ATEX Certificates
ATEX Certificates
ATEX Certificates
1
EU-Type Examination Certificate
2 Equipment intended for use in potentially explosive atmospheres
Directive 2014/34/EU
7 This product and any acceptable variations thereto are specified in the appendix to this certificate and
the documents referred to therein.
8 DEKRA Testing and Certification GmbH, Notified Body number 0158, in accordance with Article 17 of
Directive 2014/34/EU of the European Parliament and of the Council, dated 26 February 2014, certifies
that this product has been found to comply with the Essential Health and Safety Requirements relating
to the design and construction of products intended for use in potentially explosive atmospheres given
in Annex II to the Directive.
The examination and test results are recorded in the confidential Report No. BVS PP 02.2017 EU.
9 The Essential Health and Safety Requirements are assured in consideration of:
10 If the sign “X” is placed after the certificate number, it indicates that the product is subject to the Special
Conditions for Use specified in the appendix to this certificate.
11 This EU-Type Examination Certificate relates only to the design and construction of the specified
product. Further requirements of the Directive apply to the manufacturing process and supply of this
product. These are not covered by this certificate.
DEKRA Testing and Certification GmbH, Handwerkstr. 15, 70565 Stuttgart, Germany
Certification body: Dinnendahlstr. 9, 44809 Bochum, Germany
Phone +49.234.3696-400, Fax +49.234.3696-401, e-mail DTC-Certification-body@dekra.com
13 Appendix
14 EU-Type Examination Certificate
BVS 22 ATEX E 006
15 Product description
15.1 Subject and type
Control Unit type GHG 44 * * * ** * ****,
Distribution board GHG 619 ** ** * ****, EXKO * ***** * ****
Control Unit type GHG 44 * * * ** * ****
GHG 44 * * * ** * ****
1 2 3 4 5 6 7 8
1. Manufacturing marking
2. Control Unit
3. Enclosure type / Size
1 Combination of various polyester enclosures
3 light alloy enclosure - separate approval
4 Ex44 (size 1)
5 Ex45 (size 5)
7 Ex47 (size 4)
8 Ex48 (size 2)
9 Ex49 (size 3)
4. Material
2. Polyester enclosure
3. Metal enclosure
5. Counting number for e.g. single control unit, combinations or mixed applications
6./7./8. Without influence on the explosion protection with 6,8 counting number and 7 any letter
DEKRA Testing and Certification GmbH, Handwerkstr. 15, 70565 Stuttgart, Germany
Certification body: Dinnendahlstr. 9, 44809 Bochum, Germany
Phone +49.234.3696-400, Fax +49.234.3696-401, e-mail DTC-Certification-body@dekra.com
15.2 Description
The control units / distribution boxes of the type GHG 44 * * * ** * ****, GHG 619 ** ** * **** and
EXKO * ***** * **** in the types of protection Increased Safety "eb" and Protection by Enclosure "tb"
against dust explosion are used for fusing, controlling, switching, distributing and branching
electrical energy, e.g. main circuits, lighting circuits, heating circuits, control circuits, intrinsically
safe circuits, etc.
The control devices / distribution boxes are suitable for use in Zones 1, 2, 21 and 22.
Industrial components can also be used in the dust variant for Zone 21. A thermal analysis is also
carried out for this.
The used empty enclosure series of polyester or metal is separately tested and certified according
to ATEX certificate PTB 99 ATEX 3118 U.
Many different separately certified components and devices can be installed in the enclosure
according to the manufacturer's documentation (e.g. list of components).
In the case of intrinsically safe circuits in the control unit, this is a simple apparatus according to
EN 60079-11 and a marking must be added on the enclosure. The creepage and clearance
distances between the intrinsically safe circuits and earth, between two different intrinsically safe
circuits and between intrinsically safe and non-intrinsically safe circuits are taken into account when
installing the terminals.
In the case of flameproof, encapsulated, intrinsically safe or increased safety installations, the
marking on the enclosure must be supplemented accordingly.
15.3 Parameters
To determine the thermal parameters, a calculation tool which has been tested for this purpose is
used. The suitability of the calculation tool was tested as part of the approval IECExPTB19.0021
with practically determined values.
16 Report Number
None
Note:
Depending on the selection of components, the ambient temperature range can be reduced.
The instructions for use of the separately certified components and devices used must be
provided by the manufacturer to the user by passing on the complete and relevant
documentation.
DEKRA Testing and Certification GmbH, Handwerkstr. 15, 70565 Stuttgart, Germany
Certification body: Dinnendahlstr. 9, 44809 Bochum, Germany
Phone +49.234.3696-400, Fax +49.234.3696-401, e-mail DTC-Certification-body@dekra.com
18 Essential Health and Safety Requirements
The Essential Health and Safety Requirements are covered by the standards listed under item 9.
_____________________________________________________________________________________
We confirm the correctness of the translation from the German original.
In the case of arbitration only the German wording shall be valid and binding.
__________________________
____
____
________
__ ________
__
Managing Director
Direc
DEKRA Testing and Certification GmbH, Handwerkstr. 15, 70565 Stuttgart, Germany
Certification body: Dinnendahlstr. 9, 44809 Bochum, Germany
Phone +49.234.3696-400, Fax +49.234.3696-401, e-mail DTC-Certification-body@dekra.com