Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Transmission and Distribution Supply System

Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 108

Transmission and Distribution supply system.

TRANSMISSION SYSTEM

Transmission system & distribution

Generators and loads are connected together through transmission lines


transporting electric power from one place to another. Transmission line
must, therefore, take power from generators, transmit it to location where it
will be used, and then distribute it to individual consumers.
The power capability of a transmission line is proportional to the square of
the voltage on the line. Therefore, very high voltage levels are used to
transmit power over long distances. Once the power reaches the area where
it will be used, it is stepped down to a lower voltages in distribution
substations, and then delivered to customers through distribution lines.

Distribution line with no ground wire.

Dual 345 kV transmission line

There two types of transmission lines: overhead lines and


buried cables.

An overhead transmission line usually consists of three conductors or bundles of


conductors containing the three phases of the power system. The conductors are
usually aluminum cable steel reinforced (ACSR), which are steel core (for strength)
and aluminum wires (having low resistance) wrapped around the core.

In overhead transmission lines, the conductors are suspended from a pole or a tower via
insulators.

In addition to phase conductors, a transmission line usually includes one or two steel wires
called ground (shield) wires. These wires are electrically connected to the tower and to the
ground, and, therefore, are at ground potential.
In large transmission lines, these wires
are located above the phase conductors,
shielding them from lightning.

Cable lines are designed to be placed underground or


under water. The conductors are insulated from one
another and surrounded by protective sheath. Cable lines
are usually more expensive and harder to maintain. They
also have capacitance problem not suitable for long
distance.

Transmission lines are characterized by a series resistance, inductance, and shunt capacitance
per unit length. These values determine the power-carrying capacity of the transmission line and
the voltage drop across it at full load.

TRNSMISSION OF ELECTRIC POWER


ELECTRICAL SUPPLY SYSTEM:ELEMENT
ELEMENT OF
OF POWER
POWER SUPPLY
SUPPLYSYSTEM
SYSTEM
GENRATING
GENRATING STATION
STATION
PRIMARY
PRIMARY TRANSMISSION
TRANSMISSION
SECONDRY
SECONDRY TRANSMISSION
TRANSMISSION
PRIMARY
PRIMARY DISTRIBUTION
DISTRIBUTION
SECONDARY
SECONDARY DISTRIBUTION
DISTRIBUTION

TRNSMISSION OF ELECTRIC POWER


ELEMENT OF POWER SYSTEM:ELEMENT
ELEMENT OF
OF TRANSMISSION
TRANSMISSION SYSTEM
SYSTEM
PROTECTIVE
PROTECTIVE DEVICE
DEVICE

STEP
STEP UP
UP TRANSFORMER
TRANSFORMER

REGULATOR
REGULATOR

STEP
STEP DOWN
DOWN TRNSFORMER.
TRNSFORMER.

CONDUCTOR
CONDUCTOR

LINE
LINE SUPPORT.
SUPPORT.
LINE
LINE ISULATOR
ISULATOR

TRNSMISSION OF ELECTRIC POWER


TYPES OF TRANSMISSION SYSTEM:-

TRANSMISSON LINE
LINE
TRANSMISSON
A.C. TRANSMISSION
TRANSMISSION
A.C.
A.C.THREEPHASE
PHASE
MID POINT
POINT EARTH
EARTH
A.C.THREE
MID
FOURWIRE
WIRESYSTEM
SYSTEM A.C.
A.C. SINGAL
SINGAL PHASE.
PHASE.
FOUR
A.C.SINGAL
SINGALPHASE
PHASE
A.C.
TWOWIRE
WIRESYSTEM
SYSTEM
TWO

A.C.THREEPHASE
PHASE
A.C.THREE
THREEWIRE
WIRE
THREE

D.C.TRANSMISION
D.C.TRANSMISION
D.C.TWOWIRE
WIRE
D.C.TWO
SYSTEM.
SYSTEM.

MIDPOINT
POINTEARTH
EARTH
MID
TYPESYSTEM.
SYSTEM.
TYPE

SUBSTATION

SUBSTATION
FUNCTION OF SUBSTATION:

The main functions of sub-station are to receive


energy transmitted at high voltage from the
generating station, reduce to a value appropriate
for local distribution and provide facilities for
switching.

SUBSTATION
CLASSIFICATION OF SUBSTATION:-

According to Service
1.Transformer sub-station
2.Industrial sub-station
3.Switching sub-station
4.Synchronous sub-station
5.Frequency sub-station
6.Converting sub-station.

