Transmission and Distribution Supply System
Transmission and Distribution Supply System
Transmission and Distribution Supply System
TRANSMISSION SYSTEM
In overhead transmission lines, the conductors are suspended from a pole or a tower via
insulators.
In addition to phase conductors, a transmission line usually includes one or two steel wires
called ground (shield) wires. These wires are electrically connected to the tower and to the
ground, and, therefore, are at ground potential.
In large transmission lines, these wires
are located above the phase conductors,
shielding them from lightning.
Transmission lines are characterized by a series resistance, inductance, and shunt capacitance
per unit length. These values determine the power-carrying capacity of the transmission line and
the voltage drop across it at full load.
STEP
STEP UP
UP TRANSFORMER
TRANSFORMER
REGULATOR
REGULATOR
STEP
STEP DOWN
DOWN TRNSFORMER.
TRNSFORMER.
CONDUCTOR
CONDUCTOR
LINE
LINE SUPPORT.
SUPPORT.
LINE
LINE ISULATOR
ISULATOR
TRANSMISSON LINE
LINE
TRANSMISSON
A.C. TRANSMISSION
TRANSMISSION
A.C.
A.C.THREEPHASE
PHASE
MID POINT
POINT EARTH
EARTH
A.C.THREE
MID
FOURWIRE
WIRESYSTEM
SYSTEM A.C.
A.C. SINGAL
SINGAL PHASE.
PHASE.
FOUR
A.C.SINGAL
SINGALPHASE
PHASE
A.C.
TWOWIRE
WIRESYSTEM
SYSTEM
TWO
A.C.THREEPHASE
PHASE
A.C.THREE
THREEWIRE
WIRE
THREE
D.C.TRANSMISION
D.C.TRANSMISION
D.C.TWOWIRE
WIRE
D.C.TWO
SYSTEM.
SYSTEM.
MIDPOINT
POINTEARTH
EARTH
MID
TYPESYSTEM.
SYSTEM.
TYPE
SUBSTATION
SUBSTATION
FUNCTION OF SUBSTATION:
SUBSTATION
CLASSIFICATION OF SUBSTATION:-
According to Service
1.Transformer sub-station
2.Industrial sub-station
3.Switching sub-station
4.Synchronous sub-station
5.Frequency sub-station
6.Converting sub-station.
SUBSTATION
CLASSIFICATION OF SUBSTATION:-
According to Design.
1.Indoor type
Sub-station.
(a) Pole mounted
Sub-station.
SUBSTATION
MAIN EQUIPMENTS USED IN SUBSTATION:1.Main
1.Mainbus
busbar.
bar.
2.Insulator
2.Insulator. .
3.Isolator
3.Isolator. .
4.Circuit
4.Circuitbreaker
breaker. .
5.Load
5.Loadinterrupter
interrupter
Switches.
Switches.
6.Fuses
6.Fuses. .
8.Current
8.Current&
&potential
potential 9.Indicating
9.Indicating&Metering
&Metering
7.Power
transformer
.
7.Power transformer.
Transformer.
Instrument.
Transformer.
Instrument.
10.Protective
10.Protectiverelays
relays. .
11.Carrier
11.Carriercurrent
current
Equipment.
Equipment.
12.Control
12.Controlcable
cable. .
DISTRIBUTION SYSTEM
TYPES OF DISTRIBUTION SYSTEM:-
1.Primary
distribution.
2.Secondary
distribution.
DISTRIBUTION SYSTEM
MAIN PARTS OF DISTRIBUTION SYSTEM:-
3.Service mains.
2.Distributor..
1.Feeder
DISTRIBUTION TRANSFORMER
DISTRIBUTION SYSTEM
METHODS OF FEEDING A DISTRIBUTOR:1.Redial system.
2.Ring mains
system.
3.Inter connected
grid
Type system.
(c) High
dielectric
strength
SUPPORT
*FUNCTION: It provides support to overhead conductor.
