Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Power฀and฀Energy฀Series฀51 Short-circuit฀ Currents J.฀Schlabbach ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ ฀ To my wife Bettina and my children Marina and Tobias Contents List of figures xiii List of tables xxiii Foreword xxvii 1 Introduction 1.1 Objectives 1.2 Importance of short-circuit currents 1.3 Maximal and minimal short-circuit currents 1.4 Norms and standards 2 Theoretical background 2.1 General 2.2 Complex calculations, vectors and phasor diagrams 2.3 System of symmetrical components 2.3.1 Transformation matrix 2.3.2 Interpretation of the system of symmetrical components 2.3.3 Transformation of impedances 2.3.4 Measurement of impedances of the symmetrical components 2.4 Equivalent circuit diagram for short-circuits 2.5 Series and parallel connection 2.6 Definitions and terms 2.7 Ohm-system, p.u.-system and %/MVA-system 2.7.1 General 2.7.2 Correction factor using %/MVA- or p.u.-system 2.8 Examples 2.8.1 Vector diagram and system of symmetrical components 1 1 1 3 4 11 11 11 14 14 18 19 20 24 27 30 32 32 34 34 34 viii Contents 2.8.2 2.8.3 2.8.4 2.8.5 Calculation of impedances of a three-winding transformer in %/MVA Conversion of impedances (; %/MVA; p.u.) Impedances in %/MVA-system based on measurement Representation of a line in the RYB-system and in the system of symmetrical components 3 Calculation of impedance of electrical equipment 3.1 General 3.2 Equipment in a.c. systems 3.2.1 General 3.2.2 Impedance calculation 3.3 Equipment in d.c. systems 3.3.1 General 3.3.2 Impedance calculation 3.4 Examples for calculation 3.4.1 a.c. equipment 3.4.2 d.c. equipment 4 Calculation of short-circuit current in a.c. three-phase HV-systems 4.1 Types of short-circuits 4.2 Methods of calculation 4.3 Calculation of parameters of short-circuit currents 4.3.1 General 4.3.2 Calculation of short-circuit current parameters according to IEC 60909-0 4.4 Influence of motors 4.5 Minimal short-circuit currents 4.6 Examples 4.6.1 Three-phase near-to-generator short-circuit 4.6.2 Line-to-earth (single-phase) short-circuit 4.6.3 Calculation of peak short-circuit current 4.6.4 Short-circuit currents in a meshed 110-kV-system 4.6.5 Influence of impedance correction factors on short-circuit currents 4.6.6 Short-circuit currents in a.c. auxiliary supply of a power station 5 Influence of neutral earthing on single-phase short-circuit currents 5.1 General 5.2 Power system with low-impedance earthing 5.3 Power system having earthing with current limitation 5.4 Power system with isolated neutral 37 40 41 42 45 45 45 45 46 50 50 58 63 63 64 67 67 68 70 70 72 84 85 86 86 87 88 89 91 94 97 97 98 102 105 Contents 5.5 5.6 5.7 Power system with resonance earthing (Petersen-coil) 5.5.1 General 5.5.2 Calculation of displacement voltage 5.5.3 Tuning of the Petersen-coil Handling of neutrals on HV-side and LV-side of transformers Examples 5.7.1 Increase of displacement voltage for systems with resonance earthing 5.7.2 Limitation of single-phase short-circuit current by earthing through impedance 5.7.3 Design of an earthing resistor connected to an artificial neutral 5.7.4 Resonance earthing in a 20-kV-system 5.7.5 Calculation of capacitive earth-fault current and residual current 5.7.6 Voltages at neutral of a unit transformer ix 108 108 112 115 116 119 119 123 124 124 125 126 6 Calculation of short-circuit currents in low-voltage systems 6.1 General 6.2 Types of faults 6.3 Method of calculation 6.4 Calculation of short-circuit parameters 6.4.1 Impedances 6.4.2 Symmetrical short-circuit breaking current Ib 6.4.3 Steady-state short-circuit current Ik 6.5 Minimal short-circuit currents 6.6 Examples 131 131 131 132 132 132 133 134 134 135 7 Double earth-fault and short-circuit currents through earth 7.1 General 7.2 Short-circuit currents during double earth-faults 7.2.1 Impedances and initial symmetrical short-circuit current Ik 7.2.2 Power system configurations 7.2.3 Peak short-circuit current ip 7.2.4 Symmetrical short-circuit breaking current Ib and steady-state short-circuit current Ik 7.3 Short-circuit currents through earth 7.3.1 Introduction 7.3.2 Short-circuit inside a switchyard 7.3.3 Short-circuit at overhead-line tower 7.4 Examples 7.4.1 Double earth-fault in a 20-kV-system 7.4.2 Single-phase short-circuit in a 110-kV-system 139 139 139 139 140 143 143 143 143 144 145 146 146 148 x 8 9 10 Contents Factors for the calculation of short-circuit currents 8.1 General 8.2 Correction using %/MVA- or p.u.-system 8.3 Impedance correction factors 8.4 Factor κ for peak short-circuit current 8.5 Factor μ for symmetrical short-circuit breaking current 8.6 Factor λ for steady-state short-circuit current 8.7 Factor q for short-circuit breaking current of asynchronous motors 151 151 152 154 156 158 160 Calculation of short-circuit currents in d.c. auxiliary installations 9.1 General 9.2 Short-circuit currents from capacitors 9.3 Short-circuit currents from batteries 9.4 Short-circuit currents from rectifiers 9.5 Short-circuit currents from d.c. motors with independent excitation 9.6 Total short-circuit current 9.7 Example 9.7.1 Calculation of the impedances of cables and busbar conductors 9.7.2 Calculation of the short-circuit currents of the individual equipment 9.7.3 Calculation of the correction factors and corrected parameters 9.7.4 Calculation of partial short-circuit currents 9.7.5 Calculation of total short-circuit current 165 165 169 170 172 Effects of short-circuit currents 10.1 General 10.2 a.c. systems 10.2.1 Thermal effects and thermal short-circuit strength 10.2.2 Mechanical short-circuit strength of rigid conductors 10.3 d.c. auxiliary installations 10.3.1 Substitute rectangular function 10.3.2 Mechanical short-circuit strength of rigid conductors 10.3.3 Thermal short-circuit strength 10.4 Calculation examples (a.c. system) 10.4.1 Calculation of thermal effects 10.4.2 Electromagnetic effect 10.5 Calculation examples (d.c. system) 10.5.1 Thermal effect 10.5.2 Electromagnetic effect 162 174 178 182 184 185 190 191 193 195 195 195 195 201 209 209 212 215 216 216 217 218 218 220 Contents 11 12 13 xi Limitation of short-circuit currents 11.1 General 11.2 Measures 11.2.1 Measures in power systems 11.2.2 Measures in installations and switchgear arrangement 11.2.3 Measures concerning equipment 11.3 Structures of power systems 11.3.1 General 11.3.2 Radial system 11.3.3 Ring-main system 11.3.4 Meshed systems 225 225 226 226 Special problems related to short-circuit currents 12.1 Interference of pipelines 12.1.1 Introduction 12.1.2 Calculation of impedances for inductive interference 12.1.3 Calculation of induced voltage 12.1.4 Characteristic impedance of the pipeline 12.1.5 Voltage pipeline-to-earth 12.2 Considerations on earthing 12.2.1 General 12.2.2 Resistance of human body 12.2.3 Soil conditions 12.2.4 Relevant currents through earth 12.2.5 Earthing impedance 12.3 Examples 12.3.1 Interference of pipeline from 400-kV-line 12.3.2 Calculation of earthing resistances 245 245 245 247 252 253 254 257 257 257 258 259 261 262 262 264 Data of equipment 13.1 Three-phase a.c. equipment 13.1.1 System feeders 13.1.2 Transformers 13.1.3 Generators 13.1.4 Overhead lines 13.1.5 Cables 13.1.6 Reactors and resistors 13.1.7 Asynchronous motors 13.2 d.c. equipment 13.2.1 Conductors 13.2.2 Capacitors 13.2.3 Batteries 267 267 267 267 270 271 276 278 281 281 281 283 283 232 236 240 240 241 241 241 xii Contents Symbols, superscripts and subscripts 287 References 293 Index 299 List of figures Figure 1.1 Figure 2.1 Figure 2.2 Figure 2.3 Figure 2.4 Figure 2.5 Figure 2.6 Figure 2.7 Figure 2.8 Figure 2.9 Figure 2.10 Importance of short-circuit currents and definition of tasks as per IEC 60781, IEC 60865, IEC 60909 and IEC 61660 Vector diagram and time course of a.c. voltage Definition of vectors for current, voltage and power in three-phase a.c. systems. (a) Power system diagram and (b) electrical diagram for symmetrical conditions (positive-sequence component) Vector diagram of current, voltage and power of a three-phase a.c. system represented by the positive-sequence component. (a) Consumer vector system and (b) generator vector system Differentially small section of homogeneous three-phase a.c. line Vector diagram of voltages in RYB-system and in the zero-sequence component, positive- and negative-sequence components are NIL Vector diagram of voltages in RYB-system and positive-sequence component, zero- and negative-sequence components are NIL Vector diagram of voltages in RYB-system and negative-sequence component, zero- and positive-sequence components are NIL Measurement of impedance in the system of symmetrical components. (a) Positive-sequence component (identical with negative-sequence component) and (b) zero-sequence component Measuring of zero-sequence impedance of a two-winding transformer (YNd). Diagram indicates winding arrangement of the transformer: (a) measuring at star-connected winding and (b) measuring at delta-connected winding Measurement of positive-sequence impedance of a three-winding transformer (YNyn + d). Diagram indicates winding arrangement of the transformer 2 12 14 15 16 18 19 19 21 22 22 xiv List of figures Figure 2.11 Figure 2.12 Figure 2.13 Figure 2.14 Figure 2.15 Figure 2.16 Figure 2.17 Figure 2.18 Figure 2.19 Figure 2.20 Figure 2.21 Figure 4.1 Figure 4.2 Figure 4.3 Measurement of zero-sequence impedance of a three-winding transformer (YNyn + d). Diagram indicates winding arrangement of the transformer General scheme for the calculation of short-circuit currents in three-phase a.c. systems using the system of symmetrical components Equivalent circuit diagram of a single-phase short-circuit in RYB-system Equivalent circuit diagram in the system of symmetrical components for a single-phase short-circuit Equations for impedance analysis in power systems Equivalent circuit diagram of a power system with different voltage levels Graphical construction of voltages in the system of symmetrical components: (a) vector diagram RYB, (b) vector diagram of voltage in the zero-sequence component, (c) vector diagram of voltage in the positive-sequence component and (d) vector diagram of voltage in the negative-sequence component Simplified equivalent circuit diagram in RYB-components Equivalent circuit diagram in the system of symmetrical components Equivalent circuit diagram of an overhead line of infinitesimal length with earth return in RYB-system Equivalent circuit diagram of an overhead line of infinitesimal length with earth return in 012-system. (a) Positive-sequence component, (b) negative-sequence component and (c) zero-sequence component Types of short-circuits and short-circuit currents. (a) Three-phase short-circuit, (b) double-phase short-circuit without earth/ground connection, (c) double-phase short-circuit with earth/ground connection and (d) line-to-earth (line-to-ground) short-circuit Time-course of short-circuit currents. (a) Near-to-generator short-circuit (according to Figure 12 of IEC 60909:1988), (b) far-from-generator short-circuit (according to Figure 1 of IEC 60909:1988). Ik – initial (symmetrical) short-circuit current, ip – peak short-circuit current, Ik – steady-state short-circuit current and A – initial value of the aperiodic component idc Example for short-circuit current calculation with an equivalent voltage source at s.-c. location. (a) Three-phase a.c. system with three-phase short-circuit, (b) equivalent circuit diagram in 012-system (positive-sequence system), (c) equivalent circuit diagram in 012-system with equivalent voltage source 23 25 25 26 30 34 38 41 42 43 43 68 69 70 List of figures Figure 4.4 Figure 4.5 Figure 4.6 Figure 4.7 Figure 4.8 Figure 4.9 Figure 4.10 Figure 4.11 Figure 4.12 Figure 4.13 Figure 4.14 Figure 4.15 Figure 4.16 Figure 4.17 Figure 4.18 Figure 4.19 Figure 5.1 Figure 5.2 Figure 5.3 Figure 5.4 Figure 5.5 Estimate of maximal initial short-circuit current for different types of short-circuit and different impedance ratios Z1 /Z0 and Z2 /Z1 . Phase angle of Z 0 , Z 1 and Z 2 assumed to be identical. Parameter r: ratio of asymmetrical short-circuit current to three-phase short-circuit current Equivalent circuit diagram for the calculation of short-circuit currents inside power plant Equivalent circuit diagram for single-fed three-phase short-circuit Factor κ for the calculation of peak short-circuit current Equivalent circuit diagram for three-phase short-circuit fed from non-meshed sources Equivalent circuit diagram of a three-phase short-circuit in a meshed system Factor μ for calculation of symmetrical short-circuit breaking current Factors λmax and λmin for turbine generators (Figure 17 of DIN EN 60909.0 (VDE 0102)). (a) Series one and (b) series two Factors λmax and λmin for salient-pole generators (Figure 18 of DIN EN 60909.0 (VDE 0102) 1988). (a) Series one and (b) series two Factor q for the calculation of symmetrical short-circuit breaking current Equivalent circuit diagram of a 220-kV-system with short-circuit location Equivalent circuit diagram of a 110-kV-system with 220-kV-feeder Equivalent circuit diagram of a 10-kV system, f = 50 Hz A 110-kV system with short-circuit location System with different voltage levels with short-circuit location High-voltage system configuration for the auxiliary supply of a power station Equivalent circuit diagram of a single-phase short-circuit (system with low-impedance earthing). (a) Diagram in RYB-system, (b) equivalent circuit diagram in the system of symmetrical components Ratio of single-phase to three-phase short-circuit current depending on Z1 /Z0 and (γ1 − γ0 ) Earth-fault factors in relation to Z 1 /Z 0 and (γ1 − γ0 ). (a) Earth-fault factor δY and (b) earth-fault factor δB Earth-fault factor δ depending on X0 /X1 for different ratios R0 /X0 and R1 /X1 = 0.01  /I  depending on X /X Earth-fault factor δ and ratio Ik1 0 1 k3 xv 74 75 77 78 78 79 81 83 83 86 87 88 89 90 91 95 100 101 103 104 104 xvi List of figures Figure 5.6 Figure 5.7 Figure 5.8 Figure 5.9 Figure 5.10 Figure 5.11 Figure 5.12 Figure 5.13 Figure 5.14 Figure 5.15 Figure 5.16 Figure 5.17 Figure 5.18 Figure 5.19 Figure 5.20 Figure 5.21 Power system with isolated neutral with single-phase earth-fault. (a) Equivalent circuit diagram in RYB-system and (b) equivalent circuit diagram in the system of symmetrical components Limit for self-extinguishing of capacitive currents in air according to VDE 0228 part 2 Vector diagram of voltages, power system with isolated neutral. (a) Prior to fault and (b) during earth-fault Time course of phase-to-earth voltages, displacement voltage and earth-fault current. System with isolated neutral, earth-fault in phase R System with resonance earthing, earth-fault in phase R. (a) Equivalent diagram in RYB-system and (b) equivalent diagram in the system of symmetrical components Current limits according to VDE 0228 part 2:12.87 of ohmic currents IRes and capacitive currents ICE Equivalent circuit diagram of a power system with asymmetrical phase-to-earth capacitances. (a) Equivalent circuit diagram in the RYB-system and (b) equivalent circuit diagram in the system of symmetrical components Polar plot of the displacement voltage in a power system with resonance earthing Voltages and residual current in the case of an earth-fault; displacement voltage without earth-fault Current–voltage √ characteristic of a Petersen-coil; Ur = 20 kV/ 3; Ir = 640 A. (a) Minimal adjustment (50 A) and (b) maximal adjustment (640 A) Displacement voltage in non-faulted operation and residual current under earth-fault conditions; non-linear characteristic of the Petersen-coil Transformation of voltage in the zero-sequence component of transformers in the case of single-phase faults. (a) Equivalent circuit diagram in RYB-system and (b) equivalent circuit diagram in the system of symmetrical components Alternate earthing of transformer neutrals by Petersen-coils. (a) Two parallel transformers and (b) earthing at artificial neutral with reactor XD2 Fault current in the MV-system in the case of a short-circuit in the HV-system Resonance curve (displacement voltage) for different detuning factors in a 20-kV-system for different conditions Voltages in a 20-kV-system with resonance earthing for different tuning factors. (a) Phase-to-earth voltages and (b) displacement voltage (resonance curve) 105 106 107 108 109 111 112 114 115 117 118 119 121 121 122 123 List of figures xvii Figure 5.22 Figure 5.23 Figure 5.24 Figure 6.1 Figure 7.1 Figure 7.2 Figure 7.3 Figure 7.4 Figure 8.1 Figure 8.2 Figure 8.3 Figure 8.4 Figure 8.5 Figure 8.6 Figure 8.7 Figure 9.1 Figure 9.2 Figure 9.3 Figure 9.4 Equivalent circuit diagram of a 20-kV-system with resonance earthing Connection of a power station to a 220-kV-system with short-circuit location Equivalent diagram in the zero-sequence component for fault location F Equivalent circuit diagram of a LV-installation Equivalent circuit diagram with short-circuit inside switchyard B Equivalent circuit diagram with short-circuit at overhead-line tower Equivalent circuit diagram of a 20-kV-system Equivalent circuit diagram of a 110-kV-system with short-circuit location Equivalent circuit diagram of a power system with different voltage levels Equivalent circuit diagram for the calculation of impedance correction factor using %/MVA- or p.u.-system Generator directly connected to the power system. (a) Equivalent system diagram and (b) equivalent circuit diagram in the positive-sequence component Determination of the short-circuit current by superposition Equivalent circuit diagram of a power system with three-phase short-circuit. (a) Circuit diagram, (b) simplified diagram of a single-fed three-phase short-circuit and (c) time course of voltage with voltage angle ϕU Characteristic saturation curve method for determination of Potier’s reactance Calculated and measured values of factor q for the calculation of short-circuit breaking current of asynchronous motors; values of q as per Figure 4.13 (According to Figure 20 of IEC 60909-1:1991.) Equivalent circuit diagrams of equipment in d.c. auxiliary installations; typical time course of short-circuit current (according to Figure 1 of DIN EN 61660-1 (VDE 0102 Teil 10)). (a) Capacitor, (b) battery, (c) rectifier in three-phase a.c. bridge connection and (d) d.c. motor with independent excitation Standard approximation function of the short-circuit current (according to Figure 2 of IEC 61660-1:1997) Factor κC for the calculation of peak short-circuit current of capacitors (according to Figure 12 of IEC 61660-1:1997) Time-to-peak tpC for the calculation of short-circuit currents of capacitors (according to Figure 13 of IEC 61660-1:1997) 125 126 128 135 144 146 147 148 152 153 154 155 157 161 163 166 167 169 170 xviii List of figures Figure 9.5 Figure 9.6 Figure 9.7 Figure 9.8 Figure 9.9 Figure 9.10 Figure 9.11 Figure 9.12 Figure 9.13 Figure 9.14 Figure 9.15 Figure 9.16 Figure 9.17 Figure 9.18 Figure 9.19 Figure 9.20 Factor k1C for the calculation of rise-time constant (according to Figure 14 of IEC 61660-1:1997) Factor k2C for the calculation of decay-time constant (according to Figure 15 of IEC 61660-1:1997) Rise-time constant τ1B and time to peak tpB of short-circuit currents of batteries (according to Figure 10 of IEC 61660-1:1997) Factor λD for the calculation of quasi steady-state short-circuit current of rectifiers (according to Figure 7 of IEC 61660-1:1997) Factor κD for the calculation of peak short-circuit currents of rectifiers. Factor: R ∗ = (RN /XN )(1 + 2RDBr /3RN ) (according to Figure 8 of IEC 61660-1:1997) Factor κM for the calculation of peak short-circuit current of d.c. motors with independent excitation (according to Figure 17 of IEC 61660-1:1997) Time to peak of short-circuit currents for d.c. motors with independent excitation and τMec < 10 ∗ τF (according to Figure 19 of IEC 61660-1:1997) Factor k1M in the case of d.c. motors with independent excitation and τMec ≥ 10 ∗ τF (according to Figure 18 of IEC 61660-1:1997) Factor k2M in the case of d.c. motors with independent excitation and τMec < 10 ∗ τF (according to Figure 19 of IEC 61660-1:1997) Factor k3M in the case of d.c. motors with independent excitation and τMec < 10 ∗ τF (according to Figure 20 of IEC 61660-1:1997) Factor k4M in the case of d.c. motors with independent excitation and τMec < 10 ∗ τF (according to Figure 21 of IEC 61660-1:1997) Equivalent circuit diagram of a d.c. auxiliary installation Typical time curves of total short-circuit current in d.c. auxiliary installations, e.g., (a) with dominating part of motors, (b) with dominating part of rectifiers, (c) with dominating part of batteries and (d) in the case of low rectifier load (according to Figure 22 of DIN EN 61660-1 (VDE 0102 Teil 10)) Equivalent circuit diagram of the d.c. auxiliary installation (220 V), e.g., of a power station Partial short-circuit currents and total short-circuit current, d.c. auxiliary system as per Figure 9.18 Total short-circuit current, obtained by superposition of the partial short-circuit currents and approximated short-circuit current, d.c. auxiliary system as per Figure 9.18 171 171 172 173 173 176 176 177 177 178 178 180 181 182 193 194 List of figures Figure 10.1 Figure 10.2 Figure 10.3 Figure 10.4 Figure 10.5 Figure 10.6 Figure 10.7 Figure 10.8 Figure 10.9 Figure 10.10 Figure 10.11 Figure 10.12 Figure 10.13 Figure 10.14 Figure 10.15 Figure 10.16 Figure 10.17 Figure 11.1 Figure 11.2 Figure 11.3 Factor n for the calculation of thermal short-time current (heat dissipation of a.c. component) (according to Figure 22 of IEC 60909-0:2001) Factor m for the calculation of thermal short-time current (heat dissipation of d.c. component) (according to Figure 21 of IEC 60909-0:2001) Rated short-time current density of conductors. δ0 is the temperature at beginning of short-circuit and δ1 is the temperature at end of short-circuit. (a) ____: Copper; - - - -: unalloyed steel and steel cables and (b) Al, aluminium alloy, ACSR Maximal permissible thermal short-circuit current for impregnated paper-insulated cables Un up to 10 kV Arrangement of parallel conductors Correction factor k12 for the calculation of effective distance (according to Figure 1 of IEC 61660-2:1997) Factors Vσ and Vσ s for the calculation of bending stress (according to Figure 4 of IEC 60865-1:1993) Factors Vr and Vrs for the calculation of bending stress (according to Figure 5 of IEC 60865-1:1993) Factor VF for the calculation of bending stress (according to Figure 4 of IEC 60865-1:1993) Calculation of mechanical natural frequency (Factor c). Arrangement of distance elements and calculation equation (according to Figure 3 of IEC 60865-1:1993) Standard approximation function (a) and substitute rectangular function (b) (according to Figure 4 of IEC 60660-2:1997). Not to scale Factors Vσ and Vσ s for the calculation of bending stress on conductors (according to Figure 9 of IEC 61660-2:1997) Factor VF for the calculation of forces on supports (according to Figure 9 of IEC 61660-2:1997) Equivalent circuit diagram, data of equipment, resistance at 20◦ C Equivalent circuit diagram of a power system with wind power plant Arrangement of busbar conductor (data, see text) Standardised rectangular function and approximated total short-circuit current Selection of suitable voltage level for the connection of power stations Schematic diagram of a 400/132-kV-system for urban load; values of short-circuit currents in case of operation as two subsystems Schematic diagram of a 132-kV-system with power station xix 197 198 199 200 202 203 205 205 207 208 210 214 215 216 217 219 223 226 228 229 xx List of figures Figure 11.4 Figure 11.5 Figure 11.6 Figure 11.7 Figure 11.8 Figure 11.9 Figure 11.10 Figure 11.11 Figure 11.12 Figure 11.13 Figure 11.14 Figure 11.15 Figure 11.16 Figure 11.17 Figure 11.18 Equivalent circuit diagram of a 30-kV-system with feeding 132-kV-system: (a) Operation with transformers in parallel and (b) limitation of short-circuit current. Result of three-phase  = 3.2 GVA; S = 40 MVA; short-circuit current: SkQ rT ukrT = 12%; trT = 110/32; OHTL 95Al; ltot = 56 km Equivalent circuit diagram of a 380-kV-system and results of three-phase short-circuit current calculation: (a) Radial fed  = 8 GVA; OHTL system and (b) ring fed system. SkQ ACSR/AW 4 × 282/46; li = 120 km Schematic diagram of a 110-kV-substation fed from the 220-kV-system: (a) Operation with buscoupler closed and (b) operation with buscoupler open. Result of three-phase short-circuit current calculation Equivalent circuit diagram of a 6-kV-industrial system. Results of three-phase short-circuit current calculation: (a) Busbar sectionaliser closed and (b) Busbar sectionaliser open Equivalent circuit diagram of switchgear with single busbar Time course of short-circuit current in installations with and without Ip-limiter Cutaway view of an Ip-limiter support: (1) insulating tube, (2) explosive loading, (3) main conductor, (4) fuse element and (5) transducer Equivalent circuit diagram of a 10-kV-system with incoming feeder. Results of three-phase short-circuit current calculation: (a) impedance voltage 13% and (b) impedance voltage 17.5% Equivalent circuit diagram of a 10-kV-system with short-circuit limiting reactors. Results of three-phase short-circuit current calculation Equivalent circuit diagram of 11.5-kV-system fed from the 132-kV-system Equivalent circuit diagram of a power station with 132-kV-busbar. Results of three-phase short-circuit current calculation: SrG = 150 MVA; xd = 12–17.8% General structure of a radial system with one incoming feeder General structures of ring-main systems: (a) Simple structure with one feeding busbar and (b) structure with two feeding busbars (feeding from opposite sides) Principal structure of a high voltage system with different voltage levels Principal structure of meshed low voltage system: (a) Single-fed meshed system and (b) meshed system with overlapping feeding 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 List of figures Outline and distances of a high-voltage transmission-line tower. B: counterpoise; P: pipeline; L: conductor nearest to pipeline. E: first earth conductor (nearest to pipeline), also named E1; E2: second earth conductor Figure 12.2 Oblique exposure and crossing of pipeline and overhead line. (a) Plot plan and (b) elevation plan (detail from crossing location) Figure 12.3 Impedance of the human body (hand-to-hand) depending on the touch voltage Figure 12.4 Permissible touch voltage depending on the time of exposure Figure 12.5 Plot plan of the exposure length pipeline and transmission line Figure 12.6 Elevation plan of the overhead transmission tower and the pipeline Figure 12.7 Specific electric field strength (a) and specific induced voltage (b) of the pipeline between towers 2 and 11 Figure 12.8 Voltage pipeline-to-earth along the exposure length (0–6400 m) Figure 13.1 Principal structure of a power supply system and typical values of initial short-circuit power of public supply system Figure 13.2 Typical values for the impedance voltage of two-winding transformers Figure 13.3 Typical values for the ohmic losses, no-load losses and no-load current of two-winding transformers Figure 13.4 Tower outline of high-voltage transmission lines. (a) Single-circuit line and (b) double-circuit line Figure 13.5 Capacitances MV-cables (Un < 20 kV) Figure 13.6 Capacitances C1 (a) and capacitive loading current Ic (b) of HV-cables Figure 13.7 Reactance (positive-sequence system) of three-phase cables (Un ≤ 110 kV) Figure 13.8 Arrangement of a short-circuit limiting reactor √ Figure 13.9 Adjustable Petersen-coil 21 kV/ 3; 4 MVAr; Ir = 70.1–330 A; adjustable in 64 steps, 4.13 A each Figure 13.10 Earthing resistor made from CrNi-alloy steel fabric for indoor installation 3810 , 5 A for 10 s, 170 kV BIL, IP 00 Figure 13.11 Earthing resistor made from meandering wire for outdoor installation 16 , 400 A for 10 s, 75 kV BIL, IP 20 xxi Figure 12.1 250 256 258 259 263 264 265 266 268 269 269 271 276 277 277 278 279 280 281 List of tables Table 1.1 Table 1.2 Table 1.3 Table 2.1 Table 2.2 Table 2.3 Table 3.1 Table 3.2 Table 3.3 Table 3.4 Table 3.5 Table 3.6 Table 3.7 Table 3.8 Table 3.9 International documents and norms for short-circuit current calculation Selection of norms as referred in standards for short-circuit current calculation and as mentioned in this book Cross-reference list of standards on short-circuit current calculation Equivalent circuit diagrams and equations to represent short-circuits (single fault location) in three-phase a.c. systems in the RYB-system and in the 012-system Definitions of quantities in physical, relative and semirelative units Conversion of quantities between %/MVA-system, -system and p.u.-system (100 MVA-base) Impedance of system feeder, equivalent circuit diagram, calculation equations and remarks Impedance of two-winding transformer, equivalent circuit diagram, calculation equations and remarks Impedance of three-winding transformer, equivalent circuit diagram, calculation equations and remarks Equivalent circuit diagram of two- and three-winding transformers in the positive- and zero-sequence component Impedance of synchronous generator, equivalent circuit diagram, calculation equations and remarks Impedance of power-station unit, equivalent circuit diagram, calculation equations and remarks Impedance of overhead line (single-circuit), equivalent circuit diagram, calculation equations and remarks Impedance of short-circuit limiting reactor, equivalent circuit diagram, calculation equations and remarks Impedance of asynchronous motor, equivalent circuit diagram, calculation equations and remarks 5 6 9 28 33 35 46 47 48 50 51 52 53 54 55 xxiv List of tables Table 3.10 Table 3.11 Table 3.12 Table 3.13 Table 3.14 Table 3.15 Table 3.16 Table 3.17 Table 3.18 Table 4.1 Table 4.2 Table 4.3 Table 4.4 Table 5.1 Table 5.2 Table 5.3 Table 5.4 Table 6.1 Table 6.2 Table 6.3 Table 7.1 Impedance of static converter fed drive, equivalent circuit diagram, calculation equations and remarks Impedance of system load, equivalent circuit diagram, calculation equations and remarks Impedance of a conductor, equivalent circuit diagram, calculation equations and remarks Impedance of capacitor, equivalent circuit diagram, calculation equations and remarks Impedance of battery, equivalent circuit diagram, calculation equations and remarks Impedance of rectifier, equivalent circuit diagram, calculation equations and remarks Impedance of d.c. motor with independent excitation, equivalent circuit diagram, calculation equations and remarks Results of calculation of impedance in three-phase a.c. equipment Results of calculation of impedance of equipment in d.c. installations (without common branch as per IEC 61660-1) Voltage factor c according to IEC 60909-0 Equations for the calculation of initial symmetrical short-circuit currents Equivalent frequency for the calculation of decaying component Calculation of short-circuit currents of asynchronous motors Characteristics of different types of neutral handling in power systems Voltages in the zero-sequence component U0 transferred through 110/10-kV-transformer in the case of single-phase fault in the 110-kV-system according to Figure 5.17; Un : nominal system voltage Capacitive asymmetry CE for different parameters in a 20-kV-system Characteristics of a 20-kV-system with respect to resonance earthing Voltage factor c according to IEC 60909-0. (Voltage factors as per IEC 60781 are of different values. The standard is under review) Example for the calculation of maximal short-circuit currents in LV-system Example for the calculation of minimal short-circuit currents in LV-system System configurations and equations for the calculation of short-circuit currents in the case of double earth-faults 56 57 58 59 60 61 62 63 65 71 73 81 84 99 120 122 126 132 136 137 141 List of tables Table 8.1 Table 8.2 Table 8.3 Table 9.1 Table 10.1 Table 10.2 Table 10.3 Table 10.4 Table 10.5 Table 10.6 Table 11.1 Table 11.2 Table 12.1 Table 12.2 Table 12.3 Table 12.4 Table 12.5 Table 12.6 Table 13.1 Table 13.2 Table 13.3 Table 13.4 Table 13.5 Table 13.6 Table 13.7 Impedances of equipment and short-circuit current as per Figure 8.1 Impedances of equipment and short-circuit current using correction factor Assumed values of uf max for the calculation of the factor λ Resistances Rij and equivalent resistances Rresj for the calculation of correction factors; U : Voltage at short-circuit location prior to the short-circuit Maximal permissible conductor temperature and rated short-time current density; 1) – Normal operating condition; 2) – Short-circuit condition Data of materials for screening, armouring and sheaths of cables Factors α, β and γ for different arrangement of supports (according to Table 3 of IEC 60865-1:1993) Factors for the calculation of mechanical natural frequency. Swing is at right angle to the area of sub-conductor Results of calculation of thermal equivalent currents Results of short-circuit current calculation Selection of recommended voltage as per IEC 60038:1987 Result of loadflow and short-circuit analysis as per Figure 11.11 Interference between power system, communication circuits and pipelines Resistivity of soil ρ for different types of soil conditions Resistance of pipeline coatings Currents through earth for the design of earthing installations Reduction factor for typical power system installations; distance of earth conductor to phase conductor D ≈ 20 m; ρ = 100 m Resistance of earthing installations REI for different types and arrangement Data of transformers Typical data of synchronous generators Typical values of impedance of the positive-sequence component of MV-overhead lines Typical values of impedances of the positive- and zero-sequence component of HV-overhead lines (ρE = 100 m) Characteristic parameters of resistor elements Data of asynchronous motors Typical values of MKP-capacitors; self-healing dry insulation; different make of capacitor can and fuse xxv 153 154 162 179 196 201 204 209 217 218 227 237 246 248 254 260 261 262 270 271 274 274 280 282 283 xxvi List of tables Table 13.8 Table 13.9 Typical values of MKP-capacitors; resin insulation; round can Resistance of loaded batteries (data from several manufacturers) 284 284 Foreword Short-circuit currents are the dominating parameters for the design of equipment and installations, for the operation of power systems and for the analysis of outages and faults. Besides the knowledge about design of equipment in power systems, in auxiliary installations and about system operation constraints, the calculation of short-circuit currents is a central task for power system engineers. The book describes the individual equipment in power systems with respect of the parameters needed for short-circuit current calculation as well as methods for analysing the different types of short-circuits in power systems using the system of symmetrical components. Besides detailed explanation of the calculation methods for short-circuit currents and their thermal and electromagnetic effects on equipment and installations, short-time interference problems and measures for the limitation of short-circuit currents are explained. Detailed calculation procedures for the parameters and typical data of equipment are given in a separate chapter for easy reference. All aspects of the book are explained with examples based on engineering studies carried out by the author. The preparation of the book was finalised in December 2004 and reflects the actual status of the technique, norms and standards. Carrying out short-circuit studies always requires the application of the latest editions of standards, norms and technical recommendations, which can be obtained from the IEC-secretariat or from the national standard organisation. All comments in this book are given in good faith, based on the comprehensive technical experience of the author. The author wishes to thank very much his former colleague Dipl.-Ing. Heiner Rofalski for revising the text and improving the book. Most of the drawings were prepared by my students Stefan Drees and Elmar Vogel who spent much effort to obtain clear and understandable presentation. My thanks go also to the staff of IEEpublishers, especially to Ms. Sarah Cramer who encouraged me to write this book. Comments are highly appreciated. Bielefeld, December 2004 juergen.schlabbach@fh-bielefeld.de xxviii Foreword Professor Dr.-Ing. Jürgen Schlabbach, born 1952, member IEEE and VDI, studied power system engineering at the Technical University of Darmstadt/Germany, from where he got his Ph.D. in 1982. Until 1992 he was working in a consulting engineering company, responsible for planning and design of public and industrial supply systems. Since 1992 he has been professor for ‘Power system engineering and utilisation of renewable energy’ at the University of Applied Sciences in Bielefeld/Germany. His main working areas are planning of power systems, analysis of faults, power quality, interference problems and connection of renewable energy sources to power systems. He is also a consulting engineer in the mentioned fields. More information can be found on the author’s web-page http://www. fh-bielefeld.de/fb2/labor-ev. Chapter 1 Introduction 1.1 Objectives This book deals with the calculation of short-circuit currents in two- and three-phase a.c. systems as well as in d.c. systems, installed as auxiliary installations in power plants and substations. It is not the objective of this book to repeat definitions and rules of norms and standards, but to explain the procedure for calculating short-circuit currents and their effects on installations and equipment. In some cases repetition of equations, tables and diagrams from norms and standards however are deemed necessary for easy understanding. It should be emphasised in this respect that the presentation within this book is mainly concentrated on installations and equipment in high voltage systems, i.e., voltage levels up to 500 kV. Special considerations have to be taken in the case of long transmission lines and in power systems with nominal voltages above 500 kV. The calculation of short-circuit currents and of their effects are based on the procedures and rules defined in the IEC documents 61660, 60909, 60865 and 60781 as outlined in Table 1.1. 1.2 Importance of short-circuit currents Electrical power systems have to be planned, projected, constructed, commissioned and operated in such a way to enable a safe, reliable and economic supply of the load. The knowledge of the loading of the equipment at the time of commissioning and as foreseeable in the future is necessary for the design and determination of the rating of the individual equipment and of the power system as a whole. Faults, i.e., short-circuits in the power system cannot be avoided despite careful planning and design, good maintenance and thorough operation of the system. This implies influences from outside the system, such as short-circuits following lightning strokes into phase-conductors of overhead lines and damages of cables due to earth construction works as well as internal faults, e.g., due to ageing of insulation 2 Short-circuit currents materials. Short-circuit currents therefore have an important influence on the design and operation of equipment and power systems. Switchgear and fuses have to switch-off short-circuit currents in short time and in a safe way; switches and breakers have to be designed to allow even switch-on to an existing short-circuit followed by the normal switch-off operation. Short-circuit currents flowing through earth can induce impermissible voltages in neighbouring metallic pipelines, communication and power circuits. Unsymmetrical short-circuits cause displacement of the voltage neutral-to-earth and are one of the dominating criteria for the design of neutral handling. Short-circuits stimulate mechanical oscillations of generator units which will lead to oscillations of active and reactive power as well, thus causing problems of stability of the power transfer which can finally result in system black-out. Furthermore, equipment and installations must withstand the expected thermal and electromagnetic (mechanical) effects of short-circuit currents. In Figure 1.1 the typical time course of a short-circuit current is shown, which can be measured at high-voltage installations in the vicinity of power stations with synchronous generators, characterised by decaying a.c. and d.c. components of the • • Electromagnetic effects IEC 60865-1 Switch-on capability IEC 60265-1 • • • Peak short-circuit current (Maximal instantaneous value) Thermal effects IEC 60865-1 Protection measures against touch voltages in LV-installations DIN VDE 0100-470 Protection in HV-systems r.m.s. value • Breaking capability IEC 60265-1 IEC 60265-1 etc. Short-circuit breaking current (r.m.s. value at switching instant tmin) 24 19 • kA 14 • 9 4 • –1 • tmin –6 • –11 –16 Total time duration • Figure 1.1 Further aspects Touch and step voltages DIN VDE 0141 Interference DIN VDE 0228 Surge arresters IEC 60099-4 Overvoltages IEC 60071-1 IEC 60071-2 Neutral point earthing DIN VDE 0141 Insulation co-ordination IEC 60071-1 IEC 60071-2 Surge arresters IEC 60099-4 Importance of short-circuit currents and definition of tasks as per IEC 60781, IEC 60865, IEC 60909 and IEC 61660 Introduction 3 current. It is assumed that the short-circuit is switched-off approximately 14 periods after its initiation, which seems a rather long time, but was chosen for reason of a better visibility in the figure. Attention shall be put on four parameters of the short-circuit current. • The total time duration of the short-circuit current consists of the operating time of the protection devices and the total breaking time of the switchgear. • The peak short-circuit current, which is the maximal instantaneous value of the short-circuit current, occurs approximately a quarter period after the initiation of the short-circuit. As electromagnetic forces are proportional to the instantaneous value of the current, the peak short-circuit current is necessary to know in order to calculate the forces on conductors and construction parts affected by the shortcircuit current. • The r.m.s.-value of the short-circuit current is decaying in this example due to the decaying a.c. component. Currents through conductors will heat the conductor due to ohmic losses. The r.m.s. value of the short-circuit current, combined with the total time duration, is a measure for the thermal effects of the short-circuit. • The short-circuit breaking current is the r.m.s.-value of the short-circuit current at switching instant, i.e., at time of operating the circuit-breaker. While opening the contacts of the circuit-breaker, the arc inside the breaker will heat up the installation, which depends obviously on the breaking time as well. 1.3 Maximal and minimal short-circuit currents Depending on the task of engineering studies, the maximal or minimal short-circuit current has to be calculated. The maximal short-circuit current is the main design criteria for the rating of equipment to withstand the effects of short-circuit currents, i.e., thermal and electromagnetic effects. The minimal short-circuit current is needed for the design of protection systems and the minimal setting of protection relays. The short-circuit current itself depends on various parameters, such as voltage level, actual operating voltage, impedance of the system between any generation unit and the short-circuit location, impedance at the short-circuit location itself, the number of generation units in the system, the temperature of the equipment influencing the resistances and other parameters. The determination of the maximal and the minimal short-circuit current therefore is not as simple as might be seen at this stage [36]. It requires detailed knowledge of the system operation, i.e., which cables, overheadlines, transformers, generators, machines and reactors are in operation and which are switched-off. The assessment of the results of any calculation of short-circuit currents must take into account these restrictions in order to ensure that the results are on the safe side, i.e., that the safety margin of the calculated maximal short-circuit current is large enough without resulting in an uneconomic high rating of the equipment. The same applies to the minimal short-circuit current for which the safety margin must be assessed in such a way as to distinguish between the highest operating current and any short-circuit current, which has to be switched-off. 4 Short-circuit currents 1.4 Norms and standards Technical standards are harmonised on international basis. The international organisation to coordinate the works and strategies is the ISO (International Standards Organisation), whereas IEC (International Electrotechnical Commission) is responsible for the electrotechnical standardisation. The national standard organisations such as CENELEC in Europe, BSI in the United Kingdom, DKE in Germany, ANSI in the United States, JSI in Japan as well as national electrotechnical organisations such as IEE, VDE, IEEE, JES etc. are working in the working groups of IEC to include their sight and knowledge on technical items in the international standards and documents. On national basis, standards are adopted to the widest extent to the internationally agreed standards and documents. In some cases additions to the international standards are included in the national standards, however their status is ‘for information only’. The application of norms and standards has to be based on the latest issues, which can be obtained in Germany from Beuth-Verlag GmbH, Burggrafenstr. 6, D-10787 Berlin or from VDE-Verlag GmbH, Bismarckstr. 33, D-10625 Berlin. English versions are available from British Standards Institution, London/UK, in the United States from American National Standards Institute or any national standard organisation. Standards can also be searched and ordered through the web on the following URLs (appearance in alphabetical order): American National Standards Institute British Standards Institute Deutsches Institut für Normung International Electrotechnical Commission VDE-Verlag http://www.nssn.org/help.html http://www.bsonline.techindex.co.uk http://din.de http://www.iec.ch http://vde-verlag.de The structure of standards and norms dealing with short-circuit current calculation as published in IEC or EN-norms are outlined in Table 1.1. The listing should not be understood as a complete catalogue of standards but represents an overview only. Some of the mentioned standards are actually in draft status; others include corrections, additions and appendices. For details reference should be made to the IEC-homepage or the homepage of the national standards committee. The official actual standards catalogue is the only relevant document for any technical application. IEC-documents and national standards refer to other norms and standards. A short overview of these references is outlined in Table 1.2. With respect to the calculation of short-circuit currents and their effects, the standards are harmonised in most of the countries. The procedures and methods described are identical to those defined in the mentioned IEC-documents. Table 1.3 shows a cross-reference list between IEC, EN and BS. The classification numbers of the different standards differ in some cases from those of the IEC-documents or the EN-norms, however in most of the cases, classification numbers are similar, e.g.: Australian standard AS 3865, Swedish standard SS-EN 60865-1 and British standard BS EN 60865-1 are identical to IEC 60865-1 Introduction 5 (Short-circuit currents – calculation of effects; Part 1: Definitions and calculation methods). The standards’ catalogue of American National Standards Institute, to be accessed through the home-page of National Standards Systems Network, directly indicates the IEC- resp. EN-documents under the heading ‘short-circuit currents’. It is therefore fully sufficient to apply the IEC-documents for calculation of short-circuit currents and the analysis of their effects. Table 1.1 International documents and norms (with related VDE-classification) for short-circuit current calculation IEC (year) EN (year) DIN; VDE (year) Title, contents 61660-1 (1997) 61660-1 (1997) VDE 0102 Part 10 (1998–06) Short-circuit currents in d.c. auxiliary installations in power plants and substations Part 1: Calculation of short-circuit currents 61660-2 (1997) 61660-2 (1997) VDE 0103 Part 10 (1998–05) Short-circuit currents in d.c. auxiliary installations in power plants and substations Part 2: Calculation of effects 61660-3 (2000) 61660-3 Appendix 1 VDE 0102 Part 10 (2002–11) Short-circuit currents in d.c. auxiliary installations in power plants and substations Examples of calculation of short-circuit current and effects 60781 (1989) HD 581 S1 (1991) Appendix 2 VDE 0102 (1992–09) Application guide for calculation of short-circuit currents in low-voltage radial systems 60865-1 (1993) 60865-1 (1993) VDE 0103 (1994–11) Short-circuit currents – Calculation of effects Part 1: Definitions and calculation methods — — Appendix 1 VDE 103 (1996–06) Short-circuit currents – Calculation of effects Part 1: Definitions and calculation methods Examples for calculation 60909-0 (2001) 60909-0 (2001) VDE 0102 (2002–07) Short-circuit current calculation in a.c. systems 6 Short-circuit currents Table 1.1 Continued IEC (year) EN (year) DIN; VDE (year) Title, contents 60909-1 (1991) — Appendix 3 VDE 0102 (1997–05) Short-circuit current calculation in three-phase a.c. systems Part 1: Factors for the calculation of short-circuit currents in three-phase a.c. systems according to IEC 909 60909-2 (1992) — Appendix 4 VDE 0102 (2003–02) Electrical equipment Data for short-circuit current calculations in accordance with IEC 909 (1998) 60909-3 (1995) — VDE 0102 Part 3 (1997–06) Short-circuit current calculation in three-phase a.c. systems Part 3: Currents during two separate simultaneous single-phase line-to-earth short-circuits and partial short-circuit currents flowing through earth 60909-4 (2000) — Appendix 1 VDE 0102 (1992–09) Examples for the calculation of short-circuit currents Table 1.2 Selection of norms as referred in standards for short-circuit current calculation and as mentioned in this book IEC (year) EN (year) DIN; VDE (year) Title, contents 60038 (mod) (2002) HD472 S1 (1989) DIN IEC 60038 (2002) IEC standard voltages 60050(131) (1978) DIN IEC 60050-131 (1983) International Electrotechnical Vocabulary (IEV) Chapter 131: Electric and magnetic circuits 60050(151) (2001) DIN 40200 (1981–12) International Electrotechnical Vocabulary (IEV) Chapter 151: Electric and magnetic devices Some parts of DIN 40200 are identical to IEC 60050 Introduction Table 1.2 Continued IEC (year) EN (year) DIN; VDE (year) Title, contents 60050(195) (1998) International Electrotechnical Vocabulary (IEV) Chapter 195: Earthing and protection against electric shock 60050(441) (1998) International Electrotechnical Vocabulary (IEV) Chapter 441: Switchgear, controlgear and fuses 60071-1 (1993) 60071-1 (1995) VDE 0111 Part 1 (1996–07) Insulation coordination Definitions, principles and rules 60071-2 (1996) 60071-2 (1997) VDE 0111 Part 2 (1997–09) Insulation coordination Application guide TS 60479-1 (1994) Effects of currents on human being and livestock Part 1: General aspects TS 60479-2 (1982) Effects of currents passing through the human body Part 2: Special aspects 60986 (2000) Short-circuit temperature limits of electric cables with rated voltages from 6 kV up to 30 kV 60949 (1988) Calculation of thermally permissible short-circuit currents, taking into account non-adiabatic heating effects 60896-1 (1987) 60896-1 (1991) 61071-1 (mod) (1991) 61071-1 (1996) 60265, 60282, 60298, 60420, 60517, 60644, 60694, etc. 60099, 61643 60949 (1988) 7 60099-1 (1994) Stationary lead-acid batteries – General requirements and methods of test – Part 1: Vented types VDE 0560 Part 120 (1997–08) Capacitors for power electronics VDE 0670 Switchgear, circuit-breakers, fuses, etc. Various documents of IEC, parts of VDE 0670 VDE 0675 Part 1 (2000–08) Surge arresters Various documents of IEC, parts of VDE 0670 Calculation of thermally permissible short-circuit currents, taking into account non-adiabatic heating effects 8 Short-circuit currents Table 1.2 Continued IEC (year) EN (year) DIN; VDE (year) 60986 (2000) Title, contents Guide to the short-circuit temperature limits of electrical cables with a rated voltage from 1.8/3 (3.6) kV to 18/30 (36) kV EN 50160 (1999) VDE 0141 (2000–01) Earthing of special systems for electrical energy with nominal voltages above 1 kV VDE 0228 Part 1 (1987–12) Proceedings in the case of interference on telecommunication installations by electrical power installations – General VDE 0228 Part 2 (1987–12) Proceedings in the case of interference on telecommunication installations by electrical power installations interference by three-phase installations VDE 0228 Part 3 (1988–09) Proceedings in the case of interference on telecommunication installations by electrical power installations interference by alternating current traction systems VDE 0228 Part 4 (1987–12) Proceedings in the case of interference on telecommunication installations by electrical power installations interference by direct current systems VDE 0226 Part 1000 (1995–06) Current carrying capacity General, conversion factors DIN 13321 (1978–04) Electric power engineering; components in three-phase networks Concepts, quantities and their letter symbols DIN 40110-1 (1994) Quantities used in alternating current theory; two-line circuits DIN 40110-2 (2002) Quantities used in alternating current theory; three-line circuits DIN EN 50160 (2000–03) Voltage characteristics of electricity supplied by public distribution systems Introduction Table 1.3 9 Cross-reference list of standards on short-circuit current calculation IEC (year) EN (year) BS EN (year) Remarks (title see Table 1.1) 61660-1 (1997) 61660-1 (1997) 61660-1 (1997) Short-circuit currents in d.c. auxiliary installations in power plants and substations Part 1: Calculation of short-circuit currents 61660-2 (1997) 61660-2 (1997) 61660-2 (1997) Short-circuit currents in d.c. auxiliary installations in power plants and substations Part 2: Calculation of effects 61660-3 (2000) 61660-1 98/202382 DC Short-circuit currents in d.c. auxiliary installations in power plants and substations Examples of calculation of short-circuit current and effects 60781 (1989) HD 581 S1 (1991) 7638 (1993) Application guide for calculation of short-circuit currents in low-voltage radial systems 60865-1 (1993) 60865-1 (1993) 60865-1 (1994) Short-circuit currents – Calculation of effects Part 1: Definitions and calculation methods — — PD 6875-2 (1995) Short-circuit currents – Calculation of effects Part 1: Definitions and calculation methods; Examples for calculation 60909-0 (2001) 60909-0 (2001) 60909-0 (2001) Short-circuit current calculation in a.c. systems 60909-1 (1991) — PD IEC TR 60909-1 (2002) Short-circuit current calculation in three-phase a.c. systems Part 1: Factors for the calculation of short-circuit currents in three-phase a.c. systems according to IEC 909 60909-2 (1992) — PD 7639-2 (1994) 60909-3 (1995) prEN 60909-3 95/203556 DC 60909-4 (2000) — — Electrical equipment Data for short-circuit current calculations in accordance with IEC 909 (1988) Short-circuit current calculation in three-phase a.c. systems Part 3: Currents during two separate simultaneous single-phase line-to-earth short-circuits and partial short-circuit currents flowing through earth Examples for the calculation of short-circuit currents Chapter 2 Theoretical background 2.1 General A detailed deduction of the mathematical procedure is not given within the context of this book, but only the final equations are quoted. For further reading, reference is made to [1], [13]. In general, equipment in power systems is represented by equivalent circuits, which are designed for the individual tasks of power system analysis. For the calculation of no-load current and the no-load reactive power of a transformer, the no-load equivalent circuit is sufficient. Regarding the calculation of short-circuits, voltage drops and load characteristic a different equivalent circuit is required. The individual components of the equivalent circuits are resistance, inductive and capacitive reactance (reactor and capacitor), voltage source and ideal transformer. Voltage and currents of the individual components and of the equivalent circuit are linked by Ohm’s law. 2.2 Complex calculations, vectors and phasor diagrams When dealing with two- and three-phase a.c. systems, it should be noted that currents and voltages are generally not in phase. The phase position depends on the amount of inductance, capacitance and resistances of the impedance. The time course, e.g., of a current or voltage in accordance with √ u(t) = 2 ∗ U ∗ sin(ωt + ϕU ) (2.1a) √ i(t) = 2 ∗ I ∗ sin(ωt + ϕI ) (2.1b) can in this case be shown as a line diagram as per Figure 2.1. In the case of sinusoidal variables, these can be shown in the complex numerical level by rotating pointers, which rotate in the mathematically positive sense (counterclockwise) with 12 Short-circuit currents p 2 v p u (t) i (t) 3p 2 0 ^ i wI p 2 wU u^ u 3p 2 Figure 2.1 u (t ); i (t ) u^ ^i i p 2p vt wU wI Vector diagram and time course of a.c. voltage angular velocity ω as follows: √ U = 2 ∗ U ∗ e(j ωt+ϕU ) √ I = 2 ∗ I ∗ e(j ωt+ϕI ) (2.2a) (2.2b) where U and I are the r.m.s-values of voltage and current, ω is the angular frequency and ϕU and ϕI are the phase angle of voltage and current. The time course in this case is obtained as a projection on the real axis, see Figure 2.1. The generic term for an impedance Z is given as impedance or apparent resistance Z = R + jX (2.3a) The generic term for an admittance Y is admittance or apparent admittance Y = G + jB (2.3b) where R is the active resistance, X the reactance, G the active conductance and B the susceptance. The terms for the designation of resistances and admittances as per the above are stipulated in DIN 40110 (VDE 0110). The reactance depends on the particular angular frequency ω under consideration and can be calculated for capacitances C or inductances L from 1 ωC (2.4a) XL = ωL (2.4b) XC = For sinusoidal variables, the current i(t) through a capacitor, or the voltage u(t) at an inductance, can be calculated by the first derivative of the voltage, respectively Theoretical background 13 current, as follows: i(t) = C ∗ du(t) dt (2.5a) u(t) = L ∗ di(t) dt (2.5b) The derivation for sinusoidal currents and voltages at a reactance establishes that the current achieves its maximum value a quarter period after the voltage. When considering the process in the complex level, the pointer of the voltage precedes the pointer of the current by 90◦ . This corresponds to a multiplication by +j . For a capacitance on the other hand, the voltage does not reach its maximum value until a quarter period after the current; the voltage pointer lags behind the current by 90◦ , which corresponds to a multiplication by −j . This enables the relationships between current and voltage for inductances and capacitances to be shown in a complex notation U = j ωL ∗ I I= 1 ∗U j ωC (2.6a) (2.6b) The individual explanations of the quantities are given in the text above. Vectors are used to describe electrical processes. They are therefore used in d.c., a.c. and three-phase systems. Vector systems can, by definition, be chosen as required, but must not be changed during an analysis or calculation. It should also be noted that the appropriate choice of the vector system is of substantial assistance in describing and calculating special tasks. The need for vector systems is clear if one considers the Kirchhoff’s laws, for which the positive direction of currents and voltages must be specified. In this way, the positive directions of the active and reactive powers are then also stipulated. For comparison and transfer reasons, the vector system for the three-phase network (RYB components) is also to be used for other component systems (e.g., system of symmetrical components), which describe the three-phase network. If vectors are drawn as shown in Figure 2.2, the active and reactive powers generated by a generator in overexcited operation mode are positive. This vector system is designated as a generator vector system. Accordingly, the active and reactive power consumed by the load are positive when choosing the consumer vector system. When describing electrical systems voltage vectors are drawn from the phase conductor (named L1, L2, L3 or also R, Y, B) to earth (E). In other component systems, for instance in the system of symmetrical components (Section 2.3), the direction of the voltage vector is drawn from the conductor towards the particular reference conductor. On the other hand, vectors in phasor diagrams are shown in the opposite direction. The vector of a voltage conductor to earth is therefore shown in the phasor diagram from earth potential to conductor potential. 