8D Led 7 0 1 --- FC103 0 1
47311 0x1C8E Led 8 0 1 --- FC103 0 1
47312 0x1C8F Led 9 0 1 --- FC103 0 1
47313 0x1C90 Led 10 0 1 --- FC103 0 1
47314 0x1C91 Led 11 0 1 --- FC103 0 1
47315 0x1C92 Led 12 0 1 --- FC103 0 1
47318 0x1C95 Force Output Relays 0 1 --- FC126 0 1
47319 0x1C96 Relay 1 Trip 0 1 --- FC103 0 1
47320 0x1C97 Relay 2 Close 0 1 --- FC103 0 1
47321 0x1C98 Relay 3 Auxiliary 0 1 --- FC103 0 1
47322 0x1C99 Relay 4 Auxiliary 0 1 --- FC103 0 1
47323 0x1C9A Relay 5 Auxiliary 0 1 --- FC103 0 1
47324 0x1C9B Relay 6 Auxiliary 0 1 --- FC103 0 1
61850 MAPPING
47327 0x1C9E Analog input 1 Value 0 251 1 --- F88 0 1
47328 0x1C9F Analog input 1 db 0 100000 1 % F17 0 2
47330 0x1CA1 Analog input 1 Min -2147483648 2147483647 1 --- F13 0 2
47332 0x1CA3 Analog input 1 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47334 0x1CA5 Analog input 2 Value 0 251 1 --- F88 0 1
47335 0x1CA6 Analog input 2 db 0 100000 1 % F17 0 2
47337 0x1CA8 Analog input 2 Min -2147483648 2147483647 1 --- F13 0 2
47339 0x1CAA Analog input 2 Max -2147483648 2147483647 1 --- F13 214748364 2
7

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-85


350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default words
47341 0x1CAC Analog input 3 Value 0 251 1 --- F88 0 1
47342 0x1CAD Analog input 3 db 0 100000 1 % F17 0 2
47344 0x1CAF Analog input 3 Min -2147483648 2147483647 1 --- F13 0 2
47346 0x1CB1 Analog input 3 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47348 0x1CB3 Analog input 4 Value 0 251 1 --- F88 0 1
47349 0x1CB4 Analog input 4 db 0 100000 1 % F17 0 2
47351 0x1CB6 Analog input 4 Min -2147483648 2147483647 1 --- F13 0 2
47353 0x1CB8 Analog input 4 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47355 0x1CBA Analog input 5 Value 0 251 1 --- F88 0 1
47356 0x1CBB Analog input 5 db 0 100000 1 % F17 0 2
47358 0x1CBD Analog input 5 Min -2147483648 2147483647 1 --- F13 0 2
47360 0x1CBF Analog input 5 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47362 0x1CC1 Analog input 6 Value 0 251 1 --- F88 0 1
47363 0x1CC2 Analog input 6 db 0 100000 1 % F17 0 2
47365 0x1CC4 Analog input 6 Min -2147483648 2147483647 1 --- F13 0 2
47367 0x1CC6 Analog input 6 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47369 0x1CC8 Analog input 7 Value 0 251 1 --- F88 0 1
47370 0x1CC9 Analog input 7 db 0 100000 1 % F17 0 2
47372 0x1CCB Analog input 7 Min -2147483648 2147483647 1 --- F13 0 2
47374 0x1CCD Analog input 7 Max -2147483648 2147483647 1 --- F13 214748364 2
7
47376 0x1CCF Analog input 8 Value 0 251 1 --- F88 0 1
47377 0x1CD0 Analog input 8 db 0 100000 1 % F17 0 2
47379 0x1CD2 Analog input 8 Min -2147483648 2147483647 1 --- F13 0 2
47381 0x1CD4 Analog input 8 Max -2147483648 2147483647 1 --- F13 214748364 2
7

12-86 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

350 Format Codes


In some cases names of settings displayed in the HMI have been shortened. The Long
Definition column below contains the full name used in the Enervista Setup software, when
applicable. In many cases the long description is the same as the description.

Code Type Definition Long Definition


F1 unsigned 16 bits Unsigned Value
Example: 1234 stored as 1234
F1B unsigned 16 bits Unsigned Value Max Value = OFF
Example: 1234 stored as 1234
F1C unsigned 16 bits Unsigned Value Min Value = OFF
Example: 1234 stored as 1234
F2 unsigned 16 bits Unsigned Value 1 Decimal Place
Example: 123.4 stored as 1234
F2B unsigned 16 bits Unsigned Value 1 Decimal Place
Example: 123.4 stored as 1234
F3 unsigned 16 bits Unsigned Value 2 Decimal Places
Example: 12.34 stored as 1234
F3B unsigned 16 bits Unsigned Value 2 Decimal Places
Example: 12.34 stored as 1234
F4 signed 16 bits 2's Complement Signed Value
Example: -1234 stored as -1234 i.e. 64302
F4B signed 16 bits 2's Complement Signed Value Max Value
= OFF
Example: -1234 stored as -1234 i.e. 64302
F5 signed 16 bits 2's Complement Signed Value 1 Decimal
Place
Example: -123.4 stored as -1234 i.e. 64302
F6 signed 16 bits 2's Complement Signed Value 2 Decimal
Places
Example: -12.34 stored as -1234 i.e. 64302
F7 signed 16 bits 2's Complement Signed Value 3 Decimal
Places
Example: -1.234 stored as -1234 i.e. 64302
F8 signed 16 bits 2's Complement Signed Value 4 Decimal
Places
Example: -0.1234 stored as -1234 i.e. 64302
F9 unsigned 32 bits Unsigned Long Value
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: 123456 stored as 123456
i.e. 1st word: 0001 hex 2nd word: E240 hex
F10 unsigned 32 bits Unsigned Long Value 1 Decimal Place
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: 12345.6 stored as 123456
i.e. 1st word: 0001 hex 2nd word: E240 hex

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-87


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


F11 unsigned 32 bits Unsigned Long Value 1 Decimal Place
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: 1234.56 stored as 123456
i.e. 1st word: 0001 hex 2nd word: E240 hex
F12 signed 32 bits 2's Complement Signed Long Value
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: -123456 stored as -123456
i.e. 1st word: FFFE hex 2nd word: 1DC0 hex
F13 signed 32 bits 2's Complement Signed Long Value 1
Decimal Place
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: -12345.6 stored as -123456
i.e. 1st word: FFFE hex 2nd word: 1DC0 hex
F14 signed 32 bits 2's Complement Signed Long Value 2
Decimal Places
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: -1234.56 stored as -123456
i.e. 1st word: FFFE hex 2nd word: 1DC0 hex
F14A signed 32 bits 2's Complement Signed Long Value 3
Decimal Places
F15 unsigned 16 bits Hardware Revision
0 Prototype Prototype
1 A A
2 B B
3 C C
4 D D
5 E E
6 F F
7 G G
8 H H
9 I I
10 J J
11 K K
12 L L
13 M M
14 N N
15 O O
16 P P
17 Q Q
18 R R
19 S S
20 T T
21 U U
22 V V

12-88 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


23 W W
24 X X
25 Y Y
26 Z Z
F16 signed 16 bits 2's Complement Signed Value 1 Decimal
Place
F17 unsigned 32 bits Unsigned Long Value 3 Decimal Places
F17A unsigned 16 bits Unsigned Value 3 Decimal Places
F18 unsigned 32 bits Date MM/DD/YYYY
1st byte Month 1 to 12
2nd byte Day 1 to 31
3rd and 4th byte Year 2000 to 2099 2000 stored as 34867152 (i.e. 1st word: 0214 2nd word 07D0)
Example: Feb 20
F19 unsigned 32 bits Time HH:MM:SS.sss
1st byte Hours 0 to 23
2nd byte Minutes 0 to 59
3rd and 4th byte miliSeconds 0 to 59999
Example: 2:05pm stored as 235208704 (i.e. 1st word: 0E05 2nd word 0000)
F20 signed 32 bits 2's Complement Signed Long Value
F21 signed 16 bits 2's Complement Signed Value
F22 unsigned 16 bits Two 8-BIT Characters Packed Into 16-BIT
Unsigned
F23 unsigned 16 bits Unsigned Value
F24 unsigned 16 bits Unsigned Value AS Seconds SHOW AS
Duration
F24B unsigned 16 bits Unsigned Value AS Seconds SHOW AS
Duration
F25 unsigned 16 bits Trace Memory Channel Data
0 Leading Leading
1 Lagging Lagging
F26 unsigned 16 bits 350 Trace Memory Channel Data
0 Va Va
1 Vb Vb
2 Vc Vc
3 Vx Vx
4 Not Used Not Used
5 Not Used Not Used
6 Ia Ia
7 Ib Ib
8 Ic Ic
9 Ig Ig
10 Inputs 1-16 Inputs 1-16
11 Outputs 1-16 Outputs 1-16
12 Virtual Inputs1-16 Virtual Inputs 1-16
13 Virtual Inputs7-32 Virtual Inputs 17-32
14 Remote INs 1-16 Remote Inputs 1-16
15 Remote INs 17-32 Remote Inputs 17-32
16 Logic Elements Logic Elements

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-89


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


F26A unsigned 16 bits 339 Trace Memory Channel Data
0 Va Va
1 Vb Vb
2 Vc Vc
4 Not Used Not Used
5 Not Used Not Used
6 Ia Ia
7 Ib Ib
8 Ic Ic
9 Ig Ig
10 Inputs 1-16 Inputs 1-16
11 Outputs 1-16 Outputs 1-16
12 Virtual Inputs1-16 Virtual Inputs 1-16
13 Virtual Inputs7-32 Virtual Inputs 17-32
14 Remote INs 1-16 Remote Inputs 1-16
15 Remote INs 17-32 Remote Inputs 17-32
16 Logic Elements Logic Elements
F26B unsigned 16 bits 345 Trace Memory Channel Data
F27 unsigned 32 bits Unsigned Long Value 4 Decimal Places
F36 unsigned 16 bits OC Curve Selection
0 Extremely Inverse Extremely Inverse
1 Very Inverse Very Inverse
2 Normally Inverse Normally Inverse
3 Moderately Inverse Moderately Inverse
4 Definite Time Definite Time
5 IEC Curve A IEC Curve A
6 IEC Curve B IEC Curve B
7 IEC Curve C IEC Curve C
8 Flex Curve A Flex Curve A
9 Flex Curve B Flex Curve B
10 IAC Extr. Inverse IAC Extremely Inverse
11 IAC Very Inverse IAC Very Inverse
12 IAC Inverse IAC Inverse
13 IAC Short Inverse IAC Short Inverse
14 IEC Short Inverse IEC Short Inverse
15 User Curve User Curve
F37 unsigned 16 bits OC Pickup flags
1 Phase A Phase A
2 Phase B Phase B
4 Phase C Phase C
7 All Phases All Phases
F38 unsigned 16 bits OC Direction pickup flags
0x10 Direction PKP Ph A Direction PKP Phase A
0x20 Direction PKP Ph B Direction PKP Phase B
0x40 Direction PKP Ph C Direction PKP Phase C
0x80 Direction Pickup Direction Pickup
0xF0 Direction Direction

12-90 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


F48 unsigned 16 bits Simulation Status
0 Disabled Disabled
1 Prefault State Prefault State
2 Fault State Fault State
3 Postfault State Postfault State
F68 unsigned 16 bits Reset Time Model
0 Instantaneous Instantaneous
1 Linear Linear
F74 unsigned 16 bits Data Logger Sample Rate
0 1 Cycle 1 Cycle
1 1 Second 1 Second
2 1 Minute 1 Minute
3 1 Hour 1 Hour
F75 unsigned 16 bits Data Logger Status
0 Stopped Stopped
1 Started Started
2 Triggered Triggered
3 Pretrigger Pretrigger
4 PostTrigger PostTrigger
F76 unsigned 16 bits Overcurrent Direction
0 Disabled Disabled
1 Forward Forward
2 Reverse Reverse
F77 unsigned 16 bits Data Logger Channel Data
0 Disabled Disabled
1 Phase A Current Phase A Current
2 Phase B Current Phase B Current
3 Phase C Current Phase C Current
4 Avg Phase Current Average Phase Current
7 Gnd Current Gnd Current
8 System Frequency System Frequency
9 Vab Vab
10 Vbc Vbc
11 Vca Vca
12 Van Van
13 Vbn Vbn
14 Vcn Vcn
15 Power Factor Power Factor
16 Real Power Real Power
17 Reactive Pwr Reactive Power
18 Apparent Pwr Apparent Power
19 Positive Watthours Positive Watthours
20 Positive Varhours Positive Varhours
21 Hottest Stator RTD Hottest Stator RTD
22 Therm Cap. Used Thermal Capacity Used
F77B unsigned 16 bits 345 Data Logger Channel Data
F78 unsigned 16 bits DNP Object 20 Default Variation

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-91


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


1 1 (1) 32-Bit Binary Counter
2 2 (2) 16-Bit Binary Counter
5 5 (5) 32-Bit Binary Counter w/o Flag
6 6 (6) 16-Bit Binary Counter w/o Flag
F79 unsigned 16 bits DNP Object 21 Default Variation
1 1 (1) 32-Bit Frozen Counter
2 2 (2) 16-Bit Frozen Counter
9 9 (9) 32-Bit Frozen Counter w/o Flag
10 10 (10) 16-Bit Frozen Counter w/o Flag
F80 unsigned 16 bits DNP Object 22 Default Variation
1 1 (1) 32-Bit Counter Change Event
2 2 (2) 16-Bit Counter Change Event
5 5 (5) 32-Bit Counter Change Event w Time
6 6 (6) 16-Bit Counter Change Event w Time
F81 unsigned 16 bits DNP Object 23 Default Variation
1 1 (1) 32-Bit Frozen Counter Event
2 2 (2) 16-Bit Frozen Counter Event
5 5 (5) 32-Bit Frozen Counter Event w Time
6 6 (6) 16-Bit Frozen Counter Event w Time
F82 unsigned 16 bits DNP Object 30 Default Variation
1 1 (1) 32-Bit Analog Input
2 2 (2) 16-Bit Analog Input
3 3 (3) 32-Bit Analog Input w/o Flag
4 4 (4) 16-Bit Analog Input w/o Flag
F83 unsigned 16 bits DNP Object 32 Default Variation
1 1 (1) 32-Bit Analog Change Event w/o Time
2 2 (2) 16-Bit Analog Change Event w/o Time
3 3 (3) 32-Bit Analog Change Event w Time
4 4 (4) 16-Bit Analog Change Event w Time
F85 unsigned 16 bits DNP Analog Input Point Scale Factor
1 / 0.001 / 0.001
2 / 0.01 / 0.01
3 / 0.1 / 0.1
4 /1 /1
5 / 10 / 10
6 / 100 / 100
7 / 1000 / 1000
8 / 10000 / 10000
9 / 100000 / 100000
F86 unsigned 16 bits DNP and 103 Binary Output Points
0 Off Off
1 Virtual Input 1 Virtual Input 1
2 Virtual Input 2 Virtual Input 2
3 Virtual Input 3 Virtual Input 3
4 Virtual Input 4 Virtual Input 4
5 Virtual Input 5 Virtual Input 5
6 Virtual Input 6 Virtual Input 6

12-92 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


7 Virtual Input 7 Virtual Input 7
8 Virtual Input 8 Virtual Input 8
9 Virtual Input 9 Virtual Input 9
10 Virtual Input 10 Virtual Input 10
11 Virtual Input 11 Virtual Input 11
12 Virtual Input 12 Virtual Input 12
13 Virtual Input 13 Virtual Input 13
14 Virtual Input 14 Virtual Input 14
15 Virtual Input 15 Virtual Input 15
16 Virtual Input 16 Virtual Input 16
17 Virtual Input 17 Virtual Input 17
18 Virtual Input 18 Virtual Input 18
19 Virtual Input 19 Virtual Input 19
20 Virtual Input 20 Virtual Input 20
21 Virtual Input 21 Virtual Input 21
22 Virtual Input 22 Virtual Input 22
23 Virtual Input 23 Virtual Input 23
24 Virtual Input 24 Virtual Input 24
25 Virtual Input 25 Virtual Input 25
26 Virtual Input 26 Virtual Input 26
27 Virtual Input 27 Virtual Input 27
28 Virtual Input 28 Virtual Input 28
29 Virtual Input 29 Virtual Input 29
30 Virtual Input 30 Virtual Input 30
31 Virtual Input 31 Virtual Input 31
32 Virtual Input 32 Virtual Input 32
33 FC: Reset Force Coil: Reset
34 FC: Open Breaker Force Coil: Open Breaker
35 FC: Close Breaker Force Coil: Close Breaker
36 FC: Display Msg Force Coil: Display Message
37 FC: Clear Curr Dmd1 Force Coil: Clear Current Dmd1
39 FC: Clear Pwr Dmd Force Coil: Clear Power Dmd
40 FC:Clear Fault Rep FC:Clear Fault Rep
F87 unsigned 16 bits DNP/Ethernet Channel Port
0 None None
1 TCP TCP
2 UDP UDP
F88 unsigned 16 bits Analog Values
0 Disabled Disabled
1 Phase A Current Phase A Current
2 Phase B Current Phase B Current
3 Phase C Current Phase C Current
7 Gnd Current Gnd Current
8 System Frequency System Frequency
9 Vab Vab
10 Vbc Vbc
11 Vca Vca

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-93


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


12 Van Van
13 Vbn Vbn
14 Vcn Vcn
15 Power Factor Power Factor
16 Real Power Real Power
17 Reactive Pwr Reactive Power
18 Apparent Pwr Apparent Power
19 Positive Watthours Positive Watthours
20 Positive Varhours Positive Varhours
21 Negative Watthours Negative Watthours
22 Negative Varhours Negative Varhours
23 Therm Cap. Phase A Thermal Capacity Phase A
24 Therm Cap. Phase B Thermal Capacity Phase B
25 Therm Cap. Phase C Thermal Capacity Phase C
26 Ntrl Current Ntrl Current
27 Ntrl Voltage Ntrl Voltage
28 Aux Volt Auxiliary Voltage
29 NSeq Current Negative Sequence Current
43 SGnd Current Sensitive Ground Current
46 NSeq Voltage Negative Sequence Voltage
49 Zero Seq Voltage Zero Seq Voltage
50 Pos Seq Current Pos Seq Current
51 Zero Seq Current Zero Seq Current
52 Pos Seq Voltage Pos Seq Voltage
53 WGF Power 1 Wattmetric Power 1
54 WGF Power 2 Wattmetric Power 2
55 Dir Power 1 Directional Power 1
56 Dir Power 2 Directional Power 2
57 2nd Hrmc Ph A Curr 2nd Hrmc Ph A Current
58 2nd Hrmc Ph B Curr 2nd Hrmc Ph B Current
59 2nd Hrmc Ph C Curr 2nd Hrmc Ph C Current
60 FR Date (Upper 16) Fault Report Date (Upper 16)
61 FR Date (Lower 16) Fault Report Date (Lower 16)
62 FR Time (Upper 16) Fault Report Time (Upper 16)
63 FR Time (Lower 16) Fault Report Time (Lower 16)
64 FR Fault Type Fault Report Fault Type
65 FR Ia Fault Report Ia
66 FR Ia Angle Fault Report Ia Angle
67 FR Ib Fault Report Ib
68 FR Ib Angle Fault Report Ib Angle
69 FR Ic Fault Report Ic
70 FR Ic Angle Fault Report Ic Angle
71 FR Ig Fault Report Ig
72 FR Ig Angle Fault Report Ig Angle
73 FR In Fault Report In
74 FR In Angle Fault Report In Angle
75 FR Va Fault Report Va

12-94 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


76 FR Va Angle Fault Report Va Angle
77 FR Vb Fault Report Vb
78 FR Vb Angle Fault Report Vb Angle
79 FR Vc Fault Report Vc
80 FR Vc Angle Fault Report Vc Angle
81 FR Vab Fault Report Vab
82 FR Vab Angle Fault Report Vab Angle
83 FR Vbc Fault Report Vbc
84 FR Vbc Angle Fault Report Vbc Angle
85 FR Vca Fault Report Vca
86 FR Vca Angle Fault Report Vca Angle
87 FR Vn Fault Report Vn
88 FR Vn Angle Fault Report Vn Angle
89 FR Vaux Fault Report Vaux
90 FR Vaux Angle Fault Report Vaux Angle
91 FR System Freq Fault Report System Frequency
114 FR Phases Fault Report Phases
115 Current Dmd 1 PhA Current Demand 1 PhA
116 Current Dmd 1 PhB Current Demand 1 PhB
117 Current Dmd 1 PhC Current Demand 1 PhC
118 Max Curr Dmd1 PhA Max Current Demand 1 PhA
119 Max Curr Dmd1 PhB Max Current Demand 1 PhB
120 Max Curr Dmd1 PhC Max Current Demand 1 PhC
127 Real Pwr Dmd Real Power Demand
128 React Pwr Dmd Reactive Power Demand
129 App Pwr Dmd Apparent Power Demand
130 Max Real Pwr Dmd Max Real Power Demand
131 Max React Pwr Dmd Max Reactive Power Demand
132 Max App Pwr Dmd Max Apparent Power Demand
133 Total Num of Trips Total Num of Trips
154 Curr Unbalance Current Unbalance
155 PhA Curr Angle PhA Current Angle
156 PhB Curr Angle PhB Current Angle
157 PhC Curr Angle PhC Current Angle
158 Van Angle Van Angle
159 Vbn Angle Vbn Angle
160 Vcn Angle Vcn Angle
161 Ig Angle Ig Angle
162 In Angle In Angle
163 Ntrl Voltage Angle Neutral Voltage Angle
164 Vaux Angle Vaux Angle
165 Vab Angle Vab Angle
166 Vbc Angle Vbc Angle
167 Vca Angle Vca Angle
169 Bus Freq Bus Freq
170 Line Freq Line Freq
171 Voltage Unbalance Voltage Unbalance

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-95


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


178 Internal Temp Internal Temp
187 Ambient Temp Ambient Temperature
188 Internal Temp Max Internal Temperature Max
189 Pos Seq I Angle Positive Sequence I Angle
190 Neg Seq I Angle Negative Sequence I Angle
191 Zero Seq I Angle Zero Sequence I Angle
192 Pos Seq V Angle Positive Sequence V Angle
193 Neg Seq V Angle Negative Sequence V Angle
194 Zero Seq V Angle Zero Sequence V Angle
204 I^2 Counter I^2 Counter
206 Volts per Hertz Volts per Hertz
237 BKR Health Breaker Health
238 BKR Last Trip Time Breaker Last Trip Time
239 BKR Avg Trip Time Breaker Average Trip Time
240 BKR Last Close Time Breaker Last Close Time
241 BKR Avg Close Time Breaker Average Close Time
242 BKR Last Charge Time Breaker Last Charge Time
243 BKR Avg Charge Time Breaker Average Charge Time
F89 unsigned 16 bits Autoreclose Block
0 Off Off
1 On On
0x40 Contact Input 1 Contact Input 1
0x41 Contact Input 2 Contact Input 2
0x42 Contact Input 3 Contact Input 3
0x43 Contact Input 4 Contact Input 4
0x44 Contact Input 5 Contact Input 5
0x45 Contact Input 6 Contact Input 6
0x46 Contact Input 7 Contact Input 7
0x47 Contact Input 8 Contact Input 8
0x48 Contact Input 9 Contact Input 9
0x49 Contact Input 10 Contact Input 10
0x80 Virtual Input 1 Virtual Input 1
0x81 Virtual Input 2 Virtual Input 2
0x82 Virtual Input 3 Virtual Input 3
0x83 Virtual Input 4 Virtual Input 4
0x84 Virtual Input 5 Virtual Input 5
0x85 Virtual Input 6 Virtual Input 6
0x86 Virtual Input 7 Virtual Input 7
0x87 Virtual Input 8 Virtual Input 8
0x88 Virtual Input 9 Virtual Input 9
0x89 Virtual Input 10 Virtual Input 10
0x8A Virtual Input 11 Virtual Input 11
0x8B Virtual Input 12 Virtual Input 12
0x8C Virtual Input 13 Virtual Input 13
0x8D Virtual Input 14 Virtual Input 14
0x8E Virtual Input 15 Virtual Input 15
0x8F Virtual Input 16 Virtual Input 16

12-96 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x90 Virtual Input 17 Virtual Input 17
0x91 Virtual Input 18 Virtual Input 18
0x92 Virtual Input 19 Virtual Input 19
0x93 Virtual Input 20 Virtual Input 20
0x94 Virtual Input 21 Virtual Input 21
0x95 Virtual Input 22 Virtual Input 22
0x96 Virtual Input 23 Virtual Input 23
0x97 Virtual Input 24 Virtual Input 24
0x98 Virtual Input 25 Virtual Input 25
0x99 Virtual Input 26 Virtual Input 26
0x9A Virtual Input 27 Virtual Input 27
0x9B Virtual Input 28 Virtual Input 28
0x9C Virtual Input 29 Virtual Input 29
0x9D Virtual Input 30 Virtual Input 30
0x9E Virtual Input 31 Virtual Input 31
0x9F Virtual Input 32 Virtual Input 32
0xC0 Logic Element 1 Logic Element 1
0xC1 Logic Element 2 Logic Element 2
0xC2 Logic Element 3 Logic Element 3
0xC3 Logic Element 4 Logic Element 4
0xC4 Logic Element 5 Logic Element 5
0xC5 Logic Element 6 Logic Element 6
0xC6 Logic Element 7 Logic Element 7
0xC7 Logic Element 8 Logic Element 8
0xC8 Logic Element 9 Logic Element 9
0xC9 Logic Element 10 Logic Element 10
0xCA Logic Element 11 Logic Element 11
0xCB Logic Element 12 Logic Element 12
0xCC Logic Element 13 Logic Element 13
0xCD Logic Element 14 Logic Element 14
0xCE Logic Element 15 Logic Element 15
0xCF Logic Element 16 Logic Element 16
0x1C0 Remote Input 1 Remote Input 1
0x1C1 Remote Input 2 Remote Input 2
0x1C2 Remote Input 3 Remote Input 3
0x1C3 Remote Input 4 Remote Input 4
0x1C4 Remote Input 5 Remote Input 5
0x1C5 Remote Input 6 Remote Input 6
0x1C6 Remote Input 7 Remote Input 7
0x1C7 Remote Input 8 Remote Input 8
0x1C8 Remote Input 9 Remote Input 9
0x1C9 Remote Input 10 Remote Input 10
0x1CA Remote Input 11 Remote Input 11
0x1CB Remote Input 12 Remote Input 12
0x1CC Remote Input 13 Remote Input 13
0x1CD Remote Input 14 Remote Input 14
0x1CE Remote Input 15 Remote Input 15

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-97


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x1CF Remote Input 16 Remote Input 16
0x1D0 Remote Input 17 Remote Input 17
0x1D1 Remote Input 18 Remote Input 18
0x1D2 Remote Input 19 Remote Input 19
0x1D3 Remote Input 20 Remote Input 20
0x1D4 Remote Input 21 Remote Input 21
0x1D5 Remote Input 22 Remote Input 22
0x1D6 Remote Input 23 Remote Input 23
0x1D7 Remote Input 24 Remote Input 24
0x1D8 Remote Input 25 Remote Input 25
0x1D9 Remote Input 26 Remote Input 26
0x1DA Remote Input 27 Remote Input 27
0x1DB Remote Input 28 Remote Input 28
0x1DC Remote Input 29 Remote Input 29
0x1DD Remote Input 30 Remote Input 30
0x1DE Remote Input 31 Remote Input 31
0x1DF Remote Input 32 Remote Input 32
0xAF02 2nd Hrmc Alarm 2nd Harmonic Alarm
0xCF02 2nd Hrmc 2nd Harmonic
0xB881 CT Fail Alarm PKP CT Fail Alarm PKP
0xB882 CT Fail Alarm OP CT Fail Alarm OP
F89A unsigned 16 bits BKR Health Charge Input
0 Off Off
0x40 Contact Input 1 Contact Input 1
0x41 Contact Input 2 Contact Input 2
0x42 Contact Input 3 Contact Input 3
0x43 Contact Input 4 Contact Input 4
0x44 Contact Input 5 Contact Input 5
0x45 Contact Input 6 Contact Input 6
0x46 Contact Input 7 Contact Input 7
0x47 Contact Input 8 Contact Input 8
0x48 Contact Input 9 Contact Input 9
0x49 Contact Input 10 Contact Input 10
0x80 Virtual Input 1 Virtual Input 1
0x81 Virtual Input 2 Virtual Input 2
0x82 Virtual Input 3 Virtual Input 3
0x83 Virtual Input 4 Virtual Input 4
0x84 Virtual Input 5 Virtual Input 5
0x85 Virtual Input 6 Virtual Input 6
0x86 Virtual Input 7 Virtual Input 7
0x87 Virtual Input 8 Virtual Input 8
0x88 Virtual Input 9 Virtual Input 9
0x89 Virtual Input 10 Virtual Input 10
0x8A Virtual Input 11 Virtual Input 11
0x8B Virtual Input 12 Virtual Input 12
0x8C Virtual Input 13 Virtual Input 13
0x8D Virtual Input 14 Virtual Input 14

12-98 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x8E Virtual Input 15 Virtual Input 15
0x8F Virtual Input 16 Virtual Input 16
0x90 Virtual Input 17 Virtual Input 17
0x91 Virtual Input 18 Virtual Input 18
0x92 Virtual Input 19 Virtual Input 19
0x93 Virtual Input 20 Virtual Input 20
0x94 Virtual Input 21 Virtual Input 21
0x95 Virtual Input 22 Virtual Input 22
0x96 Virtual Input 23 Virtual Input 23
0x97 Virtual Input 24 Virtual Input 24
0x98 Virtual Input 25 Virtual Input 25
0x99 Virtual Input 26 Virtual Input 26
0x9A Virtual Input 27 Virtual Input 27
0x9B Virtual Input 28 Virtual Input 28
0x9C Virtual Input 29 Virtual Input 29
0x9D Virtual Input 30 Virtual Input 30
0x9E Virtual Input 31 Virtual Input 31
0x9F Virtual Input 32 Virtual Input 32
0xC0 Logic Element 1 Logic Element 1
0xC1 Logic Element 2 Logic Element 2
0xC2 Logic Element 3 Logic Element 3
0xC3 Logic Element 4 Logic Element 4
0xC4 Logic Element 5 Logic Element 5
0xC5 Logic Element 6 Logic Element 6
0xC6 Logic Element 7 Logic Element 7
0xC7 Logic Element 8 Logic Element 8
0xC8 Logic Element 9 Logic Element 9
0xC9 Logic Element 10 Logic Element 10
0xCA Logic Element 11 Logic Element 11
0xCB Logic Element 12 Logic Element 12
0xCC Logic Element 13 Logic Element 13
0xCD Logic Element 14 Logic Element 14
0xCE Logic Element 15 Logic Element 15
0xCF Logic Element 16 Logic Element 16
0x1C0 Remote Input 1 Remote Input 1
0x1C1 Remote Input 2 Remote Input 2
0x1C2 Remote Input 3 Remote Input 3
0x1C3 Remote Input 4 Remote Input 4
0x1C4 Remote Input 5 Remote Input 5
0x1C5 Remote Input 6 Remote Input 6
0x1C6 Remote Input 7 Remote Input 7
0x1C7 Remote Input 8 Remote Input 8
0x1C8 Remote Input 9 Remote Input 9
0x1C9 Remote Input 10 Remote Input 10
0x1CA Remote Input 11 Remote Input 11
0x1CB Remote Input 12 Remote Input 12
0x1CC Remote Input 13 Remote Input 13

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-99


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x1CD Remote Input 14 Remote Input 14
0x1CE Remote Input 15 Remote Input 15
0x1CF Remote Input 16 Remote Input 16
0x1D0 Remote Input 17 Remote Input 17
0x1D1 Remote Input 18 Remote Input 18
0x1D2 Remote Input 19 Remote Input 19
0x1D3 Remote Input 20 Remote Input 20
0x1D4 Remote Input 21 Remote Input 21
0x1D5 Remote Input 22 Remote Input 22
0x1D6 Remote Input 23 Remote Input 23
0x1D7 Remote Input 24 Remote Input 24
0x1D8 Remote Input 25 Remote Input 25
0x1D9 Remote Input 26 Remote Input 26
0x1DA Remote Input 27 Remote Input 27
0x1DB Remote Input 28 Remote Input 28
0x1DC Remote Input 29 Remote Input 29
0x1DD Remote Input 30 Remote Input 30
0x1DE Remote Input 31 Remote Input 31
0x1DF Remote Input 32 Remote Input 32
0xAF02 2nd Hrmc Alarm 2nd Harmonic Alarm
0xCF02 2nd Hrmc 2nd Harmonic
0xB881 CT Fail Alarm PKP CT Fail Alarm PKP
0xB882 CT Fail Alarm OP CT Fail Alarm OP
F89B unsigned 16 bits Start Thermal Protection
0 Off Off
1 On On
0x40 Contact Input 1 Contact Input 1
0x41 Contact Input 2 Contact Input 2
0x42 Contact Input 3 Contact Input 3
0x43 Contact Input 4 Contact Input 4
0x44 Contact Input 5 Contact Input 5
0x45 Contact Input 6 Contact Input 6
0x46 Contact Input 7 Contact Input 7
0x47 Contact Input 8 Contact Input 8
0x48 Contact Input 9 Contact Input 9
0x49 Contact Input 10 Contact Input 10
0x80 Virtual Input 1 Virtual Input 1
0x81 Virtual Input 2 Virtual Input 2
0x82 Virtual Input 3 Virtual Input 3
0x83 Virtual Input 4 Virtual Input 4
0x84 Virtual Input 5 Virtual Input 5
0x85 Virtual Input 6 Virtual Input 6
0x86 Virtual Input 7 Virtual Input 7
0x87 Virtual Input 8 Virtual Input 8
0x88 Virtual Input 9 Virtual Input 9
0x89 Virtual Input 10 Virtual Input 10
0x8A Virtual Input 11 Virtual Input 11

12-100 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x8B Virtual Input 12 Virtual Input 12
0x8C Virtual Input 13 Virtual Input 13
0x8D Virtual Input 14 Virtual Input 14
0x8E Virtual Input 15 Virtual Input 15
0x8F Virtual Input 16 Virtual Input 16
0x90 Virtual Input 17 Virtual Input 17
0x91 Virtual Input 18 Virtual Input 18
0x92 Virtual Input 19 Virtual Input 19
0x93 Virtual Input 20 Virtual Input 20
0x94 Virtual Input 21 Virtual Input 21
0x95 Virtual Input 22 Virtual Input 22
0x96 Virtual Input 23 Virtual Input 23
0x97 Virtual Input 24 Virtual Input 24
0x98 Virtual Input 25 Virtual Input 25
0x99 Virtual Input 26 Virtual Input 26
0x9A Virtual Input 27 Virtual Input 27
0x9B Virtual Input 28 Virtual Input 28
0x9C Virtual Input 29 Virtual Input 29
0x9D Virtual Input 30 Virtual Input 30
0x9E Virtual Input 31 Virtual Input 31
0x9F Virtual Input 32 Virtual Input 32
0xC0 Logic Element 1 Logic Element 1
0xC1 Logic Element 2 Logic Element 2
0xC2 Logic Element 3 Logic Element 3
0xC3 Logic Element 4 Logic Element 4
0xC4 Logic Element 5 Logic Element 5
0xC5 Logic Element 6 Logic Element 6
0xC6 Logic Element 7 Logic Element 7
0xC7 Logic Element 8 Logic Element 8
0xC8 Logic Element 9 Logic Element 9
0xC9 Logic Element 10 Logic Element 10
0xCA Logic Element 11 Logic Element 11
0xCB Logic Element 12 Logic Element 12
0xCC Logic Element 13 Logic Element 13
0xCD Logic Element 14 Logic Element 14
0xCE Logic Element 15 Logic Element 15
0xCF Logic Element 16 Logic Element 16
0x1C0 Remote Input 1 Remote Input 1
0x1C1 Remote Input 2 Remote Input 2
0x1C2 Remote Input 3 Remote Input 3
0x1C3 Remote Input 4 Remote Input 4
0x1C4 Remote Input 5 Remote Input 5
0x1C5 Remote Input 6 Remote Input 6
0x1C6 Remote Input 7 Remote Input 7
0x1C7 Remote Input 8 Remote Input 8
0x1C8 Remote Input 9 Remote Input 9
0x1C9 Remote Input 10 Remote Input 10

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-101


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x1CA Remote Input 11 Remote Input 11
0x1CB Remote Input 12 Remote Input 12
0x1CC Remote Input 13 Remote Input 13
0x1CD Remote Input 14 Remote Input 14
0x1CE Remote Input 15 Remote Input 15
0x1CF Remote Input 16 Remote Input 16
0x1D0 Remote Input 17 Remote Input 17
0x1D1 Remote Input 18 Remote Input 18
0x1D2 Remote Input 19 Remote Input 19
0x1D3 Remote Input 20 Remote Input 20
0x1D4 Remote Input 21 Remote Input 21
0x1D5 Remote Input 22 Remote Input 22
0x1D6 Remote Input 23 Remote Input 23
0x1D7 Remote Input 24 Remote Input 24
0x1D8 Remote Input 25 Remote Input 25
0x1D9 Remote Input 26 Remote Input 26
0x1DA Remote Input 27 Remote Input 27
0x1DB Remote Input 28 Remote Input 28
0x1DC Remote Input 29 Remote Input 29
0x1DD Remote Input 30 Remote Input 30
0x1DE Remote Input 31 Remote Input 31
0x1DF Remote Input 32 Remote Input 32
F90 unsigned 16 bits Operate / Do Not Operate
0 Do Not Operate Do Not Operate
1 Operate Operate
F91 signed 16 bits Edit Group
-1 Active Group Active Group
0 SP Group 1 Active Setpoint Group 1 Active
1 SP Group 2 Active Setpoint Group 2 Active
F92 unsigned 16 bits Phases
1 Any One Any One
2 Any Two Any Two
3 All Three All Three
F92A unsigned 16 bits Phases + Average
0 Any One Any One
1 Any Two Any Two
2 All Three All Three
3 Average Average
F93 unsigned 16 bits Phase UV Curve
0 Definite Time Definite Time
1 Inverse Time Inverse Time
F94 unsigned 16 bits Breaker Control
0 Disabled Disabled
1 Contact Input 1 Contact Input 1
2 Contact Input 2 Contact Input 2
3 Contact Input 3 Contact Input 3
4 Contact Input 4 Contact Input 4

12-102 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


5 Contact Input 5 Contact Input 5
6 Contact Input 6 Contact Input 6
7 Contact Input 7 Contact Input 7
8 Contact Input 8 Contact Input 8
9 Contact Input 9 Contact Input 9
10 Contact Input 10 Contact Input 10
F95 unsigned 16 bits Transient Recorder Buffer
0 1 1
1 3 3
2 6 6
F96 unsigned 16 bits Directional Polarizing
1 Voltage Voltage
2 Current Current
3 Dual Dual
F97 unsigned 16 bits Rear 485 Port Protocol
0 Modbus Modbus
1 IEC60870-5-103 IEC60870-5-103
2 DNP 3.0 DNP 3.0
F98 unsigned 16 bits Simulated Key Press
0 No Key Press No Key Press
1 Nav Up Key Nav Up Key
2 Nav Left Key Nav Left Key
3 Nav Down Key Navigation Down Key
4 Nav Right Key Navigation Right Key
5 Up Key Up Key
6 Down Key Down Key
7 Enter Key Enter Key
8 Menu Key Menu Key
9 Escape Key Escape Key
10 Reset Key Reset Key
F99 unsigned 16 bits SR 3 Relay Status
0 Not Ready Not Ready
1 Ready Ready
FC100 unsigned 16 bits SNTP Mode
0 Disabled Disabled
1 Unicast Unicast
2 Anycast Anycast
3 Broadcast Broadcast
FC101 unsigned 16 bits RS 485 Baud Rate
0 9600 baud 9600 baud
1 19200 baud 19200 baud
2 38400 baud 38400 baud
3 57600 baud 57600 baud
4 115200 baud 115200 baud
FC102 unsigned 16 bits RS 485 Parity
0 None None
1 Odd Odd

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-103


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


2 Even Even
FC103 unsigned 16 bits Off / On Selection
0 Off Off
1 On On
FC103A unsigned 16 bits No / Yes Selection
0 NO NO
1 YES YES
FC104 unsigned 16 bits Ground CT Type
0 1 A Secondary 1 A Secondary
1 5 A Secondary 5 A Secondary
FC105 unsigned 16 bits Differential CT Type
0 None None
1 1 A Secondary 1 A Secondary
2 5 A Secondary 5 A Secondary
3 Direct Connect Direct Connect
FC106 unsigned 16 bits Voltage Transformer Connection Type
0 Wye Wye
1 Delta Delta
FC107 unsigned 16 bits Supply Frequency
0 60 Hz 60 Hz
1 50 Hz 50 Hz
FC108 unsigned 16 bits 61850 Status
0 Not Ready Not Ready
1 Ready Ready
2 Default CID Default CID
FC109 unsigned 16 bits Flex Logic Status
0 OK OK
1 Unknown Token Unknown Token
2 TooMany Latches Too Many Latches
3 TooMany Timers Too Many Timers
4 TooMany + OneShots Too Many + One Shots
5 TooMany - OneShots Too Many - One Shots
6 TooMany Duel1Shots Too Many Duel One Shots
7 Stack Overflow Stack Overflow
8 Stack Underflow Stack Underflow
9 Program Too Long Program Too Long
FC111 unsigned 16 bits Trip Relays
0 Trip Trip
1 Alarm Alarm
FC112 unsigned 16 bits Communication Status
0 Error Error
1 OK OK
FC115 unsigned 16 bits Alarm Type Selection
0 Off Off
1 Trip Trip
2 Alarm Alarm
FC116 unsigned 16 bits Switch Type

12-104 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0 Open Open
1 Closed Closed
FC117 unsigned 16 bits Directional Voltage
0 Measured (Vx) Measured (Vx)
1 Calculated (VTs) Calculated (VTs)
FC118 unsigned 16 bits WGF Voltage
0 Calculated (Vn) Calculated (Vn)
1 Measured (Vx) Measured (Vx)
FC119 unsigned 16 bits WGF Current
0 Calculated (In) Calculated (In)
1 Measured (Ig) Measured (Ig)
FC120 unsigned 16 bits RTD Type
FC121 unsigned 16 bits RTD Application
0 None None
4 Other Other
FC122 unsigned 16 bits RTD Voting Selection
0 Off Off
FC123 unsigned 16 bits Select DV Voltage
0 17V Threshold 17V Threshold
1 33V Threshold 33V Threshold
2 84V Threshold 84V Threshold
3 166V Threshold 166V Threshold
FC124 unsigned 16 bits Phase Rotation
0 ABC ABC
1 CBA CBA
FC124A unsigned 16 bits Phase Rotation
0 ABC ABC
1 ACB ACB
FC125 unsigned 16 bits Coil Monitor
0 Healthy Healthy
1 Unhealthy Unhealthy
FC126 unsigned 16 bits Disabled / Enabled Selection
0 Disabled Disabled
1 Enabled Enabled
FC127 unsigned 16 bits System Language
0 English English
1 Chinese Chinese
FC128 unsigned 16 bits Command Status
5 None None
FC129 unsigned 16 bits Relay Status
FC130 unsigned 16 bits LED Flash
FC131 unsigned 16 bits Comm Fail Mode
1 Serial Serial
2 Serial & Ethernet Serial & Ethernet
4 Serial & FieldBus Serial & FieldBus
8 Ethernet Ethernet
16 FieldBus FieldBus

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-105


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


32 Ethernet&Fieldbus Ethernet & Fieldbus
64 All All
FC133 unsigned 16 bits Cause of Waveform Trigger
0 None None
1 Command Command
0x00C0 VO 1 Virtual Output 1
0x00C1 VO 2 Virtual Output 2
0x00C2 VO 3 Virtual Output 3
0x00C3 VO 4 Virtual Output 4
0x00C4 VO 5 Virtual Output 5
0x00C5 VO 6 Virtual Output 6
0x00C6 VO 7 Virtual Output 7
0x00C7 VO 8 Virtual Output 8
0x00C8 VO 9 Virtual Output 9
0x00C9 VO 10 Virtual Output 10
0x00CA VO 11 Virtual Output 11
0x00CB VO 12 Virtual Output 12
0x00CC VO 13 Virtual Output 13
0x00CD VO 14 Virtual Output 14
0x00CE VO 15 Virtual Output 15
0x00CF VO 16 Virtual Output 16
0x00D0 VO 17 Virtual Output 17
0x00D1 VO 18 Virtual Output 18
0x00D2 VO 19 Virtual Output 19
0x00D3 VO 20 Virtual Output 20
0x00D4 VO 21 Virtual Output 21
0x00D5 VO 22 Virtual Output 22
0x00D6 VO 23 Virtual Output 23
0x00D7 VO 24 Virtual Output 24
0x00D8 VO 25 Virtual Output 25
0x00D9 VO 26 Virtual Output 26
0x00DA VO 27 Virtual Output 27
0x00DB VO 28 Virtual Output 28
0x00DC VO 29 Virtual Output 29
0x00DD VO 30 Virtual Output 30
0x00DE VO 31 Virtual Output 31
0x00DF VO 32 Virtual Output 32
0x8001 Any Trip PickUp Any Trip PickUp
0x8002 Any Trip Any Trip
0x8004 Any Trip DropOut Any Trip DropOut
0xA001 Any Alarm PickUp Any Alarm PickUp
0xA002 Any Alarm Any Alarm
0xA004 Any Alarm DropOut Any Alarm DropOut
0xC002 Any Inhibit Any Inhibit
0xD000 Input 1 Input 1
0xD001 Input 2 Input 2
0xD002 Input 3 Input 3

12-106 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


FC133A unsigned 16 bits Data Log Trigger
0 None None
1 Command Command
0x00C0 VO 1 Virtual Output 1
0x00C1 VO 2 Virtual Output 2
0x00C2 VO 3 Virtual Output 3
0x00C3 VO 4 Virtual Output 4
0x00C4 VO 5 Virtual Output 5
0x00C5 VO 6 Virtual Output 6
0x00C6 VO 7 Virtual Output 7
0x00C7 VO 8 Virtual Output 8
0x00C8 VO 9 Virtual Output 9
0x00C9 VO 10 Virtual Output 10
0x00CA VO 11 Virtual Output 11
0x00CB VO 12 Virtual Output 12
0x00CC VO 13 Virtual Output 13
0x00CD VO 14 Virtual Output 14
0x00CE VO 15 Virtual Output 15
0x00CF VO 16 Virtual Output 16
0x00D0 VO 17 Virtual Output 17
0x00D1 VO 18 Virtual Output 18
0x00D2 VO 19 Virtual Output 19
0x00D3 VO 20 Virtual Output 20
0x00D4 VO 21 Virtual Output 21
0x00D5 VO 22 Virtual Output 22
0x00D6 VO 23 Virtual Output 23
0x00D7 VO 24 Virtual Output 24
0x00D8 VO 25 Virtual Output 25
0x00D9 VO 26 Virtual Output 26
0x00DA VO 27 Virtual Output 27
0x00DB VO 28 Virtual Output 28
0x00DC VO 29 Virtual Output 29
0x00DD VO 30 Virtual Output 30
0x00DE VO 31 Virtual Output 31
0x00DF VO 32 Virtual Output 32
0x8001 Any Trip PickUp Any Trip PickUp
0x8002 Any Trip Any Trip
0x8004 Any Trip DropOut Any Trip DropOut
0xA001 Any Alarm PickUp Any Alarm PickUp
0xA002 Any Alarm Any Alarm
0xA004 Any Alarm DropOut Any Alarm DropOut
0xC002 Any Inhibit Any Inhibit
FC134 unsigned 16 bits Cause of Event
0 No Evnt/Trp ToDate No Event/Trip To Date
1 Ctrl. Pwr Lost Control Power Lost
2 Ctrl. Pwr Applied Control Power Applied
3 Date or Time Set Date or Time Set

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-107


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


4 Reset Reset
5 Lockout Rst Closed Lockout Reset Closed
6 Factory Reload Factory Reload
7 Clock Not Set Clock Not Set
8 IRIG-B Failure IRIG-B Failure
9 Reset Trip Counter Reset Trip Counter
10 BKR Status Unknown Breaker Status Unknown
11 Clear Event Rec Clear Event Records
12 Clear Transt Rec Clear Transient Records
13 Clear Therm Cap Clear Thermal Capacity
14 Comm. Alert 1 Comm. Alert 1
15 Comm. Alert 2 Comm. Alert 2
16 Comm. Alert 3 Comm. Alert 3
17 Ethernet Link Fail Ethernet Link Failure
18 High ENET Traffic High Ethernet Traffic
19 Intern Temp. >80C Internal Temperature High
22 Emergency Restart Emergency Restart
23 Trace Mem. Trigger Trace Mem. Trigger
24 Rx Goose 1 ON Rx Goose 1 ON
25 Rx Goose 1 OFF Rx Goose 1 OFF
26 Rx Goose 2 ON Rx Goose 2 ON
27 Rx Goose 2 OFF Rx Goose 2 OFF
28 Rx Goose 3 ON Rx Goose 3 ON
29 Rx Goose 3 OFF Rx Goose 3 OFF
30 Rx Goose 4 ON Rx Goose 4 ON
31 Rx Goose 4 OFF Rx Goose 4 OFF
32 Rx Goose 5 ON Rx Goose 5 ON
33 Rx Goose 5 OFF Rx Goose 5 OFF
34 Rx Goose 6 ON Rx Goose 6 ON
35 Rx Goose 6 OFF Rx Goose 6 OFF
36 Rx Goose 7 ON Rx Goose 7 ON
37 Rx Goose 7 OFF Rx Goose 7 OFF
38 Rx Goose 8 ON Rx Goose 8 ON
39 Rx Goose 8 OFF Rx Goose 8 OFF
40 Eth Link A Fail Ethernet Link A Fail
41 Eth Link B Fail Ethernet Link B Fail
0x0040 Contact IN 1 On Contact Input 1 On
0x0041 Contact IN 2 On Contact Input 2 On
0x0042 Contact IN 3 On Contact Input 3 On
0x0043 Contact IN 4 On Contact Input 4 On
0x0044 Contact IN 5 On Contact Input 5 On
0x0045 Contact IN 6 On Contact Input 6 On
0x0046 Contact IN 7 On Contact Input 7 On
0x0047 Contact IN 8 On Contact Input 8 On
0x0048 Contact IN 9 On Contact Input 9 On
0x0049 Contact IN 10 On Contact Input 10 On
0x0060 Contact IN 1 Off Contact Input 1 Off

12-108 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x0061 Contact IN 2 Off Contact Input 2 Off
0x0062 Contact IN 3 Off Contact Input 3 Off
0x0063 Contact IN 4 Off Contact Input 4 Off
0x0064 Contact IN 5 Off Contact Input 5 Off
0x0065 Contact IN 6 Off Contact Input 6 Off
0x0066 Contact IN 7 Off Contact Input 7 Off
0x0067 Contact IN 8 Off Contact Input 8 Off
0x0068 Contact IN 9 Off Contact Input 9 Off
0x0069 Contact IN 10 Off Contact Input 10 Off
0x0080 Virtual IN 1 On Virtual Input 1 On
0x0081 Virtual IN 2 On Virtual Input 2 On
0x0082 Virtual IN 3 On Virtual Input 3 On
0x0083 Virtual IN 4 On Virtual Input 4 On
0x0084 Virtual IN 5 On Virtual Input 5 On
0x0085 Virtual IN 6 On Virtual Input 6 On
0x0086 Virtual IN 7 On Virtual Input 7 On
0x0087 Virtual IN 8 On Virtual Input 8 On
0x0088 Virtual IN 9 On Virtual Input 9 On
0x0089 Virtual IN 10 On Virtual Input 10 On
0x008A Virtual IN 11 On Virtual Input 11 On
0x008B Virtual IN 12 On Virtual Input 12 On
0x008C Virtual IN 13 On Virtual Input 13 On
0x008D Virtual IN 14 On Virtual Input 14 On
0x008E Virtual IN 15 On Virtual Input 15 On
0x008F Virtual IN 16 On Virtual Input 16 On
0x0090 Virtual IN 17 On Virtual Input 17 On
0x0091 Virtual IN 18 On Virtual Input 18 On
0x0092 Virtual IN 19 On Virtual Input 19 On
0x0093 Virtual IN 20 On Virtual Input 20 On
0x0094 Virtual IN 21 On Virtual Input 21 On
0x0095 Virtual IN 22 On Virtual Input 22 On
0x0096 Virtual IN 23 On Virtual Input 23 On
0x0097 Virtual IN 24 On Virtual Input 24 On
0x0098 Virtual IN 25 On Virtual Input 25 On
0x0099 Virtual IN 26 On Virtual Input 26 On
0x009A Virtual IN 27 On Virtual Input 27 On
0x009B Virtual IN 28 On Virtual Input 28 On
0x009C Virtual IN 29 On Virtual Input 29 On
0x009D Virtual IN 30 On Virtual Input 30 On
0x009E Virtual IN 31 On Virtual Input 31 On
0x009F Virtual IN 32 On Virtual Input 32 On
0x00A0 Virtual IN 1 Off Virtual Input 1 Off
0x00A1 Virtual IN 2 Off Virtual Input 2 Off
0x00A2 Virtual IN 3 Off Virtual Input 3 Off
0x00A3 Virtual IN 4 Off Virtual Input 4 Off
0x00A4 Virtual IN 5 Off Virtual Input 5 Off
0x00A5 Virtual IN 6 Off Virtual Input 6 Off

