Electrical Equipment Workshop (1) .PPT Version 1
Electrical Equipment Workshop (1) .PPT Version 1
Electrical Equipment Workshop (1) .PPT Version 1
ELECTRICAL
EQUIPMENT
COURSE
OUTLINE
I. STANDARD SYMBOLS FOR UNITS
Fuse (general)
Fuse Cut-Out
Battery
Capacitor
Ground or Grounding
Surge Arrester
Overload Relay
Resistor
III. SINGLE LINE DIAGRAM
SINGLE LINE DIAGRAM OR ONE LINE DIAGRAM DESCRIBED BY USING SINGLE LINES AND SIMPLIFIED SYMBOLS
THE COURSE AND COMPONENTS DEVICES OR PARTS OF AN ELECTRIC CIRCUIT. IT ILLUSTRATES THE PATH OF
ENERGY TRANSFER AND THE IDENTIFICATION OF CIRCUIT COMPONENTS WITH THEIR RATINGS.
SOURCE
NOTE:
INCOMING LINE
AM - Ammeter
51 - AC Time Overcurrent Relay
51N - Ground Fault Relay
POWER TRANSFORMER 52 - AC Circuit Breaker
Am 51 51n
52 AC CIRCUIT BREAKER
IV. SUBSTATION EQUIPMENT
1.0 POWER TRANSFORMER
1.1 SYMBOL
ANSI IEC
1.2 DEFINITION
An electrical apparatus for transferring electrical energy from one alternating
current circuit to another without a change in frequency. These are transformers
with rating above 500kVA.
1.4.1.1ANSI
1.4.1.2IEC
BASED KVA % IZ
0 - 150
151 - 300 4.00
301 - 600 5
601 - 2500 6
2500 -5000 6.5
5001 - 7500 7.50
7500 - 10,000 8.50
Above 10,000 9.50
1.5 APPLICATION
As a Unit Substation Transformer - essentially Power Transformer standard voltage
rating Throat Connected or connected by the Metal Enclosed Bus to Metal Switchgear
or Motor Control Equipments.
1.9.1 ANSI
(1)Liquid Immersed, Air Cooled (Liquid Cooled)
*OA ……………. Liquid Immersed Self Cooled
*OA/FA ……… Liquid Immersed Self Cooled/Force Air Cooled
ILLUSTRATION:
1100 KVA
Specifications of Power Transformer
*OA/FA/FA
……… Liquid-Immersed Self Cooled / Forced Air Cooled
ILLUSTRATION:
1.9.1 IEC STANDARD
(1)Kinds of Cooling Medium Symbol
- Mineral Oil or Equal Flammable O
Synthetic Insulating Liquid
- Gas G
- Water W
- Air A
(2)Kind of Circulation Symbol
- Natural N
-3
(3)Illustration
ON AN
Oil
Natural Circulation
Air
Natural
The first two (2) indicate the cooling medium that is in contact
with the winding.
The last two (2) indicates the cooling medium that is in contact
with the external cooling medium.
1.10.1 ANSI
1.11 Angular Displacement I1N1 = I2N2
E1 = aE2
Definition:
The Angular Displacement of a three phase transformer is the time angle
expressed in degree between the line to neutral voltage of the reference
identified High Voltage terminal (H1) and the line to the neutral voltage
of the corresponding identified Low Voltage terminal (Y1).
1.11.1 ANSI Standard
(1)0° Angular displacement group.
(2)30° Angular displacement group.