14 Short-circuit currents +P +Q (a) IRQ Three-phase a.c. system E R(L3) IYQ Y(L2) IBQ UYQ URQ IRQ + IYQ + IBQ = 0; URQ + UYQ + UBQ = 0; Figure 2.2 Positive sequence system B(L1) UBQ +P +Q (b) 01 IRQ UYQ= U1Q UYQ = UQ / 3 Definition of vectors for current, voltage and power in three-phase a.c. systems. (a) Power system diagram and (b) electrical diagram for symmetrical conditions (positive-sequence component) Based on the definition of the vector system, the correlation of voltage and current of an electrical system can be shown in phasor diagrams. Where steady-state or quasisteady-state operation is shown, r.m.s. value phasors are generally used. Figure 2.3 shows the phasor diagram of an ohmic-inductive load in the generator and in the consumer vector system. 2.3 System of symmetrical components 2.3.1 Transformation matrix The relationships between voltages and currents of a three-phase system can be represented by a matrix equation, e.g., with the aid of the impedance or admittance matrix. The equivalent circuits created by electrical equipment, such as lines, cables, transformers and machines, in this case have couplings in the three-phase system which are of an inductive, capacitive and galvanic type. This can be explained by using any short element of an overhead line in accordance with Figure 2.4 as an example, see also [1], [7]. The correlation of currents I and voltages U of the RYB system is as follows: ⎡ UR ⎤ ⎡ Z RR ⎢ ⎥ ⎢ ⎣U Y ⎦ = ⎣Z YR UB Z BR Z RY Z YY Z BY ⎤ ⎡ ⎤ IR ⎥ ⎢ ⎥ Z YB ⎦ ∗ ⎣I Y ⎦ Z RB Z BB (2.7) IB where Z RR , Z YY , Z BB are the self-impedances of each phase; Z RY , Z RB the coupling (mutual) impedances between phase R and Y, respectively, B; Z YR , Z YB the coupling (mutual) impedances between phase Y and R, respectively, B; and Z BR , Z BY the coupling (mutual) impedances between phase B and R, respectively, Y. All the values of this impedance matrix can generally be different. Because of the cyclic-symmetrical construction of three-phase systems only the self-impedance and Theoretical background (a) Q Positive sequence system I1 U –Q 3 R X U –R U –x 15 P1, Q1 01 +Re U –Q =U – R+ U –X 3 U –R jQ1 –SI –I1 P –1 w U – x = jXI –1 –UR = RI –1 + Im Q (b) Positive sequence system I1 U –Q 3 R X U –R U –X P1, Q1 01 +Re U –R U –Q =U – R + –UX 3 a U –X w –jQ 1 + Im RI1 = – UR – – –I1 Figure 2.3 –P1 = –U –Ux = jXI –1 – X –S1 Vector diagram of current, voltage and power of a three-phase a.c. system represented by the positive-sequence component. (a) Consumer vector system and ( b) generator vector system two coupling impedances are to be considered. A cyclic-symmetrical matrix is thus obtained. ⎤ ⎡ ⎤ ⎡ ⎤ ⎡ Z A Z M1 Z M2 IR UR ⎥ ⎢ ⎥ ⎢ ⎥ ⎢ Z Z U Z I = ∗ (2.8) ⎣ Y ⎦ ⎣ M2 A M1 ⎦ ⎣ Y ⎦ UB Z M1 Z M2 Z A IB 16 Short-circuit currents Self coefficients Coupling coefficients L⬘Ldl R⬘dl L⬘dl B L⬘Edl C⬘Ldl C⬘Edl G⬘Ldl G⬘Edl Y R E R⬘Edl L⬘Edl Longitudinal Figure 2.4 Transversal Differentially small section of homogeneous three-phase a.c. line where Z A is the self-impedances of each phase and Z M1 , Z M2 the coupling (mutual) impedances between the phases. The multiplicity of couplings between the individual components of three-phase systems complicates the application of the solution methods, particularly when calculating extended networks. For this reason, a mathematical transformation is sought which transfers the RYB-components to a different system. The following conditions should apply for the transformation: • The transformed voltages should still depend only on one transformed current. • For symmetrical operation only one component should be unequal to zero. • The linear relationship between current and voltage should be retained, i.e., the transformation should be linear. • For symmetrical operation, the current and voltage of the reference component should be retained (reference component invariant). The desired transformation should in this case enable the three systems to be decoupled in such a way that the three components, named 0, 1 and 2, are decoupled from each other in the following manner: ⎡ ⎤ ⎡ ⎤ ⎡ ⎤ U0 0 I0 Z0 0 ⎢ ⎥ ⎢ ⎥ ⎢ ⎥ (2.9) ⎣U 1 ⎦ = ⎣ 0 Z 1 0 ⎦ ∗ ⎣ I 1 ⎦ U2 0 0 Z2 I2 These requirements are fulfilled by the transformation to the system of symmetrical components [29], which is realised for voltages and currents by the transformation matrix T according to Equations (2.10). It should be noted that the factor 13 is part of the transformation and therefore belongs to the matrix T. U 012 = T ∗ U RYB (2.10a) I 012 = T ∗ I RYB (2.10b) Theoretical background ⎡ ⎤ ⎡ 1 1 U0 ⎢ ⎥ 1⎢ ⎣U 1 ⎦ = ⎣1 a 3 U2 1 a2 1 ⎤ ⎡ UR ⎤ ⎥ ⎢ ⎥ a 2 ⎦ ∗ ⎣U Y ⎦ 1 (2.10c) UB a ⎡ ⎤ ⎡ 1 1 I0 ⎢ ⎥ 1⎢ ⎣I 1 ⎦ = ⎣1 a 3 I2 1 a2 17 ⎤ ⎡ IR ⎤ ⎥ ⎢ ⎥ a 2 ⎦ ∗ ⎣I Y ⎦ IB a (2.10d) The voltage vector of the 012-system is linearly linked to the voltage vector of the RYB-system (the same applies for the currents). The system of symmetrical components is defined according to DIN 13321. The reverse transformation of the 012-system to the RYB-system is achieved by the matrix T−1 in accordance with U RYB = T −1 ∗ U 012 (2.11a) I RYB = T −1 ∗ I 012 (2.11b) ⎡ 1 ⎢ ⎥ ⎢ ⎣U Y ⎦ = ⎣1 UB 1 ⎡ ⎡ UR IR ⎤ ⎤ ⎡ 1 1 a2 1 ⎤ U0 ⎥ ⎢ ⎥ a ⎦ ∗ ⎣U 1 ⎦ a a2 1 1 ⎢ ⎥ ⎢ ⎣I Y ⎦ = ⎣1 a 2 IB 1 a ⎤ ⎡ (2.11c) U2 ⎤ ⎡ ⎤ I0 ⎥ ⎢ ⎥ a ⎦ ∗ ⎣I 1 ⎦ I2 a2 (2.11d) The following applies for both transformation matrices T and T−1 : T ∗ T−1 = E (2.12) with the identity matrix E. The complex rotational phasors a and a 2 have the following meanings: √ ◦ a = ej 120 = − 21 + j 21 3 (2.13a) √ ◦ a 2 = ej 240 = − 12 − j 21 3 (2.13b) 1 + a + a2 = 0 (2.13c) Multiplication of a vector with either a or a 2 will only change the phase shift of the vector by 120◦ or 240◦ but will not change the length (amount) of it. 18 Short-circuit currents 2.3.2 Interpretation of the system of symmetrical components If only one zero-sequence component exists, the following applies: ⎤ ⎡ ⎤ ⎡ ⎤ ⎡ ⎤ ⎡ 1 1 1 U0 U0 UR ⎥ ⎢ ⎥ ⎢ ⎥ ⎢ ⎥ ⎢ 2 1 a U a U 0 = ∗ = ⎦ ⎣ ⎦ ⎣ 0⎦ ⎣ Y⎦ ⎣ UB U0 0 1 a a2 (2.14) No phase displacement exists between the three a.c. voltages of the RYB-conductors. The zero-sequence component is thus a two-phase a.c. system. Figure 2.5 shows the phasor (vector) diagram of the voltages of the RYB-system and the voltage of the zero-sequence component. + Re –UR; –UY; –UB; –U0 +Im Figure 2.5 e jvt Vector diagram of voltages in RYB-system and in the zero-sequence component, positive- and negative-sequence components are NIL Where only a positive-sequence exists, the following applies: ⎡ ⎤ ⎡ ⎤ ⎤ ⎡ ⎤ ⎡ 1 1 1 U1 0 UR ⎥ ⎥ ⎢ ⎥ ⎢ ⎢ ⎥ ⎢ ⎣U Y ⎦ = ⎣1 a 2 a ⎦ ∗ ⎣U 1 ⎦ = ⎣a 2 U 1 ⎦ UB 0 a U1 1 a a2 (2.15) A three-phase system with a positive rotating phase sequence R, Y, B is represented by the positive-sequence component only. Figure 2.6 shows the phasor (vector) diagram of the voltages of the RYB-system and the voltage of the positive-sequence component. Where only a negative-sequence component exists, the following applies: ⎤ ⎤ ⎡ ⎤ ⎡ ⎡ ⎤ ⎡ 1 1 1 U2 0 UR ⎣U Y ⎦ = ⎣1 a 2 a ⎦ ∗ ⎣ 0 ⎦ = ⎣ a U 2 ⎦ (2.16) U2 UB a2 U 2 1 a a2 A three-phase system with a positive counter-rotating phase sequence R, B, Y is represented by the negative-sequence component only. Figure 2.7 shows the phasor (vector) diagram of the voltages of the RYB-system and the voltage of the negative-sequence component. Theoretical background 19 + Re –UR = –U1 + Im e jvt UY = a2 U1 UB = a U1 Figure 2.6 Vector diagram of voltages in RYB-system and positive-sequence component, zero- and negative-sequence components are NIL + Re UR = U2 + Im e jvt UB = a2 U2 UY = a U2 Figure 2.7 Vector diagram of voltages in RYB-system and negative-sequence component, zero- and positive-sequence components are NIL 2.3.3 Transformation of impedances For the transformation of the impedance matrix, Equations (2.17) apply in accordance with the laws of matrix multiplication, taking account of Equations (2.10) and (2.12) T URYB = T ZRYB T−1 U012 = Z012 T IRYB (2.17a) I012 (2.17b) As T URYB is equal to U012 and T IRYB is equal to I012 the impedance matrix Z012 in the system of symmetrical components is obtained by multiplying the impedance matrix ZRYB in the RYB-system with the matrix T from left and with T−1 from right. Based on Equation (2.8) the impedances as per Equations (2.18) for the conversion 20 Short-circuit currents of the impedances of the three-phase system to the 012-system are obtained. Z 0 = Z A + Z M1 + Z M2 (2.18a) Z 1 = Z A + a 2 Z M1 + a Z M2 (2.18b) Z 2 = Z A + a Z M1 + a 2 Z M2 (2.18c) The impedance values of the positive-sequence and negative-sequence components are generally equal. This applies to all non-rotating equipment. The impedance of the zero-sequence component mainly has a different value from the impedance of the positive-sequence component. If mutual coupling is absent, as perhaps with three single-pole transformers connected together to form a three-phase transformer, the impedance of the zero-sequence component is equal to the impedance of the positive- or (negative-) sequence component. 2.3.4 Measurement of impedances of the symmetrical components Any equipment can be represented by an equivalent circuit diagram using the system of symmetrical components, which can be determined. To obtain the parameters of the equivalent circuit diagram either short-circuit measurement or no-load measurement has to be carried out in accordance with Figure 2.8 with a voltage system representing the individual component of the system of symmetrical components, i.e., • Three-phase voltage system with positive rotating phase sequence RYB to measure the positive-sequence component. • Three-phase voltage system with positive counter-rotating phase sequence RBY to measure the negative-sequence component. • a.c. voltage system without any phase displacement of the voltage in the three phases of the equipment to measure the zero-sequence component. It should be noted in this respect that the type of measurement, i.e., short-circuit measurement or no-load measurement, depends on the type of analysis to be carried out. For short-circuit current calculation or voltage drop estimate, the parameters obtained by short-circuit measurement are needed. Impedance will be calculated based on the measured voltage and current as outlined in Figure 2.8. Special attention must be taken in case of transformers, as the impedance in the zero-sequence component depends on the type of winding arrangement (star or delta connection) and on the handling of the neutral of the transformer. Figure 2.9 indicates the measurement of the zero-sequence impedance in the case of a twowinding transformer with Yd-arrangement. The Y-connected winding is fed from a single-phase a.c. system; the zero-sequence impedance is present in case the neutral of the transformer is earthed (Figure 2.9(a)). Due to the delta-connection of the second winding a current in the delta winding is present in this case. If the neutral of the transformer remains isolated, the current in the Y-winding is Zero and thus the impedance is infinite. If the zero-sequence impedance of the delta-connected Theoretical background (a) B Y GS 3~ 21 1) 2) R IR (b) B Y G 1~ R IR Figure 2.8 UR 1) 2) UR Measurement of impedance in the system of symmetrical components. (a) Positive-sequence component (identical with negative-sequence component) and (b) zero-sequence component winding shall be measured, the current in the delta winding is Zero in any case and the zero-sequence impedance of the delta-connected winding is infinite (Figure 2.9(b)). To measure the impedance of three-winding transformers in the positive- and zero-sequence component three different measurements have to be carried out. For the positive-sequence component the measurement is outlined in Figure 2.10 and further explained as below: 1. Feeding with three-phase a.c. system at winding 1 (HV-side) Short-circuit at winding 2 (MV-side) Measurement of uk12 , respectively, ukHVMV 2. Feeding with three-phase a.c. system at winding 1 (HV-side) Short-circuit at winding 3 (LV-side) Measurement of uk13 , respectively, ukHVLV 3. Feeding with three-phase a.c. system at winding 2 (MV-side) Short-circuit at winding 3 (LV-side) Measurement of uk23 , respectively, ukMVLV The impedances (reactances) as per the equivalent circuit diagram (see Table 3.3) are  ukHVLV ukMVLV ukHVMV (2.19a) XTHV = 0.5 ∗ + − SrTHVMV SrTHVLV SrTMVLV  ukMVLV ukHVMV ukHVLV XTMV = 0.5 ∗ + − (2.19b) SrTMVLV SrTHVMV SrTHVLV  ukHVLV ukMVLV ukHVMV (2.19c) XTLV = 0.5 ∗ + − SrTHVLV SrTMVLV SrTHVMV 22 Short-circuit currents (a) ü I 0 3 1U I0 3I0 2U 1V I0 2V 1W I0 G 1 U0 2W 0 ü:1 (b) 1U 2U 1V 3I0 = 0 2V 1W 2W Figure 2.9 G 1 Measuring of zero-sequence impedance of a two-winding transformer ( YNd). Diagram indicates winding arrangement of the transformer: (a) measuring at star-connected winding and (b) measuring at delta-connected winding 1 (a) 3 2 1 (b) G 3~ 3 2 I11 U11 (c) 1 3 2 (d) 1 3 2 G G 3~ Figure 2.10 I11 I12 U11 U12 3~ Measurement of positive-sequence impedance of a three-winding transformer ( YNyn + d). Diagram indicates winding arrangement of the transformer Theoretical background (a) 1 OS 3 2 US MS (b) 1 3 23 2 G 1~ U01 3I 01 (c) 1 G 1~ 3I01 Figure 2.11 U01 3 2 (d) 1 3 2 U02 G 1~ 3I02 Measurement of zero-sequence impedance of a three-winding transformer ( YNyn + d). Diagram indicates winding arrangement of the transformer; for explanations see text The measurement in the zero-sequence component is carried out in a similar way as outlined in Figure 2.11. 4. Feeding with single-phase a.c. system at winding 1 (HV-side) Short-circuit at winding 2 (MV-side) Open-circuit at winding 3 (LV-side) Measurement of uk012 , respectively, uk0HVMV 5. Feeding with single-phase a.c. system at winding 1 (HV-side) Short-circuit at winding 3 (LV-side) Open-circuit at winding 2 (MV-side) Measurement of uk013 , respectively, uk0HVLV 6. Feeding with single-phase a.c. system at winding 2 (MV-side) Short-circuit at winding 3 (LV-side) Open-circuit at winding 1 (HV-side) Measurement of uk023 , respectively, uk0MVLV The impedances (reactances) as per the equivalent circuit diagram (see Table 3.3) are  u0kHVLV u0kMVLV u0kHVMV X0THV = 0.5 ∗ (2.20a) + − SrTHVMV SrTHVLV SrTMVLV  u0kMVLV u0kHVMV u0kHVLV X0TMV = 0.5 ∗ (2.20b) + − SrTMVLV SrTHVMV SrTHVLV  u0kHVLV u0kMVLV u0kHVMV X0TLV = 0.5 ∗ (2.20c) + − SrTHVLV SrTMVLV SrTHVMV 24 Short-circuit currents Any impedance in the neutral of the transformer has no effect on the impedance in the positive-sequence component, as the three phase current are summing up to zero at neutral point, and no current flows through the neutral impedance. In the zerosequence component the neutral impedance will appear with three-times its value in the RYB-system, as the current through the neutral is three-times the phase current during the measurement of zero-sequence impedance. 2.4 Equivalent circuit diagram for short-circuits The system of symmetrical components can be used for the analysis of symmetrical and asymmetrical operation of power systems. Faults in general and short-circuit currents in particular are the most severe operating conditions in power systems. Each of the different faults, e.g., single-phase-to-ground, three-phase, etc., can be represented by an equivalent circuit diagram in the RYB-system and by this in the 012-system (system of symmetrical components) as well. The calculation of shortcircuits in the system of symmetrical components is generally carried out as per Figure 2.12. 1. Draw the equivalent circuit diagram in RYB-components (RYB-system). 2. Draw the short-circuit location at the connection of the RYB-system, the shortcircuit should be assumed symmetrical to phase R. 3. Definition of fault equations in RYB-components, equations should be given preference indicating which voltages and/or currents are Zero or are equal to each other. 4. Transformation of fault conditions with the matrices T and T−1 into the 012-system (system of symmetrical components). Rearrange the transformed fault equations in such a way that voltages and/or currents are Zero or are equal to each other. 5. Draw the equivalent circuit diagrams in the system of symmetrical components. 6. Draw connection lines between the three components to realise the fault conditions. 7. Calculation of currents and voltages in the system of symmetrical components. 8. Transformation of current and voltages into the RYB-system using transformation matrix T−1 . The eight steps as defined above are explained in case of a single-phase short-circuit in a three-phase a.c. system. Figure 2.13 indicates the equivalent circuit diagram in the RYB-system (item 1 above) as well as the type of short-circuit at the short-circuit location (item 2 above). Any fault in the three-phase a.c. system has to be described by three independent conditions for the voltages of currents of combinations of both. In case of the single-phase short-circuit, the fault equations in the RYB-system (item 3 above) are U R = 0; I Y = 0; IB = 0 (2.21) Theoretical background Equivalent circuit diagram RYB (1) + (2) 25 Currents and voltages RYB (8) T –1 Fault equations RYB Currents and voltages 012 (3) (7) T –1 T Fault equations 012 Equivalent circuit diagram 012 (5) + (6) (4) Figure 2.12 General scheme for the calculation of short-circuit currents in threephase a.c. systems using the system of symmetrical components. For explanations see text Z0; Z1; Z2 B Y R IR UY; UB Figure 2.13 Equivalent circuit diagram of a single-phase short-circuit in RYB-system 26 Short-circuit currents The transformation into the system of symmetrical components (item 4 above) is carried out using the transformation matrices by Equations (2.10) and (2.11). The fault equations for the voltages in the system of symmetrical components are UR = 0 = U0 + U1 + U2 (2.22a) and for the currents I0 = I1 (2.22b) I0 = I2 (2.22c) The fault conditions as per Equations (2.22) can only be realised by a series connection of the positive-, negative- and zero-sequence component. The equivalent circuit diagram (item 5 above) in the system of symmetrical components is outlined in Figure 2.14 as well as the connection of the individual components to realise the fault conditions (item 6 above). The positive-, negative- and zero-sequence component are represented by the impedances Z 1 ; Z 2 ; Z 0 . The currents and voltages of the system of symmetrical I1 Z1 U1 E1 01 I2 Z2 U2 02 I0 Z0 U0 00 Figure 2.14 Equivalent circuit diagram in the system of symmetrical components for a single-phase short-circuit Theoretical background 27 components (item 7 above) are then calculated as I0 = I1 = I2 = U 0 = −Z 0 ∗ E1 Z0 + Z1 + Z2 E1 Z0 + Z1 + Z2 U 1 = (Z 0 + Z 2 ) ∗ U 2 = −Z 2 ∗ E1 Z0 + Z1 + Z2 E1 Z0 + Z1 + Z2 (2.23a) (2.23b) (2.23c) (2.23d) The currents and voltages of the RYB-components (item 8) are calculated using the transformation matrix, Equation (2.11) and the voltages as per Equations (2.24) are obtained U Y = E1 ∗ Z 0 ∗ (a 2 − 1) + Z 2 ∗ (a 2 − a) Z0 + Z1 + Z2 (2.24a) U B = E1 ∗ Z 0 ∗ (a − 1) + Z 2 ∗ (a − a 2 ) Z0 + Z1 + Z2 (2.24b) IR = 3 ∗ E1 Z0 + Z1 + Z2 (2.24c) E1 3 ∗ Z1 2 + k (2.25b) In the case of Z 1 = Z 2 and |Z 0 /Z 1 | = k the voltages and the current can be expressed by √ √ k2 + k + 1 |U Y | = |U B | = 3E1 (2.25a) 2+k Ik1 = All other faults in three-phase a.c. systems can be analysed in the same manner by the system of symmetrical components. Table 2.1 represents the equivalent circuit diagrams of all short-circuits which can occur in power systems (single fault location only) and the equations to describe the fault both in the RYB-system and in the system of symmetrical components. 2.5 Series and parallel connection Power systems include numerous equipment, such as lines, transformers, reactors and generators which are connected in series and/or in parallel to other equipment according to their location in the system’s topology. The related total impedance at the short-circuit location has to be obtained by mathematical procedures, including Table 2.1 Equivalent circuit diagrams and equations to represent short-circuits (single fault location) in three-phase a.c. systems in the RYB-system and in the 012-system RYB-system 012-system Equivalent circuit diagram Fault condition Voltages Three-phase B Y R I E U Fault condition Currents Voltages Currents Without earth connection UR = UY IR + IY + IB = 0 Without earth connection U1 = 0 I0 = 0 UY = UB U2 = 0 With earth connection UR = 0 With earth connection U1 = 0 UY = 0 U2 = 0 UB = 0 U0 = 0 Equivalent circuit diagram I1 “1” U1 01 I2 “2” U2 02 I0 “0” 00 U0 Double-phase Without earth connection UY = UB IR = 0 B Without earth connection U1 = U2 I 1 = −I 2 I0 = 0 I Y = −I B Y R I U E With earth connection IR = 0 UY = 0 UB = 0 I1 With earth connection U1 = U2 “1” U1 01 I1 + I2 + I0 = 0 I2 U1 = U0 U2 “2” 02 I0 “0” U0 00 Line-to-ground UR = 0 B Y IY = 0 IB = 0 U1 + U2 + U0 = 0 I1 = I2 I1 = U0 I1 R “1” I E U1 01 U I2 U2 “2” 02 I0 “0” 00 U0 30 Short-circuit currents star-delta- and delta-star-transformation. The equations to calculate total impedance within a given system topology are outlined in Figure 2.15. 2.6 Definitions and terms A clear usage of terms defined in standards and norms is essential in all areas of technique. The knowledge of IEC-documents, national standards and norms therefore Diagram Impedance–admittance Current–voltages 2 Z = Z1 + Z2 I = I 1 = I2 2 Y = Y 1Y 2 Y1 + Y2 U = U1 + U2 2 Z= Z1 Z2 Z1 + Z2 I = I 1 + I2 2 Y = Y1 + Y2 Serial connection 1 I1 I2 Z1 Z2 1 Z = 1/Y Parallel connection I1 Z = 1/Y1 1 I 1 I2 Z = 1/Y 2 2 I Z = 1/Y U = U1 = U2 Star-delta-transformation 1 I1 Z1 = 1/Y1 0 Z3 = 1/Y3 3 Z 12 = Z1 Z2 + Z1 Z3 + Z2 Z3 Z3 Z 13 = Z1 Z2 + Z1 Z3 + Z2 Z3 Z2 Z 23 = Z1 Z2 + Z1 Z3 + Z2 Z3 Z1 Y 12 = Y 1Y 2 Y1 + Y2 + Y3 I Z − I 2 Z2 I 12 = 1 1 Z 12 Z2 = 1/Y2 I2 2 I3 1 I13 I12 I 1 + I 2 + I3 = 0 Z13= 1/Y13 Z12= 1/Y12 Y 13 = Y 1Y 3 Y1 + Y2 + Y3 I Z − I 3 Z3 I 13 = 1 1 Z 13 I31 I21 Y 23 = Y 2Y 3 Y1 + Y2 + Y3 I Z − I 3 Z3 I 23 = 2 2 Z 23 3 I32 I23 Z23 = 1/Y23 Impedance: Z = R + jX Figure 2.15 2 Equations for impedance analysis in power systems [30,31] Theoretical background Diagram Impedance–admittance 31 Current–voltages Delta-star-transformation 1 I13 I12 Z13 Z12 I31 3 I21 I32 I23 Z23 2 Z1 = Z 12 Z 13 Z 12 + Z 23 + Z 13 I 1 = I 12 + I 13 Z2 = Z 12 Z 23 Z 12 + Z 23 + Z 13 I 2 = I 21 + I 23 Z3 = Z 13 Z 23 Z 12 + Z 23 + Z 13 I 3 = I 31 + I 32 1 I1 Z1 Z3 3 0 Z2 I2 2 I3 Admittance: Y = G + jB Figure 2.15 Continued is absolutely necessary. Some definitions of terms as related to short-circuit currents are based on the German standard DIN 40110 and IEC 60050 as stated below. Further reference is made to the IEC-documents as per Tables 1.1 and 1.2. Nominal value Example A suitable rounded value of a physical quantity to define or identify an element, a group of elements or an installation. The nominal value 110 kV defines a voltage level for an electrical power system. Actual voltages in the system are different from the nominal voltage 110 kV. Limiting value Example A defined minimal or maximal value of a physical quantity. The minimal value of a current setting has to be defined in order to guarantee the suitable operation of a protection or control device. Rated value The value of a physical unit for operating conditions as defined for the element, group of elements or installation by the manufacturer. The rated apparent power of a transformer should not be exceeded at the defined operating conditions, in order to protect the transformer from damage by overheating. Example 32 Short-circuit currents Rated data Example Summary of rated data and operating conditions. The definition of the rated current of a cable is not sufficient, as the thermal constraints are fixed besides others by ambient temperature, thermal resistance of the soil, duration of current loading and pre-load conditions. 2.7 Ohm-system, p.u.-system and %/MVA-system 2.7.1 General It is necessary to calculate the values of the equipment of electrical supply systems in order, for instance, to examine the behaviour of the supply system during normal operation and in the state of disturbed operation. In this connection, equipment such as generators, transformers, lines, motors and capacitors are of interest. Simulation of consumers is only necessary in special cases. It may also be possible to determine the equipment data from name plate rating or tabulated data. Various systems of units are available for calculation. 2.7.1.1 Physical quantities To describe the steady-state conditions of equipment and of the system, four basic unit quantities are required, i.e., voltage U , current I , impedance Z and power S with the units Volt, Ampere, Ohm and Watt. Other units have to be converted into the ISO-standard unit system [32]. The units are linked to each other by Ohm’s law and the power equation. U I (2.26a) S = U ∗ I∗ (2.26b) Z= where U is the voltage across the impedance Z and, I the current through the impedance (I ∗ is the conjugate-complex value of I ). In the case of a three-phase system the apparent power S is calculated as per Equation (2.26c) with the voltage U being the phase-to-phase voltage, e.g., the rated voltage of an equipment. √ S = 3 ∗ U ∗ I∗ (2.26c) If physical quantities are taken to be measurable properties of physical objects, occurrences and states from which useful sums and differences can be formed, the following then applies: Physical quantity = numerical value × unit Theoretical background 33 2.7.1.2 Relative quantities On the contrary, the unit of a relative quantity is One or 1 p.u. by definition, i.e., Relative quantity = quantity/reference quantity Because the four quantities voltage, current, impedance and power required for system calculations are linked to each other, two reference quantities only are required to specify a relative system of units. Voltage and power are usually chosen for this purpose. This system is called the per-unit system. As reference voltage either the phase-to-phase or the phase-to-earth voltage can be chosen. If the power of 100 MVA is selected as reference quantity, the system is called the p.u.-system on 100 MVAbase. Table 2.2 gives the definitions in the p.u.-system. It should be observed that the phase-to-phase voltage is chosen as reference voltage. In case the phase-to-earth voltage is selected as reference voltage, the current i  has to be calculated as per [28] as indicated by (∗1) in Table 2.2. 2.7.1.3 Semirelative quantities In the semirelative system of units only one quantity is freely chosen as the reference quantity. If the voltage is chosen, the %/MVA system is obtained, which is outstandingly suitable for network calculations because the values of the equipment Table 2.2 Definitions of quantities in physical, relative and semirelative units Ohm-system Physical units %/MVA-system Semirelative units p.u.-system Relative units No reference quantity One reference quantity Two reference quantities Voltage U u= Current I i = I ∗ UB = {I } ∗ {UB } {U } U ∗ 100% = UB {UB } ∗ MVA Impedance Z U {U } ∗1 = UB {UB } i  = I ∗ UB /SB = {I } ∗ {UB }/{SB } ∗ 1 (∗1) remark see text i  = I ∗ UB /SB = {I } √ ∗{ 3UB }/{SB } ∗ 1 z = Z/UB2 = {Z} ∗ 100/{UB2 } z = Z ∗ SB /UB2 = {Z} ∗ {SB }/UB2 ∗ 1 s = S = {S} ∗ 100% ∗ MVA s  = S/SB = {S}/{SB } ∗ 1 ∗ %/MVA Power S applies also to P and Q u = 34 Short-circuit currents can be calculated very easily. Table 2.2 gives the definitions for the %/MVA-system. The reference voltage UB in the %/MVA-system should be equal to the rated voltage of equipment Ur or to the nominal system voltage Un , i.e., it should be a phase-to-phase voltage. The impedances or reactance of electrical equipment are determined from the data of the respective rating plate (name plate) or from geometrical dimensions. The reactance, resistance or impedance should generally be calculated based on the nominal apparent power or on the nominal voltage of the system in which the equipment is used. Conversion between the different unit systems is made using the data in Table 2.3. 2.7.2 Correction factor using %/MVA- or p.u.-system In case the nominal voltage of the system is unequal to the rated voltages of the equipment connected to this system (most often the case with transformers) a correction factor for the impedances must be applied [33]. The derivation of the correction factor is explained based on Figure 2.16. Q ZB Figure 2.16 Ti T2 T1 Un Equivalent circuit diagram of a power system with different voltage levels The impedance correction factor KB for equipment B is calculated by  2  UrT1E UrT2E UrT3E UrB 2 ∗ ∗ ∗ ··· ∗ KB = UrT1A UrT2A UrT3A Un (2.27) where UrT.. are the rated voltages of the transformers at side A or E, UrB the rated voltage of the equipment B and, Un the nominal system voltage at short-circuit location. The impedance correction factor while using the %/MVA- or the p.u.-system must be applied for any equipment except power station units for which special correction factors (see Table 3.6) are valid. 2.8 Examples 2.8.1 Vector diagram and system of symmetrical components The voltages U R , U Y and U B are measured in a power system with nominal voltage Un = 10 kV. 0 U R = 6.64 kV ∗ ej 0 ; 0 U Y = 6.64 kV ∗ ej 250 ; U B = 6.64 kV ∗ ej 110 0 Table 2.3 Conversion of quantities between %/MVA-system, -system and p.u.-system (100 MVA-base) %/MVA-system → -system -system → %/MVA-system -system → p.u.-system (100 MVA) %/MVA-system → p.u.-system (100 MVA) U u 1 UB = ∗ ∗ kV % 100 kV u U 1 = ∗ 100 ∗ % kV UB /kV u U 1 = ∗ p.u. kV UB /kV u u 1 = ∗ p.u. % 100 i 1 I = ∗ kA MVA UB /kV i I UB = ∗ MVA kA kV i I UB 1 = ∗ ∗ p.u. kA kV SB /MVA i i = p.u. MVA Z 100 z = ∗ %/MVA  (UB /kV)2 Z SB 1 z = ∗ ∗ p.u.  MVA (UB /kV)2 z 1 z = ∗ p.u. %/MVA SB /MVA s S = ∗ 100 %MVA MVA s S 1 = ∗ p.u. MVA SB /MVA s s 0.01 = ∗ p.u. %MVA SB /MVA z 1 Z = ∗ ∗  %/MVA 100 s 1 S = ∗ MVA %MVA 100  UB 2 kV 36 Short-circuit currents The voltages in the system of symmetrical components U 0 , U 1 and U 2 have to be calculated by using the transformation equations. The individual voltages in units of kV are obtained by using Equation (2.10). The voltage in the zero-sequence component is U0 = 1 3 ∗ (U R + U Y + U B ) U0 = 1 3 ∗ (6.64 ∗ ej 0 + 6.64 ∗ ej 250 + 6.64 ∗ ej 110 ) 0 0 0 U 0 = 13 [(6.64 + 6.64 ∗ cos 2500 + 6.64 ∗ cos 1100 ) + j (6.64 ∗ sin 00 + 6.64 ∗ sin 2500 + 6.64 ∗ sin 1100 )] U 0 = 13 [(6.64 − 6.64 ∗ 0.342 − 6.64 ∗ 0.342) + j (6.64 ∗ 0 − 6.64 ∗ 0.94 + 6.64 ∗ 0.94)] U 0 = (0.699 + j 0.0)kV The voltage in the positive-sequence component is U1 = 1 3 ∗ (U R + a ∗ U Y + a 2 ∗ U B ) U1 = 1 3 ∗ (6.64 ∗ ej 0 + ej 120 ∗ 6.64 ∗ ej 250 + ej 240 ∗ 6.64 ∗ ej 110 ) U1 = 1 3 ∗ (6.64 ∗ ej 0 + 6.64 ∗ ej 370 + 6.64 ∗ ej 350 ) 0 0 0 0 0 0 0 0 U 1 = 13 [(6.64 + 6.64 ∗ cos 3700 + 6.64 ∗ cos 3500 ) + j (6.64 ∗ sin 00 + 6.64 ∗ sin 3700 + 6.64 ∗ sin 3500 )] U 1 = 13 [(6.64 + 6.64 ∗ 0.985 + 6.64 ∗ 0.985) + j (6.64 ∗ 0 + 6.64 ∗ 0.174 − 6.64 ∗ 0.174)] U 1 = (6.57 + j 0.0) kV The voltage in the negative-sequence component is U2 = 1 3 ∗ (U R + a 2 ∗ U Y + a ∗ U B ) U2 = 1 3 ∗ (6.64 ∗ ej 0 + ej 240 ∗ 6.64 ∗ ej 250 + ej 120 ∗ 6.64 ∗ ej 110 ) 0 0 0 0 0 Theoretical background U2 = 1 3 0 0 37 0 ∗ (6.64 ∗ ej 0 + 6.64 ∗ ej 490 + 6.64 ∗ ej 230 ) U 2 = 13 [(6.64 + 6.64 ∗ cos 4900 + 6.64 ∗ cos 2300 ) + j (6.64 ∗ sin 00 + 6.64 ∗ sin 4900 + 6.64 ∗ sin 2300 )] U 2 = 13 [(6.64 − 6.64 ∗ 0.643 − 6.64 ∗ 0.643) + j (6.64 ∗ 0 + 6.64 ∗ 0.766 − 6.64 ∗ 0.766)] U 2 = (−0.633 + j 0.0) kV The voltages in the system of symmetrical components can be obtained by graphical construction as well as outlined in Figure 2.17. The voltages are assumed to have the same value and phase displacement as mentioned above. 2.8.2 Calculation of impedances of a three-winding transformer in %/MVA The impedances of a three-winding transformer are calculated in units of %/MVA by using the Equations (2.19). The data as mentioned below are taken from the name-plate: Rated voltages Rated apparent power Rated impedance voltage UrHV /UrMV /UrTLV = 110 kV/30 kV/10 kV SrHV = 30 MVA; SrMV = 20 MVA; SrLV = 10 MVA ukrHVMV = 10%; ukrHVLV = 4.5%; ukrMVLV = 10.2% It should be noted that the rated apparent power Sr as per above indicates the apparent power of the individual winding. The maximal permissible apparent power to be transferred between the windings involved for measurement of the impedance voltage had to be taken for the calculation of impedances, i.e., SrHVMV = MAX{SrHV ; SrMV } = 20 MVA. The impedance of the high-voltage winding is calculated by  ukHVLV ukMVLV ukHVMV + − XTHV = 0.5 ∗ SrTHVMV SrTHVLV SrTMVLV XTHV = 0.5 ∗  4.5% 10.2% 10% + − 20 MVA 10 MVA 10 MVA XTHV = −0.035 % MVA 38 Short-circuit currents The impedance of the medium-voltage winding is calculated by  ukHVMV ukHVLV ukMVLV + − XTMV = 0.5 ∗ SrTMVLV SrTHVMV SrTHVLV XTMV = 0.5 ∗  XTMV = 0.535 10.2% 10% 4.5% + − 10 MVA 20 MVA 10 MVA % MVA + Re (a) UR + Im UB UY + Re (b) UY UR UB 3 · U0 + Im UB Figure 2.17 UY Graphical construction of voltages in the system of symmetrical components: (a) vector diagram RYB, (b) vector diagram of voltage in the zero-sequence component, (c) vector diagram of voltage in the positive-sequence component and (d) vector diagram of voltage in the negative-sequence component Theoretical background + Re (c) 1 3 a2 ·UB 1 3 a ·UY 1 3 + Im UR U1 ·UR UB UY + Re (d) a2 ·UY UR a ·UB + Im UB Figure 2.17 3 · U2 UY Continued The impedance of the low-voltage winding is calculated by  ukHVLV ukMVLV ukHVMV XTLV = 0.5 ∗ + − SrTHVLV SrTMVLV SrTHVMV XTLV = 0.5 ∗  XTLV = 0.485 10.2% 10% 4.5% + − 10 MVA 10 MVA 20 MVA % MVA 39 40 Short-circuit currents It should be noted that the negative value of XTHV shall not be interpreted to have a physical meaning. The model (see Table 3.4) describes the performance of the threewinding transformer at the connection point HV, MV and LV only. The impedance between any two connection points appears physically correct with a positive value. 2.8.3 Conversion of impedances (; %/MVA; p.u.) Impedance values shall be converted from one unit system into the other unit systems (%/MVA-system and p.u.-system on 100 MVA-base) by using equations as per Tables 2.2 and 2.3. • Overhead line Z = (6.2 + j 53.4)  at Un = 380 kV The impedance in the %/MVA-system is calculated by z = (6.2 + j 53.4)  ∗ % 100% = (0.0043 + 0.037) (380 kV)2 MVA The impedance in the p.u.-system on 100 MVA-base is calculated by z = (6.2 + j 53.4)  ∗ 100 MVA = (0.0043 + 0.037) p.u. (380 kV)2 • Apparent power of a transformer S = (1.22 + j 300) MVA The apparent power in the %/MVA-system is calculated by s = (1.22 + j 300) MVA ∗ 100% = (122 + j 30000)%/MVA The apparent power in the p.u.-system on 100 MVA-base is calculated by s = (1.22 + j 300) MVA = (0.0122 + j 3) p.u. 100 MVA • Voltage drop U = 12.5 kV in a 132 kV-system The voltage drop in the %/MVA-system is calculated by 100% = 9.47% 132 kV u = 12.5 kV ∗ The voltage drop in the p.u.-system on 100 MVA-base is calculated by u = 12.5 kV ∗ 1 = 0.0947 p.u. 132 kV • Rated current of a 320 MVA-transformer on 115 kV-side Ir = 1.607 kA The current in the %/MVA-system is calculated by ir = 1.607 kA ∗ 115 kV = 184.81 MVA The current in the p.u.-system on 100 MVA-base is calculated by ir = 1.607 kA ∗ 115 kV = 0.185 p.u. 100 MVA Theoretical background 41 2.8.4 Impedances in %/MVA-system based on measurement A simplified example for the application of the system of symmetrical components in representing electrical equipment is outlined in Figure 2.18 by using a short element of an overhead line in accordance to Figure 2.4. The impedance matrix (RYB-system) is thus obtained ⎤ ⎡ jXM R + jX jXM ⎥ ⎢ R + jX jXM ⎦ ZRYB = ⎣ jXM (2.28) jXM jXM R + jX where R is the resistance of the line, X the reactance of the line and XM the mutual reactance between the individual phases. IRYB R jX R jX R jX jXM B Y R URYB Figure 2.18 Simplified equivalent circuit diagram in RYB-components Voltages at the individual components R, Y and B are obtained from the current and the impedance by Ohm’s law. The voltage of phase R (component R) is given as follows: U R = (R + jX) ∗ I R + jXM ∗ I Y + jXM ∗ I B (2.29) and depends on the currents of all three phases (components) I R , I Y and I B . Using the system of symmetrical components, see Equation (2.18), the impedance matrix is simplified in such a way that the three components are decoupled from each other in the following manner: Z012 ⎤ 0 0 R + j (X + 2XM ) ⎦ 0 R + j (X − XM ) 0 =⎣ 0 0 R + j (X − XM ) ⎡ (2.30) The equivalent circuit diagram in the system of symmetrical components is outlined in Figure 2.19. 42 Short-circuit currents I1 R j(X – XM) U1 01 I2 R j(X – XM) U2 02 I0 R j(X + 2XM) U0 00 Figure 2.19 Equivalent circuit diagram in the system of symmetrical components The voltage U 1 of the component 1 (positive-sequence component) is given as below: U 1 = (R + j (X − XM )) ∗ I 1 (2.31a) and depends only on the current I 1 of the same component. Impedance of the components 1 and 2 (positive- and negative-sequence components) is identical. Voltage of the negative-sequence system therefore is given by U 2 = (R + j (X − XM )) ∗ I 2 (2.31b) The impedance of the component 0 (zero-sequence component) is different from the others and the voltage in the zero-sequence component is given by U 0 = (R + j (X + 2XM )) ∗ I 0 (2.31c) 2.8.5 Representation of a line in the RYB-system and in the system of symmetrical components Overhead lines are represented in the RYB-system by lumped elements, indicating the inductive and capacitive coupling as well as the impedance of earth return path. The equivalent circuit diagram of an infinitesimal small section of a line is outlined in Figure 2.20. The representation in the system of symmetrical components (012-system) can either be done by transformation of the individual elements using the transformation Theoretical background X R ~ XM CL CE B EB Y ~ ~ EY R ER Figure 2.20 43 XE RE E Equivalent circuit diagram of an overhead line of infinitesimal length with earth return in RYB-system (a) E1 R X –XM 3CL CE C1 = 3CL + CE 01 (b) R X –XM 3CL CE 02 (c) R 2XM X C0 = CE 3XE 3RE 00 Figure 2.21 Equivalent circuit diagram of an overhead line of infinitesimal length with earth return in 012-system. (a) Positive-sequence component, (b) negative-sequence component and (c) zero-sequence component matrix as per Equations (2.18) or by measurement according to the procedure as explained in Section 2.3.4. The line is represented in the system of symmetrical components as outlined in Figure 2.21. The reactance XE and resistance RE of the earth return path appear with its threefold value in the zero-sequence component, as the current through the neutral is three-times the phase current during the measurement of zero-sequence impedance. The capacitances between the phases CL are represented with three times its capacitance in the positive- and negative-sequence component, as they appear in the RYB-system as delta-connected and have to be transferred to 44 Short-circuit currents a star-connection for representation in the 012-system. The capacitance line-to-earth CE is represented in the three components with the same value. Please observe that the mutual reactance XM appears with different values in the positive- (negative-) and zero-sequence component as outlined in Section 2.3.3. The negative value of the reactance in the positive-, respectively, negative-sequence system has no physical meaning, as the total of the mutual reactance XM and the self-reactance X still remains positive and therefore physically correct. The equivalent voltage source E 1 , which is the internal voltage of a generator, is only present in the positive-sequence component as the symmetrical operation of the system is represented by this component. Chapter 3 Calculation of impedance of electrical equipment 3.1 General In general, equipment in power systems are represented by equivalent circuits, which are designed for the individual tasks of power system analysis, e.g., for the calculation of no-load current and the no-load reactive power of a transformer, the no-load equivalent circuit is sufficient. Regarding the calculation of short-circuits, voltage drops and load characteristic a different equivalent circuit is required. The individual components of the equivalent circuits are resistance, inductive and capacitive reactance (reactor and capacitor), voltage source and ideal transformer. Voltage and currents of the individual components and of the equivalent circuit are interlaced by Ohm’s law, which is valid for the three-phase system (RYB-system) as well as for the system of symmetrical components (012-system). A detailed deduction of the mathematical methods and equations is not given within the context of this section of the book, but only the final equations are quoted. For further reading, reference is made to [1,13]. 3.2 Equipment in a.c. systems 3.2.1 General Impedances of equipment are calculated based on name plate data, from manufacturer’s data or from geometrical arrangement. For the calculation of impedances of generators, power plants, step-up and step-down transformers, correction factors are necessary. The calculation equations as per Tables 3.1–3.11 are given in the Ohm-system only. For conversion to %/MVA-system, respectively, p.u.-system Tables 2.2 and 2.3 can be used. If not marked by index ‘1’, e.g., Z 1Q , in a different way, impedances are given for the positive-sequence component. The impedance in the zero-sequence system is marked with index ‘0’, e.g., Z 0Q . 3.2.2 Impedance calculation Table 3.1 Impedance of system feeder, equivalent circuit diagram, calculation equations and remarks Figure Symbol RQ Impedance Remarks Positive-sequence system 2 c ∗ UnQ Z1Q =  SkQ c  Ik1Q  Ik3Q  SkQ UnQ c ∗ UnQ Z1Q = √  3 ∗ Ik3Q XQ X1Q = 1 + (R1Q /X1Q )2 Zero-sequence component E 01 Equivalent circuit diagram Z1Q  Ik3Q Z0Q = 3 ∗ Z1Q ∗  − 2 ∗ Z1Q Ik1Q Voltage factor according to Table 4.1 Initial short-circuit current (single-phase short-circuit) Initial short-circuit current (three-phase short-circuit) Initial short-circuit power (three-phase short-circuit) Nominal system voltage at connection point Assumptions for resistance: • RQ ≈ 0 if UnQ ≥ 35 kV; system with overhead transmission lines • RQ = 0.1XQ respectively XQ = 0.995ZQ • The impedance in the zero-sequence component normally is given as a ratio of the impedance in the positive-sequence component. If the single-phase short-circuit current from the system feeder is known, the zero-sequence impedance can be calculated. • Reference Item 3.2 of IEC 60909 Table 3.2 Impedance of two-winding transformer, equivalent circuit diagram, calculation equations and remarks Figure Impedance HV LV ZT = RT = Symbol RT = HV RT XT LV⬘ 01 Equivalent circuit diagram Remarks 2 ukr ∗ UrT ∗ KT 100% ∗ SrT 2 uRr ∗ UrT ∗ KT 100% ∗ SrT PkrT 2 3 ∗ IrT ∗ KT XT = ZT2 − RT2 Correction factor KT : UnQ KT = Ub max cmax ∗ 1 + xT (Ib max T /IrT ) sin ϕbT Approximation: KT = 0.95 ∗ cmax 1 + 0.6xT ukr UrT SrT Impedance voltage Rated voltage (HV- or LV-side) Rated apparent power cmax Ib max T IrT PkrT uRr Ub max UnQ ϕbT Voltage factor according to Table 4.1 at LV-side Maximal current prior to short-circuit Rated current (HV- or LV-side) Ohmique losses Ohmique part of impedance voltage Maximal voltage prior to short-circuit Nominal system voltage Phase angle of current prior to short-circuit – Transformer with high rated power: XT ≈ ZT – Correction factor for positive-, negative- and zero-sequence component [35] – Impedances as per this table are related to HV-side – The impedance in the zero-sequence component can either be given as a ratio of the impedance in the positive-sequence component (see Chapter 13) or can be calculated from the impedance voltage and the losses in the zero-sequence component. – The impedance in the zero-sequence component depends on the handling of transformer neutral, see Table 3.6 – Reference Item 3.3.1 of IEC 60909 Table 3.3 Impedance of three-winding transformer, equivalent circuit diagram, calculation equations and remarks Figure Impedance LV |Z THVMV | = ukrHVMV ∗ MV HV |Z THVLV | = ukrHVLV ∗ Symbol |Z TLVMV | = ukrLVMV ∗ ∗K SrtHVMV 2 UrTHV SrtHVLV ∗K 2 UrTHV SrtHVMV ∗K ZTMV = 0.5 ∗ (Z TLVMV + Z THVMV −Z THVLV ) ∗ KTMV ZTLV = 0.5 ∗ (Z THVLV + Z TLVMV −Z THVMV ) ∗ KTLV RTLV XTLV HV MV⬘ XTHV 2 UrTHV ZTHV = 0.5 ∗ (Z THVMV + Z THVLV −Z TLVMV ) ∗ KTHV LV⬘ RTHV Remarks XTMV RTMV 01 Equivalent circuit diagram 2 uRr ∗ UrT ∗ KT 100% ∗ SrT P RT = krT2 ∗ KT∗∗ 3 ∗ IrT RT = XT = ZT2 − RT2 Voltage factor according to Table 4.1 IrT Rated current PkrT Ohmique losses SrT Rated apparent power UrT Rated voltage uRr Ohmique part of impedance voltage ukr Impedance voltage – HV, MV, LV related to voltage levels – Calculation of RT and XT similar to ZT for HV, MV and LV – Transformers with high rating: XT ≈ ZT – Correction factor for positive, negative and zero-sequence component [35] – Impedances as per this table are related to HV-side – Correction factor K not defined herewith – Correction factor KT∗∗ equal KTHV ; KTMV ; KTLV cmax Correction factor KT : cmax KTHVMV = 0.95 1 + 0.6xTHVMV cmax KTHVLV = 0.95 1 + 0.6xTHVLV cmax KTMVLV = 0.95 1 + 0.6xTMVLV – The impedance in the zero-sequence component can either be given as a ratio of the impedance in the positive-sequence component (see Chapter 13) or can be calculated from the impedance voltage and the losses in the zero-sequence component. – The impedance in the zero-sequence component depends on the handling of transformer neutral, see Table 3.4 – Reference Item 3.3.2 of IEC 60909 50 Short-circuit currents Table 3.4 Equivalent circuit diagram of two- and three-winding transformers in the positive- and zero-sequence component Type of transformer Equivalent diagram Equivalent diagram in system of symmetrical components (any vector group) in RYB-system Positive-sequence component Zero-sequence component 1 2 1 2 1 X1 1 X1 2 1 X01 1 X01 2 YNy 01 ZS YNd 1 YNy + d 1 1 X1 2 ZS 2 3ZS 01 ZS ZNy; ZNd 2 00 2 1 2 X01 3ZS 01 2 1 X1 ZS 3 X3 3 X2 2 1 3ZS X01 3 2 1 X1 ZS1 ZS2 3 X3 3 1 ES 2 1 X1 2 00 3 X2 2 1 3ZS1 X01 X02 2 X03 3ZS2(U1/U2)2 00 01 3 X3 X02 X03 01 YNyn + d 00 or 3 1 00 3 X2 2 XL 01 1 ES X01 X02 2 X03 3XL(U1/U2)2 00 3.3 Equipment in d.c. systems 3.3.1 General For the calculation of short-circuit currents in d.c. systems, the parameters of equipment contributing to the short-circuit current, i.e., capacitor, battery, rectifier and d.c. motor need to be known besides the parameter of conductors. The calculation equations as per Tables 3.12 to 3.16 are given in the Ohm-system only. For conversion to %/MVA system, p.u. system, respectively, Tables 2.2 and 2.3 can be used. Tables 3.12 to 3.16 mention the term ‘common branch’. The common branch in d.c. systems is the branch (conductor) leading parts of the short-circuit current from several different sources (capacitor, battery, rectifier and d.c. motor) according to IEC 61660-1. Table 3.5 Impedance of synchronous generator, equivalent circuit diagram, calculation equations and remarks Figure Impedance GS 3~ X1G = 2 xd ∗ UrG 100% ∗ SrG Remarks ∗ KG Salient pole generators: X2G = 0.5 ∗ (Xd + Xq ) ∗ KG Symbol RGf Zero-sequence component X0G ≈ (0.4–0.8)Xd ∗ KG XG Correction factor KG : UnQ cmax KG = ∗ UrG (1 + pG ) 1 + xd ∗ sin ϕrG EG 01 Equivalent circuit diagram cmax pG SrG UrG xd ϕrG Voltage factor according to Table 4.1 Voltage control range: UrG = const ⇒ pG = 0 Rated apparent power Rated voltage Subtransient reactance Phase angle between UrG and IrG Fictitious resistance of stator RGf (for peak s.-c. current) HV: RGf = 0.05 ∗ XG : SrG ≥ 100 MVA RGf = 0.07 ∗ XG : SrG < 100 MVA LV: RGf = 0.15 ∗ XG – Correction factor for positive-, negative- and zero-sequence component – Synchronous motors identical to synchronous generators – Calculation of decaying d.c. component with real resistance of stator – Impedance in the zero-sequence component depends on the type of winding of the generator – Reference Item 3.6 of IEC 60909 Table 3.6 Impedance of power-station unit, equivalent circuit diagram, calculation equations and remarks Figure G Impedance Remarks 2 +Z Z KW = (Z G ∗ trT THV ) ∗ KKWi UnG Nominal system voltage T Correction factor KKWi with tap-changer: GS 3~ KKWs = trT Symbol (RGf + jXG)t 2rT RT (UrG (1 + pG ))2 U2 cmax ∗ ∗ rTLV  − x | ∗ sin ϕ 2 1 + |x UrTHV T rG d Correction factor KKWi without tap-changer: UnQ KKWo = UrG (1 + pG ) cmax UrTLV ∗ (1 ± pT ) ∗ ∗ UrTHV 1 + xd sin ϕrG XT EGitrT 01 Equivalent circuit diagram 2 UnQ Generator: pG Control range of voltage: UrG = const ⇒ pG = 0 UrG Rated voltage xd Subtransient reactance ZG Impedance according to Table 3.5 ϕrG Phase angle between UrG and IrG Unit transformer: cmax Voltage factor according to Table 4.1 pT Permanent setting of winding trT Rated transformation ratio UrTLV Rated voltage LV-side UrTHV Rated voltage HV-side xT Reactance (equal impedance voltage) ZT Impedance according to Table 3.2 (two-winding transformer) • Correction factor for positive-, negative- and zero-sequence component [37] • Reference Item 3.7 of IEC 60909 Table 3.7 Impedance of overhead line (single-circuit), equivalent circuit diagram, calculation equations and remarks Figure Impedance  = R1L Symbol R⬘1L·  = RLδ X⬘1L· 01 Equivalent circuit diagram Remarks n  R1L Geometric mean distance between conductors dRY ; dYB ; dBR Distances of conductors R, Y, B Number of conductors per phase Resistance per length (pos. seq.) r rt qn  X1L α δ ρ ρE μ0 μr Radius of conductor Radius of conductor arrangement per phase Nominal cross-section of conductor Reactance per length (pos. seq.) Temperature coefficient α = 0.004 K −1 Equivalent depth of earth conductor Resistivity in mm2 /m Specific earth resistance Permeability of vacuum Relative permeability D ρ n ∗ qn  (1 + α ∗ (δ − 20◦ C)) ∗ RL20 n Single-circuitoverhead line:  = ω μ0 ln D + μr X1L 2π rB 4n Zero-sequence component: R  = 1L + 3ω μ0 R0L n 8 δ μr μ0  3 ln 3 + X0L = ω 2 2π 4n rB ∗ D with D= rB = √ 3 n Reactance: dRY ∗ dYB ∗ dBR (n−1) n ∗ r ∗ rt 1.85 δ= √ μ0 ∗ ω/ρE – – – Calculation from geometrical arrangement, see Section 13.1.4 Specific earth resistance ρE = 30 m (swamp soil)–3000 m (stone) Reference Item 3.4 of IEC 60909 Note: Impedances of other arrangements of overhead lines needed for special technical problems are dealt with in Section 12.1 and Section 13.1.4. Impedances of cables can be calculated from geometrical data only in a very time consuming manner. It is recommended to use manufacturer’s data. Tables and diagrams can be found in [1,2,8,9]. Table 3.8 Impedance of short-circuit limiting reactor, equivalent circuit diagram, calculation equations and remarks Figure Impedance ZD = ukr Un ∗√ 100% 3 ∗ IrD √ SrD = 3 ∗ Un ∗ IrD Symbol ZD ≈ XD Remarks IrD rated current SrD Un ukr Rated apparent power Nominal system voltage Rated voltage drop (impedance voltage) – 01 Equivalent circuit diagram – – – Impedances in positive-, negativeand zero-sequence component identical in case of symmetrical construction RD ≈ 0 Impedance in the zero-sequence component equal to the impedance in the positive-sequence component in case three single-phase reactors are used Reference Item 3.5 of IEC 60909 Table 3.9 Impedance of asynchronous motor, equivalent circuit diagram, calculation equations and remarks Figure Impedance ZM = M 3~ XM = Symbol RM SrM = XM Remarks 2 IrM UrM ∗ IanM SrM ZM 1 + (RM /XM )2 PrM ηrM ∗ cos ϕrM IanM Locked rotor current IrM Rated current PrM Rated active power SrM Rated apparent power ϕrM Phase angle at rated power ηrM Rated power factor MV: RM = 0.1 ∗ XM with PrMp ≥ 1 MW RM = 0.15 ∗ XM with PrMp < 1 MW PrMp Rated active power per pole pair LV: RM = 0.42 ∗ XM including connection cable E 01 Equivalent circuit diagram – – Asynchronous motors are normally operated with isolated neutrals, zero-sequence impedance therefore can be neglected Reference Item 3.8 of IEC 60909 Table 3.10 Impedance of static converter fed drive, equivalent circuit diagram, calculation equations and remarks Figure Impedance ZM = 2 IrM UrM ∗ IanM SrM RM = 0.1 XM Symbol RM XM Remarks IanM IrM SrM Locked rotor current Rated current Rated apparent power UrM Rated voltage – – – – E 01 Equivalent circuit diagram IanM /IrM = 3 Only for rectifiers, able to transfer energy for deceleration during the duration of short-circuit Static converters for photovoltaic generators or fuel cells contribute to short-circuit currents only with their rated current Reference Item 3.9 of IEC 60909 Table 3.11 Impedance of system load, equivalent circuit diagram, calculation equations and remarks Figure Impedance ZL 01 XL 01 RL 01 XC 01 Symbol, Equivalent circuit diagram ZL = 2 UrL SrL RL = 2 UrL PrL U2 ωLL = rL QrL U2 1 = rL ωCL QrL Remarks PrL QrL SrL UrL Rated active power Rated reactive power Rated apparent power Rated voltage In case UrL is unknown, the nominal system voltage Un is to be used • Reference Item 3.10 of IEC 60909 • 3.3.2 Impedance calculation Table 3.12 Impedance of a conductor, equivalent circuit diagram, calculation equations and remarks Figure Impedance RL = ρ qn  = (1 + α ∗ (δ − 20◦ C)) ∗ R  RLδ L20 Symbol Loop by single cables R⬘L · L⬘ · R⬘J L =  a  μ0  ∗ 0.25 + ln π r Loop by busbars L = Equivalent circuit diagram   a μ0 ∗ 1.5 + ln π d +b Resistance of bolted joint: Conductor qn d Conductor joint 14 ∗ ρ ∗ d RJ = qn Remarks a b d RJ RL RL20 RLδ r qn α δ ρ μ0 Distance of conductors Height of conductor (busbar) Thickness of conductor Resistance of bolted joint Specific resistance Resistance at 20◦ C Resistance at temperature δ Radius of conductor Cross-section of conductor Temperature coefficient (for Al, Cu) α = 0.004 K −1 Temperature in ◦ C Resistivity in mm2 /m Permeability RJ for calculation of minimal s.-c. currents only – Calculation of L for simple arrangement only – Reference Item 2.3 of IEC 61660-1 – Table 3.13 Impedance of capacitor, equivalent circuit diagram, calculation equations and remarks Figure RCBr ; LCBr RCL Remarks RCBr = RC + RCL + RY LCBr = LCL + LY Conductor for connection: RCL ; LCL Resistance; inductance Approximation: C ≈ 1.2 ∗ Ca.c. Symbol RC Impedance LCL RY LY Common branch: RY ; LY Resistance; inductance Capacitor: C d.c.-capacitance Ca.c. a.c.-capacitance at 100 Hz RC EC Equivalent circuit diagram – Equivalent series d.c. resistance. If unknown: maximal a.c. resistance Reference Item 2.6 of IEC 61660-1 Table 3.14 Impedance of battery, equivalent circuit diagram, calculation equations and remarks Figure RBBr; LBBr LB RBL LBL EB Equivalent circuit diagram Remarks RBBr = 0.9 ∗ RB + RBL + RY LBBr = LB + LBL + LY Conductor for connection: RBL ; LBL Resistance; inductance Approximation: RBun = 1.7 ∗ RB LBZ = 0.2 µH EBge = 1.05 ∗ UnB EBun = 0.9 ∗ UnB EBge = 1.05 ∗ UnB Symbol RB Impedance RY LY Common branch: RY ; LY Resistance; inductance Battery: EBge Voltage of charged battery EBun Voltage of discharged battery LBZ Inductance of one cell including connection RB ; LB Resistance; inductance of a charged battery RBun Resistance of discharged battery UnB Nominal voltage of battery Lead-acid battery: UnB = 2.0 V per cell – Reference Item 2.5 of IEC 61660-1 Table 3.15 Impedance of rectifier, equivalent circuit diagram, calculation equations and remarks Figure Impedance Remarks ac-side RN = RQ + RP + RT + RD Indices for ac-side: D Commutating reactor N Total Q System feeder P Connection at secondary side of transformer – ZQmin (RQ and XQ ) for calculation of max. short-circuit current – ZQmax (RQ and XQ ) for calculation of min. short-circuit current XN = XQ + XP + XT + XD Symbol RDBr ; LDBr R Q ; XQ RS RQ ; XQ Q RP ; XP RT ; XT LS RL LL RY LY RD ; XD Equivalent circuit diagram dc-side RDBr = RS + RL + RY LDBr = LS + LL + LY Indices for dc-side: L Power supply cable S DC saturated smoothing reactor Coupling branch: LS saturated inductance RY ; LY Resistance; inductance – Reference Item 2.4 of IEC 61660-1 Table 3.16 Impedance of d.c. motor with independent excitation, equivalent circuit diagram, calculation equations and remarks Figure M Motor Symbol RMBr; LMBr; M F RF LF J M RM n EF Equivalent circuit diagram EM LM RML LML RY LY Impedance Remarks RMBr = RM + RML + RY LMBr = LM + LML + LY Conductor for connection: RML Resistance LML Inductance Time constants: LMZw τM = Common branch: RMZw Resistance R 2π ∗ n0 ∗ J ∗ RMBr ∗ IrM Y LY inductance τMec = Mr ∗ UrM Motor: LF Rated current IrM τF = RF J Moment of inertia of whole rotating part Mr Rated torque n0 No-load speed RM ; LM Resistance; inductance of armature circuit including brushes UrM Rated voltage τF Field circuit time constant τM Time constant of armature circuit up to s.-c. location τMec Mechanical time constant – Reference Item 2.7 of IEC 61660-1 63 Calculation of impedance of electrical equipment 3.4 Examples for calculation 3.4.1 a.c. equipment The impedance (resistance and reactance) of equipment in a.c. three-phase power systems has to be calculated based on the data as below. Results are summarised in Table 3.17. Power system feeder Q: Two-winding transformer: Three-winding transformer:  = 3000 MVA; U SkQ nQ = 110 kV SrT = 70 MVA; UrTHV /UrTLV = 115 kV/10.5 kV; ukr = 12%; uRr = 0.5% Synchronous machine: SrG = 70 MVA; UrG = 10.5 kV; cos ϕrG = 0.9; xd = 17%; pG = ±10% SrG = 70 MVA; UrG = 10.5 kV; xd = 17%; pG = ±10% SrT = 70 MVA; UrTHV /UrTLV = 115 kV/10.5 kV; ukr = 12%; URr = 0.5%; without tap-changer Power plant consisting of synchronous machine and two-winding transformer: Overhead transmission line: s.-c. limiting reactor: Asynchronous motor: Rectifier: System load: Table 3.17 Equipment System feeder Two-winding transformer UrT = 110 kV/30 kV/10 kV; SrT = 30 MVA/20 MVA/10 MVA ukrHVMV = 10%; ukrHVLV = 4.5%; ukrMVLV = 10.2% uRrHVMV = 0.5%; uRrHVLV = 0.6%; uRrMVLV = 0.65% Al/St 240/40; r = 10.9 mm; Line length 10 km Flat arrangement, distance between phase wires 4 m ukr = 6%; IrD = 630 A; Un = 10 kV PrM = 1.2 MW; UrM = 6 kV; cos ϕrM = 0.84; ηrM = 0.93; Ian /IrM = 5.6; 2 pairs of poles SrM = 4 MVA; UrM = 6.2 kV SrL = 6 MVA; cos ϕL = 0.87; Un = 10 kV Results of calculation of impedance in three-phase a.c. equipment Z () 4.437 R () 0.441 X () 4.414 22.76 0.945 22.74 22.19 0.921 22.17 Remark Tab. RQ /XQ not defined XQ ≈ 0.995 × ZQ 3.1 Without correction factor Impedance related to 110 kV KT = 0.975 Impedance related to 110 kV 3.2 64 Short-circuit currents Table 3.17 Continued Equipment Z () R () X () Remark Three-winding transformer −3.24 62.89 58.65 1.31 1.67 6.08 −2.97 62.87 58.33 Impedance related to 110 kV 3.3 including correction factors KT = 0.986–1.018–0.985 Values from top: HV ∗ MV ∗ LV Synchronous machine 0.268 0.238 0.019 0.017 0.267 Without correction factor 0.237 KG = 0.887; UnQ = 10 kV Tables 3.5 KKWo = 0.891; UnQ = 110 kV 3.6 4.01 D = 5.04 m 3.7 0 0.55 XD ≈ ZD 3.8 4.14 0.41 4.12 SrM = 1.53 MVA 3.9 Rectifier 28.83 2.88 28.69 RM /XM = 0.1 3.10 System load 16.67 — 3.11 Power plant 65.14 3.22 54.77 Overhead transmission line 4.19 1.23 s.-c. limiting reactor 0.55 Asynchronous machine 14.5 8.22 3.4.2 d.c. equipment The impedance (resistance and reactance) of equipment in d.c. systems has to be calculated based on the data as below. Results are summarised in Table 3.18. Conductor Busbar arrangement, copper (120 × 10): qn = 1200 mm2 ; with joint: Distance a = 50 mm; Length of line loop 30 m Capacitor: MKP dry-type, self-healing; C = 9000 µF; RC = 0.5 m Connected to short-circuit location with conductor as above, l = 20 m Two bolted joints Battery: Sealed lead-acid-type; 108 cells, each: 150 Ah; UnB = 2.0 V; RB = 0.83 m; LB = 0.21 mH Connected to short-circuit location with conductor as above, l = 15 m Two bolted joints Calculation of impedance of electrical equipment Rectifier: d.c. motor (independent excitation): Table 3.18 65  = 40 MVA; R /X = 0.25 AC-system: UnQ = 600 V; SkQ Q Q Transformer: trT = 600 V/240 V; SrT = 400 kVA; ukrT = 3.5%; PkrT = 4.2 kW Rectifier: IrD = 1.2 kA; commutating reactor: LS = 0.31 µH; RS = 0.91 m Connected to short-circuit location with conductor as above, l = 10 m UrM = 225 V; PrM = 110 kW; IrM = 500 A; RM = 0.043 ; LM = 0.41 mH RF = 9.85 M; LF = 9.97 H Connected to short-circuit location with conductor as above, l = 10 m Results of calculation of impedance of equipment in d.c. installations (without common branch as per IEC 61660-1) Equipment R (m) L Others Remarks Tab. Conductor 926 0.653 µH — 3.12 — — Loop length 60 m Resistance of bolted joint — 218 nH — 218 nH 9000 µF — — 9000 µF 2.16 Capacitor Battery 0.5 309 4.32 313.82 RB = 89.6 LB = 21.6 µH EBge = 226.8 V RBun = 152.4 EBun = 194.4 V 231.5 4.32 325.42 388.22 Rectifier 0.367 1.512 1.879 163.2 nH — 21.76 µH — — — 4.667 µH 4.813 µH 9.48 µH ZQ = 1.51 m ZT = 5.04 m — 3.13 Conductor Two joints Total Voltage of discharged battery e.g., 1.8 V/cell Conductor Two joints Total 3.14 System feeder Transformer Total a.c. system 3.15 66 Short-circuit currents Table 3.18 Equipment Continued R (m) L Others Remarks 0.91 0.31 µH — 154.3 155.21 0.11 µH 0.42 µH — — Commutating reactor Conductor Total d.c. system 0.41 mH 0.11 µH 0.411 mH — d.c. motor 43.3 with 154.3 independent 197.6 excitation Motor Conductor τM = 2.08 ms Total τF = 1.01 s Tab. 3.16 Chapter 4 Calculation of short-circuit current in a.c. three-phase HV-systems 4.1 Types of short-circuits In three-phase a.c. systems it has to be distinguished between different types of short-circuits (s.-c.), as outlined in Figure 4.1. Short-circuit currents can be carried out with different methods and in different details, depending on the available data and the technical needs. IEC 60909-0 calculates characteristic parameters of the short-circuit current, which are necessary for the design of power system equipment. The course of time of short-circuit currents is outlined in Figure 4.2. Generally, one has to distinguish between near-to-generator and far-from-generator short-circuits. A near-to-generator short-circuit exists if the contribution to the short-circuit current of one synchronous generator is greater than twice its rated current, or if the contribution to the short-circuit current of synchronous or asynchronous motors is greater than 5 per cent of the short-circuit current without motors. The analysis of the short-circuit current in the case of near-to-generator shortcircuit as per Figure 4.2(a) indicates two components, besides the decaying d.c. component, a subtransient and a transient decaying a.c. component. The first or subtransient component is determined by the impedance between stator and damping winding, called subtransient reactance Xd . The subtransient component decays with the subtransient time constant T  which is normally in the range of some periods of the system frequency, i.e., T  < 70 ms. The transient component is determined by the reactance between the stator and exciter winding, called transient reactance Xd . The transient component decays with the transient time constant T  , which can last up to 2.2 s for large generators. Finally, the short-circuit current is determined by the saturated synchronous reactance Xd . In the case of a far-from-generator short-circuit as per Figure 4.2(b), the a.c. component remains constant throughout the total time duration of the short-circuit, as the influence of the changing reactance of generators can be neglected. The decaying 68 Short-circuit currents (a) B (b) Y Y R R I ⬙k2 I ⬙k3 B (c) B (d) B Y Y R R I ⬙k2E I ⬙kE2E Figure 4.1 I ⬙k1 Types of short-circuits and short-circuit currents. (a) Three-phase short-circuit, (b) double-phase short-circuit without earth/ground connection, (c) double-phase short-circuit with earth/ground connection and (d) line-to-earth (line-to-ground) short-circuit d.c. component is due to the ohmic-reactive short-circuit impedance and the instant of initiation of the short-circuit. 4.2 Methods of calculation Short-circuit current calculation according to IEC 60909-0 is carried out based on the method of ‘equivalent voltage source at the short-circuit location’, which will be explained with the equivalent circuit diagram of a power system outlined in Figure 4.3. The method is based on the presuppositions as below: • • • • Symmetrical short-circuits are represented by the positive-sequence component; unsymmetrical (unbalanced) short-circuits are represented by connection of positive-, negative- and zero-sequence component as per Table 2.1. Capacitances and parallel admittances of non-rotating load of the positive(and negative-) sequence component are neglected. Capacitances and parallel admittances of the zero-sequence component shall be neglected, except in systems with isolated neutral or with resonance earthing (systems with Petersen coil) as they have an influence on fault currents in power. Impedance of the arc at the short-circuit location is neglected. The type of short-circuit and the system topology remain unchanged during the duration of short-circuit. Calculation of short-circuit current 69 2 2I k⬙ ip (a) A 2 2Ik (b) A 2 2I ⬙k ip 2 2Ik Figure 4.2 Time-course of short-circuit currents. (a) Near-to-generator shortcircuit (according to Figure 12 of IEC 60909:1988), (b) far-fromgenerator short-circuit (according to Figure 1 of IEC 60909:1988). Ik – initial (symmetrical) short-circuit current, ip – peak short-circuit current, Ik – steady-state short-circuit current and A – initial value of the aperiodic component idc • The tap-changers of all transformers are assumed to be in main-position (middle position). • All internal voltages of system feeders, generators √ and motors are short-circuited and an equivalent voltage source with value cUn / 3 is introduced at the shortcircuit location. The voltage factor c shall be selected in accordance with Table 4.1. The voltage factor c takes account of the differences between the voltage at the short-circuit location and the internal voltage of system feeders, motors and generators 70 Short-circuit currents (a) Q T F L k3 S kQ ⬙ (b) RQt XQt XT RT RL XL F F E1 ZB CL 2 CL 2 I ⬙k ZB 01 (c) RQt XQt XT RT Zk RL XL F cUn 3 I ⬙k 01 Figure 4.3 Example for short-circuit current calculation with an equivalent voltage source at s.-c. location. (a) Three-phase a.c. system with three-phase short-circuit, (b) equivalent circuit diagram in 012-system (positivesequence system), (c) equivalent circuit diagram in 012-system with equivalent voltage source due to voltage variations (time and place), operating of transformer tap-changer, etc. Assuming the voltage factor as per Table 4.1 will result in short-circuit currents on the safe side, that are higher than in the real power system, however, avoids an uneconomic high safety margin. 4.3 Calculation of parameters of short-circuit currents 4.3.1 General The calculation of the impedances of power system equipment was explained in Chapter 3. It should be noted that the impedances shall be related to the voltage level of the short-circuit location and that all equipment belonging to the same voltage level shall have the same nominal voltage. The impedances, therefore, have to be calculated Calculation of short-circuit current Table 4.1 71 Voltage factor c according to IEC 60909-0 Nominal system voltage Un LV: 100 V up to 1000 V (inclusive) (IEC 60038, Table I) Voltage tolerance +6% Voltage tolerance +10% MV: >1 kV up to 35 kV (inclusive) (IEC 60038, Table III) HV: >35 kV (IEC 60038, Table IV) Voltage factor c for calculation of Maximal s.-c. current cmax Minimal s.-c. current cmin 1.05 1.10 1.10 0.95 0.95 1.00 1.10 1.00 Remark: cmax Un shall not exceed the highest voltage of equipment Um as per IEC 60071. in relation to the rated apparent power Sr of the equipment itself, respectively to the nominal system voltage Un . In case the %/MVA-system or the p.u.-system is used, attention must be given to deviations of rated votages of the equipment from nominal system voltages, see Section 2.7.2. The presentation within the following sections is closely related to IEC 60909-0. The IEC-document includes items for the calculation of impedances and for the calculation of the short-circuit parameters for balanced and unbalanced short-circuits, both near-to-generator and far-from-generator short-circuits. Calculation of shortcircuit currents during two separate single-phase to earth short-circuits and the partial short-circuit currents flowing through earth are dealt with in IEC 60909-3, which is currently under review. These items are explained in Chapter 7. Depending on the task, the maximal or minimal short-circuit current has to be calculated. The maximal short-circuit current is the main design criteria for the rating of equipment to withstand the effects of short-circuit currents. For the calculation of maximal short-circuit current, the items shall be considered as below: • • • • • • For the equivalent voltage source at the short-circuit location the voltage factor cmax as per Table 4.1 shall be used. National standards can define voltage factors different from those in Table 4.1. Short-circuit impedance of system feeders shall be minimal (ZQmin ), so that the contribution to the short-circuit current is maximal. The contribution of motors has to be assessed and eventually be taken into account, see Section 4.4. Resistance of lines is to be calculated for a temperature of 20◦ C. Operation of power plants and system feeders shall be in such a way that the contribution to short-circuit currents will be maximal. System topology leading to the maximal short-circuit currents shall be taken into account. 72 Short-circuit currents The minimal short-circuit current is needed for the design of protection systems and the minimal setting of protection relays; details of the presuppositions for calculation are dealt with in Section 4.5. 4.3.2 Calculation of short-circuit current parameters according to IEC 60909-0 4.3.2.1 Initial symmetrical short-circuit current Ik The initial symmetrical short-circuit current Ik is calculated for balanced and unbalanced short-circuits based on the equivalent voltage source at the short-circuit location and the short-circuit impedance seen from the short-circuit location, which has to be determined with the system of symmetrical components. The results obtained for the short-circuit currents (and the voltages of the non-faulted phases, if required) in the 012-system have to be transferred back into the RYB-system. The results for the different types of short-circuits are outlined in Table 4.2. Quantities as per Table 4.2: c Un Z1; Z2; Z0 Voltage factor according to Table 4.1 Nominal system voltage Short-circuit impedance in the positive-, negative- and zerosequence component As can be obtained from Table 4.2, the value of the initial short-circuit current depends on the impedances in the positive-, negative- and zero-sequence component. Based on the impedance ratios Z0 /Z1 and Z2 /Z1 , it can be estimated which type of short-circuit will cause the maximal initial short-circuit current. Figure 4.4 outlines the initial short-circuit currents for different types of short-circuits related to the short-circuit current of a three-phase short-circuit in variation of the impedance ratios mentioned above. As the phase angle of the impedances are different in the positive-, negative- and zero-sequence component, the diagram shall only be used for a preliminary estimate. Figure 4.4 can be used as explained below. In the case of a far-from-generator short-circuit, Z1 is equal to Z2 (Z2 /Z1 = 1). The maximal short-circuit current will occur in the case of a three-phase short-circuit if Z1 /Z0 ≤ 1. For ratios Z1 /Z0 > 1, the single-phase short-circuit will result in the highest short-circuit currents. In the case of near-to-generator short-circuits the ratio of negative- to positive-sequence impedance Z2 /Z1 mainly determines which type of short-circuit will cause the maximal short-circuit current. If Z1 /Z0 > 1 the maximal short-circuit current will always occur in the case of a single-phase short-circuit. 4.3.2.2 Short-circuit currents inside power plant When calculating short-circuit currents inside power plants, the short-circuit location itself and the installation of the unit transformer will result in a different Calculation of short-circuit current Table 4.2 73 Equations for the calculation of initial symmetrical short-circuit currents Type of short-circuit Three-phase Double-phase short-circuit without earth connection Double-phase short-circuit with earth connection General Equation Section Remarks IEC 60909-0  = √cUn Ik3 3|Z 1 |  = Ik2 cUn |2Z 1 | √     − 3cUn Z 2    IkE2E =   Z1 Z2 + Z1 Z0 + Z2 Z0    −j cUn (Z 0 − a Z 2 )  Ik2EY =  Z Z +Z Z +Z Z 1 2 1 0 2 0 4.2.1 4.3.1 4.6.1–4.6.3 Short-circuited phases R, Y and B 4.2.2 4.3.2 4.6.4 Short-circuited phases Y and B 4.2.3 4.3.3 4.6.4 Current flowing through earth     Current of phase Y    j cU (Z − a 2 Z )  n   0 2  Ik2EB =   Z1 Z2 + Z1 Z0 + Z2 Z0  Far-from-generator  (Z 1 = Z 2 ) IkE2E = Line-to-earth single-phase short-circuit General Far-from-generator (Z 1 = Z 2 ) √ 3cUn |Z 1 + 2Z 0 |  Ik2EY = cUn |Z 0 /Z 1 − a| |Z 1 + 2Z 0 |  = Ik2EB cUn |Z 0 /Z 1 − a 2 | |Z 1 + 2Z 0 | √ 3cUn  = Ik1 |Z 1 + Z 2 + Z 0 | √ 3cUn  = Ik1 |2Z 1 + Z 0 | Current of phase B Short-circuited phases Y and B 4.2.3 4.3.3 4.6.4 Current flowing through earth Current of phase Y Current of phase B Short-circuited phases Y and B 4.2.4 4.3.4 4.6.4 Short-circuited phase R 74 Short-circuit currents 1.4 kE2E r = 1.2 1.2 k1 1.0 2.5 2.0 0.8 r 1.5 Z Z1/ Z0 1.3 1.2 0.6 k2E 0.4 k3 k2 0.2 1.5 1.3 1.2 r 1.0 0 0 Figure 4.4 0.2 0.4 Z2 / Z1 0.6 0.8 1.0 Estimate of maximal initial short-circuit current for different types of short-circuit and different impedance ratios Z1 /Z0 and Z2 /Z1 . Phase angle of Z 0 , Z 1 and Z 2 assumed to be identical. Parameter r: ratio of asymmetrical short-circuit current to three-phase short-circuit current approach, respectively considerations, concerning the impedances. According to Figure 4.5 different locations have to be considered, that is, • Short-circuit between generator and unit transformer (F1) • Short-circuit at HV-side of auxiliary transformer (F2) • Short-circuit at MV-side of auxiliary transformer (F3) Furthermore, the arrangement of the unit transformer, that is, • Equipped with tap-changer • Without tap-changer has an important influence on the short-circuit currents. The short-circuit current for location F1 between generator and unit transformer, if the unit transformer is equipped with tap-changer, is calculated by   + IkT = Ik = IkG 1 c ∗ UrG 1 ∗ + √ 2 )∗Z |KGs ∗ Z G | |Z TLV + (1/trT 3 Q min | (4.1) Calculation of short-circuit current G GS 3~ 75 T I ⬙kG F1 I ⬙kT trT UnQ I ⬙kEB S ⬙kQ F2 Auxiliary transformer ürE I ⬙kEBt F3 I ⬙kM M 3~ Figure 4.5 Equivalent circuit diagram for the calculation of short-circuit currents inside power plant with the impedance correction factor KGs KGs = cmax 1 + xd ∗ sin ϕrG (4.2) When the unit transformer is not equipped with tap-changer, the short-circuit current is given as   + IkT = Ik = IkG 1 c ∗ UrG 1 ∗ + √ 2 )∗Z |KGo ∗ Z G | |Z TLV + (1/trT 3 Q min | (4.3) with the impedance correction factor KGo KGo = 1 cmax  1 + pG 1 + xd ∗ sin ϕrG (4.4) The short-circuits at the HV-side of the auxiliary transformer at location F2 are given by  = IkEB c ∗ UrG ∗ √ 3 1 1 + 2 )∗Z |KGs ∗ Z G | |KTs ∗ Z TLV + (1/trT Q min | (4.5) 76 Short-circuit currents with impedance correction factor for the generator cmax 1 + xd ∗ sin ϕrG (4.6a) and the unit transformer cmax KTs = 1 + xT ∗ sin ϕrG (4.6b) KGs = If the unit transformer is installed without tap-changer the impedance correction factors are given for the generator KGo = 1 cmax ∗  1 + pG 1 + xd ∗ sin ϕrG (4.7a) and for the unit transformer KTo = 1 cmax ∗ 1 + pG 1 + xT ∗ sin ϕrG (4.7b) which shall be used instead of correction factors KGs and KTs as per Equations (4.6), respectively. The impedance Zrsl Zrsl = 1 1 + 2 )∗Z |KGs ∗ Z G | |KTs ∗ Z TLV + (1/trT Q min | (4.8) including the correction factors is called the coupling impedance. Quantities of Equations (4.1)–(4.8) are ZG Z TLV Z Q min trT UrG c; cmax xT xd pG sin ϕrG Impedance of the generator Impedance of the unit transformer at LV-side (generator voltage) Impedance of the system feeder for maximal short-circuit current Transformation ratio of the unit transformer (trT ≥ 1) Rated voltage of generator Voltage factor as per Table 4.1 Reactance of the transformer in p.u. (impedance voltage) Subtransient reactance of the generator in p.u. Voltage control range of generator in p.u. Power factor of generator at rated operating conditions Other quantities are explained previously. Short-circuits at MV-side of the auxiliary transformer at location F3 or at the  auxiliary busbar are a superposition of the partial short-circuit current IkEBt of the auxiliary transformer related to the voltage level of the short-circuit location and of the contribution of the motors in the auxiliary system to the short-circuit current. In the case of a unit transformer without tap-changer the impedance correction factors KGo and KTo have to be considered accordingly. 77 Calculation of short-circuit current 4.3.2.3 Peak short-circuit current ip Depending on the feeding source of the short-circuit different considerations have to be taken to calculate the peak short-circuit current. Figure 4.6 indicates an equivalent circuit diagram with single-fed short-circuit. The short-circuit impedance is represented by a series connection of the individual impedances. The peak short-circuit current, which is a peak value, can be calculated for the different types of short-circuits based on the initial short-circuit current (r.m.s. value) by √  (4.9a) ip3 = κ ∗ 2Ik3 √  ip2 = κ ∗ 2Ik2 (4.9b) √  ip1 = κ ∗ 2Ik1 (4.9c) System feeder Q Transformer T Q F A Line L k3 S ⬙kQ trT:1 UnQ RQt XQt Q RT XT A RL XL F ~ cUn 3 01 Figure 4.6 Equivalent circuit diagram for single-fed three-phase short-circuit The peak short-circuit current ip2E in the case of a double-phase short-circuit with earth connection is always smaller than either of a three-phase or single-phase shortcircuit and need not be calculated separately. The factor κ can be obtained from Figure 4.7 or calculated by κ = 1.02 + 0.98 ∗ e−3(R/X) (4.10)  ; I  ; I  are the initial symmetrical short-circuit currents for three-phase, where Ik3 k2 k1 double-phase and line-to-earth short-circuit and R; X are the resistance and reactance of the short-circuit impedance. Figure 4.8 indicates an equivalent circuit diagram in the case of a short-circuit fed from non-meshed sources. The peak short-circuit current is calculated by superposing the contributions of different sources. 78 Short-circuit currents 2 1.9 1.8 1.7 1.6 k 1.5 1.4 1.3 1.2 1.1 1 0 Figure 4.7 0.2 0.4 0.6 0.8 1 R/X 1.2 1.4 1.6 1.8 2 Factor κ for the calculation of peak short-circuit current Q1 T1 B I ⬙kT1 ipT1 S ⬙kQ1 I ⬙k ; ip Q2 T2 S ⬙kQ2 Figure 4.8 I ⬙kT2 ipT2 Equivalent circuit diagram for three-phase short-circuit fed from non-meshed sources The peak short-circuit currents ip3T1 and ip3T2 of each branch, fed through the transformers T1 and T2, are calculated separately as well as the factors κT1 and κT2 . √  (4.11a) ip3T1 = κ1 ∗ 2 ∗ Ik3T1 √  (4.11b) ip3T2 = κ2 ∗ 2 ∗ Ik3T2 Calculation of short-circuit current 79 The total peak short-circuit current ip3 is given by (4.11c) ip3 = ip3T1 + ip3T2 Particular considerations are to be taken in the case of short-circuits in meshed networks according to Figure 4.9. The peak short-circuit current at the short-circuit location cannot be calculated by superposition as the R/X-ratios of the individual branches feeding the short-circuit are different and the direction of the branch short-circuit currents through the system is defined by the Ohmic law. Q F Figure 4.9 Equivalent circuit diagram of a three-phase short-circuit in a meshed system In principle, the peak short-circuit current in a meshed system will be calculated by √  ip3 = κ ∗ 2Ik3 (4.9a) as given for three-phase short-circuits, and for other types of short-circuits accordingly. The factor κ, however, will be determined with different methods as below. Uniform (smallest) ratio R/X. The factor κ is calculated based on the smallest ratio R/X of all branches of the network. Only those branches need to be taken into account which contribute to the short-circuit current in the power system corresponding to the short-circuit location, respectively those branches connected through transformers to the short-circuit location. The results are always on the safe side, however the accuracy is low. Ratio R/X at short-circuit location. Based on the ratio R/X of the total system impedance at the short-circuit location, the factor κ is calculated taking account of a safety factor of 1.15 to allow for deviations due to the different ratios R/X in the different branches. κb = 1.15 ∗ κ (4.12) The factor 1.15 ∗ κ should not exceed the value of 1.8 in LV-systems and shall not exceed 2.0 in HV-systems. The safety factor 1.15 is neglected when R/X ≤ 0.3. 80 Short-circuit currents Equivalent frequency fc . The factor κ is found from Figure 4.7 or can be calculated based on the ratio R/X: Rc f c R ∗ = X Xc f (4.13) Rc and Xc are the equivalent effective resistance and reactance at the short-circuit location at equivalent frequency fc which is fc = 20 Hz (nominal power system frequency 50 Hz) fc = 24 Hz (nominal power system frequency 60 Hz) The calculation of the equivalent impedance at equivalent frequency fc is to be carried out additionally to the calculation of impedance at nominal power system frequency [34]. IEC 60909-1 mentions accuracy limits for the different methods of calculating short-circuit currents in meshed systems. Results obtained by the method of uniform (smallest) ratio R/X are always on the safe side, if all branches contributing to the short-circuit current are taken into account. Errors can reach in rare cases up to 100 per cent. If only those branches are considered, which contribute up to 80 per cent to the short-circuit current and if the ratios R/X are in a wide range, the results can even be on the unsafe side. The method therefore shall be applied only if the ratios R/X are in a small bandwidth and if R/X < 0.3. The method ratio R/X at short-circuit location (safety factor 1.15) will lead to results on the safe and unsafe side. Applying the method to ratios 0.005 ≤ R/X ≤ 1.0 the error will be in the range +10 to −5 per cent. The method of equivalent frequency has an accuracy of ±5 per cent, if the ratio R/X of each branch is in the range of 0.005 ≤ R/X ≤ 5.0. 4.3.2.4 Decaying (aperiodic) component idc The maximal decaying aperiodic component idc is calculated by √ idc = 2 ∗ Ik ∗ e−2πf t∗(R/X) (4.14) where Ik is the initial symmetrical short-circuit current, f is the power system frequency, t is the time parameter and R, X are the resistance and reactance of the short-circuit impedance. The resistance of the short-circuit impedance shall be calculated with the real stator resistance RG of generators instead of the fictitious resistance RGf , see Table 3.5. The ratio R/X shall be calculated in meshed systems with an equivalent frequency fc which depends on the duration t of the short-circuit as outlined in Table 4.3. 4.3.2.5 Symmetrical short-circuit breaking current Ib In the case of near-to-generator short-circuits, the a.c. component of the short-circuit current is decaying to a steady-state value, see Figure 4.2(a). The short-circuit current is interrupted by the switchgear at the instant of minimal time delay tmin of the Calculation of short-circuit current Table 4.3 81 Equivalent frequency for the calculation of decaying component Factor f ∗t <1 <2.5 <5 <12.5 Ratio of equivalent frequency to power system frequency Example: f = 50 Hz fc /f 0.27 0.15 0.092 0.055 t fc <0.02 s 13.5 Hz <0.05 s 7.5 Hz <0.1 s 4.6 Hz <0.25 s 2.75 Hz Example: f = 60 Hz t fc <0.02 s 16.2 Hz <0.05 s 9.0 Hz <0.1 s 5.52 Hz <0.25 s 3.3 Hz protection. The calculation of the symmetrical short-circuit breaking current Ib is based on the initial short-circuit current and on the factor μ, Ib = μ ∗ Ik (4.15) The factor μ can be taken from Figure 4.10 or calculated by  μ = 0.84 + 0.26 ∗ e−0.26(IkG /IrG ) for tmin = 0.02 s (4.16a) μ = 0.71 + 0.51 ∗ e for tmin = 0.05 s (4.16b) for tmin = 0.10 s (4.16c) for tmin ≥ 0.25 s (4.16d) μ = 0.62 + 0.72 ∗ e μ = 0.56 + 0.94 ∗ e  /I ) −0.30(IkG rG  /I ) −0.32(IkG rG  /I ) −0.38(IkG rG 1.1 1 Minimum time delay 0.9 0.02 s m 0.8 0.05 s 0.7 0.1 s > 0.25 s 0.6 0.5 0 2 4 6 8 10 12 0 /IrM I 0kG /IrG or I kM Figure 4.10 Factor μ for calculation of symmetrical short-circuit breaking current 82 Short-circuit currents  is the initial symmetrical short-circuit current of the generator, I where IkG rG is the rated current of the generator and tmin is the minimal time delay of the protection, switchgear and auxiliaries, that is, minimal time for switching the short-circuit current off. The factor μ is valid for high-voltage synchronous generators, excited by rotating machines of rectifiers. If the excitation system is not known the factor shall be set to μ = 1. In the case of far-from-generator short-circuits, the symmetrical short-circuit breaking current Ib is equal to the initial short-circuit current Ik as the a.c. component is not decaying. 4.3.2.6 Steady-state short-circuit current Ik The steady-state short-circuit current Ik in the case of near-to-generator short-circuits depends on various factors such as saturation effects, power factor of generators, change of system topology due to operation of switching, etc. and can therefore only be determined with a certain inaccuracy. The method as per IEC 60909 determines lower and upper limits only when one synchronous machine is feeding the shortcircuit. The calculation is based on the generator-rated current assuming a factor λ which depends on the ratio of initial symmetrical short-circuit current to rated current of the generator and on the saturated synchronous reactance. Maximal excitation of the synchronous machine leads to the maximal symmetrical short-circuit breaking current Ik max = λmax ∗ IrG (4.17a) The factor λmax is valid for turbine generators according to Figure 4.11 and for salient-pole generators as per Figure 4.12. The minimal symmetrical short-circuit breaking current is calculated for constant no-load excitation of the generator with the factor λmin . Ik min = λmin ∗ IrG (4.17b) The values for λmin are included in Figures 4.11 and 4.12. Reference is made to the remarks in IEC 60909-0 on the factors. Quantities as used above are IrG  IkG xdsat Rated current of the generator Initial synchronous short-circuit current of the generator Saturated synchronous reactance of the generator, equal to the reciprocal of the short-circuit ratio of the generator In the case of far-from-generator short-circuits, the symmetrical short-circuit breaking current Ib is equal to the initial short-circuit current Ik as the a.c. component is not decaying. 83 Calculation of short-circuit current (a) 2.8 (b) 2.8 2.6 2.6 xdsat 2.4 max 2.2 2.0 1.8 1.6 1.2 1.4 1.6 1.8 2.0 2.2 2.2 2.0 1.8 1.6  1.2 1.0 1.0 1.4 0.8 0.8 min 0.6 0.4 0.2 0.2 0 0 1 2 3 4 5 6 7 8 Three-phase short circuit I 0kG/IrG Figure 4.11 min 0.6 0.4 0 1 2 3 4 5 6 7 8 Three-phase short circuit I kG 0 /IrG Factors λmax and λmin for turbine generators (Figure 17 of DIN EN 60909-0 (VDE 0102)). (a) Series one and (b) series two xdsat 0.6 (b) 5.5 (a) 5.5 5.0 5.0 xdsat 4.5 max 4.0 0.6 3.5 3.0  2.5 1.0 1.2 1.7 2.0 3.0 1.5 min 1.0 0.5 0.8 4.0 0.8 2.0 max 4.5 3.5 0 1.2 1.4 1.6 1.8 2.0 2.2 max 2.4 1.4  1.2 0 xdsat  1.0 1.2 1.7 2.0 2.5 2.0 1.5 min 1.0 0.5 0 1 2 3 4 5 6 7 8 Three-phase short circuit I 0kG/IrG Figure 4.12 0 0 1 2 3 4 5 6 7 8 Three-phase short circuit I 0kG /IrG Factors λmax and λmin for salient-pole generators (Figure 18 of DIN EN 60909-0 (VDE 0102) 1988). (a) Series one and (b) series two 84 Short-circuit currents 4.4 Influence of motors Asynchronous motors and synchronous motors have to be taken into account in MV-systems and in auxiliary supply systems of power plants and industrial networks for the calculation of maximal short-circuit currents. They contribute to the initial symmetrical short-circuit current, to the peak short-circuit current, to the symmetrical short-circuit breaking current and in case of unbalanced short-circuits to the steady-state short-circuit current as well, see Table 4.4. Synchronous motors are modelled like generators and asynchronous generators are treated as asynchronous motors. Motors of any kind, which are not in operation at the same time, e.g., due to the process or due to any interlocking, can be neglected for the calculation of short-circuit currents. Motors fed by static-rectifiers need to be considered in the case of three-phase short-circuits only, if they are able to transfer energy for deceleration for the duration of the short-circuit, as they contribute to the initial symmetrical and to the peak short-circuit current. Table 4.4 Calculation of short-circuit currents of asynchronous motors Parameter Initial symmetrical short-circuit current Peak short-circuit current Type of short-circuit Three-phase Double-phase  Ik3M = √cUn   Ik2M = 23 Ik3M √  ip3M = κM 2Ik3M ip2M = 23 ip3M 3ZM √ √ Line-to-earth √ c 3Un  Ik1M = Z +Z 1M 2M +Z0M in systems with earthed neutral only √  ip1M = κM 2Ik1M MV-motors: κM = 1.65 (RM /XM = 0.15) for active power per pole-pair <1 MW κM = 1.75 (RM /XM = 0.10) for active power per pole-pair ≥1 MW LV-motors including connection cables κM = 1.30 (RM /XM = 0.42) Symmetrical short-circuit breaking current  Ib3M = μqIk3M Steady-state short-circuit current Ik3M = 0 √  Ib2M ≈ 23 Ik3M  Ib1M ≈ Ik1M μ as per Figure 4.10, q as per Figure 4.13 √  Ik2M ≈ 23 Ik3M Quantities used in the equations are explained in the text.  Ik1M ≈ Ik1M Calculation of short-circuit current 85 Asynchronous motors in public supply systems are considered when • the sum of the rated currents is greater than 1 per cent of the initial symmetrical short-circuit current without motors; • the contribution to the initial symmetrical short-circuit current without motors is greater or equal to 5 per cent of the initial symmetrical short-circuit current without motors. Medium- and low-voltage asynchronous motors connected through two-winding transformers to the short-circuit are considered if  PrM 0.8  (4.18) > √  SrT |((c ∗ 100 SrT )/( 3UnQ /Ik )) − 0.3|  where UnQ is the nominal system voltage, SrT is the sum of rated apparent power of all transformers, directly connected to motors feeding the short-circuit, Ik is the  initial symmetrical short-circuit current without motors and PrM is the sum of rated active power of all low- and medium-voltage motors. In order to calculate the branch short-circuit current of asynchronous motors, Table 4.4 can be used. The factor q (three-phase short-circuit) depending on the minimal time delay of the protection tmin can be obtained from Figure 4.13 or by q = 1.03 + 0.12 ∗ ln(m), q = 0.79 + 0.12 ∗ ln(m), q = 0.57 + 0.12 ∗ ln(m), q = 0.26 + 0.10 ∗ ln(m), tmin = 0.02 s (4.19a) tmin = 0.05 s (4.19b) tmin ≥ 0.25 s (4.19d) tmin = 0.10 s (4.19c) where tmin is the minimal time delay of the protection, switchgear and auxiliaries, i.e., minimal time for switching the short-circuit current off and m is the active power of the motor per pole-pair in p.u. based on 1-MW-base. The factor q should not be greater than 1. 4.5 Minimal short-circuit currents In order to calculate the minimal short-circuit current, the voltage factor cmin according to Table 4.1 for the equivalent voltage source at the short-circuit location has to be considered. Furthermore, • System topology, generator dispatch and short-circuit power of feeding networks have to be defined in such a way that the minimal short-circuit current is expected. This normally applies for low-load conditions. • Motors are to be neglected. • Resistances of overhead lines and cables shall be calculated with the maximal permissible temperature at the end of the short-circuit, e.g., 80◦ C in low-voltage systems. 86 Short-circuit currents 1 Minimum time delay 0.9 0.8 0.02 s 0.7 0.6 0.05 s q 0.5 0.1 s 0.4 0.3 > 0.25 s 0.2 0.1 0 0.01 Figure 4.13 0.1 1 10 m (active power per pair of poles) MW 100 Factor q for the calculation of symmetrical short-circuit breaking current These assumptions have to be taken in the case of balanced and unbalanced shortcircuits, except where other presuppositions are mentioned. 4.6 Examples Examples for the calculation of short-circuit currents are included in IEC 60909-4 besides those given below. Reference is made to the relevant chapters where the individual quantities are explained. 4.6.1 Three-phase near-to-generator short-circuit Figure 4.14 outlines the equivalent circuit diagram of a 220-kV system. For threephase short-circuit at busbar B (maximal s.-c. currents) the branch short-circuit currents of the generators and the system feeder as well as the contribution of the generators to the symmetrical short-circuit breaking current and to the steady-state short-circuit current (tmin = 0.1 s; xdsat = 140%; Turbine generator (Series 1)) are to be calculated. Data of equipment taken from nameplates:  SrG1 = 120 MVA; UrG1 = 10.5 kV; cos ϕrG1 = 0.8; xdG1 = 18%  SrG2 = 80 MVA; UrG2 = 10.5 kV; cos ϕrG2 = 0.85; xdG2 = 16% SrT1 = 120 MVA; UrT1HV /UrT1LV = 220 kV/10.5 kV; ukrT1 = 14% SrT2 = 80 MVA; UrT2HV /UrT2LV = 220 kV/10.5 kV; ukrT2 = 12% SrT3 = 200 MVA; UrT3HV /UrT3LV = 400 kV/220 kV; ukrT3 = 12% 87 Calculation of short-circuit current B A Q Figure 4.14 G1 GS 3~ L1 L2 UnQ = 380 kV T1 T2 G2 GS 3~ Un = 220 kV Equivalent circuit diagram of a 220-kV-system with short-circuit location  = 5 GVA; U SkQ nQ = 380 kV   XL1 = XL2 = 0.4 /km; l = 50 km The impedances of equipment (positive-sequence component) including correction factors are XQK = 9.632  XT3 = 28.31  XL1 = XL2 = 20.04  XKW1K = 138.67  XKW2K = 182.52  The short-circuit impedance at the short-circuit location is XkB = 29.82  The initial symmetrical short-circuit currents are:  = 4.69 kA, at s.-c. location Ik3  Ik3Q = 1.69 kA, branch s.-c. current of system feeder The contribution of the generators to the short-circuit currents is outlined in the table below. Parameter Generator 1 Generator 2 Section  Ik3 μ Ib λmax /λmin Ik max /Ik min 21.11 kA 0.879 18.55 kA 1.75/0.46 11.55 kA/3.04 kA 16.04 kA 0.844 13.54 kA 1.82/0.47 8.01 kA/2.07 kA 4.3.2.1 4.3.2.5 4.6.2 Line-to-earth (single-phase) short-circuit The initial short-circuit current for a single-phase short-circuit at location F according to Figure 4.15 shall be calculated. 88 Short-circuit currents Q T1 A B 1 Un = 110 kV T2 UnQ = 220 kV Figure 4.15 C L2 L3 Equivalent circuit diagram of a 110-kV-system with 220-kV-feeder The data of equipment are:  = 5 GVA; X /X = 4 SkQ 0 1 SrT = 100 MVA; ukr = 12%; trT = 220 kV/115 kV; X0 /X1 = 3 XL = 0.13 /km; lL = 10 km; X0 /X1 = 3.5 The impedances in the positive- (negative-) and zero-sequence component including correction factors are: X1QK = 2.904 ; X0QK = 11.62  X1T1K = X1T2K = 15.49 ; X0T1K = X0T2K = 46.34  X1L1 = X1L2 = X1L3 = 1.295 ; X0L1 = X0L2 = X0L3 = 4.538  The impedances at the short-circuit location are X1k = 11.507 ; X0k = 49.368   = 2.895 kA. and the initial short-circuit current is Ik1 4.6.3 Calculation of peak short-circuit current The peak short-circuit current for a three-phase short-circuit at location F according to Figure 4.16 shall be calculated with the different methods, i.e., ‘superposition method’, ‘ratio R/X at s.-c. location’ and ‘equivalent frequency’. The accuracy of the results is to be assessed. The data of equipment are  = 1000 MVA; U SkQ nQ = 110 kV SrT = 10 MVA; ukrT = 10%; PkT = 70 kW; trT = 125 kV/12 kV  = 10% SrG = 20 MVA; UrG = 10.5 kV; cos ϕrG = 0.8; xdG   XL = 0.09 /km; RL = 0.123 /km; lL = 5 km The impedances of equipment including correction factors are XGK = 0.5448 ; RGfK = 0.5448  XL = 0.45 ; RL = 0.615  Calculation of short-circuit current 89 B GS 3~ A Q UnQ = 110 kV Figure 4.16 Un = 10 kV Equivalent circuit diagram of a 10-kV system, f = 50 Hz XQ = 0.122 ; RQ = 0.0122  XT = 1.416 ; RT = 0.0994  The results of short-circuit calculation are outlined in the table below: Method Impedance  Ik3 κ ip Impedance at s.-c. location Zk = (0.244 + 0.649)  9.16 kA — — Superposition of feeders A and B  = 4.118 kA 1.837 i ZkA = (0.1116 + 1.5381)  Ik3A pA = 10.7 kA  = 5.337 kA 1.157 i ZkB = (0.653 + 0.9948)  Ik3B pB = 8.73 kA ipges = 19.43 kA Ratio R/X at s.-c. location Equivalent frequency Zk = (0.244 + 0.649)  9.16 kA 1.337 19.92 kA ZkAc = (0.1116 + 0.6112)  9.16 kA ZkBc = (0.653 + 0.3979)  Zkc = (0.2509 + 0.4036)  1.485 19.24 kA The results obtained with the superposition method are the correct results. 4.6.4 Short-circuit currents in a meshed 110-kV-system The three-phase short-circuit current for the short-circuit location at busbar E in a meshed 110-kV-system shall be calculated. The system diagram is outlined in Figure 4.17. 90 Short-circuit currents GS 3~ G1 GS 3~ G2 A B T2 T1 UnQ = 380 kV Q T3 D C L4 L3 L1 Un = 110 kV Un = 220 kV L2 T4 E Figure 4.17 A 110-kV system with short-circuit location The rated data of equipment (positive-sequence component) are given below: System Q: G1: G2: T1: T2: T3: T4: Lines:  = 4000 MVA UnQ = 380 kV; SkQ  = 18%; cos ϕ SrG1 = 200 MVA; UrG1 = 10.5 kV; xd1 rG1 = 0.85; pG1 = 10%  = 15%; cos ϕ SrG2 = 120 MVA; UrG2 = 10.5 kV; xd2 rG2 = 0.8; pG2 = 10% SrT1 = 200 MVA; ukrT1 = 16%; UrT1HV /UrT1LV = 110 kV/10.5 kV; pT1 = 12% SrT2 = 100 MVA; ukrT2 = 14%; UrT2HV /UrT2LV = 110 kV/10.5 kV; pT2 = 10% SrT3 = 300 MVA; ukrT3 = 16%; UrT3HV /UrT3LV = 400 kV/220 kV; pT3 = 15% SrT4 = 300 MVA; ukrT4 = 16%; UrT4HV /UrT4LV = 220 kV/110 kV; pT4 = 12%  = 0.4 /km; l  XL1 L1 = 40 km; XL2 = 0.36 /km; lL2 = 30 km   XL3 = 0.4 /km; lL1 = 20 km; XL4 = 0.42 /km; lL4 = 100 km 91 Calculation of short-circuit current The impedances of the equipment in %/MVA calculated according to the equations as per Section 3.2.2 are outlined in the table below: No. Equipment   Ik3 x Correction Corrected Sk3 (%/MVA) as per impedance (MVA) (kA) Tables 3.2 (%/MVA) and 3.6 1 2 1+2 3 4 3+4 5 6 7 Y5; 6; 7 Generator 1 Transformer 1 Power station 1 Generator 2 Transformer 2 Power station 2 Line 1 Line 2 Line 3 L1L2 L1L3 L2L3 System Q Transformer 3 Line 4 Transformer 4 0.09 0.08 0.17 0.125 0.14 0.265 0.1322 0.0893 0.0661 0.8996 0.153 0.8576 0.227 0.041 0.0304 0.0205 8 9 10 11 8 + 9 + 10 + 11 12 Total impedance at E 0.02736 0.0533 0.0868 0.05 1.004 0.0535 1.004 0.0502 0.2212 0.096 1146 6.01 4.6.5 Influence of impedance correction factors on short-circuit currents The three-phase short-circuit current for the short-circuit location in the 110-kVsystem in a single-fed system of different voltage levels as outlined in Figure 4.18 shall be calculated. Q T1 C B T2 A L Un = 220 kV UnQ = 380 kV Figure 4.18 UnB = 110 kV System with different voltage levels with short-circuit location 92 Short-circuit currents The rated data of equipment (positive-sequence component) are given below: System Q: T1: T2: Line:  = 5000 MVA UnQ = 380 kV; SkQ SrT1 = 200 MVA; ukrT1 = 16%; 220 kV; pT1 = 12% SrT2 = 200 MVA; ukrT2 = 16%; 120 kV; pT2 = 10% XL = 0.4 /km; lL = 100 km UrT1HV /UrT1LV = 400 kV/ UrT2HV /UrT2LV = 220 kV/ The impedances of the equipment in %/MVA and the short-circuit current calculated according to the equations as per Section 3.2.2 are outlined in the table below: No. Equipment x (%/MVA)  Sk3 (MVA)  Ik3 (kA) 1 2 3 4 5 System Q Transformer 1 Line Transformer 2 Total impedance at 110 kV 0.0219 0.08 0.0826 0.08 0.2645 415.9 2.18 As indicated by the rated data of equipment and as can be seen in Figure 4.18, the rated voltage of the transformers differ from the nominal voltages of the 380-kV- and the 110-kV-systems. Correction factors for those equipment connected to the shortcircuit location through transformers must be taken into account. The results of the calculation with impedance correction factor as per Figure 2.16 and Equation (2.27) are given below. No. Equipment x (%/MVA) Correction factor as per Figure 2.16 Corrected impedance (%/MVA) 1 2 3 4 5 System Q Transformer 1 Line Transformer 2 Total impedance at 110 kV 0.0219 0.08 0.0826 0.08 1.074 1.19 1.19 1.19 0.0235 0.0952 0.0983 0.0952 0.3122  Sk3 (MVA)  Ik3 (kA) 352.3 1.85 Calculation of short-circuit current 93 The calculation of transformer impedances furthermore requires impedance correction factor as outlined in Table 3.3. The results of the analysis, taking account of both correction factors (Figure 2.16 and Table 3.3), are outlined in the table below: No. Equipment   x Correction Correction Corrected Sk3 Ik3 (%/MVA) factor factor impedance (MVA) (kA) as per as per (%/MVA) Figure 2.16 Table 3.3 1 2 3 4 5 0.0219 0.08 0.0826 0.08 0.2645 System Q Transformer 1 Line Transformer 2 Total impedance at 110 kV 1.074 1.19 1.19 1.19 1.004 1.004 0.0235 0.0956 0.0983 0.0956 0.313 351.4 1.84 Calculating the short-circuit current in the p.u.-system is similar to the calculation in the %/MVA-system. Correction factors as per Table 3.3 for the transformers and Figure 2.16 due to differences between the rated voltages of equipment and the nominal system voltages have to be taken into account. The reference voltage is equal to the nominal voltage at the short-circuit location UB = 110 kV and the reference power is 100 MVA. The results are outlined in the table below: No. Equipment x (p.u.) Correction factor as per Figure 2.16 1 2 3 4 5 0.0219 0.08 0.0826 0.08 0.2645 1.074 1.19 1.19 1.19 System Q Transformer 1 Line Transformer 2 Total impedance at 110 kV   ik3 Correction Corrected sk3 impedance (p.u.) (p.u.) factor (p.u.) as per Table 3.3 1.004 1.004 0.0235 0.0956 0.0983 0.0956 0.313 3.514 2.024 If the short-circuit current is calculated using the -system only the correction factor as per Table 3.3 for the transformers has to be taken into account. The results as per 94 Short-circuit currents calculation in the -system are outlined in the table below: No. Equipment X () 1 2 3 4 5 System Q Transformer 1 Line Transformer 2 Total impedance at 110 kV 2.844 11.519 11.894 11.519 37.78 Correction as per Table 3.3 1.004 1.004 Corrected impedance () 2.844 11.565 11.894 11.565 37.87  Sk3 (MVA)  Ik3 (kA) 351.4 1.84 The greatest influence on the short-circuit current is given by the correction factors due to the difference of the rated voltage of the transformers and the nominal voltages of the 380-kV- and the 110-kV-systems as can be seen clearly from the results. The correction factor of the transformers as per Table 3.3, however, have only a negligible effect on the system under investigation. As the individual correction factors depend on the rated data of the equipment the influence on the short-circuit current may be different in other system configurations. Thus, it should be noted that the correction factors should be taken into account in general. 4.6.6 Short-circuit currents in a.c. auxiliary supply of a power station Figure 4.19 indicates the high-voltage system configuration of the a.c. power supply of a power station. Auxiliary supply is connected to the 6-kV-busbar E. During start-up of the power station, i.e., prior to synchronization of the generator, the power supply is taken from the start-up supply through transformer T5 either from the 30-kV-system connected to busbar B or from the 110-kV-system (busbar A) or 220-kV-system (busbar Q). After synchronization the transformers T2 and T5 are both in operation for the auxiliary supply, transformer T5 is switched-off finally and the auxiliaries are supplied through transformer T2 only. The rated data of equipment are given below: System Q System A System B  = 10,000 MVA UnQ = 220 kV; SkQ  UnA = 110 kV; SkA = 3000 MVA  = 300 MVA UnB = 30 kV; SkB Calculation of short-circuit current UnQ = 220 kV Q 95 UnA = 110 kV A T3 × T1 T4 B UnB = 30 kV T5 × GS 3~ T2 G UrG = 11.5 kV Figure 4.19 G T1 T2 T3 T4 T5 UnE = 6 kV E High-voltage system configuration for the auxiliary supply of a power station SrG = 300 MVA; UrG = 11.5 kV; xd = 18%; cos ϕrG = 0.85 SrT1 = 300 MVA; ukrT1 = 14%; UrT1HV /UrT1LV = 220 kV/11.5 kV SrT2 = 25 MVA; ukrT2 = 8%; UrT2HV /UrT2LV = 11.5 kV/6 kV SrT3 = 150 MVA; ukrT3 = 12%; UrT3HV /UrT3LV = 220 kV/110 kV SrT4 = 40 MVA; ukrT4 = 10%; UrT4HV /UrT4LV = 110 kV/30 kV SrT5 = 25 MVA; ukrT5 = 8%; UrT5HV /UrT5LV = 11.5 kV/6 kV Data on the voltage control of the generator and the tap-changers of the transformers are not known. The short-circuit currents have to be calculated for threephase short-circuit at the auxiliary busbar E for the three operating conditions as mentioned. 96 Short-circuit currents The impedances of the equipment are given in the table below. No. Equipment x (%/MVA) 1 2 3 4 5 6 7 8 9 System Q System A System B Generator Transformer 1 Transformer 2 Transformer 3 Transformer 4 Transformer 5 0.0109 0.0365 0.3652 0.06 0.0467 0.32 0.8 0.25 0.32 Correction factor as per Table 3.2 and Table 3.3 Corrected impedance (%/MVA) 1.005 0.964 0.997 0.975 0.986 0.997 0.0603 0.045 0.31 0.7799 0.246 0.31 For start-up operation of the power station the total impedance is xkS =  = 22.58 kA. 0.469%/MVA, resulting in a three-phase short-circuit current of Ik3S For the intermediate operation state (both transformers T2 and T5 are in operation) the total impedance is xkI = 0.197%/MVA, the three-phase short-circuit  = 53.82 kA. For normal operation of the power station the total current is Ik3I impedance is xkN = 0.339%/MVA, resulting in a three-phase short-circuit current  = 31.23 kA. of Ik3N The highest short-circuit current appears in case the auxiliaries are supplied through the transformers T2 and T5. This condition is only present for a short-time while switching from one supply to the other. It is therefore not recommended to take this condition for the design rating of the switchgear and equipment, but to take the highest short-circuit current occurring under other operating conditions  = 31.23 kA). (Ik3 Calculation can also be done using p.u.-system, which gives identical numerical values for the impedances. The short-circuit currents in p.u.-system are calculated with reference voltage UB = 6 kV (nominal system voltage at short-circuit location). Results of calculation in %/MVA-system and p.u.-system are outlined in the table below. Operating condition x (%/MVA)  Ik3 (kA) x (p.u.)  ik3 (p.u.) Start-up operation Transformers T2 and T5 are in operation Normal operation of the power station 0.469 0.197 0.339 22.58 53.82 31.23 0.469 0.197 0.339 1.35 3.23 1.87 Chapter 5 Influence of neutral earthing on single-phase short-circuit currents 5.1 General The theoretical approach to calculate short-circuit (s.-c.) currents with symmetrical components in general and especially in the case of single-phase short-circuit was explained in detail in Chapter 2. Current and voltages in case of short-circuits with earth connection (e.g., single-phase short-circuits) depend on the positive- and zerosequence impedances Z1 and Z0 . If the ratio of zero-sequence to positive-sequence impedance is k = Z0 /Z1 the voltages in the non-faulted phases (see Equation (2.25a)) and the single-phase short-circuit current (see Equation (2.25b)) are |U Y | = |U B | = E1 ∗  Ik1 = 3 E1 ∗ Z1 2 + k √ 3∗ √ k2 + k + 1 2+k (5.1a) (5.1b) √ If the voltage E1 is set to E1 = Un / 3, similar to the equivalent voltage at short-circuit location then √ k2 + k + 1 (5.1c) |U Y | = |U B | = Un ∗ 2+k 3 Un  (5.1d) ∗ Ik1 =√ 3 ∗ Z1 2 + k The impedances in the positive-sequence (and negative-sequence) system are determined only by the network topology. The single-phase short-circuit current and the voltages of the non-faulted phases can be changed only by changing the ratio of positive-sequence to zero-sequence impedance, i.e., by changing the handling of transformer neutrals. 98 Short-circuit currents The type of neutral earthing determines the impedance Z0 of the zero-sequence component and has a dominating influence on the short-circuit current through earth,  in case of single-phase short-circuits and I  i.e., Ik1 kE2E in case of two-phase shortcircuit with earth connection. In order to change the zero-sequence impedance of the system, it is possible to earth any number of neutrals, i.e., none, a few or all transformer neutrals, leading to the highest zero-sequence impedance (no neutral earthed), respectively the lowest zero-sequence impedance (all neutrals earthed). The system is characterised less by the number of neutrals to be earthed, than by the value of the single-phase short-circuit current and by the voltages in the non-faulted phases. The different types of neutral handling in power systems (high-voltage systems only) are outlined in Table 5.1. Quantities as per Table 5.1 Un U0max ω CE Z0; Z1 δ0 v 5.2 Nominal system voltage Maximal voltage in the zero-sequence system, i.e., at neutral of transformer Angular velocity of the power system Line-to-earth capacitance of the power system Zero-sequence, respectively positive-sequence, impedance of the system Damping of the power system (see Section 5.5) Ratio indicating capacitance to reactance (see Section 5.5) Power system with low-impedance earthing Low-impedance earthing is applied in medium-voltage and high-voltage systems worldwide with nominal voltages above 10 kV. Power systems having nominal voltages Un ≥ 132 kV are generally operated with low-impedance earthing. In order to realise a power system with low-impedance earthing, it is not necessary that the neutrals of all transformers are earthed, but to fulfil the criteria, that the voltages of the non-faulted phases remain below 140 per cent of the nominal system voltage in the case of a single-phase short-circuit. The disadvantage while earthing all neutrals is seen in an increased single-phase short-circuit current, sometimes exceeding the three-phase short-circuit current. The neutral of unit transformers in power stations shall not be earthed at all, as the single-phase short-circuit current will then depend on the generation dispatch. As the contribution of one unit transformer is in the range of up to 8 kA, the influence on the single-phase short-circuit currents is significant. Based on Figure 5.1 and assuming a far-from-generator short-circuit with positivesequence impedance equal to negative-sequence impedance Z 1 = Z 2 , the singlephase short-circuit current is calculated by √ c ∗ 3 ∗ Un (5.1e) I k1 = 2 ∗ Z1 + Z0 Table 5.1 Characteristics of different types of neutral handling in power systems Single-phase fault current (short-circuit current) Increase of voltages at non-faulted phases Isolated neutral Low-impedance earthing Earthing with current limitation Resonance earthing Capacitive earth-faults current Single-phase (earth-fault) short-circuit current Single-phase (earth-fault) short-circuit current Residual earth-fault current √ I CE ≈ j 3ωCE Un √ I k1 = c 3Un /(2Z 1 + Z 0 ) √ I k1 = c 3Un /(2Z 1 + Z 0 ) √ I Rest ≈ j 3Un ωCE (δ0 + j v) Present U0max /Un ≈ 0.6 √ ≈ 3 Generally high No increase U0max /Un < 0.3–0.45 No increase U0max /Un ≈ 0.45–0.6 √ 1.38– 3 >4 Present U0max /Un ≈ 0.6 √ √ ≈ 3–1.1 ∗ 3 →Infinite Extinguishing of fault arc Self-extinguishing (see Figure 5.11) Not self-extinguishing Self-extinguishing in rare cases Self-extinguishing (see Figure 5.11) Repetition of faults Double earth-fault Reignition of earth-fault None None Double earth-fault Voltage at earthing electrode UE UE ≤ 125 V UE > 125 V permitted UE > 125 V permitted UE ≤ 125 V Touching voltage UB UB ≤ 65 V See VDE 0141 See VDE 0141 UB ≤ 65 V Earth-fault factor δ Ratio of impedances Z0 /Z1 <1.38 2–4 100 Short-circuit currents (a) Z0; Z1; Z2 B Y R IR UY; UB I1 (b) Z1 E1 = E 0 U1 01 I2 Z2 U2 02 I0 Z0 U0 00 Figure 5.1 Equivalent circuit diagram of a single-phase short-circuit (system with low-impedance earthing). (a) Diagram in RYB-system, (b) equivalent circuit diagram in the system of symmetrical components with voltage factor c according to Table 4.1. If the single-phase short-circuit current is related to the three-phase short-circuit current c ∗ Un I k3 = √ 3 ∗ Z1 (5.2) I k1 3 ∗ Z1 = I k3 2 ∗ Z1 + Z0 (5.3) it follows that The relation of single-phase to three-phase short-circuit current depending on the ratio of Z1 /Z0 with the difference of phase angles (γ1 − γ0 ) of the impedances as parameter is outlined in Figure 5.2. The phase angles γ1 and γ0 are defined by the arcustangens-function γ1 = arctan(X1 /R1 ) in the positive-sequence system respectively γ0 = arctan(X0 /R0 ) in the zero-sequence system. Influence of neutral earthing 101 3.5 3 2.5 I 0k1/I k3 0 0° 2 Degree 30° 1.5 60° 90° 1 150° 120° 0.5 0 0 0.5 1 1.5 2 2.5 3 Z1/Z0 Figure 5.2 Ratio of single-phase to three-phase short-circuit current depending on Z1 /Z0 and (γ1 − γ0 ) The voltages (power-frequency voltage) of the non-faulted phases Y and B, as calculated in Chapter 2 in detail, U Y = E1 ∗ Z 0 ∗ (a 2 − 1) + Z 2 ∗ (a 2 − a) Z0 + Z1 + Z2 (5.4a) U B = E1 ∗ Z 0 ∗ (a − 1) + Z 2 ∗ (a − a 2 ) Z0 + Z1 + Z2 (5.4b) can be simplified if Z 1 = Z 2 is assumed and by taking account of the meaning of a and a 2 as below: √ √ 3 U Y = −0.5 3 ∗ E 1 ∗ (5.5a) 1 + (2Z 1 /Z 0 ) + j √ √ 3 (5.5b) U B = −0.5 3 ∗ E 1 ∗ 1 + (2Z 1 /Z 0 ) − j Relating the voltages to the voltage E1 the earth-fault factors of the phases Y and B, δY and δB are obtained.     3   δY = −0.5 ∗ (5.6a) 1 + (2Z 1 /Z 0 ) + j      3  (5.6b) δB = −0.5 ∗ 1 + (2Z 1 /Z 0 ) − j  102 Short-circuit currents which are different from each other, depending on the impedances and the phase angle. The effect of the earthing can be described by the earth-fault factor δ according to VDE 0141/07.89 and is defined to be the maximum of the earth-fault factors δY and δB δ = MAX{δY ; δB } = ULE max √ U/ 3 (5.7) where ULEmax is the highest value of the power-frequency voltage phase-to-earth of the non-faulted phases in the case of a short-circuit with earth connection and U is the voltage between phases prior to fault. Power systems having an earth-fault factor δ < 1.4 are defined as systems with low-impedance earthing. It should be noted that the single-phase short-circuit currents shall be below the permissible limits, which are defined by the breaking capability of circuit-breakers, the short-circuit withstand capability of switchgear, installations and equipment and by other criteria such as earthing voltage, induced voltages, etc. Figure 5.3 indicates the earth-fault factors δY and δB in dependence of the ratio Z 1 /Z 0 and the difference of impedance angles (γ1 − γ0 ). An impedance angle above 90◦ is only possible in the case of a capacitive impedance of the zero-sequence component but not in systems with low-impedance earthing. Figure 5.4 presents the earth-fault factor δ in relation to X0 /X1 with the parameter R0 /X0 , whereas the impedance angle in the positive-sequence component remains constant. The earth-fault factor δ remains below 1.4 if X0 /X1 ≤ 5 can be achieved and if R0 /X0 is kept below 0.2 (alternatively X0 /X1 ≤ 4 and R0 /X0 < 0.3). An impedance ratio X0 /X1 = 2–4 can easily be achieved in power systems as the relation of zero-sequence to positive-sequence impedances of equipment is X0 /X1 ≈ 4 X0 /X1 ≈ 3 X0 /X1 ≈ 0.3 5.3 Parallel double-circuit overhead lines Single-circuit overhead lines and HV-transformers Yy(d) Unit transformers Yd in power stations (normally not to be earthed) Power system having earthing with current limitation Earthing with current limitation can be seen in some cases as a special case of the low-impedance earthing, provided the earth-fault factor is below 1.4. Earthing with current limitation is applied in urban power systems having rated voltage Un ≤ 20 kV. Some applications are known in systems with nominal voltage up to 132 kV. The criterion for the design of the earthing conditions is the value of the singlephase short-circuit current, which can be limited to some kA (1 kA or 2 kA) in mediumvoltage systems or to some 10 kA in high-voltage systems (e.g., below the three-phase short-circuit current). To realise the scheme of earthing with current limitation, the neutrals of some or all transformers are earthed through reactances or resistances Influence of neutral earthing 103 (a) 2.5 2 120° 1.5 Degree 0° 30° 150° dY 1 0.5 60° 90° 0 0 (b) 0.5 1 1.5 Z1/Z0 2 2.5 3 2 2.5 3 4 3.5 3 30° 2.5 dB Degree 0° 2 60° 1.5 120° 1 90° 150° 0.5 0 0 Figure 5.3 0.5 1 1.5 Z1/Z0 Earth-fault factors in relation to Z 1 /Z 0 and (γ1 − γ0 ). (a) Earth-fault factor δY and (b) earth-fault factor δB to such an amount that the condition for the single-phase short-circuit is fulfilled. As a disadvantage it should be noted that the earth-fault factor δ might exceed the value of 1.4, which seems to be acceptable in medium-voltage systems with nominal voltages Un = 10–20 kV. In high-voltage systems with Un = 110–132 kV the advantages and disadvantages have to be analysed in more detail. In order to estimate the required value of the earthing impedance, the zero /I  sequence impedance is considered based on Figure 5.5, indicating the ratio of Ik1 k3 as well as the earth-fault factor δ in relation to X0 /X1 . As an example, a mediumvoltage system with Un = 10 kV having an initial three-phase short-circuit power  = 100–250 MVA (I  = 5.8–14.4 kA) is regarded. In this case for the limitation Sk3 k3 104 Short-circuit currents 1.8 0.01 0.02 1.6 0.5 1.4 1.0 2.0 3.0 d 1.2 R0 /X0 1 0.8 0.6 0 Figure 5.4 1 2 3 4 5 6 X0/X1 7 8 9 10 11 12 Earth-fault factor δ depending on X0 /X1 for different ratios R0 /X0 and R1 /X1 = 0.01 2.5 d 2.0 3 0.8 3 I ⬙k3 d; I ⬙k1 1.5 1.0 Low-impedance earthing d 0.5 I ⬙k1/I ⬙k3 0 –12 Figure 5.5 –10 –8 –6 –4 –2 0 X0/X1 2 4 6 8 10  /I  depending on X /X Earth-fault factor δ and ratio Ik1 0 1 k3 12 Influence of neutral earthing 105  = 2 kA the ratio X /X = 6.7–19.6 of the single-phase short-circuit current to Ik1 0 1 is required. The earth-fault factor in this case will be δ = 1.44–1.61. By this, the system is no longer a system with low-impedance earthing. 