FAA Aircraft Wiring Practices
FAA Aircraft Wiring Practices
FAA Aircraft Wiring Practices
Wiring Overview
Physical Properties Age
Wire Degradation
Environment Maintenance
Installation
Moisture
Maintenance
25.869
Wiring Practices
Policy memo
AC 43.13-1b
AC 25-16
AC 25-10
Wire Selection
Size wires so they:
Have sufficient mechanical strength Do not exceed allowable voltage drop levels Are protected by circuit protection devices Meet circuit current-carrying requirements
Wire Selection
Conductor stranding
Plated because bare copper develops surface oxide film -- a poor conductor
Wiring Routing
Eliminate potential for chafing against structure or other components Position to eliminate/minimize use as handhold or support Minimize exposure to damage by maintenance crews or shifting cargo Avoid battery electrolytes or other corrosive fluids
A B
A B
A B
Wiring as a Handhold
Avoid this type of routing. If not avoidable, then placard
Broken wire shall not make contact with fluid line (fail-safe concept)
Wires improperly tied, riding on hydraulic lines, contaminated with caustic fluid
Wire bundles
Head of strap shall not be located in this area or touching anything to cause chafing
Wire bundle
Stand-offs
Use stand-offs to maintain clearance between wires and structure
Exception: Where impossible to install offangle clamps to maintain wiring separation in holes, bulkheads, floors, etc.
Clamping
Support wires by suitable clamps, grommets, or other devices at intervals of not more that 24 inches Supporting devices should be of suitable size and type with wire and/or cables held securely in place without damage to wire or wire insulation
Clamps
Wire bundles should be snug in clamp (no movement)
Mount clamps with attachment hardware on top (minimizes gravitational effects) Tying NOT used as alternative to clamping
Appropriate slack
Clamp Distortion
Correct clamp position
Clamp Orientation
905
Correct
Incorrect
905
Correct
Incorrect
Exceptions
Terminations/reversing direction in bundle (supported at both ends of loop) 3 times the diameter RF cables - 6 times the diameter Thermocouple wire - 20 times the diameter
Bend radii okayGreater than 3 times diameter (secured at both ends of loop)
Unused Wires
Secured
Individually cut with strands even with insulation Pre-insulated, closed-end connector or 1-inch piece of insulating tubing folded and tied back
Unused wiring Improper termination with exposed conductor (should be properly insulated and secured to bundle)
Wire Replacement
Wires should be replaced when:
Chafed or frayed Insulation suspected of being penetrated Outer insulation is cracking Damaged by or known to have been exposed to electrolyte, oil, hydraulic fluid, etc. Evidence of overheating can be seen
Wire bears evidence of being crushed or kinked Shield on shielded wire if frayed and/or corroded Wire shows evidence of breaks, cracks, dirt, or moisture in plastic sleeving Sections of wire have splices occurring at less than 10 ft intervals
Replacement wires must have the same shielding characteristics, such as shield optical coverage and resistance per unit length Replacement wires should not be installed outside the bundle shield
Incorrect procedure
Correct procedure
Terminal Strips
Barriers to prevent adjacent studs from contacting each other Current should be carried by terminal contact surface and not by stud Studs anchored against rotation Mounted such that loose metallic objects cannot fall across terminals
These conditions can cause arcing, which may result in a fire or systems failure
Wire Marking
Necessary for: Safety of operation Safety to maintenance personnel Ease of maintenance Maintaining Separation Requirements To identify performance capability, use wire material part number and five digit/letter code identifying manufacturer
Connectors
Many types, however crimped contacts generally used Circular type Rectangular Module blocks Selected to provide max. degree of safety and reliability given electrical and environmental requirements Use environmentally sealed connectors to prevent moisture penetration Plug unused pins
Circular Connectors
Pin Arrangement
e c f a b d b a c d f e g f e n a d m h c l i j k b
a, b: 115 Vac, 400 Hz, galley power c, d: 5 Vdc, discrete weight on wheels signal e, f: 28 Vdc, backup power
Conduits
Purpose
Mechanical protection of wires and cables Grouping and routing wires Absence of abrasion at end fittings Proper clamping Adequate drain points free of obstructions Minimized damage from moving objects Proper bend radii Protect wires inside metallic conduits
Standards
Wire Separation
Regulatory requirements
Manufacturers standards
EMI concerns
Consider possible modes of failure including external events, e.g. wire bundle failure or damage
Common Cause Analysis may indicate need for separation requirements Zonal Analysis will verify requirements
If fault can damage other essential circuit wires in same bundle, may need to segregate or separate wiring, as practicable, to minimize damage
May need to separate certain critical systems components including wiring, e.g., electrical power feeders, fly-by-wire control paths
STC applicants may not be aware of separation or other wiring requirements (i.e., do not have needed design data) Wiring added or moved as part of the STC should satisfy original separation requirements and wiring standards FAA policy letter on type design data for wiring (ANM-01-04)
Splicing instructions Compatible replacement wire types Pertinent clamping and routing aspects Shielding, grounding aspects, if applicable
ICA, cont.
ATSRAC recommendations
Clean-as-you-go philosophy Wiring general visual inspections (WGVI) Non-destructive testing (NDT) equipment Preemptive repair of splices/ replacement of wire
Questions ??
Thank You