SUBSTATION
CLASSIFICATION OF SUBSTATION:-

According to Design.
1.Indoor type
Sub-station.
(a) Pole mounted
Sub-station.

2.Out door type


Sub-station.

(b) Foundation mounted


Sub-station.

SUBSTATION
MAIN EQUIPMENTS USED IN SUBSTATION:1.Main
1.Mainbus
busbar.
bar.

2.Insulator
2.Insulator. .

3.Isolator
3.Isolator. .

4.Circuit
4.Circuitbreaker
breaker. .

5.Load
5.Loadinterrupter
interrupter
Switches.
Switches.

6.Fuses
6.Fuses. .

8.Current
8.Current&
&potential
potential 9.Indicating
9.Indicating&Metering
&Metering
7.Power
transformer
.
7.Power transformer.
Transformer.
Instrument.
Transformer.
Instrument.
10.Protective
10.Protectiverelays
relays. .

11.Carrier
11.Carriercurrent
current
Equipment.
Equipment.

12.Control
12.Controlcable
cable. .

DISTRIBUTION SYSTEM
TYPES OF DISTRIBUTION SYSTEM:-

1.Primary
distribution.

2.Secondary
distribution.

DISTRIBUTION SYSTEM
MAIN PARTS OF DISTRIBUTION SYSTEM:-

3.Service mains.

2.Distributor..

1.Feeder

View of distribution system.

View of L.T. distribution system.

DISTRIBUTION TRANSFORMER

DISTRIBUTION SYSTEM
METHODS OF FEEDING A DISTRIBUTOR:1.Redial system.

2.Ring mains
system.

3.Inter connected
grid
Type system.

BUS BAR SYSTEM


VARIOUS TYPES OF BUS BAR ARRANGEMENT SYSTEM:

Single bus bar system used in D.C. and A.C.


power station.
Single bus bar system with sectionalization.
Ring bus bar system.
Duplicate bus bar system.

TRNSMISSION OF ELECTRIC POWER


CHARECTERISTICS OF CONDUCTING
MATERIAL:(a) High
Conductivity

(e) Low specific


Gravity.

(b) High tensile


Strength

(C) Should not


Be brittle
(d) Low
cost

TRNSMISSION OF ELECTRIC POWER


CHARECTERISTICS OF INSULATING
MATERIAL:(a) High
(b) High tensile
specific resistance
Strength

(c) High
dielectric
strength

(e) Easily available


(d) Should
not be
porous

SUPPORT
*FUNCTION: It provides support to overhead conductor.
* SUPPORT AS A: Tower
Pole

CHARECTERISTICS OF SUPPORT
MATERIAL

(a) LOW
WEIGHT

(e) LONG
WORKING LIFE

(b) HIGH
MECHANICAL
STRENGTH

(C)HIGH
ACCESSIBILITY
(d) LOW
COST

TRNSMISSION OF ELECTRIC POWER


CLASSIFICATION OF POLES:Types of
poles
A type

Wood Pole

Steel pole

Rail pole
H type

Letasied steel
tower

Nero base tower


Brode base tower

Tubular pole
Single pole

RCC Pole

View of tubular Poles.

Transmission line (Steel tower)

Transmission line (Steel tower)

Transmission line (Steel tower)

Different type mounting arrangement of pole.

SAG
FACTORS AFFECTING ON SAG:-

FACTORS
FACTORS AFFECTING
AFFECTING ON
ON SAG
SAG..
Ice
Ice coating
coating
Wind
Wind pressure.
pressure.
Tempressure.
Tempressure.

Wight
Wight of
of conductor
conductor
Span
Span
Working
Working tensile
tensile strength
strength..

ELECTRICAL ASPECTS OF TRANSMISSION


LINE

Capacitance.

Inductance.

Resistance

Resistance

The DC resistance of a conductor is given by

RDC

(9.9.1)

Where l is the length of conductor; A cross-sectional area, is the resistivity of the


conductor. Therefore, the DC resistance per meter of the conductor is

rDC



A m

(9.9.1)

The resistivity of a conductor is a fundamental property of the material that the


conductor is made from. It varies with both type and temperature of the material. At
the same temperature, the resistivity of aluminum is higher than the resistivity of
copper.

