Power System Components and Per-unit System
5
Per-unit System
Per-unit system is the solution of an interconnected power system having several different voltage
levels that require the transformation of all impedances to a single voltage level. However, power,
voltage, current and impedance are expressed as a decimal fraction or multiples of base quantities.
In per-unit system, the different voltage levels disappear, and a power network involving
generators, transformers, and lines (of different voltage levels) reduces to a system of simple
impedances. For example, the equivalent impedance of a transformer whether referred to primary
or secondary is the same.
𝐴𝑐𝑡𝑢𝑎𝑙 𝑄𝑢𝑎𝑛𝑡𝑖𝑡𝑦
The per-unit quantity =
𝐵𝑎𝑠𝑒 𝑉𝑎𝑙𝑢𝑒 𝑜𝑓 𝑄𝑢𝑎𝑛𝑡𝑖𝑡𝑦
6
Per-unit System
𝐴𝑐𝑡𝑢𝑎𝑙 𝑄𝑢𝑎𝑛𝑡𝑖𝑡𝑦
The per-unit quantity =
𝐵𝑎𝑠𝑒 𝑉𝑎𝑙𝑢𝑒 𝑜𝑓 𝑄𝑢𝑎𝑛𝑡𝑖𝑡𝑦
Let us defined
𝑆 𝑉 𝐼 𝑍
Spu = , Vpu = , Ipu = , Zpu =
SB VB 𝐼B ZB
where, S (apparent power), V(voltage), I (current) and Z(impedance) are phasor or complex
quantities and denominators ( SB , VB , 𝐼B and ZB ) are always real numbers. To completely define
a per-unit system, minimum four base quantities are required. Two independent base values can
be arbitrarily selected at one point in a power system the three-phase base volt-ampere SB or
(MVA)B , and the line-to-line base voltage VB or (kV)B are selected.
SB
𝐼B = 2
3 ∗ VB
2 2
VB / 3 VB / 3 VB 2
𝑍B = = =
𝐼B S B SB
2 7
3 ∗ VB
Per-unit System
The impedance of generators, transformers and motors supplied by the manufacturer are generally
given in per-unit values on their own ratings. For power system analysis, all impedances must be
expressed in per-unit values on a common base.
When base quantities are changed from (MVA )B,𝑜𝑙𝑑 to (MVA )B,𝑛𝑒𝑤 and from (kV)B,𝑜𝑙𝑑 to
(kV)B,𝑛𝑒𝑤
Zactual,n𝑒𝑤 = Zactual,𝑜𝑙𝑑
Zpu,n𝑒𝑤 ∗ ZB,n𝑒𝑤 = Zpu,𝑜𝑙𝑑 ∗ ZB,𝑜𝑙𝑑
2 2
(kV)B,𝑛𝑒𝑤 (kV)B,𝑜𝑙𝑑
Zpu,n𝑒𝑤 ∗ = Zpu,𝑜𝑙𝑑 ∗
(MVA)B,𝑛𝑒𝑤 (MVA)B,𝑜𝑙𝑑
2
(MVA)B,𝑛𝑒𝑤 (kV)B,𝑜𝑙𝑑
Zpu,n𝑒𝑤 = Zpu,𝑜𝑙𝑑 ∗ 2
(MVA)B,𝑜𝑙𝑑 (kV)B,𝑣𝑒𝑤
8
Per-unit System for Transformer
The figure shows a single-phase transformer in terms of primary and secondary
reactance z𝑝 and z𝑠 and transformation ratio 1: α
VpB 1 IpB
= , =α
VSB α ISB
VpB VSB
z𝑝𝐵 = , z𝑆𝐵 =
IpB ISB
VS = 𝐸S − 𝑍𝑆 IS
𝐸p = VP − 𝑍𝑝 Ip
𝐸S = α 𝐸p
VS = α 𝐸p − 𝑍𝑆 IS
VS = α VP − 𝑍𝑝 Ip − 𝑍𝑆 IS
We can convert the actual values to per-unit
VS(pu) VS𝐵 = α Vp(pu) VPB − Zp(pu) ZPB Ip(pu) IPB − ZS(pu) ZSB IS(pu) ISB
VS(pu) VS𝐵 = α Vp(pu) VPB − Zp(pu) Ip(pu) VPB − ZS(pu) IS(pu) VS𝐵
Dividing the equation by VS𝐵
9
Per-unit System for Transformer
The figure shows a single-phase transformer in terms of primary and secondary
reactance z𝑝 and z𝑠 and transformation ratio 1: α
VS(pu) VS𝐵 = α Vp(pu) VPB − Zp(pu) Ip(pu) VPB − ZS(pu) IS(pu) VS𝐵
Dividing the equation by VS𝐵
VPB VPB
VS(pu) = α Vp(pu) − Zp(pu) Ip(pu) − ZS(pu) IS(pu)
VS𝐵 VS𝐵
1 1
VS(pu) = α Vp(pu) − Zp(pu) Ip(pu) − ZS(pu) IS(pu)
α α
VS(pu) = Vp(pu) − Zp(pu) Ip(pu) − ZS(pu) IS(pu)
IpB Ip Ip IS
= =α , =
ISB IS IpB ISB
J 𝑋𝑔(𝑃𝑈)
G ∼+
E𝑔 I𝑔
J 𝑋𝑚(𝑃𝑈)
M +∼
E𝑚 I𝑚
12
Per-unit System for transmission line
The figure shows an equivalent circuit of a T.L
J 𝑋𝑇.𝐿(𝑃𝑈)
13
Example (1)
The figure depicts a single line diagram of three-phase system using base power of 100MVA.
