FST DFS GE Mark IV Speedtronic

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Doc. No.

Ver: 1.01 Rev: 6

GE Mark IV Speedtronic
FS-8700-14

DESCRIPTION

The GE Mark IV Speedtronic driver allows the FieldServer to receive status data from Speedtronic devices over either RS-232 or RS-485 using GE Mark IV Speedtronic protocol. The Driver acts as a Passive Client and receives status data from Speedtronic devices. Note that only Digital values are supported. Fieldserver Mode Client Nodes 1-10 (max) Comments The max number of nodes is limited by the amount of physical ports on the FieldServer.

FORMAL DRIVER TYPE

Serial Passive Client

COMPATIBILITY MATRIX
Compatible with this driver Yes Yes No Yes Yes No No No

FieldServer Model FS-x2010 FS-x2011 FSx25 FS-x30 FS-x40 SlotServer ProtoCessor ProtoNode

CONNECTION INFORMATION
Connection type: Baud Rates: Data Bits: Stop Bits: Parity: Multidrop Capability EIA232 or EIA485 (Two wire, Half-Duplex) 300; 1200; 2400; 4800; 9600; 19200; 28800; 38400 Baud Vendor limitation. 8 Vendor limitation 1 Vendor limitation Even Vendor limitation No

DEVICES TESTED
Tested (FACTORY, SITE) TBC

Device GE Mark IV Speedtronic

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 1 of 8

Doc. No.

Ver: 1.01 Rev: 6

GE Mark IV Speedtronic
FS-8700-14

CONNECTION CONFIGURATIONS

P1

GE MKIV Speedtronic #1

FieldServer
R2 GE MKIV Speedtronic #10 Connection pinouts to be inserted

(408)-262-2299

GE MARK IV SPEEDTRONIC CONNECTION DIAGRAM


BASE NAME: FILE NAME: DATE: 01/05/03 BY: MF

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 2 of 8

Doc. No.

Ver: 1.01 Rev: 6

GE Mark IV Speedtronic
FS-8700-14

7 7.1

COMMUNICATIONS FUNCTIONS - SUPPORTED FUNCTIONS AT A GLANCE: Data Types Supported


Description (or Device Data Type) Integer Points Logic Points Miscellaneous Points Annunciator Alarms

FieldServer Data Type Analog Input Digital Input Analog Register Digital Register

7.2

Read Operations supported

FieldServer as a Passive Client Read All Points and Alarm Statuses

7.3

Unsupported Functions and Data Types


Reason Only Rev. 2 12/13/84 of Speedtronic protocol is currently supported

Function GE Mark IV Speedtronic

DRIVER POINT LIST


Signal Description Zero Pt. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Maximum Units Bytes

Byte No.

Miscellaneous Points 1 TIME 2 TIME 3 TIME 4 TIME 5 TIME 6 TIME 7 TIMR-01 11 TIMR-02 15 CNTR-01 19 CNTR-02 23 CNTR-03 27 CNTR-04 31 CNTR-05 Integer Points 35 TTX01-1 37 TTX01-2 39 TTX01-3 41 TTX01-4 43 TTX01-5 45 TTX01-6 47 TTX01-7

SECONDS MINUTES HOUR DAY MONTH YEAR TOTAL FIRED HOURS MANUALLY INIT STARTS PEAK FIRED HOURS TOTAL STARTS FAST LOAD STARTS FIRED STARTS TRIPS EXHAUST TEMPERATURE TC = 1 EXHAUST TEMPERATURE TC = 2 EXHAUST TEMPERATURE TC = 3 EXHAUST TEMPERATURE TC = 4 EXHAUST TEMPERATURE TC = 5 EXHAUST TEMPERATURE TC = 6 EXHAUST TEMPERATURE TC = 7

59 59 24 9 12 99 9999999.9 9999999.9 9999999.9 9999999.9 9999999.9 9999999.9 9999999.9 2048 2048 2048 2048 2048 2048 2048 DEG F DEG F DEG F DEG F DEG F DEG F DEG F

1 1 1 1 1 1 4 4 4 4 4 4 4 2 2 2 2 2 2 2

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 3 of 8

Doc. No.

Ver: 1.01 Rev: 6

GE Mark IV Speedtronic
FS-8700-14

Byte No. 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95 97 99 101 103 105 107 109 111 113 115 117 119 121 123 125 127 129 131 133 135 137 139

Signal TTX01-8 TTX01-9 TTX01-10 TTX01-11 TTX01-12 TTX01-13 TTX01-14 TTX01-15 TTX01-16 TTX01-17 TTX01-18 TTXC CTIF-1 CTIF-2 CTDA-1 CTDA-2 TTWS1FI1 TTWS1FI2 TTWS1FO1 TTWS1FO2 TTWS1FA1 TTWS1FA2 TTWS2FO1 TTWS2FO2 TTWS2AO1 TTWS2AO2 TTWS3FO1 TTWS3FO2 TTWS3AO1 TTWS3AO2 TTXSPL TTXSP1 TTXSP2 LTTH1 LTB1D LTB2D LTBT1D BTLG1 BTLG2 BTLG3 BTLG4 BTLG5 BTGJ11 BTGJ21 BB1 BB2

Description EXHAUST TEMPERATURE TC = 8 EXHAUST TEMPERATURE TC = 9 EXHAUST TEMPERATURE TC = 10 EXHAUST TEMPERATURE TC = 11 EXHAUST TEMPERATURE TC = 12 EXHAUST TEMPERATURE TC = 13 EXHAUST TEMPERATURE TC = 14 EXHAUST TEMPERATURE TC = 15 EXHAUST TEMPERATURE TC = 16 EXHAUST TEMPERATURE TC = 17 EXHAUST TEMPERATURE TC = 18 EX TEMP AVG LOW'S - HIGH AND LOW REJECTED COMP INLET FLANGE TEMP 1 COMP INLET FLANGE TEMP 2 COMP DISCHARGE TEMP 1 COMP DISCHARGE TEMP 2 TURB WHEELSPACE TEMP 1ST STG FWD INNER TURB WHEELSPACE TEMP 1ST STG FWD INNER TURB WHEELSPACE TEMP 1ST STG FWD OUTER TURB WHEELSPACE TEMP 1ST STG FWD OUTER TURB WHEELSPACE TEMP 1ST STG AFT OUTER TURB WHEELSPACE TEMP 1ST STG AFT OUTER TURB WHEELSPACE TEMP 2ND STG FWD INNER TURB WHEELSPACE TEMP 2ND STG FWD INNER TURB WHEELSPACE TEMP 2ND STG AFT OUTER TURB WHEELSPACE TEMP 2ND STG AFT OUTER TURB WHEELSPACE TEMP 3RD STG FWD INNER TURB WHEELSPACE TEMP 3RD STG FWD INNER TURB WHEELSPACE TEMP 3RD STG AFT OUTER TURB WHEELSPACE TEMP 3RD STG AFT OUTER COMBUSTION MONITOR ALLOWABLE SPREAD COMBUSTION MONITOR ACTUAL SPREAD 1 COMBUSTION MONITOR ACTUAL SPREAD 2 LUBE TEMP TURBINE HEADER, GT/GG LUBE TEMP NO. 1 TURB. BRG. DRAIN LUBE TEMP NO. 2 TURB. BRG. DRAIN LUBE TEMP NO. 1 THRUST BRG. DRAIN BEARING METAL TEMP LEAD GEAR =1 BEARING METAL TEMP LEAD GEAR =2 BEARING METAL TEMP LEAD GEAR =3 BEARING METAL TEMP LEAD GEAR =4 BEARING METAL TEMP LEAD GEAR =5 BEARING METAL TEMP GEN. JOURNAL =1 BEARING METAL TEMP GEN. JOURNAL =2 VIBRATION TRANSDUCER = 1 VIBRATION TRANSDUCER = 2

Zero Pt. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Maximum 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 2048 8 8

Units DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F IN/SEC IN/SEC

Bytes 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 4 of 8

Doc. No.