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-109


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x00A6 Virtual IN 7 Off Virtual Input 7 Off
0x00A7 Virtual IN 8 Off Virtual Input 8 Off
0x00A8 Virtual IN 9 Off Virtual Input 9 Off
0x00A9 Virtual IN 10 Off Virtual Input 10 Off
0x00AA Virtual IN 11 Off Virtual Input 11 Off
0x00AB Virtual IN 12 Off Virtual Input 12 Off
0x00AC Virtual IN 13 Off Virtual Input 13 Off
0x00AD Virtual IN 14 Off Virtual Input 14 Off
0x00AE Virtual IN 15 Off Virtual Input 15 Off
0x00AF Virtual IN 16 Off Virtual Input 16 Off
0x00B0 Virtual IN 17 Off Virtual Input 17 Off
0x00B1 Virtual IN 18 Off Virtual Input 18 Off
0x00B2 Virtual IN 19 Off Virtual Input 19 Off
0x00B3 Virtual IN 20 Off Virtual Input 20 Off
0x00B4 Virtual IN 21 Off Virtual Input 21 Off
0x00B5 Virtual IN 22 Off Virtual Input 22 Off
0x00B6 Virtual IN 23 Off Virtual Input 23 Off
0x00B7 Virtual IN 24 Off Virtual Input 24 Off
0x00B8 Virtual IN 25 Off Virtual Input 25 Off
0x00B9 Virtual IN 26 Off Virtual Input 26 Off
0x00BA Virtual IN 27 Off Virtual Input 27 Off
0x00BB Virtual IN 28 Off Virtual Input 28 Off
0x00BC Virtual IN 29 Off Virtual Input 29 Off
0x00BD Virtual IN 30 Off Virtual Input 30 Off
0x00BE Virtual IN 31 Off Virtual Input 31 Off
0x00BF Virtual IN 32 Off Virtual Input 32 Off
0x01C0 Remote IN 1 On Remote Input 1 On
0x01C1 Remote IN 2 On Remote Input 2 On
0x01C2 Remote IN 3 On Remote Input 3 On
0x01C3 Remote IN 4 On Remote Input 4 On
0x01C4 Remote IN 5 On Remote Input 5 On
0x01C5 Remote IN 6 On Remote Input 6 On
0x01C6 Remote IN 7 On Remote Input 7 On
0x01C7 Remote IN 8 On Remote Input 8 On
0x01C8 Remote IN 9 On Remote Input 9 On
0x01C9 Remote IN 10 On Remote Input 10 On
0x01CA Remote IN 11 On Remote Input 11 On
0x01CB Remote IN 12 On Remote Input 12 On
0x01CC Remote IN 13 On Remote Input 13 On
0x01CD Remote IN 14 On Remote Input 14 On
0x01CE Remote IN 15 On Remote Input 15 On
0x01CF Remote IN 16 On Remote Input 16 On
0x01D0 Remote IN 17 On Remote Input 17 On
0x01D1 Remote IN 18 On Remote Input 18 On
0x01D2 Remote IN 19 On Remote Input 19 On
0x01D3 Remote IN 20 On Remote Input 20 On
0x01D4 Remote IN 21 On Remote Input 21 On

12-110 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x01D5 Remote IN 22 On Remote Input 22 On
0x01D6 Remote IN 23 On Remote Input 23 On
0x01D7 Remote IN 24 On Remote Input 24 On
0x01D8 Remote IN 25 On Remote Input 25 On
0x01D9 Remote IN 26 On Remote Input 26 On
0x01DA Remote IN 27 On Remote Input 27 On
0x01DB Remote IN 28 On Remote Input 28 On
0x01DC Remote IN 29 On Remote Input 29 On
0x01DD Remote IN 30 On Remote Input 30 On
0x01DE Remote IN 31 On Remote Input 31 On
0x01DF Remote IN 32 On Remote Input 32 On
0x01E0 Remote IN 1 Off Remote Input 1 Off
0x01E1 Remote IN 2 Off Remote Input 2 Off
0x01E2 Remote IN 3 Off Remote Input 3 Off
0x01E3 Remote IN 4 Off Remote Input 4 Off
0x01E4 Remote IN 5 Off Remote Input 5 Off
0x01E5 Remote IN 6 Off Remote Input 6 Off
0x01E6 Remote IN 7 Off Remote Input 7 Off
0x01E7 Remote IN 8 Off Remote Input 8 Off
0x01E8 Remote IN 9 Off Remote Input 9 Off
0x01E9 Remote IN 10 Off Remote Input 10 Off
0x01EA Remote IN 11 Off Remote Input 11 Off
0x01EB Remote IN 12 Off Remote Input 12 Off
0x01EC Remote IN 13 Off Remote Input 13 Off
0x01ED Remote IN 14 Off Remote Input 14 Off
0x01EE Remote IN 15 Off Remote Input 15 Off
0x01EF Remote IN 16 Off Remote Input 16 Off
0x01F0 Remote IN 17 Off Remote Input 17 Off
0x01F1 Remote IN 18 Off Remote Input 18 Off
0x01F2 Remote IN 19 Off Remote Input 19 Off
0x01F3 Remote IN 20 Off Remote Input 20 Off
0x01F4 Remote IN 21 Off Remote Input 21 Off
0x01F5 Remote IN 22 Off Remote Input 22 Off
0x01F6 Remote IN 23 Off Remote Input 23 Off
0x01F7 Remote IN 24 Off Remote Input 24 Off
0x01F8 Remote IN 25 Off Remote Input 25 Off
0x01F9 Remote IN 26 Off Remote Input 26 Off
0x01FA Remote IN 27 Off Remote Input 27 Off
0x01FB Remote IN 28 Off Remote Input 28 Off
0x01FC Remote IN 29 Off Remote Input 29 Off
0x01FD Remote IN 30 Off Remote Input 30 Off
0x01FE Remote IN 31 Off Remote Input 31 Off
0x01FF Remote IN 32 Off Remote Input 32 Off
0x0200 Contact OUT 1 On Contact Output 1 On
0x0201 Contact OUT 2 On Contact Output 2 On
0x0202 Contact OUT 3 On Contact Output 3 On
0x0203 Contact OUT 4 On Contact Output 4 On

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-111


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x0204 Contact OUT 5 On Contact Output 5 On
0x0205 Contact OUT 6 On Contact Output 6 On
0x0206 Contact OUT 7 On Contact Output 7 On
0x0220 Contact OUT 1 Off Contact Output 1 Off
0x0221 Contact OUT 2 Off Contact Output 2 Off
0x0222 Contact OUT 3 Off Contact Output 3 Off
0x0223 Contact OUT 4 Off Contact Output 4 Off
0x0224 Contact OUT 5 Off Contact Output 5 Off
0x0225 Contact OUT 6 Off Contact Output 6 Off
0x0226 Contact OUT 7 Off Contact Output 7 Off
0x0240 Remote OUT 1 On Remote Output 1 On
0x0241 Remote OUT 2 On Remote Output 2 On
0x0242 Remote OUT 3 On Remote Output 3 On
0x0243 Remote OUT 4 On Remote Output 4 On
0x0244 Remote OUT 5 On Remote Output 5 On
0x0245 Remote OUT 6 On Remote Output 6 On
0x0246 Remote OUT 7 On Remote Output 7 On
0x0247 Remote OUT 8 On Remote Output 8 On
0x0248 Remote OUT 9 On Remote Output 9 On
0x0249 Remote OUT 10 On Remote Output 10 On
0x024A Remote OUT 11 On Remote Output 11 On
0x024B Remote OUT 12 On Remote Output 12 On
0x024C Remote OUT 13 On Remote Output 13 On
0x024D Remote OUT 14 On Remote Output 14 On
0x024E Remote OUT 15 On Remote Output 15 On
0x024F Remote OUT 16 On Remote Output 16 On
0x0250 Remote OUT 17 On Remote Output 17 On
0x0251 Remote OUT 18 On Remote Output 18 On
0x0252 Remote OUT 19 On Remote Output 19 On
0x0253 Remote OUT 20 On Remote Output 20 On
0x0254 Remote OUT 21 On Remote Output 21 On
0x0255 Remote OUT 22 On Remote Output 22 On
0x0256 Remote OUT 23 On Remote Output 23 On
0x0257 Remote OUT 24 On Remote Output 24 On
0x0258 Remote OUT 25 On Remote Output 25 On
0x0259 Remote OUT 26 On Remote Output 26 On
0x025A Remote OUT 27 On Remote Output 27 On
0x025B Remote OUT 28 On Remote Output 28 On
0x025C Remote OUT 29 On Remote Output 29 On
0x025D Remote OUT 30 On Remote Output 30 On
0x025E Remote OUT 31 On Remote Output 31 On
0x025F Remote OUT 32 On Remote Output 32 On
0x0260 Remote OUT 1 Off Remote Output 1 Off
0x0261 Remote OUT 2 Off Remote Output 2 Off
0x0262 Remote OUT 3 Off Remote Output 3 Off
0x0263 Remote OUT 4 Off Remote Output 4 Off
0x0264 Remote OUT 5 Off Remote Output 5 Off

12-112 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x0265 Remote OUT 6 Off Remote Output 6 Off
0x0266 Remote OUT 7 Off Remote Output 7 Off
0x0267 Remote OUT 8 Off Remote Output 8 Off
0x0268 Remote OUT 9 Off Remote Output 9 Off
0x0269 Remote OUT 10 Off Remote Output 10 Off
0x026A Remote OUT 11 Off Remote Output 11 Off
0x026B Remote OUT 12 Off Remote Output 12 Off
0x026C Remote OUT 13 Off Remote Output 13 Off
0x026D Remote OUT 14 Off Remote Output 14 Off
0x026E Remote OUT 15 Off Remote Output 15 Off
0x026F Remote OUT 16 Off Remote Output 16 Off
0x0270 Remote OUT 17 Off Remote Output 17 Off
0x0271 Remote OUT 18 Off Remote Output 18 Off
0x0272 Remote OUT 19 Off Remote Output 19 Off
0x0273 Remote OUT 20 Off Remote Output 20 Off
0x0274 Remote OUT 21 Off Remote Output 21 Off
0x0275 Remote OUT 22 Off Remote Output 22 Off
0x0276 Remote OUT 23 Off Remote Output 23 Off
0x0277 Remote OUT 24 Off Remote Output 24 Off
0x0278 Remote OUT 25 Off Remote Output 25 Off
0x0279 Remote OUT 26 Off Remote Output 26 Off
0x027A Remote OUT 27 Off Remote Output 27 Off
0x027B Remote OUT 28 Off Remote Output 28 Off
0x027C Remote OUT 29 Off Remote Output 29 Off
0x027D Remote OUT 30 Off Remote Output 30 Off
0x027E Remote OUT 31 Off Remote Output 31 Off
0x027F Remote OUT 32 Off Remote Output 32 Off
0x8002 Any Trip Any Trip
0x8042 Therm O/L Trip OP Thermal Overload Trip OP
0x8044 Therm O/L Trip DPO Thermal Overload Trip DPO
0x804A Therm PhA Trip OP Thermal Phase A Trip OP
0x804C Therm PhA Trip DPO Thermal Phase A Trip DPO
0x8052 Therm PhB Trip OP Thermal Phase B Trip OP
0x8054 Therm PhB Trip DPO Thermal Phase B Trip DPO
0x8062 Therm PhC Trip OP Thermal Phase C Trip OP
0x8064 Therm PhC Trip DPO Thermal Phase C Trip DPO
0x8081 PosSeq UV1 Trp PKP Positive Sequence UV 1 Trp PKP
0x8082 PosSeq UV1 Trip OP Positive Sequence UV 1 Trip OP
0x8084 PosSeq UV1 Trp DPO Positive Sequence UV 1 Trp DPO
0x8242 Arc Flash Trip OP Arc Flash Trip OP
0x83C1 Volt Hz Trip PKP Volt Hz Trip PKP
0x83C2 Volt Hz Trip OP Volt Hz Trip OP
0x83C4 Volt Hz Trip DPO Volt Hz Trip DPO
0x84C1 LE 1 Trip PKP Logic Element 1 Trip PKP
0x84C2 LE 1 Trip OP Logic Element 1 Trip OP
0x84C4 LE 1 Trip DPO Logic Element 1 Trip DPO
0x8501 LE 2 Trip PKP Logic Element 2 Trip PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-113


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x8502 LE 2 Trip OP Logic Element 2 Trip OP
0x8504 LE 2 Trip DPO Logic Element 2 Trip DPO
0x8541 LE 3 Trip PKP Logic Element 3 Trip PKP
0x8542 LE 3 Trip OP Logic Element 3 Trip OP
0x8544 LE 3 Trip DPO Logic Element 3 Trip DPO
0x8581 LE 4 Trip PKP Logic Element 4 Trip PKP
0x8582 LE 4 Trip OP Logic Element 4 Trip OP
0x8584 LE 4 Trip DPO Logic Element 4 Trip DPO
0x85C1 LE 5 Trip PKP Logic Element 5 Trip PKP
0x85C2 LE 5 Trip OP Logic Element 5 Trip OP
0x85C4 LE 5 Trip DPO Logic Element 5 Trip DPO
0x8601 LE 6 Trip PKP Logic Element 6 Trip PKP
0x8602 LE 6 Trip OP Logic Element 6 Trip OP
0x8604 LE 6 Trip DPO Logic Element 6 Trip DPO
0x8641 LE 7 Trip PKP Logic Element 7 Trip PKP
0x8642 LE 7 Trip OP Logic Element 7 Trip OP
0x8644 LE 7 Trip DPO Logic Element 7 Trip DPO
0x8681 LE 8 Trip PKP Logic Element 8 Trip PKP
0x8682 LE 8 Trip OP Logic Element 8 Trip OP
0x8684 LE 8 Trip DPO Logic Element 8 Trip DPO
0x89C2 Self Test OP Self Test OP
0x89C4 Self Test DPO Self Test Trip DPO
0x8E81 Dir Pwr 1 Trip PKP Directional Pwr 1 Trip PKP
0x8E82 Dir Pwr 1 Trip OP Directional Pwr 1 Trip OP
0x8EC1 Dir Pwr 2 Trip PKP Directional Pwr 2 Trip PKP
0x8EC2 Dir Pwr 2 Trip OP Directional Pwr 2 Trip OP
0x8F81 Fuse Fail Trip PKP Fuse Fail Trip PKP
0x8F82 Fuse Fail Trip OP Fuse Fail Trip OP
0x8F84 Fuse Fail Trip DPO Fuse Fail Trip DPO
0x8FC1 Brkn Cond Trip PKP Broken Cond Trip PKP
0x8FC2 Brkn Cond Trip OP Broken Cond Trip OP
0x8FC4 Brkn Cond Trip DPO Broken Cond Trip DPO
0x9001 Ph IOC1 Trip PKP Phase IOC 1 Trip PKP
0x9002 Ph IOC1 Trip OP Phase IOC 1 Trip OP
0x9004 Ph IOC1 Trip DPO Phase IOC 1 Trip DPO
0x9009 Ph A IOC1 Trip PKP Phase A IOC 1 Trip PKP
0x900A Ph A IOC1 Trip OP Phase A IOC 1 Trip OP
0x900C Ph A IOC1 Trip DPO Phase A IOC 1 Trip DPO
0x9011 Ph B IOC1 Trip PKP Phase B IOC 1 Trip PKP
0x9012 Ph B IOC1 Trip OP Phase B IOC 1 Trip OP
0x9014 Ph B IOC1 Trip DPO Phase B IOC 1 Trip DPO
0x9021 Ph C IOC1 Trip PKP Phase C IOC 1 Trip PKP
0x9022 Ph C IOC1 Trip OP Phase C IOC 1 Trip OP
0x9024 Ph C IOC1 Trip DPO Phase C IOC 1 Trip DPO
0x9041 Ntrl IOC1 Trip PKP Neutral IOC 1 Trip PKP
0x9042 Ntrl IOC1 Trip OP Neutral IOC 1 Trip OP
0x9044 Ntrl IOC1 Trip DPO Neutral IOC 1 Trip DPO

12-114 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x9081 Gnd IOC1 Trip PKP Ground IOC 1 Trip PKP
0x9082 Gnd IOC1 Trip OP Ground IOC 1 Trip OP
0x9084 Gnd IOC1 Trip DPO Ground IOC 1 Trip DPO
0x90C1 Ph TOC1 Trip PKP Phase TOC 1 Trip PKP
0x90C2 Ph TOC1 Trip OP Phase TOC 1 Trip OP
0x90C4 Ph TOC1 Trip DPO Phase TOC 1 Trip DPO
0x90C9 Ph A TOC1 Trip PKP Phase A TOC 1 Trip PKP
0x90CA Ph A TOC1 Trip OP Phase A TOC 1 Trip OP
0x90CC Ph A TOC1 Trip DPO Phase A TOC 1 Trip DPO
0x90D1 Ph B TOC1 Trip PKP Phase B TOC 1 Trip PKP
0x90D2 Ph B TOC1 Trip OP Phase B TOC 1 Trip OP
0x90D4 Ph B TOC1 Trip DPO Phase B TOC 1 Trip DPO
0x90E1 Ph C TOC1 Trip PKP Phase C TOC 1 Trip PKP
0x90E2 Ph C TOC1 Trip OP Phase C TOC 1 Trip OP
0x90E4 Ph C TOC1 Trip DPO Phase C TOC 1 Trip DPO
0x9101 Ntrl TOC1 Trip PKP Neutral TOC 1 Trip PKP
0x9102 Ntrl TOC1 Trip OP Neutral TOC 1 Trip OP
0x9104 Ntrl TOC1 Trip DPO Neutral TOC 1 Trip DPO
0x9141 Gnd TOC1 Trip PKP Ground TOC Trip PKP
0x9142 Gnd TOC1 Trip OP Ground TOC 1 Trip OP
0x9144 Gnd TOC1 Trip DPO Ground TOC Trip DPO
0x9181 Ph IOC2 Trip PKP Phase IOC 2 Trip PKP
0x9182 Ph IOC2 Trip OP Phase IOC 2 Trip OP
0x9184 Ph IOC2 Trip DPO Phase IOC 2 Trip DPO
0x9189 Ph A IOC2 Trip PKP Phase A IOC 2 Trip PKP
0x918A Ph A IOC2 Trip OP Phase A IOC 2 Trip OP
0x918C Ph A IOC2 Trip DPO Phase A IOC 2 Trip DPO
0x9191 Ph B IOC2 Trip PKP Phase B IOC 2 Trip PKP
0x9192 Ph B IOC2 Trip OP Phase B IOC 2 Trip OP
0x9194 Ph B IOC2 Trip DPO Phase B IOC 2 Trip DPO
0x91A1 Ph C IOC2 Trip PKP Phase C IOC 2 Trip PKP
0x91A2 Ph C IOC2 Trip OP Phase C IOC 2 Trip OP
0x91A4 Ph C IOC2 Trip DPO Phase C IOC 2 Trip DPO
0x91C1 Ntrl IOC2 Trip PKP Neutral IOC 2 Trip PKP
0x91C2 Ntrl IOC2 Trip OP Neutral IOC 2 Trip OP
0x91C4 Ntrl IOC2 Trip DPO Neutral IOC 2 Trip DPO
0x9201 Gnd IOC2 Trip PKP Ground IOC 2 Trip PKP
0x9202 Gnd IOC2 Trip OP Ground IOC 2 Trip OP
0x9204 Gnd IOC2 Trip DPO Ground IOC 2 Trip DPO
0x9301 SGnd TOC1 Trip PKP Sensitive Ground TOC 1 Trip PKP
0x9302 SGnd TOC1 Trip OP Sensitive Ground TOC 1 Trip OP
0x9304 SGnd TOC1 Trip DPO Sensitive Ground TOC 1 Trip DPO
0x93C1 NSeq OV Trp PKP Negative Sequence OV Trip PKP
0x93C2 NSeq OV Trp OP Negative Sequence OV Trip OP
0x93C4 NSeq OV Trp DPO Negative Sequence OV Trip DPO
0x9401 Ntrl OV Trip PKP Neutral OV Trip PKP
0x9402 Ntrl OV Trp OP Neutral OV Trip OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-115


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x9404 Ntrl OV Trip DPO Neutral OV Trip DPO
0x9441 Ph OV1 Trip PKP Phase OV1 Trip PKP
0x9442 Ph OV1 Trip OP Phase OV 1 Trip OP
0x9444 Ph OV1 Trip DPO Phase OV1 Trip DPO
0x9449 Ph A OV1 Trip PKP Phase A OV1 Trip PKP
0x944A Ph A OV1 Trip OP Phase A OV1 Trip OP
0x944C Ph A OV1 Trip DPO Phase A OV1 Trip DPO
0x9451 Ph B OV1 Trip PKP Phase B OV1 Trip PKP
0x9452 Ph B OV1 Trip OP Phase B OV1 Trip OP
0x9454 Ph B OV1 Trip DPO Phase B OV1 Trip DPO
0x9461 Ph C OV1 Trip PKP Phase C OV1 Trip PKP
0x9462 Ph C OV1 Trip OP Phase C OV1 Trip OP
0x9464 Ph C OV1 Trip DPO Phase C OV1 Trip DPO
0x9481 Ph UV1 Trip PKP Phase UV1 Trip PKP
0x9482 Ph UV1 Trip OP Phase UV 1 Trip OP
0x9484 Ph UV1 Trip DPO Phase UV1 Trip DPO
0x9489 Ph A UV1 Trip PKP Phase A UV1 Trip PKP
0x948A Ph A UV1 Trip OP Phase A UV1 Trip OP
0x948C Ph A UV1 Trip DPO Phase A UV1 Trip DPO
0x9491 Ph B UV1 Trip PKP Phase B UV1 Trip PKP
0x9492 Ph B UV1 Trip OP Phase B UV1 Trip OP
0x9494 Ph B UV1 Trip DPO Phase B UV1 Trip DPO
0x94A1 Ph C UV1 Trip PKP Phase C UV1 Trip PKP
0x94A2 Ph C UV1 Trip OP Phase C UV1 Trip OP
0x94A4 Ph C UV1 Trip DPO Phase C UV1 Trip DPO
0x94C1 Aux OV Trip PKP Auxiliary OV Trip PKP
0x94C2 Aux OV Trip OP Auxiliary OV Trip OP
0x94C4 Aux OV Trip DPO Auxiliary OV Trip DPO
0x9501 Aux UV Trip PKP Auxiliary UV Trip PKP
0x9502 Aux UV Trip OP Auxiliary UV Trip OP
0x9504 Aux UV Trip DPO Auxiliary UV Trip DPO
0x9541 UndrFreq1 Trip PKP Underfrequency 1 Trip PKP
0x9542 UndrFreq1 Trip OP Underfrequency 1 Trip OP
0x9544 UndrFreq1 Trip DPO Underfrequency 1 Trip DPO
0x9581 UndrFreq2 Trip PKP Underfrequency 2 Trip PKP
0x9582 UndrFreq2 Trip OP Underfrequency 2 Trip OP
0x9584 UndrFreq2 Trip DPO Underfrequency 2 Trip DPO
0x95C1 OverFreq1 Trip PKP Overfrequency 1 Trip PKP
0x95C2 OverFreq1 Trip OP Overfrequency 1 Trip OP
0x95C4 OverFreq1 Trip DPO Overfrequency 1 Trip DPO
0x9601 OverFreq2 Trip PKP Overfrequency 2 Trip PKP
0x9602 OverFreq2 Trip OP Overfrequency 2 Trip OP
0x9604 OverFreq2 Trip DPO Overfrequency 2 Trip DPO
0x9641 SGnd IOC1 Trip PKP Sensitive Ground IOC 1 Trip PKP
0x9642 SGnd IOC1 Trip OP Sensitive Ground IOC 1 Trip OP
0x9644 SGnd IOC1 Trip DPO Sensitive Ground IOC 1 Trip DPO
0x9681 SGnd IOC2 Trip PKP Sensitive Ground IOC 2 Trip PKP

12-116 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x9682 SGnd IOC2 Trip OP Sensitive Ground IOC 2 Trip OP
0x9684 SGnd IOC2 Trip DPO Sensitive Ground IOC 2 Trip DPO
0x96C1 NSeq IOC Trp PKP Negative Sequence IOC Trip PKP
0x96C2 NSeq IOC Trp OP Negative Sequence IOC Trip OP
0x96C4 NSeq IOC Trp DPO Negative Sequence IOC Trip DPO
0x9701 Ph UV2 Trip PKP Phase UV 2 Trip PKP
0x9702 Ph UV2 Trip OP Phase UV 2 Trip OP
0x9704 Ph UV2 Trip DPO Phase UV 2 Trip DPO
0x9709 Ph A UV2 Trip PKP Phase A UV 2 Trip PKP
0x970A Ph A UV2 Trip OP Phase A UV 2 Trip OP
0x970C Ph A UV2 Trip DPO Phase A UV 2 Trip DPO
0x9711 Ph B UV2 Trip PKP Phase B UV 2 Trip PKP
0x9712 Ph B UV2 Trip OP Phase B UV 2 Trip OP
0x9714 Ph B UV2 Trip DPO Phase B UV 2 Trip DPO
0x9721 Ph C UV2 Trip PKP Phase C UV 2 Trip PKP
0x9722 Ph C UV2 Trip OP Phase C UV 2 Trip OP
0x9724 Ph C UV2 Trip DPO Phase C UV 2 Trip DPO
0x9741 Ph UV3 Trip PKP Phase UV 3 Trip PKP
0x9742 Ph UV3 Trip OP Phase UV 3 Trip OP
0x9744 Ph UV3 Trip DPO Phase UV 3 Trip DPO
0x9749 Ph A UV3 Trip PKP Phase A UV 3 Trip PKP
0x974A Ph A UV3 Trip OP Phase A UV 3 Trip OP
0x974C Ph A UV3 Trip DPO Phase A UV 3 Trip DPO
0x9751 Ph B UV3 Trip PKP Phase B UV 3 Trip PKP
0x9752 Ph B UV3 Trip OP Phase B UV 3 Trip OP
0x9754 Ph B UV3 Trip DPO Phase B UV 3 Trip DPO
0x9761 Ph C UV3 Trip PKP Phase C UV 3 Trip PKP
0x9762 Ph C UV3 Trip OP Phase C UV 3 Trip OP
0x9764 Ph C UV3 Trip DPO Phase C UV 3 Trip DPO
0x9781 Ph UV4 Trip PKP Phase UV 4 Trip PKP
0x9782 Ph UV4 Trip OP Phase UV 4 Trip OP
0x9784 Ph UV4 Trip DPO Phase UV 4 Trip DPO
0x9789 Ph A UV4 Trip PKP Phase A UV 4 Trip PKP
0x978A Ph A UV4 Trip OP Phase A UV 4 Trip OP
0x978C Ph A UV4 Trip DPO Phase A UV 4 Trip DPO
0x9791 Ph B UV4 Trip PKP Phase B UV 4 Trip PKP
0x9792 Ph B UV4 Trip OP Phase B UV 4 Trip OP
0x9794 Ph B UV4 Trip DPO Phase B UV 4 Trip DPO
0x97A1 Ph C UV4 Trip PKP Phase C UV 4 Trip PKP
0x97A2 Ph C UV4 Trip OP Phase C UV 4 Trip OP
0x97A4 Ph C UV4 Trip DPO Phase C UV 4 Trip DPO
0x97C1 NSeq OV2 Trp PKP Negative Sequence OV2 Trp PKP
0x97C2 NSeq OV2 Trp OP Negative Sequence OV2 Trp OP
0x97C4 NSeq OV2 Trp DPO Negative Sequence OV2 Trp DPO
0x9801 NSeq TOC1 Trip PKP Negative Sequence TOC 1 Trip PKP
0x9802 NSeq TOC1 Trip OP Negative Sequence TOC 1 Trip OP
0x9804 NSeq TOC1 Trip DPO Negative Sequence TOC 1 Trip DPO

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-117


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x98C1 Ph OV2 Trip PKP Phase OV 2 Trip PKP
0x98C2 Ph OV2 Trip OP Phase OV 2 Trip OP
0x98C4 Ph OV2 Trip DPO Phase OV 2 Trip DPO
0x98C9 Ph A OV2 Trip PKP Phase A OV2 Trip PKP
0x98CA Ph A OV2 Trip OP Phase A OV2 Trip OP
0x98CC Ph A OV2 Trip DPO Phase A OV2 Trip DPO
0x98D1 Ph B OV2 Trip PKP Phase B OV2 Trip PKP
0x98D2 Ph B OV2 Trip OP Phase B OV2 Trip OP
0x98D4 Ph B OV2 Trip DPO Phase B OV2 Trip DPO
0x98E1 Ph C OV2 Trip PKP Phase C OV2 Trip PKP
0x98E2 Ph C OV2 Trip OP Phase C OV2 Trip OP
0x98E4 Ph C OV2 Trip DPO Phase C OV2 Trip DPO
0x9901 Ph OV3 Trip PKP Phase OV 3 Trip PKP
0x9902 Ph OV3 Trip OP Phase OV 3 Trip OP
0x9904 Ph OV3 Trip DPO Phase OV 3 Trip DPO
0x9909 Ph A OV3 Trip PKP Phase A OV 3 Trip PKP
0x990A Ph A OV3 Trip OP Phase A OV 3 Trip OP
0x990C Ph A OV3 Trip DPO Phase A OV 3 Trip DPO
0x9911 Ph B OV3 Trip PKP Phase B OV 3 Trip PKP
0x9912 Ph B OV3 Trip OP Phase B OV 3 Trip OP
0x9914 Ph B OV3 Trip DPO Phase B OV 3 Trip DPO
0x9921 Ph C OV3 Trip PKP Phase C OV 3 Trip PKP
0x9922 Ph C OV3 Trip OP Phase C OV 3 Trip OP
0x9924 Ph C OV3 Trip DPO Phase C OV 3 Trip DPO
0x9941 Ph OV4 Trip PKP Phase OV 4 Trip PKP
0x9942 Ph OV4 Trip OP Phase OV 4 Trip OP
0x9944 Ph OV4 Trip DPO Phase OV 4 Trip DPO
0x9949 Ph A OV4 Trip PKP Phase A OV 4 Trip PKP
0x994A Ph A OV4 Trip OP Phase A OV 4 Trip OP
0x994C Ph A OV4 Trip DPO Phase A OV 4 Trip DPO
0x9951 Ph B OV4 Trip PKP Phase B OV 4 Trip PKP
0x9952 Ph B OV4 Trip OP Phase B OV 4 Trip OP
0x9954 Ph B OV4 Trip DPO Phase B OV 4 Trip DPO
0x9961 Ph C OV4 Trip PKP Phase C OV 4 Trip PKP
0x9962 Ph C OV4 Trip OP Phase C OV 4 Trip OP
0x9964 Ph C OV4 Trip DPO Phase C OV 4 Trip DPO
0x9981 Ntrl OV2 Trip PKP Neutral OV 2 Trip PKP
0x9982 Ntrl OV2 Trip OP Neutral OV 2 Trip OP
0x9984 Ntrl OV2 Trip DPO Neutral OV 2 Trip DPO
0x99C1 Ntrl OV3 Trip PKP Neutral OV 3 Trip PKP
0x99C2 Ntrl OV3 Trip OP Neutral OV 3 Trip OP
0x99C4 Ntrl OV3 Trip DPO Neutral OV 3 Trip DPO
0x9A01 Ntrl OV4 Trip PKP Neutral OV 4 Trip PKP
0x9A02 Ntrl OV4 Trip OP Neutral OV 4 Trip OP
0x9A04 Ntrl OV4 Trip DPO Neutral OV 4 Trip DPO
0x9A41 OverFreq3 Trip PKP Overfrequency 3 Trip PKP
0x9A42 OverFreq3 Trip OP Overfrequency 3 Trip OP

12-118 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x9A44 OverFreq3 Trip DPO Overfrequency 3 Trip DPO
0x9A81 OverFreq4 Trip PKP Overfrequency 4 Trip PKP
0x9A82 OverFreq4 Trip OP Overfrequency 4 Trip OP
0x9A84 OverFreq4 Trip DPO Overfrequency 4 Trip DPO
0x9AC1 UndFreq3 Trip PKP Underfrequency 3 Trip PKP
0x9AC2 UndFreq3 Trip OP Underfrequency 3 Trip OP
0x9AC4 UndFreq3 Trip DPO Underfrequency 3 Trip DPO
0x9B01 UndFreq4 Trip PKP Underfrequency 4 Trip PKP
0x9B02 UndFreq4 Trip OP Underfrequency 4 Trip OP
0x9B04 UndFreq4 Trip DPO Underfrequency 4 Trip DPO
0x9C01 LE 9 Trip PKP Logic Element 9 Trip PKP
0x9C02 LE 9 Trip OP Logic Element 9 Trip OP
0x9C04 LE 9 Trip DPO Logic Element 9 Trip DPO
0x9C41 LE 10 Trip PKP Logic Element 10 Trip PKP
0x9C42 LE 10 Trip OP Logic Element 10 Trip OP
0x9C44 LE 10 Trip DPO Logic Element 10 Trip DPO
0x9C81 LE 11 Trip PKP Logic Element 11 Trip PKP
0x9C82 LE 11 Trip OP Logic Element 11 Trip OP
0x9C84 LE 11 Trip DPO Logic Element 11 Trip DPO
0x9CC1 LE 12 Trip PKP Logic Element 12 Trip PKP
0x9CC2 LE 12 Trip OP Logic Element 12 Trip OP
0x9CC4 LE 12 Trip DPO Logic Element 12 Trip DPO
0x9D01 LE 13 Trip PKP Logic Element 13 Trip PKP
0x9D02 LE 13 Trip OP Logic Element 13 Trip OP
0x9D04 LE 13 Trip DPO Logic Element 13 Trip DPO
0x9D41 LE 14 Trip PKP Logic Element 14 Trip PKP
0x9D42 LE 14 Trip OP Logic Element 14 Trip OP
0x9D44 LE 14 Trip DPO Logic Element 14 Trip DPO
0x9D81 LE 15 Trip PKP Logic Element 15 Trip PKP
0x9D82 LE 15 Trip OP Logic Element 15 Trip OP
0x9D84 LE 15 Trip DPO Logic Element 15 Trip DPO
0x9DC1 LE 16 Trip PKP Logic Element 16 Trip PKP
0x9DC2 LE 16 Trip OP Logic Element 16 Trip OP
0x9DC4 LE 16 Trip DPO Logic Element 16 Trip DPO
0x9F01 WGF 1 Trip PKP Wattmetric Gnd Fault 1 Trip PKP
0x9F02 WGF 1 Trip OP Wattmetric Gnd Fault 1 Trip OP
0x9F04 WGF 1 Trip DPO Wattmetric Gnd Fault 1 Trip DPO
0x9F41 WGF 2 Trip PKP Wattmetric Gnd Fault 2 Trip PKP
0x9F42 WGF 2 Trip OP Wattmetric Gnd Fault 2 Trip OP
0x9F44 WGF 2 Trip DPO Wattmetric Gnd Fault 2 Trip DPO
0xA002 Any Alarm Any Alarm
0xA042 Therm Lvl Alrm OP Thermal Level Alarm OP
0xA044 Therm Lvl Alrm DPO Thermal Level Alarm DPO
0xA04A Therm PhA Alrm OP Thermal Phase A Alarm OP
0xA04C Therm PhA Alrm DPO Thermal Phase A Alarm DPO
0xA052 Therm PhB Alrm OP Thermal Phase B Alarm OP
0xA054 Therm PhB Alrm DPO Thermal Phase B Alarm DPO

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-119


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xA062 Therm PhC Alrm OP Thermal Phase C Alarm OP
0xA064 Therm PhC Alrm DPO Thermal Phase C Alarm DPO
0xA081 PosSeq UV1 AlrmPKP Positive Sequence UV 1 Alarm PKP
0xA082 PosSeq UV1 Alrm OP Positive Sequence UV 1 Alarm OP
0xA084 PosSeq UV1 AlrmDPO Positive Sequence UV 1 Alarm DPO
0xA242 Arc Flash Alarm OP Arc Flash Alarm OP
0xA2C2 LightSns1 Trbl Light Sensor 1 Trouble
0xA302 LightSns2 Trbl Light Sensor 2 Trouble
0xA342 LightSns3 Trbl Light Sensor 3 Trouble
0xA382 LightSns4 Trbl Light Sensor 4 Trouble
0xA3C1 Volt Hz Alarm PKP Volt Hz Alarm PKP
0xA3C2 Volt Hz Alarm OP Volt Hz Alarm OP
0xA3C4 Volt Hz Alarm DPO Volt Hz Alarm DPO
0xA442 Light Sns Trbl Light Sensor Trouble
0xA482 Relay Not Ready Relay Not Ready
0xA4C1 LE 1 Alarm PKP Logic Element 1 Alarm PKP
0xA4C2 LE 1 Alarm OP Logic Element 1 Alarm OP
0xA4C4 LE 1 Alarm DPO Logic Element 1 Alarm DPO
0xA501 LE 2 Alarm PKP Logic Element 2 Alarm PKP
0xA502 LE 2 Alarm OP Logic Element 2 Alarm OP
0xA504 LE 2 Alarm DPO Logic Element 2 Alarm DPO
0xA541 LE 3 Alarm PKP Logic Element 3 Alarm PKP
0xA542 LE 3 Alarm OP Logic Element 3 Alarm OP
0xA544 LE 3 Alarm DPO Logic Element 3 Alarm DPO
0xA581 LE 4 Alarm PKP Logic Element 4 Alarm PKP
0xA582 LE 4 Alarm OP Logic Element 4 Alarm OP
0xA584 LE 4 Alarm DPO Logic Element 4 Alarm DPO
0xA5C1 LE 5 Alarm PKP Logic Element 5 Alarm PKP
0xA5C2 LE 5 Alarm OP Logic Element 5 Alarm OP
0xA5C4 LE 5 Alarm DPO Logic Element 5 Alarm DPO
0xA601 LE 6 Alarm PKP Logic Element 6 Alarm PKP
0xA602 LE 6 Alarm OP Logic Element 6 Alarm OP
0xA604 LE 6 Alarm DPO Logic Element 6 Alarm DPO
0xA641 LE 7 Alarm PKP Logic Element 7 Alarm PKP
0xA642 LE 7 Alarm OP Logic Element 7 Alarm OP
0xA644 LE 7 Alarm DPO Logic Element 7 Alarm DPO
0xA681 LE 8 Alarm PKP Logic Element 8 Alarm PKP
0xA682 LE 8 Alarm OP Logic Element 8 Alarm OP
0xA684 LE 8 Alarm DPO Logic Element 8 Alarm DPO
0xA742 Curr Dmd1 Alrm OP Current Demand 1 Alarm OP
0xA74A C Dmd1 PhA Alrm OP Current Demand 1 PhA Alarm OP
0xA752 C Dmd1 PhB Alrm OP Current Demand 1 PhB Alarm OP
0xA762 C Dmd1 PhC Alrm OP Current Demand 1 PhC Alarm OP
0xA782 RealP Dmd Alrm OP Real Power Demand Alarm OP
0xA7C2 ReacP Dmd Alrm OP Reactive Power Demand Alarm OP
0xA802 AppP Dmd Alrm OP Apparent Power Demand Alarm OP
0xAA02 BKR Alarm Breaker Alarm

12-120 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xAA42 BKR Trip Time Breaker Trip Time
0xAA82 BKR Close Time Breaker Close Time
0xAAC2 BKR Charge Time Breaker Charge Time
0xAB02 BKR Trp/Cls Fail Breaker Trip/Close Fail
0xAB42 BKR Charge Fail Breaker Charge Fail
0xABC1 HI Amb Temp PKP High Ambient Temperature Alarm PKP
0xABC2 HI Amb Temp OP High Ambient Temperature Alarm
0xABC4 HI Amb Temp DPO High Ambient Temperature Alarm DPO
0xAC01 LO Amb Temp PKP Low Ambient Temperature Alarm PKP
0xAC02 LO Amb Temp OP Low Ambient Temperature Alarm
0xAC04 LO Amb Temp DPO Low Ambient Temperature Alarm DPO
0xAC42 Self Test Alarm OP Self Test Alarm OP
0xAC44 Self Test Alrm DPO Self Test Alarm DPO
0xACC2 BKRTrpCntrAlrm OP Breaker Trip Control Alarm OP
0xACC4 BKRTrpCntrAlrm DPO Breaker Trip Control Alarm DPO
0xAD01 R1 CoilMonAlrm PKP Trip Coil Monitor Alarm PKP
0xAD02 R1 CoilMonAlrm OP Trip Coil Monitor Alarm OP
0xAD04 R1 CoilMonAlrm DPO Trip Coil Monitor Alarm DPO
0xAD41 R2 CoilMonAlrm PKP Close Coil Monitor Alarm PKP
0xAD42 R2 CoilMonAlrm OP Close Coil Monitor Alarm OP
0xAD44 R2 CoilMonAlrm DPO Close Coil Monitor Alarm DPO
0xAD81 BKR Fail Alrm PKP Breaker Fail Alarm PKP
0xAD82 BKR Fail Alrm OP Breaker Fail Alarm OP
0xAD84 BKR Fail Alrm DPO Breaker Fail Alarm DPO
0xADC1 BKR Stat Fail PKP Breaker Status Fail PKP
0xADC2 BKR Stat Fail OP Breaker Status Fail OP
0xADC4 BKR Stat Fail DPO Breaker Status Fail DPO
0xAE41 CLP Alarm PKP Cold Load PKP Alarm PKP
0xAE42 CLP Alarm OP Cold Load PKP Alarm OP
0xAE44 CLP Alarm DPO Cold Load PKP Alarm DPO
0xAE81 Dir Pwr 1 Alrm PKP Directional Pwr 1 Alarm PKP
0xAE82 Dir Pwr 1 Alarm OP Directional Pwr 1 Alarm OP
0xAEC1 Dir Pwr 2 Alrm PKP Directional Pwr 2 Alarm PKP
0xAEC2 Dir Pwr 2 Alarm OP Directional Pwr 2 Alarm OP
0xAF01 2nd Hrmc Alarm PKP 2nd Harmonic Alarm PKP
0xAF02 2nd Hrmc Alarm OP 2nd Harmonic Alarm OP
0xAF04 2nd Hrmc Alarm DPO 2nd Harmonic Alarm DPO
0xAF81 Fuse Fail Alrm PKP Fuse Fail Alarm PKP
0xAF82 Fuse Fail Alrm OP Fuse Fail Alarm OP
0xAF84 Fuse Fail Alrm DPO Fuse Fail Alarm DPO
0xAFC1 Brkn Cond Alrm PKP Broken Cond Alarm PKP
0xAFC2 Brkn Cond Alarm OP Broken Cond Alarm OP
0xAFC4 Brkn Cond Alrm DPO Broken Cond Alarm DPO
0xB001 Ph IOC1 Alarm PKP Phase IOC 1 Alarm PKP
0xB002 Ph IOC1 Alarm OP Phase IOC 1 Alarm OP
0xB004 Ph IOC1 Alarm DPO Phase IOC 1 Alarm DPO
0xB009 Ph A IOC1 Alrm PKP Phase A IOC 1 Alarm PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-121


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xB00A Ph A IOC1 Alrm OP Phase A IOC 1 Alarm OP
0xB00C Ph A IOC1 Alrm DPO Phase A IOC 1 Alarm DPO
0xB011 Ph B IOC1 Alrm PKP Phase B IOC 1 Alarm PKP
0xB012 Ph B IOC1 Alrm OP Phase B IOC 1 Alarm OP
0xB014 Ph B IOC1 Alrm DPO Phase B IOC 1 Alarm DPO
0xB021 Ph C IOC1 Alrm PKP Phase C IOC 1 Alarm PKP
0xB022 Ph C IOC1 Alrm OP Phase C IOC 1 Alarm OP
0xB024 Ph C IOC1 Alrm DPO Phase C IOC 1 Alarm DPO
0xB041 Ntrl IOC1 Alrm PKP Neutral IOC 1 Alarm PKP
0xB042 Ntrl IOC1 Alrm OP Neutral IOC 1 Alarm OP
0xB044 Ntrl IOC1 Alrm DPO Neutral IOC 1 Alarm DPO
0xB081 Gnd IOC1 Alarm PKP Ground IOC 1 Alarm PKP
0xB082 Gnd IOC1 Alarm OP Ground IOC 1 Alarm OP
0xB084 Gnd IOC1 Alarm DPO Ground IOC 1 Alarm DPO
0xB0C1 Ph TOC1 Alarm PKP Phase TOC 1 Alarm PKP
0xB0C2 Ph TOC1 Alarm OP Phase TOC 1 Alarm OP
0xB0C4 Ph TOC1 Alarm DPO Phase TOC 1 Alarm DPO
0xB0C9 Ph A TOC1 Alrm PKP Phase A TOC 1 Alarm PKP
0xB0CA Ph A TOC1 Alrm OP Phase A TOC 1 Alarm OP
0xB0CC Ph A TOC1 Alrm DPO Phase A TOC 1 Alarm DPO
0xB0D1 Ph B TOC1 Alrm PKP Phase B TOC 1 Alarm PKP
0xB0D2 Ph B TOC1 Alrm OP Phase B TOC 1 Alarm OP
0xB0D4 Ph B TOC1 Alrm DPO Phase B TOC 1 Alarm DPO
0xB0E1 Ph C TOC1 Alrm PKP Phase C TOC 1 Alarm PKP
0xB0E2 Ph C TOC1 Alrm OP Phase C TOC 1 Alarm OP
0xB0E4 Ph C TOC1 Alrm DPO Phase C TOC 1 Alarm DPO
0xB101 Ntrl TOC1 Alrm PKP Neutral TOC 1 Alarm PKP
0xB102 Ntrl TOC1 Alrm OP Neutral TOC 1 Alarm OP
0xB104 Ntrl TOC1 Alrm DPO Neutral TOC 1 Alarm DPO
0xB141 Gnd TOC1 Alarm PKP Ground TOC Alarm PKP
0xB142 Gnd TOC1 Alarm OP Ground TOC 1 Alarm OP
0xB144 Gnd TOC1 Alarm DPO Ground TOC Alarm DPO
0xB181 Ph IOC2 Alarm PKP Phase IOC 2 Alarm PKP
0xB182 Ph IOC2 Alarm OP Phase IOC 2 Alarm OP
0xB184 Ph IOC2 Alarm DPO Phase IOC 2 Alarm DPO
0xB189 Ph A IOC2 Alrm PKP Phase A IOC 2 Alarm PKP
0xB18A Ph A IOC2 Alrm OP Phase A IOC 2 Alarm OP
0xB18C Ph A IOC2 Alrm DPO Phase A IOC 2 Alarm DPO
0xB191 Ph B IOC2 Alrm PKP Phase B IOC 2 Alarm PKP
0xB192 Ph B IOC2 Alrm OP Phase B IOC 2 Alarm OP
0xB194 Ph B IOC2 Alrm DPO Phase B IOC 2 Alarm DPO
0xB1A1 Ph C IOC2 Alrm PKP Phase C IOC 2 Alarm PKP
0xB1A2 Ph C IOC2 Alrm OP Phase C IOC 2 Alarm OP
0xB1A4 Ph C IOC2 Alrm DPO Phase C IOC 2 Alarm DPO
0xB1C1 Ntrl IOC2 Alrm PKP Neutral IOC 2 Alarm PKP
0xB1C2 Ntrl IOC2 Alrm OP Neutral IOC 2 Alarm OP
0xB1C4 Ntrl IOC2 Alrm DPO Neutral IOC 2 Alarm DPO

12-122 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xB201 Gnd IOC2 Alarm PKP Ground IOC 2 Alarm PKP
0xB202 Gnd IOC2 Alarm OP Ground IOC 2 Alarm OP
0xB204 Gnd IOC2 Alarm DPO Ground IOC 2 Alarm DPO
0xB301 SGnd TOC1 Alrm PKP Sensitive Ground TOC 1 Alarm PKP
0xB302 SGnd TOC1 Alrm OP Sensitive Ground TOC 1 Alarm OP
0xB304 SGnd TOC1 Alrm DPO Sensitive Ground TOC 1 Alarm DPO
0xB341 NtrlDir RevAlmPKP Neutral Directional Reverse Alarm PKP
0xB342 NtrlDir RevAlm OP Neutral Directional Alarm OP
0xB344 NtrlDir RevAlmDPO Neutral Directional Reverse Alarm DPO
0xB381 GndDir Alm PKP Ground Directional Alarm PKP
0xB382 GndDir Alm OP Ground Directional Alarm OP
0xB384 GndDir Alm DPO Ground Directional Alarm DPO
0xB3C1 NSeq OV Alrm PKP Negative Sequence OV Alarm PKP
0xB3C2 NSeq OV Alrm OP Negative Sequence OV Alarm OP
0xB3C4 NSeq OV Alrm DPO Negative Sequence OV Alarm DPO
0xB401 Ntrl OV Alrm PKP Neutral OV Alarm PKP
0xB402 Ntrl OV Alrm OP Neutral OV Alarm OP
0xB404 Ntrl OV Alrm DPO Neutral OV Alarm DPO
0xB441 Ph OV1 Alarm PKP Phase OV1 Alarm PKP
0xB442 Ph OV1 Alarm OP Phase OV 1 Alarm OP
0xB444 Ph OV1 Alarm DPO Phase OV1 Alarm DPO
0xB449 Ph A OV1 Alarm PKP Phase A OV1 Alarm PKP
0xB44A Ph A OV1 Alarm OP Phase A OV1 Alarm OP
0xB44C Ph A OV1 Alarm DPO Phase A OV1 Alarm DPO
0xB451 Ph B OV1 Alarm PKP Phase B OV1 Alarm PKP
0xB452 Ph B OV1 Alarm OP Phase B OV1 Alarm OP
0xB454 Ph B OV1 Alarm DPO Phase B OV1 Alarm DPO
0xB461 Ph C OV1 Alarm PKP Phase C OV1 Alarm PKP
0xB462 Ph C OV1 Alarm OP Phase C OV1 Alarm OP
0xB464 Ph C OV1 Alarm DPO Phase C OV1 Alarm DPO
0xB481 Ph UV1 Alarm PKP Phase UV1 Alarm PKP
0xB482 Ph UV1 Alarm OP Phase UV 1 Alarm OP
0xB484 Ph UV1 Alarm DPO Phase UV1 Alarm DPO
0xB489 Ph A UV1 Alarm PKP Phase A UV1 Alarm PKP
0xB48A Ph A UV1 Alarm OP Phase A UV1 Alarm OP
0xB48C Ph A UV1 Alarm DPO Phase A UV1 Alarm DPO
0xB491 Ph B UV1 Alarm PKP Phase B UV1 Alarm PKP
0xB492 Ph B UV1 Alarm OP Phase B UV1 Alarm OP
0xB494 Ph B UV1 Alarm DPO Phase B UV1 Alarm DPO
0xB4A1 Ph C UV1 Alarm PKP Phase C UV1 Alarm PKP
0xB4A2 Ph C UV1 Alarm OP Phase C UV1 Alarm OP
0xB4A4 Ph C UV1 Alarm DPO Phase C UV1 Alarm DPO
0xB4C1 Aux OV Alarm PKP Auxiliary OV Alarm PKP
0xB4C2 Aux OV Alarm OP Auxiliary OV Alarm OP
0xB4C4 Aux OV Alarm DPO Auxiliary OV Alarm DPO
0xB501 Aux UV Alarm PKP Auxiliary UV Alarm PKP
0xB502 Aux UV Alarm OP Auxiliary UV Alarm OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-123


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xB504 Aux UV Alarm DPO Auxiliary UV Alarm DPO
0xB541 UndrFreq1 Alrm PKP Underfrequency 1 Alarm PKP
0xB542 UndrFreq1 Alrm OP Underfrequency 1 Alarm OP
0xB544 UndrFreq1 Alrm DPO Underfrequency 1 Alarm DPO
0xB581 UndrFreq2 Alrm PKP Underfrequency 2 Alarm PKP
0xB582 UndrFreq2 Alrm OP Underfrequency 2 Alarm OP
0xB584 UndrFreq2 Alrm DPO Underfrequency 2 Alarm DPO
0xB5C1 OverFreq1 Alrm PKP Overfrequency 1 Alarm PKP
0xB5C2 OverFreq1 Alrm OP Overfrequency 1 Alarm OP
0xB5C4 OverFreq1 Alrm DPO Overfrequency 1 Alarm DPO
0xB601 OverFreq2 Alrm PKP Overfrequency 2 Alarm PKP
0xB602 OverFreq2 Alrm OP Overfrequency 2 Alarm OP
0xB604 OverFreq2 Alrm DPO Overfrequency 2 Alarm DPO
0xB641 SGnd IOC1 Alrm PKP Sensitive Ground IOC 1 Alarm PKP
0xB642 SGnd IOC1 Alrm OP Sensitive Ground IOC 1 Alarm OP
0xB644 SGnd IOC1 Alrm DPO Sensitive Ground IOC 1 Alarm DPO
0xB681 SGnd IOC2 Alrm PKP Sensitive Ground IOC 2 Alarm PKP
0xB682 SGnd IOC2 Alrm OP Sensitive Ground IOC 2 Alarm OP
0xB684 SGnd IOC2 Alrm DPO Sensitive Ground IOC 2 Alarm DPO
0xB6C1 NSeq IOC Alrm PKP Negative Sequence IOC Alarm PKP
0xB6C2 NSeq IOC Alrm OP NSeq IOC Alrm OP
0xB6C4 NSeq IOC Alrm DPO Negative Sequence IOC Alarm DPO
0xB701 Ph UV2 Alrm PKP Phase UV 2 Alrm PKP
0xB702 Ph UV2 Alrm OP Phase UV 2 Alrm OP
0xB704 Ph UV2 Alrm DPO Phase UV 2 Alrm DPO
0xB709 Ph A UV2 Alrm PKP Phase A UV 2 Alrm PKP
0xB70A Ph A UV2 Alrm OP Phase A UV 2 Alrm OP
0xB70C Ph A UV2 Alrm DPO Phase A UV 2 Alrm DPO
0xB711 Ph B UV2 Alrm PKP Phase B UV 2 Alrm PKP
0xB712 Ph B UV2 Alrm OP Phase B UV 2 Alrm OP
0xB714 Ph B UV2 Alrm DPO Phase B UV 2 Alrm DPO
0xB721 Ph C UV2 Alrm PKP Phase C UV 2 Alrm PKP
0xB722 Ph C UV2 Alrm OP Phase C UV 2 Alrm OP
0xB724 Ph C UV2 Alrm DPO Phase C UV 2 Alrm DPO
0xB741 Ph UV3 Alrm PKP Phase UV 3 Alrm PKP
0xB742 Ph UV3 Alrm OP Phase UV 3 Alrm OP
0xB744 Ph UV3 Alrm DPO Phase UV 3 Alrm DPO
0xB749 Ph A UV3 Alrm PKP Phase A UV 3 Alrm PKP
0xB74A Ph A UV3 Alrm OP Phase A UV 3 Alrm OP
0xB74C Ph A UV3 Alrm DPO Phase A UV 3 Alrm DPO
0xB751 Ph B UV3 Alrm PKP Phase B UV 3 Alrm PKP
0xB752 Ph B UV3 Alrm OP Phase B UV 3 Alrm OP
0xB754 Ph B UV3 Alrm DPO Phase B UV 3 Alrm DPO
0xB761 Ph C UV3 Alrm PKP Phase C UV 3 Alrm PKP
0xB762 Ph C UV3 Alrm OP Phase C UV 3 Alrm OP
0xB764 Ph C UV3 Alrm DPO Phase C UV 3 Alrm DPO
0xB781 Ph UV4 Alrm PKP Phase UV 4 Alrm PKP