5.4 Power system with isolated neutral The operation of power systems with isolated neutrals is applicable to systems with nominal voltages up to 60 kV, however the main application is seen in power station auxiliary installations and industrial power systems with voltages up to 10 kV. In public supply systems, isolated neutrals are not very common. The analysis of a single-phase earth-fault is based on Figure 5.6. (a) ~ B (L3) ~ Y (L2) ~ R (L1) U E = n 3 GE CE (b) ~ E1 01/02 GE CE U0 00 Figure 5.6 Power system with isolated neutral with single-phase earth-fault. (a) Equivalent circuit diagram in RYB-system and (b) equivalent circuit diagram in the system of symmetrical components Contrary to power systems with low-impedance earthing or earthing with current limitation the capacitances phase-to-earth capacitances in the zero-sequence component cannot be neglected in power systems with isolated neutral as can be seen from Figure 5.6. To determine the respective parameters of the equipment, no-load measurements are necessary. The single-phase earth-fault current, in general, 106 Short-circuit currents is calculated by I1 √ c ∗ 3 ∗ Un = |2 ∗ Z 1 + Z 0 | (5.8) where Un is the nominal system voltage, c is the voltage factor as per Table 4.1 and Z 1 ; Z 0 are the positive- and zero-sequence impedances, respectively. The zero-sequence impedance Z 0 is determined by the capacitance phase-toearth CE , and is significantly higher than the positive-sequence impedance Z 1 . The single-phase earth-fault current is determined through the capacitive component by √ I R = I CE = j ω ∗ CE ∗ 3 ∗ Un (5.9) and is called capacitive earth-fault current I CE . As the capacitive earth-fault current is significantly lower than a typical short-circuit current, in most of the cases even lower than the normal operating current, the single-phase fault in a system with isolated neutral is called earth-fault instead of short-circuit. The earth-fault current increases with increasing capacitance phase-to-earth and by this with increasing line length as can be seen from Equation (5.9). Small capacitive currents in the case of faults through air can be extinguished by themselves if they remain below some 10 A depending on the voltage level. Figure 5.7 indicates the limits for self-extinguishing of capacitive currents ICE according to VDE 0228 part 2/12.87. A 140 120 100 ICE 80 60 ICE 40 20 0 Figure 5.7 3 10 20 Un 30 60 110 kV Limit for self-extinguishing of capacitive currents in air according to VDE 0228 part 2 The voltages (phase-to-earth) of the non-faulted phases in the case of an earthfault are increasing to the amount of the phase-to-phase voltage, as can be seen from Figure 5.8. Prior to fault the voltage potential of earth (E) and neutral (N) are identical, the phase-to-earth voltages are symmetrical as well as the line-to-line voltages. During the earth-fault, the voltage of the faulted phase (R) is identical to Influence of neutral earthing 107 (a) R;E (b) UR UB E,N UB UY UY N B Figure 5.8 UNE Y Vector diagram of voltages, power system with isolated neutral. (a) Prior to fault and (b) during earth-fault the voltage of the earth (E). The voltage potential of the neutral (N) is given, by definition, as the mean value of the three phases R, Y and B which is not changed by the earth-fault. A voltage displacement U NE between neutral and earth equal to the line-to-earth voltage is originating from the earth-fault. The voltage displacement is equal to the voltage U 0 of the zero-sequence component. As the impedance of the zero-sequence component is significantly higher than the impedances of the positiveand negative-sequences system, the displacement voltage is identical with the voltage at the transformer neutral. The voltages of the non-faulted phases are increased, but the three voltages phase-to-phase remain symmetrical as outlined in Figure 5.8(b). The capacitive earth-fault current and the recovery voltage at the fault location have a phase displacement of nearly 90◦ . At the instant of the maximum of the recovery voltage or shortly after it, a reignition of the fault arc is possible and probable. The time courses of the phase-to-earth voltages uR , uY and uB and of the displacement voltage uNE as well as the earth-fault current iCE are outlined in Figure 5.9 indicating the time prior, during and after the occurrence of the earth-fault. The earth-fault occurs at time instant t1 , phase R having the maximal voltage. The phase-to-earth voltage of the non-faulted phases Y and B are increasing to the value of the phase-to-phase voltage. The displacement voltage uNE increases from a very low value, ideally zero, to the phase-to-earth voltage. The transient frequency can be calculated by f ≈ 2∗π ∗ √ 1 3 ∗ L 1 ∗ C0 (5.10) where L1 is the inductance of the positive-sequence system and C0 the capacitance of the zero-sequence system. The earth-fault arc is extinguished at time t2 approximately 10 ms after ignition of the earth-fault; the current iCE has its zero-crossing, whereas the displacement voltage has nearly reached its peak value. The three phase-to-earth voltages uR , uY and uB are symmetrical to each other, however with a displacement determined by the displacement voltage at the time of arc extinguishing, i.e., the displacement voltage is equal to the peak value of the phase-to-earth voltage. Approximately 10 ms after the extinguishing √ of the arc the phase-to-earth voltage of phase R reaches the new peak value 2 ∗ 2 ∗ Un . 108 Short-circuit currents ^ u/U ^ 2.0 1.0 uR 3 1.5 uNE uY uR uNE uY 0.5 uB uR 0 uB –0.5 –1.0 Voltages uY uB –1.5 t1 t3 Earth-fault current iCE Figure 5.9 t2 Time courses of phase-to-earth voltages, displacement voltage and earth-fault current. System with isolated neutral, earth-fault in phase R This voltage may cause a reignition of the earth-fault due to the very high-voltage stress. This reignition takes place at time instant t3 with the phase-to-earth voltage of phase R having its peak value. The voltages of the non-faulted phases again are increasing, this time starting from a higher value and reaching the peak value √ √ nearly to 3 ∗ 2 ∗ Un . Besides the power-frequency overvoltage in the case of an earth-fault, the transient overvoltage with frequency according to Equation (5.10) has to be considered. The overvoltage factor kLE , taking account of both types of overvoltages, is given by the maximal peak voltage related to the peak value of phase-to-earth voltage uü (5.11) kLE = √ √ 2 ∗ U/ 3 where uü is the maximal peak voltage during the earth fault and U the phase-to-earth voltage (power-frequency). In theory, the overvoltage factor after multiple reignition of the earth-fault can reach kLE = 3.5. Due to the system damping, the overvoltage factor will be below kLE < 3 in most of the cases. 5.5 Power system with resonance earthing (Petersen-coil) 5.5.1 General Power systems with resonance earthing are widely in operation in Central European countries. The German power system statistic [3] indicates that 87 per cent of the Influence of neutral earthing 109 MV-systems having nominal voltages Un = 10–30 kV and nearly 80 per cent of 110-kV-systems are operated with resonance earthing (Criteria: Total line lengths). Some MV-systems are operated with a combined scheme of resonance earthing under normal operating conditions and low-impedance earthing in case of earthfault. Resonance earthing, therefore, is the dominating type of system earthing in Germany for power systems with voltage 10 kV up to 110 kV. In other countries such as India, South Africa and China, power systems with resonance earthing have gained an increasing importance during the last decades, however are still not so common as systems with low-voltage earthing. Resonance earthing is realised by earthing of one or several neutrals of transformers through reactances (Petersen-coils), normally adjustable, which will be set in resonance to the phase-to-earth capacitances of the system. The principal arrangement of a power system with resonance earthing is outlined in Figure 5.10. The impedances of transformers and lines of the positive-sequence component can be neglected compared with those of the zero-sequence component due to the order of magnitude of the impedances. The admittance of the zero-sequence component is (a) ~ B (L3) ~ Y (L2) ~ R (L1) E = LD Un 3 GE CE U0 310 (b) ~ E1 01/02 3RD 3LD GE CE U0 00 Figure 5.10 System with resonance earthing, earth-fault in phase R. (a) Equivalent diagram in RYB-system and (b) equivalent diagram in the system of symmetrical components 110 Short-circuit currents given by Y 0 = j ω ∗ CE + 1 + GE 3 ∗ RD + j 3 ∗ X D (5.12) where CE is the phase-to-earth capacitance of the system, ω is the angular frequency of the system, RD is the resistance of the Petersen-coil, XD is the reactance of the Petersen-coil XD = ωL and GE is the admittance representing the phase-to-earth line losses. After some conversions it follows that  1 + GE (5.13a) Y 0 = j ω ∗ CE ∗ 1 − 3 ∗ ω2 ∗ LD ∗ CE ∗ (1 − j (RD /XD )) The impedance of the Petersen-coil appears with its threefold value in the zerosequence component [1]. It is assumed that RD ≪ XD and that the losses of the Petersen-coil are summed up with the phase-to-earth losses and are represented as admittance GE of the line. The admittance in the zero-sequence component is then  1 (5.13b) + GE Y 0 = j ω ∗ CE ∗ 1 − 2 3 ∗ ω ∗ LD ∗ CE The maximal impedance is obtained if the imaginary part as per Equation (5.13b) is equal to zero; the current from the Petersen-coil ID is equal to the capacitive current ICE of the system. As indicated in Figure 5.10, the capacitance phase-to-earth CE , the reactance 3LD and the ohmic losses R0 = 1/GE are forming a parallel resonance circuit with the resonance frequency 1 ω= √ 3 ∗ L D ∗ CE (5.14) The resonance frequency in the case of resonance earthing shall be the nominal frequency of f = 50 Hz or f = 60 Hz, respectively. Defining the detuning factor v v= ID − ICE 1 =1− ICE 3 ∗ ω 2 ∗ L D ∗ CE (5.15a) GE ω ∗ CE (5.15b) and the damping d d= the admittance of the zero-sequence component is given by Y 0 = ω ∗ CE ∗ (j v + d) (5.16) The admittance will be minimal and the impedance will be maximal in the case of resonance tuning (v = 0). The earth-fault current I Res , in general, is obtained by √ (5.17a) I Res ≈ 3 ∗ Un ∗ ω ∗ CE ∗ (j v + d) In case of resonance tuning (v = 0) the earth-fault current is a pure ohmic current √ (5.17b) I Res ≈ 3 ∗ Un ∗ ω ∗ CE ∗ d Influence of neutral earthing 111 The phase-to-earth voltages of the non-faulted phases increase to the value of the phase-to-phase voltage in the case of a single-phase earth-fault, which is furthermore increased due to asymmetrical system voltages resulting in a higher displacement voltage between neutral and earth. In order to avoid the high voltages in the case of exact resonance tuning a small detuning of 8–12 per cent is chosen in practice. The task of resonance earthing is to reduce the earth-fault current at the fault location to the minimum or nearly to the minimum by adjusting the Petersen-coil to resonance or nearly to resonance with the phase-to-earth capacitances. The ohmic part of the residual current IRes cannot be compensated by this. If the residual current is small enough, a self-extinguishing of the arc at the fault location is possible. VDE 0228 part 2:12.87 defines the limits for self-extinguishing of residual currents IRes (and capacitive earth-fault currents ICE ) for different voltage levels as outlined in Figure 5.11. It can be seen from Figure 5.11 that the limit for ohmic currents, e.g., in 30-kV-systems, is twice the limit for capacitive currents. The Petersen-coil can only be tuned for one frequency (nominal frequency) in resonance; harmonics present in the system voltage are increasing the residual current at the fault location. As the phase-to-earth capacitances are changing during system operation, e.g., due to switching of lines, the Petersen-coil has to be changed also to keep system operation with resonance tuning. Reliable criteria have to be established to tune the Petersen-coil in resonance with the phase-to-earth capacitances. A 140 120 100 IRes IRes ; ICE 80 60 ICE 40 20 0 3 10 20 30 60 110 kV Un Figure 5.11 Current limits according to VDE 0228 part 2:12.87 of ohmic currents IRes and capacitive currents ICE 112 Short-circuit currents 5.5.2 Calculation of displacement voltage In real power systems, the phase-to-earth capacitances are unequal, e.g., in the case of a transmission line due to different clearance of the phase-wires above ground or the case of cables due to manufacturing tolerances. Under normal operating conditions, a displacement voltage between transformer neutral and earth U NE can be measured. As mentioned in previous sections, this voltage is equal to the voltage U 0 in the zerosequence component. The calculation of the displacement voltage can be carried out in the RYB-system (Figure 5.12(a)) as well as with the system of symmetrical components (Figure 5.12(b)). Based on Figure 5.12(a) the displacement voltage is calculated as j ω ∗ (CRE + a 2 ∗ CYE + a ∗ CBE ) Un U NE = √ ∗ 3 j ω ∗ (CRE + CYE + CBE ) − j (1/(ω ∗ LD )) + 3 ∗ GE (a) ~ B (L3) ~ Y (L2) ~ R (L1) E= (5.18) Un 3 CBE CYE GE CRE ΔC U0 = UNE LD 310 (b) ~ 1+2 E1 01/02 1 3 3LD GE CE U0 ΔCE 0 00 Figure 5.12 Equivalent circuit diagram of a power system with asymmetrical phase-to-earth capacitances. (a) Equivalent circuit diagram in the RYB-system and (b) equivalent circuit diagram in the system of symmetrical components Influence of neutral earthing 113 where Un is the nominal system voltage, ω is the angular frequency of the system, CRE ; CYE ; CBE are the line-to-earth capacitances as per Figure 5.12(a), LD is the inductance of the Petersen-coil and GE is the admittance representing the phase-to-earth line losses. If the phase-to-earth capacitances are different and if the asymmetry is assumed to be placed in phases R and Y, the capacitances are CRE = CE + CRE (5.19a) CYE = CE + CYE (5.19b) (5.19c) CBE = CE where CRE ; CYE are the asymmetry of the line-to-earth capacitances. The displacement voltage is given by Un U NE = √ ∗ 3 (3 ∗ CE + CRE + a 2 ∗ CYE CRE + CYE ) − j (1/(ω ∗ LD )) + 3 ∗ GE (5.20) Defining the asymmetry factor k k= = CRE + a 2 ∗ CYE + a ∗ CBE CRE + CYE + CBE CRE + a 2 ∗ CYE 3 ∗ CE + CRE + CYE (5.21a) the system damping d 3 ∗ GE ω ∗ (CRE + CYE + CBE ) 3 ∗ GE = ω ∗ (3 ∗ CE + CRE + CYE ) d= (5.21b) and the detuning factor v 1/(ω ∗ LD ) − ω ∗ (CRE + CYE + CBE ) ω ∗ (CRE + CYE + CBE ) 1/(ω ∗ LD ) − ω ∗ (3 ∗ CE + CRE + CYE ) = ω ∗ (3 ∗ CRE + CRE + CYE ) v= (5.21c) the displacement voltage U NE is calculated by k Un U NE = √ ∗ 3 v + jd (5.22) Assuming the asymmetrical capacitance CE concentrated in phase R ( CE ≫ CRE and CE ≫ CYE ) the displacement voltage U NE , equal to the voltage in the zero-sequence component U 0 , is calculated with the system of symmetrical 114 Short-circuit currents components based on Figure 5.12(b) j ω ∗ CE Un 1 U0 = √ ∗ ∗ 2 ∗ L ∗ C )) − j (G (ω ∗ C )) j ω ∗ 3 ∗ C 1 − (1/(3 ∗ ω 3 E D E E E (5.23) The asymmetry factor k, the system damping d and the detuning factor v can be calculated based on these assumptions: CE 3 ∗ CE GE d= ω ∗ CE (5.24a) k= v =1− 3 ∗ ω2 (5.24b) 1 ∗ LD ∗ C E (5.24c) The displacement voltage U NE , equal to the voltage in the zero-sequence component U 0 , is calculated by k Un U NE = U 0 = √ ∗ 3 v + jd (5.25) The polar plot of the displacement voltage U NE as per Equations (5.22) and (5.25) and outlined in Figure 5.13 indicates a circular plot through the zero point. The phase angle of the diameter location at v = 0 is determined by the phase angle of the capacitive asymmetry. The diameter of the polar plot is defined as per Equation (5.25) as the ratio of capacitive asymmetry k and damping d. The capacitive asymmetry is comparatively high in power systems with overhead transmission lines, resulting in a sufficient high-displacement voltage. Cable systems have a comparative small asymmetry, resulting for most of the cable systems in + Re UR + Im y=0 UY UB Figure 5.13 Polar plot of the displacement voltage in a power system with resonance earthing Influence of neutral earthing 115 an insufficient low-displacement voltage and problems while tuning the Petersencoil into resonance. Capacitors between two phases or between one phase and earth will increase the displacement voltage to the required value. 5.5.3 Tuning of the Petersen-coil ULE The Petersen-coil can be constructed as a plunger-coil (tuning-coil) with continuous adjustment of the reactance, which can be tuned into resonance by successive operation. The displacement voltage measured at the Petersen-coil is maximal in the case of resonance tuning; the value depends on the capacitive asymmetry and on the losses of the reactor. The earth-fault current will be minimal in this case and the power frequency component of the capacitive earth-fault current is compensated by the reactive current of the Petersen-coil. Figure 5.14 indicates the displacement voltage and the residual current for different tuning of the reactor. The displacement voltage shall be limited to UNE < 10 kV. It is obvious that the residual current is increased as can be seen from Figure 5.14. Residual currents above 130 A in 110-kV-systems, respectively 60 A in 10-kV-systems, are not self-extinguishing; both parameters define the tuning limits of the Petersen-coil as indicated in Figure 5.14. Tuning of the Petersen-coil can be done in such a way that the resonance circuit is either capacitive (undertuning; v < 0), resulting in an Umax ULE Unsymmetry UR UY 100% Umin ULE U0; IRes UB IRes IRes< 130 A U0 < 10 kV U0 –30% –15% 0 Max. voltage Umax Min. voltage Umin 15% Permissible tuning range V 30% Max. displacement voltage Umin Max. voltage unbalance ku Max. residual earth-fault current IRes Figure 5.14 Voltages and residual current in the case of an earth-fault; displacement voltage without earth-fault 116 Short-circuit currents ohmic-capacitive residual current or inductive (overtuning; v > 0), resulting in an ohmic-inductive residual current at the earth-fault location. A small overtuning (overcompensation) up to v = 10% is often recommended as the displacement voltage will not increase in the case of switching of lines, because the capacitances will be reduced by this and the resonance circuit will be detuned without any further adjustment. The limits for the displacement voltage and the residual current as indicated in Figure 5.14 have to be guaranteed even under outage conditions. Figure 5.14 also indicates the phase-to-earth voltages for different tuning factors (system parameters are: Un = 110 kV; ICE = 520 A; d = 3%; k = 1.2%) which also limit the range of detuning√ of the Petersen-coil. Assuming a minimal permissible voltage of Umin = 0.9 ∗ (Un / 3) according to IEC 60038, √ a maximal permissible voltage according to IEC 60071-1 of Umax = 123 kV/ 3 and a permissible asymmetry of the three voltages according to DIN EN 50160 of p = 2% it can be seen that the permissible tuning range of the Petersen-coil is v = 12–22%. All considerations carried out so far are based on a linear current-voltagecharacteristic of the Petersen-coil. √ Figure 5.15 indicates the non-linear characteristic of a Petersen-coil (Ur = 20 kV/ 3; Ir = 640 A) for minimal and maximal adjustment. Due to the non-linear characteristic, the minimum of the residual current is not achieved at the maximal displacement voltage (adjustment criteria of the Petersencoil). The difference is typically in the range of 3–15% of the rated current as outlined in Figure 5.16. 5.6 Handling of neutrals on HV-side and LV-side of transformers Special attention must be placed while selecting the type of neutral handling on HV-side and LV-side of transformers. The neutral earthing on one side of the transformer has an influence on the system performance on the other side, in case of earth-faults or single-phase short-circuits as the voltages in the zero-sequence component are transferred from one side of the transformer to the other. The neutral earthing of a 110/10-kV-transformer (vector group Yyd) according to Figure 5.17 is taken as an example. It is assumed [15] that XC0 /R0 = 0.1–0.05, first value is applied for systems with overhead lines, second value with cables. The impedances Z E1 and Z E2 as per Figure 5.17 representing the earthing are different depending on the type of neutral earthing. In case of a single-phase fault in the high-voltage system (110 kV), the voltage U0 in the zero-sequence component is transferred to the medium-voltage system (10 kV) with the same amount. Similar consideration indicates that the voltage in the zero-sequence component is transferred to the HV-side in case of a single-phase fault in the LV-system. In both cases, a fault current is measured in the system, having no fault. Table 5.2 indicates the results of a fault-analysis [16] with the voltages transferred through the transformer in case of faults. The 110/10-kV-transformer can be operated with low-impedance earthing on both sides if a third winding (compensation winding, vector group d) is available, as can be seen from Table 5.2. If the transformer is not equipped with compensation winding, Influence of neutral earthing 117 (a) 70 60 Current in A 50 40 30 20 10 0 0 2000 4000 6000 8000 Voltage in V 10,000 12,000 14,000 0 2000 4000 6000 8000 Voltage in V 10,000 12,000 14,000 (b) 800 700 Current in A 600 500 400 300 200 100 0 Figure 5.15 √ Current-voltage characteristic of a Petersen-coil; Ur = 20 kV/ 3; Ir = 640 A. (a) Minimal adjustment (50 A) and (b) maximal adjustment (640 A) the voltages in the zero-sequence component may reach values up to 70 per cent of the phase-to-earth voltage. Low-impedance earthing on the 110-kV-side and resonance earthing on the 10-kV-side should be avoided due to high voltages in the zero-sequence component, which furthermore depend on the tuning of the Petersen-coil. The maximal voltage in this case is not reached for resonance tuning but depends on the ratio XC0 /R0 . The strategy to limit the displacement voltage under normal operation conditions as per Section 5.5.2 may result in an increased displacement voltage in the 10-kV-system with resonance earthing in the case of an earth-fault in the 110-kV-system with low-impedance earthing. 118 Short-circuit currents IRest UEN ΔI IRest = f (IEN) UEN = f (IEN) Vl IEN = IDr VU Figure 5.16 Displacement voltage in non-faulted operation and residual current under earth-fault conditions; non-linear characteristic of the Petersen-coil Resonance earthing in the 110-kV-system can be combined with all types of neutral earthing in the 10-kV-system if the transformer is equipped with a compensation winding. The connection of Petersen-coils to both neutrals (110- and 10-kV) has to be investigated for special cases and is not generally recommended. The voltage transfer by stray capacitances in the case of isolated neutral in the 10-kV-system can be reduced by installing capacitances in the 10-kV-system. If the earthing of both neutrals of transformers by Petersen-coils cannot be avoided in the same substation, the earthing should be alternate in the case of two parallel transformers as indicated in Figure 5.18(a). If only one transformer is installed, the connection of one Petersencoil XD1 can be carried out directly to the transformer, the second one XD2 should be connected at an artificial neutral as per Figure 5.18(b). If the feeding system (e.g., 110 kV) is operated with low-impedance earthing and the medium-voltage system (e.g., 20 kV) is earthed through Petersen-coils or by fault limiting impedance, fault currents will occur in the medium-voltage system in the case of a single-phase short-circuit in the high-voltage system, as outlined in Figure 5.19, the value of which depends on the impedance of the earthing in the medium-voltage system. In some cases, this current may exceed the rated current of the transformer, thus causing operation of power system protection on MV-side [5,16]. Influence of neutral earthing 119 (a) 110-kV-system Transformer 10-kV-system ~ B Y ~ R ~ E ~ ~ ZE1 ZE2 k1 X1Q (b) ~ X11T C1Q U1F X12T C1 X13T 01 X1Q X11T C1Q U2F X12T C1 X13T 02 X0Q X01T + 3ZE1 ~ C0Q U0F X12T + 3ZE2 ~ X03T R0 C0 U0 00 Figure 5.17 Transformation of voltage in the zero-sequence component of transformers in the case of single-phase faults. (a) Equivalent circuit diagram in RYB-system and (b) equivalent circuit diagram in the system of symmetrical components 5.7 Examples 5.7.1 Increase of displacement voltage for systems with resonance earthing The capacitive asymmetry k of cable systems normally is below k < 0.1%; the system damping is in the range of d ≈ 2–4% resulting in a displacement voltage 120 Short-circuit currents Table 5.2 Voltages in the zero-sequence component U0 transferred through 110/10-kV-transformer in the case of single-phase fault in the 110-kVsystem according to Figure 5.17; Un : nominal system voltage 10-kV-system 110-kV-system and compensation winding of the transformer Limitation Ik1 ZE2 Low-resistance earthing ZE2 = 0  Current limitation ZE2 inductive Current limitation ZE2 ohmic Resonance earthing Isolated neutral 2000 A 500 A 2000 A 500 A Low-impedance√earthing u0 = U0 /(Un / 3) Resonance earthing With compensation winding Without compensation winding With compensation winding 0.2 0.6 0.03 0.2 0.6 0.03 0.25 0.7 0.04 0.2 0.6 0.03 0.2 0.6 0.03 <7 >10 <0.3 Voltage transfer through stray capacitances which is too low for the operation of the resonance controller. For a given capacitive asymmetry of k = 0.1% and √ system damping d = 2% the displacement voltage detuning shall will be UNE = 0.005 ∗ Un / 3 for resonance tuning (v = 0%); if the √ be v = 5% the displacement voltage will be UNE = 0.002 ∗ Un / 3 only [17]. Resonance controller normally operates sufficiently if the displacement voltage is √ above UNE > 0.03∗Un / 3. The displacement voltage, therefore, had to be increased by installing an additional capacitor in one phase [18]. The required capacitance CE for different parameters is given in Table 5.3 for a 20-kV-system earthed through Petersen-coil. Documentation of system data normally do not indicate exact values of the lineto-earth capacitances CE in each phase, furthermore the system damping d, the exact length of the cables and the non-linear characteristic of the Petersen-coil are also unknown or only to an insufficient extent and are not suitable to determine the displacement voltage UNE without measurement. It should be noted that the system damping changes with the system load as well as in the case of a power system with a significant number of overhead lines and with external climatic conditions. It can be deducted from this, that: • • • • the asymmetrical capacitance (absolute value) the angle of the asymmetrical capacitance (with respect to the three phases) the value of the displacement voltage, and the resonance curve for different detuning factors Influence of neutral earthing 121 (a) XD1 110 kV 10 kV XD2 (b) 110 kV 10 kV XD1 Figure 5.18 XD2 Alternate earthing of transformer neutrals by Petersen-coils. (a) Two parallel transformers and (b) earthing at artificial neutral with reactor XD2 T1 MV-system e.g., 20 kV Feeding system e.g., 110 kV k1 T2 Z0; Z1; Z2 Currents in the positive-, negative- and zero-sequence system Figure 5.19 Fault current in the MV-system in the case of a short-circuit in the HV-system 122 Short-circuit currents Table 5.3 Capacitive asymmetry CE for different parameters in a 20-kV-system UNE = U0 (V) Damping d (%) Detuning v (%) Asymmetry k (%) CE (nF) 346.4 2 4 6 4 6 0.134 0.19 0.17 0.216 177 251 225 285 4 6 4 6 0.224 0.316 0.283 0.361 296 417 374 477 4 577.4 2 4 0.9 0.8 05.08.98; 11:42 till 11:57 Uhr 02.07.98; 22:10 till 22:21 Uhr 12.07.98; 15:51 till 16:04 Uhr + Calculation Displacement voltage in V 0.7 0.6 0.5 0.4 + +++ + + + 0.3 0.2 0.1 + ++ + + + + + + + + + + + 0 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 Reactor current in A Figure 5.20 + + + Resonance curve (displacement voltage) for different detuning factors in a 20-kV-system for different conditions cannot be determined from system studies, but require measurement for different load conditions. The resonance curves of a 20-kV-system with total cable length of 176 km as measured for different load conditions are outlined in Figure 5.20. Furthermore, the resonance curve calculated from documented system data is also given in Figure 5.20. Voltages√refer to the secondary side of a voltage transformer in the neutral (ratio 20 kV/ 3 : 100 V). The maximal value of each of the resonance curves differ by Line-to-earth voltages in kV Influence of neutral earthing 123 12.2 U phase R 12.1 12.0 U phase Y 11.9 U phase B 11.8 11.7 11.6 11.5 11.4 11.3 11.2 11.1 11.0 10.9 10.8 250 275 300 325 350 375 400 425 450 475 500 525 550 575 600 625 Reactor current in A Figure 5.21 Voltages in a 20-kV-system with resonance earthing for different tuning factors. (a) Phase-to-earth voltages and (b) displacement voltage (resonance curve) more than 60 per cent for different load conditions and is higher than the calculated value. The resonance tuning (v = 0) of calculated and measured resonance curves differs also by 6 per cent as can be seen from Figure 5.20. A capacitance of CE = 173.3 nF was installed in phase B in order to increase the displacement voltage up to 3–5 per cent (350–580 V) of the nominal system voltage for resonance tuning. The total phase-to-earth capacitance of the 20-kV-system was determined to be CE = 44 μF. The results of measurement of the phase-to-earth voltages and the displacement voltage for different detuning √ of the Petersen-coil are outlined in Figure 5.21 (voltage transformer ratio 20 kV/ 3 : 100 V). It can be seen from Figure 5.21 that the maximal displacement voltage is in the required range between 3 and 5 per cent of the phase-to-earth voltage. For resonance tuning, the maximal phase-to-earth voltage appears in phase R with UR ≈ 12.1 kV and the minimal voltage in phase Y with UY ≈ 10.9 kV, which is only 94 per cent of the nominal phase-to-earth voltage. Exact resonance tuning shall be avoided in this system due to the low voltage in one phase and the resulting high asymmetry factor. Other measures to increase the displacement voltage such as installation of a reactor in one phase to earth and voltage additions are not considered in detail here [19]. 5.7.2 Limitation of single-phase short-circuit current by earthing through impedance An urban 11.5-kV-system is fed from a 132-kV-system; both systems are pure cable systems. The substations are equipped with four transformers each, having rated values of Sr = 40 MVA, ukr1 = 14% and ukr0 = 16%. Both systems are earthed 124 Short-circuit currents by low impedance in such a way that all transformer neutrals are solidly connected to earth. The short-circuit current level in the 132-kV-system is high, whereas the single-phase short-circuit currents is higher than the three-phase short-circuit currents  ≈ 29.3 kA; I  ≈ 37.3 kA). The maximal permissible short-circuit current in (Ik3 k1   the 132-kV-system is Ikmax = 25 kA. The = 40 kA; in the 11.5-kV-system Ikmax 132/11.5-kV-transformers cannot be operated in parallel due to the high short-circuit currents. In the case of low-impedance earthing the neutrals of each transformer, the  = 15.04 kA in case of a single-phase short-circuit current of one transformer is Ik1 short-circuit at the 11.5-kV-busbar. In the case of two transformers in parallel, the  = 29.27 kA, which is above the maximal short-circuit current is increased to Ik1 permissible short-circuit current of the 11.5-kV-system. The limitation of single-phase short-circuit currents to 25 kA in case two transformers shall be operated in parallel is possible by earthing of the 11.5-kV-transformer neutrals through a resistor having RE = 0.31  or through a reactor having XE = 0.1  (see also Figure 11.13). 5.7.3 Design of an earthing resistor connected to an artificial neutral The short-circuit limitation in a 20-kV-system having initial short-circuit power  = 700 MVA and an impedance ratio Z /Z = 4 is explained below. The singleSkQ 0 1  = 12.1 kA. The phase short-circuit current in case of low-impedance earthing is Ik1  = 3I )  single-phase short-circuit current shall be limited to Ik1max = 1.5 kA (Ik1 0 realised by earthing through a resistor to be connected to an artificial neutral. As the current through the artificial neutral is only one-third of the single-phase short-circuit current, the rated power shall be √  SrS min = 0.33 ∗ 3 ∗ Ik1 max ∗ Un = 17.55 MVA A transformer with vector group Zz is selected for the artificial neutral with SrS = 20 MVA; PCu = 1.3 kW and uk0 = 45% resulting in a required zero-sequence impedance of Z0S = 9  (R0S = 3.75 ; X0S = 8.18 ). The required rating of the earthing resistor resulting from the calculation is RE = 4.21 . The value of the initial short-circuit power of the system has only a marginal effect on the rating of the earthing. A typical design rating of the resistor is given below: Rn = 4.21  at 20◦ C (Tolerance ±5 per cent or ±10 per cent); CrNi-alloyed steel Ir = 1.5 kA, rated short-time duration t = 5 s or 10 s Ur = 13.3 kV Isolation according to IEC 60071-1, Table 5.2: Um = 17.5 kV IP 00 5.7.4 Resonance earthing in a 20-kV-system Figure 5.22 shows a 20-kV-system fed from two sides by one transformer in each of the substations S/S A and S/S B. The system is split at S/S C into two subsystems A and B during summer months. During winter months, a part of system A is connected to system B, but both systems are still operated separately. Influence of neutral earthing 125 S/S C 300 A Figure 5.22 S/S B System B 110 kV 190 A System A 60–590 A S/S A 50–500 A 110 kV 6.4 MW Equivalent circuit diagram of a 20-kV-system with resonance earthing The 20-kV-system A is a pure cable-system having a total system length of 490 km of the XLPE-type. The capacitive earth-fault current is calculated to be Ires = 453 A. The transformer in substation A has a rating of 12.5 MVA; current carrying capacity of the neutral is 361 A. The system shall be operated with resonance earthing, i.e., a reactor has to be installed in the neutral having a rated current of more than 450 A to compensate the capacitive earth-fault current. It is obvious that the reactor cannot be connected to the neutral of the transformer in substation S/S A as the required current for resonance earthing exceeds the permissible current of the transformer neutral. An additional fixed reactor with rated current 300 A is installed in substation S/S C and connected at an artificial neutral of a Zz-transformer. System B is a pure cable-system as well, having a total system length of 386 km of different type (XLPE and mass-impregnated cables); the earth-fault current is calculated to be Ires = 632 A. The feeding transformer in substation B has a rated power Sr = 25 MVA and a current carrying capacity of the neutral of 721 A. Resonance earthing is done with a fixed reactor (190 A) in parallel with a tuning-reactor (60–590 A) capable of compensating the total capacitive earth-fault current of system B. Operation in wintertime differs from the described scheme as additional generation in a combined-cycle plant is in operation with a power of 6.4 MW. In order to avoid back-feeding into the 110-kV-system additional load from system A is supplied from system B. The capacitive earth-fault current of system A is reduced and the current in system B is increased accordingly (see Table 5.4 for details). As the earthing reactor in S/S C is connected in wintertime as well to system B, the compensation scheme with different reactors at different substations are capable of realising the resonance earthing for both systems under different operating conditions. 5.7.5 Calculation of capacitive earth-fault current and residual current A 10-kV-system with isolated neutral (overhead lines, system length 170 km, CB = 9.5 nF/km; CE /CL = 5) shall be extended by cables. The existing earthing 126 Short-circuit currents Table 5.4 Condition Characteristics of a 20-kV-system with respect to resonance earthing System A System B Ires (A) Available reactors Ires Available reactors Summertime 453 30–300 A S/S A 300 A S/S C 721 A 60–590 A S/S B 190 A S/S B — Wintertime 261 30–300 A S/S A — 913 A 60–590 A S/S B 190 A S/S B 300 A S/S C concept shall be checked with respect to its suitability. The phase-to-earth capacity is calculated as CE = 1009 μF and the earth-fault current is given according to Equation (5.9) to be IE = 6.05 A which is self-extinguishing as can be seen in Figure 5.7. The capacitive earth-fault current is increased by 1.42 A/km if cables of the NAKBA-type will be installed (CE cable /CE OHL = 40) reaching the permissible limit for self-extinguishing ICE = 35 A for a cable length of 23 km. If the system earthing shall be changed to resonance earthing, the Petersen-coil shall have a reactance for resonance tuning (v = 0) of XD = 165 , the inductance will be LD = 0.525 H for 50 Hz. The resistance of the reactor is assumed to be RD = 6 k (parallel equivalent diagram). The residual current is given by IRes = 2.9 A. The ratio of residual current to capacitive current is IRes /ICE = 8.3 per cent. 5.7.6 Voltages at neutral of a unit transformer A power station with rated power 400 MVA is connected to a 220-kV-system. The neutral of the unit transformer can be earthed either through an impedance (reactor), directly without impedance or kept isolated without earthing as outlined in Figure 5.23. The rating of the reactor shall be determined in such a way to guarantee a ratio X0 /X1 = 2 in case of a short-circuit at location F. The single-phase short-circuit G A T1 F GS 3~ Un = 220kV Us S2 S1 Xs T2 Q UnQ = 380 kV Figure 5.23 Connection of a power station to a 220-kV-system with short-circuit location Influence of neutral earthing 127 current and the voltage at the transformer neutral shall be calculated for the different operating conditions. The rated data of the equipment are given below:  = 15,000 MVA; X /X System Q UnQ = 380 kV; SkQ 0Q 1Q = 3 System A G T1 T2  = 5,000 MVA; X /X UnQ = 220 kV; SkQ 0A 1A = 3  = 15%; SrG = 400 MVA; UrG = 21 kV; xd1 cos ϕrG1 = 0.8; pG1 = 10% SrT1 = 400 MVA; ukrT1 = 14%; UrT1HV /UrT1LV = 220 kV/21 kV; pT1 = 12% SrHVT2 = 660 MVA; SrMVT2 = 660 MVA; SrLVT2 = 198 MVA ukrHVMVT2 = 10.2%; ukrHVLVT2 = 13.5%; ukrMVLVT2 = 10.5% UrHVT2 = 380 kV; UrMVT2 = 220 kV; UrLVT2 = 30 kV; pT2 = 10% Line L X0T2 /X1T2 = 1 (three single-phase transformers)  = 0.3 /km; X  = 1.0 /km; l = 10 km X1L L 0L The impedances of the equipment calculated in the -system are given below. No. Equipment X1 () X0 () 1 2 3 4 3+4 System Q System A Generator G Transformer 1 Power station 10.595 3.532 18.15 16.94 35.09 42.38 10.596 5 Line 3.0 16.94 16.94 +3XS 10.0 Correction X1K as per () Table 3.3 X0K () 10.595 42.38 3.532 10.596 1.093 38.35 3.0 From right 18.681 From left 16.94+ 3Xs 10.0   Ik1 Ik3 (kA) (kA) 128 Short-circuit currents No. Equipment X1 () X1 () 6 7.422 7.422 Transformer 2 HV MV LV Correction X1K as per () Table 3.2 HV-MV 0.985 0.3436 0.3436 MV-LV 0.983 25.59 25.59 HV-LV 0.967 Total impedance at 220 kV (X0 /X1 = 2)  Ik3 (kA) X0K () 7.023 7.023 0.399 0.399  Ik1 (kA) 25.586 25.586 6.945 13.89 !! 18.29 15.09 X0A X0T1 XL X0MVT2 Us S2 X0HVT2 X0HVT2 S1 X0LVT2 3Xs Figure 5.24 Equivalent diagram in the zero-sequence component for fault location F It should be noted that the impedance of the earthing reactor appears threefold (X0S = 3XS ) in the zero-sequence component. As the rating of the reactor shall be determined to guarantee the ratio X0 /X1 = 2 for short-circuit at location F the single = 15.09 kA. By this the impedance of the reactor phase short-circuit current is Ik1 will be XS = 12.4 . In order to calculate the voltage U S at the transformer neutral while earthed with the reactor, the zero-sequence current through the reactor I 0S needs to be calculated as outlined in Figure 5.24 indicating the equivalent diagram in the zero-sequence component. The zero-sequence current through the reactor is determined by the ratio of the impedances I 0S = I  13.89  15.09 kA X0k X0k ∗ = 1.29 kA ∗ I0 = ∗ k1 = X0left X0left 3 54.16  3 Influence of neutral earthing 129 The voltage across the reactor USe at the transformer neutral is calculated by U Se = I 0S ∗ 3 ∗ XS = 1.29 kA ∗ 3 ∗ 12.41  = 48.03 kV In this case, the transformer neutral is kept isolated (S1 and S2 open); the zerosequence current through the reactor will be Zero. The voltage is determined by the zero-sequence current determined by the remaining equipment (see Figure 5.24). The zero-sequence impedance is X0 = 18.681 . The single-phase short-circuit current without earthing is calculated by √ √ 1.1 ∗ 3 ∗ 220 kV 1.1 ∗ 3 ∗ Un  = = 12.87 kA I k1 = X0 + 2 ∗ X 1 18.681  + 2 ∗ 6.945  The voltage across the reactor U Si is calculated by I k1 12.87 kA ∗ X0 = ∗ 18.681  = 80.14 kV 3 3 The insulation of the transformer neutral must be designed for the maximal voltage, i.e., 80.14 kV. U Si = Chapter 6 Calculation of short-circuit currents in low-voltage systems 6.1 General IEC 60781 presents an application guide for the calculation of short-circuit currents in low-voltage radial systems. The methods described there are identical to those as per IEC 60909-0 and as outlined in Chapter 3. The short-circuits are treated as far-from-generator short-circuits. This assumption is valid in the future as well, even with an increasing number of distributed generation units in low-voltage systems. New generation will be connected to the system in the case of • Photovoltaic installations by rectifier (six-pulse bridge or PWM-rectifier). • Small wind turbines, low-rated combined heat and power units and small hydro power plants by asynchronous generators (rotor fed). Installations with synchronous generators are comparatively rare. The following chapters describe the approach and special conditions for the calculation of short-circuit currents in low-voltage systems. 6.2 Types of faults Depending on the type of protection against electrical shock in low-voltage systems all types of short-circuit, i.e., three-phase, double-phase with and without earth connection and single-phase-to-earth short-circuits can occur. The maximal short-circuit current depends on the impedances of the positive- and zero-sequence component. Reference is made to Figure 4.4. The ratio Z2 /Z1 can be set to 1, as low-voltage systems for the most part have no generation by synchronous generators. The threephase short-circuit will lead in those cases to the maximal short-circuit current. Special attention must be given to the currents flowing through earth, as the phase angles of the impedances in the positive- and zero-sequence components differ a lot from each other in low-voltage systems. 132 Short-circuit currents 6.3 Method of calculation The method of the equivalent voltage source at the short-circuit location is applied for the calculation of short-circuit currents in low-voltage systems. • • • • • • Symmetrical short-circuits are represented by the positive-sequence component, asymmetrical (unbalanced) short-circuits are represented by connection of positive-, negative- and zero-sequence components (see also Table 2.1). Capacitances and parallel admittances of non-rotating load of the positivesequence component are neglected. Capacitances and parallel admittances of the zero-sequence component have only an influence on fault currents in power systems with isolated neutral or with resonance earthing. Impedance of the arc at the short-circuit location is neglected. The type of short-circuit and the system topology remain unchanged during the duration of the short-circuit. The tap-changer of any transformer is assumed to be in main-position. All internal√voltages are short-circuited and an equivalent voltage source with value cUn / 3 is introduced at the short-circuit location. The voltage factor c shall be selected in accordance with Table 6.1. 6.4 Calculation of short-circuit parameters 6.4.1 Impedances Calculation of impedances of equipment and the analysis of the short-circuit impedance at short-circuit location was explained in Sections 2.5 and 3.2. It should be noted that the impedances of the equipment must be related to the voltage level of the short-circuit location. Table 6.1 Voltage factor c according to IEC 60909-0. (Voltage factors as per IEC 60781 are of different values. The standard is under review) Nominal system voltage Un LV: 100 V up to 1000 V (inclusive) (IEC 60038, Table 1) Voltage tolerance +6% Voltage tolerance +10% Voltage factor c for calculation of Maximal short-circuit current, cmax Minimal short-circuit current, cmin 1.05 1.10 0.95 0.95 Remark: cmax Un shall not exceed the highest voltage of equipment Um according to IEC 60071 Calculation of short-circuit currents 133 When data for generation in LV-systems are not known, approximation as below shall be used for the branch short-circuit currents [12]: Synchronous generator Asynchronous generator Generator with rectifier Branch short-circuit current equal to eight times rated current Branch short-circuit current equal to six times rated current Branch short-circuit current equal to rated current This approximation does not include the effect of conductors between the generation unit and the short-circuit location. 6.4.1.1 Initial symmetrical short-circuit current Ik The initial symmetrical short-circuit current Ik is calculated for balanced and unbalanced short-circuits based on the equivalent voltage source at the short-circuit location. The short-circuit impedance seen from the short-circuit location has to be determined with the system of symmetrical components. The results obtained for the short-circuit currents (and the voltages of the non-faulted phases, if required) in the 012-system have to be transferred back into the RYB-system. The results for the different types of short-circuits are outlined in Table 4.2. 6.4.1.2 Peak short-circuit current ip Depending on the feeding source of the short-circuit, different considerations have to be taken to calculate the peak short-circuit current. Short-circuits in low-voltage systems normally are single-fed short-circuits. The short-circuit impedance is represented by a series connection of the individual impedances. The peak short-circuit current can be calculated for the different types of short-circuit by √  ip3 = κ ∗ 2Ik3 (6.1a) √  ip2 = κ ∗ 2Ik2 (6.1b) √  ip1 = κ ∗ 2Ik1 (6.1c) The factor κ κ = 1.02 + 0.98 ∗ e−3R/X (6.2) obtained from the ratio R/X for three-phase short-circuit shall be taken for all types of short-circuits as well. All other assumptions as per Section 4.3.2.3 are valid in low-voltage systems as well. 6.4.2 Symmetrical short-circuit breaking current Ib Short-circuits in low-voltage systems normally are far-from-generator short-circuits. The symmetrical short-circuit breaking current is identical to the initial symmetrical short-circuit current. 134 Short-circuit currents 6.4.3 Steady-state short-circuit current Ik Short-circuits in low-voltage systems normally are far-from-generator shortcircuits. The steady-state short-circuit current is identical to the initial symmetrical short-circuit current. 6.4.3.1 Influence of motors Asynchronous motors contribute to the initial symmetrical short-circuit current, to the peak short-circuit current, to the symmetrical short-circuit breaking current and in the case of unbalanced short-circuits to the steady-state short-circuit current as well. Synchronous motors are modelled like generators and asynchronous generators are treated as asynchronous motors. Motors of any kind, which are not in operation at the same time, e.g., due to the process or due to any interlocking, can be neglected for the calculation of short-circuit current to such an extent that only those motors are to be taken into account which lead to the highest contribution of the short-circuit current under realistic operating conditions. Motors fed by static-rectifiers need to be considered in the case of three-phase short-circuits only if they are able to transfer energy for deceleration at the time of short-circuit, as they contribute to the initial symmetrical and to the peak short-circuit current. Asynchronous motors in public supply systems are considered when • • the sum of the rated currents is greater than 1 per cent of the initial symmetrical short-circuit current without motors; the contribution to the initial symmetrical short-circuit current is greater or equal to 5 per cent without motors. Medium-and low-voltage motors connected through two-winding transformers to the short-circuit are considered if  0.8 PrM  (6.3) > √  SrT |(c100 SrT /( 3UnQ /Ik )) − 0.3| The influence of asynchronous motors in low-voltage systems can be neglected if  IrM ≤ 0.01 ∗ Ik (6.4)  SrT is the where UnQ is the nominal system voltage at short-circuit location Q, sum of rated apparent power of all transformers, directly connected to motors feeding the short-circuit, Ik is the initial symmetrical short-circuitcurrent without motors,  PrM is the sum of rated active power of all motors and IrM is the sum of rated currents of all motors. 6.5 Minimal short-circuit currents In order to calculate the minimal short-circuit current the voltage factor cmin according to Table 6.1 for the equivalent voltage source at the short-circuit location has to be Calculation of short-circuit currents 135 considered. Furthermore, • System topology, generator dispatch and short-circuit power of feeding networks have to be defined in such a way that the minimal short-circuit current is expected. This normally applies for low-load conditions. • Motors are to be neglected. • Resistances of overhead lines and cables shall be calculated with the maximal permissible temperature at the end of the short-circuit, e.g., 80◦ C in low-voltage systems. These assumptions have to be made in the case of balanced and unbalanced shortcircuits, except when other presuppositions are mentioned. 6.6 Examples Examples for the calculation of short-circuit currents in LV-systems are included in IEC 60781. The calculation is carried out with form-sheets, which are used for the calculation of impedances of equipment as well as for short-circuit current calculation itself. The voltage factor cmax = 1.0 as given in the examples shall be cmax = 1.05 or cmax = 1.1 according to IEC 60909-0. Reference is made to Table 6.1. Short-circuit current calculation can easily be carried out with spreadsheet analysis using, e.g., EXCEL [14]. Figure 6.1 outlines an example for a low-voltage installation. The initial symmetrical and the peak short-circuit current both for minimal and maximal conditions shall be calculated for short-circuit either at location A or at location B. The data of the equipment are given below: System feeder Transformer Cable Motor   Un = 10 kV; SkQmax = 190 MVA = 240 MVA; SkQmin SrT = 630 kVA; ukrT = 6%; urRT = 1.1%; trT = 10/0.4 kV; R0 /R1 = 1; X0 /X1 = 1  = 77.4 m/km; X  = 78 m/km; Each 4 × 240 mm2 ; RK K R0 /R1 = 4; X0 /X1 = 4.1; l = 35 m PrM = 50 kW; UrM = 0.41 kV; cos ϕrM = 0.84; ηrM = 0.94; IanM /IrM = 6 A B 35 m UnQ = 10 kV Q Un = 0.4 kV ± 6% Figure 6.1 Equivalent circuit diagram of a LV-installation M 3~ Table 6.2 Example for the calculation of maximal short-circuit currents in LV-system Data Input Low voltage Nominal voltage in kV cmax/cmin System feeder Pos. seq. system S ⬙kQmax in MVA S ⬙kQmin in MVA Transformer SrT in kVA HHV-side LV-side Pos. seq. system u1kT in % u1rRT in % Zero seq. system u0kT in % u0rRT in % Cable Length in m Cables in parallel Max. temp. °C Pos. seq. system X1⬘ in mΩ/km R1⬘ in mΩ/km Zero seq. system X0⬘ in mΩ/km R0⬘ in mΩ/km 0.4 1.1 R mΩ 240 190 0.0421 0.0333 X mΩ 0.4203 0.3328 Z1 mΩ Z0 mΩ 0.4225 0.3345 s.-c. at location A 630 10 0.4 I ⬙k3min kA 15.2381 6 1.1 2.7937 6 1.1 2.7937 15.493 15.2381 15.97 I ⬙k2min kA ip3 kA Rk/Xk 0.182 13.83 35.86 ip2 kA 31.83 I ⬙kE2E kA 16.25 ipE2E kA 36.49 I ⬙k1max kA 16.11 ip1 kA 36.18 15.493 s.-c. at location B 35 3 80 I ⬙k3min kA 0.91 78 77.4 0.903 319.8 309.6 3.612 1.282 3.731 14.78 ip3 kA Rk/Xk 0.226 31.72 I ⬙k2min kA 12.8 ip2 kA 27.47 I ⬙kE2E kA 13.02 i pE2E kA 27.95 I ⬙k1max kA 13.84 ip1 kA 29.7 5.193 Branch s.-c. current of motor Motor Active power in kW Ur in V cos h Ia/Ir Zero seq. Imp. in mΩ Rated current Assessment of motors Assessment of motors 50 410 0.84 0.94 6 99999999 171.34 407.93 442.46 I ⬙k3max kA 0.58 0.42 1.07 I ⬙k2max kA 0.51 ip2 kA 0.93 Branch s.-c. current of motor to be neglected 99999999 Ampere 1% of s.-c. current in Ampere 5% of s.-c. current in Ampere ip3 kA Rk/Xk 89.17 147.8 739 I ⬙kE2E kA 0.01 ipE2E kA 0.02 I ⬙k1max kA 0.01 ip1 kA 0.02 Table 6.3 Example for the calculation of minimal short-circuit currents in LV-system Input data Low voltage Nominal voltage in kV cmax/cmin System feeder Pos. seq. system S ⬙kQmax in MVA2 S ⬙kQmin in MVA1 Transformer SrT in kVA HV-side LV-side Pos. seq. system u1kT in % u1rRT in % Zero seq. system u0kT in % u0rRT in % Cable Length in m Cables in parallel Max. temp. °C Pos. seq. system X1⬘ in mΩ/km R1⬘ in mΩ/km Zero seq. system X0⬘ in mΩ/km R0⬘ in mΩ/km 0.4 0.95 R mΩ X mΩ Z1 mΩ 240 0.0421 0.4203 0.4225 190 0.0333 0.3328 0.3345 Z0 mΩ s.-c. at location A 630 10 0.4 6 1.1 2.7937 6 1.1 2.7937 15.2381 15.493 15.2381 I ⬙k3min kA Rk/Xk ip3 kA I ⬙k2min kA ip2 kA I ⬙kE2E kA ipE2E kA I kmin ⬙ kA ip1 kA 13.78 0.182 30.87 11.84 26.81 14.04 31.53 13.81 31.24 I ⬙k3min kA Rk/Xk ip3 kA I ⬙k2min kA ip2 kA I ⬙kE2E kA ipE2E kA I ⬙k1min kA ip1 kA 12.64 0.239 26.79 10.95 23.21 10.97 23.25 11.75 24.9 15.493 s.-c. at location B 35 3 80 78 77.4 1.1198 319.8 309.6 4.4789 0.91 3.731 1.443 5.83 138 Short-circuit currents The calculation is carried out with EXCEL; the spreadsheet is shown in Tables 6.2 and 6.3. Data for the calculation of minimal short-circuit currents are automatically transferred; results are highlighted in the tinted boxes. All fields, except the input fields, are blocked against unintentional modification. Chapter 7 Double earth-fault and short-circuit currents through earth 7.1 General IEC 60909-3 describes methods and procedures for the calculation of currents during two separate simultaneous single-phase line-to-earth short-circuits (s.-c.) at different locations of the system, which are called ‘double earth-fault’ in the context of this section. The double earth-fault is not identical to a double-phase short-circuit, where two phases have a short-circuit at the same location. Furthermore, the branch short-circuit currents flowing through earth are dealt with. 7.2 Short-circuit currents during double earth-faults 7.2.1 Impedances and initial symmetrical short-circuit current Ik  in the case of a double earth-fault, In order to calculate the short-circuit currents IkEE the mutual impedance in the positive- and zero-sequence component between the two short-circuit locations is needed. As the mutual impedance comparatively difficult to determine, the double earth-fault can only be analysed in a simple manner for special system configurations. The following cases are considered: • • • • Both short-circuit locations are on the same line. The short-circuit locations are on different lines. Single-fed line. Double-fed line. In the case of a single-fed (radial) line, both short-circuit locations are on the same line and the double earth-fault is identical to a double-phase short-circuit without earth connection, as seen from the feeding point of the line. In the case of a double-fed 140 Short-circuit currents single-circuit line, the voltage line-to-earth is changing significantly between the two short-circuit locations, whereas the line-to-line voltages are remaining almost unchanged. Details are outlined in [3]. In general, the short-circuit current in the case of a double earth-fault with shortcircuit locations A and B is calculated according to [4] by  IkEE = 3 ∗ c ∗ Un |Z 1A + Z 2A + Z 1B + Z 2B + M 1 + M 2 + Z 0 | (7.1) where Z 1A ; Z 1B are the short-circuit impedances in the positive-sequence system at location A and B, respectively, Z 2A ; Z 2B the short-circuit impedances in the negative-sequence system at location A and B, respectively, M 1 ; M 2 the mutual impedances in the positive-sequence system between the short-circuit locations A and B, respectively, and Z 0 the short-circuit impedance in the zero-sequence system between locations A and B. The impedance M 1 and M 2 , representing the mutual impedances of the positiveand negative-sequence components between the two short-circuit locations, can be measured by short-circuiting all voltages in the system and feeding the voltage U 1A (positive-sequence component), respectively the voltage U 2A (negative-sequence component), at short-circuit location A. The mutual impedances M 1 and M 2 are calculated using the voltage U 1B at short-circuit location B and the current I 1A at short-circuit location A by M1 = U 1B I 1A (7.2a) M2 = U 2B I 2A (7.2b) In case feeding shall be carried out at location B, the mutual impedances given are obtained by the voltage U 1A at short-circuit location A and the current I 1B at shortcircuit location B as below: M1 = U 1A I 1B (7.3a) M2 = U 2A I 2B (7.3b) 7.2.2 Power system configurations In the case of far-from-generator short-circuits the impedances in the positive- and negative-sequence components Z 1 = Z 2 and M 1 = M 2 are equal. Table 7.1 outlines simple systems configurations in accordance with IEC 60909-3. Table 7.1 System configurations and equations for the calculation of short-circuit currents in the case of double earth-faults Single-fed radial line Both short-circuit locations on the same line (circuit) d  = IkEE f 3 ∗ c ∗ Un |6 ∗ Z 1d + 2 ∗ Z 1f + Z 0f | d: Impedance to short-circuit location A f: Impedance between short-circuit locations A and B B A Two single-fed radial lines Short-circuit locations on different lines (circuits) d g  = IkEE d: Impedance of system feeder including busbar connection g: Impedance between busbar and short-circuit location A h: Impedance between busbar and short-circuit location B A B h 3 ∗ c ∗ Un |6 ∗ Z 1d + 2 ∗ Z 1g + Z 1h + Z 0g + Z 0h | Table 7.1 Continued Double-fed line Both short-circuit locations on the same line (circuit) d System feeder left f A  = IkEE e B System feeder right 3 ∗ c ∗ Un |(6 ∗ Z 1d ∗ Z 1e + 2 ∗ Z 1f (Z 1d + Z 1e ))/(Z 1d + Z 1f + Z 1e ) + Z 0f | d: Impedance from left till short-circuit location A e: Impedance from right till short-circuit location B f: Impedance between short-circuit locations A and B Earthing impedances in the switchyard and at the overhead tower can be neglected. The voltage factor c shall be selected in accordance to Table 4.1. Indices: 0, 1 and 2: zero-, positive- and negative-sequence components. d, e, f, g, h: length of the line as indicated in the drawing of the first column. Double earth-fault and short-circuit currents 143 7.2.3 Peak short-circuit current ip The calculation of peak short-circuit current is carried out in the same manner as described in Section 4.3.2.3. The peak short-circuit current is calculated by √  ipEE = κ ∗ 2 ∗ IkEE (7.4) The factor κ shall be the maximum of the factors obtained for three-phase short-circuit at location A or B. κ = MAX{κA ; κB } (7.5) For explanations and calculation method of quantities reference is made to Chapter 4. 