SWGRM
SWGRM
SWGRM
PMI Revision 00
Presentation outline
Basics of switchgear Components and Classification Basic design aspects Breakers, relays and fuses Typical parameters
PMI Revision 00
What is a Switchgear ?
The apparatus used for Switching, Controlling and Protecting the Electrical Circuits and equipment.
Need of Switchgear :
* Switching during normal operating conditions for the purpose of Operation and Maintenance. * Switching during Faults and Abnormal conditions and interrupting the fault currents.
PMI Revision 00
SWITCHGEAR
Historical background : up to 1875 : knife switches 1885 1900 : Bulk Oil circuit breaker : Arc extinction devices, MOCB
PMI Revision 00
PARTS OF SWITCHGEAR
Switching device
Power circuit
Control circuit
Protection
May 24, 2012 PMI Revision 00 5
Switching devices : Circuit breakers / contactors Isolators Earthing switch Control Circuit : service / test /isolated position selectors Tripping and closing circuit Spring charging, anti pumping arrangement Supply monitoring , space heaters , indications Measurement : Ammeter, voltmeter, energy meter Protection : Relays, CT, PT,
May 24, 2012 PMI Revision 00 6
Circuit Breaker
Earthing switch
Lightening Arrestor
CT
PT
Ammeter
Voltmeter
PMI Revision 00
CLASSIFICATION OF SWITCHGEARS : Method of arc quenching : Bulk oil, Min. oil, Air Break, Air Blast, SF6 , Vacuum Working voltage : 440 v, 6.6 kV, 11 kV, 400 kV etc. Indoor / out door SOME INTERLOCKS : Check synchronisation for closing Master relay contacts for trip and close HV & LV Breaker interlocks Main / Reserve supply change over
PMI Revision 00
PMI Revision 00
10
PMI Revision 00
11
PMI Revision 00
12
VSTPP -II are being controlled normally from remote through DDCMIS/PLC. The control Switch located on the Switchgear is normally used only for testing. All the logic for incomers, buscouplers , ties, transformer feeders and motor feeders is being generated in DDCMIS only . The reverse blocking schemes are still incorporated in Swgr(hardwired) In earlier projects these logics were generated in Swgr / remote panel (HARDWIRED). Such a type of control has facilitated Flexibility ,simpler wiring and helped in standardizing interface requirements . A typical Control scheme being implemented in Talcher-II is as displayed. Isolation Transformers for Lighting distribution to limit the fault of lighting Boards to 9 KA. Safety Measures for Switchgear include provision of insulated mats in front.
May 24, 2012 PMI Revision 00 13
Basic design features: Control and Safety onwards all Circuit Breakers/contactors
PMI Revision 00
14
Motors
May 24, 2012 PMI Revision 00 15
DC Chargers
Relays
PMI Revision 00
16
Relay :
A device that detects the fault and initiates the operation of the Circuit breaker to isolate the defective element from the rest of the system. The relay detects the abnormal conditions in the electrical circuits by constantly measuring the electrical quantities which are different under normal and faulty conditions.
PT
CT
CB
Source RELAY
May 24, 2012 PMI Revision 00
Load
17
without disturbing the rest of the system. Speed - Ability to disconnect the faulty part at the earliest possible time. Sensitivity - Ability of the relay to operate with low value of actuating quantity. Reliability - Ability of the system to operate under predetermined May 24, 2012 PMI Revision 00 18 conditions
Simplicity - Should be simple so that it can be easily maintained. - The simpler the protection scheme, the greater is the reliability Economy - Availability at lower cost. - Generally, the protective gear should not cost more than 5% of the total cost. However, when the apparatus to be protected is of utmost importance (e.g. Generator, GT etc) economic conditions are subordinated to reliability.
PMI Revision 00
19
Electromagnetic & Electro thermal * Attracted Armature * Induction disc * Printed disc dynamometer * Permanent magnet * Moving coil * Polarised moving Iron * Bimetallic Strip
May 24, 2012
Static
* Relay consists of Electronic circuitry such as Transistors, ICs, Diodes etc * Uses VLSI technology * Can be Programmed
PMI Revision 00 20
* Current based, with and without directional feature. * Voltage based * Impedance based * Frequency based * Power based, with and without directional feature
PMI Revision 00
21
Circuit Breakers
PMI Revision 00
22
* Movable Contact * Operating Mechanism and control circuit * Arc extinguishing medium
PMI Revision 00
23
CT
RELAY
CB
Trip Coil
DC supply
PMI Revision 00 24
Few definitions :
Breaking Capacity: Max fault current at which a CB capable of breaking. Making Capacity: Max current a CB can withstand if it closing on existing Short circuit. Restriking Voltage: After the arc has been extinguished, the voltage across the breaker terminals does not normalize instantaneously but it oscillates The transient voltage which appears across the breaker contacts at the instant of arc being extinguished. Recovery Voltage: Power frequency voltage which appears across the breaker contacts after the arc is finally extinguished and transient oscillations die out.
May 24, 2012 PMI Revision 00 25
is
PMI Revision 00
26
Arcing phenomenon :
- When a fault occurs, heavy current flows through the contacts of the circuit breaker before they are opened by the protective system. - At the instant when the contacts begin to separate, the contact area decreases rapidly and current density (I/A) increases and hence rise in temperature. -The heat produced is sufficient to ionise the medium between the contacts. This ionised medium acts as conductor and an arc is struck between the contacts. - The potential difference between the contacts is very small and is sufficient to maintain the arc. - The current flow depends upon the Arc resistance.
