Repeater Power Supply and

D1054 Trip Amplifiers DIN-Rail


Model D1054S

Characteristics: Technical Data:


General Description: Supply: 12-24 Vdc nom (10 to 30 Vdc) reverse polarity protected,
The single channel DIN Rail Repeater Power Supply and Trip Amplifier D1054S, ripple within voltage limits ≤ 5 Vpp.
provides a fully floating dc supply for energizing conventional 2 wires 4-20 mA Current consumption @ 24 V: 90 mA with 20 mA input/output and relays energized.
transmitters, or separately powered 3, 4 wires 4-20, 0-20 mA transmitters located in Current consumption @ 12 V: 190 mA with 20 mA input/output and relays energized.
Hazardous Area, and repeats the current in floating circuit to drive a Safe Area load. Power dissipation: 1.7 W with 24 V supply, 20 mA input/output and relays energized.
Output signal can be direct or reverse. Max. power consumption: at 30 V supply voltage, input short circuit,
The circuit allows bi-directional communication signals, for Hart-Smart transmitters. overload condition, relays energized and PPC1090 connected, 2.9 W.
Two independent Alarm Trip Amplifiers are also provided. Each alarm energizes, or Isolation (Test Voltage): I.S. In/Outs 1.5 KV; I.S. In/Supply 1.5 KV;
de-energizes, an SPST relay for high, low, low-startup or burnout alarm functions. Analog Out/Supply 500 V; Analog Out/Alarm Outs 1.5 KV;
The two alarm relays trip points are settable over the entire input signal range. Alarm Outs/Supply 1.5 KV; Alarm Out/Alarm Out 1.5 KV.
Function: Input: 0/4 to 20 mA (separately powered input, voltage drop ≤ 1 V) or
1 channel I.S. analog input for 2 wires loop powered or separately powered Smart 4 to 20 mA (2 wire Tx current limited at ≈ 25 mA).
transmitters, provides 3 port isolation (input/output/supply) and current (source mode) or Integration time: 100 ms.
voltage output signal. Resolution/Visualization: 1 µA.
In addition it provides two SPST relay alarm contacts with adjustable alarm trip point. Input range: 0 to +22 mA.
Signalling LEDs: Transmitter line voltage: ≥ 15.0 V at 20 mA with max. 20 mVrms ripple
Power supply indication (green), burnout (red), alarm A (red), alarm B (red). on 0.5 to 40 KHz frequency band.
Configurability: Burnout: enabled or disabled. Analog output can be programmed to detect burnout
Totally software configurable, no jumpers or switches, mA or V output signal, condition with downscale or highscale forcing.
linear or reverse, alarm trip point, high, low, low-startup or burnout alarm mode, Alarms can be programmed to detect burnout condition.
NE/ND relay operation, hysteresis, delay time, by GM Pocket Portable Configurator Burnout range: low and high separated trip point value programmable between
PPC1090, powered by the unit or configured by PC via RS-232 serial line with
-5 to +25 mA.
PPC1092 Adapter and SWC1090 Configurator software.
Output: 0/4 to 20 mA, on max. 600 Ω load source mode, current limited at 22 mA or
To operate PPC1090 or PPC1092 refer to instruction manual.
0/1 to 5 V or 0/2 to 10 V signal, limited at 11 V.
Smart Communication Frequency Band:
0.5 to 40 KHz within 3 dB (Hart and higher frequency protocols), Resolution: 1 µA current output or 1 mV voltage output.
only with mA direct current output. Transfer characteristic: linear or reverse.
EMC: Response time: ≤ 50 ms (10 to 90 % step change).
Fully compliant with CE marking applicable requirements. Output ripple: ≤ 20 mVrms on 250 Ω communication load on 0.5 to 40 KHz band.
Frequency response: 0.5 to 40 KHz bidirectional within 3 dB
Front Panel and Features: (Hart and higher frequency protocols) only with mA direct current output.
Alarm:
Trip point range: within rated limits of input sensor (see input for step resolution).
1 2 3 4 • Input from Zone 0 (Zone 20), Division 1, ON-OFF delay time: 0 to 1000 s, 100 ms step, separate setting.
installation in Zone 2, Division 2. Hysteresis: 0 to 5 mA (see input for step resolution).
• 4-20 mA loop or 0/4-20 mA externaly powered Output: voltage free SPST relay contact.
5 6 7 8 Input Signal. Contact rating: 2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load).
• 0/4-20 mA, 0/1-5 V, 0/2-10 V Output Signal Performance: Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
linear or reverse. Input:
Calibration and linearity accuracy: ≤ ± 20 µA
• Wide Band Smart Communication, Temperature influence: ≤ ± 1 µA of input for a 1 °C change.
Hart compatible. Analog Output:
• Input and Output short circuit proof. Calibration accuracy: ≤ ± 0.1 % of full scale.
C • Two independent trip amplifiers. Linearity error: ≤ ± 0.05 % of full scale.
O • Output for burnout detection. Supply voltage influence: ≤ ± 0.05 % of full scale for a min to max supply change.
Load influence: ≤ ± 0.05 % of full scale for a 0 to 100 % load resistance change.
N • Common burnout detection available when Temperature influence: ≤ ± 0.01 % on zero and span for a 1 °C change.
F using Power Bus enclosure. Compatibility:
PWR BURN • High Accuracy, µP controlled A/D converter. CE mark compliant, conforms to 94/9/EC Atex Directive and to
• Three port isolation, Input/Output/Supply. 89/336/CEE EMC Directive.
• EMC Compatibility to EN61000-6-2, EN61000-6-4. Environmental conditions: Operating: temperature limits -20 to + 60 °C,
A B relative humidity max 90 % non condensing, up to 35 °C.
ALARM • Fully programmable operating parameters. Storage: temperature limits – 45 to + 80 °C.
• ATEX, IECEx, UL & C-UL, FM & FM-C, Safety Description:
Russian Certifications.
D1054 • Type Approval Certificate DNV A-10169,
KR ITA20769-EL001 for marine applications. II (1) GD [EEx ia] IIC, I (M2) [EEx ia] I, II 3G Ex nA IIC T4, [Ex ia] IIC
• High Reliability, SMD components. associated electrical apparatus.
Uo/Voc = 26.3 V, Io/Isc = 91 mA, Po/Po = 597 mW at terminals 14-15.
• High Density, one channel, 2 trips per unit. Uo/Voc = 1.1 V, Io/Isc = 56 mA, Po/Po = 16 mW at terminals 15-16.
• Simplified installation using standard Ui/Vmax = 30 V, Ii/Imax = 128 mA, Ci = 1.05 nF, Li = 0 nH at terminals 15-16.
DIN Rail and plug-in terminal blocks. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60°C.
13 14 15 16
• 250 Vrms (Um) max. voltage allowed to the Approvals:
instruments associated with the barrier. DNV-2004-OSL-ATEX-0199 conforms to EN50014, EN50020, EN50284,
IECEx DNV 07.0001 conforms to IEC60079-0, IEC60079-11,
GM International CRR028 conforms to EN60079-0, EN60079-15,
Ordering Information: UL & C-UL E222308 conforms to UL913 (Div.1), UL 60079-0 (General, All Zones),
UL60079-11 (Intrinsic Safety “i” Zones 0 & 1) for UL and
Model: D1054S CSA-C22.2 No.157-92 (Div.1), CSA-E60079-0 (General, All Zones),
CSA-E60079-11 (Intrinsic Safety “i” Zones 0 & 1) for C-UL,
Power Bus enclosure /B FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611, 3810 and
C22.2 No.142, C22.2 No.157, C22.2 No.213, E60079-0, E60079-11, E60079-15,
Operating parameters are programmable by the GM Pocket Portable Configurator Russia according to GOST 12.2.007.0-75, R 51330.0-99, R 51330.10-99 [Exia] IIC X,
PPC1090 or via RS-232 serial line with PPC1092 Adapter and SWC1090 Configurator DNV A-10169, KR ITA20769-EL001 Type Approval Certificate for marine applications.
software. If the parameters are provided with the purchasing order the unit will be Mounting: T35 DIN Rail according to EN50022.
configured accordingly, otherwise the unit will be supplied with default parameters. Weight: about 175 g.
Connection: by polarized plug-in disconnect screw terminal blocks to accomodate
terminations up to 2.5 mm2.
Location: Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4,
Class I, Division 2, Groups A, B, C, D Temperature Code T4 and
Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
Protection class: IP 20.
Dimensions: Width 22.5 mm, Depth 99 mm, Height 114.5 mm.
Parameters Table: Image:
Safety Description Maximum External Parameters
Group Co/Ca Lo/La Lo/Ro
Cenelec (µF) (mH) (µH/Ω)
Terminals 14-15
Uo/Voc = 26.3 V IIC 0.095 4.3 59.6
Io/Isc = 91 mA IIB 0.738 17.2 238.4
Po/Po = 597 mW IIA 2.508 34.5 476.8
Terminals 15-16
Uo/Voc = 1.1 V IIC 100 11.3 2327
Io/Isc = 56 mA IIB 1000 45.3 9309
Po/Po = 16 mW IIA 1000 90.7 18618
NOTE for USA and Canada:
IIC equal to Gas Groups A, B, C, D, E, F and G
IIB equal to Gas Groups C, D, E, F and G
IIA equal to Gas Groups D, E, F and G

