Advanced Structural Design Coursework
Advanced Structural Design Coursework
ADESH SHAHI
Submitted by: Student ID: 4232971
MSC Structural Engineering, FT, Sep, 2023-2024
TABLE OF CONTENT
✓ Introduction
✓ Assumptions & Steps
✓ Design Calculations
• Design of Plate Girder
• Design of Slab
• Design of Beam
✓ Lateral Stability
✓ Wind Analysis
✓ Foundation Design
✓ Appendix 1: Structural Drawings
✓ Appendix 2: Letter to Client
INTRODUCTION
In response to the outlined project requirements for the structural design of a new two-storey
building situated at Rotary St, London SE1 6LF, this report presents a comprehensive
conceptual scheme adhering to the client's brief and planning specifications. This project,
equivalent to RIBA stage 2, necessitates the development of a structural design encompassing
both the ground and first floors, as well as the roof, incorporating elements such as column
spacing, floor areas, and cantilever structures, while adhering to Eurocode standards.
The ground floor layout is designated for an entrance, café, and social space, with a minimum
headroom of 4 meters, necessitating a steel frame structure with provisions for ground bearing
slab and columns. A floor area of 1500 m² is allotted for the ground floor, with flexibility in
column placement, provided they remain within the specified spacing parameters.
Conversely, the first floor is designated for a lecture theatre accommodating new students,
necessitating a cantilever structure with a minimum cantilever of 5 meters on both sides. The
potential structural options include plate girders, trusses, or Vierendeel structures, with a floor
coverage area of 1200 m².
Furthermore, the roof design entails a lightweight structure comprising metal decking and
insulation, emphasizing efficiency and durability. Plate girders are designated for
accommodating transfer structures, facilitating seamless load distribution.
This report will delve into the conceptualization and development of the structural scheme,
incorporating preliminary calculations, wind load analysis, and plate girder design, all in
accordance with Eurocode standards. Additionally, professional-grade structural drawings,
along with a drawing register, will be provided to ensure clarity and coherence in the
presentation of the proposed design.
3. Column Spacing:
In accordance with client specifications, column spacing on the ground floor was established
at 5 meters in both directions. This decision adhered to the stipulated requirements, ensuring
that columns were neither too close together (less than 4.5 meters apart) nor too far apart
(more than 7.5 meters apart), thereby optimizing structural integrity and spatial
functionality.
Description Reference
• Material properties:
Yield stress of steel = fy = 355 N/mm2
• Partial factors for actions:
Partial factor for permanent actions = γG = 1.35
Partial factor for variable actions = γQ = 1.50 Table A1.2(B)
Reduction factor for permanent actions = ξ = 0.925
• Loading:
Dead Load
Finishes and metal decking = 1.20 kN/m2
Ceiling and services = 0.15 kN/m2
Live Load
Total Imposed Load = qk = 0.6 kN/m2
BS EN 1991-1
Taking 10m strip,
Total Imposed Load = qk = 0.6 x 10 = 6.0 kN/m
Factored Loads
Using this design load, I will draw shear force and bending
moment diagram for the plate girder.
Shear Force
and Bending
Moment
Diagram are
drawn using
MD Solids
software.
Now,
The minimum web thickness for plate girder in buildings usually
varies between10 mm to 20 mm.
So,
Assume web size as 2700 x 14.
• Section Classification:
Flange
235 235
ε= √ = √ = 0.812 Table 5.2 EC3
fyk 355
ignoring weld size in determination of plate width;
810 − 14
Cf = = 398 mm
2
Cf 398
= = 66.3
tf 6
Web
235 235
ε= √ = √ = 0.81
fyk 355 Table 5.2 EC3
ignoring weld size in determination of plate width;
Cw = 2700 mm
Cw 2700
= = 192.85
tw 14
2700
tw = = 10.8 mm
250
hw fyk Afc
tw ≥ ( ) ( ) √
k E Aw
Where
K = Section utilization in bending = 0.55 for class 3 and above
2706
Mf,Rd = (810 x 6 x 355) x
106
ℎ𝑤 2700
= = 192.86 > 72𝜀 BS EN 1993-1-
𝑡𝑤 14 5 Cl 5.2(1)
So, Web is categorized as slender web and thus, should be checked BS EN 1993-1-
against shear buckling. 5 Cl 5.3(3)
ƞfyw hw t w
Vb,Rd = Vbw,Rd + Vbf,Rd ≤
√3γM1 BS EN 1993-1-
5 Cl A.3(1)
In the above equation, I will ignore contribution of flange to shear
resistance.