Find
• Per unit single line diagram with all values in PU
• Find the base current at each zone
• Disconnect generators 2 and 3, connect the load at bus D (15MVA, 0.8 lag power factor), and
connect the load at bus E (Zph𝛥 = 10.5 + 𝑗7.5 Ω) find VA in per-unit and actual value
G1 G3
Tr1 Tr3
A B C D F
Tr2
G2 14
Example (1)
G1 G3
Tr1 Tr3
A B C D F
Tr2
G2
Given data
Generator 1: 50MVA, 6.6KV, X=15%, Y Tr1: 62.5MVA, 6.6/138 KV, X=10%, 𝛥/ Y
Tr2: 37.5MVA, 6.6/138 KV, X=10%, 𝛥/ Y
Generator 2: 30MVA, 6.6KV, X=15%, Y
Tr3: 125MVA, 13.8/138 KV, X=12%, 𝛥/ Y
Generator 3: 100MVA, 13.8KV, X=20%, Y
TL 𝐵𝐶 =100jΩ
TL 𝐶𝐷 =80jΩ 15
Example (1)
Zone 1 Zone 2 Zone 3
G1 G3
Tr1 Tr3
A B C D F
Tr2
Zone 4 E
G2
Zone 1 Vbase = 6.6𝐾𝑉, Sbase = 100𝑀𝑉𝐴 , Zone 2 Vbase = 138𝐾𝑉, Sbase = 100𝑀𝑉𝐴
Zone 3 Vbase = 13.8𝐾𝑉, Sbase = 100𝑀𝑉𝐴 , Zone 4 Vbase = 6.6𝐾𝑉, Sbase = 100𝑀𝑉𝐴
2
(MVA)B,𝑛𝑒𝑤 (kV)B,𝑜𝑙𝑑
Zpu,n𝑒𝑤 = Zpu,𝑜𝑙𝑑 ∗ 2
(MVA)B,𝑜𝑙𝑑 (kV)B,𝑣𝑒𝑤
16
Example (1)
Zone 1 Zone 2 Zone 3
G1 G3
Tr1 Tr3
A B C D F
Tr2
For transformers
2
Zone 4 E 100 6.6
2 X 𝑇𝑟1 = 0.1 ∗ ∗ = 0.16𝑝𝑢
(MVA)B,𝑛𝑒𝑤 (kV)B,𝑜𝑙𝑑 62.5 6.6
Zpu,n𝑒𝑤 = Zpu,𝑜𝑙𝑑
(MVA)B,𝑜𝑙𝑑
∗
(kV)B,𝑣𝑒𝑤
2 G2 100 6.6
2
X 𝑇𝑟2 = 0.1 ∗ ∗ = 0.267𝑝𝑢
For generators 37.5 6.6
2
100 6.6 2 100 13.8
X𝐺1 = 0.15 ∗ ∗ = 0.3𝑝𝑢 X 𝑇𝑟3 = 0.12 ∗ ∗ = 0.096𝑝𝑢
50 6.6 125 13.8
100 6.6 2 For transmission line
X𝐺2 = 0.15 ∗ ∗ = 0.5𝑝𝑢 2
𝑉𝑏𝑎𝑠𝑒 1382
30 6.6 Z𝑏𝑎𝑠𝑒 = = 100 = 190.44Ω
2 𝑆𝑏𝑎𝑠𝑒
100 13.8 100
X𝐺3 = 0.2 ∗ ∗ = 0.2𝑝𝑢 TL 𝐵𝐶 = =0.525pu
190.44
100 13.8 80 17
TL 𝐶𝐷 = =0.42pu
190.44
Example (1)
∼+ +∼
0.267j
E𝑔1 A B C D F E𝑔3
0.5j
+∼
E𝑔2
18
Example (1)
19
Example (1)
• Disconnect generators 2 and 3 and transformer 3, connect the load 1 at bus D (15MVA, 0.8 lag power
factor), and connect the load 2 at bus E (Zph𝛥 = 10.5 + 𝑗7.5 Ω) find VA in per-unit and actual value
G1
Tr1
A B C D
