10HP FLOOR 230v
10HP FLOOR 230v
10HP FLOOR 230v
1. Product lineup
Model Capacity External appearance Power Supply
220V,3Ph,60Hz
MDV-V280W/DDN1 28kW (10HP)
2. Features
2.1 Wide application range
2.1.1 Wide capacity range
The Capacity range of side discharge type is from 20kW to 45kW, which is designed to optimize performance
and better match varieties of application requirement. Especially, the integrated designed V4+I series is focus
on provide better air conditioning system solution for the small and middle-sized buildings in the global market.
2.1.2 Flexible indoor units connection
Model Max. quantity of connectable indoor units
MDV-V252W/DDN1 11
MDV-V280W/DDN1 12
2 General Information
MCAC-VTSM-2017-05 R410A DC Inverter VRF V4 Plus Individual Series Side Discharge Type 60Hz
2.2 High efficiency
2.2.1 High efficiency DC inverter compressor
High efficiency DC inverter twin rotary compressor
- 2 balance weights
Highly Stable Moving Parts:
AC motor
Efficiency (%)
DC motor
100
80
60 45%
40
Motor speed (RPM)
20
200 1000
General Information 3
R410A DC Inverter VRF V4 Plus Individual Series Side Discharge Type 60Hz MCAC-VTSM-2017-05
2.3 Enhanced comfort
2.3.1 Intelligent soft start technology
50
8hrs 10hrs
Noise dB
Sta rt End
Notes:
This function can be activated by setting at site. Temperature (load) curve shown in the graph is just an example.
defrost
4 General Information
MCAC-VTSM-2017-05 R410A DC Inverter VRF V4 Plus Individual Series Side Discharge Type 60Hz
2.4 Easy installation and service
2.4.1Compact design for effective use of space
Easy to transport
PQE & XYE, just only one group of communication wire of PQE,
achieved both of communication for indoor & outdoor unit and
network.
P Q E X Y E X Y E Reversible communication, central controller can be connected
from indoor side or outdoor side as you wish.
P Q E P Q E P Q E P Q E
General Information 5
MCAC-VTSM-2017-05 R410A DC Inverter VRF V4 Plus Individual Series Side Discharge Type 60Hz
1. Specifications
Model MDV-V252W/DDN1 MDV-V280W/DDN1
Power supply V-Ph-Hz 220V,3Ph,60Hz 220V,3Ph,60Hz
Capacity kW 25.2 28
Cooling Power input kW 6.8 7.8
EER 3.71 3.59
Capacity kW 27 31.5
Heating Power input kW 6.4 7.6
COP 4.22 4.14
Model LNB53FCFMC LNB53FCFMC
Type Rotary Rotary
Brand MITSUBISHI MITSUBISHI
Quantity 1 1
Compressor Capacity kW 26.9 26.9
Input kW 8.8 8.8
Crankcase heater W 25 25
Refrigerant oil type FV50S FV50S
Refrigerant oil charge ml 1700+1500 1700+1500
Model WZDK170-38G-1 WZDK170-38G-1
Type DC motor DC motor
Quantity 2 2
Brand Panasonic/Nidec/Weiling Panasonic/Nidec/Weiling
Outdoor fan motor Insulation class E E
Safe class IP×4 IP×4
Input W 250(up)/185(down) 250(up)/185(down)
Output W 200(up)/150(down) 200(up)/150(down)
Rated current A 1.7(up)/1.4(down) 1.7(up)/1.4(down)
Material ASG20 ASG20
Type Axial fan Axial fan
Outdoor fan Quantity mm 2 2
Diameter mm 560 560
Height 170 170
Number of rows 2 2
Tube pitch(a)×
mm 21×19.4 21×19.4
row pitch(b)
Fin spacing mm 1.5 1.5
Outdoor coil Fin type Hydrophilic fin Hydrophilic fin
Tube outside diameter mm Ф7 Ф7
Tube type Inner groove tube Inner groove tube
Coil length×height mm 1080×1512 1080×1512
Number of circuits 18 18
Outdoor air flow m3/h 10494 10494
Sound pressure level dB(A) 58 60
Connectable Total capacity % 50-130 50-130
indoor unit Max. quantity 11 12
Net dimension
mm 1120×1558×528 1120×1558×528
(W×H×D)
Outdoor uint
Packing
mm 1270×1720×565 1270×1720×565
(W×H×D)
Specifications & Performance 9
R410A DC Inverter VRF V4 Plus Individual Series Side Discharge Type 60Hz MCAC-VTSM-2017-05
Net/Gross weight kg 147/163 147/163
Type R410A R410A
Refrigerant
Factory charged kg 6.2 6.2
Throttle type Electronic expansion valve Electronic expansion valve
Design pressure (Hi/Lo) MPa 4.4/2.6 4.4/2.6
Liquid pipe mm Ф9.53 Ф9.53
Refrigerant piping
Gas pipe mm Ф22.2 Ф22.2
oC
Ambient temp. Cooling -5~48 -5~48
range Heating oC -15~24 -15~24
Notes:
Capacities are based on the following conditions:
o o o o
Cooling: Indoor temperature 27 C DB/19 C WB; Outdoor temperature 35 C DB/24 C WB.