Resistance

The resistivity increases linearly with temperature over normal range of temperatures. If the
resistivity at one temperature is known, the resistivity at another temperature can be found from

T 2

M T2

T 1
M T1

(9.10.1)

Where T1 and T1 are temperature 1 in oC and the resistivity at that temperature, T2 and T2 are
temperature 2 in oC and the resistivity at that temperature, and M is the temperature constant.

Inductance and inductive reactance

The series inductance of a transmission line consists of two components: internal and external inductances,
which are due the magnetic flux inside and outside the conductor respectively. The inductance of a
transmission line is defined as the number of flux linkages [Wb-turns] produced per ampere of current
flowing through the line:

L
I

(9.12.1)

1. Internal inductance:
Consider a conductor of radius r carrying a current I. At a distance x from
the center of this conductor, the magnetic field intensity Hx can be found
from Amperes law:

H x dl I x

(9.12.2)

Inductance and inductive reactance

Where Hx is the magnetic field intensity at each point along a closed path, dl is a unit vector along that path
and Ix is the net current enclosed in the path. For the homogeneous materials and a circular path of radius x,
the magnitude of Hx is constant, and dl is always parallel to Hx. Therefore:

Ix
2 xH x I x H x
2 x

(9.13.1)

Assuming next that the current is distributed uniformly in the conductor:

x2
Ix 2 I
r

(9.13.2)

Thus, the magnetic intensity at radius x inside the conductor is

x
Hx
I H m
2
2 r

(9.13.3)

Inductance and inductive reactance

The flux density at a distance x from the center of the conductor is

xI
Bx H x
[T ]
2
2 r

(9.14.1)

The differential magnetic flux contained in a circular tube of thickness dx and at a distance x from the center
of the conductor is

xI
d
dx[Wb m]
2
2 r

(9.14.2)

The flux linkages per meter of length due to flux in the tube is the product of the differential flux and the
fraction of current linked:

x2
x3 I
d 2 d
dx[Wb turns m]
4
r
2 r

(9.14.3)

Inductance and inductive reactance

The total internal flux linkages per meter can be found via integration

x3 I
I
int d
dx [Wb turns m ]
4
2 r
8
0
r

(9.15.1)

Therefore, the internal inductance per meter is

int
lint
H m
I
8

(9.15.2)

If the relative permeability of the conductor is 1 (non-ferromagnetic materials, such as copper and
aluminum), the inductance per meter reduces to

0 4 107
lint

7 H m
8
8

(9.15.3)

External inductance between 2 points outside of the line

To find the inductance external to a conductor, we need to calculate the


flux linkages of the conductor due only the portion of flux between two
points P1 and P2 that lie at distances D1 and D2 from the center of the
conductor.
In the external to the conductor region, the magnetic intensity at a
distance x from the center of conductor is

Ix
I
Hx

2 x 2 x

(9.16.1)

since all the current is within the tube.


The flux density at a distance x from the center of conductor is

I
Bx H x
2 x

(9.16.2)

External inductance between 2 points outside of the line

The differential magnetic flux contained in a circular tube of thickness dx and at a distance x from the center of the conductor is

I
d
dx[Wb m]
2 x

(9.17.1)

The flux links the full current carried by the conductor, therefore:

I
d d
dx[Wb turns m]
2 x

(9.17.2)

The total external flux linkages per meter can be found via integration

D2

D2

I
I D1
ext d
dx
ln [Wb turns m]
2 x
2 D2
D1
D1
The external inductance per meter is

lex t

ex t
D2

ln H m
I
2 D1

(9.17.3)

(9.17.4)

Inductance of a single-phase 2-wire transmission line

We determine next the series inductance of a single-phase line


consisting of two conductors of radii r spaced by a distance D and
both carrying currents of magnitude I flowing into the page in the
left-hand conductor and out of the page in the right-hand conductor.

Considering two circular integration paths, we notice that the line


integral along x1 produces a net magnetic intensity since a non-zero
net current is enclosed by x1. Thus:

dl I x

(9.18.1)

Since the path of radius x2 encloses both conductors and the currents are equal and opposite, the net current
enclosed is 0 and, therefore, there are no contributions to the total inductance from the magnetic fields at
distances greater than D.

Inductance of a single-phase 2-wire transmission line

The total inductance of a wire per unit length in this transmission line is a sum of the internal inductance and
the external inductance between the conductor surface (r) and the separation distance (D):

l lint lext
2

D
1
ln H m
r
4

(9.19.1)

By symmetry, the total inductance of the other wire is the same, therefore, the total inductance of a two-wire
transmission line is

1
D
l ln H m
4
r
Where r is the radius of each conductor and D is the distance between conductors.

(9.19.2)

Inductance of a transmission line

Equations similar to (9.19.2) can be derived for three-phase lines and for lines with more phases In most of
the practical situations, the inductance of the transmission line can be found from tables supplied by line
developers.
Analysis of (9.19.2) shows that:
1.The greater the spacing between the phases of a transmission line, the greater the inductance of the line.
Since the phases of a high-voltage overhead transmission line must be spaced further apart to ensure proper
insulation, a high-voltage line will have a higher inductance than a low-voltage line. Since the spacing
between lines in buried cables is very small, series inductance of cables is much smaller than the inductance
of overhead lines.
2.The greater the radius of the conductors in a transmission line, the lower the inductance of the line. In
practical transmission lines, instead of using heavy and inflexible conductors of large radii, two and more
conductors are bundled together to approximate a large diameter conductor. The more conductors included
in the bundle, the better the approximation becomes. Bundles are often used in the high-voltage transmission
lines.

Inductance of a transmission line

A two-conductor
bundle

A four-conductor
bundle

Inductive reactance of a line

The series inductive reactance of a transmission line depends on both the inductance of the line and the
frequency of the power system. Denoting the inductance per unit length as l, the inductive reactance per unit
length will be

xI jl j 2 fl

(9.22.1)

where f is the power system frequency. Therefore, the total series inductive reactance of a transmission line
can be found as

X I xI d
where d is the length of the line.

(9.22.2)

Capacitance and capacitive reactance

Since a voltage V is applied to a pair of conductors separated by a dielectric (air), charges of equal magnitude
but opposite sign will accumulate on the conductors:

q CV

(9.23.1)

Where C is the capacitance between the pair of conductors.

In AC power systems, a transmission line carries a time-varying voltage different in each phase. This timevarying voltage causes the changes in charges stored on conductors. Changing charges produce a changing
current, which will increase the current through the transmission line and affect the power factor and voltage
drop of the line. This changing current will flow in a transmission line even if it is open circuited.

Capacitance and capacitive reactance

The capacitance of the transmission line can be found using the Gausss law:

D dA

(9.24.1)

where A specifies a closed surface; dA is the unit vector normal to the surface; q is the charge inside the
surface; D is the electric flux density at the surface:

D E

(9.24.2)

where E is the electric field intensity at that point; is the permittivity of the material:

r 0
Relative permittivity of the material
The permittivity of free space 0 = 8.8510-12 F/m

(9.24.3)

Capacitance and capacitive reactance

Electric flux lines radiate uniformly outwards from the surface of the
conductor with a positive charge on its surface. In this case, the flux
density vector D is always parallel to the normal vector dA and is
constant at all points around a path of constant radius r. Therefore:

DA QD(2 xl ) ql

(9.25.1)

were l is the length of conductor; q is the charge density; Q is the total


charge on the conductor.
Then the flux density is

The electric field intensity is

q
D
2 x
q
E
2 x

(9.25.2)

(9.25.3)

Capacitance and capacitive reactance

The potential difference between two points P1 and P2 can be found as

P2

V12 E dl

(9.26.1)

P1

where dl is a differential element tangential to the integration path between P1 and P2. The path is irrelevant.

Selection of path can simplify calculations.


For P1 - Pint, vectors E and dl are parallel; therefore, E dl =
Edx. For Pint P2 vectors are orthogonal, therefore E dl = 0.

D2

D2

D2
q
q
V12 Edx
dx
ln
2 x
2 D1
D1
D1

(9.26.2)

Capacitance of a single phase two-wire transmission line

The potential difference due to the charge on


conductor a can be found as

Vab ,a

qa
D

ln
2
r

(9.27.1)

Similarly, the potential difference due to the charge on conductor b is

or

qb
D
Vba ,b
ln
2
r
qb
D
Vab ,b
ln
2
r

(9.27.2)

(9.27.3)

Capacitance of a single phase two-wire transmission line

The total voltage between the lines is

Vab Vab ,a Vab ,b

qa
D qb
D

ln
ln
2
r 2
r

(9.28.1)

Since q1 = q2 = q, the equation reduces to

q
D
Vab
ln
r

(9.28.2)

The capacitance per unit length between the two conductors of the line is

q
q
cab
q
D
V
ln
r

(9.28.3)

Capacitance of a single phase two-wire transmission line

Thus:

cab
D
ln
r

(9.29.1)

Which is the capacitance per unit length of a single-phase two-wire transmission line.
The potential difference between each conductor and the ground (or neutral) is one half of the potential
difference between the two conductors. Therefore, the capacitance to ground of this single-phase transmission
line will be

2
cn can cbn
D
ln
r

(9.29.2)

Capacitance of a single phase two-wire transmission line

Similarly, the expressions for capacitance of three-phase lines (and for lines with more than 3 phases) can be
derived. Similarly to the inductance, the capacitance of the transmission line can be found from tables
supplied by line developers.
Analysis of (9.29.1) shows that:
1.The greater the spacing between the phases of a transmission line, the lower the capacitance of the line.
Since the phases of a high-voltage overhead transmission line must be spaced further apart to ensure proper
insulation, a high-voltage line will have a lower capacitance than a low-voltage line. Since the spacing
between lines in buried cables is very small, shunt capacitance of cables is much larger than the capacitance
of overhead lines. Cable lines are normally used for short transmission lines (to min capacitance) in urban
areas.
2.The greater the radius of the conductors in a transmission line, the higher the capacitance of the line.
Therefore, bundling increases the capacitance. Good transmission line is a compromise among the
requirements for low series inductance, low shunt capacitance, and a large enough separation to provide
insulation between the phases.

Shunt capacitive admittance

The shunt capacitive admittance of a transmission line depends on both the capacitance of the line and the
frequency of the power system. Denoting the capacitance per unit length as c, the shunt admittance per unit
length will be

yC j c j 2 fc

(9.31.1)

The total shunt capacitive admittance therefore is

YC yC d j 2 fcd

(9.31.2)

where d is the length of the line. The corresponding capacitive reactance is the reciprocal to the admittance:

1
1
ZC
j
YC
2 fcd

(9.31.3)

Example

Example 9.1: An 8000 V, 60 Hz, single-phase, transmission line consists of two hard-drawn aluminum
conductors with a radius of 2 cm spaced 1.2 m apart. If the transmission line is 30 km long and the
temperature of the conductors is 200C,
a.What is the series resistance per kilometer of this line?
b.What is the series inductance per kilometer of this line?
c.What is the shunt capacitance per kilometer of this line?
d.What is the total series reactance of this line?
e.What is the total shunt admittance of this line?

a. The series resistance of the transmission line is

l
R
A

Ignoring the skin effect, the resistivity of the line at 20 0 will be 2.8310-8 -m and the resistance per kilometer
of the line is

l 2.83 108 1000

0.0225 km
2
A
0.02

Example

b. The series inductance per kilometer of the transmission line is

1
D
1
1.2

ln

1000

ln
1000

1.738
10

H
km

4
r
4
0.02

c. The shunt capacitance per kilometer of the transmission line is

8.854 10
12
cab
1000
1000

6.794 10
9 F km
D
1.2
ln
ln
r
0.02
d. The series impedance per kilometer of the transmission line is

zse r jx r j 2 fl 0.0225 j 2 60 1.738

10
3

0.0225

j 0.655 km

Then the total series impedance of the line is

Z se 0.0225 j 0.655 30 0.675 j19.7

Example

e. The shunt admittance per kilometer of the transmission line is

yC j 2 fc j 2 60 6.794 10
9

j 2.561 106 Sm

The total shunt admittance will be

Yse j 2.561 106


30 j 7.684 10
5 S
The corresponding shunt capacitive reactance is

1
1
Z sh

j13.0k
5
Ysh j 7.684 10

TRANSMISSION LINE
CLASSIFICATION OF TRANSMISSION LINE:-

Classification of
Transmission line.
(1)Short Line.
( > 80 Km)

(2)

Medium line
(80 to 160 Km)

(3) Long line


(< 160 Km)

PERFORMANCE OF TRANSMISSION LINE

Transmission line models

Unlike the electric machines studied so far, transmission lines are characterized by their distributed
parameters: distributed resistance, inductance, and capacitance.
The distributed series and shunt elements of the transmission line make it harder to model. Such parameters
may be approximated by many small discrete resistors, capacitors, and inductors.

However, this approach is not very practical, since it would require to solve for voltages and currents at all
nodes along the line. We could also solve the exact differential equations for a line but this is also not very
practical for large power systems with many lines.

Transmission line models

Fortunately, certain simplifications can be used


Overhead transmission lines shorter than 80 km (50 miles) can be modeled as a series resistance and
inductance, since the shunt capacitance can be neglected over short distances.

The inductive reactance at 60 Hz for overhead lines is typically


much larger than the resistance of the line.

For medium-length lines (80-240 km), shunt capacitance should be


taken into account. However, it can be modeled by two capacitors
of a half of the line capacitance each.

Lines longer than 240 km (150 miles) are long transmission lines and are to be discussed later.

Transmission line models

The total series resistance, series reactance, and shunt admittance of a transmission line can be calculated as

R rd

(9.37.1)

X xd

(9.37.2)

Y yd

(9.37.3)

where r, x, and y are resistance, reactance, and shunt admittance per unit length and d is the length of the
transmission line. The values of r, x, and y can be computed from the line geometry or found in the reference
tables for the specific transmission line.

Short transmission line

The per-phase equivalent circuit of a short line


VS and VR are the sending and receiving end voltages; IS and IR are
the sending and receiving end currents. Assumption of no line
admittance leads to

IS IR

(9.38.1)

We can relate voltages through the Kirchhoffs voltage law

VS VR ZI VR RI jX L I

VR VS RI jX L I
which is very similar to the equation derived for a synchronous generator.

(9.38.2)

(9.38.3)

Short transmission line: phasor diagram

AC voltages are usually expressed as phasors.

Load with lagging power factor.

Load with unity power factor.

Load with leading power factor.


For a given source voltage VS and magnitude of the line current,
the received voltage is lower for lagging loads and higher for
leading loads.

2-port networks and ABCD models

The ABCD constants can be physically interpreted. Constant A represents the effect of a change in the receiving
end voltage on the sending end voltage; and constant D models the effect of a change in the receiving end
current on the sending end current. Naturally, both constants A and D are dimensionless.
The constant B represents the effect of a change in the receiving end current on the sending end voltage. The
constant C denotes the effect of a change in the receiving end voltage on the sending end current.
Transmission lines are 2-port linear networks, and they are often represented by ABCD models. For the short
transmission line model, IS = IR = I, and the ABCD constants are

A 1
BZ
C 0
D 1

(9.51.1)

Medium-length transmission line

Considering medium-length lines (50 to 150 mile-long), the


shunt admittance must be included in calculations.
However, the total admittance is usually modeled ( model)
as two capacitors of equal values (each corresponding to a
half of total admittance) placed at the sending and
receiving ends.

The current through the receiving end capacitor can be found as

IC 2

Y
VR
2

(9.52.1)

And the current through the series impedance elements is

I ser

Y
VR I R
2

(9.52.2)

Medium-length transmission line

From the Kirchhoffs voltage law, the sending end voltage is

VS ZI ser

YZ
VR Z I C 2 I R VR
1 VR ZI R
2

(9.53.1)

The source current will be

I S I C1 I ser

Y
Y
ZY
ZY
I C1 I C 2 I R VS VR I R Y
1 VR
1 I R (9.53.2)
2
2
4

Therefore, the ABCD constants of a medium-length transmission line are

ZY
1
2
BZ
A

If the shunt capacitance of the line is ignored, the


ABCD constants are the constants for a short
transmission line.

ZY
1
4
ZY
D
1
2

C Y

(9.53.3)

Long transmission line

For long lines, it is not accurate enough to approximate the shunt admittance by two constant capacitors at
either end of the line. Instead, both the shunt capacitance and the series impedance must be treated as
distributed quantities; the voltages and currents on the line should be found by solving differential equations of
the line.
However, it is possible to model a long transmission
line as a model with a modified series impedance Z
and a modified shunt admittance Y and to perform
calculations on that model using ABCD constants.
The modified values of series impedance and shunt
admittance are:

Z' Z

sinh d
d

tanh d 2
Y 'Y
d 2

(9.54.1)

(9.54.2)

Long transmission line

Here Z is the series impedance of the line; Y is the shunt admittance of the line; d is the length of the line; is
the propagation constant of the line:

yz

(9.55.1)

where y is the shunt admittance per kilometer and z is the series impedance per km.
As d gets small, the ratios approach 1.0 and the model becomes a medium-length line model. The ABCD
constants for a long transmission line are

Z 'Y '
A
1
2
BZ'
Z 'Y '
C Y '
1
4

Z 'Y '
D
1
2

(9.55.2)

MECHANICAL ASPECTS OF TRANSMISSION


LINE

INSULATOR

CONDUCTOR

SUPPORT

TYPES OF TRANSMISSION LINE


REPRESENTATION OF PERAMETERS OF
TRANSMISSION LINE:Nominal
Nominal
TT

Nominal
Nominal

END
END
Capacitance
Capacitance
Short
Shortlength
lengthSingle
Single
Phase
Phaseline.
line.
Short
Shortlength
lengththree
three
Phase
Phaseline.
line.
Long
Longlength
lengthtransmission
transmission
Line.
Line.

