Installation Manual For S Series HW
Installation Manual For S Series HW
Installation Manual For S Series HW
Wall-mounted Type
The following precautions include important safty items. For electrical work, follow the local national wiring
Observe them and never forget. standard, regulation and this installation instructions. An
independent circuit and single outlet must be used.
Keep this manual with the owner's manual in a handy place If electrical circuit capacity is not enough or defect in
for future reference. electrical work, it will cause electrical shock fire.
Installation must be performed in accordance with the Use the specified cable and connect tightly and clamp
requirement of NEC and CEC by authorized personnel only. the cable so that no external force will be acted on the
terminal.
If connection or fixing is not perfect, it will cause heat-up or
fire at the connection.
The safty precautions listed here are divided into two categories. In
either case, important safty information is listed which must be read Wiring routing must be properly arranged so that control
carefully. board cover is fixed properly.
If control board cover is not fixed perfectly, it will cause
WARNING heat-up at connection point of terminal, fire or electrical
shock.
Failure to observe a warning may result in death.
If the supply cord is damaged, it must be replaced by the
CAUTION manufacture or its sevice agent or similarly qualifued
Failure to observe a caution may result in injury or damage person in order to avoid a hazard.
to the equipment.
An all-pole disconnection switch having a cintract
After completing the installation, make sure that the unit operates separation of at least 3mm in a poles should be
properly during the start-up operation. Please instruct the customer connected in fixed wiring.
on how to operate the unit and keep it maintained.Also, inform
customers that they should store this installation manual along with When carrying out piping connection, take care not to let
the owner's manual for future reference. air substances go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high
pressure in the refrigeration cycle, explosion and injury.
WARNING Do not modify the length of the power supply cord or use
Be sure only trained and qualified service personnel to of extension cord, and do not share the single outlet with
install, repair or service the equipment. other electrical appliances.
Improper installation, repair, and maintenance may result in Otherwise, it will cause fire or electrical shock.
electric shocks, short-circuit, leaks, fire or other damage to
the equipment. Carry out the specified installation work after taking into
account strong winds, typhoons or earthquakes.
Install according to this installation instructions strictly. Improper installation work may result in the equipment falling
If installation is defective, it will cause water leakage, electric and causing accidents.
shocks, fire.
installation manual
1
If the refrigerant leaks during installation, ventilate the There is strong electromagnetic wave existing.
area immediately.
There are inflammable materials or gas.
Toxic gas may be produced if the refrigerant comes into the
place contacting with fire. There is acid or alkaline liquid evaporating.
After completing the installation work, check that the The appliance shall not be installed in the laundry.
refrigerant does not leak. Avoid installing it in a narrow sapce which has a high
Toxic gas may be produced if the refrigerant leaks into the requirement to noise.
room and comes into contact with a source of fire, such as a
fan heater, stove or cooker. Other special conditions.
In buses or cabinets.
installation manual
2
3. ATTACHED FITTINGS
Please check whether the following fittings are of full scope. If there are some spare fittings , please restore them carefully.
4. Wrapping tape 1
5.Drain pipe 1
7. Remote controller 1
(including operation manual)
Keep the remote controller at least 1m apart from the nearest TV set or stereo
equipment. (it is necessary to prevent image disturbances or noise interferences.)
Do not install the remote controller in a place exposed to direct sunlight or close to a
heating source, such as a stove. Remote controller
holder
Note that the positive and negative poles are right positions when loading batteries. Remote
controller
This manual is subject to changes due to technological improvement without further Fig.3-1
notices.
installation manual
3
4. INSPECTING AND HANDLING THE UNIT
At delivery, the package should be checked and any damage should 5.2 Drilling A Hole and Mounting Installation
be reported immediately to the carrier claims agent.
Board
When handling the unit, take into account the following:
Installation Board and Its Direction (unit: mm)
1 Fragile, handle the unit with care.
57
3 Move this unit as originally package as possible.
290
4 When lifting the unit , always use protectors to prevent belt
damage and pay attention to the position of the unit’s centre
of gravity. 712
915
the shape of indoor unit Fig.5-1
65
the following reauirements:
315
requirement to noise.
