CT&PT
CT&PT
CT&PT
(KnIs -Ip)
Ratio error = x 100
Ip
Where,
Kn = Rated transformation ratio
Ip = Primary current
Is= Actual secondary current when Ip is
flowing in the Primary.
PHASE DISPLACEMENT:
APPLICATION :
ROUTINE TEST
SPECIAL TEST
IR10/IR1
= less than 1.0 - dangerous
= 1.0 to 1.1 - suspicious(poor)
= 1.1 to 1.25 - questionable
= 1.25 to 2.0- good
= above 2.0 - very good
The prescribed limits of dielectric strength are as follows:
Generation
Distribution
Transmission
Substations
Bus Bar
Line switches
PT
CT
Circuit breakers
CVT
Power
G Generator
Line Bay Power Transformers
AIS Substation
(Line Bay) (Line switches)
(Circuit breakers)
CT
Protection system employed in
HV/EHV sub stations with the type of
relays
PROTECTION SYSTEM
EMPLOYED
TYPE OF RELAYS
USED TODAY
TYPE OF RELAYS USED
EARLIER
Line switches
PT
CT
Circuit breakers
CVT
Power
G Generator
Line Bay Power Transformers
Instrument
Transformer
Current sensor
Sensing
function
I2
I1
Instrument
Transformer
Current sensor
Multiple secondary
Sensing
I2
function
I2
I1
Definition of
an
Ip Instrument
Primary Magnetic core
Transformer
U p
Ip
TC : K=
Windings Is
K:
Transformation
Up
ratio TP : K=
Us
Us
Secondary Is
Definition of an
Voltage Transformer :
Instrument Transformer
Primary
U1
U1 n1
K
n1 U2 n2
K : Transformation
ratio
n2
U2
Secondary
Definition of an
Instrument Transformer
Current Transformer :
I1 Primary
n1 .I 1 n 2 .I 2
n1 I1 n 2
K
K : Transformation
I 2 n1
ratio
Ampere-Turns
Conservation
n2 Law
Secondary I2
Instrument
Transformer
Error
Primary
Up
Voltage
VoltageTransformer
Transformer::
Up (theoretically = k.US)
K
: Phase error
K.Us
Us :Rat
io e
rror
Secondary
Up
k
Us
Instrument Transformer
Error
Primary
Ip
Current
Currenttransformer
transformer::
Ip
K
: Phase error
K.Is
:Rat
io e
rror
Secondary Is
Ip
TC : K=
Is
Remi
nder
EMF Equation
Electrodynamical Forces
2.I 1 .I 2 .L 7
I1 I2 L
F .10 [N, m, A] F F
D
Magnetizatio
n curve Double logarithmic graph
1 Tesla = 104 Gauss
105
Induction [Gauss]
18.000 Gauss
104
Compared to reference curves
103
102
10-3 10-2 10-1 1
Magnetic field [AT/cm]
Remi
nder
Hysteresis cycle
Induction [B]
Br
Hc Magnetic
field [H]
Br : Remanent Induction
Hc : Coercive field
Remi
nder
Equivalent scheme of a coil with sinusoidal current
R cuivre
A
U
Iw I
I0 I0
L0 Iw
RH
U RCF
I
i0 i iw
RMK
Existing
range
•Instrument Transformer
•Current Transformers
•Hair_Pin design
•Eye-Bolt design
•Top-Core design
•Lightning Arresters
Existing
range
3 CT design
Design CT Type Voltage Range
Eye-Bolt IT 245 kV
Top-Core KT 72 to 145 kV
Eye Bolt
Design IT 72.5-245
1. Dome
2. Collar
3. Top casting
4. Insulator
5. Active part
6. Bottom casting
7. Tank
8. Support frame
9. Secondary cores
10. Pressure relief valve
11. Primary terminal
IT
IT range
range
Eye Bolt Design IT
IT range
range
Active part
manufacturing
Primary conductor (1,2 or 4 turns)
Paper insulation
Secondary cores
Eye Bolt Design IT
IT range
range
Active part
manufacturing
Design IT
IT range
range
Vacuum
treatment
High vacuum (0.01 mm Hg)
High Temperature (105 °C)
Oven
Target
Target::
Remove
Removeallallthe
thewater
watertrapped
trapped
in
inthe
thepaper
paper(and
(andin
inother
other Active
materials)
materials)during
duringinsulation
insulation part
process
process
Duration
Duration::
Up
Upto
to33weeks
weeks
Eye Bolt
Design Nitrogen filling
IT
IT rangeAssembly
range
Upper Tank
Oil filling
Porcelain insulator
Active part
Bottom Tank
Assembly
Summary of Technical data :
Rated voltage : 123 to 245 kV
Technolgy : Eye-Bolt
Expansion device : Nitrogen
Primary reconnection : 1-2
Rated primary current : 1200 Amp (1440 max)
Short circuit current : 40 kA 1”
Tuyau
range ITT
ITT range
range
Hair-Pin
design
Summary of Technical data :
Rated voltage : 245 to 420 kV
Technolgy : Hair-Pin
Expansion device : Nitrogen
Primary reconnection : 1-2
Rated primary current : 3000 Amp (3000 max)
Short circuit current : - 40 kA 1” (245 kV)
- 60 kA 1” (420 kV)
Total weight (kg)
kV 245 420
kg 1400 2300
range KT
KT range
range
Top Core
design KT 36
……..
KT 245
1. Dome
2. Oil level indicator
3. Primary terminals
5. Upper tank
6. Upper flange
7. Insulator
8. Active part
9. Base
10.Multibushing
11.Pressure relief valve
range KT
KT range
range
Top Core
design
Summary of Technical data :
Rated voltage : 72.5 to 245 kV
Technolgy : Top-core
Expansion device : Nitrogen
Primary reconnection : 1-2
Rated primary current : 2000 Amp (2400 max)
Short circuit current : - 40 kA 1” (145 kV)
- 50 kA 1” (245 kV)
Total weight (kg)
kV 72.5 145 245
kg 250 500 850
Current
CEI
Transformers
CEI600
60044-1
44-1
Protection
Accuracy classes (Protection)
accuracy classes
Maximum current error in % of I P
Burden :SN
Parameters
2. Composite error
Factors for
Protection
1. Accuracy Limiting Factor
2. Composite error
Protection
Under steady-state accuracy
conditions, classes
the r.m.s. value of the difference
between:
a) the instantaneous values of the primary current, and
b) the instantaneous values of the actual secondary current multiplied
by the rated transformation ratio
T
c
100 1
K n I s i p 2 .dt
Ip T 0
Parameters
3. Resistance of CT (Rct)
Current
Transformers
Induction
B [T]
Saturation 18500 gauss
Protection CT
curve
8000 gauss
Metering CT
Primary current
Ip/In
10 20 30 40
Factors for
Protection
1. Knee Point Voltage(Vk):
30
t
T
Simulates a lightning stroke
T1 overvoltage travelling along a HV
T2 transmission line
Intrument
Transformers
Switching impulse test (250/2500 s)
Impulse
100 %
U tests TTcrcr==250
90 250s
s
TT22==2500
2500s
s
Tc
50
t
Tcr
T2
Simulates overvoltages resulting
from line switches operations
Intrument
Transformers
Lightning impulse (chopped wave)
Impulse
100 %
U tests Imulse
Imulsewave
chopped
waveisis
90 choppedbybyusing
using
a sparking gaps after
sparking gaps after
22àà55s
s
30
t
Tc
Simulates a flash over on an
insulator resulting from a
lightning stroke
Intrument
Transformers
Lightning impulse - chopped on the front
Impulse
100 %
U tests
90 1,2s
TTcc << 1,2 s
30
t
Tc
Simulates a direct lightning on the
transformer. The quick voltage increase
provoke a floshover.
