1.NOTE-1
1.NOTE-1
1.NOTE-1
CONCEPT
We can think of the amount of water flowing through the hose from the tank as current. The higher
the pressure, the higher the flow, and vice-versa. With water, we would measure the volume of the
water flowing through the hose over a certain period of time. With electricity, we measure the
amount of charge flowing through the circuit over a period of time. Current is measured in Amperes
(usually just referred to as "Amps"). An ampere is defined as 6.241*10^18 electrons (1 Coulomb) per
second passing through a point in a circuit. Amps are represented in equations by the letter "I".
Let's say now that we have two tanks, each with a hose coming from the bottom. Each tank has the
exact same amount of water, but the hose on one tank is narrower than the hose on the other.
We measure the same amount of pressure at the end of either hose, but when the water begins to
flow, the flow rate of the water in the tank with the narrower hose will be less than the flow rate of the
water in the tank with the wider hose. In electrical terms, the current through the narrower hose is
less than the current through the wider hose. If we want the flow to be the same through both hoses,
we have to increase the amount of water (charge) in the tank with the narrower hose.
This increases the pressure (voltage) at the end of the narrower hose, pushing more water through
the tank. This is analogous to an increase in voltage that causes an increase in current.
Now we're starting to see the relationship between voltage and current. But there is a third factor to
be considered here: the width of the hose. In this analogy, the width of the hose is the resistance.
This means we need to add another term to our model:
In short, MCB is a device for overload and short circuit protection. They are used in residential &
commercial areas. Just like we spend the time to make a thorough check before buying appliances
like washing machines or refrigerators, we must also research about Miniature Circuit Breakers.
An MCB is a better alternative to a Fuse since it does not require replacement once an overload is
detected. Unlike a fuse, an MCB can be easily operated and thus offers improved operational safety
and greater convenience without incurring a large operating cost. They are used to protect lower
current circuits and have the following specifications
MCBs are classified into different types according to tripping over the range of fault current. The
important MCB types are as follows:
1. Type B MCB
2. Type C MCB
3. Type D MCB
4. Type K MCB
5. Type Z MCB
The tripping current and operating time of each of the above MCB types are given in the table
below.
Earthing Resistance:
Earthing Resistance for Single Pit=5Ω ,Earthing Grid=0.5Ω
As per NEC 1985 Earthing Resistance should be <5Ω.
Voltage between Neutral and Earth <=2 Volts
Resistance between Neutral and Earth <=1Ω
Creepage Distance=18 to 22mm/KV (Moderate Polluted Air) or
Creepage Distance=25 to 33mm/KV (Highly Polluted Air)
Insulation Resistance:
Insulation Resistance Value for Rotating Machine= (KV+1) MΩ.
Insulation Resistance Value for Motor (IS 732) = ((20xVoltage (L-L)) / (1000+ (2xKW)).
Insulation Resistance Value for Equipment (<1KV) = Minimum 1 MΩ.
Insulation Resistance Value for Equipment (>1KV) = KV 1 MΩ per 1KV.
Insulation Resistance Value for Panel = 2 x KV rating of the panel.
Min Insulation Resistance Value (Domestic) = 50 MΩ / No of Points. (All Electrical Points with Electrical fitting
& Plugs). Should be less than 0.5 MΩ
Min Insulation Resistance Value (Commercial) = 100 MΩ / No of Points. (All Electrical Points without fitting &
Plugs).Should be less than 0.5 MΩ.
Test Voltage (A.C) for Meggering = (2X Name Plate Voltage) +1000
Test Voltage (D.C) for Meggering = (2X Name Plate Voltage).
Submersible Pump Take 0.4 KWH of extra Energy at 1 meter drop of Water.
Lighting Arrestor:
Arrestor have Two Rating=
(1) MCOV=Max. Continuous Line to Ground Operating Voltage.
(2) Duty Cycle Voltage. (Duty Cycle Voltage>MCOV).
Transformer:
Current Rating of Transformer=KVAx1.4
Short Circuit Current of T.C /Generator= Current Rating / % Impedance
No Load Current of Transformer=<2% of Transformer Rated current
Capacitor Current (Ic)=KVAR / 1.732xVolt (Phase-Phase)
Typically the local utility provides transformers rated up to 500kVA For maximum connected load of 99kW,
Typically the local utility provides transformers rated up to 1250kVA For maximum connected load of 150kW.
The diversity they would apply to apartments is around 60%
Maximum HT (11kV) connected load will be around 4.5MVA per circuit.
4No. earth pits per transformer (2No. for body and 2No. for neutral earthing),
Clearances, approx.1000mm around TC allow for transformer movement for replacement.
Diesel Generator:
Diesel Generator Set Produces=3.87 Units (KWH) in 1 Litter of Diesel.
Requirement Area of Diesel Generator = for 25KW to 48KW=56 Sq.meter, 100KW=65 Sq.meter.
DG less than or equal to 1000kVA must be in a canopy.
