The Quadruple-Tank Process - Johansson
The Quadruple-Tank Process - Johansson
The Quadruple-Tank Process - Johansson
1 Introduction
Multivariable control techniques have received increased industrial interest [31]. It is often hard to tell when these methods are needed for improved performance in practice and when simpler control structures are sucient. A key issue is the functional limits of the system: what design specications are reasonable? It was already pointed out by Bode [6] that nonminimum-phase characteristics of a system impose limitations for linear feedback designs. Still it happens that unrealistic specications
K. H. Johansson is with the Department of Electrical Engineering and Computer Sciences, University of California, Berkeley, U.S.A., johans(eecs.berkeley.edu.
Figure 1: The Quadruple-Tank Process shown together with a controller interface running on a PC. are made, as pointed out in [33, 3, 11]. Performance limitations in control systems have received extensive interest recently. Several new results, particularly for scalar and multivariable linear systems, have been presented. Bode's original result together with extensions are covered in the textbooks [10, 30]. Zames and Francis [36, 38, 9] showed that right half-plane zeros impose restrictions on the sensitivity function: if the sensitivity is forced to be small in one frequency band, it has to be large in another, possibly yielding an overall bad performance. They also showed that if the system does not have any right half-plane zeros, then theoretically it can be arbitrarily well controlled. The latter result has been generalized to decentralized control structures [37, 19, 20]. This paper describes a new laboratory process, which was designed to illustrate performance limitations due to zero location in multivariable control systems. The process is called the QuadrupleTank Process and consists of four interconnected water tanks and two pumps. The system is shown in Figure 1. Its inputs are the voltages to the two pumps and the outputs are the water levels in the 2
lower two tanks. The Quadruple-Tank Process can easily be build by using two double-tank processes, which are standard processes in many control laboratories [5, 4]. The setup is thus simple, but still the process can illustrate several interesting multivariable phenomena. The linearized model of the Quadruple-Tank Process has a multivariable zero, which can be located in either the left or the right half-plane by simply changing a valve. Both the location and the direction of a multivariable zero are important for control design. They have direct physical interpretations for the Quadruple-Tank Process, which make the process suitable to use in control education. Few multivariable laboratory processes have been reported in the literature. Mechanical systems such as the helicopter model [24, 1] and the active magnetic bearing process [35] have been developed at ETH in Zrich. Davison has developed a water tank process, where multivariable water level u control and temperature{ ow control can be investigated [8]. Some multivariable laboratory processes are commercially available, for example from Quanser Consulting in Canada, Educational Control Products in U.S.A., and Feedback Instruments and TecQuipment in U.K. There does not, however, seem to exist any laboratory processes that demonstrate multivariable zero location and direction in an illustrative way. This was one of the main motivations for the development of the Quadruple-Tank Process [15]. The outline of the paper is as follows. A nonlinear model for the Quadruple-Tank Process based on physical data is derived in Section 2. It is linearized and the linear model is validated using experimental data. The location and the direction of a multivariable zero of the linearized model are derived in Section 3. It is shown that the valve positions of the process uniquely determine if the system is minimum phase or nonminimum phase. The relative gain array is also derived. Section 4 discusses the nonlinear model of the Quadruple-Tank Process. Properties of the nonlinear zero dynamics and of the stationary point of the nonlinear model are given. In Section 5 linear models are estimated from experimental data and they are compared to the physical model. Decentralized PI control of the Quadruple-Tank Process is presented in Section 6, where performance losses due to right half-plane zeros are illustrated. Some concluding remarks are given in Section 7. Early versions of this paper have been presented as [15, 18].
