ABB - Generator Protections Guide
ABB - Generator Protections Guide
ABB - Generator Protections Guide
Generator Protection
ABB Network Partner AB 1MRK 502 003-AEN
Page 15
Fig. 7 Operate values for RXNB 4. Curve A is valid for the relay ver-
sion 300 V and curve B is valid for relay version up to 600 V
excitation voltage
6.2 Rotor earth-fault relay
with ac injection
For small generators with rotating dc exciters, a suitable rotor earth-fault
protection can be arranged with ac injection and a time-overcurrent relay
as shown in Fig. 8. With current setting 15 mA , the protection operates
for earth- faults with fault resistance up to about 3 k, independent of
fault location.
The capacitance between the field circuit and earth should not exceed
0,5F. The 4F coupling capacitor should have test voltage 5 kV dc
between terminals and between terminals and earth.
Fig. 8 Rotor earth-fault relay with ac injection
6.3 Time-overcurrent
relay RAIDG
The micro-processor based time-overcurrent relay RXIDG 2H has current
scale range 15 mA to 2,6 A and a logarithmic inverse time delay. At max-
imum earth-fault resistance, for which the relay operates, the time delay is
5,8 s. The minimum operate time can be set in the range 1 to 2 s.
Single-phase relay assemblies,type RAIDG, are made up based upon the
RXIDG 2H unit. For further details, see Buyers Guide.
60
50
40
30
20
10
0
0 100 200 300V
2
Contribution U
x
from the excitation voltage
Reset
value
Operate
value
Operate
range
U
x
Curve A
Insulation resistance
k
300
250
200
150
100
50
5
0 200 400 600V
7
Contribution U
x
from the excitation voltage
Reset
value
Operate
value
Operate
range
Curve B
Insulation resistance
k
100 300 500
I >
Trip or
<
~
alarm
400
55V
110 or
220V~
4F
ABB Network Partner AB
Generator Protection 1MRK 502 003-AEN
Page 16
7 Phase short-circuit protection
In case of short-circuits between phases in the stator winding or between
the generator terminals, the machine must quickly be disconnected from
the network and brought to a complete shutdown in order to limit the
damage. Phase short-circuits on the generator bus, in the unit transfommer
or in the high voltage winding of the unit transformer, must also be
quickly disconnected from the network. The generator must be brought to
a complete shutdown in case of a transformer fault if there is no cir-
cuit-breaker between the machine and the transformer.
Although statistics show that phase short-circuits is one of the rare types
of fault in generators and generator-transformer units, it is considered
necessary to have fast-acting phase short-circuit protection for all units
with rating higher than 5-10 MVA. With known technique, this can only
be obtained by means of differential relays. Back-up protection, in the
form of an impedance relay or an undervoltage relay with overcurrent
start, should be provided. For the smallest units no differential relay is
provided, and the impedance or voltage/current relay becomes the main
protection. Overcurrent relays can be used if the sustained fault current is
sufficiently high to secure operation.
7.1 Generator differential
relays
For modern generators, the time constant of the dc component in the
short-circuit current is large, typically more than 200 ms. The risk of satu-
ration of the current transformers in case of external short-circuits is obvi-
ous. It is, therefore, important that the generator differential relay remains
stable even when the current transformers are heavily saturated.
For small and moderate size generators, ABB uses the high impedance
stabilized type of differential relay. For machines with rating above 250 -
300 MVA, the percentage stabilized, moderate impedance type is used.
Both types are fast-operating, highly sensitive relays which, in case of
external short-circuits, are completely stable even in case of fully satu-
rated current transformers.
The principle of the RADHA high-impedance differential relay is shown
in Fig. 9. The current transformers on the generator neutral and the line
side shall have identical turns ratio and similar magnetizing charac-
teristics. Hence, under normal service conditions and external faults with
unsaturated current transformers, the voltage U
re
across the relay measur-
ing circuit is negligible.
Generator Protection
ABB Network Partner AB 1MRK 502 003-AEN
Page 17
Fig. 9 The high impedance measuring principle
In case of an external short-circuit, one of the current transformers may
saturate more than the other. The worst case will be if one is completely
saturated and the other is completely unsaturated. The maximum voltage
across the relay will be:
U
max
= I
s
" ( R
CT
+ R
L
) where
I
s
" = secondary subtransient short-circuit current, symmetrical (ac) com-
ponent
R
L
= resistance of pilot wire between current transformer (CT ) and relay
R
CT
= resistance of the secondary winding of the saturated current trans-
former
The relay operate voltage is set higher than U
max
The minimum operate current depends mainly on the voltage setting of
the relay, the magnetizing characteristics and the current ratio of the CTs.
For internal faults, with fault current equal to or above the minimum oper-
ate value of the relay, the voltage across the relay goes up to the full satra-
tion voltage of the CTs and the relay operates in 10 -15 ms.
A voltage dependent resistor across the differential relay limits the voltage
to a safe level.
The primary operate current is normally between 1-5 % of rated generator
current. The relay requires dedicated CT cores.
For further details, see Buyers Guide.
G
e
1
e
2
e
1
e
2
Normal
conditions
G
R
CT
R
CT
R
L
R
L
I
S
I
S
L
1
L
2
I
1
I
2
External
fault
U
max
Normal service and external fault
without CT saturation
A. External fault with line side
CT fully saturated
B.
U
re
ABB Network Partner AB
Generator Protection 1MRK 502 003-AEN
Page 18
The principle diagram of the measuring circuits of RADSG percentage
differential relay is shown in Fig. 10. Relays d
R
and S
R
operate in less
than 1 ms in case of severe internal faults. The impulse storing circuit
across the coil of the 4 ms output relay (1) secures operation if the d
R
and
S
R
relay contacts are closed for more than 0,3 ms, and the output relay
becomes selfholding when it operates. The function of the RADSG relay
is, therefore, not affected by current transformer saturation in case of
internal faults.
Fig. 10 The RADSG generator differential relay. Principle diagram
The minimum operate current can be set as low as 3 % of rated generator
current.
If the current transformer saturates during an external fault, a certain cur-
rent I
d
will flow in the differential circuit. The d
R
relay remains stable as
long as the ratio I
d
/l
T3
is below the set stability limit (normally 20 %). The
ratio I
d
/l
T3
is determined by the ratio of the resistance in the differential
circuit to the resistance in the circuit with the saturated current trans-
former. Hence, the conditions for complete stability in case of external
faults are easily determined
For further details, see Buyers Guide.
The RADSC relay is used when the low impedance, percentage restrained
type is requested as generator differential relay. The lowest setting of
RADSC is 15 % of rated current and the operate time is approx. 20 ms at
R
d3
R
S
Tripping
1) 1)
I
T3
I
d
T
Md
S
r
d
R
1
(+) ()
(+)
R
S
T
1) To measuring circuits for phase S and T
Generator Protection
ABB Network Partner AB 1MRK 502 003-AEN
Page 19
2 times set restraint operate value. An unrestrained function, settable 5, 10
or 15 times rated current gives fast tripping for severe generator faults
with large fault currents.
For further details, see Buyers Guide.
7.2 Generator and unit
transformer
differential relay
The transformer differential relay RADSB is used for generator-trans-
former units. It is a static relay with threefold restraint:
1. Through-fault restraint for external faults
2. Magnetizing inrush restraint
3. Over-excitation restraint to counteract operation at abnormal magnetiz-
ing currents caused by high voltage
The magnetizing inrush restraint is required to keep the relay stable when
a nearby fault on an adjacent feeder is cleared.
During the time of the fault, the terminal voltage of the main transformer
is practically zero and at the instant of fault clearance, i.e. when the cir-
cuit-breaker of the faulty feeder opens, the transformer terminal voltage
quickly rises. This may cause severe magnetizing inrush currents.
For generator-transformer units with separate generator breaker, the
inrush restraint is also required when the unit transformer is energized
from the H.V. bus.
The over-excitation restraint is important for generator-transformer differ-
ential relays. Without this restraint, there is an obvious risk that the differ-
ential relay may trip the generator due to overvoltage if a substantial part
of the load is disconnected when clearing a fault. The voltage then rises
immediately and remains high until the automatic voltage regulator
(AVR) of the machine has brought it back to the normal value.
