Files For You
Files For You
Files For You
1. Phase
Single-phase or three-phase
2. Control
Hydraulic or electronic
3. Interrupters
Oil or Vacuum
4. Insulation
Oil , Air or Epoxy
SINGLE-PHASE RECLOSERS
1. Triple-Single tripping
(Ex. NOVA Type TS
reclosers)
2. Three-phase tripping
(Ex. Type KFME, WE, WVE,
VWVE reclosers)
Modes of Operation of Triple-Single
Tripping Reclosers
1. Three-phase trip & three-phase lockout
All 3 phases simultaneously trip on an
overcurrent, reclose, and sequence together.
2. Single-phase trip & three-
phase lockout
Each phase senses line
current & only the phase of
the faulted line will trip. If
any one phase sequences to
lockout, the other 2 phases
also open & lockout
2. Single-phase trip & single-phase lockout
Each individual phase trips and sequences to
lockout independent of each other.
Modes of Operation of Three-Phase
Tripping Reclosers
1. Oil Interrupters
• Reclosers using
oil for current
interruption use
the same oil for
basic insulation.
• Some reclosers
with hydraulic
control also use
the same oil for
timing and
counting
functions.
TYPES OF INTERRUPTING MEDIUM
2. Vacuum Interrupters
• On taps or laterals to
protect the main line
from troubles on these
taps or laterals.
RECLOSER APPLICATION CRITERIA
1. System voltage
2. Maximum fault current available at its
location
3. Maximum load current
4. Minimum fault current within the zone to
be protected
5. Coordination with other devices on both
the source and the load sides
RECLOSER APPLICATION CRITERIA
1. System voltage
The recloser must have a voltage rating
equal to — or greater than — the system
voltage.
4. Non-reclosing Lever
Found on Type DV
reclosers, this sets the
unit to one shot to
lockout after fault
interruption
RECLOSER CONTROL SETTINGS
1. Number of Operations
Determines the number of operations of the
recloser to lockout and also the number of
operations the timing plugs for the ground-trip
and phase-trip are to be used.
MERALCO reclosers are set to 3 counts to
lockout and the number of fast trip operations
set to 1.
5. Reset Delay
• The reset delay is the time interval after which
the count in the recloser’s memory is cleared.
• This usually occurs when a temporary fault is
cleared before lockout occurs.
• Reset times from 10 to 180 seconds are
available.
• A ten (10) second reset time is used by
MERALCO.
Ground Trip Setting Consideration
VOLTAGE
RATING
TYPE PHASE COUNT TYPICAL SETTINGS
VWVE 3 67 1. Shots to L.O. : 3
38 kV WVE 3 16 2. Reset Time : 10 sec.
DV 1 8 3. Minimum Trip Current
KFME 3 28 Ground : 200, 100, 70, etc.
15.5 kV
WE 3 6 Phase : 340, 240, 200, etc.
TOTAL COUNT 125
4. Number of Fast Trips
Ground : 1 (None for Type DV)
Phase :2
5. Reclosing Time
First : 2 seconds
Second : 15 seconds
6. TCC Curves
Ground :1&8
Phase :A&D
MERALCO’S EXISTING RECLOSERS
Specifications Summary
Specifications Summary
Nominal System Voltage (kV) 24.9 - 34.5
Maximum Rated Voltage (kV) 38
BIL (kV) 150
The DV Reclosers’
sleet hood,
showing the
manual operating
handle, non-
reclosing lever
and contact
position indicator.
Also found under
the sleet hood is
the operations
counter.
THE KYLE TYPE DV RECLOSER
Major Components
Major
Components
1. Arc interrupting
Assembly
• Heart of the
recloser
• Circuit opening is
achieved by a
double-break
moving contact
assembly
THE KYLE TYPE DV RECLOSER
Major
Components
2. Closing Solenoid
• Closes the moving
contacts and also
extends the
opening spring
located in the head
assembly.
• Only energized a
few cycles during
the closing
operation
THE KYLE TYPE DV RECLOSER
Major
Components
3. Closing Solenoid
Contactor
• Completes the
closing solenoid
circuit during the
closing operation
THE KYLE TYPE DV RECLOSER
Major Components
Cutaway
view of
hydraulic
integrator
Hydraulic
integrator
& time-
delay unit
THE KYLE TYPE DV RECLOSER
Major
Components
5. Series Trip Solenoid
• This device carries full
line current
• When current greater
than the min trip value
flows, the solenoid
plunger moves
downward causing a
trip operation
• For delayed operations
the plunger is
restrained by a time-
delay unit, & requires
more time to trip the
recloser
THE KYLE TYPE DV RECLOSER
Major Components
6. Time-Delay Unit
• A sealed time-delay unit provides consistent delay
action by forcing hydraulic fluid through orifices
• In order to ensure reliable timing characteristics, the
fluid in the time-delay units is HFA (Hydraulic Fluid,
Aircraft).
7. Head Mechanism
• Incorporates transfer linkage from the integrator,
closing solenoid & time-delay assemblies to the
moving contact rod.
THE KYLE TYPE DV RECLOSER
Hydraulic Control Setting
Setting the fast & delayed operations & the number of
operations to lockout requires partial untanking of the
recloser
1. Number of
operations to
lockout
• the lockout
lever is
indexed to 1 of
3 holes in its
assembly,
corresponding
to the number
of desired Hydraulic Integrator & Time-
operation
Delay Linkage
THE KYLE TYPE DV RECLOSER
Hydraulic Control Setting
2. Number of fast operations
• Established by indexing the sequence selector cam
• The cam is rotated until the desired number of fast
operations appears opposite an arrow above the
cam
• An indent holds the cam in the selected position.
Hydraulic
Integrator &
Time-Delay
Linkage
THE KYLE TYPE DV RECLOSER
Hydraulic Control Setting
3. Number of delayed operations
• Determined by the number of fast operations
• For example, if 3 operations to LO have been
selected & the cam has been adjusted for 1 fast
operation, the sequence will be 1 fast & 2 delayed
operations.
Hydraulic
Integrator &
Time-Delay
Linkage
THE KYLE TYPE DV RECLOSER
Hydraulic Control Setting
4. One operation to lockout
• Done through the external non-reclosing
handle, located under the sleet hood
• Moving this handle down activates the non-
reclosing feature, which overides the internal
setting, but does not change it physically.
THE KYLE TYPE DV RECLOSER
Hydraulic Control Setting
Manual Closing
of a De-
energized Type
DV Recloser
THE KYLE TYPE
KFME
ELECTRONICALLY-
CONTROLLED
RECLOSER
Phase 3
Nominal System Voltage (kV) 2.4 - 14.4
Maximum Rated Voltage (kV) 15.5
Schematic Diagram
THE KYLE TYPE KFME RECLOSER
Operating Levers and Indicators
Non-reclosing Operations
lever counter
• All operating
parameters, like
phase- and ground-
fault minimum trip
levels, TCC selection &
sequence of recloser
Form 3A Control operation are done via
the electronic control
• The Form 3A control is
a solid-state electronic
type while the Form 4C
is a microprocessor-
based control type
Form 4C Control
THE KYLE TYPE KFME RECLOSER
Nominal System Voltage (kV) 24.9 - 34.5 24.9 - 34.5 2.4 - 14.4