Function Diagram:
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC,
SAFE AREA, ZONE 2 GROUP IIC T4,
HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
CLASS I, ZONE 0, GROUP IIC

MODEL D1054S

3+
=
=
In 1 4 - Supply 12-24 Vdc
=
2 Wire Tx HHT
External 14 HHT Source I Source V
? +
Powered Tx = 1 + +
+ 15
I - 2 mA RL Out 1
V
16 = - -
-
5
6 Alarm A
Set A

7
8 Alarm B
Set B

Relay contact shown in de-energized position


Function Diagram:
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC,
SAFE AREA, ZONE 2 GROUP IIC T4,
HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
CLASS I, ZONE 0, GROUP IIC

MODEL D1054S

3+
=
=
In 1 4 - Supply 12-24 Vdc
=
2 Wire Tx HHT
External 14 HHT Source I Source V
? +
Powered Tx = 1 + +
+ 15
I - 2 mA RL Out 1
V
16 = - -
-
5
6 Alarm A
Set A

7
8 Alarm B
Set B

Relay contact shown in de-energized position


Friendly Configuration with SWC1090 Software and PPC1092 Adapter or Pocket Portable Configurator PPC1090:

Configuration Parameters:
INPUT SECTION: OUTPUT SECTION:
Input range is from 0 to +22 mA from loop powered or externally powered transmitter. Output: analog output type
Downscale: input value of measuring range corresponding to defined low output value.  4-20 mA current output range from 4 to 20 mA
Upscale: input value of measuring range corresponding to defined high output value.  0-20 mA current output range from 0 to 20 mA
Burnout Low: low burnout condition trip point value;  1-5 V voltage output range from 1 to 5 V
below this value a burnout fault condition is activated and the analog output is driven to  0-5 V voltage output range from 0 to 5 V
the configured state (see Burnout in Output Section).  2-10 V voltage output range from 2 to 10 V
Setting this value outside the measuring range will disable this function.  0-10 V voltage output range from 0 to 10 V
Burnout High: high burnout condition trip point value; Burnout: analog output burnout state
above this value a burnout fault condition is activated and the analog output is driven to  None burnout function is disabled;
the configured state (see Burnout in Output Section). analog output represents the input measure as configured
Setting this value outside the measuring range will disable this function.  Downscale analog output is forced at zero
 Upscale analog output is forced to 22 mA for current output or
11 V for voltage output
ALARM SECTION:
Type: alarm type configuration
 Off alarm functionality is disabled
 High alarm is set to high condition, the alarm output is triggered whenever
the input variable goes above the trip point value (Set)
 Low alarm is set to low condition, the alarm output is triggered whenever
the input variable goes below the trip point value (Set)
 Low & Sec alarm is set to low condition with start-up,
the alarm output is inhibited until the input variable goes above the
trip point value (Set); afterwards it behaves as a Low configuration;
typically used to solve start-up issues
 Burnout a burnout condition of the input triggers the alarm output
Set: input value of measuring range at which the alarm output is triggered
Hysteresis: alarm hysteresis value, valid range: 0 to 5 mA
ON Delay: time for which the input variable has to be in alarm condition before the
alarm output is triggered; configurable from 0 to 1000 seconds in steps of 100 ms.
OFF Delay: time for which the input variable has to be in normal condition before the
alarm output is deactivated; configurable from 0 to 1000 seconds in steps of 100 ms.
Relay: relay condition
 ND the relay is in normally de-energized condition,
it energizes (the output contact is closed) in alarm condition
 NE the relay is in normally energized condition,
it de-energizes (the output contact is opened) in alarm condition
BurnOut Oper: alarm status when a burnout condition is detected
 Nor the burnout detection on the alarm output is disabled,
the alarm follows the condition of the input variable
 Lock maintain the same alarm condition as before the burnout detection
 On the alarm condition is activated when a burnout is detected
 Off the alarm condition is deactivated when a burnout is detected

Each alarm output has independent configurations.