DG greater 1000kVA can either be in a canopy or skid mounted in an acoustically treated room
DG noise levels to be less than 75dBA @ 1meter.
DG fuel storage tanks should be a maximum of 990 Litter per unit Storage tanks above this level will trigger
more stringent explosion protection provision.
Current Transformer:
Nomenclature of CT:
Ratio: input / output current ratio
Burden (VA): total burden including pilot wires. (2.5, 5, 10, 15 and 30VA.)
Class: Accuracy required for operation (Metering: 0.2, 0.5, 1 or 3, Protection: 5, 10, 15, 20, 30).
Accuracy Limit Factor:
Nomenclature of CT: Ratio, VA Burden, Accuracy Class, Accuracy Limit Factor.Example: 1600/5, 15VA
5P10 (Ratio: 1600/5, Burden: 15VA, Accuracy Class: 5P, ALF: 10)
As per IEEE Metering CT: 0.3B0.1 rated Metering CT is accurate to 0.3 percent if the connected secondary
burden if impedance does not exceed 0.1 ohms.
As per IEEE Relaying (Protection) CT: 2.5C100 Relaying CT is accurate within 2.5 percent if the secondary
burden is less than 1.0 ohm (100 volts/100A).
Voltage Variation
> 33 KV (-) 12.5% to (+) 10%
Insulation Class:
Insulation Temperature
Class A 105°C
Class E 120°C
Class B 130°C
Class F 155°C
Class H 180°C
Class N 200°C
Facing of Meter Box Meter Box should be at front area of Building at Ground Floor.
For Commercial 1500 watt per 100 Sq. foot of the constructed area
PART-4
33 KV 3.7 Meter
11 KV 2.7 Meter
For Phase Bus bar Copper 160 Amp / Sq.cm or 1000Amp / Sq.inch
For Neutral Bus bar Same as Phase Bus bar up to 200 Amp than Size of Neutral Bus bar is at least
half of Phase Bus bar.
IR Value of Transformer:
IR Value of Transformer
Voltage 30°C 40°C 50°C
>66KV 600MΩ 300MΩ 150MΩ
22KV to 33KV 500MΩ 250MΩ 125MΩ
6.6KV to 11KV 400MΩ 200MΩ 100MΩ
<6.6KV 200MΩ 100MΩ 50MΩ
415V 100MΩ 50MΩ 20MΩ
RCCB/ELCB 6A,10A,16A,20A,32A,40A,50A,63A,80A,100A
TPIC (Triple Pole Iron Clad) main 30A, 60A, 100A, 200 A For 500 V
switch
TPN main switch 30A, 60A, 100A, 200A, 300 A For 500 V
TPNMCB 16A, 32A,63A For 500 V, beyond this TPNMCCB: 100A, 200A,
300A, 500 A For 660 V
PART-5
PART-6
Transformer Earthing Wire / Strip Size:
Size of T.C or DG Body Earthing Neutral Earthing
<315 KVA 25×3 mm Cu / 40×6 mm GI Strip 25×3 mm Cu Strip
315 KVA to 500 KVA 25×3 mm Cu / 40×6 mm GI Strip 25×3 mm Cu Strip
500 KVA to 750 KVA 25×3 mm Cu / 40×6 mm GI Strip 40×3 mm Cu Strip
750 KVA to 1000 KVA 25×3 mm Cu / 40×6 mm GI Strip 50×3 mm Cu Strip
1X160 14 90 9
Type of Contactor:
Type Application
AC1 Non Inductive Load or Slightly Inductive Load
AC2 Slip Ring Motor, Starting, Switching OFF
AC3 Squirrel Cage Motor
AC4,AC5,AC5a, Rapid Start & Rapid Stop
AC5b,AC6a
AC 5a Auxiliary Control circuit
AC 5b Electrical discharge Lamp
AC 6a Electrical Incandescent Lamp
AC 6b Transformer Switching
AC 7a Switching of Capacitor Bank
AC 7b Slightly Inductive Load in Household
AC 5a Motor Load in Household
AC 8a Hermetic refrigerant compressor motor with Manual Reset O/L Relay
AC 8b Hermetic refrigerant compressor motor with Automatic Reset O/L Relay
AC 12 Control of Resistive Load & Solid State Load
AC 13 Control of Resistive Load & Solid State Load with Transformer Isolation
AC 14 Control of small Electro Magnetic Load (<72 VA)
AC 15 Control of Electro Magnetic Load (>72 VA)
Contactor Coil:
Coil Voltage Suffix
24 Volt T
48 Volt W
110 to 127 Volt A
220 to 240 Volt B
277 Volt H
380 to 415 Volt L
Types of DB:
SPN DB
TPN DB
SL. NO Types of DB Incoming Outgoing Neutral Bar Earthing Bar
1 2 way SPN
2 4 way SPN
3 6 way SPN
4 8 way SPN
5 10 way SPN
6 12 way SPN
7 14 way SPN
8 16 way SPN
9 18 way SPN
10 20 way SPN
11
12
13
14
Types of GI BOX:
Types of Conduit: