C330D5
C330D5
C330D5
Diesel
generator set
QSL9 series
engine
230 kVA - 330 kVA 50 Hz
207 kWe - 300 kWe 60 Hz
Description
This Cummins® commercial generator set is a Cooling system - Standard integral set-
fully integrated power generation system, mounted radiator system, designed and tested
providing optimum performance, reliability, and for rated ambient temperatures, simplifies facility
versatility for stationary Standby and Prime design requirements for rejected heat.
Power.
Control system - The PowerCommand®
Features electronic control is standard equipment and
provides total system integration, including auto
Cummins heavy-duty engine - Rugged 4-cycle remote start/stop, alarm and status message
industrial diesel delivers reliable power, low display.
emissions and fast response to load changes.
Enclosures - Optional sound attenuated
Optional Permanent Magnet Generator enclosures.
(PMG) - Offers enhanced motor starting and
fault clearing short circuit capability. Warranty - Backed by a comprehensive
warranty and worldwide distributor network.
Alternator - Low reactance 2/3 pitch windings;
low waveform distortion with non-linear loads,
fault clearing short-circuits capability, and class
H insulation.
Emissions
Standby rating Prime rating compliance Data sheets
Genset Engine 50 Hz 60 Hz 50 Hz 60 Hz TA Luft/ EU
model model kVA (kWe) kWe (kVA) kVA (kWe) kWe (kVA) Stage/EPA 50 Hz 60 Hz
C275 D5 QSL9-G5 275 (220) 250 (200) 4g TA Luft DS22-CPGK
C300 D5 QSL9-G5 300 (240) 275 (220) 4g TA Luft DS23-CPGK
C330 D5 QSL9-G5 330 (264) 300 (240) 4g TA Luft DS24-CPGK
C250 D6 QSL9-G5 250 (313) 225 (282) DS69-CPGK
C275 D6 QSL9-G5 275 (344) 250 (313) DS70-CPGK
C300 D6 QSL9-G5 300 (375) 275 (344) DS71-CPGK
C250 D5e QSL9-G7 250 (200) 230 (184) EU SIII A EMERD-6136
C275 D5e QSL9-G7 275 (220) 250 (200) EU SIII A EMERD-6137
C300 D5e QSL9-G7 300 (240) 275 (220) EU SIII A EMERD-6138
C330 D5e QSL9-G7 330 (264) 300 (240) EU SIII A EMERD-6139
C230 D6e QSL9-G7 230 (288) 207 (259) EPA T3 EMERD-6140
C250 D6e QSL9-G7 250 (313) 225 (282) EPA T3 EMERD-6141
C275 D6e QSL9-G7 275 (344) 250 (313) EPA T3 EMERD-6142
C300 D6e QSL9-G7 300 (375) 275 (344) EPA T3 EMERD-6143
power.cummins.com
©2017 Cummins Inc. | SS9-CPGK-UKCA-UPDATE (02/22)
Generator set specifications
ISO8528 G3 for C300/330 D5/e, C275/300 D6/e
Governor regulation class
ISO8528 G2 for C250/275 D5/e, C230/250 D6/e
Voltage regulation, no load to full load ± 1%
Random voltage variation ± 1%
Frequency regulation Isochronous
Random frequency variation ± 0.5%
EMC compatibility BS EN61000-6-4 / BS EN61000-6-2
Engine specifications
Design 4 cycle, in-line, turbocharged, charge air-cooled
Bore 114 mm (4.5 in.)
Stroke 145 mm (5.7 in.)
Displacement 8.8 liter (543 in3)
Cylinder block Cast iron, 6 cylinder
Battery capacity 100 AH
Battery charging alternator 70 amps
Starting voltage 24 volt, negative ground
Fuel system Direct injection
Spin on fuel filters with water separator, StrataPore™ technology,
Fuel filter
extended life
Heavy duty, dry replaceable element, OptiAir™ technology, 2-stage air
Air cleaner type
filters
Lube oil filter type(s) Spin on full flow filter, StrataPore technology, extended life
122 °F (50 °C) ambient radiator for QSL9-G5 powered sets
Standard cooling system
105 °F (40 °C) ambient radiator for QSL9-G7 powered sets
Alternator specifications
Design Brushless, single bearing, revolving field
Stator 2/3 pitch
Rotor Single bearing, flexible disc
Insulation system Class H
Prime 125 ºC temp rise @ 40 ºC ambient
Standard temperature rise
Standby 163 ºC temp rise @ 27 ºC ambient
Exciter type Self excited or separately excited by PMG
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform Total Harmonic Distortion (THDV) No load <1.5%. Non distorting balanced linear load <5%
Telephone Influence Factor (TIF) < 50% per NEMA MG1-122.43
Telephone Harmonic Factor (THF) <2%
Available voltages
50 Hz Line-Neutral/Line-Line 60 Hz Line-Neutral/Line-Line
• 255/440 • 115/200 • 277/480 • 139/240
• 240/416 • 110/190 • 255/440 • 127/220
• 230/400 • 127/220 • 220/380* • 120/208
• 220/380 • 240/416 • 115/200
* Derate may be applicable at this voltage. Please consult the factory for details.
power.cummins.com
©2017 Cummins Inc. | SS9-CPGK-UKCA-UPDATE (02/22)
Generator set options (continued)
Control panel Warranty Silencer
• PowerCommand 3.3 – MLD • 10 years for major components • 25 dB(A) residential silencer for
• AC output bargraph • 5 years for Standby application open sets
• Shutdown audible alarm • 2 years for Prime application • 30/35 dB(A) critical silencer for open
• Earth fault shutdown sets
Battery charger
• Set mounted
• Standalone
*Note: Some options may not be available on all models - consult factory for availability.
power.cummins.com
©2017 Cummins Inc. | SS9-CPGK-UKCA-UPDATE (02/22)
Optional PowerCommand 3.3 control • Data logs – Includes engine run time, controller on time,
system number of start attempts, total kilowatt hours, and load
profile
• Fault history – Provides a record of the most recent fault
conditions with control date and time stamp for up to 32
events
• Real time clock for fault and event time stamping
• Exerciser clock and time of day start/stop initiate a test
with or without load, or a Base Load or Peak Shave
session
• Alternator data includes kW, kVar, power factor kVA
The PowerCommand 3.3 has the following additional
(three phase and total)
features and benefits over the PowerCommand 1.2. Refer
to document S-1570 for more detailed information on the Paralleling control functions
control. • First Start Sensor System selects first genset to close to
• AmpSentryTM – Includes integral AmpSentry protection, bus
which provides a full range of alternator protection • Phase Lock Loop Synchronizer with voltage matching
functions that are matched to the alternator provided. • Sync check relay
• Advanced voltage regulation – Three phase full wave • Isochronous kW and kVar load sharing
FET type regulator for stable operation with all load types. • Load govern control for utility paralleling
• Paralleling control function with isolated bus or utility. • Extended Paralleling (Base Load/Peak Shave) Mode
• Digital power transfer control – Provides load transfer Digital power transfer control, for use with a breaker pair to
operation in open transition, closed transition, or soft provide open transition, closed transition, ramping closed
ramping transfer modes. transition, peaking and base load functions.
Operator panel features
• 320 x 240 pixels graphic LED backlight LCD
• In addition to the 1.2 functions, the operator panel
displays paralleling breaker status and provides for direct
control of the paralleling breaker.
power.cummins.com
©2017 Cummins Inc. | SS9-CPGK-UKCA-UPDATE (02/22)
Emergency Standby Power (ESP):
Applicable for supplying power to varying electrical
load for the duration of power interruption of a reliable
utility source. Emergency Standby Power (ESP) is in
accordance with ISO 8528. Fuel Stop power in
accordance with ISO 3046, AS 2789, DIN 6271 and
BS 5514.
Limited-Time Running Power (LTP):
Applicable for supplying power to a constant electrical
load for limited hours. Limited Time Running Power
(LTP) is in accordance with ISO 8528.
Prime Power (PRP):
Applicable for supplying power to varying electrical
load for unlimited hours. Prime Power (PRP) is in
accordance with ISO 8528. Ten percent overload
capability is available in accordance with ISO 3046,
AS 2789, DIN 6271 and BS 5514.
Base Load (Continuous) Power (COP):
Applicable for supplying power continuously to a
constant electrical load for unlimited hours. Continuous
Power (COP) in accordance with ISO 8528, ISO 3046,
AS 2789, DIN 6271 and BS 5514.
This outline drawing is to provide representative configuration
details for Model series only.
* Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.
©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
SS9-CPGK-UKCA-UPDATE (02/22)
Generator set data sheet
Model: C330 D5
Frequency: 50 Hz
Fuel type: Diesel
Standby Prime
Fuel consumption kVA (kW) kVA (kW)
Ratings 330 (264) 300 (240)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
gph 4.4 7.9 12.1 16.5 3.7 6.8 10.1 13.8
L/hr 20.0 36.0 55.0 75.0 17.0 31.0 46.0 63.0
Fuel flow
Maximum fuel flow, L/hr 165
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature, °C 70
power.cummins.com
©2017 Cummins Inc. | DS24-CPGK (10/17)
Air Standby rating Prime rating
3
Combustion air, m /min 20.30 18.70
Maximum air cleaner restriction, kPa 6.2
Exhaust
3
Exhaust gas flow at set rated load, m /min 53.0 44.9
Exhaust gas temperature, °C 560 500
Maximum exhaust back pressure, kPa 10.2
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
power.cummins.com
©2017 Cummins Inc. | DS24-CPGK (10/17)
Alternator data
Connection Temp rise ºC Duty Alternator Voltage
Wye, 3-phase 163.125 S/P HC4D 380-415 V
Wye, 3-phase 125/105 S/P HC4E 380-440 V
Ratings definitions
Emergency Standby Limited-Time running Prime Power (PRP): Base load (Continuous)
Power (ESP): Power (LTP): Power (COP):
Applicable for supplying Applicable for supplying Applicable for supplying Applicable for supplying
power to varying electrical power to a constant power to varying electrical power continuously to a
load for the duration of electrical load for limited load for unlimited hours. constant electrical load for
power interruption of a hours. Limited-Time Prime Power (PRP) is in unlimited hours. Continuous
reliable utility source. Running Power (LTP) is in accordance with ISO 8528. Power (COP) is in
Emergency Standby Power accordance with ISO 8528. Ten percent overload accordance with ISO 8528,
(ESP) is in accordance with capability is available in ISO 3046, AS 2789,
ISO 8528. Fuel Stop power accordance with ISO 3046, DIN 6271 and BS 5514.
in accordance with AS 2789, DIN 6271 and
ISO 3046, AS 2789, DIN BS 5514.
6271 and BS 5514.
©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
DS24-CPGK (10/17)
HCI 434E/444E - Technical Data Sheet
HCI434E/444E
SPECIFICATIONS & OPTIONS
2
HCI434E/444E
WINDING 311
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
A.V.R. MX321 MX341
VOLTAGE REGULATION ± 0.5 % ± 1.0 % With 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)
3
HCI434E/444E
50 Winding 311
Hz THREE PHASE EFFICIENCY CURVES
4
HCI434E/444E
60 Winding 311
Hz THREE PHASE EFFICIENCY CURVES
5
HCI434E/444E
Winding 311
50
Hz
MX SX
346V 380V 400V 415V 440V 346V 380V 400V 415V 440V
30 30
25 25
20 20
P E R C E N T T R A N S IE N T V O L T A G E D IP .
P E R C E N T T R A N S IE N T V O L T A G E D IP .
15 15
10 10
5 5
0 0
0 200 400 600 800 1000 1200 0 100 200 300 400 500 600 700 800 900 1000
LOCKED ROTOR kVA LOCKED ROTOR kVA
60
Hz
MX SX
380V 416V 440V 460V 480V 380V 416V 440V 460V 480V
30 30
25 25
20 20
P E R C E N T T R A N S IE N T V O L T A G E D IP .
P E R C E N T T R A N S IE N T V O L T A G E D IP .
15 15
10 10
5 5
0 0
0 200 400 600 800 1000 1200 0 100 200 300 400 500 600 700 800 900 1000
LOCKED ROTOR kVA LOCKED ROTOR kVA
6
HCI434E
ASYMMETRICAL
CURRENT (Am ps)
1000
100
0.001 0.01 0.1 1 10
TIME (secs)
60 10000
Hz
SYMMETRICAL
ASYMMETRICAL
CURRE NT (Am ps)
1000
100
0.001 0.01 0.1 1 10
TIME (secs)
7
HCI434E/444E
Winding 311 / 0.8 Power Factor
RATINGS
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
Series Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
50 Parallel Star (V) 190 200 208 220 190 200 208 220 190 200 208 220 190 200 208 220
Hz Series Delta (V) 220 230 240 254 220 230 240 254 220 230 240 254 220 230 240 254
kVA 320 320 320 320 350 350 350 350 370 370 370 370 380 400 380 380
kW 256 256 256 256 280 280 280 280 296 296 296 296 304 320 304 304
Efficiency (%) 93.6 93.8 94.0 94.1 93.2 93.5 93.6 93.8 92.9 93.2 93.4 93.6 92.7 92.7 93.2 93.5
kW Input 274 273 272 272 300 299 299 299 319 318 317 316 328 345 326 325
Series Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480
60
Parallel Star (V) 208 220 230 240 208 220 230 240 208 220 230 240 208 220 230 240
Hz
Series Delta (V) 240 254 266 277 240 254 266 277 240 254 266 277 240 254 266 277
kVA 365 385 400 400 400 420 440 440 420 445 460 460 435 455 475 475
kW 292 308 320 320 320 336 352 352 336 356 368 368 348 364 380 380
Efficiency (%) 93.8 93.8 93.9 94.0 93.4 93.5 93.5 93.7 93.1 93.2 93.2 93.5 92.9 93.0 93.1 93.3
kW Input 311 328 341 340 343 359 376 376 361 382 395 394 375 391 408 407
DIMENSIONS