eskkkd
eskkkd
eskkkd
INPUT
Current INSTALLATION
4 – 20 mA DC Supply voltage
Operational voltage range: Rating ±10 %
50/60 ±2 Hz
OUTPUT
Approx. 2 VA (KD-24)
Current
Approx. 3.2 VA (KD-42)
4 – 20 mA DC
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
[2] POWER INPUT Mounting: Surface or DIN rail
AC Power Weight: 300 g (0.66 lb)
B: 100 V AC
KD SPECIFICATIONS ES-3592 Rev.10 Page 1/3
MG CO., LTD.
www.mgco.jp
MODEL: KD
PERFORMANCE in percentage of span
Line voltage effect
KD-24: ±0.5 % over voltage range
KD-42: ±1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input or output
to power to ground)
[.79]
20
DIN RAIL
35mm wide 6 5 4 3
80 [3.15]
80 [3.15]
2–4.5 [.18] dia.
MTG HOLE
15 [.59] deep
7 8 1 2
8–M3.5
SCREW
50 [1.97] 103 [4.06] 40 [1.57]
123 [4.84] (3.3 [.13]) 50 [1.97]
6 5 4 3
12 (.47)
7 8 1 2
MG CO., LTD.
www.mgco.jp
MODEL: KD
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
2-WIRE
TRANSMITTER
– – 6 * +
3
R OUTPUT 1
Current
+ + 1 4 –
Limiter
**
5 +
OUTPUT 2
2 –
7 U
POWER
8 V
Base Socket
MG CO., LTD.
www.mgco.jp