The ceiling is horizontal, and its structure can endure the
weight of the indoor unit. 794
1070
The outlet and the inlet are not impeded, and the
influence of external air is the least. the shape of indoor unit Fig.5-2
The air flow can reach throughout the room.
The connecting pipe and drainpipe could be extracted out
1 Fix the installation board.
easily.
There is no direct radiation from heaters. Install the installation board horizontally on structural parts in
the wall with the spaces provided around the plate.
Don't install it in a place whose air contains much salt. If
this can't be avoided, choose a anticorrosive model. In case of brick, concrete or similar type walls,make 5mmdia,
holes in the wall. Insert clip anchors for appropriate mounting
screws.
Fig.5-3
installation manual
4
False installation When connection extension drain hose,insulate the
connecting part of extension drain hose with a shield pipe
horizontal line
Extension drainhose
Drain hose
Fig.5-6
2 Connection pipe
Left piping
mounting board
of indoor unit
Left back piping
Right piping
Right back piping
Fig.5-7
horizontal line
43
. .. .. .
Always use a wall hole conduit when piercing metal lath,
. .......
ply wood or metal plate.
........................................................................................ ............
. .. . .. . ..... ... .. .. .. . .
Fig.5-8
5.3 Connective Pipe and Drainage Installation Fix the end of the connective pipe.(Refer to Tightening
Connection in REFRI-GERANT PIPING CONNECTION)
1 Drainage
Run the drain hose sloping downward. Do not install the drain
hose as illustrated below.
CAUTION
Connect the indoor unit first then the outdoor unit and bend
and arrange the pipe carefully.
Do not allow the piping to let out from the back of the
indoor unit.
Do not allow the piping to let out from the back of the
indoor unit.
installation manual
5
3 Piping and bandaging
6. REFRIGERANT PIPE INSTALLATION
Wind the connective cable, drain hose and wiring with tape
securely, evenly as shown below. CAUTION
Because the condensed water from rear of the indoor unit is Ventilate the air if there was any refrigerant leakage during
gathered in Pond Box and is piped out of room. Do not put installation.Leaked refrigerant will generate poisonous gas if
anything else in the box. meeting fire.
Connective
Pipe room 6.1 Allowed Length and Drop of Piping
cable
.. . .
.
.. . . ..
.
. Connective
Requirements are different when installing the Outdoor
.. . .. .
pipe
.. .. Unit,Please refer to Outdoor Unit Installation Manual for
.
. ... .. . .
detailed information.
Wrapping belt
Drain hose
Fig.5-9 6.2 Material and Size of the Piping
Table 6-1
5.4 Indoor Unit Installation Pipe Material Copper Pipe for Air Conditioner
Model (kW) 1.5/2.2/2.8/3.6/4.5 5.6/7.1
Pass the piping through the hole in the wall. (Gas side) Φ12.7 Φ15.9
Size(mm)
(Liquid side) Φ6.4 Φ9.5
Put the claw at the back of the indoor unit on the hook of
the installation board, move the Indoor Unit from side to
side to see that it is securely hooked.
hooker
CAUTION
The service man should note down the piping length and
Fig.5-10 refrigerant volume added on the nameplate, which is on the
Electric Control Box Cover of outdoor unit for to diagnose the
compressor when compressor malfunction occurs.
CAUTION
installation manual
6
1 Take out the faceplate,then dismantle the display cover
plate.(see Fig.7-1)
Tightening Torque
faceplate
Table 6-2
Outer diameter(mm) Tightening Torque
of connection piping (N.m)
S faceplate faceplate
NOTE
Model(kW) 1.5~7.1
Phase 1-Phase
Power
Frequency and volt 208/230V-1ph-60Hz
2 Individual connect the power cord and signal line,adjust the
dial switch.(see Fig.7-2)
Manual switch/Insurance (A) 15/15
the wire holder of power the wire holder of signal
3x2.5 cord(three-position)) line (five-position))
Indoor unit power wiring (mm2)
2x4.0+1x2.5 display cover plate
(Add eletrical auxiliary heat)
Indoor/outdoor connectingwiring
(mm2) (Electric signal) 3x0.75(3x0.75)
5A dial switch
Fuse (A)
8A
(Add eletrical auxiliary heat)
S faceplate
Power (208/230V-1ph-60Hz)
the wire holder of power the wire holder of signal
cord(three-position)) line (five-position))
INDOOR UNIT
wiring cover plate
CENTRAL CONTROL
MONITOR(CCM) COMPUTER
INDOOR UNIT
OUTDOOR UNIT dial switch
Fig.7-2
INDOOR UNIT
CAUTION
installation manual
7
7.1 Terminal Board Diagram 7.2 Horsepower set
Please refer to the indoor unit wiring diagram for the wiring.