2700
λ̅w = = 1.99
37.4 x 14 x 0.81 x √10.23
• Stiffener Design:
The stiffeners are spaced as shown in Fig. 3 below. The spacing of BS EN 1993-1-
stiffeners near the support is taken as 2500 mm whereas spacing at 5 Cl 9.2(8)
the center is set to 5000 mm for economy.
1.5ℎ𝑤 3 𝑡𝑤 3 𝑎
𝐼𝑠𝑡 ≥ 2
𝑓𝑜𝑟 < √2
𝑎 ℎ𝑤
𝑎
𝐼𝑠𝑡 ≥ 0.75ℎ𝑤 𝑡𝑤 3 𝑓𝑜𝑟 ≥ √2
ℎ𝑤
ε= √
235
= √
235
= 0.825
BS EN 10025-2
fyk 345
250 ≤ 257.4
𝑎
As ℎ = 2500 / 2700 = 0.923 < √2
𝑤
Now,
I 271.66 x 106
radius of gyration = is = √Ast = √ = 128.34 mm
s 16494
Now,
BS EN 1993-1-
𝐸 210000
𝜆1 = π√ = π√ = 77.50 5 Cl 9.4(2)
fy 345
BS EN 1993-1-
𝜆 Lcr /is 2025/128.34 5 Cl 6.3.1.2(4)
𝜆̅ = = = = 0.20
𝜆1 𝜆1 77.50
So, I provide the designed plate girders of following size in all span
for aesthetic purposes.
Flange = 810mm x 6mm
Web = 2700mm x 14mm
Description Reference
• Material properties:
Characteristics compressive strength of Concrete = fc = 32 N/mm2
Yield strength of steel reinforcement = fy = 500 N/mm2
Unit Weight of Concrete = 24 KN/m³
Diameter of Steel Reinforcement = 10 mm
Clear Cover for Concrete = 25 mm
• Loading:
Dead Load
Finishes to floor = 1.0 kN/m2
Ceiling and services = 0.15 kN/m2
Considering,
Thickness of proposed slab = 5000/30 = 166.67 mm
So,
Thickness of slab = 180 mm
Taking 1 strip,
Total Dead Load = gk = 5.47 x 1 = 5.47 kN/m
Live Load
Building category for lecture halls = C2 BS EN 1991-1
Table. 6.1
For C2 building,
Recommended Imposed Load = 3 – 4 kN/m2 Table. 6.2
Considering,
Total Imposed Load = qk = 3 .5 kN/m2
Taking 1m strip,
Total Imposed Load = qk = 3.5 x 1 = 3.5 kN/m
Factored Loads
Fd = 1.35 x 0.925 x 5.47+ 1.5 x 3.5 = 12.08 kN/m Eq. 6.10 (B)
• Slab Design :
For Steel Structures based in UK, It is recommended to use
Prestressed Precast Hollow Slabs Panels for their reliability and easy
installation. Based on the span lengths and the proposed loading, I have
calculated the slab thickness equal to 180mm with clear cover for
concrete equal to 25mm. So, I will check for different suppliers
catalogue, put my design values there and ask them to provide me the
desired slab precast panels for the proposed building. The designed data
will be as follow;
DESIGN OF BEAM:
• Material properties:
Yield stress of steel = fy = 355 N/mm2
Elastic Modulus of steel = E = 210000 N/mm2
• Loading:
Taking 5m effective width of beam for the dead and imposed loading
coming from floor slab,
Dead Load
Uniformly distributed load = gk = 13.675 kN/m
Live Load
Uniformly distributed load = qk = 8.75 kN/m
Factored Loads
Fd = 1.35 x 0.925 x 13.675+ 1.5 x 8.75 = 30.205 kN/m Eq. 6.10 (B)
VEd = 75.51 kN
• Member Checks:
The required section is to have a plastic modulus about the major axis
(y-y) that is higher than the following;
• Section Classification:
101.9 − 6 − 2 x 7.6
Cf = = 40.35 mm
2
Cf 40.35
= = 4.80
tf 8.4
Cw 225.2
= = 37.5
tw 6
So,
Section UB 254 x 102 x 25 Class 1
Basic requirement is
MEd
≤1 6.2.5
MC,Rd
So,
94.40
= 0.87 ≤ 1
108.63
Basic requirement is
VEd 6.2.6(1)
≤1
VC,Rd
Av is the shear area and for the rolled I section with load parallel to the
web is
= 1666.16 mm²
But not more than
Ƞ. hw . t w = 1 x 257.2 x 6 = 1543.2 mm²
So,
Av = 1543.2 mm²
Now,
1543.2 x 355/√3
VPl,Rd = x 10−3
1
VPl,Rd = 316.25 kN
Therefore,
75.51
= 0.24 ≤ 1
316.25
1 5 x 8.75 x 50004
w=( )( )
210000 x 3410 x 104 384
w = 9.94 mm
Given
This w = 9.94mm is less than 40mm.
So,
Use UB 254 x 102 x 25
LATERAL STABILITY:
Lateral stability is a critical aspect of structural design, particularly in tall or expansive
buildings where wind and seismic forces can exert significant lateral loads. In the context of
the proposed two-storey building, ensuring adequate lateral stability is essential to safeguard
against lateral displacement and maintain structural integrity. To address this, a comprehensive
strategy incorporating both horizontal and vertical bracing elements was devised.
• Horizontal Bracing:
Horizontal bracing serves to resist lateral forces induced by wind or seismic activity, preventing
excessive sway and maintaining the stability of the structure. In the design of the proposed
building, horizontal bracing was strategically deployed in external bays, where primary loads
are concentrated. By selectively placing horizontal bracing in these key locations, the bracing
system effectively channels lateral forces towards the building's perimeter, where they can be
efficiently dissipated into the foundation.
Location and Placement Horizontal bracing elements were positioned along the external walls
of the building, spanning between columns or structural members. This configuration ensures
that lateral forces are effectively transmitted from the upper floors to the ground, minimizing
sway and enhancing overall stability.
• Vertical Bracing:
Purpose and Function Vertical bracing elements function to resist lateral movement induced
by wind or seismic loads, preventing buckling and ensuring the structural integrity of the
building. By introducing vertical bracing within the central bay, lateral forces are effectively
redistributed, minimizing deformation and enhancing overall stability.The design of vertical
bracing systems takes into account factors such as bracing configuration, material selection,
and connection detailing. Bracing members are typically arranged in a cross-bracing or X-
bracing configuration, chosen for its effectiveness in resisting lateral forces while minimizing
interference with interior spaces.
Description Reference
• Assumptions:
Building is located
1. 100 km from coast
2. 2 km into town
3. 105 m above sea level
Calt = 1 + 0.001A[10/(0.6h)]0.2
Where
A = Altitude
h = Building height
Calt = 1.12
• Direction Factor:
Cdir = 1.0 Assume
• Displacement Height:
hdis = 0.0 m Assume
• Exposure Factor:
z = h - hdis
z = 8.0 - 0
z = 8.0 m
Ce = 2.2
• Correction Factor:
z = h - hdis
z = 8.0 - 0
z = 8.0 m
Cc = 0.84
q p = 706.65 Pa
Breadth of Building = 50 m
b + h = 50 + 8 = 58 m
Size factor zone = C
Using the above data in the following graph; I get
Co = 0.83
• Dynamic Factor:
Cd = 1.009
d = 8 + 2 = 10 m
Cf = 0.89
• Shadow Area:
Ash = h x b = 8 x 50 = 400 m²
Wind is a “Live Load”, thus has a load factor of 1.5 for ULS design.
EHF at each level are to be added to the wind loads. These are usually
0.5% of the gravity loads at that level.
Assuming that there are 2 braced bays in the direction of wind, one on
each face; each brace will take half load, i.e. 105.375 kN.
For each braced bay; all the wind load is resisted at its base.
Floor height = 4 m
Column Spacing = 5m
So,
Total force in brace = Fbase = √105.3752 + 84.32
Description Reference
FOUNDATION DESIGN:
• Assumptions:
Foundation type = Mat Foundation
The column is assumed to be pin-ended to the slab through base
plate.
Only Floor Loads are considered for base plate design.