7.2.4 Symmetrical short-circuit breaking current Ib and steady-state short-circuit current Ik In the case of far-from-generator short-circuits, the symmetrical short-circuit breaking current and the steady-state short-circuit current are identical to the initial symmetrical short-circuit current. In other cases, reference is made to Chapter 4. 7.3 Short-circuit currents through earth 7.3.1 Introduction Branch short-circuit currents can flow through earth in the case of unbalanced shortcircuits with earth connection, i.e., line-to-earth (single-phase) short-circuit and double-phase short-circuit with earth connection. Single-phase short-circuits are the dominating fault type in power systems with earthed neutrals and are leading to the  flowmaximal branch short-circuit currents flowing through earth. The current Ik1 ing through earth is equal to three-times the current in the zero-sequence component flowing towards the short-circuit location. Type, number and arrangement of earth conductors of overhead lines, the installation of counterpoise, shielding, armouring and sheaths of cables, and their connection to the earthing grid of the switchyard determine the part of the short-circuit current that will flow through the earthing installations. This part is described by means of the reduction factor pE , sometimes represented as r. The reduction factor is defined as the ratio of branch short-circuit current I Etot flowing through earth to the total short-circuit current 3I 0 , which can be described by the ratio of impedances pE = I Etot Z = 1 − LE 3I 0 ZE (7.6) where Z E is the impedance of earth conductor with earth return, Z LE is the mutual impedance between earth and line conductor with common earth return, I Etot is the branch short-circuit current through earth and I 0 is the total zero-sequence short-circuit current. 144 Short-circuit currents The loop-impedance Z E of the earth conductor and earth return is given by    μ0 μ0 δ μr   ZE = R + ∗ω+j ∗ ω ∗ ln + (7.7) 8 2π r 4 The mutual impedance Z LE of the loop earth conductor and conductor with earth return is given by   μ0 μ0 δ  Z LE = (7.8) ∗ω+j ∗ ω ∗ ln 8 2π dLE where r is the radius of earth conductor, μ0 is the absolute permeability, μr is the relative permeability, ω is the angular frequency, R  is the resistance of earth wire per √ unit length, δ is the depth of the earth return path δ = 1.85/ ω ∗ μ0 /ρE , ρE is the resistivity of soil depending on soil conditions and dLE is the distance between the earth conductor and phase conductor. Equations for the calculation of the impedances Z E and Z LE are also given in [1,6]. 7.3.2 Short-circuit inside a switchyard Figure 7.1 outlines the equivalent circuit diagram of a power system (HV) with shortcircuit inside the switchyard B. All quantities are defined according to Figure 7.1. The single-phase short-circuit current is calculated using I k1 = 3 ∗ I 0A + 3 ∗ I 0B + 3 ∗ I 0C (7.9) The total current through the earth grid at location B is (7.10) I ZB = pA ∗ 3 ∗ I 0A + p C ∗ 3 ∗ I 0C (I–pA)3I0A (I–pC)3I0C 3I0A 3I0B 3I0B 3I0C I 0K1 A ZEA IZA B UEB pA3I0A Figure 7.1 Earthwire C ZEB IZB ZEC IZC pC3I0C Earth Equivalent circuit diagram with short-circuit inside switchyard B Double earth-fault and short-circuit currents 145 The potential at the earth grid is then (7.11) U EB = Z EB ∗ I ZB with the earthing impedance of the switchyard Z EB = 1  1/RE + 1/Z P (7.12) where R E is the resistance of the earth grid and Z P is the driving point impedance (impedance of earth conductor with earth return and earthing impedance of overhead towers, respectively, input impedance of shielding, sheaths and armouring of cables). The considerations mentioned above are only valid when the short-circuit location (switchyard B) is far away from other switchyards (A and C in Figure 7.1). The current through earth is lower when the distance to the short-circuit is lower than the far-from-station distance dF defined as dF = 3 ∗ RTo ∗ dTo Re{ Z E } (7.13) where RTo is the footing resistance of tower, dTo is the distance between two towers and Z E is the impedance of earth conductor with earth return. 7.3.3 Short-circuit at overhead-line tower Figure 7.2 outlines the equivalent circuit diagram of a power system with short-circuit outside the switchyard (distance d > dF , see Equation (7.13)). The single-phase short-circuit current is calculated by I k1 = 3 ∗ I 0A + 3 ∗ I 0B + 3 ∗ I 0C (7.14) The branch current through the earthing of the tower at short-circuit location is I ZF = pC ∗ (3 ∗ I 0A + 3 ∗ I 0C ) + p C ∗ 3 ∗ I 0C = pC ∗ I k1 (7.15) and the potential at the earth grid U EF = Z EF ∗ I ZF (7.16) with the earthing impedance of the installation Z EF = 1 1/RTo + 2/Z P (7.17) where RTo is the footing resistance of tower and Z P is the driving point impedance (impedance of earth conductor with earth return and earthing impedance of overheadline towers, respectively, input impedance of shielding, sheaths and armouring of cables). 146 Short-circuit currents (I–pA)3I0A (I–pC)3I0A + 3I0B 3I0A (I–pC)3I0C Earthwire 3I0C 3IA+3I0B I 0K1 3I0B A ~ ~ ZEB IZB pA3I0A UEF IZF pC(3I0A+3I0B) C ZEC IZC ~ ZEA IZA Figure 7.2 F B pC3I0C Earth Equivalent circuit diagram with short-circuit at overhead-line tower If the short-circuit occurs in a short distance from the switchyard, the branch short-circuit current through the earth conductor and back to the switchyard can be comparatively high. The branch short-circuit current through earth is reduced accordingly. The branch short-circuit current through the earthing grid at switchyard B in the case of a short-circuit at location F is I ZB = pC ∗ (3 ∗ I 0A + 3 ∗ I 0C ) − p A ∗ 3 ∗ I 0A (7.18) The branch short-circuit current through the earthing grid can be higher or lower for the short-circuit location inside the switchyard or at any overhead-line tower outside depending on the actual earthing conditions. IEC 60909-3 presents the method to calculate the reduction factor on overhead lines. Further reference is made to [2,3,5,6]. 7.4 Examples Examples for the calculation of short-circuit currents in the case of double earthfault and for the calculation of branch short-circuit currents flowing through earth are included in IEC 60909-3 Annexes A and B. Configurations with nominal system voltage U n = 132 kV similar to those as per Figures 7.1 and 7.2 are presented. 7.4.1 Double earth-fault in a 20-kV-system Figure 7.3 represents the equivalent circuit diagram of a 20-kV-system with overhead lines to calculate the short-circuit current in the case of a double earth-fault. Data of Double earth-fault and short-circuit currents 147 A: Phase R 8 km B: Phase Y 12 km Figure 7.3 Equivalent circuit diagram of a 20-kV-system equipment are System feeder Transformer Overhead lines  = 1 GVA; U = 110 kV SkQ n SrT = 40 MVA; ukrT = 14%; trT = 110 kV/20 kV ACSR 95/15; R1 = 0.384 /km; X1 = 0.35 /km; R0 = 1.35 /km; X0 = 0.6 /km. The impedances of equipment are calculated in accordance with Section 7.3. Equipment Positive-sequence component Zero-sequence component System feeder (0.044 + j 0.438)  — Transformer (0.0 + j 1.35)  — Line to short-circuit (3.07 + j 2.8)  (10.08 + j 3.07)  location A Line to short-circuit (4.61 + j 4.2)  (16.2 + j 4.61)  location B Total impedance (42.624 + j 32.408)  (Table 7.1) The short-circuit current in the case of a double earth-fault is calculated as  = 1.23 kA. When both short-circuits occur at a tower, a part of the shortIkEE circuit current flows through the tower and the footing resistance. Depending on the resistivity of the earth, the footing resistance and the surge impedance of the 148 Short-circuit currents line, this part is approximately 10–25 per cent smaller than the total short-circuit current. 7.4.2 Single-phase short-circuit in a 110-kV-system Figure 7.4 indicates the equivalent circuit diagram of a 110-kV-system with shortcircuit location F. The single-phase short-circuit current, the branch short-circuit currents flowing through the earth and the potential of the earth grid shall be calculated. The data of equipment are Earth wire A 45 km B Un = 110 kV ZEB Figure 7.4 Feeder A Feeder B Feeder C 80 km C UEB Equivalent circuit diagram of a 110-kV-system with short-circuit location  SkQA = 1.5 GVA; SrT = 250 MVA; u1kT = 16%; u0kT = 20%; u0rR = 0.2%  = 2.0 GVA; SrT = 350 MVA; u1kT = 14%; u0kT = 18%; SkQB u0rR = 0.2%  = 1.1 GVA; SrT = 200 MVA; u1kT = 15%; u0kT = SkQC 19%; u0rR = 0.2% Line ACSR 2 × 240/40; earth wire 240/40; reduction factor p ≈ 0.6 Z 1 = (0.059 + j 0.302) /km; Z 0 = (0.27 + j 1.51) /km Double earth-fault and short-circuit currents 149 The impedances of equipment are calculated in accordance to Section 7.3 and Section 3.2. Equipment Positive-sequence component Zero-sequence component Feeder A including transformer Feeder B including transformer Feeder C including transformer Line A–B Line B–C Impedance at short-circuit location (0.0 + j 8.87)  (0.1 + j 9.68)  (0.0 + j 6.66)  (0.06 + j 6.22)  (0.0 + j 12.1)  (0.12 + j 11.5)  (2.655 + j 13.59)  (12.15 + j 21.6)  (4.72 + j 24.16)  (67.95 + j 120.8)  (0.178 + j 4.512)  (0.407 + j 5.11)  The single-phase short-circuit current is calculated as I k1 = (0.798 − j 14.785) kA and |I k1 | = 14.8 kA, respectively. The current in the zero-sequence component is I 0 = 13 I k1 = (0.266 − j 4.928) kA and the branch short-circuit currents of the three feeders A, B and C are I 0A = (0.179 − j 0.732) kA I 0B = (0.502 − j 4.036) kA I 0C = (0.057 − j 0.16) kA The total current through the earth grid is I ZB = (0.425−j 1.426) kA. The impedance of the earth grid depends on the resistivity of the soil, the footing resistance of the tower and the surge impedance of the line. Assuming (in accordance with IEC 60909-3) the impedance of the earthing grid to be Z EB = (0.68 + j 0.49)  the potential of the earth grid is U EB = (0.987 − j 0.761) kV and |U EB | = 1.246 kV, respectively. Chapter 8 Factors for the calculation of short-circuit currents 8.1 General Several factors for the calculation of short-circuit (s.-c.) currents have been introduced in previous sections, the origin of which will be explained within this section. • Voltage factor cmax and cmin for different voltage levels as per Table 4.1. • Correction factor using the %/MVA- or the p.u.-system as mentioned in Chapter 2. • Impedance correction factors for synchronous machines, power station units and transformers as per Tables 3.2, 3.3, 3.5 and 3.6. • Factors for the calculation of different parameters of the short-circuit current based on the initial short-circuit current as per Chapter 4. The factors are necessary as the method of the equivalent voltage source at the short-circuit location is used for the calculation of short-circuit currents which is based on some simplifications such as neglecting the load current prior to fault, assuming the tap-changer of transformers in middle-position, calculating the impedance of equipment based on the name-plate data or on data for rated operating conditions and neglecting voltage control gear for generators and transformers. The main task of short-circuit analysis is to determine the maximal short-circuit current which is one of the main criteria for the rating of equipment in electrical power systems. It is obvious that the parameters of the short-circuit current as calculated with the equivalent voltage source at the short-circuit location will differ from those currents, which may be measured during short-circuit tests or may be calculated with transient network analysing programmes. In order to obtain results on the safe side without uneconomic safety margin the correction factors will be applied. Detailed deductions of the various correction factors are given in IEC 60909-1:1991-10. 152 Short-circuit currents 8.2 Correction using %/MVA- or p.u.-system The need to use special correction factors for the impedances using the %/MVAsystem, applies also to the p.u.-system. The calculation of short-circuit currents can be carried out using the %/MVA- or the p.u.-system as outlined in Section 2.7. The rated voltage of equipment Ur is chosen as reference voltage UB for the calculation of the impedance of transformers, generators, etc. For system feeders and lines the rated voltage is not defined, therefore the nominal system voltage Un is taken as reference voltage. The rated voltages of transformers in most cases are unequal to the nominal voltage of the power system, connected to the transformer. Figure 8.1 indicates a 110/10-kV-system as an example. Q1 T2 T1 F L Q2 Un = 220 kV Figure 8.1 Equivalent circuit diagram of a power system with different voltage levels Rated data of equipment are given below:   = 1 GVA; U UnQ1 = 110 kV; SkQ1 nQ2 = 220 kV; SkQ2 = 3 GVA SrT2 = 300 MVA; ukrT2 = 15%; trT2 = 225 kV/115 kV SrT1 = 250 MVA; ukrT1 = 17%; trT1 = 220 kV/115 kV RL = 0.03 /km; XL = 0.12 /km; l = 100 km The impedances of the equipment using the Ohm-system related to the short-circuit location (Column 2), the %/MVA-system (Column 3) and the p.u.-system (Column 4) are summarised in Table 8.1. The values in the %/MVA-system are converted to the Ohm-system by using the equations as per Table 2.3 (Column 5). The result (Column 6) indicates a difference of 6.3 per cent for the total short-circuit impedance. The differences of the impedances result from the fact that the calculation in the Ohm-system takes account of the real transformation ratio of the transformers tr = UrTHV /UrTMV , whereas the calculation in the %/MVA- and in the p.u.-system assumes a voltage of 100 per cent for all different voltage levels. The final conversion to the Ohm-system is done using the voltage at the short-circuit location UnF , thus denying the differences between rated voltages of the transformers and nominal voltages of the connected power systems. These differences obviously will result in differences of the short-circuit currents as outlined in Table 8.1. A correction of the impedances is necessary in case the rated voltages of transformers and the nominal system voltages differ from each other. Factors for the calculation of short-circuit currents 153 Table 8.1 Impedances of equipment and short-circuit current as per Figure 8.1 1 2 3 Equipment Impedance Impedance Impedance Impedance Difference related to (%/MVA) (p.u.) (%/MVA) → () (%) s.-c. (p.u.) → () location () System Q1 13.929 Transformer T2 6.917 System Q2 4.849 Line L 3.279 Transformer T1 8.993 Total s.-c. 16.206 impedance Short-circuit 4.31 kA current Q ZB 4 5 0.11 0.05 0.037 0.0248 0.068 0.126 0.11 0.05 0.037 0.0248 0.068 0.126 4.60 kA 10.12 p.u. Ti 6 13.31 6.05 4.48 3.0 8.228 15.246 4.7 14.3 8.2 9.3 9.3 6.3 — 6.3 T2 T1 Un Figure 8.2 Equivalent circuit diagram for the calculation of impedance correction factor using %/MVA- or p.u.-system The impedance correction factors (see Figure 8.2 for explanation) are obtained starting from the short-circuit location F indicated in Figure 8.1 by multiplying the ratios of the rated voltages of all transformers T1 –Ti between the short-circuit location F and the equipment under consideration B, then going back with the ratio of the rated voltage of the equipment UrB and the nominal voltage Un at the short-circuit location. For system feeders and lines the nominal system voltage at the very location UnB has to be taken instead of the rated voltage, which is not defined for feeders and lines. The impedance correction factor KB is calculated by KB =  UrT1E UrT2E UrT3E ∗ ∗ ∗ ··· UrT1A UrT2A UrT3A 2 ∗  UrB UnF 2 (8.1) The impedance correction factor using the %/MVA- or the p.u.-system must be applied for any equipment [33] except power station units for which special correction factors are valid. 154 Short-circuit currents Table 8.2 Impedances of equipment and short-circuit current using correction factor 1 2 3 Equipment Impedance Impedance Correction factor Impedance Impedance (%/MVA) (p.u.) related to s.-c. (%/MVA) KB as per location () Equation (8.1) using KB using KB System Q1 13.929 Transformer T2 6.917 System Q2 4.849 Line L 3.279 Transformer T1 8.993 Total s.-c. 16.206 impedance Short-circuit 4.31 kA current 4 5 6 0.11 0.05 0.037 0.0248 0.068 0.126 1.046 1.093 1.143 1.093 1.093 — 0.115 0.057 0.04 0.027 0.0743 0.134 0.115 0.057 0.04 0.027 0.0743 0.134 — — 4.31 A 9.48 p.u. Applying the impedance correction factors as per Equation (8.1) the impedances calculated with the %/MVA- and the p.u.-system are identical to those obtained by using the Ohm-system as outlined in Table 8.2. 8.3 Impedance correction factors Within this book the deduction of the impedance correction factor KG for synchronous machines (generators) is given. The factor is valid for generators connected directly without unit transformers to the power system which is normally the fact in mediumvoltage and low-voltage systems [37]. Assuming an overexcited turbine generator as per Figure 8.3 with voltage control at the terminal connection to UG = (1 ± pG )∗UrG , the control range normally is set to (1 + pG ) = 1.05. Prior to fault the generator generates the apparent power S G = PG + j QG to be fed into the system. (a) X ⬙d (b) GS 3~ UrG Figure 8.3 ~ UG Un E⬙ RG IG UrG 3 01 Generator directly connected to the power system. (a) Equivalent system diagram and ( b) equivalent circuit diagram in the positive-sequence component Factors for the calculation of short-circuit currents 155 ZG ~ ~ ZG IG UG 3 E0 ZG I 0kUb ~ UG 3 ~ ~ ~ E0 I 0kG UG 3 ~ UG 3 ~ UG = UrG (1⫾PG) 3 Figure 8.4 Determination of the short-circuit current by superposition In the case of a short-circuit as indicated F in Figure 8.3(a) the short-circuit current can be calculated by superposition of the generator current I G prior √ to fault and the short-circuit current I kUb based on the voltage Ub = UG = UrG / 3 prior to fault as outlined in Figure 8.4. The generator current I G prior to fault is given by IG √ E  − (U rG / 3) = ZG (8.2) and the fault current I kUb can be calculated by I kUb √ U rG / 3 = ZG (8.3) The short-circuit current of the generator I kG is obtained by superposition of the two currents I kG = I kUb + IG √ √ U rG / 3 E  − (U rG / 3) = + ZG ZG (8.4) where E  is the subtransient voltage of the generator, U rG is the rated generator voltage and Z G is the generator impedance. If the method of the equivalent voltage source with the voltage E  is used the short-circuit current I kG is calculated by I kG = E  ZG (8.5a) which is different from the calculation √ as per Equation (8.4). If the voltage at the short-circuit location E  = c ∗ Un / 3 with the voltage factor c as per Table 4.1 and 156 Short-circuit currents an impedance correction factor K G are introduced, the short-circuit current I kG is found to be c ∗ Un c ∗ Un I kG = √ =√ (8.5b) 3 ∗ ZG ∗ K G 3 ∗ (RG + j Xd ) ∗ K G where K G is the impedance correction factor (to be determined), Un is the nominal system voltage, Z G is the generator impedance, RG is the stator resistance of the generator and Xd is the subtransient reactance of the generator. Equations (8.5a) and (8.5b) are set to be equal. The unknown internal subtransient voltage of the generator E  can be found in accordance with Figure 8.3(b). U E  = √rG + IG ∗ (cos ϕG − j sin ϕG ) ∗ (RG + j Xd ) 3 (8.6) where U rG is the rated voltage of the generator and ϕG is the phase angle of the generator current (power factor: cos ϕ) and other quantities are explained above. The impedance correction factor K G is then calculated by √  3 ∗ IG Un KG = ∗c∗ 1+ ∗ (RG ∗ cos ϕG + Xd ∗ sin ϕG ) UrG UrG √ −1 3 ∗ IG  (8.7) ∗ (Xd ∗ cos ϕG − RG ∗ sin ϕG ) +j UrG The resistance RG normally can be neglected against the subtransient reactance Xd of the generator; the correction factor then results in KG ≈ Un c ∗ UrG 1 + (IG /IrG ) ∗ xd ∗ sin ϕG (8.8) 2 )∗S . whereas the subtransient reactance is introduced as a p.u.-value xd = (Xd /UrG rG The correction factor is maximal when the maximal voltage factor cmax and rated operating conditions with IG = IrG and ϕG = ϕrG are applied. The impedance correction factor KG is given by KG ≈ cmax Un ∗ UrG 1 + xd ∗ sin ϕG (8.9) For other equipment such as power station units and transformers impedance correction factors can be deducted in a similar way [35] as explained for the correction factor of the generator. Details can be found in IEC 60909-1. 8.4 Factor κ for peak short-circuit current The peak short-circuit current is the maximal instant value of the short-circuit current which occurs normally within the first few milliseconds after the occurrence of the short-circuit. The system configuration with a single-fed three-phase short-circuit is dealt with in Figure 8.5. Factors for the calculation of short-circuit currents 157 (a) Q T Un Uk; SrT; UrT S ⬙kQ t=0 (b) Rtot ik(t) Xtot ~ U u (t) =c 2 n .sin (v) 3 (c) u u (t) vt wu Figure 8.5 Equivalent circuit diagram of a power system with three-phase shortcircuit. (a) Circuit diagram, ( b) simplified diagram of a single-fed threephase short-circuit and (c) time course of voltage with voltage angle ϕU The time course of the short-circuit current ik (t) is calculated from the differential equation L∗ √ dik (t) c ∗ Un + R ∗ ik (t) = 2 ∗ √ ∗ sin(ωt + ϕU ) dt 3 (8.10) The solution of the differential equation is given by ik (t) = √ 1 c ∗ Un 2∗ √ ∗ √ ∗ (sin(ωt + ϕU − γ ) − e−t/T 2 3 R + X2 ∗ sin(ϕU − γ )) (8.11) where Un is the nominal system voltage, ϕU is the angle of voltage related to zero crossing as per Figure 8.5, c is the voltage factor according to Table 4.1, T is the time constant: T = L/R, X is the reactance of the short-circuit impedance: X = ωL, R is the resistance of the short-circuit impedance, ω is the angular velocity and γ the angle of the short-circuit impedance: γ = arctan(X/R). 158 Short-circuit currents The initial short-circuit current Ik is equal to the first part (periodic term) of Equation (8.11), the second term is the aperiodic and decaying d.c.-component of the current. If the time course of the short-circuit current as per Equation (8.11) is related to the peak value of the initial short-circuit current Ik = √ 1 c ∗ Un 2∗ √ ∗ √ 2 3 R + X2 (8.12) the peak factor κ is obtained κ(t) = sin(ωt + ϕU − γ ) − e−t/T ∗ sin(ϕU − γ ) (8.13a) The maximum of the peak factor κ determines the maximum of the short-circuit current (peak short-circuit current ip ) to be calculated by partial differentiation of Equation (8.13a) with respect to ϕU and t. The maximum of the peak factor always occurs for short-circuits at ϕU = 0 and t ≤ 10 ms (50 Hz), respectively t ≤ 8.33 ms (60 Hz), whatever the ratio R/X might be κ(t) = sin(ωt − γ ) + e−(R/X)∗ωt ∗ sin γ (8.13b) A sufficient approximation of the peak factor κ is given by κ = 1.02 + 0.98 ∗ e−3(R/X) (8.14) Special attention for the calculation of peak short-circuit current must be given in the case of short-circuits in meshed systems or in systems having parallel lines with R/X-ratios different from each other [34]. A detailed analysis of these conditions is given in IEC 60909-1 and is mentioned in Chapter 4. The peak factor κ according to Equation (8.14) is outlined in Figure 4.7. 8.5 Factor µ for symmetrical short-circuit breaking current The short-circuit current in the case of a near-to-generator short-circuit decays significantly during the first periods after initiation of the short-circuit due to the change of the rotor flux in the generator. This behaviour cannot be calculated exactly as eddy currents in the forged rotor of turbine generators, non-linearities of the iron and saturation effects especially in the stator tooth are difficult to be calculated. Furthermore, the decay of the short-circuit current and by this the breaking current depend on different generator and system parameters such as time constants of the generator itself, location of short-circuit in the system, operational condition prior to the fault, operation of excitation and voltage control device, tap-changer position of transformers, etc. which cause unpredictable deviations of the calculated results from those obtained from measurements. Detailed calculations with digital programmes are therefore only applicable in special cases if high safety requirements are to be met. Factors for the calculation of short-circuit currents 159 The time decay of the a.c. part of the short-circuit current is calculated by   Ikac (t) = (Ik − Ik ) ∗ e−t/TN + (Ik − Ik ) ∗ e−t/TN + Ik (8.15) Equation (8.15) is composed of the initial short-circuit current Ik = Xd E  + XN (8.16a) the transient short-circuit current Ik = E Xd + XN (8.16b) and the steady-state short-circuit current Ik = E Xd + X N (8.16c) where E; E  ; E  are the steady-state, transient and subtransient voltages, Xd ; Xd ; Xd is the steady-state, transient and subtransient reactance of the generator and XN is the reactance between the generator and the short-circuit location, e.g., including the reactance of the unit transformer. The individual components of the short-circuit currents as per Equations (8.15) and (8.16) are declining with different time constants, i.e., the subtransient time con stant TN which can be set approximately equal to the subtransient time constant TdN  in the direct axis. Typical values of the time constants are TN ≈ 0.03–0.04 s and TN ≈ 1.0–1.5 s and are calculated by TN = T  ∗ Xd Xd + XN ∗ Xd Xd + XN (8.17a) TN = T  ∗ Xd Xd + XN ∗ Xd Xd + XN (8.17b) The units T  and T  are the subtransient and transient time constants of the generator. Regarding the time course of the decaying a.c. part of the current as per  Equation (8.15), the approximation e−t/TN ≈ 1 can be assumed if the time range (minimal time delay of circuit-breakers) t = tmin = 0.02–0.25 s is considered: Ikac (t) ≈ Ik  X  + XN ∗ 1 − d Xd + XN ∗e −tmin /TN X  + XN + d Xd + XN  = Ik ∗ μ (8.18) with tmin being the minimal time for breaking the short-circuit current. The second part of Equation (8.18) is taken as the factor μ for the calculation of the breaking current. 160 Short-circuit currents As the exponent tmin /TN may be greater or smaller than 1, the infinite progression √  for e−t/TN is applied. For no-load conditions, where E  ≈ E  ≈ E ≈ UrG / 3, the factor μ is obtained by  X − Xd X − Xd tmin  + e−tmin /TN − 1 ∗ μ ≈ 1 −  d √ ∗ Ik ∗ tmin + d  Xd + XN TN T0 ∗ (UrG / 3) (8.19) with the no-load subtransient time constant T0 = T  ∗ Xd Xd (8.17c) When if tmin ≪ TN the last part of Equation (8.19) can be neglected. The factor μ can be presented depending on the minimal time delay of the circuit-breaker tmin and the ratio Ik /IrG as outlined in Figure 4.10. 8.6 Factor λ for steady-state short-circuit current The steady-state short-circuit currents of generators are determined by the method of excitation, the maximal possible excitation voltage, the type of voltage control and strongly by the saturation effects. As salient-pole and turbine generators differ significantly with respect to their reactances and are mostly equipped with different types of excitation, the steady-state short-circuit currents of both generators will differ even if all other conditions are equal. The calculation is carried out with the factor λ based on the rated current IrG of the generator which is determined separately for minimal and maximal current. Ik max = λmax ∗ IrG (8.20a) Ik min = λmin ∗ IrG (8.20b) The factor λ is found from the characteristic curve method as per Figure 8.6 defining Potier’s reactance XP . Ik = E0 (If ) XP + XN (8.21) where XP is the Potier’s reactance as per Figure 8.6, E0 is the no-load voltage, If is the excitation current and XN is the reactance between the generator and the short-circuit location, e.g., including the reactance of the unit transformer. The value of Potier’s reactance is between the transient reactance Xd (pole saturation only) and the stator leakage reactance Xσ (teeth saturation only). The method to determine Potier’s reactance requires detailed knowledge of the saturation within the machine and is not practicable for the determination of the factor λ. Factors for the calculation of short-circuit currents 161 E0 UL UrG / 3 UrG/ 3 XP E0 (If) UL E0 (If) XP/IrG UrG/ 3 1 Ifkr/IfOd UL (If) 1 Figure 8.6 If /IfOd Characteristic saturation curve method for determination of Potier’s reactance IEC 60909-1 recommends a simplified method. Potier’s reactance and the source voltage E0 which is a function of the field current If are reduced due to the saturation as can be seen from Figure 8.6. Both effects compensate each other to a certain extent and are ignored therefore. The current Ik is calculated by Ik = uf max ∗ Er Xdsat + XN (8.22) where uf max is the highest possible excitation voltage (p.u.-value), Er is the internal steady-state voltage of the generator at rated operating conditions, Xdsat is the saturated value of the synchronous reactance (equal to the reciprocal of the short-circuit ratio) and XN is the reactances between the generator and the short-circuit location, e.g., including the reactance of the unit transformer. Furthermore, the subtransient internal voltage is given as E  = IG ∗ (Xd + XN ) (8.23) By this the factor λ is determined to be λ= Ik uf max ∗ Er =  )  IrG (Xdsat − Xd ) ∗ IrG + E  ∗ (IrG /IkG (8.24) 162 Short-circuit currents Table 8.3 Assumed values of uf max for the calculation of the factor λ uf max = Uf max /Ufr Type of synchronous machine Salient-pole generator Turbine generator Series 1 1.3 1.6 Series 2 1.6 2.0 The voltages E  and Er can be determined if RG ≪ Xd by UrG E  ≈ √ ∗ (1 + xd ∗ sin ϕrG ) 3 (8.25) Ur Er ≈ √ ∗ 3 (8.26) 2 +2∗x 1 + xdsat dsat ∗ sin ϕrG √ √ where xd = Xd ∗ (( 3 ∗ IrG )/UrG ) and xdsat = Xdsat ∗ (( 3 ∗ IrG )/UrG ). √ The rated impedance is ZrG = UrG /( 3 ∗ IrG ). The values for λmax and λmin as per Figures 4.11 and 4.12 are calculated by Equations (8.23)–(8.25), cos ϕrG = 0.85 and Xd = 0.2 ∗ ZrG . The highest possible excitation voltage (p.u.-value) uf max is assumed for the calculation in accordance with the values as per Table 8.3. 8.7 Factor q for short-circuit breaking current of asynchronous motors Asynchronous motors are contributing to the short-circuit current as outlined in Chapter 4. As the short-circuit current of asynchronous motors decays faster as compared with the short-circuit current of synchronous machines, the short-circuit  using breaking current is based on the initial short-circuit current of the motor IkM the factor μ which is identical to the factor for the calculation of breaking current of synchronous generators and an additional factor q  IbM = q ∗ μ ∗ IkM (8.27) The factor q as per Figure 4.13 is derived from the results of transient calculations and measurements using 28 motors with different rating PrM = 11–160 kW in the low-voltage range and up to PrM = 160 kW–10 MW in the mediumvoltage range. A detailed list of the rated data of the asynchronous motors is included in Table 2 of IEC 60909-1:1991 (similar to those given in Tables 13.6 Factors for the calculation of short-circuit currents 163 and 13.7). The minimum time delay of the circuit-breakers was assumed in four steps tmin = 0.02–0.05–0.1–≥0.25 s. The results are outlined in Figure 8.7. 1 0.02 s 0.05 s 0.1 s 0.9 0.8 0.7 >0.25 s 0.6 q 0.5 Minimal time delay 0.02 s 0.05 s 0.1 s 0.4 0.3 0.2 > 0.25 s 0.1 0 0.01 Figure 8.7 0.1 1 m (active power per pair of poles) 10 MW 100 Calculated and measured values of factor q for the calculation of shortcircuit breaking current of asynchronous motors; values of q as per Figure 4.13 (According to Figure 20 of IEC 60909-1:1991.) As can be seen from Figure 8.7 the values of the factor q (approximation) as per Figure 4.13 are mean values of the calculated and measured ones with the 50 per centfrequency deviation between the exact values and the approximated values in the range of q < 5%. Chapter 9 Calculation of short-circuit currents in d.c. auxiliary installations 9.1 General The calculation of short-circuit currents in d.c. auxiliary installations, e.g., in power plants and substations is dealt with in IEC 61660-1. Contrary to the approach for the calculation of short-circuit currents in a.c. three-phase systems, the determination of the exact time course of the short-circuit current is needed besides the calculation of defined parameters [42]. The equipment as below contribute to short-circuit currents in d.c. installations: • Smoothing capacitors • Stationary batteries (normally of the lead-acid type) • Rectifiers (IEC 61660-1 deals only with rectifiers in three-phase a.c. bridge connection for 50 Hz, parameters for 60 Hz are actually under consideration) • d.c. motors with independent excitation. The branch short-circuit currents from the equipment mentioned above are characterised by different time course, depending on the ohmic, inductive and capacitive parts, the d.c. voltage source and other parameters. Figure 9.1 presents the equivalent circuit diagrams of the equipment and the typical time course of the short-circuit current. d.c. installations in auxiliary supply systems include several pieces of equipment; the total short-circuit current at the short-circuit location is the superposition of the individual branch short-circuit currents from the different equipment. In principle the short-circuit current can be defined by a time function i1 (t), describing the time span tp from short-circuit initiation till the maximal short-circuit current ip (peak shortcircuit current) and a time function i2 (t), describing the decaying time course to the 166 Short-circuit currents (a) iC ipC tpC t (b) iB ipB IkB tpB t (c) iD ipD IkD ~ – IkD tpD t (d) iM ipM IkM IkM tpM M t Motor without additional inertia mass Motor with additional inertia mass Figure 9.1 Equivalent circuit diagrams of equipment in d.c. auxiliary installations; typical time course of short-circuit current (according to Figure 1 of DIN EN 61660-1 (VDE 0102 Teil 10)). (a) Capacitor, (b) battery, (c) rectifier in three-phase a.c. bridge connection and (d) d.c. motor with independent excitation Calculation in d.c. auxiliary installations 167 1.2 1 1 ip i1(t) 0.8 i/ip i2(t) tP 0.6 Ik 0.4 t2 0.2 Tk 0 0 2 4 6 8 10 12 14 16 18 t Figure 9.2 Standard approximation function of the short-circuit current (according to Figure 2 of IEC 61660-1:1997) quasi steady-state short-circuit current Ik as outlined in Figure 9.2. Time functions can be calculated according to [50] by 1 − e−t/τ1 for 0 ≤ t ≤ tp 1 − e−tp /τ1  Ik Ik i2 (t) = ip 1− ∗ e−(t−tp )/τ2 + ip ip (9.1a) i1 (t) = ip ∗ for tp ≤ t ≤ Tk (9.1b) If no distinct maximum of the short-circuit current is present, the peak shortcircuit current ip and the quasi steady-state short-circuit current Ik are equal. This time course as well is described by the standard approximation function according to Figure 9.2. The approach to calculate the parameter ip and Ik , the time constants τ1 and τ2 and the time to peak tp is explained below: • • The parameter of the short-circuit current will be calculated for each branch separately, i.e., for each individual equipment contributing to the short-circuit current. In case of several sources, the short-circuit parameters will be calculated by superposition of the branch short-circuit currents by: – Calculation of the branch short-circuit currents taking account of the common branch, i.e., that branch in the installation carrying branch short-circuit currents from different sources. – Correction of the branch short-circuit currents by a factor σ , which depends on the different resistances. 168 Short-circuit currents – Calculation of the time course of the branch short-circuit currents with the corrected impedances. – Superposition of the calculated time functions of the branch short-circuit currents to determine the total short-circuit current. – The thermal and electromagnetic effects of short-circuit currents are calculated using the standard approximation function. The calculation of impedances of the sources in d.c. auxiliary installations feeding the short-circuit current was dealt with in Section 3.3. The calculation of the shortcircuit parameters is carried out as mentioned above and explained below. For the calculation of maximal short-circuit currents in d.c. auxiliary installations the items as below had to be taken into account: • • • • • • • Short-circuit impedance of system shall be minimal (ZQmin ), so that the contribution to the short-circuit current is maximal. Resistance of lines is to be calculated for a temperature of 20◦ C. System topology leading to the maximal short-circuit currents shall be taken into account. Joint resistance of busbars shall be neglected. Control circuits to limit the contribution of rectifiers are disconnected, i.e., limitation is not active. Batteries are fully charged. Systems coupled by diodes are regarded as directly connected. For the calculation of minimal short-circuit currents in d.c. auxiliary installations the items as stated below shall be considered: • • • • • • • Short-circuit impedance of system shall be maximal (ZQmax ), so that the contribution to the short-circuit current is minimal. System topology leading to the minimal short-circuit currents shall be taken into account. Resistance of lines shall be calculated for maximal permissible operating temperature. Joint resistance of busbar has to be taken into account. Contribution of rectifiers to the short-circuit current is limited to the rated value of the current limiter. Voltage of batteries shall be defined equal to the minimal discharge voltage as per manufacturer’s information. Systems coupled by diodes are regarded as disconnected. The current limiting characteristic of fuses and switchgear in d.c. auxiliary installations has to be taken into account for the calculation of both maximal and minimal short-circuit current. Calculation in d.c. auxiliary installations 169 9.2 Short-circuit currents from capacitors The quasi steady-state short-circuit current of a capacitor is zero IkC = 0 (9.2) The peak short-circuit current ipC is calculated using ipC = κC ∗ EC RCBr (9.3) where EC is the capacitor voltage at the instant of short-circuit and RCBr is the resistance of capacitor including connection and common branch (see Section 3.3.1 and Table 3.13). The factor κC depends on the eigen-frequency ω0 1 ω0 = √ LCBr ∗ C (9.4a) 2 ∗ LCBr 1 = δ RCBr (9.4b) and on the decay coefficient δ where LCBr is the inductance of the capacitor connection including common branch (see Table 3.13) and C is the capacitance. The reasonable range of values for κC is outlined in Figure 9.3; equations for the calculation of κC are included in the Annex of IEC 61660-1:1997 and are not repeated here. 1 0.9 103 0.8 0.7 kC 0.6 . 0.5 104 0.4 v0 0.3 105 0.2 0.1 0 0.1 1 10 ms 100 1/d . Figure 9.3 Factor κC for the calculation of peak short-circuit current of capacitors (according to Figure 12 of IEC 61660-1:1997) 170 Short-circuit currents 10 ms tpC 103 1 . v0 104 0.1 105 0.01 0.1 10 1 ms 100 . 1/d Figure 9.4 Time-to-peak tpC for the calculation of short-circuit currents of capacitors (according to Figure 13 of IEC 61660-1:1997) The time-to-peak tpC also depends on the eigen-frequency ω0 and the decay coefficient δ. The reasonable range of values for tpC is outlined in Figure 9.4; equations for the calculation of tpC are included in the Annex of IEC 61660-1:1997. The rise-time constant τ1C τ1C = k1C ∗ tpC (9.5a) and the decay-time constant τ2C τ2C = k2C ∗ RCBr ∗ C (9.5b) depend upon the factors k1C and k2C , i.e., upon eigen-frequency and decay component. Reasonable ranges of values are outlined in Figures 9.5 and 9.6. Quantities of Equations (9.5) are explained above. Calculation equation for the factors k1C and k2C are not included in IEC 61660-1:1997. 9.3 Short-circuit currents from batteries As rise-time constants of the short-circuit current of batteries are always below 100 ms, the quasi steady-state short-circuit current Ik is calculated for the time instant of 1 s after initiation of the short-circuit. 0.95 ∗ EB IkB = (9.6) RBBr + 0.1 ∗ RB where EB is the open-circuit voltage of the battery, RBBr is the resistance of the battery including connection and common branch (see Section 3.3.1 and Table 3.14) and RB is the resistance of the charged battery. Calculation in d.c. auxiliary installations 171 0.8 0.7 0.6 . k1C 105 0.5 104 0.4 v0 0.3 103 0.2 0.1 0 0.1 1 10 ms 100 . 1/d Figure 9.5 Factor k1C for the calculation of rise-time constant (according to Figure 14 of IEC 61660-1:1997) 10,000 k2C . 1000 105 100 104 v0 10 103 1 0.1 1 10 . Figure 9.6 ms 100 1/d Factor k2C for the calculation of decay-time constant (according to Figure 15 of IEC 61660-1:1997) The peak short-circuit current ipB is calculated using the battery voltage EB by ipB = EB RBBr (9.7) Reasonable ranges of the values for the rise-time constant τ1B and the time-to-peak tpB , both depending on the decay component δ 1 2 = δ RBBr /LBBr + 1/TB (9.8) 172 Short-circuit currents 100 ms tpB tpB 10 1B . 1B 1 0.1 0.1 1 . Figure 9.7 1/d 10 ms 100 Rise-time constant τ1B and time to peak tpB of short-circuit currents of batteries (according to Figure 10 of IEC 61660-1:1997) where LBBr is the reactance of the battery including connection and common branch (see Table 3.14) and TB is the time constant of the battery assumed to be TB = 30 ms (outlined in Figure 9.7). The decay-time constant is set to τ2B = 100 ms. More details of the calculation of short-circuit currents fed from batteries are included in [56]. 9.4 Short-circuit currents from rectifiers The quasi steady-state short-circuit current IkD of a rectifier in three-phase a.c. bridge connection is √ 3∗ 2 UrTLV c ∗ Un ∗ (9.9) ∗√ IkD = λD ∗ π 3 ∗ ZN UrTHV where Un is the nominal system voltage on a.c. side of rectifier, ZN is the network impedance a.c. side, UrTLV is the rated voltage at low voltage side of transformer (a.c. side) and UrTHV is the rated voltage at high voltage side of transformer (a.c. side). The factor λD depends on the ratio RN /XN of the a.c. side of the rectifier as well as on the ratio of the resistances RDBr /RN (ratio of resistance d.c. side to resistance a.c. side). A reasonable range of values of the factor λD is outlined in Figure 9.8. Equations for the calculation of λD are included in IEC 61660-1:1997. The peak short-circuit current is calculated using ipD = κD ∗ IkD (9.10) whereas the factor κD depends on the ratio of the inductivities LDBr /LN (ratio of inductance d.c. side to inductance a.c. side) and on the resistances and reactances Calculation in d.c. auxiliary installations 173 1.1 1 0.01 0.9 0.8 1.5 0.7 RDZw/RN D 0.6 5.0 . 0.5 0.4 0.3 0.2 0.1 0 0 0.1 0.2 0.3 0.4 0.5 0.6 . Figure 9.8 0.7 0.8 RN/XN 0.9 1 1.1 1.2 Factor λD for the calculation of quasi steady-state short-circuit current of rectifiers (according to Figure 7 of IEC 61660-1:1997) 2 1.9 1.8 kD 1.7 1.6 . 1.5 1.4 RDBr /RN 1.3 0.01 1.2 1.0 1.1 1 5.0 0.9 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 . Figure 9.9 0.8 0.9 1 1.1 1.2 1.3 1.4 R* Factor κD for the calculation of peak short-circuit currents of rectifiers. Factor: R ∗ = (RN /XN )(1 + 2RDBr /3RN ) (according to Figure 8 of IEC 61660-1:1997) RN , RBBr and XN . The reasonable range of values of the factor κD is outlined in Figure 9.9. Equations for the calculation are included in IEC 61660-1:1997. In the case of κD < 1.0 no distinct maximum of the short-circuit current is present, thus the peak short-circuit current can be neglected as the quasi steady-state shortcircuit current will be the maximal value of the current. IEC 61660-1 determines for 174 Short-circuit currents κD < 1.05 the time to peak tpD equal to the duration of the short-circuit Tk . For all other cases (κD ≥ 1.05) the time to peak is calculated using tpD = (3 ∗ κD + 6) ms   LDBr tpD = (3 ∗ κD + 6) + 4 −1 LN ms for LDBr ≤1 LN (9.11a) for LDBr >1 LN (9.11b) The rise-time constant τ1D for rectifiers fed from 50 Hz (60-Hz-values are actually under consideration) is   LDBr (9.12a) ms for κD ≥ 1.05 τ1D = 2 + (κD − 0.9) ∗ 2.5 + 9 ∗ LN    RN 2 LDBr τ1D = 0.7 + 7 − ∗ 1+ ∗ XN 3 LN  LDBr (9.12b) ∗ 0.1 + 0.2 ∗ ms for κD < 1.05 LN A suitable approximation, giving results on the safe side is τ1D = tpD 3 (9.12c) The decay-time constant τ2D for 50 Hz is calculated using τ2D = 2 ms RN /XN ∗ (0.6 + 0.9 ∗ (RDBr /RN )) (9.13) Quantities as per Equations (9.11)–(9.13) are: XN is the inductance of system N (a.c. side) XN = ωLN , RN is the resistance of system N (a.c. side), RDBr is the resistance of d.c. side including smoothing reactor, connection and common branch (see Section 3.3.1 and Table 3.15), LDBr is the inductance of d.c. side including smoothing reactor (saturated value), connection and common branch (see Table 3.15) and κD the factor as per Figure 9.9. More details of the calculation of short-circuit currents fed from rectifiers are included in [54]. 9.5 Short-circuit currents from d.c. motors with independent excitation Branch short-circuit currents from d.c. motors with independent excitation are only considered if the total sum of the rated currents of all d.c. motors is greater than 1 per cent of the branch short-circuit currents of one rectifier. The parameters of the motor, i.e., rated voltage UrM , rated current IrM , saturated inductance of the field circuit at short-circuit LF and the unsaturated inductance Calculation in d.c. auxiliary installations 175 of the field circuit at no-load LOF , determine the quasi steady-state short-circuit current IkM which is calculated using  LF UrM − IrM ∗ RM IkM = (9.14) ∗ LOF RMBr where LF is the field inductance, LOF is field inductance at no-load, UrM is the rated voltage, IrM is the rated current of the motor, RM is the resistance of the motor and RMBr the resistance of the motor including connection and common branch (see Section 3.3.1 and Table 3.16). Equation (9.14) is valid when the speed of the motor remains constant during the duration of the short-circuit. When the speed of the motor decreases to zero (n → 0) the quasi steady-state short-circuit current is IkM = 0. The mechanical time constant τMec , the time constants of the field circuit τF and the armature circuit τM determine the peak short-circuit current ipM , which is calculated using ipM = κM ∗ UrM − IrM ∗ RM RMBr (9.15) The factor κM is equal to One in the case of nominal speed and in all cases where τMec ≥ 10∗ tF , else (τMec < 10 ∗ τF ). κM depends on the eigen-frequency ω0 , ω0 =   RM ∗ IrM 1 ∗ 1− τMec ∗ τM UrM (9.16a) where τMec is the mechanical time constant (see Table 3.16) and τM the time constant of armature circuit up to short-circuit location (see Table 3.16); and on the decay coefficient δ. 1 = 2 ∗ τM δ (9.16b) The reasonable range of the factor κM is outlined in Figure 9.10. The time to peak tpM , the rise-time and the decay-time constants τ1M and τ2M depend on the value of the mechanical time constant τMec . IEC 61660-1:1997 defines four factors k1M , k2M , k3M and k4M which are outlined in Figures 9.12 to 9.15. Calculation equations are not included in IEC 61000-1:1997. When the motor speed remains constant or in all cases when τMec ≥ 10 ∗ τF the time to peak tpM is calculated using tpM = k1M ∗ τM (9.17) the rise-time constant τ1M τ1M = k2M ∗ τM (9.18) 176 Short-circuit currents 1.1 1 1 0.9 M 0.8 20 0 0.7 0.6 0.5 . 100 0.4 0.3 0.2 0.1 0 1 ms 10 . Figure 9.10 100 1/d Factor κM for the calculation of peak short-circuit current of d.c. motors with independent excitation (according to Figure 17 of IEC 61660-1:1997) 1000 ms tpM 100 1 10 . 0 100 10 1 1 Figure 9.11 10 . 1/ ms 100 Time to peak of short-circuit currents for d.c. motors with independent excitation and τMec < 10 ∗ τF (according to Figure 19 of IEC 61660-1:1997) and the decay-time constant τ2M τ2M = τF τ2M = k4M ∗ n = nn = const. LOF ∗ τMec LF n→0 (9.19a) (9.19b) For all other cases, i.e., τMec < 10 ∗ τF the reasonable range of the time to peak tpM is outlined in Figure 9.11. Calculation in d.c. auxiliary installations 177 12 10 k1m 0.9 . LF /LOF 0.6 8 0.2 6 4 1 10 Figure 9.12 F/M . 100 1000 Factor k1M in the case of d.c. motors with independent excitation and τMec ≥ 10 ∗ τF (according to Figure 18 of IEC 61660-1:1997) 1 0.9 k2M 0.8 0.7 LF/LOF . 0.6 0.2 0.5 0.4 0.4 0.9 0,. 0.2 0.1 0 1 Figure 9.13 10 F/M . 100 1000 Factor k2M in the case of d.c. motors with independent excitation and τMec < 10 ∗ τF (according to Figure 18 of IEC 61660-1:1997) The rise-time constant and the decay-time constant τ1M and τ2M are calculated using τ1M = k3M ∗ τM τ2M = k4M ∗ τMec The factors k1M , k2M , k3M and k4M are outlined in Figures 9.12 to 9.15. (9.20a) (9.20b) 178 Short-circuit currents 1.1 1 1 0.9 10 0.8 k3M 0.7 0 . 0.6 100 0.5 0.4 0.3 0.2 0.1 0 1 Figure 9.14 10 1/ . 100 ms Factor k3M in the case of d.c. motors with independent excitation and τMec < 10 ∗ τF (according to Figure 20 of IEC 61660-1:1997) 10 9 k4M 8 7 . 6 5 4 100 0 3 50 2 1–10 1 0 1 Figure 9.15 10 1/ ms 100 Factor k4M in the case of d.c. motors with independent excitation and τMec < 10 ∗ τF (according to Figure 21 of IEC 61660-1:1997) More details of the calculation of short-circuit currents fed from motors with independent excitation are included in [52]. 9.6 Total short-circuit current The calculation of the total short-circuit current is carried out taking into account the common branches of the d.c. installation. A common branch is a branch, Calculation in d.c. auxiliary installations 179 e.g., conductor circuit, which carries branch short-circuit currents from different sources. When no common branch exists in the d.c. installation, the total short-circuit current is calculated by adding the branch (partial) short-circuit currents. Otherwise, the partial short-circuit currents of the different sources (Index j) are to be corrected (Index kor) with factors σj , which reflect the different resistances of the sources and the common branches RY . The peak short-circuit current and quasi steady-state short-circuit current are calculated by (9.21a) ipkorj = σj ∗ ipj (9.21b) Ikkorj = σj ∗ Ikj with the correction factor σj for each source j σj = Rresj ∗ (Rij + RY ) Rresj ∗ Rij + Rij ∗ RY + Rresj ∗ RY (9.22) The resistance up to the common branch of a source is named Rij and the equivalent resistance of the other sources up to the common branch which contributes to the short-circuit current is named Rresj . Resistances of capacitors are neglected and the resistance of motors shall only be taken into account if the motor contributes to the quasi steady-state short-circuit current. The calculation equations of the resistances Rij and equivalent resistances Rresj are outlined in Table 9.1. It is assumed, that all four sources are contributing to the short-circuit current through one common branch, as outlined in Figure 9.16. Table 9.1 Resistances Rij and equivalent resistances Rresj for the calculation of correction factors; U: Voltage at short-circuit location prior to the short-circuit [42,50,57] Source j Resistance Rij Equivalent resistance Rresj Capacitor RiC = RC + RCL RresC = Battery RiB = RB + RBL Rectifier RiD = d.c. motor with independent excitation RiM = RM + RML U − RY IkD 1 1/RiD + 1/RiB + 1/RiM 1 RresB = 1/RiD + 1/RiM 1 RresD = 1/RiB + 1/RiM 1 RresM = 1/RiD + 1/RiB Remarks: Index L – Connection of equipment; index Y – Common branch (see Section 3.3.1); and indices C; B; D; M – Capacitor; battery; rectifier; motor 180 Short-circuit currents M Motor Load Line (Coupling branch) Rectifier Battery Capacitor Figure 9.16 Equivalent circuit diagram of a d.c. auxiliary installation Rise-time and decay-time constants τ1M and τ2M of the partial short-circuit currents are not corrected. The total short-circuit current is calculated by superposition of the corrected partial short-circuit currents of the different sources. i1 (t) = m  i2 (t) = m  j =1 j =1 ipkorj ∗ ipkorj 1 − e−t/τ1j 1 − e−tpj /τ1j  1− Ikkorj ipkorj for 0 ≤ t ≤ tpj (9.23a) ∗ e−(t−tpj )/τ2j + Ikkorj ipkorj for tpj ≤ t ≤ Tk (9.23b) The calculation of the thermal and electromagnetic (mechanical) effects of shortcircuit currents as per IEC 61660-2 is based on the standard approximation function. Typical time-curves of total short-circuit currents are outlined in Figure 9.17. The peak short-circuit current ip , the quasi steady-state short-circuit current Ik and the decay-time constant τ2 are determined graphically from the time curve of the total short-circuit current. The rise-time constant is calculated in accordance with Calculation in d.c. auxiliary installations 181 (a) i ip 0.9 (ip – Ik) 31 22 Ik tp (b) t i 1 = min Ik t (c) i ip 0.9 (ip – Ik) 22 31 Ik t tp (d) i ip 1 = min 0.9 (ip – Ik) 2t2 Ik tp t Total short-circuit current Standard approximation function Figure 9.17 Typical time curves of total short-circuit current in d.c. auxiliary installations, e.g., (a) with dominating part of motors, (b) with dominating part of rectifiers, (c) with dominating part of batteries and (d) in the case of low rectifier load (according to Figure 22 of DIN EN 61660-1 (VDE 0102 Teil 10)) 182 Short-circuit currents Figure 9.17(a) and (c), respectively by τ1 = tp 3 (9.24a) and for time curves as per Figure 9.17(b) or (d) τ1 = MIN{τ1C ; τ1B ; τ1D ; τ1M } (9.24b) The rise-time constant τ1C of capacitors is neglected in the case where ipC ≤ 0.5 ∗ ip (9.25) The decay-time constant τ2 is equal to 50 per cent of that time span in which the short-circuit current i2 (t) is reduced to 0.9 ∗ (ip –Ik ), i.e., the short-circuit current has the value of (Ik + 0.1 ∗ ip ). Reference is made to Figure 9.17. i2 (tp + 2τ2 ) = 0.9 ∗ (ip − Ik ) (9.26a) i2 (tp + 2τ2 ) = Ik + 0.1 ∗ ip (9.26b) and 9.7 Example The short-circuit currents at location F at the main busbar of the auxiliary supply installation of a power station are to be calculated. The 220-V-installation as outlined in Figure 9.18 include a battery of 1100 Ah, feeding from an a.c. LV-system through rectifier with smoothing capacitor and a d.c. motor. The data and parameter of the equipment are given below: Q T D C Cable Rectifier Capacitor Q Battery Figure 9.18 F L1 L4 L3 M M L2 Cable coupling branch Cable Motor Load Busbar Equivalent circuit diagram of the d.c. auxiliary installation (220 V), e.g., of a power station Calculation in d.c. auxiliary installations 183 Equipment Quantity Parameter Remarks Battery B Nominal voltage Capacity for 10 h-discharge Resistance per cell Inductance per cell Number of cells UnB = 225 V K10 = 1100 Ah Table 3.14 Power system AC/DCtransformer Nominal voltage Initial short-circuit power Resistance UnQ = 660 V  = 33.3 MVA SkQ Rated voltages UrTHV /UrTLV = 660 V/240 V SrT = 380 kVA ukT = 3.2% PCu = 4 kW; uRT = 0.5% Table 3.2 Rated voltage Rated current Resistance Reactance a.c. capacitance Resistance UrD = 220 V IrD = 1000 A RDBr = 0.87 m XDBr = 29 µH Cac = 70 mF RC = 8 m Table 3.15 Rated voltage Rated power Rated current No-load speed Inductance of armature circuit Resistance of armature Inductance of field circuit Resistance of field circuit Moment of inertia Motor speed Tk > 1 s UrM = 220 V PrM = 95 kW IrM = 432 A n0 = 25 s−1 LM = 0.4 mH Rated power Impedance voltage Losses; resistance voltage Rectifier D Smoothing reactor Smoothing capacitor C d.c. motor M RBZ = 0.12 m LBZ = 0.2 µH n = 109 Table 3.1 RQ /XQ = 0.28 RM = 41.9 m LF = 9.9 H RF = 9.9  J = 6.5 kg m2 n→0 Table 3.15 Table 3.13 Table 3.16 184 Short-circuit currents Equipment Quantity Parameter Remarks Cables L1; L2; L3 Cross section Number of cables Specific resistance Radius of conductor Length of cables Table 3.12 Conductor bars L4 Cross section Number of bars Width and height Specific resistance Distance between sub-conductors Distance of bars Length of bar qn = 300 mm2 3 in parallel (triangle) ρ = 0.0173 mm2 /m r = 10.5 mm L1 = 2 m; L2 = 6 m; L3 = 20 m qn = 400 mm2 2 in parallel d × b = 10 mm × 40 mm ρ = 0.0173 mm2 /m aS = 10 mm Table 3.12 am = 75 mm L4 = 14 m The calculation of the short-circuit current is as follows: 1 Calculation of the impedances of cables and busbar conductors (Section 9.7.1). 2 Calculation of the short-circuit currents of the individual equipment (Section 9.7.2). 3 Calculation of the correction factors (Section 9.7.3). 4 Calculation of partial short-circuit currents (Section 9.7.4). 5 Calculation of total short-circuit current (Section 9.7.5). 9.7.1 Calculation of the impedances of cables and busbar conductors Three cables are laid in triangle arrangement. Specific resistance and inductance are calculated according to Table 3.12. 0.0173 mm2 /m ρ =2 = 0.0384 m/m 3qn 3 ∗ 300 mm2  a μ0 1  L = ∗ ln + π rB 4n R = 2 with rB = n n ∗ rT ∗ r n−1 = 3 3 ∗ 17.3 mm ∗ (10.5 mm)2 = 17.9 mm  1 75 mm 4π ∗ 10−7 H/m L = + ln π 17.9 mm 4 ∗ 3  = 0.607 µH/m Calculation in d.c. auxiliary installations 185 Two rectangular busbars are laid in parallel. Specific resistance and inductance are calculated according to Table 3.12. ρ 0.0173 mm2 /m = 0.0433 m/m =2∗ 2qn 2 ∗ 400 mm2  μ0 a ∗ ln L = π 0.223 ∗ (2d + dS + b)  4π ∗ 10−7 H/m 75 mm = ∗ ln = 0.628 µH/m π 0.223 ∗ (30 + 40) mm R = 2 The resistances and inductances of the individual connections by cables and bars as per Figure 9.18 are summarised below: Connection L1 Length(m) 2 Resistance R(m) 0.0768 Inductance L(µH) 1.212 L2 6 0.2304 3.636 L3 L4 20 14 0.768 0.606 12.12 8.792 9.7.2 Calculation of the short-circuit currents of the individual equipment 9.7.2.1 Short-circuit current from capacitor Total impedance of the capacitor according to Table 3.13 with common branch (cable L2) and capacitor connection (cable L1) RCBr = RC + RL1 + RL2 = (8 + 0.0708 + 0.2304) m = 8.301 m LCBr = LL1 + LL2 = (1.212 + 3.636) µH = 4.848 µH Peak short-circuit current as per Equation (9.3) ipC = κC ∗ EC RCBr Factor κC depends on the eigen-frequency ω0 1 1 = 1.717 ∗ 103 /s ω0 = √ =√ 4.848 µH ∗ 70 mF LCBr ∗ C and on the decay coefficient δ 1 2 ∗ LCBr 2 ∗ 4.848 µH = = 1.168 ms = δ RCBr 8.301 m → κC = 0.65 as per Figure 9.3 ipC = κC ∗ EC 225 V = 17.62 kA = 0.65 ∗ RCBr 8.301 m Time-to-peak tpC = 1.1 ms as per Figure 9.4. 