2 Physical Model
In this section we derive a mathematical model for the Quadruple-Tank Process from physical data. The section ends with some further comments on the construction of the process. A schematic diagram of the process is shown in Figure 2. The target is to control the level in the lower two tanks with two pumps. The process inputs are v1 and v2 (input voltages to the pumps) and the outputs are y1 and y2 (voltages from level measurement devices). Mass balances and Bernoulli's law yield dh1 = a1 p2gh + a3 p2gh +
1k1 v ; 1 A 3 A 1 dt A1 1 1 dh2 = a2 p2gh + a4 p2gh +
2k2 v ; 2 A 4 A 2 dt A2 2 2 (1) dh3 = a3 p2gh + (1
2)k2 v ;
3 dt A3 A3 2 dh4 = a4 p2gh + (1 1)k1 v ; 4 dt A4 A4 1 where Ai is the cross-section of Tank i, ai the cross-section of the outlet hole, and hi the water level. The voltage applied to Pump i is vi and the corresponding ow is ki vi . The parameters 1; 2 2 (0; 1) are determined from how the valves are set prior to an experiment. The ow to Tank 1 is 1k1 v1 and the ow to Tank 4 is (1 1)k1v1 and similarly for Tank 2 and Tank 3. The acceleration of gravity is denoted g . The measured level signals are kc h1 and kc h2. The parameter values of the laboratory
A1; A3 [cm2] 28 A2; A4 [cm2] 32 a1; a3 [cm2] 0:071 a2; a4 [cm2] 0:057 kc [V/cm] 0:50 g [cm/s2] 981
The model and control of the Quadruple-Tank Process are studied at two operating points: P at which the system will be shown to have minimum-phase characteristics and P+ at which it will be shown to have nonminimum-phase characteristics. The chosen operating points correspond to the following parameter values: 4
Tank 3
Tank 4
Pump 1
v1
Tank 1
y1
Tank 2
y2
Pump 2
v2
Figure 2: Schematic diagram of the Quadruple-Tank Process. The water levels in Tank 1 and Tank 2 are controlled by two pumps. The positions of the valves determine the location of a multivariable zero for the linearized model. The zero can be put in either the left or the right half-plane. (h0; h0) 1 2 0; h0) (h3 4 0 0 (v1 ; v2 ) (k1; k2) ( 1; 2)
P (12:4; 12:7) [cm] [cm] (1:8; 1:4) (3:00; 3:00) [V] [cm3/Vs] (3:33; 3:35) (0:70; 0:60)
P+ (12:6; 13:0) (4:8; 4:9) (3:15; 3:15) (3:14; 3:29) (0:43; 0:34)
Introduce the variables xi := hi h0 and ui := vi vi0. The linearized state-space equation is then i
given by
2 6 6 6 dx = 6 6 dt 6 6 6 4
(2)
s Ai 2h0 ; Ti = a g i i
i = 1; : : :; 4:
(3)
The corresponding transfer matrix is 3 2 1c1 (1 2 )c1 6 1 sT (1 + sT3 )(1 + sT1) 7 ; 7 G(s) = 6 (1 + 1)1c2 5 4 2c2 (1 + sT4 )(1 + sT2) 1 + sT2 where c1 = T1 k1kc =A1 and c2 = T2k2kc =A2 . Note the way 1 and 2 enter the matrix. For the two operating points P and P+ we have the following time constants:
(4)
P P+ (T1; T2) (62; 90) (63; 91) (T3; T4) (23; 30) (39; 56)
The dominating time constants are thus similar for both operating conditions. The physical modeling gives the two transfer matrices 2 3 2:6 1:5 1 + 62s (1 + 23s)(1 + 62s) 7 G (s) = 6 (5) 4 5 1:4 2:8 (1 + 30s)(1 + 90s) 1 + 90s 6
Output y1 1 1
Output y2
0.5
0.5
0.5
1.5 0
500
1500
1.5 0
500
1500
Figure 3: Validation of the minimum-phase model G . The outputs from the model (dashed lines) together with the outputs from the real process (solid lines) are shown.
Output y1 1.5 1 0.5 [Volt] 0 0.5 1 1.5 0 500 1000 Time [s] 1500 [Volt] 1.5 1 0.5 0 0.5 1 1.5 0 500 1000 Time [s] 1500 Output y2
Figure 4: Validation of the nonminimum-phase model G+ . Same variables as in Figure 3 are shown.
3 2:5 1:5 1 + 63s (1 + 39s)(1 + 63s) 7 : (6) 5 2:5 1:6 (1 + 56s)(1 + 91s) 1 + 91s Figures 3 and 4 show simulations of these two models compared to real data obtained from identication experiments discussed in Section 5. The inputs are pseudo-random binary sequences (PRBSs) with low amplitudes, so that the dynamics are captured by a linear model. The model outputs agree well with the responses of the real process. The Quadruple-Tank Process is simple to build. The four tanks are made out of plexiglas tubes.
7
and
2 G+(s) = 6 4
The height of each tank is 20 cm and the diameter is about 6 cm. The pumps are gear pumps with a capacity of 2:5 `=min. Capacitive electrodes are used for measuring the water levels. The tanks and the pumps are connected by exible tubings, each with a diameter of 6 mm. The equipment is of the same type as used for the double tank process described in [5, 4].
Zero location
cc Q4 1 2
1
2 i=1(1 + sTi) (7) (1
1)(1
2) : (1 + sT3)(1 + sT4)
1
2 The transfer matrix G thus has two nite zeros for
1 ;
2 2 (0; 1). One of them is always in the left half-plane, but the other can be located either in the left or the right half-plane, as follows from the following root-locus argument. Introduce a parameter 2 (0; 1) as
det G(s) = The zeros of the transfer matrix in (4) are the zeros of the numerator polynomial of the rational function
:= (1
1)(1
2)=
1
2:
If is small, the two zeros are close to 1=T3 and 1=T4, respectively. Furthermore, one zero tends to 1 and one zero tends to +1 as 1. If = 1 one zero is located at the origin. This case corresponds to
1 +
2 = 1. It follows that the system is nonminimum phase for 0 <
1 +
2 < 1 and minimum phase for 1 <
1 +
2 < 2: 8
2
1
P P+
Figure 5: Depending on the values of the valve parameters 1 and 2 the system is minimum or nonminimum phase. Above the straight line between (0; 1) and (1; 0) the system is minimum phase and below it is nonminimum phase. The two cases studied in this paper corresponds to the two dots. Recall that 1 + 2 = 1:30 > 1 for P and 1 + 2 = 0:77 < 1 for P+ . Figure 5 shows the location of the two operating points P and P+ . For operating points above the solid line the system is minimum phase and below it is nonminimum phase. The multivariable zero being in the left or in right half-plane has a straightforward physical interpretation. Let qi denote the ow through Pump i and assume that q1 = q2 . Then the sum of the ows to the upper tanks is [2 ( 1 + 2 )]q1 and the sum of the ows to the lower tanks is ( 1 + 2 )q1. Hence, the ow to the lower tanks is greater than the ow to the upper tanks if 1 + 2 > 1, i.e., if the system is minimum phase. The ow to the lower tanks is smaller than the ow to the upper tanks if the system is nonminimum phase. It is intuitively easier to control y1 with u1 and y2 with u2, if most of the ows goes directly to the lower tanks. The control problem is particularly hard if the total ow going to the left tanks (Tanks 1 and 3) is equal to the total ow going to the right 9
tanks (Tanks 2 and 4). This corresponds to 1 + 2 = 1, i.e., a multivariable zero in the origin. There is thus an immediate connection between the zero location of the model and physical intuition of controlling the Quadruple-Tank Process.
Zero direction
An important dierence between scalar systems and multivariable systems is that not only the location of a multivariable zero is important but also its direction. We dene the (output) direction of a zero z as a vector 2 R2 of unit length such as T G(z ) = 0. If is parallel to a unit vector, then the zero is only associated with one output. If this is not the case, then the eect of a right half-plane zero may be distributed between both outputs. See [30] for further discussions. For the transfer matrix G in (4), the zero direction of a zero z > 0 is given by 3 23 2 3T 2
1c1 (1
2 )c1 T 15 6 1 + zT1 (1 + zT3 )(1 + zT1 ) 7 = 405 : 6 7 4 (8) 4 (1
1)c2 5 0
2c2 2 (1 + zT4)(1 + zT2) 1 + zT2 Note that it follows from this equation that 1; 2 6= 0, so the zero is never associated with only one output. If we solve (8) for
2 and simplify, it is easy to show that
(9)
From this equation it is possible to conclude that if 1 is small, then z is mostly associated with the rst output. If 1 is close to one, then z is mostly associated with the second output. Hence, for a given zero location, the relative size of 1 and 2 determines which output the right half-plane zero is related to.
