Dekra 21ukex0304u
Dekra 21ukex0304u
Dekra 21ukex0304u
CERTIFICATE
(1)
UK Type Examination
(2) Component intended for use on/in an Product or
protective system intended for use in potentially
explosive atmospheres - UKSI 2016:1107 (as amended)
– Schedule 3A, Part 1
(3) UK Type Examination Certificate Number: DEKRA 21UKEX0304U Issue Number: 0
(7) This product and any acceptable variation thereto is specified in the schedule to this certificate and the
documents therein referred to.
(8) DEKRA Certification UK Ltd., Approved Body number 8505 in accordance with Regulation 42 of the Equipment
and Protective Systems Intended for Use in Potentially Explosive Atmospheres Regulations 2016, UKSI
2016:1107 (as amended), certifies that this product has been found to comply with the Essential Health and
Safety Requirements relating to the design and construction of products intended for use in potentially explosive
atmospheres given in Schedule 1 of the Regulations.
The examination and test results are recorded in confidential test report number EX22090002-011 Issue 0.
(9) Compliance with the Essential Health and Safety Requirements has been assured by compliance with:
except in respect of those requirements listed at item 18 of the Schedule to this certificate.
(10) The sign ”U” is placed after the certificate number. It indicates that this certificate must not be mistaken for a
certificate intended for an equipment or protective system. This partial certification may be used as a basis for
certification of an equipment or protective system.
(11) This UK Type Examination Certificate relates only to the design and construction of the specified product.
Further requirements of the Regulations apply to the manufacturing process and supply of this product. These
are not covered by this certificate.
II 2 GD Ex eb IIC Gb
DEKRA Certification UK Ltd., Stokenchurch House, Oxford Road, Stokenchurch, Buckinghamshire HP14 3SX, United Kingdom
T +44 330 9120368 certification.uk@dekra.com www.DEKRA-UK.co.uk Registered 13129030
(13) SCHEDULE
(14) to UK Type Examination Certificate DEKRA 21UKEX0304U Issue No. 0
(15) Description
Terminal Blocks (all colors) UT 2,5; UT 4; UT 4-MTD; UT 6; UT 10; UT 10 SL; UT 16; UT 35; UT 35
IB, Protective Conductor Terminal Blocks UT 2,5-PE; UT 4-PE; UT 4-MTD-PE; UT 4-MTD-PE/S;
UT 6-PE; UT 10-PE; UT 16-PE; UT 35-PE; UT 35-PE IB and accessories are intended for the
connection of copper conductors in enclosures fulfilling the degree of protection which is required
by the applied type of protection for the end-application. The Terminal Blocks and Protective
Conductor Terminal Blocks are intended for installation on mounting rails type NS 35 according to
IEC 60715 Section TH 35.
The Pick-off Terminal Blocks AGK 4-UT 10; AGK 4-UT 16 and AGK 4-UT 35 are to be used in
combination with the associated Terminal Blocks UT 10 (SL); UT 16; UT 35 (IB).
Electrical data
Installation instructions
The instructions provided with the product shall be followed in detail to assure safe operation.
EX22090002-011 Issue 0.
1. The Terminal Blocks, the Protective Conductor Terminal Blocks and the Pick-off Terminal
Blocks shall be mounted in a certified enclosure that meets the requirements of a type of
protection as specified in EN IEC 60079-0 clause 1, with a degree of protection at least as
required for Ex e. For combustible dust these enclosures must satisfy the requirements
according to EN IEC 60079-0 and EN 60079-31.
2. When assembling with other certified series and sizes and using the associated accessories,
the required creepage distances and clearances have to be observed.
3. The installation instruction of the manufacturer shall be followed e.g. for the use of cover,
jumpers, end brackets. The data regarding current and associated temperature rise shall be
used as guideline for the given conductor cross sections. The cross section has influence on
the temperature rise which shall be assessed in the end application.
4. If the Terminal Blocks and Pick-off Terminal Blocks are used in electrical equipment of
temperature classes T1 up to T5, the highest temperature of the insulating material shall not
exceed the maximum value of the operating temperature range.
5. If the Terminal Blocks and Pick-off Terminal Blocks are used in electrical equipment of
temperature classes T6 the permissible ambient temperature range is -60 °C < Tamb < +40 °C.
6. The electrical data per Annex 1 to NL/KEM/ExTR06.0033/05 applies.
In addition to the Essential Health and Safety Requirements covered by the standards listed at item
9, all other requirements are demonstrated in the report.