12-124 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xB782 Ph UV4 Alrm OP Phase UV 4 Alrm OP
0xB784 Ph UV4 Alrm DPO Phase UV 4 Alrm DPO
0xB789 Ph A UV4 Alrm PKP Phase A UV 4 Alrm PKP
0xB78A Ph A UV4 Alrm OP Phase A UV 4 Alrm OP
0xB78C Ph A UV4 Alrm DPO Phase A UV 4 Alrm DPO
0xB791 Ph B UV4 Alrm PKP Phase B UV 4 Alrm PKP
0xB792 Ph B UV4 Alrm OP Phase B UV 4 Alrm OP
0xB794 Ph B UV4 Alrm DPO Phase B UV 4 Alrm DPO
0xB7A1 Ph C UV4 Alrm PKP Phase C UV 4 Alrm PKP
0xB7A2 Ph C UV4 Alrm OP Phase C UV 4 Alrm OP
0xB7A4 Ph C UV4 Alrm DPO Phase C UV 4 Alrm DPO
0xB7C1 NSeq OV2 Alrm PKP Negative Sequence OV2 Alrm PKP
0xB7C2 NSeq OV2 Alrm OP Negative Sequence OV2 Alrm OP
0xB7C4 NSeq OV2 Alrm DPO Negative Sequence OV2 Alrm DPO
0xB801 NSeq TOC1 Alrm PKP Negative Sequence TOC 1 Alarm PKP
0xB802 NSeq TOC1 Alrm OP Negative Sequence TOC 1 Alarm OP
0xB804 NSeq TOC1 Alrm DPO Negative Sequence TOC 1 Alarm DPO
0xB881 CTFail Alrm PKP CT Fail Alarm PKP
0xB882 CTFail Alrm OP CT Fail Alarm OP
0xB884 CTFail Alrm DPO CT Fail Alarm DPO
0xB8C1 Ph OV2 Alarm PKP Phase OV 2 Alarm PKP
0xB8C2 Ph OV2 Alarm OP Phase OV 2 Alarm OP
0xB8C4 Ph OV2 Alarm DPO Phase OV 2 Alarm DPO
0xB8C9 Ph A OV2 Alarm PKP Ph A OV2 Alarm PKP
0xB8CA Ph A OV2 Alarm OP Ph A OV2 Alarm OP
0xB8CC Ph A OV2 Alarm DPO Ph A OV2 Alarm DPO
0xB8D1 Ph B OV2 Alarm PKP Ph B OV2 Alarm PKP
0xB8D2 Ph B OV2 Alarm OP Ph B OV2 Alarm OP
0xB8D4 Ph B OV2 Alarm DPO Ph B OV2 Alarm DPO
0xB8E1 Ph C OV2 Alarm PKP Ph C OV2 Alarm PKP
0xB8E2 Ph C OV2 Alarm OP Ph C OV2 Alarm OP
0xB8E4 Ph C OV2 Alarm DPO Ph C OV2 Alarm DPO
0xB901 Ph OV3 Alarm PKP Phase OV 3 Alarm PKP
0xB902 Ph OV3 Alarm OP Phase OV 3 Alarm OP
0xB904 Ph OV3 Alarm DPO Phase OV 3 Alarm DPO
0xB909 Ph A OV3 Alarm PKP Phase A OV 3 Alarm PKP
0xB90A Ph A OV3 Alarm OP Phase A OV 3 Alarm OP
0xB90C Ph A OV3 Alarm DPO Phase A OV 3 Alarm DPO
0xB911 Ph B OV3 Alarm PKP Phase B OV 3 Alarm PKP
0xB912 Ph B OV3 Alarm OP Phase B OV 3 Alarm OP
0xB914 Ph B OV3 Alarm DPO Phase B OV 3 Alarm DPO
0xB921 Ph C OV3 Alarm PKP Phase C OV 3 Alarm PKP
0xB922 Ph C OV3 Alarm OP Phase C OV 3 Alarm OP
0xB924 Ph C OV3 Alarm DPO Phase C OV 3 Alarm DPO
0xB941 Ph OV4 Alarm PKP Phase OV 4 Alarm PKP
0xB942 Ph OV4 Alarm OP Phase OV 4 Alarm OP
0xB944 Ph OV4 Alarm DPO Phase OV 4 Alarm DPO

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-125


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xB949 Ph A OV4 Alarm PKP Phase A OV 4 Alarm PKP
0xB94A Ph A OV4 Alarm OP Phase A OV 4 Alarm OP
0xB94C Ph A OV4 Alarm DPO Phase A OV 4 Alarm DPO
0xB951 Ph B OV4 Alarm PKP Phase B OV 4 Alarm PKP
0xB952 Ph B OV4 Alarm OP Phase B OV 4 Alarm OP
0xB954 Ph B OV4 Alarm DPO Phase B OV 4 Alarm DPO
0xB961 Ph C OV4 Alarm PKP Phase C OV 4 Alarm PKP
0xB962 Ph C OV4 Alarm OP Phase C OV 4 Alarm OP
0xB964 Ph C OV4 Alarm DPO Phase C OV 4 Alarm DPO
0xB981 Ntrl OV2 Alrm PKP Neutral OV 2 Alarm PKP
0xB982 Ntrl OV2 Alrm OP Neutral OV 2 Alarm OP
0xB984 Ntrl OV2 Alrm DPO Neutral OV 2 Alarm DPO
0xB9C1 Ntrl OV3 Alrm PKP Neutral OV 3 Alarm PKP
0xB9C2 Ntrl OV3 Alrm OP Neutral OV 3 Alarm OP
0xB9C4 Ntrl OV3 Alrm DPO Neutral OV 3 Alarm DPO
0xBA01 Ntrl OV4 Alrm PKP Neutral OV 4 Alarm PKP
0xBA02 Ntrl OV4 Alrm OP Neutral OV 4 Alarm OP
0xBA04 Ntrl OV4 Alrm DPO Neutral OV 4 Alarm DPO
0xBA41 OverFreq3 Alrm PKP Overfrequency 3 Alrm PKP
0xBA42 OverFreq3 Alrm OP Overfrequency 3 Alrm OP
0xBA44 OverFreq3 Alrm DPO Overfrequency 3 Alrm DPO
0xBA81 OverFreq4 Alrm PKP Overfrequency 4 Alrm PKP
0xBA82 OverFreq4 Alrm OP Overfrequency 4 Alrm OP
0xBA84 OverFreq4 Alrm DPO Overfrequency 4 Alrm DPO
0xBAC1 UndFreq3 Alrm PKP Underfrequency 3 Alrm PKP
0xBAC2 UndFreq3 Alarm OP Underfrequency 3 Alarm OP
0xBAC4 UndFreq3 Alrm DPO Underfrequency 3 Alrm DPO
0xBB01 UndFreq4 Alarm PKP Underfrequency 4 Alarm PKP
0xBB02 UndFreq4 Alarm OP Underfrequency 4 Alarm OP
0xBB04 UndFreq4 Alarm DPO Underfrequency 4 Alarm DPO
0xBC01 LE 9 Alarm PKP Logic Element 9 Alarm PKP
0xBC02 LE 9 Alarm OP Logic Element 9 Alarm OP
0xBC04 LE 9 Alarm DPO Logic Element 9 Alarm DPO
0xBC41 LE 10 Alarm PKP Logic Element 10 Alarm PKP
0xBC42 LE 10 Alarm OP Logic Element 10 Alarm OP
0xBC44 LE 10 Alarm DPO Logic Element 10 Alarm DPO
0xBC81 LE 11 Alarm PKP Logic Element 11 Alarm PKP
0xBC82 LE 11 Alarm OP Logic Element 11 Alarm OP
0xBC84 LE 11 Alarm DPO Logic Element 11 Alarm DPO
0xBCC1 LE 12 Alarm PKP Logic Element 12 Alarm PKP
0xBCC2 LE 12 Alarm OP Logic Element 12 Alarm OP
0xBCC4 LE 12 Alarm DPO Logic Element 12 Alarm DPO
0xBD01 LE 13 Alarm PKP Logic Element 13 Alarm PKP
0xBD02 LE 13 Alarm OP Logic Element 13 Alarm OP
0xBD04 LE 13 Alarm DPO Logic Element 13 Alarm DPO
0xBD41 LE 14 Alarm PKP Logic Element 14 Alarm PKP
0xBD42 LE 14 Alarm OP Logic Element 14 Alarm OP

12-126 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xBD44 LE 14 Alarm DPO Logic Element 14 Alarm DPO
0xBD81 LE 15 Alarm PKP Logic Element 15 Alarm PKP
0xBD82 LE 15 Alarm OP Logic Element 15 Alarm OP
0xBD84 LE 15 Alarm DPO Logic Element 15 Alarm DPO
0xBDC1 LE 16 Alarm PKP Logic Element 16 Alarm PKP
0xBDC2 LE 16 Alarm OP Logic Element 16 Alarm OP
0xBDC4 LE 16 Alarm DPO Logic Element 16 Alarm DPO
0xBE02 PhDir RevAlm OP Ph Directional Reverse Alarm OP
0xBE04 PhDir RevAlm DPO Ph Directional Reverse Alarm DPO
0xBE0A PhADir RevAlm OP Ph A Directional Reverse Alarm OP
0xBE0C PhADir RevAlm DPO Ph A Directional Reverse Alarm DPO
0xBE12 PhBDir RevAlm OP Ph B Directional Reverse Alarm OP
0xBE14 PhBDir RevAlm DPO Ph B Directional Reverse Alarm DPO
0xBE22 PhCDir RevAlm OP Ph C Directional Reverse Alarm OP
0xBE24 PhCDir RevAlm DPO Ph C Directional Reverse Alarm DPO
0xBE42 PhDir UndAlm OP Ph Directional Und Alarm OP
0xBE44 PhDir UndAlm DPO Ph Directional Und Alarm DPO
0xBE4A PhADir UndAlm OP Ph A Directional Und Alarm OP
0xBE4C PhADir UndAlm DPO Ph A Directional Und Alarm DPO
0xBE52 PhBDir UndAlm OP Ph B Directional Und Alarm OP
0xBE54 PhBDir UndAlm DPO Ph B Directional Und Alarm DPO
0xBE62 PhCDir UndAlm OP Ph C Directional Und Alarm OP
0xBE64 PhCDir UndAlm DPO Ph C Directional Und Alarm DPO
0xBE82 GndDir UndAlm OP Ground Directional Und Alarm OP
0xBE84 GndDir UndAlm DPO Ground Directional Und Alarm DPO
0xBEC2 NtrlDir UndAlm OP Neutral Directional Und Alarm OP
0xBEC4 NtrlDir UndAlm DPO Neutral Directional Und Alarm DPO
0xBF01 WGF 1 Alarm PKP Wattmetric Gnd Fault 1 Alarm PKP
0xBF02 WGF 1 Alarm OP Wattmetric Gnd Fault 1 Alarm OP
0xBF04 WGF 1 Alarm DPO Wattmetric Gnd Fault 1 Alarm DPO
0xBF41 WGF 2 Alarm PKP Wattmetric Gnd Fault 2 Alarm PKP
0xBF42 WGF 2 Alarm OP Wattmetric Gnd Fault 2 Alarm OP
0xBF44 WGF 2 Alarm DPO Wattmetric Gnd Fault 2 Alarm DPO
0xC042 Output Relay 3 On Output Relay 3 On
0xC044 Output Relay 3 Off Output Relay 3 Off
0xC082 Output Relay 4 On Output Relay 4 On
0xC084 Output Relay 4 Off Output Relay 4 Off
0xC0C2 Output Relay 5 On Output Relay 5 On
0xC0C4 Output Relay 5 Off Output Relay 5 Off
0xC102 Output Relay 6 On Output Relay 6 On
0xC104 Output Relay 6 Off Output Relay 6 Off
0xC142 Self-Test Rly 7 OP Self-Test Rly 7 OP
0xC144 Self-Tst Rly 7 DPO Self-Tst Rly 7 DPO
0xC202 BKR Connected Breaker Connected OP
0xC242 Arc Flash OP Arc Flash OP
0xC282 Any Pkp OP Any Pkp OP
0xC2C1 Lockout PKP Lockout PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-127


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xC2C2 Lockout OP Lockout OP
0xC2C4 Lockout DPO Lockout DPO
0xC302 Sync Operation Synchrocheck Operation
0xC342 Sync Close OP Synchrocheck Close OP
0xC382 Sync Condition Synchrocheck Condition
0xC442 HS Phase IOC OP HS Phase IOC OP
0xC44A HS PhA IOC OP HS PhA IOC OP
0xC452 HS PhB IOC OP HS PhB IOC OP
0xC462 HS PhC IOC OP HS PhC IOC OP
0xC482 HSGnd IOC OP HS Ground IOC OP
0xC4C1 LE 1 PKP Logic Element 1 PKP
0xC4C2 LE 1 OP Logic Element 1 OP
0xC4C4 LE 1 DPO Logic Element 1 DPO
0xC501 LE 2 PKP Logic Element 2 PKP
0xC502 LE 2 OP Logic Element 2 OP
0xC504 LE 2 DPO Logic Element 2 DPO
0xC541 LE 3 PKP Logic Element 3 PKP
0xC542 LE 3 OP Logic Element 3 OP
0xC544 LE 3 DPO Logic Element 3 DPO
0xC581 LE 4 PKP Logic Element 4 PKP
0xC582 LE 4 OP Logic Element 4 OP
0xC584 LE 4 DPO Logic Element 4 DPO
0xC5C1 LE 5 PKP Logic Element 5 PKP
0xC5C2 LE 5 OP Logic Element 5 OP
0xC5C4 LE 5 DPO Logic Element 5 DPO
0xC601 LE 6 PKP Logic Element 6 PKP
0xC602 LE 6 OP Logic Element 6 OP
0xC604 LE 6 DPO Logic Element 6 DPO
0xC641 LE 7 PKP Logic Element 7 PKP
0xC642 LE 7 OP Logic Element 7 OP
0xC644 LE 7 DPO Logic Element 7 DPO
0xC681 LE 8 PKP Logic Element 8 PKP
0xC682 LE 8 OP Logic Element 8 OP
0xC684 LE 8 DPO Logic Element 8 DPO
0xC742 Testing ON Testing ON
0xC744 Testing OFF Testing OFF
0xC882 Setpoint Group2 On Setpoint Group2 On
0xC902 BKR Open Breaker Open
0xC942 BKR Close Breaker Close
0xC982 Maint. Req. OP Maintenance Required OP
0xCA02 52a Contact OP 52a Contact OP
0xCA42 52b Contact OP 52b Contact OP
0xCA44 52b Contact DPO 52b Contact DPO
0xCA82 Reset OK Reset OK
0xCAC2 L/O Rst Closed OP Lockout Reset Closed OP
0xCAC4 L/O Rst Closed DPO Lockout Reset Closed DPO
0xCB02 AR Close AR Close

12-128 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xCB42 AR N/Ready AR N/Ready
0xCB44 AR N/Ready DPO AR N/Ready DPO
0xCB82 AR In Progress AR In Progress
0xCBC2 AR Disabled AR Disabled
0xCC02 AR Ext. Init AR Ext. Init
0xCC42 AR Ready AR Ready
0xCCC2 BKR Stat Open Breaker Status Open OP
0xCD02 BKR Stat Clsd Breaker Status Closed OP
0xCD42 Setpoint Group1 On Setpoint Group1 On
0xCD82 Light Sensor 1 OP Light Sensor 1 OP
0xCDC2 Light Sensor 2 OP Light Sensor 2 OP
0xCE81 Dir Pwr 1 PKP Directional Pwr 1 PKP
0xCE82 Dir Pwr 1 OP Directional Pwr 1 OP
0xCEC1 Dir Pwr 2 PKP Directional Pwr 2 PKP
0xCEC2 Dir Pwr 2 OP Directional Pwr 2 OP
0xCF01 2nd Hrmc PKP 2nd Harmonic PKP
0xCF02 2nd Hrmc OP 2nd Harmonic OP
0xCF04 2nd Hrmc DPO 2nd Harmonic DPO
0xCF42 Light Sensor 3 OP Light Sensor 3 OP
0xCF82 Light Sensor 4 OP Light Sensor 4 OP
0xCFC1 Brkn Cond PKP Broken Cond PKP
0xCFC2 Brkn Cond OP Broken Cond OP
0xCFC4 Brkn Cond DPO Broken Cond DPO
0xD341 Ntrl Dir Rev PKP Neutral Directional Reverse PKP
0xD342 Ntrl Dir Rev OP Neutral Directional Rev OP
0xD344 Ntrl Dir Rev DPO Neutral Directional Reverse DPO
0xD382 Gnd Dir OP Ground Directional OP
0xD384 Gnd Dir DPO Ground Directional DPO
0xD441 Ph OV1 PKP Phase OV1 PKP
0xD442 Ph OV1 OP Ph OV 1 OP
0xD444 Ph OV1 DPO Phase OV1 DPO
0xD481 Ph UV1 PKP Phase UV1 PKP
0xD482 Ph UV1 OP Ph UV 1 OP
0xD484 Ph UV1 DPO Phase UV1 DPO
0xD701 Ph UV2 PKP Phase UV 2 PKP
0xD702 Ph UV2 OP Phase UV 2 OP
0xD704 Ph UV2 DPO Phase UV 2 DPO
0xD741 Ph UV3 PKP Phase UV 3 PKP
0xD742 Ph UV3 OP Phase UV 3 OP
0xD744 Ph UV3 DPO Phase UV 3 DPO
0xD781 Ph UV4 PKP Phase UV 4 PKP
0xD782 Ph UV4 OP Phase UV 4 OP
0xD784 Ph UV4 DPO Phase UV 4 DPO
0xD801 NSeq TOC1 PKP Negative Sequence TOC 1 PKP
0xD802 NSeq TOC1 OP Negative Sequence TOC 1 OP
0xD804 NSeq TOC1 DPO Negative Sequence TOC 1 DPO
0xD8C1 Ph OV2 PKP Ph OV2 PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-129


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xD8C2 Ph OV2 OP Ph OV2 OP
0xD8C4 Ph OV2 DPO Ph OV2 DPO
0xD901 Ph OV3 PKP Phase OV 3 PKP
0xD902 Ph OV3 OP Phase OV 3 OP
0xD904 Ph OV3 DPO Phase OV 3 DPO
0xD941 Ph OV4 PKP Phase OV 4 PKP
0xD942 Ph OV4 OP Phase OV 4 OP
0xD944 Ph OV4 DPO Phase OV 4 DPO
0xDC01 LE 9 PKP Logic Element 9 PKP
0xDC02 LE 9 OP Logic Element 9 OP
0xDC04 LE 9 DPO Logic Element 9 DPO
0xDC41 LE 10 PKP Logic Element 10 PKP
0xDC42 LE 10 OP Logic Element 10 OP
0xDC44 LE 10 DPO Logic Element 10 DPO
0xDC81 LE 11 PKP Logic Element 11 PKP
0xDC82 LE 11 OP Logic Element 11 OP
0xDC84 LE 11 DPO Logic Element 11 DPO
0xDCC1 LE 12 PKP Logic Element 12 PKP
0xDCC2 LE 12 OP Logic Element 12 OP
0xDCC4 LE 12 DPO Logic Element 12 DPO
0xDD01 LE 13 PKP Logic Element 13 PKP
0xDD02 LE 13 OP Logic Element 13 OP
0xDD04 LE 13 DPO Logic Element 13 DPO
0xDD41 LE 14 PKP Logic Element 14 PKP
0xDD42 LE 14 OP Logic Element 14 OP
0xDD44 LE 14 DPO Logic Element 14 DPO
0xDD81 LE 15 PKP Logic Element 15 PKP
0xDD82 LE 15 OP Logic Element 15 OP
0xDD84 LE 15 DPO Logic Element 15 DPO
0xDDC1 LE 16 PKP Logic Element 16 PKP
0xDDC2 LE 16 OP Logic Element 16 OP
0xDDC4 LE 16 DPO Logic Element 16 DPO
0xDE02 PhDir Rev OP Ph Directional Reverse OP
0xDE04 PhDir Rev DPO Ph Directional Reverse DPO
0xDE0A PhADir Rev OP Ph A Directional Reverse OP
0xDE0C PhADir Rev DPO Ph A Directional Reverse DPO
0xDE12 PhBDir Rev OP Ph B Directional Reverse OP
0xDE14 PhBDir Rev DPO Ph B Directional Reverse DPO
0xDE22 PhCDir Rev OP Ph C Directional Reverse OP
0xDE24 PhCDir Rev DPO Ph C Directional Reverse DPO
0xDE42 PhDir Und OP Ph Directional Und OP
0xDE44 PhDir Und DPO Ph Directional Und DPO
0xDE4A PhADir Und OP Ph A Directional Und OP
0xDE4C PhADir Und DPO Ph A Directional Und DPO
0xDE52 PhBDir Und OP Ph B Directional Und OP
0xDE54 PhBDir Und DPO Ph B Directional Und DPO
0xDE62 PhCDir Und OP Ph C Directional Und OP

12-130 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xDE64 PhCDir Und DPO Ph C Directional Und DPO
0xDE82 GndDir Und OP Ground Directional Und OP
0xDE84 GndDir Und DPO Ground Directional Und DPO
0xDEC2 NtrlDir Und OP Neutral Directional Und OP
0xDEC4 NtrlDir Und DPO Neutral Directional Und DPO
0xDF01 WGF 1 PKP Wattmetric Gnd Fault 1 PKP
0xDF02 WGF 1 OP Wattmetric Gnd Fault 1 OP
0xDF04 WGF 1 DPO Wattmetric Gnd Fault 1 DPO
0xDF41 WGF 2 PKP Wattmetric Gnd Fault 2 PKP
0xDF42 WGF 2 OP Wattmetric Gnd Fault 2 OP
0xDF44 WGF 2 DPO Wattmetric Gnd Fault 2 DPO
0xE002 Any Block Any Block
0xE004 Any Block DPO Any Block DPO
0xE042 Therm O/L Block Thermal Level Block
0xE044 Therm O/L Blk DPO Thermal Level Block DPO
0xE082 PosSeq UV1 Block Positive Sequence UV 1 Block
0xE084 PosSeq UV1 BlckDPO Positive Sequence UV 1 Block DPO
0xE182 Output Relay 1 Blk Output Relay 1 Block
0xE184 Relay 1 Blk DPO Relay 1 Block DPO
0xE1C2 Output Relay 2 Blk Output Relay 2 Block
0xE1C4 Relay 2 Blk DPO Relay 2 Block DPO
0xE242 Arc Flash Block Arc Flash Block
0xE244 Arc Flash Blck DPO Arc Flash Blck DPO
0xE2C2 Lockout Block Lockout Block
0xE2C4 Lockout Block DPO Lockout Block DPO
0xE3C2 Volt Hz Block Volt Hz Block
0xE3C4 Volt Hz Block DPO Volt Hz Block DPO
0xE742 Curr Dmd1 Block Current Demand 1 Block OP
0xE744 Curr Dmd1 Blk DPO Current Demand 1 Block DPO
0xE782 RealP Dmd Block Real Power Demand Block OP
0xE784 RealP Dmd Blk DPO Real Power Demand Block DPO
0xE7C2 ReacP Dmd Block Reactive Power Demand Block OP
0xE7C4 ReacP Dmd Blk DPO Reactive Power Demand Block DPO
0xE802 AppP Dmd Block Apparent Power Demand Block OP
0xE804 AppP Dmd Block DPO Apparent Power Demand Block DPO
0xE882 Group Change Blk Group Change Blk
0xE884 Grp Change Blk DPO Group Change Block DPO
0xEB02 AR Block AR Block
0xEB04 AR Block DPO AR Block DPO
0xEE82 Dir Pwr 1 Block Directional Pwr 1 Block
0xEE84 Dir Pwr 1 Blk DPO Directional Pwr 1 Block DPO
0xEEC2 Dir Pwr 2 Block Directional Pwr 2 Block
0xEEC4 Dir Pwr 2 Blk DPO Directional Pwr 2 Block DPO
0xEFC2 Brkn Cond Block Broken Cond Block
0xEFC4 Brkn Cond Blk DPO Broken Cond Block DPO
0xF002 Ph IOC1 Block Phase IOC 1 Block
0xF004 Ph IOC1 Block DPO Phase IOC 1 Block DPO

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-131


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xF042 Ntrl IOC1 Block Neutral IOC 1 Block
0xF044 Ntrl IOC1 Blk DPO Neutral IOC 1 Block DPO
0xF082 Gnd IOC1 Block Ground IOC 1 Block
0xF084 Gnd IOC1 Block DPO Ground IOC 1 Block DPO
0xF0C2 Ph TOC1 Block Phase TOC 1 Block
0xF0C4 Ph TOC1 Block DPO Phase TOC 1 Block DPO
0xF102 Ntrl TOC1 Block Neutral TOC 1 Block
0xF104 Ntrl TOC1 BlockDPO Neutral TOC 1 Block DPO
0xF142 Gnd TOC1 Block Ground TOC 1 Block
0xF144 Gnd TOC1 Block DPO Ground TOC 1 Block DPO
0xF182 Ph IOC2 Block Phase IOC 2 Block
0xF184 Ph IOC2 Block DPO Phase IOC 2 Block DPO
0xF1C2 Ntrl IOC2 Block Neutral IOC 2 Block
0xF1C4 Ntrl IOC2 Blk DPO Neutral IOC 2 Block DPO
0xF202 Gnd IOC2 Block Ground IOC 2 Block
0xF204 Gnd IOC2 Block DPO Ground IOC 2 Block DPO
0xF302 SGnd TOC1 Block Sensitive Ground TOC 1 Block
0xF304 SGnd TOC1 BlockDPO Sensitive Ground TOC 1 Block DPO
0xF342 Ntrl Dir Rev Block Neutral Directional Rev Block
0xF344 Ntrl Dir Block DPO Neutral Directional Block DPO
0xF382 Gnd Dir Block Ground Directional Block
0xF384 Gnd Dir Block DPO Ground Directional Block DPO
0xF3C2 NSeq OV Block Negative Sequence OV OP
0xF3C4 NSeq OV Blk DPO Negative Sequence OV Block DPO
0xF402 Ntrl OV Block Neutral OV Block
0xF404 Ntrl OV Block DPO Neutral OV Block DPO
0xF442 Ph OV1 Block Ph OV 1 Block
0xF444 Ph OV1 Block DPO Ph OV 1 Block DPO
0xF482 Ph UV1 Block Ph UV 1 Block
0xF484 Ph UV1 Block DPO Ph UV 1 Block DPO
0xF4C2 Aux OV Block Auxiliary OV Block
0xF4C4 Aux OV Block DPO Auxiliary OV Block DPO
0xF502 Aux UV Block Auxiliary UV Block
0xF504 Aux UV Block DPO Auxiliary UV Block DPO
0xF542 UndrFreq1 Block Underfrequency 1 Block
0xF544 UndrFreq1 BlockDPO Underfrequency 1 Block DPO
0xF582 UndrFreq2 Block Underfrequency 2 Block
0xF584 UndrFreq2 BlockDPO Underfrequency 2 Block DPO
0xF5C2 OverFreq1 Block Overfrequency 1 Block
0xF5C4 OverFreq1 Blk DPO Overfrequency 1 Block DPO
0xF602 OverFreq2 Block Overfrequency 2 Block
0xF604 OverFreq2 BlockDPO Overfrequency 2 Block DPO
0xF642 SGnd IOC1 Block Sensitive Ground IOC 1 Block
0xF644 SGnd IOC1 Blk DPO Sensitive Ground IOC 1 Block DPO
0xF682 SGnd IOC2 Block Sensitive Ground IOC 2 Block
0xF684 SGnd IOC2 Blk DPO Sensitive Ground IOC 2 Block DPO
0xF6C2 NSeq IOC Block Negative Sequence IOC Block

12-132 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xF6C4 NSeq IOC Block DPO Negative Sequence IOC Block DPO
0xF702 Ph UV2 Block Phase UV 2 Block OP
0xF704 Ph UV2 Block DPO Phase UV 2 Block DPO
0xF742 Ph UV3 Block Phase UV 3 Block OP
0xF744 Ph UV3 Block DPO Phase UV 3 Block DPO
0xF782 Ph UV4 Block Phase UV 4 Block OP
0xF784 Ph UV4 Block DPO Phase UV 4 Block DPO
0xF7C2 NSeq OV2 Block Negative Sequence OV2 Block
0xF7C4 NSeq OV2 Blk DPO Negative Sequence OV2 Blk DPO
0xF802 NSeq TOC1 Blk Negative Sequence TOC 1 Block
0xF804 NSeq TOC1 Blk DPO Negative Sequence TOC 1 Block DPO
0xF882 CTFail Block CT Fail Block
0xF884 CTFail Block DPO CT Fail Block DPO
0xF8C2 Ph OV2 Block Ph OV2 Block
0xF8C4 Ph OV2 Block DPO Ph OV2 Block DPO
0xF902 Ph OV3 Block Phase OV 3 Block OP
0xF904 Ph OV3 Block DPO Phase OV 3 Block DPO
0xF942 Ph OV4 Block Phase OV 4 Block OP
0xF944 Ph OV4 Block DPO Phase OV 4 Block DPO
0xF982 Ntrl OV2 Block Neutral OV 2 Block
0xF984 Ntrl OV2 Block DPO Neutral OV 2 Block DPO
0xF9C2 Ntrl OV3 Block Neutral OV 3 Block
0xF9C4 Ntrl OV3 Block DPO Neutral OV 3 Block DPO
0xFA02 Ntrl OV4 Block Neutral OV 4 Block
0xFA04 Ntrl OV4 Block DPO Neutral OV 4 Block DPO
0xFA42 OverFreq3 Block Overfrequency 3 Block
0xFA44 OverFreq3 Blk DPO Overfrequency 3 Blk DPO
0xFA82 OverFreq4 Block Overfrequency 4 Block
0xFA84 OverFreq4 Blk DPO Overfrequency 4 Blk DPO
0xFAC2 UndFreq3 Block Underfrequency 3 Block
0xFAC4 UndFreq3 Block DPO Underfrequency 3 Block DPO
0xFB02 UndFreq4 Block Underfrequency 4 Block
0xFB04 UndFreq4 Block DPO Underfrequency 4 Block DPO
0xFE02 PhDir Block Ph Directional Block
0xFE04 PhDir Block DPO Ph Directional Block DPO
0xFE0A PhADir Block PhA Directional Block
0xFE0C PhADir Block DPO PhA Directional Block DPO
0xFE12 PhBDir Block PhB Directional Block
0xFE14 PhBDir Block DPO PhB Directional Block DPO
0xFE22 PhCDir Block PhC Directional Block
0xFE24 PhCDir Block DPO PhC Directional Block DPO
0xFF02 WGF 1 Block Wattmetric Gnd Fault 1 Block
0xFF04 WGF 1 BlockDPO Wattmetric Gnd Fault 1 Block DPO
0xFF42 WGF 2 Block Wattmetric Gnd Fault 2 Block
0xFF44 WGF 2 BlockDPO Wattmetric Gnd Fault 2 Block DPO
FC134A unsigned 16 bits Active Targets
0 No Active Targets No Active Targets

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-133


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


7 Clock Not Set Clock Not Set
8 IRIG-B Failure IRIG-B Failure
14 Comm. Alert 1 Comm. Alert 1
15 Comm. Alert 2 Comm. Alert 2
16 Comm. Alert 3 Comm. Alert 3
17 Ethernet Link Fail Ethernet Link Failure
18 High ENET Traffic High Ethernet Traffic
19 Intern Temp. >80C Internal Temperature High
40 Eth Link A Fail Ethernet Link A Fail
41 Eth Link B Fail Ethernet Link B Fail
0x8040 Therm O/L Trip Therm O/L Trip
0x8080 PosSeq UV1 Trip Positive Sequence UV 1 Trip
0x8240 Arc Flash Trip Arc Flash Trip
0x83C0 Volt Hz Trip Volt Hz Trip
0x8480 Relay Not Config Relay Not Config
0x84C0 LE 1 Trip Logic Element 1 Trip
0x8500 LE 2 Trip Logic Element 2 Trip
0x8540 LE 3 Trip Logic Element 3 Trip
0x8580 LE 4 Trip Logic Element 4 Trip
0x85C0 LE 5 Trip Logic Element 5 Trip
0x8600 LE 6 Trip Logic Element 6 Trip
0x8640 LE 7 Trip Logic Element 7 Trip
0x8680 LE 8 Trip Logic Element 8 Trip
0x89C0 Self Test Trip Self Test Trip
0x8D00 Rly #1 Trip OP Rly #1 Trip OP
0x8D40 Rly #2 Trip OP Rly #2 Trip OP
0x8D80 BKR Failure BKR Failure
0x8E80 Dir Pwr 1 Trip Directional Pwr 1 Trip
0x8EC0 Dir Pwr 2 Trip Directional Pwr 2 Trip
0x8F80 Fuse Fail Trip Fuse Fail Trip
0x8FC0 Brkn Cond Trip Broken Cond Trip
0x9000 Ph IOC1 Trip Phase IOC 1 Trip
0x9040 Ntrl IOC1 Trip Neutral IOC 1 Trip
0x9080 Gnd IOC1 Trip Ground IOC 1 Trip
0x90C0 Ph TOC1 Trip Phase TOC 1 Trip
0x9100 Ntrl TOC1 Trip Neutral TOC 1 Trip
0x9140 Gnd TOC1 Trip Ground TOC 1 Trip
0x9180 Ph IOC2 Trip Phase IOC 2 Trip
0x91C0 Ntrl IOC2 Trip Neutral IOC 2 Trip
0x9200 Gnd IOC2 Trip Ground IOC 2 Trip
0x9300 SGnd TOC1 Trip Sensitive Ground TOC 1 Trip
0x93C0 NSeq OV Trip Negative Sequence OV Trip
0x9400 Ntrl OV Trip Neutral OV Trip
0x9440 Ph OV1 Trip Phase OV 1 Trip
0x9480 Ph UV1 Trip Phase UV 1 Trip
0x94C0 Aux OV Trip Auxiliary OV Trip
0x9500 Aux UV Trip Auxiliary UV Trip

12-134 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x9540 UndrFreq1 Trip Underfrequency 1 Trip
0x9580 UndrFreq2 Trip Underfrequency 2 Trip
0x95C0 OverFreq1 Trip Overfrequency 1 Trip
0x9600 OverFreq2 Trip Overfrequency 2 Trip
0x9640 SGnd IOC1 Trip Sensitive Ground IOC 1 Trip
0x9680 SGnd IOC2 Trip Sensitive Ground IOC 2 Trip
0x96C0 NSeq IOC Trip Negative Sequence IOC Trip
0x9700 Ph UV2 Trip Phase UV 2 Trip
0x9740 Ph UV3 Trip Phase UV 3 Trip
0x9780 Ph UV4 Trip Phase UV 4 Trip
0x97C0 NSeq OV2 Trip Negative Sequence OV2 Trip
0x9800 NSeq TOC1 Trip Negative Sequence TOC 1 Trip
0x98C0 Ph OV2 Trip Ph OV2 Trip
0x9900 Ph OV3 Trip Ph OV3 Trip
0x9940 Ph OV4 Trip Ph OV4 Trip
0x9980 Ntrl OV2 Trip Neutral OV 2 Trip
0x99C0 Ntrl OV3 Trip Neutral OV 3 Trip
0x9A00 Ntrl OV4 Trip Neutral OV 4 Trip
0x9A40 OverFreq3 Trip Overfrequency 3 Trip
0x9A80 OverFreq4 Trip Overfrequency 4 Trip
0x9AC0 UndFreq3 Trip Underfrequency 3 Trip
0x9B00 UndFreq4 Trip Underfrequency 4 Trip
0x9C00 LE 9 Trip Logic Element 9 Trip
0x9C40 LE 10 Trip Logic Element 10 Trip
0x9C80 LE 11 Trip Logic Element 11 Trip
0x9CC0 LE 12 Trip Logic Element 12 Trip
0x9D00 LE 13 Trip Logic Element 13 Trip
0x9D40 LE 14 Trip Logic Element 14 Trip
0x9D80 LE 15 Trip Logic Element 15 Trip
0x9DC0 LE 16 Trip Logic Element 16 Trip
0x9F00 WGF 1 Trip Wattmetric Gnd Fault 1 Trip
0x9F40 WGF 2 Trip Wattmetric Gnd Fault 2 Trip
0xA040 Therm Lvl Alrm Thermal Level Alarm
0xA080 PosSeq UV1 Alrm Positive Sequence UV 1 Alarm
0xA240 Arc Flash Alarm Arc Flash Alarm
0xA2C0 Light Sens1 Trouble Light Sensor 1 Trouble
0xA300 Light Sens2 Trouble Light Sensor 2 Trouble
0xA340 Light Sens3 Trouble Light Sensor 3 Trouble
0xA380 Light Sens4 Trouble Light Sensor 4 Trouble
0xA3C0 Volt Hz Alarm Volt Hz Alarm
0xA440 LightSns Trbl Alrm Light Sensor Trouble Alarm
0xA480 Not Configured Not Configured
0xA4C0 LE 1 Alarm Logic Element 1 Alarm
0xA500 LE 2 Alarm Logic Element 2 Alarm
0xA540 LE 3 Alarm Logic Element 3 Alarm
0xA580 LE 4 Alarm Logic Element 4 Alarm
0xA5C0 LE 5 Alarm Logic Element 5 Alarm

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-135


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xA600 LE 6 Alarm Logic Element 6 Alarm
0xA640 LE 7 Alarm Logic Element 7 Alarm
0xA680 LE 8 Alarm Logic Element 8 Alarm
0xA740 Curr Dmd1 Alrm Current Demand 1 Alarm
0xA780 RealP Dmd Alrm Real Power Demand Alarm
0xA7C0 ReacP Dmd Alrm Reactive Power Demand Alarm
0xA800 AppP Dmd Alrm Apparent Power Demand Alarm
0xAA00 BKR Alarm Breaker Alarm
0xAA40 BKR Trip Time Breaker Trip Time
0xAA80 BKR Close Time Breaker Close Time
0xAAC0 BKR Charge Time Breaker Charge Time
0xAB00 BKR Trp/Cls Fail Breaker Trip/Close Fail
0xAB40 BKR Charge Fail Breaker Charge Fail
0xABC0 HI Ambient Temp High Ambient Temperature Alarm
0xAC00 LO Ambient Temp Low Ambient Temperature Alarm
0xAC40 Self Test Alarm Self Test Alarm
0xACC0 BKRTrpCntrAlrm Breaker Trip Control Alarm
0xAD00 Rly1 Coil Mn Alrm Relay # 1 Coil Monitor Alarm
0xAD40 Rly2 Coil Mn Alrm Relay # 2 Coil Monitor Alarm
0xAD80 BKR Fail Alrm BKR Fail Alrm
0xADC0 BKRStatus Fail Breaker Status Fail
0xAE40 CLP Alarm Cold Load PKP Alarm
0xAE80 Dir Pwr 1 Alarm Directional Pwr 1 Alarm
0xAEC0 Dir Pwr 2 Alarm Directional Pwr 2 Alarm
0xAF00 2nd Hrmc Alarm 2nd Harmonic Alarm
0xAF80 Fuse Fail Alrm Fuse Fail Alrm
0xAFC0 Brkn Cond Alarm Broken Cond Alarm
0xB000 Ph IOC1 Alarm Phase IOC 1 Alarm
0xB040 Ntrl IOC1 Alarm Neutral IOC 1 Alarm
0xB080 Gnd IOC1 Alarm Ground IOC 1 Alarm
0xB0C0 Ph TOC1 Alarm Phase TOC 1 Alarm
0xB100 Ntrl TOC1 Alrm Neutral TOC 1 Alarm
0xB140 Gnd TOC1 Alarm Ground TOC 1 Alarm
0xB180 Ph IOC2 Alarm Phase IOC 2 Alarm
0xB1C0 Ntrl IOC2 Alarm Neutral IOC 2 Alarm
0xB200 Gnd IOC2 Alarm Ground IOC 2 Alarm
0xB300 SGnd TOC1 Alarm Sensitive Ground TOC 1 Alarm
0xB340 NtrlDir RevAlm Neutral Directional Alarm
0xB3C0 NSeq OV Alarm Negative Sequence OV Alarm
0xB400 Ntrl OV Alarm Neutral OV Alarm
0xB440 Ph OV1 Alarm Phase OV 1 Alarm
0xB480 Ph UV1 Alarm Phase UV 1 Alarm
0xB4C0 Aux OV Alarm Auxiliary OV Alarm
0xB500 Aux UV Alarm Auxiliary UV Alarm
0xB540 UndrFreq1 Alarm Underfrequency 1 Alarm
0xB580 UndrFreq2 Alarm Underfrequency 2 Alarm
0xB5C0 OverFreq1 Alrm Overfrequency 1 Alarm

12-136 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xB600 OverFreq2 Alrm Overfrequency 2 Alarm
0xB640 SGnd IOC1 Alarm Sensitive Ground IOC 1 Alarm
0xB680 SGnd IOC2 Alarm Sensitive Ground IOC 2 Alarm
0xB6C0 NSeq IOC Alrm Negative Sequence IOC Alarm
0xB700 Ph UV2 Alarm Phase UV 2 Alarm
0xB740 Ph UV3 Alarm Phase UV 3 Alarm
0xB780 Ph UV4 Alarm Phase UV 4 Alarm
0xB7C0 NSeq OV2 Alrm Negative Sequence OV2 Alrm
0xB800 NSeq TOC1 Alarm Negative Sequence TOC 1 Alarm
0xB880 CTFail Alrm CT Fail Alarm
0xB8C0 Ph OV2 Alarm Ph OV2 Alarm
0xB900 Ph OV3 Alarm Ph OV3 Alarm
0xB940 Ph OV4 Alarm Ph OV4 Alarm
0xB980 Ntrl OV2 Alarm Neutral OV 2 Alarm
0xB9C0 Ntrl OV3 Alarm Neutral OV 3 Alarm
0xBA00 Ntrl OV4 Alarm Neutral OV 4 Alarm
0xBA40 OverFreq3 Alarm Overfrequency 3 Alarm
0xBA80 OverFreq4 Alarm Overfrequency 4 Alarm
0xBAC0 UndFreq3 Alarm Underfrequency 3 Alarm
0xBB00 UndFreq4 Alarm Underfrequency 4 Alarm
0xBC00 LE 9 Alarm Logic Element 9 Alarm
0xBC40 LE 10 Alarm Logic Element 10 Alarm
0xBC80 LE 11 Alarm Logic Element 11 Alarm
0xBCC0 LE 12 Alarm Logic Element 12 Alarm
0xBD00 LE 13 Alarm Logic Element 13 Alarm
0xBD40 LE 14 Alarm Logic Element 14 Alarm
0xBD80 LE 15 Alarm Logic Element 15 Alarm
0xBDC0 LE 16 Alarm Logic Element 16 Alarm
0xBE00 PhDir RevAlm Ph Directional Reverse Alarm
0xBE40 PhDir UndAlm Ph Directional Und Alarm
0xBE80 GndDir UndAlm Ground Directional Und Alarm
0xBEC0 NtrlDir UndAlm Neutral Directional Und Alarm
0xBF00 WGF 1 Alarm Wattmetric Gnd Fault 1 Alarm
0xBF40 WGF 2 Alarm Wattmetric Gnd Fault 2 Alarm
0xC040 Output Relay 3 Output Relay 3
0xC080 Output Relay 4 Output Relay 4
0xC0C0 Output Relay 5 Output Relay 5
0xC100 Output Relay 6 Output Relay 6
0xC140 Output Relay 7 Output Relay 7
0xC180 Relay1 Coil Relay # 1 Coil
0xC1C0 Relay2 Coil Relay # 2 Coil
0xC240 Arc Flash Arc Flash
0xC2C0 Lockout Lockout
0xC300 Sync Operation Synchrocheck Operation
0xC340 Sync Close OP Synchrocheck Close OP
0xC380 Sync Condition Synchrocheck Condition
0xC440 HS Phase IOC HS Phase IOC

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-137


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xC480 HS Gnd IOC HS Gnd IOC
0xC4C0 LE 1 LE 1
0xC500 LE 2 LE 2
0xC540 LE 3 LE 3
0xC580 LE 4 LE 4
0xC5C0 LE 5 LE 5
0xC600 LE 6 LE 6
0xC640 LE 7 LE 7
0xC680 LE 8 LE 8
0xC6C0 DeadBus >= LiveBus DeadBus >= LiveBus
0xC700 DeadLine>=LiveLine DeadLine >= LiveLine
0xC740 Testing Testing
0xC880 Setpoint Group2 Setpoint Group2
0xC900 Open BKR Open Breaker
0xC940 Close BKR Close Breaker
0xC980 Maint Required Maint Required
0xCA00 52a Contact 52a Contact
0xCA40 52b Contact 52b Contact
0xCA80 Reset OK Reset OK
0xCAC0 L/O Rst Closed Lockout Reset Closed
0xCB00 AR Close AR Close
0xCB40 AR N/Ready AR N/Ready
0xCB80 AR In Progress AR In Progress
0xCBC0 AR Disabled AR Disabled
0xCC00 AR Ext. Init AR Ext. Init
0xCC40 AR Ready AR Ready
0xCCC0 BKR Stat Open Breaker Status Open
0xCD00 BKR Stat Clsd Breaker Status Closed
0xCD40 Setpoint Group1 Setpoint Group1
0xCD80 Light Sensor 1 Light Sensor 1
0xCDC0 Light Sensor 2 Light Sensor 2
0xCE80 Dir Pwr 1 Directional Pwr 1
0xCEC0 Dir Pwr 2 Directional Pwr 2
0xCF00 2nd Hrmc 2nd Harmonic
0xCF40 Light Sensor 3 Light Sensor 3
0xCF80 Light Sensor 4 Light Sensor 4
0xCFC0 Brkn Cond Broken Cond
0xD340 Ntrl Dir Rev Neutral Directional Rev
0xD380 Gnd Dir Ground Directional
0xD700 Ph UV2 Phase UV 2
0xD740 Ph UV3 Phase UV 3
0xD780 Ph UV4 Phase UV 4
0xD8C0 Ph OV2 Ph OV2
0xD900 Ph OV3 Ph OV3
0xD940 Ph OV4 Ph OV4
0xDC00 LE 9 LE 9
0xDC40 LE 10 LE 10

12-138 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xDC80 LE 11 LE 11
0xDCC0 LE 12 LE 12
0xDD00 LE 13 LE 13
0xDD40 LE 14 LE 14
0xDD80 LE 15 LE 15
0xDDC0 LE 16 LE 16
0xDE00 PhDir Rev Ph Directional Reverse
0xDE40 PhDir Und Ph Directional Und
0xDE80 GndDir Und Ground Directional Und
0xDEC0 NtrlDir Und Neutral Directional Und
0xDF00 WGF 1 Wattmetric Gnd Fault 1
0xDF40 WGF 2 Wattmetric Gnd Fault 2
0xE040 Therm O/L Block Thermal Level Block
0xE080 PosSeq UV1 Block Positive Sequence UV 1 Block
0xE180 Output Relay 1 BLK Output Relay 1 BLK
0xE1C0 Output Relay 2 BLK Output Relay 2 BLK
0xE240 Arc Flash Block Arc Flash Block
0xE2C0 Lockout Block Lockout Block
0xE3C0 Volt Hz Block Volt Hz Block
0xE440 LightSns Trbl Blk Light Sensor Trouble Block
0xE740 Curr Dmd1 Block Current Demand 1 Block
0xE780 RealPwr Dmd Block Real Power Demand Block
0xE7C0 ReacPwr Dmd Block Reactive Power Demand Block
0xE800 AppPwr Dmd Block Apparent Power Demand Block
0xE880 Group Change Blk Group Change Blk
0xEB00 AR Block AR Block
0xEE80 Dir Pwr 1 Block Directional Pwr 1 Block
0xEEC0 Dir Pwr 2 Block Directional Pwr 2 Block
0xEF00 2nd Hrmc Block 2nd Harmonic Block
0xEFC0 Brkn Cond Block Broken Cond Block
0xF000 Ph IOC1 Block Phase IOC 1 Block
0xF040 Ntrl IOC1 Block Neutral IOC 1 Block
0xF080 Gnd IOC1 Block Ground IOC 1 Block
0xF0C0 Ph TOC1 Block Phase TOC 1 Block
0xF100 Ntrl TOC1 Block Neutral TOC 1 Block
0xF140 Gnd TOC1 Block Ground TOC 1 Block
0xF180 Ph IOC2 Block Phase IOC 2 Block
0xF1C0 Ntrl IOC2 Block Neutral IOC 2 Block
0xF200 Gnd IOC2 Block Ground IOC 2 Block
0xF300 SGnd TOC1 Block Sensitive Ground TOC 1 Block
0xF340 Ntrl Dir Rev Block Neutral Directional Block
0xF380 Gnd Dir Block Ground Directional Block
0xF3C0 NSeq OV Block Negative Sequence OV Block
0xF400 Ntrl OV Block Neutral OV Block
0xF440 Ph OV1 Block Phase OV 1 Block
0xF480 Ph UV1 Block Phase UV 1 Block
0xF4C0 Aux OV Block Auxiliary OV Block

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-139


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xF500 Aux UV Block Auxiliary UV Block
0xF540 UndrFreq1 Block Underfrequency 1 Block
0xF580 UndrFreq2 Block Underfrequency 2 Block
0xF5C0 OverFreq1 Block Overfrequency 1 Block
0xF600 OverFreq2 Block Overfrequency 2 Block
0xF640 SGnd IOC1 Block Sensitive Ground IOC 1 Block
0xF680 SGnd IOC2 Block Sensitive Ground IOC 2 Block
0xF6C0 NSeq IOC Block Negative Sequence IOC Block
0xF700 Ph UV2 Block Phase UV 2 Block OP
0xF740 Ph UV3 Block Phase UV 3 Block OP
0xF780 Ph UV4 Block Phase UV 4 Block OP
0xF7C0 NSeq OV2 Blk Negative Sequence OV2 Blk
0xF800 NSeq TOC1 Block Negative Sequence TOC 1 Block
0xF880 CTFail Block CT Fail Block
0xF8C0 Ph OV2 Block Ph OV2 Block
0xF900 Ph OV3 Block Ph OV3 Block
0xF940 Ph OV4 Block Ph OV4 Block
0xF980 Ntrl OV2 Block Neutral OV 2 Block
0xF9C0 Ntrl OV3 Block Neutral OV 3 Block
0xFA00 Ntrl OV4 Block Neutral OV 4 Block
0xFA40 OverFreq3 Block Overfrequency 3 Block
0xFA80 OverFreq4 Block Overfrequency 4 Block
0xFAC0 UndFreq3 Block Underfrequency 3 Block
0xFB00 UndFreq4 Block Underfrequency 4 Block
0xFE00 PhDir Block Ph Directional Block
0xFF00 WGF 1 Block Wattmetric Gnd Fault 1 Block
0xFF40 WGF 2 Block Wattmetric Gnd Fault 2 Block
FC134B unsigned 16 bits DNP Binary Inputs
0 Off Off
0x0001 On On
0x0040 Contact IN 1 On Contact Input 1 On
0x0041 Contact IN 2 On Contact Input 2 On
0x0042 Contact IN 3 On Contact Input 3 On
0x0043 Contact IN 4 On Contact Input 4 On
0x0044 Contact IN 5 On Contact Input 5 On
0x0045 Contact IN 6 On Contact Input 6 On
0x0046 Contact IN 7 On Contact Input 7 On
0x0047 Contact IN 8 On Contact Input 8 On
0x0048 Contact IN 9 On Contact Input 9 On
0x0049 Contact IN 10 On Contact Input 10 On
0x0060 Contact IN 1 Off Contact Input 1 Off
0x0061 Contact IN 2 Off Contact Input 2 Off
0x0062 Contact IN 3 Off Contact Input 3 Off
0x0063 Contact IN 4 Off Contact Input 4 Off
0x0064 Contact IN 5 Off Contact Input 5 Off
0x0065 Contact IN 6 Off Contact Input 6 Off
0x0066 Contact IN 7 Off Contact Input 7 Off

12-140 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x0067 Contact IN 8 Off Contact Input 8 Off
0x0068 Contact IN 9 Off Contact Input 9 Off
0x0069 Contact IN 10 Off Contact Input 10 Off
0x0080 Virtual IN 1 On Virtual Input 1 On
0x0081 Virtual IN 2 On Virtual Input 2 On
0x0082 Virtual IN 3 On Virtual Input 3 On
0x0083 Virtual IN 4 On Virtual Input 4 On
0x0084 Virtual IN 5 On Virtual Input 5 On
0x0085 Virtual IN 6 On Virtual Input 6 On
0x0086 Virtual IN 7 On Virtual Input 7 On
0x0087 Virtual IN 8 On Virtual Input 8 On
0x0088 Virtual IN 9 On Virtual Input 9 On
0x0089 Virtual IN 10 On Virtual Input 10 On
0x008A Virtual IN 11 On Virtual Input 11 On
0x008B Virtual IN 12 On Virtual Input 12 On
0x008C Virtual IN 13 On Virtual Input 13 On
0x008D Virtual IN 14 On Virtual Input 14 On
0x008E Virtual IN 15 On Virtual Input 15 On
0x008F Virtual IN 16 On Virtual Input 16 On
0x0090 Virtual IN 17 On Virtual Input 17 On
0x0091 Virtual IN 18 On Virtual Input 18 On
0x0092 Virtual IN 19 On Virtual Input 19 On
0x0093 Virtual IN 20 On Virtual Input 20 On
0x0094 Virtual IN 21 On Virtual Input 21 On
0x0095 Virtual IN 22 On Virtual Input 22 On
0x0096 Virtual IN 23 On Virtual Input 23 On
0x0097 Virtual IN 24 On Virtual Input 24 On
0x0098 Virtual IN 25 On Virtual Input 25 On
0x0099 Virtual IN 26 On Virtual Input 26 On
0x009A Virtual IN 27 On Virtual Input 27 On
0x009B Virtual IN 28 On Virtual Input 28 On
0x009C Virtual IN 29 On Virtual Input 29 On
0x009D Virtual IN 30 On Virtual Input 30 On
0x009E Virtual IN 31 On Virtual Input 31 On
0x009F Virtual IN 32 On Virtual Input 32 On
0x01C0 Remote IN 1 On Remote Input 1 On
0x01C1 Remote IN 2 On Remote Input 2 On
0x01C2 Remote IN 3 On Remote Input 3 On
0x01C3 Remote IN 4 On Remote Input 4 On
0x01C4 Remote IN 5 On Remote Input 5 On
0x01C5 Remote IN 6 On Remote Input 6 On
0x01C6 Remote IN 7 On Remote Input 7 On
0x01C7 Remote IN 8 On Remote Input 8 On
0x01C8 Remote IN 9 On Remote Input 9 On
0x01C9 Remote IN 10 On Remote Input 10 On
0x01CA Remote IN 11 On Remote Input 11 On
0x01CB Remote IN 12 On Remote Input 12 On