186 Short-circuit currents Rise-time constant and decay-time constant as per Equation (9.5) are τ1C = k1C ∗ tpC τ2C = k2C ∗ RCBr ∗ C With factors k1C and k2C depending on eigen-frequency and decay component k1C ≈ 0.38 as per Figure 9.5 and k2C ≈ 1.4 as per Figure 9.6 τ1C = 0.38 ∗ 11 ms = 0.42 ms τ2C = 1.4 ∗ 8.301 m ∗ 70 mF = 0.813 ms 9.7.2.2 Short-circuit current from battery Total impedance of the battery as per Table 3.14 with common branch (cable L2) and battery connection (cable L4). The battery consists of 109 cells. RBBr = 0.9 ∗ RB + RL4 + RL2 = (0.9 ∗ 109 ∗ 0.12 + 0.606 + 0.2304) m = 12.608 m LBBr = LB + LL4 + LL2 = (109 ∗ 0.2 + 8.792 + 3.636) µH = 34.228 µH Quasi steady-state short-circuit current as per Equation (9.6) IkB = 0.95 ∗ 1.05 ∗ 225 V 0.95 ∗ EB = 16.13 kA = RBBr + 0.1 ∗ RB (12.608 + 0.1 ∗ 109 ∗ 0.12) m Peak short-circuit current according to Equation (9.7) is ipB = 1.05 ∗ 225 V EB = = 18.74 kA RBBr 12.608 m The decay component δ is 1 2 2 = = = 4.98 ms δ RBBr /LBBr + 1/TB 12.608 m/34.228 µH + 1/30 ms Time-to-peak and rise-time constant as per Figure 9.7 are tpB = 13.7 ms and τ1B = 2.6 ms. The decay-time constant is τ2B = 100 ms per definition. 9.7.2.3 Short-circuit current from rectifier Impedance of system feeder Q related to 220 V as per Table 3.1 ZQ = 2 c ∗ UnQ  SkQ = 1.0 ∗ (220 V)2 = 1.73 m 33.3 MVA Calculation in d.c. auxiliary installations 187 Resistance and reactance due to the ratio of RQ /XQ XQ = 0.963 ∗ ZQ = 1.666 m RQ = 2 − X 2 = 0.466 m ZQ Q Impedance of transformer according to Table 3.2 ZT = 2 ukT UrTLV 3.2% (240 V)2 ∗ = ∗ = 4.85 m SrT 100% 380 kVA 100% RT = 2 uRT UrTLV 1.05% (240 V)2 ∗ = ∗ = 1.592 m SrT 100% 380 kVA 100% XT = ZT2 − RT2 = 4.581 m Total impedance a.c. side according to Table 3.15 RN = RQ + RT = (0.466 + 1.592) m = 2.058 m XN = XQ + XT = (1.666 + 4.581) m = 6.247 m and inductance LN = XN /ω = (6.247/100 ∗ π) µH = 4.581 µH Total impedance d.c. side according to Table 3.15 with common branch (cable L2) RDBr = RS + RL1 + RL2 = (0.87 + 0.0768 + 0.2304) m = 1.177 m LDBr = LS + LL1 + LL2 = (29 + 1.212 + 3.636) µH = 33.85 µH Quasi steady-state short-circuit current of the rectifier as per Equation (9.9) √ UrTLV 3∗ 2 c ∗ Un ∗ ∗√ IkD = λD ∗ π 3 ∗ ZN UrTHV Factor λD depending on RN /XN and RDBr /RN RN /XN = 0.33 and RDBr /RN = 0.572 → λD = 0.92 as per Figure 9.8 IkD √ 240 V 1.0 ∗ 240 V 3∗ 2 ∗ ∗√ = 26.44 kA = 0.92 ∗ π 3 ∗ 6.58 m 660 V Peak short-circuit current as per Equation (9.10) ipD = κD ∗ IkD Factor κD depends on LDBr /LN and RN , RBBr and XN  2 RDBr RN LDBr /LN = 1.702 and 1+ ∗ = 0.455 → κD = 1.12 XN 3 RN 188 Short-circuit currents as per Figure 9.9 ipD = 1.12 ∗ 26.44 kA = 29.61 kA Time to peak according to Equation (9.11b) as κD = 1.12 ≥ 1.05 and LDBr /LN = 1.702 > 1   LDBr tpD = (3 ∗ κD + 6) + 4 −1 LN   33.85 = (3 ∗ 1.12 + 6) + 4 −1 ms = 12.17 ms 19.89 Rise-time constant τ1D as per Equation (9.12a)   LDBr τ1D = 2 + (κD − 0.9) ∗ 2.5 + 9 ∗ LN   33.85 = 2 + (1.12 − 0.9) ∗ 2.5 + 9 ∗ 19.89 ms = 5.92 ms Decay-time constant τ2D as per Equation (9.13) 2 RN /XN ∗ (0.6 + 0.9 ∗ RDBr /RN ) 2 = ms = 5.44 ms 2.058/6.247 ∗ (0.6 + 0.9 ∗ 1.177/2.058) τ2D = 9.7.2.4 Short-circuit currents from d.c. motor Total impedance of the motor as per Table 3.16 with connection cable L3, common branch is neglected in this case RMBr = RM + RL3 = (41.9 + 0.768) m LMBr = LM + LL3 = (400 + 12.12) µH = 412.12 µH Quasi steady-state short-circuit current (n → 0) IkM = 0 Peak short-circuit current according to Equation (9.15) ipM = κM ∗ UrM − IrM ∗ RM RMBr With factor κM depending on the eigen-frequency ω0 and on the decay coefficient δ as per Equation (9.16)   1 RM ∗ IrM ω0 = ∗ 1− τMec ∗ τM UrM 1 = 2 ∗ τM δ Calculation in d.c. auxiliary installations 189 Mechanical time constant as per Table 3.16 τMec = 2π ∗ n0 J ∗ RMZw ∗ IrM 2π ∗ n0 ∗ J ∗ RMZw ∗ IrM = Mr ∗ UrM (PrM /2π n0 ) ∗ UrM τMec = 2π ∗ 25/s ∗ 6.5 kgm2 ∗ 42.67 m ∗ 432 A = 134.4 ms (100 kW/2π ∗ 25/s) ∗ 220 V Time constant of armature circuit as per Table 3.16 τM = 412.12 µH LMBr = 9.66 ms = RMBr 42.67 m Time constant of the field circuit τF = 9.9 H LF =1s = RF 9.9  Giving the eigen-frequency ω0 =   1 41.9 m ∗ 432 A ∗ 1− 134.4 ms ∗ 9.66 ms 220 V = 37.61/s and the decay coefficient 1/δ = 2 ∗ 9.66 ms = 19.32 ms. As τMec = 134.4 ms < 10∗ tF = 100 s → κM = 0.81 as per Figure 9.10 ipM = 0.81 ∗ 220 V − 432 A ∗ 41.9 m = 3.83 kA 42.67 m Time to peak as τMec < 10 ∗ τF tpM = 28 ms according to Figure 9.11 Rise-time and decay-time as per Equation (9.20) constants depend on the mechanical time constant as per Equations (9.18) to (9.19) τ1M = k3M ∗ τM τ2M = k4M ∗ τMec with factors k3M and k4M k3M = 0.78 according to Figure 9.14 k4M = 1.05 according to Figure 9.15 τ1M = 0.78 ∗ 9.66 ms = 7.53 ms τ2M = 1.05 ∗ 134.4 ms = 141.1 ms 190 Short-circuit currents 9.7.2.5 Summary of results The result of the short-circuit currents of the individual equipment are summarised below Symbol Equipment ip (kA) Ik (kA) tp (ms) τ1 (ms) τ2 (ms) C B D M 17.62 18.74 29.61 3.83 0.98 100 5.44 141.1 Capacitor Battery Rectifier Motor 0.0 16.13 26.44 0.0 1.1 13.7 12.17 28 0.42 2.6 5.92 7.53 9.7.3 Calculation of the correction factors and corrected parameters Correction factors σ as per Table 9.1 are only to be calculated for rectifier, capacitor and battery, as the motor feeds the short-circuit directly. Source j Resistance Rij Capacitor Battery Rectifier Motor Equivalent resistance Rresj 1 (1/RiD ) + (1/RiB ) + (1/RiM ) 1 RresC = RiC = RC m (1/8.29) + (1/13.686) RiC = 8 m RresC = 5.16 m 1 RresB = RiB = RB + RL4 (1/RiD ) + (1/RiM ) RiB = (109 ∗ 0.12 + 0.606) m RresB = RiD RiB = 13.686 m RresB = 8.29 m U 1 − RL2 RresD = RiD = IkD (1/RiB) + (1/RiM ) 225 V − 0.2304 m RresD = RiB RiD = 26.44 kA RiD = 8.29 m RresD = 13.686 m RiM = RM + RL3 As the motor is feeding RiM = (41.9 + 0.768) m the short-circuit directly, RiM is RiM = 42.668 m neglected RiC = RC + RCL RresC = Calculation of correction factors σ as per Equation (9.22) • Capacitor RresC ∗ (RiC + RL2 ) RresC ∗ RiC + RiC ∗ RL2 + RresC ∗ RL2 5.16 ∗ (8 + 0.2304) = 0.958 σC = 5.16 ∗ 8 + 8 ∗ 0.2304 + 5.16 ∗ 0.2304 σC = Calculation in d.c. auxiliary installations 191 • • Battery σB = RresB ∗ (RiB + RL2 ) RresC ∗ RiB + RiB ∗ RL2 + RresB ∗ RL2 σB = 8.29 ∗ (13.686 + 0.2304) = 0.973 8.29 ∗ 13.686 + 13.686 ∗ 0.2304 + 8.29 ∗ 0.2304 Rectifier σD = RresD ∗ (RiD + RL2 ) RresD ∗ RiD + RiD ∗ RL2 + RresD ∗ RL2 σD = 13.686 ∗ (8.29 + 0.2304) = 0.984 13.686 ∗ 8.29 + 8.29 ∗ 0.2304 + 13.686 ∗ 0.2304 • Motor Correction factor of the motor is set to 1, as the motor is feeding the short-circuit directly. • Correction of parameters Correction of peak short-circuit current and quasi steady-state short-circuit current is carried out for the individual results based on Equation (9.21) ipkorj = σj ∗ ipj Ikkorj = σj ∗ Ikj Symbol Equipment σ C B D M Capacitor Battery Rectifier Motor ip Ik ipkor Ikkor tp (kA) (kA) (kA) (kA) (ms) τ1 τ2 (ms) (ms) 0.958 17.62 0.0 16.88 0.0 1.1 0.42 0.973 18.74 16.13 18.23 15.69 13.7 2.6 0.984 29.61 26.44 29.14 26.02 12.17 5.92 1 3.83 0.0 3.83 0.0 28 7.53 9.7.4 Calculation of partial short-circuit currents The partial short-circuit currents are calculated based on Equation (9.1) 1 − e−t/τ1 1 − e−tp /τ1  Ik Ik i2 (t) = ip ∗ e−(t−tp )/τ2 + 1− ip ip i1 (t) = ip ∗ for 0 ≤ t ≤ tp for tp ≤ t ≤ Tk 0.98 100 5.44 141.1 192 Short-circuit currents • Capacitor 1 − e−t/0.42 1 − e−1.1/0.42 i1C (t) = 16.88 kA ∗ • i1C (t) = 18.21 kA ∗ (1 − e−t/0.42 ) for 0 ≤ t ≤ 1.1 ms i2C (t) = 16.88 kA ∗ (1 − e−(t−1.1)/0.98 ) for 1.1 ms ≤ t ≤ Tk Battery 1 − e−t/2.6 1 − e−13.7/2.6 i1B (t) = 18.23 kA ∗ i1B (t) = 18.32 kA ∗ (1 − e−t/2.6 )  i2B (t) = 16.88 kA ∗ 1− 15.69 18.23 for 0 ≤ t ≤ 13.7 ms ∗ e−(t−13.7)/100 + 15.69 18.23 i2B (t) = 16.88 kA ∗ (0.139 ∗ e−(t−13.7)/100 + 0.861) for 13.7 ms ≤ t ≤ Tk • Rectifier i1D (t) = 29.14 kA ∗ 1 − e−t/5.92 1 − e−12.17/5.92 i1D (t) = 33.42 kA ∗ (1 − e−t/5.2 )  26.02 i2D (t) = 29.14 kA ∗ 1− 29.14 for 0 ≤ t ≤ 12.17 ms ∗ e−(t−12.17)/5.44 + 26.02 29.14 i2D (t) = 29.14 kA ∗ (0.107 ∗ e−(t−12.17)/5.44 + 0.893) for 12.17 ms ≤ t ≤ Tk • Motor i1M (t) = 3.83 kA ∗ 1 − e−t/7.53 1 − e−28/7.53 i1M (t) = 3.83 kA ∗ (1 − e−t/7.53 ) for 0 ≤ t ≤ 28 ms i2M (t) = 3.83 kA ∗ e−(t−28)/141.1 for 28 ms ≤ t ≤ Tk The corrected partial short-circuit currents of the different equipment (sources) are outlined in Figure 9.19. Calculation in d.c. auxiliary installations 193 60 0.9(ip–Ik) Total ip = 50.5 kA 50 Ik = 46.6 kA 2t2 = 34.5 ms Current in A 40 30 Rectifier 20 Battery 10 0 Capacitor tp = 12.1 ms 0 Figure 9.19 10 Motor 20 30 Time in ms 40 50 60 Partial short-circuit currents and total short-circuit current, d.c. auxiliary system as per Figure 9.18 9.7.5 Calculation of total short-circuit current The total short-circuit current is calculated by superposition of the corrected partial short-circuit currents of the different sources as per Equation (9.23) i1 (t) = m  ipkorj ∗ i2 (t) = m  ipkorj j =1 j =1 1 − e−t/τ1j 1 − e−tpj /τ1 j  1− Ikkorj ipkorj for 0 ≤ t ≤ tpj ∗ e−(t−tpj )/τ2j + Ikkorj ipkorj for tpj ≤ t ≤ TK The total short-circuit current obtained by superposition is outlined in Figure 9.19. The peak short-circuit current ip = 50.5 kA the quasi steady-state short-circuit current Ik = 46.6 kA the time-to-peak tp = 12.1 ms and the decay-time constant τ2 = 17.3 ms 194 Short-circuit currents 60 Iappr 50 Isup Current in A 40 Approximated total short-circuit current Iappr 30 Total short-circuit current by superposition Isup 20 10 0 0 10 Figure 9.20 20 30 Time in ms 40 50 60 Total short-circuit current, obtained by superposition of the partial short-circuit currents and approximated short-circuit current, d.c. auxiliary system as per Figure 9.18 are obtained from Figure 9.19 as indicated. The rise-time constant can be estimated according to Equation (9.24) either by τ1 = tp 12.1 ms = = 4.03 ms 3 3 (time course as per Figure 9.17(a) and (c)) or τ1 = MIN{τ1C ; τ1B ; τ1D ; τ1M } (time course as per Figure 9.17(b) and (d)) τ1 = MIN{5.92; 2.6; 0.42; 7.53} ms = 0.42 ms Comparison of the two different values revealed that the approximated time course of the total short-circuit current fits best to the superposition of the partial short-circuit currents, see Figure 9.20, if the rise-time constant is τ1 = 4.03 ms, which also is in line with the typical time course of the short-circuit current as per Figure 9.17(b) and (d). Chapter 10 Effects of short-circuit currents 10.1 General Calculation methods for the thermal and electromagnetic effects of short-circuit currents are dealt with within IEC 61660-2, which is applicable to short-circuit currents in d.c. auxiliary installations in power plants and substations and IEC 60865-1, related to three-phase a.c. systems. 10.2 10.2.1 a.c. systems Thermal effects and thermal short-circuit strength The thermal withstand capability (thermal short-circuit strength) of equipment is determined by the maximal permissible conductor temperature prior to the shortcircuit, the duration of the short-circuit and the short-circuit current itself. The maximal permissible temperature of conductors under normal operating conditions and in the case of short-circuits, e.g., as per DIN VDE 0276, is summarised in Table 10.1. Figures are given for a short-circuit duration of Tk = 5 s. It is assumed that no heat transfer is taking place during the short-circuit duration (adiabatic heating). Skin- and proximity-effects are neglected, the specific caloric heat of the conductor and insulation is constant and the relation resistance-to-temperature is linear. Special consideration is to be taken for conductors in a.c. installations with cross-section above 600 mm2 , as the skin-effect has to be taken into account. Additional requirements according to IEC 60986:1989 and IEC 60949:1988 for cables and isolated conductors are to be met. 10.2.1.1 Conductors and equipment The analysis is based on the calculation of the thermal equivalent short-time current Ith   Tk 2 Q 0 ik (t) dt Ith = = (10.1) R ∗ Tk R ∗ Tk 196 Short-circuit currents Table 10.1 Maximal permissible conductor temperature and rated short-time current density; 1) – Normal operating condition; 2) – Short-circuit condition Type of cable Maximum Temperature at beginning of short-circuit (◦ C) permissible temperature 90 80 70 65 60 50 40 30 20 (◦ C) Rated short-time current density in A/mm2 ; tkr = 1 s 1) 2) Copper conductor Cables with soft-soldering XPE-cables PVC-cables (mm2 ) ≤300 >300 Mass-impregnated cables (kV) 0.6/1 3.6/6 6/10 12/20 18/30 Radial-screen cable 12/20 — 160 100 108 115 119 122 129 136 143 150 90 250 143 149 154 157 159 165 170 176 181 70 160 70 140 — — — — 115 119 122 129 136 143 150 103 107 111 118 126 133 140 80 80 70 65 60 65 — — — — — — 149 113 — — — — 154 120 120 — — — 250 170 170 170 150 170 157 124 124 124 — 124 159 127 127 127 117 127 165 134 134 134 124 134 170 141 141 141 131 141 176 147 147 147 138 147 181 154 154 154 145 154 Aluminium conductor XPE-cables PVC-cables (mm2 ) ≤300 >300 Mass-impregnated cables (kV) 0.6/1 3.6/6 6/10 12/20 18/30 Radial-screen cable 12/20 90 250 94 98 102 104 105 109 113 116 120 70 160 70 140 — — — — 80 80 70 65 60 65 — — — — — — 98 75 — — — — 250 170 170 170 150 170 76 68 78 71 81 73 85 78 90 83 95 88 99 93 102 104 105 109 113 116 120 80 82 84 89 93 97 102 80 82 84 89 93 97 102 — 82 84 89 93 97 102 — — 77 82 87 91 96 — 82 84 89 93 97 102 where Q is the thermal heat produced by the short-circuit current, R the resistance of the equipment, Tk the short-circuit duration and ik (t) the time course of shortcircuit current which produces the same thermal heat Q within the conductor as the short-circuit current ik (t) during the short-circuit duration Tk . The thermal equivalent Effects of short-circuit currents 197 short-time current is calculated from the initial short-circuit current Ik by using √ Ith = Ik ∗ m + n (10.2) The factors m and n represent the heat dissipation of the d.c. component and the a.c. component of the short-circuit current [38]. Suitable ranges of values for m and n are outlined in Figures 10.1 and 10.2. If an interrupting short-circuit is present or if multiple short-circuits (number n) occur with different duration Tki and current Ithi the resulting thermal equivalent rated short-time current is   n 1  2 ∗T  Ith = (10.3) Ithi ki Tk i=1 where Tk = n  Tki i=1 IEC 60909-0 includes calculation equations for the factors m and n. 1.1 1 . 1 0.9 . 2.5 0.8 0.7 n 0.6 I ⬙k / Ik 10 0.5 0.4 0.3 0.2 0.1 0 0.01 Figure 10.1 0.1 1 Tk 10 Factor n for the calculation of thermal short-time current (heat dissipation of a.c. component) (according to Figure 22 of IEC 60909-0:2001) According to IEC 60865-1 separate considerations have to be taken concerning the thermal strength of equipment, i.e., transformers, transducers, etc., and conductors, i.e., busbars, cables, etc. Equipment have a suitable thermal short-circuit strength if the rated short-time short-circuit current Ithr (as per manufacturer’s data) for the short-circuit duration Tk < Tkr (e.g., Tkr = 1 s) is above the thermal equivalent short-circuit current Ith . Ith ≤ Ithr for Tk ≤ Tkr (10.4a) 198 Short-circuit currents 2 1.8 1.6 1.4 1.2 m 1 1.95 0.8 0.6 1.6 0.4 0.2 k 1.1 0 0.1 1 Figure 10.2 10 100 Tk 1000 Factor m for the calculation of thermal short-time current (heat dissipation of d.c. component) (according to Figure 21 of IEC 60909-0:2001) In case the short-circuit duration Tk is longer than the rated short-circuit duration Tkr , the thermal short-circuit strength is fulfilled if  Tkr Ith ≤ Ithr ∗ for Tk ≥ Tkr (10.4b) Tk The maximal permissible values for conductor material can be obtained from Figure 10.3. In the case of bare conductors the thermal short-time current density Jth is calculated on the basis of the thermal equivalent short-time current and the conductor cross-section qn . Jth = Ith qn (10.5) where qn is the nominal cross-section of conductor and Ith is the equivalent short-circuit current. In the case of overhead line conductors of the Al/St-type, only the cross-section of the aluminium part is considered. Conductors have sufficient thermal short-circuit strength if  Tkr (10.6) Jth ≤ Jthr ∗ Tk Values for the rated short-time current density are included in Table 10.1 and Figure 10.3. In IEC 60865 equations for the calculation of rated short-time current density are included. Effects of short-circuit currents 199 A/mm2 (a) 200 180 d1 160 300°C 140 250°C 120 200°C 180°C 100 Jthr 80 160°C 60 140°C 40 300°C 250°C 200°C 100°C 120°C 20 0 A/mm2 (b) 140 120 d1 100 300°C 250°C 80 200°C 180°C 160°C 140°C Jthr 60 40 100°C 20 0 20 40 60 80 100 120°C 120 130 °C d0 Figure 10.3 Rated short-time current density of conductors. δ0 is the temperature at beginning of short-circuit and δ1 is the temperature at end of shortcircuit [1]. (a) ——: Copper; - - - -: unalloyed steel and steel cables and (b) Al, aluminium alloy, ACSR Regarding non-insulated conductors, e.g., bare conductors and busbars, the thermal equivalent short-time current density is allowed to exceed the rated short-time current density in the case Tk < Tkr . Manufacturer’s cable lists usually include data on the maximal permissible thermal short-circuit currents Ithz . An example is outlined in Figure 10.4. The rated short-time current is given for a short-circuit duration of Tk = 1 s. 10.2.1.2 Cable screening, armouring and sheath Sheaths, screening and armouring of cables carry parts of the short-circuit current in the case of asymmetrical short-circuits. Depending on the type of the short-circuit and the method of cable-laying, this current can be in the range of the short-circuit current itself, e.g., when the cables are laid in air or on wall-racks. In case cables are laid in earth the part of the short-circuit current through the sheaths, armouring and 200 Short-circuit currents kA 100 90 80 70 60 50 40 30 25 20 mm2 15 300 240 Ithz 300 185 240 150 185 120 150 95 10 9 8 7 6 5 120 q 70 95 4 3 50 70 2.5 2 1.5 1 0.1 Figure 10.4 35 50 Cu Al 0.2 0.3 0.4 0.5 0.6 0.8 tk 1 1.5 2 3 4 5s 25 35 25 16 Maximal permissible thermal short-circuit current for impregnated paper-insulated cables Un up to 10 kV Source: KABELRHEYDT screening is lower than the short-circuit current, as one part is flowing through earth as well. Due to the comparatively high specific resistance of lead (used for sheaths) and steel (used for armouring), the short-circuit current preferably flows through the screening made from copper or aluminium. Data of the different materials are outlined in Table 10.2. Due to different production processes and degree of purity of the material, data obtained from other tables can be slightly different. The maximal permissible temperature δ0 or screening and sheaths of cables are to be observed in the case of short-circuits. It is assumed for the analysis that the heat Effects of short-circuit currents 201 Table 10.2 Data of materials for screening, armouring and sheaths of cables Material Specific caloric heat (J/K ∗ mm3 ) Specific resistance ( ∗ mm2 /m) Temperature coefficient of resistance (K−1 ) Copper Aluminium Lead Steel 3.48 ∗ 10−3 2.39 ∗ 10−3 1.45 ∗ 10−3 3.56 ∗ 10−3 17.28 ∗ 10−6 28.6 ∗ 10−6 214 ∗ 10−6 143 ∗ 10−6 3.8 ∗ 10−3 4.0 ∗ 10−3 4.35 ∗ 10−3 4.95 ∗ 10−3 production within the cable during the short-circuit duration is an adiabatic process. The heat is dissipated to the surroundings only after the short-circuit is switched-off. The maximal permissible short-circuit current density Jthz , respectively the maximal permissible short-circuit current Ithz , for the given cross-section qn is calculated by   δ1 + β 1 Qc ∗ (β + 20◦ C) ∗ ln (10.7a) ∗√ Jthz = ρ20 δ0 + β Tkr Ithz =   δ1 + β Qc ∗ (β + 20◦ C) ∗ ln ρ20 δ0 + β qn ∗√ Tkr (10.7b) where Qc is the specific caloric heat, α0 is the thermal coefficient of resistance, β is the parameter: β = 1/α0 − 20◦ C, δ1 is the maximal permissible temperature at end of short-circuit, δ0 is the maximal permissible temperature at beginning of short-circuit, ρ20 is the specific resistance at 20◦ C, qn the nominal cross-section of screening or sheath and Tkr is the rated short-circuit duration. The calculation for short-circuit duration different from the rated short-circuit duration is performed using  Tkr for Tk ≥ Tkr (10.4b) Ith ≤ Ithr ∗ Tk 10.2.2 Mechanical short-circuit strength of rigid conductors 10.2.2.1 General Currents in conductors induce electromagnetic forces into other conductors. The arrangement of parallel conductors, such as busbars and conductors of overhead lines, is of special interest as the electromagnetic forces will be maximal as compared with transversal arrangements. Three-phase and double-phase short-circuits without earth connection normally cause the highest forces. The currents inducing the electromagnetic forces are a function of time; therefore the forces are also a function of 202 Short-circuit currents time. Electromagnetic forces lead to stresses in rigid conductors, to forces (bending, compression and tensile stress) on support structures and to tensile forces in slack conductors. Within this section, only stresses on rigid conductors are explained. 10.2.2.2 Electromagnetic forces Figure 10.5 shows the arrangement of parallel conductors as can be found in busbar arrangements. In the case of a double-phase short-circuit without earth connection the forces on the conductors Y and B are μ0 l ∗ ∗ i Y ∗ iB (10.8) Fk2 = 2π a where μ0 is the permeability, a is the spacing of conductors, l is the length of conductors and iY ; iB are the peak values of short-circuit current in phases Y and B.  = 2r B a Y a R l Figure 10.5 Arrangement of parallel conductors Assuming that the distance between the support structures is large as compared with the spacing between the conductors [13], which on the other hand is assumed to be large as compared with the conductor radius r (l/a > 10; a/r > 10), typical in high-voltage installations, the Skin- and Proximity-effects can be neglected. The amplitude of the force Fk2 is acting always in the same direction. In the case of a three-phase short-circuit, the central conductor is exposed to the maximal force, as the magnetic fields caused by the outer conductors R and B are superimposed. The force Fk3 on the central conductor acting in the opposite direction is μ0 l (10.9) ∗ ∗ iY ∗ (iR − iB ) Fk3 = 2π a Due to the decaying d.c. component, the maximal forces act immediately after the initiation of the short-circuit. With the peak short-circuit current ip2 , respectively ip3 , being the maximal value of the short-circuit current the maximal forces are l μ0 ∗ ∗ i2 (10.10) 2π am p2 √ l μ0 3 2 ∗ ∗ ip3 ∗ (10.11) Fk3 max = 2π am 2 In the case the conductors are arranged at the edges of an isosceles triangle, the calculation of the forces is identical to that mentioned above. Fk2 max = Effects of short-circuit currents 203 The assumptions made above for the spacing and lengths (l/a > 10; a/r > 10), are normally not fulfilled in low-voltage and medium-voltage installations. The Skin- and Proximity-effects cannot be neglected and the influence on the electromagnetic forces is considered by the effective distance am using a correction factor k12 a (10.12) am = k12 A suitable range of values of the correction factor k12 for conductors with rectangular cross-section is given in Figure 10.6. The electromagnetic force is increased in the case of flat conductor arrangement and reduced in the case of standing arrangement as compared with circular cross-section. 1.3 1.2 < 0.1 1.1 k12 1 1.0 0.9 k1ss 0.8 . 5.0 0.7 0.6 b/d 0.5 20.0 0.4 0.3 0.2 1 10 Figure 10.6 a1s /d 100 Correction factor k12 for the calculation of effective distance (according to Figure 1 of IEC 61660-2:1997) If the main conductor is composed of several sub-conductors (number n), each sub-conductor carries only the nth part of total current and the maximal force Fs max on the sub-conductors is  ip 2 μ0 ls (10.13) ∗ ∗ Fs max = 2π as n where ls is the length of sub-conductor, n is the number of sub-conductors, as is the spacing between sub-conductors and ip is the peak short-circuit current. The three-phase short-circuit in three-phase systems, respectively the two-phase short-circuit in two-phase systems, will cause the maximal force. The effective distance of the sub-conductors as in the case of circular cross-section is n  1 a1i = as i=2 (10.14a) 204 Short-circuit currents and for rectangular cross-section n  k1i 1 = as a1i (10.14b) i=2 whereas the factor k1i (named k1ss ) can be taken from Figure 10.6. 10.2.2.3 Calculation of stresses in rigid conductors The forces on the support structures of conductors and the stresses in the conductors themselves depend on the type of mechanical fixing and the elasticity. The mechanical system composed of conductor, fixing and supporting structure has a mechanical natural frequency, which can be actuated by the frequency of the current (50 Hz or 60 Hz), thus increasing the mechanical forces. As axial forces in rigid conductors can be neglected, the bending stress σm for the main conductor, respectively σs for the sub-conductors, are calculated using Fm ∗ l 8∗Z Fs ∗ ls σs = Vσ s ∗ Vrs ∗ 8 ∗ Zs (10.15a) σm = Vσ ∗ Vr ∗ β ∗ (10.15b) where l; ls are the lengths of conductor, respectively sub-conductor, Fm ; Fs are the forces on main conductor respectively on sub-conductor, V is the factor as explained below and Zs is the section moduli depending on the shape of conductor. Whereas Fm respectively Fs is the force Fm3 in the case of three-phase short-circuits in three-phase systems. In two-phase systems the force Fm2 in the case of two-phase short-circuits has to be used. Typical ranges of values of the factors Vσ , Vr (respectively Vσ s , Vrs ) are shown in Figures 10.7 and 10.8. The factor β takes account of type and number of supports and can be obtained from Table 10.3. Table 10.3 Factors α, β and γ for different arrangement of supports (according to Table 3 of IEC 60865-1:1993) Type of bar and fixing of support Single-span bar Multiple-span bar with equidistant simple supports Factor α Factor β Factor γ Support A Support B Both simple A: fixed B: simple Both fixed 0.5 0.625 0.5 0.375 1 0.73 1.57 2.45 0.5 0.5 0.5 3.56 2 spans A:fixed B: simple 3 and more bars A: fixed B: simple 0.375 1.25 0.73 2.45 0.4 1.1 0.73 3.56 Effects of short-circuit currents 205 1.2 1 V 0.8 1.25  . V s . 0.6 Three-phase and double-phase short-circuits 1.0 >1.6 0.4 0.2 0 0.01 Figure 10.7 0.1 1 fc /f 10 Factors Vσ and Vσ s for the calculation of bending stress (according to Figure 4 of IEC 60865-1:1993) 1.9 1.8 1.7 Vr 1.6 1.5 . Vrs 1.4 1.3 1.2 1.1 1 0.01 Figure 10.8 0.1 1 fc /f 10 Factors Vr and Vrs for the calculation of bending stress (according to Figure 5 of IEC 60865-1:1993) If the busbar consists of multiple bars supported in unequal distances, the maximal supporting distance is regarded. If the supporting distance is less than 20 per cent of the distance of neighbouring bars, the bars have to be coupled by joints. Joints between two supports are permitted, if the distance between the supporting points is less than 70 per cent of the supporting distances of neighbouring bars. The values of section moduli Z, respectively Zs , for typical arrangements of rectangular cross-sections with stiffening elements are outlined in Table 5 of IEC 60865-1:1993. Values for Z are between 0.867 d 2 b and 3.48 d 2 b, with b being the height of the conductor and d the thickness of the conductor, respectively the 206 Short-circuit currents stiffening element. Furthermore, the factor of plasticity q has to be considered. Values of q are given for typical arrangements in Table 4 of IEC EN 608651:1993. Values for q are between 1.19 and 1.83 for rectangular cross-section and for U-, H- and I-shape profiles. In the case of circular ring section type conductors, the factor of plasticity depends on the diameter and the thickness of the wall. Reference is made to IEC 61865-1:1993. The conductor has sufficient electromagnetic strength with respect to bending stress, if the bending stress value σm is below the product of factor of plasticity and the stress corresponding to the yield point. σm ≤ q ∗ Rp0.2 (10.16) When the distance between the conductors is affected significantly by the shortcircuit, the value of the plasticity factor shall be set to q = 1. If the conductor is composed of sub-conductors the total bending stress, i.e., the sum of σm and σs as per above has to be considered. The short-circuit strength is given, if σtot = σm + σs ≤ q ∗ Rp0.2 (10.17) If only limit values of the stress corresponding to the yield point rather than readings are available, the minimal values should be used. Quantities as per Equations (10.16) and (10.17) are q Rp0.2 Factor of plasticity Stress corresponding to the yield point More information on mechanical short-circuit stress on rigid conductors is included in [47]. 10.2.2.4 Forces on supports The relevant force to be considered for short-circuit strength is the dynamic force Fd to be calculated by Fd = VF ∗ Vr ∗ α ∗ Fm (10.18) The three-phase short-circuit in three-phase systems, respectively the two-phase short-circuit in two-phase systems, will cause the maximal force to be used for the force Fm . Typical values for the factors Vr and VF are shown in Figures 10.8 and 10.9. The factor α depends on the type and the number of supports and can be obtained from Table 10.3. The short-circuit strength of supports and fixing material is sufficient, if the dynamic force Fd is below the rated force FrB as per manufacturer’s data. Fd ≤ FrB (10.19) Standards for the short-circuit stress on foundations are actually under discussion. Effects of short-circuit currents 207 3 Maximal value for double-phase short-circuits Maximal value for three-phase short-circuits VF . 2 1.0 1 1.25 > 1.6 0 0.01 Figure 10.9 0.1 k 1 fc /f 10 Factor VF for the calculation of bending stress (according to Figure 4 of IEC 60865-1:1993) 10.2.2.5 Influence of conductor oscillation In Sections 10.2.2.3 and 10.2.2.4, factors are explained which take account of the function of time of the bending stress and forces. Deviations from values for Vσ , Vr , Vσ s , Vrs and VF are permitted, if the mechanical natural frequency of the arrangement is taken into account. It should be noted in this respect that the required data are difficult to obtain. The mechanical natural frequency fc of a conductor, either main or sub-conductor is calculated by γ fc = 2 ∗ l  E∗J m (10.20) The mechanical natural frequency of main conductors, composed of several sub-conductors with rectangular cross-sections, can be calculated by γ fc = c ∗ 2 ∗ l  E ∗ Js ms (10.21a) and for sub-conductors by 3.56 fcs = 2 ∗ l  E ∗ Js ms (10.21b) 208 Short-circuit currents Quantities as per Equations (10.20) and (10.21) are: Factor taking account of type and number of supports (Table 10.3) Young’s modulus Second mechanical moment of the conductor, respectively subconductor Specific mass (mass per length), respectively sub-conductor Conductor length, respectively sub-conductor length Factor as per Equation (10.21c) taking account of stiffening elements (Figure 10.10). γ E J ; Js m ; ms l; ls c c= cc (10.21c) 1 + ξm (mz /(n ∗ l ∗ ms )) where cc is the factor as per Table 10.4, ξm is the factor as per Table 10.4, mz the specific mass of stiffening elements and n is the number of sub-conductors. l ls k=1 ls k=4 Figure 10.10 Calculation of mechanical natural frequency (Factor c). Arrangement of distance elements and calculation equation (according to Figure 3 of IEC 60865-1:1993) Number k and type of distance of stiffening elements, the ratio of the mass of stiffening (distance) elements mz to the specific mass of the conductor ms l separately for the two swing directions in parallel or rectangular to the side with largest crosssection and the second moments J and Js of the conductor, respectively the subconductor area, are duly considered. The Young’s modulus E and the specific mass m depend on the construction and on the type of material. The remarks as per Annex A.3 of IEC 60865:1993 shall be observed. The bending stress and the dynamic force on supports are calculated taking account of the mechanical natural frequency fc and the factors Vσ , Vr , Vσ s , Vrs and VF Effects of short-circuit currents 209 Table 10.4 Factors for the calculation of mechanical natural frequency. Swing is at right angle to the area of sub-conductor Stiffening or distance elements Number k Stiffening element cc Distance element cc 0 1 2 3 4 1.0 1.0 1.48 1.75 2.14 1.0 1.0 1.0 1.0 1.0 ls /l ξm — 0.5 0.33 0.25 0.2 0.0 2.5 3.0 4.0 5.0 obtained from Figures 10.7 to 10.9. Parameters are the factor κ as per Chapter 4 and the ratio of mechanical natural frequency fc to power frequency f (50 or 60 Hz). Calculation equations are included in the Annex of IEC 60865-1:1993. More information on the electromechanical effects and conductor oscillations can be found in [46,49,51,53,55]. 10.3 d.c. auxiliary installations 10.3.1 Substitute rectangular function The calculation of thermal and electromagnetic effects of short-circuit currents in d.c. auxiliary installations is carried out similar to the analysis in a.c. systems. In general, two alternatives for the calculation are possible. The simplified approach (first alternative) is based on the standard approximation function [41] of the short-circuit current 1 − e−t/τ1 for 0 ≤ t ≤ tp i1 (t) = ip ∗ 1 − e−tp /τ1  Ik Ik i2 (t) = ip ∗ e−(t−tp )/τ2 + 1− ip ip (10.22a) for tp ≤ t ≤ Tk (10.22b) The electromagnetic effects are calculated using the peak short-circuit current ip of the standard approximation function. The second alternative is based on the substitute rectangular function, which achieves the same effects as the standard approximation function [40,41]. Quantities as per Equations (10.22) are explained in Figure 10.11. The substitute rectangular function is defined by IR2 and tR according to Figure 10.11 210 Short-circuit currents (a) 1.2 1 1 ip i1(t) 0.8 i2(t) tp 0.6 i/ip Ik 0.4 2 0.2 0 Tk 0 2 4 6 8 10 12 14 16 18 t (b) 1.2 ip2 1 tp 0.8 i22(t) i12(t) Substitute rectangular function IR 0.6 )2 (i/ip 0.4 tR Ik2 0.2 0 Tk 0 Figure 10.11 2 4 6 8 t 10 12 14 16 18 Standard approximation function (a) and substitute rectangular function (b) (according to Figure 4 of IEC 60660-2:1997). Not to scale and calculated by IR2 = 0.2887 ∗ tR = 3.464 ∗   A3i Ig Ig Ai (10.23a) (10.23b) whereas Ai and Ig are calculated by factors mθ 1 , mθ 2 , mg1 , mg2 , mIg1 and mIg2 , depending on the peak short-circuit current ip , the short-circuit duration Tk and the Effects of short-circuit currents 211 time to peak tp Ai = ip2 ∗ (tp ∗ mθ 1 + (Tk − tp ) ∗ mθ 2 )  3 t (Tk − tp )3 2 p Ig = ip mIg1 + mIg2 + mθ 1 ∗ tp ∗ (tg − mg1 ∗ tp )2 12 12  + mθ 2 ∗ (Tk − tp ) ∗ (tp + mg2 ∗ (Tk − tp ) − tg )2 (10.24a) (10.24b) where tg = mθ 1 ∗ mg1 ∗ tp2 + mθ 2 ∗ (Tk − tp ) ∗ (tp + mg2 ∗ (Tk − tp )) mθ 1 ∗ tp + mθ 2 ∗ (Tk − tp ) (10.24c) or can be taken from diagrams in IEC 60865, which include calculation equations for the factors mθ 1 , mθ 2 , mg1 , mg2 , mIg1 and mIg2 . The mechanical natural frequency of either main or sub-conductors are to be taken into account for the calculation of the substitute rectangular function. The mechanical natural frequency is calculated by γ fc = 2 ∗ l  E∗J m (10.25a) The factor γ takes account of the type and number of supports and can be obtained from Table 10.3. For main conductors composed of several sub-conductors, the mechanical natural frequency is to be calculated by γ fc = c ∗ 2 ∗ l  E ∗ Js ms (10.25b) For the calculation of the bending stress of sub-conductors, the mechanical natural frequency [43,44] is calculated by 3.56 fcs = 2 ∗ l  E ∗ Js ms (10.25c) Quantities as per Equations (10.25) are: γ E J ; Js m ; ms l; ls c Factor taking account of the type and number of supports (Table 10.3) Young’s modulus Second mechanical moment of the conductor, respectively subconductor Specific mass (mass per length), respectively sub-conductor Conductor length, respectively sub-conductor length Factor taking account of stiffening elements (Equation 10.21c). 212 Short-circuit currents The vibration period Tme of the main conductor, respectively Tmes of the subconductor is calculated by Tme = 1 fc (10.26a) Tmes = 1 fcs (10.26b) where fc ; fcs are the natural mechanical frequency of the conductor, respectively sub-conductors. The parameters tR and IR2 of the substitute rectangular function are calculated for the short-circuit duration Tk , in the case Tk ≤ 0.5Tme . In the case Tk > 0.5Tme the parameters are calculated for the equivalent short-circuit duration being Tke = MAX{0.5Tme ; 1.5tp }. In the case Tk = tp , i.e., the short-circuit current has a decreasing function only, the substitute rectangular function is calculated, independently from the vibration period Tme for the total short-circuit duration Tk . The calculation of the force for the main conductor is done by FR max = ls μ0 ∗ ∗ IR2 2π am respectively, in the case of sub-conductors (number n) by  μ0 ls IRs 2 FRs max = ∗ ∗ 2π as n (10.27a) (10.27b) where IR ; IRs are the current of the substitute rectangular function, l; ls is the length of conductor, respectively sub-conductor, am ; as is the effective distance between conductor, respectively sub-conductor, and n is the number of sub-conductors. 10.3.2 Mechanical short-circuit strength of rigid conductors 10.3.2.1 Forces The calculation of electromagnetic effects on rigid conductors is based on the substitute rectangular function as per Figure 10.11 and described in Section 10.3.1. The substitute rectangular function leads to identical bending stress and forces as the standard approximation function. The forces between main conductors are calculated by FR = μ0 l ∗ IR2 ∗ 2π am and between sub-conductors (number n) by using  IRs 2 μ0 ls FRs = ∗ ∗ 2π as n (10.28a) (10.28b) Effects of short-circuit currents 213 Quantities as per Equations (10.28) are: IR ; IRs l; ls am ; as n Current of the substitute rectangular function Length of conductor, respectively sub-conductor Effective distance between conductor, respectively sub-conductor Number of sub-conductors The bending stress and forces on supports for both main and sub-conductors are calculated similar to a.c. installations as described in Sections 10.2.2.2 to 10.2.2.4. The effective distance of main conductors am is calculated from the distance a by am = a k12 (10.29) with the correction factor k12 according to Figure 10.6. The effective distance of sub-conductors as in the case of circular conductors is calculated by n  1 a1i = as (10.30a) i=2 respectively, in the case of rectangular cross-sections n  k1i 1 = as a1i (10.30b) i=2 with the factor k1i according to Figure 10.6. 10.3.2.2 Bending stress The bending stress on main conductors σm , respectively on sub-conductors σs , resulting from the bending forces is calculated using FR ∗ l 8∗Z FRs ∗ ls σs = Vσ s ∗ 16 ∗ Zs σm = Vσ ∗ β ∗ (10.31a) (10.31b) where Z; Zs are the section moduli of the main, respectively sub-conductors, V is the factor as explained below, l; ls is the length of conductor, respectively sub-conductor, and β is the factor taking account of the type and number of supports (Table 10.3). The forces FR and FRs are the forces as calculated for the substitute rectangular function. Typical values of Vσ and Vσ s are outlined in Figure 10.12. IEC 61660-2:1997 indicates in Table 2 that Vσ and Vσ s should be lower than 1. If the busbar consists of multiple bars supported in unequal distances, the maximal supporting distance is to be considered. If a supporting distance is less than 20 per cent of the distance of neighbouring bars, the bars have to be coupled by joints. Joints between two supports are permitted, if the distance between the supporting points is less than 70 per cent of the supporting distances of neighbouring bars. 214 Short-circuit currents 1.2 1 Vs 0.8 . VsS 0.6 0.4 0.2 0 0 0.1 0.2 0.3 . Figure 10.12 tR/Tme 0.4 0.5 Factors Vσ and Vσ s for the calculation of bending stress on conductors (according to Figure 9 of IEC 61660-2:1997) The conductor has sufficient electromagnetic strength with respect to bending stress, if the bending stress σm is below the product of factor of plasticity and stress corresponding to the yield point σm ≤ q ∗ Rp0.2 (10.32a) In the case of several sub-conductors the total bending stress, i.e., the sum of the stresses σm and σs is to be considered σtot = σm + σs ≤ q ∗ Rp0.2 (10.32b) where q is the factor of plasticity and Rp0.2 is the stress corresponding to the yield point. Values for the factor of plasticity q for typical arrangements are included in Table 4 of IEC 60660-2:1997. Values are between q = 1.19–1.83 for rectangular cross-sections, U-, H- and I-shape profiles. For circular ring section type conductors the factor of plasticity depends on the diameter and wall thickness. Reference is made to IEC 61660-2:1997. 10.3.2.3 Forces on supports The dynamical force Fd is the dominating parameter for the short-circuit strength of supports to be calculated by Fd = VF ∗ α ∗ FR (10.33) whereas the force FR is the force calculated on the basis of the substitute rectangular function. Typical values of VF are outlined in Figure 10.13. The factor α takes account of the type and number of supports and can be obtained from Table 10.3. The requirements regarding the short-circuit strength of supports and fixing material are fulfilled if the dynamical force Fd remains below the rated value FrB Effects of short-circuit currents 215 . 2.2 2 1.8 1.6 VF 1.4 1.2 1 0.8 0.6 0.4 0.2 0 0 Figure 10.13 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 tR/Tme 0.45 0.5 Factor VF for the calculation of forces on supports (according to Figure 9 of IEC 61660-2:1997) as per manufacturer’s data (10.34) Fd ≤ FrB Standardisation of stresses on foundations is actually under consideration. More information on the theoretical background can be found in [43–45,48]. 10.3.3 Thermal short-circuit strength The thermal short-circuit strength is analysed using the thermal equivalent short-time current Ith and the short-circuit duration Tk .  Ai Ith = (10.35) Tk with Ai as per Equation (10.24a). The upper limit of the thermal equivalent short-time current is defined as Ith = ip . IEC 61660-2 indicates that separate considerations for equipment (e.g., transformers, transducers) and conductors (e.g., busbars, cables) have to be taken. The thermal short-circuit strength of equipment is fulfilled if the thermal equivalent short-time current Ith is below the rated thermal equivalent short-time current Ithr Ith ≤ Ithr for Tk ≤ Tkr (10.36a) with the rated short-circuit duration Tkr assumed equal to 1 s. If the short-circuit duration Tk is longer than the rated short-circuit duration Tkr , the thermal short-circuit 216 Short-circuit currents strength is given if  Ith ≤ Ithr ∗ Tkr Tk for Tk ≥ Tkr (10.36b) Permissible values for conductor material of cables are outlined in Table 10.1 and in Figure 10.3. In order to analyse the short-circuit strength of bare conductors, the thermal equivalent short-time current density Jth is calculated using the thermal equivalent current and the cross-section qn Jth = Ith qn (10.37) where Ith is the thermal equivalent current and qn the cross-section of the conductor. The steel part of Al/St-conductors is not taken into account for the cross-section. Conductors have sufficient thermal strength if the thermal equivalent short-time density Jth is below the rated thermal equivalent short-time density Jthr , whereas short-circuit durations different from the rated short-circuit duration have to be considered.  Tkr (10.38) Jth ≤ Jthr ∗ Tk Data on the rated short-time current density of conductor material are given in Table 10.1 and Figure 10.3. In non-insulated conductors, i.e., bare conductors and busbars, the thermal equivalent short-time current density is allowed to be above the rated short-time current density in the case Tk < Tkr . 10.4 10.4.1 Calculation examples (a.c. system) Calculation of thermal effects The thermal short-circuit strength of a cable N2XS2Y 240 6/10 kV is to be analysed. Figure 10.14 indicates the equivalent circuit diagram of a power system. In the case of near-to-generator short-circuit (three-phase) the maximal short-circuit current at the busbars Q, respectively A, and the thermal equivalent short-circuit current Ith for the short-circuit duration 0.1 s; 1.2 s; 2 s and 4 s are to be calculated as well as the A Q N2XS2Y240 6/10 kV Figure 10.14 Equivalent circuit diagram, data of equipment, resistance at 20◦ C Effects of short-circuit currents 217 short-circuit current density Jthz permitted for a cable sheath of copper (initial temperature 80◦ C; temperature at the end of short-circuit 350◦ C; short-circuit duration 0.2 s; 1.2 s; 2 s). Data of equipment are given below:  UnQ = 10 kV; SkQ = 520 MVA   RK = 0.11 /km; l = 2 km = 0.0754 /km; XK The maximal short-circuit current is given for short-circuits at the sending-end of  the cable (approximately identical to location Q) Ik3Q = 30.03 kA. The maximal  = 13.28 kA. Table 10.1 indicates a value short-circuit current at location A is Ik3A of Jthr = 143 A/mm2 . The thermal equivalent rated current is Ithr = 34.32 kA. The calculation results are outlined in Table 10.5. Table 10.5 Results of calculation of thermal equivalent currents tk (s) Ithz (kA) IthQ (kA) IthA (kA) Jthz (A/mm2 ) 0.2 1.2 2 4 76.26 31.33 24.27 17.16 14.12 11.73 9.62 8.81 31.92 26.52 21.86 19.92 689 285 221 — The short-circuit strength is sufficient if Ith ≤ Ithz . This is fulfilled if tk < 2 s for short-circuits near busbar A and tk < 4 s for short-circuits near busbar Q. 10.4.2 Electromagnetic effect A wind power plant is connected to the public supply system by four cables in parallel laid on racks as indicated in Figure 10.15. The relevant parameters of the short-circuit current and the maximal forces on the cables, respectively on the fixing material, are to be calculated. The permissible distance of the fixing clamps is to be determined. The maximal permissible force on the clamps is Fzul = 40 kN. Q T F2 F1 4 × 3 Single-core cables G GS 3~ Figure 10.15 Equivalent circuit diagram of a power system with wind power plant The data of equipment are given below:  = 1000 MVA; UnQ = 110 kV SkQ SrT = 2.5 MVA; ukrT = 6%; uRrT = 0.8%; trT = 20 kV/0.66 kV 218 Short-circuit currents  SrG = 2.5 MVA; UrG = 0.66 kV; cos ϕrG = 0.85; xdG = 18 per cent Each cable: XL = 9.84 m; RL = 10.82 m Short-circuits are fed from the generator as well as from the power system feeder. Short-circuit currents are given in Table 10.6. Table 10.6 Results of short-circuit current calculation Parameter Generator Power system feeder Short-circuit location F1 (kA) F2 (kA)  = 13.3 Ik3  = 12.17 Ik3 ip = 32.05 ip = 27.07 ip = 65.59 ip = 86.66  = 34.48 Ik3  = 36.43 Ik3 The maximal short-circuit current (peak short-circuit current) ip = 86.66 kA is given for a short-circuit at location F2 and is taken as the basis for the analysis. The force on the fixing material is Fs = 51.79 N/m. The distance of the fixing clamps shall be below d ≤ 0.77 m. 10.5 Calculation examples (d.c. system) 10.5.1 Thermal effect The thermal effect of the short-circuit current is to be calculated. The conductor of the main busbar has a cross section qn = 2 × 400 mm2 (d × b = 10 mm × 40 mm; Cu), ρ = 0.0173 mm2 /m, see Figure 10.16. The short-circuit duration is Tk = 100 ms. Temperature at beginning of short-circuit is δ0 = 20◦ C and at the end δ1 = 250◦ C. The short-circuit parameters are summarised below: Peak short-circuit current ip = 50.5 kA Quasi steady-state short-circuit current Ik = 46.6 kA Time-to-peak tp = 12.1 ms Rise-time constant τ1 = 4.03 ms Decay-time constant τ2 = 17.3 ms The time course of the short-circuit current is given by i1 (t) = 47.99 kA ∗ (1 − e−t/4.03 ) for 0 ≤ t ≤ 12.1 ms i2 (t) = 50.5 kA ∗ (0.077 ∗ e−(t−12.1)/17.3 + 0.923) for 12.1 ms ≤ t ≤ Tk Effects of short-circuit currents 219 I d am ls Figure 10.16 as a12 height b Arrangement of busbar conductor (data, see text) The thermal equivalent short-time current Ith as per Equation (10.35)   Ai 206.11 kA2 = = 45.4 kA Ith = Tk 0.1 s with Ai as per Equation (10.24a) Ai = ip2 ∗ (tp ∗ mθ 1 + (Tk − tp ) ∗ mθ 2 ) = 50.52 kA2 ∗ (0.0121 s ∗ 0.65 + (0.1 s − 0.0121 s) ∗ 0.83) = 206.11 kA2 Factors mθ 1 and mθ 2 are calculated as per IEC 61660-2 mθ 1 = 0.65 mθ 2 = 0.83 The thermal equivalent short-time current density Jth according to Equation (10.37) is calculated as Jth = Ith 45(4) kA = 56.75 A/mm2 = qn 2(400) mm2 Conductors have sufficient thermal strength if the thermal equivalent short-time density Jth is below the rated thermal equivalent short-time density Jthr taken from Figure 10.3 (Jthr = 190 A/mm2 ).  Tkr Jth ≤ Jthr ∗ Tk  1s 2 2 56.75 A/mm ≤ 190 A/mm ∗ = 600 A/mm2 0.1 s The busbar-conductor has sufficient thermal short-circuit strength. 220 Short-circuit currents 10.5.2 Electromagnetic effect The configuration as per Sections 9.7 and 10.5.1 is regarded. The conductor arrangement is outlined in Figure 10.16. The distances are: am = 75 mm; b = 40 mm; as = 10 mm; l = 1050 mm; ls = 35 mm. The mechanical constants of the busbar are: Stress corresponding to the yield point Rp0.2 = 340 N/mm2 Specific mass of subconductor ms = 3.5 kg/m Young’s modulus E = 106 kN/mm2 Stiffening elements have dimension 40/40/10 mm. 10.5.2.1 Calculation of forces with simplified approach Peak force between main conductors FRm = 4π ∗ 10−7 ∗ (Vs/Am) μ0 l 2 1.05 m ip = ∗ ∗ ∗ 50.52 ∗ kA2 2π am 2π 0.0765 m = 7000.7 N Effective distance of main conductors am according to Equation (10.29) am = 0.075 m a = = 0.0765 m k12 0.98 with the correction factor k12 = 0.98 according to Figure 10.6. Peak force between sub-conductors   50.5 ∗ kA 4π ∗ 10−7 ∗ (Vs/Am) 0.35 m μ0 ls ip 2 FRs = ∗ ∗ ∗ = 2π as n 2π 0.028 m 2 = 1593.9 N Effective distance of sub-conductors as as = 0.02 m a12 = = 0.028 m k12 0.72 with the correction factor k12 = 0.72 according to Figure 10.6. 10.5.2.2 Calculation of forces with substitute rectangular function Parameters of short-circuit current remain identical to those mentioned above. ip = 50.5 kA; tp = 12.1 ms; Tk = 100 ms Mechanical natural frequency of main conductor as per Equation (10.25)  E ∗ Js γ fc = c ∗ 2 ∗ ms l 2 Effects of short-circuit currents 221 with c ≈ 1.44 as per Figure 10.10, factor γ as per Table 10.3 and the second mechanical moment J of the conductor, respectively sub-conductor d3 ∗ b 0.013 ∗ 0.04 4 = m = 3.33 ∗ 10−9 m4 12 12  106 kN/mm2 ∗ 3.33 ∗ 10−9 m4 3.56 ∗ fc = 1.44 ∗ = 46.7 Hz 2 2 3.5 kg/m 1.05 m J = Js = Vibration period Tme as per Equation (10.26) Tme = 1 1 s = 21.4 ms = fc 46.7 Mechanical natural frequency of sub-conductors   3.56 E ∗ Js 106 kN/mm2 ∗ 3.33 ∗ 10−9 m4 3.56 fcs = 2 ∗ = ∗ ms 3.5 kg/m ls 0.352 m2 = 291.8 Hz Vibration period Tmes Tmes = 1 1 s = 3.43 ms = fc 291.8 Substitute rectangular function to be calculated for the equivalent short-circuit duration Tke , as Tk > 0.5Tme . Tke = MAX{0.5 ∗ Tme ; 1.5 ∗ tp } = MAX{0.5 ∗ 21.4 ms; 1.5 ∗ 12.1 ms} = 18.2 ms Parameters of the substitute rectangular function (in this case identical for the main conductor and for the sub-conductors) as per Equations (10.23) and (10.24)  A3i IR2 = 0.2887 ∗ Ig  Ig tR = 3.464 ∗ Ai  3 tp (Tk − tp )3 mIg1 + mIg2 + mθ 1 ∗ tp ∗ (tg − mg1 ∗ tp )2 Ig = ip2 12 12  + mθ 2 ∗ (Tk − tp ) ∗ (tp + mg2 ∗ (Tk − tp ) − tg )2 Ai = ip2 ∗ (tp ∗ mθ 1 + (Tk − tp ) ∗ mθ 2 ) tg = mθ 1 ∗ mg1 ∗ tp2 + mθ 2 ∗ (Tk − tp ) ∗ (tp + mg2 ∗ (Tk − tp )) mθ 1 ∗ tp + mθ 2 ∗ (Tk − tp ) 222 Short-circuit currents Factors mθ 1 , mθ 2 , mg1 , mg2 , mIg1 and mIg2 are calculated according to IEC 61660-2 mθ 1 = 0.65; mg1 = 0.63; mIg1 = 0.42; mθ 2 = 0.83 mg2 = 0.47 mIg2 = 0.86 Ai = (50.5 kA)2 ∗ (0.0121 s ∗ 0.65 + (0.0182 − 0.0121 s) ∗ 0.83) = 32.97 kA2 s tg = [0.65 ∗ 0.63 ∗ (0.0121 s)2 + 0.83 ∗ (0.0182 − 0.0121 s) ∗ (0.0121 + 0.47 ∗ (0.0182 − 0.0121 s))] ∗ [0.65 ∗ 0.0121 s + 0.83 ∗ (0.0182 − 0.0121 s)]−1 tg = 0.0105 s tp3 (Tk − tp )3 mIg2 + mθ 1 ∗ tp ∗ (tg − mg1 ∗ tp )2 12 12  2 + mθ 2 ∗ (Tk − tp ) ∗ (tp + mg2 ∗ (Tk − tp ) − tg ) Ig = (50.5 kA)  mIg1 + ⎤ (0.0182 − 0.0121 s)3 (0.0121 s)3 ∗ 0.42 + ∗ 0.86 + · · · ⎥ ⎢ 12 12 ⎥ ⎢ ⎥ ⎢ 2 ⎢· · · 0.65 ∗ 0.0121 s ∗ (0.0105 s − 0.63 ∗ 0.0121 s)3 + · · ·⎥ Ig = (50.5 kA) ⎢ ⎥ ⎥ ⎢ ⎥ ⎢· · · 0.83 ∗ (0.0182 − 0.0121 s) ∗ (0.0121 s + 0.47 ⎦ ⎣ ⎡ Ig = 457.2 A2 s3 ∗(0.0182 − 0.0121 s) − 0.0105 s)2 The parameters of the substitute rectangular function  (32.97 ∗ 106 A2 s)3 IR2 = 0.2887 ∗ = 2556 ∗ 106 A2 3 457.2 A2 s  3 457.2 A2 s tR = 3.464 ∗ = 12.9 ms 32.97 ∗ 106 A2 s The standardised rectangular function and the approximated total short-circuit current (see e.g., Section 9.7) are outlined in Figure 10.17. Peak force between main conductors as per Equation (10.27) FRm = 4π ∗ 10−7 ∗ (Vs/Am) μ0 l 1.05 m ∗ IR2 = ∗ ∗ ∗ 2556 ∗ 106 A2 2π am 2π 0.0765 m = 7016.5 N Effective distance of main conductors am = 0.0765 m as per above. Effects of short-circuit currents 223 60 IR 50 Current (A) 40 Approximated total short-circuit current Iappr Tke 30 tR 20 Substitute rectangular function (IR; tR) Tk 10 0 0 10 Figure 10.17 20 30 Time (ms) 40 50 60 Standardised rectangular function and approximated total shortcircuit current Peak force between sub-conductors  μ0 ls IRs 2 4π ∗ 10−7 ∗ (Vs/Am) 0.35 m = ∗ ∗ FRs = 2π as n 2π 0.028 m  6 2 2556 ∗ 10 A ∗ = 1597.5 N 4 10.5.2.3 Bending stress Bending stresses σm ; σs on main, respectively, sub-conductors (Equation (10.31)) are calculated for the forces obtained by the substitute rectangular function only. σm = Vσ ∗ β ∗ FRm ∗ l 7016.5 N ∗ 1.05 m = 1.0 ∗ 0.73 ∗ 8∗Z 8 ∗ 3.47 ∗ 10−6 N/mm2 = 193.7 N/mm2 σs = Vσ s ∗ 1597.5 N ∗ 0.35 m FRs ∗ ls = 1.0 ∗ = 49.9 N/mm2 16 ∗ Zs 16 ∗ 0.667 ∗ 10−6 N/mm2 with Vσ and Vσ s equal One as per Figure 10.12 and the factor β = 0.73 as per Table 10.3. Total bending stress σtot = σm + σs = (193.7 + 49.9) N/mm2 = 243.6 N/mm2 ≤ q ∗ Rp0.2 = 1.5 ∗ 340 N/mm2 224 Short-circuit currents Conductors have sufficient electromagnetic strength as σtot ≤ q ∗ Rp0.2 = 1.5 ∗ 340 N/mm2 = 510 N/mm2 and if σs ≤ Rp0.2 = 340 N/mm2 10.5.2.4 Forces on supports Forces on outer supports Fd = VF ∗ α ∗ FRm = 2.0 ∗ 0.4 ∗ 7016.5 N = 5.61 kN Forces on inner supports Fd = VF ∗ α ∗ FRm = 2.0 ∗ 1.1 ∗ 7016.5 N = 15.4 kN Chapter 11 Limitation of short-circuit currents 11.1 General The expansion of electrical power systems by new power stations and new lines (overhead transmission lines and cable circuits) results in an increase of short-circuit currents due to an increase in sources feeding the short-circuit and due to a reduction of system impedance. The improvement of existing installations and the replacement of equipment are necessary, in case the permissible short-circuit current will be exceeded. Measures to limit the short-circuit currents can also be realised which might be more economic than the replacement of equipment and installations. Different measures have to be taken into account such as measures affecting the whole system (higher voltage level), measures concerning installations and substations (separate operation of busbars) and measures related to equipment (Ip-limiter). All measures have an influence on the system reliability as well, which must be guaranteed under outage conditions of equipment after the measures for limitation of short-circuit currents are in operation. Measures for short-circuit current limitation decrease the voltage stability, increase the reactive power requirement, reduce the dynamic stability and increase the complexity of operation. Furthermore some measures to limit short-circuit currents will contradict requirements for a high short-circuit level, e.g., to reduce flicker in the case of connection of arc-furnace. The decision on location of power stations is determined beside other criteria by the availability of primary energy (lignite coal fired power stations are build nearby the coal mine), requirement of cooling water (thermal power stations are placed near the sea or at large rivers), geological conditions (hydro power stations can only be build if water reservoirs are available), requirements of the power system (each power station requires a system connection at suitable voltage level) and the vicinity to consumers (combined heat and energy stations need heat consumers nearby). The connection of large power stations is determined by the branch short-circuit current from the generators. Figure 11.1 outlines considerations to select the suitable 226 Short-circuit currents kA 600 S ⬙kG/S ⬙kQ 0.025 500 0.1 0.15 380 kV 400 Un Nuclear power station 1310 MW 300 220 kV 200 110 kV Hardcoal power station 600 MW Lignite coal power station 400 MW 100 Small hydropower station ∑ 220 MW Gas turbine 120 MW 40 60 100 200 400 600 1000 2000 6000 MVA SrG Figure 11.1 Selection of suitable voltage level for the connection of power stations voltage level for the connection of power stations to the power system. It is assumed that more than one power station is connected to the system. As generation of electrical energy without consumers is without any sense, a suitable power system has to be planned and constructed accordingly. An increased amount of small combined heat and power stations (distributed generation) with connection to the medium-voltage and even to the low-voltage system requires additional considerations with respect to protection, operation and short-circuit level in the different voltage levels [25]. 11.2 Measures 11.2.1 Measures in power systems 11.2.1.1 Selection of nominal system voltage A higher nominal system voltage by constant rated power of feeding transformers will reduce the short-circuit level proportionally. The selection of nominal system voltage must take into account the recommended voltages as per IEC 60038:1987 and the common practice in the utility itself and maybe in the whole country. Table 11.1 lists a selection of recommended voltages. The table also includes information on typical applications in Europe. The short-circuit current is directly proportional to the voltage level, respectively to the voltage ratio of feeding transformers, if all other parameters are constant. Limitation of short-circuit currents 227 Table 11.1 Selection of recommended voltage as per IEC 60038:1987 Nominal voltage Application Low voltage (V) 400–230 500 Medium voltage (kV) 6 10 20 30 High voltage (kV) Private consumers According to Small industrial consumers IEC Table I Motor connection in industry Not listed in IEC HV-motors in industry, auxiliary supply in power stations Urban distribution systems, industrial systems Industrial systems, rural distribution systems Electrolysis, arc furnace, rectifiers 110 Urban transport systems 220 Transport system with regional task Transmission system country-wide 380 Remarks According to IEC Table III According to IEC Table III According to IEC Table III Not listed in IEC According to IEC Table IV According to IEC Table IV According to IEC Table V the highest voltage of equipment Ubmax = 420 kV is defined The selection of a new nominal system voltage normally is only possible when new electrification projects are considered. As the impedance voltage of transformers increases with increasing voltage an additional positive effect on the reduction of short-circuit currents is seen. As a by-effect it should be noted that the transmittable power of overhead lines and cables is increased with increasing voltage without increasing the cross-section of the conductor. On the other hand, the voltage drop of the transformer is increased in the case of increase of impedance voltage. 