CORONA

FACTORS AFFECTING IN CORONA LOSSES.

Condition of the corona effect.


Potential difference is two conductor.

CORONA
FACTORS AFFECTING ON CORONA LOSS:-

Factors affecting on
corona loss.
(1)Condition on the
Atmosphere.

(2) Potential difference


Between two conductor.

CORONA
METHODS USED TO REDUCE CORONA LOSS:-

*Use of bundle
Conductor.

*Increase of conductor
Diameter.

TRNSMISSION OF ELECTRIC POWER


TYPES OF INSULATORS:(A) Pin type Insulator.

(C) Strain
Insulator.

(D)Shackle type
Insulator.

(B) Suspension type


Insulator.

(E) Egg or Stay


Insulator.

TYPES OF INSULATORS USED IN


OVERHEAD SYSTEM.
Pin type insulator.
Suspension type insulator.
Strain type insulator.
Shackle type insulator.
Egg or Stay insulator.
Ring type insulator

TYPES OF INSULATORS

APPLICATIONS OF INSULATOR
TYPES

APPLICATIONS

Pine type

L.T., H.T. distribution


Not above 66 kv

Suspension type

O.h. transmission
More than 33 kv

Strain type
Shackle type

At the end or sharp


curve
As strain insulator on
L.T. distribution

UNDERGROUND CABLE

UNDERGROUND CABLE
CLASSIFICATION OF CABLE:1. Low voltage (L.T.) cable (operating

Voltage up to 1 KV
2. High voltage (H.T)
Cable (operating voltage
Up to 11 KV)

4. Extra super tension


(E.H.T.) cable (operating
Voltage up to 66KV.

3.Super tension (S.T)


Cable (operating voltage
Up to 33 KV.)

5.Extra super voltage


Cable (operating voltage
up to 132 KV.

TYPES OF CABLE

UNDERGROUND CABLE
Core
Belted paper
Lead sheath
Bedding
Single wire
armoring
Overall Serving

UNDERGROUND CABLE
EXTRA SUPER VOLTAGE CABLE:Oil filled cables.
(A) Single core oil filled cables used up to 132 KV.
(B) Three core oil filled cables used up to 66 KV.
Gas pressure cables.
(A) External pressure cables.
(B) Internal pressure cable.
(a) High pressure gas filled cable.
(b) Gas cushion cable.
(c) Impregnated pressure cable

TYPES OF INSULATING MATERIALS USED IN


CABLE
Vulcanized
Vulcanized
India
India
Rubber
Rubber. .Impregnated
Varnished
Varnished
Impregnated
cambric
Paper.
cambric
Paper.

Polyvinyle
Polyvinyle
chloride
chloride

Types
Typesofof
Materials
Materials. .

Enamel
Enamel
Insulation.
Insulation.

Silk
Silk&&
Cotton
Cotton. .

Rubber.
Rubber.

UNDERGROUND CABLE
REQUIRED PROPERTIES OF INSULATING
MATERIALS FOR CABLE:High resitivity.
High dielectric strength.
Low thermal co-efficient.
Low water absorption.
Low permittivity.
Non inflammable.
Chemical stability.
High mechanical strength.
High viscosity at impregnation temperature.
Capability to with stand high rupturing voltage.
High tensile strength and plasticity.

UNDER GROUND CABLE


METHODS OF LAYING UNDER GROUND CABLE:-

1.Solid system.

2.Direct laying.

3. Draw-in
System.

UNDER GROUND CABLE


FAULTS WHICH ARE LIKELY TO OCCUR IN
UNDER GROUND CABLE:-

1. Insulating fault between


line and earth.
2. Insulation fail between
two core.
3. Open circuit fault.

References

www.google.com
www.wikipedia.com
www.fadooengineers.com
www.ieee.org
www.engineerszone.com

THANK YOU

You might also like