Delta - Wye
Delta - delta
Wye-Delta
Wye - Wye
IEC TRANSFORMER VECTOR GROUP
PHASE SHIFT (DEG) CONNECTION
0 LAG Yy0 Dd0 Dz0
30° LAG Yd1 Dy1 Yz1
60° LAG Dd2 Dz2
120° LAG Dd4 Dz4
150 LAG Yd5 Dy5 Yz5
180 LAG Yy6 Dd6 Dz6
150 LAG Yd7 Dd7 Yz7
120 LAG Dd8 Dz8
60 LAG Dd10 Dz10
30 LAG Yd11 Dy11 Yz11
1.13.1 ANSI
DISTRIBUTION LEVEL
Design Assumption:
P.F. of Power Transformer …………….. 0.8
Primary Line …………………………………… 69000 volts
6000
kVAT = = 7500 kVA
0.8
Capacity ………………………………………….. 7500 kVA
High Voltage Rating ……………………….. 69 kV Delta
Secondary Voltage Rating ……………… 4.16Y / 24kV
Grounded Wye
Vector Group ………………………………….. 30° Angular Displacement
Impedance Voltage ……………………….. 8.0%
Insulation Withstand Rating
High Voltage BIL ……………. 350 kV
Secondary Voltage BIL ….. 75 kV
Frequency …………….………………………… 60 Hz
Short Circuit Apparent Power ……….. 9800 MVA
1.15 MERALCO STANDARD
Transformer Bank
The preferred transformer connection is DELTA Primary, WYE Secondary, the WYE
grounded DELTA connection is not allowed. The following shall be the minimum
Basic Impulse Level (BIL) of Transformer.
The transformer should be provided with at least five (5) voltage taps at the high
voltage windings.
2.0 CIRCUIT BREAKERS
Are mechanical switching devices designed to open and close a circuit under
normal
conditions and to open the circuit automatically on a pre-determined current
overload
without injury to itself when properly applied with its
rating.
4) Hydraulic
- the breaker is closed by energy pre-stored in a compressed and
completely confined gas and transmitted through the medium
of a liquid usually oil.
A) Illustration:
Consider the 38 kV oil blasts circuit breaker as shown in the tabulation,
Max. kV 38
Min. kV 38
= 23 kV
1.65
Minimum Symmetrical
Interrupting Rating = 22 A
Maximum Symmetrical
Interrupting Rating = 1.65 x 22 (Table 2.4)
= 36 kA
B) Application:
Applying at 34.5 kV
Minimum Symmetrical
Interrupting Rating = 38 x 22 = 24 kA
34.5
Maximum Symmetrical
Interrupting Rating = 36 kA
3 Short Circuit Rating
8 1.0
5 1.1 MCCB M.F. =
3 1.3 1.5
2 1.4
HIGH VOLTAGE SWITCHGEAR COMPONENTS AND FUNCTION
Function:
To protect the system against line instantaneous and time overcurrent and time
ground overcurrent.
Principle of Operation:
The main contacts are housed within a vacuum in an insulating cylinder of glass and
ceramic having metal end plates supporting the contacts.
Function:
1. Used to protect step down transformer loads (34.5kV/4.16kV) against overcurrent
due to overload or short circuit.
2. Used to disconnect or isolate step down transformer load (34.5kV/4.16kV) from
high voltage source for maintenance purposes.
Function:
Is the line switch used to disconnect or isolate the high voltage from HV switching
station.
2.7.4 Lightning Arrester (LA)
Function:
Protects the switchgear against earth faults such as lightning and temporary over
voltage
Principle of Operation:
Under the influence of a surge voltage, an arrester momentarily connects the live
conductor to earth. The charge resulting from the voltage is thus discharged
harmlessly.
Function:
Step down the high voltage source (34.5kV/110V) for metering purposes and sensor
of over-under voltage relay (25/59). They are provided with high voltage current
limiting fuse on the primary side for protection. It also provides control source to
the entire circuit.
2.7.7 Current Transformer (CT)
Function:
Steps down the high current (500:5A) for metering purposes and sensor of over
current relays (50/51/51N).
2.7.8 Under Voltage / Over Voltage Relay (27/59)
Function:
voltage phase loss (single phasing), phase reversal phase unbalance. Any of the
said abnormal power conditions will able the VCB (52M) to trip.
Function:
1. Used to monitor the system for overload and short circuit conditions that will
cause the VCB (52M) to trip.
2. Reduces the fault clearing time for high fault currents (instantaneous)
3. Used for accurate measurement of current and timing (time overcurrent)
Function:
It is a time overcurrent relay used to protect the system from ground fault.