11.2.1.2 Operation as separate subsystems The power system is operated as several subsystems, which are connected at higher voltage level. Figure 11.2 outlines the general structure of a 132-kV-cable system (total load approximately 1500 MW). The system is supplied from the 400-kV-system and by a power station connected to the 132-kV-level. Assuming a meshed system operation, i.e., the 132-kV-system is operated as one system with all breakers closed, the short-circuit currents in the case of three-phase and single-phase short-circuits are  = 26.0–37.4 kA and I  = 37.3–45.7 kA. Operating the 132-kV-system as two Ik3 k1 separate subsystems coupled only on the 400 kV-level, the short-circuit currents will be reduced to the values as outlined in Figure 11.2. 228 Short-circuit currents GS 3~ ∑ 2815 MW 2 × 500 MVA 132-kV-subsystem 1 I ⬙k3= 19.3–26.1 kA ∑ 520 MW I ⬙1k = 24.2–32.8 kA GS 3~ 400-kV-system 132-kV-subsystem 2 GS 3~ I ⬙k3= 15.4–22.3 kA I ⬙1k = 20.9–26.5 kA ∑ 440 MW 2 × 500 MVA GS 3~ Figure 11.2 ∑ 1090 MW Schematic diagram of a 400/132-kV-system for urban load; values of short-circuit currents in case of operation as two subsystems Operating the 132-kV-system as two separate subsystems will require additional cable circuits and an extension of the switchgear to fulfil the (n − 1)-criteria for a reliable power supply. 11.2.1.3 Distribution of feeding locations Power stations and system feeders from higher voltage levels are to be connected to several busbars in the system. This measure was realised in the power system Limitation of short-circuit currents 229 as per Figure 11.2, which is a by-effect to the system separation. A further example is outlined in Figure 11.3. A power station of 395 MW is connected to a 132-kV-system, which has a second supply from the 220-kV-system. The 132-kV-system is a pure cable network and the shortest cable length between any two substations is 11.2 km. In the case when the busbar-coupler K in the power station is closed, the three-phase  = 37.6 kA; the short-circuit currents at the short-circuit current at the busbar is Ik3  = 33.5 kA. If the busbar-coupler K busbars in the 132-kV-system remain below Ik3 is operated opened, the short-circuit currents at the busbar in the power station are  = 28.0 kA and I  = 29.3 kA. For short-circuits at the busbars in the system itself Ik3 k3 the short-circuit currents are reduced up to 4.1 kA. 220-kV-system ∑ 203 MW GS 3~ 132-kV-system K ∑ 192 MW Figure 11.3 GS 3~ Schematic diagram of a 132-kV-system with power station The generators and the 132-kV-cables in the power stations need to be switchedon to the busbars in such a way that the generated power can be transferred to the power system without overloading any of the cable even under outage conditions. 230 Short-circuit currents 11.2.1.4 Coupling of power system at busbars with low short-circuit level Different parts of the power system shall be connected only at busbars with low shortcircuit level. Figure 11.4 outlines a 30-kV-system with overhead lines, which is fed from the 110-kV-system by two transformers operated in parallel. The three-phase  = 10.09 kA. If the transformers are not operated in parallel short-circuit current is Ik3 and the system is coupled at busbar K7 the short-circuit current at the feeding busbar  = 5.94 kA. is Ik3 K8 Un = 30.000 kV I 0k (L1) = 10.091 kA S k0 (L1) = 524.341 MVA (a) K3 K2 K1 K7 Un= 30.000 kV I 0k (L1) = 2.199 kA S k0 (L1) =114.241 MVA EL5 3200 MVA K5 K4 K6 EL9 K9 Un = 30.000 kV I k0 (L1) = 10.091 kA S k0 (L1) = 524.341 MVA K8 Un = 30.000 kV I 0k (L1) = 5.935 kA S k0 (L1) = 308.375 MVA (b) K3 K2 K1 K7 Un = 30.000 kV I 0k (L1) = 2.193 kA S k0 (L1) = 113.929 MVA EL5 3200 MVA K4 K5 K6 EL9 K9 Un = 30.000 kV I 0k (L1) = 5.935 kA S k0 (L1) = 308.375 MVA Figure 11.4 Equivalent circuit diagram of a 30-kV-system with feeding 132kV-system: (a) Operation with transformers in parallel and (b) limitation of short-circuit current. Result of three-phase short-circuit  = 3.2 GVA; S = 40 MVA; u current: SkQ rT krT = 12%; trT = 110/32; OHTL 95Al; ltot = 56 km It should be noted that the short-circuit level at busbar K7 is affected only to a minor extent. If the transformers are loaded only up to 50 per cent of their rated power Limitation of short-circuit currents 231 and if the lines have sufficient thermal rating, both system configurations have the same supply reliability. 11.2.1.5 Restructuring of the power system Restructuring of power systems is comparatively costly and complicated. In medium voltage systems restructuring is in most cases only possible together with the commissioning of new primaries, loop-in and loop-out of cable (overhead line) circuits and the operation of the system as a radial system. In a high voltage system, restructuring requires a total different system topology. Figure 11.5 outlines the comparison of two system topologies, i.e., ring fed system and radial fed system. (a) Each system I 0k (L1) = 12.155 kA S k0 (L1) = 8000.000 MVA K12 Un =380.000 kV I 0k (L1) =17.575 kA S k0 (L1) =11567.2 MVA K13 K14 K15 K16 K11 Un = 380.000 kV I k0 (L1) = 23.517 kA S k0 (L1) =15478.5 MVA (b) K17 K18 EL166 EL167 EL173 EL169 EL179 EL178 K20 Un =380.000 kA I 0k (L1) = 22.668 kA S k0 (L1) =14919.6 MVA Figure 11.5 K19 Eaeh system I 0k (L1) = 12.155 kA S k0 (L1) = 8000.000 MVA EL177 EL170 K21 Equivalent circuit diagram of a 380-kV-system and results of threephase short-circuit current calculation: (a) Radial fed system and  = 8 GVA; OHTL ACSR/AW 4 × 282/46; (b) ring fed system. SkQ li = 120 km  = As can be seen from Figure 11.5 the short-circuit currents are reduced from Ik3  23.6 kA to Ik3 = 22.7 kA (3.8 per cent) with the new topology. The reduction of the short-circuit currents is comparatively small, but will be more significant, if an increased number of feeders (or generators) shall be connected [2]. 232 Short-circuit currents 11.2.2 Measures in installations and switchgear arrangement 11.2.2.1 Multiple busbar operation The connection of lines and feeders to more than one busbar per substation is advantageous as compared with the operation of the substation with single busbar or with busbar coupler closed. Figure 11.6 outlines the schematic diagram of a 110-kV (a) D Un =110.000 kV I k0 (L1) = 13.009 kA S k0 (L1) = 2478.597 MVA Spare busbar SS1 Un = 110.000 kV I k0 (L1) = 16.330 kA S k0 (L1) = 3111.364 MVA C Un =110.000 kV I 0k (L1) = 15.435 kA S k0 (L1) = 2940.679 MVA SS2 Un =110.000 kV I 0k (L1) = 16.330 kA S k0 (L1) = 3111.371 MVA B A (b) D Un = 110.000 kV I k0 (L1) = 12.779 kA S k0 (L1) = 2434.703 MVA Spare busbar SS1 Un = 110.000 kV I k0 (L1) = 14.932 kA S k0 (L1) = 2844.867 MVA SS2 Un = 110.000 kV I k0 (L1) = 15.282 kA S k0 (L1) = 2911.615 MVA Figure 11.6 C Un = 110.000 kV I k0 (L1) = 15.434 kA S k0 (L1) = 2940.645 MVA A B Schematic diagram of a 110-kV-substation fed from the 220-kV-system: (a) Operation with buscoupler closed and (b) operation with buscoupler open. Result of three-phase short-circuit current calculation Limitation of short-circuit currents 233 system. The 110-kV-substation is equipped with a double busbar and one additional spare busbar. The substation is fed from the 220-kV-system; outgoing 110-kV-cables are connected to each of the two busbars in operation. The operation with two busbars reduces the three-phase short-circuit current from  = 16.3 kA to I  = 14.9 kA (8.6 per cent ) at SS1 and I  = 15.3 kA (6.1 per cent) Ik3 k3 k3 at SS2. Each of the two busbars SS1 and SS2 can be switched-on to the spare busbar without coupling the busbars. 11.2.2.2 Busbar sectionaliser in single busbar switchgear Single busbars can be equipped with busbar sectionaliser, so that an operation mode similar to double busbar operation is possible. The outgoing cables and the feeding transformers need to be connected to the busbar section in such a way that the loading of feeders is approximately equal. Figure 11.7 indicates an industrial system with nominal voltage of 6 kV, which is fed from the 30-kV-system. (a) BB_110 K3 Un = 6.000 kV I k0 (L1) = 11.353 kA S k0 (L1) =117.986 MVA M BB_04_1 K4 Un = 6.000 kV I k0 (L1) = 11.353 kA S k0 (L1) =117.985 MVA M M M BB_110 K3 Un = 6.000 kV I k0 (L1) = 9.482 kA S k0 (L1) = 98.537 MVA BB_04_1 M K4 Un = 6.000 kV I k0 (L1) = 9.478 kA S k0 (L1) = 98.503 MVA M M M BB_6_2 M Figure 11.7 M BB_6_2 M (b) M M M Equivalent circuit diagram of a 6-kV-industrial system. Results of threephase short-circuit current calculation: (a) Busbar sectionaliser closed and (b) busbar sectionaliser open 234 Short-circuit currents The short-circuit current at the feeding busbar is reduced by 16.8 per cent from  = 11.4 kA to I  = 9.48 kA in the case when the busbar sectionaliser is kept open. Ik3 k3 The outgoing feeders have to be arranged in such a way that the loading will be approximately equal for both busbar sections K3 and K4. 11.2.2.3 Short-circuit current limiting equipment Short-circuit current limiting equipment and fuses (medium voltage and low voltage systems) can be installed to reduce the short-circuit level in parts of the installations. In medium voltage installations, Ip-limiter can be installed. Figure 11.8 outlines the schematic diagram of an industrial system. The existing switchgear A with low shortcircuit rating shall be extended with the busbar section B, which is fed by an additional  system feeder Q2. The maximal permissible short-circuit current IkAmax of busbar section A is exceeded by this extension. Q1 Q2 T1 T2 i1; I1 i2; I2 A B i3 = i1+ i2 I3 = I1+ I2 Figure 11.8 Equivalent circuit diagram of switchgear with single busbar The total short-circuit current from both system feeders shall be limited to the  permissible short-circuit current IkAmax of busbar section A in the case of a short /I  circuit at busbar A. If the relation IkQ1 kQ2 depends on the ratio ZQ1 /ZQ2 of the feeders Q1 and Q2 it is sufficient to measure the partial short-circuit current through the Ip-limiter. The current ratio is  IkQ1 I1 =  I2 IkQ2 (11.1) and the total short-circuit current I3 = I2 ∗ 1 +  IkQ1  IkQ2  ≤ IkAmax (11.2) Limitation of short-circuit currents 235 i 40 kA i1 + i2 With Ip-limiter i1 + i2 Without Ip-limiter 20 kA i1 i2 t Figure 11.9 Time course of short-circuit current in installations with and without Ip-limiter The threshold value I2an of the Ip-limiter is  I2an = IkA max ∗  IkQ2  + I  IkQ1 kQ2 (11.3)   When the permissible short-circuit currents IkAmax of both busbar sections and IkBmax A and B are exceeded, the threshold value I1an of the Ip-limiter for short-circuits at busbar section B is needed as well  I1an = IkB max ∗  IkQ1  + I  IkQ2 kQ1 (11.4) The threshold value Ian of the Ip-limiter is set to the minimum of both values Ian = MIN{I1an ; I2an } (11.5) The detailed design and determination of the settings are determined, besides other factors, by different topologies of the power system, different phase angles of the branch short-circuit currents and different rating of the switchgear in the system. Figure 11.9 outlines the time curves of short-circuit currents at section A as per Figure 11.8. The branch short-circuit current i2 from system feeder Q2 is switched off by the Ip-limiter within 7 ms, thus reducing the peak short-circuit current significantly. The technical layout of one phase of an Ip-limiter is shown in Figure 11.10. Inside an insulating tube (1) the main current conductor (3) with a breaking element, blown by a triggerable explosive loading, (2) is located. When the threshold value is exceeded, the tripping circuit triggers the explosive loading; the arc inside the insulating tube cannot be quenched and is commutated to the fuse element (4), which 236 Short-circuit currents 4 1 2 3 5 Figure 11.10 Cutaway view of an Ip-limiter support: (1) insulating tube, (2) explosive loading, (3) main conductor, (4) fuse element and (5) transducer Source: ABB Calor Emag Schaltanlagen AG is able to quench the short-circuit according to the fuse It-characteristic. The main elements, i.e., the isolating tube with main conductor and fuse element, need to be replaced after operation of the Ip-limiter. A measuring unit with tripping circuit is needed to compare the actual current value with the threshold value. Ip-limiters are nowadays available with thyristor technique. The short-circuit current can be limited within 1–2 ms after initiation of the fault. The Ip-limiter is back in operation after fault clearing; an exchange of main conductor and fuse is not necessary. Additional operational functions, such as limitation of start-up current of large motors can also be realised. Superconducting Ip-limiters are actually in laboratory tests [7]. 11.2.3 Measures concerning equipment 11.2.3.1 Impedance voltage of transformers Transformers with high impedance voltage are reducing the short-circuit level, however the reactive power losses are increased and the tap-changer needs to be designed for higher voltage drops. Figure 11.11 indicates the equivalent circuit diagram of a 10-kV-system fed from a 110-kV-system by three transformers SrT = 40 MVA. The system load is SL = 72 MVA, cos ϕ = 0.8. The short-circuit  = 2.2 GVA; the voltage at the 10-kV-busbar shall power of the 110-kV-system is SkQ be controlled within a bandwidth of ±0.125 kV around U = 10.6 kV. (a) 110 kV EL149 EL148 EL150 EL151 EL148 10-KV Un = 10.000 kA I k0 (L1) = 35.221 kA S 0k(L1) = 610.042 MVA I 0k(L1) = 11.740 kA S 0k(L1) = 203.347 MVA Each cable I k0 (L1) = 0.000 kA S k0 (L1) = 0.000 MVA (b) 110 kV EL149 EL148 EL150 EL151 EL148 I 0k(L1) = 9.719 kA S 0k(L1) =168.333 MVA 10-kV Un = 10.000 kV I k0 (L1) = 29.156 kA S k0 (L1) = 504.999 MVA Each cable I k0 (L1) = 0.000 kA S 0k(L1) = 0.000 MVA Figure 11.11 Equivalent circuit diagram of a 10-kV-system with incoming feeder. Results of three-phase short-circuit current calculation: (a) Impedance voltage 13% and (b) impedance voltage 17.5% Table 11.2 UkrT (%) 13 17.5 Result of loadflow and short-circuit analysis as per Figure 11.11  Ik3 (kA)  Ik1 (kA) Tap-changer position Reactive power losses of one transformer (Mvar) 35.2 29.2 22.5 20.7 +6 +8 2.61 3.58 238 Short-circuit currents The relevant results of loadflow and short-circuit analysis are outlined in Table 11.2. As can be seen the increase of the impedance voltage from 13 to 17.5 per cent reduces the short-circuit current, but increases the reactive power losses and increases the number of steps at the tap-changer to control the voltage. 11.2.3.2 Short-circuit limiting reactor The application of short-circuit limiting reactors can be defined as a measure related to switchyards or a measure related to equipment. Figure 11.12 outlines the equivalent circuit diagram of a 10-kV-system in industry with direct connection to an urban 10-kV-system. Two reactors are installed to limit the short-circuit currents. The three-phase short-circuit current without local generation in the industrial system  = 20.43 kA. at the coupling busbar between industry and utility is Ik3 I 0k(L1) = 21.29 kA I 0k(L1) =14.43 kA I 0k(L1) = 21.06 kA I 0k(L1) = 21.06 kA I k0 (L1) =19.28 kA I 0k(L1) =19.28 kA M I 0k(L1) = 1.75 kA M I k0 (L1) = 1.60 kA I 0k(L1) =19.24 kA I k0 (L1) = 19.24 kA M I k0 (L1) = 1.32 kA Ik0(L1) = 1.80 kA Figure 11.12 M I k0 (L1) = 1.46 kA Equivalent circuit diagram of a 10-kV-system with short-circuit limiting reactors. Results of three-phase short-circuit current calculation The industrial system is connected to a heat and power plant with four generators 6.25 MVA each, three out of four are allowed to be in operation at the same time. The short-circuit current is increased by this to 25.6 kA. To limit the short-circuit  ≤ 21.5 kA reactors with I = 1600 A; u = 20% were installed. The current to Ik3 n k  = 21.3 kA. short-circuit current is reduced to Ik3 11.2.3.3 Earthing impedances Single-phase short-circuit currents can be reduced significantly by the installation of earthing impedances in the neutral of transformers or at artificial neutrals without affecting the three-phase short-circuit currents. Figure 11.13 represents an 11.5-kV-system fed from the 132-kV-system. Each substation is equipped with four transformers (Sr = 40 MVA, uk = 14%). The 132-kV-system has direct neutral  ≈ 29.3 kA and I  ≈ 37.3 kA. earthing, the short-circuit currents are Ik3 k1 Limitation of short-circuit currents 239 S 0kQ = 6.7 GVA Z0/Z1 = 0.454 UnQ = 132 kV Figure 11.13 Un = 11.5 kV Equivalent circuit diagram of 11.5-kV-system fed from the 132kV-system The permissible short-circuit current in the 11.5-kV-system is 25 kA. The  = 15.04 kA when one single-phase short-circuit currents at 11.5-kV-busbar are Ik1  transformer is in operation and Ik1 = 29.27 kA when two transformers are operated in parallel. In order to limit the single-phase short-circuit current on the 11.5-kV-side to  < 25 kA (two transformers in parallel), an earthing resistance of R = 0.31  or Ik1 E an earthing reactor of XE = 0.1  need to be installed in the 11.5-kV-neutral of each of the transformers [3]. 11.2.3.4 Increased subtransient reactance of generators Generators are the direct sources for short-circuit currents; the contribution of one generator to the short-circuit current is inversely proportional to the subtransient reactance Xd when the voltage is not changed, see Chapters 3 and 4. An increased subtransient reactance reduces the branch short-circuit current and by this the total short-circuit current. Figure 11.14 indicates the results of short-circuit current calculation of a power station. Generators of different make but identical rating SrG = 150 MVA are installed. The three-phase branch short-circuit currents are in  = 2.32–2.75 kA depending on the subtransient reactance. the range of Ik3 240 Short-circuit currents EL144 400 EL142 EL143 EL143 Ik(L1) = 7.967 kA Sk⬙(L1) = 1821.450 MVA 132K Un =132.000 kV Ik⬙(L1) = 31.569 kA Sk⬙(L1) = 7217.597 MVA GT4A1T Ik⬙(L1) = 2.749 kA Sk⬙(L1) = 628.456 MVA GT2T Ik⬙(L1) = 2.322 kA Sk⬙(L1) = 530.987 MVA GT3T Ik⬙(L1) = 2.535 kA Sk⬙(L1) = 579.469 MVA Figure 11.14 GT1A1T Ik⬙(L1) = 2.749 kA Sk⬙(L1) = 628.456 MVA GT1T Ik⬙(L1) = 2.535 kA Sk⬙(L1) = 579.469 MVA GT2A1T Ik⬙(L1) = 2.749 kA Sk⬙(L1) = 628.456 MVA Equivalent circuit diagram of a power station with 132-kV-busbar. Results of three-phase short-circuit current calculation: SrG = 150 MVA; xd = 12–17.8% High subtransient reactance of generators has a negative impact on the dynamic stability performance of the generators. In the case of short-circuits on the transmission line with subsequent fault clearing the transmittable power from a power station is reduced if the fault clearing time of the protection is kept constant, respectively, the fault clearing time must be reduced to keep the transmittable power constant. Details can be obtained from [2, 26]. 11.3 Structures of power systems 11.3.1 General It should be noted that some of the measures as per Section 11.2 to reduce short-circuit currents can only be applied in certain power systems. Ip-limiters are only available in low voltage and medium voltage systems. When only a single busbar is installed, the operation with two busbars is not possible and in a radial fed system, no additional feeding point is normally available. Within this section, the main structures of power systems are introduced: • • • Radial system Ring-main system Meshed system More details can be obtained from [26]. Limitation of short-circuit currents 241 11.3.2 Radial system Radial systems represent the simplest topology of a power system and can usually be found in low voltage systems. Figure 11.15 outlines the general structure, with one feeding point and distributing of the lines in several branches. This structure is suitable in the case of low load density but also for the connection of high bulk-supply loads. The calculation of short-circuit currents is comparatively easy, as there are no meshed lines in the system and only one topology has to be analysed. MV/LV-transformer Figure 11.15 General structure of a radial system with one incoming feeder 11.3.3 Ring-main system In a ring-main system the receiving end of each line of a radial system is to be connected either back to the feeding busbar or to an additional feeding busbar. Ringmain systems are most often planned for medium voltage systems, and in rare cases for low voltage systems as well. Normally ring-main systems are operated with open breaker or isolator in one primary as indicated in Figure 11.16(a). This enables an operation similar to radial systems but with a switchable reserve for all consumers. Feeding busbars can be planned at several locations of the system as indicated in Figure 11.16(b). Short-circuit current calculation is more complicated than in radial systems as several operating conditions, i.e., system topologies, are to be taken into account to determine the minimal and the maximal short-circuit current. 11.3.4 Meshed systems Meshed systems are normally applied only for high voltage systems or in industrial supply systems for MV-level as well. With the consideration of consumer load and 242 Short-circuit currents (a) (b) Switch (normally open) Figure 11.16 MV/LV-transformer General structures of ring-main systems: (a) Simple structure with one feeding busbar and (b) structure with two feeding busbars (feeding from opposite sides) Interconnection lines to neigbouring countries GS 3~ GS 3~ 380-kV transmission system 220-kV subtransmission system (regional distribution) Industrial systems 35-kV 20-kV GS 3~ 110-kV (urban area with generation) 10-kV (20-kV) distribution system Figure 11.17 110-kV system (rural areas) 10-kV 20-kV (35-kV) Principal structure of a high voltage system with different voltage levels GS 3~ 110-kV-system (industry with generation) GS 3~ 244 Short-circuit currents capability of power stations, the system is planned, constructed and operated in such a way as to allow the supply of consumers without overloading of any equipment and without violating the permissible voltage profile even under outage of one ((n − 1)criteria) or more equipment at the same time. The calculation of maximal short-circuit currents seems relatively simple, if all equipment are assumed to be in operation. As far as different operation schedules of the power stations are considered, different system topologies need to be considered. The calculation of the minimal short-circuit current, however, is much more difficult, as a close cooperation between planning and operation is required. A large number of different topologies in the meshed power system have to be analysed to ensure that the calculated short-circuit current is the minimal current. The principal structure of a meshed high voltage system is outlined in Figure 11.17. A special type of meshed systems is applied to low voltage systems; the principal structure is outlined in Figure 11.18. The reliability of supply is comparatively high, as reserve in the case of outage of any line or infeed is provided through the remaining lines. (a) MV-cable Switch (normally open) 2 1 (b) 3 3 2 2 1 3 1 3 2 1 1; 2; 3 Connection to MV-cable No. 1; 2; 3 Figure 11.18 Principal structure of meshed low voltage system: (a) Single-fed meshed system and (b) meshed system with overlapping feeding Chapter 12 Special problems related to short-circuit currents 12.1 12.1.1 Interference of pipelines Introduction Interference between overhead lines, communication circuits and pipelines is caused by asymmetrical currents, which may be due to short-circuits, asymmetrical operation or asymmetrical design of equipment, especially asymmetrical outline of overhead line towers with respect to pipelines and communication circuits. This interference is based on inductive, ohmic and capacitive coupling between the short-circuit path (e.g., overhead line) and the circuit affected by interference (e.g., pipeline). Normal operating currents, respectively voltages, cause magnetic as well as electric fields which are asymmetrical in the vicinity of overhead lines which may cause interference problems in the long-time range. Short-circuit currents on overhead transmission lines and cables and short-circuit currents through earth cause interference in the short-time range only when the shortcircuit is switched off after some seconds by the power system protection. Interference problems may arise in cable and overhead line systems to a different extent depending on the handling of the system neutral. The induced voltage in pipelines and communication circuits may endanger technical installations and safety of workers when defined limits will be exceeded. Within the context of this book, only the short-time interference, in the following called interference, is dealt with. Table 12.1 outlines the needs for the analysis of interference problems. Interference problems may occur in most of the cases by inductive and ohmic coupling in power systems with low-impedance earthing consisting mainly of overhead lines, as can be seen from Table 12.1. In systems with isolated neutral or resonance earthing interference problems have to be regarded only when the fault current is not self-extinguishing (see Chapters 5 and 7). Capacitive coupling does not cause any Table 12.1 Interference between power system, communication circuits and pipelines Power system Interference of communication circuits and pipelines by: Handling of neutrals Operating condition Low-impedance earthing Without fault OHTL Cable Short-circuit OHTL Cable Without fault OHTL Cable Short-circuit; Earth fault OHTL Cable No interference Double earth fault OHTL Cable Present No interference Isolated neutral; Resonance earthing Inductive coupling Capacitive coupling Only if circuits on same tower No interference problems Present Present in special cases No interference No interference Only if circuits on same tower No interference Present No interference No interference No interference Ohmic coupling No interference Present No interference No interference No interference Present No interference Special problems related to short-circuit currents 247 severe problems in pipelines and communication circuits. It should be noted furthermore that interference of communication circuits is decreasing due to the decreasing installations of overhead communication circuits, which are replaced by wireless communication or by cable circuits, which can be protected easily against interference. The explanations on interference are therefore concentrated within this section to the interference of pipelines. Regulations on the permissible values for voltages induced in pipelines and communication circuits and/or for touch voltages exist in various countries. The main aim is to protect any person likely to work on the pipeline or power circuit against electrocution hazard. According to an international survey carried out by CIGRE [20], the maximum permissible touch voltage is defined in different countries in different ways, ranging from 200 V up to 1500 V depending on the maximal fault duration time. In Germany, the maximal permissible touch voltage and the maximal permissible voltage pipeline-to-earth are both limited to 1000 V for a fault-duration of 0.5 s. Higher values are applied only in Australia (1500 V) and in Brazil (1700 V), whereas the Brazilian regulation defines the admissible value of a touch current, which is converted for comparison into the voltage limit. Within this survey, only two US-utilities have answered the questions on voltage limits. The limit for the touch voltage applied there is given to be 500 V, whereas the voltage pipeline-to-earth should be less than 5 kV. It is unclear and could not be clarified in the CIGRE-survey, why low value for touch voltage (500 V) as compared with other countries resulted in a comparatively high value for the pipeline-to-earth voltage (5 kV). According to [21] the maximal permissible voltage pipeline-to-earth for shorttime interference shall be below 1000 V. If ASME/IEEE-standard No. 80 is applied a maximal permissible touch voltage is defined in relation to the fault duration time for different body weight of the person involved. If the most severe restrictions are applied, i.e., 50 kg body weight and fault duration (clearing time) of 150 ms, the maximal permissible touch voltage Ut50 is 350 V. This is the recommended limit as per IEEE-standard No. 80 item 6, where it is mentioned that the actual transferred voltage should be less than the maximum allowable touch voltage Etouch to ensure safety. 12.1.2 Calculation of impedances for inductive interference In order to calculate the interference of pipelines the loop-impedances, coupling impedances and self-impedances of the line conductor, earth conductors and the pipeline itself are required. The loop-impedance of the pipeline with earth return is Z P = RP μ0 + ∗ω+j 8   μP μ0 δ + ∗ ω ∗ ln 2π rP 4 (12.1) where rP is the outer radius of the pipeline, μ0 is the absolute permeability, μP is the fictitious relative permeability of the pipeline, δ is the depth of earth return path and ω is the angular frequency. 248 Short-circuit currents Equation (12.1) is composed of RP μ0 ∗ω 8 δ μ0 ∗ ω ∗ ln 2π rP μP μ0 ∗ω∗ 2π 4 Resistance of the pipeline per unit length Resistance of the earth return path per unit length Outer reactance of the loop with earth return path per unit length Internal (inner) reactance of the conductor (pipeline) per unit length The depth δ of the earth return path is given by Equation (12.2) with the resistivity of soil ρ (specific soil resistance) according to Table 12.2. δ=√ Table 12.2 Parameters 1.85 ω ∗ (μ0 /ρ) (12.2) Resistivity of soil ρ for different types of soil conditions Type of soil Alluvial soil – swamp soil Specific soil resistance 30 ρ (m) σ = 1/ρ (µS/cm) 333 Depth of earth return 510 δ at 50 Hz (m) Depth of earth return 465 δ at 60 Hz (m) Clay Limestone clay – farm soil Wet sand Wet gravel Dry sand Dray gravel Stony soil 50 100 200 500 1000 3000 20 660 10 930 5 1320 2 2080 1 2940 0.33 5100 600 850 1205 1900 2684 4655 The resistance RP of the pipeline can be calculated from the conductivity κP and the thickness d of the pipeline wall taking eddy currents and the dissipation of the current into the outer level of the pipeline wall into account.  3   (12.3) RP = Rdc ∗ x + 0.25 + 64 ∗ x The increase of the inner inductivity Xi is given by  3 3  ∗ x− + Xi = Rdc 64 ∗ x 128 ∗ x 2 (12.4) Special problems related to short-circuit currents 249  , the with the parameter x = d/(2 ∗ δP ), the d.c. resistance of the pipeline wall Rdc depth of current in the pipeline wall δP and d being the thickness of the pipeline wall: 1 δP = √ ω/2 ∗ (κP ∗ μP ∗ μ0 ) (12.5) Comparing the loop-impedance as per Equation (12.1) with the inner inductance of the pipeline as per Equation (12.4) the fictitious relative permeability of the pipeline will be  μP = 4 ∗ Rdc ∗ x − 3/(64 ∗ x) + 3/(128 ∗ x 2 ) (ω ∗ μ0 )/2π (12.6) Coupling impedances [2] need to be calculated for the analysis of the interference problems. For the individual distances and impedances reference is made to Figure 12.1 indicating a typical interference problem between a 380-kV-line with two earth wires, counterpoise and a pipeline. The coupling impedance Z LP of the loop conductor and pipeline with earth return is obtained from   μ0 μ0 δ  Z LP = (12.7) ∗ω+j ∗ ω ∗ ln 8 2π dLP min The coupling impedance Z EP of the loop earth conductor and pipeline with earth return is obtained from   μ0 δ μ0  Z EP = ∗ω+j ∗ ω ∗ ln (12.8) 8 2π dEP min Coupling impedance Z LE of the loop earth conductor and conductor with earth return is given by   μ0 δ μ0 Z LE = ∗ω+j ∗ ω ∗ ln (12.9) 8 2π dLE In case a second earth conductor is installed, the coupling impedance Z EP2 of the loop second earth conductor and pipeline with earth return is calculated by   μ0 δ μ0  Z EP2 = (12.10) ∗ω+j ∗ ω ∗ ln 8 2π dEP2 min The coupling impedance Z LE2 of the loop second earth conductor and conductor with earth return is obtained from   μ0 μ0 δ  Z LE2 = (12.11) ∗ω+j ∗ ω ∗ ln 8 2π dLE2 The coupling impedance Z E12 of the loop first and second earth conductor and conductor with earth return is obtained from   μ0 δ μ0 Z E12 = (12.12) ∗ω+j ∗ ω ∗ ln 8 2π dE12 250 Short-circuit currents E2 E; E1 dE12 dLE dLE2 s L dEP2min dLBmin dEPmin dLPmin P B hP dBP d Figure 12.1 Outline and distances of a high-voltage transmission-line tower. B: counterpoise; P: pipeline; L: conductor nearest to pipeline. E; first earth conductor (nearest to pipeline), also named E1; E2: second earth conductor Special problems related to short-circuit currents 251 Furthermore the loop-impedance Z E of the earth conductor and earth return is given by    μ0 δ μr μ0 ∗ω+j ∗ ω ∗ ln + (12.13) Z E = R  + 8 2π r 4 Quantities as per Equations (12.7) to (12.13) are: dLPmin dEPmin dLE dEP2min dLE2 dE12 r R Minimal distance between the pipeline and the lowest conductor nearest to the pipeline Minimal distance between the pipeline and the earth conductor Distance between the earth conductor and the lowest conductor nearest to the pipeline Minimal distance between the pipeline and the second earth conductor Distance between the second earth conductor and the lowest conductor nearest to the pipeline Distance between the first and second earth conductor Radius of earth conductor Resistance of earth wire per unit length. Generally the minimal distances between the conductors and the pipeline have to be considered. This includes considerations on the conductor sag and the conductor swing under worst conditions. The mean effective height hS of the conductor may be calculated from hS = hL − 0.667 ∗ s̄ (12.14) where hL is the conductor height at the tower and s̄ is the conductor sag. In some cases a counterpoise parallel to the pipelines is used to reduce the induced voltage into the pipeline. The coupling impedances with the conductor are needed in these cases. The coupling impedance Z B of the loop counterpoise and earth return is obtained from    μB μ0 δ μ0   + ∗ω+j ∗ ω ∗ ln (12.15) Z B = RB + 8 2π rB 4 The coupling impedance Z LB of the loop conductor and counterpoise with earth return is obtained from   μ0 δ μ0 ∗ω+j ∗ ω ∗ ln (12.16) Z LB = 8 2π dLB min The coupling impedance Z BP of the loop pipeline and counterpoise with earth return is calculated from   μ0 μ0 δ  (12.17) ∗ω+j ∗ ω ∗ ln Z BP = 8 2π dBP where rB is the radius of counterpoise, μB is the fictitious relative permeability of counterpoise, RB the resistance of counterpoise per unit length, dLBmin is the minimal 252 Short-circuit currents distance between counterpoise and the lowest conductor nearest to the pipeline, dBP is the distance between counterpoise and pipeline. 12.1.3 Calculation of induced voltage Based on the impedance calculations as per Section 12.1.2 the induced voltage into the pipeline can be calculated for any configuration as follows: U iP = −Z LP ∗ r  ∗ I kE ∗ lPp ∗ w (12.18) where Z LP is the coupling impedance of the loop pipeline and conductor nearest to earth with earth return, I kE is the initial short-circuit current (asymmetrical) of the overhead line, lPp is the length of parallel exposure between pipeline and overhead line, r  is the screening factor as per Equation (12.18) and w is a probability factor taking into account that all worse conditions do not occur at the same time instant [21]. The screening factor depends on the presence of earth wires, counterpoises and any other compensation circuit capable to reduce the induced voltage into the pipeline. If only one earth wire is present as compensation circuit the screening factor r  is calculated based on the coupling and loop-impedances by r = 1 − Z LE ∗ Z EP Z E ∗ Z LP (12.19) If more than one earth conductor or additional compensation circuits are present, additional considerations for the screening factor are required. The total screening factor is then given by the difference of the individual factors of each earth conductor and/or compensation circuit taking into account the correction factor which represents the influence of each earth wire and compensation circuit on the current in the other wire [22]. In the case of two earth conductors the total screening factor r tot is given by r tot = 1 − Z LE2 ∗ Z EP2 Z LE ∗ Z EP − ∗ k ∗ k1 2 Z E ∗ Z LP Z E2 ∗ Z LP (12.20) Correction factors k1 and k2 are calculated by k1 = 1 − (Z LE ∗ Z E12 )/(Z E ∗ Z LE2 ) 1 − (Z E12 ∗ Z E12 )/(Z E ∗ Z E2 ) (12.21a) k2 = 1 − (Z LE2 ∗ Z E12 )/(Z E2 ∗ Z LE ) 1 − (Z E12 ∗ Z E12 )/(Z E ∗ Z E2 ) (12.21b) Special problems related to short-circuit currents 253 Correction factors for other arrangements and numbers of conductors can be obtained, respectively calculated, as per [39]. Impedances as per Equations (12.19) to (12.21) are calculated according to Section 12.1.2 Z LP Z EP Z LE Z EP2 Z LE2 Z E12 ZE Z E2 Coupling impedance of the loop conductor and pipeline with earth return as per Equation (12.7) Coupling impedance of the loop first earth conductor and pipeline with earth return as per Equation (12.8) Coupling impedance of the loop first earth conductor and conductor with earth return as per Equation (12.9) Coupling impedance of the loop second earth conductor and pipeline with earth return as per Equation (12.10) Coupling impedance of the loop first earth conductor and conductor with earth return as per Equation (12.11) Coupling impedance of the loop first and second earth conductor with earth return as per Equation (12.12) Loop-impedance of earth conductor and earth return as per Equation (12.13) Loop-impedance of second earth conductor and earth return as per Equation (12.13) For three and more compensation circuits, e.g., two earth conductors and a counterpoise, the screening factor needs to be calculated either from the individual current distribution within the different compensation circuits or by means of the multiplication method or other methods as outlined in [3]. 12.1.4 Characteristic impedance of the pipeline The induced voltage U iP is only an indication for the inductive interference but does not take into account the earthing conditions and the conductivity of the pipeline coating. In order to calculate step and touch voltages the voltage between pipeline and earth is to be calculated taking account of the earthing and conductivity conditions of the pipeline. Based on the analysis of the system equivalent, i.e., faulted phase conductor, presence of earth conductors, counterpoise, pipeline and earthing conditions, the pipeline must be represented by means of its characteristic impedance and its conductivity. The conductivity of the pipeline against the surrounding earth is determined by  of the bare (uncoated) the resistance RI of the pipeline coating and the resistance RPE pipeline in earth (see Table 12.3). The total resistance is given by   = RI + RPE RCtot (12.22) The specific reactance due to the capacitance of the pipeline can be neglected for  of interference analysis as it is much smaller than the resistance. The resistance RPE 254 Short-circuit currents Table 12.3 Resistance of pipeline coatings [23] Type of coating Thickness of coating (mm) Specific coating resistance (k m2 ) Bitumen Polyethylene Epoxy resin 4–6 2–3 0.3–0.6 10 100 10 the bare (uncoated) pipeline in earth is calculated by  2∗l ρ ∗ 2 ∗ ln 4π d  = RPE + ln (2 ∗ hP )2 + (l/2)2 + l/2 (2 ∗ hP )2 + (l/2)2 − l/2 (12.23) where hP is the depth of pipeline under ground, l is the total length of pipeline, d is the outer diameter of pipeline and ρ is the resistivity of the soil as per Table 12.2. It should be noted that the influence of the earth resistivity is comparatively low for high resistance of pipeline coating. The characteristic impedance Z W , the propagation constant γ and the characteristic length LK of the pipeline are required prior to the calculation of the voltage pipeline-to-earth.  Z P ∗ RPE ZW = γ =  LK = (12.24) Z P  RPE (12.25) 1 Re   Z P /RPE  (12.26) where Z P is the loop-impedance of pipeline and earth return per unit length as per  is the resistance of the bare (uncoated) pipeline as per Equation (12.1) and RPE Equation (12.23). 12.1.5 Voltage pipeline-to-earth The voltage pipeline-to-earth U PE (x) along the exposure length is calculated based on the theory of line propagation for each individual location x of the pipeline. Using the abbreviations I ∗kE = r tot ∗ I kE ∗ Z LP ∗w ZP (12.27a) Special problems related to short-circuit currents 255 and b = 0.5 ∗  ∗l Z P ∗ RPE (12.27b) where l is the length of pipeline, Z P is the loop-impedance of pipeline and earth return per unit length as per Equation (12.1), R PE is the resistance of the bare (uncoated) pipeline as per Equation (12.23), r tot is the total reduction factor as per Equation (12.20), Z LP the coupling impedance of the loop conductor and pipeline with earth return as per Equation (12.7), I kE is the short-circuit current through earth and w the probability factor. The voltage pipeline-to-earth along the exposure length (parameter x) is calculated taking account of the earthing resistances R1 and R2 at the end of the pipeline, respectively at the end of section, under investigation by U PE (x) = Z W ∗ I ∗kE ∗ {R1 (Z W + R2 )eb+γ x + R2 (Z W − R1 )e−b+γ x − R1 (Z W − R2 )e−b−γ x − R2 (Z W + R+ )eb−γ x } ∗{(Z W +R1 ) ∗ (Z W + R2 )e2b − (Z W − R1 ) ∗ (Z W − R2 )e−2b }−1 (12.28) Outside the exposure length (parameter y) the voltage pipeline-to-earth decays for each individual location y of the pipeline according to U PE (y) = U 1 ∗ + RA − Z W (RA + Z W )e2γ l + (RA − Z W ) (RA + Z W )e2γ l (RA + Z W )e2γ l + (RA − Z W ) eγ l e−γ l (12.29) where U 1 is the voltage at the end of exposure length, RA is the far-end impedance of the pipeline, l is the total length of pipeline outside exposure length, γ is the propagation constant and Z W is the characteristic impedance. The method described above assumes constant parameters I ∗kE and for the effec of the pipeline coating against earth and constant distance between tive resistance RPtot the pipeline and the overhead line. In other cases the analysis has to be carried out for each individual section having constant or nearly constant parameters by separation of the exposure length into subdivisions for which constant parameters can be assumed. In case of oblique exposures or crossing between overhead line and pipeline the exposure length has to be divided into different subsections having equal induced voltages. An average distance ao between the overhead line and the pipeline has to be calculated ao = √ a1 ∗ a 2 (12.30) 256 Short-circuit currents (a) Pipeline lII a3 lI lIII a2 lIV OHTL a1 (b) L L Tower dLPc Tower P Figure 12.2 Oblique exposure and crossing of pipeline and overhead line. (a) Plot plan and (b) elevation plan (detail from crossing location) The parameters a1 and a2 are the distances at the ends of the oblique exposure, see Figure 12.2 for details. The ratio a1 /a2 should not exceed the value of three otherwise further subdivisions have to be selected. Distances of more than 1000 m between overhead line and pipeline can be neglected for short-time interference. Crossings shall be handled similarly to oblique exposures with the restriction that the subdivisions in the vicinity of the crossing shall be selected as short as possible. Special problems related to short-circuit currents 257 The distance between the overhead line and the pipeline at the location of crossing shall be set equal to the minimal height of the overhead conductor above the pipeline dLPc , taking account of the average conductor sag, see Figure 12.2(b). The average distance ac between the overhead line and the pipeline is given by ac = a2 ∗ dLPc (12.31) The results for each subdivision have to be superimposed for each location of the pipeline. 12.2 12.2.1 Considerations on earthing General The influence of neutral handling and to some extent of the earthing was outlined already in Chapters 5 and 7. The handling of neutrals, however, requires additionally the analysis of the earth itself, of earthing grids and rods and on step and touch voltages related to earthing. With respect to the main task of this book, i.e., calculation and analysis of short-circuit currents and their effects, the earthing in power systems are only dealt with in relation to the impact of short-circuit currents on earthing. Special problems such as corrosion of earthing material, influence of earthing on lightning and on fast-front overvoltages are not explained here. More details can be found in [5, 26]. Equipment and installations in power systems have to be designed and operated in such a way to avoid impermissible conditions with respect to the health of human beings and animals also taking into account reliable and sufficient operation of the technical installations. Earthing in power systems is one of the main items to ensure this safe and secure operation. Asymmetrical operation and short-circuits cause currents flowing through earth which may flow as well through the human body in the case of contact of the body with earth or with installations connected to earth. The earthing problem is determined by • • • • • Resistance of human body Electrical conditions of the earth Current through earth Fault duration Earthing impedance 12.2.2 Resistance of human body The impedance of the human body, which is mainly a resistance, is determined by the location of contacts to the electrical installations and depends on the touch voltage as well. Figure 12.3 indicates the resistance of the body if measured between the two hands, valid approximately 10 ms after initiation of currents through the body. As 258 Short-circuit currents 5 4.5 4 3.5 R (kΩ) 3 2.5 2 1.5 1 0.5 0 0 100 Figure 12.3 200 300 400 UB (V) 500 600 700 800 Impedance of the human body (hand-to-hand) depending on the touch voltage can be seen the resistance is between 3.5 k and 1.1 k decreasing with increasing touch voltage. For other contacts the resistance is reduced, e.g., • • • • One hand to breast One hand to knee Two hands to breast Two hands to knee reduction to 45 per cent of resistance as per Figure 12.3 reduction to 70 per cent of resistance as per Figure 12.3 reduction to 23 per cent of resistance as per Figure 12.3 reduction to 45 per cent of resistance as per Figure 12.3 It should be noted in this respect that the current through the human body is the critical physical phenomena causing uncontrolled operation of the heart (ventricle flicker) or muscle convulsion. The critical current is a function of the exposure time [24]. The duration of the permissible touch voltage UB therefore depends on the exposure time as well (fault duration) and is outlined in Figure 12.4. The permissible touch voltage is set in most of the standards to UB = 65 V, resulting in a negligible risk for ventricle flicker independent from the time of exposure. If this voltage limit cannot be guaranteed the exposure time must be limited. 12.2.3 Soil conditions The resistivity of the soil depends on the type of soil (swamp soil, stony soil) as outlined in Table 12.2. The differences are determined by the humidity of the soil. The value for swamp soil is between 10,000 m (humidity less than 10 per cent) and 30 m (humidity 90 per cent). It is obvious that the resistivity of the soil varies in a wider range if surface electrodes will be used for earthing as the soil humidity Special problems related to short-circuit currents 259 800 700 600 UB (V) 500 400 300 200 100 0 0.1 Figure 12.4 1 Time of exposure (s) 10 Permissible touch voltage depending on the time of exposure varies in a wider range throughout the year as compared with deep-ground earthing by earthing rods. The resistivity for surface electrodes varies throughout the year in a range of ±30 per cent, in the case of deep-earthing only in a range of ±8 per cent of the average value, the highest value occurring in March and the lowest value in August (European countries). It is therefore recommended to use surface electrodes only in those installations where the soil humidity is nearly constant throughout the year and to use deep-ground earthing for other conditions. 12.2.4 Relevant currents through earth Currents through earth are only existing in the case of asymmetrical short-circuits with earth connection. In most of the cases (X0 /X1 > 1), the single-phase short-circuit  is greater than the current through earth I  current Ik1 kE2E in case of a double-phase short-circuit. Only in case of power systems (e.g., 115 and 132 kV) having high amount of cables, power stations with high rating closely connected to the system under investigation and when all transformer neutrals are earthed through low impedance, can the ratio X0 /X1 be below One. In these cases the double-phase short-circuit current may exceed the single-phase short-circuit current. Current through earth causes voltage drops UE at the impedance of the earth, at the earthing itself and at the connection lines between the equipment (e.g., neutrals of transformers, transformer tank, overhead line tower) and earth. The currents to be taken into account as summarised in Table 12.4 depend on the type of neutral handling in the system. Table 12.4 Currents through earth for the design of earthing installations Valid for Type of neutral handling Isolated neutral Low-impedance earthing Earthing with current limitation Resonance earthing Voltage at earthing Touch voltage ICE Current through earthing impedance Current through earthing impedance 2 + I2 With reactor: IrD res Without reactor: IRes Thermal stress of earthing and earthing connections  IkEE  or I  Ik1 kE2E  or I  Ik1 kE2E  IkEE Earthing connections Earthing voltage UE Touch voltage UB  or I   or I  Ik1 Ik1 kE2E kE2E UE ≤ 125 V: no measures required UE > 125 V then UB ≤ 65 V UE > 125 V then UB according to or equivalent measures VDE 0141 depending on fault according to VDE 0141 duration or fast switch-off or equivalent measures according to VDE 0141 ICE  IkEE UE > 125 V then UB ≤ 65 V or equivalent measures according to VDE 0141 Special problems related to short-circuit currents 261 Table 12.5 Reduction factor for typical power system installations; distance of earth conductor to phase conductor D ≈ 20 m; ρ = 100 m Number of conductors Type and cross-section 1 Earth conductor St 50–90 Al/St 50/30 Al/St 120/70 Al/St 240/40 Al/St 120/70; counterpoise Cu 120 2 Earth conductors Cable sheet Al/St 95/55 NA2XS(2)Y; 150Al; 20 kV Single-core cable; 110 kV N2XS(SL)2Y; 240Cu; 110 kV Cables in steel tube Reduction factor 0.98 0.78 0.7 0.65 0.52 0.5 0.5 0.1 0.27 <0.05 As mentioned already in Section 7.3, a part of the single- or double-phase earthfault current is flowing through earth and the relevant impedances of the earthing installations, depending on the reduction factor of the earth conductor and/or of cable screens and sheets connected to earth. Detailed investigations are required to determine the reduction factor. For rough estimates the reduction factors for typical installations are given in Table 12.5. 12.2.5 Earthing impedance The impedance, i.e., the resistance of the earthing installations is determined by the material of the earthing grid, electrodes and rods and by the presence of any connection of earth conductor, counterpoise, cable sheets and other earthed installations in the vicinity of the earthing installation. The earthing resistance is proportional to the resistivity of the soil and depends furthermore on the specific arrangements of the earthing installations as outlined in Table 12.6. The equations as per Table 12.6 for the calculation of the resistance of earthing installation indicate that it is not recommendable to increase the number of meshes in an earthing grid in order to reduce the earthing impedance, as the effect is only marginal. Increasing the number of earthing rods on the same earthing installation is highly recommendable as the total earthing impedance is approximately reciprocal to the number of rods. Sufficient distance between the individual rods (at least more than the rod-length) shall be provided in this case. Material, cross-sections and laying of the earthing installations must comply with the relevant standards, e.g., ANSI C 33.8 (standard for safety grounding and bonding equipment). 262 Short-circuit currents Table 12.6 Resistance of earthing installations REI for different types and arrangement Type of earthing Earthing resistance Single deep-ground rod REI = l d Multiple deep-ground rod d 1 2 n a Surface electrode 4l ρ ∗ ln 2π ∗ l d ρ 4l 1 ∗ ln a≥l REI ≈ k ∗ ∗ n 2π ∗ l d k = 1.2–1.5 n = 5: k ≈ 1.2 n = 10: k ≈ 1.25 d REI = 2l ρ ∗ ln πl d REI ≈  4l ρ ∗ 2.5 + ln 2π ∗ l d l Crossed surface electrode Earthing grid: uniform resistivity of soil l b l Earthing grid: two layers of resistivity Earthing grid D1 r1 r2 12.3 12.3.1  ρ ρ 4b ∗ l REI ≈ + π 2∗D ltot ltot total length of earthing grid  ρ2 ρ ∗ D1 4b ∗ l D= REI ≈ + 1 π 2∗D b∗l ρ1 : resistivity of surface layer ρ2 : resistivity of deep layer D= Examples Interference of pipeline from 400-kV-line The exposure of a 32 -pipeline with an overhead line (400 kV) as outlined in Figure 12.5 is analysed. The nearest distance of the pipeline is 27 m at tower No. 3, increasing to 160 m at tower No. 7 over a length of approximately 1600 m, decreasing to 120 m over a length of 1450 m and then crossing the overhead line at an angle of 90◦ between towers Nos 10 and 11. The elevation plan of the tower and the pipeline is given in Figure 12.6. Special problems related to short-circuit currents 263 1450 m #7 #10 #11 1620 m OHTL 140 m #3 120 m 60 m 27 m Pipeline 3074 m Figure 12.5 Plot plan of the exposure length pipeline and transmission line The pipeline parameters are outlined below. The pipeline is not buried into earth, but laid directly on the surface. The total exposure length is 3074 m. At location x = 0 at tower No. 2 the pipeline is equipped with an isolating flange. The average sag of the line conductor and of the earth conductor is 10.2 m, the specific resistivity of the soil is 4 m. Type of pipeline Diameter Thickness of wall Conductivity Relative permeability Specific resistance of pipeline coating 32 steel pipe 1524 mm 22.2 mm 5.56 Sm/mm2 200 20.3 /km The induced voltage of the pipeline was calculated with the procedure explained in the previous sections. The individual sections of the exposure length were chosen according to the distances between the transmission towers. The specific field strength and the specific induced voltage, both related to units of the short-circuit current, are given in Figure 12.7. The analysis of the voltage pipeline-to-earth indicated a maximum value of U PE = 18.1 V/kA which was obtained by superposition of the result from each section. The voltage U PE along the exposure length and a further 3 km outside the exposure section is outlined in Figure 12.8. Short-circuit current calculation for the 400-kV-system under investigation indicated that the single-phase short-circuit current will always give the maximal asymmetrical short-circuit current. In order to cover future increase of short-circuit level, the maximal permissible short-circuit current in the system Ik = 40 kA was taken as a basis for the assessment of interference problems. The voltage 264 Short-circuit currents 9.15 m–9.33 m 12.6 m 5.6 m 58.0 m 12.6 m 7.0 m 6.45 m 25.8 m 0.4 m 27–140–120 m Figure 12.6 Elevation plan of the overhead transmission tower and the pipeline pipeline-to-earth will reach U PE = 724 V in this case. With respect to [21] the voltage pipeline-to-earth will be below the maximal permissible voltage which is U PEmax = 1000 V. If ASME/IEEE-standard No. 80 is applied (50 kg body weight and fault duration 150 ms) the voltage pipeline-to-earth will be above the maximal permissible voltage U t50 ≈ UPEmax = 350 V. Earthing at intermediate locations especially at the location where the voltage pipeline-to-earth is maximal must be done in order to reduce the voltage. More details on this example can be found in [27]. 12.3.2 Calculation of earthing resistances The resistance of an earthing grid within a switchyard of 80 m × 110 m; grid width 10 m × 10 m; ρ = 100 m is REI ≈ ρ 100 m 100 m ρ + + = 0.532  = 2∗D ltot 2 ∗ 105.9 m 1950 m Special problems related to short-circuit currents 265 (a) 160 Electric field strength in V/(km*kA) 140 120 100 80 60 40 20 0 2 3 4 5 6 7 Tower no. 2 3 4 5 6 8 9 10 11 8 9 10 11 (b) 350 Induced voltage in V/kA 300 250 200 150 100 50 0 Figure 12.7 7 Tow er no. Specific electric field strength (a) and specific induced voltage (b) of the pipeline between towers 2 and 11 Effective length   4b ∗ l 4 ∗ 80 m ∗ 110 m D= = = 105.9 m π π Total length of the earthing grid ltot = 9 ∗ 110 m + 12 ∗ 80 m = 1950 m. If the grid width is reduced to 5 m × 5 m, the total length of the earthing grid is ltot = 3550 m. The resistance of the earthing grid is REI = 0.5 m. The same earthing grid (80 m × 110 m; grid width 10 m × 10 m) is now examined, except that the soil resistivity is assumed to be in two layers, the surface layer with a thickness D1 = 4 m with ρ1 = 400 m and the deeper layer with ρ2 = 600 m. 266 Short-circuit currents 20 18 Voltage pipeline to earth (V/kA) 16 14 12 10 8 6 4 2 0 0 400 800 1200 1600 2000 2400 2800 3200 3600 4000 4400 4800 5200 5600 6000 6400 Exposure length (m) Figure 12.8 Voltage pipeline-to-earth along the exposure length (0–6400 m) The earthing resistance is ρ 1 ∗ D1 400 m 100 m ∗ 4 m ρ2 + = + = 1.93  2∗D b∗l 2 ∗ 105.9 m 80 m ∗ 110 m The resistance of an earthing with five deep-ground rods of length l = 15 m; diameter d = 20 mm; distance a = 30 m; ρ = 100 m is given by REI ≈ 1 ρ 4l 1 100 m 4 ∗ 15 m ∗ ∗ ln = 1.2 ∗ ∗ ∗ ln = 2.04  n 2π ∗ l d 5 2π ∗ 15 m 0.02 m whereas the earthing impedance of one rod is REI ≈ k ∗ 4l 100 m 4 ∗ 15 m ρ ∗ ln = ∗ ln = 8.5  2π ∗ l d 2π ∗ 15 m 0.02 m The earthing impedance of a surface electrode with length l = 60 m; diameter d = 4 mm; ρ = 100 m is REI = REI = ρ 2l 100 m 2 ∗ 60 m ∗ ln = ∗ ln = 5.47  πl d π 60 m 0.004 Chapter 13 Data of equipment 13.1 Three-phase a.c. equipment A summary of relevant data of equipment is given in IEC 60909-2:1992. The data are based on a survey carried out by IEC TC 73. In some countries this document does not have the character of a standard. 13.1.1 System feeders Impedances of power system feeders, respectively, their initial short-circuit power are difficult to determine as typical values, the structure of the power systems (cable or overhead line system), the voltage levels or the application task, i.e., for rural, urban or industrial power supply can vary in a wide range. Typical ranges of the initial short-circuit power (three-phase short-circuit) are given in Figure 13.1 for a power system with different voltage levels. 