Chater-2 Transformerrs
Chater-2 Transformerrs
Chater-2 Transformerrs
Transformers
Presentation Outline
Construction features
Principles of Operation
Ideal and Practical Models
Equivalent Circuit
Transformer Tests
Voltage Regulation and
Efficiency
Three Phase Transformers
and Group Connection
Parallel Operation of
Transformers
per unit analysis
1. Construction of Transformers
A transformer is an electrical device which is used to transform
either current or voltage level.
The basic components of a transformer are
Primary coil – the coil connected
to the incoming (supply) voltage.
Secondary coil – the coil connected
to a load.
Laminated iron core – creates magnetic coupling between
the two coils
There is no electrical connection between the two coils, which
are constructed using insulated wire.
Step-up transformer increases the output voltage - there are
more turns on the secondary than on the primary.
Step-down transformer decreases the output voltage - there are
fewer turns on the secondary than on the primary.
Construction ...
Depending on how the windings are placed,
core types
There are two types of transformers
Core type transformer
shell types
N1 v1 I 2
N 2 v2 I1
3. Transformers with no-load
therefore
5. Equivalent circuit of transformers
To study the characterstics and performance of transformers, it is
necessary to draw equivalent circuit containing the parameters of
the transformer.
R1, R2 - resistances of the
primary and secondary coils
Xl1, Xl2 - reactances of the
primary and secondary coils
RC, Xm magnetizing resistance and reactance of the core
material respectively
,
I2 is component of the primary current which would exactly
counteract the mmf due to the secondary current.
Equivalent circuit of transformers …
The load voltage and current referred to the primary side are
The power measured during open circuit test represents the core
loss due to the impedance of the core.
The power measured during short circuit test represents the
copper loss (resistive loss) due to the impedance of the windings
6.1 No load (open circuit) test
It is used to determine the shunt parameters of the equivalent
circuit, Xm and Rc
Usually performed on the low voltage side.
The test is performed at rated voltage and frequency
under no load
6.2 short circuit test
It is used to determine the series parameters of the equivalent
circuit (Xeq) and Rsc (Req)
Usually performed on the high voltage side.
This test is performed at reduced voltage (5 – 10 % of the
rated voltage) and at rated frequency with the output of the low
voltage winding short circuited such that rated current flows on
the high voltage side.
6.3 Polarity test
Terminals of different windings are of same polarity if currents
entering (or leaving) them produce flux in the same direction in
the core.
Terminals labeled with a dot have similar polarity
To check polarity
Example 3
With the instruments located on the high-voltage side and the
low-voltage side short-circuited, the short-circuit test readings
for the 50-kVA 2400:240-V transformer of Example 1 are 48
V, 20.8 A, and 617 W.
An open-circuit test with the low-voltage side energized gives
instrument readings on that side of 240 V, 5.41 A, and 186 W.
Draw the equivalent circuit of the transformer and label the
Parameters
(a) referred to the high voltage side
(b) referred to the low voltage side
Example 4
V2 I 2Cos 2
*100
Losses V2 I 2Cos 2
V2 I 2Cos 2
2 2 2
*100
V1 / Rc1 I1 R1 I 2 R2 V2 I 2Cos 2
V2 I 2Cos 2
2 2
*100
V1 / Rc1 I 2 Req 2 V2 I 2Cos 2
Cos 2 = load power factor
Condition for maximum efficiency
***
Cont’d…
V2 I 2Cos 2
max *100
V2 I 2Cos 2 2 PFe
Maximum efficiency
100 pf=1
pf= 0.8
pf= 0.6
At this load current
core loss = copper loss
0
Definition:
The transformer vector group show the phase difference
between the primary and secondary sides of the transformer.
It also determines the high voltage and low voltage windings
arrangement of three phase transformers.
Winding connection designations:
•The vector for the high voltage winding is taken as the reference
vector. Displacement of the vectors of other windings from the
reference vector, with anticlockwise rotation, is represented by the
use of clock hour figure.
Cont’d…
The value of VAbase must be the same over the entire system
under analysis. Usually the rated values of the transformer are
taken as base values.
For a single-phase system,
Pbase, Qbase, VAbase = VbaseIbase
Rbase, Xbase, Zbase = Vbase/Ibase
The procedure for per unit analysis can be summarized as
Example
The exciting current measured on the low-voltage side of a
50-kVA, 2400:240-V transformer is 5.41 A. Its equivalent
impedance referred to the high-voltage side is 1.42 + j 1.82
Ω. Using the transformer rating as the base, express in per
unit on the low- and high-voltage sides
(a) the exciting current and
(b) the equivalent impedance.
Problem:
A 15-kVA 120:460-V transformer has an equivalent series
impedance of 0.018 + j0.042 per unit. Calculate the
equivalent series impedance in ohms
a) referred to the low-voltage side and
b) referred to the high-voltage side.
Ans : ZLV = 0.017 + j0.040 Ω and ZHV = 0.25 + j0.60 Ω
Transformer name plate
LV side
notation
Transformer
Arching horn
Bushings
Transformer
nameplate
Thermometer
Conservator Tank
Used Silka gel
New Silka gel