* SUPPORT AS A: Tower
Pole
CHARECTERISTICS OF SUPPORT
MATERIAL
(a) LOW
WEIGHT
(e) LONG
WORKING LIFE
(b) HIGH
MECHANICAL
STRENGTH
(C)HIGH
ACCESSIBILITY
(d) LOW
COST
Wood Pole
Steel pole
Rail pole
H type
Letasied steel
tower
Tubular pole
Single pole
RCC Pole
SAG
FACTORS AFFECTING ON SAG:-
FACTORS
FACTORS AFFECTING
AFFECTING ON
ON SAG
SAG..
Ice
Ice coating
coating
Wind
Wind pressure.
pressure.
Tempressure.
Tempressure.
Wight
Wight of
of conductor
conductor
Span
Span
Working
Working tensile
tensile strength
strength..
Capacitance.
Inductance.
Resistance
Resistance
RDC
(9.9.1)
rDC
A m
(9.9.1)
Resistance
The resistivity increases linearly with temperature over normal range of temperatures. If the
resistivity at one temperature is known, the resistivity at another temperature can be found from
T 2
M T2
T 1
M T1
(9.10.1)
Where T1 and T1 are temperature 1 in oC and the resistivity at that temperature, T2 and T2 are
temperature 2 in oC and the resistivity at that temperature, and M is the temperature constant.
The series inductance of a transmission line consists of two components: internal and external inductances,
which are due the magnetic flux inside and outside the conductor respectively. The inductance of a
transmission line is defined as the number of flux linkages [Wb-turns] produced per ampere of current
flowing through the line:
L
I
(9.12.1)
1. Internal inductance:
Consider a conductor of radius r carrying a current I. At a distance x from
the center of this conductor, the magnetic field intensity Hx can be found
from Amperes law:
H x dl I x
(9.12.2)
Where Hx is the magnetic field intensity at each point along a closed path, dl is a unit vector along that path
and Ix is the net current enclosed in the path. For the homogeneous materials and a circular path of radius x,
the magnitude of Hx is constant, and dl is always parallel to Hx. Therefore:
Ix
2 xH x I x H x
2 x
(9.13.1)
x2
Ix 2 I
r
(9.13.2)
x
Hx
I H m
2
2 r
(9.13.3)
xI
Bx H x
[T ]
2
2 r
(9.14.1)
The differential magnetic flux contained in a circular tube of thickness dx and at a distance x from the center
of the conductor is
xI
d
dx[Wb m]
2
2 r
(9.14.2)
The flux linkages per meter of length due to flux in the tube is the product of the differential flux and the
fraction of current linked:
x2
x3 I
d 2 d
dx[Wb turns m]
4
r
2 r
(9.14.3)
The total internal flux linkages per meter can be found via integration
x3 I
I
int d
dx [Wb turns m ]
4
2 r
8
0
r
(9.15.1)
int
lint
H m
I
8
(9.15.2)
If the relative permeability of the conductor is 1 (non-ferromagnetic materials, such as copper and
aluminum), the inductance per meter reduces to
0 4 107
lint
7 H m
8
8
(9.15.3)
Ix
I
Hx
2 x 2 x
(9.16.1)
I
Bx H x
2 x
(9.16.2)
The differential magnetic flux contained in a circular tube of thickness dx and at a distance x from the center of the conductor is
I
d
dx[Wb m]
2 x
(9.17.1)
The flux links the full current carried by the conductor, therefore:
I
d d
dx[Wb turns m]
2 x
(9.17.2)
The total external flux linkages per meter can be found via integration
D2
D2
I
I D1
ext d
dx
ln [Wb turns m]
2 x
2 D2
D1
D1
The external inductance per meter is
lex t
ex t
D2
ln H m
I
2 D1
(9.17.3)
(9.17.4)
dl I x
(9.18.1)
Since the path of radius x2 encloses both conductors and the currents are equal and opposite, the net current
enclosed is 0 and, therefore, there are no contributions to the total inductance from the magnetic fields at
distances greater than D.
The total inductance of a wire per unit length in this transmission line is a sum of the internal inductance and
the external inductance between the conductor surface (r) and the separation distance (D):
l lint lext
2
D
1
ln H m
r
4
(9.19.1)
By symmetry, the total inductance of the other wire is the same, therefore, the total inductance of a two-wire
transmission line is
1
D
l ln H m
4
r
Where r is the radius of each conductor and D is the distance between conductors.
(9.19.2)
Equations similar to (9.19.2) can be derived for three-phase lines and for lines with more phases In most of
the practical situations, the inductance of the transmission line can be found from tables supplied by line
developers.
Analysis of (9.19.2) shows that:
1.The greater the spacing between the phases of a transmission line, the greater the inductance of the line.
Since the phases of a high-voltage overhead transmission line must be spaced further apart to ensure proper
insulation, a high-voltage line will have a higher inductance than a low-voltage line. Since the spacing
between lines in buried cables is very small, series inductance of cables is much smaller than the inductance
of overhead lines.
2.The greater the radius of the conductors in a transmission line, the lower the inductance of the line. In
practical transmission lines, instead of using heavy and inflexible conductors of large radii, two and more
conductors are bundled together to approximate a large diameter conductor. The more conductors included
in the bundle, the better the approximation becomes. Bundles are often used in the high-voltage transmission
lines.
A two-conductor
bundle
A four-conductor
bundle
The series inductive reactance of a transmission line depends on both the inductance of the line and the
frequency of the power system. Denoting the inductance per unit length as l, the inductive reactance per unit
length will be
xI jl j 2 fl
(9.22.1)
where f is the power system frequency. Therefore, the total series inductive reactance of a transmission line
can be found as
X I xI d
where d is the length of the line.
(9.22.2)
Since a voltage V is applied to a pair of conductors separated by a dielectric (air), charges of equal magnitude
but opposite sign will accumulate on the conductors:
q CV
(9.23.1)
In AC power systems, a transmission line carries a time-varying voltage different in each phase. This timevarying voltage causes the changes in charges stored on conductors. Changing charges produce a changing
current, which will increase the current through the transmission line and affect the power factor and voltage
drop of the line. This changing current will flow in a transmission line even if it is open circuited.
The capacitance of the transmission line can be found using the Gausss law:
D dA
(9.24.1)
where A specifies a closed surface; dA is the unit vector normal to the surface; q is the charge inside the
surface; D is the electric flux density at the surface:
D E
(9.24.2)
where E is the electric field intensity at that point; is the permittivity of the material:
r 0
Relative permittivity of the material
The permittivity of free space 0 = 8.8510-12 F/m
(9.24.3)
Electric flux lines radiate uniformly outwards from the surface of the
conductor with a positive charge on its surface. In this case, the flux
density vector D is always parallel to the normal vector dA and is
constant at all points around a path of constant radius r. Therefore:
DA QD(2 xl ) ql
(9.25.1)
q
D
2 x
q
E
2 x
(9.25.2)
(9.25.3)
P2
V12 E dl
(9.26.1)
P1
where dl is a differential element tangential to the integration path between P1 and P2. The path is irrelevant.
D2
D2
D2
q
q
V12 Edx
dx
ln
2 x
2 D1
D1
D1
(9.26.2)
Vab ,a
qa
D
ln
2
r
(9.27.1)
or
qb
D
Vba ,b
ln
2
r
qb
D
Vab ,b
ln
2
r
(9.27.2)
(9.27.3)
qa
D qb
D
ln
ln
2
r 2
r
(9.28.1)
q
D
Vab
ln
r
(9.28.2)
The capacitance per unit length between the two conductors of the line is
q
q
cab
q
D
V
ln
r
(9.28.3)
Thus:
cab
D
ln
r
(9.29.1)
Which is the capacitance per unit length of a single-phase two-wire transmission line.
The potential difference between each conductor and the ground (or neutral) is one half of the potential
difference between the two conductors. Therefore, the capacitance to ground of this single-phase transmission
line will be
2
cn can cbn
D
ln
r
(9.29.2)
Similarly, the expressions for capacitance of three-phase lines (and for lines with more than 3 phases) can be
derived. Similarly to the inductance, the capacitance of the transmission line can be found from tables
supplied by line developers.
Analysis of (9.29.1) shows that:
1.The greater the spacing between the phases of a transmission line, the lower the capacitance of the line.
