Compression Member
Compression Member
Columns Theory:
Stocky columns (short) fail by yielding of the material at
the cross section, but most columns fail by buckling at P P
loads for less then yielding forces. (a) (b)
C-1
For slender columns, Euler (1759) predicted the critical buckling load (P cr)
also known as Euler Buckling Load as:
Pcr
2 EI
Pcr 2 (C 1)
L
where: E = Young Modulus of Elasticity.
I = Minor moment of Inertia.
L = Unbraced length of column.
if B 0, then cL = n where n = 0, 1, 2, 3
cL =
Note: The critical buckling load
Pcr
L is a function of the section
EI
2EI properties (A, L, r) and
Pcr 2 ---- Euler Buckling Critical Load
L the modulus of elasticity
2E Ar 2
for material, and is not a
L2 where: r = minor radius of gyration
2EA function of the strength or
L / r 2 grade of the material.
2
Pcr E
Fcr (C 2)
Ag L
r
2
C-3
Example C-1
Find the critical buckling load for W 12 x 50, supported in a pinned-pinned
condition, and has an over-all length of 20 feet?
Solution:
2E
Fcr
Lr 2
rmin = ry = 1.96 inch (properties of section).
2 29000
Fcr 19 ksi
2012 2
1.96
Pcr = Fcr A = 19.1 x 14.7 = 280.8 kips
Note:
The steel grade is not a factor affecting buckling,
also note Fcr << Fy.
C-4
For short (stocky) columns; Equation (C-2) gives high values for
(Fcr), sometimes greater then proportional limit, Engessor (1889)
proposed to use (Et) instead of (E) in Euler formula:
2 Et I
Pcr 2
(C 3)
L
where:
Et = Tangent Modulus of Elasticity
Et < E
When (Fcr) exceeds (Fpl), this is called
Inelastic Buckling, constantly variable
(Et) need to be used to predict (Fcr)
in the inelastic zone.
Shanley (1947), resolved this inconsistency.
C-5
Depending on (L/r) value the column buckling
strength was presented as shown by Shanley.
Residual Stresses:-
Due to uneven cooling of hot-rolled sections,
residual stresses develop as seen here.
C-6
The Euler buckling formula (C-1) is based on:
where:
1 Perfectly straight column. (no crookedness).
K = Effective length factor.
2 Load is concentric (no eccentricity).
(Kl) = Effective length.
3 Column is pinned on both ends.
(Kl/r) = Effective slenderness ratio.
The Previous conditions are
very difficult to achieve in a realistic
building condition, especially the free
rotation of pinned ends. Thus an
effective slenderness factor is
introduced to account for various end
conditions:
Thus:
2E 2E t
Fcr , or Fcr C 4
KL r 2 Klr 2
see commentary
(C C2.2) (page 16.1-240)
C-7
AISC (Chapter E) of LRFD code stipulates:
Pu (factored load) c Pn
where:
Pu = Sum of factored loads on column.
c = Resistance factor for compression = 0.90
Pn = Nominal compressive strength = Fcr Ag
Fcr = Critical buckling Stress. (E3 of LFRD)
a) for
Kl
4.71 E
Fy
or F e 0.44Fy
r
Fy
Fcr 0.658 Fe
Fy E - 3.2
b) for
Kl
4.71 E
Fy
or F e 0.44Fy
r
Fcr 0.877Fe E - 3.3
where:
2E
Fe E - 3.4
KL 2
r C-8
The above two equations of the LRFD
code can be illustrated as below:
where:
Kl Fy
c
r E
C-9
Example C-2
Determine the design compressive strength (cPn) of W 14x74 with an
untraced length of (20 ft), both ends are pinned, (A-36) steel is used?
Solution: Fy
Fcr 0.658 Fy (0.658)1.178 x 36
Fe
Kl =1 x 20 x 12 = 240 in
rmin = ry = 2.48 0.611 36 21.99 ksi
Kl 240
c Pn = 0.9 x Fcr x Ag = 0.9 x (21.99) x 21.8
96.77 200 (0k)
r 2.48
max.