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-141


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x01CC Remote IN 13 On Remote Input 13 On
0x01CD Remote IN 14 On Remote Input 14 On
0x01CE Remote IN 15 On Remote Input 15 On
0x01CF Remote IN 16 On Remote Input 16 On
0x01D0 Remote IN 17 On Remote Input 17 On
0x01D1 Remote IN 18 On Remote Input 18 On
0x01D2 Remote IN 19 On Remote Input 19 On
0x01D3 Remote IN 20 On Remote Input 20 On
0x01D4 Remote IN 21 On Remote Input 21 On
0x01D5 Remote IN 22 On Remote Input 22 On
0x01D6 Remote IN 23 On Remote Input 23 On
0x01D7 Remote IN 24 On Remote Input 24 On
0x01D8 Remote IN 25 On Remote Input 25 On
0x01D9 Remote IN 26 On Remote Input 26 On
0x01DA Remote IN 27 On Remote Input 27 On
0x01DB Remote IN 28 On Remote Input 28 On
0x01DC Remote IN 29 On Remote Input 29 On
0x01DD Remote IN 30 On Remote Input 30 On
0x01DE Remote IN 31 On Remote Input 31 On
0x01DF Remote IN 32 On Remote Input 32 On
0x01E0 Remote IN 1 Off Remote Input 1 Off
0x01E1 Remote IN 2 Off Remote Input 2 Off
0x01E2 Remote IN 3 Off Remote Input 3 Off
0x01E3 Remote IN 4 Off Remote Input 4 Off
0x01E4 Remote IN 5 Off Remote Input 5 Off
0x01E5 Remote IN 6 Off Remote Input 6 Off
0x01E6 Remote IN 7 Off Remote Input 7 Off
0x01E7 Remote IN 8 Off Remote Input 8 Off
0x01E8 Remote IN 9 Off Remote Input 9 Off
0x01E9 Remote IN 10 Off Remote Input 10 Off
0x01EA Remote IN 11 Off Remote Input 11 Off
0x01EB Remote IN 12 Off Remote Input 12 Off
0x01EC Remote IN 13 Off Remote Input 13 Off
0x01ED Remote IN 14 Off Remote Input 14 Off
0x01EE Remote IN 15 Off Remote Input 15 Off
0x01EF Remote IN 16 Off Remote Input 16 Off
0x01F0 Remote IN 17 Off Remote Input 17 Off
0x01F1 Remote IN 18 Off Remote Input 18 Off
0x01F2 Remote IN 19 Off Remote Input 19 Off
0x01F3 Remote IN 20 Off Remote Input 20 Off
0x01F4 Remote IN 21 Off Remote Input 21 Off
0x01F5 Remote IN 22 Off Remote Input 22 Off
0x01F6 Remote IN 23 Off Remote Input 23 Off
0x01F7 Remote IN 24 Off Remote Input 24 Off
0x01F8 Remote IN 25 Off Remote Input 25 Off
0x01F9 Remote IN 26 Off Remote Input 26 Off
0x01FA Remote IN 27 Off Remote Input 27 Off

12-142 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x01FB Remote IN 28 Off Remote Input 28 Off
0x01FC Remote IN 29 Off Remote Input 29 Off
0x01FD Remote IN 30 Off Remote Input 30 Off
0x01FE Remote IN 31 Off Remote Input 31 Off
0x01FF Remote IN 32 Off Remote Input 32 Off
0x06C6 Clock Not Set Clock Not Set
0x06C9 Relay Not Ready Relay Not Ready
0x06CA IRIG-B Failure IRIG-B Failure
0x06CE Ethernet Link Fail Ethernet Link Failure
0x06D0 Intern Temp. >80C Internal Temperature High
0x06D5 Eth Link A Fail Ethernet Link A Fail
0x06D6 Eth Link B Fail Ethernet Link B Fail
0x06E0 Order Code Error Order Code Error
0x06E1 RTC Error RTC Error
0x06E2 Cal Error Cal Error
0x06E3 EEPROM Error EEPROM Error
0x06E4 Sys Health Error Sys Health Error
0x06E5 CPU 33V Error CPU 33V Error
0x06E6 Analog V Rail Fail Analog Voltage Rail Fail
0x8002 Any Trip Any Trip
0x8042 Therm O/L Trip OP Thermal Overload Trip OP
0x8044 Therm O/L Trip DPO Thermal Overload Trip DPO
0x804A Therm PhA Trip OP Thermal Phase A Trip OP
0x804C Therm PhA Trip DPO Thermal Phase A Trip DPO
0x8052 Therm PhB Trip OP Thermal Phase B Trip OP
0x8054 Therm PhB Trip DPO Thermal Phase B Trip DPO
0x8062 Therm PhC Trip OP Thermal Phase C Trip OP
0x8064 Therm PhC Trip DPO Thermal Phase C Trip DPO
0x8081 PosSeq UV1 Trp PKP Positive Sequence UV 1 Trp PKP
0x8082 PosSeq UV1 Trip OP Positive Sequence UV 1 Trip OP
0x8084 PosSeq UV1 Trp DPO Positive Sequence UV 1 Trp DPO
0x8242 Arc Flash Trip OP Arc Flash Trip OP
0x83C1 Volt Hz Trip PKP Volt Hz Trip PKP
0x83C2 Volt Hz Trip OP Volt Hz Trip OP
0x83C4 Volt Hz Trip DPO Volt Hz Trip DPO
0x84C1 LE 1 Trip PKP Logic Element 1 Trip PKP
0x84C2 LE 1 Trip OP Logic Element 1 Trip OP
0x84C4 LE 1 Trip DPO Logic Element 1 Trip DPO
0x8501 LE 2 Trip PKP Logic Element 2 Trip PKP
0x8502 LE 2 Trip OP Logic Element 2 Trip OP
0x8504 LE 2 Trip DPO Logic Element 2 Trip DPO
0x8541 LE 3 Trip PKP Logic Element 3 Trip PKP
0x8542 LE 3 Trip OP Logic Element 3 Trip OP
0x8544 LE 3 Trip DPO Logic Element 3 Trip DPO
0x8581 LE 4 Trip PKP Logic Element 4 Trip PKP
0x8582 LE 4 Trip OP Logic Element 4 Trip OP
0x8584 LE 4 Trip DPO Logic Element 4 Trip DPO

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-143


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x85C1 LE 5 Trip PKP Logic Element 5 Trip PKP
0x85C2 LE 5 Trip OP Logic Element 5 Trip OP
0x85C4 LE 5 Trip DPO Logic Element 5 Trip DPO
0x8601 LE 6 Trip PKP Logic Element 6 Trip PKP
0x8602 LE 6 Trip OP Logic Element 6 Trip OP
0x8604 LE 6 Trip DPO Logic Element 6 Trip DPO
0x8641 LE 7 Trip PKP Logic Element 7 Trip PKP
0x8642 LE 7 Trip OP Logic Element 7 Trip OP
0x8644 LE 7 Trip DPO Logic Element 7 Trip DPO
0x8681 LE 8 Trip PKP Logic Element 8 Trip PKP
0x8682 LE 8 Trip OP Logic Element 8 Trip OP
0x8684 LE 8 Trip DPO Logic Element 8 Trip DPO
0x89C2 Self Test OP Self Test OP
0x8E81 Dir Pwr 1 Trip PKP Directional Pwr 1 Trip PKP
0x8E82 Dir Pwr 1 Trip OP Directional Pwr 1 Trip OP
0x8EC1 Dir Pwr 2 Trip PKP Directional Pwr 2 Trip PKP
0x8EC2 Dir Pwr 2 Trip OP Directional Pwr 2 Trip OP
0x8F81 Fuse Fail Trip PKP Fuse Fail Trip PKP
0x8F82 Fuse Fail Trip OP Fuse Fail Trip OP
0x8F84 Fuse Fail Trip DPO Fuse Fail Trip DPO
0x8FC1 Brkn Cond Trip PKP Broken Cond Trip PKP
0x8FC2 Brkn Cond Trip OP Broken Cond Trip OP
0x8FC4 Brkn Cond Trip DPO Broken Cond Trip DPO
0x9001 Ph IOC1 Trip PKP Phase IOC 1 Trip PKP
0x9002 Ph IOC1 Trip OP Phase IOC 1 Trip OP
0x9004 Ph IOC1 Trip DPO Phase IOC 1 Trip DPO
0x9009 Ph A IOC1 Trip PKP Phase A IOC 1 Trip PKP
0x900A Ph A IOC1 Trip OP Phase A IOC 1 Trip OP
0x900C Ph A IOC1 Trip DPO Phase A IOC 1 Trip DPO
0x9011 Ph B IOC1 Trip PKP Phase B IOC 1 Trip PKP
0x9012 Ph B IOC1 Trip OP Phase B IOC 1 Trip OP
0x9014 Ph B IOC1 Trip DPO Phase B IOC 1 Trip DPO
0x9021 Ph C IOC1 Trip PKP Phase C IOC 1 Trip PKP
0x9022 Ph C IOC1 Trip OP Phase C IOC 1 Trip OP
0x9024 Ph C IOC1 Trip DPO Phase C IOC 1 Trip DPO
0x9041 Ntrl IOC1 Trip PKP Neutral IOC 1 Trip PKP
0x9042 Ntrl IOC1 Trip OP Neutral IOC 1 Trip OP
0x9044 Ntrl IOC1 Trip DPO Neutral IOC 1 Trip DPO
0x9081 Gnd IOC1 Trip PKP Ground IOC 1 Trip PKP
0x9082 Gnd IOC1 Trip OP Ground IOC 1 Trip OP
0x9084 Gnd IOC1 Trip DPO Ground IOC 1 Trip DPO
0x90C1 Ph TOC1 Trip PKP Phase TOC 1 Trip PKP
0x90C2 Ph TOC1 Trip OP Phase TOC 1 Trip OP
0x90C4 Ph TOC1 Trip DPO Phase TOC 1 Trip DPO
0x90C9 Ph A TOC1 Trip PKP Phase A TOC 1 Trip PKP
0x90CA Ph A TOC1 Trip OP Phase A TOC 1 Trip OP
0x90CC Ph A TOC1 Trip DPO Phase A TOC 1 Trip DPO

12-144 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x90D1 Ph B TOC1 Trip PKP Phase B TOC 1 Trip PKP
0x90D2 Ph B TOC1 Trip OP Phase B TOC 1 Trip OP
0x90D4 Ph B TOC1 Trip DPO Phase B TOC 1 Trip DPO
0x90E1 Ph C TOC1 Trip PKP Phase C TOC 1 Trip PKP
0x90E2 Ph C TOC1 Trip OP Phase C TOC 1 Trip OP
0x90E4 Ph C TOC1 Trip DPO Phase C TOC 1 Trip DPO
0x9101 Ntrl TOC1 Trip PKP Neutral TOC 1 Trip PKP
0x9102 Ntrl TOC1 Trip OP Neutral TOC 1 Trip OP
0x9104 Ntrl TOC1 Trip DPO Neutral TOC 1 Trip DPO
0x9141 Gnd TOC1 Trip PKP Ground TOC Trip PKP
0x9142 Gnd TOC1 Trip OP Ground TOC 1 Trip OP
0x9144 Gnd TOC1 Trip DPO Ground TOC Trip DPO
0x9181 Ph IOC2 Trip PKP Phase IOC 2 Trip PKP
0x9182 Ph IOC2 Trip OP Phase IOC 2 Trip OP
0x9184 Ph IOC2 Trip DPO Phase IOC 2 Trip DPO
0x9189 Ph A IOC2 Trip PKP Phase A IOC 2 Trip PKP
0x918A Ph A IOC2 Trip OP Phase A IOC 2 Trip OP
0x918C Ph A IOC2 Trip DPO Phase A IOC 2 Trip DPO
0x9191 Ph B IOC2 Trip PKP Phase B IOC 2 Trip PKP
0x9192 Ph B IOC2 Trip OP Phase B IOC 2 Trip OP
0x9194 Ph B IOC2 Trip DPO Phase B IOC 2 Trip DPO
0x91A1 Ph C IOC2 Trip PKP Phase C IOC 2 Trip PKP
0x91A2 Ph C IOC2 Trip OP Phase C IOC 2 Trip OP
0x91A4 Ph C IOC2 Trip DPO Phase C IOC 2 Trip DPO
0x91C1 Ntrl IOC2 Trip PKP Neutral IOC 2 Trip PKP
0x91C2 Ntrl IOC2 Trip OP Neutral IOC 2 Trip OP
0x91C4 Ntrl IOC2 Trip DPO Neutral IOC 2 Trip DPO
0x9201 Gnd IOC2 Trip PKP Ground IOC 2 Trip PKP
0x9202 Gnd IOC2 Trip OP Ground IOC 2 Trip OP
0x9204 Gnd IOC2 Trip DPO Ground IOC 2 Trip DPO
0x9301 SGnd TOC1 Trip PKP Sensitive Ground TOC 1 Trip PKP
0x9302 SGnd TOC1 Trip OP Sensitive Ground TOC 1 Trip OP
0x9304 SGnd TOC1 Trip DPO Sensitive Ground TOC 1 Trip DPO
0x93C1 NSeq OV Trp PKP Negative Sequence OV Trip PKP
0x93C2 NSeq OV Trp OP Negative Sequence OV Trip OP
0x93C4 NSeq OV Trp DPO Negative Sequence OV Trip DPO
0x9401 Ntrl OV Trip PKP Neutral OV Trip PKP
0x9402 Ntrl OV Trp OP Neutral OV Trip OP
0x9404 Ntrl OV Trip DPO Neutral OV Trip DPO
0x9441 Ph OV1 Trip PKP Phase OV1 Trip PKP
0x9442 Ph OV1 Trip OP Phase OV 1 Trip OP
0x9444 Ph OV1 Trip DPO Phase OV1 Trip DPO
0x9449 Ph A OV1 Trip PKP Phase A OV1 Trip PKP
0x944A Ph A OV1 Trip OP Phase A OV1 Trip OP
0x944C Ph A OV1 Trip DPO Phase A OV1 Trip DPO
0x9451 Ph B OV1 Trip PKP Phase B OV1 Trip PKP
0x9452 Ph B OV1 Trip OP Phase B OV1 Trip OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-145


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x9454 Ph B OV1 Trip DPO Phase B OV1 Trip DPO
0x9461 Ph C OV1 Trip PKP Phase C OV1 Trip PKP
0x9462 Ph C OV1 Trip OP Phase C OV1 Trip OP
0x9464 Ph C OV1 Trip DPO Phase C OV1 Trip DPO
0x9481 Ph UV1 Trip PKP Phase UV1 Trip PKP
0x9482 Ph UV1 Trip OP Phase UV 1 Trip OP
0x9484 Ph UV1 Trip DPO Phase UV1 Trip DPO
0x9489 Ph A UV1 Trip PKP Phase A UV1 Trip PKP
0x948A Ph A UV1 Trip OP Phase A UV1 Trip OP
0x948C Ph A UV1 Trip DPO Phase A UV1 Trip DPO
0x9491 Ph B UV1 Trip PKP Phase B UV1 Trip PKP
0x9492 Ph B UV1 Trip OP Phase B UV1 Trip OP
0x9494 Ph B UV1 Trip DPO Phase B UV1 Trip DPO
0x94A1 Ph C UV1 Trip PKP Phase C UV1 Trip PKP
0x94A2 Ph C UV1 Trip OP Phase C UV1 Trip OP
0x94A4 Ph C UV1 Trip DPO Phase C UV1 Trip DPO
0x94C1 Aux OV Trip PKP Auxiliary OV Trip PKP
0x94C2 Aux OV Trip OP Auxiliary OV Trip OP
0x94C4 Aux OV Trip DPO Auxiliary OV Trip DPO
0x9501 Aux UV Trip PKP Auxiliary UV Trip PKP
0x9502 Aux UV Trip OP Auxiliary UV Trip OP
0x9504 Aux UV Trip DPO Auxiliary UV Trip DPO
0x9541 UndrFreq1 Trip PKP Underfrequency 1 Trip PKP
0x9542 UndrFreq1 Trip OP Underfrequency 1 Trip OP
0x9544 UndrFreq1 Trip DPO Underfrequency 1 Trip DPO
0x9581 UndrFreq2 Trip PKP Underfrequency 2 Trip PKP
0x9582 UndrFreq2 Trip OP Underfrequency 2 Trip OP
0x9584 UndrFreq2 Trip DPO Underfrequency 2 Trip DPO
0x95C1 OverFreq1 Trip PKP Overfrequency 1 Trip PKP
0x95C2 OverFreq1 Trip OP Overfrequency 1 Trip OP
0x95C4 OverFreq1 Trip DPO Overfrequency 1 Trip DPO
0x9601 OverFreq2 Trip PKP Overfrequency 2 Trip PKP
0x9602 OverFreq2 Trip OP Overfrequency 2 Trip OP
0x9604 OverFreq2 Trip DPO Overfrequency 2 Trip DPO
0x9641 SGnd IOC1 Trip PKP Sensitive Ground IOC 1 Trip PKP
0x9642 SGnd IOC1 Trip OP Sensitive Ground IOC 1 Trip OP
0x9644 SGnd IOC1 Trip DPO Sensitive Ground IOC 1 Trip DPO
0x9681 SGnd IOC2 Trip PKP Sensitive Ground IOC 2 Trip PKP
0x9682 SGnd IOC2 Trip OP Sensitive Ground IOC 2 Trip OP
0x9684 SGnd IOC2 Trip DPO Sensitive Ground IOC 2 Trip DPO
0x96C1 NSeq IOC Trp PKP Negative Sequence IOC Trip PKP
0x96C2 NSeq IOC Trp OP Negative Sequence IOC Trip OP
0x96C4 NSeq IOC Trp DPO Negative Sequence IOC Trip DPO
0x9701 Ph UV2 Trip PKP Phase UV 2 Trip PKP
0x9702 Ph UV2 Trip OP Phase UV 2 Trip OP
0x9704 Ph UV2 Trip DPO Phase UV 2 Trip DPO
0x9709 Ph A UV2 Trip PKP Phase A UV 2 Trip PKP

12-146 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x970A Ph A UV2 Trip OP Phase A UV 2 Trip OP
0x970C Ph A UV2 Trip DPO Phase A UV 2 Trip DPO
0x9711 Ph B UV2 Trip PKP Phase B UV 2 Trip PKP
0x9712 Ph B UV2 Trip OP Phase B UV 2 Trip OP
0x9714 Ph B UV2 Trip DPO Phase B UV 2 Trip DPO
0x9721 Ph C UV2 Trip PKP Phase C UV 2 Trip PKP
0x9722 Ph C UV2 Trip OP Phase C UV 2 Trip OP
0x9724 Ph C UV2 Trip DPO Phase C UV 2 Trip DPO
0x9741 Ph UV3 Trip PKP Phase UV 3 Trip PKP
0x9742 Ph UV3 Trip OP Phase UV 3 Trip OP
0x9744 Ph UV3 Trip DPO Phase UV 3 Trip DPO
0x9749 Ph A UV3 Trip PKP Phase A UV 3 Trip PKP
0x974A Ph A UV3 Trip OP Phase A UV 3 Trip OP
0x974C Ph A UV3 Trip DPO Phase A UV 3 Trip DPO
0x9751 Ph B UV3 Trip PKP Phase B UV 3 Trip PKP
0x9752 Ph B UV3 Trip OP Phase B UV 3 Trip OP
0x9754 Ph B UV3 Trip DPO Phase B UV 3 Trip DPO
0x9761 Ph C UV3 Trip PKP Phase C UV 3 Trip PKP
0x9762 Ph C UV3 Trip OP Phase C UV 3 Trip OP
0x9764 Ph C UV3 Trip DPO Phase C UV 3 Trip DPO
0x9781 Ph UV4 Trip PKP Phase UV 4 Trip PKP
0x9782 Ph UV4 Trip OP Phase UV 4 Trip OP
0x9784 Ph UV4 Trip DPO Phase UV 4 Trip DPO
0x9789 Ph A UV4 Trip PKP Phase A UV 4 Trip PKP
0x978A Ph A UV4 Trip OP Phase A UV 4 Trip OP
0x978C Ph A UV4 Trip DPO Phase A UV 4 Trip DPO
0x9791 Ph B UV4 Trip PKP Phase B UV 4 Trip PKP
0x9792 Ph B UV4 Trip OP Phase B UV 4 Trip OP
0x9794 Ph B UV4 Trip DPO Phase B UV 4 Trip DPO
0x97A1 Ph C UV4 Trip PKP Phase C UV 4 Trip PKP
0x97A2 Ph C UV4 Trip OP Phase C UV 4 Trip OP
0x97A4 Ph C UV4 Trip DPO Phase C UV 4 Trip DPO
0x97C1 NSeq OV2 Trp PKP Negative Sequence OV2 Trp PKP
0x97C2 NSeq OV2 Trp OP Negative Sequence OV2 Trp OP
0x97C4 NSeq OV2 Trp DPO Negative Sequence OV2 Trp DPO
0x9801 NSeq TOC1 Trip PKP Negative Sequence TOC 1 Trip PKP
0x9802 NSeq TOC1 Trip OP Negative Sequence TOC 1 Trip OP
0x9804 NSeq TOC1 Trip DPO Negative Sequence TOC 1 Trip DPO
0x98C1 Ph OV2 Trip PKP Phase OV 2 Trip PKP
0x98C2 Ph OV2 Trip OP Phase OV 2 Trip OP
0x98C4 Ph OV2 Trip DPO Phase OV 2 Trip DPO
0x98C9 Ph A OV2 Trip PKP Phase A OV2 Trip PKP
0x98CA Ph A OV2 Trip OP Phase A OV2 Trip OP
0x98CC Ph A OV2 Trip DPO Phase A OV2 Trip DPO
0x98D1 Ph B OV2 Trip PKP Phase B OV2 Trip PKP
0x98D2 Ph B OV2 Trip OP Phase B OV2 Trip OP
0x98D4 Ph B OV2 Trip DPO Phase B OV2 Trip DPO

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-147


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x98E1 Ph C OV2 Trip PKP Phase C OV2 Trip PKP
0x98E2 Ph C OV2 Trip OP Phase C OV2 Trip OP
0x98E4 Ph C OV2 Trip DPO Phase C OV2 Trip DPO
0x9901 Ph OV3 Trip PKP Phase OV 3 Trip PKP
0x9902 Ph OV3 Trip OP Phase OV 3 Trip OP
0x9904 Ph OV3 Trip DPO Phase OV 3 Trip DPO
0x9909 Ph A OV3 Trip PKP Phase A OV 3 Trip PKP
0x990A Ph A OV3 Trip OP Phase A OV 3 Trip OP
0x990C Ph A OV3 Trip DPO Phase A OV 3 Trip DPO
0x9911 Ph B OV3 Trip PKP Phase B OV 3 Trip PKP
0x9912 Ph B OV3 Trip OP Phase B OV 3 Trip OP
0x9914 Ph B OV3 Trip DPO Phase B OV 3 Trip DPO
0x9921 Ph C OV3 Trip PKP Phase C OV 3 Trip PKP
0x9922 Ph C OV3 Trip OP Phase C OV 3 Trip OP
0x9924 Ph C OV3 Trip DPO Phase C OV 3 Trip DPO
0x9941 Ph OV4 Trip PKP Phase OV 4 Trip PKP
0x9942 Ph OV4 Trip OP Phase OV 4 Trip OP
0x9944 Ph OV4 Trip DPO Phase OV 4 Trip DPO
0x9949 Ph A OV4 Trip PKP Phase A OV 4 Trip PKP
0x994A Ph A OV4 Trip OP Phase A OV 4 Trip OP
0x994C Ph A OV4 Trip DPO Phase A OV 4 Trip DPO
0x9951 Ph B OV4 Trip PKP Phase B OV 4 Trip PKP
0x9952 Ph B OV4 Trip OP Phase B OV 4 Trip OP
0x9954 Ph B OV4 Trip DPO Phase B OV 4 Trip DPO
0x9961 Ph C OV4 Trip PKP Phase C OV 4 Trip PKP
0x9962 Ph C OV4 Trip OP Phase C OV 4 Trip OP
0x9964 Ph C OV4 Trip DPO Phase C OV 4 Trip DPO
0x9981 Ntrl OV2 Trip PKP Neutral OV 2 Trip PKP
0x9982 Ntrl OV2 Trip OP Neutral OV 2 Trip OP
0x9984 Ntrl OV2 Trip DPO Neutral OV 2 Trip DPO
0x99C1 Ntrl OV3 Trip PKP Neutral OV 3 Trip PKP
0x99C2 Ntrl OV3 Trip OP Neutral OV 3 Trip OP
0x99C4 Ntrl OV3 Trip DPO Neutral OV 3 Trip DPO
0x9A01 Ntrl OV4 Trip PKP Neutral OV 4 Trip PKP
0x9A02 Ntrl OV4 Trip OP Neutral OV 4 Trip OP
0x9A04 Ntrl OV4 Trip DPO Neutral OV 4 Trip DPO
0x9A41 OverFreq3 Trip PKP Overfrequency 3 Trip PKP
0x9A42 OverFreq3 Trip OP Overfrequency 3 Trip OP
0x9A44 OverFreq3 Trip DPO Overfrequency 3 Trip DPO
0x9A81 OverFreq4 Trip PKP Overfrequency 4 Trip PKP
0x9A82 OverFreq4 Trip OP Overfrequency 4 Trip OP
0x9A84 OverFreq4 Trip DPO Overfrequency 4 Trip DPO
0x9AC1 UndFreq3 Trip PKP Underfrequency 3 Trip PKP
0x9AC2 UndFreq3 Trip OP Underfrequency 3 Trip OP
0x9AC4 UndFreq3 Trip DPO Underfrequency 3 Trip DPO
0x9B01 UndFreq4 Trip PKP Underfrequency 4 Trip PKP
0x9B02 UndFreq4 Trip OP Underfrequency 4 Trip OP

12-148 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x9B04 UndFreq4 Trip DPO Underfrequency 4 Trip DPO
0x9C01 LE 9 Trip PKP Logic Element 9 Trip PKP
0x9C02 LE 9 Trip OP Logic Element 9 Trip OP
0x9C04 LE 9 Trip DPO Logic Element 9 Trip DPO
0x9C41 LE 10 Trip PKP Logic Element 10 Trip PKP
0x9C42 LE 10 Trip OP Logic Element 10 Trip OP
0x9C44 LE 10 Trip DPO Logic Element 10 Trip DPO
0x9C81 LE 11 Trip PKP Logic Element 11 Trip PKP
0x9C82 LE 11 Trip OP Logic Element 11 Trip OP
0x9C84 LE 11 Trip DPO Logic Element 11 Trip DPO
0x9CC1 LE 12 Trip PKP Logic Element 12 Trip PKP
0x9CC2 LE 12 Trip OP Logic Element 12 Trip OP
0x9CC4 LE 12 Trip DPO Logic Element 12 Trip DPO
0x9D01 LE 13 Trip PKP Logic Element 13 Trip PKP
0x9D02 LE 13 Trip OP Logic Element 13 Trip OP
0x9D04 LE 13 Trip DPO Logic Element 13 Trip DPO
0x9D41 LE 14 Trip PKP Logic Element 14 Trip PKP
0x9D42 LE 14 Trip OP Logic Element 14 Trip OP
0x9D44 LE 14 Trip DPO Logic Element 14 Trip DPO
0x9D81 LE 15 Trip PKP Logic Element 15 Trip PKP
0x9D82 LE 15 Trip OP Logic Element 15 Trip OP
0x9D84 LE 15 Trip DPO Logic Element 15 Trip DPO
0x9DC1 LE 16 Trip PKP Logic Element 16 Trip PKP
0x9DC2 LE 16 Trip OP Logic Element 16 Trip OP
0x9DC4 LE 16 Trip DPO Logic Element 16 Trip DPO
0x9F01 WGF 1 Trip PKP Wattmetric Gnd Fault 1 Trip PKP
0x9F02 WGF 1 Trip OP Wattmetric Gnd Fault 1 Trip OP
0x9F04 WGF 1 Trip DPO Wattmetric Gnd Fault 1 Trip DPO
0x9F41 WGF 2 Trip PKP Wattmetric Gnd Fault 2 Trip PKP
0x9F42 WGF 2 Trip OP Wattmetric Gnd Fault 2 Trip OP
0x9F44 WGF 2 Trip DPO Wattmetric Gnd Fault 2 Trip DPO
0xA002 Any Alarm Any Alarm
0xA042 Therm Lvl Alrm OP Thermal Level Alarm OP
0xA044 Therm Lvl Alrm DPO Thermal Level Alarm DPO
0xA04A Therm PhA Alrm OP Thermal Phase A Alarm OP
0xA04C Therm PhA Alrm DPO Thermal Phase A Alarm DPO
0xA052 Therm PhB Alrm OP Thermal Phase B Alarm OP
0xA054 Therm PhB Alrm DPO Thermal Phase B Alarm DPO
0xA062 Therm PhC Alrm OP Thermal Phase C Alarm OP
0xA064 Therm PhC Alrm DPO Thermal Phase C Alarm DPO
0xA081 PosSeq UV1 AlrmPKP Positive Sequence UV 1 Alarm PKP
0xA082 PosSeq UV1 Alrm OP Positive Sequence UV 1 Alarm OP
0xA084 PosSeq UV1 AlrmDPO Positive Sequence UV 1 Alarm DPO
0xA242 Arc Flash Alarm OP Arc Flash Alarm OP
0xA2C2 LightSns1 Trbl Light Sensor 1 Trouble
0xA302 LightSns2 Trbl Light Sensor 2 Trouble
0xA342 LightSns3 Trbl Light Sensor 3 Trouble

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-149


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xA382 LightSns4 Trbl Light Sensor 4 Trouble
0xA3C1 Volt Hz Alarm PKP Volt Hz Alarm PKP
0xA3C2 Volt Hz Alarm OP Volt Hz Alarm OP
0xA3C4 Volt Hz Alarm DPO Volt Hz Alarm DPO
0xA442 Light Sns Trbl Light Sensor Trouble
0xA4C1 LE 1 Alarm PKP Logic Element 1 Alarm PKP
0xA4C2 LE 1 Alarm OP Logic Element 1 Alarm OP
0xA4C4 LE 1 Alarm DPO Logic Element 1 Alarm DPO
0xA501 LE 2 Alarm PKP Logic Element 2 Alarm PKP
0xA502 LE 2 Alarm OP Logic Element 2 Alarm OP
0xA504 LE 2 Alarm DPO Logic Element 2 Alarm DPO
0xA541 LE 3 Alarm PKP Logic Element 3 Alarm PKP
0xA542 LE 3 Alarm OP Logic Element 3 Alarm OP
0xA544 LE 3 Alarm DPO Logic Element 3 Alarm DPO
0xA581 LE 4 Alarm PKP Logic Element 4 Alarm PKP
0xA582 LE 4 Alarm OP Logic Element 4 Alarm OP
0xA584 LE 4 Alarm DPO Logic Element 4 Alarm DPO
0xA5C1 LE 5 Alarm PKP Logic Element 5 Alarm PKP
0xA5C2 LE 5 Alarm OP Logic Element 5 Alarm OP
0xA5C4 LE 5 Alarm DPO Logic Element 5 Alarm DPO
0xA601 LE 6 Alarm PKP Logic Element 6 Alarm PKP
0xA602 LE 6 Alarm OP Logic Element 6 Alarm OP
0xA604 LE 6 Alarm DPO Logic Element 6 Alarm DPO
0xA641 LE 7 Alarm PKP Logic Element 7 Alarm PKP
0xA642 LE 7 Alarm OP Logic Element 7 Alarm OP
0xA644 LE 7 Alarm DPO Logic Element 7 Alarm DPO
0xA681 LE 8 Alarm PKP Logic Element 8 Alarm PKP
0xA682 LE 8 Alarm OP Logic Element 8 Alarm OP
0xA684 LE 8 Alarm DPO Logic Element 8 Alarm DPO
0xA742 Curr Dmd1 Alrm OP Current Demand 1 Alarm OP
0xA74A C Dmd1 PhA Alrm OP Current Demand 1 PhA Alarm OP
0xA752 C Dmd1 PhB Alrm OP Current Demand 1 PhB Alarm OP
0xA762 C Dmd1 PhC Alrm OP Current Demand 1 PhC Alarm OP
0xA782 RealP Dmd Alrm OP Real Power Demand Alarm OP
0xA7C2 ReacP Dmd Alrm OP Reactive Power Demand Alarm OP
0xA802 AppP Dmd Alrm OP Apparent Power Demand Alarm OP
0xAA02 BKR Alarm Breaker Alarm
0xAA42 BKR Trip Time Breaker Trip Time
0xAA82 BKR Close Time Breaker Close Time
0xAAC2 BKR Charge Time Breaker Charge Time
0xAB02 BKR Trp/Cls Fail Breaker Trip/Close Fail
0xAB42 BKR Charge Fail Breaker Charge Fail
0xABC1 HI Amb Temp PKP High Ambient Temperature Alarm PKP
0xABC2 HI Amb Temp OP High Ambient Temperature Alarm
0xABC4 HI Amb Temp DPO High Ambient Temperature Alarm DPO
0xAC01 LO Amb Temp PKP Low Ambient Temperature Alarm PKP
0xAC02 LO Amb Temp OP Low Ambient Temperature Alarm

12-150 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xAC04 LO Amb Temp DPO Low Ambient Temperature Alarm DPO
0xAC42 Self Test Alarm OP Self Test Alarm OP
0xACC2 BKRTrpCntrAlrm OP Breaker Trip Control Alarm OP
0xAD02 R1 CoilMonAlrm OP Trip Coil Monitor Alarm OP
0xAD42 R2 CoilMonAlrm OP Close Coil Monitor Alarm OP
0xAD81 BKR Fail Alrm PKP Breaker Fail Alarm PKP
0xAD82 BKR Fail Alrm OP Breaker Fail Alarm OP
0xAD84 BKR Fail Alrm DPO Breaker Fail Alarm DPO
0xADC2 BKR Stat Fail OP Breaker Status Fail OP
0xAE41 CLP Alarm PKP Cold Load PKP Alarm PKP
0xAE42 CLP Alarm OP Cold Load PKP Alarm OP
0xAE81 Dir Pwr 1 Alrm PKP Directional Pwr 1 Alarm PKP
0xAE82 Dir Pwr 1 Alarm OP Directional Pwr 1 Alarm OP
0xAEC1 Dir Pwr 2 Alrm PKP Directional Pwr 2 Alarm PKP
0xAEC2 Dir Pwr 2 Alarm OP Directional Pwr 2 Alarm OP
0xAF01 2nd Hrmc Alarm PKP 2nd Harmonic Alarm PKP
0xAF02 2nd Hrmc Alarm OP 2nd Harmonic Alarm OP
0xAF04 2nd Hrmc Alarm DPO 2nd Harmonic Alarm DPO
0xAF81 Fuse Fail Alrm PKP Fuse Fail Alarm PKP
0xAF82 Fuse Fail Alrm OP Fuse Fail Alarm OP
0xAF84 Fuse Fail Alrm DPO Fuse Fail Alarm DPO
0xAFC1 Brkn Cond Alrm PKP Broken Cond Alarm PKP
0xAFC2 Brkn Cond Alarm OP Broken Cond Alarm OP
0xAFC4 Brkn Cond Alrm DPO Broken Cond Alarm DPO
0xB001 Ph IOC1 Alarm PKP Phase IOC 1 Alarm PKP
0xB002 Ph IOC1 Alarm OP Phase IOC 1 Alarm OP
0xB004 Ph IOC1 Alarm DPO Phase IOC 1 Alarm DPO
0xB009 Ph A IOC1 Alrm PKP Phase A IOC 1 Alarm PKP
0xB00A Ph A IOC1 Alrm OP Phase A IOC 1 Alarm OP
0xB00C Ph A IOC1 Alrm DPO Phase A IOC 1 Alarm DPO
0xB011 Ph B IOC1 Alrm PKP Phase B IOC 1 Alarm PKP
0xB012 Ph B IOC1 Alrm OP Phase B IOC 1 Alarm OP
0xB014 Ph B IOC1 Alrm DPO Phase B IOC 1 Alarm DPO
0xB021 Ph C IOC1 Alrm PKP Phase C IOC 1 Alarm PKP
0xB022 Ph C IOC1 Alrm OP Phase C IOC 1 Alarm OP
0xB024 Ph C IOC1 Alrm DPO Phase C IOC 1 Alarm DPO
0xB041 Ntrl IOC1 Alrm PKP Neutral IOC 1 Alarm PKP
0xB042 Ntrl IOC1 Alrm OP Neutral IOC 1 Alarm OP
0xB044 Ntrl IOC1 Alrm DPO Neutral IOC 1 Alarm DPO
0xB081 Gnd IOC1 Alarm PKP Ground IOC 1 Alarm PKP
0xB082 Gnd IOC1 Alarm OP Ground IOC 1 Alarm OP
0xB084 Gnd IOC1 Alarm DPO Ground IOC 1 Alarm DPO
0xB0C1 Ph TOC1 Alarm PKP Phase TOC 1 Alarm PKP
0xB0C2 Ph TOC1 Alarm OP Phase TOC 1 Alarm OP
0xB0C4 Ph TOC1 Alarm DPO Phase TOC 1 Alarm DPO
0xB0C9 Ph A TOC1 Alrm PKP Phase A TOC 1 Alarm PKP
0xB0CA Ph A TOC1 Alrm OP Phase A TOC 1 Alarm OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-151


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xB0CC Ph A TOC1 Alrm DPO Phase A TOC 1 Alarm DPO
0xB0D1 Ph B TOC1 Alrm PKP Phase B TOC 1 Alarm PKP
0xB0D2 Ph B TOC1 Alrm OP Phase B TOC 1 Alarm OP
0xB0D4 Ph B TOC1 Alrm DPO Phase B TOC 1 Alarm DPO
0xB0E1 Ph C TOC1 Alrm PKP Phase C TOC 1 Alarm PKP
0xB0E2 Ph C TOC1 Alrm OP Phase C TOC 1 Alarm OP
0xB0E4 Ph C TOC1 Alrm DPO Phase C TOC 1 Alarm DPO
0xB101 Ntrl TOC1 Alrm PKP Neutral TOC 1 Alarm PKP
0xB102 Ntrl TOC1 Alrm OP Neutral TOC 1 Alarm OP
0xB104 Ntrl TOC1 Alrm DPO Neutral TOC 1 Alarm DPO
0xB141 Gnd TOC1 Alarm PKP Ground TOC Alarm PKP
0xB142 Gnd TOC1 Alarm OP Ground TOC 1 Alarm OP
0xB144 Gnd TOC1 Alarm DPO Ground TOC Alarm DPO
0xB181 Ph IOC2 Alarm PKP Phase IOC 2 Alarm PKP
0xB182 Ph IOC2 Alarm OP Phase IOC 2 Alarm OP
0xB184 Ph IOC2 Alarm DPO Phase IOC 2 Alarm DPO
0xB189 Ph A IOC2 Alrm PKP Phase A IOC 2 Alarm PKP
0xB18A Ph A IOC2 Alrm OP Phase A IOC 2 Alarm OP
0xB18C Ph A IOC2 Alrm DPO Phase A IOC 2 Alarm DPO
0xB191 Ph B IOC2 Alrm PKP Phase B IOC 2 Alarm PKP
0xB192 Ph B IOC2 Alrm OP Phase B IOC 2 Alarm OP
0xB194 Ph B IOC2 Alrm DPO Phase B IOC 2 Alarm DPO
0xB1A1 Ph C IOC2 Alrm PKP Phase C IOC 2 Alarm PKP
0xB1A2 Ph C IOC2 Alrm OP Phase C IOC 2 Alarm OP
0xB1A4 Ph C IOC2 Alrm DPO Phase C IOC 2 Alarm DPO
0xB1C1 Ntrl IOC2 Alrm PKP Neutral IOC 2 Alarm PKP
0xB1C2 Ntrl IOC2 Alrm OP Neutral IOC 2 Alarm OP
0xB1C4 Ntrl IOC2 Alrm DPO Neutral IOC 2 Alarm DPO
0xB201 Gnd IOC2 Alarm PKP Ground IOC 2 Alarm PKP
0xB202 Gnd IOC2 Alarm OP Ground IOC 2 Alarm OP
0xB204 Gnd IOC2 Alarm DPO Ground IOC 2 Alarm DPO
0xB301 SGnd TOC1 Alrm PKP Sensitive Ground TOC 1 Alarm PKP
0xB302 SGnd TOC1 Alrm OP Sensitive Ground TOC 1 Alarm OP
0xB304 SGnd TOC1 Alrm DPO Sensitive Ground TOC 1 Alarm DPO
0xB342 NtrlDir RevAlm OP Neutral Directional Alarm OP
0xB344 NtrlDir RevAlmDPO Neutral Directional Reverse Alarm DPO
0xB382 GndDir Alm OP Ground Directional Alarm OP
0xB384 GndDir Alm DPO Ground Directional Alarm DPO
0xB3C1 NSeq OV Alrm PKP Negative Sequence OV Alarm PKP
0xB3C2 NSeq OV Alrm OP Negative Sequence OV Alarm OP
0xB3C4 NSeq OV Alrm DPO Negative Sequence OV Alarm DPO
0xB401 Ntrl OV Alrm PKP Neutral OV Alarm PKP
0xB402 Ntrl OV Alrm OP Neutral OV Alarm OP
0xB404 Ntrl OV Alrm DPO Neutral OV Alarm DPO
0xB441 Ph OV1 Alarm PKP Phase OV1 Alarm PKP
0xB442 Ph OV1 Alarm OP Phase OV 1 Alarm OP
0xB444 Ph OV1 Alarm DPO Phase OV1 Alarm DPO

12-152 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xB449 Ph A OV1 Alarm PKP Phase A OV1 Alarm PKP
0xB44A Ph A OV1 Alarm OP Phase A OV1 Alarm OP
0xB44C Ph A OV1 Alarm DPO Phase A OV1 Alarm DPO
0xB451 Ph B OV1 Alarm PKP Phase B OV1 Alarm PKP
0xB452 Ph B OV1 Alarm OP Phase B OV1 Alarm OP
0xB454 Ph B OV1 Alarm DPO Phase B OV1 Alarm DPO
0xB461 Ph C OV1 Alarm PKP Phase C OV1 Alarm PKP
0xB462 Ph C OV1 Alarm OP Phase C OV1 Alarm OP
0xB464 Ph C OV1 Alarm DPO Phase C OV1 Alarm DPO
0xB481 Ph UV1 Alarm PKP Phase UV1 Alarm PKP
0xB482 Ph UV1 Alarm OP Phase UV 1 Alarm OP
0xB484 Ph UV1 Alarm DPO Phase UV1 Alarm DPO
0xB489 Ph A UV1 Alarm PKP Phase A UV1 Alarm PKP
0xB48A Ph A UV1 Alarm OP Phase A UV1 Alarm OP
0xB48C Ph A UV1 Alarm DPO Phase A UV1 Alarm DPO
0xB491 Ph B UV1 Alarm PKP Phase B UV1 Alarm PKP
0xB492 Ph B UV1 Alarm OP Phase B UV1 Alarm OP
0xB494 Ph B UV1 Alarm DPO Phase B UV1 Alarm DPO
0xB4A1 Ph C UV1 Alarm PKP Phase C UV1 Alarm PKP
0xB4A2 Ph C UV1 Alarm OP Phase C UV1 Alarm OP
0xB4A4 Ph C UV1 Alarm DPO Phase C UV1 Alarm DPO
0xB4C1 Aux OV Alarm PKP Auxiliary OV Alarm PKP
0xB4C2 Aux OV Alarm OP Auxiliary OV Alarm OP
0xB4C4 Aux OV Alarm DPO Auxiliary OV Alarm DPO
0xB501 Aux UV Alarm PKP Auxiliary UV Alarm PKP
0xB502 Aux UV Alarm OP Auxiliary UV Alarm OP
0xB504 Aux UV Alarm DPO Auxiliary UV Alarm DPO
0xB541 UndrFreq1 Alrm PKP Underfrequency 1 Alarm PKP
0xB542 UndrFreq1 Alrm OP Underfrequency 1 Alarm OP
0xB544 UndrFreq1 Alrm DPO Underfrequency 1 Alarm DPO
0xB581 UndrFreq2 Alrm PKP Underfrequency 2 Alarm PKP
0xB582 UndrFreq2 Alrm OP Underfrequency 2 Alarm OP
0xB584 UndrFreq2 Alrm DPO Underfrequency 2 Alarm DPO
0xB5C1 OverFreq1 Alrm PKP Overfrequency 1 Alarm PKP
0xB5C2 OverFreq1 Alrm OP Overfrequency 1 Alarm OP
0xB5C4 OverFreq1 Alrm DPO Overfrequency 1 Alarm DPO
0xB601 OverFreq2 Alrm PKP Overfrequency 2 Alarm PKP
0xB602 OverFreq2 Alrm OP Overfrequency 2 Alarm OP
0xB604 OverFreq2 Alrm DPO Overfrequency 2 Alarm DPO
0xB641 SGnd IOC1 Alrm PKP Sensitive Ground IOC 1 Alarm PKP
0xB642 SGnd IOC1 Alrm OP Sensitive Ground IOC 1 Alarm OP
0xB644 SGnd IOC1 Alrm DPO Sensitive Ground IOC 1 Alarm DPO
0xB681 SGnd IOC2 Alrm PKP Sensitive Ground IOC 2 Alarm PKP
0xB682 SGnd IOC2 Alrm OP Sensitive Ground IOC 2 Alarm OP
0xB684 SGnd IOC2 Alrm DPO Sensitive Ground IOC 2 Alarm DPO
0xB6C1 NSeq IOC Alrm PKP Negative Sequence IOC Alarm PKP
0xB6C2 NSeq IOC Alrm OP NSeq IOC Alrm OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-153


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xB6C4 NSeq IOC Alrm DPO Negative Sequence IOC Alarm DPO
0xB701 Ph UV2 Alrm PKP Phase UV 2 Alrm PKP
0xB702 Ph UV2 Alrm OP Phase UV 2 Alrm OP
0xB704 Ph UV2 Alrm DPO Phase UV 2 Alrm DPO
0xB709 Ph A UV2 Alrm PKP Phase A UV 2 Alrm PKP
0xB70A Ph A UV2 Alrm OP Phase A UV 2 Alrm OP
0xB70C Ph A UV2 Alrm DPO Phase A UV 2 Alrm DPO
0xB711 Ph B UV2 Alrm PKP Phase B UV 2 Alrm PKP
0xB712 Ph B UV2 Alrm OP Phase B UV 2 Alrm OP
0xB714 Ph B UV2 Alrm DPO Phase B UV 2 Alrm DPO
0xB721 Ph C UV2 Alrm PKP Phase C UV 2 Alrm PKP
0xB722 Ph C UV2 Alrm OP Phase C UV 2 Alrm OP
0xB724 Ph C UV2 Alrm DPO Phase C UV 2 Alrm DPO
0xB741 Ph UV3 Alrm PKP Phase UV 3 Alrm PKP
0xB742 Ph UV3 Alrm OP Phase UV 3 Alrm OP
0xB744 Ph UV3 Alrm DPO Phase UV 3 Alrm DPO
0xB749 Ph A UV3 Alrm PKP Phase A UV 3 Alrm PKP
0xB74A Ph A UV3 Alrm OP Phase A UV 3 Alrm OP
0xB74C Ph A UV3 Alrm DPO Phase A UV 3 Alrm DPO
0xB751 Ph B UV3 Alrm PKP Phase B UV 3 Alrm PKP
0xB752 Ph B UV3 Alrm OP Phase B UV 3 Alrm OP
0xB754 Ph B UV3 Alrm DPO Phase B UV 3 Alrm DPO
0xB761 Ph C UV3 Alrm PKP Phase C UV 3 Alrm PKP
0xB762 Ph C UV3 Alrm OP Phase C UV 3 Alrm OP
0xB764 Ph C UV3 Alrm DPO Phase C UV 3 Alrm DPO
0xB781 Ph UV4 Alrm PKP Phase UV 4 Alrm PKP
0xB782 Ph UV4 Alrm OP Phase UV 4 Alrm OP
0xB784 Ph UV4 Alrm DPO Phase UV 4 Alrm DPO
0xB789 Ph A UV4 Alrm PKP Phase A UV 4 Alrm PKP
0xB78A Ph A UV4 Alrm OP Phase A UV 4 Alrm OP
0xB78C Ph A UV4 Alrm DPO Phase A UV 4 Alrm DPO
0xB791 Ph B UV4 Alrm PKP Phase B UV 4 Alrm PKP
0xB792 Ph B UV4 Alrm OP Phase B UV 4 Alrm OP
0xB794 Ph B UV4 Alrm DPO Phase B UV 4 Alrm DPO
0xB7A1 Ph C UV4 Alrm PKP Phase C UV 4 Alrm PKP
0xB7A2 Ph C UV4 Alrm OP Phase C UV 4 Alrm OP
0xB7A4 Ph C UV4 Alrm DPO Phase C UV 4 Alrm DPO
0xB7C1 NSeq OV2 Alrm PKP Negative Sequence OV2 Alrm PKP
0xB7C2 NSeq OV2 Alrm OP Negative Sequence OV2 Alrm OP
0xB7C4 NSeq OV2 Alrm DPO Negative Sequence OV2 Alrm DPO
0xB801 NSeq TOC1 Alrm PKP Negative Sequence TOC 1 Alarm PKP
0xB802 NSeq TOC1 Alrm OP Negative Sequence TOC 1 Alarm OP
0xB804 NSeq TOC1 Alrm DPO Negative Sequence TOC 1 Alarm DPO
0xB881 CTFail Alrm PKP CT Fail Alarm PKP
0xB882 CTFail Alrm OP CT Fail Alarm OP
0xB884 CTFail Alrm DPO CT Fail Alarm DPO
0xB8C1 Ph OV2 Alarm PKP Phase OV 2 Alarm PKP

12-154 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xB8C2 Ph OV2 Alarm OP Phase OV 2 Alarm OP
0xB8C4 Ph OV2 Alarm DPO Phase OV 2 Alarm DPO
0xB8C9 Ph A OV2 Alarm PKP Ph A OV2 Alarm PKP
0xB8CA Ph A OV2 Alarm OP Ph A OV2 Alarm OP
0xB8CC Ph A OV2 Alarm DPO Ph A OV2 Alarm DPO
0xB8D1 Ph B OV2 Alarm PKP Ph B OV2 Alarm PKP
0xB8D2 Ph B OV2 Alarm OP Ph B OV2 Alarm OP
0xB8D4 Ph B OV2 Alarm DPO Ph B OV2 Alarm DPO
0xB8E1 Ph C OV2 Alarm PKP Ph C OV2 Alarm PKP
0xB8E2 Ph C OV2 Alarm OP Ph C OV2 Alarm OP
0xB8E4 Ph C OV2 Alarm DPO Ph C OV2 Alarm DPO
0xB901 Ph OV3 Alarm PKP Phase OV 3 Alarm PKP
0xB902 Ph OV3 Alarm OP Phase OV 3 Alarm OP
0xB904 Ph OV3 Alarm DPO Phase OV 3 Alarm DPO
0xB909 Ph A OV3 Alarm PKP Phase A OV 3 Alarm PKP
0xB90A Ph A OV3 Alarm OP Phase A OV 3 Alarm OP
0xB90C Ph A OV3 Alarm DPO Phase A OV 3 Alarm DPO
0xB911 Ph B OV3 Alarm PKP Phase B OV 3 Alarm PKP
0xB912 Ph B OV3 Alarm OP Phase B OV 3 Alarm OP
0xB914 Ph B OV3 Alarm DPO Phase B OV 3 Alarm DPO
0xB921 Ph C OV3 Alarm PKP Phase C OV 3 Alarm PKP
0xB922 Ph C OV3 Alarm OP Phase C OV 3 Alarm OP
0xB924 Ph C OV3 Alarm DPO Phase C OV 3 Alarm DPO
0xB941 Ph OV4 Alarm PKP Phase OV 4 Alarm PKP
0xB942 Ph OV4 Alarm OP Phase OV 4 Alarm OP
0xB944 Ph OV4 Alarm DPO Phase OV 4 Alarm DPO
0xB949 Ph A OV4 Alarm PKP Phase A OV 4 Alarm PKP
0xB94A Ph A OV4 Alarm OP Phase A OV 4 Alarm OP
0xB94C Ph A OV4 Alarm DPO Phase A OV 4 Alarm DPO
0xB951 Ph B OV4 Alarm PKP Phase B OV 4 Alarm PKP
0xB952 Ph B OV4 Alarm OP Phase B OV 4 Alarm OP
0xB954 Ph B OV4 Alarm DPO Phase B OV 4 Alarm DPO
0xB961 Ph C OV4 Alarm PKP Phase C OV 4 Alarm PKP
0xB962 Ph C OV4 Alarm OP Phase C OV 4 Alarm OP
0xB964 Ph C OV4 Alarm DPO Phase C OV 4 Alarm DPO
0xB981 Ntrl OV2 Alrm PKP Neutral OV 2 Alarm PKP
0xB982 Ntrl OV2 Alrm OP Neutral OV 2 Alarm OP
0xB984 Ntrl OV2 Alrm DPO Neutral OV 2 Alarm DPO
0xB9C1 Ntrl OV3 Alrm PKP Neutral OV 3 Alarm PKP
0xB9C2 Ntrl OV3 Alrm OP Neutral OV 3 Alarm OP
0xB9C4 Ntrl OV3 Alrm DPO Neutral OV 3 Alarm DPO
0xBA01 Ntrl OV4 Alrm PKP Neutral OV 4 Alarm PKP
0xBA02 Ntrl OV4 Alrm OP Neutral OV 4 Alarm OP
0xBA04 Ntrl OV4 Alrm DPO Neutral OV 4 Alarm DPO
0xBA41 OverFreq3 Alrm PKP Overfrequency 3 Alrm PKP
0xBA42 OverFreq3 Alrm OP Overfrequency 3 Alrm OP
0xBA44 OverFreq3 Alrm DPO Overfrequency 3 Alrm DPO