Instrument
Transformers
Copped impulse wave [EDF 600 impulses]
Impulse
T test
c
h
t
TTcc 0,5
0,5s
s
hh 0,3H
0,3H
H
U EGAT THA
Qualification
Current
Transformer
Routine tests
CEI
CEI600
CEI
60044-1
60-1
CEI 60-1
44-1
Routine
The following tests apply to each individual transformers:
a) verification of terminal markings
tests withstand test on primary winding
b) power-frequency
c) partial discharge measurement
d) power-frequency withstand test on secondary windings
e) power-frequency withstand tests, between sections
f) inter-turn overvoltage test
g) determination of errors
The order of the tests is not standardized, but determination of errors
shall be performed after the other tests.
Typical ( Maximum) lead
lengths based on voltage level
of substations
Voltage Level in kV Lead Length in Meters
400 1000
220 800
132 500
Typical Burdens - Analog and
Digital Meters
( Current Transformer Circuit )
METERS/LOADS TYPICAL VA TYPICAL VA
BURDEN BURDEN
( ANALOG TYPE ) ( DIGITAL TYPE )
AMMETER 1 0.5
PF METER 1 0.1
TRANSDUCER 1
TOTAL 5 1.8
Typical Burden Calculation
400kV Current Transformer
Metering core
The max burdens of all the meters/load = 5 VA (approx) considering analog
meters and max lead length for 400kV switchyard = 1000 meters
The control cable size is 2.5 sq.mm. Always 2 runs of cable are used. Resistance of
2.5sq.mm cable is 8.5 ohms per kilometre for 2 runs of cable it is 4.25 Ohms
= 2 *1*1* 4.25
= 8.5 VA
the optimum total burden = 5 + 8.5 = 13.5VA
The control cable size is 2.5 sq.mm. Always 2 runs of cable are used. Resistance of
2.5sq.mm cable is 8.5 ohms per kilometre for 2 runs of cable it is 4.25 Ohms
NOTE: FOR 400KV CT's ONLY CLASS PS CORES ARE USED. HENCE THIS CALCULATION IS OMITTED FOR 400KV
CT’s.
RMK
Existing
range
•Instrument Transformer
•Current Transformers
•Hair_Pin design
•Eye-Bolt design
•Top-Core design
•Condensor Bushings
Capacitor Voltage Transformer
"CCV" Range
Accuracy Protection
Revenue Metering Measurements
Automation
Diagnosis
Sequence of Event Recorder
Disturbance Recording
CVT Communication to the station level
Capacitor Voltage
Transformer
Definitions
Element
ElementPack
Pack
(or
(orpack)
pack)
Pile of elements : ± 10 to 25 kV
Capacitor Voltage
Transformer
Definitions HV Power line
Capacitor
CapacitorUnit
Unit
(or
(orunit)
unit)
Assembly of elements in an
insulating container: ± 245 kV.
Can be connected to a HV line
Ground
Capacitor Voltage
Transformer
Definitions HV Power line
Capacitor
CapacitorSTACK
STACK
(or
(orstack)
stack)
Ground
Capacitor Voltage
Transformer
Definitions HV Power line
Capacitor
CapacitorVoltage
VoltageDivider
Divider
((or
orCVT
CVT))
Connecting an MV inductive
voltage transformer to a tap.
Ground
Capacitor Voltage
Transformer
BasicsP Intermediate
1
Voltage :
10 to 20 kV/3
C1
S1
C2
P2 S2
Transformer
Magnetic
Transformer
C L R Lfs
Equivalent
EquivalentDiagram
Rs
Diagram
e a a
Vp . C1
U’P = Lμ Rw Us Zc
k . (C1+C2)
Inductive VT
RMK
RMK -- CVT
CVT
CCV 72.5 to 765 kV
Oil expansion device
Capacitor elements
Capacitor column
Insulating oil
Insulator flange
MV Transformer
Damping circuit
Capacitor Voltage Transformer
Diagram
HV Terminal
C1
C2
L P
GS MV
D S S S S
MCB
GS HF DC HF N 11 11 11 11
12 12 12 12
14 14 14 14
2n
4n
3n
2a
4a
1n
3a
1a
GROUND
PLC System
Capacitor Voltage Transformer
Line trap
PLC system HV line
C1
During HF
communication, earthing
of signals or entry into P2
C2
magnetic part must be
avoided. Inductive
Part
Good tuning
High intermediate voltage
Phase error :
VA 1
(en minutos) = 3440. . R.sin L . - . cos
2
V a C .