RATED VOLTAGE AND INSULATION LEVELS FOR MEDIUM VOLTAGE
METAL-ENCLOSED SWITCHGEAR ASSEMBLIES
VOLTAGE (rms kV) INSULATION (rms kV)
SWITCHGEAR ASSEMBLY Maximum 60Hz, 1 min Basic Impulse
Nominated Rated Withstand Level (BIL)
Rated
4.16 4.76 19 60
7.20 8.25 36 95
13.8 15.0 36 95
34.5 38.0 80 150
Metal-Enclosed 4.16 4.76 19 60
Interrupter 7.20 8.25 26 75
13.8 15.0 36 95
14.4 15.5 50 110
23.0 25.8 60 125
34.5 38.0 80 150
Station-Type 14.4 15.5 50 110
Cubicle 34.5 38.0 80 150
69.0 72.5 160 250
2.8 MERALCO STANDARD SPECIFICATION
The power circuit or equivalent (e.g. vacuum fault interrupter with a gang operated load break switch
is a padmounted switchgear) shall be three pole with the following minimum specifications;
The circuit breaker shall be equipped with phase and ground overcurrent relays, the setting of which
shall be done by MERALCO.
The circuit breaker shall be so set as a non-reclosing device. The circuit breaker be provided with a
complete control mechanism that would enable it to trip and close even when there is no power at
the company's distribution system.
High Voltage Air Switches
13.8 kV
34.5 kV
69.0 kV
14.4 kV
38.0 kV
72.0 kV
60 Hz
50 Hz
Illustration:
A W PF WH
CT Ratings of the Multi-Ratio Type
Current Ratings (A) Secondary Taps Current Rating (A) Secondary Taps
600 : 5 3000 : 5
50 : 5 X2 - X 3 300 : 5 X2 - X3
100 : 5 X1 - X2 500 : 5 X1 - X2
150 : 5 X1 - X3 800 : 5 X1 - X3
200 : 5 X4 - X5 1000 : 5 X4 - X5
250 : 5 X3 - X4 1200 : 5 X3 - X4
300 : 5 X2 - X4 1500 : 5 X2 - X4
400 : 5 X1 - X4 2000 : 5 X1 - X4
450 : 5 X3 - X5 2200 : 5 X3 - X5
500 : 5 X2 - X5 2500 : 5 X2 - X5
600 : 5 X1 - X5 3000 : 5 X1 - X5
1200 : 5 2000 : 5
100 : 5 X2 - X3 300 : 5 X3 - X4
200 : 5 X1 - X2 400 : 5 X1 - X2
300 : 5 X1 - X3 500 : 5 X1 - X2
400 : 5 X4 - X5 800 : 5 X2 - X3
500 : 5 X3 - X4 1200 : 5 X1 - X3
600 : 5 X2 - X4 1500 : 5 X1 - X4
900 : 5 X3 - X5 1500 : 5 X2 - X5
4 Standard
1200 :5 Current Rating
X1 - X5 Secondary 2000 : 5 X1 - X5
=5A
Current Transformer Ratio
Rated Primary Amperes
=
5 Amperes
4 Types of CT Construction
4.2.2 Through or Bar Type - this type has the primary and secondary
windings completely insulated and permanently assembled iron
core. The primary windings usually consists of a bar type conductor
passing through the core window.