1 0.8 0.6
=2 = 1 =0
=1
2
0.4 0.2 0 0
0.2
0.4
0.6
0.8
Figure 6: Contour plot of the RGA as a function of the valve parameters 1 and 2. The plot is drawn for = 10; 9; : : :; 10. We have 0 below the straight line between (0; 1) and (1; 0) and 1 above the line. Close to the line, jj is large. See [13] for a summary of closed-loop properties predicted from the RGA. McAvoy [25] proposed that one should strive for a pairing with 0:67 < < 1:50. The system is particularly hard to control if < 0. The RGA of the Quadruple-Tank Process is given by the simple expression
= + 1 2 1 : 1 2
(10)
Note that the RGA is only depending on the valve settings and no other physical parameters of the process. Figure 6 shows a contour plot of as a function of 1 and 2 . The edges of the box 0 1 ; 2 1 corresponds to = 0 and = 1 as is shown in the gure. The magnitude of increases as 1 + 2 becomes close to one. There are no 1; 2 2 (0; 1) such that 2 (0; 1). From (10) we see for instance that < 0 if 1 + 2 < 1, which corresponds to the nonminimum-phase setting discussed previously. If the valves of the Quadruple-Tank Process are set such that 1 + 2 < 1, then the RGA analysis 11
suggests that another input{output pairing for decentralized control should be chosen. Let 2 3 e G G G = 4 21 225
G11 G12
e be the linearized model with y1 and y2 permuted. The RGA for G is e = (1 1 1 )(1 2) : 1 2 e e Hence, if 1 + 2 < 1 then > 0 so a decentralized control structure corresponding to G is preferable according to the RGA. This is intuitive from physical considerations.
The characteristic equation for the linearized dynamics of (11) is (1 + sT )(1 + sT ) (1 1)(1 2) = 0;
where T3 and T4 are the time constants dened in (3). The solutions of this equation are equal to the zeros of G, compare (7). In particular, it follows that the nonlinear system is nonminimum phase for 0 < 1 + 2 < 1 and minimum phase for 1 < 1 + 2 < 2. This is not surprising since the operations of taking a linear approximation and calculating the zero dynamics commute [14]. Some nonlinear design methods like feedback linearization techniques require that the zero dynamics are stable. Modications to these have been proposed to extend the applicability to nonminimum-phase systems. The nonlinear zero dynamics of the Quadruple-Tank Process can be made stable or unstable by simply changing a valve. The process is thus suitable to illustrate how sensitive a nonlinear design method is to the stability of the zero dynamics.
1 2
Steady-state conditions
For a stationary operating point (h0; v 0), the dierential equations in (1) give that a3 q2gh0 = (1
2)k2 v0;
2 A3 q 3 A3 a4 0 (1
1)k1 0 A4 2gh4 = A4 v1 ;
13
a1 q2gh0 =
1k1 v0 + (1
2)k2 v0; 2 A1 q 1 A1 1 A1 a2 2gh0 = (1
1)k1 v0 +
2k2 v0: 2 A2 A2 1 A2 2 0 0 It follows that there exists a unique constant input (v1 ; v2 ) giving the steady-state levels (h0 ; h0) if 1 2
and only if the matrix
and thus
is non-singular, i.e., if and only if 1 + 2 6= 1. The singularity of this matrix is natural. In stationarity, the ow through Tank 1 is 1q1 + (1 2)q2 and the ow through Tank 2 is 2 q2 + (1 1)q1 , where qi is the ow through Pump i. If 1 + 2 = 1, these ows equal 1(q1 + q2) and (1 1)(q1 + q2), respectively. The stationary ows through Tank 1 and Tank 2 are thus dependent, and so must the levels also be. Note that the condition 1 + 2 = 1 is equivalent to that G in (4) has a zero in the origin.
Output y1 1 1
Output y2
0.5
0.5
0.5
1.5 0
500
1500
1.5 0
500
1500
Figure 7: Validation of identied state-space model for the minimum-phase setting. Outputs from model (dashed) together with the outputs from the real process (solid) are shown. and 220. Its two zeros are located in 0:288 and 0:019. The validation results are of similar quality as the result for the physical models shown in Figures 3 and 4. Note that the minimum-phase setting gives an identied model with no right half-plane zero, whereas the nonminimum-phase setting gives a dominating right half-plane zero, i.e., a right half-plane zero close to the origin compared to the time scale given by the time constants. This agrees with the physical model. Gray-box models with structure xed to the linear state-space equation (2) gave similar validation results as the ones previously shown. Because of the xed structure, the number of poles and zeros are the same as for the physical model. For the minimum-phase setting we have time constants (T1; T2; T3; T4) = (96; 99; 32; 39) and zeros at 0:045 and 0:012, whereas for the nonminimumphase setting we have (T1; T2; T3; T4) = (77; 112; 53; 55) and zeros at 0:014 and 0:051. The zeros agree very well with the ones derived from the physical model. The conclusion of this section is that the Quadruple-Tank Process is also suitable to illustrate multivariable system identication techniques.