Load1
Tr2
Load2
20
Example (1)
• Disconnect generators 2 and 3 and transformer 3, connect the load 1 at bus D (15MVA, 0.8 lag power
factor), and connect the load 2 at bus E (Zph𝛥 = 10.5 + 𝑗7.5 Ω) find VA in per-unit and actual value
∼+
0.267j
E𝑔1 A B C D
E Load1
Load2
∼+
0.267j
E𝑔1 A B C D
Load
Tr3 Tr4 23
Example (2)
• Per unit single line diagram with all values in PU
Line 1 : j48.4
Line 2: j65.43
Load: 3ph , 57MVA, 10.45KV, 0.6lag PF
Load
Tr3 Tr4
24
Example (2)
• The per unit reactance at new bases
2
(MVA)B,𝑛𝑒𝑤 (kV)B,𝑜𝑙𝑑
Zpu,n𝑒𝑤 = Zpu,𝑜𝑙𝑑 ∗ 2
(MVA)B,𝑜𝑙𝑑 (kV)B,𝑣𝑒𝑤
2
100 22
X𝐺 = 0.18 ∗ ∗ = 0.2𝑝𝑢
90 22
2
100 22 M 0.8 lead PF
X 𝑇𝑟1 = 0.10 ∗ ∗ = 0.2𝑝𝑢
50 22 Line 1 : j48.4
2 Line 2: j65.43
100 11
X 𝑇𝑟2 = 0.06 ∗ ∗ = 0.15𝑝𝑢 Load: 3ph , 57MVA, 10.45KV, 0.6lag PF
40 11
2
100 22
X 𝑇𝑟3 = 0.064 ∗ ∗ = 0.16𝑝𝑢
40 22
2
100 11
X 𝑇𝑟4 = 0.08 ∗ ∗ = 0.2𝑝𝑢
40 11
2
100 10.45
X𝑀 = 0.185 ∗ ∗ = 0.25𝑝𝑢
66.5 11 25
Example (2)
• The per unit reactance at new bases
VB 2 220 2
ZBase)line1 = = = 484Ω
SB 100
110 2
ZBase)line2 = = 121Ω
100
VL 2 10.45 2 M 0.8 lead PF
Zl𝑜𝑎𝑑 = = = 1.9158∠ 53.13°Ω Line 1 : j48.4
SL 57∠ −53.13°
11 2 Line 2: j65.43
ZBase)l𝑜𝑎𝑑 = =1.21 Load: 3ph , 57MVA, 10.45KV, 0.6lag PF
100
48.4
Zpu)line1 = = 0.1𝑝𝑢
484
65.43
Zpu)line2 = = 0.54𝑝𝑢
121
1.9158∠ 53.13°
Zpu)l𝑜𝑎𝑑 = = 0.95 + 𝑗1.2667𝑝𝑢
1.21
26
Example (2)
• The per unit reactance diagram 𝐼 = I𝑀 + I𝐿
V4 0.95∠0°
Voltage at bus 1 I𝐿 = = = 0.36 − 𝑗. 48 𝑝𝑢
Z𝑙𝑜𝑎𝑑 0.95+𝑗1.2667
V1 = V4 + 𝐼𝑍 S𝑀 66.5/100∠36.87°
I𝑀 = = = 0.56+j0.42
V4 0.95∠0°
10.45
V4 = = 0.95∠ 0°𝑝𝑢 I= 0.92+j0.06 pu
11
V1 = 0.95∠ 0° + 0.3 ∗ 0.92+j0.06 = 0.968 + 𝑗0.276𝑝𝑢
0.45 ∗ 0.9
Z 𝑇𝑜𝑡𝑎𝑙 = = 0.3𝑝𝑢 V1 =22*(0.968 + 𝑗0.276) = 22 ∠ 15.91°KV
0.9 + 0.45
1 2 3 4 𝑀
j0.2 j0.2 j0.1 j0.15 j0.25
∼+ ∼+
E𝑔1 0.95 j1.2667
5 6
j0.16 j0.54 j0.2
Load
27