Three-Phase Unbalanced System With PV Systems
Three-Phase Unbalanced System With PV Systems
with PV systems
Topology
• LINE model
I1 R + jX I2
jB1 jB2
V1 V2
Yprim
This is one phase line model ,which easily to expand three phase
line model, Simply let R, X, B, G, C, etc. represent 3x3 matrix
Notation stays the same, I1, I2, V1, V2 etc become 3x1 vectors
Model
General Concept
Compensation
Yprim Current
Compensation Phase 1
Yprim Current
Compensation Phase 2
3 Yprim Current
Compensation Phase 3
Yprim Current
Load have two connect way, this is Y connected way. According to the previous PC
element Equivalent model, the Y connected load can model like this .
Model
Load - 3-phase Delta connected
Compensation Phase 1
Yprim Current
1
Compensation Phase 2
Yprim Current
Compensation Phase 3
Yprim Current
3 Conductors/Terminal
According to the previous PC element Equivalent model,
the 3-phase Delta load can model like this .
Thansformer Model
the active power, P, is a function of the Irradiance, temperature (T), and rated power at
the mpp, Pmpp at a selected temperature and an irradiance of 1.0 kW/m2
Model
PC Elements
Comp. Currents
I1
I2
Y
= Node
Iinj V
Voltages
Im
Iteration Loop
…until converged
Capacitor Data:
Line Segment Data:
Node Ph-A Ph-B Ph-C
kVAr kVAr kVAr
Node A Node B Length(ft.) Config. 675 200 200 200
632 645 500 603 611 100
632 633 500 602 Total 200 200 300
633 634 0 XFM-1
645 646 300 603
650
684
632
652
2000
800
601
607
Regulator Data:
632 671 2000 601
671 684 300 604 Regulator ID: 1
671 680 1000 601 Line Segment: 650 - 632
671 692 0 Switch Location: 50
684 611 300 605 Phases: A - B -C
692 675 500 606 Connection: 3-Ph,LG
Monitoring Phase: A-B-C
Bandwidth: 2.0 volts
PT Ratio: 20