Lecture 06
Lecture 06
EEE-435
Industrial Electronics
Text Book: Chapter 07 (Industrial electronics by Frank D. Petruzella
1
Advantages of SSR over EMR
• Solid-state relays have several advantages over electromechanical
types:
• The SSR is more reliable and has a longer life because it has no
moving parts.
• It is compatible with transistor and IC circuitry and does not generate
as much electromagnetic interference.
• The SSR is more resistant to shock and vibration, has a much faster
response time, and does not exhibit contact bounce.
ON-DELAY TIMER
• The on-delay timer is sometimes referred to as DOE, which stands for
delay on energize. The time delay of the contacts begins once the timer
is switched on; hence the term on-delay timing.
• Figure 7-18 shows the NEMA symbols for the on-delay timer normally
open (NO) and normally closed (NC) contacts. The operation of the
timed contacts can be summarized as follows.
• Once initiated, DOE timed contacts change state after a set time period
has passed.
• After that time has passed, all normally open timed contacts close and
all normally closed contacts open.
• Once the timed contacts change state, they will remain in this position
until the power is removed from the coil or electronic circuit.
• The circuit shown in Figure 7-19 illustrates the timing function of an on-delay
timing relay. In this example a simple dashpot timer with a time delay setting of
10 seconds can be assumed. The same operation applies to electronic timers
that perform a similar function. The operation of the circuit can be summarized
as follows.
• When the switch is closed, power is applied to the coil but the contacts are
delayed from changing position.
• With the switch still closed, after the 10-second timing period the normally open
contacts (TR1-1) close to energize load 1 and the normally closed contacts (TR1-
2) open to deenergize load 2.
• If the switch is then opened, the coil deenergizes immediately, returning both
timed contacts to their normal state, switching load 1 on and load 2 off.
OFF-Delay Timer
• The off-delay timer is sometimes referred to as DODE, which stands
for delay on deenergize. The operation of the off-delay timer is the
exact opposite of that of the on-delay timer. When power is applied
to the coil or electronic circuit, the timed contacts will change state
immediately. When power is removed, however, there is a time delay
before the timed contacts change to their normal deenergized
positions. Figure 7-20 shows the standard NEMA symbols and
illustrates the timing function of an off-delay timing relay.
• Figure 7-21 shows the wiring diagram for the automatic pumping
down of a pump using a level sensor switch and plug-in cube-type off-
delay timer.
Latching Relays
• Latching relays typically use a mechanical latch or permanent magnet
to hold the contacts in their last energized position without the need
for continued application of coil power.
• They are especially useful in applications where power must be
conserved, such as a battery-operated device, or where it is desirable
to have a relay stay in one position if power is interrupted.
Mechanical Latching Relays
• Logic is the ability to make decisions when one or more different factors must be
taken into consideration. Control logic functions describe how inputs interact
with each other to control the outputs and include AND, OR, NOT, NAND, and
NOR functions.
• In electronic circuits these functions are implemented using digital circuits
known as gates.
• The AND logic function operates like a series circuit. AND logic is used when two
or more inputs are connected in series and they all must be closed in order to
energize the output load. Figure 7-34 shows a simple application of the
• AND logic function. Most AND logic circuits use normally open input devices
connected in series. In this application both the temperature switch and the float
switch inputs must be closed to energize the solenoid output.
OR logic function
• The OR logic function operates like a parallel circuit. OR logic is used
when two or more inputs are connected in parallel and any one of the
inputs can close to energize the output load.
• Figure 7-35 shows a simple application of the OR logic function. Most
OR logic circuits use normally open input devices connected in
parallel.
• In this circuit, any one of the two pushbutton inputs can close to
energize the motor starter coil load.