Since the phases of a high-voltage overhead transmission line must be spaced further apart to ensure proper
insulation, a high-voltage line will have a lower capacitance than a low-voltage line. Since the spacing
between lines in buried cables is very small, shunt capacitance of cables is much larger than the capacitance
of overhead lines. Cable lines are normally used for short transmission lines (to min capacitance) in urban
areas.
2.The greater the radius of the conductors in a transmission line, the higher the capacitance of the line.
Therefore, bundling increases the capacitance. Good transmission line is a compromise among the
requirements for low series inductance, low shunt capacitance, and a large enough separation to provide
insulation between the phases.
The shunt capacitive admittance of a transmission line depends on both the capacitance of the line and the
frequency of the power system. Denoting the capacitance per unit length as c, the shunt admittance per unit
length will be
yC j c j 2 fc
(9.31.1)
YC yC d j 2 fcd
(9.31.2)
where d is the length of the line. The corresponding capacitive reactance is the reciprocal to the admittance:
1
1
ZC
j
YC
2 fcd
(9.31.3)
Example
Example 9.1: An 8000 V, 60 Hz, single-phase, transmission line consists of two hard-drawn aluminum
conductors with a radius of 2 cm spaced 1.2 m apart. If the transmission line is 30 km long and the
temperature of the conductors is 200C,
a.What is the series resistance per kilometer of this line?
b.What is the series inductance per kilometer of this line?
c.What is the shunt capacitance per kilometer of this line?
d.What is the total series reactance of this line?
e.What is the total shunt admittance of this line?
l
R
A
Ignoring the skin effect, the resistivity of the line at 20 0 will be 2.8310-8 -m and the resistance per kilometer
of the line is
0.0225 km
2
A
0.02
Example
1
D
1
1.2
ln
1000
ln
1000
1.738
10
H
km
4
r
4
0.02
8.854 10
12
cab
1000
1000
6.794 10
9 F km
D
1.2
ln
ln
r
0.02
d. The series impedance per kilometer of the transmission line is
10
3
0.0225
j 0.655 km
Example
yC j 2 fc j 2 60 6.794 10
9
j 2.561 106 Sm
1
1
Z sh
j13.0k
5
Ysh j 7.684 10
TRANSMISSION LINE
CLASSIFICATION OF TRANSMISSION LINE:-
Classification of
Transmission line.
(1)Short Line.
( > 80 Km)
(2)
Medium line
(80 to 160 Km)
Unlike the electric machines studied so far, transmission lines are characterized by their distributed
parameters: distributed resistance, inductance, and capacitance.
The distributed series and shunt elements of the transmission line make it harder to model. Such parameters
may be approximated by many small discrete resistors, capacitors, and inductors.
However, this approach is not very practical, since it would require to solve for voltages and currents at all
nodes along the line. We could also solve the exact differential equations for a line but this is also not very
practical for large power systems with many lines.
Lines longer than 240 km (150 miles) are long transmission lines and are to be discussed later.
The total series resistance, series reactance, and shunt admittance of a transmission line can be calculated as
R rd
(9.37.1)
X xd
(9.37.2)
Y yd
(9.37.3)
where r, x, and y are resistance, reactance, and shunt admittance per unit length and d is the length of the
transmission line. The values of r, x, and y can be computed from the line geometry or found in the reference
tables for the specific transmission line.
IS IR
(9.38.1)
VS VR ZI VR RI jX L I
VR VS RI jX L I
which is very similar to the equation derived for a synchronous generator.
(9.38.2)
(9.38.3)
The ABCD constants can be physically interpreted. Constant A represents the effect of a change in the receiving
end voltage on the sending end voltage; and constant D models the effect of a change in the receiving end
current on the sending end current. Naturally, both constants A and D are dimensionless.
The constant B represents the effect of a change in the receiving end current on the sending end voltage. The
constant C denotes the effect of a change in the receiving end voltage on the sending end current.
