Model 225XL

Electraray® Hazardous Location LED Warning


Light
2561351 Rev F2 1123

Limited Warranty: This product’s limited warranty can be T-Code at Max Ambient Temperature
found at www.fedsig.com/SSG-Warranty
UL/cUL Hazardous Location Rating 40°C 55°C 66°C
SAFETY MESSAGES TO INSTALLERS AND USERS : Class I, Division 2, Groups A, B, C, D T6 T5 T4A
Products should be installed by a licensed electrician and
follow all safety instructions. Failure to do so may result Class II, Division 2, Groups F, G T6 T6 T6
in property damage, serious injury, or death.
Class III T6 T6 T6
• To avoid electrical shock hazards, do not connect Installation
wires when power is applied.
• To be an effective warning device, this product
produces bright light that could be hazardous to WARNING - EXPLOSION HAZARD: Do not install the unit
eyesight. Do not stare directly at the light. Rapid in a hazardous location if the operating temperature
flashing could induce photosensitive epilepsy. exceeds the atmosphere’s ignition temperature.

• Never alter the unit in any manner. Safety in Unpacking the Device: After unpacking the device,
hazardous locations may be endangered if additional examine it for damage and verify the parts. The unit
openings or alternations are made. comes with one 225XL assembled unit with flying leads. If
• WARNING - EXPLOSION HAZARD: Do not disconnect a part is missing or damaged, do not attempt to install it;
while circuit is live or unless the area is known to be contact Federal Signal Customer Support.
free of ignitable concentrations.
Figure 1 Exploded view
OVERVIEW - The model 225XL hazardous location
warning light is available in 24 VAC/DC or self-detecting Elliptical
120-240 VAC. The unit comes standard in flashing mode Outer Dome
and is field-configurable to steady. with 12"
Curvature
Radius
This device is intended for permanent installation
and operation in accordance with Title 46, Code of
Regulations, Parts 110-113, or Title 33, Code of Federal
Regulations, Part 183, Sub-part I, Section 183.410, and the Fresnel
Lens
applicable requirements of the American Boat and Yacht
PCBA
Council, Inc. and/or ANSI/NFPA 302, “Fire Protection
Standard for Pleasure and Commercial Motor Craft.”
Silicone
Gasket
Certifications and Ratings
• UL and cUL Listed for Class I, Division 2, Groups A, B, Zinc Alloy
C and D; Class II Division 2, Groups F and G; Class III;
E-coated
Base
or non-hazardous locations.
• Type 4X, IP66 enclosure. Indoor or outdoor use.
Elliptical
• IP69K Compliant 5.5"/ 139.7 mm Outer Dome
with 12"
• Marine Listed Curvature
Radius
• Model 225XLis NSF Certified (dome-up) for Splash
7.5"/ 190.5 mm

Zones and Non-food Zones to NSF/ANSI 2: Food LED


Lamp
Equipment. Inner
• Electrical ratings: 0.38A (24VAC/DC), 0.21A
Fresnel
Lens
(120VAC), 0.13A (240VAC).
1/2"
• Certified Operating Temperature: -58°F to 150°F NPT Pipe
Mount
(-50°C to 66°C).
Mounting the Device: 225XL comes standard to mount Changing the Flash Pattern from Flashing
1/2” NPT threaded pipe. (default) to Steady
To comply with NEC Section 300-14, which requires a 1. Find and locate J3 mini jumper on the board
minimum of 6” of free conductor at a junction. The pipe
Figure 3 Jumper location
used to join the unit to a splice box should be no longer
than 10”.

J3 Jumper Location
Wall mounting bracket LHWB is sold separately and is not

Steady
Flash
NSF Certified.

• Pipe Mount: Feed wires through the pipe and turn


clockwise to tighten. To prevent the connection from
loosening, tighten the fixture to a minimum of Bottom View

5 ft-lb (6.8 Nm) after threading onto the pipe. 2. Switch jumper from flash to steady

Figure 2 Pipe mounting Testing and Operating


AC
After installation, test the system to verify that each
DC
Beacon Beacon signal operates and establish a program for periodic
1/2" conduit testing of the device. Provide copy of these instructions
1/2" conduit (not supplied) to all operating personnel.
(not supplied)
Black to Line
(Black to (L or L1)
Negative White to Neutral Maintenance and Service
Red to (N or L2)
Positive)
Green/yellow to Technical Assistance: Contact our Technical Support
Earth (Ground)
Wire nuts Wire nuts Team at +1 708-587-3587 or signalsupport@fedsig.com.
(not supplied) (not supplied)
Junction box Junction box Repair Service: A return authorization is required. Contact
(not supplied) (not supplied)
your Authorized Distributor or Federal Signal Customer
Support. Defective products under warranty will be
repaired or replaced at Federal Signal’s discretion.
ELECTRICAL CONNECTIONS: To avoid electrical shock,
do not connect wires when circuits are energized. Wiring Product Returns: Returns require authorization from
must comply to code in the country of use. Federal Signal. Contact your Authorized Distributor for
more information on our return policy or to request a
• 24 VAC/DC Models: Connect the red (+) lead to the return.
positive or the phase (hot) side of the power source
and the black (-) lead to the negative or common
side of the power source.
• 120-240 VAC 50/60 Hz Models: Connect the black
lead to the phase (hot) side of the power source and
the white lead to the common (neutral) side of the
power source. If required by local building codes,
the green/yellow lead in the housing is provided for
connection to earth ground.

2645 Federal Signal Drive, University Park, Illinois 60484


Additional translations available at signaling.fedsig.com
Traducciones adicionales disponibles en signaling.fedsig.com
Customer Support 1-800-344-4634+1-708-534-4756, iordersup@fedsig.com
Technical Support 1-800-755-7621+1-708-587-3587, signalsupport@fedsig.com
signaling.fedsig.com

2 Federal Signal signaling.fedsig.com

You might also like