X1
X2
X3
X4
4 Connections
There are three ways that the current transformers are usually
connected on three phase circuits namely:
Ip
Is =
CTR
4.3.2 Delta Connection
The delta connection is used for power transformer differential
relay schemes. The summary of the associated CT connections
for transformer differential relaying is given as follows:
V W FM WH
13.8 kV
13800 / 120V
6.1 Classification
a) Station Type (transmission)
b) Intermediate Type Arrester
c) Distribution Type (distribution, pole type)
Lightning Strike
- direct strike
- induce strike (via travelling wave)
6.5 Protective Margin
% Protective Margin = Insulation
6.6 Illustration:
The insulation withstand of a 34.5 kV power transformer are:
ARRESTER A ARRESTER B
3)Delta System
Minimum Arrester Rating …………….……….… L-L voltage
1 10 21 3 21 48
3 12 25
6 24 60
6 15 27
9 18 30 9 30 72
12 36 90
Station Type Arrester 15 39 96
3 48 192 468
6 60 240 492
9 72 258 540
12 90 276 576
15 96 294 612
21 108 312 648
24 120 372 684
30 144 376 720
36 168 420
39 180 444
PROTECTIVE RELAYS
- are applied to detect defective lines apparatus or other dangerous or into lerable
operating conditions. They can initiate or permit switching or provide alarms. The
instrument transformer as the sensor relays as initiator and CB for isolation.
7.1.1 Electromagnetic
SOLENOID COIL
FIXED
CONTACT
ARMATURE
MOVING
CONTACT
FIXED
CONTACT
MOVING
CONTACT
ELECTROMAGNET
ARMATURE
HINGED POINT
a)Overcurrent Relays
1. Time overcurrent relays (for motor application, overload relay)
(51) device function number
1.5 -
12A 1.5, 2, 2.5, 3, 4, 5, 6, 7, 8, 10, 12
Unit Range
0.5 - 4
2 - 16
10 - 8°
20 - 16°
d)Illustration INSTANTANEOUS OVERCURRENT RELAY
50
No. 4/0 AWG
[Copper Conductor
TIME OVERCURRENT RELAY Ampacity = 480A]
UNIT RANGE
51
2 - 16A
480
Relay Current = = 4A
600/5 (CTR)
7 Determination of Current Tap Setting
min. Pu trooping current
Current Tap Setting =
CT Ratio
7.2.1 For wye connected CT's
Ip
* Ip
TAP CURRENT =
CT (Ratio)
(* Relay Current)
Ip TAP CURRENT =
* 3I
p
CT (Ratio)
(* Relay Current)
HV FUSES
These are fuses whose classifications includes the medium voltage range and rated
from 2.3 to 161 kV.
8 Types
8.1.1 Distribution Fuse Cut-out
(cross mounted, pole mounted application)
8.1.2 Power Fuse
(applicable to station and substation structure)
1 7 30 100 300
1 10 40 125 400
2 15 50 150
3 20 65 200
5 25 80 250
10 200
25 300
## 400
Rated Nominal and Maximum Voltages
2.4 2.75
4.8 5.5
7.2 8.25
13.8 15.0
14.4 15.5
23.0 25.0
34.8 38.0
46.0 48.3
69.0 72.5
92.0
115.0 121.0
138.0 145.0
161.0 169.0
QUARTZ SAND
FINE WIRES
2.4 2.75 9
4.8 6.5 17
7.2 8.25 25
13.8 15.0 45
14.4 15.5 45
23.0 25.8 75
34.5 38.0 109
b) Metal Clad
Switchgear
4.16 4.76 19 60
7.2 8.25 36 95
13.8 15.0 36 95
34.5 38.0 80 150
Power Switchgear are principally used to terminate the incoming line service and
to protect and control centers, panelboards and others.
9.1 Classifications
9.1.1 Open Switchgear - no enclosure as part of the supporting structure.
d.Function of Components
d.1Interrupter Switches - combined the function of disconnect switch
and a circuit interrupter for interrupting at rated voltage current not
exceeding its continous current rating.
d.2Power Fuses - provide the necessary overcurrent protection.
d.3Buses - should be properly braced to withstand the electromagnetic
forces generated by the flow of a circuit current.
9.2.2 Metal-clad HV Power Circuit Breaker Switchgear
1.Major Components
a.Power Circuit Breaker
b.Buses
c.Voltage and Current Transformer
d.Metering
e.Protective Devices
2.Voltage Rating Range
a.4.16 kV
b.13.8 kV
c.23 kV
d.34.5 kV
3.Continous Current Ratings
a.1200 A
b.2000 A
c.3000 A