Full Theses
Full Theses
Full Theses
K.P.N. Prasanna
(118624N)
University of Moratuwa
Sri Lanka
March 2016
COMPARATIVE STUDY ON SEISMIC ANALYSIS OF
BUILDINGS FOR DIFFERENT CODE OF PRACTICES
COMMONLY USED IN SRI LANKA
K.P.N. Prasanna
(118624N)
Thesis submitted in partial fulfillment of the requirements for the degree of Master of
Engineering in Structural Engineering Design
University of Moratuwa
Sri Lanka
March 2016
DECLARATION
I declare that this is my own work and this thesis does not incorporate without
acknowledgement any material previously submitted for a Degree or Diploma in any
other university or institute of higher learning and to the best of my knowledge and
believe it does not contain any material previously published or written by another
person except where the acknowledgement is made in the text.
Also I hereby grant the University of Moratuwa the non-exclusive right to reproduce
and distribute my thesis, in whole or in part, electronic or other medium. I retain the
right to use this content in whole or part in future works.
The above candidate has carried out this research for the Degree of Masters in
Engineering in Structural Engineering Designs under my supervision.
i
ACKNOWLEDGEMENT
There are many people, who have contributed in making this research and the
accompanying thesis a reality, to whom I am very grateful.
My special thanks go to Prof. M.T.R. Jayasinghe, the former head of the Department
of Civil Engineering of University of Moratuwa for making me interested in the field
of seismology.
I would also like to express my gratitude to all other members of the academic and
non-academic staff of the Department of Civil Engineering of University of
Moratuwa, for their support extended towards me in various means to finalize this
project successfully.
ii
ABSTRACT
Earthquake threat has been identified by many countries and analysis and design
against seismic effects have therefore become almost a basic part of their structural
design process. Sri Lanka has also identified the importance of designing buildings
against seismic actions, specially due to recent incidents, which took place in and
around the Island. However, Sri Lanka does not have its own code of practice for
designing against seismic actions. Also there are not many established guidelines
available in the country for this purpose. As a result, when it is required to analyze
and design buildings against seismic actions, the engineers and scientists in the
country face difficulties, basically with which codes and guidelines to follow. It is
obvious that all of those codes are not equally suitable for conditions in Sri Lanka
and also will not give out similar results.
The aim of this research is to check the performance level that a building can achieve
when analyzed according to different codes of practice, which are commonly used in
Sri Lanka in seismic analysis. In this context, three codes of practice were
considered, taking into account their applicability over the others in Sri Lankan
context, namely the Australian code (AS1170.4-2007), the Indian code (IS 1893
(Part 1):2002) and the Euro code (BS EN-1998-1:2004). The recommendations
provided in the research, conducted by the University of Moratuwa, Sri Lanka, aimed
at providing guidance on suitable analysis procedures for buildings in Sri Lanka,
based on the euro code were also inco-operated in the analysis.
First, the seismic analysis procedures outlined in those codes with respect to both
static and dynamic analysis were discussed in detail. Then, the analysis procedures
introduced in the respective codes of practice were compared and contrasted,
considering how they handle the major effects, characteristics of the structures and
geotechnical considerations etc.
According to the results obtained in the analysis, it has been found that, irrespective
of the code of practice, which has been used in the analysis, the structures have
achieved Immediate Occupancy Level (IOL)in all twenty seven cases, according to
FEMA356 standards. It was also found that the Indian code has given the highest
drift values in many occasions while the Euro code also has given very close or
sometimes similar drift values. In contrast, the Australian code has generally resulted
lowest drift values. Further, it has also been identified that the Euro code has given
the highest design base shear forces in all eighteen occasions. On the other hand, the
Indian code has given lowest design base shear force in many occasions. The
Australian code has also shown the lowest design base shear forces in few occasions.
iii
TABLE OF CONTENTS
2.3 Analysis procedure as described in Indian code [IS 1893 (Part 1) : 2002] ................. 34
2.4Comparison of analysis procedures as described in the Euro code, the Australian code
and the Indian code ............................................................................................................ 44
v
2.4.2 Structural regularity ............................................................................................. 45
vi
4.2.2.2.2 Calculating seismic base shear............................................................... 68
vii
5.1.2.2. Equivalent static analysis .............................................................................. 92
viii
5.3.2.1 Structural Model .......................................................................................... 116
6.1.2.3.4 Storey shear forces by modal response spectrum analysis method....... 134
ix
6.2.2 Method of analysis ............................................................................................. 140
6.2.2.3.4 Storey shear forces by modal response spectrum analysis method..... 146
6.3.2.3.4 Storey shear forces by modal response spectrum analysis method....... 157
x
7.2 Comparison based on higheststorey drift ratios ......................................................... 163
xi
LIST OF TABLES
Table EN-4 : Basic value of the behavior factor (q0) for systems 10
regular in elevation (EN 1998-1:2004/5.2.2.2
(Table 5.1))
xii
Table AS-7 : Value of Ks for structures not exceeding 15m 32
xiii
Table EA-10 : Parameters defining the criteria for damage 62
limitation requirement by modal response spectrum
analysis – Medium soil conditions
xiv
limitation requirement by modal response spectrum
analysis - Soft soil conditions
xv
method)
xvi
Table AA-7 : Torsional moments - Building A 98
Table AB-2 : Design seismic base shear of building B (T1 from 107
modal analysis)
Table AB-3 : Design seismic base shear of building B (T1 from eq. 107
6.2(7) of AS 1170.4-2007)
xvii
spectrum analysis method)
Table AB-9 : Design displacement (di) of the test building at each 111
storey level (Modal response spectrum analysis
method)
Table AC-2 : Design seismic base shear of building C (T1 from 119
modal analysis)
Table AC-3 : Design seismic base shear of building C (T1 from eq. 119
6.2(7) of AS 1170.4-2007)
Table AC-9 : Design displacement (di) of the test building at each 123
xviii
storey level (Modal response spectrum analysis
method)
Table IA-2 : Design seismic base shear by static lateral force 131
method - Building A
xix
limitation requirement by modal response spectrum
analysis – Building A
Table IB-2 : Design seismic base shear by static lateral force 143
method - Building B
xx
Table IC-2 : Design seismic base shear by static lateral force 154
method - Building C
Table 7.1.1 : Transient lateral drift at roof level of the three 162
structures
Table 7.1.2 : Code of practice for highest and lowest drift ratio at 162
roof level
Table 7.2.1 : Highest storey drift ratio at any storey level 163
Table 7.3.1 : Design base shear force of the three structures 165
xxi
Table 7.3.2 : Code of practice for highest and lowest design base 165
shear force
xxii
Table C1 : Material properties used in the analysis 202
xxiii
LIST OF FIGURES
xxiv
Figure B3 : Plan View – 2nd to 13th floor 188
xxv
1.0 INTRODUCTION
1.1 Background
It has now been realized that Sri Lanka can no longer be considered isolated from
seismic threat when the recent past events occurred in and around the island are
considered. Therefore, the higher authorities, scientists and engineers in the relevant
fields have taken the initiative to study the possible earthquakes in Sri Lanka and
their adverse effects [5].
Since, Sri Lanka is located at a reasonable distance from the Indo-Australian plate
boundary, it has not been facing a big threat against inter-plate type earthquakes.
Other than inter-plate earthquakes, that can happen at plate boundaries, intra-plate
earthquakes can also take place within the tectonic plates, causing significant
damages. Therefore, the scientists and engineers in the country have identified the
importance of designing structures against possible earthquakes, that can happen in
the future. However, in Sri Lanka, there is not much established guidelines available
for analysis and designing of buildings against seismic actions. The engineers and
scientists face difficulties basically with what code of practice to follow and how to
apply the other codes for Sri Lankan conditions.
One main nature of dynamic analysis is its high sensitivity to the characteristics of
ground motions selected and engineering assumptions made, which in turn are
dependent on the experience and judgment of the analyst. Studies in the past have
shown that distinctly different results could be obtained from analysis of the same
building conducted by different analysts. Therefore, dynamic analysis procedures
were regarded as unsafe, unless conducted by experienced and knowledgeable
engineers [7]. This reiterates the importance of explicit knowledge of the ground
condition of the location, validity of assumptions, availability of seismic data
particular to the location etc, when dealing with dynamic analysis.
1
Since there is no own code of practice for seismic analysis, the engineers of Sri
Lanka have to use one of available codes among many. But, it is clear that each of
these codes are not equally convenient and suitable to be applied in Sri Lankan
conditions and would not give same results after analysis. These codes are prepared
to suit with their geotechnical conditions, environment and structures. Therefore it is
very important and useful to make a detail discussion and study through these codes
to check the applicability of these codes for Sri Lankan conditions and to check
results through some analysis.
1.3 Objevtives
The main objectives of this research can be pointed out as,
* To discuss and compare the seismic analysis procedures described in the Australian
code (AS1170.4-2007), the Indian code (IS 1893 (Part 1):2002) and the Euro code
(EN 1998-1:2004).
* To demonstrate through case studies how to apply the static and dynamic seismic
analysis procedures described in selected codes to analyse buildings in Sri Lanka
under different geotechnical considerations.
* To compare the performance level that can be achieved through analysis against
three of these codes separately.
2
1.4 Methodology
Firstly, three main seismic analysis codes that are often used by Sri Lankan engineers
were identified, namely the Euro code, EC-8 (EN 1998-1:2004), the Australian code
(AS 1170.4-2007) and the Indian code (IS 1893 (Part 1):2002). In literature review
section, the analysis procedures that have been established in each of those codes
were then outlined in step by step.
In order the results to be more fair and general, the analysis were repeated for
different geotechnical conditions, that can be commonly found in Sri Lanka.
Finally, the structural performance level, that has been reached, when analysed
according to different codes of practice were found and compared.
The methodology adopted in this study has been described in detail in Chapter 3.
At latter part of the chapter, it also compare and contrast the analysis procedure
described in each code of practice, how they have defined different parameters and
how they have considered different structural effects etc.
It describes how the three codes of practice were selected for analysis.
3
It also explains the selection of buildings for analysis.
It further describes the soil categories that the analysis to be based on for Sri Lankan
conditions
It also describes in detail the procedure adopted to obtain seismic response quantities
dynamically by Response Spectrum Analysis (RSA).
It further demonstrate the established method to check the structure against damage
limitation requirements and against allowable inter-storey drift coefficient.
It further demonstrates the established method to check the structure against damage
limitation requirements and against allowable inter-storey drift coefficient.
4
It explains basic characteristics of ETABS computer models, developed to fulfill the
requirements established in the code, the procedures described with respect to static
and dynamic(RSA) analysis to obtain response quantities and its vertical distribution
etc.
It further demonstrates the established method to check the structure against damage
limitation requirements.
5
2.0 LITERATURE REVIEW
Analysis of structures for seismic effects has now become almost a basic part of the
structural design procedures almost all over the world. To achieve this purpose, some
countries have developed their own codes of practice and they therefore analyse and
design the structures accordingly. However, for countries those who do not have
their own codes of practice have to depend upon some other codes of practice which
can be used for their purposes with appropriate adjustments.
Sri Lanka also does not have its own code of practice for seismic analysis. This
chapter presents a detail analysis and discussion made on three codes of practice,
which are commonly used in seismic analysis in Sri Lanka, namely the Euro code
(EN 1998-1:2004) with national guidelines developed for seismic analysis of
buildings in Sri Lanka by Disaster Management Centre (DMC), Sri Lanka, the
Australian code (AS 1170.4-2007) and the Indian code (IS 1893 (Part 1):2002.
Firstly the analysis procedures established in all three codes were out lined in brief,
highlighting how those codes are used in analysis process in Sri Lanka. Then those
three codes of practice were compared and contrasted under different criteria
considering how those codes have defined different parameters and how they have
proposed values for them etc, which is very important to find out the advantages and
disadvantages of adopting one code over the other.
6
Table EN-1: Classification of buildings into important classes
Buildings of low-moderate Car parking buildings, Shopping centres less than 10,000m 2 gross
II importance for safety of public area , Public assembly buildings for fewer than 100 persons
and other properties Emergency medical and other emergency facilities not designated as
post-disaster, Airport terminals, principal railway stations
The structures shall be classified into four categories (Table EN-1). The importance
class I includes the structures which does not require an explicit seismic
consideration in the design process. The importance class II, III and IV include the
structures identified as important during an earthquake event considering their
function, the consequences of failure and the economic aspects. Therefore,
importance class II, III and IV buildings shall be designed for seismic actions having
475, 1500 and 2500 year return periods respectively [5].
The design peak ground acceleration value for each category of buildings shall be
then calculated as
Where,
: Design peak ground acceleration
7
: Importance factor (Refer Table EN-2)
: Peak ground acceleration for 475 years return period seismic action
(Refer Table EN-2: Note)
Importance Class
I --
II 1
III 1.5
IV 1.8
Note: For Sri Lanka, the (reference) peak ground acceleration for475 year
return period shall be taken as 0.1g and is assumed same for the whole
country [5].
1893 (Part 1): 2002 to be used in the seismic analysis according to Euro code for
Where
: elastic response spectra
T : vibration period of a linear single-degree-of-freedom system
: lower limit of the period of the constant spectral acceleration branch
: upper limit of the period of the constant spectral acceleration branch
S : soil factor
The horizontal elastic response spectra are given for three types of soil classified
based on the Standard Penetration Test value (NSPT) [5]. Refer table EN-3 for the soil
classification and the corresponding parameters defining the elastic response spectra.
8
Table EN-3 :Soil classification and parameters defining horizontal elastic
response spectra
I
>30 1 0.1 0.4
(Hard soil)
II
10-30 1.36 0.1 0.55
(Medium soil)
III
<10 1.67 0.1 0.67
(Soft soil)
The design response spectrum for the seismic analysis of buildings shall be obtained
by reducing the elastic response spectra by the value of behavior factor (q) as
recommended in EC 8 and are given in the specific sections of the code. The design
response spectra shall be then given as
Where
: design horizontal response spectrum
q : behavior factor
T, TB, TC, S: as defined in Section 2.1.2 above
In selecting the behavior factors, the buildings of importance class II, III and IV shall
be considered as ductility class medium (DCM) or high (DCH).
The behavior factor (q) used in the reinforced concrete structures as given in EN
1998-1/5.2.2.2 is given by
≥1.5
Where
9
q: behavior factor
: basic value of the behavior factor (Refer Table EN-4)
: factor reflecting the prevailing failure mode in structural systems with
walls (Refer Table EN-5)
Table EN-4 :Basic value of the behavior factor (q0) for systems regular in
elevation (EN 1998-1:2004/5.2.2.2 (Table 5.1))
α1: the value by which the horizontal seismic design action is multiplied in order to
first reach the flexural resistance in any member in the structure, while all other
design actions remain constant
αu: the value by which the horizontal seismic design action is multiplied, in order to
form plastic hinges in a number of sections sufficient for the development of
overall structural instability, while all other design actions remain constant (This
value may be obtained from a nonlinear static (pushover) global analysis)
10
Table EN-5 : Factor kw reflecting the prevailing failure mode(EN 1998-
1:2004/5.2.2.2 (11)P)
Structural Type1 kw
Frame and frame-equivalent dual systems 1.00
∑ ∑
Where
: height of the wall i
: length of the section of wall i
11
It is recommended to use the vertical elastic response spectrum recommended in IS
1893-1:2002, where 2/3 of horizontal elastic response spectrum as vertical elastic
response spectra [5].
∑ ∑
Where
: permanent load
: variable load
(EN 1998-1: 4.2.4)
: factor representing the quasi permanent value of the variable action
(EN 1990:2002 - Table EN-7)
φ : (EN 1998-1: Table 4.2- Refer Table EN-9)
∑ ∑
Where,
G : permanent actions (self-weight and other dead loads)
A : design seismic action
Q : variable actions (live loads)
: factor representing the quasi permanent value of the variable action
(EN 1990:2002 - Table EN-7)
12
Table EN-7 : Recommended values of ψ factors in EN 1990/Table A1.1
13
Table EN-9 : Values of φ factors
Y-direction;
For definitions of the centre of stiffness and of the torsional radius in multi storey
buildings refer "Manual for the seismic design of steel and concrete buildings to
Euro Code 8".
A building must satisfy all the requirements given in Clause 4.2.3.3 of EN 1998-
1:2004 to be classified as regular in elevation. The requirements are briefed here as
follows.
14
o All the vertical load resisting elements shall continue uninterrupted from
foundation level to the top of the building or where set backs are present to
the top of the setback.
o Mass and stiffness shall either remain constant with height or reduce only
gradually without abrupt changes.
o In buildings with moment-resisting frames, the lateral resistance of each
storey (i.e. the seismic shear initiating failure within that storey, for the code-
specified distribution of seismic loads) shall not vary „disproportionately‟
between storeys.
o Buildings with setbacks (i.e. where the plan area suddenly reduces between
successive storeys) are generally irregular, but may be classified as regular if
additional condition defined in the EC 8 are satisfied.
a) The use of above two methods of analysis shall be decided based on the
structural characteristics of the building.
b) For the consequences of structural regularity on the structural analysis method
refer Table EN-10 (EN 1998-1:2004/ Table 4.1)
c) The criteria given in EN 1998-1: 2004/ 4.3.1 shall be considered in the structural
model used in the analysis
15
2.1.5.4.1 Static lateral force method of analysis
a) The static lateral force method of analysis is used for buildings only which
satisfy the requirements given in EN 1998-1:2004/4.3.3.2.1 (2).
b) The total seismic base shear of the building shall be determined by the following
expression (See EN 1998-1:2004/eq.4.5).
Where
Sd(T1): the spectral acceleration obtained from the design response spectrum
for the fundamental period of vibration T1.
m: the seismic mass of the building (Refer Clause 3.2.4 of EN 1998-
1:2004)
λ: correction factor as given in EN 1998-1:2004/ 4.3.3.2.2
T1: fundamental period of vibration of the building as given in EN 1998-
1:2004/4.3.3.2.1 (2), (3), (4) & (5).
c) The total horizontal load shall then be distributed over the height of the building.
Normally the distribution of lateral loads shall be done by making simple
assumption on the mode shape, that is, for regular buildings, the mode shape is a
straight line of which the displacement is directly proportional to the height
(fundamental mode of vibration). With this assumption, the force at storey level
Fk shall be determined as (EN 1998-1:2004/eq.4.10)
Where zi and zj represent the heights of the masses mi, mj above the level of
application of the seismic action.
16
b) The response of all modes of vibration contribution significantly to the global
response shall be considered. The code specifies that, this requirement is taken to
be satisfied if
- The sum of the effective modal masses for modes taken into analysis
amounts to 90% of the total mass of the structure
- All modes with effective modal masses greater than 5% of the total mass
are taken
c) Combination of modal responses is an important step in the modal response
spectrum analysis. EN 1998-1:2004/4.3.3.3.2 recommends the “Complete
Quadratic Combination” (CQC) rule as an accurate procedure for this. The
results of the modal analysis in each direction are then combined by the
recommended methods as described in EN 1998-1:2004/4.3.3.5.1.
d) EC 8 recommends the accidental torsional effects to be taken into account in the
seismic analysis whenever a spatial model is used.
eai = ±0.05. Li
where
eai is the accidental eccentricity of storey mass i from its nominal location,
applied in the same direction at all floors;
17
2.1.5.6. Displacements and drift
2.1.5.6.1 Displacement
As described in EN 1998-1:2004/4.3.4, in the case of a linear analysis the
displacement of a point of the structural system induced by the design seismic action
is calculated by the product of displacement behavior factor and the displacement of
the same point of the structural system as determined from the linear analysis.
Where, reduction factor accounts for the lower return period to be considered in
damage limitation requirement and it is 0.4 for the buildings of importance class III
and IV and 0.5 for buildings of important class I and II (Clause 4.4.3.2 (2) of EN
1998-1:2001). The value of has three different figures, 0.005, 0.0075 and 0.01
depending on the type of non-structural elements in the building. The„h‟ is the height
of the storey.
Where is inter-storey drift, h is the storey height, is the total seismic storey
shear and is the total gravity load at and above the storey considered in the
seismic design situation.
18
For the values of inter-storey drift sensitivity coefficient between 0.1 and 0.2, the
code advices to multiply the seismic action effects obtained from the analysis by a
factor equal to 1/(1-θ). However, the inter-storey drift sensitivity coefficient shall not
exceed 0.3.
For ultimate limit states for structures of importance levels 1 to 4, the annual
probability of exceedance (P) for wind, snow and earthquake loads shall be
determined as,
P = Pref X (50/N)
where,
19
Table AS-2 :Classification of buildings into important classes
Importance
Comment Examples
level
Structures presenting a low Farm buildings, isolated structures, towers in rural situations
1 degree of hazard to life and Fences, masts, walls, in-ground swimming pools
other property
Hotels, offices, apartments less than 15 storeys high
Structures with special post- Ancillary installations necessary for the operation of importance
4 level 4 structures (emergency power, phone, radio, etc.)
disaster functions
Special structures Structures that have special functions or whose failure poses
(outside the scope of this catastrophic risk to a large area(e.g. 100 km2) ora large number
5 Standard-acceptable of people (e.g. 100 000)
probability of failure to be Dams, extreme hazard facilities
determined by special study)
20
The structures shall be classified into five important classes (Table AS-2). The
importance class 1 includes the structures, which does not require an explicit seismic
consideration in the design process and also the domestic structures that comply with
the definition given in appendix A and with the provisions of appendix A of the code
are deemed to satisfy the standard. All other structures identified as important during
an earthquake event considering their function, the consequences of failure and the
economic aspects. Therefore, importance class 2, 3 and 4structures shall be designed
for seismic actions having 500, 1000 and 2500 years return periods respectively.
Where,
kp : Probability factor (Refer Table AS-4)
21
: Hazard factor (Table 3.2 of AS 1170.4 provides different values for
"z" based on the location in Australia. However this can be taken as 0.1
for Sri Lanka)
Sub-soil classes have been defined in Clause 4.1.1 of AS 1170.4-2007 as,
However, in this analysis, only three soil conditions were considered Be, Ce and Ee to
represent Sri Lankan conditions, loose soil, medium soil and hard soil.
1/2500 1.8
1/2000 1.7
1/1500 1.5
1/1000 1.3
1/800 1.25
1/500 1.0
1/250 0.75
1/200 0.7
1/100 0.5
1/50 0.35
1/25 0.25
1/20 0.20
22
Table AS-5 : Equations for spectra
It has been proposed to use recommendations provided in the Indian code, IS 1893
(Part 1):2002 for defining the vertical elastic spectra, which has been defined as 2/3
of the horizontal elastic spectra [5].
Wi = ∑ ∑
Where
Gi and Qi are summed between the mid-heights of adjacent storeys
= permanent action (self-weight or "dead load) at level i
= earthquake-imposed action combination factor
23
0.6 for storage applications
0.3 for all other applications
Ed =[G, Eu, ]
Where,
G : permanent actions (self-weight or"dead" action)
Eu :ultimate earthquake action
: combination factor for imposed action
Q : imposed action
(h) Apply the forces to the structure at the eccentricities specified in Clause 6.6 of
AS 1170.4-2007.
(i) Take P-delta effects into account as specified in Clause 6.7 of AS 1170.4-2007.
The set of equivalent static forces in the direction being considered shall be assumed
to act simultaneously at each level of the structure and shall be applied taking into
account the torsion effects as given in combination with other actions as specified in
AS/NZS 1170.0. (Refer Clause 6.2.1 of AS 1170.4-2007)
The horizontal equivalent static shear force (V) acting at the base of the structure
(base shear) in the direction being considered shall be calculated from the following
equations
Where
Cd(T1)=horizontal design action coefficient (value of the horizontal design
response spectrum at the fundamental natural period of the structure)
=C(T1)Sp/µ (Refer AS 1170.4-2007/eq 6.2(4) )
25
Sp = Structural performance factor, as given in Clause 6.5 of AS 1170.4-
2007.
µ = Structural ductility factor, as given in Clause 6.5 of AS 1170.4-2007.
T1 = Fundamental natural period of the structure, as given in Clause 6.2.3 of
AS 1170.4-2007 as,
T1 = 1.25kthn0.75
where,
kt = 0.11 for moment-resisting steel frames
=0.075 for moment-resisting concrete frames
= 0.06 for eccentrically-braced steel frames
= 0.05 for all other structures
hn =height from the base of the structure to the uppermost seismic
weight or mass, in meters.
It should be noted that the base shear obtained using the fundamental structure period
(T1) determined by a rigorous structural analysis shall be not less than 80% of the
The horizontal equivalent static design force (Fi) at each level (i) shall be obtained as
(AS 1170.4-2007/eq. 6.3(1))
Where
26
k=exponent depend on the fundamental period of the structure (T1), which is
taken as-
1.0 when T1≤0.5;
2.0 when T1≥2.5; or
linearly interpolated between 1.0 and 2.0 for 0.5< T1<2.5
n=number of levels in a structure
The horizontal equivalent static earthquake shear force(Vi) at storey i is the sum of all
the horizontal forces at and above the ith level (Fi to Fn).
Table AS- 6 :Structural ductility factor (µ) and structural performance factor
(Sp) - Basic structures
27
*The design of structures with µ>3 is outside the scope of this standard (Refer clause
2.2)
di = dieµ/Sp
Where,
die : deflection at the ith level determined by an elastic analysis carried
out using the horizontal equivalent static earthquake forces (Fi).
(b) For θ>0.2, the structure is potentially unstable and shall be re-designed.
(c) For 0.1<θ≤0.2, P-delta effects shall be calculated as described in Clause 6.7.3.2
of AS1170.4-2007.
28
∑ ( ∑ )
Where,
i = Level of the structure under consideration.
hsi= Inter-storey height of level i, measured from centre-line to centre-line of
the floors.
.
When P-delta effects need to be considered, the values of the horizontal earthquake
shear forces and moments, the resulting member forces and moments, and the storey
drifts shall be determined by,
(a) scaling the equivalent static forces and deflections by the factor (0.9/(1-θ))≥1.0
or.
Cd(T) = C(T)Sp/µ
= KpZCh(T)Sp/µ
Where,
b) Site specific design response spectra developed for the specific site as described
in Clause 7.2(b) of AS 1170.4-2007.
29
c) Where design includes consideration of vertical earthquake actions, both upwards
and downwards directions shall be considered and the vertical design response
spectrum shall be as follows (Refer Clause 7.2(3) of AS 1170.4-2007)
Cvd(T) = Cv(Tv)Sp
= 0.5C(Tv)Sp
= 0.5KpZCh(Tv)Sp
Where,
Cv(Tv) = elastic site hazard spectrum for vertical loading for the vertical
period of vibration
30
2.2.4.4 Earthquake design categories
Once the importance level, kp, Z, soil category and building height is known, the
earthquake design category of the structure can be found referring to table AS-3.
Fi = 0.1Wi
Where,
31
c) Forces shall be applied at the centre of mass of each floor except where offset
from the centre of mass is required for the consideration of torsion effects.
d) Earthquake forces shall be calculated using the equivalent static method for
structures exceeding 15m.
e) For structures not exceeding 15m, the earthquake forces shall be calculated and
applied according to Clause 5.4.2.3 of AS 1170.4-2007 and the minimum
horizontal static force to be applied simultaneously at each level for the given
direction is given by,
Fi = Ks[KpZSp/µ]Wi
Where,
Kp and Z are given in section 3 and Sp and µ are given in Clause 6.5 of AS
1170.4-2007
32
a) Alternatively, dynamic analysis shall be used to find out design earthquake
actions according to Section 7 of AS 1170.4-2007.
b) Vertical earthquake actions need not be considered. For parts and components
refer Clause 5.4.6 and 8.1.3 of AS 1170.4-2007.
c) The inter-storey drift at the ultimate limit state shall not exceed1.5% of the storey
height of each level (Refer Clause 5.4.4 of AS 1170.4-2007).
c) Earthquake forces shall be calculated using the dynamic analysis method given in
Section 7 of AS 1170.4-2007.
d) Vertical earthquake actions need not be considered. For parts and components,
refer Clause 8.1.3 of AS 1170.4-2007.
e) The inter-storey drift at the ultimate limit state shall not exceed1.5% of the storey
height of each level (Refer Clause 5.5.4 of AS 1170.4-2007).
33
2.3 Analysis procedure as described in Indian code [IS 1893 (Part 1)
: 2002]
The design approach adopted in this standard is to ensure that structures possess at
least a minimum strength to withstand minor earthquakes (<Design Based
Earthquake, DBE), which occurs frequently, without damages; resist moderate
earthquakes (DBE) without significant structural damage though some non-structural
damage may occur; and aims that structures withstand a major earthquake
(Maximum Considered Earthquake, MCE) without collapse.
Where
: 5 percent spectra
The horizontal elastic response spectra are given for three types of soil classified
based on the Standard Penetration Test value (NSPT). For the soil classification and
the corresponding parameters defining the elastic response spectra see Table 3.
34
Table IS-1: Soil classification and parameters defining horizontal elastic
response spectra
III soil)
(Medium <10 1.67 0.1 0.67
(Soft soil)
The design acceleration spectrum vertical motions, when require, may be taken as
two-thirds of the design horizontal acceleration spectrum (See Clause 6.4.5 of IS
1893 (Part 1) : 2002).
Ah=
Where
Z : Zone factor given in table 2 of IS 1893 (Part 1) : 2002, is for the
Maximum considered Earthquake(MCE) and service life of structure
in a zone. The factor 2 in the denominator of Z is used so as to reduce
the maximum Considered Earthquake (MCE) zone factor to the
factor for Design Basis Earthquake (DBE).
35
hazardous consequences of its failure, post-earthquake functional
needs, historical value, or economic importance.
II III IV V
Seismic Zone
Seismic Intensity Low Moderate Severe Very Severe
Z 0.10 0.16 0.24 0.36
Notes:
1. The design engineer may choose values of importance factor I greater than
those mentioned above.
2. Buildings not covered in SI No. (i) and (ii) above may be designed for
higher value of I, depending on economy, strategy considerations like
multi-storey buildings having several residential units.
3. This does not apply to temporary structures.
36
Table IS-4 : Response reduction factor1), R (Table 7 of IS 1893 (Part 1) :
2002)
SI No. Lateral load resisting system R
Building Frame Systems
i) Ordinary RC moment-resisting frame (OMRF)2) 3.0
ii) Special RC moment-resisting frame (SMRF)3) 5.0
iii) Steel frame with
a) Concentric braces 4.0
b) Eccentric braces 5.0
iv) Steel moment-resisting frame designed as per SP 6 (6) 5.0
4)
Building with Shear Walls
v) Load bearing masonry wall buildings5)
a) Unreinforced 1.5
b) Reinforced with horizontal RC bands 2.5
c) Reinforced with horizontal RC bands and vertical bars at 3.0
corners of rooms and jambs of openings.
vi) Ordinary reinforced concrete shear walls6) 3.0
7)
vii) Ductile shear walls 4.0
Building with Dual Systems8)
viii) Ordinary shear wall with OMRF 3.0
ix) Ordinary shear wall with SMRF 4.0
x) Ductile shear wall with OMRF 4.5
xi) Ductile shear wall with SMRF 5.0
(Note: Refer Table 7of IS 1893 (Part 1) : 2002 for full details, which are described by
superscripts 1 to 8 )
*) Buildings with shear walls also include buildings having shear walls and frames,
but where;
a) frames are not designed to carry lateral loads, or
b) frames are designed to carry lateral loads but do not fulfill the requirements of '
dual systems '.
*) Buildings with dual systems consist of shear walls (or braced frames ) and
moment resisting frames such that;
a) the two systems are designed to resist the total design force in proportion to
their lateral stiffness considering the interaction of the dual system at all floor levels;
and
b) the moment resisting frames are designed to independently resist at least 25
percent of the design seismic base shear.
37
2.3.4 Seismic analysis of buildings
2.3.4.1 Seismic weight of the building
The seismic weight of a building shall be calculated as per Clause 7.43 of IS 1893
(Part 1) : 2002. The seismic weight of the whole building is the sum of the seismic
weights of all the floors. The seismic weight of each floor is its full dead load plus an
appropriate amount of imposed loads as given in table 8 of IS 1893 (Part 1) : 2002.
38
o Diaphragm discontinuity:
Diaphragm with abrupt discontinuities or variations in stiffness,
including those having cut-out or open areas greater than 50percent of
the gross enclosed diaphragm area, or changes in effective diaphragm
stiffness of more than 50 percent from one storey to the next.
o Out-of-Plane Offsets:
Discontinuities in a lateral force resistance path, such as out-of-plane
offsets of vertical elements.
o Non-parallel System:
The vertical elements resisting the lateral force are not parallel to or
symmetric about the major orthogonal axes or the lateral force
resisting elements.
39
o Vertical geometric irregularity:
A weak storey is one in which the storey lateral strength is less than
80 percent of that in the storey above.
a) The use of above two methods of analysis shall be decided based on the structural
characteristics of the building.
b) For the consequences of structural regularity on the structural analysis method,
refer Table IS-6 (Clause 7.8.1of IS 1893 (Part 1) : 2002)
40
Note-
For irregular buildings, lesser than 40min height in zones II and III, dynamic analysis, even
though not mandatory, is recommended in IS 1893 (Part 1) :2002.
VB = AhW
Where
Ah: Design horizontal acceleration spectrum value using the fundamental
natural period Ta in the considered direction of vibration.
W: Seismic weight of the building.
Where,
h = Height of the building, in m and
d = Base dimension of the building at the plinth level, in m, along
the considered direction of the lateral force.
41
2.3.4.3.1.2 Distribution of design force
The design base shear ( VB ) shall be distributed along the height of the building as
per the following expression ( Refer Clause 7.7.1 of IS 1893 (Part 1) : 2002);
Where
Qi: Design lateral force at floor i,
W: Seismic weight of the floor i ,
hi: Height of floor i measured from base ,
n: Number of storeys in the building is the number of levels at which the
masses are located.
This type of analysis is generally recommended to use for any building. The following are
the important aspects that should be considered in the analysis procedure in accordance with
the code.
b) The number of modes to be used in the analysis should be such that the sum
total of modal masses of all modes considered is at least 90 percent of the
total seismic mass correction beyond 33 percent. If modes with natural
frequency beyond 33HZ are to be considered, modal combination shall be
carried out only for modes up to 33HZ. The effect of higher modes shall be
42
included by considering missing mass correction following well established
procedures (Refer Clause 7.8.4.2 of IS 1893 (Part 1) : 2002).
43
2.3.4.5 Storey drift limitation
The storey drifts in any storey due to the minimum specified design lateral force,
with partial safety factor of 1.0, shall not exceed 0.004 times the storey height (Refer
Clause 7.11.1of IS 1893 (Part 1) : 2002).
There shall be no drift limit for single storey building which has been designed to
accommodate storey drift.
The sub-soil types, defined in the Indian code seems to be more convenient to be applied in
Sri Lankan conditions, basically because of its simplicity in defining the sub-soil categories,
which does not require sophisticated soil tests in doing so.
44
2.4.2 Structural regularity
For the purpose of seismic design, building structures are categorized into being regular or
non-regular. However, the regularity has been considered in seismic design process by
different codes of practice in different ways.
The Australian code has considered all the buildings to be irregular since, the most of the
buildings in Australia are irregular.
The Indian code seems to address the irregularities by just requiring dynamic analysis.
However, the Euro code has considered the effect of a building being irregular in many
ways. In instance, the code recommends to use a reduced value for basic behavior factor,
for buildings, which are not regular in elevation.
45
2.4.6 P-delta effects
The Euro code and the Australian code have described the way to determine the P-
delta effects in calculation based upon θ, the inter-storey sensitivity coefficient,
according to the Euro code and the inter-storey stability coefficient, according to the
Australian code. However, the Indian code does not provide such a method to
determine the P-delta effects in seismic design calculation.
In their research, Yogendra Singh [15] intended to compare the code provisions for seismic
analysis and design of ductile RC frame buildings. All current seismic design codes are
based on a prescriptive Forced-Based Design approach. In this approach, a linear elastic
analysis is performed and inelastic energy dissipation is considered indirectly through a
response reduction factor (or a behavior factor). Building codes define different ductile
classes and specify different response reduction factors based on the material, configuration
and detailing. Codes also differ specifying the effective stiffness of RC members, procedures
to estimate drift and allowable limits on drift. This research paper presents a comparative
study of different ductility classes and corresponding response reduction factors,
reinforcement detailing provisions and a case study of seismic performance of a ductile RC
frame building designed using four major codes ASCE7 (United States), EN 1998-1 (Euro),
NZS 1170.5 (New Zealand) and IS 1893 (India)
Based upon the results, as a conclusion, it states that the comparison of broad ductility
classes suggests significant variation in different codes. It also conclude that, it is not
possible to directly compare the response reduction factors for various ductility classes due
to the variation in provisions for reinforcement detailing and capacity design provisions. It
further states that the most of codes combine the effect of overstrength and ductility in a
single reduction factor, except for NZS 1170.5, which considers the overstrength separately
through a "structural performance factor".
This study also confirms that NZS 1170.5 results in the highest design base shear for a given
period, for almost all the cases considered in the study. The design base shear as per Euro
46
code 8 has become close to that of NZS 1170.5, while IS 1893 has resulted in lowest design
base shear force for a given hazard. Based upon the seismic performance of an eight storied
RC frame building, it has been noted that the inter storey drift ratio was greater than 2.5% for
DBE and, equal or greater 4% for MCE for most of the codes.
Pravin Ashok Shirule [14] has performed a parametric study on reinforced concrete
structural walls and moment resisting frame building representative of structural types, using
response spectrum method. The objective of this project was to investigate the differences
caused by the use of different codes in the dynamic analysis of multistoried RC building.
Here, the design spectra recommended by Indian Standard Code, IS 1893 (Part a) : 2002 and
two other codes, namely the Uniform Building Code and the Euro Code8 have been
considered for comparison.
To evaluate the seismic response of the buildings, elastic analysis has been performed by
using response spectrum method using the computer software SAP2000. Through this study,
it has concluded that the base shear using Indian code is higher in all the three buildings,
when compared to that of with other codes, which lead to overestimate the overturning
moments in the building.
The study further concludes that for the buildings, UBC code gives the maximum and IS
gives the minimum displacement values.
47
Based on analysis, it concludes that the buildings designed using Euro code perform better
comparing to the Indian code and the American code. It further suggests the requirement of
improvements for Indian and American codes in performance based design.
In the research conducted by Mehul J. Bhavsar [18], a comparative study has been done
based upon a seismic analysis performed for a RC building according to Indian standard and
Euro standard. The paper highlights the importance of doing such a study, because there is a
possibility that the International Standards may have more parameters that are not included
in Indian Standards. It further mention the importance of Euro code in developing country
like India, because most of the Gulf countries, which are having remarkable infrastructures
also follow Euro code.
In making the comparison, it has considered most of important criteria such as response
reduction factor, ductility classes, maximum storey displacements, drift limitations, base
shear, reactions and axial loads etc.
The paper concludes that the design base shear force obtained with IS 1893 was lower than
the design base shear force calculated using the Euro code, because of the high response
reduction factor, which has been used in analysis with Indian code.
48
3.0 METHODOLOGY
As described in the introduction chapter, firstly three main seismic analysis codes
that are often used by Sri Lankan engineers were identified, namely the Euro code,
EC-8 (EN 1998-1:2004), the Australian code (AS 1170.4-2007) and the Indian code
(IS 1893 (Part 1):2002). In literature review section, the analysis procedures that
have been established in each of those codes were outlined in step by step, discussing
the important parameters and how they are to be used in Sri Lankan conditions etc.
Since these codes have established their own analysis procedures and parameters
irrespective of other codes, it was very important to make a detail discussion over
their analysis procedures, how those codes have defined different parameters and
their proposed values and how those codes have considered different structural
effects in their analysis etc. The latter parts of the literature review chapter has been
used for this purpose.
The next task was to demonstrate through case studies how to apply the static and
dynamic seismic analysis procedures described in those codes to analyse buildings in
Sri Lanka under different geotechnical considerations. In order to achieve this
objective, three different reinforced concrete building structures were selected for
analysis namely, building "A", an eighteen storied residential apartment building,
building "B", a fourteen storied residential apartment building and building "C", a ten
storied residential apartment building.
Since it better represents the actual behavior of the structure, three dimensional
computer models of those buildings were developed with elements of actual sizes,
according to the guidelines provided in relevant sections of the particular codes of
practice. For all the modeling and analysis purposes, computer software "ETABS"
version 9.7 has been used.
The structures were then dynamically analysed for seismic effects as described in the
respective codes of practice. Response Spectrum Analysis (RSA) was used for all
dynamic analysis purposes. Equivalent static analysis were also done as per
requirements, established in particular codes of practice.
49
In order the results to be more general, all of the above three buildings were analysed
for three different soil conditions, which can be commonly found in Sri Lanka,
namely soft soil, medium soil and hard soil. In this way, a total of twenty seven cases
were studied. A detail description of the analysis procedures have been presented in
the respective sections of the analysis chapter
Finally the output results, like drifts and base shear forces obtained under different
codes and soil conditions were studied to find out how they vary when moving
between different soil conditions and different codes of practice, which helped in
making final conclusion of the research.
50
4.0 ANALYSIS ACCORDING TO EURO CODE { EN 1998-
1:2004}
4.1 BUILDING "A"
4.1.1 Design seismic action
Classification of building
Since this is an apartment building having more than 10 storeys, the structure is
categorized as importance level III (Table EN1)
(Table EN-2)
This building has been designed for Ductility Class Medium (DCM) conditions. The
behavior factor, q for this building, according to Clause 5.2.2.2 of EN 1998-1:2004,
The structural type of the building has been considered as torsionally flexible system.
The for a torsionally flexible system, which is regular in elevation is given as,
(Table EN-4)
Since the selected building is irregular in elevation, 80% of the has to be used in
calculations, as described in appendix A-2.1.2.
And,
51
∑ ∑
0=9.96
Therefore,
= (1+9.96)/3
Therefore,
q = (0.8×2× 1) = 1.6
Elastic response spectrum and design response spectrum for three different types of
soil conditions and are shown in figure EA-1.
T(S)
52
was also performed in order to obtain the horizontal force acting on each storey,
which was used to determine accidental torsional effects as described in section
2.1.5.5.
All the computer analysis were performed with the ETABs software (CSI 2002.
ETABS Integrated Building Design Software, Computers and Structures Inc.
Berkley).
4.1.2.1Structural Model
The EN 1998-1:2004 recommends using a spatial model as the preference method
for all type of buildings(Clause 4.3.1of EN 1998-1:2004). On account of that, for the
test building a three dimensional (spatial) model was developed.
In this study, the building has been considered to have no significant structural effect
from the masonry infill walls on its behavior when subjected to seismic load. The
reinforced concrete frame wall system was considered as the only lateral load
resisting system in the building and therefore, the presence of masonry infill walls
were neglected in the model. However, their weight was considered in the
calculation of seismic weight of the building.
It is required that the model should fulfill all the requirements specified in the code.
The basic characteristics of the model of the test building considering the
requirements in the code are as follows.
o Column and beam elements were modeled as line elements whereas the
floor slabs and concrete walls were modeled as shell elements.
o Unreinforced masonry infill walls were not included in the model
assuming that they have no contribution to the stiffness or the lateral
strength of the building, but the weight of those walls were applied to the
model.
o The elements were modeled with the actual sizes such that they adequately
represent the distribution of stiffness and mass of the building.
o The cracked elements were considered in the analysis according to Clause
4.3.1(6) of EN 1998-1: 2004.The elastic flexural and shear properties of
the cracked sections were taken to be equal to one-half of the
53
corresponding stiffness of the un-cracked elements (EN 1998-1:
2004/4.3.1 (7)).
o Torsional stiffness of the cracked section was set equal to 10% of the
torsional stiffness of the un-cracked section.
o Frames were connected by means of rigid diaphragms in horizontal plane
at each floor level.
o The accidental torsional effects were considered by applying torsional
moments about vertical axis.
54
4.1.2.2 Lateral force method of analysis
The lateral force method of analysis has been carried out in three main steps as
follows.
As described in section 2.1.5.1, the seismic mass of the building was taken as the
following combination of dead load and the variable loads as,
∑Gk,j+ ∑Ʊ E,iQk,I
As described in section 2.1.5.4.1, the seismic base shear force for each horizontal
direction was determined by the following equation,
where,
55
: The value of the ordinate of the design response
spectrum, corresponding to the fundamental period T1 of the
building for different soil conditions – Refer figure EA-1
The values of λ for three different soil conditions are shown in table EA-2.
The base shear forces for each horizontal direction, Fb for three soil conditions are
shown in Table EA-3.
The seismic base shear (Fb) was distributed at each storey level by using the
following expression as shown in section 2.1.5.4.1(C),
The distribution of seismic base shear at each storey level is shown in Table EA-4.
56
Table EA-4 :Distribution of seismic base shear at each storey level - Building A
The general rules recommended for this type of analysis, as described in clause
4.3.3.3 of EN 11998-1:2004 were followed in the case of the test building and are
given as follows.
57
4.1.2.3.2 Periods and effective masses
In the modal response spectrum analysis, 12 modes of vibration were taken into
account as the sum of the modal masses in each horizontal direction to exceed 90%
of the total mass of the structure.
The horizontal forces ( and ) for three soil conditions were obtained from the
lateral force method of analysis. The calculation of torsional moments at each storey
level is shown in Table EA-6.
58
Table EA-6 : Torsional moments at each horizontal direction
In the case of test building, the storey shear forces and the displacement of the centre
of mass of each floor level of the building were obtained by performing response
spectrum analysis for the system. The design displacement values for three different
soil conditions were calculated according to section 2.1.5.6.
Storey shear forces and displacement of the centre of mass of each floor level of the
building are shown in table EA-7 and EA-8 respectively.
59
Table EA-7 : Storey shear forces of building A (Modal response spectrum analysis
method)
Table EA-8 : displacement (ds) of the test building at each storey level (Modal
response spectrum analysis method)
60
4.1.2.3.5 Inter-storey drift
The inter-storey drift (dr) was evaluated as described in section 2.1.5.6.2, considering
the difference of the lateral displacements (ds) in centre of mass (CM) at the top and
bottom of the storey, obtained by response spectrum analysis.
The inter-storey drift (dr) was then checked for damage limitation requirement given
by the following equation ,
Since the structure is of importance level III, the value was selected to 0.4.
All parameters for the verification of the damage limitation requirement for response
spectrum analysis are listed in tables EA-9, EA-10 and EA-11 for soft, medium and
hard soil conditions respectively.
61
Table EA-10 : Parameters defining the criteria for damage limitation
requirement by modal response spectrum analysis – Medium soil
conditions
62
4.1.2.3.6 P-Δ effects
As described in section 2.1.5.7, the P-Δ effects was checked according to the
equation given as,
Where,
Ptot: Is the total gravity load, including appropriate amount of imposed load at
and above the storey considered in the seismic design situation – From table
EA-1.
dr: Is the inter-storey drift – From table EA-9, EA-10, EA-11 as appropriately
for particular soil type.
Vtot: Is the total seismic storey shear from response spectrum analysis.
The calculation of the inter-storey drift sensitivity coefficient from modal response
spectrum analysis are shown in Table EA-12, EA-13 and EA-14 for soft, medium
and hard soil conditions respectively.
63
Table EA-13 : Calculation of inter-storey drift sensitivity coefficient at each
level of building A from modal response spectrum analysis –
Medium soil conditions
64
4.2 BUILDING "B"
4.2.1 Design seismic action
Classification of building
Since this is an apartment building having more than 10 storeys, the structure has
been categorized as importance level III (Table EN-1)
The structural type of the building has been considered as torsionally flexible system.
The for a torsionally flexible system, which is regular in elevation is given as,
(Table EN-4)
Since the selected building is irregular in elevation, 80% of the has to be used in
calculations, as described in appendix A-2.1.2.
And,
∑ ∑
0=17.28
65
Therefore,
= (1+17.28)/3
Therefore,
q = (0.8×2× 1) = 1.6
Elastic response spectrum and design response spectrum for three different types of
soil conditions and are shown in figure EB-1.
T(S)
66
All the computer analysis were performed with the ETABs software (CSI 2002.
ETABS Integrated Building Design Software, Computers and Structures Inc.
Berkley).
As described in section 2.1.5.1, the seismic mass of the building was taken as the
following combination of dead load and the variable loads as,
∑Gk,j+ ∑Ʊ E,iQk,I
As described in section 2.1.5.4.1, the seismic base shear force for each horizontal
direction was determined by the following equation,
68
m: The seismic mass of the building - Refer table EB-1
The base shear force for each horizontal directions for three
soil conditions are shown in Table EB-3.
Distribution of seismic base shear at each storey level is shown in Table EB-4.
69
Table EB-4 : Distribution of seismic base shear at each storey level - Building B
70
Table EB-5 : Periods and effective modal mass participation of building B
(Modal response spectrum analysis)
The horizontal forces ( and ) for three soil conditions were obtained from the
lateral force method of analysis. The calculation of torsional moments at each storey
level is shown in Table EB-6.
71
Table EB-6 : Torsional moments at each horizontal direction
Storey shear forces and displacement of the centre of mass of each floor level of the
building are shown in table EB-7 and EB-8 only.
72
Table EB-8 : Design displacement (ds) of the test building at each storey level
(Modal response spectrum analysis method)
4.2.2.3.5Inter-storey drift
The inter-storey drift (dr) was evaluated as described in section 2.1.5.6.2, considering
the difference of the lateral displacements (ds) in centre of mass (CM) at the top and
bottom of the storey, obtained by response spectrum analysis.
The inter-storey drift (dr) was then checked for damage limitation requirement given by the
following equation ,
Since the structure is of importance level III, the value was selected to 0.4.
All parameters for the verification of the damage limitation requirement for response
spectrum analysis are listed in tables EB-9, EB-10 and EB-11 for soft, medium and hard soil
conditions respectively.
73
Table EB-9 : Parameters defining the criteria for damage limitation
requirement by modal response spectrum analysis - Soft soil
conditions
74
Table EB-11 : Parameters defining the criteria for damage limitation
requirement by modal response spectrum analysis - Hard soil
conditions
As described in section 2.1.5.7, the P-Δ effects was checked according to the
equation given as,
Where,
Ptot: Is the total gravity load, including appropriate amount of imposed load at
and above the storey considered in the seismic design situation – From table
EB-1.
dr: Is the inter-storey drift – From table EB-9, EB-10, EB-11 as appropriately
for particular soil type.
Vtot: Is the total seismic storey shear from response spectrum analysis.
The calculation of the inter-storey drift sensitivity coefficient from modal response
spectrum analysis are shown in Table EB-12, EB-13 and EB-14 for soft, medium and
hard soil conditions respectively.
75
Table EB-12 : Calculation of inter-storey drift sensitivity coefficient at each
level of building B from modal response spectrum analysis – Soft
soil conditions.
76
Table EB-14 : Calculation of inter-storey drift sensitivity coefficient at each
level of building B from modal response spectrum analysis –
Hard soil conditions.
Since this is an apartment building having 10 storeys, the structure has been
categorized as importance level III (Table EN1).
The structural type of the building has been considered as torsionally flexible system.
The for a torsionally flexible system, which is regular in elevation is given as,
77
(Table EN-4)
And,
∑ ∑
0=9.96
Therefore,
= (1+9.96)/3
Therefore,
q = (2× 1) = 2.0
Elastic response spectrum and design response spectrum for three different types of
soil conditions and are shown in figure EC-1.
All the computer analysis were performed with the ETABs software (CSI 2002.
ETABS Integrated Building Design Software, Computers and Structures Inc.
Berkley).
79
Figure EC-2 : Three dimensional (spatial) model of the building C
80
4.3.2.2.1 Estimation of seismic mass of the building
As described in section 2.1.5.1, the seismic mass of the building was taken as the
following combination of dead load and the variable loads as,
∑Gk,j+ ∑Ʊ E,iQk,I
The base shear force for each horizontal directions for three
soil conditions are shown in Table EC-3.
81
Table EC-2 : Correction factor, λ for building C
Distribution of seismic base shear at each storey level is shown in Table EC-4.
Table EC-4 : Distribution of seismic base shear at each storey level - Building C
82
4.3.2.3 Modal response spectrum analysis
4.3.2.3.1 General rules
The general rules recommended for this type of analysis, as described in clause
4.3.3.3 of EN 11998-1:2004 were followed in the case of the test building in a
similar way as in building A, which is described in section 4.1.2.3.1.
In the case of test building, the storey shear forces and the displacement of the centre
of mass of each floor level of the building were obtained by performing response
spectrum analysis for the system. The design displacement values for three different
soil conditions were calculated according to section 2.1.5.6.
Storey shear forces and displacement of the centre of mass of each floor level of the
building are shown in table EC-7 and EC-8 only.
84
Table EC-8 : Design displacement (ds) of the test building at each storey level
(Modal response spectrum analysis method)
The inter-storey drift (dr) was evaluated as described in section 2.1.5.6.2, considering
the difference of the lateral displacements (ds) in centre of mass (CM) at the top and
bottom of the storey, obtained by response spectrum analysis.
The inter-storey drift (dr) was then checked for damage limitation requirement given
by the following equation ,
Since the structure is of importance level III, the value was selected to 0.4.
All parameters for the verification of the damage limitation requirement for response
spectrum analysis are listed in tables EC-9, EC-10 and EC-11 for soft, medium and hard soil
conditions respectively.
85
Table EC-9 : Parameters defining the criteria for damage limitation
requirement by modal response spectrum analysis - Soft soil
conditions
86
4.3.2.3.6 P-Δ effects
As described in section 2.1.5.7, the P-Δ effects was checked according to the
equation given as,
Where,
Ptot: Is the total gravity load, including appropriate amount of imposed load at
and above the storey considered in the seismic design situation – From table
EC-1.
dr: Is the inter-storey drift – From table EC-9, EC-10, EC-11 as appropriately
for particular soil type.
Vtot: Is the total seismic storey shear from response spectrum analysis.
The calculation of the inter-storey drift sensitivity coefficient from modal response
spectrum analysis are shown in Table EC-12, EC-13 and EC-14 for soft, medium and
hard soil conditions respectively.
87
Table EC-13 : Calculation of inter-storey drift sensitivity coefficient at each
level of building C from modal response spectrum analysis –
Medium soil conditions.
88
5.0 ANALYSIS ACCORDING TO AUSTRALIAN CODE { AS
1170.4-2007}
5.1 BUILDING "A"
The selected building is an eighteen storied reinforced concrete apartment building,
which includes aground floor and seventeen above floors. The basic descriptions and
calculations of this structure are described in appendix A.
Classification of building
This is an apartment building having more than 15 storeys. Therefore the building is
categorized as Importance level 3 (Table AS-2)
Probability factor, kp
Hazard factor, Z
The hazard factor, Z for different locations in Australia is given in table 3.2 of AS
1170.4-2007. However, for Sri Lankan conditions, it was considered to be 0.1
throughout the country.
Sub-soil class
89
Importance level: 3
Therefore, according to table AS-3, the building shall be designed for earthquake design
categories based on sub-soil classes as follows III (EDC III).
90
5.1.2.1 Structural Model
A three dimensional mathematical model was used in this analysis since it could
represent the special distribution of the mass and the stiffness of the structure
adequately.
In this study, the building was considered to have no significant structural effect
from the masonry infill walls on its behavior when subjected to seismic load. The
reinforced concrete frame wall system was considered as the only lateral load
resisting system in the building and therefore, the presence of masonry infill walls
were not considered in making the model. However, their weight was considered in
the calculation of seismic weight of the building.
It was required that the model should fulfill all the requirements specified in the
code. The basic characteristics of the model of the test building considering the
requirements in the code are as follows.
91
Figure AA-1: Three dimensional (spatial) model of building A
Equivalent static analysis can be carried out in three main steps as follows.
92
b). Calculating the seismic base shear in relevant directions
Wi = ∑ ∑
V = Cd(T1)Wt
V = 0.0494Ch(T1)Wt
T1= 1.53 S
93
Ch(T1): The values of the spectral shape factors are obtained
from table 6.4 of AS 1170.4:2007.
The base shear forces for each horizontal direction, based on T1 calculated according
to both of above methods are shown in Table AA-2 and AA-3.Base shear forces
calculated using T1, obtained from modal analysis were then checked weather they
exceed 80% of the base shear values obtained with T1 calculated using the above
equation. Base shear forces of the structure, after the comparison are shown in Table
AA-4.
Table AA-2 : Design seismic base shear of building A (T1 from modal analysis)
Table AA-3 : Design seismic base shear of building A (T1 from eq. 6.2(7) of AS
1170.4-2007)
94
5.1.2.2.3 Distribution of lateral forces
The seismic base shear (V) was then distributed at each storey level by using the
following expression as shown in 2.2.4.3.1.3,
Fi = kF,iV (Refer AS 1170.4: 2007/eq 6.3(1) )
The values for k in X direction (kx) and in Y direction (ky) were calculated
according to Clause 6.3 of AS 1170.4-2002, as follows.
k=exponent depend on the fundamental period of the structure (T1), which is taken
as-
1.0 when T1≤0.5;
2.0 when T1≥2.5; or
linearly interpolated between 1.0 and 2.0 for 0.5< T1<2.5
The distribution of seismic base shear at each storey level is shown in Table AA-5
95
5.1.2.3 Modal response spectrum analysis
5.1.2.3.1. General rules
The general rules recommended for this type of analysis were followed in the case of
the test building and are given as follows.
o Modal response spectrum analysis was performed independently for the
ground excitation in two horizontal directions.
o For the combination of different modes, the “Complete Quadratic
Combination (CQC) rule was used.
o The results of the modal analysis in both directions were combined by the
SRSS rule.
o The load combinations were considered according to Clause 4.2.2 of AS
1170.0; 2002.
o The accidental torsional effect was considered by means of torsional
moments about the vertical axis according to Clauses 7.4.4.1 and 6.6 of
AS 1170.4-2007.
96
Table AA-6 : Periods and effective modal mass participation of building A
(Modal response spectrum analysis
The horizontal forces ( and ) for three soil conditions were obtained from the
lateral force method of analysis. The calculations of torsional moments at each storey
level are listed in tables AA-7 for very soft soil, shallow soil and rock conditions.
97
Table AA-7 : Torsional moments - Building A
Storey shear forces and displacement of the centre of mass of each floor level of the
building are shown in table AA-8 and AA-9 respectively.
98
Table AA-9: Design displacement (di) of the test building at each storey level
(Modal response spectrum analysis method)
The inter-storey drift (dst) at each floor levels were then checked against the
maximum allowable value for damage limitation requirement, given as 1.5% of the
storey height(h) according to clause 5.5.4 of AS 1170.4-2007.
All parameters for the verification of the damage limitation requirement obtained by
response spectrum analysis for different soil conditions are listed in Table AA-10.
99
Table AA-10 : Parameters defining the criteria for damage limitation
requirement by modal response spectrum analysis – Building A
∑ ( ∑ )
Where,
dst: The design storey drift – From table AA-8, as appropriately for particular
soil type.
Fj: Horizontal dynamic force at the jth level, obtained from response
spectrum analysis - From table AA-8 as appropriately.
100
The calculation procedure related to inter-storey stability coefficient for three
different ground conditions are listed in table AA-11, AA-12 and AA-13.
101
Table AA-13 : Calculation of inter-storey stability coefficient at each level of
building A from modal response spectrum analysis – Rock
conditions
Probability factor, kp
102
Hazard factor, Z
The hazard factor, Z for different locations in Australia is given in table 3.2 of AS
1170.4-2007. However, for Sri Lankan conditions, it was considered to be 0.1
throughout the country.
Sub-soil class
Importance level: 2
Therefore, according to table AS-3, the building shall be designed for earthquake design
categories based on sub-soil classes as follows.
103
Cd(T) = 0.1 X 0.38 X Ch(T)
104
Figure AB-1: Three dimensional (spatial) model of building B
Equivalent static analysis can be carried out in three main steps as follows.
105
5.2.2.2.1 Estimation of seismic weight of the building
As described in section 2.2.4.1 the seismic weight of the building can be found by
following combination of dead load and the variable loads as,
Wi = ∑ ∑
V = Cd(T1)Wt
V = 0.0494Ch(T1)Wt
T1= 1.11 S
106
Ch(T1): The values of the spectral shape factors are obtained
from table 6.4 of AS 1170.4:2007.
The base shear forces for each horizontal direction, based on T1 calculated according
to both of above methods are shown in Table AB-2 and AB-3.Base shear forces
calculated using T1, obtained from modal analysis were then checked weather they
exceed 80% of the base shear values obtained with T1 calculated using the above
equation. Base shear forces of the structure, after the comparison are shown in Table
AB-4.
Table AB-2 : Design seismic base shear of building B (T1 from modal analysis)
Table AB-3 : Design seismic base shear of building B (T1 from eq. 6.2(7) of AS
1170.4-2007)
107
5.2.2.2.3 Distribution of lateral forces
The seismic base shear (V) was then distributed at each storey level by using the
following expression as shown in 2.2.4.3.1.3,
Fi = kF,iV (Refer AS 1170.4: 2007/eq 6.3(1) )
The values for k in X direction (kx) and in Y direction (ky) were calculated
according to Clause 6.3 of AS 1170.4-2002, as described in section 5.1.2.2.3, in case
of building A.
The distribution of seismic base shear at each storey level is shown in Table AB-5
108
o The results of the modal analysis in both directions were combined by the
SRSS rule.
o The load combinations were considered according to Clause 2.2.2 of AS
1170.0; 2002.
o The accidental torsional effect was considered by means of torsional
moments about the vertical axis according to Clauses 7.4.4.1 and 6.6 of
AS 1170.4-2007.
109
of torsional moments ( and ) was then added to the combined (SRSS)
results of the seismic actions in both horizontal directions.
The horizontal forces ( and ) for three soil conditions were obtained from the
lateral force method of analysis. The calculation of torsional moments at each storey
levels are listed in tables AB-7 for very soft soil, shallow soil and rock conditions
respectively.
In the case of test building, the storey shear forces and the displacement of the centre
of mass of each floor level of the building were obtained by performing response
spectrum analysis for the system. The design displacement values for three different
soil conditions were calculated according to section 2.2.4.3.1.5
Storey shear forces and displacement of the centre of mass of each floor level of the
building are shown in table AB-8 and AB-9 respectively.
110
Table AB-8: Storey shear forces of building B (Modal response spectrum
analysis method)
Table AB-9: Design displacement (di) of the test building at each storey level
(Modal response spectrum analysis method)
The design drift(dst) at each floor levels of the structure were evaluated similar way
in building A, as described in section 5.1.2.3.5, considering the difference of the
deflections (di) in centre of mass (CM) at the top and bottom of the storey, obtained
by response spectrum analysis.
The inter-storey drift (dst) at each floor levels were then checked against the
maximum allowable value for damage limitation requirement, given as 1.5% of the
storey height(h) according to clause 5.5.4 of AS 1170.4-2007.
111
All parameters for the verification of the damage limitation requirement obtained by
response spectrum analysis for different soil conditions are listed in Table AB-10.
As described in section 5.1.2.3.6 for building A, the P-Δ effects in building B was
checked according to the following equation,
∑ ( ∑ )
Where,
dst: The design storey drift – From table AB-8, as appropriately for particular
soil type.
Fj: Horizontal dynamic force at the jth level, obtained from response
spectrum analysis - From table AB-8as appropriately.
112
The calculation procedure related to inter-storey stability coefficient(θ) for three
different ground conditions are listed in table AB-11, AB-12 and AB-13.
113
Table AB-13 :Calculation of inter-storey stability coefficient at each level of
building B from modal response spectrum analysis – Rock
conditions
Classification of building
Since this is an apartment building having less than 15 storeys, the building has been
categorized as Importance level 2 (Table AS-2)
Probability factor, kp
114
Hazard factor, Z
The hazard factor, Z for different locations in Australia is given in table 3.2 of AS
1170.4-2007. However, for Sri Lankan conditions, it was considered to be 0.1
throughout the country.
Sub-soil class
Importance level: 2
Therefore, according to table AS-3, the building shall be designed for earthquake design
categories based on sub-soil classes as follows.
115
Sp/µ = 0.38 (Table AS-6)
116
Figure AC-1: Three dimensional (spatial) model of building C
Equivalent static analysis can be carried out in three main steps as follows.
117
5.3.2.2.1 Estimation of seismic weight of the building
As described in section 2.2.4.1 the seismic weight of the building can be found by
following combination of dead load and the variable loads as,
Wi = ∑ ∑
V = Cd(T1)Wt
V = 0.038Ch(T1)Wt
T1= 0.83 S
118
Wt : The seismic weight of the building - Refer table AC-1
The base shear force for each horizontal direction, based on T1 calculated according
to both of above methods are shown in Table AC-2 and AC-3.Base shear forces
calculated using T1, obtained from modal analysis were then checked weather they
exceed 80% of the base shear values obtained with T1 calculated using the above
equation. Base shear forces of the structure, after the comparison are shown in Table
AC-4.
Table AC-2 : Design seismic base shear of building C (T1 from modal analysis)
Table AC-3 : Design seismic base shear of building C (T1 from eq. 6.2(7) of AS
1170.4-2007)
119
=∑ [KpZCh(T1) /]Wt (Refer AS 1170.4: 2007/eq 6.2(2)
The values for k in X direction (kx) and in Y direction (ky) were calculated
according to Clause 6.3 of AS 1170.4-2002, as described in section 5.1.2.2.3, in case
of building A.
The distribution of seismic base shear at each storey level is shown in Table AC-5
120
5.3.2.3.2 Periods and effective masses
In the modal response spectrum analysis, adequate modes of vibrations were taken in
to account described in Clause 7.4.2 of AS1170.4-2007.
The horizontal forces ( and ) for three soil conditions were obtained from the
lateral force method of analysis. The calculation of torsional moments at each storey
levels are listed in tables AC-7 for very soft soil, shallow soil and rock conditions
respectively.
121
Table AC-7 : Torsional moments - Building C
In the case of test building, the storey shear forces and the displacement of the centre
of mass of each floor level of the building were obtained by performing response
spectrum analysis for the system. The design displacement values for three different
soil conditions were calculated according to section 2.1.5.6.
Storey shear forces and displacement of the centre of mass of each floor level of the
building are shown in table AC-8 and AC-9 respectively.
122
Table AC-9:Design displacement (di) of the test building at each storey level
(Modal response spectrum analysis method)
The design drift(dst) at each floor levels of the structure were evaluated similar way
in building A, as described in section 5.1.2.3.5, considering the difference of the
deflections (di) in centre of mass (CM) at the top and bottom of the storey, obtained
by response spectrum analysis.
The inter-storey drift (dst) at each floor levels were then checked against the
maximum allowable value for damage limitation requirement, given as 1.5% of the
storey height(h) according to clause 5.5.4 of AS 1170.4-2007.
All parameters for the verification of the damage limitation requirement for response
spectrum analysis for different soil conditions are listed in Table AC-10.
123
5.3.2.3.6 P-Δ effects
As described in section 5.1.2.3.6 for building A, the P-Δ effects in building C was
checked according to the following equation,
∑ ( ∑ )
Where,
dst: The design storey drift – From table AC-8, as appropriately for particular
soil type.
Fj: Horizontal dynamic force at the jth level, obtained from response
spectrum analysis - From table AC-8 as appropriately.
124
Table AC-12 : Calculation of inter-storey stability coefficient at each level of
building C from modal response spectrum analysis – Shallow
soil conditions
125
6 .0 ANALYSIS ACCORDING TO IS 1893(Part 1) : 2002
6.1 BUILDING "A"
The selected building is an eighteen storied reinforced concrete apartment building,
which includes a Ground floor and seventeen above floors. The basic descriptions
and calculations of this structure are described in appendix A.
The zone factor, Z for different zones in India is given in table 2 of IS1893 (Part 1) :
2002. However, the value of this factor has been considered as 0.1 for all areas in Sri
Lanka, which also satisfy the requirement established for zone II.
Importance factor, I
This is an apartment building having 18 storeys. Therefore, according to note 2 of
table 6 of IS 1893 (Part1) :2002, the important factor has been selected as 1.5.
Ah = 0.025 Sa/g
Structural Regularity
In this study, the building was considered to have no significant structural effect
from the masonry infill walls on its behavior when subjected to seismic load. The
reinforced concrete frame wall system was considered as the only lateral load
resisting system in the building and therefore, the presence of masonry infill walls
were not considered in making the model. However, their weight was considered in
the calculation of seismic weight of the building.
It is required that the model should fulfill all the requirements specified in the code.
The basic characteristics of the model of the test building considering the
requirements in the code are as follows.
o Column and beam elements are modeled as line elements whereas the
floor slabs and concrete walls are modeled as shell elements.
127
o The elements were modeled with the actual sizes such that they
adequately represent the distribution of stiffness and mass of the
building.
o Even though it is not specifically discussed about the influence of
cracked sections in IS 1893 (Part 1) : 2002, this influence was
reflected in the model by multiplying the moment of inertia and shear
area of the un-cracked sections by 0.5 in order to take the elastic
flexural and shear properties one-half of those corresponding to un-
cracked elements. Torsional stiffness of the cracked sections were set
equal to 10% of the torsional stiffness of the un-cracked sections.
o Frames are connected by means of rigid diaphragms in horizontal
plane at each floor level.
o The accidental torsional effects were considered by applying torsional
moments about vertical axis as described in Clause 7.9 of IS 1893
(Part 1) : 2002.
128
Figure IA-1: Three dimensional (spatial) model of building A
Analysis according to lateral force method can be carried out in three main steps as
follows.
129
6.1.2.2.1 Seismic weight of the building
The seismic weight of the building was calculated considering both the dead load and
the variable loads as described in section 2.3.4.1.
VB = AhW
Where
Ah: Design horizontal acceleration spectrum value using the fundamental
natural period Ta in the considered direction of vibration.
W: Seismic weight of the building - Refer table IA-1.
Ah: Design horizontal acceleration spectrum value using the fundamental
natural period Ta in the considered direction of vibration, which was
calculated in 6.1.1 as 0.025 Sa/g, where Sa/g can be found from figure
IA-1, with respect to fundamental natural period of vibration (Ta) in
the relevant direction
The fundamental natural period of vibration (Ta) has been obtained by model analysis
performed on the three dimensional computer model of the building.
130
The design base shear force acting in each horizontal direction is shown in table IA-
2.
Table IA-2 :Design seismic base shear by static lateral force method - Building
A
Where
Qi: Design lateral force at floor i,
Wi: Seismic weight of the floor i - From table IA-1,
hi: Height of floor i measured from base ,
n: Number of storeys in the building is the number of levels at which the
masses are located
The distribution of design seismic base shear at each storey level is shown in Table
IA-3
131
Table IA-3: Distribution of design seismic base shear at each storey level -
Building A
132
6.1.2.3.2 Periods and effective masses
In the modal response spectrum analysis, adequate number of modes of vibration
were taken in to account as the sum of the modal masses in each horizontal directions
to exceeds 90% of the total mass of the structure as given in Clause 7.8.4.2 of IS
1893-1:2002.
Table IA-4 : Periods and effective modal mass participation by modal response
spectrum analysis - Building A
The horizontal forces ( and ) for three soil conditions were obtained from the
lateral force method of analysis. The calculation of torsional moments at each storey
133
levels are listed in tables IA-5 for soft, medium and hard soil conditions
respectively.
When the design base shear ( VB ), obtained by response spectrum analysis is lesser
than the base shear (̅̅̅), obtained by equivalent static method, then, as per section
7.6 of IS 1893 (Part 1) : 2002, the response quantities like storey shear forces and
displacements were multiplied by ̅̅̅/VB. The summary of base shear forces obtained
by static and dynamic analysis methods are listed in IA-7 and storey shear forces
after modification are listed in table IA-8.
134
Table IA-6 : Storey shear forces by modal response spectrum analysis method -
Building A
Table IA-8 : Modified storey shear forces by modal response spectrum analysis
method - Building A
135
6.1.2.3.5 Storey displacement and drift
In case of test building, the displacement of the centre of mass (CM) of each floor
level of the building was obtained by performing response spectrum analysis for the
system. The drift(dr) at each floor levels of the structure was evaluated considering
the difference of the deflections (d) in centre of mass (CM) at the top and bottom of
the storey.
The displacement values at each storey for soft, medium and hard soil conditions are
listed in table IA-9 and all the parameters for the verification of the damage
limitation requirement for response spectrum analysis are listed in Table IA-10. The
displacement values after modifications are also listed in table IA-11. The
displacement values listed, in Table IA-9 were then adjusted by multiplying by 2R to
obtain the displacement values at ultimate limit state at Maximum Considered Earth
Quake (MCE) situation. The adjusted displacement values are listed in Table IA-12.
136
Table IA-9 : Storey displacement (d) by modal response spectrum analysis
method - Building A
137
Table IA-11 : Modified storey displacements by modal response spectrum
analysis method - Building A
138
6.2 BUILDING "B"
The selected building is a fourteen storied reinforced concrete apartment building,
which includes a Ground floor and thirteen above floors. The basic descriptions and
calculations of this structure are described in appendix B.
The zone factor, Z for different zones in India is given in table 2 of IS1893 (Part 1) :
2002. However, the value of this factor has been considered as 0.1 for all areas in Sri
Lanka, which also satisfy the requirement established for zone II.
Importance factor, I
This is an apartment building having 14 storeys. Therefore, according to note 2 of
table 6 of IS 1893 (Part1) :2002, the important factor was selected as 1.5.
The value for Sa/g for different soil conditions can be taken from figure 2 of IS 1893
(Part1) :2002, based on the natural period of vibration of the structure.
Ah = 0.025 Sa/g
Structural Regularity
In this study, the building was considered to have no significant structural effect
from the masonry infill walls on its behavior when subjected to seismic load. The
reinforced concrete frame wall system was considered as the only lateral load
resisting system in the building and therefore, the presence of masonry infill walls
were not considered in making the model. However, their weight was considered in
the calculation of seismic weight of the building.
As described in section 6.1.2.1 in case of building A, the model for this building was
also developed fulfilling all the requirements specified in the code.
140
Figure IB-1 : Three dimensional (spatial) model of building B
As described in section 6.1.2.2, the analysis according to lateral force method can be
carried out in three main steps as follows.
141
6.2.2.2.1 Seismic weight of the building
The seismic weight of the building was calculated considering both the dead load and
the variable loads as described in section 2.3.4.1.
VB = AhW
Where
Ah: Design horizontal acceleration spectrum value using the fundamental
natural period Ta in the considered direction of vibration.
W: Seismic weight of the building - Refer table IB-1.
Ah: Design horizontal acceleration spectrum value using the fundamental
natural period Ta in the considered direction of vibration, which was
calculated in 6.2.1 as 0.025 Sa/g, where Sa/g can be found from figure
IB-1 with respect to fundamental natural period of vibration (Ta) in
the relevant direction
The fundamental natural period of vibration (Ta) has been obtained by model analysis
performed on the three dimensional computer model of the building,
142
The design base shear force acting in each horizontal direction is shown in table IB-
2.
Table IB-2: Design seismic base shear by equivalent static method - Building B
Where
Qi: Design lateral force at floor i,
Wi: Seismic weight of the floor i - From table IB-1,
hi: Height of floor i measured from base ,
n: Number of storeys in the building is the number of levels at which the
masses are located
The distribution of design seismic base shear at each storey level is shown in table
IB-3
143
Table IB-3: Distribution of design seismic base shear at each storey level -
Building B
144
Table IB-4 : Periods and effective modal mass participation by modal response
spectrum analysis - Building B
The horizontal forces ( and ) for three soil conditions were obtained from the
lateral force method of analysis. The calculation of torsional moments at each storey
levels are listed in tables IB-5 for soft, medium and hard soil conditions
respectively.
145
6.2.2.3.4 Storey shear forces by modal response spectrum analysis
method
Storey shear forces were obtained by performing modal response spectrum analysis for
the test building for three different soil conditions and they are listed in table IB-6.
When the design base shear ( VB ), obtained by response spectrum analysis is lesser
than the base shear (̅̅̅), obtained by equivalent static method, then, as per section
7.6 of IS 1893 (Part 1) : 2002, the response quantities like storey shear forces and
displacements were multiplied by ̅̅̅/VB. The summary of base shear forces obtained
by static and dynamic analysis methods are listed in IB-7 and storey shear forces
after modification are listed in table IB-8.
.
Table IB-6: Storey shear forces by modal response spectrum analysis method -
Building B
146
Table IB-8 : Modified storey shear forces by modal response spectrum analysis
method - Building B
In case of test building, the displacement of the centre of mass (CM) of each floor
level of the building was obtained by performing response spectrum analysis for the
system. The drift(dr) at each floor levels of the structure was evaluated considering
the difference of the deflections (d) in centre of mass (CM) at the top and bottom of
the storey.
The displacement values at each storey for soft, medium and hard soil conditions are
listed in table IB-9 and all the parameters for the verification of the damage
limitation requirement for response spectrum analysis are listed in Table IB-10. The
displacement values after modifications are also listed in table IB-11.The
displacement values, listed in Table IB-9 were then adjusted, multiplying by 2R to
147
obtain the displacement values at ultimate limit state at Maximum Considered Earth
Quake (MCE) situation. The adjusted displacement values are listed in Table IB-12.
148
Table IB-11 : Modified storey displacements by modal response spectrum
analysis method - Building B
149
6.3 BUILDING "C"
The selected building is a 10 storied reinforced concrete apartment building, which
includes a ground floor and 9 floors above. The basic descriptions and calculations
of this structure are described in appendix C.
Zone factor, Z
The zone factor, Z for different zones in India is given in table 2 of IS1893 (Part 1) :
2002. However, the value of this factor has been considered as 0.1 for all areas in Sri
Lanka, which also satisfy the requirement established for zone II.
Importance factor, I
This is an apartment building having 10 storeys. Therefore, according to note 2 of
table 6 of IS 1893 (Part1) :2002, the important factor was selected as 1.5.
The value for Sa/g for different soil conditions can be taken from figure 2 of IS 1893
(Part1) :2002, based on the natural period of vibration of the structure.
Ah = 0.025 Sa/g
150
6.3.2 Method of analysis
The height of the selected building is nearly 40m. It is located in an area similar to
zone II. The design seismic forces were obtained by performing dynamic analysis.
A modal response spectrum analysis has been performed on a three dimensional
structural model of the building. However, a static lateral force method of analysis
has also been performed since the base shear force obtained by dynamic analysis
has to be compared against that of calculated by static lateral force method. The
shear forces, calculated by static lateral force method were also used to determine
the accidental torsional moments, which were assigned in the model as specified in
the code.
6.3.2.1Structural Model
A three dimensional mathematical model was used in this analysis since it can
represent the special distribution of the mass and the stiffness of the structure
adequately.
In this study, the building was considered to have no significant structural effect
from the masonry infill walls on its behavior when subjected to seismic load. The
reinforced concrete frame wall system was considered as the only lateral load
resisting system in the building and therefore, the presence of masonry infill walls
were not considered in making the model. However, their weight was considered in
the calculation of seismic weight of the building.
As described in section 6.1.2.1 in case of building A, the model for this building was
also developed fulfilling all the requirements specified in the code.
151
Figure IC-1: Three dimensional (spatial) model of building C
152
6.3.2.2.1 Seismic weight of the building
The seismic weight of the building was calculated considering both the dead load and
the variable loads as described in section 2.3.4.1.
VB = AhW
Where
Ah: Design horizontal acceleration spectrum value using the fundamental
natural period Ta in the considered direction of vibration.
W: Seismic weight of the building - Refer table IC-1.
Ah: Design horizontal acceleration spectrum value using the fundamental
natural period Ta in the considered direction of vibration, which was
calculated in 6.3.1 as 0.025 Sa/g, where Sa/g can be found from figure
IC-1 with respect to fundamental natural period of vibration (Ta) in
the relevant direction
The fundamental natural period of vibration (Ta) has been obtained by model analysis
performed on the three dimensional computer model of the building.
153
The design base shear force acting in each horizontal direction is shown in table IC-
2.
Table IC-2 : Design seismic base shear by equivalent static method - Building C
Where
Qi: Design lateral force at floor i,
Wi: Seismic weight of the floor i - From table IC-1,
hi: Height of floor i measured from base ,
n: Number of storeys in the building is the number of levels at which the
masses are located
The distribution of design seismic base shear at each storey level is shown in table
IC-3
154
Table IC-3 : Distribution of design seismic base shear at each storey level -
Building C
155
Table IC-4 : Periods and effective modal mass participation by modal response
spectrum analysis - Building C
The horizontal forces ( and ) for three soil conditions were obtained from the
lateral force method of analysis. The calculation of torsional moments at each storey
levels are listed in tables IC-5 for soft, medium and hard soil conditions
respectively.
156
Table IC-5 : Torsional moments - Building C
Storey shear forces were obtained by performing modal response spectrum analysis for
the test building for three different soil conditions and they are listed in table IC-6.
When the design base shear ( VB ), obtained by response spectrum analysis is lesser
than the base shear (̅̅̅), obtained by equivalent static method, then, as per section
7.6 of IS 1893 (Part 1) : 2002, the response quantities like storey shear forces and
displacements were multiplied by ̅̅̅/VB. The summary of base shear forces obtained
by static and dynamic analysis methods are listed in IC-7 and storey shear forces
after modification are listed in table IC-8.
Table IC-6 : Storey shear forces by modal response spectrum analysis method -
Building C
157
Table IC-7 : Summary of base shear forces - Building C
Table IC-8 : Modified storey shear forces by modal response spectrum analysis
method - Building C
The displacement values at each storey for soft, medium and hard soil conditions are
listed in table IC-9 and all the parameters for the verification of the damage
158
limitation requirement for response spectrum analysis are listed in Table IC-10. The
displacement values after modifications are also listed in table IC-11.The
displacement values, listed in Table IC-9 were then adjusted, multiplying by 2R to
obtain the displacement values at ultimate limit state at Maximum Considered Earth
Quake (MCE) situation. The adjusted displacement values are listed in Table IC-12.
159
Table IC-11 : Modified storey displacements by modal response spectrum
analysis method - Building C
160
7.0 COMPARISON OF PERFORMANCE LEVEL
OFBUILDINGS WITH DIFFERENT CODES OF PRACTICE
As described in analysis chapters, the selected three structures have been analysed as
per three different codes of practice. In order to be more general, the structures were
analysed for three different soil conditions, which can be commonly found in the
country. In this way, totally 27 cases were analysed. The output of those analysis
were tabulated in respective subsection of the analysis chapter.
This chapter presents a detail comparison and study on analysis output. The output
values were compared under different criteria to find out possible varying patterns.
161
Table 7.1.1- Transient lateral drift at roof level of the three structures
According to the results obtained and presented in Table 7.1.1, it can be clearly
identified that in all twenty seven cases, the transient lateral drift at roof level has
been maintained below 1%, which is the minimum drift to be maintained by a
structure to achieve Immediate Occupancy Level (IOL), according to FEMA356
standards.
Based on values from Table 7.1.1, Table 7.1.2 has been prepared to determine the
code of practice, which has given the maximum and the minimum values of the
transient drift at roof level.
Table 7.1.2Code of practice for highest and lowest drift ratioat roof level
162
According to the above table, for all three buildings, except in soft/very soft soil
conditions, most of times, the highest drift ratio at roof level have been achieved,
when they were analysed according only to Indian code (10 out of 18 occasions). At
three occasions, both the Euro code and the Indian code have given highest values.In
case of soft/very soft soil conditions, most of times (5 out of 6 occasions), the
Australian code has given the highest drift values. The possible reason may be that,
when analysing according to Australian code, to be more conservative, the "Very soft
soil" condition was adopted instead of "Soft soil" condition, which was the soil
condition adopted in the analysis according to Euro code and the Indian code.
Generally, it can be also noted that, in most of cases (13 out of 18 occasions), the
lowest drift values have been achieved, when they were analysed according to the
Australiancode.
The highest drift ratio at individual floor levels is an important parameter to be considered
in finding out the performance of a structure. The Table 7.2.1 presents the highest drift ratios
achieved when the structures were analysed according to different codes of practice under
different soil conditions.
163
Based on values from Table 7.2.1, Table 7.2.2 has been prepared to determine the
code of practice, which has given the maximum and the minimum values of the
highest storey drift ratio at roof level.
Table 7.2.2 - Code of practice for maximum and minimum value of highest
storey drift ratio at any storey level
The distribution of highest drift ratio at individual floor levels also follows almost the
same pattern as lateral drift at roof level of the structures, which has been described
in section 7.1.
According to the above table, for all three buildings, except in soft/very soft soil
conditions, most of times, the highest drift ratio at any floor level have been
achieved, when they were analysed according only to Indian code (10 out of 18
occasions). Only at one occasion the Euro code only has given highest drift ratio. At
two occasions, both the Euro code and the Indian code have given highest values. In
case of soft/very soft soil conditions, most of times (5 out of 6 occasions), the
Australian code has given the highest drift values..
Generally, it can be also noted that, in most of cases (13 out of 18 occasions), the
lowest drift values have been achieved, when they were analysed according to the
Australian code.
The design base shear is also an important parameter, that can be used as a basis for
a comparison of analysis results. The design base shear forces obtained by each
analysis case are presented in Table 7.3.1
164
Table 7.3.1- Design base shear force of the three structures
Based on values from Table 7.3.1, Table 7.3.2 has been prepared to determine the
code of practice, which has given the highest and the lowest values of the design
base shear force.
Table 7.3.2 - Code of practice for highest and lowest design base shear force
According to the results presented in Table 7.3.2, it can be clearly stated that the
Euro code has given the highest design base shear values at all eighteen occasions.
165
Further, the Indian code has given lowest base shear values at many occasions (12
out of 18 occasions). The reason seems to be that, the Indian code recommends to
use a reduced zone factor (Z/2) to represent Design Basis Earthquake (DBE), which
tends to give lower response quantities consequently ( Refer Clause 6.4.2 of IS 1893
(Part1) :2002).
166
8.0 CONCLUSION AND RECOMMENDATIONS
According to Table 7.1.1 in previous chapter, it can be clearly concluded that, in all
twenty seven cases, irrespective of the code of practice, which has been used in
analysis procedure, the structures have achieved Immediate Occupancy Level (IOL),
according to FEMA356 standards.
Referring to Tables 7.1.1,7.1.2, 7.2.1 and 7.2.2, Generally, it can be also concluded
that the Indian code has given highest drift values at many occasions while the Euro
code also has caused in very close or sometimes similar drift values as in case of
Indian code. The Australian code has generally caused in giving lowest drift values.
As per Table 7.3.2, it can be clearly concluded that the Euro code has given the
highest design base shear values at all eighteen occasions.Further,it has been noted
that the Indian code has given lowest base shear values at many occasions. The
reason for Indian code to produced lower design base shear forces at many occasions
is mainly because it allows to use reduced values for zone factor, Z to represent
Design Basis Earthquake (DBE) instead of Maximum Considered Earthquake
(MCE). .
When the three codes of practice are compared, it has been noted that overall, the
Euro code has describe the whole analysis process in detail and has considered the
structural effects in many ways, like in case of regularity. The one who follows the
code may feel it is easy to do so and also get much confident about his work. This
will give many benefits, specially for beginners, who do not have an explicit
knowledge at the start.
Another very important feature in Euro code is that, adopting nationally developed
guidelines in analysis process is much easier with it.
Considering all above, as the main conclusion, it can be recommended to adopt the
Euro code with recommendations provided by the research " Developing national
guidelines for seismic analysis and design of (Engineered) buildings in Sri Lanka
"conducted by the University of Moratuwa, Sri Lanka, for seismic analysis and
design process of buildings in Sri Lanka.
167
REFERENCES
[2] AS 1170.1-1989 Australian Standard: SAA Loading Code, Part 1: Dead and
live loads and load combinations.
[4] IS 1893(Part 1) : 2002 Indian Stan Standard: Criteria for earthquake resistant
design of structures, Part 1: General provisions and buildings (Fifth
Revision).
[7] Murat Saatcioglu and JagMohan Humar, "Dynamic analysis of buildings for
earthquake resistant design".
[8] Sudhir K Jain, " Review of Indian seismic code IS 1893 (Part 1) : 2002.
168
[12] K.S. Vipin, P. Anbazhagan and T.G. Sitharam , "Estimation of peak ground
acceleration for South India with local site effects: Probabilistic approach".
[13] Richard Fenwick, David Lau and Barry Davidson, "A comparison of the
seismic design requirements in the New Zealand loading standard with other
major design codes".
[14] Pravin Ashok Shirule and Bharti V. Mahajan "Response Spectrum Analysis
of Asymmetrical Building"
[15] Yogendra Singh, Vijay Namdev and Dominic H. Lang "A comparative Study
of Code Provisions for Ductile RC Buildings".
[16] P.P.Tapkire and Saeed J.Birajdar "Comparative study of High Rise Building
using Indian Standards and Euro Standards under Seismic Forces".
[18] Mehul J. Bhavsar, Kavita N. Choksi, Sejal K. Bhatt and Shrenik K. Shah "
Comparative Study of typical R.C. building using INDIAN STANDARDS
and EURU STANDARDS under seismic forces".
169
APPENDIX A : BASIC DETAILS OF BUILDING - A
A1. Eighteen storied residential apartment building
As the first case study, the selected building is a 18 storied reinforced concrete
apartment building, which includes a ground floor and 17 above ground floors,
where the ground floor up to fourth floor were used for parking purposes. Typical
floor plan and a schematic cross section showing the dimension of the building in
plan and elevation are given in Fig. A1 and A2 respectively. The total height of the
building above the ground level is 71.2m and the plan dimension are29.49m x
19.38m
The main structural system consists of concrete frames and shear walls, whereas
unreinforced masonry walls are used as partition walls.
At fifth floor level, the columns located at grid C1 and E1 on grid 1 have moved
along grid 1 and the columns at grid A3, C1 and E1 on grid 8 have been shifted along
grid 8 and also the columns grid H and K on grid 3 have been moved to grid 2. All
the columns then continued up to roof level. Similarly, the shear walls located
between grid E1 to H on grid 1 and C1 to J on grid 8 terminates at 5th floor level.
Also the shear wall between grids D1 to F1 have been moved from grid 3 to 2 from
the fifth floor onwards.
The structure has been designed with C30 concrete, except the columns from ground
floor up to sixth floor slab level, where C40 concrete was used.
All analysis were performed with the ETABS software (CSI 2002 ETABS Integrated
Building Design Software, Computers & Structures Inc. Berkeley) on a three
dimensional (spatial) mathematical model.
170
Figure A1: Plan View - Ground floor
174
Figure A8: Cross section A-A of the buildings
175
Table A1 :Material properties used in the analysis
Material Properties
Strength Density
Material Modulus of elasticity (kN/mm2)
(N/mm2) (kN/m3)
Concrete (C30) 30 24 26
Concrete (C40) 40 24 28
Steel 460 - -
Masonry - 22 -
Live Load
From first floor up to fourth floor 3.0 kN/m2
176
Table A3 : Approximate calculation of dead load on the test buildings
177
Table A3 : Approximate calculation of dead load on the test buildings (Contd.)
178
Table A4 : Approximate calculation of imposed load on the test buildings
Imposed Load
Refer Table A6
o The torsional radius shall be larger than the radius of the gyration of the
floor mass in plan
According to Table A6, the selected building does not fulfill this requirement. The
building was considered as torsionally flexible.
180
Table A6 :Structural eccentricity, torsional radius and radii of gyration in each
horizontal direction
181
In order to determine the structural eccentricity using the method above, computer
analysis of the spatial model of the building is performed. In this analysis, static
loads, Fix,Fiy and Miof same magnitude are applied at the centre of mass of floor level
i and the rotations of floors about vertical axis, Rz,i, due to each static load cases are
obtained. The results obtained from the computer analysis for the test building
including the eccentricities in both directions X and Y at tech floor level are shown
in Table A2.
The torsional radius rx (ry) is defined as the square root of the ratio of torsional
stiffness (KM) to the lateral stiffness in one direction Ky (Kx). It can be calculated
from the computer analysis using the expression;
rx (ry) =
(A.3)
182
The values correspond to each parameter in the above expression obtained from the
computer analysis are given in Table A1.3. The torsional radii, rx and ry are also
given in the table.
A2.1.1.1.3. Radius of gyration of the floor mass in plan (lx and ly)
The radius of gyration is defined as the square root of the ratio of the polar moment
of inertia to the mass, the polar moment of inertia being calculated about the centre
of mass. The manual for the seismic design of steel and concrete building to Euro
code 8 gives an expression for the radius of gyration (ls) applied to a rectangular
building of side lengths of l and b, and a uniform mass distribution as,
(A.4)
For the test building, the radius of gyration is calculated as shown in Table A9.
183
Table A9 :Radius of gyration
Clause 4.2.3.3
184
APPENDIX B : BASIC DETAILS OF BUILDING - B
B.1. Fourteen storied residential apartment building
The selected building is a 14 storied reinforced concrete apartment building, which
includes the ground floor and 13 above ground floors. Typical floor plan and a
schematic cross section showing the dimension of the building in plan and elevation
are given in Fig. B1 and B2 respectively. The total height of the building above the
ground level is 46.3m and the plan dimension are 44.3m x 20.6m
The main structural system consists of concrete frame with shear walls, whereas
unreinforced masonry walls are used as partition walls.
At first floor level, the columns located at grid B‟-1, B‟-2, B, B‟4 and B,-5 move on
to grids B-1, B-2, B-4 and B-5 .
All analysis were performed with the ETABS software (CSI 2002 ETABS Integrated
Building Design Software, Computers & Structures Inc. Berkeley) on a three
dimensional (spatial) mathematical model.
185
Figure B1: Plan View - Ground floor
186
Figure B2 : Plan View - First floor
187
Figure B3 : Plan View – 2nd to 13th floor
188
Figure B4 : Plan View – Roof floor
189
Figure B5 : Cross section A-A of the buildings
Material Properties
Strength Density
Material Modulus of elasticity (kN/mm2)
(N/mm2) (kN/m3)
Concrete (C30) 30 24 26
Concrete (C40) 40 24 28
Steel 460 - -
Masonry - 22 -
190
Table B2 : Design loads used in the analysis
Live Load
From first floor up to roof floor 2.0 kN/m2
Superimposed Dead Load
th
Finishes -From first floor up to 13 floor 1.5 kN/m2
Finishes –Roof floor 2.4 kN/m2
Masonry walls-From first floor up to thirteenth floor 2.5 kN/m2
191
Table B3 : Approximate calculation of dead load of the test building
192
Table B3 : Approximate calculation of dead load of the test building (Contd.)
193
Table B3 : Approximate calculation of dead load of the test building (Contd.)
194
Table B3 : Approximate calculation of dead load of the test building (Contd.)
195
Table B3 : Approximate calculation of dead load of the test building (Contd.)
196
Table B4 : Approximate calculation of imposed load of the test buildings
Refer Table B6
o The torsional radius shall be larger than the radius of the gyration of the
floor mass in plan
According to Table B6, the selected building does not fulfill this requirement. The
building was considered as torsionally flexible.
198
B2.1.1.1 Determining the structural eccentricities, torsional radii
and radii of gyration
Structural eccentricities and torsional radii are calculated using the same method as
described in A2.1.1.1 under the building A. The results are tabulated as below.
199
Table B9 : Radius of gyration
Clause 4.2.3.3
200
APPENDIX C : BASIC DETAILS OF BUILDING - C
C1. Ten storied residential apartment building
The selected building is a 10 storied reinforced concrete apartment building, which
includes the ground floor and 9 above ground floors. Typical floor plan and a
schematic cross section showing the dimension of the building in plan and elevation
are given in Fig. C1 and C2 respectively. The total height of the building above the
ground level is 31.46m and the plan dimensions are 41.3m x 25.6m
The main structural system consists of concrete frame shear walls, whereas
unreinforced masonry walls are used as partition walls..
All analysis was performed with the ETABS software (CSI 2002 ETABS Integrated
Building Design Software, Computers & Structures Inc. Berkeley) on a three
dimensional (spatial) mathematical model.
201
Figure C2: Plan View - Typical Floor
Strength Density
Material Modulus of elasticity (kN/mm2)
(N/mm2) (kN/m3)
Concrete (C25) 25 24 24
Steel 460 - -
Masonry - 22 -
Live Load
From first floor up to roof floor 2.0 kN/m2
Superimposed Dead Load
th
Finishes -From first floor up to 9 floor 1.5 kN/m2
Finishes –Roof floor 2.4 kN/m2
th
Masonry walls-From first floor up to 9 floor 2.5 kN/m2
202
Table C3 : Approximate calculation of dead load on the test building
203
Table C3 : Approximate calculation of dead load on the test building (Contd.)
204
Table C4 : Approximate calculation of imposed load on the test buildings
205
o The in-plan stiffness of the building shall be sufficiently large in
comparison with the lateral stiffness of the vertical structural elements
The in-situ concrete floor slab of thickness 125mmconnected to the lateral
load resisting system proves that the lateral stiffness of the building is
large in comparison with the vertical stiffness of the test building.
Refer Table C6
o The torsional radius shall be larger than the radius of the gyration of the
floor mass in plan
According to Table C6, the selected building does not fulfill this requirement. The
building was considered as torsionally fleixible
206
C2.1.1.1 Determining the structural eccentricities, torsional radii
and radii of gyration
Structural eccentricities and torsional radii have been calculated using the same
method as described in A2.1.1.1 under the building A. The results are tabulated as
below.
207
Table C9 : Radius of gyration
Clause 4.2.3.3
In this building, all the lateral load resisting system run without interruption from
foundation to the top. Also both the lateral stiffness and the mass of the individual
storeys remain constant or reduced gradually. Further, the ratio of the actual storey
resistance to the resistance required by the analysis do not vary disproportionately
between adjacent storeys. Since these requirements have been fulfilled in the case of
investigated building, the building was considered as regular in elevation.
208