Horsepower code
PO WER_S
NOTE EF 0
D
123 4
ABC
The air-conditioners can connect with Central Control Monitor
(CCM). Before operation, please wiring correctly and set system 56
789
address and network address of indoor units.
ENC1
RED
RED
3 4500W(1.5HP)
POWER IN POWER IN 5600W(2.0HP)
4
INDOOR UNIT POWER INDOOR UNIT POWER 7100W(2.5HP)
5
208/230V-1ph-60Hz 208/230V-1ph-60Hz
(Conventional) (Special for UL)
YELL OW
BLA CK
BLA CK
WHIT E
GRAY
BLU E
X Y (E) P Q (E)
MAIN BOARD DISPLAY BOARD Please switch off the power before setting,otherwise the
unexpected error will occur.
WIRE CONTROLLER
installation manual
8
7.4 Main board Code designation
SW1 definition
SW1 ● 1 means factory test mode SW1
ON ON ● 01 means DC fan static pressure is 1
● 0 means auto addressing mode
(reserved)
(default setting)
1234 1234
SW1 SW1
ON ● 1 means DC fan Is chosen ON ● 10 means DC fan static pressure is 2
● 0 means AC fan Is chosen
(reserved)
1234 1234
SW1 SW1
ON ● 00 means DC fan static pressure is 0
ON ● 11 means DC fan static pressure is 3
(reserved) (reserved)
1234 1234
SW2 definition
SW 2 SW2
ON ● 00 means shutting down the ON ● 00 means the time of stopping
unit to"stop cold air" at 15 degrees indoor fan is 4 minutes
1234 1234
SW 2 ● 01 means shutting down the SW2
ON ON ● 01 means the time of stopping
unit to"stop cold air" at 20 degrees indoor fan is 8 minutes
1234 1234
SW 2 ● 10 means shutting down the SW2
ON ON ● 10 means the time of stopping
unit to"stop cold air" at 24 degrees
indoor fan is 12 minutes
1234 1234
SW 2 ● 11 means shutting down the SW2
ON unit to"stop cold air" at 26 degrees ON ● 11 means the time of stopping
indoor fan is 16 minutes
1234 1234
SW5 definition
S W5 SW5
ON ● 00 means temp.compensation ON ● 10 means temp.compensation
value is 6 degrees under heat mode value is 4 degrees under heat mode
1 2 1 2
S W5 SW5
ON ● 01 means temp.compensation ON ● 11 means temp.compensation
value is 2 degrees under heat mode value is 8 degrees under heat mode
1 2 1 2
J1,J2 definition
SW6 definition
SW6
J1
without jumper "J1" for
ON ● 1 means old display panel auto restart function
● 0 means new display panel
1 2 3
SW6 J1
ON ● 1 means auto air blow under auto mode with jumper "J1" for
● 0 means auto air blow under non-auto mode non-auto restart function
1 2 3
SW6 J2
ON reserved reserved
1 2 3
installation manual
9
0/1 definition
According to the user’s requirement, install the remote controller
frame where the remote controller’s signal can reach the indoor
ON unit smoothly.
Means 0
Test operation
● Set the air conditioner under the mode of “COOLING”with the
ON remote controller, and check the following points per the
Means 1 ● “Owner’s Manual”If there is any malfunction, please resolve it
through chapter “Troubles And Causes ”.
● The length of the tubing and the added stow capacity of the
refrigerant have been recorded.
● The power voltage fits the rated voltage of the air conditioner.
installation manual
10
202000172227