• Material properties:
Characteristics compressive strength of Concrete = fc = 32 N/mm2
Yield strength of steel reinforcement = fy = 500 N/mm2
Unit Weight of Concrete = 24 KN/m³
No. of Columns = 77
Load taken by individual column = 9825/77 = 127.60 kN
Live Load
Live load of Roof = 0.60 kN/m2
Live load of First Floor = 3.50 kN/m2
Area of Roof = 1200 m²
Area of First Floor = 1500 m²
No. of Columns = 77
Load taken by individual column = 5970/77 = 77.50 kN
Factored Loads
NA 2.15
Fd = 1.35 x 0.925 x 127.60+ 1.5 x 77.50 = 275.60 kN BS EN 1992-1-1
NA 2 Table NA 1
• Column Details:
𝛼𝑜 𝑓𝑐
𝑓𝑜𝑑 =
𝛾𝐶
Where
αo = 0.85 for axial loading
So,
0.85 x 32
fod = = 18.13 N/mm²
1.5
Where
c = cantilever outstand of flange
1760 = Perimeter
15000 = Sectional Area in mm2
15201 = 4c2 + 1760c +15000
0.5
3fod
tp = c ( )
fy γ o
3 x 18.13 0.5
t p = 29.54 ( )
355 x 1
t p = 11.56 mm
STRUCTURAL DRAWING
100.0 m
3.0 m
Lecture Theatre
40m x 30m
50.0 m
21.0 m
Entrance
Cafe
15m x 10m
Social Space
30m x 40m
50.0 m
Rest Room
15m x 10m
1.0 m
5.0 m
5.0 m
50.0 m
5.0 m
5.0 m
21.0 m
5.0 m 5.0 m 5.0 m 5.0 m 5.0 m 5.0 m 5.0 m 5.0 m 5.0 m 5.0 m
5.0 m
5.0 m
5.0 m
5.0 m
50.0 m
5.0 m
5.0 m
1.0 m
0.014
8.0000
17.2521
4.0000
5.0000 5.0000 5.0000 5.0000 5.0000 5.0000 5.0000 5.0000 5.0000 5.0000
Elevation
0.0383
5.1756
18.7mm
Plate Girder Size
10.0000 10.0000 10.0000 10.0000
12mm 314.5mm
8.0000
4.0000
Side View
374mm
8.4mm
0.5400
367mm
Base Plate
6mm 257.2mm
Slab Section
Sheet Name:
2.50 2.50 2.50 2.50 5.00 5.00 5.00 5.00 2.50 2.50 2.50 2.50 Elevations & Sections
101.9mm Project Name:
2-Storey Building
UB 254 x 102 x 25 Address:
London South Bank University
Designed by:
Plate Girder with Stiffener Adesh Shahi
Scale: Sheet No: Date:
40 : 1 05 March 25, 2024
Appendix 2
LETTER TO CLIENT
Dear Client,
I hope this letter finds you well. Following our recent discussion regarding the proposed
expansion of the building footprint, I have conducted a thorough analysis of the structural
implications associated with doubling the size of the structure.
Expanding the footprint of the building will have significant implications on the structural
design and integrity of the entire framework. Below, I have outlined the key considerations:
• Load Distribution: Doubling the floor area will necessitate a redistribution of the
loads throughout the structure, particularly vertical loads such as dead and live loads.
This will require a reassessment of the existing foundation design to ensure it can
adequately support the increased loads without compromising stability.
• Structural Stability: The increase in floor area will introduce additional lateral forces
on the building, particularly wind loads. It will be imperative to reassess the lateral
stability system, including bracing and shear walls, to ensure the structure can
withstand these forces and maintain stability during extreme weather conditions.
• Column Spacing and Layout: The expansion of the building footprint may
necessitate a reconsideration of the column spacing and layout to accommodate the
larger floor area while maintaining adequate structural support and minimizing
interference with the architectural design and functional requirements of the spaces.
• Foundation Design: The enlargement of the building footprint will require a
reassessment of the foundation design to ensure it can adequately distribute the
increased loads to the underlying soil strata without exceeding allowable bearing
pressures or causing excessive settlement.
• Cost and Time Implications: Doubling the size of the building footprint will
inevitably result in increased material and construction costs, as well as potentially
extending the project timeline. It will be essential to carefully consider these
implications and adjust the project budget and schedule accordingly.
In conclusion, while expanding the footprint of the building presents exciting opportunities for
enhancing functionality and accommodating future growth, it is essential to carefully evaluate
and address the structural implications to ensure the safety, stability, and integrity of the
structure.
I am available to discuss these considerations further and provide any additional information
or clarification as needed. Thank you for entrusting me with this project, and I look forward to
our continued collaboration.
Sincerely,
Adesh Shahi