Ver: 1.01 Rev: 6

GE Mark IV Speedtronic
FS-8700-14

Byte No. 141 143 145 147 149 151 153 155 157 159 161 163 165 167 169 171 173 175 177 179 181 183 185 187 189 191 193 195 197 199 201 203 205 207 207

Signal BB4 BB5 BB7 BB8 BB9 BB-MAX PN TNH TNR FSR1 FSR2 CPD FPCI TTRXB CSRGV CSGV FOROUT FO FSROUT FSG FPRG FSGR DW SVL SFL DVAR DDUMP1 DDUMP2 DDUMP3 DDUMP4 DDUMP5 DDUMP6 DDUMP7 DDUMP8 DDUMP8

Description VIBRATION TRANSDUCER = 4 VIBRATION TRANSDUCER = 5 VIBRATION TRANSDUCER = 7 VIBRATION TRANSDUCER = 8 VIBRATION TRANSDUCER = 9 VIBRATION MAX SELECT TURBINE STARTING DEVICE SPEED TURBINE SPEED HP SPEED CONTROL REFERENCE LIQUID FUEL STROKE REF. FROM FUEL SPLITTER GAS FUEL STROKE REF. FROM FUEL SPLITTER COMPRESSOR DISCHARGE PRESSURE INTERVALVE PRESSURE SPEED BIASED TEMPERATURE CONTROL REF. VIGV REFEENCE ANGLE INLET GUIDE VANE ANGLE (SCALED) LIQUID FUEL FLOW REFERENCE LIQUID FUEL FLOW GAS CONTROL VALVE POSITION REFERENCE GAS CONTROL VALVE LVDT POSITION GAS RATIO VALVE CONTROL PRESS REF. SPEED RATIO VALVE CALIBR. POS. GENERATOR LOAD SYSTEM LINE VOLTAGE SYSTEM LINE FREQUENCY GENERATOR LOAD VARS (SCALED)

SPARE POINT SEQUENCING)

(OPT.

WRITTEN

TO

BY

Zero Pt. 0 0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0 0 0 0 0 0 0 0 0

Maximum 8 8 8 8 8 8 125 125 125 100 100 2048 2048 2048 100 100 10 64 10 100 10 10 204.80 150 62.50 204.80 32768 32768 32768 32768 32768 32768 32768 32768 32768

Units IN/SEC IN/SEC IN/SEC IN/SEC IN/SEC IN/SEC % SPEED % SPEED % SPEED % % PSI PSI DEG F DEGR DEGR V DC m/SEC V DC % V DC V DC MW V RMS HZ MVAR CNT1S CNT1S CNT1S CNT1S CNT1S CNT1S CNT1S CNT1S CNT1S

Bytes 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 5 of 8

Doc. No.

Ver: 1.01 Rev: 6

GE Mark IV Speedtronic
FS-8700-14

Byte No. Signal Logic points 0 L30D-SD 1 L30D-SU 2 L30D-RUN 3 L30D-RSZ 211 4 L30D-RSZ 5 L30D-STG 6 L30D-CRN 7 L63SUF 1 0 1 2 3 212 4 5 6 7 0 1 2 3 213 4 5 6 7 0 1 2 3 214 4 5 6 7 0 1 2 3 215 4 5 6 7 0 1 2 216 3 4 5