Transmission lines are 2-port linear networks, and they are often represented by ABCD models. For the short
transmission line model, IS = IR = I, and the ABCD constants are
A 1
BZ
C 0
D 1
(9.51.1)
IC 2
Y
VR
2
(9.52.1)
I ser
Y
VR I R
2
(9.52.2)
VS ZI ser
YZ
VR Z I C 2 I R VR
1 VR ZI R
2
(9.53.1)
I S I C1 I ser
Y
Y
ZY
ZY
I C1 I C 2 I R VS VR I R Y
1 VR
1 I R (9.53.2)
2
2
4
ZY
1
2
BZ
A
ZY
1
4
ZY
D
1
2
C Y
(9.53.3)
For long lines, it is not accurate enough to approximate the shunt admittance by two constant capacitors at
either end of the line. Instead, both the shunt capacitance and the series impedance must be treated as
distributed quantities; the voltages and currents on the line should be found by solving differential equations of
the line.
However, it is possible to model a long transmission
line as a model with a modified series impedance Z
and a modified shunt admittance Y and to perform
calculations on that model using ABCD constants.
The modified values of series impedance and shunt
admittance are:
Z' Z
sinh d
d
tanh d 2
Y 'Y
d 2
(9.54.1)
(9.54.2)
Here Z is the series impedance of the line; Y is the shunt admittance of the line; d is the length of the line; is
the propagation constant of the line:
yz
(9.55.1)
where y is the shunt admittance per kilometer and z is the series impedance per km.
As d gets small, the ratios approach 1.0 and the model becomes a medium-length line model. The ABCD
constants for a long transmission line are
Z 'Y '
A
1
2
BZ'
Z 'Y '
C Y '
1
4
Z 'Y '
D
1
2
(9.55.2)
INSULATOR
CONDUCTOR
SUPPORT
Nominal
Nominal
END
END
Capacitance
Capacitance
Short
Shortlength
lengthSingle
Single
Phase
Phaseline.
line.
Short
Shortlength
lengththree
three
Phase
Phaseline.
line.
Long
Longlength
lengthtransmission
transmission
Line.
Line.
CORONA
CORONA
FACTORS AFFECTING ON CORONA LOSS:-
Factors affecting on
corona loss.
(1)Condition on the
Atmosphere.
CORONA
METHODS USED TO REDUCE CORONA LOSS:-
*Use of bundle
Conductor.
*Increase of conductor
Diameter.
(C) Strain
Insulator.
(D)Shackle type
Insulator.
TYPES OF INSULATORS
APPLICATIONS OF INSULATOR
TYPES
APPLICATIONS
Pine type
Suspension type
O.h. transmission
More than 33 kv
Strain type
Shackle type
UNDERGROUND CABLE
UNDERGROUND CABLE
CLASSIFICATION OF CABLE:1. Low voltage (L.T.) cable (operating
Voltage up to 1 KV
2. High voltage (H.T)
Cable (operating voltage
Up to 11 KV)
TYPES OF CABLE
UNDERGROUND CABLE
Core
Belted paper
Lead sheath
Bedding
Single wire
armoring
Overall Serving
UNDERGROUND CABLE
EXTRA SUPER VOLTAGE CABLE:Oil filled cables.
(A) Single core oil filled cables used up to 132 KV.
(B) Three core oil filled cables used up to 66 KV.
Gas pressure cables.
(A) External pressure cables.
(B) Internal pressure cable.
(a) High pressure gas filled cable.
(b) Gas cushion cable.
(c) Impregnated pressure cable
Polyvinyle
Polyvinyle
chloride
chloride
Types
Typesofof
Materials
Materials. .
Enamel
Enamel
Insulation.
Insulation.
Silk
Silk&&
Cotton
Cotton. .
Rubber.
Rubber.
UNDERGROUND CABLE
REQUIRED PROPERTIES OF INSULATING
MATERIALS FOR CABLE:High resitivity.
High dielectric strength.
Low thermal co-efficient.
Low water absorption.
Low permittivity.
Non inflammable.
Chemical stability.
High mechanical strength.
High viscosity at impregnation temperature.
Capability to with stand high rupturing voltage.
High tensile strength and plasticity.
1.Solid system.
2.Direct laying.
3. Draw-in
System.
References
www.google.com
www.wikipedia.com
www.fadooengineers.com
www.ieee.org
www.engineerszone.com
THANK YOU