s e
Capacitor Voltage Transformer
Damping
Primary
Primary Short
ShortCircuit &Circuit
Circuit& Transient
TransientResponse
Response
Ce Rs
La
Rp
Rw La m
Vi Lµ
Vs
Zc
Rpa m
Ra m
Capacitor Voltage Transformer
Damping
Primary
Primary Short
ShortCircuit &Circuit
Circuit& Transient
TransientResponse
Response
Vs Secondary voltage
t
Capacitor Voltage Transformer
Damping
Primary
Primary Short
ShortCircuit &Circuit
Circuit& Transient
TransientResponse
Response
Vi Secondary error Primary voltage
IEC today :
max 10% after 20ms
10% t
Vs Secondary voltage t
R R-L-C R-L-R
••High
Highburden
burden ••Efficient
Efficient ••Efficient
Efficient
••jeopardize
jeopardize ••Easy
Easytotodesign
design ••Sophisticated
Sophisticateddesign
design
accuracy
accuracy ••Expensive
Expensive ••Economical
Economical
Te nsion primaire
Primary Voltage
Damping &Circuit
-50
Primary
Primary Short
ShortCircuit
-100
-150
-200
Circuit& Transient
TransientResponse
Response
300
400
350
450
500
550
600
TeSecondary
nsion se condaire
Voltage
200
100
R-L-R
R-L-R 0
-100
-200
300
400
350
450
500
550
600
% error
% Erreur at ire
se conda secondary
(tra nsitoire )
7
-1
-2
300
350
400
450
500
550
600
Capacitor Voltage Transformer
Ferroresonance
Ferroresonance according IEC 186
C2 SGC
Ith
N2 Z
N1
L R1 Ferroresonance
D R2 Damping device
on inductive PT
L'1
L1
"Transformer type" Ferroresonance
compensating RL SGL Damping device
inductance L2
on inductance
L'2
Capacitor Voltage Transformer
Ferroresonance Primary voltage
Fuse
operation
Short-circuit
Secondary
current
Without
damping
device
Secondary
voltage
250
200
Ferroresonance
-100
-150 Primary
-200
-250 voltage
5 50
6 00
6 50
7 00
75 0
350
400
450
500
100
80
60
40
20
0
-20
-40
-60 Secondary
-80
-100 5 50
current
6 00
6 50
7 00
75 0
350
400
450
500
-200
-400
Secondary
-600
voltage
5 50
6 00
6 50
7 00
75 0
350
400
450
500
Voltage Transformers
IEC
Metering
IEC600
60044-2
44-2
Accuracy Classes
Accuracy classes - Multiple windings
Same conditions except, accuracy to be garanteed with
- Other windings loaded between 0% to 100%
f -f
100% VA
T NP
f) Determination of errors.
Typical Burdens - Analog and
Digital Meters
(Voltage Transformer Circuit )
METERS/LOADS TYPICAL VA TYPICAL VA BURDEN
BURDEN ( DIGITAL TYPE )
( ANALOG TYPE )
VOLTMETER 5 1
WATTMETER& 4 0.1
VARMETER
ENERGY METER 1 0.1
PF METER 4
ELECTRONIC 6
SYNCHROSCOPE
FREQUENCY 7 1
METER
TRANSDUCER 1
TOTAL 28 12.2
MAXIMUM BURDEN IMPOSED ON THE
CAPACITOR VOLTAGE TRANSFORMER
TheMETERING
max burdens of all WINDING INVAA(approx)
the meters/load = 28 400KV when analog meters
areSUBSTATION
considered and max lead length for 400kv switchyard = 1000 meters
The control cable size is 2.5 sq.mm. Always 2 runs of cable are used.
Resistance of 2.5sq.mm cable is 8.5 ohms per kilometre for 2 runs of cable it is
4.25 Ohms
MEASURING ELEMENT
COMPARING ELEMENT