Discharge Detection Using Straight Detectors

This document discusses discharge detection using straight detectors. It describes the components of a straight detector system, including a HV transformer, resonant filter, test object, coupling capacitor, detection impedance, band pass filter, and amplifier. It provides examples of discharge patterns that can be detected from corona, voids in insulating materials. However, it notes that straight detectors have drawbacks like noise problems, ineffective filtering, difficulty rejecting external disturbances, and difficult tuning of filters.

Uploaded by

Joyson Pereira
Copyright
© © All Rights Reserved
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
978 views

Discharge Detection Using Straight Detectors

This document discusses discharge detection using straight detectors. It describes the components of a straight detector system, including a HV transformer, resonant filter, test object, coupling capacitor, detection impedance, band pass filter, and amplifier. It provides examples of discharge patterns that can be detected from corona, voids in insulating materials. However, it notes that straight detectors have drawbacks like noise problems, ineffective filtering, difficulty rejecting external disturbances, and difficult tuning of filters.

Uploaded by

Joyson Pereira
Copyright
© © All Rights Reserved
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 10

Discharge Detection using

straight detectors
2

Discharge Detection Methods


Various methods are available for measuring
discharge detection especially for analyzing
Partial Discharge (PD).
1.Discharge Detector using straight detectors
2.Balanced detection methods
3.Narrow band & Wide band circuits
Discharge Detection using straight
detectors
Component descriptions of
straight detectors
HV Transformer is free from discharge
The resonant filter is used to prevent any pulses
starting from the capacitance of the windings and
bushings of the transformer
Cx is the test object- 100 pF to 0.1pF
Cc is the coupling capacitor
Zm is the detection impedance
The signal is developed across detection impedance Zm
Then the signal is passed through band pass filter
(10kHz frequency) ,amplifier and displayed Unit (on the
CRO & multi channel analyzer unit).

30
Discharge patterns

Input side
Discharge patterns - corona
Discharge patterns voids in
insulating materials
Discharge patterns voids in
insulating materials
Drawbacks of straight detectors
Noise problems.
The filter used to block the noise sources may
not be effective.
External disturbances are not fully rejected.
Tuning of filters is a difficult task.