6 Decentralized PI Control
The decentralized control law u = diagfC1; C2g(r y ) in Figure 9 is in this section applied to the real process as well as to nonlinear and linear process models. PI controllers of the form
1 ; C (s) = K 1 + ` = 1; 2
< <
Ti< s
15
Output y1 1.5 1 0.5 [Volt] 0 0.5 1 1.5 0 500 1000 Time [s] 1500 [Volt] 1.5 1 0.5 0 0.5 1 1.5 0 500
Output y2
1500
Figure 8: Validation of identied state-space model for the nonminimum-phase setting. Same variables as in Figure 7 are shown.
r1 r2
C1
u1 u2
G
y1 y2
C2
Figure 9: Decentralized control structure with two PI controllers C1 and C2. are tuned manually based on simulations of the linear physical models (5) and (6). For the minimum-phase setting it is easy to nd controller parameters that give good performance. The controller settings (K1; Ti1) = (3:0; 30) and (K2; Ti2) = (2:7; 40) give the responses shown in Figure 10. The responses are given for a step in the reference signal r1. The top four plots show control of the simulated nonlinear model in (1) (dashed lines) and control of an identied linear statespace model (solid). The four lower plots show the responses of the real process. The discrepancies between simulations and the true time responses are small. Manually tuning to nd controller parameters that give good closed-loop performance is dicult for the nonminimum-phase setting. This is, of course, due to that the nonminimum-phase process is 16
Output y1 7.2 7 [Volt] [Volt] 6.8 6.6 6.4 6.2 6 100 200 Time [s] Input u1 6 5 [Volt] 4 3 2 100 200 Time [s] Output y1 7.2 7 [Volt] [Volt] 6.8 6.6 6.4 6.2 6 100 200 Time [s] Input u1 6 5 [Volt] 4 3 2 100 200 Time [s] 300 [Volt] 6 5 4 3 2 100 300 7.2 7 6.8 6.6 6.4 6.2 6 100 300 [Volt] 6 5 4 3 2 100 300 7.2 7 6.8 6.6 6.4 6.2 6 100
Output y2
300
300
300
300
Figure 10: Results of PI control of minimum-phase system. The upper four plots show simulations with the nonlinear physical model (dashed) and the identied linear model (solid). The four lower plots show experimental results.
17
Output y2
1000
3000
1000
3000
5 4.5 4 3.5 3 2.5 1000 2000 Time [s] Output y1 8 7.5 [Volt] 7 6.5 6 [Volt] 3000
5 4.5 4 3.5 3 2.5 1000 2000 Time [s] Output y2 8 7.5 7 6.5 6 3000
[Volt]
1000
3000
[Volt]
1000
3000
[Volt]
Figure 11: Results of PI control of nonminimum-phase system. Same variables are shown as in Figure 10. Note the ten times longer time scales.
18
[Volt]
generically harder to control than the minimum-phase process. The controller parameters (K1; Ti1) = (1:5; 110) and (K2; Ti2) = ( 0:12; 220) stabilize the process and give reasonable performance, see Figure 11. They give, however, much slower responses than in the minimum-phase case. Note the dierent time scales compared to Figure 10. The settling time is approximately ten times longer for the nonminimum-phase setting. (The control signal u2 seems to be noiseless in Figure 11, which is due to the low gain K2.) Note that the closed-loop performance will be better if y1 and y2 are permuted in the control structure in Figure 9, as was suggested by the RGA analysis in Section 3. Recall that e the RGA is given by = 0:64 for the original pairing and = 1:64 if the process outputs are permuted. The permutation, however, does not change the location of the right half-plane zero, and experiments have shown that the settling times are still much larger than for the minimum-phase setting [29]. Centralized multivariable control has also been tested on the Quadruple-Tank Process [12]. These experiments indicate that for the minimum-phase system it is not possible to achieve much faster response than with the decentralized PI controller in this section. For the nonminimum-phase case, however, a multivariable controller based on H1 design methods gave 30{40% faster settling time than the responses shown here. Note that this is still several times slower than the response time of the minimum-phase system. An interesting property of the H1 controller for the nonminimumphase system is that it happens to get an dominating anti-diagonal structure, contrary to the diagonal controller described in this section. This is intuitive and agrees also with the RGA analysis, which suggested a permutation of y1 and y2 . Multivariable controller-tuning method based on relay feedback experiments have also been investigated on the Quadruple-Tank Process [17, 29]. It was shown in [29] that several of the methods proposed in the literature cannot handle automatic control design for both the minimum-phase and the nonminimum-phase setting. The minimal achievable settling times for the step responses are important characteristics of the system. A lower bound on the settling time for multivariable control systems is derived in [16] by generalizing scalar results by Middleton [26]. It is shown that given a xed undershoot in y1 and a xed interaction to y2 , then, if the right half-plane zero is close to the origin, the step response will necessarily have a large settling time with any linear controller. The bound also takes the direction of the zero into account. Using the lower bound in [16], it is possible to show that the nonminimumphase system must have a settling time that is considerably larger than the minimum-phase response 19
shown in this paper. The minimum-phase setting of the Quadruple-Tank Process can theoretically be arbitrarily tight controlled with a decentralized controller [15].