For normally designed transformers with grain-oriented core, the RADSB
relay remains stable up to about 140% of rated voltage.
In addition to the restrained function, the relay has also a high set, unre-
strained differential current measuring circuitry. The unrestrained opera-
tion must be set higher than the maximum inrush current of the trans-
former. It gives fast tripping (10 - 20 ms) for severe faults with large fault
current.
For further details, see Buyers Guide.
ABB Network Partner AB
Generator Protection 1MRK 502 003-AEN
Page 20
7.3 Phase short-circuit
back-up relays
As a back-up short-circuit protection, a three-phase overcurrent relay with
definite or inverse time-delay can be used if the generator short-circuit
current without any doubt gives operation of the relay. This is normally
the case for generators with excitation system not supplied from the gen-
erator bus and with the AVR in service.
In the case of a static excitation system, which receives its power from the
generator terminals, the magnitude of a sustained phase short-circuit cur-
rent depends on the generator terminal voltage. In case of a nearby inter-
phase fault, the generator terminal voltage drops and the fault current may
fall below the setting of the overcurrent relay within a few seconds as
shown in Fig. 11.
Fig. 11 Exemple on dependence of short-circuit current for generator
with excitation system fed from generator bus in case of short-
circuit close to the generator terminals
The short-circuit current may drop below rated current after 0.5 - 1 s also
for generators with excitation system not fed from the generator terminals
if the fault occurs when the automatic voltage regulator is out of service.
For this reason, an impedance measuring relay is generally recommended
for back-up short-circuit protection.
The impedance relay is normally connected to current transtormers on the
generator neutral side to provide back-up also when the generator is dis-
connected from the system. At reduced voltages, the current required for
operation will be reduced. At zero voltage, operation is obtained with a
current of less than 20 % of rated relay current.
10
5.0
2.0
1.5
1.0
0.5
0.2
0.1
1 2 3
I
SC
/lm
2
3
time (s)
Generator Protection
ABB Network Partner AB 1MRK 502 003-AEN
Page 21
7.4 Impedance relay RAZK The micro-processor based impedance relay RXZK 22H has two imped-
ance measuring stages and definite time delay. The impedance measuring
characteristic is polygonal with independent setting of the reach in the X
and R directions, see Fig. 12.
Impedance stage Z1 is set to reach only into the unit transformer and will
provide a fast back-up protection for phase short-circuits on the generator
terminals, the generator bus and the low voltage winding of the unit trans-
former. It should be observed that with this low setting, the relay protects
only the part of the stator winding which is close to the terminals. The
relay should measures phase currents and voltage between phases to
measure correctly the short-circuit impedance in case of two-phase faults.
Impedance stage Z2 is normally set to operate at 70 % of rated generator
load impedance, corresponding to an operate current of 1/0.7=1.4 times
rated current at rated voltage. The selectivity against other relays in the
network has to be secured by a proper time delay setting.
Three-phase relay assemblies RAZK are made up based upon the
RXZK22H units. For further details, see Buyers Guide.
a) Connection of relay b) Operate characteristic, = 90
Fig. 12 Impedance relay
G
Z<
X
R
= 90
ABB Network Partner AB
Generator Protection 1MRK 502 003-AEN
Page 22
8 Phase interturn short-circuit protection
Modern medium size and large size turbo-generators have the stator wind-
ing designed with only one turn per phase per slot. For these machines,
interturn faults can only occur in case of double earth-faults or as a result
of severe mechanical damage on the stator end winding. The latter is con-
sidered rather unlikely to occur.
Even hydro-generators above a certain size normally have their stator
winding designed with one turn per phase per slot.
In ABB generators, multiturn windings are used in some cases for
machines up to about 50 MVA.
It is generally considered difficult to obtain a reliable protection against
short-circuiting of one turn if the stator winding has a large number of
turns per phase.
For generators with split neutrals, the conventional inter-turn fault protec-
tive scheme comprises a time delayed low-set overcurrent relay which
senses the current flowing in the connection between the neutrals of the
stator winding, see Fig. 13. The fault current can be extensively large in
case of interturn faults, hence, the time delay must be short, 0,2 to 0,4 s,
and the overcurrent relay must be set higher than the maximum unbal-
anced current flowing between the neutrals in case of an external short-
circuit. The maximum unbalanced current in case of external faults and
the minimum unbalanced current for single-turn short-circuits have to be
obtained from the manufacturer of the machine.