May 24, 2012 PMI Revision 00 27
Relay time
to
PMI Revision 00
29
Air Break CB :
PMI Revision 00
30
Air Blast CB :
PMI Revision 00
31
32
Bulk Oil CB :
PMI Revision 00
33
Minimum Oil CB :
PMI Revision 00
34
SF6 CB :
8. Puffer cylinder 9. Nozzle 10. Fixed position 11. Fixed contact 12. Moving contact 13. Gas inlet
35
Advantage of SF6
* Inert gas with high dielectric
strength.
* Colour less and odour less. * Non-toxic and non- inflammable. * Sf6 is blown axially to the arc, hence it removes the heat by axial convection and radial dissipation. As a result the arc dia reduces and comes to zero at current zero. * Gas pressure in the chamber is at 5 ksc. * SF6 is filled at a pressure of 12 ksc in the tank and maintained by means of an individual or a common compressor. * The decomposition products of arcing are not explosive hence no chance of fire. Disadvantages * SF6 gas condensates at low temperature & high pressure
May 24, 2012 PMI Revision 00 36
Vacuum CB :
PMI Revision 00
37
Advantage of vacuum CB
* Used
up to 66 KV. * Vacuum is of the range of 106 to 108 torr. * Vacuum is highly dielectric, so arc cant persists. * Separation of contacts causes the release of metal vapour from the contacts, the density of vapour depends on the fault current. * At current zero the vapour emission will tends to zero and the density will becomes zero and dielectric strength will build up and restriking will be prevented. * No emission to atmosphere, hence pollution free. * Non- explosive and silent operation. * Compact size.
May 24, 2012 PMI Revision 00 38
Disadvantage of vacuum CB
* High
initial cost. * Surge suppressors (R or RC combination) are to be connected at load side for limiting switching overvoltage while switching low pf loads.
PMI Revision 00
39
PMI Revision 00
40
Few definitions :
Rated current : - Current which can be carried without fusing Minimum fusing current : - Min value of the rms current at which the fuse melts. Fusing factor : - FF = Min fusing current / Rated current Prospective current : - Current which would have flown if the fuse is absent. Cut-off current : - Maximum value of fault current actually reached before the fuse elements melts.
PMI Revision 00
41
Characteristics of Fuse :
I Prospective current
Pre-arcing time
May 24, 2012
Arcing time
PMI Revision Total operating 00 42
PMI Revision 00
43
Types of Fuses :
LV fuses
Semi-enclosed rewirable fuse : - consists of porcelain base and a fuse carrier. - used where low currents are to be interrupted. - used in domestic and lighting applications HRC cartridge fuse : - consists of heat resistant ceramic body and the cartridge is filled with filler material such as chalk, plaster of Paris, quartz or marble dust which acts as arc quenching and cooling medium. - when fuse element (silver) melts, high resistance substance is formed due to the chemical reaction between the silver vapor and the filling powder. Thus Arc is quenched.
May 24, 2012 PMI Revision 00 44
HV fuses
(i) Expulsion type : - consists of hollow tube made of synthetic-resin bonded paper in which fuse wire is placed - when fuse element melts, it causes decomposition of the inner coating of the tube resulting in formation of gases which extinguishes the arc. - used in the level of 11 KV, 250 MVA and generally used for protection of distribution transformers. (ii) Drop-out fuse : - Expulsion type fuse. - when fuse melts, the fuse element carrying tube drops down due to gravity, so that, can be spotted easily.
May 24, 2012 PMI Revision 00 45
Coordination between Fuses and a O/C protection devices: Char of Fuse Char of O/C prot devices Capacity of Circuit breaker
PMI Revision 00
46
STAGE-II
RATING 6.6 KV 11KV 415V MAKE SIEMENS SIEMENS EE QUENCHING MEDIUM VACUUM VACUUM AIR
PMI Revision 00
47
OS I
LOCATION SLURRY P/H-1 RAW WATER P/H COMPR: - 1 COLONY S/S CW P/H 1 RATING 415 V 6.6 KV 6.6 KV 11 KV 6.6 KV MAKE NGEF ASEA/ ABB ASEA GEC ASEA/ ABB MEDIUM AIR MOCB/ VACCUM MOCB MOCB MOCB/SF6/ VACUUM
PMI Revision 00
48
OS II & 33KV
LOCATION SLURRY P/H - 2 CW P/H - 2 DM PLANT MCC 33 KV S/S 1&2
May 24, 2012
S/Y
Make AEG NGEF BHEL ABB BHEL
May 24, 2012
Voltage Rating (KV) 400 220 & 400 220 & 400 220 & 400 132
Operating Mechanism
CENTERALISED AIR COMPRESSOR SYSTEM INDIVIDUAL AIR COMPRESSOR SYSTEM HYDRAULIC INDIVIDUAL AIR COMPRESSOR SYSTEM MOTORISED
PMI Revision 00
PMI Revision 00
51
AEG (Air) 37 34
30 42
27.3 42
253 NA
23 33
PMI Revision 00
52
THANK YOU