Electrical Systems in Power Plants - An Overview
Electrical Systems in Power Plants - An Overview
Electrical Systems in Power Plants - An Overview
- An overview
Conventional Power Plant – 3D rendering
The innards of a Gas Turbine
Electrical System – The Vital
Link..
Electrical systems in a power plant are a vital link in the
process of power generation. The vital link includes:
Starting
Generation
Power evacuation & distribution
Control of auxiliary system
Support systems
Emergency backup
Elect. Power to start a power plant
The auxiliaries of a power plant which needs to be put into operation for plant
startup are mostly driven by electrical motors and in some instances using
steam turbine as prime movers ( eg.: feed pumps, fans etc..).
HV: 33,110,132,220 KV
EHV: 110,132,220,400,765 KV
Em./ BS
DG: MV
MV: 4.2,6.6,11,13.8kV
MV: 3.3,6.6,11kV
M M
DC: 125,220 V UPS: 110,220 V
DC: 110,220 V UPS: 110,220 V
Em. DG: LV Em. DG: LV
Typical for Coal PP Typical for GT PP
Generation system
The generation system essentially consists
of the following: Air,H2 or Water cooled
Voltage level
MVA & MVAR capability
• Generator
IPBD
• Excitation system Static
Brushless
SPBD
Cables
Water-cooled
Hydrogen-cooled
Load interconnection – Grid connected PP
To Grid (Load) To Grid (Load)
• Startup power is usually taken from grid by
EHV: 110,132,220,400,765 KV backcharging the elect. system
• All the generated power, less station loads
is exported
• Generally MV & LV system expansion is not
expected
• Normally grid disturbance (black out)
MV: 3.3,6.6,11kV
results in unit tripping.
Gen: 11,15.75,21kV
M
LV: 380,400,415,480 V
M
DC: 110,220 V UPS: 110,220 V
Em. DG: LV
Load Interconnection- Captive PP
To Grid (Back up)
• Startup power is either taken from
grid or from local generation (DG
HV: 33,110,132,220 KV
set !)
• Grid is usually used as a backup
• All the generated power, less
MV: 11kV
station loads normally consumed
Em./ BS
DG: MV
Consumers
• Generally HV & MV system is
M expanded to cater to industry
MV: 3.3, 6.6kV
expansion
Consumers
Gen: 11,15.75 kV M
• Normally grid disturbance
LV: 380,400,415,480 V
results in unit Islanding.
• Load shedding is adopted to
M balance generation and load and
DC: 125,220 V UPS: 110,220 V
to optimise use of spinning
Em. DG: LV
reserve of captive units
Power Evacuation.…
Typical power evacuation concepts for grid connected and captive power
plants:
1 2 3 4 5 6
What is an auxiliary system of a power
plant?
ELECTRICAL LOAD LIST
Support Systems
In a power plant in addition to catering to the auxiliaries of
the power plant, the following support systems are
engineered as a part of the electrical discipline.
Safety • Operation
• Shutdown
Adding a bit
of aesthetics
for TG bldg.
lighting !.
Some practices…
Use of
Cable
Junction box
at motor
end!
A great opportunity lies ahead of you to shape your career,
seize those opportunities as you encounter them because;