Fig. 13 Connection of interturn short-circuit protection
Due to the difficulties in obtaining a reliable and secure interturn protec-
tion, it is in most cases omitted. It is assumed that the interturn fault, first
of all, will lead to a single phase earth-fault at the faulty spot, and the
machine will then be tripped by the earth-fault relay within 0,3 - 0,4 s.
Generator Protection
ABB Network Partner AB 1MRK 502 003-AEN
Page 23
8.1 Interturn short-circuit
current relay RAIDK
The micro-processor based time-overcurrent relay RXIDK 2H is used for
the interturn protection acc. to Fig. 13. For this application, the relay is
provided with an optional filter which gives a damping factor of more
than 40 for third harmonic currents. Current stage 1 of the relay is pro-
grammable for five different inverse time characteristics and definite time
delay. Normally, a definite time delay of 0,3-0,5 s is used.
Relay assemblies, type RAIDK, are made up based upon the RXIDK 2H
units. For further details, see Buyers Guide.
ABB Network Partner AB
Generator Protection 1MRK 502 003-AEN
Page 24
9 Thermal overload protection
Overloads up to 1.4 times the rated current are not normally detected by
the impedance or overcurrent protection. Sustained overloads within this
range are usually supervised by temperature monitors (resistance ele-
ments) embedded at various points in the stator slots. The temperature
monitoring system enables measurements measuring points.
As an additional check of the stator winding temperature, an accurate
thermal overload reay may be used. With modern relays, it is possible to
obtain relay time-constants down to some few minutes, which is required
for adequate thermal protection of directly cooled machines.
The temperature rise of the stator winding is, in addition to the magnitude
of the current, also influenced by the coolant flow, the coolant tempera-
ture, etc. The current overload relay can, therefore, not be expected to
give an exact measurement of the winding temperature under all condi-
tions.
9.1 Thermal overload relay
RAVK
The micro-processor based thermal overload relay RXVK 2H has a ther-
mal time constant ( settable in the range 2-62 minutes in steps of 2 min-
utes and a current stage with dependent time delay, settable 0,03 - 5 s. The
relay has output contact for alarm when the measured thermal content is
95 % of operate value.
Single and multiphase protection assemblies, type RAVK, are built up
based upon the RXVK 2H units. For further details, see Buyers Guide.
Generator Protection
ABB Network Partner AB 1MRK 502 003-AEN
Page 25
10 Negative phase-sequence current protection
When the generator is connected to a balanced load, the phase currents are
equal in magnitude and displaced electrically by 120. The ampere-turns
wave produced by the stator currents rotate synchronously with the rotor
and no eddy currents are induced in the rotor parts.
Unbalanced loading gives rise to a negative sequence component in the
stator current. The negative-sequence current produces an additional
ampere-turn wave which rotates backwards, hence it moves relatively to
the rotor at twice the synchronous speed. The double frequency eddy cur-
rents induced in the rotor may cause excessive heating, primarily in the
surface of cylindrical rotors and in the damper winding of rotors with sali-
ent poles.
The approximate heating effect on the rotor of a synchronous machine for
various unbalanced fault or severe load unbalance conditions is deter-
mined by the product I
2
2
t = K, where I
2
is the negative sequence current
expressed in per unit (p.u.) stator current, t the duration in seconds and K a
constant depending on the heating characteristic of the machine, i.e., the
type of machine and the method of cooling adopted.
The capability of the machine to withstand continously unbalanced cur-
rents is expressed as negative sequence current in percent of rated stator
current.
Typical values for generators are given in Table 1 .
') The lower values are typical for large machines (P >800 MVA)
Single-phase and, especially, two-phase short circuits give rise to large
negative sequence currents. The faults are, however, cleared by other
relays in a time much shorter than the operate time of the negative
sequence relay. E.g. a two-phase shortcircuit with fault current equal to
3.46 times rated generator current implies a negative sequence current
component equal to twice the rated current (2 p.u). Hence, a nega-
tive-sequence relay with the setting I
2
2
t = 10 s would trip with a time
delay of 10 / 2
2
= 2,5 s.