7 Conclusions
A new multivariable laboratory process that consists of four interconnected water tanks has been described. A motivation for developing this process was to illustrate concepts in multivariable control or as stated in [21]:
[The control laboratory's] main purpose is to provide the connection between abstract control theory and the real world. Therefore it should give an indication of how control theory can be applied and also an indication of some of its limitations.
It was shown that the Quadruple-Tank Process is well suited to illustrate performance limitations in multivariable control design caused by right half-plane zeros. This followed from that the linearized model of the process has a multivariable zero that in a direct way is connected to the physical positions of two valves. The positions are given by two parameters 1; 2 2 (0; 1). It was shown that 1 + 2 determines the location of the zero, so that if 1 + 2 < 1 the system is nonminimum phase and if 1 + 2 > 1 the system is minimum phase. The quotient 1 = 2 gives the zero direction. Models from physical data and experimental data were derived and they were shown to have responses similar to the real process. Decentralized PI control showed that it was much more dicult to control the process in the nonminimum-phase setting than in the minimum-phase setting. The Quadruple-Tank Process is used today in several courses in the control education at LTH in Lund and at KTH in Stockholm. The experiments described in this paper have been performed using the PC interface shown in Figure 1 [28], which has been developed in the man-machine interface generator InTouch from Wonderware Corporation. The interface is connected to the real process as well as to a real-time kernel [2]. This gives a exible experimental platform where controllers can be designed in Matlab, loaded into the interface, simulated with the nonlinear model, and nally tested on the real process.
20
Acknowledgment
The experiments shown in this paper were done by Jos Luis Rocha Nunes [28], when he was visiting e the Department of Automatic Control at Lund Institute of Technology as an ERASMUS student. The laboratory process was built by Rolf Braun. Their work is gratefully acknowledged as well as comments from Karl Johan strm and Per Hagander on the manuscript. The project was supported A o by the Swedish Research Council for Engineering Science under contract 95{759.
References
[1] M. kesson, E. Gustafson, and K. H. Johansson. Control design for a helicopter lab process. In A IFAC'96, Preprints 13th World Congress of IFAC, San Francisco, CA, July 1996. [2] L. Andersson and A. Blomdell. A real-time programming environment and a real-time kernel. In Lars Asplund, editor, National Swedish Symposium on Real-Time Systems, Technical Report No 30 1991-06-21. Dept. of Computer Systems, Uppsala University, Uppsala, Sweden, 1991. [3] K. J. strm. Fundamental limitations of control system performance. In A. Paulraj, C. Schaper, A o and V. Roychowdhury, editors, Mathematical Engineering: A Kailath Festschrift. Kluwer Academic Publishers, 1996. [4] K. J. strm and M. Lundh. Lund control program combines theory with hands-on experience. A o IEEE Control Systems Magazine, 12(3):22{30, 1992. [5] K. J. strm and A.-B. Ostberg. A teaching laboratory for process control. IEEE Control A o Systems Magazine, 6:37{42, 1986. [6] H. W. Bode. Network Analysis and Feedback Amplier Design. Van Nostrand, New York, NY, 1945. [7] E. Bristol. On a new measure of interaction for multivariable process control. IEEE Transactions on Automatic Control, 11:133, 1966. [8] E. J. Davison. Description of multivariable apparatus for real time-control studies (MARTS). Technical Report 8514a, Dept. of Electrical Engineering, Univ. of Toronto, Canada, 1985. 21
[9] B. A. Francis. A Course in H1 Control Theory. Springer-Verlag, Berlin, Germany, 1987. [10] J. Freudenberg and D. Looze. Frequency Domain Properties of Scalar and Multivariable Feedback Systems. Springer-Verlag, Berlin, Germany, 1988. [11] G. C. Goodwin. Dening the performance envelope in industrial control. In 16th American Control Conference, Albuquerque, NM, 1997. Plenary Session I. [12] M. Grebeck. A comparison of controllers for the quadruple tank system. Technical report, Department of Automatic Control, Lund Institute of Technology, Lund, Sweden, 1998. [13] P. Grosdidier, M. Morari, and B. R. Holt. Closed-loop properties from steady-state gain information. Ind. Eng. Chem. Fundam., 24(2):221{235, 1985. [14] A. Isidori. Nonlinear Control Systems. Springer-Verlag, second edition, 1989. [15] K. H. Johansson. Relay feedback and multivariable control. PhD thesis, Department of Automatic Control, Lund Institute of Technology, Lund, Sweden, November 1997. [16] K. H. Johansson. Interaction bounds in multivariable control systems. In IFAC World Congress, Beijing, 1999. [17] K. H. Johansson, B. James, G. F. Bryant, and K. J. strm. Multivariable controller tuning. A o In 17th American Control Conference, Philadelphia, PA, 1998. [18] K. H. Johansson and J. L. R. Nunes. A multivariable laboratory process with an adjustable zero. In 17th American Control Conference, Philadelphia, PA, 1998. [19] K. H. Johansson and A. Rantzer. Multi-loop control of minimum phase processes. In Proc. 16th American Control Conference, Albuquerque, NM, 1997. [20] K. H. Johansson and A. Rantzer. Decentralized control of sequentially minimum phase systems. IEEE Transactions on Automatic Control, 2000. To appear. [21] N. A. Kheir, K. J. strm, D. Auslander, K. C. Cheok, G. F. Franklin, M. Masten, and M. RaA o bins. Control systems engineering education. Automatica, 32(2):147{166, 1996. [22] L. Ljung. System Identication Toolbox, Version 4.0.3. The Mathworks, Inc, 1997. 22
[23] L. Ljung. System Identication|Theory for the User. Prentice Hall, Upper Saddle River, N.J., 2nd edition edition, 1999. [24] M. Mansour and W. Schaufelberger. Software and laboratory experiment using computers in control education. IEEE Control Systems Magazine, 9(3):19{24, 1989. [25] T. J. McAvoy. Interaction Analysis: Principles and Applications. Instrument Society of America, Research Triangle Park, NC, 1983. [26] R. H. Middleton. Trade-os in linear control system design. Automatica, 27(2):281{292, 1991. [27] M. Morari and E. Zariou. Robust Process Control. Prentice-Hall, Englewood Clis, NJ, 1989. [28] J. R. Nunes. Modeling and control of the quadruple-tank process. Master thesis, Department of Automatic Control, Lund Institute of Technology, Lund, Sweden, 1997. [29] V. Recica. Automatic tuning of multivariable controllers. Master thesis, Department of Automatic Control, Lund Institute of Technology, Lund, Sweden, 1998. [30] M. M. Seron, J. H. Braslavsky, and G. C. Goodwin. Fundamental Limitations in Filtering and Control. Springer-Verlag, 1997. [31] F. G. Shinskey. Controlling Multivariable Processes. Instrument Society of America, Research Triangle Park, NC, 1981. [32] S. Skogestad and I. Postlethwaite. Multivariable Feedback Control|Analysis and Design. John Wiley & Sons, 1996. [33] G. Stein. Respect the unstable. In 30th IEEE Conference on Decision and Control, Honolulu, HI, 1990. [34] P. Van Overschee and B. De Moor. N4SID: Subspace algorithms for the identication of combined deterministic-stochastic systems. Automatica, 30(1):75{93, 1994. [35] D. Vischer and H. Bleuler. A new approach to sensorless and voltage controlled AMBs based on network theory concepts. In 2nd International Symposium on Magnetic Bearings, Institute of Industrial Sciencek, Tokyo University, 1990. 23
[36] G. Zames. Feedback and optimal sensitivity: Model reference transformations, multiplicative seminorms and approximate inverses. IEEE Transactions on Automatic Control, AC-26:301{ 320, 1981. [37] G. Zames and D. Bensoussan. Multivariable feedback, sensitivity, and decetralized control. IEEE Transactions on Automatic Control, 28(11):1030{1035, 1983. [38] G. Zames and B. A. Francis. Feedback, minimax sensitivity, and optimal robustness. IEEE Transactions on Automatic Control, 28(5):585{601, 1983.
24