o o o o
Heating: Indoor temperature 20 C DB/15 C WB; Outdoor temperature 7 C DB/6 C WB.
Piping length: Interconnecting piping length 7.5m, level difference of zero.
Sound values are measured in a semi-anechoic room, at a position 1m in front of the unit and 1.3m above the floor.
The above data may be changed without notice for future improvement on quality and performance.
2. Dimensions
MDV-V252W/DDN1 MDV-V280W/DDN1
Unit: mm
1558
1120
668 205.8
494
528
414
400
3. Service space
MDV-V252W/DDN1 MDV-V280W/DDN1
Single unit installation
(Wall or obstacle)
Air inlet
>300
>300
Maintain the electric
wire and pipeline
Air inlet
>600
>3000
Air outlet
>300
>600
>3000
4. Piping diagrams
MDV-V252W/DDN1 MDV-V280W/DDN1
Key components:
Oil separator: It is used to separate oil from high pressure and high temperature gas refrigerant, which is
pumped out from compressor. The separation efficiency is up to 99%, it makes the oil return back to each
compressor very soon.
Gas-liquid separator: It is used to store the liquid refrigerant and oil; it can protect the compressor from liquid
hammer.
Four-way valve (ST1): It is used to change the refrigerant flow direction; it is closed in cooling mode and
opened in heating mode.
EXV (Electromagnetic Expansion Valve): It is used to adjust refrigerant volume.
SV2: It is used to protect compressor. When any compressor discharge temperature is higher than 100oC, SV2
will be open to spray a little liquid refrigerant to cooling compressor, and it will be closed when the discharge
temperature is lower than 90oC.
SV4: It is used to help the oil in oil separator return back to compressor, guarantee the oil balance among
compressors. When the unit is initial power on, SV4 will open 120 seconds, then it will reopen after DC inverter
compressor running 5 minutes and then it will close after DC inverter compressor running 15 minutes. Later,
SV4 will open 3 minutes after DC inverter running 20 minutes regularly.
SV5: It is used to enlarge refrigerant volume to accelerate defrosting speed. In defrosting mode, SV5 will be
open to cut the refrigerant flowing circle, so the defrosting process will take less time, in cooling mode, SV5 will
always be closed.
SV6: It is used to by-pass refrigerant. It will be closed in heating and standby mode. It will be open in forced
cooling and oil return mode. In cooling mode, it will be open or closed according to discharge pressure.
SV7: It is used to balance system pressure before open the unit, and it can guarantee system reliability in low
temperature heating mode.
High pressure sensor: It is used to supervisor the discharge pressure of the compressor and to control the
DC fan speed.
T3: Pipe temperature sensor; T4: Ambient temperature sensor
5 Wiring diagram
MDV-V252W/DDN1
CN4
CN7
CN24
~ 3 ~ 2 ~1
4
5
MDV-V280W/DDN1
6. Electric characteristics
Units Power supply Compressor OFM
Model
Hz Voltage Min. Max. MCA TOCA MFA MSC RLA kW FLA
MDV-V252W/DDN1 60 220 198 242 35 37.8 40 / 28 0.17×2 2.1+1.7
MDV-V280W/DDN1 60 220 198 242 35 37.8 40 / 28 0.17×2 2.1+1.7
Notes:
1. RLA is based on the following conditions, Indoor temp. 27°C DB/19°C WB, Outdoor temp. 35°C DB
2. TOCA means the total value of each OC set.
3. MSC means the Max. current during the starting of compressor.
4. Voltage range: Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above
listed range limits.
5. Maximum allowable voltage variation between phases is 2%.
6. Selection wire size based on the value of MCA.
7. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth circuit breaker).
Symbols:
MCA: Min. Circuit Amps. (A)
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
MSC: Max. Starting Amps. (A)
RLA: Rated Locked Amps. (A)
OFM: Outdoor Fan Motor.
FLA: Full Load Amps. (A)
kW: Rated Motor Output (KW)