Table 1:
Type of generator Max.
permitted
K = I
2
2
t
(seconds)
Max.
permitted
continuous I
2
(percent)
Cylindrical rotor:
indirectly cooled 30 10
directly cooled 5-10
1)
8
1)
Salient pole:
with damper winding 40 10
without damper winding 40 5
ABB Network Partner AB
Generator Protection 1MRK 502 003-AEN
Page 26
Examples on load dissymmetries which give rise to negative-sequence
currents in the generator are:
Unbalanced single-phase loads, such as railroads and induction fur-
naces
Transmission line dissymmetries due to non-transposed phase wires
or open conductor (circuit-breaker pole failure)
An open conductor may give rise to a considerable negative-sequence
current, as a maximum of more than 50 % of rated machine current. The
combination of two or more of the above mentioned dissymmetries can
give rise to harmful negative phase sequence currents, even if each of
them gives rise to a relatively small unbalance. It is, therefore, considered
as good engineering practice to provide negative-sequence current protec-
tion for all, but the small size generators.
10.1Negative-sequence
current relay RARIB
with thermal memory
The diagram in Fig. 14 indicates the measuring functions in RARIB and
the setting ranges.
The power consumption in the current sequence filter (2) is only 0.1 VA/
phase. The input current to the relay measuring circuit is adapted to the
rated generator secondary current by the aid of the potentiometer (3).
The measuring unit for I
2
t has the setting range 1-63 s in steps of 1 s. The
unit is provided with a thermal memory and the cooling down time of the
relay is settable in 7 steps in the range (2,65 - 170) x k. The blocking relay
resets when the heat content in the memory is 50 % of the tripping level.
The memory function secures adequate protection, even in case of
repeated periods of unbalanced loading which eventually results in exces-
sive heating of the machine, if it is not tripped.
For further details, see Buyers Guide
.
Fig. 14 Negative phase-sequence relay RARIB
<
0.1s alt.
6s
6
8
9
10
11
t
I
0-50%
Instrument
Alarm
Start
Blocking
Tripping
1
2 3
4
5
I
R
I
S
I
T
RXTBIC 4
RXTUG 2H
RXKEB2H
RXIEK 2H
Generator Protection
ABB Network Partner AB 1MRK 502 003-AEN
Page 27
11Loss-of-excitation protection
A complete loss-of-excitation may occur as a result of:
unintentional opening of the field breaker
an open circuit or a short circuit of the main field
a fault in the automatic voltage regulator (AVR), with the result that
the field current is reduced to zero
When a generator with sufficient active load looses the field current, it
goes out of synchronism and starts to run asynchronously at a speed
higher than the system, absorbing reactive power (var) for its excitation
from the system.
The maximum active power that can be generated without loss of syn-
chronism when the generator looses its excitation depends on the differ-
ence between the direct axis and quadrature axis synchronous reactances.
For generators with salient poles, the difference is normally sufficiently
large to keep the machine running synchronously, even with an active
load of 15-25 % of rated load.
For turbo-generators with cylindrical rotor, the direct and quadrature axis
reactances are practically equal, and the machine falls out of synchronism
even with a very small active load. The slip speed increases with the
active load.
The stator end regions and parts of the rotor will be overheated, if the
machine is permitted to run for a long time at high slip speeds. The maxi-
mum permitted hot spot temperature is, for most turbo qenerators,
obtained by running the machine continously unexcited with an active
load of 20 - 35 %.
The generator terminal voltage varies periodically due to the large varia-
tion in the reactive current taken from the network. The low voltage inter-
vals could make the generator auxiliary induction motors stall, which
would lead to a complete shutdown of a thermal power station.
Reduced excitation, causing excessive heating at the end region of the sta-
tor core, may be obtained during normal system condition, when there is a
continous tendency towards an increasing system voltage (dropping of
reactive loads). In that case, the normal automatic voltage regulator
(AVR) action will reduce the field excitation.
The normal working characteristic of a typical turbogenerator is shown in
Fig 15. The curve A-B-C-D represents the capability limit, beyond which
the machine is not normally allowed to work. The apparent power vector
S represents rated power at rated power factor (PF = 0,8).
If the system voltage should start to increase steadily, the field excitation
would be reduced correspondingly by the normal operation of the AVR.
The point of vector S then moves along the vertical line BH. Continous
operation below the line DC causes severe local heating of the stator end
structure owing to an end leakage flux, which enters and leaves the stator
ABB Network Partner AB
Generator Protection 1MRK 502 003-AEN
Page 28
core perpendicular to the lamnations. In exceptional cases, this may cause
blue-ing of iron parts of the end structure, or charring of the armature
winding insulation.
Fig. 15 Typical capability curves for round rotor turbo-generator
The minimum excitation required to ensure synchronism is termed theo-
retcal stability limit. A safety margin is normally added to get a practical
stability limit.
When an automatic voltage regulator (AVR) with fast response and no
dead band is in service, the safe limit may approach the theoretical value.
For medium size and large size generators the automatic voltage regulator
(AVR) normally has a control function, which prevents it from lowering
the excitation current beyond the safe limit (negative var limiter).
11.1Loss-of-excitation
relay RAGPK
The function of the RAGPK loss-of-excitation relay is explained with ref-
erence to Fig. 16.
The relay RXPDK comprises a directional current stage (I), with charac-
teristic angle settable -120 to +120 and a nondirectional current stage
(I>).
0.8
0.6
-0.3
-0.5
0.2 0.4 0.8 0.6 1
37
o
R
a
t
e
d
M
V
A
p
.
f
.
0
.
8
l
a
g
18
o
E
D
p.u.
-MVAr
H
C
F
p.u. MW
B
A
p.u.
+MVAr
F
X
e
=0
X
e
=0.2
R
a
te
d
M
V
A
p
.f
. 0
.9
5
le
a
d
AB: Field current limit
BC: Stator current limit
CD: End region heating limit of stator,
due to leakage flux
EF: Steady-state limit without AVR
Xe: External impedance to infinite system
S
Generator Protection
ABB Network Partner AB 1MRK 502 003-AEN
Page 29
The dircetional current operate characteristic of RXPDK is normally set
to coincide as close as possible with the thermal capability curve for the
underexcited generator. For generators with negative var limiter, RXPDK
is set to give back-up for the limiter. The current operate characteristic
can, alternatively, be set to coincide as close as possible to the stability
limiting curve for the generator, when run with constant field current (the
AVR out of service).
The dircetional current stage is programmable for five inverse time char-
acteristics or definite time. A typical setting is 2 s definite time.
A potential-free contact on RXPDK is used to provide a signal when the
generator is run outside its thermal capability (or stability) range.
The RAGPK loss-of-excitation relay also comprises an undervoltage relay
RXEDK 2H. Tripping is obtained when the directional current stage oper-
ates simultaneously with the undervoltage or the overcurrent function (or
both). The undervoltage relay is normally set to 90 % of rated generator
terminal voltage and the overcurrent stage I> is normally set to 110-115 %
of rated generator load current.
For further details, see Buyers Guide.
Fig. 16 The RAGPK relay
0.8
0.6
-0.2
-0.4
0.2 0.4 0.8 0.6 1
D H
C
p.u. MW
B
A
p.u.
+MVAr
1.4 1.2
-0.6
-0.8
-0.4
-0.2
0
Operating area for RXPDK
P
Q
U<
I>
Tripping
Loss-of-
exitation
Alarm
Under-
exitation
RXPDK relay setting for
a typical turbo-generator
Basic tripping circuit of RAGPK
I
I
+
16A
17A 116 117
118
226 227
228
117 118
116
121 211
Tripping
relay 16B
17B
101
119
228 227
1
8
A
1
A
2
B
2
A
1
0
1
+ +
UL
107
Generator Protection
ABB Network Partner AB 1MRK 502 003-AEN
Page 39
Fig. 22 Reverse power relay for generator with V-connected VTs
17Protection against inadvertent energization (dead machine protection)
Despite the existence of interlockng schemes, a number of generators
have been inadvertently energized while at standstill or on turning gear. In
some cases, severe damage has been caused to the machine and even dam-
age beyond repair has been reported.
Three-phase energization of a generator which is at standstill or on turning
gear causes it to behave and accelerate similarly to an induction motor.
The machine, at this point, essentially represents the subtransient reac-
tance to the system and it can be expected to draw from one to four per
unit current, depending on the equivalent system impedance. Machine ter-
minal voltage can range from 20 % to 70 % of rated voltage, again,
depending on the system equivalent impedance. Higher quantities of
machine current and voltage (3 to 4 per unit current and 50 % to 70 %
rated voltage) can be expected if the generator is connected to a strong
system. Lower current and voltage values (1 to 2 per unit current and 20
% to 40 % rated voltage) are representative of weaker svstems.
Since a generator behaves similarly to an induction motor, high currents
will develop in the rotor during the period it is accelerating. Although the
rotor may be thermally damaged from excessive high currents, the time to
damage will be on the order of a few seconds. Of more critical concern,
however, is the bearing, which can be damaged in a fraction of a second
due to low oil pressure. Therefore, it is essential that high speed clearing
be provided.
The conventional generator protective relays do not secure fast tripping in
case of inadvertent energization. For the offset mho type of loss-of-excita-
tion relay, operation is marginal when setting and relay tolerances are con-
sidered, and the operate time would, in any case, be in the order of
hundreds of milliseconds. The back-up impedance relay and the reverse
power relay would operate with a typical time delay of 1-2 or 10-20 s
respectively.
G
(R)
(S)
(T)
L1
L2
L3
3A
4A
3B
4B
9B
10B
9A
10A
101
U
I
I
U
U
U
R
,I
R
U
T
U
S
U
1
ABB Network Partner AB
Generator Protection 1MRK 502 003-AEN
Page 40
For big and important machines, fast protection against inadvertent ener-
gization should, therefore, be included in the protective scheme.
17.1Dead machine
protective relay
RAGUA
The three-phase, static, high speed relay type RAGUA is shown in Fig.
23. The three overcurrent units RXIB 2 with operate time about 4 ms initi-
ate instantaneous tripping, if the generator terminal voltage is below set
operate value of the two undervoltage units RXEG 2. The timer, pos 143,
prevents blocking of the instantaneous function by the transient voltage
pulse, which will appear on the machine terminals when the breaker is
inadvertently closed. The timer, pos. 343, is activated when the generator
is in service and the set time delay prevents faulty operation of the relay
on nearby faults. The RXSF 1 relay, pos. 331, operates if the voltage to
one of the undervoltage units, RXEG 2, is lost.
For further details, see Buyers Guide.
Fig. 23 Dead machine protective relay RAGUA. Simplified diagram
G
+
EL
U
>
<
U
>
<
I >
I >
I >
+
R R
I
R
I
S
I
T
Trip
Fuse fail
331
143
343
Generator Protection
ABB Network Partner AB 1MRK 502 003-AEN
Page 41
18Special relays for pumped-storage generator/motors
For the high power reversible generator-motors, the so-called synchro-
nous starting method is normally used when starting up the machine for
pumping service. The machine is started up with the aid of a generator or
a static convertor. In both cases, a reduced voltage is applied to the
machine at low frequency and it typically takes 1-2 minutes to bring the
machine up to rated speed. The saturation voltage of current transformers
and, hence, the overcurrent figure (ALF), decreases with the frequency.
Static relay with input transformers have a limited low frequency
response. It is ABBs practice to include special stator ground-fault and
short-circuit protective relays to cover electrical faults during the start-
ing-up period.
ABB Network Partner AB
Generator Protection 1MRK 502 003-AEN
Page 42
18.1Sensitive generator
differential relay
The operate characteristic of the three-phase sensitive generator differen-
tial relay is shown in Fig. 24. The relay is connected in parallel with the
RADHA or RADSG differential relay. With the extremely low setting, the
relay is not stable in case of external faults and saturated current trans-
formers and it is, therefore, blocked, when the machine comes up to 80 -
90 % of rated speed ( and frequency ). At this frequency, the RADHA and
the RADSG generator differential relays are fully operative.
The voltage measuring elements comprise current relays type RXIK 1
with a special RC-filter on the input terminals.