13.1.2 Transformers Transformers are constructed with defined rated power with respect to their application. In low-voltage and to a certain extent in medium-voltage systems, transformers are build with standard rated power and standard impedance voltage. Transformers in high-voltage systems, sometimes also in medium-voltage systems, have to meet special application conditions, such as the internal standard of the utility with special defined values for rated power, impedance voltage and ohmic losses. It should be noted in this respect that the minimisation of the impedance voltage is limited by the minimal insulation thickness of the windings. Typical values for the impedance voltage of transformers are outlined in Figure 13.2. Figure 13.3 gives data for the short-circuit losses (ohmic losses). The relation of the impedance voltage (%-value) 268 Short-circuit currents GS 3~ 250–1300 MVA S k⬙ = 20–50 GVA 380 kV GS 3~ 50–600 MVA Sr = 630–1000 MVA uk = 10–16% 220 kV and 110 kV GS 3~ S k⬙ = 2–5 GVA < 60 MVA Sr = 12.5–63 MVA uk = 11–20% S ⬙k = 100–500 MVA 10–30 kV 0.4 kV Figure 13.1 Sr = 50–630 kVA uk = 4% Sr = 630–2.5 MVA uk = 6% S k⬙ = 2–5 MVA < 1 MVA GS 3~ Principal structure of a power supply system and typical values of initial short-circuit power of public supply system [7] to the rated power (MVA-value) as per IEC 60909-2:1992 is given below: ukr = 8 + 0.92 ∗ ln(SrT ) (13.1) Further data are included in Table 13.1. The impedance voltage of auto-transformers is lower than that of full-winding transformers. Data of equipment 269 % 18 UrOS = 110 kV 16 14 12 UrOS > 220 kV 10 uk 8 2 6 1 4 UrOS < 30 kV Low-voltage transformers 2 0 0 1 10 100 1000 MVA SrT Figure 13.2 Typical values for the impedance voltage of two-winding transformers 300 250 Losses (kW) 200 150 No-load losses type a No-load losses type b Short-circuit losses type a 100 Short-circuit losses type b 50 0 0 Figure 13.3 10 20 30 40 50 60 Rated power (MVA) 70 80 90 Typical values for the ohmic losses, no-load losses and no-load current of two-winding transformers 270 Short-circuit currents Table 13.1 Data of transformers Voltage levels Sr (MVA) MV/LV Un < 1 kV 0.05–0.63 0.63–2.5 4 6 2.5–25 6–9 25–63 10–16 MV/MV Un = 1–66 kV HV/MV Un > 66 kV ukr (%) uRr (%) 1–2 1–1.5 0.7–1 0.6–0.8 The ratio of positive to negative sequence impedance of transformers depends on the vector group and is typically in the range of Vector group YNd Vector group Yzn Vector group Yyn (three-limb core) Vector group Yyn (five limb core and three single-phase transformers) Vector group YNynd 13.1.3 X0 /X1 ≈ 0.8–1.0 X0 /X1 ≈ 0.1 X0 /X1 ≈ 3.0–10.0 X0 /X1 ≈ 10.0–100.0 X0 /X1 ≈ 1.5–3.2 Generators The parameters such as rated power, rated voltage, power factor and subtransient reactance and synchronous reactance are needed to calculate the impedance of generators and by this the contribution to the short-circuit current. Rated voltages within one power range may vary depending on the construction type of the generator. The subtransient reactance of synchronous generators is typically in the range of 10–30 per cent depending on the rated power as mentioned in IEC 60909-2. The synchronous reactance is between 100 and 300 per cent, whereas salient pole generators normally have lower values than turbo generators. Typical values are summarised in Table 13.2. Power factor of generators with rated power below 20 MVA is approximately cos ϕr = 0.8 and increases for high rated machines (>1000 MVA) to cos ϕr = 0.85 on average. The ratio of saturated to unsaturated reactance xdsat /xd is between 0.8 and 0.9, whereas in the case of rated power below 100 MVA, the ratio can be between 0.65 and 1.0. Zero-sequence reactance of synchronous generators are x0 ≈ (0.4–0.8)xd depending on the winding arrangement. Data of equipment 271 Table 13.2 Typical data of synchronous generators (average values) Rated power SrG (MVA) Below 4 4–20 20–200 Above 200 Synchronous motors 13.1.4 Rated voltage UrG (kV) Subtransient reactance xd (%) 0.48–11.5 2.2–13.8 6–22 20–27 Up to 11.5 10–25 8–16 10–20 18–30 12–25 Synchronous reactance xd (%) 110–170–230 120–180–210 160–205–260 220–230–240 Overhead lines Impedances of overhead lines depend on the geometrical arrangement of phase conductors, on the tower outline and on the number and type of conductors. The zerosequence impedance furthermore depends on the earth resistivity, on the arrangement of earth conductors and on the design of the earthing system, including conductive installations in earth, respectively, connected to earth, e.g., pipelines, counterpoise and cable sheaths. The calculation of impedances of overhead lines in the positivesequence and the zero-sequence component are outlined below based on the tower outline as per Figure 13.4. The equations are valid for overhead lines which are symmetrically constructed and operated. All circuits are assumed to be in operation except as noted. (a) (b) E B E b B Y r R Figure 13.4 y System b Y R System a Tower outline of high-voltage transmission lines. (a) Single-circuit line and (b) double-circuit line 272 Short-circuit currents The distances between phase wires RYB are named dRY , dYB and dBR for the single-circuit line (and similar for the double-circuit line) and the average distances for the calculation of impedances are D= 3 dRY dYB dBR (13.2a) DmRy = 3 dRy dYb dBr (13.2b) DmRr = 3 dRr dYy dBb (13.2c) 3 Dab = DaE = 3 dRr dYy dBb ∗ 3 (13.2d) dRy dRb dYb (13.2e) dRq dYq dBq Bundle-conductors of n conductors with radius r in a circular arrangement on the radius rT must be represented by an equivalent radius rB rB = n nr ∗ rTn−1 (13.3) The impedance in the positive-sequence component is calculated for a single-circuit line (μ0 = 4π 10−4 H/km)  R μ0 D 1 ln (13.4) + Z 1I = 1 + j ω n 2π rB 4n The impedance of the double-circuit line is  R D ∗ DmRy μ0 1 ln + Z 1II = 1 + j ω n 2π rB ∗ DmRr 4n (13.5) The calculation of the impedance of the zero-sequence component has to take account of the earth conductor. The impedance of the zero-sequence component of a single-circuit line without earth conductor is given by Z 0I = R1 μ0 μ0 + 3ω + jω n 8 2π 3 ∗ ln δ 3 rB D2 + 1 4n (13.6a) and for operation with one earth conductor (index E) Z 0IE = R1 μ0 μ0 + 3ω + jω n 8 2π 3 ∗ ln δ 3 rB D 2 + 1 4n −3 (Z aE )2 Z E (13.6b) The loop-impedance Z E of the arrangement earth conductor and earth return, see Equation (12.13), is  μ0 μr μ0 δ Z E = RE + ω + + jω ln (13.7a) 8 2π rE 4 Data of equipment 273 The coupling impedance Z aq of phase conductor and earth conductor (see Equation (12.11), where Z aE is named Z LE2 ) Z aE = ω μ0 μ0 δ + jω ∗ ln 8 2π DaE (13.7b) The distance Daq is given by Equation (13.2e) and the depth δ of the earth return path (see Equation (12.2)) is 1.85 δ=√ μ0 (ω/ρ) (13.8) The resistivity of the soil ρ is between 30 m (Swamp soil) and 3000 m (Stony soil) as outlined in Table 12.2. The impedance of the zero-sequence component of a double-circuit overhead line without earth conductor is given by Z 0II = R1 μ0 μ0 + 3ω + jω n 8 2π 3 ∗ ln δ 3 rB D2 + 1 4n + 3Z ab (13.9a) and in the case of operation with earth conductor Z 0IIE = R1 μ0 μ0 + 3ω + jω n 8 2π 3 ∗ ln δ 3 rB D 2 + 1 4n + 3Z ab − 6 (Z aE )2 Z E (13.9b) where Z aE is the coupling impedance of phase conductor and earth conductor according to Equation (13.7b), Z E is the impedance of the loop phase conductor and earth return according to Equation (13.7a) and Z ab is the coupling impedance between the systems a and b according to Equation (13.10). Z ab = ω μ0 μ0 δ + jω ∗ ln 8 2π Dab (13.10) The relative permeability μr relevant for overhead lines is Conductors from Cu or Al Conductors from Al/St, cross-section ratio > 6 Conductors from Al/St, one layer of Al only Conductors from Steel (St) μr μr μr μr =1 ≈1 ≈ 5–10 ≈ 25 Typical values for the impedances of MV-overhead lines are summarised in Table 13.3. Table 13.4 shows the impedances of HV-overhead lines. 274 Short-circuit currents Table 13.3 Table 13.4 Typical values of impedance of the positive-sequence component of MV-overhead lines Conductor Un (kV) Resistance (/km) Reactance (/km) 50 Al 50 Cu 50 Cu 70 Cu 70 Al 95 Al 150/25 Al/St 2 ∗ 240/40 Al/St 4 ∗ 240/40 Al/St 10–20 10–20 10–20 10–30 10–20 20–30 110 220 380 0.579 0.365 0.365 0.217 0.439 0.378 0.192 0.06 0.03 0.355 0.355 0.423 0.417 0.345 0.368 0.398 0.3 0.26 Typical values of impedances of the positive- and zero-sequence component of HV-overhead lines (ρE = 100 m) Conductor Earth wire AlSt 240/40 Al/St 2 ∗ 240/40 Al/St 4 ∗ 240/40 St 50 Al/St 44/32 Al/St 240/40 Al/St 44/32 Al/St 240/40 Al/St 240/40 Al/St 240/40 Un (kV) Positive-sequence impedance (/km) 110 0.12 + j 0.39 220 0.12 + j 0.42 400 0.06 + j 0.3 0.03 + j 0.26 Zero-sequence impedance (/km) One circuit Two circuits 0.31 + j 1.38 0.32 + j 1.26 0.22 + j 1.1 0.3 + j 1.19 0.22 + j 1.1 0.16 + j 0.98 0.13 + j 0.091 0.5 + j 2.2 0.52 + j 1.86 0.33 + j 1.64 0.49 + j 1.78 0.32 + j 1.61 0.26 + j 1.49 0.24 + j 1.39 A detailed list of impedances of overhead lines of different voltage levels is given in IEC 60909-2:1992. The capacitances of overhead lines are only needed for special problems, i.e., in case of isolated neutral or if the system is operated with resonance earthing (see Chapter 5), or in case of double-circuit faults. The capacitance of the positivesequence component for single-circuit line is given by (ε0 = 8.854 ∗ 10−12 F/m)  = C1I 2π ε0 ln(D/rB ) (13.11a) Data of equipment 275 The capacitance of the positive-sequence component for a double-circuit line is given by 2πε0 ln(DDmRy /rB DmRr )  = C1II (13.11b) Similar to the calculation of the impedance of the zero-sequence component, the earth conductor has to be considered for the calculation of capacitances of the zerosequence component. In the case of operation without earth conductor the capacitance of the single-circuit line is calculated by  C0I = 2πε0 (13.12a) 3 ∗ ln(2h/ 3 rB D 2 )  = C0IE √ 3 3 ∗ (ln(2h/ r B 2πε0 2 D ) − (ln((h + h 2 q )/Daq )) / ln(2hq /rq )) (13.12b) The capacitances of the double-circuit line are calculated by  C0II = 4h2  3 ∗ ln 2h ∗   = 2π ε0 / 3 ∗ ln C0IIE 2h ∗ 3 2πε0  3 / rB D 2 ∗ 2 + DmRy 2 4h2 + DmRy rB D 2 ∗ 3 2 DmRr DmRy 3 2 DmRr DmRy −2 (13.13a)  (ln ((h + hE )/DaE ))2 ln(2hE /rE ) (13.13b) To take account of the conductor sag, the average height h of the conductor is used h= 3 hR hY hB = 3 hr hy hb (13.14) The influence of the tower on the capacitance in the zero-sequence component is considered by an increase of 6 per cent (overhead lines with nominal voltage 400 kV), up to 10 per cent (overhead lines with nominal voltage 60 kV). It should be observed that the capacitance in the positive-sequence component is given by C1 = 3CL + CE (13.15a) 276 Short-circuit currents and the capacitance in the zero-sequence component is identical to the line-to-earth capacitance (see Section 13.2) (13.15b) C0 = CE 13.1.5 Cables Impedances of cables differ very much depending on the type and thickness of insulation, the cable construction, cross-section of conductor, screening, sheaths and armouring and on the type of cable laying, i.e., flat formation or triangle formation. Sheaths and armouring have especially in low voltage cables a strong influence on the impedance. The installation of other conductive installations, e.g., pipelines and screening, armouring and sheaths of other cables have a strong influence on the zerosequence impedance, which therefore can only be given for simple arrangements. Reference is made to [1], [2], [8], [9] and to data-sheets of manufacturers. Due to the high permittivity εr of the insulation and the small distance between phase conductor and sheeth, identical to earth potential, the capacitances of cables are significantly higher as compared with overhead lines. Figures 13.5 and 13.6 indicate values for the capacitances and the capacitive loading currents of MV- and HV-cables. Figure 13.7 indicates typical values of reactances (positive-sequence system) of cables of different construction. mF/km 1.0 0.9 1 0.8 4 0.7 3 2 0.6 5 C⬘1 0.5 0.4 6 0.3 0.2 0.1 10 Figure 13.5 15 25 35 50 70 95 120 185 q Capacitances MV-cables (Un < 20 kV ) 1) Mass-impregnated cable NKBA 1kV 3) Three-core cable NEKEBY 10 kV 5) VPE-cable N2XSEY 10 kV 300 500 mm2 2) Mass-impregnated cable NKBA 6/10 kV 4) PVC-cable NYSEY 10 kV 6) VPE-cable N2XSEYBY 20 kV Data of equipment 277 (a) mF/km 0.6 (b) A/km 14 0.5 10 8 7 6 5 4 I⬘C 3 0.4 C⬘1 0.3 0.2 1 2 0.1 1 3 2 300 0 150 2 1400 mm 625 q Figure 13.6 4 4 3 0 150 2 300 625 1400 mm2 q Capacitances C1 (a) and capacitive loading current Ic (b) of HV-cables 1) Single-core oil-filled 2) single-core oil-filled cable 110 kV cable 220 kV 3) VPE-cable 110 kV 4) VPE-cable 220 kV Ω/km 0.20 7 9 0.18 6 8 0.16 3 0.14 5 4 X ⬘1 0.12 0.10 2 0.08 1 0.06 10 Figure 13.7 15 25 35 50 70 95 120 185 q 500 mm2 Reactance (positive-sequence system) of three-phase (Un ≤110 kV) 1) 0,6/1 kV, 4-conductor, NKBA 2) 0,6/1 kV, 4-conductor, NA2XY 3) Three-core cable with armouring 10 kV 4) PVC-cable NYFGby, 10 kV 5) VPE-cable NA2XSEY, 10 kV 6) Single-core oil-filled cable (triangle formation) 110 kV 7) Single-core oil-filled cable (flat formation) 110 kV 8) VPE-cable (triangle formation) 110 kV cables 278 Short-circuit currents 13.1.6 Reactors and resistors Short-circuit limiting reactors are constructed for all voltage levels, from low voltage up to 750 kV. The reactors are manufactured with oil-insulated windings and as air-insulated core-type reactors. Figure 13.8 shows a short-circuit limiting reactor (air-insulated core-type; 10 kV; 630 A; 6 per cent). Petersen-coils are constructed as reactor with fixed reactance, with tap-changer and with continuous controllable reactors. The control range normally is limited to 1 : 2.5 for tap-changer control and 1 : 10 for continuous control. Standards as per Figure 13.8 Arrangement of a short-circuit limiting reactor Source: Mohndruck Data of equipment 279 IEC 60289:1998 are applicable. The values as per below need to be specified: √ Rated voltage Ur (phase voltage) or Ur / 3 depending on application Rated current Ir (fixed reactance) or maximal current to be controlled Rated frequency 50 or 60 Hz; for traction systems other frequencies are used Operating method Continuous operation or short-time operation (e.g., 2 h or some minutes) Control range Minimal and maximal adjustable current Figure 13.9 shows a Petersen-coil adjustable in steps by tap-changer (oilinsulated). Earthing resistors are designed individually for the special applications. They are typically made from stainless steel, cast steel, NiO–Cr- or CuO–Ni-alloy. The maximal permissible temperature, the temperature coefficient and the assumed cost determine the selection of material. Stainless steel is an advantage compared with cast steel due to low temperature coefficient. Low-impedance resistors are mainly arranged from meandered wire elements, high-impedance resistors are arranged from Figure 13.9 √ Adjustable Petersen-coil 21 kV/ 3; 4 MVAr; Ir = 70.1–330 A; adjustable in 64 steps, 4.13 A each Source: SGB Starkstromgerätebau 280 Short-circuit currents steel plate grid or steel fabrics. Some characteristic parameters of resistor elements are given in Table 13.5. Rating and design of resistors are based on ANSI/IEEE 32:1972 and EN 60529, creeping distances are determined in accordance to IEC 60815, insulation must comply with IEC 60071 and high-voltage testing shall be carried out based on Table 13.5 Characteristic parameters of resistor elements Material CuNi 44 or NiCr 8020 Cast steel CrNi-alloy steel Arrangement Resistance at 20◦ C () Rated current (A) Thermal time constant (s) Temperature coefficient (K−1 ) Maximal temperature (◦ C) Wire elements 1500–0.5 <20 20–90 0.004 Cast element 0.2–0.01 25–125 240–600 0.075 400 Steel grid and fabric 0.75–0.04 25–250 120 0.05 760 Figure 13.10 Earthing resistor made from CrNi-alloy steel fabric for indoor installation 3810 , 5 A for 10 s, 170 kV BIL, IP 00 Source: Schniewindt KG Data of equipment 281 Figure 13.11 Earthing resistor made from meandering wire for outdoor installation 16 , 400 A for 10 s, 75 kV BIL, IP 20 Source: Schniewindt KG IEC 60060. Earthing resistors can be suitably designed for indoor and outdoor installations. Figures 13.10 and 13.11 show two different types of resistors. 13.1.7 Asynchronous motors Data of asynchronous motors are included in IEC 60781:1989 (mentioned as A in Table 13.6) , IEC 60909-2:1992, in [10] (mentioned as B in Table 13.6) and in IEC 60909-1:1991 (mentioned as C in Table 13.6). Table 13.6 outlines the relevant data of asynchronous motors for LV- and MV-application. 13.2 d.c. equipment Data of d.c. equipment are not documented in a similar way as for a.c. equipment. Literature also presents less information. All data listed hereafter are based on manufacturers’ data, information from calculation examples and incomplete data from literature. They should be used for preliminary information only. 13.2.1 Conductors Resistance of conductors in d.c. auxiliary installations is calculated from the crosssection of the cable or busbar and the material constant. The specific resistance of 282 Short-circuit currents Table 13.6 Data of asynchronous motors SrM (kVA) PrM (kW) UrM (kV) 14.9 24 24 11 18.5 18.5 20 22 22 30 40 45 50 55 75 160 0.38 0.38 0.38 0.4 0.38 0.38 0.38 0.4 0.38 0.41 0.38 0.38 0.38 29.5 29.5 40 57.8 69.6 90 191.5 IrM (A) 22.5 36.6 36.5 45 45 60.8 88 106 137 291 ηrM cos ϕrM IanM /IrM RS (m) I0 (A) 0.89 0.83 0.85 0.85 370 a 1002 236.7 9 0.89 0.93 8.5 6.0 6 6 0.9 0.9 0.93 0.92 0.94 0.92 0.94 0.95 0.83 0.84 0.85 0.85 0.84 0.86 0.88 0.88 6 6.5 6 6.7 6 1.3 6.8 6.3 SrM (MVA) PrM (MW) UrM (kV) IrM (A) 0.197 0.259 0.218 0.27 0.281 0.299 0.353 0.374 0.467 0.54 0.685 0.837 0.842 1.697 2.09 2.4 3.07 5.245 6.85 11.64 0.16 0.175 0.18 0.225 0.23 0.25 0.3 0.32 0.4 0.46 0.55 0.63 0.7 1.4 1.8 2.1 2.65 4.5 6 10 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 19 25 21 19 27 29 34 36 45 52 66 80.5 81 163 201 231 296 504 659 1120 ηrM cos ϕrM Pair of poles Ref. 13 2 2 2 a 813 160 91.67 16 22.6 3 3 2 50.34 31.0 2 36.67 22.97 7 38 43 74 2 2 2 B C B A C B B A B B B B B IanM / IrM RS () I0 (A) 5.7 a 30.39 a 32.2 a 28.94 a 22.97 a 21.38 0.94 0.89 5.3 0.955 0.89 5.33 0.95 0.94 0.85 0.8 5.3 5.2 0.948 0.968 0.971 0.96 0.975 0.973 0.977 0.87 0.89 0.9 0.9 0.88 0.9 0.88 5 5.2 5.1 5 4.7 5.5 4 a Motor impedance instead of resistance. 1830 6.6 720 11.8 0340 806.1 a 7.13 169 98 100 73.26 27.3 11 9 21.5 27.4 a 16.43 a 16.04 a 9.52 44 50 58.6 60 94 138 154 Pair of poles Ref. 1 6 2 2 1 1 1 1 2 1 3 6 3 2 3 2 1 2 2 2 C C C C C B C C B C B B C B B B B B B B Data of equipment 283 materials at temperature of 20◦ C shall be used in accordance with IEC 61660-3:2000 as given below: Copper Aluminium 1 mm2 54 m 1 mm2 ρ= 34 m ρ= Resistance for other temperatures has to be calculated as given in Table 3.12. Inductance of d.c. conductors installations depends on the arrangement of the conductors and can only be calculated for simple layout as mentioned in Table 3.12. 13.2.2 Capacitors Capacitors in d.c. auxiliary installations are installed up to some 10 mF for smoothing of the d.c. voltage. Typical values of the d.c. resistance and the a.c. resistance, respectively, are summarised together with other relevant data in Tables 13.7 and 13.8. According to information received from manufacturers, the inductance of capacitors is in the range of nano-Henry and can be neglected as compared with the inductance of the connecting cables. 13.2.3 Batteries The detailed data of batteries as requested in IEC 61660-1:1997 are not available from data sheets of manufacturers, as some data, such as voltage of loaded and unloaded Table 13.7 Typical values of MKP-capacitors; selfhealing dry insulation; different make of capacitor can and fuse Capacitor can Capacity (μF) Nominal voltage (V) Resistance (m) Rectangular 12.000 9.000 4.000 500 200 1250 1.600 490 250 900 1000 1900 900 1100 440 690 440 250 0.8 0.5 0.5 2.5 3 <2 <2 <7.5 <3 Round Prismatic (Internal fuse) Prismatic (External fuse) 284 Short-circuit currents Table 13.8 Table 13.9 Typical values of MKPcapacitors; resin insulation; round can Capacity (μF) Nominal voltage (V) Resistance (m) 500 1100 2000 500 750 1500 500 1000 1800 420 420 420 500 500 500 640 640 640 0.6 0.5 0.5 0.8 0.6 0.5 0.6 0.6 0.5 Resistance of loaded batteries (data from several manufacturers) 2-V-batteries Capacity RB ; manufacturer 1 RB ; manufacturer 2 12-V-batteries Capacity RB ; manufacturer 3 RB ; manufacturer 4 Ah 100 200 300 400 500 600 800 1000 2000 3000 m 0.9 0.8 0.75 0.7 0.65 0.63 0.6 0.55 0.5 0.45 m — 0.4 0.35 0.32 0.3 — 0.2 0.15 0.08 0.05 Ah 40 m 9.5 m 9.7 55 5.8 8.5 65 5.8 — 75 5.5 6.3 80 5.5 6.3 90 5.2 — 100 150 4.3 4.0 5 4.0 200 3.8 3.6 — — battery, depend on the layout and the operational requirements, e.g., required voltage tolerance and voltage drops of connecting cables, of the whole battery plant. A battery cell with UnB = 2.0 V is taken as an example. The voltage of the loaded battery is 2.23 V/cell, which is contrary to IEC 61660-1:1997 stating a value of EBge = 1.115 ∗ UnB instead of EBge = 1.05 ∗ UnB . When the minimal voltage at the consumer inside a 220-V-installation shall be not less than Umin = 0.9 ∗ Un the minimal permissible voltage at the battery plant is EBmin = 191.4 V taking account of a voltage drop of 3 per cent at the connecting circuits. It is therefore necessary to install 108 battery cells with a minimal voltage of EBun = 1.772 V/cell. If the minimal voltage shall be set to EBun = 1.833 V/cell as recommended by some manufacturers, only 105 cells need to be installed. The maximal voltage at the battery plant is EBge = 240.8 V (108 cells) and EBge = 234.2 V (105 cells), respectively. The number of cells and the minimal permissible voltage depend on the loading time of the battery, the required capacity and the discharge time and vice versa. Data of equipment 285 Values of the inductance of 12-V-batteries are in the range of LB = 1–10 μH and LBZ = 0.17–1.7 μH/cell, respectively [11]. These values are in the same range as inductances of conductors and cannot be neglected. Values of the internal resistance of batteries are in the range of RB = 0.05– 70 m/cell. Batteries with high capacity have small value of resistance and batteries with low capacity have high value of resistance. Typical values are outlined in Table 13.9. The values of the resistance differ very much especially for 2-V-batteries. It should be noted, that batteries with very low internal resistance are made from lead-grid cathode and grid-anodes, and batteries with high internal resistance are made from grid-anodes and lead-sheaths cathode sometimes also with additional stretched copper grid. Symbols, superscripts and subscripts A detailed explanation of the quantities and symbols is included in the text for each equation, table and figure. It cannot be avoided that some symbols and subscripts are used for different physical quantities. It should be noted that e.g., using the symbol ‘J’ for the current density cannot be mixed up with the symbol ‘J’ for the second mechanical moment, as both symbols will not occur in the same equations and even not in a similar context. Symbols for quantities A C D E E E F G I J K L M P Q Q R S T U X Y Aperiodic current Capacitance Geometric mean distance, geometric factor Young’s modulus Matrix of unity Voltage Mechanical force Conductance Current Current density Factor Inductance Mutual impedance Active power Reactive power Thermal heat Resistance Apparent power Total time, time constant Voltage Reactance Admittance 288 Symbols, superscripts and subscripts Z Z a a; a 2 c d d f h k l; l m n p q q q r r s t t v w α ε τ ω ϕ ρ μ μ λ κ δ δ δ γ γ σ Impedance Section moduli Distance Complex operational phasor Voltage factor Distance, diameter Damping factor Frequency Conductor height Factor Length Mass Number Control range Cross-section Factor of plasticity Factor Radius Reduction factor Conductor sag Time instant Transformation ratio Detuning factor Probability factor Temperature & permittivity coefficient Permittivity Time constant Angular frequency Phase angle Resistivity Factor according to IEC 60909 Permeability Factor according to IEC 60909 Factor according to IEC 60909 Earth-fault factor (a.c.) Decay coefficient (d.c.) Depth of earth return path Impedance angle Propagation constant Mechanical stress Quantities (Example U) U U Capital letter used for r.m.s-value Underlined capital letter indicates phasor (vector) Symbols, superscripts and subscripts 289 Û |U | u u u(t) Ū U U Peak value Complex value %/ MVA-value Instantaneous value Time course Average value Vector (matrix) Complex vector (matrix) Superscripts (Example U) U∗ u U U  Conjugate–complex value p.u.-value Transient value Subtransient value Order of subscripts (Example U) First order Next order Next order Next order Next order Next order UYbTmaxi Component (R, Y, B or 0, 1, 2) UY Type of operation (n; r; b) UYb Indication of equipment UYbT Number of equipment UYbT4 Special condition UYbTmax Index UYbTmaxi Indicates voltage of phase Y before short-circuit, equipment is T ransformer number 4 maximal value for alternative i In most of the cases, positive-sequence system is used without subscript ‘1’ Subscripts, components, systems 0; 1; 2 Zero-, positive-, negative-sequence systems ac a.c. system dc d.c. system R; Y; B Phases of three-phase a.c. system Subscripts, type of operation 0 an b b e No-load value, eigenvalue Locked rotor, starting Before (prior to) fault, beginning Breaking End 290 Symbols, superscripts and subscripts k Short-circuit value k1 Single-phase short-circuit k2 Double-phase short-circuit k3 Three-phase short-circuit m Highest value (IEC 60038) n Nominal value r Rated value s; sat Saturated value δ At temperature δ Subscripts, indication of equipment B B Br C D E F G J KW L M M N P Q R S T To X Y Z Battery Counterpoise Branch Capacitor Reactor, rectifier Earth, earth wire Field Generator Joint for connection Power station Line; load Motor Mutual value Network (a.c. system) Pipeline System feeder Resistance Special earthing impedance Transformer Overhead-line tower Reactance Common branch (d.c. system) Battery cell Subscripts, special conditions 20 Value at 20◦ C f Fictitious ge Loaded max Maximal value min Minimal value Symbols, superscripts and subscripts 291 o res s th tot un Without tap-changer Residual With tap-changer Thermal Total Unloaded Other subscripts 0; 1 1; 2; 3 a; b; c B c d HV; MV; LV I i; j Mec m p q res s U W I II Condition at beginning or ending respectively Different sides of a transformer Index Base or reference Equivalent Direct axis High-, medium-, low-voltage side of a transformer Current Index Mechanical Main conductor Pole pair Quadrature axis Equivalent resistance Subconductor Voltage Characteristic impedance One circuit in operation Two circuits in operation References 1 Schlabbach, J.: Electrical power system engineering (Elektroenergieversorgung). 2nd revised edition, VDE-Verlag. Berlin, Offenbach/Germany, 2003. ISBN 3-8007-2662-9. 2 Oeding, D. and Oswald, B.: Electrical systems and power stations (Elektrische Kraftwerke und Netze). 6th edition, Springer-Verlag. Berlin, Heidelberg, New York, 2004. ISBN 3-5400-0863-2. 3 Schlabbach, J.: Neutral handling (Sternpunktbehandlung). Systems engineering, Vol. 15. VWEW-Energieverlag, Frankfurt/Germany, 2002. ISBN 3-8022-0677-0. 4 CCITT: Directives CCITT, Vol. V, Chapter 5. ITU, Geneva/Switzerland. 5 Niemand, T. and Kunz, H.: Earthing in power systems (Erdungsanlagen). Systems engineering, Vol. 6. VWEW-Energieverlag, Frankfurt/Germany, 1996. ISBN 3-8022-0362-3. 6 Arbitration agency of VDEW: Technical recommendation No. 1 – Induced voltages in telecommunication circuits. VWEW-Energieverlag, Frankfurt/Germany, 1987. 7 Schlabbach, J., Blume, D., and Stephanblome, T.: Voltage quality in electrical power systems. Power and Energy Series, No. 36. IEE-publishers, Stevenage, UK, 2001. ISBN 0-85296-975-9. 8 ABB: Switchgear Manual. 9th edition, Cornelsen-Girardet, Essen/Germany, 1993. ISBN 3-464-48234-0. 9 VDEW: Cable-book (Kabelhandbuch). 6th edition, VWEW-Energieverlag, Frankfurt/Germany, 2001. ISBN 3-8022-0665-7. 10 Scheifele, J.: Contribution of asynchronous motors to short-circuit currents (Beitrag von Drehstrom-Asynchronmotoren zum Kurzschlussstrom). Ph.D. thesis, Technical University of Darmstadt/Germany, 1984. 11 Gretsch, R.: Design of electrical installations in automobiles (Ein Beitrag zur Gestaltung der elektrischen Anlage in Kraftfahrzeugen). Dr. -Ing. habil. thesis, University Erlangen-Nürnberg/Germany, 1979. 12 VDEW: Distributed generation in LV-systems (Eigenerzeugungsanlagen am Niederspannungsnetz). 4th edition, VWEW-Energieverlag, Frankfurt/Germany, 2001. ISBN 3-8022-0790-4. 294 References 13 Balzer, G., Nelles, D., and Tuttas, C.: Short-circuit current calculation acc. VDE 0102 (Kurzschlußstromberechnung nach VDE 0102). VDE-technical reports, Vol. 77. VDE-Verlag, Berlin, Offenbach/Germany, 2001. ISBN 3-8007-2101-5. 14 Pistora, G.: Calculation of short-circuit currents and voltage drop (Berechnung von Kurzschlussströmen und Spannungsfällen). VDE-technical reports, Vol. 118. VDE-Verlag, Berlin, Offenbach/Germany, 2004. ISBN 3-8007-2640-8. 15 Gröber, H. and Komurka, J.: Transformation of zero-sequence voltage through transformers (Übertragung der Nullspannung bei zweiseitig geerdeten Transformatoren). Technical report of FGH, Mannheim/Germany, 1973. 16 Balzer, G.: Double-side earthing of transformers (Beidseitige Sternpunktbehandlung von Transformatoren). In VDE: Neutral handling in 10-kV- to 110-kV-system. ETG-Report, Vol. 24. VDE-Verlag, Berlin, Offenbach/Germany, 1988, pp. 172–187. 17 SPEZIELEKTRA: Resonant earthing controller EZR2 (Erdschlußkompensationsregler EZR2). Operation manual N 9/4.88, Spezielektra, Linz/Austria, 1988. 18 Schäfer, D., Schlabbach, J., Gehrmann, A., and Kroll, R.: Increase of displacement voltage in MV cable systems with resonant earthing (Erhöhung der Verlagerungsspannung in Mittelspannungs-Kabelnetzen mit Erdschlußkompensation). Elektrizitätswirtschaft, Vol. 93 (1994), VWEW-Energieverlag, Frankfurt/ Germany, pp. 1295–1298. 19 Fiernkranz, K.: MV-systems with isolated neutrals or resonant earthing (Mittelspannungsnetze mit isoliertem Sternpunkt oder Erdschlußkompensation). ETG-Report, Vol. 24. VDE-Verlag, Berlin, Offenbach/Germany, 1988. 20 Kouteynikoff, P. and Sforzini, A.: Results of an international survey of the rules limiting interference coupled into metallic pipes. CIGRE Committee 36. ELECTRA, Geneva, Switzerland, 1986. 21 Arbitration agency of VDEW: Technical recommendation No. 3 – Measures for construction of pipelines in the vicinity of HV/AC three-phase installations (German). VWEW-Energieverlag, Frankfurt/Germany, 1982. 22 Arbitration agency of VDEW: Technical recommendation No. 5 – Principles of calculation and measurement of reduction factor of pipelines and earth wires (German). VWEW-Energieverlag, Frankfurt/Germany, 1980. 23 Arbitration agency of VDEW: Technical recommendation No. 7 – Measures for the installation and operation of pipelines in the vicinity of three-phase high-voltage installations (German). VWEW-Energieverlag, Frankfurt/Germany, 1985. 24 IEC 60479-1: Effects of currents passing through the human body. International electrotechnical commission, Geneva, Switzerland, 1994. 25 Jenkins, N., Allan, R., Crossley, P., Kirschen, D., and Strbaq, G.: Embedded generation. Power and Energy Series, No. 31. IEE Publishers, Stevenage, UK, 2000. ISBN 0-85296-774-8. 26 Schlabbach, J. (Ed.) and Metz, D.: Power system engineering (Netzsystemtechnik). VDE-Verlag, Berlin, Offenbach/Germany, 2005. ISBN 3-8007-2821-4. References 295 27 Schlabbach, J.: Short-time interference of pipelines. Report on research and development No. 14. University of Applied Sciences, Bielefeld/Germany, 2000. ISBN 3-923216-52-1. 28 Cory, B. and Weedy, B.: Electrical power systems. 4th edition. John Wiley & Sons Ltd., Chichester, England, 1998. ISBN 0-471-91659-5. 29 Funk, G.: System of symmetrical components (Symmetrische Komponenten). Elitera-Verlag, Berlin, Germany, 1976. ISBN 3-8708-7087-7. 30 Kories, R. and Schmidt-Walter, H.: Electrotechnical handbook (Taschenbuch der Eletrotechnik). 6th revised edition, Verlag Harri Deutsch, Frankfurt/Germany, 2004. ISBN 3-8171-1734-5. 31 Metz, D., Naundorf, U., and Schlabbach, J.: Handbook of electrotechnical equations (Kleine Formelsammlung Elektrotechnik). 4th edition, Fachbuchverlag Leipzig, Germany, 2003. ISBN 3-446-22545-5. 32 Wildi, T.: Units and conversion charts. IEEE Press, New York, USA, 1990. ISBN 0-87942-273-4. 33 Oeding, D. and Schünemann, H.: Calculation of short-circuit currents in HV-systems using %/MVA-system (Berechnung der Kurzschlussströme in Hochspannungsnetzen mit %/MVA-system). BBC-News, Mannheim/Germany, 1965. 34 Koglin, H.: The decaying d.c. component of short-circuit currents (Der anklingende Gleichstrom beim Kurzschluss in Elektroenergieversorgungsnetzen). Ph.D. thesis, University of Darmstadt/Germany, 1971. 35 Pitz, V. and Waider, G.: Impedance correction factors of network transformers for short-circuit current calculation (Impedanzkorrekturfaktoren für Netztransformatoren bei der Kurzschlussstromberechnung). Elektrie 47 (1993), pp. 301–304. 36 Scheifele, J. and Waider, G.: Maximal short-circuit currents through linear optimisation (maximale Kurzschlussströme durch lineare Optimierung). etzArchiv 10 (1998), pp. 275–280. 37 Oeding, D. and Waider, G.: Maximal partial short-circuit currents of power stations (Maximale Teilkurzschlussströme von Kraftwerksblöcken ohne Stufenschalter). etzArchiv 10 (1988), pp. 173–180. 38 Balzer, G. and Deter, O.: Calculation of thermal effects of equipment due to short-circuit currents (Berechnung der thermischen Kurzschlussbeanspruchung von Starkstromanlagen). etzArchiv 7 (1985), pp. 287–290. 39 Tuttas, C.: Approximation of reduction factors of complex conductor arrangement (Berechnung des Reduktionsfaktors komplizierter Leiteranordnungen). AEG-report 54, Frankfurt, Germany, 1981, pp. 153–157. 40 Hosemann, G., Nietsch, C., and Tsanakas, D.: Short-circuit stress in d.c. auxiliary systems. Cigre-report 23-104, Geneva, Switzerland, 1992. 41 Tsanakas, D.: Substitution function for the calculation of mechanical and thermal stress due to short-circuits in d.c. installations (Ersatzfunktion für die Bestimmung der mechanischen und thermischen Kurzschlussbeanspruchung in Gleichstromanlagen). etzArchiv 10 (1988), pp. 355–360. 296 References 42 Nietsch, C.: Calculation of short-circuit currents in d.c. installations. University of Erlangen/Germany, EV-report F254, 1989. 43 Tsanakas, D., Meyer, W., and Safigianni, A.: Dynamical short-circuit stress in d.c. installations (Dynamische Kurzschlussbeanspruchung in Gleichstromanlagen). Archiv für Eletrotechnik 74 (1991), pp. 305–313. 44 Tsanakas, D. and Papadias, A.: Influence of short-circuit duration on dynamic stresses in substations. IEEE Transactions PAS 102 (1983), pp. 492–501. 45 Hosemann, G. and Tsanakas, D.: Dynamic short-circuit stress of busbar structures with stiff conductor. Parametric studies and conclusions. Electra 68, Geneva, Switzerland, 1980, pp. 37–64. 46 Meyer, W.: Additional calculation acc. IEC 60865-1 for the determination of short-circuit stress of lines (Ergänzung des Berechnungsverfahrens nach IEC 60865-1 zur Ermittlung der Kurzschlussbeanspruchung von Leitungsseilen mit Schlaufen im Spannfeld). EE-report, University of Erlangen/Germany, 2002. 47 Meyer, W.: Mechanical short-circuit stress of rigid conductors in IEC 865-1 – Information on the norm (Mechanische Kurzschlussbeanspruchung von biegesteifen Leitern in IEC 865-1 – Hintergründe zur Norm). EE-report, University of Erlangen/Germany, 2002. 48 Tsanakas, D.: Dynamic stress in high-voltage structures by short-circuits of short-duration. CIGRE-Symposium High currents in power systems. Proc. Report 500-01, Brussels, Belgium, 1985. 49 Rüger, W. and Hosemann, G.: Mechanical short-circuit effects of single-core cables. IEEE Trans. PD, 4 (1989) pp. 68–74. 50 Nietsch, C. and Tsanakas, D.: Short-circuit currents in d.c. auxiliary installations (Kurzschlussströme in Gleichstrom-Eigenbedarfsanlagen). Elektrie 46 (1992), pp. 18–22. 51 Hosemann, C., Zeitler, E., Miri, A., and Stein, N.: The behaviour of droppers in HV substations under short-circuit. Proceedings of the 5th International symposium on short-circuit currents in power systems. Proc. Report 3.2, Zlin, Czech Republic, 1992. 52 Tsanakas, D., Meyer, W., and Nietsch, C.: Short-circuit currents of motors in d.c. auxiliary installations in power plants and substations. Electromotion ’99, Patras/Greece, pp. 489–496. 53 Stein, N., Meyer, W., and Miri, A.: Test and calculation of short-circuit forces and displacements in HV substations with strained conductors and droppers. ETEP 10 (2000), pp. 131–138. 54 Herold, G. and Kunz, M.: Fast analytical short-circuit current calculation of rectifier fed auxiliary subsystems. ETEP 13 (2003), pp. 151–159. 55 Pitz, V., Köster, H.-J., et al.: Short-circuit mechanical effects on outdoor HV substations with wide bundling. CIGRE-Session 2004. Proc. Report B3-107, Paris, France. 56 Wessnigk, K. and Griesbach, P.: Digital calculation of short-circuit current in battery-fed d.c. installations (Digitale Berechnung des zeitlichen Kurzschlussstromverlaufs in batteriegespeisten Gleichstromnetzen). Elektrie 43 (1989), pp. 379–381. References 297 57 Albert, K., Apelt, O., Bär, G., and Koglin, H.-J. (Ed.): Electrical power supply (Elektrischer Eigenbedarf). VDE-Verlag, Berlin, Offenbach/Germany, 1993. ISBN 3-8007-1586-4. IEC-standards, EN-norms and other standards and norms mentioned within the context of this book are listed in Tables 1.1 and 1.2. Extracts from the norms DIN EN 60909-0 (VDE 0102) and DIN EN 61660-1 (VDE 0102 part 10) are permitted for this edition of the book by licensee agreement 392.004 of DIN (Deutsches Institut für Normung e.V.) and VDE (Verband der Elektrotechnik Elektronik Informationstechnik e.V.) on 16.12.2004. An additional permission is required for other usages and editions. Standards are only to be applied based on their actual issues, available from VDE-Verlag GmbH, Bismarckstr. 33, D-10625 Berlin, Beuth-Verlag GmbH, Burggrafenstr. 6, D-10787 Berlin or the national standard organisation. English versions of the norms are also available through BSI in London/UK. The English text of this book was neither checked by DIN (Deutsches Institut für Normung e.V., Berlin) nor by VDE (Verband der Elektrotechnik Elektronik Informationstechnik e.V., Frankfurt). Index %/MVA system semirelative units 33–4 conversion of quantities with p.u. and ohm systems 35 example 40 correction factor 34 HV three-phase examples 93 impedance based on measurement example 41–2 impedance calculations for a three-winding transformer 37–40 impedance results of various equipment 91 impedances calculation HV three-phase example 92 a.c. systems, impedance: see impedance calculations for a.c. equipment a.c. systems, mechanical effects: see conductors, a.c., mechanical effects of short circuits a.c. systems, thermal effects about thermal effects 195 see also conductors, a.c., thermal effects admittance/reactance/impedance 12 American National Standards Institute, web address 4 asynchronous motors data of 281–2 factor q for short-circuit breaking current 162–3 impedance calculations 55, 63–4 auxiliary installations supply of a power station calculations example 94–6 see also batteries in d.c. auxiliary installations; d.c. auxiliary installations, effects of short circuits; d.c. auxiliary installations, short-circuit current calculations; d.c. motors in auxiliary installations batteries in d.c. auxiliary installations example data 283–5 impedance calculations 60, 64, 65 short-circuit currents 170–2 breaking current with short-circuits: see short-circuit breaking current British Standards Institute, web address 4 busbar/switchgear short-circuit current limitation measures busbar sectionaliser in single busbar switchgear 233–4 Ip-limiter usage 234–6 medium and low voltage limiting equipment 234–6 multiple busbar operation 232–6 time curves of short-circuit currents 235 cables capacitances 276–7 impedances 276 reactances 276–7 see also conductors capacitors in auxiliary installations factor κ 169–71 impedance calculations 59, 64, 65 short-circuit currents 169–70 typical values of capacity and resistance 283–4 causes of short circuit currents 1–3 communication circuit interference: see pipelines/communication circuits, interference with complex calculations 11–14 300 Index conductors, a.c., mechanical effects of short circuits about mechanical effects 201–2 conductor oscillation influence 207–9 bending stress and dynamic force on supports 208–9 mechanical natural frequency 207–8 electromagnetic forces 202–4 fixing clamps calculations example 217–18 forces and stresses in rigid conductor support calculations 204–7 conductors, a.c., thermal effects of short circuits bare conductors 198–9 cable calculation example 216–17 cable screening, armouring and sheath 199–201 maximal permissible short-circuit current density 201 maximal permissible temperature 200–1 heat dissipation considerations, factors m and n 197–8 IEC 60865–1 197 IEC 60909–0 197 impregnated paper-insulated cables 199–200 maximum permissible temperature and current density table 196 overhead line conductors type Al/St 198 rated short-time current density 199 thermal equivalent short-time current 195–7 conductors, d.c. equipment, impedance/resistance calculations 58, 64, 65, 281–3 converter fed drive, impedance calculations 56 correction factors d.c. auxiliary installations, short-circuit current calculations, σ 179 example 190–1 with HV three-phase systems examples 76, 91–4 impedance correction factor K G 154–6 examples 91–4 impedances of equipment and short-circuit current example 154 %/MVA- or p.u.-system 34, 152–4 current limitation earthing power system 102–5 earth-fault factor δ 103, 104 d.c. auxiliary installations, effects of short circuits bending stress on conductors 213–14 bending stress of sub-conductors 211 calculation example 223–4 equivalent circuit diagrams and short-circuit current time course 166 force calculation for main- and sub-conductors 212–15 calculation example 222–3 forces on supports 214–15 mechanical natural frequency of main and sub-conductors 211 standard approximation function (simplified approach) 209 electromagnetic effect example 220 substitute rectangular function approach 209–16 calculation example 220–3 thermal effects calculation example 218–19 thermal short circuit strength 215–16 vibration period and natural mechanical frequency of conductors 212 calculation example 220–1 d.c. auxiliary installations, short-circuit current calculations about auxiliary installations 165–8 correction factor σ 179 equivalent circuit diagram 180 example battery short-circuit current 186 capacitor short-circuit current 185–6 correction factors and corrected parameters 190–1 data and parameters 183–4 equivalent diagram 182 impedances of cable and busbar conductors 184–5 partial short-circuit currents 191–3 rectifier short-circuit current 186–8 total short-circuit current 193–4 maximal short-circuit current calculations 168 minimal short-circuit current calculations 168 time function calculations 167 total short-circuit current 178–82 typical time curves 181 see also batteries in d.c. auxiliary installations; capacitors in auxiliary installations; d.c. motors in auxiliary installations; impedance calculations Index 301 for d.c. equipment; rectifiers in auxiliary installations d.c. motors in auxiliary installations factor κ 175–8 IEC 61000–1:1997 175 IEC 61660–1:1997 175, 178 impedance calculations 62, 65, 66 with independent excitation, short-circuit currents 174–8 factors k 175–8 short-circuit current calculations, example 188–9 definitions and terms 30–2 Deutsches Institute für Normung, web address 4 double earth-faults about double-earth faults 139 fault in a 20-kV-system example 146–8 impedances 139–40 peak short-circuit current 143 power system configurations 140–2 steady-state short-circuit current 143 symmetrical short-circuit breaking current 143 symmetrical short-circuit current 139–40 see also earth currents from short circuits earth currents from short circuits about short-circuits through earth 143–5 short-circuit at overhead-line tower 145–6 short-circuit inside a switchyard 144–5 single-phase short-circuit in a 110-kV-system example 148–9 earth faults: see double earth-faults; earth currents from short circuits earth-fault factor δ and current limitation earthing 103, 104 and low impedance neutral earthing effects 102 earthing considerations about earthing 257 earthing grid resistance calculation example 264–6 earthing impedance 261–2 resistance of different types of earthing 262 human body resistance 257–9 relevant currents through earth 259–61 design information 260 soil conditions and resistivity 258–9 earthing rods 259 see also neutral earthing earthing resistors about earthing resistors 279–81 characteristic parameters 280–1 electromagnetic forces, on a.c. conductors 202–4 equivalent circuit diagrams for short circuits 24–9, 43 factors about factors 151 factor k for d.c. motor short-circuit currents 175–8 factor κ for peak short-circuit current 77–80, 156–8 with d.c. motors 175–8 factor q for short-circuit breaking current of asynchronous motors 162–3 factor λ for steady-state short-circuit current 82–3, 160–2 factor μ for symmetrical short-circuit breaking current 81–2, 158–60 factors m and n, heat dissipation 197 IEC 60909–1:1991–10 151, 162 impedances of equipment and short-circuit current example 152–3 induced voltage calculation, screening factor 252 isolated neutral power system, overvoltage factor 108 see also correction factors faults, as causes of short circuit currents 1–3 fuses, and short circuit currents 2 generators power factor data 270 rated voltage data 270–1 short circuit current limitation, subtransient reactance influence 239–40 sutransient reactance data 270–1 synchronous reactance data 270–1 zero-sequence reactance data 270 human body resistance 257–9 HV a.c. three-phase system short circuit current calculations about HV short circuits 67–8 about parameter calculations 70–2 assumptions and methods 68–71 auxiliary supply of a power station calculations example 94–6 decaying (aperiodic) component 80–1 302 Index HV a.c. three-phase system short circuit current calculations (continued) far-from generator short-circuit 67–9 IEC 60909–0 71, 72–83 impedance correction factor examples 91–4 initial symmetrical short-circuit current 72–4 double-phase 73 far-from-generator 73 line-to-earth 73 three-phase 73 inside power plant short-circuit currents 72–6 correction factors 76, 91–4 equivalent circuit diagrams 74–5 locations around transformers 74–6 line-to-earth (single-phase) short-circuit example 87–8 maximal and minimal short-circuit currents 71–2 meshed 110-kV-system example 89–91 minimal short-circuit currents 85–6 motor influences 84–5 near-to-generator short-circuit example 86–7 peak short-circuit currents 77–80 calculation example 88–9 equivalent frequency method 80 factor κ 77–80 meshed networks 79–80 non-meshed fed 77–8 ratio R/X method 80 single-fed 77 steady-state short-circuit current 82–3 factor λ 82–3 subtransient reactance 67 symmetrical short-circuit breaking current 80–2 factor μ 81–2 types of short circuit 67–9 IEC 60038 6, 226–7 IEC 60050 6, 7 IEC 60071 7 IEC 60265 7 IEC 60282 7 IEC 60479 7 IEC 60781 2, 5, 9, 131, 132 IEC 60865 2, 5, 9, 197 IEC 60896 7 IEC 60909 5, 6, 9, 71, 72–83, 131, 132, 139, 151, 162, 197 IEC 60949 7 IEC 60986 7, 8 IEC 61000 175 IEC 61071 7 IEC 61660 5, 9, 175, 178 IEC document list 5–9 impedance impedance/admittance/reactance 12 impedances of a three-winding transformer in MVA example 37–40 measurement for symmetrical components 20–4 in %/MVA-system for auxiliary supply 96 in %/MVA-system based on measurement example 41–2 impedance calculations for a.c. equipment about impedance for a.c. systems 45 asynchronous motors 55, 63–4 calculation examples 63–4 converter fed drive 56 for HV a.c. three-phase equipment under short circuit examples 91 overhead transmission lines 53, 63–4 power-station unit 52, 63–4 short-circuit limiting reactor 54, 63–4 synchronous generators 51, 63–4 system feeder 46, 63 system loads 57, 63–4 three-winding transformer 48–50, 63–4 two-winding transformer 47, 63 impedance calculations for d.c. equipment about impedance for d.c. systems 50 batteries 60, 64 calculation examples 64–6 capacitors 59, 64, 65 conductors 58, 64, 65 motors, d.c. 62, 65, 66 rectifiers 61, 63–4, 65–6 impedance correction factor KG 154–6 examples 91–4 impedance matrix, transformation of 19–20 inductive interference calculations 247–52 interference: see pipelines/communication circuits, interference with International Electrotechnical Commission, web address 4 Ip-limiters 234–6 isolated neutral power system 105–8 capacitive earth-fault current 106–7 earth faults 105–8 earth-fault arcs 107–8 overvoltage factor 108 Index 303 limitation of short-circuit currents about limitation measures 225–6 coupling of power system at busbars with low short-circuit level 230–1 distribution of feeding locations 228–9 earthing impedances in neutral of transformers 238 and generator subtransient reactance 239–40 meshed systems 241–4 nominal system voltage selection 226–7 IEC 60038:1987 recommended voltages 226–7 operating subsystems separately 227–8 radial systems 241 restructuring power systems 231 ring-main systems 241–2 short-circuit limiting reactors 238 see also busbar/switchgear short-circuit current limitation measures; transformers limiting value, definition 31 low-impedance neutral earthing power system 98–102 earth-fault factor δ 102, 103, 104 single-phase short-circuit current 98–100 single/three-phase short circuit relation 100–1 low-voltage (LV) systems, short circuit current calculations about short-circuit currents in LV systems 131 calculation methods 132 IEC 60781 131, 132 IEC 60909–0 131, 132 impedance calculations 132–3 approximations for generators and rectifiers 133 initial symmetrical short-circuit current 133 maximal short-circuit current calculation example 135–6 minimal short-circuit currents 134–5 calculation example 135, 137 motor influences 134 peak short-circuit current 133 steady-state short-circuit current 134 symmetrical short-circuit breaking current 133 types of faults 131 matrix equations 14–17 cyclic-symmetrical matrix 15–16 see also transformations/transformation matrix maximal and minmal short-circuit currents 3 meshed systems, limitation of short-circuit currents 241–4 motors, influence for HV a.c. three-phase systems 84–5 motors, d.c.: see d.c. motors neutral earthing about neutral earthing 97–8 characteristics of different fault types summary 99 design of an earthing resistor connected to an artificial neutral example 124 limitation of single-phase short-circuit current by earthing through impedance example 123–4 transformer HV-side and LV-side considerations 116–19 compensation windings 116–18 voltages at neutral of a unit transformer example 126–9 see also current limitation earthing power system; isolated neutral power system; low-impedance neutral earthing power system; resonance earthing power systems (Peterson-coil) nominal value, definition 31 norms about technical standards and norms 4–5 international documents and norms 5–6 norms as referred in standards 6–9 ohm-system physical quantities voltage/current/impedance 32 conversion of quantities with p.u. and %/MVA systems 35 example 40 HV three-phase correction factor examples 94 overhead transmission lines capacitances 274–6 conductor sag considerations 275 coupling impedance 273 distance between phase wires 272 impedance calculations/data 53, 63–4, 271–6 impedance in the positive-sequence component for a single and double circuit line 272 304 Index overhead transmission lines (continued) impedance of the zero-sequence component 272 loop impedance 272 relative permeability for 273 resistivity of soil 273 thermal effects 198 typical impedance values 274 parallel and series connection 27, 30 peak short-circuit currents 2–3 double earth faults 143 factor κ 77–80, 156–8, 175–8 low-voltage (LV) systems 133 see also HV a.c. three-phase system short circuit current calculations Peterson-coil: see resonance earthing power systems (Peterson-coil) phasor diagrams 11–14 pipelines/communication circuits, interference with about pipeline interference 245–7 characteristic impedance of the pipeline 253–4 pipeline coating resistance 254 coupling types summary table 246 induced voltage calculation 252–3 coupling impedances 253 screening factor 252 inductive interference calculations 247–52 coupling impedances 249–51 earth return path considerations 248–9 interference of pipeline from 400-kV-line example 262–6 pipeline-to-earth voltage 254–7 oblique exposure 255–6 safety aspects 247 Potier’s reactance 160–1 power system short-circuit current limitation: see limitation of short-circuit currents power-station unit, impedance calculation 52, 63–4 p.u.-system relative units 33–4 conversion of quantities with ohm and MVA systems 35 example 40 correction factor 34 radial systems, limitation of short-circuit currents 241 rated data, definition 32 rated value, definition 31 reactance/admittance/impedance 12 reactors, short-circuit current limiting: see resonance earthing power systems (Peterson-coil) rectifiers in auxiliary installations impedance calculations 61, 63–4, 65–6 short-circuit currents 172–4 relative quantities/p.u.-system 33–4 resonance earthing power systems (Peterson-coil) 108–16, 278–9 20-kV-system example 124–5 about resonance earthing 108–11 alternate earthing of parallel transformer neutrals 118, 121 basic principles 109–11 capacitive earth-fault current and residual current calculation example 125–6 current limits 111 displacement voltage calculations 112–15 fault currents in MV-system from fault in HV-system 118, 121 impedance calculations 54, 63–4 increase of displacement voltage example 119–23 capacitive asymmetry in a 20-kV-system 120, 122 resonance curve for detuning factors in a 20-kV-system 122 Peterson-coils 278–9 tuning 115–16 resonance frequency/tuning 110–11 usage worldwide 108–9 see also neutral earthing ring-main systems, limitation of short-circuit currents 241–2 r.m.s. value of short-circuit currents 2–3 RYB-system representation of a line example 42–4 see also symmetrical components safety, interference with pipelines and communication circuits 247 screening factor, pipelines/communication circuits 252 semirelative quantities and %/MVA system: see %/MVA system semirelative units series and parallel connection 27, 30 short-circuit breaking current about breaking current value 2–3 double earth faults 143 Index 305 factor μ for symmetrical breaking 81–2, 158–60 low-voltage (LV) systems current calculations 133 three-phase systems calculations 80–2 short-circuit current limitation: see limitation of short-circuit currents short-circuit currents about short circuit currents 1–3 equivalent circuit diagrams 24–9 importance of 1–3 maximal and minimal 3 typical time course 2–3 see also busbar/switchgear short-circuit current limitation measures; d.c. auxiliary installations, short-circuit current calculations; earth currents from short circuits; HV a.c. three-phase system short circuit current calculations; limitation of short-circuit currents; low-voltage (LV) systems, short circuit current calculations short-circuit limiting reactors: see resonance earthing power systems (Peterson-coil) soil conditions and resistivity 248, 258–9 standards about technical standards and norms 4–5 American National Standards Institute 4 British Standards Institute 4 definitions and terms 30–2 Deutsches Institute für Normung 4 international documents and norms 5–6 International Electrotechnical Commission 4 norms as referred in standards 6–9 VDE-Verlag 4 see also IEC substitute rectangular function approach: see d.c. auxiliary installations, effects of short circuits subtransient reactance of generators 67, 239–40 switchgear and short circuit currents 2 see also busbar/switchgear short-circuit current limitation measures symmetrical components example 34–7 impedance measurement of 20–4 interpretation of the system of 18–19 and representation of a line in the RYB-system example 42–4 transformation of impedances 19–20 transformation matrix 14–17 see also ohm-system physical quantities voltage/current/impedance; %/MVA system semirelative units; p.u.-system relative units synchronous generators, impedance calculation 51, 63–4 system feeders impedance calculations 46, 63 ranges of initial short-circuit power 267, 268 system loads, impedance calculations 57, 63–4 terms and definitions 30–2 thermal effects of short circuits: see conductors, a.c., thermal effects of short circuits thermal equivalent short-time current for conductors 195–7 three-phase systems: see HV a.c. three-phase system short circuit current calculations time course of short circuit currents 2 transformations/transformation matrix 14–17 complex rotational phasors 17 cyclic-symmetrical matrix 15–16 delta-star-transformation 31 reverse transformation 17 star-delta-transformation 30 transformation of impedances 19–20 transformers impedance calculations in %/MVA 37–40 and impedance measurement for symmetrical components 20–3 ratio of positive to negative sequence impedance 270 short-circuit current limitation measures 236–8 earthing impedances in the neutrals 238–9 impedance voltage considerations 236–8 loadflow and short-circuit analysis results 237 three-winding, impedance calculations 21–4, 48–50, 63–4 306 Index transformers (continued) two-winding, impedance calculations 47, 63 typical values two-winding transformer impedance voltage 267–70 ohmic losses, no-load losses and no-load current 267, 269 see also neutral earthing transmission lines: see overhead transmission lines VDE documents 5–9 VDE-Verlag, web address 4 vectors/vector diagrams 11–15 example 34–7 web addresses, standards institutions 4 Short-circuit฀Currents The฀calculation฀of฀short-circuit฀currents฀is฀a฀central฀task฀for฀Power฀ System฀engineers,฀as฀they฀are฀essential฀parameters฀for฀the฀design฀of฀ electrical฀equipment฀and฀installations,฀the฀operation฀of฀power฀systems฀ and฀the฀analysis฀of฀outages฀and฀faults. Short-circuit฀Currents฀gives฀an฀overview฀of฀the฀components฀within฀ power฀systems฀with฀respect฀to฀the฀parameters฀needed฀for฀shortcircuit฀current฀calculation.฀It฀also฀explains฀how฀to฀use฀the฀system฀of฀ symmetrical฀components฀to฀analyse฀different฀types฀of฀short-circuits฀ in฀power฀systems.฀The฀thermal฀and฀elctromagnetic฀effects฀of฀shortcircuit฀currents฀on฀equipment฀and฀installations,฀short-time฀interference฀ problems฀and฀measures฀for฀the฀limitation฀of฀short-circuit฀currents฀are฀ also฀discussed.฀Detailed฀calculation฀procedures฀and฀typical฀data฀of฀ equipment฀are฀provided฀in฀a฀separate฀chapter฀for฀easy฀reference,฀and฀ worked฀examples฀are฀included฀throughout. Professor฀Dr-Ing฀Jürgen฀Schlabbach฀received฀ his฀PhD฀in฀1982฀from฀the฀Technical฀University฀ of฀Darmstadt,฀Germany.฀Until฀1992฀he฀worked฀ as฀a฀Consultant฀Engineer฀with฀responsibility฀for฀ the฀planning฀and฀design฀of฀public฀and฀industrial฀ supply฀systems.฀Since฀1992฀he฀has฀worked฀at฀the฀ University฀of฀Applied฀Sciences฀in฀Bielefeld,฀Germany฀ as฀Professor฀for฀Power฀System฀Engineering฀and฀ Utilisation฀of฀Renewable฀Energy.฀His฀main฀interests฀ are฀power฀systems฀planning,฀fault฀analysis,฀power฀ quality,฀interference฀problems฀and฀connection฀of฀ renewable฀energy฀sources฀to฀power฀systems,฀and฀ he฀carries฀out฀consultancy฀work฀in฀these฀fields.฀He฀is฀ a฀member฀of฀the฀IEEE฀and฀VDI. The฀Institution฀of฀Engineering฀and฀Technology www.theiet.org฀ 0-86341-514-8 978-0-86341-514-2