C330D5

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

Specification sheet

Diesel
generator set
QSL9 series
engine
230 kVA - 330 kVA 50 Hz
207 kWe - 300 kWe 60 Hz
Description
This Cummins® commercial generator set is a Cooling system - Standard integral set-
fully integrated power generation system, mounted radiator system, designed and tested
providing optimum performance, reliability, and for rated ambient temperatures, simplifies facility
versatility for stationary Standby and Prime design requirements for rejected heat.
Power.
Control system - The PowerCommand®
Features electronic control is standard equipment and
provides total system integration, including auto
Cummins heavy-duty engine - Rugged 4-cycle remote start/stop, alarm and status message
industrial diesel delivers reliable power, low display.
emissions and fast response to load changes.
Enclosures - Optional sound attenuated
Optional Permanent Magnet Generator enclosures.
(PMG) - Offers enhanced motor starting and
fault clearing short circuit capability. Warranty - Backed by a comprehensive
warranty and worldwide distributor network.
Alternator - Low reactance 2/3 pitch windings;
low waveform distortion with non-linear loads,
fault clearing short-circuits capability, and class
H insulation.

Emissions
Standby rating Prime rating compliance Data sheets
Genset Engine 50 Hz 60 Hz 50 Hz 60 Hz TA Luft/ EU
model model kVA (kWe) kWe (kVA) kVA (kWe) kWe (kVA) Stage/EPA 50 Hz 60 Hz
C275 D5 QSL9-G5 275 (220) 250 (200) 4g TA Luft DS22-CPGK
C300 D5 QSL9-G5 300 (240) 275 (220) 4g TA Luft DS23-CPGK
C330 D5 QSL9-G5 330 (264) 300 (240) 4g TA Luft DS24-CPGK
C250 D6 QSL9-G5 250 (313) 225 (282) DS69-CPGK
C275 D6 QSL9-G5 275 (344) 250 (313) DS70-CPGK
C300 D6 QSL9-G5 300 (375) 275 (344) DS71-CPGK
C250 D5e QSL9-G7 250 (200) 230 (184) EU SIII A EMERD-6136
C275 D5e QSL9-G7 275 (220) 250 (200) EU SIII A EMERD-6137
C300 D5e QSL9-G7 300 (240) 275 (220) EU SIII A EMERD-6138
C330 D5e QSL9-G7 330 (264) 300 (240) EU SIII A EMERD-6139
C230 D6e QSL9-G7 230 (288) 207 (259) EPA T3 EMERD-6140
C250 D6e QSL9-G7 250 (313) 225 (282) EPA T3 EMERD-6141
C275 D6e QSL9-G7 275 (344) 250 (313) EPA T3 EMERD-6142
C300 D6e QSL9-G7 300 (375) 275 (344) EPA T3 EMERD-6143

power.cummins.com
©2017 Cummins Inc. | SS9-CPGK-UKCA-UPDATE (02/22)
Generator set specifications
ISO8528 G3 for C300/330 D5/e, C275/300 D6/e
Governor regulation class
ISO8528 G2 for C250/275 D5/e, C230/250 D6/e
Voltage regulation, no load to full load ± 1%
Random voltage variation ± 1%
Frequency regulation Isochronous
Random frequency variation ± 0.5%
EMC compatibility BS EN61000-6-4 / BS EN61000-6-2

Engine specifications
Design 4 cycle, in-line, turbocharged, charge air-cooled
Bore 114 mm (4.5 in.)
Stroke 145 mm (5.7 in.)
Displacement 8.8 liter (543 in3)
Cylinder block Cast iron, 6 cylinder
Battery capacity 100 AH
Battery charging alternator 70 amps
Starting voltage 24 volt, negative ground
Fuel system Direct injection
Spin on fuel filters with water separator, StrataPore™ technology,
Fuel filter
extended life
Heavy duty, dry replaceable element, OptiAir™ technology, 2-stage air
Air cleaner type
filters
Lube oil filter type(s) Spin on full flow filter, StrataPore technology, extended life
122 °F (50 °C) ambient radiator for QSL9-G5 powered sets
Standard cooling system
105 °F (40 °C) ambient radiator for QSL9-G7 powered sets

Alternator specifications
Design Brushless, single bearing, revolving field
Stator 2/3 pitch
Rotor Single bearing, flexible disc
Insulation system Class H
Prime 125 ºC temp rise @ 40 ºC ambient
Standard temperature rise
Standby 163 ºC temp rise @ 27 ºC ambient
Exciter type Self excited or separately excited by PMG
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform Total Harmonic Distortion (THDV) No load <1.5%. Non distorting balanced linear load <5%
Telephone Influence Factor (TIF) < 50% per NEMA MG1-122.43
Telephone Harmonic Factor (THF) <2%

Available voltages
50 Hz Line-Neutral/Line-Line 60 Hz Line-Neutral/Line-Line
• 255/440 • 115/200 • 277/480 • 139/240
• 240/416 • 110/190 • 255/440 • 127/220
• 230/400 • 127/220 • 220/380* • 120/208
• 220/380 • 240/416 • 115/200
* Derate may be applicable at this voltage. Please consult the factory for details.

Generator set options


Engine • High alternator temp shutdown Fuel tank
• Water jacket heater 120 or 240 V • Low temp rise alternator • Low fuel level warning or shutdown
Circuit breaker • High fuel level warning
Enclosure • Extended fuel tank capacity: 691 /
• Sound attenuated canopy • 3 pole main circuit breaker std.
scope, 4 pole as an option 1200 liters
Alternator • Motorised 3 or 4 pole circuit breaker
• Alternator heater • Aux contacts and trip alarm
• Exciter voltage regulator (PMG) • Shunt trip – 24 V dc

power.cummins.com
©2017 Cummins Inc. | SS9-CPGK-UKCA-UPDATE (02/22)
Generator set options (continued)
Control panel Warranty Silencer
• PowerCommand 3.3 – MLD • 10 years for major components • 25 dB(A) residential silencer for
• AC output bargraph • 5 years for Standby application open sets
• Shutdown audible alarm • 2 years for Prime application • 30/35 dB(A) critical silencer for open
• Earth fault shutdown sets
Battery charger
• Set mounted
• Standalone

*Note: Some options may not be available on all models - consult factory for availability.

PowerCommand 1.2 control system • Lube oil pressure


• Coolant temperature
Other data
• Genset model data
• Start attempts, starts, running hours, kVA hours
• Fault history and control hours time stamp for up to 10
events
• Data logging and fault simulation (requires InPower).
The PowerCommand control system is an integrated Standard control functions
microprocessor based generator set control system Digital governing
providing voltage regulation, engine protection, alternator
protection, operator interface and isochronous governing. • Integrated digital electronic isochronous governor
Refer to document S-1567 for more detailed information on • Temperature dynamic governing
the control. • Configurable inputs: Control includes (4) input signals
Major features include from customer
• Power management – Control function provides battery Digital voltage regulation
monitoring and testing features and smart starting control • Integrated digital electronic voltage regulator
system. • Line to Line voltage sensing
• Digital voltage regulation – Single phase full wave SCR • Configurable torque matching
type regulator.
Engine protection
• Communications interface – Control comes standard with
PCCNet and Modbus interface. • Battery voltage monitoring and protection
• Regulation compliant – Prototype tested: CE, UKCA, UL, • Overspeed shutdown
and CSA compliant. • Low oil pressure warning and shutdown
• Service - InPower™ PC-based service tool available for • High/low coolant temperature warning or shutdown
detailed diagnostics, setup, data logging and fault • Low coolant level warning or shutdown
simulation. • Fail to start (overcrank) shutdown
• Easily upgradeable – PowerCommand controls are • Fail to crank shutdown
designed with common control interfaces.
• Cranking lockout
• Reliable design – The control system is designed for
reliable operation in harsh environment. • Sensor failure indication
• Low fuel level warning or shutdown (optional)
Operator panel features
• Fuel-in-rupture-basin warning or shutdown (optional)
• 128 x 128 pixels graphic LED backlight LCD • Full authority electronic engine protection
• Auto, manual, start, stop, fault reset and lamp test/panel • Battle short to allow some shutdown faults to be
lamp switches. bypassed
• Alpha-numeric display with pushbuttons. Control functions
• LED lamps indicating genset running, remote start, not in • Time delay start and cool down
auto, common shutdown, common warning, manual run
• Cycle cranking
mode, auto mode and stop mode.
• Configurable inputs (4) and outputs (2)
• Multiple language support.
Alternator data • Remote emergency stop
• Line-to-Neutral and Line-to-Line AC volts
• 3-phase AC current
• Frequency
• kVA (three phase and total)
Engine data
• DC voltage
• Engine speed

power.cummins.com
©2017 Cummins Inc. | SS9-CPGK-UKCA-UPDATE (02/22)
Optional PowerCommand 3.3 control • Data logs – Includes engine run time, controller on time,
system number of start attempts, total kilowatt hours, and load
profile
• Fault history – Provides a record of the most recent fault
conditions with control date and time stamp for up to 32
events
• Real time clock for fault and event time stamping
• Exerciser clock and time of day start/stop initiate a test
with or without load, or a Base Load or Peak Shave
session
• Alternator data includes kW, kVar, power factor kVA
The PowerCommand 3.3 has the following additional
(three phase and total)
features and benefits over the PowerCommand 1.2. Refer
to document S-1570 for more detailed information on the Paralleling control functions
control. • First Start Sensor System selects first genset to close to
• AmpSentryTM – Includes integral AmpSentry protection, bus
which provides a full range of alternator protection • Phase Lock Loop Synchronizer with voltage matching
functions that are matched to the alternator provided. • Sync check relay
• Advanced voltage regulation – Three phase full wave • Isochronous kW and kVar load sharing
FET type regulator for stable operation with all load types. • Load govern control for utility paralleling
• Paralleling control function with isolated bus or utility. • Extended Paralleling (Base Load/Peak Shave) Mode
• Digital power transfer control – Provides load transfer Digital power transfer control, for use with a breaker pair to
operation in open transition, closed transition, or soft provide open transition, closed transition, ramping closed
ramping transfer modes. transition, peaking and base load functions.
Operator panel features
• 320 x 240 pixels graphic LED backlight LCD
• In addition to the 1.2 functions, the operator panel
displays paralleling breaker status and provides for direct
control of the paralleling breaker.

power.cummins.com
©2017 Cummins Inc. | SS9-CPGK-UKCA-UPDATE (02/22)
Emergency Standby Power (ESP):
Applicable for supplying power to varying electrical
load for the duration of power interruption of a reliable
utility source. Emergency Standby Power (ESP) is in
accordance with ISO 8528. Fuel Stop power in
accordance with ISO 3046, AS 2789, DIN 6271 and
BS 5514.
Limited-Time Running Power (LTP):
Applicable for supplying power to a constant electrical
load for limited hours. Limited Time Running Power
(LTP) is in accordance with ISO 8528.
Prime Power (PRP):
Applicable for supplying power to varying electrical
load for unlimited hours. Prime Power (PRP) is in
accordance with ISO 8528. Ten percent overload
capability is available in accordance with ISO 3046,
AS 2789, DIN 6271 and BS 5514.
Base Load (Continuous) Power (COP):
Applicable for supplying power continuously to a
constant electrical load for unlimited hours. Continuous
Power (COP) in accordance with ISO 8528, ISO 3046,
AS 2789, DIN 6271 and BS 5514.
This outline drawing is to provide representative configuration
details for Model series only.

See respective model data sheet for specific model outline


drawing number.

Do not use for installation design

Open narrow skid


Length Width Height Weight* Weight*
Alternator (mm) (mm) (mm) (kg) (kg)
Models frame Dim “A” Dim “B” Dim “C” dry wet
C250 D5e, C230 D6e, C275 D5/e, C250 D6/e UCD274K 3135 1100 2018 2129 2181
C300 D5/e, C330 D5/e, C275 D6/e, C300 D6/e HC4D 3135 1100 2018 2352 2404

Enclosed wide skid


Length Width Height Weight* Weight*
Alternator (mm) (mm) (mm) (kg) (kg)
Models frame Dim “A” Dim “B” Dim “C” dry wet
C250 D5e, C230 D6e, C275 D5/e, C250 D6/e UCD274K 4259 1424 2349 4125 4177
C300 D5/e, C330 D5/e, C275 D6/e, C300 D6/e HC4D 4259 1424 2349 4348 4400

* Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.

Codes and standards


The CE marking is only valid when
This generator set is designed in
equipment is used in a fixed
facilities certified to ISO 9001 and
installation application. Material
manufactured in facilities certified to
compliance declaration is available
ISO 9001 or ISO 9002.
upon request.
The UKCA marking is only valid
All enclosed products are designed when equipment is used in a fixed
2000/14/EC to meet or exceed EU noise installation application. Material
legislation 2000/14/EC step 2006. compliance declaration is available
upon request.
This generator set has been
ISO 8528 designed to comply with ISO 8528
standards.
Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s electrical system
except through an approved device or after building main switch is open.
For more information contact your local Cummins
distributor or visit power.cummins.com

©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
SS9-CPGK-UKCA-UPDATE (02/22)
Generator set data sheet

Model: C330 D5
Frequency: 50 Hz
Fuel type: Diesel

Spec sheet: SS29-CPGK


Noise data sheet (open/enclosed): ND50OS/MSP-2023
Airflow data sheet: AF50-550

Standby Prime
Fuel consumption kVA (kW) kVA (kW)
Ratings 330 (264) 300 (240)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
gph 4.4 7.9 12.1 16.5 3.7 6.8 10.1 13.8
L/hr 20.0 36.0 55.0 75.0 17.0 31.0 46.0 63.0

Engine Standby rating Prime rating


Engine manufacturer Cummins
Engine model QSL9-G5
Configuration 4 cycle; in-line; 6 cylinder diesel
Aspiration Turbocharged and charge air-cooled
Gross engine power output, kWm 310 268
BMEP at set rated load, kPa 2785 2413
Bore, mm 114
Stroke, mm 145
Rated speed, rpm 1500
Piston speed, m/s 7.2
Compression ratio 16.8:1
Lube oil capacity, L 26.5
Overspeed limit, rpm 1800 ± 50
Regenerative power, kW 27
Governor type Electronic
Starting voltage 24 Volts DC

Fuel flow
Maximum fuel flow, L/hr 165
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature, °C 70

power.cummins.com
©2017 Cummins Inc. | DS24-CPGK (10/17)
Air Standby rating Prime rating
3
Combustion air, m /min 20.30 18.70
Maximum air cleaner restriction, kPa 6.2

Exhaust
3
Exhaust gas flow at set rated load, m /min 53.0 44.9
Exhaust gas temperature, °C 560 500
Maximum exhaust back pressure, kPa 10.2

Standard set-mounted radiator cooling


Ambient design, °C 50
Fan load, kW m 10
Coolant capacity (with radiator), L 15
3
Cooling system air flow, m /sec @ 12.7 mm H2O 7.93
Total heat rejection, Btu/min 10190 8415
Maximum cooling air flow static restriction, mm H2O 19.1

Weights* Open Enclosed


Unit dry weight, kgs 2346 4095
Unit wet weight, kgs 2570 4734
* Weights represent a set with standard features. See outline drawing for weights of other configurations.

Dimensions Length Width Height


Standard open set dimensions, mm 3135 1100 1928
Enclosed set standard dimensions, mm 4258 1424 2215

Genset outline
Open set

Enclosed set

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

power.cummins.com
©2017 Cummins Inc. | DS24-CPGK (10/17)
Alternator data
Connection Temp rise ºC Duty Alternator Voltage
Wye, 3-phase 163.125 S/P HC4D 380-415 V
Wye, 3-phase 125/105 S/P HC4E 380-440 V

Ratings definitions
Emergency Standby Limited-Time running Prime Power (PRP): Base load (Continuous)
Power (ESP): Power (LTP): Power (COP):
Applicable for supplying Applicable for supplying Applicable for supplying Applicable for supplying
power to varying electrical power to a constant power to varying electrical power continuously to a
load for the duration of electrical load for limited load for unlimited hours. constant electrical load for
power interruption of a hours. Limited-Time Prime Power (PRP) is in unlimited hours. Continuous
reliable utility source. Running Power (LTP) is in accordance with ISO 8528. Power (COP) is in
Emergency Standby Power accordance with ISO 8528. Ten percent overload accordance with ISO 8528,
(ESP) is in accordance with capability is available in ISO 3046, AS 2789,
ISO 8528. Fuel Stop power accordance with ISO 3046, DIN 6271 and BS 5514.
in accordance with AS 2789, DIN 6271 and
ISO 3046, AS 2789, DIN BS 5514.
6271 and BS 5514.

Formulas for calculating full load currents:

Three phase output Single phase output

kW x 1000 kW x SinglePhaseFactor x 1000


Voltage x 1.73 x 0.8 Voltage

For more information contact your local Cummins distributor


or visit power.cummins.com

©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
DS24-CPGK (10/17)
HCI 434E/444E - Technical Data Sheet
HCI434E/444E
SPECIFICATIONS & OPTIONS

STANDARDS WINDINGS & ELECTRICAL PERFORMANCE


Newage Stamford industrial generators meet the All generator stators are wound to 2/3 pitch. This
requirements of BS EN 60034 and the relevant section eliminates triplen (3rd, 9th, 15th …) harmonics on the
of other international standards such as BS5000, VDE voltage waveform and is found to be the optimum
0530, NEMA MG1-32, IEC34, CSA C22.2-100, AS1359. design for trouble-free supply of non-linear loads. The
Other standards and certifications can be considered on 2/3 pitch design avoids excessive neutral currents
request. sometimes seen with higher winding pitches, when in
parallel with the mains. A fully connected damper
VOLTAGE REGULATORS winding reduces oscillations during paralleling. This
winding, with the 2/3 pitch and carefully selected pole
AS440 AVR - STANDARD and tooth designs, ensures very low waveform
With this self-excited system the main stator provides distortion.
power via the Automatic Voltage Regulator (AVR) to the
exciter stator. The high efficiency semi-conductors of TERMINALS & TERMINAL BOX
the AVR ensure positive build-up from initial low levels Standard generators are 3-phase reconnectable with 12
of residual voltage. ends brought out to the terminals, which are mounted
The exciter rotor output is fed to the main rotor through on a cover at the non-drive end of the generator. A
a three-phase full-wave bridge rectifier. The rectifier is sheet steel terminal box contains the AVR and provides
protected by a surge suppressor against surges ample space for the customers' wiring and gland
caused, for example, by short circuit or out-of-phase arrangements. It has removable panels for easy
paralleling. access.
The AS440 will support a range of electronic
accessories, including a 'droop' Current Transformer SHAFT & KEYS
(CT) to permit parallel operation with other ac All generator rotors are dynamically balanced to better
generators. than BS6861:Part 1 Grade 2.5 for minimum vibration in
operation. Two bearing generators are balanced with a
MX341 AVR half key.
This sophisticated AVR is incorporated into the
Stamford Permanent Magnet Generator (PMG) control INSULATION/IMPREGNATION
system. The insulation system is class 'H'.
The PMG provides power via the AVR to the main All wound components are impregnated with materials
exciter, giving a source of constant excitation power and processes designed specifically to provide the high
independent of generator output. The main exciter build required for static windings and the high
output is then fed to the main rotor, through a full wave mechanical strength required for rotating components.
bridge, protected by a surge suppressor. The AVR has
in-built protection against sustained over-excitation, QUALITY ASSURANCE
caused by internal or external faults. This de-excites Generators are manufactured using production
the machine after a minimum of 5 seconds. procedures having a quality assurance level to BS EN
An engine relief load acceptance feature can enable full ISO 9001.
load to be applied to the generator in a single step.
If three-phase sensing is required with the PMG system The stated voltage regulation may not be maintained in
the MX321 AVR must be used. the presence of certain radio transmitted signals. Any
We recommend three-phase sensing for applications change in performance will fall within the limits of
with greatly unbalanced or highly non-linear loads. Criteria 'B' of EN 61000-6-2:2001. At no time will the
steady-state voltage regulation exceed 2%.
MX321 AVR
The most sophisticated of all our AVRs combines all the
features of the MX341 with, additionally, three-phase
rms sensing, for improved regulation and performance.
Over voltage protection is built-in and short circuit
current level adjustments is an optional facility. NB Continuous development of our products entitles us
to change specification details without notice, therefore
they must not be regarded as binding.

Front cover drawing typical of product range.

2
HCI434E/444E
WINDING 311
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
A.V.R. MX321 MX341
VOLTAGE REGULATION ± 0.5 % ± 1.0 % With 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)

CONTROL SYSTEM SELF EXCITED


A.V.R. AS440
VOLTAGE REGULATION ± 1.0 % With 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT WILL NOT SUSTAIN A SHORT CIRCUIT

INSULATION SYSTEM CLASS H


PROTECTION IP23
RATED POWER FACTOR 0.8
STATOR WINDING DOUBLE LAYER LAP
WINDING PITCH TWO THIRDS
WINDING LEADS 12
STATOR WDG. RESISTANCE 0.009 Ohms PER PHASE AT 22°C SERIES STAR CONNECTED
ROTOR WDG. RESISTANCE 1.19 Ohms at 22°C
EXCITER STATOR RESISTANCE 18 Ohms at 22°C
EXCITER ROTOR RESISTANCE 0.068 Ohms PER PHASE AT 22°C
R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
MAXIMUM OVERSPEED 2250 Rev/Min
BEARING DRIVE END BALL. 6317 (ISO)
BEARING NON-DRIVE END BALL. 6314 (ISO)
1 BEARING 2 BEARING
WEIGHT COMP. GENERATOR 1024 kg 1030 kg
WEIGHT WOUND STATOR 470 kg 470 kg
WEIGHT WOUND ROTOR 400 kg 377 kg
WR² INERTIA 4.6331 kgm2 4.4343 kgm2
SHIPPING WEIGHTS in a crate 1095 kg 1100 kg
PACKING CRATE SIZE 155 x 87 x 107(cm) 155 x 87 x 107(cm)
50 Hz 60 Hz
TELEPHONE INTERFERENCE THF<2% TIF<50
COOLING AIR 0.8 m³/sec 1700 cfm 0.99 m³/sec 2100 cfm
VOLTAGE SERIES STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
VOLTAGE PARALLEL STAR 190/110 200/115 208/120 220/127 208/120 220/127 230/133 240/138
VOLTAGE SERIES DELTA 220/110 230/115 240/120 254/127 240/120 254/127 266/133 277/138
kVA BASE RATING FOR
350 350 350 350 400 420 440 440
REACTANCE VALUES
Xd DIR. AXIS SYNCHRONOUS 3.01 2.71 2.52 2.24 3.47 3.26 3.12 2.87
X'd DIR. AXIS TRANSIENT 0.20 0.18 0.17 0.15 0.21 0.20 0.19 0.17
X''d DIR. AXIS SUBTRANSIENT 0.14 0.13 0.12 0.11 0.15 0.14 0.13 0.12
Xq QUAD. AXIS REACTANCE 2.58 2.33 2.16 1.92 2.92 2.74 2.63 2.41
X''q QUAD. AXIS SUBTRANSIENT 0.36 0.32 0.30 0.27 0.41 0.38 0.37 0.34
XL LEAKAGE REACTANCE 0.07 0.06 0.06 0.05 0.08 0.08 0.07 0.07
X2 NEGATIVE SEQUENCE 0.24 0.22 0.20 0.18 0.28 0.26 0.25 0.23
X0 ZERO SEQUENCE 0.10 0.09 0.08 0.07 0.10 0.09 0.09 0.08
REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.08s
T''d SUB-TRANSTIME CONST. 0.019s
T'do O.C. FIELD TIME CONST. 1.7s
Ta ARMATURE TIME CONST. 0.018s
SHORT CIRCUIT RATIO 1/Xd

3
HCI434E/444E
50 Winding 311
Hz THREE PHASE EFFICIENCY CURVES

4
HCI434E/444E
60 Winding 311
Hz THREE PHASE EFFICIENCY CURVES

5
HCI434E/444E
Winding 311

Locked Rotor Motor Starting Curve

50
Hz
MX SX
346V 380V 400V 415V 440V 346V 380V 400V 415V 440V
30 30

25 25

20 20

P E R C E N T T R A N S IE N T V O L T A G E D IP .
P E R C E N T T R A N S IE N T V O L T A G E D IP .

15 15

10 10

5 5

0 0
0 200 400 600 800 1000 1200 0 100 200 300 400 500 600 700 800 900 1000
LOCKED ROTOR kVA LOCKED ROTOR kVA

60
Hz
MX SX
380V 416V 440V 460V 480V 380V 416V 440V 460V 480V
30 30

25 25

20 20
P E R C E N T T R A N S IE N T V O L T A G E D IP .

P E R C E N T T R A N S IE N T V O L T A G E D IP .

15 15

10 10

5 5

0 0
0 200 400 600 800 1000 1200 0 100 200 300 400 500 600 700 800 900 1000
LOCKED ROTOR kVA LOCKED ROTOR kVA

6
HCI434E

Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed


Based on star (wye) connection.
50 10000
Hz
SYMMETRICAL

ASYMMETRICAL
CURRENT (Am ps)

1000

100
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 1,500 Amps

60 10000
Hz
SYMMETRICAL

ASYMMETRICAL
CURRE NT (Am ps)

1000

100
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 1,600 Amps


Note 1 Note 2
The following multiplication factors should be The following multiplication factor should be used to convert the
used to adjust the values from curve between values calculated in accordance with NOTE 1 to those applicable
time 0.001 seconds and the minimum current to the various types of short circuit :
point in respect of nominal operating voltage :
50Hz 60Hz 3-phase 2-phase L-L 1-phase L-N
Voltage Factor Voltage Factor Instantaneous x 1.00 x 0.87 x 1.30
380v X 1.00 416v X 1.00 Minimum x 1.00 x 1.80 x 3.20
400v X 1.05 440v X 1.06 Sustained x 1.00 x 1.50 x 2.50
415v X 1.10 460v X 1.10 Max. sustained duration 10 sec. 5 sec. 2 sec.
440v X 1.16 480v X 1.15 All other times are unchanged
The sustained current value is constant irrespective
of voltage level
Note 3
Curves are drawn for Star (Wye) connected machines. For other
connection the following multipliers should be applied to current
values as shown :

7
HCI434E/444E
Winding 311 / 0.8 Power Factor

RATINGS
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C

Series Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
50 Parallel Star (V) 190 200 208 220 190 200 208 220 190 200 208 220 190 200 208 220
Hz Series Delta (V) 220 230 240 254 220 230 240 254 220 230 240 254 220 230 240 254

kVA 320 320 320 320 350 350 350 350 370 370 370 370 380 400 380 380

kW 256 256 256 256 280 280 280 280 296 296 296 296 304 320 304 304

Efficiency (%) 93.6 93.8 94.0 94.1 93.2 93.5 93.6 93.8 92.9 93.2 93.4 93.6 92.7 92.7 93.2 93.5

kW Input 274 273 272 272 300 299 299 299 319 318 317 316 328 345 326 325

Series Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480
60
Parallel Star (V) 208 220 230 240 208 220 230 240 208 220 230 240 208 220 230 240
Hz
Series Delta (V) 240 254 266 277 240 254 266 277 240 254 266 277 240 254 266 277

kVA 365 385 400 400 400 420 440 440 420 445 460 460 435 455 475 475

kW 292 308 320 320 320 336 352 352 336 356 368 368 348 364 380 380

Efficiency (%) 93.8 93.8 93.9 94.0 93.4 93.5 93.5 93.7 93.1 93.2 93.2 93.5 92.9 93.0 93.1 93.3

kW Input 311 328 341 340 343 359 376 376 361 382 395 394 375 391 408 407

DIMENSIONS

Barnack Road • Stamford • Lincolnshire • PE9 2NB


Tel: 00 44 (0)1780 484000 • Fax: 00 44 (0)1780 484100

© 2006 TD_HCI4E.GB_10.06_04_GB