Fig. 24 Operate characteristic of the sensitive differential relay
18.2Low-frequency
overcurrent relay
The operate characteristic of a three-phase overcurrent relay with current
elements type RXIK 1 is shown in Fig. 25. Different frequency/current
characteristics are available.
Fig. 25 Operate characteristic of low-frequency current relay
30
20
10
U
(V)
10 20 30 40 50 60 f(Hz)
Highest setting
Lowest setting
3
2
1
I
(A)
10 20 30 40 50 60 f(Hz)
Highest setting
Lowest setting
4
Generator Protection
ABB Network Partner AB 1MRK 502 003-AEN
Page 43
18.3Sensitive stator
earth-fault relay
A single-phase, overvoltage relay with operate characteristic acc. to Fig.
24 is used to provide stator earth-fault protection during start-up. The
built-in timer type RXKL 1 has setting range from 20 ms to 99 h.
The relay is connected in parallel with the 95 % stator earth-fault relay.
ABB Network Partner AB
Generator Protection 1MRK 502 003-AEN
Page 44
19Protective schemes for generators
The number and types of relays to be included in a generator protective
scheme depends on the size and the importance of the machine and also
the system layout. Hence, tables 1 and 2 below should only be regarded as
general recommendations.
1 only necessary for steam and diesel drives
2 only necessary for thyristor excitation from generator terminals
3 only necessary for pump operation
4 only necessary when several bars of the same phase in the same slot
5 not necessary with Pelton turbines
6 overcurrent should not be used with self supported static excitation
system
7 when unbalanced load is expected
8 common for hydro generators
Table 2: Proposed protection equipment for different types of generators with different rating
Generator size
Protection
I
0-4 MVA
II
4-15 MVA
III
15-50 MVA
IV
50-200 MVA
V
Large turbo-
alternators
Rotor overload X
Rotor earth fault X X X X X
Interturn fault X
4
X
4
X
4
Differential generator X X X X
Differential block (transformer) X X X X
Underfrequency X
3
X
3
X
3
Overvoltage X X X X X
Stator earth fault X X X X X
Loss of excitation X X X X
Pole-slip (out of step) X X
Reverse power X
1
X
5
X
5
X
5
X
Under impedance X
2
X X X
Unbalance (I
2
current) X
7
X
7
X X
Overcurrent (definite time) X
6
X
6
Stator overload X
Overcurrent / Undervoltage X
6
X
6
Dead machine X X X
Shaft current X
8
X
Generator Protection
ABB Network Partner AB 1MRK 502 003-AEN
Page 45
Table 3: Example on relay functions divided into two function groups
Auxiliary transformer(s)
The auxiliary transformer is usually included in the overall block-differ-
ential protective zone. In addition it is provided with a three-phase two-
step time-overcurrent relay e.g. type RAIDK, which serves as back-up
short-circuit protection.
The transformer for exitation power supply is also provided with a three-
phase two-step time-overcurrent relay e.g. type RAIDK for short circuit
protection.
Type of fault ANSI Protection function System
Generator stator A B
Short circuit 87G Generator differential X
21 Minimum impedance or alternatively X
51/27 Overcurrent/undervoltage for thyristor
magnetisation
X
51 Overcurrent X
Dissymmetry 46 Negative sequence overcurrent X
Stator overload 49 Thermal overload X
Stator earth fault 59 95% stator earth fault X X
Loss of excitation 40 Reactive current and phase angle X
Motoring 32 Reverse power
Redundant protection used for large
generators
X
X
X
Overspeed 81 Max. frequency X
Turbine blade fatique 81 Min. frequency X
Interturn fault 59 or 51N X (X)
Overvoltage 59 Overvoltage X
Over magnetization 24 V/Hz X
Low voltage 27 Undervoltage X
Inadvertent breaker closing
(Dead-machine protection)
50/27 Overcurrent with low voltage X
Shaft current - Overcurrent, fixed time X
Generator rotor
Rotor overload 49 Thermal overload X
Rotor earth fault 64R Injected AC
Injected DC
X
X
Step-up (Block) transformer
Short circuit/earth fault 87T Differential protection X
Overcurrent 50/51 Time overcurrent with instantaneous
function
X
Breaker failure protection 50BFR X
Earth fault differential prot. 87D X
Over magnetization prot. 24 V/Hz X