Inspection of Electric Equipment
Inspection of Electric Equipment
Inspection of Electric Equipment
-K P Kalyan Reddy
Visakh New LPG Terminal
Scope
• For the electrical system and equipment, a value that ensures the
operation of the protective device in the electrical circuit but not in
excess of 4 ohms. However, for generating stations and large sub-
stations this value shall not be more than 1 ohm.
• For lightning protection, the value of 4 ohms as earth resistance shall be
desirable, but in no case it shall be more than 10 ohms.
• 7 Ohms for storage tanks
• 1 Ohm for main earth grid, and bonding connections between joints in
pipelines & associated facilities.
• 2 Ohms for each electrode to the general mass of the earth
Earth Continuity Test
• Building and Structures: The ohmic resistance of lightning protective system complete with
air terminations but excluding earth electrode connections should not exceed 1 ohm.
• The continuity of lightning conductors and bonding connections of structures shall be tested
to ensure that there are no open circuits. Also, checks shall be made to ensure that the
clearances from other structures are maintained to prevent flashover to the structure during
lightning.
• b) Lightning arrestor: On Line Measurement of Third Harmonic Resistive Leakage Current.
The total current (IT) through the Surge Arrester having Capacitive component (IC) and
Resistive Current (IR) flows through the Leakage Current monitor.
• The IR component has 3rd, 5th and other harmonics present in it.
• When degradation of the metal oxide discs occur, the variation of 3rd harmonic Resistive
currents is more pronounced than other harmonics currents, total current ( IT) and total
Capacitive current ( IC).
Lightening Protection Test Method.
• A clamp type CT probe is connected to the ground wire which allows the leakage current to be
detected.
• The probe output passes through a shielded cable to the detector unit. A band pass filter is
built into the initial stage to pass the 3rd harmonic and to cut off the 5th & higher harmonics.
• After the 3rd harmonic is selected, it is amplified and then displayed. A compensating
antenna is also provided, output of which is fed to the test kit to compensate for the
harmonics present in the system voltage.
• The harmonics present in the EHV system are compensated and filter circuits are provided for
bypassing undesired currents and only 3rd harmonic resistive current is measured. The
following parameters are measured: •
• True RMS value of total current, flowing through ground circuit.
• • Peak value of total current • True RMS value of third harmonic leakage current. • Ambient
Temperature.
Interpretation of Results.
• Proper care shall be taken for taking oil samples for testing. It
should be ensured that the sample bottle is clean and dry. The
bottle shall be properly rinsed with the same oil which has to be
tested, before filling up the sample.
• The Oil Testing shall be carried out as per IS 1866. The various
tests and the recommended limits for the characteristics of Oil
based on IS 1866 are as follow
Transformer Oil Testing
Transformer Oil Testing
Dissolved Gas Analysis
• This test is used to determine the amount of specific gases generated in Transformer oil during
service.
• The amount of gases and certain combinations of those is the first indication of a possible
malfunction that may eventually lead to failure if not corrected.
• Some of the mechanisms which lead to generation of gases due to the chemical decomposition of
oil are arcing, partial discharges, low-energy sparking, severe overloading, overheating of the
insulation etc. Certain empirical values are provided to give an indication of the impending failure.
• For DGA testing the sample should be obtained using a clean, moisture free, gas tight container.
Care should be taken to purge the container of all free gas at the time of taking the sample.
• The first step in evaluating DGA results is to consider the concentration levels (in ppm) of each key
gas. It is recommended that values for each of the key gases be trended over time so that the
rate-of-change of the various gas concentrations can be evaluated. Basically, any sharp increase in
key gas concentration is indicative of a potential problem within the transformer
Dissolved Gas Analysis
Thermography