= 433.44 kips (Answer)
2E 2 x2900
Fe 2
30.56 ksi
Kl (96.77) 2
Also from (table 4-22) LFRD Page 4-320
r
c Fcr = 19.75 ksi (by interpolation)
0.44 Fy = 0.44 x 36 =15.84 ksi c Pn = c Fcr Ag = 430.55 kips
Fe 0.44 Fy Equ. E-3.2 (much faster)
(controls) C-10
For must profiles used as column, the
buckling of thin elements in the section
may proceed the ever-all bucking of
the member as a whole, this is called
local bucking. To prevent local bucking
from accruing prior to total buckling.
AISC provides upper limits on width to
thickness ratios (known as b/t ratio) as
shown here.
See also:
Part 1 on properties
of various sections.
C-11
Depending on their ( b/t ) ratios (referred to as ) ,
sections are classified as:
a) Compact sections are those with flanges fully welded
(connected) to their web and their:
p (AISC B4)
b) Non compact Sections:
p r (B4)
c) Slender Section:
> r (B4)
r
A) By direct LRFD
Fe 0.44 Fy ( 22 ksi) Equ. (E 3.2)
From properties: 50
Ag =19.1 in2 Fcr 0.658 Fy 96.2
rx = 5.28 in
0.8045 x 50 40.225 ksi
ry = 3.02 in
15 ft.
Solution: A A
x
x-axis Lx = 25 ft, kx = 0.8, rx = 5.89 in. x x
x
y-axis
Section (AB) Ly = 15 ft, ky = 0.8, ry = 1.92 in.
Section (BC) Ly = 10 ft., ky = 1.0, ry = 1.92 in.
Kl 0.8 25 12
41 Enter table (4-22) , Fc = 24.1 ksi
r x 5.98
Kl
max
0.8 15 12 Column capacity Pn = Fcr Ag = 24.1 x 15.6 = 376 kips
75
r y 1.92 (controls)
C-15
Design with Columns Load Table (4) LFRD:-
A) Design with Column Load Table (4) LFRD:
The selection of an economical rolled shape to resist a given
compressive load is simple with the aid of the column load tables.
Enter the table with the effective length and move horizontally until
you find the desired design strength (or something slightly larger). In
some cases, Usually the category of shape (W, WT, etc.) will have
been decided upon in advance. Often the overall nominal
dimensions will also be known because of architectural or other
requirements. As pointed out earlier, all tabulated values correspond
to a slenderness ratio of 200 or less. The tabulated unsymmetrical
shapes the structural tees and the single and double-angles
require special consideration and are covered later.
C-16
EXAMPLE C - 5
A compression member is subjected to service loads of 165 kips dead load
and 535 kips live load. The member is 26 feet long and pinned in each end.
Use (A572 Gr 50) steel and select a W14 shape.
ANSWER
Use a W14 145, But practically W14 132 is OK.
C-17
EXAMPLE C - 6
Select the lightest W-shape that can resists a factored compressive load P u of
190 kips. The effective length is 24 feet. Use ASTM A572 Grade 50 steel.
SOLUTION
The appropriate strategy here is to fined the lightest shape for each nominal
size and then choose the lightest overall. The choices are as follows.
W4, W5 and W6: None of the tabulated shape will work.
W8: W 8 58, cPn = 205 kips
W10: W10 49, cPn = 254 kips
W12: W12 53, cPn = 261 kips
W14: W14 61, cPn = 293 kips
Note that the load capacity is not proportional to the weight (or cross-
sectional area). Although the W8 58 has the smallest design strength of
the four choices, it is the second heaviest.
ANSWER Use a W10 49. C-18
Example C-7
Select the lightest W 10 section made of
A 572-Gr50 steel to resist a factored load
of (600 kips) ?
Solution:
Assume weak axis (y-y) controls buckling:
Enter design tables of AISC (Section 4) with KyLy = 9 ft.