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-155


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xBA81 OverFreq4 Alrm PKP Overfrequency 4 Alrm PKP
0xBA82 OverFreq4 Alrm OP Overfrequency 4 Alrm OP
0xBA84 OverFreq4 Alrm DPO Overfrequency 4 Alrm DPO
0xBAC1 UndFreq3 Alrm PKP Underfrequency 3 Alrm PKP
0xBAC2 UndFreq3 Alarm OP Underfrequency 3 Alarm OP
0xBAC4 UndFreq3 Alrm DPO Underfrequency 3 Alrm DPO
0xBB01 UndFreq4 Alarm PKP Underfrequency 4 Alarm PKP
0xBB02 UndFreq4 Alarm OP Underfrequency 4 Alarm OP
0xBB04 UndFreq4 Alarm DPO Underfrequency 4 Alarm DPO
0xBC01 LE 9 Alarm PKP Logic Element 9 Alarm PKP
0xBC02 LE 9 Alarm OP Logic Element 9 Alarm OP
0xBC04 LE 9 Alarm DPO Logic Element 9 Alarm DPO
0xBC41 LE 10 Alarm PKP Logic Element 10 Alarm PKP
0xBC42 LE 10 Alarm OP Logic Element 10 Alarm OP
0xBC44 LE 10 Alarm DPO Logic Element 10 Alarm DPO
0xBC81 LE 11 Alarm PKP Logic Element 11 Alarm PKP
0xBC82 LE 11 Alarm OP Logic Element 11 Alarm OP
0xBC84 LE 11 Alarm DPO Logic Element 11 Alarm DPO
0xBCC1 LE 12 Alarm PKP Logic Element 12 Alarm PKP
0xBCC2 LE 12 Alarm OP Logic Element 12 Alarm OP
0xBCC4 LE 12 Alarm DPO Logic Element 12 Alarm DPO
0xBD01 LE 13 Alarm PKP Logic Element 13 Alarm PKP
0xBD02 LE 13 Alarm OP Logic Element 13 Alarm OP
0xBD04 LE 13 Alarm DPO Logic Element 13 Alarm DPO
0xBD41 LE 14 Alarm PKP Logic Element 14 Alarm PKP
0xBD42 LE 14 Alarm OP Logic Element 14 Alarm OP
0xBD44 LE 14 Alarm DPO Logic Element 14 Alarm DPO
0xBD81 LE 15 Alarm PKP Logic Element 15 Alarm PKP
0xBD82 LE 15 Alarm OP Logic Element 15 Alarm OP
0xBD84 LE 15 Alarm DPO Logic Element 15 Alarm DPO
0xBDC1 LE 16 Alarm PKP Logic Element 16 Alarm PKP
0xBDC2 LE 16 Alarm OP Logic Element 16 Alarm OP
0xBDC4 LE 16 Alarm DPO Logic Element 16 Alarm DPO
0xBE02 PhDir RevAlm OP Ph Directional Reverse Alarm OP
0xBE04 PhDir RevAlm DPO Ph Directional Reverse Alarm DPO
0xBE0A PhADir RevAlm OP Ph A Directional Reverse Alarm OP
0xBE0C PhADir RevAlm DPO Ph A Directional Reverse Alarm DPO
0xBE12 PhBDir RevAlm OP Ph B Directional Reverse Alarm OP
0xBE14 PhBDir RevAlm DPO Ph B Directional Reverse Alarm DPO
0xBE22 PhCDir RevAlm OP Ph C Directional Reverse Alarm OP
0xBE24 PhCDir RevAlm DPO Ph C Directional Reverse Alarm DPO
0xBE42 PhDir UndAlm OP Ph Directional Und Alarm OP
0xBE44 PhDir UndAlm DPO Ph Directional Und Alarm DPO
0xBE4A PhADir UndAlm OP Ph A Directional Und Alarm OP
0xBE4C PhADir UndAlm DPO Ph A Directional Und Alarm DPO
0xBE52 PhBDir UndAlm OP Ph B Directional Und Alarm OP
0xBE54 PhBDir UndAlm DPO Ph B Directional Und Alarm DPO

12-156 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xBE62 PhCDir UndAlm OP Ph C Directional Und Alarm OP
0xBE64 PhCDir UndAlm DPO Ph C Directional Und Alarm DPO
0xBE82 GndDir UndAlm OP Ground Directional Und Alarm OP
0xBE84 GndDir UndAlm DPO Ground Directional Und Alarm DPO
0xBEC2 NtrlDir UndAlm OP Neutral Directional Und Alarm OP
0xBEC4 NtrlDir UndAlm DPO Neutral Directional Und Alarm DPO
0xBF01 WGF 1 Alarm PKP Wattmetric Gnd Fault 1 Alarm PKP
0xBF02 WGF 1 Alarm OP Wattmetric Gnd Fault 1 Alarm OP
0xBF04 WGF 1 Alarm DPO Wattmetric Gnd Fault 1 Alarm DPO
0xBF41 WGF 2 Alarm PKP Wattmetric Gnd Fault 2 Alarm PKP
0xBF42 WGF 2 Alarm OP Wattmetric Gnd Fault 2 Alarm OP
0xBF44 WGF 2 Alarm DPO Wattmetric Gnd Fault 2 Alarm DPO
0xC042 Output Relay 3 On Output Relay 3 On
0xC082 Output Relay 4 On Output Relay 4 On
0xC0C2 Output Relay 5 On Output Relay 5 On
0xC102 Output Relay 6 On Output Relay 6 On
0xC142 Self-Test Rly 7 OP Self-Test Rly 7 OP
0xC182 Rly1 Coil OP Relay # 1 Coil OP
0xC1C2 Rly2 Coil OP Relay # 2 Coil OP
0xC202 BKR Connected Breaker Connected OP
0xC242 Arc Flash OP Arc Flash OP
0xC282 Any Pkp OP Any Pkp OP
0xC2C2 Lockout OP Lockout OP
0xC2C4 Lockout DPO Lockout DPO
0xC302 Sync Operation Synchrocheck Operation
0xC342 Sync Close OP Synchrocheck Close OP
0xC382 Sync Condition Synchrocheck Condition
0xC442 HS Phase IOC OP HS Phase IOC OP
0xC44A HS PhA IOC OP HS PhA IOC OP
0xC452 HS PhB IOC OP HS PhB IOC OP
0xC462 HS PhC IOC OP HS PhC IOC OP
0xC482 HSGnd IOC OP HS Ground IOC OP
0xC4C1 LE 1 PKP Logic Element 1 PKP
0xC4C2 LE 1 OP Logic Element 1 OP
0xC4C4 LE 1 DPO Logic Element 1 DPO
0xC501 LE 2 PKP Logic Element 2 PKP
0xC502 LE 2 OP Logic Element 2 OP
0xC504 LE 2 DPO Logic Element 2 DPO
0xC541 LE 3 PKP Logic Element 3 PKP
0xC542 LE 3 OP Logic Element 3 OP
0xC544 LE 3 DPO Logic Element 3 DPO
0xC581 LE 4 PKP Logic Element 4 PKP
0xC582 LE 4 OP Logic Element 4 OP
0xC584 LE 4 DPO Logic Element 4 DPO
0xC5C1 LE 5 PKP Logic Element 5 PKP
0xC5C2 LE 5 OP Logic Element 5 OP
0xC5C4 LE 5 DPO Logic Element 5 DPO

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-157


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xC601 LE 6 PKP Logic Element 6 PKP
0xC602 LE 6 OP Logic Element 6 OP
0xC604 LE 6 DPO Logic Element 6 DPO
0xC641 LE 7 PKP Logic Element 7 PKP
0xC642 LE 7 OP Logic Element 7 OP
0xC644 LE 7 DPO Logic Element 7 DPO
0xC681 LE 8 PKP Logic Element 8 PKP
0xC682 LE 8 OP Logic Element 8 OP
0xC684 LE 8 DPO Logic Element 8 DPO
0xC742 Testing ON Testing ON
0xC744 Testing OFF Testing OFF
0xC882 Setpoint Group2 On Setpoint Group2 On
0xC902 BKR Open Breaker Open
0xC942 BKR Close Breaker Close
0xC982 Maint. Req. OP Maintenance Required OP
0xCA02 52a Contact OP 52a Contact OP
0xCA42 52b Contact OP 52b Contact OP
0xCA82 Reset OK Reset OK
0xCAC2 L/O Rst Closed OP Lockout Reset Closed OP
0xCB02 AR Close AR Close
0xCB42 AR N/Ready AR N/Ready
0xCB82 AR In Progress AR In Progress
0xCBC2 AR Disabled AR Disabled
0xCC02 AR Ext. Init AR Ext. Init
0xCC42 AR Ready AR Ready
0xCCC2 BKR Stat Open Breaker Status Open OP
0xCD02 BKR Stat Clsd Breaker Status Closed OP
0xCD42 Setpoint Group1 On Setpoint Group1 On
0xCD82 Light Sensor 1 OP Light Sensor 1 OP
0xCDC2 Light Sensor 2 OP Light Sensor 2 OP
0xCE81 Dir Pwr 1 PKP Directional Pwr 1 PKP
0xCE82 Dir Pwr 1 OP Directional Pwr 1 OP
0xCEC1 Dir Pwr 2 PKP Directional Pwr 2 PKP
0xCEC2 Dir Pwr 2 OP Directional Pwr 2 OP
0xCF01 2nd Hrmc PKP 2nd Harmonic PKP
0xCF02 2nd Hrmc OP 2nd Harmonic OP
0xCF04 2nd Hrmc DPO 2nd Harmonic DPO
0xCF42 Light Sensor 3 OP Light Sensor 3 OP
0xCF82 Light Sensor 4 OP Light Sensor 4 OP
0xCFC1 Brkn Cond PKP Broken Cond PKP
0xCFC2 Brkn Cond OP Broken Cond OP
0xCFC4 Brkn Cond DPO Broken Cond DPO
0xD342 Ntrl Dir Rev OP Neutral Directional Rev OP
0xD344 Ntrl Dir Rev DPO Neutral Directional Reverse DPO
0xD382 Gnd Dir OP Ground Directional OP
0xD384 Gnd Dir DPO Ground Directional DPO
0xDC01 LE 9 PKP Logic Element 9 PKP

12-158 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xDC02 LE 9 OP Logic Element 9 OP
0xDC04 LE 9 DPO Logic Element 9 DPO
0xDC41 LE 10 PKP Logic Element 10 PKP
0xDC42 LE 10 OP Logic Element 10 OP
0xDC44 LE 10 DPO Logic Element 10 DPO
0xDC81 LE 11 PKP Logic Element 11 PKP
0xDC82 LE 11 OP Logic Element 11 OP
0xDC84 LE 11 DPO Logic Element 11 DPO
0xDCC1 LE 12 PKP Logic Element 12 PKP
0xDCC2 LE 12 OP Logic Element 12 OP
0xDCC4 LE 12 DPO Logic Element 12 DPO
0xDD01 LE 13 PKP Logic Element 13 PKP
0xDD02 LE 13 OP Logic Element 13 OP
0xDD04 LE 13 DPO Logic Element 13 DPO
0xDD41 LE 14 PKP Logic Element 14 PKP
0xDD42 LE 14 OP Logic Element 14 OP
0xDD44 LE 14 DPO Logic Element 14 DPO
0xDD81 LE 15 PKP Logic Element 15 PKP
0xDD82 LE 15 OP Logic Element 15 OP
0xDD84 LE 15 DPO Logic Element 15 DPO
0xDDC1 LE 16 PKP Logic Element 16 PKP
0xDDC2 LE 16 OP Logic Element 16 OP
0xDDC4 LE 16 DPO Logic Element 16 DPO
0xDE02 PhDir Rev OP Ph Directional Reverse OP
0xDE04 PhDir Rev DPO Ph Directional Reverse DPO
0xDE0A PhADir Rev OP Ph A Directional Reverse OP
0xDE0C PhADir Rev DPO Ph A Directional Reverse DPO
0xDE12 PhBDir Rev OP Ph B Directional Reverse OP
0xDE14 PhBDir Rev DPO Ph B Directional Reverse DPO
0xDE22 PhCDir Rev OP Ph C Directional Reverse OP
0xDE24 PhCDir Rev DPO Ph C Directional Reverse DPO
0xDE42 PhDir Und OP Ph Directional Und OP
0xDE44 PhDir Und DPO Ph Directional Und DPO
0xDE4A PhADir Und OP Ph A Directional Und OP
0xDE4C PhADir Und DPO Ph A Directional Und DPO
0xDE52 PhBDir Und OP Ph B Directional Und OP
0xDE54 PhBDir Und DPO Ph B Directional Und DPO
0xDE62 PhCDir Und OP Ph C Directional Und OP
0xDE64 PhCDir Und DPO Ph C Directional Und DPO
0xDE82 GndDir Und OP Ground Directional Und OP
0xDE84 GndDir Und DPO Ground Directional Und DPO
0xDEC2 NtrlDir Und OP Neutral Directional Und OP
0xDEC4 NtrlDir Und DPO Neutral Directional Und DPO
0xDF01 WGF 1 PKP Wattmetric Gnd Fault 1 PKP
0xDF02 WGF 1 OP Wattmetric Gnd Fault 1 OP
0xDF04 WGF 1 DPO Wattmetric Gnd Fault 1 DPO
0xDF41 WGF 2 PKP Wattmetric Gnd Fault 2 PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-159


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xDF42 WGF 2 OP Wattmetric Gnd Fault 2 OP
0xDF44 WGF 2 DPO Wattmetric Gnd Fault 2 DPO
0xE002 Any Block Any Block
0xE042 Therm O/L Block Thermal Level Block
0xE082 PosSeq UV1 Block Positive Sequence UV 1 Block
0xE182 Output Relay 1 Blk Output Relay 1 Block
0xE1C2 Output Relay 2 Blk Output Relay 2 Block
0xE242 Arc Flash Block Arc Flash Block
0xE2C2 Lockout Block Lockout Block
0xE3C2 Volt Hz Block Volt Hz Block
0xE742 Curr Dmd1 Block Current Demand 1 Block OP
0xE782 RealP Dmd Block Real Power Demand Block OP
0xE7C2 ReacP Dmd Block Reactive Power Demand Block OP
0xE802 AppP Dmd Block Apparent Power Demand Block OP
0xE882 Group Change Blk Group Change Blk
0xEB02 AR Block AR Block
0xEE82 Dir Pwr 1 Block Directional Pwr 1 Block
0xEEC2 Dir Pwr 2 Block Directional Pwr 2 Block
0xEFC2 Brkn Cond Block Broken Cond Block
0xF002 Ph IOC1 Block Phase IOC 1 Block
0xF042 Ntrl IOC1 Block Neutral IOC 1 Block
0xF082 Gnd IOC1 Block Ground IOC 1 Block
0xF0C2 Ph TOC1 Block Phase TOC 1 Block
0xF102 Ntrl TOC1 Block Neutral TOC 1 Block
0xF142 Gnd TOC1 Block Ground TOC 1 Block
0xF182 Ph IOC2 Block Phase IOC 2 Block
0xF1C2 Ntrl IOC2 Block Neutral IOC 2 Block
0xF202 Gnd IOC2 Block Ground IOC 2 Block
0xF302 SGnd TOC1 Block Sensitive Ground TOC 1 Block
0xF342 Ntrl Dir Rev Block Neutral Directional Rev Block
0xF382 Gnd Dir Block Ground Directional Block
0xF3C2 NSeq OV Block Negative Sequence OV OP
0xF402 Ntrl OV Block Neutral OV Block
0xF442 Ph OV1 Block Ph OV 1 Block
0xF482 Ph UV1 Block Ph UV 1 Block
0xF4C2 Aux OV Block Auxiliary OV Block
0xF502 Aux UV Block Auxiliary UV Block
0xF542 UndrFreq1 Block Underfrequency 1 Block
0xF582 UndrFreq2 Block Underfrequency 2 Block
0xF5C2 OverFreq1 Block Overfrequency 1 Block
0xF602 OverFreq2 Block Overfrequency 2 Block
0xF642 SGnd IOC1 Block Sensitive Ground IOC 1 Block
0xF682 SGnd IOC2 Block Sensitive Ground IOC 2 Block
0xF6C2 NSeq IOC Block Negative Sequence IOC Block
0xF702 Ph UV2 Block Phase UV 2 Block OP
0xF742 Ph UV3 Block Phase UV 3 Block OP
0xF782 Ph UV4 Block Phase UV 4 Block OP

12-160 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xF7C2 NSeq OV2 Block Negative Sequence OV2 Block
0xF802 NSeq TOC1 Blk Negative Sequence TOC 1 Block
0xF882 CTFail Block CT Fail Block
0xF8C2 Ph OV2 Block Ph OV2 Block
0xF902 Ph OV3 Block Phase OV 3 Block OP
0xF942 Ph OV4 Block Phase OV 4 Block OP
0xF982 Ntrl OV2 Block Neutral OV 2 Block
0xF9C2 Ntrl OV3 Block Neutral OV 3 Block
0xFA02 Ntrl OV4 Block Neutral OV 4 Block
0xFA42 OverFreq3 Block Overfrequency 3 Block
0xFA82 OverFreq4 Block Overfrequency 4 Block
0xFAC2 UndFreq3 Block Underfrequency 3 Block
0xFB02 UndFreq4 Block Underfrequency 4 Block
0xFE02 PhDir Block Ph Directional Block
0xFF02 WGF 1 Block Wattmetric Gnd Fault 1 Block
0xFF42 WGF 2 Block Wattmetric Gnd Fault 2 Block
FC134C unsigned 16 bits Logic Element Trigger
0x0000 Off Off
0x0001 On On
0x0040 Contact IN 1 On Contact Input 1 On
0x0041 Contact IN 2 On Contact Input 2 On
0x0042 Contact IN 3 On Contact Input 3 On
0x0043 Contact IN 4 On Contact Input 4 On
0x0044 Contact IN 5 On Contact Input 5 On
0x0045 Contact IN 6 On Contact Input 6 On
0x0046 Contact IN 7 On Contact Input 7 On
0x0047 Contact IN 8 On Contact Input 8 On
0x0048 Contact IN 9 On Contact Input 9 On
0x0049 Contact IN 10 On Contact Input 10 On
0x0060 Contact IN 1 Off Contact Input 1 Off
0x0061 Contact IN 2 Off Contact Input 2 Off
0x0062 Contact IN 3 Off Contact Input 3 Off
0x0063 Contact IN 4 Off Contact Input 4 Off
0x0064 Contact IN 5 Off Contact Input 5 Off
0x0065 Contact IN 6 Off Contact Input 6 Off
0x0066 Contact IN 7 Off Contact Input 7 Off
0x0067 Contact IN 8 Off Contact Input 8 Off
0x0068 Contact IN 9 Off Contact Input 9 Off
0x0069 Contact IN 10 Off Contact Input 10 Off
0x0080 Virtual IN 1 On Virtual Input 1 On
0x0081 Virtual IN 2 On Virtual Input 2 On
0x0082 Virtual IN 3 On Virtual Input 3 On
0x0083 Virtual IN 4 On Virtual Input 4 On
0x0084 Virtual IN 5 On Virtual Input 5 On
0x0085 Virtual IN 6 On Virtual Input 6 On
0x0086 Virtual IN 7 On Virtual Input 7 On
0x0087 Virtual IN 8 On Virtual Input 8 On

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-161


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x0088 Virtual IN 9 On Virtual Input 9 On
0x0089 Virtual IN 10 On Virtual Input 10 On
0x008A Virtual IN 11 On Virtual Input 11 On
0x008B Virtual IN 12 On Virtual Input 12 On
0x008C Virtual IN 13 On Virtual Input 13 On
0x008D Virtual IN 14 On Virtual Input 14 On
0x008E Virtual IN 15 On Virtual Input 15 On
0x008F Virtual IN 16 On Virtual Input 16 On
0x0090 Virtual IN 17 On Virtual Input 17 On
0x0091 Virtual IN 18 On Virtual Input 18 On
0x0092 Virtual IN 19 On Virtual Input 19 On
0x0093 Virtual IN 20 On Virtual Input 20 On
0x0094 Virtual IN 21 On Virtual Input 21 On
0x0095 Virtual IN 22 On Virtual Input 22 On
0x0096 Virtual IN 23 On Virtual Input 23 On
0x0097 Virtual IN 24 On Virtual Input 24 On
0x0098 Virtual IN 25 On Virtual Input 25 On
0x0099 Virtual IN 26 On Virtual Input 26 On
0x009A Virtual IN 27 On Virtual Input 27 On
0x009B Virtual IN 28 On Virtual Input 28 On
0x009C Virtual IN 29 On Virtual Input 29 On
0x009D Virtual IN 30 On Virtual Input 30 On
0x009E Virtual IN 31 On Virtual Input 31 On
0x009F Virtual IN 32 On Virtual Input 32 On
0x00A0 Virtual IN 1 Off Virtual Input 1 Off
0x00A1 Virtual IN 2 Off Virtual Input 2 Off
0x00A2 Virtual IN 3 Off Virtual Input 3 Off
0x00A3 Virtual IN 4 Off Virtual Input 4 Off
0x00A4 Virtual IN 5 Off Virtual Input 5 Off
0x00A5 Virtual IN 6 Off Virtual Input 6 Off
0x00A6 Virtual IN 7 Off Virtual Input 7 Off
0x00A7 Virtual IN 8 Off Virtual Input 8 Off
0x00A8 Virtual IN 9 Off Virtual Input 9 Off
0x00A9 Virtual IN 10 Off Virtual Input 10 Off
0x00AA Virtual IN 11 Off Virtual Input 11 Off
0x00AB Virtual IN 12 Off Virtual Input 12 Off
0x00AC Virtual IN 13 Off Virtual Input 13 Off
0x00AD Virtual IN 14 Off Virtual Input 14 Off
0x00AE Virtual IN 15 Off Virtual Input 15 Off
0x00AF Virtual IN 16 Off Virtual Input 16 Off
0x00B0 Virtual IN 17 Off Virtual Input 17 Off
0x00B1 Virtual IN 18 Off Virtual Input 18 Off
0x00B2 Virtual IN 19 Off Virtual Input 19 Off
0x00B3 Virtual IN 20 Off Virtual Input 20 Off
0x00B4 Virtual IN 21 Off Virtual Input 21 Off
0x00B5 Virtual IN 22 Off Virtual Input 22 Off
0x00B6 Virtual IN 23 Off Virtual Input 23 Off

12-162 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x00B7 Virtual IN 24 Off Virtual Input 24 Off
0x00B8 Virtual IN 25 Off Virtual Input 25 Off
0x00B9 Virtual IN 26 Off Virtual Input 26 Off
0x00BA Virtual IN 27 Off Virtual Input 27 Off
0x00BB Virtual IN 28 Off Virtual Input 28 Off
0x00BC Virtual IN 29 Off Virtual Input 29 Off
0x00BD Virtual IN 30 Off Virtual Input 30 Off
0x00BE Virtual IN 31 Off Virtual Input 31 Off
0x00BF Virtual IN 32 Off Virtual Input 32 Off
0x01C0 Remote IN 1 On Remote Input 1 On
0x01C1 Remote IN 2 On Remote Input 2 On
0x01C2 Remote IN 3 On Remote Input 3 On
0x01C3 Remote IN 4 On Remote Input 4 On
0x01C4 Remote IN 5 On Remote Input 5 On
0x01C5 Remote IN 6 On Remote Input 6 On
0x01C6 Remote IN 7 On Remote Input 7 On
0x01C7 Remote IN 8 On Remote Input 8 On
0x01C8 Remote IN 9 On Remote Input 9 On
0x01C9 Remote IN 10 On Remote Input 10 On
0x01CA Remote IN 11 On Remote Input 11 On
0x01CB Remote IN 12 On Remote Input 12 On
0x01CC Remote IN 13 On Remote Input 13 On
0x01CD Remote IN 14 On Remote Input 14 On
0x01CE Remote IN 15 On Remote Input 15 On
0x01CF Remote IN 16 On Remote Input 16 On
0x01D0 Remote IN 17 On Remote Input 17 On
0x01D1 Remote IN 18 On Remote Input 18 On
0x01D2 Remote IN 19 On Remote Input 19 On
0x01D3 Remote IN 20 On Remote Input 20 On
0x01D4 Remote IN 21 On Remote Input 21 On
0x01D5 Remote IN 22 On Remote Input 22 On
0x01D6 Remote IN 23 On Remote Input 23 On
0x01D7 Remote IN 24 On Remote Input 24 On
0x01D8 Remote IN 25 On Remote Input 25 On
0x01D9 Remote IN 26 On Remote Input 26 On
0x01DA Remote IN 27 On Remote Input 27 On
0x01DB Remote IN 28 On Remote Input 28 On
0x01DC Remote IN 29 On Remote Input 29 On
0x01DD Remote IN 30 On Remote Input 30 On
0x01DE Remote IN 31 On Remote Input 31 On
0x01DF Remote IN 32 On Remote Input 32 On
0x01E0 Remote IN 1 Off Remote Input 1 Off
0x01E1 Remote IN 2 Off Remote Input 2 Off
0x01E2 Remote IN 3 Off Remote Input 3 Off
0x01E3 Remote IN 4 Off Remote Input 4 Off
0x01E4 Remote IN 5 Off Remote Input 5 Off
0x01E5 Remote IN 6 Off Remote Input 6 Off

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-163


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x01E6 Remote IN 7 Off Remote Input 7 Off
0x01E7 Remote IN 8 Off Remote Input 8 Off
0x01E8 Remote IN 9 Off Remote Input 9 Off
0x01E9 Remote IN 10 Off Remote Input 10 Off
0x01EA Remote IN 11 Off Remote Input 11 Off
0x01EB Remote IN 12 Off Remote Input 12 Off
0x01EC Remote IN 13 Off Remote Input 13 Off
0x01ED Remote IN 14 Off Remote Input 14 Off
0x01EE Remote IN 15 Off Remote Input 15 Off
0x01EF Remote IN 16 Off Remote Input 16 Off
0x01F0 Remote IN 17 Off Remote Input 17 Off
0x01F1 Remote IN 18 Off Remote Input 18 Off
0x01F2 Remote IN 19 Off Remote Input 19 Off
0x01F3 Remote IN 20 Off Remote Input 20 Off
0x01F4 Remote IN 21 Off Remote Input 21 Off
0x01F5 Remote IN 22 Off Remote Input 22 Off
0x01F6 Remote IN 23 Off Remote Input 23 Off
0x01F7 Remote IN 24 Off Remote Input 24 Off
0x01F8 Remote IN 25 Off Remote Input 25 Off
0x01F9 Remote IN 26 Off Remote Input 26 Off
0x01FA Remote IN 27 Off Remote Input 27 Off
0x01FB Remote IN 28 Off Remote Input 28 Off
0x01FC Remote IN 29 Off Remote Input 29 Off
0x01FD Remote IN 30 Off Remote Input 30 Off
0x01FE Remote IN 31 Off Remote Input 31 Off
0x01FF Remote IN 32 Off Remote Input 32 Off
0x8002 Any Trip Any Trip
0x8042 Therm O/L Trip OP Thermal Overload Trip OP
0x8044 Therm O/L Trip DPO Thermal Overload Trip DPO
0x8081 PosSeq UV1 Trp PKP Positive Sequence UV 1 Trp PKP
0x8082 PosSeq UV1 Trip OP Positive Sequence UV 1 Trip OP
0x8084 PosSeq UV1 Trp DPO Positive Sequence UV 1 Trp DPO
0x8242 Arc Flash Trip OP Arc Flash Trip OP
0x83C1 Volt Hz Trip PKP Volt Hz Trip PKP
0x83C2 Volt Hz Trip OP Volt Hz Trip OP
0x83C4 Volt Hz Trip DPO Volt Hz Trip DPO
0x84C1 LE 1 Trip PKP Logic Element 1 Trip PKP
0x84C2 LE 1 Trip OP Logic Element 1 Trip OP
0x84C4 LE 1 Trip DPO Logic Element 1 Trip DPO
0x8501 LE 2 Trip PKP Logic Element 2 Trip PKP
0x8502 LE 2 Trip OP Logic Element 2 Trip OP
0x8504 LE 2 Trip DPO Logic Element 2 Trip DPO
0x8541 LE 3 Trip PKP Logic Element 3 Trip PKP
0x8542 LE 3 Trip OP Logic Element 3 Trip OP
0x8544 LE 3 Trip DPO Logic Element 3 Trip DPO
0x8581 LE 4 Trip PKP Logic Element 4 Trip PKP
0x8582 LE 4 Trip OP Logic Element 4 Trip OP

12-164 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x8584 LE 4 Trip DPO Logic Element 4 Trip DPO
0x85C1 LE 5 Trip PKP Logic Element 5 Trip PKP
0x85C2 LE 5 Trip OP Logic Element 5 Trip OP
0x85C4 LE 5 Trip DPO Logic Element 5 Trip DPO
0x8601 LE 6 Trip PKP Logic Element 6 Trip PKP
0x8602 LE 6 Trip OP Logic Element 6 Trip OP
0x8604 LE 6 Trip DPO Logic Element 6 Trip DPO
0x8641 LE 7 Trip PKP Logic Element 7 Trip PKP
0x8642 LE 7 Trip OP Logic Element 7 Trip OP
0x8644 LE 7 Trip DPO Logic Element 7 Trip DPO
0x8681 LE 8 Trip PKP Logic Element 8 Trip PKP
0x8682 LE 8 Trip OP Logic Element 8 Trip OP
0x8684 LE 8 Trip DPO Logic Element 8 Trip DPO
0x8E81 Dir Pwr 1 Trip PKP Directional Pwr 1 Trip PKP
0x8E82 Dir Pwr 1 Trip OP Directional Pwr 1 Trip OP
0x8EC1 Dir Pwr 2 Trip PKP Directional Pwr 2 Trip PKP
0x8EC2 Dir Pwr 2 Trip OP Directional Pwr 2 Trip OP
0x8F81 Fuse Fail Trip PKP Fuse Fail Trip PKP
0x8F82 Fuse Fail Trip OP Fuse Fail Trip OP
0x8F84 Fuse Fail Trip DPO Fuse Fail Trip DPO
0x8FC1 Brkn Cond Trip PKP Broken Cond Trip PKP
0x8FC2 Brkn Cond Trip OP Broken Cond Trip OP
0x8FC4 Brkn Cond Trip DPO Broken Cond Trip DPO
0x9001 Ph IOC1 Trip PKP Phase IOC 1 Trip PKP
0x9002 Ph IOC1 Trip OP Phase IOC 1 Trip OP
0x9004 Ph IOC1 Trip DPO Phase IOC 1 Trip DPO
0x9041 Ntrl IOC1 Trip PKP Neutral IOC 1 Trip PKP
0x9042 Ntrl IOC1 Trip OP Neutral IOC 1 Trip OP
0x9044 Ntrl IOC1 Trip DPO Neutral IOC 1 Trip DPO
0x9081 Gnd IOC1 Trip PKP Ground IOC 1 Trip PKP
0x9082 Gnd IOC1 Trip OP Ground IOC 1 Trip OP
0x9084 Gnd IOC1 Trip DPO Ground IOC 1 Trip DPO
0x90C1 Ph TOC1 Trip PKP Phase TOC 1 Trip PKP
0x90C2 Ph TOC1 Trip OP Phase TOC 1 Trip OP
0x90C4 Ph TOC1 Trip DPO Phase TOC 1 Trip DPO
0x9101 Ntrl TOC1 Trip PKP Neutral TOC 1 Trip PKP
0x9102 Ntrl TOC1 Trip OP Neutral TOC 1 Trip OP
0x9104 Ntrl TOC1 Trip DPO Neutral TOC 1 Trip DPO
0x9141 Gnd TOC1 Trip PKP Ground TOC Trip PKP
0x9142 Gnd TOC1 Trip OP Ground TOC 1 Trip OP
0x9144 Gnd TOC1 Trip DPO Ground TOC Trip DPO
0x9181 Ph IOC2 Trip PKP Phase IOC 2 Trip PKP
0x9182 Ph IOC2 Trip OP Phase IOC 2 Trip OP
0x9184 Ph IOC2 Trip DPO Phase IOC 2 Trip DPO
0x91C1 Ntrl IOC2 Trip PKP Neutral IOC 2 Trip PKP
0x91C2 Ntrl IOC2 Trip OP Neutral IOC 2 Trip OP
0x91C4 Ntrl IOC2 Trip DPO Neutral IOC 2 Trip DPO

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-165


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x9201 Gnd IOC2 Trip PKP Ground IOC 2 Trip PKP
0x9202 Gnd IOC2 Trip OP Ground IOC 2 Trip OP
0x9204 Gnd IOC2 Trip DPO Ground IOC 2 Trip DPO
0x9301 SGnd TOC1 Trip PKP Sensitive Ground TOC 1 Trip PKP
0x9302 SGnd TOC1 Trip OP Sensitive Ground TOC 1 Trip OP
0x9304 SGnd TOC1 Trip DPO Sensitive Ground TOC 1 Trip DPO
0x93C1 NSeq OV Trp PKP Negative Sequence OV Trip PKP
0x93C2 NSeq OV Trp OP Negative Sequence OV Trip OP
0x93C4 NSeq OV Trp DPO Negative Sequence OV Trip DPO
0x9401 Ntrl OV Trip PKP Neutral OV Trip PKP
0x9402 Ntrl OV Trp OP Neutral OV Trip OP
0x9404 Ntrl OV Trip DPO Neutral OV Trip DPO
0x9441 Ph OV1 Trip PKP Phase OV1 Trip PKP
0x9442 Ph OV1 Trip OP Phase OV 1 Trip OP
0x9444 Ph OV1 Trip DPO Phase OV1 Trip DPO
0x9481 Ph UV1 Trip PKP Phase UV1 Trip PKP
0x9482 Ph UV1 Trip OP Phase UV 1 Trip OP
0x9484 Ph UV1 Trip DPO Phase UV1 Trip DPO
0x94C1 Aux OV Trip PKP Auxiliary OV Trip PKP
0x94C2 Aux OV Trip OP Auxiliary OV Trip OP
0x94C4 Aux OV Trip DPO Auxiliary OV Trip DPO
0x9501 Aux UV Trip PKP Auxiliary UV Trip PKP
0x9502 Aux UV Trip OP Auxiliary UV Trip OP
0x9504 Aux UV Trip DPO Auxiliary UV Trip DPO
0x9541 UndrFreq1 Trip PKP Underfrequency 1 Trip PKP
0x9542 UndrFreq1 Trip OP Underfrequency 1 Trip OP
0x9544 UndrFreq1 Trip DPO Underfrequency 1 Trip DPO
0x9581 UndrFreq2 Trip PKP Underfrequency 2 Trip PKP
0x9582 UndrFreq2 Trip OP Underfrequency 2 Trip OP
0x9584 UndrFreq2 Trip DPO Underfrequency 2 Trip DPO
0x95C1 OverFreq1 Trip PKP Overfrequency 1 Trip PKP
0x95C2 OverFreq1 Trip OP Overfrequency 1 Trip OP
0x95C4 OverFreq1 Trip DPO Overfrequency 1 Trip DPO
0x9601 OverFreq2 Trip PKP Overfrequency 2 Trip PKP
0x9602 OverFreq2 Trip OP Overfrequency 2 Trip OP
0x9604 OverFreq2 Trip DPO Overfrequency 2 Trip DPO
0x9641 SGnd IOC1 Trip PKP Sensitive Ground IOC 1 Trip PKP
0x9642 SGnd IOC1 Trip OP Sensitive Ground IOC 1 Trip OP
0x9644 SGnd IOC1 Trip DPO Sensitive Ground IOC 1 Trip DPO
0x9681 SGnd IOC2 Trip PKP Sensitive Ground IOC 2 Trip PKP
0x9682 SGnd IOC2 Trip OP Sensitive Ground IOC 2 Trip OP
0x9684 SGnd IOC2 Trip DPO Sensitive Ground IOC 2 Trip DPO
0x96C1 NSeq IOC Trp PKP Negative Sequence IOC Trip PKP
0x96C2 NSeq IOC Trp OP Negative Sequence IOC Trip OP
0x96C4 NSeq IOC Trp DPO Negative Sequence IOC Trip DPO
0x9701 Ph UV2 Trip PKP Phase UV 2 Trip PKP
0x9702 Ph UV2 Trip OP Phase UV 2 Trip OP

12-166 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x9704 Ph UV2 Trip DPO Phase UV 2 Trip DPO
0x9741 Ph UV3 Trip PKP Phase UV 3 Trip PKP
0x9742 Ph UV3 Trip OP Phase UV 3 Trip OP
0x9744 Ph UV3 Trip DPO Phase UV 3 Trip DPO
0x9781 Ph UV4 Trip PKP Phase UV 4 Trip PKP
0x9782 Ph UV4 Trip OP Phase UV 4 Trip OP
0x9784 Ph UV4 Trip DPO Phase UV 4 Trip DPO
0x97C1 NSeq OV2 Trp PKP Negative Sequence OV2 Trp PKP
0x97C2 NSeq OV2 Trp OP Negative Sequence OV2 Trp OP
0x97C4 NSeq OV2 Trp DPO Negative Sequence OV2 Trp DPO
0x9801 NSeq TOC1 Trip PKP Negative Sequence TOC 1 Trip PKP
0x9802 NSeq TOC1 Trip OP Negative Sequence TOC 1 Trip OP
0x9804 NSeq TOC1 Trip DPO Negative Sequence TOC 1 Trip DPO
0x98C1 Ph OV2 Trip PKP Phase OV 2 Trip PKP
0x98C2 Ph OV2 Trip OP Phase OV 2 Trip OP
0x98C4 Ph OV2 Trip DPO Phase OV 2 Trip DPO
0x9901 Ph OV3 Trip PKP Phase OV 3 Trip PKP
0x9902 Ph OV3 Trip OP Phase OV 3 Trip OP
0x9904 Ph OV3 Trip DPO Phase OV 3 Trip DPO
0x9941 Ph OV4 Trip PKP Phase OV 4 Trip PKP
0x9942 Ph OV4 Trip OP Phase OV 4 Trip OP
0x9944 Ph OV4 Trip DPO Phase OV 4 Trip DPO
0x9981 Ntrl OV2 Trip PKP Neutral OV 2 Trip PKP
0x9982 Ntrl OV2 Trip OP Neutral OV 2 Trip OP
0x9984 Ntrl OV2 Trip DPO Neutral OV 2 Trip DPO
0x99C1 Ntrl OV3 Trip PKP Neutral OV 3 Trip PKP
0x99C2 Ntrl OV3 Trip OP Neutral OV 3 Trip OP
0x99C4 Ntrl OV3 Trip DPO Neutral OV 3 Trip DPO
0x9A01 Ntrl OV4 Trip PKP Neutral OV 4 Trip PKP
0x9A02 Ntrl OV4 Trip OP Neutral OV 4 Trip OP
0x9A04 Ntrl OV4 Trip DPO Neutral OV 4 Trip DPO
0x9A41 OverFreq3 Trip PKP Overfrequency 3 Trip PKP
0x9A42 OverFreq3 Trip OP Overfrequency 3 Trip OP
0x9A44 OverFreq3 Trip DPO Overfrequency 3 Trip DPO
0x9A81 OverFreq4 Trip PKP Overfrequency 4 Trip PKP
0x9A82 OverFreq4 Trip OP Overfrequency 4 Trip OP
0x9A84 OverFreq4 Trip DPO Overfrequency 4 Trip DPO
0x9AC1 UndFreq3 Trip PKP Underfrequency 3 Trip PKP
0x9AC2 UndFreq3 Trip OP Underfrequency 3 Trip OP
0x9AC4 UndFreq3 Trip DPO Underfrequency 3 Trip DPO
0x9B01 UndFreq4 Trip PKP Underfrequency 4 Trip PKP
0x9B02 UndFreq4 Trip OP Underfrequency 4 Trip OP
0x9B04 UndFreq4 Trip DPO Underfrequency 4 Trip DPO
0x9C01 LE 9 Trip PKP Logic Element 9 Trip PKP
0x9C02 LE 9 Trip OP Logic Element 9 Trip OP
0x9C04 LE 9 Trip DPO Logic Element 9 Trip DPO
0x9C41 LE 10 Trip PKP Logic Element 10 Trip PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-167


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x9C42 LE 10 Trip OP Logic Element 10 Trip OP
0x9C44 LE 10 Trip DPO Logic Element 10 Trip DPO
0x9C81 LE 11 Trip PKP Logic Element 11 Trip PKP
0x9C82 LE 11 Trip OP Logic Element 11 Trip OP
0x9C84 LE 11 Trip DPO Logic Element 11 Trip DPO
0x9CC1 LE 12 Trip PKP Logic Element 12 Trip PKP
0x9CC2 LE 12 Trip OP Logic Element 12 Trip OP
0x9CC4 LE 12 Trip DPO Logic Element 12 Trip DPO
0x9D01 LE 13 Trip PKP Logic Element 13 Trip PKP
0x9D02 LE 13 Trip OP Logic Element 13 Trip OP
0x9D04 LE 13 Trip DPO Logic Element 13 Trip DPO
0x9D41 LE 14 Trip PKP Logic Element 14 Trip PKP
0x9D42 LE 14 Trip OP Logic Element 14 Trip OP
0x9D44 LE 14 Trip DPO Logic Element 14 Trip DPO
0x9D81 LE 15 Trip PKP Logic Element 15 Trip PKP
0x9D82 LE 15 Trip OP Logic Element 15 Trip OP
0x9D84 LE 15 Trip DPO Logic Element 15 Trip DPO
0x9DC1 LE 16 Trip PKP Logic Element 16 Trip PKP
0x9DC2 LE 16 Trip OP Logic Element 16 Trip OP
0x9DC4 LE 16 Trip DPO Logic Element 16 Trip DPO
0x9F01 WGF 1 Trip PKP Wattmetric Gnd Fault 1 Trip PKP
0x9F02 WGF 1 Trip OP Wattmetric Gnd Fault 1 Trip OP
0x9F04 WGF 1 Trip DPO Wattmetric Gnd Fault 1 Trip DPO
0x9F41 WGF 2 Trip PKP Wattmetric Gnd Fault 2 Trip PKP
0x9F42 WGF 2 Trip OP Wattmetric Gnd Fault 2 Trip OP
0x9F44 WGF 2 Trip DPO Wattmetric Gnd Fault 2 Trip DPO
0xA002 Any Alarm Any Alarm
0xA042 Therm Lvl Alrm OP Thermal Level Alarm OP
0xA044 Therm Lvl Alrm DPO Thermal Level Alarm DPO
0xA081 PosSeq UV1 AlrmPKP Positive Sequence UV 1 Alarm PKP
0xA082 PosSeq UV1 Alrm OP Positive Sequence UV 1 Alarm OP
0xA084 PosSeq UV1 AlrmDPO Positive Sequence UV 1 Alarm DPO
0xA242 Arc Flash Alarm OP Arc Flash Alarm OP
0xA2C2 LightSns1 Trbl Light Sensor 1 Trouble
0xA302 LightSns2 Trbl Light Sensor 2 Trouble
0xA342 LightSns3 Trbl Light Sensor 3 Trouble
0xA382 LightSns4 Trbl Light Sensor 4 Trouble
0xA3C1 Volt Hz Alarm PKP Volt Hz Alarm PKP
0xA3C2 Volt Hz Alarm OP Volt Hz Alarm OP
0xA3C4 Volt Hz Alarm DPO Volt Hz Alarm DPO
0xA442 Light Sns Trbl Light Sensor Trouble
0xA4C1 LE 1 Alarm PKP Logic Element 1 Alarm PKP
0xA4C2 LE 1 Alarm OP Logic Element 1 Alarm OP
0xA4C4 LE 1 Alarm DPO Logic Element 1 Alarm DPO
0xA501 LE 2 Alarm PKP Logic Element 2 Alarm PKP
0xA502 LE 2 Alarm OP Logic Element 2 Alarm OP
0xA504 LE 2 Alarm DPO Logic Element 2 Alarm DPO

12-168 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xA541 LE 3 Alarm PKP Logic Element 3 Alarm PKP
0xA542 LE 3 Alarm OP Logic Element 3 Alarm OP
0xA544 LE 3 Alarm DPO Logic Element 3 Alarm DPO
0xA581 LE 4 Alarm PKP Logic Element 4 Alarm PKP
0xA582 LE 4 Alarm OP Logic Element 4 Alarm OP
0xA584 LE 4 Alarm DPO Logic Element 4 Alarm DPO
0xA5C1 LE 5 Alarm PKP Logic Element 5 Alarm PKP
0xA5C2 LE 5 Alarm OP Logic Element 5 Alarm OP
0xA5C4 LE 5 Alarm DPO Logic Element 5 Alarm DPO
0xA601 LE 6 Alarm PKP Logic Element 6 Alarm PKP
0xA602 LE 6 Alarm OP Logic Element 6 Alarm OP
0xA604 LE 6 Alarm DPO Logic Element 6 Alarm DPO
0xA641 LE 7 Alarm PKP Logic Element 7 Alarm PKP
0xA642 LE 7 Alarm OP Logic Element 7 Alarm OP
0xA644 LE 7 Alarm DPO Logic Element 7 Alarm DPO
0xA681 LE 8 Alarm PKP Logic Element 8 Alarm PKP
0xA682 LE 8 Alarm OP Logic Element 8 Alarm OP
0xA684 LE 8 Alarm DPO Logic Element 8 Alarm DPO
0xA742 Curr Dmd1 Alrm OP Current Demand 1 Alarm OP
0xA782 RealP Dmd Alrm OP Real Power Demand Alarm OP
0xA7C2 ReacP Dmd Alrm OP Reactive Power Demand Alarm OP
0xA802 AppP Dmd Alrm OP Apparent Power Demand Alarm OP
0xAA02 BKR Alarm Breaker Alarm
0xAA42 BKR Trip Time Breaker Trip Time
0xAA82 BKR Close Time Breaker Close Time
0xAAC2 BKR Charge Time Breaker Charge Time
0xAB02 BKR Trp/Cls Fail Breaker Trip/Close Fail
0xAB42 BKR Charge Fail Breaker Charge Fail
0xABC1 HI Amb Temp PKP High Ambient Temperature Alarm PKP
0xABC2 HI Amb Temp OP High Ambient Temperature Alarm
0xABC4 HI Amb Temp DPO High Ambient Temperature Alarm DPO
0xAC01 LO Amb Temp PKP Low Ambient Temperature Alarm PKP
0xAC02 LO Amb Temp OP Low Ambient Temperature Alarm
0xAC04 LO Amb Temp DPO Low Ambient Temperature Alarm DPO
0xAC42 Self Test Alarm OP Self Test Alarm OP
0xACC2 BKRTrpCntrAlrm OP Breaker Trip Control Alarm OP
0xAD02 R1 CoilMonAlrm OP Trip Coil Monitor Alarm OP
0xAD42 R2 CoilMonAlrm OP Close Coil Monitor Alarm OP
0xAD81 BKR Fail Alrm PKP Breaker Fail Alarm PKP
0xAD82 BKR Fail Alrm OP Breaker Fail Alarm OP
0xAD84 BKR Fail Alrm DPO Breaker Fail Alarm DPO
0xADC2 BKR Stat Fail OP Breaker Status Fail OP
0xAE41 CLP Alarm PKP Cold Load PKP Alarm PKP
0xAE42 CLP Alarm OP Cold Load PKP Alarm OP
0xAE81 Dir Pwr 1 Alrm PKP Directional Pwr 1 Alarm PKP
0xAE82 Dir Pwr 1 Alarm OP Directional Pwr 1 Alarm OP
0xAEC1 Dir Pwr 2 Alrm PKP Directional Pwr 2 Alarm PKP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-169


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xAEC2 Dir Pwr 2 Alarm OP Directional Pwr 2 Alarm OP
0xAF01 2nd Hrmc Alarm PKP 2nd Harmonic Alarm PKP
0xAF02 2nd Hrmc Alarm OP 2nd Harmonic Alarm OP
0xAF04 2nd Hrmc Alarm DPO 2nd Harmonic Alarm DPO
0xAF81 Fuse Fail Alrm PKP Fuse Fail Alarm PKP
0xAF82 Fuse Fail Alrm OP Fuse Fail Alarm OP
0xAF84 Fuse Fail Alrm DPO Fuse Fail Alarm DPO
0xAFC1 Brkn Cond Alrm PKP Broken Cond Alarm PKP
0xAFC2 Brkn Cond Alarm OP Broken Cond Alarm OP
0xAFC4 Brkn Cond Alrm DPO Broken Cond Alarm DPO
0xB001 Ph IOC1 Alarm PKP Phase IOC 1 Alarm PKP
0xB002 Ph IOC1 Alarm OP Phase IOC 1 Alarm OP
0xB004 Ph IOC1 Alarm DPO Phase IOC 1 Alarm DPO
0xB041 Ntrl IOC1 Alrm PKP Neutral IOC 1 Alarm PKP
0xB042 Ntrl IOC1 Alrm OP Neutral IOC 1 Alarm OP
0xB044 Ntrl IOC1 Alrm DPO Neutral IOC 1 Alarm DPO
0xB081 Gnd IOC1 Alarm PKP Ground IOC 1 Alarm PKP
0xB082 Gnd IOC1 Alarm OP Ground IOC 1 Alarm OP
0xB084 Gnd IOC1 Alarm DPO Ground IOC 1 Alarm DPO
0xB0C1 Ph TOC1 Alarm PKP Phase TOC 1 Alarm PKP
0xB0C2 Ph TOC1 Alarm OP Phase TOC 1 Alarm OP
0xB0C4 Ph TOC1 Alarm DPO Phase TOC 1 Alarm DPO
0xB101 Ntrl TOC1 Alrm PKP Neutral TOC 1 Alarm PKP
0xB102 Ntrl TOC1 Alrm OP Neutral TOC 1 Alarm OP
0xB104 Ntrl TOC1 Alrm DPO Neutral TOC 1 Alarm DPO
0xB141 Gnd TOC1 Alarm PKP Ground TOC Alarm PKP
0xB142 Gnd TOC1 Alarm OP Ground TOC 1 Alarm OP
0xB144 Gnd TOC1 Alarm DPO Ground TOC Alarm DPO
0xB181 Ph IOC2 Alarm PKP Phase IOC 2 Alarm PKP
0xB182 Ph IOC2 Alarm OP Phase IOC 2 Alarm OP
0xB184 Ph IOC2 Alarm DPO Phase IOC 2 Alarm DPO
0xB1C1 Ntrl IOC2 Alrm PKP Neutral IOC 2 Alarm PKP
0xB1C2 Ntrl IOC2 Alrm OP Neutral IOC 2 Alarm OP
0xB1C4 Ntrl IOC2 Alrm DPO Neutral IOC 2 Alarm DPO
0xB201 Gnd IOC2 Alarm PKP Ground IOC 2 Alarm PKP
0xB202 Gnd IOC2 Alarm OP Ground IOC 2 Alarm OP
0xB204 Gnd IOC2 Alarm DPO Ground IOC 2 Alarm DPO
0xB301 SGnd TOC1 Alrm PKP Sensitive Ground TOC 1 Alarm PKP
0xB302 SGnd TOC1 Alrm OP Sensitive Ground TOC 1 Alarm OP
0xB304 SGnd TOC1 Alrm DPO Sensitive Ground TOC 1 Alarm DPO
0xB342 NtrlDir RevAlm OP Neutral Directional Alarm OP
0xB344 NtrlDir RevAlmDPO Neutral Directional Reverse Alarm DPO
0xB382 GndDir Alm OP Ground Directional Alarm OP
0xB384 GndDir Alm DPO Ground Directional Alarm DPO
0xB3C1 NSeq OV Alrm PKP Negative Sequence OV Alarm PKP
0xB3C2 NSeq OV Alrm OP Negative Sequence OV Alarm OP
0xB3C4 NSeq OV Alrm DPO Negative Sequence OV Alarm DPO

12-170 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xB401 Ntrl OV Alrm PKP Neutral OV Alarm PKP
0xB402 Ntrl OV Alrm OP Neutral OV Alarm OP
0xB404 Ntrl OV Alrm DPO Neutral OV Alarm DPO
0xB441 Ph OV1 Alarm PKP Phase OV1 Alarm PKP
0xB442 Ph OV1 Alarm OP Phase OV 1 Alarm OP
0xB444 Ph OV1 Alarm DPO Phase OV1 Alarm DPO
0xB481 Ph UV1 Alarm PKP Phase UV1 Alarm PKP
0xB482 Ph UV1 Alarm OP Phase UV 1 Alarm OP
0xB484 Ph UV1 Alarm DPO Phase UV1 Alarm DPO
0xB4C1 Aux OV Alarm PKP Auxiliary OV Alarm PKP
0xB4C2 Aux OV Alarm OP Auxiliary OV Alarm OP
0xB4C4 Aux OV Alarm DPO Auxiliary OV Alarm DPO
0xB501 Aux UV Alarm PKP Auxiliary UV Alarm PKP
0xB502 Aux UV Alarm OP Auxiliary UV Alarm OP
0xB504 Aux UV Alarm DPO Auxiliary UV Alarm DPO
0xB541 UndrFreq1 Alrm PKP Underfrequency 1 Alarm PKP
0xB542 UndrFreq1 Alrm OP Underfrequency 1 Alarm OP
0xB544 UndrFreq1 Alrm DPO Underfrequency 1 Alarm DPO
0xB581 UndrFreq2 Alrm PKP Underfrequency 2 Alarm PKP
0xB582 UndrFreq2 Alrm OP Underfrequency 2 Alarm OP
0xB584 UndrFreq2 Alrm DPO Underfrequency 2 Alarm DPO
0xB5C1 OverFreq1 Alrm PKP Overfrequency 1 Alarm PKP
0xB5C2 OverFreq1 Alrm OP Overfrequency 1 Alarm OP
0xB5C4 OverFreq1 Alrm DPO Overfrequency 1 Alarm DPO
0xB601 OverFreq2 Alrm PKP Overfrequency 2 Alarm PKP
0xB602 OverFreq2 Alrm OP Overfrequency 2 Alarm OP
0xB604 OverFreq2 Alrm DPO Overfrequency 2 Alarm DPO
0xB641 SGnd IOC1 Alrm PKP Sensitive Ground IOC 1 Alarm PKP
0xB642 SGnd IOC1 Alrm OP Sensitive Ground IOC 1 Alarm OP
0xB644 SGnd IOC1 Alrm DPO Sensitive Ground IOC 1 Alarm DPO
0xB681 SGnd IOC2 Alrm PKP Sensitive Ground IOC 2 Alarm PKP
0xB682 SGnd IOC2 Alrm OP Sensitive Ground IOC 2 Alarm OP
0xB684 SGnd IOC2 Alrm DPO Sensitive Ground IOC 2 Alarm DPO
0xB6C1 NSeq IOC Alrm PKP Negative Sequence IOC Alarm PKP
0xB6C2 NSeq IOC Alrm OP NSeq IOC Alrm OP
0xB6C4 NSeq IOC Alrm DPO Negative Sequence IOC Alarm DPO
0xB701 Ph UV2 Alrm PKP Phase UV 2 Alrm PKP
0xB702 Ph UV2 Alrm OP Phase UV 2 Alrm OP
0xB704 Ph UV2 Alrm DPO Phase UV 2 Alrm DPO
0xB741 Ph UV3 Alrm PKP Phase UV 3 Alrm PKP
0xB742 Ph UV3 Alrm OP Phase UV 3 Alrm OP
0xB744 Ph UV3 Alrm DPO Phase UV 3 Alrm DPO
0xB781 Ph UV4 Alrm PKP Phase UV 4 Alrm PKP
0xB782 Ph UV4 Alrm OP Phase UV 4 Alrm OP
0xB784 Ph UV4 Alrm DPO Phase UV 4 Alrm DPO
0xB7C1 NSeq OV2 Alrm PKP Negative Sequence OV2 Alrm PKP
0xB7C2 NSeq OV2 Alrm OP Negative Sequence OV2 Alrm OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-171


