Electronic Earthing
Electronic Earthing
Electronic Earthing
Earthing Methods
1) Multiple Earthing Connections
# In a commercial/non-industrial building it is not unusual to find neutral connected to earth/panel enclosures at more than one location.
# Results in noise causing errors or worse. # Whether accidental or intentional, this practice is not recommended.
Multiple Earthing
The N current gets divided & a part of it will be flowing thru ground/ground wire, even w/o earth fault
Ground Loops
Earthing Methods
2) Separate/Isolated Earthing Connection
# To earth computers to isolated earthing electrodes separate from the power system earthing electrode system. # While continuous low-level noise are eliminated, other catastrophic incidents are encountered.
# Since unsafe, therefore not recommended.
Isolated Earthing
Building Steel/Power System Earthing
Isolated Earthing
Why Unsafe?
Large voltages impressed on computer components under thunderstorm conditions (direct strike or charge induced because of clouds overhead).
With isolated earthing, a fault in a computer requires fault current to pass thru the resistance of both the isolated & power system ground in series. In this case the current would be insufficient to operate the protective device.
Isolated Earthing
20A CB
Computer Modules
Earthing Methods
3) Single Point Earthing Connection
# To prevent stray/circulating currents from affecting the computer signals & operations, it is necessary to keep the computer ground system separate from the equipment ground components & connect together at only one point. # Recommended method, as it eliminates problems of earlier two methods.
Y
B N
Earthing Methods
4) Single Point Earthing Connection plus Connection with Grid in the Floor
# For each group of computer equipment, provide a grid network in the raised floor, with tie wires from each computer unit to the grid & one from the grid to the room grounding point.
# Recommended method, as it also eliminates problems of interference from radio frequencies.
CASE HISTORIES
1)PC experiencing frequent lock ups & unexplained failures
2)Erratic computer operation within a large office building experiencing several lightning storms 3)Intermittent data memory errors & data transmission errors between remote terminals & a central computer system.
Problem 1
No problem was found in the utility supply; earthing was also found to be okay. The power outlet serving the computer was examined for polarity, revealing the phase & the neutral conductors were reversed at the receptacle. Once the conductors were correctly connected, the PC ran w/o problems.
Problem 2
The earthing conductors of all the computers in the building were connected to isolated earthing electrode system (consisted of 6 rods driven into the earth away from building). The computer manufacturer was persuaded to permit earthing of the computer system to the building earthing system, which had concrete encased earthing electrodes. Immediately the erratic operations ceased.
Problem 3
In the installation of a multistory office building, several floors of modular workstations were powered from a common, 3 phase step down transformer with a shared neutral. Mainframe terminals in these workstations experienced intermittent data memory errors & data transmission errors, & occasionally hardware failures. It was found that considerable (& variable) neutral current existed. RMS values of N to earth didnt exceed 3.7V, but the peak voltage ranged up to 10V.
Problem 3
Each floor of the building was isolated into 2 sections via shielded isolation transformers. Individual N conductors were installed for all workstation branch circuits. Re-establishment of the N-E bond at the new isolation transformers, combined with the reduced neutral current in the dedicated neutrals, reduced N-E voltage to less than 2V. The problem was solved.