Select W 10 x 54 (capacity = 625 k > 600 k OK)
Check strong axis buckling strength:
Solution:
Try Fcr = 24 ksi (two-thirds of Fy):
Pu 1054
Required gA 48 . 8 in 2
2E 2 x29000
Fe 22.9 ksi
2
Kl 111.8 2
r
Fe 0.44 Fy (15.84) LRFD Equ. E . 3.2 C-21
Fy
36
Fcr 0.658 Fe Fy 0.658 x36 0.532 x 36
22.9
18.64 ksi
cPn 0.9 A gFcr 0.9 x 56.4 x 18.64 943kips 1054 k
(N.G.)
Try Fcr 18.64 ksi (the value just computed for the W18 x 192) :
Pu 1054
Required A g 62.83 in2
cFcr 0.9(18.64)
Try W18 x 234 :
A g 68.8 in2 . 62.83 in 2
KL 26(12)
109.5 200 (OK)
rmin 2.85
C-22
2E 2 29000
Fe 23.87ksi
Klr 2 109.5 2
cPn 0.9 A gFcr 0.9 x 68.8 x 19.15 1185 kips 1054 k (OK)
This shape is not in the column load tables, so the width - thickness
ratios must be cheacked :
bf 95
2.8 15.8 (OK)
2t f 36
h 253
13.8 42.2 (OK)
tw 36
a) Diagonal
bracing
b) Shear Walls
(masonry,
reinforcement concrete
or steel plate)
C-24
Ic /L c where
GA
Ig /L g A is top of column
Ic /L c where
GB
Ig /L g B is bottom of column
Solution:
W12 x 96
12'
Column (AB): W24 x 55 W24 x 68
A
W12 x 120
Joint (A): 12'
W24 x 55 W24 x 68
Ic /L c B
GA
W12 x 120
Ig /L g 15'
0.94
C-26
For joint B,:-
Ic /L c 1070/12 1070/15 160.5
G 0.95
Ig /L g 169.2 169.2
From the alignment chart for sideways uninhibited, with GA = 0.94 and GB = 0.95,
Kx = 1.3 for column AB.
Column (BC):
C-30
Example C 10 :- Calculate the capacity of the built-up column shown below.
Lx = Ly = 25 ft, Kx = 1.6, Ky = 1.0 Fy = 42 ksi ?
Solution:-
Ixx 2 110 8x 21 (5 0.25) 2 440.5 in4
Iyy 27.25 7.35(5 0.953) 2
( 121 21 83 ) 298 in4
A g 2 7.35 4 22.70 in2
Ixx 440.5
rx 4.41 in
A 22.70
Iyy298.0 From table 4.22 page 4.321
ry 3.62 in
A 22.70 cFcr = 18.3 ksi
K xlx 1.6 25 12
108.84 (controls)
rx 4.41 Design Nominal Strength = cFcr Ag
K yl y 1.0 25 12 =18.3 x 22.70
82.90
ry 3.62 = 415.4 kips. C-31
The effective length factor (K) was introduced in page (C-7) for six ideal conditions,
these are not encountered in practical field conditions. LRFD commentary provides
both real conditions and standard ideal conditions (C-C2.2) (page 16.1-239 to 242)
Braced Frames: Unbraced Frames:
No lateral movement is allowed Lateral movement possible
(0.5 < K < 1.0) (sideway prevented) (1.0 < K < 20.0) (sideway allowed)
a) Diagonal
bracing
b) Shear Walls
(masonry,
reinforcement concrete
or steel plate)
C-23
Ic /L c where
GA
Ig /L g A is top of column
Ic /L c where
GB
Ig /L g B is bottom of column
C-25
For joint B,:-
Ic /L c 1070/12 1070/15 160.5
G 0.95
Ig /L g 169.2 169.2
From the alignment chart for sideways uninhibited, with GA = 0.94 and GB = 0.95,
Kx = 1.3 for column AB.
Column (BC):