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xB7C4 NSeq OV2 Alrm DPO Negative Sequence OV2 Alrm DPO
0xB801 NSeq TOC1 Alrm PKP Negative Sequence TOC 1 Alarm PKP
0xB802 NSeq TOC1 Alrm OP Negative Sequence TOC 1 Alarm OP
0xB804 NSeq TOC1 Alrm DPO Negative Sequence TOC 1 Alarm DPO
0xB881 CTFail Alrm PKP CT Fail Alarm PKP
0xB882 CTFail Alrm OP CT Fail Alarm OP
0xB884 CTFail Alrm DPO CT Fail Alarm DPO
0xB8C1 Ph OV2 Alarm PKP Phase OV 2 Alarm PKP
0xB8C2 Ph OV2 Alarm OP Phase OV 2 Alarm OP
0xB8C4 Ph OV2 Alarm DPO Phase OV 2 Alarm DPO
0xB901 Ph OV3 Alarm PKP Phase OV 3 Alarm PKP
0xB902 Ph OV3 Alarm OP Phase OV 3 Alarm OP
0xB904 Ph OV3 Alarm DPO Phase OV 3 Alarm DPO
0xB941 Ph OV4 Alarm PKP Phase OV 4 Alarm PKP
0xB942 Ph OV4 Alarm OP Phase OV 4 Alarm OP
0xB944 Ph OV4 Alarm DPO Phase OV 4 Alarm DPO
0xB981 Ntrl OV2 Alrm PKP Neutral OV 2 Alarm PKP
0xB982 Ntrl OV2 Alrm OP Neutral OV 2 Alarm OP
0xB984 Ntrl OV2 Alrm DPO Neutral OV 2 Alarm DPO
0xB9C1 Ntrl OV3 Alrm PKP Neutral OV 3 Alarm PKP
0xB9C2 Ntrl OV3 Alrm OP Neutral OV 3 Alarm OP
0xB9C4 Ntrl OV3 Alrm DPO Neutral OV 3 Alarm DPO
0xBA01 Ntrl OV4 Alrm PKP Neutral OV 4 Alarm PKP
0xBA02 Ntrl OV4 Alrm OP Neutral OV 4 Alarm OP
0xBA04 Ntrl OV4 Alrm DPO Neutral OV 4 Alarm DPO
0xBA41 OverFreq3 Alrm PKP Overfrequency 3 Alrm PKP
0xBA42 OverFreq3 Alrm OP Overfrequency 3 Alrm OP
0xBA44 OverFreq3 Alrm DPO Overfrequency 3 Alrm DPO
0xBA81 OverFreq4 Alrm PKP Overfrequency 4 Alrm PKP
0xBA82 OverFreq4 Alrm OP Overfrequency 4 Alrm OP
0xBA84 OverFreq4 Alrm DPO Overfrequency 4 Alrm DPO
0xBAC1 UndFreq3 Alrm PKP Underfrequency 3 Alrm PKP
0xBAC2 UndFreq3 Alarm OP Underfrequency 3 Alarm OP
0xBAC4 UndFreq3 Alrm DPO Underfrequency 3 Alrm DPO
0xBB01 UndFreq4 Alarm PKP Underfrequency 4 Alarm PKP
0xBB02 UndFreq4 Alarm OP Underfrequency 4 Alarm OP
0xBB04 UndFreq4 Alarm DPO Underfrequency 4 Alarm DPO
0xBC01 LE 9 Alarm PKP Logic Element 9 Alarm PKP
0xBC02 LE 9 Alarm OP Logic Element 9 Alarm OP
0xBC04 LE 9 Alarm DPO Logic Element 9 Alarm DPO
0xBC41 LE 10 Alarm PKP Logic Element 10 Alarm PKP
0xBC42 LE 10 Alarm OP Logic Element 10 Alarm OP
0xBC44 LE 10 Alarm DPO Logic Element 10 Alarm DPO
0xBC81 LE 11 Alarm PKP Logic Element 11 Alarm PKP
0xBC82 LE 11 Alarm OP Logic Element 11 Alarm OP
0xBC84 LE 11 Alarm DPO Logic Element 11 Alarm DPO
0xBCC1 LE 12 Alarm PKP Logic Element 12 Alarm PKP

12-172 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xBCC2 LE 12 Alarm OP Logic Element 12 Alarm OP
0xBCC4 LE 12 Alarm DPO Logic Element 12 Alarm DPO
0xBD01 LE 13 Alarm PKP Logic Element 13 Alarm PKP
0xBD02 LE 13 Alarm OP Logic Element 13 Alarm OP
0xBD04 LE 13 Alarm DPO Logic Element 13 Alarm DPO
0xBD41 LE 14 Alarm PKP Logic Element 14 Alarm PKP
0xBD42 LE 14 Alarm OP Logic Element 14 Alarm OP
0xBD44 LE 14 Alarm DPO Logic Element 14 Alarm DPO
0xBD81 LE 15 Alarm PKP Logic Element 15 Alarm PKP
0xBD82 LE 15 Alarm OP Logic Element 15 Alarm OP
0xBD84 LE 15 Alarm DPO Logic Element 15 Alarm DPO
0xBDC1 LE 16 Alarm PKP Logic Element 16 Alarm PKP
0xBDC2 LE 16 Alarm OP Logic Element 16 Alarm OP
0xBDC4 LE 16 Alarm DPO Logic Element 16 Alarm DPO
0xBE02 PhDir RevAlm OP Ph Directional Reverse Alarm OP
0xBE04 PhDir RevAlm DPO Ph Directional Reverse Alarm DPO
0xBE0A PhADir RevAlm OP Ph A Directional Reverse Alarm OP
0xBE0C PhADir RevAlm DPO Ph A Directional Reverse Alarm DPO
0xBE12 PhBDir RevAlm OP Ph B Directional Reverse Alarm OP
0xBE14 PhBDir RevAlm DPO Ph B Directional Reverse Alarm DPO
0xBE22 PhCDir RevAlm OP Ph C Directional Reverse Alarm OP
0xBE24 PhCDir RevAlm DPO Ph C Directional Reverse Alarm DPO
0xBE42 PhDir UndAlm OP Ph Directional Und Alarm OP
0xBE44 PhDir UndAlm DPO Ph Directional Und Alarm DPO
0xBE4A PhADir UndAlm OP Ph A Directional Und Alarm OP
0xBE4C PhADir UndAlm DPO Ph A Directional Und Alarm DPO
0xBE52 PhBDir UndAlm OP Ph B Directional Und Alarm OP
0xBE54 PhBDir UndAlm DPO Ph B Directional Und Alarm DPO
0xBE62 PhCDir UndAlm OP Ph C Directional Und Alarm OP
0xBE64 PhCDir UndAlm DPO Ph C Directional Und Alarm DPO
0xBE82 GndDir UndAlm OP Ground Directional Und Alarm OP
0xBE84 GndDir UndAlm DPO Ground Directional Und Alarm DPO
0xBEC2 NtrlDir UndAlm OP Neutral Directional Und Alarm OP
0xBEC4 NtrlDir UndAlm DPO Neutral Directional Und Alarm DPO
0xBF01 WGF 1 Alarm PKP Wattmetric Gnd Fault 1 Alarm PKP
0xBF02 WGF 1 Alarm OP Wattmetric Gnd Fault 1 Alarm OP
0xBF04 WGF 1 Alarm DPO Wattmetric Gnd Fault 1 Alarm DPO
0xBF41 WGF 2 Alarm PKP Wattmetric Gnd Fault 2 Alarm PKP
0xBF42 WGF 2 Alarm OP Wattmetric Gnd Fault 2 Alarm OP
0xBF44 WGF 2 Alarm DPO Wattmetric Gnd Fault 2 Alarm DPO
0xC042 Output Relay 3 On Output Relay 3 On
0xC082 Output Relay 4 On Output Relay 4 On
0xC0C2 Output Relay 5 On Output Relay 5 On
0xC102 Output Relay 6 On Output Relay 6 On
0xC142 Self-Test Rly 7 OP Self-Test Rly 7 OP
0xC182 Rly1 Coil OP Relay # 1 Coil OP
0xC1C2 Rly2 Coil OP Relay # 2 Coil OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-173


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xC202 BKR Connected Breaker Connected OP
0xC242 Arc Flash OP Arc Flash OP
0xC282 Any Pkp OP Any Pkp OP
0xC2C2 Lockout OP Lockout OP
0xC2C4 Lockout DPO Lockout DPO
0xC302 Sync Operation Synchrocheck Operation
0xC342 Sync Close OP Synchrocheck Close OP
0xC382 Sync Condition Synchrocheck Condition
0xC442 HS Phase IOC OP HS Phase IOC OP
0xC482 HSGnd IOC OP HS Ground IOC OP
0xC4C1 LE 1 PKP Logic Element 1 PKP
0xC4C2 LE 1 OP Logic Element 1 OP
0xC4C4 LE 1 DPO Logic Element 1 DPO
0xC501 LE 2 PKP Logic Element 2 PKP
0xC502 LE 2 OP Logic Element 2 OP
0xC504 LE 2 DPO Logic Element 2 DPO
0xC541 LE 3 PKP Logic Element 3 PKP
0xC542 LE 3 OP Logic Element 3 OP
0xC544 LE 3 DPO Logic Element 3 DPO
0xC581 LE 4 PKP Logic Element 4 PKP
0xC582 LE 4 OP Logic Element 4 OP
0xC584 LE 4 DPO Logic Element 4 DPO
0xC5C1 LE 5 PKP Logic Element 5 PKP
0xC5C2 LE 5 OP Logic Element 5 OP
0xC5C4 LE 5 DPO Logic Element 5 DPO
0xC601 LE 6 PKP Logic Element 6 PKP
0xC602 LE 6 OP Logic Element 6 OP
0xC604 LE 6 DPO Logic Element 6 DPO
0xC641 LE 7 PKP Logic Element 7 PKP
0xC642 LE 7 OP Logic Element 7 OP
0xC644 LE 7 DPO Logic Element 7 DPO
0xC681 LE 8 PKP Logic Element 8 PKP
0xC682 LE 8 OP Logic Element 8 OP
0xC684 LE 8 DPO Logic Element 8 DPO
0xC742 Testing ON Testing ON
0xC744 Testing OFF Testing OFF
0xC882 Setpoint Group2 On Setpoint Group2 On
0xC902 BKR Open Breaker Open
0xC942 BKR Close Breaker Close
0xC982 Maint. Req. OP Maintenance Required OP
0xCA02 52a Contact OP 52a Contact OP
0xCA42 52b Contact OP 52b Contact OP
0xCA82 Reset OK Reset OK
0xCAC2 L/O Rst Closed OP Lockout Reset Closed OP
0xCB02 AR Close AR Close
0xCB42 AR N/Ready AR N/Ready
0xCB82 AR In Progress AR In Progress

12-174 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xCBC2 AR Disabled AR Disabled
0xCC02 AR Ext. Init AR Ext. Init
0xCC42 AR Ready AR Ready
0xCCC2 BKR Stat Open Breaker Status Open OP
0xCD02 BKR Stat Clsd Breaker Status Closed OP
0xCD42 Setpoint Group1 On Setpoint Group1 On
0xCD82 Light Sensor 1 OP Light Sensor 1 OP
0xCDC2 Light Sensor 2 OP Light Sensor 2 OP
0xCE81 Dir Pwr 1 PKP Directional Pwr 1 PKP
0xCE82 Dir Pwr 1 OP Directional Pwr 1 OP
0xCEC1 Dir Pwr 2 PKP Directional Pwr 2 PKP
0xCEC2 Dir Pwr 2 OP Directional Pwr 2 OP
0xCF01 2nd Hrmc PKP 2nd Harmonic PKP
0xCF02 2nd Hrmc OP 2nd Harmonic OP
0xCF04 2nd Hrmc DPO 2nd Harmonic DPO
0xCF42 Light Sensor 3 OP Light Sensor 3 OP
0xCF82 Light Sensor 4 OP Light Sensor 4 OP
0xCFC1 Brkn Cond PKP Broken Cond PKP
0xCFC2 Brkn Cond OP Broken Cond OP
0xCFC4 Brkn Cond DPO Broken Cond DPO
0xD342 Ntrl Dir Rev OP Neutral Directional Rev OP
0xD344 Ntrl Dir Rev DPO Neutral Directional Reverse DPO
0xD382 Gnd Dir OP Ground Directional OP
0xD384 Gnd Dir DPO Ground Directional DPO
0xDC01 LE 9 PKP Logic Element 9 PKP
0xDC02 LE 9 OP Logic Element 9 OP
0xDC04 LE 9 DPO Logic Element 9 DPO
0xDC41 LE 10 PKP Logic Element 10 PKP
0xDC42 LE 10 OP Logic Element 10 OP
0xDC44 LE 10 DPO Logic Element 10 DPO
0xDC81 LE 11 PKP Logic Element 11 PKP
0xDC82 LE 11 OP Logic Element 11 OP
0xDC84 LE 11 DPO Logic Element 11 DPO
0xDCC1 LE 12 PKP Logic Element 12 PKP
0xDCC2 LE 12 OP Logic Element 12 OP
0xDCC4 LE 12 DPO Logic Element 12 DPO
0xDD01 LE 13 PKP Logic Element 13 PKP
0xDD02 LE 13 OP Logic Element 13 OP
0xDD04 LE 13 DPO Logic Element 13 DPO
0xDD41 LE 14 PKP Logic Element 14 PKP
0xDD42 LE 14 OP Logic Element 14 OP
0xDD44 LE 14 DPO Logic Element 14 DPO
0xDD81 LE 15 PKP Logic Element 15 PKP
0xDD82 LE 15 OP Logic Element 15 OP
0xDD84 LE 15 DPO Logic Element 15 DPO
0xDDC1 LE 16 PKP Logic Element 16 PKP
0xDDC2 LE 16 OP Logic Element 16 OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-175


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xDDC4 LE 16 DPO Logic Element 16 DPO
0xDE02 PhDir Rev OP Ph Directional Reverse OP
0xDE04 PhDir Rev DPO Ph Directional Reverse DPO
0xDE0A PhADir Rev OP Ph A Directional Reverse OP
0xDE0C PhADir Rev DPO Ph A Directional Reverse DPO
0xDE12 PhBDir Rev OP Ph B Directional Reverse OP
0xDE14 PhBDir Rev DPO Ph B Directional Reverse DPO
0xDE22 PhCDir Rev OP Ph C Directional Reverse OP
0xDE24 PhCDir Rev DPO Ph C Directional Reverse DPO
0xDE42 PhDir Und OP Ph Directional Und OP
0xDE44 PhDir Und DPO Ph Directional Und DPO
0xDE4A PhADir Und OP Ph A Directional Und OP
0xDE4C PhADir Und DPO Ph A Directional Und DPO
0xDE52 PhBDir Und OP Ph B Directional Und OP
0xDE54 PhBDir Und DPO Ph B Directional Und DPO
0xDE62 PhCDir Und OP Ph C Directional Und OP
0xDE64 PhCDir Und DPO Ph C Directional Und DPO
0xDE82 GndDir Und OP Ground Directional Und OP
0xDE84 GndDir Und DPO Ground Directional Und DPO
0xDEC2 NtrlDir Und OP Neutral Directional Und OP
0xDEC4 NtrlDir Und DPO Neutral Directional Und DPO
0xDF01 WGF 1 PKP Wattmetric Gnd Fault 1 PKP
0xDF02 WGF 1 OP Wattmetric Gnd Fault 1 OP
0xDF04 WGF 1 DPO Wattmetric Gnd Fault 1 DPO
0xDF41 WGF 2 PKP Wattmetric Gnd Fault 2 PKP
0xDF42 WGF 2 OP Wattmetric Gnd Fault 2 OP
0xDF44 WGF 2 DPO Wattmetric Gnd Fault 2 DPO
0xE002 Any Block Any Block
0xE042 Therm O/L Block Thermal Level Block
0xE082 PosSeq UV1 Block Positive Sequence UV 1 Block
0xE182 Output Relay 1 Blk Output Relay 1 Block
0xE1C2 Output Relay 2 Blk Output Relay 2 Block
0xE242 Arc Flash Block Arc Flash Block
0xE2C2 Lockout Block Lockout Block
0xE3C2 Volt Hz Block Volt Hz Block
0xE742 Curr Dmd1 Block Current Demand 1 Block OP
0xE782 RealP Dmd Block Real Power Demand Block OP
0xE7C2 ReacP Dmd Block Reactive Power Demand Block OP
0xE802 AppP Dmd Block Apparent Power Demand Block OP
0xE882 Group Change Blk Group Change Blk
0xEB02 AR Block AR Block
0xEE82 Dir Pwr 1 Block Directional Pwr 1 Block
0xEEC2 Dir Pwr 2 Block Directional Pwr 2 Block
0xEFC2 Brkn Cond Block Broken Cond Block
0xF002 Ph IOC1 Block Phase IOC 1 Block
0xF042 Ntrl IOC1 Block Neutral IOC 1 Block
0xF082 Gnd IOC1 Block Ground IOC 1 Block

12-176 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xF0C2 Ph TOC1 Block Phase TOC 1 Block
0xF102 Ntrl TOC1 Block Neutral TOC 1 Block
0xF142 Gnd TOC1 Block Ground TOC 1 Block
0xF182 Ph IOC2 Block Phase IOC 2 Block
0xF1C2 Ntrl IOC2 Block Neutral IOC 2 Block
0xF202 Gnd IOC2 Block Ground IOC 2 Block
0xF302 SGnd TOC1 Block Sensitive Ground TOC 1 Block
0xF342 Ntrl Dir Rev Block Neutral Directional Rev Block
0xF382 Gnd Dir Block Ground Directional Block
0xF3C2 NSeq OV Block Negative Sequence OV OP
0xF402 Ntrl OV Block Neutral OV Block
0xF442 Ph OV1 Block Ph OV 1 Block
0xF482 Ph UV1 Block Ph UV 1 Block
0xF4C2 Aux OV Block Auxiliary OV Block
0xF502 Aux UV Block Auxiliary UV Block
0xF542 UndrFreq1 Block Underfrequency 1 Block
0xF582 UndrFreq2 Block Underfrequency 2 Block
0xF5C2 OverFreq1 Block Overfrequency 1 Block
0xF602 OverFreq2 Block Overfrequency 2 Block
0xF642 SGnd IOC1 Block Sensitive Ground IOC 1 Block
0xF682 SGnd IOC2 Block Sensitive Ground IOC 2 Block
0xF6C2 NSeq IOC Block Negative Sequence IOC Block
0xF702 Ph UV2 Block Phase UV 2 Block OP
0xF742 Ph UV3 Block Phase UV 3 Block OP
0xF782 Ph UV4 Block Phase UV 4 Block OP
0xF7C2 NSeq OV2 Block Negative Sequence OV2 Block
0xF802 NSeq TOC1 Blk Negative Sequence TOC 1 Block
0xF882 CTFail Block CT Fail Block
0xF8C2 Ph OV2 Block Ph OV2 Block
0xF902 Ph OV3 Block Phase OV 3 Block OP
0xF942 Ph OV4 Block Phase OV 4 Block OP
0xF982 Ntrl OV2 Block Neutral OV 2 Block
0xF9C2 Ntrl OV3 Block Neutral OV 3 Block
0xFA02 Ntrl OV4 Block Neutral OV 4 Block
0xFA42 OverFreq3 Block Overfrequency 3 Block
0xFA82 OverFreq4 Block Overfrequency 4 Block
0xFAC2 UndFreq3 Block Underfrequency 3 Block
0xFB02 UndFreq4 Block Underfrequency 4 Block
0xFE02 PhDir Block Ph Directional Block
0xFF02 WGF 1 Block Wattmetric Gnd Fault 1 Block
0xFF42 WGF 2 Block Wattmetric Gnd Fault 2 Block
FC134D unsigned 16 bits Lockout Trigger
0x0000 Off Off
0x0001 On On
0x0040 Contact IN 1 On Contact Input 1 On
0x0041 Contact IN 2 On Contact Input 2 On
0x0042 Contact IN 3 On Contact Input 3 On

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-177


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x0043 Contact IN 4 On Contact Input 4 On
0x0044 Contact IN 5 On Contact Input 5 On
0x0045 Contact IN 6 On Contact Input 6 On
0x0046 Contact IN 7 On Contact Input 7 On
0x0047 Contact IN 8 On Contact Input 8 On
0x0048 Contact IN 9 On Contact Input 9 On
0x0049 Contact IN 10 On Contact Input 10 On
0x0060 Contact IN 1 Off Contact Input 1 Off
0x0061 Contact IN 2 Off Contact Input 2 Off
0x0062 Contact IN 3 Off Contact Input 3 Off
0x0063 Contact IN 4 Off Contact Input 4 Off
0x0064 Contact IN 5 Off Contact Input 5 Off
0x0065 Contact IN 6 Off Contact Input 6 Off
0x0066 Contact IN 7 Off Contact Input 7 Off
0x0067 Contact IN 8 Off Contact Input 8 Off
0x0068 Contact IN 9 Off Contact Input 9 Off
0x0069 Contact IN 10 Off Contact Input 10 Off
0x0080 Virtual IN 1 On Virtual Input 1 On
0x0081 Virtual IN 2 On Virtual Input 2 On
0x0082 Virtual IN 3 On Virtual Input 3 On
0x0083 Virtual IN 4 On Virtual Input 4 On
0x0084 Virtual IN 5 On Virtual Input 5 On
0x0085 Virtual IN 6 On Virtual Input 6 On
0x0086 Virtual IN 7 On Virtual Input 7 On
0x0087 Virtual IN 8 On Virtual Input 8 On
0x0088 Virtual IN 9 On Virtual Input 9 On
0x0089 Virtual IN 10 On Virtual Input 10 On
0x008A Virtual IN 11 On Virtual Input 11 On
0x008B Virtual IN 12 On Virtual Input 12 On
0x008C Virtual IN 13 On Virtual Input 13 On
0x008D Virtual IN 14 On Virtual Input 14 On
0x008E Virtual IN 15 On Virtual Input 15 On
0x008F Virtual IN 16 On Virtual Input 16 On
0x0090 Virtual IN 17 On Virtual Input 17 On
0x0091 Virtual IN 18 On Virtual Input 18 On
0x0092 Virtual IN 19 On Virtual Input 19 On
0x0093 Virtual IN 20 On Virtual Input 20 On
0x0094 Virtual IN 21 On Virtual Input 21 On
0x0095 Virtual IN 22 On Virtual Input 22 On
0x0096 Virtual IN 23 On Virtual Input 23 On
0x0097 Virtual IN 24 On Virtual Input 24 On
0x0098 Virtual IN 25 On Virtual Input 25 On
0x0099 Virtual IN 26 On Virtual Input 26 On
0x009A Virtual IN 27 On Virtual Input 27 On
0x009B Virtual IN 28 On Virtual Input 28 On
0x009C Virtual IN 29 On Virtual Input 29 On
0x009D Virtual IN 30 On Virtual Input 30 On

12-178 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x009E Virtual IN 31 On Virtual Input 31 On
0x009F Virtual IN 32 On Virtual Input 32 On
0x00A0 Virtual IN 1 Off Virtual Input 1 Off
0x00A1 Virtual IN 2 Off Virtual Input 2 Off
0x00A2 Virtual IN 3 Off Virtual Input 3 Off
0x00A3 Virtual IN 4 Off Virtual Input 4 Off
0x00A4 Virtual IN 5 Off Virtual Input 5 Off
0x00A5 Virtual IN 6 Off Virtual Input 6 Off
0x00A6 Virtual IN 7 Off Virtual Input 7 Off
0x00A7 Virtual IN 8 Off Virtual Input 8 Off
0x00A8 Virtual IN 9 Off Virtual Input 9 Off
0x00A9 Virtual IN 10 Off Virtual Input 10 Off
0x00AA Virtual IN 11 Off Virtual Input 11 Off
0x00AB Virtual IN 12 Off Virtual Input 12 Off
0x00AC Virtual IN 13 Off Virtual Input 13 Off
0x00AD Virtual IN 14 Off Virtual Input 14 Off
0x00AE Virtual IN 15 Off Virtual Input 15 Off
0x00AF Virtual IN 16 Off Virtual Input 16 Off
0x00B0 Virtual IN 17 Off Virtual Input 17 Off
0x00B1 Virtual IN 18 Off Virtual Input 18 Off
0x00B2 Virtual IN 19 Off Virtual Input 19 Off
0x00B3 Virtual IN 20 Off Virtual Input 20 Off
0x00B4 Virtual IN 21 Off Virtual Input 21 Off
0x00B5 Virtual IN 22 Off Virtual Input 22 Off
0x00B6 Virtual IN 23 Off Virtual Input 23 Off
0x00B7 Virtual IN 24 Off Virtual Input 24 Off
0x00B8 Virtual IN 25 Off Virtual Input 25 Off
0x00B9 Virtual IN 26 Off Virtual Input 26 Off
0x00BA Virtual IN 27 Off Virtual Input 27 Off
0x00BB Virtual IN 28 Off Virtual Input 28 Off
0x00BC Virtual IN 29 Off Virtual Input 29 Off
0x00BD Virtual IN 30 Off Virtual Input 30 Off
0x00BE Virtual IN 31 Off Virtual Input 31 Off
0x00BF Virtual IN 32 Off Virtual Input 32 Off
0x8002 Any Trip Any Trip
0x8042 Therm O/L Trip OP Thermal Overload Trip OP
0x804A Therm PhA Trip OP Thermal Phase A Trip OP
0x8052 Therm PhB Trip OP Thermal Phase B Trip OP
0x8062 Therm PhC Trip OP Thermal Phase C Trip OP
0x8082 PosSeq UV1 Trip OP Positive Sequence UV 1 Trip OP
0x8242 Arc Flash Trip OP Arc Flash Trip OP
0x83C2 Volt Hz Trip OP Volt Hz Trip OP
0x84C2 LE 1 Trip OP Logic Element 1 Trip OP
0x8502 LE 2 Trip OP Logic Element 2 Trip OP
0x8542 LE 3 Trip OP Logic Element 3 Trip OP
0x8582 LE 4 Trip OP Logic Element 4 Trip OP
0x85C2 LE 5 Trip OP Logic Element 5 Trip OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-179


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x8602 LE 6 Trip OP Logic Element 6 Trip OP
0x8642 LE 7 Trip OP Logic Element 7 Trip OP
0x8682 LE 8 Trip OP Logic Element 8 Trip OP
0x89C2 Self Test OP Self Test OP
0x8E82 Dir Pwr 1 Trip OP Directional Pwr 1 Trip OP
0x8EC2 Dir Pwr 2 Trip OP Directional Pwr 2 Trip OP
0x8F82 Fuse Fail Trip OP Fuse Fail Trip OP
0x8FC2 Brkn Cond Trip OP Broken Cond Trip OP
0x9002 Ph IOC1 Trip OP Phase IOC 1 Trip OP
0x900A Ph A IOC1 Trip OP Phase A IOC 1 Trip OP
0x9012 Ph B IOC1 Trip OP Phase B IOC 1 Trip OP
0x9022 Ph C IOC1 Trip OP Phase C IOC 1 Trip OP
0x9042 Ntrl IOC1 Trip OP Neutral IOC 1 Trip OP
0x9082 Gnd IOC1 Trip OP Ground IOC 1 Trip OP
0x90C2 Ph TOC1 Trip OP Phase TOC 1 Trip OP
0x90CA Ph A TOC1 Trip OP Phase A TOC 1 Trip OP
0x90D2 Ph B TOC1 Trip OP Phase B TOC 1 Trip OP
0x90E2 Ph C TOC1 Trip OP Phase C TOC 1 Trip OP
0x9102 Ntrl TOC1 Trip OP Neutral TOC 1 Trip OP
0x9142 Gnd TOC1 Trip OP Ground TOC 1 Trip OP
0x9182 Ph IOC2 Trip OP Phase IOC 2 Trip OP
0x918A Ph A IOC2 Trip OP Phase A IOC 2 Trip OP
0x9192 Ph B IOC2 Trip OP Phase B IOC 2 Trip OP
0x91A2 Ph C IOC2 Trip OP Phase C IOC 2 Trip OP
0x91C2 Ntrl IOC2 Trip OP Neutral IOC 2 Trip OP
0x9202 Gnd IOC2 Trip OP Ground IOC 2 Trip OP
0x9302 SGnd TOC1 Trip OP Sensitive Ground TOC 1 Trip OP
0x93C2 NSeq OV Trp OP Negative Sequence OV Trip OP
0x9402 Ntrl OV Trp OP Neutral OV Trip OP
0x9442 Ph OV1 Trip OP Phase OV 1 Trip OP
0x944A Ph A OV1 Trip OP Phase A OV1 Trip OP
0x9452 Ph B OV1 Trip OP Phase B OV1 Trip OP
0x9462 Ph C OV1 Trip OP Phase C OV1 Trip OP
0x9482 Ph UV1 Trip OP Phase UV 1 Trip OP
0x948A Ph A UV1 Trip OP Phase A UV1 Trip OP
0x9492 Ph B UV1 Trip OP Phase B UV1 Trip OP
0x94A2 Ph C UV1 Trip OP Phase C UV1 Trip OP
0x94C2 Aux OV Trip OP Auxiliary OV Trip OP
0x9502 Aux UV Trip OP Auxiliary UV Trip OP
0x9542 UndrFreq1 Trip OP Underfrequency 1 Trip OP
0x9582 UndrFreq2 Trip OP Underfrequency 2 Trip OP
0x95C2 OverFreq1 Trip OP Overfrequency 1 Trip OP
0x9602 OverFreq2 Trip OP Overfrequency 2 Trip OP
0x9642 SGnd IOC1 Trip OP Sensitive Ground IOC 1 Trip OP
0x9682 SGnd IOC2 Trip OP Sensitive Ground IOC 2 Trip OP
0x96C2 NSeq IOC Trp OP Negative Sequence IOC Trip OP
0x9702 Ph UV2 Trip OP Phase UV 2 Trip OP

12-180 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x970A Ph A UV2 Trip OP Phase A UV 2 Trip OP
0x9712 Ph B UV2 Trip OP Phase B UV 2 Trip OP
0x9722 Ph C UV2 Trip OP Phase C UV 2 Trip OP
0x9742 Ph UV3 Trip OP Phase UV 3 Trip OP
0x974A Ph A UV3 Trip OP Phase A UV 3 Trip OP
0x9752 Ph B UV3 Trip OP Phase B UV 3 Trip OP
0x9762 Ph C UV3 Trip OP Phase C UV 3 Trip OP
0x9782 Ph UV4 Trip OP Phase UV 4 Trip OP
0x978A Ph A UV4 Trip OP Phase A UV 4 Trip OP
0x9792 Ph B UV4 Trip OP Phase B UV 4 Trip OP
0x97A2 Ph C UV4 Trip OP Phase C UV 4 Trip OP
0x97C2 NSeq OV2 Trp OP Negative Sequence OV2 Trp OP
0x9802 NSeq TOC1 Trip OP Negative Sequence TOC 1 Trip OP
0x98C2 Ph OV2 Trip OP Phase OV 2 Trip OP
0x98CA Ph A OV2 Trip OP Phase A OV2 Trip OP
0x98D2 Ph B OV2 Trip OP Phase B OV2 Trip OP
0x98E2 Ph C OV2 Trip OP Phase C OV2 Trip OP
0x9902 Ph OV3 Trip OP Phase OV 3 Trip OP
0x990A Ph A OV3 Trip OP Phase A OV 3 Trip OP
0x9912 Ph B OV3 Trip OP Phase B OV 3 Trip OP
0x9922 Ph C OV3 Trip OP Phase C OV 3 Trip OP
0x9942 Ph OV4 Trip OP Phase OV 4 Trip OP
0x994A Ph A OV4 Trip OP Phase A OV 4 Trip OP
0x9952 Ph B OV4 Trip OP Phase B OV 4 Trip OP
0x9962 Ph C OV4 Trip OP Phase C OV 4 Trip OP
0x9982 Ntrl OV2 Trip OP Neutral OV 2 Trip OP
0x99C2 Ntrl OV3 Trip OP Neutral OV 3 Trip OP
0x9A02 Ntrl OV4 Trip OP Neutral OV 4 Trip OP
0x9A42 OverFreq3 Trip OP Overfrequency 3 Trip OP
0x9A82 OverFreq4 Trip OP Overfrequency 4 Trip OP
0x9AC2 UndFreq3 Trip OP Underfrequency 3 Trip OP
0x9B02 UndFreq4 Trip OP Underfrequency 4 Trip OP
0x9C02 LE 9 Trip OP Logic Element 9 Trip OP
0x9C42 LE 10 Trip OP Logic Element 10 Trip OP
0x9C82 LE 11 Trip OP Logic Element 11 Trip OP
0x9CC2 LE 12 Trip OP Logic Element 12 Trip OP
0x9D02 LE 13 Trip OP Logic Element 13 Trip OP
0x9D42 LE 14 Trip OP Logic Element 14 Trip OP
0x9D82 LE 15 Trip OP Logic Element 15 Trip OP
0x9DC2 LE 16 Trip OP Logic Element 16 Trip OP
0x9F02 WGF 1 Trip OP Wattmetric Gnd Fault 1 Trip OP
0x9F42 WGF 2 Trip OP Wattmetric Gnd Fault 2 Trip OP
FC134E unsigned 16 bits Fault Report Trigger
0x0000 Off Off
0x8002 Any Trip Any Trip
0x8042 Therm O/L Trip OP Thermal Overload Trip OP
0x804A Therm PhA Trip OP Thermal Phase A Trip OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-181


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x8052 Therm PhB Trip OP Thermal Phase B Trip OP
0x8062 Therm PhC Trip OP Thermal Phase C Trip OP
0x8082 PosSeq UV1 Trip OP Positive Sequence UV 1 Trip OP
0x8242 Arc Flash Trip OP Arc Flash Trip OP
0x83C2 Volt Hz Trip OP Volt Hz Trip OP
0x84C2 LE 1 Trip OP Logic Element 1 Trip OP
0x8502 LE 2 Trip OP Logic Element 2 Trip OP
0x8542 LE 3 Trip OP Logic Element 3 Trip OP
0x8582 LE 4 Trip OP Logic Element 4 Trip OP
0x85C2 LE 5 Trip OP Logic Element 5 Trip OP
0x8602 LE 6 Trip OP Logic Element 6 Trip OP
0x8642 LE 7 Trip OP Logic Element 7 Trip OP
0x8682 LE 8 Trip OP Logic Element 8 Trip OP
0x89C2 Self Test OP Self Test OP
0x8E82 Dir Pwr 1 Trip OP Directional Pwr 1 Trip OP
0x8EC2 Dir Pwr 2 Trip OP Directional Pwr 2 Trip OP
0x8F82 Fuse Fail Trip OP Fuse Fail Trip OP
0x8FC2 Brkn Cond Trip OP Broken Cond Trip OP
0x9002 Ph IOC1 Trip OP Phase IOC 1 Trip OP
0x900A Ph A IOC1 Trip OP Phase A IOC 1 Trip OP
0x9012 Ph B IOC1 Trip OP Phase B IOC 1 Trip OP
0x9022 Ph C IOC1 Trip OP Phase C IOC 1 Trip OP
0x9042 Ntrl IOC1 Trip OP Neutral IOC 1 Trip OP
0x9082 Gnd IOC1 Trip OP Ground IOC 1 Trip OP
0x90C2 Ph TOC1 Trip OP Phase TOC 1 Trip OP
0x90CA Ph A TOC1 Trip OP Phase A TOC 1 Trip OP
0x90D2 Ph B TOC1 Trip OP Phase B TOC 1 Trip OP
0x90E2 Ph C TOC1 Trip OP Phase C TOC 1 Trip OP
0x9102 Ntrl TOC1 Trip OP Neutral TOC 1 Trip OP
0x9142 Gnd TOC1 Trip OP Ground TOC 1 Trip OP
0x9182 Ph IOC2 Trip OP Phase IOC 2 Trip OP
0x918A Ph A IOC2 Trip OP Phase A IOC 2 Trip OP
0x9192 Ph B IOC2 Trip OP Phase B IOC 2 Trip OP
0x91A2 Ph C IOC2 Trip OP Phase C IOC 2 Trip OP
0x91C2 Ntrl IOC2 Trip OP Neutral IOC 2 Trip OP
0x9202 Gnd IOC2 Trip OP Ground IOC 2 Trip OP
0x9302 SGnd TOC1 Trip OP Sensitive Ground TOC 1 Trip OP
0x93C2 NSeq OV Trp OP Negative Sequence OV Trip OP
0x9402 Ntrl OV Trp OP Neutral OV Trip OP
0x9442 Ph OV1 Trip OP Phase OV 1 Trip OP
0x944A Ph A OV1 Trip OP Phase A OV1 Trip OP
0x9452 Ph B OV1 Trip OP Phase B OV1 Trip OP
0x9462 Ph C OV1 Trip OP Phase C OV1 Trip OP
0x9482 Ph UV1 Trip OP Phase UV 1 Trip OP
0x948A Ph A UV1 Trip OP Phase A UV1 Trip OP
0x9492 Ph B UV1 Trip OP Phase B UV1 Trip OP
0x94A2 Ph C UV1 Trip OP Phase C UV1 Trip OP

12-182 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x94C2 Aux OV Trip OP Auxiliary OV Trip OP
0x9502 Aux UV Trip OP Auxiliary UV Trip OP
0x9542 UndrFreq1 Trip OP Underfrequency 1 Trip OP
0x9582 UndrFreq2 Trip OP Underfrequency 2 Trip OP
0x95C2 OverFreq1 Trip OP Overfrequency 1 Trip OP
0x9602 OverFreq2 Trip OP Overfrequency 2 Trip OP
0x9642 SGnd IOC1 Trip OP Sensitive Ground IOC 1 Trip OP
0x9682 SGnd IOC2 Trip OP Sensitive Ground IOC 2 Trip OP
0x96C2 NSeq IOC Trp OP Negative Sequence IOC Trip OP
0x9702 Ph UV2 Trip OP Phase UV 2 Trip OP
0x970A Ph A UV2 Trip OP Phase A UV 2 Trip OP
0x9712 Ph B UV2 Trip OP Phase B UV 2 Trip OP
0x9722 Ph C UV2 Trip OP Phase C UV 2 Trip OP
0x9742 Ph UV3 Trip OP Phase UV 3 Trip OP
0x974A Ph A UV3 Trip OP Phase A UV 3 Trip OP
0x9752 Ph B UV3 Trip OP Phase B UV 3 Trip OP
0x9762 Ph C UV3 Trip OP Phase C UV 3 Trip OP
0x9782 Ph UV4 Trip OP Phase UV 4 Trip OP
0x978A Ph A UV4 Trip OP Phase A UV 4 Trip OP
0x9792 Ph B UV4 Trip OP Phase B UV 4 Trip OP
0x97A2 Ph C UV4 Trip OP Phase C UV 4 Trip OP
0x97C2 NSeq OV2 Trp OP Negative Sequence OV2 Trp OP
0x9802 NSeq TOC1 Trip OP Negative Sequence TOC 1 Trip OP
0x98C2 Ph OV2 Trip OP Phase OV 2 Trip OP
0x98CA Ph A OV2 Trip OP Phase A OV2 Trip OP
0x98D2 Ph B OV2 Trip OP Phase B OV2 Trip OP
0x98E2 Ph C OV2 Trip OP Phase C OV2 Trip OP
0x9902 Ph OV3 Trip OP Phase OV 3 Trip OP
0x990A Ph A OV3 Trip OP Phase A OV 3 Trip OP
0x9912 Ph B OV3 Trip OP Phase B OV 3 Trip OP
0x9922 Ph C OV3 Trip OP Phase C OV 3 Trip OP
0x9942 Ph OV4 Trip OP Phase OV 4 Trip OP
0x994A Ph A OV4 Trip OP Phase A OV 4 Trip OP
0x9952 Ph B OV4 Trip OP Phase B OV 4 Trip OP
0x9962 Ph C OV4 Trip OP Phase C OV 4 Trip OP
0x9982 Ntrl OV2 Trip OP Neutral OV 2 Trip OP
0x99C2 Ntrl OV3 Trip OP Neutral OV 3 Trip OP
0x9A02 Ntrl OV4 Trip OP Neutral OV 4 Trip OP
0x9A42 OverFreq3 Trip OP Overfrequency 3 Trip OP
0x9A82 OverFreq4 Trip OP Overfrequency 4 Trip OP
0x9AC2 UndFreq3 Trip OP Underfrequency 3 Trip OP
0x9B02 UndFreq4 Trip OP Underfrequency 4 Trip OP
0x9C02 LE 9 Trip OP Logic Element 9 Trip OP
0x9C42 LE 10 Trip OP Logic Element 10 Trip OP
0x9C82 LE 11 Trip OP Logic Element 11 Trip OP
0x9CC2 LE 12 Trip OP Logic Element 12 Trip OP
0x9D02 LE 13 Trip OP Logic Element 13 Trip OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-183


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x9D42 LE 14 Trip OP Logic Element 14 Trip OP
0x9D82 LE 15 Trip OP Logic Element 15 Trip OP
0x9DC2 LE 16 Trip OP Logic Element 16 Trip OP
0x9F02 WGF 1 Trip OP Wattmetric Gnd Fault 1 Trip OP
0x9F42 WGF 2 Trip OP Wattmetric Gnd Fault 2 Trip OP
FC134F unsigned 16 bits Lockout Reset
0 Off Off
0x0001 On On
0x0040 Contact IN 1 On Contact Input 1 On
0x0041 Contact IN 2 On Contact Input 2 On
0x0042 Contact IN 3 On Contact Input 3 On
0x0043 Contact IN 4 On Contact Input 4 On
0x0044 Contact IN 5 On Contact Input 5 On
0x0045 Contact IN 6 On Contact Input 6 On
0x0046 Contact IN 7 On Contact Input 7 On
0x0047 Contact IN 8 On Contact Input 8 On
0x0048 Contact IN 9 On Contact Input 9 On
0x0049 Contact IN 10 On Contact Input 10 On
0x0060 Contact IN 1 Off Contact Input 1 Off
0x0061 Contact IN 2 Off Contact Input 2 Off
0x0062 Contact IN 3 Off Contact Input 3 Off
0x0063 Contact IN 4 Off Contact Input 4 Off
0x0064 Contact IN 5 Off Contact Input 5 Off
0x0065 Contact IN 6 Off Contact Input 6 Off
0x0066 Contact IN 7 Off Contact Input 7 Off
0x0067 Contact IN 8 Off Contact Input 8 Off
0x0068 Contact IN 9 Off Contact Input 9 Off
0x0069 Contact IN 10 Off Contact Input 10 Off
0x0080 Virtual IN 1 On Virtual Input 1 On
0x0081 Virtual IN 2 On Virtual Input 2 On
0x0082 Virtual IN 3 On Virtual Input 3 On
0x0083 Virtual IN 4 On Virtual Input 4 On
0x0084 Virtual IN 5 On Virtual Input 5 On
0x0085 Virtual IN 6 On Virtual Input 6 On
0x0086 Virtual IN 7 On Virtual Input 7 On
0x0087 Virtual IN 8 On Virtual Input 8 On
0x0088 Virtual IN 9 On Virtual Input 9 On
0x0089 Virtual IN 10 On Virtual Input 10 On
0x008A Virtual IN 11 On Virtual Input 11 On
0x008B Virtual IN 12 On Virtual Input 12 On
0x008C Virtual IN 13 On Virtual Input 13 On
0x008D Virtual IN 14 On Virtual Input 14 On
0x008E Virtual IN 15 On Virtual Input 15 On
0x008F Virtual IN 16 On Virtual Input 16 On
0x0090 Virtual IN 17 On Virtual Input 17 On
0x0091 Virtual IN 18 On Virtual Input 18 On
0x0092 Virtual IN 19 On Virtual Input 19 On

12-184 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x0093 Virtual IN 20 On Virtual Input 20 On
0x0094 Virtual IN 21 On Virtual Input 21 On
0x0095 Virtual IN 22 On Virtual Input 22 On
0x0096 Virtual IN 23 On Virtual Input 23 On
0x0097 Virtual IN 24 On Virtual Input 24 On
0x0098 Virtual IN 25 On Virtual Input 25 On
0x0099 Virtual IN 26 On Virtual Input 26 On
0x009A Virtual IN 27 On Virtual Input 27 On
0x009B Virtual IN 28 On Virtual Input 28 On
0x009C Virtual IN 29 On Virtual Input 29 On
0x009D Virtual IN 30 On Virtual Input 30 On
0x009E Virtual IN 31 On Virtual Input 31 On
0x009F Virtual IN 32 On Virtual Input 32 On
0xA4C2 LE 1 Alarm OP Logic Element 1 Alarm OP
0xA502 LE 2 Alarm OP Logic Element 2 Alarm OP
0xA542 LE 3 Alarm OP Logic Element 3 Alarm OP
0xA582 LE 4 Alarm OP Logic Element 4 Alarm OP
0xA5C2 LE 5 Alarm OP Logic Element 5 Alarm OP
0xA602 LE 6 Alarm OP Logic Element 6 Alarm OP
0xA642 LE 7 Alarm OP Logic Element 7 Alarm OP
0xA682 LE 8 Alarm OP Logic Element 8 Alarm OP
0xBC02 LE 9 Alarm OP Logic Element 9 Alarm OP
0xBC42 LE 10 Alarm OP Logic Element 10 Alarm OP
0xBC82 LE 11 Alarm OP Logic Element 11 Alarm OP
0xBCC2 LE 12 Alarm OP Logic Element 12 Alarm OP
0xBD02 LE 13 Alarm OP Logic Element 13 Alarm OP
0xBD42 LE 14 Alarm OP Logic Element 14 Alarm OP
0xBD82 LE 15 Alarm OP Logic Element 15 Alarm OP
0xBDC2 LE 16 Alarm OP Logic Element 16 Alarm OP
0xC4C2 LE 1 OP Logic Element 1 OP
0xC502 LE 2 OP Logic Element 2 OP
0xC542 LE 3 OP Logic Element 3 OP
0xC582 LE 4 OP Logic Element 4 OP
0xC5C2 LE 5 OP Logic Element 5 OP
0xC602 LE 6 OP Logic Element 6 OP
0xC642 LE 7 OP Logic Element 7 OP
0xC682 LE 8 OP Logic Element 8 OP
0xDC02 LE 9 OP Logic Element 9 OP
0xDC42 LE 10 OP Logic Element 10 OP
0xDC82 LE 11 OP Logic Element 11 OP
0xDCC2 LE 12 OP Logic Element 12 OP
0xDD02 LE 13 OP Logic Element 13 OP
0xDD42 LE 14 OP Logic Element 14 OP
0xDD82 LE 15 OP Logic Element 15 OP
0xDDC2 LE 16 OP Logic Element 16 OP
FC135 unsigned 16 bits Motor Speed During Trip / Motor Speed
During Event

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-185


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


FC136 unsigned 16 bits Motor Speed During Trip / Motor Speed
During Event
0 None None
1 A A
2 B B
FC139 unsigned 16 bits Starter Type
0 None None
4 Wye-Delta Wye-Delta
5 Inverter Inverter
6 Soft Starter Soft Starter
7 Custom Starter Custom Starter
FC140 unsigned 16 bits Interlock Function
0 Disabled Disabled
1 Trip Trip
2 Alarm Alarm
FC141 unsigned 16 bits Timer Type
0 Millisecond Millisecond
1 Second Second
2 Minute Minute
FC142 unsigned 16 bits FlexLogic Bit Field EEETTTTTTTSSSSSS
0x0000 Off Off
0x0001 On On
0x0040 Contact Inputs Contact Inputs
0x0080 Virtual Inputs Virtual Inputs
0x00C0 Virtual Outputs Virtual Outputs
0x01C0 Remote Inputs Remote Inputs
0x0380 Insert Insert
0x0400 End End
0x0440 NOT NOT
0x0480 XOR XOR
0x04C0 LATCH LATCH
0x0500 OR OR
0x0540 AND AND
0x0580 NOR NOR
0x05C0 NAND NAND
0x0600 TIMER TIMER
0x0640 ASSIGN ASSIGN
0x8000 Trip Trip
0x8E81 Dir Pwr 1 Trip PKP Directional Pwr 1 Trip PKP
0x8E82 Dir Pwr 1 Trip OP Directional Pwr 1 Trip OP
0x8EC1 Dir Pwr 2 Trip PKP Directional Pwr 2 Trip PKP
0x8EC2 Dir Pwr 2 Trip OP Directional Pwr 2 Trip OP
0x8FC1 Brkn Cond Trip PKP Broken Cond Trip PKP
0x8FC2 Brkn Cond Trip OP Broken Cond Trip OP
0x8FC4 Brkn Cond Trip DPO Broken Cond Trip DPO
0x9F01 WGF 1 Trip PKP Wattmetric Gnd Fault 1 Trip PKP
0x9F02 WGF 1 Trip OP Wattmetric Gnd Fault 1 Trip OP

12-186 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x9F04 WGF 1 Trip DPO Wattmetric Gnd Fault 1 Trip DPO
0x9F41 WGF 2 Trip PKP Wattmetric Gnd Fault 2 Trip PKP
0x9F42 WGF 2 Trip OP Wattmetric Gnd Fault 2 Trip OP
0x9F44 WGF 2 Trip DPO Wattmetric Gnd Fault 2 Trip DPO
0xA000 Alarm Alarm
0xAE81 Dir Pwr 1 Alrm PKP Directional Pwr 1 Alarm PKP
0xAE82 Dir Pwr 1 Alarm OP Directional Pwr 1 Alarm OP
0xAEC1 Dir Pwr 2 Alrm PKP Directional Pwr 2 Alarm PKP
0xAEC2 Dir Pwr 2 Alarm OP Directional Pwr 2 Alarm OP
0xAF01 2nd Hrmc Alarm PKP 2nd Harmonic Alarm PKP
0xAF02 2nd Hrmc Alarm OP 2nd Harmonic Alarm OP
0xAF04 2nd Hrmc Alarm DPO 2nd Harmonic Alarm DPO
0xAFC1 Brkn Cond Alrm PKP Broken Cond Alarm PKP
0xAFC2 Brkn Cond Alarm OP Broken Cond Alarm OP
0xAFC4 Brkn Cond Alrm DPO Broken Cond Alarm DPO
0xB881 CTFail Alrm PKP CT Fail Alarm PKP
0xB882 CTFail Alrm OP CT Fail Alarm OP
0xB884 CTFail Alrm DPO CT Fail Alarm DPO
0xBE02 PhDir RevAlm OP Ph Directional Reverse Alarm OP
0xBE04 PhDir RevAlm DPO Ph Directional Reverse Alarm DPO
0xBE0A PhADir RevAlm OP Ph A Directional Reverse Alarm OP
0xBE0C PhADir RevAlm DPO Ph A Directional Reverse Alarm DPO
0xBE12 PhBDir RevAlm OP Ph B Directional Reverse Alarm OP
0xBE14 PhBDir RevAlm DPO Ph B Directional Reverse Alarm DPO
0xBE22 PhCDir RevAlm OP Ph C Directional Reverse Alarm OP
0xBE24 PhCDir RevAlm DPO Ph C Directional Reverse Alarm DPO
0xBE42 PhDir UndAlm OP Ph Directional Und Alarm OP
0xBE44 PhDir UndAlm DPO Ph Directional Und Alarm DPO
0xBE4A PhADir UndAlm OP Ph A Directional Und Alarm OP
0xBE4C PhADir UndAlm DPO Ph A Directional Und Alarm DPO
0xBE52 PhBDir UndAlm OP Ph B Directional Und Alarm OP
0xBE54 PhBDir UndAlm DPO Ph B Directional Und Alarm DPO
0xBE62 PhCDir UndAlm OP Ph C Directional Und Alarm OP
0xBE64 PhCDir UndAlm DPO Ph C Directional Und Alarm DPO
0xBE82 GndDir UndAlm OP Ground Directional Und Alarm OP
0xBE84 GndDir UndAlm DPO Ground Directional Und Alarm DPO
0xBEC2 NtrlDir UndAlm OP Neutral Directional Und Alarm OP
0xBEC4 NtrlDir UndAlm DPO Neutral Directional Und Alarm DPO
0xBF01 WGF 1 Alarm PKP Wattmetric Gnd Fault 1 Alarm PKP
0xBF02 WGF 1 Alarm OP Wattmetric Gnd Fault 1 Alarm OP
0xBF04 WGF 1 Alarm DPO Wattmetric Gnd Fault 1 Alarm DPO
0xBF41 WGF 2 Alarm PKP Wattmetric Gnd Fault 2 Alarm PKP
0xBF42 WGF 2 Alarm OP Wattmetric Gnd Fault 2 Alarm OP
0xBF44 WGF 2 Alarm DPO Wattmetric Gnd Fault 2 Alarm DPO
0xC000 Control Control
0xC302 Sync Operation Synchrocheck Operation
0xC342 Sync Close OP Synchrocheck Close OP

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-187


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0xC382 Sync Condition Synchrocheck Condition
0xCE81 Dir Pwr 1 PKP Directional Pwr 1 PKP
0xCE82 Dir Pwr 1 OP Directional Pwr 1 OP
0xCEC1 Dir Pwr 2 PKP Directional Pwr 2 PKP
0xCEC2 Dir Pwr 2 OP Directional Pwr 2 OP
0xCF01 2nd Hrmc PKP 2nd Harmonic PKP
0xCF02 2nd Hrmc OP 2nd Harmonic OP
0xCF04 2nd Hrmc DPO 2nd Harmonic DPO
0xCFC1 Brkn Cond PKP Broken Cond PKP
0xCFC2 Brkn Cond OP Broken Cond OP
0xCFC4 Brkn Cond DPO Broken Cond DPO
0xD881 CTFail PKP CT Fail PKP
0xD882 CTFail OP CT Fail OP
0xD884 CTFail DPO CT Fail DPO
0xDE02 PhDir Rev OP Ph Directional Reverse OP
0xDE04 PhDir Rev DPO Ph Directional Reverse DPO
0xDE0A PhADir Rev OP Ph A Directional Reverse OP
0xDE0C PhADir Rev DPO Ph A Directional Reverse DPO
0xDE12 PhBDir Rev OP Ph B Directional Reverse OP
0xDE14 PhBDir Rev DPO Ph B Directional Reverse DPO
0xDE22 PhCDir Rev OP Ph C Directional Reverse OP
0xDE24 PhCDir Rev DPO Ph C Directional Reverse DPO
0xDE42 PhDir Und OP Ph Directional Und OP
0xDE44 PhDir Und DPO Ph Directional Und DPO
0xDE4A PhADir Und OP Ph A Directional Und OP
0xDE4C PhADir Und DPO Ph A Directional Und DPO
0xDE52 PhBDir Und OP Ph B Directional Und OP
0xDE54 PhBDir Und DPO Ph B Directional Und DPO
0xDE62 PhCDir Und OP Ph C Directional Und OP
0xDE64 PhCDir Und DPO Ph C Directional Und DPO
0xDE82 GndDir Und OP Ground Directional Und OP
0xDE84 GndDir Und DPO Ground Directional Und DPO
0xDEC2 NtrlDir Und OP Neutral Directional Und OP
0xDEC4 NtrlDir Und DPO Neutral Directional Und DPO
0xDF01 WGF 1 PKP Wattmetric Gnd Fault 1 PKP
0xDF02 WGF 1 OP Wattmetric Gnd Fault 1 OP
0xDF04 WGF 1 DPO Wattmetric Gnd Fault 1 DPO
0xDF41 WGF 2 PKP Wattmetric Gnd Fault 2 PKP
0xDF42 WGF 2 OP Wattmetric Gnd Fault 2 OP
0xDF44 WGF 2 DPO Wattmetric Gnd Fault 2 DPO
0xEE81 Dir Pwr 1 Blk PKP Directional Pwr 1 Block PKP
0xEE82 Dir Pwr 1 Block Directional Pwr 1 Block
0xEEC1 Dir Pwr 2 Blk PKP Directional Pwr 2 Block PKP
0xEEC2 Dir Pwr 2 Block Directional Pwr 2 Block
0xEFC1 Brkn Cond Blk PKP Broken Cond Block PKP
0xEFC2 Brkn Cond Block Broken Cond Block
0xF881 CTFail Block PKP CT Fail Block PKP

12-188 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0xF882 CTFail Block CT Fail Block
0xFE02 PhDir Block Ph Directional Block
0xFE0A PhADir Block PhA Directional Block
0xFE12 PhBDir Block PhB Directional Block
0xFE22 PhCDir Block PhC Directional Block
0xFF01 WGF 1 BlockPKP Wattmetric Gnd Fault 1 Block PKP
0xFF02 WGF 1 Block Wattmetric Gnd Fault 1 Block
0xFF41 WGF 2 BlockPKP Wattmetric Gnd Fault 2 Block PKP
0xFF42 WGF 2 Block Wattmetric Gnd Fault 2 Block
FC143 unsigned 16 bits Drive Status
0 Drive Unavailable Drive Unavailable
1 Available Auto Available Auto
2 Available Manual Available Manual
3 Available Available
4 Running Running
5 ESD Trip / Stop ESD Trip / Stop
FC144 unsigned 32 bits LED Status - 350
0x00000002 In Service Green In Service Green
0x00000004 Trouble Red Trouble Red
0x00000008 Trouble Green Trouble Green
0x00000020 SP Group 1 Green SP Group 1 Green
0x00000080 SP Group 2 Green SP Group 2 Green
0x00000040 Trip Red Trip Red
0x00000400 Alarm Red Alarm Red
0x00000800 Alarm Green Alarm Green
0x00001000 Pickup Red Pickup Red
0x00002000 Pickup Green Pickup Green
0x00004000 Maintenance Red Maintenance Red
0x00008000 Maintenance Green Maintenance Green
0x00010000 BKR Open Red BKR Open Red
0x00020000 BKR Open Green BKR Open Green
0x00040000 BKR Closed Red BKR Closed Red
0x00080000 BKR Closed Green BKR Closed Green
FC144A unsigned 32 bits LED Status - 339
FC144B unsigned 32 bits LED Status - 345
FC145 unsigned 16 bits Element Status 1
FC146 unsigned 16 bits Element Status 2
FC147 unsigned 16 bits LED Intensity
0 Level 1 Level 1
12 Level 5 Level 5
15 Level 6 Level 6
3 Level 2 Level 2
6 Level 3 Level 3
9 Level 4 Level 4
FC148 unsigned 16 bits Trigger Mode
0 Overwrite Overwrite
1 Protected Protected

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-189


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


FC149 unsigned 16 bits OR / AND Selection
0 OR OR
1 AND AND
2 NOR NOR
3 NAND NAND
4 XOR XOR
5 XNOR XNOR
FC149A unsigned 16 bits AND / LATCH Selection
0 AND AND
1 LATCH LATCH
FC150 unsigned 32 bits IP Address
FC155 unsigned 16 bits Profibus Baud Rate
0x0001 9600 9600
0x0002 19200 19200
0x0004 31250 31250
0x0008 45450 45450
0x0010 93750 93750
0x0020 187500 187500
0x0040 500000 500000
0x0080 1500000 1500000
0x07E2 Auto Detect Auto Detect
FC156 unsigned 16 bits DeviceNet Baud Rate
0 125 kbps 125 kbps
1 250 kbps 250 kbps
2 500 kbps 500 kbps
FC157 unsigned 16 bits LED Colour
0 Off Off
1 Red Red
2 Green Green
3 Orange Orange
FC157A unsigned 16 bits LED Colour (Subset A)
0 None None
1 Red Red
2 Green Green
FC160 unsigned 16 bits Auto/Manual Mode
0 Auto Auto
1 Manual Manual
FC167 unsigned 32 bits Contact/Virtual Input/Output Status
FC168 unsigned 32 bits Contact/Virtual Input/Output Status
FC169 unsigned 16 bits Month
0 Not Set Not Set
1 January January
2 February February
3 March March
4 April April
5 May May
6 June June

12-190 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


7 July July
8 August August
9 September September
10 October October
11 November November
12 December December
FC170 unsigned 16 bits Count of Week
0 Not Set Not Set
1 1st 1st
2 2nd 2nd
3 3rd 3rd
4 4th 4th
5 Last Last
FC171 unsigned 16 bits Weekdays
0 Not Set Not Set
1 SUN SUN
2 MON MON
3 TUE TUE
4 WED WED
5 THU THU
6 FRI FRI
7 SAT SAT
FC172 unsigned 16 bits Auto/Manual Control Stop Mode
0 Always Enabled Always Enabled
1 Follow Ctrl Mode Follow Control Mode
FC173 unsigned 16 bits Wire Selection
0 2W 2W
1 3W 3W
FC174 unsigned 16 bits Source Stop Action
0 Stop Stop
1 Trip Trip
FC175 unsigned 16 bits Test Auto/Manual Mode
0 On On
1 Off Off
2 Unaffected Unaffected
FC176 unsigned 16 bits Auxiliary VT Connection
0 Vab VT Vab VT
1 Vbc VT Vbc VT
2 Vca VT Vca VT
3 Van VT Van VT
4 Vbn VT Vbn VT
5 Vcn VT Vcn VT
6 Vn Vn
FC177 unsigned 16 bits LED Color Invert
0 Green/Red Green/Red
1 Red/Green Red/Green
FC178 unsigned 16 bits Motor Status

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-191


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


FC179 unsigned 32 bits Alarm Status 1
0x00000001 Any Alarm Any Alarm
0x00000002 Therm Level Alarm Thermal Level Alarm
0x00000004 Gnd Fault Alarm Gnd Fault Alarm
0x00000008 Acceleration Alarm Acceleration Alarm
0x00000020 Under Pwr Alarm Under Power Alarm
0x00000040 Reserved Reserved
0x00000080 Reserved Reserved
0x00000100 Mech Jam Alarm Mechanical Jam Alarm
0x00000200 Under Curr Alarm Undercurrent Alarm
0x00000400 Unbalance Alarm Unbalance Alarm
0x00000800 RTD 1 Alarm RTD 1 Alarm
0x00001000 RTD 2 Alarm RTD 2 Alarm
0x00002000 RTD 3 Alarm RTD 3 Alarm
0x00004000 RTD 4 Alarm RTD 4 Alarm
0x00008000 RTD 5 Alarm RTD 5 Alarm
0x00010000 RTD 6 Alarm RTD 6 Alarm
0x00020000 RTD Trouble Alarm RTD Trouble Alarm
0x00040000 Not Configured Not Configured
0x00080000 LE 1 Alarm Logic Element 1 Alarm
0x00100000 LE 2 Alarm Logic Element 2 Alarm
0x00200000 LE 3 Alarm Logic Element 3 Alarm
0x00400000 LE 4 Alarm Logic Element 4 Alarm
0x00800000 LE 5 Alarm Logic Element 5 Alarm
0x01000000 LE 6 Alarm Logic Element 6 Alarm
0x02000000 LE 7 Alarm Logic Element 7 Alarm
0x04000000 LE 8 Alarm Logic Element 8 Alarm
0x08000000 RTD 7 Alarm RTD 7 Alarm
0x10000000 RTD 8 Alarm RTD 8 Alarm
0x20000000 RTD 9 Alarm RTD 9 Alarm
0x40000000 RTD 10 Alarm RTD 10 Alarm
0x80000000 RTD 11 Alarm RTD 11 Alarm
FC180 unsigned 32 bits Alarm Status 2
0x00000001 RTD 12 Alarm RTD 12 Alarm
0x00000002 Reserved Reserved
0x00000004 Reserved Reserved
0x00000008 Reserved Reserved
0x00000010 Reserved Reserved
0x00000020 Reserved Reserved
0x00000040 Motor Run Hrs Motor Running Hours
0x00000080 I^2 Counter Alarm I^2 Counter Alarm
0x00000100 Welded Contactor Welded Contactor
0x00000800 Reserved Reserved
0x00001000 Load Increase Alrm Load Increase Alarm
0x00002000 Reserved Reserved
0x00004000 Reserved Reserved
0x00008000 High Ambient Temp High Ambient Temperature Alarm

12-192 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x00010000 Low Ambient Temp Low Ambient Temperature Alarm
0x00020000 Self Test Alarm Self Test Alarm
0x00040000 Comm Fail Alarm Comm Fail Alarm
0x00080000 BKRTrip Cntr Alarm Breaker Trip Counter Alarm
0x00100000 Rly1 74 Alarm Relay 1 74 Alarm
0x00200000 Rly2 74 Alarm Relay 2 74 Alarm
0x00400000 BKR Fail Alarm Breaker Fail Alarm
0x00800000 BKR Status Failure Breaker Status Failure
0x01000000 Reserved Reserved
0x02000000 CLP Alarm Cold Load PKP Alarm
0x04000000 Reserved Reserved
0x08000000 BKR2 Status Fail Breaker 2 Status Failure
0x10000000 Reserved Reserved
0x20000000 BKR2 Fail Alrm Breaker 2 Failure Alarm
0x40000000 FuseFail Alarm Fuse Fail Alarm
0x80000000 Ph Revrsl Alarm Phase Reversal Alarm
FC181 unsigned 32 bits Alarm Status 3
0x00000001 Ph IOC1 Alarm Phase IOC 1 Alarm
0x00000002 Ntrl IOC1 Alarm Neutral IOC 1 Alarm
0x00000004 Gnd IOC1 Alarm Ground IOC 1 Alarm
0x00000008 Ph TOC1 Alarm Phase TOC 1 Alarm
0x00000010 Ntrl TOC1 Alarm Neutral TOC1 Alarm
0x00000020 Gnd TOC1 Alarm Sensitive Ground TOC 1 Alarm
0x00000040 Ph IOC2 Alarm Phase IOC 2 Alarm
0x00000080 Ntrl IOC2 Alarm Neutral IOC 2 Alarm
0x00000100 Gnd IOC2 Alarm Ground IOC 2 Alarm
0x00000200 Ph TOC2 Alrm Phase TOC 2 Alarm
0x00000400 Ntrl TOC2 Alarm Neutral TOC 2 Alarm
0x00000800 Gnd TOC2 Alrm Sensitive Ground TOC 2 Alarm
0x00001000 SGnd TOC1 Alarm Sensitive Ground TOC 1 Alarm
0x00002000 Ntrl Dir Rev Alm Neutral Directional Alarm
0x00004000 Gnd Dir Alarm Ground Directional Alarm
0x00008000 NSeq OV Alarm Negative Sequence OV Alarm
0x00010000 Ntrl OV Alarm Ntrl OV Alarm
0x00020000 Phase OV Alarm Phase OV Alarm
0x00040000 Phase UV Alarm Phase UV Alarm
0x00080000 Aux OV Alarm Auxiliary OV Alarm
0x00100000 Aux UV Alarm Auxiliary UV Alarm
0x00200000 UnderFreq1 Alarm Underfrequency 1 Alarm
0x00400000 UnderFreq2 Alarm Underfrequency 2 Alarm
0x00800000 OverFreq1 Alrm Overfrequency 1 Alarm
0x01000000 OverFreq2 Alrm Overfrequency 2 Alarm
0x02000000 SGnd IOC1 Alarm Sensitive Ground IOC 1 Alarm
0x04000000 SGnd IOC2 Alarm Sensitive Ground IOC 2 Alarm
0x08000000 Nseq IOC Alarm Negative Sequence IOC Alarm
0x10000000 Diff 87P Alarm Diff 87P Alarm
0x20000000 Diff 87REF 1 Alarm Diff 87REF 1 Alarm

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-193


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x40000000 Diff 87REF 2 Alarm Diff 87REF 2 Alarm
0x80000000 Inst 50/87P Alarm Inst 50/87P Alarm
FC182 unsigned 32 bits Alarm Status 4
0x00000001 NSeq TOC1 Alarm Negative Sequence TOC 1 Alarm
0x00000002 NSeq TOC2 Alarm Negative Sequence TOC 2 Alarm
0x00000004 Ph OV2 Alarm Phase OV 2 Alarm
0x00000008 Ph UV2 Alarm Phase UV 2 Alarm
0x00000010 Short Circuit Alrm Short Circuit Alarm
0x00000020 SPD2 S/C Alarm SPD2 S/C Alarm
0x00000040 SPD2 U/C Alarm SPD2 U/C Alarm
0x00000080 SGnd TOC2 Alarm Sensitive Ground TOC 2 Alarm
0x00000100 Reserved Reserved
0x00000200 Reserved Reserved
0x00000400 Reserved Reserved
0x00000800 Reserved Reserved
0x00001000 Reserved Reserved
0x00002000 Reserved Reserved
0x00004000 Reserved Reserved
0x00008000 Reserved Reserved
0x00010000 LE 9 Alarm Logic Element 9 Alarm
0x00020000 LE 10 Alarm Logic Element 10 Alarm
0x00040000 LE 11 Alarm Logic Element 11 Alarm
0x00080000 LE 12 Alarm Logic Element 12 Alarm
0x00100000 LE 13 Alarm Logic Element 13 Alarm
0x00200000 LE 14 Alarm Logic Element 14 Alarm
0x00400000 LE 15 Alarm Logic Element 15 Alarm
0x00800000 LE 16 Alarm Logic Element 16 Alarm
0x01000000 Reserved Reserved
0x02000000 Reserved Reserved
0x04000000 Reserved Reserved
0x08000000 Reserved Reserved
0x10000000 Reserved Reserved
0x20000000 Reserved Reserved
0x40000000 Reserved Reserved
0x80000000 Reserved Reserved
FC183 unsigned 32 bits Trip Status 1
0x00000001 Any Trip Any Trip
0x00000002 Therm O/L Trip Thermal O/L Trip
0x00000004 Gnd Fault Trip Gnd Fault Trip
0x00000008 Acceleration Trip Acceleration Trip
0x00000020 Under Pwr Trip Under Power Trip
0x00000040 Single Phase Trip Single Phase Trip
0x00000080 Reserved Reserved
0x00000100 Mech Jam Trip Mechanical Jam Trip
0x00000200 Under Curr Trip Undercurrent Trip
0x00000400 Unbalance Trip Unbalance Trip
0x00000800 RTD 1 Trip RTD 1 Trip

12-194 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x00001000 RTD 2 Trip RTD 2 Trip
0x00002000 RTD 3 Trip RTD 3 Trip
0x00004000 RTD 4 Trip RTD 4 Trip
0x00008000 RTD 5 Trip RTD 5 Trip
0x00010000 RTD 6 Trip RTD 6 Trip
0x00020000 Comm Fail Trip Comm Fail Trip
0x00040000 Relay Not Config. Relay Not Configured
0x00080000 LE 1 Trip Logic Element 1 Trip
0x00100000 LE 2 Trip Logic Element 2 Trip
0x00200000 LE 3 Trip Logic Element 3 Trip
0x00400000 LE 4 Trip Logic Element 4 Trip
0x00800000 LE 5 Trip Logic Element 5 Trip
0x01000000 LE 6 Trip Logic Element 6 Trip
0x02000000 LE 7 Trip Logic Element 7 Trip
0x04000000 LE 8 Trip Logic Element 8 Trip
0x08000000 RTD 7 Trip RTD 7 Trip
0x10000000 RTD 8 Trip RTD 8 Trip
0x20000000 RTD 9 Trip RTD 9 Trip
0x40000000 RTD 10 Trip RTD 10 Trip
0x80000000 RTD 11 Trip RTD 11 Trip
FC184 unsigned 32 bits Trip Status 2
0x00000001 RTD 12 Trip RTD 12 Trip
0x00000002 Reserved Reserved
0x00000004 Reserved Reserved
0x00000008 Reserved Reserved
0x00000010 Reserved Reserved
0x00000020 Reserved Reserved
0x00000040 Reserved Internal Temperature Trip
0x00000080 Self Test Trip Self Test Trip
0x00000100 Reserved Reserved
0x00000200 Reserved Reserved
0x00000400 Reserved Reserved
0x00000800 Reserved Reserved
0x00001000 Reserved Reserved
0x00002000 Reserved Reserved
0x00004000 Reserved Reserved
0x00008000 Reserved Reserved
0x00010000 Reserved Reserved
0x00020000 Reserved Reserved
0x00040000 Reserved Reserved
0x00080000 BKRTrip Cntr Trip Breaker Trip Counter Trip
0x00100000 Rly1 74 Trip Relay 1 74 Trip
0x00200000 Rly2 74 Trip Relay 2 74 Trip
0x00400000 BKR Failure Breaker Failure
0x00800000 Reserved Reserved
0x01000000 Reserved Reserved
0x02000000 Reserved Reserved

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-195


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x04000000 Reserved Reserved
0x08000000 Reserved Reserved
0x10000000 Reserved Reserved
0x20000000 BKR 2 Failure Breaker 2 Failure
0x40000000 FuseFail Trip FuseFail Trip
0x80000000 Ph Revrsl Trip Phase Reversal Trip
FC185 unsigned 32 bits Trip Status 3
0x00000001 Ph IOC1 Trip Phase IOC 1 Trip
0x00000002 Ntrl IOC1 Trip Neutral IOC 1 Trip
0x00000004 Gnd IOC1 Trip Ground IOC 1 Trip
0x00000008 Ph TOC1 Trip Phase TOC 1 Trip
0x00000010 Ntrl TOC1 Trip Neutral TOC1 Trip
0x00000020 Gnd TOC1 Trip Sensitive Ground TOC 1 Trip
0x00000040 Ph IOC2 Trip Phase IOC 2 Trip
0x00000080 Ntrl IOC2 Trip Neutral IOC 2 Trip
0x00000100 Gnd IOC2 Trip Ground IOC 2 Trip
0x00000200 Ph TOC2 Trip Phase TOC 2 Trip
0x00000400 Ntrl TOC2 Trip Neutral TOC 2 Trip
0x00000800 Gnd TOC2 Trip Sensitive Ground TOC 2 Trip
0x00001000 SGnd TOC1 Trip Sensitive Ground TOC 1 Trip
0x00002000 Reserved Reserved
0x00004000 Reserved Reserved
0x00008000 NSeq OV Trip Negative Sequence OV Trip
0x00010000 Ntrl OV Trip Ntrl OV Trip
0x00020000 Phase OV Trip Phase OV Trip
0x00040000 Phase UV Trip Phase UV Trip
0x00080000 Aux OV Trip Auxiliary OV Trip
0x00100000 Aux UV Trip Auxiliary UV Trip
0x00200000 UnderFreq1 Trip Underfrequency 1 Trip
0x00400000 UnderFreq2 Trip Underfrequency 2 Trip
0x00800000 OVERFREQ1 TRIP Overfrequency 1 Trip
0x01000000 OVERFREQ2 TRIP Overfrequency 2 Trip
0x02000000 SGnd IOC1 Trip Sensitive Ground IOC 1 Trip
0x04000000 SGnd IOC2 Trip Sensitive Ground IOC 2 Trip
0x08000000 Nseq IOC Trip Negative Sequence IOC Trip
0x10000000 Diff 87P Trip Diff 87P Trip
0x20000000 Diff 87REF 1 Trip Diff 87REF 1 Trip
0x40000000 Diff 87REF 2 Trip Diff 87REF 2 Trip
0x80000000 Inst 50/87P Trip Inst 50/87P Trip
FC186 unsigned 32 bits Trip Status 4
0x00000001 NSeq TOC1 Trip Negative Sequence TOC 1 Trip
0x00000002 NSeq TOC2 Trip Negative Sequence TOC 2 Trip
0x00000004 Phase OV 2 Trip Phase OV 2 Trip
0x00000008 Phase UV 2 Trip Phase UV 2 Trip
0x00000010 Short Circuit Trip Short Circuit Trip
0x00000020 SPD2 S/C Trip SPD2 S/C Trip
0x00000040 SPD2 U/C Trip SPD2 U/C Trip

12-196 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x00000080 SGnd TOC2 Trip Sensitive Ground TOC 2 Trip
0x00000100 Reserved Reserved
0x00000200 Reserved Reserved
0x00000400 Reserved Reserved
0x00000800 Reserved Reserved
0x00001000 Reserved Reserved
0x00002000 Reserved Reserved
0x00004000 Reserved Reserved
0x00008000 Reserved Reserved
0x00010000 LE 9 Trip Logic Element 9 Trip
0x00020000 LE 10 Trip Logic Element 10 Trip
0x00040000 LE 11 Trip Logic Element 11 Trip
0x00080000 LE 12 Trip Logic Element 12 Trip
0x00100000 LE 13 Trip Logic Element 13 Trip
0x00200000 LE 14 Trip Logic Element 14 Trip
0x00400000 LE 15 Trip Logic Element 15 Trip
0x00800000 LE 16 Trip Logic Element 16 Trip
0x01000000 Reserved Reserved
0x02000000 Reserved Reserved
0x04000000 Reserved Reserved
0x08000000 Reserved Reserved
0x10000000 Reserved Reserved
0x20000000 Reserved Reserved
0x40000000 Reserved Reserved
0x80000000 Reserved Reserved
FC187 unsigned 32 bits Message Status 1
FC188 unsigned 32 bits Message Status 2
FC189 unsigned 32 bits Message Status 3
FC190 unsigned 32 bits Message Status 4
FC191 unsigned 32 bits Ctrl Element Status 1
FC192 unsigned 32 bits Ctrl Element Status 2
FC193 unsigned 32 bits Ctrl Status 3
FC194 unsigned 32 bits Ctrl Status 4
FC195 unsigned 16 bits Command Status
0 Normal Normal
1 Gain Forced to X1 Gain Forced to X1
FC196 unsigned 16 bits Digital Alarm
0 Active Low Active Low
1 Active High Active High
FC197 unsigned 16 bits Breaker Counter Alarm
0 Disabled Disabled
1 Alarm Alarm
2 Latched Alarm Latched Alarm
3 Trip Trip
FC198 unsigned 16 bits Output Relay Operation
FC199 unsigned 16 bits Output Relay Type
0 Self-Reset Self-Reset

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-197


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


1 Latched Latched
FC200 unsigned 32 bits Block Status 1
FC201 unsigned 32 bits Block Status 2
FC202 unsigned 32 bits Block Status 3
FC203 unsigned 32 bits Block Status 4
FC204 unsigned 16 bits Contact Input FlexLogic Bit Field Values
0x0000 Disabled Disabled
0x0040 Contact Input 1 Contact Input 1
0x0041 Contact Input 2 Contact Input 2
0x0042 Contact Input 3 Contact Input 3
0x0043 Contact Input 4 Contact Input 4
0x0044 Contact Input 5 Contact Input 5
0x0045 Contact Input 6 Contact Input 6
0x0046 Contact Input 7 Contact Input 7
0x0047 Contact Input 8 Contact Input 8
0x0048 Contact Input 9 Contact Input 9
0x0049 Contact Input 10 Contact Input 10
FC204A unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset A)
0x0000 Disabled Disabled
0x0040 Contact Input 1 Contact Input 1
FC204B unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset B)
0x0000 Disabled Disabled
0x0042 Contact Input 3 Contact Input 3
0x0043 Contact Input 4 Contact Input 4
0x0044 Contact Input 5 Contact Input 5
0x0045 Contact Input 6 Contact Input 6
0x0046 Contact Input 7 Contact Input 7
0x0047 Contact Input 8 Contact Input 8
0x0048 Contact Input 9 Contact Input 9
0x0049 Contact Input 10 Contact Input 10
FC204C unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset C)
0x0000 Disabled Disabled
0x0041 Contact Input 2 Contact Input 2
FC204D unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset D)
0x0000 Disabled Disabled
0x0042 Contact Input 3 W2 Breaker 52a (CI#3)
FC204E unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset E)
0x0000 Disabled Disabled
0x0044 Contact Input 5 Contact Input 5
0x0045 Contact Input 6 Contact Input 6
0x0046 Contact Input 7 Contact Input 7
0x0047 Contact Input 8 Contact Input 8
0x0048 Contact Input 9 Contact Input 9

12-198 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


0x0049 Contact Input 10 Contact Input 10
FC204F unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset F)
0x0000 Disabled Disabled
0x0043 Contact Input 4 W2 Breaker 52b (CI#4)
FC205 unsigned 16 bits Element Type 1
0 Disabled Disabled
1 Alarm Alarm
2 Latched Alarm Latched Alarm
3 Trip Trip
4 Control Control
FC206 unsigned 16 bits Element Type 2
0 Disabled Disabled
1 Alarm Alarm
2 Latched Alarm Latched Alarm
FC207 unsigned 16 bits Element Type 3
0 Disabled Disabled
1 Alarm Alarm
2 Latched Alarm Latched Alarm
3 Control Control
FC208 unsigned 16 bits Relay Operation (Failsafe
0 Failsafe Failsafe
1 Non-Failsafe Non-Failsafe
FC212 unsigned 16 bits LCD Test Paint Color
0 None None
1 Red Red
2 Green Green
3 Blue Blue
FC214 unsigned 16 bits MAC Address
FC215 unsigned 32 bits GOOSE Receive Status
FC216 unsigned 16 bits Received GOOSE Message Formatting
0x0000 { {
0x0001 } }
0x0002 Bool Bool
0x0003 Byte Byte
0x0004 Ubyte Ubyte
0x0005 Short Short
0x0006 Ushort Ushort
0x0007 Long Long
0x0008 Ulong Ulong
0x0009 Int64 Int64
0x000A Uint64 Uint64
0x000B Float Float
0x000C Double Double
0x000D Btime4 Btime4
0x000E Btime6 Btime6
0x000F Utctime Utctime

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-199


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


0x0010 Bcd Bcd
0x0011 Vstring Vstring
0x0012 Ostring Ostring
0x0013 Ovstring Ovstring
0x0014 Bstring Bstring
0x0015 Bvstring Bvstring
0x00FF Row Row
FC217 unsigned 16 bits Remote Input Item Source
FC218 unsigned 16 bits Remote Input Item Mask
FC219 unsigned 32 bits GOOSE Source
0x0000 Disabled Disabled
0x0001 1 1
0x0002 2 2
0x0004 3 3
0x0008 4 4
0x0010 5 5
0x0020 6 6
0x0040 7 7
0x0080 8 8
FC220 unsigned 16 bits Remote Input Default State
0 On On
1 Off Off
2 Latest/On Latest/On
3 Latest/Off Latest/Off
FC221 unsigned 16 bits IEC103 ASDU Identification Type
3 3 3
9 9 9
FC222 unsigned 16 bits GOOSE Type
0 Simplified Simplified
1 Advanced Advanced
FC225 unsigned 16 bits Security Audit Trail Change Method
0 Unknown Unknown
1 USB USB
2 COM1 COM1
3 Ethernet Ethernet
4 KeyPad KeyPad
FC226 unsigned 16 bits Security Audit Trail Event Type
0 Unknown Unknown
1 Setpoint Change Setpoint Change
2 Firmware File Firmware File
3 Factory Reload Factory Reload
4 Setpoint File Setpoint File
FC230 unsigned 16 bits Ethernet Connection Type
0 Copper Copper
1 Fiber Fiber
FC235 unsigned 16 bits Switching Device
0 BKR Breaker

12-200 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


1 Contactor Contactor
FC236 unsigned 16 bits Thermal O/L Curve
0 Standard Standard
1 Flex Curve Flex Curve
2 Flex Curve B Flex Curve B
FC240 unsigned 16 bits Self Test Error
0 None None
1 Order Code Error Order Code Error
2 RTC Error RTC Error
4 Cal Error Cal Error
8 EEPROM Error EEPROM Error
16 System Health System Health
17 PSU Serial# Blank PSU Serial# Blank
18 INP Serial# Blank INP Serial# Blank
19 ANLG Serial# Blank ANLG Serial# Blank
20 MAG Serial# Blank MAG Serial# Blank
21 COMM Serial# Blank COMM Serial# Blank
22 CCP Serial# Blank CCP Serial# Blank
23 CPU Serial# Blank CPU Serial# Blank
24 PSU Serial# Inval PSU Serial# Invalid
25 INP Serial# Inval INP Serial# Invalid
26 ANLG Serial# Inval ANLG Serial# Invalid
27 MAG Serial# Inval MAG Serial# Invalid
28 COMM Serial# Inval COMM Serial# Invalid
29 CCP Serial# Inval CCP Serial# Invalid
30 CPU Serial# Inval CPU Serial# Invalid
32 3.3V Error 3.3V Error
64 Analog V Error Analog V Error
128 DPRAM Checksum DPRAM Checksum
256 DPRAM Heart Beat DPRAM Heart Beat
512 COMM Error COMM Error
513 DAUGHTER Error DAUGHTER Error
514 COMM HW Rev Error COMM HW Revision Error
1024 Link Error Link Error
2048 Traffic Error Traffic Error
4096 Internal Temp Internal Temp
FC401 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 None None
FC402 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 None None
FC403 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 None None
FC404 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 Off Off

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-201


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


1 On On
FC405 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 100 Ohm Pt 100 Ohm Platinum
1 120 Ohm Ni 120 Ohm Nickel
2 100 Ohm Ni 100 Ohm Nickel
FC406 unsigned 16 bits PC Program Reserved for FlexLogic Bit (Do
Not Use)
0 Off Off
1 On On
FC407 unsigned 16 bits PC Program Reserved for Output Relay
Bits (Do Not Use)
0 Disabled Disabled
3 3 3
4 4 4
5 5 5
6 6 6
7 7 7
FC408 unsigned 16 bits Inrush Function
FC409 unsigned 16 bits Inhibit Mode
0 Per Phase Per Phase
1 2-out-of-3 2-out-of-3
2 Average Average
FC410 unsigned 16 bits Overexcitation Function
FC411 unsigned 16 bits Internal Compensation
0 Internal(software) Internal(software)
1 External(with CTs) External(with CTs)
FC412 unsigned 16 bits Winding Connection
0 Wye Wye
1 Delta Delta
2 Zig-Zag Zig-Zag
FC413 unsigned 16 bits Grounding Connection
0 Not Within zone Not Within zone
1 Within zone Within zone
FC415 unsigned 16 bits SR345 CT Type
0 1 A Secondary 1 A Secondary
1 5 A Secondary 5 A Secondary
FC418 unsigned 16 bits CT Inputs
FC419 unsigned 16 bits XFMR Type
FC420 unsigned 16 bits Modbus File Transfer State
0 Idle Idle
1 Write Write
2 Read Read
3 File Error File Error
4 File OK File OK
5 Start Start
6 Ready Ready
7 File Over File Over

12-202 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES 350 FORMAT CODES

Code Type Definition Long Definition


FC421 unsigned 16 bits Redundancy type
0 None None
1 LLA LLA
2 PRP PRP
3 HSR HSR
4 DAISY CHAIN DAISY CHAIN
FC422 unsigned 16 bits Redundancy Port
0 Internal(software) Internal(software)
1 PTP PTP
3 SNTP SNTP
5 IRIGB IRIGB
FC423 unsigned 16 bits Redundancy State
0 Disabled Disabled
1 No Signal No Signal
2 Calibrating Calibrating
3 Synchronized Synchronized
FC424 unsigned 16 bits Dead Condition
0 None None
1 Dead Line-Dead Bus Dead Line-Dead Bus
2 Live Line-Dead Bus Live Line-Dead Bus
3 Dead Line-Live Bus Dead Line-Live Bus
4 Any Line-Dead Bus Any Line-Dead Bus
5 Dead Line-Any Bus Dead Line-Any Bus
6 One Live-Othr Dead One Live-Other Dead
7 Not Both Live Not Both Live
FC425 unsigned 16 bits Epoch type
0 UTC since 1995 UTC since 1995
1 UTC since 1900 UTC since 1900
2 UTC since 1970 UTC since 1970
3 TAI since 1970 TAI since 1970
FC426 unsigned 16 bits RSTP State
0 Discarding Discarding
1 Learning Learning
2 Forwarding Forwarding
FC427 unsigned 16 bits WGF Curve Selection
0 Inverse Inverse
4 Definite Time Definite Time
8 Flex Curve A Flex Curve A
9 Flex Curve B Flex Curve B
FC428 unsigned 16 bits Fault Recorder Type
0 TOC A TOC A
1 TOC B TOC B
2 TOC C TOC C
FC429 unsigned 16 bits Transient Sampling Rate
0 4 4
1 8 8
2 16 16

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 12-203


350 FORMAT CODES CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES

Code Type Definition Long Definition


3 32 32
FC430 unsigned 16 bits Power Unit
0 Kw Kw
1 Mw Mw
FC431 unsigned 16 bits Demand Measurement Type
0 Blk Interval Blk Interval
1 Exponential Exponential
2 Rolling Dmd Rolling Dmd
FC432 unsigned 16 bits Demand Time
0 5 min 5 min
1 10 min 10 min
2 15 min 15 min
3 20 min 20 min
4 30 min 30 min
FC433 unsigned 16 bits BKR Alarm Counter
0 Detection Detection
1 Monitoring Monitoring
FC434 unsigned 16 bits 61850 NV Status
0 Unknown Unknown
1 Header Error Header Error
2 Parse Error Parse Error
3 Passed to Validated Passed to Validated
4 Empty Empty
FC435 unsigned 16 bits Volts Per Herz Voltage Mode
0 Phase-Gnd Phase-Gnd
1 Phase-Phase Phase-Phase
FC436 unsigned 16 bits Volts Per Herz Curves
4 Definite Time Definite Time
8 Flex Curve A Flex Curve A
9 Flex Curve B Flex Curve B
16 Inverse A Inverse A
17 Inverse B Inverse B
18 Inverse C Inverse C
None

12-204 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


GE
Grid Solutions

3 Series Protective Relay Platform

Appendix A: IEC 61850


Implementation Details

IEC 61850 Implementation Details

MICS
This sections contains the Model Implementation Conformance Statement (MICS) for the
IEC 61850 interface in 3 Series Family of protective relays.
Date: January 31, 2017
Version: 1.13

1 INTRODUCTION
This model implementation conformance statement is applicable for 3 Series Family, with
firmware 2.30:
This MICS document specifies the modelling extensions compared to IEC 61850 edition 1.
For the exact details on the standardized model please compare the ICD substation
configuration file: SR350.icd, SR339.icd, SR345.icd, version 2.30.
• Clause 2 contains the list of implemented logical nodes.
• Clause 3 describes the new and extended logical nodes.
• Clause 4 describes the new and extended common data classes.

1.1 Logical Nodes List


The following is a list of logical nodes and number of instances that will be supported*
within the 3 Series relays:
*Note: Depending on the relay order code, the number of LN may changer.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-1


MICS

L: System Logical Nodes Description ANSI 350 339 345


LPHD 1 Physical device information - Yes Yes Yes
LLN0 Logical node zero - Yes Yes Yes

P:Logical Nodes for protection Description ANSI 350 339 345


functions
phsPIOC Instantaneous Overcurrent 50P Yes(2) - Yes(2)
ndPIOC Instantaneous Neutral 50N Yes(2) Yes(1) Yes(2)
Overcurrent
gndPIOC Instantaneous Ground 50G Yes(2) - Yes(2)
Overcurrent
gndPIOC Ground Fault 50G - Yes(1) -
hsePIOC Instantaneous Sensitive 50SG Yes(2) - Yes(2)
Ground Overcurrent
ngseqPIOC Instantaneous Negative 50_2(46) Yes(1) - Yes(2)
Sequence Overcurrent
scPIOC Short Circuit 50P - Yes(1) -
phsPTOC Time Phase Overcurrent 51P Yes(1) Yes(1) Yes(2)
ndPTOC Time Neutral Overcurrent 51N Yes(1) Yes(1) Yes(2)
gndPTOC Time Ground Overcurrent 51G Yes(1) - Yes(2)
hsePTOC Time Sensitive Ground 51SG Yes(1) - Yes(2)
Overcurrent
ngseqPTOC Time Negative Sequence 51_2(46) Yes(1) - Yes(2)
Overcurrent
jamPTOC Mechanical Jam 51R - Yes(1) -
unbalPTOC Current Unbalance 46 - Yes(1) -
accelPTOC Acceleration 48 - Yes(1) -
ldincPTOC Load Increase - - Yes(1) -
PTUC Phase undecurrent 37 - Yes(1) -
PTOF Overfrequency 81O Yes(4) Yes(2) -
phsPTOV Phase Overvoltage 59P Yes(4) Yes(2) -
auxPTOV Auxiliary Overvoltage 59X Yes(1) - -
ndPTOV Neutral Overvoltage 59N Yes(4) - -
ngseqPTOV Negative Sequence 59_2 Yes(2) Yes(1) -
Overvoltage
phsrevPTOV Phase Reversal Overvoltage 47 - Yes(1) -
phsPTUV Phase Undervoltage 27P Yes(4) Yes(2) -
auxPTUV Auxiliary Undervoltage 27X Yes(1) -
psseqPTUV Positive Sequence 27P_1 Yes(1) Yes(2) -
Undervoltage
PTUF Underfrequency 81U Yes(4) Yes(2) -
PTTR Thermal O/L 49 Yes(1) Yes(1) Yes(1)
PDOP Directional Power 32 Yes(2) Yes(2) -
ndPDOP Wattmetric Ground Fault 32N Yes(2) - -
PMRI Restart Inhibit 66 - Yes(1) -
PDUP UnderPower 37P - Yes(1) -
pcntPDIF Percent Differential 87T - - Yes(1)
instPDIF Instantaneous Differential 87T-50 - - Yes(1)
rgfPDIF Restricted Ground Fault RGF - - Yes(2)
PVPH Volts per Hertz 24 Yes(1) - -

A-2 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


R:Logical Nodes for protection Description ANSI 350 339 345
functions
ndRDIR Neutral Directional 67N Yes(1) Yes(1) -
Overcurrent
gndRDIR Ground Directional 67G Yes(1) - -
Overcurrent
hseRDIR Sensitive Ground Directional 67SG Yes(1) - -
Overcurrent
phsRDIR Phase Directional Overcurrent 67P Yes(1) - -
RREC Autorecloser 79 Yes(1) - -
rptRFLO Fault Report - Yes(1) Yes(1) Yes(1)
RBRF Breaker Failure 50BF Yes(1) Yes(1) Yes(2)
RSYN Synchrocheck 25 Yes(1) - -

G:Logical Nodes for generic Description ANSI 350 339 345


functions
GGIO1 Remote Outputs - Yes Yes Yes
GGIO2 Contact Inputs/Outputs - Yes Yes Yes
GGIO3 Virtual Inputs - Yes Yes Yes
GGIO4 Logic Elements - Yes Yes Yes
GGIO5 Remote Inputs - Yes Yes Yes
rtdGGIO6 RTD's - - Yes Yes
GGIO7 Analog Operands - Yes Yes Yes

M:Logical Nodes for metering Description ANSI 350 339 345


and measurement
MMXU1 Measurement - Yes Yes Yes
MMXU2 Measurement - - - Yes
MMXU3 Differential Current - - - Yes
MMXU4 Differential 2 Harmonic - - - Yes
MMXU5 Differential 5 Harmonic - - - Yes
MMXU6 Restraint Current - - - Yes
MSQI1 Sequence and Imbalance - Yes Yes Yes
MSQI2 Sequence and Imbalance - - - Yes
MMTR1 Metering (Energy) - Yes Yes -

X:Logical Nodes for switchgear Description ANSI 350 339 345


XCBR Circuit Breaker - Yes Yes Yes(2)

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-3


MICS

2 LOGICAL NODES
The tables in this section use the following abbreviations:
• M: Data is mandatory in the IEC 61850-7-4.
• O: Data is optional in the IEC 61850-7-4 and is used in the device.
• C: Data is conditional in the IEC 61850-7-4 and is used in the device.
• E: Data is an extension to the IEC 61850-7-4.
• AC_CO_M: The attribute is mandatory, if the controllable status class supports control.
• AC_CO_O: The attribute is optional, if the controllable status class supports control
• AC_ST: The attribute is mandatory, if the controllable status class supports status
information.
• AC_LN0_M: The attribute shall be present if the data NamPlt belongs to LLN0
• AC_DLD_M: Applies to lnNs in all CDC LPL only, shall be present if LN name space of
this LN deviates from the LN name space referenced by ldNs of the logical device in
which this LN is contained.
• AC_DLN_M: Applies to dataNs in all CDCs, dataNs shall be present if the name space of
the DATA deviates from the name space defined in ldNs/lnNs
• AC_DLNDA_M: Applies to cdcNs and cdcName in all CDCs only, shall be present if CDC
name space of this data deviates from the CDC name space referenced by either the
dataNs of the data, the lnNs of the logical node in which the data is defined or ldNs of
the logical device in which the data is contained.

2.1 System Logical Nodes. LN Group: L


2.1.1 LPHD (Physical device information)

LPHD class
Attribute Name Attr. Type Explanation M/O/C/E Notes
LPHD Physical device M
information
Data
Common Logical Node Information
PhyNam DPL_0 Physical device name M
plate
PhyHealth INS_1 Physical device health M 1: when normal. (No errors)
2: when minor error is
present (e.g. "High ENET
Traffic" alarm)
3: when major error is
present. (e.g. "Error Code 1"
or "RELAY NOT READY")
Proxy SPS_1 Indicates if this LN is a M
proxy
SetChang SPS_2 Setting Change O
FWSuccess SPS_2 Firmware Updated O

2.1.2 LLN0 (Logical node zero)

LLN0 class
Attribute Name Attr. Type Explanation M/O/C/E Notes
LLN0 Logical node zero
Data
Common Logical Node Information

A-4 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_0 Name plate M
GoCB (ACSI class GOOSE control block)
GoCB GoCB

2.1.3 GoCB (GOOSE control block class definition)

GoCB class
Attribute Name Attribute Type FC Notes
GoEna BOOLEAN GO Enable (TRUE), disable (FALSE)
GoID VISIBLE STRING65 GO
DatSet Object Reference GO
ConfRev INT32U GO
NdsCom BOOLEAN GO
DstAddress PHYCOMADDR GO

2.2 Logical Nodes for protection functions. LN Group:P


2.2.1 PDIF (Differential)
pcntPDIF: Transformer Percent Differential

PDIF class
Attribute Name Attr. Type Explanation M/O/C/E Notes
PcntPDIF Overpower
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_0 Start M XRFM PCNT DIFF PKP
Op ACT_0 Operate M XRFM PCNT DIFF OP
Blk ACT_3 Block E XRFM PCNT DIFF BLK

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-5


MICS

instPDIF: Transformer Instantaneous Differential

PDIF class
Attribute Name Attr. Type Explanation M/O/C/E Notes
InstPDIF Overpower
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_2 Start M XRFM INST DIFF PKP
Op ACT_2 Operate M XRFM INST DIFF OP
Blk ACT_3 Block E XRFM INST DIFF BLK

rgfPDIF: Restricted Ground Fault Differential

PDIF class
Attribute Name Attr. Type Explanation M/O/C/E Notes
RgfPDIF Overpower
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_2 Start M RESTD GND FAULT PKP
Op ACT_2 Operate M RESTD GND FAULT OP
Blk ACT_3 Block E RESTD GND FAULT BLK

2.2.2 PDOP (Directional Overpower)


PDOP: Directional overpower

PDOP class
Attribute Name Attr. Type Explanation M/O/C/E Notes
PDOP Overpower
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_2 Start M Directional Power PKP
Op ACT_2 Operate M Directional Power OP
Blk ACT_3 Block E Directional Power BLK

A-6 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


NdPDOP: Wattmetric Ground Fault

PDOP class
Attribute Name Attr. Type Explanation M/O/C/E Notes
NdPDOP Overpower
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Measured Values
Watt MV_6 Wattmetric Power E
Status Information
Str ACD_2 Start M Wattmetric Ground Fault
PKP
Op ACT_2 Operate M Wattmetric Ground Fault
OP
Blk ACT_3 Block E Wattmetric Ground Fault
BLK

2.2.3 PDUP (Directional Underpower)


PDUP: Directional underpower

PDUP class
Attribute Name Attr. Type Explanation M/O/C/E Notes
PDUP Underpower
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_1 Start M UnderPower PKP
Op ACT_1 Operate M UnderPower OP
Blk ACT_3 Block E UnderPower BLK

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-7


MICS

2.2.4 PIOC (Instantaneous overcurrent)


phsPIOC: phase IOC

PIOC class
Attribute Name Attr. Type Explanation M/O/C/E Notes
PhsPIOC Instantaneous
overcurrent
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_0 Start O Phase IOC PKP
Op ACT_0 Operate M Phase IOC OP
Blk ACT_3 Block E Phase IOC BLK

ndPIOC: neutral IOC

PIOC class
Attribute Name Attr. Type Explanation M/O/C/E Notes
NdPIOC Instantaneous
overcurrent
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_1 Start O Neutral IOC PKP
Op ACT_1 Operate M Neutral IOC OP
Blk ACT_3 Block E Neutral IOC BLK

A-8 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


gndPIOC: ground fault IOC

PIOC class
Attribute Name Attr. Type Explanation M/O/C/E Notes
GndPIOC Instantaneous
overcurrent
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_1 Start O Ground IOC PKP
Op ACT_1 Operate M Ground IOC OP
Blk ACT_3 Block E Ground IOC BLK

hsePIOC: Sensitive Ground IOC

PIOC class
Attribute Name Attr. Type Explanation M/O/C/E Notes
HsePIOC Instantaneous
overcurrent
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_1 Start O Sens Gnd IOC PKP
Op ACT_1 Operate M Sens Gnd IOC OP
Blk ACT_3 Block E Sens Gnd IOC BLK

ngseqPIOC: Negative Sequence IOC

PIOC class
Attribute Name Attr. Type Explanation M/O/C/E Notes
NgSeqPIOC Instantaneous
overcurrent
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_2 Start O Neq Seq IOC PKP
Op ACT_2 Operate M Neq Seq IOC OP
Blk ACT_3 Block E Neq Seq IOC BLK

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-9


MICS

2.2.5 PMRI (Motor restart inhibition)


PMRI: Motor restart inhibition

PMRI class
Attribute Name Attr. Type Explanation M/O/C/E Notes
PMRI Motor restart inhibition
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Strlnh SPS_0 Restart inhibited O

2.2.6 PTOC (Time overcurrent)


phsPTOC: Phase TOC

PTOC class
Attribute Name Attr. Type Explanation M/O/C/E Notes
PhsPTOC Time overcurrent
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_0 Start O Phase TOC PKP
Op ACT_0 Operate M Phase TOC OP
Blk ACT_3 Block E Phase TOC BLK

ndPTOC: neutral TOC

PTOC class
Attribute Name Attr. Type Explanation M/O/C/E Notes
NdPTOC Time overcurrent
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_1 Start O Neutral TOC PKP
Op ACT_1 Operate M Neutral TOC OP
Blk ACT_3 Block E Neutral TOC BLK

A-10 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


gndPTOC: ground TOC

PTOC class
Attribute Name Attr. Type Explanation M/O/C/E Notes
GndPTOC Time overcurrent
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_1 Start O Ground TOC PKP
Op ACT_1 Operate M Ground TOC OP
Blk ACT_3 Block E Ground TOC BLK

hsePTOC: sensitive ground TOC

PTOC class
Attribute Name Attr. Type Explanation M/O/C/E Notes
HsePTOC Time overcurrent
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_1 Start O Sensitive Ground TOC PKP
Op ACT_1 Operate M Sensitive Ground TOC OP
Blk ACT_3 Block E Sensitive Ground TOC BLK

NgSeqPTOC: Negative Sequence TOC(339/350)

PTOC class
Attribute Name Attr. Type Explanation M/O/C/E Notes
NgSeqPTOC_0 Time overcurrent
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_2 Start O Negative Sequence TOC
PKP
Op ACT_2 Operate M Negative Sequence TOC OP
Blk ACT_3 Block E Negative Sequence TOC
BLK

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-11


MICS

NgSeqPTOC: Negative Sequence TOC(345)

PTOC class
Attribute Name Attr. Type Explanation M/O/C/E Notes
NgSeqPTOC_1 Time overcurrent
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_1 Start O Negative Sequence TOC
PKP
Op ACT_1 Operate M Negative Sequence TOC OP
Blk ACT_3 Block E Negative Sequence TOC
BLK

jamPTOC: Mechanical Jam

PTOC class
Attribute Name Attr. Type Explanation M/O/C/E Notes
jamPTOC Time overcurrent
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_1 Start O Mechanical Jam PKP
Op ACT_1 Operate M Mechanical JamOP
Blk ACT_3 Block E Mechanical Jam BLK

unbalPTOC: Current unbalanced

PTOC class
Attribute Name Attr. Type Explanation M/O/C/E Notes
unbalPTOC Time overcurrent
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_1 Start O Current unbal PKP
Op ACT_1 Operate M Current unbal OP
Blk ACT_3 Block E Current unbal BLK

A-12 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


accelPTOC: Acceleration

PTOC class
Attribute Name Attr. Type Explanation M/O/C/E Notes
accelPTOC Time overcurrent
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_1 Start O Acceleration PKP
Op ACT_1 Operate M Acceleration OP
Blk ACT_3 Block E Acceleration BLK

ldincPTOC: Load Increase

PTOC class
Attribute Name Attr. Type Explanation M/O/C/E Notes
ldincPTOC Time overcurrent
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_1 Start O Load Increase Alarm PKP
Op ACT_1 Operate M Load Increase Alarm OP
Blk ACT_3 Block E Load Increase Alarm BLK

2.2.7 PTOF (OverFrequency)


PTOF: over frequency

PTOF class
Attribute Name Attr. Type Explanation M/O/C/E Notes
PTOF OverFrequency
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_2 Start M PTOF PKP
Op ACT_2 Operate M PTOF OP
Blk ACT_3 Block E PTOF BLK

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-13


MICS

2.2.8 PTOV (Overvoltage)


phsPTOV: phase overvoltage

PTOV class
Attribute Name Attr. Type Explanation M/O/C/E Notes
PhsPTOV Overvoltage
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_0 Start M Phase TOV PKP
Op ACT_0 Operate M Phase TOV OP
Blk ACT_3 Block E Phase TOV BLK

auxPTOV: auxiliary overvoltage

PTOV class
Attribute Name Attr. Type Explanation M/O/C/E Notes
AuxPTOV Overvoltage
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_2 Start M Auxiliary PTOV PKP
Op ACT_2 Operate M Auxiliary PTOV OP
Blk ACT_3 Block E Auxiliary PTOV BLK

ndPTOV: neutral overvoltage

PTOV class
Attribute Name Attr. Type Explanation M/O/C/E Notes
NdPTOV Overvoltage
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_2 Start M Neutral TOV PKP
Op ACT_2 Operate M Neutral TOV OP
Blk ACT_3 Block E Neutral TOV BLK

A-14 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


ngseqPTOV: negative sequence overvoltage

PTOV class
Attribute Name Attr. Type Explanation M/O/C/E Notes
NgSeqPTOV Overvoltage
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_2 Start M Negative Sequence TOV
PKP
Op ACT_2 Operate M Negative Sequence TOV OP
Blk ACT_3 Block E Negative Sequence TOV
BLK

phsrevPTOV: phase reversal overvoltage

PTOV class
Attribute Name Attr. Type Explanation M/O/C/E Notes
PhsRevPTOV Overvoltage
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_2 Start M Phase Reversal PKP
Op ACT_2 Operate M Phase Reversal TOV OP
Blk ACT_3 Block E Phase Reversal TOV BLK

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-15


MICS

2.2.9 PTTR (Thermal overload)


PTTR: Thermal O/L (350/345)

PTTR class
Attribute Name Attr. Type Explanation M/O/C/E Notes
PTTR_0 Thermal Overload
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Measured values
ThmCapPhsA MV_5 Thermal Capacity Phs A E
ThmCapPhsB MV_5 Thermal Capacity Phs B E
ThmCapPhsC MV_5 Thermal Capacity Phs C E
Status Information
Str ACD_0 Start M PTTR PKP
Op ACT_0 Operate M PTTR OP
Blk ACT_3 Block E PTTR BLK

PTTR: Thermal O/L(339)

PTTR class
Attribute Name Attr. Type Explanation M/O/C/E Notes
PTTR_1 Thermal Overload
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Measured values
Amp MV_0 Motor Load (x FLA) O
OvlTripTm MV_5 Time to O/L Trip E
ThmCap MV_5 Motor Thermal Capacity E
Used (%)
ThmLOTm MV_5 Overload Lockout Time E
MotUnb MV_5 Current Unbalance (%) E
BiasMotLod MV_5 Biased Motor Load (x FLA) E
TotLOTm MV_5 Motor Lockout Time E
Status Information
Str ACD_2 Start M PTTR PKP
Op ACT_2 Operate M PTTR OP
Blk ACT_3 Block E PTTR BLK

A-16 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


2.2.10 PTUC (UnderCurrent)
PTUC: under current

PTUC class
Attribute Name Attr. Type Explanation M/O/C/E Notes
PTUC Undercurrent
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_1 Start M Undercurrent PKP
Op ACT_1 Operate M Undercurrent OP
Blk ACT_3 Block E Undercurrent BLK

2.2.11 PTUF (Underfrequency)


PTUF: under frequency

PTUF class
Attribute Name Attr. Type Explanation M/O/C/E Notes
PTUF UnderFrequency
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_2 Start M PTUF PKP
Op ACT_2 Operate M PTUF OP
Blk ACT_3 Block E PTUF BLK

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-17


MICS

2.2.12 PTUV (Undervoltage)


phsPTUV: phase undervoltage

PTUV class
Attribute Name Attr. Type Explanation M/O/C/E Notes
PhsPTUV Undervoltage
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_0 Start M Phase PTUV PKP
Op ACT_0 Operate M Phase PTUV OP
Blk ACT_3 Block E Phase PTUV BLK

auxPTUV: auxiliary undervoltage

PTUV class
Attribute Name Attr. Type Explanation M/O/C/E Notes
AuxPTUV Undervoltage
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_2 Start M Auxiliary UV PKP
Op ACT_2 Operate M Auxiliary UV OP
Blk ACT_3 Block E Auxiliary UV BLK

psseqPTUV: positive sequence undervoltage

PTUV class
Attribute Name Attr. Type Explanation M/O/C/E Notes
PsSeqPTUV Undervoltage
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_2 Start M Positive Seq UV PKP
Op ACT_2 Operate M Positive Seq UV OP
Blk ACT_3 Block E Positive Seq UV BLK

A-18 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


2.2.13 PVPH (Volts per Hz)
PVPH: Volts per Hz

PVPH class
Attribute Name Attr. Type Explanation M/O/C/E Notes
PVPH Volts per Hz
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_2 Start M Volts Hz PKP
Op ACT_2 Operate M Volts Hz OP
Blk ACT_3 Block E Volts Hz BLK

2.3 Logical Nodes for protection related functions. LN Group: R


2.3.1 RDIR (Directional element)
phsRDIR: phase directional overcurrent

RDIR class
Attribute Name Attr. Type Explanation M/O/C/E Notes
PhsRDIR Directional Element
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Dir ACD_0 Directions M
Op ACT_5 Operate E
Blk ACT_3 Block E

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-19


MICS

ndRDIR: neutral directional overcurrent

RDIR class
Attribute Name Attr. Type Explanation M/O/C/E Notes
NdRDIR_0 Directional Element
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Dir ACD_1 Directions M
Op ACT_4 Operate E
Blk ACT_3 Block E

gndRDIR: ground directional overcurrent

RDIR class
Attribute Name Attr. Type Explanation M/O/C/E Notes
GndRDIR Directional Element
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Dir ACD_1 Directions M
Op ACT_4 Operate E
Blk ACT_3 Block E

hseRDIR: ground directional overcurrent

RDIR class
Attribute Name Attr. Type Explanation M/O/C/E Notes
HseRDIR Directional Element
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Dir ACD_1 Directions M
Op ACT_4 Operate E
Blk ACT_3 Block E

A-20 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


2.3.2 RBRF (Breaker failure)
RBRF: breaker failure (350)

RBRF class
Attribute Name Attr. Type Explanation M/O/C/E Notes
RBRF_0 Breaker failure element
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_2 Start M
Opln ACT_2 Operate C

RBRF: breaker failure (339/345)

RBRF class
Attribute Name Attr. Type Explanation M/O/C/E Notes
RBRF_1 Breaker failure element
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Str ACD_2 Start M
OpEx ACT_2 Operate C

2.3.3 RFLO (Fault locator)


rptRFLO: Fault report (350/339)

RFLO class
Attribute Name Attr. Type Explanation M/O/C/E Notes
RFLO_0 Fault locator element
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Measured Values
FltZ CMV_2 Fault Impedance M
FltDiskm MV_2 Fault Distance in Km M
FltCause INS_5 E
FltPhases INS_5 E

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-21


MICS

FltIa CMV_3 E
FltIb CMV_3 E
FltIc CMV_3 E
FltIg CMV_3 E
FltIn CMV_3 E
FltVan CMV_3 E
FltVbn CMV_3 E
FltVcn CMV_3 E
FltVab CMV_3 E
FltVbc CMV_3 E
FltVca CMV_3 E
FltVn CMV_3 E
FltVaux CMV_3 E
FltFreq MV_3 E

rptRFLO: Fault report (345)

RFLO class
Attribute Name Attr. Type Explanation M/O/C/E Notes
RFLO_1 Fault locator element
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Measured Values
FltZ CMV_2 Fault Impedance M
FltDiskm MV_2 Fault Distance in Km M
FltCause INS_5 E
FltPhases INS_5 E
FltIa CMV_3 E
FltIb CMV_3 E
FltIc CMV_3 E
FltIg CMV_3 E
FltIn CMV_3 E
FltIa2 CMV_3 E
FltIb2 CMV_3 E
FltIc2 CMV_3 E
FltIg2 CMV_3 E
FltIn2 CMV_3 E
FltIaDiff CMV_3 E
FltIaRest CMV_3 E
FltIbDiff CMV_3 E
FltIbRest CMV_3 E
FltIcDiff CMV_3 E
FltIcRest CMV_3 E
FltFreq MV_3 E

A-22 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


2.3.4RREC (Autoreclosing)
RREC: Recloser

RREC class
Attribute Name Attr. Type Explanation M/O/C/E Notes
RREC Autoreclosing element
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Op ACT_2 M
AutoRecSt INS_3 Operate M

2.3.5RSYN (Synchronism-check)
RSYN: Synchronism-check

RSYN class
Attribute Name Attr. Type Explanation M/O/C/E Notes
RSYN Synchronism-check
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Rel SPS_0 Release M

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-23


MICS

2.4 Logical Nodes for generic references. LN Group: G


2.4.1 GGIO (Generic process I/O)
GGIO1: Remote Outputs logical node
GGIO class
Attribute Name Attr. Type Explanation M/O/C/E Notes
GGIO_0 Generic process I/O
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status information
Ind1 SPS_0 Remote Output 1 O
Ind2 SPS_0 Remote Output 2 O
.. .. .. ..
Ind32 SPS_0 Remote Output 32 O

GGIO2: Contact I/O logical node


GGIO class
Attribute Name Attr. Type Explanation M/O/C/E Notes
GGIO_1 Generic process I/O
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Controls
Ind1 SPS_0 Contact input 1 O
Ind2 SPS_0 Contact input 2 O
.. .. .. ..
Ind10 SPS_0 Contact input 10 O
Ind11 SPS_0 Contact Output 1 O
Ind12 SPS_0 Contact Output 2 O
.. .. ..
Ind17 SPS_0 Contact Output 7 O

A-24 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


GGIO3: Virtual Inputs logical node.

GGIO class
Attribute Name Attr. Type Explanation M/O/C/E Notes
GGIO_2 Generic process I/O
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Controls
SPCSO1 SPC_0 Single point controllable O
status output
SPCSO2 SPC_0 Single point controllable O
status output
.. .. .. ..
SPCSO32 SPC_0 Single point controllable O
status output
Status information
Ind1 SPS_0 Virtual Input 1 O
Ind2 SPS_0 Virtual Input 2 O
.. .. .. ..
Ind32 SPS_0 Virtual Input 32 O

GGIO4: Logic Elements logical node.

GGIO class
Attribute Name Attr. Type Explanation M/O/C/E Notes
GGIO_3 Generic process I/O
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status information
Ind1 SPS_0 Logic Element 1 O
Ind2 SPS_0 Logic Element 2 O
.. .. .. ..
Ind16 SPS_0 Logic Element 16 O

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-25


MICS

GGIO5: remote inputs logical node.

GGIO class
Attribute Name Attr. Type Explanation M/O/C/E Notes
GGIO_0 Generic process I/O
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Status information
Ind1 SPS_0 Remote digital input 1 O
Ind2 SPS_0 Remote digital input 2 O
.. .. .. ..
Ind32 SPS_0 Remote digital input 32 O

rtdGGIO6: RTDs.

GGIO class
Attribute Name Attr. Type Explanation M/O/C/E Notes
GGIO_4 Generic process I/O
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Measured Values
AnIn1 MV_0 RTD 1 Temp O
AnIn2 MV_0 RTD 2 Temp O
.. .. .. ..
AnIn12 MV_0 RTD 12 Temp O
Status information
Alm1 SPS_0 RTD 1 Alarm O
Alm 2 SPS_0 RTD 2 Alarm O
.. .. .. ..
Alm 12 SPS_0 RTD 12 Alarm O
Ind1 SPS_0 RTD 1 Trip O
Ind2 SPS_0 RTD 2 Trip O
.. .. .. ..
Ind12 SPS_0 RTD 12 Trip O

A-26 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


GGIO7: Analog Operands logical node.

GGIO class
Attribute Name Attr. Type Explanation M/O/C/E Notes
GGIO_5 Generic process I/O
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Measured Values
AnIn1 MV_0 Analog Operand 1 O
AnIn2 MV_0 Analog Operand 2 O
.. .. .. ..
AnIn8 MV_0 Analog Operand 8 O

2.5 Logical Nodes for metering and measurement. LN Group: M


2.5.1 MMXU
MMXU1: measurements (339/350).

MMXU class
Attribute Name Attr. Type Explanation M/O/C/E Notes
MMXU_0 Measurement
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Measured values
TotW MV_0 Total active power (P) O
TotVAr MV_0 Total reactive power (Q) O
TotVA MV_0 Total apparent power (S) O
TotPF MV_0 Average power factor (PF) O
Hz MV_0 Line Frequency O
PPV DEL_0 Phase to phase voltages O
(VL1L2,...)
PhV WYE_0 Phase to ground voltages O
(VL1ER, ...)
A WYE_1 Phase currents (IL1, ...) O
AuxV CMV_1 Auxiliary Phase Voltage E

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-27


MICS

MMXU1: W1 Phase currents (345).

MMXU class
Attribute Name Attr. Type Explanation M/O/C/E Notes
MMXU_1 Measurement
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Measured values
A WYE_1 Phase currents (IL1, ...) O W1 Phase currents

MMXU2: W2 Phase currents(345).

MMXU class
Attribute Name Attr. Type Explanation M/O/C/E Notes
MMXU_1 Measurement
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Measured values
A WYE_1 Phase currents (IL1, ...) O W2 Phase currents

MMXU3: Idiff 1 Phase Currents (345)

MMXU class
Attribute Name Attr. Type Explanation M/O/C/E Notes
DiffMMXU Measurement
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Measured values
A WYE_2 Phase currents (IL1, ...) O Idiff 1 Phase Currents

A-28 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


MMXU4: Idiff 2 Phase Currents (345)

MMXU class
Attribute Name Attr. Type Explanation M/O/C/E Notes
DiffMMXU Measurement
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Measured values
A WYE_2 Phase currents (IL1, ...) O Idiff 2 Phase Currents

MMXU5: Idiff 5 Phase Currents (345)

MMXU class
Attribute Name Attr. Explanation M/O/C/E Notes
Type
DiffMMXU Measurement
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Measured values
A WYE_2 Phase currents (IL1, ...) O Idiff 5 Phase Currents

MMXU6: I Restraint Phase Currents (345).

MMXU class
Attribute Name Attr. Explanation M/O/C/E Notes
Type
DiffMMXU Measurement
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Measured values
A WYE_2 Phase currents (IL1, ...) O I Restraint Phase Currents

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-29


MICS

2.5.2 MSQI
MSQI: Sequence and imbalance (339/350)

MSQI class
Attribute Name Attr. Explanation M/O/C/E Notes
Type
MSQI Sequence and imbalance
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Measured values
SeqA SEQ_0 O
SeqV SEQ_0 O

MSQI: Sequence and imbalance (345)

MSQI class
Attribute Name Attr. Explanation M/O/C/E Notes
Type
MSQI_1 Sequence and imbalance
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Measured values
SeqA SEQ_0 O

A-30 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


2.5.3 MMTR
MMTR: Metering

MMTR class
Attribute Name Attr. Explanation M/O/C/E Notes
Type
MMTR_0 Metering
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Measured values
PosTotWh MV_5 E
NegTotWh MV_5 E
PosTotVArh MV_5 E
NegTotVArh MV_5 E

2.6 Logical Nodes for switchgear. LN Group: X


2.6.1 XCBR (Circuit breaker)
XCBR: circuit breaker

XCBR class
Attribute Name Attr. Explanation M/O/C/E Notes
Type
XCBR Circuit breaker
Data
Common Logical Node Information
Mod INC_0 Mode M
Beh INS_0 Behaviour M
Health INS_1 Health M
NamPlt LPL_1 Name plate M
Loc SPS_0 Local operation M Local / Remote
OpCnt INS_2 Operation counter M Breaker openings
Controls
Pos DPC_0 Switch position M Breaker open, close
BlkOpn SPC_1 Block opening M
BlkCls SPC_1 Block closing M
Status information
CBOpCap INS_4 Cicruit breaker operating O
capability

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-31


MICS

3 COMMON DATA CLASS

3.1 Common data class specifications for status information


3.1.1 Single Point Status (SPS)

SPS_0
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
status
stVal Boolean ST dchg M
q BVstring13 ST qchg M
t Utctime ST M
configuration, description and extension
d Vstring255 DC O

SPS_1
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
status
stVal Boolean ST dchg M
q BVstring13 ST qchg M
t Utctime ST M

3.1.2 Integer Status (INS)

INS_0
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
status
stVal Enum ST dchg Beh M
q BVstring13 ST qchg M
t Utctime ST M

INS_1
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
status
stVal Enum ST dchg Health M
1: when normal. (No errors)
2: when minor error is
present (e.g. "High ENET
Traffic" alarm)
3: when major error is
present. (e.g. "Error Code 1"
or "RELAY NOT READY")
q BVstring13 ST qchg M
t Utctime ST M

A-32 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


INS_2
Attribute
Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
status
stVal INT32 ST dchg M
q BVstring13 ST qchg M
t Utctime ST M

INS_3
Attribute
Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
status
IstVal Enum ST dchg AutoRecSt M
q BVstring13 ST qchg M
t Utctime ST M

INS_4
Attribute
Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
status
stVal Enum ST dchg CBOpCap M
q BVstring13 ST qchg M
t Utctime ST M

INS_5
Attribute
Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
status
stVal INT32 ST dchg M
q BVstring13 ST qchg M
t Utctime ST M
configuration, descripcion and extension
d Vstring255 DC O
dataNs Vstring255 EX GE Multilin SR3 AC_DLN_M
Namespace:2003

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-33


MICS

3.1.3 Protection activation information (ACT)

ACT_0
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
general Boolean ST dchg M
phsA Boolean ST dchg O
phsB Boolean ST dchg O
phsC Boolean ST dchg O
q Bvstring13 ST qchg M
t Utctime ST M
configuration, description and extension
d Vstring255 DC O

ACT_1
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
general Boolean ST dchg M
neut Boolean ST dchg O
q Bvstring13 ST qchg M
t Utctime ST M
configuration, description and extension
d Vstring255 DC O

ACT_2
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
general Boolean ST dchg M
q Bvstring13 ST qchg M
t Utctime ST M
configuration, description and extension
d Vstring255 DC O

ACT_3
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
general Boolean ST dchg M
q Bvstring13 ST qchg M
t Utctime ST M
configuration, description and extension
d Vstring255 DC O
dataNs Vstring255 EX GE Multilin SR3 AC_DLN_M
Namespace:2003

A-34 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


ACT_4
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
general Boolean ST dchg M
neut Boolean ST dchg O
q Bvstring13 ST qchg M
t Utctime ST M
configuration, description and extension
d Vstring255 DC O
dataNs Vstring255 EX IEC 61850-7-4:2003 AC_DLN_M

ACT_5
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
phsA Boolean ST dchg O
phsB Boolean ST dchg O
phsC Boolean ST dchg O
q Bvstring13 ST qchg M
t Utctime ST M
configuration, description and extension
d Vstring255 DC O
dataNs Vstring255 EX IEC 61850-7-4:2003 AC_DLN_M

3.1.4 Directional protection activation information (ACD)

ACD_0
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
general Boolean ST dchg M
dirGeneral Enumerated ST dchg unknown | forward | backward | both M
(Byte)
phsA Boolean ST dchg GC_2(1)
dirPhsA Enumerated ST dchg unknown | forward | backward GC_2(1)
(Byte)
phsB Boolean ST dchg GC_2(2)
dirPhsB Enumerated ST dchg unknown | forward | backward GC_2(2)
(Byte)
phsC Boolean ST dchg GC_2(3)
dirPhsC Enumerated ST dchg unknown | forward | backward GC_2(3)
(Byte)
q Bvstring13 ST qchg M
t Utctime ST M
configuration, description and extension
d Vstring255 DC O

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-35


MICS

ACD_1
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
general Boolean ST dchg M
dirGeneral Enumerated ST dchg unknown | forward | backward | both M
(Byte)
neut Boolean ST dchg GC_2(1)
dirNeut Enumerated ST dchg unknown | forward | backward GC_2(1)
(Byte)
q Bvstring13 ST qchg M
t Utctime ST M
configuration, description and extension
d Vstring255 DC O

ACD_2
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
general Boolean ST dchg M
dirGeneral Enumerated ST dchg unknown | forward | backward | both M
(Byte)
q Bvstring13 ST qchg M
t Utctime ST M
configuration, description and extension
d Vstring255 DC O

A-36 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


3.2 Common data class specifications for measurand information
3.2.1 Measured Value (MV)

MV_0
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
measured attributes
instMag FloatAnalogueValue MX ------ O
f FLOAT32 GC_1
mag FloatAnalogueValue MX dchg M
f FLOAT32 GC_1
range ENUMERATED(Byte) MX dchg O
q BVstring13 MX qchg M
t Utctime MX M
configuration, description and extension
units Unit CF O
SIUnit ENUMERATED(Byte) M
Multiplier ENUMERATED(Byte) O
db INT32U CF O
zeroDb INT32U CF O
rangeC RangeConfig CF O
hhLim FloatAnalogueValue
f FLOAT32 GC_1
hlim FloatAnalogueValue
f FLOAT32 GC_1
lLim FloatAnalogueValue
f FLOAT32 GC_1
llLim FloatAnalogueValue
f FLOAT32 GC_1
min FloatAnalogueValue
f FLOAT32 GC_1
max FloatAnalogueValue
f FLOAT32 GC_1
limDb INT32U
d Vstring255 DC O

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-37


MICS

MV_2
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
measured attributes
mag FloatAnalogueValue MX dchg M
f FLOAT32 GC_1
q BVstring13 MX qchg M
t Utctime MX M
configuration, description and extension
units Unit CF O
SIUnit ENUMERATED(Byte) M
Multiplier ENUMERATED(Byte) O
d Vstring255 DC O

MV_3
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
measured attributes
mag FloatAnalogueValue MX dchg M
f FLOAT32 GC_1
q BVstring13 MX qchg M
t Utctime MX M
configuration, description and extension
units Unit CF O
SIUnit ENUMERATED(Byte) M
Multiplier ENUMERATED(Byte) O
d Vstring255 DC O
dataNs Vstring255 EX GE Multilin SR3 AC_DLN_M
Namespace:2003

MV_4
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
measured attributes
mag IntAnalogueValue MX dchg M
f INT32 GC_1
q BVstring13 MX qchg M
t Utctime MX M
configuration, description and extension
units Unit CF O
SIUnit ENUMERATED(Byte) M
Multiplier ENUMERATED(Byte) O
d Vstring255 DC O

A-38 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


MV_5
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
measured attributes
instMag FloatAnalogueValue MX ------ O
f FLOAT32 GC_1
mag FloatAnalogueValue MX dchg M
f FLOAT32 GC_1
range ENUMERATED(Byte) MX dchg O
q BVstring13 MX qchg M
t Utctime MX M
configuration, description and extension
units Unit CF O
SIUnit ENUMERATED(Byte) M
Multiplier ENUMERATED(Byte) O
db INT32U CF O
zeroDb INT32U CF O
rangeC RangeConfig CF O
hhLim FloatAnalogueValue
f FLOAT32 GC_1
hlim FloatAnalogueValue
f FLOAT32 GC_1
lLim FloatAnalogueValue
f FLOAT32 GC_1
llLim FloatAnalogueValue
f FLOAT32 GC_1
min FloatAnalogueValue
f FLOAT32 GC_1
max FloatAnalogueValue
f FLOAT32 GC_1
limDb INT32U
d Vstring255 DC O
dataNs Vstring255 EX GE Multilin SR3 AC_DLN_M
Namespace:2003

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-39


MICS

MV_6
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
measured attributes
instMag FloatAnalogueValue MX ------ O
f FLOAT32 GC_1
mag FloatAnalogueValue MX dchg M
f FLOAT32 GC_1
range ENUMERATED(Byte) MX dchg O
q BVstring13 MX qchg M
t Utctime MX M
configuration, description and extension
units Unit CF O
SIUnit ENUMERATED(Byte) M
Multiplier ENUMERATED(Byte) O
db INT32U CF O
zeroDb INT32U CF O
rangeC RangeConfig CF O
hhLim FloatAnalogueValue
f FLOAT32 GC_1
hlim FloatAnalogueValue
f FLOAT32 GC_1
lLim FloatAnalogueValue
f FLOAT32 GC_1
llLim FloatAnalogueValue
f FLOAT32 GC_1
min FloatAnalogueValue
f FLOAT32 GC_1
max FloatAnalogueValue
f FLOAT32 GC_1
limDb INT32U
d Vstring255 DC O
dataNs Vstring255 EX IEC 61850-7-4:2003 AC_DLN_M

A-40 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


3.2.2 Complex Measured Value (CMV)

CMV_0
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
measured attributes
instCVal FloatVector MX ------ O
mag FloatAnalogueValue
f FLOAT32
cVal FloatVector MX dchg M
mag FloatAnalogueValue
f FLOAT32
range ENUMERATED(Byte) MX dchg O
q BVstring13 MX qchg M
t Utctime MX M
configuration, description and extension
units Unit CF O
SIUnit Byte M
Multiplier Byte O
db INT32U CF O
dbAng INT32U CF O
zeroDb INT32U CF O
rangeC RangeConfig CF O
d Vstring255 DC O
cdcNs Vstring255 EX GE Multilin SR3 AC_DLNDA
Namespace:2003 _M
cdcName Vstring255 EX CMV AC_DLNDA
_M

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-41


MICS

CMV_1
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
measured attributes
instCVal FloatVector MX ------ O
mag FloatAnalogueValue
f FLOAT32
cVal FloatVector MX dchg M
mag FloatAnalogueValue
f FLOAT32
range ENUMERATED(Byte) MX dchg O
q BVstring13 MX qchg M
t Utctime MX M
configuration, description and extension
units Unit CF O
SIUnit Byte M
Multiplier Byte O
db INT32U CF O
dbAng INT32U CF O
zeroDb INT32U CF O
rangeC RangeConfig CF O
d Vstring255 DC O
dataNs Vstring255 EX GE Multilin SR3 AC_DLN_M
Namespace:2003

CMV_2
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
measured attributes
cVal FloatVector MX dchg M
mag FloatAnalogueValue
f FLOAT32
q BVstring13 MX qchg M
t Utctime MX M
configuration, description and extension
units Unit CF O
SIUnit Byte M
Multiplier Byte O
d Vstring255 DC O

A-42 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


CMV_3
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
measured attributes
cVal FloatVector MX dchg M
mag FloatAnalogueValue
f FLOAT32
q BVstring13 MX qchg M
t Utctime MX M
configuration, description and extension
units Unit CF O
SIUnit Byte M
Multiplier Byte O
d Vstring255 DC O
dataNs Vstring255 EX GE Multilin SR3 AC_DLN_M
Namespace:2003

3.2.3 Phase to ground related measured values of a three phase system ( WYE )

WYE_0
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
Data
phsA CMV_0 GC_1
phsB CMV_0 GC_1
phsC CMV_0 GC_1
neut CMV_0 GC_1
configuration, description and extension
d Vstring255 DC O

WYE_1
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
Data
phsA CMV_0 GC_1
phsB CMV_0 GC_1
phsC CMV_0 GC_1
neut CMV_0 GC_1
net CMV_0 GC_1
res CMV_0 GC_1
configuration, description and extension
d Vstring255 DC O

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-43


MICS

WYE_2
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
Data
phsA CMV_0 GC_1
phsB CMV_0 GC_1
phsC CMV_0 GC_1
configuration, description and extension
d Vstring255 DC O

3.2.4 Phase to phase related measured values of a three phase system ( DEL )

DEL_0
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
Data
phsAB CMV_0 GC_1
phsBC CMV_0 GC_1
phsCA CMV_0 GC_1
configuration, description and extension
d Vstring255 DC O

3.2.5 Sequence (SEQ)

SEQ_0
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
Data
c1 CMV_0 GC_1
c2 CMV_0 GC_1
c3 CMV_0 GC_1
configuration, description and extension
d Vstring255 DC O

A-44 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


3.3 Common data class specifications for controllable status information
3.3.1 Controllable single point (SPC)

SPC_0
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
Oper ctlVal Boolean CO AC_CO_M
origin Originator CO AC_CO_M
orCat ENUMERATED M
orIdent OCTECT64 M
ctlNum INT8U CO M
T Btime6 CO M
Test Boolean CO M
Check ENUMERATED CO M
stVal Boolean ST FALSE | TRUE AC_ST
q Quality ST AC_ST
t TimeStamp ST AC_ST
configuration, description and extension
ctlModel ENUMERATED CF ctlModel_1 M
operTimeout INT32U CF AC_CO_O
cdcNs Vstring255 EX GE Multilin SR3 AC_DLNDA
Namespace:2003 _M
cdcName Vstring255 EX SPC AC_DLNDA
_M

SPC_1
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
stVal Boolean ST FALSE | TRUE AC_ST
q Quality ST AC_ST
t TimeStamp ST AC_ST
configuration, description and extension
ctlModel ENUMERATED CF ctlModel M

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-45


MICS

3.3.2 Controllable double point (DPC).

DPC_0
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
SBO
SBOw
Oper ctlVal Boolean CO AC_CO_M
origin Originator CO,ST AC_CO_M
orCat ENUMERATED M
orIdent OCTECT64 M
ctlNum INT8U CO,ST M
T Btime6 CO M
Test Boolean CO M
Check ENUMERATED CO M
Cancel
stVal CODE ENUM ST dchg intermediate-state | off | on M
| bad-state
q BVstring13 ST qchg AC_ST
t Utctime ST AC_ST
configuration, description and extension
ctlModel ENUMERATED CF M
sboTimeout INT32U CF AC_CO_O
sboClass ENUMERATED CF AC_CO_O
operTimeout INT32U CF AC_CO_O
d Vstring255 DC O
cdcNs Vstring255 EX GE Multilin SR3 AC_DLNDA
Namespace:2003 _M
cdcName Vstring255 EX DPC AC_DLNDA
_M

3.3.3 Controllable integer status (INC)

INC_0 (type Mod)


Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
status
stVal Enum ST dcgh M
q BVstring13 ST qchg M
t Utctime ST M
configuration, description and extension
ctlModel ENUMERATED CF M

A-46 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


3.4 Common data class specifications for description information
3.4.1 Device name plate (DPL)

DPL_0 (type Mod)


Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
vendor Vstring255 DC M
swRev Vstring255 DC O
serNum Vstring255 DC O
model Vstring255 DC O
location Vstring255 DC O

3.4.2 Logical node name plate (LPL)

LPL_0 (type Mod)


Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
vendor Vstring255 DC M
swRev Vstring255 DC M
d Vstring255 DC M
configRev Vstring255 DC AC_LN0_M
ldNs Vstring255 EX AC_DLD_M

LPL_1 (type Mod)


Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
vendor Vstring255 DC M
swRev Vstring255 DC M
d Vstring255 DC M

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-47


TICS

TICS
This section contains the TISSUES (Technical Issues) Implementation Conformance
Statement (TICS) for the IEC 61850 interface in the 3 Series Family of protective relays.

Date: January 3, 2017


Version 1.10

1 Introduction
This tissues conformance statement is applicable to the 3 Series family with firmware
version 2.30.

2 Implemented IntOp TISSUES


During the October 2006 meeting IEC TC57 working group 10 decided that:
• green Tissues with the category "IntOp" are mandatory for IEC 61850 edition 1
• Tissues with the category "Ed.2" Tissues should not be implemented.

Mandatory Edition 1 Tissues


The following table gives an overview of the implemented mandatory Tissues.

Part Tissue Description Implemented


Nr Y/na
8-1 116 GetNameList with empty response? Y
165 Improper Error Response for GetDataSetValues Y
183 GetNameList error handling Y
226 Control negative response (SBOns) with LastApplError na
545 Skip file directories with no files na
7-4 252 AlmThm should have CDC SPS na
7-3 28 Definition of APC na
54 Point def xVal, not cVal na
55 Ineut = Ires ? Y
63 mag in CDC CMV Y
65 Deadband calculation of a Vector and trigger option Y
219 operTm in ACT na
270 WYE and DEL rms values na
1199 BCR na
7-2 30 control parameter T na
31 Typo na
32 Typo in syntax na
35 Typo Syntax Control time na
36 Syntax parameter DSet-Ref missing na
37 Syntax GOOSE "T" type Y
39 Add DstAddr to GoCB Y
40 GOOSE Message "AppID" to "GoID "Y
41 GsCB "AppID" to "GsID "na
42 SV timestamp: "EntryTime" to "TimeStamp "na

A-48 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


Part Tissue Description Implemented
Nr Y/na
43 Control "T" semantic na
44 AddCause - Object not sel Y
45 Missing AddCauses na
46 Synchro check cancel na
47 "." in LD Name? Y
49 BRCB TimeOfEntry (part of #453) -
50 LNName start with number? na
51 ARRAY [0..num] missing na
52 Ambiguity GOOSE SqNum Y
53 Add DstAddr to GsCB, SV na
151 Name constraint for control blocks etc. Y
166 DataRef attribute in Log na
185 Logging - Integrity periode na
189 SV Format na
190 BRCB: EntryId and TimeOfEntry (part of #453) -
191 BRCB: Integrity and buffering reports (part of #453) -
234 New type CtxInt (Enum are mapped to 8 bit integer) na
275 Confusing statement on GI usage (part of #453) -
278 EntryId not valid for a server (part of #453) -
297 Sequence Number Y
298 Type of SqNum Y
305 Reporting with BufTm = 0 na
322 Write Configuration attribute of BRCBs Y
329 Reporting and BufOvl
333 Enabling of an incomplete GoCB na
335 Clearing of BufOvfl Y
348 URCB class and report na
349 BRCB TimeofEntry has two definitions na
453 Combination of all reporting and logging tissues Y
1281 Trigger option GI is by default Y
6 1 Syntax na
5 tExtensionAttributeNameEnum is restricted Y
8 SIUnit enumeration for W Y
10 Base type for bitstring usage Y
17 DAI/SDI elements syntax Y
169 Ordering of enum differs from 7-3 na

• Tissue 49, 190, 191, 275 and 278 are part of tissue #453, all other technical tissues in
the table are mandatory if applicable.
NOTE
• Editorial tissues are marked as "na".

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-49


TICS

3 Other Implemented TISSUES


Part Tissue Description
Nr
8-1 177 Ignoring OptFlds bits for URCB
7-4 79 AutoRecSt value 4 = "unsuccessful"

A-50 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


PICS
This section contains the Protocol Implementation Conformance Statement (PICS) for the
IEC 61850 interface in the 3 Series Family of protective relays.
Version 1.10
Date: January 3, 2017

1 General
The following ACSI conformance statements are used to provide an overview and details
about 3 Series Family, with firmware 2.30:
• ACSI basic conformance statement,
• ACSI models conformance statement,
• ACSI service conformance statement
The statements specify the communication features mapped to IEC 61850-8-1 and IEC
61850-9-2.

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-51


PICS

2 ASCI basic conformance statement


The basic conformance statement is defined in Table A.1.

Table A.1: Basic conformance statement


Client/ Server/ Value/
Subscriber Publisher Comments
Client-Server roles
B11 Server side (of TWO-PARTY- - Y
APPLICATION-ASSOCIATION)
B12 Client side of (TWO-PARTY- -
APPLICATION-ASSOCIATION)

SCSMs supported
B21 SCSM: IEC 6185-8-1 used Y
B22 SCSM: IEC 6185-9-1 used Deprecated
B23 SCSM: IEC 6185-9-2 used
B24 SCSM: other

Generic substation event model (GSE)


B31 Publisher side - Y
B32 Subscriber side Y -

Transmission of sampled value model (SVC)


B41 Publisher side -
B42 Subscriber side -
- = not applicable
Y = supported
N or empty = not supported

A-52 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


3 ACSI models conformance statement
The ACSI models conformance statement is defined in Table A.2.
Table A.2: ACSI models conformance statement
Client/ Server/ Value/
Subscriber Publisher Comments
If Server or Client side (B11/12) supported
M1 Logical device Y
M2 Logical node Y
M3 Data Y
M4 Data set Y
M5 Substitution
M6 Setting group control
Reporting
M7 Buffered report control Y
M7-1 sequence-number Y
M7-2 report-time-stamp Y
M7-3 reason-for-inclusion Y
M7-4 data-set-name Y
M7-5 data-reference Y
M7-6 buffer-overflow Y
M7-7 entryID Y
M7-8 BufTm Y
M7-9 IntgPd Y
M7-10 GI Y
M7-11 conf-revision Y
M8 Unbuffered report control Y
M8-1 sequence-number Y
M8-2 report-time-stamp Y
M8-3 reason-for-inclusion Y
M8-4 data-set-name Y
M8-5 data-reference Y
M8-6 BufTm Y
M8-7 IntgPd Y
M8-8 GI Y
M8-9 conf-revision Y
Logging
M9 Log control
M9-1 IntgPd
M10 Log
M11 Control Y
M17 File Transfer
M18 Application association Y
M19 GOOSE Control Block Y
M20 Sampled Value Control Block
If GSE (B31/32) is supported
M12 GOOSE Y
M13 GSSE Deprecated

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-53


PICS

Client/ Server/ Value/


Subscriber Publisher Comments
If SVC (B41/B42) is supported
M14 Multicast SVC
M15 Unicast SVC
For all IEDs
M16 Time Y Y Time source
with
required accu-
racy shall be
available.
Only Time
Masters are
SNTP (Mode4
response) time
servers.
All other
Client/Server
devices
require SNTP
(Mode 3
request)
clients
Y = service is supported
N or empty = service is not supported

A-54 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


4 ACSI service conformance statement
The ACSI service conformance statement is defined in Table A.3 (depending on the
statements in Table A.1).
Table A.3: Table A.3 - ACSI service Conformance statement
Ed ACSI Service AA: Client Sub Server Pub Comments
TP/MC (C) (S)
Server
S1 1,2 GetServerDirectory(LOGICAL-DEVICE) TP Y

Application association
S2 1,2 Associate TP Y
S3 1,2 Abort TP Y
S4 1,2 Release TP Y

Logical device
S5 1,2 GetLogicalDeviceDirectory TP Y

Logical node
S6 1,2 GetLogicalNodeDirectory TP Y
S7 1,2 GetAllDataValues TP Y

Data
S8 1,2 GetDataValues TP Y
S9 1,2 SetDataValues TP Y
S10 1,2 GetDataDirectory TP Y
S11 1,2 GetDataDefinition TP Y

Data set
S12 1,2 GetDataSetValues TP Y
S13 1,2 SetDataSetValues TP N
S14 1,2 CreateDataSet TP N
S15 1,2 DeleteDataSet TP N
S16 1,2 GetDataSetDirectory TP Y

Substitution
S17 1 SetDataValues TP Ed1 only

Setting group control


S18 1,2 SelectActiveSG TP
S19 1,2 SelectEditSG TP
S20 1,2 SetEditSGValues TP
S21 1,2 ConfirmEditSGValues TP
S22 1,2 GetEditSGValues TP
S23 1,2 GetSGCBValues TP

Reporting
Buffered report control block (BRCB)

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-55


PICS

Ed ACSI Service AA: Client Sub Server Pub Comments


TP/MC (C) (S)
S24 1,2 Report TP Y
S24-1 1,2 data- Y
change
(dchg)
S24-2 1,2 quality- N
change
(qchg)
S24-3 1,2 data-update N
(dupd)
S25 1,2 GetBRCBValues TP Y
S26 1,2 SetBRCBValues TP Y
Unbuffered report control block (URCB)
S27 1,2 Report TP Y
S27-1 1,2 data- Y
change
(dchg)
S27-2 1,2 quality- N
change
(qchg)
S27-3 1,2 data-update N
(dupd)
S28 1,2 GetURCBValues TP Y
S29 1,2 SetURCBValues TP Y

Logging
Log control
S30 1,2 GetLCBValues TP N
S31 1,2 SetLCBValues TP N
Log
S32 1,2 QueryLogByTime TP N
S33 1,2 QueryLogAfter TP N
S34 1,2 GetLogStatusValues TP N

Generic substation event model (GSE)


GOOSE
S35 1,2 SendGOOSEMessage MC Y
GOOSE Control Block
S36 1,2 GetGoReference TP
S37 1,2 GetGOOSEElementNumber TP
S38 1,2 GetGoCBValues TP Y
S39 1,2 SetGoCBValues TP Y
GSSE (Ed2:61850-7-2 Annex C)
S40 1,2 SendGSSEMessage MC N Deprecated in Edition 2
GSSE Control
Block (Ed2:61850-7-2 Annex C)
S41 1,2 GetGsReference TP N Deprecated in Edition 2
S42 1,2 GetGSSEDataOffset TP N Deprecated in Edition 2
S43 1,2 GetGsCBValues TP N Deprecated in Edition 2
S44 1,2 SetGsCBValues TP N Deprecated in Edition 2

A-56 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


Ed ACSI Service AA: Client Sub Server Pub Comments
TP/MC (C) (S)
Transmission of sampled value model (SVC)
Multicast SV
S45 1,2 SendMSVMessage MC N Use for 9-2LE or IEC 61869-9
Multicast Sampled Value Control Block
S46 1,2 GetMSVCBValues TP N
S47 1,2 SetMSVCBValues TP N
Unicast SV
S48 1,2 SendUSVMessage TP N
Unicast Sampled Value Control Block
S49 1,2 GetUSVCBValues TP N
S50 1,2 SetUSVCBValues TP N

Control
S51 1,2 Select TP Y SBO Normal Security
S52 1,2 SelectWithValue TP Y SBO Enhanced Security
S53 1,2 Cancel TP Y
S54 1,2 Operate TP Y
S55 1,2 CommandTermination TP Y
S56 1,2 TimeActivatedOperate TP N

File transfer
S57 1,2 GetFile TP N
S58 1,2 SetFile TP N
S59 1,2 DeleteFile TP N
S60 1,2 GetFileAttributeValues TP N
S61 1,2 GetServerDirectory (FILE) TP N

Time
T1 1,2 Time resolution of internal clock - 10(1ms) nearest negative power of 2 in seconds
T2 2 Time accuracy of internal clock - TL (ms) (low accuracy), T3 < 7) (only Ed2)
1,2 - T0 (ms) (<= 10 ms), 7 <= T3 < 10)
1,2 - Y T1 (µs) (<= 1 ms), 10 <= T3 < 13
1,2 - T2 (µs) (<= 100 µS), 13 <= T3 < 15
1,2 - T3 (µs) (<= 25 µS), 15 <= T3 < 18
1,2 - T4 (µs) (<= 4 µS), 18 <= T3 < 20
1,2 - T5 (µs) (<= 1 µS), T3 >= 20)
T3 1,2 Supported TimeStamp resolution - 10(1ms) nearest negative power of 2 in seconds

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-57


PIXIT

PIXIT
This section contains the Protocol Implementation eXtra Information for Testing (PIXIT) for
the IEC 61850 interface in the 3 Series Family of protective relays.

Version 1.10
Date: January 3, 2017

Introduction
This document specifies the protocol implementation extra information for testing (PIXIT)
of the IEC 61850 interface in the 3 Series Family with firmware version 2.30
Together with the PICS and the MICS, the PIXIT forms the basis for a conformance test
according to IEC 61850-10. The PIXIT entries contain information which is not available in
the PICS, MICS, TICS documents or SCL file.
Each table specifies the PIXIT for applicable ACSI service model as structured in IEC 61850-
10. The "Ed" column indicates if the entry is applicable for IEC 61850 Edition 1 and/or
Edition 2.

PIXIT for Association model

ID Ed Description Value / Clarification


As1 1 Maximum number of clients that can set-up an 3
association simultaneously
As2 1,2 TCP_KEEPALIVE value. The recommended range is 20 seconds but if no application message is
1..20s detected within the As3 value, the device will
close the connection.
As3 1,2 Lost connection detection time 120 seconds (Configurable)
As4 - Authentication is not supported yet
As5 1,2 What association parameters are necessary for Transport selector Y
successful association Session selector Y
Presentation selector Y
AP Title N
AE Qualifier N
As6 1,2 If association parameters are necessary for Transport selector 0001
association, describe the correct values e.g. Session selector 0001
Presentation selector 00000001
AP Title NA
AE Qualifier NA
As7 1,2 What is the maximum and minimum MMS PDU size Max MMS PDU size 120000
Min MMS PDU size 700.
As8 1,2 What is the maximum start up time after a power 45-50 seconds.
supply interrupt (90 seconds in the worst case when creating
default.cid)

A-58 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


PIXIT for Server model
ID Ed Description Value / Clarification
Sr1 1,2 Which analogue value (MX) quality bits Validity:
are supported (can be set by server) Y Good,
N Invalid,
N Reserved,
N Questionable
Details:
N Overflow
N OutofRange
N BadReference
N Oscillatory
N Failure
N OldData
N Inconsistent
N Inaccurate
Source:
Y Process
N Substituted
N Test
N OperatorBlocked
Sr2 1,2 Which status value (ST) quality bits are Validity:
supported (can be set by server) Y Good,
N Invalid,
N Reserved,
N Questionable
Details:
N BadReference
N Oscillatory
N Failure
N OldData
N Inconsistent
N Inaccurate
Source:
Y Process
N Substituted
N Test
N OperatorBlocked
Sr3 - What is the maximum number of data Deprecated
object references in one GetDataValues
request
Sr4 - What is the maximum number of data Deprecated
object references in one SetDataValues
request
Sr5 1 Which Mode values are supported* On Y
[On-]Blocked N
Test N
Test/Blocked N
Off N

* IEC 61850-6:2009 clause 9.5.6 states that if only a subrange of the enumeration value set
is supported, this shall be indicated within an ICD file by an enumeration type, where the
unsupported values are missing

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-59


PIXIT

PIXIT for Data set model


ID Ed Description Value / Clarification
Ds1 1 What is the maximum number of data elements in one 64
data set (compare ICD setting)
Ds2 1 How many persistent data sets can be created by one or NOT SUPPORTED
more clients
(this number includes predefined datasets)
Ds3 1 How many non-persistent data sets can be created by one NOT SUPPORTED
or more clients

PIXIT for Substitution model


ID Ed Description Value / Clarification
Sb1 1 Are substituted values stored in volatile memory NOT SUPPORTED

PIXIT for Setting group control model


ID Ed Description Value / Clarification
Sg1 1 What is the number of supported setting groups for each NOT SUPPORTED
logical device
Sg2 1,2 What is the effect of when and how the non-volatile NOT SUPPORTED
storage is updated
(compare IEC 61850-8-1 $16.2.4)
Sg3 1 Can multiple clients edit the same setting group NOT SUPPORTED
Sg4 1 What happens if the association is lost while editing a NOT SUPPORTED
setting group
Sg5 1 Is EditSG value 0 allowed NOT SUPPORTED
Sg6 2 When ResvTms is not present how long is an edit setting NOT SUPPORTED
group locked

A-60 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


PIXIT for Reporting model
ID Ed Description Value / Clarification
Rp1 1 The supported trigger conditions are integrity Y
(compare PICS) data change Y
quality change N
data update N
general interrogation Y
Y
Rp2 1 The supported optional fields are sequence-number Y
report-time-stamp Y
reason-for-inclusion Y
data-set-name Y
data-reference Y
buffer-overflow Y
entryID Y
conf-rev Y
segmentation Y
Rp3 1,2 Can the server send segmented reports Y
Rp4 1,2 Mechanism on second internal data change Send report immediately
notification of the same analogue data value within
buffer period (Compare IEC 61850-7-2 $14.2.2.9)
Rp5 1 Multi client URCB approach Each URCB is visible to all
(compare IEC 61850-7-2:2003 $14.2.1) clients

Rp6 - What is the format of EntryID Deprecated


Rp7 1,2 What is the buffer size for each BRCB or how many Buffer size = 50000 Bytes
reports can be buffered
Rp8 - Pre-configured RCB attributes that are dynamic, Deprecated
compare SCL report settings
Rp9 1 May the reported data set contain:
- structured data objects Y
- data attributes Y

Rp10 1,2 What is the scan cycle for binary events Event Driven
Is this fixed, configurable Fixed

Rp11 1 Does the device support to pre-assign a RCB to a N


specific client in the SCL
Rp12 2 After restart of the server is the value of ConfRev Restored from original
restored from the original configuration or retained configuration
prior to restart

PIXIT for Logging model


ID Ed Description Value / Clarification
Lg1 1,2 What is the default value of LogEna NOT SUPPORTED
(Compare IEC 61850-8-1 $17.3.3.2.1, the default value
should be FALSE)
Lg2 - What is the format of EntryID Deprecated
Lg3 1,2 Are there are multiple Log Control Blocks that specify the NOT SUPPORTED
Journaling of the same MMS NamedVariable and TrgOps
and the Event Condition
(Compare IEC 61850-8-1 $17.3.3.3.2)

Lg4 1 Pre-configured LCB attributes that cannot be changed NOT SUPPORTED


online

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-61


PIXIT

PIXIT for GOOSE publish model

ID Ed Description Value / Clarification


Gp1 1,2 Can the test (Ed1) / simulation (Ed2) flag in the N
published GOOSE be set
Gp2 1 What is the behaviour when the GOOSE publish DUT keeps GoEna=F
configuration is incorrect Relay will not send GOOSE message.
Gp3 1,2 Published FCD supported common data classes SPS, INS, ENS, ACT, ACD, MV, CMV, SAV, WYE, DEL, SEQ, INC, ENC, SPC,
are DPC, INC, ENC. (Only the elements with FC=ST or MX will be
published).
Gp4 1,2 What is the slow retransmission time Configured by Enervista on GoCB MaxTime (0-60000 ms)
Is it fixed or configurable
Gp5 1,2 What is the fastest retransmission time Fixed. MinTime = 4 ms
Is it fixed or configurable
Gp6 - Can the GOOSE publish be turned on / off by using Y
SetGoCBValues(GoEna)
Gp7 1,2 What is the initial GOOSE sqNum after restart sqNum = 1
Gp8 1 May the GOOSE data set contain:
- structured data objects (FCD) Y
- timestamp data attributes Y
Gp9 1 How is the retransmission curve after a change. - sqNum = 0 New change
- sqNum = 1 -> 4ms later with TAL = 1000
- sqNum = 2 -> 8ms later with TAL = 1000
- sqNum = 3 -> 16ms later with TAL = 4000
- sqNum = 4 -> 1000ms later with TAL = Update time* x 4
- sqNum = 5 -> Update time* later with TAL = Update time* x 4
- sqNum = 6-> Update time* later with TAL = Update time* x 4
- sqNum = 7 ……..
- ………….

*Update time is configured in the Enervista 3 Series Setup

A-62 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


PIXIT for GOOSE subscribe model

ID Ed Description Value / Clarification


Gs1 1,2 What elements of a subscribed GOOSE header are checked to decide the Y destination MAC address
message is valid and the allData values are accepted? If yes, describe the Y APPID
conditions. N gocbRef
Notes: Y timeAllowedtoLive
- the VLAN tag may be removed by a ethernet switch and shall not be N datSet
checked Y goID
- the simulation flag shall always be checked (Ed2) Nt
- the ndsCom shall always be checked (Ed2) N stNum
N sqNum
N simulation / test
N confRev
Y ndsCom
Y numDatSetEntries
Gs2 1,2 When is a subscribed GOOSE marked as lost message does not arrive after TAL
(TAL = time allowed to live value from the last received GOOSE message)

Gs3 1,2 What is the behaviour when one or more subscribed GOOSE messages Message will be ignored, but when the next
isn't received or syntactically incorrect (missing GOOSE) correct message will be received, it will be
proceed as normal.
Gs4 1,2 What is the behaviour when a subscribed GOOSE message is out-of- Message will be proceeded
order
Gs5 1,2 What is the behaviour when a subscribed GOOSE message is duplicated Message will be ignored
Gs6 1 Does the device subscribe to GOOSE messages with/without the VLAN Y, with the VLAN tag
tag Y, without the VLAN tag

Gs7 1 May the GOOSE data set contain:


- structured data objects (FCD) Y
- timestamp data attributes N
Gs8 1,2 Subscribed FCD supported common data classes are DUT can receive all kinds of data but only
digitals can be mapped.
Gs9 1,2 Are subscribed GOOSE with test=T (Ed1) / simulation=T (Ed2) accepted in N
test/simulation mode
Gs10 1 What is the behaviour when a subscribed GOOSE message with TAL = 0 is The message will be ignored.
received by the subscriber.
Gs11 1 What is the behaviour when a subscribed GOOSE message hasn't the The message will be ignored.
expected data structure.

PIXIT for GOOSE performance

ID Ed Description Value / Clarification


Gf1 1,2 Performance class P2/P3
Gf2 1,2 GOOSE ping-pong processing method Event driven based
Gf3 1,2 Application logic scan cycle (ms) Max. <8 ms
Min. <4 ms
Gf4 1 Maximum number of data attributes in GOOSEdataset (value and quality 64
has to be counted asseparate attributes)

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-63


PIXIT

PIXIT for Control model

ID Ed Description Value / Clarification


Ct1 - What control models are supported Deprecated
(compare PICS)
Ct2 1,2 Is the control model fixed, configurable and/or dynamic Configurable & Dynamic
Ct3 - Is TimeActivatedOperate supported (compare PICS or SCL) Deprecated
Ct4 1,2 Is "operate-many" supported (compare sboClass) Deprecated
Ct5 1 Will the DUT activate the control output when the test attribute is set in N
the SelectWithValue and/or Operate request (when N test procedure Ctl2
is applicable)
Ct6 - What are the conditions for the time (T) attribute in the SelectWithValue Deprecated
and/or Operate request
Ct7 - Is pulse configuration supported (compare pulseConfig) Deprecated
Ct8 1 What is the behaviour of the DUT when the check conditions are set N synchrocheck
Is this behaviour fixed, configurable, online changeable N interlock-check
DUT ignores the check value and always
perform the check
Ct9 1,2 Which additional cause diagnosis are supported Y Unknown
Y Not-supported
Y Blocked-by-switching-hierarchy
Y Select-failed
Y Invalid-position
Y Position-reached
N Step-limit
N Blocked-by-Mode
N Blocked-by-process
N Blocked-by-interlocking
N Blocked-by-synchrocheck
Y Command-already-in-execution
N Blocked-by-health
N 1-of-n-control
N Abortion-by-cancel
Y Time-limit-over
N Abortion-by-trip
Y Object-not-selected

Edition 1 specific values:


N Parameter-change-in-execution

Edition 2 specific values:


N Object-already-selected
N No-access-authority
N Ended-with-overshoot
N Abortion-due-to-deviation
N Abortion-by-communication-loss
N Blocked-by-command
N None
N Inconsistent-parameters
N Locked-by-other-client
N Parameter-change-in-
execution
Ct10 1,2 How to force a "test-not-ok" respond with SelectWithValue request Device in local mode
Ct11 1,2 How to force a "test-not-ok" respond with Select request Device in local mode
Ct12 1,2 How to force a "test-not-ok" respond with Operate request DOns: Sending T=1
SBOns: Sending T=1
DOes: Sending T=1
SBOes: Sending T=1
Ct13 1,2 Which origin categories are supported / accepted N bay-control
Y station-control
Y remote-control
N automatic-bay
Y automatic-station
Y automatic-remote
N maintenance
N process

A-64 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


ID Ed Description Value / Clarification
Ct14 1,2 What happens if the orCat value is not supported or invalid DOns: control is rejected (Oper-
ObjectAccessDenied).
SBOns: control is rejected (Oper-
ObjectAccessDenied).
DOes: control is rejected (Oper- ServiceError,
ObjectAccessDenied).
SBOes: control is rejected (SBOw- ServiceError,
ObjectAccessDenied).

orCat supported:
2 (station control), 3 (remote-control),
5 (automatic-station), 6 (automatic-remote)
Ct15 1,2 Does the IED accept a SelectWithValue / Operate with the same control DOns: N
value as the current status value SBOns: N
DOes: N
Is this behaviour configurable SBOes: N
Configurable: N
Ct16 1,2 Does the IED accept a select/operate on the same control object from 2 DOns: N
different clients at the same time SBOns: N
DOes: Y
SBOes: N
Ct17 1 Does the IED accept a Select/SelectWithValue from the same client when SBOns: N
the control object is already selected (Tissue #334) SBOes: N
Ct18 1,2 Is for SBOes the internal validation performed during the SelectWithValue SelectWithValue and Operate
and/or Operate step
Ct19 - Can a control operation be blocked by Mod=Off or [On-]Blocked Deprecated
(Compare PIXIT-Sr5)
Ct20 1,2 Does the IED support local / remote operation Y (Only for XCBR)
Ct21 1,2 Does the IED send an InformationReport with LastApplError as part of the SBOns: N
Operate response- for control with normal security DOns: N
Ct22 2 How to force a "parameter-change-in-execution "SBOns:Not Applicable
SBOes:Not Applicable
Ct23 1,2 How many SBOns/SBOes control objects be selected at the same time? SBOns: n = "1"
SBOes: n = "1"
Ct24 1,2 Does the DUT support any operate timeout > 0 Y
Ct25 1,2 When CDC=DPC is supported, is it possible to have DPC (Controllable N
Double Point) go to the intermediate state? (00)

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A-65


PIXIT

PIXIT for Time synchronisation model

ID Ed Description Value / Clarification


Tm1 1,2 What time quality bits are supported (may be set by the IED) Y LeapSecondsKnown
N ClockFailure
Y ClockNotSynchronized.

Tm2 1,2 Describe the behaviour when the time server(s) ceases to respond On one time server: An event is generated
What is the time server lost detection time On all time servers: An event is generated
60 seconds (AnyCast)
30 seconds (Unicast)
8 min (Broadcast
Tm3 1,2 How long does it take to take over the new time from time server 2 seconds
Tm4 1,2 When is the time quality bit "ClockFailure" set Never
Tm5 1,2 When is the time quality bit "Clock not Synchronized" set 60 seconds (Unicast) or 30 seconds (Anycast)
after the time server(s) ceases to respond or 8
min in Broadcast.
Tm6 - Is the timestamp of a binary event adjusted to the configured scan cycle Deprecated
Tm7 1 Does the device support time zone and daylight saving Y
Tm8 1,2 Which attributes of the SNTP response packet are validated Y Leap indicator not equal to 3
Y Mode is equal to SERVER
N OriginateTimestamp is equal to value sent by
the SNTP client as Transmit Timestamp
Y RX/TX timestamp fields are checked for
reasonableness
Y SNTP version 3 and/or 4
N other (describe)

Tm9 1,2 Do the COMTRADE files have local time or UTC time and is this Local
configurable N

PIXIT for File transfer model

ID Ed Description Value / Clarification


Ft1 1 What is structure of files and directories Not Applicable
Where are the COMTRADE files stored Not Applicable
Are comtrade files zipped and what files are included in each zip file Not Applicable
Ft2 1,2 Directory names are separated from the file name by Not Applicable
Ft3 1 The maximum file name size including path (recommended 64 chars) Not Applicable
Ft4 1,2 Are directory/file name case sensitive Not Applicable
Ft5 1,2 Maximum file size for SetFile Not Applicable
Ft6 1 Is the requested file path included in the MMS fileDirectory respond file Not Applicable
name
Ft7 1 Is the wild char supported MMS fileDirectory request Not Applicable
Ft8 1,2 Is it allowed that 2 clients get a file at the same time Not Applicable
Ft9 1,2 Which files can be deleted Not Applicable

PIXIT for Service tracking model

ID Ed Description Value / Clarification


Tr1 2 Which ACSI services are tracked by LTRK.GenTrk Not Applicable

A-66 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE


GE
Grid Solutions

3 Series Protective Relay Platform

Appendix B: Warranty and Revision


History

Warranty and Revision History

Warranty
For products shipped as of 1 October 2013, GE warrants most of its GE manufactured
products for 10 years. For warranty details including any limitations and disclaimers, see
our Terms and Conditions at https://www.gegridsolutions.com/multilin/warranty.htm
For products shipped before 1 October 2013, the standard 24-month warranty applies.

Change notes
Manual Revision history

Table 1: Revision History


MANUAL P/N RELEASE DATE
1601-0246-A1 June 2016
1601-0246-A2 March 2017
1601-0246-A3 September 2017
1601-0246-A4 July 2019
1601-0246-A5 June 2021

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE B-1


CHANGE NOTES

Major Updates
For information on the updates included in this release of the 3 Series Communications
Guide, please refer to the latest release notes for the 3 Series 2.6x version online.

This manual replaces the following individual product Communications Guides: