Data sheet F 4006 6X, 5X, 4X, Issue 1018

Dimensions in mm

min. 200 mm

control valve cone

H
valve seat

flow controller cone

h1
actuator casing

min. max.
Order Nr. Stroke min. dp
DN Flowrate Flowrate H h1 L
PN 16 [mm] [kPa]
@ 25% [m³/h] @ 100% [m³/h]
F 4006 62 50 15 3,75 15 40 295 210 230
F 4006 63 65 15 5,00 20 40 295 210 290
F 4006 64 80 20 9,00 36 40 332 230 310
F 4006 65 100 20 10,75 43 40 332 232 350
F 4006 66 125 40 25,00 100 40 520 410 400
F 4006 56 125 HF 40 37,50 150 70 480 480 400
F 4006 67 150 40 36,25 145 40 520 380 480
F 4006 57 150 HF 40 50,00 200 70 520 380 480
F 4006 68 200 40 52,5 210 40 558 560 600
F 4006 58 200 HF 40 75 300 70 558 560 600
F 4006 48 200 UHF 40 87,5 350 85 558 560 600

Technical data
Max. operating pressure 16 bar
Max. differential pressure 4 bar
Diff. pressure across the restrictor 0,2 bar
Min. operating temperature 2 °C (pure water)
Min. operating temperature - 20 °C (frost protection)
Max. operating temperature 110 °C
Valve characteristic linear
Type of connection Flanged (EN 1092-2)
Valve body material EN-GJL-250
Gasket material EPDM
Cones, stem, seat material CW617N-R320-S, WN1.4305, WN1.4305
Impulse tube WN1.4301
Diaphragm material EPDM
Water purity in accordance with the OENORM H 5195 and VDI 2035 standards.
Ethylene and propylene glycol can be mixed to a ratio of 25 - 50 vol. [%].

Page 1
HERZ - Compact Flanged PIBCV

Pursuant to Article 33 of the REACH Regulation (EC No. 1907/2006), we are obliged to point out that the material lead
is listed on the SVHC list and that all brass components manufactured in our products exceed 0.1% (w / w) lead (CAS:
7439-92-1 / EINECS: 231-100-4). Since lead is a component part of an alloy, actual exposure is not possible and
therefore no additional information on safe use is necessary.
Installation
Recommended installation: Install the valve in the return flow pipe of the system. Electric actuator should be placed in
upward position, at ± 45° angle to the vertical pipe axis.
Permissible installation: The valve should be installed in horizontal supply flow pipes of the system.
The valves must be installed for the correct application using clean fittings. A HERZ strainer (4111) should be fitted to
prevent impurities.
For installation, the local and international rules and standards have to be followed.

Flow adjustment
The adjustment of the flow rate is caried out by limiting the valve stroke. The set point for the valve flow limitation can be
adjusted by a flow meter or by using the flow charts.
The set point for the flow limitation can be adjusted by turning the adjustable nut.

Safety instructions and disposal


Prior to the assembly, maintenance and disassembly, the system must be depressurized, cooled down and emptied.
Only authorized, trained and qualified personnel may perform activities of assembly, start-up, operation and disassembly
of the equipment.
Before disposal the valve must be dismantled into groups of structural components and delivered to authorized waste
recycling organizations in order to preserve the environment. Local legislations must be obeyed when disposing of the
components.

Page 2
HERZ - Compact Flanged PIBCV

Actuator Selection
1 7712 29 1 7712 28 1 7712 31 1 7712 30 1 7712 31
Order 24 V; 0-10V, 230 V, 2-3 24 V; 0-10V, 230 V, 2-3 24 V; 0-10V,
number DN Hub [mm] 2-3 Pkt, 500 Pkt, 500 N, 2-3 Pkt, Pkt, 1000N, 2-3 Pkt,
N, 20mm 1000N, 20mm 2500N,
20mm 20mm 40mm
+ Adapter + Adapter
F 4006 61 40 11
1 7712 20 1 7712 20
+ Adapter + Adapter
F 4006 62 50 15
1 7712 20 1 7712 20
+ Adapter + Adapter
F 4006 63 65 15
1 7712 20 1 7712 20
+ Adapter + Adapter
F 4006 64 80 20
1 7712 17 1 7712 17
+ Adapter + Adapter
F 4006 65 100 20
1 7712 17 1 7712 17
Direct
F 4006 66 125 40
Mounting
Direct
F 4006 56 125 HF 40
Mounting
Direct
F 4006 67 150 40
Mounting
Direct
F 4006 57 150 HF 40
Mounting
Direct
F 4006 68 200 40
Mounting
Direct
F 4006 58 200 HF 40
Mounting
Direct
F 4006 48 200 UHF 40
Mounting

Please note: all diagrams are indicative in nature and do not claim to be complete.
All specifications and statements within this brochure are according to information available at the time of printing and meant for informational purpose only. Herz Armaturen reserves the right to modify and change products
as well as its technical specifications and/or it functioning according to technological progress and requirements. It is understood that all images of Herz products are symbolic representations and therefore may visually
differ from the actual product. Colours may differ due to printing technology used. In case of any further questions don’t hesitate to contact your closest HERZ Branch-office.

Page 3
HERZ - Compact Flanged PIBCV

HERZ standard diagram F 4006 6x


Order no.: F 4006 62 DN50
17

16

15 DN 50
14

13

12

11
flow rate [m³/h]

10

2
25% 30% 35% 40% 45% 50% 55% 60% 65% 70% 75% 80% 85% 90% 95% 100%
presetting

HERZ standard diagram F 4006 6x


Order no.: F 4006 63, 64 DN65 and DN80
40

38

36
DN 80
34

32

30

28

26
flow rate [m³/h]

24

22

20 DN 65
18

16

14

12

10

4
25% 30% 35% 40% 45% 50% 55% 60% 65% 70% 75% 80% 85% 90% 95% 100%
presetting

Page 4
HERZ - Compact Flanged PIBCV

HERZ standard diagram F 4006 6x


Order no.: F 4006 65, 66 DN100 and DN125
105

DN 125
95

85

75

65
flow rate [m³/h]

55

45
DN 100
35

25

15

5
25% 30% 35% 40% 45% 50% 55% 60% 65% 70% 75% 80% 85% 90% 95% 100%
presetting

HERZ standard diagram F 4006 6x


Order no.: F 4006 56 DN125 HF
160

150 DN 125 HF
140

130

120

110

100
flow rate [m³/h]

90

80

70

60

50

40

30

20
25% 30% 35% 40% 45% 50% 55% 60% 65% 70% 75% 80% 85% 90% 95% 100%
presetting

Page 5
HERZ - Compact Flanged PIBCV

HERZ standard diagram F 4006 6x


Order no.: F 4006 67 DN150
175

150

DN 150

125
flow rate [m³/h]

100

75

50

25
25% 30% 35% 40% 45% 50% 55% 60% 65% 70% 75% 80% 85% 90% 95% 100%
presetting

HERZ standard diagram F 4006 6x


Order no.: F 4006 57 DN150 HF
225

200 DN 150 HF

175

150
flow rate [m³/h]

125

100

75

50

25
25% 30% 35% 40% 45% 50% 55% 60% 65% 70% 75% 80% 85% 90% 95% 100%
presetting

Page 6
HERZ - Compact Flanged PIBCV

HERZ standard diagram F 4006 6x


Order no.: F 4006 68 DN200
225

200 DN 200

175

150
flow rate [m³/h]

125

100

75

50

25
25% 30% 35% 40% 45% 50% 55% 60% 65% 70% 75% 80% 85% 90% 95% 100%
presetting

HERZ standard diagram F 4006 6x


Order no.: F 4006 58 DN200 HF

335

310
DN 200 HF
285

260

235
flow rate [m³/h]

210

185

160

135

110

85

60

35
25% 30% 35% 40% 45% 50% 55% 60% 65% 70% 75% 80% 85% 90% 95% 100%
presetting

Page 7
HERZ - Compact Flanged PIBCV

HERZ standard diagram F 4006 6x


Order no.: F 4006 58 DN200 HF

385

360 DN 200 UHF


335

310

285

260
flow rate [m³/h]

235

210

185

160

135

110

85

60

35
25% 30% 35% 40% 45% 50% 55% 60% 65% 70% 75% 80% 85% 90% 95% 100%
presetting