Description NORMAL DISPLAY MESSAGE "SHUTDOWN STATUS" NORMAL DISPLAY MESSAGE "STARTUP STATUS" NORMAL DISPLAY MESSAGE "RUN STATUS" NORMAL DISPLAY MESSAGE "NOT READY TO START" NORMAL DISPLAY MESSAGE "READY TO START" NORMAL DISPLAY MESSAGE "STARTING" NORMAL DISPLAY MESSAGE "CRANKING" STARTUP FSR FIRING FUEL COMMAND STARTUP FSR WARMUP FUEL COMMAND NORMAL DISPLAY MESSAGE "ACCELERATING" NORMAL DISPLAY MESSAGE "FULL SPEED NO LOAD" NORMAL DISPLAY MESSAGE "SYNCHRONIZING" NORMAL DISPLAY MESSAGE "SPINNING RESERVE" NORMAL DISPLAY MESSAGE "LOADING" NORMAL DISPLAY MESSAGE "FAST LOADING" NORMAL DISPLAY MESSAGE "PRESELECTED LOAD" NORMAL DISPLAY MESSAGE "BASE LOAD" NORMAL DISPLAY MESSAGE "PEAK LOAD" NORMAL DISPLAY MESSAGE "PART LOAD" NORMAL DISPLAY MESSAGE "UNLOADING" NORMAL DISPLAY MESSAGE "FIRED SHUTDOWN" NORMAL DISPLAY MESSAGE "COASTING DOWN" NORMAL DISPLAY MESSAGE "ON COOLDOWN" NORMAL DISPLAY MESSAGE "OFF COOLDOWN" OFF MODE SELECTED CRANK MODE SELECTED FIRE MODE SELECTED AUTO MODE SELECTED REMOTE MODE SELECTED NORMAL DISPLAY MESSAGE "START SELECT" NORMAL DISPLAY MESSAGE "STOP SELECT" PRE-SELECTED LOAD COMMAND BASE LOAD COMMAND PEAK LOAD COMMAND FSR SHUTDOWN CONTROL FSR STARTUP CONTROL FSR ACCELERATION CONTROL HP SPEED FSR TEMPERATURE CONTROL FSR SPEED DROOP CONTROL FSR SPEED ISOCH CONTROL MIN FSR LOGIC FSR MANUAL CONTROL SEQUENCE IN PROGRESS 10V CONTROL MESSAGE - MAXIMUM ANGLE 10V CONTROL MESSAGE - TEMPERATURE CONTROL 10V CONTROL MESSAGE - MANUAL CONTROL

Logic Zero 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Logic One 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Bytes 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 6 of 8

Doc. No.

Ver: 1.01 Rev: 6

GE Mark IV Speedtronic
FS-8700-14

Byte No. Signal Logic points 6 7 0 1 2 3 217 4 5 6 7 0 1 2 3 218 4 5 6 7 0 1 2 3 219 4 5 6 7 0 1 2 3 220 4 5 6 7 0 1 2 3 221 4 5 6 7

Description NORMAL DISPLAY MESSAGE "VOLTAGE MATCHING" AUXILIARY TO FAST LOAD START SIGNAL WATER WASH SELECTED FUEL LINE PURGE IN PROGRESS MASTER PROTECTIVE SIGNAL NORMAL SHUTDOWN TURBINE COMPLETE SEQUENCE HP ZERO SPEED SIGNAL MINIMUM SPEED SIGNAL (APPR 20%) ACCELERATING FUEL SPEED SIGNAL (APPR 40%) HP OPERATING SPEED SIGNAL FLAME DETECTED CHANNEL =1 FLAME DETECTED CHANNEL =2 FLAME DETECTED CHANNEL =3 FLAME DETECTED CHANNEL =4 GENERATOR BREAKER CLOSURE SPARE POINT (OPT. WRITTEN TO BY SEQUENCING)

Logic Zero 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Logic One 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Bytes 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8 1/8

SPARE POINT (OPT. WRITTEN TO BY SEQUENCING)

SPARE POINT (OPT. WRITTEN TO BY SEQUENCING)

SPARE POINT (OPT. WRITTEN TO BY SEQUENCING)

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 7 of 8

Doc. No.

Ver: 1.01 Rev: 6

GE Mark IV Speedtronic
FS-8700-14

Byte No. Annunciator Alarms 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253

Description ALARM 0-7 ALARM 8-15 ALARM 16-23 ALARM 24-31 ALARM 32-39 ALARM 40-47 ALARM 48-55 ALARM 56-63 ALARM 64-71 ALARM 72-79 ALARM 80-87 ALARM 88-95 ALARM 96-103 ALARM 104-111 ALARM 112-119 ALARM 120-127 ALARM 128-135 ALARM 136-143 ALARM 144-151 ALARM 152-159 ALARM 160-167 ALARM 168-175 ALARM 176-183 ALARM 184-191 ALARM 192-199 ALARM 200-207 ALARM 208-215 ALARM 216-223 ALARM 224-231 ALARM 232-239 ALARM 240-247 ALARM 248-255

LogicZero 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

LogicOne FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF

Bytes 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 8 of 8